Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:28:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2251.64 | 4405.02 | 4405.02 |
Net Site Energy | 2251.64 | 4405.02 | 4405.02 |
Total Source Energy | 5372.52 | 10510.58 | 10510.58 |
Net Source Energy | 5372.52 | 10510.58 | 10510.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 245.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 361.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.44 | 313.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 64.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1407.46 | 844.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 245.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 361.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.44 | 313.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 245.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 361.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.44 | 313.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 64.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1337.06 | 732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1026.67 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2753.50 | 1651.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1337.06 | 732.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1026.67 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2753.50 | 1651.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1407.461 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1407.461 | 100.00 |
Total On-Site and Utility Electric Sources | 1407.461 | 100.00 |
Total Electricity End Uses | 1407.461 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4080.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 14.4672 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.5854 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 14.4672 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.5854 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 13.6812 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JUN-17:10 | 03-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 14-FEB-07:40 |
Heating | 0.00 | 68019.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 38263.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13460.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4189.66 | 22443.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2025.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84928.28 | 104039.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 68019.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 38263.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13460.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4189.66 | 22443.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 509.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 970.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 778.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1145.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.93 | 340.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 202.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4457.43 | 915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 128.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1523.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2241.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.43 | 665.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 396.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8720.34 | 1790.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 128.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1523.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2241.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.43 | 665.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 396.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8720.34 | 1790.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.87 |
KITCHEN DIRECT AIR | 1.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 1.00 | 1.00 | 4.87 |
PSZ-AC_2:2 | 1.93 | 1.93 | 1.93 | 1.93 | 1.93 | 1.93 | 1.00 | 1.000000 | 1.93 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.87 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.93 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.87 | 9149.74 |
PSZ-AC_2:2_ADDAQ FAN | 1.93 | 2107.81 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.87 | 4.87 | 4.87 | 4.87 | 102393.85 | 133775.90 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.93 | 1.93 | 1.93 | 1.93 | 47822.42 | 89024.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.87 | 2.44 | 4.87 | 102393.85 | 51147.78 | 102393.85 | 0.757660 | 0.757660 |
PSZ-AC_2:2 COOLING COIL | 1.93 | 0.962904 | 1.93 | 47822.42 | 23911.21 | 47822.42 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 133775.90 |
PSZ-AC_2:2 HEATING COIL | 89024.48 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 14.467 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 79.395 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.585 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.665 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 5378.143 | 14.467 | 19.198 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5378.143 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1615.060 | 11.585 | 214.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1615.060 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.173 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6183 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.28463157E-12 | 0.13995018E-14 | -0.88704156E-13 | 0.19110497E-15 |
34 | 6 | 0.23910712E-07 | 0.31113548E-09 | 0.55171738E-08 | -0.10983793E-12 |
35 | 5 | -0.16561564E-03 | 0.27534435E-05 | -0.85461923E-04 | 0.54660651E-08 |
36 | 4 | 0.26301405 | 0.13802408E-02 | 0.89229334E-01 | -0.29509762E-04 |
37 | 3 | -6.6882438 | 0.43887669E-01 | -2.1674554 | 0.26179268E-01 |
38 | 2 | 38.963313 | 0.15961158 | 14.559020 | -0.31209900 |
39 | 1 | -79.082427 | 0.73450034E-01 | -28.507859 | 1.0474370 |
40 | 0 | 46.824349 | 0.15062771E-02 | 16.306989 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 48302.34096 | 57962.80915 | 4.06114 | 4.87337 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 8090.35073 | 9708.42087 | 0.39984 | 1.33138 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -5.20000 | 2.80840E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22495.00209 | 26994.00251 | 1.60484 | 1.92581 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 76917.22 | 4.87337 | 4.87337 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63151.41 | 1.33138 | 1.33138 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 44706.28 | 1.92581 | 1.92581 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 71157.79 | 1.50017 | 1.50017 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.87337 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.92581 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.87337 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.87337 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.87337 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.87337 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.87337 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.87337 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.92581 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.92581 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.92581 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92581 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.92581 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.92581 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.87337 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.92581 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.87337 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.87337 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9149.74095 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.87337 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.87337 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.87337 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.87337 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.87337 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.43668 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.87337 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 102393.85000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 51147.78460 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 102393.85000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75766 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75766 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 102393.85000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 133775.89533 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 133775.89533 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.92581 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.92581 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2107.80816 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.92581 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.92581 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.92581 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.92581 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.92581 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96290 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.92581 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47822.42000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 23911.20765 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 47822.42000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47822.42000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 89024.47889 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 89024.47889 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 98883.1 | 9.74 | 9.62 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 46453.6 | 10.12 | 9.99 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.173 | 0.998 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.5102133361E-002 | 0.1770370123 | Pass | Pass | 4.0435122982E-002 | 8.2497511542E-002 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2339240010 | 0.6220536727 | Pass | Pass | 5.7635745524E-002 | 0.2571907593 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4786487135 | 0.4719097618 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1253.03 | 92.75 | 1105.83 | 102.67 | 1334.79 | 3889.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.998 | 1.173 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 14.4672 | 371.75 | 5378.14 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 97.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.5854 | 139.41 | 1615.06 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.38 |
Interior Lighting Total | 13.6812 | 511.15 | 6993.20 | 127.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.77 | 83.77 | 71.99 | |
Exterior Lighting Total | 4578.48 | 71.99 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 102393.85 | 77579.72 | 24814.13 | 0.76 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47822.42 | 33527.34 | 14295.08 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 98883.1 | 9.74 | 9.62 | ||||
PSZ-AC_2:2 COOLING COIL | 46453.6 | 10.12 | 9.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 133775.90 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 89024.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.87 | 9149.74 | 1877.50 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.93 | 2107.81 | 1094.51 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 48302.34 | 57962.81 | 155.92 | 4.061 | 4.873 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00826 | 37.97 | 0.00687 | 1.331 | 0.00 |
