Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695

Simulation Timestamp: 2023-10-16 08:30:09


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 172.46 337.39 337.39
Net Site Energy 172.46 337.39 337.39
Total Source Energy 520.38 1018.05 1018.05
Net Source Energy 520.38 1018.05 1018.05


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 16.40 12.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 160.07 12.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 16.40 12.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 11.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 23.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 24.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 16.40 12.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 11.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 23.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 24.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 148.46 24.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 313.16 24.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 148.46 24.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 313.16 24.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 160.075 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 160.075 100.00
     
Total On-Site and Utility Electric Sources 160.075 100.00
Total Electricity End Uses 160.075 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 30.67
Time Setpoint Not Met During Occupied Cooling 13.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2227.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
RunPeriod RUNPERIOD 1
Weather File Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Latitude [deg] 39.72
Longitude [deg] -104.8
Elevation [m] 1726.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.0938 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.0938 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.0938 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.0938 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.0938 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.0938 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.0938 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.0938 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.0938 9.29 6.7800  
Conditioned Total 511.16             6.0938 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.0938 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 20-MAR-07:30 21-DEC-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 9264.13 32064.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1937.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1934.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2630.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 19092.54 32064.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 9264.13 32064.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1937.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1934.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2630.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 51.92 13.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 35.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 82.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 75.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 77.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 506.96 13.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 101.58 26.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 70.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 161.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 146.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 151.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 991.78 26.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 101.58 26.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 70.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 161.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 146.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 151.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 991.78 26.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.333977
PERIMETER_ZN_1 DIRECT AIR 0.374555
PERIMETER_ZN_2 DIRECT AIR 0.299628
PERIMETER_ZN_3 DIRECT AIR 0.332587
PERIMETER_ZN_4 DIRECT AIR 0.386757
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.333977 0.333977 0.333977 0.333977 0.333977 0.333977 1.00 1.00 0.333977
PSZ-AC:2 0.374555 0.374555 0.374555 0.374555 0.374555 0.374555 1.00 1.00 0.374555
PSZ-AC:3 0.299628 0.299628 0.299628 0.299628 0.299628 0.299628 1.00 1.00 0.299628
PSZ-AC:4 0.332587 0.332587 0.332587 0.332587 0.332587 0.332587 1.00 1.00 0.332587
PSZ-AC:5 0.386757 0.386757 0.386757 0.386757 0.386757 0.386757 1.00 1.000000 0.386757
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.333977 0.064622
PSZ-AC:2_OA_CONTROLLER 0.374555 0.048988
PSZ-AC:3_OA_CONTROLLER 0.299628 0.029060
PSZ-AC:4_OA_CONTROLLER 0.332587 0.048988
PSZ-AC:5_OA_CONTROLLER 0.386757 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.333977 5528.51 0.800655
PSZ-AC:2 HP COOLING COIL 0.374555 6200.22 0.800655
PSZ-AC:3 HP COOLING COIL 0.299628 4959.91 0.800655
PSZ-AC:4 HP COOLING COIL 0.332587 5505.49 0.800655
PSZ-AC:5 HP COOLING COIL 0.386757 6402.21 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.333977 0.333977 0.333977 0.333977 5528.51 5528.51 40.00 3921.24 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.374555 0.374555 0.374555 0.374555 6200.22 6200.22 40.00 6706.94 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.299628 0.299628 0.299628 0.299628 4959.91 4959.91 40.00 4201.36 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.332587 0.332587 0.332587 0.332587 5505.49 5505.49 40.00 6620.95 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.386757 0.386757 0.386757 0.386757 6402.21 6402.21 40.00 4201.36 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.333977
PSZ-AC:2 FAN 0.374555
PSZ-AC:3 FAN 0.299628
PSZ-AC:4 FAN 0.332587
PSZ-AC:5 FAN 0.386757
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.333977 5528.51
PSZ-AC:2 HEATING COIL 0.374555 6200.22
PSZ-AC:3 HEATING COIL 0.299628 4959.91
PSZ-AC:4 HEATING COIL 0.332587 5505.49
PSZ-AC:5 HEATING COIL 0.386757 6402.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 3921.24
PSZ-AC:2_SUPPHEATCOIL 6706.94
PSZ-AC:3_SUPPHEATCOIL 4201.36
PSZ-AC:4_SUPPHEATCOIL 6620.95
PSZ-AC:5_SUPPHEATCOIL 4201.36
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 7.10 3.00 -1.00 0.80 -0.20 4.80 6.10 13.70 22.20 22.70 21.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 39.72 -104.75 -7.00 1726.00 82237 0.9774


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.95 23.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 911.976 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 911.976
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.8908E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.1096E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.0824E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.2847E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2468E-003
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.4069E-003
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 5.9281E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 6.6223E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1631E-002
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.1523E-002
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1875E-002
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.2538E-002
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0543E-002
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.3692E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.0557E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 2.7398E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 9.1948E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 9.7709E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 9.2532E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.0466E-002
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.4530E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.5473E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.1973E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.5312E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.8789E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.0709E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.0716E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.2472E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2368E-003
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3789E-003
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 5.8800E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 6.5152E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.8064E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.8270E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.0089E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.0268E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1785E-003
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1930E-003
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 5.5492E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 5.6218E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.8011E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.8051E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.0044E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.0078E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1747E-003
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1774E-003
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 5.5277E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 5.5418E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.8082E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.3442E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.0356E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.5630E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.9165E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.2634E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 9.3882E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.0544E-003
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.2789E-003
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.4334E-003
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.1619E-003
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.2752E-003
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.1009E-003
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.1524E-003
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.3017E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.9405E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.2763E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 4.0950E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.1917E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.3438E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.6642E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.9313E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.5442E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.9083E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2966E-002
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 6.2328E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.3360E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.8510E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.1255E-002
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.5822E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.4209E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.1234E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.5249E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.8936E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.4747E-003
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.8552E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.2151E-003
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.4251E-003
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.3481E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0047E-003
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.7007E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.9837E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 5.3659E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.3543E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.4541E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.0974E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 5.8676E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.4747E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.1774E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.5586E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.2569E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.6901E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.0786E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.8311E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.8302E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.4329E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.7226E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 4.1264E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.4440E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.1085E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.2721E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.1015E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.5521E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.8496E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.8668E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 8.3747E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.5015E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.6633E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.5810E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.3435E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.9642E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.6893E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.1264E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 6.3148E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.9048E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.0542E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.0662E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.1721E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.5611E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.6419E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.0713E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.1092E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.8599E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.8903E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.0307E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.0526E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.5368E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.5520E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.5719E-003
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.9522E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.5327E-003
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.9279E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.2401E-003
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.4520E-003
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.3633E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0058E-003
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.3408E-002
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.3426E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.3908E-002
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.9963E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1413E-002
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.6103E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.3993E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.0833E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 5.2907E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.0666E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.2239E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.3418E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.7359E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.9608E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.5408E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.8748E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.3049E-003
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.4575E-003
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1931E-003
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.3053E-003
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1201E-003
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.1724E-003
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 9.3152E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.9504E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3078.97023 3694.76428 0.27831 0.33398 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 32.61733 5.47329E-003 149.65740 8.05449 6.46220E-002 0.00000
2 CORE_ZN Heating 1222.16768 1466.60121 6.49131E-002 7.78957E-002 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -17.90000 9.55238E-004 149.65740 8.05449 6.46220E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3453.01588 4143.61906 0.31213 0.37456 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.90000 5.47527E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 4084.49888 4901.39865 0.21693 0.26032 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -17.90000 9.55238E-004 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2762.38378 3314.86054 0.24969 0.29963 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 27.85667 5.46603E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2611.32340 3133.58808 0.13869 0.16643 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -17.90000 9.55238E-004 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3066.17096 3679.40515 0.27716 0.33259 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 33.16000 5.47412E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 4011.78519 4814.14222 0.21307 0.25568 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -17.90000 9.55238E-004 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3565.65067 4278.78081 0.32230 0.38676 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 30.59467 5.47019E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2611.32340 3133.58808 0.13869 0.16643 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -17.90000 9.55238E-004 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4191.60 0.33398 0.33398 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 3921.24 7.78957E-002 7.78957E-002 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 PSZ-AC:2 Cooling Sensible 4561.21 0.37456 0.37456 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 6706.94 0.26032 0.26032 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3376.83 0.29963 0.29963 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 4201.36 0.16643 0.16643 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 4068.56 0.33259 0.33259 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 6620.95 0.25568 0.25568 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4403.99 0.38676 0.38676 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 4201.36 0.16643 0.16643 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.33398
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.37456
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29963
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.33259
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.38676
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.33398
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.33398
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.33398
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.33398
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.33398
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.33398
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.37456
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.37456
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.37456
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.37456
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.37456
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.37456
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29963
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29963
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29963
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.29963
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29963
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.29963
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.33259
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.33259
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.33259
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.33259
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.33259
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.33259
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.38676
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.38676
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.38676
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.38676
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.38676
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.38676
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.33398
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.37456
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.29963
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.33259
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.38676
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.33398
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46220E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.33398
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5528.50522
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.33398
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.33398
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.33398
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.33398
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5528.50522
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5528.50522
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3921.23888
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.33398
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.33398
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5528.50522
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 3921.23888
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.37456
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.37456
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6200.21697
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.37456
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.37456
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.37456
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.37456
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6200.21697
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6200.21697
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 6706.93513
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.37456
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.37456
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6200.21697
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 6706.93513
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29963
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29963
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4959.90514
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29963
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29963
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29963
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29963
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4959.90514
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4959.90514
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4201.36140
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.29963
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29963
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4959.90514
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 4201.36140
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.33259
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.33259
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5505.48850
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.33259
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.33259
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.33259
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.33259
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5505.48850
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5505.48850
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 6620.94964
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.33259
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.33259
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5505.48850
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 6620.94964
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.38676
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.38676
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6402.20589
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.38676
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.38676
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.38676
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.38676
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6402.20589
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6402.20589
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4201.36140
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.38676
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.38676
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6402.20589
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 4201.36140
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5266.8 3.43 11.69 12.22 11.56 11.36
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 5906.7 3.43 11.69 12.22 11.56 11.36
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4725.1 3.43 11.69 12.22 11.56 11.36
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 5244.8 3.43 11.69 12.22 11.56 11.36
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 6099.1 3.43 11.69 12.22 11.56 11.36


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5793.5 3226.6 7.33 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6497.4 3618.7 7.35 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5197.6 2894.8 7.32 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 5769.4 3213.2 7.32 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 6709.0 3736.5 7.32 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.4508454968E-002 8.7441237162E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 8.4449760709E-002 7.0973706468E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.1898432099 0.2576860840 Pass Pass 1.9567674485 12.5479281144 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.3483094309 0.3473691757 Pass Pass 0.4207170723 0.6873522912 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.2284468453 0.2564137212 Pass Pass 0.9418243145 2.1204242203 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.4352035624 0.5164233466 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1078.63 39.87 0.00 105.25 0.235659E+182 0.235659E+182



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB -17.90 0.00 -17.90 Wetbulb [C] 2.50 180.00
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 33.90 14.80 15.00 Wetbulb [C] 3.60 30.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 11.00 10      
Feb 15.00 16      
Mar 88.00 32      
Apr 159.00 54      
May 30.00 24      
Jun 11.00 4      
Jul 167.00 26      
Aug 33.00 24      
Sep 8.00 8      
Oct 13.00 10      
Nov 12.00 22      
Dec 11.00 18      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.903 1.045 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.903 1.045 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.903 1.045 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.903 1.045 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.118 0.122 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.118 0.122 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.3628_SHGC_SOUTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.3628_SHGC_SOUTH_0.38   3.91 0.00 0.00 3.91 3.91 2.061 0.381 0.381             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.3628_SHGC_EAST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.3628_SHGC_EAST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.3628_SHGC_EAST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.3628_SHGC_EAST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.3628_SHGC_NORTH_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.3628_SHGC_WEST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.3628_SHGC_WEST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.3628_SHGC_WEST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.3628_SHGC_WEST_0.38   2.79 0.00 0.00 2.79 2.79 2.061 0.381 0.381             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.061 0.381 0.381                      
North Total or Average             16.72 2.061 0.381 0.381                      
Non-North Total or Average             42.93 2.061 0.381 0.381                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.98 0.97 0.97 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.49 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.42 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.89 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.89 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.89 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.89 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.0938 149.66 911.98 LightsWired LTG_SCH_OFFICE 50.53 168.00 49.65 0.0000 Y 8.50
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 41.25 0.0000 Y 5.35
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 42.69 0.0000 Y 3.29
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 43.81 0.0000 Y 5.69
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 42.66 0.0000 Y 3.28
Interior Lighting Total       6.0938 511.16 3114.87               26.11


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   42.26 42.26 0.53
EXTERIOR_LIGHTS_B 202.25 AstronomicalClock -   83.67 62.97 2.39
EXTERIOR_LIGHTS_C 780.12 AstronomicalClock -   83.67 46.88 6.86
Exterior Lighting Total 1049.10           9.78



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5528.51 4426.43 1102.08 0.80 4.32    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6200.22 4964.24 1235.98 0.80 4.32    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4959.91 3971.17 988.73 0.80 4.32    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5505.49 4408.00 1097.49 0.80 4.32    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6402.21 5125.96 1276.25 0.80 4.32    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5266.8 3.43 11.69 12.22 11.56 11.36
PSZ-AC:2 HP COOLING COIL   5906.7 3.43 11.69 12.22 11.56 11.36
PSZ-AC:3 HP COOLING COIL   4725.1 3.43 11.69 12.22 11.56 11.36
PSZ-AC:4 HP COOLING COIL   5244.8 3.43 11.69 12.22 11.56 11.36
PSZ-AC:5 HP COOLING COIL   6099.1 3.43 11.69 12.22 11.56 11.36
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5793.5 3226.6 7.33 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6497.4 3618.7 7.35 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5197.6 2894.8 7.32 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 5769.4 3213.2 7.32 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 6709.0 3736.5 7.32 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5528.51 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   3921.24 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6200.22 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   6706.94 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4959.91 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   4201.36 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   5505.49 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   6620.95 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   6402.21 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   4201.36 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.33 374.09 1120.11 1.00 1.82 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.37 419.54 1120.11 1.00 1.75 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.30 335.62 1120.11 1.00 1.90 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.33 372.53 1120.11 1.00 1.83 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.39 433.21 1120.11 1.00 1.73 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3078.97 3694.76 24.69 0.278 0.334 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00908 32.62 0.00547 0.065 0.00
PERIMETER_ZN_1 3453.02 4143.62 36.52 0.312 0.375 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 23.89 23.89 0.00880 33.90 0.00548 0.049 0.00
PERIMETER_ZN_2 2762.38 3314.86 49.25 0.250 0.300 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 23.89 23.89 0.00871 27.86 0.00547 0.029 0.00
PERIMETER_ZN_3 3066.17 3679.41 32.43 0.277 0.333 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00884 33.16 0.00547 0.049 0.00
PERIMETER_ZN_4 3565.65 4278.78 63.58 0.322 0.387 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 23.89 23.89 0.00867 30.59 0.00547 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1222.17 1466.60 9.80 0.065 0.078 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 -17.90 0.00096 0.065 0.00
PERIMETER_ZN_1 4084.50 4901.40 43.20 0.217 0.260 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 -17.90 0.00096 0.049 0.00
PERIMETER_ZN_2 2611.32 3133.59 46.56 0.139 0.166 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00776 -17.90 0.00096 0.029 0.00
PERIMETER_ZN_3 4011.79 4814.14 42.43 0.213 0.256 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00776 -17.90 0.00096 0.049 0.00
PERIMETER_ZN_4 2611.32 3133.59 46.56 0.139 0.166 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00776 -17.90 0.00096 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.33 0.33 0.08 0.08 0.3340 0.3340 0.3340 1.0000 1.0000
PSZ-AC:2 0.37 0.37 0.26 0.26 0.3746 0.3746 0.3746 1.0000 1.0000
PSZ-AC:3 0.30 0.30 0.17 0.17 0.2996 0.2996 0.2996 1.0000 1.0000
PSZ-AC:4 0.33 0.33 0.26 0.26 0.3326 0.3326 0.3326 1.0000 1.0000
PSZ-AC:5 0.39 0.39 0.17 0.17 0.3868 0.3868 0.3868 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5528.505 4426.427 0.333977 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5033.19 5033.19 0.333977 26.70 15.05 0.00838342 12.80 10.10 0.00838342 32.62 0.00547329 14.65 19.3493 23.89 0.00908721 39.9350 3053.99 0.00 5527.56 3991.67
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5528.505 5528.505 0.333977 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5528.51 5528.51 0.333977 13.56 8.71 0.00663689 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 19.3493 21.11 0.00800000 41.6969 1222.17 0.00 5535.77 5535.77
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 3921.239 3921.239 -999.0 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3921.24 3921.24 0.333977 13.56 8.71 0.00663689 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 19.3493 21.11 0.00800000 41.6969 1222.17 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6200.217 4964.236 0.374555 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 5550.50 5550.50 0.374555 26.32 14.91 0.00836390 12.80 10.09 0.00836390 33.90 0.00547527 15.07 13.0789 23.89 0.00879855 38.6835 3453.02 0.00 6199.15 4476.66
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6200.217 6200.217 0.374555 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6200.22 6200.22 0.374555 16.01 9.92 0.00687539 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 13.0789 21.11 0.00776619 40.4952 4084.50 0.00 6208.36 6208.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 6706.935 6706.935 -999.0 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6706.94 6706.94 0.374555 16.01 9.92 0.00687539 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 13.0789 21.11 0.00776619 40.4952 4084.50 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4959.905 3971.174 0.299628 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 4648.23 4648.23 0.299628 25.40 14.63 0.00839802 12.80 10.12 0.00839802 27.86 0.00546603 13.03 9.6987 23.89 0.00871352 38.3141 2760.86 0.00 4959.05 3581.13
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4959.905 4959.905 0.299628 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4959.91 4959.91 0.299628 17.33 10.64 0.00709689 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 9.6987 21.11 0.00775653 40.4457 2611.32 0.00 4966.42 4966.42
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 4201.361 4201.361 -999.0 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4201.36 4201.36 0.299628 17.33 10.64 0.00709689 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 9.6987 21.11 0.00775653 40.4457 2611.32 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5505.489 4407.998 0.332587 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 4966.58 4966.58 0.332587 26.38 14.91 0.00834018 12.80 10.06 0.00834018 33.16 0.00547412 14.83 14.7293 23.89 0.00883620 38.8464 3059.76 0.00 5504.54 3975.05
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5505.489 5505.489 0.332587 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5505.49 5505.49 0.332587 15.36 9.55 0.00675949 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 14.7293 21.11 0.00776209 40.4742 4011.79 0.00 5512.72 5512.72
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 6620.950 6620.950 -999.0 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6620.95 6620.95 0.332587 15.36 9.55 0.00675949 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 14.7293 21.11 0.00776209 40.4742 4011.79 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6402.206 5125.960 0.386757 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 5882.62 5882.62 0.386757 25.52 14.69 0.00842619 12.80 10.14 0.00842619 30.59 0.00547019 13.98 7.5138 23.89 0.00866635 38.1095 3565.65 0.00 6401.11 4622.50
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6402.206 6402.206 0.386757 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6402.21 6402.21 0.386757 18.18 11.10 0.00724550 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 7.5138 21.11 0.00775653 40.4457 2611.32 0.00 6410.62 6410.62
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 4201.361 4201.361 -999.0 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4201.36 4201.36 0.386757 18.18 11.10 0.00724550 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 7.5138 21.11 0.00775653 40.4457 2611.32 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5528.505 4426.427 0.333977 -999.0 -999.000 -999.0000 1.11957 1.00000 1020.4244 1004.8586 0.9774 PSZ-AC:1 FAN Fan:OnOff 0.333977 0.32644168   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5033.19 5033.19 0.9104 0.32644168 0.333977 26.70 15.05 0.00838342 48213.0 12.80 10.10 0.00838342 34027.9 -999.0 -999.00 -999.00 -999.00 374.090 4659.10 32.62 0.00547329 14.65 0.06462205 19.3493 23.89 0.00908160 23.89 0.00908721 39.9350 3053.99 0.00 5527.56 3991.67 0.31354970 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926411 37693.4
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5528.505 5528.505 0.333977 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:1 FAN Fan:OnOff 0.333977 0.32644168   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5528.51 5528.51 1.0000 0.32644168 0.333977 13.56 8.71 0.00663689 30393.3 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5528.51 -17.90 0.00095524 -17.90 0.06462205 19.3493 21.11 0.00800000 21.11 0.00800000 41.6969 1222.17 0.00 5535.77 5535.77 0.32067336 21.11 15.56 0.00875166 43444.1 38.02 21.14 0.00875166 60707.1
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3921.239 3921.239 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:1 FAN Fan:OnOff 0.333977 0.32644168   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3921.24 3921.24 1.0000 0.32644168 0.333977 13.56 8.71 0.00663689 30393.3 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3921.24 -17.90 0.00095524 -17.90 0.06462205 19.3493 21.11 0.00800000 21.11 0.00800000 41.6969 1222.17 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6200.217 4964.236 0.374555 -999.0 -999.000 -999.0000 1.13040 1.00000 1020.3881 1004.8586 0.9774 PSZ-AC:2 FAN Fan:OnOff 0.374555 0.36610425   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 5550.50 5550.50 0.8952 0.36610425 0.374555 26.32 14.91 0.00836390 47775.9 12.80 10.09 0.00836390 33978.6 -999.0 -999.00 -999.00 -999.00 419.542 5130.96 33.90 0.00547527 15.07 0.04898769 13.0789 23.89 0.00879855 23.89 0.00879855 38.6835 3453.02 0.00 6199.15 4476.66 0.35164590 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926411 37693.4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6200.217 6200.217 0.374555 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:2 FAN Fan:OnOff 0.374555 0.36610425   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6200.22 6200.22 1.0000 0.36610425 0.374555 16.01 9.92 0.00687539 33484.2 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6200.22 -17.90 0.00095524 -17.90 0.04898769 13.0789 21.11 0.00776619 21.11 0.00776619 40.4952 4084.50 0.00 6208.36 6208.36 0.35963507 21.11 15.56 0.00875166 43444.1 38.02 21.14 0.00875166 60707.1
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 6706.935 6706.935 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:2 FAN Fan:OnOff 0.374555 0.36610425   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6706.94 6706.94 1.0000 0.36610425 0.374555 16.01 9.92 0.00687539 33484.2 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6706.94 -17.90 0.00095524 -17.90 0.04898769 13.0789 21.11 0.00776619 21.11 0.00776619 40.4952 4084.50 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4959.905 3971.174 0.299628 -999.0 -999.000 -999.0000 1.26635 1.00000 1020.4515 1004.8586 0.9774 PSZ-AC:3 FAN Fan:OnOff 0.299628 0.29286755   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 4648.23 4648.23 0.9372 0.29286755 0.299628 25.40 14.63 0.00839802 46919.8 12.80 10.12 0.00839802 34064.7 -999.0 -999.00 -999.00 -999.00 335.616 4312.61 27.86 0.00546603 13.03 0.02906013 9.6987 23.89 0.00871293 23.89 0.00871352 38.3141 2760.86 0.00 4959.05 3581.13 0.28130150 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926411 37693.4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4959.905 4959.905 0.299628 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:3 FAN Fan:OnOff 0.299628 0.29286755   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4959.91 4959.91 1.0000 0.29286755 0.299628 17.33 10.64 0.00709689 35387.1 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4959.91 -17.90 0.00095524 -17.90 0.02906013 9.6987 21.11 0.00775653 21.11 0.00775653 40.4457 2611.32 0.00 4966.42 4966.42 0.28769249 21.11 15.56 0.00875166 43444.1 38.02 21.14 0.00875166 60707.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4201.361 4201.361 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:3 FAN Fan:OnOff 0.299628 0.29286755   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4201.36 4201.36 1.0000 0.29286755 0.299628 17.33 10.64 0.00709689 35387.1 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4201.36 -17.90 0.00095524 -17.90 0.02906013 9.6987 21.11 0.00775653 21.11 0.00775653 40.4457 2611.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5505.489 4407.998 0.332587 -999.0 -999.000 -999.0000 1.13459 1.00000 1020.3440 1004.8586 0.9774 PSZ-AC:4 FAN Fan:OnOff 0.332587 0.32508261   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 4966.58 4966.58 0.9021 0.32508261 0.332587 26.38 14.91 0.00834018 47773.0 12.80 10.06 0.00834018 33918.7 -999.0 -999.00 -999.00 -999.00 372.533 4594.05 33.16 0.00547412 14.83 0.04898769 14.7293 23.89 0.00883525 23.89 0.00883620 38.8464 3059.76 0.00 5504.54 3975.05 0.31224431 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926411 37693.4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5505.489 5505.489 0.332587 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:4 FAN Fan:OnOff 0.332587 0.32508261   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5505.49 5505.49 1.0000 0.32508261 0.332587 15.36 9.55 0.00675949 32535.9 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5505.49 -17.90 0.00095524 -17.90 0.04898769 14.7293 21.11 0.00776209 21.11 0.00776209 40.4742 4011.79 0.00 5512.72 5512.72 0.31933830 21.11 15.56 0.00875166 43444.1 38.02 21.14 0.00875166 60707.1
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 6620.950 6620.950 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:4 FAN Fan:OnOff 0.332587 0.32508261   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6620.95 6620.95 1.0000 0.32508261 0.332587 15.36 9.55 0.00675949 32535.9 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6620.95 -17.90 0.00095524 -17.90 0.04898769 14.7293 21.11 0.00776209 21.11 0.00776209 40.4742 4011.79 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6402.206 5125.960 0.386757 -999.0 -999.000 -999.0000 1.23044 1.00000 1020.5039 1004.8586 0.9774 PSZ-AC:5 FAN Fan:OnOff 0.386757 0.37803109   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 5882.62 5882.62 0.9188 0.37803109 0.386757 25.52 14.69 0.00842619 47113.0 12.80 10.14 0.00842619 34135.9 -999.0 -999.00 -999.00 -999.00 433.210 5449.41 30.59 0.00547019 13.98 0.02906013 7.5138 23.89 0.00866635 23.89 0.00866635 38.1095 3565.65 0.00 6401.11 4622.50 0.36310172 26.67 19.44 0.01118466 55322.4 14.21 13.42 0.00926411 37693.4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6402.206 6402.206 0.386757 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:5 FAN Fan:OnOff 0.386757 0.37803109   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6402.21 6402.21 1.0000 0.37803109 0.386757 18.18 11.10 0.00724550 36631.4 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6402.21 -17.90 0.00095524 -17.90 0.02906013 7.5138 21.11 0.00775653 21.11 0.00775653 40.4457 2611.32 0.00 6410.62 6410.62 0.37135116 21.11 15.56 0.00875166 43444.1 38.02 21.14 0.00875166 60707.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4201.361 4201.361 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PSZ-AC:5 FAN Fan:OnOff 0.386757 0.37803109   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4201.36 4201.36 1.0000 0.37803109 0.386757 18.18 11.10 0.00724550 36631.4 40.00 18.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4201.36 -17.90 0.00095524 -17.90 0.02906013 7.5138 21.11 0.00775653 21.11 0.00775653 40.4457 2611.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2138.67 2658.83 899.50
PERIMETER_ZN_1 2163.67 2770.33 1271.67
PERIMETER_ZN_2 2372.83 2358.83 1463.83
PERIMETER_ZN_3 2799.00 3019.00 2040.00
PERIMETER_ZN_4 2656.33 2927.00 1755.50
ATTIC 0.00 0.00 0.00
Facility 3417.17 3227.33 2227.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 1.33 1.33 1.33 1.33
PERIMETER_ZN_1 53.67 12.33 28.50 11.50
PERIMETER_ZN_2 75.17 0.00 3.67 0.00
PERIMETER_ZN_3 92.00 0.00 4.83 0.00
PERIMETER_ZN_4 74.17 3.00 3.33 0.17
ATTIC 0.00 0.00 0.00 0.00
Facility 222.67 16.67 30.67 13.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.394 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.393 0.416 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.368 0.062 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.393 0.050 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.394 0.057 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.046
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.021
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.021
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.156


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.55 0.00 762126.55 0.00 762126.55 1606483.19 5484.00 2016.00 1260.00 0.00
PERIMETER_ZN_1 592786.58 0.00 592786.58 762929.19 1355715.78 1217818.28 5423.53 2017.04 1319.43 139.84
PERIMETER_ZN_2 359561.67 0.00 359561.67 150025.23 509586.89 702184.69 5382.91 1513.00 1864.09 1055.71
PERIMETER_ZN_3 619593.88 0.00 619593.88 225037.84 844631.72 1217818.28 5302.47 2018.15 1439.38 356.92
PERIMETER_ZN_4 356950.62 0.00 356950.62 150025.23 506975.84 722425.48 5406.55 2016.58 1336.87 311.56
Total Facility 2691019.29 0.00 2691019.29 1288017.48 3979036.78 5466729.92 5484.00 2020.72 1988.28 1279.97


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0565 1008.00 2016.00 1260.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0397 0.0772 0.0428 1006.14 2016.00 1261.86
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0035 0.0243 0.0249 1001.72 1512.00 1014.28
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0048 0.0423 0.0428 1002.92 2016.00 1265.08
PERIMETER_ZN_4 0.0223 0.0000 0.0223 0.0032 0.0255 0.0254 1003.42 2016.00 1264.58
Total Facility 0.1675 0.0000 0.1675 0.0512 0.2187 0.1925 1008.00 2016.00 1772.17


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 728123.73 0.00 728123.73 1606483.19 7500.00 0.00 1260.00 0.00
PSZ-AC:2 566338.98 0.00 566338.98 1217818.28 7441.81 0.58 1317.61 139.39
PSZ-AC:3 343519.57 0.00 343519.57 702184.69 6898.16 1.19 1860.64 1049.53
PSZ-AC:4 591950.25 0.00 591950.25 1217818.28 7323.41 2.68 1433.91 355.65
PSZ-AC:5 341025.01 0.00 341025.01 722425.48 7423.77 0.35 1335.88 303.62


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0472 0.0000 0.0472 0.0565 3024.00 0.00 1260.00
PSZ-AC:2 0.0358 0.0000 0.0358 0.0428 3022.14 0.00 1261.86
PSZ-AC:3 0.0199 0.0000 0.0199 0.0249 2513.72 0.00 1014.28
PSZ-AC:4 0.0358 0.0000 0.0358 0.0428 3018.92 0.00 1265.08
PSZ-AC:5 0.0213 0.0000 0.0213 0.0254 3019.42 0.00 1264.58


