Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:28:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2104.78 | 4117.72 | 4117.72 |
Net Site Energy | 2104.78 | 4117.72 | 4117.72 |
Total Source Energy | 5184.88 | 10143.49 | 10143.49 |
Net Source Energy | 5184.88 | 10143.49 | 10143.49 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 543.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.36 | 241.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1393.80 | 710.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 543.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 66.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 156.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.36 | 241.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 543.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 66.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 156.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.36 | 241.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 56.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 217.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1519.34 | 471.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 990.02 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2726.78 | 1390.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 217.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1519.34 | 471.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 990.02 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2726.78 | 1390.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1393.804 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1393.804 | 100.00 |
Total On-Site and Utility Electric Sources | 1393.804 | 100.00 |
Total Electricity End Uses | 1393.804 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1813.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6902.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 8.5664 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6055 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 8.5664 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6055 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.8498 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:00 | 07-JAN-11:20 | - | - | - | - | - | - | - | - | - | - | 15-FEB-07:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52341.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22750.50 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9875.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2993.63 | 16649.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1768.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 92769.83 | 42897.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52341.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9875.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2993.63 | 16649.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 498.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1722.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 210.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 141.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 497.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.67 | 261.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 177.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4414.18 | 770.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 411.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 972.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.92 | 511.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 347.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8635.72 | 1507.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 411.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 972.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.92 | 511.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 347.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8635.72 | 1507.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.61 |
KITCHEN DIRECT AIR | 1.69 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.61 | 4.61 | 4.61 | 4.61 | 4.61 | 4.61 | 1.00 | 0.999927 | 4.61 |
PSZ-AC_2:2 | 1.69 | 1.69 | 1.69 | 1.69 | 1.69 | 1.69 | 1.00 | 1.000000 | 1.69 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.61 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.69 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.61 | 7817.08 |
PSZ-AC_2:2_ADDAQ FAN | 1.69 | 1806.54 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.61 | 4.61 | 4.61 | 3.04 | 114478.98 | 119293.52 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.69 | 1.69 | 1.69 | 1.11 | 41923.98 | 62982.00 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.61 | 2.31 | 3.07 | 114478.98 | 57239.49 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.69 | 0.844139 | 1.13 | 41923.98 | 20961.99 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 119293.52 |
PSZ-AC_2:2 HEATING COIL | 62982.00 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 8.566 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 73.494 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.605 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1070.246 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3184.542 | 8.566 | 11.368 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3184.542 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1339.051 | 9.605 | 177.878 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1339.051 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.6398E-004 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.5401E-003 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.9084E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.2416E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.2221E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.7749E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.8584E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.2816E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.1755E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1082E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.2679E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1900E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.5681E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.5307E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.4376E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.4378E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.3404E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.2741E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.8212E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.2493E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.1767E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8126E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.2816E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8584E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 52636.09822 | 63163.31786 | 3.84144 | 4.60973 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 1364.02548 | 1636.83057 | 5.84942E-002 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 12.70000 | 9.15345E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22730.56199 | 27276.67439 | 1.40690 | 1.68828 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 12.70000 | 9.15345E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 92654.41 | 4.61007 | 4.61007 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43959.14 | 1.33138 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 50511.01 | 1.68828 | 1.68828 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 40182.71 | 1.21700 | 1.21700 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60973 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.68828 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60973 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60973 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60973 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60973 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.61007 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.61007 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99993 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.68828 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.68828 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.68828 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.68828 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.68828 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.68828 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.61007 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.68828 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.61007 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.61007 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7817.08278 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.61007 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.61007 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.61007 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.04265 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.61007 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.30503 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.07338 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 114478.98000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 57239.49000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 114478.98000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 119293.52356 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 119293.52356 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.68828 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.68828 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1806.53807 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.68828 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.68828 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.68828 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11426 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.68828 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.84414 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12552 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41923.98000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20961.99000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41923.98000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62982.00413 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 62982.00413 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 111202.3 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40724.0 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.6376153125E-002 | 0.2043663514 | Pass | Pass | 3.3652314838E-002 | 9.3001881042E-002 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2063772240 | 0.5719758651 | Pass | Pass | 7.0684437010E-002 | 0.3263706583 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3222080101 | 0.2546332813 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 981.30 | -67.3 | -693.4 | 30.39 | 2839.39 | 3090.39 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 8.5664 | 371.75 | 3184.54 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.14 | 0.0000 | Y | 47.31 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6055 | 139.41 | 1339.05 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.17 |
Interior Lighting Total | 8.8498 | 511.15 | 4523.59 | 66.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3184.54 | 796.14 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3184.54 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 158.08 | AstronomicalClock | - | 48.85 | 48.85 | 1.45 | |
EXTERIOR_LIGHTS_B | 3137.97 | AstronomicalClock | - | 83.85 | 73.35 | 43.21 | |
Exterior Lighting Total | 3296.05 | 44.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 114478.98 | 80258.92 | 34220.06 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41923.98 | 29392.06 | 12531.92 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 111202.3 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 40724.0 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 119293.52 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 62982.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.61 | 7817.08 | 1695.65 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.69 | 1806.54 | 1070.05 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 52636.10 | 63163.32 | 169.91 | 3.841 | 4.610 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00867 | 42.70 | 0.01078 | 1.331 | 0.00 |