KITCHEN | 22495.00 | 26994.00 | 193.64 | 1.605 | 1.926 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00870 | 36.93 | 0.00687 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8090.35 | 9708.42 | 26.12 | 0.400 | 1.331 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00772 | -5.20 | 0.00281 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 20.73 | 0.00247 | -5.20 | 0.00281 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.87 | 4.87 | 1.33 | 1.33 | 4.8734 | 4.8734 | 4.8734 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.93 | 1.93 | 1.50 | 1.50 | 1.9258 | 1.9258 | 1.9258 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 102393.850 | 77579.724 | 4.873370 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 102393.85 | 92719.47 | 4.873370 | 27.84 | 15.72 | 0.00788197 | 11.04 | 8.59 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.3194 | 23.99 | 0.00826196 | 38.6083 | 48284.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 133775.895 | 133775.895 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 133775.90 | 133775.90 | 4.873370 | 13.84 | 9.14 | 0.00638072 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 27.3194 | 21.00 | 0.00772350 | 43.3231 | 8081.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 47822.420 | 33527.342 | 1.925810 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 47822.42 | 46933.49 | 1.925810 | 35.78 | 17.73 | 0.00721879 | 11.77 | 8.90 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 77.8982 | 25.98 | 0.00869335 | 36.0447 | 21643.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 89024.479 | 89024.479 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 89024.48 | 89024.48 | 1.925809 | -4.05 | -4.64 | 0.00273705 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 77.8982 | 21.13 | 0.00248560 | 13.9477 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 102393.850 | 77579.724 | 4.873370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4922 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.873370 | 5.08941442 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 102393.85 | 92719.47 | 1.0000 | 5.08941493 | 4.873370 | 27.84 | 15.72 | 0.00788197 | 48099.9 | 11.04 | 8.59 | 0.00700000 | 28740.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102393.85 | 38.10 | 0.00687148 | 18.17 | 1.33137743 | 27.3194 | 23.99 | 0.00826196 | 23.99 | 0.00826196 | 38.6083 | 48284.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 133775.895 | 133775.895 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.873370 | 5.08941442 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 133775.90 | 133775.90 | 1.0000 | 5.08941442 | 4.873370 | 13.84 | 9.14 | 0.00638072 | 30030.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 133775.90 | -5.20 | 0.00280840 | -5.20 | 1.33137743 | 27.3194 | 21.00 | 0.00772350 | 21.00 | 0.00772350 | 43.3231 | 8081.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47822.420 | 33527.342 | 1.925810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2594 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.925809 | 2.01118310 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 47822.42 | 46933.49 | 1.0000 | 2.01118449 | 1.925810 | 35.78 | 17.73 | 0.00721879 | 54491.3 | 11.77 | 8.90 | 0.00700000 | 29487.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47822.42 | 38.10 | 0.00687148 | 18.17 | 1.50017041 | 77.8982 | 25.95 | 0.00869335 | 25.98 | 0.00869335 | 36.0447 | 21643.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89024.479 | 89024.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.925809 | 2.01118310 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 89024.48 | 89024.48 | 1.0000 | 2.01118310 | 1.925809 | -4.05 | -4.64 | 0.00273705 | 2754.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89024.48 | -5.20 | 0.00280840 | -5.20 | 1.50017041 | 77.8982 | 0.00 | 0.00248560 | 21.13 | 0.00248560 | 13.9477 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.87 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.50 | 1.93 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3818.83 | 2419.67 | 522.83 |
KITCHEN | 5302.00 | 5653.50 | 4068.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5307.83 | 5859.33 | 4080.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 24.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 211.83 | 0.00 | 0.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 235.67 | 0.00 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 6.092 | 0.929 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.966 | 0.056 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.135 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.455 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 49954905.79 | 0.00 | 49954905.79 | 7606126.83 | 57561032.62 | 41986318.57 | 1427.29 | 4589.34 | 2743.37 | 216.06 |
KITCHEN | 43572812.61 | 0.00 | 43572812.61 | 265172.33 | 43837984.94 | 47309374.20 | 1408.81 | 5115.97 | 2235.22 | 694.44 |
Total Facility | 93527718.40 | 0.00 | 93527718.40 | 7871299.16 | 0.10E+09 | 89295692.77 | 1451.42 | 5663.75 | 3332.04 | 740.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.8862 | 0.0000 | 1.8862 | 0.2879 | 2.1742 | 1.3314 | 0.00 | 4516.70 | 2670.30 |
KITCHEN | 1.6172 | 0.0000 | 1.6172 | 0.0064 | 1.6236 | 1.5002 | 0.00 | 5031.94 | 2155.06 |
Total Facility | 3.5034 | 0.0000 | 3.5034 | 0.2944 | 3.7978 | 2.8315 | 0.00 | 5573.20 | 3211.55 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 54482254.76 | 0.00 | 54482254.76 | 41986318.57 | 1427.05 | 0.00 | 7332.95 | 216.04 |
PSZ-AC_2:2 | 47521762.85 | 0.00 | 47521762.85 | 47309374.20 | 1399.51 | 2.08 | 7358.41 | 694.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.0572 | 0.0000 | 2.0572 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.7637 | 0.0000 | 1.7637 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1531.47 | 1292.04 | 4579.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4581.07 | 2443.07 | 857.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 3.7206 | 2.3490 | 1.4523 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.6362 | 2.0590 | 1.6395 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
Electricity:Building | 604.81 | 4434.71 | 01-JAN-01:10 | 33358.73 | 02-JAN-11:10 |
Electricity:Zone:DINING | 223.13 | 1289.45 | 01-JAN-01:10 | 11839.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 587.95 | 4025.67 | 01-JAN-01:10 | 30993.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.68 | 3145.26 | 01-JAN-01:10 | 21518.76 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 64.07 | 1038.02 | 19-DEC-23:30 | 3441.39 | 29-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 123.11 | 1103.73 | 12-FEB-01:10 | 6472.12 | 16-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.67 | 0.00 | 01-JAN-11:10 | 1506.24 | 13-OCT-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 30.55 | 759.40 | 21-APR-03:50 | 1076.23 | 14-APR-03:20 |
ElectricityPurchased:Facility | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
ElectricityPurchased:Plant | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
Cogeneration:ElectricityPurchased | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
ElectricityNet:Plant | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
Cogeneration:ElectricityNet | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
General:Cogeneration:ElectricityNet | 1407.46 | 10116.92 | 12-FEB-01:10 | 84928.28 | 02-JUN-17:10 |
Electricity:HVAC | 607.55 | 0.00 | 01-JAN-01:10 | 51724.26 | 02-JUN-17:10 |
Fans:Electricity | 361.72 | 0.00 | 01-JAN-01:10 | 13460.95 | 01-JAN-09:40 |
General:Fans:Electricity | 361.72 | 0.00 | 01-JAN-01:10 | 13460.95 | 01-JAN-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 245.83 | 0.00 | 01-JAN-00:10 | 38263.30 | 02-JUN-17:10 |
General:Cooling:Electricity | 245.83 | 0.00 | 01-JAN-00:10 | 38263.30 | 02-JUN-17:10 |
ExteriorLights:Electricity | 71.99 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.99 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.44 | 0.00 | 01-JAN-01:10 | 4742.17 | 17-NOV-07:50 |
Water Heater:WaterSystems:Electricity | 75.44 | 0.00 | 01-JAN-01:10 | 4742.17 | 17-NOV-07:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-JAN-09:00 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-JAN-09:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 844.18 | 2803.57 | 01-JAN-01:10 | 104039.73 | 03-FEB-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 60.63 | 0.00 | 01-JAN-01:10 | 68397.15 | 03-FEB-07:00 |
Heating:NaturalGas | 60.63 | 0.00 | 01-JAN-01:10 | 68397.15 | 03-FEB-07:00 |
General:Heating:NaturalGas | 60.63 | 0.00 | 01-JAN-01:10 | 68397.15 | 03-FEB-07:00 |
NaturalGas:Plant | 313.76 | 993.32 | 01-JAN-00:10 | 26105.40 | 01-FEB-07:20 |
WaterSystems:NaturalGas | 313.76 | 993.32 | 01-JAN-00:10 | 26105.40 | 01-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 313.76 | 993.32 | 01-JAN-00:10 | 26105.40 | 01-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1954.29 | 3206.79 | 06-JAN-01:10 | 189698.48 | 21-JUL-18:00 |
EnergyTransfer:Building | 854.69 | 1603.40 | 06-JAN-01:10 | 59777.30 | 16-MAY-03:50 |
EnergyTransfer:Zone:KITCHEN | 474.31 | 1603.40 | 06-JAN-01:10 | 29181.99 | 21-APR-03:40 |
Refrigeration:EnergyTransfer | 151.73 | 2714.17 | 02-FEB-23:10 | 7834.84 | 14-APR-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.86 | 1357.09 | 02-FEB-23:10 | 3917.42 | 14-APR-03:20 |
General:Refrigeration:EnergyTransfer | 75.86 | 1357.09 | 02-FEB-23:10 | 3917.42 | 14-APR-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 75.86 | 1357.09 | 02-FEB-23:10 | 3917.42 | 14-APR-03:20 |
EnergyTransfer:Plant | 292.70 | 1603.40 | 06-JAN-01:10 | 18050.25 | 06-FEB-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.44 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 60.43 | 1288.21 | 21-APR-03:50 | 2238.70 | 14-APR-03:20 |
EnergyTransfer:Zone:DINING | 380.38 | 0.00 | 01-JAN-01:10 | 46344.00 | 16-MAY-03:50 |
Heating:EnergyTransfer | 2.09 | 0.00 | 01-JAN-00:10 | 18145.32 | 11-MAY-03:50 |
Heating:EnergyTransfer:Zone:DINING | 2.09 | 0.00 | 01-JAN-00:10 | 18145.32 | 11-MAY-03:50 |
General:Heating:EnergyTransfer | 2.09 | 0.00 | 01-JAN-00:10 | 18145.32 | 11-MAY-03:50 |
General:Heating:EnergyTransfer:Zone:DINING | 2.09 | 0.00 | 01-JAN-00:10 | 18145.32 | 11-MAY-03:50 |
Cooling:EnergyTransfer | 776.74 | 0.00 | 01-JAN-01:10 | 55517.26 | 17-JUN-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 378.29 | 0.00 | 01-JAN-01:10 | 36300.01 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer | 776.74 | 0.00 | 01-JAN-01:10 | 55517.26 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 378.29 | 0.00 | 01-JAN-01:10 | 36300.01 | 17-JUN-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 47.71 | 27-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 47.71 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 398.45 | 0.00 | 01-JAN-01:10 | 25466.21 | 21-APR-03:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 398.45 | 0.00 | 01-JAN-01:10 | 25466.21 | 21-APR-03:40 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
EnergyTransfer:HVAC | 806.90 | 0.00 | 01-JAN-01:10 | 124213.86 | 21-JUL-18:00 |
HeatingCoils:EnergyTransfer | 48.50 | 0.00 | 01-JAN-01:10 | 54717.72 | 03-FEB-07:00 |
CoolingCoils:EnergyTransfer | 758.40 | 0.00 | 01-JAN-00:10 | 124213.86 | 21-JUL-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15489.34 | 31-JAN-07:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.091 | -378.281 | 0.000 | 0.000 | 211.880 | 97.852 | 93.957 | 43.547 | 0.000 | 14.970 | 0.000 | 0.000 | -24.426 | 0.000 | -48.532 | -13.058 |
KITCHEN | 0.000 | 0.000 | 0.000 | -398.442 | 0.000 | 0.000 | 5.349 | 29.385 | 297.857 | 0.000 | 0.000 | 0.191 | 68.155 | 0.000 | 0.000 | 0.000 | -2.496 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.053 | 38.229 | 0.000 | 0.000 | 0.000 | -48.282 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.091 | -776.723 | 0.000 | 0.000 | 217.229 | 127.237 | 391.814 | 43.547 | 0.000 | 25.214 | 106.384 | 0.000 | -24.426 | 0.000 | -99.310 | -13.059 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-MAY-03:01 | 0.00 | 0.00 | 0.00 | -121210.37 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 121800.45 | 0.00 | -1989.78 | 0.00 | -312.14 | 0.00 |
KITCHEN | 21-FEB-04:41 | 0.00 | 0.00 | 0.00 | -80749.36 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 77081.43 | 0.00 | -0.00 | 0.00 | -395.81 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-03:01 | 0.00 | 0.00 | 0.00 | -193723.35 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 811.40 | 189716.84 | 0.00 | -1989.78 | 0.00 | -590.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 27-APR-03:04 | 0.00 | 0.00 | 62557.60 | 0.00 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1548.26 | 0.00 | 0.00 | -62721.19 |
KITCHEN | 27-DEC-05:03 | 0.00 | 0.00 | 476.32 | 0.00 | 0.00 | 0.00 | 22.48 | 323.01 | 7256.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.93 | -8061.80 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-APR-03:04 | 0.00 | 0.00 | 62557.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1439.71 | 0.00 | 0.00 | -1548.26 | 0.00 | 0.00 | -68224.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8734 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8734 | 0.2732 | 1.0000 | Not calculated | 1.3314 | 0.2732 | ||
PSZ-AC_2:2 | 1.9258 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9258 | 0.0948 | 1.0000 | Not calculated | 0.1826 | 0.0948 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8734 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8734 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2732 | ||
PSZ-AC_2:2 | 1.9258 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9258 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.0948 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8734 | 4.8734 | 4.8734 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9258 | 1.9258 | 1.9258 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8734 | 4.8734 | 4.8734 | 4.8734 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9258 | 1.9258 | 1.9258 | 1.9258 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8734 | 4.8734 | 4.8734 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9258 | 1.9258 | 1.9258 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8734 | 4.8734 | 4.8734 | 4.8734 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9258 | 1.9258 | 1.9258 | 1.9258 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 0.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 60.63 | 68397.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 245.83 | 38263.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 127.24 | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.99 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 361.72 | 13460.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.44 | 4742.17 | 313.76 | 26105.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.67 | 1506.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.55 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 524.79 | 1407.46 |
Natural Gas | 469.79 | 844.18 |
Additional | 0.00 | 0.00 |
Total | 994.57 | 2251.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 248.92 |
Space Heating | 0.00 |
Space Cooling | 480.94 |
Fans (All) | 707.65 |
Service Water Heating | 147.59 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2753.50 |
Subtotal | 2753.50 |
Natural Gas [MJ/m2] | |
Space Heating | 118.62 |
Service Water Heating | 613.83 |
Miscellaneous (All) | 1651.52 |
Subtotal | 1651.52 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.65 |
Space Heating | 2.69 |
Space Cooling | 10.92 |
Fans (All) | 16.06 |
Service Water Heating | 17.29 |
