Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2023-10-16 08:30:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 265.67 519.75 519.75
Net Site Energy 265.67 519.75 519.75
Total Source Energy 629.88 1232.27 1232.27
Net Source Energy 629.88 1232.27 1232.27


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 25.04 101.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 164.14 101.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 25.04 101.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 6.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 23.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 25.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 25.04 101.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 6.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 23.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 25.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 155.92 198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 321.11 198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 155.92 198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 321.11 198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 164.136 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 164.136 100.00
     
Total On-Site and Utility Electric Sources 164.136 100.00
Total Electricity End Uses 164.136 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 177.33
Time Setpoint Not Met During Occupied Cooling 4.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 2784.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
RunPeriod RUNPERIOD 1
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [m] 359.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.0938 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.0938 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.0938 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.0938 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.0938 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.0938 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.0938 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.0938 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.0938 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.0938 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.0938 9.29 6.7800  
Conditioned Total 511.16             6.0938 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.0938 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 05-DEC-08:30 05-JAN-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 8277.06 44645.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2009.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1651.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2747.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 18010.11 44645.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 8277.06 44645.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2009.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1651.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2747.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 79.30 110.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 82.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 73.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 80.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 519.82 110.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 155.14 215.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 37.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 162.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 143.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 156.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1016.94 215.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 155.14 215.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 37.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 162.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 143.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 156.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1016.94 215.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.271547
PERIMETER_ZN_1 DIRECT AIR 0.355717
PERIMETER_ZN_2 DIRECT AIR 0.259216
PERIMETER_ZN_3 DIRECT AIR 0.279370
PERIMETER_ZN_4 DIRECT AIR 0.308293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.271547 0.271547 0.271547 0.271547 0.271547 0.271547 1.00 1.00 0.271547
PSZ-AC:2 0.355717 0.355717 0.355717 0.355717 0.355717 0.355717 1.00 1.00 0.355717
PSZ-AC:3 0.259216 0.259216 0.259216 0.259216 0.259216 0.259216 1.00 1.00 0.259216
PSZ-AC:4 0.279370 0.279370 0.279370 0.279370 0.279370 0.279370 1.00 1.00 0.279370
PSZ-AC:5 0.308293 0.308293 0.308293 0.308293 0.308293 0.308293 1.00 1.00 0.308293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.271547 0.064622
PSZ-AC:2_OA_CONTROLLER 0.355717 0.048988
PSZ-AC:3_OA_CONTROLLER 0.259216 0.029060
PSZ-AC:4_OA_CONTROLLER 0.279370 0.048988
PSZ-AC:5_OA_CONTROLLER 0.308293 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.271547 5218.75 0.792673
PSZ-AC:2 HP COOLING COIL 0.355717 6301.80 0.800536
PSZ-AC:3 HP COOLING COIL 0.259216 4290.95 0.800655
PSZ-AC:4 HP COOLING COIL 0.279370 5244.83 0.800176
PSZ-AC:5 HP COOLING COIL 0.308293 5103.35 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.271547 0.271547 0.271547 0.271547 5218.75 5218.75 40.00 5730.78 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.355717 0.355717 0.355717 0.355717 6301.80 6301.80 40.00 9238.35 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.259216 0.259216 0.259216 0.259216 4290.95 4290.95 40.00 5766.69 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.279370 0.279370 0.279370 0.279370 5244.83 5244.83 40.00 9175.86 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.308293 0.308293 0.308293 0.308293 5103.35 5103.35 40.00 5804.84 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.271547
PSZ-AC:2 FAN 0.355717
PSZ-AC:3 FAN 0.259216
PSZ-AC:4 FAN 0.279370
PSZ-AC:5 FAN 0.308293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.271547 5218.75
PSZ-AC:2 HEATING COIL 0.355717 6301.80
PSZ-AC:3 HEATING COIL 0.259216 4290.95
PSZ-AC:4 HEATING COIL 0.279370 5244.83
PSZ-AC:5 HEATING COIL 0.308293 5103.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 5730.78
PSZ-AC:2_SUPPHEATCOIL 9238.35
PSZ-AC:3_SUPPHEATCOIL 5766.69
PSZ-AC:4_SUPPHEATCOIL 9175.86
PSZ-AC:5_SUPPHEATCOIL 5804.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 5.40 -2.00 -14.60 -16.90 -11.50 -6.20 4.00 13.40 18.00 19.70 17.90 12.30


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 359.00 97086 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 3.29 36.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.094 6.780 0.000 0.000 0.000 0.000 12.874 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 911.976 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 911.976
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 691.337 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 691.337
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 410.110 6.094 113.226 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 410.110


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 1.924E-002 1.696E-004 2.278E-004 0.200 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 1.283E-002 1.906E-004 2.278E-004 0.225 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 1.924E-002 1.696E-004 2.178E-004 0.200 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 1.283E-002 1.906E-004 2.278E-004 0.225 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.1292E-003
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.3441E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.3919E-003
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.5882E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2872E-003
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.4467E-003
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 6.2296E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 6.9602E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1111E-002
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.1102E-002
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1198E-002
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.1981E-002
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0304E-002
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.2526E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.3161E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 2.8838E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.1663E-002
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.3472E-002
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.2238E-002
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.5195E-002
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 9.6023E-003
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.4050E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.4121E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.6643E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.1320E-003
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.3803E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.3977E-003
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.6367E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2883E-003
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.4550E-003
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 6.1794E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 6.8477E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.0446E-003
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.0699E-003
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.3191E-003
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.3420E-003
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.2198E-003
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.2369E-003
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 5.8346E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 5.9106E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.0384E-003
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.0432E-003
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.3136E-003
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.3178E-003
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.2154E-003
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.2186E-003
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 5.8123E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 5.8269E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.2160E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.9598E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.5478E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 4.3244E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.0278E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.4323E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 9.8617E-004
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.1086E-003
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.5243E-003
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.6940E-003
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.4426E-003
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.5694E-003
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.2607E-003
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.3225E-003
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.7774E-004
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0449E-003
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.9360E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 4.6152E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.8473E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.8975E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.3141E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.4668E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.7766E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.0609E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.7420E-002
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.9838E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.8939E-002
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.8866E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2852E-002
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 6.4975E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.6996E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.2873E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.9358E-003
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.4776E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.9792E-003
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.5780E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.3896E-003
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.6343E-003
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.8259E-004
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0561E-003
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 7.4879E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 8.8810E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.0232E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.1259E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.9450E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.7227E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.1666E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.8052E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.6042E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.9346E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.6594E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.0217E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.6500E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1504E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.0257E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.5608E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 6.5943E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 4.8019E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.0963E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.6117E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.5020E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.2499E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.8389E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.9993E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 7.6672E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 9.4232E-004
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.1486E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.4959E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.9987E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.7916E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.2675E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.0307E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.8491E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 7.0617E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.4925E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.6604E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.4758E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.5843E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.8471E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.9317E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.7892E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.8313E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.4440E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.4776E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.4401E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.4624E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.8218E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.8377E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.6157E-003
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.9692E-003
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.5598E-003
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.9179E-003
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.2509E-003
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.4601E-003
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.8418E-004
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0572E-003
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.2361E-002
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.1835E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.2517E-002
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.7403E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1064E-002
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.5674E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.6773E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2450E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 5.9887E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.5354E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.7238E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.6750E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.8964E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.0445E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.7733E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.0255E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.3445E-003
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.5237E-003
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.2068E-003
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.3385E-003
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1322E-003
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.1872E-003
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 9.7915E-004
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.0460E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 2955.44409 3546.53290 0.22629 0.27155 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 28.86000 1.27237E-002 149.65740 8.05449 6.46220E-002 0.00000
2 CORE_ZN Heating 1436.53082 1723.83698 6.46291E-002 7.75549E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 149.65740 8.05449 6.46220E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3871.27743 4645.53292 0.29643 0.35572 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10000 1.27259E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 5227.65923 6273.19107 0.23519 0.28222 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2821.27199 3385.52639 0.21601 0.25922 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 25.38800 1.27176E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 3343.29669 4011.95602 0.15041 0.18049 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 2664.78513 3197.74215 0.20404 0.24485 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 29.19067 1.27243E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 5174.81390 6209.77668 0.23281 0.27937 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3355.41318 4026.49581 0.25691 0.30829 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 26.19400 1.27190E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 3375.55822 4050.66986 0.15186 0.18223 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 3864.15 0.27155 0.27155 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 5730.78 7.75549E-002 7.75549E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 PSZ-AC:2 Cooling Sensible 4926.52 0.35572 0.35572 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 9238.35 0.28222 0.28222 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3383.67 0.25922 0.25922 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 5766.69 0.18049 0.18049 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 3449.43 0.24485 0.24485 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 9175.86 0.27937 0.27937 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4041.89 0.30829 0.30829 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 5804.84 0.18223 0.18223 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.27155
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.35572
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.25922
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.27937
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30829
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.27155
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.27155
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.27155
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.27155
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.27155
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.27155
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.35572
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.35572
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.35572
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.35572
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.35572
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.35572
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.25922
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.25922
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.25922
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.25922
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.25922
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.25922
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.27937
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.27937
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.27937
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.27937
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.27937
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.27937
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30829
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30829
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30829
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.30829
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30829
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.30829
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.27155
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.35572
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.25922
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.27937
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.30829
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.27155
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46220E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.27155
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5218.74669
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.79267
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.27155
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.27155
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.27155
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.27155
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5218.74669
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5218.74669
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5730.78017
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.27155
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.27155
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5218.74669
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 5730.78017
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.35572
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.35572
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6301.80143
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80054
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.35572
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.35572
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.35572
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.35572
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6301.80143
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6301.80143
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 9238.35109
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.35572
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.35572
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6301.80143
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 9238.35109
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.25922
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.25922
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4290.94686
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.25922
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.25922
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.25922
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.25922
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4290.94686
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4290.94686
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5766.69279
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.25922
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.25922
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4290.94686
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 5766.69279
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.27937
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.27937
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5244.83347
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80018
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.27937
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.27937
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.27937
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.27937
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5244.83347
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5244.83347
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 9175.86038
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.27937
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.27937
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5244.83347
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 9175.86038
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30829
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30829
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5103.35129
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30829
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30829
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30829
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30829
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5103.35129
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5103.35129
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5804.84274
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.30829
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30829
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5103.35129
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 5804.84274
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5005.5 3.67 12.53 13.11 12.40 12.31
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6022.8 3.61 12.33 12.89 12.19 12.01
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4087.8 3.56 12.15 12.69 12.00 11.75
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 5025.5 3.66 12.48 13.05 12.34 12.22
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4861.7 3.56 12.15 12.69 12.00 11.75


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5435.1 3012.0 7.39 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6584.5 3658.6 7.38 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4496.6 2504.3 7.33 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 5467.2 3032.1 7.38 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5347.9 2978.5 7.32 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 0.1493805786 0.1531860158 Pass Pass 0.6268010579 0.9568733995 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 0.4841654225 0.5820275145 Pass Pass 0.4623076215 0.5548951948 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.8056787389 0.7739927826 Pass Pass 0.6223547897 0.6281481032 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.8618031962 0.8019195600 Pass Pass 0.6293738016 0.6402524135 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.8320152389 0.7980170515 Pass Pass 0.6283972117 0.6371833488 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2990766226 0.2948094150 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 824.22 34.68 0.00 161.15 38.04 1058.10



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -32.70 0.00 -32.70 Wetbulb [C] 2.40 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 30.10 12.40 21.10 Wetbulb [C] 4.70 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 12.00 13      
Apr 16.00 23      
May 0.00 0      
Jun 190.00 53      
Jul 136.00 41      
Aug 87.00 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.903 1.045 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.215 0.223 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.903 1.045 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.242 0.252 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.903 1.045 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.215 0.223 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.903 1.045 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.242 0.252 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.096 0.098 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.096 0.098 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.096 0.098 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.096 0.098 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.096 0.098 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.096 0.098 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.096 0.098 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.096 0.098 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.096 0.098 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.096 0.098 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.2922_SHGC_SOUTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.2922_SHGC_SOUTH_0.4   3.91 0.00 0.00 3.91 3.91 1.659 0.401 0.401             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.2922_SHGC_EAST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.2922_SHGC_EAST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.2922_SHGC_EAST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.2922_SHGC_EAST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.2922_SHGC_NORTH_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.2922_SHGC_WEST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.2922_SHGC_WEST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.2922_SHGC_WEST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.2922_SHGC_WEST_0.4   2.79 0.00 0.00 2.79 2.79 1.659 0.401 0.401             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 1.659 0.401 0.401                      
North Total or Average             16.72 1.659 0.401 0.401                      
Non-North Total or Average             42.93 1.659 0.401 0.401                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 1.00 1.00 1.00 0.03 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.22 0.84 0.69 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.10 0.00 1.00 0.00 0.00 1.00 0.77 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.0938 149.66 911.98 LightsWired LTG_SCH_OFFICE 50.53 168.00 49.65 0.0000 Y 8.50
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 41.52 0.0000 Y 5.39
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 42.73 0.0000 Y 3.29
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.0938 113.45 691.34 LightsWired LTG_SCH_OFFICE 50.53 168.00 44.06 0.0000 Y 5.72
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.0938 67.30 410.11 LightsWired LTG_SCH_OFFICE 50.53 168.00 42.79 0.0000 Y 3.29
Interior Lighting Total       6.0938 511.16 3114.87               26.19


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 691.34 165.85
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 691.34 20.88
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 410.11 98.39
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 410.11 12.39


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   42.55 42.55 0.53
EXTERIOR_LIGHTS_B 202.25 AstronomicalClock -   83.52 63.04 2.39
EXTERIOR_LIGHTS_C 780.12 AstronomicalClock -   83.52 47.99 7.03
Exterior Lighting Total 1049.10           9.95



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5218.75 4136.76 1081.99 0.79 4.53    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6301.80 5044.82 1256.99 0.80 4.53    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4290.95 3435.57 855.38 0.80 4.53    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5244.83 4196.79 1048.05 0.80 4.53    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5103.35 4086.03 1017.33 0.80 4.53    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5005.5 3.67 12.53 13.11 12.40 12.31
PSZ-AC:2 HP COOLING COIL   6022.8 3.61 12.33 12.89 12.19 12.01
PSZ-AC:3 HP COOLING COIL   4087.8 3.56 12.15 12.69 12.00 11.75
PSZ-AC:4 HP COOLING COIL   5025.5 3.66 12.48 13.05 12.34 12.22
PSZ-AC:5 HP COOLING COIL   4861.7 3.56 12.15 12.69 12.00 11.75
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5435.1 3012.0 7.39 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6584.5 3658.6 7.38 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4496.6 2504.3 7.33 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 5467.2 3032.1 7.38 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5347.9 2978.5 7.32 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5218.75 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   5730.78 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6301.80 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   9238.35 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4290.95 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   5766.69 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   5244.83 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   9175.86 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   5103.35 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   5804.84 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.27 304.16 1120.11 1.00 1.97 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.36 398.44 1120.11 1.00 1.78 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.26 290.35 1120.11 1.00 2.01 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.28 312.92 1120.11 1.00 1.95 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.31 345.32 1120.11 1.00 1.88 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 2955.44 3546.53 23.70 0.226 0.272 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 23.89 23.89 0.00911 28.86 0.01272 0.065 0.00
PERIMETER_ZN_1 3871.28 4645.53 40.95 0.296 0.356 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 23.89 23.89 0.00891 30.10 0.01273 0.049 0.00
PERIMETER_ZN_2 2821.27 3385.53 50.30 0.216 0.259 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 23.89 23.89 0.00884 25.39 0.01272 0.029 0.00
PERIMETER_ZN_3 2664.79 3197.74 28.19 0.204 0.245 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 23.89 23.89 0.00909 29.19 0.01272 0.049 0.00
PERIMETER_ZN_4 3355.41 4026.50 59.83 0.257 0.308 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 23.89 23.89 0.00879 26.19 0.01272 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1436.53 1723.84 11.52 0.065 0.078 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 -32.70 0.00018 0.065 0.00
PERIMETER_ZN_1 5227.66 6273.19 55.29 0.235 0.282 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00790 -32.70 0.00018 0.049 0.00
PERIMETER_ZN_2 3343.30 4011.96 59.61 0.150 0.180 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00790 -32.70 0.00018 0.029 0.00
PERIMETER_ZN_3 5174.81 6209.78 54.74 0.233 0.279 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00790 -32.70 0.00018 0.049 0.00
PERIMETER_ZN_4 3375.56 4050.67 60.19 0.152 0.182 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00790 -32.70 0.00018 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.27 0.27 0.08 0.08 0.2715 0.2715 0.2715 1.0000 1.0000
PSZ-AC:2 0.36 0.36 0.28 0.28 0.3557 0.3557 0.3557 1.0000 1.0000
PSZ-AC:3 0.26 0.26 0.18 0.18 0.2592 0.2592 0.2592 1.0000 1.0000
PSZ-AC:4 0.24 0.24 0.28 0.28 0.2794 0.2794 0.2794 1.0000 1.0000
PSZ-AC:5 0.31 0.31 0.18 0.18 0.3083 0.3083 0.3083 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5218.747 4136.761 0.271547 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 5234.38 4210.37 0.271547 26.02 17.84 0.00996691 12.80 11.72 0.00850000 28.86 0.01272368 20.77 23.7977 23.89 0.00911217 47.2731 2933.90 0.00 5217.85 4043.92
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5218.747 5218.747 0.271547 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5218.75 5218.75 0.271547 8.30 7.22 0.00613982 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 23.7977 21.11 0.00800000 49.2257 1436.53 0.00 5225.60 5225.60
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 5730.780 5730.780 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5730.78 5730.78 0.271547 8.30 7.22 0.00613982 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 23.7977 21.11 0.00800000 49.2257 1436.53 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6301.801 5044.816 0.355717 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 6197.24 5349.29 0.355717 25.69 17.31 0.00943553 12.80 11.72 0.00850000 30.10 0.01272586 21.13 13.7715 23.89 0.00891003 46.2406 3871.28 0.00 6300.72 4930.48
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6301.801 6301.801 0.355717 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6301.80 6301.80 0.355717 13.70 10.41 0.00683753 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 13.7715 21.11 0.00790027 48.6209 5227.66 0.00 6310.08 6310.08
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 9238.351 9238.351 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9238.35 9238.35 0.355717 13.70 10.41 0.00683753 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 13.7715 21.11 0.00790027 48.6209 5227.66 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4290.947 3435.569 0.259216 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 4293.07 3771.99 0.259216 25.01 16.95 0.00927772 12.80 11.72 0.00850000 25.39 0.01271761 19.73 11.2108 23.89 0.00884405 45.9007 2814.02 0.00 4290.21 3356.60
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4290.947 4290.947 0.259216 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4290.95 4290.95 0.259216 15.08 11.19 0.00703144 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 11.2108 21.11 0.00789610 48.5957 3343.30 0.00 4296.59 4296.59
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 5766.693 5766.693 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5766.69 5766.69 0.259216 15.08 11.19 0.00703144 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 11.2108 21.11 0.00789610 48.5957 3343.30 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5244.833 4196.788 0.279370 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 5232.11 4286.76 0.279370 25.90 17.68 0.00981942 12.80 11.72 0.00850000 29.19 0.01272426 20.87 17.5350 23.89 0.00909578 47.1895 2654.00 0.00 5243.93 4101.78
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5244.833 5244.833 0.279370 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5244.83 5244.83 0.279370 11.67 9.22 0.00654628 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 17.5350 21.11 0.00789926 48.6148 5174.81 0.00 5251.73 5251.73
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 9175.860 9175.860 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 9175.86 9175.86 0.279370 11.67 9.22 0.00654628 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 17.5350 21.11 0.00789926 48.6148 5174.81 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5103.351 4086.025 0.308293 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 5079.06 4549.03 0.308293 25.06 16.87 0.00915824 12.80 11.72 0.00850000 26.19 0.01271901 19.97 9.4261 23.89 0.00878692 45.6084 3354.22 0.00 5102.48 3992.10
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5103.351 5103.351 0.308293 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5103.35 5103.35 0.308293 16.04 11.72 0.00716997 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 9.4261 21.11 0.00789708 48.6016 3375.56 0.00 5110.06 5110.06
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 5804.843 5804.843 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5804.84 5804.84 0.308293 16.04 11.72 0.00716997 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 9.4261 21.11 0.00789708 48.6016 3375.56 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5218.747 4136.761 0.271547 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.3680 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.271547 0.31334529   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 Sensible 5234.38 4210.37 1.0030 0.31334529 0.271547 26.02 17.84 0.00996691 51555.5 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 304.162 4930.22 28.86 0.01272368 20.77 0.06462205 23.7977 23.89 0.00910598 23.89 0.00911217 47.2731 2933.90 0.00 5217.85 4043.92 0.30097052 26.67 19.44 0.01118466 55322.4 13.53 13.52 0.00965537 37985.6
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5218.747 5218.747 0.271547 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.271547 0.31334529   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5218.75 5218.75 1.0000 0.31334529 0.271547 8.30 7.22 0.00613982 23794.8 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5218.75 -32.70 0.00018338 -32.70 0.06462205 23.7977 21.11 0.00800000 21.11 0.00800000 49.2257 1436.53 0.00 5225.60 5225.60 0.30780839 21.11 15.56 0.00875166 43444.1 37.74 21.05 0.00875166 60420.9
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5730.780 5730.780 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.271547 0.31334529   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5730.78 5730.78 1.0000 0.31334529 0.271547 8.30 7.22 0.00613982 23794.8 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5730.78 -32.70 0.00018338 -32.70 0.06462205 23.7977 21.11 0.00800000 21.11 0.00800000 49.2257 1436.53 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6301.801 5044.816 0.355717 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.3802 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.355717 0.41047053   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 6197.24 5349.29 0.9834 0.41047053 0.355717 25.69 17.31 0.00943553 49866.3 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 398.441 5798.80 30.10 0.01272586 21.13 0.04898769 13.7715 23.89 0.00891003 23.89 0.00891003 46.2406 3871.28 0.00 6300.72 4930.48 0.39426005 26.67 19.44 0.01118466 55322.4 14.44 14.03 0.00982201 39341.3
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6301.801 6301.801 0.355717 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.355717 0.41047053   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6301.80 6301.80 1.0000 0.41047053 0.355717 13.70 10.41 0.00683753 31039.9 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6301.80 -32.70 0.00018338 -32.70 0.04898769 13.7715 21.11 0.00790027 21.11 0.00790027 48.6209 5227.66 0.00 6310.08 6310.08 0.40321739 21.11 15.56 0.00875166 43444.1 36.44 20.66 0.00875166 59093.4
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 9238.351 9238.351 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.355717 0.41047053   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9238.35 9238.35 1.0000 0.41047053 0.355717 13.70 10.41 0.00683753 31039.9 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9238.35 -32.70 0.00018338 -32.70 0.04898769 13.7715 21.11 0.00790027 21.11 0.00790027 48.6209 5227.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4290.947 3435.569 0.259216 -999.0 -999.000 -999.0000 1.02070 1.00000 1022.0868 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.259216 0.29911590   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 Sensible 4293.07 3771.99 1.0005 0.29911590 0.259216 25.01 16.95 0.00927772 48762.6 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 290.350 4002.72 25.39 0.01271761 19.73 0.02906013 11.2108 23.89 0.00884339 23.89 0.00884405 45.9007 2814.02 0.00 4290.21 3356.60 0.28730308 26.67 19.44 0.01118466 55322.4 15.25 14.42 0.00991057 40389.7
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4290.947 4290.947 0.259216 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.259216 0.29911590   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4290.95 4290.95 1.0000 0.29911590 0.259216 15.08 11.19 0.00703144 32932.4 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4290.95 -32.70 0.00018338 -32.70 0.02906013 11.2108 21.11 0.00789610 21.11 0.00789610 48.5957 3343.30 0.00 4296.59 4296.59 0.29383043 21.11 15.56 0.00875166 43444.1 35.43 20.36 0.00875166 58066.8
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5766.693 5766.693 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.259216 0.29911590   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5766.69 5766.69 1.0000 0.29911590 0.259216 15.08 11.19 0.00703144 32932.4 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5766.69 -32.70 0.00018338 -32.70 0.02906013 11.2108 21.11 0.00789610 21.11 0.00789610 48.5957 3343.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5244.833 4196.788 0.279370 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.0938 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.279370 0.32237228   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 Sensible 5232.11 4286.76 0.9976 0.32237228 0.279370 25.90 17.68 0.00981942 51054.6 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 312.925 4919.18 29.19 0.01272426 20.87 0.04898769 17.5350 23.89 0.00909286 23.89 0.00909578 47.1895 2654.00 0.00 5243.93 4101.78 0.30964101 26.67 19.44 0.01118466 55322.4 13.72 13.67 0.00973842 38386.9
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5244.833 5244.833 0.279370 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.279370 0.32237228   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5244.83 5244.83 1.0000 0.32237228 0.279370 11.67 9.22 0.00654628 28244.5 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5244.83 -32.70 0.00018338 -32.70 0.04898769 17.5350 21.11 0.00789926 21.11 0.00789926 48.6148 5174.81 0.00 5251.73 5251.73 0.31667586 21.11 15.56 0.00875166 43444.1 37.35 20.94 0.00875166 60028.0
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 9175.860 9175.860 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.279370 0.32237228   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 9175.86 9175.86 1.0000 0.32237228 0.279370 11.67 9.22 0.00654628 28244.5 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9175.86 -32.70 0.00018338 -32.70 0.04898769 17.5350 21.11 0.00789926 21.11 0.00789926 48.6148 5174.81 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5103.351 4086.025 0.308293 -999.0 -999.000 -999.0000 1.03345 1.00000 1021.8647 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.308293 0.35574748   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 5079.06 4549.03 0.9952 0.35574748 0.308293 25.06 16.87 0.00915824 48508.7 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 345.322 4733.74 26.19 0.01271901 19.97 0.02906013 9.4261 23.89 0.00878766 23.89 0.00878692 45.6084 3354.22 0.00 5102.48 3992.10 0.34169814 26.67 19.44 0.01118466 55322.4 15.25 14.42 0.00991057 40389.7
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5103.351 5103.351 0.308293 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.308293 0.35574748   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5103.35 5103.35 1.0000 0.35574748 0.308293 16.04 11.72 0.00716997 34260.5 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5103.35 -32.70 0.00018338 -32.70 0.02906013 9.4261 21.11 0.00789708 21.11 0.00789708 48.6016 3375.56 0.00 5110.06 5110.06 0.34946131 21.11 15.56 0.00875166 43444.1 35.43 20.36 0.00875166 58066.8
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5804.843 5804.843 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.308293 0.35574748   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5804.84 5804.84 1.0000 0.35574748 0.308293 16.04 11.72 0.00716997 34260.5 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5804.84 -32.70 0.00018338 -32.70 0.02906013 9.4261 21.11 0.00789708 21.11 0.00789708 48.6016 3375.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2974.17 3174.17 2116.17
PERIMETER_ZN_1 3052.33 3381.17 2407.33
PERIMETER_ZN_2 2623.17 2681.17 2028.00
PERIMETER_ZN_3 3060.33 3515.33 2596.83
PERIMETER_ZN_4 3089.00 3346.50 2444.33
ATTIC 0.00 0.00 0.00
Facility 3612.50 3691.17 2784.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 34.17 4.67 34.17 4.67
PERIMETER_ZN_1 307.83 0.17 158.00 0.17
PERIMETER_ZN_2 286.83 0.17 24.50 0.17
PERIMETER_ZN_3 304.17 0.00 42.33 0.00
PERIMETER_ZN_4 280.83 0.00 22.33 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 776.83 4.83 177.33 4.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.396 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.396 0.394 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.375 0.024 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.400 0.020 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.400 0.023 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.046
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.021
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.035
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.021
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.156


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 765948.95 0.00 765948.95 0.00 765948.95 1606483.19 5467.57 2016.00 1276.43 16.43
PERIMETER_ZN_1 684113.19 0.00 684113.19 635899.79 1320012.98 1217818.28 4934.10 2018.82 1807.08 697.32
PERIMETER_ZN_2 429081.16 0.00 429081.16 57288.75 486369.91 702184.69 4760.56 1514.54 2484.90 1741.56
PERIMETER_ZN_3 734946.29 0.00 734946.29 85933.12 820879.41 1217818.28 4662.27 2019.18 2078.55 991.37
PERIMETER_ZN_4 424473.57 0.00 424473.57 57288.75 481762.32 722425.48 4809.48 2018.98 1931.54 975.65
Total Facility 3038563.15 0.00 3038563.15 836410.40 3874973.55 5466729.92 5475.74 2027.46 2892.79 2164.90


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0565 1008.00 2016.00 1260.00
PERIMETER_ZN_1 0.0377 0.0000 0.0377 0.0376 0.0753 0.0428 988.03 2016.00 1279.97
PERIMETER_ZN_2 0.0212 0.0000 0.0212 0.0014 0.0225 0.0249 960.62 1512.00 1055.37
PERIMETER_ZN_3 0.0380 0.0000 0.0380 0.0019 0.0399 0.0428 962.31 2016.17 1305.53
PERIMETER_ZN_4 0.0225 0.0000 0.0225 0.0013 0.0238 0.0254 964.61 2016.00 1303.39
Total Facility 0.1688 0.0000 0.1688 0.0421 0.2109 0.1925 1008.00 2016.17 1831.40


