Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:30:10


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 165.73 324.22 324.22
Net Site Energy 165.73 324.22 324.22
Total Source Energy 524.86 1026.80 1026.80
Net Source Energy 524.86 1026.80 1026.80


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 33.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 165.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 33.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 24.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 22.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 33.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 24.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 22.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 158.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 324.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 158.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 324.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 165.726 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 165.726 100.00
     
Total On-Site and Utility Electric Sources 165.726 100.00
Total Electricity End Uses 165.726 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 298.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 844.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.0938 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.0938 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.0938 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.0938 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.0938 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.0938 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.0938 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.0938 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.0938 9.29 6.7800  
Conditioned Total 511.16             6.0938 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.0938 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUN-15:00 27-MAR-06:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 1522.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8024.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1742.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2023.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2718.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 17833.68 1522.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 1522.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8024.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1742.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2023.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2718.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 107.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 84.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 76.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 72.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 524.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 209.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 148.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 142.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1026.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 209.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 148.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 142.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1026.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.331613
PERIMETER_ZN_1 DIRECT AIR 0.408540
PERIMETER_ZN_2 DIRECT AIR 0.303639
PERIMETER_ZN_3 DIRECT AIR 0.403745
PERIMETER_ZN_4 DIRECT AIR 0.358535
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.331613 0.331613 0.331613 0.331613 0.331613 0.331613 1.00 1.00 0.331613
PSZ-AC:2 0.408540 0.408540 0.408540 0.408540 0.408540 0.408540 1.00 1.00 0.408540
PSZ-AC:3 0.303639 0.303639 0.303639 0.303639 0.303639 0.303639 1.00 1.00 0.303639
PSZ-AC:4 0.403745 0.403745 0.403745 0.403745 0.403745 0.403745 1.00 1.000000 0.403745
PSZ-AC:5 0.358535 0.358535 0.358535 0.358535 0.358535 0.358535 1.00 1.00 0.358535
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.331613 0.064622
PSZ-AC:2_OA_CONTROLLER 0.408540 0.048988
PSZ-AC:3_OA_CONTROLLER 0.303639 0.029060
PSZ-AC:4_OA_CONTROLLER 0.403745 0.048988
PSZ-AC:5_OA_CONTROLLER 0.358535 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.331613 6164.70 0.800379
PSZ-AC:2 HP COOLING COIL 0.408540 7134.16 0.800516
PSZ-AC:3 HP COOLING COIL 0.303639 5026.31 0.800655
PSZ-AC:4 HP COOLING COIL 0.403745 7059.90 0.800049
PSZ-AC:5 HP COOLING COIL 0.358535 5935.03 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.331613 0.331613 0.331613 0.331613 6164.70 6164.70 40.00 2804.01 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.408540 0.408540 0.408540 0.408540 7134.16 7134.16 40.00 3672.71 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.303639 0.303639 0.303639 0.303639 5026.31 5026.31 40.00 2270.53 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.403745 0.403745 0.403745 0.403745 7059.90 7059.90 40.00 3604.54 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.358535 0.358535 0.358535 0.358535 5935.03 5935.03 40.00 2260.93 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.331613
PSZ-AC:2 FAN 0.408540
PSZ-AC:3 FAN 0.303639
PSZ-AC:4 FAN 0.403745
PSZ-AC:5 FAN 0.358535
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.331613 6164.70
PSZ-AC:2 HEATING COIL 0.408540 7134.16
PSZ-AC:3 HEATING COIL 0.303639 5026.31
PSZ-AC:4 HEATING COIL 0.403745 7059.90
PSZ-AC:5 HEATING COIL 0.358535 5935.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2804.01
PSZ-AC:2_SUPPHEATCOIL 3672.71
PSZ-AC:3_SUPPHEATCOIL 2270.53
PSZ-AC:4_SUPPHEATCOIL 3604.54
PSZ-AC:5_SUPPHEATCOIL 2260.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 911.976 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 911.976
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 1.203E-002 1.060E-004 1.424E-004 0.125 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 8.017E-003 1.191E-004 1.424E-004 0.141 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 1.203E-002 1.060E-004 1.361E-004 0.125 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 8.017E-003 1.191E-004 1.424E-004 0.141 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1137E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.2367E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1972E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3064E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.0846E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 9.0105E-004
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.9490E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.4114E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.4949E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 5.8564E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.3827E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 6.0605E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.3012E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.3709E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.3709E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.8142E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.5804E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.5610E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.6909E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.0182E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.8881E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.4264E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.8006E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6773E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1141E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.2495E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1991E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3244E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.0923E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.0596E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.9164E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.3398E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.0627E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.0771E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1542E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1669E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.6889E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.7883E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.6914E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.7405E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.0590E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.0618E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1510E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1534E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.6628E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.6814E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.6767E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.6863E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7019E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.0749E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7969E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.1677E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.2633E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.4966E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.2630E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.0214E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.7445E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.6751E-004
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.0894E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.7786E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.5183E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.8563E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.1908E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.6168E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3282E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.6205E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.6932E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1789E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.4296E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9553E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0319E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9280E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 9.5502E-003
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.4265E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.0016E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.2277E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.9264E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.8175E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.6144E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.0693E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0114E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.2670E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.7867E-004
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.2448E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.2612E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 9.6796E-004
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.2223E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.6881E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2332E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.0300E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.4144E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.0344E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.8433E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.2685E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.9068E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.3116E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.6224E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1601E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0699E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6515E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0277E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.1813E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.5564E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6125E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.6469E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.5808E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.8128E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.9386E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.4960E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.2443E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7002E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8862E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3335E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.3116E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.4846E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.2265E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.8732E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.3068E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9723E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.4551E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.8508E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.9740E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.1033E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.1990E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.5741E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.6352E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.6983E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.7529E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.8148E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.8396E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.0746E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.0941E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.5533E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.5661E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6816E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.6920E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.9674E-004
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0867E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.3559E-004
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0212E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.4407E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.6695E-004
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.2325E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.6949E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.2130E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.5824E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.1352E-003
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2540E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.7742E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2592E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.5992E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.0426E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3166E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.5476E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.6116E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0510E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.1998E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.7185E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.0289E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9056E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.8631E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.8301E-004
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.9873E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.6932E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7284E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.0340E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1999E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.6233E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3419.23601 4103.08321 0.27634 0.33161 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 39.64733 5.62931E-003 149.65740 8.05449 6.46220E-002 0.00000
2 CORE_ZN Heating 819.84253 983.81103 3.89335E-002 6.46220E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 149.65740 8.05449 6.46220E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4212.43864 5054.92637 0.34045 0.40854 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 39.82467 5.62958E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 2167.93230 2601.51877 0.10295 0.12354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3130.87980 3757.05576 0.25303 0.30364 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 37.07600 5.62532E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1363.70002 1636.44003 6.47604E-002 7.77125E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 4163.00344 4995.60413 0.33645 0.40375 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 39.82467 5.62958E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 2110.27996 2532.33596 0.10021 0.12026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3696.90483 4436.28579 0.29878 0.35854 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 37.82967 5.62649E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1355.58690 1626.70428 6.43752E-002 7.72502E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 5158.25 0.33161 0.33161 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2804.01 6.46220E-002 6.46220E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 5834.29 0.40854 0.40854 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 3672.71 0.12354 0.12354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 4119.90 0.30364 0.30364 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2270.53 7.77125E-002 7.77125E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 5775.88 0.40375 0.40375 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 3604.54 0.12026 0.12026 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4812.69 0.35854 0.35854 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2260.93 7.72502E-002 7.72502E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.33161
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40854
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30364
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40375
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.35854
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.33161
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.33161
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.33161
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.33161
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.33161
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.33161
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40854
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40854
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40854
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.40854
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40854
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.40854
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30364
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30364
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30364
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.30364
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30364
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.30364
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40375
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40375
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40375
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.40375
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40375
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.40375
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.35854
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.35854
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.35854
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.35854
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.35854
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.35854
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.33161
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.40854
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.30364
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.40375
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.35854
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.33161
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46220E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.33161
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6164.70255
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80038
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.33161
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.33161
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.33161
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.33161
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6164.70255
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6164.70255
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2804.01330
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.33161
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.33161
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6164.70255
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2804.01330
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40854
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40854
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7134.16035
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80052
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40854
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40854
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40854
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40854
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7134.16035
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7134.16035
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3672.71144
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.40854
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40854
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7134.16035
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 3672.71144
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30364
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30364
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5026.31153
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30364
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30364
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30364
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30364
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5026.31153
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5026.31153
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2270.52769
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.30364
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30364
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5026.31153
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2270.52769
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40375
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40375
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7059.89568
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80005
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40375
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40375
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40375
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40375
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7059.89568
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7059.89568
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3604.53634
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.40375
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40375
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7059.89568
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 3604.53634
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.35854
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.35854
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5935.03242
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.35854
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.35854
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.35854
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.35854
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5935.03242
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5935.03242
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2260.93375
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.35854
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.35854
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5935.03242
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2260.93375
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5904.4 3.37 11.48 12.02 11.37 11.35
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6813.8 3.32 11.35 11.87 11.23 11.14
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4788.3 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 6743.2 3.33 11.35 11.87 11.23 11.15
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 5654.0 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 6428.6 3566.4 7.41 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 7458.7 4146.4 7.36 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5267.2 2933.5 7.32 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 7380.7 4102.8 7.36 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 6219.5 3463.9 7.34 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.6634152868E-002 8.1017571838E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 7.8606949630E-002 5.0722382307E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 3.9945191967E-002 3.3926287081E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 3.0356362359E-002 1.5474127277E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 6.2711523018E-002 4.4933080695E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.4968130166 0.4845735810 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1124.91 28.07 0.00 48.59 172.05 1373.63



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.4547_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.4547_SHGC_SOUTH_0.25   3.91 0.00 0.00 3.91 3.91 2.584 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.4547_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.4547_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.4547_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.4547_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.4547_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.4547_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.4547_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.4547_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.4547_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.584 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.584 0.251 0.251                      
North Total or Average             16.72 2.584 0.251 0.251                      
Non-North Total or Average             42.93 2.584 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.15 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.05 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.0938 149.66 911.98 LightsWired LTG_SCH_OFFICE 50.53 168.00 49.65 0.0000 Y 8.50
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 42.06 0.0000 Y 5.46
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 43.46 0.0000 Y 3.35
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 45.51 0.0000 Y 5.91
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 43.80 0.0000 Y 3.37
Interior Lighting Total       6.0938 511.16 3114.87               26.58


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   41.79 41.79 0.52
EXTERIOR_LIGHTS_B 202.25 AstronomicalClock -   83.79 62.79 2.38
EXTERIOR_LIGHTS_C 780.12 AstronomicalClock -   83.79 47.06 6.89
Exterior Lighting Total 1049.10           9.80



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6164.70 4934.10 1230.60 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7134.16 5711.01 1423.15 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5026.31 4024.34 1001.97 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7059.90 5648.27 1411.63 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5935.03 4751.91 1183.12 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5904.4 3.37 11.48 12.02 11.37 11.35
PSZ-AC:2 HP COOLING COIL   6813.8 3.32 11.35 11.87 11.23 11.14
PSZ-AC:3 HP COOLING COIL   4788.3 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   6743.2 3.33 11.35 11.87 11.23 11.15
PSZ-AC:5 HP COOLING COIL   5654.0 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 6428.6 3566.4 7.41 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 7458.7 4146.4 7.36 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5267.2 2933.5 7.32 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 7380.7 4102.8 7.36 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 6219.5 3463.9 7.34 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6164.70 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2804.01 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   7134.16 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   3672.71 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   5026.31 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2270.53 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   7059.90 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   3604.54 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   5935.03 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2260.93 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.33 371.44 1120.11 1.00 1.83 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.41 457.61 1120.11 1.00 1.70 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.30 340.11 1120.11 1.00 1.89 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.40 452.24 1120.11 1.00 1.71 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.36 401.60 1120.11 1.00 1.78 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3419.24 4103.08 27.42 0.276 0.332 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00902 39.65 0.00563 0.065 0.00
PERIMETER_ZN_1 4212.44 5054.93 44.56 0.340 0.409 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 23.89 23.89 0.00880 39.82 0.00563 0.049 0.00
PERIMETER_ZN_2 3130.88 3757.06 55.83 0.253 0.304 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 23.89 23.89 0.00873 37.08 0.00563 0.029 0.00
PERIMETER_ZN_3 4163.00 4995.60 44.03 0.336 0.404 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 23.89 23.89 0.00880 39.82 0.00563 0.049 0.00
PERIMETER_ZN_4 3696.90 4436.29 65.92 0.299 0.359 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 23.89 23.89 0.00870 37.83 0.00563 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 819.84 983.81 6.57 0.039 0.065 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 0.50 0.00432 0.065 0.00
PERIMETER_ZN_1 2167.93 2601.52 22.93 0.103 0.124 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00795 0.50 0.00432 0.049 0.00
PERIMETER_ZN_2 1363.70 1636.44 24.32 0.065 0.078 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00795 0.50 0.00432 0.029 0.00
PERIMETER_ZN_3 2110.28 2532.34 22.32 0.100 0.120 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00795 0.50 0.00432 0.049 0.00
PERIMETER_ZN_4 1355.59 1626.70 24.17 0.064 0.077 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00795 0.50 0.00432 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.33 0.33 0.06 0.06 0.3316 0.3316 0.3316 1.0000 1.0000
PSZ-AC:2 0.41 0.41 0.12 0.12 0.4085 0.4085 0.4085 1.0000 1.0000
PSZ-AC:3 0.30 0.30 0.08 0.08 0.3036 0.3036 0.3036 1.0000 1.0000
PSZ-AC:4 0.40 0.40 0.12 0.12 0.4037 0.4037 0.4037 1.0000 1.0000
PSZ-AC:5 0.36 0.36 0.08 0.08 0.3585 0.3585 0.3585 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6164.703 4934.101 0.331613 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5420.12 5420.12 0.331613 27.96 16.63 0.00836218 12.80 11.10 0.00836218 39.65 0.00562931 18.22 19.4872 23.89 0.00902927 44.3836 3390.18 0.00 6163.65 4692.18
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6164.703 6164.703 0.331613 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6164.70 6164.70 0.331613 17.09 11.76 0.00728201 40.00 20.06 0.00800000 0.50 0.00431558 0.50 19.4872 21.11 0.00800000 46.6350 819.12 0.00 6172.80 6172.80
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2804.013 2804.013 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 2804.01 2804.01 0.331613 17.09 11.76 0.00728201 40.00 20.06 0.00800000 0.50 0.00431558 0.50 19.4872 21.11 0.00800000 46.6350 819.12 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7134.160 5711.012 0.408540 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 6190.19 6190.19 0.408540 26.80 16.28 0.00841555 12.80 11.15 0.00841555 39.82 0.00562958 18.28 11.9909 23.89 0.00879577 43.2510 4204.35 0.00 7132.94 5430.12
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7134.160 7134.160 0.408540 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7134.16 7134.16 0.408540 18.64 12.58 0.00751314 40.00 20.06 0.00800000 0.50 0.00431558 0.50 11.9909 21.11 0.00794880 46.3405 2167.93 0.00 7143.54 7143.54
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 3672.711 3672.711 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3672.71 3672.71 0.408540 18.64 12.58 0.00751314 40.00 20.06 0.00800000 0.50 0.00431558 0.50 11.9909 21.11 0.00794880 46.3405 2167.93 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5026.312 4024.343 0.303639 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 4490.47 4490.47 0.303639 26.16 16.08 0.00843584 12.80 11.17 0.00843584 37.08 0.00562532 17.41 9.5706 23.89 0.00873460 42.9541 3121.54 0.00 5025.45 3826.16
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5026.312 5026.312 0.303639 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5026.31 5026.31 0.303639 19.14 12.85 0.00759835 40.00 20.06 0.00800000 0.50 0.00431558 0.50 9.5706 21.11 0.00794578 46.3232 1363.70 0.00 5032.92 5032.92
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2270.528 2270.528 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2270.53 2270.53 0.303639 19.14 12.85 0.00759835 40.00 20.06 0.00800000 0.50 0.00431558 0.50 9.5706 21.11 0.00794578 46.3232 1363.70 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7059.896 5648.266 0.403745 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 6127.00 6127.00 0.403745 26.83 16.29 0.00841410 12.80 11.15 0.00841410 39.82 0.00562958 18.28 12.1333 23.89 0.00879919 43.2676 4155.97 0.00 7058.68 5370.73
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7059.896 7059.896 0.403745 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7059.90 7059.90 0.403745 18.61 12.56 0.00750676 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.1333 21.11 0.00794742 46.3326 2110.28 0.00 7069.17 7069.17
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 3604.536 3604.536 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3604.54 3604.54 0.403745 18.61 12.56 0.00750676 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.1333 21.11 0.00794742 46.3326 2110.28 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5935.032 4751.915 0.358535 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 5248.40 5248.40 0.358535 26.02 16.05 0.00844887 12.80 11.18 0.00844887 37.83 0.00562649 17.65 8.1052 23.89 0.00869749 42.7740 3695.29 0.00 5934.01 4517.90
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5935.032 5935.032 0.358535 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5935.03 5935.03 0.358535 19.44 13.01 0.00765125 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.1052 21.11 0.00794546 46.3213 1355.59 0.00 5942.83 5942.83
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2260.934 2260.934 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2260.93 2260.93 0.358535 19.44 13.01 0.00765125 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.1052 21.11 0.00794546 46.3213 1355.59 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6164.703 4934.101 0.331613 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3849 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.331613 0.36251738   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5420.12 5420.12 0.8792 0.36251738 0.331613 27.96 16.63 0.00836218 49447.7 12.80 11.10 0.00836218 33974.2 -999.0 -999.00 -999.00 -999.00 371.442 5048.68 39.65 0.00562931 18.22 0.06462205 19.4872 23.89 0.00902364 23.89 0.00902927 44.3836 3390.18 0.00 6163.65 4692.18 0.34820069 26.67 19.44 0.01118466 55322.4 13.49 13.38 0.00952778 37621.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6164.703 6164.703 0.331613 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.331613 0.36251738   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6164.70 6164.70 1.0000 0.36251738 0.331613 17.09 11.76 0.00728201 35619.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6164.70 0.50 0.00431558 0.50 0.06462205 19.4872 21.11 0.00800000 21.11 0.00800000 46.6350 819.12 0.00 6172.80 6172.80 0.35611159 21.11 15.56 0.00875166 43444.1 38.09 21.16 0.00875166 60778.0
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2804.013 2804.013 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.331613 0.36251738   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 2804.01 2804.01 1.0000 0.36251738 0.331613 17.09 11.76 0.00728201 35619.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2804.01 0.50 0.00431558 0.50 0.06462205 19.4872 21.11 0.00800000 21.11 0.00800000 46.6350 819.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7134.160 5711.012 0.408540 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.4841 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.408540 0.44661304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 Sensible 6190.19 6190.19 0.8677 0.44661304 0.408540 26.80 16.28 0.00841555 48400.1 12.80 11.15 0.00841555 34109.0 -999.0 -999.00 -999.00 -999.00 457.608 5732.58 39.82 0.00562958 18.28 0.04898769 11.9909 23.89 0.00879513 23.89 0.00879577 43.2510 4204.35 0.00 7132.94 5430.12 0.42897520 26.67 19.44 0.01118466 55322.4 14.29 13.79 0.00962831 38694.5
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7134.160 7134.160 0.408540 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.408540 0.44661304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7134.16 7134.16 1.0000 0.44661304 0.408540 18.64 12.58 0.00751314 37779.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7134.16 0.50 0.00431558 0.50 0.04898769 11.9909 21.11 0.00794880 21.11 0.00794880 46.3405 2167.93 0.00 7143.54 7143.54 0.43872125 21.11 15.56 0.00875166 43444.1 37.06 20.85 0.00875166 59726.7
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3672.711 3672.711 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.408540 0.44661304   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3672.71 3672.71 1.0000 0.44661304 0.408540 18.64 12.58 0.00751314 37779.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3672.71 0.50 0.00431558 0.50 0.04898769 11.9909 21.11 0.00794880 21.11 0.00794880 46.3405 2167.93 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5026.312 4024.343 0.303639 -999.0 -999.000 -999.0000 1.02126 1.00000 1020.5218 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.303639 0.33193692   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 4490.47 4490.47 0.8934 0.33193692 0.303639 26.16 16.08 0.00843584 47790.0 12.80 11.17 0.00843584 34160.2 -999.0 -999.00 -999.00 -999.00 340.109 4150.37 37.08 0.00562532 17.41 0.02906013 9.5706 23.89 0.00873329 23.89 0.00873460 42.9541 3121.54 0.00 5025.45 3826.16 0.31882792 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5026.312 5026.312 0.303639 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.303639 0.33193692   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5026.31 5026.31 1.0000 0.33193692 0.303639 19.14 12.85 0.00759835 38503.4 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5026.31 0.50 0.00431558 0.50 0.02906013 9.5706 21.11 0.00794578 21.11 0.00794578 46.3232 1363.70 0.00 5032.92 5032.92 0.32607150 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2270.528 2270.528 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.303639 0.33193692   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2270.53 2270.53 1.0000 0.33193692 0.303639 19.14 12.85 0.00759835 38503.4 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2270.53 0.50 0.00431558 0.50 0.02906013 9.5706 21.11 0.00794578 21.11 0.00794578 46.3232 1363.70 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7059.896 5648.266 0.403745 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.4814 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.403745 0.44137181   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 Sensible 6127.00 6127.00 0.8679 0.44137181 0.403745 26.83 16.29 0.00841410 48419.6 12.80 11.15 0.00841410 34105.3 -999.0 -999.00 -999.00 -999.00 452.238 5674.76 39.82 0.00562958 18.28 0.04898769 12.1333 23.89 0.00879861 23.89 0.00879919 43.2676 4155.97 0.00 7058.68 5370.73 0.42394096 26.67 19.44 0.01118466 55322.4 14.28 13.78 0.00962357 38672.2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7059.896 7059.896 0.403745 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.403745 0.44137181   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7059.90 7059.90 1.0000 0.44137181 0.403745 18.61 12.56 0.00750676 37732.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7059.90 0.50 0.00431558 0.50 0.04898769 12.1333 21.11 0.00794742 21.11 0.00794742 46.3326 2110.28 0.00 7069.17 7069.17 0.43357263 21.11 15.56 0.00875166 43444.1 37.08 20.86 0.00875166 59748.6
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3604.536 3604.536 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.403745 0.44137181   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3604.54 3604.54 1.0000 0.44137181 0.403745 18.61 12.56 0.00750676 37732.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3604.54 0.50 0.00431558 0.50 0.04898769 12.1333 21.11 0.00794742 21.11 0.00794742 46.3326 2110.28 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5935.032 4751.915 0.358535 -999.0 -999.000 -999.0000 1.02053 1.00000 1020.5460 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.358535 0.39194873   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 5248.40 5248.40 0.8843 0.39194873 0.358535 26.02 16.05 0.00844887 47688.3 12.80 11.18 0.00844887 34193.1 -999.0 -999.00 -999.00 -999.00 401.598 4846.80 37.83 0.00562649 17.65 0.02906013 8.1052 23.89 0.00869781 23.89 0.00869749 42.7740 3695.29 0.00 5934.01 4517.90 0.37646971 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5935.032 5935.032 0.358535 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.358535 0.39194873   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5935.03 5935.03 1.0000 0.39194873 0.358535 19.44 13.01 0.00765125 38945.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5935.03 0.50 0.00431558 0.50 0.02906013 8.1052 21.11 0.00794546 21.11 0.00794546 46.3213 1355.59 0.00 5942.83 5942.83 0.38502287 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2260.934 2260.934 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.358535 0.39194873   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2260.93 2260.93 1.0000 0.39194873 0.358535 19.44 13.01 0.00765125 38945.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2260.93 0.50 0.00431558 0.50 0.02906013 8.1052 21.11 0.00794546 21.11 0.00794546 46.3213 1355.59 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2325.83 1415.83 397.50
PERIMETER_ZN_1 2167.00 1600.67 541.17
PERIMETER_ZN_2 1801.00 1767.67 559.50
PERIMETER_ZN_3 1949.17 2294.67 581.67
PERIMETER_ZN_4 2193.83 2099.33 732.17
ATTIC 0.00 0.00 0.00
Facility 2684.83 2582.50 844.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 238.83 0.00 238.83
PERIMETER_ZN_1 0.00 127.00 0.00 114.83
PERIMETER_ZN_2 0.00 64.83 0.00 23.50
PERIMETER_ZN_3 0.00 4.17 0.00 3.50
PERIMETER_ZN_4 0.00 44.17 0.00 5.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 376.17 0.00 298.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.398 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.397 0.364 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.371 0.013 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.397 0.011 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.398 0.012 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.046
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.021
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.021
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.156


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762207.08 0.00 762207.08 0.00 762207.08 1606483.19 5484.00 2016.00 1260.00 2.58
PERIMETER_ZN_1 581482.50 0.00 581482.50 557163.44 1138645.95 1217818.28 5482.05 2016.08 1261.87 131.56
PERIMETER_ZN_2 346714.45 0.00 346714.45 29340.95 376055.40 702184.69 5479.52 1512.42 1768.06 986.49
PERIMETER_ZN_3 579660.90 0.00 579660.90 44011.42 623672.32 1217818.28 5483.22 2016.10 1260.68 76.51
PERIMETER_ZN_4 347526.25 0.00 347526.25 29340.95 376867.20 722425.48 5478.10 2016.18 1265.71 224.65
Total Facility 2617591.18 0.00 2617591.18 659856.77 3277447.95 5466729.92 5484.00 2016.78 1775.20 1156.47


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0565 1008.00 2016.00 1260.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0343 0.0718 0.0428 1008.00 2016.00 1260.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0007 0.0215 0.0249 1008.00 1512.00 1008.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0010 0.0385 0.0428 1008.00 2016.00 1260.00
PERIMETER_ZN_4 0.0223 0.0000 0.0223 0.0007 0.0229 0.0254 1007.30 2016.03 1260.67
Total Facility 0.1674 0.0000 0.1674 0.0367 0.2041 0.1925 1008.00 2016.03 1764.67


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 910893.55 0.00 910893.55 1606483.19 5484.00 0.00 3276.00 2.42
PSZ-AC:2 694914.39 0.00 694914.39 1217818.28 5480.55 0.07 3279.39 127.69
PSZ-AC:3 414349.28 0.00 414349.28 702184.69 5477.92 0.31 3281.77 978.23
PSZ-AC:4 692737.43 0.00 692737.43 1217818.28 5482.75 0.04 3277.20 74.46
PSZ-AC:5 415319.45 0.00 415319.45 722425.48 5475.78 0.39 3283.83 211.44


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0591 0.0000 0.0591 0.0565 1008.00 0.00 3276.00
PSZ-AC:2 0.0448 0.0000 0.0448 0.0428 1008.00 0.00 3276.00
PSZ-AC:3 0.0248 0.0000 0.0248 0.0249 1008.00 0.00 2520.00
PSZ-AC:4 0.0448 0.0000 0.0448 0.0428 1008.00 0.00 3276.00
PSZ-AC:5 0.0266 0.0000 0.0266 0.0254 1006.71 0.04 3277.24