Receptacle Equipment | 41.33 |
Miscellaneous | 6.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8425.50 | 334.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7910.50 | 834.50 | 15.00 | 0.00 | 0.00 |
ATTIC | 5876.00 | 872.17 | 687.83 | 974.00 | 350.00 |
Min | 5876.00 | 334.50 | 0.00 | 0.00 | 0.00 |
Max | 8425.50 | 872.17 | 687.83 | 974.00 | 350.00 |
Average | 7404.00 | 680.39 | 234.28 | 324.67 | 116.67 |
Sum | 22212.00 | 2041.17 | 702.83 | 974.00 | 350.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822885.00 | 1337.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822885.00 | 1337.00 | 0.00 | 0.00 | 0.00 |
Average | 280706.00 | 445.67 | 0.00 | 0.00 | 0.00 |
Sum | 842118.00 | 1337.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8302.17 | 457.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6771.17 | 1988.50 | 0.33 | 0.00 | 0.00 |
ATTIC | 6098.67 | 1191.67 | 353.33 | 318.00 | 798.33 |
Min | 6098.67 | 457.83 | 0.00 | 0.00 | 0.00 |
Max | 8302.17 | 1988.50 | 353.33 | 318.00 | 798.33 |
Average | 7057.33 | 1212.67 | 117.89 | 106.00 | 266.11 |
Sum | 21172.00 | 3638.00 | 353.67 | 318.00 | 798.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 814328.67 | 9893.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15496.50 | 3736.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 814328.67 | 9893.33 | 0.00 | 0.00 | 0.00 |
Average | 276608.39 | 4543.28 | 0.00 | 0.00 | 0.00 |
Sum | 829825.17 | 13629.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195103E+11 | 21825.66 | 05-JAN-05:01 | -2.1 | -5.7 | 0.139097E+11 | 13956.42 | 07-JAN-19:00 | 10.60 | 4.42 |
February | 0.189167E+11 | 21013.55 | 07-FEB-13:00 | 20.60 | 9.66 | 0.129971E+11 | 14050.50 | 18-FEB-19:10 | 14.32 | 6.23 |
March | 0.232673E+11 | 109759.78 | 16-MAR-03:01 | 15.68 | 5.60 | 0.148670E+11 | 14051.38 | 25-MAR-18:10 | 18.62 | 7.41 |
April | 0.304699E+11 | 121038.80 | 22-APR-03:01 | 11.83 | 5.33 | 0.147696E+11 | 14051.39 | 08-APR-18:00 | 11.83 | 5.33 |
May | 0.379485E+11 | 121226.85 | 06-MAY-03:01 | 12.38 | 3.15 | 0.154228E+11 | 14052.56 | 13-MAY-18:00 | 30.00 | 14.69 |
June | 0.430225E+11 | 107295.54 | 12-JUN-03:01 | 17.38 | 6.37 | 0.150216E+11 | 14052.93 | 17-JUN-18:00 | 32.20 | 17.71 |
July | 0.443118E+11 | 79498.46 | 03-JUL-03:01 | 28.90 | 17.76 | 0.153387E+11 | 14051.87 | 29-JUL-18:19 | 33.70 | 18.90 |
August | 0.438834E+11 | 96100.09 | 23-AUG-03:01 | 21.83 | 12.04 | 0.155326E+11 | 14053.13 | 19-AUG-18:49 | 21.83 | 12.04 |
September | 0.401325E+11 | 112280.41 | 30-SEP-03:01 | 11.52 | 7.08 | 0.149000E+11 | 14051.68 | 30-SEP-18:19 | 23.90 | 11.41 |
October | 0.334627E+11 | 117083.85 | 31-OCT-03:01 | 13.43 | 6.06 | 0.152588E+11 | 14052.63 | 21-OCT-18:00 | 13.43 | 6.06 |
November | 0.240264E+11 | 106895.13 | 08-NOV-04:01 | 15.92 | 7.68 | 0.140601E+11 | 14050.37 | 04-NOV-18:10 | 15.92 | 7.68 |
December | 0.193333E+11 | 20213.54 | 17-DEC-05:01 | -0.4 | -3.6 | 0.136054E+11 | 14050.32 | 09-DEC-19:10 | -0.4 | -3.6 |
Annual Sum or Average | 0.378285E+12 | 0.175684E+12 | ||||||||
Minimum of Months | 0.189167E+11 | 20213.54 | -2.1 | -5.7 | 0.129971E+11 | 13956.42 | -0.4 | -3.6 | ||
Maximum of Months | 0.443118E+11 | 121226.85 | 28.90 | 17.76 | 0.155326E+11 | 14053.13 | 33.70 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321144E+11 | 38959.36 | 28-JAN-05:01 | -2.9 | -6.3 | 0.104620E+11 | 6931.03 | 03-JAN-11:00 | -2.9 | -6.3 |
February | 0.283318E+11 | 80755.13 | 21-FEB-04:41 | 4.40 | -0.5 | 0.948351E+10 | 6934.92 | 07-FEB-11:50 | 4.40 | -0.5 |
March | 0.312015E+11 | 77594.01 | 26-MAR-03:01 | 5.50 | 0.44 | 0.105380E+11 | 6934.91 | 06-MAR-11:00 | 5.50 | 0.44 |
April | 0.312571E+11 | 76393.54 | 16-APR-03:01 | 9.50 | 0.80 | 0.102437E+11 | 6934.94 | 26-APR-10:39 | 21.33 | 12.02 |
May | 0.340059E+11 | 72546.59 | 06-MAY-03:01 | 12.38 | 3.15 | 0.106029E+11 | 6934.95 | 19-MAY-10:00 | 31.70 | 18.11 |
June | 0.347719E+11 | 61469.98 | 12-JUN-03:01 | 17.38 | 6.37 | 0.102664E+11 | 6934.96 | 09-JUN-10:50 | 17.38 | 6.37 |
July | 0.366326E+11 | 45417.58 | 11-JUL-03:21 | 23.60 | 15.66 | 0.106028E+11 | 6934.96 | 06-JUL-10:00 | 23.60 | 15.66 |
August | 0.365463E+11 | 50198.37 | 23-AUG-01:22 | 23.30 | 12.45 | 0.106090E+11 | 6934.96 | 07-AUG-10:30 | 23.30 | 12.45 |
September | 0.348077E+11 | 61370.52 | 30-SEP-03:01 | 11.52 | 7.08 | 0.102606E+11 | 6934.95 | 19-SEP-10:50 | 11.52 | 7.08 |
October | 0.342120E+11 | 69386.72 | 24-OCT-03:41 | 9.40 | 5.16 | 0.105849E+11 | 6934.94 | 20-OCT-10:00 | 9.40 | 5.16 |
November | 0.320529E+11 | 72341.13 | 25-NOV-04:01 | 4.32 | 2.53 | 0.101766E+11 | 6934.95 | 09-NOV-11:50 | 4.32 | 2.53 |
December | 0.325175E+11 | 67853.43 | 16-DEC-04:01 | 10.50 | 3.35 | 0.104498E+11 | 6917.02 | 11-DEC-11:00 | 10.50 | 3.35 |
Annual Sum or Average | 0.398452E+12 | 0.124280E+12 | ||||||||
Minimum of Months | 0.283318E+11 | 38959.36 | -2.9 | -6.3 | 0.948351E+10 | 6917.02 | -2.9 | -6.3 | ||
Maximum of Months | 0.366326E+11 | 80755.13 | 23.60 | 15.66 | 0.106090E+11 | 6934.96 | 31.70 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 | 3.92 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 | 2.41 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 | 8.41 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 | 11.56 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 | 17.07 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 | 17.18 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 | 8.67 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 | 5.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 | 5.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.00 | 0.00 | 6.42 | 1.84 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.00 | 0.00 | 27.63 | 18.12 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10252201.85 | 11763.51 | 28-JAN-05:01 | -2.9 |
February | 5680350.82 | 8972.00 | 03-FEB-05:01 | -3.8 |
March | 2939480.28 | 29618.13 | 16-MAR-03:02 | 15.68 |
April | 0.105908E+09 | 62567.48 | 27-APR-03:04 | 15.73 |
May | 0.332329E+09 | 59265.47 | 03-MAY-03:04 | 17.15 |
June | 0.555641E+09 | 32977.71 | 01-JUN-03:43 | 21.27 |
July | 0.483435E+09 | 18722.00 | 02-JUL-23:01 | 33.48 |
August | 0.404807E+09 | 27532.44 | 11-AUG-03:47 | 24.22 |
September | 0.116156E+09 | 14450.00 | 05-SEP-03:47 | 16.78 |
October | 45977200.58 | 14633.39 | 30-OCT-03:02 | 11.10 |
November | 4856864.58 | 25477.04 | 08-NOV-04:02 | 15.92 |
December | 22598593.06 | 14340.17 | 27-DEC-05:01 | -3.8 |
Annual Sum or Average | 0.209058E+10 | |||
Minimum of Months | 2939480.28 | 8972.00 | -3.8 | |
Maximum of Months | 0.555641E+09 | 62567.48 | 33.48 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 22857.50 | 380.96 | 16-JUL-03:02 | 25.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 28625.53 | 477.09 | 27-DEC-05:03 | -3.8 |
Annual Sum or Average | 51483.03 | |||
Minimum of Months | 0.00 | 0.00 | -3.8 | |
Maximum of Months | 28625.53 | 477.09 | 27.32 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826825E+10 | 4840.33 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.748896E+10 | 4840.33 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.839991E+10 | 4840.33 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.803398E+10 | 4840.33 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.833408E+10 | 4840.33 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.811917E+10 | 4840.33 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.824986E+10 | 4840.33 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.839991E+10 | 4840.33 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.803591E+10 | 4840.33 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.826728E+10 | 4840.33 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.800397E+10 | 4840.33 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.825082E+10 | 4840.33 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.978521E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.748896E+10 | 4840.33 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.839991E+10 | 4840.33 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.248296E+10 | 1453.55 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.224894E+10 | 1453.55 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.252250E+10 | 1453.55 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.241261E+10 | 1453.55 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.250273E+10 | 1453.55 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.243819E+10 | 1453.55 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.247744E+10 | 1453.55 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.252250E+10 | 1453.55 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.241319E+10 | 1453.55 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.248267E+10 | 1453.55 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.240360E+10 | 1453.55 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.247773E+10 | 1453.55 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.293850E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.224894E+10 | 1453.55 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.252250E+10 | 1453.55 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.826825E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923803E+10 |
February | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717045E+10 |
March | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4826963.83 | 0.640924E+10 |
April | 0.292871E+11 | 0.803398E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707032E+09 | 0.265801E+10 |
May | 0.303219E+11 | 0.833408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197813E+10 | 0.913484E+09 |
June | 0.295292E+11 | 0.811917E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390699E+10 | 0.237586E+09 |
July | 0.300798E+11 | 0.824986E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349952E+10 | 0.172227E+09 |
August | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287625E+10 | 0.426901E+09 |
September | 0.292871E+11 | 0.803591E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164844E+10 | 0.866270E+09 |
October | 0.300980E+11 | 0.826728E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348806E+09 | 0.328452E+10 |
November | 0.290996E+11 | 0.800397E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717353E+10 |
December | 0.300798E+11 | 0.825082E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998164E+10 |
Annual Sum or Average | 0.356244E+12 | 0.978521E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149700E+11 | 0.485319E+11 |
Minimum of Months | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172227E+09 |
Maximum of Months | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390699E+10 | 0.998164E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.248296E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354313E+09 |
February | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340382E+09 |
March | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351911E+09 |
April | 0.786997E+09 | 0.241261E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 9186751.20 | 0.230646E+09 |
May | 0.814802E+09 | 0.250273E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 30069958.84 | 0.153363E+09 |
June | 0.793501E+09 | 0.243819E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 60958792.91 | 68789133.21 |
July | 0.808298E+09 | 0.247744E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 44593172.49 | 54615440.77 |
August | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 33624536.41 | 69514143.06 |
September | 0.786997E+09 | 0.241319E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 9954412.63 | 67223640.31 |
October | 0.808786E+09 | 0.248267E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2908847.30 | 0.194451E+09 |
November | 0.781956E+09 | 0.240360E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294009E+09 |
December | 0.808298E+09 | 0.247773E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316704E+09 |
Annual Sum or Average | 0.957291E+10 | 0.293850E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.191296E+09 | 0.249592E+10 |
Minimum of Months | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54615440.77 |
Maximum of Months | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 60958792.91 | 0.354313E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880285E+09 | 0.274091E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824148E+09 | 0.285362E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851051E+09 | 0.381217E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841830E+09 | 0.451027E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822245E+09 | 0.478127E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718934E+09 | 0.531645E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560292E+09 | 0.531880E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664049E+09 | 0.502440E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888130E+09 | 0.470643E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849117E+09 | 0.359933E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944807E+09 | 0.292617E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120814E+10 | 0.269197E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100530E+11 | 0.482818E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560292E+09 | 0.269197E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120814E+10 | 0.531880E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 4840.33 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10490.48 | 26-JAN-19:55 |
