Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2023-10-16 08:30:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 154.78 302.81 302.81
Net Site Energy 154.78 302.81 302.81
Total Source Energy 487.56 953.83 953.83
Net Source Energy 487.56 953.83 953.83


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 5.95 1.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 153.51 1.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 5.95 1.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 19.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 19.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 23.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 5.95 1.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 19.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 19.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 134.74 2.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 300.33 2.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 134.74 2.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 300.33 2.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 153.514 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 153.514 100.00
     
Total On-Site and Utility Electric Sources 153.514 100.00
Total Electricity End Uses 153.514 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 4.67
Time Setpoint Not Met During Occupied Cooling 103.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 1832.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.0938 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.0938 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.0938 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.0938 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.0938 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.0938 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.0938 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.0938 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.0938 9.29 6.7800  
Conditioned Total 511.16             6.0938 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.0938 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 06-FEB-08:30 13-FEB-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 8503.71 20389.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2014.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1638.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2733.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 18215.90 20389.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 8503.71 20389.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2014.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1638.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2733.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 18.84 1.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 62.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 83.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 61.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 74.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 486.18 1.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 36.87 2.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 123.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 120.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 146.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 951.14 2.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 36.87 2.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 123.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 120.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 146.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 951.14 2.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.295376
PERIMETER_ZN_1 DIRECT AIR 0.317490
PERIMETER_ZN_2 DIRECT AIR 0.250564
PERIMETER_ZN_3 DIRECT AIR 0.309892
PERIMETER_ZN_4 DIRECT AIR 0.289758
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.295376 0.295376 0.295376 0.295376 0.295376 0.295376 1.00 1.00 0.295376
PSZ-AC:2 0.317490 0.317490 0.317490 0.317490 0.317490 0.317490 1.00 1.00 0.317490
PSZ-AC:3 0.250564 0.250564 0.250564 0.250564 0.250564 0.250564 1.00 1.000000 0.250564
PSZ-AC:4 0.309892 0.309892 0.309892 0.309892 0.309892 0.309892 1.00 1.00 0.309892
PSZ-AC:5 0.289758 0.289758 0.289758 0.289758 0.289758 0.289758 1.00 1.00 0.289758
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.295376 0.064622
PSZ-AC:2_OA_CONTROLLER 0.317490 0.048988
PSZ-AC:3_OA_CONTROLLER 0.250564 0.029060
PSZ-AC:4_OA_CONTROLLER 0.309892 0.048988
PSZ-AC:5_OA_CONTROLLER 0.289758 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.295376 6333.25 0.749845
PSZ-AC:2 HP COOLING COIL 0.317490 6311.13 0.778164
PSZ-AC:3 HP COOLING COIL 0.250564 4573.49 0.800428
PSZ-AC:4 HP COOLING COIL 0.309892 6182.04 0.777078
PSZ-AC:5 HP COOLING COIL 0.289758 5149.80 0.800434
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.295376 0.295376 0.295376 0.295376 6333.25 6333.25 40.00 3490.52 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.317490 0.317490 0.317490 0.317490 6311.13 6311.13 40.00 5410.56 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.250564 0.250564 0.250564 0.250564 4573.49 4573.49 40.00 3376.23 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.309892 0.309892 0.309892 0.309892 6182.04 6182.04 40.00 5390.04 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.289758 0.289758 0.289758 0.289758 5149.80 5149.80 40.00 3399.39 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.295376
PSZ-AC:2 FAN 0.317490
PSZ-AC:3 FAN 0.250564
PSZ-AC:4 FAN 0.309892
PSZ-AC:5 FAN 0.289758
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.295376 6333.25
PSZ-AC:2 HEATING COIL 0.317490 6311.13
PSZ-AC:3 HEATING COIL 0.250564 4573.49
PSZ-AC:4 HEATING COIL 0.309892 6182.04
PSZ-AC:5 HEATING COIL 0.289758 5149.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 3490.52
PSZ-AC:2_SUPPHEATCOIL 5410.56
PSZ-AC:3_SUPPHEATCOIL 3376.23
PSZ-AC:4_SUPPHEATCOIL 5390.04
PSZ-AC:5_SUPPHEATCOIL 3399.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 911.976 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 911.976
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 1.203E-002 1.060E-004 1.424E-004 0.125 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 8.017E-003 1.191E-004 1.424E-004 0.141 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 1.203E-002 1.060E-004 1.361E-004 0.125 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 8.017E-003 1.191E-004 1.424E-004 0.141 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.0732E-003
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.1827E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1468E-003
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.2413E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 7.9003E-004
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 8.7288E-004
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.9490E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.4114E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.6439E-003
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.9592E-003
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.3867E-003
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.9700E-003
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.6773E-003
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 3.9809E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.3709E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.8142E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 7.6903E-003
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.4702E-003
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.0498E-003
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 8.1597E-003
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.4188E-003
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.6916E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.8006E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6773E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.0835E-003
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.2395E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1598E-003
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3089E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 7.9949E-004
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.0494E-004
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.9164E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.3398E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.0261E-003
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.0422E-003
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1082E-003
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1228E-003
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.5528E-004
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.6612E-004
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.6914E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.7405E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.0221E-003
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.0251E-003
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1047E-003
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1074E-003
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.5243E-004
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.5445E-004
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.6767E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.6863E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.6903E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.1291E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7777E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.2285E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.2664E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.5182E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.2630E-004
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.0214E-004
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.5373E-004
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0429E-003
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.0757E-004
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.7449E-004
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.1063E-004
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.4688E-004
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.1908E-004
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.6168E-004
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3542E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.6886E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.7763E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.2913E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.6105E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1204E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0319E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9280E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.1510E-002
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.1393E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2472E-002
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.0797E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.7060E-003
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.1790E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.6144E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.0693E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0918E-003
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.3908E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0775E-003
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.3980E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.8426E-004
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0359E-003
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.2223E-004
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.6881E-004
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2204E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.0039E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.4195E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.0387E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.8877E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.3506E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.9068E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.3116E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.6113E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1017E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0898E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6256E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.1799E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.2493E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.5564E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6125E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.6762E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.5951E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.8092E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.9395E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.3309E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.1929E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7002E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8862E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3076E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.3119E-004
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.4653E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.2162E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.8574E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.2522E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9723E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.4551E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.8232E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.9485E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.0892E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.1849E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.5883E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.6434E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.6983E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.7529E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.7873E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.8124E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.0611E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.0804E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.5696E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.5811E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6816E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.6920E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.2247E-004
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.8010E-004
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.4404E-004
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.9139E-004
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.8511E-004
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.9546E-004
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.2325E-004
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.6949E-004
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.0736E-003
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.1889E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.7713E-003
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.8083E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.0535E-003
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.9253E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.5992E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.0426E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.2924E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.5282E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.5557E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9963E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.0505E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.5746E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.0289E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9056E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.3942E-004
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.3732E-004
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.4157E-004
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.1253E-004
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.2076E-004
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.4949E-004
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1999E-004
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.6233E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3234.43677 3881.32412 0.24615 0.29538 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.45000 1.44715E-002 149.65740 8.05449 6.46220E-002 0.00000
2 CORE_ZN Heating 1086.93214 1304.31857 4.86037E-002 6.46220E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 149.65740 8.05449 6.46220E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3476.53927 4171.84713 0.26457 0.31749 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83000 1.44722E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 3250.76735 3900.92081 0.14536 0.17443 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2743.77346 3292.52815 0.20880 0.25056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 31.97750 1.44688E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2069.30052 2483.16063 9.25298E-002 0.11104 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3393.35143 4072.02172 0.25824 0.30989 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 33.70333 1.44720E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 3233.41519 3880.09823 0.14458 0.17350 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3172.95109 3807.54131 0.24146 0.28976 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 31.88250 1.44687E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2088.88355 2506.66026 9.34054E-002 0.11209 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4542.07 0.29538 0.29538 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 3490.52 6.46220E-002 6.46220E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 4675.45 0.31749 0.31749 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 5410.56 0.17443 0.17443 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3515.81 0.25056 0.25056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 3376.23 0.11104 0.11104 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 4569.93 0.30989 0.30989 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 5390.04 0.17350 0.17350 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4019.64 0.28976 0.28976 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 3399.39 0.11209 0.11209 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29538
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.31749
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.25056
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30989
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28976
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29538
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29538
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29538
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.29538
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29538
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.29538
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.31749
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.31749
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.31749
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.31749
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.31749
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.31749
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.25056
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.25056
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.25056
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.25056
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.25056
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.25056
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30989
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30989
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30989
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.30989
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30989
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.30989
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28976
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28976
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28976
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.28976
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28976
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.28976
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.29538
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.31749
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.25056
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.30989
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.28976
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29538
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46220E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29538
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6333.24951
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.74984
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29538
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29538
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29538
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29538
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6333.24951
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6333.24951
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3490.51962
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.29538
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29538
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6333.24951
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 3490.51962
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.31749
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.31749
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6311.13145
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77816
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.31749
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.31749
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.31749
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.31749
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6311.13145
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6311.13145
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5410.55782
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.31749
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.31749
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6311.13145
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 5410.55782
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.25056
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.25056
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4573.49446
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80043
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.25056
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.25056
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.25056
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.25056
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4573.49446
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4573.49446
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3376.23270
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.25056
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.25056
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4573.49446
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 3376.23270
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30989
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30989
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6182.04289
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77708
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30989
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30989
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30989
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30989
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6182.04289
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6182.04289
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5390.03854
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.30989
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30989
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6182.04289
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 5390.03854
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28976
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28976
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5149.80041
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80043
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28976
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28976
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28976
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28976
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5149.80041
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5149.80041
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3399.39005
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.28976
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28976
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5149.80041
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 3399.39005
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 6100.9 3.45 11.78 12.35 11.68 11.79
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6061.6 3.41 11.63 12.18 11.52 11.56
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4376.9 3.35 11.44 11.98 11.33 11.29
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 5938.5 3.41 11.63 12.19 11.53 11.57
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4922.5 3.34 11.39 11.92 11.27 11.20


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 6569.3 3628.9 7.48 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6564.3 3634.1 7.44 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4772.8 2649.4 7.40 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 6429.2 3558.9 7.44 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5380.1 2989.1 7.36 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 5.4024225796E-003 4.4134917837E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 6.0258166111E-002 0.1130798566 Pass Pass 0.1346813626 0.6587448912 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 8.8941383082E-002 0.1404016750 Pass Pass 0.1520692295 0.6963673186 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 8.3011943692E-002 0.1407755261 Pass Pass 0.1467462272 0.6902759991 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.1048694301 0.1527472003 Pass Pass 0.2057399323 0.9077514791 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2466753893 0.2397739043 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1083.70 31.20 0.00 52.21 0.301061E+158 0.301061E+158



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.4237_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.4237_SHGC_SOUTH_0.25   3.91 0.00 0.00 3.91 3.91 2.408 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.4237_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.4237_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.4237_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.4237_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.4237_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.4237_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.4237_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.4237_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.4237_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.408 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.408 0.251 0.251                      
North Total or Average             16.72 2.408 0.251 0.251                      
Non-North Total or Average             42.93 2.408 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.40 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.09 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.0938 149.66 911.98 LightsWired LTG_SCH_OFFICE 50.53 168.00 49.65 0.0000 Y 8.50
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 41.91 0.0000 Y 5.44
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 43.35 0.0000 Y 3.34
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 44.97 0.0000 Y 5.84
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 43.61 0.0000 Y 3.36
Interior Lighting Total       6.0938 511.16 3114.87               26.47


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   41.77 41.77 0.52
EXTERIOR_LIGHTS_B 202.25 AstronomicalClock -   83.77 62.77 2.38
EXTERIOR_LIGHTS_C 780.12 AstronomicalClock -   83.77 47.60 6.97
Exterior Lighting Total 1049.10           9.88



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6333.25 4748.95 1584.30 0.75 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6311.13 4911.10 1400.03 0.78 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4573.49 3660.75 912.74 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6182.04 4803.93 1378.12 0.78 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5149.80 4122.07 1027.73 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   6100.9 3.45 11.78 12.35 11.68 11.79
PSZ-AC:2 HP COOLING COIL   6061.6 3.41 11.63 12.18 11.52 11.56
PSZ-AC:3 HP COOLING COIL   4376.9 3.35 11.44 11.98 11.33 11.29
PSZ-AC:4 HP COOLING COIL   5938.5 3.41 11.63 12.19 11.53 11.57
PSZ-AC:5 HP COOLING COIL   4922.5 3.34 11.39 11.92 11.27 11.20
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 6569.3 3628.9 7.48 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6564.3 3634.1 7.44 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4772.8 2649.4 7.40 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 6429.2 3558.9 7.44 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5380.1 2989.1 7.36 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6333.25 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   3490.52 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6311.13 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   5410.56 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4573.49 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   3376.23 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   6182.04 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   5390.04 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   5149.80 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   3399.39 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.30 330.85 1120.11 1.00 1.91 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.32 355.62 1120.11 1.00 1.86 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.25 280.66 1120.11 1.00 2.04 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.31 347.11 1120.11 1.00 1.87 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.29 324.56 1120.11 1.00 1.92 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3234.44 3881.32 25.93 0.246 0.295 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 23.89 23.89 0.00905 33.45 0.01447 0.065 0.00
PERIMETER_ZN_1 3476.54 4171.85 36.77 0.265 0.317 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 23.89 23.89 0.00894 33.83 0.01447 0.049 0.00
PERIMETER_ZN_2 2743.77 3292.53 48.92 0.209 0.251 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 23.89 23.89 0.00884 31.98 0.01447 0.029 0.00
PERIMETER_ZN_3 3393.35 4072.02 35.89 0.258 0.310 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 23.89 23.89 0.00895 33.70 0.01447 0.049 0.00
PERIMETER_ZN_4 3172.95 3807.54 56.58 0.241 0.290 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 23.89 23.89 0.00879 31.88 0.01447 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1086.93 1304.32 8.72 0.049 0.065 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 -6.30 0.00230 0.065 0.00
PERIMETER_ZN_1 3250.77 3900.92 34.38 0.145 0.174 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 -6.30 0.00230 0.049 0.00
PERIMETER_ZN_2 2069.30 2483.16 36.90 0.093 0.111 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00785 -6.30 0.00230 0.029 0.00
PERIMETER_ZN_3 3233.42 3880.10 34.20 0.145 0.174 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00786 -6.30 0.00230 0.049 0.00
PERIMETER_ZN_4 2088.88 2506.66 37.25 0.093 0.112 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00785 -6.30 0.00230 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.30 0.30 0.06 0.06 0.2954 0.2954 0.2954 1.0000 1.0000
PSZ-AC:2 0.32 0.32 0.17 0.17 0.3175 0.3175 0.3175 1.0000 1.0000
PSZ-AC:3 0.25 0.25 0.11 0.11 0.2506 0.2506 0.2506 1.0000 1.0000
PSZ-AC:4 0.31 0.31 0.17 0.17 0.3099 0.3099 0.3099 1.0000 1.0000
PSZ-AC:5 0.29 0.29 0.11 0.11 0.2898 0.2898 0.2898 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6333.250 4748.953 0.295376 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 6244.63 4902.42 0.295376 26.92 18.41 0.01023904 12.80 11.77 0.00850000 33.45 0.01447152 23.29 21.8779 23.89 0.00906047 47.2966 3203.83 0.00 6332.16 4663.50
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6333.250 6333.250 0.295376 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6333.25 6333.25 0.295376 15.11 10.97 0.00675248 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 21.8779 21.11 0.00800000 49.5265 1086.30 0.00 6341.57 6341.57
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 3490.520 3490.520 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 3490.52 3490.52 0.295376 15.11 10.97 0.00675248 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 21.8779 21.11 0.00800000 49.5265 1086.30 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6311.131 4911.098 0.317490 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 6121.46 5054.27 0.317490 26.37 17.88 0.00979463 12.80 11.77 0.00850000 33.83 0.01447222 23.39 15.4297 23.89 0.00894180 46.6854 3472.44 0.00 6310.05 4818.10
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6311.131 6311.131 0.317490 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6311.13 6311.13 0.317490 16.88 11.95 0.00699842 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.4297 21.11 0.00785603 48.6475 3250.77 0.00 6319.43 6319.43
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 5410.558 5410.558 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5410.56 5410.56 0.317490 16.88 11.95 0.00699842 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.4297 21.11 0.00785603 48.6475 3250.77 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4573.494 3660.754 0.250564 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 4452.82 3811.92 0.250564 25.77 17.44 0.00949128 12.80 11.77 0.00850000 31.98 0.01446884 22.89 11.5979 23.89 0.00883846 46.1525 2741.44 0.00 4572.71 3588.75
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4573.494 4573.494 0.250564 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4573.49 4573.49 0.250564 17.93 12.57 0.00720553 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 11.5979 21.11 0.00784940 48.6070 2069.30 0.00 4579.50 4579.50
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 3376.233 3376.233 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3376.23 3376.23 0.250564 17.93 12.57 0.00720553 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 11.5979 21.11 0.00784940 48.6070 2069.30 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6182.043 4803.927 0.309892 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 6007.09 4940.97 0.309892 26.38 17.91 0.00982449 12.80 11.77 0.00850000 33.70 0.01447198 23.36 15.8080 23.89 0.00895262 46.7407 3389.19 0.00 6180.98 4712.47
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6182.043 6182.043 0.309892 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6182.04 6182.04 0.309892 16.78 11.89 0.00697675 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.8080 21.11 0.00785528 48.6429 3233.42 0.00 6190.17 6190.17
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 5390.039 5390.039 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5390.04 5390.04 0.309892 16.78 11.89 0.00697675 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.8080 21.11 0.00785528 48.6429 3233.42 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5149.800 4122.074 0.289758 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 4998.95 4356.71 0.289758 25.63 17.29 0.00936117 12.80 11.77 0.00850000 31.88 0.01446866 22.87 10.0291 23.89 0.00879140 45.9102 3172.21 0.00 5148.92 4041.18
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5149.800 5149.800 0.289758 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5149.80 5149.80 0.289758 18.36 12.83 0.00729386 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 10.0291 21.11 0.00785078 48.6155 2088.88 0.00 5156.57 5156.57
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 3399.390 3399.390 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3399.39 3399.39 0.289758 18.36 12.83 0.00729386 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 10.0291 21.11 0.00785078 48.6155 2088.88 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6333.250 4748.953 0.295376 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.8739 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.295376 0.34292473   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 Sensible 6244.63 4902.42 0.9860 0.34292473 0.295376 26.92 18.41 0.01023904 53173.3 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 330.853 5913.78 33.45 0.01447152 23.29 0.06462205 21.8779 23.89 0.00905374 23.89 0.00906047 47.2966 3203.83 0.00 6332.16 4663.50 0.32938179 26.67 19.44 0.01118466 55322.4 12.81 12.79 0.00919838 36098.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6333.250 6333.250 0.295376 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.295376 0.34292473   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6333.25 6333.25 1.0000 0.34292473 0.295376 15.11 10.97 0.00675248 32263.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6333.25 -6.30 0.00229779 -6.30 0.06462205 21.8779 21.11 0.00800000 21.11 0.00800000 49.5265 1086.30 0.00 6341.57 6341.57 0.33686514 21.11 15.56 0.00875166 43444.1 39.55 21.59 0.00875166 62269.4
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3490.520 3490.520 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.295376 0.34292473   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 3490.52 3490.52 1.0000 0.34292473 0.295376 15.11 10.97 0.00675248 32263.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3490.52 -6.30 0.00229779 -6.30 0.06462205 21.8779 21.11 0.00800000 21.11 0.00800000 49.5265 1086.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6311.131 4911.098 0.317490 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.0477 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.317490 0.36859841   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 6121.46 5054.27 0.9699 0.36859841 0.317490 26.37 17.88 0.00979463 51469.6 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 355.623 5765.84 33.83 0.01447222 23.39 0.04898769 15.4297 23.89 0.00894122 23.89 0.00894180 46.6854 3472.44 0.00 6310.05 4818.10 0.35404156 26.67 19.44 0.01118466 55322.4 13.36 13.34 0.00953242 37499.5
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6311.131 6311.131 0.317490 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.317490 0.36859841   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6311.13 6311.13 1.0000 0.36859841 0.317490 16.88 11.95 0.00699842 34684.3 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6311.13 -6.30 0.00229779 -6.30 0.04898769 15.4297 21.11 0.00785603 21.11 0.00785603 48.6475 3250.77 0.00 6319.43 6319.43 0.36208516 21.11 15.56 0.00875166 43444.1 38.20 21.19 0.00875166 60897.0
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5410.558 5410.558 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.317490 0.36859841   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5410.56 5410.56 1.0000 0.36859841 0.317490 16.88 11.95 0.00699842 34684.3 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5410.56 -6.30 0.00229779 -6.30 0.04898769 15.4297 21.11 0.00785603 21.11 0.00785603 48.6475 3250.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4573.494 3660.754 0.250564 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.4838 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.250564 0.29089883   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 4452.82 3811.92 0.9736 0.29089883 0.250564 25.77 17.44 0.00949128 50087.7 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 280.659 4172.17 31.98 0.01446884 22.89 0.02906013 11.5979 23.89 0.00883825 23.89 0.00883846 46.1525 2741.44 0.00 4572.71 3588.75 0.27941053 26.67 19.44 0.01118466 55322.4 14.11 13.89 0.00980394 38956.8
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4573.494 4573.494 0.250564 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.250564 0.29089883   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4573.49 4573.49 1.0000 0.29089883 0.250564 17.93 12.57 0.00720553 36278.2 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4573.49 -6.30 0.00229779 -6.30 0.02906013 11.5979 21.11 0.00784940 21.11 0.00784940 48.6070 2069.30 0.00 4579.50 4579.50 0.28575856 21.11 15.56 0.00875166 43444.1 36.81 20.77 0.00875166 59469.9
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3376.233 3376.233 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.250564 0.29089883   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3376.23 3376.23 1.0000 0.29089883 0.250564 17.93 12.57 0.00720553 36278.2 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3376.23 -6.30 0.00229779 -6.30 0.02906013 11.5979 21.11 0.00784940 21.11 0.00784940 48.6070 2069.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6182.043 4803.927 0.309892 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.1032 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309892 0.35977727   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 Sensible 6007.09 4940.97 0.9717 0.35977727 0.309892 26.38 17.91 0.00982449 51563.7 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 347.112 5659.98 33.70 0.01447198 23.36 0.04898769 15.8080 23.89 0.00895187 23.89 0.00895262 46.7407 3389.19 0.00 6180.98 4712.47 0.34556879 26.67 19.44 0.01118466 55322.4 13.33 13.31 0.00951850 37436.0
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6182.043 6182.043 0.309892 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309892 0.35977727   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6182.04 6182.04 1.0000 0.35977727 0.309892 16.78 11.89 0.00697675 34523.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6182.04 -6.30 0.00229779 -6.30 0.04898769 15.8080 21.11 0.00785528 21.11 0.00785528 48.6429 3233.42 0.00 6190.17 6190.17 0.35341989 21.11 15.56 0.00875166 43444.1 38.26 21.21 0.00875166 60959.2
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5390.039 5390.039 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309892 0.35977727   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5390.04 5390.04 1.0000 0.35977727 0.309892 16.78 11.89 0.00697675 34523.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5390.04 -6.30 0.00229779 -6.30 0.04898769 15.8080 21.11 0.00785528 21.11 0.00785528 48.6429 3233.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5149.800 4122.074 0.289758 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.2420 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.289758 0.33640189   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 4998.95 4356.71 0.9707 0.33640189 0.289758 25.63 17.29 0.00936117 49616.9 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 324.560 4674.39 31.88 0.01446866 22.87 0.02906013 10.0291 23.89 0.00879184 23.89 0.00879140 45.9102 3172.21 0.00 5148.92 4041.18 0.32311656 26.67 19.44 0.01118466 55322.4 14.44 14.05 0.00984051 39387.2
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5149.800 5149.800 0.289758 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.289758 0.33640189   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5149.80 5149.80 1.0000 0.33640189 0.289758 18.36 12.83 0.00729386 36940.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5149.80 -6.30 0.00229779 -6.30 0.02906013 10.0291 21.11 0.00785078 21.11 0.00785078 48.6155 2088.88 0.00 5156.57 5156.57 0.33045757 21.11 15.56 0.00875166 43444.1 36.39 20.65 0.00875166 59048.4
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3399.390 3399.390 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.289758 0.33640189   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3399.39 3399.39 1.0000 0.33640189 0.289758 18.36 12.83 0.00729386 36940.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3399.39 -6.30 0.00229779 -6.30 0.02906013 10.0291 21.11 0.00785078 21.11 0.00785078 48.6155 2088.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2553.17 2343.67 1036.67
PERIMETER_ZN_1 2500.17 2681.17 1293.00
PERIMETER_ZN_2 2244.83 2239.33 1185.00
PERIMETER_ZN_3 2697.00 2756.17 1464.33
PERIMETER_ZN_4 2701.00 2618.50 1357.67
ATTIC 0.00 0.00 0.00
Facility 3218.17 3056.33 1832.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 77.83 0.00 77.83
PERIMETER_ZN_1 5.83 37.50 4.50 37.50
PERIMETER_ZN_2 7.67 3.17 0.00 2.83
PERIMETER_ZN_3 9.33 4.50 0.17 4.50
PERIMETER_ZN_4 8.67 4.33 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 26.50 107.67 4.67 103.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.397 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.396 0.371 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.370 0.016 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.396 0.013 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.396 0.015 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.046
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.021
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.021
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.156


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.55 0.00 762126.55 0.00 762126.55 1606483.19 5484.00 2016.00 1260.00 0.00
PERIMETER_ZN_1 579939.95 0.00 579939.95 577686.13 1157626.07 1217818.28 5477.82 2016.25 1265.93 29.25
PERIMETER_ZN_2 345217.79 0.00 345217.79 36850.63 382068.41 702184.69 5476.03 1512.17 1771.80 835.95
PERIMETER_ZN_3 583605.09 0.00 583605.09 55275.94 638881.03 1217818.28 5469.29 2016.28 1274.43 78.77
PERIMETER_ZN_4 345432.50 0.00 345432.50 36850.63 382283.12 722425.48 5478.30 2016.38 1265.32 103.54
Total Facility 2616321.87 0.00 2616321.87 706663.32 3322985.19 5466729.92 5484.00 2017.08 1786.88 921.46


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0565 1008.00 2016.00 1260.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0351 0.0726 0.0428 1008.00 2016.00 1260.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0009 0.0217 0.0249 1008.00 1512.00 1008.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0013 0.0387 0.0428 1008.00 2016.00 1260.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0008 0.0231 0.0254 1008.00 2016.00 1260.00
Total Facility 0.1673 0.0000 0.1673 0.0382 0.2055 0.1925 1008.00 2016.00 1764.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1027244.87 0.00 1027244.87 1606483.19 5484.00 0.00 3276.00 0.00
PSZ-AC:2 781681.64 0.00 781681.64 1217818.28 5476.03 0.06 3283.92 28.92
PSZ-AC:3 465307.50 0.00 465307.50 702184.69 5472.35 0.22 3287.43 834.55
PSZ-AC:4 786621.76 0.00 786621.76 1217818.28 5460.08 0.47 3299.45 77.60
PSZ-AC:5 465596.90 0.00 465596.90 722425.48 5471.73 0.33 3287.93 101.88