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3418.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3577.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3637.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3587.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0617 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0468 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0278 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0468 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0277 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 524
Defaulted Fields 360
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
Electricity:Building 74.40 895.38 09-JUL-13:30 5350.97 02-JAN-16:50
Electricity:Zone:CORE_ZN 22.64 284.81 01-JAN-00:10 1566.66 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.40 895.38 09-JUL-13:30 5350.97 02-JAN-16:50
InteriorLights:Electricity 26.11 327.73 09-JUL-13:30 2025.66 02-JAN-16:50
InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.11 327.73 09-JUL-13:30 2025.66 02-JAN-16:50
LightsWired:InteriorLights:Electricity 26.11 327.73 09-JUL-13:30 2025.66 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.11 327.73 09-JUL-13:30 2025.66 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_1 16.07 191.62 01-JAN-07:50 1187.63 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.35 65.63 01-JAN-07:50 449.59 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.35 65.63 01-JAN-07:50 449.59 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_2 9.65 113.67 01-JAN-08:00 704.52 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 38.93 01-JAN-08:00 266.70 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 38.93 01-JAN-08:00 266.70 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_3 16.41 191.62 07-MAY-09:20 1187.63 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.69 65.63 07-MAY-09:20 449.59 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.69 65.63 07-MAY-09:20 449.59 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_4 9.64 113.67 01-JAN-13:50 704.52 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.28 38.93 01-JAN-13:50 266.70 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.28 38.93 01-JAN-13:50 266.70 02-JAN-16:50
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
ElectricityPurchased:Plant 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
Cogeneration:ElectricityPurchased 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
General:Cogeneration:ElectricityPurchased 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
ElectricityNet:Plant 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
Cogeneration:ElectricityNet 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
General:Cogeneration:ElectricityNet 160.07 1467.38 09-JUL-13:30 19092.54 20-MAR-07:30
ExteriorLights:Electricity 9.78 0.00 01-JAN-07:30 1049.10 01-JAN-06:10
General:ExteriorLights:Electricity 9.78 0.00 01-JAN-07:30 1049.10 01-JAN-06:10
Electricity:HVAC 51.44 0.00 01-JAN-10:00 11309.47 20-MAR-06:30
Fans:Electricity 23.71 0.00 01-JAN-00:40 1934.99 02-JAN-06:20
General:Fans:Electricity 23.71 0.00 01-JAN-00:40 1934.99 02-JAN-06:20
Cooling:Electricity 11.33 0.00 01-JAN-00:10 6175.75 26-JUN-15:10
General:Cooling:Electricity 11.33 0.00 01-JAN-00:10 6175.75 26-JUN-15:10
Heating:Electricity 16.40 0.00 01-JAN-10:00 9374.48 20-MAR-06:30
General:Heating:Electricity 16.40 0.00 01-JAN-10:00 9374.48 20-MAR-06:30
Electricity:Plant 24.45 572.00 02-JAN-06:10 2821.78 13-FEB-12:30
WaterSystems:Electricity 24.45 572.00 02-JAN-06:10 2821.78 13-FEB-12:30
Water Heater:WaterSystems:Electricity 24.45 572.00 02-JAN-06:10 2821.78 13-FEB-12:30
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-08:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 12.38 0.00 01-JAN-00:20 32064.81 21-DEC-07:10
NaturalGas:HVAC 12.38 0.00 01-JAN-00:20 32064.81 21-DEC-07:10
Heating:NaturalGas 12.38 0.00 01-JAN-00:20 32064.81 21-DEC-07:10
General:Heating:NaturalGas 12.38 0.00 01-JAN-00:20 32064.81 21-DEC-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 12-JAN-12:50
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 12-JAN-12:50
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 15-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 15-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 165.75 0.00 01-JAN-00:40 62151.87 06-FEB-07:10
EnergyTransfer:Building 76.27 0.00 01-JAN-00:40 28740.12 06-FEB-07:20
EnergyTransfer:Zone:CORE_ZN 14.92 0.00 01-JAN-00:10 5163.48 05-SEP-07:20
Heating:EnergyTransfer 30.38 0.00 01-JAN-00:40 28740.12 06-FEB-07:20
Heating:EnergyTransfer:Zone:CORE_ZN 1.02 0.00 01-JAN-00:10 4345.43 26-DEC-07:20
General:Heating:EnergyTransfer 30.38 0.00 01-JAN-00:40 28740.12 06-FEB-07:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 1.02 0.00 01-JAN-00:10 4345.43 26-DEC-07:20
Cooling:EnergyTransfer 45.88 0.00 01-JAN-00:10 19563.58 17-JUL-07:20
Cooling:EnergyTransfer:Zone:CORE_ZN 13.90 0.00 01-JAN-00:10 5163.48 05-SEP-07:20
General:Cooling:EnergyTransfer 45.88 0.00 01-JAN-00:10 19563.58 17-JUL-07:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 13.90 0.00 01-JAN-00:10 5163.48 05-SEP-07:20
EnergyTransfer:Zone:PERIMETER_ZN_1 19.83 0.00 01-JAN-00:10 8151.11 06-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 7.45 0.00 01-JAN-00:10 8151.11 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 7.45 0.00 01-JAN-00:10 8151.11 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 12.39 0.00 01-JAN-00:10 5496.81 05-SEP-12:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 12.39 0.00 01-JAN-00:10 5496.81 05-SEP-12:30
EnergyTransfer:Zone:PERIMETER_ZN_2 12.08 0.00 01-JAN-00:40 4798.05 06-FEB-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 5.15 0.00 01-JAN-00:40 4798.05 06-FEB-07:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 5.15 0.00 01-JAN-00:40 4798.05 06-FEB-07:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 6.93 0.00 01-JAN-00:10 4185.27 17-JUL-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 6.93 0.00 01-JAN-00:10 4185.27 17-JUL-07:20
EnergyTransfer:Zone:PERIMETER_ZN_3 17.95 0.00 01-JAN-00:40 6829.87 06-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 11.03 0.00 01-JAN-00:40 6829.87 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 11.03 0.00 01-JAN-00:40 6829.87 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 6.93 0.00 01-JAN-00:10 4084.61 17-JUL-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 6.93 0.00 01-JAN-00:10 4084.61 17-JUL-07:20
EnergyTransfer:Zone:PERIMETER_ZN_4 11.48 0.00 01-JAN-00:40 4808.48 06-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 5.73 0.00 01-JAN-00:40 4808.48 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 5.73 0.00 01-JAN-00:40 4808.48 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 5.75 0.00 01-JAN-00:10 3710.38 16-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 5.75 0.00 01-JAN-00:10 3710.38 16-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
EnergyTransfer:HVAC 89.49 0.00 01-JAN-00:40 33414.19 06-FEB-07:10
CoolingCoils:EnergyTransfer 51.23 0.00 01-JAN-00:10 22578.41 17-JUL-14:20
HeatingCoils:EnergyTransfer 38.26 0.00 01-JAN-00:40 33414.19 06-FEB-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 14-FEB-07:10 102.15 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 1.023 -13.899 0.000 0.000 5.291 8.499 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -15.054
PERIMETER_ZN_1 0.000 0.000 7.447 -12.385 0.000 0.000 4.014 5.353 10.719 28.292 0.000 0.470 0.000 0.000 -10.632 0.000 -9.054 -24.225
PERIMETER_ZN_2 0.000 0.000 5.154 -6.927 0.000 0.000 1.766 3.286 6.359 11.471 0.000 0.027 0.000 0.000 -5.490 0.000 -1.859 -13.787
PERIMETER_ZN_3 0.000 0.000 11.026 -6.926 0.000 0.000 4.130 5.686 10.719 5.396 0.000 0.048 0.000 0.000 -8.311 0.000 -2.675 -19.093
PERIMETER_ZN_4 0.000 0.000 5.732 -5.746 0.000 0.000 2.406 3.284 6.359 10.512 0.000 0.027 0.000 0.000 -5.705 0.000 -1.891 -14.978
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9.637 25.235 0.000 0.000 0.000 -34.871 -0.000
Total Facility 0.000 0.000 30.382 -45.883 0.000 0.000 17.607 26.109 48.296 55.671 0.000 10.209 25.235 0.000 -30.138 0.000 -50.351 -87.137


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 03-JUL-07:02 0.00 0.00 0.00 -5512.17 0.00 0.00 497.32 593.08 973.59 0.00 0.00 0.00 3448.18 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 05-SEP-07:02 0.00 0.00 0.00 -5725.10 0.00 0.00 387.46 379.13 738.04 1.79 0.00 0.00 4435.42 0.00 -0.00 0.00 -216.75 0.00
PERIMETER_ZN_2 09-JUN-07:02 0.00 0.00 0.00 -4498.39 0.00 0.00 227.60 194.67 437.82 2165.31 0.00 0.00 1486.57 0.00 -0.00 0.00 -13.57 0.00
PERIMETER_ZN_3 03-JUL-07:02 0.00 0.00 0.00 -5236.07 0.00 0.00 396.87 366.92 738.04 15.18 0.00 0.00 3728.34 0.00 -0.00 0.00 -9.28 0.00
PERIMETER_ZN_4 21-AUG-06:02 0.00 0.00 0.00 -5587.61 0.00 0.00 39.75 116.23 218.91 0.00 0.00 0.00 5257.27 0.00 -33.74 0.00 -10.80 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-SEP-07:02 0.00 0.00 0.00 -26201.75 0.00 0.00 1709.07 1818.46 3325.31 241.35 0.00 279.81 19136.07 0.00 -29.80 0.00 -278.51 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 09-JAN-07:01 0.00 0.00 7128.27 0.00 0.00 0.00 159.89 276.77 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8051.72
PERIMETER_ZN_1 06-MAR-06:01 0.00 0.00 8788.31 0.00 0.00 0.00 68.24 114.89 369.02 0.00 0.00 0.00 0.00 0.00 -569.85 0.00 -485.38 -8285.23
PERIMETER_ZN_2 09-JAN-06:01 0.00 0.00 6947.31 0.00 0.00 0.00 40.93 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -238.40 0.00 -49.09 -6987.81
PERIMETER_ZN_3 24-DEC-10:11 0.00 0.00 8260.11 0.00 0.00 0.00 0.00 75.76 125.99 0.00 0.00 0.00 0.00 0.00 -46.42 0.00 -146.73 -8268.70
PERIMETER_ZN_4 09-JAN-06:01 0.00 0.00 8823.13 0.00 0.00 0.00 40.89 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -240.82 0.00 -50.57 -8859.70
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-JAN-07:01 0.00 0.00 36499.25 0.00 0.00 0.00 546.10 945.30 1662.65 0.00 0.00 827.24 0.00 0.00 -1403.90 0.00 -2011.49 -37065.16



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3340 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3340 0.1935 1.0000 Not calculated 0.0646 0.1935    
PSZ-AC:2 0.3746 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3746 0.1308 1.0000 Not calculated 0.0490 0.1308    
PSZ-AC:3 0.2996 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2996 0.0970 1.0000 Not calculated 0.0291 0.0970    
PSZ-AC:4 0.3326 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3326 0.1473 1.0000 Not calculated 0.0490 0.1473    
PSZ-AC:5 0.3868 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3868 0.0751 1.0000 Not calculated 0.0291 0.0751    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3340 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3340 1.0000 1.0000 Not calculated 0.0646 0.1935    
PSZ-AC:2 0.3746 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3746 1.0000 1.0000 Not calculated 0.0490 0.1308    
PSZ-AC:3 0.2996 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2996 1.0000 1.0000 Not calculated 0.0291 0.0970    
PSZ-AC:4 0.3326 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3326 1.0000 1.0000 Not calculated 0.0490 0.1473    
PSZ-AC:5 0.3868 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3868 1.0000 1.0000 Not calculated 0.0291 0.0751    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.002360 8.0545 0.000305 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.002360 8.05 0.000305 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3340 0.3340 0.3340 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3746 0.3746 0.3746 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2996 0.2996 0.2996 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3326 0.3326 0.3326 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3868 0.3868 0.3868 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3340 0.3340 0.3340 0.3340 0.0646 1.0000
PSZ-AC:2 0.3746 0.3746 0.3746 0.3746 0.0490 1.0000
PSZ-AC:3 0.2996 0.2996 0.2996 0.2996 0.0291 1.0000
PSZ-AC:4 0.3326 0.3326 0.3326 0.3326 0.0490 1.0000
PSZ-AC:5 0.3868 0.3868 0.3868 0.3868 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3340 0.3340 0.3340 No 0.0646 0.8296 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3746 0.3746 0.3746 No 0.0490 0.1882 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2996 0.2996 0.2996 No 0.0291 0.1746 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3326 0.3326 0.3326 No 0.0490 0.1916 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3868 0.3868 0.3868 No 0.0291 0.1746 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3340 0.3340 0.3340 0.3340 0.0646 1.0000
PSZ-AC:2 0.3746 0.3746 0.3746 0.3746 0.0490 1.0000
PSZ-AC:3 0.2996 0.2996 0.2996 0.2996 0.0291 1.0000
PSZ-AC:4 0.3326 0.3326 0.3326 0.3326 0.0490 1.0000
PSZ-AC:5 0.3868 0.3868 0.3868 0.3868 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 30.67
Number of hours cooling loads not met 13.00
Number of hours not met 43.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 16.40 9374.48 12.38 32064.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 11.33 6175.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.11 2025.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.78 1049.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 23.71 1934.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 24.45 2821.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 160.07
Natural Gas 0.00 12.38
Additional 0.00 0.00
Total 48.30 172.46


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.08
Space Heating 32.07
Space Cooling 22.17
Fans (All) 46.38
Service Water Heating 47.83
Receptacle Equipment 94.48
Miscellaneous (All) 313.16
Subtotal 313.16


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.23
Service Water Heating 0.00
Miscellaneous (All) 24.23
Subtotal 24.23


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 15.14
Space Heating 16.69
Space Cooling 6.57
Fans (All) 13.75
Service Water Heating 14.18
Receptacle Equipment 28.00
Miscellaneous 5.67


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2635. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8574.83 185.17 0.00 0.00 0.00
PERIMETER_ZN_1 8569.33 190.67 0.00 0.00 0.00
PERIMETER_ZN_2 8459.17 300.83 0.00 0.00 0.00
PERIMETER_ZN_3 8718.83 41.17 0.00 0.00 0.00
PERIMETER_ZN_4 8406.67 353.33 0.00 0.00 0.00
ATTIC 6848.50 589.50 559.33 754.67 8.00
Min 6848.50 41.17 0.00 0.00 0.00
Max 8718.83 589.50 559.33 754.67 8.00
Average 8262.89 276.78 93.22 125.78 1.33
Sum 49577.33 1660.67 559.33 754.67 8.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 8385.17 374.83 0.00 0.00 0.00
PERIMETER_ZN_1 8664.00 96.00 0.00 0.00 0.00
PERIMETER_ZN_2 8631.83 128.17 0.00 0.00 0.00
PERIMETER_ZN_3 8738.83 21.17 0.00 0.00 0.00
PERIMETER_ZN_4 8646.00 114.00 0.00 0.00 0.00
ATTIC 7076.83 820.83 318.67 273.00 270.67
Min 7076.83 21.17 0.00 0.00 0.00
Max 8738.83 820.83 318.67 273.00 270.67
Average 8357.11 259.17 53.11 45.50 45.11
Sum 50142.67 1555.00 318.67 273.00 270.67


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17885.83 6.17 0.00 0.00 0.00
PERIMETER_ZN_1 13355.33 0.67 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13355.17 0.83 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17885.83 6.17 0.00 0.00 0.00
Average 9364.72 1.28 0.00 0.00 0.00
Sum 56188.33 7.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:09

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.365895E+09 1972.05 05-JAN-18:03 -18.2 -18.2 0.236888E+09 402.33 25-JAN-14:00 14.00 4.48
February 0.380170E+09 1547.28 02-FEB-07:06 -9.7 -9.7 0.208134E+09 380.23 27-FEB-16:00 13.00 4.60
March 0.534611E+09 1672.01 15-MAR-15:55 19.00 5.38 0.273968E+09 402.34 17-MAR-10:00 7.00 6.41
April 0.355387E+09 1428.15 03-APR-06:06 -7.7 -7.7 0.244359E+09 402.34 13-APR-13:09 17.50 9.42
May 0.871019E+09 5078.92 17-MAY-07:01 19.50 10.18 0.302228E+09 435.83 18-MAY-07:10 18.17 10.10
June 0.227388E+10 5336.62 09-JUN-07:02 12.57 5.42 0.317485E+09 469.22 26-JUN-07:10 22.07 12.41
July 0.231246E+10 5512.04 03-JUL-07:02 11.33 7.79 0.289458E+09 469.22 03-JUL-07:10 11.33 7.79
August 0.256030E+10 5446.68 17-AUG-07:02 14.33 5.88 0.332210E+09 469.22 09-AUG-07:10 14.33 5.88
September 0.206416E+10 5480.22 15-SEP-07:03 11.75 5.37 0.287754E+09 469.22 13-SEP-07:10 11.75 5.37
October 0.112829E+10 5332.89 11-OCT-07:03 13.67 5.23 0.280468E+09 448.10 11-OCT-07:10 13.67 5.23
November 0.641706E+09 1685.15 29-NOV-18:13 -13.0 -13.0 0.254312E+09 402.38 10-NOV-14:39 -13.0 -13.0
December 0.411605E+09 2242.55 21-DEC-18:01 -21.7 -21.8 0.222773E+09 402.33 04-DEC-16:10 -21.7 -21.8
                     
Annual Sum or Average 0.138995E+11         0.325004E+10        
Minimum of Months 0.355387E+09 1428.15   -21.7 -21.8 0.208134E+09 380.23   -21.7 -21.8
Maximum of Months 0.256030E+10 5512.04   19.50 10.18 0.332210E+09 469.22   22.07 12.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.454786E+09 3142.42 20-JAN-14:37 20.33 6.84 0.188922E+09 305.00 11-JAN-16:30 20.33 6.84
February 0.288808E+09 2239.20 27-FEB-14:15 14.00 4.75 0.167828E+09 304.99 27-FEB-13:09 14.00 4.75
March 0.443767E+09 3611.47 15-MAR-14:05 20.83 6.19 0.208134E+09 304.99 31-MAR-13:30 19.50 6.68
April 0.103777E+09 1482.28 21-APR-12:10 14.33 6.08 0.176936E+09 306.23 06-APR-15:09 14.33 6.08
May 0.284549E+09 1878.05 18-MAY-14:10 23.83 11.33 0.214601E+09 309.67 04-MAY-12:50 23.83 11.33
June 0.173567E+10 5512.70 26-JUN-07:02 22.07 12.41 0.238672E+09 355.75 27-JUN-07:10 22.47 9.00
July 0.180775E+10 5485.07 17-JUL-06:01 22.50 11.12 0.217658E+09 355.76 25-JUL-07:10 23.33 14.79
August 0.243284E+10 5659.10 21-AUG-06:02 19.75 12.40 0.250649E+09 355.70 21-AUG-07:10 21.17 13.07
September 0.239880E+10 5724.76 05-SEP-07:02 14.68 7.70 0.217027E+09 355.70 13-SEP-07:10 20.18 12.26
October 0.126743E+10 5453.23 10-OCT-12:10 23.17 7.88 0.207257E+09 334.94 10-OCT-14:09 25.00 8.67
November 0.808569E+09 4729.87 07-NOV-13:55 22.00 7.34 0.196715E+09 304.99 09-NOV-13:09 20.00 8.90
December 0.358284E+09 2566.62 14-DEC-14:25 16.15 4.44 0.176080E+09 304.99 04-DEC-13:09 16.15 4.44
                     
Annual Sum or Average 0.123850E+11         0.246048E+10        
Minimum of Months 0.103777E+09 1482.28   14.00 4.44 0.167828E+09 304.99   14.00 4.44
Maximum of Months 0.243284E+10 5724.76   23.83 12.41 0.250649E+09 355.76   25.00 14.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8345791.82 509.96 05-JAN-18:03 -18.2 -18.2 74055769.86 178.22 20-JAN-15:39 18.67 7.30
February 12868691.61 506.00 06-FEB-06:04 -10.0 -10.1 65692390.43 162.52 27-FEB-13:00 14.00 4.75
March 81074629.13 1089.22 15-MAR-10:04 15.17 4.28 87210476.82 180.92 13-MAR-12:09 15.17 4.28
April 76174123.53 1004.06 21-APR-08:54 12.00 5.98 78046396.11 180.97 07-APR-10:09 12.00 5.98
May 0.320134E+09 4294.14 17-MAY-07:01 19.50 10.18 97163448.23 198.65 17-MAY-07:10 19.50 10.18
June 0.158436E+10 4498.65 09-JUN-07:02 12.57 5.42 0.105329E+09 211.01 19-JUN-07:10 22.98 13.93
July 0.146065E+10 4481.57 03-JUL-07:02 11.33 7.79 95854027.96 211.00 19-JUL-07:10 21.33 14.20
August 0.171566E+10 4464.46 21-AUG-06:02 19.75 12.40 0.110169E+09 211.01 07-AUG-07:10 19.75 12.40
September 0.125694E+10 4432.18 05-SEP-07:02 14.68 7.70 94716459.23 211.01 06-SEP-07:10 17.25 13.03
October 0.324061E+09 1887.26 11-OCT-10:04 23.17 8.56 88213142.02 188.03 11-OCT-07:10 23.17 8.56
November 75550835.58 688.33 09-NOV-13:13 20.00 8.84 79466500.32 181.17 16-NOV-16:19 13.00 6.02
December 11657692.33 684.63 21-DEC-18:01 -21.7 -21.8 69559460.75 167.69 01-DEC-15:39 -21.7 -21.8
                     
Annual Sum or Average 0.692748E+10         0.104548E+10        
Minimum of Months 8345791.82 506.00   -21.7 -21.8 65692390.43 162.52   -21.7 -21.8
Maximum of Months 0.171566E+10 4498.65   23.17 12.40 0.110169E+09 211.01   23.17 14.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8346719.64 1202.49 05-JAN-18:03 -18.2 -18.2 0.167042E+09 263.95 20-JAN-15:00 18.00 7.49
February 3119677.52 997.39 02-FEB-06:04 -9.2 -9.2 0.150093E+09 233.83 17-FEB-16:40 13.33 6.60
March 30067865.68 959.81 02-MAR-06:04 -8.2 -8.2 0.190628E+09 305.05 14-MAR-14:50 23.00 7.59
April 23126823.31 908.37 03-APR-05:04 -8.0 -8.0 0.168475E+09 304.99 20-APR-15:39 20.00 8.62
May 0.242896E+09 1540.54 18-MAY-14:55 23.00 11.61 0.215836E+09 308.66 05-MAY-13:09 23.00 11.61
June 0.164164E+10 5106.27 15-JUN-07:02 16.28 11.51 0.239699E+09 355.69 19-JUN-07:10 22.98 13.93
July 0.164709E+10 5235.87 03-JUL-07:02 11.33 7.79 0.218181E+09 355.70 19-JUL-07:10 21.33 14.20
August 0.173591E+10 5144.45 15-AUG-07:02 14.00 10.42 0.250433E+09 355.70 21-AUG-07:10 21.17 13.07
September 0.126902E+10 5146.92 05-SEP-07:02 14.68 7.70 0.214961E+09 355.69 12-SEP-07:10 19.95 11.80
October 0.261262E+09 1654.70 11-OCT-15:13 25.33 9.18 0.195143E+09 304.99 03-OCT-14:20 25.33 9.18
November 55706253.98 1023.69 29-NOV-18:03 -13.0 -13.0 0.174935E+09 305.08 09-NOV-11:39 -13.0 -13.0
December 7690201.43 1464.42 21-DEC-18:01 -21.7 -21.8 0.158699E+09 257.79 04-DEC-15:50 -21.7 -21.8
                     
Annual Sum or Average 0.692588E+10         0.234412E+10        
Minimum of Months 3119677.52 908.37   -21.7 -21.8 0.150093E+09 233.83   -21.7 -21.8
Maximum of Months 0.173591E+10 5235.87   25.33 11.61 0.250433E+09 355.70   25.33 14.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 18904383.61 626.34 20-JAN-16:22 15.00 6.47 0.103512E+09 181.20 20-JAN-14:50 15.00 6.47
February 15010333.62 410.70 02-FEB-06:04 -9.2 -9.2 92031961.01 180.92 17-FEB-16:00 13.00 6.46
March 63637712.60 1583.18 15-MAR-15:55 19.00 5.38 0.119538E+09 182.80 10-MAR-14:20 19.00 5.38
April 22431979.94 1150.12 07-APR-15:53 21.00 8.12 0.105286E+09 185.08 20-APR-12:00 22.00 9.15
May 0.224692E+09 1772.70 31-MAY-15:57 28.00 14.86 0.132086E+09 185.66 04-MAY-13:30 28.00 14.86
June 0.130510E+10 5503.38 05-JUN-07:01 19.18 11.36 0.143506E+09 211.67 15-JUN-07:10 16.28 11.51
July 0.120188E+10 5572.54 03-JUL-07:02 11.33 7.79 0.130267E+09 211.00 19-JUL-07:10 21.33 14.20
August 0.138787E+10 5587.55 21-AUG-06:02 19.75 12.40 0.149999E+09 211.00 16-AUG-07:10 19.75 12.40
September 0.109175E+10 5560.04 11-SEP-06:01 19.00 9.04 0.129081E+09 211.00 05-SEP-07:10 19.00 9.04
October 0.318937E+09 2751.18 11-OCT-15:54 24.00 8.61 0.121506E+09 189.11 11-OCT-07:10 24.00 8.61
November 81832413.75 1423.37 07-NOV-15:53 21.00 7.19 0.110236E+09 182.40 17-NOV-13:50 13.83 6.31
December 13659425.72 566.29 21-DEC-18:01 -21.7 -21.8 97770833.55 180.92 01-DEC-16:49 -21.7 -21.8
                     
Annual Sum or Average 0.574571E+10         0.143482E+10        
Minimum of Months 13659425.72 410.70   -21.7 -21.8 92031961.01 180.92   -21.7 -21.8
Maximum of Months 0.138787E+10 5587.55   28.00 14.86 0.149999E+09 211.67   28.00 14.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 0.50 -1.8 0.00 0.00 01-JAN-00:10 0.50 -1.8
February 0.00 0.00 01-FEB-00:10 -5.3 -5.3 0.00 0.00 01-FEB-00:10 -5.3 -5.3
March 0.00 0.00 01-MAR-00:10 -1.1 -1.1 0.00 0.00 01-MAR-00:10 -1.1 -1.1
April 0.00 0.00 01-APR-00:10 5.90 2.10 0.00 0.00 01-APR-00:10 5.90 2.10
May 0.00 0.00 01-MAY-00:10 5.43 4.75 0.00 0.00 01-MAY-00:10 5.43 4.75
June 0.00 0.00 01-JUN-00:10 15.88 11.26 0.00 0.00 01-JUN-00:10 15.88 11.26
July 0.00 0.00 01-JUL-00:10 22.27 10.91 0.00 0.00 01-JUL-00:10 22.27 10.91
August 0.00 0.00 01-AUG-00:10 18.93 15.43 0.00 0.00 01-AUG-00:10 18.93 15.43
September 0.00 0.00 01-SEP-00:05 18.18 10.64 0.00 0.00 01-SEP-00:10 18.18 10.64
October 0.00 0.00 01-OCT-00:10 10.30 8.03 0.00 0.00 01-OCT-00:10 10.30 8.03
November 0.00 0.00 01-NOV-00:10 -5.7 -5.7 0.00 0.00 01-NOV-00:10 -5.7 -5.7
December 0.00 0.00 01-DEC-00:05 2.77 -0.5 0.00 0.00 01-DEC-00:10 2.77 -0.5
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -5.7 -5.7 0.00 0.00   -5.7 -5.7
Maximum of Months 0.00 0.00   22.27 15.43 0.00 0.00   22.27 15.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217222E+09 7128.30 09-JAN-07:01 4.17
February 0.234542E+09 6604.21 17-FEB-07:01 0.50
March 97247368.95 7116.99 06-MAR-07:01 2.00
April 82751210.58 6682.75 25-APR-06:01 2.83
May 18307482.28 6283.44 03-MAY-07:02 4.33
June 38608674.84 1111.07 26-JUN-17:01 37.70
July 26894150.78 783.33 24-JUL-17:02 32.50
August 35016918.93 1021.30 16-AUG-16:03 36.83
September 14225312.72 649.00 12-SEP-16:03 30.82
October 14669042.99 4815.78 25-OCT-07:03 1.50
November 42383122.84 5995.78 03-NOV-06:01 -1.5
December 0.201179E+09 6556.11 29-DEC-07:01 1.00
         
Annual Sum or Average 0.102305E+10      
Minimum of Months 14225312.72 649.00   -1.5
Maximum of Months 0.234542E+09 7128.30   37.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.958691E+09 8596.92 06-JAN-06:01 -7.0
February 0.139749E+10 8733.18 08-FEB-06:01 -5.8
March 0.117798E+10 8788.28 06-MAR-06:01 1.17
April 0.997397E+09 8720.54 04-APR-05:01 -2.2
May 0.264218E+09 7974.18 02-MAY-06:01 0.17
June 52963645.35 923.88 26-JUN-17:12 37.70
July 41775473.98 676.52 24-JUL-17:11 32.00
August 40372920.30 810.08 16-AUG-17:12 35.33
September 23071592.38 3784.96 22-SEP-07:03 0.37
October 0.506233E+09 8389.95 31-OCT-05:01 -8.2
November 0.628373E+09 8761.32 01-NOV-05:01 -3.0
December 0.135851E+10 8669.90 11-DEC-06:01 -5.8
         
Annual Sum or Average 0.744706E+10      
Minimum of Months 23071592.38 676.52   -8.2
Maximum of Months 0.139749E+10 8788.28   37.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.975786E+09 6947.28 09-JAN-06:01 4.00
February 0.105149E+10 6508.10 15-FEB-06:01 -2.3
March 0.679836E+09 6886.71 06-MAR-06:01 1.17
April 0.458333E+09 6609.88 04-APR-05:01 -2.2
May 73339919.52 6193.06 02-MAY-06:01 0.17
June 31964794.46 620.76 26-JUN-17:12 37.70
July 26397916.06 477.69 24-JUL-17:11 32.00
August 29644703.47 563.02 16-AUG-17:12 35.33
September 17459695.02 396.24 12-SEP-17:11 28.83
October 0.239799E+09 6220.22 25-OCT-06:01 -1.5
November 0.429805E+09 6287.36 01-NOV-05:01 -3.0
December 0.114027E+10 6790.77 27-DEC-06:01 0.50
         
Annual Sum or Average 0.515412E+10      
Minimum of Months 17459695.02 396.24   -3.0
Maximum of Months 0.114027E+10 6947.28   37.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.221961E+10 8098.94 16-JAN-08:52 -8.0
February 0.231947E+10 8117.31 05-FEB-21:53 -7.0
March 0.153281E+10 8221.19 05-MAR-08:51 -6.0
April 0.976671E+09 8058.80 17-APR-05:01 -8.0
May 0.173401E+09 7019.00 02-MAY-06:01 0.17
June 38669503.72 889.31 26-JUN-17:12 37.70
July 28555540.61 649.04 24-JUL-17:02 32.50
August 33721949.70 804.29 16-AUG-17:01 35.67
September 17882992.20 2349.87 22-SEP-07:03 0.37
October 0.402015E+09 7837.99 31-OCT-05:01 -8.2
November 0.980613E+09 7854.25 01-NOV-05:01 -3.0
December 0.230293E+10 8260.27 24-DEC-10:11 -8.3
         
