Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:27:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2287.19 | 4474.57 | 4474.57 |
Net Site Energy | 2287.19 | 4474.57 | 4474.57 |
Total Source Energy | 5216.55 | 10205.46 | 10205.46 |
Net Source Energy | 5216.55 | 10205.46 | 10205.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 158.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 153.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 71.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.47 | 344.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 62.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1314.08 | 973.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 158.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 153.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 71.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 362.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.47 | 344.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 158.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 153.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 71.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 362.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.47 | 344.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 62.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1156.94 | 984.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1024.21 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2570.82 | 1903.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1156.94 | 984.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1024.21 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2570.82 | 1903.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1314.083 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1314.083 | 100.00 |
Total On-Site and Utility Electric Sources | 1314.083 | 100.00 |
Total Electricity End Uses | 1314.083 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3690.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 14.4672 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.5854 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 14.4672 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.5854 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 13.6812 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-16:10 | 15-DEC-04:19 | - | - | - | - | - | - | - | - | - | - | 30-JAN-07:00 |
Heating | 0.00 | 163386.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35276.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22286.02 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13529.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3133.95 | 993.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2010.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 82547.94 | 168904.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 163386.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35276.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 20918.44 | 4525.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13529.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3133.95 | 993.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 508.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 171.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 485.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 227.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1146.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.03 | 373.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 198.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4161.70 | 1054.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 335.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 950.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2243.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.62 | 731.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 389.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8141.79 | 2063.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 335.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 950.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 445.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2243.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.62 | 731.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 389.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8141.79 | 2063.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.89 |
KITCHEN DIRECT AIR | 1.96 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.89 | 4.89 | 4.89 | 4.89 | 4.89 | 4.89 | 1.00 | 1.00 | 4.89 |
PSZ-AC_2:2 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.00 | 1.96 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.89 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.96 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.89 | 9175.74 |
PSZ-AC_2:2_ADDAQ FAN | 1.96 | 2150.67 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.89 | 4.89 | 4.89 | 4.89 | 87304.50 | 130708.83 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.96 | 44302.75 | 90017.88 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.89 | 2.44 | 4.89 | 87304.50 | 43603.92 | 87304.50 | 0.800690 | 0.800690 |
PSZ-AC_2:2 COOLING COIL | 1.96 | 0.982485 | 1.96 | 44302.75 | 21320.65 | 44302.75 | 0.731930 | 0.731930 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 130708.83 |
PSZ-AC_2:2 HEATING COIL | 90017.88 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 14.467 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 79.395 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.585 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.665 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 5378.143 | 14.467 | 19.198 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5378.143 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1615.060 | 11.585 | 214.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1615.060 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5103_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.901 | 2.901 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.5103_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.901 | 2.901 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.5103_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.901 | 2.901 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.5103_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.901 | 2.901 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.82275E-002 | 0.31435 | 0.46430 | 0.46430 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10444 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.82275E-002 | 0.31435 | 0.46430 | 0.46430 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10444 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.82275E-002 | 0.31435 | 0.46430 | 0.46430 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10444 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.82275E-002 | 0.31435 | 0.46430 | 0.46430 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10444 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 45939.83668 | 55127.80401 | 4.07268 | 4.88722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 8710.11110 | 10452.13332 | 0.45390 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -7.90000 | 2.34317E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21766.70895 | 26120.05074 | 1.63748 | 1.96497 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 69123.70 | 4.88722 | 4.88722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63468.20 | 1.33138 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 38342.30 | 1.96497 | 1.96497 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 71514.74 | 1.50017 | 1.50017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.88722 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.96497 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.88722 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.88722 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.88722 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.88722 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.88722 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.88722 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.96497 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96497 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.96497 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.96497 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.96497 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.96497 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.88722 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.96497 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.88722 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.88722 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9175.74176 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.88722 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.88722 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.88722 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.88722 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.88722 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.44361 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.88722 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 87304.50000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 43603.91981 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 87304.50000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80069 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80069 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 87304.50000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 130708.83434 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 130708.83434 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.96497 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.96497 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2150.67064 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.96497 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.96497 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.96497 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.96497 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.96497 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98249 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.96497 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44302.75000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 21320.64511 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 44302.75000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73193 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73193 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44302.75000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 90017.88112 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 90017.88112 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 83745.1 | 9.54 | 9.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 42894.8 | 10.01 | 9.88 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5103_SHGC_EAST_0.4 | N/A | 2.901 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5103_SHGC_SOUTH_0.4 | N/A | 2.901 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5103_SHGC_WEST_0.4 | N/A | 2.901 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.0560656797E-002 | 0.1942138100 | Pass | Pass | 5.2339095183E-002 | 0.1118647652 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1956480846 | 0.6050430924 | Pass | Pass | 3.4390786426E-002 | 0.1081802596 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4833249541 | 0.5048891936 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1226.63 | 129.52 | 1534.77 | 113.80 | 956.58 | 3961.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5103_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.901 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5103_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.901 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5103_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.901 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.901 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.901 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 14.4672 | 371.75 | 5378.14 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 97.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.5854 | 139.41 | 1615.06 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.38 |
Interior Lighting Total | 13.6812 | 511.15 | 6993.20 | 127.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.71 | 83.71 | 71.94 | |
Exterior Lighting Total | 4578.48 | 71.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 87304.50 | 69903.84 | 17400.66 | 0.80 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44302.75 | 32426.51 | 11876.24 | 0.73 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 83745.1 | 9.54 | 9.42 | ||||
PSZ-AC_2:2 COOLING COIL | 42894.8 | 10.01 | 9.88 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 130708.83 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 90017.88 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 4.89 | 9175.74 | 1877.50 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.96 | 2150.67 | 1094.51 | 1.00 | 1.29 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 45939.84 | 55127.80 | 148.29 | 4.073 | 4.887 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00817 | 34.97 | 0.00570 | 1.331 | 0.00 |