February | 30255.31 | 04-FEB-19:10 | 4840.33 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 10726.17 | 08-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 4840.33 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.89 | 22-MAR-13:00 | 11494.37 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 4840.33 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.24 | 21-APR-12:55 | 8383.21 | 10-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 4840.33 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5410.17 | 19-MAY-17:03 | 4612.78 | 06-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 4840.33 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7489.97 | 02-JUN-17:03 | 2139.27 | 13-JUN-06:05 |
July | 30255.31 | 01-JUL-18:10 | 4840.33 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7294.57 | 03-JUL-17:03 | 1847.67 | 05-JUL-06:05 |
August | 30255.31 | 05-AUG-18:10 | 4840.33 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6349.66 | 07-AUG-17:03 | 3140.73 | 16-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 4840.33 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4686.50 | 19-SEP-17:02 | 5120.27 | 30-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 4840.33 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.25 | 04-OCT-17:02 | 7057.36 | 23-OCT-19:00 |
November | 30255.31 | 04-NOV-18:10 | 4840.33 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9930.21 | 25-NOV-19:30 |
December | 30255.31 | 02-DEC-19:10 | 4840.33 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 11543.52 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.67 | |||||
Maximum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 7489.97 | 11543.52 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1453.55 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1343.24 | 26-JAN-01:10 |
February | 813.01 | 04-FEB-19:10 | 1453.55 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1797.75 | 09-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 1453.55 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1424.73 | 20-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 1453.55 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 136.99 | 21-APR-14:53 | 1708.15 | 11-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 1453.55 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 137.18 | 19-MAY-13:53 | 1260.31 | 04-MAY-01:50 |
June | 813.01 | 03-JUN-18:10 | 1453.55 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 213.40 | 10-JUN-00:47 | 891.38 | 28-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 1453.55 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 416.62 | 02-JUL-23:09 | 451.36 | 30-JUL-01:20 |
August | 813.01 | 05-AUG-18:10 | 1453.55 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 170.87 | 24-AUG-00:47 | 675.57 | 14-AUG-00:40 |
September | 813.01 | 02-SEP-18:10 | 1453.55 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 43.32 | 10-SEP-15:00 | 315.29 | 25-SEP-02:53 |
October | 813.01 | 07-OCT-18:10 | 1453.55 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 169.75 | 02-OCT-00:47 | 896.02 | 24-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 1453.55 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1143.17 | 10-NOV-04:20 |
December | 813.01 | 02-DEC-19:10 | 1453.55 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1453.02 | 18-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 315.29 | ||||||
Maximum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 416.62 | 1797.75 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.00 | 02-JAN-07:55 | 5960.77 | 28-JAN-14:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2029.39 | 10-FEB-24:00 | 6536.78 | 09-FEB-12:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1785.58 | 06-MAR-02:70 | 7871.09 | 20-MAR-12:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1860.03 | 27-APR-05:40 | 8302.72 | 30-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.03 | 21-MAY-02:00 | 7833.12 | 12-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2073.79 | 14-JUN-03:51 | 8139.51 | 29-JUN-12:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.54 | 01-JUL-05:30 | 7783.13 | 06-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.03 | 26-AUG-06:00 | 7870.64 | 03-AUG-12:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.72 | 12-SEP-04:00 | 7744.97 | 05-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.38 | 16-OCT-02:00 | 6625.16 | 08-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2016.96 | 23-NOV-01:00 | 6231.30 | 07-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.42 | 20-DEC-03:52 | 6239.13 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.03 | 5960.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.42 | 8302.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21825.66 | 05-JAN-05:01 | 16808.50 | 10756.29 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.96 |
February | 21013.55 | 07-FEB-13:00 | 26893.61 | 4840.33 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1868.10 |
March | 109759.78 | 16-MAR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.82 |
April | 121038.80 | 22-APR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.02 |
May | 121226.85 | 06-MAY-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.14 |
June | 107295.54 | 12-JUN-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.61 |
July | 79498.46 | 03-JUL-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 | 0.00 |
August | 96100.09 | 23-AUG-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.50 |
September | 112280.41 | 30-SEP-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.95 |
October | 117083.85 | 31-OCT-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.18 |
November | 106895.13 | 08-NOV-04:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 |
December | 20213.54 | 17-DEC-05:01 | 0.00 | 8067.21 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20213.54 | 0.00 | 4840.33 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 121226.85 | 26893.61 | 10756.29 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 | 1868.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38959.36 | 28-JAN-05:01 | 0.00 | 2422.59 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.57 |
February | 80755.13 | 21-FEB-04:41 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 395.81 |
March | 77594.01 | 26-MAR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 205.79 |
April | 76393.54 | 16-APR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 237.32 |
May | 72546.59 | 06-MAY-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 278.56 |
June | 61469.98 | 12-JUN-03:01 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 109.22 |
July | 45417.58 | 11-JUL-03:21 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 111.02 |
August | 50198.37 | 23-AUG-01:22 | 0.00 | 1453.55 | 16315.42 | 4887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 |
September | 61370.52 | 30-SEP-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 |
October | 69386.72 | 24-OCT-03:41 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 363.49 |
November | 72341.13 | 25-NOV-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 212.40 |
December | 67853.43 | 16-DEC-04:01 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 734.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38959.36 | 0.00 | 1453.55 | 16315.42 | 4887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 | |
Maximum of Months | 80755.13 | 0.00 | 2422.59 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 734.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.41 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.02 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.68 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.43 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1258.35 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.32 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1400.08 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.93 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.90 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.39 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.86 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.39 | 100.02 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.988611E+11 | 56363.72 | 03-JAN-17:10 | 0.850900E+11 | 99140.11 | 27-JAN-07:40 |
February | 0.903419E+11 | 58204.20 | 21-FEB-17:00 | 0.738862E+11 | 104039.73 | 03-FEB-07:10 |
March | 0.101747E+12 | 62872.38 | 22-MAR-11:00 | 0.756125E+11 | 88484.48 | 02-MAR-06:10 |
April | 0.111508E+12 | 72522.71 | 19-APR-18:40 | 0.658632E+11 | 49471.19 | 12-APR-06:10 |
May | 0.128948E+12 | 79153.31 | 19-MAY-11:00 | 0.657072E+11 | 43223.17 | 07-MAY-10:00 |
June | 0.139116E+12 | 84928.28 | 02-JUN-17:10 | 0.619086E+11 | 42947.24 | 03-JUN-10:20 |
July | 0.150964E+12 | 84727.76 | 03-JUL-17:19 | 0.627319E+11 | 42754.01 | 02-JUL-10:30 |
August | 0.143547E+12 | 83133.17 | 04-AUG-18:00 | 0.629809E+11 | 42732.62 | 27-AUG-10:39 |
September | 0.130478E+12 | 80155.65 | 15-SEP-11:00 | 0.617744E+11 | 42981.31 | 30-SEP-10:30 |
October | 0.115551E+12 | 80380.89 | 04-OCT-17:00 | 0.655078E+11 | 43266.10 | 29-OCT-10:30 |
November | 0.976137E+11 | 64670.91 | 09-NOV-17:10 | 0.716900E+11 | 72630.42 | 28-NOV-07:10 |
December | 0.987866E+11 | 51764.23 | 09-DEC-17:00 | 0.914257E+11 | 97018.69 | 27-DEC-07:10 |
Annual Sum or Average | 0.140746E+13 | 0.844178E+12 | ||||
Minimum of Months | 0.903419E+11 | 51764.23 | 0.617744E+11 | 42732.62 | ||
Maximum of Months | 0.150964E+12 | 84928.28 | 0.914257E+11 | 104039.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.107512E+11 | 0.707100E+10 | 0.391293E+11 | 0.00 | 0.302498E+11 | 37879553.69 | 0.00 | 0.101703E+09 | 0.00 | 0.00 | 0.00 | 0.639296E+10 | 0.00 |
February | 0.973789E+10 | 0.604909E+10 | 0.353426E+11 | 0.00 | 0.273364E+11 | 34213790.43 | 0.00 | 0.134532E+10 | 0.00 | 0.00 | 0.00 | 0.578306E+10 | 0.00 |
March | 0.109224E+11 | 0.621666E+10 | 0.391293E+11 | 0.00 | 0.302858E+11 | 37879553.69 | 0.00 | 0.339331E+10 | 0.00 | 0.00 | 0.00 | 0.645622E+10 | 0.00 |
April | 0.104466E+11 | 0.553264E+10 | 0.378671E+11 | 0.00 | 0.297701E+11 | 36657632.61 | 0.00 | 0.163480E+11 | 0.00 | 0.00 | 0.00 | 0.619539E+10 | 0.00 |
May | 0.108368E+11 | 0.530188E+10 | 0.391293E+11 | 0.00 | 0.310463E+11 | 37879553.69 | 0.00 | 0.305903E+11 | 0.00 | 0.00 | 0.00 | 0.641521E+10 | 0.00 |
June | 0.105574E+11 | 0.492278E+10 | 0.378671E+11 | 0.00 | 0.300976E+11 | 36657632.61 | 0.00 | 0.439501E+11 | 0.00 | 0.00 | 0.00 | 0.623623E+10 | 0.00 |
July | 0.107273E+11 | 0.517826E+10 | 0.391293E+11 | 0.00 | 0.311579E+11 | 37879553.69 | 0.00 | 0.526862E+11 | 0.00 | 0.00 | 0.00 | 0.637154E+10 | 0.00 |
August | 0.109224E+11 | 0.553264E+10 | 0.391293E+11 | 0.00 | 0.311509E+11 | 37879553.69 | 0.00 | 0.446536E+11 | 0.00 | 0.00 | 0.00 | 0.644973E+10 | 0.00 |
September | 0.104491E+11 | 0.580185E+10 | 0.378671E+11 | 0.00 | 0.301774E+11 | 36657632.61 | 0.00 | 0.344808E+11 | 0.00 | 0.00 | 0.00 | 0.619451E+10 | 0.00 |
October | 0.107500E+11 | 0.649961E+10 | 0.391293E+11 | 0.00 | 0.308536E+11 | 37879553.69 | 0.00 | 0.163419E+11 | 0.00 | 0.00 | 0.00 | 0.638047E+10 | 0.00 |
November | 0.104076E+11 | 0.671114E+10 | 0.378671E+11 | 0.00 | 0.293633E+11 | 36657632.61 | 0.00 | 0.193657E+10 | 0.00 | 0.00 | 0.00 | 0.618285E+10 | 0.00 |
December | 0.107286E+11 | 0.717539E+10 | 0.391293E+11 | 0.00 | 0.302300E+11 | 37879553.69 | 0.00 | 7217954.46 | 0.00 | 0.00 | 0.00 | 0.638547E+10 | 0.00 |
Annual Sum or Average | 0.127237E+12 | 0.719929E+11 | 0.460716E+12 | 0.00 | 0.361719E+12 | 0.446001E+09 | 0.00 | 0.245835E+12 | 0.00 | 0.00 | 0.00 | 0.754436E+11 | 0.00 |
Minimum of Months | 0.973789E+10 | 0.492278E+10 | 0.353426E+11 | 0.00 | 0.273364E+11 | 34213790.43 | 0.00 | 7217954.46 | 0.00 | 0.00 | 0.00 | 0.578306E+10 | 0.00 |
Maximum of Months | 0.109224E+11 | 0.717539E+10 | 0.391293E+11 | 0.00 | 0.311579E+11 | 37879553.69 | 0.00 | 0.526862E+11 | 0.00 | 0.00 | 0.00 | 0.645622E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.148332E+11 | 0.00 | 0.303571E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.104228E+11 | 0.00 | 0.274249E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.612564E+10 | 0.00 | 0.295871E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.523217E+09 | 0.00 | 0.267274E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.130312E+09 | 0.00 | 0.256772E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 39504338.41 | 0.00 | 0.232564E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 17965581.82 | 0.00 | 0.228142E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 24902627.79 | 0.00 | 0.230563E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 11902546.78 | 0.00 | 0.231498E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 14704956.29 | 0.00 | 0.255934E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.631788E+10 | 0.00 | 0.267595E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.221691E+11 | 0.00 | 0.293568E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.606311E+11 | 0.00 | 0.313760E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 11902546.78 | 0.00 | 0.228142E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.221691E+11 | 0.00 | 0.303571E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6293.88 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13460.95 | 01-JAN-09:39 | 17.86 | 30-JAN-08:00 | 0.00 | 01-JAN-00:10 |
February | 6293.88 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13460.95 | 01-FEB-20:30 | 17.86 | 03-FEB-08:50 | 0.00 | 01-FEB-00:10 |
March | 6293.88 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13460.95 | 01-MAR-05:30 | 17.86 | 02-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 6293.88 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13460.95 | 02-APR-12:39 | 17.86 | 04-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 6293.88 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13460.95 | 01-MAY-12:50 | 17.86 | 21-MAY-08:20 | 0.00 | 01-MAY-00:10 |