Annual Sum or Average 0.110263E+11      
Minimum of Months 17882992.20 649.04   -8.3
Maximum of Months 0.231947E+10 8260.27   37.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101688E+10 8823.10 09-JAN-06:01 4.00
February 0.111007E+10 7865.92 17-FEB-07:01 0.50
March 0.833649E+09 8154.49 06-MAR-06:01 1.17
April 0.581752E+09 7932.79 25-APR-06:01 2.83
May 0.146247E+09 7859.29 03-MAY-06:01 2.33
June 43975135.36 649.81 26-JUN-17:12 37.70
July 41927383.27 548.54 17-JUL-17:22 32.00
August 39003833.83 594.30 16-AUG-17:12 35.33
September 27028492.97 481.76 22-SEP-07:03 0.37
October 0.246167E+09 7079.66 25-OCT-06:01 -1.5
November 0.460957E+09 7488.61 22-NOV-07:01 0.33
December 0.118419E+10 7913.10 27-DEC-06:01 0.50
         
Annual Sum or Average 0.573184E+10      
Minimum of Months 27028492.97 481.76   -1.5
Maximum of Months 0.118419E+10 8823.10   37.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 0.50
February 0.00 0.00 01-FEB-00:10 -5.3
March 0.00 0.00 01-MAR-00:10 -1.1
April 0.00 0.00 01-APR-00:10 5.90
May 0.00 0.00 01-MAY-00:10 5.43
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:05 18.18
October 0.00 0.00 01-OCT-00:10 10.30
November 0.00 0.00 01-NOV-00:10 -5.7
December 0.00 0.00 01-DEC-00:05 2.77
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -5.7
Maximum of Months 0.00 0.00   22.27



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.714248E+09 593.08 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.645736E+09 593.08 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.752015E+09 593.08 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.685116E+09 593.08 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.733131E+09 593.08 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.722883E+09 593.08 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.695364E+09 593.08 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.752015E+09 593.08 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.685116E+09 593.08 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.714248E+09 593.08 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.704000E+09 593.08 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.695364E+09 593.08 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.849924E+10     0.141401E+11    
Minimum of Months 0.645736E+09 593.08   0.107295E+10 973.59  
Maximum of Months 0.752015E+09 593.08   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.459375E+09 449.59 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.413661E+09 445.67 06-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.472450E+09 433.74 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.428484E+09 428.02 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.450283E+09 391.47 19-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.443190E+09 400.15 16-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.428179E+09 394.90 28-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.465448E+09 409.87 28-AUG-15:00 0.953087E+09 738.04 01-AUG-07:10
September 0.426813E+09 409.25 21-SEP-15:00 0.861220E+09 738.04 01-SEP-07:10
October 0.456687E+09 440.20 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.456049E+09 449.59 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.452431E+09 449.59 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.535305E+10     0.107191E+11    
Minimum of Months 0.413661E+09 391.47   0.813362E+09 738.04  
Maximum of Months 0.472450E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287935E+09 266.70 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.258555E+09 264.59 06-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.291561E+09 257.36 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.259545E+09 253.57 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.271617E+09 240.24 12-MAY-13:30 0.549505E+09 437.82 01-MAY-07:10
June 0.267730E+09 233.11 16-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.257642E+09 235.74 12-JUL-15:00 0.518151E+09 437.82 03-JUL-07:10
August 0.283348E+09 247.34 28-AUG-15:00 0.565383E+09 437.82 01-AUG-07:10
September 0.260155E+09 248.62 21-SEP-15:00 0.510887E+09 437.82 01-SEP-07:10
October 0.281844E+09 261.33 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.283985E+09 266.70 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.282582E+09 266.70 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.328650E+10     0.635872E+10    
Minimum of Months 0.257642E+09 233.11   0.482497E+09 437.82  
Maximum of Months 0.291561E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.511651E+09 449.59 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.456389E+09 446.02 06-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.510813E+09 435.43 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.444407E+09 430.01 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.453544E+09 402.26 12-MAY-13:30 0.926320E+09 738.04 01-MAY-07:10
June 0.445722E+09 401.35 16-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.430692E+09 395.88 28-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.483731E+09 413.91 28-AUG-15:00 0.953087E+09 738.04 01-AUG-07:10
September 0.454693E+09 415.78 21-SEP-15:00 0.861220E+09 738.04 01-SEP-07:10
October 0.494403E+09 441.36 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.501105E+09 449.59 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.498878E+09 449.59 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.568603E+10     0.107191E+11    
Minimum of Months 0.430692E+09 395.88   0.813362E+09 738.04  
Maximum of Months 0.511651E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287257E+09 266.70 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.256654E+09 264.48 06-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.291985E+09 258.56 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.260500E+09 255.81 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.272437E+09 242.84 01-MAY-07:19 0.549505E+09 437.82 01-MAY-07:10
June 0.267932E+09 242.96 16-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.258820E+09 243.28 12-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.283622E+09 245.53 21-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.262138E+09 250.91 25-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.280177E+09 261.82 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.282075E+09 266.70 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.280313E+09 266.70 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.328391E+10     0.635872E+10    
Minimum of Months 0.256654E+09 242.84   0.482497E+09 437.82  
Maximum of Months 0.291985E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.714248E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.685116E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.733131E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.722883E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.695364E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.685116E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.714248E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.704000E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.695364E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.849924E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.459375E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.106266E+10
February 0.488155E+09 0.413661E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.116478E+10
March 0.590925E+09 0.472450E+09 0.953087E+09 0.00 0.00 0.00 0.00 1329.95 0.105023E+10
April 0.513848E+09 0.428484E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.00 0.856914E+09
May 0.565233E+09 0.450283E+09 0.926320E+09 0.00 0.00 0.00 0.00 10154097.28 0.506027E+09
June 0.565233E+09 0.443190E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.151332E+09 0.186579E+09
July 0.513848E+09 0.428179E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.124985E+09 0.189473E+09
August 0.590925E+09 0.465448E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.129277E+09 0.238921E+09
September 0.513848E+09 0.426813E+09 0.861220E+09 0.00 0.00 0.00 0.00 53839976.05 0.361372E+09
October 0.539540E+09 0.456687E+09 0.900233E+09 0.00 0.00 0.00 0.00 739286.20 0.965469E+09
November 0.539540E+09 0.456049E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.106352E+10
December 0.513848E+09 0.452431E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.140829E+10
                   
Annual Sum or Average 0.647448E+10 0.535305E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.470328E+09 0.905424E+10
Minimum of Months 0.488155E+09 0.413661E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.186579E+09
Maximum of Months 0.590925E+09 0.472450E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.151332E+09 0.140829E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.287935E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.128961E+09
February 0.211974E+09 0.258555E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.207247E+09
March 0.256600E+09 0.291561E+09 0.565383E+09 0.00 0.00 0.00 0.00 86.22 0.220012E+09
April 0.223130E+09 0.259545E+09 0.511694E+09 0.00 0.00 0.00 0.00 0.00 0.228011E+09
May 0.245443E+09 0.271617E+09 0.549505E+09 0.00 0.00 0.00 0.00 497783.78 0.125729E+09
June 0.245443E+09 0.267730E+09 0.542644E+09 0.00 0.00 0.00 0.00 9289866.62 65727734.57
July 0.223130E+09 0.257642E+09 0.518151E+09 0.00 0.00 0.00 0.00 8836238.14 69054822.65
August 0.256600E+09 0.283348E+09 0.565383E+09 0.00 0.00 0.00 0.00 5583109.67 69760839.75
September 0.223130E+09 0.260155E+09 0.510887E+09 0.00 0.00 0.00 0.00 2377285.46 0.102659E+09
October 0.234287E+09 0.281844E+09 0.534030E+09 0.00 0.00 0.00 0.00 74175.66 0.192362E+09
November 0.234287E+09 0.283985E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.156683E+09
December 0.223130E+09 0.282582E+09 0.517747E+09 0.00 0.00 0.00 0.00 2456.83 0.292363E+09
                   
Annual Sum or Average 0.281144E+10 0.328650E+10 0.635872E+10 0.00 0.00 0.00 0.00 26661002.38 0.185857E+10
Minimum of Months 0.211974E+09 0.257642E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 65727734.57
Maximum of Months 0.256600E+09 0.291561E+09 0.565383E+09 0.00 0.00 0.00 0.00 9289866.62 0.292363E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.511651E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.189091E+09
February 0.488155E+09 0.456389E+09 0.813362E+09 0.00 0.00 0.00 0.00 19607.48 0.302929E+09
March 0.590925E+09 0.510813E+09 0.953087E+09 0.00 0.00 0.00 0.00 285.80 0.319182E+09
April 0.513848E+09 0.444407E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.00 0.329704E+09
May 0.565233E+09 0.453544E+09 0.926320E+09 0.00 0.00 0.00 0.00 932959.97 0.179781E+09
June 0.565233E+09 0.445722E+09 0.914754E+09 0.00 0.00 0.00 0.00 15783172.56 92634433.53
July 0.513848E+09 0.430692E+09 0.873466E+09 0.00 0.00 0.00 0.00 16810370.61 94327882.49
August 0.590925E+09 0.483731E+09 0.953087E+09 0.00 0.00 0.00 0.00 9440502.38 95085205.90
September 0.513848E+09 0.454693E+09 0.861220E+09 0.00 0.00 0.00 0.00 4653971.44 0.140745E+09
October 0.539540E+09 0.494403E+09 0.900233E+09 0.00 0.00 0.00 0.00 111454.70 0.273251E+09
November 0.539540E+09 0.501105E+09 0.888667E+09 0.00 0.00 0.00 0.00 53145.70 0.227308E+09
December 0.513848E+09 0.498878E+09 0.872785E+09 0.00 0.00 0.00 0.00 87800.86 0.431347E+09
                   
Annual Sum or Average 0.647448E+10 0.568603E+10 0.107191E+11 0.00 0.00 0.00 0.00 47893271.50 0.267538E+10
Minimum of Months 0.488155E+09 0.430692E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 92634433.53
Maximum of Months 0.590925E+09 0.511651E+09 0.953087E+09 0.00 0.00 0.00 0.00 16810370.61 0.431347E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.287257E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.130655E+09
February 0.289580E+09 0.256654E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.209697E+09
March 0.350544E+09 0.291985E+09 0.565383E+09 0.00 0.00 0.00 0.00 86.22 0.223210E+09
April 0.304821E+09 0.260500E+09 0.511694E+09 0.00 0.00 0.00 0.00 0.00 0.231051E+09
May 0.335303E+09 0.272437E+09 0.549505E+09 0.00 0.00 0.00 0.00 557130.45 0.128487E+09
June 0.335303E+09 0.267932E+09 0.542644E+09 0.00 0.00 0.00 0.00 9009354.45 70912065.48
July 0.304821E+09 0.258820E+09 0.518151E+09 0.00 0.00 0.00 0.00 9421820.58 69607688.89
August 0.350544E+09 0.283622E+09 0.565383E+09 0.00 0.00 0.00 0.00 5525883.69 73183340.28
September 0.304821E+09 0.262138E+09 0.510887E+09 0.00 0.00 0.00 0.00 2543155.76 0.105265E+09
October 0.320062E+09 0.280177E+09 0.534030E+09 0.00 0.00 0.00 0.00 74134.16 0.194970E+09
November 0.320062E+09 0.282075E+09 0.527169E+09 0.00 0.00 0.00 0.00 4.21 0.159168E+09
December 0.304821E+09 0.280313E+09 0.517747E+09 0.00 0.00 0.00 0.00 5136.85 0.294937E+09
                   
Annual Sum or Average 0.384075E+10 0.328391E+10 0.635872E+10 0.00 0.00 0.00 0.00 27136706.38 0.189114E+10
Minimum of Months 0.289580E+09 0.256654E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 69607688.89
Maximum of Months 0.350544E+09 0.291985E+09 0.565383E+09 0.00 0.00 0.00 0.00 9421820.58 0.294937E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109934E+10 0.185216E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.894617E+09 0.226920E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.803485E+09 0.293275E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.565037E+09 0.303282E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.559207E+09 0.386308E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.638162E+09 0.426223E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.581990E+09 0.383694E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.648219E+09 0.392710E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.869494E+09 0.297548E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.926246E+09 0.246828E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.928759E+09 0.201311E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112222E+10 0.143821E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.963678E+10 0.348714E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.559207E+09 0.143821E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112222E+10 0.426223E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 593.08 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 593.08 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 593.08 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 593.08 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 593.08 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 593.08 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 593.08 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 593.08 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 593.08 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 593.08 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 593.08 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 593.08 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 449.59 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 5373.09 05-JAN-17:03
February 732.70 01-FEB-08:09 445.67 06-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4232.42 02-FEB-07:10
March 732.70 01-MAR-08:09 433.74 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 2.22 14-MAR-13:00 4094.29 02-MAR-07:10
April 732.70 03-APR-07:10 428.02 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3815.75 17-APR-06:10
May 732.70 01-MAY-07:10 391.47 19-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 466.41 31-MAY-16:03 2794.28 02-MAY-06:10
June 732.70 01-JUN-07:10 400.15 16-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 1680.64 26-JUN-16:03 1779.58 09-JUN-06:03
July 732.70 03-JUL-07:10 394.90 28-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 1421.69 17-JUL-11:55 1775.98 03-JUL-06:03
August 732.70 01-AUG-07:10 409.87 28-AUG-15:00 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 1473.36 16-AUG-16:03 1645.28 17-AUG-06:03
September 732.70 01-SEP-07:10 409.25 21-SEP-15:00 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 750.50 12-SEP-16:03 3245.42 21-SEP-16:02
October 732.70 02-OCT-07:10 440.20 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 122.63 11-OCT-11:55 4321.80 30-OCT-07:00
November 732.70 01-NOV-07:10 449.59 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4892.34 29-NOV-17:53
December 732.70 01-DEC-08:09 449.59 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 6475.83 21-DEC-17:02
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   391.47   738.04   0.00 0.00 0.00 0.00 0.00   1645.28  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 1680.64   6475.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 266.70 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 220.37 12-JAN-07:00
February 434.65 01-FEB-08:09 264.59 06-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 309.33 24-FEB-19:03
March 434.65 01-MAR-08:09 257.36 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.14 14-MAR-13:00 650.63 19-MAR-07:00
April 434.65 03-APR-07:10 253.57 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 391.34 15-APR-05:00
May 434.65 01-MAY-07:10 240.24 12-MAY-13:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 12.90 17-MAY-14:43 248.82 02-MAY-05:55
June 434.65 01-JUN-07:10 233.11 16-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 55.19 26-JUN-18:53 155.33 08-JUN-23:00
July 434.65 03-JUL-07:10 235.74 12-JUL-15:00 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 72.73 16-JUL-12:10 165.95 03-JUL-03:00
August 434.65 01-AUG-07:10 247.34 28-AUG-15:00 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 39.71 02-AUG-15:53 203.98 27-AUG-17:55
September 434.65 01-SEP-07:10 248.62 21-SEP-15:00 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 22.22 10-SEP-13:00 171.70 22-SEP-02:00
October 434.65 02-OCT-07:10 261.33 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 5.98 11-OCT-14:00 349.09 29-OCT-09:00
November 434.65 01-NOV-07:10 266.70 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 334.24 01-NOV-04:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 1.36 02-DEC-14:55 623.91 21-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   233.11   437.82   0.00 0.00 0.00 0.00 0.00   155.33  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 72.73   650.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 449.59 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 330.55 12-JAN-07:00
February 732.70 01-FEB-08:09 446.02 06-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 3.64 26-FEB-12:55 461.56 24-FEB-19:03
March 732.70 01-MAR-08:09 435.43 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.46 14-MAR-13:00 975.87 19-MAR-07:00
April 732.70 03-APR-07:10 430.01 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 584.08 15-APR-05:00
May 732.70 01-MAY-07:10 402.26 12-MAY-13:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 19.34 17-MAY-14:43 373.23 02-MAY-05:55
June 732.70 01-JUN-07:10 401.35 16-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 84.46 26-JUN-18:53 228.49 08-JUN-23:00
July 732.70 03-JUL-07:10 395.88 28-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 138.87 16-JUL-12:00 236.24 03-JUL-03:00
August 732.70 01-AUG-07:10 413.91 28-AUG-15:00 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 59.56 02-AUG-15:53 284.72 27-AUG-17:55
September 732.70 01-SEP-07:10 415.78 21-SEP-15:00 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 46.84 10-SEP-14:45 256.63 22-SEP-02:00
October 732.70 02-OCT-07:10 441.36 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 8.98 11-OCT-14:00 508.27 29-OCT-09:00
November 732.70 01-NOV-07:10 449.59 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 7.21 05-NOV-14:53 493.30 01-NOV-04:00
December 732.70 01-DEC-08:09 449.59 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 6.65 02-DEC-12:25 936.97 21-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   395.88   738.04   0.00 0.00 0.00 0.00 0.00   228.49  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 138.87   975.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 266.70 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 220.37 12-JAN-07:00
February 434.65 01-FEB-08:09 264.48 06-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 327.95 24-FEB-19:03
March 434.65 01-MAR-08:09 258.56 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.14 14-MAR-13:00 650.63 19-MAR-07:00
April 434.65 03-APR-07:10 255.81 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 387.97 15-APR-05:00
May 434.65 01-MAY-07:10 242.84 01-MAY-07:19 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 12.89 17-MAY-14:43 249.30 18-MAY-18:03
June 434.65 01-JUN-07:10 242.96 16-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 47.91 26-JUN-18:44 172.77 08-JUN-21:55
July 434.65 03-JUL-07:10 243.28 12-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 85.53 16-JUL-12:00 169.89 03-JUL-03:00
August 434.65 01-AUG-07:10 245.53 21-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 39.71 02-AUG-15:53 217.94 27-AUG-17:55
September 434.65 01-SEP-07:10 250.91 25-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 27.68 10-SEP-13:00 171.28 22-SEP-02:00
October 434.65 02-OCT-07:10 261.82 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 5.98 11-OCT-14:00 345.44 29-OCT-09:00
November 434.65 01-NOV-07:10 266.70 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.01 05-NOV-13:00 334.24 01-NOV-04:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 1.39 02-DEC-12:35 624.76 21-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   242.84   437.82   0.00 0.00 0.00 0.00 0.00   169.89  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 85.53   650.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2181.51 14-JAN-08:51 4334.19 31-JAN-13:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1362.48 07-FEB-08:62 5154.09 12-FEB-13:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1389.81 23-MAR-06:53 5873.22 26-MAR-12:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1525.76 07-APR-03:55 6442.42 24-APR-12:30
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1259.30 13-MAY-05:33 6022.29 09-MAY-12:20
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1498.91 06-JUN-22:00 5692.92 22-JUN-12:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1103.80 01-JUL-05:33 5864.56 03-JUL-12:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1215.28 15-AUG-03:00 5635.89 13-AUG-11:50
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1362.25 28-SEP-06:53 5079.75 20-SEP-12:30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1505.77 14-OCT-07:22 5055.83 04-OCT-13:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1510.71 30-NOV-07:53 4722.79 12-NOV-12:30
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2177.28 23-DEC-08:51 3921.07 21-DEC-13:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1103.80   3921.07  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2181.51   6442.42  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1972.05 05-JAN-18:03 425.28 1107.07 778.87 0.00 0.00 0.00 0.00 0.00 0.00
February 1547.28 02-FEB-07:06 1420.81 1937.36 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
March 1672.01 15-MAR-15:55 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
April 1428.15 03-APR-06:06 1420.81 1937.36 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
May 5078.92 17-MAY-07:01 6765.77 4151.53 6815.12 0.00 0.00 0.00 0.00 0.00 0.00
June 5336.62 09-JUN-07:02 5799.23 3558.46 5841.53 0.00 0.00 0.00 0.00 0.00 0.00
July 5512.04 03-JUL-07:02 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
August 5446.68 17-AUG-07:02 5799.23 3558.46 5841.53 0.00 0.00 0.00 0.00 0.00 0.00
September 5480.22 15-SEP-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
October 5332.89 11-OCT-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
November 1685.15 29-NOV-18:13 318.96 830.30 584.15 0.00 0.00 0.00 0.00 0.00 0.00
December 2242.55 21-DEC-18:01 744.23 1937.36 1363.02 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1428.15   318.96 830.30 584.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5512.04   6765.77 4151.53 6815.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3142.42 20-JAN-14:37 2198.10 984.47 2214.13 0.00 0.00 0.00 0.00 0.00 70.99
February 2239.20 27-FEB-14:15 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 260.63
March 3611.47 15-MAR-14:05 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 62.37
April 1482.28 21-APR-12:10 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 188.37
May 1878.05 18-MAY-14:10 732.70 328.16 738.04 0.00 0.00 0.00 0.00 0.00 1.22
June 5512.70 26-JUN-07:02 4396.19 2138.67 4428.26 0.00 0.00 0.00 0.00 0.00 58.89
July 5485.07 17-JUL-06:01 1077.07 1282.21 2583.15 0.00 0.00 0.00 0.00 0.00 495.28
August 5659.10 21-AUG-06:02 923.20 1127.70 2214.13 0.00 0.00 0.00 0.00 0.00 805.40
September 5724.76 05-SEP-07:02 3663.49 1895.66 3690.21 0.00 0.00 0.00 0.00 0.00 216.75
October 5453.23 10-OCT-12:10 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 24.26
November 4729.87 07-NOV-13:55 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 39.99
December 2566.62 14-DEC-14:25 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 156.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1482.28   732.70 328.16 738.04 0.00 0.00 0.00 0.00 0.00 1.22
Maximum of Months 5724.76   4396.19 2138.67 4428.26 0.00 0.00 0.00 0.00 0.00 805.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 509.96 05-JAN-18:03 191.24 497.84 350.25 0.00 0.00 0.00 0.00 0.00 27.80
February 506.00 06-FEB-06:04 430.30 613.41 1970.17 0.00 0.00 0.00 0.00 0.00 234.09
March 1089.22 15-MAR-10:04 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 5.10
April 1004.06 21-APR-08:54 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 21.22
May 4294.14 17-MAY-07:01 3042.52 1362.66 3064.72 0.00 0.00 0.00 0.00 0.00 11.81
June 4498.65 09-JUN-07:02 2607.88 1168.00 2626.90 0.00 0.00 0.00 0.00 0.00 13.57
July 4481.57 03-JUL-07:02 2173.23 984.45 2189.08 0.00 0.00 0.00 0.00 0.00 6.32
August 4464.46 21-AUG-06:02 547.65 593.10 1313.45 0.00 0.00 0.00 0.00 0.00 11.46
September 4432.18 05-SEP-07:02 2173.23 1071.11 2189.08 0.00 0.00 0.00 0.00 0.00 17.63
October 1887.26 11-OCT-10:04 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 2.16
November 688.33 09-NOV-13:13 1303.94 593.59 1313.45 0.00 0.00 0.00 0.00 0.00 1.10
December 684.63 21-DEC-18:01 334.68 871.22 612.94 0.00 0.00 0.00 0.00 0.00 145.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 506.00   191.24 497.84 350.25 0.00 0.00 0.00 0.00 0.00 1.10
Maximum of Months 4498.65   3042.52 1362.66 3064.72 0.00 0.00 0.00 0.00 0.00 234.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1202.49 05-JAN-18:03 322.39 839.23 590.43 0.00 0.00 0.00 0.00 0.00 41.67
February 997.39 02-FEB-06:04 564.18 804.25 2583.15 0.00 0.00 0.00 0.00 0.00 206.21
March 959.81 02-MAR-06:04 564.18 804.25 2583.15 0.00 0.00 0.00 0.00 0.00 160.63
April 908.37 03-APR-05:04 725.37 1034.04 3321.19 0.00 0.00 0.00 0.00 0.00 85.01
May 1540.54 18-MAY-14:55 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 2.61
June 5106.27 15-JUN-07:02 4396.19 1992.41 4428.26 0.00 0.00 0.00 0.00 0.00 13.37
July 5235.87 03-JUL-07:02 3663.49 1834.61 3690.21 0.00 0.00 0.00 0.00 0.00 9.28
August 5144.45 15-AUG-07:02 3663.49 1895.98 3690.21 0.00 0.00 0.00 0.00 0.00 29.95
September 5146.92 05-SEP-07:02 3663.49 1963.30 3690.21 0.00 0.00 0.00 0.00 0.00 27.08
October 1654.70 11-OCT-15:13 2930.79 1580.26 2952.17 0.00 0.00 0.00 0.00 5.01 0.00
November 1023.69 29-NOV-18:03 322.39 839.23 590.43 0.00 0.00 0.00 0.00 0.00 60.18
December 1464.42 21-DEC-18:01 564.18 1468.65 1033.26 0.00 0.00 0.00 0.00 0.00 218.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 908.37   322.39 656.31 590.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5235.87   4396.19 1992.41 4428.26 0.00 0.00 0.00 0.00 5.01 218.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 626.34 20-JAN-16:22 2173.23 1203.58 2189.08 0.00 0.00 0.00 0.00 0.00 6.97
February 410.70 02-FEB-06:04 334.68 477.09 1532.36 0.00 0.00 0.00 0.00 0.00 137.15
March 1583.18 15-MAR-15:55 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 8.55
April 1150.12 07-APR-15:53 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 0.00 14.49
May 1772.70 31-MAY-15:57 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 7.97 0.00
June 5503.38 05-JUN-07:01 3042.52 1652.49 3064.72 0.00 0.00 0.00 0.00 0.00 8.55
July 5572.54 03-JUL-07:02 2173.23 1158.54 2189.08 0.00 0.00 0.00 0.00 0.00 6.19
August 5587.55 21-AUG-06:02 547.65 697.35 1313.45 0.00 0.00 0.00 0.00 0.00 10.80
September 5560.04 11-SEP-06:01 638.93 841.02 1532.36 0.00 0.00 0.00 0.00 0.00 10.40
October 2751.18 11-OCT-15:54 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.24 0.00
November 1423.37 07-NOV-15:53 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 2.61
December 566.29 21-DEC-18:01 334.68 871.22 612.94 0.00 0.00 0.00 0.00 0.00 145.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 410.70   334.68 477.09 612.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5587.55   3042.52 1652.49 3064.72 0.00 0.00 0.00 0.00 7.97 145.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1087.78 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 546.89 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 434.25 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 599.87 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 401.87 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 647.20 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 799.59 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 420.45 0.00
September 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.32 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 411.76 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 563.80 0.00
December 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.81 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.32 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.81 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.148728E+11 17956.77 31-JAN-08:30 0.205933E+10 32064.81 05-JAN-07:10
February 0.139865E+11 17363.17 06-FEB-16:00 0.189438E+10 26745.43 06-FEB-07:10
March 0.144996E+11 19092.54 20-MAR-07:30 0.658644E+09 15767.84 29-MAR-06:10
April 0.122901E+11 17998.94 03-APR-07:30 0.477342E+09 21250.07 03-APR-06:10
May 0.117475E+11 13848.26 02-MAY-07:19 18661958.03 6909.71 02-MAY-06:10
June 0.133603E+11 15885.10 26-JUN-15:20 0.00 0.00 01-JUN-00:10
July 0.128441E+11 15439.32 17-JUL-12:20 0.00 0.00 01-JUL-00:10
August 0.141128E+11 15365.40 16-AUG-15:20 0.00 0.00 01-AUG-00:10
September 0.125068E+11 14509.85 12-SEP-15:50 158621.08 264.37 22-SEP-07:10
October 0.129056E+11 17329.14 31-OCT-07:00 0.470558E+09 19022.20 30-OCT-06:10
November 0.134245E+11 17515.76 29-NOV-08:30 0.695594E+09 20900.71 30-NOV-07:10
December 0.135243E+11 16234.44 26-DEC-08:09 0.610974E+10 32064.81 21-DEC-07:10
             
Annual Sum or Average 0.160075E+12     0.123844E+11    
Minimum of Months 0.117475E+11 13848.26   0.00 0.00  
Maximum of Months 0.148728E+11 19092.54   0.610974E+10 32064.81  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.226047E+10 0.110138E+10 0.405300E+10 0.00 0.206608E+10 0.02 0.320819E+10 63286257.90 0.00 0.00 0.00 0.212041E+10 0.00
February 0.203099E+10 0.891080E+09 0.366466E+10 0.00 0.193824E+10 0.01 0.351606E+10 22814845.42 0.00 0.00 0.00 0.192263E+10 0.00
March 0.231882E+10 0.841797E+09 0.429420E+10 0.00 0.219153E+10 0.00 0.253282E+10 0.152790E+09 0.00 0.00 0.00 0.216759E+10 0.00
April 0.207805E+10 0.683684E+09 0.388642E+10 0.00 0.187879E+10 0.00 0.167610E+10 64389960.86 0.00 0.00 0.00 0.202262E+10 0.00
May 0.218101E+10 0.614281E+09 0.417360E+10 0.00 0.199227E+10 0.00 0.206314E+09 0.492094E+09 0.00 0.00 0.00 0.208798E+10 0.00
June 0.214746E+10 0.556303E+09 0.412149E+10 0.00 0.199348E+10 0.00 0.00 0.253691E+10 0.00 0.00 0.00 0.200464E+10 0.00
July 0.207070E+10 0.589672E+09 0.393546E+10 0.00 0.181340E+10 0.00 0.00 0.244038E+10 0.00 0.00 0.00 0.199445E+10 0.00
August 0.226816E+10 0.662450E+09 0.429420E+10 0.00 0.208368E+10 0.00 0.00 0.275801E+10 0.00 0.00 0.00 0.204633E+10 0.00
September 0.208891E+10 0.752658E+09 0.388029E+10 0.00 0.181421E+10 0.00 21748048.18 0.200389E+10 0.00 0.00 0.00 0.194513E+10 0.00
October 0.222736E+10 0.926395E+09 0.405607E+10 0.00 0.190465E+10 0.00 0.118351E+10 0.566761E+09 0.00 0.00 0.00 0.204090E+10 0.00
November 0.222721E+10 0.102730E+10 0.400396E+10 0.00 0.191298E+10 0.00 0.204515E+10 0.188846E+09 0.00 0.00 0.00 0.201905E+10 0.00
December 0.220957E+10 0.113789E+10 0.393240E+10 0.00 0.211604E+10 0.00 0.200517E+10 44591774.62 0.00 0.00 0.00 0.207861E+10 0.00
                           