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0666 0.0000 0.0666 0.0565 1008.00 0.00 3276.00
PSZ-AC:2 0.0505 0.0000 0.0505 0.0428 1008.00 0.00 3276.00
PSZ-AC:3 0.0280 0.0000 0.0280 0.0249 1008.00 0.00 2520.00
PSZ-AC:4 0.0505 0.0000 0.0505 0.0428 1008.00 0.00 3276.00
PSZ-AC:5 0.0300 0.0000 0.0300 0.0254 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3304.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3354.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3353.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3377.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0871 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0660 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0392 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0660 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0392 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 524
Defaulted Fields 360
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
Electricity:Building 74.76 896.82 24-JUN-13:30 5350.52 30-OCT-07:10
Electricity:Zone:CORE_ZN 22.64 284.81 01-JAN-00:10 1566.66 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.76 896.82 24-JUN-13:30 5350.52 30-OCT-07:10
InteriorLights:Electricity 26.47 329.18 24-JUN-13:30 2025.22 30-OCT-07:10
InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.47 329.18 24-JUN-13:30 2025.22 30-OCT-07:10
LightsWired:InteriorLights:Electricity 26.47 329.18 24-JUN-13:30 2025.22 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.47 329.18 24-JUN-13:30 2025.22 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_1 16.16 191.62 01-JAN-11:20 1187.49 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.44 65.63 01-JAN-11:20 449.44 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.44 65.63 01-JAN-11:20 449.44 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_2 9.70 113.67 08-JAN-10:50 704.44 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.34 38.93 08-JAN-10:50 266.62 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.34 38.93 08-JAN-10:50 266.62 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_3 16.56 192.39 20-MAY-15:30 1187.50 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.84 66.41 20-MAY-15:30 449.45 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.84 66.41 20-MAY-15:30 449.45 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_4 9.72 113.67 14-JAN-14:40 704.44 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.36 38.93 14-JAN-14:40 266.62 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.36 38.93 14-JAN-14:40 266.62 30-OCT-07:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
ElectricityPurchased:Plant 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
Cogeneration:ElectricityPurchased 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
General:Cogeneration:ElectricityPurchased 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
ElectricityNet:Plant 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
Cogeneration:ElectricityNet 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
General:Cogeneration:ElectricityNet 153.51 1468.82 24-JUN-13:30 18215.90 06-FEB-08:30
ExteriorLights:Electricity 9.88 0.00 01-JAN-07:50 1049.10 01-JAN-06:10
General:ExteriorLights:Electricity 9.88 0.00 01-JAN-07:50 1049.10 01-JAN-06:10
Electricity:HVAC 45.26 0.00 01-JAN-00:10 10142.52 06-FEB-08:30
Fans:Electricity 19.45 0.00 01-JAN-00:10 1638.81 02-JAN-06:20
General:Fans:Electricity 19.45 0.00 01-JAN-00:10 1638.81 02-JAN-06:20
Cooling:Electricity 19.87 0.00 01-JAN-00:10 6744.64 07-JUL-16:00
General:Cooling:Electricity 19.87 0.00 01-JAN-00:10 6744.64 07-JUL-16:00
Heating:Electricity 5.95 0.00 01-JAN-00:10 8503.71 06-FEB-08:30
General:Heating:Electricity 5.95 0.00 01-JAN-00:10 8503.71 06-FEB-08:30
Electricity:Plant 23.61 572.00 07-APR-09:30 2802.39 02-FEB-12:40
WaterSystems:Electricity 23.61 572.00 07-APR-09:30 2802.39 02-FEB-12:40
Water Heater:WaterSystems:Electricity 23.61 572.00 07-APR-09:30 2802.39 02-FEB-12:40
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 10-JAN-11:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 10-JAN-11:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1.27 0.00 01-JAN-00:10 20389.14 13-FEB-07:10
NaturalGas:HVAC 1.27 0.00 01-JAN-00:10 20389.14 13-FEB-07:10
Heating:NaturalGas 1.27 0.00 01-JAN-00:10 20389.14 13-FEB-07:10
General:Heating:NaturalGas 1.27 0.00 01-JAN-00:10 20389.14 13-FEB-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 10-JAN-12:10
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 10-JAN-12:10
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 03-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 03-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 177.89 0.00 01-JAN-00:10 57703.50 09-JAN-07:10
EnergyTransfer:Building 74.80 0.00 01-JAN-00:10 26543.73 09-JAN-07:10
EnergyTransfer:Zone:CORE_ZN 19.56 0.00 01-JAN-00:10 5146.13 02-JAN-07:10
Heating:EnergyTransfer 11.28 0.00 01-JAN-00:10 26543.73 09-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.64 0.00 01-JAN-00:10 5146.13 02-JAN-07:10
General:Heating:EnergyTransfer 11.28 0.00 01-JAN-00:10 26543.73 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.64 0.00 01-JAN-00:10 5146.13 02-JAN-07:10
Cooling:EnergyTransfer 63.52 0.00 01-JAN-00:10 19908.82 17-JUL-07:20
Cooling:EnergyTransfer:Zone:CORE_ZN 18.93 0.00 01-JAN-00:10 4680.34 25-SEP-07:10
General:Cooling:EnergyTransfer 63.52 0.00 01-JAN-00:10 19908.82 17-JUL-07:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 18.93 0.00 01-JAN-00:10 4680.34 25-SEP-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 18.17 0.00 01-JAN-00:10 7902.06 09-JAN-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.21 0.00 01-JAN-00:10 7902.06 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.21 0.00 01-JAN-00:10 7902.06 09-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 14.97 0.00 01-JAN-00:10 5156.86 11-OCT-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 14.97 0.00 01-JAN-00:10 5156.86 11-OCT-16:00
EnergyTransfer:Zone:PERIMETER_ZN_2 11.15 0.00 01-JAN-00:10 4188.58 13-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.85 0.00 01-JAN-00:10 4188.58 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.85 0.00 01-JAN-00:10 4188.58 13-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 9.29 0.00 01-JAN-00:10 3710.01 10-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 9.29 0.00 01-JAN-00:10 3710.01 10-JUL-10:10
EnergyTransfer:Zone:PERIMETER_ZN_3 15.41 0.00 01-JAN-00:10 6671.64 13-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.60 0.00 01-JAN-00:10 6671.64 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.60 0.00 01-JAN-00:10 6671.64 13-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.81 0.00 01-JAN-00:10 4515.83 17-JUL-08:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.81 0.00 01-JAN-00:10 4515.83 17-JUL-08:00
EnergyTransfer:Zone:PERIMETER_ZN_4 10.50 0.00 01-JAN-00:10 4100.65 09-JAN-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 1.99 0.00 01-JAN-00:10 4100.65 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 1.99 0.00 01-JAN-00:10 4100.65 09-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 8.51 0.00 01-JAN-00:10 3425.43 17-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 8.51 0.00 01-JAN-00:10 3425.43 17-JUL-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
EnergyTransfer:HVAC 103.10 0.00 01-JAN-00:10 31240.27 13-FEB-07:10
CoolingCoils:EnergyTransfer 89.20 0.00 01-JAN-00:10 30823.39 21-AUG-07:10
HeatingCoils:EnergyTransfer 13.90 0.00 01-JAN-00:10 31240.27 13-FEB-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 02-FEB-07:10 89.10 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.638 -18.926 0.000 0.000 5.096 8.499 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -9.448
PERIMETER_ZN_1 0.000 0.000 3.205 -14.967 0.000 0.000 3.917 5.439 10.719 14.493 0.000 0.733 0.000 0.000 -7.433 0.000 -4.713 -11.393
PERIMETER_ZN_2 0.000 0.000 1.853 -9.293 0.000 0.000 1.706 3.338 6.359 6.950 0.000 0.011 0.000 0.000 -3.881 0.000 -0.357 -6.685
PERIMETER_ZN_3 0.000 0.000 3.597 -11.814 0.000 0.000 3.972 5.836 10.719 4.397 0.000 0.020 0.000 0.000 -6.145 0.000 -0.518 -10.065
PERIMETER_ZN_4 0.000 0.000 1.987 -8.514 0.000 0.000 2.330 3.357 6.359 7.033 0.000 0.011 0.000 0.000 -4.214 0.000 -0.366 -7.982
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9.679 29.991 0.000 0.000 0.000 -39.670 -0.000
Total Facility 0.000 0.000 11.280 -63.514 0.000 0.000 17.021 26.469 48.296 32.873 0.000 10.454 29.991 0.000 -21.673 0.000 -45.624 -45.573


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 12-OCT-07:03 0.00 0.00 0.00 -6144.49 0.00 0.00 533.58 593.08 973.59 0.00 0.00 0.00 4044.25 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 11-OCT-16:00 0.00 0.00 0.00 -5170.61 0.00 0.00 421.64 328.16 738.04 1837.78 0.00 46.78 1798.21 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_2 08-JUN-07:02 0.00 0.00 0.00 -4302.91 0.00 0.00 232.33 194.67 437.82 1651.32 0.00 0.00 1791.77 0.00 -0.00 0.00 -5.00 0.00
PERIMETER_ZN_3 19-SEP-07:02 0.00 0.00 0.00 -5194.02 0.00 0.00 401.83 430.57 738.04 0.00 0.00 0.00 3833.11 0.00 -205.40 0.00 -4.13 0.00
PERIMETER_ZN_4 15-SEP-07:02 0.00 0.00 0.00 -4477.99 0.00 0.00 231.42 256.32 437.82 0.00 0.00 0.00 3715.11 0.00 -162.67 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JUN-07:02 0.00 0.00 0.00 -22721.86 0.00 0.00 1718.26 1796.86 3325.31 1829.85 0.00 650.47 13469.09 0.00 0.00 0.00 -67.99 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:01 0.00 0.00 8023.55 0.00 0.00 0.00 88.20 151.56 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8750.11
PERIMETER_ZN_1 02-JAN-06:01 0.00 0.00 8836.75 0.00 0.00 0.00 68.19 114.89 369.02 0.00 0.00 0.00 0.00 0.00 -479.80 0.00 -341.27 -8567.78
PERIMETER_ZN_2 02-JAN-06:01 0.00 0.00 6813.87 0.00 0.00 0.00 40.45 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -259.09 0.00 -23.14 -6859.16
PERIMETER_ZN_3 02-JAN-06:01 0.00 0.00 8626.85 0.00 0.00 0.00 68.19 114.89 369.02 0.00 0.00 0.00 0.00 0.00 -397.21 0.00 -33.97 -8747.77
PERIMETER_ZN_4 02-JAN-06:01 0.00 0.00 7293.67 0.00 0.00 0.00 40.45 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -264.69 0.00 -23.27 -7333.23
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-06:01 0.00 0.00 39594.69 0.00 0.00 0.00 305.49 517.66 1662.65 0.00 0.00 370.82 0.00 0.00 -1400.79 0.00 -421.65 -40628.88



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2954 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2954 0.2188 1.0000 Not calculated 0.0646 0.2188    
PSZ-AC:2 0.3175 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3175 0.1543 1.0000 Not calculated 0.0490 0.1543    
PSZ-AC:3 0.2506 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2506 0.1160 1.0000 Not calculated 0.0291 0.1160    
PSZ-AC:4 0.3099 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3099 0.1581 1.0000 Not calculated 0.0490 0.1581    
PSZ-AC:5 0.2898 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2898 0.1003 1.0000 Not calculated 0.0291 0.1003    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2954 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2954 1.0000 1.0000 Not calculated 0.0646 0.2188    
PSZ-AC:2 0.3175 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3175 1.0000 1.0000 Not calculated 0.0490 0.1543    
PSZ-AC:3 0.2506 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2506 1.0000 1.0000 Not calculated 0.0291 0.1160    
PSZ-AC:4 0.3099 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3099 1.0000 1.0000 Not calculated 0.0490 0.1581    
PSZ-AC:5 0.2898 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2898 1.0000 1.0000 Not calculated 0.0291 0.1003    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.002360 8.0545 0.000305 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.002360 8.05 0.000305 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2954 0.2954 0.2954 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3175 0.3175 0.3175 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2506 0.2506 0.2506 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3099 0.3099 0.3099 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2898 0.2898 0.2898 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2954 0.2954 0.2954 0.2954 0.0646 1.0000
PSZ-AC:2 0.3175 0.3175 0.3175 0.3175 0.0490 1.0000
PSZ-AC:3 0.2506 0.2506 0.2506 0.2506 0.0291 1.0000
PSZ-AC:4 0.3099 0.3099 0.3099 0.3099 0.0490 1.0000
PSZ-AC:5 0.2898 0.2898 0.2898 0.2898 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2954 0.2954 0.2954 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3175 0.3175 0.3175 No 0.0490 0.2808 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2506 0.2506 0.2506 No 0.0291 0.2617 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3099 0.3099 0.3099 No 0.0490 0.2823 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2898 0.2898 0.2898 No 0.0291 0.2593 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2954 0.2954 0.2954 0.2954 0.0646 1.0000
PSZ-AC:2 0.3175 0.3175 0.3175 0.3175 0.0490 1.0000
PSZ-AC:3 0.2506 0.2506 0.2506 0.2506 0.0291 1.0000
PSZ-AC:4 0.3099 0.3099 0.3099 0.3099 0.0490 1.0000
PSZ-AC:5 0.2898 0.2898 0.2898 0.2898 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 4.67
Number of hours cooling loads not met 103.00
Number of hours not met 107.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 5.95 8503.71 1.27 20389.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 19.87 6744.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.47 2025.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.88 1049.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 19.45 1638.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.61 2802.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 153.51
Natural Gas 0.00 1.27
Additional 0.00 0.00
Total 48.30 154.78


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.78
Space Heating 11.64
Space Cooling 38.86
Fans (All) 38.05
Service Water Heating 46.19
Receptacle Equipment 94.48
Miscellaneous (All) 300.33
Subtotal 300.33


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 2.48
Service Water Heating 0.00
Miscellaneous (All) 2.48
Subtotal 2.48


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 17.10
Space Heating 4.66
Space Cooling 12.83
Fans (All) 12.56
Service Water Heating 15.25
Receptacle Equipment 31.20
Miscellaneous 6.38


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2635. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 7299.83 1460.17 0.00 0.00 0.00
PERIMETER_ZN_1 7424.00 1336.00 0.00 0.00 0.00
PERIMETER_ZN_2 7406.00 1354.00 0.00 0.00 0.00
PERIMETER_ZN_3 7648.17 1111.83 0.00 0.00 0.00
PERIMETER_ZN_4 7246.50 1513.50 0.00 0.00 0.00
ATTIC 6221.67 613.67 626.83 749.17 548.67
Min 6221.67 613.67 0.00 0.00 0.00
Max 7648.17 1513.50 626.83 749.17 548.67
Average 7207.69 1231.53 104.47 124.86 91.44
Sum 43246.17 7389.17 626.83 749.17 548.67


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 5933.83 2826.17 0.00 0.00 0.00
PERIMETER_ZN_1 6466.83 2293.17 0.00 0.00 0.00
PERIMETER_ZN_2 6588.83 2171.17 0.00 0.00 0.00
PERIMETER_ZN_3 6686.17 2073.83 0.00 0.00 0.00
PERIMETER_ZN_4 6550.50 2209.50 0.00 0.00 0.00
ATTIC 5748.00 1450.50 388.00 335.83 837.67
Min 5748.00 1450.50 0.00 0.00 0.00
Max 6686.17 2826.17 388.00 335.83 837.67
Average 6329.03 2170.72 64.67 55.97 139.61
Sum 37974.17 13024.33 388.00 335.83 837.67


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17278.67 613.33 0.00 0.00 0.00
PERIMETER_ZN_1 12793.83 562.17 0.00 0.00 0.00
PERIMETER_ZN_2 4722.50 65.50 0.00 0.00 0.00
PERIMETER_ZN_3 13033.17 322.83 0.00 0.00 0.00
PERIMETER_ZN_4 6741.67 62.33 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17278.67 613.33 0.00 0.00 0.00
Average 9094.97 271.03 0.00 0.00 0.00
Sum 54569.83 1626.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:03

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.358039E+09 1761.03 26-JAN-08:05 -5.4 -7.4 0.228469E+09 390.46 20-JAN-16:00 -5.4 -7.4
February 0.440301E+09 1766.08 03-FEB-06:02 -8.4 -9.9 0.223728E+09 404.31 21-FEB-15:20 22.60 11.20
March 0.859114E+09 4411.14 31-MAR-07:03 17.88 16.12 0.314214E+09 440.91 31-MAR-07:10 17.88 16.12
April 0.112425E+10 5113.31 18-APR-07:03 14.32 12.63 0.282688E+09 444.65 19-APR-07:10 16.28 14.49
May 0.182660E+10 5248.73 17-MAY-07:02 17.57 13.83 0.315727E+09 469.22 08-MAY-07:10 17.57 13.83
June 0.268311E+10 6025.72 08-JUN-07:02 14.45 9.54 0.319372E+09 469.21 28-JUN-07:10 23.17 20.05
July 0.278894E+10 4862.25 25-JUL-06:02 21.10 18.18 0.295348E+09 469.21 18-JUL-07:10 21.10 18.18
August 0.316886E+10 4698.15 28-AUG-06:02 21.10 20.28 0.340747E+09 469.22 14-AUG-07:10 21.10 20.28
September 0.237793E+10 5518.88 14-SEP-07:02 13.17 11.75 0.289785E+09 469.22 20-SEP-07:10 16.47 13.40
October 0.167241E+10 6144.78 12-OCT-07:03 7.67 5.95 0.299396E+09 469.22 10-OCT-07:10 7.67 5.95
November 0.103076E+10 2739.62 03-NOV-07:03 13.40 12.69 0.290492E+09 412.81 03-NOV-07:10 13.40 12.69
December 0.595901E+09 1763.14 18-DEC-08:05 -5.0 -6.8 0.244801E+09 403.83 11-DEC-14:50 -5.0 -6.8
                     
Annual Sum or Average 0.189262E+11         0.344477E+10        
Minimum of Months 0.358039E+09 1761.03   -8.4 -9.9 0.223728E+09 390.46   -5.4 -7.4
Maximum of Months 0.316886E+10 6144.78   21.10 20.28 0.340747E+09 469.22   23.17 20.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.132874E+09 979.94 06-JAN-06:03 -4.4 -7.1 0.175892E+09 304.99 31-JAN-14:39 20.93 13.10
February 0.246500E+09 2317.86 28-FEB-15:30 24.15 13.12 0.166486E+09 304.99 22-FEB-15:50 24.15 13.12
March 0.448277E+09 2961.74 30-MAR-15:00 27.80 17.08 0.222329E+09 305.11 28-MAR-12:20 27.80 17.08
April 0.498216E+09 2583.59 17-APR-16:08 28.80 16.45 0.201909E+09 305.02 19-APR-14:00 26.70 17.60
May 0.985957E+09 3755.53 30-MAY-07:02 22.07 19.14 0.234566E+09 319.18 30-MAY-07:10 22.07 19.14
June 0.212876E+10 4950.59 06-JUN-07:02 21.57 16.07 0.240587E+09 355.70 26-JUN-07:10 23.48 21.74
July 0.242482E+10 4757.12 17-JUL-16:05 32.30 21.89 0.220603E+09 355.69 14-JUL-07:10 32.30 21.89
August 0.305536E+10 4748.26 29-AUG-16:05 32.20 22.08 0.256562E+09 355.70 14-AUG-07:10 32.20 22.08
September 0.221615E+10 5089.54 25-SEP-06:02 19.40 16.66 0.219938E+09 355.69 07-SEP-07:10 19.40 16.66
October 0.155594E+10 5171.09 11-OCT-16:00 26.10 17.12 0.221580E+09 333.80 11-OCT-07:10 26.10 17.12
November 0.889692E+09 4118.25 06-NOV-14:30 20.60 10.97 0.212057E+09 305.02 01-NOV-13:30 20.60 10.97
December 0.385028E+09 2482.49 12-DEC-14:20 22.80 16.78 0.184654E+09 305.00 14-DEC-16:10 14.82 10.69
                     
Annual Sum or Average 0.149676E+11         0.255716E+10        
Minimum of Months 0.132874E+09 979.94   -4.4 -7.1 0.166486E+09 304.99   14.82 10.69
Maximum of Months 0.305536E+10 5171.09   32.30 22.08 0.256562E+09 355.70   32.30 22.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4777028.08 571.31 26-JAN-06:05 -5.0 -6.9 72841820.33 169.45 31-JAN-16:00 19.40 13.37
February 34590655.72 626.00 03-FEB-06:05 -8.4 -9.9 70432830.67 182.71 21-FEB-15:20 22.60 11.20
March 0.154631E+09 1063.14 30-MAR-15:47 27.80 17.41 96437356.00 180.94 30-MAR-14:30 27.80 17.41
April 0.366124E+09 1595.54 17-APR-10:24 24.20 15.92 90145961.30 181.06 11-APR-08:09 24.20 15.92
May 0.839069E+09 3752.10 18-MAY-07:02 18.95 15.19 0.103471E+09 211.06 30-MAY-07:10 22.07 19.14
June 0.159657E+10 4302.79 08-JUN-07:02 14.45 9.54 0.105857E+09 211.00 28-JUN-07:10 23.17 20.05
July 0.180137E+10 3712.35 10-JUL-10:06 27.48 20.82 96900021.57 211.17 28-JUL-07:10 19.40 19.40
August 0.205812E+10 3534.06 14-AUG-10:02 27.98 22.40 0.111534E+09 211.00 07-AUG-07:10 27.98 22.40
September 0.137479E+10 4028.14 15-SEP-07:02 15.65 12.98 95894455.74 211.00 01-SEP-07:10 15.65 12.98
October 0.724392E+09 3713.13 10-OCT-07:02 15.65 14.73 96706283.12 211.00 19-OCT-07:10 19.40 19.12
November 0.275221E+09 1048.76 06-NOV-11:04 17.30 12.97 90647311.79 180.93 06-NOV-13:20 19.47 12.50
December 63332504.61 601.28 01-DEC-08:05 -2.9 -4.1 75027617.41 180.92 14-DEC-16:10 14.82 10.69
                     
Annual Sum or Average 0.929298E+10         0.110590E+10        
Minimum of Months 4777028.08 571.31   -8.4 -9.9 70432830.67 169.45   14.82 10.69
Maximum of Months 0.205812E+10 4302.79   27.98 22.40 0.111534E+09 211.17   27.98 22.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8326099.76 1052.95 26-JAN-06:05 -5.0 -6.9 0.168161E+09 277.53 20-JAN-16:00 -5.0 -6.9
February 34134673.17 1200.38 03-FEB-06:05 -8.4 -9.9 0.158140E+09 304.99 28-FEB-16:19 23.50 12.67
March 0.186003E+09 1513.19 30-MAR-15:57 27.80 17.47 0.212997E+09 305.72 29-MAR-10:09 27.80 17.47
April 0.353299E+09 1691.91 19-APR-14:55 26.70 17.60 0.202209E+09 307.43 27-APR-13:00 21.70 11.95
May 0.990634E+09 4721.58 18-MAY-07:02 18.95 15.19 0.236430E+09 338.47 30-MAY-07:10 22.07 19.14
June 0.205742E+10 5146.93 07-JUN-07:02 14.68 11.67 0.241157E+09 355.70 26-JUN-07:10 23.48 21.74
July 0.234425E+10 4799.01 25-JUL-06:02 21.10 18.18 0.220333E+09 355.70 27-JUL-07:10 21.70 21.64
August 0.276660E+10 4437.08 28-AUG-06:02 21.10 20.28 0.253613E+09 355.70 14-AUG-07:10 21.10 20.28
September 0.174423E+10 5194.44 19-SEP-07:02 16.38 13.19 0.218489E+09 355.70 01-SEP-07:10 16.38 13.19
October 0.855232E+09 4426.08 11-OCT-07:02 17.38 15.92 0.220244E+09 355.69 19-OCT-07:10 19.40 19.12
November 0.371261E+09 1286.95 03-NOV-15:10 21.60 17.31 0.202571E+09 305.19 27-NOV-15:39 22.20 17.93
December 0.102712E+09 1132.27 01-DEC-07:04 -3.8 -4.7 0.168412E+09 304.99 13-DEC-13:30 19.45 17.14
                     
Annual Sum or Average 0.118141E+11         0.250276E+10        
Minimum of Months 8326099.76 1052.95   -8.4 -9.9 0.158140E+09 277.53   -5.0 -6.9
Maximum of Months 0.276660E+10 5194.44   27.80 20.28 0.253613E+09 355.70   27.80 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 17828032.80 595.17 26-JAN-07:04 -5.1 -7.1 0.100718E+09 178.40 20-JAN-16:00 -5.1 -7.1
February 32375294.83 983.08 28-FEB-16:45 23.80 12.87 96155225.77 180.92 28-FEB-13:09 23.80 12.87
March 0.149567E+09 1698.76 30-MAR-15:57 27.80 17.47 0.131535E+09 187.25 31-MAR-07:10 17.88 16.12
April 0.289235E+09 1864.55 17-APR-15:57 28.90 16.41 0.122824E+09 180.95 03-APR-12:50 28.90 16.41
May 0.724113E+09 4083.97 18-MAY-07:02 18.95 15.19 0.141605E+09 210.19 22-MAY-07:10 17.48 17.31
June 0.142584E+10 4286.14 09-JUN-07:02 17.85 11.69 0.144005E+09 211.00 28-JUN-07:10 23.17 20.05
July 0.164815E+10 4474.60 09-JUL-18:12 32.60 22.55 0.131460E+09 211.00 26-JUL-07:10 22.38 22.32
August 0.197649E+10 4453.63 13-AUG-18:02 30.92 21.87 0.151267E+09 211.00 07-AUG-07:10 30.92 21.87
September 0.127230E+10 4478.15 15-SEP-07:02 15.65 12.98 0.130533E+09 211.00 05-SEP-07:10 15.65 12.98
October 0.657012E+09 4143.51 10-OCT-07:02 15.65 14.73 0.132430E+09 211.00 19-OCT-07:10 19.40 19.12
November 0.267348E+09 1689.86 06-NOV-16:25 19.75 10.05 0.124575E+09 180.93 06-NOV-13:39 19.75 10.05
December 54088580.36 582.78 18-DEC-07:04 -5.1 -6.9 0.103755E+09 183.28 11-DEC-15:20 -5.1 -6.9
                     
Annual Sum or Average 0.851435E+10         0.151086E+10        
Minimum of Months 17828032.80 582.78   -5.1 -7.1 96155225.77 178.40   -5.1 -7.1
Maximum of Months 0.197649E+10 4478.15   32.60 22.55 0.151267E+09 211.00   30.92 22.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70 4.97 0.00 0.00 01-JAN-00:10 5.70 4.97
February 0.00 0.00 01-FEB-00:10 9.92 7.50 0.00 0.00 01-FEB-00:10 9.92 7.50
March 0.00 0.00 01-MAR-00:10 15.32 8.51 0.00 0.00 01-MAR-00:10 15.32 8.51
April 0.00 0.00 01-APR-00:10 12.05 7.82 0.00 0.00 01-APR-00:10 12.05 7.82
May 0.00 0.00 01-MAY-00:10 16.68 16.68 0.00 0.00 01-MAY-00:10 16.68 16.68
June 0.00 0.00 01-JUN-00:10 20.93 18.59 0.00 0.00 01-JUN-00:10 20.93 18.59
July 0.00 0.00 01-JUL-00:10 22.28 21.38 0.00 0.00 01-JUL-00:10 22.28 21.38
August 0.00 0.00 01-AUG-00:10 25.13 21.87 0.00 0.00 01-AUG-00:10 25.13 21.87
September 0.00 0.00 01-SEP-00:10 21.40 18.46 0.00 0.00 01-SEP-00:10 21.40 18.46
October 0.00 0.00 01-OCT-00:10 16.85 15.92 0.00 0.00 01-OCT-00:10 16.85 15.92
November 0.00 0.00 01-NOV-00:10 9.70 6.60 0.00 0.00 01-NOV-00:10 9.70 6.60
December 0.00 0.00 01-DEC-00:10 1.80 1.51 0.00 0.00 01-DEC-00:10 1.80 1.51
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   1.80 1.51 0.00 0.00   1.80 1.51
Maximum of Months 0.00 0.00   25.13 21.87 0.00 0.00   25.13 21.87



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.287304E+09 8023.63 02-JAN-06:01 3.30
February 0.106404E+09 7431.15 07-FEB-07:01 2.30
March 10617822.60 2554.35 20-MAR-07:03 5.10
April 18494371.28 597.86 17-APR-16:03 28.80
May 24235396.16 710.97 19-MAY-16:13 30.60
June 44592032.45 928.98 06-JUN-16:03 33.90
July 44014921.31 1020.92 07-JUL-16:03 35.50
August 49538148.24 1013.67 01-AUG-16:03 35.00
September 21970388.62 751.97 07-SEP-16:03 31.52
October 6342259.54 643.19 10-OCT-16:03 29.82
November 1605343.00 2051.93 22-NOV-08:62 -2.2
December 22756682.21 7308.26 26-DEC-07:01 3.30
         
Annual Sum or Average 0.637875E+09      
Minimum of Months 1605343.00 597.86   -2.2
Maximum of Months 0.287304E+09 8023.63   35.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142418E+10 8836.95 02-JAN-06:01 3.30
February 0.847851E+09 8576.36 06-FEB-06:01 0.50
March 0.175836E+09 7640.84 06-MAR-07:02 2.80
April 0.108384E+09 7884.57 06-APR-06:02 1.20
May 36332278.15 3974.73 11-MAY-07:03 10.28
June 48578966.97 756.92 06-JUN-17:12 33.53
July 44544844.72 811.13 07-JUL-17:11 34.63
August 48320342.13 793.44 01-AUG-17:02 34.72
September 22152316.50 564.23 07-SEP-17:12 30.40
October 22144988.72 4772.22 31-OCT-07:03 7.80
November 71966064.04 7795.35 22-NOV-07:01 -3.2
December 0.354897E+09 8091.43 26-DEC-07:01 3.30
         