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1019893.63 0.00 1019893.63 1606483.19 5467.57 0.00 3292.43 16.43
PSZ-AC:2 910925.84 0.00 910925.84 1217818.28 4896.97 3.06 3859.98 695.88
PSZ-AC:3 571339.83 0.00 571339.83 702184.69 4696.85 3.46 4059.69 1737.12
PSZ-AC:4 978612.27 0.00 978612.27 1217818.28 4608.84 5.21 4145.95 990.28
PSZ-AC:5 565204.63 0.00 565204.63 722425.48 4751.32 3.23 4005.45 971.41


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0658 0.0000 0.0658 0.0565 1008.00 0.00 3276.00
PSZ-AC:2 0.0502 0.0000 0.0502 0.0428 988.03 0.00 3295.97
PSZ-AC:3 0.0282 0.0000 0.0282 0.0249 960.62 0.00 2567.38
PSZ-AC:4 0.0506 0.0000 0.0506 0.0428 961.89 0.00 3322.11
PSZ-AC:5 0.0300 0.0000 0.0300 0.0254 964.44 0.00 3319.56


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3292.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3991.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 4307.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 4312.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 4292.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0860 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0652 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0387 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0652 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0387 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 524
Defaulted Fields 360
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
Electricity:Building 74.48 895.38 29-APR-09:30 5350.97 02-JAN-08:10
Electricity:Zone:CORE_ZN 22.64 284.81 01-JAN-00:10 1566.66 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.48 895.38 29-APR-09:30 5350.97 02-JAN-08:10
InteriorLights:Electricity 26.19 327.73 29-APR-09:30 2025.66 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.19 327.73 29-APR-09:30 2025.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity 26.19 327.73 29-APR-09:30 2025.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.50 118.61 01-JAN-00:10 593.08 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.19 327.73 29-APR-09:30 2025.66 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_1 16.11 191.62 01-JAN-09:00 1187.63 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.39 65.63 01-JAN-09:00 449.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.39 65.63 01-JAN-09:00 449.59 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_2 9.65 113.67 01-JAN-08:40 704.52 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 38.93 01-JAN-08:40 266.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 38.93 01-JAN-08:40 266.70 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_3 16.44 191.62 29-APR-08:30 1187.63 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.72 65.63 29-APR-08:30 449.59 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.72 65.63 29-APR-08:30 449.59 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_4 9.65 113.67 01-JAN-14:10 704.52 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.29 38.93 01-JAN-14:10 266.70 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.29 38.93 01-JAN-14:10 266.70 02-JAN-08:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
ElectricityPurchased:Plant 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
Cogeneration:ElectricityPurchased 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
General:Cogeneration:ElectricityPurchased 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
ElectricityNet:Plant 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
Cogeneration:ElectricityNet 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
General:Cogeneration:ElectricityNet 164.14 1467.38 29-APR-09:30 18010.11 05-DEC-08:30
ExteriorLights:Electricity 9.95 0.00 01-JAN-08:20 1049.10 01-JAN-06:10
General:ExteriorLights:Electricity 9.95 0.00 01-JAN-08:20 1049.10 01-JAN-06:10
Electricity:HVAC 54.41 0.00 04-FEB-13:10 9955.64 21-MAR-06:30
Fans:Electricity 23.24 0.00 01-JAN-12:40 1651.20 01-JAN-00:20
General:Fans:Electricity 23.24 0.00 01-JAN-12:40 1651.20 01-JAN-00:20
Cooling:Electricity 6.13 0.00 01-JAN-00:10 5114.42 29-JUN-16:00
General:Cooling:Electricity 6.13 0.00 01-JAN-00:10 5114.42 29-JUN-16:00
Heating:Electricity 25.04 0.00 04-FEB-13:10 8304.44 21-MAR-06:30
General:Heating:Electricity 25.04 0.00 04-FEB-13:10 8304.44 21-MAR-06:30
Electricity:Plant 25.29 572.00 02-JAN-06:10 2848.31 24-FEB-12:50
WaterSystems:Electricity 25.29 572.00 02-JAN-06:10 2848.31 24-FEB-12:50
Water Heater:WaterSystems:Electricity 25.29 572.00 02-JAN-06:10 2848.31 24-FEB-12:50
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-08:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 101.54 0.00 01-JAN-12:40 44645.66 05-JAN-07:10
NaturalGas:HVAC 101.54 0.00 01-JAN-12:40 44645.66 05-JAN-07:10
Heating:NaturalGas 101.54 0.00 01-JAN-12:40 44645.66 05-JAN-07:10
General:Heating:NaturalGas 101.54 0.00 01-JAN-12:40 44645.66 05-JAN-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 02-FEB-12:20
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 02-FEB-12:20
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 27-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 27-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 265.37 0.00 01-JAN-12:40 66565.08 17-JAN-07:10
EnergyTransfer:Building 109.13 0.00 01-JAN-12:40 30501.47 17-JAN-07:10
EnergyTransfer:Zone:CORE_ZN 13.44 0.00 01-JAN-00:10 5456.65 17-JAN-07:10
Heating:EnergyTransfer 82.02 0.00 01-JAN-12:40 30501.47 17-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 3.60 0.00 01-JAN-00:10 5456.65 17-JAN-07:10
General:Heating:EnergyTransfer 82.02 0.00 01-JAN-12:40 30501.47 17-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 3.60 0.00 01-JAN-00:10 5456.65 17-JAN-07:10
Cooling:EnergyTransfer 27.12 0.00 01-JAN-00:10 16119.54 24-JUL-15:10
Cooling:EnergyTransfer:Zone:CORE_ZN 9.84 0.00 01-JAN-00:10 4142.12 28-AUG-07:20
General:Cooling:EnergyTransfer 27.12 0.00 01-JAN-00:10 16119.54 24-JUL-15:10
General:Cooling:EnergyTransfer:Zone:CORE_ZN 9.84 0.00 01-JAN-00:10 4142.12 28-AUG-07:20
EnergyTransfer:Zone:PERIMETER_ZN_1 29.89 0.00 01-JAN-00:40 8989.18 04-DEC-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 23.67 0.00 01-JAN-00:40 8989.18 04-DEC-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 23.67 0.00 01-JAN-00:40 8989.18 04-DEC-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 6.22 0.00 01-JAN-00:10 5171.05 01-SEP-14:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 6.22 0.00 01-JAN-00:10 5171.05 01-SEP-14:40
EnergyTransfer:Zone:PERIMETER_ZN_2 18.33 0.00 01-JAN-00:40 4866.30 13-MAR-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 14.53 0.00 01-JAN-00:40 4866.30 13-MAR-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 14.53 0.00 01-JAN-00:40 4866.30 13-MAR-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 3.79 0.00 01-JAN-00:10 3453.09 24-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 3.79 0.00 01-JAN-00:10 3453.09 24-JUL-09:00
EnergyTransfer:Zone:PERIMETER_ZN_3 29.34 0.00 01-JAN-00:40 7052.95 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 25.32 0.00 01-JAN-00:40 7052.95 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 25.32 0.00 01-JAN-00:40 7052.95 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 4.02 0.00 01-JAN-00:10 2922.03 24-JUL-14:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 4.02 0.00 01-JAN-00:10 2922.03 24-JUL-14:50
EnergyTransfer:Zone:PERIMETER_ZN_4 18.14 0.00 01-JAN-00:40 4821.64 02-JAN-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 14.89 0.00 01-JAN-00:40 4821.64 02-JAN-07:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 14.89 0.00 01-JAN-00:40 4821.64 02-JAN-07:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 3.25 0.00 01-JAN-00:10 3135.42 24-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 3.25 0.00 01-JAN-00:10 3135.42 24-JUL-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
EnergyTransfer:HVAC 156.23 0.00 01-JAN-12:40 36062.90 17-JAN-07:10
CoolingCoils:EnergyTransfer 30.78 0.00 01-JAN-00:10 23857.49 30-JUN-16:00
HeatingCoils:EnergyTransfer 125.45 0.00 01-JAN-12:40 36062.90 17-JAN-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 118.65 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 3.602 -9.840 0.000 0.000 5.464 8.499 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -21.865
PERIMETER_ZN_1 0.000 0.000 23.673 -6.217 0.000 0.000 4.201 5.388 10.719 20.995 0.000 0.119 0.000 0.000 -10.901 0.000 -13.254 -34.722
PERIMETER_ZN_2 0.000 0.000 14.534 -3.795 0.000 0.000 1.822 3.289 6.359 8.219 0.000 0.004 0.000 0.000 -6.068 0.000 -1.183 -23.182
PERIMETER_ZN_3 0.000 0.000 25.318 -4.018 0.000 0.000 4.224 5.717 10.719 4.357 0.000 0.008 0.000 0.000 -9.729 0.000 -1.749 -34.848
PERIMETER_ZN_4 0.000 0.000 14.889 -3.248 0.000 0.000 2.481 3.294 6.359 8.344 0.000 0.003 0.000 0.000 -6.320 0.000 -1.195 -24.608
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.065 19.723 0.000 0.000 0.000 -30.789 -0.000
Total Facility 0.000 0.000 82.016 -27.118 0.000 0.000 18.192 26.188 48.296 41.915 0.000 11.199 19.724 0.000 -33.017 0.000 -48.169 -139.225


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 11-SEP-07:03 0.00 0.00 0.00 -5039.21 0.00 0.00 529.96 593.08 973.59 0.00 0.00 0.00 2942.58 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 01-SEP-14:40 0.00 0.00 0.00 -5172.54 0.00 0.00 427.32 328.16 738.04 4055.46 0.00 45.67 0.00 0.00 -0.00 0.00 0.00 -422.10
PERIMETER_ZN_2 07-JUN-07:02 0.00 0.00 0.00 -3934.35 0.00 0.00 225.54 194.67 437.82 3237.78 0.00 0.00 0.00 0.00 -0.00 0.00 -6.69 -154.77
PERIMETER_ZN_3 07-JUL-07:02 0.00 0.00 0.00 -4575.22 0.00 0.00 399.51 332.46 738.04 285.56 0.00 0.00 2830.81 0.00 -0.00 0.00 -11.15 0.00
PERIMETER_ZN_4 07-AUG-07:02 0.00 0.00 0.00 -4369.82 0.00 0.00 224.94 237.37 437.82 55.24 0.00 0.00 3427.51 0.00 -0.00 0.00 -13.06 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 14-AUG-07:02 0.00 0.00 0.00 -20347.55 0.00 0.00 1775.77 1918.20 3325.31 0.00 0.00 0.00 13989.38 0.00 -196.63 0.00 -464.49 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 21-FEB-06:01 0.00 0.00 7301.82 0.00 0.00 0.00 87.59 151.56 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8027.76
PERIMETER_ZN_1 20-FEB-06:42 0.00 0.00 10150.01 0.00 0.00 0.00 0.00 89.92 125.99 0.00 0.00 0.00 0.00 0.00 -782.40 0.00 -145.04 -9438.48
PERIMETER_ZN_2 30-JAN-06:01 0.00 0.00 7306.56 0.00 0.00 0.00 41.76 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -298.16 0.00 -66.50 -7270.72
PERIMETER_ZN_3 20-FEB-05:32 0.00 0.00 8256.76 0.00 0.00 0.00 0.00 89.92 125.99 0.00 0.00 0.00 0.00 0.00 -621.78 0.00 -144.98 -7705.90
PERIMETER_ZN_4 21-FEB-06:01 0.00 0.00 8350.92 0.00 0.00 0.00 40.45 68.16 218.91 0.00 0.00 0.00 0.00 0.00 -213.82 0.00 -63.39 -8401.22
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-FEB-06:01 0.00 0.00 40579.28 0.00 0.00 0.00 306.82 517.66 1662.65 0.00 0.00 1003.69 0.00 0.00 -1142.47 0.00 -606.82 -42320.82



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2715 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2715 0.2380 1.0000 Not calculated 0.0646 0.2380    
PSZ-AC:2 0.3557 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3557 0.1377 1.0000 Not calculated 0.0490 0.1377    
PSZ-AC:3 0.2592 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2592 0.1121 1.0000 Not calculated 0.0291 0.1121    
PSZ-AC:4 0.2794 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2794 0.2001 1.0000 Not calculated 0.0490 0.1754    
PSZ-AC:5 0.3083 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3083 0.0943 1.0000 Not calculated 0.0291 0.0943    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2715 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2715 1.0000 1.0000 Not calculated 0.0646 0.2380    
PSZ-AC:2 0.3557 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3557 1.0000 1.0000 Not calculated 0.0490 0.1377    
PSZ-AC:3 0.2592 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2592 1.0000 1.0000 Not calculated 0.0291 0.1121    
PSZ-AC:4 0.2794 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2794 1.0000 1.0000 Not calculated 0.0490 0.1754    
PSZ-AC:5 0.3083 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3083 1.0000 1.0000 Not calculated 0.0291 0.0943    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.002360 8.0545 0.000305 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.002360 6.1058 0.000305 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.002360 3.6221 0.000305 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.002360 8.05 0.000305 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.002360 6.11 0.000305 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.002360 3.62 0.000305 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2715 0.2715 0.2715 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3557 0.3557 0.3557 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2592 0.2592 0.2592 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2794 0.2794 0.2794 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3083 0.3083 0.3083 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2715 0.2715 0.2715 0.2715 0.0646 1.0000
PSZ-AC:2 0.3557 0.3557 0.3557 0.3557 0.0490 1.0000
PSZ-AC:3 0.2592 0.2592 0.2592 0.2592 0.0291 1.0000
PSZ-AC:4 0.2794 0.2794 0.2794 0.2794 0.0490 1.0000
PSZ-AC:5 0.3083 0.3083 0.3083 0.3083 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2715 0.2715 0.2715 No 0.0646 0.8332 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3557 0.3557 0.3557 No 0.0490 0.1736 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2592 0.2592 0.2592 No 0.0291 0.1610 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2794 0.2794 0.2794 No 0.0490 0.1754 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3083 0.3083 0.3083 No 0.0291 0.1595 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2715 0.2715 0.2715 0.2715 0.0646 1.0000
PSZ-AC:2 0.3557 0.3557 0.3557 0.3557 0.0490 1.0000
PSZ-AC:3 0.2592 0.2592 0.2592 0.2592 0.0291 1.0000
PSZ-AC:4 0.2794 0.2794 0.2794 0.2794 0.0490 1.0000
PSZ-AC:5 0.3083 0.3083 0.3083 0.3083 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [m2] 511.16
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 177.33
Number of hours cooling loads not met 4.83
Number of hours not met 182.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 25.04 8304.44 101.54 44645.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 6.13 5114.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.19 2025.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.95 1049.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 23.24 1651.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 25.29 2848.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 164.14
Natural Gas 0.00 101.54
Additional 0.00 0.00
Total 48.30 265.67


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.23
Space Heating 48.99
Space Cooling 11.99
Fans (All) 45.47
Service Water Heating 49.48
Receptacle Equipment 94.48
Miscellaneous (All) 321.11
Subtotal 321.11


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 198.64
Service Water Heating 0.00
Miscellaneous (All) 198.64
Subtotal 198.64


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 9.86
Space Heating 47.64
Space Cooling 2.31
Fans (All) 8.75
Service Water Heating 9.52
Receptacle Equipment 18.18
Miscellaneous 3.75


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2635. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8582.17 177.83 0.00 0.00 0.00
PERIMETER_ZN_1 8544.33 215.67 0.00 0.00 0.00
PERIMETER_ZN_2 8605.00 155.00 0.00 0.00 0.00
PERIMETER_ZN_3 8730.17 29.83 0.00 0.00 0.00
PERIMETER_ZN_4 8424.17 335.83 0.00 0.00 0.00
ATTIC 7531.67 438.00 358.33 357.17 74.83
Min 7531.67 29.83 0.00 0.00 0.00
Max 8730.17 438.00 358.33 357.17 74.83
Average 8402.92 225.36 59.72 59.53 12.47
Sum 50417.50 1352.17 358.33 357.17 74.83


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7505.00 1255.00 0.00 0.00 0.00
PERIMETER_ZN_1 7961.17 798.83 0.00 0.00 0.00
PERIMETER_ZN_2 8104.83 655.17 0.00 0.00 0.00
PERIMETER_ZN_3 8166.67 593.33 0.00 0.00 0.00
PERIMETER_ZN_4 8000.83 759.17 0.00 0.00 0.00
ATTIC 7522.17 687.67 210.00 172.00 168.17
Min 7505.00 593.33 0.00 0.00 0.00
Max 8166.67 1255.00 210.00 172.00 168.17
Average 7876.78 791.53 35.00 28.67 28.03
Sum 47260.67 4749.17 210.00 172.00 168.17


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17740.00 152.00 0.00 0.00 0.00
PERIMETER_ZN_1 13251.33 104.67 0.00 0.00 0.00
PERIMETER_ZN_2 4775.17 12.83 0.00 0.00 0.00
PERIMETER_ZN_3 13289.33 66.67 0.00 0.00 0.00
PERIMETER_ZN_4 6796.17 7.83 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17740.00 152.00 0.00 0.00 0.00
Average 9308.67 57.33 0.00 0.00 0.00
Sum 55852.00 344.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:30:16

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 65972394.25 3339.73 05-JAN-06:46 -32.3 -32.4 0.218746E+09 304.45 23-JAN-13:09 -19.2 -19.7
February 0.119168E+09 3355.50 17-FEB-06:01 -31.6 -31.7 0.199067E+09 304.44 13-FEB-14:09 -31.6 -31.7
March 0.273204E+09 2829.84 16-MAR-05:01 -24.2 -24.5 0.241888E+09 327.19 31-MAR-15:00 8.90 3.77
April 0.465272E+09 2058.50 05-APR-05:01 -13.4 -13.9 0.222370E+09 394.07 13-APR-15:00 20.00 8.11
May 0.780120E+09 4220.27 19-MAY-07:03 14.87 10.69 0.293425E+09 462.18 26-MAY-07:10 20.08 16.35
June 0.142852E+10 4686.68 07-JUN-07:02 19.50 11.27 0.313724E+09 469.21 30-JUN-07:10 26.02 21.73
July 0.196505E+10 4635.55 18-JUL-07:01 14.97 13.05 0.288278E+09 469.22 26-JUL-07:10 16.38 13.78
August 0.212775E+10 4755.35 02-AUG-07:03 12.88 11.28 0.330575E+09 469.22 07-AUG-07:10 13.98 13.37
September 0.131719E+10 5039.32 11-SEP-07:03 12.30 10.34 0.282645E+09 469.22 01-SEP-07:10 12.30 10.34
October 0.778978E+09 2015.18 30-OCT-07:05 -9.0 -9.4 0.253007E+09 402.34 02-OCT-15:09 -9.0 -9.4
November 0.411466E+09 2546.29 29-NOV-06:01 -20.3 -20.5 0.223924E+09 367.52 01-NOV-15:00 -20.3 -20.5
December 0.107810E+09 3025.72 21-DEC-06:01 -27.3 -27.5 0.208968E+09 304.45 18-DEC-13:09 -27.3 -27.5
                     
Annual Sum or Average 0.984049E+10         0.307662E+10        
Minimum of Months 65972394.25 2015.18   -32.3 -32.4 0.199067E+09 304.44   -31.6 -31.7
Maximum of Months 0.212775E+10 5039.32   19.50 13.05 0.330575E+09 469.22   26.02 21.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7681393.70 2392.45 05-JAN-13:05 -27.6 -27.9 0.159556E+09 230.75 03-JAN-10:30 -27.6 -27.9
February 38552231.25 1417.39 10-FEB-13:33 -13.2 -14.4 0.148242E+09 272.38 28-FEB-15:39 6.10 1.55
March 60193918.13 1203.70 02-MAR-06:04 -8.3 -8.8 0.181726E+09 280.27 31-MAR-15:20 8.50 3.01
April 76032603.07 1230.86 04-APR-05:04 -9.0 -10.5 0.168525E+09 304.99 18-APR-14:50 15.47 9.11
May 0.398463E+09 2744.34 18-MAY-14:10 28.57 16.73 0.208958E+09 310.34 10-MAY-15:30 28.57 16.73
June 0.869404E+09 4069.07 30-JUN-14:10 31.28 23.89 0.230231E+09 355.70 30-JUN-07:10 31.28 23.89
July 0.152396E+10 4657.15 24-JUL-12:00 28.30 19.76 0.216362E+09 355.69 24-JUL-07:10 28.30 19.76
August 0.173849E+10 4465.02 29-AUG-14:30 25.60 20.40 0.248171E+09 337.33 09-AUG-07:10 25.60 20.40
September 0.103724E+10 5172.62 01-SEP-14:40 25.93 17.92 0.203277E+09 306.39 01-SEP-14:09 25.93 17.92
October 0.375660E+09 3464.17 20-OCT-14:00 18.90 10.07 0.184598E+09 305.00 19-OCT-13:50 18.90 10.07
November 89961928.32 1138.88 28-NOV-06:04 -7.8 -8.4 0.169722E+09 304.99 17-NOV-15:00 -7.8 -8.4
December 1739547.02 1190.82 04-DEC-06:04 -9.4 -9.8 0.153986E+09 230.75 18-DEC-11:00 -22.8 -23.6
                     
Annual Sum or Average 0.621738E+10         0.227335E+10        
Minimum of Months 1739547.02 1138.88   -27.6 -27.9 0.148242E+09 230.75   -27.6 -27.9
Maximum of Months 0.173849E+10 5172.62   31.28 23.89 0.248171E+09 355.70   31.28 23.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2145498.49 1184.79 05-JAN-18:01 -28.4 -28.6 70734204.00 136.88 03-JAN-09:00 -28.4 -28.6
February 2034903.76 924.38 01-FEB-18:03 -23.6 -24.1 64251369.81 136.88 13-FEB-13:00 -20.0 -20.8
March 2296577.61 668.86 02-MAR-06:04 -8.3 -8.8 78010987.06 136.88 13-MAR-08:00 -13.3 -14.1
April 28904537.98 616.42 06-APR-05:04 -6.0 -6.9 71037208.61 174.99 18-APR-10:39 17.57 11.16
May 0.231492E+09 3060.02 18-MAY-07:02 18.48 13.33 92311909.45 192.35 26-MAY-07:10 20.08 16.35
June 0.747117E+09 3934.26 07-JUN-07:02 19.50 11.27 0.102807E+09 211.00 21-JUN-07:10 16.57 14.02
July 0.119299E+10 3855.32 18-JUL-07:01 14.97 13.05 95322807.40 211.01 07-JUL-07:10 14.97 13.05
August 0.101717E+10 3840.06 02-AUG-07:03 12.88 11.28 0.108956E+09 211.00 21-AUG-07:10 15.97 15.14
September 0.471431E+09 3179.50 05-SEP-07:02 8.77 7.97 89281244.63 208.30 01-SEP-07:10 8.77 7.97
October 90320236.31 723.02 30-OCT-05:04 -9.9 -10.6 77177437.35 180.93 19-OCT-15:39 -9.9 -10.6
November 6583016.74 713.44 24-NOV-06:04 -10.5 -11.1 71724264.10 154.71 01-NOV-15:00 -10.5 -11.1
December 2236671.10 1069.58 19-DEC-18:01 -24.5 -24.9 67580306.58 136.88 29-DEC-08:50 -16.1 -16.6
                     
Annual Sum or Average 0.379472E+10         0.989195E+09        
Minimum of Months 2034903.76 616.42   -28.4 -28.6 64251369.81 136.88   -28.4 -28.6
Maximum of Months 0.119299E+10 3934.26   19.50 13.33 0.108956E+09 211.01   20.08 16.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4215031.80 2286.10 05-JAN-18:01 -28.4 -28.6 0.164255E+09 230.76 03-JAN-11:00 -28.4 -28.6
February 3868732.99 1896.33 01-FEB-18:03 -23.6 -24.1 0.149204E+09 230.76 13-FEB-14:00 -18.9 -19.8
March 4026624.24 1685.37 23-MAR-05:05 -17.1 -17.4 0.181154E+09 230.75 15-MAR-12:09 -17.1 -17.4
April 7168223.34 1055.10 20-APR-05:05 -4.1 -6.7 0.159027E+09 254.43 13-APR-15:00 -4.1 -6.7
May 0.229016E+09 1789.48 26-MAY-07:03 20.08 16.35 0.203306E+09 311.95 26-MAY-07:10 20.08 16.35
June 0.688974E+09 3801.90 27-JUN-07:02 20.47 17.58 0.231712E+09 355.70 30-JUN-07:10 26.02 21.73
July 0.119089E+10 4575.48 07-JUL-07:02 16.28 13.09 0.216830E+09 355.69 24-JUL-07:10 20.97 18.41
August 0.117766E+10 4419.34 14-AUG-07:02 15.10 13.70 0.248242E+09 353.24 09-AUG-07:10 15.10 13.70
September 0.535297E+09 3554.54 01-SEP-07:03 16.38 15.95 0.200979E+09 329.14 01-SEP-07:10 16.38 15.95
October 0.161860E+09 1146.04 25-OCT-07:05 -3.2 -3.4 0.172430E+09 301.02 20-OCT-15:00 -3.2 -3.4
November 10443096.09 1260.65 28-NOV-18:03 -10.8 -11.5 0.166444E+09 256.59 01-NOV-15:00 -10.8 -11.5
December 4502327.99 2084.98 19-DEC-18:01 -24.5 -24.9 0.157046E+09 230.76 18-DEC-11:00 -24.5 -24.9
                     
Annual Sum or Average 0.401793E+10         0.225063E+10        
Minimum of Months 3868732.99 1055.10   -28.4 -28.6 0.149204E+09 230.75   -28.4 -28.6
Maximum of Months 0.119089E+10 4575.48   20.47 17.58 0.248242E+09 355.70   26.02 21.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 2008185.50 1110.77 05-JAN-18:01 -28.4 -28.6 97723205.32 136.88 03-JAN-11:00 -28.4 -28.6
February 5127358.67 868.72 01-FEB-18:03 -23.6 -24.1 88751921.00 140.50 08-FEB-16:49 3.48 -1.2
March 11620736.63 713.74 20-MAR-05:04 -8.7 -8.9 0.107900E+09 150.63 31-MAR-15:00 8.90 3.77
April 15793906.57 577.22 03-APR-05:04 -4.3 -5.8 97244151.30 180.92 13-APR-15:00 20.00 8.11
May 0.221218E+09 3789.92 26-MAY-07:03 20.08 16.35 0.126559E+09 207.22 26-MAY-07:10 20.08 16.35
June 0.550194E+09 3882.05 22-JUN-07:02 18.27 16.37 0.139616E+09 211.00 30-JUN-07:10 26.02 21.73
July 0.971665E+09 4315.06 07-JUL-07:02 16.28 13.09 0.130159E+09 211.00 05-JUL-07:10 16.28 13.09
August 0.966020E+09 4370.03 07-AUG-07:02 13.98 13.37 0.148844E+09 211.00 09-AUG-07:10 19.68 18.07
September 0.400397E+09 3315.94 01-SEP-07:03 16.38 15.95 0.123456E+09 204.90 01-SEP-07:10 16.38 15.95
October 91038425.61 961.88 19-OCT-15:57 21.70 13.55 0.107499E+09 181.68 18-OCT-15:09 21.70 13.55
November 10543707.58 759.12 24-NOV-06:04 -10.5 -11.1 99037813.64 159.01 01-NOV-15:00 -10.5 -11.1
December 1936432.37 995.22 19-DEC-18:01 -24.5 -24.9 93310584.67 136.88 18-DEC-11:00 -24.5 -24.9
                     
Annual Sum or Average 0.324756E+10         0.136010E+10        
Minimum of Months 1936432.37 577.22   -28.4 -28.6 88751921.00 136.88   -28.4 -28.6
Maximum of Months 0.971665E+09 4370.03   21.70 16.37 0.148844E+09 211.00   26.02 21.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9 -22.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.00 0.00 01-FEB-00:03 -23.1 -23.5 0.00 0.00 01-FEB-00:10 -23.1 -23.5
March 0.00 0.00 01-MAR-00:10 -1.3 -3.3 0.00 0.00 01-MAR-00:10 -1.3 -3.3
April 0.00 0.00 01-APR-00:10 3.52 0.38 0.00 0.00 01-APR-00:10 3.52 0.38
May 0.00 0.00 01-MAY-00:05 -0.0 -1.4 0.00 0.00 01-MAY-00:10 -0.0 -1.4
June 0.00 0.00 01-JUN-00:10 11.35 8.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.00 0.00 01-JUL-00:10 15.83 13.57 0.00 0.00 01-JUL-00:10 15.83 13.57
August 0.00 0.00 01-AUG-00:10 17.07 15.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.00 0.00 01-SEP-00:10 19.75 18.15 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.00 0.00 01-OCT-00:10 7.52 6.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.00 0.00 01-NOV-00:10 3.60 0.51 0.00 0.00 01-NOV-00:10 3.60 0.51
December 0.00 0.00 01-DEC-00:05 -8.8 -9.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -23.1 -23.5 0.00 0.00   -23.1 -23.5
Maximum of Months 0.00 0.00   19.75 18.15 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109823E+10 7113.48 30-JAN-06:01 -4.0
February 0.650151E+09 7301.86 21-FEB-06:01 2.80
March 0.509668E+09 6884.15 27-MAR-06:01 -3.4
April 0.148874E+09 6947.80 03-APR-06:01 -3.8
May 48147892.04 6862.14 01-MAY-06:01 -3.5
June 18172306.74 1012.29 29-JUN-16:03 34.90
July 16450097.47 610.16 28-JUL-16:03 29.32
August 11110877.28 680.40 08-AUG-16:03 30.40
September 847986.59 347.00 01-SEP-16:03 25.82
October 24828358.31 6573.25 10-OCT-06:01 3.90
November 0.294998E+09 6873.69 06-NOV-07:01 -3.9
December 0.780153E+09 6866.87 05-DEC-07:01 -1.1
         