Annual Sum or Average 0.261087E+11 0.978489E+10 0.482958E+11 0.00 0.237053E+11 0.03 0.163951E+11 0.113348E+11 0.00 0.00 0.00 0.244503E+11 0.00
Minimum of Months 0.203099E+10 0.556303E+09 0.366466E+10 0.00 0.181340E+10 0.00 0.00 22814845.42 0.00 0.00 0.00 0.192263E+10 0.00
Maximum of Months 0.231882E+10 0.113789E+10 0.429420E+10 0.00 0.219153E+10 0.02 0.351606E+10 0.275801E+10 0.00 0.00 0.00 0.216759E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.205933E+10 0.00 0.00 0.00 0.00
February 0.00 0.00 0.189438E+10 0.00 0.00 0.00 0.00
March 0.00 0.00 0.658644E+09 0.00 0.00 0.00 0.00
April 0.00 0.00 0.477342E+09 0.00 0.00 0.00 0.00
May 0.00 0.00 18661958.03 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 158621.08 0.00 0.00 0.00 0.00
October 0.00 0.00 0.470558E+09 0.00 0.00 0.00 0.00
November 0.00 0.00 0.695594E+09 0.00 0.00 0.00 0.00
December 0.00 0.00 0.610974E+10 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.123844E+11 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.610974E+10 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2025.66 02-JAN-16:49 1049.10 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1934.99 02-JAN-06:19 0.00 05-JAN-08:09 8823.00 17-JAN-07:30
February 2013.83 06-FEB-16:00 1049.10 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1934.99 01-FEB-06:19 0.00 01-FEB-11:20 8333.83 21-FEB-07:30
March 1978.18 21-MAR-07:10 1049.10 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1934.99 01-MAR-06:10 0.00 01-MAR-00:10 9374.48 20-MAR-06:30
April 1960.48 03-APR-07:10 1049.10 01-APR-05:10 3325.31 03-APR-07:10 0.00 1934.99 03-APR-05:19 0.00 01-APR-00:10 8072.49 24-APR-06:19
May 1846.28 19-MAY-07:10 659.04 01-MAY-18:49 3325.31 01-MAY-07:10 0.00 1934.99 01-MAY-05:10 0.00 01-MAY-00:10 6396.24 02-MAY-06:30
June 1870.64 16-JUN-07:10 659.04 01-JUN-19:19 3325.31 01-JUN-07:10 0.00 1934.99 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 1853.44 28-JUL-07:10 659.04 01-JUL-19:30 3325.31 03-JUL-07:10 0.00 1934.99 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 1906.71 28-AUG-15:00 1049.10 10-AUG-05:10 3325.31 01-AUG-07:10 0.00 1934.99 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 1908.77 21-SEP-15:00 1049.10 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1934.99 01-SEP-05:10 0.00 01-SEP-00:10 1459.78 22-SEP-06:10
October 1997.78 30-OCT-07:10 1049.10 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1934.99 02-OCT-05:10 0.00 01-OCT-00:10 7676.58 31-OCT-06:30
November 2025.66 06-NOV-16:49 1049.10 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1934.99 01-NOV-05:10 0.00 01-NOV-00:10 8367.32 01-NOV-06:30
December 2025.66 01-DEC-16:30 1049.10 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1934.99 01-DEC-06:10 0.00 01-DEC-00:10 7244.28 26-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 1846.28   659.04   3325.31   0.00 1934.99   0.00   0.00  
Maximum of Months 2025.66   1049.10   3325.31   0.00 1934.99   0.00   9374.48  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 825.10 20-JAN-15:30 0.00 0.00 0.00 2821.26 30-JAN-12:50 0.00
February 447.55 27-FEB-14:20 0.00 0.00 0.00 2821.78 13-FEB-12:30 0.00
March 1718.51 15-MAR-15:30 0.00 0.00 0.00 2821.07 01-MAR-12:09 0.00
April 860.54 20-APR-12:00 0.00 0.00 0.00 2815.48 03-APR-11:00 0.00
May 2486.81 17-MAY-14:09 0.00 0.00 0.00 2807.17 01-MAY-11:50 0.00
June 6175.75 26-JUN-15:09 0.00 0.00 0.00 2797.14 01-JUN-11:09 0.00
July 5741.24 17-JUL-12:09 0.00 0.00 0.00 2788.57 03-JUL-11:30 0.00
August 5775.08 16-AUG-15:00 0.00 0.00 0.00 2784.30 28-AUG-11:39 0.00
September 4827.14 12-SEP-15:00 0.00 0.00 0.00 2789.17 29-SEP-11:09 0.00
October 3426.02 11-OCT-14:50 0.00 0.00 0.00 2798.11 31-OCT-11:39 0.00
November 1725.60 07-NOV-15:09 0.00 0.00 0.00 2807.92 30-NOV-12:09 0.00
December 636.99 04-DEC-15:20 0.00 0.00 0.00 2816.03 29-DEC-12:39 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 447.55   0.00 0.00 0.00 2784.30   0.00
Maximum of Months 6175.75   0.00 0.00 0.00 2821.78   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17956.77 31-JAN-08:30 1963.22 3325.31 0.00 0.00 1934.99 0.00 7990.10 0.00 0.00
February 17363.17 06-FEB-16:00 2013.83 3325.31 0.00 0.00 1934.99 0.00 7314.90 0.00 0.00
March 19092.54 20-MAR-07:30 1937.88 3325.31 0.00 0.00 1934.99 0.00 9264.13 0.00 0.00
April 17998.94 03-APR-07:30 1945.09 3325.31 0.00 0.00 1934.99 0.00 8053.16 0.00 0.00
May 13848.26 02-MAY-07:19 1708.57 3325.31 0.00 0.00 1934.99 0.00 5690.97 0.00 0.00
June 15885.10 26-JUN-15:20 1700.87 3325.31 0.00 0.00 1934.99 0.00 0.00 6172.07 0.00
July 15439.32 17-JUL-12:20 1667.62 3325.31 0.00 0.00 1934.99 0.00 0.00 5738.02 0.00
August 15365.40 16-AUG-15:20 1744.48 3325.31 0.00 0.00 1934.99 0.00 0.00 5613.27 0.00
September 14509.85 12-SEP-15:50 1720.90 3325.31 0.00 0.00 1934.99 0.00 0.00 4780.17 0.00
October 17329.14 31-OCT-07:00 1887.29 3325.31 0.00 0.00 1934.99 0.00 7449.96 0.00 0.00
November 17515.76 29-NOV-08:30 1951.84 3325.31 0.00 0.00 1934.99 0.00 7567.24 0.00 0.00
December 16234.44 26-DEC-08:09 1770.63 3325.31 0.00 0.00 1934.99 0.00 6463.04 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 13848.26   1667.62 3325.31 0.00 0.00 1934.99 0.00 0.00 0.00 0.00
Maximum of Months 19092.54   2013.83 3325.31 0.00 0.00 1934.99 0.00 9264.13 6172.07 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 32064.81 05-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 26745.43 06-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 15767.84 29-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 21250.07 03-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 6909.71 02-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 264.37 22-SEP-07:10 0.00 0.00 0.00
October 0.00 0.00 19022.20 30-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 20900.71 30-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 32064.81 21-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 32064.81   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.08 0.17 19.08 0.00 19.08 0.00 19.08
February 0.17 19.38 0.17 19.38 0.00 19.38 0.00 19.38
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 24.60 0.83 24.60
August 0.00 0.00 0.00 0.00 0.33 24.48 0.33 24.48
September 0.00 0.00 0.00 0.00 0.17 24.56 0.17 24.56
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 19.39 1.00 19.39 0.00 19.39 0.00 19.39
                 
Annual Sum or Average 1.33 19.35 1.33 19.35 1.33 21.09 1.33 21.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.39 1.00 19.39 0.83 24.60 0.83 24.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 18.63 4.33 18.70 0.00 18.70 0.00 18.70
February 14.67 15.87 4.17 16.52 0.00 16.52 0.00 16.52
March 4.83 15.41 0.67 15.88 0.00 15.88 0.00 15.88
April 4.83 16.83 2.33 17.52 0.00 17.52 0.00 17.52
May 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 24.55 0.67 24.55
August 0.00 0.00 0.00 0.00 0.33 24.58 0.33 24.58
September 0.00 0.00 0.00 0.00 5.00 25.52 4.33 25.19
October 0.67 19.24 0.67 19.24 6.33 23.88 6.17 24.25
November 1.00 19.12 1.00 19.12 0.00 19.12 0.00 19.12
December 23.00 17.20 15.17 17.70 0.00 17.70 0.00 17.70
                 
Annual Sum or Average 53.67 16.83 28.50 17.47 12.33 18.46 11.50 19.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23.00 19.43 15.17 19.43 6.33 25.52 6.17 25.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.67 14.91 0.33 14.96 0.00 14.96 0.00 14.96
February 18.67 14.52 0.17 14.53 0.00 14.53 0.00 14.53
March 11.33 14.73 0.00 14.73 0.00 14.73 0.00 14.73
April 5.67 14.83 0.00 14.83 0.00 14.83 0.00 14.83
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 14.96 0.00 14.96 0.00 14.96 0.00 14.96
December 25.50 15.00 3.17 15.30 0.00 15.30 0.00 15.30
                 
Annual Sum or Average 75.17 14.81 3.67 14.94 0.00 14.94 0.00 14.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25.50 15.00 3.17 15.30 0.00 15.30 0.00 15.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 20.83 14.86 0.33 14.94 0.00 14.94 0.00 14.94
February 21.33 14.72 0.67 14.85 0.00 14.85 0.00 14.85
March 12.33 14.79 0.00 14.79 0.00 14.79 0.00 14.79
April 5.50 14.87 0.00 14.87 0.00 14.87 0.00 14.87
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 14.99 0.00 14.99 0.00 14.99 0.00 14.99
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 31.67 15.18 3.83 15.60 0.00 15.60 0.00 15.60
                 
Annual Sum or Average 92.00 14.93 4.83 15.14 0.00 15.14 0.00 15.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.67 15.18 3.83 15.60 0.00 15.60 0.00 15.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.67 14.95 0.33 15.03 0.00 15.03 0.00 15.03
February 17.17 14.53 0.17 14.54 0.00 14.54 0.00 14.54
March 11.17 14.73 0.00 14.73 0.00 14.73 0.00 14.73
April 6.50 14.83 0.00 14.83 0.00 14.83 0.00 14.83
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.67 30.11 0.17 30.10
July 0.00 0.00 0.00 0.00 1.50 30.12 0.00 30.12
August 0.00 0.00 0.00 0.00 0.33 30.23 0.00 30.23
September 0.00 0.00 0.00 0.00 0.50 30.27 0.00 30.27
October 0.17 14.99 0.00 14.99 0.00 14.99 0.00 14.99
November 0.17 14.96 0.00 14.96 0.00 14.96 0.00 14.96
December 26.33 15.03 2.83 15.36 0.00 15.36 0.00 15.36
                 
Annual Sum or Average 74.17 14.84 3.33 14.98 3.00 15.55 0.17 15.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26.33 15.03 2.83 15.36 1.50 30.27 0.17 30.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 21.16 159.50 20.88 159.50 20.73
February 323.00 20.90 181.00 20.69 181.00 20.59
March 386.00 21.78 119.00 21.43 119.00 21.21
April 340.00 22.07 67.67 21.78 67.67 21.58
May 246.67 23.25 42.33 23.33 12.17 23.24
June 17.17 25.65 331.83 25.00 17.17 25.03
July 31.50 25.76 339.50 25.00 31.50 25.06
August 13.67 25.90 359.00 25.01 13.67 25.04
September 24.50 23.99 226.00 24.99 1.33 25.00
October 223.17 22.66 44.83 22.57 28.50 22.35
November 356.17 21.95 77.33 21.64 77.33 21.43
December 340.00 21.03 190.67 20.80 190.67 20.69
             
Annual Sum or Average 2658.83 21.88 2138.67 22.45 899.50 22.18
Minimum of Months 13.67 20.90 42.33 20.69 1.33 20.59
Maximum of Months 386.00 25.90 359.00 25.01 190.67 25.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 346.50 21.20 175.17 20.75 175.17 20.53
February 321.67 20.99 190.83 20.59 190.83 20.40
March 370.17 21.35 199.00 20.89 199.00 20.67
April 340.00 21.30 182.17 20.89 182.17 20.70
May 362.00 22.48 69.50 22.11 69.50 21.85
June 57.67 23.84 168.33 24.95 8.50 24.95
July 43.17 24.40 248.17 24.86 31.33 24.84
August 20.83 24.11 279.17 25.01 4.33 25.02
September 52.83 23.33 201.67 24.83 4.33 24.82
October 215.83 21.80 125.00 21.79 83.33 21.46
November 303.67 21.57 120.33 21.13 118.83 20.87
December 336.00 20.89 204.33 20.46 204.33 20.26
             
Annual Sum or Average 2770.33 21.59 2163.67 21.86 1271.67 21.51
Minimum of Months 20.83 20.89 69.50 20.46 4.33 20.26
Maximum of Months 370.17 24.40 279.17 25.01 204.33 25.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.04 256.00 19.88 256.00 19.83
February 266.00 19.81 242.50 19.72 242.50 19.68
March 322.00 20.86 220.50 20.45 220.50 20.28
April 280.00 21.23 145.17 20.75 145.17 20.51
May 272.50 22.76 48.50 22.44 43.67 22.16
June 8.67 25.60 247.83 25.29 3.67 25.33
July 22.33 25.91 263.67 25.19 22.33 25.24
August 4.50 25.31 270.83 25.25 2.67 25.26
September 42.67 23.37 151.17 24.83 2.00 24.79
October 272.17 22.16 87.67 21.63 86.33 21.30
November 294.00 20.86 180.67 20.45 180.67 20.26
December 280.00 19.86 258.33 19.77 258.33 19.73
             
Annual Sum or Average 2358.83 21.05 2372.83 21.49 1463.83 21.11
Minimum of Months 4.50 19.81 48.50 19.72 2.00 19.68
Maximum of Months 322.00 25.91 270.83 25.29 258.33 25.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.03 346.17 20.00 346.17 19.99
February 323.00 19.90 323.00 19.90 323.00 19.90
March 391.00 20.56 315.17 20.35 315.17 20.27
April 340.00 20.82 235.00 20.56 235.00 20.45
May 362.00 22.54 66.17 22.19 66.17 21.93
June 32.00 24.14 193.17 25.17 3.50 25.20
July 18.67 24.47 256.17 24.91 18.17 24.88
August 23.67 24.01 230.50 25.00 2.50 25.00
September 120.50 23.55 105.33 24.27 2.00 24.24
October 354.17 21.92 122.00 21.46 122.00 21.18
November 357.00 20.60 273.33 20.37 273.33 20.28
December 340.00 19.95 333.00 19.93 333.00 19.92
             
Annual Sum or Average 3019.00 21.00 2799.00 21.22 2040.00 20.92
Minimum of Months 18.67 19.90 66.17 19.90 2.00 19.90
Maximum of Months 391.00 24.47 346.17 25.17 346.17 25.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.51 283.17 20.29 283.17 20.20
February 323.00 20.31 275.33 20.16 275.33 20.10
March 381.00 21.20 245.83 20.81 244.00 20.63
April 333.17 21.51 171.83 21.10 169.83 20.89
May 308.50 22.85 77.00 22.74 49.67 22.48
June 57.83 27.69 244.83 26.11 46.67 26.44
July 43.17 27.35 282.33 25.54 43.17 25.75
August 55.33 27.69 291.50 25.87 46.33 26.17
September 81.00 24.25 178.67 25.13 14.17 25.24
October 291.33 22.24 114.00 21.95 91.33 21.61
November 355.67 21.27 201.50 20.85 201.50 20.65
December 340.00 20.32 290.33 20.14 290.33 20.08
             
Annual Sum or Average 2927.00 21.66 2656.33 21.93 1755.50 21.65
Minimum of Months 43.17 20.31 77.00 20.14 14.17 20.08
Maximum of Months 381.00 27.69 291.50 26.11 290.33 26.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 3168771.54 689555.85 6.72 3168744.50 27.04 0.00 0.06 25-JAN-16:10 0.00 01-JAN-00:03 274.43 25-JAN-16:10 274.43 25-JAN-16:10 0.08 24-JAN-16:50 59.51 25-JAN-16:10 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.163429E+09 34661778.96 49.10 0.159821E+09 3608297.87 0.00 0.38 15-MAR-14:00 0.00 01-MAR-00:10 1800.06 15-MAR-14:00 1800.06 15-MAR-14:00 205.10 17-MAR-14:33 375.25 14-MAR-14:54 0.00
April 77812336.01 16664888.44 36.08 73491832.82 4320503.19 0.00 0.24 21-APR-13:30 0.00 01-APR-00:10 1094.75 21-APR-13:20 1051.79 21-APR-13:43 160.96 28-APR-15:05 231.55 21-APR-13:20 0.00
May 0.822626E+09 0.176523E+09 162.68 0.745280E+09 77345897.98 0.00 1.00 17-MAY-07:01 0.00 01-MAY-00:10 5309.60 18-MAY-07:02 5264.69 17-MAY-07:01 467.40 22-MAY-13:15 991.50 18-MAY-07:02 0.00
June 0.289424E+10 0.639750E+09 233.87 0.268743E+10 0.206818E+09 0.00 1.00 02-JUN-07:02 0.00 01-JUN-00:10 5746.87 21-JUN-07:02 5382.99 27-JUN-06:02 1778.52 21-JUN-07:13 1305.00 26-JUN-14:55 0.00
July 0.295353E+10 0.635335E+09 217.95 0.267198E+10 0.281548E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5797.73 28-JUL-07:03 5455.77 18-JUL-06:02 2009.17 28-JUL-07:15 1248.18 17-JUL-13:00 0.00
August 0.317928E+10 0.685734E+09 246.93 0.292179E+10 0.257489E+09 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 5786.71 04-AUG-07:02 5434.58 21-AUG-06:02 1855.65 04-AUG-07:07 1219.97 16-AUG-14:00 0.00
September 0.230012E+10 0.483703E+09 206.54 0.219976E+10 0.100364E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:05 5538.40 06-SEP-07:02 5361.44 11-SEP-06:01 1023.78 06-SEP-07:15 1091.44 11-SEP-12:20 0.00
October 0.705238E+09 0.147430E+09 130.69 0.678420E+09 26817580.13 0.00 1.00 11-OCT-07:03 0.00 01-OCT-00:10 5202.67 11-OCT-07:03 5202.67 11-OCT-07:03 309.04 03-OCT-13:20 967.94 11-OCT-07:03 0.00
November 0.124990E+09 26436965.20 40.90 0.122015E+09 2974735.60 0.00 0.35 09-NOV-14:00 0.00 01-NOV-00:10 1688.48 09-NOV-14:00 1620.04 09-NOV-13:57 115.23 09-NOV-17:00 351.17 09-NOV-14:00 0.00
December 8932.71 1954.36 0.21 8932.71 -0.0 0.00 0.00 04-DEC-15:53 0.00 01-DEC-00:05 14.28 04-DEC-15:53 14.28 04-DEC-15:53 0.00 04-DEC-15:53 3.12 04-DEC-15:53 0.00
                                       
Annual Sum or Average 0.132244E+11 0.284693E+10 1331.66 0.122632E+11 0.961286E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.317928E+10 0.685734E+09 246.93 0.292179E+10 0.281548E+09 0.00 1.00   0.00   5797.73   5455.77   2009.17   1305.00   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.288653E+09 59342515.98 52.82 0.288531E+09 122619.12 0.00 0.62 20-JAN-14:15 0.00 01-JAN-00:03 3404.40 20-JAN-14:15 3404.40 20-JAN-14:15 20.14 10-JAN-15:20 675.59 20-JAN-14:15 0.00
February 0.106620E+09 22454492.54 33.58 0.106620E+09 0.00 0.00 0.41 27-FEB-14:15 0.00 01-FEB-00:10 2179.64 27-FEB-14:15 2179.64 27-FEB-14:15 0.00 27-FEB-15:13 447.57 27-FEB-14:15 0.00
March 0.375618E+09 77397517.20 63.77 0.375618E+09 0.00 0.00 0.71 14-MAR-13:30 0.00 01-MAR-00:10 3890.14 15-MAR-13:55 3890.14 15-MAR-13:55 0.00 16-MAR-15:40 794.47 14-MAR-13:30 0.00
April 93395907.23 19867685.05 32.63 93350034.61 45872.61 0.00 0.29 20-APR-13:00 0.00 01-APR-00:10 1520.08 20-APR-13:00 1520.08 20-APR-13:00 14.27 28-APR-14:40 323.12 20-APR-13:00 0.00
May 0.354884E+09 79046727.37 92.18 0.351068E+09 3816146.04 0.00 0.48 17-MAY-14:00 0.00 01-MAY-00:10 2479.55 17-MAY-13:50 2479.55 17-MAY-13:50 109.46 30-MAY-16:00 590.34 17-MAY-13:50 0.00
June 0.226126E+10 0.527121E+09 217.79 0.217679E+10 84472823.66 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 6091.13 19-JUN-07:02 6004.81 26-JUN-07:02 928.10 22-JUN-07:02 1424.04 26-JUN-16:08 0.00
July 0.232507E+10 0.525272E+09 198.02 0.219548E+10 0.129590E+09 0.00 1.00 10-JUL-07:02 0.00 01-JUL-00:10 6311.86 24-JUL-07:02 5983.71 18-JUL-06:02 1304.85 26-JUL-07:02 1364.67 17-JUL-12:00 0.00
August 0.296656E+10 0.660959E+09 227.73 0.284888E+10 0.117682E+09 0.00 1.00 03-AUG-07:02 0.00 01-AUG-00:10 6502.12 04-AUG-07:02 6085.55 21-AUG-06:02 2171.15 04-AUG-07:02 1398.90 16-AUG-16:08 0.00
September 0.266461E+10 0.561750E+09 199.84 0.263686E+10 27754151.73 0.00 1.00 05-SEP-07:02 0.00 01-SEP-00:05 6130.63 06-SEP-07:02 6019.17 13-SEP-07:02 775.82 06-SEP-07:02 1287.74 12-SEP-16:05 0.00
October 0.117143E+10 0.234322E+09 122.30 0.116979E+10 1648903.23 0.00 1.00 10-OCT-10:53 0.00 01-OCT-00:10 5783.74 10-OCT-11:00 5783.74 10-OCT-11:00 144.07 03-OCT-11:00 1178.25 11-OCT-14:00 0.00
November 0.624967E+09 0.125990E+09 81.55 0.624930E+09 37514.98 0.00 0.89 07-NOV-13:55 0.00 01-NOV-00:10 5056.31 07-NOV-13:55 5056.31 07-NOV-13:55 12.23 14-NOV-16:40 974.76 07-NOV-13:55 0.00
December 0.207528E+09 43089796.87 42.43 0.207528E+09 -0.0 0.00 0.51 01-DEC-14:25 0.00 01-DEC-00:05 2720.49 01-DEC-14:25 2720.49 01-DEC-14:25 0.00 15-DEC-15:50 553.90 01-DEC-14:25 0.00
                                       
Annual Sum or Average 0.134406E+11 0.293661E+10 1364.62 0.130754E+11 0.365171E+09 0.00                         0.00
Minimum of Months 93395907.23 19867685.05 32.63 93350034.61 -0.0 0.00 0.29   0.00   1520.08   1520.08   0.00   323.12   0.00
Maximum of Months 0.296656E+10 0.660959E+09 227.73 0.284888E+10 0.129590E+09 0.00 1.00   0.00   6502.12   6085.55   2171.15   1424.04   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 87030677.75 18666172.28 39.90 87030677.75 -0.0 0.00 0.29 14-MAR-10:05 0.00 01-MAR-00:10 1189.96 14-MAR-10:05 1189.96 14-MAR-10:05 0.00 13-MAR-08:40 249.24 14-MAR-10:05 0.00
April 83439969.42 17875191.69 47.27 83437355.73 2613.69 0.00 0.24 21-APR-08:54 0.00 01-APR-00:10 997.02 21-APR-08:54 997.02 21-APR-08:54 1.41 13-APR-15:40 210.30 21-APR-08:54 0.00
May 0.423791E+09 93059346.58 148.32 0.417624E+09 6166925.20 0.00 1.00 17-MAY-07:01 0.00 01-MAY-00:10 4723.18 17-MAY-07:01 4723.18 17-MAY-07:01 141.95 31-MAY-08:41 880.87 17-MAY-07:01 0.00
June 0.198225E+10 0.452453E+09 235.75 0.192552E+10 56732809.32 0.00 1.00 05-JUN-07:01 0.00 01-JUN-00:10 5118.76 21-JUN-07:02 4869.68 26-JUN-06:02 1183.29 21-JUN-07:02 985.50 26-JUN-15:00 0.00
July 0.184074E+10 0.414731E+09 220.12 0.176435E+10 76387878.86 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5169.05 28-JUL-07:03 4833.10 18-JUL-06:02 1537.85 28-JUL-07:03 1072.95 17-JUL-10:43 0.00
August 0.211673E+10 0.472462E+09 246.03 0.204266E+10 74071647.22 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 5153.27 04-AUG-07:02 4904.65 21-AUG-06:02 1348.48 04-AUG-07:12 958.58 04-AUG-07:02 0.00
September 0.147833E+10 0.321132E+09 200.74 0.146446E+10 13868941.32 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:05 4908.23 06-SEP-07:02 4825.27 13-SEP-07:02 459.62 06-SEP-07:12 918.51 06-SEP-07:02 0.00
October 0.323742E+09 69170727.62 106.34 0.323228E+09 514280.46 0.00 0.52 11-OCT-10:04 0.00 01-OCT-00:10 2201.69 11-OCT-10:04 2201.69 11-OCT-10:04 41.52 03-OCT-11:00 461.61 11-OCT-10:04 0.00
November 65084846.98 13948271.06 37.20 65084846.98 0.00 0.00 0.22 09-NOV-13:13 0.00 01-NOV-00:10 911.88 09-NOV-13:13 911.88 09-NOV-13:13 0.00 08-NOV-16:22 192.94 09-NOV-13:13 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.840115E+10 0.187350E+10 1281.66 0.817340E+10 0.227745E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.211673E+10 0.472462E+09 246.03 0.204266E+10 76387878.86 0.00 1.00   0.00   5169.05   4904.65   1537.85   1072.95   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 8322995.43 1818340.50 8.44 8322995.43 0.00 0.00 0.17 14-MAR-14:40 0.00 01-MAR-00:10 776.89 14-MAR-14:40 776.89 14-MAR-14:40 0.00 14-MAR-14:20 171.44 14-MAR-14:40 0.00
April 846094.66 184638.62 2.58 846094.66 0.00 0.00 0.03 20-APR-16:00 0.00 01-APR-00:10 132.97 20-APR-16:00 132.97 20-APR-16:00 0.00 20-APR-15:40 28.97 20-APR-16:00 0.00
May 0.266790E+09 59624411.44 88.16 0.260224E+09 6565751.61 0.00 0.45 17-MAY-14:00 0.00 01-MAY-00:10 2059.71 17-MAY-14:00 2059.71 17-MAY-14:00 106.12 24-MAY-16:00 492.10 17-MAY-14:00 0.00
June 0.213053E+10 0.491018E+09 224.29 0.204267E+10 87862374.45 0.00 1.00 05-JUN-07:01 0.00 01-JUN-00:10 5691.07 21-JUN-07:02 5318.93 26-JUN-07:02 1589.73 21-JUN-07:02 1277.09 26-JUN-14:55 0.00
July 0.212682E+10 0.477561E+09 205.59 0.200033E+10 0.126483E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5723.02 28-JUL-07:03 5328.05 06-JUL-07:01 1819.41 28-JUL-07:03 1217.37 17-JUL-13:00 0.00
August 0.221633E+10 0.500425E+09 231.65 0.210613E+10 0.110194E+09 0.00 1.00 02-AUG-07:02 0.00 01-AUG-00:10 5776.12 04-AUG-07:02 5320.99 21-AUG-07:02 1833.99 04-AUG-07:12 1128.59 16-AUG-15:53 0.00
September 0.148617E+10 0.325629E+09 187.92 0.146123E+10 24935627.71 0.00 1.00 05-SEP-07:02 0.00 01-SEP-00:05 5431.18 06-SEP-07:02 5343.20 13-SEP-07:02 571.27 06-SEP-07:02 1016.34 06-SEP-07:02 0.00
October 0.160153E+09 34847387.25 57.68 0.159985E+09 168216.34 0.00 0.46 11-OCT-14:25 0.00 01-OCT-00:10 2128.73 11-OCT-14:35 2128.73 11-OCT-14:35 26.11 03-OCT-14:00 483.45 11-OCT-14:00 0.00
November 11594998.09 2498846.45 9.32 11594998.09 -0.0 0.00 0.16 09-NOV-14:00 0.00 01-NOV-00:10 702.68 09-NOV-13:57 702.68 09-NOV-13:57 0.00 08-NOV-15:32 150.24 09-NOV-13:57 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.840754E+10 0.189361E+10 1015.64 0.805133E+10 0.356210E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.221633E+10 0.500425E+09 231.65 0.210613E+10 0.126483E+09 0.00 1.00   0.00   5776.12   5343.20   1833.99   1277.09   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 15097386.40 3254186.07 10.46 15097386.40 -0.0 0.00 0.16 20-JAN-15:58 0.00 01-JAN-00:03 844.54 20-JAN-15:58 844.54 20-JAN-15:58 0.00 20-JAN-14:25 180.39 20-JAN-15:58 0.00
February 1665237.52 360352.87 1.33 1665237.52 -0.0 0.00 0.09 17-FEB-16:38 0.00 01-FEB-00:10 462.22 17-FEB-16:38 462.22 17-FEB-16:38 0.00 17-FEB-15:58 99.82 17-FEB-16:38 0.00
March 94076775.52 20246357.16 36.47 94076775.52 -0.0 0.00 0.35 15-MAR-15:55 0.00 01-MAR-00:10 1875.96 15-MAR-15:55 1875.96 15-MAR-15:55 0.00 31-MAR-14:45 389.22 15-MAR-15:55 0.00
April 45505716.27 9797557.06 28.44 45244809.28 260906.99 0.00 0.28 07-APR-16:00 0.00 01-APR-00:10 1500.07 07-APR-16:00 1500.07 07-APR-16:00 47.73 28-APR-15:10 314.51 07-APR-16:00 0.00
May 0.377025E+09 83840343.45 129.92 0.366659E+09 10365822.34 0.00 0.44 31-MAY-15:53 0.00 01-MAY-00:10 2427.24 31-MAY-15:53 2324.11 31-MAY-15:57 167.59 22-MAY-15:53 564.69 31-MAY-15:53 0.00
June 0.179473E+10 0.426564E+09 239.91 0.173198E+10 62751448.02 0.00 1.00 05-JUN-07:01 0.00 01-JUN-00:10 6639.50 21-JUN-07:02 6219.74 06-JUN-07:02 1686.23 21-JUN-07:02 1284.54 26-JUN-16:05 0.00
July 0.166620E+10 0.387479E+09 220.43 0.157920E+10 87007870.24 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 6514.82 26-JUL-07:02 6242.14 18-JUL-06:02 1746.74 31-JUL-07:02 1265.42 24-JUL-07:02 0.00
August 0.188481E+10 0.438430E+09 250.30 0.180680E+10 78007234.37 0.00 1.00 03-AUG-07:02 0.00 01-AUG-00:10 6695.56 04-AUG-07:02 6338.02 21-AUG-06:02 1798.28 04-AUG-07:02 1243.21 04-AUG-07:02 0.00
September 0.139603E+10 0.311678E+09 204.30 0.137762E+10 18408296.57 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:05 6343.62 06-SEP-07:02 6240.72 14-SEP-07:02 411.60 06-SEP-07:02 1187.12 06-SEP-07:02 0.00
October 0.378714E+09 80991042.88 103.37 0.377847E+09 866865.74 0.00 0.58 11-OCT-15:54 0.00 01-OCT-00:10 3186.68 11-OCT-15:54 3186.68 11-OCT-15:54 71.36 03-OCT-15:32 673.12 11-OCT-15:48 0.00
November 93659874.40 19972001.42 37.21 93659232.06 642.34 0.00 0.33 07-NOV-15:58 0.00 01-NOV-00:10 1773.33 07-NOV-15:58 1773.33 07-NOV-15:58 0.56 14-NOV-16:20 368.98 07-NOV-15:58 0.00
December 6928303.97 1500023.39 6.39 6928303.97 -0.0 0.00 0.11 04-DEC-15:40 0.00 01-DEC-00:05 557.43 04-DEC-15:40 557.43 04-DEC-15:40 0.00 01-DEC-15:03 120.05 04-DEC-15:40 0.00
                                       