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3278.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3403.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3498.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3350.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3538.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0772 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0347 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0343 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 524
Defaulted Fields 360
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
Electricity:Building 74.88 896.95 03-SEP-11:30 5350.97 28-NOV-16:30
Electricity:Zone:CORE_ZN 22.64 284.81 01-JAN-00:10 1566.66 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.88 896.95 03-SEP-11:30 5350.97 28-NOV-16:30
InteriorLights:Electricity 26.58 329.30 03-SEP-11:30 2025.66 28-NOV-16:30
InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.58 329.30 03-SEP-11:30 2025.66 28-NOV-16:30
LightsWired:InteriorLights:Electricity 26.58 329.30 03-SEP-11:30 2025.66 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.58 329.30 03-SEP-11:30 2025.66 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_1 16.18 191.62 01-JAN-08:40 1187.63 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.46 65.63 01-JAN-08:40 449.59 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.46 65.63 01-JAN-08:40 449.59 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_2 9.70 113.67 01-JAN-08:20 704.52 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.35 38.93 01-JAN-08:20 266.70 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.35 38.93 01-JAN-08:20 266.70 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_3 16.63 191.62 03-JUN-18:10 1187.63 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.91 65.63 03-JUN-18:10 449.59 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.91 65.63 03-JUN-18:10 449.59 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_4 9.73 113.67 01-JAN-14:30 704.52 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.37 38.93 01-JAN-14:30 266.70 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.37 38.93 01-JAN-14:30 266.70 28-NOV-16:30
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
ElectricityPurchased:Plant 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
Cogeneration:ElectricityPurchased 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
General:Cogeneration:ElectricityPurchased 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
ElectricityNet:Plant 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
Cogeneration:ElectricityNet 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
General:Cogeneration:ElectricityNet 165.73 1468.95 03-SEP-11:30 17833.68 28-JUN-16:00
ExteriorLights:Electricity 9.80 0.00 01-JAN-07:30 1049.10 01-JAN-06:10
General:ExteriorLights:Electricity 9.80 0.00 01-JAN-07:30 1049.10 01-JAN-06:10
Electricity:HVAC 58.09 0.00 01-JAN-00:20 10047.08 28-JUN-16:00
Fans:Electricity 24.04 0.00 01-JAN-00:10 2023.00 17-MAR-11:20
General:Fans:Electricity 24.04 0.00 01-JAN-00:10 2023.00 17-MAR-11:20
Cooling:Electricity 33.81 0.00 01-JAN-00:10 8024.09 28-JUN-16:00
General:Cooling:Electricity 33.81 0.00 01-JAN-00:10 8024.09 28-JUN-16:00
Heating:Electricity 0.24 0.00 01-JAN-00:20 3723.96 02-JAN-07:10
General:Heating:Electricity 0.24 0.00 01-JAN-00:20 3723.96 02-JAN-07:10
Electricity:Plant 22.96 572.00 23-FEB-15:30 2784.46 24-JAN-13:00
WaterSystems:Electricity 22.96 572.00 23-FEB-15:30 2784.46 24-JAN-13:00
Water Heater:WaterSystems:Electricity 22.96 572.00 23-FEB-15:30 2784.46 24-JAN-13:00
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 1522.05 27-MAR-06:10
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 1522.05 27-MAR-06:10
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 1522.05 27-MAR-06:10
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 1522.05 27-MAR-06:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 252.24 0.00 01-JAN-00:10 55579.45 14-AUG-07:10
EnergyTransfer:Building 113.56 0.00 01-JAN-00:10 25997.24 18-SEP-07:20
EnergyTransfer:Zone:CORE_ZN 27.45 0.00 01-JAN-00:10 5848.20 10-OCT-07:10
Heating:EnergyTransfer 2.54 0.00 01-JAN-00:10 10111.88 02-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 1391.82 28-JUN-17:10
General:Heating:EnergyTransfer 2.54 0.00 01-JAN-00:10 10111.88 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 1391.82 28-JUN-17:10
Cooling:EnergyTransfer 111.03 0.00 01-JAN-00:10 25997.24 18-SEP-07:20
Cooling:EnergyTransfer:Zone:CORE_ZN 27.01 0.00 01-JAN-00:10 5848.20 10-OCT-07:10
General:Cooling:EnergyTransfer 111.03 0.00 01-JAN-00:10 25997.24 18-SEP-07:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 27.01 0.00 01-JAN-00:10 5848.20 10-OCT-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 30.40 0.00 01-JAN-00:10 6125.33 18-SEP-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.58 0.00 01-JAN-00:10 3209.27 27-MAR-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.58 0.00 01-JAN-00:10 3209.27 27-MAR-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 29.82 0.00 01-JAN-00:10 6125.33 18-SEP-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 29.82 0.00 01-JAN-00:10 6125.33 18-SEP-07:20
EnergyTransfer:Zone:PERIMETER_ZN_2 18.04 0.00 01-JAN-00:10 4344.89 18-SEP-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.39 0.00 01-JAN-00:10 1815.98 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.39 0.00 01-JAN-00:10 1815.98 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 17.65 0.00 01-JAN-00:10 4344.89 18-SEP-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 17.65 0.00 01-JAN-00:10 4344.89 18-SEP-07:20
EnergyTransfer:Zone:PERIMETER_ZN_3 21.23 0.00 01-JAN-00:10 6040.69 18-SEP-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.71 0.00 01-JAN-00:10 3715.68 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.71 0.00 01-JAN-00:10 3715.68 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 20.53 0.00 01-JAN-00:10 6040.69 18-SEP-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 20.53 0.00 01-JAN-00:10 6040.69 18-SEP-07:20
EnergyTransfer:Zone:PERIMETER_ZN_4 16.43 0.00 01-JAN-00:10 4413.26 14-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.41 0.00 01-JAN-00:10 1600.69 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.41 0.00 01-JAN-00:10 1600.69 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 16.02 0.00 01-JAN-00:10 4413.26 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 16.02 0.00 01-JAN-00:10 4413.26 14-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
EnergyTransfer:HVAC 138.68 0.00 01-JAN-00:10 32205.46 05-SEP-07:10
CoolingCoils:EnergyTransfer 138.34 0.00 01-JAN-00:10 32205.46 05-SEP-07:10
HeatingCoils:EnergyTransfer 0.34 0.00 01-JAN-00:10 11418.43 02-JAN-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 77.09 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.439 -27.014 0.000 0.000 4.887 8.499 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.952
PERIMETER_ZN_1 0.000 0.000 0.584 -29.818 0.000 0.000 3.736 5.459 10.719 20.049 0.000 1.925 0.000 0.000 -7.036 0.000 -2.514 -3.105
PERIMETER_ZN_2 0.000 0.000 0.389 -17.649 0.000 0.000 1.621 3.345 6.359 10.274 0.000 0.044 0.000 0.000 -3.526 0.000 -0.175 -0.681
PERIMETER_ZN_3 0.000 0.000 0.708 -20.525 0.000 0.000 3.793 5.906 10.719 5.907 0.000 0.071 0.000 0.000 -5.383 0.000 -0.245 -0.951
PERIMETER_ZN_4 0.000 0.000 0.415 -16.019 0.000 0.000 2.226 3.372 6.359 9.873 0.000 0.041 0.000 0.000 -3.898 0.000 -0.180 -2.188
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 13.267 27.095 0.000 0.000 0.000 -40.362 -0.001
Total Facility 0.000 0.000 2.535 -111.025 0.000 0.000 16.263 26.581 48.296 46.104 0.000 15.348 27.095 0.000 -19.844 0.000 -43.476 -7.877


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 12-OCT-07:03 0.00 0.00 0.00 -6397.36 0.00 0.00 510.41 593.08 973.59 0.00 0.00 0.00 4320.29 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 10-OCT-06:01 0.00 0.00 0.00 -6870.10 0.00 0.00 64.29 209.81 369.02 0.00 0.00 0.00 8322.24 0.00 -595.34 0.00 -1499.92 0.00
PERIMETER_ZN_2 10-OCT-06:01 0.00 0.00 0.00 -4730.75 0.00 0.00 38.49 124.46 218.91 0.00 0.00 0.00 4662.80 0.00 -310.38 0.00 -3.52 0.00
PERIMETER_ZN_3 10-OCT-06:01 0.00 0.00 0.00 -6747.50 0.00 0.00 70.89 209.81 369.02 0.00 0.00 0.00 6534.57 0.00 -431.89 0.00 -4.91 0.00
PERIMETER_ZN_4 16-JUL-18:42 0.00 0.00 0.00 -5627.39 0.00 0.00 0.00 42.73 74.74 1090.23 0.00 0.00 4421.06 0.00 -0.00 0.00 -1.38 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-OCT-06:01 0.00 0.00 0.00 -30226.25 0.00 0.00 296.62 945.30 1662.65 0.00 0.00 874.29 29606.13 0.00 -1646.89 0.00 -1511.85 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-08:62 0.00 0.00 5055.94 0.00 0.00 0.00 697.55 593.08 973.59 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7320.15
PERIMETER_ZN_1 27-MAR-06:02 0.00 0.00 7454.47 0.00 0.00 0.00 115.38 209.81 369.02 0.00 0.00 0.00 0.00 0.00 -837.28 0.00 -2740.63 -4570.77
PERIMETER_ZN_2 02-JAN-07:01 0.00 0.00 4380.29 0.00 0.00 0.00 71.90 124.46 218.91 0.00 0.00 0.00 0.00 0.00 -314.30 0.00 -3.60 -4477.66
PERIMETER_ZN_3 27-MAR-06:02 0.00 0.00 8341.42 0.00 0.00 0.00 119.34 209.81 369.02 0.00 0.00 0.00 0.00 0.00 -625.28 0.00 -12.31 -8401.99
PERIMETER_ZN_4 02-JAN-07:01 0.00 0.00 5170.96 0.00 0.00 0.00 71.53 124.46 218.91 0.00 0.00 0.00 0.00 0.00 -316.49 0.00 -3.69 -5265.68
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-07:01 0.00 0.00 26242.62 0.00 0.00 0.00 528.90 945.30 1662.65 0.00 0.00 1489.48 0.00 0.00 -1755.79 0.00 -2129.44 -26983.73



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3316 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3316 0.1949 1.0000 Not calculated 0.0646 0.1949    
PSZ-AC:2 0.4085 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4085 0.1199 1.0000 Not calculated 0.0490 0.1199    
PSZ-AC:3 0.3036 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3036 0.0957 1.0000 Not calculated 0.0291 0.0957    
PSZ-AC:4 0.4037 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4037 0.1213 1.0000 Not calculated 0.0490 0.1213    
PSZ-AC:5 0.3585 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3585 0.0811 1.0000 Not calculated 0.0291 0.0811    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3316 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3316 1.0000 1.0000 Not calculated 0.0646 0.1949    
PSZ-AC:2 0.4085 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4085 1.0000 1.0000 Not calculated 0.0490 0.1199    
PSZ-AC:3 0.3036 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3036 1.0000 1.0000 Not calculated 0.0291 0.0957    
PSZ-AC:4 0.4037 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4037 1.0000 1.0000 Not calculated 0.0490 0.1213    
PSZ-AC:5 0.3585 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3585 1.0000 1.0000 Not calculated 0.0291 0.0811    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.002360 8.0545 0.000305 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.002360 8.05 0.000305 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3316 0.3316 0.3316 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4085 0.4085 0.4085 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3036 0.3036 0.3036 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4037 0.4037 0.4037 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3585 0.3585 0.3585 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3316 0.3316 0.3316 0.3316 0.0646 1.0000
PSZ-AC:2 0.4085 0.4085 0.4085 0.4085 0.0490 1.0000
PSZ-AC:3 0.3036 0.3036 0.3036 0.3036 0.0291 1.0000
PSZ-AC:4 0.4037 0.4037 0.4037 0.4037 0.0490 1.0000
PSZ-AC:5 0.3585 0.3585 0.3585 0.3585 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3316 0.3316 0.3316 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4085 0.4085 0.4085 No 0.0490 0.3965 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3036 0.3036 0.3036 No 0.0291 0.3739 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4037 0.4037 0.4037 No 0.0490 0.4074 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3585 0.3585 0.3585 No 0.0291 0.3762 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3316 0.3316 0.3316 0.3316 0.0646 1.0000
PSZ-AC:2 0.4085 0.4085 0.4085 0.4085 0.0490 1.0000
PSZ-AC:3 0.3036 0.3036 0.3036 0.3036 0.0291 1.0000
PSZ-AC:4 0.4037 0.4037 0.4037 0.4037 0.0490 1.0000
PSZ-AC:5 0.3585 0.3585 0.3585 0.3585 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 298.67
Number of hours not met 298.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.24 3723.96 0.00 1522.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 33.81 8024.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.58 2025.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.80 1049.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 24.04 2023.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 22.96 2784.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 165.73
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 48.30 165.73


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 52.00
Space Heating 0.47
Space Cooling 66.14
Fans (All) 47.04
Service Water Heating 44.91
Receptacle Equipment 94.48
Miscellaneous (All) 324.22
Subtotal 324.22


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 16.04
Space Heating 0.14
Space Cooling 20.40
Fans (All) 14.51
Service Water Heating 13.85
Receptacle Equipment 29.14
Miscellaneous 5.91


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2635. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 6845.67 1914.33 0.00 0.00 0.00
PERIMETER_ZN_1 6905.33 1854.67 0.00 0.00 0.00
PERIMETER_ZN_2 6797.67 1962.33 0.00 0.00 0.00
PERIMETER_ZN_3 7060.50 1699.50 0.00 0.00 0.00
PERIMETER_ZN_4 6587.00 2173.00 0.00 0.00 0.00
ATTIC 5332.33 943.17 875.50 1305.83 303.17
Min 5332.33 943.17 0.00 0.00 0.00
Max 7060.50 2173.00 875.50 1305.83 303.17
Average 6588.08 1757.83 145.92 217.64 50.53
Sum 39528.50 10547.00 875.50 1305.83 303.17


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7068.00 1692.00 0.00 0.00 0.00
PERIMETER_ZN_1 7536.50 1223.50 0.00 0.00 0.00
PERIMETER_ZN_2 7500.67 1259.33 0.00 0.00 0.00
PERIMETER_ZN_3 7553.33 1206.67 0.00 0.00 0.00
PERIMETER_ZN_4 7449.17 1310.83 0.00 0.00 0.00
ATTIC 5481.50 1500.83 431.67 364.33 981.67
Min 5481.50 1206.67 0.00 0.00 0.00
Max 7553.33 1692.00 431.67 364.33 981.67
Average 7098.19 1365.53 71.94 60.72 163.61
Sum 42589.17 8193.17 431.67 364.33 981.67


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17769.67 122.33 0.00 0.00 0.00
PERIMETER_ZN_1 13325.50 30.50 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13340.33 15.67 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17769.67 122.33 0.00 0.00 0.00
Average 9337.92 28.08 0.00 0.00 0.00
Sum 56027.50 168.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:10

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.113656E+10 2868.46 27-JAN-08:63 11.83 5.09 0.294802E+09 413.84 27-JAN-08:09 11.83 5.09
February 0.777413E+09 2148.67 01-FEB-16:05 15.83 6.96 0.264981E+09 402.35 23-FEB-16:00 17.00 10.81
March 0.120149E+10 5761.13 21-MAR-07:03 16.15 9.27 0.324790E+09 439.85 21-MAR-07:10 16.15 9.27
April 0.219834E+10 6167.14 07-APR-07:03 12.40 6.89 0.288935E+09 469.21 26-APR-07:10 21.50 10.77
May 0.287252E+10 6124.65 30-MAY-06:02 18.67 9.89 0.318992E+09 469.21 15-MAY-07:10 18.67 9.89
June 0.350848E+10 6161.13 26-JUN-05:02 22.17 10.13 0.327665E+09 469.22 30-JUN-07:10 29.33 19.12
July 0.328480E+10 6313.19 03-JUL-05:02 20.33 7.70 0.305199E+09 469.50 24-JUL-07:19 26.67 19.22
August 0.362263E+10 6099.77 23-AUG-06:01 22.00 12.48 0.344892E+09 469.23 16-AUG-07:10 22.00 12.48
September 0.311955E+10 6043.73 28-SEP-06:02 21.10 12.33 0.298486E+09 469.25 25-SEP-07:10 21.10 12.33
October 0.255441E+10 6397.24 12-OCT-07:03 8.67 3.88 0.304777E+09 469.23 02-OCT-07:10 8.67 3.88
November 0.169627E+10 6135.35 06-NOV-08:62 12.67 4.88 0.300239E+09 469.22 01-NOV-07:10 12.67 4.88
December 0.104126E+10 2315.28 26-DEC-16:50 23.00 10.75 0.280398E+09 403.04 26-DEC-08:09 23.00 10.75
                     
Annual Sum or Average 0.270137E+11         0.365415E+10        
Minimum of Months 0.777413E+09 2148.67   8.67 3.88 0.264981E+09 402.35   8.67 3.88
Maximum of Months 0.362263E+10 6397.24   23.00 12.48 0.344892E+09 469.50   29.33 19.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192872E+10 5275.94 30-JAN-14:40 24.67 9.55 0.223367E+09 305.00 09-JAN-11:00 24.67 9.55
February 0.672314E+09 3460.75 01-FEB-15:30 15.50 6.96 0.194857E+09 305.90 10-FEB-10:20 17.00 9.46
March 0.788104E+09 3064.21 20-MAR-14:30 27.70 14.31 0.237416E+09 305.00 01-MAR-16:10 27.70 14.31
April 0.186566E+10 6247.64 26-APR-07:02 21.50 10.77 0.217477E+09 355.69 25-APR-07:10 21.50 10.77
May 0.230245E+10 6401.23 08-MAY-06:01 20.50 9.41 0.241101E+09 355.69 10-MAY-07:10 24.33 12.29
June 0.349759E+10 6652.71 19-JUN-05:02 22.17 10.17 0.244969E+09 355.70 30-JUN-07:10 29.33 19.12
July 0.361161E+10 6617.30 31-JUL-05:02 25.83 15.57 0.223633E+09 355.72 17-JUL-07:10 25.83 15.57
August 0.410671E+10 6736.14 14-AUG-05:02 26.00 16.58 0.257659E+09 356.02 28-AUG-12:09 36.33 20.98
September 0.383269E+10 6785.66 25-SEP-05:02 23.72 17.67 0.227368E+09 356.34 11-SEP-12:09 23.72 17.67
October 0.326732E+10 6870.07 10-OCT-06:01 16.50 11.11 0.234071E+09 367.57 02-OCT-12:09 16.50 11.11
November 0.243933E+10 6313.74 01-NOV-16:05 27.67 15.49 0.226742E+09 348.32 01-NOV-07:10 27.67 15.49
December 0.150531E+10 5494.58 26-DEC-13:55 23.00 10.16 0.209686E+09 305.00 13-DEC-11:30 23.00 10.16
                     
Annual Sum or Average 0.298178E+11         0.273834E+10        
Minimum of Months 0.672314E+09 3064.21   15.50 6.96 0.194857E+09 305.00   16.50 9.46
Maximum of Months 0.410671E+10 6870.07   27.70 17.67 0.257659E+09 367.57   36.33 20.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.403872E+09 1153.53 31-JAN-16:07 29.00 10.73 95376679.52 180.93 09-JAN-13:20 29.00 10.73
February 0.158959E+09 837.06 01-FEB-11:02 13.17 6.52 84099803.29 183.10 17-FEB-13:20 20.00 13.40
March 0.374947E+09 1369.96 23-MAR-10:45 23.43 10.94 0.103807E+09 181.63 08-MAR-11:50 23.43 10.94
April 0.139957E+10 4519.71 17-APR-07:02 17.67 10.67 95817318.90 211.00 26-APR-07:10 21.50 10.77
May 0.188342E+10 4512.78 30-MAY-06:02 18.67 9.89 0.106221E+09 211.00 25-MAY-07:10 18.67 9.89
June 0.274374E+10 4620.15 19-JUN-05:02 22.17 10.17 0.107881E+09 211.00 30-JUN-07:10 29.33 19.12
July 0.271138E+10 4698.54 30-JUL-09:02 29.50 18.97 98303467.10 211.02 17-JUL-07:10 29.50 18.97
August 0.290995E+10 4682.14 13-AUG-09:02 32.17 20.93 0.112922E+09 211.02 01-AUG-07:10 32.17 20.93
September 0.233680E+10 4685.26 10-SEP-09:42 31.13 19.29 97709826.61 211.02 25-SEP-07:10 23.48 17.89
October 0.161850E+10 4730.72 10-OCT-06:01 16.50 11.11 0.100486E+09 211.01 02-OCT-07:10 16.50 11.11
November 0.809441E+09 4449.16 01-NOV-07:02 19.83 14.36 98503348.36 211.00 01-NOV-07:10 19.83 14.36
December 0.298990E+09 1076.88 26-DEC-13:55 23.00 10.16 89388341.05 181.22 21-DEC-08:00 23.00 10.16
                     
Annual Sum or Average 0.176496E+11         0.119052E+10        
Minimum of Months 0.158959E+09 837.06   13.17 6.52 84099803.29 180.93   16.50 9.89
Maximum of Months 0.290995E+10 4730.72   32.17 20.93 0.112922E+09 211.02   32.17 20.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.296284E+09 1352.77 27-JAN-16:27 26.50 9.48 0.212779E+09 305.01 13-JAN-13:09 26.50 9.48
February 88425217.01 744.22 01-FEB-16:15 15.67 6.89 0.183840E+09 305.04 03-FEB-14:50 16.83 7.75
March 0.318216E+09 1624.14 17-MAR-15:55 26.60 14.13 0.232334E+09 305.16 07-MAR-15:30 26.60 14.13
April 0.141276E+10 6450.48 17-APR-07:02 17.67 10.67 0.217826E+09 355.69 26-APR-07:10 21.50 10.77
May 0.212727E+10 6429.37 30-MAY-06:02 18.67 9.89 0.241642E+09 355.69 12-MAY-07:10 18.67 9.89
June 0.333447E+10 6621.93 19-JUN-05:02 22.17 10.17 0.244341E+09 355.70 30-JUN-07:10 29.33 19.12
July 0.343539E+10 6544.25 31-JUL-06:02 25.00 15.78 0.222285E+09 355.72 17-JUL-07:10 25.00 15.78
August 0.363387E+10 6690.81 14-AUG-05:02 26.00 16.58 0.255280E+09 355.71 16-AUG-07:10 31.00 20.55
September 0.302026E+10 6552.53 25-SEP-05:02 23.72 17.67 0.221240E+09 355.73 25-SEP-07:10 23.48 17.89
October 0.179013E+10 6747.45 10-OCT-06:01 16.50 11.11 0.228573E+09 355.71 02-OCT-07:10 16.50 11.11
November 0.830066E+09 6386.65 01-NOV-07:02 19.83 14.36 0.223777E+09 343.86 01-NOV-07:10 19.83 14.36
December 0.238071E+09 1208.40 01-DEC-15:40 23.20 10.01 0.198034E+09 305.00 13-DEC-14:09 16.00 9.55
                     
Annual Sum or Average 0.205252E+11         0.268195E+10        
Minimum of Months 88425217.01 744.22   15.67 6.89 0.183840E+09 305.00   16.00 7.75
Maximum of Months 0.363387E+10 6747.45   26.60 17.67 0.255280E+09 355.73   31.00 20.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.411045E+09 2089.04 31-JAN-16:55 29.00 10.73 0.130454E+09 181.12 31-JAN-09:20 29.00 10.73
February 0.133725E+09 1436.92 01-FEB-16:52 15.00 6.61 0.113087E+09 182.79 22-FEB-11:00 17.00 12.24
March 0.299407E+09 1739.34 16-MAR-15:57 28.80 13.95 0.141247E+09 183.63 28-MAR-13:30 19.40 7.11
April 0.119421E+10 5183.41 17-APR-07:02 17.67 10.67 0.130892E+09 211.00 26-APR-07:10 21.50 10.77
May 0.164716E+10 5217.31 08-MAY-06:01 20.50 9.41 0.144668E+09 211.00 25-MAY-07:10 23.33 10.24
June 0.252170E+10 5270.17 21-JUN-06:02 19.17 9.24 0.145640E+09 211.00 19-JUN-07:10 19.17 9.24
July 0.243176E+10 5627.70 16-JUL-18:42 30.17 20.38 0.132118E+09 211.02 17-JUL-07:10 27.33 20.24
August 0.263340E+10 5400.26 22-AUG-06:01 23.33 15.64 0.151713E+09 211.01 11-AUG-07:10 23.33 15.64
September 0.218771E+10 5390.15 25-SEP-05:02 23.72 17.67 0.131901E+09 211.03 25-SEP-07:10 23.48 17.89
October 0.143361E+10 5482.62 10-OCT-06:01 16.50 11.11 0.136797E+09 211.01 02-OCT-07:10 16.50 11.11
November 0.822385E+09 5183.55 02-NOV-07:02 16.50 11.83 0.134470E+09 211.00 03-NOV-07:10 15.17 12.00
December 0.303298E+09 2214.33 26-DEC-16:23 23.00 10.75 0.121483E+09 180.96 20-DEC-13:09 23.00 10.75
                     
Annual Sum or Average 0.160194E+11         0.161447E+10        
Minimum of Months 0.133725E+09 1436.92   15.00 6.61 0.113087E+09 180.96   15.17 7.11
Maximum of Months 0.263340E+10 5627.70   30.17 20.38 0.151713E+09 211.03   29.00 20.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27 1.81 0.00 0.00 01-JAN-00:10 4.27 1.81
February 0.00 0.00 01-FEB-00:10 11.90 4.43 0.00 0.00 01-FEB-00:10 11.90 4.43
March 0.00 0.00 01-MAR-00:10 11.85 8.83 0.00 0.00 01-MAR-00:10 11.85 8.83
April 0.00 0.00 01-APR-00:10 15.28 7.34 0.00 0.00 01-APR-00:10 15.28 7.34
May 0.00 0.00 01-MAY-00:10 19.10 7.18 0.00 0.00 01-MAY-00:10 19.10 7.18
June 0.00 0.00 01-JUN-00:10 25.83 11.09 0.00 0.00 01-JUN-00:10 25.83 11.09
July 0.00 0.00 01-JUL-00:05 27.73 14.60 0.00 0.00 01-JUL-00:10 27.73 14.60
August 0.00 0.00 01-AUG-00:10 29.40 18.35 0.00 0.00 01-AUG-00:10 29.40 18.35
September 0.00 0.00 01-SEP-00:10 26.22 16.66 0.00 0.00 01-SEP-00:10 26.22 16.66
October 0.00 0.00 01-OCT-00:10 25.15 15.51 0.00 0.00 01-OCT-00:10 25.15 15.51
November 0.00 0.00 01-NOV-00:10 17.23 10.27 0.00 0.00 01-NOV-00:10 17.23 10.27
December 0.00 0.00 01-DEC-00:10 9.20 2.98 0.00 0.00 01-DEC-00:10 9.20 2.98
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   4.27 1.81 0.00 0.00   4.27 1.81
Maximum of Months 0.00 0.00   29.40 18.35 0.00 0.00   29.40 18.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11250348.69 5055.81 02-JAN-08:62 7.00
February 36759.99 52.28 09-FEB-17:02 19.83
March 15230245.50 610.66 16-MAR-16:03 28.72
April 43043941.64 999.25 14-APR-17:02 34.83
May 64254821.67 1127.35 15-MAY-17:01 36.67
June 88355430.17 1479.13 28-JUN-17:01 41.83
July 63268295.70 1283.99 20-JUL-17:01 39.00
August 66799017.47 1411.38 25-AUG-17:01 40.67
September 54082522.14 1140.84 08-SEP-16:03 38.02
October 28711069.03 951.27 06-OCT-16:03 34.83
November 3802658.83 504.12 01-NOV-16:03 27.67
December 617984.24 267.71 22-DEC-17:02 23.33
         
Annual Sum or Average 0.439453E+09      
Minimum of Months 36759.99 52.28   7.00
Maximum of Months 88355430.17 5055.81   41.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16984256.77 5556.10 02-JAN-07:01 6.00
February 48520824.68 5147.99 13-FEB-07:03 8.33
March 88483943.45 7454.70 27-MAR-06:02 1.97
April 48570542.02 869.10 14-APR-17:11 34.67
May 77628320.51 975.12 31-MAY-17:11 36.67
June 80922651.15 1181.29 28-JUN-17:12 41.67
July 56543257.30 1067.06 20-JUL-17:12 39.00
August 60242427.64 1123.40 25-AUG-17:01 40.67
September 43305093.58 892.02 07-SEP-17:22 36.65
October 23781867.34 762.74 06-OCT-17:11 33.33
November 6638567.00 362.63 02-NOV-17:12 24.67
December 32639351.85 3898.45 07-DEC-08:62 3.50
         
