Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:28:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2172.52 | 4250.24 | 4250.24 |
Net Site Energy | 2172.52 | 4250.24 | 4250.24 |
Total Source Energy | 5277.57 | 10324.83 | 10324.83 |
Net Source Energy | 5277.57 | 10324.83 | 10324.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 12.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 300.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 52.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 351.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.42 | 286.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 65.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1403.05 | 769.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 12.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 300.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 52.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 351.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.42 | 286.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 12.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 300.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 52.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 351.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.42 | 286.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 65.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1424.10 | 586.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1028.58 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2744.87 | 1505.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1424.10 | 586.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1028.58 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2744.87 | 1505.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1403.052 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1403.052 | 100.00 |
Total On-Site and Utility Electric Sources | 1403.052 | 100.00 |
Total Electricity End Uses | 1403.052 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 3.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4682.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 12.0182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6242 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 12.0182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6242 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 11.3653 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-17:19 | 07-DEC-06:10 | - | - | - | - | - | - | - | - | - | - | 24-FEB-19:10 |
Heating | 0.00 | 53618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41908.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13107.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4433.20 | 14910.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2061.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 86999.26 | 80296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 53618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 41908.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13107.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4433.20 | 14910.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 521.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 994.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 13.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 951.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 306.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 166.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1113.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.84 | 310.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 206.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4443.46 | 834.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1862.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 324.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2177.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.26 | 608.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 403.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8693.02 | 1631.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1862.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 324.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2177.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.26 | 608.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 403.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8693.02 | 1631.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.82 |
KITCHEN DIRECT AIR | 1.85 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 1.00 | 0.999990 | 4.82 |
PSZ-AC_2:2 | 1.85 | 1.85 | 1.85 | 1.85 | 1.85 | 1.85 | 1.00 | 1.00 | 1.85 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.82 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.85 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.82 | 8919.51 |
PSZ-AC_2:2_ADDAQ FAN | 1.85 | 1984.41 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.82 | 4.82 | 4.82 | 4.82 | 99541.39 | 130663.55 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.85 | 1.85 | 1.85 | 1.85 | 46051.90 | 80663.62 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.82 | 2.41 | 4.82 | 99541.39 | 49645.90 | 99541.39 | 0.763930 | 0.763930 |
PSZ-AC_2:2 COOLING COIL | 1.85 | 0.927255 | 1.85 | 46051.90 | 23025.95 | 46051.90 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 130663.55 |
PSZ-AC_2:2 HEATING COIL | 80663.62 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 12.018 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 76.946 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.624 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.704 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 4467.734 | 12.018 | 15.948 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4467.734 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1341.663 | 9.624 | 178.225 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1341.663 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 50198.21241 | 60237.85489 | 4.01982 | 4.82378 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 5271.62790 | 6325.95347 | 0.24889 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 0.50000 | 4.31558E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22740.41135 | 27288.49362 | 1.54543 | 1.85451 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | 00:10:00 | 0.50000 | 4.31558E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 83861.66 | 4.82383 | 4.82383 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 57769.76 | 1.33138 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 50203.17 | 1.85451 | 1.85451 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 65093.85 | 1.50017 | 1.50017 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.82378 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.85451 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.82378 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.82378 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.82378 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.82378 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.82383 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.82383 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.85451 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.85451 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.85451 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.85451 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.85451 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.85451 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.82383 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.85451 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.82383 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.82383 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 8919.50658 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.82383 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.82383 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.82383 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.82383 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.82383 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.41191 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.82383 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 99541.39000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 49645.89504 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 99541.39000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76393 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76393 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 99541.39000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 130663.54583 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 130663.54583 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.85451 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.85451 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1984.41348 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.85451 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.85451 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.85451 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.85451 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.85451 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.92726 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.85451 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 46051.90000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 23025.94984 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 46051.90000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46051.90000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 80663.61657 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 80663.61657 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 96061.8 | 10.16 | 10.03 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 44733.8 | 11.29 | 11.15 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.9589428970E-002 | 0.2318840856 | Pass | Pass | 8.0106693849E-002 | 0.2346937429 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2088895706 | 0.7759107581 | Pass | Pass | 2.6720730315E-002 | 8.4665384598E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4485363591 | 0.4071432603 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1098.52 | 61.48 | 793.59 | 108.56 | 1616.91 | 3679.07 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 12.0182 | 371.75 | 4467.73 | LightsWired | LTG_SCH_DINING | 93.20 | 168.00 | 92.65 | 0.0000 | Y | 77.70 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6242 | 139.41 | 1341.66 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.21 |
Interior Lighting Total | 11.3653 | 511.15 | 5809.40 | 96.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 3334.35 | AstronomicalClock | - | 83.79 | 83.79 | 52.44 | |
Exterior Lighting Total | 3334.35 | 52.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 99541.39 | 76042.65 | 23498.74 | 0.76 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46051.90 | 32286.07 | 13765.83 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 96061.8 | 10.16 | 10.03 | ||||
PSZ-AC_2:2 COOLING COIL | 44733.8 | 11.29 | 11.15 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 130663.55 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 80663.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1110.54 | 4.82 | 8919.51 | 1849.05 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.85 | 1984.41 | 1070.05 | 1.00 | 1.33 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 50198.21 | 60237.85 | 162.04 | 4.020 | 4.824 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00935 | 40.53 | 0.00563 | 1.331 | 0.00 |