Annual Sum or Average 0.775445E+10 0.178411E+10 1268.53 0.749678E+10 0.257669E+09 0.00                         0.00
Minimum of Months 1665237.52 360352.87 1.33 1665237.52 -0.0 0.00 0.09   0.00   462.22   462.22   0.00   99.82   0.00
Maximum of Months 0.188481E+10 0.438430E+09 250.30 0.180680E+10 87007870.24 0.00 1.00   0.00   6695.56   6338.02   1798.28   1284.54   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.72 0.00 0.00 0.00
February 151.27 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 58.95 20.22 38.74 61.33 44.85 0.00 0.00 0.00
May 48.77 3.47 45.30 53.25 27.98 0.00 0.00 0.00
June 43.18 0.51 42.67 57.85 18.12 0.00 0.00 0.00
July 45.88 2.07 43.81 62.41 17.60 0.00 0.00 0.00
August 60.78 19.36 41.42 84.73 21.12 0.00 0.00 0.00
September 93.13 50.25 42.88 125.61 32.62 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.80 61.95 36.86 119.85 45.59 0.00 0.00 0.00
Minimum of Months 43.18 0.51 27.11 53.25 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.30 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.71 0.00 0.00 0.00
February 151.26 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 58.82 20.16 38.66 61.08 44.87 0.00 0.00 0.00
May 48.73 3.46 45.28 53.19 27.98 0.00 0.00 0.00
June 43.17 0.50 42.67 57.84 18.12 0.00 0.00 0.00
July 45.87 2.07 43.80 62.38 17.60 0.00 0.00 0.00
August 60.67 19.31 41.37 84.53 21.12 0.00 0.00 0.00
September 93.03 50.21 42.82 125.43 32.64 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.77 61.93 36.84 119.79 45.59 0.00 0.00 0.00
Minimum of Months 43.17 0.50 27.11 53.19 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.28 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.71 0.00 0.00 0.00
February 151.26 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 58.82 20.16 38.66 61.08 44.87 0.00 0.00 0.00
May 48.73 3.46 45.28 53.19 27.98 0.00 0.00 0.00
June 43.17 0.50 42.67 57.84 18.12 0.00 0.00 0.00
July 45.87 2.07 43.80 62.38 17.60 0.00 0.00 0.00
August 60.67 19.31 41.37 84.53 21.12 0.00 0.00 0.00
September 93.02 50.21 42.81 125.42 32.65 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.77 61.93 36.84 119.79 45.59 0.00 0.00 0.00
Minimum of Months 43.17 0.50 27.11 53.19 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.28 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.71 0.00 0.00 0.00
February 151.26 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 58.82 20.16 38.66 61.08 44.87 0.00 0.00 0.00
May 48.73 3.46 45.28 53.19 27.98 0.00 0.00 0.00
June 43.17 0.50 42.67 57.84 18.12 0.00 0.00 0.00
July 45.87 2.07 43.80 62.38 17.60 0.00 0.00 0.00
August 60.67 19.31 41.37 84.53 21.12 0.00 0.00 0.00
September 93.02 50.21 42.81 125.42 32.65 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.77 61.93 36.84 119.79 45.59 0.00 0.00 0.00
Minimum of Months 43.17 0.50 27.11 53.19 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.28 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.71 0.00 0.00 0.00
February 151.26 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 58.82 20.16 38.66 61.08 44.87 0.00 0.00 0.00
May 48.73 3.46 45.28 53.19 27.98 0.00 0.00 0.00
June 43.17 0.50 42.67 57.84 18.12 0.00 0.00 0.00
July 45.87 2.07 43.80 62.38 17.60 0.00 0.00 0.00
August 60.67 19.31 41.37 84.53 21.12 0.00 0.00 0.00
September 93.04 50.21 42.83 125.42 32.62 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.77 61.93 36.84 119.79 45.59 0.00 0.00 0.00
Minimum of Months 43.17 0.50 27.11 53.19 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.28 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 157.84 130.37 27.46 186.84 65.72 0.00 0.00 0.00
February 151.27 121.20 30.07 178.10 67.35 0.00 0.00 0.00
March 108.61 71.79 36.83 130.05 51.98 0.00 0.00 0.00
April 59.00 20.24 38.76 61.38 44.80 0.00 0.00 0.00
May 48.77 3.47 45.30 53.25 27.98 0.00 0.00 0.00
June 43.18 0.51 42.67 57.85 18.12 0.00 0.00 0.00
July 45.88 2.08 43.81 62.41 17.60 0.00 0.00 0.00
August 60.82 19.38 41.44 84.81 21.12 0.00 0.00 0.00
September 93.15 50.26 42.89 125.55 32.53 0.00 0.00 0.00
October 124.07 88.73 35.34 152.29 60.47 0.00 0.00 0.00
November 151.66 121.45 30.21 181.77 65.81 0.00 0.00 0.00
December 145.03 117.92 27.11 167.96 74.90 0.00 0.00 0.00
                 
Annual Sum or Average 98.81 61.95 36.86 119.86 45.58 0.00 0.00 0.00
Minimum of Months 43.18 0.51 27.11 53.25 17.60 0.00 0.00 0.00
Maximum of Months 157.84 130.37 45.30 186.84 74.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 221.58 182.65 38.93 262.14 91.73 0.00 0.00 0.00
February 212.45 169.80 42.65 249.98 93.81 0.00 0.00 0.00
March 156.12 103.31 52.81 187.33 72.28 0.00 0.00 0.00
April 95.55 37.40 58.15 105.35 62.14 0.00 0.00 0.00
May 79.39 10.38 69.00 92.24 39.08 0.00 0.00 0.00
June 69.56 6.08 63.47 96.37 25.53 0.00 0.00 0.00
July 74.53 8.31 66.21 104.17 24.73 0.00 0.00 0.00
August 101.32 39.03 62.29 144.60 29.69 0.00 0.00 0.00
September 145.11 81.55 63.56 197.54 45.71 0.00 0.00 0.00
October 174.50 124.31 50.19 213.71 84.23 0.00 0.00 0.00
November 212.96 170.15 42.81 255.02 91.77 0.00 0.00 0.00
December 203.65 165.21 38.44 235.71 104.38 0.00 0.00 0.00
                 
Annual Sum or Average 145.17 91.07 54.10 178.26 63.59 0.00 0.00 0.00
Minimum of Months 69.56 6.08 38.44 92.24 24.73 0.00 0.00 0.00
Maximum of Months 221.58 182.65 69.00 262.14 104.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.18 31.01 19.17 48.32 63.13 0.00 0.00 0.00
February 66.38 42.03 24.36 66.54 64.98 0.00 0.00 0.00
March 79.24 46.37 32.87 84.86 48.85 0.00 0.00 0.00
April 80.10 39.18 40.93 83.96 41.96 0.00 0.00 0.00
May 92.80 38.88 53.92 109.30 26.61 0.00 0.00 0.00
June 113.49 59.14 54.35 152.00 17.48 0.00 0.00 0.00
July 102.74 48.77 53.97 137.76 17.22 0.00 0.00 0.00
August 104.25 57.00 47.24 138.48 20.35 0.00 0.00 0.00
September 87.65 47.61 40.04 110.64 29.61 0.00 0.00 0.00
October 64.13 35.24 28.89 68.32 56.60 0.00 0.00 0.00
November 50.19 28.43 21.76 49.45 62.11 0.00 0.00 0.00
December 43.76 25.47 18.29 40.13 74.72 0.00 0.00 0.00
                 
Annual Sum or Average 77.95 41.57 36.38 90.92 43.52 0.00 0.00 0.00
Minimum of Months 43.76 25.47 18.29 40.13 17.22 0.00 0.00 0.00
Maximum of Months 113.49 59.14 54.35 152.00 74.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.18 31.01 19.17 48.32 63.13 0.00 0.00 0.00
February 66.38 42.03 24.35 66.54 64.98 0.00 0.00 0.00
March 79.24 46.37 32.87 84.86 48.85 0.00 0.00 0.00
April 80.10 39.18 40.92 83.96 41.96 0.00 0.00 0.00
May 92.80 38.88 53.92 109.30 26.61 0.00 0.00 0.00
June 113.49 59.14 54.35 152.00 17.48 0.00 0.00 0.00
July 102.74 48.77 53.97 137.76 17.22 0.00 0.00 0.00
August 104.24 57.00 47.24 138.48 20.35 0.00 0.00 0.00
September 87.65 47.61 40.04 110.63 29.60 0.00 0.00 0.00
October 64.13 35.24 28.89 68.32 56.60 0.00 0.00 0.00
November 50.19 28.43 21.76 49.45 62.11 0.00 0.00 0.00
December 43.76 25.47 18.29 40.13 74.72 0.00 0.00 0.00
                 
Annual Sum or Average 77.95 41.57 36.38 90.92 43.52 0.00 0.00 0.00
Minimum of Months 43.76 25.47 18.29 40.13 17.22 0.00 0.00 0.00
Maximum of Months 113.49 59.14 54.35 152.00 74.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.18 31.01 19.17 48.32 63.13 0.00 0.00 0.00
February 66.38 42.03 24.35 66.54 64.98 0.00 0.00 0.00
March 79.24 46.37 32.87 84.86 48.85 0.00 0.00 0.00
April 80.10 39.18 40.92 83.96 41.96 0.00 0.00 0.00
May 92.80 38.88 53.92 109.30 26.61 0.00 0.00 0.00
June 113.49 59.14 54.35 152.00 17.48 0.00 0.00 0.00
July 102.74 48.77 53.97 137.76 17.22 0.00 0.00 0.00
August 104.24 57.00 47.24 138.48 20.35 0.00 0.00 0.00
September 87.65 47.61 40.04 110.63 29.60 0.00 0.00 0.00
October 64.13 35.24 28.89 68.32 56.60 0.00 0.00 0.00
November 50.19 28.43 21.76 49.45 62.11 0.00 0.00 0.00
December 43.76 25.47 18.29 40.13 74.72 0.00 0.00 0.00
                 
Annual Sum or Average 77.95 41.57 36.38 90.92 43.52 0.00 0.00 0.00
Minimum of Months 43.76 25.47 18.29 40.13 17.22 0.00 0.00 0.00
Maximum of Months 113.49 59.14 54.35 152.00 74.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 50.29 31.08 19.21 48.50 63.10 0.00 0.00 0.00
February 66.42 42.06 24.37 66.61 64.97 0.00 0.00 0.00
March 79.24 46.37 32.87 84.87 48.85 0.00 0.00 0.00
April 80.10 39.18 40.93 83.96 41.96 0.00 0.00 0.00
May 92.80 38.88 53.92 109.30 26.61 0.00 0.00 0.00
June 113.49 59.14 54.35 152.00 17.48 0.00 0.00 0.00
July 102.74 48.77 53.97 137.76 17.22 0.00 0.00 0.00
August 104.25 57.00 47.24 138.48 20.35 0.00 0.00 0.00
September 87.65 47.61 40.04 110.64 29.61 0.00 0.00 0.00
October 64.14 35.24 28.89 68.34 56.60 0.00 0.00 0.00
November 50.28 28.49 21.79 49.63 62.10 0.00 0.00 0.00
December 43.89 25.55 18.34 40.34 74.65 0.00 0.00 0.00
                 
Annual Sum or Average 77.98 41.59 36.39 90.98 43.51 0.00 0.00 0.00
Minimum of Months 43.89 25.55 18.34 40.34 17.22 0.00 0.00 0.00
Maximum of Months 113.49 59.14 54.35 152.00 74.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.60 0.19 33.42 23.09 41.86 0.00 0.00 0.00
May 45.79 1.47 44.33 46.86 25.53 0.00 0.00 0.00
June 50.52 5.36 45.17 68.22 16.70 0.00 0.00 0.00
July 47.61 2.99 44.62 64.30 16.32 0.00 0.00 0.00
August 38.47 0.89 37.58 49.64 19.23 0.00 0.00 0.00
September 32.19 0.01 32.18 36.89 29.41 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.61 0.91 29.70 28.59 43.92 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.52 5.36 45.17 68.22 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.56 0.18 33.38 23.07 41.92 0.00 0.00 0.00
May 45.64 1.41 44.23 46.59 25.54 0.00 0.00 0.00
June 50.35 5.27 45.08 67.88 16.70 0.00 0.00 0.00
July 47.45 2.92 44.53 63.98 16.32 0.00 0.00 0.00
August 38.34 0.84 37.50 49.40 19.23 0.00 0.00 0.00
September 32.18 0.01 32.18 36.89 29.41 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.55 0.89 29.66 28.49 43.92 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.35 5.27 45.08 67.88 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.55 0.18 33.37 23.07 41.94 0.00 0.00 0.00
May 45.64 1.41 44.23 46.59 25.54 0.00 0.00 0.00
June 50.35 5.27 45.08 67.88 16.70 0.00 0.00 0.00
July 47.45 2.92 44.53 63.98 16.32 0.00 0.00 0.00
August 38.34 0.84 37.50 49.40 19.24 0.00 0.00 0.00
September 32.18 0.01 32.18 36.89 29.42 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.55 0.89 29.66 28.49 43.93 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.35 5.27 45.08 67.88 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.55 0.18 33.37 23.07 41.94 0.00 0.00 0.00
May 45.64 1.41 44.23 46.59 25.54 0.00 0.00 0.00
June 50.35 5.27 45.08 67.88 16.70 0.00 0.00 0.00
July 47.45 2.92 44.53 63.98 16.32 0.00 0.00 0.00
August 38.34 0.84 37.50 49.40 19.24 0.00 0.00 0.00
September 32.18 0.01 32.18 36.89 29.42 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.55 0.89 29.66 28.49 43.93 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.35 5.27 45.08 67.88 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.56 0.18 33.38 23.07 41.93 0.00 0.00 0.00
May 45.64 1.41 44.23 46.59 25.54 0.00 0.00 0.00
June 50.35 5.27 45.08 67.88 16.70 0.00 0.00 0.00
July 47.45 2.92 44.53 63.98 16.32 0.00 0.00 0.00
August 38.34 0.84 37.49 49.40 19.24 0.00 0.00 0.00
September 32.18 0.01 32.18 36.90 29.42 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.55 0.89 29.66 28.49 43.93 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.35 5.27 45.08 67.88 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.89 0.00 15.89 4.83 66.36 0.00 0.00 0.00
February 20.03 0.00 20.03 6.25 66.93 0.00 0.00 0.00
March 27.00 0.00 27.00 16.30 49.58 0.00 0.00 0.00
April 33.58 0.18 33.39 23.09 41.91 0.00 0.00 0.00
May 45.77 1.45 44.32 46.80 25.54 0.00 0.00 0.00
June 50.50 5.34 45.16 68.16 16.70 0.00 0.00 0.00
July 47.56 2.96 44.60 64.19 16.32 0.00 0.00 0.00
August 38.42 0.88 37.54 49.56 19.24 0.00 0.00 0.00
September 32.19 0.01 32.18 36.90 29.42 0.00 0.00 0.00
October 23.11 0.00 23.11 14.36 55.89 0.00 0.00 0.00
November 17.60 0.00 17.60 6.92 62.82 0.00 0.00 0.00
December 14.81 0.00 14.81 3.90 77.83 0.00 0.00 0.00
                 
Annual Sum or Average 30.59 0.90 29.69 28.56 43.93 0.00 0.00 0.00
Minimum of Months 14.81 0.00 14.81 3.90 16.32 0.00 0.00 0.00
Maximum of Months 50.50 5.34 45.16 68.16 77.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.56 34.24 19.33 54.74 65.47 0.00 0.00 0.00
February 64.01 39.78 24.23 64.15 66.41 0.00 0.00 0.00
March 74.07 41.03 33.04 78.37 50.33 0.00 0.00 0.00
April 68.29 28.90 39.40 69.21 43.48 0.00 0.00 0.00
May 82.68 28.91 53.78 97.48 28.33 0.00 0.00 0.00
June 101.71 48.27 53.44 137.77 20.10 0.00 0.00 0.00
July 82.38 29.84 52.54 111.54 18.65 0.00 0.00 0.00
August 87.25 42.71 44.54 115.99 21.79 0.00 0.00 0.00
September 77.87 37.29 40.58 99.15 31.94 0.00 0.00 0.00
October 66.45 38.11 28.35 72.69 58.26 0.00 0.00 0.00
November 55.19 33.74 21.45 56.63 63.73 0.00 0.00 0.00
December 44.75 26.72 18.03 41.90 75.47 0.00 0.00 0.00
                 
Annual Sum or Average 71.53 35.75 35.79 83.38 45.22 0.00 0.00 0.00
Minimum of Months 44.75 26.72 18.03 41.90 18.65 0.00 0.00 0.00
Maximum of Months 101.71 48.27 53.78 137.77 75.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.45 34.16 19.28 54.53 65.50 0.00 0.00 0.00
February 63.97 39.75 24.22 64.07 66.42 0.00 0.00 0.00
March 74.07 41.03 33.04 78.36 50.33 0.00 0.00 0.00
April 68.29 28.90 39.40 69.21 43.48 0.00 0.00 0.00
May 82.68 28.91 53.77 97.47 28.33 0.00 0.00 0.00
June 101.71 48.27 53.44 137.77 20.10 0.00 0.00 0.00
July 82.38 29.84 52.54 111.53 18.65 0.00 0.00 0.00
August 87.25 42.71 44.54 115.99 21.79 0.00 0.00 0.00
September 77.87 37.29 40.58 99.15 31.94 0.00 0.00 0.00
October 66.44 38.10 28.34 72.66 58.26 0.00 0.00 0.00
November 55.11 33.69 21.42 56.47 63.75 0.00 0.00 0.00
December 44.64 26.65 17.98 41.70 75.52 0.00 0.00 0.00
                 
Annual Sum or Average 71.50 35.73 35.78 83.32 45.23 0.00 0.00 0.00
Minimum of Months 44.64 26.65 17.98 41.70 18.65 0.00 0.00 0.00
Maximum of Months 101.71 48.27 53.77 137.77 75.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.45 34.16 19.28 54.53 65.50 0.00 0.00 0.00
February 63.97 39.75 24.22 64.07 66.42 0.00 0.00 0.00
March 74.07 41.03 33.04 78.36 50.33 0.00 0.00 0.00
April 68.29 28.90 39.40 69.21 43.48 0.00 0.00 0.00
May 82.68 28.91 53.77 97.47 28.33 0.00 0.00 0.00
June 101.71 48.27 53.44 137.77 20.10 0.00 0.00 0.00
July 82.38 29.84 52.54 111.53 18.65 0.00 0.00 0.00
August 87.25 42.71 44.54 115.99 21.79 0.00 0.00 0.00
September 77.87 37.29 40.58 99.15 31.94 0.00 0.00 0.00
October 66.44 38.10 28.34 72.66 58.26 0.00 0.00 0.00
November 55.11 33.69 21.42 56.47 63.75 0.00 0.00 0.00
December 44.64 26.65 17.98 41.70 75.52 0.00 0.00 0.00
                 
Annual Sum or Average 71.50 35.73 35.78 83.32 45.23 0.00 0.00 0.00
Minimum of Months 44.64 26.65 17.98 41.70 18.65 0.00 0.00 0.00
Maximum of Months 101.71 48.27 53.77 137.77 75.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.45 34.16 19.29 54.53 65.50 0.00 0.00 0.00
February 63.97 39.75 24.22 64.07 66.42 0.00 0.00 0.00
March 74.07 41.03 33.04 78.36 50.33 0.00 0.00 0.00
April 68.29 28.90 39.40 69.21 43.48 0.00 0.00 0.00
May 82.68 28.91 53.78 97.48 28.33 0.00 0.00 0.00
June 101.71 48.27 53.44 137.77 20.10 0.00 0.00 0.00
July 82.38 29.84 52.54 111.54 18.65 0.00 0.00 0.00
August 87.25 42.71 44.54 115.99 21.79 0.00 0.00 0.00
September 77.87 37.29 40.58 99.15 31.94 0.00 0.00 0.00
October 66.44 38.10 28.34 72.67 58.26 0.00 0.00 0.00
November 55.11 33.69 21.42 56.47 63.75 0.00 0.00 0.00
December 44.64 26.65 17.99 41.70 75.52 0.00 0.00 0.00
                 
Annual Sum or Average 71.50 35.73 35.78 83.32 45.23 0.00 0.00 0.00
Minimum of Months 44.64 26.65 17.99 41.70 18.65 0.00 0.00 0.00
Maximum of Months 101.71 48.27 53.78 137.77 75.52 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422748E+09 0.349188E+09 73559514.33 0.500437E+09 0.176012E+09
February 0.365942E+09 0.293202E+09 72739789.53 0.430865E+09 0.162928E+09
March 0.290907E+09 0.192271E+09 98636441.93 0.348338E+09 0.139226E+09
April 0.152807E+09 52404684.76 0.100402E+09 0.158954E+09 0.116259E+09
May 0.130622E+09 9284368.27 0.121337E+09 0.142618E+09 74932977.69
June 0.111910E+09 1309716.24 0.110601E+09 0.149948E+09 46971919.43
July 0.122889E+09 5555639.14 0.117333E+09 0.167146E+09 47128038.25
August 0.162784E+09 51844313.22 0.110939E+09 0.226932E+09 56568715.73
September 0.241404E+09 0.130250E+09 0.111154E+09 0.325568E+09 84552884.92
October 0.332304E+09 0.237643E+09 94660953.67 0.407884E+09 0.161964E+09
November 0.393110E+09 0.314798E+09 78312572.29 0.471143E+09 0.170581E+09
December 0.388458E+09 0.315840E+09 72618222.57 0.449853E+09 0.200620E+09
           
Annual Sum or Average 0.311588E+10 0.195359E+10 0.116229E+10 0.377969E+10 0.143774E+10
Minimum of Months 0.111910E+09 1309716.24 72618222.57 0.142618E+09 46971919.43
Maximum of Months 0.422748E+09 0.349188E+09 0.121337E+09 0.500437E+09 0.200620E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422746E+09 0.349188E+09 73557593.33 0.500435E+09 0.176010E+09
February 0.365940E+09 0.293202E+09 72737783.23 0.430863E+09 0.162927E+09
March 0.290904E+09 0.192271E+09 98632665.33 0.348335E+09 0.139225E+09
April 0.152451E+09 52255461.63 0.100195E+09 0.158321E+09 0.116307E+09
May 0.130532E+09 9263116.15 0.121269E+09 0.142462E+09 74932264.42
June 0.111899E+09 1308146.44 0.110591E+09 0.149932E+09 46970767.45
July 0.122852E+09 5544955.49 0.117307E+09 0.167083E+09 47127109.17
August 0.162510E+09 51716985.50 0.110793E+09 0.226399E+09 56571389.02
September 0.241137E+09 0.130141E+09 0.110996E+09 0.325107E+09 84595828.20
October 0.332301E+09 0.237643E+09 94658053.08 0.407882E+09 0.161963E+09
November 0.393108E+09 0.314798E+09 78310591.09 0.471142E+09 0.170580E+09
December 0.388456E+09 0.315840E+09 72616277.59 0.449852E+09 0.200618E+09
           
Annual Sum or Average 0.311484E+10 0.195317E+10 0.116166E+10 0.377781E+10 0.143783E+10
Minimum of Months 0.111899E+09 1308146.44 72616277.59 0.142462E+09 46970767.45
Maximum of Months 0.422746E+09 0.349188E+09 0.121269E+09 0.500435E+09 0.200618E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422746E+09 0.349188E+09 73557593.33 0.500435E+09 0.176010E+09
February 0.365940E+09 0.293202E+09 72737783.23 0.430863E+09 0.162927E+09
March 0.290904E+09 0.192271E+09 98632665.33 0.348335E+09 0.139225E+09
April 0.152450E+09 52255438.90 0.100194E+09 0.158320E+09 0.116307E+09
May 0.130532E+09 9263116.15 0.121269E+09 0.142462E+09 74932264.42
June 0.111899E+09 1308146.44 0.110591E+09 0.149932E+09 46970767.45
July 0.122852E+09 5544955.49 0.117307E+09 0.167083E+09 47127109.17
August 0.162510E+09 51716459.30 0.110793E+09 0.226398E+09 56571787.66
September 0.241102E+09 0.130135E+09 0.110967E+09 0.325082E+09 84631400.28
October 0.332301E+09 0.237643E+09 94658053.08 0.407882E+09 0.161963E+09
November 0.393108E+09 0.314798E+09 78310591.09 0.471142E+09 0.170580E+09
December 0.388456E+09 0.315840E+09 72616277.59 0.449852E+09 0.200618E+09
           
Annual Sum or Average 0.311480E+10 0.195317E+10 0.116163E+10 0.377779E+10 0.143786E+10
Minimum of Months 0.111899E+09 1308146.44 72616277.59 0.142462E+09 46970767.45
Maximum of Months 0.422746E+09 0.349188E+09 0.121269E+09 0.500435E+09 0.200618E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422746E+09 0.349188E+09 73557593.33 0.500435E+09 0.176010E+09
February 0.365940E+09 0.293202E+09 72737783.23 0.430863E+09 0.162927E+09
March 0.290904E+09 0.192271E+09 98632665.33 0.348335E+09 0.139225E+09
April 0.152450E+09 52255438.90 0.100194E+09 0.158320E+09 0.116307E+09
May 0.130532E+09 9263116.15 0.121269E+09 0.142462E+09 74932264.42
June 0.111899E+09 1308146.44 0.110591E+09 0.149932E+09 46970767.45
July 0.122852E+09 5544955.49 0.117307E+09 0.167083E+09 47127109.17
August 0.162510E+09 51716544.67 0.110793E+09 0.226398E+09 56571532.52
September 0.241107E+09 0.130135E+09 0.110971E+09 0.325080E+09 84622067.08
October 0.332301E+09 0.237643E+09 94658053.08 0.407882E+09 0.161963E+09
November 0.393108E+09 0.314798E+09 78310591.09 0.471142E+09 0.170580E+09
December 0.388456E+09 0.315840E+09 72616277.59 0.449852E+09 0.200618E+09
           
Annual Sum or Average 0.311480E+10 0.195317E+10 0.116164E+10 0.377778E+10 0.143785E+10
Minimum of Months 0.111899E+09 1308146.44 72616277.59 0.142462E+09 46970767.45
Maximum of Months 0.422746E+09 0.349188E+09 0.121269E+09 0.500435E+09 0.200618E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422746E+09 0.349188E+09 73557593.33 0.500435E+09 0.176010E+09
February 0.365940E+09 0.293202E+09 72737783.23 0.430863E+09 0.162927E+09
March 0.290904E+09 0.192271E+09 98632665.33 0.348335E+09 0.139225E+09
April 0.152450E+09 52255473.61 0.100195E+09 0.158320E+09 0.116306E+09
May 0.130532E+09 9263116.15 0.121269E+09 0.142462E+09 74932264.42
June 0.111899E+09 1308146.44 0.110591E+09 0.149932E+09 46970767.45
July 0.122852E+09 5544955.49 0.117307E+09 0.167083E+09 47127109.17
August 0.162511E+09 51717730.03 0.110793E+09 0.226400E+09 56570155.17
September 0.241150E+09 0.130142E+09 0.111008E+09 0.325082E+09 84550635.58
October 0.332301E+09 0.237643E+09 94658053.08 0.407882E+09 0.161963E+09
November 0.393108E+09 0.314798E+09 78310591.09 0.471142E+09 0.170580E+09
December 0.388456E+09 0.315840E+09 72616277.59 0.449852E+09 0.200618E+09
           
Annual Sum or Average 0.311485E+10 0.195317E+10 0.116168E+10 0.377779E+10 0.143778E+10
Minimum of Months 0.111899E+09 1308146.44 72616277.59 0.142462E+09 46970767.45
Maximum of Months 0.422746E+09 0.349188E+09 0.121269E+09 0.500435E+09 0.200618E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.422748E+09 0.349188E+09 73559514.23 0.500437E+09 0.176012E+09
February 0.365942E+09 0.293202E+09 72739789.43 0.430865E+09 0.162928E+09
March 0.290907E+09 0.192271E+09 98636441.73 0.348338E+09 0.139226E+09
April 0.152940E+09 52474047.68 0.100466E+09 0.159100E+09 0.116128E+09
May 0.130624E+09 9288594.97 0.121335E+09 0.142621E+09 74928398.58
June 0.111911E+09 1309962.46 0.110601E+09 0.149950E+09 46971919.37
July 0.122892E+09 5559109.28 0.117333E+09 0.167157E+09 47128038.20
August 0.162889E+09 51901874.91 0.110987E+09 0.227156E+09 56570474.73
September 0.241453E+09 0.130279E+09 0.111173E+09 0.325433E+09 84323153.82
October 0.332304E+09 0.237643E+09 94660953.52 0.407884E+09 0.161964E+09
November 0.393110E+09 0.314798E+09 78312572.19 0.471143E+09 0.170581E+09
December 0.388458E+09 0.315840E+09 72618222.47 0.449853E+09 0.200620E+09
           