KITCHEN | 21766.71 | 26120.05 | 187.37 | 1.637 | 1.965 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.98 | 0.00874 | 33.89 | 0.00570 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8710.11 | 10452.13 | 28.12 | 0.454 | 1.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00762 | -7.90 | 0.00234 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.52 | 0.00211 | -7.90 | 0.00234 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.89 | 4.89 | 1.33 | 1.33 | 4.8872 | 4.8872 | 4.8872 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.96 | 1.96 | 1.50 | 1.50 | 1.9650 | 1.9650 | 1.9650 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 87304.500 | 69903.840 | 4.887220 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 87304.50 | 82445.42 | 4.887220 | 27.02 | 14.58 | 0.00749707 | 10.94 | 8.10 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 27.2420 | 23.99 | 0.00817049 | 36.2130 | 45920.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 130708.834 | 130708.834 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 130708.83 | 130708.83 | 4.887218 | 13.13 | 8.17 | 0.00617948 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 27.2420 | 21.00 | 0.00761587 | 40.5214 | 8703.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 44302.750 | 32426.512 | 1.964970 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 44302.75 | 44302.75 | 1.964970 | 33.23 | 15.66 | 0.00632058 | 11.71 | 7.72 | 0.00632058 | 35.10 | 0.00569938 | 15.77 | 76.3457 | 25.98 | 0.00873630 | 34.3511 | 20882.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 90017.881 | 90017.881 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 90017.88 | 90017.88 | 1.964970 | -6.03 | -6.82 | 0.00229223 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 76.3457 | 19.94 | 0.00212781 | 12.1921 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 87304.500 | 69903.840 | 4.887220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.7767 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.887218 | 4.84034433 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 87304.50 | 82445.42 | 1.0000 | 4.84034615 | 4.887220 | 27.02 | 14.58 | 0.00749707 | 46273.8 | 10.94 | 8.10 | 0.00700000 | 28641.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87304.50 | 35.10 | 0.00569938 | 15.77 | 1.33137743 | 27.2420 | 23.99 | 0.00817049 | 23.99 | 0.00817049 | 36.2130 | 45920.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 130708.834 | 130708.834 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.887218 | 4.84034433 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 130708.83 | 130708.83 | 1.0000 | 4.84034433 | 4.887218 | 13.13 | 8.17 | 0.00617948 | 28795.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 130708.83 | -7.90 | 0.00234317 | -7.90 | 1.33137743 | 27.2420 | 21.00 | 0.00761587 | 21.00 | 0.00761587 | 40.5214 | 8703.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44302.750 | 32426.512 | 1.964970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.5897 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.964970 | 1.94612393 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 44302.75 | 44302.75 | 1.0000 | 1.94612376 | 1.964970 | 33.23 | 15.66 | 0.00632058 | 49586.9 | 11.71 | 7.72 | 0.00632058 | 27714.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44302.75 | 35.10 | 0.00569938 | 15.77 | 1.50017041 | 76.3457 | 25.95 | 0.00873630 | 25.98 | 0.00873630 | 34.3511 | 20882.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90017.881 | 90017.881 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.964970 | 1.94612393 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 90017.88 | 90017.88 | 1.0000 | 1.94612393 | 1.964970 | -6.03 | -6.82 | 0.00229223 | -353.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90017.88 | -7.90 | 0.00234317 | -7.90 | 1.50017041 | 76.3457 | 0.00 | 0.00212781 | 19.94 | 0.00212781 | 12.1921 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.89 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.50 | 1.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3330.83 | 3031.00 | 441.17 |
KITCHEN | 4685.67 | 5885.83 | 3682.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4697.67 | 5983.50 | 3690.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 1.83 | 20.17 | 0.00 | 0.00 |
KITCHEN | 0.00 | 170.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.83 | 189.17 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 6.042 | 0.944 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.879 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.112 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.393 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 49652981.32 | 0.00 | 49652981.32 | 7781456.15 | 57434437.47 | 41986318.57 | 1432.23 | 4608.52 | 2719.25 | 222.02 |
KITCHEN | 43261946.95 | 0.00 | 43261946.95 | 287577.93 | 43549524.88 | 47309374.20 | 1430.84 | 5264.08 | 2065.08 | 615.50 |
Total Facility | 92914928.28 | 0.00 | 92914928.28 | 8069034.08 | 0.10E+09 | 89295692.77 | 1452.57 | 5723.34 | 3199.28 | 661.90 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.8793 | 0.0000 | 1.8793 | 0.2940 | 2.1732 | 1.3314 | 0.00 | 4528.34 | 2658.66 |
KITCHEN | 1.6180 | 0.0000 | 1.6180 | 0.0068 | 1.6248 | 1.5002 | 0.00 | 5163.24 | 2023.76 |
Total Facility | 3.4973 | 0.0000 | 3.4973 | 0.3008 | 3.7981 | 2.8315 | 0.00 | 5621.64 | 3117.07 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48705095.57 | 0.00 | 48705095.57 | 41986318.57 | 6040.38 | 29.99 | 2689.63 | 222.02 |
PSZ-AC_2:2 | 42436066.75 | 0.00 | 42436066.75 | 47309374.20 | 6693.68 | 34.48 | 2031.83 | 615.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8434 | 0.0000 | 1.8434 | 1.3314 | 4527.98 | 29.28 | 2629.74 |
PSZ-AC_2:2 | 1.5871 | 0.0000 | 1.5871 | 1.5002 | 5162.01 | 32.95 | 1992.04 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1488.93 | 1323.15 | 4596.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4656.93 | 2255.61 | 889.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 3.3573 | 2.1051 | 1.3063 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.4718 | 1.8803 | 1.4728 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
Electricity:Building | 604.81 | 4434.71 | 01-JAN-01:10 | 33358.73 | 02-JAN-11:10 |
Electricity:Zone:DINING | 223.13 | 1289.45 | 01-JAN-01:10 | 11839.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 587.95 | 4025.67 | 01-JAN-01:10 | 30993.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.68 | 3145.26 | 01-JAN-01:10 | 21518.76 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.81 | 1038.02 | 04-MAR-23:30 | 3441.39 | 23-AUG-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 121.88 | 1103.60 | 03-DEC-01:10 | 6468.81 | 31-JUL-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.20 | 0.00 | 01-JAN-11:10 | 1507.80 | 30-MAY-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 29.75 | 777.33 | 24-NOV-00:30 | 1076.23 | 12-MAY-03:20 |
ElectricityPurchased:Facility | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
ElectricityPurchased:Plant | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
Cogeneration:ElectricityPurchased | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
ElectricityNet:Plant | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
Cogeneration:ElectricityNet | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
General:Cogeneration:ElectricityNet | 1314.08 | 10116.79 | 03-DEC-01:10 | 82547.94 | 28-JUN-16:10 |
Electricity:HVAC | 515.46 | 0.00 | 01-JAN-01:10 | 48956.93 | 21-JUL-17:10 |
Fans:Electricity | 362.09 | 0.00 | 01-JAN-01:10 | 13529.82 | 11-MAR-14:20 |
General:Fans:Electricity | 362.09 | 0.00 | 01-JAN-01:10 | 13529.82 | 11-MAR-14:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 153.37 | 0.00 | 01-JAN-00:10 | 35427.11 | 21-JUL-17:10 |
General:Cooling:Electricity | 153.37 | 0.00 | 01-JAN-00:10 | 35427.11 | 21-JUL-17:10 |
ExteriorLights:Electricity | 71.94 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 71.94 | 0.00 | 01-JAN-07:20 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.27 | 03-MAR-19:30 |
Water Heater:WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.27 | 03-MAR-19:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 19-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 19-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 973.11 | 2803.57 | 01-JAN-01:10 | 168904.99 | 15-DEC-04:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 158.37 | 0.00 | 01-JAN-01:10 | 163386.04 | 15-DEC-04:20 |
Heating:NaturalGas | 158.37 | 0.00 | 01-JAN-01:10 | 163386.04 | 15-DEC-04:20 |
General:Heating:NaturalGas | 158.37 | 0.00 | 01-JAN-01:10 | 163386.04 | 15-DEC-04:20 |
NaturalGas:Plant | 344.95 | 993.32 | 01-JAN-00:10 | 30106.19 | 07-FEB-20:00 |
WaterSystems:NaturalGas | 344.95 | 993.32 | 01-JAN-00:10 | 30106.19 | 07-FEB-20:00 |
Water Heater:WaterSystems:NaturalGas | 344.95 | 993.32 | 01-JAN-00:10 | 30106.19 | 07-FEB-20:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 01-FEB-07:40 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 01-FEB-07:40 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1717.62 | 3206.70 | 16-DEC-01:10 | 173330.78 | 21-JUL-17:20 |
EnergyTransfer:Building | 803.29 | 1603.35 | 16-DEC-01:10 | 58018.09 | 21-JUL-17:20 |
EnergyTransfer:Zone:KITCHEN | 460.22 | 1603.35 | 16-DEC-01:10 | 25297.19 | 21-MAR-11:00 |
Refrigeration:EnergyTransfer | 146.78 | 2714.17 | 14-JAN-23:10 | 7834.84 | 12-MAY-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.39 | 1357.09 | 14-JAN-23:10 | 3917.42 | 12-MAY-03:20 |
General:Refrigeration:EnergyTransfer | 73.39 | 1357.09 | 14-JAN-23:10 | 3917.42 | 12-MAY-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 73.39 | 1357.09 | 14-JAN-23:10 | 3917.42 | 12-MAY-03:20 |
EnergyTransfer:Plant | 315.02 | 1603.35 | 16-DEC-01:10 | 19434.50 | 13-FEB-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.35 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 58.04 | 1341.98 | 24-NOV-00:30 | 2238.70 | 12-MAY-03:20 |
EnergyTransfer:Zone:DINING | 343.06 | 0.00 | 01-JAN-01:10 | 40467.38 | 14-JUN-03:50 |
Heating:EnergyTransfer | 1.22 | 0.00 | 01-JAN-00:10 | 15022.75 | 14-JUN-03:50 |
Heating:EnergyTransfer:Zone:DINING | 1.22 | 0.00 | 01-JAN-00:10 | 15022.75 | 14-JUN-03:50 |
General:Heating:EnergyTransfer | 1.22 | 0.00 | 01-JAN-00:10 | 15022.75 | 14-JUN-03:50 |
General:Heating:EnergyTransfer:Zone:DINING | 1.22 | 0.00 | 01-JAN-00:10 | 15022.75 | 14-JUN-03:50 |
Cooling:EnergyTransfer | 728.67 | 0.00 | 01-JAN-01:10 | 55693.91 | 21-JUL-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 341.84 | 0.00 | 01-JAN-01:10 | 36738.02 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer | 728.67 | 0.00 | 01-JAN-01:10 | 55693.91 | 21-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 341.84 | 0.00 | 01-JAN-01:10 | 36738.02 | 21-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 624.79 | 22-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 624.79 | 22-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 386.83 | 0.00 | 01-JAN-01:10 | 22742.31 | 24-OCT-15:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 386.83 | 0.00 | 01-JAN-01:10 | 22742.31 | 24-OCT-15:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
PlantLoopHeatingDemand:Plant | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
EnergyTransfer:HVAC | 599.30 | 0.00 | 01-JAN-01:10 | 131445.82 | 15-DEC-04:20 |
HeatingCoils:EnergyTransfer | 126.70 | 0.00 | 01-JAN-01:10 | 130708.83 | 15-DEC-04:50 |
CoolingCoils:EnergyTransfer | 472.61 | 0.00 | 01-JAN-00:10 | 101662.27 | 21-JUL-17:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16941.74 | 06-FEB-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.219 | -341.840 | 0.000 | 0.000 | 216.903 | 97.852 | 93.957 | 66.019 | 0.000 | 7.690 | 0.001 | 0.000 | -27.381 | 0.000 | -71.195 | -43.226 |
KITCHEN | 0.000 | 0.000 | 0.004 | -386.818 | 0.000 | 0.000 | 5.700 | 29.385 | 297.857 | 0.000 | 0.000 | 0.091 | 57.290 | 0.000 | 0.000 | 0.000 | -3.510 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.683 | 37.292 | 0.000 | 0.000 | 0.000 | -45.974 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.223 | -728.657 | 0.000 | 0.000 | 222.604 | 127.237 | 391.814 | 66.019 | 0.000 | 16.464 | 94.583 | 0.000 | -27.381 | 0.000 | -120.679 | -43.226 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 19-OCT-03:01 | 0.00 | 0.00 | 0.00 | -113709.76 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 114024.80 | 0.00 | -1982.42 | 0.00 | -44.47 | 0.00 |
KITCHEN | 31-OCT-03:41 | 0.00 | 0.00 | 0.00 | -75383.08 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 71649.87 | 0.00 | -0.00 | 0.00 | -330.52 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-OCT-03:01 | 0.00 | 0.00 | 0.00 | -181616.78 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1157.09 | 176746.60 | 0.00 | -1982.42 | 0.00 | -80.08 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 14-JUN-03:47 | 0.00 | 0.00 | 45054.64 | 0.00 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1231.41 | 0.00 | -153.13 | -45381.94 |
KITCHEN | 22-JAN-05:03 | 0.00 | 0.00 | 6238.57 | 0.00 | 0.00 | 0.00 | 0.00 | 242.26 | 7256.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -161.52 | -13576.23 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-JUN-03:47 | -7691.83 | 7691.83 | 45054.64 | -7691.83 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1068.29 | 0.00 | 0.00 | -1231.41 | 0.00 | -390.11 | -42585.16 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8872 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8872 | 0.2724 | 1.0000 | Not calculated | 1.3314 | 0.2724 | ||
PSZ-AC_2:2 | 1.9650 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9650 | 0.0929 | 1.0000 | Not calculated | 0.1826 | 0.0929 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.8872 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.8872 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2724 | ||
