Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:27:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2382.36 | 4660.75 | 4660.75 |
Net Site Energy | 2382.36 | 4660.75 | 4660.75 |
Total Source Energy | 5565.85 | 10888.80 | 10888.80 |
Net Source Energy | 5565.85 | 10888.80 | 10888.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 263.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 366.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.39 | 313.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 66.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1432.25 | 950.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 263.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 366.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.39 | 313.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 167.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 263.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 366.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.39 | 313.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 66.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1381.31 | 939.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1030.92 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2801.99 | 1858.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1381.31 | 939.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1030.92 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2801.99 | 1858.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1432.248 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1432.248 | 100.00 |
Total On-Site and Utility Electric Sources | 1432.248 | 100.00 |
Total Electricity End Uses | 1432.248 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5872.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 14.4672 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.5854 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 14.4672 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.5854 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 13.6812 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JUN-17:19 | 27-DEC-07:49 | - | - | - | - | - | - | - | - | - | - | 14-FEB-07:40 |
Heating | 0.00 | 78113.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41383.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13633.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4443.74 | 24758.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2060.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 88509.34 | 116448.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 78113.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 41383.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13633.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4443.74 | 24758.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 513.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1001.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 181.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 834.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1161.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.75 | 339.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 209.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4535.93 | 1029.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 354.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1632.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2272.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.07 | 663.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 410.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8873.91 | 2014.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 354.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1632.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2272.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.07 | 663.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 410.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8873.91 | 2014.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.95 |
KITCHEN DIRECT AIR | 1.95 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.95 | 4.95 | 4.95 | 4.95 | 4.95 | 4.95 | 1.00 | 0.999954 | 4.95 |
PSZ-AC_2:2 | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.00 | 1.00 | 1.95 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.95 | 2.64 |
PSZ-AC_2:2_OA_CONTROLLER | 1.95 | 0.187543 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.95 | 9299.24 |
PSZ-AC_2:2_ADDAQ FAN | 1.95 | 2130.61 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.95 | 4.95 | 4.95 | 4.95 | 117805.79 | 171444.63 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.95 | 1.95 | 1.95 | 1.95 | 42215.18 | 64938.63 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.95 | 2.48 | 4.95 | 117805.79 | 58852.95 | 117805.79 | 0.714880 | 0.714880 |
PSZ-AC_2:2 COOLING COIL | 1.95 | 0.973323 | 1.95 | 42215.18 | 20274.96 | 42215.18 | 0.745640 | 0.745640 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 171444.63 |
PSZ-AC_2:2 HEATING COIL | 64938.63 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 14.467 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 79.395 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.585 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.665 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 5378.143 | 14.467 | 19.198 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5378.143 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1615.060 | 11.585 | 214.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1615.060 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.500 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4325 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 6 | 0.19952834E-07 | 0.37147198E-09 | 0.46430291E-08 | -0.89111870E-13 |
34 | 5 | -0.14466088E-03 | 0.34030017E-05 | -0.74831287E-04 | 0.46077240E-08 |
35 | 4 | 0.23721950 | 0.17579200E-02 | 0.80016642E-01 | -0.26003020E-04 |
36 | 3 | -6.1742659 | 0.57392279E-01 | -2.0151465 | 0.23669466E-01 |
37 | 2 | 37.264580 | 0.21353215 | 13.926457 | -0.29319906 |
38 | 1 | -77.776780 | 0.10018737 | -27.938560 | 1.0196200 |
39 | 0 | 46.824358 | 0.20941775E-02 | 16.322275 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 49093.44234 | 58912.13081 | 4.12731 | 4.95277 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
2 | DINING | Heating | 9299.77442 | 11159.72931 | 0.45961 | 2.64387 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -5.20000 | 2.80840E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
3 | KITCHEN | Cooling | 22738.43132 | 27286.11758 | 1.62221 | 1.94665 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
4 | KITCHEN | Heating | 249.96378 | 299.95654 | 1.11879E-002 | 0.18754 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 97278.58 | 4.95300 | 4.95300 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 125407.04 | 2.64387 | 2.64387 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 29038.42 | 1.94665 | 1.94665 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 8895.77 | 0.18754 | 0.18754 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.95277 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.94665 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.95277 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.95277 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.95277 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.95277 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95300 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.95300 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99995 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.94665 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.94665 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.94665 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.94665 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.94665 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.94665 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.95300 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.94665 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95300 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.64387 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.95300 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9299.24165 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.95300 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.95300 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.95300 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.95300 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.95300 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.47650 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.95300 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 117805.79000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 58852.95023 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 117805.79000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71488 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71488 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 117805.79000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 171444.62689 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 171444.62689 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.94665 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.18754 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.94665 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2130.61497 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.94665 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.94665 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.94665 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.94665 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.94665 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97332 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.94665 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42215.18000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20274.95854 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 42215.18000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74564 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74564 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42215.18000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64938.62509 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 64938.62509 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 114272.3 | 9.89 | 9.76 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40816.1 | 9.96 | 9.83 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1074833276 | 0.3348708457 | Pass | Pass | 4.6787449237E-002 | 0.1096798124 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1099616599 | 0.5640494452 | Pass | Pass | 5.8544063241E-002 | 0.2274342540 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4711967024 | 0.4629900603 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1257.15 | 81.78 | 1661.94 | 301.89 | 1442.37 | 4745.15 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 14.4672 | 371.75 | 5378.14 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 97.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.5854 | 139.41 | 1615.06 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.38 |
Interior Lighting Total | 13.6812 | 511.15 | 6993.20 | 127.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.77 | 83.77 | 71.99 | |
Exterior Lighting Total | 4578.48 | 71.99 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 117805.79 | 84217.00 | 33588.79 | 0.71 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42215.18 | 31477.33 | 10737.85 | 0.75 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 114272.3 | 9.89 | 9.76 | ||||
PSZ-AC_2:2 COOLING COIL | 40816.1 | 9.96 | 9.83 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 171444.63 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 64938.63 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 2.64 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.95 | 9299.24 | 1877.50 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.95 | 2130.61 | 1094.51 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 49093.44 | 58912.13 | 158.47 | 4.127 | 4.953 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00824 | 37.84 | 0.00687 | 2.644 | 0.00 |
KITCHEN | 22738.43 | 27286.12 | 195.73 | 1.622 | 1.947 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00868 | 36.93 | 0.00687 | 0.188 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9299.77 | 11159.73 | 30.02 | 0.460 | 2.644 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 2.644 | 0.00 |