KITCHEN | 22740.41 | 27288.49 | 195.75 | 1.545 | 1.855 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01012 | 39.60 | 0.00563 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5271.63 | 6325.95 | 17.02 | 0.249 | 1.331 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00771 | 0.50 | 0.00432 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | 00:10:00 | 19.00 | 24.61 | 0.00396 | 0.50 | 0.00432 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.82 | 4.82 | 1.33 | 1.33 | 4.8238 | 4.8238 | 4.8238 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.85 | 1.85 | 1.50 | 1.50 | 1.8545 | 1.8545 | 1.8545 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 99541.390 | 76042.654 | 4.823830 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 99541.39 | 99541.39 | 4.823830 | 28.63 | 16.82 | 0.00832582 | 11.14 | 10.38 | 0.00832582 | 40.80 | 0.00563111 | 18.58 | 27.6000 | 23.99 | 0.00935365 | 45.6683 | 50174.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 130663.546 | 130663.546 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | 130663.55 | 130663.55 | 4.823830 | 15.34 | 10.56 | 0.00677597 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 27.6000 | 21.00 | 0.00771391 | 45.2940 | 5267.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 46051.900 | 32286.066 | 1.854510 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 46051.90 | 46051.90 | 1.854510 | 38.46 | 18.39 | 0.00633965 | 11.84 | 8.62 | 0.00633965 | 40.80 | 0.00563111 | 18.58 | 80.8931 | 25.99 | 0.01012126 | 43.8285 | 21830.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 80663.617 | 80663.617 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 80663.62 | 80663.62 | 1.854510 | 0.40 | 0.35 | 0.00424730 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 80.8931 | 24.61 | 0.00395818 | 18.7808 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 99541.390 | 76042.654 | 4.823830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3173 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.823830 | 5.27338255 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 99541.39 | 99541.39 | 1.0000 | 5.27338306 | 4.823830 | 28.63 | 16.82 | 0.00832582 | 50036.3 | 11.14 | 10.38 | 0.00832582 | 32191.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99541.39 | 40.80 | 0.00563111 | 18.58 | 1.33137743 | 27.6000 | 23.99 | 0.00935365 | 23.99 | 0.00935365 | 45.6683 | 50174.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 130663.546 | 130663.546 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.823830 | 5.27338255 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 02:10:00 | Sensible | 130663.55 | 130663.55 | 1.0000 | 5.27338255 | 4.823830 | 15.34 | 10.56 | 0.00677597 | 32555.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 130663.55 | 0.50 | 0.00431558 | 0.50 | 1.33137743 | 27.6000 | 21.00 | 0.00771391 | 21.00 | 0.00771391 | 45.2940 | 5267.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46051.900 | 32286.066 | 1.854510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.6251 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.854510 | 2.02733972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 46051.90 | 46051.90 | 1.0000 | 2.02733961 | 1.854510 | 38.46 | 18.39 | 0.00633965 | 54951.3 | 11.84 | 8.62 | 0.00633965 | 27889.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46051.90 | 40.80 | 0.00563111 | 18.58 | 1.50017041 | 80.8931 | 25.95 | 0.01012126 | 25.99 | 0.01012126 | 43.8285 | 21830.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 80663.617 | 80663.617 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.854510 | 2.02733972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 80663.62 | 80663.62 | 1.0000 | 2.02733972 | 1.854510 | 0.40 | 0.35 | 0.00424730 | 11031.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80663.62 | 0.50 | 0.00431558 | 0.50 | 1.50017041 | 80.8931 | 0.00 | 0.00395818 | 24.61 | 0.00395818 | 18.7808 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.82 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.50 | 1.85 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4429.83 | 1431.83 | 341.17 |
KITCHEN | 6042.67 | 5573.83 | 4658.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6049.67 | 5770.17 | 4682.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 224.67 | 0.00 | 3.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 224.67 | 0.00 | 3.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 6.017 | 0.913 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.804 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.198 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.556 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 48792271.11 | 0.00 | 48792271.11 | 7437117.95 | 56229389.06 | 41986318.57 | 1460.00 | 4730.21 | 2569.79 | 113.72 |
KITCHEN | 42868466.53 | 0.00 | 42868466.53 | 230040.68 | 43098507.20 | 47309374.20 | 1408.93 | 5264.72 | 2086.35 | 702.10 |
Total Facility | 91660737.64 | 0.00 | 91660737.64 | 7667158.62 | 99327896.26 | 89295692.77 | 1460.00 | 5764.29 | 3119.13 | 702.32 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.8581 | 0.0000 | 1.8581 | 0.2821 | 2.1401 | 1.3314 | 0.00 | 4652.03 | 2534.97 |
KITCHEN | 1.5912 | 0.0000 | 1.5912 | 0.0055 | 1.5967 | 1.5002 | 0.00 | 5175.01 | 2011.99 |
Total Facility | 3.4493 | 0.0000 | 3.4493 | 0.2876 | 3.7369 | 2.8315 | 0.00 | 5667.80 | 3027.76 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 58310921.71 | 0.00 | 58310921.71 | 41986318.57 | 1460.00 | 0.00 | 7300.00 | 113.72 |
PSZ-AC_2:2 | 51230972.43 | 0.00 | 51230972.43 | 47309374.20 | 1389.67 | 1.75 | 7368.57 | 702.10 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.2205 | 0.0000 | 2.2205 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.9016 | 0.0000 | 1.9016 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1349.12 | 1227.47 | 4724.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4702.78 | 2311.55 | 874.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 4.0366 | 2.6384 | 1.5914 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.7931 | 2.1791 | 1.7929 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
Electricity:Building | 574.49 | 4184.74 | 01-JAN-01:10 | 31858.89 | 02-JAN-11:10 |
Electricity:Zone:DINING | 202.98 | 1123.36 | 01-JAN-01:10 | 10843.36 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 557.63 | 3775.71 | 01-JAN-01:10 | 29493.74 | 02-JAN-11:10 |
InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 371.51 | 3061.38 | 01-JAN-01:10 | 21015.54 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 65.04 | 1038.02 | 05-DEC-23:30 | 3441.39 | 13-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 124.05 | 1103.52 | 07-DEC-01:10 | 6477.18 | 13-NOV-19:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.09 | 0.00 | 01-JAN-11:10 | 1526.90 | 25-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 31.10 | 750.85 | 16-DEC-06:00 | 1076.23 | 08-JAN-04:30 |
ElectricityPurchased:Facility | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
ElectricityPurchased:Plant | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
Cogeneration:ElectricityPurchased | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
General:Cogeneration:ElectricityPurchased | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
ElectricityNet:Plant | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
Cogeneration:ElectricityNet | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
General:Cogeneration:ElectricityNet | 1403.05 | 8622.62 | 07-DEC-01:10 | 86999.26 | 28-JUN-17:20 |
Electricity:HVAC | 652.07 | 0.00 | 01-JAN-01:10 | 55236.71 | 28-JUN-17:10 |
Fans:Electricity | 351.50 | 0.00 | 01-JAN-01:10 | 13107.32 | 01-JAN-17:40 |
General:Fans:Electricity | 351.50 | 0.00 | 01-JAN-01:10 | 13107.32 | 01-JAN-17:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 300.57 | 0.00 | 01-JAN-00:10 | 42129.39 | 28-JUN-17:10 |
General:Cooling:Electricity | 300.57 | 0.00 | 01-JAN-00:10 | 42129.39 | 28-JUN-17:10 |
ExteriorLights:Electricity | 52.44 | 0.00 | 01-JAN-07:30 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 52.44 | 0.00 | 01-JAN-07:30 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4742.12 | 09-FEB-07:40 |
Water Heater:WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4742.12 | 09-FEB-07:40 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 769.47 | 2803.57 | 01-JAN-01:10 | 80296.00 | 07-DEC-06:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 12.84 | 0.00 | 01-JAN-01:10 | 53618.67 | 07-DEC-06:10 |
Heating:NaturalGas | 12.84 | 0.00 | 01-JAN-01:10 | 53618.67 | 07-DEC-06:10 |
General:Heating:NaturalGas | 12.84 | 0.00 | 01-JAN-01:10 | 53618.67 | 07-DEC-06:10 |
NaturalGas:Plant | 286.84 | 993.32 | 01-JAN-00:10 | 21877.50 | 30-JAN-07:50 |
WaterSystems:NaturalGas | 286.84 | 993.32 | 01-JAN-00:10 | 21877.50 | 30-JAN-07:50 |
Water Heater:WaterSystems:NaturalGas | 286.84 | 993.32 | 01-JAN-00:10 | 21877.50 | 30-JAN-07:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2169.38 | 3207.61 | 07-DEC-01:10 | 193511.38 | 18-AUG-11:10 |
EnergyTransfer:Building | 905.02 | 1603.81 | 07-DEC-01:10 | 61727.40 | 26-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN | 479.00 | 1603.81 | 07-DEC-01:10 | 29117.19 | 31-OCT-04:10 |
Refrigeration:EnergyTransfer | 155.13 | 2714.19 | 05-DEC-23:30 | 7834.84 | 17-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.57 | 1357.09 | 05-DEC-23:30 | 3917.42 | 17-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 77.57 | 1357.09 | 05-DEC-23:30 | 3917.42 | 17-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.57 | 1357.09 | 05-DEC-23:30 | 3917.42 | 17-JAN-04:50 |
EnergyTransfer:Plant | 273.02 | 1603.81 | 07-DEC-01:10 | 16856.73 | 23-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.49 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 62.08 | 1262.54 | 16-DEC-06:00 | 2238.70 | 08-JAN-04:30 |
EnergyTransfer:Zone:DINING | 426.03 | 0.00 | 01-JAN-01:10 | 39608.69 | 28-JUN-17:20 |
Heating:EnergyTransfer | 2.83 | 0.00 | 01-JAN-00:10 | 13757.65 | 29-JUN-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.83 | 0.00 | 01-JAN-00:10 | 13757.65 | 29-JUN-23:10 |
General:Heating:EnergyTransfer | 2.83 | 0.00 | 01-JAN-00:10 | 13757.65 | 29-JUN-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.83 | 0.00 | 01-JAN-00:10 | 13757.65 | 29-JUN-23:10 |
Cooling:EnergyTransfer | 824.63 | 0.00 | 01-JAN-01:10 | 59100.46 | 26-AUG-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 423.20 | 0.00 | 01-JAN-01:10 | 39608.69 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer | 824.63 | 0.00 | 01-JAN-01:10 | 59100.46 | 26-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 423.20 | 0.00 | 01-JAN-01:10 | 39608.69 | 28-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 73.73 | 17-JUL-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 73.73 | 17-JUL-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 401.43 | 0.00 | 01-JAN-01:10 | 25199.77 | 31-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 401.43 | 0.00 | 01-JAN-01:10 | 25199.77 | 31-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
PlantLoopHeatingDemand:Plant | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
General:WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
EnergyTransfer:HVAC | 991.34 | 0.00 | 01-JAN-01:10 | 125118.09 | 19-JUL-12:00 |
HeatingCoils:EnergyTransfer | 10.27 | 0.00 | 01-JAN-01:10 | 42894.93 | 07-DEC-06:10 |
CoolingCoils:EnergyTransfer | 981.06 | 0.00 | 01-JAN-00:10 | 125118.09 | 19-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
WaterUse:WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14209.46 | 25-JAN-19:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.826 | -423.197 | 0.000 | 0.000 | 208.356 | 77.705 | 93.957 | 49.407 | 0.000 | 28.876 | 10.797 | 0.000 | -16.871 | 0.000 | -31.857 | -0.002 |
KITCHEN | 0.000 | 0.000 | 0.000 | -401.421 | 0.000 | 0.000 | 5.056 | 19.212 | 297.857 | 0.000 | 0.000 | 0.407 | 80.702 | 0.000 | 0.000 | 0.000 | -1.813 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.266 | 35.632 | 0.000 | 0.000 | 0.000 | -46.898 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.826 | -824.619 | 0.000 | 0.000 | 213.412 | 96.917 | 391.814 | 49.407 | 0.000 | 40.549 | 127.131 | 0.000 | -16.871 | 0.000 | -80.568 | -0.003 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 01-JUL-04:01 | 0.00 | 0.00 | 0.00 | -54864.59 | 0.00 | 0.00 | 0.00 | 640.63 | 2172.30 | 0.00 | 0.00 | 0.00 | 53347.66 | 0.00 | -1253.24 | 0.00 | -42.75 | 0.00 |
KITCHEN | 31-OCT-04:01 | 0.00 | 0.00 | 0.00 | -73097.21 | 0.00 | 0.00 | 4.25 | 211.18 | 7256.93 | 0.00 | 0.00 | 0.00 | 65723.95 | 0.00 | -0.00 | 0.00 | -99.09 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-04:01 | 0.00 | 0.00 | 0.00 | -101186.24 | 0.00 | 0.00 | 805.94 | 1065.36 | 9429.23 | 0.00 | 0.00 | 804.88 | 90552.89 | 0.00 | -1320.98 | 0.00 | -151.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 17912.54 | 0.00 | 0.00 | 0.00 | 973.97 | 640.63 | 543.07 | 516.99 | 0.00 | 312.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20899.96 |
KITCHEN | 17-JUL-04:03 | 0.00 | 0.00 | 442.70 | 0.00 | 0.00 | 0.00 | 6.82 | 211.18 | 7256.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.67 | -7913.96 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-23:01 | -10024.35 | 10024.35 | 17912.54 | -10024.35 | 0.00 | 0.00 | 996.44 | 799.01 | 3382.99 | 516.99 | 0.00 | 1222.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14806.60 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8238 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8238 | 0.2760 | 1.0000 | Not calculated | 1.3314 | 0.2760 | ||
PSZ-AC_2:2 | 1.8545 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8545 | 0.0985 | 1.0000 | Not calculated | 0.1826 | 0.0985 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8238 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8238 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2760 | ||
PSZ-AC_2:2 | 1.8545 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8545 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.0985 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8238 | 4.8238 | 4.8238 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8545 | 1.8545 | 1.8545 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8238 | 4.8238 | 4.8238 | 4.8238 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8545 | 1.8545 | 1.8545 | 1.8545 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8238 | 4.8238 | 4.8238 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8545 | 1.8545 | 1.8545 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8238 | 4.8238 | 4.8238 | 4.8238 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8545 | 1.8545 | 1.8545 | 1.8545 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 3.83 |
Number of hours not met | 3.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 12.84 | 53618.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 300.57 | 42129.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.92 | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 52.44 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 351.50 | 13107.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.42 | 4742.12 | 286.84 | 21877.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.09 | 1526.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.10 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 525.76 | 1403.05 |
Natural Gas | 469.79 | 769.47 |
Additional | 0.00 | 0.00 |
Total | 995.55 | 2172.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 189.60 |
Space Heating | 0.00 |
Space Cooling | 588.03 |
Fans (All) | 687.65 |