KITCHEN | 22730.56 | 27276.67 | 195.66 | 1.407 | 1.688 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.00873 | 41.93 | 0.01078 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 1364.03 | 1636.83 | 4.40 | 0.058 | 1.331 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 28.33 | 0.00678 | 12.70 | 0.00915 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.61 | 4.61 | 1.33 | 1.33 | 4.6101 | 4.6097 | 4.6101 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.69 | 1.69 | 1.22 | 1.22 | 1.6883 | 1.6883 | 1.6883 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 114478.980 | 80258.923 | 4.610070 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 57239.49 | 44838.15 | 3.073380 | 29.42 | 18.86 | 0.00927939 | 11.42 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 43.3196 | 23.99 | 0.00866930 | 46.6684 | 52635.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 119293.524 | 119293.524 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 119293.52 | 119293.52 | 4.610069 | 18.60 | 14.36 | 0.00845921 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 28.8798 | 21.00 | 0.00817730 | 52.8233 | 1360.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41923.980 | 29392.064 | 1.688280 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 20961.99 | 16419.07 | 1.125520 | 38.64 | 22.38 | 0.01027403 | 11.93 | 10.17 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 108.1280 | 25.99 | 0.00872738 | 41.6998 | 22730.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 62982.004 | 62982.004 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 62982.00 | 62982.00 | 1.688279 | 9.15 | 9.15 | 0.00848977 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 72.0854 | 28.33 | 0.00677592 | 28.3004 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 114478.980 | 80258.923 | 4.610070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0899 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.610069 | 5.54865538 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 57239.49 | 44838.15 | 1.0000 | 3.69910474 | 3.073380 | 29.42 | 18.86 | 0.00927939 | 53274.8 | 11.42 | 9.95 | 0.00700000 | 29132.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57239.49 | 42.80 | 0.01078182 | 23.86 | 1.33137743 | 43.3196 | 23.98 | 0.00866930 | 23.99 | 0.00866930 | 46.6684 | 52635.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 119293.524 | 119293.524 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.610069 | 5.54865538 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | Sensible | 119293.52 | 119293.52 | 1.0000 | 5.54865538 | 4.610069 | 18.60 | 14.36 | 0.00845921 | 40141.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 119293.52 | 12.70 | 0.00915345 | 12.70 | 1.33137743 | 28.8798 | 21.00 | 0.00817730 | 21.00 | 0.00817730 | 52.8233 | 1360.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41923.980 | 29392.064 | 1.688280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9389 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.688279 | 2.03200384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 20961.99 | 16419.07 | 1.0000 | 1.35467022 | 1.125520 | 38.64 | 22.38 | 0.01027403 | 65254.6 | 11.93 | 10.17 | 0.00700000 | 29651.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20961.99 | 42.80 | 0.01078182 | 23.86 | 1.21700195 | 108.1280 | 25.95 | 0.00872738 | 25.99 | 0.00872738 | 41.6998 | 22730.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62982.004 | 62982.004 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.688279 | 2.03200384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 62982.00 | 62982.00 | 1.0000 | 2.03200384 | 1.688279 | 9.15 | 9.15 | 0.00848977 | 30576.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62982.00 | 12.70 | 0.00915345 | 12.70 | 1.21700195 | 72.0854 | 0.00 | 0.00677592 | 28.33 | 0.00677592 | 28.3004 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6915.67 | 2910.50 | 2759.67 |
KITCHEN | 7182.67 | 6902.83 | 6902.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7182.67 | 7053.33 | 6902.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 40.33 | 0.00 | 40.33 |
KITCHEN | 0.00 | 2152.00 | 0.00 | 1813.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2152.00 | 0.00 | 1813.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.370 | 0.880 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.412 | 0.028 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.236 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.509 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35039233.78 | 0.00 | 35039233.78 | 7007285.43 | 42046519.20 | 41986318.57 | 1457.64 | 7302.36 | 0.00 | 138.52 |
KITCHEN | 32348739.90 | 0.00 | 32348739.90 | 118319.23 | 32467059.13 | 38379373.44 | 4429.79 | 4264.12 | 66.10 | 1083.60 |
Total Facility | 67387973.67 | 0.00 | 67387973.67 | 7125604.66 | 74513578.33 | 80365692.01 | 4500.76 | 7308.44 | 66.10 | 1094.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3316 | 0.0000 | 1.3316 | 0.2685 | 1.6001 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1773 | 0.0000 | 1.1773 | 0.0031 | 1.1804 | 1.2170 | 2955.36 | 4231.64 | 0.00 |
Total Facility | 2.5089 | 0.0000 | 2.5089 | 0.2716 | 2.7805 | 2.5484 | 2955.36 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50756159.24 | 0.00 | 50756159.24 | 41986318.57 | 1455.44 | 0.41 | 7304.15 | 138.52 |
PSZ-AC_2:2 | 46860933.96 | 0.00 | 46860933.96 | 38379373.44 | 1311.48 | 4.27 | 7444.25 | 1083.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.7055 | 0.0000 | 1.7055 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 23.21 | 0.00 | 7302.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 5674.95 | 2595.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7502 | 1.6271 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
Electricity:Building | 523.41 | 3391.80 | 01-JAN-01:10 | 29524.97 | 02-JAN-11:10 |
Electricity:Zone:DINING | 172.59 | 943.57 | 01-JAN-01:10 | 9073.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 516.47 | 3255.52 | 01-JAN-01:10 | 27381.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 66.48 | 618.91 | 01-JAN-01:10 | 3713.52 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 47.31 | 460.84 | 01-JAN-01:10 | 2765.04 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 66.48 | 618.91 | 01-JAN-01:10 | 3713.52 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 66.48 | 618.91 | 01-JAN-01:10 | 3713.52 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 47.31 | 460.84 | 01-JAN-01:10 | 2765.04 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 66.48 | 618.91 | 01-JAN-01:10 | 3713.52 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 350.82 | 2448.23 | 01-JAN-01:10 | 20451.55 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 56.06 | 1004.38 | 02-JAN-23:30 | 3219.34 | 09-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 124.93 | 1190.76 | 20-JAN-01:10 | 6585.49 | 24-JUN-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.91 | 0.00 | 01-JAN-11:10 | 1532.35 | 18-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 33.22 | 867.08 | 01-JAN-05:20 | 1076.23 | 01-JAN-04:20 |
ElectricityPurchased:Facility | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
ElectricityPurchased:Plant | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
Cogeneration:ElectricityPurchased | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
ElectricityNet:Plant | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
Cogeneration:ElectricityNet | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
General:Cogeneration:ElectricityNet | 1393.80 | 6779.14 | 20-JAN-01:10 | 92769.83 | 16-AUG-12:00 |
Electricity:HVAC | 700.81 | 0.00 | 01-JAN-01:10 | 62445.06 | 10-AUG-13:00 |
Fans:Electricity | 156.93 | 0.00 | 01-JAN-01:10 | 10447.75 | 23-JUN-12:00 |
General:Fans:Electricity | 156.93 | 0.00 | 01-JAN-01:10 | 10447.75 | 23-JUN-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 543.88 | 0.00 | 01-JAN-00:10 | 52341.76 | 16-AUG-12:00 |
General:Cooling:Electricity | 543.88 | 0.00 | 01-JAN-00:10 | 52341.76 | 16-AUG-12:00 |
ExteriorLights:Electricity | 44.66 | 0.00 | 01-JAN-07:10 | 3296.05 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.66 | 0.00 | 01-JAN-07:10 | 3296.05 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.36 | 0.00 | 01-JAN-01:10 | 4739.24 | 09-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 75.36 | 0.00 | 01-JAN-01:10 | 4739.24 | 09-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 710.98 | 2758.01 | 01-JAN-01:10 | 42897.95 | 07-JAN-11:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.01 | 0.00 | 01-JAN-00:10 | 799.80 | 16-JAN-06:50 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 799.80 | 16-JAN-06:50 |
General:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 799.80 | 16-JAN-06:50 |
NaturalGas:Plant | 241.19 | 947.76 | 01-JAN-01:10 | 17305.41 | 03-JAN-07:20 |
WaterSystems:NaturalGas | 241.19 | 947.76 | 01-JAN-01:10 | 17305.41 | 03-JAN-07:20 |
Water Heater:WaterSystems:NaturalGas | 241.19 | 947.76 | 01-JAN-01:10 | 17305.41 | 03-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3201.02 | 3640.12 | 20-JAN-01:10 | 230655.23 | 09-SEP-18:20 |
EnergyTransfer:Building | 963.73 | 1820.06 | 20-JAN-01:10 | 61876.16 | 30-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 475.15 | 1820.06 | 20-JAN-01:10 | 26413.82 | 09-OCT-10:50 |
Refrigeration:EnergyTransfer | 161.96 | 3531.64 | 02-JAN-23:30 | 7834.84 | 03-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.98 | 1765.82 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 80.98 | 1765.82 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.98 | 1765.82 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
EnergyTransfer:Plant | 241.37 | 1820.06 | 20-JAN-01:10 | 14620.95 | 09-JAN-19:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.55 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.43 | 1611.25 | 01-JAN-05:20 | 2238.70 | 01-JAN-04:20 |
EnergyTransfer:Zone:DINING | 488.58 | 0.00 | 01-JAN-01:10 | 42505.28 | 16-AUG-12:00 |
Heating:EnergyTransfer | 3.99 | 0.00 | 01-JAN-00:10 | 15457.94 | 20-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 3.99 | 0.00 | 01-JAN-00:10 | 15457.94 | 20-JUL-23:10 |
General:Heating:EnergyTransfer | 3.99 | 0.00 | 01-JAN-00:10 | 15457.94 | 20-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 3.99 | 0.00 | 01-JAN-00:10 | 15457.94 | 20-JUL-23:10 |
Cooling:EnergyTransfer | 878.76 | 0.00 | 01-JAN-01:10 | 58828.14 | 30-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 484.59 | 0.00 | 01-JAN-01:10 | 42505.28 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 878.76 | 0.00 | 01-JAN-01:10 | 58828.14 | 30-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 484.59 | 0.00 | 01-JAN-01:10 | 42505.28 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 360.65 | 11-MAY-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 360.65 | 11-MAY-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 394.17 | 0.00 | 01-JAN-01:10 | 22914.24 | 20-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 394.17 | 0.00 | 01-JAN-01:10 | 22914.24 | 20-JUL-19:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
PlantLoopHeatingDemand:Plant | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
EnergyTransfer:HVAC | 1995.93 | 0.00 | 01-JAN-00:10 | 168524.69 | 21-AUG-20:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 639.84 | 16-JAN-06:50 |
CoolingCoils:EnergyTransfer | 1995.92 | 0.00 | 01-JAN-00:10 | 168524.69 | 21-AUG-20:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12020.94 | 10-JAN-07:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.990 | -484.587 | 0.000 | 0.000 | 206.223 | 47.309 | 93.957 | 45.971 | 0.000 | 50.772 | 50.516 | 0.000 | -6.525 | 0.000 | -7.626 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.001 | -394.160 | 0.000 | 0.000 | 4.421 | 19.174 | 287.132 | 0.000 | 0.000 | 0.428 | 83.399 | 0.000 | 0.000 | 0.000 | -0.394 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.475 | 26.333 | 0.000 | 0.000 | 0.000 | -39.809 | -0.001 |
Total Facility | 0.000 | 0.000 | 3.991 | -878.748 | 0.000 | 0.000 | 210.644 | 66.483 | 381.090 | 45.971 | 0.000 | 64.675 | 160.248 | 0.000 | -6.525 | 0.000 | -47.829 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-MAY-04:01 | 0.00 | 0.00 | 0.00 | -71319.40 | 0.00 | 0.00 | 686.76 | 614.46 | 2172.30 | 0.00 | 0.00 | 6.98 | 67895.48 | 0.00 | -56.58 | 0.00 | 0.00 | 0.00 |
KITCHEN | 06-JAN-04:21 | 0.00 | 0.00 | 0.00 | -51345.47 | 0.00 | 0.00 | 0.00 | 158.07 | 3481.39 | 0.00 | 0.00 | 0.00 | 47850.34 | 0.00 | -0.00 | 0.00 | -144.34 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:01 | 0.00 | 0.00 | 0.00 | -105400.33 | 0.00 | 0.00 | 691.28 | 825.22 | 9089.15 | 0.00 | 0.00 | 387.61 | 94465.37 | 0.00 | -56.58 | 0.00 | -1.73 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 22593.31 | 0.00 | 0.00 | 0.00 | 973.97 | 460.84 | 543.07 | 999.62 | 0.00 | 214.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25785.22 |
KITCHEN | 03-JUL-04:03 | 0.00 | 0.00 | 2393.03 | 0.00 | 0.00 | 0.00 | 7.33 | 210.77 | 6916.85 | 0.00 | 0.00 | 2.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9530.39 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-23:01 | -12564.67 | 12564.67 | 22593.31 | -12564.67 | 0.00 | 0.00 | 996.46 | 618.91 | 3042.91 | 999.62 | 0.00 | 1243.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16930.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.6097 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.6101 | 0.2888 | 1.0000 | Not calculated | 1.3314 | 0.2888 | ||
PSZ-AC_2:2 | 1.6883 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6883 | 0.1082 | 1.0000 | Not calculated | 0.1826 | 0.1082 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.6097 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.6097 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2888 | ||
PSZ-AC_2:2 | 1.6883 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6883 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1082 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6097 | 4.6097 | 4.6097 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6883 | 1.6883 | 1.6883 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.6097 | 4.6101 | 4.6097 | 4.6097 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6883 | 1.6883 | 1.6883 | 1.6883 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6097 | 4.6097 | 4.6097 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6883 | 1.6883 | 1.6883 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.6097 | 4.6097 | 4.6097 | 4.6097 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6883 | 1.6883 | 1.6883 | 1.6883 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1813.17 |
Number of hours not met | 1813.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.01 | 799.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 543.88 | 52341.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 66.48 | 3713.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.66 | 3296.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 156.93 | 10447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.36 | 4739.24 | 241.19 | 17305.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.91 | 1532.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.22 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 506.05 | 1393.80 |