KITCHEN | 249.96 | 299.96 | 2.15 | 0.011 | 0.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.00 | 0.00279 | -5.20 | 0.00281 | 0.188 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.95 | 4.95 | 2.64 | 2.64 | 4.9530 | 4.9528 | 4.9530 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.95 | 1.95 | 0.19 | 0.19 | 1.9466 | 1.9466 | 1.9466 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 117805.790 | 84217.003 | 4.953000 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 117805.79 | 112019.11 | 4.953000 | 31.52 | 16.62 | 0.00751108 | 11.04 | 8.59 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 53.3792 | 23.99 | 0.00824417 | 38.5262 | 49064.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 171444.627 | 171444.627 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 02:50:00 | 171444.63 | 171444.63 | 4.952997 | 7.01 | 4.64 | 0.00511593 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 53.3792 | 21.00 | 0.00775798 | 43.5141 | 9287.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 42215.180 | 31477.327 | 1.946650 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 42215.18 | 35608.58 | 1.946650 | 27.01 | 15.95 | 0.00850779 | 11.77 | 8.90 | 0.00700000 | 36.93 | 0.00686961 | 17.82 | 9.6342 | 25.99 | 0.00868244 | 35.9995 | 22738.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 64938.625 | 64938.625 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 64938.63 | 64938.63 | 1.946646 | 8.21 | 2.65 | 0.00302106 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.6342 | 19.00 | 0.00304374 | 19.4657 | 182.17 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 117805.790 | 84217.003 | 4.953000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8027 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.952997 | 5.17257207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 117805.79 | 112019.11 | 1.0000 | 5.17257507 | 4.953000 | 31.52 | 16.62 | 0.00751108 | 50902.2 | 11.04 | 8.59 | 0.00700000 | 28739.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 117805.79 | 38.10 | 0.00687148 | 18.17 | 2.64386968 | 53.3792 | 23.99 | 0.00824417 | 23.99 | 0.00824417 | 38.5262 | 49064.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 171444.627 | 171444.627 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.952997 | 5.17257207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 02:50:00 | Sensible | 171444.63 | 171444.63 | 1.0000 | 5.17257207 | 4.952997 | 7.01 | 4.64 | 0.00511593 | 19909.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171444.63 | -5.20 | 0.00280840 | -5.20 | 2.64386968 | 53.3792 | 21.00 | 0.00775798 | 21.00 | 0.00775798 | 43.5141 | 9287.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42215.180 | 31477.327 | 1.946650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6556 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.946646 | 2.03294440 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 42215.18 | 35608.58 | 1.0000 | 2.03294837 | 1.946650 | 27.01 | 15.95 | 0.00850779 | 48850.3 | 11.77 | 8.90 | 0.00700000 | 29489.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42215.18 | 36.93 | 0.00686961 | 17.82 | 0.18754328 | 9.6342 | 25.96 | 0.00868244 | 25.99 | 0.00868244 | 35.9995 | 22738.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64938.625 | 64938.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.946646 | 2.03294440 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 64938.63 | 64938.63 | 1.0000 | 2.03294440 | 1.946646 | 8.21 | 2.65 | 0.00302106 | 15852.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64938.63 | -5.20 | 0.00280840 | -5.20 | 0.18754328 | 9.6342 | 9.64 | 0.00304374 | 19.00 | 0.00304374 | 19.4657 | 182.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 2.64 | 4.95 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.19 | 1.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3626.17 | 3367.33 | 694.83 |
KITCHEN | 7187.00 | 5626.33 | 5626.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7187.00 | 7041.17 | 5872.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.33 | 18.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 236.17 | 0.00 | 1.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.33 | 254.33 | 0.00 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 9.068 | 0.927 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.863 | 0.056 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 8.162 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 1.605 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 2.6439 | 2.644 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1242 | 0.053 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 2.7680 | 2.697 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 74301645.07 | 0.00 | 74301645.07 | 7606126.83 | 81907771.90 | 83377074.30 | 1443.25 | 5646.15 | 1670.60 | 210.03 |
KITCHEN | 27920878.56 | 0.00 | 27920878.56 | 265172.33 | 28186050.89 | 5914364.89 | 1033.70 | 1899.07 | 5827.23 | 772.51 |
Total Facility | 0.10E+09 | 0.00 | 0.10E+09 | 7871299.16 | 0.11E+09 | 89291439.19 | 1450.48 | 5652.72 | 5837.33 | 816.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 2.8150 | 0.0000 | 2.8150 | 0.2879 | 3.1030 | 2.6439 | 0.00 | 5557.34 | 1629.66 |
KITCHEN | 1.0193 | 0.0000 | 1.0193 | 0.0064 | 1.0257 | 0.1875 | 0.00 | 1891.17 | 5295.83 |
Total Facility | 3.8343 | 0.0000 | 3.8343 | 0.2944 | 4.1287 | 2.8314 | 0.00 | 5560.21 | 5298.71 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 81035511.04 | 0.00 | 81035511.04 | 83377074.30 | 1443.23 | 0.00 | 7316.77 | 210.03 |
PSZ-AC_2:2 | 30451313.33 | 0.00 | 30451313.33 | 5914364.89 | 1015.20 | 4.56 | 7740.24 | 772.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 3.0702 | 0.0000 | 3.0702 | 2.6439 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1117 | 0.0000 | 1.1117 | 0.1875 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1477.80 | 280.90 | 5638.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 5665.94 | 2293.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 3.7836 | 3.3169 | 2.8841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.4358 | 0.2046 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
Electricity:Building | 604.81 | 4434.71 | 01-JAN-01:10 | 33358.73 | 02-JAN-11:10 |
Electricity:Zone:DINING | 223.13 | 1289.45 | 01-JAN-01:10 | 11839.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 587.95 | 4025.67 | 01-JAN-01:10 | 30993.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.68 | 3145.26 | 01-JAN-01:10 | 21518.76 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.24 | 1192.40 | 15-APR-22:30 | 3441.39 | 19-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 125.22 | 1258.64 | 07-JUN-01:40 | 6472.64 | 16-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.53 | 0.00 | 01-JAN-11:10 | 1495.84 | 05-MAY-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 31.86 | 817.08 | 10-MAY-03:30 | 1076.23 | 13-FEB-13:10 |
ElectricityPurchased:Facility | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
ElectricityPurchased:Plant | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
Cogeneration:ElectricityPurchased | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
General:Cogeneration:ElectricityPurchased | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
ElectricityNet:Plant | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
Cogeneration:ElectricityNet | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
General:Cogeneration:ElectricityNet | 1432.25 | 10308.38 | 31-MAY-00:40 | 88509.34 | 02-JUN-17:20 |
Electricity:HVAC | 630.23 | 0.00 | 01-JAN-01:10 | 55468.42 | 02-JUN-17:10 |
Fans:Electricity | 366.75 | 0.00 | 01-JAN-01:10 | 13633.26 | 01-JAN-19:50 |
General:Fans:Electricity | 366.75 | 0.00 | 01-JAN-01:10 | 13633.26 | 01-JAN-19:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 263.48 | 0.00 | 01-JAN-00:10 | 41835.16 | 02-JUN-17:10 |
General:Cooling:Electricity | 263.48 | 0.00 | 01-JAN-00:10 | 41835.16 | 02-JUN-17:10 |
ExteriorLights:Electricity | 71.99 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.99 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4737.03 | 09-NOV-07:20 |
Water Heater:WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4737.03 | 09-NOV-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 02-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 02-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 950.11 | 2803.57 | 01-JAN-01:10 | 116448.20 | 27-DEC-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 167.23 | 0.00 | 01-JAN-00:10 | 84040.00 | 03-FEB-07:00 |
Heating:NaturalGas | 167.23 | 0.00 | 01-JAN-00:10 | 84040.00 | 03-FEB-07:00 |
General:Heating:NaturalGas | 167.23 | 0.00 | 01-JAN-00:10 | 84040.00 | 03-FEB-07:00 |
NaturalGas:Plant | 313.10 | 993.32 | 01-JAN-00:10 | 25906.46 | 30-JAN-07:20 |
WaterSystems:NaturalGas | 313.10 | 993.32 | 01-JAN-00:10 | 25906.46 | 30-JAN-07:20 |
Water Heater:WaterSystems:NaturalGas | 313.10 | 993.32 | 01-JAN-00:10 | 25906.46 | 30-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2104.07 | 3906.92 | 13-JUN-00:30 | 197650.25 | 21-JUL-18:00 |
EnergyTransfer:Building | 858.58 | 1953.46 | 13-JUN-00:30 | 65550.84 | 12-JUN-03:50 |
EnergyTransfer:Zone:KITCHEN | 452.40 | 1953.46 | 13-JUN-00:30 | 25437.50 | 03-JUL-11:00 |
Refrigeration:EnergyTransfer | 159.85 | 3640.18 | 12-APR-22:10 | 7834.84 | 28-FEB-04:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.92 | 1820.09 | 12-APR-22:10 | 3917.42 | 28-FEB-04:20 |
General:Refrigeration:EnergyTransfer | 79.92 | 1820.09 | 12-APR-22:10 | 3917.42 | 28-FEB-04:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.92 | 1820.09 | 12-APR-22:10 | 3917.42 | 28-FEB-04:20 |
EnergyTransfer:Plant | 296.76 | 1912.61 | 07-JUN-01:40 | 18126.68 | 23-JAN-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.57 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 64.35 | 1461.24 | 10-MAY-03:30 | 2238.70 | 13-FEB-13:10 |
EnergyTransfer:Zone:DINING | 406.18 | 0.00 | 01-JAN-01:10 | 55379.04 | 12-JUN-03:50 |
Heating:EnergyTransfer | 1.85 | 0.00 | 01-JAN-00:10 | 23569.17 | 12-JUN-03:50 |
Heating:EnergyTransfer:Zone:DINING | 1.85 | 0.00 | 01-JAN-00:10 | 23569.17 | 12-JUN-03:50 |
General:Heating:EnergyTransfer | 1.85 | 0.00 | 01-JAN-00:10 | 23569.17 | 12-JUN-03:50 |
General:Heating:EnergyTransfer:Zone:DINING | 1.85 | 0.00 | 01-JAN-00:10 | 23569.17 | 12-JUN-03:50 |
Cooling:EnergyTransfer | 776.81 | 0.00 | 01-JAN-01:10 | 56820.67 | 17-JUN-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 404.33 | 0.00 | 01-JAN-01:10 | 37061.18 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer | 776.81 | 0.00 | 01-JAN-01:10 | 56820.67 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 404.33 | 0.00 | 01-JAN-01:10 | 37061.18 | 17-JUN-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 34.91 | 06-JUN-03:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 34.91 | 06-JUN-03:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 372.48 | 0.00 | 01-JAN-01:10 | 21587.67 | 03-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 372.48 | 0.00 | 01-JAN-01:10 | 21587.67 | 03-JUL-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
PlantLoopHeatingDemand:Plant | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
EnergyTransfer:HVAC | 948.72 | 0.00 | 01-JAN-00:10 | 132256.55 | 21-JUL-11:10 |
HeatingCoils:EnergyTransfer | 132.53 | 0.00 | 01-JAN-00:10 | 66601.70 | 03-FEB-07:00 |
CoolingCoils:EnergyTransfer | 816.20 | 0.00 | 01-JAN-00:10 | 132256.55 | 21-JUL-11:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15489.22 | 30-JAN-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.850 | -404.324 | 0.000 | 0.000 | 218.550 | 97.852 | 93.957 | 44.163 | 0.000 | 14.970 | 0.270 | 0.000 | -23.001 | 0.000 | -44.288 | -0.001 |
KITCHEN | 0.000 | 0.000 | 0.000 | -372.472 | 0.000 | 0.000 | 4.764 | 29.385 | 297.857 | 0.000 | 0.000 | 0.191 | 43.184 | 0.000 | 0.000 | 0.000 | -2.909 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.512 | 38.521 | 0.000 | 0.000 | 0.000 | -48.033 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.850 | -776.796 | 0.000 | 0.000 | 223.314 | 127.237 | 391.814 | 44.163 | 0.000 | 24.673 | 81.975 | 0.000 | -23.001 | 0.000 | -95.230 | -0.002 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-MAY-03:01 | 0.00 | 0.00 | 0.00 | -133253.77 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 133422.05 | 0.00 | -1849.36 | 0.00 | -30.77 | 0.00 |
KITCHEN | 17-NOV-04:41 | 0.00 | 0.00 | 0.00 | -85188.15 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 81167.62 | 0.00 | -0.00 | 0.00 | -43.21 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-MAY-03:01 | 0.00 | 0.00 | 0.00 | -199052.44 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1416.39 | 193768.99 | 0.00 | -1849.36 | 0.00 | -59.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 14-MAY-03:46 | 0.00 | 0.00 | 71579.07 | 0.00 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -998.26 | 0.00 | -18.07 | -72274.59 |
KITCHEN | 06-JUN-03:02 | 0.00 | 0.00 | 349.10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.73 | -4387.11 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-MAY-03:46 | -6773.55 | 6773.55 | 71579.07 | -6773.55 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 458.78 | 0.00 | 0.00 | -998.26 | 0.00 | -133.39 | -69908.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.9528 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.9530 | 0.5338 | 1.0000 | Not calculated | 2.6439 | 0.5338 | ||
PSZ-AC_2:2 | 1.9466 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.9466 | 0.0638 | 1.0000 | Not calculated | 0.1242 | 0.0638 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.9528 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 4.9528 | 1.0000 | 1.0000 | Not calculated | 2.6439 | 0.5338 | ||
PSZ-AC_2:2 | 1.9466 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.9466 | 0.6620 | 1.0000 | Not calculated | 0.1242 | 0.0638 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.007112 | 371.75 | 2.6439 | 1.0000 | 2.6439 | 1.000 | 2.6439 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000381 | 139.41 | 0.1242 | 1.0000 | 0.1242 | 1.000 | 0.1242 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.007112 | 371.7481 | 2.6439 | 2.6439 | 2.6439 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000381 | 139.4052 | 0.1242 | 0.1242 | 0.1242 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9528 | 4.9528 | 4.9528 | No | 2.6439 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9466 | 1.9466 | 1.9466 | No | 0.1242 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.9528 | 4.9530 | 4.9528 | 4.9528 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.9466 | 1.9466 | 1.9466 | 1.9466 | 0.1242 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9528 | 4.9528 | 4.9528 | No | 2.6439 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9466 | 1.9466 | 1.9466 | No | 0.1242 | 0.6620 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.9528 | 4.9528 | 4.9528 | 4.9528 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.9466 | 1.9466 | 1.9466 | 1.9466 | 0.1242 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 167.23 | 84040.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 263.48 | 41835.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 127.24 | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.99 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 366.75 | 13633.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.39 | 4737.03 | 313.10 | 25906.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.53 | 1495.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.86 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 526.96 | 1432.25 |