Service Water Heating | 147.54 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2744.87 |
Subtotal | 2744.87 |
Natural Gas [MJ/m2] | |
Space Heating | 25.12 |
Service Water Heating | 561.17 |
Miscellaneous (All) | 1505.36 |
Subtotal | 1505.36 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.46 |
Space Heating | 0.59 |
Space Cooling | 13.84 |
Fans (All) | 16.18 |
Service Water Heating | 16.67 |
Receptacle Equipment | 42.83 |
Miscellaneous | 5.43 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4860. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8303.17 | 456.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7397.83 | 1347.50 | 14.67 | 0.00 | 0.00 |
ATTIC | 5257.17 | 1048.50 | 904.50 | 1259.17 | 290.67 |
Min | 5257.17 | 456.83 | 0.00 | 0.00 | 0.00 |
Max | 8303.17 | 1347.50 | 904.50 | 1259.17 | 290.67 |
Average | 6986.06 | 950.94 | 306.39 | 419.72 | 96.89 |
Sum | 20958.17 | 2852.83 | 919.17 | 1259.17 | 290.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822670.33 | 1551.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822670.33 | 1551.67 | 0.00 | 0.00 | 0.00 |
Average | 280634.44 | 517.22 | 0.00 | 0.00 | 0.00 |
Sum | 841903.33 | 1551.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8236.33 | 523.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6651.50 | 2107.67 | 0.83 | 0.00 | 0.00 |
ATTIC | 5421.83 | 1604.33 | 458.00 | 361.67 | 914.17 |
Min | 5421.83 | 523.67 | 0.00 | 0.00 | 0.00 |
Max | 8236.33 | 2107.67 | 458.00 | 361.67 | 914.17 |
Average | 6769.89 | 1411.89 | 152.94 | 120.56 | 304.72 |
Sum | 20309.67 | 4235.67 | 458.83 | 361.67 | 914.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 812366.33 | 11855.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15818.17 | 3414.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 812366.33 | 11855.67 | 0.00 | 0.00 | 0.00 |
Average | 276061.50 | 5090.17 | 0.00 | 0.00 | 0.00 |
Sum | 828184.50 | 15270.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:35
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272115E+11 | 24924.88 | 27-JAN-14:00 | 27.00 | 9.99 | 0.149564E+11 | 14053.40 | 07-JAN-19:00 | 27.00 | 9.99 |
February | 0.198497E+11 | 18963.83 | 22-FEB-14:00 | 21.00 | 12.01 | 0.134295E+11 | 14050.31 | 25-FEB-19:10 | 14.83 | 9.57 |
March | 0.258436E+11 | 26755.14 | 16-MAR-17:05 | 27.83 | 13.62 | 0.151771E+11 | 14051.51 | 18-MAR-18:49 | 23.67 | 11.80 |
April | 0.363565E+11 | 34360.66 | 14-APR-17:03 | 34.83 | 14.48 | 0.148938E+11 | 14052.62 | 15-APR-18:00 | 25.00 | 13.61 |
May | 0.407657E+11 | 34556.09 | 31-MAY-17:15 | 36.67 | 13.94 | 0.154445E+11 | 14051.40 | 20-MAY-18:00 | 36.67 | 13.94 |
June | 0.468064E+11 | 42093.05 | 30-JUN-04:02 | 27.83 | 15.76 | 0.150417E+11 | 14054.39 | 17-JUN-18:49 | 27.83 | 15.76 |
July | 0.470409E+11 | 54905.25 | 01-JUL-04:01 | 19.00 | 6.82 | 0.153583E+11 | 14053.07 | 22-JUL-18:00 | 36.00 | 20.16 |
August | 0.471573E+11 | 49532.01 | 18-AUG-04:02 | 26.83 | 17.22 | 0.155539E+11 | 14052.50 | 05-AUG-18:19 | 26.83 | 17.22 |
September | 0.434546E+11 | 46177.32 | 01-SEP-04:01 | 24.30 | 19.74 | 0.149309E+11 | 14053.38 | 30-SEP-18:00 | 28.80 | 16.04 |
October | 0.361871E+11 | 42630.42 | 05-OCT-04:01 | 19.83 | 13.81 | 0.152481E+11 | 14051.50 | 21-OCT-18:00 | 22.00 | 14.08 |
November | 0.279257E+11 | 28007.10 | 01-NOV-17:02 | 25.67 | 14.36 | 0.145723E+11 | 14051.39 | 04-NOV-18:19 | 16.33 | 7.56 |
December | 0.246015E+11 | 23712.26 | 22-DEC-13:00 | 24.00 | 9.96 | 0.146005E+11 | 14051.41 | 02-DEC-19:49 | 24.00 | 9.96 |
Annual Sum or Average | 0.423200E+12 | 0.179207E+12 | ||||||||
Minimum of Months | 0.198497E+11 | 18963.83 | 19.00 | 6.82 | 0.134295E+11 | 14050.31 | 14.83 | 7.56 | ||
Maximum of Months | 0.471573E+11 | 54905.25 | 36.67 | 19.74 | 0.155539E+11 | 14054.39 | 36.67 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317251E+11 | 64979.45 | 24-JAN-04:41 | 12.83 | 6.44 | 0.105577E+11 | 6934.93 | 23-JAN-11:00 | 12.83 | 6.44 |
February | 0.287370E+11 | 53981.05 | 17-FEB-04:21 | 11.50 | 11.50 | 0.950863E+10 | 6934.90 | 17-FEB-11:00 | 18.00 | 14.26 |
March | 0.313369E+11 | 59453.44 | 21-MAR-03:31 | 14.40 | 8.65 | 0.105682E+11 | 6934.95 | 03-MAR-11:00 | 14.40 | 8.65 |
April | 0.322492E+11 | 65867.18 | 04-APR-03:41 | 16.00 | 6.41 | 0.102574E+11 | 6934.92 | 07-APR-10:00 | 20.00 | 10.79 |
May | 0.342143E+11 | 65836.71 | 16-MAY-03:21 | 19.50 | 7.15 | 0.106051E+11 | 6934.91 | 26-MAY-10:50 | 27.83 | 12.63 |
June | 0.353635E+11 | 60868.89 | 13-JUN-03:21 | 21.50 | 8.63 | 0.102673E+11 | 6934.92 | 30-JUN-10:09 | 34.33 | 19.17 |
July | 0.369379E+11 | 58790.94 | 02-JUL-03:21 | 19.45 | 6.99 | 0.106032E+11 | 6934.95 | 21-JUL-10:39 | 34.67 | 22.02 |
August | 0.369112E+11 | 62591.41 | 25-AUG-03:21 | 21.50 | 9.58 | 0.106097E+11 | 6934.98 | 03-AUG-10:39 | 21.50 | 9.58 |
September | 0.354065E+11 | 57672.09 | 29-SEP-03:21 | 21.10 | 11.58 | 0.102635E+11 | 6934.95 | 12-SEP-10:50 | 21.10 | 11.58 |
October | 0.342288E+11 | 73048.67 | 31-OCT-04:01 | 10.00 | 4.50 | 0.105885E+11 | 6934.97 | 03-OCT-10:00 | 10.00 | 4.50 |
November | 0.319752E+11 | 65864.46 | 21-NOV-04:21 | 11.00 | 7.38 | 0.102232E+11 | 6934.95 | 14-NOV-11:00 | 11.00 | 7.38 |
December | 0.323461E+11 | 40402.62 | 07-DEC-05:01 | -1.1 | -5.5 | 0.105212E+11 | 6934.90 | 01-DEC-11:09 | -1.1 | -5.5 |
Annual Sum or Average | 0.401432E+12 | 0.124574E+12 | ||||||||
Minimum of Months | 0.287370E+11 | 40402.62 | -1.1 | -5.5 | 0.950863E+10 | 6934.90 | -1.1 | -5.5 | ||
Maximum of Months | 0.369379E+11 | 73048.67 | 21.50 | 11.58 | 0.106097E+11 | 6934.98 | 34.67 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 | 1.81 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 | 11.09 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 | 14.60 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 | 18.35 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 | 16.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 | 15.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 | 10.27 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.00 | 0.00 | 4.27 | 1.81 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.00 | 0.00 | 29.40 | 18.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2035998.23 | 5786.05 | 01-JAN-06:03 | 0.92 |
February | 1444594.97 | 2425.76 | 05-FEB-06:03 | 7.83 |
March | 2382373.57 | 4384.88 | 26-MAR-05:03 | 0.50 |
April | 88324455.99 | 9514.13 | 24-APR-23:02 | 26.83 |
May | 0.274894E+09 | 11330.89 | 07-MAY-23:01 | 28.00 |
June | 0.708882E+09 | 17885.45 | 29-JUN-23:01 | 32.83 |
July | 0.664789E+09 | 17912.13 | 20-JUL-23:01 | 32.83 |
August | 0.593723E+09 | 15268.55 | 13-AUG-23:01 | 31.00 |
September | 0.393756E+09 | 13725.05 | 06-SEP-23:01 | 29.80 |
October | 88005693.59 | 10717.09 | 03-OCT-23:01 | 27.67 |
November | 718243.13 | 2448.20 | 24-NOV-06:03 | 3.17 |
December | 6948292.17 | 5058.45 | 07-DEC-06:03 | -0.7 |
Annual Sum or Average | 0.282590E+10 | |||
Minimum of Months | 718243.13 | 2425.76 | -0.7 | |
Maximum of Months | 0.708882E+09 | 17912.13 | 32.83 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 44237.07 | 442.37 | 17-JUL-04:03 | 27.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 44237.07 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 44237.07 | 442.37 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656587E+10 | 3843.73 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.594703E+10 | 3843.73 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.667042E+10 | 3843.73 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.637984E+10 | 3843.73 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.661815E+10 | 3843.73 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.644748E+10 | 3843.73 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.655127E+10 | 3843.73 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.667042E+10 | 3843.73 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.638137E+10 | 3843.73 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.656511E+10 | 3843.73 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.635601E+10 | 3843.73 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.655204E+10 | 3843.73 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.777050E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.594703E+10 | 3843.73 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.667042E+10 | 3843.73 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162334E+10 | 950.33 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.147034E+10 | 950.33 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.164919E+10 | 950.33 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.157735E+10 | 950.33 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.163627E+10 | 950.33 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.159407E+10 | 950.33 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.161973E+10 | 950.33 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.164919E+10 | 950.33 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.157773E+10 | 950.33 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.162315E+10 | 950.33 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.157145E+10 | 950.33 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.161992E+10 | 950.33 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.192117E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.147034E+10 | 950.33 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.164919E+10 | 950.33 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.656587E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65661510.85 | 0.495068E+10 |
February | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623865E+10 |
March | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172921E+09 | 0.466145E+10 |
April | 0.292871E+11 | 0.637984E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216319E+10 | 0.103428E+10 |
May | 0.303219E+11 | 0.661815E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373084E+10 | 0.389316E+09 |
June | 0.295292E+11 | 0.644748E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646428E+10 | 71176955.62 |
July | 0.300798E+11 | 0.655127E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560358E+10 | 62942153.60 |
August | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525172E+10 | 0.151558E+09 |
September | 0.292871E+11 | 0.638137E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384889E+10 | 0.241552E+09 |
October | 0.300980E+11 | 0.656511E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143664E+10 | 0.234027E+10 |
November | 0.290996E+11 | 0.635601E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122919E+09 | 0.482300E+10 |
December | 0.300798E+11 | 0.655204E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15148176.59 | 0.689232E+10 |
Annual Sum or Average | 0.356244E+12 | 0.777050E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288758E+11 | 0.318572E+11 |
Minimum of Months | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62942153.60 |
Maximum of Months | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646428E+10 | 0.689232E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162334E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 211507.09 | 0.268632E+09 |
February | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198453E+09 |
March | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 735544.79 | 0.289765E+09 |
April | 0.786997E+09 | 0.157735E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 23960425.11 | 0.119860E+09 |
May | 0.814802E+09 | 0.163627E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 52121545.63 | 85108091.71 |
June | 0.793501E+09 | 0.159407E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.107343E+09 | 35123414.73 |
July | 0.808298E+09 | 0.161973E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 92279418.37 | 36689292.39 |
August | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 65528024.96 | 49991596.58 |
September | 0.786997E+09 | 0.157773E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 48895704.83 | 74426371.84 |
October | 0.808786E+09 | 0.162315E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 15921932.50 | 0.163719E+09 |
November | 0.781956E+09 | 0.157145E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 440231.37 | 0.246574E+09 |
December | 0.808298E+09 | 0.161992E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2.93 | 0.244193E+09 |
Annual Sum or Average | 0.957291E+10 | 0.192117E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.407438E+09 | 0.181254E+10 |
Minimum of Months | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35123414.73 |
Maximum of Months | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.107343E+09 | 0.289765E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113303E+10 | 0.289999E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682334E+09 | 0.288180E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679560E+09 | 0.366576E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106519E+10 | 0.500698E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113654E+10 | 0.524954E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950237E+09 | 0.529691E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653011E+09 | 0.482230E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852378E+09 | 0.463270E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672225E+09 | 0.362465E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114988E+10 | 0.326289E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948906E+09 | 0.283724E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134288E+10 | 0.271702E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112662E+11 | 0.468978E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653011E+09 | 0.271702E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134288E+10 | 0.529691E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3843.73 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.26 | 31-JAN-14:00 | 8485.02 | 01-JAN-08:00 |