June | 6293.88 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13460.95 | 02-JUN-06:00 | 17.86 | 02-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 6293.88 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13460.95 | 01-JUL-23:19 | 17.86 | 03-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 6293.88 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13460.95 | 02-AUG-16:49 | 17.86 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 6293.88 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13460.95 | 01-SEP-04:30 | 17.86 | 03-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 6293.88 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13460.95 | 01-OCT-09:39 | 17.86 | 01-OCT-08:00 | 0.00 | 01-OCT-00:10 |
November | 6293.88 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13460.95 | 04-NOV-13:30 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 6293.88 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13460.95 | 01-DEC-05:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13460.95 | 17.86 | 0.00 | ||||||
Maximum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13460.95 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4839.47 | 03-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.56 | 06-JAN-19:30 | 0.00 |
February | 11101.58 | 06-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.92 | 02-FEB-19:00 | 0.00 |
March | 15361.98 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4741.89 | 14-MAR-06:49 | 0.00 |
April | 25013.31 | 21-APR-12:00 | 0.00 | 0.00 | 0.00 | 4742.10 | 11-APR-06:30 | 0.00 |
May | 31144.90 | 19-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4739.79 | 02-MAY-06:40 | 0.00 |
June | 38263.30 | 02-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4737.22 | 20-JUN-06:49 | 0.00 |
July | 37834.96 | 03-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.89 | 21-JUL-18:30 | 0.00 |
August | 35242.65 | 07-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.87 | 03-AUG-18:30 | 0.00 |
September | 32180.89 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4737.59 | 12-SEP-06:19 | 0.00 |
October | 30262.53 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 4741.18 | 11-OCT-06:10 | 0.00 |
November | 15223.57 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4742.17 | 17-NOV-07:49 | 0.00 |
December | 1600.99 | 16-DEC-04:10 | 0.00 | 0.00 | 0.00 | 4741.94 | 06-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1600.99 | 0.00 | 0.00 | 0.00 | 4736.87 | 0.00 | ||
Maximum of Months | 38263.30 | 0.00 | 0.00 | 0.00 | 4742.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56363.72 | 03-JAN-17:10 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 4722.42 | 0.00 |
February | 58204.20 | 21-FEB-17:00 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 6439.10 | 0.00 |
March | 62872.38 | 22-MAR-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 14905.55 | 0.00 |
April | 72522.71 | 19-APR-18:40 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 22411.18 | 0.00 |
May | 79153.31 | 19-MAY-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 31144.90 | 0.00 |
June | 84928.28 | 02-JUN-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 38263.30 | 0.00 |
July | 84727.76 | 03-JUL-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 37809.01 | 0.00 |
August | 83133.17 | 04-AUG-18:00 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 32927.62 | 0.00 |
September | 80155.65 | 15-SEP-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 32180.89 | 0.00 |
October | 80380.89 | 04-OCT-17:00 | 6293.88 | 20676.91 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 28848.98 | 0.00 |
November | 64670.91 | 09-NOV-17:10 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 13005.20 | 0.00 |
December | 51764.23 | 09-DEC-17:00 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 51764.23 | 6293.88 | 19067.80 | 0.00 | 0.00 | 13460.95 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84928.28 | 6293.88 | 23090.58 | 4578.48 | 0.00 | 13460.95 | 17.86 | 0.00 | 38263.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 64276.93 | 27-JAN-07:10 | 0.00 | 26104.56 | 26-JAN-19:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 68397.15 | 03-FEB-06:00 | 0.00 | 26105.40 | 01-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 61813.98 | 02-MAR-06:10 | 0.00 | 25234.96 | 01-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 22696.05 | 12-APR-05:00 | 0.00 | 21956.53 | 03-APR-06:19 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 22889.74 | 16-MAY-03:49 | 0.00 | 17986.85 | 02-MAY-06:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 7658.49 | 06-JUN-03:49 | 0.00 | 17396.80 | 01-JUN-18:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 5041.59 | 05-JUL-03:49 | 0.00 | 17099.27 | 03-JUL-06:30 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 9612.64 | 11-AUG-03:49 | 0.00 | 17118.28 | 31-AUG-18:40 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 6683.33 | 05-SEP-03:49 | 0.00 | 17392.64 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 3453.84 | 25-OCT-05:00 | 0.00 | 17811.47 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 45885.78 | 27-NOV-23:19 | 0.00 | 22382.51 | 30-NOV-19:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 65365.00 | 27-DEC-07:10 | 0.00 | 25095.43 | 29-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 3453.84 | 0.00 | 17099.27 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 68397.15 | 0.00 | 26105.40 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.70 | 0.00 | 24.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.04 | 0.00 | 25.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.05 | 0.00 | 25.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.96 | 0.00 | 24.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.95 | 0.00 | 24.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.79 | 0.00 | 24.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.00 | 24.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.17 | 24.93 | 0.00 | 24.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.05 | 0.00 | 25.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.44 | 0.00 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 0.00 | 27.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.46 | 0.00 | 28.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 30.45 | 0.00 | 30.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 30.72 | 0.00 | 30.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 30.76 | 0.17 | 30.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 30.93 | 0.17 | 30.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 30.85 | 0.33 | 30.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 31.02 | 0.00 | 31.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 30.66 | 0.00 | 30.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.76 | 0.00 | 28.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.44 | 0.00 | 27.44 |
Annual Sum or Average | 0.00 | 0.00 | 211.83 | 30.47 | 0.67 | 30.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.44 | 0.00 | 27.44 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 31.02 | 0.33 | 31.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.67 | 21.76 | 25.50 | 21.73 | 16.00 | 21.66 |
February | 331.83 | 22.02 | 31.33 | 22.02 | 14.67 | 21.94 |
March | 288.83 | 22.13 | 20.33 | 22.16 | 6.83 | 22.12 |
April | 98.33 | 22.78 | 250.50 | 23.74 | 0.00 | 23.74 |
May | 21.33 | 24.14 | 470.83 | 24.17 | 2.33 | 24.19 |
June | 27.67 | 27.37 | 558.67 | 24.37 | 26.83 | 24.51 |
July | 183.67 | 24.63 | 609.00 | 24.30 | 183.67 | 24.36 |
August | 98.67 | 25.02 | 611.83 | 24.31 | 98.67 | 24.39 |
September | 102.50 | 24.40 | 577.00 | 24.17 | 98.33 | 24.21 |
October | 75.50 | 23.45 | 510.83 | 23.98 | 34.83 | 24.00 |
November | 263.83 | 21.79 | 117.33 | 22.42 | 5.00 | 22.38 |
December | 476.83 | 21.63 | 35.67 | 21.51 | 35.67 | 21.40 |
Annual Sum or Average | 2419.67 | 22.46 | 3818.83 | 23.44 | 522.83 | 23.49 |
Minimum of Months | 21.33 | 21.63 | 20.33 | 21.51 | 0.00 | 21.40 |
Maximum of Months | 476.83 | 27.37 | 611.83 | 24.37 | 183.67 | 24.51 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 455.67 | 19.97 | 167.00 | 20.61 | 73.50 | 20.50 |
February | 333.67 | 20.49 | 250.17 | 22.00 | 74.67 | 21.97 |
March | 352.00 | 21.72 | 337.83 | 23.33 | 120.50 | 23.53 |
April | 394.50 | 25.11 | 501.83 | 25.45 | 332.67 | 25.59 |
May | 487.50 | 25.95 | 597.50 | 25.92 | 482.83 | 25.94 |
June | 561.33 | 26.00 | 592.00 | 26.00 | 561.33 | 26.00 |
July | 609.00 | 26.00 | 609.00 | 26.00 | 609.00 | 26.00 |
August | 611.83 | 25.99 | 612.00 | 25.99 | 611.83 | 25.99 |
September | 557.33 | 25.93 | 584.33 | 25.90 | 553.67 | 25.92 |
October | 464.67 | 25.57 | 555.17 | 25.52 | 431.17 | 25.65 |
November | 371.00 | 21.66 | 303.33 | 23.06 | 126.67 | 23.38 |
December | 455.00 | 19.63 | 191.83 | 20.28 | 90.67 | 20.12 |
Annual Sum or Average | 5653.50 | 24.01 | 5302.00 | 24.68 | 4068.50 | 24.92 |
Minimum of Months | 333.67 | 19.63 | 167.00 | 20.28 | 73.50 | 20.12 |
Maximum of Months | 611.83 | 26.00 | 612.00 | 26.00 | 611.83 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.33359 | 26.11819 | -0.0590 | 7.15615 |
February | 551.00000 | 22.79846 | 22.15181 | 0.03111 | 7.05481 |
March | 612.00000 | 23.11477 | 20.45172 | 0.10784 | 7.07443 |
April | 590.00000 | 23.85547 | 23.07738 | 0.35173 | 8.45161 |
May | 611.00000 | 24.11914 | 31.77488 | -0.3063 | 7.70066 |
June | 592.00000 | 24.21156 | 36.93380 | -0.1882 | 6.57098 |
July | 609.00000 | 24.20347 | 51.99699 | -0.0754 | 5.81901 |
August | 612.00000 | 24.19070 | 47.13220 | -0.1125 | 5.94139 |
September | 590.00000 | 24.10712 | 45.79422 | -0.1515 | 6.09173 |
October | 610.00000 | 23.93744 | 38.94351 | 0.51496 | 11.11555 |
November | 591.00000 | 22.99652 | 26.10274 | 0.14711 | 7.65161 |
December | 609.00000 | 22.14037 | 23.25563 | -0.1195 | 7.51885 |
Annual Sum or Average | 7187.00000 | 23.50362 | 32.89602 | 0.01116 | 7.34927 |
Minimum of Months | 551.00000 | 22.14037 | 20.45172 | -0.3063 | 5.81901 |
Maximum of Months | 612.00000 | 24.21156 | 51.99699 | 0.51496 | 11.11555 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.94154 | 31.03537 | -0.1200 | 9.88706 |
February | 551.00000 | 22.11223 | 26.62413 | 0.11660 | 12.25410 |
March | 612.00000 | 23.02537 | 24.60797 | 0.31908 | 14.45665 |
April | 590.00000 | 25.02903 | 24.86613 | 0.82271 | 23.11237 |
May | 611.00000 | 25.81491 | 31.40993 | 0.51317 | 12.40944 |
June | 592.00000 | 25.99223 | 36.00387 | 0.65886 | 14.76615 |
July | 609.00000 | 26.00235 | 50.37430 | 0.79212 | 18.62634 |
August | 612.00000 | 25.99286 | 45.58309 | 0.74661 | 17.22175 |
September | 590.00000 | 25.83231 | 44.74867 | 0.67556 | 16.22092 |
October | 610.00000 | 25.10780 | 39.51159 | 0.98755 | 28.36014 |
November | 591.00000 | 22.59646 | 30.06137 | 0.29168 | 14.53467 |
December | 609.00000 | 20.69094 | 28.29955 | -0.1890 | 10.24305 |
Annual Sum or Average | 7187.00000 | 24.10356 | 34.49528 | 0.46931 | 16.02502 |
Minimum of Months | 551.00000 | 20.69094 | 24.60797 | -0.1890 | 9.88706 |
Maximum of Months | 612.00000 | 26.00235 | 50.37430 | 0.98755 | 28.36014 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.232339E+09 | 83145003.00 | 12.39 | 0.229774E+09 | 2565646.64 | 0.00 | 0.15 | 03-JAN-14:00 | 0.00 | 01-JAN-00:05 | 11877.57 | 03-JAN-14:00 | 11877.57 | 03-JAN-14:00 | 404.10 | 12-JAN-14:00 | 4193.64 | 03-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.279729E+10 | 0.980693E+09 | 76.24 | 0.279704E+10 | 247923.18 | 0.00 | 0.29 | 06-FEB-14:00 | 0.00 | 01-FEB-00:10 | 24402.24 | 06-FEB-14:00 | 24402.24 | 06-FEB-14:00 | 375.94 | 08-FEB-04:15 | 8319.71 | 06-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.705207E+10 | 0.245251E+10 | 160.92 | 0.705207E+10 | 1290.02 | 0.00 | 1.00 | 16-MAR-03:01 | 0.00 | 01-MAR-00:10 | 101016.37 | 16-MAR-03:01 | 101016.37 | 16-MAR-03:01 | 1.70 | 10-MAR-17:53 | 28458.90 | 16-MAR-03:01 | 0.00 | 01-MAR-00:10 |
April | 0.321819E+11 | 0.108124E+11 | 360.25 | 0.316365E+11 | 0.545416E+09 | 0.00 | 1.00 | 02-APR-03:02 | 0.00 | 01-APR-00:01 | 101016.37 | 02-APR-03:02 | 101016.37 | 05-APR-03:41 | 26884.82 | 30-APR-03:01 | 28458.90 | 02-APR-03:02 | 0.00 | 01-APR-00:01 |
May | 0.588337E+11 | 0.196304E+11 | 511.18 | 0.553004E+11 | 0.353334E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 101016.37 | 15-MAY-03:15 | 101016.37 | 01-MAY-03:01 | 42135.84 | 25-MAY-03:01 | 28458.90 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.806550E+11 | 0.274826E+11 | 561.41 | 0.741746E+11 | 0.648041E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 101016.37 | 01-JUN-03:01 | 101016.37 | 14-JUN-03:15 | 48787.89 | 28-JUN-03:01 | 28636.70 | 15-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.101856E+12 | 0.330880E+11 | 600.23 | 0.756511E+11 | 0.262050E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 110548.41 | 21-JUL-03:01 | 101016.37 | 03-JUL-03:01 | 71543.25 | 21-JUL-03:01 | 29212.33 | 21-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.859724E+11 | 0.282630E+11 | 578.93 | 0.693135E+11 | 0.166588E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 108065.15 | 02-AUG-03:01 | 99467.64 | 23-AUG-03:01 | 54565.37 | 02-AUG-03:14 | 29011.74 | 02-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.683229E+11 | 0.222415E+11 | 498.68 | 0.545902E+11 | 0.137328E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 106003.06 | 22-SEP-03:01 | 87325.99 | 29-SEP-03:01 | 57836.83 | 14-SEP-03:11 | 28849.99 | 22-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.326982E+11 | 0.108681E+11 | 352.18 | 0.275178E+11 | 0.518040E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 103495.19 | 04-OCT-03:01 | 101016.37 | 02-OCT-03:01 | 52636.10 | 04-OCT-03:01 | 28654.62 | 04-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.408241E+10 | 0.142012E+10 | 105.39 | 0.390783E+10 | 0.174582E+09 | 0.00 | 1.00 | 08-NOV-04:01 | 0.00 | 01-NOV-00:01 | 101016.37 | 08-NOV-04:01 | 98588.03 | 08-NOV-04:01 | 12836.67 | 10-NOV-04:01 | 28458.90 | 08-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 811155.15 | 295396.70 | 0.50 | 811155.15 | 0.00 | 0.00 | 0.02 | 08-DEC-14:00 | 0.00 | 01-DEC-00:05 | 1250.94 | 08-DEC-14:00 | 1250.94 | 08-DEC-14:00 | 0.00 | 08-DEC-14:00 | 455.42 | 08-DEC-14:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.474685E+12 | 0.157323E+12 | 3818.30 | 0.402172E+12 | 0.725136E+11 | 0.00 | ||||||||||||||
