Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:27:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2367.09 | 4630.89 | 4630.89 |
Net Site Energy | 2367.09 | 4630.89 | 4630.89 |
Total Source Energy | 5782.38 | 11312.43 | 11312.43 |
Net Source Energy | 5782.38 | 11312.43 | 11312.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 66.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 369.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 372.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.39 | 286.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 66.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1544.15 | 822.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 66.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 369.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 372.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.39 | 286.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 66.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 369.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 372.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.39 | 286.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 66.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1600.06 | 690.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1031.05 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3020.90 | 1609.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1600.06 | 690.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1031.05 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3020.90 | 1609.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1544.145 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1544.145 | 100.00 |
Total On-Site and Utility Electric Sources | 1544.145 | 100.00 |
Total Electricity End Uses | 1544.145 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5913.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 14.4672 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.5854 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 14.4672 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.5854 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 13.6812 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-17:10 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 24-FEB-19:10 |
Heating | 0.00 | 65561.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 51756.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13788.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4165.54 | 17506.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2061.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 98760.37 | 96645.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 65561.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 51756.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13788.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4165.54 | 17506.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 513.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1003.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 72.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1171.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1178.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.75 | 310.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 209.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4890.31 | 892.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 141.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2291.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2306.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.07 | 607.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 410.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9567.20 | 1745.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 141.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2291.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2306.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.07 | 607.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 410.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9567.20 | 1745.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 5.06 |
KITCHEN DIRECT AIR | 1.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 5.06 | 5.06 | 5.06 | 5.06 | 5.06 | 5.06 | 1.00 | 1.00 | 5.06 |
PSZ-AC_2:2 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.000000 | 1.90 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 5.06 | 2.64 |
PSZ-AC_2:2_OA_CONTROLLER | 1.90 | 0.187543 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 5.06 | 9502.15 |
PSZ-AC_2:2_ADDAQ FAN | 1.90 | 2082.83 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 5.06 | 5.06 | 5.06 | 5.06 | 125678.43 | 165172.07 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.90 | 41997.07 | 83514.83 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 5.06 | 2.53 | 5.06 | 125678.43 | 62839.21 | 125678.43 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.90 | 0.951495 | 1.90 | 41997.07 | 20177.58 | 41997.07 | 0.739770 | 0.739770 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 165172.07 |
PSZ-AC_2:2 HEATING COIL | 83514.83 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 14.467 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 79.395 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.585 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.665 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 5378.143 | 14.467 | 19.198 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5378.143 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1615.060 | 11.585 | 214.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1615.060 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.2003 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.500 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.892 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4325 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.20636098E-16 | 0.18100998E-15 | 0.17288268E-13 | -0.34766289E-16 |
24 | 3 | -0.71341822E-08 | 0.14427768E-06 | -0.58767875E-04 | 0.16137435E-12 |
25 | 2 | 0.62866063E-04 | 0.30866150E-02 | 1.1745480 | -0.77421164E-04 |
26 | 1 | -0.70719755E-01 | 0.78899699E-01 | -17.315014 | 0.34200793 |
27 | 0 | 0.20250090 | 0.49857543E-01 | 16.272369 | |
28 | 4 | 0.17288268E-13 | 0.18100998E-15 | 0.20636098E-16 | -0.34766289E-16 |
29 | 3 | -0.58767875E-04 | 0.14427768E-06 | -0.71341822E-08 | 0.16137435E-12 |
30 | 2 | 1.1745480 | 0.30866150E-02 | 0.62866063E-04 | -0.77421164E-04 |
31 | 1 | -17.315014 | 0.78899699E-01 | -0.70719755E-01 | 0.34200793 |
32 | 0 | 16.272369 | 0.49857543E-01 | 0.20250090 | |
33 | 6 | 0.19952834E-07 | 0.37147198E-09 | 0.46430291E-08 | -0.89111870E-13 |
34 | 5 | -0.14466088E-03 | 0.34030017E-05 | -0.74831287E-04 | 0.46077240E-08 |
35 | 4 | 0.23721950 | 0.17579200E-02 | 0.80016642E-01 | -0.26003020E-04 |
36 | 3 | -6.1742659 | 0.57392279E-01 | -2.0151465 | 0.23669466E-01 |
37 | 2 | 37.264580 | 0.21353215 | 13.926457 | -0.29319906 |
38 | 1 | -77.776780 | 0.10018737 | -27.938560 | 1.0196200 |
39 | 0 | 46.824358 | 0.20941775E-02 | 16.322275 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
2 | NONRESWINDOW_U_0.7141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
3 | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
4 | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 52667.59770 | 63201.11724 | 4.21756 | 5.06107 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
2 | DINING | Heating | 6982.15914 | 8378.59097 | 0.32965 | 2.64387 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 0.50000 | 4.31558E-003 | 371.74807 | 280.14173 | 2.64387 | 0.00000 |
3 | KITCHEN | Cooling | 23334.97992 | 28001.97591 | 1.58583 | 1.90299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 0.18754 | 00:10:00 | 0.50000 | 4.31558E-003 | 139.40524 | 7.52790 | 0.18754 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 110976.62 | 5.06107 | 5.06107 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 114720.07 | 2.64387 | 2.64387 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 30321.01 | 1.90299 | 1.90299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 8137.69 | 0.18754 | 0.18754 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.06107 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.90299 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06107 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.06107 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.06107 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 5.06107 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06107 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 5.06107 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.90299 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.90299 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.90299 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90299 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.90299 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.90299 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 5.06107 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.90299 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06107 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.64387 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.06107 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9502.14864 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.06107 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.06107 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.06107 