Annual Sum or Average 0.360163E+10      
Minimum of Months 847986.59 347.00   -4.0
Maximum of Months 0.109823E+10 7301.86   34.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.595680E+10 10135.52 17-JAN-06:01 -5.9
February 0.388090E+10 10150.13 20-FEB-06:42 -10.7
March 0.368898E+10 9961.39 17-MAR-05:01 -8.1
April 0.155904E+10 10077.62 10-APR-05:01 -2.7
May 0.371342E+09 9966.43 01-MAY-05:01 -3.4
June 55559326.02 5127.09 13-JUN-07:02 14.08
July 24645314.15 552.38 28-JUL-17:23 28.90
August 16719340.77 513.38 08-AUG-17:23 28.85
September 31145605.10 4717.05 29-SEP-07:03 7.88
October 0.672692E+09 9566.49 30-OCT-05:01 -9.9
November 0.218062E+10 10065.54 27-NOV-06:01 -7.1
December 0.523447E+10 10111.49 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.236729E+11      
Minimum of Months 16719340.77 513.38   -10.7
Maximum of Months 0.595680E+10 10150.13   28.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383024E+10 7306.56 30-JAN-06:01 -4.0
February 0.268612E+10 7232.25 21-FEB-06:01 2.80
March 0.230502E+10 7190.93 22-MAR-05:01 -2.3
April 0.749410E+09 7167.04 17-APR-05:01 -1.1
May 0.102174E+09 7159.38 01-MAY-05:01 -3.4
June 24367677.25 531.87 29-JUN-17:23 33.60
July 15979497.54 381.78 28-JUL-17:23 28.90
August 14181730.64 369.86 08-AUG-17:23 28.85
September 3757640.24 1558.63 29-SEP-07:03 7.88
October 0.267713E+09 6673.27 30-OCT-05:01 -9.9
November 0.127279E+10 7105.09 07-NOV-06:01 -6.2
December 0.326225E+10 7067.51 05-DEC-06:01 -1.1
         
Annual Sum or Average 0.145340E+11      
Minimum of Months 3757640.24 369.86   -9.9
Maximum of Months 0.383024E+10 7306.56   33.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.630195E+10 8143.54 15-JAN-11:32 -10.2
February 0.468622E+10 8256.91 20-FEB-05:32 -11.5
March 0.428135E+10 8095.94 05-MAR-12:32 -10.4
April 0.179156E+10 7972.82 10-APR-05:01 -2.7
May 0.325427E+09 7755.87 01-MAY-05:01 -3.4
June 31914001.12 795.29 29-JUN-16:03 34.90
July 17836490.94 512.01 28-JUL-16:03 29.32
August 13676971.35 552.57 08-AUG-16:03 30.40
September 3772130.10 3630.65 29-SEP-07:03 7.88
October 0.471649E+09 7767.43 30-OCT-05:01 -9.9
November 0.215637E+10 7964.62 27-NOV-06:01 -7.1
December 0.523635E+10 8022.92 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.253181E+11      
Minimum of Months 3772130.10 512.01   -11.5
Maximum of Months 0.630195E+10 8256.91   34.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.385106E+10 7829.54 30-JAN-06:01 -4.0
February 0.270451E+10 8350.84 21-FEB-06:01 2.80
March 0.235771E+10 8164.99 21-MAR-05:01 0.00
April 0.917194E+09 8216.22 17-APR-05:01 -1.1
May 0.164002E+09 8084.59 01-MAY-05:01 -3.4
June 40606136.52 529.60 29-JUN-17:23 33.60
July 16676865.54 378.57 28-JUL-17:23 28.90
August 15191997.74 382.97 08-AUG-17:23 28.85
September 3690901.96 497.50 29-SEP-07:03 7.88
October 0.263897E+09 7530.42 11-OCT-06:01 1.20
November 0.126177E+10 7749.35 08-NOV-06:02 -3.9
December 0.329258E+10 8022.45 05-DEC-06:01 -1.1
         
Annual Sum or Average 0.148889E+11      
Minimum of Months 3690901.96 378.57   -4.0
Maximum of Months 0.385106E+10 8350.84   33.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9
February 0.00 0.00 01-FEB-00:03 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:05 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:10 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:05 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.714248E+09 593.08 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.645736E+09 593.08 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.752015E+09 593.08 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.685116E+09 593.08 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.733131E+09 593.08 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.722883E+09 593.08 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.695364E+09 593.08 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.752015E+09 593.08 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.685116E+09 593.08 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.714248E+09 593.08 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.704000E+09 593.08 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.695364E+09 593.08 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.849924E+10     0.141401E+11    
Minimum of Months 0.645736E+09 593.08   0.107295E+10 973.59  
Maximum of Months 0.752015E+09 593.08   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.468831E+09 449.59 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.412747E+09 438.17 02-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.475637E+09 435.38 03-MAR-16:00 0.953087E+09 738.04 01-MAR-08:09
April 0.426864E+09 418.50 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.448742E+09 385.75 19-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.442845E+09 418.45 30-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.425991E+09 397.77 03-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.468436E+09 430.34 31-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.430593E+09 430.92 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.457852E+09 448.60 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.463370E+09 449.59 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.466254E+09 449.59 01-DEC-16:19 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.538816E+10     0.107191E+11    
Minimum of Months 0.412747E+09 385.75   0.813362E+09 738.04  
Maximum of Months 0.475637E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289410E+09 266.70 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.254263E+09 262.50 02-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.291457E+09 259.95 03-MAR-16:00 0.565383E+09 437.82 01-MAR-08:09
April 0.260053E+09 245.92 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.271018E+09 239.48 05-MAY-15:00 0.549505E+09 437.82 01-MAY-07:10
June 0.266748E+09 246.99 30-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.256886E+09 241.06 25-JUL-15:39 0.518151E+09 437.82 03-JUL-07:10
August 0.283340E+09 255.16 31-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.262335E+09 255.12 19-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.281822E+09 266.13 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.285865E+09 266.70 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.286194E+09 266.70 01-DEC-16:19 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.328939E+10     0.635872E+10    
Minimum of Months 0.254263E+09 239.48   0.482497E+09 437.82  
Maximum of Months 0.291457E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.513026E+09 449.59 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.450530E+09 441.38 02-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.514627E+09 437.38 03-MAR-16:00 0.953087E+09 738.04 01-MAR-08:09
April 0.456539E+09 422.37 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.458321E+09 396.86 19-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.445523E+09 420.07 30-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.431969E+09 400.92 25-JUL-15:30 0.873466E+09 738.04 03-JUL-07:10
August 0.482402E+09 432.40 31-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.459168E+09 433.25 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.497705E+09 448.86 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.504665E+09 449.59 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.502818E+09 449.59 01-DEC-16:19 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.571729E+10     0.107191E+11    
Minimum of Months 0.431969E+09 396.86   0.813362E+09 738.04  
Maximum of Months 0.514627E+09 449.59   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289315E+09 266.70 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.253555E+09 259.65 02-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.292459E+09 260.00 13-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.262070E+09 253.18 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.271200E+09 242.24 12-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.267200E+09 250.96 30-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.258226E+09 243.19 03-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.283727E+09 257.00 31-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.262627E+09 257.76 19-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.281277E+09 266.28 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.285828E+09 266.70 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.286875E+09 266.70 01-DEC-16:19 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.329436E+10     0.635872E+10    
Minimum of Months 0.253555E+09 242.24   0.482497E+09 437.82  
Maximum of Months 0.292459E+09 266.70   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.714248E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.685116E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.733131E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.722883E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.695364E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.685116E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.714248E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.704000E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.695364E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.849924E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.645736E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.752015E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.468831E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.246912E+10
February 0.488155E+09 0.412747E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.187730E+10
March 0.590925E+09 0.475637E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.172635E+10
April 0.513848E+09 0.426864E+09 0.862580E+09 0.00 0.00 0.00 0.00 541125.25 0.964963E+09
May 0.565233E+09 0.448742E+09 0.926320E+09 0.00 0.00 0.00 0.00 17696322.10 0.451836E+09
June 0.565233E+09 0.442845E+09 0.914754E+09 0.00 0.00 0.00 0.00 42989588.64 0.240799E+09
July 0.513848E+09 0.425991E+09 0.873466E+09 0.00 0.00 0.00 0.00 37993013.86 0.191943E+09
August 0.590925E+09 0.468436E+09 0.953087E+09 0.00 0.00 0.00 0.00 19104246.63 0.331034E+09
September 0.513848E+09 0.430593E+09 0.861220E+09 0.00 0.00 0.00 0.00 611048.31 0.573599E+09
October 0.539540E+09 0.457852E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.928231E+09
November 0.539540E+09 0.463370E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.131431E+10
December 0.513848E+09 0.466254E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.218460E+10
                   
Annual Sum or Average 0.647448E+10 0.538816E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.118935E+09 0.132541E+11
Minimum of Months 0.488155E+09 0.412747E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.191943E+09
Maximum of Months 0.590925E+09 0.475637E+09 0.953087E+09 0.00 0.00 0.00 0.00 42989588.64 0.246912E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.289410E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.202863E+09
February 0.211974E+09 0.254263E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.169377E+09
March 0.256600E+09 0.291457E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.115331E+09
April 0.223130E+09 0.260053E+09 0.511694E+09 0.00 0.00 0.00 0.00 947769.95 92730128.74
May 0.245443E+09 0.271018E+09 0.549505E+09 0.00 0.00 0.00 0.00 353981.74 45332568.14
June 0.245443E+09 0.266748E+09 0.542644E+09 0.00 0.00 0.00 0.00 1240986.93 27811633.98
July 0.223130E+09 0.256886E+09 0.518151E+09 0.00 0.00 0.00 0.00 984594.29 23132889.03
August 0.256600E+09 0.283340E+09 0.565383E+09 0.00 0.00 0.00 0.00 399839.34 34490749.05
September 0.223130E+09 0.262335E+09 0.510887E+09 0.00 0.00 0.00 0.00 15348.35 54781031.52
October 0.234287E+09 0.281822E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 72728790.97
November 0.234287E+09 0.285865E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.132323E+09
December 0.223130E+09 0.286194E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.211633E+09
                   
Annual Sum or Average 0.281144E+10 0.328939E+10 0.635872E+10 0.00 0.00 0.00 0.00 3942520.60 0.118253E+10
Minimum of Months 0.211974E+09 0.254263E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 23132889.03
Maximum of Months 0.256600E+09 0.291457E+09 0.565383E+09 0.00 0.00 0.00 0.00 1240986.93 0.211633E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.513026E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.304477E+09
February 0.488155E+09 0.450530E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.254028E+09
March 0.590925E+09 0.514627E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.172617E+09
April 0.513848E+09 0.456539E+09 0.862580E+09 0.00 0.00 0.00 0.00 1940834.33 0.135243E+09
May 0.565233E+09 0.458321E+09 0.926320E+09 0.00 0.00 0.00 0.00 686695.41 64031794.91
June 0.565233E+09 0.445523E+09 0.914754E+09 0.00 0.00 0.00 0.00 2321193.52 38548838.59
July 0.513848E+09 0.431969E+09 0.873466E+09 0.00 0.00 0.00 0.00 1858037.70 32842246.16
August 0.590925E+09 0.482402E+09 0.953087E+09 0.00 0.00 0.00 0.00 707997.89 47326830.57
September 0.513848E+09 0.459168E+09 0.861220E+09 0.00 0.00 0.00 0.00 23100.49 77772123.02
October 0.539540E+09 0.497705E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.106091E+09
November 0.539540E+09 0.504665E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.198329E+09
December 0.513848E+09 0.502818E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.317654E+09
                   
Annual Sum or Average 0.647448E+10 0.571729E+10 0.107191E+11 0.00 0.00 0.00 0.00 7537859.34 0.174896E+10
Minimum of Months 0.488155E+09 0.431969E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 32842246.16
Maximum of Months 0.590925E+09 0.514627E+09 0.953087E+09 0.00 0.00 0.00 0.00 2321193.52 0.317654E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.289315E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.202951E+09
February 0.289580E+09 0.253555E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.169658E+09
March 0.350544E+09 0.292459E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.116461E+09
April 0.304821E+09 0.262070E+09 0.511694E+09 0.00 0.00 0.00 0.00 579761.06 94131116.84
May 0.335303E+09 0.271200E+09 0.549505E+09 0.00 0.00 0.00 0.00 264385.20 47984614.97
June 0.335303E+09 0.267200E+09 0.542644E+09 0.00 0.00 0.00 0.00 1101001.56 28626614.12
July 0.304821E+09 0.258226E+09 0.518151E+09 0.00 0.00 0.00 0.00 937974.21 25632789.60
August 0.350544E+09 0.283727E+09 0.565383E+09 0.00 0.00 0.00 0.00 390752.14 35770861.35
September 0.304821E+09 0.262627E+09 0.510887E+09 0.00 0.00 0.00 0.00 15315.62 55991142.87
October 0.320062E+09 0.281277E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 73490548.34
November 0.320062E+09 0.285828E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.132491E+09
December 0.304821E+09 0.286875E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.211620E+09
                   
Annual Sum or Average 0.384075E+10 0.329436E+10 0.635872E+10 0.00 0.00 0.00 0.00 3289189.79 0.119481E+10
Minimum of Months 0.289580E+09 0.253555E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 25632789.60
Maximum of Months 0.350544E+09 0.292459E+09 0.565383E+09 0.00 0.00 0.00 0.00 1101001.56 0.211620E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.129094E+10 0.118377E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111201E+10 0.173072E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.949935E+09 0.273003E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.880620E+09 0.329732E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.758073E+09 0.417244E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.627699E+09 0.403162E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.769397E+09 0.428317E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.661054E+09 0.342483E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.696611E+09 0.256528E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.999127E+09 0.163283E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111773E+10 0.848707E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120208E+10 0.887872E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110653E+11 0.307886E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.627699E+09 0.848707E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.129094E+10 0.428317E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 593.08 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 593.08 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 593.08 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 593.08 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 593.08 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 593.08 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 593.08 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 593.08 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 593.08 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 593.08 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 593.08 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 593.08 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   593.08   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 449.59 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 9875.42 06-JAN-07:01
February 732.70 01-FEB-08:09 438.17 02-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 9377.28 14-FEB-07:01
March 732.70 01-MAR-08:09 435.38 03-MAR-16:00 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7210.99 16-MAR-06:02
April 732.70 03-APR-07:10 418.50 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 42.19 23-APR-16:00 5385.03 05-APR-06:10
May 732.70 01-MAY-07:10 385.75 19-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 706.22 25-MAY-16:02 3859.79 01-MAY-06:10
June 732.70 01-JUN-07:10 418.45 30-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 1480.43 29-JUN-16:03 1755.74 02-JUN-06:03
July 732.70 03-JUL-07:10 397.77 03-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 714.79 28-JUL-16:03 1804.55 18-JUL-06:02
August 732.70 01-AUG-07:10 430.34 31-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 851.72 08-AUG-16:03 2211.03 25-AUG-06:03
September 732.70 01-SEP-07:10 430.92 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 177.32 01-SEP-16:03 3206.56 06-SEP-06:03
October 732.70 02-OCT-07:10 448.60 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 5014.13 30-OCT-07:00
November 732.70 01-NOV-07:10 449.59 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 6329.39 29-NOV-07:02
December 732.70 01-DEC-08:09 449.59 01-DEC-16:19 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 8669.24 20-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   385.75   738.04   0.00 0.00 0.00 0.00 0.00   1755.74  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 1480.43   9875.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 266.70 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 309.92 04-JAN-06:00
February 434.65 01-FEB-08:09 262.50 02-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 387.28 12-FEB-22:56
March 434.65 01-MAR-08:09 259.95 03-MAR-16:00 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 193.07 15-MAR-05:10
April 434.65 03-APR-07:10 245.92 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 53.88 23-APR-15:55 194.07 04-APR-18:03
May 434.65 01-MAY-07:10 239.48 05-MAY-15:00 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 8.12 10-MAY-18:10 81.09 20-MAY-06:00
June 434.65 01-JUN-07:10 246.99 30-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 24.86 29-JUN-18:10 53.76 15-JUN-19:53
July 434.65 03-JUL-07:10 241.06 25-JUL-15:39 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 11.21 15-JUL-18:00 58.42 06-JUL-22:00
August 434.65 01-AUG-07:10 255.16 31-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 9.45 08-AUG-16:00 82.35 27-AUG-06:00
September 434.65 01-SEP-07:10 255.12 19-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 1.57 01-SEP-14:55 99.08 20-SEP-01:00
October 434.65 02-OCT-07:10 266.13 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 122.90 31-OCT-19:00
November 434.65 01-NOV-07:10 266.70 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 206.73 22-NOV-02:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:19 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 299.50 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   239.48   437.82   0.00 0.00 0.00 0.00 0.00   53.76  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 53.88   387.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 449.59 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 464.89 04-JAN-06:00
February 732.70 01-FEB-08:09 441.38 02-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 573.39 12-FEB-22:52
March 732.70 01-MAR-08:09 437.38 03-MAR-16:00 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 289.60 15-MAR-05:10
April 732.70 03-APR-07:10 422.37 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 98.90 23-APR-15:55 290.96 04-APR-18:03
May 732.70 01-MAY-07:10 396.86 19-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 16.94 10-MAY-18:10 121.02 20-MAY-06:00
June 732.70 01-JUN-07:10 420.07 30-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 38.15 29-JUN-18:10 77.15 09-JUN-19:55
July 732.70 03-JUL-07:10 400.92 25-JUL-15:30 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 26.25 23-JUL-14:53 88.59 06-JUL-22:00
August 732.70 01-AUG-07:10 432.40 31-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 14.18 08-AUG-16:00 115.93 27-AUG-06:00
September 732.70 01-SEP-07:10 433.25 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 2.35 01-SEP-15:00 149.28 20-SEP-01:00
October 732.70 02-OCT-07:10 448.86 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 184.42 31-OCT-19:00
November 732.70 01-NOV-07:10 449.59 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 312.70 22-NOV-02:00
December 732.70 01-DEC-08:09 449.59 01-DEC-16:19 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 449.47 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   396.86   738.04   0.00 0.00 0.00 0.00 0.00   77.15  
Maximum of Months 732.70   449.59   738.04   0.00 0.00 0.00 0.00 98.90   573.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 266.70 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 309.92 04-JAN-06:00
February 434.65 01-FEB-08:09 259.65 02-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 381.98 12-FEB-22:52
March 434.65 01-MAR-08:09 260.00 13-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 193.07 15-MAR-05:10
April 434.65 03-APR-07:10 253.18 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 35.82 23-APR-15:55 196.55 04-APR-18:03
May 434.65 01-MAY-07:10 242.24 12-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 4.36 24-MAY-15:00 82.50 20-MAY-06:00
June 434.65 01-JUN-07:10 250.96 30-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 14.35 29-JUN-18:10 68.21 15-JUN-19:53
July 434.65 03-JUL-07:10 243.19 03-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 10.55 15-JUL-18:00 73.54 06-JUL-22:00
August 434.65 01-AUG-07:10 257.00 31-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 9.45 08-AUG-16:00 84.58 27-AUG-06:00
September 434.65 01-SEP-07:10 257.76 19-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 1.57 01-SEP-15:00 99.95 20-SEP-01:00
October 434.65 02-OCT-07:10 266.28 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 122.72 31-OCT-19:00
November 434.65 01-NOV-07:10 266.70 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 206.62 22-NOV-02:00
December 434.65 01-DEC-08:09 266.70 01-DEC-16:19 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 299.48 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   242.24   437.82   0.00 0.00 0.00 0.00 0.00   68.21  
Maximum of Months 434.65   266.70   437.82   0.00 0.00 0.00 0.00 35.82   381.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1905.79 28-JAN-02:55 3811.02 31-JAN-12:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1956.50 17-FEB-07:35 4309.18 01-FEB-13:30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1727.95 07-MAR-05:53 6983.56 23-MAR-13:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1884.06 22-APR-04:00 5873.74 21-APR-13:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1656.95 18-MAY-04:55 6994.35 01-MAY-13:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1659.70 04-JUN-04:00 6215.64 14-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1787.54 15-JUL-04:53 6574.64 13-JUL-12:40
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1791.70 05-AUG-03:55 5894.15 05-AUG-13:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1617.85 10-SEP-06:23 4762.82 06-SEP-12:30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1685.68 25-OCT-07:03 4533.62 09-OCT-12:30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1644.03 19-NOV-07:20 2818.28 10-NOV-12:50
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1497.00 03-DEC-01:42 2938.02 26-DEC-13:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1497.00   2818.28  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1956.50   6994.35  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 3339.73 05-JAN-06:46 531.60 757.81 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
February 3355.50 17-FEB-06:01 850.55 1212.49 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
March 2829.84 16-MAR-05:01 850.55 1212.49 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
April 2058.50 05-APR-05:01 744.23 1060.93 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
May 4220.27 19-MAY-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
June 4686.68 07-JUN-07:02 4832.69 2965.38 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
July 4635.55 18-JUL-07:01 6765.77 4151.53 6815.12 0.00 0.00 0.00 0.00 0.00 0.00
August 4755.35 02-AUG-07:03 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
September 5039.32 11-SEP-07:03 2899.62 1779.23 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
October 2015.18 30-OCT-07:05 3866.15 2372.30 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
November 2546.29 29-NOV-06:01 850.55 1212.49 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
December 3025.72 21-DEC-06:01 744.23 1060.93 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2015.18   531.60 757.81 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5039.32   6765.77 4151.53 6815.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2392.45 05-JAN-13:05 5861.59 2625.25 5904.34 0.00 0.00 0.00 0.00 0.00 1375.96
February 1417.39 10-FEB-13:33 2198.10 984.47 2214.13 0.00 0.00 0.00 0.00 0.00 863.12
March 1203.70 02-MAR-06:04 564.18 804.25 2583.15 0.00 0.00 0.00 0.00 0.00 771.78
April 1230.86 04-APR-05:04 564.18 804.25 2583.15 0.00 0.00 0.00 0.00 0.00 778.10
May 2744.34 18-MAY-14:10 732.70 328.16 738.04 0.00 0.00 0.00 0.00 103.67 0.00
June 4069.07 30-JUN-14:10 732.70 328.16 738.04 0.00 0.00 0.00 0.00 168.73 0.00
July 4657.15 24-JUL-12:00 894.47 583.39 1387.52 0.00 0.00 0.00 0.00 650.07 0.00
August 4465.02 29-AUG-14:30 732.70 328.16 738.04 0.00 0.00 0.00 0.00 39.02 0.00
September 5172.62 01-SEP-14:40 1465.40 656.31 1476.09 0.00 0.00 0.00 0.00 45.67 0.00
October 3464.17 20-OCT-14:00 732.70 328.16 738.04 0.00 0.00 0.00 0.00 0.00 117.25
November 1138.88 28-NOV-06:04 644.77 919.15 2952.17 0.00 0.00 0.00 0.00 0.00 804.04
December 1190.82 04-DEC-06:04 725.37 1034.04 3321.19 0.00 0.00 0.00 0.00 0.00 849.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1138.88   564.18 328.16 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5172.62   5861.59 2625.25 5904.34 0.00 0.00 0.00 0.00 650.07 1375.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1184.79 05-JAN-18:01 382.49 995.68 700.51 0.00 0.00 0.00 0.00 0.00 41.11
February 924.38 01-FEB-18:03 191.24 497.84 350.25 0.00 0.00 0.00 0.00 0.00 4.52
March 668.86 02-MAR-06:04 334.68 477.09 1532.36 0.00 0.00 0.00 0.00 0.00 93.93
April 616.42 06-APR-05:04 382.49 545.25 1751.27 0.00 0.00 0.00 0.00 0.00 26.67
May 3060.02 18-MAY-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 0.90
June 3934.26 07-JUN-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 6.69
July 3855.32 18-JUL-07:01 3042.52 1362.66 3064.72 0.00 0.00 0.00 0.00 0.00 3.41
August 3840.06 02-AUG-07:03 1738.59 778.66 1751.27 0.00 0.00 0.00 0.00 0.00 8.60
September 3179.50 05-SEP-07:02 2173.23 973.33 2189.08 0.00 0.00 0.00 0.00 0.00 8.82
October 723.02 30-OCT-05:04 334.68 477.09 1532.36 0.00 0.00 0.00 0.00 0.00 42.58
November 713.44 24-NOV-06:04 382.49 545.25 1751.27 0.00 0.00 0.00 0.00 0.00 75.81
December 1069.58 19-DEC-18:01 382.49 995.68 700.51 0.00 0.00 0.00 0.00 0.00 38.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 616.42   191.24 477.09 350.25 0.00 0.00 0.00 0.00 0.00 0.90
Maximum of Months 3934.26   3042.52 1362.66 3064.72 0.00 0.00 0.00 0.00 0.00 93.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2286.10 05-JAN-18:01 644.77 1678.45 1180.87 0.00 0.00 0.00 0.00 0.00 61.64
February 1896.33 01-FEB-18:03 322.39 839.23 590.43 0.00 0.00 0.00 0.00 0.00 6.77
March 1685.37 23-MAR-05:05 644.77 919.15 2952.17 0.00 0.00 0.00 0.00 0.00 0.00
April 1055.10 20-APR-05:05 322.39 459.57 1476.09 0.00 0.00 0.00 0.00 0.00 93.96
May 1789.48 26-MAY-07:03 2930.79 1327.84 2952.17 0.00 0.00 0.00 0.00 0.00 3.99
June 3801.90 27-JUN-07:02 3663.49 1656.10 3690.21 0.00 0.00 0.00 0.00 0.00 3.22
July 4575.48 07-JUL-07:02 3663.49 1662.28 3690.21 0.00 0.00 0.00 0.00 0.00 11.15
August 4419.34 14-AUG-07:02 3663.49 2086.28 3690.21 0.00 0.00 0.00 0.00 0.00 9.99
September 3554.54 01-SEP-07:03 2930.79 1569.64 2952.17 0.00 0.00 0.00 0.00 0.00 5.81
October 1146.04 25-OCT-07:05 2930.79 1737.52 2952.17 0.00 0.00 0.00 0.00 0.00 0.00
November 1260.65 28-NOV-18:03 322.39 839.23 590.43 0.00 0.00 0.00 0.00 0.00 46.60
December 2084.98 19-DEC-18:01 644.77 1678.45 1180.87 0.00 0.00 0.00 0.00 0.00 58.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1055.10   322.39 459.57 590.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4575.48   3663.49 2086.28 3690.21 0.00 0.00 0.00 0.00 0.00 93.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1110.77 05-JAN-18:01 382.49 995.68 700.51 0.00 0.00 0.00 0.00 0.00 41.15
February 868.72 01-FEB-18:03 191.24 497.84 350.25 0.00 0.00 0.00 0.00 0.00 4.54
March 713.74 20-MAR-05:04 382.49 545.25 1751.27 0.00 0.00 0.00 0.00 0.00 5.98
April 577.22 03-APR-05:04 382.49 545.25 1751.27 0.00 0.00 0.00 0.00 0.00 61.23
May 3789.92 26-MAY-07:03 1738.59 895.12 1751.27 0.00 0.00 0.00 0.00 0.00 2.94
June 3882.05 22-JUN-07:02 2173.23 1120.41 2189.08 0.00 0.00 0.00 0.00 0.00 4.84
July 4315.06 07-JUL-07:02 2173.23 1149.43 2189.08 0.00 0.00 0.00 0.00 0.00 7.74
August 4370.03 07-AUG-07:02 2173.23 1186.83 2189.08 0.00 0.00 0.00 0.00 0.00 13.06
September 3315.94 01-SEP-07:03 1738.59 975.81 1751.27 0.00 0.00 0.00 0.00 0.00 3.94
October 961.88 19-OCT-15:57 1303.94 584.00 1313.45 0.00 0.00 0.00 0.00 0.00 2.29
November 759.12 24-NOV-06:04 382.49 545.25 1751.27 0.00 0.00 0.00 0.00 0.00 76.12
December 995.22 19-DEC-18:01 382.49 995.68 700.51 0.00 0.00 0.00 0.00 0.00 38.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 577.22   191.24 497.84 350.25 0.00 0.00 0.00 0.00 0.00 2.29
Maximum of Months 4370.03   2173.23 1186.83 2189.08 0.00 0.00 0.00 0.00 0.00 76.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 889.38 0.00
February 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1211.69 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 932.54 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 971.52 0.00
May 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1209.95 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 583.27 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 781.94 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 572.55 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 238.58 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 110.95 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1029.51 0.00
December 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 540.52 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 110.95 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1211.69 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.156007E+11 17446.00 19-JAN-08:39 0.362583E+11 44645.66 05-JAN-07:10
February 0.144634E+11 16863.85 09-FEB-08:50 0.205874E+11 44645.66 14-FEB-07:10
March 0.175068E+11 17594.37 27-MAR-07:30 0.119512E+11 44250.68 06-MAR-07:10
April 0.132090E+11 16805.02 10-APR-07:40 0.133425E+10 38241.10 05-APR-06:10
May 0.116115E+11 15532.91 01-MAY-07:10 80990226.12 18282.81 01-MAY-06:10
June 0.118025E+11 14430.29 29-JUN-15:30 0.00 0.00 01-JUN-00:10
July 0.120286E+11 13913.36 24-JUL-14:09 0.00 0.00 01-JUL-00:10
August 0.129350E+11 14177.15 08-AUG-15:39 0.00 0.00 01-AUG-00:10
September 0.109434E+11 13169.25 01-SEP-15:50 0.00 0.00 01-SEP-00:10
October 0.123438E+11 16291.44 30-OCT-07:40 0.218154E+09 22597.71 30-OCT-06:10
November 0.155993E+11 17686.72 27-NOV-16:30 0.332473E+10 40100.96 29-NOV-07:10
December 0.160918E+11 18010.11 05-DEC-08:30 0.277823E+11 44643.55 26-DEC-07:10
             