Minimum of Months | 811155.15 | 295396.70 | 0.50 | 811155.15 | 0.00 | 0.00 | 0.02 | 0.00 | 1250.94 | 1250.94 | 0.00 | 455.42 | 0.00 | |||||||
Maximum of Months | 0.101856E+12 | 0.330880E+11 | 600.23 | 0.756511E+11 | 0.262050E+11 | 0.00 | 1.00 | 0.00 | 110548.41 | 101016.37 | 71543.25 | 29212.33 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 52636792.31 | 18557589.71 | 7.51 | 49719134.69 | 2917657.62 | 0.00 | 0.15 | 13-JAN-04:05 | 0.00 | 01-JAN-00:05 | 5828.93 | 13-JAN-04:05 | 4321.55 | 13-JAN-04:05 | 1507.38 | 13-JAN-04:05 | 2013.05 | 13-JAN-04:05 | 0.00 | 01-JAN-00:05 |
February | 0.106398E+10 | 0.364626E+09 | 64.10 | 0.104995E+10 | 14033663.41 | 0.00 | 1.00 | 07-FEB-04:01 | 0.00 | 01-FEB-00:10 | 47179.07 | 20-FEB-04:41 | 43588.26 | 07-FEB-04:41 | 15534.87 | 14-FEB-04:41 | 13023.30 | 07-FEB-04:01 | 0.00 | 01-FEB-00:10 |
March | 0.276923E+10 | 0.940798E+09 | 135.44 | 0.275466E+10 | 14571470.50 | 0.00 | 1.00 | 05-MAR-04:01 | 0.00 | 01-MAR-00:10 | 47179.07 | 05-MAR-04:01 | 46657.45 | 16-MAR-03:01 | 20939.32 | 11-MAR-04:01 | 13023.30 | 05-MAR-04:01 | 0.00 | 01-MAR-00:10 |
April | 0.171277E+11 | 0.553561E+10 | 352.86 | 0.167776E+11 | 0.350143E+09 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 47179.07 | 30-APR-03:31 | 47179.07 | 21-APR-03:01 | 17608.13 | 30-APR-03:31 | 13023.30 | 01-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.344884E+11 | 0.109599E+11 | 520.69 | 0.324659E+11 | 0.202248E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 47179.07 | 23-MAY-01:22 | 47179.07 | 15-MAY-02:52 | 22952.09 | 25-MAY-03:01 | 13023.30 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.513111E+11 | 0.164675E+11 | 597.61 | 0.473406E+11 | 0.397053E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 47179.07 | 03-JUN-01:22 | 47179.07 | 01-JUN-02:62 | 26179.34 | 28-JUN-03:21 | 14342.80 | 02-JUN-16:46 | 0.00 | 01-JUN-00:01 |
July | 0.651863E+11 | 0.195982E+11 | 638.25 | 0.477202E+11 | 0.174661E+11 | 0.00 | 1.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:01 | 51528.73 | 21-JUL-10:56 | 46669.22 | 03-JUL-01:22 | 35223.78 | 21-JUL-03:01 | 13749.11 | 03-JUL-16:12 | 0.00 | 01-JUL-00:01 |
August | 0.531131E+11 | 0.163906E+11 | 611.75 | 0.424951E+11 | 0.106180E+11 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 50130.37 | 02-AUG-03:43 | 46307.14 | 23-AUG-00:42 | 29430.78 | 02-AUG-03:43 | 13249.95 | 02-AUG-03:43 | 0.00 | 01-AUG-00:01 |
September | 0.398552E+11 | 0.122393E+11 | 504.00 | 0.310366E+11 | 0.881861E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 49582.52 | 22-SEP-03:01 | 39324.74 | 11-SEP-00:42 | 31564.88 | 22-SEP-03:01 | 13207.95 | 22-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.171917E+11 | 0.547384E+10 | 339.71 | 0.138295E+11 | 0.336223E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 47443.35 | 04-OCT-03:01 | 47017.59 | 02-OCT-00:20 | 27288.19 | 04-OCT-03:01 | 13043.94 | 04-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.153080E+10 | 0.516450E+09 | 81.26 | 0.138107E+10 | 0.149738E+09 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 47179.07 | 01-NOV-03:01 | 47174.38 | 24-NOV-04:41 | 23318.06 | 03-NOV-03:01 | 13023.30 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 20964759.91 | 6922557.75 | 2.26 | 17079448.35 | 3885311.56 | 0.00 | 1.00 | 11-DEC-04:01 | 0.00 | 01-DEC-00:05 | 47179.07 | 11-DEC-04:01 | 42712.35 | 16-DEC-04:01 | 10799.66 | 11-DEC-04:01 | 13023.30 | 11-DEC-04:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.283711E+12 | 0.885122E+11 | 3855.44 | 0.236918E+12 | 0.467933E+11 | 0.00 | ||||||||||||||
Minimum of Months | 20964759.91 | 6922557.75 | 2.26 | 17079448.35 | 2917657.62 | 0.00 | 0.15 | 0.00 | 5828.93 | 4321.55 | 1507.38 | 2013.05 | 0.00 | |||||||
Maximum of Months | 0.651863E+11 | 0.195982E+11 | 638.25 | 0.477202E+11 | 0.174661E+11 | 0.00 | 1.00 | 0.00 | 51528.73 | 47179.07 | 35223.78 | 14342.80 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.72 | 87.67 | 74.05 | 144.86 | 440.09 | 0.00 | 0.00 | 0.00 |
February | 216.90 | 123.67 | 93.24 | 235.30 | 386.84 | 0.00 | 0.00 | 0.00 |
March | 267.28 | 147.12 | 120.16 | 320.30 | 321.12 | 0.00 | 0.00 | 0.00 |
April | 322.16 | 178.60 | 143.56 | 485.92 | 191.32 | 0.00 | 0.00 | 0.00 |
May | 332.13 | 180.35 | 151.77 | 581.07 | 117.93 | 0.00 | 0.00 | 0.00 |
June | 332.31 | 184.73 | 147.58 | 680.18 | 65.72 | 0.00 | 0.00 | 0.00 |
July | 298.19 | 155.84 | 142.35 | 613.19 | 54.68 | 0.00 | 0.00 | 0.00 |
August | 284.06 | 145.41 | 138.65 | 555.12 | 75.45 | 0.00 | 0.00 | 0.00 |
September | 281.77 | 160.84 | 120.94 | 503.75 | 134.74 | 0.00 | 0.00 | 0.00 |
October | 215.77 | 116.21 | 99.55 | 304.72 | 228.71 | 0.00 | 0.00 | 0.00 |
November | 193.24 | 112.25 | 80.99 | 202.35 | 376.43 | 0.00 | 0.00 | 0.00 |
December | 161.85 | 85.81 | 76.04 | 136.39 | 476.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.64 | 139.80 | 115.84 | 397.48 | 238.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.72 | 85.81 | 74.05 | 136.39 | 54.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.31 | 184.73 | 151.77 | 680.18 | 476.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 572.71 | 433.74 | 138.97 | 780.41 | 567.20 | 0.00 | 0.00 | 0.00 |
February | 539.44 | 382.50 | 156.94 | 747.80 | 515.42 | 0.00 | 0.00 | 0.00 |
March | 423.27 | 240.28 | 182.99 | 589.99 | 458.02 | 0.00 | 0.00 | 0.00 |
April | 295.79 | 112.05 | 183.74 | 473.65 | 294.60 | 0.00 | 0.00 | 0.00 |
May | 209.73 | 31.59 | 178.14 | 385.01 | 180.47 | 0.00 | 0.00 | 0.00 |
June | 179.10 | 11.78 | 167.32 | 429.45 | 96.42 | 0.00 | 0.00 | 0.00 |
July | 181.96 | 16.71 | 165.25 | 434.88 | 79.58 | 0.00 | 0.00 | 0.00 |
August | 230.12 | 59.38 | 170.74 | 506.39 | 111.57 | 0.00 | 0.00 | 0.00 |
September | 363.97 | 189.81 | 174.16 | 720.65 | 200.49 | 0.00 | 0.00 | 0.00 |
October | 497.87 | 338.36 | 159.52 | 816.19 | 317.03 | 0.00 | 0.00 | 0.00 |
November | 598.17 | 457.37 | 140.80 | 856.55 | 495.11 | 0.00 | 0.00 | 0.00 |
December | 587.87 | 441.40 | 146.46 | 781.70 | 605.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.11 | 225.33 | 163.78 | 625.97 | 325.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.10 | 11.78 | 138.97 | 385.01 | 79.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 598.17 | 457.37 | 183.74 | 856.55 | 605.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.74 | 96.26 | 74.48 | 174.15 | 455.78 | 0.00 | 0.00 | 0.00 |
February | 192.17 | 101.98 | 90.19 | 212.62 | 411.78 | 0.00 | 0.00 | 0.00 |
March | 262.06 | 140.47 | 121.60 | 328.81 | 344.86 | 0.00 | 0.00 | 0.00 |
April | 300.72 | 162.15 | 138.57 | 463.00 | 210.83 | 0.00 | 0.00 | 0.00 |
May | 324.54 | 173.62 | 150.92 | 575.65 | 129.45 | 0.00 | 0.00 | 0.00 |
June | 315.85 | 169.55 | 146.29 | 652.33 | 69.48 | 0.00 | 0.00 | 0.00 |
July | 280.50 | 139.34 | 141.16 | 582.52 | 56.76 | 0.00 | 0.00 | 0.00 |
August | 271.57 | 138.31 | 133.26 | 535.02 | 80.17 | 0.00 | 0.00 | 0.00 |
September | 278.77 | 155.56 | 123.20 | 512.88 | 147.02 | 0.00 | 0.00 | 0.00 |
October | 240.23 | 140.61 | 99.62 | 364.64 | 241.93 | 0.00 | 0.00 | 0.00 |
November | 200.52 | 122.01 | 78.51 | 237.82 | 399.62 | 0.00 | 0.00 | 0.00 |
December | 161.78 | 87.87 | 73.91 | 153.42 | 498.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 250.17 | 135.74 | 114.43 | 400.20 | 253.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.78 | 87.87 | 73.91 | 153.42 | 56.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.54 | 173.62 | 150.92 | 652.33 | 498.16 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.433151E+09 | 0.234807E+09 | 0.198344E+09 | 0.387984E+09 | 0.117875E+10 |
February | 0.524729E+09 | 0.299173E+09 | 0.225557E+09 | 0.569226E+09 | 0.935853E+09 |
March | 0.715889E+09 | 0.394046E+09 | 0.321843E+09 | 0.857885E+09 | 0.860084E+09 |
April | 0.835038E+09 | 0.462932E+09 | 0.372106E+09 | 0.125951E+10 | 0.495892E+09 |
May | 0.889572E+09 | 0.483062E+09 | 0.406511E+09 | 0.155632E+10 | 0.315853E+09 |
June | 0.861349E+09 | 0.478815E+09 | 0.382534E+09 | 0.176302E+10 | 0.170355E+09 |
July | 0.798665E+09 | 0.417389E+09 | 0.381276E+09 | 0.164238E+10 | 0.146453E+09 |
August | 0.760824E+09 | 0.389460E+09 | 0.371364E+09 | 0.148683E+10 | 0.202084E+09 |
September | 0.730358E+09 | 0.416888E+09 | 0.313470E+09 | 0.130571E+10 | 0.349237E+09 |
October | 0.577906E+09 | 0.311258E+09 | 0.266648E+09 | 0.816162E+09 | 0.612578E+09 |
November | 0.500881E+09 | 0.290951E+09 | 0.209930E+09 | 0.524504E+09 | 0.975710E+09 |
December | 0.433504E+09 | 0.229837E+09 | 0.203668E+09 | 0.365315E+09 | 0.127588E+10 |
Annual Sum or Average | 0.806187E+10 | 0.440862E+10 | 0.365325E+10 | 0.125348E+11 | 0.751873E+10 |
Minimum of Months | 0.433151E+09 | 0.229837E+09 | 0.198344E+09 | 0.365315E+09 | 0.146453E+09 |
Maximum of Months | 0.889572E+09 | 0.483062E+09 | 0.406511E+09 | 0.176302E+10 | 0.127588E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153394E+10 | 0.116173E+10 | 0.372210E+09 | 0.209024E+10 | 0.151920E+10 |
February | 0.130501E+10 | 0.925338E+09 | 0.379671E+09 | 0.180907E+10 | 0.124691E+10 |
March | 0.113369E+10 | 0.643560E+09 | 0.490131E+09 | 0.158024E+10 | 0.122675E+10 |
April | 0.766688E+09 | 0.290422E+09 | 0.476266E+09 | 0.122769E+10 | 0.763595E+09 |
May | 0.561737E+09 | 84602673.36 | 0.477134E+09 | 0.103120E+10 | 0.483381E+09 |
June | 0.464219E+09 | 30523046.33 | 0.433696E+09 | 0.111314E+10 | 0.249925E+09 |
July | 0.487367E+09 | 44757428.53 | 0.442610E+09 | 0.116478E+10 | 0.213150E+09 |
August | 0.616358E+09 | 0.159043E+09 | 0.457315E+09 | 0.135631E+10 | 0.298824E+09 |
September | 0.943408E+09 | 0.491993E+09 | 0.451415E+09 | 0.186792E+10 | 0.519672E+09 |
October | 0.133350E+10 | 0.906251E+09 | 0.427248E+09 | 0.218608E+10 | 0.849137E+09 |
November | 0.155046E+10 | 0.118551E+10 | 0.364946E+09 | 0.222017E+10 | 0.128333E+10 |
December | 0.157454E+10 | 0.118225E+10 | 0.392285E+09 | 0.209370E+10 | 0.162248E+10 |
Annual Sum or Average | 0.122709E+11 | 0.710598E+10 | 0.516493E+10 | 0.197405E+11 | 0.102763E+11 |
Minimum of Months | 0.464219E+09 | 30523046.33 | 0.364946E+09 | 0.103120E+10 | 0.213150E+09 |
Maximum of Months | 0.157454E+10 | 0.118551E+10 | 0.490131E+09 | 0.222017E+10 | 0.162248E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.457322E+09 | 0.257826E+09 | 0.199495E+09 | 0.466444E+09 | 0.122076E+10 |
February | 0.464890E+09 | 0.246714E+09 | 0.218177E+09 | 0.514374E+09 | 0.996188E+09 |
March | 0.701908E+09 | 0.376225E+09 | 0.325682E+09 | 0.880689E+09 | 0.923667E+09 |
April | 0.779467E+09 | 0.420284E+09 | 0.359184E+09 | 0.120009E+10 | 0.546483E+09 |
May | 0.869251E+09 | 0.465026E+09 | 0.404225E+09 | 0.154183E+10 | 0.346724E+09 |
June | 0.818671E+09 | 0.439483E+09 | 0.379189E+09 | 0.169084E+10 | 0.180094E+09 |
July | 0.751290E+09 | 0.373206E+09 | 0.378084E+09 | 0.156022E+10 | 0.152024E+09 |
August | 0.727383E+09 | 0.370460E+09 | 0.356923E+09 | 0.143299E+10 | 0.214715E+09 |
September | 0.722563E+09 | 0.403216E+09 | 0.319346E+09 | 0.132939E+10 | 0.381075E+09 |
October | 0.643428E+09 | 0.376600E+09 | 0.266828E+09 | 0.976653E+09 | 0.647976E+09 |
November | 0.519742E+09 | 0.316247E+09 | 0.203495E+09 | 0.616422E+09 | 0.103582E+10 |
December | 0.433316E+09 | 0.235344E+09 | 0.197971E+09 | 0.410913E+09 | 0.133428E+10 |
Annual Sum or Average | 0.788923E+10 | 0.428063E+10 | 0.360860E+10 | 0.126209E+11 | 0.797981E+10 |
Minimum of Months | 0.433316E+09 | 0.235344E+09 | 0.197971E+09 | 0.410913E+09 | 0.152024E+09 |
Maximum of Months | 0.869251E+09 | 0.465026E+09 | 0.404225E+09 | 0.169084E+10 | 0.133428E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1022.15 | 1385.81 | 905.17 | 617.67 | 287.50 | 0.00 | 0.00 |
February | 1126.41 | 1244.74 | 948.51 | 608.14 | 340.36 | 0.00 | 0.00 |
March | 1173.53 | 1058.41 | 952.62 | 527.86 | 424.75 | 0.00 | 0.00 |
April | 1371.48 | 645.66 | 918.67 | 452.79 | 465.88 | 0.00 | 0.00 |
May | 1517.74 | 403.87 | 866.40 | 385.56 | 480.84 | 0.00 | 0.00 |
June | 1754.91 | 224.57 | 827.25 | 366.06 | 461.20 | 0.00 | 0.00 |
July | 1624.33 | 184.76 | 760.65 | 311.89 | 448.76 | 0.00 | 0.00 |
August | 1587.44 | 258.10 | 785.75 | 343.10 | 442.65 | 0.00 | 0.00 |
September | 1714.79 | 459.76 | 924.51 | 506.21 | 418.30 | 0.00 | 0.00 |
October | 1461.14 | 763.26 | 953.87 | 595.17 | 358.69 | 0.00 | 0.00 |
November | 1232.44 | 1206.89 | 991.93 | 691.63 | 300.30 | 0.00 | 0.00 |
December | 977.14 | 1485.92 | 911.50 | 615.08 | 296.42 | 0.00 | 0.00 |
Annual Sum or Average | 1380.86 | 774.53 | 894.91 | 500.86 | 394.05 | 0.00 | 0.00 |
Minimum of Months | 977.14 | 184.76 | 760.65 | 311.89 | 287.50 | 0.00 | 0.00 |
Maximum of Months | 1754.91 | 1485.92 | 991.93 | 691.63 | 480.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.273772E+10 | 0.371176E+10 | 0.242441E+10 | 0.165436E+10 | 0.770049E+09 | 0.00 | 0.00 |
February | 0.272500E+10 | 0.301128E+10 | 0.229463E+10 | 0.147122E+10 | 0.823404E+09 | 0.00 | 0.00 |
March | 0.314317E+10 | 0.283486E+10 | 0.255149E+10 | 0.141383E+10 | 0.113766E+10 | 0.00 | 0.00 |
April | 0.355487E+10 | 0.167355E+10 | 0.238119E+10 | 0.117364E+10 | 0.120756E+10 | 0.00 | 0.00 |
May | 0.406511E+10 | 0.108171E+10 | 0.232056E+10 | 0.103269E+10 | 0.128787E+10 | 0.00 | 0.00 |
June | 0.454872E+10 | 0.582096E+09 | 0.214424E+10 | 0.948820E+09 | 0.119542E+10 | 0.00 | 0.00 |