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.06107 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.06107 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.53054 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.06107 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 125678.43000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 62839.21033 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 125678.43000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 125678.43000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 165172.07330 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 165172.07330 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.90299 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.18754 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.90299 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2082.83391 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.90299 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90299 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90299 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90299 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.90299 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95150 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.90299 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41997.07000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20177.58274 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41997.07000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73977 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73977 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41997.07000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 83514.83408 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 83514.83408 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 122081.2 | 9.93 | 9.81 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40631.2 | 9.98 | 9.86 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | N/A | 4.059 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | N/A | 4.059 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | N/A | 4.059 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.200 | 0.193 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.200 | 0.191 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.9930081082E-002 | 0.4010112845 | Pass | Pass | 7.9200615492E-002 | 0.2284783720 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 8.6240294629E-002 | 0.4341153669 | Pass | Pass | 8.5967896013E-002 | 0.3779905259 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4435683538 | 0.4039305827 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1106.25 | 50.03 | 1257.00 | 263.69 | 1842.83 | 4519.81 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.190 | 0.200 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 4.059 | 0.254 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 4.059 | 0.254 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 14.4672 | 371.75 | 5378.14 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 97.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.5854 | 139.41 | 1615.06 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.38 |
Interior Lighting Total | 13.6812 | 511.15 | 6993.20 | 127.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.79 | 83.79 | 72.01 | |
Exterior Lighting Total | 4578.48 | 72.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 125678.43 | 88110.63 | 37567.80 | 0.70 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41997.07 | 31068.17 | 10928.90 | 0.74 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 122081.2 | 9.93 | 9.81 | ||||
PSZ-AC_2:2 COOLING COIL | 40631.2 | 9.98 | 9.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 165172.07 | 0.79 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 83514.83 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 2.64 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 5.06 | 9502.15 | 1877.50 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.90 | 2082.83 | 1094.51 | 1.00 | 1.29 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 52667.60 | 63201.12 | 170.01 | 4.218 | 5.061 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00932 | 40.53 | 0.00563 | 2.644 | 0.00 |
KITCHEN | 23334.98 | 28001.98 | 200.87 | 1.586 | 1.903 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01008 | 39.60 | 0.00563 | 0.188 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 6982.16 | 8378.59 | 22.54 | 0.330 | 2.644 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 2.644 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 0.188 | 00:10:00 | 19.00 | 22.46 | 0.00391 | 0.50 | 0.00432 | 0.188 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 5.06 | 5.06 | 2.64 | 2.64 | 5.0611 | 5.0611 | 5.0611 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.90 | 1.90 | 0.19 | 0.19 | 1.9030 | 1.9030 | 1.9030 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 125678.430 | 88110.634 | 5.061070 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 125678.43 | 125678.43 | 5.061070 | 32.78 | 17.42 | 0.00739051 | 11.11 | 9.42 | 0.00739051 | 40.80 | 0.00563111 | 18.58 | 52.2393 | 23.99 | 0.00931877 | 45.5005 | 52612.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 165172.073 | 165172.073 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | 165172.07 | 165172.07 | 5.061070 | 10.29 | 7.52 | 0.00597014 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 52.2393 | 21.00 | 0.00777985 | 45.6763 | 6976.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41997.070 | 31068.172 | 1.902990 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 41997.07 | 36004.46 | 1.902990 | 27.30 | 17.42 | 0.00964235 | 11.82 | 10.84 | 0.00850000 | 39.60 | 0.00562924 | 18.21 | 9.8552 | 25.99 | 0.01008109 | 43.6548 | 23334.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 83514.834 | 83514.834 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 83514.83 | 83514.83 | 1.902991 | 0.05 | -0.28 | 0.00395008 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.8552 | 22.46 | 0.00391013 | 21.1217 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 125678.430 | 88110.634 | 5.061070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5786 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.061070 | 5.53273269 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 125678.43 | 125678.43 | 1.0000 | 5.53273245 | 5.061070 | 32.78 | 17.42 | 0.00739051 | 51872.7 | 11.11 | 9.42 | 0.00739051 | 29803.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 125678.43 | 40.80 | 0.00563111 | 18.58 | 2.64386968 | 52.2393 | 23.99 | 0.00931877 | 23.99 | 0.00931877 | 45.5005 | 52612.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 165172.073 | 165172.073 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.061070 | 5.53273269 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 01:50:00 | Sensible | 165172.07 | 165172.07 | 1.0000 | 5.53273269 | 5.061070 | 10.29 | 7.52 | 0.00597014 | 25385.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 165172.07 | 0.50 | 0.00431558 | 0.50 | 2.64386968 | 52.2393 | 21.00 | 0.00777985 | 21.00 | 0.00777985 | 45.6763 | 6976.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41997.070 | 31068.172 | 1.902990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7647 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.902991 | 2.08033856 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 41997.07 | 36004.46 | 1.0000 | 2.08033766 | 1.902990 | 27.30 | 17.42 | 0.00964235 | 52041.1 | 11.82 | 10.84 | 0.00850000 | 33323.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41997.07 | 39.60 | 0.00562924 | 18.21 | 0.18754328 | 9.8552 | 25.96 | 0.01008109 | 25.99 | 0.01008109 | 43.6548 | 23334.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 83514.834 | 83514.834 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.902991 | 2.08033856 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 83514.83 | 83514.83 | 1.0000 | 2.08033856 | 1.902991 | 0.05 | -0.28 | 0.00395008 | 9928.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83514.83 | 0.50 | 0.00431558 | 0.50 | 0.18754328 | 9.8552 | 0.00 | 0.00391013 | 22.46 | 0.00391013 | 21.1217 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 2.64 | 5.06 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.19 | 1.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3900.33 | 2252.00 | 387.67 |
KITCHEN | 7187.00 | 5827.33 | 5827.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7187.00 | 6935.17 | 5913.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.17 | 25.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 268.33 | 0.00 | 0.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 293.33 | 0.00 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 9.122 | 0.912 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 7.967 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 8.252 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 1.608 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 2.6439 | 2.644 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1242 | 0.053 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 2.7680 | 2.697 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 74506326.62 | 0.00 | 74506326.62 | 7437117.95 | 81943444.57 | 83377074.30 | 1444.57 | 5698.14 | 1617.29 | 217.85 |
KITCHEN | 25390619.73 | 0.00 | 25390619.73 | 230040.68 | 25620660.40 | 5914364.89 | 1010.43 | 2905.53 | 4844.04 | 863.13 |