Annual Sum or Average 0.584261E+09      
Minimum of Months 6638567.00 362.63   1.97
Maximum of Months 88483943.45 7454.70   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35605639.87 4380.29 02-JAN-07:01 6.00
February 25564369.93 1967.47 13-FEB-08:63 10.17
March 38533959.18 3370.03 27-MAR-06:02 1.97
April 31655416.69 581.64 14-APR-17:11 34.67
May 44069235.96 637.25 31-MAY-17:11 36.67
June 51587272.48 768.75 28-JUN-17:12 41.67
July 36501376.24 693.34 20-JUL-17:12 39.00
August 40743233.79 732.08 25-AUG-17:12 40.33
September 35725832.77 618.44 07-SEP-17:22 36.65
October 23844774.08 536.52 06-OCT-17:11 33.33
November 11924562.53 343.93 09-NOV-17:12 26.00
December 13463955.80 2442.49 18-DEC-08:62 5.83
         
Annual Sum or Average 0.389220E+09      
Minimum of Months 11924562.53 343.93   1.97
Maximum of Months 51587272.48 4380.29   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112085E+09 6268.51 02-JAN-06:03 4.33
February 51782915.50 4686.13 27-FEB-08:62 8.50
March 92513488.39 8341.45 27-MAR-06:02 1.97
April 46369640.53 885.21 14-APR-17:11 34.67
May 64022860.13 975.76 31-MAY-17:11 36.67
June 78894124.24 1200.65 28-JUN-17:12 41.67
July 56929425.03 1074.30 20-JUL-17:12 39.00
August 63341916.57 1149.57 25-AUG-17:01 40.67
September 51465194.06 940.94 07-SEP-17:01 37.02
October 33107477.58 808.38 06-OCT-17:11 33.33
November 14878665.77 530.23 24-NOV-08:62 7.33
December 42403207.16 5823.96 18-DEC-07:03 3.33
         
Annual Sum or Average 0.707794E+09      
Minimum of Months 14878665.77 530.23   1.97
Maximum of Months 0.112085E+09 8341.45   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 48317283.71 5170.96 02-JAN-07:01 6.00
February 61091511.40 2331.26 13-FEB-08:63 10.17
March 69263630.37 3192.42 27-MAR-06:02 1.97
April 30133738.75 580.75 14-APR-17:11 34.67
May 35246487.20 646.10 31-MAY-17:11 36.67
June 22983388.13 770.66 28-JUN-17:12 41.67
July 27487962.55 713.57 18-JUL-17:12 38.00
August 25525711.53 733.28 25-AUG-17:12 40.33
September 27011525.15 607.03 28-SEP-17:22 35.50
October 22912881.70 581.27 03-OCT-17:23 33.50
November 14839005.05 345.20 01-NOV-07:04 19.83
December 29701927.21 2846.01 18-DEC-08:62 5.83
         
Annual Sum or Average 0.414515E+09      
Minimum of Months 14839005.05 345.20   1.97
Maximum of Months 69263630.37 5170.96   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.714248E+09 593.08 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.645736E+09 593.08 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.752015E+09 593.08 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.685116E+09 593.08 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.733131E+09 593.08 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.722883E+09 593.08 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.695364E+09 593.08 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.752015E+09 593.08 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.685116E+09 593.08 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.714248E+09 593.08 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.704000E+09 593.08 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.695364E+09 593.08 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.849924E+10     0.141401E+11    
Minimum of Months 0.645736E+09 593.08   0.107295E+10 973.59  
Maximum of Months 0.752015E+09 593.08   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.450562E+09 442.12 20-JAN-16:00 0.899552E+09 738.04 02-JAN-08:09
February 0.413093E+09 438.90 10-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.474885E+09 434.30 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.435025E+09 418.31 04-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.480791E+09 409.00 05-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.483399E+09 411.48 22-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.457766E+09 420.34 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.492919E+09 437.56 04-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.432908E+09 420.00 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.448384E+09 424.15 27-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.445916E+09 449.59 28-NOV-16:30 0.888667E+09 738.04 01-NOV-07:10
December 0.443239E+09 449.59 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.545889E+10     0.107191E+11    
Minimum of Months 0.413093E+09 409.00   0.813362E+09 738.04  
Maximum of Months 0.492919E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287463E+09 263.01 20-JAN-16:00 0.533626E+09 437.82 02-JAN-08:09
February 0.258588E+09 260.44 10-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.293593E+09 254.82 09-MAR-16:00 0.565383E+09 437.82 01-MAR-08:09
April 0.265266E+09 242.11 03-APR-15:00 0.511694E+09 437.82 03-APR-07:10
May 0.283381E+09 241.60 25-MAY-15:30 0.549505E+09 437.82 01-MAY-07:10
June 0.279908E+09 243.64 02-JUN-15:00 0.542644E+09 437.82 01-JUN-07:10
July 0.268913E+09 249.34 13-JUL-15:00 0.518151E+09 437.82 03-JUL-07:10
August 0.292800E+09 259.39 04-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.266956E+09 248.64 29-SEP-14:30 0.510887E+09 437.82 01-SEP-07:10
October 0.283277E+09 255.92 31-OCT-15:00 0.534030E+09 437.82 02-OCT-07:10
November 0.283495E+09 266.70 28-NOV-16:30 0.527169E+09 437.82 01-NOV-07:10
December 0.281713E+09 266.70 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.334535E+10     0.635872E+10    
Minimum of Months 0.258588E+09 241.60   0.482497E+09 437.82  
Maximum of Months 0.293593E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.515154E+09 443.42 20-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.459955E+09 440.67 10-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.523428E+09 437.28 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.467509E+09 420.02 04-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.491187E+09 412.23 26-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.481632E+09 403.67 12-JUN-09:30 0.914754E+09 738.04 01-JUN-07:10
July 0.464106E+09 418.92 28-JUL-12:39 0.873466E+09 738.04 03-JUL-07:10
August 0.514586E+09 438.21 04-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.471948E+09 432.35 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.508915E+09 440.25 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.504887E+09 449.59 28-NOV-16:30 0.888667E+09 738.04 01-NOV-07:10
December 0.503041E+09 449.59 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.590635E+10     0.107191E+11    
Minimum of Months 0.459955E+09 403.67   0.813362E+09 738.04  
Maximum of Months 0.523428E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287913E+09 263.37 20-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.259670E+09 261.57 03-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.296045E+09 261.31 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.268163E+09 255.79 04-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.286472E+09 251.01 05-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.282589E+09 250.43 27-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.273832E+09 254.10 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.298642E+09 260.37 04-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.269172E+09 258.28 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.285661E+09 262.25 27-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.281794E+09 266.70 28-NOV-16:30 0.527169E+09 437.82 01-NOV-07:10
December 0.281673E+09 266.70 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.337163E+10     0.635872E+10    
Minimum of Months 0.259670E+09 250.43   0.482497E+09 437.82  
Maximum of Months 0.298642E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.714248E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.685116E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.733131E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.722883E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.695364E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.685116E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.714248E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.704000E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.695364E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.849924E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.450562E+09 0.899552E+09 0.00 0.00 0.00 0.00 5285801.51 0.347559E+09
February 0.488155E+09 0.413093E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.421001E+09
March 0.590925E+09 0.474885E+09 0.953087E+09 0.00 0.00 0.00 0.00 16363835.40 0.357086E+09
April 0.513848E+09 0.435025E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.145482E+09 0.127392E+09
May 0.565233E+09 0.480791E+09 0.926320E+09 0.00 0.00 0.00 0.00 0.261242E+09 77717185.50
June 0.565233E+09 0.483399E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.431413E+09 24680388.18
July 0.513848E+09 0.457766E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.336371E+09 15828196.41
August 0.590925E+09 0.492919E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.365773E+09 31987611.67
September 0.513848E+09 0.432908E+09 0.861220E+09 0.00 0.00 0.00 0.00 0.245072E+09 57472457.75
October 0.539540E+09 0.448384E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.105644E+09 0.225436E+09
November 0.539540E+09 0.445916E+09 0.888667E+09 0.00 0.00 0.00 0.00 12110255.57 0.340243E+09
December 0.513848E+09 0.443239E+09 0.872785E+09 0.00 0.00 0.00 0.00 701207.39 0.487343E+09
                   
Annual Sum or Average 0.647448E+10 0.545889E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.192546E+10 0.251375E+10
Minimum of Months 0.488155E+09 0.413093E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 15828196.41
Maximum of Months 0.590925E+09 0.492919E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.431413E+09 0.487343E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.287463E+09 0.533626E+09 0.00 0.00 0.00 0.00 71243.62 25295608.07
February 0.211974E+09 0.258588E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 19119969.97
March 0.256600E+09 0.293593E+09 0.565383E+09 0.00 0.00 0.00 0.00 184236.95 25278950.61
April 0.223130E+09 0.265266E+09 0.511694E+09 0.00 0.00 0.00 0.00 2890109.08 10767562.82
May 0.245443E+09 0.283381E+09 0.549505E+09 0.00 0.00 0.00 0.00 5748719.33 7183459.10
June 0.245443E+09 0.279908E+09 0.542644E+09 0.00 0.00 0.00 0.00 11854846.27 3164130.19
July 0.223130E+09 0.268913E+09 0.518151E+09 0.00 0.00 0.00 0.00 9970833.47 3782200.91
August 0.256600E+09 0.292800E+09 0.565383E+09 0.00 0.00 0.00 0.00 6898615.30 4596106.65
September 0.223130E+09 0.266956E+09 0.510887E+09 0.00 0.00 0.00 0.00 4372154.85 7692390.14
October 0.234287E+09 0.283277E+09 0.534030E+09 0.00 0.00 0.00 0.00 1539305.64 17837905.89
November 0.234287E+09 0.283495E+09 0.527169E+09 0.00 0.00 0.00 0.00 134513.03 25499449.98
December 0.223130E+09 0.281713E+09 0.517747E+09 0.00 0.00 0.00 0.00 12023.96 25220081.33
                   
Annual Sum or Average 0.281144E+10 0.334535E+10 0.635872E+10 0.00 0.00 0.00 0.00 43676601.49 0.175438E+09
Minimum of Months 0.211974E+09 0.258588E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 3164130.19
Maximum of Months 0.256600E+09 0.293593E+09 0.565383E+09 0.00 0.00 0.00 0.00 11854846.27 25499449.98



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.515154E+09 0.899552E+09 0.00 0.00 0.00 0.00 250618.92 34866916.99
February 0.488155E+09 0.459955E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 27075148.06
March 0.590925E+09 0.523428E+09 0.953087E+09 0.00 0.00 0.00 0.00 359196.51 35703891.88
April 0.513848E+09 0.467509E+09 0.862580E+09 0.00 0.00 0.00 0.00 5457840.04 14509034.61
May 0.565233E+09 0.491187E+09 0.926320E+09 0.00 0.00 0.00 0.00 10050849.27 9758380.84
June 0.565233E+09 0.481632E+09 0.914754E+09 0.00 0.00 0.00 0.00 18126318.41 4432990.81
July 0.513848E+09 0.464106E+09 0.873466E+09 0.00 0.00 0.00 0.00 15412698.68 5291497.00
August 0.590925E+09 0.514586E+09 0.953087E+09 0.00 0.00 0.00 0.00 10782688.64 6215240.23
September 0.513848E+09 0.471948E+09 0.861220E+09 0.00 0.00 0.00 0.00 7016252.44 10658985.07
October 0.539540E+09 0.508915E+09 0.900233E+09 0.00 0.00 0.00 0.00 2715325.54 24710353.71
November 0.539540E+09 0.504887E+09 0.888667E+09 0.00 0.00 0.00 0.00 370931.26 36114925.36
December 0.513848E+09 0.503041E+09 0.872785E+09 0.00 0.00 0.00 0.00 69211.41 35598855.72
                   
Annual Sum or Average 0.647448E+10 0.590635E+10 0.107191E+11 0.00 0.00 0.00 0.00 70611931.11 0.244936E+09
Minimum of Months 0.488155E+09 0.459955E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 4432990.81
Maximum of Months 0.590925E+09 0.523428E+09 0.953087E+09 0.00 0.00 0.00 0.00 18126318.41 36114925.36



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.287913E+09 0.533626E+09 0.00 0.00 0.00 0.00 88674.92 25965348.70
February 0.289580E+09 0.259670E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 19261991.18
March 0.350544E+09 0.296045E+09 0.565383E+09 0.00 0.00 0.00 0.00 187119.33 25772860.71
April 0.304821E+09 0.268163E+09 0.511694E+09 0.00 0.00 0.00 0.00 2533718.75 11784783.35
May 0.335303E+09 0.286472E+09 0.549505E+09 0.00 0.00 0.00 0.00 5235828.35 7765028.80
June 0.335303E+09 0.282589E+09 0.542644E+09 0.00 0.00 0.00 0.00 11135575.09 3395162.59
July 0.304821E+09 0.273832E+09 0.518151E+09 0.00 0.00 0.00 0.00 9669272.82 3938582.49
August 0.350544E+09 0.298642E+09 0.565383E+09 0.00 0.00 0.00 0.00 6686607.86 4678330.41
September 0.304821E+09 0.269172E+09 0.510887E+09 0.00 0.00 0.00 0.00 4172021.22 7927373.02
October 0.320062E+09 0.285661E+09 0.534030E+09 0.00 0.00 0.00 0.00 1546160.69 18361159.67
November 0.320062E+09 0.281794E+09 0.527169E+09 0.00 0.00 0.00 0.00 147933.49 26124675.96
December 0.304821E+09 0.281673E+09 0.517747E+09 0.00 0.00 0.00 0.00 12293.23 25398636.75
                   
Annual Sum or Average 0.384075E+10 0.337163E+10 0.635872E+10 0.00 0.00 0.00 0.00 41415205.74 0.180374E+09
Minimum of Months 0.289580E+09 0.259670E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 3395162.59
Maximum of Months 0.350544E+09 0.298642E+09 0.565383E+09 0.00 0.00 0.00 0.00 11135575.09 26124675.96



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139244E+10 0.235017E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.796741E+09 0.239114E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.933382E+09 0.319225E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120893E+10 0.438476E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.130182E+10 0.466999E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108929E+10 0.469071E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.768288E+09 0.421707E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.966274E+09 0.393880E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.840907E+09 0.315874E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133147E+10 0.290506E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.114905E+10 0.236697E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148861E+10 0.209610E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132672E+11 0.403618E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.768288E+09 0.209610E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148861E+10 0.469071E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 593.08 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 593.08 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 593.08 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 593.08 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 593.08 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 593.08 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 593.08 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 593.08 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 593.08 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 593.08 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 593.08 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 593.08 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 442.12 20-JAN-16:00 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 532.33 31-JAN-17:02 2467.52 12-JAN-07:03
February 732.70 01-FEB-08:09 438.90 10-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2563.71 01-FEB-07:03
March 732.70 01-MAR-08:09 434.30 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 589.58 16-MAR-16:03 2749.23 27-MAR-06:10
April 732.70 03-APR-07:10 418.31 04-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 1386.27 14-APR-16:03 1915.69 21-APR-06:03
May 732.70 01-MAY-07:10 409.00 05-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 1652.91 31-MAY-16:03 1645.31 01-MAY-06:03
June 732.70 01-JUN-07:10 411.48 22-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 2282.47 28-JUN-16:03 926.24 21-JUN-06:02
July 732.70 03-JUL-07:10 420.34 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 1909.95 20-JUL-16:03 650.99 03-JUL-06:02
August 732.70 01-AUG-07:10 437.56 04-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 2160.32 25-AUG-16:03 926.74 24-AUG-06:02
September 732.70 01-SEP-07:10 420.00 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 1770.27 08-SEP-16:03 1269.17 22-SEP-06:03
October 732.70 02-OCT-07:10 424.15 27-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 1343.99 03-OCT-16:03 2659.17 25-OCT-06:03
November 732.70 01-NOV-07:10 449.59 28-NOV-16:30 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 437.61 09-NOV-13:00 2612.83 24-NOV-07:03
December 732.70 01-DEC-08:09 449.59 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 43.68 21-DEC-14:55 3233.67 05-DEC-07:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   409.00   738.04   0.00 0.00 0.00 0.00 0.00   650.99  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 2282.47   3233.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 263.01 20-JAN-16:00 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 1.49 31-JAN-14:00 38.38 01-JAN-01:00
February 434.65 01-FEB-08:09 260.44 10-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 51.12 02-FEB-23:00
March 434.65 01-MAR-08:09 254.82 09-MAR-16:00 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 3.16 15-MAR-12:55 42.29 28-MAR-04:00
April 434.65 03-APR-07:10 242.11 03-APR-15:00 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 17.21 30-APR-16:00 32.29 16-APR-09:00
May 434.65 01-MAY-07:10 241.60 25-MAY-15:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 22.09 31-MAY-18:10 21.00 23-MAY-05:00
June 434.65 01-JUN-07:10 243.64 02-JUN-15:00 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 37.79 30-JUN-18:10 14.85 13-JUN-06:00
July 434.65 03-JUL-07:10 249.34 13-JUL-15:00 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 39.54 22-JUL-17:53 25.13 17-JUL-19:52
August 434.65 01-AUG-07:10 259.39 04-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 35.76 13-AUG-15:53 32.52 05-AUG-17:22
September 434.65 01-SEP-07:10 248.64 29-SEP-14:30 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 21.31 17-SEP-12:20 25.02 03-SEP-05:00
October 434.65 02-OCT-07:10 255.92 31-OCT-15:00 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 14.36 01-OCT-14:10 55.45 22-OCT-13:52
November 434.65 01-NOV-07:10 266.70 28-NOV-16:30 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 2.73 19-NOV-14:55 47.30 29-NOV-02:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.95 25-DEC-14:00 37.76 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   241.60   437.82   0.00 0.00 0.00 0.00 0.00   14.85  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 39.54   55.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 443.42 20-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 7.73 16-JAN-11:53 51.85 01-JAN-01:00
February 732.70 01-FEB-08:09 440.67 10-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 73.56 02-FEB-23:00
March 732.70 01-MAR-08:09 437.28 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 5.46 18-MAR-17:02 61.27 28-MAR-04:00
April 732.70 03-APR-07:10 420.02 04-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 35.25 30-APR-14:53 37.88 26-APR-21:00
May 732.70 01-MAY-07:10 412.23 26-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 33.70 31-MAY-18:10 31.05 23-MAY-05:00
June 732.70 01-JUN-07:10 403.67 12-JUN-09:30 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 57.17 30-JUN-18:10 21.11 13-JUN-06:00
July 732.70 03-JUL-07:10 418.92 28-JUL-12:39 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 59.31 22-JUL-17:53 35.89 17-JUL-19:52
August 732.70 01-AUG-07:10 438.21 04-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 54.16 13-AUG-16:05 45.86 05-AUG-17:22
September 732.70 01-SEP-07:10 432.35 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 32.53 17-SEP-12:00 36.00 03-SEP-05:00
October 732.70 02-OCT-07:10 440.25 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 21.79 01-OCT-14:17 74.46 22-OCT-13:52
November 732.70 01-NOV-07:10 449.59 28-NOV-16:30 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 11.80 19-NOV-14:55 68.31 29-NOV-02:00
December 732.70 01-DEC-08:09 449.59 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 4.78 25-DEC-15:53 55.25 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   403.67   738.04   0.00 0.00 0.00 0.00 0.00   21.11  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 59.31   74.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 263.37 20-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 2.89 16-JAN-11:53 39.61 01-JAN-01:00
February 434.65 01-FEB-08:09 261.57 03-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 53.22 02-FEB-23:00
March 434.65 01-MAR-08:09 261.31 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 3.16 15-MAR-13:00 42.97 28-MAR-04:00
April 434.65 03-APR-07:10 255.79 04-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 18.45 30-APR-13:00 33.71 26-APR-18:02
May 434.65 01-MAY-07:10 251.01 05-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 17.71 31-MAY-18:02 21.85 23-MAY-05:00
June 434.65 01-JUN-07:10 250.43 27-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 36.25 30-JUN-18:10 15.09 13-JUN-06:00
July 434.65 03-JUL-07:10 254.10 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 39.54 22-JUL-18:00 25.37 17-JUL-19:52
August 434.65 01-AUG-07:10 260.37 04-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 35.76 13-AUG-16:00 32.29 05-AUG-17:22
September 434.65 01-SEP-07:10 258.28 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 21.30 17-SEP-12:25 24.77 03-SEP-05:00
October 434.65 02-OCT-07:10 262.25 27-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 14.32 01-OCT-14:10 51.70 22-OCT-14:00
November 434.65 01-NOV-07:10 266.70 28-NOV-16:30 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 4.04 19-NOV-13:00 47.59 29-NOV-02:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 1.33 25-DEC-14:00 37.82 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   250.43   437.82   0.00 0.00 0.00 0.00 0.00   15.09  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 39.54   53.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1735.83 28-JAN-07:53 4634.17 09-JAN-13:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1402.22 02-FEB-06:00 5691.97 28-FEB-13:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1519.22 27-MAR-07:32 6167.80 26-MAR-12:50
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1656.24 22-APR-06:42 6446.02 27-APR-12:50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1694.31 14-MAY-06:32 6292.26 27-MAY-12:50
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1473.69 16-JUN-06:02 6154.02 25-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1599.09 03-JUL-06:02 6156.45 27-JUL-13:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1641.44 25-AUG-06:42 5958.87 07-AUG-13:40
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1687.22 17-SEP-04:55 5592.33 07-SEP-13:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1575.78 14-OCT-01:00 5438.89 26-OCT-12:40
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1509.68 27-NOV-08:62 5100.97 14-NOV-13:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1833.47 21-DEC-07:05 4256.19 14-DEC-13:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1402.22   4256.19  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1833.47   6446.02  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2868.46 27-JAN-08:63 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
February 2148.67 01-FEB-16:05 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
March 5761.13 21-MAR-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
April 6167.14 07-APR-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
May 6124.65 30-MAY-06:02 1217.84 1660.60 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
June 6161.13 26-JUN-05:02 531.60 757.81 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
July 6313.19 03-JUL-05:02 531.60 757.81 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
August 6099.77 23-AUG-06:01 1420.81 1937.36 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
September 6043.73 28-SEP-06:02 1217.84 1660.60 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
October 6397.24 12-OCT-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
November 6135.35 06-NOV-08:62 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
December 2315.28 26-DEC-16:50 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2148.67   531.60 757.81 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6397.24   4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5275.94 30-JAN-14:40 732.70 328.16 738.04 0.00 0.00 0.00 0.00 16.23 0.00
February 3460.75 01-FEB-15:30 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 177.67
March 3064.21 20-MAR-14:30 732.70 328.16 738.04 0.00 0.00 0.00 0.00 78.07 0.00
April 6247.64 26-APR-07:02 3663.49 1918.89 3690.21 0.00 0.00 0.00 0.00 0.00 61.69
May 6401.23 08-MAY-06:01 1077.07 1403.54 2583.15 0.00 0.00 0.00 0.00 0.00 803.45
June 6652.71 19-JUN-05:02 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 129.73
July 6617.30 31-JUL-05:02 402.98 574.47 1845.11 0.00 0.00 0.00 0.00 0.00 51.94
August 6736.14 14-AUG-05:02 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 63.31
September 6785.66 25-SEP-05:02 402.98 574.47 1845.11 0.00 0.00 0.00 0.00 0.00 104.94
October 6870.07 10-OCT-06:01 1077.07 1468.65 2583.15 0.00 0.00 0.00 0.00 0.00 1499.92
November 6313.74 01-NOV-16:05 937.85 889.66 1476.09 0.00 0.00 0.00 0.00 374.66 0.00
December 5494.58 26-DEC-13:55 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 0.00 18.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3064.21   402.98 328.16 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6870.07   3663.49 1918.89 3690.21 0.00 0.00 0.00 0.00 374.66 1499.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1153.53 31-JAN-16:07 1303.94 731.47 1313.45 0.00 0.00 0.00 0.00 1.25 0.00
February 837.06 01-FEB-11:02 2173.23 1073.66 2189.08 0.00 0.00 0.00 0.00 0.00 3.94
March 1369.96 23-MAR-10:45 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 0.39
April 4519.71 17-APR-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 2.19
May 4512.78 30-MAY-06:02 547.65 545.06 1313.45 0.00 0.00 0.00 0.00 0.00 2.47
June 4620.15 19-JUN-05:02 286.87 408.94 1313.45 0.00 0.00 0.00 0.00 0.00 7.87
July 4698.54 30-JUL-09:02 0.00 233.59 448.42 0.00 0.00 0.00 0.00 0.00 0.13
August 4682.14 13-AUG-09:02 0.00 233.59 448.42 0.00 0.00 0.00 0.00 1.89 0.00
September 4685.26 10-SEP-09:42 0.00 233.59 448.42 0.00 0.00 0.00 0.00 1.78 0.00
October 4730.72 10-OCT-06:01 638.93 871.22 1532.36 0.00 0.00 0.00 0.00 0.00 3.52
November 4449.16 01-NOV-07:02 2173.23 1276.90 2189.08 0.00 0.00 0.00 0.00 0.00 1.22
December 1076.88 26-DEC-13:55 869.29 483.09 875.63 0.00 0.00 0.00 0.00 0.00 0.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 837.06   0.00 233.59 448.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4730.72   2173.23 1276.90 2189.08 0.00 0.00 0.00 0.00 1.89 7.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1352.77 27-JAN-16:27 2198.10 1217.40 2214.13 0.00 0.00 0.00 0.00 1.07 0.00
February 744.22 01-FEB-16:15 2930.79 1643.50 2952.17 0.00 0.00 0.00 0.00 0.00 4.91
March 1624.14 17-MAR-15:55 2930.79 1509.50 2952.17 0.00 0.00 0.00 0.00 1.95 0.00
April 6450.48 17-APR-07:02 3663.49 1996.70 3690.21 0.00 0.00 0.00 0.00 0.00 3.28
May 6429.37 30-MAY-06:02 923.20 1115.04 2214.13 0.00 0.00 0.00 0.00 0.00 3.39
June 6621.93 19-JUN-05:02 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 11.61
July 6544.25 31-JUL-06:02 923.20 1180.06 2214.13 0.00 0.00 0.00 0.00 0.00 1.12
August 6690.81 14-AUG-05:02 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 4.86
September 6552.53 25-SEP-05:02 402.98 574.47 1845.11 0.00 0.00 0.00 0.00 0.00 7.55
October 6747.45 10-OCT-06:01 1077.07 1468.65 2583.15 0.00 0.00 0.00 0.00 0.00 4.91
November 6386.65 01-NOV-07:02 3663.49 2192.27 3690.21 0.00 0.00 0.00 0.00 0.00 1.74
December 1208.40 01-DEC-15:40 1465.40 827.93 1476.09 0.00 0.00 0.00 0.00 0.00 0.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 744.22   402.98 574.47 1476.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6747.45   3663.49 2192.27 3690.21 0.00 0.00 0.00 0.00 1.95 11.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2089.04 31-JAN-16:55 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 1.25 0.00
February 1436.92 01-FEB-16:52 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 6.14
March 1739.34 16-MAR-15:57 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 2.32 0.00
April 5183.41 17-APR-07:02 2173.23 1252.99 2189.08 0.00 0.00 0.00 0.00 0.00 2.10
May 5217.31 08-MAY-06:01 638.93 844.70 1532.36 0.00 0.00 0.00 0.00 0.00 1.88
June 5270.17 21-JUN-06:02 547.65 722.17 1313.45 0.00 0.00 0.00 0.00 0.00 2.51
July 5627.70 16-JUL-18:42 0.00 256.40 448.42 0.00 0.00 0.00 0.00 0.00 1.38
August 5400.26 22-AUG-06:01 638.93 856.36 1532.36 0.00 0.00 0.00 0.00 0.00 1.43
September 5390.15 25-SEP-05:02 239.06 340.78 1094.54 0.00 0.00 0.00 0.00 0.00 5.16
October 5482.62 10-OCT-06:01 638.93 871.22 1532.36 0.00 0.00 0.00 0.00 0.00 3.50
November 5183.55 02-NOV-07:02 2173.23 1309.59 2189.08 0.00 0.00 0.00 0.00 0.00 2.37
December 2214.33 26-DEC-16:23 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 0.00 0.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1436.92   0.00 256.40 448.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5627.70   2173.23 1309.59 2189.08 0.00 0.00 0.00 0.00 2.32 6.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 782.43 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 962.42 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 980.81 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1235.45 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1051.70 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1231.60 0.00
July 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 686.84 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 608.17 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 687.04 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 495.96 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1306.59 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1054.01 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 495.96 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1306.59 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.124205E+11 13272.45 31-JAN-15:39 142664.82 237.77 02-JAN-06:10
February 0.105697E+11 11640.67 01-FEB-15:50 0.00 0.00 01-FEB-00:10
March 0.125504E+11 12927.43 20-MAR-15:00 913228.36 1522.05 27-MAR-06:10
April 0.129225E+11 15214.33 14-APR-14:39 0.00 0.00 01-APR-00:10
May 0.145648E+11 15854.49 31-MAY-15:30 0.00 0.00 01-MAY-00:10
June 0.161586E+11 17833.68 28-JUN-15:00 0.00 0.00 01-JUN-00:10
July 0.156606E+11 17458.07 10-JUL-15:09 0.00 0.00 01-JUL-00:10
August 0.171145E+11 17589.06 14-AUG-15:50 0.00 0.00 01-AUG-00:10
September 0.150608E+11 17186.62 07-SEP-15:20 0.00 0.00 01-SEP-00:10
October 0.140375E+11 16929.66 02-OCT-14:09 0.00 0.00 01-OCT-00:10
November 0.127878E+11 14504.58 01-NOV-14:00 0.00 0.00 01-NOV-00:10
December 0.118785E+11 12834.94 26-DEC-16:49 128401.22 214.00 18-DEC-07:10
             