July | 0.435062E+10 | 0.494866E+09 | 0.203732E+10 | 0.835353E+09 | 0.120197E+10 | 0.00 | 0.00 |
August | 0.425181E+10 | 0.691304E+09 | 0.210456E+10 | 0.918963E+09 | 0.118560E+10 | 0.00 | 0.00 |
September | 0.444473E+10 | 0.119170E+10 | 0.239633E+10 | 0.131210E+10 | 0.108423E+10 | 0.00 | 0.00 |
October | 0.391352E+10 | 0.204432E+10 | 0.255483E+10 | 0.159411E+10 | 0.960724E+09 | 0.00 | 0.00 |
November | 0.319448E+10 | 0.312825E+10 | 0.257108E+10 | 0.179271E+10 | 0.778371E+09 | 0.00 | 0.00 |
December | 0.261718E+10 | 0.397988E+10 | 0.244136E+10 | 0.164743E+10 | 0.793924E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.435469E+11 | 0.244256E+11 | 0.282220E+11 | 0.157952E+11 | 0.124268E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261718E+10 | 0.494866E+09 | 0.203732E+10 | 0.835353E+09 | 0.770049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.454872E+10 | 0.397988E+10 | 0.257108E+10 | 0.179271E+10 | 0.128787E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639283E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167666959.7 | 81.22 | 0.00 | 0.00 |
February | 0.578301E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148727804.1 | 81.22 | 0.00 | 0.00 |
March | 0.645605E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162191500.9 | 81.22 | 0.00 | 0.00 |
April | 0.619526E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151761863.4 | 81.21 | 0.00 | 0.00 |
May | 0.641504E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154843298.3 | 81.21 | 0.00 | 0.00 |
June | 0.623600E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149408769.0 | 81.21 | 0.00 | 0.00 |
July | 0.637138E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154278095.5 | 81.21 | 0.00 | 0.00 |
August | 0.644954E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154300204.0 | 81.21 | 0.00 | 0.00 |
September | 0.619445E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149618143.0 | 81.21 | 0.00 | 0.00 |
October | 0.638029E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156462163.2 | 81.21 | 0.00 | 0.00 |
November | 0.618255E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157930170.9 | 81.22 | 0.00 | 0.00 |
December | 0.638541E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168326847.4 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754418E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.187552E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578301E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168326847.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645605E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148727804.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.223008E+11 | -0.213397E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -961142580.2 | 58.99 | 0.00 | 0.00 |
February | 0.201388E+11 | -0.192955E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -843325092.7 | 58.99 | 0.00 | 0.00 |
March | 0.216767E+11 | -0.207657E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -910930661.9 | 58.99 | 0.00 | 0.00 |
April | 0.194434E+11 | -0.186091E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -834210405.9 | 58.99 | 0.00 | 0.00 |
May | 0.185263E+11 | -0.176825E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843741441.2 | 58.98 | 0.00 | 0.00 |
June | 0.166482E+11 | -0.158357E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -812513124.6 | 58.98 | 0.00 | 0.00 |
July | 0.162191E+11 | -0.153805E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838586637.3 | 58.99 | 0.00 | 0.00 |
August | 0.164209E+11 | -0.155821E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838779320.3 | 58.99 | 0.00 | 0.00 |
September | 0.165640E+11 | -0.157495E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -814436536.3 | 58.99 | 0.00 | 0.00 |
October | 0.184602E+11 | -0.176017E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -858529246.2 | 58.99 | 0.00 | 0.00 |
November | 0.194635E+11 | -0.185730E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -890483116.9 | 58.99 | 0.00 | 0.00 |
December | 0.214953E+11 | -0.205281E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -967192916.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.227357E+12 | -0.216943E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.104139E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.162191E+11 | -0.213397E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -967192916.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.223008E+11 | -0.153805E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -812513124.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544159E+10 | 37260.30 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385914E+10 | 35603.57 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231799E+10 | 34286.64 | 16-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226940E+09 | 65979.13 | 27-APR-03:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104250E+09 | 60873.84 | 03-MAY-03:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31603470.73 | 30542.70 | 01-JUN-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14372465.45 | 12099.82 | 05-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19922102.23 | 23070.33 | 11-AUG-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9522037.43 | 16039.99 | 05-SEP-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7315851.97 | 21352.77 | 30-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221511E+10 | 38743.43 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.828815E+10 | 41455.27 | 27-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7315851.97 | 12099.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.828815E+10 | 65979.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.642494E+10 | 29844.79 | 28-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447909E+10 | 28883.19 | 03-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258252E+10 | 33173.73 | 02-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191633E+09 | 8876.46 | 12-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4448113.06 | 1588.63 | 25-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283920E+10 | 23754.64 | 16-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944717E+10 | 34261.98 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.944717E+10 | 34261.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.232339E+09 | 0.229774E+09 | 11877.57 | 03-JAN-14:00 | 11877.57 | 0.00 |
February | 0.00 | 0.00 | 0.279729E+10 | 0.279704E+10 | 24402.24 | 06-FEB-14:00 | 24402.24 | 0.00 |
March | 0.00 | 0.00 | 0.705207E+10 | 0.705207E+10 | 101016.37 | 16-MAR-03:01 | 101016.37 | 0.00 |
April | 0.00 | 0.00 | 0.321819E+11 | 0.316365E+11 | 101016.37 | 02-APR-03:02 | 101016.37 | 0.00 |
May | 0.00 | 0.00 | 0.588337E+11 | 0.553004E+11 | 101016.37 | 15-MAY-03:15 | 101016.37 | 0.00 |
June | 0.00 | 0.00 | 0.806550E+11 | 0.741746E+11 | 101016.37 | 01-JUN-03:01 | 101016.37 | 0.00 |
July | 0.00 | 0.00 | 0.101856E+12 | 0.756511E+11 | 110548.41 | 21-JUL-03:01 | 39005.15 | 0.00 |
August | 0.00 | 0.00 | 0.859724E+11 | 0.693135E+11 | 108065.15 | 02-AUG-03:01 | 54203.85 | 0.00 |
September | 0.00 | 0.00 | 0.683229E+11 | 0.545902E+11 | 106003.06 | 22-SEP-03:01 | 50166.53 | 0.00 |
October | 0.00 | 0.00 | 0.326982E+11 | 0.275178E+11 | 103495.19 | 04-OCT-03:01 | 50859.08 | 0.00 |
November | 0.00 | 0.00 | 0.408241E+10 | 0.390783E+10 | 101016.37 | 08-NOV-04:01 | 98588.03 | 0.00 |
December | 0.00 | 0.00 | 811155.15 | 811155.15 | 1250.94 | 08-DEC-14:00 | 1250.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.474685E+12 | 0.402172E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 811155.15 | 811155.15 | 1250.94 | 1250.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101856E+12 | 0.756511E+11 | 110548.41 | 101016.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 52636792.31 | 49719134.69 | 5828.93 | 13-JAN-04:05 | 4321.55 | 0.00 |
February | 0.00 | 0.00 | 0.106398E+10 | 0.104995E+10 | 47179.07 | 20-FEB-04:41 | 41184.81 | 0.00 |
March | 0.00 | 0.00 | 0.276923E+10 | 0.275466E+10 | 47179.07 | 05-MAR-04:01 | 37678.89 | 0.00 |
April | 0.00 | 0.00 | 0.171277E+11 | 0.167776E+11 | 47179.07 | 30-APR-03:31 | 29570.94 | 0.00 |
May | 0.00 | 0.00 | 0.344884E+11 | 0.324659E+11 | 47179.07 | 23-MAY-01:22 | 31440.81 | 0.00 |
June | 0.00 | 0.00 | 0.513111E+11 | 0.473406E+11 | 47179.07 | 03-JUN-01:22 | 45315.64 | 0.00 |
July | 0.00 | 0.00 | 0.651863E+11 | 0.477202E+11 | 51528.73 | 21-JUL-10:56 | 21712.19 | 0.00 |
August | 0.00 | 0.00 | 0.531131E+11 | 0.424951E+11 | 50130.37 | 02-AUG-03:43 | 20699.59 | 0.00 |
September | 0.00 | 0.00 | 0.398552E+11 | 0.310366E+11 | 49582.52 | 22-SEP-03:01 | 18017.64 | 0.00 |
October | 0.00 | 0.00 | 0.171917E+11 | 0.138295E+11 | 47443.35 | 04-OCT-03:01 | 20155.16 | 0.00 |
November | 0.00 | 0.00 | 0.153080E+10 | 0.138107E+10 | 47179.07 | 01-NOV-03:01 | 25024.18 | 0.00 |
December | 0.00 | 0.00 | 20964759.91 | 17079448.35 | 47179.07 | 11-DEC-04:01 | 36379.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.283711E+12 | 0.236918E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 20964759.91 | 17079448.35 | 5828.93 | 4321.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.651863E+11 | 0.477202E+11 | 51528.73 | 45315.64 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8428.47 | 16107.43 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 8437.13 | 16101.15 | 03-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 8214.25 | 15803.78 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7642.21 | 14918.40 | 03-APR-18:17 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 7065.37 | 13882.83 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6574.39 | 12787.88 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 6208.40 | 11930.28 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 6283.63 | 11982.30 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6540.99 | 12757.16 | 29-SEP-18:24 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7035.62 | 13889.29 | 31-OCT-18:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7628.02 | 14979.88 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8125.76 | 15759.45 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 7342.50 | ||||
Minimum of Months | 0.00 | 0.00 | 6208.40 | 11930.28 | ||
Maximum of Months | 0.00 | 0.00 | 8437.13 | 16107.43 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.510936E+10 | 0.64 | 2203.40 | 01-JAN-00:05 | 0.73 |
February | 0.462219E+10 | 0.64 | 2203.40 | 01-FEB-00:10 | 0.74 |
March | 0.512820E+10 | 0.64 | 2203.40 | 01-MAR-00:10 | 0.74 |
April | 0.528886E+10 | 0.68 | 2203.40 | 01-APR-03:01 | 0.73 |
May | 0.561786E+10 | 0.70 | 2203.40 | 01-MAY-00:12 | 0.74 |
June | 0.544007E+10 | 0.70 | 2203.40 | 01-JUN-00:10 | 0.73 |
July | 0.562344E+10 | 0.69 | 2203.40 | 01-JUL-00:09 | 0.73 |
August | 0.562179E+10 | 0.69 | 2203.40 | 01-AUG-00:09 | 0.73 |
September | 0.544022E+10 | 0.69 | 2203.40 | 01-SEP-00:09 | 0.72 |
October | 0.552860E+10 | 0.68 | 2203.40 | 01-OCT-00:17 | 0.73 |
November | 0.500360E+10 | 0.64 | 2203.40 | 01-NOV-02:25 | 0.73 |
December | 0.509053E+10 | 0.63 | 2203.40 | 01-DEC-00:05 | 0.73 |
Annual Sum or Average | 0.635147E+11 | 0.67 | |||
Minimum of Months | 0.462219E+10 | 0.63 | 2203.40 | 0.72 | |
Maximum of Months | 0.562344E+10 | 0.70 | 2203.40 | 0.74 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204222E+11 | 1.48 | 9149.74 | 01-JAN-05:10 | 1.77 |
February | 0.184465E+11 | 1.48 | 9149.74 | 01-FEB-09:48 | 1.78 |
March | 0.204246E+11 | 1.48 | 9149.74 | 01-MAR-05:30 | 1.78 |
April | 0.198404E+11 | 1.51 | 9149.74 | 01-APR-09:13 | 1.78 |
May | 0.205778E+11 | 1.51 | 9149.74 | 01-MAY-11:07 | 1.78 |
June | 0.199329E+11 | 1.50 | 9149.74 | 01-JUN-06:05 | 1.78 |
July | 0.206110E+11 | 1.50 | 9149.74 | 01-JUL-06:40 | 1.76 |
August | 0.206218E+11 | 1.50 | 9149.74 | 01-AUG-08:32 | 1.76 |
September | 0.200190E+11 | 1.50 | 9149.74 | 01-SEP-04:30 | 1.75 |
October | 0.205192E+11 | 1.51 | 9149.74 | 01-OCT-09:20 | 1.77 |
November | 0.197766E+11 | 1.49 | 9149.74 | 02-NOV-16:12 | 1.76 |
December | 0.204229E+11 | 1.48 | 9149.74 | 01-DEC-06:00 | 1.77 |
Annual Sum or Average | 0.241615E+12 | 1.50 | |||
Minimum of Months | 0.184465E+11 | 1.48 | 9149.74 | 1.75 | |
Maximum of Months | 0.206218E+11 | 1.51 | 9149.74 | 1.78 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.471820E+10 | 0.89 | 2107.81 | 01-JAN-05:15 | 1.03 |
February | 0.426773E+10 | 0.90 | 2107.81 | 01-FEB-00:30 | 1.04 |
March | 0.473308E+10 | 0.90 | 2107.81 | 01-MAR-00:50 | 1.04 |
April | 0.464086E+10 | 0.95 | 2107.81 | 21-APR-07:46 | 1.04 |
May | 0.485061E+10 | 0.96 | 2107.81 | 01-MAY-09:50 | 1.04 |
June | 0.472459E+10 | 0.95 | 2107.81 | 01-JUN-04:25 | 1.04 |
July | 0.492351E+10 | 0.95 | 2107.81 | 01-JUL-04:08 | 1.03 |
August | 0.490731E+10 | 0.95 | 2107.81 | 01-AUG-04:10 | 1.02 |
September | 0.471827E+10 | 0.96 | 2107.81 | 01-SEP-04:10 | 1.02 |
October | 0.480580E+10 | 0.95 | 2107.81 | 01-OCT-08:19 | 1.03 |
November | 0.458307E+10 | 0.90 | 2107.81 | 02-NOV-16:28 | 1.03 |
December | 0.471666E+10 | 0.89 | 2107.81 | 01-DEC-00:40 | 1.03 |
Annual Sum or Average | 0.565897E+11 | 0.93 | |||
Minimum of Months | 0.426773E+10 | 0.89 | 2107.81 | 1.02 | |