Natural Gas | 469.79 | 950.11 |
Additional | 0.00 | 0.00 |
Total | 996.74 | 2382.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 248.92 |
Space Heating | 0.00 |
Space Cooling | 515.46 |
Fans (All) | 717.50 |
Service Water Heating | 147.48 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2801.99 |
Subtotal | 2801.99 |
Natural Gas [MJ/m2] | |
Space Heating | 327.15 |
Service Water Heating | 612.53 |
Miscellaneous (All) | 1858.76 |
Subtotal | 1858.76 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.34 |
Space Heating | 7.02 |
Space Cooling | 11.06 |
Fans (All) | 15.39 |
Service Water Heating | 16.31 |
Receptacle Equipment | 39.06 |
Miscellaneous | 5.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 6817. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8513.67 | 246.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7585.17 | 1159.83 | 15.00 | 0.00 | 0.00 |
ATTIC | 5876.83 | 876.67 | 693.00 | 973.33 | 340.17 |
Min | 5876.83 | 246.33 | 0.00 | 0.00 | 0.00 |
Max | 8513.67 | 1159.83 | 693.00 | 973.33 | 340.17 |
Average | 7325.22 | 760.94 | 236.00 | 324.44 | 113.39 |
Sum | 21975.67 | 2282.83 | 708.00 | 973.33 | 340.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 823403.00 | 819.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823403.00 | 819.00 | 0.00 | 0.00 | 0.00 |
Average | 280878.67 | 273.00 | 0.00 | 0.00 | 0.00 |
Sum | 842636.00 | 819.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8347.00 | 413.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 5403.33 | 3356.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 6101.83 | 1198.00 | 355.50 | 321.17 | 783.50 |
Min | 5403.33 | 413.00 | 0.00 | 0.00 | 0.00 |
Max | 8347.00 | 3356.67 | 355.50 | 321.17 | 783.50 |
Average | 6617.39 | 1655.89 | 118.50 | 107.06 | 261.17 |
Sum | 19852.17 | 4967.67 | 355.50 | 321.17 | 783.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 814438.33 | 9783.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12009.67 | 7223.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 814438.33 | 9783.67 | 0.00 | 0.00 | 0.00 |
Average | 275482.67 | 5669.00 | 0.00 | 0.00 | 0.00 |
Sum | 826448.00 | 17007.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242482E+11 | 44128.48 | 28-JAN-00:01 | -0.2 | -4.1 | 0.124837E+11 | 12937.19 | 03-JAN-12:00 | -0.2 | -4.1 |
February | 0.226087E+11 | 43616.35 | 03-FEB-00:01 | 0.00 | -4.1 | 0.118958E+11 | 13359.40 | 11-FEB-19:19 | 14.63 | 3.95 |
March | 0.264047E+11 | 43835.19 | 02-MAR-00:01 | -0.1 | -4.1 | 0.139808E+11 | 14051.38 | 25-MAR-18:10 | 18.62 | 7.41 |
April | 0.318339E+11 | 131107.18 | 15-APR-03:01 | 13.62 | 3.62 | 0.144337E+11 | 14051.39 | 08-APR-18:00 | 13.62 | 3.62 |
May | 0.386375E+11 | 133279.09 | 08-MAY-03:01 | 12.70 | 4.04 | 0.153395E+11 | 14051.72 | 13-MAY-18:00 | 30.00 | 14.69 |
June | 0.437483E+11 | 120184.07 | 12-JUN-03:01 | 17.38 | 6.37 | 0.150151E+11 | 14052.77 | 17-JUN-18:00 | 32.20 | 17.71 |
July | 0.449673E+11 | 84678.55 | 16-JUL-03:01 | 25.50 | 15.43 | 0.153340E+11 | 14051.46 | 08-JUL-18:10 | 25.50 | 15.43 |
August | 0.444567E+11 | 103569.91 | 23-AUG-03:01 | 21.83 | 12.04 | 0.155249E+11 | 14053.17 | 19-AUG-18:00 | 21.83 | 12.04 |
September | 0.409517E+11 | 119119.03 | 30-SEP-03:01 | 11.52 | 7.08 | 0.148326E+11 | 14052.00 | 30-SEP-18:00 | 21.70 | 10.59 |
October | 0.353446E+11 | 124258.32 | 31-OCT-03:01 | 13.43 | 6.06 | 0.148118E+11 | 14052.86 | 21-OCT-18:19 | 13.43 | 6.06 |
November | 0.275916E+11 | 97545.20 | 10-NOV-04:01 | 18.12 | 10.96 | 0.130013E+11 | 12941.45 | 08-NOV-12:00 | 18.12 | 10.96 |
December | 0.235349E+11 | 46399.78 | 28-DEC-00:01 | -1.1 | -2.7 | 0.123600E+11 | 12484.49 | 08-DEC-12:00 | -1.1 | -2.7 |
Annual Sum or Average | 0.404328E+12 | 0.169013E+12 | ||||||||
Minimum of Months | 0.226087E+11 | 43616.35 | -1.1 | -4.1 | 0.118958E+11 | 12484.49 | -1.1 | -4.1 | ||
Maximum of Months | 0.449673E+11 | 133279.09 | 25.50 | 15.43 | 0.155249E+11 | 14053.17 | 32.20 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265187E+11 | 85018.35 | 06-JAN-04:41 | 0.78 | -3.7 | 0.106026E+11 | 6934.78 | 02-JAN-11:09 | 0.78 | -3.7 |
February | 0.242504E+11 | 79964.84 | 22-FEB-04:11 | 3.70 | -1.3 | 0.957777E+10 | 6934.90 | 07-FEB-11:30 | 3.70 | -1.3 |
March | 0.277355E+11 | 82280.11 | 30-MAR-03:01 | 1.70 | -2.6 | 0.106088E+11 | 6934.91 | 06-MAR-11:50 | 1.70 | -2.6 |
April | 0.300942E+11 | 74640.49 | 12-APR-03:01 | 6.78 | 0.95 | 0.102630E+11 | 6934.94 | 26-APR-10:00 | 21.70 | 12.40 |
May | 0.337736E+11 | 67919.45 | 06-MAY-03:01 | 12.38 | 3.15 | 0.106060E+11 | 6935.00 | 16-MAY-10:00 | 27.80 | 12.11 |
June | 0.350968E+11 | 56909.96 | 12-JUN-03:01 | 17.38 | 6.37 | 0.102665E+11 | 6935.00 | 21-JUN-10:00 | 33.30 | 15.58 |
July | 0.367682E+11 | 43634.27 | 11-JUL-03:21 | 23.60 | 15.66 | 0.106028E+11 | 6941.29 | 21-JUL-10:00 | 25.60 | 22.26 |
August | 0.365601E+11 | 48032.63 | 23-AUG-01:22 | 23.30 | 12.45 | 0.106091E+11 | 6934.96 | 07-AUG-10:00 | 23.30 | 12.45 |
September | 0.344125E+11 | 58823.12 | 30-SEP-03:01 | 11.52 | 7.08 | 0.102632E+11 | 6934.98 | 29-SEP-10:00 | 11.52 | 7.08 |
October | 0.327097E+11 | 67025.48 | 24-OCT-03:31 | 9.40 | 5.20 | 0.106029E+11 | 6934.93 | 25-OCT-10:00 | 18.30 | 11.06 |
November | 0.280057E+11 | 85168.53 | 17-NOV-04:41 | -0.1 | -2.6 | 0.102603E+11 | 6934.98 | 10-NOV-11:50 | -0.1 | -2.6 |
December | 0.265562E+11 | 84504.50 | 07-DEC-04:01 | 0.10 | -3.0 | 0.106023E+11 | 6934.78 | 27-DEC-11:20 | 3.33 | 0.21 |
Annual Sum or Average | 0.372482E+12 | 0.124865E+12 | ||||||||
Minimum of Months | 0.242504E+11 | 43634.27 | -0.1 | -3.7 | 0.957777E+10 | 6934.78 | -0.1 | -3.7 | ||
Maximum of Months | 0.367682E+11 | 85168.53 | 23.60 | 15.66 | 0.106091E+11 | 6941.29 | 33.30 | 22.26 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6.70 | 3.92 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 | 1.84 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 | 2.41 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 | 8.41 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 | 11.56 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 | 17.07 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 | 17.18 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 | 8.67 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 | 5.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8.95 | 5.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.00 | 0.00 | 6.42 | 1.84 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.00 | 0.00 | 27.63 | 18.12 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54612573.74 | 32002.19 | 28-JAN-04:01 | -2.3 |
February | 55207690.97 | 29198.31 | 02-FEB-04:01 | -1.3 |
March | 17397445.93 | 31927.36 | 02-MAR-04:01 | -3.0 |
April | 56152806.12 | 64413.65 | 20-APR-03:47 | 19.82 |
May | 0.241660E+09 | 71579.86 | 14-MAY-03:46 | 20.28 |
June | 0.510592E+09 | 70707.52 | 12-JUN-03:47 | 18.12 |
July | 0.378742E+09 | 30431.27 | 02-JUL-23:01 | 33.48 |
August | 0.321056E+09 | 34860.15 | 27-AUG-03:44 | 19.97 |
September | 69846067.78 | 48494.54 | 11-SEP-03:47 | 16.97 |
October | 41266636.39 | 36876.45 | 31-OCT-03:02 | 13.43 |
November | 8657840.13 | 31518.88 | 28-NOV-04:01 | -0.6 |
December | 95043373.81 | 31126.47 | 27-DEC-04:01 | -1.6 |
Annual Sum or Average | 0.185023E+10 | |||
Minimum of Months | 8657840.13 | 29198.31 | -3.0 | |
Maximum of Months | 0.510592E+09 | 71579.86 | 33.48 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 20945.09 | 349.08 | 06-JUN-03:02 | 25.32 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8.95 |
Annual Sum or Average | 20945.09 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 20945.09 | 349.08 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826825E+10 | 4840.33 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.748896E+10 | 4840.33 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.839991E+10 | 4840.33 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.803398E+10 | 4840.33 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.833408E+10 | 4840.33 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.811917E+10 | 4840.33 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.824986E+10 | 4840.33 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.839991E+10 | 4840.33 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.803591E+10 | 4840.33 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.826728E+10 | 4840.33 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.800397E+10 | 4840.33 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.825082E+10 | 4840.33 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.978521E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.748896E+10 | 4840.33 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.839991E+10 | 4840.33 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.248296E+10 | 1453.55 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.224894E+10 | 1453.55 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.252250E+10 | 1453.55 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.241261E+10 | 1453.55 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.250273E+10 | 1453.55 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.243819E+10 | 1453.55 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.247744E+10 | 1453.55 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.252250E+10 | 1453.55 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.241319E+10 | 1453.55 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.248267E+10 | 1453.55 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.240360E+10 | 1453.55 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.247773E+10 | 1453.55 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.293850E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.224894E+10 | 1453.55 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.252250E+10 | 1453.55 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.826825E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834222E+10 |
February | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646902E+10 |
March | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4826322.37 | 0.583597E+10 |
April | 0.292871E+11 | 0.803398E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707024E+09 | 0.243651E+10 |
May | 0.303219E+11 | 0.833408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197819E+10 | 0.856872E+09 |
June | 0.295292E+11 | 0.811917E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390706E+10 | 0.231534E+09 |
July | 0.300798E+11 | 0.824986E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349948E+10 | 0.167849E+09 |
August | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287624E+10 | 0.420141E+09 |
September | 0.292871E+11 | 0.803591E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164849E+10 | 0.826932E+09 |
October | 0.300980E+11 | 0.826728E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348829E+09 | 0.299556E+10 |
November | 0.290996E+11 | 0.800397E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650312E+10 |
December | 0.300798E+11 | 0.825082E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920224E+10 |
Annual Sum or Average | 0.356244E+12 | 0.978521E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149701E+11 | 0.442880E+11 |
Minimum of Months | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167849E+09 |
Maximum of Months | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390706E+10 | 0.920224E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.248296E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449035E+09 |
February | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415803E+09 |
March | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416915E+09 |
April | 0.786997E+09 | 0.241261E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 9162367.22 | 0.252902E+09 |
May | 0.814802E+09 | 0.250273E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 30010088.42 | 0.157323E+09 |
June | 0.793501E+09 | 0.243819E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 60724275.27 | 68951723.98 |
July | 0.808298E+09 | 0.247744E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 44471691.00 | 55102591.55 |
August | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 33612045.03 | 69946694.05 |
September | 0.786997E+09 | 0.241319E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 9955456.35 | 68803870.91 |
October | 0.808786E+09 | 0.248267E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2928057.93 | 0.208073E+09 |
November | 0.781956E+09 | 0.240360E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350872E+09 |
December | 0.808298E+09 | 0.247773E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395301E+09 |
Annual Sum or Average | 0.957291E+10 | 0.293850E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.190864E+09 | 0.290903E+10 |
Minimum of Months | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55102591.55 |