Annual Sum or Average 0.320519E+10      
Minimum of Months 22144988.72 564.23   -3.2
Maximum of Months 0.142418E+10 8836.95   34.72



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.895607E+09 6813.98 02-JAN-06:01 3.30
February 0.507086E+09 6482.29 07-FEB-06:02 2.20
March 68484534.81 6002.01 06-MAR-07:02 2.80
April 29212941.80 5915.54 07-APR-06:02 2.80
May 25961635.92 404.15 19-MAY-17:23 30.00
June 32130239.10 508.65 06-JUN-17:12 33.53
July 30999398.66 542.08 07-JUL-17:11 34.63
August 36749464.23 530.90 18-AUG-17:11 34.23
September 19263486.49 406.52 07-SEP-17:12 30.40
October 9460644.39 1757.93 26-OCT-07:03 2.57
November 14963341.45 5163.90 22-NOV-07:01 -3.2
December 0.183292E+09 6247.92 26-DEC-07:01 3.30
         
Annual Sum or Average 0.185321E+10      
Minimum of Months 9460644.39 404.15   -3.2
Maximum of Months 0.895607E+09 6813.98   34.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.169220E+10 8626.98 02-JAN-06:01 3.30
February 0.101139E+10 8527.42 06-FEB-06:01 0.50
March 0.143041E+09 7613.01 06-MAR-07:02 2.80
April 64826872.63 7532.47 07-APR-06:02 2.80
May 29263643.74 592.92 19-MAY-17:02 30.40
June 41443359.84 756.46 06-JUN-17:12 33.53
July 40118918.86 811.98 07-JUL-17:11 34.63
August 47684372.08 807.44 01-AUG-17:02 34.72
September 22858784.65 583.06 07-SEP-17:12 30.40
October 9934939.96 3996.96 26-OCT-07:03 2.57
November 41068922.38 7621.48 22-NOV-07:01 -3.2
December 0.453182E+09 7963.09 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.359702E+10      
Minimum of Months 9934939.96 583.06   -3.2
Maximum of Months 0.169220E+10 8626.98   34.72



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.914871E+09 7293.79 02-JAN-06:01 3.30
February 0.548157E+09 7149.41 15-FEB-07:01 4.40
March 77804957.54 4656.90 06-MAR-07:02 2.80
April 39604408.28 5042.28 06-APR-06:02 1.20
May 28011997.30 403.16 19-MAY-17:23 30.00
June 34197085.49 513.86 06-JUN-17:12 33.53
July 29261875.42 548.33 07-JUL-17:11 34.63
August 34400108.63 531.09 18-AUG-17:11 34.23
September 19908762.98 413.26 07-SEP-17:12 30.40
October 9617973.61 548.94 26-OCT-07:03 2.57
November 23991882.30 5483.62 22-NOV-07:01 -3.2
December 0.226802E+09 7170.09 26-DEC-07:01 3.30
         
Annual Sum or Average 0.198663E+10      
Minimum of Months 9617973.61 403.16   -3.2
Maximum of Months 0.914871E+09 7293.79   34.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.714248E+09 593.08 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.645736E+09 593.08 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.752015E+09 593.08 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.685116E+09 593.08 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.733131E+09 593.08 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.722883E+09 593.08 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.695364E+09 593.08 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.752015E+09 593.08 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.685116E+09 593.08 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.714248E+09 593.08 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.704000E+09 593.08 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.695364E+09 593.08 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.849924E+10     0.141401E+11    
Minimum of Months 0.645736E+09 593.08   0.107295E+10 973.59  
Maximum of Months 0.752015E+09 593.08   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463697E+09 443.42 03-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.421570E+09 447.92 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.477985E+09 444.66 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.437035E+09 439.36 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.465269E+09 425.51 24-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.458445E+09 422.37 23-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.442265E+09 430.16 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.471878E+09 437.27 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.438339E+09 441.08 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.458840E+09 449.44 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.452448E+09 448.30 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.451026E+09 443.51 06-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.543880E+10     0.107191E+11    
Minimum of Months 0.421570E+09 422.37   0.813362E+09 738.04  
Maximum of Months 0.477985E+09 449.44   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.290715E+09 263.09 03-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.260989E+09 265.77 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.294868E+09 263.74 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.265721E+09 260.06 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.279970E+09 246.27 02-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.274597E+09 245.26 23-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.265393E+09 252.87 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.286407E+09 258.64 24-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.267762E+09 261.55 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.286018E+09 266.62 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.283410E+09 265.91 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.281683E+09 263.17 06-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.333753E+10     0.635872E+10    
Minimum of Months 0.260989E+09 245.26   0.482497E+09 437.82  
Maximum of Months 0.294868E+09 266.62   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.513901E+09 444.67 03-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.461795E+09 448.03 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.522082E+09 445.12 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.466067E+09 439.99 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.479893E+09 423.45 24-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.463565E+09 420.27 23-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.449808E+09 429.40 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.494005E+09 437.68 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.471789E+09 442.22 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.507848E+09 449.45 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.503636E+09 448.72 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.501737E+09 444.81 06-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.583613E+10     0.107191E+11    
Minimum of Months 0.449808E+09 420.27   0.813362E+09 738.04  
Maximum of Months 0.522082E+09 449.45   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289400E+09 263.84 03-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.261887E+09 265.77 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.295936E+09 264.18 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.267925E+09 261.74 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.282986E+09 257.70 24-MAY-07:30 0.549505E+09 437.82 01-MAY-07:10
June 0.277713E+09 253.84 23-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.268576E+09 257.30 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.289330E+09 260.57 24-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.270194E+09 262.58 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.288008E+09 266.62 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.282886E+09 266.22 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.282500E+09 263.89 06-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.335734E+10     0.635872E+10    
Minimum of Months 0.261887E+09 253.84   0.482497E+09 437.82  
Maximum of Months 0.295936E+09 266.62   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.714248E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.685116E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.733131E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.722883E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.695364E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.685116E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.714248E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.704000E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.695364E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.849924E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.463697E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.959553E+09
February 0.488155E+09 0.421570E+09 0.813362E+09 0.00 0.00 0.00 0.00 154546.16 0.701142E+09
March 0.590925E+09 0.477985E+09 0.953087E+09 0.00 0.00 0.00 0.00 3471179.70 0.500525E+09
April 0.513848E+09 0.437035E+09 0.862580E+09 0.00 0.00 0.00 0.00 22906057.54 0.286728E+09
May 0.565233E+09 0.465269E+09 0.926320E+09 0.00 0.00 0.00 0.00 58578497.51 0.175386E+09
June 0.565233E+09 0.458445E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.178297E+09 89669834.78
July 0.513848E+09 0.442265E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.187074E+09 74441103.37
August 0.590925E+09 0.471878E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.205392E+09 58531750.79
September 0.513848E+09 0.438339E+09 0.861220E+09 0.00 0.00 0.00 0.00 66224164.56 0.133949E+09
October 0.539540E+09 0.458840E+09 0.900233E+09 0.00 0.00 0.00 0.00 10967783.92 0.414717E+09
November 0.539540E+09 0.452448E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.601602E+09
December 0.513848E+09 0.451026E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.716492E+09
                   
Annual Sum or Average 0.647448E+10 0.543880E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.733065E+09 0.471274E+10
Minimum of Months 0.488155E+09 0.421570E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 58531750.79
Maximum of Months 0.590925E+09 0.477985E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.205392E+09 0.959553E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.290715E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 63772533.87
February 0.211974E+09 0.260989E+09 0.482497E+09 0.00 0.00 0.00 0.00 88728.75 53569600.99
March 0.256600E+09 0.294868E+09 0.565383E+09 0.00 0.00 0.00 0.00 155731.59 35397605.30
April 0.223130E+09 0.265721E+09 0.511694E+09 0.00 0.00 0.00 0.00 409271.05 21688879.77
May 0.245443E+09 0.279970E+09 0.549505E+09 0.00 0.00 0.00 0.00 745932.14 15982494.42
June 0.245443E+09 0.274597E+09 0.542644E+09 0.00 0.00 0.00 0.00 3278548.00 9667779.30
July 0.223130E+09 0.265393E+09 0.518151E+09 0.00 0.00 0.00 0.00 2856291.85 7691978.31
August 0.256600E+09 0.286407E+09 0.565383E+09 0.00 0.00 0.00 0.00 2836410.82 6318814.40
September 0.223130E+09 0.267762E+09 0.510887E+09 0.00 0.00 0.00 0.00 696402.00 10698800.83
October 0.234287E+09 0.286018E+09 0.534030E+09 0.00 0.00 0.00 0.00 159983.31 30754693.64
November 0.234287E+09 0.283410E+09 0.527169E+09 0.00 0.00 0.00 0.00 27442.51 41004880.88
December 0.223130E+09 0.281683E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 60676044.44
                   
Annual Sum or Average 0.281144E+10 0.333753E+10 0.635872E+10 0.00 0.00 0.00 0.00 11254742.02 0.357224E+09
Minimum of Months 0.211974E+09 0.260989E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 6318814.40
Maximum of Months 0.256600E+09 0.294868E+09 0.565383E+09 0.00 0.00 0.00 0.00 3278548.00 63772533.87



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.513901E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 94456480.75
February 0.488155E+09 0.461795E+09 0.813362E+09 0.00 0.00 0.00 0.00 349482.34 78605254.47
March 0.590925E+09 0.522082E+09 0.953087E+09 0.00 0.00 0.00 0.00 317275.35 50127450.33
April 0.513848E+09 0.466067E+09 0.862580E+09 0.00 0.00 0.00 0.00 836022.84 31190107.62
May 0.565233E+09 0.479893E+09 0.926320E+09 0.00 0.00 0.00 0.00 1479570.96 22590928.46
June 0.565233E+09 0.463565E+09 0.914754E+09 0.00 0.00 0.00 0.00 5475192.27 13809201.50
July 0.513848E+09 0.449808E+09 0.873466E+09 0.00 0.00 0.00 0.00 4812347.76 10659002.71
August 0.590925E+09 0.494005E+09 0.953087E+09 0.00 0.00 0.00 0.00 4734362.16 8649555.94
September 0.513848E+09 0.471789E+09 0.861220E+09 0.00 0.00 0.00 0.00 1270317.75 15308602.49
October 0.539540E+09 0.507848E+09 0.900233E+09 0.00 0.00 0.00 0.00 384206.83 44139904.01
November 0.539540E+09 0.503636E+09 0.888667E+09 0.00 0.00 0.00 0.00 75304.67 58864483.78
December 0.513848E+09 0.501737E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 89117098.91
                   
Annual Sum or Average 0.647448E+10 0.583613E+10 0.107191E+11 0.00 0.00 0.00 0.00 19734082.93 0.517518E+09
Minimum of Months 0.488155E+09 0.449808E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 8649555.94
Maximum of Months 0.590925E+09 0.522082E+09 0.953087E+09 0.00 0.00 0.00 0.00 5475192.27 94456480.75



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.289400E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 64222133.90
February 0.289580E+09 0.261887E+09 0.482497E+09 0.00 0.00 0.00 0.00 152492.98 53938702.42
March 0.350544E+09 0.295936E+09 0.565383E+09 0.00 0.00 0.00 0.00 106775.94 37105949.91
April 0.304821E+09 0.267925E+09 0.511694E+09 0.00 0.00 0.00 0.00 396236.98 23007652.39
May 0.335303E+09 0.282986E+09 0.549505E+09 0.00 0.00 0.00 0.00 745342.92 16725437.51
June 0.335303E+09 0.277713E+09 0.542644E+09 0.00 0.00 0.00 0.00 3080609.79 10374991.22
July 0.304821E+09 0.268576E+09 0.518151E+09 0.00 0.00 0.00 0.00 2696760.98 7862708.57
August 0.350544E+09 0.289330E+09 0.565383E+09 0.00 0.00 0.00 0.00 2587750.13 7037917.74
September 0.304821E+09 0.270194E+09 0.510887E+09 0.00 0.00 0.00 0.00 715181.41 11358427.17
October 0.320062E+09 0.288008E+09 0.534030E+09 0.00 0.00 0.00 0.00 160627.93 31621054.69
November 0.320062E+09 0.282886E+09 0.527169E+09 0.00 0.00 0.00 0.00 8293.02 41583533.75
December 0.304821E+09 0.282500E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 61116084.47
                   
Annual Sum or Average 0.384075E+10 0.335734E+10 0.635872E+10 0.00 0.00 0.00 0.00 10650072.07 0.365955E+09
Minimum of Months 0.289580E+09 0.261887E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 7037917.74
Maximum of Months 0.350544E+09 0.295936E+09 0.565383E+09 0.00 0.00 0.00 0.00 3080609.79 64222133.90



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.945958E+09 0.214551E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.823537E+09 0.219433E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.873608E+09 0.340476E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.768981E+09 0.410406E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.632105E+09 0.474041E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.645626E+09 0.460146E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.635956E+09 0.461534E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.707106E+09 0.429483E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.874334E+09 0.301306E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.821543E+09 0.275991E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.966604E+09 0.201737E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.983917E+09 0.177917E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.967927E+10 0.396702E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.632105E+09 0.177917E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.983917E+09 0.474041E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 593.08 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 593.08 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 593.08 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 593.08 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 593.08 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 593.08 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 593.08 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 593.08 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 593.08 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 593.08 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 593.08 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 593.08 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 443.42 03-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4551.03 27-JAN-08:00
February 732.70 01-FEB-08:09 447.92 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 26.12 28-FEB-15:00 4871.63 03-FEB-08:00
March 732.70 01-MAR-08:09 444.66 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 476.43 30-MAR-16:03 2817.52 06-MAR-08:00
April 732.70 03-APR-07:10 439.36 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 654.06 17-APR-16:03 3085.57 06-APR-06:10
May 732.70 01-MAY-07:10 425.51 24-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 907.56 19-MAY-16:03 2010.82 11-MAY-06:03
June 732.70 01-JUN-07:10 422.37 23-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 1334.46 06-JUN-16:03 1685.18 08-JUN-06:05
July 732.70 03-JUL-07:10 430.16 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 1536.75 07-JUL-16:03 1072.40 10-JUL-06:01
August 732.70 01-AUG-07:10 437.27 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 1473.78 01-AUG-16:03 1084.60 25-AUG-06:03
September 732.70 01-SEP-07:10 441.08 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 959.61 07-SEP-16:03 1825.01 14-SEP-06:03
October 732.70 02-OCT-07:10 449.44 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 713.91 10-OCT-16:03 2911.75 26-OCT-06:05
November 732.70 01-NOV-07:10 448.30 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3859.09 22-NOV-07:09
December 732.70 01-DEC-08:09 443.51 06-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4324.36 18-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   422.37   738.04   0.00 0.00 0.00 0.00 0.00   1072.40  
Maximum of Months 732.70   449.44   738.04   0.00 0.00 0.00 0.00 1536.75   4871.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 263.09 03-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 106.01 07-JAN-18:10
February 434.65 01-FEB-08:09 265.77 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 4.96 26-FEB-15:25 136.55 12-FEB-01:00
March 434.65 01-MAR-08:09 263.74 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 3.86 11-MAR-15:53 78.36 22-MAR-03:00
April 434.65 03-APR-07:10 260.06 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 7.11 02-APR-17:00 52.55 05-APR-18:10
May 434.65 01-MAY-07:10 246.27 02-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 6.40 19-MAY-18:10 37.92 10-MAY-04:00
June 434.65 01-JUN-07:10 245.26 23-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 17.69 06-JUN-18:10 30.56 07-JUN-03:00
July 434.65 03-JUL-07:10 252.87 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 10.43 21-JUL-18:10 24.03 28-JUL-18:05
August 434.65 01-AUG-07:10 258.64 24-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 12.55 18-AUG-18:10 19.04 07-AUG-21:00
September 434.65 01-SEP-07:10 261.55 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 5.08 06-SEP-11:53 28.97 28-SEP-18:05
October 434.65 02-OCT-07:10 266.62 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 2.74 11-OCT-14:00 59.87 24-OCT-06:00
November 434.65 01-NOV-07:10 265.91 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 6.06 19-NOV-14:55 83.23 07-NOV-02:00
December 434.65 01-DEC-08:09 263.17 06-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 130.77 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   245.26   437.82   0.00 0.00 0.00 0.00 0.00   19.04  
Maximum of Months 434.65   266.62   437.82   0.00 0.00 0.00 0.00 17.69   136.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 444.67 03-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 159.03 07-JAN-18:05
February 732.70 01-FEB-08:09 448.03 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 19.06 26-FEB-12:55 204.82 12-FEB-01:00
March 732.70 01-MAR-08:09 445.12 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 7.31 11-MAR-15:53 116.66 22-MAR-03:00
April 732.70 03-APR-07:10 439.99 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 12.75 16-APR-11:53 77.23 05-APR-18:10
May 732.70 01-MAY-07:10 423.45 24-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 10.79 19-MAY-18:10 56.48 10-MAY-04:00
June 732.70 01-JUN-07:10 420.27 23-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 28.74 11-JUN-14:55 45.03 07-JUN-03:00
July 732.70 03-JUL-07:10 429.40 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 16.11 21-JUL-18:10 35.59 28-JUL-18:10
August 732.70 01-AUG-07:10 437.68 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 20.95 06-AUG-13:53 26.31 07-AUG-21:00
September 732.70 01-SEP-07:10 442.22 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 7.63 06-SEP-12:00 42.80 28-SEP-18:10
October 732.70 02-OCT-07:10 449.45 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 9.23 08-OCT-14:00 88.12 24-OCT-06:00
November 732.70 01-NOV-07:10 448.72 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 12.20 19-NOV-14:55 122.56 07-NOV-02:00
December 732.70 01-DEC-08:09 444.81 06-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 195.23 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   420.27   738.04   0.00 0.00 0.00 0.00 0.00   26.31  
Maximum of Months 732.70   449.45   738.04   0.00 0.00 0.00 0.00 28.74   204.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 263.84 03-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 106.19 07-JAN-18:10
February 434.65 01-FEB-08:09 265.77 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 10.96 26-FEB-12:55 136.54 12-FEB-01:00
March 434.65 01-MAR-08:09 264.18 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 3.47 30-MAR-16:00 79.57 22-MAR-03:00
April 434.65 03-APR-07:10 261.74 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 7.19 16-APR-11:53 58.39 05-APR-18:10
May 434.65 01-MAY-07:10 257.70 24-MAY-07:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 6.13 07-MAY-11:55 38.92 10-MAY-04:00
June 434.65 01-JUN-07:10 253.84 23-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 16.58 11-JUN-14:55 31.39 07-JUN-03:00
July 434.65 03-JUL-07:10 257.30 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 9.28 08-JUL-18:24 25.03 28-JUL-18:05
August 434.65 01-AUG-07:10 260.57 24-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 12.55 06-AUG-13:53 18.46 07-AUG-21:00
September 434.65 01-SEP-07:10 262.58 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 5.08 06-SEP-11:53 29.64 28-SEP-18:05
October 434.65 02-OCT-07:10 266.62 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 2.88 08-OCT-14:00 61.39 24-OCT-06:00
November 434.65 01-NOV-07:10 266.22 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 3.58 19-NOV-14:55 84.58 07-NOV-02:00
December 434.65 01-DEC-08:09 263.89 06-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 130.22 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   253.84   437.82   0.00 0.00 0.00 0.00 0.00   18.46  
Maximum of Months 434.65   266.62   437.82   0.00 0.00 0.00 0.00 16.58   136.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1776.73 29-JAN-06:55 5123.61 10-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1473.36 09-FEB-08:32 5865.70 12-FEB-13:50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1635.14 19-MAR-07:23 6399.85 19-MAR-13:40
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1504.91 10-APR-06:20 7033.20 09-APR-14:20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1344.14 20-MAY-05:50 6940.33 10-MAY-14:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1617.69 11-JUN-06:03 6354.14 02-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1249.84 05-JUL-03:00 6552.73 12-JUL-14:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1291.33 10-AUG-05:10 7176.26 04-AUG-14:52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1533.05 15-SEP-07:13 6178.53 15-SEP-13:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1651.52 14-OCT-07:23 5356.45 13-OCT-13:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1654.71 23-NOV-07:30 4551.28 21-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1696.88 10-DEC-08:42 4169.36 17-DEC-13:40
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1249.84   4169.36  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1776.73   7176.26  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1761.03 26-JAN-08:05 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
February 1766.08 03-FEB-06:02 637.92 909.37 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
March 4411.14 31-MAR-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
April 5113.31 18-APR-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
May 5248.73 17-MAY-07:02 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
June 6025.72 08-JUN-07:02 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
July 4862.25 25-JUL-06:02 1217.84 1660.60 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
August 4698.15 28-AUG-06:02 1217.84 1660.60 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
September 5518.88 14-SEP-07:02 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
October 6144.78 12-OCT-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
November 2739.62 03-NOV-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
December 1763.14 18-DEC-08:05 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1761.03   637.92 909.37 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6144.78   4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 979.94 06-JAN-06:03 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 651.81
February 2317.86 28-FEB-15:30 732.70 328.16 738.04 0.00 0.00 0.00 0.00 6.04 0.00
March 2961.74 30-MAR-15:00 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 88.05 0.00
April 2583.59 17-APR-16:08 937.85 990.08 1476.09 0.00 0.00 0.00 0.00 563.08 0.00
May 3755.53 30-MAY-07:02 3663.49 1965.27 3690.21 0.00 0.00 0.00 0.00 0.00 40.58
June 4950.59 06-JUN-07:02 3663.49 2002.31 3690.21 0.00 0.00 0.00 0.00 0.00 61.90
July 4757.12 17-JUL-16:05 937.85 978.91 1476.09 0.00 0.00 0.00 0.00 1068.81 0.00
August 4748.26 29-AUG-16:05 937.85 889.66 1476.09 0.00 0.00 0.00 0.00 1031.56 0.00
September 5089.54 25-SEP-06:02 769.33 1049.03 1845.11 0.00 0.00 0.00 0.00 0.00 1004.97
October 5171.09 11-OCT-16:00 2198.10 984.47 2214.13 0.00 0.00 0.00 0.00 46.78 0.00
November 4118.25 06-NOV-14:30 732.70 328.16 738.04 0.00 0.00 0.00 0.00 0.00 77.21
December 2482.49 12-DEC-14:20 732.70 328.16 738.04 0.00 0.00 0.00 0.00 0.00 24.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 979.94   483.58 328.16 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5171.09   3663.49 2002.31 3690.21 0.00 0.00 0.00 0.00 1068.81 1004.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 571.31 26-JAN-06:05 191.24 272.62 875.63 0.00 0.00 0.00 0.00 0.00 66.32
February 626.00 03-FEB-06:05 286.87 408.94 1313.45 0.00 0.00 0.00 0.00 0.00 74.47
March 1063.14 30-MAR-15:47 1303.94 698.99 1313.45 0.00 0.00 0.00 0.00 3.43 0.00
April 1595.54 17-APR-10:24 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.13 0.00
May 3752.10 18-MAY-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 1.25
June 4302.79 08-JUN-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 5.00
July 3712.35 10-JUL-10:06 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 1.93 0.00
August 3534.06 14-AUG-10:02 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 3.66 0.00
September 4028.14 15-SEP-07:02 2173.23 1072.75 2189.08 0.00 0.00 0.00 0.00 0.00 0.00
October 3713.13 10-OCT-07:02 2173.23 1139.76 2189.08 0.00 0.00 0.00 0.00 0.00 0.60
November 1048.76 06-NOV-11:04 2173.23 985.55 2189.08 0.00 0.00 0.00 0.00 0.00 7.20
December 601.28 01-DEC-08:05 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 12.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 571.31   191.24 272.62 875.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4302.79   2173.23 1139.76 2189.08 0.00 0.00 0.00 0.00 3.66 74.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1052.95 26-JAN-06:05 322.39 459.57 1476.09 0.00 0.00 0.00 0.00 0.00 99.56
February 1200.38 03-FEB-06:05 483.58 689.36 2214.13 0.00 0.00 0.00 0.00 0.00 112.06
March 1513.19 30-MAR-15:57 2198.10 1152.39 2214.13 0.00 0.00 0.00 0.00 5.21 0.00
April 1691.91 19-APR-14:55 1465.40 737.99 1476.09 0.00 0.00 0.00 0.00 3.25 0.00
May 4721.58 18-MAY-07:02 3663.49 1886.53 3690.21 0.00 0.00 0.00 0.00 0.00 1.69
June 5146.93 07-JUN-07:02 3663.49 1844.72 3690.21 0.00 0.00 0.00 0.00 0.00 11.75
July 4799.01 25-JUL-06:02 923.20 1171.47 2214.13 0.00 0.00 0.00 0.00 0.00 3.60
August 4437.08 28-AUG-06:02 923.20 1258.84 2214.13 0.00 0.00 0.00 0.00 0.00 5.25
September 5194.44 19-SEP-07:02 3663.49 2152.83 3690.21 0.00 0.00 0.00 0.00 0.00 4.13
October 4426.08 11-OCT-07:02 3663.49 2164.41 3690.21 0.00 0.00 0.00 0.00 0.00 5.69
November 1286.95 03-NOV-15:10 732.70 408.26 738.04 0.00 0.00 0.00 0.00 0.00 1.79
December 1132.27 01-DEC-07:04 1077.07 1468.65 2583.15 0.00 0.00 0.00 0.00 0.00 20.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1052.95   322.39 408.26 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5194.44   3663.49 2164.41 3690.21 0.00 0.00 0.00 0.00 5.21 112.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 595.17 26-JAN-07:04 638.93 871.22 1532.36 0.00 0.00 0.00 0.00 0.00 17.30
February 983.08 28-FEB-16:45 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 0.09
March 1698.76 30-MAR-15:57 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 3.47 0.00
April 1864.55 17-APR-15:57 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 1.30 0.00
May 4083.97 18-MAY-07:02 2173.23 1247.24 2189.08 0.00 0.00 0.00 0.00 0.00 1.15
June 4286.14 09-JUN-07:02 2173.23 1232.05 2189.08 0.00 0.00 0.00 0.00 0.00 3.47
July 4474.60 09-JUL-18:12 0.00 155.73 298.95 0.00 0.00 0.00 0.00 4.58 0.00
August 4453.63 13-AUG-18:02 0.00 194.66 373.68 0.00 0.00 0.00 0.00 1.81 0.00
September 4478.15 15-SEP-07:02 2173.23 1281.58 2189.08 0.00 0.00 0.00 0.00 0.00 0.00
October 4143.51 10-OCT-07:02 2173.23 1300.06 2189.08 0.00 0.00 0.00 0.00 0.00 0.60
November 1689.86 06-NOV-16:25 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 4.16
December 582.78 18-DEC-07:04 638.93 871.22 1532.36 0.00 0.00 0.00 0.00 0.00 12.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 582.78   0.00 155.73 298.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4478.15   2173.23 1300.06 2189.08 0.00 0.00 0.00 0.00 4.58 17.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 523.90 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82.00 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.16 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 998.17 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.18 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 730.08 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 705.00 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 632.53 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.05 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 235.36 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1036.42 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.69
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1036.42 38.69



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.141805E+11 17860.83 09-JAN-08:30 0.655492E+09 19710.07 09-JAN-07:10
February 0.116893E+11 18215.90 06-FEB-08:30 0.457485E+09 20389.14 13-FEB-07:10
March 0.118999E+11 12610.67 30-MAR-15:00 1876615.21 2117.24 06-MAR-07:10
April 0.110581E+11 12699.89 17-APR-15:00 6342672.04 4428.79 06-APR-06:10
May 0.126021E+11 13784.45 30-MAY-15:30 0.00 0.00 01-MAY-00:10
June 0.140341E+11 15465.29 26-JUN-07:19 0.00 0.00 01-JUN-00:10
July 0.140304E+11 16122.22 07-JUL-15:50 0.00 0.00 01-JUL-00:10
August 0.156780E+11 15967.83 07-AUG-14:00 0.00 0.00 01-AUG-00:10
September 0.130499E+11 15522.23 07-SEP-15:39 0.00 0.00 01-SEP-00:10
October 0.122372E+11 14508.08 10-OCT-15:50 56765.23 94.61 26-OCT-07:10
November 0.113976E+11 12390.82 22-NOV-08:39 20039633.18 6910.09 22-NOV-07:10
December 0.116574E+11 14928.16 04-DEC-08:39 0.127610E+09 12002.75 04-DEC-07:10
             