Natural Gas | 469.79 | 710.98 |
Additional | 0.00 | 0.00 |
Total | 975.84 | 2104.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 130.06 |
Space Heating | 0.00 |
Space Cooling | 1064.02 |
Fans (All) | 307.01 |
Service Water Heating | 147.43 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 2726.78 |
Subtotal | 2726.78 |
Natural Gas [MJ/m2] | |
Space Heating | 0.01 |
Service Water Heating | 471.85 |
Miscellaneous (All) | 1390.93 |
Subtotal | 1390.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.16 |
Space Heating | 0.00 |
Space Cooling | 25.84 |
Fans (All) | 7.46 |
Service Water Heating | 15.04 |
Receptacle Equipment | 43.70 |
Miscellaneous | 4.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7655.50 | 724.00 | 378.17 | 2.33 | 0.00 |
KITCHEN | 5137.83 | 2547.67 | 1026.50 | 48.00 | 0.00 |
ATTIC | 3604.83 | 1040.33 | 1499.00 | 1444.33 | 1171.50 |
Min | 3604.83 | 724.00 | 378.17 | 2.33 | 0.00 |
Max | 7655.50 | 2547.67 | 1499.00 | 1444.33 | 1171.50 |
Average | 5466.06 | 1437.33 | 967.89 | 498.22 | 390.50 |
Sum | 16398.17 | 4312.00 | 2903.67 | 1494.67 | 1171.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821396.33 | 1680.00 | 1113.00 | 32.67 | 0.00 |
KITCHEN | 13460.00 | 3425.00 | 2202.17 | 145.83 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821396.33 | 3425.00 | 2202.17 | 145.83 | 0.00 |
Average | 278285.44 | 1701.67 | 1105.06 | 59.50 | 0.00 |
Sum | 834856.33 | 5105.00 | 3315.17 | 178.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 4533.67 | 3894.50 | 328.67 | 3.17 | 0.00 |
KITCHEN | 1073.00 | 7036.17 | 626.83 | 24.00 | 0.00 |
ATTIC | 2789.50 | 2321.83 | 1244.83 | 761.33 | 1642.50 |
Min | 1073.00 | 2321.83 | 328.67 | 3.17 | 0.00 |
Max | 4533.67 | 7036.17 | 1244.83 | 761.33 | 1642.50 |
Average | 2798.72 | 4417.50 | 733.44 | 262.83 | 547.50 |
Sum | 8396.17 | 13252.50 | 2200.33 | 788.50 | 1642.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 501218.67 | 322212.33 | 756.00 | 35.00 | 0.00 |
KITCHEN | 2475.00 | 15186.33 | 1497.67 | 74.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 501218.67 | 322212.33 | 1497.67 | 74.00 | 0.00 |
Average | 167897.89 | 112466.22 | 751.22 | 36.33 | 0.00 |
Sum | 503693.67 | 337398.67 | 2253.67 | 109.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292852E+11 | 25346.72 | 23-JAN-12:57 | 27.40 | 16.52 | 0.151410E+11 | 14051.40 | 28-JAN-19:49 | 22.08 | 16.97 |
February | 0.278257E+11 | 29257.15 | 07-FEB-12:53 | 31.00 | 20.84 | 0.137978E+11 | 14051.42 | 11-FEB-19:10 | 19.33 | 13.92 |
March | 0.333224E+11 | 37072.77 | 02-MAR-06:02 | 28.80 | 15.43 | 0.154839E+11 | 14052.54 | 25-MAR-18:10 | 27.38 | 20.47 |
April | 0.362878E+11 | 37578.75 | 28-APR-11:55 | 42.00 | 19.18 | 0.149137E+11 | 14053.04 | 08-APR-18:10 | 42.00 | 19.18 |
May | 0.449032E+11 | 71351.49 | 12-MAY-04:01 | 28.67 | 19.72 | 0.154549E+11 | 14051.74 | 13-MAY-18:49 | 31.58 | 23.75 |
June | 0.464341E+11 | 61841.80 | 02-JUN-04:01 | 28.33 | 18.21 | 0.150410E+11 | 14051.87 | 03-JUN-18:10 | 35.28 | 25.40 |
July | 0.511224E+11 | 64523.46 | 04-JUL-04:01 | 30.42 | 16.66 | 0.154311E+11 | 14111.51 | 01-JUL-18:19 | 30.42 | 16.66 |
August | 0.530329E+11 | 53988.39 | 06-AUG-04:01 | 35.67 | 22.58 | 0.156701E+11 | 14666.22 | 22-AUG-17:30 | 36.00 | 30.49 |
September | 0.476782E+11 | 53047.17 | 02-SEP-04:01 | 30.48 | 22.94 | 0.149514E+11 | 14055.32 | 09-SEP-18:19 | 34.87 | 28.10 |
October | 0.449218E+11 | 58506.13 | 04-OCT-04:01 | 26.92 | 20.11 | 0.153572E+11 | 14051.88 | 14-OCT-18:40 | 31.40 | 24.17 |
November | 0.377295E+11 | 49775.50 | 02-NOV-04:01 | 23.50 | 21.49 | 0.148350E+11 | 14053.49 | 18-NOV-19:00 | 25.00 | 16.38 |
December | 0.320476E+11 | 29304.80 | 12-DEC-06:03 | 23.03 | 17.89 | 0.152628E+11 | 14053.64 | 02-DEC-19:40 | 23.03 | 17.89 |
Annual Sum or Average | 0.484591E+12 | 0.181340E+12 | ||||||||
Minimum of Months | 0.278257E+11 | 25346.72 | 23.03 | 15.43 | 0.137978E+11 | 14051.40 | 19.33 | 13.92 | ||
Maximum of Months | 0.530329E+11 | 71351.49 | 42.00 | 22.94 | 0.156701E+11 | 14666.22 | 42.00 | 30.49 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312223E+11 | 51346.50 | 06-JAN-04:21 | 14.25 | 12.94 | 0.105957E+11 | 6934.95 | 25-JAN-11:09 | 21.33 | 15.53 |
February | 0.283556E+11 | 44658.35 | 16-FEB-05:01 | 14.85 | 12.50 | 0.957486E+10 | 6934.94 | 10-FEB-11:09 | 14.85 | 12.50 |
March | 0.317634E+11 | 45524.57 | 17-MAR-03:11 | 18.33 | 15.05 | 0.106076E+11 | 6934.95 | 06-MAR-11:09 | 18.33 | 15.05 |
April | 0.316184E+11 | 32499.20 | 28-APR-03:31 | 26.33 | 15.47 | 0.102636E+11 | 6941.52 | 28-APR-10:00 | 40.00 | 18.54 |
May | 0.344726E+11 | 36285.53 | 11-MAY-03:22 | 29.95 | 16.90 | 0.106142E+11 | 6994.66 | 30-MAY-10:00 | 36.00 | 26.94 |
June | 0.335913E+11 | 36743.97 | 02-JUN-04:01 | 28.33 | 18.21 | 0.103131E+11 | 7012.87 | 09-JUN-10:50 | 38.63 | 27.06 |
July | 0.343147E+11 | 37041.32 | 03-JUL-04:01 | 29.00 | 16.97 | 0.107011E+11 | 7049.41 | 25-JUL-10:50 | 35.92 | 28.99 |
August | 0.345878E+11 | 27968.71 | 15-AUG-04:01 | 29.75 | 23.27 | 0.107270E+11 | 7053.09 | 08-AUG-10:00 | 29.75 | 23.27 |
September | 0.337421E+11 | 34252.66 | 26-SEP-04:01 | 26.97 | 19.72 | 0.103319E+11 | 7054.00 | 11-SEP-10:00 | 26.97 | 19.72 |
October | 0.352249E+11 | 39909.22 | 20-OCT-04:01 | 22.50 | 16.21 | 0.106177E+11 | 7007.98 | 07-OCT-10:50 | 22.50 | 16.21 |
November | 0.330523E+11 | 41881.30 | 26-NOV-05:01 | 17.00 | 14.53 | 0.102619E+11 | 6974.12 | 01-NOV-10:00 | 17.00 | 14.53 |
December | 0.322219E+11 | 46736.46 | 22-DEC-04:11 | 15.93 | 13.94 | 0.106003E+11 | 6934.97 | 15-DEC-11:39 | 15.93 | 13.94 |
Annual Sum or Average | 0.394167E+12 | 0.125209E+12 | ||||||||
Minimum of Months | 0.283556E+11 | 27968.71 | 14.25 | 12.50 | 0.957486E+10 | 6934.94 | 14.85 | 12.50 | ||
Maximum of Months | 0.352249E+11 | 51346.50 | 29.95 | 23.27 | 0.107270E+11 | 7054.00 | 40.00 | 28.99 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 | 14.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 | 23.56 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 | 27.02 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 | 21.17 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 | 15.63 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.00 | 0.00 | 15.70 | 12.84 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 104054.64 | 693.70 | 29-JAN-06:05 | 22.00 |
February | 725990.81 | 1972.74 | 09-FEB-06:05 | 22.92 |
March | 25830944.69 | 7385.46 | 27-MAR-23:02 | 27.83 |
April | 96390150.43 | 8762.08 | 28-APR-23:02 | 28.83 |
May | 0.520471E+09 | 15637.49 | 31-MAY-23:01 | 33.03 |
June | 0.695034E+09 | 18641.33 | 08-JUN-23:01 | 34.83 |
July | 0.831959E+09 | 22589.62 | 20-JUL-23:01 | 37.67 |
August | 0.792424E+09 | 21780.98 | 05-AUG-23:01 | 37.00 |
September | 0.626966E+09 | 16009.96 | 04-SEP-23:01 | 33.22 |
October | 0.341641E+09 | 11904.91 | 05-OCT-23:01 | 30.67 |
November | 56033867.21 | 9989.28 | 01-NOV-23:01 | 29.50 |
December | 784659.36 | 2041.39 | 12-DEC-06:05 | 23.03 |
Annual Sum or Average | 0.398837E+10 | |||
Minimum of Months | 104054.64 | 693.70 | 22.00 | |
Maximum of Months | 0.831959E+09 | 22589.62 | 37.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 287053.24 | 2163.88 | 11-MAY-04:03 | 29.58 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 295600.52 | 2393.32 | 03-JUL-04:03 | 29.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 582653.77 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 295600.52 | 2393.32 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.408217E+10 | 2765.04 | 02-JAN-17:30 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.367376E+10 | 2765.04 | 01-FEB-17:40 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.406950E+10 | 2765.04 | 01-MAR-18:10 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.384435E+10 | 2765.04 | 01-APR-18:19 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.396234E+10 | 2765.04 | 01-MAY-18:30 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.384406E+10 | 2765.04 | 01-JUN-18:40 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.393036E+10 | 2765.04 | 01-JUL-18:40 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.400478E+10 | 2765.04 | 01-AUG-19:10 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.385924E+10 | 2765.04 | 01-SEP-18:19 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.401400E+10 | 2765.04 | 02-OCT-17:40 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.393503E+10 | 2765.04 | 01-NOV-17:30 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.408907E+10 | 2765.04 | 01-DEC-17:30 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.473087E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.367376E+10 | 2765.04 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.408907E+10 | 2765.04 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162018E+10 | 948.48 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.146748E+10 | 948.48 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.164598E+10 | 948.48 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.157428E+10 | 948.48 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.163308E+10 | 948.48 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.159097E+10 | 948.48 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.161658E+10 | 948.48 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.164598E+10 | 948.48 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.157466E+10 | 948.48 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.161999E+10 | 948.48 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.156840E+10 | 948.48 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.161677E+10 | 948.48 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.191743E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.146748E+10 | 948.48 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.164598E+10 | 948.48 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.408217E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60769464.35 | 0.261490E+10 |
February | 0.272721E+11 | 0.367376E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404133E+09 | 0.178936E+10 |
March | 0.305458E+11 | 0.406950E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125884E+10 | 0.102044E+10 |
April | 0.292871E+11 | 0.384435E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306674E+10 | 0.257488E+09 |
May | 0.303219E+11 | 0.396234E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651377E+10 | 19891640.48 |
June | 0.295292E+11 | 0.384406E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726484E+10 | 2140953.61 |
July | 0.300798E+11 | 0.393036E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867648E+10 | 0.00 |
August | 0.305458E+11 | 0.400478E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892280E+10 | 0.00 |
September | 0.292871E+11 | 0.385924E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682398E+10 | 1850963.85 |
October | 0.300980E+11 | 0.401400E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503747E+10 | 30429686.88 |
November | 0.290996E+11 | 0.393503E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235589E+10 | 0.273159E+09 |
December | 0.300798E+11 | 0.408907E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386611E+09 | 0.161676E+10 |
Annual Sum or Average | 0.356244E+12 | 0.473087E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507723E+11 | 0.762642E+10 |
Minimum of Months | 0.272721E+11 | 0.367376E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60769464.35 | 0.00 |
Maximum of Months | 0.305458E+11 | 0.408907E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892280E+10 | 0.261490E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162018E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 102178.33 | 84505377.11 |
February | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 2494174.62 | 85484478.27 |
March | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 9170881.73 | 55746497.77 |
April | 0.786997E+09 | 0.157428E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 22988372.26 | 31942402.06 |
May | 0.814802E+09 | 0.163308E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 57967170.05 | 8780307.68 |
June | 0.793501E+09 | 0.159097E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 67927038.04 | 5505191.42 |
July | 0.808298E+09 | 0.161658E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 81168375.35 | 836113.40 |
August | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 80722165.68 | 683156.30 |
September | 0.786997E+09 | 0.157466E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 54128992.34 | 5233050.77 |
October | 0.808786E+09 | 0.161999E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 36851502.14 | 14380506.11 |
November | 0.781956E+09 | 0.156840E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 13285482.82 | 33040227.10 |
December | 0.808298E+09 | 0.161677E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1000027.81 | 67599623.17 |
Annual Sum or Average | 0.957291E+10 | 0.191743E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.427806E+09 | 0.393737E+09 |
Minimum of Months | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 102178.33 | 683156.30 |