Annual Sum or Average 0.164136E+12     0.101537E+12    
Minimum of Months 0.109434E+11 13169.25   0.00 0.00  
Maximum of Months 0.175068E+11 18010.11   0.362583E+11 44645.66  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.227483E+10 0.121343E+10 0.405300E+10 0.00 0.281562E+10 0.02 0.305280E+10 0.00 0.00 0.00 0.00 0.219105E+10 0.00
February 0.201683E+10 0.948361E+09 0.366466E+10 0.00 0.224618E+10 0.02 0.359493E+10 0.00 0.00 0.00 0.00 0.199241E+10 0.00
March 0.232620E+10 0.857324E+09 0.429420E+10 0.00 0.225652E+10 0.00 0.551449E+10 0.00 0.00 0.00 0.00 0.225811E+10 0.00
April 0.209064E+10 0.658111E+09 0.388642E+10 0.00 0.162204E+10 0.00 0.284536E+10 4416234.12 0.00 0.00 0.00 0.210199E+10 0.00
May 0.218241E+10 0.555919E+09 0.417360E+10 0.00 0.170283E+10 0.00 0.398284E+09 0.423664E+09 0.00 0.00 0.00 0.217481E+10 0.00
June 0.214520E+10 0.483152E+09 0.412149E+10 0.00 0.170008E+10 0.00 8894362.48 0.125943E+10 0.00 0.00 0.00 0.208427E+10 0.00
July 0.206844E+10 0.522632E+09 0.393546E+10 0.00 0.154571E+10 0.00 0.00 0.189745E+10 0.00 0.00 0.00 0.205885E+10 0.00
August 0.226992E+10 0.618460E+09 0.429420E+10 0.00 0.177735E+10 0.00 0.00 0.185936E+10 0.00 0.00 0.00 0.211567E+10 0.00
September 0.209984E+10 0.747542E+09 0.388029E+10 0.00 0.154552E+10 0.00 38904287.94 0.631390E+09 0.00 0.00 0.00 0.199988E+10 0.00
October 0.223290E+10 0.967310E+09 0.405607E+10 0.00 0.162280E+10 0.00 0.131538E+10 52196150.13 0.00 0.00 0.00 0.209713E+10 0.00
November 0.224373E+10 0.111920E+10 0.400396E+10 0.00 0.185261E+10 0.00 0.430153E+10 385260.46 0.00 0.00 0.00 0.207794E+10 0.00
December 0.223751E+10 0.126190E+10 0.393240E+10 0.00 0.255261E+10 0.00 0.396927E+10 0.00 0.00 0.00 0.00 0.213816E+10 0.00
                           
Annual Sum or Average 0.261884E+11 0.995333E+10 0.482958E+11 0.00 0.232399E+11 0.04 0.250399E+11 0.612829E+10 0.00 0.00 0.00 0.252903E+11 0.00
Minimum of Months 0.201683E+10 0.483152E+09 0.366466E+10 0.00 0.154552E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.199241E+10 0.00
Maximum of Months 0.232620E+10 0.126190E+10 0.429420E+10 0.00 0.281562E+10 0.02 0.551449E+10 0.189745E+10 0.00 0.00 0.00 0.225811E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.362583E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.205874E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.119512E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.133425E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 80990226.12 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.218154E+09 0.00 0.00 0.00 0.00
November 0.00 0.00 0.332473E+10 0.00 0.00 0.00 0.00
December 0.00 0.00 0.277823E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.101537E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.362583E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2025.66 02-JAN-08:09 1049.10 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1651.20 01-JAN-00:20 0.00 02-JAN-08:09 7745.57 19-JAN-08:30
February 1994.78 02-FEB-16:00 1049.10 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1651.20 01-FEB-06:30 0.00 14-FEB-07:10 7618.25 09-FEB-07:30
March 1984.00 03-MAR-16:00 1049.10 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1651.20 01-MAR-06:19 0.00 01-MAR-00:10 8304.44 21-MAR-06:30
April 1933.06 03-APR-07:10 1049.10 01-APR-05:10 3325.31 03-APR-07:10 0.00 1651.20 03-APR-05:19 0.00 01-APR-00:10 7523.86 10-APR-06:00
May 1840.35 19-MAY-08:30 659.04 01-MAY-19:30 3325.31 01-MAY-07:10 0.00 1651.20 01-MAY-05:30 0.00 01-MAY-00:10 6486.31 01-MAY-06:30
June 1929.56 30-JUN-07:10 659.04 01-JUN-19:00 3325.31 01-JUN-07:10 0.00 1651.20 01-JUN-05:10 0.00 01-JUN-00:10 375.36 02-JUN-07:10
July 1863.96 03-JUL-07:10 659.04 01-JUL-20:19 3325.31 03-JUL-07:10 0.00 1651.20 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 1967.98 31-AUG-07:10 1049.10 15-AUG-05:10 3325.31 01-AUG-07:10 0.00 1651.20 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 1970.12 19-SEP-07:10 1049.10 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1651.20 01-SEP-05:10 0.00 01-SEP-00:10 964.18 29-SEP-07:10
October 2022.94 31-OCT-07:10 1049.10 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1651.20 02-OCT-05:10 0.00 01-OCT-00:10 6780.17 30-OCT-07:30
November 2025.66 06-NOV-16:49 1049.10 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1651.20 01-NOV-05:10 0.00 01-NOV-00:10 7599.19 06-NOV-07:30
December 2025.66 01-DEC-16:19 1049.10 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1651.20 01-DEC-06:19 0.00 01-DEC-00:10 8277.81 05-DEC-07:30
                           
Annual Sum or Average             0.00            
Minimum of Months 1840.35   659.04   3325.31   0.00 1651.20   0.00   0.00  
Maximum of Months 2025.66   1049.10   3325.31   0.00 1651.20   0.00   8304.44  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 2846.08 31-JAN-12:20 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 2848.31 24-FEB-12:50 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 2848.24 01-MAR-12:20 0.00
April 275.88 13-APR-15:00 0.00 0.00 0.00 2843.85 03-APR-11:09 0.00
May 3061.92 25-MAY-15:00 0.00 0.00 0.00 2835.76 01-MAY-11:09 0.00
June 5114.42 29-JUN-15:00 0.00 0.00 0.00 2823.80 01-JUN-11:00 0.00
July 4513.38 24-JUL-14:39 0.00 0.00 0.00 2812.68 03-JUL-11:00 0.00
August 4779.34 08-AUG-15:50 0.00 0.00 0.00 2806.06 01-AUG-11:00 0.00
September 3731.37 01-SEP-15:30 0.00 0.00 0.00 2807.47 29-SEP-11:30 0.00
October 1180.41 20-OCT-14:50 0.00 0.00 0.00 2816.57 31-OCT-11:09 0.00
November 64.72 17-NOV-13:30 0.00 0.00 0.00 2827.63 30-NOV-12:39 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 2837.94 29-DEC-12:20 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 0.00   0.00 0.00 0.00 2806.06   0.00
Maximum of Months 5114.42   0.00 0.00 0.00 2848.31   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17446.00 19-JAN-08:39 1970.99 3325.31 0.00 0.00 1651.20 0.00 7743.84 0.00 0.00
February 16863.85 09-FEB-08:50 1892.10 3325.31 0.00 0.00 1651.20 0.00 7238.58 0.00 0.00
March 17594.37 27-MAR-07:30 1738.21 3325.31 0.00 0.00 1651.20 0.00 8124.02 0.00 0.00
April 16805.02 10-APR-07:40 1779.87 3325.31 0.00 0.00 1651.20 0.00 7294.86 0.00 0.00
May 15532.91 01-MAY-07:10 1783.94 3325.31 0.00 0.00 1651.20 0.00 6022.11 0.00 0.00
June 14430.29 29-JUN-15:30 1662.78 3325.31 0.00 0.00 1651.20 0.00 0.00 5022.50 0.00
July 13913.36 24-JUL-14:09 1692.35 3325.31 0.00 0.00 1651.20 0.00 0.00 4508.51 0.00
August 14177.15 08-AUG-15:39 1665.98 3325.31 0.00 0.00 1651.20 0.00 0.00 4772.21 0.00
September 13169.25 01-SEP-15:50 1711.98 3325.31 0.00 0.00 1651.20 0.00 0.00 3719.04 0.00
October 16291.44 30-OCT-07:40 1840.80 3325.31 0.00 0.00 1651.20 0.00 6733.29 0.00 0.00
November 17686.72 27-NOV-16:30 2025.66 3325.31 1049.10 0.00 1651.20 0.00 6857.91 0.00 0.00
December 18010.11 05-DEC-08:30 2009.09 3325.31 0.00 0.00 1651.20 0.00 8277.06 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 13169.25   1662.78 3325.31 0.00 0.00 1651.20 0.00 0.00 0.00 0.00
Maximum of Months 18010.11   2025.66 3325.31 1049.10 0.00 1651.20 0.00 8277.06 5022.50 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 44645.66 05-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 44645.66 14-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 44250.68 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 38241.10 05-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 18282.81 01-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 22597.71 30-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 40100.96 29-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 44643.55 26-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 44645.66   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.00 19.20 15.00 19.20 0.00 19.20 0.00 19.20
February 6.33 19.44 6.33 19.44 0.00 19.44 0.00 19.44
March 2.67 19.31 2.67 19.31 0.00 19.31 0.00 19.31
April 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.17 24.63 1.17 24.63
July 0.00 0.00 0.00 0.00 2.00 24.65 2.00 24.65
August 0.00 0.00 0.00 0.00 1.33 24.52 1.33 24.52
September 0.00 0.00 0.00 0.00 0.17 24.53 0.17 24.53
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.31 0.17 19.31 0.00 19.31 0.00 19.31
December 9.83 19.19 9.83 19.19 0.00 19.19 0.00 19.19
                 
Annual Sum or Average 34.17 19.25 34.17 19.25 4.67 19.59 4.67 19.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15.00 19.44 15.00 19.44 2.00 24.65 2.00 24.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 120.33 16.23 59.33 16.77 0.00 16.77 0.00 16.77
February 57.67 16.52 31.50 17.04 0.00 17.04 0.00 17.04
March 30.50 16.54 17.00 17.09 0.00 17.09 0.00 17.09
April 4.00 17.88 3.00 18.30 0.00 18.30 0.00 18.30
May 0.33 19.31 0.33 19.31 0.00 19.31 0.00 19.31
June 0.00 0.00 0.00 0.00 0.17 24.45 0.17 24.45
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 19.27 0.50 19.27 0.00 19.27 0.00 19.27
November 13.17 16.22 4.67 16.87 0.00 16.87 0.00 16.87
December 81.33 16.39 41.67 16.97 0.00 16.97 0.00 16.97
                 
Annual Sum or Average 307.83 16.39 158.00 16.94 0.17 16.95 0.17 16.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 120.33 19.31 59.33 19.31 0.17 24.45 0.17 24.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 98.50 14.86 12.83 15.15 0.00 15.15 0.00 15.15
February 59.00 14.86 4.33 15.06 0.00 15.06 0.00 15.06
March 33.83 14.77 1.33 14.89 0.00 14.89 0.00 14.89
April 6.83 14.85 0.00 14.85 0.00 14.85 0.00 14.85
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 24.56 0.17 24.56
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 17.00 14.81 0.00 14.81 0.00 14.81 0.00 14.81
December 71.67 14.72 6.00 14.93 0.00 14.93 0.00 14.93
                 
Annual Sum or Average 286.83 14.81 24.50 15.02 0.17 15.03 0.17 15.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 98.50 14.86 12.83 15.15 0.17 24.56 0.17 24.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 103.50 15.21 18.00 15.68 0.00 15.68 0.00 15.68
February 66.67 15.22 9.17 15.65 0.00 15.65 0.00 15.65
March 40.50 15.20 5.00 15.63 0.00 15.63 0.00 15.63
April 6.83 15.11 0.33 15.31 0.00 15.31 0.00 15.31
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 19.41 0.17 19.41 0.00 19.41 0.00 19.41
November 14.67 14.95 0.33 15.04 0.00 15.04 0.00 15.04
December 71.83 15.00 9.33 15.40 0.00 15.40 0.00 15.40
                 
Annual Sum or Average 304.17 15.15 42.33 15.57 0.00 15.57 0.00 15.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 103.50 19.41 18.00 19.41 0.00 19.41 0.00 19.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 97.67 14.88 12.17 15.19 0.00 15.19 0.00 15.19
February 58.17 14.86 3.83 15.07 0.00 15.07 0.00 15.07
March 32.33 14.81 1.50 14.98 0.00 14.98 0.00 14.98
April 5.50 14.89 0.00 14.89 0.00 14.89 0.00 14.89
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 15.67 14.80 0.00 14.80 0.00 14.80 0.00 14.80
December 71.50 14.69 4.83 14.87 0.00 14.87 0.00 14.87
                 
Annual Sum or Average 280.83 14.82 22.33 15.04 0.00 15.04 0.00 15.04
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 97.67 14.89 12.17 15.19 0.00 15.19 0.00 15.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.22 357.00 20.22 357.00 20.22
February 323.00 20.34 323.00 20.34 323.00 20.34
March 391.00 20.47 364.33 20.45 364.33 20.44
April 340.00 21.14 170.33 20.91 170.33 20.80
May 270.00 22.80 86.33 22.97 28.33 22.83
June 147.83 24.42 203.67 24.62 64.33 24.73
July 60.33 25.90 333.17 24.95 60.33 25.08
August 78.67 25.80 368.50 24.90 78.67 25.04
September 152.33 23.71 111.33 24.18 13.33 24.20
October 357.00 22.01 59.17 21.76 59.17 21.58
November 357.00 20.67 257.33 20.57 257.33 20.53
December 340.00 20.30 340.00 20.30 340.00 20.30
             
Annual Sum or Average 3174.17 21.45 2974.17 21.69 2116.17 21.49
Minimum of Months 60.33 20.22 59.17 20.22 13.33 20.22
Maximum of Months 391.00 25.90 368.50 24.95 364.33 25.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 19.19 357.00 19.19 357.00 19.19
February 323.00 19.61 311.17 19.56 311.17 19.55
March 391.00 19.92 375.50 19.88 375.50 19.87
April 340.00 20.77 258.17 20.53 258.17 20.43
May 302.33 21.93 125.83 21.81 91.83 21.54
June 260.00 23.47 138.50 23.80 79.50 23.89
July 77.67 24.72 262.50 24.76 51.17 24.86
August 105.33 24.64 300.33 24.70 55.33 24.85
September 195.50 22.56 109.83 23.26 18.17 23.26
October 332.33 21.27 167.67 20.97 163.67 20.80
November 357.00 20.27 305.83 20.15 305.83 20.11
December 340.00 19.40 340.00 19.40 340.00 19.40
             
Annual Sum or Average 3381.17 20.88 3052.33 20.99 2407.33 20.77
Minimum of Months 77.67 19.19 109.83 19.19 18.17 19.19
Maximum of Months 391.00 24.72 375.50 24.76 375.50 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 19.19 294.00 19.19 294.00 19.19
February 266.00 19.32 266.00 19.32 266.00 19.32
March 322.00 19.49 322.00 19.49 322.00 19.49
April 280.00 20.24 243.67 20.09 243.67 20.04
May 249.00 21.99 91.33 21.76 72.67 21.46
June 139.50 23.71 129.83 24.26 35.67 24.33
July 26.50 25.48 249.83 24.99 21.83 25.06
August 50.67 24.26 238.00 24.77 15.00 24.82
September 185.50 22.83 43.83 23.12 12.50 23.10
October 294.00 20.88 181.67 20.59 181.67 20.46
November 294.00 19.81 283.00 19.78 283.00 19.77
December 280.00 19.30 280.00 19.30 280.00 19.30
             
Annual Sum or Average 2681.17 20.52 2623.17 20.73 2028.00 20.47
Minimum of Months 26.50 19.19 43.83 19.19 12.50 19.19
Maximum of Months 322.00 25.48 322.00 24.99 322.00 25.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 19.51 357.00 19.51 357.00 19.51
February 323.00 19.61 323.00 19.61 323.00 19.61
March 391.00 19.76 391.00 19.76 391.00 19.76
April 340.00 20.15 331.83 20.13 331.83 20.12
May 339.17 21.84 130.67 21.54 118.17 21.30
June 264.67 23.54 120.00 23.85 58.00 23.92
July 56.33 24.69 218.00 24.80 33.17 24.87
August 96.83 24.17 220.50 24.53 34.00 24.59
September 293.33 22.86 37.17 22.94 19.50 22.93
October 357.00 20.71 250.33 20.53 250.33 20.45
November 357.00 20.03 340.83 20.00 340.83 19.99
December 340.00 19.62 340.00 19.62 340.00 19.62
             
Annual Sum or Average 3515.33 20.81 3060.33 20.80 2596.83 20.61
Minimum of Months 56.33 19.51 37.17 19.51 19.50 19.51
Maximum of Months 391.00 24.69 391.00 24.80 391.00 24.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 19.54 357.00 19.54 357.00 19.54
February 323.00 19.68 323.00 19.68 323.00 19.68
March 391.00 19.93 384.83 19.91 384.83 19.91
April 340.00 20.76 272.33 20.56 272.33 20.48
May 292.33 22.41 127.67 22.53 78.50 22.31
June 210.67 24.08 159.50 24.63 52.17 24.81
July 72.33 27.20 255.83 25.83 62.00 26.14
August 85.00 25.67 275.00 25.28 43.17 25.53
September 224.67 23.20 70.83 23.72 9.33 23.78
October 353.50 21.26 185.83 20.94 184.83 20.78
November 357.00 20.07 337.17 20.03 337.17 20.02
December 340.00 19.63 340.00 19.63 340.00 19.63
             
Annual Sum or Average 3346.50 21.07 3089.00 21.20 2444.33 20.98
Minimum of Months 72.33 19.54 70.83 19.54 9.33 19.54
Maximum of Months 391.00 27.20 384.83 25.83 384.83 26.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 0.657192E+09 0.133251E+09 113.63 0.529803E+09 0.127390E+09 0.00 1.00 25-MAY-07:03 0.00 01-MAY-00:05 5500.70 26-MAY-07:03 4029.71 18-MAY-07:02 1598.85 26-MAY-07:13 972.49 26-MAY-07:03 0.00
June 0.190731E+10 0.376221E+09 208.90 0.144163E+10 0.465681E+09 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 5833.31 30-JUN-06:02 4737.68 07-JUN-07:02 2416.53 23-JUN-07:05 1161.65 29-JUN-16:00 0.00
July 0.269756E+10 0.515904E+09 206.67 0.205070E+10 0.646854E+09 0.00 1.00 03-JUL-06:03 0.00 01-JUL-00:10 5798.02 05-JUL-06:03 4487.36 24-JUL-15:05 2622.40 05-JUL-06:03 1066.56 24-JUL-14:00 0.00
August 0.277324E+10 0.527914E+09 232.12 0.205115E+10 0.722089E+09 0.00 1.00 01-AUG-07:03 0.00 01-AUG-00:10 5654.54 30-AUG-07:02 4260.00 02-AUG-07:03 2327.38 30-AUG-07:08 1074.37 08-AUG-15:00 0.00
September 0.102718E+10 0.201191E+09 169.13 0.843816E+09 0.183364E+09 0.00 1.00 01-SEP-07:03 0.00 01-SEP-00:10 5596.10 01-SEP-07:03 4603.70 11-SEP-07:03 2273.66 19-SEP-07:03 982.59 01-SEP-07:03 0.00
October 36558497.41 7525515.03 22.39 31644137.74 4914359.67 0.00 0.23 20-OCT-15:03 0.00 01-OCT-00:10 1044.69 20-OCT-15:03 993.06 20-OCT-15:03 135.99 02-OCT-15:55 211.90 20-OCT-15:03 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.909904E+10 0.176201E+10 952.84 0.694875E+10 0.215029E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.277324E+10 0.527914E+09 232.12 0.205115E+10 0.722089E+09 0.00 1.00   0.00   5833.31   4737.68   2622.40   1161.65   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 20703335.61 4240705.68 11.17 20703335.61 -0.0 0.00 0.21 13-APR-14:55 0.00 01-APR-00:10 1106.75 13-APR-14:55 1106.75 13-APR-14:55 0.00 18-APR-15:00 224.08 13-APR-14:55 0.00
May 0.501408E+09 0.104865E+09 83.10 0.441796E+09 59612020.13 0.00 0.64 25-MAY-14:30 0.00 01-MAY-00:05 3818.40 25-MAY-14:20 3410.68 18-MAY-14:10 855.14 26-MAY-12:00 808.00 25-MAY-15:00 0.00
June 0.132281E+10 0.271402E+09 159.77 0.105061E+10 0.272200E+09 0.00 1.00 28-JUN-07:01 0.00 01-JUN-00:10 7063.73 30-JUN-06:02 4905.24 30-JUN-14:20 2972.30 30-JUN-06:02 1342.00 30-JUN-12:05 0.00
July 0.217873E+10 0.433846E+09 192.13 0.174715E+10 0.431581E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 6945.68 05-JUL-07:02 5306.48 24-JUL-13:40 3198.96 05-JUL-07:02 1263.18 24-JUL-11:55 0.00
August 0.235326E+10 0.460659E+09 213.52 0.186908E+10 0.484172E+09 0.00 1.00 08-AUG-11:45 0.00 01-AUG-00:10 6803.27 30-AUG-07:02 5110.27 08-AUG-14:20 2750.91 30-AUG-07:02 1311.60 08-AUG-15:10 0.00
September 0.953694E+09 0.184966E+09 114.54 0.888242E+09 65452256.71 0.00 1.00 01-SEP-13:20 0.00 01-SEP-00:10 6353.19 01-SEP-13:20 5686.81 01-SEP-14:40 1093.79 01-SEP-07:05 1209.42 01-SEP-14:35 0.00
October 0.183776E+09 36256889.56 34.23 0.181984E+09 1791443.62 0.00 0.62 20-OCT-14:00 0.00 01-OCT-00:10 3575.43 20-OCT-14:00 3575.43 20-OCT-14:00 102.17 19-OCT-13:50 680.26 20-OCT-14:00 0.00
November 1857079.72 385260.46 2.42 1857079.72 0.00 0.00 0.06 17-NOV-13:30 0.00 01-NOV-00:10 312.64 17-NOV-13:30 312.64 17-NOV-13:30 0.00 17-NOV-15:35 64.72 17-NOV-13:30 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.751623E+10 0.149662E+10 810.87 0.620143E+10 0.131481E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.235326E+10 0.460659E+09 213.52 0.186908E+10 0.484172E+09 0.00 1.00   0.00   7063.73   5686.81   3198.96   1342.00   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 0.299682E+09 62938716.53 88.11 0.269813E+09 29869138.39 0.00 0.84 18-MAY-07:02 0.00 01-MAY-00:05 3516.95 18-MAY-07:02 3308.04 18-MAY-07:02 725.12 26-MAY-07:03 645.59 18-MAY-07:02 0.00
June 0.104861E+10 0.215127E+09 199.35 0.896334E+09 0.152271E+09 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 4790.43 30-JUN-06:02 4289.54 07-JUN-07:02 1970.71 30-JUN-06:02 862.65 30-JUN-06:02 0.00
July 0.159830E+10 0.317504E+09 208.86 0.136583E+10 0.232472E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 4718.95 05-JUL-07:02 3989.28 27-JUL-07:02 1965.47 05-JUL-07:12 817.25 05-JUL-07:02 0.00
August 0.137405E+10 0.273417E+09 226.53 0.114036E+10 0.233683E+09 0.00 1.00 01-AUG-07:03 0.00 01-AUG-00:10 4637.11 30-AUG-07:02 3997.56 02-AUG-07:03 1617.76 30-AUG-07:04 811.16 30-AUG-07:02 0.00
September 0.445732E+09 89244718.18 122.54 0.414282E+09 31449695.63 0.00 1.00 01-SEP-07:03 0.00 01-SEP-00:10 4602.02 01-SEP-07:03 3119.36 05-SEP-07:02 1536.10 01-SEP-07:03 807.98 01-SEP-07:03 0.00
October 15240320.90 3151784.37 11.01 15088727.62 151593.28 0.00 0.17 20-OCT-14:55 0.00 01-OCT-00:10 605.02 20-OCT-14:55 605.02 20-OCT-14:55 23.40 19-OCT-16:00 123.87 20-OCT-14:55 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.478161E+10 0.961382E+09 856.41 0.410171E+10 0.679896E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.159830E+10 0.317504E+09 226.53 0.136583E+10 0.233683E+09 0.00 1.00   0.00   4790.43   4289.54   1970.71   862.65   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 0.245880E+09 51934661.82 56.93 0.204892E+09 40987756.63 0.00 0.51 26-MAY-07:03 0.00 01-MAY-00:05 2564.69 26-MAY-07:03 2009.85 25-MAY-16:00 627.02 26-MAY-07:03 530.73 25-MAY-15:55 0.00
June 0.100868E+10 0.207847E+09 159.80 0.789990E+09 0.218687E+09 0.00 1.00 27-JUN-07:02 0.00 01-JUN-00:10 5854.06 30-JUN-06:02 4019.63 27-JUN-07:02 2440.21 30-JUN-06:02 1054.42 30-JUN-06:02 0.00
July 0.168445E+10 0.337504E+09 196.78 0.133784E+10 0.346605E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5780.40 05-JUL-07:02 4571.76 07-JUL-07:02 2586.14 05-JUL-07:06 999.68 05-JUL-07:02 0.00
August 0.157663E+10 0.314451E+09 220.20 0.121729E+10 0.359336E+09 0.00 1.00 01-AUG-07:03 0.00 01-AUG-00:10 5670.58 09-AUG-07:02 4354.22 14-AUG-07:02 2191.76 30-AUG-07:04 991.71 09-AUG-07:02 0.00
September 0.343792E+09 69555545.99 88.63 0.296780E+09 47011197.54 0.00 1.00 01-SEP-07:03 0.00 01-SEP-00:10 5586.71 01-SEP-07:03 3534.69 01-SEP-07:03 2052.01 01-SEP-07:03 983.78 01-SEP-07:03 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.485942E+10 0.981292E+09 722.34 0.384680E+10 0.101263E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.168445E+10 0.337504E+09 220.20 0.133784E+10 0.359336E+09 0.00 1.00   0.00   5854.06   4571.76   2586.14   1054.42   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 847696.98 175528.44 1.00 847696.98 -0.0 0.00 0.10 13-APR-15:53 0.00 01-APR-00:10 412.33 13-APR-16:00 412.33 13-APR-16:00 0.00 13-APR-16:00 85.06 13-APR-16:00 0.00
May 0.334252E+09 70674309.52 86.26 0.295231E+09 39020698.68 0.00 1.00 26-MAY-07:03 0.00 01-MAY-00:05 5329.68 26-MAY-07:03 4335.73 26-MAY-07:03 993.95 26-MAY-07:03 945.00 26-MAY-07:03 0.00
June 0.901013E+09 0.188833E+09 184.32 0.738877E+09 0.162136E+09 0.00 1.00 22-JUN-07:02 0.00 01-JUN-00:10 5706.22 30-JUN-06:02 4309.27 22-JUN-07:02 2151.14 30-JUN-06:02 1025.97 30-JUN-06:02 0.00
July 0.143678E+10 0.292692E+09 207.08 0.119121E+10 0.245572E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5587.60 05-JUL-07:02 4694.67 07-JUL-07:02 2188.14 05-JUL-07:04 970.35 05-JUL-07:02 0.00
August 0.140167E+10 0.282923E+09 229.89 0.114198E+10 0.259688E+09 0.00 1.00 01-AUG-07:03 0.00 01-AUG-00:10 5500.88 30-AUG-07:02 4676.33 07-AUG-07:02 1760.81 30-AUG-07:02 963.50 30-AUG-07:02 0.00
September 0.426670E+09 86432453.81 123.26 0.386502E+09 40167939.06 0.00 1.00 01-SEP-07:03 0.00 01-SEP-00:10 5469.45 01-SEP-07:03 3673.45 01-SEP-07:03 1796.01 01-SEP-07:03 960.59 01-SEP-07:03 0.00
October 25611084.33 5261961.17 13.50 25083496.32 527588.01 0.00 0.29 19-OCT-15:53 0.00 01-OCT-00:10 1305.64 19-OCT-15:53 1232.08 19-OCT-15:57 73.61 19-OCT-15:53 264.64 19-OCT-15:53 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.452684E+10 0.926992E+09 845.32 0.377973E+10 0.747113E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.143678E+10 0.292692E+09 229.89 0.119121E+10 0.259688E+09 0.00 1.00   0.00   5706.22   4694.67   2188.14   1025.97   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.20 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.64 47.64 41.99 101.29 38.33 0.00 0.00 0.00
May 66.74 18.42 48.32 79.01 21.75 0.00 0.00 0.00
June 57.02 9.70 47.32 70.39 15.68 0.00 0.00 0.00
July 62.97 14.51 48.46 79.51 17.07 0.00 0.00 0.00
August 74.58 28.82 45.76 93.25 20.96 0.00 0.00 0.00
September 90.55 49.11 41.44 107.80 31.76 0.00 0.00 0.00
October 77.90 46.73 31.18 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.21 43.82 38.39 88.81 46.75 0.00 0.00 0.00
Minimum of Months 57.02 9.70 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.20 83.45 48.46 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.19 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.51 47.58 41.93 101.09 38.38 0.00 0.00 0.00
May 66.64 18.38 48.27 78.82 21.75 0.00 0.00 0.00
June 56.99 9.69 47.30 70.33 15.68 0.00 0.00 0.00
July 62.91 14.49 48.42 79.39 17.07 0.00 0.00 0.00
August 74.45 28.76 45.69 93.00 20.96 0.00 0.00 0.00
September 90.50 49.09 41.41 107.73 31.78 0.00 0.00 0.00
October 77.90 46.73 31.17 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.17 43.80 38.36 88.73 46.76 0.00 0.00 0.00
Minimum of Months 56.99 9.69 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.19 83.45 48.42 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.19 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.51 47.58 41.93 101.09 38.38 0.00 0.00 0.00
May 66.64 18.38 48.27 78.82 21.75 0.00 0.00 0.00
June 56.99 9.69 47.30 70.33 15.68 0.00 0.00 0.00
July 62.91 14.49 48.42 79.39 17.07 0.00 0.00 0.00
August 74.45 28.76 45.69 93.00 20.96 0.00 0.00 0.00
September 90.49 49.09 41.41 107.73 31.79 0.00 0.00 0.00
October 77.90 46.73 31.17 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.16 43.80 38.36 88.73 46.76 0.00 0.00 0.00
Minimum of Months 56.99 9.69 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.19 83.45 48.42 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.19 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.51 47.58 41.93 101.09 38.38 0.00 0.00 0.00
May 66.64 18.38 48.27 78.82 21.75 0.00 0.00 0.00
June 56.99 9.69 47.30 70.33 15.68 0.00 0.00 0.00
July 62.91 14.49 48.42 79.39 17.07 0.00 0.00 0.00
August 74.45 28.76 45.69 93.00 20.96 0.00 0.00 0.00
September 90.49 49.09 41.41 107.73 31.79 0.00 0.00 0.00
October 77.90 46.73 31.17 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.16 43.80 38.36 88.73 46.76 0.00 0.00 0.00
Minimum of Months 56.99 9.69 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.19 83.45 48.42 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.19 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.51 47.58 41.93 101.09 38.37 0.00 0.00 0.00
May 66.64 18.38 48.27 78.82 21.75 0.00 0.00 0.00
June 56.99 9.69 47.30 70.33 15.68 0.00 0.00 0.00
July 62.91 14.49 48.42 79.39 17.07 0.00 0.00 0.00
August 74.45 28.76 45.69 93.00 20.96 0.00 0.00 0.00
September 90.50 49.09 41.41 107.73 31.78 0.00 0.00 0.00
October 77.90 46.73 31.17 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.17 43.80 38.36 88.73 46.76 0.00 0.00 0.00
Minimum of Months 56.99 9.69 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.19 83.45 48.42 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.59 67.88 28.72 87.09 91.51 0.00 0.00 0.00
February 122.20 83.45 38.75 124.30 75.70 0.00 0.00 0.00
March 107.29 68.85 38.44 112.65 60.94 0.00 0.00 0.00
April 89.65 47.65 41.99 101.22 38.24 0.00 0.00 0.00
May 66.74 18.42 48.33 79.00 21.75 0.00 0.00 0.00
June 57.03 9.70 47.32 70.40 15.68 0.00 0.00 0.00
July 62.97 14.52 48.46 79.51 17.07 0.00 0.00 0.00
August 74.58 28.81 45.76 93.24 20.96 0.00 0.00 0.00
September 90.54 49.10 41.44 107.76 31.74 0.00 0.00 0.00
October 77.90 46.73 31.18 83.83 42.24 0.00 0.00 0.00
November 69.73 44.42 25.31 67.46 57.76 0.00 0.00 0.00
December 74.44 49.40 25.04 62.30 88.72 0.00 0.00 0.00
                 