Annual Sum or Average 0.153514E+12     0.126890E+10    
Minimum of Months 0.110581E+11 12390.82   0.00 0.00  
Maximum of Months 0.156780E+11 18215.90   0.655492E+09 20389.14  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.227196E+10 0.104159E+10 0.405300E+10 0.00 0.167201E+10 0.02 0.307279E+10 1212269.35 0.00 0.00 0.00 0.206793E+10 0.00
February 0.205198E+10 0.859607E+09 0.366466E+10 0.00 0.150459E+10 0.00 0.166839E+10 71227763.49 0.00 0.00 0.00 0.186888E+10 0.00
March 0.234289E+10 0.852821E+09 0.429420E+10 0.00 0.176401E+10 0.00 0.189515E+09 0.367136E+09 0.00 0.00 0.00 0.208929E+10 0.00
April 0.212186E+10 0.730701E+09 0.388642E+10 0.00 0.153392E+10 0.00 72726946.15 0.766206E+09 0.00 0.00 0.00 0.194629E+10 0.00
May 0.224125E+10 0.668987E+09 0.417360E+10 0.00 0.168732E+10 0.00 587930.53 0.182931E+10 0.00 0.00 0.00 0.200105E+10 0.00
June 0.219720E+10 0.614171E+09 0.412149E+10 0.00 0.168776E+10 0.00 0.00 0.349804E+10 0.00 0.00 0.00 0.191539E+10 0.00
July 0.212141E+10 0.651105E+09 0.393546E+10 0.00 0.154001E+10 0.00 0.00 0.386754E+10 0.00 0.00 0.00 0.191486E+10 0.00
August 0.229364E+10 0.720095E+09 0.429420E+10 0.00 0.176884E+10 0.00 0.00 0.463966E+10 0.00 0.00 0.00 0.196153E+10 0.00
September 0.213320E+10 0.781509E+09 0.388029E+10 0.00 0.153392E+10 0.00 0.00 0.284182E+10 0.00 0.00 0.00 0.187911E+10 0.00
October 0.225496E+10 0.904977E+09 0.405607E+10 0.00 0.161069E+10 0.00 15345527.77 0.141768E+10 0.00 0.00 0.00 0.197753E+10 0.00
November 0.222638E+10 0.980716E+09 0.400396E+10 0.00 0.161062E+10 0.00 0.147628E+09 0.466503E+09 0.00 0.00 0.00 0.196179E+10 0.00
December 0.221231E+10 0.107054E+10 0.393240E+10 0.00 0.153392E+10 0.00 0.783076E+09 98691588.62 0.00 0.00 0.00 0.202648E+10 0.00
                           
Annual Sum or Average 0.264690E+11 0.987682E+10 0.482958E+11 0.00 0.194476E+11 0.02 0.595006E+10 0.198650E+11 0.00 0.00 0.00 0.236102E+11 0.00
Minimum of Months 0.205198E+10 0.614171E+09 0.366466E+10 0.00 0.150459E+10 0.00 0.00 1212269.35 0.00 0.00 0.00 0.186888E+10 0.00
Maximum of Months 0.234289E+10 0.107054E+10 0.429420E+10 0.00 0.176884E+10 0.02 0.307279E+10 0.463966E+10 0.00 0.00 0.00 0.208929E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.655492E+09 0.00 0.00 0.00 0.00
February 0.00 0.00 0.457485E+09 0.00 0.00 0.00 0.00
March 0.00 0.00 1876615.21 0.00 0.00 0.00 0.00
April 0.00 0.00 6342672.04 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 56765.23 0.00 0.00 0.00 0.00
November 0.00 0.00 20039633.18 0.00 0.00 0.00 0.00
December 0.00 0.00 0.127610E+09 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.126890E+10 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.655492E+09 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2008.10 03-JAN-08:09 1049.10 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1638.81 02-JAN-06:10 0.00 10-JAN-11:39 8279.37 10-JAN-07:30
February 2020.56 01-FEB-08:09 1049.10 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1638.81 01-FEB-06:10 0.00 01-FEB-07:10 8503.71 06-FEB-08:30
March 2010.79 21-MAR-07:10 1049.10 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1638.81 01-MAR-06:10 0.00 01-MAR-00:10 3454.26 23-MAR-06:10
April 1994.23 03-APR-07:10 1049.10 01-APR-05:10 3325.31 03-APR-07:10 0.00 1638.81 03-APR-05:10 0.00 01-APR-00:10 3847.74 06-APR-06:30
May 1943.22 24-MAY-07:10 1049.10 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 1638.81 01-MAY-05:10 0.00 01-MAY-00:10 345.73 11-MAY-07:10
June 1934.81 23-JUN-07:10 1049.10 01-JUN-05:10 3325.31 01-JUN-07:10 0.00 1638.81 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 1962.80 27-JUL-07:10 1049.10 01-JUL-05:10 3325.31 03-JUL-07:10 0.00 1638.81 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 1987.24 24-AUG-07:10 1049.10 01-AUG-05:10 3325.31 01-AUG-07:10 0.00 1638.81 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2000.50 29-SEP-07:10 1049.10 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1638.81 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2025.22 30-OCT-07:10 1049.10 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1638.81 02-OCT-05:10 0.00 01-OCT-00:10 1368.53 26-OCT-07:10
November 2022.23 01-NOV-07:10 1049.10 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1638.81 01-NOV-05:10 0.00 01-NOV-00:10 5017.05 22-NOV-07:30
December 2008.45 06-DEC-08:09 1049.10 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1638.81 01-DEC-06:10 0.00 01-DEC-00:10 6893.68 04-DEC-07:30
                           
Annual Sum or Average             0.00            
Minimum of Months 1934.81   1049.10   3325.31   0.00 1638.81   0.00   0.00  
Maximum of Months 2025.22   1049.10   3325.31   0.00 1638.81   0.00   8503.71  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 125.51 31-JAN-14:50 0.00 0.00 0.00 2802.28 26-JAN-12:09 0.00
February 1695.29 28-FEB-16:40 0.00 0.00 0.00 2802.39 02-FEB-12:39 0.00
March 3158.89 30-MAR-15:00 0.00 0.00 0.00 2799.27 01-MAR-12:50 0.00
April 3204.11 17-APR-15:00 0.00 0.00 0.00 2790.19 04-APR-11:50 0.00
May 4512.10 30-MAY-14:00 0.00 0.00 0.00 2780.48 01-MAY-11:09 0.00
June 6012.94 26-JUN-14:00 0.00 0.00 0.00 2769.05 01-JUN-11:20 0.00
July 6744.64 07-JUL-15:00 0.00 0.00 0.00 2760.39 05-JUL-11:50 0.00
August 6588.46 18-AUG-15:00 0.00 0.00 0.00 2760.28 31-AUG-11:30 0.00
September 6136.85 07-SEP-15:00 0.00 0.00 0.00 2767.46 29-SEP-11:30 0.00
October 5063.30 10-OCT-15:00 0.00 0.00 0.00 2778.49 31-OCT-11:20 0.00
November 2381.20 02-NOV-14:30 0.00 0.00 0.00 2789.59 29-NOV-12:20 0.00
December 1523.34 13-DEC-13:09 0.00 0.00 0.00 2798.45 29-DEC-12:50 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 125.51   0.00 0.00 0.00 2760.28   0.00
Maximum of Months 6744.64   0.00 0.00 0.00 2802.39   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17860.83 09-JAN-08:30 1976.78 3325.31 0.00 0.00 1638.81 0.00 8187.45 0.00 0.00
February 18215.90 06-FEB-08:30 2014.58 3325.31 0.00 0.00 1638.81 0.00 8503.71 0.00 0.00
March 12610.67 30-MAR-15:00 1734.42 3325.31 0.00 0.00 1638.81 0.00 0.00 3158.89 0.00
April 12699.89 17-APR-15:00 1782.81 3325.31 0.00 0.00 1638.81 0.00 0.00 3204.11 0.00
May 13784.45 30-MAY-15:30 1666.25 3325.31 0.00 0.00 1638.81 0.00 0.00 4416.43 0.00
June 15465.29 26-JUN-07:19 1889.96 3325.31 0.00 0.00 1638.81 0.00 0.00 5899.06 0.00
July 16122.22 07-JUL-15:50 1706.94 3325.31 0.00 0.00 1638.81 0.00 0.00 6720.56 0.00
August 15967.83 07-AUG-14:00 1747.62 3325.31 0.00 0.00 1638.81 0.00 0.00 6546.16 0.00
September 15522.23 07-SEP-15:39 1724.44 3325.31 0.00 0.00 1638.81 0.00 0.00 6101.94 0.00
October 14508.08 10-OCT-15:50 1762.41 3325.31 0.00 0.00 1638.81 0.00 0.00 5043.45 0.00
November 12390.82 22-NOV-08:39 1788.65 3325.31 0.00 0.00 1638.81 0.00 2912.42 0.00 0.00
December 14928.16 04-DEC-08:39 1798.76 3325.31 0.00 0.00 1638.81 0.00 5437.24 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 12390.82   1666.25 3325.31 0.00 0.00 1638.81 0.00 0.00 0.00 0.00
Maximum of Months 18215.90   2014.58 3325.31 0.00 0.00 1638.81 0.00 8503.71 6720.56 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 19710.07 09-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 20389.14 13-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 2117.24 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 4428.79 06-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 94.61 26-OCT-07:10 0.00 0.00 0.00
November 0.00 0.00 6910.09 22-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 12002.75 04-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 20389.14   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 24.47 0.17 24.47
June 0.00 0.00 0.00 0.00 6.00 24.71 6.00 24.71
July 0.00 0.00 0.00 0.00 29.00 24.77 29.00 24.77
August 0.00 0.00 0.00 0.00 38.67 24.81 38.67 24.81
September 0.00 0.00 0.00 0.00 3.67 24.74 3.67 24.74
October 0.00 0.00 0.00 0.00 0.33 24.51 0.33 24.51
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   77.83 24.78 77.83 24.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 38.67 24.81 38.67 24.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 18.17 2.33 18.57 0.00 18.57 0.00 18.57
February 2.83 18.05 2.17 18.46 0.00 18.46 0.00 18.46
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 24.60 0.33 24.60
July 0.00 0.00 0.00 0.00 3.33 24.56 3.33 24.56
August 0.00 0.00 0.00 0.00 14.67 24.66 14.67 24.66
September 0.00 0.00 0.00 0.00 14.00 24.61 14.00 24.61
October 0.00 0.00 0.00 0.00 5.17 24.64 5.17 24.64
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 5.83 18.11 4.50 18.52 37.50 23.31 37.50 23.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 18.17 2.33 18.57 14.67 24.66 14.67 24.66



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 14.91 0.00 14.91 0.00 14.91 0.00 14.91
February 3.17 14.86 0.00 14.86 0.00 14.86 0.00 14.86
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 25.67 0.67 25.19
August 0.00 0.00 0.00 0.00 2.33 24.94 2.17 24.75
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7.67 14.89 0.00 14.89 3.17 17.88 2.83 19.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 14.91 0.00 14.91 2.33 25.67 2.17 25.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.67 15.03 0.17 15.11 0.00 15.11 0.00 15.11
February 4.67 14.90 0.00 14.90 0.00 14.90 0.00 14.90
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.62 0.17 24.62
July 0.00 0.00 0.00 0.00 1.33 24.62 1.33 24.62
August 0.00 0.00 0.00 0.00 3.00 24.60 3.00 24.60
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9.33 14.97 0.17 15.01 4.50 18.09 4.50 19.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.67 15.03 0.17 15.11 3.00 24.62 3.00 24.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.17 14.93 0.00 14.93 0.00 14.93 0.00 14.93
February 3.50 14.87 0.00 14.87 0.00 14.87 0.00 14.87
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.50 30.16 0.00 30.16
August 0.00 0.00 0.00 0.00 1.83 30.11 0.00 30.11
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.67 14.90 0.00 14.90 4.33 19.98 0.00 19.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.17 14.93 0.00 14.93 2.50 30.16 0.00 30.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.87 234.17 20.75 234.17 20.69
February 321.33 21.70 116.50 21.42 116.50 21.26
March 304.67 23.28 52.50 23.43 15.83 23.44
April 148.00 23.76 112.33 24.20 23.17 24.21
May 68.50 25.06 307.83 24.83 57.50 24.89
June 101.00 26.48 361.33 25.39 101.00 25.58
July 133.83 26.84 340.00 25.73 133.83 25.98
August 157.50 26.78 391.00 25.74 157.50 25.97
September 67.50 26.40 337.67 25.20 67.50 25.37
October 97.17 24.36 187.33 24.71 34.00 24.82
November 250.67 23.40 35.00 23.50 18.17 23.52
December 336.50 22.12 77.50 22.02 77.50 21.94
             
Annual Sum or Average 2343.67 23.34 2553.17 23.85 1036.67 23.87
Minimum of Months 67.50 20.87 35.00 20.75 15.83 20.69
Maximum of Months 357.00 26.84 391.00 25.74 234.17 25.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.71 241.17 20.47 241.17 20.37
February 312.33 21.22 173.00 20.85 173.00 20.67
March 331.67 22.35 73.33 22.20 54.50 21.98
April 247.67 22.77 71.50 22.86 41.17 22.74
May 150.33 23.64 201.00 24.15 58.17 24.16
June 134.00 25.82 336.83 25.25 122.00 25.42
July 163.17 26.41 340.00 25.59 163.17 25.79
August 190.67 26.61 391.00 25.77 190.67 25.98
September 86.67 26.26 313.83 25.32 80.17 25.52
October 139.17 23.40 184.83 24.23 33.17 24.34
November 252.67 22.66 54.67 22.75 20.50 22.64
December 315.83 21.71 119.00 21.39 115.33 21.20
             
Annual Sum or Average 2681.17 22.97 2500.17 23.39 1293.00 23.36
Minimum of Months 86.67 20.71 54.67 20.47 20.50 20.37
Maximum of Months 357.00 26.61 391.00 25.77 241.17 25.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.09 259.17 19.99 259.17 19.95
February 266.00 20.85 171.83 20.51 171.83 20.35
March 297.83 22.29 64.50 22.02 57.50 21.78
April 190.17 22.99 54.83 23.12 21.33 22.97
May 72.67 23.76 201.00 24.53 25.33 24.52
June 89.33 26.61 297.67 25.63 86.00 25.82
July 133.17 27.03 280.00 26.04 133.17 26.28
August 157.17 27.03 322.00 26.07 157.17 26.30
September 60.67 26.52 265.00 25.44 56.67 25.63
October 132.00 23.34 121.33 24.08 17.17 24.13
November 266.83 22.64 43.67 22.46 35.83 22.27
December 279.50 21.08 163.83 20.75 163.83 20.60
             
Annual Sum or Average 2239.33 22.79 2244.83 23.22 1185.00 23.12
Minimum of Months 60.67 20.09 43.67 19.99 17.17 19.95
Maximum of Months 297.83 27.03 322.00 26.07 259.17 26.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.23 322.17 20.16 322.17 20.14
February 323.00 20.75 228.83 20.52 228.83 20.42
March 373.17 22.00 104.67 21.74 99.17 21.54
April 275.50 22.90 61.83 22.87 42.33 22.73
May 115.33 23.75 189.00 24.33 33.67 24.33
June 89.00 26.22 341.83 25.32 80.67 25.50
July 132.00 26.84 340.00 25.66 132.00 25.92
August 155.67 26.82 391.00 25.68 155.67 25.93
September 52.83 26.09 296.00 25.12 48.67 25.26
October 203.50 23.33 113.67 23.79 18.33 23.84
November 339.17 22.41 74.17 22.18 69.00 21.99
December 340.00 20.93 233.83 20.74 233.83 20.65
             
Annual Sum or Average 2756.17 22.52 2697.00 22.91 1464.33 22.79
Minimum of Months 52.83 20.23 61.83 20.16 18.33 20.14
Maximum of Months 373.17 26.84 391.00 25.68 322.17 25.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.38 305.67 20.28 305.67 20.24
February 319.67 21.05 202.17 20.73 202.17 20.59
March 335.00 22.41 84.83 22.33 60.33 22.10
April 215.50 23.16 95.83 23.59 28.17 23.46
May 93.67 24.39 230.83 24.93 34.33 25.01
June 112.17 27.41 348.33 25.90 109.33 26.21
July 135.67 27.67 340.00 26.13 135.67 26.47
August 162.00 27.65 391.00 26.16 162.00 26.50
September 83.50 27.31 311.67 25.71 79.17 26.01
October 160.67 23.64 157.17 24.35 21.17 24.46
November 305.33 22.77 52.00 22.66 38.17 22.49
December 338.33 21.37 181.50 21.04 181.50 20.88
             
Annual Sum or Average 2618.50 23.05 2701.00 23.46 1357.67 23.41
Minimum of Months 83.50 20.38 52.00 20.28 21.17 20.24
Maximum of Months 357.00 27.67 391.00 26.16 305.67 26.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 78035408.14 17818887.85 26.66 73694563.81 4340844.32 0.00 0.34 28-FEB-15:00 0.00 01-FEB-00:10 1902.97 28-FEB-15:00 1746.71 28-FEB-15:00 161.23 28-FEB-14:25 443.49 28-FEB-15:00 0.00
March 0.636450E+09 0.141393E+09 134.56 0.493079E+09 0.143371E+09 0.00 1.00 31-MAR-07:03 0.00 01-MAR-00:10 6664.44 31-MAR-07:03 4393.93 31-MAR-07:03 2270.51 31-MAR-07:03 1296.78 31-MAR-07:03 0.00
April 0.128694E+10 0.288178E+09 177.29 0.102785E+10 0.259093E+09 0.00 1.00 18-APR-07:03 0.00 01-APR-00:10 6575.75 21-APR-07:03 4876.55 18-APR-07:03 2116.91 21-APR-07:03 1284.56 21-APR-07:03 0.00
May 0.264716E+10 0.579824E+09 222.72 0.197575E+10 0.671407E+09 0.00 1.00 03-MAY-07:03 0.00 01-MAY-00:10 6929.18 26-MAY-07:03 5128.51 17-MAY-07:02 3132.95 26-MAY-07:08 1329.35 30-MAY-07:02 0.00
June 0.427876E+10 0.940208E+09 238.55 0.314359E+10 0.113517E+10 0.00 1.00 01-JUN-07:03 0.00 01-JUN-00:10 7055.24 26-JUN-06:02 5879.78 09-JUN-07:02 3199.59 23-JUN-06:03 1489.52 27-JUN-13:00 0.00
July 0.456495E+10 0.991135E+09 222.17 0.324733E+10 0.131762E+10 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:10 7153.67 27-JUL-06:03 5243.32 24-JUL-15:35 3576.02 27-JUL-06:05 1557.82 07-JUL-16:00 0.00
August 0.536270E+10 0.115882E+10 256.32 0.372107E+10 0.164164E+10 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 7195.74 24-AUG-06:02 5085.47 29-AUG-14:50 3583.41 24-AUG-06:06 1541.03 18-AUG-16:00 0.00
September 0.352727E+10 0.753025E+09 213.41 0.260053E+10 0.926734E+09 0.00 1.00 01-SEP-06:03 0.00 01-SEP-00:10 7080.11 07-SEP-06:02 5154.31 15-SEP-07:02 3152.54 07-SEP-06:04 1467.10 06-SEP-13:20 0.00
October 0.192687E+10 0.413640E+09 196.47 0.145023E+10 0.476634E+09 0.00 1.00 02-OCT-07:03 0.00 01-OCT-00:10 6988.33 19-OCT-07:02 5378.17 12-OCT-07:03 3387.12 19-OCT-07:06 1328.39 19-OCT-07:02 0.00
November 0.667188E+09 0.146968E+09 135.32 0.554943E+09 0.112245E+09 0.00 0.57 03-NOV-07:03 0.00 01-NOV-00:10 3440.86 03-NOV-07:03 2329.22 03-NOV-07:03 1111.63 03-NOV-07:03 725.02 03-NOV-07:03 0.00
December 0.117449E+09 25961775.72 27.95 79276903.27 38171680.99 0.00 0.35 13-DEC-13:10 0.00 01-DEC-00:10 2122.05 13-DEC-13:10 1322.94 13-DEC-13:10 799.68 13-DEC-13:20 459.14 13-DEC-13:10 0.00
                                       
Annual Sum or Average 0.250938E+11 0.545697E+10 1851.41 0.183673E+11 0.672642E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.536270E+10 0.115882E+10 256.32 0.372107E+10 0.164164E+10 0.00 1.00   0.00   7195.74   5879.78   3583.41   1557.82   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 5310400.41 1212269.35 3.50 4793189.36 517211.06 0.00 0.10 31-JAN-14:50 0.00 01-JAN-00:05 551.46 31-JAN-14:50 502.32 31-JAN-14:50 50.08 31-JAN-14:40 125.51 31-JAN-14:50 0.00
February 0.169364E+09 37696455.12 32.67 0.169326E+09 38506.56 0.00 0.48 28-FEB-15:30 0.00 01-FEB-00:10 2687.62 28-FEB-15:30 2687.62 28-FEB-15:30 18.52 22-FEB-15:40 605.85 28-FEB-15:30 0.00
March 0.448599E+09 0.100550E+09 87.44 0.387925E+09 60673717.39 0.00 0.67 30-MAR-14:20 0.00 01-MAR-00:10 3955.30 30-MAR-14:10 3541.43 30-MAR-15:00 697.84 30-MAR-11:52 911.02 30-MAR-14:10 0.00
April 0.648616E+09 0.150333E+09 109.72 0.573485E+09 75130726.47 0.00 0.57 17-APR-14:55 0.00 01-APR-00:10 3284.24 19-APR-14:25 3147.41 17-APR-16:08 724.23 04-APR-13:23 781.18 17-APR-14:45 0.00
May 0.156037E+10 0.355855E+09 190.76 0.121618E+10 0.344182E+09 0.00 0.99 30-MAY-07:02 0.00 01-MAY-00:10 6691.51 30-MAY-07:02 4123.49 30-MAY-07:02 2568.03 30-MAY-07:02 1304.45 30-MAY-07:02 0.00
June 0.343497E+10 0.776347E+09 222.05 0.257857E+10 0.856397E+09 0.00 1.00 05-JUN-07:02 0.00 01-JUN-00:10 7102.47 26-JUN-06:02 5321.97 06-JUN-07:02 3478.08 23-JUN-07:04 1480.81 23-JUN-12:02 0.00
July 0.393776E+10 0.875110E+09 210.19 0.286618E+10 0.107157E+10 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 7160.46 26-JUL-07:02 5467.58 10-JUL-16:08 3850.02 26-JUL-07:02 1548.36 07-JUL-16:08 0.00
August 0.501004E+10 0.109744E+10 250.20 0.357665E+10 0.143338E+10 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 7228.72 24-AUG-06:02 5445.43 29-AUG-16:08 3770.29 24-AUG-07:02 1537.01 01-AUG-16:08 0.00
September 0.317233E+10 0.686421E+09 202.24 0.248026E+10 0.692070E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 7063.86 07-SEP-06:02 5557.32 25-SEP-14:35 3105.14 07-SEP-07:06 1468.78 07-SEP-16:00 0.00
October 0.182209E+10 0.388837E+09 164.32 0.151785E+10 0.304235E+09 0.00 1.00 10-OCT-07:02 0.00 01-OCT-00:10 6973.47 19-OCT-07:02 5650.46 11-OCT-16:00 3421.80 19-OCT-07:04 1423.96 10-OCT-15:53 0.00
November 0.748818E+09 0.161583E+09 118.17 0.696177E+09 52640161.48 0.00 0.73 06-NOV-14:30 0.00 01-NOV-00:10 4281.33 06-NOV-14:30 4281.33 06-NOV-14:30 686.71 02-NOV-12:10 881.11 06-NOV-14:30 0.00
December 0.233621E+09 51532881.18 55.04 0.202945E+09 30675860.82 0.00 0.57 12-DEC-14:00 0.00 01-DEC-00:10 3390.93 12-DEC-14:00 2771.96 12-DEC-14:20 691.30 12-DEC-13:05 731.05 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.211919E+11 0.468292E+10 1646.30 0.162704E+11 0.492151E+10 0.00                         0.00
Minimum of Months 5310400.41 1212269.35 3.50 4793189.36 38506.56 0.00 0.10   0.00   551.46   502.32   18.52   125.51   0.00
Maximum of Months 0.501004E+10 0.109744E+10 250.20 0.357665E+10 0.143338E+10 0.00 1.00   0.00   7228.72   5650.46   3850.02   1548.36   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 26987348.61 6259447.57 16.99 26987348.61 -0.0 0.00 0.24 28-FEB-15:10 0.00 01-FEB-00:10 920.10 28-FEB-15:10 920.10 28-FEB-15:10 0.00 27-FEB-12:10 217.79 28-FEB-15:10 0.00
March 0.178670E+09 40798195.99 78.53 0.152656E+09 26013859.68 0.00 0.40 30-MAR-16:00 0.00 01-MAR-00:10 1623.73 30-MAR-16:00 1477.84 30-MAR-15:47 308.60 30-MAR-10:53 391.42 30-MAR-16:00 0.00
April 0.485874E+09 0.112597E+09 140.21 0.446006E+09 39867876.05 0.00 0.48 17-APR-11:00 0.00 01-APR-00:10 2016.38 17-APR-11:00 1901.55 17-APR-10:55 351.39 04-APR-14:43 462.84 17-APR-11:00 0.00
May 0.121709E+10 0.277235E+09 208.97 0.103103E+10 0.186061E+09 0.00 1.00 08-MAY-07:02 0.00 01-MAY-00:10 4969.43 31-MAY-07:03 4046.11 18-MAY-07:02 1830.68 31-MAY-07:03 959.53 30-MAY-07:02 0.00
June 0.232675E+10 0.533536E+09 236.28 0.192746E+10 0.399291E+09 0.00 1.00 01-JUN-07:03 0.00 01-JUN-00:10 5115.37 26-JUN-06:02 4497.75 08-JUN-07:02 2038.60 23-JUN-07:04 979.73 26-JUN-06:02 0.00
July 0.262433E+10 0.594853E+09 233.33 0.212605E+10 0.498280E+09 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:10 5141.10 27-JUL-06:03 4106.19 10-JUL-10:06 2264.11 27-JUL-06:03 1067.90 07-JUL-11:03 0.00
August 0.307972E+10 0.695283E+09 263.09 0.244029E+10 0.639426E+09 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 5181.88 21-AUG-06:01 3964.01 07-AUG-10:12 2246.65 24-AUG-06:02 1063.58 07-AUG-13:00 0.00
September 0.190094E+10 0.420965E+09 210.20 0.158984E+10 0.311104E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 5093.49 05-SEP-06:02 4243.01 15-SEP-07:02 1862.98 05-SEP-06:03 971.76 07-SEP-07:02 0.00
October 0.884980E+09 0.195567E+09 174.51 0.756830E+09 0.128150E+09 0.00 1.00 02-OCT-07:03 0.00 01-OCT-00:10 5056.26 19-OCT-07:02 3887.83 10-OCT-07:02 2222.95 19-OCT-07:04 959.89 19-OCT-07:02 0.00
November 0.226464E+09 50791274.03 99.50 0.208541E+09 17923438.10 0.00 0.32 03-NOV-15:00 0.00 01-NOV-00:10 1331.56 03-NOV-15:00 1180.39 06-NOV-14:00 251.09 03-NOV-15:40 294.20 03-NOV-15:00 0.00
December 28759666.50 6481557.50 17.18 21654533.45 7105133.05 0.00 0.21 13-DEC-13:10 0.00 01-DEC-00:10 893.24 13-DEC-13:10 648.95 13-DEC-13:10 261.35 13-DEC-12:00 198.30 13-DEC-13:10 0.00
                                       