Annual Sum or Average 0.165726E+12     1184294.41    
Minimum of Months 0.105697E+11 11640.67   0.00 0.00  
Maximum of Months 0.171145E+11 17833.68   913228.36 1522.05  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.225534E+10 0.102459E+10 0.405300E+10 0.00 0.198820E+10 0.01 38070913.09 0.105153E+10 0.00 0.00 0.00 0.200980E+10 0.00
February 0.203704E+10 0.852054E+09 0.366466E+10 0.00 0.179885E+10 0.00 24944093.86 0.377460E+09 0.00 0.00 0.00 0.181469E+10 0.00
March 0.233997E+10 0.846034E+09 0.429420E+10 0.00 0.217755E+10 0.00 52584712.52 0.816926E+09 0.00 0.00 0.00 0.202318E+10 0.00
April 0.212108E+10 0.725366E+09 0.388642E+10 0.00 0.189445E+10 0.00 0.00 0.240945E+10 0.00 0.00 0.00 0.188571E+10 0.00
May 0.227496E+10 0.668309E+09 0.417360E+10 0.00 0.208678E+10 0.00 0.00 0.342572E+10 0.00 0.00 0.00 0.193540E+10 0.00
June 0.225041E+10 0.617431E+09 0.412149E+10 0.00 0.212211E+10 0.00 0.00 0.519560E+10 0.00 0.00 0.00 0.185160E+10 0.00
July 0.215998E+10 0.652638E+09 0.393546E+10 0.00 0.194623E+10 0.00 0.00 0.510309E+10 0.00 0.00 0.00 0.186319E+10 0.00
August 0.235096E+10 0.716737E+09 0.429420E+10 0.00 0.222302E+10 0.00 0.00 0.562114E+10 0.00 0.00 0.00 0.190846E+10 0.00
September 0.212610E+10 0.772705E+09 0.388029E+10 0.00 0.192591E+10 0.00 0.00 0.452045E+10 0.00 0.00 0.00 0.183532E+10 0.00
October 0.224048E+10 0.899328E+09 0.405607E+10 0.00 0.199929E+10 0.00 0.00 0.290773E+10 0.00 0.00 0.00 0.193465E+10 0.00
November 0.222009E+10 0.968127E+09 0.400396E+10 0.00 0.198826E+10 0.00 11899296.48 0.167815E+10 0.00 0.00 0.00 0.191731E+10 0.00
December 0.220503E+10 0.105543E+10 0.393240E+10 0.00 0.189391E+10 0.00 0.111212E+09 0.701248E+09 0.00 0.00 0.00 0.197930E+10 0.00
                           
Annual Sum or Average 0.265815E+11 0.979875E+10 0.482958E+11 0.00 0.240446E+11 0.01 0.238711E+09 0.338085E+11 0.00 0.00 0.00 0.229586E+11 0.00
Minimum of Months 0.203704E+10 0.617431E+09 0.366466E+10 0.00 0.179885E+10 0.00 0.00 0.377460E+09 0.00 0.00 0.00 0.181469E+10 0.00
Maximum of Months 0.235096E+10 0.105543E+10 0.429420E+10 0.00 0.222302E+10 0.01 0.111212E+09 0.562114E+10 0.00 0.00 0.00 0.202318E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 142664.82 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 913228.36 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 128401.22 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 1184294.41 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 913228.36 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2003.89 20-JAN-16:00 1049.10 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 2023.00 02-JAN-06:10 0.00 20-JAN-10:30 3723.96 02-JAN-07:10
February 1994.62 10-FEB-08:09 1049.10 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 2023.00 01-FEB-06:10 0.00 01-FEB-00:10 1745.99 13-FEB-07:10
March 1978.71 21-MAR-07:10 1049.10 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 2023.00 17-MAR-11:20 0.00 01-MAR-00:10 2676.35 27-MAR-06:10
April 1892.50 06-APR-07:10 1049.10 01-APR-05:10 3325.31 03-APR-07:10 0.00 2023.00 03-APR-05:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 1901.63 26-MAY-08:30 1049.10 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 2023.00 01-MAY-05:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 1851.83 07-JUN-12:30 1049.10 01-JUN-05:10 3325.31 01-JUN-07:10 0.00 2023.00 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 1918.05 13-JUL-15:00 1049.10 01-JUL-05:10 3325.31 03-JUL-07:10 0.00 2023.00 10-JUL-15:39 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 1988.60 04-AUG-07:10 1049.10 01-AUG-05:10 3325.31 01-AUG-07:10 0.00 2023.00 08-AUG-16:40 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 1949.79 29-SEP-07:10 1049.10 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 2023.00 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 1971.09 27-OCT-07:10 1049.10 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 2023.00 02-OCT-05:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 2025.66 28-NOV-16:30 1049.10 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 2023.00 01-NOV-05:10 0.00 01-NOV-00:10 250.00 23-NOV-01:39
December 2025.66 01-DEC-16:30 1049.10 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 2023.00 01-DEC-06:10 0.00 01-DEC-00:10 2086.47 07-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 1851.83   1049.10   3325.31   0.00 2023.00   0.00   0.00  
Maximum of Months 2025.66   1049.10   3325.31   0.00 2023.00   0.00   3723.96  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 3553.58 31-JAN-16:30 0.00 0.00 0.00 2784.46 24-JAN-12:00 0.00
February 1806.08 01-FEB-15:00 0.00 0.00 0.00 2784.11 02-FEB-12:30 0.00
March 3144.61 16-MAR-15:00 0.00 0.00 0.00 2780.12 01-MAR-12:39 0.00
April 5607.20 14-APR-15:00 0.00 0.00 0.00 2770.05 03-APR-11:30 0.00
May 6144.03 31-MAY-15:00 0.00 0.00 0.00 2760.17 01-MAY-11:20 0.00
June 8024.09 28-JUN-15:00 0.00 0.00 0.00 2749.69 01-JUN-11:39 0.00
July 7735.88 31-JUL-15:00 0.00 0.00 0.00 2742.42 05-JUL-11:39 0.00
August 7771.99 14-AUG-15:00 0.00 0.00 0.00 2745.35 30-AUG-11:00 0.00
September 7466.41 08-SEP-15:50 0.00 0.00 0.00 2753.67 29-SEP-11:00 0.00
October 7158.66 02-OCT-14:09 0.00 0.00 0.00 2764.98 30-OCT-11:00 0.00
November 4670.97 01-NOV-14:00 0.00 0.00 0.00 2775.62 30-NOV-12:39 0.00
December 2989.48 26-DEC-16:30 0.00 0.00 0.00 2782.24 28-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 1806.08   0.00 0.00 0.00 2742.42   0.00
Maximum of Months 8024.09   0.00 0.00 0.00 2784.46   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 13272.45 31-JAN-15:39 1763.85 3325.31 0.00 0.00 2023.00 0.00 0.00 3436.24 0.00
February 11640.67 01-FEB-15:50 1773.01 3325.31 0.00 0.00 2023.00 0.00 0.00 1795.44 0.00
March 12927.43 20-MAR-15:00 1750.15 3325.31 0.00 0.00 2023.00 0.00 0.00 3088.15 0.00
April 15214.33 14-APR-14:39 1727.49 3325.31 0.00 0.00 2023.00 0.00 0.00 5423.78 0.00
May 15854.49 31-MAY-15:30 1783.15 3325.31 0.00 0.00 2023.00 0.00 0.00 5999.58 0.00
June 17833.68 28-JUN-15:00 1742.99 3325.31 0.00 0.00 2023.00 0.00 0.00 8024.09 0.00
July 17458.07 10-JUL-15:09 1794.40 3325.31 0.00 0.00 2023.00 0.00 0.00 7598.14 0.00
August 17589.06 14-AUG-15:50 1756.32 3325.31 0.00 0.00 2023.00 0.00 0.00 7766.87 0.00
September 17186.62 07-SEP-15:20 1752.86 3325.31 0.00 0.00 2023.00 0.00 0.00 7364.45 0.00
October 16929.66 02-OCT-14:09 1714.21 3325.31 0.00 0.00 2023.00 0.00 0.00 7158.66 0.00
November 14504.58 01-NOV-14:00 1771.41 3325.31 0.00 0.00 2023.00 0.00 0.00 4670.97 0.00
December 12834.94 26-DEC-16:49 1809.88 3325.31 0.00 0.00 2023.00 0.00 0.00 2930.63 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 11640.67   1714.21 3325.31 0.00 0.00 2023.00 0.00 0.00 1795.44 0.00
Maximum of Months 17833.68   1809.88 3325.31 0.00 0.00 2023.00 0.00 0.00 8024.09 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 237.77 02-JAN-06:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 1522.05 27-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 214.00 18-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 1522.05   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 24.54 0.17 24.54
June 0.00 0.00 0.00 0.00 39.67 24.81 39.67 24.81
July 0.00 0.00 0.00 0.00 82.50 24.87 82.50 24.87
August 0.00 0.00 0.00 0.00 56.83 24.92 56.83 24.92
September 0.00 0.00 0.00 0.00 49.00 24.83 49.00 24.83
October 0.00 0.00 0.00 0.00 10.67 24.68 10.67 24.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   238.83 24.86 238.83 24.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 82.50 24.92 82.50 24.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 5.50 24.65 5.50 24.65
July 0.00 0.00 0.00 0.00 11.83 24.87 11.33 24.76
August 0.00 0.00 0.00 0.00 22.17 25.47 19.33 25.15
September 0.00 0.00 0.00 0.00 52.67 25.48 47.17 25.23
October 0.00 0.00 0.00 0.00 34.83 25.54 31.50 25.30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   127.00 25.40 114.83 25.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 52.67 25.54 47.17 25.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 14.67 27.77 4.83 26.99
July 0.00 0.00 0.00 0.00 19.17 28.20 5.50 27.39
August 0.00 0.00 0.00 0.00 21.83 26.69 9.50 26.10
September 0.00 0.00 0.00 0.00 9.17 27.32 3.67 26.54
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   64.83 27.47 23.50 26.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 21.83 28.20 9.50 27.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.50 0.17 24.50
July 0.00 0.00 0.00 0.00 1.00 24.67 1.00 24.67
August 0.00 0.00 0.00 0.00 2.50 26.02 1.83 25.40
September 0.00 0.00 0.00 0.00 0.50 24.65 0.50 24.65
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.17 25.47 3.50 25.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.50 26.02 1.83 25.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 30.04 0.00 30.04
May 0.00 0.00 0.00 0.00 2.17 30.15 0.00 30.15
June 0.00 0.00 0.00 0.00 11.50 30.33 3.67 30.28
July 0.00 0.00 0.00 0.00 13.83 30.37 0.83 30.36
August 0.00 0.00 0.00 0.00 9.33 30.45 0.50 30.43
September 0.00 0.00 0.00 0.00 6.17 30.20 0.00 30.20
October 0.00 0.00 0.00 0.00 1.00 30.07 0.00 30.07
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   44.17 30.34 5.00 30.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.83 30.45 3.67 30.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 190.33 23.57 16.17 23.59 4.00 23.53
February 262.83 23.60 0.50 23.61 0.00 23.61
March 205.50 23.73 49.17 24.01 3.00 24.01
April 9.33 23.89 200.67 25.50 0.00 25.50
May 0.17 27.75 226.33 25.88 0.17 25.88
June 59.17 28.02 363.50 25.92 59.17 26.18
July 115.17 27.68 340.00 26.22 115.17 26.51
August 111.50 27.53 388.83 25.98 111.50 26.27
September 75.17 27.66 340.00 25.87 75.17 26.15
October 36.50 26.13 237.17 25.51 21.67 25.67
November 80.67 24.01 154.33 24.57 7.67 24.58
December 269.50 23.69 9.17 23.74 0.00 23.74
             
Annual Sum or Average 1415.83 24.77 2325.83 25.24 397.50 25.46
Minimum of Months 0.17 23.57 0.50 23.59 0.00 23.53
Maximum of Months 269.50 28.02 388.83 26.22 115.17 26.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 128.33 23.20 80.50 23.79 5.50 23.70
February 250.33 22.95 12.67 22.81 12.50 22.68
March 300.83 23.15 40.00 23.12 20.67 22.96
April 86.50 23.79 105.33 25.18 0.00 25.18
May 48.67 23.97 130.83 25.94 0.00 25.94
June 71.17 28.46 268.50 26.68 71.17 26.99
July 120.00 28.04 335.33 26.28 120.00 26.65
August 128.00 28.01 381.17 26.23 128.00 26.59
September 114.00 28.23 340.00 26.38 114.00 26.75
October 78.00 26.22 245.67 25.86 43.83 26.16
November 64.67 23.74 178.33 24.55 11.83 24.58
December 210.17 23.23 48.67 23.30 13.67 23.15
             
Annual Sum or Average 1600.67 24.72 2167.00 25.23 541.17 25.50
Minimum of Months 48.67 22.95 12.67 22.81 0.00 22.68
Maximum of Months 300.83 28.46 381.17 26.68 128.00 26.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 272.00 23.37 11.33 23.25 11.33 23.14
February 266.00 22.88 16.33 22.72 16.33 22.59
March 270.67 23.20 25.17 23.12 15.83 22.99
April 21.17 24.08 130.33 25.82 0.00 25.82
May 3.83 27.00 194.17 26.26 2.67 26.29
June 109.00 28.49 295.67 26.74 109.00 27.11
July 115.17 28.35 280.00 26.71 115.17 27.08
August 129.83 28.16 322.00 26.59 129.83 26.94
September 106.33 28.12 279.33 26.50 106.33 26.85
October 72.00 25.53 161.50 25.71 27.83 25.96
November 131.50 23.81 63.00 24.17 3.00 24.17
December 270.17 23.07 22.17 22.88 22.17 22.72
             
Annual Sum or Average 1767.67 24.64 1801.00 25.21 559.50 25.49
Minimum of Months 3.83 22.88 11.33 22.72 0.00 22.59
Maximum of Months 272.00 28.49 322.00 26.74 129.83 27.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 356.33 23.07 28.50 22.89 28.50 22.73
February 323.00 22.43 25.00 22.26 25.00 22.12
March 360.50 22.97 34.17 22.81 30.00 22.64
April 100.83 23.94 95.67 25.03 0.00 25.03
May 24.50 23.90 147.67 26.20 0.00 26.20
June 105.50 28.47 303.50 26.64 105.50 27.01
July 112.67 28.24 336.83 26.27 112.67 26.66
August 117.83 28.01 383.33 26.10 117.83 26.46
September 84.67 27.97 338.00 25.94 84.67 26.28
October 129.17 24.42 154.83 25.00 18.17 25.18
November 239.67 23.66 49.67 23.80 7.33 23.78
December 340.00 22.73 52.00 22.46 52.00 22.25
             
Annual Sum or Average 2294.67 24.04 1949.17 24.63 581.67 24.83
Minimum of Months 24.50 22.43 25.00 22.26 0.00 22.12
Maximum of Months 360.50 28.47 383.33 26.64 117.83 27.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 268.67 23.39 29.33 23.39 13.17 23.27
February 300.67 22.88 20.67 22.75 18.17 22.61
March 304.17 23.22 52.67 23.39 16.00 23.27
April 104.50 26.24 155.33 26.61 50.00 26.95
May 86.17 28.37 190.33 27.47 77.83 27.77
June 118.83 29.26 325.83 27.01 118.83 27.48
July 120.67 28.72 336.50 26.57 120.67 27.02
August 133.50 28.58 385.83 26.46 133.50 26.89
September 113.00 28.60 340.00 26.42 113.00 26.85
October 108.83 25.72 209.17 25.83 42.67 26.16
November 145.67 23.85 115.67 24.41 1.67 24.43
December 294.67 23.12 32.50 22.96 26.67 22.79
             
Annual Sum or Average 2099.33 25.00 2193.83 25.41 732.17 25.78
Minimum of Months 86.17 22.88 20.67 22.75 1.67 22.61
Maximum of Months 304.17 29.26 385.83 27.47 133.50 27.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.111193E+10 0.249750E+09 183.01 0.108571E+10 26213588.01 0.00 0.57 31-JAN-17:00 0.00 01-JAN-00:10 3058.55 31-JAN-16:55 3058.55 31-JAN-16:55 427.82 09-JAN-11:00 748.47 31-JAN-16:55 0.00
February 0.588181E+09 0.130788E+09 143.13 0.516168E+09 72012422.15 0.00 0.37 01-FEB-16:00 0.00 01-FEB-00:10 1952.95 01-FEB-15:57 1952.95 01-FEB-15:57 412.38 17-FEB-12:00 425.53 01-FEB-15:57 0.00
March 0.119128E+10 0.268630E+09 201.63 0.112672E+10 64559963.13 0.00 0.98 21-MAR-07:03 0.00 01-MAR-00:10 5836.15 21-MAR-07:03 5836.15 21-MAR-07:03 454.85 06-MAR-14:11 1149.44 21-MAR-07:03 0.00
April 0.256366E+10 0.600386E+09 210.49 0.256073E+10 2922393.80 0.00 1.00 03-APR-07:02 0.00 01-APR-00:10 6091.21 26-APR-06:03 6091.21 26-APR-06:03 112.31 07-APR-11:00 1235.61 25-APR-07:02 0.00
May 0.349577E+10 0.844948E+09 240.43 0.349577E+10 0.00 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 6117.73 11-MAY-06:03 6117.73 11-MAY-06:03 0.00 10-MAY-06:42 1403.58 31-MAY-16:00 0.00
June 0.444142E+10 0.113415E+10 251.07 0.442775E+10 13667968.46 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 6280.68 26-JUN-05:02 6280.68 26-JUN-05:02 743.19 30-JUN-08:00 1619.45 28-JUN-15:50 0.00
July 0.452293E+10 0.108901E+10 237.45 0.405404E+10 0.468896E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:05 6834.51 14-JUL-06:02 6300.39 03-JUL-05:02 2571.02 14-JUL-06:15 1599.77 19-JUL-13:30 0.00
August 0.504862E+10 0.121455E+10 270.22 0.449368E+10 0.554938E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 6673.57 10-AUG-06:02 6307.39 28-AUG-05:02 2143.82 04-AUG-07:10 1572.59 25-AUG-15:37 0.00
September 0.420010E+10 0.977425E+09 229.06 0.373894E+10 0.461162E+09 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 6783.94 05-SEP-05:02 6273.98 18-SEP-05:02 2098.62 05-SEP-06:10 1550.27 08-SEP-15:00 0.00
October 0.292078E+10 0.662094E+09 221.44 0.278841E+10 0.132361E+09 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 6611.01 03-OCT-06:01 6327.83 02-OCT-05:02 1736.89 03-OCT-06:15 1489.24 02-OCT-13:57 0.00
November 0.181264E+10 0.398257E+09 207.80 0.166641E+10 0.146228E+09 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 6487.03 14-NOV-08:62 5980.16 20-NOV-08:62 2331.65 14-NOV-08:62 1262.26 14-NOV-08:62 0.00
December 0.769065E+09 0.171063E+09 164.78 0.761641E+09 7424127.99 0.00 0.48 26-DEC-16:43 0.00 01-DEC-00:10 2620.08 26-DEC-16:50 2620.08 26-DEC-16:50 251.54 13-DEC-11:45 579.21 26-DEC-16:50 0.00
                                       
Annual Sum or Average 0.326664E+11 0.774104E+10 2560.51 0.307160E+11 0.195039E+10 0.00                         0.00
Minimum of Months 0.588181E+09 0.130788E+09 143.13 0.516168E+09 0.00 0.00 0.37   0.00   1952.95   1952.95   0.00   425.53   0.00
Maximum of Months 0.504862E+10 0.121455E+10 270.22 0.449368E+10 0.554938E+09 0.00 1.00   0.00   6834.51   6327.83   2571.02   1619.45   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.207168E+10 0.448961E+09 187.51 0.206635E+10 5325899.94 0.00 0.89 30-JAN-14:40 0.00 01-JAN-00:10 5773.79 30-JAN-14:40 5773.79 30-JAN-14:40 448.27 09-JAN-11:02 1252.58 31-JAN-16:00 0.00
February 0.665733E+09 0.145801E+09 117.66 0.649782E+09 15951287.41 0.00 0.55 01-FEB-15:30 0.00 01-FEB-00:10 3462.79 01-FEB-15:30 3462.79 01-FEB-15:30 258.53 16-FEB-11:55 730.77 01-FEB-15:30 0.00
March 0.943530E+09 0.216125E+09 158.30 0.939928E+09 3602141.23 0.00 0.60 16-MAR-15:20 0.00 01-MAR-00:10 3728.07 20-MAR-14:30 3728.07 20-MAR-14:30 114.64 17-MAR-11:01 900.75 16-MAR-15:20 0.00
April 0.230007E+10 0.560342E+09 197.72 0.230007E+10 -0.0 0.00 1.00 25-APR-07:02 0.00 01-APR-00:10 6883.41 26-APR-07:02 6883.41 26-APR-07:02 0.00 18-APR-07:55 1602.98 14-APR-16:05 0.00
May 0.293284E+10 0.746005E+09 222.57 0.293284E+10 -0.0 0.00 1.00 02-MAY-07:02 0.00 01-MAY-00:10 6905.04 11-MAY-07:02 6905.04 11-MAY-07:02 0.00 15-MAY-11:00 1672.10 31-MAY-16:05 0.00
June 0.437906E+10 0.116823E+10 258.33 0.437217E+10 6887757.21 0.00 1.00 01-JUN-07:02 0.00 01-JUN-00:10 7157.36 19-JUN-05:02 7157.36 19-JUN-05:02 647.72 30-JUN-07:14 1846.38 28-JUN-16:10 0.00
July 0.474110E+10 0.118299E+10 262.95 0.437553E+10 0.365576E+09 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:05 7895.87 14-JUL-06:02 7368.18 31-JUL-05:02 2860.06 14-JUL-06:03 1827.97 19-JUL-13:00 0.00
August 0.538331E+10 0.134166E+10 300.13 0.496935E+10 0.413966E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 7703.41 10-AUG-06:02 7406.47 14-AUG-05:02 2660.20 04-AUG-07:15 1818.28 27-AUG-16:42 0.00
September 0.483725E+10 0.115450E+10 271.06 0.448030E+10 0.356943E+09 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 7672.71 05-SEP-05:02 7424.50 25-SEP-05:02 2357.95 05-SEP-07:04 1780.96 08-SEP-15:00 0.00
October 0.369487E+10 0.840794E+09 241.98 0.362203E+10 72840329.38 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7603.40 03-OCT-06:01 7351.55 02-OCT-05:02 1960.98 03-OCT-07:08 1716.61 02-OCT-14:00 0.00
November 0.267635E+10 0.574832E+09 200.76 0.259317E+10 83173464.81 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 7140.08 01-NOV-07:02 6864.76 01-NOV-16:05 1231.13 14-NOV-13:05 1546.08 01-NOV-14:55 0.00
December 0.148598E+10 0.317896E+09 161.37 0.148476E+10 1214933.21 0.00 0.89 26-DEC-13:55 0.00 01-DEC-00:10 5902.94 26-DEC-13:55 5902.94 26-DEC-13:55 161.81 13-DEC-11:55 1216.91 26-DEC-14:00 0.00
                                       
Annual Sum or Average 0.361118E+11 0.869814E+10 2580.36 0.347863E+11 0.132548E+10 0.00                         0.00
Minimum of Months 0.665733E+09 0.145801E+09 117.66 0.649782E+09 -0.0 0.00 0.55   0.00   3462.79   3462.79   0.00   730.77   0.00
Maximum of Months 0.538331E+10 0.134166E+10 300.13 0.496935E+10 0.413966E+09 0.00 1.00   0.00   7895.87   7424.50   2860.06   1846.38   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.534382E+09 0.122668E+09 168.10 0.532387E+09 1994525.64 0.00 0.40 31-JAN-16:07 0.00 01-JAN-00:10 1656.73 31-JAN-16:07 1656.73 31-JAN-16:07 138.48 09-JAN-10:00 419.27 31-JAN-16:07 0.00
February 0.188548E+09 42635946.56 112.59 0.181901E+09 6646184.59 0.00 0.22 23-FEB-11:02 0.00 01-FEB-00:10 938.93 23-FEB-11:02 887.62 23-FEB-11:04 118.10 16-FEB-11:35 209.96 23-FEB-11:02 0.00
March 0.511742E+09 0.118592E+09 172.51 0.509996E+09 1745387.53 0.00 0.40 20-MAR-14:40 0.00 01-MAR-00:10 1720.07 20-MAR-14:40 1720.07 20-MAR-14:40 53.43 02-MAR-10:00 423.34 20-MAR-15:55 0.00
April 0.171096E+10 0.410092E+09 208.86 0.171096E+10 0.00 0.00 1.00 03-APR-07:02 0.00 01-APR-00:10 4911.55 17-APR-07:02 4911.55 17-APR-07:02 0.00 12-APR-07:48 997.78 25-APR-07:02 0.00
May 0.232405E+10 0.577245E+09 241.71 0.232405E+10 0.00 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 4910.58 30-MAY-06:02 4910.58 30-MAY-06:02 0.00 15-MAY-16:15 1001.68 31-MAY-07:01 0.00
June 0.334936E+10 0.883240E+09 309.91 0.334612E+10 3240349.64 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 5085.81 19-JUN-05:02 5085.81 19-JUN-05:02 319.80 30-JUN-08:00 1276.26 17-JUN-13:41 0.00
July 0.342786E+10 0.860521E+09 319.22 0.324652E+10 0.181336E+09 0.00 1.00 02-JUL-09:22 0.00 01-JUL-00:05 5519.10 14-JUL-06:02 5187.23 30-JUL-09:42 1735.00 14-JUL-06:03 1276.12 19-JUL-13:00 0.00
August 0.370673E+10 0.929930E+09 322.10 0.350357E+10 0.203159E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 5406.74 10-AUG-06:02 5222.76 21-AUG-05:02 1380.41 04-AUG-07:04 1254.57 15-AUG-16:05 0.00
September 0.295392E+10 0.714742E+09 267.19 0.278048E+10 0.173440E+09 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 5410.34 05-SEP-05:02 5236.76 25-SEP-05:02 1246.05 05-SEP-06:13 1226.61 10-SEP-15:42 0.00
October 0.192209E+10 0.448985E+09 226.75 0.188586E+10 36229290.84 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 5330.73 03-OCT-06:01 5173.61 02-OCT-05:02 1086.50 03-OCT-07:13 1161.09 02-OCT-11:02 0.00
November 0.994301E+09 0.224221E+09 204.47 0.957803E+09 36497683.05 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 5069.90 03-NOV-07:02 4968.49 01-NOV-07:02 1455.90 13-NOV-08:62 995.33 03-NOV-07:02 0.00
December 0.334860E+09 75745836.25 141.21 0.334350E+09 510017.15 0.00 0.33 22-DEC-15:10 0.00 01-DEC-00:10 1388.21 26-DEC-13:55 1388.21 26-DEC-13:55 49.96 13-DEC-11:50 327.59 22-DEC-15:10 0.00
                                       