PSZ-AC_2:2 | 1.9650 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.9650 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.0929 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8872 | 4.8872 | 4.8872 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9650 | 1.9650 | 1.9650 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8872 | 4.8872 | 4.8872 | 4.8872 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9650 | 1.9650 | 1.9650 | 1.9650 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8872 | 4.8872 | 4.8872 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9650 | 1.9650 | 1.9650 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.8872 | 4.8872 | 4.8872 | 4.8872 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.9650 | 1.9650 | 1.9650 | 1.9650 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 158.37 | 163386.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 153.37 | 35427.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 127.24 | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 71.94 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 362.09 | 13529.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.47 | 4742.27 | 344.95 | 30106.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.20 | 1507.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.75 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 523.53 | 1314.08 |
Natural Gas | 469.79 | 973.11 |
Additional | 0.00 | 0.00 |
Total | 993.32 | 2287.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 248.92 |
Space Heating | 0.00 |
Space Cooling | 300.04 |
Fans (All) | 708.37 |
Service Water Heating | 147.65 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2570.82 |
Subtotal | 2570.82 |
Natural Gas [MJ/m2] | |
Space Heating | 309.84 |
Service Water Heating | 674.84 |
Miscellaneous (All) | 1903.75 |
Subtotal | 1903.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.56 |
Space Heating | 6.92 |
Space Cooling | 6.71 |
Fans (All) | 15.83 |
Service Water Heating | 18.38 |
Receptacle Equipment | 40.68 |
Miscellaneous | 5.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8636.50 | 123.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8099.00 | 660.50 | 0.50 | 0.00 | 0.00 |
ATTIC | 6520.67 | 669.67 | 570.33 | 836.83 | 162.50 |
Min | 6520.67 | 123.50 | 0.00 | 0.00 | 0.00 |
Max | 8636.50 | 669.67 | 570.33 | 836.83 | 162.50 |
Average | 7752.06 | 484.56 | 190.28 | 278.94 | 54.17 |
Sum | 23256.17 | 1453.67 | 570.83 | 836.83 | 162.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 823641.00 | 581.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823641.00 | 581.00 | 0.00 | 0.00 | 0.00 |
Average | 280958.00 | 193.67 | 0.00 | 0.00 | 0.00 |
Sum | 842874.00 | 581.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8620.67 | 139.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7713.50 | 1046.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 6773.00 | 873.17 | 292.33 | 289.17 | 532.33 |
Min | 6773.00 | 139.33 | 0.00 | 0.00 | 0.00 |
Max | 8620.67 | 1046.50 | 292.33 | 289.17 | 532.33 |
Average | 7702.39 | 686.33 | 97.44 | 96.39 | 177.44 |
Sum | 23107.17 | 2059.00 | 292.33 | 289.17 | 532.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823431.00 | 791.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 17766.67 | 1466.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823431.00 | 1466.33 | 0.00 | 0.00 | 0.00 |
Average | 280399.22 | 752.44 | 0.00 | 0.00 | 0.00 |
Sum | 841197.67 | 2257.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169850E+11 | 24495.96 | 20-JAN-00:01 | -6.9 | -7.0 | 0.128641E+11 | 12938.38 | 23-JAN-12:39 | 12.23 | 3.24 |
February | 0.163750E+11 | 21740.06 | 11-FEB-05:01 | -3.4 | -4.6 | 0.119486E+11 | 13623.39 | 11-FEB-19:10 | 8.95 | 2.44 |
March | 0.209899E+11 | 20831.26 | 08-MAR-14:00 | 22.80 | 9.68 | 0.144120E+11 | 14051.38 | 25-MAR-18:10 | 17.33 | 5.38 |
April | 0.259999E+11 | 106829.99 | 28-APR-03:01 | 12.12 | 4.05 | 0.145043E+11 | 14051.48 | 29-APR-18:10 | 23.53 | 8.85 |
May | 0.307688E+11 | 108877.49 | 16-MAY-03:41 | 11.65 | 3.09 | 0.153112E+11 | 14052.64 | 27-MAY-18:00 | 24.40 | 12.44 |
June | 0.378881E+11 | 109123.52 | 20-JUN-03:01 | 10.78 | 4.69 | 0.150000E+11 | 14053.22 | 24-JUN-18:00 | 27.20 | 14.79 |
July | 0.426807E+11 | 80753.85 | 21-JUL-03:01 | 22.52 | 12.64 | 0.153325E+11 | 14054.48 | 29-JUL-18:10 | 28.95 | 16.22 |
August | 0.424165E+11 | 80957.49 | 19-AUG-03:01 | 21.52 | 12.18 | 0.155262E+11 | 14053.46 | 19-AUG-18:00 | 28.90 | 15.74 |
September | 0.370810E+11 | 100552.24 | 21-SEP-03:01 | 14.40 | 7.35 | 0.148970E+11 | 14052.66 | 23-SEP-18:49 | 16.15 | 12.60 |
October | 0.307136E+11 | 113732.86 | 19-OCT-03:01 | 9.40 | 3.36 | 0.148407E+11 | 14051.38 | 21-OCT-18:10 | 16.13 | 6.44 |
November | 0.218308E+11 | 100653.16 | 01-NOV-03:01 | 9.73 | 6.96 | 0.135005E+11 | 14042.62 | 18-NOV-19:19 | 9.03 | 1.41 |
December | 0.181148E+11 | 22917.54 | 09-DEC-05:02 | -5.4 | -6.5 | 0.125228E+11 | 12938.08 | 01-DEC-12:50 | -5.4 | -6.5 |
Annual Sum or Average | 0.341844E+12 | 0.170660E+12 | ||||||||
Minimum of Months | 0.163750E+11 | 20831.26 | -6.9 | -7.0 | 0.119486E+11 | 12938.08 | -5.4 | -6.5 | ||
Maximum of Months | 0.426807E+11 | 113732.86 | 22.80 | 12.64 | 0.155262E+11 | 14054.48 | 28.95 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311527E+11 | 40748.18 | 26-JAN-05:01 | -5.5 | -8.2 | 0.104186E+11 | 6888.45 | 05-JAN-11:00 | -5.5 | -8.2 |
February | 0.277886E+11 | 44597.71 | 14-FEB-04:41 | 0.28 | -2.9 | 0.942422E+10 | 6934.66 | 14-FEB-11:00 | 17.20 | 6.01 |
March | 0.307711E+11 | 42912.71 | 31-MAR-03:41 | 3.45 | 1.28 | 0.104935E+11 | 6934.68 | 08-MAR-11:00 | 3.45 | 1.28 |
April | 0.302833E+11 | 73392.66 | 18-APR-03:01 | 7.70 | 0.47 | 0.102085E+11 | 6934.91 | 14-APR-10:00 | 7.70 | 0.47 |
May | 0.320689E+11 | 70473.92 | 16-MAY-03:41 | 11.65 | 3.09 | 0.105820E+11 | 6934.96 | 26-MAY-10:00 | 19.40 | 11.15 |
June | 0.329959E+11 | 66552.03 | 20-JUN-03:31 | 11.33 | 4.95 | 0.102620E+11 | 6934.95 | 01-JUN-10:09 | 11.33 | 4.95 |
July | 0.352675E+11 | 47899.26 | 21-JUL-02:62 | 22.30 | 12.30 | 0.106028E+11 | 6934.97 | 07-JUL-10:50 | 22.30 | 12.30 |
August | 0.353482E+11 | 48021.53 | 29-AUG-03:41 | 16.10 | 12.92 | 0.106085E+11 | 6934.97 | 18-AUG-10:00 | 16.10 | 12.92 |
September | 0.333722E+11 | 59004.72 | 22-SEP-03:31 | 16.10 | 8.28 | 0.102583E+11 | 6934.99 | 29-SEP-10:00 | 25.00 | 14.07 |
October | 0.336574E+11 | 75358.54 | 31-OCT-03:41 | 5.10 | 0.83 | 0.105463E+11 | 6934.96 | 04-OCT-10:00 | 5.10 | 0.83 |
November | 0.321606E+11 | 68126.48 | 10-NOV-04:01 | 5.00 | 2.37 | 0.101197E+11 | 6934.57 | 09-NOV-11:39 | 5.00 | 2.37 |
December | 0.319624E+11 | 45061.43 | 15-DEC-05:01 | -9.1 | -11.9 | 0.104051E+11 | 6872.59 | 01-DEC-11:00 | -9.1 | -11.9 |
Annual Sum or Average | 0.386829E+12 | 0.123929E+12 | ||||||||
Minimum of Months | 0.277886E+11 | 40748.18 | -9.1 | -11.9 | 0.942422E+10 | 6872.59 | -9.1 | -11.9 | ||
Maximum of Months | 0.353482E+11 | 75358.54 | 22.30 | 12.92 | 0.106085E+11 | 6934.99 | 25.00 | 14.07 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 | -5.2 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 | 2.84 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 | 4.92 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 | 8.96 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 | 14.90 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.86 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 | 10.88 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 | 5.34 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.00 | 0.00 | -3.2 | -5.2 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.00 | 0.00 | 21.95 | 16.86 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185187E+09 | 33934.78 | 17-JAN-04:02 | -3.3 |
February | 0.194446E+09 | 45011.79 | 06-FEB-04:02 | -4.4 |
March | 13076883.28 | 10141.07 | 05-MAR-05:01 | -1.9 |
April | 4518036.96 | 21944.71 | 28-APR-03:02 | 12.12 |
May | 25851961.42 | 22069.56 | 16-MAY-03:42 | 11.65 |
June | 0.178282E+09 | 45068.24 | 14-JUN-03:47 | 17.23 |
July | 0.265042E+09 | 13947.93 | 28-JUL-03:47 | 18.30 |
August | 0.184720E+09 | 19837.94 | 18-AUG-03:45 | 21.28 |
September | 29595712.50 | 24308.87 | 14-SEP-03:45 | 16.20 |
October | 10523834.32 | 26238.50 | 07-OCT-03:45 | 18.62 |
November | 1697804.18 | 7705.89 | 01-NOV-03:03 | 9.73 |
December | 0.126331E+09 | 35787.11 | 15-DEC-05:01 | -9.1 |
Annual Sum or Average | 0.121927E+10 | |||
Minimum of Months | 1697804.18 | 7705.89 | -9.1 | |
Maximum of Months | 0.265042E+09 | 45068.24 | 21.28 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1382628.73 | 6247.91 | 22-JAN-05:03 | -5.6 |
February | 947560.47 | 4640.24 | 05-FEB-05:03 | -4.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 1500187.42 | 6112.21 | 23-DEC-05:03 | -5.1 |
Annual Sum or Average | 3830376.61 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 1500187.42 | 6247.91 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826825E+10 | 4840.33 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.748896E+10 | 4840.33 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.839991E+10 | 4840.33 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.803398E+10 | 4840.33 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.833408E+10 | 4840.33 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.811917E+10 | 4840.33 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.824986E+10 | 4840.33 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.839991E+10 | 4840.33 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.803591E+10 | 4840.33 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.826728E+10 | 4840.33 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.800397E+10 | 4840.33 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.825082E+10 | 4840.33 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.978521E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.748896E+10 | 4840.33 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.839991E+10 | 4840.33 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.248296E+10 | 1453.55 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.224894E+10 | 1453.55 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.252250E+10 | 1453.55 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.241261E+10 | 1453.55 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.250273E+10 | 1453.55 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.243819E+10 | 1453.55 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.247744E+10 | 1453.55 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.252250E+10 | 1453.55 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.241319E+10 | 1453.55 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.248267E+10 | 1453.55 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.240360E+10 | 1453.55 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.247773E+10 | 1453.55 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.293850E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.224894E+10 | 1453.55 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.252250E+10 | 1453.55 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.826825E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121656E+11 |
February | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100255E+11 |
March | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849954E+10 |
April | 0.292871E+11 | 0.803398E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31140534.67 | 0.517132E+10 |
May | 0.303219E+11 | 0.833408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362400E+09 | 0.327235E+10 |
June | 0.295292E+11 | 0.811917E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210202E+10 | 0.128815E+10 |
July | 0.300798E+11 | 0.824986E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261370E+10 | 0.507113E+09 |
August | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186099E+10 | 0.817017E+09 |
September | 0.292871E+11 | 0.803591E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624230E+09 | 0.185911E+10 |
October | 0.300980E+11 | 0.826728E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95470446.83 | 0.565453E+10 |
November | 0.290996E+11 | 0.800397E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951247E+10 |
December | 0.300798E+11 | 0.825082E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124219E+11 |
Annual Sum or Average | 0.356244E+12 | 0.978521E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768996E+10 | 0.711947E+11 |
Minimum of Months | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507113E+09 |
Maximum of Months | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261370E+10 | 0.124219E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.248296E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449815E+09 |
February | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430927E+09 |
March | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460367E+09 |
April | 0.786997E+09 | 0.241261E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 525.48 | 0.311392E+09 |
May | 0.814802E+09 | 0.250273E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3515090.79 | 0.262360E+09 |
June | 0.793501E+09 | 0.243819E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 27732834.91 | 0.159590E+09 |
July | 0.808298E+09 | 0.247744E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 35459694.36 | 0.103020E+09 |
August | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19213000.66 | 0.135178E+09 |
September | 0.786997E+09 | 0.241319E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 4816924.64 | 0.170404E+09 |
October | 0.808786E+09 | 0.248267E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 584366.20 | 0.264596E+09 |
November | 0.781956E+09 | 0.240360E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367129E+09 |
December | 0.808298E+09 | 0.247773E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395200E+09 |
Annual Sum or Average | 0.957291E+10 | 0.293850E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 91322437.04 | 0.350998E+10 |
Minimum of Months | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103020E+09 |