Total Facility | 99896946.35 | 0.00 | 99896946.35 | 7667158.62 | 0.11E+09 | 89291439.19 | 1451.02 | 5710.64 | 4859.36 | 915.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 2.8218 | 0.0000 | 2.8218 | 0.2821 | 3.1039 | 2.6439 | 0.00 | 5612.26 | 1574.74 |
KITCHEN | 0.9149 | 0.0000 | 0.9149 | 0.0055 | 0.9204 | 0.1875 | 0.00 | 2893.24 | 4293.76 |
Total Facility | 3.7367 | 0.0000 | 3.7367 | 0.2876 | 4.0243 | 2.8314 | 0.00 | 5621.14 | 4302.64 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 89040543.30 | 0.00 | 89040543.30 | 83377074.30 | 1444.54 | 0.02 | 7315.44 | 217.82 |
PSZ-AC_2:2 | 30343659.20 | 0.00 | 30343659.20 | 5914364.89 | 974.77 | 3.33 | 7781.89 | 863.13 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 3.3722 | 0.0000 | 3.3722 | 2.6439 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.0934 | 0.0000 | 1.0934 | 0.1875 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1386.44 | 329.34 | 5689.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 4676.22 | 3373.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 4.2355 | 3.6935 | 3.1602 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6794 | 0.2241 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
Electricity:Building | 604.81 | 4434.71 | 01-JAN-01:10 | 33358.73 | 02-JAN-11:10 |
Electricity:Zone:DINING | 223.13 | 1289.45 | 01-JAN-01:10 | 11839.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 587.95 | 4025.67 | 01-JAN-01:10 | 30993.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.68 | 3145.26 | 01-JAN-01:10 | 21518.76 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.31 | 1192.39 | 13-OCT-22:30 | 3441.39 | 09-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 125.28 | 1225.94 | 27-JUN-01:50 | 6478.17 | 09-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.54 | 0.00 | 01-JAN-11:10 | 1497.80 | 10-NOV-04:20 |
MedTempRefrigeration:Refrigeration:Electricity | 31.91 | 832.67 | 03-JUL-04:00 | 1076.23 | 08-JAN-14:30 |
ElectricityPurchased:Facility | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
ElectricityPurchased:Plant | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
Cogeneration:ElectricityPurchased | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
ElectricityNet:Plant | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
Cogeneration:ElectricityNet | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
General:Cogeneration:ElectricityNet | 1544.15 | 10335.68 | 28-JUN-02:40 | 98760.37 | 28-JUN-17:10 |
Electricity:HVAC | 742.04 | 0.00 | 01-JAN-01:10 | 65544.65 | 28-JUN-17:10 |
Fans:Electricity | 372.23 | 0.00 | 01-JAN-01:10 | 13788.39 | 01-JAN-00:20 |
General:Fans:Electricity | 372.23 | 0.00 | 01-JAN-01:10 | 13788.39 | 01-JAN-00:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 369.81 | 0.00 | 01-JAN-00:10 | 51756.26 | 28-JUN-17:10 |
General:Cooling:Electricity | 369.81 | 0.00 | 01-JAN-00:10 | 51756.26 | 28-JUN-17:10 |
ExteriorLights:Electricity | 72.01 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.01 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4736.99 | 27-JUN-06:20 |
Water Heater:WaterSystems:Electricity | 75.39 | 0.00 | 01-JAN-01:10 | 4736.99 | 27-JUN-06:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 23-FEB-15:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 822.95 | 2803.57 | 01-JAN-01:10 | 96645.05 | 06-DEC-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 66.66 | 0.00 | 01-JAN-00:20 | 67885.18 | 06-DEC-07:00 |
Heating:NaturalGas | 66.66 | 0.00 | 01-JAN-00:20 | 67885.18 | 06-DEC-07:00 |
General:Heating:NaturalGas | 66.66 | 0.00 | 01-JAN-00:20 | 67885.18 | 06-DEC-07:00 |
NaturalGas:Plant | 286.50 | 993.32 | 01-JAN-00:10 | 21754.00 | 20-JAN-19:20 |
WaterSystems:NaturalGas | 286.50 | 993.32 | 01-JAN-00:10 | 21754.00 | 20-JAN-19:20 |
Water Heater:WaterSystems:NaturalGas | 286.50 | 993.32 | 01-JAN-00:10 | 21754.00 | 20-JAN-19:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 16-MAR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 16-MAR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2385.25 | 3938.68 | 04-JUN-01:00 | 211129.44 | 28-JUN-17:20 |
EnergyTransfer:Building | 940.97 | 1969.34 | 04-JUN-01:00 | 74085.89 | 17-OCT-03:50 |
EnergyTransfer:Zone:KITCHEN | 475.04 | 1969.34 | 04-JUN-01:00 | 25827.74 | 12-JUL-11:00 |
Refrigeration:EnergyTransfer | 160.20 | 3640.20 | 12-OCT-22:10 | 7834.84 | 07-FEB-04:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.10 | 1820.10 | 12-OCT-22:10 | 3917.42 | 07-FEB-04:20 |
General:Refrigeration:EnergyTransfer | 80.10 | 1820.10 | 12-OCT-22:10 | 3917.42 | 07-FEB-04:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 80.10 | 1820.10 | 12-OCT-22:10 | 3917.42 | 07-FEB-04:20 |
EnergyTransfer:Plant | 275.55 | 1839.25 | 27-JUN-01:50 | 16858.84 | 23-JAN-19:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.58 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 64.52 | 1508.00 | 03-JUL-04:00 | 2238.70 | 08-JAN-14:30 |
EnergyTransfer:Zone:DINING | 465.93 | 0.00 | 01-JAN-01:10 | 60508.67 | 17-OCT-03:50 |
Heating:EnergyTransfer | 2.95 | 0.00 | 01-JAN-00:10 | 25604.28 | 17-OCT-03:50 |
Heating:EnergyTransfer:Zone:DINING | 2.95 | 0.00 | 01-JAN-00:10 | 25604.28 | 17-OCT-03:50 |
General:Heating:EnergyTransfer | 2.95 | 0.00 | 01-JAN-00:10 | 25604.28 | 17-OCT-03:50 |
General:Heating:EnergyTransfer:Zone:DINING | 2.95 | 0.00 | 01-JAN-00:10 | 25604.28 | 17-OCT-03:50 |
Cooling:EnergyTransfer | 857.92 | 0.00 | 01-JAN-01:10 | 62347.08 | 28-JUN-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 462.98 | 0.00 | 01-JAN-01:10 | 41893.30 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer | 857.92 | 0.00 | 01-JAN-01:10 | 62347.08 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 462.98 | 0.00 | 01-JAN-01:10 | 41893.30 | 28-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 394.95 | 0.00 | 01-JAN-01:10 | 21978.63 | 22-JUL-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 394.95 | 0.00 | 01-JAN-01:10 | 21978.63 | 22-JUL-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
EnergyTransfer:HVAC | 1168.74 | 0.00 | 01-JAN-00:20 | 140103.76 | 19-JUL-12:00 |
HeatingCoils:EnergyTransfer | 52.83 | 0.00 | 01-JAN-00:20 | 53799.00 | 06-DEC-07:00 |
CoolingCoils:EnergyTransfer | 1115.91 | 0.00 | 01-JAN-00:10 | 140103.76 | 19-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14210.91 | 26-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.949 | -462.973 | 0.000 | 0.000 | 212.851 | 97.852 | 93.957 | 54.257 | 0.000 | 28.895 | 21.903 | 0.000 | -20.834 | 0.000 | -28.857 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -394.937 | 0.000 | 0.000 | 4.763 | 29.385 | 297.857 | 0.000 | 0.000 | 0.409 | 64.499 | 0.000 | 0.000 | 0.000 | -1.977 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.810 | 35.686 | 0.000 | 0.000 | 0.000 | -46.497 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.949 | -857.910 | 0.000 | 0.000 | 217.615 | 127.237 | 391.814 | 54.257 | 0.000 | 40.114 | 122.089 | 0.000 | -20.834 | 0.000 | -77.331 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 18-OCT-03:01 | 0.00 | 0.00 | 0.00 | -141022.32 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 141516.65 | 0.00 | -2051.68 | 0.00 | -154.49 | 0.00 |
KITCHEN | 05-DEC-04:01 | 0.00 | 0.00 | 0.00 | -86294.32 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 82623.91 | 0.00 | -0.00 | 0.00 | -393.33 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-MAY-03:01 | 0.00 | 0.00 | 0.00 | -205727.85 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 674.94 | 201768.22 | 0.00 | -2069.62 | 0.00 | -421.27 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 25-MAY-03:46 | 0.00 | 0.00 | 78001.42 | 0.00 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1045.96 | 0.00 | -4.91 | -78662.40 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-MAY-03:46 | -7649.26 | 7649.26 | 78001.42 | -7649.26 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 809.73 | 0.00 | 0.00 | -1045.96 | 0.00 | -41.44 | -75850.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.0611 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 5.0611 | 0.5224 | 1.0000 | Not calculated | 2.6439 | 0.5224 | ||
PSZ-AC_2:2 | 1.9030 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.9030 | 0.0652 | 1.0000 | Not calculated | 0.1242 | 0.0652 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.0611 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 2.6439 | 5.0611 | 1.0000 | 1.0000 | Not calculated | 2.6439 | 0.5224 | ||
PSZ-AC_2:2 | 1.9030 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1242 | 1.9030 | 0.6620 | 1.0000 | Not calculated | 0.1242 | 0.0652 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.007112 | 371.75 | 2.6439 | 1.0000 | 2.6439 | 1.000 | 2.6439 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000381 | 139.41 | 0.1242 | 1.0000 | 0.1242 | 1.000 | 0.1242 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.007112 | 371.7481 | 2.6439 | 2.6439 | 2.6439 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000381 | 139.4052 | 0.1242 | 0.1242 | 0.1242 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0611 | 5.0611 | 5.0611 | No | 2.6439 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9030 | 1.9030 | 1.9030 | No | 0.1242 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.0611 | 5.0611 | 5.0611 | 5.0611 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.9030 | 1.9030 | 1.9030 | 1.9030 | 0.1242 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0611 | 5.0611 | 5.0611 | No | 2.6439 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9030 | 1.9030 | 1.9030 | No | 0.1242 | 0.6620 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.0611 | 5.0611 | 5.0611 | 5.0611 | 2.6439 | 1.0000 |