Maximum of Months | 0.492351E+10 | 0.96 | 2107.81 | 1.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:05 | 5.36 | 5.36 | 48.83 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:10 | 5.36 | 5.36 | 49.97 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:10 | 5.36 | 5.36 | 50.13 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.64 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.04 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 53.63 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.84 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.19 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 53.75 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.18 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.96 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 50.57 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.83 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.19 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.83 | 59.67 | 8428.47 | 16107.43 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 49.97 | 58.98 | 8437.13 | 16101.15 | 03-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.13 | 59.00 | 8214.25 | 15803.78 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.15 | 51.15 | 7642.21 | 14918.40 | 03-APR-18:17 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.04 | 51.04 | 7065.37 | 13882.83 | 01-MAY-06:53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.32 | 52.32 | 6574.39 | 12787.88 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.66 | 52.66 | 6208.40 | 11930.28 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.47 | 52.47 | 6283.63 | 11982.30 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.10 | 52.10 | 6540.99 | 12757.16 | 29-SEP-18:24 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 50.16 | 50.16 | 7035.62 | 13889.29 | 31-OCT-18:37 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.17 | 51.17 | 7628.02 | 14979.88 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.57 | 59.41 | 8125.76 | 15759.45 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 7342.50 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.83 | 50.16 | 6208.40 | 11930.28 | ||
Maximum of Months | 0.00 | 0.00 | 52.66 | 59.67 | 8437.13 | 16107.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.205054E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.194272E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.228771E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.306528E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.402083E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.474155E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.536990E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.488848E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.422604E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.313873E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.211967E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204232E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.398938E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194272E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.536990E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.473675E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.463236E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.567387E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.101765E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.158105E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211921E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.245217E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.212979E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169576E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102796E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.509952E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.472358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145102E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.463236E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245217E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204222E+11 | 0.232339E+09 | 0.544159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184465E+11 | 0.279729E+10 | 0.385914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204246E+11 | 0.705207E+10 | 0.231799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198404E+11 | 0.321819E+11 | 0.226940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205778E+11 | 0.588337E+11 | 0.104250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199329E+11 | 0.806550E+11 | 31603470.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206110E+11 | 0.101856E+12 | 14372465.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206218E+11 | 0.859724E+11 | 19922102.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200190E+11 | 0.683229E+11 | 9522037.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205192E+11 | 0.326982E+11 | 7315851.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197766E+11 | 0.408241E+10 | 0.221511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204229E+11 | 811155.15 | 0.828815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241615E+12 | 0.474685E+12 | 0.225359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.184465E+11 | 811155.15 | 7315851.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206218E+11 | 0.101856E+12 | 0.828815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.471820E+10 | 52636792.31 | 0.642494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426773E+10 | 0.106398E+10 | 0.447909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473308E+10 | 0.276923E+10 | 0.258252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464086E+10 | 0.171277E+11 | 0.191633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485061E+10 | 0.344884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472459E+10 | 0.513111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.492351E+10 | 0.651863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.490731E+10 | 0.531131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471827E+10 | 0.398552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480580E+10 | 0.171917E+11 | 4448113.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458307E+10 | 0.153080E+10 | 0.283920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471666E+10 | 20964759.91 | 0.944717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565897E+11 | 0.283711E+12 | 0.259690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.426773E+10 | 20964759.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492351E+10 | 0.651863E+11 | 0.944717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204222E+11 | 0.00 | 0.00 | 0.00 | 83145003.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184465E+11 | 0.00 | 0.00 | 0.00 | 0.980693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204246E+11 | 0.00 | 0.00 | 0.00 | 0.245251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198404E+11 | 0.00 | 0.00 | 0.00 | 0.108124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205778E+11 | 0.00 | 0.00 | 0.00 | 0.196304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199329E+11 | 0.00 | 0.00 | 0.00 | 0.274826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206110E+11 | 0.00 | 0.00 | 0.00 | 0.330880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206218E+11 | 0.00 | 0.00 | 0.00 | 0.282630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200190E+11 | 0.00 | 0.00 | 0.00 | 0.222415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205192E+11 | 0.00 | 0.00 | 0.00 | 0.108681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197766E+11 | 0.00 | 0.00 | 0.00 | 0.142012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204229E+11 | 0.00 | 0.00 | 0.00 | 295396.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241615E+12 | 0.00 | 0.00 | 0.00 | 0.157323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.184465E+11 | 0.00 | 0.00 | 0.00 | 295396.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206218E+11 | 0.00 | 0.00 | 0.00 | 0.330880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.471820E+10 | 0.00 | 0.00 | 0.00 | 18557589.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426773E+10 | 0.00 | 0.00 | 0.00 | 0.364626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473308E+10 | 0.00 | 0.00 | 0.00 | 0.940798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464086E+10 | 0.00 | 0.00 | 0.00 | 0.553561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485061E+10 | 0.00 | 0.00 | 0.00 | 0.109599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472459E+10 | 0.00 | 0.00 | 0.00 | 0.164675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.492351E+10 | 0.00 | 0.00 | 0.00 | 0.195982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.490731E+10 | 0.00 | 0.00 | 0.00 | 0.163906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471827E+10 | 0.00 | 0.00 | 0.00 | 0.122393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480580E+10 | 0.00 | 0.00 | 0.00 | 0.547384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458307E+10 | 0.00 | 0.00 | 0.00 | 0.516450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471666E+10 | 0.00 | 0.00 | 0.00 | 6922557.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565897E+11 | 0.00 | 0.00 | 0.00 | 0.885122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.426773E+10 | 0.00 | 0.00 | 0.00 | 6922557.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.492351E+10 | 0.00 | 0.00 | 0.00 | 0.195982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339644E+11 | 0.00 | 0.00 | 26498403.91 | 0.00 | 0.517884E+09 | 0.222083E+11 | 0.00 | 4.00 |
February | 0.233750E+11 | 0.00 | 0.00 | 45131738.14 | 0.00 | 0.311439E+09 | 0.256899E+11 | 0.00 | 4.86 |
March | 0.196713E+11 | 0.00 | 0.00 | 73805736.40 | 0.00 | 0.109195E+09 | 0.320004E+11 | 0.00 | 5.59 |
April | 0.577200E+10 | 0.384970E+09 | 52082.70 | 0.126945E+09 | 0.00 | 6954432.40 | 0.254001E+11 | 58431.88 | 5.78 |
May | 0.132115E+10 | 0.331776E+10 | 161286.41 | 0.107135E+09 | 817418.42 | 7414049.49 | 0.146405E+11 | 91505.39 | 5.30 |
June | 0.442101E+09 | 0.964973E+10 | 930977.49 | 39648980.05 | 34253436.33 | 2100832.35 | 0.410544E+10 | 80100.35 | 4.69 |
July | 0.331994E+09 | 0.220664E+11 | 3403646.27 | 7972827.22 | 0.153226E+09 | 98994.39 | 0.846170E+09 | 70313.47 | 4.78 |
August | 0.483538E+09 | 0.124279E+11 | 3945510.96 | 34022792.13 | 77774710.78 | 8123.67 | 0.529299E+10 | 121950.38 | 5.19 |
September | 0.121174E+10 | 0.761049E+10 | 1303606.23 | 79585969.11 | 23372224.94 | 284992.80 | 0.123783E+11 | 33234.99 | 5.62 |
October | 0.349155E+10 | 0.161648E+10 | 107649.29 | 0.120718E+09 | 2899003.72 | 1552677.52 | 0.332230E+11 | 5971.85 | 6.49 |
November | 0.210989E+11 | 0.00 | 0.00 | 66567404.07 | 0.00 | 22081587.00 | 0.328731E+11 | 0.00 | 5.23 |
December | 0.394011E+11 | 0.00 | 0.00 | 21633688.63 | 0.00 | 0.888739E+09 | 0.189793E+11 | 0.00 | 3.88 |
Annual Sum or Average | 0.150565E+12 | 0.570737E+11 | 9904759.34 | 0.749666E+09 | 0.292343E+09 | 0.186775E+10 | 0.227638E+12 | 461508.30 | 5.12 |
Minimum of Months | 0.331994E+09 | 0.00 | 0.00 | 7972827.22 | 0.00 | 8123.67 | 0.846170E+09 | 0.00 | 3.88 |
Maximum of Months | 0.394011E+11 | 0.220664E+11 | 3945510.96 | 0.126945E+09 | 0.153226E+09 | 0.888739E+09 | 0.332230E+11 | 121950.38 | 6.49 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.433038E+11 | 0.00 | 0.00 | 12513400.41 | 0.00 | 0.00 | 0.154522E+11 | 0.00 | 10.75 |
February | 0.305571E+11 | 0.00 | 0.00 | 34126406.28 | 0.00 | 0.00 | 0.206510E+11 | 0.00 | 11.18 |
March | 0.258385E+11 | 0.00 | 0.00 | 58488238.68 | 0.00 | 0.00 | 0.277649E+11 | 0.00 | 11.63 |
April | 0.716720E+10 | 18664531.47 | 0.00 | 0.121051E+09 | 0.00 | 0.00 | 0.298193E+11 | 0.00 | 12.31 |
May | 0.110213E+10 | 0.578584E+09 | 0.00 | 0.144554E+09 | 0.00 | 0.00 | 0.218722E+11 | 0.00 | 12.54 |
June | 2404375.58 | 0.360329E+10 | 0.00 | 0.115923E+09 | 0.00 | 0.00 | 0.939084E+10 | 0.00 | 12.27 |
July | 0.00 | 0.106819E+11 | 0.00 | 40398585.69 | 0.00 | 0.00 | 0.338908E+10 | 0.00 | 12.51 |
August | 0.00 | 0.424441E+10 | 0.00 | 0.104392E+09 | 0.00 | 0.00 | 0.946198E+10 | 0.00 | 12.65 |
September | 0.684153E+09 | 0.197123E+10 | 0.00 | 0.139957E+09 | 0.00 | 0.00 | 0.177540E+11 | 0.00 | 12.77 |
October | 0.474410E+10 | 0.338142E+09 | 0.00 | 0.124456E+09 | 0.00 | 0.00 | 0.342624E+11 | 0.00 | 12.62 |
November | 0.257938E+11 | 0.00 | 0.00 | 51084168.45 | 0.00 | 0.00 | 0.281176E+11 | 0.00 | 11.30 |
December | 0.485738E+11 | 0.00 | 0.00 | 10286100.06 | 0.00 | 0.00 | 0.138371E+11 | 0.00 | 10.65 |
Annual Sum or Average | 0.187767E+12 | 0.214362E+11 | 0.00 | 0.957230E+09 | 0.00 | 0.00 | 0.231773E+12 | 0.00 | 11.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10286100.06 | 0.00 | 0.00 | 0.338908E+10 | 0.00 | 10.65 |
Maximum of Months | 0.485738E+11 | 0.106819E+11 | 0.00 | 0.144554E+09 | 0.00 | 0.00 | 0.342624E+11 | 0.00 | 12.77 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.650710E+11 | 0.141944E+11 | 0.176180E+12 | 0.433642E+10 | 0.231182E+11 |
February | 0.707696E+11 | 0.118546E+11 | 0.146907E+12 | 0.939608E+10 | 0.277752E+11 |
March | 0.120171E+12 | 0.120448E+11 | 0.146839E+12 | 0.156477E+11 | 0.389706E+11 |
April | 0.134514E+12 | 0.814021E+10 | 0.996173E+11 | 0.142542E+11 | 0.928425E+11 |
May | 0.151258E+12 | 0.523461E+10 | 0.587651E+11 | 0.911175E+10 | 0.153370E+12 |
June | 0.142416E+12 | 0.274415E+10 | 0.113573E+11 | 0.339550E+10 | 0.207090E+12 |
July | 0.133218E+12 | -7697168.1 | -0.268860E+11 | -722674454.3 | 0.252503E+12 |
August | 0.120534E+12 | 0.208399E+10 | 0.724874E+10 | 0.398194E+10 | 0.215810E+12 |
September | 0.104552E+12 | 0.324796E+10 | 0.408647E+11 | 0.777992E+10 | 0.174342E+12 |
October | 0.897200E+11 | 0.705597E+10 | 0.104692E+12 | 0.183801E+11 | 0.939390E+11 |
November | 0.672761E+11 | 0.116839E+11 | 0.153802E+12 | 0.136540E+11 | 0.306091E+11 |
December | 0.535261E+11 | 0.144745E+11 | 0.186444E+12 | 0.345337E+10 | 0.244226E+11 |
Annual Sum or Average | 0.125303E+13 | 0.927513E+11 | 0.110583E+13 | 0.102668E+12 | 0.133479E+13 |
Minimum of Months | 0.535261E+11 | -7697168.1 | -0.268860E+11 | -722674454.3 | 0.231182E+11 |
Maximum of Months | 0.151258E+12 | 0.144745E+11 | 0.186444E+12 | 0.183801E+11 | 0.252503E+12 |