Maximum of Months | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 35459694.36 | 0.460367E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863432E+09 | 0.254289E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628953E+09 | 0.288911E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642622E+09 | 0.345231E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710982E+09 | 0.454212E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699865E+09 | 0.482426E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603871E+09 | 0.482256E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537494E+09 | 0.513063E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474453E+09 | 0.508539E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703366E+09 | 0.408677E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859403E+09 | 0.335956E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927151E+09 | 0.270948E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103102E+10 | 0.252942E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868262E+10 | 0.459745E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474453E+09 | 0.252942E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103102E+10 | 0.513063E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 4840.33 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 14995.09 | 19-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 4840.33 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 13695.95 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 4840.33 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 10609.37 | 04-MAR-19:53 |
April | 30255.31 | 01-APR-18:10 | 4840.33 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 978.84 | 13-APR-17:02 | 9947.12 | 15-APR-18:10 |
May | 30255.31 | 06-MAY-18:10 | 4840.33 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3006.81 | 19-MAY-17:03 | 8119.56 | 01-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 4840.33 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6503.59 | 28-JUN-17:02 | 7014.04 | 08-JUN-20:00 |
July | 30255.31 | 01-JUL-18:10 | 4840.33 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6608.42 | 21-JUL-17:03 | 3011.67 | 07-JUL-18:00 |
August | 30255.31 | 05-AUG-18:10 | 4840.33 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4603.33 | 04-AUG-17:03 | 3647.42 | 25-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 4840.33 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3088.93 | 20-SEP-17:02 | 4912.88 | 23-SEP-18:53 |
October | 30255.31 | 07-OCT-18:10 | 4840.33 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291.28 | 11-OCT-12:55 | 10613.15 | 24-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 4840.33 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 10703.48 | 27-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 4840.33 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 13495.53 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3011.67 | |||||
Maximum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 6608.42 | 14995.09 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1453.55 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1595.64 | 17-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 1453.55 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1614.63 | 05-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 1453.55 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1746.02 | 14-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 1453.55 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.75 | 13-APR-16:53 | 1611.46 | 23-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 1453.55 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 53.14 | 19-MAY-14:53 | 1349.14 | 18-MAY-02:20 |
June | 813.01 | 03-JUN-18:10 | 1453.55 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 119.40 | 17-JUN-15:53 | 1078.72 | 10-JUN-03:00 |
July | 813.01 | 01-JUL-18:10 | 1453.55 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 132.07 | 04-JUL-14:53 | 550.98 | 05-JUL-02:40 |
August | 813.01 | 05-AUG-18:10 | 1453.55 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 69.77 | 02-AUG-13:00 | 682.18 | 08-AUG-00:40 |
September | 813.01 | 02-SEP-18:10 | 1453.55 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 43.91 | 03-SEP-15:00 | 808.80 | 08-SEP-02:10 |
October | 813.01 | 07-OCT-18:10 | 1453.55 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 17.09 | 01-OCT-15:52 | 999.08 | 08-OCT-01:10 |
November | 813.01 | 04-NOV-18:10 | 1453.55 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1705.97 | 26-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 1453.55 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2310.01 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 550.98 | ||||||
Maximum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 132.07 | 2310.01 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1993.12 | 10-JAN-23:53 | 5307.39 | 29-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.71 | 14-FEB-07:23 | 6281.34 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.88 | 08-MAR-05:00 | 7070.58 | 30-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1838.08 | 01-APR-04:00 | 8158.36 | 08-APR-13:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1804.31 | 09-MAY-03:55 | 8261.56 | 28-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1821.32 | 20-JUN-02:00 | 7520.94 | 03-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.26 | 14-JUL-05:53 | 7253.84 | 28-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.28 | 17-AUG-04:10 | 7351.23 | 03-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1523.31 | 27-SEP-23:00 | 6920.40 | 09-SEP-12:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1778.83 | 29-OCT-22:00 | 6759.34 | 14-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.52 | 12-NOV-23:00 | 5884.37 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1786.09 | 13-DEC-02:70 | 5601.28 | 22-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.28 | 5307.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1993.12 | 8261.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24495.96 | 20-JAN-00:01 | 15127.65 | 7260.49 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21740.06 | 11-FEB-05:01 | 0.00 | 8067.21 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 |
March | 20831.26 | 08-MAR-14:00 | 23531.91 | 4840.33 | 6034.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.95 |
April | 106829.99 | 28-APR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.70 |
May | 108877.49 | 16-MAY-03:41 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.86 |
June | 109123.52 | 20-JUN-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.30 |
July | 80753.85 | 21-JUL-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.74 |
August | 80957.49 | 19-AUG-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.24 |
September | 100552.24 | 21-SEP-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
October | 113732.86 | 19-OCT-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 |
November | 100653.16 | 01-NOV-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.85 |
December | 22917.54 | 09-DEC-05:02 | 0.00 | 8067.21 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20831.26 | 0.00 | 4840.33 | 6034.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113732.86 | 23531.91 | 8067.21 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40748.18 | 26-JAN-05:01 | 451.67 | 3230.12 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 |
February | 44597.71 | 14-FEB-04:41 | 0.00 | 1938.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42912.71 | 31-MAR-03:41 | 0.00 | 1938.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 538.27 |
April | 73392.66 | 18-APR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 364.60 |
May | 70473.92 | 16-MAY-03:41 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 225.29 |
June | 66552.03 | 20-JUN-03:31 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 |
July | 47899.26 | 21-JUL-02:62 | 0.00 | 1453.55 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 |
August | 48021.53 | 29-AUG-03:41 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 221.59 |
September | 59004.72 | 22-SEP-03:31 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 226.65 |
October | 75358.54 | 31-OCT-03:41 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 330.52 |
November | 68126.48 | 10-NOV-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 314.08 |
December | 45061.43 | 15-DEC-05:01 | 451.67 | 3230.12 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40748.18 | 0.00 | 1453.55 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75358.54 | 451.67 | 3230.12 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 538.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.60 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.82 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.86 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.91 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.35 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.47 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.56 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.38 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.36 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.89 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.86 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.987909E+11 | 51780.97 | 05-JAN-17:30 | 0.118655E+12 | 104505.02 | 26-JAN-07:30 |
February | 0.891877E+11 | 54528.74 | 14-FEB-16:19 | 0.986081E+11 | 106957.02 | 06-FEB-07:30 |
March | 0.989900E+11 | 57569.88 | 08-MAR-13:00 | 0.852780E+11 | 84160.21 | 05-MAR-06:49 |
April | 0.100899E+12 | 65474.35 | 28-APR-18:49 | 0.709783E+11 | 60647.28 | 06-APR-06:40 |
May | 0.111596E+12 | 70276.96 | 23-MAY-10:00 | 0.690796E+11 | 44284.87 | 02-MAY-18:19 |
June | 0.123471E+12 | 82547.94 | 28-JUN-16:10 | 0.649110E+11 | 43449.48 | 03-JUN-10:30 |
July | 0.138199E+12 | 82093.20 | 21-JUL-17:19 | 0.655929E+11 | 43210.70 | 04-JUL-10:30 |
August | 0.133837E+12 | 77994.89 | 17-AUG-10:00 | 0.656189E+11 | 43136.06 | 27-AUG-10:00 |
September | 0.117740E+12 | 72972.86 | 02-SEP-18:30 | 0.640856E+11 | 43333.57 | 30-SEP-10:20 |
October | 0.106777E+12 | 71132.15 | 11-OCT-10:00 | 0.717254E+11 | 78573.02 | 26-OCT-06:00 |
November | 0.957199E+11 | 51867.68 | 09-NOV-17:49 | 0.815242E+11 | 91074.62 | 27-NOV-07:40 |
December | 0.988760E+11 | 51755.37 | 01-DEC-17:40 | 0.117052E+12 | 168904.99 | 15-DEC-04:19 |
Annual Sum or Average | 0.131408E+13 | 0.973109E+12 | ||||
Minimum of Months | 0.891877E+11 | 51755.37 | 0.640856E+11 | 43136.06 | ||
Maximum of Months | 0.138199E+12 | 82547.94 | 0.118655E+12 | 168904.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.107512E+11 | 0.716990E+10 | 0.391293E+11 | 0.00 | 0.303108E+11 | 37879553.69 | 0.00 | 2557141.68 | 0.00 | 0.00 | 0.00 | 0.639620E+10 | 0.00 |
February | 0.973789E+10 | 0.610678E+10 | 0.353426E+11 | 0.00 | 0.274218E+11 | 34213790.43 | 0.00 | 0.209483E+09 | 0.00 | 0.00 | 0.00 | 0.578798E+10 | 0.00 |
March | 0.109224E+11 | 0.622765E+10 | 0.391293E+11 | 0.00 | 0.303929E+11 | 37879553.69 | 0.00 | 0.639208E+09 | 0.00 | 0.00 | 0.00 | 0.645987E+10 | 0.00 |
April | 0.104466E+11 | 0.548044E+10 | 0.378671E+11 | 0.00 | 0.295837E+11 | 36657632.61 | 0.00 | 0.611300E+10 | 0.00 | 0.00 | 0.00 | 0.619906E+10 | 0.00 |
May | 0.108368E+11 | 0.519749E+10 | 0.391293E+11 | 0.00 | 0.308637E+11 | 37879553.69 | 0.00 | 0.136213E+11 | 0.00 | 0.00 | 0.00 | 0.641752E+10 | 0.00 |
June | 0.105574E+11 | 0.478268E+10 | 0.378671E+11 | 0.00 | 0.301281E+11 | 36657632.61 | 0.00 | 0.284470E+11 | 0.00 | 0.00 | 0.00 | 0.623671E+10 | 0.00 |
July | 0.107273E+11 | 0.507112E+10 | 0.391293E+11 | 0.00 | 0.313309E+11 | 37879553.69 | 0.00 | 0.398832E+11 | 0.00 | 0.00 | 0.00 | 0.637156E+10 | 0.00 |
August | 0.109224E+11 | 0.545297E+10 | 0.391293E+11 | 0.00 | 0.313251E+11 | 37879553.69 | 0.00 | 0.348618E+11 | 0.00 | 0.00 | 0.00 | 0.644976E+10 | 0.00 |
September | 0.104491E+11 | 0.579636E+10 | 0.378671E+11 | 0.00 | 0.301979E+11 | 36657632.61 | 0.00 | 0.217673E+11 | 0.00 | 0.00 | 0.00 | 0.619500E+10 | 0.00 |
October | 0.107500E+11 | 0.654356E+10 | 0.391293E+11 | 0.00 | 0.307636E+11 | 37879553.69 | 0.00 | 0.778018E+10 | 0.00 | 0.00 | 0.00 | 0.638405E+10 | 0.00 |
November | 0.104076E+11 | 0.681003E+10 | 0.378671E+11 | 0.00 | 0.294328E+11 | 36657632.61 | 0.00 | 40762736.51 | 0.00 | 0.00 | 0.00 | 0.618728E+10 | 0.00 |
December | 0.107286E+11 | 0.730176E+10 | 0.391293E+11 | 0.00 | 0.303362E+11 | 37879553.69 | 0.00 | 2723684.82 | 0.00 | 0.00 | 0.00 | 0.638910E+10 | 0.00 |
Annual Sum or Average | 0.127237E+12 | 0.719407E+11 | 0.460716E+12 | 0.00 | 0.362087E+12 | 0.446001E+09 | 0.00 | 0.153368E+12 | 0.00 | 0.00 | 0.00 | 0.754741E+11 | 0.00 |
Minimum of Months | 0.973789E+10 | 0.478268E+10 | 0.353426E+11 | 0.00 | 0.274218E+11 | 34213790.43 | 0.00 | 2557141.68 | 0.00 | 0.00 | 0.00 | 0.578798E+10 | 0.00 |
Maximum of Months | 0.109224E+11 | 0.730176E+10 | 0.391293E+11 | 0.00 | 0.313309E+11 | 37879553.69 | 0.00 | 0.398832E+11 | 0.00 | 0.00 | 0.00 | 0.645987E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.460064E+11 | 0.00 | 0.327493E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.327417E+11 | 0.00 | 0.298280E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.128677E+11 | 0.00 | 0.325105E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.263609E+10 | 0.00 | 0.297296E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.341837E+09 | 0.00 | 0.288381E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 41784317.07 | 0.00 | 0.262566E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 12052720.15 | 0.00 | 0.256812E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 10108574.13 | 0.00 | 0.257091E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 25495727.24 | 0.00 | 0.254474E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.402800E+10 | 0.00 | 0.277977E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.140796E+11 | 0.00 | 0.288320E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.455827E+11 | 0.00 | 0.315692E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.158374E+12 | 0.00 | 0.344949E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 10108574.13 | 0.00 | 0.254474E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.460064E+11 | 0.00 | 0.327493E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6293.88 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13529.82 | 01-JAN-05:10 | 17.86 | 19-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 6293.88 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13529.82 | 01-FEB-05:10 | 17.86 | 06-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 6293.88 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13529.82 | 11-MAR-14:20 | 17.86 | 30-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 6293.88 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13529.82 | 01-APR-06:00 | 17.86 | 07-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 6293.88 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13529.82 | 01-MAY-07:40 | 17.86 | 30-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 6293.88 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13529.82 | 01-JUN-10:39 | 17.86 | 03-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 6293.88 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13529.82 | 01-JUL-04:10 | 17.86 | 07-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 6293.88 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13529.82 | 29-AUG-22:10 | 17.86 | 05-AUG-08:39 | 0.00 | 01-AUG-00:10 |