Maximum of Months | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 60724275.27 | 0.449035E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797203E+09 | 0.276526E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761430E+09 | 0.286155E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792181E+09 | 0.380718E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806967E+09 | 0.448275E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798156E+09 | 0.473658E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703925E+09 | 0.525779E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548857E+09 | 0.526146E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647347E+09 | 0.497137E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858284E+09 | 0.465880E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810976E+09 | 0.358159E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877666E+09 | 0.293317E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110877E+10 | 0.271559E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951177E+10 | 0.480331E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548857E+09 | 0.271559E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110877E+10 | 0.526146E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 4840.33 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 10490.49 | 26-JAN-19:55 |
February | 30255.31 | 04-FEB-19:10 | 4840.33 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 10650.11 | 08-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 4840.33 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.89 | 22-MAR-13:00 | 11494.37 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 4840.33 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3699.22 | 21-APR-12:55 | 6706.90 | 10-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 4840.33 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5410.15 | 19-MAY-17:03 | 3936.76 | 06-MAY-06:05 |
June | 30255.31 | 03-JUN-18:10 | 4840.33 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7489.97 | 02-JUN-17:03 | 2057.55 | 29-JUN-06:20 |
July | 30255.31 | 01-JUL-18:10 | 4840.33 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7294.83 | 03-JUL-17:03 | 1840.10 | 05-JUL-06:10 |
August | 30255.31 | 05-AUG-18:10 | 4840.33 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6349.99 | 07-AUG-17:03 | 3140.74 | 16-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 4840.33 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4686.77 | 19-SEP-17:02 | 4558.10 | 30-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 4840.33 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3247.27 | 04-OCT-17:02 | 6279.12 | 23-OCT-18:55 |
November | 30255.31 | 04-NOV-18:10 | 4840.33 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9595.49 | 27-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 4840.33 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 11543.53 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.10 | |||||
Maximum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 7489.97 | 11543.53 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1453.55 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1715.97 | 26-JAN-01:10 |
February | 813.01 | 04-FEB-19:10 | 1453.55 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2128.18 | 09-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 1453.55 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1784.86 | 20-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 1453.55 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 136.99 | 21-APR-14:53 | 1820.96 | 11-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 1453.55 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 137.18 | 19-MAY-13:53 | 1249.90 | 04-MAY-01:50 |
June | 813.01 | 03-JUN-18:10 | 1453.55 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 170.44 | 10-JUN-00:20 | 876.55 | 28-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 1453.55 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 416.61 | 02-JUL-23:02 | 446.48 | 30-JUL-01:20 |
August | 813.01 | 05-AUG-18:10 | 1453.55 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 159.73 | 24-AUG-01:30 | 672.49 | 14-AUG-00:40 |
September | 813.01 | 02-SEP-18:10 | 1453.55 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 43.34 | 10-SEP-15:00 | 314.31 | 25-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 1453.55 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 138.84 | 02-OCT-00:47 | 896.65 | 24-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 1453.55 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1149.44 | 10-NOV-04:20 |
December | 813.01 | 02-DEC-19:10 | 1453.55 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1536.47 | 18-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 314.31 | ||||||
Maximum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 416.61 | 2128.18 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.48 | 02-JAN-07:55 | 5943.24 | 28-JAN-13:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.73 | 10-FEB-24:00 | 6495.23 | 09-FEB-12:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 31-MAR-04:55 | 7799.85 | 20-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.71 | 27-APR-05:40 | 8198.40 | 30-APR-12:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.80 | 21-MAY-01:52 | 7754.66 | 12-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.65 | 14-JUN-03:51 | 8056.71 | 29-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1653.87 | 01-JUL-05:30 | 7694.11 | 06-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.47 | 27-AUG-22:30 | 7783.16 | 03-AUG-12:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.87 | 17-SEP-23:55 | 7666.78 | 05-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1610.13 | 16-OCT-01:53 | 6575.14 | 08-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.38 | 23-NOV-01:00 | 6191.17 | 07-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.55 | 20-DEC-03:52 | 6243.63 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.47 | 5943.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.55 | 8198.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 44128.48 | 28-JAN-00:01 | 16808.50 | 10756.29 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 |
February | 43616.35 | 03-FEB-00:01 | 16808.50 | 8067.21 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.59 |
March | 43835.19 | 02-MAR-00:01 | 16808.50 | 8067.21 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.18 |
April | 131107.18 | 15-APR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.59 |
May | 133279.09 | 08-MAY-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 |
June | 120184.07 | 12-JUN-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 |
July | 84678.55 | 16-JUL-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
August | 103569.91 | 23-AUG-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.21 |
September | 119119.03 | 30-SEP-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.42 |
October | 124258.32 | 31-OCT-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.39 |
November | 97545.20 | 10-NOV-04:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.26 |
December | 46399.78 | 28-DEC-00:01 | 16808.50 | 8067.21 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 43616.35 | 0.00 | 7260.49 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 133279.09 | 16808.50 | 10756.29 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 683.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 85018.35 | 06-JAN-04:41 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 279.91 |
February | 79964.84 | 22-FEB-04:11 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 267.81 |
March | 82280.11 | 30-MAR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 |
April | 74640.49 | 12-APR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 191.87 |
May | 67919.45 | 06-MAY-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 283.60 |
June | 56909.96 | 12-JUN-03:01 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 114.46 |
July | 43634.27 | 11-JUL-03:21 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 114.09 |
August | 48032.63 | 23-AUG-01:22 | 0.00 | 1453.55 | 16315.42 | 4887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 |
September | 58823.12 | 30-SEP-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 115.99 |
October | 67025.48 | 24-OCT-03:31 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 383.45 |
November | 85168.53 | 17-NOV-04:41 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 |
December | 84504.50 | 07-DEC-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 43634.27 | 0.00 | 1453.55 | 16315.42 | 4887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85168.53 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 383.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.39 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.13 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.16 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.52 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.56 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.80 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.66 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.32 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.65 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.83 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.69 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.83 | 209.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.998040E+11 | 56943.32 | 03-JAN-17:10 | 0.110619E+12 | 111772.99 | 27-JAN-07:10 |
February | 0.911868E+11 | 58499.10 | 21-FEB-17:00 | 0.906375E+11 | 114868.25 | 02-FEB-07:30 |
March | 0.102671E+12 | 63363.24 | 22-MAR-11:00 | 0.893050E+11 | 103612.33 | 02-MAR-07:00 |
April | 0.113092E+12 | 75492.05 | 19-APR-18:40 | 0.692163E+11 | 71983.70 | 12-APR-06:10 |
May | 0.131805E+12 | 82146.39 | 19-MAY-11:00 | 0.659179E+11 | 43219.30 | 06-MAY-10:00 |
June | 0.143488E+12 | 88509.34 | 02-JUN-17:19 | 0.619869E+11 | 42947.15 | 03-JUN-10:30 |
July | 0.155126E+12 | 88039.27 | 03-JUL-17:19 | 0.627574E+11 | 42753.65 | 02-JUL-10:30 |
August | 0.147210E+12 | 86346.50 | 04-AUG-18:00 | 0.630226E+11 | 42732.50 | 27-AUG-10:39 |
September | 0.133097E+12 | 82919.88 | 15-SEP-11:00 | 0.620591E+11 | 45706.09 | 30-SEP-05:00 |
October | 0.116501E+12 | 82633.38 | 04-OCT-17:00 | 0.673737E+11 | 57165.57 | 25-OCT-06:10 |
November | 0.984929E+11 | 65109.74 | 09-NOV-17:10 | 0.877015E+11 | 88871.78 | 28-NOV-07:10 |
December | 0.997744E+11 | 51986.01 | 26-DEC-17:40 | 0.119513E+12 | 116448.20 | 27-DEC-07:49 |
Annual Sum or Average | 0.143225E+13 | 0.950110E+12 | ||||
Minimum of Months | 0.911868E+11 | 51986.01 | 0.619869E+11 | 42732.50 | ||
Maximum of Months | 0.155126E+12 | 88509.34 | 0.119513E+12 | 116448.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.107512E+11 | 0.707100E+10 | 0.391293E+11 | 0.00 | 0.306869E+11 | 37879553.69 | 0.00 | 0.154192E+09 | 0.00 | 0.00 | 0.00 | 0.637980E+10 | 0.00 |
February | 0.973789E+10 | 0.604909E+10 | 0.353426E+11 | 0.00 | 0.277720E+11 | 34213790.43 | 0.00 | 0.143533E+10 | 0.00 | 0.00 | 0.00 | 0.577401E+10 | 0.00 |
March | 0.109224E+11 | 0.621666E+10 | 0.391293E+11 | 0.00 | 0.308177E+11 | 37879553.69 | 0.00 | 0.351516E+10 | 0.00 | 0.00 | 0.00 | 0.644839E+10 | 0.00 |
April | 0.104466E+11 | 0.553264E+10 | 0.378671E+11 | 0.00 | 0.301839E+11 | 36657632.61 | 0.00 | 0.174190E+11 | 0.00 | 0.00 | 0.00 | 0.619294E+10 | 0.00 |
May | 0.108368E+11 | 0.530188E+10 | 0.391293E+11 | 0.00 | 0.313980E+11 | 37879553.69 | 0.00 | 0.330570E+11 | 0.00 | 0.00 | 0.00 | 0.641472E+10 | 0.00 |
June | 0.105574E+11 | 0.492278E+10 | 0.378671E+11 | 0.00 | 0.304503E+11 | 36657632.61 | 0.00 | 0.479380E+11 | 0.00 | 0.00 | 0.00 | 0.623618E+10 | 0.00 |
July | 0.107273E+11 | 0.517826E+10 | 0.391293E+11 | 0.00 | 0.315481E+11 | 37879553.69 | 0.00 | 0.564503E+11 | 0.00 | 0.00 | 0.00 | 0.637150E+10 | 0.00 |
August | 0.109224E+11 | 0.553264E+10 | 0.391293E+11 | 0.00 | 0.315129E+11 | 37879553.69 | 0.00 | 0.479402E+11 | 0.00 | 0.00 | 0.00 | 0.644968E+10 | 0.00 |
September | 0.104491E+11 | 0.580185E+10 | 0.378671E+11 | 0.00 | 0.304712E+11 | 36657632.61 | 0.00 | 0.367812E+11 | 0.00 | 0.00 | 0.00 | 0.619423E+10 | 0.00 |
October | 0.107500E+11 | 0.649961E+10 | 0.391293E+11 | 0.00 | 0.312908E+11 | 37879553.69 | 0.00 | 0.167781E+11 | 0.00 | 0.00 | 0.00 | 0.637818E+10 | 0.00 |
November | 0.104076E+11 | 0.671114E+10 | 0.378671E+11 | 0.00 | 0.299189E+11 | 36657632.61 | 0.00 | 0.196723E+10 | 0.00 | 0.00 | 0.00 | 0.617418E+10 | 0.00 |
December | 0.107286E+11 | 0.717539E+10 | 0.391293E+11 | 0.00 | 0.306997E+11 | 37879553.69 | 0.00 | 44124480.87 | 0.00 | 0.00 | 0.00 | 0.637178E+10 | 0.00 |
Annual Sum or Average | 0.127237E+12 | 0.719929E+11 | 0.460716E+12 | 0.00 | 0.366750E+12 | 0.446001E+09 | 0.00 | 0.263480E+12 | 0.00 | 0.00 | 0.00 | 0.753856E+11 | 0.00 |
Minimum of Months | 0.973789E+10 | 0.492278E+10 | 0.353426E+11 | 0.00 | 0.277720E+11 | 34213790.43 | 0.00 | 44124480.87 | 0.00 | 0.00 | 0.00 | 0.577401E+10 | 0.00 |
Maximum of Months | 0.109224E+11 | 0.717539E+10 | 0.391293E+11 | 0.00 | 0.315481E+11 | 37879553.69 | 0.00 | 0.564503E+11 | 0.00 | 0.00 | 0.00 | 0.644968E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.405066E+11 | 0.00 | 0.302131E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.272847E+11 | 0.00 | 0.273143E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.199094E+11 | 0.00 | 0.294959E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.390133E+10 | 0.00 | 0.267023E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.345929E+09 | 0.00 | 0.256723E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.119482E+09 | 0.00 | 0.232548E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 43963723.22 | 0.00 | 0.228138E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 69572496.04 | 0.00 | 0.230533E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.295284E+09 | 0.00 | 0.231512E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.190972E+10 | 0.00 | 0.255642E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.224283E+11 | 0.00 | 0.266606E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.504111E+11 | 0.00 | 0.292023E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.167225E+12 | 0.00 | 0.313098E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 43963723.22 | 0.00 | 0.228138E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.504111E+11 | 0.00 | 0.302131E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6293.88 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13633.26 | 01-JAN-19:49 | 17.86 | 02-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 6293.88 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13633.26 | 02-FEB-12:50 | 17.86 | 03-FEB-08:00 | 0.00 | 01-FEB-00:10 |