Annual Sum or Average 0.311618E+10 0.195375E+10 0.116242E+10 0.377994E+10 0.143738E+10
Minimum of Months 0.111911E+09 1309962.46 72618222.47 0.142621E+09 46971919.37
Maximum of Months 0.422748E+09 0.349188E+09 0.121335E+09 0.500437E+09 0.200620E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.593480E+09 0.489217E+09 0.104263E+09 0.702103E+09 0.245698E+09
February 0.513948E+09 0.410780E+09 0.103168E+09 0.604748E+09 0.226950E+09
March 0.418147E+09 0.276714E+09 0.141433E+09 0.501742E+09 0.193601E+09
April 0.247666E+09 96942970.45 0.150723E+09 0.273058E+09 0.161078E+09
May 0.212631E+09 27808695.41 0.184823E+09 0.247048E+09 0.104679E+09
June 0.180289E+09 15763794.93 0.164525E+09 0.249803E+09 66185479.29
July 0.199610E+09 22267280.56 0.177342E+09 0.279017E+09 66247864.10
August 0.271384E+09 0.104546E+09 0.166838E+09 0.387299E+09 79527953.49
September 0.376134E+09 0.211389E+09 0.164745E+09 0.512014E+09 0.118488E+09
October 0.467382E+09 0.332941E+09 0.134441E+09 0.572407E+09 0.225608E+09
November 0.551996E+09 0.441036E+09 0.110960E+09 0.661010E+09 0.237879E+09
December 0.545455E+09 0.442496E+09 0.102960E+09 0.631317E+09 0.279575E+09
           
Annual Sum or Average 0.457812E+10 0.287190E+10 0.170622E+10 0.562157E+10 0.200552E+10
Minimum of Months 0.180289E+09 15763794.93 0.102960E+09 0.247048E+09 66185479.29
Maximum of Months 0.593480E+09 0.489217E+09 0.184823E+09 0.702103E+09 0.279575E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134408E+09 83057065.08 51350940.77 0.129410E+09 0.169100E+09
February 0.160596E+09 0.101674E+09 58921293.81 0.160964E+09 0.157198E+09
March 0.212244E+09 0.124203E+09 88040149.48 0.227299E+09 0.130850E+09
April 0.207622E+09 0.101542E+09 0.106080E+09 0.217627E+09 0.108758E+09
May 0.248564E+09 0.104142E+09 0.144422E+09 0.292745E+09 71265383.48
June 0.294178E+09 0.153300E+09 0.140879E+09 0.393980E+09 45306699.77
July 0.275183E+09 0.130628E+09 0.144555E+09 0.368971E+09 46135048.84
August 0.279213E+09 0.152677E+09 0.126536E+09 0.370900E+09 54507792.11
September 0.227189E+09 0.123398E+09 0.103791E+09 0.286768E+09 76736280.55
October 0.171762E+09 94381538.24 77380267.73 0.182988E+09 0.151610E+09
November 0.130101E+09 73695210.46 56405757.33 0.128176E+09 0.160998E+09
December 0.117207E+09 68221584.21 48985305.72 0.107486E+09 0.200118E+09
           
Annual Sum or Average 0.245827E+10 0.131092E+10 0.114735E+10 0.286732E+10 0.137258E+10
Minimum of Months 0.117207E+09 68221584.21 48985305.72 0.107486E+09 45306699.77
Maximum of Months 0.294178E+09 0.153300E+09 0.144555E+09 0.393980E+09 0.200118E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134406E+09 83057065.08 51349019.86 0.129409E+09 0.169098E+09
February 0.160594E+09 0.101674E+09 58919287.61 0.160963E+09 0.157197E+09
March 0.212240E+09 0.124203E+09 88036373.08 0.227296E+09 0.130850E+09
April 0.207617E+09 0.101542E+09 0.106075E+09 0.217622E+09 0.108759E+09
May 0.248558E+09 0.104142E+09 0.144416E+09 0.292737E+09 71264464.98
June 0.294174E+09 0.153300E+09 0.140874E+09 0.393976E+09 45305494.56
July 0.275177E+09 0.130628E+09 0.144549E+09 0.368964E+09 46133999.51
August 0.279209E+09 0.152677E+09 0.126531E+09 0.370896E+09 54506549.67
September 0.227185E+09 0.123398E+09 0.103787E+09 0.286764E+09 76734695.67
October 0.171759E+09 94381538.24 77377367.29 0.182986E+09 0.151610E+09
November 0.130099E+09 73695210.46 56403776.23 0.128175E+09 0.160997E+09
December 0.117205E+09 68221584.21 48983360.85 0.107485E+09 0.200117E+09
           
Annual Sum or Average 0.245822E+10 0.131092E+10 0.114730E+10 0.286727E+10 0.137257E+10
Minimum of Months 0.117205E+09 68221584.21 48983360.85 0.107485E+09 45305494.56
Maximum of Months 0.294174E+09 0.153300E+09 0.144549E+09 0.393976E+09 0.200117E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134406E+09 83057065.08 51349019.86 0.129409E+09 0.169098E+09
February 0.160594E+09 0.101674E+09 58919287.61 0.160963E+09 0.157197E+09
March 0.212240E+09 0.124203E+09 88036373.08 0.227296E+09 0.130850E+09
April 0.207617E+09 0.101542E+09 0.106075E+09 0.217622E+09 0.108759E+09
May 0.248558E+09 0.104142E+09 0.144416E+09 0.292737E+09 71264464.98
June 0.294174E+09 0.153300E+09 0.140874E+09 0.393976E+09 45305494.56
July 0.275177E+09 0.130628E+09 0.144549E+09 0.368964E+09 46133999.51
August 0.279209E+09 0.152677E+09 0.126531E+09 0.370896E+09 54506549.67
September 0.227185E+09 0.123398E+09 0.103787E+09 0.286764E+09 76734695.67
October 0.171759E+09 94381538.24 77377367.29 0.182986E+09 0.151610E+09
November 0.130099E+09 73695210.46 56403776.23 0.128175E+09 0.160997E+09
December 0.117205E+09 68221584.21 48983360.85 0.107485E+09 0.200117E+09
           
Annual Sum or Average 0.245822E+10 0.131092E+10 0.114730E+10 0.286727E+10 0.137257E+10
Minimum of Months 0.117205E+09 68221584.21 48983360.85 0.107485E+09 45305494.56
Maximum of Months 0.294174E+09 0.153300E+09 0.144549E+09 0.393976E+09 0.200117E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134686E+09 83236994.98 51448803.15 0.129906E+09 0.168994E+09
February 0.160688E+09 0.101743E+09 58944732.22 0.161140E+09 0.157170E+09
March 0.212249E+09 0.124206E+09 88042640.60 0.227308E+09 0.130850E+09
April 0.207622E+09 0.101542E+09 0.106080E+09 0.217627E+09 0.108758E+09
May 0.248564E+09 0.104142E+09 0.144422E+09 0.292745E+09 71265383.52
June 0.294178E+09 0.153300E+09 0.140879E+09 0.393980E+09 45306699.83
July 0.275183E+09 0.130628E+09 0.144555E+09 0.368971E+09 46135048.90
August 0.279213E+09 0.152677E+09 0.126536E+09 0.370900E+09 54507792.18
September 0.227192E+09 0.123399E+09 0.103792E+09 0.286773E+09 76736280.64
October 0.171788E+09 94399252.42 77388751.77 0.183044E+09 0.151610E+09
November 0.130332E+09 73849952.50 56482183.87 0.128639E+09 0.160956E+09
December 0.117543E+09 68429508.93 49113285.92 0.108036E+09 0.199952E+09
           
Annual Sum or Average 0.245924E+10 0.131155E+10 0.114768E+10 0.286907E+10 0.137224E+10
Minimum of Months 0.117543E+09 68429508.93 49113285.92 0.108036E+09 45306699.83
Maximum of Months 0.294178E+09 0.153300E+09 0.144555E+09 0.393980E+09 0.199952E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42550520.69 0.00 42550520.69 12928561.77 0.177734E+09
February 48463518.71 0.00 48463518.71 15118109.98 0.161906E+09
March 72324519.14 0.00 72324519.14 43669241.96 0.132789E+09
April 87102189.24 487541.72 86614647.53 59840218.39 0.108503E+09
May 0.122655E+09 3934912.71 0.118720E+09 0.125511E+09 68372891.07
June 0.130959E+09 13889641.36 0.117070E+09 0.176832E+09 43279790.42
July 0.127516E+09 8001899.18 0.119514E+09 0.172217E+09 43708400.44
August 0.103042E+09 2382211.64 0.100660E+09 0.132963E+09 51512380.34
September 83424855.23 19304.43 83405550.81 95623347.26 76236267.22
October 61905377.59 0.00 61905377.59 38472094.31 0.149705E+09
November 45613782.77 0.00 45613782.77 17931880.83 0.162837E+09
December 39677494.36 0.00 39677494.36 10442438.37 0.208452E+09
           
Annual Sum or Average 0.965235E+09 28715511.03 0.936519E+09 0.901550E+09 0.138504E+10
Minimum of Months 39677494.36 0.00 39677494.36 10442438.37 43279790.42
Maximum of Months 0.130959E+09 13889641.36 0.119514E+09 0.176832E+09 0.208452E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42548599.69 0.00 42548599.69 12927557.13 0.177733E+09
February 48461512.40 0.00 48461512.40 15117303.56 0.161905E+09
March 72320742.55 0.00 72320742.55 43666622.56 0.132789E+09
April 86993092.08 463066.43 86530025.65 59795555.82 0.108652E+09
May 0.122250E+09 3784048.35 0.118466E+09 0.124778E+09 68403707.31
June 0.130511E+09 13667074.71 0.116844E+09 0.175940E+09 43278521.26
July 0.127077E+09 7811828.24 0.119266E+09 0.171367E+09 43709154.11
August 0.102693E+09 2261801.03 0.100431E+09 0.132304E+09 51516780.48
September 83420153.80 19276.37 83400877.43 95619729.61 76235948.60
October 61902477.00 0.00 61902477.00 38470651.86 0.149705E+09
November 45611801.57 0.00 45611801.57 17930978.97 0.162836E+09
December 39675549.39 0.00 39675549.39 10441852.08 0.208451E+09
           
Annual Sum or Average 0.963465E+09 28007095.14 0.935458E+09 0.898360E+09 0.138521E+10
Minimum of Months 39675549.39 0.00 39675549.39 10441852.08 43278521.26
Maximum of Months 0.130511E+09 13667074.71 0.119266E+09 0.175940E+09 0.208451E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42548599.69 0.00 42548599.69 12927557.13 0.177733E+09
February 48461512.40 0.00 48461512.40 15117303.56 0.161905E+09
March 72320742.55 0.00 72320742.55 43666622.56 0.132789E+09
April 86963586.82 456922.91 86506663.92 59786293.26 0.108696E+09
May 0.122250E+09 3784048.35 0.118466E+09 0.124778E+09 68403707.31
June 0.130511E+09 13667074.71 0.116844E+09 0.175940E+09 43278521.26
July 0.127077E+09 7811828.24 0.119266E+09 0.171367E+09 43709154.11
August 0.102690E+09 2261702.30 0.100429E+09 0.132306E+09 51522513.25
September 83417235.48 18863.04 83398372.44 95623701.39 76245007.16
October 61902477.00 0.00 61902477.00 38470651.86 0.149705E+09
November 45611801.57 0.00 45611801.57 17930978.97 0.162836E+09
December 39675549.39 0.00 39675549.39 10441852.08 0.208451E+09
           
Annual Sum or Average 0.963430E+09 28000439.55 0.935430E+09 0.898357E+09 0.138527E+10
Minimum of Months 39675549.39 0.00 39675549.39 10441852.08 43278521.26
Maximum of Months 0.130511E+09 13667074.71 0.119266E+09 0.175940E+09 0.208451E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42548599.69 0.00 42548599.69 12927557.13 0.177733E+09
February 48461512.40 0.00 48461512.40 15117303.56 0.161905E+09
March 72320742.55 0.00 72320742.55 43666622.56 0.132789E+09
April 86963586.82 456922.91 86506663.92 59786293.26 0.108696E+09
May 0.122250E+09 3784048.35 0.118466E+09 0.124778E+09 68403707.31
June 0.130511E+09 13667074.71 0.116844E+09 0.175940E+09 43278521.26
July 0.127077E+09 7811828.24 0.119266E+09 0.171367E+09 43709154.11
August 0.102688E+09 2261645.69 0.100427E+09 0.132308E+09 51527757.26
September 83417508.49 18868.38 83398640.11 95630330.24 76251308.77
October 61902477.00 0.00 61902477.00 38470651.86 0.149705E+09
November 45611801.57 0.00 45611801.57 17930978.97 0.162836E+09
December 39675549.39 0.00 39675549.39 10441852.08 0.208451E+09
           
Annual Sum or Average 0.963428E+09 28000388.29 0.935428E+09 0.898365E+09 0.138529E+10
Minimum of Months 39675549.39 0.00 39675549.39 10441852.08 43278521.26
Maximum of Months 0.130511E+09 13667074.71 0.119266E+09 0.175940E+09 0.208451E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42548599.69 0.00 42548599.69 12927557.13 0.177733E+09
February 48461512.40 0.00 48461512.40 15117303.56 0.161905E+09
March 72320742.55 0.00 72320742.55 43666622.56 0.132789E+09
April 86977860.33 461407.98 86516452.35 59799750.67 0.108682E+09
May 0.122250E+09 3784048.35 0.118466E+09 0.124778E+09 68403707.31
June 0.130511E+09 13667074.71 0.116844E+09 0.175940E+09 43278521.26
July 0.127077E+09 7811829.38 0.119266E+09 0.171368E+09 43709154.11
August 0.102687E+09 2261693.15 0.100426E+09 0.132311E+09 51531723.68
September 83419897.66 19188.67 83400708.99 95637299.26 76254273.97
October 61902477.00 0.00 61902477.00 38470651.86 0.149705E+09
November 45611801.57 0.00 45611801.57 17930978.97 0.162836E+09
December 39675549.39 0.00 39675549.39 10441852.08 0.208451E+09
           
Annual Sum or Average 0.963444E+09 28005242.24 0.935439E+09 0.898388E+09 0.138528E+10
Minimum of Months 39675549.39 0.00 39675549.39 10441852.08 43278521.26
Maximum of Months 0.130511E+09 13667074.71 0.119266E+09 0.175940E+09 0.208451E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42550520.59 0.00 42550520.59 12928561.71 0.177734E+09
February 48463518.60 0.00 48463518.60 15118109.93 0.161906E+09
March 72324518.95 0.00 72324518.95 43669241.83 0.132789E+09
April 87036257.74 479293.61 86556964.13 59853235.18 0.108626E+09
May 0.122580E+09 3876467.74 0.118703E+09 0.125351E+09 68403245.79
June 0.130884E+09 13835628.32 0.117048E+09 0.176659E+09 43279416.29
July 0.127385E+09 7916924.32 0.119468E+09 0.171921E+09 43709823.62
August 0.102913E+09 2354325.39 0.100559E+09 0.132748E+09 51528403.05
September 83424173.77 19189.02 83404984.75 95642375.58 76256743.34
October 61905377.44 0.00 61905377.44 38472094.23 0.149705E+09
November 45613782.67 0.00 45613782.67 17931880.78 0.162837E+09
December 39677494.26 0.00 39677494.26 10442438.34 0.208452E+09
           
Annual Sum or Average 0.964758E+09 28481828.40 0.936276E+09 0.900737E+09 0.138523E+10
Minimum of Months 39677494.26 0.00 39677494.26 10442438.34 43279416.29
Maximum of Months 0.130884E+09 13835628.32 0.119468E+09 0.176659E+09 0.208452E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143457E+09 91695970.52 51761163.98 0.146625E+09 0.175344E+09
February 0.154850E+09 96232883.55 58617033.14 0.155183E+09 0.160656E+09
March 0.198386E+09 0.109883E+09 88503061.85 0.209895E+09 0.134796E+09
April 0.177017E+09 74897540.52 0.102119E+09 0.179386E+09 0.112704E+09
May 0.221462E+09 77427733.68 0.144034E+09 0.261083E+09 75885127.22
June 0.263645E+09 0.125120E+09 0.138525E+09 0.357098E+09 52098513.91
July 0.220657E+09 79928671.97 0.140728E+09 0.298735E+09 49946027.19
August 0.233697E+09 0.114394E+09 0.119303E+09 0.310681E+09 58365286.46
September 0.201843E+09 96649879.33 0.105193E+09 0.256999E+09 82793167.99
October 0.177980E+09 0.102061E+09 75919289.19 0.194690E+09 0.156039E+09
November 0.143059E+09 87456399.19 55603061.07 0.146775E+09 0.165193E+09
December 0.119865E+09 71579939.87 48284993.47 0.112228E+09 0.202150E+09
           
Annual Sum or Average 0.225592E+10 0.112733E+10 0.112859E+10 0.262938E+10 0.142597E+10
Minimum of Months 0.119865E+09 71579939.87 48284993.47 0.112228E+09 49946027.19
Maximum of Months 0.263645E+09 0.125120E+09 0.144034E+09 0.357098E+09 0.202150E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143154E+09 91502999.06 51651358.10 0.146064E+09 0.175435E+09
February 0.154753E+09 96161949.36 58590757.53 0.155002E+09 0.160690E+09
March 0.198379E+09 0.109882E+09 88496363.99 0.209885E+09 0.134796E+09
April 0.177011E+09 74897540.52 0.102114E+09 0.179381E+09 0.112704E+09
May 0.221455E+09 77427733.68 0.144027E+09 0.261075E+09 75884316.55
June 0.263640E+09 0.125120E+09 0.138520E+09 0.357094E+09 52097313.70
July 0.220651E+09 79928671.97 0.140722E+09 0.298729E+09 49945030.53
August 0.233692E+09 0.114394E+09 0.119299E+09 0.310677E+09 58364101.57
September 0.201838E+09 96648981.16 0.105189E+09 0.256991E+09 82791698.41
October 0.177947E+09 0.102041E+09 75906160.60 0.194626E+09 0.156039E+09
November 0.142845E+09 87322347.61 55523125.87 0.146358E+09 0.165230E+09
December 0.119562E+09 71391204.47 48170756.49 0.111693E+09 0.202262E+09
           
Annual Sum or Average 0.225493E+10 0.112672E+10 0.112821E+10 0.262757E+10 0.142624E+10
Minimum of Months 0.119562E+09 71391204.47 48170756.49 0.111693E+09 49945030.53
Maximum of Months 0.263640E+09 0.125120E+09 0.144027E+09 0.357094E+09 0.202262E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143154E+09 91502999.06 51651358.10 0.146064E+09 0.175435E+09
February 0.154753E+09 96161949.36 58590757.53 0.155002E+09 0.160690E+09
March 0.198379E+09 0.109882E+09 88496363.99 0.209885E+09 0.134796E+09
April 0.177011E+09 74897540.52 0.102114E+09 0.179381E+09 0.112704E+09
May 0.221455E+09 77427733.68 0.144027E+09 0.261075E+09 75884316.55
June 0.263640E+09 0.125120E+09 0.138520E+09 0.357094E+09 52097313.70
July 0.220651E+09 79928671.97 0.140722E+09 0.298729E+09 49945030.53
August 0.233692E+09 0.114394E+09 0.119299E+09 0.310677E+09 58364101.57
September 0.201838E+09 96648981.16 0.105189E+09 0.256991E+09 82791698.41
October 0.177947E+09 0.102041E+09 75906160.60 0.194626E+09 0.156039E+09
November 0.142845E+09 87322347.61 55523125.87 0.146358E+09 0.165230E+09
December 0.119562E+09 71391204.47 48170756.49 0.111693E+09 0.202262E+09
           
Annual Sum or Average 0.225493E+10 0.112672E+10 0.112821E+10 0.262757E+10 0.142624E+10
Minimum of Months 0.119562E+09 71391204.47 48170756.49 0.111693E+09 49945030.53
Maximum of Months 0.263640E+09 0.125120E+09 0.144027E+09 0.357094E+09 0.202262E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143156E+09 91502999.06 51653279.10 0.146065E+09 0.175436E+09
February 0.154755E+09 96161949.36 58592763.83 0.155003E+09 0.160691E+09
March 0.198382E+09 0.109882E+09 88500140.59 0.209888E+09 0.134796E+09
April 0.177017E+09 74897540.52 0.102119E+09 0.179386E+09 0.112704E+09
May 0.221462E+09 77427733.68 0.144034E+09 0.261083E+09 75885127.26
June 0.263645E+09 0.125120E+09 0.138525E+09 0.357098E+09 52098513.97
July 0.220657E+09 79928671.97 0.140728E+09 0.298735E+09 49946027.24
August 0.233697E+09 0.114394E+09 0.119303E+09 0.310681E+09 58365286.52
September 0.201842E+09 96648981.16 0.105193E+09 0.256995E+09 82793168.07
October 0.177950E+09 0.102041E+09 75909061.19 0.194627E+09 0.156039E+09
November 0.142847E+09 87322347.61 55525107.07 0.146359E+09 0.165231E+09
December 0.119564E+09 71391204.47 48172701.47 0.111694E+09 0.202263E+09
           
Annual Sum or Average 0.225497E+10 0.112672E+10 0.112825E+10 0.262762E+10 0.142625E+10
Minimum of Months 0.119564E+09 71391204.47 48172701.47 0.111694E+09 49946027.24
Maximum of Months 0.263645E+09 0.125120E+09 0.144034E+09 0.357098E+09 0.202263E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1383.18 486.02 1168.59 964.88 203.71 0.00 0.00
February 1318.59 497.90 1120.04 896.99 223.05 0.00 0.00
March 967.65 384.16 807.79 534.03 273.76 0.00 0.00
April 472.33 331.24 448.77 158.50 290.27 0.00 0.00
May 411.49 206.94 371.87 31.15 340.71 0.00 0.00
June 443.45 134.26 328.59 9.11 319.48 0.00 0.00
July 478.51 130.30 349.76 20.74 329.02 0.00 0.00
August 652.25 156.42 465.61 155.00 310.61 0.00 0.00
September 950.35 241.40 703.51 382.90 320.61 0.00 0.00
October 1127.42 447.05 918.90 656.66 262.24 0.00 0.00
November 1345.63 486.64 1122.94 898.85 224.08 0.00 0.00
December 1243.44 553.79 1073.85 872.74 201.11 0.00 0.00
               
Annual Sum or Average 897.14 337.13 737.87 462.71 275.16 0.00 0.00
Minimum of Months 411.49 130.30 328.59 9.11 201.11 0.00 0.00
Maximum of Months 1383.18 553.79 1168.59 964.88 340.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 193.44 252.49 200.83 124.11 76.72 0.00 0.00
February 266.22 259.90 265.57 168.14 97.43 0.00 0.00
March 339.46 195.42 316.97 185.49 131.48 0.00 0.00
April 335.84 167.84 320.40 156.70 163.70 0.00 0.00
May 437.19 106.43 371.21 155.53 215.68 0.00 0.00
June 607.99 69.92 453.98 236.57 217.40 0.00 0.00
July 551.03 68.90 410.96 195.08 215.88 0.00 0.00
August 553.91 81.40 416.98 228.01 188.97 0.00 0.00
September 442.54 118.42 350.60 190.43 160.17 0.00 0.00
October 273.30 226.42 256.52 140.96 115.56 0.00 0.00
November 197.98 248.44 200.86 113.79 87.07 0.00 0.00
December 160.72 298.79 175.16 101.96 73.20 0.00 0.00
               
Annual Sum or Average 363.74 174.08 311.83 166.30 145.54 0.00 0.00
Minimum of Months 160.72 68.90 175.16 101.96 73.20 0.00 0.00
Maximum of Months 607.99 298.79 453.98 236.57 217.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 28.96 398.15 95.32 0.00 95.32 0.00 0.00
February 37.49 401.55 120.19 0.00 120.19 0.00 0.00
March 97.82 297.47 162.01 0.00 162.01 0.00 0.00
April 138.44 251.48 201.40 1.08 200.32 0.00 0.00
May 280.01 153.22 274.13 8.57 265.56 0.00 0.00
June 407.89 100.18 302.43 31.79 270.64 0.00 0.00
July 384.41 97.91 284.95 17.61 267.34 0.00 0.00
August 296.80 115.42 230.25 5.15 225.11 0.00 0.00
September 221.36 176.50 193.10 0.04 193.06 0.00 0.00
October 86.18 335.36 138.67 0.00 138.67 0.00 0.00
November 41.51 376.94 105.58 0.00 105.58 0.00 0.00
December 23.39 466.96 88.88 0.00 88.88 0.00 0.00
               
Annual Sum or Average 171.10 263.55 183.40 5.37 178.04 0.00 0.00
Minimum of Months 23.39 97.91 88.88 0.00 88.88 0.00 0.00
Maximum of Months 407.89 466.96 302.43 31.79 270.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 218.33 261.95 213.90 136.73 77.18 0.00 0.00
February 256.36 265.68 255.92 159.03 96.89 0.00 0.00
March 313.45 201.31 296.27 164.10 132.17 0.00 0.00
April 276.83 173.93 273.17 115.58 157.59 0.00 0.00
May 389.90 113.33 330.73 115.63 215.10 0.00 0.00
June 551.07 80.40 406.86 193.09 213.77 0.00 0.00
July 446.14 74.59 329.53 119.37 210.16 0.00 0.00
August 463.98 87.16 349.01 170.84 178.17 0.00 0.00
September 396.60 127.77 311.48 149.15 162.33 0.00 0.00
October 290.68 233.03 265.77 152.40 113.37 0.00 0.00
November 226.02 254.97 220.52 134.81 85.72 0.00 0.00
December 167.00 302.02 178.67 106.69 71.98 0.00 0.00
               
Annual Sum or Average 333.34 180.89 286.05 142.93 143.11 0.00 0.00
Minimum of Months 167.00 74.59 178.67 106.69 71.98 0.00 0.00
Maximum of Months 551.07 302.02 406.86 193.09 215.10 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.370472E+10 0.130176E+10 0.312996E+10 0.258435E+10 0.545613E+09 0.00 0.00
February 0.318993E+10 0.120451E+10 0.270959E+10 0.216999E+10 0.539599E+09 0.00 0.00
March 0.259174E+10 0.102894E+10 0.216358E+10 0.143034E+10 0.733237E+09 0.00 0.00
April 0.122427E+10 0.858568E+09 0.116321E+10 0.410844E+09 0.752370E+09 0.00 0.00
May 0.110213E+10 0.554262E+09 0.996004E+09 83434123.25 0.912570E+09 0.00 0.00
June 0.114943E+10 0.348011E+09 0.851707E+09 23616059.38 0.828091E+09 0.00 0.00
July 0.128165E+10 0.349007E+09 0.936800E+09 55561850.92 0.881238E+09 0.00 0.00
August 0.174698E+10 0.418949E+09 0.124710E+10 0.415160E+09 0.831938E+09 0.00 0.00
September 0.246332E+10 0.625716E+09 0.182349E+10 0.992473E+09 0.831014E+09 0.00 0.00
October 0.301969E+10 0.119738E+10 0.246119E+10 0.175880E+10 0.702395E+09 0.00 0.00
November 0.348786E+10 0.126136E+10 0.291065E+10 0.232982E+10 0.580828E+09 0.00 0.00
December 0.333043E+10 0.148328E+10 0.287620E+10 0.233753E+10 0.538661E+09 0.00 0.00
               
Annual Sum or Average 0.282921E+11 0.106317E+11 0.232695E+11 0.145919E+11 0.867755E+10 0.00 0.00
Minimum of Months 0.110213E+10 0.348011E+09 0.851707E+09 23616059.38 0.538661E+09 0.00 0.00
Maximum of Months 0.370472E+10 0.148328E+10 0.312996E+10 0.258435E+10 0.912570E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.518110E+09 0.676268E+09 0.537906E+09 0.332408E+09 0.205498E+09 0.00 0.00
February 0.644029E+09 0.628759E+09 0.642470E+09 0.406766E+09 0.235705E+09 0.00 0.00
March 0.909199E+09 0.523400E+09 0.848972E+09 0.496816E+09 0.352156E+09 0.00 0.00
April 0.870498E+09 0.435034E+09 0.830479E+09 0.406169E+09 0.424310E+09 0.00 0.00
May 0.117097E+10 0.285060E+09 0.994244E+09 0.416568E+09 0.577676E+09 0.00 0.00
June 0.157591E+10 0.181224E+09 0.117670E+10 0.613199E+09 0.563505E+09 0.00 0.00
July 0.147587E+10 0.184538E+09 0.110072E+10 0.522512E+09 0.578209E+09 0.00 0.00
August 0.148359E+10 0.218029E+09 0.111684E+10 0.610709E+09 0.506134E+09 0.00 0.00
September 0.114707E+10 0.306942E+09 0.908751E+09 0.493593E+09 0.415157E+09 0.00 0.00
October 0.732003E+09 0.606439E+09 0.687068E+09 0.377544E+09 0.309524E+09 0.00 0.00
November 0.513164E+09 0.643945E+09 0.520631E+09 0.294936E+09 0.225695E+09 0.00 0.00
December 0.430460E+09 0.800272E+09 0.469160E+09 0.273094E+09 0.196065E+09 0.00 0.00
               
Annual Sum or Average 0.114709E+11 0.548991E+10 0.983395E+10 0.524431E+10 0.458963E+10 0.00 0.00
Minimum of Months 0.430460E+09 0.181224E+09 0.469160E+09 0.273094E+09 0.196065E+09 0.00 0.00
Maximum of Months 0.157591E+10 0.800272E+09 0.117670E+10 0.613199E+09 0.578209E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 77567351.99 0.106640E+10 0.255295E+09 0.00 0.255295E+09 0.00 0.00
February 90705434.14 0.971432E+09 0.290773E+09 0.00 0.290773E+09 0.00 0.00
March 0.262005E+09 0.796734E+09 0.433932E+09 0.00 0.433932E+09 0.00 0.00
April 0.358840E+09 0.651833E+09 0.522037E+09 2805155.55 0.519231E+09 0.00 0.00
May 0.749974E+09 0.410391E+09 0.734234E+09 22947573.85 0.711287E+09 0.00 0.00
June 0.105725E+10 0.259673E+09 0.783887E+09 82393568.53 0.701494E+09 0.00 0.00
July 0.102961E+10 0.262255E+09 0.763211E+09 47166137.60 0.716045E+09 0.00 0.00
August 0.794937E+09 0.309136E+09 0.616714E+09 13783379.20 0.602931E+09 0.00 0.00
September 0.573777E+09 0.457480E+09 0.500524E+09 114689.91 0.500409E+09 0.00 0.00
October 0.230827E+09 0.898231E+09 0.371421E+09 0.00 0.371421E+09 0.00 0.00
November 0.107588E+09 0.977017E+09 0.273675E+09 0.00 0.273675E+09 0.00 0.00
December 62652285.05 0.125071E+10 0.238057E+09 0.00 0.238057E+09 0.00 0.00
               