September | 6293.88 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13529.82 | 01-SEP-04:10 | 17.86 | 03-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 6293.88 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13529.82 | 01-OCT-08:20 | 17.86 | 20-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 6293.88 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13529.82 | 01-NOV-07:49 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 6293.88 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13529.82 | 04-DEC-22:49 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13529.82 | 17.86 | 0.00 | ||||||
Maximum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13529.82 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 587.94 | 24-JAN-04:19 | 0.00 | 0.00 | 0.00 | 4742.00 | 25-JAN-19:00 | 0.00 |
February | 8159.81 | 14-FEB-16:10 | 0.00 | 0.00 | 0.00 | 4741.84 | 07-FEB-07:49 | 0.00 |
March | 11428.01 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 4742.27 | 03-MAR-19:30 | 0.00 |
April | 18102.77 | 13-APR-17:10 | 0.00 | 0.00 | 0.00 | 4741.87 | 19-APR-06:40 | 0.00 |
May | 22678.01 | 19-MAY-17:19 | 0.00 | 0.00 | 0.00 | 4741.40 | 02-MAY-06:49 | 0.00 |
June | 35276.25 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 4739.84 | 09-JUN-06:00 | 0.00 |
July | 35427.11 | 21-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.68 | 19-JUL-06:19 | 0.00 |
August | 29016.59 | 17-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4737.42 | 31-AUG-06:19 | 0.00 |
September | 25072.16 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 4737.94 | 11-SEP-06:19 | 0.00 |
October | 21616.01 | 10-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4741.78 | 13-OCT-06:40 | 0.00 |
November | 4930.59 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4741.97 | 15-NOV-07:49 | 0.00 |
December | 591.30 | 29-DEC-04:19 | 0.00 | 0.00 | 0.00 | 4741.50 | 05-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 587.94 | 0.00 | 0.00 | 0.00 | 4736.68 | 0.00 | ||
Maximum of Months | 35427.11 | 0.00 | 0.00 | 0.00 | 4742.27 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 51780.97 | 05-JAN-17:30 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 54528.74 | 14-FEB-16:19 | 6293.88 | 22286.02 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 7873.95 | 0.00 |
March | 57569.88 | 08-MAR-13:00 | 6293.88 | 21481.47 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 11428.01 | 0.00 |
April | 65474.35 | 28-APR-18:49 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 15239.15 | 0.00 |
May | 70276.96 | 23-MAY-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 19177.33 | 0.00 |
June | 82547.94 | 28-JUN-16:10 | 6293.88 | 22286.02 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 35276.25 | 0.00 |
July | 82093.20 | 21-JUL-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 35110.64 | 0.00 |
August | 77994.89 | 17-AUG-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 27215.78 | 0.00 |
September | 72972.86 | 02-SEP-18:30 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 22989.40 | 0.00 |
October | 71132.15 | 11-OCT-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 20025.97 | 0.00 |
November | 51867.68 | 09-NOV-17:49 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 51755.37 | 01-DEC-17:40 | 6293.88 | 22286.02 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 51755.37 | 6293.88 | 19067.80 | 0.00 | 0.00 | 13529.82 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82547.94 | 6293.88 | 24699.69 | 4578.48 | 0.00 | 13529.82 | 17.86 | 0.00 | 35276.25 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 77486.52 | 21-JAN-06:00 | 0.00 | 30036.75 | 31-JAN-07:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 84617.39 | 04-FEB-04:49 | 0.00 | 30106.19 | 07-FEB-19:00 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 57911.08 | 05-MAR-06:00 | 0.00 | 29658.81 | 02-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 32400.43 | 08-APR-05:00 | 0.00 | 27651.72 | 03-APR-06:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 13325.50 | 06-MAY-05:00 | 0.00 | 24672.70 | 01-MAY-06:49 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 19599.23 | 14-JUN-03:49 | 0.00 | 20646.51 | 01-JUN-18:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 6019.51 | 28-JUL-03:49 | 0.00 | 17715.72 | 03-JUL-18:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 6970.66 | 27-AUG-03:49 | 0.00 | 17631.51 | 31-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 9083.80 | 04-SEP-03:49 | 0.00 | 18348.76 | 27-SEP-18:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 50737.38 | 26-OCT-05:10 | 0.00 | 22921.14 | 31-OCT-06:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 59366.42 | 27-NOV-06:10 | 0.00 | 26404.98 | 30-NOV-07:49 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 163386.04 | 15-DEC-04:19 | 0.00 | 28837.95 | 29-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 6019.51 | 0.00 | 17631.51 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 163386.04 | 0.00 | 30106.19 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 0.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.65 | 0.00 | 24.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.84 | 0.00 | 24.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.82 | 0.00 | 24.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.84 | 0.00 | 24.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.93 | 0.00 | 24.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.91 | 0.00 | 24.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
Annual Sum or Average | 1.83 | 20.28 | 0.00 | 20.28 | 20.17 | 24.47 | 0.00 | 24.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.41 | 0.00 | 20.41 | 5.00 | 24.93 | 0.00 | 24.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.02 | 0.00 | 27.02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.17 | 0.00 | 27.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 0.00 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 29.46 | 0.00 | 29.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 30.33 | 0.00 | 30.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 30.76 | 0.00 | 30.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 30.97 | 0.00 | 30.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 30.98 | 0.00 | 30.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.90 | 0.00 | 30.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 30.31 | 0.00 | 30.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.90 | 0.00 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.95 | 0.00 | 26.95 |
Annual Sum or Average | 0.00 | 0.00 | 170.50 | 30.39 | 0.00 | 30.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.95 | 0.00 | 26.95 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 30.98 | 0.00 | 30.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 555.00 | 21.29 | 74.33 | 21.11 | 74.33 | 20.97 |
February | 459.50 | 21.34 | 54.50 | 21.16 | 54.50 | 21.02 |
March | 389.00 | 21.84 | 15.50 | 21.78 | 12.50 | 21.70 |
April | 200.67 | 22.30 | 93.33 | 22.84 | 0.83 | 22.83 |
May | 89.50 | 22.80 | 332.33 | 23.79 | 2.83 | 23.79 |
June | 13.00 | 24.59 | 529.83 | 24.14 | 5.17 | 24.16 |
July | 92.00 | 24.82 | 608.83 | 24.25 | 92.00 | 24.32 |
August | 68.33 | 24.75 | 612.00 | 24.21 | 68.33 | 24.26 |
September | 27.33 | 24.04 | 563.83 | 24.08 | 26.33 | 24.08 |
October | 157.50 | 21.81 | 309.50 | 23.25 | 4.00 | 23.23 |
November | 390.17 | 21.60 | 50.50 | 21.73 | 14.00 | 21.67 |
December | 589.00 | 21.19 | 86.33 | 21.03 | 86.33 | 20.91 |
Annual Sum or Average | 3031.00 | 21.75 | 3330.83 | 22.82 | 441.17 | 22.76 |
Minimum of Months | 13.00 | 21.19 | 15.50 | 21.03 | 0.83 | 20.91 |
Maximum of Months | 589.00 | 24.82 | 612.00 | 24.25 | 92.00 | 24.32 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 568.83 | 19.48 | 217.50 | 19.46 | 200.50 | 19.37 |
February | 477.17 | 19.55 | 187.33 | 19.79 | 144.17 | 19.65 |
March | 383.33 | 19.95 | 236.83 | 21.38 | 62.33 | 21.22 |
April | 358.50 | 22.88 | 357.00 | 24.10 | 170.00 | 24.38 |
May | 398.00 | 25.15 | 511.50 | 25.38 | 337.17 | 25.54 |
June | 503.33 | 25.94 | 580.67 | 25.86 | 498.67 | 25.90 |
July | 608.67 | 26.00 | 609.00 | 26.00 | 608.67 | 26.00 |
August | 603.50 | 25.97 | 612.00 | 25.96 | 603.50 | 25.97 |
September | 496.17 | 25.96 | 586.83 | 25.82 | 496.17 | 25.87 |
October | 434.67 | 23.53 | 413.17 | 24.37 | 270.83 | 24.69 |
November | 453.83 | 19.96 | 165.33 | 20.56 | 81.50 | 20.52 |
December | 599.83 | 19.27 | 208.50 | 19.20 | 208.50 | 19.16 |
Annual Sum or Average | 5885.83 | 22.86 | 4685.67 | 23.66 | 3682.00 | 23.92 |
Minimum of Months | 358.50 | 19.27 | 165.33 | 19.20 | 62.33 | 19.16 |
Maximum of Months | 608.67 | 26.00 | 612.00 | 26.00 | 608.67 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.52933 | 21.07861 | -0.2905 | 8.80533 |
February | 551.00000 | 21.77652 | 22.61353 | -0.2188 | 8.39179 |
March | 612.00000 | 22.61371 | 21.66687 | -0.0118 | 7.12535 |
April | 590.00000 | 23.42828 | 18.16727 | 0.20144 | 7.28152 |
May | 611.00000 | 23.86044 | 25.73485 | -0.4790 | 11.12987 |
June | 592.00000 | 24.09127 | 33.96377 | -0.2761 | 7.20918 |
July | 609.00000 | 24.16345 | 45.19328 | -0.1395 | 5.91225 |
August | 612.00000 | 24.14568 | 44.56498 | -0.1404 | 5.87155 |
September | 590.00000 | 24.06950 | 39.41012 | -0.2217 | 6.45053 |
October | 610.00000 | 23.44213 | 26.99872 | 0.30888 | 9.01057 |
November | 591.00000 | 22.40023 | 22.29213 | -0.0221 | 7.21224 |
December | 609.00000 | 21.28082 | 19.32893 | -0.3430 | 8.92136 |
Annual Sum or Average | 7187.00000 | 23.07315 | 28.46682 | -0.1360 | 7.77958 |
Minimum of Months | 551.00000 | 21.28082 | 18.16727 | -0.4790 | 5.87155 |
Maximum of Months | 612.00000 | 24.16345 | 45.19328 | 0.30888 | 11.12987 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.75774 | 26.79501 | -0.4460 | 11.38117 |
February | 551.00000 | 20.16643 | 28.27921 | -0.3491 | 11.44704 |
March | 612.00000 | 21.69481 | 26.81019 | 0.00509 | 11.38650 |
April | 590.00000 | 23.59601 | 22.19891 | 0.44181 | 15.78519 |
May | 611.00000 | 24.88865 | 27.49686 | 0.12148 | 12.82581 |
June | 592.00000 | 25.71947 | 33.79301 | 0.50374 | 12.48101 |
July | 609.00000 | 25.99566 | 43.63911 | 0.70453 | 15.91541 |
August | 612.00000 | 25.95535 | 42.98306 | 0.68521 | 15.49260 |
September | 590.00000 | 25.69322 | 38.74919 | 0.54276 | 13.09057 |
October | 610.00000 | 23.70189 | 29.89742 | 0.56908 | 19.86407 |
November | 591.00000 | 20.82471 | 27.38139 | -0.1438 | 10.21296 |
December | 609.00000 | 19.31739 | 24.92748 | -0.5431 | 12.15083 |
Annual Sum or Average | 7187.00000 | 23.12517 | 31.10931 | 0.17697 | 13.52541 |
Minimum of Months | 551.00000 | 19.31739 | 22.19891 | -0.5431 | 10.21296 |
Maximum of Months | 612.00000 | 25.99566 | 43.63911 | 0.70453 | 19.86407 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 28468.69 | 10401.80 | 0.53 | 28468.69 | -0.0 | 0.00 | 0.00 | 25-JAN-15:30 | 0.00 | 01-JAN-00:03 | 23.64 | 25-JAN-15:30 | 23.64 | 25-JAN-15:30 | 0.00 | 25-JAN-15:37 | 8.64 | 25-JAN-15:30 | 0.00 | 01-JAN-00:03 |
February | 0.475592E+09 | 0.166264E+09 | 12.17 | 0.475592E+09 | 0.00 | 0.00 | 0.25 | 14-FEB-15:00 | 0.00 | 01-FEB-00:01 | 17619.65 | 14-FEB-15:00 | 17619.65 | 14-FEB-15:00 | 0.00 | 14-FEB-16:10 | 6069.48 | 14-FEB-15:00 | 0.00 | 01-FEB-00:01 |
March | 0.149208E+10 | 0.525960E+09 | 62.75 | 0.149201E+10 | 70956.31 | 0.00 | 0.36 | 08-MAR-14:00 | 0.00 | 01-MAR-00:03 | 25858.90 | 08-MAR-14:00 | 25858.90 | 08-MAR-14:00 | 65.46 | 16-MAR-12:15 | 8675.31 | 08-MAR-14:00 | 0.00 | 01-MAR-00:03 |