Annual Sum or Average 0.219588E+11 0.540862E+10 2694.62 0.213140E+11 0.644799E+09 0.00                         0.00
Minimum of Months 0.188548E+09 42635946.56 112.59 0.181901E+09 0.00 0.00 0.22   0.00   938.93   887.62   0.00   209.96   0.00
Maximum of Months 0.370673E+10 0.929930E+09 322.10 0.350357E+10 0.203159E+09 0.00 1.00   0.00   5519.10   5236.76   1735.00   1276.26   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.404531E+09 94633049.49 113.41 0.402845E+09 1685542.74 0.00 0.36 31-JAN-17:00 0.00 01-JAN-00:10 2056.48 31-JAN-16:42 2056.48 31-JAN-16:42 91.41 09-JAN-13:30 523.63 31-JAN-16:50 0.00
February 67583183.83 15370301.43 40.24 62197441.38 5385742.46 0.00 0.15 22-FEB-15:55 0.00 01-FEB-00:10 896.29 16-FEB-15:55 833.84 22-FEB-16:03 134.39 17-FEB-16:30 202.61 16-FEB-15:55 0.00
March 0.435110E+09 0.102759E+09 119.22 0.431585E+09 3525039.38 0.00 0.38 16-MAR-15:53 0.00 01-MAR-00:10 2263.73 16-MAR-15:57 2263.73 16-MAR-15:57 105.49 17-MAR-10:50 567.85 16-MAR-15:57 0.00
April 0.183926E+10 0.453173E+09 199.83 0.183926E+10 -0.0 0.00 1.00 05-APR-07:02 0.00 01-APR-00:10 6884.35 17-APR-07:02 6884.35 17-APR-07:02 0.00 17-APR-10:26 1402.69 25-APR-07:02 0.00
May 0.276072E+10 0.701239E+09 236.46 0.276072E+10 -0.0 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 6853.98 11-MAY-07:02 6853.98 11-MAY-07:02 0.00 11-MAY-08:38 1408.08 31-MAY-07:01 0.00
June 0.421557E+10 0.112230E+10 266.46 0.420948E+10 6093322.19 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 7101.61 19-JUN-05:02 7101.61 19-JUN-05:02 464.92 30-JUN-08:00 1817.39 28-JUN-16:00 0.00
July 0.451027E+10 0.112982E+10 266.87 0.419954E+10 0.310733E+09 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:05 7758.25 14-JUL-06:02 7270.47 31-JUL-05:02 2547.57 14-JUL-06:03 1803.98 19-JUL-14:00 0.00
August 0.484058E+10 0.121626E+10 290.82 0.448872E+10 0.351856E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 7582.94 10-AUG-06:02 7337.23 14-AUG-05:02 2037.95 04-AUG-07:04 1785.48 13-AUG-18:02 0.00
September 0.394717E+10 0.955418E+09 238.54 0.365183E+10 0.295339E+09 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 7730.80 05-SEP-05:02 7181.62 25-SEP-05:02 2217.15 05-SEP-06:13 1716.24 10-SEP-15:32 0.00
October 0.219763E+10 0.523142E+09 214.07 0.213294E+10 64690843.44 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7502.77 03-OCT-06:01 7217.97 02-OCT-05:02 1669.47 03-OCT-07:06 1652.95 02-OCT-14:00 0.00
November 0.104306E+10 0.237999E+09 181.62 0.979155E+09 63901705.77 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 7093.71 03-NOV-07:02 6959.58 01-NOV-07:02 2092.68 13-NOV-08:62 1393.11 03-NOV-07:02 0.00
December 0.218327E+09 50089113.78 79.19 0.217853E+09 474873.24 0.00 0.29 22-DEC-15:25 0.00 01-DEC-00:10 1685.76 22-DEC-15:35 1685.76 22-DEC-15:35 45.37 13-DEC-13:50 403.38 22-DEC-15:05 0.00
                                       
Annual Sum or Average 0.264798E+11 0.660220E+10 2246.72 0.253761E+11 0.110368E+10 0.00                         0.00
Minimum of Months 67583183.83 15370301.43 40.24 62197441.38 -0.0 0.00 0.15   0.00   896.29   833.84   0.00   202.61   0.00
Maximum of Months 0.484058E+10 0.121626E+10 290.82 0.448872E+10 0.351856E+09 0.00 1.00   0.00   7758.25   7337.23   2547.57   1817.39   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.589047E+09 0.135518E+09 161.55 0.586419E+09 2627231.92 0.00 0.53 31-JAN-17:00 0.00 01-JAN-00:10 2653.34 31-JAN-16:55 2653.34 31-JAN-16:55 108.86 09-JAN-11:53 657.01 31-JAN-16:55 0.00
February 0.190520E+09 42863871.36 88.04 0.181282E+09 9238698.45 0.00 0.33 22-FEB-16:23 0.00 01-FEB-00:10 1742.82 22-FEB-16:23 1677.34 22-FEB-16:33 117.11 13-FEB-16:23 382.73 22-FEB-16:23 0.00
March 0.473389E+09 0.110821E+09 153.90 0.469299E+09 4089587.61 0.00 0.45 16-MAR-15:53 0.00 01-MAR-00:10 2298.63 16-MAR-15:57 2298.63 16-MAR-15:57 132.28 06-MAR-16:34 570.14 16-MAR-15:57 0.00
April 0.155951E+10 0.385454E+09 217.44 0.155951E+10 -0.0 0.00 1.00 04-APR-07:02 0.00 01-APR-00:10 5808.52 17-APR-07:02 5808.52 17-APR-07:02 0.00 17-APR-10:24 1179.33 25-APR-07:02 0.00
May 0.215976E+10 0.556285E+09 266.96 0.215976E+10 -0.0 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 5806.77 30-MAY-06:02 5806.77 30-MAY-06:02 0.00 10-MAY-10:00 1258.34 07-MAY-16:53 0.00
June 0.323212E+10 0.887682E+09 344.28 0.322810E+10 4026406.63 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 5908.13 02-JUN-06:02 5908.13 02-JUN-06:02 287.54 30-JUN-08:10 1528.74 28-JUN-18:42 0.00
July 0.323813E+10 0.840748E+09 321.11 0.304011E+10 0.198011E+09 0.00 1.00 01-JUL-17:23 0.00 01-JUL-00:05 6510.76 14-JUL-06:02 6155.38 16-JUL-18:42 1900.20 14-JUL-06:02 1500.79 22-JUL-16:23 0.00
August 0.353990E+10 0.918742E+09 334.80 0.331399E+10 0.225917E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 6380.01 10-AUG-06:02 6139.96 14-AUG-05:02 1489.63 04-AUG-07:02 1522.16 26-AUG-16:23 0.00
September 0.288728E+10 0.718364E+09 279.23 0.269774E+10 0.189541E+09 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 6364.23 05-SEP-05:02 6181.47 25-SEP-05:02 1364.05 05-SEP-07:12 1453.24 10-SEP-15:32 0.00
October 0.180163E+10 0.432717E+09 236.94 0.175908E+10 42547999.67 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 6288.67 03-OCT-06:01 6113.50 02-OCT-05:02 1140.25 03-OCT-07:13 1271.88 02-OCT-05:02 0.00
November 0.107240E+10 0.242845E+09 204.76 0.102493E+10 47467083.64 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 6240.65 13-NOV-08:62 5871.59 01-NOV-07:02 1745.13 13-NOV-08:62 1214.63 13-NOV-08:62 0.00
December 0.383174E+09 86454020.97 123.82 0.382511E+09 663115.52 0.00 0.50 22-DEC-16:23 0.00 01-DEC-00:10 2586.74 26-DEC-16:30 2586.74 26-DEC-16:30 47.45 13-DEC-14:20 581.21 22-DEC-16:27 0.00
                                       
Annual Sum or Average 0.211269E+11 0.535849E+10 2732.84 0.204027E+11 0.724129E+09 0.00                         0.00
Minimum of Months 0.190520E+09 42863871.36 88.04 0.181282E+09 -0.0 0.00 0.33   0.00   1742.82   1677.34   0.00   382.73   0.00
Maximum of Months 0.353990E+10 0.918742E+09 344.28 0.331399E+10 0.225917E+09 0.00 1.00   0.00   6510.76   6181.47   1900.20   1528.74   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.67 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.21 22.67 23.54 69.06 39.45 0.00 0.00 0.00
April 30.35 7.28 23.07 54.18 24.84 0.00 0.00 0.00
May 22.19 0.00 22.19 43.18 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.44 1.70 19.74 51.38 10.34 0.00 0.00 0.00
September 36.81 13.52 23.28 73.73 15.56 0.00 0.00 0.00
October 70.66 48.89 21.78 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.60 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.86 29.62 21.24 85.12 30.13 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.18 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.66 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.20 22.66 23.54 69.04 39.46 0.00 0.00 0.00
April 30.20 7.21 22.99 53.80 24.84 0.00 0.00 0.00
May 22.19 0.00 22.19 43.17 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.41 1.68 19.73 51.32 10.34 0.00 0.00 0.00
September 36.71 13.49 23.22 73.52 15.56 0.00 0.00 0.00
October 70.66 48.89 21.77 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.59 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.06 30.13 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.17 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.66 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.20 22.66 23.54 69.04 39.46 0.00 0.00 0.00
April 30.20 7.21 22.99 53.80 24.84 0.00 0.00 0.00
May 22.19 0.00 22.19 43.17 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.41 1.68 19.73 51.32 10.34 0.00 0.00 0.00
September 36.71 13.49 23.22 73.50 15.56 0.00 0.00 0.00
October 70.66 48.89 21.77 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.59 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.06 30.13 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.17 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.66 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.20 22.66 23.54 69.04 39.46 0.00 0.00 0.00
April 30.20 7.21 22.99 53.80 24.84 0.00 0.00 0.00
May 22.19 0.00 22.19 43.17 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.41 1.68 19.73 51.32 10.34 0.00 0.00 0.00
September 36.71 13.49 23.22 73.50 15.56 0.00 0.00 0.00
October 70.66 48.89 21.77 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.59 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.06 30.13 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.17 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.66 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.20 22.66 23.54 69.04 39.46 0.00 0.00 0.00
April 30.20 7.21 22.99 53.80 24.84 0.00 0.00 0.00
May 22.19 0.00 22.19 43.17 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.41 1.68 19.73 51.32 10.33 0.00 0.00 0.00
September 36.72 13.49 23.23 73.50 15.54 0.00 0.00 0.00
October 70.66 48.89 21.77 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.59 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.06 30.12 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.17 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.24 49.67 0.00 0.00 0.00
February 62.57 42.65 19.92 88.73 43.31 0.00 0.00 0.00
March 46.21 22.67 23.54 69.05 39.44 0.00 0.00 0.00
April 30.33 7.28 23.05 54.13 24.81 0.00 0.00 0.00
May 22.19 0.00 22.19 43.18 17.88 0.00 0.00 0.00
June 22.10 0.00 22.10 56.88 9.08 0.00 0.00 0.00
July 21.06 0.06 21.00 50.59 8.38 0.00 0.00 0.00
August 21.44 1.70 19.74 51.39 10.33 0.00 0.00 0.00
September 36.83 13.53 23.29 73.72 15.50 0.00 0.00 0.00
October 70.66 48.89 21.78 116.24 36.00 0.00 0.00 0.00
November 84.94 65.44 19.50 128.07 47.93 0.00 0.00 0.00
December 92.57 73.61 18.96 135.60 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 50.86 29.62 21.24 85.11 30.12 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.18 8.38 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.24 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.85 111.91 27.94 214.44 69.66 0.00 0.00 0.00
February 88.12 59.75 28.37 124.69 60.48 0.00 0.00 0.00
March 73.11 37.97 35.14 111.76 55.18 0.00 0.00 0.00
April 52.48 17.82 34.66 96.32 35.21 0.00 0.00 0.00
May 33.10 1.14 31.96 63.92 25.54 0.00 0.00 0.00
June 31.38 0.00 31.38 79.06 13.10 0.00 0.00 0.00
July 30.42 0.43 29.99 71.70 11.98 0.00 0.00 0.00
August 36.06 6.54 29.52 84.35 14.77 0.00 0.00 0.00
September 59.91 24.70 35.21 118.90 22.05 0.00 0.00 0.00
October 102.35 71.10 31.25 168.02 50.71 0.00 0.00 0.00
November 119.35 91.69 27.66 179.42 67.13 0.00 0.00 0.00
December 129.97 103.13 26.85 189.85 83.47 0.00 0.00 0.00
                 
Annual Sum or Average 74.66 43.83 30.83 125.28 42.38 0.00 0.00 0.00
Minimum of Months 30.42 0.00 26.85 63.92 11.98 0.00 0.00 0.00
Maximum of Months 139.85 111.91 35.21 214.44 83.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 50.04 43.75 0.00 0.00 0.00
February 36.85 21.25 15.60 44.20 40.85 0.00 0.00 0.00
March 45.69 23.56 22.13 62.03 36.47 0.00 0.00 0.00
April 65.00 38.40 26.60 106.13 23.08 0.00 0.00 0.00
May 66.94 39.23 27.71 115.63 17.31 0.00 0.00 0.00
June 69.70 42.67 27.02 135.70 8.89 0.00 0.00 0.00
July 58.53 32.62 25.90 113.02 8.38 0.00 0.00 0.00
August 55.90 31.62 24.28 108.35 10.31 0.00 0.00 0.00
September 45.93 22.08 23.85 84.57 14.32 0.00 0.00 0.00
October 47.00 28.60 18.40 71.29 33.22 0.00 0.00 0.00
November 36.35 21.91 14.44 46.04 44.48 0.00 0.00 0.00
December 33.25 20.18 13.08 38.25 54.93 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.45 27.95 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 38.25 8.38 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 135.70 54.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 50.04 43.75 0.00 0.00 0.00
February 36.85 21.25 15.60 44.20 40.85 0.00 0.00 0.00
March 45.69 23.56 22.13 62.02 36.47 0.00 0.00 0.00
April 65.00 38.40 26.60 106.13 23.08 0.00 0.00 0.00
May 66.94 39.23 27.71 115.63 17.31 0.00 0.00 0.00
June 69.70 42.67 27.02 135.70 8.89 0.00 0.00 0.00
July 58.52 32.62 25.90 113.02 8.38 0.00 0.00 0.00
August 55.89 31.62 24.28 108.35 10.31 0.00 0.00 0.00
September 45.93 22.08 23.85 84.57 14.32 0.00 0.00 0.00
October 47.00 28.60 18.40 71.29 33.22 0.00 0.00 0.00
November 36.35 21.91 14.44 46.04 44.48 0.00 0.00 0.00
December 33.25 20.18 13.08 38.25 54.93 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.45 27.95 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 38.25 8.38 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 135.70 54.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 50.04 43.75 0.00 0.00 0.00
February 36.85 21.25 15.60 44.20 40.85 0.00 0.00 0.00
March 45.69 23.56 22.13 62.02 36.47 0.00 0.00 0.00
April 65.00 38.40 26.60 106.13 23.08 0.00 0.00 0.00
May 66.94 39.23 27.71 115.63 17.31 0.00 0.00 0.00
June 69.70 42.67 27.02 135.70 8.89 0.00 0.00 0.00
July 58.52 32.62 25.90 113.02 8.38 0.00 0.00 0.00
August 55.89 31.62 24.28 108.35 10.31 0.00 0.00 0.00
September 45.93 22.08 23.85 84.57 14.32 0.00 0.00 0.00
October 47.00 28.60 18.40 71.29 33.22 0.00 0.00 0.00
November 36.35 21.91 14.44 46.04 44.48 0.00 0.00 0.00
December 33.25 20.18 13.08 38.25 54.93 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.45 27.95 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 38.25 8.38 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 135.70 54.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.78 23.75 14.03 50.12 43.75 0.00 0.00 0.00
February 36.85 21.25 15.60 44.20 40.85 0.00 0.00 0.00
March 45.69 23.56 22.13 62.03 36.47 0.00 0.00 0.00
April 65.00 38.40 26.60 106.13 23.08 0.00 0.00 0.00
May 66.94 39.23 27.71 115.63 17.31 0.00 0.00 0.00
June 69.70 42.67 27.02 135.70 8.89 0.00 0.00 0.00
July 58.53 32.62 25.90 113.02 8.38 0.00 0.00 0.00
August 55.90 31.62 24.28 108.35 10.31 0.00 0.00 0.00
September 45.93 22.08 23.85 84.57 14.32 0.00 0.00 0.00
October 47.00 28.60 18.40 71.30 33.22 0.00 0.00 0.00
November 36.37 21.92 14.44 46.08 44.48 0.00 0.00 0.00
December 33.29 20.20 13.09 38.35 54.92 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.46 27.95 0.00 0.00 0.00
Minimum of Months 33.29 20.20 13.09 38.35 8.38 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 135.70 54.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.01 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.71 0.22 21.49 36.43 23.05 0.00 0.00 0.00
May 24.98 1.79 23.20 47.36 16.47 0.00 0.00 0.00
June 28.63 4.75 23.88 69.22 8.65 0.00 0.00 0.00
July 24.54 2.35 22.20 57.49 8.06 0.00 0.00 0.00
August 20.15 0.47 19.68 48.89 9.83 0.00 0.00 0.00
September 18.89 0.01 18.88 40.18 14.30 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.13 0.00 0.00 0.00
                 
Annual Sum or Average 18.30 0.80 17.50 31.28 28.44 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.63 4.75 23.88 69.22 57.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.00 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.66 0.20 21.46 36.41 23.14 0.00 0.00 0.00
May 24.85 1.71 23.14 47.03 16.48 0.00 0.00 0.00
June 28.53 4.69 23.84 68.96 8.65 0.00 0.00 0.00
July 24.45 2.29 22.15 57.23 8.06 0.00 0.00 0.00
August 20.06 0.43 19.64 48.68 9.83 0.00 0.00 0.00
September 18.89 0.01 18.88 40.18 14.30 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.12 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.19 28.45 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 68.96 57.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.00 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.66 0.20 21.46 36.41 23.16 0.00 0.00 0.00
May 24.85 1.71 23.14 47.03 16.48 0.00 0.00 0.00
June 28.53 4.69 23.84 68.96 8.65 0.00 0.00 0.00
July 24.45 2.29 22.15 57.23 8.06 0.00 0.00 0.00
August 20.06 0.43 19.63 48.68 9.83 0.00 0.00 0.00
September 18.88 0.00 18.88 40.18 14.31 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.12 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.19 28.45 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 68.96 57.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.00 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.66 0.20 21.46 36.41 23.16 0.00 0.00 0.00
May 24.85 1.71 23.14 47.03 16.48 0.00 0.00 0.00
June 28.53 4.69 23.84 68.96 8.65 0.00 0.00 0.00
July 24.45 2.29 22.15 57.23 8.06 0.00 0.00 0.00
August 20.06 0.43 19.63 48.68 9.83 0.00 0.00 0.00
September 18.88 0.00 18.88 40.18 14.31 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.12 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.19 28.45 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 68.96 57.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.00 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.66 0.20 21.46 36.43 23.16 0.00 0.00 0.00
May 24.85 1.71 23.14 47.03 16.48 0.00 0.00 0.00
June 28.53 4.69 23.84 68.96 8.65 0.00 0.00 0.00
July 24.45 2.29 22.15 57.23 8.06 0.00 0.00 0.00
August 20.06 0.43 19.64 48.69 9.83 0.00 0.00 0.00
September 18.89 0.00 18.88 40.19 14.31 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.12 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.19 28.45 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 68.96 57.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 11.01 44.82 0.00 0.00 0.00
February 13.17 0.00 13.17 8.29 41.73 0.00 0.00 0.00
March 17.53 0.00 17.53 19.05 37.61 0.00 0.00 0.00
April 21.72 0.22 21.50 36.54 23.16 0.00 0.00 0.00
May 25.00 1.78 23.21 47.38 16.48 0.00 0.00 0.00
June 28.63 4.75 23.88 69.20 8.65 0.00 0.00 0.00
July 24.52 2.33 22.19 57.41 8.06 0.00 0.00 0.00
August 20.13 0.46 19.67 48.84 9.83 0.00 0.00 0.00
September 18.89 0.00 18.88 40.19 14.32 0.00 0.00 0.00
October 14.80 0.00 14.80 20.45 34.28 0.00 0.00 0.00
November 12.26 0.00 12.26 9.50 45.96 0.00 0.00 0.00
December 10.93 0.00 10.93 6.25 57.13 0.00 0.00 0.00
                 
Annual Sum or Average 18.30 0.80 17.50 31.28 28.45 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 6.25 8.06 0.00 0.00 0.00
Maximum of Months 28.63 4.75 23.88 69.20 57.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.61 24.68 14.93 58.31 48.67 0.00 0.00 0.00
February 31.48 15.28 16.20 38.28 43.23 0.00 0.00 0.00
March 41.41 19.78 21.63 57.77 39.18 0.00 0.00 0.00
April 63.49 35.86 27.64 106.59 26.92 0.00 0.00 0.00
May 63.22 34.85 28.36 112.35 20.58 0.00 0.00 0.00
June 67.36 38.96 28.40 133.24 11.01 0.00 0.00 0.00
July 48.43 22.16 26.28 96.96 9.53 0.00 0.00 0.00
August 46.50 22.97 23.52 93.59 11.40 0.00 0.00 0.00
September 40.59 16.88 23.70 77.01 15.85 0.00 0.00 0.00
October 42.35 24.18 18.17 66.65 36.58 0.00 0.00 0.00
November 39.49 23.94 15.55 55.28 48.74 0.00 0.00 0.00
December 31.82 18.17 13.65 41.39 59.69 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.28 30.90 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.65 38.28 9.53 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 133.24 59.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.24 48.67 0.00 0.00 0.00
February 31.48 15.28 16.20 38.27 43.23 0.00 0.00 0.00
March 41.40 19.78 21.62 57.77 39.18 0.00 0.00 0.00
April 63.49 35.86 27.64 106.59 26.92 0.00 0.00 0.00
May 63.22 34.85 28.36 112.35 20.58 0.00 0.00 0.00
June 67.36 38.96 28.40 133.24 11.01 0.00 0.00 0.00
July 48.43 22.16 26.27 96.96 9.53 0.00 0.00 0.00
August 46.50 22.97 23.52 93.59 11.40 0.00 0.00 0.00
September 40.59 16.88 23.70 77.01 15.85 0.00 0.00 0.00
October 42.35 24.18 18.17 66.64 36.58 0.00 0.00 0.00
November 39.47 23.93 15.55 55.24 48.74 0.00 0.00 0.00
December 31.78 18.14 13.64 41.29 59.69 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.26 30.90 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 38.27 9.53 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 133.24 59.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.24 48.67 0.00 0.00 0.00
February 31.48 15.28 16.20 38.27 43.23 0.00 0.00 0.00
March 41.40 19.78 21.62 57.77 39.18 0.00 0.00 0.00
April 63.49 35.86 27.64 106.59 26.92 0.00 0.00 0.00
May 63.22 34.85 28.36 112.35 20.58 0.00 0.00 0.00
June 67.36 38.96 28.40 133.24 11.01 0.00 0.00 0.00
July 48.43 22.16 26.27 96.96 9.53 0.00 0.00 0.00
August 46.50 22.97 23.52 93.59 11.40 0.00 0.00 0.00
September 40.59 16.88 23.70 77.01 15.85 0.00 0.00 0.00
October 42.35 24.18 18.17 66.64 36.58 0.00 0.00 0.00
November 39.47 23.93 15.55 55.24 48.74 0.00 0.00 0.00
December 31.78 18.14 13.64 41.29 59.69 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.26 30.90 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 38.27 9.53 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 133.24 59.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.24 48.67 0.00 0.00 0.00
February 31.48 15.28 16.20 38.27 43.23 0.00 0.00 0.00
March 41.41 19.78 21.63 57.77 39.18 0.00 0.00 0.00
April 63.49 35.86 27.64 106.59 26.92 0.00 0.00 0.00
May 63.22 34.85 28.36 112.35 20.58 0.00 0.00 0.00
June 67.36 38.96 28.40 133.24 11.01 0.00 0.00 0.00
July 48.43 22.16 26.28 96.96 9.53 0.00 0.00 0.00
August 46.50 22.97 23.52 93.59 11.40 0.00 0.00 0.00
September 40.59 16.88 23.70 77.01 15.85 0.00 0.00 0.00
October 42.35 24.18 18.17 66.64 36.58 0.00 0.00 0.00
November 39.47 23.93 15.55 55.24 48.74 0.00 0.00 0.00
December 31.78 18.14 13.64 41.29 59.69 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.26 30.90 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 38.27 9.53 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 133.24 59.69 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266843E+09 0.213943E+09 52899745.93 0.410435E+09 0.133025E+09
February 0.151368E+09 0.103176E+09 48191558.41 0.214652E+09 0.104781E+09
March 0.123774E+09 60715423.36 63058201.87 0.184976E+09 0.105674E+09
April 78673348.58 18865663.10 59807685.48 0.140435E+09 64376240.81
May 59442718.63 949.91 59441768.72 0.115646E+09 47889167.50
June 57289639.04 0.15 57289638.89 0.147423E+09 23535941.95
July 56408208.06 171573.11 56236634.95 0.135507E+09 22446841.12
August 57423213.63 4540325.02 52882888.61 0.137606E+09 27683046.81
September 95401199.54 35049197.75 60352001.79 0.191097E+09 40331968.58
October 0.189259E+09 0.130936E+09 58323328.64 0.311344E+09 96421826.90
November 0.220167E+09 0.169633E+09 50534722.99 0.331968E+09 0.124231E+09
December 0.247928E+09 0.197151E+09 50777148.14 0.363178E+09 0.159652E+09
           
Annual Sum or Average 0.160398E+10 0.934182E+09 0.669795E+09 0.268427E+10 0.950048E+09
Minimum of Months 56408208.06 0.15 48191558.41 0.115646E+09 22446841.12
Maximum of Months 0.266843E+09 0.213943E+09 63058201.87 0.410435E+09 0.159652E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410435E+09 0.133022E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.214651E+09 0.104779E+09
March 0.123736E+09 60693913.88 63041699.24 0.184905E+09 0.105689E+09
April 78267668.14 18687090.55 59580577.59 0.139454E+09 64373677.74
May 59435708.34 0.00 59435708.34 0.115635E+09 47886595.15
June 57287929.29 0.00 57287929.29 0.147423E+09 23534246.43
July 56404281.07 170394.54 56233886.53 0.135501E+09 22445643.58
August 57357018.90 4512755.83 52844263.06 0.137445E+09 27681676.45
September 95164159.81 34966468.63 60197691.18 0.190556E+09 40330559.44
October 0.189258E+09 0.130936E+09 58321795.39 0.311343E+09 96419127.76
November 0.220166E+09 0.169633E+09 50533289.02 0.331967E+09 0.124229E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.363177E+09 0.159649E+09
           
Annual Sum or Average 0.160321E+10 0.933870E+09 0.669341E+09 0.268249E+10 0.950040E+09
Minimum of Months 56404281.07 0.00 48189778.08 0.115635E+09 22445643.58
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410435E+09 0.159649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410435E+09 0.133022E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.214651E+09 0.104779E+09
March 0.123736E+09 60693913.88 63041699.24 0.184905E+09 0.105689E+09
April 78267668.14 18687090.55 59580577.59 0.139454E+09 64373677.74
May 59435708.34 0.00 59435708.34 0.115635E+09 47886595.15
June 57287929.29 0.00 57287929.29 0.147423E+09 23534246.43
July 56404281.07 170394.54 56233886.53 0.135501E+09 22445643.58
August 57356485.00 4512244.25 52844240.74 0.137443E+09 27681676.45
September 95141249.64 34963755.66 60177493.99 0.190511E+09 40330856.91
October 0.189258E+09 0.130936E+09 58321795.39 0.311343E+09 96419127.76
November 0.220166E+09 0.169633E+09 50533289.02 0.331967E+09 0.124229E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.363177E+09 0.159649E+09
           