PSZ-AC_2:2 | 1.9030 | 1.9030 | 1.9030 | 1.9030 | 0.1242 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 0.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 66.66 | 67885.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 369.81 | 51756.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 127.24 | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.01 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 372.23 | 13788.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.39 | 4736.99 | 286.50 | 21754.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.54 | 1497.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.91 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 527.02 | 1544.15 |
Natural Gas | 469.79 | 822.95 |
Additional | 0.00 | 0.00 |
Total | 996.81 | 2367.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 248.92 |
Space Heating | 0.00 |
Space Cooling | 723.48 |
Fans (All) | 728.22 |
Service Water Heating | 147.48 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 3020.90 |
Subtotal | 3020.90 |
Natural Gas [MJ/m2] | |
Space Heating | 130.42 |
Service Water Heating | 560.49 |
Miscellaneous (All) | 1609.98 |
Subtotal | 1609.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.38 |
Space Heating | 2.82 |
Space Cooling | 15.62 |
Fans (All) | 15.73 |
Service Water Heating | 15.29 |
Receptacle Equipment | 39.31 |
Miscellaneous | 5.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 6817. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8414.50 | 345.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7593.00 | 1153.83 | 13.17 | 0.00 | 0.00 |
ATTIC | 5254.67 | 1059.17 | 912.00 | 1249.50 | 284.67 |
Min | 5254.67 | 345.50 | 0.00 | 0.00 | 0.00 |
Max | 8414.50 | 1153.83 | 912.00 | 1249.50 | 284.67 |
Average | 7087.39 | 852.83 | 308.39 | 416.50 | 94.89 |
Sum | 21262.17 | 2558.50 | 925.17 | 1249.50 | 284.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822882.67 | 1339.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822882.67 | 1339.33 | 0.00 | 0.00 | 0.00 |
Average | 280705.22 | 446.44 | 0.00 | 0.00 | 0.00 |
Sum | 842115.67 | 1339.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8369.33 | 390.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 5075.17 | 3684.17 | 0.67 | 0.00 | 0.00 |
ATTIC | 5419.50 | 1621.83 | 454.00 | 363.17 | 901.50 |
Min | 5075.17 | 390.67 | 0.00 | 0.00 | 0.00 |
Max | 8369.33 | 3684.17 | 454.00 | 363.17 | 901.50 |
Average | 6288.00 | 1898.89 | 151.56 | 121.06 | 300.50 |
Sum | 18864.00 | 5696.67 | 454.67 | 363.17 | 901.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 813071.00 | 11151.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 10341.50 | 8891.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 813071.00 | 11151.00 | 0.00 | 0.00 | 0.00 |
Average | 274470.83 | 6680.83 | 0.00 | 0.00 | 0.00 |
Sum | 823412.50 | 20042.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:27:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307226E+11 | 103378.32 | 08-JAN-04:01 | 17.00 | 11.36 | 0.143377E+11 | 14051.80 | 14-JAN-19:19 | 17.67 | 9.41 |
February | 0.244503E+11 | 35340.19 | 01-FEB-05:02 | 5.00 | 3.59 | 0.122372E+11 | 13578.60 | 25-FEB-19:19 | 14.67 | 9.60 |
March | 0.290794E+11 | 110730.10 | 18-MAR-03:01 | 14.03 | 9.79 | 0.145920E+11 | 14051.98 | 18-MAR-18:49 | 23.67 | 11.80 |
April | 0.390856E+11 | 136596.50 | 19-APR-03:01 | 14.82 | 5.67 | 0.147548E+11 | 14053.04 | 15-APR-18:30 | 14.82 | 5.67 |
May | 0.435764E+11 | 140732.27 | 01-MAY-03:01 | 13.58 | 4.86 | 0.154005E+11 | 14051.38 | 20-MAY-18:00 | 32.00 | 13.37 |
June | 0.503574E+11 | 119431.99 | 21-JUN-03:01 | 20.67 | 9.46 | 0.150269E+11 | 14055.55 | 17-JUN-18:00 | 20.67 | 9.46 |
July | 0.502925E+11 | 122940.56 | 01-JUL-03:01 | 20.92 | 7.93 | 0.153438E+11 | 14053.58 | 22-JUL-18:00 | 36.00 | 20.16 |
August | 0.503071E+11 | 121347.65 | 24-AUG-03:01 | 20.17 | 9.90 | 0.155369E+11 | 14052.53 | 05-AUG-18:19 | 20.17 | 9.90 |
September | 0.461189E+11 | 111635.80 | 29-SEP-03:01 | 21.83 | 11.88 | 0.149121E+11 | 14053.20 | 30-SEP-18:40 | 29.73 | 16.06 |
October | 0.390698E+11 | 141026.82 | 18-OCT-03:01 | 14.00 | 5.24 | 0.149851E+11 | 14052.72 | 28-OCT-18:49 | 20.17 | 10.54 |
November | 0.312318E+11 | 102515.56 | 02-NOV-03:01 | 14.17 | 11.17 | 0.139632E+11 | 14050.41 | 04-NOV-18:10 | 16.67 | 7.72 |
December | 0.286854E+11 | 43757.70 | 06-DEC-00:01 | 0.83 | -4.2 | 0.136215E+11 | 14051.42 | 02-DEC-19:49 | 0.83 | -4.2 |
Annual Sum or Average | 0.462977E+12 | 0.174712E+12 | ||||||||
Minimum of Months | 0.244503E+11 | 35340.19 | 0.83 | -4.2 | 0.122372E+11 | 13578.60 | 0.83 | -4.2 | ||
Maximum of Months | 0.503574E+11 | 141026.82 | 21.83 | 11.88 | 0.155369E+11 | 14055.55 | 36.00 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297059E+11 | 74225.99 | 02-JAN-04:01 | 4.83 | 1.48 | 0.106028E+11 | 6934.92 | 10-JAN-11:00 | 18.00 | 11.23 |
February | 0.258533E+11 | 72503.29 | 03-FEB-04:01 | 7.00 | 2.58 | 0.957782E+10 | 6934.94 | 15-FEB-11:00 | 18.00 | 13.11 |
March | 0.295897E+11 | 78110.01 | 27-MAR-03:01 | 3.53 | 0.03 | 0.106089E+11 | 6934.96 | 01-MAR-11:00 | 3.53 | 0.03 |
April | 0.326946E+11 | 79006.30 | 21-APR-03:51 | 8.00 | 0.42 | 0.102631E+11 | 6934.93 | 06-APR-10:09 | 8.00 | 0.42 |
May | 0.350607E+11 | 65012.65 | 01-MAY-03:01 | 13.58 | 4.86 | 0.106061E+11 | 6934.95 | 17-MAY-10:00 | 32.00 | 12.47 |
June | 0.367229E+11 | 55114.24 | 13-JUN-03:21 | 21.50 | 8.63 | 0.102665E+11 | 6934.98 | 23-JUN-10:00 | 35.00 | 16.20 |
July | 0.381161E+11 | 52570.84 | 02-JUL-02:42 | 20.10 | 7.28 | 0.106029E+11 | 6934.95 | 21-JUL-10:00 | 36.00 | 22.14 |
August | 0.379660E+11 | 53142.44 | 25-AUG-02:62 | 21.00 | 8.78 | 0.106092E+11 | 6934.98 | 31-AUG-10:00 | 34.00 | 18.59 |
September | 0.361828E+11 | 49179.14 | 29-SEP-02:62 | 21.28 | 11.66 | 0.102632E+11 | 6934.97 | 12-SEP-10:00 | 21.28 | 11.66 |
October | 0.337804E+11 | 74646.55 | 25-OCT-03:11 | 8.33 | 2.03 | 0.106030E+11 | 6934.95 | 02-OCT-10:50 | 8.33 | 2.03 |
November | 0.301732E+11 | 81542.96 | 23-NOV-04:11 | 2.33 | -1.1 | 0.102604E+11 | 6934.95 | 14-NOV-11:00 | 2.33 | -1.1 |
December | 0.291000E+11 | 86449.54 | 05-DEC-04:01 | -0.3 | -3.3 | 0.106025E+11 | 6934.90 | 27-DEC-11:00 | 18.00 | 8.61 |
Annual Sum or Average | 0.394946E+12 | 0.124866E+12 | ||||||||
Minimum of Months | 0.258533E+11 | 49179.14 | -0.3 | -3.3 | 0.957782E+10 | 6934.90 | 2.33 | -1.1 | ||
Maximum of Months | 0.381161E+11 | 86449.54 | 21.50 | 11.66 | 0.106092E+11 | 6934.98 | 36.00 | 22.14 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 | 1.81 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 | 11.09 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 | 14.60 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 | 18.35 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 | 16.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 | 15.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 | 10.27 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 9.20 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.00 | 0.00 | 4.27 | 1.81 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.00 | 0.00 | 29.40 | 18.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7547150.63 | 8949.60 | 08-JAN-04:03 | 17.00 |
February | 2319130.98 | 6132.93 | 03-FEB-05:02 | 7.00 |
March | 3306017.35 | 19751.14 | 18-MAR-03:02 | 14.03 |
April | 0.108669E+09 | 65497.05 | 12-APR-03:47 | 18.17 |
May | 0.335453E+09 | 78004.13 | 25-MAY-03:46 | 20.33 |
June | 0.818290E+09 | 61685.55 | 24-JUN-03:45 | 21.67 |
July | 0.677475E+09 | 75635.89 | 02-JUL-03:45 | 19.08 |
August | 0.559267E+09 | 46664.38 | 25-AUG-03:28 | 21.50 |
September | 0.330944E+09 | 49956.82 | 16-SEP-03:47 | 19.30 |
October | 0.101711E+09 | 76812.85 | 17-OCT-03:47 | 17.17 |
November | 1772204.18 | 4305.07 | 18-NOV-05:05 | 6.83 |
December | 1859301.64 | 4669.89 | 05-DEC-05:02 | 2.83 |
Annual Sum or Average | 0.294861E+10 | |||
Minimum of Months | 1772204.18 | 4305.07 | 2.83 | |
Maximum of Months | 0.818290E+09 | 78004.13 | 21.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826825E+10 | 4840.33 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.748896E+10 | 4840.33 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.839991E+10 | 4840.33 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.803398E+10 | 4840.33 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.833408E+10 | 4840.33 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.811917E+10 | 4840.33 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.824986E+10 | 4840.33 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.839991E+10 | 4840.33 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.803591E+10 | 4840.33 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.826728E+10 | 4840.33 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.800397E+10 | 4840.33 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.825082E+10 | 4840.33 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.978521E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.748896E+10 | 4840.33 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.839991E+10 | 4840.33 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.248296E+10 | 1453.55 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.224894E+10 | 1453.55 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.252250E+10 | 1453.55 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.241261E+10 | 1453.55 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.250273E+10 | 1453.55 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.243819E+10 | 1453.55 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.247744E+10 | 1453.55 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.252250E+10 | 1453.55 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.241319E+10 | 1453.55 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.248267E+10 | 1453.55 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.240360E+10 | 1453.55 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.247773E+10 | 1453.55 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.293850E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.224894E+10 | 1453.55 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.252250E+10 | 1453.55 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.826825E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65661055.49 | 0.452039E+10 |
February | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546553E+10 |
March | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172916E+09 | 0.426146E+10 |
April | 0.292871E+11 | 0.803398E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216338E+10 | 0.942751E+09 |
May | 0.303219E+11 | 0.833408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373090E+10 | 0.359106E+09 |
June | 0.295292E+11 | 0.811917E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646751E+10 | 60903252.74 |
July | 0.300798E+11 | 0.824986E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561019E+10 | 53560466.85 |
August | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525693E+10 | 0.140134E+09 |
September | 0.292871E+11 | 0.803591E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385188E+10 | 0.223251E+09 |
October | 0.300980E+11 | 0.826728E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143709E+10 | 0.215882E+10 |
November | 0.290996E+11 | 0.800397E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122922E+09 | 0.441206E+10 |
December | 0.300798E+11 | 0.825082E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15148187.90 | 0.625940E+10 |
Annual Sum or Average | 0.356244E+12 | 0.978521E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288945E+11 | 0.288574E+11 |
Minimum of Months | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53560466.85 |
Maximum of Months | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646751E+10 | 0.625940E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.248296E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 211558.44 | 0.307020E+09 |
February | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235274E+09 |
March | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 735689.64 | 0.324937E+09 |
April | 0.786997E+09 | 0.241261E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 23960004.88 | 0.120101E+09 |
May | 0.814802E+09 | 0.250273E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 52099128.07 | 80768332.57 |
June | 0.793501E+09 | 0.243819E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.107545E+09 | 30271634.68 |
July | 0.808298E+09 | 0.247744E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 93082848.72 | 32179024.91 |
August | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 66093653.27 | 44976222.38 |
September | 0.786997E+09 | 0.241319E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 48964899.54 | 67693269.47 |
October | 0.808786E+09 | 0.248267E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 15959949.47 | 0.170649E+09 |
November | 0.781956E+09 | 0.240360E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 440297.25 | 0.275589E+09 |
December | 0.808298E+09 | 0.247773E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 17.79 | 0.287637E+09 |
Annual Sum or Average | 0.957291E+10 | 0.293850E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.409093E+09 | 0.197709E+10 |
Minimum of Months | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30271634.68 |
Maximum of Months | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.107545E+09 | 0.324937E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106861E+10 | 0.289178E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629120E+09 | 0.288391E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627633E+09 | 0.365387E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103339E+10 | 0.495664E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111047E+10 | 0.519091E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938653E+09 | 0.522537E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643253E+09 | 0.475840E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841707E+09 | 0.457362E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657228E+09 | 0.358353E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110676E+10 | 0.323601E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894521E+09 | 0.282626E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125885E+10 | 0.271626E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108102E+11 | 0.464966E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627633E+09 | 0.271626E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125885E+10 | 0.522537E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 4840.33 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.28 | 31-JAN-14:00 | 8485.02 | 01-JAN-08:00 |
February | 30255.31 | 04-FEB-19:10 | 4840.33 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 7763.40 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 4840.33 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495.25 | 20-MAR-17:03 | 8320.71 | 26-MAR-06:10 |
April | 30255.31 | 01-APR-18:10 | 4840.33 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5852.83 | 14-APR-17:03 | 3992.98 | 06-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 4840.33 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6933.79 | 31-MAY-17:03 | 2990.99 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 4840.33 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.91 | 28-JUN-17:10 | 1541.70 | 21-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 4840.33 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8298.45 | 22-JUL-18:03 | 2002.25 | 01-JUL-06:10 |
August | 30255.31 | 05-AUG-18:10 | 4840.33 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8983.71 | 25-AUG-17:03 | 4380.95 | 05-AUG-18:10 |
September | 30255.31 | 02-SEP-18:10 | 4840.33 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7077.47 | 07-SEP-17:03 | 2147.53 | 22-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 4840.33 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.41 | 06-OCT-12:00 | 5670.04 | 25-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 4840.33 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.45 | 01-NOV-13:00 | 8578.86 | 23-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 4840.33 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 752.96 | 25-DEC-14:00 | 10164.54 | 05-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1541.70 | |||||
Maximum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.91 | 10164.54 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1453.55 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 10.29 | 31-JAN-15:25 | 980.40 | 01-JAN-01:10 |
February | 813.01 | 04-FEB-19:10 | 1453.55 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 846.17 | 05-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 1453.55 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 18.53 | 15-MAR-15:00 | 818.76 | 08-MAR-05:00 |
April | 813.01 | 01-APR-18:10 | 1453.55 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 100.90 | 30-APR-15:02 | 444.25 | 27-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 1453.55 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 166.50 | 20-MAY-13:53 | 352.67 | 14-MAY-02:50 |
June | 813.01 | 03-JUN-18:10 | 1453.55 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 223.05 | 19-JUN-13:53 | 256.71 | 13-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 1453.55 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 216.41 | 22-JUL-16:00 | 427.45 | 27-JUL-00:40 |
August | 813.01 | 05-AUG-18:10 | 1453.55 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 170.72 | 13-AUG-15:53 | 491.63 | 19-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 1453.55 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 181.34 | 17-SEP-24:00 | 378.05 | 16-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 1453.55 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 85.93 | 10-OCT-14:53 | 593.31 | 26-OCT-02:10 |
November | 813.01 | 04-NOV-18:10 | 1453.55 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 16.10 | 01-NOV-15:53 | 980.48 | 29-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 1453.55 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.02 | 21-DEC-14:55 | 737.42 | 09-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 256.71 | ||||||
Maximum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 223.05 | 980.48 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1588.53 | 18-JAN-07:30 | 5730.39 | 09-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1431.93 | 02-FEB-05:45 | 7567.89 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.92 | 19-MAR-07:42 | 8091.77 | 26-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1552.66 | 30-APR-06:00 | 8150.58 | 27-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1634.99 | 24-MAY-06:23 | 7780.09 | 27-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.60 | 20-JUN-05:53 | 7585.84 | 25-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.34 | 07-JUL-03:51 | 7536.85 | 27-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1702.33 | 25-AUG-06:33 | 7405.50 | 07-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.52 | 17-SEP-04:53 | 7033.49 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.79 | 26-OCT-07:13 | 6206.91 | 04-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1542.56 | 19-NOV-02:53 | 6272.11 | 14-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.73 | 21-DEC-07:35 | 5369.58 | 14-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.92 | 5369.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.73 | 8150.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 103378.32 | 08-JAN-04:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.09 |