Maximum of Months | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 81168375.35 | 85484478.27 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116326E+10 | 0.259656E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844039E+09 | 0.270686E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115101E+10 | 0.343956E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113208E+10 | 0.372206E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112985E+10 | 0.415478E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102377E+10 | 0.393121E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100105E+10 | 0.407512E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105291E+10 | 0.376819E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113440E+10 | 0.340429E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132634E+10 | 0.312913E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132503E+10 | 0.251455E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119132E+10 | 0.236625E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134751E+11 | 0.398086E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844039E+09 | 0.236625E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132634E+10 | 0.415478E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2765.04 | 02-JAN-17:30 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.90 | 23-JAN-14:00 | 3925.50 | 01-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2765.04 | 01-FEB-17:40 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4308.96 | 06-FEB-14:00 | 3964.19 | 20-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2765.04 | 01-MAR-18:10 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8200.42 | 27-MAR-11:10 | 3884.14 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2765.04 | 01-APR-18:19 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.29 | 28-APR-11:55 | 2879.94 | 01-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 2765.04 | 01-MAY-18:30 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10410.62 | 31-MAY-19:00 | 1209.31 | 01-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2765.04 | 01-JUN-18:40 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10826.24 | 12-JUN-12:00 | 1021.03 | 22-JUN-08:00 |
July | 30255.31 | 01-JUL-18:10 | 2765.04 | 01-JUL-18:40 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12354.03 | 21-JUL-12:00 | 0.00 | 01-JUL-00:01 |
August | 30255.31 | 05-AUG-18:10 | 2765.04 | 01-AUG-19:10 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12531.38 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 30255.31 | 02-SEP-18:10 | 2765.04 | 01-SEP-18:19 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9821.02 | 26-SEP-12:00 | 261.98 | 25-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 2765.04 | 02-OCT-17:40 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8139.25 | 04-OCT-12:00 | 1416.74 | 29-OCT-07:00 |
November | 30255.31 | 04-NOV-18:10 | 2765.04 | 01-NOV-17:30 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5099.23 | 01-NOV-11:55 | 2653.83 | 26-NOV-07:10 |
December | 30255.31 | 02-DEC-19:10 | 2765.04 | 01-DEC-17:30 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2555.44 | 01-DEC-13:00 | 3872.07 | 31-DEC-07:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.90 | 0.00 | |||||
Maximum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 12531.38 | 3964.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 948.48 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 8.94 | 23-JAN-13:50 | 469.09 | 18-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 948.48 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 41.17 | 05-FEB-14:55 | 375.02 | 10-FEB-04:40 |
March | 813.01 | 04-MAR-19:10 | 948.48 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 86.05 | 27-MAR-11:00 | 231.35 | 14-MAR-03:30 |
April | 813.01 | 01-APR-18:10 | 948.48 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 108.11 | 28-APR-12:51 | 226.67 | 05-APR-01:00 |
May | 813.01 | 06-MAY-18:10 | 948.48 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 303.73 | 21-MAY-12:52 | 109.23 | 02-MAY-03:30 |
June | 813.01 | 03-JUN-18:10 | 948.48 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 167.33 | 09-JUN-23:04 | 159.42 | 06-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 948.48 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 209.29 | 13-JUL-23:25 | 81.99 | 07-JUL-03:20 |
August | 813.01 | 05-AUG-18:10 | 948.48 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 225.58 | 01-AUG-24:00 | 76.75 | 08-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 948.48 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 96.54 | 06-SEP-23:10 | 99.95 | 28-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 948.48 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 96.93 | 19-OCT-14:55 | 173.06 | 20-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 948.48 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 58.72 | 01-NOV-23:03 | 172.48 | 21-NOV-04:30 |
December | 813.01 | 02-DEC-19:10 | 948.48 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 16.08 | 10-DEC-13:00 | 283.81 | 27-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 8.94 | 76.75 | ||||||
Maximum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 303.73 | 469.09 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.20 | 03-JAN-07:10 | 5417.32 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2450.36 | 15-FEB-07:42 | 5866.42 | 22-FEB-13:45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2366.90 | 27-MAR-06:43 | 6807.75 | 30-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2042.35 | 26-APR-06:00 | 6732.60 | 30-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.25 | 04-MAY-07:51 | 6501.62 | 30-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.89 | 16-JUN-05:50 | 6273.60 | 08-JUN-12:25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1754.76 | 04-JUL-04:40 | 6417.25 | 04-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.86 | 05-AUG-01:51 | 6369.74 | 30-AUG-11:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2473.91 | 30-SEP-07:41 | 5848.41 | 17-SEP-13:43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.10 | 29-OCT-04:55 | 5669.26 | 04-OCT-12:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1714.53 | 05-NOV-07:23 | 4969.41 | 07-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.71 | 19-DEC-05:00 | 5327.54 | 25-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.86 | 4969.41 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.25 | 6807.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25346.72 | 23-JAN-12:57 | 80680.82 | 6221.35 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.02 | 0.00 |
February | 29257.15 | 07-FEB-12:53 | 80680.82 | 6221.35 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4238.21 | 0.00 |
March | 37072.77 | 02-MAR-06:02 | 16808.50 | 6144.57 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 523.42 | 0.00 |
April | 37578.75 | 28-APR-11:55 | 53787.21 | 4147.56 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.29 | 0.00 |
May | 71351.49 | 12-MAY-04:01 | 13446.80 | 4915.66 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 0.00 |
June | 61841.80 | 02-JUN-04:01 | 13446.80 | 4915.66 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 0.00 |
July | 64523.46 | 04-JUL-04:01 | 0.00 | 3225.85 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
August | 53988.39 | 06-AUG-04:01 | 0.00 | 3225.85 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 | 0.00 |
September | 53047.17 | 02-SEP-04:01 | 0.00 | 3225.85 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 0.00 |
October | 58506.13 | 04-OCT-04:01 | 11765.95 | 4301.20 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
November | 49775.50 | 02-NOV-04:01 | 11765.95 | 4301.20 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
December | 29304.80 | 12-DEC-06:03 | 13446.80 | 4915.66 | 12551.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25346.72 | 0.00 | 3225.85 | 12551.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71351.49 | 80680.82 | 6221.35 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.29 | 140.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51346.50 | 06-JAN-04:21 | 0.00 | 1106.52 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 144.34 |
February | 44658.35 | 16-FEB-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
March | 45524.57 | 17-MAR-03:11 | 0.00 | 1422.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 |
April | 32499.20 | 28-APR-03:31 | 0.00 | 1106.52 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 15.48 |
May | 36285.53 | 11-MAY-03:22 | 0.00 | 948.45 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
June | 36743.97 | 02-JUN-04:01 | 361.34 | 1686.13 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
July | 37041.32 | 03-JUL-04:01 | 316.17 | 1475.37 | 45038.79 | 22809.15 | 0.00 | 0.00 | 0.00 | 1.14 | 0.00 |
August | 27968.71 | 15-AUG-04:01 | 361.34 | 1686.13 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 |
September | 34252.66 | 26-SEP-04:01 | 361.34 | 1686.13 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 |
October | 39909.22 | 20-OCT-04:01 | 361.34 | 1686.13 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 |
November | 41881.30 | 26-NOV-05:01 | 0.00 | 1580.75 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 |
December | 46736.46 | 22-DEC-04:11 | 0.00 | 1422.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 36.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27968.71 | 0.00 | 948.45 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51346.50 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 4.60 | 144.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.46 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.53 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.65 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.88 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.17 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.07 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.46 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.83 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.62 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.23 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.33 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.53 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.852943E+11 | 56121.08 | 24-JAN-11:00 | 0.641022E+11 | 42897.95 | 07-JAN-11:20 |
February | 0.807568E+11 | 60072.22 | 06-FEB-18:19 | 0.574014E+11 | 42856.97 | 04-FEB-11:20 |
March | 0.945075E+11 | 67208.75 | 27-MAR-10:00 | 0.623123E+11 | 42687.46 | 04-MAR-11:09 |
April | 0.101899E+12 | 76721.92 | 28-APR-11:00 | 0.583117E+11 | 42450.58 | 01-APR-10:50 |
May | 0.123421E+12 | 86004.28 | 31-MAY-11:00 | 0.584295E+11 | 42123.10 | 06-MAY-10:09 |
June | 0.135486E+12 | 89323.70 | 09-JUN-11:00 | 0.552865E+11 | 41915.85 | 03-JUN-10:20 |
July | 0.154037E+12 | 89606.32 | 19-JUL-11:39 | 0.565121E+11 | 41812.70 | 29-JUL-10:30 |
August | 0.158708E+12 | 92769.83 | 16-AUG-11:00 | 0.572676E+11 | 41923.48 | 27-AUG-10:50 |
September | 0.139988E+12 | 89351.69 | 07-SEP-11:00 | 0.567648E+11 | 42207.47 | 30-SEP-10:20 |
October | 0.124285E+12 | 84958.89 | 07-OCT-18:49 | 0.605337E+11 | 42475.66 | 29-OCT-10:00 |
November | 0.103256E+12 | 76109.11 | 01-NOV-11:00 | 0.603799E+11 | 42711.95 | 26-NOV-11:09 |
December | 0.921647E+11 | 61331.62 | 05-DEC-18:19 | 0.636788E+11 | 42881.88 | 31-DEC-11:30 |
Annual Sum or Average | 0.139380E+13 | 0.710980E+12 | ||||
Minimum of Months | 0.807568E+11 | 56121.08 | 0.552865E+11 | 41812.70 | ||
Maximum of Months | 0.158708E+12 | 92769.83 | 0.641022E+11 | 42897.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.570236E+10 | 0.430091E+10 | 0.382185E+11 | 0.00 | 0.107006E+11 | 37879553.69 | 0.00 | 0.153339E+11 | 0.00 | 0.00 | 0.00 | 0.638029E+10 | 0.00 |
February | 0.514124E+10 | 0.370964E+10 | 0.345199E+11 | 0.00 | 0.972906E+10 | 34213790.43 | 0.00 | 0.176479E+11 | 0.00 | 0.00 | 0.00 | 0.577394E+10 | 0.00 |
March | 0.571548E+10 | 0.385198E+10 | 0.382185E+11 | 0.00 | 0.109088E+11 | 37879553.69 | 0.00 | 0.246660E+11 | 0.00 | 0.00 | 0.00 | 0.644801E+10 | 0.00 |
April | 0.541863E+10 | 0.345647E+10 | 0.369856E+11 | 0.00 | 0.110288E+11 | 36657632.61 | 0.00 | 0.342472E+11 | 0.00 | 0.00 | 0.00 | 0.619235E+10 | 0.00 |
May | 0.559542E+10 | 0.335362E+10 | 0.382185E+11 | 0.00 | 0.129873E+11 | 37879553.69 | 0.00 | 0.520885E+11 | 0.00 | 0.00 | 0.00 | 0.641359E+10 | 0.00 |
June | 0.543503E+10 | 0.314401E+10 | 0.369856E+11 | 0.00 | 0.148761E+11 | 36657632.61 | 0.00 | 0.640969E+11 | 0.00 | 0.00 | 0.00 | 0.623290E+10 | 0.00 |
July | 0.554694E+10 | 0.328638E+10 | 0.382185E+11 | 0.00 | 0.175197E+11 | 37879553.69 | 0.00 | 0.781865E+11 | 0.00 | 0.00 | 0.00 | 0.636543E+10 | 0.00 |
August | 0.565077E+10 | 0.347426E+10 | 0.382185E+11 | 0.00 | 0.182538E+11 | 37879553.69 | 0.00 | 0.817282E+11 | 0.00 | 0.00 | 0.00 | 0.644260E+10 | 0.00 |
September | 0.543389E+10 | 0.360875E+10 | 0.369856E+11 | 0.00 | 0.157201E+11 | 36657632.61 | 0.00 | 0.673075E+11 | 0.00 | 0.00 | 0.00 | 0.618998E+10 | 0.00 |
October | 0.563399E+10 | 0.399833E+10 | 0.382185E+11 | 0.00 | 0.132122E+11 | 37879553.69 | 0.00 | 0.519908E+11 | 0.00 | 0.00 | 0.00 | 0.637676E+10 | 0.00 |
November | 0.550342E+10 | 0.410118E+10 | 0.369856E+11 | 0.00 | 0.111364E+11 | 36657632.61 | 0.00 | 0.346752E+11 | 0.00 | 0.00 | 0.00 | 0.617344E+10 | 0.00 |
December | 0.570584E+10 | 0.437012E+10 | 0.382185E+11 | 0.00 | 0.108577E+11 | 37879553.69 | 0.00 | 0.219078E+11 | 0.00 | 0.00 | 0.00 | 0.637149E+10 | 0.00 |
Annual Sum or Average | 0.664830E+11 | 0.446556E+11 | 0.449992E+12 | 0.00 | 0.156930E+12 | 0.446001E+09 | 0.00 | 0.543876E+12 | 0.00 | 0.00 | 0.00 | 0.753608E+11 | 0.00 |
Minimum of Months | 0.514124E+10 | 0.314401E+10 | 0.345199E+11 | 0.00 | 0.972906E+10 | 34213790.43 | 0.00 | 0.153339E+11 | 0.00 | 0.00 | 0.00 | 0.577394E+10 | 0.00 |