Annual Sum or Average 0.129806E+11 0.293437E+10 1678.79 0.107273E+11 0.225322E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.307972E+10 0.695283E+09 263.09 0.244029E+10 0.639426E+09 0.00 1.00   0.00   5181.88   4497.75   2264.11   1067.90   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 9677970.30 2304267.25 4.25 9677970.30 -0.0 0.00 0.16 28-FEB-16:53 0.00 01-FEB-00:10 853.13 28-FEB-16:57 853.13 28-FEB-16:57 0.00 28-FEB-13:50 201.23 28-FEB-16:53 0.00
March 0.159193E+09 36398875.02 45.59 0.121832E+09 37361480.26 0.00 0.42 30-MAR-15:53 0.00 01-MAR-00:10 2370.60 30-MAR-15:53 2085.99 30-MAR-15:57 495.91 31-MAR-11:00 567.99 30-MAR-15:53 0.00
April 0.469808E+09 0.109560E+09 103.12 0.396909E+09 72898490.48 0.00 0.45 19-APR-14:55 0.00 01-APR-00:10 2569.74 19-APR-14:55 2200.74 19-APR-14:55 642.22 04-APR-14:32 600.05 19-APR-14:55 0.00
May 0.152915E+10 0.349021E+09 202.04 0.120673E+10 0.322418E+09 0.00 1.00 19-MAY-07:02 0.00 01-MAY-00:10 6706.45 31-MAY-07:03 4951.31 18-MAY-07:02 2713.83 31-MAY-07:03 1295.18 30-MAY-07:02 0.00
June 0.320067E+10 0.730229E+09 234.14 0.250275E+10 0.697921E+09 0.00 1.00 01-JUN-07:03 0.00 01-JUN-00:10 6928.79 26-JUN-06:02 5297.14 06-JUN-07:02 2959.20 23-JUN-07:06 1324.64 26-JUN-06:02 0.00
July 0.364302E+10 0.818927E+09 219.50 0.278408E+10 0.858936E+09 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:10 6946.21 27-JUL-06:03 5278.86 10-JUL-14:00 3258.58 27-JUL-06:03 1468.43 07-JUL-16:00 0.00
August 0.439581E+10 0.980735E+09 253.70 0.328980E+10 0.110601E+10 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 7017.88 21-AUG-06:01 5082.15 07-AUG-13:00 3252.02 21-AUG-06:06 1457.06 07-AUG-15:00 0.00
September 0.254921E+10 0.563709E+09 208.59 0.200279E+10 0.546419E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 6864.19 05-SEP-06:02 5284.94 19-SEP-07:02 2714.14 05-SEP-06:03 1315.37 07-SEP-07:02 0.00
October 0.102256E+10 0.226099E+09 156.76 0.802012E+09 0.220550E+09 0.00 1.00 02-OCT-07:03 0.00 01-OCT-00:10 6841.60 19-OCT-07:02 4513.53 11-OCT-07:02 3206.19 19-OCT-07:06 1297.92 19-OCT-07:02 0.00
November 0.212798E+09 47690748.10 69.14 0.184891E+09 27906571.71 0.00 0.34 03-NOV-15:00 0.00 01-NOV-00:10 1964.50 03-NOV-15:00 1504.92 03-NOV-15:00 459.59 03-NOV-15:00 431.70 03-NOV-15:00 0.00
December 24128816.47 5412925.45 9.72 15750066.86 8378749.61 0.00 0.19 13-DEC-13:10 0.00 01-DEC-00:10 1090.79 13-DEC-13:10 707.29 13-DEC-13:10 383.50 13-DEC-13:10 241.98 13-DEC-13:10 0.00
                                       
Annual Sum or Average 0.172160E+11 0.387009E+10 1506.55 0.133172E+11 0.389880E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.439581E+10 0.980735E+09 253.70 0.328980E+10 0.110601E+10 0.00 1.00   0.00   7017.88   5297.14   3258.58   1468.43   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 30852340.08 7148705.70 15.88 30852340.08 0.00 0.00 0.29 28-FEB-16:42 0.00 01-FEB-00:10 1304.22 28-FEB-16:45 1304.22 28-FEB-16:45 0.00 22-FEB-14:20 300.88 28-FEB-16:45 0.00
March 0.210308E+09 47995566.60 75.40 0.177151E+09 33156566.47 0.00 0.50 30-MAR-15:53 0.00 01-MAR-00:10 2369.58 30-MAR-15:53 2156.99 30-MAR-15:57 420.83 31-MAR-07:03 561.66 30-MAR-15:53 0.00
April 0.451074E+09 0.105538E+09 131.70 0.400690E+09 50384630.47 0.00 0.53 17-APR-15:53 0.00 01-APR-00:10 2444.04 17-APR-15:53 2360.22 17-APR-15:57 403.45 04-APR-14:10 592.18 17-APR-15:53 0.00
May 0.115954E+10 0.267370E+09 210.06 0.954051E+09 0.205491E+09 0.00 1.00 18-MAY-07:02 0.00 01-MAY-00:10 5592.63 31-MAY-07:03 4513.27 18-MAY-07:02 2005.10 31-MAY-07:03 1079.98 30-MAY-07:02 0.00
June 0.221624E+10 0.517718E+09 238.01 0.179594E+10 0.420295E+09 0.00 1.00 01-JUN-07:03 0.00 01-JUN-00:10 5700.93 26-JUN-06:02 4704.64 09-JUN-07:02 2177.20 23-JUN-07:04 1101.30 26-JUN-06:02 0.00
July 0.253473E+10 0.587516E+09 244.57 0.201537E+10 0.519360E+09 0.00 1.00 03-JUL-06:02 0.00 01-JUL-00:10 5785.03 27-JUL-06:03 5116.42 09-JUL-18:53 2469.12 27-JUL-06:03 1252.55 08-JUL-17:02 0.00
August 0.307959E+10 0.707386E+09 279.10 0.240706E+10 0.672528E+09 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 5807.01 24-AUG-06:02 4964.09 13-AUG-18:02 2370.93 24-AUG-06:02 1214.02 06-AUG-18:02 0.00
September 0.185684E+10 0.417696E+09 213.08 0.152339E+10 0.333446E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 5740.85 05-SEP-06:02 4819.84 15-SEP-07:02 2039.44 05-SEP-06:03 1093.22 07-SEP-07:02 0.00
October 0.868257E+09 0.193535E+09 176.89 0.727336E+09 0.140922E+09 0.00 1.00 02-OCT-07:03 0.00 01-OCT-00:10 5688.80 19-OCT-07:02 4438.46 10-OCT-07:02 2460.60 19-OCT-07:04 1080.56 19-OCT-07:02 0.00
November 0.265997E+09 59469569.63 100.57 0.242858E+09 23138279.41 0.00 0.41 06-NOV-16:30 0.00 01-NOV-00:10 1872.11 06-NOV-16:25 1872.11 06-NOV-16:25 281.97 03-NOV-15:00 406.08 06-NOV-16:25 0.00
December 41336229.28 9302448.77 19.99 31204075.48 10132153.80 0.00 0.21 12-DEC-14:53 0.00 01-DEC-00:10 965.25 12-DEC-14:35 743.86 12-DEC-14:53 273.97 13-DEC-12:00 219.12 12-DEC-14:53 0.00
                                       
Annual Sum or Average 0.127148E+11 0.292068E+10 1705.26 0.103059E+11 0.240885E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.307959E+10 0.707386E+09 279.10 0.240706E+10 0.672528E+09 0.00 1.00   0.00   5807.01   5116.42   2469.12   1252.55   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.72 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.84 24.11 23.73 67.14 34.01 0.00 0.00 0.00
April 29.36 6.15 23.21 43.07 27.62 0.00 0.00 0.00
May 23.77 0.00 23.77 35.47 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.57 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.60 1.63 23.97 48.39 10.95 0.00 0.00 0.00
September 32.18 10.19 22.00 52.92 21.02 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.98 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.27 20.57 21.71 61.35 31.85 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.98 35.47 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.71 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.83 24.10 23.73 67.12 34.02 0.00 0.00 0.00
April 29.26 6.10 23.15 42.84 27.63 0.00 0.00 0.00
May 23.77 0.00 23.77 35.46 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.56 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.56 1.62 23.94 48.32 10.95 0.00 0.00 0.00
September 32.10 10.16 21.94 52.74 21.03 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.97 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.25 20.56 21.70 61.30 31.86 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.97 35.46 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.71 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.83 24.10 23.73 67.12 34.02 0.00 0.00 0.00
April 29.26 6.10 23.15 42.84 27.63 0.00 0.00 0.00
May 23.77 0.00 23.77 35.46 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.56 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.56 1.62 23.94 48.31 10.95 0.00 0.00 0.00
September 32.09 10.16 21.94 52.73 21.04 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.97 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.25 20.56 21.70 61.30 31.86 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.97 35.46 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.71 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.83 24.10 23.73 67.12 34.02 0.00 0.00 0.00
April 29.26 6.10 23.15 42.84 27.63 0.00 0.00 0.00
May 23.77 0.00 23.77 35.46 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.56 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.56 1.62 23.94 48.31 10.95 0.00 0.00 0.00
September 32.10 10.16 21.94 52.73 21.04 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.97 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.25 20.56 21.70 61.30 31.86 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.97 35.46 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.71 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.83 24.10 23.73 67.12 34.02 0.00 0.00 0.00
April 29.26 6.10 23.15 42.84 27.63 0.00 0.00 0.00
May 23.77 0.00 23.77 35.46 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.56 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.56 1.62 23.94 48.32 10.95 0.00 0.00 0.00
September 32.11 10.16 21.95 52.73 21.02 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.97 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.26 20.56 21.70 61.30 31.86 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.97 35.46 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.96 44.37 18.59 77.33 57.33 0.00 0.00 0.00
February 58.72 39.82 18.90 78.12 49.12 0.00 0.00 0.00
March 47.84 24.11 23.73 67.13 34.01 0.00 0.00 0.00
April 29.35 6.15 23.21 43.01 27.57 0.00 0.00 0.00
May 23.77 0.00 23.77 35.47 19.16 0.00 0.00 0.00
June 24.63 0.00 24.63 44.57 14.34 0.00 0.00 0.00
July 24.05 0.06 23.99 44.56 11.60 0.00 0.00 0.00
August 25.59 1.63 23.96 48.38 10.95 0.00 0.00 0.00
September 32.19 10.19 22.00 52.87 20.96 0.00 0.00 0.00
October 55.78 36.33 19.45 82.91 38.55 0.00 0.00 0.00
November 61.18 41.06 20.12 83.32 47.17 0.00 0.00 0.00
December 62.11 44.14 17.98 79.27 52.50 0.00 0.00 0.00
                 
Annual Sum or Average 42.27 20.57 21.71 61.33 31.84 0.00 0.00 0.00
Minimum of Months 23.77 0.00 17.98 35.47 10.95 0.00 0.00 0.00
Maximum of Months 62.96 44.37 24.63 83.32 57.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.68 62.17 26.52 108.85 79.80 0.00 0.00 0.00
February 82.74 55.79 26.95 109.92 68.47 0.00 0.00 0.00
March 74.17 39.01 35.17 106.67 47.57 0.00 0.00 0.00
April 48.93 13.77 35.16 75.64 38.71 0.00 0.00 0.00
May 36.80 1.43 35.37 56.52 26.95 0.00 0.00 0.00
June 35.36 0.00 35.35 63.29 20.27 0.00 0.00 0.00
July 35.13 0.38 34.75 64.60 16.40 0.00 0.00 0.00
August 42.21 5.43 36.79 80.36 15.55 0.00 0.00 0.00
September 52.24 18.87 33.37 87.44 29.59 0.00 0.00 0.00
October 80.11 52.20 27.91 119.12 53.93 0.00 0.00 0.00
November 86.20 57.53 28.67 117.19 65.96 0.00 0.00 0.00
December 87.45 61.84 25.62 111.54 73.27 0.00 0.00 0.00
                 
Annual Sum or Average 62.41 30.58 31.83 91.68 44.58 0.00 0.00 0.00
Minimum of Months 35.13 0.00 25.62 56.52 15.55 0.00 0.00 0.00
Maximum of Months 88.68 62.17 36.79 119.12 79.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.77 11.32 13.45 19.64 58.76 0.00 0.00 0.00
February 31.27 16.94 14.33 33.34 48.23 0.00 0.00 0.00
March 38.87 17.71 21.16 47.68 31.15 0.00 0.00 0.00
April 46.50 21.03 25.46 67.23 25.48 0.00 0.00 0.00
May 50.66 21.22 29.44 78.77 18.54 0.00 0.00 0.00
June 52.32 21.67 30.65 90.05 13.95 0.00 0.00 0.00
July 51.23 21.44 29.79 89.63 11.59 0.00 0.00 0.00
August 47.00 18.57 28.43 83.52 10.70 0.00 0.00 0.00
September 39.04 17.37 21.67 60.63 19.77 0.00 0.00 0.00
October 33.61 17.49 16.12 42.65 36.16 0.00 0.00 0.00
November 26.98 12.35 14.64 27.30 44.85 0.00 0.00 0.00
December 23.45 10.84 12.61 19.40 51.13 0.00 0.00 0.00
                 
Annual Sum or Average 38.84 17.32 21.52 55.10 30.77 0.00 0.00 0.00
Minimum of Months 23.45 10.84 12.61 19.40 10.70 0.00 0.00 0.00
Maximum of Months 52.32 21.67 30.65 90.05 58.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.77 11.32 13.45 19.64 58.76 0.00 0.00 0.00
February 31.27 16.94 14.33 33.34 48.23 0.00 0.00 0.00
March 38.87 17.71 21.16 47.68 31.15 0.00 0.00 0.00
April 46.50 21.03 25.46 67.23 25.48 0.00 0.00 0.00
May 50.66 21.22 29.44 78.77 18.54 0.00 0.00 0.00
June 52.32 21.67 30.65 90.05 13.95 0.00 0.00 0.00
July 51.23 21.44 29.79 89.63 11.59 0.00 0.00 0.00
August 47.00 18.57 28.43 83.52 10.70 0.00 0.00 0.00
September 39.04 17.37 21.67 60.63 19.77 0.00 0.00 0.00
October 33.61 17.49 16.12 42.65 36.16 0.00 0.00 0.00
November 26.98 12.35 14.64 27.30 44.85 0.00 0.00 0.00
December 23.45 10.84 12.61 19.40 51.13 0.00 0.00 0.00
                 
Annual Sum or Average 38.84 17.32 21.52 55.10 30.77 0.00 0.00 0.00
Minimum of Months 23.45 10.84 12.61 19.40 10.70 0.00 0.00 0.00
Maximum of Months 52.32 21.67 30.65 90.05 58.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.77 11.32 13.45 19.64 58.76 0.00 0.00 0.00
February 31.27 16.94 14.33 33.34 48.23 0.00 0.00 0.00
March 38.87 17.71 21.16 47.68 31.15 0.00 0.00 0.00
April 46.50 21.03 25.46 67.23 25.48 0.00 0.00 0.00
May 50.66 21.22 29.44 78.77 18.54 0.00 0.00 0.00
June 52.32 21.67 30.65 90.05 13.95 0.00 0.00 0.00
July 51.23 21.44 29.79 89.63 11.59 0.00 0.00 0.00
August 47.00 18.57 28.43 83.52 10.70 0.00 0.00 0.00
September 39.04 17.37 21.67 60.63 19.77 0.00 0.00 0.00
October 33.61 17.49 16.12 42.65 36.16 0.00 0.00 0.00
November 26.98 12.35 14.64 27.30 44.85 0.00 0.00 0.00
December 23.45 10.84 12.61 19.40 51.13 0.00 0.00 0.00
                 
Annual Sum or Average 38.84 17.32 21.52 55.10 30.77 0.00 0.00 0.00
Minimum of Months 23.45 10.84 12.61 19.40 10.70 0.00 0.00 0.00
Maximum of Months 52.32 21.67 30.65 90.05 58.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.80 11.34 13.46 19.67 58.72 0.00 0.00 0.00
February 31.27 16.94 14.33 33.34 48.23 0.00 0.00 0.00
March 38.87 17.71 21.16 47.68 31.15 0.00 0.00 0.00
April 46.50 21.03 25.46 67.23 25.48 0.00 0.00 0.00
May 50.66 21.22 29.44 78.77 18.54 0.00 0.00 0.00
June 52.32 21.67 30.65 90.05 13.95 0.00 0.00 0.00
July 51.23 21.44 29.79 89.63 11.59 0.00 0.00 0.00
August 47.00 18.57 28.43 83.52 10.70 0.00 0.00 0.00
September 39.04 17.37 21.67 60.63 19.77 0.00 0.00 0.00
October 33.61 17.49 16.12 42.65 36.16 0.00 0.00 0.00
November 27.00 12.35 14.65 27.33 44.85 0.00 0.00 0.00
December 23.49 10.86 12.63 19.46 51.10 0.00 0.00 0.00
                 
Annual Sum or Average 38.85 17.33 21.52 55.11 30.76 0.00 0.00 0.00
Minimum of Months 23.49 10.86 12.63 19.46 10.70 0.00 0.00 0.00
Maximum of Months 52.32 21.67 30.65 90.05 58.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.26 0.09 21.17 27.09 26.30 0.00 0.00 0.00
May 25.23 0.73 24.50 37.35 18.24 0.00 0.00 0.00
June 27.45 1.59 25.86 49.20 13.53 0.00 0.00 0.00
July 26.01 1.12 24.89 48.02 11.10 0.00 0.00 0.00
August 23.43 0.24 23.19 44.22 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.77 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.38 0.00 10.38 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.23 0.32 17.91 23.28 32.47 0.00 0.00 0.00
Minimum of Months 10.38 0.00 10.38 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.45 1.59 25.86 49.20 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.24 0.09 21.15 27.09 26.36 0.00 0.00 0.00
May 25.14 0.69 24.45 37.17 18.27 0.00 0.00 0.00
June 27.38 1.56 25.82 49.02 13.53 0.00 0.00 0.00
July 25.93 1.08 24.84 47.81 11.10 0.00 0.00 0.00
August 23.36 0.22 23.15 44.08 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.77 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.37 0.00 10.37 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.20 0.30 17.89 23.22 32.48 0.00 0.00 0.00
Minimum of Months 10.37 0.00 10.37 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.38 1.56 25.82 49.02 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.23 0.08 21.15 27.09 26.37 0.00 0.00 0.00
May 25.14 0.69 24.45 37.17 18.27 0.00 0.00 0.00
June 27.38 1.56 25.82 49.02 13.53 0.00 0.00 0.00
July 25.93 1.08 24.84 47.81 11.10 0.00 0.00 0.00
August 23.36 0.22 23.15 44.08 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.77 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.37 0.00 10.37 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.20 0.30 17.89 23.22 32.48 0.00 0.00 0.00
Minimum of Months 10.37 0.00 10.37 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.38 1.56 25.82 49.02 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.23 0.08 21.15 27.09 26.37 0.00 0.00 0.00
May 25.14 0.69 24.45 37.17 18.27 0.00 0.00 0.00
June 27.38 1.56 25.82 49.02 13.53 0.00 0.00 0.00
July 25.93 1.08 24.84 47.81 11.10 0.00 0.00 0.00
August 23.36 0.22 23.15 44.08 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.77 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.37 0.00 10.37 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.20 0.30 17.89 23.22 32.48 0.00 0.00 0.00
Minimum of Months 10.37 0.00 10.37 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.38 1.56 25.82 49.02 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.24 0.09 21.15 27.10 26.37 0.00 0.00 0.00
May 25.14 0.69 24.45 37.17 18.27 0.00 0.00 0.00
June 27.38 1.56 25.82 49.02 13.53 0.00 0.00 0.00
July 25.93 1.08 24.84 47.81 11.10 0.00 0.00 0.00
August 23.36 0.22 23.15 44.08 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.77 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.37 0.00 10.37 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.20 0.30 17.89 23.22 32.48 0.00 0.00 0.00
Minimum of Months 10.37 0.00 10.37 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.38 1.56 25.82 49.02 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.22 0.00 11.22 2.51 64.83 0.00 0.00 0.00
February 12.50 0.00 12.50 7.16 52.51 0.00 0.00 0.00
March 17.57 0.00 17.57 15.56 32.53 0.00 0.00 0.00
April 21.27 0.09 21.17 27.15 26.35 0.00 0.00 0.00
May 25.22 0.72 24.50 37.36 18.27 0.00 0.00 0.00
June 27.45 1.59 25.86 49.19 13.53 0.00 0.00 0.00
July 26.01 1.11 24.90 47.99 11.10 0.00 0.00 0.00
August 23.43 0.24 23.19 44.22 10.24 0.00 0.00 0.00
September 17.71 0.00 17.71 25.78 19.86 0.00 0.00 0.00
October 13.55 0.00 13.55 12.10 37.91 0.00 0.00 0.00
November 12.03 0.00 12.03 6.79 48.08 0.00 0.00 0.00
December 10.38 0.00 10.38 2.52 55.72 0.00 0.00 0.00
                 
Annual Sum or Average 18.23 0.31 17.91 23.28 32.48 0.00 0.00 0.00
Minimum of Months 10.38 0.00 10.38 2.51 10.24 0.00 0.00 0.00
Maximum of Months 27.45 1.59 25.86 49.19 64.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.54 12.02 13.52 22.74 61.47 0.00 0.00 0.00
February 29.16 13.76 15.40 32.70 51.41 0.00 0.00 0.00
March 42.75 20.74 22.01 56.19 34.13 0.00 0.00 0.00
April 47.57 21.74 25.83 70.48 28.39 0.00 0.00 0.00
May 47.33 17.78 29.56 74.94 20.67 0.00 0.00 0.00
June 49.64 18.87 30.77 86.52 15.90 0.00 0.00 0.00
July 46.80 17.16 29.64 83.23 12.87 0.00 0.00 0.00
August 46.10 17.18 28.92 82.61 12.16 0.00 0.00 0.00
September 38.05 15.96 22.09 59.72 21.44 0.00 0.00 0.00
October 34.23 17.81 16.42 46.12 39.52 0.00 0.00 0.00
November 27.44 12.45 14.99 31.39 48.99 0.00 0.00 0.00
December 22.70 10.07 12.62 21.07 54.97 0.00 0.00 0.00
                 
Annual Sum or Average 38.15 16.31 21.85 55.76 33.40 0.00 0.00 0.00
Minimum of Months 22.70 10.07 12.62 21.07 12.16 0.00 0.00 0.00
Maximum of Months 49.64 21.74 30.77 86.52 61.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.51 12.00 13.51 22.72 61.50 0.00 0.00 0.00
February 29.16 13.76 15.40 32.69 51.41 0.00 0.00 0.00
March 42.75 20.74 22.01 56.19 34.13 0.00 0.00 0.00
April 47.57 21.74 25.83 70.48 28.39 0.00 0.00 0.00
May 47.33 17.78 29.55 74.94 20.67 0.00 0.00 0.00
June 49.64 18.87 30.77 86.52 15.90 0.00 0.00 0.00
July 46.80 17.16 29.64 83.23 12.87 0.00 0.00 0.00
August 46.10 17.18 28.92 82.60 12.16 0.00 0.00 0.00
September 38.05 15.96 22.09 59.71 21.44 0.00 0.00 0.00
October 34.23 17.81 16.42 46.12 39.52 0.00 0.00 0.00
November 27.42 12.44 14.98 31.36 48.99 0.00 0.00 0.00
December 22.66 10.05 12.61 21.01 54.99 0.00 0.00 0.00
                 
Annual Sum or Average 38.15 16.30 21.85 55.75 33.40 0.00 0.00 0.00
Minimum of Months 22.66 10.05 12.61 21.01 12.16 0.00 0.00 0.00
Maximum of Months 49.64 21.74 30.77 86.52 61.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.51 12.00 13.51 22.72 61.50 0.00 0.00 0.00
February 29.16 13.76 15.40 32.69 51.41 0.00 0.00 0.00
March 42.75 20.74 22.01 56.19 34.13 0.00 0.00 0.00
April 47.57 21.74 25.83 70.48 28.39 0.00 0.00 0.00
May 47.33 17.78 29.55 74.94 20.67 0.00 0.00 0.00
June 49.64 18.87 30.77 86.52 15.90 0.00 0.00 0.00
July 46.80 17.16 29.64 83.23 12.87 0.00 0.00 0.00
August 46.10 17.18 28.92 82.60 12.16 0.00 0.00 0.00
September 38.05 15.96 22.09 59.71 21.44 0.00 0.00 0.00
October 34.23 17.81 16.42 46.12 39.52 0.00 0.00 0.00
November 27.42 12.44 14.98 31.36 48.99 0.00 0.00 0.00
December 22.66 10.05 12.61 21.01 54.99 0.00 0.00 0.00
                 
Annual Sum or Average 38.15 16.30 21.85 55.75 33.40 0.00 0.00 0.00
Minimum of Months 22.66 10.05 12.61 21.01 12.16 0.00 0.00 0.00
Maximum of Months 49.64 21.74 30.77 86.52 61.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.51 12.00 13.51 22.72 61.50 0.00 0.00 0.00
February 29.16 13.76 15.40 32.69 51.41 0.00 0.00 0.00
March 42.75 20.74 22.01 56.19 34.13 0.00 0.00 0.00
April 47.57 21.74 25.83 70.48 28.39 0.00 0.00 0.00
May 47.33 17.78 29.56 74.94 20.67 0.00 0.00 0.00
June 49.64 18.87 30.77 86.52 15.90 0.00 0.00 0.00
July 46.80 17.16 29.64 83.23 12.87 0.00 0.00 0.00
August 46.10 17.18 28.92 82.61 12.16 0.00 0.00 0.00
September 38.05 15.96 22.09 59.72 21.44 0.00 0.00 0.00
October 34.23 17.81 16.42 46.12 39.52 0.00 0.00 0.00
November 27.42 12.44 14.98 31.36 48.99 0.00 0.00 0.00
December 22.66 10.05 12.61 21.01 54.99 0.00 0.00 0.00
                 
Annual Sum or Average 38.15 16.30 21.85 55.75 33.40 0.00 0.00 0.00
Minimum of Months 22.66 10.05 12.61 21.01 12.16 0.00 0.00 0.00
Maximum of Months 49.64 21.74 30.77 86.52 61.50 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168640E+09 0.118850E+09 49789936.22 0.207110E+09 0.153556E+09
February 0.142044E+09 96330965.03 45713155.11 0.188986E+09 0.118826E+09
March 0.128140E+09 64576537.96 63563592.79 0.179838E+09 91101943.88
April 76099966.48 15941127.00 60158839.48 0.111632E+09 71592477.65
May 63668783.65 1257.36 63667526.29 95006882.63 51320509.98
June 63841339.76 0.22 63841339.54 0.115514E+09 37160001.38
July 64412796.23 158836.79 64253959.44 0.119363E+09 31064899.72
August 68560021.87 4362326.01 64197695.87 0.129605E+09 29326105.24
September 83423193.98 26410168.46 57013025.52 0.137171E+09 54482758.53
October 0.149402E+09 97313147.03 52088479.15 0.222056E+09 0.103254E+09
November 0.158584E+09 0.106436E+09 52147619.44 0.215973E+09 0.122268E+09
December 0.166359E+09 0.118214E+09 48145445.95 0.212322E+09 0.140610E+09
           
Annual Sum or Average 0.133318E+10 0.648595E+09 0.684581E+09 0.193458E+10 0.100456E+10
Minimum of Months 63668783.65 0.22 45713155.11 95006882.63 29326105.24
Maximum of Months 0.168640E+09 0.118850E+09 64253959.44 0.222056E+09 0.153556E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168638E+09 0.118850E+09 49787919.18 0.207109E+09 0.153555E+09
February 0.142042E+09 96330965.03 45711320.54 0.188985E+09 0.118825E+09
March 0.128113E+09 64562678.78 63550325.67 0.179786E+09 91107957.13
April 75834419.30 15822642.79 60011776.51 0.111030E+09 71628332.57
May 63656215.38 0.00 63656215.38 94983673.95 51319278.33
June 63837880.00 0.00 63837880.00 0.115510E+09 37158742.89
July 64406728.92 157605.76 64249123.15 0.119351E+09 31063813.43
August 68470939.79 4338589.94 64132349.85 0.129408E+09 29324861.34
September 83209844.30 26328599.60 56881244.70 0.136700E+09 54506277.19
October 0.149400E+09 97313147.03 52086513.09 0.222054E+09 0.103252E+09
November 0.158582E+09 0.106436E+09 52145620.55 0.215971E+09 0.122267E+09
December 0.166358E+09 0.118214E+09 48143597.58 0.212321E+09 0.140608E+09
           
Annual Sum or Average 0.133255E+10 0.648354E+09 0.684194E+09 0.193321E+10 0.100462E+10
Minimum of Months 63656215.38 0.00 45711320.54 94983673.95 29324861.34
Maximum of Months 0.168638E+09 0.118850E+09 64249123.15 0.222054E+09 0.153555E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168638E+09 0.118850E+09 49787919.18 0.207109E+09 0.153555E+09
February 0.142042E+09 96330965.03 45711320.54 0.188985E+09 0.118825E+09
March 0.128113E+09 64562678.78 63550325.67 0.179786E+09 91107957.13
April 75834419.30 15822642.79 60011776.51 0.111030E+09 71628332.57
May 63656215.38 0.00 63656215.38 94983673.95 51319278.33
June 63837880.00 0.00 63837880.00 0.115510E+09 37158742.89
July 64406728.92 157605.76 64249123.15 0.119351E+09 31063813.43
August 68470647.49 4338317.57 64132329.92 0.129407E+09 29324861.34
September 83187686.67 26325479.37 56862207.30 0.136677E+09 54529167.46
October 0.149400E+09 97313147.03 52086513.09 0.222054E+09 0.103252E+09
November 0.158582E+09 0.106436E+09 52145620.55 0.215971E+09 0.122267E+09
December 0.166358E+09 0.118214E+09 48143597.58 0.212321E+09 0.140608E+09
           