April | 0.128002E+11 | 0.433915E+10 | 212.38 | 0.127958E+11 | 4415315.13 | 0.00 | 1.00 | 13-APR-03:01 | 0.00 | 01-APR-00:01 | 86130.01 | 27-APR-03:01 | 86130.01 | 13-APR-03:01 | 12554.99 | 15-APR-03:01 | 24265.03 | 13-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.274499E+11 | 0.913560E+10 | 345.22 | 0.268770E+11 | 0.572855E+09 | 0.00 | 1.00 | 09-MAY-03:01 | 0.00 | 01-MAY-00:01 | 86130.01 | 19-MAY-03:01 | 86130.01 | 16-MAY-03:41 | 34157.61 | 24-MAY-03:01 | 24265.03 | 09-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.547462E+11 | 0.182234E+11 | 465.92 | 0.524749E+11 | 0.227131E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 86130.01 | 06-JUN-03:01 | 86130.01 | 14-JUN-03:43 | 37712.75 | 05-JUN-03:01 | 24265.03 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.776921E+11 | 0.254228E+11 | 571.78 | 0.659092E+11 | 0.117829E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 86904.03 | 16-JUL-03:01 | 85069.54 | 21-JUL-03:01 | 45290.66 | 01-JUL-03:51 | 24326.61 | 16-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.693438E+11 | 0.224920E+11 | 539.16 | 0.590298E+11 | 0.103140E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 86764.73 | 14-AUG-03:01 | 83458.36 | 19-AUG-03:01 | 43213.05 | 26-AUG-03:01 | 24315.57 | 14-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.440517E+11 | 0.143930E+11 | 434.16 | 0.390985E+11 | 0.495323E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 86130.01 | 02-SEP-03:42 | 82343.66 | 21-SEP-03:01 | 41512.73 | 06-SEP-03:01 | 24265.03 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.161757E+11 | 0.538896E+10 | 230.33 | 0.150234E+11 | 0.115233E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 86130.01 | 01-OCT-03:01 | 86130.01 | 16-OCT-03:01 | 28236.48 | 03-OCT-03:01 | 24265.03 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 72712276.93 | 25560884.01 | 5.28 | 68777173.09 | 3935103.84 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 86130.01 | 01-NOV-03:01 | 69934.70 | 01-NOV-03:01 | 16195.31 | 01-NOV-03:01 | 24265.03 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 178.20 | 65.11 | 0.08 | 178.20 | 0.00 | 0.00 | 0.00 | 29-DEC-14:25 | 0.00 | 01-DEC-00:05 | 0.59 | 29-DEC-14:25 | 0.59 | 29-DEC-14:25 | 0.00 | 01-DEC-00:05 | 0.22 | 29-DEC-14:25 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.304300E+12 | 0.100113E+12 | 2879.77 | 0.273245E+12 | 0.310550E+11 | 0.00 | ||||||||||||||
Minimum of Months | 178.20 | 65.11 | 0.08 | 178.20 | -0.0 | 0.00 | 0.00 | 0.00 | 0.59 | 0.59 | 0.00 | 0.22 | 0.00 | |||||||
Maximum of Months | 0.776921E+11 | 0.254228E+11 | 571.78 | 0.659092E+11 | 0.117829E+11 | 0.00 | 1.00 | 0.00 | 86904.03 | 86130.01 | 45290.66 | 24326.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 7263137.16 | 2546739.88 | 0.96 | 5791165.27 | 1471971.89 | 0.00 | 0.14 | 10-JAN-04:08 | 0.00 | 01-JAN-00:03 | 4723.56 | 10-JAN-04:08 | 3949.98 | 10-JAN-04:08 | 1218.01 | 13-JAN-04:10 | 1638.57 | 10-JAN-04:08 | 0.00 | 01-JAN-00:03 |
February | 0.124265E+09 | 43219078.36 | 10.41 | 0.121855E+09 | 2409286.06 | 0.00 | 0.18 | 14-FEB-15:55 | 0.00 | 01-FEB-00:01 | 6504.92 | 14-FEB-15:55 | 6504.92 | 14-FEB-15:55 | 1474.95 | 17-FEB-04:08 | 2230.35 | 14-FEB-15:55 | 0.00 | 01-FEB-00:01 |
March | 0.325714E+09 | 0.113248E+09 | 33.07 | 0.323127E+09 | 2587011.02 | 0.00 | 0.23 | 08-MAR-16:07 | 0.00 | 01-MAR-00:03 | 8129.22 | 08-MAR-16:07 | 8129.22 | 08-MAR-16:07 | 1171.33 | 03-MAR-04:08 | 2758.12 | 08-MAR-16:07 | 0.00 | 01-MAR-00:03 |
April | 0.532968E+10 | 0.177385E+10 | 185.56 | 0.530992E+10 | 19760762.16 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 43706.76 | 13-APR-03:01 | 43706.76 | 13-APR-03:01 | 11730.35 | 15-APR-03:21 | 12064.80 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.138601E+11 | 0.448574E+10 | 318.73 | 0.133943E+11 | 0.465750E+09 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 43706.76 | 21-MAY-03:01 | 43706.76 | 20-MAY-03:01 | 21594.47 | 24-MAY-03:01 | 12064.80 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.320137E+11 | 0.102236E+11 | 466.12 | 0.305040E+11 | 0.150972E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 43706.76 | 22-JUN-00:42 | 41190.33 | 28-JUN-00:42 | 22612.34 | 05-JUN-03:31 | 13531.83 | 28-JUN-15:57 | 0.00 | 01-JUN-00:01 |
July | 0.462918E+11 | 0.144604E+11 | 586.27 | 0.392692E+11 | 0.702263E+10 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 44327.53 | 01-JUL-03:01 | 39987.71 | 21-JUL-00:42 | 26328.09 | 01-JUL-03:01 | 13177.57 | 22-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.396487E+11 | 0.123698E+11 | 548.65 | 0.334189E+11 | 0.622983E+10 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 43706.76 | 10-AUG-03:21 | 38995.36 | 16-AUG-00:42 | 26078.55 | 13-AUG-03:01 | 12064.80 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 |
September | 0.232689E+11 | 0.737432E+10 | 414.27 | 0.200199E+11 | 0.324900E+10 | 0.00 | 1.00 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 | 43706.76 | 30-SEP-03:21 | 36928.76 | 22-SEP-03:31 | 25100.08 | 06-SEP-03:31 | 12064.80 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 |
October | 0.738070E+10 | 0.239121E+10 | 197.33 | 0.656980E+10 | 0.810901E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 43706.76 | 09-OCT-03:01 | 39797.54 | 16-OCT-03:01 | 19219.90 | 03-OCT-04:01 | 12064.80 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 47227058.40 | 15201852.49 | 4.67 | 36041600.03 | 11185458.37 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 43706.76 | 01-NOV-04:01 | 32039.01 | 09-NOV-04:01 | 17061.33 | 03-NOV-03:41 | 12064.80 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 7714687.77 | 2723619.70 | 1.65 | 6443022.61 | 1271665.17 | 0.00 | 0.12 | 26-DEC-04:10 | 0.00 | 01-DEC-00:05 | 3984.59 | 26-DEC-04:10 | 3052.81 | 19-DEC-04:08 | 1150.56 | 26-DEC-04:10 | 1388.98 | 26-DEC-04:10 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.168306E+12 | 0.532559E+11 | 2767.69 | 0.148979E+12 | 0.193265E+11 | 0.00 | ||||||||||||||
Minimum of Months | 7263137.16 | 2546739.88 | 0.96 | 5791165.27 | 1271665.17 | 0.00 | 0.12 | 0.00 | 3984.59 | 3052.81 | 1150.56 | 1388.98 | 0.00 | |||||||
Maximum of Months | 0.462918E+11 | 0.144604E+11 | 586.27 | 0.392692E+11 | 0.702263E+10 | 0.00 | 1.00 | 0.00 | 44327.53 | 43706.76 | 26328.09 | 13531.83 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.39 | 172.05 | 135.34 | 243.43 | 461.50 | 0.00 | 0.00 | 0.00 |
February | 372.25 | 200.10 | 172.15 | 329.05 | 417.20 | 0.00 | 0.00 | 0.00 |
March | 494.68 | 281.82 | 212.86 | 505.76 | 329.29 | 0.00 | 0.00 | 0.00 |
April | 671.05 | 381.87 | 289.19 | 769.82 | 229.10 | 0.00 | 0.00 | 0.00 |
May | 641.09 | 365.16 | 275.93 | 783.61 | 176.26 | 0.00 | 0.00 | 0.00 |
June | 691.38 | 425.86 | 265.52 | 949.92 | 116.26 | 0.00 | 0.00 | 0.00 |
July | 639.42 | 365.53 | 273.89 | 926.58 | 79.62 | 0.00 | 0.00 | 0.00 |
August | 632.87 | 348.83 | 284.04 | 879.48 | 92.60 | 0.00 | 0.00 | 0.00 |
September | 527.73 | 295.29 | 232.44 | 680.99 | 156.62 | 0.00 | 0.00 | 0.00 |
October | 459.78 | 291.97 | 167.81 | 508.13 | 269.00 | 0.00 | 0.00 | 0.00 |
November | 357.59 | 209.78 | 147.82 | 324.60 | 383.91 | 0.00 | 0.00 | 0.00 |
December | 291.28 | 177.67 | 113.61 | 237.11 | 485.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.72 | 293.37 | 214.35 | 596.11 | 265.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 291.28 | 172.05 | 113.61 | 237.11 | 79.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 691.38 | 425.86 | 289.19 | 949.92 | 485.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1132.82 | 880.95 | 251.86 | 1274.14 | 609.36 | 0.00 | 0.00 | 0.00 |
February | 1116.63 | 817.22 | 299.41 | 1282.37 | 563.52 | 0.00 | 0.00 | 0.00 |
March | 830.32 | 506.67 | 323.65 | 963.41 | 468.22 | 0.00 | 0.00 | 0.00 |
April | 637.69 | 261.33 | 376.36 | 758.98 | 343.36 | 0.00 | 0.00 | 0.00 |
May | 429.17 | 97.09 | 332.08 | 511.77 | 259.65 | 0.00 | 0.00 | 0.00 |
June | 358.77 | 43.08 | 315.69 | 521.68 | 175.46 | 0.00 | 0.00 | 0.00 |
July | 397.14 | 62.31 | 334.83 | 639.90 | 115.30 | 0.00 | 0.00 | 0.00 |
August | 540.24 | 170.39 | 369.85 | 822.58 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 766.94 | 431.72 | 335.22 | 1074.89 | 227.68 | 0.00 | 0.00 | 0.00 |
October | 1033.26 | 760.05 | 273.21 | 1293.19 | 369.87 | 0.00 | 0.00 | 0.00 |
November | 1165.55 | 897.03 | 268.52 | 1346.17 | 506.25 | 0.00 | 0.00 | 0.00 |
December | 1235.35 | 1019.76 | 215.58 | 1401.92 | 621.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 801.87 | 493.95 | 307.92 | 989.24 | 365.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.77 | 43.08 | 215.58 | 511.77 | 115.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1235.35 | 1019.76 | 376.36 | 1401.92 | 621.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.01 | 180.79 | 136.22 | 282.16 | 485.14 | 0.00 | 0.00 | 0.00 |
February | 407.26 | 235.00 | 172.27 | 394.61 | 435.73 | 0.00 | 0.00 | 0.00 |
March | 454.43 | 241.39 | 213.04 | 468.79 | 347.67 | 0.00 | 0.00 | 0.00 |
April | 581.39 | 309.42 | 271.96 | 654.33 | 241.80 | 0.00 | 0.00 | 0.00 |
May | 552.86 | 285.66 | 267.21 | 666.56 | 182.75 | 0.00 | 0.00 | 0.00 |
June | 589.11 | 328.09 | 261.02 | 818.00 | 126.52 | 0.00 | 0.00 | 0.00 |
July | 531.88 | 259.90 | 271.98 | 779.55 | 83.34 | 0.00 | 0.00 | 0.00 |
August | 544.07 | 251.28 | 292.78 | 763.24 | 97.94 | 0.00 | 0.00 | 0.00 |
September | 493.64 | 260.63 | 233.01 | 645.15 | 165.66 | 0.00 | 0.00 | 0.00 |
October | 451.76 | 281.39 | 170.37 | 515.87 | 287.06 | 0.00 | 0.00 | 0.00 |
November | 353.01 | 207.66 | 145.35 | 332.16 | 398.35 | 0.00 | 0.00 | 0.00 |
December | 303.12 | 189.29 | 113.84 | 266.13 | 500.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.00 | 252.42 | 212.58 | 549.45 | 278.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.12 | 180.79 | 113.84 | 266.13 | 83.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 589.11 | 328.09 | 292.78 | 818.00 | 500.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823309E+09 | 0.460814E+09 | 0.362495E+09 | 0.652013E+09 | 0.123608E+10 |
February | 0.900536E+09 | 0.484081E+09 | 0.416455E+09 | 0.796043E+09 | 0.100930E+10 |
March | 0.132495E+10 | 0.754821E+09 | 0.570126E+09 | 0.135462E+10 | 0.881978E+09 |
April | 0.173937E+10 | 0.989803E+09 | 0.749570E+09 | 0.199537E+10 | 0.593831E+09 |
May | 0.171710E+10 | 0.978046E+09 | 0.739051E+09 | 0.209882E+10 | 0.472095E+09 |
June | 0.179206E+10 | 0.110384E+10 | 0.688216E+09 | 0.246220E+10 | 0.301357E+09 |
July | 0.171262E+10 | 0.979037E+09 | 0.733588E+09 | 0.248175E+10 | 0.213261E+09 |
August | 0.169507E+10 | 0.934296E+09 | 0.760770E+09 | 0.235560E+10 | 0.248007E+09 |
September | 0.136788E+10 | 0.765398E+09 | 0.602484E+09 | 0.176512E+10 | 0.405956E+09 |
October | 0.123148E+10 | 0.782015E+09 | 0.449467E+09 | 0.136096E+10 | 0.720479E+09 |
November | 0.926882E+09 | 0.543745E+09 | 0.383137E+09 | 0.841362E+09 | 0.995095E+09 |
December | 0.780158E+09 | 0.475874E+09 | 0.304285E+09 | 0.635064E+09 | 0.130064E+10 |
Annual Sum or Average | 0.160114E+11 | 0.925177E+10 | 0.675964E+10 | 0.187989E+11 | 0.837807E+10 |
Minimum of Months | 0.780158E+09 | 0.460814E+09 | 0.304285E+09 | 0.635064E+09 | 0.213261E+09 |
Maximum of Months | 0.179206E+10 | 0.110384E+10 | 0.760770E+09 | 0.248175E+10 | 0.130064E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303413E+10 | 0.235954E+10 | 0.674595E+09 | 0.341264E+10 | 0.163212E+10 |
February | 0.270136E+10 | 0.197702E+10 | 0.724336E+09 | 0.310231E+10 | 0.136326E+10 |
March | 0.222393E+10 | 0.135706E+10 | 0.866876E+09 | 0.258039E+10 | 0.125409E+10 |
April | 0.165289E+10 | 0.677374E+09 | 0.975514E+09 | 0.196726E+10 | 0.889978E+09 |
May | 0.114949E+10 | 0.260044E+09 | 0.889445E+09 | 0.137072E+10 | 0.695439E+09 |
June | 0.929943E+09 | 0.111665E+09 | 0.818278E+09 | 0.135220E+10 | 0.454783E+09 |
July | 0.106370E+10 | 0.166901E+09 | 0.896798E+09 | 0.171392E+10 | 0.308833E+09 |
August | 0.144699E+10 | 0.456374E+09 | 0.990617E+09 | 0.220320E+10 | 0.364554E+09 |
September | 0.198792E+10 | 0.111902E+10 | 0.868897E+09 | 0.278612E+10 | 0.590158E+09 |
October | 0.276749E+10 | 0.203572E+10 | 0.731779E+09 | 0.346368E+10 | 0.990664E+09 |
November | 0.302111E+10 | 0.232510E+10 | 0.696011E+09 | 0.348928E+10 | 0.131220E+10 |
December | 0.330875E+10 | 0.273134E+10 | 0.577419E+09 | 0.375490E+10 | 0.166489E+10 |
Annual Sum or Average | 0.252877E+11 | 0.155771E+11 | 0.971056E+10 | 0.311966E+11 | 0.115210E+11 |
Minimum of Months | 0.929943E+09 | 0.111665E+09 | 0.577419E+09 | 0.135220E+10 | 0.308833E+09 |
Maximum of Months | 0.330875E+10 | 0.273134E+10 | 0.990617E+09 | 0.375490E+10 | 0.166489E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.849074E+09 | 0.484231E+09 | 0.364843E+09 | 0.755732E+09 | 0.129939E+10 |
February | 0.985250E+09 | 0.568501E+09 | 0.416748E+09 | 0.954629E+09 | 0.105412E+10 |
March | 0.121714E+10 | 0.646543E+09 | 0.570602E+09 | 0.125561E+10 | 0.931193E+09 |
April | 0.150695E+10 | 0.802021E+09 | 0.704932E+09 | 0.169602E+10 | 0.626736E+09 |
May | 0.148079E+10 | 0.765106E+09 | 0.715684E+09 | 0.178531E+10 | 0.489482E+09 |
June | 0.152696E+10 | 0.850402E+09 | 0.676560E+09 | 0.212026E+10 | 0.327927E+09 |
July | 0.142460E+10 | 0.696121E+09 | 0.728478E+09 | 0.208795E+10 | 0.223208E+09 |
August | 0.145722E+10 | 0.673032E+09 | 0.784193E+09 | 0.204427E+10 | 0.262326E+09 |
September | 0.127951E+10 | 0.675554E+09 | 0.603961E+09 | 0.167223E+10 | 0.429380E+09 |
October | 0.120999E+10 | 0.753674E+09 | 0.456312E+09 | 0.138171E+10 | 0.768855E+09 |
November | 0.914990E+09 | 0.538252E+09 | 0.376739E+09 | 0.860962E+09 | 0.103253E+10 |
December | 0.811882E+09 | 0.506984E+09 | 0.304898E+09 | 0.712796E+09 | 0.134089E+10 |
Annual Sum or Average | 0.146644E+11 | 0.796042E+10 | 0.670395E+10 | 0.173275E+11 | 0.878604E+10 |
Minimum of Months | 0.811882E+09 | 0.484231E+09 | 0.304898E+09 | 0.712796E+09 | 0.223208E+09 |
Maximum of Months | 0.152696E+10 | 0.850402E+09 | 0.784193E+09 | 0.212026E+10 | 0.134089E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1734.54 | 1490.81 | 1757.21 | 1233.79 | 523.42 | 0.00 | 0.00 |
February | 1953.39 | 1363.81 | 1896.14 | 1252.32 | 643.82 | 0.00 | 0.00 |
March | 1886.65 | 1093.88 | 1779.43 | 1029.88 | 749.55 | 0.00 | 0.00 |
April | 2129.32 | 760.45 | 1890.13 | 952.62 | 937.51 | 0.00 | 0.00 |
May | 1931.00 | 587.72 | 1623.12 | 747.91 | 875.22 | 0.00 | 0.00 |
June | 2266.14 | 394.77 | 1639.26 | 797.03 | 842.23 | 0.00 | 0.00 |
July | 2338.44 | 270.67 | 1568.45 | 687.75 | 880.70 | 0.00 | 0.00 |
August | 2453.08 | 314.42 | 1717.17 | 770.50 | 946.68 | 0.00 | 0.00 |
September | 2380.72 | 529.66 | 1788.32 | 987.64 | 800.67 | 0.00 | 0.00 |
October | 2278.87 | 887.61 | 1944.80 | 1333.41 | 611.39 | 0.00 | 0.00 |
November | 1948.68 | 1234.25 | 1876.15 | 1314.47 | 561.68 | 0.00 | 0.00 |
December | 1818.37 | 1521.05 | 1829.75 | 1386.72 | 443.03 | 0.00 | 0.00 |
Annual Sum or Average | 2093.45 | 868.25 | 1774.59 | 1039.74 | 734.85 | 0.00 | 0.00 |
Minimum of Months | 1734.54 | 270.67 | 1568.45 | 687.75 | 443.03 | 0.00 | 0.00 |
Maximum of Months | 2453.08 | 1521.05 | 1944.80 | 1386.72 | 946.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464578E+10 | 0.399298E+10 | 0.470652E+10 | 0.330458E+10 | 0.140193E+10 | 0.00 | 0.00 |