Maximum of Months | 0.571548E+10 | 0.437012E+10 | 0.382185E+11 | 0.00 | 0.182538E+11 | 37879553.69 | 0.00 | 0.817282E+11 | 0.00 | 0.00 | 0.00 | 0.644801E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 5302036.10 | 0.00 | 0.241972E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.213629E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.224126E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.196991E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.185298E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.166738E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.166123E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.173679E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.181522E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.206340E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.217673E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.237791E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 5302036.10 | 0.00 | 0.241188E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.166123E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 5302036.10 | 0.00 | 0.241972E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3713.52 | 02-JAN-17:30 | 3296.05 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 5116.69 | 24-JAN-11:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3713.52 | 01-FEB-17:40 | 3296.05 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 5406.19 | 07-FEB-15:00 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3713.52 | 01-MAR-18:10 | 3296.05 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 5987.58 | 27-MAR-11:09 | 17.86 | 25-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 3713.52 | 01-APR-18:19 | 3296.05 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 7457.45 | 29-APR-18:00 | 17.86 | 01-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 3713.52 | 01-MAY-18:30 | 3296.05 | 01-MAY-05:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 9898.19 | 30-MAY-17:00 | 17.86 | 04-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 3713.52 | 01-JUN-18:40 | 3296.05 | 01-JUN-05:10 | 24359.61 | 01-JUN-10:09 | 0.00 | 10447.75 | 23-JUN-11:00 | 17.86 | 10-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 3713.52 | 01-JUL-18:40 | 3296.05 | 01-JUL-05:10 | 24359.61 | 01-JUL-10:09 | 0.00 | 10447.75 | 05-JUL-11:50 | 17.86 | 06-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 3713.52 | 01-AUG-19:10 | 3296.05 | 01-AUG-05:10 | 24359.61 | 01-AUG-10:09 | 0.00 | 10447.75 | 03-AUG-11:50 | 17.86 | 03-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 3713.52 | 01-SEP-18:19 | 3296.05 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 10447.75 | 07-SEP-12:30 | 17.86 | 01-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 3713.52 | 02-OCT-17:40 | 3296.05 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 10309.07 | 07-OCT-18:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 3713.52 | 01-NOV-17:30 | 3296.05 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 8581.71 | 01-NOV-11:00 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3713.52 | 01-DEC-17:30 | 3296.05 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 5554.23 | 05-DEC-12:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 5116.69 | 17.86 | 0.00 | ||||||
Maximum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 10447.75 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19335.29 | 24-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4739.24 | 09-JAN-07:19 | 0.00 |
February | 23970.26 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4737.78 | 22-FEB-07:19 | 0.00 |
March | 29827.15 | 27-MAR-11:09 | 0.00 | 0.00 | 0.00 | 4737.45 | 08-MAR-07:19 | 0.00 |
April | 38803.09 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 4736.72 | 06-APR-18:30 | 0.00 |
May | 45862.72 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4737.02 | 19-MAY-18:30 | 0.00 |
June | 48463.57 | 09-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4736.82 | 20-JUN-18:49 | 0.00 |
July | 49309.53 | 21-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.66 | 03-JUL-18:30 | 0.00 |
August | 52341.76 | 16-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4736.09 | 15-AUG-18:49 | 0.00 |
September | 48316.50 | 07-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.10 | 15-SEP-06:49 | 0.00 |
October | 42653.33 | 07-OCT-18:00 | 0.00 | 0.00 | 0.00 | 4736.87 | 18-OCT-18:19 | 0.00 |
November | 37001.23 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 4736.60 | 07-NOV-07:19 | 0.00 |
December | 24675.62 | 05-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4737.95 | 18-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19335.29 | 0.00 | 0.00 | 0.00 | 4736.09 | 0.00 | ||
Maximum of Months | 52341.76 | 0.00 | 0.00 | 0.00 | 4739.24 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56121.08 | 24-JAN-11:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 5116.69 | 17.86 | 0.00 | 17734.00 | 0.00 |
February | 60072.22 | 06-FEB-18:19 | 3713.52 | 20336.83 | 3296.05 | 0.00 | 5178.80 | 17.86 | 0.00 | 21439.50 | 0.00 |
March | 67208.75 | 27-MAR-10:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 5624.70 | 17.86 | 0.00 | 28301.10 | 0.00 |
April | 76721.92 | 28-APR-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 7457.10 | 17.86 | 0.00 | 38803.09 | 0.00 |
May | 86004.28 | 31-MAY-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 9606.18 | 17.86 | 0.00 | 45862.72 | 0.00 |
June | 89323.70 | 09-JUN-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 10307.07 | 17.86 | 0.00 | 48463.57 | 0.00 |
July | 89606.32 | 19-JUL-11:39 | 3022.26 | 22750.50 | 0.00 | 0.00 | 10447.75 | 17.86 | 0.00 | 48605.06 | 0.00 |
August | 92769.83 | 16-AUG-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 9875.06 | 17.86 | 0.00 | 52341.76 | 0.00 |
September | 89351.69 | 07-SEP-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 10447.75 | 17.86 | 0.00 | 48316.50 | 0.00 |
October | 84958.89 | 07-OCT-18:49 | 3713.52 | 18727.72 | 3296.05 | 0.00 | 10265.24 | 17.86 | 0.00 | 42511.77 | 0.00 |
November | 76109.11 | 01-NOV-11:00 | 3022.26 | 22750.50 | 0.00 | 0.00 | 8581.71 | 17.86 | 0.00 | 37001.23 | 0.00 |
December | 61331.62 | 05-DEC-18:19 | 3713.52 | 20336.83 | 3296.05 | 0.00 | 5272.32 | 17.86 | 0.00 | 22541.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 56121.08 | 3022.26 | 18727.72 | 0.00 | 0.00 | 5116.69 | 17.86 | 0.00 | 17734.00 | 0.00 | |
Maximum of Months | 92769.83 | 3713.52 | 24359.61 | 3296.05 | 0.00 | 10447.75 | 17.86 | 0.00 | 52341.76 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 799.80 | 16-JAN-06:49 | 0.00 | 17305.41 | 03-JAN-07:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 17262.48 | 01-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 17055.19 | 01-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 16694.46 | 03-APR-18:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16363.28 | 01-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16065.50 | 01-JUN-18:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 15917.23 | 31-JUL-18:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16094.82 | 31-AUG-18:40 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16391.13 | 29-SEP-18:10 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 16778.23 | 31-OCT-18:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 17095.27 | 30-NOV-19:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 17281.67 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 15917.23 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 799.80 | 0.00 | 17305.41 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 24.85 | 17.00 | 24.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 25.02 | 20.67 | 25.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.79 | 2.67 | 24.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.33 | 24.94 | 40.33 | 24.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 25.02 | 20.67 | 25.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.93 | 0.00 | 30.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.99 | 0.00 | 30.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 31.09 | 0.00 | 31.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 30.67 | 3.83 | 30.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 28.88 | 56.83 | 28.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 324.67 | 28.44 | 294.67 | 28.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 505.17 | 29.14 | 472.00 | 29.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 547.33 | 29.37 | 511.67 | 29.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 399.67 | 28.69 | 369.17 | 28.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 127.83 | 28.86 | 96.83 | 28.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 30.47 | 8.17 | 29.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 31.11 | 0.00 | 31.11 |
Annual Sum or Average | 0.00 | 0.00 | 2152.00 | 29.11 | 1813.17 | 28.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 28.44 | 0.00 | 28.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 547.33 | 31.11 | 511.67 | 31.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.50 | 22.37 | 488.33 | 23.75 | 8.17 | 23.76 |
February | 79.00 | 23.33 | 492.50 | 23.92 | 41.67 | 23.95 |
March | 78.67 | 23.90 | 566.83 | 24.06 | 63.50 | 24.07 |
April | 115.83 | 24.45 | 586.00 | 24.20 | 115.83 | 24.24 |
May | 186.17 | 24.76 | 611.00 | 24.38 | 186.17 | 24.45 |
June | 412.00 | 24.43 | 592.00 | 24.36 | 412.00 | 24.38 |
July | 470.67 | 24.46 | 609.00 | 24.40 | 470.67 | 24.42 |
August | 512.83 | 24.46 | 612.00 | 24.42 | 512.83 | 24.43 |
September | 437.50 | 24.41 | 590.00 | 24.35 | 437.50 | 24.37 |
October | 281.67 | 24.47 | 610.00 | 24.31 | 281.67 | 24.35 |
November | 129.33 | 24.42 | 591.00 | 24.19 | 129.33 | 24.23 |
December | 119.33 | 23.84 | 567.00 | 23.99 | 100.33 | 24.00 |
Annual Sum or Average | 2910.50 | 24.33 | 6915.67 | 24.24 | 2759.67 | 24.28 |
Minimum of Months | 78.67 | 22.37 | 488.33 | 23.75 | 8.17 | 23.76 |
Maximum of Months | 512.83 | 24.76 | 612.00 | 24.42 | 512.83 | 24.45 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.17 | 25.99 | 605.67 | 25.78 | 486.17 | 25.85 |
February | 483.67 | 26.00 | 551.00 | 25.89 | 483.67 | 25.92 |
March | 570.50 | 26.02 | 612.00 | 25.98 | 570.50 | 25.99 |
April | 588.00 | 26.06 | 590.00 | 26.06 | 588.00 | 26.06 |
May | 611.00 | 26.23 | 611.00 | 26.23 | 611.00 | 26.23 |
June | 592.00 | 27.15 | 592.00 | 27.15 | 592.00 | 27.15 |
July | 609.00 | 28.35 | 609.00 | 28.35 | 609.00 | 28.35 |
August | 612.00 | 28.73 | 612.00 | 28.73 | 612.00 | 28.73 |
September | 590.00 | 27.61 | 590.00 | 27.61 | 590.00 | 27.61 |
October | 610.00 | 26.40 | 610.00 | 26.40 | 610.00 | 26.40 |
November | 591.00 | 26.07 | 591.00 | 26.07 | 591.00 | 26.07 |
December | 559.50 | 25.98 | 609.00 | 25.92 | 559.50 | 25.94 |
Annual Sum or Average | 6902.83 | 26.75 | 7182.67 | 26.70 | 6902.83 | 26.72 |
Minimum of Months | 483.67 | 25.98 | 551.00 | 25.78 | 483.67 | 25.85 |
Maximum of Months | 612.00 | 28.73 | 612.00 | 28.73 | 612.00 | 28.73 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.72283 | 50.83865 | 0.49998 | 10.90416 |
February | 551.00000 | 23.87185 | 54.17898 | 0.56782 | 12.18502 |
March | 612.00000 | 24.02065 | 51.29172 | 0.59316 | 12.68794 |
April | 590.00000 | 24.15175 | 54.86263 | 0.67026 | 14.69030 |
May | 611.00000 | 24.26427 | 57.51211 | -0.0356 | 5.99918 |
June | 592.00000 | 24.30572 | 65.27706 | 0.06059 | 6.42563 |
July | 609.00000 | 24.35880 | 67.62073 | 0.12778 | 7.04525 |
August | 612.00000 | 24.38334 | 68.95265 | 0.16562 | 7.19009 |
September | 590.00000 | 24.30507 | 67.81992 | 0.10679 | 6.61730 |
October | 610.00000 | 24.24023 | 61.46034 | 0.79689 | 18.83364 |
November | 591.00000 | 24.14272 | 57.52917 | 0.71307 | 15.91114 |
December | 609.00000 | 23.93932 | 55.43052 | 0.60513 | 13.00230 |
Annual Sum or Average | 7187.00000 | 24.14359 | 59.41966 | 0.40471 | 10.94654 |
Minimum of Months | 551.00000 | 23.72283 | 50.83865 | -0.0356 | 5.99918 |
Maximum of Months | 612.00000 | 24.38334 | 68.95265 | 0.79689 | 18.83364 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.59899 | 48.13760 | 1.14951 | 33.80255 |
February | 551.00000 | 25.78738 | 50.95620 | 1.22187 | 36.88802 |
March | 612.00000 | 25.93929 | 48.99806 | 1.25123 | 38.11041 |
April | 590.00000 | 26.05471 | 52.76993 | 1.32908 | 41.93052 |
May | 611.00000 | 26.23001 | 57.00829 | 0.92503 | 24.07158 |
June | 592.00000 | 27.14586 | 63.41501 | 1.30784 | 41.96408 |
July | 609.00000 | 28.34585 | 65.71720 | 1.75299 | 61.32430 |
August | 612.00000 | 28.72510 | 66.87881 | 1.90560 | 67.93097 |
September | 590.00000 | 27.60722 | 65.30087 | 1.49474 | 50.06364 |
October | 610.00000 | 26.39662 | 59.05784 | 1.51556 | 51.42230 |
November | 591.00000 | 26.07247 | 54.44451 | 1.36948 | 43.99559 |
December | 609.00000 | 25.86272 | 51.63636 | 1.25947 | 38.58659 |
Annual Sum or Average | 7187.00000 | 26.65369 | 57.05625 | 1.37475 | 44.23041 |
Minimum of Months | 551.00000 | 25.59899 | 48.13760 | 0.92503 | 24.07158 |
Maximum of Months | 612.00000 | 28.72510 | 66.87881 | 1.90560 | 67.93097 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.315391E+11 | 0.970135E+10 | 454.14 | 0.220898E+11 | 0.944936E+10 | 0.00 | 0.84 | 24-JAN-13:00 | 0.00 | 01-JAN-00:10 | 47728.08 | 24-JAN-13:00 | 34078.84 | 23-JAN-14:00 | 21261.87 | 30-JAN-14:00 | 12871.38 | 24-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 0.374342E+11 | 0.112080E+11 | 447.89 | 0.256872E+11 | 0.117471E+11 | 0.00 | 1.00 | 07-FEB-12:43 | 0.00 | 01-FEB-00:03 | 60585.26 | 07-FEB-13:00 | 44071.24 | 06-FEB-14:00 | 25797.88 | 06-FEB-18:20 | 16218.13 | 07-FEB-13:00 | 0.00 | 01-FEB-00:03 |
March | 0.532663E+11 | 0.157082E+11 | 524.39 | 0.389025E+11 | 0.143639E+11 | 0.00 | 1.00 | 01-MAR-18:03 | 0.00 | 01-MAR-00:03 | 66361.64 | 28-MAR-11:23 | 59256.07 | 27-MAR-11:13 | 29586.19 | 28-MAR-18:00 | 19178.56 | 27-MAR-11:03 | 0.00 | 01-MAR-00:03 |
April | 0.761488E+11 | 0.216266E+11 | 547.36 | 0.537542E+11 | 0.223946E+11 | 0.00 | 1.00 | 03-APR-11:05 | 0.00 | 01-APR-00:01 | 85461.78 | 29-APR-19:00 | 71566.66 | 28-APR-11:55 | 42574.92 | 29-APR-19:00 | 25706.30 | 28-APR-11:55 | 0.00 | 01-APR-00:01 |
May | 0.114891E+12 | 0.328718E+11 | 588.12 | 0.808474E+11 | 0.340431E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:01 | 125482.57 | 18-MAY-04:02 | 91550.70 | 12-MAY-04:01 | 87392.70 | 30-MAY-04:01 | 33711.43 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.145313E+12 | 0.412145E+11 | 573.34 | 0.881047E+11 | 0.572086E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:01 | 125482.57 | 24-JUN-04:02 | 80146.50 | 02-JUN-04:01 | 88117.83 | 27-JUN-04:01 | 36238.24 | 09-JUN-12:00 | 0.00 | 01-JUN-00:01 |