Annual Sum or Average 82.21 43.82 38.38 88.80 46.74 0.00 0.00 0.00
Minimum of Months 57.03 9.70 25.04 62.30 15.68 0.00 0.00 0.00
Maximum of Months 122.20 83.45 48.46 124.30 91.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.98 95.10 40.89 122.90 127.37 0.00 0.00 0.00
February 172.10 116.91 55.19 175.32 105.44 0.00 0.00 0.00
March 151.35 96.46 54.88 158.88 84.72 0.00 0.00 0.00
April 136.12 74.49 61.64 156.98 53.36 0.00 0.00 0.00
May 107.53 34.99 72.55 131.67 30.48 0.00 0.00 0.00
June 92.42 21.16 71.25 117.81 22.01 0.00 0.00 0.00
July 102.53 29.50 73.03 133.17 23.99 0.00 0.00 0.00
August 117.70 49.30 68.40 149.91 29.35 0.00 0.00 0.00
September 128.87 69.34 59.53 153.64 44.34 0.00 0.00 0.00
October 110.19 65.46 44.73 118.67 58.96 0.00 0.00 0.00
November 98.40 62.24 36.17 95.33 80.49 0.00 0.00 0.00
December 104.89 69.21 35.69 87.99 123.36 0.00 0.00 0.00
                 
Annual Sum or Average 121.17 65.02 56.16 133.21 65.16 0.00 0.00 0.00
Minimum of Months 92.42 21.16 35.69 87.99 22.01 0.00 0.00 0.00
Maximum of Months 172.10 116.91 73.03 175.32 127.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.75 12.78 16.96 12.79 104.02 0.00 0.00 0.00
February 46.63 20.32 26.31 30.33 79.90 0.00 0.00 0.00
March 63.51 32.35 31.16 52.46 60.28 0.00 0.00 0.00
April 87.49 47.54 39.95 91.84 34.25 0.00 0.00 0.00
May 93.54 41.38 52.15 109.64 19.77 0.00 0.00 0.00
June 106.11 51.01 55.10 132.03 15.14 0.00 0.00 0.00
July 104.23 49.17 55.05 130.63 16.14 0.00 0.00 0.00
August 80.34 35.43 44.91 96.39 19.46 0.00 0.00 0.00
September 64.71 29.43 35.28 69.44 29.02 0.00 0.00 0.00
October 39.17 15.28 23.90 32.77 39.98 0.00 0.00 0.00
November 24.99 8.65 16.34 13.46 59.87 0.00 0.00 0.00
December 22.93 8.78 14.15 8.09 100.83 0.00 0.00 0.00
                 
Annual Sum or Average 63.68 29.37 34.31 65.15 48.11 0.00 0.00 0.00
Minimum of Months 22.93 8.65 14.15 8.09 15.14 0.00 0.00 0.00
Maximum of Months 106.11 51.01 55.10 132.03 104.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.75 12.78 16.96 12.78 104.02 0.00 0.00 0.00
February 46.63 20.32 26.31 30.32 79.90 0.00 0.00 0.00
March 63.51 32.35 31.15 52.45 60.28 0.00 0.00 0.00
April 87.49 47.54 39.95 91.84 34.25 0.00 0.00 0.00
May 93.53 41.38 52.15 109.63 19.77 0.00 0.00 0.00
June 106.10 51.01 55.10 132.03 15.14 0.00 0.00 0.00
July 104.23 49.17 55.05 130.63 16.14 0.00 0.00 0.00
August 80.33 35.43 44.91 96.39 19.46 0.00 0.00 0.00
September 64.71 29.43 35.27 69.44 29.02 0.00 0.00 0.00
October 39.17 15.28 23.89 32.77 39.98 0.00 0.00 0.00
November 24.99 8.65 16.34 13.46 59.87 0.00 0.00 0.00
December 22.93 8.78 14.14 8.09 100.83 0.00 0.00 0.00
                 
Annual Sum or Average 63.67 29.37 34.31 65.14 48.11 0.00 0.00 0.00
Minimum of Months 22.93 8.65 14.14 8.09 15.14 0.00 0.00 0.00
Maximum of Months 106.10 51.01 55.10 132.03 104.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.75 12.78 16.96 12.78 104.02 0.00 0.00 0.00
February 46.63 20.32 26.31 30.32 79.90 0.00 0.00 0.00
March 63.51 32.35 31.15 52.45 60.28 0.00 0.00 0.00
April 87.49 47.54 39.95 91.84 34.25 0.00 0.00 0.00
May 93.53 41.38 52.15 109.63 19.77 0.00 0.00 0.00
June 106.10 51.01 55.10 132.03 15.14 0.00 0.00 0.00
July 104.23 49.17 55.05 130.63 16.14 0.00 0.00 0.00
August 80.33 35.43 44.91 96.39 19.46 0.00 0.00 0.00
September 64.71 29.43 35.27 69.44 29.02 0.00 0.00 0.00
October 39.17 15.28 23.89 32.77 39.98 0.00 0.00 0.00
November 24.99 8.65 16.34 13.46 59.87 0.00 0.00 0.00
December 22.93 8.78 14.14 8.09 100.83 0.00 0.00 0.00
                 
Annual Sum or Average 63.67 29.37 34.31 65.14 48.11 0.00 0.00 0.00
Minimum of Months 22.93 8.65 14.14 8.09 15.14 0.00 0.00 0.00
Maximum of Months 106.10 51.01 55.10 132.03 104.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.87 12.83 17.04 12.82 103.82 0.00 0.00 0.00
February 46.75 20.37 26.38 30.46 79.82 0.00 0.00 0.00
March 63.53 32.36 31.17 52.49 60.27 0.00 0.00 0.00
April 87.49 47.54 39.95 91.84 34.25 0.00 0.00 0.00
May 93.54 41.38 52.15 109.64 19.77 0.00 0.00 0.00
June 106.11 51.01 55.10 132.03 15.14 0.00 0.00 0.00
July 104.23 49.17 55.05 130.63 16.14 0.00 0.00 0.00
August 80.34 35.43 44.91 96.39 19.46 0.00 0.00 0.00
September 64.71 29.43 35.28 69.45 29.02 0.00 0.00 0.00
October 39.21 15.29 23.92 32.84 39.98 0.00 0.00 0.00
November 25.07 8.68 16.39 13.55 59.81 0.00 0.00 0.00
December 23.03 8.82 14.21 8.11 100.66 0.00 0.00 0.00
                 
Annual Sum or Average 63.72 29.38 34.34 65.18 48.07 0.00 0.00 0.00
Minimum of Months 23.03 8.68 14.21 8.11 15.14 0.00 0.00 0.00
Maximum of Months 106.11 51.01 55.10 132.03 103.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.27 0.00 25.27 6.13 65.91 0.00 0.00 0.00
April 33.28 0.26 33.02 21.80 35.52 0.00 0.00 0.00
May 46.48 2.51 43.97 48.60 18.94 0.00 0.00 0.00
June 52.02 5.74 46.28 61.86 14.22 0.00 0.00 0.00
July 49.81 4.26 45.55 59.29 15.31 0.00 0.00 0.00
August 37.75 0.65 37.10 40.54 18.60 0.00 0.00 0.00
September 29.26 0.01 29.25 23.81 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.29 0.00 13.29 1.49 64.66 0.00 0.00 0.00
December 11.13 0.00 11.13 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.38 1.12 28.25 23.08 51.41 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 0.03 14.22 0.00 0.00 0.00
Maximum of Months 52.02 5.74 46.28 61.86 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.26 0.00 25.26 6.13 65.91 0.00 0.00 0.00
April 33.26 0.26 33.00 21.79 35.55 0.00 0.00 0.00
May 46.37 2.47 43.90 48.41 18.96 0.00 0.00 0.00
June 51.87 5.67 46.20 61.59 14.22 0.00 0.00 0.00
July 49.66 4.20 45.45 59.00 15.31 0.00 0.00 0.00
August 37.68 0.63 37.06 40.41 18.60 0.00 0.00 0.00
September 29.26 0.01 29.25 23.80 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.28 0.00 13.28 1.49 64.66 0.00 0.00 0.00
December 11.12 0.00 11.12 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.33 1.11 28.23 23.00 51.42 0.00 0.00 0.00
Minimum of Months 11.12 0.00 11.12 0.03 14.22 0.00 0.00 0.00
Maximum of Months 51.87 5.67 46.20 61.59 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.26 0.00 25.26 6.13 65.91 0.00 0.00 0.00
April 33.25 0.25 32.99 21.79 35.56 0.00 0.00 0.00
May 46.37 2.47 43.90 48.41 18.96 0.00 0.00 0.00
June 51.87 5.67 46.20 61.59 14.22 0.00 0.00 0.00
July 49.66 4.20 45.45 59.00 15.31 0.00 0.00 0.00
August 37.68 0.62 37.06 40.41 18.60 0.00 0.00 0.00
September 29.25 0.01 29.25 23.80 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.28 0.00 13.28 1.49 64.66 0.00 0.00 0.00
December 11.12 0.00 11.12 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.33 1.11 28.23 23.00 51.42 0.00 0.00 0.00
Minimum of Months 11.12 0.00 11.12 0.03 14.22 0.00 0.00 0.00
Maximum of Months 51.87 5.67 46.20 61.59 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.26 0.00 25.26 6.13 65.91 0.00 0.00 0.00
April 33.25 0.25 32.99 21.79 35.56 0.00 0.00 0.00
May 46.37 2.47 43.90 48.41 18.96 0.00 0.00 0.00
June 51.87 5.67 46.20 61.59 14.22 0.00 0.00 0.00
July 49.66 4.20 45.45 59.00 15.31 0.00 0.00 0.00
August 37.68 0.62 37.06 40.41 18.60 0.00 0.00 0.00
September 29.25 0.01 29.25 23.81 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.28 0.00 13.28 1.49 64.66 0.00 0.00 0.00
December 11.12 0.00 11.12 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.33 1.11 28.23 23.00 51.42 0.00 0.00 0.00
Minimum of Months 11.12 0.00 11.12 0.03 14.22 0.00 0.00 0.00
Maximum of Months 51.87 5.67 46.20 61.59 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.26 0.00 25.26 6.13 65.91 0.00 0.00 0.00
April 33.25 0.26 33.00 21.80 35.56 0.00 0.00 0.00
May 46.37 2.47 43.90 48.41 18.96 0.00 0.00 0.00
June 51.87 5.67 46.20 61.59 14.22 0.00 0.00 0.00
July 49.66 4.20 45.45 59.00 15.31 0.00 0.00 0.00
August 37.68 0.63 37.06 40.41 18.60 0.00 0.00 0.00
September 29.26 0.01 29.25 23.81 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.28 0.00 13.28 1.49 64.66 0.00 0.00 0.00
December 11.12 0.00 11.12 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.33 1.11 28.23 23.01 51.42 0.00 0.00 0.00
Minimum of Months 11.12 0.00 11.12 0.03 14.22 0.00 0.00 0.00
Maximum of Months 51.87 5.67 46.20 61.59 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.21 0.00 13.21 0.20 115.60 0.00 0.00 0.00
February 20.43 0.00 20.43 2.44 88.96 0.00 0.00 0.00
March 25.27 0.00 25.27 6.13 65.91 0.00 0.00 0.00
April 33.28 0.26 33.02 21.82 35.54 0.00 0.00 0.00
May 46.48 2.52 43.96 48.63 18.96 0.00 0.00 0.00
June 51.99 5.72 46.27 61.80 14.22 0.00 0.00 0.00
July 49.79 4.26 45.53 59.24 15.31 0.00 0.00 0.00
August 37.75 0.65 37.11 40.54 18.60 0.00 0.00 0.00
September 29.26 0.01 29.25 23.81 29.19 0.00 0.00 0.00
October 20.09 0.00 20.09 9.30 41.31 0.00 0.00 0.00
November 13.29 0.00 13.29 1.49 64.66 0.00 0.00 0.00
December 11.13 0.00 11.13 0.03 110.38 0.00 0.00 0.00
                 
Annual Sum or Average 29.37 1.12 28.25 23.08 51.42 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 0.03 14.22 0.00 0.00 0.00
Maximum of Months 51.99 5.72 46.27 61.80 115.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.22 13.03 17.19 14.40 106.11 0.00 0.00 0.00
February 49.10 22.93 26.17 35.60 82.98 0.00 0.00 0.00
March 64.30 33.45 30.85 55.50 63.01 0.00 0.00 0.00
April 81.50 41.60 39.90 85.29 36.85 0.00 0.00 0.00
May 99.55 47.95 51.61 118.74 22.08 0.00 0.00 0.00
June 95.76 41.66 54.10 119.22 16.28 0.00 0.00 0.00
July 101.96 47.46 54.51 127.87 17.92 0.00 0.00 0.00
August 84.17 38.47 45.69 102.26 21.03 0.00 0.00 0.00
September 66.38 30.33 36.05 72.41 30.76 0.00 0.00 0.00
October 41.97 17.30 24.66 37.45 41.68 0.00 0.00 0.00
November 25.58 8.93 16.65 14.89 61.28 0.00 0.00 0.00
December 22.95 8.32 14.63 8.34 102.24 0.00 0.00 0.00
                 
Annual Sum or Average 63.70 29.32 34.38 66.17 50.07 0.00 0.00 0.00
Minimum of Months 22.95 8.32 14.63 8.34 16.28 0.00 0.00 0.00
Maximum of Months 101.96 47.95 54.51 127.87 106.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.10 12.98 17.12 14.36 106.30 0.00 0.00 0.00
February 48.98 22.88 26.11 35.47 83.06 0.00 0.00 0.00
March 64.27 33.44 30.84 55.46 63.01 0.00 0.00 0.00
April 81.50 41.60 39.90 85.28 36.85 0.00 0.00 0.00
May 99.55 47.95 51.61 118.74 22.08 0.00 0.00 0.00
June 95.76 41.66 54.10 119.22 16.28 0.00 0.00 0.00
July 101.96 47.46 54.50 127.87 17.92 0.00 0.00 0.00
August 84.16 38.47 45.69 102.26 21.03 0.00 0.00 0.00
September 66.37 30.33 36.05 72.40 30.76 0.00 0.00 0.00
October 41.93 17.29 24.64 37.37 41.68 0.00 0.00 0.00
November 25.49 8.89 16.59 14.78 61.33 0.00 0.00 0.00
December 22.84 8.28 14.56 8.33 102.41 0.00 0.00 0.00
                 
Annual Sum or Average 63.66 29.31 34.35 66.14 50.11 0.00 0.00 0.00
Minimum of Months 22.84 8.28 14.56 8.33 16.28 0.00 0.00 0.00
Maximum of Months 101.96 47.95 54.50 127.87 106.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.10 12.98 17.12 14.36 106.30 0.00 0.00 0.00
February 48.98 22.88 26.11 35.47 83.06 0.00 0.00 0.00
March 64.27 33.44 30.84 55.46 63.01 0.00 0.00 0.00
April 81.50 41.60 39.90 85.28 36.85 0.00 0.00 0.00
May 99.55 47.95 51.61 118.74 22.08 0.00 0.00 0.00
June 95.76 41.66 54.10 119.22 16.28 0.00 0.00 0.00
July 101.96 47.46 54.50 127.87 17.92 0.00 0.00 0.00
August 84.16 38.47 45.69 102.26 21.03 0.00 0.00 0.00
September 66.37 30.33 36.05 72.40 30.76 0.00 0.00 0.00
October 41.93 17.29 24.64 37.37 41.68 0.00 0.00 0.00
November 25.49 8.89 16.59 14.78 61.33 0.00 0.00 0.00
December 22.84 8.28 14.56 8.33 102.41 0.00 0.00 0.00
                 
Annual Sum or Average 63.66 29.31 34.35 66.14 50.11 0.00 0.00 0.00
Minimum of Months 22.84 8.28 14.56 8.33 16.28 0.00 0.00 0.00
Maximum of Months 101.96 47.95 54.50 127.87 106.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.10 12.98 17.12 14.36 106.30 0.00 0.00 0.00
February 48.99 22.88 26.11 35.47 83.06 0.00 0.00 0.00
March 64.28 33.44 30.84 55.46 63.01 0.00 0.00 0.00
April 81.50 41.60 39.90 85.29 36.85 0.00 0.00 0.00
May 99.55 47.95 51.61 118.74 22.08 0.00 0.00 0.00
June 95.76 41.66 54.10 119.22 16.28 0.00 0.00 0.00
July 101.96 47.46 54.51 127.87 17.92 0.00 0.00 0.00
August 84.17 38.47 45.69 102.26 21.03 0.00 0.00 0.00
September 66.37 30.33 36.05 72.40 30.76 0.00 0.00 0.00
October 41.93 17.29 24.64 37.38 41.68 0.00 0.00 0.00
November 25.49 8.89 16.59 14.78 61.33 0.00 0.00 0.00
December 22.84 8.28 14.56 8.33 102.41 0.00 0.00 0.00
                 
Annual Sum or Average 63.66 29.31 34.35 66.14 50.11 0.00 0.00 0.00
Minimum of Months 22.84 8.28 14.56 8.33 16.28 0.00 0.00 0.00
Maximum of Months 101.96 47.95 54.51 127.87 106.30 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258718E+09 0.181800E+09 76917833.27 0.233256E+09 0.245090E+09
February 0.295615E+09 0.201875E+09 93739376.98 0.300715E+09 0.183135E+09
March 0.287374E+09 0.184413E+09 0.102962E+09 0.301726E+09 0.163209E+09
April 0.232339E+09 0.123492E+09 0.108847E+09 0.262535E+09 99346062.73
May 0.178770E+09 49339284.67 0.129430E+09 0.211618E+09 58252538.01
June 0.147806E+09 25151282.29 0.122655E+09 0.182462E+09 40646969.70
July 0.168667E+09 38875096.78 0.129791E+09 0.212963E+09 45724230.75
August 0.199756E+09 77180732.44 0.122575E+09 0.249760E+09 56150139.27
September 0.234711E+09 0.127294E+09 0.107416E+09 0.279419E+09 82319291.08
October 0.208648E+09 0.125149E+09 83499351.06 0.224524E+09 0.113131E+09
November 0.180744E+09 0.115141E+09 65603046.82 0.174853E+09 0.149712E+09
December 0.199380E+09 0.132304E+09 67075491.83 0.166861E+09 0.237632E+09
           
Annual Sum or Average 0.259253E+10 0.138202E+10 0.121051E+10 0.280069E+10 0.147435E+10
Minimum of Months 0.147806E+09 25151282.29 65603046.82 0.166861E+09 40646969.70
Maximum of Months 0.295615E+09 0.201875E+09 0.129791E+09 0.301726E+09 0.245090E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258715E+09 0.181800E+09 76915043.56 0.233254E+09 0.245089E+09
February 0.295611E+09 0.201875E+09 93735882.40 0.300712E+09 0.183135E+09
March 0.287370E+09 0.184413E+09 0.102957E+09 0.301722E+09 0.163209E+09
April 0.232019E+09 0.123337E+09 0.108682E+09 0.262033E+09 99468566.43
May 0.178502E+09 49218160.66 0.129283E+09 0.211108E+09 58251799.87
June 0.147712E+09 25116894.40 0.122595E+09 0.182289E+09 40646360.03
July 0.168489E+09 38804690.91 0.129684E+09 0.212636E+09 45723434.21
August 0.199402E+09 77036856.12 0.122365E+09 0.249103E+09 56149614.57
September 0.234578E+09 0.127236E+09 0.107341E+09 0.279231E+09 82379347.60
October 0.208643E+09 0.125149E+09 83494872.31 0.224519E+09 0.113130E+09
November 0.180741E+09 0.115141E+09 65600127.02 0.174850E+09 0.149711E+09
December 0.199377E+09 0.132304E+09 67072929.50 0.166859E+09 0.237631E+09
           
Annual Sum or Average 0.259116E+10 0.138143E+10 0.120973E+10 0.279832E+10 0.147452E+10
Minimum of Months 0.147712E+09 25116894.40 65600127.02 0.166859E+09 40646360.03
Maximum of Months 0.295611E+09 0.201875E+09 0.129684E+09 0.301722E+09 0.245089E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258715E+09 0.181800E+09 76915043.56 0.233254E+09 0.245089E+09
February 0.295611E+09 0.201875E+09 93735882.40 0.300712E+09 0.183135E+09
March 0.287370E+09 0.184413E+09 0.102957E+09 0.301722E+09 0.163209E+09
April 0.232013E+09 0.123336E+09 0.108677E+09 0.262028E+09 99474622.07
May 0.178502E+09 49218160.66 0.129283E+09 0.211108E+09 58251799.87
June 0.147712E+09 25116894.40 0.122595E+09 0.182289E+09 40646360.03
July 0.168489E+09 38804690.91 0.129684E+09 0.212636E+09 45723434.21
August 0.199402E+09 77036861.58 0.122365E+09 0.249103E+09 56149609.74
September 0.234561E+09 0.127233E+09 0.107328E+09 0.279228E+09 82405418.35
October 0.208643E+09 0.125149E+09 83494872.31 0.224519E+09 0.113130E+09
November 0.180741E+09 0.115141E+09 65600127.02 0.174850E+09 0.149711E+09
December 0.199377E+09 0.132304E+09 67072929.50 0.166859E+09 0.237631E+09
           
Annual Sum or Average 0.259114E+10 0.138143E+10 0.120971E+10 0.279831E+10 0.147456E+10
Minimum of Months 0.147712E+09 25116894.40 65600127.02 0.166859E+09 40646360.03
Maximum of Months 0.295611E+09 0.201875E+09 0.129684E+09 0.301722E+09 0.245089E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258715E+09 0.181800E+09 76915043.56 0.233254E+09 0.245089E+09
February 0.295611E+09 0.201875E+09 93735882.40 0.300712E+09 0.183135E+09
March 0.287370E+09 0.184413E+09 0.102957E+09 0.301722E+09 0.163209E+09
April 0.232013E+09 0.123336E+09 0.108677E+09 0.262028E+09 99474622.07
May 0.178502E+09 49218160.66 0.129283E+09 0.211108E+09 58251799.87
June 0.147712E+09 25116894.40 0.122595E+09 0.182289E+09 40646360.03
July 0.168489E+09 38804690.91 0.129684E+09 0.212636E+09 45723434.21
August 0.199402E+09 77036879.87 0.122365E+09 0.249103E+09 56149599.45
September 0.234561E+09 0.127233E+09 0.107328E+09 0.279228E+09 82405809.12
October 0.208643E+09 0.125149E+09 83494872.31 0.224519E+09 0.113130E+09
November 0.180741E+09 0.115141E+09 65600127.02 0.174850E+09 0.149711E+09
December 0.199377E+09 0.132304E+09 67072929.50 0.166859E+09 0.237631E+09
           
Annual Sum or Average 0.259114E+10 0.138143E+10 0.120971E+10 0.279831E+10 0.147456E+10
Minimum of Months 0.147712E+09 25116894.40 65600127.02 0.166859E+09 40646360.03
Maximum of Months 0.295611E+09 0.201875E+09 0.129684E+09 0.301722E+09 0.245089E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258715E+09 0.181800E+09 76915043.56 0.233254E+09 0.245089E+09
February 0.295611E+09 0.201875E+09 93735882.40 0.300712E+09 0.183135E+09
March 0.287370E+09 0.184413E+09 0.102957E+09 0.301722E+09 0.163209E+09
April 0.232021E+09 0.123337E+09 0.108683E+09 0.262029E+09 99462051.99
May 0.178502E+09 49218160.66 0.129283E+09 0.211108E+09 58251799.87
June 0.147712E+09 25116894.40 0.122595E+09 0.182289E+09 40646360.03
July 0.168489E+09 38804690.91 0.129684E+09 0.212636E+09 45723434.21
August 0.199402E+09 77037053.29 0.122365E+09 0.249104E+09 56149589.18
September 0.234575E+09 0.127235E+09 0.107340E+09 0.279228E+09 82382632.23
October 0.208643E+09 0.125149E+09 83494872.31 0.224519E+09 0.113130E+09
November 0.180741E+09 0.115141E+09 65600127.02 0.174850E+09 0.149711E+09
December 0.199377E+09 0.132304E+09 67072929.50 0.166859E+09 0.237631E+09
           
Annual Sum or Average 0.259116E+10 0.138143E+10 0.120973E+10 0.279831E+10 0.147452E+10
Minimum of Months 0.147712E+09 25116894.40 65600127.02 0.166859E+09 40646360.03
Maximum of Months 0.295611E+09 0.201875E+09 0.129684E+09 0.301722E+09 0.245089E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258718E+09 0.181800E+09 76917833.13 0.233256E+09 0.245090E+09
February 0.295615E+09 0.201875E+09 93739376.80 0.300715E+09 0.183135E+09
March 0.287374E+09 0.184413E+09 0.102962E+09 0.301726E+09 0.163209E+09
April 0.232361E+09 0.123512E+09 0.108849E+09 0.262369E+09 99125569.81
May 0.178766E+09 49329044.26 0.129437E+09 0.211598E+09 58248509.19
June 0.147810E+09 25152533.01 0.122657E+09 0.182467E+09 40646967.58
July 0.168667E+09 38878106.81 0.129789E+09 0.212970E+09 45724230.71
August 0.199745E+09 77176192.76 0.122569E+09 0.249736E+09 56149026.43
September 0.234684E+09 0.127280E+09 0.107404E+09 0.279320E+09 82277421.80
October 0.208648E+09 0.125149E+09 83499350.83 0.224524E+09 0.113131E+09
November 0.180744E+09 0.115141E+09 65603046.67 0.174853E+09 0.149712E+09
December 0.199380E+09 0.132304E+09 67075491.69 0.166861E+09 0.237632E+09
           