March | 6293.88 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13633.26 | 01-MAR-13:00 | 17.86 | 06-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 6293.88 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13633.26 | 01-APR-05:30 | 17.86 | 04-APR-09:09 | 0.00 | 01-APR-00:10 |
May | 6293.88 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13633.26 | 01-MAY-14:09 | 17.86 | 19-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 6293.88 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13633.26 | 04-JUN-04:30 | 17.86 | 02-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 6293.88 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13633.26 | 18-JUL-04:19 | 17.86 | 01-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 6293.88 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13633.26 | 02-AUG-04:00 | 17.86 | 05-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 6293.88 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13633.26 | 03-SEP-21:30 | 17.86 | 03-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 6293.88 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13633.26 | 03-OCT-22:30 | 17.86 | 01-OCT-08:00 | 0.00 | 01-OCT-00:10 |
November | 6293.88 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13633.26 | 02-NOV-07:49 | 17.86 | 16-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 6293.88 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13633.26 | 01-DEC-17:00 | 17.86 | 13-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13633.26 | 17.86 | 0.00 | ||||||
Maximum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13633.26 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5293.29 | 03-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4736.48 | 30-JAN-19:00 | 0.00 |
February | 11545.56 | 06-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4736.78 | 10-FEB-07:19 | 0.00 |
March | 15994.84 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4736.74 | 22-MAR-06:19 | 0.00 |
April | 27577.45 | 21-APR-12:00 | 0.00 | 0.00 | 0.00 | 4736.66 | 27-APR-06:19 | 0.00 |
May | 33999.87 | 19-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4737.01 | 15-MAY-18:30 | 0.00 |
June | 41835.16 | 02-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.75 | 12-JUN-06:49 | 0.00 |
July | 41320.51 | 03-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.88 | 21-JUL-18:30 | 0.00 |
August | 38518.95 | 07-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.88 | 03-AUG-18:30 | 0.00 |
September | 34769.29 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.64 | 22-SEP-18:30 | 0.00 |
October | 32759.55 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 4736.62 | 20-OCT-18:30 | 0.00 |
November | 15468.35 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4737.03 | 09-NOV-07:19 | 0.00 |
December | 2686.69 | 13-DEC-05:10 | 0.00 | 0.00 | 0.00 | 4736.95 | 04-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2686.69 | 0.00 | 0.00 | 0.00 | 4736.48 | 0.00 | ||
Maximum of Months | 41835.16 | 0.00 | 0.00 | 0.00 | 4737.03 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56943.32 | 03-JAN-17:10 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 4988.67 | 0.00 |
February | 58499.10 | 21-FEB-17:00 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 6671.96 | 0.00 |
March | 63363.24 | 22-MAR-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 15271.25 | 0.00 |
April | 75492.05 | 19-APR-18:40 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 25133.17 | 0.00 |
May | 82146.39 | 19-MAY-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 33999.87 | 0.00 |
June | 88509.34 | 02-JUN-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 41383.38 | 0.00 |
July | 88039.27 | 03-JUL-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 40923.52 | 0.00 |
August | 86346.50 | 04-AUG-18:00 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 35958.75 | 0.00 |
September | 82919.88 | 15-SEP-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 34769.29 | 0.00 |
October | 82633.38 | 04-OCT-17:00 | 6293.88 | 20676.91 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 31099.35 | 0.00 |
November | 65109.74 | 09-NOV-17:10 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 13132.49 | 0.00 |
December | 51986.01 | 26-DEC-17:40 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 51986.01 | 6293.88 | 19067.80 | 0.00 | 0.00 | 13633.26 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88509.34 | 6293.88 | 23090.58 | 4578.48 | 0.00 | 13633.26 | 17.86 | 0.00 | 41383.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 79287.77 | 27-JAN-07:10 | 0.00 | 25906.46 | 30-JAN-07:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 84040.00 | 03-FEB-06:00 | 0.00 | 25897.30 | 02-FEB-07:30 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 76902.66 | 02-MAR-05:10 | 0.00 | 24848.10 | 03-MAR-07:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 44944.81 | 12-APR-05:00 | 0.00 | 21482.28 | 07-APR-06:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 28141.02 | 11-MAY-03:49 | 0.00 | 17800.77 | 01-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 30311.49 | 12-JUN-03:49 | 0.00 | 17402.80 | 01-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 10168.16 | 14-JUL-03:49 | 0.00 | 17099.47 | 03-JUL-06:30 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 14058.47 | 30-AUG-03:49 | 0.00 | 17117.67 | 31-AUG-06:49 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 21829.60 | 11-SEP-03:49 | 0.00 | 17391.22 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 29786.13 | 25-OCT-05:00 | 0.00 | 17809.99 | 31-OCT-18:00 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 63287.85 | 28-NOV-05:10 | 0.00 | 22083.40 | 29-NOV-07:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 80140.51 | 27-DEC-07:10 | 0.00 | 24918.42 | 29-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 10168.16 | 0.00 | 17099.47 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 84040.00 | 0.00 | 25906.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.61 | 0.00 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.81 | 0.00 | 24.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.06 | 0.00 | 25.06 |
July | 0.17 | 20.36 | 0.00 | 20.36 | 4.00 | 24.84 | 0.00 | 24.84 |
August | 0.17 | 20.41 | 0.00 | 20.41 | 3.00 | 24.77 | 0.00 | 24.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.87 | 0.00 | 24.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.83 | 0.00 | 24.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.38 | 0.00 | 20.38 | 18.17 | 24.86 | 0.00 | 24.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.41 | 0.00 | 20.41 | 4.00 | 25.06 | 0.00 | 25.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.63 | 0.00 | 28.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 29.03 | 0.00 | 29.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 29.15 | 0.00 | 29.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 30.44 | 0.00 | 30.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 30.65 | 0.17 | 30.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 30.70 | 0.33 | 30.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 30.87 | 0.50 | 30.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 30.86 | 0.17 | 30.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 30.93 | 0.00 | 30.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 30.60 | 0.00 | 30.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 29.93 | 0.00 | 29.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.59 | 0.00 | 28.59 |
Annual Sum or Average | 0.00 | 0.00 | 236.17 | 30.49 | 1.17 | 30.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.59 | 0.00 | 28.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 30.93 | 0.50 | 30.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 586.00 | 21.03 | 63.33 | 20.84 | 63.17 | 20.68 |
February | 463.83 | 21.30 | 47.33 | 21.12 | 45.83 | 20.97 |
March | 424.83 | 21.44 | 31.50 | 21.28 | 31.50 | 21.14 |
April | 179.33 | 21.90 | 184.33 | 22.93 | 3.00 | 22.89 |
May | 53.00 | 22.55 | 430.83 | 23.94 | 1.50 | 23.95 |
June | 27.00 | 26.43 | 553.67 | 24.30 | 21.67 | 24.40 |
July | 199.00 | 24.50 | 609.00 | 24.25 | 199.00 | 24.30 |
August | 94.00 | 24.66 | 611.83 | 24.21 | 94.00 | 24.26 |
September | 124.33 | 23.70 | 548.33 | 23.98 | 100.17 | 24.00 |
October | 189.17 | 21.95 | 391.50 | 23.32 | 32.33 | 23.35 |
November | 426.00 | 21.20 | 76.83 | 21.32 | 25.00 | 21.16 |
December | 600.83 | 21.04 | 77.67 | 20.83 | 77.67 | 20.67 |
Annual Sum or Average | 3367.33 | 21.71 | 3626.17 | 22.78 | 694.83 | 22.76 |
Minimum of Months | 27.00 | 21.03 | 31.50 | 20.83 | 1.50 | 20.67 |
Maximum of Months | 600.83 | 26.43 | 611.83 | 24.30 | 199.00 | 24.40 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.00 | 25.99 | 610.00 | 25.99 | 365.00 | 25.99 |
February | 314.83 | 25.99 | 551.00 | 25.99 | 314.83 | 25.99 |
March | 365.17 | 25.99 | 612.00 | 25.99 | 365.17 | 25.99 |
April | 404.00 | 26.00 | 590.00 | 26.00 | 404.00 | 26.00 |
May | 506.83 | 26.00 | 611.00 | 26.00 | 506.83 | 26.00 |
June | 568.67 | 26.00 | 592.00 | 26.00 | 568.67 | 26.00 |
July | 609.00 | 26.00 | 609.00 | 26.00 | 609.00 | 26.00 |
August | 612.00 | 26.00 | 612.00 | 26.00 | 612.00 | 26.00 |
September | 579.33 | 26.00 | 590.00 | 26.00 | 579.33 | 26.00 |
October | 544.00 | 26.00 | 610.00 | 26.00 | 544.00 | 26.00 |
November | 401.67 | 25.99 | 591.00 | 25.99 | 401.67 | 25.99 |
December | 355.83 | 25.99 | 609.00 | 25.99 | 355.83 | 25.99 |
Annual Sum or Average | 5626.33 | 26.00 | 7187.00 | 26.00 | 5626.33 | 26.00 |
Minimum of Months | 314.83 | 25.99 | 551.00 | 25.99 | 314.83 | 25.99 |
Maximum of Months | 612.00 | 26.00 | 612.00 | 26.00 | 612.00 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.14864 | 24.81275 | -0.3199 | 8.73040 |
February | 551.00000 | 21.72174 | 21.24859 | -0.2043 | 8.12486 |
March | 612.00000 | 22.21558 | 19.84018 | -0.0894 | 7.68601 |
April | 590.00000 | 23.37226 | 21.99488 | 0.24032 | 7.96315 |
May | 611.00000 | 23.93419 | 30.18246 | -0.3677 | 9.17565 |
June | 592.00000 | 24.17590 | 34.92532 | -0.2009 | 6.62186 |
July | 609.00000 | 24.17246 | 51.88307 | -0.0752 | 5.69642 |
August | 612.00000 | 24.14354 | 46.36602 | -0.1218 | 5.87833 |
September | 590.00000 | 23.93312 | 45.36571 | -0.2011 | 6.95258 |
October | 610.00000 | 23.31226 | 39.54155 | 0.37873 | 9.74953 |
November | 591.00000 | 21.95591 | 25.68193 | -0.0816 | 7.91916 |
December | 609.00000 | 21.07901 | 21.56287 | -0.3555 | 9.12746 |
Annual Sum or Average | 7187.00000 | 22.93611 | 32.03686 | -0.1164 | 7.80376 |
Minimum of Months | 551.00000 | 21.07901 | 19.84018 | -0.3677 | 5.69642 |
Maximum of Months | 612.00000 | 24.17590 | 51.88307 | 0.37873 | 9.74953 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.99222 | 30.33890 | 0.96540 | 24.97812 |
February | 551.00000 | 25.99357 | 26.84596 | 0.94917 | 24.29751 |
March | 612.00000 | 25.99493 | 24.78460 | 0.95502 | 24.54281 |
April | 590.00000 | 25.99796 | 28.59560 | 1.05977 | 29.27681 |
May | 611.00000 | 26.00021 | 37.25135 | 0.61500 | 14.12263 |
June | 592.00000 | 26.00242 | 44.95250 | 0.73940 | 17.40042 |
July | 609.00000 | 26.00257 | 52.22580 | 0.81313 | 19.42352 |
August | 612.00000 | 26.00204 | 49.24231 | 0.78032 | 18.42673 |
September | 590.00000 | 26.00112 | 47.41968 | 0.74546 | 17.42395 |
October | 610.00000 | 25.99835 | 39.18320 | 1.17194 | 34.19225 |
November | 591.00000 | 25.99379 | 29.06509 | 1.01306 | 26.97781 |
December | 609.00000 | 25.99190 | 29.12377 | 0.95551 | 24.56935 |
Annual Sum or Average | 7187.00000 | 25.99761 | 36.65589 | 0.89651 | 22.95787 |
Minimum of Months | 551.00000 | 25.99190 | 24.78460 | 0.61500 | 14.12263 |
Maximum of Months | 612.00000 | 26.00257 | 52.22580 | 1.17194 | 34.19225 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.177036E+09 | 63668507.04 | 10.00 | 0.173410E+09 | 3626194.02 | 0.00 | 0.12 | 03-JAN-14:00 | 0.00 | 01-JAN-00:01 | 10586.64 | 03-JAN-14:00 | 10399.55 | 03-JAN-14:00 | 529.92 | 12-JAN-14:00 | 3766.49 | 03-JAN-14:00 | 0.00 | 01-JAN-00:01 |