Annual Sum or Average 0.133253E+10 0.648351E+09 0.684175E+09 0.193318E+10 0.100464E+10
Minimum of Months 63656215.38 0.00 45711320.54 94983673.95 29324861.34
Maximum of Months 0.168638E+09 0.118850E+09 64249123.15 0.222054E+09 0.153555E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168638E+09 0.118850E+09 49787919.18 0.207109E+09 0.153555E+09
February 0.142042E+09 96330965.03 45711320.54 0.188985E+09 0.118825E+09
March 0.128113E+09 64562678.78 63550325.67 0.179786E+09 91107957.13
April 75834419.30 15822642.79 60011776.51 0.111030E+09 71628332.57
May 63656215.38 0.00 63656215.38 94983673.95 51319278.33
June 63837880.00 0.00 63837880.00 0.115510E+09 37158742.89
July 64406728.92 157605.76 64249123.15 0.119351E+09 31063813.43
August 68470645.41 4338315.49 64132329.92 0.129407E+09 29324857.82
September 83190441.45 26325474.50 56864966.95 0.136677E+09 54523595.82
October 0.149400E+09 97313147.03 52086513.09 0.222054E+09 0.103252E+09
November 0.158582E+09 0.106436E+09 52145620.55 0.215971E+09 0.122267E+09
December 0.166358E+09 0.118214E+09 48143597.58 0.212321E+09 0.140608E+09
           
Annual Sum or Average 0.133253E+10 0.648351E+09 0.684178E+09 0.193318E+10 0.100463E+10
Minimum of Months 63656215.38 0.00 45711320.54 94983673.95 29324857.82
Maximum of Months 0.168638E+09 0.118850E+09 64249123.15 0.222054E+09 0.153555E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168638E+09 0.118850E+09 49787919.18 0.207109E+09 0.153555E+09
February 0.142042E+09 96330965.03 45711320.54 0.188985E+09 0.118825E+09
March 0.128113E+09 64562678.78 63550325.67 0.179786E+09 91107957.13
April 75834419.30 15822642.79 60011776.51 0.111030E+09 71628332.57
May 63656215.38 0.00 63656215.38 94983673.95 51319278.33
June 63837880.00 0.00 63837880.00 0.115510E+09 37158742.89
July 64406728.92 157605.76 64249123.15 0.119351E+09 31063813.43
August 68470863.68 4338533.76 64132329.92 0.129407E+09 29324695.02
September 83216233.29 26328788.00 56887445.28 0.136681E+09 54473738.13
October 0.149400E+09 97313147.03 52086513.09 0.222054E+09 0.103252E+09
November 0.158582E+09 0.106436E+09 52145620.55 0.215971E+09 0.122267E+09
December 0.166358E+09 0.118214E+09 48143597.58 0.212321E+09 0.140608E+09
           
Annual Sum or Average 0.133255E+10 0.648355E+09 0.684200E+09 0.193319E+10 0.100458E+10
Minimum of Months 63656215.38 0.00 45711320.54 94983673.95 29324695.02
Maximum of Months 0.168638E+09 0.118850E+09 64249123.15 0.222054E+09 0.153555E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168640E+09 0.118850E+09 49789936.12 0.207110E+09 0.153556E+09
February 0.142044E+09 96330965.03 45713155.01 0.188986E+09 0.118826E+09
March 0.128134E+09 64573476.82 63560592.68 0.179804E+09 91081014.07
April 76084955.93 15937465.45 60147490.48 0.111488E+09 71472300.48
May 63668287.35 1465.58 63666821.77 95006301.93 51320509.92
June 63841351.46 1.53 63841349.93 0.115514E+09 37160001.32
July 64412122.01 158603.83 64253518.18 0.119361E+09 31064899.67
August 68550516.87 4364433.66 64186083.21 0.129593E+09 29325693.70
September 83436474.45 26416744.61 57019729.85 0.137046E+09 54318168.28
October 0.149402E+09 97313147.03 52088479.05 0.222056E+09 0.103254E+09
November 0.158584E+09 0.106436E+09 52147619.34 0.215973E+09 0.122268E+09
December 0.166359E+09 0.118214E+09 48145445.86 0.212322E+09 0.140610E+09
           
Annual Sum or Average 0.133316E+10 0.648597E+09 0.684560E+09 0.193426E+10 0.100426E+10
Minimum of Months 63668287.35 1.53 45713155.01 95006301.93 29325693.70
Maximum of Months 0.168640E+09 0.118850E+09 64253518.18 0.222056E+09 0.153556E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237533E+09 0.166511E+09 71022012.35 0.291546E+09 0.213744E+09
February 0.200157E+09 0.134961E+09 65195888.63 0.265909E+09 0.165646E+09
March 0.198667E+09 0.104473E+09 94193870.38 0.285706E+09 0.127405E+09
April 0.126832E+09 35686452.41 91145127.46 0.196049E+09 0.100348E+09
May 98559274.87 3834428.78 94724846.09 0.151389E+09 72171725.63
June 91642291.17 12098.00 91630193.17 0.164054E+09 52536010.52
July 94091462.12 1013538.93 93077923.19 0.173018E+09 43936898.88
August 0.113066E+09 14533455.67 98532810.69 0.215233E+09 41644656.13
September 0.135408E+09 48902138.34 86505879.39 0.226650E+09 76701181.53
October 0.214579E+09 0.139823E+09 74755836.33 0.319053E+09 0.144454E+09
November 0.223432E+09 0.149118E+09 74313769.10 0.303767E+09 0.170968E+09
December 0.234232E+09 0.165619E+09 68612223.11 0.298761E+09 0.196242E+09
           
Annual Sum or Average 0.196820E+10 0.964487E+09 0.100371E+10 0.289114E+10 0.140580E+10
Minimum of Months 91642291.17 12098.00 65195888.63 0.151389E+09 41644656.13
Maximum of Months 0.237533E+09 0.166511E+09 98532810.69 0.319053E+09 0.213744E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66338589.41 30324633.68 36013955.73 52613682.84 0.157385E+09
February 75644296.17 40983114.42 34661181.75 80646766.34 0.116686E+09
March 0.104099E+09 47427097.20 56671731.21 0.127716E+09 83433668.87
April 0.120521E+09 54519715.26 66000856.17 0.174270E+09 66042815.95
May 0.135690E+09 56825772.85 78864610.15 0.210984E+09 49649377.97
June 0.135621E+09 56170023.09 79451225.90 0.233419E+09 36155978.86
July 0.137205E+09 57417373.32 79787741.62 0.240074E+09 31047260.06
August 0.125897E+09 49749384.95 76147133.13 0.223713E+09 28651809.71
September 0.101198E+09 45017110.06 56180420.06 0.157152E+09 51243727.28
October 90024722.41 46846070.25 43178652.16 0.114222E+09 96863350.26
November 69943165.74 32002281.97 37940883.77 70756291.81 0.116250E+09
December 62805375.01 29027825.37 33777549.64 51965966.39 0.136949E+09
           
Annual Sum or Average 0.122499E+10 0.546310E+09 0.678676E+09 0.173753E+10 0.970358E+09
Minimum of Months 62805375.01 29027825.37 33777549.64 51965966.39 28651809.71
Maximum of Months 0.137205E+09 57417373.32 79787741.62 0.240074E+09 0.157385E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66336572.48 30324633.68 36011938.80 52612429.40 0.157385E+09
February 75642461.70 40983114.42 34659347.28 80645383.75 0.116685E+09
March 0.104096E+09 47427097.20 56668926.37 0.127713E+09 83432188.40
April 0.120517E+09 54519715.26 65997709.82 0.174266E+09 66041310.26
May 0.135687E+09 56825772.85 78860972.44 0.210979E+09 49648075.27
June 0.135618E+09 56170023.09 79447768.99 0.233414E+09 36154655.31
July 0.137201E+09 57417373.32 79784121.86 0.240070E+09 31046115.91
August 0.125893E+09 49749384.95 76143604.33 0.223708E+09 28650568.66
September 0.101195E+09 45017110.06 56177612.63 0.157148E+09 51242257.77
October 90022756.45 46846070.25 43176686.20 0.114220E+09 96861871.84
November 69941166.95 32002281.97 37938884.98 70754464.40 0.116248E+09
December 62803526.74 29027825.37 33775701.37 51964587.71 0.136948E+09
           
Annual Sum or Average 0.122495E+10 0.546310E+09 0.678643E+09 0.173750E+10 0.970342E+09
Minimum of Months 62803526.74 29027825.37 33775701.37 51964587.71 28650568.66
Maximum of Months 0.137201E+09 57417373.32 79784121.86 0.240070E+09 0.157385E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66336572.48 30324633.68 36011938.80 52612429.40 0.157385E+09
February 75642461.70 40983114.42 34659347.28 80645383.75 0.116685E+09
March 0.104096E+09 47427097.20 56668926.37 0.127713E+09 83432188.40
April 0.120517E+09 54519715.26 65997709.82 0.174266E+09 66041310.26
May 0.135687E+09 56825772.85 78860972.44 0.210979E+09 49648075.27
June 0.135618E+09 56170023.09 79447768.99 0.233414E+09 36154655.31
July 0.137201E+09 57417373.32 79784121.86 0.240070E+09 31046115.91
August 0.125893E+09 49749384.95 76143604.33 0.223708E+09 28650568.66
September 0.101195E+09 45017110.06 56177612.63 0.157148E+09 51242257.77
October 90022756.45 46846070.25 43176686.20 0.114220E+09 96861871.84
November 69941166.95 32002281.97 37938884.98 70754464.40 0.116248E+09
December 62803526.74 29027825.37 33775701.37 51964587.71 0.136948E+09
           
Annual Sum or Average 0.122495E+10 0.546310E+09 0.678643E+09 0.173750E+10 0.970342E+09
Minimum of Months 62803526.74 29027825.37 33775701.37 51964587.71 28650568.66
Maximum of Months 0.137201E+09 57417373.32 79784121.86 0.240070E+09 0.157385E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66411465.64 30365098.62 36046367.02 52684837.80 0.157272E+09
February 75652336.64 40987919.48 34664417.16 80658999.01 0.116678E+09
March 0.104099E+09 47427098.96 56671761.97 0.127716E+09 83433629.57
April 0.120521E+09 54519715.26 66000856.34 0.174270E+09 66042816.03
May 0.135690E+09 56825772.85 78864610.34 0.210984E+09 49649378.04
June 0.135621E+09 56170023.09 79451226.08 0.233419E+09 36155978.93
July 0.137205E+09 57417373.32 79787741.81 0.240074E+09 31047260.12
August 0.125897E+09 49749384.95 76147133.31 0.223713E+09 28651809.78
September 0.101198E+09 45017110.06 56180420.21 0.157152E+09 51243727.36
October 90026552.76 46847439.26 43179113.49 0.114227E+09 96863319.71
November 69985648.80 32024054.88 37961593.92 70849070.33 0.116239E+09
December 62902676.17 29079680.58 33822995.59 52122390.26 0.136863E+09
           
Annual Sum or Average 0.122521E+10 0.546431E+09 0.678778E+09 0.173787E+10 0.970140E+09
Minimum of Months 62902676.17 29079680.58 33822995.59 52122390.26 28651809.78
Maximum of Months 0.137205E+09 57417373.32 79787741.81 0.240074E+09 0.157272E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30045884.37 0.00 30045884.37 6734645.39 0.173636E+09
February 30247558.73 0.00 30247558.73 17313628.29 0.127035E+09
March 47058100.22 0.00 47058100.22 41674293.98 87134861.44
April 55114785.50 237039.24 54877746.26 70224026.59 68175945.89
May 67565039.38 1950048.09 65614991.28 0.100040E+09 48867045.57
June 71151812.19 4127469.00 67024343.18 0.127519E+09 35070633.67
July 69677327.08 2998820.29 66678506.79 0.128628E+09 29741592.39
August 62746589.60 635077.18 62111512.42 0.118452E+09 27428525.84
September 45916266.22 6287.85 45909978.37 66793777.78 51470036.15
October 36301597.54 0.00 36301597.54 32412159.07 0.101545E+09
November 31172199.37 0.00 31172199.37 17603673.43 0.124623E+09
December 27789905.48 0.00 27789905.48 6760356.98 0.149245E+09
           
Annual Sum or Average 0.574787E+09 9954741.65 0.564832E+09 0.734155E+09 0.102397E+10
Minimum of Months 27789905.48 0.00 27789905.48 6734645.39 27428525.84
Maximum of Months 71151812.19 4127469.00 67024343.18 0.128628E+09 0.173636E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30043867.33 0.00 30043867.33 6733751.23 0.173635E+09
February 30245724.16 0.00 30245724.16 17312270.19 0.127034E+09
March 47055295.23 0.00 47055295.23 41671368.59 87133495.95
April 55044727.55 221888.29 54822839.26 70217934.86 68321927.21
May 67330561.33 1856218.04 65474343.29 99551477.30 48926453.41
June 70956643.87 4040794.31 66915849.56 0.127057E+09 35069373.82
July 69442414.50 2897627.91 66544786.59 0.128067E+09 29740695.90
August 62577928.42 584399.92 61993528.50 0.118069E+09 27431134.94
September 45913007.52 6267.83 45906739.69 66790676.29 51469922.64
October 36299631.47 0.00 36299631.47 32410364.42 0.101544E+09
November 31170200.48 0.00 31170200.48 17602025.52 0.124622E+09
December 27788057.11 0.00 27788057.11 6759266.13 0.149244E+09
           
Annual Sum or Average 0.573868E+09 9607196.31 0.564261E+09 0.732242E+09 0.102417E+10
Minimum of Months 27788057.11 0.00 27788057.11 6733751.23 27431134.94
Maximum of Months 70956643.87 4040794.31 66915849.56 0.128067E+09 0.173635E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30043867.33 0.00 30043867.33 6733751.23 0.173635E+09
February 30245724.16 0.00 30245724.16 17312270.19 0.127034E+09
March 47055295.23 0.00 47055295.23 41671368.59 87133495.95
April 55031771.30 218954.04 54812817.27 70217852.68 68351416.75
May 67330561.33 1856218.04 65474343.29 99551477.30 48926453.41
June 70956643.87 4040794.31 66915849.56 0.127057E+09 35069373.82
July 69442414.50 2897627.91 66544786.59 0.128067E+09 29740695.90
August 62577388.52 584406.16 61992982.35 0.118070E+09 27433665.07
September 45911543.39 6161.36 45905382.02 66793799.63 51476066.15
October 36299631.47 0.00 36299631.47 32410364.42 0.101544E+09
November 31170200.48 0.00 31170200.48 17602025.52 0.124622E+09
December 27788057.11 0.00 27788057.11 6759266.13 0.149244E+09
           
Annual Sum or Average 0.573853E+09 9604161.82 0.564249E+09 0.732247E+09 0.102421E+10
Minimum of Months 27788057.11 0.00 27788057.11 6733751.23 27433665.07
Maximum of Months 70956643.87 4040794.31 66915849.56 0.128067E+09 0.173635E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30043867.33 0.00 30043867.33 6733751.23 0.173635E+09
February 30245724.16 0.00 30245724.16 17312270.19 0.127034E+09
March 47055295.23 0.00 47055295.23 41671368.59 87133495.95
April 55031771.30 218954.04 54812817.27 70217852.68 68351416.75
May 67330561.33 1856218.04 65474343.29 99551477.30 48926453.41
June 70956643.87 4040794.31 66915849.56 0.127057E+09 35069373.82
July 69442414.50 2897627.91 66544786.59 0.128067E+09 29740695.90
August 62577972.45 584418.96 61993553.49 0.118073E+09 27435650.05
September 45912184.53 6144.37 45906040.15 66799309.81 51480576.81
October 36299631.47 0.00 36299631.47 32410364.42 0.101544E+09
November 31170200.48 0.00 31170200.48 17602025.52 0.124622E+09
December 27788057.11 0.00 27788057.11 6759266.13 0.149244E+09
           
Annual Sum or Average 0.573854E+09 9604157.63 0.564250E+09 0.732255E+09 0.102422E+10
Minimum of Months 27788057.11 0.00 27788057.11 6733751.23 27435650.05
Maximum of Months 70956643.87 4040794.31 66915849.56 0.128067E+09 0.173635E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30043867.33 0.00 30043867.33 6733751.23 0.173635E+09
February 30245724.16 0.00 30245724.16 17312270.19 0.127034E+09
March 47055295.23 0.00 47055295.23 41671368.59 87133495.95
April 55043357.47 221671.07 54821686.40 70237824.72 68345279.65
May 67330561.33 1856218.04 65474343.29 99551477.30 48926453.41
June 70956643.87 4040794.31 66915849.56 0.127057E+09 35069373.82
July 69442414.50 2897627.91 66544786.59 0.128067E+09 29740695.90
August 62578782.29 584437.02 61994345.27 0.118076E+09 27437386.58
September 45913385.96 6177.97 45907208.00 66805213.74 51484353.51
October 36299631.47 0.00 36299631.47 32410364.42 0.101544E+09
November 31170200.48 0.00 31170200.48 17602025.52 0.124622E+09
December 27788057.11 0.00 27788057.11 6759266.13 0.149244E+09
           
Annual Sum or Average 0.573868E+09 9606926.32 0.564261E+09 0.732284E+09 0.102422E+10
Minimum of Months 27788057.11 0.00 27788057.11 6733751.23 27437386.58
Maximum of Months 70956643.87 4040794.31 66915849.56 0.128067E+09 0.173635E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 30045884.26 0.00 30045884.26 6734645.35 0.173636E+09
February 30247558.63 0.00 30247558.63 17313628.22 0.127035E+09
March 47058100.08 0.00 47058100.08 41674293.83 87134861.37
April 55119357.93 238100.21 54881257.72 70367210.87 68311960.46
May 67549720.65 1938542.57 65611178.08 0.100058E+09 48927643.25
June 71147968.66 4120185.66 67027783.00 0.127498E+09 35070633.61
July 69652277.10 2972993.79 66679283.30 0.128546E+09 29741829.96
August 62744695.82 630648.85 62114046.98 0.118445E+09 27438717.67
September 45917140.76 6191.76 45910949.01 66810567.50 51485886.73
October 36301597.44 0.00 36301597.44 32412158.98 0.101545E+09
November 31172199.27 0.00 31172199.27 17603673.35 0.124623E+09
December 27789905.38 0.00 27789905.38 6760356.92 0.149245E+09
           
Annual Sum or Average 0.574746E+09 9906662.83 0.564840E+09 0.734223E+09 0.102420E+10
Minimum of Months 27789905.38 0.00 27789905.38 6734645.35 27438717.67
Maximum of Months 71147968.66 4120185.66 67027783.00 0.128546E+09 0.173636E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 68402769.20 32188317.65 36214451.55 60919519.99 0.164629E+09
February 70541954.16 33286726.72 37255227.45 79097861.55 0.124379E+09
March 0.114498E+09 55553088.88 58945114.32 0.150490E+09 91424658.39
April 0.123296E+09 56344473.89 66951568.69 0.182682E+09 73599464.42
May 0.126776E+09 47613280.42 79162330.35 0.200712E+09 55360099.06
June 0.128669E+09 48908055.39 79761437.64 0.224258E+09 41206072.52
July 0.125356E+09 45962469.43 79393746.68 0.222928E+09 34478307.77
August 0.123481E+09 46013787.73 77467400.38 0.221252E+09 32557589.68
September 98634725.68 41379970.63 57254755.05 0.154784E+09 55565904.46
October 91682732.73 47710913.17 43971819.56 0.123532E+09 0.105856E+09
November 71123295.77 32265259.23 38858036.54 81373834.11 0.126971E+09
December 60791710.39 26977083.17 33814627.22 56439894.19 0.147243E+09
           
Annual Sum or Average 0.120325E+10 0.514203E+09 0.689051E+09 0.175847E+10 0.105327E+10
Minimum of Months 60791710.39 26977083.17 33814627.22 56439894.19 32557589.68
Maximum of Months 0.128669E+09 56344473.89 79761437.64 0.224258E+09 0.164629E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 68332031.00 32149607.73 36182423.26 60840102.02 0.164722E+09
February 70532639.82 33282738.45 37249901.37 79082422.68 0.124382E+09
March 0.114495E+09 55553087.94 58942224.56 0.150487E+09 91423287.96
April 0.123293E+09 56344473.89 66948422.34 0.182679E+09 73598133.47
May 0.126772E+09 47613280.42 79158692.64 0.200707E+09 55358904.11
June 0.128666E+09 48908055.39 79757980.73 0.224254E+09 41204869.16
July 0.125353E+09 45962469.43 79390126.93 0.222923E+09 34477197.04
August 0.123478E+09 46013787.73 77463871.58 0.221248E+09 32556305.69
September 98631918.24 41379970.63 57251947.61 0.154780E+09 55564462.13
October 91679086.17 47709609.23 43969476.95 0.123526E+09 0.105854E+09
November 71081194.86 32246318.82 38834876.04 81283479.63 0.126975E+09
December 60695252.07 26926434.46 33768817.61 56260361.01 0.147297E+09
           
Annual Sum or Average 0.120301E+10 0.514090E+09 0.688919E+09 0.175807E+10 0.105341E+10
Minimum of Months 60695252.07 26926434.46 33768817.61 56260361.01 32556305.69
Maximum of Months 0.128666E+09 56344473.89 79757980.73 0.224254E+09 0.164722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 68332031.00 32149607.73 36182423.26 60840102.02 0.164722E+09
February 70532639.82 33282738.45 37249901.37 79082422.68 0.124382E+09
March 0.114495E+09 55553087.94 58942224.56 0.150487E+09 91423287.96
April 0.123293E+09 56344473.89 66948422.34 0.182679E+09 73598133.47
May 0.126772E+09 47613280.42 79158692.64 0.200707E+09 55358904.11
June 0.128666E+09 48908055.39 79757980.73 0.224254E+09 41204869.16
July 0.125353E+09 45962469.43 79390126.93 0.222923E+09 34477197.04
August 0.123478E+09 46013787.73 77463871.58 0.221248E+09 32556305.69
September 98631918.24 41379970.63 57251947.61 0.154780E+09 55564462.13
October 91679086.17 47709609.23 43969476.95 0.123526E+09 0.105854E+09
November 71081194.86 32246318.82 38834876.04 81283479.63 0.126975E+09
December 60695252.07 26926434.46 33768817.61 56260361.01 0.147297E+09
           
Annual Sum or Average 0.120301E+10 0.514090E+09 0.688919E+09 0.175807E+10 0.105341E+10
Minimum of Months 60695252.07 26926434.46 33768817.61 56260361.01 32556305.69
Maximum of Months 0.128666E+09 56344473.89 79757980.73 0.224254E+09 0.164722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 68334048.04 32149607.73 36184440.30 60841266.18 0.164723E+09
February 70534474.39 33282738.45 37251735.94 79083921.14 0.124383E+09
March 0.114498E+09 55553087.94 58945029.55 0.150490E+09 91424658.46
April 0.123296E+09 56344473.89 66951568.85 0.182682E+09 73599464.49
May 0.126776E+09 47613280.42 79162330.54 0.200712E+09 55360099.12
June 0.128669E+09 48908055.39 79761437.82 0.224258E+09 41206072.59
July 0.125356E+09 45962469.43 79393746.87 0.222928E+09 34478307.83
August 0.123481E+09 46013787.73 77467400.56 0.221252E+09 32557589.74
September 98634725.82 41379970.63 57254755.20 0.154784E+09 55565904.53
October 91681052.24 47709609.23 43971443.01 0.123527E+09 0.105856E+09
November 71083193.76 32246318.82 38836874.93 81285184.38 0.126976E+09
December 60697100.44 26926434.46 33770665.98 56261587.75 0.147298E+09
           
Annual Sum or Average 0.120304E+10 0.514090E+09 0.688951E+09 0.175811E+10 0.105343E+10
Minimum of Months 60697100.44 26926434.46 33770665.98 56261587.75 32557589.74
Maximum of Months 0.128669E+09 56344473.89 79761437.82 0.224258E+09 0.164723E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 572.80 423.79 466.46 328.41 138.05 0.00 0.00
February 578.63 363.18 435.03 294.70 140.32 0.00 0.00
March 509.44 251.64 361.18 183.64 177.54 0.00 0.00
April 333.03 204.41 224.67 50.48 174.19 0.00 0.00
May 269.32 141.91 179.41 1.43 177.97 0.00 0.00
June 330.68 106.28 183.13 0.00 183.13 0.00 0.00
July 331.97 85.99 179.41 0.73 178.68 0.00 0.00
August 370.39 81.24 195.66 15.16 180.50 0.00 0.00
September 404.15 155.66 245.01 79.88 165.14 0.00 0.00
October 616.55 285.23 414.79 270.20 144.59 0.00 0.00
November 617.13 348.98 453.29 303.91 149.38 0.00 0.00
December 587.17 388.25 460.12 326.65 133.47 0.00 0.00
               
Annual Sum or Average 459.56 235.70 315.98 153.95 162.02 0.00 0.00
Minimum of Months 269.32 81.24 179.41 0.00 133.47 0.00 0.00
Maximum of Months 617.13 423.79 466.46 328.41 183.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 78.60 235.00 99.10 45.30 53.79 0.00 0.00
February 133.35 192.93 125.08 67.77 57.31 0.00 0.00
March 190.73 124.60 155.46 70.83 84.63 0.00 0.00
April 268.93 101.92 185.99 84.14 101.85 0.00 0.00
May 315.09 74.15 202.64 84.87 117.78 0.00 0.00
June 360.21 55.80 209.29 86.68 122.61 0.00 0.00
July 358.53 46.37 204.90 85.75 119.15 0.00 0.00
August 334.10 42.79 188.01 74.30 113.72 0.00 0.00
September 242.52 79.08 156.17 69.47 86.70 0.00 0.00
October 170.58 144.66 134.44 69.96 64.48 0.00 0.00
November 109.23 179.39 107.95 49.39 58.56 0.00 0.00
December 77.66 204.49 93.83 43.37 50.46 0.00 0.00
               
Annual Sum or Average 220.40 123.07 155.38 69.30 86.08 0.00 0.00
Minimum of Months 77.66 42.79 93.83 43.37 50.46 0.00 0.00
Maximum of Months 360.21 235.00 209.29 86.68 122.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 15.09 388.97 67.30 0.00 67.30 0.00 0.00
February 42.94 315.07 75.02 0.00 75.02 0.00 0.00
March 93.35 195.19 105.41 0.00 105.41 0.00 0.00
April 162.61 158.12 127.46 0.52 126.94 0.00 0.00
May 223.38 109.58 151.00 4.22 146.78 0.00 0.00
June 294.46 81.18 164.40 9.42 154.98 0.00 0.00
July 287.28 66.62 155.73 6.56 149.17 0.00 0.00
August 264.78 61.46 140.31 1.35 138.96 0.00 0.00
September 154.63 119.16 106.28 0.01 106.27 0.00 0.00
October 72.61 227.47 81.32 0.00 81.32 0.00 0.00
November 40.75 288.48 72.15 0.00 72.15 0.00 0.00
December 15.14 334.33 62.25 0.00 62.25 0.00 0.00
               
Annual Sum or Average 139.44 194.86 109.24 1.85 107.39 0.00 0.00
Minimum of Months 15.09 61.46 62.25 0.00 62.25 0.00 0.00
Maximum of Months 294.46 388.97 164.40 9.42 154.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 90.89 245.97 102.08 48.03 54.05 0.00 0.00
February 130.76 205.66 116.63 55.03 61.59 0.00 0.00
March 224.74 136.54 170.99 82.96 88.03 0.00 0.00
April 281.91 113.58 190.27 86.95 103.32 0.00 0.00
May 299.75 82.68 189.33 71.11 118.22 0.00 0.00
June 346.07 63.59 198.56 75.48 123.09 0.00 0.00
July 332.92 51.49 187.21 68.64 118.57 0.00 0.00
August 330.42 48.62 184.41 68.72 115.69 0.00 0.00
September 238.86 85.75 152.21 63.86 88.35 0.00 0.00
October 184.48 158.09 136.92 71.25 65.67 0.00 0.00
November 125.47 195.95 109.71 49.77 59.94 0.00 0.00
December 84.09 219.96 90.68 40.23 50.45 0.00 0.00
               