Annual Sum or Average 0.259251E+10 0.138201E+10 0.121050E+10 0.280040E+10 0.147408E+10
Minimum of Months 0.147810E+09 25152533.01 65603046.67 0.166861E+09 40646967.58
Maximum of Months 0.295615E+09 0.201875E+09 0.129789E+09 0.301726E+09 0.245090E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.364218E+09 0.254705E+09 0.109513E+09 0.329182E+09 0.341137E+09
February 0.416353E+09 0.282830E+09 0.133523E+09 0.424134E+09 0.255090E+09
March 0.405366E+09 0.258365E+09 0.147002E+09 0.425553E+09 0.226918E+09
April 0.352831E+09 0.193072E+09 0.159759E+09 0.406882E+09 0.138310E+09
May 0.288015E+09 93709163.73 0.194306E+09 0.352652E+09 81625940.56
June 0.239549E+09 54858173.34 0.184691E+09 0.305352E+09 57050915.71
July 0.274608E+09 79012782.96 0.195595E+09 0.356688E+09 64256991.63
August 0.315252E+09 0.132039E+09 0.183212E+09 0.401532E+09 78620215.03
September 0.334032E+09 0.179729E+09 0.154303E+09 0.398231E+09 0.114922E+09
October 0.295129E+09 0.175335E+09 0.119794E+09 0.317851E+09 0.157931E+09
November 0.255057E+09 0.161314E+09 93742856.35 0.247099E+09 0.208626E+09
December 0.280942E+09 0.185360E+09 95581461.85 0.235664E+09 0.330403E+09
           
Annual Sum or Average 0.382135E+10 0.205033E+10 0.177102E+10 0.420082E+10 0.205489E+10
Minimum of Months 0.239549E+09 54858173.34 93742856.35 0.235664E+09 57050915.71
Maximum of Months 0.416353E+09 0.282830E+09 0.195595E+09 0.425553E+09 0.341137E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79674171.33 34235427.12 45438744.21 34243639.43 0.278602E+09
February 0.112814E+09 49161409.22 63652811.30 73363274.35 0.193293E+09
March 0.170102E+09 86654416.25 83447322.72 0.140498E+09 0.161458E+09
April 0.226781E+09 0.123220E+09 0.103561E+09 0.238051E+09 88787936.97
May 0.250525E+09 0.110835E+09 0.139689E+09 0.293648E+09 52940558.24
June 0.275028E+09 0.132214E+09 0.142815E+09 0.342235E+09 39255043.05
July 0.279165E+09 0.131710E+09 0.147455E+09 0.349881E+09 43232071.26
August 0.215175E+09 94886395.19 0.120289E+09 0.258179E+09 52115986.35
September 0.167724E+09 76290340.07 91433166.51 0.179999E+09 75230042.75
October 0.104922E+09 40920348.32 64001617.51 87779262.38 0.107075E+09
November 64779871.32 22415755.56 42364115.76 34891511.87 0.155188E+09
December 61414737.49 23528664.48 37886073.01 21679105.03 0.270074E+09
           
Annual Sum or Average 0.200810E+10 0.926072E+09 0.108203E+10 0.205445E+10 0.151725E+10
Minimum of Months 61414737.49 22415755.56 37886073.01 21679105.03 39255043.05
Maximum of Months 0.279165E+09 0.132214E+09 0.147455E+09 0.349881E+09 0.278602E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79671381.76 34235427.12 45435954.64 34242774.81 0.278603E+09
February 0.112811E+09 49161409.22 63649316.91 73361071.55 0.193294E+09
March 0.170097E+09 86654416.25 83442938.73 0.140495E+09 0.161458E+09
April 0.226776E+09 0.123220E+09 0.103556E+09 0.238046E+09 88787468.03
May 0.250517E+09 0.110835E+09 0.139682E+09 0.293639E+09 52939716.48
June 0.275022E+09 0.132214E+09 0.142808E+09 0.342227E+09 39254383.50
July 0.279158E+09 0.131710E+09 0.147448E+09 0.349874E+09 43231107.28
August 0.215169E+09 94886395.19 0.120282E+09 0.258171E+09 52115290.08
September 0.167718E+09 76290340.07 91427857.38 0.179993E+09 75229320.49
October 0.104917E+09 40920348.32 63997138.99 87774653.75 0.107074E+09
November 64776951.67 22415755.56 42361196.11 34889823.83 0.155189E+09
December 61412175.29 23528664.48 37883510.81 21678647.97 0.270075E+09
           
Annual Sum or Average 0.200805E+10 0.926072E+09 0.108197E+10 0.205439E+10 0.151725E+10
Minimum of Months 61412175.29 22415755.56 37883510.81 21678647.97 39254383.50
Maximum of Months 0.279158E+09 0.132214E+09 0.147448E+09 0.349874E+09 0.278603E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79671381.76 34235427.12 45435954.64 34242774.81 0.278603E+09
February 0.112811E+09 49161409.22 63649316.91 73361071.55 0.193294E+09
March 0.170097E+09 86654416.25 83442938.73 0.140495E+09 0.161458E+09
April 0.226776E+09 0.123220E+09 0.103556E+09 0.238046E+09 88787468.03
May 0.250517E+09 0.110835E+09 0.139682E+09 0.293639E+09 52939716.48
June 0.275022E+09 0.132214E+09 0.142808E+09 0.342227E+09 39254383.50
July 0.279158E+09 0.131710E+09 0.147448E+09 0.349874E+09 43231107.28
August 0.215169E+09 94886395.19 0.120282E+09 0.258171E+09 52115290.08
September 0.167718E+09 76290340.07 91427857.38 0.179993E+09 75229320.49
October 0.104917E+09 40920348.32 63997138.99 87774653.75 0.107074E+09
November 64776951.67 22415755.56 42361196.11 34889823.83 0.155189E+09
December 61412175.29 23528664.48 37883510.81 21678647.97 0.270075E+09
           
Annual Sum or Average 0.200805E+10 0.926072E+09 0.108197E+10 0.205439E+10 0.151725E+10
Minimum of Months 61412175.29 22415755.56 37883510.81 21678647.97 39254383.50
Maximum of Months 0.279158E+09 0.132214E+09 0.147448E+09 0.349874E+09 0.278603E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80009069.89 34368040.21 45641029.68 34346905.03 0.278078E+09
February 0.113088E+09 49280530.50 63807419.50 73685821.00 0.193099E+09
March 0.170158E+09 86682625.00 83475673.27 0.140584E+09 0.161435E+09
April 0.226781E+09 0.123220E+09 0.103561E+09 0.238051E+09 88787936.99
May 0.250525E+09 0.110835E+09 0.139689E+09 0.293648E+09 52940558.29
June 0.275028E+09 0.132214E+09 0.142815E+09 0.342235E+09 39255043.08
July 0.279165E+09 0.131710E+09 0.147455E+09 0.349881E+09 43232071.30
August 0.215175E+09 94886445.14 0.120289E+09 0.258179E+09 52115986.39
September 0.167737E+09 76294683.29 91442452.72 0.180023E+09 75230042.78
October 0.105016E+09 40958783.93 64057609.93 87950929.91 0.107073E+09
November 64991942.45 22496654.59 42495287.85 35131790.69 0.155038E+09
December 61693584.31 23623452.32 38070131.99 21725993.28 0.269616E+09
           
Annual Sum or Average 0.200937E+10 0.926571E+09 0.108280E+10 0.205544E+10 0.151590E+10
Minimum of Months 61693584.31 22496654.59 38070131.99 21725993.28 39255043.08
Maximum of Months 0.279165E+09 0.132214E+09 0.147455E+09 0.349881E+09 0.278078E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35382545.75 0.00 35382545.75 545832.70 0.309622E+09
February 49431423.64 0.00 49431423.64 5905114.22 0.215212E+09
March 67673633.78 0.00 67673633.78 16431275.75 0.176521E+09
April 86261573.83 680711.13 85580862.70 56513580.41 92060762.55
May 0.124496E+09 6723121.17 0.117773E+09 0.130175E+09 50733683.73
June 0.134831E+09 14874426.79 0.119957E+09 0.160353E+09 36846329.60
July 0.133410E+09 11421388.20 0.121988E+09 0.158792E+09 41015444.58
August 0.101115E+09 1733360.30 99381589.66 0.108570E+09 49817315.21
September 75832140.15 18659.71 75813480.45 61706725.41 75655452.58
October 53812295.12 0.00 53812295.12 24914234.71 0.110654E+09
November 34435906.63 0.00 34435906.63 3870112.46 0.167588E+09
December 29798820.40 0.00 29798820.40 73383.36 0.295649E+09
           
Annual Sum or Average 0.926480E+09 35451667.30 0.891028E+09 0.727851E+09 0.162138E+10
Minimum of Months 29798820.40 0.00 29798820.40 73383.36 36846329.60
Maximum of Months 0.134831E+09 14874426.79 0.121988E+09 0.160353E+09 0.309622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35379756.04 0.00 35379756.04 545553.62 0.309624E+09
February 49427929.06 0.00 49427929.06 5903677.74 0.215213E+09
March 67669249.56 0.00 67669249.56 16428691.79 0.176522E+09
April 86198353.50 665751.13 85532602.37 56489243.35 92146381.27
May 0.124187E+09 6611513.37 0.117575E+09 0.129653E+09 50779627.74
June 0.134448E+09 14706602.41 0.119741E+09 0.159631E+09 36845632.25
July 0.133001E+09 11258747.96 0.121742E+09 0.158032E+09 41014532.60
August 0.100928E+09 1674407.81 99253904.63 0.108240E+09 49826426.55
September 75829490.17 18772.28 75810717.88 61701476.22 75651704.52
October 53807816.37 0.00 53807816.37 24910046.46 0.110654E+09
November 34432986.83 0.00 34432986.83 3868979.04 0.167589E+09
December 29796258.07 0.00 29796258.07 73290.13 0.295650E+09
           
Annual Sum or Average 0.925106E+09 34935794.98 0.890170E+09 0.725476E+09 0.162152E+10
Minimum of Months 29796258.07 0.00 29796258.07 73290.13 36845632.25
Maximum of Months 0.134448E+09 14706602.41 0.121742E+09 0.159631E+09 0.309624E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35379756.04 0.00 35379756.04 545553.62 0.309624E+09
February 49427929.06 0.00 49427929.06 5903677.74 0.215213E+09
March 67669249.56 0.00 67669249.56 16428691.79 0.176522E+09
April 86171706.08 660112.97 85511593.11 56479677.38 92183943.58
May 0.124187E+09 6611513.37 0.117575E+09 0.129653E+09 50779627.74
June 0.134448E+09 14706602.41 0.119741E+09 0.159631E+09 36845632.25
July 0.133000E+09 11258682.02 0.121742E+09 0.158031E+09 41014532.60
August 0.100925E+09 1673761.05 99250955.70 0.108235E+09 49827554.78
September 75828840.84 18745.60 75810095.24 61702279.96 75653444.93
October 53807816.37 0.00 53807816.37 24910046.46 0.110654E+09
November 34432986.83 0.00 34432986.83 3868979.04 0.167589E+09
December 29796258.07 0.00 29796258.07 73290.13 0.295650E+09
           
Annual Sum or Average 0.925074E+09 34929417.42 0.890145E+09 0.725462E+09 0.162156E+10
Minimum of Months 29796258.07 0.00 29796258.07 73290.13 36845632.25
Maximum of Months 0.134448E+09 14706602.41 0.121742E+09 0.159631E+09 0.309624E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35379756.04 0.00 35379756.04 545553.62 0.309624E+09
February 49427929.06 0.00 49427929.06 5903677.74 0.215213E+09
March 67669249.56 0.00 67669249.56 16428691.79 0.176522E+09
April 86171706.08 660112.97 85511593.11 56479677.38 92183943.58
May 0.124187E+09 6611513.37 0.117575E+09 0.129653E+09 50779627.74
June 0.134448E+09 14706602.41 0.119741E+09 0.159631E+09 36845632.25
July 0.133000E+09 11258682.02 0.121742E+09 0.158031E+09 41014532.60
August 0.100923E+09 1673751.62 99249570.23 0.108233E+09 49828198.29
September 75828681.64 18786.99 75809894.65 61703733.88 75655094.34
October 53807816.37 0.00 53807816.37 24910046.46 0.110654E+09
November 34432986.83 0.00 34432986.83 3868979.04 0.167589E+09
December 29796258.07 0.00 29796258.07 73290.13 0.295650E+09
           
Annual Sum or Average 0.925073E+09 34929449.38 0.890143E+09 0.725462E+09 0.162156E+10
Minimum of Months 29796258.07 0.00 29796258.07 73290.13 36845632.25
Maximum of Months 0.134448E+09 14706602.41 0.121742E+09 0.159631E+09 0.309624E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35379756.04 0.00 35379756.04 545553.62 0.309624E+09
February 49427929.06 0.00 49427929.06 5903677.74 0.215213E+09
March 67669249.56 0.00 67669249.56 16428691.79 0.176522E+09
April 86196590.78 664932.49 85531658.29 56499562.35 92160934.79
May 0.124187E+09 6611513.37 0.117575E+09 0.129653E+09 50779627.74
June 0.134448E+09 14706602.41 0.119741E+09 0.159631E+09 36845632.25
July 0.133001E+09 11258709.33 0.121742E+09 0.158032E+09 41014532.60
August 0.100925E+09 1674671.49 99250413.39 0.108238E+09 49828798.52
September 75829027.16 18896.80 75810130.36 61705425.84 75656052.71
October 53807816.37 0.00 53807816.37 24910046.46 0.110654E+09
November 34432986.83 0.00 34432986.83 3868979.04 0.167589E+09
December 29796258.07 0.00 29796258.07 73290.13 0.295650E+09
           
Annual Sum or Average 0.925100E+09 34935325.88 0.890165E+09 0.725489E+09 0.162154E+10
Minimum of Months 29796258.07 0.00 29796258.07 73290.13 36845632.25
Maximum of Months 0.134448E+09 14706602.41 0.121742E+09 0.159631E+09 0.309624E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35382545.61 0.00 35382545.61 545832.69 0.309622E+09
February 49431423.45 0.00 49431423.45 5905114.14 0.215212E+09
March 67673633.55 0.00 67673633.55 16431275.62 0.176521E+09
April 86259902.85 678941.64 85580961.21 56554375.33 92108132.09
May 0.124499E+09 6757938.31 0.117741E+09 0.130258E+09 50778093.47
June 0.134753E+09 14822923.25 0.119930E+09 0.160187E+09 36846318.05
July 0.133352E+09 11398948.84 0.121953E+09 0.158680E+09 41014877.66
August 0.101123E+09 1734612.05 99388073.26 0.108593E+09 49829391.40
September 75831617.35 18827.07 75812790.28 61711473.36 75660600.42
October 53812294.89 0.00 53812294.89 24914234.49 0.110654E+09
November 34435906.48 0.00 34435906.48 3870112.40 0.167588E+09
December 29798820.27 0.00 29798820.27 73383.35 0.295649E+09
           
Annual Sum or Average 0.926352E+09 35412191.15 0.890940E+09 0.727724E+09 0.162148E+10
Minimum of Months 29798820.27 0.00 29798820.27 73383.35 36846318.05
Maximum of Months 0.134753E+09 14822923.25 0.121953E+09 0.160187E+09 0.309622E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80946092.64 34895096.84 46050995.80 38562618.03 0.284207E+09
February 0.118784E+09 55468158.45 63315774.89 86131760.65 0.200754E+09
March 0.172215E+09 89587223.60 82627409.53 0.148643E+09 0.168754E+09
April 0.211260E+09 0.107834E+09 0.103426E+09 0.221060E+09 95520567.88
May 0.266648E+09 0.128418E+09 0.138229E+09 0.318040E+09 59146445.70
June 0.248212E+09 0.107976E+09 0.140237E+09 0.309029E+09 42189372.68
July 0.273100E+09 0.127107E+09 0.145992E+09 0.342483E+09 47987404.19
August 0.225430E+09 0.103042E+09 0.122388E+09 0.273904E+09 56319286.93
September 0.172049E+09 78607895.13 93440770.99 0.187682E+09 79719683.57
October 0.112403E+09 46342988.81 66059790.97 0.100295E+09 0.111643E+09
November 66302804.43 23139340.44 43163463.99 38586735.60 0.158827E+09
December 61457612.82 22279976.48 39177636.34 22344190.29 0.273839E+09
           
Annual Sum or Average 0.200881E+10 0.924698E+09 0.108411E+10 0.208676E+10 0.157891E+10
Minimum of Months 61457612.82 22279976.48 39177636.34 22344190.29 42189372.68
Maximum of Months 0.273100E+09 0.128418E+09 0.145992E+09 0.342483E+09 0.284207E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80622364.36 34766160.37 45856203.99 38472652.43 0.284719E+09
February 0.118502E+09 55348303.18 63154012.38 85801331.42 0.200945E+09
March 0.172152E+09 89558993.59 82592814.07 0.148544E+09 0.168771E+09
April 0.211255E+09 0.107834E+09 0.103421E+09 0.221055E+09 95520236.30
May 0.266640E+09 0.128418E+09 0.138222E+09 0.318031E+09 59145669.51
June 0.248206E+09 0.107976E+09 0.140230E+09 0.309021E+09 42188718.00
July 0.273093E+09 0.127107E+09 0.145986E+09 0.342476E+09 47986616.92
August 0.225424E+09 0.103042E+09 0.122382E+09 0.273897E+09 56318615.40
September 0.172032E+09 78603229.22 93428743.28 0.187655E+09 79719179.43
October 0.112296E+09 46301701.56 65994194.96 0.100105E+09 0.111643E+09
November 66064959.61 23055227.01 43009732.60 38306008.74 0.158971E+09
December 61184077.85 22184412.71 38999665.14 22306198.67 0.274294E+09
           
Annual Sum or Average 0.200747E+10 0.924195E+09 0.108328E+10 0.208567E+10 0.158022E+10
Minimum of Months 61184077.85 22184412.71 38999665.14 22306198.67 42188718.00
Maximum of Months 0.273093E+09 0.128418E+09 0.145986E+09 0.342476E+09 0.284719E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80622364.36 34766160.37 45856203.99 38472652.43 0.284719E+09
February 0.118502E+09 55348303.18 63154012.38 85801331.42 0.200945E+09
March 0.172152E+09 89558993.59 82592814.07 0.148544E+09 0.168771E+09
April 0.211255E+09 0.107834E+09 0.103421E+09 0.221055E+09 95520236.30
May 0.266640E+09 0.128418E+09 0.138222E+09 0.318031E+09 59145669.51
June 0.248206E+09 0.107976E+09 0.140230E+09 0.309021E+09 42188718.00
July 0.273093E+09 0.127107E+09 0.145986E+09 0.342476E+09 47986616.92
August 0.225424E+09 0.103042E+09 0.122382E+09 0.273897E+09 56318615.40
September 0.172032E+09 78603229.22 93428743.28 0.187655E+09 79719179.43
October 0.112296E+09 46301701.56 65994194.96 0.100105E+09 0.111643E+09
November 66064959.61 23055227.01 43009732.60 38306008.74 0.158971E+09
December 61184077.85 22184412.71 38999665.14 22306198.67 0.274294E+09
           
Annual Sum or Average 0.200747E+10 0.924195E+09 0.108328E+10 0.208567E+10 0.158022E+10
Minimum of Months 61184077.85 22184412.71 38999665.14 22306198.67 42188718.00
Maximum of Months 0.273093E+09 0.128418E+09 0.145986E+09 0.342476E+09 0.284719E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80625154.07 34766160.37 45858993.70 38473514.60 0.284718E+09
February 0.118506E+09 55348303.18 63157506.96 85803542.66 0.200945E+09
March 0.172156E+09 89558993.59 82597198.29 0.148548E+09 0.168770E+09
April 0.211260E+09 0.107834E+09 0.103426E+09 0.221060E+09 95520567.90
May 0.266648E+09 0.128418E+09 0.138229E+09 0.318040E+09 59146445.74
June 0.248212E+09 0.107976E+09 0.140237E+09 0.309029E+09 42189372.71
July 0.273100E+09 0.127107E+09 0.145992E+09 0.342483E+09 47987404.23
August 0.225430E+09 0.103042E+09 0.122388E+09 0.273904E+09 56319286.96
September 0.172037E+09 78603229.22 93434052.68 0.187661E+09 79719683.60
October 0.112300E+09 46301701.56 65998673.71 0.100109E+09 0.111644E+09
November 66067879.41 23055227.01 43012652.40 38307669.94 0.158970E+09
December 61186640.18 22184412.71 39002227.47 22306739.76 0.274293E+09
           
Annual Sum or Average 0.200753E+10 0.924195E+09 0.108333E+10 0.208573E+10 0.158022E+10
Minimum of Months 61186640.18 22184412.71 39002227.47 22306739.76 42189372.71
Maximum of Months 0.273100E+09 0.128418E+09 0.145992E+09 0.342483E+09 0.284718E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 645.42 676.40 715.55 502.35 213.19 0.00 0.00
February 921.13 559.64 905.27 617.59 287.68 0.00 0.00
March 834.78 450.32 795.10 509.57 285.53 0.00 0.00
April 763.81 283.39 673.46 360.12 313.34 0.00 0.00
May 604.95 160.96 507.60 145.33 362.27 0.00 0.00
June 539.90 116.10 434.42 79.33 355.09 0.00 0.00
July 609.75 126.42 480.10 116.48 363.62 0.00 0.00
August 708.42 155.13 564.65 221.98 342.67 0.00 0.00
September 800.09 234.97 671.95 363.90 308.05 0.00 0.00
October 621.63 312.39 577.58 345.81 231.77 0.00 0.00
November 500.07 427.04 516.79 328.77 188.02 0.00 0.00
December 461.76 655.67 551.53 365.59 185.94 0.00 0.00
               
Annual Sum or Average 665.74 345.67 614.25 327.88 286.37 0.00 0.00
Minimum of Months 461.76 116.10 434.42 79.33 185.94 0.00 0.00
Maximum of Months 921.13 676.40 905.27 617.59 363.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 51.17 415.87 119.11 51.18 67.93 0.00 0.00
February 121.42 319.51 186.64 81.33 105.31 0.00 0.00
March 209.85 241.12 254.05 129.42 124.63 0.00 0.00
April 367.36 137.02 349.97 190.15 159.81 0.00 0.00
May 438.54 79.06 374.13 165.52 208.61 0.00 0.00
June 528.13 60.58 424.42 204.03 220.39 0.00 0.00
July 522.52 64.56 416.91 196.70 220.21 0.00 0.00
August 385.57 77.83 321.34 141.71 179.64 0.00 0.00
September 277.78 116.10 258.83 117.73 141.10 0.00 0.00
October 131.15 159.91 156.73 61.13 95.60 0.00 0.00
November 53.93 239.42 100.05 34.62 65.43 0.00 0.00
December 32.39 403.16 91.82 35.17 56.65 0.00 0.00
               
Annual Sum or Average 260.61 192.40 254.74 117.48 137.26 0.00 0.00
Minimum of Months 32.39 60.58 91.82 34.62 56.65 0.00 0.00
Maximum of Months 528.13 415.87 424.42 204.03 220.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.22 693.60 79.26 0.00 79.26 0.00 0.00
February 14.64 533.76 122.59 0.00 122.59 0.00 0.00
March 36.80 395.43 151.59 0.00 151.59 0.00 0.00
April 130.79 213.29 199.56 1.55 198.01 0.00 0.00
May 290.85 113.72 278.43 14.91 263.52 0.00 0.00
June 370.01 85.29 311.49 34.15 277.33 0.00 0.00
July 354.54 91.88 298.22 25.33 272.89 0.00 0.00
August 242.72 111.61 226.23 3.80 222.44 0.00 0.00
September 142.84 175.13 175.53 0.04 175.49 0.00 0.00
October 55.81 247.88 120.54 0.00 120.54 0.00 0.00
November 8.96 387.94 79.71 0.00 79.71 0.00 0.00
December 0.16 662.30 66.75 0.00 66.75 0.00 0.00
               
Annual Sum or Average 138.17 308.50 176.09 6.68 169.41 0.00 0.00
Minimum of Months 0.16 85.29 66.75 0.00 66.75 0.00 0.00
Maximum of Months 370.01 693.60 311.49 34.15 277.33 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 57.49 425.01 120.53 51.97 68.56 0.00 0.00
February 142.00 332.17 196.05 91.56 104.49 0.00 0.00
March 221.88 252.04 257.12 133.76 123.36 0.00 0.00
April 341.14 147.41 326.02 166.41 159.60 0.00 0.00
May 474.96 88.33 398.21 191.78 206.43 0.00 0.00
June 476.89 65.11 383.04 166.63 216.41 0.00 0.00
July 511.47 71.67 407.85 189.83 218.02 0.00 0.00
August 409.05 84.11 336.66 153.89 182.77 0.00 0.00
September 289.60 123.02 265.49 121.30 144.19 0.00 0.00
October 149.57 166.73 167.75 69.16 98.58 0.00 0.00
November 59.21 245.26 102.04 35.61 66.43 0.00 0.00
December 33.32 409.47 91.48 33.17 58.31 0.00 0.00
               
Annual Sum or Average 264.58 200.39 254.67 117.24 137.43 0.00 0.00
Minimum of Months 33.32 65.11 91.48 33.17 58.31 0.00 0.00
Maximum of Months 511.47 425.01 407.85 191.78 218.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.172869E+10 0.181166E+10 0.191652E+10 0.134551E+10 0.571009E+09 0.00 0.00
February 0.222840E+10 0.135389E+10 0.219003E+10 0.149408E+10 0.695945E+09 0.00 0.00
March 0.223587E+10 0.120615E+10 0.212960E+10 0.136484E+10 0.764754E+09 0.00 0.00
April 0.197979E+10 0.734549E+09 0.174560E+10 0.933422E+09 0.812175E+09 0.00 0.00
May 0.162029E+10 0.431125E+09 0.135956E+10 0.389250E+09 0.970307E+09 0.00 0.00
June 0.139943E+10 0.300924E+09 0.112601E+10 0.205630E+09 0.920383E+09 0.00 0.00
July 0.163316E+10 0.338596E+09 0.128590E+10 0.311985E+09 0.973912E+09 0.00 0.00
August 0.189743E+10 0.415509E+09 0.151236E+10 0.594544E+09 0.917818E+09 0.00 0.00
September 0.207384E+10 0.609046E+09 0.174170E+10 0.943240E+09 0.798461E+09 0.00 0.00
October 0.166496E+10 0.836700E+09 0.154700E+10 0.926227E+09 0.620772E+09 0.00 0.00
November 0.129619E+10 0.110688E+10 0.133951E+10 0.852161E+09 0.487349E+09 0.00 0.00
December 0.123678E+10 0.175615E+10 0.147721E+10 0.979186E+09 0.498024E+09 0.00 0.00
               
Annual Sum or Average 0.209948E+11 0.109012E+11 0.193710E+11 0.103401E+11 0.903091E+10 0.00 0.00
Minimum of Months 0.123678E+10 0.300924E+09 0.112601E+10 0.205630E+09 0.487349E+09 0.00 0.00
Maximum of Months 0.223587E+10 0.181166E+10 0.219003E+10 0.149408E+10 0.973912E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.137061E+09 0.111387E+10 0.319026E+09 0.137074E+09 0.181952E+09 0.00 0.00
February 0.293743E+09 0.772951E+09 0.451524E+09 0.196765E+09 0.254759E+09 0.00 0.00
March 0.562072E+09 0.645810E+09 0.680455E+09 0.346646E+09 0.333809E+09 0.00 0.00
April 0.952193E+09 0.355151E+09 0.907114E+09 0.492881E+09 0.414233E+09 0.00 0.00
May 0.117457E+10 0.211761E+09 0.100208E+10 0.443341E+09 0.558742E+09 0.00 0.00
June 0.136892E+10 0.157019E+09 0.110010E+10 0.528855E+09 0.571245E+09 0.00 0.00
July 0.139951E+10 0.172926E+09 0.111665E+10 0.526841E+09 0.589806E+09 0.00 0.00
August 0.103270E+10 0.208463E+09 0.860688E+09 0.379546E+09 0.481142E+09 0.00 0.00
September 0.720009E+09 0.300919E+09 0.670897E+09 0.305166E+09 0.365731E+09 0.00 0.00
October 0.351279E+09 0.428296E+09 0.419773E+09 0.163720E+09 0.256054E+09 0.00 0.00
November 0.139775E+09 0.620575E+09 0.259326E+09 89743921.28 0.169582E+09 0.00 0.00
December 86759593.60 0.107984E+10 0.245933E+09 94209445.77 0.151723E+09 0.00 0.00
               
Annual Sum or Average 0.821860E+10 0.606758E+10 0.803356E+10 0.370479E+10 0.432878E+10 0.00 0.00
Minimum of Months 86759593.60 0.157019E+09 0.245933E+09 89743921.28 0.151723E+09 0.00 0.00
Maximum of Months 0.139951E+10 0.111387E+10 0.111665E+10 0.528855E+09 0.589806E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3273879.85 0.185774E+10 0.212284E+09 0.00 0.212284E+09 0.00 0.00
February 35424939.34 0.129127E+10 0.296575E+09 0.00 0.296575E+09 0.00 0.00
March 98577318.51 0.105913E+10 0.406024E+09 0.00 0.406024E+09 0.00 0.00
April 0.339014E+09 0.552842E+09 0.517260E+09 4010562.31 0.513249E+09 0.00 0.00
May 0.779011E+09 0.304597E+09 0.745742E+09 39927112.97 0.705815E+09 0.00 0.00
June 0.959065E+09 0.221075E+09 0.807375E+09 88523759.70 0.718851E+09 0.00 0.00
July 0.949598E+09 0.246088E+09 0.798763E+09 67855158.36 0.730908E+09 0.00 0.00
August 0.650099E+09 0.298948E+09 0.605939E+09 10164564.31 0.595775E+09 0.00 0.00
September 0.370229E+09 0.453930E+09 0.454980E+09 112688.45 0.454867E+09 0.00 0.00
October 0.149469E+09 0.663924E+09 0.322856E+09 0.00 0.322856E+09 0.00 0.00
November 23216141.02 0.100553E+10 0.206604E+09 0.00 0.206604E+09 0.00 0.00
December 439927.24 0.177390E+10 0.178783E+09 0.00 0.178783E+09 0.00 0.00
               