February | 0.251316E+10 | 0.886906E+09 | 70.58 | 0.250839E+10 | 4769426.56 | 0.00 | 0.25 | 06-FEB-14:00 | 0.00 | 01-FEB-00:01 | 23305.20 | 06-FEB-14:00 | 23305.20 | 06-FEB-14:00 | 395.45 | 07-FEB-14:00 | 8037.10 | 06-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.646753E+10 | 0.226486E+10 | 151.50 | 0.646547E+10 | 2061339.33 | 0.00 | 0.34 | 22-MAR-13:00 | 0.00 | 01-MAR-00:01 | 32602.41 | 22-MAR-13:00 | 32602.41 | 22-MAR-13:00 | 152.81 | 03-MAR-18:20 | 10996.77 | 22-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.343555E+11 | 0.115708E+11 | 352.12 | 0.336895E+11 | 0.666051E+09 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 116220.97 | 02-APR-03:01 | 116220.97 | 21-APR-03:18 | 34176.88 | 30-APR-03:01 | 32742.43 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.669910E+11 | 0.223194E+11 | 505.79 | 0.630349E+11 | 0.395616E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 116220.97 | 01-MAY-03:01 | 116220.97 | 09-MAY-03:01 | 50358.87 | 25-MAY-03:01 | 32742.43 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.983806E+11 | 0.332687E+11 | 559.48 | 0.907506E+11 | 0.763001E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 116220.97 | 05-JUN-03:25 | 116220.97 | 01-JUN-03:41 | 58395.73 | 28-JUN-03:01 | 32946.99 | 15-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.123150E+12 | 0.394713E+11 | 599.21 | 0.907838E+11 | 0.323663E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 127145.00 | 21-JUL-03:01 | 107306.30 | 03-JUL-03:01 | 82658.65 | 21-JUL-03:01 | 33605.72 | 21-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.101568E+12 | 0.331504E+11 | 575.26 | 0.816887E+11 | 0.198794E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 124376.95 | 02-AUG-03:01 | 108230.37 | 23-AUG-03:01 | 64463.68 | 02-AUG-03:01 | 33382.15 | 02-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.780762E+11 | 0.253095E+11 | 488.64 | 0.615064E+11 | 0.165698E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 122020.16 | 22-SEP-03:01 | 95313.22 | 29-SEP-03:01 | 68219.31 | 22-SEP-03:11 | 33197.21 | 22-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.341683E+11 | 0.113709E+11 | 337.01 | 0.280005E+11 | 0.616773E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 119010.81 | 04-OCT-03:01 | 110438.44 | 02-OCT-03:01 | 62080.67 | 04-OCT-03:01 | 32962.75 | 04-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.363180E+10 | 0.127043E+10 | 90.72 | 0.337475E+10 | 0.257049E+09 | 0.00 | 1.00 | 10-NOV-04:01 | 0.00 | 01-NOV-00:01 | 116220.97 | 10-NOV-04:01 | 96278.01 | 10-NOV-04:01 | 19942.96 | 10-NOV-04:01 | 32742.43 | 10-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 292.38 | 106.84 | 0.08 | 292.38 | 0.00 | 0.00 | 0.00 | 09-DEC-14:10 | 0.00 | 01-DEC-00:02 | 0.97 | 09-DEC-14:10 | 0.97 | 09-DEC-14:10 | 0.00 | 01-DEC-00:02 | 0.36 | 09-DEC-14:10 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.549479E+12 | 0.180947E+12 | 3740.39 | 0.461976E+12 | 0.875030E+11 | 0.00 | ||||||||||||||
Minimum of Months | 292.38 | 106.84 | 0.08 | 292.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.97 | 0.00 | 0.36 | 0.00 | |||||||
Maximum of Months | 0.123150E+12 | 0.394713E+11 | 599.21 | 0.907838E+11 | 0.323663E+11 | 0.00 | 1.00 | 0.00 | 127145.00 | 116220.97 | 82658.65 | 33605.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.274573E+09 | 90523486.04 | 18.72 | 0.246161E+09 | 28411618.57 | 0.00 | 1.00 | 01-JAN-04:01 | 0.00 | 01-JAN-00:01 | 41647.26 | 06-JAN-04:41 | 39577.93 | 01-JAN-04:01 | 20986.77 | 16-JAN-04:01 | 11496.30 | 01-JAN-04:01 | 0.00 | 01-JAN-00:01 |
February | 0.162310E+10 | 0.548421E+09 | 83.64 | 0.160551E+10 | 17594979.42 | 0.00 | 1.00 | 06-FEB-04:01 | 0.00 | 01-FEB-00:01 | 41647.26 | 06-FEB-04:41 | 39959.34 | 07-FEB-04:41 | 17989.74 | 27-FEB-04:01 | 11496.30 | 06-FEB-04:01 | 0.00 | 01-FEB-00:01 |
March | 0.372601E+10 | 0.125030E+10 | 165.63 | 0.371192E+10 | 14095811.76 | 0.00 | 1.00 | 03-MAR-04:01 | 0.00 | 01-MAR-00:01 | 41647.26 | 05-MAR-04:11 | 41647.26 | 10-MAR-04:01 | 18379.95 | 11-MAR-04:01 | 11496.30 | 03-MAR-04:01 | 0.00 | 01-MAR-00:01 |
April | 0.185369E+11 | 0.584817E+10 | 360.61 | 0.162915E+11 | 0.224534E+10 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 41647.26 | 02-APR-03:31 | 41647.26 | 03-APR-03:01 | 14989.92 | 30-APR-03:31 | 11496.30 | 01-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.345787E+11 | 0.107376E+11 | 520.80 | 0.281200E+11 | 0.645872E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 41647.26 | 01-MAY-03:01 | 41647.26 | 03-MAY-03:01 | 20033.57 | 25-MAY-03:31 | 11496.30 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.463483E+11 | 0.146692E+11 | 597.49 | 0.361827E+11 | 0.101656E+11 | 0.00 | 1.00 | 01-JUN-02:62 | 0.00 | 01-JUN-00:01 | 41647.26 | 22-JUN-01:22 | 41647.26 | 01-JUN-03:43 | 23065.01 | 28-JUN-03:21 | 11704.82 | 15-JUN-02:62 | 0.00 | 01-JUN-00:01 |
July | 0.560236E+11 | 0.169790E+11 | 636.18 | 0.378988E+11 | 0.181247E+11 | 0.00 | 1.00 | 01-JUL-00:20 | 0.00 | 01-JUL-00:01 | 46272.85 | 21-JUL-10:42 | 41521.73 | 26-JUL-00:12 | 31372.42 | 21-JUL-03:01 | 11858.36 | 20-JUL-15:01 | 0.00 | 01-JUL-00:01 |
August | 0.482990E+11 | 0.147898E+11 | 605.86 | 0.346600E+11 | 0.136390E+11 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 44252.51 | 02-AUG-03:43 | 41647.26 | 24-AUG-00:42 | 25850.53 | 14-AUG-03:01 | 11696.38 | 02-AUG-03:43 | 0.00 | 01-AUG-00:01 |
September | 0.378933E+11 | 0.114717E+11 | 501.75 | 0.272492E+11 | 0.106441E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 43768.94 | 22-SEP-04:02 | 33622.53 | 11-SEP-02:62 | 27933.83 | 22-SEP-03:01 | 11659.31 | 22-SEP-04:02 | 0.00 | 01-SEP-00:01 |
October | 0.172016E+11 | 0.540723E+10 | 345.79 | 0.136371E+11 | 0.356453E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 41880.55 | 04-OCT-03:01 | 41647.26 | 02-OCT-01:06 | 23976.22 | 04-OCT-03:01 | 11514.52 | 04-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.207509E+10 | 0.696803E+09 | 110.87 | 0.195184E+10 | 0.123243E+09 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 41647.26 | 04-NOV-03:11 | 41647.26 | 24-NOV-04:41 | 20796.25 | 03-NOV-03:01 | 11496.30 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.138331E+09 | 44124374.03 | 8.27 | 0.123186E+09 | 15144615.93 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:02 | 41647.26 | 11-DEC-04:01 | 41042.41 | 18-DEC-04:01 | 13621.88 | 14-DEC-04:01 | 11496.30 | 01-DEC-04:01 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.266718E+12 | 0.825329E+11 | 3955.60 | 0.201678E+12 | 0.650404E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.138331E+09 | 44124374.03 | 8.27 | 0.123186E+09 | 14095811.76 | 0.00 | 1.00 | 0.00 | 41647.26 | 33622.53 | 13621.88 | 11496.30 | 0.00 | |||||||
Maximum of Months | 0.560236E+11 | 0.169790E+11 | 636.18 | 0.378988E+11 | 0.181247E+11 | 0.00 | 1.00 | 0.00 | 46272.85 | 41647.26 | 31372.42 | 11858.36 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.72 | 87.67 | 74.05 | 149.63 | 405.45 | 0.00 | 0.00 | 0.00 |
February | 216.90 | 123.67 | 93.24 | 242.35 | 357.39 | 0.00 | 0.00 | 0.00 |
March | 267.28 | 147.12 | 120.16 | 330.30 | 299.27 | 0.00 | 0.00 | 0.00 |
April | 322.16 | 178.60 | 143.56 | 493.24 | 181.55 | 0.00 | 0.00 | 0.00 |
May | 332.13 | 180.35 | 151.77 | 583.47 | 114.28 | 0.00 | 0.00 | 0.00 |
June | 332.31 | 184.73 | 147.58 | 679.14 | 64.82 | 0.00 | 0.00 | 0.00 |
July | 298.19 | 155.84 | 142.35 | 612.23 | 53.59 | 0.00 | 0.00 | 0.00 |
August | 284.06 | 145.41 | 138.65 | 554.32 | 74.14 | 0.00 | 0.00 | 0.00 |
September | 281.77 | 160.84 | 120.94 | 505.08 | 130.76 | 0.00 | 0.00 | 0.00 |
October | 215.77 | 116.21 | 99.55 | 311.85 | 214.30 | 0.00 | 0.00 | 0.00 |
November | 193.24 | 112.25 | 80.99 | 209.73 | 347.76 | 0.00 | 0.00 | 0.00 |
December | 161.85 | 85.81 | 76.04 | 140.72 | 445.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.64 | 139.80 | 115.84 | 401.53 | 223.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.72 | 85.81 | 74.05 | 140.72 | 53.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.31 | 184.73 | 151.77 | 679.14 | 445.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 572.71 | 433.74 | 138.97 | 797.87 | 528.76 | 0.00 | 0.00 | 0.00 |
February | 539.44 | 382.50 | 156.94 | 763.12 | 479.44 | 0.00 | 0.00 | 0.00 |
March | 423.27 | 240.28 | 182.99 | 604.63 | 428.58 | 0.00 | 0.00 | 0.00 |
April | 295.79 | 112.05 | 183.74 | 479.90 | 277.56 | 0.00 | 0.00 | 0.00 |
May | 209.73 | 31.59 | 178.14 | 386.02 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 179.10 | 11.78 | 167.32 | 427.86 | 95.03 | 0.00 | 0.00 | 0.00 |
July | 181.96 | 16.71 | 165.25 | 433.47 | 78.00 | 0.00 | 0.00 | 0.00 |
August | 230.12 | 59.38 | 170.74 | 505.18 | 109.63 | 0.00 | 0.00 | 0.00 |
September | 363.97 | 189.81 | 174.16 | 721.40 | 193.89 | 0.00 | 0.00 | 0.00 |
October | 497.87 | 338.36 | 159.52 | 825.05 | 296.20 | 0.00 | 0.00 | 0.00 |
November | 598.17 | 457.37 | 140.80 | 871.46 | 459.52 | 0.00 | 0.00 | 0.00 |
December | 587.87 | 441.40 | 146.46 | 797.72 | 571.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 389.11 | 225.33 | 163.78 | 633.52 | 306.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.10 | 11.78 | 138.97 | 386.02 | 78.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 598.17 | 457.37 | 183.74 | 871.46 | 571.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.74 | 96.26 | 74.48 | 182.75 | 424.70 | 0.00 | 0.00 | 0.00 |
February | 192.17 | 101.98 | 90.19 | 220.51 | 383.17 | 0.00 | 0.00 | 0.00 |
March | 262.06 | 140.47 | 121.60 | 336.72 | 321.19 | 0.00 | 0.00 | 0.00 |
April | 300.72 | 162.15 | 138.57 | 466.81 | 197.80 | 0.00 | 0.00 | 0.00 |
May | 324.54 | 173.62 | 150.92 | 576.40 | 124.14 | 0.00 | 0.00 | 0.00 |
June | 315.85 | 169.55 | 146.29 | 651.22 | 68.47 | 0.00 | 0.00 | 0.00 |
July | 280.50 | 139.34 | 141.16 | 581.52 | 55.60 | 0.00 | 0.00 | 0.00 |
August | 271.57 | 138.31 | 133.26 | 534.15 | 78.75 | 0.00 | 0.00 | 0.00 |
September | 278.77 | 155.56 | 123.20 | 513.14 | 141.93 | 0.00 | 0.00 | 0.00 |
October | 240.23 | 140.61 | 99.62 | 368.38 | 224.20 | 0.00 | 0.00 | 0.00 |
November | 200.52 | 122.01 | 78.51 | 243.42 | 369.32 | 0.00 | 0.00 | 0.00 |
December | 161.78 | 87.87 | 73.91 | 160.68 | 469.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 250.17 | 135.74 | 114.43 | 403.75 | 237.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.78 | 87.87 | 73.91 | 160.68 | 55.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.54 | 173.62 | 150.92 | 651.22 | 469.93 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.433151E+09 | 0.234807E+09 | 0.198344E+09 | 0.400780E+09 | 0.108596E+10 |
February | 0.524729E+09 | 0.299173E+09 | 0.225557E+09 | 0.586303E+09 | 0.864586E+09 |
March | 0.715889E+09 | 0.394046E+09 | 0.321843E+09 | 0.884663E+09 | 0.801561E+09 |
April | 0.835038E+09 | 0.462932E+09 | 0.372106E+09 | 0.127847E+10 | 0.470565E+09 |
May | 0.889572E+09 | 0.483062E+09 | 0.406511E+09 | 0.156275E+10 | 0.306080E+09 |
June | 0.861349E+09 | 0.478815E+09 | 0.382534E+09 | 0.176034E+10 | 0.168025E+09 |
July | 0.798665E+09 | 0.417389E+09 | 0.381276E+09 | 0.163980E+10 | 0.143531E+09 |
August | 0.760824E+09 | 0.389460E+09 | 0.371364E+09 | 0.148469E+10 | 0.198570E+09 |
September | 0.730358E+09 | 0.416888E+09 | 0.313470E+09 | 0.130918E+10 | 0.338929E+09 |
October | 0.577906E+09 | 0.311258E+09 | 0.266648E+09 | 0.835257E+09 | 0.573978E+09 |
November | 0.500881E+09 | 0.290951E+09 | 0.209930E+09 | 0.543632E+09 | 0.901390E+09 |
December | 0.433504E+09 | 0.229837E+09 | 0.203668E+09 | 0.376897E+09 | 0.119301E+10 |
Annual Sum or Average | 0.806187E+10 | 0.440862E+10 | 0.365325E+10 | 0.126628E+11 | 0.704618E+10 |
Minimum of Months | 0.433151E+09 | 0.229837E+09 | 0.198344E+09 | 0.376897E+09 | 0.143531E+09 |
Maximum of Months | 0.889572E+09 | 0.483062E+09 | 0.406511E+09 | 0.176034E+10 | 0.119301E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153394E+10 | 0.116173E+10 | 0.372210E+09 | 0.213701E+10 | 0.141623E+10 |
February | 0.130501E+10 | 0.925338E+09 | 0.379671E+09 | 0.184614E+10 | 0.115986E+10 |
March | 0.113369E+10 | 0.643560E+09 | 0.490131E+09 | 0.161944E+10 | 0.114792E+10 |
April | 0.766688E+09 | 0.290422E+09 | 0.476266E+09 | 0.124391E+10 | 0.719432E+09 |
May | 0.561737E+09 | 84602673.36 | 0.477134E+09 | 0.103393E+10 | 0.463807E+09 |
June | 0.464219E+09 | 30523046.33 | 0.433696E+09 | 0.110900E+10 | 0.246330E+09 |
July | 0.487367E+09 | 44757428.53 | 0.442610E+09 | 0.116100E+10 | 0.208910E+09 |
August | 0.616358E+09 | 0.159043E+09 | 0.457315E+09 | 0.135308E+10 | 0.293634E+09 |
September | 0.943408E+09 | 0.491993E+09 | 0.451415E+09 | 0.186987E+10 | 0.502567E+09 |
October | 0.133350E+10 | 0.906251E+09 | 0.427248E+09 | 0.220983E+10 | 0.793334E+09 |
November | 0.155046E+10 | 0.118551E+10 | 0.364946E+09 | 0.225884E+10 | 0.119108E+10 |
December | 0.157454E+10 | 0.118225E+10 | 0.392285E+09 | 0.213661E+10 | 0.153150E+10 |
Annual Sum or Average | 0.122709E+11 | 0.710598E+10 | 0.516493E+10 | 0.199787E+11 | 0.967460E+10 |
Minimum of Months | 0.464219E+09 | 30523046.33 | 0.364946E+09 | 0.103393E+10 | 0.208910E+09 |
Maximum of Months | 0.157454E+10 | 0.118551E+10 | 0.490131E+09 | 0.225884E+10 | 0.153150E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.457322E+09 | 0.257826E+09 | 0.199495E+09 | 0.489473E+09 | 0.113750E+10 |
February | 0.464890E+09 | 0.246714E+09 | 0.218177E+09 | 0.533467E+09 | 0.926968E+09 |
March | 0.701908E+09 | 0.376225E+09 | 0.325682E+09 | 0.901860E+09 | 0.860265E+09 |
April | 0.779467E+09 | 0.420284E+09 | 0.359184E+09 | 0.120998E+10 | 0.512690E+09 |
May | 0.869251E+09 | 0.465026E+09 | 0.404225E+09 | 0.154382E+10 | 0.332504E+09 |
June | 0.818671E+09 | 0.439483E+09 | 0.379189E+09 | 0.168796E+10 | 0.177465E+09 |
July | 0.751290E+09 | 0.373206E+09 | 0.378084E+09 | 0.155754E+10 | 0.148922E+09 |
August | 0.727383E+09 | 0.370460E+09 | 0.356923E+09 | 0.143067E+10 | 0.210924E+09 |
September | 0.722563E+09 | 0.403216E+09 | 0.319346E+09 | 0.133006E+10 | 0.367872E+09 |
October | 0.643428E+09 | 0.376600E+09 | 0.266828E+09 | 0.986659E+09 | 0.600499E+09 |
November | 0.519742E+09 | 0.316247E+09 | 0.203495E+09 | 0.630955E+09 | 0.957278E+09 |
December | 0.433316E+09 | 0.235344E+09 | 0.197971E+09 | 0.430367E+09 | 0.125867E+10 |
Annual Sum or Average | 0.788923E+10 | 0.428063E+10 | 0.360860E+10 | 0.127328E+11 | 0.749156E+10 |
Minimum of Months | 0.433316E+09 | 0.235344E+09 | 0.197971E+09 | 0.430367E+09 | 0.148922E+09 |
Maximum of Months | 0.869251E+09 | 0.465026E+09 | 0.404225E+09 | 0.168796E+10 | 0.125867E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1063.01 | 1291.66 | 905.17 | 617.67 | 287.50 | 0.00 | 0.00 |
February | 1163.55 | 1157.56 | 948.51 | 608.14 | 340.36 | 0.00 | 0.00 |
March | 1211.96 | 989.36 | 952.62 | 527.86 | 424.75 | 0.00 | 0.00 |
April | 1394.02 | 610.97 | 918.67 | 452.79 | 465.88 | 0.00 | 0.00 |
May | 1524.53 | 390.23 | 866.40 | 385.56 | 480.84 | 0.00 | 0.00 |
June | 1751.28 | 221.39 | 827.25 | 366.06 | 461.20 | 0.00 | 0.00 |
July | 1621.04 | 181.01 | 760.65 | 311.89 | 448.76 | 0.00 | 0.00 |
August | 1584.68 | 253.54 | 785.75 | 343.10 | 442.65 | 0.00 | 0.00 |
September | 1718.40 | 445.35 | 924.51 | 506.21 | 418.30 | 0.00 | 0.00 |
October | 1484.43 | 713.85 | 953.87 | 595.17 | 358.69 | 0.00 | 0.00 |
November | 1268.13 | 1120.11 | 991.93 | 691.63 | 300.30 | 0.00 | 0.00 |