February | 30255.31 | 04-FEB-19:10 | 3843.73 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9095.18 | 04-FEB-19:55 |
March | 30255.31 | 04-MAR-19:10 | 3843.73 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495.45 | 20-MAR-17:03 | 8320.64 | 26-MAR-06:10 |
April | 30255.31 | 01-APR-18:10 | 3843.73 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5852.83 | 14-APR-17:03 | 4424.55 | 22-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 3843.73 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6933.79 | 31-MAY-17:03 | 3632.98 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 3843.73 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.90 | 28-JUN-17:10 | 1543.22 | 21-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 3843.73 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8298.14 | 22-JUL-18:03 | 2002.56 | 01-JUL-06:05 |
August | 30255.31 | 05-AUG-18:10 | 3843.73 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8983.67 | 25-AUG-17:03 | 4380.93 | 05-AUG-18:10 |
September | 30255.31 | 02-SEP-18:10 | 3843.73 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7077.55 | 07-SEP-17:03 | 2305.12 | 22-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 3843.73 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.37 | 06-OCT-12:00 | 6421.66 | 25-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 3843.73 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.45 | 01-NOV-13:00 | 8931.05 | 23-NOV-20:55 |
December | 30255.31 | 02-DEC-19:10 | 3843.73 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 752.95 | 25-DEC-14:00 | 10240.23 | 05-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.22 | |||||
Maximum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.90 | 10240.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 950.33 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 10.29 | 31-JAN-15:30 | 800.60 | 01-JAN-01:40 |
February | 813.01 | 04-FEB-19:10 | 950.33 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 738.51 | 05-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 950.33 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 18.53 | 15-MAR-15:00 | 873.84 | 28-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 950.33 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 100.89 | 30-APR-15:02 | 410.17 | 27-APR-00:20 |
May | 813.01 | 06-MAY-18:10 | 950.33 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 166.50 | 20-MAY-14:00 | 354.85 | 14-MAY-02:50 |
June | 813.01 | 03-JUN-18:10 | 950.33 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 223.10 | 19-JUN-13:53 | 328.11 | 13-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 950.33 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 216.46 | 22-JUL-15:53 | 431.89 | 27-JUL-00:40 |
August | 813.01 | 05-AUG-18:10 | 950.33 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 170.71 | 13-AUG-15:52 | 494.55 | 19-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 950.33 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 221.35 | 18-SEP-00:20 | 382.67 | 16-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 950.33 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 85.93 | 10-OCT-14:53 | 560.05 | 26-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 950.33 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 16.08 | 01-NOV-15:53 | 945.36 | 29-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 950.33 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25-DEC-15:53 | 652.88 | 17-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 328.11 | ||||||
Maximum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 223.10 | 945.36 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.58 | 18-JAN-07:30 | 5755.35 | 09-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.25 | 02-FEB-05:45 | 7623.77 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.36 | 19-MAR-07:42 | 8147.62 | 26-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.37 | 30-APR-06:00 | 8223.88 | 27-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.49 | 14-MAY-06:32 | 7852.87 | 27-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1597.51 | 20-JUN-05:53 | 7678.13 | 25-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.45 | 03-JUL-05:55 | 7624.74 | 27-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1722.27 | 25-AUG-06:33 | 7488.20 | 07-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.92 | 17-SEP-04:53 | 7117.36 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.50 | 26-OCT-07:13 | 6275.27 | 04-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.63 | 19-NOV-03:00 | 6316.04 | 14-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.36 | 21-DEC-07:25 | 5380.72 | 14-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.36 | 5380.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2137.36 | 8223.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24924.88 | 27-JAN-14:00 | 47063.81 | 7687.45 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.80 | 0.00 |
February | 18963.83 | 22-FEB-14:00 | 23531.91 | 3843.73 | 6034.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.00 |
March | 26755.14 | 16-MAR-17:05 | 107574.42 | 15374.90 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2109.48 | 0.00 |
April | 34360.66 | 14-APR-17:03 | 107574.42 | 15374.90 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5852.83 | 0.00 |
May | 34556.09 | 31-MAY-17:15 | 107574.42 | 15374.90 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6856.61 | 0.00 |
June | 42093.05 | 30-JUN-04:02 | 8404.25 | 4270.93 | 14482.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 0.00 |
July | 54905.25 | 01-JUL-04:01 | 0.00 | 5765.65 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
August | 49532.01 | 18-AUG-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
September | 46177.32 | 01-SEP-04:01 | 11765.95 | 5979.30 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
October | 42630.42 | 05-OCT-04:01 | 13446.80 | 6833.49 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.68 |
November | 28007.10 | 01-NOV-17:02 | 134468.03 | 19218.63 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 942.99 | 0.00 |
December | 23712.26 | 22-DEC-13:00 | 53787.21 | 7687.45 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18963.83 | 0.00 | 3843.73 | 6034.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54905.25 | 134468.03 | 19218.63 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6856.61 | 1549.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64979.45 | 24-JAN-04:41 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 439.71 |
February | 53981.05 | 17-FEB-04:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 27.75 |
March | 59453.44 | 21-MAR-03:31 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 266.95 |
April | 65867.18 | 04-APR-03:41 | 0.00 | 1425.45 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 98.57 |
May | 65836.71 | 16-MAY-03:21 | 0.00 | 1583.83 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 147.73 |
June | 60868.89 | 13-JUN-03:21 | 0.00 | 1425.45 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 |
July | 58790.94 | 02-JUL-03:21 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 138.55 |
August | 62591.41 | 25-AUG-03:21 | 0.00 | 1583.83 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 170.92 |
September | 57672.09 | 29-SEP-03:21 | 0.00 | 1425.45 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 227.07 |
October | 73048.67 | 31-OCT-04:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 |
November | 65864.46 | 21-NOV-04:21 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 506.40 |
December | 40402.62 | 07-DEC-05:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 140.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40402.62 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 27.75 | |
Maximum of Months | 73048.67 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 506.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.36 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.23 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.22 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.08 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.16 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.11 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.80 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.22 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.17 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.24 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1359.57 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1359.57 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.100139E+12 | 63001.85 | 31-JAN-18:19 | 0.696388E+11 | 70819.12 | 01-JAN-07:49 |
February | 0.849757E+11 | 54655.96 | 18-FEB-11:00 | 0.627034E+11 | 50200.19 | 08-FEB-06:10 |
March | 0.100368E+12 | 65449.47 | 17-MAR-10:00 | 0.689666E+11 | 73930.94 | 26-MAR-05:10 |
April | 0.116044E+12 | 74364.75 | 14-APR-17:19 | 0.627265E+11 | 43172.37 | 01-APR-10:20 |
May | 0.127809E+12 | 77357.21 | 31-MAY-17:19 | 0.628675E+11 | 42805.86 | 06-MAY-10:39 |
June | 0.139044E+12 | 86999.26 | 28-JUN-17:19 | 0.593292E+11 | 42542.03 | 03-JUN-10:20 |
July | 0.145963E+12 | 84823.56 | 19-JUL-11:00 | 0.603091E+11 | 42389.98 | 01-JUL-10:20 |
August | 0.145074E+12 | 85035.72 | 25-AUG-17:19 | 0.607667E+11 | 42431.46 | 26-AUG-10:09 |
September | 0.134366E+12 | 81756.86 | 01-SEP-11:00 | 0.598526E+11 | 42683.13 | 30-SEP-10:09 |
October | 0.115294E+12 | 77213.32 | 02-OCT-10:00 | 0.637155E+11 | 42977.30 | 29-OCT-10:00 |
November | 0.976075E+11 | 67828.29 | 01-NOV-10:00 | 0.646730E+11 | 64953.26 | 23-NOV-06:49 |
December | 0.963669E+11 | 61490.38 | 22-DEC-11:00 | 0.739220E+11 | 80296.00 | 07-DEC-06:10 |
Annual Sum or Average | 0.140305E+13 | 0.769471E+12 | ||||
Minimum of Months | 0.849757E+11 | 54655.96 | 0.593292E+11 | 42389.98 | ||
Maximum of Months | 0.145963E+12 | 86999.26 | 0.739220E+11 | 80296.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.818922E+10 | 0.513557E+10 | 0.391293E+11 | 0.00 | 0.294825E+11 | 37879553.69 | 0.00 | 0.638189E+10 | 0.00 | 0.00 | 0.00 | 0.638509E+10 | 0.00 |
February | 0.741737E+10 | 0.440534E+10 | 0.353426E+11 | 0.00 | 0.265846E+11 | 34213790.43 | 0.00 | 0.552177E+09 | 0.00 | 0.00 | 0.00 | 0.578077E+10 | 0.00 |
March | 0.831961E+10 | 0.452938E+10 | 0.391293E+11 | 0.00 | 0.295611E+11 | 37879553.69 | 0.00 | 0.689465E+10 | 0.00 | 0.00 | 0.00 | 0.645318E+10 | 0.00 |
April | 0.795718E+10 | 0.402723E+10 | 0.378671E+11 | 0.00 | 0.290528E+11 | 36657632.61 | 0.00 | 0.255332E+11 | 0.00 | 0.00 | 0.00 | 0.619345E+10 | 0.00 |
May | 0.825441E+10 | 0.385518E+10 | 0.391293E+11 | 0.00 | 0.300958E+11 | 37879553.69 | 0.00 | 0.344388E+11 | 0.00 | 0.00 | 0.00 | 0.641454E+10 | 0.00 |
June | 0.804156E+10 | 0.360310E+10 | 0.378671E+11 | 0.00 | 0.291671E+11 | 36657632.61 | 0.00 | 0.486593E+11 | 0.00 | 0.00 | 0.00 | 0.623579E+10 | 0.00 |
July | 0.817100E+10 | 0.377115E+10 | 0.391293E+11 | 0.00 | 0.301547E+11 | 37879553.69 | 0.00 | 0.526679E+11 | 0.00 | 0.00 | 0.00 | 0.637119E+10 | 0.00 |
August | 0.831961E+10 | 0.402323E+10 | 0.391293E+11 | 0.00 | 0.301537E+11 | 37879553.69 | 0.00 | 0.512772E+11 | 0.00 | 0.00 | 0.00 | 0.644931E+10 | 0.00 |
September | 0.795910E+10 | 0.422529E+10 | 0.378671E+11 | 0.00 | 0.291903E+11 | 36657632.61 | 0.00 | 0.433920E+11 | 0.00 | 0.00 | 0.00 | 0.619380E+10 | 0.00 |
October | 0.818826E+10 | 0.473744E+10 | 0.391293E+11 | 0.00 | 0.299588E+11 | 37879553.69 | 0.00 | 0.213111E+11 | 0.00 | 0.00 | 0.00 | 0.637966E+10 | 0.00 |
November | 0.792746E+10 | 0.489549E+10 | 0.378671E+11 | 0.00 | 0.286986E+11 | 36657632.61 | 0.00 | 0.672643E+10 | 0.00 | 0.00 | 0.00 | 0.617842E+10 | 0.00 |
December | 0.817196E+10 | 0.523360E+10 | 0.391293E+11 | 0.00 | 0.293967E+11 | 37879553.69 | 0.00 | 0.273949E+10 | 0.00 | 0.00 | 0.00 | 0.637987E+10 | 0.00 |
Annual Sum or Average | 0.969167E+11 | 0.524420E+11 | 0.460716E+12 | 0.00 | 0.351497E+12 | 0.446001E+09 | 0.00 | 0.300574E+12 | 0.00 | 0.00 | 0.00 | 0.754151E+11 | 0.00 |
Minimum of Months | 0.741737E+10 | 0.360310E+10 | 0.353426E+11 | 0.00 | 0.265846E+11 | 34213790.43 | 0.00 | 0.552177E+09 | 0.00 | 0.00 | 0.00 | 0.578077E+10 | 0.00 |