Annual Sum or Average 0.435742E+10 0.972898E+10 0.555318E+10 0.210594E+09 0.534259E+10 0.00 0.00
Minimum of Months 439927.24 0.221075E+09 0.178783E+09 0.00 0.178783E+09 0.00 0.00
Maximum of Months 0.959065E+09 0.185774E+10 0.807375E+09 88523759.70 0.730908E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.153969E+09 0.113835E+10 0.322816E+09 0.139194E+09 0.183622E+09 0.00 0.00
February 0.343526E+09 0.803577E+09 0.474294E+09 0.221513E+09 0.252781E+09 0.00 0.00
March 0.594279E+09 0.675064E+09 0.688674E+09 0.358264E+09 0.330410E+09 0.00 0.00
April 0.884231E+09 0.382082E+09 0.845031E+09 0.431336E+09 0.413695E+09 0.00 0.00
May 0.127214E+10 0.236584E+09 0.106658E+10 0.513673E+09 0.552902E+09 0.00 0.00
June 0.123610E+10 0.168756E+09 0.992836E+09 0.431903E+09 0.560933E+09 0.00 0.00
July 0.136992E+10 0.191948E+09 0.109238E+10 0.508429E+09 0.583956E+09 0.00 0.00
August 0.109560E+10 0.225276E+09 0.901707E+09 0.412168E+09 0.489539E+09 0.00 0.00
September 0.750654E+09 0.318878E+09 0.688150E+09 0.314418E+09 0.373732E+09 0.00 0.00
October 0.400614E+09 0.446573E+09 0.449295E+09 0.185248E+09 0.264047E+09 0.00 0.00
November 0.153478E+09 0.635711E+09 0.264501E+09 92305021.48 0.172196E+09 0.00 0.00
December 89255180.49 0.109671E+10 0.245012E+09 88833214.62 0.156179E+09 0.00 0.00
               
Annual Sum or Average 0.834377E+10 0.631951E+10 0.803128E+10 0.369728E+10 0.433399E+10 0.00 0.00
Minimum of Months 89255180.49 0.168756E+09 0.245012E+09 88833214.62 0.156179E+09 0.00 0.00
Maximum of Months 0.136992E+10 0.113835E+10 0.109238E+10 0.513673E+09 0.583956E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -16.9 -17.4 -20.0 3.73 -31.9 33.25 98.18 0.00
February -11.6 -12.7 -16.7 4.33 -26.7 48.91 138.70 0.00
March -6.2 -7.6 -10.8 3.55 -19.4 56.69 163.76 0.01
April 3.97 0.41 -4.8 4.72 -9.1 70.41 207.70 0.01
May 13.43 8.45 3.53 3.60 2.20 102.27 202.62 0.00
June 18.03 14.19 11.55 3.74 7.84 104.36 210.60 0.06
July 19.67 16.51 14.78 3.14 8.97 101.67 223.82 0.04
August 17.94 15.20 13.59 3.45 8.99 87.39 175.79 0.04
September 12.29 9.87 7.80 3.78 3.34 70.27 143.96 0.00
October 5.42 3.47 1.07 3.53 -4.7 51.74 90.11 0.00
November -2.0 -3.6 -6.9 4.42 -13.7 34.68 65.95 0.00
December -14.6 -15.1 -18.1 3.91 -28.3 29.58 68.99 0.00
                 
Annual Sum or Average 3.36 1.04 -2.0 3.82 -8.4 66.03 149.18 0.01
Minimum of Months -16.9 -17.4 -20.0 3.14 -31.9 29.58 65.95 0.00
Maximum of Months 19.67 16.51 14.78 4.72 8.99 104.36 223.82 0.06



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.10 29-JAN-14:00 -1.0 -4.4 2.60 -11.4 145.00 110.00
February 8.90 20-FEB-15:00 2.87 -6.7 8.80 -9.0 49.00 646.00
March 11.10 26-MAR-15:00 5.48 -1.1 5.20 -5.7 53.00 842.00
April 26.70 23-APR-15:00 16.95 11.10 11.30 12.03 75.50 811.00
May 29.40 25-MAY-17:00 19.26 13.90 1.50 16.49 47.50 582.00
June 35.00 29-JUN-15:00 24.72 21.10 6.70 24.66 132.00 705.00
July 31.10 15-JUL-14:20 25.35 23.33 8.07 19.93 299.67 518.33
August 30.60 08-AUG-14:00 23.36 20.60 6.70 17.93 163.50 672.50
September 26.10 01-SEP-14:00 17.82 13.30 3.60 14.28 112.00 751.50
October 22.20 19-OCT-14:00 13.62 7.20 6.70 8.15 35.50 701.50
November 18.30 01-NOV-14:00 13.44 10.00 3.10 11.84 105.00 30.50
December 1.10 28-DEC-02:00 0.43 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.10   -1.0 -6.7 1.50 -11.4 0.00 0.00
Maximum of Months 35.00   25.35 23.33 11.30 24.66 299.67 842.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -35.6 06-JAN-08:00 -35.7 -37.8 0.00 -57.8 27.00 381.00
February -33.3 14-FEB-06:00 -33.4 -36.7 0.00 -55.6 0.00 0.00
March -28.9 05-MAR-06:00 -29.1 -32.2 1.50 -50.6 27.00 41.50
April -13.9 05-APR-05:00 -14.4 -16.1 0.00 -32.5 14.50 199.00
May -3.9 01-MAY-05:00 -6.2 -12.2 0.00 -22.4 35.00 415.00
June 1.10 04-JUN-04:00 0.62 0.00 0.00 -14.9 37.00 169.50
July 6.10 02-JUL-04:00 6.10 6.10 0.00 -8.8 33.50 204.50
August 4.40 19-AUG-03:00 4.40 4.40 0.00 -10.7 0.00 0.00
September 1.10 06-SEP-03:00 1.10 1.10 0.00 -14.7 0.00 0.00
October -10.0 30-OCT-03:00 -10.7 -12.8 1.50 -28.2 0.00 0.00
November -20.6 29-NOV-05:00 -20.8 -22.2 2.10 -37.8 0.00 0.00
December -31.1 24-DEC-06:19 -31.3 -35.1 3.33 -53.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -35.6   -35.7 -37.8 0.00 -57.8 0.00 0.00
Maximum of Months 6.10   6.10 6.10 3.33 -8.8 37.00 415.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.5 16-JAN-12:00 0.00 -1.1 5.70 -6.6 172.50 3.00
February 3.34 21-FEB-12:00 6.70 -1.1 7.70 -6.0 270.00 303.00
March 5.48 26-MAR-15:00 11.10 -1.1 5.20 -5.7 53.00 842.00
April 16.95 23-APR-15:00 26.70 11.10 11.30 12.03 75.50 811.00
May 19.91 26-MAY-11:00 25.60 17.20 6.20 22.64 300.50 6.00
June 24.72 29-JUN-15:00 35.00 21.10 6.70 24.66 132.00 705.00
July 25.76 15-JUL-13:00 31.10 23.90 7.70 18.99 333.00 421.00
August 23.36 08-AUG-14:00 30.60 20.60 6.70 17.93 163.50 672.50
September 18.67 01-SEP-00:00 19.00 17.50 2.80 16.30 0.00 0.00
October 13.72 19-OCT-13:00 21.70 7.80 5.70 7.75 54.50 739.00
November 14.29 21-NOV-12:00 15.00 13.90 5.20 11.46 134.50 25.50
December 0.43 28-DEC-02:00 1.10 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.5   0.00 -1.1 2.80 -6.6 0.00 0.00
Maximum of Months 25.76   35.00 23.90 11.30 24.66 333.00 842.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 16-JAN-11:00 -0.6 -0.8 5.70 -7.3 164.50 5.00
February -0.6 21-FEB-08:00 4.40 2.25 8.80 -6.6 123.00 89.50
March 0.00 29-MAR-20:00 1.70 0.95 1.50 -4.8 0.00 0.00
April 11.10 23-APR-13:00 24.40 16.08 10.80 9.72 98.50 903.50
May 17.20 26-MAY-11:00 25.60 19.91 6.20 22.64 300.50 6.00
June 22.80 29-JUN-23:19 26.30 23.71 5.20 14.28 0.00 0.00
July 23.90 15-JUL-13:00 31.10 25.76 7.70 18.99 333.00 421.00
August 20.60 08-AUG-14:00 30.60 23.36 6.70 17.93 163.50 672.50
September 17.92 01-SEP-00:10 19.75 18.15 3.22 13.23 0.00 0.00
October 12.20 07-OCT-12:20 14.47 13.17 3.43 9.20 163.17 18.50
November 13.90 21-NOV-12:00 15.00 14.29 5.20 11.46 134.50 25.50
December -0.0 05-DEC-17:00 0.00 -0.0 1.50 -6.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -0.6 -0.8 1.50 -7.3 0.00 0.00
Maximum of Months 23.90   31.10 25.76 10.80 22.64 333.00 903.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 1.89 11.66 0.00
February 18.00 13.00 16.00 0.58 19.92 0.00
March 18.00 13.00 16.00 0.81 26.63 0.00
April 18.00 13.00 16.00 2.58 37.52 0.00
May 18.00 13.00 16.00 5.43 45.25 0.00
June 18.00 13.00 16.00 8.61 47.76 0.00
July 18.00 13.00 16.00 11.25 48.86 0.00
August 18.00 13.00 16.00 12.66 38.94 0.00
September 18.00 13.00 16.00 12.41 29.23 0.00
October 18.00 13.00 16.00 10.60 17.37 0.00
November 18.00 13.00 16.00 7.72 10.89 0.00
December 18.00 13.00 16.00 4.55 9.11 0.00
             
Annual Sum or Average 18.00 13.00 16.00 6.63 28.63 0.00
Minimum of Months 18.00 13.00 16.00 0.58 9.11 0.00
Maximum of Months 18.00 13.00 16.00 12.66 48.86 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.659792E+09 -580507700.3 0.00 0.00 744.00 0.00 -79284331.3 58.99 0.00 0.00
February 0.608220E+09 -537237823.4 0.00 0.00 672.00 0.00 -70981715.4 58.99 0.00 0.00
March 0.725331E+09 -647667418.4 0.00 0.00 744.00 0.00 -77663763.3 59.00 0.00 0.00
April 0.619668E+09 -546357009.8 0.00 0.00 720.00 0.00 -73311255.2 59.00 0.00 0.00
May 0.641836E+09 -571529278.6 0.00 0.00 744.00 0.00 -70306285.5 58.98 0.00 0.00
June 0.601827E+09 -536063898.8 0.00 0.00 720.00 0.00 -65762723.3 58.99 0.00 0.00
July 0.527482E+09 -461629395.9 0.00 0.00 744.00 0.00 -65852144.3 58.98 0.00 0.00
August 0.582376E+09 -516016050.0 0.00 0.00 744.00 0.00 -66360122.4 59.00 0.00 0.00
September 0.516992E+09 -451314999.1 0.00 0.00 720.00 0.00 -65677403.7 58.98 0.00 0.00
October 0.565510E+09 -492284001.2 0.00 0.00 744.00 0.00 -73226062.3 59.00 0.00 0.00
November 0.595619E+09 -521139205.8 0.00 0.00 720.00 0.00 -74480168.8 58.99 0.00 0.00
December 0.605470E+09 -526555266.8 0.00 0.00 744.00 0.00 -78914270.0 59.00 0.00 0.00
                     
Annual Sum or Average 0.725012E+10 -0.638830E+10 0.00 0.00 8760.00 0.00 -861820245.6 58.99 0.00 0.00
Minimum of Months 0.516992E+09 -647667418.4 0.00 0.00 672.00 0.00 -79284331.3 58.98 0.00 0.00
Maximum of Months 0.725331E+09 -451314999.1 0.00 0.00 744.00 0.00 -65677403.7 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.76 0.73 01-JAN-08:00 739.39 22.83 80.33 189.00 1419.01 30.30 201.33 165.00
February 265.33 0.76 0.73 01-FEB-08:50 1595.38 25.39 121.17 213.83 1866.38 32.22 255.50 208.00
March 254.17 0.76 0.73 02-MAR-10:39 3468.40 28.12 140.33 242.83 652.83 22.65 215.17 181.83
April 296.33 0.78 0.73 01-APR-10:39 599.45 17.21 2.00 234.33 483.08 21.56 219.33 169.33
May 437.50 0.78 0.73 01-MAY-08:00 481.12 17.53 0.00 274.67 363.39 21.87 279.50 208.67
June 401.83 0.78 0.73 01-JUN-08:09 461.00 17.54 0.00 246.17 344.02 21.89 270.33 165.83
July 409.17 0.78 0.73 01-JUL-07:00 504.47 17.93 0.00 271.83 378.54 22.30 293.67 196.83
August 352.83 0.77 0.73 01-AUG-07:00 602.48 18.26 1.33 248.50 460.62 22.61 265.00 194.33
September 344.17 0.77 0.73 01-SEP-07:49 688.90 18.34 12.50 237.33 496.29 22.35 228.17 195.83
October 299.00 0.76 0.73 01-OCT-07:10 1221.71 24.90 143.50 217.83 504.38 22.90 201.50 166.17
November 255.50 0.77 0.73 01-NOV-08:30 733.31 24.85 120.00 166.50 1104.03 29.84 216.67 143.50
December 226.33 0.77 0.73 01-DEC-08:30 653.69 22.61 76.50 138.00 1088.94 31.10 201.83 125.17
                         
Annual Sum or Average 3785.50 0.77     902.08 20.67 697.67 2680.83 690.63 24.50 2848.00 2120.50
Minimum of Months 226.33 0.76 0.73   461.00 17.21 0.00 138.00 344.02 21.56 201.33 125.17
Maximum of Months 437.50 0.78 0.73   3468.40 28.12 143.50 274.67 1866.38 32.22 293.67 208.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.82 0.73 01-JAN-08:39 610.73 20.66 71.83 79.17 286.59 22.26 94.00 36.50
February 265.33 0.81 0.73 01-FEB-08:00 825.70 18.97 48.83 120.67 546.62 24.18 146.33 76.50
March 254.17 0.80 0.73 02-MAR-10:50 1263.37 18.64 39.83 128.50 1002.98 23.28 119.50 92.67
April 296.33 0.80 0.73 01-APR-10:39 453.38 15.19 0.50 155.83 386.82 20.24 129.67 109.50
May 437.50 0.79 0.73 01-MAY-05:49 435.24 16.07 0.00 218.67 366.34 22.12 226.50 159.00
June 401.83 0.79 0.73 01-JUN-05:10 470.29 16.23 0.00 202.83 436.29 22.84 224.83 156.33
July 409.17 0.79 0.73 01-JUL-05:10 479.53 16.45 0.00 207.50 425.77 22.75 237.33 166.00
August 352.83 0.79 0.73 01-AUG-07:49 462.78 16.45 0.00 170.83 378.59 21.31 176.83 121.67
September 344.17 0.80 0.73 01-SEP-06:49 447.43 16.22 8.00 150.33 322.49 20.74 143.67 94.83
October 299.00 0.82 0.73 01-OCT-06:00 899.56 19.33 78.00 110.33 346.54 22.06 127.00 47.83
November 255.50 0.83 0.73 05-NOV-08:09 576.49 19.67 78.33 65.17 203.98 20.98 73.83 21.33
December 226.33 0.83 0.73 01-DEC-08:50 489.61 20.28 68.33 51.50 170.64 18.91 29.50 12.17
                         
Annual Sum or Average 3785.50 0.80     592.55 17.53 393.67 1661.33 404.98 21.87 1729.00 1094.33
Minimum of Months 226.33 0.79 0.73   435.24 15.19 0.00 51.50 170.64 18.91 29.50 12.17
Maximum of Months 437.50 0.83 0.73   1263.37 20.66 78.33 218.67 1002.98 24.18 237.33 166.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.90 0.80 30-JAN-12:30 139.93 12.86 0.00 0.00 100.44 16.98 0.00 0.00
February 265.33 0.88 0.74 26-FEB-12:30 177.32 14.19 0.00 0.00 129.30 18.32 0.00 0.00
March 254.17 0.86 0.74 24-MAR-10:30 194.75 14.78 0.00 2.17 145.04 18.94 5.67 0.00
April 296.33 0.84 0.73 29-APR-08:30 223.27 15.32 0.00 11.17 162.37 19.26 19.83 0.00
May 437.50 0.79 0.73 03-MAY-05:40 326.59 16.90 0.00 108.17 209.71 21.69 142.33 5.00
June 401.83 0.77 0.73 01-JUN-18:10 367.21 19.23 33.17 182.17 268.26 22.98 247.00 18.67
July 409.17 0.77 0.73 01-JUL-09:30 351.62 18.88 27.00 176.33 233.96 21.53 214.67 0.00
August 352.83 0.79 0.73 01-AUG-08:30 303.98 16.87 0.00 59.17 202.49 20.74 113.17 0.00
September 344.17 0.85 0.74 03-SEP-11:30 216.45 15.40 0.00 0.50 152.91 19.30 2.17 0.00
October 299.00 0.88 0.74 07-OCT-11:30 174.33 14.16 0.00 0.00 121.46 18.03 0.00 0.00
November 255.50 0.91 0.82 01-NOV-13:30 134.80 12.69 0.00 0.00 94.40 16.52 0.00 0.00
December 226.33 0.91 0.84 04-DEC-12:20 129.27 12.60 0.00 0.00 90.84 16.54 0.00 0.00
                         
Annual Sum or Average 3785.50 0.84     245.32 15.75 60.17 539.67 170.14 19.64 744.83 23.67
Minimum of Months 226.33 0.77 0.73   129.27 12.60 0.00 0.00 90.84 16.52 0.00 0.00
Maximum of Months 437.50 0.91 0.84   367.21 19.23 33.17 182.17 268.26 22.98 247.00 18.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.82 0.73 01-JAN-14:09 545.49 20.44 65.83 82.50 272.83 22.06 97.33 31.50
February 265.33 0.80 0.73 01-FEB-13:39 825.81 19.27 49.67 123.67 553.86 24.43 151.00 77.00
March 254.17 0.80 0.73 02-MAR-11:30 1222.16 18.91 39.17 133.50 902.54 23.34 131.33 85.83
April 296.33 0.81 0.73 01-APR-11:39 433.83 15.37 0.33 146.67 361.99 20.29 127.33 103.17
May 437.50 0.79 0.73 01-MAY-13:20 436.54 16.21 0.00 220.50 359.84 21.03 205.17 156.17
June 401.83 0.79 0.73 01-JUN-11:30 447.55 16.56 0.00 189.17 377.79 21.53 202.83 136.00
July 409.17 0.79 0.73 01-JUL-13:09 476.87 16.74 0.00 203.83 403.76 21.72 212.17 155.17
August 352.83 0.79 0.73 01-AUG-11:09 493.37 16.83 0.17 182.00 434.00 21.83 187.33 135.17
September 344.17 0.80 0.73 01-SEP-13:20 490.57 16.45 6.67 158.67 688.41 22.76 166.83 105.67
October 299.00 0.81 0.73 01-OCT-11:00 988.42 19.96 81.33 119.67 372.85 22.38 131.33 64.67
November 255.50 0.83 0.73 01-NOV-13:30 525.81 19.54 73.50 65.83 201.56 20.86 75.67 24.67
December 226.33 0.84 0.73 01-DEC-13:20 343.42 18.32 41.67 47.67 170.02 19.02 36.50 10.50
                         
Annual Sum or Average 3785.50 0.80     583.15 17.63 358.33 1673.67 426.89 21.77 1724.83 1085.50
Minimum of Months 226.33 0.79 0.73   343.42 15.37 0.00 47.67 170.02 19.02 36.50 10.50
Maximum of Months 437.50 0.84 0.73   1222.16 20.44 81.33 220.50 902.54 24.43 212.17 156.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.490941E+09 2965.46 17-JAN-13:40 0.00 0.00 0.00 0.00 0.00
February 0.794643E+09 4457.37 21-FEB-08:23 0.00 0.00 0.00 0.00 0.00
March 0.123436E+10 4246.29 28-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.463873E+09 4639.18 24-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 60376971.60 5200.38 03-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.136639E+09 5302.69 31-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.915126E+09 5812.86 01-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.808892E+09 3019.74 28-DEC-12:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.490485E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123436E+10 5812.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110831E+10 3761.41 16-JAN-10:43 0.00 0.00 0.00 0.00 0.00
February 0.129760E+10 5316.02 21-FEB-08:15 0.00 0.00 0.00 0.00 0.00
March 0.232078E+10 5127.53 28-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.155741E+10 7143.41 18-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.371295E+09 6537.83 10-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 9734778.76 5490.67 13-JUN-07:02 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 43258303.88 5446.98 29-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.863171E+09 6620.66 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.202774E+10 6937.77 01-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.147984E+10 3761.73 28-DEC-13:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.110791E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.232078E+10 7143.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.807362E+09 2575.41 29-JAN-16:43 0.00 0.00 0.00 0.00 0.00
February 0.118924E+10 3619.72 21-FEB-08:15 0.00 0.00 0.00 0.00 0.00
March 0.176382E+10 3491.38 28-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.872092E+09 4864.01 18-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 84133679.90 4451.66 10-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 614638.89 1893.46 29-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.391886E+09 4508.06 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.141150E+10 4640.36 01-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.107280E+10 2451.90 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.759344E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176382E+10 4864.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.117414E+10 3303.09 29-JAN-14:05 0.00 0.00 0.00 0.00 0.00
February 0.186601E+10 4712.65 20-FEB-18:13 0.00 0.00 0.00 0.00 0.00
March 0.292604E+10 4322.07 28-MAR-07:23 0.00 0.00 0.00 0.00 0.00
April 0.200519E+10 6155.21 18-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 0.340219E+09 6032.23 16-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 2616950.15 4305.64 29-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.781136E+09 5510.21 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.232434E+10 5841.92 01-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.144566E+10 3126.24 17-DEC-11:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128654E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292604E+10 6155.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.843712E+09 3046.08 16-JAN-10:43 0.00 0.00 0.00 0.00 0.00
February 0.115949E+10 4285.55 21-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.177169E+10 4152.40 28-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.101038E+10 5784.91 18-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.131563E+09 5294.50 10-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 146980.03 702.59 29-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 0.356781E+09 5361.57 31-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.139886E+10 5518.92 01-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.110531E+10 2916.12 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.777793E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177169E+10 5784.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319657E+10 5730.78 01-JAN-10:23 0.00 0.00 0.00 0.00 0.00
February 0.158276E+10 5730.78 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.739070E+09 5730.78 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 55162114.02 5730.78 04-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 3780811.65 5306.54 01-MAY-06:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9188984.32 5730.78 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.168187E+09 5730.78 07-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.202179E+10 5730.78 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.777650E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319657E+10 5730.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.779565E+10 9238.35 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.440263E+10 9238.35 01-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.279360E+10 9238.35 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.444941E+09 9238.35 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 29791561.08 7311.21 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 85113287.60 8360.37 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.945383E+09 9238.35 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.617512E+10 9238.35 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.226722E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779565E+10 9238.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.481911E+10 5766.69 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.269923E+10 5766.69 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.144554E+10 5766.69 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 99783172.04 5766.69 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 3405042.53 5331.62 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 17896368.26 5766.69 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.359863E+09 5766.69 07-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.373425E+10 5766.69 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.131791E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.481911E+10 5766.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.849741E+10 9175.86 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.514240E+10 9175.86 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.319385E+10 9175.86 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.379705E+09 9175.86 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 23520772.18 5654.81 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 49164011.88 6934.99 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.900743E+09 9175.86 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.666771E+10 9175.86 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.248545E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.849741E+10 9175.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.469788E+10 5804.84 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.264292E+10 5804.84 01-FEB-03:53 0.00 0.00 0.00 0.00 0.00
March 0.138889E+10 5804.84 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 87806032.54 5804.84 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 4293993.46 5804.84 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 13160895.33 5804.84 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.285609E+09 5804.84 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.362700E+10 5804.84 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127476E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.469788E+10 5804.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.657192E+09 0.529803E+09 5500.70 26-MAY-07:03 3997.44 0.00
June 0.00 0.00 0.190731E+10 0.144163E+10 5833.31 30-JUN-06:02 3522.16 0.00
July 0.00 0.00 0.269756E+10 0.205070E+10 5798.02 05-JUL-06:03 3175.62 0.00
August 0.00 0.00 0.277324E+10 0.205115E+10 5654.54 30-AUG-07:02 3381.60 0.00
September 0.00 0.00 0.102718E+10 0.843816E+09 5596.10 01-SEP-07:03 3405.31 0.00
October 0.00 0.00 36558497.41 31644137.74 1044.69 20-OCT-15:03 993.06 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.909904E+10 0.694875E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.277324E+10 0.205115E+10 5833.31   3997.44 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 20703335.61 20703335.61 1106.75 13-APR-14:55 1106.75 0.00
May 0.00 0.00 0.501408E+09 0.441796E+09 3818.40 25-MAY-14:20 3211.89 0.00
June 0.00 0.00 0.132281E+10 0.105061E+10 7063.73 30-JUN-06:02 4091.43 0.00
July 0.00 0.00 0.217873E+10 0.174715E+10 6945.68 05-JUL-07:02 3746.72 0.00
August 0.00 0.00 0.235326E+10 0.186908E+10 6803.27 30-AUG-07:02 4052.36 0.00
September 0.00 0.00 0.953694E+09 0.888242E+09 6353.19 01-SEP-13:20 5581.34 0.00
October 0.00 0.00 0.183776E+09 0.181984E+09 3575.43 20-OCT-14:00 3575.43 0.00
November 0.00 0.00 1857079.72 1857079.72 312.64 17-NOV-13:30 312.64 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.751623E+10 0.620143E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.235326E+10 0.186908E+10 7063.73   5581.34 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.299682E+09 0.269813E+09 3516.95 18-MAY-07:02 3308.04 0.00
June 0.00 0.00 0.104861E+10 0.896334E+09 4790.43 30-JUN-06:02 2819.72 0.00
July 0.00 0.00 0.159830E+10 0.136583E+10 4718.95 05-JUL-07:02 2804.05 0.00
August 0.00 0.00 0.137405E+10 0.114036E+10 4637.11 30-AUG-07:02 3067.04 0.00
September 0.00 0.00 0.445732E+09 0.414282E+09 4602.02 01-SEP-07:03 3065.92 0.00
October 0.00 0.00 15240320.90 15088727.62 605.02 20-OCT-14:55 605.02 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.478161E+10 0.410171E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.159830E+10 0.136583E+10 4790.43   3308.04 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.245880E+09 0.204892E+09 2564.69 26-MAY-07:03 1937.67 0.00
June 0.00 0.00 0.100868E+10 0.789990E+09 5854.06 30-JUN-06:02 3413.85 0.00
July 0.00 0.00 0.168445E+10 0.133784E+10 5780.40 05-JUL-07:02 3241.70 0.00
August 0.00 0.00 0.157663E+10 0.121729E+10 5670.58 09-AUG-07:02 3634.75 0.00
September 0.00 0.00 0.343792E+09 0.296780E+09 5586.71 01-SEP-07:03 3534.69 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.485942E+10 0.384680E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.168445E+10 0.133784E+10 5854.06   3634.75 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 847696.98 847696.98 412.33 13-APR-16:00 412.33 0.00
May 0.00 0.00 0.334252E+09 0.295231E+09 5329.68 26-MAY-07:03 4335.73 0.00
June 0.00 0.00 0.901013E+09 0.738877E+09 5706.22 30-JUN-06:02 3555.08 0.00
July 0.00 0.00 0.143678E+10 0.119121E+10 5587.60 05-JUL-07:02 3456.24 0.00
August 0.00 0.00 0.140167E+10 0.114198E+10 5500.88 30-AUG-07:02 3740.07 0.00
September 0.00 0.00 0.426670E+09 0.386502E+09 5469.45 01-SEP-07:03 3673.45 0.00
October 0.00 0.00 25611084.33 25083496.32 1305.64 19-OCT-15:53 1232.03 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.452684E+10 0.377973E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.143678E+10 0.119121E+10 5706.22   4335.73 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 338.90 816.93 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 312.53 827.04 24-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 0.00     52.76    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   338.90 827.04  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.315718E+09 0.37 304.16 01-JAN-00:15 0.97
February 0.270461E+09 0.35 304.16 01-FEB-06:01 0.96
March 0.327400E+09 0.39 304.16 01-MAR-06:01 0.96
April 0.284696E+09 0.35 304.16 03-APR-05:01 0.96
May 0.313166E+09 0.37 304.16 01-MAY-05:01 0.96
June 0.313166E+09 0.38 304.16 01-JUN-05:10 0.95
July 0.284696E+09 0.33 304.16 03-JUL-05:10 0.94
August 0.327400E+09 0.38 304.16 01-AUG-05:10 0.95
September 0.284696E+09 0.34 304.16 01-SEP-05:10 0.94
October 0.298931E+09 0.35 304.16 02-OCT-05:05 0.95
November 0.298931E+09 0.36 304.16 01-NOV-05:10 0.95
December 0.285900E+09 0.34 304.16 01-DEC-06:01 0.96
           