Annual Sum or Average 0.160319E+10 0.933866E+09 0.669321E+09 0.268244E+10 0.950040E+09
Minimum of Months 56404281.07 0.00 48189778.08 0.115635E+09 22445643.58
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410435E+09 0.159649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410435E+09 0.133022E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.214651E+09 0.104779E+09
March 0.123736E+09 60693913.88 63041699.24 0.184905E+09 0.105689E+09
April 78267668.14 18687090.55 59580577.59 0.139454E+09 64373677.74
May 59435708.34 0.00 59435708.34 0.115635E+09 47886595.15
June 57287929.29 0.00 57287929.29 0.147423E+09 23534246.43
July 56404281.07 170394.54 56233886.53 0.135501E+09 22445643.58
August 57356485.83 4512245.09 52844240.74 0.137443E+09 27681662.67
September 95141642.97 34963761.71 60177881.26 0.190507E+09 40326532.20
October 0.189258E+09 0.130936E+09 58321795.39 0.311343E+09 96419127.76
November 0.220166E+09 0.169633E+09 50533289.02 0.331967E+09 0.124229E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.363177E+09 0.159649E+09
           
Annual Sum or Average 0.160319E+10 0.933866E+09 0.669321E+09 0.268244E+10 0.950036E+09
Minimum of Months 56404281.07 0.00 48189778.08 0.115635E+09 22445643.58
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410435E+09 0.159649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410435E+09 0.133022E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.214651E+09 0.104779E+09
March 0.123736E+09 60693913.88 63041699.24 0.184905E+09 0.105689E+09
April 78267668.14 18687090.55 59580577.59 0.139454E+09 64373677.74
May 59435708.34 0.00 59435708.34 0.115635E+09 47886595.15
June 57287929.29 0.00 57287929.29 0.147423E+09 23534246.43
July 56404281.07 170394.54 56233886.53 0.135501E+09 22445643.58
August 57357113.83 4512873.09 52844240.74 0.137444E+09 27680712.26
September 95170505.55 34967401.67 60203103.89 0.190518E+09 40277840.95
October 0.189258E+09 0.130936E+09 58321795.39 0.311343E+09 96419127.76
November 0.220166E+09 0.169633E+09 50533289.02 0.331967E+09 0.124229E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.363177E+09 0.159649E+09
           
Annual Sum or Average 0.160322E+10 0.933871E+09 0.669347E+09 0.268245E+10 0.949986E+09
Minimum of Months 56404281.07 0.00 48189778.08 0.115635E+09 22445643.58
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410435E+09 0.159649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266843E+09 0.213943E+09 52899745.87 0.410435E+09 0.133025E+09
February 0.151368E+09 0.103176E+09 48191558.32 0.214652E+09 0.104781E+09
March 0.123777E+09 60716572.78 63060794.87 0.184945E+09 0.105635E+09
April 78623562.49 18878481.13 59745081.35 0.140302E+09 64312138.17
May 59442469.92 955.41 59441514.51 0.115646E+09 47889167.37
June 57289638.97 0.17 57289638.81 0.147423E+09 23535941.87
July 56408473.20 172071.49 56236401.71 0.135509E+09 22446841.06
August 57432644.12 4549795.93 52882848.19 0.137636E+09 27680362.00
September 95454789.18 35079705.88 60375083.30 0.191080E+09 40174018.26
October 0.189259E+09 0.130936E+09 58323328.56 0.311344E+09 96421826.76
November 0.220167E+09 0.169633E+09 50534722.92 0.331968E+09 0.124231E+09
December 0.247928E+09 0.197151E+09 50777148.08 0.363178E+09 0.159652E+09
           
Annual Sum or Average 0.160399E+10 0.934237E+09 0.669758E+09 0.268412E+10 0.949784E+09
Minimum of Months 56408473.20 0.17 48191558.32 0.115646E+09 22446841.06
Maximum of Months 0.266843E+09 0.213943E+09 63060794.87 0.410435E+09 0.159652E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.374564E+09 0.299737E+09 74826647.49 0.574365E+09 0.186579E+09
February 0.213185E+09 0.144551E+09 68634130.43 0.301647E+09 0.146312E+09
March 0.195807E+09 0.101695E+09 94111665.67 0.299335E+09 0.147792E+09
April 0.136040E+09 46192476.64 89847367.99 0.249661E+09 91260331.28
May 88652969.90 3040335.41 85612634.49 0.171211E+09 68401796.73
June 81336276.40 0.00 81336276.40 0.204922E+09 33961644.88
July 81470509.01 1151108.36 80319400.65 0.192029E+09 32074630.96
August 96586500.72 17512319.26 79074181.45 0.225920E+09 39551851.73
September 0.155285E+09 64030085.40 91254515.35 0.308180E+09 57162823.83
October 0.274137E+09 0.190426E+09 83711190.32 0.450035E+09 0.135834E+09
November 0.309357E+09 0.237657E+09 71699602.02 0.465050E+09 0.174004E+09
December 0.348122E+09 0.276211E+09 71911026.45 0.508489E+09 0.223578E+09
           
Annual Sum or Average 0.235454E+10 0.138220E+10 0.972339E+09 0.395084E+10 0.133651E+10
Minimum of Months 81336276.40 0.00 68634130.43 0.171211E+09 32074630.96
Maximum of Months 0.374564E+09 0.299737E+09 94111665.67 0.574365E+09 0.223578E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101108E+09 63546576.21 37561711.42 0.134025E+09 0.117183E+09
February 89156448.25 51412224.00 37744224.25 0.106934E+09 98836150.20
March 0.122373E+09 63100302.53 59272519.05 0.166129E+09 97692662.17
April 0.168483E+09 99526921.43 68956237.73 0.275082E+09 59816199.10
May 0.179285E+09 0.105070E+09 74215161.27 0.309713E+09 46355972.78
June 0.180654E+09 0.110610E+09 70044833.64 0.351724E+09 23048073.41
July 0.156754E+09 87380273.63 69373964.48 0.302719E+09 22445999.64
August 0.149710E+09 84678567.99 65031464.34 0.290211E+09 27619317.28
September 0.119057E+09 57233808.13 61823508.39 0.219206E+09 37128816.49
October 0.125883E+09 76611304.13 49271407.80 0.190945E+09 88981167.48
November 94227627.53 56799513.76 37428113.76 0.119342E+09 0.115302E+09
December 89065440.69 54042000.93 35023439.76 0.102458E+09 0.147135E+09
           
Annual Sum or Average 0.157576E+10 0.910011E+09 0.665747E+09 0.256849E+10 0.881545E+09
Minimum of Months 89065440.69 51412224.00 35023439.76 0.102458E+09 22445999.64
Maximum of Months 0.180654E+09 0.110610E+09 74215161.27 0.351724E+09 0.147135E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101107E+09 63546576.21 37560574.53 0.134025E+09 0.117180E+09
February 89154668.02 51412224.00 37742444.02 0.106932E+09 98834968.08
March 0.122370E+09 63100302.53 59269968.56 0.166127E+09 97690673.03
April 0.168481E+09 99526921.43 68954415.81 0.275082E+09 59813725.16
May 0.179283E+09 0.105070E+09 74213239.31 0.309713E+09 46353451.03
June 0.180653E+09 0.110610E+09 70043124.14 0.351724E+09 23046400.53
July 0.156752E+09 87380273.63 69371691.73 0.302718E+09 22444829.26
August 0.149708E+09 84678567.99 65029386.82 0.290210E+09 27617878.20
September 0.119055E+09 57233808.13 61820918.36 0.219203E+09 37127275.18
October 0.125881E+09 76611304.13 49269874.63 0.190944E+09 88978512.88
November 94226193.63 56799513.76 37426679.87 0.119341E+09 0.115300E+09
December 89064211.12 54042000.93 35022210.18 0.102457E+09 0.147132E+09
           
Annual Sum or Average 0.157574E+10 0.910011E+09 0.665725E+09 0.256848E+10 0.881520E+09
Minimum of Months 89064211.12 51412224.00 35022210.18 0.102457E+09 22444829.26
Maximum of Months 0.180653E+09 0.110610E+09 74213239.31 0.351724E+09 0.147132E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101107E+09 63546576.21 37560574.53 0.134025E+09 0.117180E+09
February 89154668.02 51412224.00 37742444.02 0.106932E+09 98834968.08
March 0.122370E+09 63100302.53 59269968.56 0.166127E+09 97690673.03
April 0.168481E+09 99526921.43 68954415.81 0.275082E+09 59813725.16
May 0.179283E+09 0.105070E+09 74213239.31 0.309713E+09 46353451.03
June 0.180653E+09 0.110610E+09 70043124.14 0.351724E+09 23046400.53
July 0.156752E+09 87380273.63 69371691.73 0.302718E+09 22444829.26
August 0.149708E+09 84678567.99 65029386.82 0.290210E+09 27617878.20
September 0.119055E+09 57233808.13 61820918.36 0.219203E+09 37127275.18
October 0.125881E+09 76611304.13 49269874.63 0.190944E+09 88978512.88
November 94226193.63 56799513.76 37426679.87 0.119341E+09 0.115300E+09
December 89064211.12 54042000.93 35022210.18 0.102457E+09 0.147132E+09
           
Annual Sum or Average 0.157574E+10 0.910011E+09 0.665725E+09 0.256848E+10 0.881520E+09
Minimum of Months 89064211.12 51412224.00 35022210.18 0.102457E+09 22444829.26
Maximum of Months 0.180653E+09 0.110610E+09 74213239.31 0.351724E+09 0.147132E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101188E+09 63601417.01 37586602.01 0.134240E+09 0.117183E+09
February 89159587.76 51414048.25 37745539.50 0.106941E+09 98835325.80
March 0.122373E+09 63100302.53 59272541.23 0.166129E+09 97692662.28
April 0.168483E+09 99526921.43 68956237.82 0.275082E+09 59816199.23
May 0.179285E+09 0.105070E+09 74215161.37 0.309713E+09 46355972.91
June 0.180654E+09 0.110610E+09 70044833.73 0.351724E+09 23048073.50
July 0.156754E+09 87380273.63 69373964.60 0.302719E+09 22445999.70
August 0.149710E+09 84678567.99 65031464.45 0.290211E+09 27619317.36
September 0.119057E+09 57233808.13 61823508.53 0.219206E+09 37128816.58
October 0.125887E+09 76614337.36 49272597.49 0.190957E+09 88981167.62
November 94264143.10 56824711.01 37439432.09 0.119432E+09 0.115293E+09
December 89170266.74 54108356.13 35061910.61 0.102709E+09 0.147106E+09
           
Annual Sum or Average 0.157599E+10 0.910162E+09 0.665824E+09 0.256906E+10 0.881505E+09
Minimum of Months 89159587.76 51414048.25 35061910.61 0.102709E+09 22445999.70
Maximum of Months 0.180654E+09 0.110610E+09 74215161.37 0.351724E+09 0.147106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31501559.87 0.00 31501559.87 29475921.83 0.120053E+09
February 31868350.37 0.00 31868350.37 20054128.45 0.100949E+09
March 46953321.85 0.00 46953321.85 51016227.78 0.100724E+09
April 56265071.89 559685.93 55705385.96 94417455.21 59741525.11
May 66916377.60 4787855.16 62128522.44 0.126862E+09 44119733.57
June 74209000.56 12320373.92 61888626.63 0.179425E+09 22415258.53
July 65740615.29 6290286.77 59450328.52 0.153988E+09 21583817.76
August 53958378.82 1247610.05 52710768.78 0.130947E+09 26327631.23
September 48959657.22 13027.65 48946629.57 0.104154E+09 37078107.69
October 39637540.76 0.00 39637540.76 54778951.06 91817531.96
November 31780795.03 0.00 31780795.03 24629789.38 0.119133E+09
December 29273396.86 0.00 29273396.86 16738898.53 0.153005E+09
           
Annual Sum or Average 0.577064E+09 25218839.47 0.551845E+09 0.986488E+09 0.896948E+09
Minimum of Months 29273396.86 0.00 29273396.86 16738898.53 21583817.76
Maximum of Months 74209000.56 12320373.92 62128522.44 0.179425E+09 0.153005E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 29475772.72 0.120050E+09
February 31866570.04 0.00 31866570.04 20052603.55 0.100948E+09
March 46950771.23 0.00 46950771.23 51013683.68 0.100722E+09
April 56151870.26 523541.79 55628328.48 94387533.45 59986457.80
May 66569867.44 4591312.98 61978554.46 0.125960E+09 44130478.78
June 73957358.79 12156471.89 61800886.91 0.178754E+09 22413551.78
July 65473566.69 6141638.73 59331927.96 0.153296E+09 21582607.58
August 53740238.93 1148599.77 52591639.15 0.130393E+09 26328988.52
September 48955498.28 12975.89 48942522.38 0.104150E+09 37078408.46
October 39636007.51 0.00 39636007.51 54778314.98 91814631.82
November 31779361.06 0.00 31779361.06 24629007.49 0.119131E+09
December 29272167.22 0.00 29272167.22 16738545.78 0.153001E+09
           
Annual Sum or Average 0.575854E+09 24574541.05 0.551279E+09 0.983629E+09 0.897187E+09
Minimum of Months 29272167.22 0.00 29272167.22 16738545.78 21582607.58
Maximum of Months 73957358.79 12156471.89 61978554.46 0.178754E+09 0.153001E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 29475772.72 0.120050E+09
February 31866570.04 0.00 31866570.04 20052603.55 0.100948E+09
March 46950771.23 0.00 46950771.23 51013683.68 0.100722E+09
April 56133467.93 517640.06 55615827.87 94384804.00 60030172.46
May 66569867.44 4591312.98 61978554.46 0.125960E+09 44130478.78
June 73957358.79 12156471.89 61800886.91 0.178754E+09 22413551.78
July 65473566.69 6141638.73 59331927.96 0.153296E+09 21582607.58
August 53738527.70 1148515.99 52590011.72 0.130394E+09 26332579.21
September 48949849.07 12582.69 48937266.37 0.104151E+09 37089862.49
October 39636007.51 0.00 39636007.51 54778314.98 91814631.82
November 31779361.06 0.00 31779361.06 24629007.49 0.119131E+09
December 29272167.22 0.00 29272167.22 16738545.78 0.153001E+09
           
Annual Sum or Average 0.575828E+09 24568162.34 0.551260E+09 0.983627E+09 0.897245E+09
Minimum of Months 29272167.22 0.00 29272167.22 16738545.78 21582607.58
Maximum of Months 73957358.79 12156471.89 61978554.46 0.178754E+09 0.153001E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 29475772.72 0.120050E+09
February 31866570.04 0.00 31866570.04 20052603.55 0.100948E+09
March 46950771.23 0.00 46950771.23 51013683.68 0.100722E+09
April 56133467.93 517640.06 55615827.87 94384804.00 60030172.46
May 66569867.44 4591312.98 61978554.46 0.125960E+09 44130478.78
June 73957358.79 12156471.89 61800886.91 0.178754E+09 22413551.78
July 65473566.69 6141638.73 59331927.96 0.153296E+09 21582607.58
August 53738296.02 1148501.29 52589794.72 0.130396E+09 26335900.81
September 48947750.21 12469.82 48935280.39 0.104158E+09 37101072.61
October 39636007.51 0.00 39636007.51 54778314.98 91814631.82
November 31779361.06 0.00 31779361.06 24629007.49 0.119131E+09
December 29272167.22 0.00 29272167.22 16738545.78 0.153001E+09
           
Annual Sum or Average 0.575826E+09 24568034.77 0.551258E+09 0.983637E+09 0.897260E+09
Minimum of Months 29272167.22 0.00 29272167.22 16738545.78 21582607.58
Maximum of Months 73957358.79 12156471.89 61978554.46 0.178754E+09 0.153001E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 29475772.72 0.120050E+09
February 31866570.04 0.00 31866570.04 20052603.55 0.100948E+09
March 46950771.23 0.00 46950771.23 51013683.68 0.100722E+09
April 56154979.71 523295.75 55631683.97 94431788.44 60028265.48
May 66569867.44 4591312.98 61978554.46 0.125960E+09 44130478.78
June 73957358.79 12156471.89 61800886.91 0.178754E+09 22413551.78
July 65473566.69 6141638.73 59331927.96 0.153296E+09 21582607.58
August 53739799.30 1148571.05 52591228.25 0.130400E+09 26336640.96
September 48950782.79 12737.91 48938044.88 0.104166E+09 37103739.59
October 39636007.51 0.00 39636007.51 54778314.98 91814631.82
November 31779361.06 0.00 31779361.06 24629007.49 0.119131E+09
December 29272167.22 0.00 29272167.22 16738545.78 0.153001E+09
           
Annual Sum or Average 0.575852E+09 24574028.30 0.551278E+09 0.983696E+09 0.897261E+09
Minimum of Months 29272167.22 0.00 29272167.22 16738545.78 21582607.58
Maximum of Months 73957358.79 12156471.89 61978554.46 0.178754E+09 0.153001E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31501559.81 0.00 31501559.81 29475921.83 0.120053E+09
February 31868350.28 0.00 31868350.28 20054128.37 0.100949E+09
March 46953321.72 0.00 46953321.72 51016227.65 0.100724E+09
April 56287489.68 557361.15 55730128.53 94719880.77 60024782.62
May 66948930.02 4780076.94 62168853.07 0.126900E+09 44133006.92
June 74203775.61 12305919.54 61897856.07 0.179378E+09 22415258.44
July 65676652.37 6235417.07 59441235.31 0.153775E+09 21583634.63
August 53911080.70 1218754.64 52692326.06 0.130814E+09 26336688.82
September 48954337.80 12776.48 48941561.33 0.104171E+09 37105414.26
October 39637540.68 0.00 39637540.68 54778951.02 91817531.80
November 31780794.96 0.00 31780794.96 24629789.34 0.119133E+09
December 29273396.80 0.00 29273396.80 16738898.51 0.153005E+09
           
Annual Sum or Average 0.576997E+09 25110305.81 0.551887E+09 0.986451E+09 0.897280E+09
Minimum of Months 29273396.80 0.00 29273396.80 16738898.51 21583634.63
Maximum of Months 74203775.61 12305919.54 62168853.07 0.179378E+09 0.153005E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106098E+09 66107369.58 39990520.20 0.156189E+09 0.130348E+09
February 76164350.99 36975538.40 39188812.60 92596916.61 0.104579E+09
March 0.110899E+09 52976548.59 57922865.93 0.154743E+09 0.104946E+09
April 0.164575E+09 92940014.96 71635344.90 0.276281E+09 69772945.99
May 0.169319E+09 93350428.99 75968144.53 0.300930E+09 55116556.34
June 0.174606E+09 0.100989E+09 73617114.44 0.345346E+09 28539407.37
July 0.129728E+09 59351700.54 70376487.55 0.259693E+09 25531769.02
August 0.124543E+09 61535883.24 63006732.73 0.250679E+09 30526618.02
September 0.105206E+09 43765069.40 61440446.58 0.199615E+09 41091346.00
October 0.113435E+09 64756536.42 48677982.55 0.178513E+09 97967542.23
November 0.102353E+09 62042530.21 40310121.32 0.143288E+09 0.126329E+09
December 85219470.46 48660570.40 36558900.06 0.110870E+09 0.159865E+09
           
Annual Sum or Average 0.146214E+10 0.783451E+09 0.678693E+09 0.246874E+10 0.974613E+09
Minimum of Months 76164350.99 36975538.40 36558900.06 92596916.61 25531769.02
Maximum of Months 0.174606E+09 0.100989E+09 75968144.53 0.345346E+09 0.159865E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106021E+09 66056046.72 39965012.30 0.155985E+09 0.130345E+09
February 76159040.40 36973544.43 39185495.97 92587121.51 0.104579E+09
March 0.110897E+09 52976548.59 57920288.66 0.154740E+09 0.104944E+09
April 0.164574E+09 92940014.96 71633522.99 0.276280E+09 69770276.06
May 0.169317E+09 93350428.99 75966222.57 0.300930E+09 55113759.84
June 0.174604E+09 0.100989E+09 73615404.93 0.345347E+09 28537461.99
July 0.129726E+09 59351700.54 70374214.80 0.259692E+09 25530427.40
August 0.124541E+09 61535883.24 63004655.21 0.250678E+09 30524957.19
September 0.105203E+09 43765069.40 61437856.55 0.199612E+09 41089608.50
October 0.113428E+09 64753215.96 48674917.00 0.178499E+09 97964685.05
November 0.102310E+09 62016171.25 40293511.99 0.143182E+09 0.126330E+09
December 85114323.13 48593588.74 36520734.39 0.110592E+09 0.159862E+09
           
Annual Sum or Average 0.146189E+10 0.783301E+09 0.678592E+09 0.246812E+10 0.974590E+09
Minimum of Months 76159040.40 36973544.43 36520734.39 92587121.51 25530427.40
Maximum of Months 0.174604E+09 0.100989E+09 75966222.57 0.345347E+09 0.159862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106021E+09 66056046.72 39965012.30 0.155985E+09 0.130345E+09
February 76159040.40 36973544.43 39185495.97 92587121.51 0.104579E+09
March 0.110897E+09 52976548.59 57920288.66 0.154740E+09 0.104944E+09
April 0.164574E+09 92940014.96 71633522.99 0.276280E+09 69770276.06
May 0.169317E+09 93350428.99 75966222.57 0.300930E+09 55113759.84
June 0.174604E+09 0.100989E+09 73615404.93 0.345347E+09 28537461.99
July 0.129726E+09 59351700.54 70374214.80 0.259692E+09 25530427.40
August 0.124541E+09 61535883.24 63004655.21 0.250678E+09 30524957.19
September 0.105203E+09 43765069.40 61437856.55 0.199612E+09 41089608.50
October 0.113428E+09 64753215.96 48674917.00 0.178499E+09 97964685.05
November 0.102310E+09 62016171.25 40293511.99 0.143182E+09 0.126330E+09
December 85114323.13 48593588.74 36520734.39 0.110592E+09 0.159862E+09
           
Annual Sum or Average 0.146189E+10 0.783301E+09 0.678592E+09 0.246812E+10 0.974590E+09
Minimum of Months 76159040.40 36973544.43 36520734.39 92587121.51 25530427.40
Maximum of Months 0.174604E+09 0.100989E+09 75966222.57 0.345347E+09 0.159862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106022E+09 66056046.72 39966149.25 0.155985E+09 0.130348E+09
February 76160820.73 36973544.43 39187276.29 92588741.06 0.104580E+09
March 0.110899E+09 52976548.59 57922839.28 0.154743E+09 0.104946E+09
April 0.164575E+09 92940014.96 71635344.99 0.276281E+09 69772946.13
May 0.169319E+09 93350428.99 75968144.63 0.300930E+09 55116556.49
June 0.174606E+09 0.100989E+09 73617114.53 0.345346E+09 28539407.47
July 0.129728E+09 59351700.54 70376487.67 0.259693E+09 25531769.09
August 0.124543E+09 61535883.24 63006732.83 0.250679E+09 30526618.11
September 0.105206E+09 43765069.40 61440446.72 0.199615E+09 41091346.10
October 0.113430E+09 64753215.96 48676450.25 0.178500E+09 97967542.38
November 0.102311E+09 62016171.25 40294945.97 0.143183E+09 0.126332E+09
December 85115552.77 48593588.74 36521964.03 0.110592E+09 0.159865E+09
           
Annual Sum or Average 0.146192E+10 0.783301E+09 0.678614E+09 0.246814E+10 0.974617E+09
Minimum of Months 76160820.73 36973544.43 36521964.03 92588741.06 25531769.09
Maximum of Months 0.174606E+09 0.100989E+09 75968144.63 0.345346E+09 0.159865E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1133.88 367.65 737.61 591.17 146.44 0.00 0.00
February 657.05 320.34 463.54 315.65 147.89 0.00 0.00
March 526.01 291.91 350.32 173.95 176.37 0.00 0.00
April 419.83 184.19 233.95 61.22 172.73 0.00 0.00
May 322.97 132.81 166.25 1.14 165.11 0.00 0.00
June 420.31 67.58 163.99 0.00 163.99 0.00 0.00
July 375.24 62.26 156.77 0.81 155.96 0.00 0.00
August 392.37 76.78 164.60 16.67 147.93 0.00 0.00
September 560.34 115.32 280.39 105.72 174.67 0.00 0.00
October 865.48 266.71 526.32 364.41 161.90 0.00 0.00
November 947.86 354.70 628.99 484.36 144.64 0.00 0.00
December 1003.42 441.11 685.37 544.77 140.59 0.00 0.00
               
Annual Sum or Average 635.75 223.12 379.73 221.53 158.21 0.00 0.00
Minimum of Months 322.97 62.26 156.77 0.00 140.59 0.00 0.00
Maximum of Months 1133.88 441.11 737.61 591.17 176.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 200.24 175.00 151.03 94.92 56.10 0.00 0.00
February 176.81 163.42 147.41 85.01 62.41 0.00 0.00
March 248.10 145.90 182.75 94.24 88.52 0.00 0.00
April 424.51 92.31 260.00 153.59 106.41 0.00 0.00
May 462.53 69.23 267.75 156.91 110.83 0.00 0.00
June 542.78 35.57 278.79 170.69 108.09 0.00 0.00
July 452.09 33.52 234.10 130.50 103.60 0.00 0.00
August 433.41 41.25 223.58 126.46 97.12 0.00 0.00
September 338.28 57.30 183.73 88.32 95.40 0.00 0.00
October 285.17 132.89 188.00 114.41 73.58 0.00 0.00
November 184.20 177.93 145.43 87.66 57.76 0.00 0.00
December 153.11 219.72 133.05 80.73 52.32 0.00 0.00
               
Annual Sum or Average 325.80 111.81 199.87 115.43 84.44 0.00 0.00
Minimum of Months 153.11 33.52 133.05 80.73 52.32 0.00 0.00
Maximum of Months 542.78 219.72 278.79 170.69 110.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 66.03 268.93 70.57 0.00 70.57 0.00 0.00
February 49.73 250.37 79.04 0.00 79.04 0.00 0.00
March 114.28 225.63 105.18 0.00 105.18 0.00 0.00
April 218.64 138.82 130.06 1.23 128.83 0.00 0.00
May 282.85 98.85 149.40 10.43 138.97 0.00 0.00
June 414.28 51.88 171.39 28.26 143.13 0.00 0.00
July 343.84 48.35 146.85 13.85 133.00 0.00 0.00
August 292.47 58.99 120.53 2.64 117.89 0.00 0.00
September 241.11 85.86 113.32 0.03 113.29 0.00 0.00
October 122.71 205.68 88.79 0.00 88.79 0.00 0.00
November 57.01 275.77 73.56 0.00 73.56 0.00 0.00
December 37.50 342.75 65.57 0.00 65.57 0.00 0.00
               
Annual Sum or Average 187.33 170.70 109.63 4.71 104.92 0.00 0.00
Minimum of Months 37.50 48.35 65.57 0.00 65.57 0.00 0.00
Maximum of Months 414.28 342.75 171.39 28.26 143.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 233.03 194.66 158.36 98.67 59.69 0.00 0.00
February 153.09 172.92 125.93 61.13 64.79 0.00 0.00
March 231.10 156.73 165.62 79.12 86.50 0.00 0.00
April 426.36 107.67 253.97 143.43 110.55 0.00 0.00
May 449.42 82.31 252.86 139.41 113.45 0.00 0.00
June 532.94 44.04 269.45 155.85 113.61 0.00 0.00
July 387.83 38.13 193.74 88.64 105.10 0.00 0.00
August 374.37 45.59 185.99 91.90 94.09 0.00 0.00
September 308.05 63.41 162.35 67.54 94.81 0.00 0.00
October 266.58 146.31 169.40 96.71 72.69 0.00 0.00
November 221.00 194.95 157.90 95.71 62.19 0.00 0.00
December 165.26 238.74 127.15 72.60 54.56 0.00 0.00
               