Maximum of Months | 0.831961E+10 | 0.523360E+10 | 0.391293E+11 | 0.00 | 0.301547E+11 | 37879553.69 | 0.00 | 0.526679E+11 | 0.00 | 0.00 | 0.00 | 0.645318E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.158061E+10 | 0.00 | 0.281584E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.138047E+10 | 0.00 | 0.252845E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.207877E+10 | 0.00 | 0.269882E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.241138E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.229677E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.207166E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.204094E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.208670E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.212399E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 60999932.19 | 0.00 | 0.237548E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.110738E+10 | 0.00 | 0.249530E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.663202E+10 | 0.00 | 0.273903E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.128403E+11 | 0.00 | 0.286844E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.204094E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.663202E+10 | 0.00 | 0.281584E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4794.05 | 02-JAN-10:09 | 3334.35 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13107.32 | 01-JAN-17:40 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4794.05 | 01-FEB-10:09 | 3334.35 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13107.32 | 01-FEB-05:10 | 17.86 | 23-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 4794.05 | 01-MAR-10:09 | 3334.35 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13107.32 | 01-MAR-05:10 | 17.86 | 07-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 4794.05 | 01-APR-16:10 | 3334.35 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13107.32 | 01-APR-04:10 | 17.86 | 22-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 4794.05 | 01-MAY-09:09 | 3334.35 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13107.32 | 01-MAY-04:10 | 17.86 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 4794.05 | 01-JUN-09:09 | 3334.35 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13107.32 | 01-JUN-23:10 | 17.86 | 27-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 4794.05 | 01-JUL-16:10 | 3334.35 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13107.32 | 01-JUL-23:10 | 17.86 | 07-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 4794.05 | 01-AUG-09:09 | 3334.35 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13107.32 | 03-AUG-23:19 | 17.86 | 02-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 4794.05 | 01-SEP-09:09 | 3334.35 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13107.32 | 04-SEP-23:10 | 17.86 | 13-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 4794.05 | 02-OCT-09:09 | 3334.35 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13107.32 | 02-OCT-14:39 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 4794.05 | 01-NOV-09:09 | 3334.35 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13107.32 | 02-NOV-04:10 | 17.86 | 07-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 4794.05 | 01-DEC-10:09 | 3334.35 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13107.32 | 01-DEC-05:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 13107.32 | 17.86 | 0.00 | ||||||
Maximum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 13107.32 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 17552.66 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.68 | 23-JAN-07:10 | 0.00 |
February | 9925.20 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4742.12 | 09-FEB-07:40 | 0.00 |
March | 18883.84 | 20-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4741.31 | 07-MAR-07:49 | 0.00 |
April | 29417.36 | 14-APR-17:10 | 0.00 | 0.00 | 0.00 | 4740.45 | 21-APR-06:19 | 0.00 |
May | 32433.68 | 31-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4738.48 | 01-MAY-06:19 | 0.00 |
June | 42129.39 | 28-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.70 | 23-JUN-18:30 | 0.00 |
July | 40137.76 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.73 | 07-JUL-06:19 | 0.00 |
August | 40475.15 | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.66 | 29-AUG-18:30 | 0.00 |
September | 35632.41 | 01-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.71 | 26-SEP-18:30 | 0.00 |
October | 31241.20 | 01-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4741.22 | 12-OCT-06:19 | 0.00 |
November | 21687.86 | 01-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4740.50 | 08-NOV-07:00 | 0.00 |
December | 14803.51 | 22-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4741.61 | 05-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9925.20 | 0.00 | 0.00 | 0.00 | 4736.66 | 0.00 | ||
Maximum of Months | 42129.39 | 0.00 | 0.00 | 0.00 | 4742.12 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63001.85 | 31-JAN-18:19 | 4794.05 | 20676.91 | 3334.35 | 0.00 | 13107.32 | 17.86 | 0.00 | 14749.72 | 0.00 |
February | 54655.96 | 18-FEB-11:00 | 4261.38 | 24699.69 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 6072.06 | 0.00 |
March | 65449.47 | 17-MAR-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 16281.36 | 0.00 |
April | 74364.75 | 14-APR-17:19 | 4794.05 | 20676.91 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 29307.44 | 0.00 |
May | 77357.21 | 31-MAY-17:19 | 4794.05 | 20676.91 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 32308.06 | 0.00 |
June | 86999.26 | 28-JUN-17:19 | 4794.05 | 20676.91 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 41908.53 | 0.00 |
July | 84823.56 | 19-JUL-11:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 38696.87 | 0.00 |
August | 85035.72 | 25-AUG-17:19 | 4794.05 | 20676.91 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 39982.86 | 0.00 |
September | 81756.86 | 01-SEP-11:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 35632.41 | 0.00 |
October | 77213.32 | 02-OCT-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 28288.44 | 0.00 |
November | 67828.29 | 01-NOV-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 18641.35 | 0.00 |
December | 61490.38 | 22-DEC-11:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 12762.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 54655.96 | 4261.38 | 20676.91 | 0.00 | 0.00 | 13107.32 | 17.86 | 0.00 | 6072.06 | 0.00 | |
Maximum of Months | 86999.26 | 4794.05 | 24699.69 | 3334.35 | 0.00 | 13107.32 | 17.86 | 0.00 | 41908.53 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 48580.61 | 01-JAN-06:10 | 0.00 | 21877.50 | 30-JAN-07:49 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 23966.28 | 09-FEB-06:10 | 0.00 | 21642.56 | 08-FEB-07:30 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 47429.65 | 26-MAR-05:10 | 0.00 | 19934.13 | 03-MAR-19:40 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 17633.22 | 03-APR-18:49 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 17252.59 | 01-MAY-06:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16872.24 | 01-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16624.06 | 03-JUL-06:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16727.67 | 31-AUG-18:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 17010.45 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 10054.21 | 25-OCT-05:00 | 0.00 | 17423.14 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 41073.56 | 23-NOV-06:10 | 0.00 | 17835.67 | 30-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 53618.67 | 07-DEC-06:10 | 0.00 | 20888.41 | 29-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16624.06 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 53618.67 | 0.00 | 21877.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 30.28 | 0.00 | 30.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 30.27 | 0.00 | 30.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 30.57 | 0.00 | 30.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 31.22 | 0.00 | 31.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 31.42 | 0.00 | 31.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 30.86 | 3.83 | 30.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 31.41 | 0.00 | 31.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 31.43 | 0.00 | 31.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 31.64 | 0.00 | 31.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 31.30 | 0.00 | 31.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 30.85 | 0.00 | 30.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 30.10 | 0.00 | 30.10 |
Annual Sum or Average | 0.00 | 0.00 | 224.67 | 31.20 | 3.83 | 31.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 30.10 | 0.00 | 30.10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 31.64 | 3.83 | 31.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.67 | 22.25 | 152.17 | 22.96 | 8.33 | 22.95 |
February | 204.50 | 22.08 | 213.50 | 23.04 | 11.17 | 23.07 |
March | 183.83 | 22.22 | 233.50 | 23.21 | 1.00 | 23.20 |
April | 30.17 | 23.42 | 356.67 | 24.13 | 0.33 | 24.13 |
May | 6.33 | 24.98 | 420.00 | 24.29 | 1.50 | 24.31 |
June | 22.00 | 29.49 | 551.33 | 24.53 | 22.00 | 24.72 |
July | 67.17 | 26.07 | 585.00 | 24.49 | 67.17 | 24.64 |
August | 74.50 | 25.76 | 602.33 | 24.46 | 74.50 | 24.59 |
September | 79.83 | 25.30 | 589.83 | 24.38 | 79.83 | 24.48 |
October | 61.17 | 23.05 | 398.17 | 24.00 | 8.17 | 24.04 |
November | 185.17 | 22.75 | 271.00 | 23.49 | 54.00 | 23.54 |
December | 309.50 | 22.03 | 56.33 | 22.17 | 13.17 | 22.08 |
Annual Sum or Average | 1431.83 | 22.95 | 4429.83 | 23.89 | 341.17 | 23.97 |
Minimum of Months | 6.33 | 22.03 | 56.33 | 22.17 | 0.33 | 22.08 |
Maximum of Months | 309.50 | 29.49 | 602.33 | 24.53 | 79.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.00 | 23.31 | 395.67 | 24.37 | 218.83 | 24.67 |
February | 281.83 | 22.00 | 328.50 | 23.40 | 97.83 | 23.71 |
March | 396.50 | 23.77 | 434.83 | 24.61 | 251.00 | 24.90 |
April | 424.17 | 25.90 | 562.00 | 25.86 | 414.17 | 25.90 |
May | 475.50 | 26.03 | 607.67 | 25.99 | 475.50 | 26.00 |
June | 564.00 | 26.07 | 592.00 | 26.07 | 564.00 | 26.07 |
July | 593.33 | 26.06 | 609.00 | 26.06 | 593.33 | 26.06 |
August | 606.83 | 26.07 | 612.00 | 26.07 | 606.83 | 26.07 |
September | 589.50 | 26.06 | 590.00 | 26.06 | 589.50 | 26.06 |
October | 473.83 | 25.48 | 548.00 | 25.61 | 427.50 | 25.73 |
November | 408.17 | 24.13 | 434.83 | 24.79 | 286.50 | 25.03 |
December | 364.17 | 21.52 | 328.17 | 22.99 | 133.17 | 23.16 |
Annual Sum or Average | 5573.83 | 25.00 | 6042.67 | 25.36 | 4658.17 | 25.53 |
Minimum of Months | 281.83 | 21.52 | 328.17 | 22.99 | 97.83 | 23.16 |
Maximum of Months | 606.83 | 26.07 | 612.00 | 26.07 | 606.83 | 26.07 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.39217 | 26.25746 | 0.24636 | 7.64035 |
February | 551.00000 | 23.23862 | 40.17700 | 0.26349 | 7.86268 |
March | 612.00000 | 23.45984 | 30.62845 | 0.27122 | 7.93636 |
April | 590.00000 | 24.09641 | 21.82274 | 0.44072 | 9.42854 |
May | 611.00000 | 24.20746 | 20.67224 | -0.3331 | 7.82544 |
June | 592.00000 | 24.31211 | 28.01889 | -0.1871 | 6.70004 |
July | 609.00000 | 24.29732 | 44.39531 | -0.0745 | 6.23107 |
August | 612.00000 | 24.29129 | 46.44151 | -0.0581 | 6.00195 |
September | 590.00000 | 24.25408 | 46.76226 | -0.0765 | 5.88029 |
October | 610.00000 | 23.96123 | 29.86214 | 0.47158 | 10.54850 |
November | 591.00000 | 23.60192 | 31.21807 | 0.35299 | 9.06974 |
December | 609.00000 | 22.98707 | 20.02619 | 0.09720 | 7.28558 |
Annual Sum or Average | 7187.00000 | 23.84430 | 32.12786 | 0.11640 | 7.69857 |
Minimum of Months | 551.00000 | 22.98707 | 20.02619 | -0.3331 | 5.88029 |
Maximum of Months | 612.00000 | 24.31211 | 46.76226 | 0.47158 | 10.54850 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.76904 | 29.54719 | 0.54595 | 17.68778 |
February | 551.00000 | 22.91214 | 43.67203 | 0.43012 | 14.50918 |
March | 612.00000 | 24.00576 | 33.20346 | 0.62045 | 19.19191 |
April | 590.00000 | 25.65828 | 23.23512 | 0.98994 | 26.99639 |
May | 611.00000 | 25.94327 | 21.65421 | 0.49912 | 11.13038 |
June | 592.00000 | 26.07018 | 27.93744 | 0.64801 | 14.36356 |
July | 609.00000 | 26.06037 | 43.63540 | 0.77559 | 18.26203 |
August | 612.00000 | 26.07189 | 45.44647 | 0.79023 | 18.69610 |
September | 590.00000 | 26.05564 | 45.02979 | 0.77895 | 18.27894 |
October | 610.00000 | 25.25660 | 30.89054 | 0.96917 | 28.04057 |
November | 591.00000 | 24.19197 | 33.10781 | 0.70497 | 21.78535 |
December | 609.00000 | 22.73678 | 24.08215 | 0.27637 | 14.27578 |
Annual Sum or Average | 7187.00000 | 24.90452 | 33.38204 | 0.66983 | 18.61463 |
Minimum of Months | 551.00000 | 22.73678 | 21.65421 | 0.27637 | 11.13038 |
Maximum of Months | 612.00000 | 26.07189 | 45.44647 | 0.98994 | 28.04057 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.140662E+11 | 0.458170E+10 | 239.75 | 0.139953E+11 | 70930832.06 | 0.00 | 0.46 | 31-JAN-14:00 | 0.00 | 01-JAN-00:03 | 39232.99 | 31-JAN-14:00 | 39232.99 | 31-JAN-14:00 | 3383.50 | 08-JAN-13:50 | 12187.57 | 31-JAN-14:00 | 0.00 | 01-JAN-00:03 |
February | 0.121261E+10 | 0.408583E+09 | 49.08 | 0.106971E+10 | 0.142898E+09 | 0.00 | 0.26 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 | 20946.00 | 18-FEB-13:53 | 17127.17 | 18-FEB-13:57 | 3819.36 | 18-FEB-13:53 | 6845.24 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 |
March | 0.147693E+11 | 0.478289E+10 | 241.17 | 0.144156E+11 | 0.353779E+09 | 0.00 | 0.49 | 20-MAR-17:10 | 0.00 | 01-MAR-00:03 | 41628.81 | 20-MAR-17:10 | 41562.17 | 20-MAR-17:03 | 4783.74 | 17-MAR-11:10 | 12848.59 | 20-MAR-17:10 | 0.00 | 01-MAR-00:03 |
April | 0.529114E+11 | 0.168915E+11 | 461.66 | 0.528144E+11 | 96978234.82 | 0.00 | 0.68 | 14-APR-17:03 | 0.00 | 01-APR-00:01 | 59175.94 | 14-APR-17:03 | 59175.94 | 14-APR-17:03 | 2869.63 | 15-APR-19:00 | 19504.95 | 14-APR-17:03 | 0.00 | 01-APR-00:01 |
May | 0.690379E+11 | 0.223034E+11 | 527.70 | 0.690344E+11 | 3487274.94 | 0.00 | 0.72 | 31-MAY-17:03 | 0.00 | 01-MAY-00:01 | 62246.96 | 31-MAY-17:03 | 62246.96 | 31-MAY-17:03 | 1560.63 | 26-MAY-05:03 | 21272.61 | 31-MAY-17:03 | 0.00 | 01-MAY-00:01 |
June | 0.904741E+11 | 0.306914E+11 | 563.75 | 0.899359E+11 | 0.538214E+09 | 0.00 | 0.86 | 28-JUN-17:07 | 0.00 | 01-JUN-00:01 | 77285.09 | 17-JUN-18:10 | 74828.15 | 28-JUN-17:07 | 11862.19 | 17-JUN-17:10 | 27862.60 | 28-JUN-17:07 | 0.00 | 01-JUN-00:01 |
July | 0.104276E+12 | 0.335040E+11 | 589.88 | 0.887895E+11 | 0.154868E+11 | 0.00 | 0.87 | 17-JUL-04:02 | 0.00 | 01-JUL-00:01 | 89035.36 | 23-JUL-04:02 | 69253.15 | 20-JUL-17:30 | 46414.26 | 14-JUL-05:03 | 27242.46 | 19-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.102091E+12 | 0.328362E+11 | 590.58 | 0.864109E+11 | 0.156803E+11 | 0.00 | 0.84 | 18-AUG-11:30 | 0.00 | 01-AUG-00:01 | 79332.81 | 18-AUG-11:30 | 72703.20 | 25-AUG-17:08 | 34389.86 | 01-AUG-05:03 | 26456.76 | 25-AUG-17:08 | 0.00 | 01-AUG-00:01 |