February | 35340.19 | 01-FEB-05:02 | 8404.25 | 5378.14 | 14482.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.09 |
March | 110730.10 | 18-MAR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.74 |
April | 136596.50 | 19-APR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.14 |
May | 140732.27 | 01-MAY-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 |
June | 119431.99 | 21-JUN-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 |
July | 122940.56 | 01-JUL-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.15 |
August | 121347.65 | 24-AUG-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.95 |
September | 111635.80 | 29-SEP-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.89 |
October | 141026.82 | 18-OCT-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 |
November | 102515.56 | 02-NOV-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.70 |
December | 43757.70 | 06-DEC-00:01 | 16808.50 | 8067.21 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 35340.19 | 0.00 | 5378.14 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 | |
Maximum of Months | 141026.82 | 16808.50 | 8067.21 | 14482.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 74225.99 | 02-JAN-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 381.24 |
February | 72503.29 | 03-FEB-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 330.79 |
March | 78110.01 | 27-MAR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 134.65 |
April | 79006.30 | 21-APR-03:51 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 127.01 |
May | 65012.65 | 01-MAY-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 202.80 |
June | 55114.24 | 13-JUN-03:21 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 160.68 |
July | 52570.84 | 02-JUL-02:42 | 0.00 | 1211.29 | 11343.43 | 2715.37 | 0.00 | 0.00 | 0.00 | 0.00 | 135.59 |
August | 53142.44 | 25-AUG-02:62 | 0.00 | 1453.55 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 116.75 |
September | 49179.14 | 29-SEP-02:62 | 0.00 | 1211.29 | 11343.43 | 2715.37 | 0.00 | 0.00 | 0.00 | 0.00 | 149.41 |
October | 74646.55 | 25-OCT-03:11 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 254.13 |
November | 81542.96 | 23-NOV-04:11 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 191.60 |
December | 86449.54 | 05-DEC-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 393.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 49179.14 | 0.00 | 1211.29 | 11343.43 | 2715.37 | 0.00 | 0.00 | 0.00 | 0.00 | 116.75 | |
Maximum of Months | 86449.54 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 393.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.04 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.57 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.63 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 996.20 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.07 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.81 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.40 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.18 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.50 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.27 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.53 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.53 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.107823E+12 | 69267.05 | 31-JAN-17:10 | 0.788233E+11 | 89587.37 | 01-JAN-07:00 |
February | 0.910161E+11 | 57532.56 | 18-FEB-13:00 | 0.734843E+11 | 69551.16 | 28-FEB-07:10 |
March | 0.108050E+12 | 71438.66 | 17-MAR-11:00 | 0.770434E+11 | 89976.64 | 26-MAR-05:40 |
April | 0.127385E+12 | 83135.86 | 14-APR-17:19 | 0.633021E+11 | 49480.20 | 21-APR-05:10 |
May | 0.141430E+12 | 86232.84 | 31-MAY-17:19 | 0.631175E+11 | 42806.72 | 06-MAY-10:30 |
June | 0.156008E+12 | 98760.37 | 28-JUN-17:10 | 0.595159E+11 | 42542.84 | 03-JUN-10:50 |
July | 0.164295E+12 | 95346.68 | 19-JUL-11:00 | 0.603975E+11 | 42387.98 | 01-JUL-10:20 |
August | 0.163195E+12 | 95595.02 | 25-AUG-17:10 | 0.608290E+11 | 42429.17 | 26-AUG-10:09 |
September | 0.150438E+12 | 91171.95 | 08-SEP-18:40 | 0.599433E+11 | 42671.63 | 30-SEP-10:39 |
October | 0.125951E+12 | 86537.80 | 02-OCT-10:00 | 0.661063E+11 | 64902.99 | 25-OCT-06:30 |
November | 0.104945E+12 | 73013.02 | 01-NOV-11:00 | 0.711907E+11 | 87321.88 | 23-NOV-06:40 |
December | 0.103609E+12 | 65477.26 | 22-DEC-11:00 | 0.891954E+11 | 96645.05 | 06-DEC-07:10 |
Annual Sum or Average | 0.154415E+13 | 0.822949E+12 | ||||
Minimum of Months | 0.910161E+11 | 57532.56 | 0.595159E+11 | 42387.98 | ||
Maximum of Months | 0.164295E+12 | 98760.37 | 0.891954E+11 | 96645.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.107512E+11 | 0.705177E+10 | 0.391293E+11 | 0.00 | 0.313633E+11 | 37879553.69 | 0.00 | 0.751601E+10 | 0.00 | 0.00 | 0.00 | 0.637966E+10 | 0.00 |
February | 0.973789E+10 | 0.604909E+10 | 0.353426E+11 | 0.00 | 0.282956E+11 | 34213790.43 | 0.00 | 0.691264E+09 | 0.00 | 0.00 | 0.00 | 0.577382E+10 | 0.00 |
March | 0.109224E+11 | 0.621941E+10 | 0.391293E+11 | 0.00 | 0.313448E+11 | 37879553.69 | 0.00 | 0.833180E+10 | 0.00 | 0.00 | 0.00 | 0.644828E+10 | 0.00 |
April | 0.104466E+11 | 0.552989E+10 | 0.378671E+11 | 0.00 | 0.306721E+11 | 36657632.61 | 0.00 | 0.312056E+11 | 0.00 | 0.00 | 0.00 | 0.619291E+10 | 0.00 |
May | 0.108368E+11 | 0.529364E+10 | 0.391293E+11 | 0.00 | 0.317939E+11 | 37879553.69 | 0.00 | 0.422919E+11 | 0.00 | 0.00 | 0.00 | 0.641471E+10 | 0.00 |
June | 0.105574E+11 | 0.494751E+10 | 0.378671E+11 | 0.00 | 0.307767E+11 | 36657632.61 | 0.00 | 0.601152E+11 | 0.00 | 0.00 | 0.00 | 0.623618E+10 | 0.00 |
July | 0.107273E+11 | 0.517826E+10 | 0.391293E+11 | 0.00 | 0.318725E+11 | 37879553.69 | 0.00 | 0.653143E+11 | 0.00 | 0.00 | 0.00 | 0.637169E+10 | 0.00 |
August | 0.109224E+11 | 0.552439E+10 | 0.391293E+11 | 0.00 | 0.318650E+11 | 37879553.69 | 0.00 | 0.635842E+11 | 0.00 | 0.00 | 0.00 | 0.644979E+10 | 0.00 |
September | 0.104491E+11 | 0.580185E+10 | 0.378671E+11 | 0.00 | 0.308519E+11 | 36657632.61 | 0.00 | 0.537381E+11 | 0.00 | 0.00 | 0.00 | 0.619435E+10 | 0.00 |
October | 0.107500E+11 | 0.650510E+10 | 0.391293E+11 | 0.00 | 0.316798E+11 | 37879553.69 | 0.00 | 0.258510E+11 | 0.00 | 0.00 | 0.00 | 0.637817E+10 | 0.00 |
November | 0.104076E+11 | 0.672212E+10 | 0.378671E+11 | 0.00 | 0.304582E+11 | 36657632.61 | 0.00 | 0.785042E+10 | 0.00 | 0.00 | 0.00 | 0.617410E+10 | 0.00 |
December | 0.107286E+11 | 0.718638E+10 | 0.391293E+11 | 0.00 | 0.312599E+11 | 37879553.69 | 0.00 | 0.332108E+10 | 0.00 | 0.00 | 0.00 | 0.637165E+10 | 0.00 |
Annual Sum or Average | 0.127237E+12 | 0.720094E+11 | 0.460716E+12 | 0.00 | 0.372234E+12 | 0.446001E+09 | 0.00 | 0.369811E+12 | 0.00 | 0.00 | 0.00 | 0.753853E+11 | 0.00 |
Minimum of Months | 0.973789E+10 | 0.494751E+10 | 0.353426E+11 | 0.00 | 0.282956E+11 | 34213790.43 | 0.00 | 0.691264E+09 | 0.00 | 0.00 | 0.00 | 0.577382E+10 | 0.00 |
Maximum of Months | 0.109224E+11 | 0.718638E+10 | 0.391293E+11 | 0.00 | 0.318725E+11 | 37879553.69 | 0.00 | 0.653143E+11 | 0.00 | 0.00 | 0.00 | 0.644979E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.108302E+11 | 0.00 | 0.280934E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.122418E+11 | 0.00 | 0.252040E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.102059E+11 | 0.00 | 0.269378E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.584364E+09 | 0.00 | 0.241051E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.250422E+09 | 0.00 | 0.229674E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.177053E+09 | 0.00 | 0.207262E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 88131475.02 | 0.00 | 0.204097E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 55304375.65 | 0.00 | 0.208740E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 85045950.20 | 0.00 | 0.212456E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.246757E+10 | 0.00 | 0.237391E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.767664E+10 | 0.00 | 0.249014E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.220017E+11 | 0.00 | 0.272940E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.666642E+11 | 0.00 | 0.286498E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 55304375.65 | 0.00 | 0.204097E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.220017E+11 | 0.00 | 0.280934E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6293.88 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13788.39 | 01-JAN-00:20 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 6293.88 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13788.39 | 01-FEB-05:10 | 17.86 | 23-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 6293.88 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13788.39 | 01-MAR-07:49 | 17.86 | 12-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 6293.88 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13788.39 | 01-APR-07:40 | 17.86 | 22-APR-08:39 | 0.00 | 01-APR-00:10 |