February | 0.472563E+10 | 0.329933E+10 | 0.458714E+10 | 0.302961E+10 | 0.155754E+10 | 0.00 | 0.00 |
March | 0.505320E+10 | 0.292984E+10 | 0.476602E+10 | 0.275842E+10 | 0.200760E+10 | 0.00 | 0.00 |
April | 0.551919E+10 | 0.197109E+10 | 0.489921E+10 | 0.246920E+10 | 0.243002E+10 | 0.00 | 0.00 |
May | 0.517200E+10 | 0.157416E+10 | 0.434737E+10 | 0.200320E+10 | 0.234418E+10 | 0.00 | 0.00 |
June | 0.587383E+10 | 0.102325E+10 | 0.424896E+10 | 0.206591E+10 | 0.218305E+10 | 0.00 | 0.00 |
July | 0.626327E+10 | 0.724955E+09 | 0.420092E+10 | 0.184206E+10 | 0.235886E+10 | 0.00 | 0.00 |
August | 0.657033E+10 | 0.842138E+09 | 0.459928E+10 | 0.206370E+10 | 0.253558E+10 | 0.00 | 0.00 |
September | 0.617084E+10 | 0.137287E+10 | 0.463532E+10 | 0.255997E+10 | 0.207534E+10 | 0.00 | 0.00 |
October | 0.610372E+10 | 0.237737E+10 | 0.520896E+10 | 0.357140E+10 | 0.163756E+10 | 0.00 | 0.00 |
November | 0.505097E+10 | 0.319918E+10 | 0.486298E+10 | 0.340709E+10 | 0.145589E+10 | 0.00 | 0.00 |
December | 0.487032E+10 | 0.407399E+10 | 0.490079E+10 | 0.371419E+10 | 0.118660E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.660191E+11 | 0.273812E+11 | 0.559635E+11 | 0.327893E+11 | 0.231742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.464578E+10 | 0.724955E+09 | 0.420092E+10 | 0.184206E+10 | 0.118660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657033E+10 | 0.407399E+10 | 0.520896E+10 | 0.371419E+10 | 0.253558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639615E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -170981275.9 | 81.22 | 0.00 | 0.00 |
February | 0.578782E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -153544255.0 | 81.22 | 0.00 | 0.00 |
March | 0.645975E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165890943.2 | 81.22 | 0.00 | 0.00 |
April | 0.619893E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155470992.6 | 81.22 | 0.00 | 0.00 |
May | 0.641733E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157151209.3 | 81.21 | 0.00 | 0.00 |
June | 0.623656E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149978894.9 | 81.21 | 0.00 | 0.00 |
July | 0.637135E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154242710.5 | 81.21 | 0.00 | 0.00 |
August | 0.644959E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154352155.8 | 81.21 | 0.00 | 0.00 |
September | 0.619480E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149981873.8 | 81.21 | 0.00 | 0.00 |
October | 0.638399E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160157296.9 | 81.21 | 0.00 | 0.00 |
November | 0.618707E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162442269.8 | 81.22 | 0.00 | 0.00 |
December | 0.638905E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171979263.4 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754724E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190617E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578782E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -171979263.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645975E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149978894.9 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.242248E+11 | -0.232334E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -991432479.3 | 58.99 | 0.00 | 0.00 |
February | 0.220770E+11 | -0.211897E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -887332489.1 | 58.99 | 0.00 | 0.00 |
March | 0.240306E+11 | -0.230857E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -944859951.3 | 58.99 | 0.00 | 0.00 |
April | 0.218566E+11 | -0.209887E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -867965099.8 | 58.99 | 0.00 | 0.00 |
May | 0.210735E+11 | -0.202087E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864767284.6 | 58.98 | 0.00 | 0.00 |
June | 0.190614E+11 | -0.182437E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -817781041.6 | 58.99 | 0.00 | 0.00 |
July | 0.185310E+11 | -0.176928E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838161351.8 | 58.98 | 0.00 | 0.00 |
August | 0.185518E+11 | -0.177127E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839160004.9 | 58.98 | 0.00 | 0.00 |
September | 0.184103E+11 | -0.175925E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -817768929.4 | 58.99 | 0.00 | 0.00 |
October | 0.202387E+11 | -0.193463E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -892371857.6 | 58.99 | 0.00 | 0.00 |
November | 0.211373E+11 | -0.202055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -931783676.0 | 58.99 | 0.00 | 0.00 |
December | 0.232663E+11 | -0.222657E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100059E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.252459E+12 | -0.241765E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.106940E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184103E+11 | -0.232334E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.100059E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.242248E+11 | -0.175925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -817768929.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177945E+11 | 130708.83 | 20-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125302E+11 | 130708.83 | 04-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455725E+10 | 32970.93 | 04-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.851530E+09 | 29742.42 | 28-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112424E+09 | 30645.69 | 16-MAY-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33427453.66 | 47038.14 | 14-JUN-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9642176.12 | 14446.82 | 28-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8086859.31 | 18382.01 | 18-AUG-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20396581.80 | 27380.65 | 14-SEP-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137922E+10 | 26782.08 | 07-OCT-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458665E+10 | 27867.92 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173653E+11 | 130708.83 | 15-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8086859.31 | 14446.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177945E+11 | 130708.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190106E+11 | 40850.76 | 22-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136632E+11 | 38954.68 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.573695E+10 | 23719.37 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125735E+10 | 21165.01 | 06-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161046E+09 | 10711.75 | 06-MAY-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184319E+10 | 24924.79 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.667700E+10 | 29182.75 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191008E+11 | 44365.94 | 15-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191008E+11 | 44365.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28468.69 | 28468.69 | 23.64 | 25-JAN-15:30 | 23.64 | 0.00 |
February | 0.00 | 0.00 | 0.475592E+09 | 0.475592E+09 | 17619.65 | 14-FEB-15:00 | 17619.65 | 0.00 |
March | 0.00 | 0.00 | 0.149208E+10 | 0.149201E+10 | 25858.90 | 08-MAR-14:00 | 25858.90 | 0.00 |
April | 0.00 | 0.00 | 0.128002E+11 | 0.127958E+11 | 86130.01 | 27-APR-03:01 | 86130.01 | 0.00 |
May | 0.00 | 0.00 | 0.274499E+11 | 0.268770E+11 | 86130.01 | 19-MAY-03:01 | 82411.37 | 0.00 |
June | 0.00 | 0.00 | 0.547462E+11 | 0.524749E+11 | 86130.01 | 06-JUN-03:01 | 54576.03 | 0.00 |
July | 0.00 | 0.00 | 0.776921E+11 | 0.659092E+11 | 86904.03 | 16-JUL-03:01 | 44234.99 | 0.00 |
August | 0.00 | 0.00 | 0.693438E+11 | 0.590298E+11 | 86764.73 | 14-AUG-03:01 | 48660.45 | 0.00 |
September | 0.00 | 0.00 | 0.440517E+11 | 0.390985E+11 | 86130.01 | 02-SEP-03:42 | 59768.06 | 0.00 |
October | 0.00 | 0.00 | 0.161757E+11 | 0.150234E+11 | 86130.01 | 01-OCT-03:01 | 67648.18 | 0.00 |
November | 0.00 | 0.00 | 72712276.93 | 68777173.09 | 86130.01 | 01-NOV-03:01 | 69934.70 | 0.00 |
December | 0.00 | 0.00 | 178.20 | 178.20 | 0.59 | 29-DEC-14:25 | 0.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.304300E+12 | 0.273245E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 178.20 | 178.20 | 0.59 | 0.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.776921E+11 | 0.659092E+11 | 86904.03 | 86130.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7263137.16 | 5791165.27 | 4723.56 | 10-JAN-04:08 | 3949.98 | 0.00 |
February | 0.00 | 0.00 | 0.124265E+09 | 0.121855E+09 | 6504.92 | 14-FEB-15:55 | 6504.92 | 0.00 |
March | 0.00 | 0.00 | 0.325714E+09 | 0.323127E+09 | 8129.22 | 08-MAR-16:07 | 8129.22 | 0.00 |
April | 0.00 | 0.00 | 0.532968E+10 | 0.530992E+10 | 43706.76 | 13-APR-03:01 | 43706.76 | 0.00 |
May | 0.00 | 0.00 | 0.138601E+11 | 0.133943E+11 | 43706.76 | 21-MAY-03:01 | 27271.21 | 0.00 |
June | 0.00 | 0.00 | 0.320137E+11 | 0.305040E+11 | 43706.76 | 22-JUN-00:42 | 36509.44 | 0.00 |
July | 0.00 | 0.00 | 0.462918E+11 | 0.392692E+11 | 44327.53 | 01-JUL-03:01 | 17999.44 | 0.00 |
August | 0.00 | 0.00 | 0.396487E+11 | 0.334189E+11 | 43706.76 | 10-AUG-03:21 | 31196.23 | 0.00 |
September | 0.00 | 0.00 | 0.232689E+11 | 0.200199E+11 | 43706.76 | 30-SEP-03:21 | 29938.77 | 0.00 |
October | 0.00 | 0.00 | 0.738070E+10 | 0.656980E+10 | 43706.76 | 09-OCT-03:01 | 31366.47 | 0.00 |
November | 0.00 | 0.00 | 47227058.40 | 36041600.03 | 43706.76 | 01-NOV-04:01 | 30270.95 | 0.00 |
December | 0.00 | 0.00 | 7714687.77 | 6443022.61 | 3984.59 | 26-DEC-04:10 | 2834.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168306E+12 | 0.148979E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7263137.16 | 5791165.27 | 3984.59 | 2834.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.462918E+11 | 0.392692E+11 | 44327.53 | 43706.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 9133.77 | 17540.39 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9218.28 | 17569.82 | 01-FEB-07:32 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 9078.89 | 17402.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 8558.01 | 16635.91 | 03-APR-06:57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8006.59 | 15678.61 | 01-MAY-18:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 7501.04 | 14527.03 | 01-JUN-06:33 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7069.37 | 13639.93 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7076.77 | 13422.38 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 7250.39 | 14038.59 | 29-SEP-06:57 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7685.51 | 15093.72 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8256.63 | 16192.88 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8773.41 | 17060.12 | 29-DEC-19:57 |
Annual Sum or Average | 0.00 | 8127.80 | ||||
Minimum of Months | 0.00 | 0.00 | 7069.37 | 13422.38 | ||
Maximum of Months | 0.00 | 0.00 | 9218.28 | 17569.82 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.499567E+10 | 0.66 | 2203.40 | 01-JAN-00:03 | 0.78 |
February | 0.453923E+10 | 0.66 | 2203.40 | 01-FEB-00:01 | 0.78 |
March | 0.509647E+10 | 0.67 | 2203.40 | 01-MAR-00:03 | 0.78 |
April | 0.506078E+10 | 0.69 | 2203.40 | 01-APR-03:02 | 0.77 |
May | 0.545290E+10 | 0.71 | 2203.40 | 01-MAY-01:35 | 0.77 |
June | 0.538821E+10 | 0.73 | 2203.40 | 01-JUN-00:30 | 0.77 |
July | 0.562334E+10 | 0.73 | 2203.40 | 01-JUL-00:10 | 0.77 |
August | 0.562354E+10 | 0.73 | 2203.40 | 01-AUG-00:09 | 0.76 |
September | 0.543577E+10 | 0.73 | 2203.40 | 01-SEP-00:10 | 0.77 |
October | 0.534019E+10 | 0.70 | 2203.40 | 01-OCT-00:12 | 0.77 |
November | 0.494808E+10 | 0.67 | 2203.40 | 01-NOV-01:23 | 0.77 |
December | 0.500492E+10 | 0.66 | 2203.40 | 01-DEC-00:05 | 0.78 |
Annual Sum or Average | 0.625091E+11 | 0.69 | |||
Minimum of Months | 0.453923E+10 | 0.66 | 2203.40 | 0.76 | |
Maximum of Months | 0.562354E+10 | 0.73 | 2203.40 | 0.78 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205115E+11 | 1.57 | 9175.74 | 03-JAN-08:52 | 1.87 |
February | 0.185418E+11 | 1.58 | 9175.74 | 05-FEB-13:10 | 1.88 |
March | 0.204818E+11 | 1.56 | 9175.74 | 04-MAR-22:45 | 1.88 |
April | 0.198376E+11 | 1.58 | 9175.74 | 01-APR-04:20 | 1.88 |
May | 0.205303E+11 | 1.59 | 9175.74 | 06-MAY-04:07 | 1.88 |
June | 0.199603E+11 | 1.59 | 9175.74 | 02-JUN-10:00 | 1.86 |
July | 0.207223E+11 | 1.58 | 9175.74 | 01-JUL-04:06 | 1.84 |
August | 0.207271E+11 | 1.58 | 9175.74 | 29-AUG-22:10 | 1.85 |
September | 0.199845E+11 | 1.59 | 9175.74 | 13-SEP-07:26 | 1.86 |
October | 0.205543E+11 | 1.59 | 9175.74 | 25-OCT-17:00 | 1.87 |
November | 0.198231E+11 | 1.57 | 9175.74 | 06-NOV-07:53 | 1.87 |
December | 0.205270E+11 | 1.58 | 9175.74 | 04-DEC-22:50 | 1.87 |
Annual Sum or Average | 0.242202E+12 | 1.58 | |||
Minimum of Months | 0.185418E+11 | 1.56 | 9175.74 | 1.84 | |
Maximum of Months | 0.207271E+11 | 1.59 | 9175.74 | 1.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.480361E+10 | 0.92 | 2150.67 | 01-JAN-08:48 | 1.09 |
February | 0.434072E+10 | 0.93 | 2150.67 | 01-FEB-00:03 | 1.09 |
March | 0.481463E+10 | 0.94 | 2150.67 | 01-MAR-05:20 | 1.09 |
April | 0.468534E+10 | 0.96 | 2150.67 | 01-APR-04:18 | 1.10 |
May | 0.488041E+10 | 1.00 | 2150.67 | 02-MAY-04:06 | 1.09 |
June | 0.477956E+10 | 1.01 | 2150.67 | 01-JUN-08:48 | 1.08 |
July | 0.498527E+10 | 1.01 | 2150.67 | 01-JUL-04:13 | 1.07 |
August | 0.497447E+10 | 1.01 | 2150.67 | 01-AUG-07:45 | 1.08 |
September | 0.477756E+10 | 1.02 | 2150.67 | 01-SEP-04:30 | 1.08 |
October | 0.486905E+10 | 0.98 | 2150.67 | 01-OCT-09:18 | 1.09 |
November | 0.466159E+10 | 0.94 | 2150.67 | 01-NOV-22:20 | 1.09 |
December | 0.480424E+10 | 0.93 | 2150.67 | 01-DEC-08:23 | 1.09 |
Annual Sum or Average | 0.573764E+11 | 0.97 | |||
Minimum of Months | 0.434072E+10 | 0.92 | 2150.67 | 1.07 | |