Annual Sum or Average 313.07 123.62 185.43 99.36 86.08 0.00 0.00
Minimum of Months 153.09 38.13 125.93 61.13 54.56 0.00 0.00
Maximum of Months 532.94 238.74 269.45 155.85 113.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.303698E+10 0.984719E+09 0.197562E+10 0.158340E+10 0.392221E+09 0.00 0.00
February 0.158954E+10 0.774973E+09 0.112139E+10 0.763609E+09 0.357776E+09 0.00 0.00
March 0.140887E+10 0.781846E+09 0.938300E+09 0.465903E+09 0.472397E+09 0.00 0.00
April 0.108819E+10 0.477422E+09 0.606407E+09 0.158685E+09 0.447722E+09 0.00 0.00
May 0.865036E+09 0.355721E+09 0.445281E+09 3042240.72 0.442239E+09 0.00 0.00
June 0.108945E+10 0.175160E+09 0.425067E+09 0.32 0.425067E+09 0.00 0.00
July 0.100504E+10 0.166747E+09 0.419904E+09 2176331.11 0.417728E+09 0.00 0.00
August 0.105093E+10 0.205636E+09 0.440869E+09 44652558.49 0.396217E+09 0.00 0.00
September 0.145241E+10 0.298900E+09 0.726758E+09 0.274020E+09 0.452738E+09 0.00 0.00
October 0.231810E+10 0.714353E+09 0.140969E+10 0.976042E+09 0.433645E+09 0.00 0.00
November 0.245685E+10 0.919380E+09 0.163035E+10 0.125545E+10 0.374902E+09 0.00 0.00
December 0.268755E+10 0.118148E+10 0.183569E+10 0.145912E+10 0.376569E+09 0.00 0.00
               
Annual Sum or Average 0.200489E+11 0.703634E+10 0.119753E+11 0.698610E+10 0.498922E+10 0.00 0.00
Minimum of Months 0.865036E+09 0.166747E+09 0.419904E+09 0.32 0.357776E+09 0.00 0.00
Maximum of Months 0.303698E+10 0.118148E+10 0.197562E+10 0.158340E+10 0.472397E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.536316E+09 0.468725E+09 0.404511E+09 0.254241E+09 0.150269E+09 0.00 0.00
February 0.427739E+09 0.395341E+09 0.356625E+09 0.205651E+09 0.150975E+09 0.00 0.00
March 0.664512E+09 0.390767E+09 0.489486E+09 0.252401E+09 0.237085E+09 0.00 0.00
April 0.110033E+10 0.239260E+09 0.673929E+09 0.398108E+09 0.275821E+09 0.00 0.00
May 0.123885E+10 0.185419E+09 0.717137E+09 0.420281E+09 0.296857E+09 0.00 0.00
June 0.140690E+10 92188947.97 0.722614E+09 0.442438E+09 0.280176E+09 0.00 0.00
July 0.121087E+10 89781657.86 0.627012E+09 0.349521E+09 0.277491E+09 0.00 0.00
August 0.116084E+10 0.110474E+09 0.598836E+09 0.338714E+09 0.260122E+09 0.00 0.00
September 0.876818E+09 0.148512E+09 0.476224E+09 0.228935E+09 0.247289E+09 0.00 0.00
October 0.763791E+09 0.355919E+09 0.503532E+09 0.306448E+09 0.197084E+09 0.00 0.00
November 0.477456E+09 0.461194E+09 0.376944E+09 0.227223E+09 0.149721E+09 0.00 0.00
December 0.410077E+09 0.588502E+09 0.356364E+09 0.216234E+09 0.140130E+09 0.00 0.00
               
Annual Sum or Average 0.102745E+11 0.352609E+10 0.630322E+10 0.364020E+10 0.266302E+10 0.00 0.00
Minimum of Months 0.410077E+09 89781657.86 0.356364E+09 0.205651E+09 0.140130E+09 0.00 0.00
Maximum of Months 0.140690E+10 0.588502E+09 0.722614E+09 0.442438E+09 0.296857E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.176855E+09 0.720306E+09 0.189005E+09 0.00 0.189005E+09 0.00 0.00
February 0.120319E+09 0.605689E+09 0.191203E+09 0.00 0.191203E+09 0.00 0.00
March 0.306087E+09 0.604334E+09 0.281710E+09 0.00 0.281710E+09 0.00 0.00
April 0.566714E+09 0.359829E+09 0.337126E+09 3199164.74 0.333927E+09 0.00 0.00
May 0.757593E+09 0.264765E+09 0.400145E+09 27933184.01 0.372212E+09 0.00 0.00
June 0.107382E+10 0.134485E+09 0.444242E+09 73252181.00 0.370990E+09 0.00 0.00
July 0.920945E+09 0.129498E+09 0.393312E+09 37092258.76 0.356219E+09 0.00 0.00
August 0.783341E+09 0.157995E+09 0.322826E+09 7060552.78 0.315766E+09 0.00 0.00
September 0.624947E+09 0.222554E+09 0.293718E+09 76570.44 0.293641E+09 0.00 0.00
October 0.328671E+09 0.550894E+09 0.237819E+09 0.00 0.237819E+09 0.00 0.00
November 0.147776E+09 0.714790E+09 0.190679E+09 0.00 0.190679E+09 0.00 0.00
December 0.100432E+09 0.918015E+09 0.175635E+09 0.00 0.175635E+09 0.00 0.00
               
Annual Sum or Average 0.590750E+10 0.538315E+10 0.345742E+10 0.148614E+09 0.330881E+10 0.00 0.00
Minimum of Months 0.100432E+09 0.129498E+09 0.175635E+09 0.00 0.175635E+09 0.00 0.00
Maximum of Months 0.107382E+10 0.918015E+09 0.444242E+09 73252181.00 0.372212E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.624143E+09 0.521386E+09 0.424162E+09 0.264276E+09 0.159887E+09 0.00 0.00
February 0.370360E+09 0.418316E+09 0.304643E+09 0.147896E+09 0.156747E+09 0.00 0.00
March 0.618966E+09 0.419779E+09 0.443592E+09 0.211906E+09 0.231686E+09 0.00 0.00
April 0.110512E+10 0.279086E+09 0.658298E+09 0.371760E+09 0.286538E+09 0.00 0.00
May 0.120372E+10 0.220461E+09 0.677270E+09 0.373402E+09 0.303869E+09 0.00 0.00
June 0.138139E+10 0.114154E+09 0.698421E+09 0.403956E+09 0.294465E+09 0.00 0.00
July 0.103877E+10 0.102124E+09 0.518908E+09 0.237407E+09 0.281501E+09 0.00 0.00
August 0.100271E+10 0.122103E+09 0.498166E+09 0.246144E+09 0.252023E+09 0.00 0.00
September 0.798454E+09 0.164362E+09 0.420817E+09 0.175060E+09 0.245757E+09 0.00 0.00
October 0.714011E+09 0.391864E+09 0.453720E+09 0.259016E+09 0.194704E+09 0.00 0.00
November 0.572835E+09 0.505320E+09 0.409283E+09 0.248091E+09 0.161192E+09 0.00 0.00
December 0.442646E+09 0.639453E+09 0.340564E+09 0.194441E+09 0.146122E+09 0.00 0.00
               
Annual Sum or Average 0.987313E+10 0.389841E+10 0.584785E+10 0.313335E+10 0.271449E+10 0.00 0.00
Minimum of Months 0.370360E+09 0.102124E+09 0.304643E+09 0.147896E+09 0.146122E+09 0.00 0.00
Maximum of Months 0.138139E+10 0.639453E+09 0.698421E+09 0.403956E+09 0.303869E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.478809E+09 -410118789.8 0.00 0.00 744.00 0.00 -68690469.0 58.99 0.00 0.00
February 0.430503E+09 -367461488.1 0.00 0.00 672.00 0.00 -63041403.2 58.99 0.00 0.00
March 0.491246E+09 -422746020.3 0.00 0.00 744.00 0.00 -68500327.4 58.98 0.00 0.00
April 0.402071E+09 -338571830.9 0.00 0.00 720.00 0.00 -63499151.3 58.98 0.00 0.00
May 0.403093E+09 -338342909.4 0.00 0.00 744.00 0.00 -64749844.5 58.99 0.00 0.00
June 0.369728E+09 -308469180.5 0.00 0.00 720.00 0.00 -61258707.3 58.99 0.00 0.00
July 0.330279E+09 -267766251.9 0.00 0.00 744.00 0.00 -62513164.1 58.98 0.00 0.00
August 0.376121E+09 -312719932.5 0.00 0.00 744.00 0.00 -63400763.3 58.99 0.00 0.00
September 0.353084E+09 -291935475.0 0.00 0.00 720.00 0.00 -61148669.2 58.99 0.00 0.00
October 0.402291E+09 -337237750.4 0.00 0.00 744.00 0.00 -65053247.8 58.99 0.00 0.00
November 0.435220E+09 -370147077.8 0.00 0.00 720.00 0.00 -65073317.5 59.00 0.00 0.00
December 0.446750E+09 -377844579.3 0.00 0.00 744.00 0.00 -68905326.5 58.99 0.00 0.00
                     
Annual Sum or Average 0.491920E+10 -0.414336E+10 0.00 0.00 8760.00 0.00 -775834391.1 58.99 0.00 0.00
Minimum of Months 0.330279E+09 -422746020.3 0.00 0.00 672.00 0.00 -68905326.5 58.98 0.00 0.00
Maximum of Months 0.491246E+09 -267766251.9 0.00 0.00 744.00 0.00 -61148669.2 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.75 0.73 01-JAN-08:39 2239.94 28.67 180.00 278.17 533.36 20.82 136.17 230.83
February 241.00 0.76 0.73 01-FEB-09:09 2605.50 28.68 148.50 202.50 439.26 20.85 117.33 148.00
March 344.33 0.78 0.73 02-MAR-09:20 404.36 16.53 2.33 218.83 312.33 20.63 176.67 151.50
April 380.33 0.80 0.73 03-APR-12:09 299.54 15.90 0.00 107.00 226.25 20.05 101.67 29.33
May 403.17 0.84 0.73 20-MAY-12:20 233.29 15.29 0.00 20.67 176.27 19.55 37.50 0.00
June 418.17 0.86 0.74 16-JUN-11:30 195.90 14.33 0.00 2.17 151.14 18.65 8.00 0.00
July 399.50 0.84 0.73 14-JUL-13:39 224.31 14.89 0.00 18.50 168.61 19.13 58.50 0.00
August 361.83 0.83 0.73 01-AUG-10:30 253.77 15.42 0.00 59.67 190.45 19.66 68.50 5.17
September 350.17 0.79 0.73 01-SEP-08:50 371.21 16.38 0.00 201.00 279.24 20.54 180.33 110.67
October 348.00 0.77 0.73 01-OCT-08:20 719.17 17.31 22.67 258.17 388.56 20.59 142.83 199.83
November 288.50 0.75 0.73 01-NOV-08:39 2050.86 27.23 157.00 245.50 542.80 23.50 154.00 216.17
December 290.67 0.74 0.73 01-DEC-07:40 1833.36 28.05 161.67 260.83 626.84 24.35 175.50 239.67
                         
Annual Sum or Average 4135.50 0.80     831.18 19.10 672.17 1873.00 316.06 20.52 1357.00 1331.17
Minimum of Months 241.00 0.74 0.73   195.90 14.33 0.00 2.17 151.14 18.65 8.00 0.00
Maximum of Months 418.17 0.86 0.74   2605.50 28.68 180.00 278.17 626.84 24.35 180.33 239.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.84 0.73 01-JAN-08:20 917.48 17.20 56.17 89.67 684.44 23.41 92.50 79.50
February 241.00 0.83 0.73 01-FEB-08:20 1017.70 17.35 42.17 80.33 862.09 24.23 89.17 70.00
March 344.33 0.83 0.73 01-MAR-07:00 303.13 13.93 0.33 111.33 255.49 18.94 83.33 86.50
April 380.33 0.83 0.73 01-APR-07:10 306.12 13.72 0.00 116.33 275.84 19.11 62.17 105.67
May 403.17 0.83 0.73 01-MAY-06:30 306.85 13.77 0.00 131.50 282.62 19.35 58.17 120.67
June 418.17 0.84 0.73 01-JUN-06:19 283.00 13.12 0.00 125.00 264.30 18.74 33.50 117.50
July 399.50 0.83 0.73 01-JUL-06:19 289.23 13.69 0.00 121.67 260.59 19.03 56.50 111.50
August 361.83 0.83 0.73 01-AUG-06:49 295.00 13.75 0.00 116.00 264.20 19.18 59.00 103.33
September 350.17 0.83 0.73 01-SEP-06:00 299.67 14.18 0.00 108.00 249.80 19.02 88.67 82.50
October 348.00 0.84 0.73 01-OCT-07:49 361.77 13.64 7.33 109.17 277.90 18.51 69.67 89.50
November 288.50 0.85 0.73 01-NOV-08:09 859.77 17.73 54.00 78.67 488.63 22.17 77.00 69.33
December 290.67 0.84 0.73 01-DEC-07:00 1291.47 20.20 85.33 89.67 702.67 23.78 85.67 69.67
                         
Annual Sum or Average 4135.50 0.83     500.29 14.92 245.33 1277.33 378.74 20.18 855.33 1105.67
Minimum of Months 241.00 0.83 0.73   283.00 13.12 0.00 78.67 249.80 18.51 33.50 69.33
Maximum of Months 418.17 0.85 0.73   1291.47 20.20 85.33 131.50 862.09 24.23 92.50 120.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.93 0.86 23-JAN-14:30 102.60 11.03 0.00 0.00 82.22 15.47 0.00 0.00
February 241.00 0.91 0.84 14-FEB-14:30 128.57 12.14 0.00 0.00 96.05 16.18 0.00 0.00
March 344.33 0.90 0.74 14-MAR-14:30 149.96 13.35 0.00 0.00 108.08 17.20 0.00 0.00
April 380.33 0.87 0.74 07-APR-15:30 182.91 14.58 0.00 0.00 132.13 18.41 0.00 0.00
May 403.17 0.85 0.73 31-MAY-18:10 213.03 15.46 0.00 1.17 152.14 19.32 3.50 1.50
June 418.17 0.85 0.73 01-JUN-18:10 217.45 15.34 0.00 6.83 217.45 22.57 79.50 48.83
July 399.50 0.85 0.74 14-JUL-16:30 217.34 15.40 0.00 4.50 151.18 19.11 4.67 0.00
August 361.83 0.87 0.74 08-AUG-15:30 184.10 14.70 0.00 0.00 130.67 18.49 0.00 0.00
September 350.17 0.88 0.74 17-SEP-15:30 172.09 14.08 0.00 0.67 122.22 17.85 0.17 0.00
October 348.00 0.92 0.79 07-OCT-09:30 120.34 11.87 0.00 0.00 91.58 15.97 0.00 0.00
November 288.50 0.92 0.84 03-NOV-14:30 112.01 11.68 0.00 0.00 86.75 16.05 0.00 0.00
December 290.67 0.93 0.86 31-DEC-12:30 103.50 11.21 0.00 0.00 81.81 15.68 0.00 0.00
                         
Annual Sum or Average 4135.50 0.89     164.13 13.61 0.00 13.17 125.62 17.93 87.83 50.33
Minimum of Months 241.00 0.85 0.73   102.60 11.03 0.00 0.00 81.81 15.47 0.00 0.00
Maximum of Months 418.17 0.93 0.86   217.45 15.46 0.00 6.83 217.45 22.57 79.50 48.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.85 0.73 01-JAN-14:30 1352.24 19.34 84.83 99.83 756.19 22.83 97.00 83.33
February 241.00 0.84 0.73 01-FEB-14:39 844.55 16.83 40.67 74.67 389.27 21.06 79.33 60.17
March 344.33 0.84 0.73 02-MAR-13:00 288.13 14.00 0.00 110.17 234.96 18.75 85.17 75.33
April 380.33 0.83 0.73 01-APR-14:20 317.73 13.91 0.00 127.17 285.67 19.20 104.17 113.83
May 403.17 0.83 0.73 01-MAY-14:09 302.52 13.91 0.00 119.83 277.26 19.19 82.50 111.83
June 418.17 0.84 0.73 01-JUN-14:20 288.78 13.42 0.00 124.67 270.65 18.85 79.00 115.83
July 399.50 0.84 0.73 01-JUL-14:20 266.79 13.84 0.00 98.67 235.51 18.95 83.33 83.00
August 361.83 0.84 0.73 01-AUG-14:09 267.10 13.64 0.00 90.83 234.75 18.74 63.00 77.83
September 350.17 0.83 0.73 01-SEP-13:30 287.44 14.36 0.00 102.33 260.99 19.26 96.33 74.17
October 348.00 0.84 0.73 01-OCT-13:50 361.46 13.78 7.33 101.00 606.32 21.23 92.83 84.00
November 288.50 0.84 0.73 01-NOV-13:39 899.69 17.58 52.83 93.17 617.04 22.74 88.33 81.50
December 290.67 0.84 0.73 01-DEC-13:50 819.96 18.01 60.67 87.33 481.40 21.91 84.33 67.00
                         
Annual Sum or Average 4135.50 0.84     486.72 14.99 246.33 1229.67 372.86 20.06 1035.33 1027.83
Minimum of Months 241.00 0.83 0.73   266.79 13.42 0.00 74.67 234.75 18.74 63.00 60.17
Maximum of Months 418.17 0.85 0.73   1352.24 19.34 84.83 127.17 756.19 22.83 104.17 115.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 4003164.04 5938.95 02-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4003164.04     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4003164.04 5938.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10568970.38 6034.32 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 43140336.55 5691.89 13-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 63052335.02 5821.62 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 44850939.84 4791.75 07-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161613E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 63052335.02 6034.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8470814.57 4691.01 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 2302862.02 2277.45 13-FEB-08:63 0.00 0.00 0.00 0.00 0.00
March 3896222.06 3885.66 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 2972772.45 2884.49 18-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17642671.10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 8470814.57 4691.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 49516498.61 6801.36 02-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 23663615.83 5388.59 09-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 24459119.10 6324.13 27-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 141513.41 943.42 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 30945809.29 6066.14 18-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128727E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 49516498.61 6801.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10514003.56 5539.11 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 5368437.12 2632.36 13-FEB-08:63 0.00 0.00 0.00 0.00 0.00
March 5112827.86 3680.88 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 5728295.56 3291.33 18-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 26723564.10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 10514003.56 5539.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 298038.33 2483.65 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 298038.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 298038.33 2483.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 114131.85 760.88 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 432544.36 3604.54 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 102720.98 684.81 18-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 649397.19     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 432544.36 3604.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.111193E+10 0.108571E+10 3058.55 31-JAN-16:55 3058.55 0.00
February 0.00 0.00 0.588181E+09 0.516168E+09 1952.95 01-FEB-15:57 1952.95 0.00
March 0.00 0.00 0.119128E+10 0.112672E+10 5836.15 21-MAR-07:03 5836.15 0.00
April 0.00 0.00 0.256366E+10 0.256073E+10 6091.21 26-APR-06:03 6091.21 0.00
May 0.00 0.00 0.349577E+10 0.349577E+10 6117.73 11-MAY-06:03 6117.73 0.00
June 0.00 0.00 0.444142E+10 0.442775E+10 6280.68 26-JUN-05:02 6280.68 0.00
July 0.00 0.00 0.452293E+10 0.405404E+10 6834.51 14-JUL-06:02 4385.72 0.00
August 0.00 0.00 0.504862E+10 0.449368E+10 6673.57 10-AUG-06:02 4837.91 0.00
September 0.00 0.00 0.420010E+10 0.373894E+10 6783.94 05-SEP-05:02 5027.56 0.00
October 0.00 0.00 0.292078E+10 0.278841E+10 6611.01 03-OCT-06:01 5082.42 0.00
November 0.00 0.00 0.181264E+10 0.166641E+10 6487.03 14-NOV-08:62 4155.38 0.00
December 0.00 0.00 0.769065E+09 0.761641E+09 2620.08 26-DEC-16:50 2620.08 0.00
                 
Annual Sum or Average 0.00 0.00 0.326664E+11 0.307160E+11       0.00
Minimum of Months 0.00 0.00 0.588181E+09 0.516168E+09 1952.95   1952.95 0.00
Maximum of Months 0.00 0.00 0.504862E+10 0.449368E+10 6834.51   6280.68 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.207168E+10 0.206635E+10 5773.79 30-JAN-14:40 5773.79 0.00
February 0.00 0.00 0.665733E+09 0.649782E+09 3462.79 01-FEB-15:30 3462.79 0.00
March 0.00 0.00 0.943530E+09 0.939928E+09 3728.07 20-MAR-14:30 3728.07 0.00
April 0.00 0.00 0.230007E+10 0.230007E+10 6883.41 26-APR-07:02 6883.41 0.00
May 0.00 0.00 0.293284E+10 0.293284E+10 6905.04 11-MAY-07:02 6905.04 0.00
June 0.00 0.00 0.437906E+10 0.437217E+10 7157.36 19-JUN-05:02 7157.36 0.00
July 0.00 0.00 0.474110E+10 0.437553E+10 7895.87 14-JUL-06:02 5139.68 0.00
August 0.00 0.00 0.538331E+10 0.496935E+10 7703.41 10-AUG-06:02 5655.53 0.00
September 0.00 0.00 0.483725E+10 0.448030E+10 7672.71 05-SEP-05:02 6634.43 0.00
October 0.00 0.00 0.369487E+10 0.362203E+10 7603.40 03-OCT-06:01 6205.17 0.00
November 0.00 0.00 0.267635E+10 0.259317E+10 7140.08 01-NOV-07:02 6830.54 0.00
December 0.00 0.00 0.148598E+10 0.148476E+10 5902.94 26-DEC-13:55 5902.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.361118E+11 0.347863E+11       0.00
Minimum of Months 0.00 0.00 0.665733E+09 0.649782E+09 3462.79   3462.79 0.00
Maximum of Months 0.00 0.00 0.538331E+10 0.496935E+10 7895.87   7157.36 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.534382E+09 0.532387E+09 1656.73 31-JAN-16:07 1656.73 0.00
February 0.00 0.00 0.188548E+09 0.181901E+09 938.93 23-FEB-11:02 887.39 0.00
March 0.00 0.00 0.511742E+09 0.509996E+09 1720.07 20-MAR-14:40 1720.07 0.00
April 0.00 0.00 0.171096E+10 0.171096E+10 4911.55 17-APR-07:02 4911.55 0.00
May 0.00 0.00 0.232405E+10 0.232405E+10 4910.58 30-MAY-06:02 4910.58 0.00
June 0.00 0.00 0.334936E+10 0.334612E+10 5085.81 19-JUN-05:02 5085.81 0.00
July 0.00 0.00 0.342786E+10 0.324652E+10 5519.10 14-JUL-06:02 3870.69 0.00
August 0.00 0.00 0.370673E+10 0.350357E+10 5406.74 10-AUG-06:02 4178.27 0.00
September 0.00 0.00 0.295392E+10 0.278048E+10 5410.34 05-SEP-05:02 4690.71 0.00
October 0.00 0.00 0.192209E+10 0.188586E+10 5330.73 03-OCT-06:01 4494.43 0.00
November 0.00 0.00 0.994301E+09 0.957803E+09 5069.90 03-NOV-07:02 4588.05 0.00
December 0.00 0.00 0.334860E+09 0.334350E+09 1388.21 26-DEC-13:55 1388.21 0.00
                 
Annual Sum or Average 0.00 0.00 0.219588E+11 0.213140E+11       0.00
Minimum of Months 0.00 0.00 0.188548E+09 0.181901E+09 938.93   887.39 0.00
Maximum of Months 0.00 0.00 0.370673E+10 0.350357E+10 5519.10   5085.81 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.404531E+09 0.402845E+09 2056.48 31-JAN-16:42 2056.48 0.00
February 0.00 0.00 67583183.83 62197441.38 896.29 16-FEB-15:55 798.35 0.00
March 0.00 0.00 0.435110E+09 0.431585E+09 2263.73 16-MAR-15:57 2263.73 0.00
April 0.00 0.00 0.183926E+10 0.183926E+10 6884.35 17-APR-07:02 6884.35 0.00
May 0.00 0.00 0.276072E+10 0.276072E+10 6853.98 11-MAY-07:02 6853.98 0.00
June 0.00 0.00 0.421557E+10 0.420948E+10 7101.61 19-JUN-05:02 7101.61 0.00
July 0.00 0.00 0.451027E+10 0.419954E+10 7758.25 14-JUL-06:02 5306.77 0.00
August 0.00 0.00 0.484058E+10 0.448872E+10 7582.94 10-AUG-06:02 5739.91 0.00
September 0.00 0.00 0.394717E+10 0.365183E+10 7730.80 05-SEP-05:02 5957.07 0.00
October 0.00 0.00 0.219763E+10 0.213294E+10 7502.77 03-OCT-06:01 6207.24 0.00
November 0.00 0.00 0.104306E+10 0.979155E+09 7093.71 03-NOV-07:02 6295.95 0.00
December 0.00 0.00 0.218327E+09 0.217853E+09 1685.76 22-DEC-15:35 1685.76 0.00
                 
Annual Sum or Average 0.00 0.00 0.264798E+11 0.253761E+11       0.00
Minimum of Months 0.00 0.00 67583183.83 62197441.38 896.29   798.35 0.00
Maximum of Months 0.00 0.00 0.484058E+10 0.448872E+10 7758.25   7101.61 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.589047E+09 0.586419E+09 2653.34 31-JAN-16:55 2653.34 0.00
February 0.00 0.00 0.190520E+09 0.181282E+09 1742.82 22-FEB-16:23 1672.85 0.00
March 0.00 0.00 0.473389E+09 0.469299E+09 2298.63 16-MAR-15:57 2298.63 0.00
April 0.00 0.00 0.155951E+10 0.155951E+10 5808.52 17-APR-07:02 5808.52 0.00
May 0.00 0.00 0.215976E+10 0.215976E+10 5806.77 30-MAY-06:02 5806.77 0.00
June 0.00 0.00 0.323212E+10 0.322810E+10 5908.13 02-JUN-06:02 5908.13 0.00
July 0.00 0.00 0.323813E+10 0.304011E+10 6510.76 14-JUL-06:02 4610.56 0.00
August 0.00 0.00 0.353990E+10 0.331399E+10 6380.01 10-AUG-06:02 4942.09 0.00
September 0.00 0.00 0.288728E+10 0.269774E+10 6364.23 05-SEP-05:02 5679.59 0.00
October 0.00 0.00 0.180163E+10 0.175908E+10 6288.67 03-OCT-06:01 5356.04 0.00
November 0.00 0.00 0.107240E+10 0.102493E+10 6240.65 13-NOV-08:62 4495.52 0.00
December 0.00 0.00 0.383174E+09 0.382511E+09 2586.74 26-DEC-16:30 2586.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.211269E+11 0.204027E+11       0.00
Minimum of Months 0.00 0.00 0.190520E+09 0.181282E+09 1742.82   1672.85 0.00
Maximum of Months 0.00 0.00 0.353990E+10 0.331399E+10 6510.76   5908.13 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 164.86 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     14.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   164.86 513.97  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.365054E+09 0.37 371.44 02-JAN-06:03 1.01
February 0.330287E+09 0.37 371.44 01-FEB-06:05 1.01
March 0.399821E+09 0.40 371.44 01-MAR-06:10 1.01
April 0.347670E+09 0.36 371.44 03-APR-05:10 1.01
May 0.382437E+09 0.39 371.44 01-MAY-05:10 1.01
June 0.382437E+09 0.40 371.44 01-JUN-05:10 1.01
July 0.347968E+09 0.35 371.44 03-JUL-05:02 1.00
August 0.400047E+09 0.40 371.44 01-AUG-05:03 1.00
September 0.347670E+09 0.36 371.44 01-SEP-05:10 1.00
October 0.365054E+09 0.37 371.44 02-OCT-05:02 1.00
November 0.365054E+09 0.38 371.44 01-NOV-05:10 1.01
December 0.347670E+09 0.35 371.44 01-DEC-06:10 1.01
           
Annual Sum or Average 0.438117E+10 0.38      
Minimum of Months 0.330287E+09 0.35 371.44   1.00
Maximum of Months 0.400047E+09 0.40 371.44   1.01