Annual Sum or Average 223.01 133.61 152.60 65.21 87.39 0.00 0.00
Minimum of Months 84.09 48.62 90.68 40.23 50.45 0.00 0.00
Maximum of Months 346.07 245.97 198.56 86.95 123.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.153419E+10 0.113507E+10 0.124937E+10 0.879613E+09 0.369754E+09 0.00 0.00
February 0.139982E+10 0.878595E+09 0.105241E+10 0.712947E+09 0.339467E+09 0.00 0.00
March 0.136448E+10 0.674005E+09 0.967393E+09 0.491873E+09 0.475519E+09 0.00 0.00
April 0.863205E+09 0.529840E+09 0.582354E+09 0.130856E+09 0.451499E+09 0.00 0.00
May 0.721335E+09 0.380087E+09 0.480521E+09 3837151.71 0.476684E+09 0.00 0.00
June 0.857121E+09 0.275489E+09 0.474677E+09 12099.75 0.474664E+09 0.00 0.00
July 0.889145E+09 0.230319E+09 0.480543E+09 1961402.60 0.478582E+09 0.00 0.00
August 0.992056E+09 0.217594E+09 0.524060E+09 40613972.10 0.483446E+09 0.00 0.00
September 0.104755E+10 0.403480E+09 0.635072E+09 0.207037E+09 0.428034E+09 0.00 0.00
October 0.165137E+10 0.763968E+09 0.111098E+10 0.723702E+09 0.387279E+09 0.00 0.00
November 0.159959E+10 0.904565E+09 0.117493E+10 0.787734E+09 0.387191E+09 0.00 0.00
December 0.157267E+10 0.103988E+10 0.123238E+10 0.874903E+09 0.357478E+09 0.00 0.00
               
Annual Sum or Average 0.144925E+11 0.743289E+10 0.996469E+10 0.485509E+10 0.510960E+10 0.00 0.00
Minimum of Months 0.721335E+09 0.217594E+09 0.474677E+09 12099.75 0.339467E+09 0.00 0.00
Maximum of Months 0.165137E+10 0.113507E+10 0.124937E+10 0.879613E+09 0.483446E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.210519E+09 0.629422E+09 0.265423E+09 0.121339E+09 0.144084E+09 0.00 0.00
February 0.322597E+09 0.466733E+09 0.302582E+09 0.163937E+09 0.138644E+09 0.00 0.00
March 0.510858E+09 0.333732E+09 0.416390E+09 0.189708E+09 0.226681E+09 0.00 0.00
April 0.697070E+09 0.264168E+09 0.482076E+09 0.218079E+09 0.263997E+09 0.00 0.00
May 0.843925E+09 0.198595E+09 0.542754E+09 0.227303E+09 0.315451E+09 0.00 0.00
June 0.933666E+09 0.144621E+09 0.542478E+09 0.224680E+09 0.317798E+09 0.00 0.00
July 0.960288E+09 0.124187E+09 0.548813E+09 0.229669E+09 0.319144E+09 0.00 0.00
August 0.894842E+09 0.114605E+09 0.503579E+09 0.198998E+09 0.304581E+09 0.00 0.00
September 0.628600E+09 0.204972E+09 0.404785E+09 0.180068E+09 0.224716E+09 0.00 0.00
October 0.456890E+09 0.387450E+09 0.360097E+09 0.187386E+09 0.172711E+09 0.00 0.00
November 0.283114E+09 0.464985E+09 0.279811E+09 0.128031E+09 0.151780E+09 0.00 0.00
December 0.208014E+09 0.547705E+09 0.251315E+09 0.116163E+09 0.135152E+09 0.00 0.00
               
Annual Sum or Average 0.695038E+10 0.388117E+10 0.490010E+10 0.218536E+10 0.271474E+10 0.00 0.00
Minimum of Months 0.208014E+09 0.114605E+09 0.251315E+09 0.116163E+09 0.135152E+09 0.00 0.00
Maximum of Months 0.960288E+09 0.629422E+09 0.548813E+09 0.229669E+09 0.319144E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 40404295.66 0.104181E+10 0.180267E+09 0.00 0.180267E+09 0.00 0.00
February 0.103876E+09 0.762208E+09 0.181478E+09 0.00 0.181478E+09 0.00 0.00
March 0.250034E+09 0.522804E+09 0.282337E+09 0.00 0.282337E+09 0.00 0.00
April 0.421479E+09 0.409854E+09 0.330386E+09 1356606.88 0.329029E+09 0.00 0.00
May 0.598300E+09 0.293497E+09 0.404437E+09 11313462.82 0.393124E+09 0.00 0.00
June 0.763247E+09 0.210419E+09 0.426126E+09 24410831.91 0.401716E+09 0.00 0.00
July 0.769442E+09 0.178446E+09 0.417099E+09 17562325.72 0.399537E+09 0.00 0.00
August 0.709182E+09 0.164601E+09 0.375803E+09 3603388.10 0.372200E+09 0.00 0.00
September 0.400793E+09 0.308866E+09 0.275484E+09 37231.14 0.275446E+09 0.00 0.00
October 0.194466E+09 0.609264E+09 0.217802E+09 0.00 0.217802E+09 0.00 0.00
November 0.105615E+09 0.747734E+09 0.187025E+09 0.00 0.187025E+09 0.00 0.00
December 40557778.43 0.895468E+09 0.166732E+09 0.00 0.166732E+09 0.00 0.00
               
Annual Sum or Average 0.439740E+10 0.614497E+10 0.344498E+10 58283846.56 0.338669E+10 0.00 0.00
Minimum of Months 40404295.66 0.164601E+09 0.166732E+09 0.00 0.166732E+09 0.00 0.00
Maximum of Months 0.769442E+09 0.104181E+10 0.426126E+09 24410831.91 0.401716E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.243438E+09 0.658793E+09 0.273401E+09 0.128637E+09 0.144764E+09 0.00 0.00
February 0.316347E+09 0.497525E+09 0.282142E+09 0.133135E+09 0.149007E+09 0.00 0.00
March 0.601955E+09 0.365696E+09 0.457987E+09 0.222212E+09 0.235775E+09 0.00 0.00
April 0.730722E+09 0.294395E+09 0.493178E+09 0.225378E+09 0.267800E+09 0.00 0.00
May 0.802839E+09 0.221438E+09 0.507095E+09 0.190453E+09 0.316642E+09 0.00 0.00
June 0.897023E+09 0.164822E+09 0.514671E+09 0.195632E+09 0.319039E+09 0.00 0.00
July 0.891703E+09 0.137911E+09 0.501418E+09 0.183850E+09 0.317568E+09 0.00 0.00
August 0.885000E+09 0.130228E+09 0.493918E+09 0.184055E+09 0.309863E+09 0.00 0.00
September 0.619128E+09 0.222261E+09 0.394533E+09 0.165520E+09 0.229013E+09 0.00 0.00
October 0.494110E+09 0.423420E+09 0.366722E+09 0.190840E+09 0.175882E+09 0.00 0.00
November 0.325225E+09 0.507896E+09 0.284369E+09 0.129004E+09 0.155365E+09 0.00 0.00
December 0.225215E+09 0.589129E+09 0.242879E+09 0.107756E+09 0.135123E+09 0.00 0.00
               
Annual Sum or Average 0.703270E+10 0.421351E+10 0.481231E+10 0.205647E+10 0.275584E+10 0.00 0.00
Minimum of Months 0.225215E+09 0.130228E+09 0.242879E+09 0.107756E+09 0.135123E+09 0.00 0.00
Maximum of Months 0.897023E+09 0.658793E+09 0.514671E+09 0.225378E+09 0.319039E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.536712E+09 -460002855.3 0.00 0.00 744.00 0.00 -76708662.0 58.99 0.00 0.00
February 0.484309E+09 -417140281.1 0.00 0.00 672.00 0.00 -67168488.3 58.99 0.00 0.00
March 0.557803E+09 -487582202.9 0.00 0.00 744.00 0.00 -70221143.2 59.01 0.00 0.00
April 0.463305E+09 -397135187.5 0.00 0.00 720.00 0.00 -66169465.3 58.99 0.00 0.00
May 0.469000E+09 -402400100.3 0.00 0.00 744.00 0.00 -66599772.1 58.97 0.00 0.00
June 0.432245E+09 -369192003.5 0.00 0.00 720.00 0.00 -63052667.6 59.01 0.00 0.00
July 0.382395E+09 -318298203.3 0.00 0.00 744.00 0.00 -64096809.5 59.02 0.00 0.00
August 0.429288E+09 -365180930.4 0.00 0.00 744.00 0.00 -64107178.5 59.00 0.00 0.00
September 0.396376E+09 -333338835.1 0.00 0.00 720.00 0.00 -63036837.4 58.98 0.00 0.00
October 0.445789E+09 -378586205.7 0.00 0.00 744.00 0.00 -67202796.7 59.00 0.00 0.00
November 0.479303E+09 -412036936.7 0.00 0.00 720.00 0.00 -67265577.4 58.99 0.00 0.00
December 0.493926E+09 -420540151.3 0.00 0.00 744.00 0.00 -73385635.4 59.00 0.00 0.00
                     
Annual Sum or Average 0.557045E+10 -0.476143E+10 0.00 0.00 8760.00 0.00 -809015033.4 59.00 0.00 0.00
Minimum of Months 0.382395E+09 -487582202.9 0.00 0.00 672.00 0.00 -76708662.0 58.97 0.00 0.00
Maximum of Months 0.557803E+09 -318298203.3 0.00 0.00 744.00 0.00 -63036837.4 59.02 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.77 0.73 01-JAN-11:20 1239.04 25.03 138.50 203.67 539.34 22.99 155.50 164.17
February 263.00 0.78 0.73 01-FEB-13:00 2048.55 26.08 138.33 185.50 388.11 20.14 104.00 137.67
March 351.67 0.78 0.73 01-MAR-12:00 418.02 16.74 4.00 211.50 323.34 20.86 166.17 155.33
April 369.33 0.80 0.73 01-APR-11:39 324.12 16.07 0.00 152.17 240.23 20.23 155.00 60.83
May 407.00 0.81 0.73 01-MAY-13:30 294.14 16.05 0.00 146.00 213.99 20.23 175.33 3.17
June 411.67 0.81 0.73 01-JUN-11:09 277.74 15.71 0.00 113.67 203.39 19.90 156.67 0.17
July 411.00 0.81 0.73 01-JUL-10:00 292.60 15.93 0.00 144.83 212.92 20.09 181.17 6.83
August 390.50 0.79 0.73 01-AUG-11:50 353.32 16.75 0.00 208.83 255.43 20.90 231.50 66.83
September 298.50 0.79 0.73 01-SEP-09:39 391.18 17.05 6.50 175.50 287.95 20.86 165.33 106.67
October 293.50 0.77 0.73 01-OCT-11:09 1199.90 23.02 113.17 226.33 380.74 20.55 121.17 152.33
November 299.00 0.77 0.73 01-NOV-09:39 1263.60 25.34 148.17 215.67 470.68 25.35 227.17 178.33
December 285.17 0.77 0.73 01-DEC-07:00 819.11 23.70 111.17 198.17 598.81 24.33 178.67 158.33
                         
Annual Sum or Average 4071.00 0.79     672.62 19.22 659.83 2181.83 326.34 21.22 2017.67 1190.67
Minimum of Months 263.00 0.77 0.73   277.74 15.71 0.00 113.67 203.39 19.90 104.00 0.17
Maximum of Months 411.67 0.81 0.73   2048.55 26.08 148.17 226.33 598.81 25.35 231.50 178.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.85 0.73 04-JAN-09:09 550.12 16.81 48.33 65.17 314.14 20.53 80.67 41.83
February 263.00 0.85 0.73 02-FEB-08:30 773.89 16.51 40.50 67.33 480.16 20.63 60.50 45.17
March 351.67 0.84 0.73 02-MAR-08:50 281.31 14.28 1.67 96.83 223.63 18.96 73.67 61.17
April 369.33 0.83 0.73 02-APR-09:39 292.54 14.16 0.00 109.67 242.87 19.07 83.00 81.50
May 407.00 0.82 0.73 01-MAY-08:39 308.42 14.72 0.00 131.00 260.33 19.61 114.17 98.17
June 411.67 0.82 0.73 01-JUN-07:30 306.38 14.66 0.00 130.17 260.97 19.58 116.83 103.33
July 411.00 0.82 0.73 01-JUL-06:30 313.50 14.79 0.00 130.67 267.53 19.71 128.50 105.67
August 390.50 0.82 0.73 01-AUG-06:00 323.51 15.09 0.00 133.17 267.12 19.90 130.83 96.67
September 298.50 0.83 0.73 01-SEP-08:20 303.60 14.42 0.67 91.83 249.47 19.21 78.83 69.83
October 293.50 0.84 0.73 01-OCT-11:30 927.33 16.44 45.00 85.33 228.50 18.30 50.00 63.50
November 299.00 0.85 0.73 01-NOV-09:39 639.10 17.08 54.50 72.17 481.38 22.54 97.83 53.17
December 285.17 0.84 0.73 01-DEC-08:09 742.24 19.24 76.33 69.00 367.46 21.82 78.50 42.50
                         
Annual Sum or Average 4071.00 0.83     452.66 15.52 267.00 1182.33 295.71 19.92 1093.33 862.50
Minimum of Months 263.00 0.82 0.73   281.31 14.16 0.00 65.17 223.63 18.30 50.00 41.83
Maximum of Months 411.67 0.85 0.73   927.33 19.24 76.33 133.17 481.38 22.54 130.83 105.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.92 0.84 30-JAN-14:30 113.54 11.66 0.00 0.00 82.49 15.69 0.00 0.00
February 263.00 0.92 0.81 22-FEB-11:30 121.31 11.80 0.00 0.00 88.72 15.79 0.00 0.00
March 351.67 0.89 0.79 29-MAR-10:30 157.16 13.65 0.00 0.00 112.51 17.52 0.00 0.00
April 369.33 0.87 0.74 24-APR-09:30 190.51 14.67 0.00 0.00 132.90 18.40 0.00 0.00
May 407.00 0.83 0.74 30-MAY-15:30 240.73 15.89 0.00 8.33 164.07 19.68 11.17 0.00
June 411.67 0.82 0.74 28-JUN-16:30 261.82 16.16 0.00 30.33 184.86 21.22 78.83 4.83
July 411.00 0.82 0.74 12-JUL-09:30 257.73 16.09 0.00 19.83 177.90 20.90 58.33 1.00
August 390.50 0.83 0.74 09-AUG-09:30 240.81 15.83 0.00 2.83 162.45 19.54 6.00 0.00
September 298.50 0.88 0.74 05-SEP-11:30 179.74 14.41 0.00 0.00 126.46 18.14 0.00 0.00
October 293.50 0.91 0.81 02-OCT-14:30 127.77 12.22 0.00 0.00 94.55 16.28 0.00 0.00
November 299.00 0.92 0.83 10-NOV-14:30 118.55 11.98 0.00 0.00 86.38 15.94 0.00 0.00
December 285.17 0.92 0.85 28-DEC-12:30 109.97 11.70 0.00 0.00 80.59 15.80 0.00 0.00
                         
Annual Sum or Average 4071.00 0.87     185.27 14.11 0.00 61.33 130.12 18.20 154.33 5.83
Minimum of Months 263.00 0.82 0.74   109.97 11.66 0.00 0.00 80.59 15.69 0.00 0.00
Maximum of Months 411.67 0.92 0.85   261.82 16.16 0.00 30.33 184.86 21.22 78.83 4.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.84 0.73 04-JAN-14:20 891.19 18.84 72.17 77.33 522.56 22.45 96.00 47.67
February 263.00 0.85 0.73 01-FEB-14:30 273.89 13.61 0.00 81.50 368.88 20.72 91.50 59.83
March 351.67 0.83 0.73 02-MAR-15:09 303.94 14.57 0.00 115.67 244.78 19.22 97.33 76.67
April 369.33 0.83 0.73 01-APR-14:30 296.84 14.45 0.00 114.33 245.32 19.19 88.67 80.67
May 407.00 0.82 0.73 01-MAY-13:50 302.90 14.95 0.00 124.50 252.07 19.71 126.50 90.50
June 411.67 0.82 0.73 01-JUN-13:50 302.80 14.89 0.00 127.17 254.91 19.68 128.00 95.33
July 411.00 0.82 0.73 01-JUL-14:20 304.95 14.94 0.00 123.67 254.87 19.69 129.83 95.50
August 390.50 0.81 0.73 01-AUG-13:39 329.18 15.38 0.00 139.33 269.35 20.06 145.50 102.00
September 298.50 0.82 0.73 01-SEP-13:00 315.29 14.91 3.17 102.50 252.77 19.52 95.67 73.83
October 293.50 0.84 0.73 01-OCT-13:39 880.82 16.77 48.50 91.50 243.78 18.58 64.67 58.00
November 299.00 0.84 0.73 01-NOV-13:39 634.55 17.32 55.33 76.33 414.54 22.47 98.33 58.67
December 285.17 0.85 0.73 01-DEC-14:09 704.13 19.09 76.83 64.00 359.22 21.89 81.17 42.00
                         
Annual Sum or Average 4071.00 0.83     440.32 15.69 256.00 1237.83 298.81 20.17 1243.17 880.67
Minimum of Months 263.00 0.81 0.73   273.89 13.61 0.00 64.00 243.78 18.58 64.67 42.00
Maximum of Months 411.67 0.85 0.73   891.19 19.09 76.83 139.33 522.56 22.47 145.50 102.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.746718E+09 6651.14 19-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.296544E+09 6471.29 08-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 952388.87 3592.69 20-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 546375.50 3642.50 22-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 69284106.69 5722.88 22-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111404E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.746718E+09 6651.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160193E+10 7241.11 19-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.969150E+09 6667.13 16-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.220021E+09 5927.88 23-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 96542591.59 6032.28 27-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 1831368.24 4569.02 11-MAY-07:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 22084355.38 5512.88 31-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 92008493.56 5347.25 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.443750E+09 5830.55 29-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.344732E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160193E+10 7241.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110117E+10 4685.98 31-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.607170E+09 4673.18 08-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 57955247.59 4295.76 23-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 7844721.11 3840.60 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 531583.08 2304.87 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 12093122.89 3228.74 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.244652E+09 4225.23 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.203142E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110117E+10 4685.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.211041E+10 7093.00 19-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.122509E+10 6550.40 16-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.169154E+09 6494.84 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 35388628.82 5994.02 10-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1486081.00 5001.40 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 62542161.95 6202.06 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.626249E+09 6352.19 06-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.423032E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.211041E+10 7093.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108198E+10 4757.65 18-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.615458E+09 5182.04 08-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 54045874.94 4821.65 23-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 12076993.09 4324.55 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 249632.21 969.62 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 24278850.34 3404.47 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.273163E+09 4757.65 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.206125E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108198E+10 5182.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 27817863.65 3490.52 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 13186768.39 3490.52 02-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 771.12 5.14 22-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 5638927.53 3490.52 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 46644330.69     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 27817863.65 3490.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.260638E+09 5410.56 06-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.147154E+09 5410.56 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 503677.53 3166.50 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 2910058.35 4710.19 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 45412.18 302.75 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 10885073.00 5410.56 22-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 51615171.26 5410.56 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.473752E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.260638E+09 5410.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 50853558.83 3376.23 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 39521744.90 3376.23 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 278760.09 2787.60 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 608098.77 3376.23 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1226777.39 3376.23 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 8249700.88 3376.23 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100739E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 50853558.83 3376.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152766E+09 5390.04 06-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.128682E+09 5390.04 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 629270.46 3312.80 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 1281370.38 4504.38 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2907876.30 5390.04 22-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 29969572.33 5390.04 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.316236E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152766E+09 5390.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 32317726.60 3399.39 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 37443029.79 3399.39 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 89584.08 895.84 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 274610.13 2374.11 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1011208.73 3399.39 22-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 6614993.20 3399.39 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 77751152.52     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 37443029.79 3399.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 78035408.14 73694563.81 1902.97 28-FEB-15:00 1746.71 0.00
March 0.00 0.00 0.636450E+09 0.493079E+09 6664.44 31-MAR-07:03 4393.93 0.00
April 0.00 0.00 0.128694E+10 0.102785E+10 6575.75 21-APR-07:03 4458.84 0.00
May 0.00 0.00 0.264716E+10 0.197575E+10 6929.18 26-MAY-07:03 3825.52 0.00
June 0.00 0.00 0.427876E+10 0.314359E+10 7055.24 26-JUN-06:02 4283.03 0.00
July 0.00 0.00 0.456495E+10 0.324733E+10 7153.67 27-JUL-06:03 3599.08 0.00
August 0.00 0.00 0.536270E+10 0.372107E+10 7195.74 24-AUG-06:02 3664.25 0.00
September 0.00 0.00 0.352727E+10 0.260053E+10 7080.11 07-SEP-06:02 3956.23 0.00
October 0.00 0.00 0.192687E+10 0.145023E+10 6988.33 19-OCT-07:02 3609.11 0.00
November 0.00 0.00 0.667188E+09 0.554943E+09 3440.86 03-NOV-07:03 2329.22 0.00
December 0.00 0.00 0.117449E+09 79276903.27 2122.05 13-DEC-13:10 1322.94 0.00
                 
Annual Sum or Average 0.00 0.00 0.250938E+11 0.183673E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.536270E+10 0.372107E+10 7195.74   4458.84 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 5310400.41 4793189.36 551.46 31-JAN-14:50 502.32 0.00
February 0.00 0.00 0.169364E+09 0.169326E+09 2687.62 28-FEB-15:30 2687.62 0.00
March 0.00 0.00 0.448599E+09 0.387925E+09 3955.30 30-MAR-14:10 3484.18 0.00
April 0.00 0.00 0.648616E+09 0.573485E+09 3284.24 19-APR-14:25 2821.92 0.00
May 0.00 0.00 0.156037E+10 0.121618E+10 6691.51 30-MAY-07:02 4123.49 0.00
June 0.00 0.00 0.343497E+10 0.257857E+10 7102.47 26-JUN-06:02 4206.75 0.00
July 0.00 0.00 0.393776E+10 0.286618E+10 7160.46 26-JUL-07:02 3310.43 0.00
August 0.00 0.00 0.501004E+10 0.357665E+10 7228.72 24-AUG-06:02 3506.18 0.00
September 0.00 0.00 0.317233E+10 0.248026E+10 7063.86 07-SEP-06:02 4103.99 0.00
October 0.00 0.00 0.182209E+10 0.151785E+10 6973.47 19-OCT-07:02 3551.91 0.00
November 0.00 0.00 0.748818E+09 0.696177E+09 4281.33 06-NOV-14:30 4281.33 0.00
December 0.00 0.00 0.233621E+09 0.202945E+09 3390.93 12-DEC-14:00 2765.28 0.00
                 
Annual Sum or Average 0.00 0.00 0.211919E+11 0.162704E+11       0.00
Minimum of Months 0.00 0.00 5310400.41 4793189.36 551.46   502.32 0.00
Maximum of Months 0.00 0.00 0.501004E+10 0.357665E+10 7228.72   4281.33 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 26987348.61 26987348.61 920.10 28-FEB-15:10 920.10 0.00
March 0.00 0.00 0.178670E+09 0.152656E+09 1623.73 30-MAR-16:00 1476.64 0.00
April 0.00 0.00 0.485874E+09 0.446006E+09 2016.38 17-APR-11:00 1901.38 0.00
May 0.00 0.00 0.121709E+10 0.103103E+10 4969.43 31-MAY-07:03 3138.75 0.00
June 0.00 0.00 0.232675E+10 0.192746E+10 5115.37 26-JUN-06:02 3334.44 0.00
July 0.00 0.00 0.262433E+10 0.212605E+10 5141.10 27-JUL-06:03 2876.99 0.00
August 0.00 0.00 0.307972E+10 0.244029E+10 5181.88 21-AUG-06:01 3054.41 0.00
September 0.00 0.00 0.190094E+10 0.158984E+10 5093.49 05-SEP-06:02 3292.86 0.00
October 0.00 0.00 0.884980E+09 0.756830E+09 5056.26 19-OCT-07:02 2866.34 0.00
November 0.00 0.00 0.226464E+09 0.208541E+09 1331.56 03-NOV-15:00 1086.74 0.00
December 0.00 0.00 28759666.50 21654533.45 893.24 13-DEC-13:10 648.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.129806E+11 0.107273E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.307972E+10 0.244029E+10 5181.88   3334.44 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 9677970.30 9677970.30 853.13 28-FEB-16:57 853.13 0.00
March 0.00 0.00 0.159193E+09 0.121832E+09 2370.60 30-MAR-15:53 2085.90 0.00
April 0.00 0.00 0.469808E+09 0.396909E+09 2569.74 19-APR-14:55 2200.74 0.00
May 0.00 0.00 0.152915E+10 0.120673E+10 6706.45 31-MAY-07:03 3992.63 0.00
June 0.00 0.00 0.320067E+10 0.250275E+10 6928.79 26-JUN-06:02 4253.74 0.00
July 0.00 0.00 0.364302E+10 0.278408E+10 6946.21 27-JUL-06:03 3687.63 0.00
August 0.00 0.00 0.439581E+10 0.328980E+10 7017.88 21-AUG-06:01 3895.99 0.00
September 0.00 0.00 0.254921E+10 0.200279E+10 6864.19 05-SEP-06:02 4200.80 0.00
October 0.00 0.00 0.102256E+10 0.802012E+09 6841.60 19-OCT-07:02 3673.48 0.00
November 0.00 0.00 0.212798E+09 0.184891E+09 1964.50 03-NOV-15:00 1504.92 0.00
December 0.00 0.00 24128816.47 15750066.86 1090.79 13-DEC-13:10 707.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.172160E+11 0.133172E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.439581E+10 0.328980E+10 7017.88   4253.74 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 30852340.08 30852340.08 1304.22 28-FEB-16:45 1304.22 0.00
March 0.00 0.00 0.210308E+09 0.177151E+09 2369.58 30-MAR-15:53 2156.80 0.00
April 0.00 0.00 0.451074E+09 0.400690E+09 2444.04 17-APR-15:53 2360.11 0.00
May 0.00 0.00 0.115954E+10 0.954051E+09 5592.63 31-MAY-07:03 3587.53 0.00
June 0.00 0.00 0.221624E+10 0.179594E+10 5700.93 26-JUN-06:02 3985.77 0.00
July 0.00 0.00 0.253473E+10 0.201537E+10 5785.03 27-JUL-06:03 3315.91 0.00
August 0.00 0.00 0.307959E+10 0.240706E+10 5807.01 24-AUG-06:02 3436.09 0.00
September 0.00 0.00 0.185684E+10 0.152339E+10 5740.85 05-SEP-06:02 3785.38 0.00
October 0.00 0.00 0.868257E+09 0.727336E+09 5688.80 19-OCT-07:02 3273.82 0.00
November 0.00 0.00 0.265997E+09 0.242858E+09 1872.11 06-NOV-16:25 1872.11 0.00
December 0.00 0.00 41336229.28 31204075.48 965.25 12-DEC-14:35 732.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.127148E+11 0.103059E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.307959E+10 0.240706E+10 5807.01   3985.77 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 252.03 601.05 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 26.83 601.07 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     23.46    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   252.03 601.07  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.325162E+09 0.35 330.85 02-JAN-06:01 0.95
February 0.294195E+09 0.35 330.85 01-FEB-06:05 0.94
March 0.356130E+09 0.38 330.85 01-MAR-06:05 0.95
April 0.309679E+09 0.34 330.85 03-APR-05:10 0.94
May 0.340646E+09 0.36 330.85 01-MAY-05:10 0.94
June 0.340646E+09 0.37 330.85 01-JUN-05:10 0.94
July 0.309679E+09 0.33 330.85 03-JUL-05:10 0.94
August 0.356130E+09 0.38 330.85 01-AUG-05:10 0.93
September 0.309679E+09 0.34 330.85 01-SEP-05:10 0.94
October 0.325162E+09 0.35 330.85 02-OCT-05:10 0.94
November 0.325162E+09 0.36 330.85 01-NOV-05:10 0.95
December 0.309679E+09 0.33 330.85 01-DEC-06:03 0.95
           
Annual Sum or Average 0.390195E+10 0.35      
Minimum of Months 0.294195E+09 0.33 330.85   0.93
Maximum of Months 0.356130E+09 0.38 330.85   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.360920E+09 0.38 355.62 02-JAN-06:01 0.95
February 0.321719E+09 0.36 355.62 01-FEB-06:05 0.95
March 0.382793E+09 0.38 355.62 01-MAR-06:05 0.95
April 0.332863E+09 0.34 355.62 03-APR-05:10 0.94
May 0.366149E+09 0.36 355.62 01-MAY-05:10 0.94
June 0.366149E+09 0.37 355.62 01-JUN-05:10 0.94
July 0.332863E+09 0.33 355.62 03-JUL-05:10 0.94
August 0.382793E+09 0.38 355.62 01-AUG-05:10 0.93
September 0.332863E+09 0.34 355.62 01-SEP-05:10 0.94
October 0.349573E+09 0.35 355.62 02-OCT-05:10 0.94
November 0.349506E+09 0.36 355.62 01-NOV-05:10 0.95
December 0.332863E+09 0.33 355.62 01-DEC-06:03 0.95
           