July | 0.177985E+12 | 0.517920E+11 | 612.48 | 0.103335E+12 | 0.746504E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:01 | 125482.57 | 06-JUL-05:03 | 87203.54 | 04-JUL-04:01 | 91746.72 | 05-JUL-04:02 | 36886.40 | 21-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.188373E+12 | 0.548416E+11 | 620.37 | 0.106615E+12 | 0.817579E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 | 125482.57 | 31-AUG-04:01 | 85819.48 | 16-AUG-12:00 | 87415.84 | 08-AUG-04:01 | 38991.77 | 10-AUG-12:55 | 0.00 | 01-AUG-00:01 |
September | 0.157708E+12 | 0.438243E+11 | 577.73 | 0.882039E+11 | 0.695046E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:01 | 125482.57 | 12-SEP-04:02 | 77273.67 | 13-SEP-04:01 | 89954.87 | 11-SEP-04:02 | 36231.60 | 07-SEP-11:53 | 0.00 | 01-SEP-00:01 |
October | 0.119883E+12 | 0.326952E+11 | 586.45 | 0.741352E+11 | 0.457475E+11 | 0.00 | 1.00 | 01-OCT-04:02 | 0.00 | 01-OCT-00:01 | 125482.57 | 13-OCT-04:01 | 75036.72 | 04-OCT-04:01 | 89639.89 | 08-OCT-04:01 | 31903.69 | 07-OCT-19:00 | 0.00 | 01-OCT-00:01 |
November | 0.790207E+11 | 0.218796E+11 | 547.63 | 0.517139E+11 | 0.273068E+11 | 0.00 | 1.00 | 01-NOV-04:02 | 0.00 | 01-NOV-00:01 | 125482.57 | 02-NOV-04:01 | 59668.10 | 02-NOV-04:01 | 66519.09 | 03-NOV-04:01 | 31212.55 | 02-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.471561E+11 | 0.138417E+11 | 507.05 | 0.308421E+11 | 0.163140E+11 | 0.00 | 1.00 | 05-DEC-12:40 | 0.00 | 01-DEC-00:05 | 63673.68 | 05-DEC-13:00 | 37974.26 | 01-DEC-13:00 | 30499.91 | 05-DEC-13:00 | 16070.40 | 05-DEC-13:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.122872E+13 | 0.351205E+12 | 6586.94 | 0.764230E+12 | 0.464488E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.315391E+11 | 0.970135E+10 | 447.89 | 0.220898E+11 | 0.944936E+10 | 0.00 | 0.84 | 0.00 | 47728.08 | 34078.84 | 21261.87 | 12871.38 | 0.00 | |||||||
Maximum of Months | 0.188373E+12 | 0.548416E+11 | 620.37 | 0.106615E+12 | 0.817579E+11 | 0.00 | 1.00 | 0.00 | 125482.57 | 91550.70 | 91746.72 | 38991.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.216697E+11 | 0.563258E+10 | 526.56 | 0.146940E+11 | 0.697572E+10 | 0.00 | 1.00 | 05-JAN-05:01 | 0.00 | 01-JAN-00:10 | 41359.98 | 07-JAN-05:01 | 31126.31 | 05-JAN-05:01 | 19406.02 | 06-JAN-04:21 | 10092.94 | 06-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.254842E+11 | 0.643985E+10 | 516.08 | 0.170375E+11 | 0.844668E+10 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:03 | 41359.98 | 17-FEB-05:01 | 27859.00 | 16-FEB-05:01 | 18622.27 | 07-FEB-04:31 | 10092.94 | 03-FEB-05:01 | 0.00 | 01-FEB-00:03 |
March | 0.357866E+11 | 0.895780E+10 | 624.67 | 0.261713E+11 | 0.961532E+10 | 0.00 | 1.00 | 01-MAR-04:02 | 0.00 | 01-MAR-01:01 | 43764.85 | 28-MAR-11:00 | 39028.06 | 27-MAR-10:58 | 23452.56 | 24-MAR-03:31 | 11244.04 | 27-MAR-11:00 | 0.00 | 01-MAR-00:03 |
April | 0.516943E+11 | 0.126205E+11 | 656.02 | 0.371365E+11 | 0.145578E+11 | 0.00 | 1.00 | 01-APR-10:31 | 0.00 | 01-APR-00:01 | 45953.66 | 29-APR-19:17 | 41570.83 | 28-APR-12:15 | 25602.91 | 29-APR-19:55 | 13099.66 | 28-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.764278E+11 | 0.192166E+11 | 704.87 | 0.567137E+11 | 0.197141E+11 | 0.00 | 1.00 | 01-MAY-03:32 | 0.00 | 01-MAY-00:01 | 45953.66 | 16-MAY-03:32 | 42795.22 | 31-MAY-18:00 | 29619.57 | 30-MAY-03:22 | 13002.09 | 31-MAY-19:00 | 0.00 | 01-MAY-00:01 |
June | 0.905075E+11 | 0.228824E+11 | 684.19 | 0.581590E+11 | 0.323485E+11 | 0.00 | 1.00 | 01-JUN-00:08 | 0.00 | 01-JUN-00:01 | 45953.66 | 24-JUN-07:55 | 42828.88 | 27-JUN-11:02 | 32159.98 | 08-JUN-03:22 | 13005.53 | 12-JUN-11:53 | 0.00 | 01-JUN-00:01 |
July | 0.101329E+12 | 0.263945E+11 | 709.10 | 0.638331E+11 | 0.374957E+11 | 0.00 | 1.00 | 01-JUL-00:09 | 0.00 | 01-JUL-00:01 | 45953.66 | 06-JUL-05:20 | 42719.38 | 29-JUL-16:33 | 31419.80 | 27-JUL-03:50 | 13882.71 | 21-JUL-11:53 | 0.00 | 01-JUL-00:01 |
August | 0.103214E+12 | 0.268867E+11 | 709.86 | 0.636892E+11 | 0.395252E+11 | 0.00 | 1.00 | 01-AUG-00:06 | 0.00 | 01-AUG-00:01 | 45953.66 | 31-AUG-04:03 | 42759.23 | 15-AUG-11:25 | 32403.27 | 08-AUG-03:50 | 13762.40 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 0.945358E+11 | 0.234832E+11 | 684.78 | 0.552239E+11 | 0.393119E+11 | 0.00 | 1.00 | 01-SEP-00:07 | 0.00 | 01-SEP-00:01 | 45953.66 | 11-SEP-05:40 | 42467.61 | 04-SEP-11:53 | 31477.91 | 10-SEP-06:00 | 12647.54 | 26-SEP-13:00 | 0.00 | 01-SEP-00:01 |
October | 0.802328E+11 | 0.192956E+11 | 704.33 | 0.503594E+11 | 0.298735E+11 | 0.00 | 1.00 | 01-OCT-00:08 | 0.00 | 01-OCT-00:01 | 45953.66 | 01-OCT-07:53 | 39050.61 | 09-OCT-10:43 | 33592.49 | 07-OCT-03:22 | 11515.89 | 05-OCT-12:00 | 0.00 | 01-OCT-00:01 |
November | 0.536834E+11 | 0.127956E+11 | 658.35 | 0.352450E+11 | 0.184384E+11 | 0.00 | 1.00 | 01-NOV-03:22 | 0.00 | 01-NOV-00:01 | 45953.66 | 07-NOV-17:05 | 31006.15 | 20-NOV-05:02 | 27663.11 | 08-NOV-04:22 | 10955.98 | 01-NOV-13:55 | 0.00 | 01-NOV-00:01 |
December | 0.326413E+11 | 0.806607E+10 | 587.38 | 0.205791E+11 | 0.120622E+11 | 0.00 | 1.00 | 01-DEC-04:31 | 0.00 | 01-DEC-01:01 | 42773.74 | 10-DEC-04:22 | 29528.10 | 19-DEC-05:01 | 24481.01 | 26-DEC-04:11 | 10189.30 | 10-DEC-04:22 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.767207E+12 | 0.192671E+12 | 7766.19 | 0.498842E+12 | 0.268365E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.216697E+11 | 0.563258E+10 | 516.08 | 0.146940E+11 | 0.697572E+10 | 0.00 | 1.00 | 0.00 | 41359.98 | 27859.00 | 18622.27 | 10092.94 | 0.00 | |||||||
Maximum of Months | 0.103214E+12 | 0.268867E+11 | 709.86 | 0.638331E+11 | 0.395252E+11 | 0.00 | 1.00 | 0.00 | 45953.66 | 42828.88 | 33592.49 | 13882.71 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 150.78 | 45.48 | 105.30 | 197.70 | 158.79 | 0.00 | 0.00 | 0.00 |
February | 164.65 | 44.62 | 120.02 | 237.99 | 132.98 | 0.00 | 0.00 | 0.00 |
March | 182.03 | 44.90 | 137.13 | 300.04 | 100.91 | 0.00 | 0.00 | 0.00 |
April | 221.59 | 64.48 | 157.11 | 429.19 | 64.00 | 0.00 | 0.00 | 0.00 |
May | 247.24 | 78.74 | 168.51 | 573.41 | 19.71 | 0.83 | 0.00 | 0.00 |
June | 242.19 | 74.04 | 168.15 | 597.49 | 7.19 | 0.50 | 0.00 | 0.00 |
July | 226.08 | 65.14 | 160.94 | 633.63 | 0.37 | 1.50 | 0.00 | 0.00 |
August | 231.57 | 71.10 | 160.47 | 644.24 | 0.28 | 0.00 | 0.00 | 0.00 |
September | 217.57 | 67.21 | 150.36 | 536.22 | 10.44 | 3.00 | 0.00 | 0.00 |
October | 197.38 | 64.39 | 132.99 | 428.50 | 33.21 | 2.00 | 0.00 | 0.00 |
November | 165.34 | 52.22 | 113.12 | 299.49 | 76.80 | 0.00 | 0.00 | 0.00 |
December | 134.06 | 36.86 | 97.20 | 190.88 | 134.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.50 | 59.16 | 139.35 | 423.44 | 61.22 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 134.06 | 36.86 | 97.20 | 190.88 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 247.24 | 78.74 | 168.51 | 644.24 | 158.79 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.36 | 177.27 | 198.10 | 567.35 | 217.32 | 0.00 | 0.00 | 0.00 |
February | 350.90 | 143.52 | 207.38 | 558.71 | 186.09 | 0.00 | 0.00 | 0.00 |
March | 285.77 | 75.42 | 210.35 | 502.22 | 145.88 | 0.00 | 0.00 | 0.00 |
April | 228.22 | 25.21 | 203.01 | 472.57 | 93.75 | 0.00 | 0.00 | 0.00 |
May | 193.08 | 3.64 | 189.44 | 526.35 | 28.79 | 0.83 | 0.00 | 0.00 |
June | 181.09 | 0.22 | 180.86 | 544.14 | 10.45 | 0.50 | 0.00 | 0.00 |
July | 180.84 | 1.20 | 179.64 | 634.32 | 0.52 | 1.50 | 0.00 | 0.00 |
August | 209.19 | 13.92 | 195.28 | 702.72 | 0.38 | 0.00 | 0.00 | 0.00 |
September | 277.29 | 63.76 | 213.53 | 725.72 | 14.58 | 3.00 | 0.00 | 0.00 |
October | 363.20 | 144.76 | 218.44 | 773.38 | 46.31 | 2.00 | 0.00 | 0.00 |
November | 401.97 | 194.75 | 207.23 | 727.47 | 107.02 | 0.00 | 0.00 | 0.00 |
December | 371.99 | 184.08 | 187.90 | 592.18 | 184.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.51 | 85.33 | 199.18 | 610.95 | 85.83 | 7.83 | 0.00 | 0.00 |
Minimum of Months | 180.84 | 0.22 | 179.64 | 472.57 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 401.97 | 194.75 | 218.44 | 773.38 | 217.32 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.56 | 42.73 | 105.83 | 201.32 | 166.83 | 0.00 | 0.00 | 0.00 |
February | 169.55 | 48.51 | 121.04 | 251.90 | 139.10 | 0.00 | 0.00 | 0.00 |
March | 200.28 | 59.30 | 140.98 | 336.26 | 106.01 | 0.00 | 0.00 | 0.00 |
April | 219.00 | 61.52 | 157.47 | 423.42 | 67.39 | 0.00 | 0.00 | 0.00 |
May | 238.24 | 71.30 | 166.94 | 554.56 | 20.42 | 0.67 | 0.00 | 0.00 |
June | 246.11 | 77.55 | 168.57 | 600.93 | 7.39 | 0.33 | 0.00 | 0.00 |
July | 225.73 | 64.46 | 161.27 | 629.51 | 0.34 | 1.33 | 0.00 | 0.00 |
August | 231.60 | 70.28 | 161.32 | 642.00 | 0.24 | 0.00 | 0.00 | 0.00 |
September | 220.69 | 69.43 | 151.26 | 538.85 | 10.25 | 2.67 | 0.00 | 0.00 |
October | 196.30 | 63.64 | 132.66 | 424.10 | 33.81 | 1.83 | 0.00 | 0.00 |
November | 168.78 | 55.38 | 113.40 | 308.12 | 81.61 | 0.00 | 0.00 | 0.00 |
December | 140.74 | 42.37 | 98.37 | 209.26 | 141.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.58 | 60.58 | 140.00 | 427.67 | 64.19 | 6.83 | 0.00 | 0.00 |
Minimum of Months | 140.74 | 42.37 | 98.37 | 201.32 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 246.11 | 77.55 | 168.57 | 642.00 | 166.83 | 2.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.403852E+09 | 0.121807E+09 | 0.282045E+09 | 0.529524E+09 | 0.425309E+09 |
February | 0.398315E+09 | 0.107953E+09 | 0.290362E+09 | 0.575749E+09 | 0.321699E+09 |
March | 0.487539E+09 | 0.120260E+09 | 0.367279E+09 | 0.803626E+09 | 0.270291E+09 |
April | 0.574366E+09 | 0.167138E+09 | 0.407227E+09 | 0.111246E+10 | 0.165878E+09 |
May | 0.662213E+09 | 0.210887E+09 | 0.451326E+09 | 0.153583E+10 | 52788676.80 |
June | 0.627756E+09 | 0.191905E+09 | 0.435851E+09 | 0.154870E+10 | 18632849.01 |
July | 0.605530E+09 | 0.174479E+09 | 0.431051E+09 | 0.169711E+10 | 984768.47 |
August | 0.620233E+09 | 0.190426E+09 | 0.429808E+09 | 0.172553E+10 | 755959.84 |
September | 0.563950E+09 | 0.174212E+09 | 0.389738E+09 | 0.138989E+10 | 27057494.80 |
October | 0.528668E+09 | 0.172460E+09 | 0.356207E+09 | 0.114769E+10 | 88960148.48 |
November | 0.428573E+09 | 0.135354E+09 | 0.293219E+09 | 0.776274E+09 | 0.199064E+09 |
December | 0.359053E+09 | 98724595.84 | 0.260329E+09 | 0.511247E+09 | 0.359108E+09 |
Annual Sum or Average | 0.626005E+10 | 0.186561E+10 | 0.439444E+10 | 0.133536E+11 | 0.193053E+10 |
Minimum of Months | 0.359053E+09 | 98724595.84 | 0.260329E+09 | 0.511247E+09 | 755959.84 |
Maximum of Months | 0.662213E+09 | 0.210887E+09 | 0.451326E+09 | 0.172553E+10 | 0.425309E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100537E+10 | 0.474797E+09 | 0.530578E+09 | 0.151959E+10 | 0.582075E+09 |
February | 0.848898E+09 | 0.347198E+09 | 0.501700E+09 | 0.135164E+10 | 0.450186E+09 |
March | 0.765409E+09 | 0.201996E+09 | 0.563414E+09 | 0.134515E+10 | 0.390726E+09 |
April | 0.591541E+09 | 65334216.03 | 0.526207E+09 | 0.122491E+10 | 0.242998E+09 |
May | 0.517154E+09 | 9758207.31 | 0.507396E+09 | 0.140977E+10 | 77111879.45 |
June | 0.469381E+09 | 580490.77 | 0.468800E+09 | 0.141040E+10 | 27087842.32 |
July | 0.484351E+09 | 3204865.85 | 0.481147E+09 | 0.169897E+10 | 1390363.07 |
August | 0.560307E+09 | 37270545.30 | 0.523037E+09 | 0.188216E+10 | 1029054.65 |
September | 0.718745E+09 | 0.165272E+09 | 0.553472E+09 | 0.188108E+10 | 37779053.83 |
October | 0.972804E+09 | 0.387733E+09 | 0.585071E+09 | 0.207142E+10 | 0.124040E+09 |
November | 0.104192E+10 | 0.504791E+09 | 0.537128E+09 | 0.188560E+10 | 0.277402E+09 |
December | 0.996325E+09 | 0.493047E+09 | 0.503277E+09 | 0.158610E+10 | 0.494863E+09 |
Annual Sum or Average | 0.897221E+10 | 0.269098E+10 | 0.628123E+10 | 0.192668E+11 | 0.270669E+10 |
Minimum of Months | 0.469381E+09 | 580490.77 | 0.468800E+09 | 0.122491E+10 | 1029054.65 |
Maximum of Months | 0.104192E+10 | 0.504791E+09 | 0.585071E+09 | 0.207142E+10 | 0.582075E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397897E+09 | 0.114453E+09 | 0.283444E+09 | 0.539221E+09 | 0.446850E+09 |
February | 0.410173E+09 | 0.117346E+09 | 0.292827E+09 | 0.609403E+09 | 0.336504E+09 |
March | 0.536435E+09 | 0.158823E+09 | 0.377613E+09 | 0.900628E+09 | 0.283940E+09 |
April | 0.567641E+09 | 0.159470E+09 | 0.408171E+09 | 0.109750E+10 | 0.174669E+09 |
May | 0.638114E+09 | 0.190981E+09 | 0.447133E+09 | 0.148532E+10 | 54698227.18 |
June | 0.637928E+09 | 0.200997E+09 | 0.436930E+09 | 0.155762E+10 | 19152193.42 |
July | 0.604602E+09 | 0.172661E+09 | 0.431940E+09 | 0.168608E+10 | 901055.98 |
August | 0.620321E+09 | 0.188250E+09 | 0.432070E+09 | 0.171952E+10 | 653918.90 |
September | 0.572036E+09 | 0.179958E+09 | 0.392078E+09 | 0.139669E+10 | 26567470.69 |
October | 0.525773E+09 | 0.170450E+09 | 0.355324E+09 | 0.113592E+10 | 90561305.03 |
November | 0.437471E+09 | 0.143536E+09 | 0.293935E+09 | 0.798636E+09 | 0.211543E+09 |
December | 0.376967E+09 | 0.113494E+09 | 0.263474E+09 | 0.560481E+09 | 0.378162E+09 |
Annual Sum or Average | 0.632536E+10 | 0.191042E+10 | 0.441494E+10 | 0.134870E+11 | 0.202420E+10 |
Minimum of Months | 0.376967E+09 | 0.113494E+09 | 0.263474E+09 | 0.539221E+09 | 653918.90 |
Maximum of Months | 0.638114E+09 | 0.200997E+09 | 0.447133E+09 | 0.171952E+10 | 0.446850E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 953.66 | 530.23 | 674.70 | 265.48 | 409.22 | 0.00 | 0.00 |
February | 1038.66 | 448.22 | 685.10 | 236.65 | 448.45 | 0.00 | 0.00 |
March | 1131.46 | 345.75 | 668.08 | 179.61 | 488.47 | 0.00 | 0.00 |
April | 1320.59 | 220.55 | 668.81 | 151.21 | 517.59 | 0.00 | 0.00 |
May | 1652.21 | 66.82 | 678.57 | 153.68 | 524.89 | 0.00 | 0.00 |
June | 1742.28 | 24.75 | 669.39 | 151.81 | 517.59 | 0.00 | 0.00 |
July | 1897.45 | 1.22 | 632.65 | 130.80 | 501.84 | 0.00 | 0.00 |
August | 1988.95 | 0.91 | 672.36 | 155.30 | 517.07 | 0.00 | 0.00 |
September | 1800.28 | 34.75 | 715.56 | 200.40 | 515.16 | 0.00 | 0.00 |
October | 1624.35 | 111.71 | 756.89 | 272.79 | 484.10 | 0.00 | 0.00 |
November | 1330.09 | 260.45 | 736.10 | 302.35 | 433.75 | 0.00 | 0.00 |
December | 983.84 | 451.54 | 646.78 | 263.32 | 383.47 | 0.00 | 0.00 |
Annual Sum or Average | 1457.72 | 206.90 | 683.59 | 205.07 | 478.52 | 0.00 | 0.00 |
Minimum of Months | 953.66 | 0.91 | 632.65 | 130.80 | 383.47 | 0.00 | 0.00 |