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.449738E+09 0.37 457.61 02-JAN-06:03 1.01
February 0.406905E+09 0.37 457.61 01-FEB-06:05 1.01
March 0.492570E+09 0.41 457.61 01-MAR-06:10 1.01
April 0.428321E+09 0.37 457.61 03-APR-05:10 1.01
May 0.471154E+09 0.39 457.61 01-MAY-05:10 1.02
June 0.473397E+09 0.42 457.61 01-JUN-05:10 1.01
July 0.434764E+09 0.39 457.61 03-JUL-05:02 1.01
August 0.501696E+09 0.45 457.61 01-AUG-05:03 1.00
September 0.441565E+09 0.43 457.61 01-SEP-05:10 1.00
October 0.457419E+09 0.41 457.61 02-OCT-05:02 1.00
November 0.449796E+09 0.38 457.61 01-NOV-05:10 1.01
December 0.428712E+09 0.36 457.61 01-DEC-06:10 1.01
           
Annual Sum or Average 0.543604E+10 0.39      
Minimum of Months 0.406905E+09 0.36 457.61   1.00
Maximum of Months 0.501696E+09 0.45 457.61   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.334259E+09 0.37 340.11 02-JAN-06:03 1.01
February 0.302425E+09 0.37 340.11 01-FEB-06:05 1.01
March 0.366093E+09 0.41 340.11 01-MAR-06:10 1.01
April 0.318342E+09 0.37 340.11 03-APR-05:10 1.01
May 0.350268E+09 0.39 340.11 01-MAY-05:10 1.01
June 0.362970E+09 0.49 340.11 01-JUN-05:10 1.01
July 0.335564E+09 0.47 340.11 02-JUL-09:22 1.01
August 0.379367E+09 0.48 340.11 01-AUG-05:03 1.00
September 0.326273E+09 0.42 340.11 01-SEP-05:10 1.00
October 0.335336E+09 0.38 340.11 02-OCT-05:02 1.00
November 0.334259E+09 0.38 340.11 01-NOV-05:10 1.01
December 0.318342E+09 0.35 340.11 01-DEC-06:10 1.01
           
Annual Sum or Average 0.406350E+10 0.41      
Minimum of Months 0.302425E+09 0.35 340.11   1.00
Maximum of Months 0.379367E+09 0.49 340.11   1.01



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.444460E+09 0.37 452.24 02-JAN-06:03 1.01
February 0.402130E+09 0.37 452.24 01-FEB-06:05 1.01
March 0.486789E+09 0.41 452.24 01-MAR-06:10 1.01
April 0.423295E+09 0.36 452.24 03-APR-05:10 1.01
May 0.465624E+09 0.39 452.24 01-MAY-05:10 1.01
June 0.469431E+09 0.42 452.24 01-JUN-05:10 1.01
July 0.430795E+09 0.40 452.24 03-JUL-05:02 1.01
August 0.493213E+09 0.44 452.24 01-AUG-05:03 1.00
September 0.425386E+09 0.38 452.24 01-SEP-05:10 1.00
October 0.444592E+09 0.37 452.24 02-OCT-05:02 1.00
November 0.444460E+09 0.38 452.24 01-NOV-05:10 1.01
December 0.423295E+09 0.35 452.24 01-DEC-06:10 1.01
           
Annual Sum or Average 0.535347E+10 0.39      
Minimum of Months 0.402130E+09 0.35 452.24   1.00
Maximum of Months 0.493213E+09 0.44 452.24   1.01



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.394691E+09 0.37 401.60 02-JAN-06:03 1.01
February 0.357101E+09 0.37 401.60 01-FEB-06:05 1.01
March 0.432280E+09 0.41 401.60 01-MAR-06:10 1.01
April 0.376820E+09 0.37 401.60 03-APR-05:10 1.01
May 0.417299E+09 0.41 401.60 01-MAY-05:10 1.01
June 0.433873E+09 0.52 401.60 01-JUN-05:10 1.01
July 0.397138E+09 0.47 401.60 01-JUL-17:23 1.01
August 0.448693E+09 0.49 401.60 01-AUG-05:03 1.00
September 0.385015E+09 0.43 401.60 01-SEP-05:10 1.00
October 0.396886E+09 0.39 401.60 02-OCT-05:02 1.00
November 0.394691E+09 0.38 401.60 01-NOV-05:10 1.01
December 0.375896E+09 0.35 401.60 01-DEC-06:10 1.01
           
Annual Sum or Average 0.481038E+10 0.41      
Minimum of Months 0.357101E+09 0.35 401.60   1.00
Maximum of Months 0.448693E+09 0.52 401.60   1.01



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.01 0.00 0.00 02-JAN-07:01 0.00 0.00 44.41 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 18.53 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 18.53 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 18.53 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 18.53 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 18.53 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00 0.00 18.53 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 18.53 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 18.53 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 18.53 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 18.53 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 18.53 0.00
                 
Annual Sum or Average 0.01 0.00            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 18.53 0.00
Maximum of Months 0.01 0.00 0.00   0.00 0.00 44.41 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 164.86 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 18.53 18.53 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 18.53 18.53 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 18.53 18.53 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 18.53 18.53 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 18.53 18.53 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 18.53 18.53 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 18.53 18.53 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 18.53 18.53 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 18.53 18.53 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 18.53 18.53 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 18.53 18.53 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         14.00    
Minimum of Months 0.00 0.00   18.53 18.53 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 164.86 513.97  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.616184E+09 0.00 0.00
February 0.00 0.00 0.00 0.461075E+09 0.00 0.00
March 0.00 0.00 0.00 0.669440E+09 0.00 0.00
April 0.00 0.00 0.00 0.948056E+09 0.00 0.00
May 0.00 0.00 0.00 0.122738E+10 0.00 0.00
June 0.00 0.00 0.00 0.151658E+10 0.00 0.00
July 0.00 0.00 0.00 0.143698E+10 0.00 0.00
August 0.00 0.00 0.00 0.161460E+10 0.00 0.00
September 0.00 0.00 0.00 0.132509E+10 0.00 0.00
October 0.00 0.00 0.00 0.102715E+10 0.00 0.00
November 0.00 0.00 0.00 0.763491E+09 0.00 0.00
December 0.00 0.00 0.00 0.521913E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.121279E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.461075E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.161460E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.902309E+09 0.00 0.00
February 0.00 0.00 0.00 0.567217E+09 0.00 0.00
March 0.00 0.00 0.00 0.731479E+09 0.00 0.00
April 0.00 0.00 0.00 0.988664E+09 0.00 0.00
May 0.00 0.00 0.00 0.121716E+10 0.00 0.00
June 0.00 0.00 0.00 0.164163E+10 0.00 0.00
July 0.00 0.00 0.00 0.161775E+10 0.00 0.00
August 0.00 0.00 0.00 0.184336E+10 0.00 0.00
September 0.00 0.00 0.00 0.159607E+10 0.00 0.00
October 0.00 0.00 0.00 0.129821E+10 0.00 0.00
November 0.00 0.00 0.00 0.102481E+10 0.00 0.00
December 0.00 0.00 0.00 0.766634E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.141953E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.567217E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.184336E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.459829E+09 0.00 0.00
February 0.00 0.00 0.00 0.345824E+09 0.00 0.00
March 0.00 0.00 0.00 0.487039E+09 0.00 0.00
April 0.00 0.00 0.00 0.728434E+09 0.00 0.00
May 0.00 0.00 0.00 0.927512E+09 0.00 0.00
June 0.00 0.00 0.00 0.124621E+10 0.00 0.00
July 0.00 0.00 0.00 0.119609E+10 0.00 0.00
August 0.00 0.00 0.00 0.130930E+10 0.00 0.00
September 0.00 0.00 0.00 0.104101E+10 0.00 0.00
October 0.00 0.00 0.00 0.784322E+09 0.00 0.00
November 0.00 0.00 0.00 0.558660E+09 0.00 0.00
December 0.00 0.00 0.00 0.398324E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.948255E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.345824E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.130930E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.555066E+09 0.00 0.00
February 0.00 0.00 0.00 0.425387E+09 0.00 0.00
March 0.00 0.00 0.00 0.598961E+09 0.00 0.00
April 0.00 0.00 0.00 0.876468E+09 0.00 0.00
May 0.00 0.00 0.00 0.116686E+10 0.00 0.00
June 0.00 0.00 0.00 0.159173E+10 0.00 0.00
July 0.00 0.00 0.00 0.156061E+10 0.00 0.00
August 0.00 0.00 0.00 0.170947E+10 0.00 0.00
September 0.00 0.00 0.00 0.138080E+10 0.00 0.00
October 0.00 0.00 0.00 0.967734E+09 0.00 0.00
November 0.00 0.00 0.00 0.682688E+09 0.00 0.00
December 0.00 0.00 0.00 0.487567E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.120034E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.425387E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.170947E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.533764E+09 0.00 0.00
February 0.00 0.00 0.00 0.401749E+09 0.00 0.00
March 0.00 0.00 0.00 0.545895E+09 0.00 0.00
April 0.00 0.00 0.00 0.762274E+09 0.00 0.00
May 0.00 0.00 0.00 0.973584E+09 0.00 0.00
June 0.00 0.00 0.00 0.132155E+10 0.00 0.00
July 0.00 0.00 0.00 0.123789E+10 0.00 0.00
August 0.00 0.00 0.00 0.136743E+10 0.00 0.00
September 0.00 0.00 0.00 0.110338E+10 0.00 0.00
October 0.00 0.00 0.00 0.829603E+09 0.00 0.00
November 0.00 0.00 0.00 0.637716E+09 0.00 0.00
December 0.00 0.00 0.00 0.467587E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.101824E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.401749E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.136743E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.365054E+09 0.111193E+10 4003164.04 0.00 0.00 0.00 0.00 0.00
February 0.330287E+09 0.588181E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.399821E+09 0.119128E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.347670E+09 0.256366E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.382437E+09 0.349577E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.382437E+09 0.444142E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.347968E+09 0.452293E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.400047E+09 0.504862E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.347670E+09 0.420010E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.365054E+09 0.292078E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.365054E+09 0.181264E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347670E+09 0.769065E+09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.438117E+10 0.326664E+11 4003164.04 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.330287E+09 0.588181E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400047E+09 0.504862E+10 4003164.04 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.449738E+09 0.207168E+10 10568970.38 0.00 0.00 0.00 0.00 0.00
February 0.406905E+09 0.665733E+09 43140336.55 0.00 0.00 0.00 0.00 0.00
March 0.492570E+09 0.943530E+09 63350373.35 0.00 0.00 0.00 0.00 0.00
April 0.428321E+09 0.230007E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.471154E+09 0.293284E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.473397E+09 0.437906E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.434764E+09 0.474110E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.501696E+09 0.538331E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.441565E+09 0.483725E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.457419E+09 0.369487E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.449796E+09 0.267635E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.428712E+09 0.148598E+10 44850939.84 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.543604E+10 0.361118E+11 0.161911E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.406905E+09 0.665733E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.501696E+09 0.538331E+10 63350373.35 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.334259E+09 0.534382E+09 8470814.57 0.00 0.00 0.00 0.00 0.00
February 0.302425E+09 0.188548E+09 2302862.02 0.00 0.00 0.00 0.00 0.00
March 0.366093E+09 0.511742E+09 3896222.06 0.00 0.00 0.00 0.00 0.00
April 0.318342E+09 0.171096E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.350268E+09 0.232405E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.362970E+09 0.334936E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.335564E+09 0.342786E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.379367E+09 0.370673E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.326273E+09 0.295392E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.335336E+09 0.192209E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.334259E+09 0.994301E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.318342E+09 0.334860E+09 2972772.45 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.406350E+10 0.219588E+11 17642671.10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.302425E+09 0.188548E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379367E+09 0.370673E+10 8470814.57 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.444460E+09 0.404531E+09 49630630.46 0.00 0.00 0.00 0.00 0.00
February 0.402130E+09 67583183.83 23663615.83 0.00 0.00 0.00 0.00 0.00
March 0.486789E+09 0.435110E+09 24891663.46 0.00 0.00 0.00 0.00 0.00
April 0.423295E+09 0.183926E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.465624E+09 0.276072E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.469431E+09 0.421557E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.430795E+09 0.451027E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.493213E+09 0.484058E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.425386E+09 0.394717E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.444592E+09 0.219763E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.444460E+09 0.104306E+10 141513.41 0.00 0.00 0.00 0.00 0.00
December 0.423295E+09 0.218327E+09 31048530.27 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.535347E+10 0.264798E+11 0.129376E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.402130E+09 67583183.83 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.493213E+09 0.484058E+10 49630630.46 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.394691E+09 0.589047E+09 10514003.56 0.00 0.00 0.00 0.00 0.00
February 0.357101E+09 0.190520E+09 5368437.12 0.00 0.00 0.00 0.00 0.00
March 0.432280E+09 0.473389E+09 5112827.86 0.00 0.00 0.00 0.00 0.00
April 0.376820E+09 0.155951E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.417299E+09 0.215976E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.433873E+09 0.323212E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.397138E+09 0.323813E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.448693E+09 0.353990E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.385015E+09 0.288728E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.396886E+09 0.180163E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.394691E+09 0.107240E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.375896E+09 0.383174E+09 5728295.56 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.481038E+10 0.211269E+11 26723564.10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.357101E+09 0.190520E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.448693E+09 0.353990E+10 10514003.56 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.365054E+09 0.00 0.00 1380361.51 0.249750E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.330287E+09 0.00 0.00 0.00 0.130788E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.399821E+09 0.00 0.00 990000.00 0.268630E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.347670E+09 0.00 0.00 0.00 0.600386E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.382437E+09 0.00 0.00 0.00 0.844948E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.382437E+09 0.00 0.00 0.00 0.113415E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.347968E+09 0.00 0.00 0.00 0.108901E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.400047E+09 0.00 0.00 0.00 0.121455E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.347670E+09 0.00 0.00 0.00 0.977425E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.365054E+09 0.00 0.00 0.00 0.662094E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.365054E+09 0.00 0.00 180000.00 0.398257E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347670E+09 0.00 0.00 3180000.00 0.171063E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.438117E+10 0.00 0.00 5730361.51 0.774104E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.330287E+09 0.00 0.00 0.00 0.130788E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400047E+09 0.00 0.00 3180000.00 0.121455E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.449738E+09 0.00 0.00 3610824.95 0.448961E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.406905E+09 0.00 0.00 14509901.36 0.145801E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.492570E+09 0.00 0.00 22784162.86 0.216125E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.428321E+09 0.00 0.00 0.00 0.560342E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.471154E+09 0.00 0.00 0.00 0.746005E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.473397E+09 0.00 0.00 0.00 0.116823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.434764E+09 0.00 0.00 0.00 0.118299E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.501696E+09 0.00 0.00 0.00 0.134166E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.441565E+09 0.00 0.00 0.00 0.115450E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.457419E+09 0.00 0.00 0.00 0.840794E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.449796E+09 0.00 0.00 180000.00 0.574832E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.428712E+09 0.00 0.00 20025889.23 0.317896E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.543604E+10 0.00 0.00 61110778.40 0.869814E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.406905E+09 0.00 0.00 0.00 0.145801E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.501696E+09 0.00 0.00 22784162.86 0.134166E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.334259E+09 0.00 0.00 2901300.80 0.122668E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.302425E+09 0.00 0.00 763569.74 42635946.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.366093E+09 0.00 0.00 2353722.87 0.118592E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.318342E+09 0.00 0.00 0.00 0.410092E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.350268E+09 0.00 0.00 0.00 0.577245E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.362970E+09 0.00 0.00 0.00 0.883240E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.335564E+09 0.00 0.00 0.00 0.860521E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.379367E+09 0.00 0.00 0.00 0.929930E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.326273E+09 0.00 0.00 0.00 0.714742E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.335336E+09 0.00 0.00 0.00 0.448985E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.334259E+09 0.00 0.00 180000.00 0.224221E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.318342E+09 0.00 0.00 4235992.87 75745836.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.406350E+10 0.00 0.00 10434586.29 0.540862E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.302425E+09 0.00 0.00 0.00 42635946.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379367E+09 0.00 0.00 4235992.87 0.929930E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.444460E+09 0.00 0.00 15973199.05 94633049.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.402130E+09 0.00 0.00 7886423.42 15370301.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.486789E+09 0.00 0.00 9413676.99 0.102759E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.423295E+09 0.00 0.00 0.00 0.453173E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.465624E+09 0.00 0.00 0.00 0.701239E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.469431E+09 0.00 0.00 0.00 0.112230E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.430795E+09 0.00 0.00 0.00 0.112982E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.493213E+09 0.00 0.00 0.00 0.121626E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.425386E+09 0.00 0.00 0.00 0.955418E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.444592E+09 0.00 0.00 0.00 0.523142E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.444460E+09 0.00 0.00 229296.48 0.237999E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.423295E+09 0.00 0.00 14182554.68 50089113.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.535347E+10 0.00 0.00 47685150.62 0.660220E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.402130E+09 0.00 0.00 0.00 15370301.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.493213E+09 0.00 0.00 15973199.05 0.121626E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.394691E+09 0.00 0.00 3555226.78 0.135518E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.357101E+09 0.00 0.00 1784199.34 42863871.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.432280E+09 0.00 0.00 2793149.80 0.110821E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.376820E+09 0.00 0.00 0.00 0.385454E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.417299E+09 0.00 0.00 0.00 0.556285E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.433873E+09 0.00 0.00 0.00 0.887682E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.397138E+09 0.00 0.00 0.00 0.840748E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.448693E+09 0.00 0.00 0.00 0.918742E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.385015E+09 0.00 0.00 0.00 0.718364E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.396886E+09 0.00 0.00 0.00 0.432717E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.394691E+09 0.00 0.00 180000.00 0.242845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.375896E+09 0.00 0.00 5237300.01 86454020.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.481038E+10 0.00 0.00 13549875.93 0.535849E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.357101E+09 0.00 0.00 0.00 42863871.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.448693E+09 0.00 0.00 5237300.01 0.918742E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.380233E+09 0.00 0.00 5820672.33 0.00 1725825.21 0.600103E+09 0.00 0.19
February 0.459525E+09 0.00 0.00 3084038.92 0.00 0.00 0.604979E+09 0.00 0.19
March 0.420740E+09 0.00 0.00 5609396.97 0.00 0.00 0.630151E+09 0.00 0.21
April 0.149805E+09 726389.23 0.00 13724359.42 28766.23 0.00 0.351391E+09 0.00 0.19
May 0.101526E+09 12890373.57 0.00 16470646.06 1448554.35 0.00 0.230177E+09 0.00 0.20
June 41053289.26 0.133586E+09 0.00 14777241.48 13465955.54 0.00 96704187.07 0.00 0.21
July 4922534.16 0.381671E+09 0.00 5653201.40 27389851.59 0.00 39181882.49 0.00 0.18
August 16674669.81 0.451004E+09 0.00 3098781.36 21831468.25 0.00 43029250.16 0.00 0.21
September 25139638.39 0.259708E+09 0.00 5423855.00 12902683.11 0.00 50271165.31 0.00 0.19
October 0.175043E+09 57210085.96 0.00 11400482.52 2263822.49 0.00 0.450374E+09 0.00 0.19
November 0.278371E+09 150718.98 0.00 8830036.67 0.00 0.00 0.573418E+09 0.00 0.20
December 0.515636E+09 0.00 0.00 4654261.13 0.00 0.00 0.679099E+09 0.00 0.18
                   
Annual Sum or Average 0.256867E+10 0.129695E+10 0.00 98546973.25 79331101.56 1725825.21 0.434888E+10 0.00 0.19
Minimum of Months 4922534.16 0.00 0.00 3084038.92 0.00 0.00 39181882.49 0.00 0.18
Maximum of Months 0.515636E+09 0.451004E+09 0.00 16470646.06 27389851.59 1725825.21 0.679099E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.189251E+09 245957.33 0.00 9450334.94 0.00 3386009.64 0.228013E+09 0.00 0.19
February 0.259922E+09 0.00 0.00 2957566.80 0.00 22570247.34 0.238294E+09 0.00 0.19
March 0.249163E+09 2467839.73 0.00 2830286.87 379863.82 30830149.61 0.161955E+09 0.00 0.21
April 74262042.52 69919443.13 0.00 4405387.37 7889007.24 0.00 63957179.53 0.00 0.19
May 52276410.00 0.152928E+09 0.00 3316564.69 19134220.61 0.00 13534944.74 0.00 0.20
June 21543124.02 0.350241E+09 0.00 914070.31 35696235.61 0.00 10150984.53 0.00 0.21
July 2361511.83 0.446580E+09 0.00 503652.95 32899652.42 0.00 6266911.04 0.00 0.18
August 12921681.92 0.501089E+09 0.00 777046.71 28150216.90 0.00 9122254.58 0.00 0.21
September 14605651.08 0.318975E+09 0.00 1059088.01 19560558.18 0.00 10382628.12 0.00 0.19
October 0.101805E+09 85258278.73 0.00 8753993.78 4848411.96 0.00 0.148893E+09 0.00 0.19
November 0.157005E+09 5442247.52 0.00 10933561.37 603239.11 0.00 0.208726E+09 0.00 0.20
December 0.253827E+09 0.00 0.00 7351927.59 0.00 28969654.28 0.286107E+09 0.00 0.18
                   
Annual Sum or Average 0.138894E+10 0.193315E+10 0.00 53253481.38 0.149161E+09 85756060.86 0.138540E+10 0.00 0.20
Minimum of Months 2361511.83 0.00 0.00 503652.95 0.00 0.00 6266911.04 0.00 0.18
Maximum of Months 0.259922E+09 0.501089E+09 0.00 10933561.37 35696235.61 30830149.61 0.286107E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135820E+09 39486.08 0.00 2166354.53 0.00 4785566.92 0.125091E+09 0.00 0.19
February 0.189886E+09 0.00 0.00 761625.61 0.00 1814699.48 0.136453E+09 0.00 0.19
March 0.166488E+09 1039380.71 0.00 1723252.84 27514.83 3120508.96 0.117515E+09 0.00 0.21
April 44536019.90 38082593.10 0.00 5200043.98 1958633.00 0.00 53244876.74 0.00 0.19
May 23794170.78 81600107.31 0.00 4266640.06 6733938.08 0.00 23061866.12 0.00 0.20
June 11305792.38 0.205373E+09 0.00 1828331.05 16684098.92 0.00 12446901.48 0.00 0.21
July 586049.25 0.298905E+09 0.00 533730.20 19954825.90 0.00 4060923.52 0.00 0.19
August 5058919.33 0.332887E+09 0.00 677018.11 17226879.38 0.00 7668009.72 0.00 0.22
September 6817322.64 0.219548E+09 0.00 776294.74 12299888.92 0.00 8195002.83 0.00 0.19
October 60900407.42 58478617.62 0.00 4688547.71 2544476.71 0.00 0.101643E+09 0.00 0.19
November 93000144.25 4274235.85 0.00 3954114.36 406944.14 0.00 0.140522E+09 0.00 0.20
December 0.205727E+09 31465.25 0.00 1461680.35 0.00 1274866.72 0.146580E+09 0.00 0.18
                   
Annual Sum or Average 0.943920E+09 0.124026E+10 0.00 28037633.53 77837199.87 10995642.07 0.876481E+09 0.00 0.20
Minimum of Months 586049.25 0.00 0.00 533730.20 0.00 0.00 4060923.52 0.00 0.18
Maximum of Months 0.205727E+09 0.332887E+09 0.00 5200043.98 19954825.90 4785566.92 0.146580E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.311424E+09 0.00 0.00 1097726.40 0.00 22226561.28 0.144698E+09 0.00 0.19
February 0.465004E+09 0.00 0.00 204240.98 0.00 20275072.14 84547371.13 0.00 0.19
March 0.363661E+09 44693.17 0.00 1215178.70 2612.58 19032541.22 0.134087E+09 0.00 0.21
April 89705549.84 36944771.30 0.00 5157865.24 2635508.38 0.00 98567372.46 0.00 0.19
May 48366166.91 91753870.75 0.00 4951052.62 9375304.07 0.00 42223736.70 0.00 0.20
June 20400821.36 0.286202E+09 0.00 2429939.78 25278519.48 0.00 22872937.28 0.00 0.21
July 1521678.05 0.454732E+09 0.00 654028.38 32290274.77 0.00 7635627.87 0.00 0.19
August 12162395.82 0.509753E+09 0.00 936922.40 28079738.92 0.00 10766477.04 0.00 0.21
September 12288407.97 0.324532E+09 0.00 1206829.44 19720570.21 0.00 15199227.01 0.00 0.19
October 0.119016E+09 78415383.31 0.00 5001351.43 4069662.92 0.00 0.184795E+09 0.00 0.19
November 0.208242E+09 2635924.70 0.00 3553467.49 642309.69 139355.04 0.226947E+09 0.00 0.20
December 0.461668E+09 0.00 0.00 718867.20 0.00 25650854.06 0.132170E+09 0.00 0.18
                   
Annual Sum or Average 0.211346E+10 0.178501E+10 0.00 27127470.06 0.122095E+09 87324383.73 0.110451E+10 0.00 0.19
Minimum of Months 1521678.05 0.00 0.00 204240.98 0.00 0.00 7635627.87 0.00 0.18
Maximum of Months 0.465004E+09 0.509753E+09 0.00 5157865.24 32290274.77 25650854.06 0.226947E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.160677E+09 0.00 0.00 2043010.18 0.00 5247283.85 0.134414E+09 0.00 0.19
February 0.241673E+09 0.00 0.00 637188.72 0.00 4322041.29 0.103611E+09 0.00 0.19
March 0.206259E+09 34158.85 0.00 1316761.69 1540.47 5029801.52 0.108100E+09 0.00 0.21
April 52854023.42 22472444.39 0.00 4232376.59 527555.73 0.00 66222919.96 0.00 0.19
May 28641762.67 55436151.60 0.00 3546056.11 2802350.83 0.00 28279780.74 0.00 0.20
June 12725878.02 0.183957E+09 0.00 1665275.63 6345038.73 0.00 12828078.90 0.00 0.22
July 372428.13 0.287759E+09 0.00 558374.97 16130858.61 0.00 4163819.01 0.00 0.19
August 4713304.34 0.324651E+09 0.00 741884.57 11784494.10 0.00 8319255.64 0.00 0.22
September 7349964.88 0.205309E+09 0.00 753665.47 8577136.50 0.00 8699119.44 0.00 0.19
October 64437151.90 49437087.26 0.00 4211488.17 1948851.67 0.00 0.120395E+09 0.00 0.19
November 0.103081E+09 2798717.45 0.00 3893922.55 281955.19 0.00 0.156104E+09 0.00 0.20
December 0.240238E+09 0.00 0.00 1453748.43 0.00 7007233.19 0.136434E+09 0.00 0.18
                   
Annual Sum or Average 0.112302E+10 0.113185E+10 0.00 25053753.09 48399781.83 21606359.85 0.887570E+09 0.00 0.20
Minimum of Months 372428.13 0.00 0.00 558374.97 0.00 0.00 4163819.01 0.00 0.18
Maximum of Months 0.241673E+09 0.324651E+09 0.00 4232376.59 16130858.61 7007233.19 0.156104E+09 0.00 0.22



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:30:10

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.584126E+11 0.134624E+10 0.00 0.793884E+10 0.571797E+10
February 0.649156E+11 0.176704E+10 0.00 0.767799E+10 0.202849E+10
March 0.916238E+11 0.276400E+10 0.00 0.801593E+10 0.432822E+10
April 0.126763E+12 0.330809E+10 0.00 0.399801E+10 0.123829E+11
May 0.133741E+12 0.332104E+10 0.00 0.247449E+10 0.170989E+11
June 0.139859E+12 0.329009E+10 0.00 -66213149.6 0.248131E+11
July 0.124913E+12 0.300888E+10 0.00 -0.195088E+10 0.255434E+11
August 0.110405E+12 0.255003E+10 0.00 -0.174202E+10 0.281403E+11
September 0.890868E+11 0.206780E+10 0.00 -729552293.7 0.233462E+11
October 0.778197E+11 0.181254E+10 0.00 0.479890E+10 0.154447E+11
November 0.614182E+11 0.154371E+10 0.00 0.770133E+10 0.928865E+10
December 0.459506E+11 0.128828E+10 0.00 0.104754E+11 0.391939E+10
           
Annual Sum or Average 0.112491E+13 0.280677E+11 0.00 0.485922E+11 0.172052E+12
Minimum of Months 0.459506E+11 0.128828E+10 0.00 -0.195088E+10 0.202849E+10
Maximum of Months 0.139859E+12 0.332104E+10 0.00 0.104754E+11 0.281403E+11