May | 6293.88 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13788.39 | 01-MAY-07:10 | 17.86 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 6293.88 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13788.39 | 01-JUN-09:50 | 17.86 | 05-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 6293.88 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13788.39 | 01-JUL-18:10 | 17.86 | 03-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 6293.88 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13788.39 | 01-AUG-07:40 | 17.86 | 02-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 6293.88 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13788.39 | 01-SEP-07:49 | 17.86 | 01-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 6293.88 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13788.39 | 01-OCT-08:30 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 6293.88 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13788.39 | 01-NOV-04:10 | 17.86 | 07-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 6293.88 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13788.39 | 01-DEC-00:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13788.39 | 17.86 | 0.00 | ||||||
Maximum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13788.39 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 21831.53 | 31-JAN-17:10 | 0.00 | 0.00 | 0.00 | 4736.39 | 23-JAN-19:00 | 0.00 |
February | 11308.51 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4736.67 | 27-FEB-19:00 | 0.00 |
March | 23959.25 | 20-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4736.77 | 20-MAR-18:00 | 0.00 |
April | 36031.34 | 14-APR-17:10 | 0.00 | 0.00 | 0.00 | 4736.61 | 07-APR-18:30 | 0.00 |
May | 39093.84 | 15-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4736.85 | 04-MAY-18:30 | 0.00 |
June | 51756.26 | 28-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.99 | 27-JUN-06:19 | 0.00 |
July | 48897.09 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.90 | 03-JUL-06:19 | 0.00 |
August | 48855.40 | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.57 | 14-AUG-06:49 | 0.00 |
September | 43625.61 | 08-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4736.76 | 18-SEP-18:00 | 0.00 |
October | 37875.66 | 02-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4736.64 | 06-OCT-18:30 | 0.00 |
November | 26473.89 | 01-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4736.75 | 10-NOV-07:19 | 0.00 |
December | 17504.57 | 25-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4736.51 | 05-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11308.51 | 0.00 | 0.00 | 0.00 | 4736.39 | 0.00 | ||
Maximum of Months | 51756.26 | 0.00 | 0.00 | 0.00 | 4736.99 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 69267.05 | 31-JAN-17:10 | 6293.88 | 22286.02 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 21831.53 | 0.00 |
February | 57532.56 | 18-FEB-13:00 | 5594.56 | 21481.47 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 11308.51 | 0.00 |
March | 71438.66 | 17-MAR-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 23131.37 | 0.00 |
April | 83135.86 | 14-APR-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 35855.28 | 0.00 |
May | 86232.84 | 31-MAY-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 38956.51 | 0.00 |
June | 98760.37 | 28-JUN-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 51756.26 | 0.00 |
July | 95346.68 | 19-JUL-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 47043.28 | 0.00 |
August | 95595.02 | 25-AUG-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 48855.40 | 0.00 |
September | 91171.95 | 08-SEP-18:40 | 6293.88 | 19067.80 | 4578.48 | 0.00 | 13788.39 | 17.86 | 0.00 | 40817.90 | 0.00 |
October | 86537.80 | 02-OCT-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 35348.08 | 0.00 |
November | 73013.02 | 01-NOV-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 24730.00 | 0.00 |
December | 65477.26 | 22-DEC-11:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 14478.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 57532.56 | 5594.56 | 19067.80 | 0.00 | 0.00 | 13788.39 | 17.86 | 0.00 | 11308.51 | 0.00 | |
Maximum of Months | 98760.37 | 6293.88 | 24699.69 | 4578.48 | 0.00 | 13788.39 | 17.86 | 0.00 | 51756.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 63151.72 | 01-JAN-06:10 | 0.00 | 21754.00 | 20-JAN-19:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 43279.40 | 09-FEB-05:19 | 0.00 | 21563.37 | 03-FEB-19:00 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 63547.09 | 26-MAR-05:00 | 0.00 | 19112.27 | 10-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 28279.73 | 12-APR-03:49 | 0.00 | 17632.00 | 03-APR-18:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 32926.59 | 29-MAY-03:49 | 0.00 | 17252.95 | 01-MAY-18:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 17906.81 | 24-JUN-03:49 | 0.00 | 16867.41 | 01-JUN-18:19 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 23794.47 | 02-JUL-03:49 | 0.00 | 16622.90 | 03-JUL-06:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 9538.32 | 07-AUG-03:49 | 0.00 | 16724.77 | 31-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 20888.46 | 16-SEP-03:49 | 0.00 | 17015.56 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 35924.65 | 25-OCT-05:00 | 0.00 | 17435.74 | 31-OCT-18:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 61079.22 | 23-NOV-06:00 | 0.00 | 17816.09 | 30-NOV-07:30 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 67885.18 | 06-DEC-06:00 | 0.00 | 20943.91 | 29-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 9538.32 | 0.00 | 16622.90 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 67885.18 | 0.00 | 21754.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.71 | 0.00 | 24.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.74 | 0.00 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.24 | 0.00 | 25.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.39 | 0.00 | 25.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.38 | 0.00 | 25.38 |
September | 0.17 | 20.31 | 0.00 | 20.31 | 3.50 | 24.88 | 0.00 | 24.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.83 | 0.00 | 24.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.58 | 0.00 | 24.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.31 | 0.00 | 20.31 | 25.00 | 25.08 | 0.00 | 25.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.31 | 0.00 | 20.31 | 4.83 | 25.39 | 0.00 | 25.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 29.75 | 0.00 | 29.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 29.84 | 0.00 | 29.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 29.95 | 0.00 | 29.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 30.70 | 0.00 | 30.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 30.70 | 0.17 | 30.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 30.71 | 0.00 | 30.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 30.80 | 0.17 | 30.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.74 | 0.17 | 30.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 30.96 | 0.00 | 30.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.71 | 0.00 | 30.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 30.35 | 0.00 | 30.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 29.53 | 0.00 | 29.53 |
Annual Sum or Average | 0.00 | 0.00 | 268.33 | 30.54 | 0.50 | 30.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 29.53 | 0.00 | 29.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 30.96 | 0.17 | 30.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.17 | 21.39 | 101.83 | 21.82 | 21.33 | 21.73 |
February | 401.50 | 21.33 | 82.67 | 21.62 | 16.00 | 21.54 |
March | 300.17 | 21.51 | 163.50 | 22.27 | 9.33 | 22.19 |
April | 94.67 | 22.42 | 301.33 | 23.68 | 0.00 | 23.68 |
May | 40.00 | 23.13 | 365.67 | 24.07 | 1.00 | 24.08 |
June | 21.33 | 29.43 | 516.33 | 24.49 | 21.33 | 24.68 |
July | 69.00 | 25.93 | 579.50 | 24.43 | 68.83 | 24.57 |
August | 73.50 | 25.66 | 597.67 | 24.38 | 73.50 | 24.50 |
September | 69.50 | 24.97 | 581.00 | 24.25 | 69.50 | 24.32 |
October | 139.67 | 22.00 | 344.17 | 23.45 | 7.83 | 23.48 |
November | 299.33 | 21.79 | 208.17 | 22.55 | 60.17 | 22.58 |
December | 431.17 | 21.34 | 58.50 | 21.24 | 38.83 | 21.06 |
Annual Sum or Average | 2252.00 | 22.02 | 3900.33 | 23.29 | 387.67 | 23.33 |
Minimum of Months | 21.33 | 21.33 | 58.50 | 21.24 | 0.00 | 21.06 |
Maximum of Months | 431.17 | 29.43 | 597.67 | 24.49 | 73.50 | 24.68 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.50 | 26.00 | 610.00 | 26.00 | 408.50 | 26.00 |
February | 418.50 | 25.99 | 551.00 | 25.99 | 418.50 | 25.99 |
March | 425.83 | 26.00 | 612.00 | 26.00 | 425.83 | 26.00 |
April | 434.50 | 26.00 | 590.00 | 26.00 | 434.50 | 26.00 |
May | 474.83 | 26.00 | 611.00 | 26.00 | 474.83 | 26.00 |
June | 555.67 | 26.00 | 592.00 | 26.00 | 555.67 | 26.00 |
July | 595.83 | 26.00 | 609.00 | 26.00 | 595.83 | 26.00 |
August | 603.33 | 26.00 | 612.00 | 26.00 | 603.33 | 26.00 |
September | 589.33 | 26.00 | 590.00 | 26.00 | 589.33 | 26.00 |
October | 493.17 | 26.00 | 610.00 | 26.00 | 493.17 | 26.00 |
November | 453.33 | 26.00 | 591.00 | 26.00 | 453.33 | 26.00 |
December | 374.50 | 25.99 | 609.00 | 25.99 | 374.50 | 25.99 |
Annual Sum or Average | 5827.33 | 26.00 | 7187.00 | 26.00 | 5827.33 | 26.00 |
Minimum of Months | 374.50 | 25.99 | 551.00 | 25.99 | 374.50 | 25.99 |
Maximum of Months | 603.33 | 26.00 | 612.00 | 26.00 | 603.33 | 26.00 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.63623 | 25.98754 | 0.08867 | 7.70217 |
February | 551.00000 | 21.99403 | 41.22541 | 0.00020 | 6.92897 |
March | 612.00000 | 22.74861 | 30.36472 | 0.12186 | 7.70082 |