September | 0.892367E+11 | 0.280123E+11 | 555.07 | 0.741977E+11 | 0.150390E+11 | 0.00 | 0.84 | 01-SEP-12:00 | 0.00 | 01-SEP-00:01 | 82852.45 | 02-SEP-04:02 | 65698.07 | 07-SEP-17:02 | 37361.85 | 04-SEP-05:03 | 24170.41 | 08-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.445148E+11 | 0.141710E+11 | 410.82 | 0.414059E+11 | 0.310890E+10 | 0.00 | 0.76 | 03-OCT-12:00 | 0.00 | 01-OCT-00:01 | 70600.90 | 03-OCT-12:00 | 58560.68 | 06-OCT-13:00 | 30749.63 | 03-OCT-04:02 | 21034.39 | 02-OCT-11:53 | 0.00 | 01-OCT-00:01 |
November | 0.145147E+11 | 0.467350E+10 | 222.20 | 0.135251E+11 | 0.989548E+09 | 0.00 | 0.57 | 01-NOV-12:55 | 0.00 | 01-NOV-00:01 | 49227.77 | 01-NOV-12:55 | 42429.71 | 01-NOV-13:00 | 11665.35 | 12-NOV-12:55 | 14890.04 | 01-NOV-12:55 | 0.00 | 01-NOV-00:01 |
December | 0.607455E+10 | 0.199707E+10 | 131.67 | 0.606656E+10 | 7992249.44 | 0.00 | 0.41 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 | 33914.10 | 22-DEC-14:00 | 33914.10 | 22-DEC-14:00 | 1193.34 | 12-DEC-13:00 | 10688.99 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.603180E+12 | 0.194854E+12 | 4583.33 | 0.551661E+12 | 0.515189E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.121261E+10 | 0.408583E+09 | 49.08 | 0.106971E+10 | 3487274.94 | 0.00 | 0.26 | 0.00 | 20946.00 | 17127.17 | 1193.34 | 6845.24 | 0.00 | |||||||
Maximum of Months | 0.104276E+12 | 0.335040E+11 | 590.58 | 0.899359E+11 | 0.156803E+11 | 0.00 | 0.87 | 0.00 | 89035.36 | 74828.15 | 46414.26 | 27862.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.608478E+10 | 0.180019E+10 | 214.54 | 0.598828E+10 | 96496690.66 | 0.00 | 1.00 | 24-JAN-04:41 | 0.00 | 01-JAN-00:03 | 45432.37 | 24-JAN-04:41 | 38080.13 | 24-JAN-04:41 | 9525.92 | 08-JAN-05:01 | 11086.71 | 24-JAN-04:41 | 0.00 | 01-JAN-00:03 |
February | 0.470732E+09 | 0.143594E+09 | 37.93 | 0.372676E+09 | 98056352.20 | 0.00 | 1.00 | 17-FEB-04:21 | 0.00 | 01-FEB-00:03 | 45432.37 | 17-FEB-04:21 | 21029.11 | 17-FEB-04:21 | 24403.26 | 17-FEB-04:21 | 11086.71 | 17-FEB-04:21 | 0.00 | 01-FEB-00:03 |
March | 0.724981E+10 | 0.211177E+10 | 224.39 | 0.692868E+10 | 0.321129E+09 | 0.00 | 1.00 | 17-MAR-03:11 | 0.00 | 01-MAR-00:03 | 45432.37 | 17-MAR-03:11 | 35030.76 | 21-MAR-03:31 | 13648.37 | 17-MAR-03:51 | 11086.71 | 17-MAR-03:11 | 0.00 | 01-MAR-00:03 |
April | 0.305936E+11 | 0.864173E+10 | 464.44 | 0.304698E+11 | 0.123776E+09 | 0.00 | 1.00 | 04-APR-03:41 | 0.00 | 01-APR-00:01 | 45432.37 | 30-APR-02:62 | 45432.37 | 14-APR-03:31 | 9423.17 | 07-APR-03:31 | 11086.71 | 04-APR-03:41 | 0.00 | 01-APR-00:01 |
May | 0.428343E+11 | 0.121354E+11 | 551.04 | 0.427985E+11 | 35883606.96 | 0.00 | 1.00 | 02-MAY-03:31 | 0.00 | 01-MAY-00:01 | 45432.37 | 08-MAY-01:22 | 45432.37 | 02-MAY-03:31 | 9381.73 | 26-MAY-03:21 | 11345.20 | 15-MAY-17:00 | 0.00 | 01-MAY-00:01 |
June | 0.615906E+11 | 0.179679E+11 | 604.70 | 0.613657E+11 | 0.224932E+09 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 45978.53 | 17-JUN-16:00 | 45432.37 | 08-JUN-00:20 | 6615.28 | 30-JUN-07:50 | 14365.90 | 16-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.700247E+11 | 0.191639E+11 | 639.87 | 0.600756E+11 | 0.994910E+10 | 0.00 | 1.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:01 | 50278.01 | 14-JUL-03:21 | 45432.37 | 02-JUL-03:21 | 30632.14 | 14-JUL-02:42 | 13116.36 | 12-JUL-13:52 | 0.00 | 01-JUL-00:01 |
August | 0.671193E+11 | 0.184410E+11 | 638.65 | 0.573640E+11 | 0.975527E+10 | 0.00 | 1.00 | 01-AUG-00:12 | 0.00 | 01-AUG-00:01 | 49554.02 | 01-AUG-03:01 | 45432.37 | 25-AUG-00:42 | 25889.04 | 20-AUG-00:42 | 14139.17 | 25-AUG-15:23 | 0.00 | 01-AUG-00:01 |
September | 0.568275E+11 | 0.153797E+11 | 592.64 | 0.470544E+11 | 0.977309E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 49643.69 | 02-SEP-00:11 | 45432.37 | 18-SEP-02:10 | 31044.95 | 04-SEP-03:21 | 12158.78 | 08-SEP-16:00 | 0.00 | 01-SEP-00:01 |
October | 0.255258E+11 | 0.714013E+10 | 408.51 | 0.234053E+11 | 0.212045E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:01 | 48440.26 | 03-OCT-02:62 | 45432.37 | 17-OCT-02:62 | 25778.30 | 03-OCT-03:21 | 11290.97 | 03-OCT-02:62 | 0.00 | 01-OCT-00:01 |
November | 0.707737E+10 | 0.205293E+10 | 207.53 | 0.636696E+10 | 0.710408E+09 | 0.00 | 1.00 | 01-NOV-03:32 | 0.00 | 01-NOV-00:01 | 45432.37 | 03-NOV-03:31 | 31629.92 | 21-NOV-04:21 | 26343.56 | 14-NOV-04:21 | 11086.71 | 01-NOV-03:32 | 0.00 | 01-NOV-00:01 |
December | 0.248450E+10 | 0.742425E+09 | 118.88 | 0.246698E+10 | 17524066.77 | 0.00 | 0.41 | 22-DEC-14:55 | 0.00 | 01-DEC-00:05 | 15826.07 | 22-DEC-14:55 | 15826.07 | 22-DEC-14:55 | 5706.06 | 13-DEC-05:01 | 4539.40 | 22-DEC-14:55 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.377883E+12 | 0.105721E+12 | 4703.12 | 0.344657E+12 | 0.332261E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.470732E+09 | 0.143594E+09 | 37.93 | 0.372676E+09 | 17524066.77 | 0.00 | 0.41 | 0.00 | 15826.07 | 15826.07 | 5706.06 | 4539.40 | 0.00 | |||||||
Maximum of Months | 0.700247E+11 | 0.191639E+11 | 639.87 | 0.613657E+11 | 0.994910E+10 | 0.00 | 1.00 | 0.00 | 50278.01 | 45432.37 | 31044.95 | 14365.90 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 196.32 | 123.22 | 73.10 | 254.26 | 268.51 | 0.00 | 0.00 | 0.00 |
February | 195.15 | 112.28 | 82.87 | 226.49 | 270.30 | 0.00 | 0.00 | 0.00 |
March | 242.32 | 124.67 | 117.65 | 322.50 | 229.27 | 0.00 | 0.00 | 0.00 |
April | 345.32 | 205.75 | 139.57 | 591.05 | 129.17 | 0.00 | 0.00 | 0.00 |
May | 358.48 | 212.71 | 145.77 | 659.83 | 91.67 | 0.00 | 0.00 | 0.00 |
June | 372.98 | 231.72 | 141.26 | 794.42 | 43.85 | 0.00 | 0.00 | 0.00 |
July | 315.49 | 178.01 | 137.47 | 678.07 | 34.36 | 0.00 | 0.00 | 0.00 |
August | 299.68 | 171.22 | 128.46 | 634.30 | 45.45 | 0.00 | 0.00 | 0.00 |
September | 245.58 | 118.44 | 127.13 | 499.08 | 61.35 | 0.00 | 0.00 | 0.00 |
October | 246.44 | 149.91 | 96.54 | 395.41 | 173.44 | 0.00 | 0.00 | 0.00 |
November | 189.64 | 113.81 | 75.84 | 240.88 | 254.34 | 0.00 | 0.00 | 0.00 |
December | 173.23 | 104.77 | 68.46 | 197.37 | 322.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 265.37 | 154.07 | 111.30 | 458.90 | 159.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.23 | 104.77 | 68.46 | 197.37 | 34.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 372.98 | 231.72 | 145.77 | 794.42 | 322.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 693.33 | 553.89 | 139.44 | 1083.75 | 368.25 | 0.00 | 0.00 | 0.00 |
February | 432.62 | 290.03 | 142.59 | 604.22 | 368.77 | 0.00 | 0.00 | 0.00 |
March | 358.14 | 181.48 | 176.66 | 535.34 | 331.81 | 0.00 | 0.00 | 0.00 |
April | 314.33 | 129.48 | 184.85 | 606.61 | 197.66 | 0.00 | 0.00 | 0.00 |
May | 210.03 | 36.54 | 173.49 | 449.05 | 142.31 | 0.00 | 0.00 | 0.00 |
June | 177.78 | 13.56 | 164.21 | 511.60 | 67.18 | 0.00 | 0.00 | 0.00 |
July | 180.15 | 17.13 | 163.02 | 497.28 | 51.33 | 0.00 | 0.00 | 0.00 |
August | 222.76 | 62.74 | 160.02 | 577.25 | 66.08 | 0.00 | 0.00 | 0.00 |
September | 316.42 | 133.74 | 182.69 | 691.06 | 88.84 | 0.00 | 0.00 | 0.00 |
October | 507.91 | 351.61 | 156.30 | 871.45 | 242.29 | 0.00 | 0.00 | 0.00 |
November | 597.03 | 458.55 | 138.49 | 917.28 | 345.56 | 0.00 | 0.00 | 0.00 |
December | 645.68 | 511.55 | 134.13 | 965.21 | 436.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 388.05 | 228.34 | 159.71 | 693.35 | 224.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 177.78 | 13.56 | 134.13 | 449.05 | 51.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 693.33 | 553.89 | 184.85 | 1083.75 | 436.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.14 | 128.43 | 77.71 | 297.01 | 293.37 | 0.00 | 0.00 | 0.00 |
February | 166.97 | 81.04 | 85.94 | 192.07 | 286.22 | 0.00 | 0.00 | 0.00 |
March | 220.95 | 105.68 | 115.28 | 299.43 | 244.36 | 0.00 | 0.00 | 0.00 |
April | 338.38 | 193.13 | 145.25 | 589.49 | 142.58 | 0.00 | 0.00 | 0.00 |
May | 339.60 | 190.31 | 149.29 | 633.99 | 102.74 | 0.00 | 0.00 | 0.00 |
June | 360.00 | 211.69 | 148.31 | 768.31 | 48.20 | 0.00 | 0.00 | 0.00 |
July | 261.87 | 122.03 | 139.84 | 580.05 | 36.80 | 0.00 | 0.00 | 0.00 |
August | 250.68 | 126.05 | 124.62 | 547.63 | 47.09 | 0.00 | 0.00 | 0.00 |
September | 218.15 | 91.72 | 126.42 | 453.56 | 64.33 | 0.00 | 0.00 | 0.00 |
October | 224.12 | 128.52 | 95.59 | 368.88 | 186.80 | 0.00 | 0.00 | 0.00 |
November | 205.15 | 123.78 | 81.37 | 289.19 | 273.18 | 0.00 | 0.00 | 0.00 |
December | 164.60 | 93.32 | 71.28 | 209.52 | 349.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.66 | 133.16 | 113.50 | 436.78 | 172.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.60 | 81.04 | 71.28 | 192.07 | 36.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.00 | 211.69 | 149.29 | 768.31 | 349.92 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.525815E+09 | 0.330026E+09 | 0.195789E+09 | 0.681020E+09 | 0.719169E+09 |
February | 0.472106E+09 | 0.271630E+09 | 0.200476E+09 | 0.547922E+09 | 0.653910E+09 |
March | 0.649042E+09 | 0.333919E+09 | 0.315123E+09 | 0.863781E+09 | 0.614084E+09 |
April | 0.895072E+09 | 0.533304E+09 | 0.361769E+09 | 0.153201E+10 | 0.334806E+09 |
May | 0.960147E+09 | 0.569718E+09 | 0.390429E+09 | 0.176729E+10 | 0.245523E+09 |
June | 0.966769E+09 | 0.600618E+09 | 0.366150E+09 | 0.205913E+10 | 0.113650E+09 |
July | 0.844997E+09 | 0.476785E+09 | 0.368211E+09 | 0.181616E+10 | 92023587.33 |
August | 0.802674E+09 | 0.458597E+09 | 0.344077E+09 | 0.169892E+10 | 0.121743E+09 |
September | 0.636531E+09 | 0.307003E+09 | 0.329528E+09 | 0.129361E+10 | 0.159007E+09 |
October | 0.660072E+09 | 0.401512E+09 | 0.258560E+09 | 0.105906E+10 | 0.464549E+09 |
November | 0.491558E+09 | 0.294985E+09 | 0.196573E+09 | 0.624349E+09 | 0.659250E+09 |
December | 0.463977E+09 | 0.280606E+09 | 0.183371E+09 | 0.528646E+09 | 0.864364E+09 |
Annual Sum or Average | 0.836876E+10 | 0.485870E+10 | 0.351006E+10 | 0.144719E+11 | 0.504208E+10 |
Minimum of Months | 0.463977E+09 | 0.271630E+09 | 0.183371E+09 | 0.528646E+09 | 92023587.33 |
Maximum of Months | 0.966769E+09 | 0.600618E+09 | 0.390429E+09 | 0.205913E+10 | 0.864364E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185703E+10 | 0.148355E+10 | 0.373477E+09 | 0.290271E+10 | 0.986322E+09 |
February | 0.104660E+10 | 0.701644E+09 | 0.344960E+09 | 0.146173E+10 | 0.892118E+09 |
March | 0.959244E+09 | 0.486075E+09 | 0.473169E+09 | 0.143387E+10 | 0.888713E+09 |
April | 0.814736E+09 | 0.335612E+09 | 0.479125E+09 | 0.157234E+10 | 0.512323E+09 |
May | 0.562539E+09 | 97856651.04 | 0.464683E+09 | 0.120274E+10 | 0.381156E+09 |
June | 0.460802E+09 | 35156463.06 | 0.425645E+09 | 0.132607E+10 | 0.174127E+09 |
July | 0.482508E+09 | 45876740.08 | 0.436631E+09 | 0.133192E+10 | 0.137487E+09 |
August | 0.596644E+09 | 0.168037E+09 | 0.428607E+09 | 0.154610E+10 | 0.177000E+09 |
September | 0.820170E+09 | 0.346646E+09 | 0.473524E+09 | 0.179123E+10 | 0.230273E+09 |
October | 0.136040E+10 | 0.941760E+09 | 0.418636E+09 | 0.233408E+10 | 0.648956E+09 |
November | 0.154750E+10 | 0.118855E+10 | 0.358955E+09 | 0.237759E+10 | 0.895680E+09 |
December | 0.172940E+10 | 0.137015E+10 | 0.359253E+09 | 0.258522E+10 | 0.116953E+10 |
Annual Sum or Average | 0.122376E+11 | 0.720091E+10 | 0.503666E+10 | 0.218656E+11 | 0.709369E+10 |
Minimum of Months | 0.460802E+09 | 35156463.06 | 0.344960E+09 | 0.120274E+10 | 0.137487E+09 |
Maximum of Months | 0.185703E+10 | 0.148355E+10 | 0.479125E+09 | 0.290271E+10 | 0.116953E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.552136E+09 | 0.343997E+09 | 0.208139E+09 | 0.795503E+09 | 0.785760E+09 |
February | 0.403944E+09 | 0.196042E+09 | 0.207902E+09 | 0.464647E+09 | 0.692435E+09 |
March | 0.591796E+09 | 0.283041E+09 | 0.308756E+09 | 0.802001E+09 | 0.654505E+09 |
April | 0.877069E+09 | 0.500583E+09 | 0.376486E+09 | 0.152795E+10 | 0.369579E+09 |
May | 0.909581E+09 | 0.509722E+09 | 0.399860E+09 | 0.169808E+10 | 0.275173E+09 |
June | 0.933119E+09 | 0.548695E+09 | 0.384424E+09 | 0.199145E+10 | 0.124937E+09 |
July | 0.701403E+09 | 0.326845E+09 | 0.374558E+09 | 0.155361E+10 | 98565456.80 |
August | 0.671420E+09 | 0.337626E+09 | 0.333794E+09 | 0.146678E+10 | 0.126133E+09 |
September | 0.565440E+09 | 0.237748E+09 | 0.327692E+09 | 0.117563E+10 | 0.166739E+09 |
October | 0.600274E+09 | 0.344236E+09 | 0.256038E+09 | 0.987995E+09 | 0.500335E+09 |
November | 0.531752E+09 | 0.320848E+09 | 0.210903E+09 | 0.749592E+09 | 0.708085E+09 |
December | 0.440872E+09 | 0.249960E+09 | 0.190912E+09 | 0.561182E+09 | 0.937216E+09 |
Annual Sum or Average | 0.777881E+10 | 0.419934E+10 | 0.357946E+10 | 0.137744E+11 | 0.543946E+10 |
Minimum of Months | 0.403944E+09 | 0.196042E+09 | 0.190912E+09 | 0.464647E+09 | 98565456.80 |
Maximum of Months | 0.933119E+09 | 0.548695E+09 | 0.399860E+09 | 0.199145E+10 | 0.937216E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1604.30 | 899.41 | 1095.80 | 805.55 | 290.25 | 0.00 | 0.00 |
February | 990.12 | 892.63 | 794.75 | 483.35 | 311.40 | 0.00 | 0.00 |
March | 1120.45 | 768.61 | 821.42 | 411.83 | 409.59 | 0.00 | 0.00 |
April | 1756.52 | 438.78 | 998.02 | 528.36 | 469.67 | 0.00 | 0.00 |
May | 1721.92 | 315.76 | 908.10 | 439.55 | 468.55 | 0.00 | 0.00 |
June | 2064.71 | 149.61 | 910.76 | 456.97 | 453.79 | 0.00 | 0.00 |
July | 1750.76 | 117.84 | 757.51 | 317.17 | 440.34 | 0.00 | 0.00 |
August | 1754.32 | 153.76 | 773.13 | 360.01 | 413.11 | 0.00 | 0.00 |
September | 1637.85 | 208.67 | 780.15 | 343.90 | 436.24 | 0.00 | 0.00 |
October | 1614.41 | 581.23 | 978.47 | 630.04 | 348.43 | 0.00 | 0.00 |
November | 1417.04 | 842.77 | 991.83 | 696.14 | 295.69 | 0.00 | 0.00 |
December | 1331.83 | 1069.01 | 983.52 | 709.65 | 273.87 | 0.00 | 0.00 |
Annual Sum or Average | 1566.70 | 534.97 | 900.09 | 515.57 | 384.52 | 0.00 | 0.00 |