Maximum of Months | 0.498527E+10 | 1.02 | 2150.67 | 1.10 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:03 | 5.36 | 5.36 | 48.54 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 48.21 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 48.61 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 51.87 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.26 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.41 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.20 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 53.26 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 53.50 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.17 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.57 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 49.60 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.21 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 53.50 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48.54 | 59.83 | 9133.77 | 17540.39 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 48.21 | 58.78 | 9218.28 | 17569.82 | 01-FEB-07:32 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.61 | 58.68 | 9078.89 | 17402.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.67 | 49.67 | 8558.01 | 16635.91 | 03-APR-06:57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 50.69 | 50.69 | 8006.59 | 15678.61 | 01-MAY-18:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.02 | 51.02 | 7501.04 | 14527.03 | 01-JUN-06:33 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.78 | 51.78 | 7069.37 | 13639.93 | 03-JUL-06:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.94 | 51.94 | 7076.77 | 13422.38 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.09 | 52.09 | 7250.39 | 14038.59 | 29-SEP-06:57 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 49.43 | 49.43 | 7685.51 | 15093.72 | 31-OCT-18:50 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.40 | 50.40 | 8256.63 | 16192.88 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.60 | 58.94 | 8773.41 | 17060.12 | 29-DEC-19:57 |
Annual Sum or Average | 0.00 | 8127.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.21 | 49.43 | 7069.37 | 13422.38 | ||
Maximum of Months | 0.00 | 0.00 | 52.09 | 59.83 | 9218.28 | 17569.82 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.205116E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.187081E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.210077E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.241767E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.296659E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.381837E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.461450E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.432191E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.343775E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259433E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.198487E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.205270E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342315E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.187081E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.461450E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.480615E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.438394E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.492788E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.645920E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.936615E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.150032E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.194457E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.173443E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.121519E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.726026E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.467679E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.480696E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110632E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438394E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194457E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205115E+11 | 28468.69 | 0.177945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185418E+11 | 0.475592E+09 | 0.125302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204818E+11 | 0.149208E+10 | 0.455725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198376E+11 | 0.128002E+11 | 0.851530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205303E+11 | 0.274499E+11 | 0.112424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199603E+11 | 0.547462E+11 | 33427453.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207223E+11 | 0.776921E+11 | 9642176.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207271E+11 | 0.693438E+11 | 8086859.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199845E+11 | 0.440517E+11 | 20396581.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205543E+11 | 0.161757E+11 | 0.137922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198231E+11 | 72712276.93 | 0.458665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205270E+11 | 178.20 | 0.173653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242202E+12 | 0.304300E+12 | 0.592487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185418E+11 | 178.20 | 8086859.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207271E+11 | 0.776921E+11 | 0.177945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.480361E+10 | 7263137.16 | 0.190106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.434072E+10 | 0.124265E+09 | 0.136632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481463E+10 | 0.325714E+09 | 0.573695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468534E+10 | 0.532968E+10 | 0.125735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.488041E+10 | 0.138601E+11 | 0.161046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.477956E+10 | 0.320137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498527E+10 | 0.462918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.497447E+10 | 0.396487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477756E+10 | 0.232689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486905E+10 | 0.738070E+10 | 0.184319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466159E+10 | 47227058.40 | 0.667700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480424E+10 | 7714687.77 | 0.191008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573764E+11 | 0.168306E+12 | 0.674501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.434072E+10 | 7263137.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.498527E+10 | 0.462918E+11 | 0.191008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.205115E+11 | 0.00 | 0.00 | 0.00 | 10401.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185418E+11 | 0.00 | 0.00 | 0.00 | 0.166264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204818E+11 | 0.00 | 0.00 | 0.00 | 0.525960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198376E+11 | 0.00 | 0.00 | 0.00 | 0.433915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205303E+11 | 0.00 | 0.00 | 0.00 | 0.913560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199603E+11 | 0.00 | 0.00 | 0.00 | 0.182234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207223E+11 | 0.00 | 0.00 | 0.00 | 0.254228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207271E+11 | 0.00 | 0.00 | 0.00 | 0.224920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199845E+11 | 0.00 | 0.00 | 0.00 | 0.143930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205543E+11 | 0.00 | 0.00 | 0.00 | 0.538896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198231E+11 | 0.00 | 0.00 | 0.00 | 25560884.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205270E+11 | 0.00 | 0.00 | 0.00 | 65.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242202E+12 | 0.00 | 0.00 | 0.00 | 0.100113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185418E+11 | 0.00 | 0.00 | 0.00 | 65.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207271E+11 | 0.00 | 0.00 | 0.00 | 0.254228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.480361E+10 | 0.00 | 0.00 | 0.00 | 2546739.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.434072E+10 | 0.00 | 0.00 | 0.00 | 43219078.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481463E+10 | 0.00 | 0.00 | 0.00 | 0.113248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468534E+10 | 0.00 | 0.00 | 0.00 | 0.177385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.488041E+10 | 0.00 | 0.00 | 0.00 | 0.448574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.477956E+10 | 0.00 | 0.00 | 0.00 | 0.102236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498527E+10 | 0.00 | 0.00 | 0.00 | 0.144604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.497447E+10 | 0.00 | 0.00 | 0.00 | 0.123698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477756E+10 | 0.00 | 0.00 | 0.00 | 0.737432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486905E+10 | 0.00 | 0.00 | 0.00 | 0.239121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466159E+10 | 0.00 | 0.00 | 0.00 | 15201852.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480424E+10 | 0.00 | 0.00 | 0.00 | 2723619.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573764E+11 | 0.00 | 0.00 | 0.00 | 0.532559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.434072E+10 | 0.00 | 0.00 | 0.00 | 2546739.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.498527E+10 | 0.00 | 0.00 | 0.00 | 0.144604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.519162E+11 | 0.00 | 0.00 | 10784733.32 | 0.00 | 0.451240E+10 | 0.914789E+10 | 0.00 | 3.66 |
February | 0.416234E+11 | 0.00 | 0.00 | 18909872.76 | 0.00 | 0.331025E+10 | 0.116548E+11 | 0.00 | 3.88 |
March | 0.285187E+11 | 0.00 | 0.00 | 52441144.95 | 0.00 | 0.380091E+09 | 0.277672E+11 | 0.00 | 4.69 |
April | 0.134314E+11 | 0.00 | 0.00 | 0.103028E+09 | 0.00 | 2168975.53 | 0.329705E+11 | 0.00 | 5.82 |
May | 0.556543E+10 | 70573876.38 | 0.00 | 0.140193E+09 | 0.00 | 3505207.20 | 0.314977E+11 | 0.00 | 6.05 |
June | 0.153147E+10 | 0.316634E+10 | 0.00 | 0.113139E+09 | 1391290.03 | 3193017.27 | 0.173145E+11 | 0.00 | 5.46 |
July | 0.698210E+09 | 0.787369E+10 | 306346.68 | 50139503.12 | 15756346.99 | 343528.67 | 0.688062E+10 | 29273.76 | 5.40 |
August | 0.847170E+09 | 0.474485E+10 | 364961.78 | 83769075.57 | 6850360.80 | 71209.06 | 0.118134E+11 | 26445.97 | 5.79 |
September | 0.128119E+10 | 0.794766E+09 | 73398.61 | 0.154691E+09 | 0.00 | 2818810.88 | 0.257461E+11 | 22338.89 | 6.44 |
October | 0.141991E+11 | 43870898.76 | 0.00 | 0.115152E+09 | 0.00 | 4042755.44 | 0.352381E+11 | 0.00 | 5.91 |
November | 0.325932E+11 | 0.00 | 0.00 | 33520869.63 | 0.00 | 16562329.58 | 0.247228E+11 | 0.00 | 4.01 |
December | 0.575400E+11 | 0.00 | 0.00 | 3463891.71 | 0.00 | 0.386816E+10 | 0.456724E+10 | 0.00 | 3.55 |
Annual Sum or Average | 0.249745E+12 | 0.166941E+11 | 744707.07 | 0.879232E+09 | 23997997.82 | 0.121036E+11 | 0.239321E+12 | 78058.62 | 5.06 |
Minimum of Months | 0.698210E+09 | 0.00 | 0.00 | 3463891.71 | 0.00 | 71209.06 | 0.456724E+10 | 0.00 | 3.55 |
Maximum of Months | 0.575400E+11 | 0.787369E+10 | 364961.78 | 0.154691E+09 | 15756346.99 | 0.451240E+10 | 0.352381E+11 | 29273.76 | 6.44 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.667555E+11 | 0.00 | 0.00 | 1852644.15 | 0.00 | 16798896.52 | 0.405195E+10 | 0.00 | 10.56 |
February | 0.537204E+11 | 0.00 | 0.00 | 7607705.50 | 0.00 | 15786014.57 | 0.641440E+10 | 0.00 | 10.68 |
March | 0.386041E+11 | 0.00 | 0.00 | 29745971.86 | 0.00 | 0.00 | 0.196053E+11 | 0.00 | 10.99 |
April | 0.202253E+11 | 0.00 | 0.00 | 73141554.72 | 0.00 | 0.00 | 0.286716E+11 | 0.00 | 12.01 |
May | 0.762915E+10 | 0.00 | 0.00 | 0.119993E+09 | 0.00 | 0.00 | 0.339509E+11 | 0.00 | 12.51 |
June | 0.138287E+10 | 0.797574E+09 | 0.00 | 0.151037E+09 | 0.00 | 0.00 | 0.232061E+11 | 0.00 | 12.49 |
July | 5207147.66 | 0.180262E+10 | 0.00 | 0.149591E+09 | 0.00 | 0.00 | 0.130390E+11 | 0.00 | 12.79 |
August | 13319145.05 | 0.561425E+09 | 0.00 | 0.169265E+09 | 0.00 | 0.00 | 0.185499E+11 | 0.00 | 12.95 |
September | 0.633208E+09 | 17798454.08 | 0.00 | 0.160105E+09 | 0.00 | 0.00 | 0.311885E+11 | 0.00 | 12.97 |
October | 0.186726E+11 | 0.00 | 0.00 | 87961493.03 | 0.00 | 0.00 | 0.316550E+11 | 0.00 | 12.01 |
November | 0.440914E+11 | 0.00 | 0.00 | 11827423.94 | 0.00 | 0.00 | 0.146244E+11 | 0.00 | 10.66 |
December | 0.697655E+11 | 0.00 | 0.00 | 768991.49 | 0.00 | 20668767.26 | 0.148472E+10 | 0.00 | 10.55 |
Annual Sum or Average | 0.321499E+12 | 0.317942E+10 | 0.00 | 0.962895E+09 | 0.00 | 53253678.35 | 0.226442E+12 | 0.00 | 11.77 |
Minimum of Months | 5207147.66 | 0.00 | 0.00 | 768991.49 | 0.00 | 0.00 | 0.148472E+10 | 0.00 | 10.55 |
Maximum of Months | 0.697655E+11 | 0.180262E+10 | 0.00 | 0.169265E+09 | 0.00 | 20668767.26 | 0.339509E+11 | 0.00 | 12.97 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.553254E+11 | 0.170319E+11 | 0.207391E+12 | 0.130240E+10 | 0.287460E+11 |
February | 0.727084E+11 | 0.152052E+11 | 0.176856E+12 | 0.262707E+10 | 0.256732E+11 |
March | 0.102746E+12 | 0.144313E+11 | 0.168006E+12 | 0.990782E+10 | 0.279676E+11 |
April | 0.136085E+12 | 0.114452E+11 | 0.132454E+12 | 0.169397E+11 | 0.500953E+11 |
May | 0.148069E+12 | 0.951034E+10 | 0.111683E+12 | 0.176521E+11 | 0.828985E+11 |
June | 0.139580E+12 | 0.578996E+10 | 0.620162E+11 | 0.107633E+11 | 0.145561E+12 |
July | 0.140789E+12 | 0.341694E+10 | 0.250103E+11 | 0.579350E+10 | 0.196158E+12 |
August | 0.134310E+12 | 0.475084E+10 | 0.431793E+11 | 0.899620E+10 | 0.175472E+12 |
September | 0.104775E+12 | 0.619786E+10 | 0.827974E+11 | 0.167050E+11 | 0.117871E+12 |
October | 0.803965E+11 | 0.103405E+11 | 0.139705E+12 | 0.180581E+11 | 0.571743E+11 |
November | 0.612321E+11 | 0.143716E+11 | 0.175536E+12 | 0.492041E+10 | 0.219728E+11 |
December | 0.506096E+11 | 0.170302E+11 | 0.210132E+12 | 0.132678E+09 | 0.269868E+11 |
Annual Sum or Average | 0.122663E+13 | 0.129522E+12 | 0.153477E+13 | 0.113798E+12 | 0.956576E+12 |
Minimum of Months | 0.506096E+11 | 0.341694E+10 | 0.250103E+11 | 0.132678E+09 | 0.219728E+11 |
Maximum of Months | 0.148069E+12 | 0.170319E+11 | 0.210132E+12 | 0.180581E+11 | 0.196158E+12 |