Annual Sum or Average 0.539573E+10 0.831129E+10 0.578376E+10 0.169211E+09 0.561455E+10 0.00 0.00
Minimum of Months 62652285.05 0.259673E+09 0.238057E+09 0.00 0.238057E+09 0.00 0.00
Maximum of Months 0.105725E+10 0.125071E+10 0.783887E+09 82393568.53 0.716045E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.584775E+09 0.701607E+09 0.572922E+09 0.366205E+09 0.206717E+09 0.00 0.00
February 0.620189E+09 0.642726E+09 0.619110E+09 0.384719E+09 0.234391E+09 0.00 0.00
March 0.839553E+09 0.539185E+09 0.793526E+09 0.439530E+09 0.353996E+09 0.00 0.00
April 0.717533E+09 0.450816E+09 0.708056E+09 0.299590E+09 0.408466E+09 0.00 0.00
May 0.104432E+10 0.303539E+09 0.885832E+09 0.309711E+09 0.576122E+09 0.00 0.00
June 0.142838E+10 0.208392E+09 0.105457E+10 0.500481E+09 0.554089E+09 0.00 0.00
July 0.119493E+10 0.199782E+09 0.882615E+09 0.319715E+09 0.562901E+09 0.00 0.00
August 0.124271E+10 0.233459E+09 0.934778E+09 0.457575E+09 0.477203E+09 0.00 0.00
September 0.102798E+10 0.331170E+09 0.807360E+09 0.386597E+09 0.420763E+09 0.00 0.00
October 0.778569E+09 0.624155E+09 0.711825E+09 0.408185E+09 0.303641E+09 0.00 0.00
November 0.585839E+09 0.660872E+09 0.571598E+09 0.349423E+09 0.222174E+09 0.00 0.00
December 0.447296E+09 0.808924E+09 0.478553E+09 0.285754E+09 0.192799E+09 0.00 0.00
               
Annual Sum or Average 0.105121E+11 0.570463E+10 0.902075E+10 0.450748E+10 0.451326E+10 0.00 0.00
Minimum of Months 0.447296E+09 0.199782E+09 0.478553E+09 0.285754E+09 0.192799E+09 0.00 0.00
Maximum of Months 0.142838E+10 0.808924E+09 0.105457E+10 0.500481E+09 0.576122E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 0.85 -1.5 -4.5 2.30 -12.1 27.63 226.20 0.01
February -0.2 -2.7 -6.1 3.74 -13.6 32.55 253.27 0.01
March 4.82 0.36 -5.5 4.48 -7.8 54.65 233.06 0.03
April 6.08 2.29 -2.0 5.23 -4.9 81.86 179.11 0.05
May 13.74 7.52 1.82 4.10 2.75 117.64 180.87 0.01
June 22.16 12.46 5.10 4.19 9.76 95.26 290.95 0.00
July 22.71 13.25 6.43 4.25 12.01 110.54 215.12 0.03
August 21.74 12.79 6.20 3.81 10.76 77.72 272.61 0.02
September 18.54 9.35 1.35 4.13 5.52 70.51 233.03 0.01
October 7.12 2.51 -2.7 3.54 -5.8 44.60 216.74 0.01
November 3.03 0.31 -2.9 2.79 -8.8 30.71 220.86 0.01
December -1.0 -4.5 -9.5 4.43 -15.4 27.45 194.75 0.01
                 
Annual Sum or Average 10.02 4.37 -1.0 3.91 -2.2 64.46 226.11 0.02
Minimum of Months -1.0 -4.5 -9.5 2.30 -15.4 27.45 179.11 0.00
Maximum of Months 22.71 13.25 6.43 5.23 12.01 117.64 290.95 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 20-JAN-12:00 6.97 -11.0 0.50 6.55 41.00 961.00
February 20.00 18-FEB-12:00 7.74 -5.0 3.60 6.35 56.00 998.00
March 24.00 14-MAR-12:00 7.90 -12.0 3.10 11.65 160.00 837.50
April 22.00 19-APR-13:09 8.49 -5.7 5.52 11.55 235.67 789.67
May 29.00 17-MAY-12:00 11.92 -3.0 5.10 18.99 432.50 162.00
June 39.40 26-JUN-14:00 15.63 -2.8 4.60 21.96 136.50 752.00
July 37.00 16-JUL-12:00 14.90 -3.0 3.10 26.65 319.50 109.50
August 37.00 16-AUG-13:00 16.36 3.00 3.60 28.27 90.00 895.00
September 32.70 09-SEP-12:00 13.05 -3.9 3.00 16.30 270.50 562.00
October 27.00 11-OCT-13:00 9.73 -9.0 4.60 12.03 89.50 844.00
November 22.00 06-NOV-13:09 7.10 -13.0 2.60 4.92 88.67 883.33
December 22.00 01-DEC-13:00 7.94 -8.0 2.60 5.13 49.00 862.00
                 
Annual Sum or Average                
Minimum of Months 20.00   6.97 -13.0 0.50 4.92 41.00 109.50
Maximum of Months 39.40   16.36 3.00 5.52 28.27 432.50 998.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -19.0 05-JAN-18:00 -19.0 -19.0 1.50 -37.1 0.00 0.00
February -20.0 12-FEB-04:00 -20.0 -20.0 3.60 -39.1 0.00 0.00
March -15.6 19-MAR-06:00 -15.6 -15.6 10.80 -25.3 24.00 0.00
April -8.0 03-APR-02:00 -8.0 -8.0 3.10 -22.2 0.00 0.00
May -1.0 03-MAY-01:00 -2.4 -4.0 4.10 -15.7 0.00 0.00
June 6.60 09-JUN-03:00 3.45 0.00 3.60 -6.9 0.00 0.00
July 9.00 02-JUL-04:00 3.30 -3.0 3.60 -5.3 20.00 184.50
August 11.00 12-AUG-22:00 7.22 4.00 4.10 5.13 0.00 0.00
September -1.7 22-SEP-05:10 -2.9 -4.3 3.60 -15.8 0.00 0.00
October -10.0 30-OCT-03:00 -10.0 -10.0 2.60 -18.6 0.00 0.00
November -15.0 29-NOV-20:00 -15.0 -15.0 3.10 -33.5 0.00 0.00
December -23.0 22-DEC-02:00 -23.0 -23.0 3.60 -42.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -23.0   -23.0 -23.0 1.50 -42.7 0.00 0.00
Maximum of Months 11.00   7.22 4.00 10.80 5.13 24.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 7.55 20-JAN-11:00 20.00 -6.0 2.60 7.95 43.00 971.50
February 7.98 18-FEB-14:00 19.00 -3.0 3.60 5.94 151.00 410.00
March 8.00 31-MAR-17:00 15.00 2.00 2.60 1.58 19.50 261.00
April 12.50 28-APR-13:00 18.00 9.00 9.80 9.72 335.00 196.50
May 14.87 31-MAY-13:00 28.00 7.00 4.60 14.47 157.50 830.50
June 19.65 18-JUN-11:00 29.40 15.50 6.10 16.85 272.50 596.00
July 19.75 30-JUL-13:00 29.00 16.00 3.60 18.99 217.50 412.00
August 18.80 05-AUG-14:09 25.83 15.33 6.62 20.54 196.33 4.00
September 14.95 01-SEP-11:00 24.40 9.40 3.00 10.69 193.50 684.00
October 9.73 11-OCT-13:00 27.00 -9.0 4.60 12.03 89.50 844.00
November 9.33 09-NOV-10:00 20.00 0.00 1.50 11.07 112.00 860.50
December 7.94 01-DEC-13:00 22.00 -8.0 2.60 5.13 49.00 862.00
                 
Annual Sum or Average                
Minimum of Months 7.55   15.00 -9.0 1.50 1.58 19.50 4.00
Maximum of Months 19.75   29.40 16.00 9.80 20.54 335.00 971.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.00 28-JAN-10:00 5.00 5.00 1.00 -6.2 207.00 309.00
February 5.00 19-FEB-14:30 5.00 5.00 1.80 -0.4 188.00 467.00
March 7.00 17-MAR-14:00 8.00 7.39 8.20 1.16 121.50 3.00
April 9.00 28-APR-13:00 18.00 12.50 9.80 9.72 335.00 196.50
May 11.00 21-MAY-21:10 12.83 11.73 2.68 6.78 0.00 0.00
June 15.50 18-JUN-11:00 29.40 19.65 6.10 16.85 272.50 596.00
July 17.00 28-JUL-16:00 20.00 17.92 5.70 15.02 155.00 32.00
August 18.00 04-AUG-01:00 18.00 18.00 2.60 8.74 0.00 0.00
September 12.20 30-SEP-14:00 17.20 13.90 5.10 9.72 209.00 82.50
October 6.00 01-OCT-19:00 9.00 7.28 3.10 3.69 0.00 0.00
November 7.00 09-NOV-23:00 8.00 7.40 4.10 3.06 0.00 0.00
December 1.00 30-DEC-14:00 7.00 4.06 9.80 -1.2 101.00 91.50
                 
Annual Sum or Average                
Minimum of Months 1.00   5.00 4.06 1.00 -6.2 0.00 0.00
Maximum of Months 18.00   29.40 19.65 9.80 16.85 335.00 596.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 8.52 21.53 0.00
February 18.00 13.00 16.00 7.90 29.36 0.00
March 18.00 13.00 16.00 8.65 35.75 0.00
April 18.00 13.00 16.00 10.64 38.62 0.00
May 18.00 13.00 16.00 13.34 48.35 0.00
June 18.00 13.00 16.00 16.03 59.81 0.00
July 18.00 13.00 16.00 17.97 52.29 0.00
August 18.00 13.00 16.00 18.66 51.98 0.00
September 18.00 13.00 16.00 17.88 41.73 0.00
October 18.00 13.00 16.00 15.85 30.82 0.00
November 18.00 13.00 16.00 13.14 23.90 0.00
December 18.00 13.00 16.00 10.46 18.59 0.00
             
Annual Sum or Average 18.00 13.00 16.00 13.28 37.76 0.00
Minimum of Months 18.00 13.00 16.00 7.90 18.59 0.00
Maximum of Months 18.00 13.00 16.00 18.66 59.81 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.589095E+09 -513092839.7 0.00 0.00 744.00 0.00 -76002487.3 59.00 0.00 0.00
February 0.538842E+09 -470008922.9 0.00 0.00 672.00 0.00 -68833338.3 58.99 0.00 0.00
March 0.634566E+09 -560353269.0 0.00 0.00 744.00 0.00 -74212438.1 59.00 0.00 0.00
April 0.539646E+09 -468261125.7 0.00 0.00 720.00 0.00 -71384714.6 58.99 0.00 0.00
May 0.556913E+09 -487191964.9 0.00 0.00 744.00 0.00 -69720682.9 58.98 0.00 0.00
June 0.521053E+09 -457137961.1 0.00 0.00 720.00 0.00 -63915436.4 59.01 0.00 0.00
July 0.461912E+09 -396701068.8 0.00 0.00 744.00 0.00 -65210843.4 58.99 0.00 0.00
August 0.514653E+09 -449186902.4 0.00 0.00 744.00 0.00 -65466060.2 58.99 0.00 0.00
September 0.462275E+09 -398502690.9 0.00 0.00 720.00 0.00 -63772313.7 58.98 0.00 0.00
October 0.508480E+09 -438858694.2 0.00 0.00 744.00 0.00 -69621620.5 58.99 0.00 0.00
November 0.537073E+09 -466070925.8 0.00 0.00 720.00 0.00 -71002270.1 58.98 0.00 0.00
December 0.545575E+09 -469388845.9 0.00 0.00 744.00 0.00 -76186633.0 59.00 0.00 0.00
                     
Annual Sum or Average 0.641008E+10 -0.557476E+10 0.00 0.00 8760.00 0.00 -835328838.5 58.99 0.00 0.00
Minimum of Months 0.461912E+09 -560353269.0 0.00 0.00 672.00 0.00 -76186633.0 58.98 0.00 0.00
Maximum of Months 0.634566E+09 -396701068.8 0.00 0.00 744.00 0.00 -63772313.7 59.01 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.75 0.73 01-JAN-07:49 2273.81 28.17 150.17 248.83 3911.89 34.12 218.33 234.17
February 245.50 0.75 0.73 01-FEB-10:39 3179.42 27.57 129.50 221.00 996.26 24.26 135.67 201.67
March 296.17 0.76 0.73 01-MAR-07:19 818.13 17.97 6.83 245.00 579.98 22.15 176.83 195.17
April 296.67 0.77 0.73 03-APR-10:39 525.35 17.77 0.00 203.50 402.15 22.08 208.33 148.17
May 415.33 0.78 0.73 01-MAY-07:00 455.95 17.65 0.00 273.50 333.38 21.96 287.17 189.00
June 421.50 0.78 0.73 01-JUN-08:00 373.53 17.03 0.00 228.17 279.43 21.43 266.83 111.50
July 430.33 0.78 0.73 02-JUL-08:30 416.06 17.23 0.00 257.00 306.33 21.55 277.00 166.50
August 394.50 0.78 0.73 01-AUG-07:00 460.45 17.27 0.00 249.50 354.75 21.56 254.00 178.67
September 354.00 0.77 0.73 01-SEP-07:00 838.13 18.59 17.00 259.00 480.22 22.14 237.83 221.17
October 262.67 0.75 0.73 01-OCT-06:00 4177.78 27.78 137.17 235.83 734.36 22.88 201.67 198.33
November 257.67 0.75 0.73 01-NOV-08:39 2395.93 27.77 135.00 229.50 1300.30 25.92 168.33 213.83
December 251.17 0.74 0.73 01-DEC-07:49 1539.80 26.13 109.67 222.33 3269.27 33.39 194.17 212.33
                         
Annual Sum or Average 3902.00 0.77     1259.12 20.88 685.33 2873.17 939.10 23.92 2626.17 2270.50
Minimum of Months 245.50 0.74 0.73   373.53 17.03 0.00 203.50 279.43 21.43 135.67 111.50
Maximum of Months 430.33 0.78 0.73   4177.78 28.17 150.17 273.50 3911.89 34.12 287.17 234.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.83 0.73 01-JAN-07:00 1538.38 20.36 82.67 105.67 387.26 21.77 94.33 74.33
February 245.50 0.82 0.73 01-FEB-10:50 1498.45 18.52 43.17 90.33 1509.54 24.58 85.50 80.50
March 296.17 0.81 0.73 01-MAR-07:19 491.37 15.52 1.83 124.67 437.23 20.56 110.00 97.33
April 296.67 0.79 0.73 04-APR-07:10 463.47 15.86 0.00 144.83 392.71 20.81 140.50 103.67
May 415.33 0.79 0.73 01-MAY-06:30 444.14 16.22 0.00 211.17 373.75 21.18 215.17 151.67
June 421.50 0.79 0.73 01-JUN-05:30 448.34 15.73 0.00 188.00 426.46 22.64 209.17 165.00
July 430.33 0.79 0.73 01-JUL-05:40 442.68 15.89 0.00 211.50 382.69 20.92 207.67 156.00
August 394.50 0.80 0.73 01-AUG-05:00 462.54 15.41 0.00 186.33 407.35 20.51 178.00 147.83
September 354.00 0.80 0.73 01-SEP-05:00 516.15 15.85 5.50 166.50 412.49 20.79 143.00 126.50
October 262.67 0.81 0.73 01-OCT-06:49 1433.57 19.03 44.83 111.83 988.73 23.60 112.83 88.17
November 257.67 0.82 0.73 01-NOV-08:39 1173.43 18.90 51.00 103.67 598.08 22.84 102.33 80.50
December 251.17 0.83 0.73 01-DEC-07:00 1532.60 21.15 78.00 94.50 410.96 22.31 94.67 68.67
                         
Annual Sum or Average 3902.00 0.80     786.58 17.06 307.00 1739.00 524.63 21.73 1693.17 1340.17
Minimum of Months 245.50 0.79 0.73   442.68 15.41 0.00 90.33 373.75 20.51 85.50 68.67
Maximum of Months 430.33 0.83 0.73   1538.38 21.15 82.67 211.50 1509.54 24.58 215.17 165.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.91 0.80 30-JAN-12:30 126.80 11.82 0.00 0.00 100.05 16.33 0.00 0.00
February 245.50 0.89 0.74 28-FEB-11:30 152.40 13.33 0.00 0.00 120.56 17.83 1.33 0.00
March 296.17 0.86 0.74 29-MAR-12:30 201.97 14.89 0.00 0.33 150.63 19.01 14.83 0.00
April 296.67 0.81 0.74 10-APR-09:30 269.63 16.32 0.00 28.67 190.37 20.20 71.00 0.00
May 415.33 0.77 0.73 01-MAY-08:20 380.36 17.25 1.17 185.33 223.06 21.14 201.33 2.50
June 421.50 0.77 0.73 01-JUN-05:19 350.04 18.99 33.67 164.50 261.24 24.00 253.83 26.17
July 430.33 0.78 0.73 01-JUL-18:19 329.24 17.18 0.00 160.50 232.45 22.26 248.33 9.17
August 394.50 0.81 0.73 03-AUG-09:20 289.11 16.19 0.00 53.83 190.85 20.08 87.67 0.00
September 354.00 0.84 0.73 03-SEP-15:30 225.41 15.44 0.00 15.00 163.62 19.45 28.50 0.00
October 262.67 0.87 0.74 01-OCT-12:30 188.14 14.58 0.00 0.00 146.15 18.91 0.67 0.00
November 257.67 0.90 0.78 01-NOV-11:30 143.61 12.85 0.00 0.00 114.61 17.37 0.33 0.00
December 251.17 0.91 0.82 31-DEC-12:30 132.36 12.48 0.00 0.00 104.87 17.04 0.00 0.00
                         
Annual Sum or Average 3902.00 0.83     249.36 15.50 34.83 608.17 176.48 19.87 907.83 37.83
Minimum of Months 245.50 0.77 0.73   126.80 11.82 0.00 0.00 100.05 16.33 0.00 0.00
Maximum of Months 430.33 0.91 0.82   380.36 18.99 33.67 185.33 261.24 24.00 253.83 26.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.83 0.73 01-JAN-13:50 1738.23 20.95 82.50 107.83 499.73 22.81 100.00 82.83
February 245.50 0.82 0.73 01-FEB-13:09 1331.36 19.06 45.17 97.67 832.32 23.47 82.17 83.50
March 296.17 0.81 0.73 01-MAR-11:50 430.30 15.84 1.83 124.17 909.23 23.27 117.50 100.83
April 296.67 0.80 0.73 03-APR-12:09 426.40 16.11 0.00 135.50 347.89 20.94 128.17 93.17
May 415.33 0.80 0.73 01-MAY-13:09 436.20 16.46 0.00 201.33 357.25 21.17 203.50 143.83
June 421.50 0.80 0.73 01-JUN-13:09 426.92 15.91 0.00 181.83 393.87 21.09 190.67 156.33
July 430.33 0.80 0.73 01-JUL-13:30 416.45 16.13 0.00 195.67 357.37 21.00 200.83 153.83
August 394.50 0.80 0.73 01-AUG-11:30 401.28 15.59 0.00 157.00 343.17 20.61 144.50 114.33
September 354.00 0.81 0.73 01-SEP-11:00 493.52 16.13 5.50 153.17 370.49 20.99 148.50 122.33
October 262.67 0.80 0.73 01-OCT-11:00 1575.79 19.30 45.50 112.50 760.73 24.02 112.33 92.00
November 257.67 0.82 0.73 01-NOV-11:20 1767.36 21.75 77.17 101.00 965.50 25.44 109.67 84.00
December 251.17 0.82 0.73 01-DEC-13:09 1427.43 21.96 80.67 95.83 366.68 23.05 85.50 70.00
                         
Annual Sum or Average 3902.00 0.80     810.50 17.55 338.33 1663.50 510.10 22.07 1623.33 1297.00
Minimum of Months 245.50 0.80 0.73   401.28 15.59 0.00 95.83 343.17 20.61 82.17 70.00
Maximum of Months 430.33 0.83 0.73   1767.36 21.96 82.50 201.33 965.50 25.44 203.50 156.33



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.478345E+09 5104.78 09-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.558130E+09 5104.78 27-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.273151E+09 5899.01 08-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.175950E+09 5957.98 18-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 8949988.87 5551.71 01-MAY-07:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.111782E+09 3533.79 25-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.214842E+09 4647.85 22-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.268548E+09 5494.87 01-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208970E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.558130E+09 5957.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.813035E+09 5725.00 09-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.127875E+10 5331.42 17-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.120578E+10 6615.74 08-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.974024E+09 7086.40 19-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 0.226916E+09 7469.50 04-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 9313206.65 3853.40 22-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.474176E+09 5183.00 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.629620E+09 5212.56 22-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.625086E+09 6484.54 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.623670E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127875E+10 7469.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.951656E+09 4579.76 09-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.109291E+10 4241.06 27-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.723678E+09 5109.36 08-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.452331E+09 5265.96 27-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 45073757.94 4678.54 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 100068.35 667.12 22-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.282613E+09 4052.07 26-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.514106E+09 4217.26 16-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.627284E+09 5187.35 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.468975E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109291E+10 5265.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218179E+10 5500.26 01-JAN-10:01 0.00 0.00 0.00 0.00 0.00
February 0.230740E+10 5083.52 27-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.167520E+10 5874.45 08-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.102791E+10 6292.37 19-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 0.148579E+09 6632.55 04-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 477900.35 3186.00 22-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.452431E+09 5001.96 27-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.114270E+10 5933.17 07-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.154747E+10 5757.95 01-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104840E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.230740E+10 6632.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.936315E+09 5848.20 20-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.112781E+10 5474.33 27-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.806143E+09 6595.12 08-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.515329E+09 6103.23 18-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 64672505.62 6039.02 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 115515.32 770.10 22-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.275338E+09 4681.35 26-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.499970E+09 4219.23 03-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.627155E+09 6695.79 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.485285E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.112781E+10 6695.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.135450E+09 3921.24 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 53594298.66 3921.24 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 13928807.44 3921.24 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 12932934.89 3921.24 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 993876.53 3196.27 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 4581178.12 3921.24 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 22292019.31 3921.24 01-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.394545E+09 3921.24 07-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.638318E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.394545E+09 3921.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.451478E+09 6706.94 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.485326E+09 6706.94 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.222594E+09 6706.94 19-MAR-06:42 0.00 0.00 0.00 0.00 0.00
April 0.177554E+09 6706.94 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 9462491.17 5007.27 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 126896.87 845.98 22-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.200301E+09 6706.94 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.228991E+09 6706.94 02-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.126391E+10 6706.94 19-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.303974E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.126391E+10 6706.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.229840E+09 4201.36 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.197126E+09 4201.36 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 51920515.87 4201.36 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 36231037.53 4201.36 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 769518.06 3828.07 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 27039944.55 4201.36 23-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 57035753.32 4201.36 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.849804E+09 4201.36 06-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.144977E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.849804E+09 4201.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.647209E+09 6620.95 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.664948E+09 6620.95 05-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.199366E+09 6620.95 19-MAR-06:42 0.00 0.00 0.00 0.00 0.00
April 0.137192E+09 6554.15 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 3013106.29 4541.73 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.134179E+09 6620.95 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.215893E+09 6620.95 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.158933E+10 6620.95 19-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.359113E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158933E+10 6620.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.183485E+09 4201.36 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.114506E+09 4201.36 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 39106408.24 4201.36 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 17963706.73 4201.36 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 690574.37 4201.36 02-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 10345813.39 4201.36 23-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 32263464.31 4201.36 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.790202E+09 4201.36 05-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118856E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.790202E+09 4201.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3168771.54 3168744.50 274.43 25-JAN-16:10 274.43 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.163429E+09 0.159821E+09 1800.06 15-MAR-14:00 1800.06 0.00
April 0.00 0.00 77812336.01 73491832.82 1094.75 21-APR-13:20 1043.76 0.00
May 0.00 0.00 0.822626E+09 0.745280E+09 5309.60 18-MAY-07:02 5182.00 0.00
June 0.00 0.00 0.289424E+10 0.268743E+10 5746.87 21-JUN-07:02 4054.94 0.00
July 0.00 0.00 0.295353E+10 0.267198E+10 5797.73 28-JUL-07:03 3870.87 0.00
August 0.00 0.00 0.317928E+10 0.292179E+10 5786.71 04-AUG-07:02 4024.84 0.00
September 0.00 0.00 0.230012E+10 0.219976E+10 5538.40 06-SEP-07:02 4646.37 0.00
October 0.00 0.00 0.705238E+09 0.678420E+09 5202.67 11-OCT-07:03 5202.67 0.00
November 0.00 0.00 0.124990E+09 0.122015E+09 1688.48 09-NOV-14:00 1619.94 0.00
December 0.00 0.00 8932.71 8932.71 14.28 04-DEC-15:53 14.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.132244E+11 0.122632E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.317928E+10 0.292179E+10 5797.73   5202.67 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.288653E+09 0.288531E+09 3404.40 20-JAN-14:15 3404.40 0.00
February 0.00 0.00 0.106620E+09 0.106620E+09 2179.64 27-FEB-14:15 2179.64 0.00
March 0.00 0.00 0.375618E+09 0.375618E+09 3890.14 15-MAR-13:55 3890.14 0.00
April 0.00 0.00 93395907.23 93350034.61 1520.08 20-APR-13:00 1520.08 0.00
May 0.00 0.00 0.354884E+09 0.351068E+09 2479.55 17-MAY-13:50 2479.55 0.00
June 0.00 0.00 0.226126E+10 0.217679E+10 6091.13 19-JUN-07:02 5804.73 0.00
July 0.00 0.00 0.232507E+10 0.219548E+10 6311.86 24-JUL-07:02 5184.16 0.00
August 0.00 0.00 0.296656E+10 0.284888E+10 6502.12 04-AUG-07:02 4330.98 0.00
September 0.00 0.00 0.266461E+10 0.263686E+10 6130.63 06-SEP-07:02 5354.81 0.00
October 0.00 0.00 0.117143E+10 0.116979E+10 5783.74 10-OCT-11:00 5783.74 0.00
November 0.00 0.00 0.624967E+09 0.624930E+09 5056.31 07-NOV-13:55 5056.31 0.00
December 0.00 0.00 0.207528E+09 0.207528E+09 2720.49 01-DEC-14:25 2720.49 0.00
                 
Annual Sum or Average 0.00 0.00 0.134406E+11 0.130754E+11       0.00
Minimum of Months 0.00 0.00 93395907.23 93350034.61 1520.08   1520.08 0.00
Maximum of Months 0.00 0.00 0.296656E+10 0.284888E+10 6502.12   5804.73 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 87030677.75 87030677.75 1189.96 14-MAR-10:05 1189.96 0.00
April 0.00 0.00 83439969.42 83437355.73 997.02 21-APR-08:54 997.02 0.00
May 0.00 0.00 0.423791E+09 0.417624E+09 4723.18 17-MAY-07:01 4723.18 0.00
June 0.00 0.00 0.198225E+10 0.192552E+10 5118.76 21-JUN-07:02 3935.47 0.00
July 0.00 0.00 0.184074E+10 0.176435E+10 5169.05 28-JUL-07:03 3631.20 0.00
August 0.00 0.00 0.211673E+10 0.204266E+10 5153.27 04-AUG-07:02 3870.41 0.00
September 0.00 0.00 0.147833E+10 0.146446E+10 4908.23 06-SEP-07:02 4567.26 0.00
October 0.00 0.00 0.323742E+09 0.323228E+09 2201.69 11-OCT-10:04 2201.69 0.00
November 0.00 0.00 65084846.98 65084846.98 911.88 09-NOV-13:13 911.88 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.840115E+10 0.817340E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.211673E+10 0.204266E+10 5169.05   4723.18 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 8322995.43 8322995.43 776.89 14-MAR-14:40 776.89 0.00
April 0.00 0.00 846094.66 846094.66 132.97 20-APR-16:00 132.97 0.00
May 0.00 0.00 0.266790E+09 0.260224E+09 2059.71 17-MAY-14:00 2059.71 0.00
June 0.00 0.00 0.213053E+10 0.204267E+10 5691.07 21-JUN-07:02 4101.34 0.00
July 0.00 0.00 0.212682E+10 0.200033E+10 5723.02 28-JUL-07:03 3903.61 0.00
August 0.00 0.00 0.221633E+10 0.210613E+10 5776.12 04-AUG-07:02 4034.43 0.00
September 0.00 0.00 0.148617E+10 0.146123E+10 5431.18 06-SEP-07:02 4859.92 0.00
October 0.00 0.00 0.160153E+09 0.159985E+09 2128.73 11-OCT-14:35 2128.73 0.00
November 0.00 0.00 11594998.09 11594998.09 702.68 09-NOV-13:57 702.68 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.840754E+10 0.805133E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.221633E+10 0.210613E+10 5776.12   4859.92 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 15097386.40 15097386.40 844.54 20-JAN-15:58 844.54 0.00
February 0.00 0.00 1665237.52 1665237.52 462.22 17-FEB-16:38 462.22 0.00
March 0.00 0.00 94076775.52 94076775.52 1875.96 15-MAR-15:55 1875.96 0.00
April 0.00 0.00 45505716.27 45244809.28 1500.07 07-APR-16:00 1500.07 0.00
May 0.00 0.00 0.377025E+09 0.366659E+09 2427.24 31-MAY-15:53 2324.09 0.00
June 0.00 0.00 0.179473E+10 0.173198E+10 6639.50 21-JUN-07:02 4953.27 0.00
July 0.00 0.00 0.166620E+10 0.157920E+10 6514.82 26-JUL-07:02 5467.02 0.00
August 0.00 0.00 0.188481E+10 0.180680E+10 6695.56 04-AUG-07:02 4897.28 0.00
September 0.00 0.00 0.139603E+10 0.137762E+10 6343.62 06-SEP-07:02 5932.02 0.00
October 0.00 0.00 0.378714E+09 0.377847E+09 3186.68 11-OCT-15:54 3186.68 0.00
November 0.00 0.00 93659874.40 93659232.06 1773.33 07-NOV-15:58 1773.33 0.00
December 0.00 0.00 6928303.97 6928303.97 557.43 04-DEC-15:40 557.43 0.00
                 
Annual Sum or Average 0.00 0.00 0.775445E+10 0.749678E+10       0.00
Minimum of Months 0.00 0.00 1665237.52 1665237.52 462.22   462.22 0.00
Maximum of Months 0.00 0.00 0.188481E+10 0.180680E+10 6695.56   5932.02 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 289.93 694.43 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 155.38 696.80 13-FEB-12:17
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 0.00     36.54    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   289.93 696.80  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.367656E+09 0.41 374.09 02-JAN-06:01 1.13
February 0.332641E+09 0.41 374.09 01-FEB-06:01 1.13
March 0.402671E+09 0.45 374.09 01-MAR-06:02 1.12
April 0.350149E+09 0.41 374.09 03-APR-05:01 1.13
May 0.385163E+09 0.43 374.09 01-MAY-05:02 1.12
June 0.385163E+09 0.45 374.09 01-JUN-05:10 1.12
July 0.350149E+09 0.39 374.09 03-JUL-05:10 1.12
August 0.402671E+09 0.45 374.09 01-AUG-05:05 1.11
September 0.350149E+09 0.41 374.09 01-SEP-05:10 1.12
October 0.367656E+09 0.41 374.09 02-OCT-05:05 1.12
November 0.367656E+09 0.43 374.09 01-NOV-05:01 1.13
December 0.350149E+09 0.39 374.09 01-DEC-06:05 1.13
           