Minimum of Months | 990.12 | 117.84 | 757.51 | 317.17 | 273.87 | 0.00 | 0.00 |
Maximum of Months | 2064.71 | 1069.01 | 1095.80 | 805.55 | 469.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429696E+10 | 0.240898E+10 | 0.293498E+10 | 0.215757E+10 | 0.777404E+09 | 0.00 | 0.00 |
February | 0.239529E+10 | 0.215946E+10 | 0.192265E+10 | 0.116932E+10 | 0.753338E+09 | 0.00 | 0.00 |
March | 0.300100E+10 | 0.205866E+10 | 0.220008E+10 | 0.110303E+10 | 0.109705E+10 | 0.00 | 0.00 |
April | 0.455290E+10 | 0.113731E+10 | 0.258688E+10 | 0.136950E+10 | 0.121738E+10 | 0.00 | 0.00 |
May | 0.461200E+10 | 0.845736E+09 | 0.243227E+10 | 0.117730E+10 | 0.125497E+10 | 0.00 | 0.00 |
June | 0.535173E+10 | 0.387794E+09 | 0.236069E+10 | 0.118447E+10 | 0.117622E+10 | 0.00 | 0.00 |
July | 0.468924E+10 | 0.315634E+09 | 0.202891E+10 | 0.849507E+09 | 0.117940E+10 | 0.00 | 0.00 |
August | 0.469876E+10 | 0.411835E+09 | 0.207074E+10 | 0.964259E+09 | 0.110648E+10 | 0.00 | 0.00 |
September | 0.424532E+10 | 0.540868E+09 | 0.202214E+10 | 0.891397E+09 | 0.113074E+10 | 0.00 | 0.00 |
October | 0.432405E+10 | 0.155675E+10 | 0.262074E+10 | 0.168751E+10 | 0.933234E+09 | 0.00 | 0.00 |
November | 0.367297E+10 | 0.218446E+10 | 0.257081E+10 | 0.180438E+10 | 0.766431E+09 | 0.00 | 0.00 |
December | 0.356717E+10 | 0.286323E+10 | 0.263425E+10 | 0.190071E+10 | 0.733535E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.494074E+11 | 0.168707E+11 | 0.283851E+11 | 0.162590E+11 | 0.121262E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239529E+10 | 0.315634E+09 | 0.192265E+10 | 0.849507E+09 | 0.733535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535173E+10 | 0.286323E+10 | 0.293498E+10 | 0.215757E+10 | 0.125497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638505E+10 | -0.622516E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159889667.6 | 81.22 | 0.00 | 0.00 |
February | 0.578059E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146301598.8 | 81.22 | 0.00 | 0.00 |
March | 0.645305E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159183314.3 | 81.21 | 0.00 | 0.00 |
April | 0.619331E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149811400.0 | 81.21 | 0.00 | 0.00 |
May | 0.641432E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154124231.2 | 81.21 | 0.00 | 0.00 |
June | 0.623561E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149023632.3 | 81.21 | 0.00 | 0.00 |
July | 0.637103E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153941393.8 | 81.21 | 0.00 | 0.00 |
August | 0.644911E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153894297.4 | 81.21 | 0.00 | 0.00 |
September | 0.619363E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148816691.4 | 81.21 | 0.00 | 0.00 |
October | 0.637961E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155776889.8 | 81.21 | 0.00 | 0.00 |
November | 0.617815E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153525023.3 | 81.21 | 0.00 | 0.00 |
December | 0.637974E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162657962.0 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754132E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.184695E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578059E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162657962.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645305E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146301598.8 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.205300E+11 | -0.196402E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -889720813.0 | 58.98 | 0.00 | 0.00 |
February | 0.184155E+11 | -0.175945E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -821065679.3 | 58.99 | 0.00 | 0.00 |
March | 0.195845E+11 | -0.187012E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -883314299.5 | 58.98 | 0.00 | 0.00 |
April | 0.173392E+11 | -0.165231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -816153916.7 | 58.98 | 0.00 | 0.00 |
May | 0.163426E+11 | -0.155054E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -837170119.9 | 58.99 | 0.00 | 0.00 |
June | 0.146057E+11 | -0.137968E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -808893751.0 | 58.98 | 0.00 | 0.00 |
July | 0.142864E+11 | -0.134511E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -835369065.5 | 58.98 | 0.00 | 0.00 |
August | 0.146536E+11 | -0.138190E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834621686.1 | 58.97 | 0.00 | 0.00 |
September | 0.150264E+11 | -0.142195E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -806944718.0 | 58.98 | 0.00 | 0.00 |
October | 0.169819E+11 | -0.161297E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852224214.6 | 58.98 | 0.00 | 0.00 |
November | 0.180111E+11 | -0.171609E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -850163588.5 | 58.99 | 0.00 | 0.00 |
December | 0.199043E+11 | -0.189892E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -915157554.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.205681E+12 | -0.195531E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.101508E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.142864E+11 | -0.196402E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -915157554.2 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.205300E+11 | -0.134511E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -806944718.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.577699E+09 | 28835.38 | 01-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473516E+09 | 18083.75 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837060E+09 | 27995.13 | 26-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20191387.55 | 3947.70 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370238E+09 | 24831.11 | 23-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228622E+10 | 30289.65 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228622E+10 | 30289.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686786E+09 | 19843.92 | 01-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630859E+09 | 10869.19 | 09-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825956E+09 | 19726.85 | 26-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28608558.20 | 4226.69 | 25-OCT-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.515667E+09 | 17888.72 | 23-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301940E+10 | 22346.03 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.301940E+10 | 22346.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.140662E+11 | 0.139953E+11 | 39232.99 | 31-JAN-14:00 | 39232.99 | 0.00 |
February | 0.00 | 0.00 | 0.121261E+10 | 0.106971E+10 | 20946.00 | 18-FEB-13:53 | 17126.64 | 0.00 |
March | 0.00 | 0.00 | 0.147693E+11 | 0.144156E+11 | 41628.81 | 20-MAR-17:10 | 41560.68 | 0.00 |
April | 0.00 | 0.00 | 0.529114E+11 | 0.528144E+11 | 59175.94 | 14-APR-17:03 | 59175.94 | 0.00 |
May | 0.00 | 0.00 | 0.690379E+11 | 0.690344E+11 | 62246.96 | 31-MAY-17:03 | 62246.96 | 0.00 |
June | 0.00 | 0.00 | 0.904741E+11 | 0.899359E+11 | 77285.09 | 17-JUN-18:10 | 68202.16 | 0.00 |
July | 0.00 | 0.00 | 0.104276E+12 | 0.887895E+11 | 89035.36 | 23-JUL-04:02 | 60852.77 | 0.00 |
August | 0.00 | 0.00 | 0.102091E+12 | 0.864109E+11 | 79332.81 | 18-AUG-11:30 | 62542.72 | 0.00 |
September | 0.00 | 0.00 | 0.892367E+11 | 0.741977E+11 | 82852.45 | 02-SEP-04:02 | 50700.64 | 0.00 |
October | 0.00 | 0.00 | 0.445148E+11 | 0.414059E+11 | 70600.90 | 03-OCT-12:00 | 54300.56 | 0.00 |
November | 0.00 | 0.00 | 0.145147E+11 | 0.135251E+11 | 49227.77 | 01-NOV-12:55 | 42428.02 | 0.00 |
December | 0.00 | 0.00 | 0.607455E+10 | 0.606656E+10 | 33914.10 | 22-DEC-14:00 | 33914.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.603180E+12 | 0.551661E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.121261E+10 | 0.106971E+10 | 20946.00 | 17126.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104276E+12 | 0.899359E+11 | 89035.36 | 68202.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.608478E+10 | 0.598828E+10 | 45432.37 | 24-JAN-04:41 | 38080.13 | 0.00 |
February | 0.00 | 0.00 | 0.470732E+09 | 0.372676E+09 | 45432.37 | 17-FEB-04:21 | 21029.11 | 0.00 |
March | 0.00 | 0.00 | 0.724981E+10 | 0.692868E+10 | 45432.37 | 17-MAR-03:11 | 32627.21 | 0.00 |
April | 0.00 | 0.00 | 0.305936E+11 | 0.304698E+11 | 45432.37 | 30-APR-02:62 | 45432.37 | 0.00 |
May | 0.00 | 0.00 | 0.428343E+11 | 0.427985E+11 | 45432.37 | 08-MAY-01:22 | 45432.37 | 0.00 |
June | 0.00 | 0.00 | 0.615906E+11 | 0.613657E+11 | 45978.53 | 17-JUN-16:00 | 45321.26 | 0.00 |
July | 0.00 | 0.00 | 0.700247E+11 | 0.600756E+11 | 50278.01 | 14-JUL-03:21 | 19919.35 | 0.00 |
August | 0.00 | 0.00 | 0.671193E+11 | 0.573640E+11 | 49554.02 | 01-AUG-03:01 | 25809.27 | 0.00 |
September | 0.00 | 0.00 | 0.568275E+11 | 0.470544E+11 | 49643.69 | 02-SEP-00:11 | 28536.36 | 0.00 |
October | 0.00 | 0.00 | 0.255258E+11 | 0.234053E+11 | 48440.26 | 03-OCT-02:62 | 24220.98 | 0.00 |
November | 0.00 | 0.00 | 0.707737E+10 | 0.636696E+10 | 45432.37 | 03-NOV-03:31 | 27155.32 | 0.00 |
December | 0.00 | 0.00 | 0.248450E+10 | 0.246698E+10 | 15826.07 | 22-DEC-14:55 | 15826.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.377883E+12 | 0.344657E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.470732E+09 | 0.372676E+09 | 15826.07 | 15826.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.700247E+11 | 0.613657E+11 | 50278.01 | 45432.37 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7794.81 | 14849.55 | 24-JAN-19:08 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7735.57 | 14790.65 | 01-FEB-19:25 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7444.87 | 14376.89 | 02-MAR-07:42 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6838.92 | 13430.64 | 03-APR-18:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6254.83 | 12363.85 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5789.39 | 11242.90 | 01-JUN-18:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5489.97 | 10507.43 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5625.83 | 10819.93 | 31-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5952.52 | 11668.01 | 29-SEP-18:12 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6487.62 | 12884.33 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7084.55 | 13929.97 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 7552.49 | 14611.84 | 29-DEC-20:00 |
Annual Sum or Average | 0.00 | 6664.99 | ||||
Minimum of Months | 0.00 | 0.00 | 5489.97 | 10507.43 | ||
Maximum of Months | 0.00 | 0.00 | 7794.81 | 14849.55 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.512986E+10 | 0.61 | 2203.40 | 01-JAN-00:03 | 0.70 |
February | 0.459245E+10 | 0.60 | 2203.40 | 01-FEB-00:03 | 0.71 |
March | 0.520356E+10 | 0.62 | 2203.40 | 01-MAR-00:03 | 0.70 |
April | 0.541042E+10 | 0.66 | 2203.40 | 01-APR-02:45 | 0.70 |
May | 0.563016E+10 | 0.67 | 2203.40 | 01-MAY-00:19 | 0.70 |
June | 0.544077E+10 | 0.67 | 2203.40 | 01-JUN-00:10 | 0.70 |
July | 0.562357E+10 | 0.66 | 2203.40 | 01-JUL-00:09 | 0.70 |
August | 0.562410E+10 | 0.66 | 2203.40 | 01-AUG-00:08 | 0.70 |
September | 0.544206E+10 | 0.66 | 2203.40 | 01-SEP-00:09 | 0.70 |
October | 0.552659E+10 | 0.66 | 2203.40 | 01-OCT-00:09 | 0.70 |
November | 0.511488E+10 | 0.63 | 2203.40 | 01-NOV-00:55 | 0.70 |
December | 0.505119E+10 | 0.60 | 2203.40 | 01-DEC-00:05 | 0.70 |
Annual Sum or Average | 0.637896E+11 | 0.64 | |||
Minimum of Months | 0.459245E+10 | 0.60 | 2203.40 | 0.70 | |
Maximum of Months | 0.563016E+10 | 0.67 | 2203.40 | 0.71 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199083E+11 | 1.39 | 8919.51 | 02-JAN-13:20 | 1.68 |
February | 0.179817E+11 | 1.38 | 8919.51 | 01-FEB-00:03 | 1.68 |
March | 0.199083E+11 | 1.39 | 8919.51 | 18-MAR-08:33 | 1.66 |
April | 0.192661E+11 | 1.39 | 8919.51 | 01-APR-04:01 | 1.67 |
May | 0.199083E+11 | 1.39 | 8919.51 | 01-MAY-04:01 | 1.67 |
June | 0.192661E+11 | 1.39 | 8919.51 | 01-JUN-04:04 | 1.67 |
July | 0.199092E+11 | 1.38 | 8919.51 | 01-JUL-04:02 | 1.67 |
August | 0.199083E+11 | 1.38 | 8919.51 | 01-AUG-04:05 | 1.64 |
September | 0.192661E+11 | 1.38 | 8919.51 | 01-SEP-04:03 | 1.65 |
October | 0.199083E+11 | 1.39 | 8919.51 | 01-OCT-04:04 | 1.66 |
November | 0.192661E+11 | 1.39 | 8919.51 | 26-NOV-15:57 | 1.67 |
December | 0.199083E+11 | 1.39 | 8919.51 | 08-DEC-14:35 | 1.68 |
Annual Sum or Average | 0.234406E+12 | 1.39 | |||
Minimum of Months | 0.179817E+11 | 1.38 | 8919.51 | 1.64 | |
Maximum of Months | 0.199092E+11 | 1.39 | 8919.51 | 1.68 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.444434E+10 | 0.84 | 1984.41 | 08-JAN-16:56 | 0.95 |
February | 0.401046E+10 | 0.83 | 1984.41 | 01-FEB-06:10 | 0.97 |
March | 0.444915E+10 | 0.85 | 1984.41 | 08-MAR-15:40 | 0.97 |
April | 0.437621E+10 | 0.91 | 1984.41 | 10-APR-08:11 | 0.97 |
May | 0.455726E+10 | 0.91 | 1984.41 | 19-MAY-06:20 | 0.97 |
June | 0.446021E+10 | 0.89 | 1984.41 | 15-JUN-05:40 | 0.97 |
July | 0.462192E+10 | 0.88 | 1984.41 | 01-JUL-06:23 | 0.97 |
August | 0.462130E+10 | 0.88 | 1984.41 | 05-AUG-17:52 | 0.95 |
September | 0.448207E+10 | 0.89 | 1984.41 | 01-SEP-04:09 | 0.95 |
October | 0.452383E+10 | 0.89 | 1984.41 | 08-OCT-21:20 | 0.97 |
November | 0.431760E+10 | 0.86 | 1984.41 | 11-NOV-18:08 | 0.95 |
December | 0.443718E+10 | 0.83 | 1984.41 | 05-DEC-09:28 | 0.97 |
Annual Sum or Average | 0.533015E+11 | 0.87 | |||
Minimum of Months | 0.401046E+10 | 0.83 | 1984.41 | 0.95 | |