Annual Sum or Average 0.360516E+10 0.36      
Minimum of Months 0.270461E+09 0.33 304.16   0.94
Maximum of Months 0.327400E+09 0.39 304.16   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.701800E+09 0.67 398.44 01-JAN-00:05 0.97
February 0.519532E+09 0.55 398.44 01-FEB-00:03 0.97
March 0.525480E+09 0.50 398.44 01-MAR-06:01 0.96
April 0.385441E+09 0.38 398.44 02-APR-08:43 0.96
May 0.410326E+09 0.37 398.44 01-MAY-05:01 0.96
June 0.410235E+09 0.38 398.44 01-JUN-05:10 0.95
July 0.372941E+09 0.33 398.44 03-JUL-05:10 0.95
August 0.428882E+09 0.38 398.44 01-AUG-05:10 0.95
September 0.372941E+09 0.34 398.44 01-SEP-05:10 0.94
October 0.391588E+09 0.35 398.44 02-OCT-05:05 0.95
November 0.438429E+09 0.42 398.44 01-NOV-05:10 0.96
December 0.615522E+09 0.59 398.44 01-DEC-06:01 0.96
           
Annual Sum or Average 0.557312E+10 0.44      
Minimum of Months 0.372941E+09 0.33 398.44   0.94
Maximum of Months 0.701800E+09 0.67 398.44   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.548079E+09 0.73 290.35 01-JAN-00:05 0.97
February 0.444943E+09 0.68 290.35 01-FEB-00:03 0.96
March 0.425671E+09 0.58 290.35 01-MAR-06:01 0.96
April 0.290595E+09 0.42 290.35 02-APR-02:65 0.96
May 0.299456E+09 0.37 290.35 01-MAY-05:01 0.96
June 0.298944E+09 0.38 290.35 01-JUN-05:10 0.95
July 0.271768E+09 0.33 290.35 03-JUL-05:10 0.95
August 0.312533E+09 0.38 290.35 01-AUG-05:10 0.95
September 0.271768E+09 0.34 290.35 01-SEP-05:10 0.94
October 0.285356E+09 0.35 290.35 02-OCT-05:05 0.95
November 0.340675E+09 0.48 290.35 01-NOV-05:10 0.96
December 0.509121E+09 0.68 290.35 01-DEC-05:45 0.96
           
Annual Sum or Average 0.429891E+10 0.48      
Minimum of Months 0.271768E+09 0.33 290.35   0.94
Maximum of Months 0.548079E+09 0.73 290.35   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.604335E+09 0.72 312.92 01-JAN-00:05 0.97
February 0.496321E+09 0.68 312.92 01-FEB-00:03 0.96
March 0.482587E+09 0.60 312.92 01-MAR-06:01 0.96
April 0.320653E+09 0.42 312.92 02-APR-00:10 0.96
May 0.323625E+09 0.37 312.92 01-MAY-03:35 0.96
June 0.322187E+09 0.38 312.92 01-JUN-05:10 0.95
July 0.292898E+09 0.33 312.92 03-JUL-05:10 0.95
August 0.336832E+09 0.38 312.92 01-AUG-05:10 0.95
September 0.292898E+09 0.34 312.92 01-SEP-05:10 0.94
October 0.307543E+09 0.35 312.92 02-OCT-05:05 0.95
November 0.376473E+09 0.47 312.92 01-NOV-05:10 0.96
December 0.547884E+09 0.66 312.92 01-DEC-06:01 0.96
           
Annual Sum or Average 0.470423E+10 0.47      
Minimum of Months 0.292898E+09 0.33 312.92   0.94
Maximum of Months 0.604335E+09 0.72 312.92   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.645693E+09 0.72 345.32 01-JAN-00:05 0.97
February 0.514918E+09 0.67 345.32 01-FEB-00:03 0.96
March 0.495386E+09 0.58 345.32 01-MAR-06:01 0.96
April 0.340651E+09 0.42 345.32 02-APR-08:43 0.96
May 0.356258E+09 0.37 345.32 01-MAY-05:01 0.96
June 0.355543E+09 0.38 345.32 01-JUN-05:10 0.95
July 0.323411E+09 0.33 345.32 03-JUL-05:10 0.95
August 0.371705E+09 0.38 345.32 01-AUG-05:10 0.95
September 0.323221E+09 0.34 345.32 01-SEP-05:10 0.94
October 0.339382E+09 0.35 345.32 02-OCT-05:05 0.95
November 0.398101E+09 0.48 345.32 01-NOV-05:10 0.96
December 0.594183E+09 0.67 345.32 01-DEC-05:45 0.96
           
Annual Sum or Average 0.505845E+10 0.47      
Minimum of Months 0.323221E+09 0.33 345.32   0.94
Maximum of Months 0.645693E+09 0.72 345.32   0.97



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:03 0.00 0.00 38.07 0.00
February 0.02 0.00 0.00 01-FEB-07:02 0.00 0.00 0.98 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.42 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.42 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 0.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.42 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.42 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.42 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.42 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.42 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00 0.42 0.00
                 
Annual Sum or Average 0.04 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.42 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 38.07 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 48.89 48.89 338.90 816.93 31-JAN-12:20
February 0.00 0.00 01-FEB-00:03 0.99 0.99 312.53 827.04 24-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.42 0.42 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.42 0.42 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:05 0.42 0.42 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.42 0.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.42 0.42 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.42 0.42 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.42 0.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.42 0.42 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.42 0.42 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 0.42 0.42 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 0.00         52.76    
Minimum of Months 0.00 0.00   0.42 0.42 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 338.90 827.04  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.632643E+09 0.00 0.00
February 0.00 0.00 0.00 0.684627E+09 0.00 0.00
March 0.00 0.00 0.00 0.100173E+10 0.00 0.00
April 0.00 0.00 0.00 0.511532E+09 0.00 0.00
May 0.00 0.00 0.00 0.470420E+09 0.00 0.00
June 0.00 0.00 0.00 0.689386E+09 0.00 0.00
July 0.00 0.00 0.00 0.800600E+09 0.00 0.00
August 0.00 0.00 0.00 0.855314E+09 0.00 0.00
September 0.00 0.00 0.00 0.486630E+09 0.00 0.00
October 0.00 0.00 0.00 0.381466E+09 0.00 0.00
November 0.00 0.00 0.00 0.778818E+09 0.00 0.00
December 0.00 0.00 0.00 0.789049E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.808221E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.381466E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.100173E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.139754E+10 0.00 0.00
February 0.00 0.00 0.00 0.121926E+10 0.00 0.00
March 0.00 0.00 0.00 0.172957E+10 0.00 0.00
April 0.00 0.00 0.00 0.106767E+10 0.00 0.00
May 0.00 0.00 0.00 0.643603E+09 0.00 0.00
June 0.00 0.00 0.00 0.684681E+09 0.00 0.00
July 0.00 0.00 0.00 0.806787E+09 0.00 0.00
August 0.00 0.00 0.00 0.889541E+09 0.00 0.00
September 0.00 0.00 0.00 0.573371E+09 0.00 0.00
October 0.00 0.00 0.00 0.794307E+09 0.00 0.00
November 0.00 0.00 0.00 0.141406E+10 0.00 0.00
December 0.00 0.00 0.00 0.152519E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.127456E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.573371E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.172957E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.108103E+10 0.00 0.00
February 0.00 0.00 0.00 0.109597E+10 0.00 0.00
March 0.00 0.00 0.00 0.136384E+10 0.00 0.00
April 0.00 0.00 0.00 0.701603E+09 0.00 0.00
May 0.00 0.00 0.00 0.395430E+09 0.00 0.00
June 0.00 0.00 0.00 0.514071E+09 0.00 0.00
July 0.00 0.00 0.00 0.589271E+09 0.00 0.00
August 0.00 0.00 0.00 0.585949E+09 0.00 0.00
September 0.00 0.00 0.00 0.361969E+09 0.00 0.00
October 0.00 0.00 0.00 0.468481E+09 0.00 0.00
November 0.00 0.00 0.00 0.105205E+10 0.00 0.00
December 0.00 0.00 0.00 0.119664E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.940631E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.361969E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.136384E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.132408E+10 0.00 0.00
February 0.00 0.00 0.00 0.143981E+10 0.00 0.00
March 0.00 0.00 0.00 0.193010E+10 0.00 0.00
April 0.00 0.00 0.00 0.115175E+10 0.00 0.00
May 0.00 0.00 0.00 0.494412E+09 0.00 0.00
June 0.00 0.00 0.00 0.530035E+09 0.00 0.00
July 0.00 0.00 0.00 0.630401E+09 0.00 0.00
August 0.00 0.00 0.00 0.651283E+09 0.00 0.00
September 0.00 0.00 0.00 0.364042E+09 0.00 0.00
October 0.00 0.00 0.00 0.639019E+09 0.00 0.00
November 0.00 0.00 0.00 0.147245E+10 0.00 0.00
December 0.00 0.00 0.00 0.143269E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.120601E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.364042E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.193010E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.120760E+10 0.00 0.00
February 0.00 0.00 0.00 0.116916E+10 0.00 0.00
March 0.00 0.00 0.00 0.145924E+10 0.00 0.00
April 0.00 0.00 0.00 0.808049E+09 0.00 0.00
May 0.00 0.00 0.00 0.476648E+09 0.00 0.00
June 0.00 0.00 0.00 0.544376E+09 0.00 0.00
July 0.00 0.00 0.00 0.616103E+09 0.00 0.00
August 0.00 0.00 0.00 0.654627E+09 0.00 0.00
September 0.00 0.00 0.00 0.410455E+09 0.00 0.00
October 0.00 0.00 0.00 0.513602E+09 0.00 0.00
November 0.00 0.00 0.00 0.112504E+10 0.00 0.00
December 0.00 0.00 0.00 0.131356E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.102985E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.410455E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.145924E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.315718E+09 0.00 0.368751E+10 0.00 0.00 0.00 0.00 0.00
February 0.270461E+09 0.00 0.237740E+10 0.00 0.00 0.00 0.00 0.00
March 0.327400E+09 0.00 0.197343E+10 0.00 0.00 0.00 0.00 0.00
April 0.284696E+09 0.00 0.519035E+09 0.00 0.00 0.00 0.00 0.00
May 0.313166E+09 0.657192E+09 64157783.25 0.00 0.00 0.00 0.00 0.00
June 0.313166E+09 0.190731E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.284696E+09 0.269756E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.327400E+09 0.277324E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.284696E+09 0.102718E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.298931E+09 36558497.41 0.145828E+09 0.00 0.00 0.00 0.00 0.00
November 0.298931E+09 0.00 0.108331E+10 0.00 0.00 0.00 0.00 0.00
December 0.285900E+09 0.00 0.283068E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.360516E+10 0.909904E+10 0.126814E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.270461E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.327400E+09 0.277324E+10 0.368751E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.701800E+09 0.00 0.890396E+10 0.00 0.00 0.00 0.00 0.00
February 0.519532E+09 0.00 0.570023E+10 0.00 0.00 0.00 0.00 0.00
March 0.525480E+09 0.00 0.511439E+10 0.00 0.00 0.00 0.00 0.00
April 0.385441E+09 20703335.61 0.200235E+10 0.00 0.00 0.00 0.00 0.00
May 0.410326E+09 0.501408E+09 0.401086E+09 0.00 0.00 0.00 0.00 0.00
June 0.410235E+09 0.132281E+10 9734778.76 0.00 0.00 0.00 0.00 0.00
July 0.372941E+09 0.217873E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.428882E+09 0.235326E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.372941E+09 0.953694E+09 43258303.88 0.00 0.00 0.00 0.00 0.00
October 0.391588E+09 0.183776E+09 0.948285E+09 0.00 0.00 0.00 0.00 0.00
November 0.438429E+09 1857079.72 0.297312E+10 0.00 0.00 0.00 0.00 0.00
December 0.615522E+09 0.00 0.765497E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.557312E+10 0.751623E+10 0.337514E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.372941E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.701800E+09 0.235326E+10 0.890396E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.548079E+09 0.00 0.562647E+10 0.00 0.00 0.00 0.00 0.00
February 0.444943E+09 0.00 0.388847E+10 0.00 0.00 0.00 0.00 0.00
March 0.425671E+09 0.00 0.320936E+10 0.00 0.00 0.00 0.00 0.00
April 0.290595E+09 0.00 0.971875E+09 0.00 0.00 0.00 0.00 0.00
May 0.299456E+09 0.299682E+09 87538722.42 0.00 0.00 0.00 0.00 0.00
June 0.298944E+09 0.104861E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271768E+09 0.159830E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.312533E+09 0.137405E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.271768E+09 0.445732E+09 614638.89 0.00 0.00 0.00 0.00 0.00
October 0.285356E+09 15240320.90 0.409782E+09 0.00 0.00 0.00 0.00 0.00
November 0.340675E+09 0.00 0.177136E+10 0.00 0.00 0.00 0.00 0.00
December 0.509121E+09 0.00 0.480705E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.429891E+10 0.478161E+10 0.207725E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.271768E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.548079E+09 0.159830E+10 0.562647E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.604335E+09 0.00 0.967155E+10 0.00 0.00 0.00 0.00 0.00
February 0.496321E+09 0.00 0.700841E+10 0.00 0.00 0.00 0.00 0.00
March 0.482587E+09 0.00 0.611989E+10 0.00 0.00 0.00 0.00 0.00
April 0.320653E+09 0.00 0.238489E+10 0.00 0.00 0.00 0.00 0.00
May 0.323625E+09 0.245880E+09 0.363739E+09 0.00 0.00 0.00 0.00 0.00
June 0.322187E+09 0.100868E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.292898E+09 0.168445E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.336832E+09 0.157663E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.292898E+09 0.343792E+09 2616950.15 0.00 0.00 0.00 0.00 0.00
October 0.307543E+09 0.00 0.830300E+09 0.00 0.00 0.00 0.00 0.00
November 0.376473E+09 0.00 0.322509E+10 0.00 0.00 0.00 0.00 0.00
December 0.547884E+09 0.00 0.811337E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.470423E+10 0.485942E+10 0.377199E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.292898E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.604335E+09 0.168445E+10 0.967155E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.645693E+09 0.00 0.554159E+10 0.00 0.00 0.00 0.00 0.00
February 0.514918E+09 0.00 0.380241E+10 0.00 0.00 0.00 0.00 0.00
March 0.495386E+09 0.00 0.316058E+10 0.00 0.00 0.00 0.00 0.00
April 0.340651E+09 847696.98 0.109818E+10 0.00 0.00 0.00 0.00 0.00
May 0.356258E+09 0.334252E+09 0.135857E+09 0.00 0.00 0.00 0.00 0.00
June 0.355543E+09 0.901013E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.323411E+09 0.143678E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.371705E+09 0.140167E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.323221E+09 0.426670E+09 146980.03 0.00 0.00 0.00 0.00 0.00
October 0.339382E+09 25611084.33 0.369942E+09 0.00 0.00 0.00 0.00 0.00
November 0.398101E+09 0.00 0.168447E+10 0.00 0.00 0.00 0.00 0.00
December 0.594183E+09 0.00 0.473232E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.505845E+10 0.452684E+10 0.205255E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.323221E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.645693E+09 0.143678E+10 0.554159E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.315718E+09 0.00 0.00 0.316925E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.270461E+09 0.00 0.00 0.414166E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.327400E+09 0.00 0.00 0.674330E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.284696E+09 0.00 0.00 0.226836E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.313166E+09 0.00 0.00 24003194.81 0.133251E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.313166E+09 0.00 0.00 0.00 0.376221E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.284696E+09 0.00 0.00 0.00 0.515904E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.327400E+09 0.00 0.00 0.00 0.527914E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.284696E+09 0.00 0.00 743265.30 0.201191E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.298931E+09 0.00 0.00 75009195.91 7525515.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.298931E+09 0.00 0.00 0.479887E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.285900E+09 0.00 0.00 0.503148E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.360516E+10 0.00 0.00 0.271505E+10 0.176201E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.270461E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.327400E+09 0.00 0.00 0.674330E+09 0.527914E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.701800E+09 0.00 0.00 0.695741E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.519532E+09 0.00 0.00 0.699728E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.525480E+09 0.00 0.00 0.120409E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.385441E+09 0.00 0.00 0.677988E+09 4240705.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.410326E+09 0.00 0.00 0.128411E+09 0.104865E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.410235E+09 0.00 0.00 3044362.48 0.271402E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.372941E+09 0.00 0.00 0.00 0.433846E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.428882E+09 0.00 0.00 0.00 0.460659E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.372941E+09 0.00 0.00 15464412.35 0.184966E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.391588E+09 0.00 0.00 0.366462E+09 36256889.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.438429E+09 0.00 0.00 0.975243E+09 385260.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.615522E+09 0.00 0.00 0.909666E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.557312E+10 0.00 0.00 0.567584E+10 0.149662E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.372941E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.701800E+09 0.00 0.00 0.120409E+10 0.460659E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.548079E+09 0.00 0.00 0.532950E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.444943E+09 0.00 0.00 0.651031E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.425671E+09 0.00 0.00 0.938166E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.290595E+09 0.00 0.00 0.411008E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.299456E+09 0.00 0.00 33035627.30 62938716.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.298944E+09 0.00 0.00 0.00 0.215127E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271768E+09 0.00 0.00 0.00 0.317504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.312533E+09 0.00 0.00 0.00 0.273417E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.271768E+09 0.00 0.00 956913.74 89244718.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.285356E+09 0.00 0.00 0.179974E+09 3151784.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.340675E+09 0.00 0.00 0.711378E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.509121E+09 0.00 0.00 0.687519E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.429891E+10 0.00 0.00 0.414602E+10 0.961382E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.271768E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.548079E+09 0.00 0.00 0.938166E+09 0.317504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.604335E+09 0.00 0.00 0.719746E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.496321E+09 0.00 0.00 0.943493E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.482587E+09 0.00 0.00 0.144752E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.320653E+09 0.00 0.00 0.831093E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.323625E+09 0.00 0.00 0.118853E+09 51934661.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.322187E+09 0.00 0.00 0.00 0.207847E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.292898E+09 0.00 0.00 0.00 0.337504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.336832E+09 0.00 0.00 0.00 0.314451E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.292898E+09 0.00 0.00 1588390.87 69555545.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.307543E+09 0.00 0.00 0.331477E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.376473E+09 0.00 0.00 0.109598E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.547884E+09 0.00 0.00 0.884810E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.470423E+10 0.00 0.00 0.637456E+10 0.981292E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.292898E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.604335E+09 0.00 0.00 0.144752E+10 0.337504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.645693E+09 0.00 0.00 0.561910E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.514918E+09 0.00 0.00 0.654239E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.495386E+09 0.00 0.00 0.963855E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.340651E+09 0.00 0.00 0.467222E+09 175528.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.356258E+09 0.00 0.00 49716275.10 70674309.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.355543E+09 0.00 0.00 0.00 0.188833E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.323411E+09 0.00 0.00 0.00 0.292692E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.371705E+09 0.00 0.00 0.00 0.282923E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.323221E+09 0.00 0.00 801305.68 86432453.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.339382E+09 0.00 0.00 0.168958E+09 5261961.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.398101E+09 0.00 0.00 0.726935E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.594183E+09 0.00 0.00 0.719376E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.505845E+10 0.00 0.00 0.431301E+10 0.926992E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.323221E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.645693E+09 0.00 0.00 0.963855E+09 0.292692E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.506506E+09 0.00 0.00 0.00 0.00 0.298840E+10 0.00 0.00 0.20
February 0.750800E+09 0.00 0.00 0.00 0.00 0.184534E+10 0.00 0.00 0.19
March 0.119371E+10 0.00 0.00 0.00 0.00 0.145832E+10 0.00 0.00 0.21
April 0.128813E+10 0.00 0.00 0.00 0.00 0.352115E+09 0.00 0.00 0.19
May 0.711726E+09 8679091.79 0.00 1753331.08 779384.32 56144141.07 0.297920E+09 0.00 0.20
June 0.231621E+09 0.152991E+09 0.00 3940508.08 12628096.03 0.00 0.371180E+09 0.00 0.21
July 0.136900E+09 0.184617E+09 0.00 5406688.78 12496429.77 0.00 0.170602E+09 0.00 0.18
August 0.192771E+09 0.139521E+09 0.00 5924593.19 11793398.15 0.00 0.277929E+09 0.00 0.21
September 0.426786E+09 2972274.07 0.00 4179339.04 44815.54 0.00 0.728102E+09 0.00 0.19
October 0.149807E+10 0.00 0.00 256749.30 0.00 55559324.05 0.183548E+09 0.00 0.19
November 0.128644E+10 0.00 0.00 0.00 0.00 0.759337E+09 0.00 0.00 0.20
December 0.741989E+09 0.00 0.00 0.00 0.00 0.221789E+10 0.00 0.00 0.18
                   
Annual Sum or Average 0.896546E+10 0.488780E+09 0.00 21461209.48 37742123.81 0.973311E+10 0.202928E+10 0.00 0.19
Minimum of Months 0.136900E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.149807E+10 0.184617E+09 0.00 5924593.19 12628096.03 0.298840E+10 0.728102E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 48211770.56 0.00 0.00 0.00 0.00 0.366493E+10 0.00 0.00 0.33
February 99635927.50 0.00 0.00 0.00 0.00 0.234300E+10 0.00 0.00 0.27
March 0.138845E+09 0.00 0.00 0.00 0.00 0.195876E+10 0.00 0.00 0.25
April 0.215509E+09 0.00 0.00 61012.68 0.00 0.729903E+09 24977223.96 0.00 0.19
May 0.279912E+09 18410408.42 0.00 424855.58 1447618.19 0.157873E+09 41938975.40 0.00 0.20
June 0.184334E+09 0.122136E+09 0.00 1325147.89 8271320.13 6292672.84 92398660.06 0.00 0.21
July 92521339.54 0.156057E+09 0.00 2553279.17 8402463.27 0.00 73966267.28 0.00 0.18
August 0.144114E+09 0.130963E+09 0.00 3080398.97 7151005.70 0.00 0.131750E+09 0.00 0.21
September 0.375107E+09 6973453.00 0.00 2933612.74 110157.01 32389252.34 0.206877E+09 0.00 0.19
October 0.407754E+09 0.00 0.00 700570.46 0.00 0.457760E+09 89327920.50 0.00 0.19
November 0.204524E+09 0.00 0.00 15325.60 200698.33 0.118577E+10 9052420.74 0.00 0.22
December 3883810.61 0.00 0.00 0.00 0.00 0.309488E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.219435E+10 0.434540E+09 0.00 11094203.09 25583262.63 0.136316E+11 0.670289E+09 0.00 0.23
Minimum of Months 3883810.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.407754E+09 0.156057E+09 0.00 3080398.97 8402463.27 0.366493E+10 0.206877E+09 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4066195.63 0.00 0.00 0.00 0.00 0.237431E+10 0.00 0.00 0.35
February 4545226.56 0.00 0.00 0.00 0.00 0.167831E+10 0.00 0.00 0.32
March 7824791.39 0.00 0.00 0.00 0.00 0.137880E+10 0.00 0.00 0.28
April 0.142844E+09 0.00 0.00 0.00 0.00 0.460176E+09 0.00 0.00 0.20
May 0.211655E+09 15020634.67 0.00 486377.37 1016577.30 59870034.40 27340979.59 0.00 0.20
June 87047554.09 94769000.84 0.00 1881632.44 7584675.03 0.00 85291595.89 0.00 0.21
July 43507207.63 0.129956E+09 0.00 2495796.91 8489333.63 0.00 41090144.35 0.00 0.18
August 72462442.30 0.100898E+09 0.00 2120598.11 8606387.09 0.00 78682342.98 0.00 0.21
September 0.243389E+09 5176058.08 0.00 1601648.74 230293.41 224831.97 0.137601E+09 0.00 0.19
October 0.278764E+09 0.00 0.00 45186.81 0.00 0.279719E+09 11244163.42 0.00 0.19
November 35925582.31 0.00 0.00 0.00 78407.59 0.860464E+09 0.00 0.00 0.23
December 4252292.16 0.00 0.00 0.00 0.00 0.208349E+10 0.00 0.00 0.33
                   
Annual Sum or Average 0.113628E+10 0.345819E+09 0.00 8631240.38 26005674.05 0.917536E+10 0.381251E+09 0.00 0.24
Minimum of Months 4066195.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.278764E+09 0.129956E+09 0.00 2495796.91 8606387.09 0.237431E+10 0.137601E+09 0.00 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6616285.32 0.00 0.00 0.00 0.00 0.409427E+10 0.00 0.00 0.36
February 6489264.63 0.00 0.00 0.00 0.00 0.292997E+10 0.00 0.00 0.33
March 8191519.74 0.00 0.00 0.00 0.00 0.246561E+10 0.00 0.00 0.29
April 47693682.54 0.00 0.00 0.00 0.00 0.101571E+10 0.00 0.00 0.20
May 0.328213E+09 11182266.83 0.00 240449.00 1491952.98 0.170202E+09 23128529.44 0.00 0.20
June 0.215808E+09 0.126102E+09 0.00 1106531.45 13288700.43 0.00 0.117167E+09 0.00 0.21
July 89300482.12 0.160138E+09 0.00 2420002.47 13468241.13 0.00 86287241.25 0.00 0.18
August 0.129829E+09 0.119912E+09 0.00 2608173.05 13184065.79 0.00 0.161013E+09 0.00 0.21
September 0.506086E+09 4002055.79 0.00 911041.62 250759.84 810874.29 0.169018E+09 0.00 0.19
October 0.452651E+09 0.00 0.00 0.00 0.00 0.532112E+09 0.00 0.00 0.19
November 46555634.25 0.00 0.00 0.00 110894.23 0.154745E+10 0.00 0.00 0.24
December 7000697.46 0.00 0.00 0.00 0.00 0.354071E+10 0.00 0.00 0.33
                   
Annual Sum or Average 0.184443E+10 0.421335E+09 0.00 7286197.59 41794614.39 0.162969E+11 0.556613E+09 0.00 0.24
Minimum of Months 6489264.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.506086E+09 0.160138E+09 0.00 2608173.05 13468241.13 0.409427E+10 0.169018E+09 0.00 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4128106.33 0.00 0.00 0.00 0.00 0.238737E+10 0.00 0.00 0.35
February 17991951.94 0.00 0.00 0.00 0.00 0.165441E+10 0.00 0.00 0.31
March 47986858.05 0.00 0.00 0.00 0.00 0.134136E+10 0.00 0.00 0.27
April 0.124483E+09 0.00 0.00 1217.99 0.00 0.492912E+09 478373.77 0.00 0.19
May 0.224563E+09 11348336.05 0.00 345785.49 676801.29 69228198.75 28324737.84 0.00 0.20
June 0.106900E+09 87361554.92 0.00 929663.68 7306584.83 0.00 86528358.59 0.00 0.21
July 49184340.70 0.112618E+09 0.00 1852814.92 7442879.07 0.00 47806021.52 0.00 0.18
August 71326891.38 88851675.43 0.00 1934446.50 7876716.27 0.00 88285894.39 0.00 0.21
September 0.258317E+09 3311900.61 0.00 1147071.56 158399.65 144802.21 0.150863E+09 0.00 0.19
October 0.310204E+09 0.00 0.00 80670.60 0.00 0.272315E+09 20801659.40 0.00 0.19
November 61214344.57 0.00 0.00 0.00 58982.97 0.844167E+09 0.00 0.00 0.23
December 4089882.85 0.00 0.00 0.00 0.00 0.208393E+10 0.00 0.00 0.32
                   
Annual Sum or Average 0.128039E+10 0.303492E+09 0.00 6291670.74 23520364.09 0.914584E+10 0.423088E+09 0.00 0.24
Minimum of Months 4089882.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.310204E+09 0.112618E+09 0.00 1934446.50 7876716.27 0.238737E+10 0.150863E+09 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:30:16

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.242149E+11 0.307751E+10 0.00 0.252880E+11 0.587997E+10
February 0.436907E+11 0.310855E+10 0.00 0.197699E+11 0.140545E+10
March 0.689862E+11 0.391014E+10 0.00 0.188233E+11 -0.211196E+10
April 0.943355E+11 0.372698E+10 0.00 0.117449E+11 -0.277076E+10
May 0.115453E+12 0.410336E+10 0.00 0.925465E+10 0.188898E+10
June 0.120300E+12 0.329892E+10 0.00 0.445857E+10 0.744701E+10
July 0.123456E+12 0.278806E+10 0.00 0.357117E+10 0.114933E+11
August 0.101143E+12 0.255433E+10 0.00 0.518993E+10 0.113382E+11
September 0.710643E+11 0.231523E+10 0.00 0.973598E+10 0.382073E+10
October 0.356345E+11 0.167189E+10 0.00 0.135270E+11 -857219594.9
November 0.123598E+11 0.152162E+10 0.00 0.157482E+11 -0.310885E+10
December 0.135828E+11 0.260726E+10 0.00 0.240385E+11 0.361324E+10
           
Annual Sum or Average 0.824221E+12 0.346838E+11 0.00 0.161150E+12 0.380381E+11
Minimum of Months 0.123598E+11 0.152162E+10 0.00 0.357117E+10 -0.310885E+10
Maximum of Months 0.123456E+12 0.410336E+10 0.00 0.252880E+11 0.114933E+11