Maximum of Months | 1988.95 | 530.23 | 756.89 | 302.35 | 524.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255428E+10 | 0.142018E+10 | 0.180712E+10 | 0.711056E+09 | 0.109607E+10 | 0.00 | 0.00 |
February | 0.251273E+10 | 0.108432E+10 | 0.165739E+10 | 0.572496E+09 | 0.108489E+10 | 0.00 | 0.00 |
March | 0.303051E+10 | 0.926061E+09 | 0.178938E+10 | 0.481078E+09 | 0.130831E+10 | 0.00 | 0.00 |
April | 0.342298E+10 | 0.571654E+09 | 0.173355E+10 | 0.391943E+09 | 0.134161E+10 | 0.00 | 0.00 |
May | 0.442528E+10 | 0.178968E+09 | 0.181748E+10 | 0.411627E+09 | 0.140585E+10 | 0.00 | 0.00 |
June | 0.451599E+10 | 64141838.07 | 0.173506E+10 | 0.393483E+09 | 0.134158E+10 | 0.00 | 0.00 |
July | 0.508213E+10 | 3255128.29 | 0.169448E+10 | 0.350345E+09 | 0.134414E+10 | 0.00 | 0.00 |
August | 0.532721E+10 | 2437943.17 | 0.180086E+10 | 0.415946E+09 | 0.138491E+10 | 0.00 | 0.00 |
September | 0.466633E+10 | 90073057.65 | 0.185473E+10 | 0.519442E+09 | 0.133529E+10 | 0.00 | 0.00 |
October | 0.435066E+10 | 0.299194E+09 | 0.202724E+10 | 0.730643E+09 | 0.129660E+10 | 0.00 | 0.00 |
November | 0.344759E+10 | 0.675080E+09 | 0.190796E+10 | 0.783681E+09 | 0.112428E+10 | 0.00 | 0.00 |
December | 0.263511E+10 | 0.120942E+10 | 0.173235E+10 | 0.705266E+09 | 0.102708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459708E+11 | 0.652478E+10 | 0.215576E+11 | 0.646701E+10 | 0.150906E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251273E+10 | 2437943.17 | 0.165739E+10 | 0.350345E+09 | 0.102708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532721E+10 | 0.142018E+10 | 0.202724E+10 | 0.783681E+09 | 0.140585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638017E+10 | -0.622520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154961178.0 | 81.21 | 0.00 | 0.00 |
February | 0.577382E+10 | -0.563431E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -139507216.3 | 81.21 | 0.00 | 0.00 |
March | 0.644794E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154069194.1 | 81.21 | 0.00 | 0.00 |
April | 0.619225E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148773556.9 | 81.22 | 0.00 | 0.00 |
May | 0.641341E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153226609.9 | 81.21 | 0.00 | 0.00 |
June | 0.623273E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -146151789.1 | 81.21 | 0.00 | 0.00 |
July | 0.636524E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148164273.4 | 81.22 | 0.00 | 0.00 |
August | 0.644243E+10 | -0.629519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147237229.0 | 81.22 | 0.00 | 0.00 |
September | 0.618988E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -145075756.8 | 81.22 | 0.00 | 0.00 |
October | 0.637662E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152792551.6 | 81.21 | 0.00 | 0.00 |
November | 0.617330E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148676656.2 | 81.21 | 0.00 | 0.00 |
December | 0.637136E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154258021.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753591E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179289E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577382E+10 | -0.629519E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -154961178.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644794E+10 | -0.563431E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -139507216.3 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.174401E+11 | -0.165952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844928416.3 | 58.99 | 0.00 | 0.00 |
February | 0.153509E+11 | -0.145922E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -758696994.2 | 58.98 | 0.00 | 0.00 |
March | 0.159970E+11 | -0.151603E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -836704850.2 | 58.99 | 0.00 | 0.00 |
April | 0.138808E+11 | -0.130744E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -806443971.0 | 58.98 | 0.00 | 0.00 |
May | 0.128696E+11 | -0.120408E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -828845780.9 | 58.98 | 0.00 | 0.00 |
June | 0.114407E+11 | -0.106582E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -782503350.5 | 58.98 | 0.00 | 0.00 |
July | 0.113277E+11 | -0.105454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -782287894.7 | 58.98 | 0.00 | 0.00 |
August | 0.119406E+11 | -0.111667E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -773972505.0 | 58.98 | 0.00 | 0.00 |
September | 0.126305E+11 | -0.118577E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -772800812.7 | 58.99 | 0.00 | 0.00 |
October | 0.145671E+11 | -0.137421E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -824981817.6 | 58.99 | 0.00 | 0.00 |
November | 0.155476E+11 | -0.147419E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -805716207.2 | 58.98 | 0.00 | 0.00 |
December | 0.170937E+11 | -0.162554E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838322538.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.170086E+12 | -0.160430E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.965621E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.113277E+11 | -0.165952E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -844928416.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.174401E+11 | -0.105454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -758696994.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.77 | 0.75 | 01-JAN-07:00 | 771.95 | 24.51 | 219.00 | 292.33 | 741.26 | 24.23 | 220.33 | 292.67 |
February | 308.33 | 0.77 | 0.75 | 01-FEB-07:00 | 720.36 | 21.84 | 153.17 | 268.83 | 710.43 | 21.89 | 159.50 | 268.33 |
March | 357.50 | 0.77 | 0.75 | 01-MAR-08:20 | 723.34 | 19.89 | 100.00 | 312.17 | 705.90 | 20.00 | 114.17 | 313.00 |
April | 375.00 | 0.77 | 0.75 | 01-APR-07:30 | 699.66 | 19.31 | 81.67 | 328.83 | 612.17 | 19.36 | 83.17 | 326.33 |
May | 405.33 | 0.77 | 0.75 | 01-MAY-06:40 | 622.53 | 19.22 | 71.67 | 356.83 | 625.74 | 19.20 | 73.00 | 356.67 |
June | 403.50 | 0.77 | 0.75 | 01-JUN-06:49 | 587.75 | 20.73 | 106.50 | 348.50 | 612.98 | 19.18 | 71.83 | 348.67 |
July | 405.00 | 0.78 | 0.75 | 01-JUL-06:00 | 581.58 | 19.51 | 79.67 | 347.33 | 592.68 | 19.04 | 77.00 | 346.33 |
August | 395.83 | 0.77 | 0.75 | 01-AUG-06:00 | 692.92 | 19.49 | 99.50 | 345.67 | 638.66 | 19.50 | 103.17 | 344.67 |
September | 358.83 | 0.77 | 0.75 | 01-SEP-07:10 | 747.90 | 20.21 | 124.33 | 322.33 | 701.39 | 20.18 | 125.33 | 319.83 |
October | 351.17 | 0.77 | 0.75 | 01-OCT-07:10 | 791.03 | 21.40 | 177.33 | 318.00 | 867.05 | 22.17 | 202.83 | 316.83 |
November | 318.83 | 0.76 | 0.75 | 01-NOV-06:00 | 858.62 | 24.44 | 237.17 | 296.17 | 832.82 | 24.60 | 239.17 | 298.17 |
December | 319.00 | 0.77 | 0.75 | 01-DEC-07:30 | 780.12 | 24.36 | 218.33 | 285.50 | 732.02 | 24.25 | 217.00 | 286.17 |
Annual Sum or Average | 4323.33 | 0.77 | 708.26 | 21.08 | 1668.33 | 3822.50 | 691.80 | 20.95 | 1686.50 | 3817.67 | ||
Minimum of Months | 308.33 | 0.76 | 0.75 | 581.58 | 19.22 | 71.67 | 268.83 | 592.68 | 19.04 | 71.83 | 268.33 | |
Maximum of Months | 405.33 | 0.78 | 0.75 | 858.62 | 24.51 | 237.17 | 356.83 | 867.05 | 24.60 | 239.17 | 356.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4241628.88 | 639.84 | 16-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4241628.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4241628.88 | 639.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.315391E+11 | 0.220898E+11 | 47728.08 | 24-JAN-13:00 | 26740.22 | 0.00 |
February | 0.00 | 0.00 | 0.374342E+11 | 0.256872E+11 | 60585.26 | 07-FEB-13:00 | 43915.14 | 0.00 |
March | 0.00 | 0.00 | 0.532663E+11 | 0.389025E+11 | 66361.64 | 28-MAR-11:23 | 38742.66 | 0.00 |
April | 0.00 | 0.00 | 0.761488E+11 | 0.537542E+11 | 85461.78 | 29-APR-19:00 | 42886.87 | 0.00 |
May | 0.00 | 0.00 | 0.114891E+12 | 0.808474E+11 | 125482.57 | 18-MAY-04:02 | 52815.32 | 0.00 |
June | 0.00 | 0.00 | 0.145313E+12 | 0.881047E+11 | 125482.57 | 24-JUN-04:02 | 39345.68 | 0.00 |
July | 0.00 | 0.00 | 0.177985E+12 | 0.103335E+12 | 125482.57 | 06-JUL-05:03 | 48095.84 | 0.00 |
August | 0.00 | 0.00 | 0.188373E+12 | 0.106615E+12 | 125482.57 | 31-AUG-04:01 | 44924.43 | 0.00 |
September | 0.00 | 0.00 | 0.157708E+12 | 0.882039E+11 | 125482.57 | 12-SEP-04:02 | 38788.59 | 0.00 |
October | 0.00 | 0.00 | 0.119883E+12 | 0.741352E+11 | 125482.57 | 13-OCT-04:01 | 65614.33 | 0.00 |
November | 0.00 | 0.00 | 0.790207E+11 | 0.517139E+11 | 125482.57 | 02-NOV-04:01 | 59668.10 | 0.00 |
December | 0.00 | 0.00 | 0.471561E+11 | 0.308421E+11 | 63673.68 | 05-DEC-13:00 | 33173.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122872E+13 | 0.764230E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.315391E+11 | 0.220898E+11 | 47728.08 | 26740.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188373E+12 | 0.106615E+12 | 125482.57 | 65614.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216697E+11 | 0.146940E+11 | 41359.98 | 07-JAN-05:01 | 26148.37 | 0.00 |
February | 0.00 | 0.00 | 0.254842E+11 | 0.170375E+11 | 41359.98 | 17-FEB-05:01 | 26608.77 | 0.00 |
March | 0.00 | 0.00 | 0.357866E+11 | 0.261713E+11 | 43764.85 | 28-MAR-11:00 | 23962.40 | 0.00 |
April | 0.00 | 0.00 | 0.516943E+11 | 0.371365E+11 | 45953.66 | 29-APR-19:17 | 21861.18 | 0.00 |
May | 0.00 | 0.00 | 0.764278E+11 | 0.567137E+11 | 45953.66 | 16-MAY-03:32 | 20582.99 | 0.00 |
June | 0.00 | 0.00 | 0.905075E+11 | 0.581590E+11 | 45953.66 | 24-JUN-07:55 | 17997.04 | 0.00 |
July | 0.00 | 0.00 | 0.101329E+12 | 0.638331E+11 | 45953.66 | 06-JUL-05:20 | 16563.78 | 0.00 |
August | 0.00 | 0.00 | 0.103214E+12 | 0.636892E+11 | 45953.66 | 31-AUG-04:03 | 20794.52 | 0.00 |
September | 0.00 | 0.00 | 0.945358E+11 | 0.552239E+11 | 45953.66 | 11-SEP-05:40 | 15657.47 | 0.00 |
October | 0.00 | 0.00 | 0.802328E+11 | 0.503594E+11 | 45953.66 | 01-OCT-07:53 | 17299.05 | 0.00 |
November | 0.00 | 0.00 | 0.536834E+11 | 0.352450E+11 | 45953.66 | 07-NOV-17:05 | 22987.07 | 0.00 |
December | 0.00 | 0.00 | 0.326413E+11 | 0.205791E+11 | 42773.74 | 10-DEC-04:22 | 21864.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.767207E+12 | 0.498842E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.216697E+11 | 0.146940E+11 | 41359.98 | 15657.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103214E+12 | 0.638331E+11 | 45953.66 | 26608.77 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6661.33 | 12637.03 | 06-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6497.25 | 12518.71 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6126.86 | 11942.37 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5512.13 | 10852.83 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4964.78 | 9831.80 | 01-MAY-18:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4583.57 | 8865.95 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4409.04 | 8403.69 | 31-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4639.98 | 9002.64 | 31-AUG-19:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5044.19 | 9927.23 | 29-SEP-18:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5598.44 | 11110.66 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6153.91 | 12046.51 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 6534.30 | 12581.26 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 5555.38 | ||||
Minimum of Months | 0.00 | 0.00 | 4409.04 | 8403.69 | ||
Maximum of Months | 0.00 | 0.00 | 6661.33 | 12637.03 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207032E+10 | 0.25 | 824.13 | 01-JAN-00:10 | 0.26 |
February | 0.187955E+10 | 0.25 | 824.13 | 01-FEB-00:03 | 0.26 |
March | 0.209381E+10 | 0.25 | 824.13 | 01-MAR-00:03 | 0.26 |
April | 0.203663E+10 | 0.25 | 824.13 | 01-APR-00:20 | 0.26 |
May | 0.210752E+10 | 0.25 | 824.13 | 01-MAY-00:12 | 0.26 |
June | 0.203651E+10 | 0.25 | 824.13 | 01-JUN-00:08 | 0.26 |
July | 0.210762E+10 | 0.25 | 824.13 | 01-JUL-00:09 | 0.26 |
August | 0.210816E+10 | 0.25 | 824.13 | 01-AUG-00:06 | 0.26 |
September | 0.203799E+10 | 0.25 | 824.13 | 01-SEP-00:07 | 0.26 |
October | 0.210297E+10 | 0.25 | 824.13 | 01-OCT-00:08 | 0.26 |
November | 0.203656E+10 | 0.25 | 824.13 | 01-NOV-00:10 | 0.26 |
December | 0.209169E+10 | 0.25 | 824.13 | 01-DEC-00:05 | 0.26 |
Annual Sum or Average | 0.247093E+11 | 0.25 | |||
Minimum of Months | 0.187955E+10 | 0.25 | 824.13 | 0.26 | |
Maximum of Months | 0.210816E+10 | 0.25 | 824.13 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.697926E+10 | 0.70 | 3151.99 | 16-JAN-06:50 | 0.84 |
February | 0.630381E+10 | 0.70 | 3268.36 | 07-FEB-13:00 | 0.86 |
March | 0.698343E+10 | 0.70 | 3603.12 | 27-MAR-12:00 | 0.92 |
April | 0.681895E+10 | 0.70 | 4854.71 | 29-APR-19:00 | 1.09 |
May | 0.783925E+10 | 0.74 | 7817.08 | 18-MAY-04:02 | 1.37 |
June | 0.921848E+10 | 0.83 | 7817.08 | 01-JUN-04:01 | 1.37 |
July | 0.113022E+11 | 0.91 | 7817.08 | 01-JUL-04:02 | 1.36 |
August | 0.119600E+11 | 0.95 | 7817.08 | 01-AUG-04:01 | 1.36 |
September | 0.991647E+10 | 0.86 | 7817.08 | 01-SEP-04:01 | 1.37 |
October | 0.797169E+10 | 0.75 | 7817.08 | 01-OCT-04:02 | 1.36 |
November | 0.689092E+10 | 0.70 | 7817.08 | 02-NOV-04:01 | 1.37 |
December | 0.697928E+10 | 0.70 | 3299.40 | 05-DEC-13:00 | 0.86 |
Annual Sum or Average | 0.991637E+11 | 0.77 | |||
Minimum of Months | 0.630381E+10 | 0.70 | 3151.99 | 0.84 | |
Maximum of Months | 0.119600E+11 | 0.95 | 7817.08 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165103E+10 | 0.51 | 1806.54 | 06-JAN-05:01 | 0.88 |
February | 0.154570E+10 | 0.52 | 1806.54 | 03-FEB-05:01 | 0.87 |
March | 0.183155E+10 | 0.54 | 1806.54 | 17-MAR-03:11 | 0.87 |
April | 0.217321E+10 | 0.59 | 1806.54 | 18-APR-03:31 | 0.87 |
May | 0.304050E+10 | 0.68 | 1806.54 | 02-MAY-03:31 | 0.87 |
June | 0.362108E+10 | 0.75 | 1806.54 | 01-JUN-04:01 | 0.87 |
July | 0.410992E+10 | 0.78 | 1806.54 | 01-JUL-03:23 | 0.86 |
August | 0.418560E+10 | 0.78 | 1806.54 | 01-AUG-00:06 | 0.86 |
September | 0.376560E+10 | 0.76 | 1806.54 | 01-SEP-00:07 | 0.86 |
October | 0.313752E+10 | 0.69 | 1806.54 | 01-OCT-00:08 | 0.86 |
November | 0.220892E+10 | 0.60 | 1806.54 | 01-NOV-03:22 | 0.87 |
December | 0.178668E+10 | 0.53 | 1806.54 | 10-DEC-04:22 | 0.87 |