Maximum of Months | 0.462192E+10 | 0.91 | 1984.41 | 0.97 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:03 | 5.36 | 5.36 | 49.72 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.05 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.73 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 53.45 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.55 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 53.79 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 54.40 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.51 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 54.63 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 53.17 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 52.73 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 50.96 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.72 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.63 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 49.72 | 59.80 | 7794.81 | 14849.55 | 24-JAN-19:08 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.05 | 58.27 | 7735.57 | 14790.65 | 01-FEB-19:25 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.73 | 59.45 | 7444.87 | 14376.89 | 02-MAR-07:42 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.03 | 52.03 | 6838.92 | 13430.64 | 03-APR-18:47 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.25 | 52.25 | 6254.83 | 12363.85 | 01-MAY-18:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.89 | 52.89 | 5789.39 | 11242.90 | 01-JUN-18:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.41 | 53.41 | 5489.97 | 10507.43 | 03-JUL-18:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.66 | 53.66 | 5625.83 | 10819.93 | 31-AUG-18:12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.63 | 53.63 | 5952.52 | 11668.01 | 29-SEP-18:12 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.25 | 51.25 | 6487.62 | 12884.33 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.65 | 51.65 | 7084.55 | 13929.97 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.96 | 58.63 | 7552.49 | 14611.84 | 29-DEC-20:00 |
Annual Sum or Average | 0.00 | 6664.99 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.72 | 51.25 | 5489.97 | 10507.43 | ||
Maximum of Months | 0.00 | 0.00 | 53.66 | 59.80 | 7794.81 | 14849.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.244900E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183903E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.246912E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361576E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.422117E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.499575E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.534133E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.527446E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.472784E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.340793E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.239396E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.219054E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.429259E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183903E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.534133E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.624453E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.415406E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.656092E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.130179E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166927E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.224281E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.237858E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.230623E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.198618E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116640E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.637053E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.517960E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159022E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.415406E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237858E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199083E+11 | 0.140662E+11 | 0.577699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179817E+11 | 0.121261E+10 | 0.473516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199083E+11 | 0.147693E+11 | 0.837060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192661E+11 | 0.529114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199083E+11 | 0.690379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192661E+11 | 0.904741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199092E+11 | 0.104276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199083E+11 | 0.102091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192661E+11 | 0.892367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199083E+11 | 0.445148E+11 | 20191387.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192661E+11 | 0.145147E+11 | 0.370238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199083E+11 | 0.607455E+10 | 0.228622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234406E+12 | 0.603180E+12 | 0.456492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179817E+11 | 0.121261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199092E+11 | 0.104276E+12 | 0.228622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.444434E+10 | 0.608478E+10 | 0.686786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401046E+10 | 0.470732E+09 | 0.630859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444915E+10 | 0.724981E+10 | 0.825956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437621E+10 | 0.305936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455726E+10 | 0.428343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446021E+10 | 0.615906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.462192E+10 | 0.700247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.462130E+10 | 0.671193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448207E+10 | 0.568275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452383E+10 | 0.255258E+11 | 28608558.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.431760E+10 | 0.707737E+10 | 0.515667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443718E+10 | 0.248450E+10 | 0.301940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533015E+11 | 0.377883E+12 | 0.570728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401046E+10 | 0.470732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.462192E+10 | 0.700247E+11 | 0.301940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.458170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179817E+11 | 0.00 | 0.00 | 0.00 | 0.408583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.478289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192661E+11 | 0.00 | 0.00 | 0.00 | 0.168915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.223034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192661E+11 | 0.00 | 0.00 | 0.00 | 0.306914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199092E+11 | 0.00 | 0.00 | 0.00 | 0.335040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.328362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192661E+11 | 0.00 | 0.00 | 0.00 | 0.280123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.141710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192661E+11 | 0.00 | 0.00 | 0.00 | 0.467350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199083E+11 | 0.00 | 0.00 | 0.00 | 0.199707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234406E+12 | 0.00 | 0.00 | 0.00 | 0.194854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179817E+11 | 0.00 | 0.00 | 0.00 | 0.408583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199092E+11 | 0.00 | 0.00 | 0.00 | 0.335040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.444434E+10 | 0.00 | 0.00 | 0.00 | 0.180019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401046E+10 | 0.00 | 0.00 | 0.00 | 0.143594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444915E+10 | 0.00 | 0.00 | 0.00 | 0.211177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437621E+10 | 0.00 | 0.00 | 0.00 | 0.864173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455726E+10 | 0.00 | 0.00 | 0.00 | 0.121354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446021E+10 | 0.00 | 0.00 | 0.00 | 0.179679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.462192E+10 | 0.00 | 0.00 | 0.00 | 0.191639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.462130E+10 | 0.00 | 0.00 | 0.00 | 0.184410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448207E+10 | 0.00 | 0.00 | 0.00 | 0.153797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452383E+10 | 0.00 | 0.00 | 0.00 | 0.714013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.431760E+10 | 0.00 | 0.00 | 0.00 | 0.205293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443718E+10 | 0.00 | 0.00 | 0.00 | 0.742425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533015E+11 | 0.00 | 0.00 | 0.00 | 0.105721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.401046E+10 | 0.00 | 0.00 | 0.00 | 0.143594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.462192E+10 | 0.00 | 0.00 | 0.00 | 0.191639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134609E+11 | 14131118.89 | 0.00 | 0.104149E+09 | 0.00 | 21908471.89 | 0.332283E+11 | 0.00 | 5.91 |
February | 0.147712E+11 | 0.00 | 0.00 | 57024458.90 | 0.00 | 35307322.04 | 0.337607E+11 | 0.00 | 4.97 |
March | 0.126674E+11 | 51347366.00 | 0.00 | 99044061.59 | 0.00 | 40071353.29 | 0.323214E+11 | 0.00 | 5.82 |
April | 0.271316E+10 | 0.251465E+10 | 0.00 | 0.123628E+09 | 1289125.39 | 0.00 | 0.147351E+11 | 0.00 | 5.01 |
May | 0.132966E+10 | 0.562629E+10 | 0.00 | 85363105.55 | 2581196.42 | 0.00 | 0.819689E+10 | 0.00 | 4.45 |
June | 0.364767E+09 | 0.158662E+11 | 0.00 | 21767900.09 | 62668655.22 | 0.00 | 0.258026E+10 | 0.00 | 4.10 |
July | 0.241840E+09 | 0.242056E+11 | 0.00 | 8157487.21 | 0.192229E+09 | 0.00 | 0.112662E+10 | 0.00 | 3.99 |
August | 0.295574E+09 | 0.224240E+11 | 0.00 | 10198252.60 | 0.143602E+09 | 0.00 | 0.182579E+10 | 0.00 | 4.29 |
September | 0.521348E+09 | 0.161913E+11 | 0.00 | 18002831.58 | 66996456.71 | 0.00 | 0.330432E+10 | 0.00 | 4.58 |
October | 0.497509E+10 | 0.371175E+10 | 0.00 | 0.102612E+09 | 14082157.86 | 0.00 | 0.237201E+11 | 0.00 | 5.75 |
November | 0.104212E+11 | 71858028.70 | 0.00 | 0.100647E+09 | 164327.76 | 11325435.10 | 0.354889E+11 | 0.00 | 5.97 |
December | 0.211560E+11 | 0.00 | 0.00 | 77143162.58 | 0.00 | 80148381.56 | 0.320106E+11 | 0.00 | 5.26 |
Annual Sum or Average | 0.829182E+11 | 0.906771E+11 | 0.00 | 0.807739E+09 | 0.483612E+09 | 0.188761E+09 | 0.222299E+12 | 0.00 | 5.01 |
Minimum of Months | 0.241840E+09 | 0.00 | 0.00 | 8157487.21 | 0.00 | 0.00 | 0.112662E+10 | 0.00 | 3.99 |
Maximum of Months | 0.211560E+11 | 0.242056E+11 | 0.00 | 0.123628E+09 | 0.192229E+09 | 80148381.56 | 0.354889E+11 | 0.00 | 5.97 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175540E+11 | 0.00 | 0.00 | 83765462.27 | 0.00 | 0.00 | 0.308659E+11 | 0.00 | 11.73 |
February | 0.186450E+11 | 0.00 | 0.00 | 40094371.37 | 0.00 | 0.00 | 0.279865E+11 | 0.00 | 11.09 |
March | 0.158927E+11 | 0.00 | 0.00 | 83911451.35 | 0.00 | 0.00 | 0.308308E+11 | 0.00 | 11.75 |
April | 0.254664E+10 | 0.425378E+09 | 0.00 | 0.153628E+09 | 0.00 | 0.00 | 0.230012E+11 | 0.00 | 11.94 |
May | 0.614386E+09 | 0.172207E+10 | 0.00 | 0.153010E+09 | 0.00 | 0.00 | 0.169818E+11 | 0.00 | 11.85 |
June | 41331563.25 | 0.926027E+10 | 0.00 | 80563425.60 | 0.00 | 0.00 | 0.655016E+10 | 0.00 | 11.72 |
July | 22952050.72 | 0.141440E+11 | 0.00 | 37514147.57 | 0.00 | 0.00 | 0.292755E+10 | 0.00 | 11.85 |
August | 4527427.15 | 0.121538E+11 | 0.00 | 40592152.71 | 0.00 | 0.00 | 0.385284E+10 | 0.00 | 12.02 |
September | 31328540.90 | 0.768222E+10 | 0.00 | 64599150.06 | 0.00 | 0.00 | 0.666395E+10 | 0.00 | 12.30 |
October | 0.537914E+10 | 0.137370E+10 | 0.00 | 0.111766E+09 | 0.00 | 0.00 | 0.269230E+11 | 0.00 | 12.15 |
November | 0.132496E+11 | 0.00 | 0.00 | 86006096.38 | 0.00 | 0.00 | 0.327838E+11 | 0.00 | 11.83 |
December | 0.283472E+11 | 0.00 | 0.00 | 55315543.67 | 0.00 | 0.00 | 0.266689E+11 | 0.00 | 11.30 |
Annual Sum or Average | 0.102329E+12 | 0.467614E+11 | 0.00 | 0.990766E+09 | 0.00 | 0.00 | 0.236037E+12 | 0.00 | 11.80 |
Minimum of Months | 4527427.15 | 0.00 | 0.00 | 37514147.57 | 0.00 | 0.00 | 0.292755E+10 | 0.00 | 11.09 |
Maximum of Months | 0.283472E+11 | 0.141440E+11 | 0.00 | 0.153628E+09 | 0.00 | 0.00 | 0.327838E+11 | 0.00 | 12.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:35
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.565078E+11 | 0.889466E+10 | 0.131819E+12 | 0.171809E+11 | 0.514351E+11 |
February | 0.640112E+11 | 0.104357E+11 | 0.135583E+12 | 0.114087E+11 | 0.226712E+11 |
March | 0.908362E+11 | 0.993126E+10 | 0.129464E+12 | 0.166501E+11 | 0.545621E+11 |
April | 0.124631E+12 | 0.557491E+10 | 0.708149E+11 | 0.826434E+10 | 0.139193E+12 |
May | 0.132395E+12 | 0.383034E+10 | 0.438352E+11 | 0.472382E+10 | 0.177741E+12 |
June | 0.138175E+12 | 0.816700E+09 | -0.108115E+11 | 0.187887E+10 | 0.232555E+12 |
July | 0.123199E+12 | -0.115619E+10 | -0.372686E+11 | 0.395233E+09 | 0.259819E+12 |
August | 0.104333E+12 | -0.102534E+10 | -0.295232E+11 | 0.109810E+10 | 0.254078E+12 |
September | 0.860305E+11 | -294414578.9 | -0.724422E+10 | 0.187066E+10 | 0.218457E+12 |
October | 0.761140E+11 | 0.499726E+10 | 0.849737E+11 | 0.137491E+11 | 0.118386E+12 |
November | 0.591480E+11 | 0.863275E+10 | 0.128389E+12 | 0.179742E+11 | 0.517392E+11 |
December | 0.431403E+11 | 0.108419E+11 | 0.153562E+12 | 0.133693E+11 | 0.362713E+11 |
Annual Sum or Average | 0.109852E+13 | 0.614795E+11 | 0.793594E+12 | 0.108563E+12 | 0.161691E+13 |
Minimum of Months | 0.431403E+11 | -0.115619E+10 | -0.372686E+11 | 0.395233E+09 | 0.226712E+11 |
Maximum of Months | 0.138175E+12 | 0.108419E+11 | 0.153562E+12 | 0.179742E+11 | 0.259819E+12 |