December | 1013.93 | 1401.95 | 911.50 | 615.08 | 296.42 | 0.00 | 0.00 |
Annual Sum or Average | 1400.40 | 729.36 | 894.91 | 500.86 | 394.05 | 0.00 | 0.00 |
Minimum of Months | 1013.93 | 181.01 | 760.65 | 311.89 | 287.50 | 0.00 | 0.00 |
Maximum of Months | 1751.28 | 1401.95 | 991.93 | 691.63 | 480.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.284716E+10 | 0.345958E+10 | 0.242441E+10 | 0.165436E+10 | 0.770049E+09 | 0.00 | 0.00 |
February | 0.281486E+10 | 0.280036E+10 | 0.229463E+10 | 0.147122E+10 | 0.823404E+09 | 0.00 | 0.00 |
March | 0.324611E+10 | 0.264989E+10 | 0.255149E+10 | 0.141383E+10 | 0.113766E+10 | 0.00 | 0.00 |
April | 0.361331E+10 | 0.158364E+10 | 0.238119E+10 | 0.117364E+10 | 0.120756E+10 | 0.00 | 0.00 |
May | 0.408330E+10 | 0.104519E+10 | 0.232056E+10 | 0.103269E+10 | 0.128787E+10 | 0.00 | 0.00 |
June | 0.453932E+10 | 0.573847E+09 | 0.214424E+10 | 0.948820E+09 | 0.119542E+10 | 0.00 | 0.00 |
July | 0.434180E+10 | 0.484822E+09 | 0.203732E+10 | 0.835353E+09 | 0.120197E+10 | 0.00 | 0.00 |
August | 0.424440E+10 | 0.679090E+09 | 0.210456E+10 | 0.918963E+09 | 0.118560E+10 | 0.00 | 0.00 |
September | 0.445409E+10 | 0.115434E+10 | 0.239633E+10 | 0.131210E+10 | 0.108423E+10 | 0.00 | 0.00 |
October | 0.397591E+10 | 0.191198E+10 | 0.255483E+10 | 0.159411E+10 | 0.960724E+09 | 0.00 | 0.00 |
November | 0.328699E+10 | 0.290332E+10 | 0.257108E+10 | 0.179271E+10 | 0.778371E+09 | 0.00 | 0.00 |
December | 0.271570E+10 | 0.375499E+10 | 0.244136E+10 | 0.164743E+10 | 0.793924E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.441629E+11 | 0.230011E+11 | 0.282220E+11 | 0.157952E+11 | 0.124268E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271570E+10 | 0.484822E+09 | 0.203732E+10 | 0.835353E+09 | 0.770049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.453932E+10 | 0.375499E+10 | 0.257108E+10 | 0.179271E+10 | 0.128787E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.637967E+10 | -0.622519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154481188.9 | 81.21 | 0.00 | 0.00 |
February | 0.577386E+10 | -0.563434E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -139526619.5 | 81.21 | 0.00 | 0.00 |
March | 0.644830E+10 | -0.629390E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154394453.0 | 81.21 | 0.00 | 0.00 |
April | 0.619282E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149316387.1 | 81.21 | 0.00 | 0.00 |
May | 0.641453E+10 | -0.626021E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154317849.1 | 81.21 | 0.00 | 0.00 |
June | 0.623598E+10 | -0.608661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149374274.8 | 81.21 | 0.00 | 0.00 |
July | 0.637134E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154236041.2 | 81.21 | 0.00 | 0.00 |
August | 0.644948E+10 | -0.629523E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154249818.5 | 81.21 | 0.00 | 0.00 |
September | 0.619400E+10 | -0.604484E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149157591.1 | 81.21 | 0.00 | 0.00 |
October | 0.637810E+10 | -0.622386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154243348.3 | 81.21 | 0.00 | 0.00 |
November | 0.617400E+10 | -0.602464E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149360879.2 | 81.21 | 0.00 | 0.00 |
December | 0.637161E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154502673.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753837E+11 | -0.735665E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181716E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577386E+10 | -0.629523E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -154502673.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644948E+10 | -0.563434E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -139526619.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.221801E+11 | -0.213396E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -840509207.8 | 58.99 | 0.00 | 0.00 |
February | 0.200547E+11 | -0.192955E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -759183110.9 | 58.99 | 0.00 | 0.00 |
March | 0.216054E+11 | -0.207658E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839602558.1 | 58.98 | 0.00 | 0.00 |
April | 0.194212E+11 | -0.186094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811727093.0 | 58.99 | 0.00 | 0.00 |
May | 0.185214E+11 | -0.176823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839078307.6 | 58.99 | 0.00 | 0.00 |
June | 0.166479E+11 | -0.158357E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -812199457.2 | 58.99 | 0.00 | 0.00 |
July | 0.162186E+11 | -0.153804E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838206402.0 | 58.99 | 0.00 | 0.00 |
August | 0.164204E+11 | -0.155821E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838307517.2 | 58.99 | 0.00 | 0.00 |
September | 0.165598E+11 | -0.157496E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -810237949.0 | 58.99 | 0.00 | 0.00 |
October | 0.184398E+11 | -0.176017E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838184674.4 | 58.98 | 0.00 | 0.00 |
November | 0.193850E+11 | -0.185729E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -812104352.5 | 58.99 | 0.00 | 0.00 |
December | 0.213688E+11 | -0.205280E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -840747921.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.226823E+12 | -0.216943E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.988009E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.162186E+11 | -0.213396E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -840747921.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.221801E+11 | -0.153804E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -759183110.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.321014E+11 | 91334.19 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216232E+11 | 87776.28 | 03-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157782E+11 | 97453.23 | 02-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309181E+10 | 62588.12 | 20-APR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274149E+09 | 73525.85 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94689240.42 | 72065.56 | 12-JUN-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34841250.65 | 19721.61 | 05-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 55136203.11 | 34168.94 | 27-AUG-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234012E+09 | 51899.89 | 11-SEP-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151345E+10 | 44802.84 | 31-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177744E+11 | 79280.75 | 28-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399508E+11 | 84363.06 | 27-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 34841250.65 | 19721.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.399508E+11 | 97453.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.177036E+09 | 0.173410E+09 | 10586.64 | 03-JAN-14:00 | 10399.55 | 0.00 |
February | 0.00 | 0.00 | 0.251316E+10 | 0.250839E+10 | 23305.20 | 06-FEB-14:00 | 23305.20 | 0.00 |
March | 0.00 | 0.00 | 0.646753E+10 | 0.646547E+10 | 32602.41 | 22-MAR-13:00 | 32602.41 | 0.00 |
April | 0.00 | 0.00 | 0.343555E+11 | 0.336895E+11 | 116220.97 | 02-APR-03:01 | 110626.83 | 0.00 |
May | 0.00 | 0.00 | 0.669910E+11 | 0.630349E+11 | 116220.97 | 01-MAY-03:01 | 116220.97 | 0.00 |
June | 0.00 | 0.00 | 0.983806E+11 | 0.907506E+11 | 116220.97 | 05-JUN-03:25 | 94324.33 | 0.00 |
July | 0.00 | 0.00 | 0.123150E+12 | 0.907838E+11 | 127145.00 | 21-JUL-03:01 | 44486.34 | 0.00 |
August | 0.00 | 0.00 | 0.101568E+12 | 0.816887E+11 | 124376.95 | 02-AUG-03:01 | 59913.27 | 0.00 |
September | 0.00 | 0.00 | 0.780762E+11 | 0.615064E+11 | 122020.16 | 22-SEP-03:01 | 55927.38 | 0.00 |
October | 0.00 | 0.00 | 0.341683E+11 | 0.280005E+11 | 119010.81 | 04-OCT-03:01 | 56930.14 | 0.00 |
November | 0.00 | 0.00 | 0.363180E+10 | 0.337475E+10 | 116220.97 | 10-NOV-04:01 | 96278.01 | 0.00 |
December | 0.00 | 0.00 | 292.38 | 292.38 | 0.97 | 09-DEC-14:10 | 0.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.549479E+12 | 0.461976E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 292.38 | 292.38 | 0.97 | 0.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123150E+12 | 0.907838E+11 | 127145.00 | 116220.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.274573E+09 | 0.246161E+09 | 41647.26 | 06-JAN-04:41 | 38174.27 | 0.00 |
February | 0.00 | 0.00 | 0.162310E+10 | 0.160551E+10 | 41647.26 | 06-FEB-04:41 | 35475.33 | 0.00 |
March | 0.00 | 0.00 | 0.372601E+10 | 0.371192E+10 | 41647.26 | 05-MAR-04:11 | 33603.07 | 0.00 |
April | 0.00 | 0.00 | 0.185369E+11 | 0.162915E+11 | 41647.26 | 02-APR-03:31 | 39804.78 | 0.00 |
May | 0.00 | 0.00 | 0.345787E+11 | 0.281200E+11 | 41647.26 | 01-MAY-03:01 | 41647.26 | 0.00 |
June | 0.00 | 0.00 | 0.463483E+11 | 0.361827E+11 | 41647.26 | 22-JUN-01:22 | 36868.76 | 0.00 |
July | 0.00 | 0.00 | 0.560236E+11 | 0.378988E+11 | 46272.85 | 21-JUL-10:42 | 19865.14 | 0.00 |
August | 0.00 | 0.00 | 0.482990E+11 | 0.346600E+11 | 44252.51 | 02-AUG-03:43 | 18572.87 | 0.00 |
September | 0.00 | 0.00 | 0.378933E+11 | 0.272492E+11 | 43768.94 | 22-SEP-04:02 | 15837.07 | 0.00 |
October | 0.00 | 0.00 | 0.172016E+11 | 0.136371E+11 | 41880.55 | 04-OCT-03:01 | 17904.33 | 0.00 |
November | 0.00 | 0.00 | 0.207509E+10 | 0.195184E+10 | 41647.26 | 04-NOV-03:11 | 28582.36 | 0.00 |
December | 0.00 | 0.00 | 0.138331E+09 | 0.123186E+09 | 41647.26 | 11-DEC-04:01 | 32740.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.266718E+12 | 0.201678E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.138331E+09 | 0.123186E+09 | 41647.26 | 15837.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.560236E+11 | 0.378988E+11 | 46272.85 | 41647.26 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 8428.45 | 16093.75 | 27-JAN-19:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 8436.94 | 16084.78 | 08-FEB-07:47 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 8214.14 | 15806.93 | 01-MAR-19:37 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7642.04 | 14916.53 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 7065.40 | 13888.64 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6574.37 | 12786.11 | 01-JUN-06:42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 6208.42 | 11930.80 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 6283.65 | 11984.46 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6541.09 | 12754.42 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7035.57 | 13901.20 | 31-OCT-18:45 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7628.05 | 14986.98 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8125.99 | 15750.84 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 7342.50 | ||||
Minimum of Months | 0.00 | 0.00 | 6208.42 | 11930.80 | ||
Maximum of Months | 0.00 | 0.00 | 8436.94 | 16093.75 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.514341E+10 | 0.64 | 2203.40 | 01-JAN-00:01 | 0.73 |
February | 0.469656E+10 | 0.65 | 2203.40 | 01-FEB-00:01 | 0.73 |
March | 0.526592E+10 | 0.65 | 2203.40 | 01-MAR-00:01 | 0.73 |
April | 0.536408E+10 | 0.69 | 2203.40 | 01-APR-01:25 | 0.73 |
May | 0.562671E+10 | 0.70 | 2203.40 | 01-MAY-00:12 | 0.74 |
June | 0.544007E+10 | 0.69 | 2203.40 | 01-JUN-00:10 | 0.73 |
July | 0.562331E+10 | 0.69 | 2203.40 | 01-JUL-00:09 | 0.73 |
August | 0.562410E+10 | 0.69 | 2203.40 | 01-AUG-00:09 | 0.73 |
September | 0.544021E+10 | 0.69 | 2203.40 | 01-SEP-00:09 | 0.72 |
October | 0.561961E+10 | 0.69 | 2203.40 | 01-OCT-00:10 | 0.73 |
November | 0.518175E+10 | 0.66 | 2203.40 | 01-NOV-00:50 | 0.73 |
December | 0.515531E+10 | 0.64 | 2203.40 | 01-DEC-00:02 | 0.73 |
Annual Sum or Average | 0.641810E+11 | 0.67 | |||
Minimum of Months | 0.469656E+10 | 0.64 | 2203.40 | 0.72 | |
Maximum of Months | 0.562671E+10 | 0.70 | 2203.40 | 0.74 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207590E+11 | 1.49 | 9299.24 | 01-JAN-08:50 | 1.77 |
February | 0.187511E+11 | 1.49 | 9299.24 | 01-FEB-14:30 | 1.78 |
March | 0.207571E+11 | 1.48 | 9299.24 | 01-MAR-14:00 | 1.78 |
April | 0.201245E+11 | 1.50 | 9299.24 | 01-APR-05:30 | 1.78 |
May | 0.208689E+11 | 1.51 | 9299.24 | 01-MAY-10:50 | 1.78 |
June | 0.202257E+11 | 1.51 | 9299.24 | 02-JUN-06:13 | 1.77 |
July | 0.209440E+11 | 1.50 | 9299.24 | 05-JUL-06:50 | 1.75 |
August | 0.209253E+11 | 1.50 | 9299.24 | 02-AUG-05:00 | 1.74 |
September | 0.202690E+11 | 1.50 | 9299.24 | 02-SEP-06:30 | 1.75 |
October | 0.208093E+11 | 1.50 | 9299.24 | 01-OCT-08:21 | 1.77 |
November | 0.200908E+11 | 1.48 | 9299.24 | 01-NOV-04:07 | 1.77 |
December | 0.207617E+11 | 1.49 | 9299.24 | 01-DEC-09:38 | 1.78 |
Annual Sum or Average | 0.245286E+12 | 1.50 | |||
Minimum of Months | 0.187511E+11 | 1.48 | 9299.24 | 1.74 | |
Maximum of Months | 0.209440E+11 | 1.51 | 9299.24 | 1.78 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.478448E+10 | 0.90 | 2130.61 | 03-JAN-12:40 | 1.04 |
February | 0.432432E+10 | 0.91 | 2130.61 | 04-FEB-14:55 | 1.04 |
March | 0.479471E+10 | 0.92 | 2130.61 | 03-MAR-12:50 | 1.04 |
April | 0.469538E+10 | 0.96 | 2130.61 | 01-APR-09:05 | 1.04 |
May | 0.490239E+10 | 0.96 | 2130.61 | 01-MAY-10:20 | 1.04 |
June | 0.478458E+10 | 0.95 | 2130.61 | 01-JUN-06:20 | 1.03 |
July | 0.498077E+10 | 0.95 | 2130.61 | 01-JUL-05:20 | 1.02 |
August | 0.496345E+10 | 0.95 | 2130.61 | 01-AUG-04:20 | 1.02 |
September | 0.476201E+10 | 0.96 | 2130.61 | 20-SEP-04:30 | 1.03 |
October | 0.486180E+10 | 0.96 | 2130.61 | 01-OCT-08:56 | 1.03 |
November | 0.464634E+10 | 0.93 | 2130.61 | 23-NOV-11:50 | 1.04 |
December | 0.478272E+10 | 0.90 | 2130.61 | 02-DEC-05:10 | 1.03 |
Annual Sum or Average | 0.572830E+11 | 0.94 | |||
Minimum of Months | 0.432432E+10 | 0.90 | 2130.61 | 1.02 | |