Annual Sum or Average 0.441187E+10 0.42      
Minimum of Months 0.332641E+09 0.39 374.09   1.11
Maximum of Months 0.402671E+09 0.45 374.09   1.13



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.417691E+09 0.42 419.54 02-JAN-06:01 1.13
February 0.414115E+09 0.48 419.54 01-FEB-06:01 1.13
March 0.474169E+09 0.50 419.54 01-MAR-06:02 1.13
April 0.407037E+09 0.45 419.54 02-APR-21:55 1.13
May 0.431961E+09 0.43 419.54 01-MAY-05:02 1.13
June 0.431961E+09 0.45 419.54 01-JUN-05:10 1.12
July 0.392691E+09 0.39 419.54 03-JUL-05:10 1.13
August 0.451595E+09 0.45 419.54 01-AUG-05:05 1.12
September 0.394868E+09 0.42 419.54 01-SEP-05:10 1.13
October 0.413347E+09 0.42 419.54 02-OCT-05:05 1.13
November 0.412326E+09 0.43 419.54 01-NOV-05:01 1.13
December 0.439230E+09 0.45 419.54 01-DEC-06:05 1.14
           
Annual Sum or Average 0.508099E+10 0.44      
Minimum of Months 0.392691E+09 0.39 419.54   1.12
Maximum of Months 0.474169E+09 0.50 419.54   1.14



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.368852E+09 0.53 335.62 01-JAN-04:43 1.13
February 0.348796E+09 0.54 335.62 01-FEB-06:01 1.13
March 0.384643E+09 0.53 335.62 01-MAR-06:02 1.13
April 0.328268E+09 0.47 335.62 02-APR-23:03 1.13
May 0.345550E+09 0.43 335.62 01-MAY-05:02 1.13
June 0.345550E+09 0.45 335.62 01-JUN-05:10 1.12
July 0.314634E+09 0.40 335.62 03-JUL-05:10 1.13
August 0.361257E+09 0.45 335.62 01-AUG-05:05 1.12
September 0.314136E+09 0.41 335.62 01-SEP-05:10 1.13
October 0.330105E+09 0.42 335.62 02-OCT-05:05 1.13
November 0.333834E+09 0.44 335.62 01-NOV-05:01 1.13
December 0.384745E+09 0.54 335.62 01-DEC-06:05 1.13
           
Annual Sum or Average 0.416037E+10 0.47      
Minimum of Months 0.314136E+09 0.40 335.62   1.12
Maximum of Months 0.384745E+09 0.54 335.62   1.13



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.445736E+09 0.57 372.53 01-JAN-00:10 1.13
February 0.407721E+09 0.55 372.53 01-FEB-06:01 1.13
March 0.439283E+09 0.54 372.53 01-MAR-06:02 1.13
April 0.373445E+09 0.47 372.53 02-APR-05:05 1.13
May 0.383560E+09 0.43 372.53 01-MAY-05:02 1.13
June 0.383560E+09 0.45 372.53 01-JUN-05:10 1.12
July 0.348691E+09 0.39 372.53 03-JUL-05:10 1.13
August 0.400994E+09 0.45 372.53 01-AUG-05:05 1.12
September 0.348691E+09 0.41 372.53 01-SEP-05:10 1.13
October 0.367304E+09 0.42 372.53 02-OCT-05:05 1.13
November 0.369541E+09 0.43 372.53 01-NOV-05:01 1.13
December 0.452082E+09 0.55 372.53 01-DEC-06:05 1.13
           
Annual Sum or Average 0.472061E+10 0.47      
Minimum of Months 0.348691E+09 0.39 372.53   1.12
Maximum of Months 0.452082E+09 0.57 372.53   1.13



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.466145E+09 0.53 433.21 01-JAN-07:23 1.13
February 0.434970E+09 0.53 433.21 01-FEB-06:01 1.13
March 0.490764E+09 0.52 433.21 01-MAR-06:02 1.13
April 0.419889E+09 0.48 433.21 03-APR-03:03 1.13
May 0.446033E+09 0.43 433.21 01-MAY-05:02 1.13
June 0.447243E+09 0.46 433.21 01-JUN-05:10 1.12
July 0.407235E+09 0.41 433.21 03-JUL-05:10 1.13
August 0.467159E+09 0.46 433.21 01-AUG-05:05 1.12
September 0.406368E+09 0.41 433.21 01-SEP-05:10 1.13
October 0.426243E+09 0.42 433.21 02-OCT-05:05 1.13
November 0.429618E+09 0.43 433.21 01-NOV-05:01 1.13
December 0.489833E+09 0.54 433.21 01-DEC-06:05 1.13
           
Annual Sum or Average 0.533150E+10 0.47      
Minimum of Months 0.406368E+09 0.41 433.21   1.12
Maximum of Months 0.490764E+09 0.54 433.21   1.13



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:01 0.00 0.00 42.95 0.00
February 0.01 0.00 0.00 01-FEB-07:01 0.00 0.00 7.98 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 7.84 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 7.84 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 7.84 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 7.84 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 7.84 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 7.84 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 7.84 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 7.84 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 7.84 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00 7.84 0.00
                 
Annual Sum or Average 0.03 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 7.84 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 42.95 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 48.89 48.89 289.93 694.43 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 7.98 7.98 155.38 696.80 13-FEB-12:17
March 0.00 0.00 01-MAR-00:10 7.84 7.84 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 7.84 7.84 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 7.84 7.84 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 7.84 7.84 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 7.84 7.84 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 7.84 7.84 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:05 7.84 7.84 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 7.84 7.84 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 7.84 7.84 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 7.84 7.84 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 0.00         36.54    
Minimum of Months 0.00 0.00   7.84 7.84 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 289.93 696.80  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.651374E+09 0.00 0.00
February 0.00 0.00 0.00 0.630439E+09 0.00 0.00
March 0.00 0.00 0.00 0.588303E+09 0.00 0.00
April 0.00 0.00 0.00 0.463468E+09 0.00 0.00
May 0.00 0.00 0.00 0.566747E+09 0.00 0.00
June 0.00 0.00 0.00 0.102491E+10 0.00 0.00
July 0.00 0.00 0.00 0.985483E+09 0.00 0.00
August 0.00 0.00 0.00 0.108840E+10 0.00 0.00
September 0.00 0.00 0.00 0.835091E+09 0.00 0.00
October 0.00 0.00 0.00 0.602598E+09 0.00 0.00
November 0.00 0.00 0.00 0.548378E+09 0.00 0.00
December 0.00 0.00 0.00 0.479361E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.846456E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.463468E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.108840E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.933583E+09 0.00 0.00
February 0.00 0.00 0.00 0.110638E+10 0.00 0.00
March 0.00 0.00 0.00 0.113444E+10 0.00 0.00
April 0.00 0.00 0.00 0.854821E+09 0.00 0.00
May 0.00 0.00 0.00 0.591861E+09 0.00 0.00
June 0.00 0.00 0.00 0.959081E+09 0.00 0.00
July 0.00 0.00 0.00 0.917963E+09 0.00 0.00
August 0.00 0.00 0.00 0.111255E+10 0.00 0.00
September 0.00 0.00 0.00 0.962899E+09 0.00 0.00
October 0.00 0.00 0.00 0.931869E+09 0.00 0.00
November 0.00 0.00 0.00 0.920611E+09 0.00 0.00
December 0.00 0.00 0.00 0.772322E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.111984E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.591861E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.113444E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.910401E+09 0.00 0.00
February 0.00 0.00 0.00 0.937329E+09 0.00 0.00
March 0.00 0.00 0.00 0.787835E+09 0.00 0.00
April 0.00 0.00 0.00 0.578823E+09 0.00 0.00
May 0.00 0.00 0.00 0.457490E+09 0.00 0.00
June 0.00 0.00 0.00 0.798003E+09 0.00 0.00
July 0.00 0.00 0.00 0.729365E+09 0.00 0.00
August 0.00 0.00 0.00 0.833719E+09 0.00 0.00
September 0.00 0.00 0.00 0.636643E+09 0.00 0.00
October 0.00 0.00 0.00 0.584709E+09 0.00 0.00
November 0.00 0.00 0.00 0.666559E+09 0.00 0.00
December 0.00 0.00 0.00 0.698983E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.861986E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.457490E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.937329E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.153522E+10 0.00 0.00
February 0.00 0.00 0.00 0.149667E+10 0.00 0.00
March 0.00 0.00 0.00 0.121443E+10 0.00 0.00
April 0.00 0.00 0.00 0.833278E+09 0.00 0.00
May 0.00 0.00 0.00 0.497563E+09 0.00 0.00
June 0.00 0.00 0.00 0.874577E+09 0.00 0.00
July 0.00 0.00 0.00 0.826252E+09 0.00 0.00
August 0.00 0.00 0.00 0.901419E+09 0.00 0.00
September 0.00 0.00 0.00 0.675886E+09 0.00 0.00
October 0.00 0.00 0.00 0.674141E+09 0.00 0.00
November 0.00 0.00 0.00 0.977489E+09 0.00 0.00
December 0.00 0.00 0.00 0.112766E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.116346E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.497563E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.153522E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.101529E+10 0.00 0.00
February 0.00 0.00 0.00 0.104654E+10 0.00 0.00
March 0.00 0.00 0.00 0.939064E+09 0.00 0.00
April 0.00 0.00 0.00 0.694765E+09 0.00 0.00
May 0.00 0.00 0.00 0.555712E+09 0.00 0.00
June 0.00 0.00 0.00 0.873807E+09 0.00 0.00
July 0.00 0.00 0.00 0.794714E+09 0.00 0.00
August 0.00 0.00 0.00 0.905589E+09 0.00 0.00
September 0.00 0.00 0.00 0.719432E+09 0.00 0.00
October 0.00 0.00 0.00 0.694508E+09 0.00 0.00
November 0.00 0.00 0.00 0.764042E+09 0.00 0.00
December 0.00 0.00 0.00 0.807108E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.981058E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.555712E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.104654E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.367656E+09 3168771.54 0.613795E+09 0.00 0.00 0.00 0.00 0.00
February 0.332641E+09 0.00 0.611724E+09 0.00 0.00 0.00 0.00 0.00
March 0.402671E+09 0.163429E+09 0.287080E+09 0.00 0.00 0.00 0.00 0.00
April 0.350149E+09 77812336.01 0.188883E+09 0.00 0.00 0.00 0.00 0.00
May 0.385163E+09 0.822626E+09 9943865.40 0.00 0.00 0.00 0.00 0.00
June 0.385163E+09 0.289424E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.350149E+09 0.295353E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.402671E+09 0.317928E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350149E+09 0.230012E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367656E+09 0.705238E+09 0.116363E+09 0.00 0.00 0.00 0.00 0.00
November 0.367656E+09 0.124990E+09 0.237134E+09 0.00 0.00 0.00 0.00 0.00
December 0.350149E+09 8932.71 0.663093E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.441187E+10 0.132244E+11 0.272802E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.332641E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402671E+09 0.317928E+10 0.663093E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.417691E+09 0.288653E+09 0.126451E+10 0.00 0.00 0.00 0.00 0.00
February 0.414115E+09 0.106620E+09 0.176407E+10 0.00 0.00 0.00 0.00 0.00
March 0.474169E+09 0.375618E+09 0.142838E+10 0.00 0.00 0.00 0.00 0.00
April 0.407037E+09 93395907.23 0.115158E+10 0.00 0.00 0.00 0.00 0.00
May 0.431961E+09 0.354884E+09 0.236379E+09 0.00 0.00 0.00 0.00 0.00
June 0.431961E+09 0.226126E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.392691E+09 0.232507E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.451595E+09 0.296656E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.394868E+09 0.266461E+10 9440103.52 0.00 0.00 0.00 0.00 0.00
October 0.413347E+09 0.117143E+10 0.674477E+09 0.00 0.00 0.00 0.00 0.00
November 0.412326E+09 0.624967E+09 0.858611E+09 0.00 0.00 0.00 0.00 0.00
December 0.439230E+09 0.207528E+09 0.188900E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.508099E+10 0.134406E+11 0.927644E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.392691E+09 93395907.23 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.474169E+09 0.296656E+10 0.188900E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.368852E+09 0.00 0.118150E+10 0.00 0.00 0.00 0.00 0.00
February 0.348796E+09 0.00 0.129004E+10 0.00 0.00 0.00 0.00 0.00
March 0.384643E+09 87030677.75 0.775598E+09 0.00 0.00 0.00 0.00 0.00
April 0.328268E+09 83439969.42 0.488562E+09 0.00 0.00 0.00 0.00 0.00
May 0.345550E+09 0.423791E+09 45843276.00 0.00 0.00 0.00 0.00 0.00
June 0.345550E+09 0.198225E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.314634E+09 0.184074E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.361257E+09 0.211673E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.314136E+09 0.147833E+10 100068.35 0.00 0.00 0.00 0.00 0.00
October 0.330105E+09 0.323742E+09 0.309653E+09 0.00 0.00 0.00 0.00 0.00
November 0.333834E+09 65084846.98 0.571142E+09 0.00 0.00 0.00 0.00 0.00
December 0.384745E+09 0.00 0.147709E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.416037E+10 0.840115E+10 0.613952E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.314136E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384745E+09 0.211673E+10 0.147709E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.445736E+09 0.00 0.282900E+10 0.00 0.00 0.00 0.00 0.00
February 0.407721E+09 0.00 0.297235E+10 0.00 0.00 0.00 0.00 0.00
March 0.439283E+09 8322995.43 0.187457E+10 0.00 0.00 0.00 0.00 0.00
April 0.373445E+09 846094.66 0.116510E+10 0.00 0.00 0.00 0.00 0.00
May 0.383560E+09 0.266790E+09 0.151592E+09 0.00 0.00 0.00 0.00 0.00
June 0.383560E+09 0.213053E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.348691E+09 0.212682E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.400994E+09 0.221633E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.348691E+09 0.148617E+10 477900.35 0.00 0.00 0.00 0.00 0.00
October 0.367304E+09 0.160153E+09 0.586610E+09 0.00 0.00 0.00 0.00 0.00
November 0.369541E+09 11594998.09 0.135859E+10 0.00 0.00 0.00 0.00 0.00
December 0.452082E+09 0.00 0.313681E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.472061E+10 0.840754E+10 0.140751E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.348691E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.452082E+09 0.221633E+10 0.313681E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.466145E+09 15097386.40 0.111980E+10 0.00 0.00 0.00 0.00 0.00
February 0.434970E+09 1665237.52 0.124232E+10 0.00 0.00 0.00 0.00 0.00
March 0.490764E+09 94076775.52 0.845249E+09 0.00 0.00 0.00 0.00 0.00
April 0.419889E+09 45505716.27 0.533293E+09 0.00 0.00 0.00 0.00 0.00
May 0.446033E+09 0.377025E+09 65363079.99 0.00 0.00 0.00 0.00 0.00
June 0.447243E+09 0.179473E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.407235E+09 0.166620E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.467159E+09 0.188481E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.406368E+09 0.139603E+10 115515.32 0.00 0.00 0.00 0.00 0.00
October 0.426243E+09 0.378714E+09 0.285684E+09 0.00 0.00 0.00 0.00 0.00
November 0.429618E+09 93659874.40 0.532233E+09 0.00 0.00 0.00 0.00 0.00
December 0.489833E+09 6928303.97 0.141736E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.533150E+10 0.775445E+10 0.604141E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.406368E+09 1665237.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.490764E+09 0.188481E+10 0.141736E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.367656E+09 0.00 0.00 0.283029E+09 689555.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.332641E+09 0.00 0.00 0.297798E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.402671E+09 0.00 0.00 0.150970E+09 34661778.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.350149E+09 0.00 0.00 96654472.10 16664888.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.385163E+09 0.00 0.00 5060624.92 0.176523E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.385163E+09 0.00 0.00 0.00 0.639750E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.350149E+09 0.00 0.00 0.00 0.635335E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.402671E+09 0.00 0.00 0.00 0.685734E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350149E+09 0.00 0.00 1240228.67 0.483703E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367656E+09 0.00 0.00 87512411.79 0.147430E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.367656E+09 0.00 0.00 0.154285E+09 26436965.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.350149E+09 0.00 0.00 0.129210E+09 1954.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.441187E+10 0.00 0.00 0.120576E+10 0.284693E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.332641E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402671E+09 0.00 0.00 0.297798E+09 0.685734E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.417691E+09 0.00 0.00 0.456550E+09 59342515.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.414115E+09 0.00 0.00 0.669811E+09 22454492.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.474169E+09 0.00 0.00 0.582877E+09 77397517.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.407037E+09 0.00 0.00 0.427916E+09 19867685.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.431961E+09 0.00 0.00 80853667.62 79046727.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.431961E+09 0.00 0.00 0.00 0.527121E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.392691E+09 0.00 0.00 0.00 0.525272E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.451595E+09 0.00 0.00 0.00 0.660959E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.394868E+09 0.00 0.00 6280334.29 0.561750E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.413347E+09 0.00 0.00 0.284200E+09 0.234322E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.412326E+09 0.00 0.00 0.382295E+09 0.125990E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.439230E+09 0.00 0.00 0.290003E+09 43089796.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.508099E+10 0.00 0.00 0.318079E+10 0.293661E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.392691E+09 0.00 0.00 0.00 19867685.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.474169E+09 0.00 0.00 0.669811E+09 0.660959E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.368852E+09 0.00 0.00 0.541548E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.348796E+09 0.00 0.00 0.588533E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.384643E+09 0.00 0.00 0.384526E+09 18666172.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.328268E+09 0.00 0.00 0.232679E+09 17875191.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.345550E+09 0.00 0.00 18881258.70 93059346.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.345550E+09 0.00 0.00 0.00 0.452453E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.314634E+09 0.00 0.00 0.00 0.414731E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.361257E+09 0.00 0.00 0.00 0.472462E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.314136E+09 0.00 0.00 1374614.35 0.321132E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.330105E+09 0.00 0.00 0.185434E+09 69170727.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.333834E+09 0.00 0.00 0.318777E+09 13948271.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.384745E+09 0.00 0.00 0.314238E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.416037E+10 0.00 0.00 0.258599E+10 0.187350E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.314136E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384745E+09 0.00 0.00 0.588533E+09 0.472462E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.445736E+09 0.00 0.00 0.108948E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.407721E+09 0.00 0.00 0.108895E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.439283E+09 0.00 0.00 0.773326E+09 1818340.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.373445E+09 0.00 0.00 0.459648E+09 184638.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.383560E+09 0.00 0.00 54378911.70 59624411.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.383560E+09 0.00 0.00 0.00 0.491018E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.348691E+09 0.00 0.00 0.00 0.477561E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.400994E+09 0.00 0.00 0.00 0.500425E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.348691E+09 0.00 0.00 1567030.37 0.325629E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367304E+09 0.00 0.00 0.271990E+09 34847387.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.369541E+09 0.00 0.00 0.605448E+09 2498846.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.452082E+09 0.00 0.00 0.675575E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.472061E+10 0.00 0.00 0.502036E+10 0.189361E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.348691E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.452082E+09 0.00 0.00 0.108948E+10 0.500425E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.466145E+09 0.00 0.00 0.545893E+09 3254186.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.434970E+09 0.00 0.00 0.611212E+09 360352.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.490764E+09 0.00 0.00 0.428054E+09 20246357.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.419889E+09 0.00 0.00 0.265078E+09 9797557.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.446033E+09 0.00 0.00 25839138.86 83840343.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.447243E+09 0.00 0.00 0.00 0.426564E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.407235E+09 0.00 0.00 0.00 0.387479E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.467159E+09 0.00 0.00 0.00 0.438430E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.406368E+09 0.00 0.00 1385840.50 0.311678E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.426243E+09 0.00 0.00 0.187274E+09 80991042.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.429618E+09 0.00 0.00 0.314451E+09 19972001.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.489833E+09 0.00 0.00 0.315775E+09 1500023.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.533150E+10 0.00 0.00 0.269496E+10 0.178411E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.406368E+09 0.00 0.00 0.00 360352.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.490764E+09 0.00 0.00 0.611212E+09 0.438430E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118599E+10 0.00 0.00 47782.68 0.00 0.457099E+09 31576026.55 0.00 0.19
February 0.114368E+10 0.00 0.00 0.00 0.00 0.443509E+09 0.00 0.00 0.19
March 0.116812E+10 0.00 0.00 1016417.74 0.00 0.213191E+09 0.205899E+09 0.00 0.21
April 0.976437E+09 0.00 0.00 483738.61 0.00 0.155515E+09 0.134347E+09 0.00 0.19
May 0.512203E+09 0.00 0.00 3798825.37 0.00 5000300.82 0.529352E+09 0.00 0.20
June 0.124456E+09 9876310.99 0.00 11581684.88 695879.21 0.00 0.242289E+09 0.00 0.21
July 85132660.51 28443082.01 0.00 10385753.57 442541.17 0.00 0.178099E+09 0.00 0.18
August 0.112544E+09 12172849.99 0.00 15010388.78 336894.16 0.00 0.304693E+09 0.00 0.21
September 0.200053E+09 0.00 0.00 11781480.02 0.00 0.00 0.464419E+09 0.00 0.19
October 0.833849E+09 0.00 0.00 4474048.99 0.00 62520636.71 0.582391E+09 0.00 0.19
November 0.130607E+10 0.00 0.00 815060.04 0.00 0.125361E+09 0.219759E+09 0.00 0.20
December 0.129370E+10 0.00 0.00 656.22 0.00 0.452498E+09 2031860.27 0.00 0.18
                   
Annual Sum or Average 0.894224E+10 50492242.98 0.00 59395836.90 1475314.54 0.191469E+10 0.289486E+10 0.00 0.19
Minimum of Months 85132660.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.130607E+10 28443082.01 0.00 15010388.78 695879.21 0.457099E+09 0.582391E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.358031E+09 0.00 0.00 1447636.50 0.00 0.491902E+09 0.131808E+09 0.00 0.19
February 0.346612E+09 0.00 0.00 656059.92 0.00 0.585042E+09 0.108209E+09 0.00 0.21
March 0.287859E+09 0.00 0.00 1721344.62 0.00 0.490693E+09 0.111843E+09 0.00 0.22
April 0.225730E+09 0.00 0.00 419778.46 0.00 0.383767E+09 42531034.30 0.00 0.19
May 0.264297E+09 1662163.01 0.00 849823.98 154902.82 91833498.74 94067746.29 0.00 0.20
June 59498454.99 82841121.41 0.00 3196060.21 8455400.38 0.00 49673062.77 0.00 0.20
July 55429325.04 83812161.70 0.00 2865948.10 6048239.77 0.00 34320496.23 0.00 0.18
August 76178740.65 65981860.24 0.00 6473481.76 5562446.34 0.00 73976054.33 0.00 0.21
September 0.119214E+09 13318683.34 0.00 9094710.63 960807.09 4366525.29 0.125218E+09 0.00 0.19
October 0.258101E+09 0.00 0.00 6122268.27 0.00 0.273225E+09 0.247667E+09 0.00 0.19
November 0.399496E+09 0.00 0.00 3377315.11 0.00 0.331185E+09 0.192079E+09 0.00 0.20
December 0.313240E+09 0.00 0.00 1073089.09 0.00 0.776549E+09 0.110233E+09 0.00 0.20
                   
Annual Sum or Average 0.276369E+10 0.247616E+09 0.00 37297516.66 21181796.40 0.342856E+10 0.132162E+10 0.00 0.20
Minimum of Months 55429325.04 0.00 0.00 419778.46 0.00 0.00 34320496.23 0.00 0.18
Maximum of Months 0.399496E+09 83812161.70 0.00 9094710.63 8455400.38 0.776549E+09 0.247667E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 98668679.21 0.00 0.00 0.00 0.00 0.541455E+09 0.00 0.00 0.21
February 99171441.81 0.00 0.00 0.00 0.00 0.544932E+09 0.00 0.00 0.22
March 0.166841E+09 0.00 0.00 399386.15 0.00 0.336701E+09 34197820.13 0.00 0.22
April 0.162042E+09 0.00 0.00 397223.90 0.00 0.198340E+09 43502738.76 0.00 0.19
May 0.141064E+09 692992.90 0.00 1570056.94 17899.04 32734878.99 0.119780E+09 0.00 0.20
June 29064789.27 51954892.02 0.00 4177112.74 2939300.44 0.00 31938848.18 0.00 0.20
July 23457612.01 59777130.46 0.00 3032541.66 2390709.33 0.00 27303696.61 0.00 0.18
August 33783000.36 40683735.34 0.00 5957442.32 1973950.24 0.00 54017104.25 0.00 0.21
September 70783612.60 6655021.14 0.00 5956588.09 267697.37 94422.85 85605510.94 0.00 0.19
October 0.182425E+09 0.00 0.00 1651265.49 0.00 0.162847E+09 0.124424E+09 0.00 0.19
November 0.189146E+09 0.00 0.00 255869.52 0.00 0.326388E+09 32944487.53 0.00 0.20
December 96556953.75 0.00 0.00 0.00 0.00 0.678912E+09 0.00 0.00 0.22
                   
Annual Sum or Average 0.129300E+10 0.159764E+09 0.00 23397486.80 7589556.43 0.282240E+10 0.553714E+09 0.00 0.20
Minimum of Months 23457612.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.189146E+09 59777130.46 0.00 5957442.32 2939300.44 0.678912E+09 0.124424E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70803732.62 0.00 0.00 0.00 0.00 0.112769E+10 0.00 0.00 0.23
February 11817565.78 0.00 0.00 0.00 0.00 0.116649E+10 0.00 0.00 0.23
March 0.165778E+09 0.00 0.00 18925.66 0.00 0.776233E+09 11553564.44 0.00 0.22
April 0.212088E+09 0.00 0.00 0.00 0.00 0.496333E+09 0.00 0.00 0.20
May 0.325405E+09 165961.41 0.00 751152.09 4513.51 81432760.16 0.114092E+09 0.00 0.20
June 59553456.95 52656826.82 0.00 4480032.12 4113449.49 0.00 66721152.11 0.00 0.20
July 51922117.00 64529791.82 0.00 3685687.19 3111255.73 0.00 45424249.05 0.00 0.18
August 76574715.10 36665927.85 0.00 6762382.36 2958458.37 0.00 0.105787E+09 0.00 0.21
September 0.138146E+09 1346640.70 0.00 5988883.53 359220.90 156630.63 0.159179E+09 0.00 0.19
October 0.400965E+09 0.00 0.00 601785.01 0.00 0.307326E+09 0.107818E+09 0.00 0.19
November 0.217909E+09 0.00 0.00 49851.90 0.00 0.703702E+09 15142054.34 0.00 0.20
December 51142322.36 0.00 0.00 0.00 0.00 0.135634E+10 0.00 0.00 0.23
                   
Annual Sum or Average 0.178211E+10 0.155365E+09 0.00 22338699.86 10546898.00 0.601571E+10 0.625716E+09 0.00 0.21
Minimum of Months 11817565.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.400965E+09 64529791.82 0.00 6762382.36 4113449.49 0.135634E+10 0.159179E+09 0.00 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145112E+09 0.00 0.00 56219.78 0.00 0.496061E+09 10097327.18 0.00 0.21
February 0.134191E+09 0.00 0.00 7585.60 0.00 0.506625E+09 1599750.35 0.00 0.21
March 0.163810E+09 0.00 0.00 323239.85 0.00 0.358416E+09 34384944.95 0.00 0.22
April 0.171585E+09 0.00 0.00 129351.19 0.00 0.223276E+09 21521557.26 0.00 0.19
May 0.177087E+09 300849.77 0.00 945683.74 6087.65 37082172.48 0.103832E+09 0.00 0.20
June 36915056.62 34768490.27 0.00 3194150.90 1397718.66 0.00 36991239.90 0.00 0.21
July 31271120.35 43781976.35 0.00 2596678.56 1350878.86 0.00 26203951.82 0.00 0.18
August 43795325.34 24873541.24 0.00 4832203.09 760726.34 0.00 64491657.41 0.00 0.21
September 77917166.95 1258751.92 0.00 5110336.21 67628.35 95157.06 0.101555E+09 0.00 0.19
October 0.204862E+09 0.00 0.00 1540221.39 0.00 0.163900E+09 0.130850E+09 0.00 0.19
November 0.212177E+09 0.00 0.00 374616.70 0.00 0.319234E+09 41991239.12 0.00 0.20
December 0.136708E+09 0.00 0.00 14603.92 0.00 0.647952E+09 5270999.12 0.00 0.21
                   
Annual Sum or Average 0.153543E+10 0.104984E+09 0.00 19124890.93 3583039.86 0.275264E+10 0.578790E+09 0.00 0.20
Minimum of Months 31271120.35 0.00 0.00 7585.60 0.00 0.00 1599750.35 0.00 0.18
Maximum of Months 0.212177E+09 43781976.35 0.00 5110336.21 1397718.66 0.647952E+09 0.130850E+09 0.00 0.22



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:30:09

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.502346E+11 0.198806E+10 0.00 0.127756E+11 0.189852E+190
February 0.682423E+11 0.313663E+10 0.00 0.120556E+11 0.189378E+190
March 0.913911E+11 0.395098E+10 0.00 0.110461E+11 0.193752E+190
April 0.100770E+12 0.416805E+10 0.00 0.985337E+10 0.187410E+190
May 0.125434E+12 0.432710E+10 0.00 0.712771E+10 0.207403E+190
June 0.138292E+12 0.395632E+10 0.00 0.334303E+10 0.215640E+190
July 0.127705E+12 0.350073E+10 0.00 0.289477E+10 0.211266E+190
August 0.124734E+12 0.359158E+10 0.00 0.321956E+10 0.222329E+190
September 0.889936E+11 0.284816E+10 0.00 0.553039E+10 0.196595E+190
October 0.692142E+11 0.311460E+10 0.00 0.113855E+11 0.181851E+190
November 0.564081E+11 0.247394E+10 0.00 0.122401E+11 0.171572E+190
December 0.372145E+11 0.281623E+10 0.00 0.137813E+11 0.189524E+190
           
Annual Sum or Average 0.107863E+13 0.398724E+11 0.00 0.105253E+12 0.235657E+191
Minimum of Months 0.372145E+11 0.198806E+10 0.00 0.289477E+10 0.171572E+190
Maximum of Months 0.138292E+12 0.432710E+10 0.00 0.137813E+11 0.222329E+190