Annual Sum or Average | 0.330573E+11 | 0.64 | |||
Minimum of Months | 0.154570E+10 | 0.51 | 1806.54 | 0.86 | |
Maximum of Months | 0.418560E+10 | 0.78 | 1806.54 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 50.91 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 51.33 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.67 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.20 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 54.08 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 55.08 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 55.01 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.84 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 54.92 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 53.54 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:02 | 5.36 | 5.36 | 54.35 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 51.77 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.91 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.08 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.91 | 59.47 | 6661.33 | 12637.03 | 06-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.33 | 58.15 | 6497.25 | 12518.71 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.67 | 58.14 | 6126.86 | 11942.37 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.12 | 53.12 | 5512.13 | 10852.83 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.30 | 53.30 | 4964.78 | 9831.80 | 01-MAY-18:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.31 | 54.31 | 4583.57 | 8865.95 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.62 | 54.62 | 4409.04 | 8403.69 | 31-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.27 | 54.27 | 4639.98 | 9002.64 | 31-AUG-19:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 54.20 | 54.20 | 5044.19 | 9927.23 | 29-SEP-18:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.97 | 51.97 | 5598.44 | 11110.66 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.45 | 53.45 | 6153.91 | 12046.51 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.77 | 58.35 | 6534.30 | 12581.26 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 5555.38 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.91 | 51.97 | 4409.04 | 8403.69 | ||
Maximum of Months | 0.00 | 0.00 | 54.62 | 59.47 | 6661.33 | 12637.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166806E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.175118E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226917E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.284456E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.407111E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.504329E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.630942E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.668016E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.537408E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.406669E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.287705E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.208210E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.450369E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166806E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.668016E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.728361E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.798555E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107893E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147937E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222571E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265035E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.305044E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310723E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.272488E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224332E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150045E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.985276E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.225729E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.728361E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310723E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.697926E+10 | 0.315391E+11 | 4241628.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630381E+10 | 0.374342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698343E+10 | 0.532663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.681895E+10 | 0.761488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.783925E+10 | 0.114891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.921848E+10 | 0.145313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113022E+11 | 0.177985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119600E+11 | 0.188373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.991647E+10 | 0.157708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.797169E+10 | 0.119883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689092E+10 | 0.790207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697928E+10 | 0.471561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.991637E+11 | 0.122872E+13 | 4241628.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630381E+10 | 0.315391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119600E+11 | 0.188373E+12 | 4241628.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165103E+10 | 0.216697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154570E+10 | 0.254842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183155E+10 | 0.357866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217321E+10 | 0.516943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.304050E+10 | 0.764278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.362108E+10 | 0.905075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410992E+10 | 0.101329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418560E+10 | 0.103214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.376560E+10 | 0.945358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313752E+10 | 0.802328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220892E+10 | 0.536834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178668E+10 | 0.326413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330573E+11 | 0.767207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154570E+10 | 0.216697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418560E+10 | 0.103214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.697926E+10 | 0.00 | 0.00 | 0.00 | 0.970135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630381E+10 | 0.00 | 0.00 | 0.00 | 0.112080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.698343E+10 | 0.00 | 0.00 | 0.00 | 0.157082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.681895E+10 | 0.00 | 0.00 | 0.00 | 0.216266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.783925E+10 | 0.00 | 0.00 | 0.00 | 0.328718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.921848E+10 | 0.00 | 0.00 | 0.00 | 0.412145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113022E+11 | 0.00 | 0.00 | 0.00 | 0.517920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119600E+11 | 0.00 | 0.00 | 0.00 | 0.548416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.991647E+10 | 0.00 | 0.00 | 0.00 | 0.438243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.797169E+10 | 0.00 | 0.00 | 0.00 | 0.326952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689092E+10 | 0.00 | 0.00 | 0.00 | 0.218796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697928E+10 | 0.00 | 0.00 | 0.00 | 0.138417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.991637E+11 | 0.00 | 0.00 | 0.00 | 0.351205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.630381E+10 | 0.00 | 0.00 | 0.00 | 0.970135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119600E+11 | 0.00 | 0.00 | 0.00 | 0.548416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165103E+10 | 0.00 | 0.00 | 0.00 | 0.563258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154570E+10 | 0.00 | 0.00 | 0.00 | 0.643985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183155E+10 | 0.00 | 0.00 | 0.00 | 0.895780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217321E+10 | 0.00 | 0.00 | 0.00 | 0.126205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.304050E+10 | 0.00 | 0.00 | 0.00 | 0.192166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.362108E+10 | 0.00 | 0.00 | 0.00 | 0.228824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.410992E+10 | 0.00 | 0.00 | 0.00 | 0.263945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418560E+10 | 0.00 | 0.00 | 0.00 | 0.268867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.376560E+10 | 0.00 | 0.00 | 0.00 | 0.234832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313752E+10 | 0.00 | 0.00 | 0.00 | 0.192956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220892E+10 | 0.00 | 0.00 | 0.00 | 0.127956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178668E+10 | 0.00 | 0.00 | 0.00 | 0.806607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330573E+11 | 0.00 | 0.00 | 0.00 | 0.192671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154570E+10 | 0.00 | 0.00 | 0.00 | 0.563258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418560E+10 | 0.00 | 0.00 | 0.00 | 0.268867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.707712E+10 | 0.692570E+09 | 0.00 | 72965542.64 | 2599.73 | 0.00 | 0.124070E+11 | 0.00 | 3.59 |
February | 0.406704E+10 | 0.276805E+10 | 0.00 | 58523112.94 | 5758340.95 | 0.00 | 0.880131E+10 | 0.00 | 3.61 |
March | 0.236486E+10 | 0.674419E+10 | 0.00 | 53501428.02 | 22389860.85 | 0.00 | 0.664289E+10 | 0.00 | 3.63 |
April | 0.731840E+09 | 0.197379E+11 | 0.00 | 12515864.78 | 0.131942E+09 | 0.00 | 0.223578E+10 | 0.00 | 3.63 |
May | 51043483.29 | 0.438618E+11 | 0.00 | 2631952.03 | 0.794894E+09 | 0.00 | 0.309626E+09 | 0.00 | 3.65 |
June | 9458580.20 | 0.672060E+11 | 0.00 | 2108917.59 | 0.140801E+10 | 0.00 | 66332380.26 | 0.00 | 3.69 |
July | 8827039.45 | 0.893640E+11 | 0.00 | 952051.74 | 0.248738E+10 | 0.00 | 47645045.14 | 0.00 | 3.71 |
August | 122470.29 | 0.957131E+11 | 0.00 | 372507.22 | 0.227417E+10 | 0.00 | 7193783.39 | 0.00 | 3.72 |
September | 2274865.39 | 0.752929E+11 | 0.00 | 1916844.13 | 0.150584E+10 | 0.00 | 60937023.57 | 0.00 | 3.67 |
October | 70569036.87 | 0.467494E+11 | 0.00 | 4170495.79 | 0.732093E+09 | 0.00 | 0.218317E+09 | 0.00 | 3.63 |
November | 0.669885E+09 | 0.199684E+11 | 0.00 | 13515057.35 | 0.115623E+09 | 0.00 | 0.188111E+10 | 0.00 | 3.62 |
December | 0.340974E+10 | 0.481273E+10 | 0.00 | 54378416.25 | 7461293.74 | 0.00 | 0.870942E+10 | 0.00 | 3.60 |
Annual Sum or Average | 0.184628E+11 | 0.472911E+12 | 0.00 | 0.277552E+09 | 0.948557E+10 | 0.00 | 0.413875E+11 | 0.00 | 3.65 |
Minimum of Months | 122470.29 | 0.692570E+09 | 0.00 | 372507.22 | 2599.73 | 0.00 | 7193783.39 | 0.00 | 3.59 |
Maximum of Months | 0.707712E+10 | 0.957131E+11 | 0.00 | 72965542.64 | 0.248738E+10 | 0.00 | 0.124070E+11 | 0.00 | 3.72 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229598E+10 | 0.299933E+09 | 0.00 | 97441201.51 | 0.00 | 0.00 | 0.239275E+11 | 0.00 | 8.19 |
February | 0.929478E+09 | 0.119838E+10 | 0.00 | 90536354.85 | 0.00 | 0.00 | 0.175124E+11 | 0.00 | 8.31 |
March | 0.428088E+09 | 0.305642E+10 | 0.00 | 96136482.93 | 0.00 | 0.00 | 0.145499E+11 | 0.00 | 8.48 |
April | 46708938.75 | 0.991830E+10 | 0.00 | 53798251.20 | 0.00 | 0.00 | 0.502160E+10 | 0.00 | 8.79 |
May | 487659.97 | 0.256082E+11 | 0.00 | 16361103.45 | 1591.70 | 0.00 | 0.790895E+09 | 0.00 | 9.13 |
June | 0.00 | 0.400552E+11 | 0.00 | 1945656.86 | 0.00 | 0.00 | 44565275.44 | 0.00 | 9.59 |
July | 348545.57 | 0.487239E+11 | 0.00 | 1153377.78 | 0.00 | 0.00 | 41054003.77 | 0.00 | 10.14 |
August | 0.00 | 0.500489E+11 | 0.00 | 7403.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
September | 0.00 | 0.434599E+11 | 0.00 | 922362.14 | 0.00 | 0.00 | 21592284.40 | 0.00 | 9.69 |
October | 2299470.46 | 0.290753E+11 | 0.00 | 13868687.55 | 8794.62 | 0.00 | 0.739192E+09 | 0.00 | 9.18 |
November | 50896691.43 | 0.115334E+11 | 0.00 | 46213362.79 | 202340.23 | 0.00 | 0.440674E+10 | 0.00 | 8.78 |
December | 0.711394E+09 | 0.266814E+10 | 0.00 | 85235712.48 | 0.00 | 0.00 | 0.166623E+11 | 0.00 | 8.39 |
Annual Sum or Average | 0.446568E+10 | 0.265646E+12 | 0.00 | 0.503620E+09 | 212726.55 | 0.00 | 0.837178E+11 | 0.00 | 9.08 |
Minimum of Months | 0.00 | 0.299933E+09 | 0.00 | 7403.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 |
Maximum of Months | 0.229598E+10 | 0.500489E+11 | 0.00 | 97441201.51 | 202340.23 | 0.00 | 0.239275E+11 | 0.00 | 10.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.527889E+11 | 0.493367E+10 | 0.933504E+11 | 0.822358E+10 | 0.904231E+11 |
February | 0.617371E+11 | 0.347685E+10 | 0.621318E+11 | 0.620802E+10 | 0.100986E+12 |
March | 0.848519E+11 | 0.215215E+10 | 0.434040E+11 | 0.566931E+10 | 0.137504E+12 |
April | 0.975853E+11 | -0.179231E+10 | -0.155973E+11 | 0.463886E+10 | 0.186467E+12 |
May | 0.109484E+12 | -0.675540E+10 | -0.929100E+11 | 0.192188E+10 | 0.270242E+12 |
June | 0.109688E+12 | -0.117247E+11 | -0.152026E+12 | 28119733.85 | 0.326747E+12 |
July | 0.108449E+12 | -0.155705E+11 | -0.192366E+12 | -0.306107E+10 | 0.386006E+12 |
August | 0.106059E+12 | -0.174954E+11 | -0.202194E+12 | -0.437009E+10 | 0.401785E+12 |
September | 0.868065E+11 | -0.143359E+11 | -0.168269E+12 | -431676452.3 | 0.346622E+12 |
October | 0.674658E+11 | -0.870742E+10 | -0.104165E+12 | 0.827727E+09 | 0.278491E+12 |
November | 0.500569E+11 | -0.337134E+10 | -0.202048E+11 | 0.392024E+10 | 0.190454E+12 |
December | 0.463307E+11 | 0.191884E+10 | 0.554112E+11 | 0.682003E+10 | 0.123663E+12 |
Annual Sum or Average | 0.981304E+12 | -0.672714E+11 | -0.693435E+12 | 0.303949E+11 | 0.283939E+13 |
Minimum of Months | 0.463307E+11 | -0.174954E+11 | -0.202194E+12 | -0.437009E+10 | 0.904231E+11 |
Maximum of Months | 0.109688E+12 | 0.493367E+10 | 0.933504E+11 | 0.822358E+10 | 0.401785E+12 |