Annual Sum or Average 0.421106E+10 0.36      
Minimum of Months 0.321719E+09 0.33 355.62   0.93
Maximum of Months 0.382793E+09 0.38 355.62   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.288671E+09 0.40 280.66 02-JAN-06:01 0.95
February 0.259667E+09 0.39 280.66 01-FEB-06:05 0.95
March 0.302101E+09 0.38 280.66 01-MAR-06:05 0.95
April 0.262696E+09 0.34 280.66 03-APR-05:10 0.94
May 0.288966E+09 0.36 280.66 01-MAY-05:10 0.94
June 0.288966E+09 0.37 280.66 01-JUN-05:10 0.94
July 0.264639E+09 0.35 280.66 03-JUL-05:10 0.94
August 0.303256E+09 0.39 280.66 01-AUG-05:10 0.94
September 0.262696E+09 0.34 280.66 01-SEP-05:10 0.94
October 0.275831E+09 0.35 280.66 02-OCT-05:10 0.94
November 0.275831E+09 0.36 280.66 01-NOV-05:10 0.95
December 0.262696E+09 0.33 280.66 01-DEC-06:03 0.95
           
Annual Sum or Average 0.333602E+10 0.36      
Minimum of Months 0.259667E+09 0.33 280.66   0.94
Maximum of Months 0.303256E+09 0.40 280.66   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.364542E+09 0.41 347.11 02-JAN-06:01 0.95
February 0.329337E+09 0.40 347.11 01-FEB-06:05 0.95
March 0.373632E+09 0.38 347.11 01-MAR-06:05 0.95
April 0.324897E+09 0.34 347.11 03-APR-05:10 0.94
May 0.357387E+09 0.36 347.11 01-MAY-05:10 0.94
June 0.357387E+09 0.37 347.11 01-JUN-05:10 0.94
July 0.324897E+09 0.33 347.11 03-JUL-05:10 0.94
August 0.373632E+09 0.38 347.11 01-AUG-05:10 0.94
September 0.324897E+09 0.34 347.11 01-SEP-05:10 0.94
October 0.341142E+09 0.35 347.11 02-OCT-05:10 0.94
November 0.341142E+09 0.36 347.11 01-NOV-05:10 0.95
December 0.324897E+09 0.33 347.11 01-DEC-06:03 0.95
           
Annual Sum or Average 0.413779E+10 0.36      
Minimum of Months 0.324897E+09 0.33 347.11   0.94
Maximum of Months 0.373632E+09 0.41 347.11   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.332716E+09 0.41 324.56 02-JAN-06:01 0.95
February 0.299673E+09 0.39 324.56 01-FEB-06:05 0.95
March 0.349356E+09 0.38 324.56 01-MAR-06:05 0.95
April 0.303788E+09 0.34 324.56 03-APR-05:10 0.94
May 0.334167E+09 0.36 324.56 01-MAY-05:10 0.94
June 0.334609E+09 0.38 324.56 01-JUN-05:10 0.94
July 0.307931E+09 0.36 324.56 03-JUL-05:10 0.94
August 0.353033E+09 0.40 324.56 01-AUG-05:10 0.94
September 0.303788E+09 0.34 324.56 01-SEP-05:10 0.94
October 0.318977E+09 0.35 324.56 02-OCT-05:10 0.94
November 0.318977E+09 0.36 324.56 01-NOV-05:10 0.95
December 0.303788E+09 0.33 324.56 01-DEC-06:03 0.95
           
Annual Sum or Average 0.386080E+10 0.37      
Minimum of Months 0.299673E+09 0.33 324.56   0.94
Maximum of Months 0.353033E+09 0.41 324.56   0.95



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:01 0.00 0.00 43.71 0.00
February 0.00 0.00 0.00 01-FEB-07:01 0.00 0.00 13.42 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 13.42 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 13.42 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 13.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 13.42 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 13.42 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 13.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 13.42 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 13.42 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 13.42 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 13.42 0.00
                 
Annual Sum or Average 0.02 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 13.42 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 43.71 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.89 48.89 252.03 601.05 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 13.42 13.42 26.83 601.07 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 13.42 13.42 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 13.42 13.42 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 13.42 13.42 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 13.42 13.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 13.42 13.42 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 13.42 13.42 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 13.42 13.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 13.42 13.42 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 13.42 13.42 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 13.42 13.42 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         23.46    
Minimum of Months 0.00 0.00   13.42 13.42 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 252.03 601.07  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.660123E+09 0.00 0.00
February 0.00 0.00 0.00 0.446449E+09 0.00 0.00
March 0.00 0.00 0.00 0.498353E+09 0.00 0.00
April 0.00 0.00 0.00 0.599087E+09 0.00 0.00
May 0.00 0.00 0.00 0.920471E+09 0.00 0.00
June 0.00 0.00 0.00 0.128085E+10 0.00 0.00
July 0.00 0.00 0.00 0.130081E+10 0.00 0.00
August 0.00 0.00 0.00 0.151495E+10 0.00 0.00
September 0.00 0.00 0.00 0.106270E+10 0.00 0.00
October 0.00 0.00 0.00 0.739312E+09 0.00 0.00
November 0.00 0.00 0.00 0.475604E+09 0.00 0.00
December 0.00 0.00 0.00 0.371446E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.987017E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.371446E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.151495E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.103391E+10 0.00 0.00
February 0.00 0.00 0.00 0.748916E+09 0.00 0.00
March 0.00 0.00 0.00 0.558297E+09 0.00 0.00
April 0.00 0.00 0.00 0.518344E+09 0.00 0.00
May 0.00 0.00 0.00 0.722593E+09 0.00 0.00
June 0.00 0.00 0.00 0.114250E+10 0.00 0.00
July 0.00 0.00 0.00 0.120797E+10 0.00 0.00
August 0.00 0.00 0.00 0.148023E+10 0.00 0.00
September 0.00 0.00 0.00 0.101928E+10 0.00 0.00
October 0.00 0.00 0.00 0.746447E+09 0.00 0.00
November 0.00 0.00 0.00 0.551665E+09 0.00 0.00
December 0.00 0.00 0.00 0.556107E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.102863E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.518344E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.148023E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.770645E+09 0.00 0.00
February 0.00 0.00 0.00 0.526406E+09 0.00 0.00
March 0.00 0.00 0.00 0.363659E+09 0.00 0.00
April 0.00 0.00 0.00 0.379547E+09 0.00 0.00
May 0.00 0.00 0.00 0.566201E+09 0.00 0.00
June 0.00 0.00 0.00 0.822502E+09 0.00 0.00
July 0.00 0.00 0.00 0.859492E+09 0.00 0.00
August 0.00 0.00 0.00 0.998540E+09 0.00 0.00
September 0.00 0.00 0.00 0.683662E+09 0.00 0.00
October 0.00 0.00 0.00 0.472089E+09 0.00 0.00
November 0.00 0.00 0.00 0.335896E+09 0.00 0.00
December 0.00 0.00 0.00 0.370126E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.714876E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.335896E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.998540E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.123715E+10 0.00 0.00
February 0.00 0.00 0.00 0.831939E+09 0.00 0.00
March 0.00 0.00 0.00 0.468522E+09 0.00 0.00
April 0.00 0.00 0.00 0.448502E+09 0.00 0.00
May 0.00 0.00 0.00 0.706408E+09 0.00 0.00
June 0.00 0.00 0.00 0.108762E+10 0.00 0.00
July 0.00 0.00 0.00 0.114382E+10 0.00 0.00
August 0.00 0.00 0.00 0.135437E+10 0.00 0.00
September 0.00 0.00 0.00 0.888607E+09 0.00 0.00
October 0.00 0.00 0.00 0.568251E+09 0.00 0.00
November 0.00 0.00 0.00 0.419189E+09 0.00 0.00
December 0.00 0.00 0.00 0.566876E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.972125E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.419189E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.135437E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.816826E+09 0.00 0.00
February 0.00 0.00 0.00 0.574836E+09 0.00 0.00
March 0.00 0.00 0.00 0.416831E+09 0.00 0.00
April 0.00 0.00 0.00 0.415077E+09 0.00 0.00
May 0.00 0.00 0.00 0.601537E+09 0.00 0.00
June 0.00 0.00 0.00 0.852326E+09 0.00 0.00
July 0.00 0.00 0.00 0.895447E+09 0.00 0.00
August 0.00 0.00 0.00 0.106042E+10 0.00 0.00
September 0.00 0.00 0.00 0.721484E+09 0.00 0.00
October 0.00 0.00 0.00 0.513112E+09 0.00 0.00
November 0.00 0.00 0.00 0.393046E+09 0.00 0.00
December 0.00 0.00 0.00 0.425287E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.768623E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.393046E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.106042E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.325162E+09 0.00 0.774536E+09 0.00 0.00 0.00 0.00 0.00
February 0.294195E+09 78035408.14 0.309731E+09 0.00 0.00 0.00 0.00 0.00
March 0.356130E+09 0.636450E+09 952388.87 0.00 0.00 0.00 0.00 0.00
April 0.309679E+09 0.128694E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.340646E+09 0.264716E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.340646E+09 0.427876E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.309679E+09 0.456495E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.356130E+09 0.536270E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.309679E+09 0.352727E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.325162E+09 0.192687E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.325162E+09 0.667188E+09 547146.62 0.00 0.00 0.00 0.00 0.00
December 0.309679E+09 0.117449E+09 74923034.22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.390195E+10 0.250938E+11 0.116069E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294195E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356130E+09 0.536270E+10 0.774536E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.360920E+09 5310400.41 0.186257E+10 0.00 0.00 0.00 0.00 0.00
February 0.321719E+09 0.169364E+09 0.111630E+10 0.00 0.00 0.00 0.00 0.00
March 0.382793E+09 0.448599E+09 0.220525E+09 0.00 0.00 0.00 0.00 0.00
April 0.332863E+09 0.648616E+09 99452649.94 0.00 0.00 0.00 0.00 0.00
May 0.366149E+09 0.156037E+10 1831368.24 0.00 0.00 0.00 0.00 0.00
June 0.366149E+09 0.343497E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.332863E+09 0.393776E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.382793E+09 0.501004E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.332863E+09 0.317233E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.349573E+09 0.182209E+10 22129767.57 0.00 0.00 0.00 0.00 0.00
November 0.349506E+09 0.748818E+09 0.102894E+09 0.00 0.00 0.00 0.00 0.00
December 0.332863E+09 0.233621E+09 0.495365E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.421106E+10 0.211919E+11 0.392107E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.321719E+09 5310400.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.382793E+09 0.501004E+10 0.186257E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.288671E+09 0.00 0.115203E+10 0.00 0.00 0.00 0.00 0.00
February 0.259667E+09 26987348.61 0.646692E+09 0.00 0.00 0.00 0.00 0.00
March 0.302101E+09 0.178670E+09 58234007.68 0.00 0.00 0.00 0.00 0.00
April 0.262696E+09 0.485874E+09 8452819.88 0.00 0.00 0.00 0.00 0.00
May 0.288966E+09 0.121709E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.288966E+09 0.232675E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.264639E+09 0.262433E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.303256E+09 0.307972E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262696E+09 0.190094E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.275831E+09 0.884980E+09 531583.08 0.00 0.00 0.00 0.00 0.00
November 0.275831E+09 0.226464E+09 13319900.28 0.00 0.00 0.00 0.00 0.00
December 0.262696E+09 28759666.50 0.252902E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.333602E+10 0.129806E+11 0.213216E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.259667E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.303256E+09 0.307972E+10 0.115203E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.364542E+09 0.00 0.226318E+10 0.00 0.00 0.00 0.00 0.00
February 0.329337E+09 9677970.30 0.135377E+10 0.00 0.00 0.00 0.00 0.00
March 0.373632E+09 0.159193E+09 0.169783E+09 0.00 0.00 0.00 0.00 0.00
April 0.324897E+09 0.469808E+09 36669999.20 0.00 0.00 0.00 0.00 0.00
May 0.357387E+09 0.152915E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.357387E+09 0.320067E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.324897E+09 0.364302E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.373632E+09 0.439581E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.324897E+09 0.254921E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.341142E+09 0.102256E+10 1486081.00 0.00 0.00 0.00 0.00 0.00
November 0.341142E+09 0.212798E+09 65450038.25 0.00 0.00 0.00 0.00 0.00
December 0.324897E+09 24128816.47 0.656218E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.413779E+10 0.172160E+11 0.454656E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.324897E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.373632E+09 0.439581E+10 0.226318E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.332716E+09 0.00 0.111430E+10 0.00 0.00 0.00 0.00 0.00
February 0.299673E+09 30852340.08 0.652901E+09 0.00 0.00 0.00 0.00 0.00
March 0.349356E+09 0.210308E+09 54135459.01 0.00 0.00 0.00 0.00 0.00
April 0.303788E+09 0.451074E+09 12351603.22 0.00 0.00 0.00 0.00 0.00
May 0.334167E+09 0.115954E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.334609E+09 0.221624E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.307931E+09 0.253473E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.353033E+09 0.307959E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.303788E+09 0.185684E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.318977E+09 0.868257E+09 249632.21 0.00 0.00 0.00 0.00 0.00
November 0.318977E+09 0.265997E+09 25290059.07 0.00 0.00 0.00 0.00 0.00
December 0.303788E+09 41336229.28 0.279778E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.386080E+10 0.127148E+11 0.213901E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.299673E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.353033E+09 0.307959E+10 0.111430E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.325162E+09 0.00 0.00 0.334961E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.294195E+09 0.00 0.00 0.134436E+09 17818887.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.356130E+09 0.00 0.00 829991.66 0.141393E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.309679E+09 0.00 0.00 1230000.00 0.288178E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.340646E+09 0.00 0.00 0.00 0.579824E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.340646E+09 0.00 0.00 0.00 0.940208E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.309679E+09 0.00 0.00 0.00 0.991135E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.356130E+09 0.00 0.00 0.00 0.115882E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.309679E+09 0.00 0.00 0.00 0.753025E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.325162E+09 0.00 0.00 510000.00 0.413640E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.325162E+09 0.00 0.00 3472938.25 0.146968E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.309679E+09 0.00 0.00 35805214.80 25961775.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.390195E+10 0.00 0.00 0.511245E+09 0.545697E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294195E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356130E+09 0.00 0.00 0.334961E+09 0.115882E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.360920E+09 0.00 0.00 0.671779E+09 1212269.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.321719E+09 0.00 0.00 0.389500E+09 37696455.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.382793E+09 0.00 0.00 74954448.98 0.100550E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.332863E+09 0.00 0.00 35147611.52 0.150333E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.366149E+09 0.00 0.00 587930.53 0.355855E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.366149E+09 0.00 0.00 0.00 0.776347E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.332863E+09 0.00 0.00 0.00 0.875110E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.382793E+09 0.00 0.00 0.00 0.109744E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.332863E+09 0.00 0.00 0.00 0.686421E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.349573E+09 0.00 0.00 8036212.99 0.388837E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.349506E+09 0.00 0.00 40576154.03 0.161583E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.332863E+09 0.00 0.00 0.171711E+09 51532881.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.421106E+10 0.00 0.00 0.139229E+10 0.468292E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.321719E+09 0.00 0.00 0.00 1212269.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.382793E+09 0.00 0.00 0.671779E+09 0.109744E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.288671E+09 0.00 0.00 0.481974E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.259667E+09 0.00 0.00 0.260480E+09 6259447.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.302101E+09 0.00 0.00 20759697.38 40798195.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262696E+09 0.00 0.00 4253167.11 0.112597E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.288966E+09 0.00 0.00 0.00 0.277235E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.288966E+09 0.00 0.00 0.00 0.533536E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.264639E+09 0.00 0.00 0.00 0.594853E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.303256E+09 0.00 0.00 0.00 0.695283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262696E+09 0.00 0.00 0.00 0.420965E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.275831E+09 0.00 0.00 690642.23 0.195567E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.275831E+09 0.00 0.00 9273304.27 50791274.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.262696E+09 0.00 0.00 0.100948E+09 6481557.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.333602E+10 0.00 0.00 0.878378E+09 0.293437E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.259667E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.303256E+09 0.00 0.00 0.481974E+09 0.695283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.364542E+09 0.00 0.00 0.872610E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.329337E+09 0.00 0.00 0.500297E+09 2304267.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.373632E+09 0.00 0.00 58491334.93 36398875.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.324897E+09 0.00 0.00 14044399.22 0.109560E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.357387E+09 0.00 0.00 0.00 0.349021E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.357387E+09 0.00 0.00 0.00 0.730229E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.324897E+09 0.00 0.00 0.00 0.818927E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.373632E+09 0.00 0.00 0.00 0.980735E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.324897E+09 0.00 0.00 0.00 0.563709E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.341142E+09 0.00 0.00 1009645.88 0.226099E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.341142E+09 0.00 0.00 30356633.99 47690748.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.324897E+09 0.00 0.00 0.236566E+09 5412925.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.413779E+10 0.00 0.00 0.171337E+10 0.387009E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.324897E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.373632E+09 0.00 0.00 0.872610E+09 0.980735E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.332716E+09 0.00 0.00 0.484109E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.299673E+09 0.00 0.00 0.268014E+09 7148705.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.349356E+09 0.00 0.00 19479204.15 47995566.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.303788E+09 0.00 0.00 5751768.30 0.105538E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.334167E+09 0.00 0.00 0.00 0.267370E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.334609E+09 0.00 0.00 0.00 0.517718E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.307931E+09 0.00 0.00 0.00 0.587516E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.353033E+09 0.00 0.00 0.00 0.707386E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.303788E+09 0.00 0.00 0.00 0.417696E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.318977E+09 0.00 0.00 599026.67 0.193535E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.318977E+09 0.00 0.00 14598747.62 59469569.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.303788E+09 0.00 0.00 0.112197E+09 9302448.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.386080E+10 0.00 0.00 0.904749E+09 0.292068E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.299673E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.353033E+09 0.00 0.00 0.484109E+09 0.707386E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115824E+10 0.00 0.00 0.00 0.00 0.547633E+09 0.00 0.00 0.19
February 0.104864E+10 0.00 0.00 286100.69 0.00 0.231913E+09 90752622.10 0.00 0.19
March 0.747877E+09 894567.65 0.00 2317519.36 129690.80 440762.01 0.464957E+09 0.00 0.21
April 0.325745E+09 8694522.52 0.00 4638016.14 360204.96 0.00 0.375518E+09 0.00 0.19
May 0.144032E+09 0.178403E+09 0.00 4082662.61 8630645.75 0.00 0.162649E+09 0.00 0.20
June 55446345.15 0.735306E+09 0.00 2423500.80 53131264.81 0.00 59145269.48 0.00 0.21
July 12536238.44 0.877518E+09 0.00 900289.62 66024467.16 0.00 10011783.80 0.00 0.18
August 9866304.40 0.113056E+10 0.00 397160.79 95500487.22 0.00 6176935.98 0.00 0.21
September 67860065.54 0.409581E+09 0.00 4159393.21 26823845.74 0.00 89861803.32 0.00 0.19
October 0.305789E+09 0.125221E+09 0.00 4874326.27 8393196.24 0.00 0.503686E+09 0.00 0.19
November 0.673441E+09 0.00 0.00 3078376.32 649020.97 325781.78 0.610825E+09 0.00 0.20
December 0.124885E+10 0.00 0.00 366680.40 0.00 35219960.47 0.105729E+09 0.00 0.18
                   
Annual Sum or Average 0.579832E+10 0.346618E+10 0.00 27524026.22 0.259643E+09 0.815532E+09 0.247931E+10 0.00 0.19
Minimum of Months 9866304.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.124885E+10 0.113056E+10 0.00 4874326.27 95500487.22 0.547633E+09 0.610825E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.321747E+09 0.00 0.00 7766.04 0.00 0.684707E+09 4930123.65 0.00 0.19
February 0.264141E+09 0.00 0.00 588893.75 27623.42 0.438037E+09 44898534.66 0.00 0.19
March 0.372742E+09 5294221.47 0.00 1022519.21 576305.58 0.105925E+09 95170616.62 0.00 0.21
April 0.225053E+09 15121812.10 0.00 890946.58 1084276.01 48367980.65 57546354.27 0.00 0.19
May 0.116223E+09 0.127678E+09 0.00 1145671.07 7197577.60 625315.08 55099891.17 0.00 0.20
June 44551981.80 0.522800E+09 0.00 1075771.01 31555650.80 0.00 20846368.71 0.00 0.21
July 19641397.43 0.620164E+09 0.00 526983.98 39043528.07 0.00 5365765.42 0.00 0.18
August 13929295.55 0.804803E+09 0.00 465847.27 53676833.42 0.00 3751470.06 0.00 0.21
September 65669472.04 0.304960E+09 0.00 2380247.90 13973170.73 0.00 34700555.38 0.00 0.19
October 0.248758E+09 0.101543E+09 0.00 3507768.96 3813108.58 13562024.15 0.187577E+09 0.00 0.19
November 0.398027E+09 1368913.11 0.00 2861084.33 1814965.05 47789548.66 0.216644E+09 0.00 0.20
December 0.408078E+09 89696.44 0.00 833537.68 0.00 0.218355E+09 0.106937E+09 0.00 0.18
                   
Annual Sum or Average 0.249856E+10 0.250382E+10 0.00 15307037.77 0.152763E+09 0.155737E+10 0.833468E+09 0.00 0.19
Minimum of Months 13929295.55 0.00 0.00 7766.04 0.00 0.00 3751470.06 0.00 0.18
Maximum of Months 0.408078E+09 0.804803E+09 0.00 3507768.96 53676833.42 0.684707E+09 0.216644E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 56571216.28 0.00 0.00 0.00 0.00 0.549796E+09 0.00 0.00 0.19
February 0.132852E+09 0.00 0.00 55620.05 34171.03 0.317983E+09 10057156.28 0.00 0.20
March 0.267644E+09 2916736.58 0.00 370194.17 906837.83 41338560.79 44015398.31 0.00 0.21
April 0.148896E+09 12100518.88 0.00 1063515.70 658679.37 5113353.30 63777277.22 0.00 0.19
May 56883466.87 0.107810E+09 0.00 1368709.19 5939663.07 0.00 42036083.06 0.00 0.20
June 19125930.80 0.370089E+09 0.00 1088469.50 25972979.85 0.00 16127559.31 0.00 0.21
July 4326600.68 0.442147E+09 0.00 218975.07 32768694.66 0.00 3202542.22 0.00 0.18
August 3637381.90 0.566755E+09 0.00 131440.82 48064208.61 0.00 2592145.76 0.00 0.21
September 31533060.39 0.214707E+09 0.00 1544265.72 13333193.68 0.00 22425940.26 0.00 0.19
October 0.151462E+09 68216768.70 0.00 1928043.54 4547466.53 183471.49 0.132014E+09 0.00 0.19
November 0.299634E+09 846675.66 0.00 763142.38 1874729.39 8488550.60 0.101553E+09 0.00 0.20
December 0.247240E+09 0.00 0.00 47935.92 290205.83 0.174592E+09 10712730.98 0.00 0.18
                   
Annual Sum or Average 0.141981E+10 0.178559E+10 0.00 8580312.06 0.134391E+09 0.109749E+10 0.448514E+09 0.00 0.19
Minimum of Months 3637381.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.299634E+09 0.566755E+09 0.00 1928043.54 48064208.61 0.549796E+09 0.132014E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70038020.74 0.00 0.00 0.00 0.00 0.101539E+10 0.00 0.00 0.20
February 0.185200E+09 0.00 13780.79 14517.06 24945.20 0.640984E+09 2555807.32 47.55 0.20
March 0.460566E+09 2327972.70 0.00 263446.80 1292282.14 0.117132E+09 41524893.07 0.00 0.21
April 0.292873E+09 9885274.49 0.00 796964.49 1006382.23 26049542.40 64888561.23 0.00 0.19
May 0.109150E+09 0.146592E+09 0.00 1414481.01 10300112.24 0.00 71880843.35 0.00 0.20
June 33563639.06 0.591411E+09 0.00 1147423.52 45348163.35 0.00 28968967.70 0.00 0.21
July 8030199.54 0.714023E+09 0.00 362774.41 56518935.96 0.00 5859590.19 0.00 0.18
August 5905903.60 0.922675E+09 0.00 234073.78 83403551.27 0.00 4636534.96 0.00 0.21
September 53617002.82 0.335238E+09 0.00 2068370.76 23232173.81 0.00 41072657.70 0.00 0.19
October 0.298796E+09 98485025.95 0.00 1705467.82 7762238.75 427976.66 0.204658E+09 0.00 0.19
November 0.556999E+09 139033.84 71270.16 611392.13 3394059.56 42963748.60 0.117722E+09 268.79 0.20
December 0.351047E+09 0.00 0.00 34879.77 474936.94 0.392517E+09 15070937.74 0.00 0.18
                   
Annual Sum or Average 0.242579E+10 0.282078E+10 85050.95 8653791.53 0.232758E+09 0.223546E+10 0.598839E+09 316.34 0.20
Minimum of Months 5905903.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.556999E+09 0.922675E+09 71270.16 2068370.76 83403551.27 0.101539E+10 0.204658E+09 268.79 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118747E+09 0.00 0.00 0.00 0.00 0.512036E+09 0.00 0.00 0.19
February 0.155704E+09 0.00 0.00 72172.52 19745.02 0.315752E+09 9813407.34 0.00 0.19
March 0.284610E+09 2363209.29 0.00 368480.91 232466.26 51570159.68 42938107.04 0.00 0.21
April 0.165007E+09 7048837.32 0.00 817094.47 511051.00 11480191.30 59590634.92 0.00 0.19
May 60715255.21 91296555.84 0.00 1038913.59 4968027.48 0.00 45700966.59 0.00 0.20
June 21420073.94 0.351782E+09 0.00 797802.05 25572846.71 0.00 17309565.30 0.00 0.21
July 3917775.82 0.425414E+09 0.00 165310.45 32180412.50 0.00 2388390.45 0.00 0.18
August 3381513.13 0.554590E+09 0.00 97184.13 47107575.64 0.00 1764507.30 0.00 0.21
September 31294821.11 0.201116E+09 0.00 1488041.05 12884121.09 0.00 25989231.00 0.00 0.19
October 0.156747E+09 61962635.20 0.00 1568106.95 4450699.66 190270.74 0.147416E+09 0.00 0.19
November 0.304633E+09 194749.92 0.00 794631.69 1925573.06 22340864.14 0.110714E+09 0.00 0.20
December 0.255333E+09 0.00 0.00 72990.37 154343.95 0.188545E+09 15329538.90 0.00 0.18
                   
Annual Sum or Average 0.156151E+10 0.169577E+10 0.00 7280728.18 0.130007E+09 0.110191E+10 0.478954E+09 0.00 0.20
Minimum of Months 3381513.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.304633E+09 0.554590E+09 0.00 1568106.95 47107575.64 0.512036E+09 0.147416E+09 0.00 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:30:03

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.516288E+11 0.241148E+10 0.00 0.127101E+11 0.222943E+166
February 0.571875E+11 0.231562E+10 0.00 0.102259E+11 0.215365E+166
March 0.950203E+11 0.322714E+10 0.00 0.815269E+10 0.249892E+166
April 0.115072E+12 0.360874E+10 0.00 0.552168E+10 0.274618E+166
May 0.132056E+12 0.394514E+10 0.00 0.249477E+10 0.284498E+166
June 0.134207E+12 0.335126E+10 0.00 -0.189604E+10 0.282532E+166
July 0.128528E+12 0.298413E+10 0.00 -0.461939E+10 0.281834E+166
August 0.117645E+12 0.231017E+10 0.00 -0.622468E+10 0.280334E+166
September 0.863638E+11 0.160516E+10 0.00 -506033400.6 0.248522E+166
October 0.751568E+11 0.200721E+10 0.00 0.574983E+10 0.242496E+166
November 0.489835E+11 0.172871E+10 0.00 0.932804E+10 0.218960E+166
December 0.418497E+11 0.170507E+10 0.00 0.112700E+11 0.208589E+166
           
Annual Sum or Average 0.108370E+13 0.311998E+11 0.00 0.522068E+11 0.301058E+167
Minimum of Months 0.418497E+11 0.160516E+10 0.00 -0.622468E+10 0.208589E+166
Maximum of Months 0.134207E+12 0.394514E+10 0.00 0.127101E+11 0.284498E+166