Maximum of Months | 0.498077E+10 | 0.96 | 2130.61 | 1.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 49.70 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 48.87 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 49.16 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.56 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.82 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 53.87 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.83 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.19 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 53.74 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.29 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.77 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 49.76 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.87 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.19 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 49.70 | 59.92 | 8428.45 | 16093.75 | 27-JAN-19:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 48.87 | 59.84 | 8436.94 | 16084.78 | 08-FEB-07:47 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.16 | 59.42 | 8214.14 | 15806.93 | 01-MAR-19:37 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.45 | 50.45 | 7642.04 | 14916.53 | 03-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.46 | 51.46 | 7065.40 | 13888.64 | 01-MAY-06:55 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.47 | 52.47 | 6574.37 | 12786.11 | 01-JUN-06:42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.65 | 52.65 | 6208.42 | 11930.80 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.48 | 52.48 | 6283.65 | 11984.46 | 31-AUG-18:15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.11 | 52.11 | 6541.09 | 12754.42 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 50.04 | 50.04 | 7035.57 | 13901.20 | 31-OCT-18:45 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.22 | 51.22 | 7628.05 | 14986.98 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 49.76 | 59.85 | 8125.99 | 15750.84 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 7342.50 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.87 | 50.04 | 6208.42 | 11930.80 | ||
Maximum of Months | 0.00 | 0.00 | 52.65 | 59.92 | 8436.94 | 16093.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208226E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.196380E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.230220E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.316953E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.431884E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.534944E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.604153E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.540757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.455785E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.321802E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.213613E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207617E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.426233E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.196380E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.604153E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.487500E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.487274E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.604501E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.105436E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.156400E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.194538E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.219598E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.197532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.162337E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102690E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.534314E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.482685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139816E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.482685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219598E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207590E+11 | 0.177036E+09 | 0.321014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187511E+11 | 0.251316E+10 | 0.216232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207571E+11 | 0.646753E+10 | 0.157782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201245E+11 | 0.343555E+11 | 0.309181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208689E+11 | 0.669910E+11 | 0.274149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202257E+11 | 0.983806E+11 | 94689240.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209440E+11 | 0.123150E+12 | 34841250.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209253E+11 | 0.101568E+12 | 55136203.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202690E+11 | 0.780762E+11 | 0.234012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208093E+11 | 0.341683E+11 | 0.151345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200908E+11 | 0.363180E+10 | 0.177744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207617E+11 | 292.38 | 0.399508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245286E+12 | 0.549479E+12 | 0.132526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187511E+11 | 292.38 | 34841250.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209440E+11 | 0.123150E+12 | 0.399508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.478448E+10 | 0.274573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432432E+10 | 0.162310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.479471E+10 | 0.372601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469538E+10 | 0.185369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490239E+10 | 0.345787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.478458E+10 | 0.463483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498077E+10 | 0.560236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496345E+10 | 0.482990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476201E+10 | 0.378933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486180E+10 | 0.172016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464634E+10 | 0.207509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.478272E+10 | 0.138331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572830E+11 | 0.266718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.432432E+10 | 0.138331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.498077E+10 | 0.560236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.207590E+11 | 0.00 | 0.00 | 0.00 | 63668507.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187511E+11 | 0.00 | 0.00 | 0.00 | 0.886906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207571E+11 | 0.00 | 0.00 | 0.00 | 0.226486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201245E+11 | 0.00 | 0.00 | 0.00 | 0.115708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208689E+11 | 0.00 | 0.00 | 0.00 | 0.223194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202257E+11 | 0.00 | 0.00 | 0.00 | 0.332687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.209440E+11 | 0.00 | 0.00 | 0.00 | 0.394713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209253E+11 | 0.00 | 0.00 | 0.00 | 0.331504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202690E+11 | 0.00 | 0.00 | 0.00 | 0.253095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208093E+11 | 0.00 | 0.00 | 0.00 | 0.113709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200908E+11 | 0.00 | 0.00 | 0.00 | 0.127043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207617E+11 | 0.00 | 0.00 | 0.00 | 106.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245286E+12 | 0.00 | 0.00 | 0.00 | 0.180947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187511E+11 | 0.00 | 0.00 | 0.00 | 106.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209440E+11 | 0.00 | 0.00 | 0.00 | 0.394713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.478448E+10 | 0.00 | 0.00 | 0.00 | 90523486.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432432E+10 | 0.00 | 0.00 | 0.00 | 0.548421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.479471E+10 | 0.00 | 0.00 | 0.00 | 0.125030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469538E+10 | 0.00 | 0.00 | 0.00 | 0.584817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.490239E+10 | 0.00 | 0.00 | 0.00 | 0.107376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.478458E+10 | 0.00 | 0.00 | 0.00 | 0.146692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498077E+10 | 0.00 | 0.00 | 0.00 | 0.169790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496345E+10 | 0.00 | 0.00 | 0.00 | 0.147898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476201E+10 | 0.00 | 0.00 | 0.00 | 0.114717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486180E+10 | 0.00 | 0.00 | 0.00 | 0.540723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464634E+10 | 0.00 | 0.00 | 0.00 | 0.696803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.478272E+10 | 0.00 | 0.00 | 0.00 | 44124374.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572830E+11 | 0.00 | 0.00 | 0.00 | 0.825329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.432432E+10 | 0.00 | 0.00 | 0.00 | 44124374.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.498077E+10 | 0.00 | 0.00 | 0.00 | 0.169790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.794550E+11 | 0.00 | 0.00 | 5527942.33 | 0.00 | 0.200298E+10 | 0.670471E+10 | 0.00 | 7.09 |
February | 0.559081E+11 | 0.00 | 0.00 | 22754815.87 | 0.00 | 0.235727E+10 | 0.128982E+11 | 0.00 | 7.38 |
March | 0.472543E+11 | 0.00 | 0.00 | 47271221.35 | 0.00 | 0.771918E+09 | 0.211286E+11 | 0.00 | 7.65 |
April | 0.171302E+11 | 0.212635E+10 | 347053.01 | 86728470.00 | 258346.76 | 14900073.29 | 0.186494E+11 | 78359.82 | 7.79 |
May | 0.517079E+10 | 0.981184E+10 | 1025610.50 | 71556810.61 | 4294351.12 | 6520384.12 | 0.111587E+11 | 498228.16 | 7.74 |
June | 0.709920E+09 | 0.253225E+11 | 5563823.86 | 29137152.75 | 76048860.34 | 2809033.76 | 0.378707E+10 | 301302.75 | 7.57 |
July | 0.561233E+09 | 0.422408E+11 | 8739806.88 | 7037458.10 | 0.231284E+09 | 0.00 | 0.878223E+09 | 190482.25 | 7.66 |
August | 0.739280E+09 | 0.267413E+11 | 9428463.54 | 28055614.72 | 0.123962E+09 | 7757.76 | 0.516616E+10 | 355568.07 | 7.77 |
September | 0.355013E+10 | 0.164002E+11 | 3869413.17 | 57806210.34 | 35643529.41 | 588328.93 | 0.108808E+11 | 147860.88 | 7.88 |
October | 0.172115E+11 | 0.363566E+10 | 67325.41 | 87457567.83 | 5909881.19 | 1725607.55 | 0.238934E+11 | 30004.94 | 8.04 |
November | 0.534086E+11 | 0.00 | 0.00 | 37606626.16 | 0.00 | 0.197702E+09 | 0.200229E+11 | 0.00 | 7.45 |
December | 0.855122E+11 | 0.00 | 0.00 | 2634464.12 | 0.00 | 0.463106E+10 | 0.513549E+10 | 0.00 | 7.03 |
Annual Sum or Average | 0.366611E+12 | 0.126279E+12 | 29041496.37 | 0.483574E+09 | 0.477401E+09 | 0.998748E+10 | 0.140304E+12 | 1601806.88 | 7.59 |
Minimum of Months | 0.561233E+09 | 0.00 | 0.00 | 2634464.12 | 0.00 | 0.00 | 0.878223E+09 | 0.00 | 7.03 |
Maximum of Months | 0.855122E+11 | 0.422408E+11 | 9428463.54 | 87457567.83 | 0.231284E+09 | 0.463106E+10 | 0.238934E+11 | 498228.16 | 8.04 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.110137E+09 | 0.00 | 0.00 | 0.480204E+11 | 0.00 | 6.18 |
February | 0.00 | 0.00 | 0.00 | 0.111335E+09 | 0.00 | 0.00 | 0.430060E+11 | 0.00 | 7.53 |
March | 0.00 | 0.00 | 0.00 | 0.132650E+09 | 0.00 | 0.00 | 0.473968E+11 | 0.00 | 8.80 |
April | 0.00 | 0.00 | 0.00 | 0.152985E+09 | 0.00 | 0.00 | 0.339818E+11 | 0.00 | 9.29 |
May | 0.00 | 3019511.49 | 0.00 | 0.167716E+09 | 0.00 | 0.00 | 0.216360E+11 | 0.00 | 8.12 |
June | 0.00 | 72835488.07 | 0.00 | 0.177727E+09 | 0.00 | 0.00 | 0.103062E+11 | 0.00 | 5.81 |
July | 0.00 | 0.188633E+10 | 0.00 | 79217930.27 | 0.00 | 0.00 | 0.403265E+10 | 0.00 | 6.19 |
August | 0.00 | 0.442111E+09 | 0.00 | 0.152264E+09 | 0.00 | 0.00 | 0.103336E+11 | 0.00 | 7.19 |
September | 0.00 | 0.170491E+09 | 0.00 | 0.167173E+09 | 0.00 | 0.00 | 0.180613E+11 | 0.00 | 8.70 |
October | 0.00 | 20152966.06 | 0.00 | 0.154774E+09 | 0.00 | 0.00 | 0.374804E+11 | 0.00 | 10.58 |
November | 0.00 | 0.00 | 0.00 | 0.122053E+09 | 0.00 | 0.00 | 0.474684E+11 | 0.00 | 8.20 |
December | 0.00 | 0.00 | 0.00 | 0.112402E+09 | 0.00 | 0.00 | 0.484091E+11 | 0.00 | 5.84 |
Annual Sum or Average | 0.00 | 0.259494E+10 | 0.00 | 0.164043E+10 | 0.00 | 0.00 | 0.370133E+12 | 0.00 | 7.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 79217930.27 | 0.00 | 0.00 | 0.403265E+10 | 0.00 | 5.81 |
Maximum of Months | 0.00 | 0.188633E+10 | 0.00 | 0.177727E+09 | 0.00 | 0.00 | 0.484091E+11 | 0.00 | 10.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.664802E+11 | 0.124187E+11 | 0.277453E+12 | 0.361811E+11 | 0.317555E+11 |
February | 0.717503E+11 | 0.105413E+11 | 0.223913E+12 | 0.347921E+11 | 0.335236E+11 |
March | 0.120954E+12 | 0.110318E+11 | 0.216907E+12 | 0.409105E+11 | 0.435319E+11 |
April | 0.134635E+12 | 0.732379E+10 | 0.139698E+12 | 0.297543E+11 | 0.983134E+11 |
May | 0.151025E+12 | 0.442820E+10 | 0.846499E+11 | 0.180675E+11 | 0.163905E+12 |
June | 0.141902E+12 | 0.193006E+10 | 0.330785E+11 | 0.694904E+10 | 0.223823E+12 |
July | 0.132722E+12 | -166843902.1 | -0.393628E+11 | 0.148153E+10 | 0.268042E+12 |
August | 0.120169E+12 | 0.167884E+10 | 0.106113E+11 | 0.826783E+10 | 0.229695E+12 |
September | 0.104334E+12 | 0.283421E+10 | 0.513682E+11 | 0.154849E+11 | 0.184012E+12 |
October | 0.899295E+11 | 0.650929E+10 | 0.133895E+12 | 0.346865E+11 | 0.961066E+11 |
November | 0.681907E+11 | 0.104540E+11 | 0.229562E+12 | 0.399187E+11 | 0.357039E+11 |
December | 0.550580E+11 | 0.128017E+11 | 0.300169E+12 | 0.353936E+11 | 0.339562E+11 |
Annual Sum or Average | 0.125715E+13 | 0.817849E+11 | 0.166194E+13 | 0.301888E+12 | 0.144237E+13 |
Minimum of Months | 0.550580E+11 | -166843902.1 | -0.393628E+11 | 0.148153E+10 | 0.317555E+11 |
Maximum of Months | 0.151025E+12 | 0.128017E+11 | 0.300169E+12 | 0.409105E+11 | 0.268042E+12 |