April | 590.00000 | 23.79124 | 19.75453 | 0.37484 | 8.85841 |
May | 611.00000 | 24.04701 | 17.94609 | -0.3762 | 8.77338 |
June | 592.00000 | 24.24764 | 24.95034 | -0.1973 | 6.91671 |
July | 609.00000 | 24.23476 | 42.69656 | -0.0789 | 6.29865 |
August | 612.00000 | 24.21535 | 44.82931 | -0.0676 | 6.05953 |
September | 590.00000 | 24.16255 | 45.15233 | -0.0962 | 5.91923 |
October | 610.00000 | 23.53492 | 28.88057 | 0.38070 | 9.89575 |
November | 591.00000 | 22.83920 | 31.08056 | 0.19175 | 8.53400 |
December | 609.00000 | 22.10147 | 18.98789 | -0.0916 | 8.08294 |
Annual Sum or Average | 7187.00000 | 23.38693 | 30.91257 | 0.02044 | 7.64574 |
Minimum of Months | 551.00000 | 21.99403 | 17.94609 | -0.3762 | 5.91923 |
Maximum of Months | 612.00000 | 24.24764 | 45.15233 | 0.38070 | 9.89575 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.99685 | 28.48563 | 1.02825 | 27.62389 |
February | 551.00000 | 25.99402 | 39.43060 | 1.08392 | 30.02546 |
March | 612.00000 | 25.99705 | 32.48537 | 1.05589 | 28.86000 |
April | 590.00000 | 25.99983 | 34.37260 | 1.15927 | 34.01136 |
May | 611.00000 | 26.00143 | 37.74192 | 0.65710 | 15.55621 |
June | 592.00000 | 26.00322 | 44.47884 | 0.78061 | 18.89488 |
July | 609.00000 | 26.00276 | 49.28077 | 0.82315 | 20.00344 |
August | 612.00000 | 26.00256 | 49.97343 | 0.82154 | 19.94732 |
September | 590.00000 | 26.00206 | 49.38123 | 0.80630 | 19.37040 |
October | 610.00000 | 25.99923 | 34.56084 | 1.15880 | 33.79756 |
November | 591.00000 | 25.99628 | 32.79855 | 1.09217 | 30.57894 |
December | 609.00000 | 25.99506 | 24.27395 | 0.97994 | 25.57878 |
Annual Sum or Average | 7187.00000 | 25.99923 | 38.07356 | 0.95272 | 25.30942 |
Minimum of Months | 551.00000 | 25.99402 | 24.27395 | 0.65710 | 15.55621 |
Maximum of Months | 612.00000 | 26.00322 | 49.97343 | 1.15927 | 34.01136 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.143840E+11 | 0.497268E+10 | 229.58 | 0.141843E+11 | 0.199679E+09 | 0.00 | 1.00 | 08-JAN-04:01 | 0.00 | 01-JAN-00:01 | 123987.71 | 08-JAN-04:01 | 95626.46 | 08-JAN-04:01 | 28361.25 | 08-JAN-04:01 | 34930.52 | 08-JAN-04:01 | 0.00 | 01-JAN-00:01 |
February | 0.107246E+10 | 0.382119E+09 | 41.78 | 0.896674E+09 | 0.175789E+09 | 0.00 | 0.21 | 18-FEB-13:53 | 0.00 | 01-FEB-00:05 | 21068.19 | 18-FEB-13:53 | 15976.37 | 18-FEB-13:57 | 5092.66 | 18-FEB-13:53 | 7328.51 | 18-FEB-13:53 | 0.00 | 01-FEB-00:05 |
March | 0.159181E+11 | 0.545527E+10 | 232.43 | 0.151135E+11 | 0.804566E+09 | 0.00 | 1.00 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 | 123987.71 | 17-MAR-03:01 | 94882.23 | 17-MAR-03:01 | 31205.54 | 18-MAR-03:01 | 34930.52 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.635834E+11 | 0.213957E+11 | 461.63 | 0.632351E+11 | 0.348320E+09 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 123987.71 | 15-APR-03:26 | 123987.71 | 11-APR-03:01 | 31164.66 | 17-APR-03:01 | 34930.52 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.868506E+11 | 0.294686E+11 | 531.04 | 0.867647E+11 | 85915959.31 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 123987.71 | 06-MAY-03:01 | 123987.71 | 02-MAY-03:41 | 19119.07 | 11-MAY-03:15 | 34930.52 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.122543E+12 | 0.433016E+11 | 580.94 | 0.121569E+12 | 0.973502E+09 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 123987.71 | 02-JUN-03:24 | 123987.71 | 05-JUN-03:14 | 15135.44 | 17-JUN-17:10 | 40016.38 | 28-JUN-17:03 | 0.00 | 01-JUN-00:01 |
July | 0.140344E+12 | 0.468577E+11 | 609.41 | 0.117537E+12 | 0.228074E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 137758.50 | 14-JUL-03:01 | 123987.71 | 02-JUL-03:01 | 79674.46 | 14-JUL-03:02 | 37404.56 | 19-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.136095E+12 | 0.455476E+11 | 607.78 | 0.113442E+12 | 0.226527E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 133007.05 | 01-AUG-03:01 | 123987.71 | 24-AUG-03:01 | 62556.03 | 07-AUG-03:01 | 37487.09 | 25-AUG-17:03 | 0.00 | 01-AUG-00:01 |
September | 0.115890E+12 | 0.379950E+11 | 572.87 | 0.941681E+11 | 0.217221E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 136210.37 | 04-SEP-03:01 | 123987.71 | 18-SEP-03:01 | 79977.83 | 04-SEP-03:01 | 35898.79 | 04-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.535030E+11 | 0.178972E+11 | 409.56 | 0.485621E+11 | 0.494089E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 133125.22 | 03-OCT-03:01 | 123987.71 | 16-OCT-03:01 | 67113.50 | 03-OCT-03:02 | 35647.64 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.151551E+11 | 0.516860E+10 | 208.89 | 0.138672E+11 | 0.128788E+10 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 126618.85 | 13-NOV-04:01 | 94223.11 | 01-NOV-03:01 | 72666.81 | 13-NOV-04:01 | 35138.55 | 13-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.602873E+10 | 0.210237E+10 | 125.47 | 0.599654E+10 | 32197248.36 | 0.00 | 0.35 | 22-DEC-14:00 | 0.00 | 01-DEC-00:02 | 35895.77 | 22-DEC-14:00 | 35895.77 | 22-DEC-14:00 | 1738.11 | 12-DEC-13:00 | 12077.85 | 22-DEC-14:00 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.771367E+12 | 0.260544E+12 | 4611.40 | 0.695336E+12 | 0.760310E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.107246E+10 | 0.382119E+09 | 41.78 | 0.896674E+09 | 32197248.36 | 0.00 | 0.21 | 0.00 | 21068.19 | 15976.37 | 1738.11 | 7328.51 | 0.00 | |||||||
Maximum of Months | 0.140344E+12 | 0.468577E+11 | 609.41 | 0.121569E+12 | 0.228074E+11 | 0.00 | 1.00 | 0.00 | 137758.50 | 123987.71 | 79977.83 | 40016.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.773394E+10 | 0.254332E+10 | 257.33 | 0.750490E+10 | 0.229035E+09 | 0.00 | 1.00 | 02-JAN-04:01 | 0.00 | 01-JAN-00:01 | 41432.10 | 06-JAN-04:01 | 41111.13 | 17-JAN-04:01 | 21303.98 | 09-JAN-04:01 | 11436.90 | 02-JAN-04:01 | 0.00 | 01-JAN-00:01 |
February | 0.920824E+09 | 0.309145E+09 | 65.56 | 0.737773E+09 | 0.183051E+09 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 | 41432.10 | 02-FEB-04:01 | 35848.29 | 10-FEB-04:01 | 23718.64 | 18-FEB-04:21 | 11436.90 | 01-FEB-04:01 | 0.00 | 01-FEB-00:05 |
March | 0.892014E+10 | 0.287653E+10 | 256.08 | 0.807291E+10 | 0.847234E+09 | 0.00 | 1.00 | 01-MAR-04:11 | 0.00 | 01-MAR-00:03 | 41432.10 | 07-MAR-04:21 | 38474.31 | 25-MAR-03:01 | 21240.73 | 06-MAR-04:11 | 11436.90 | 01-MAR-04:11 | 0.00 | 01-MAR-00:03 |
April | 0.313920E+11 | 0.980997E+10 | 468.18 | 0.265051E+11 | 0.488690E+10 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 41432.10 | 02-APR-03:31 | 41432.10 | 05-APR-03:31 | 11199.20 | 17-APR-03:01 | 11436.90 | 01-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.405252E+11 | 0.128233E+11 | 554.15 | 0.339457E+11 | 0.657946E+10 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 41432.10 | 04-MAY-03:01 | 41432.10 | 02-MAY-03:01 | 9383.02 | 19-MAY-10:32 | 11436.90 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.507012E+11 | 0.168135E+11 | 621.06 | 0.418634E+11 | 0.883776E+10 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 41432.10 | 03-JUN-01:22 | 41432.10 | 02-JUN-03:31 | 10356.07 | 18-JUN-10:32 | 11931.58 | 28-JUN-16:43 | 0.00 | 01-JUN-00:01 |
July | 0.585105E+11 | 0.184566E+11 | 649.64 | 0.434957E+11 | 0.150149E+11 | 0.00 | 1.00 | 01-JUL-00:11 | 0.00 | 01-JUL-00:01 | 45851.08 | 14-JUL-03:01 | 42099.47 | 21-JUL-00:42 | 27659.67 | 14-JUL-02:42 | 11930.69 | 23-JUL-00:42 | 0.00 | 01-JUL-00:01 |
August | 0.572436E+11 | 0.180366E+11 | 648.85 | 0.420565E+11 | 0.151871E+11 | 0.00 | 1.00 | 01-AUG-00:12 | 0.00 | 01-AUG-00:01 | 45190.83 | 01-AUG-03:01 | 41432.10 | 25-AUG-00:42 | 22966.02 | 20-AUG-00:42 | 11798.26 | 28-AUG-10:32 | 0.00 | 01-AUG-00:01 |
September | 0.511947E+11 | 0.157431E+11 | 606.62 | 0.371034E+11 | 0.140913E+11 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 45272.61 | 02-SEP-00:11 | 41432.10 | 18-SEP-00:28 | 28326.49 | 04-SEP-03:33 | 11734.09 | 02-SEP-00:11 | 0.00 | 01-SEP-00:01 |
October | 0.254044E+11 | 0.795387E+10 | 421.09 | 0.207619E+11 | 0.464254E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:01 | 44333.95 | 03-OCT-03:01 | 41432.10 | 14-OCT-03:01 | 23749.50 | 03-OCT-03:01 | 11659.91 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.832613E+10 | 0.268182E+10 | 232.99 | 0.732347E+10 | 0.100266E+10 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 41432.10 | 03-NOV-03:01 | 40895.09 | 29-NOV-04:01 | 26386.39 | 12-NOV-04:01 | 11436.90 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.366891E+10 | 0.121871E+10 | 152.87 | 0.361844E+10 | 50464972.00 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:02 | 41432.10 | 15-DEC-04:01 | 41432.10 | 09-DEC-04:01 | 21087.70 | 13-DEC-04:21 | 11436.90 | 01-DEC-04:01 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.344542E+12 | 0.109266E+12 | 4934.42 | 0.272989E+12 | 0.715523E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.920824E+09 | 0.309145E+09 | 65.56 | 0.737773E+09 | 50464972.00 | 0.00 | 1.00 | 0.00 | 41432.10 | 35848.29 | 9383.02 | 11436.90 | 0.00 | |||||||
Maximum of Months | 0.585105E+11 | 0.184566E+11 | 649.64 | 0.434957E+11 | 0.151871E+11 | 0.00 | 1.00 | 0.00 | 45851.08 | 42099.47 | 28326.49 | 11931.58 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.11 | 103.78 | 61.33 | 266.07 | 332.50 | 0.00 | 0.00 | 0.00 |
February | 163.35 | 93.82 | 69.53 | 236.68 | 327.09 | 0.00 | 0.00 | 0.00 |
March | 202.52 | 103.80 | 98.71 | 337.08 | 286.70 | 0.00 | 0.00 | 0.00 |
April | 288.23 | 171.12 | 117.10 | 643.44 | 160.94 | 0.00 | 0.00 | 0.00 |
May | 299.38 | 177.07 | 122.30 | 726.66 | 114.47 | 0.00 | 0.00 | 0.00 |
June | 311.61 | 193.08 | 118.52 | 897.59 | 53.69 | 0.00 | 0.00 | 0.00 |
July | 263.72 | 148.38 | 115.34 | 766.75 | 42.74 | 0.00 | 0.00 | 0.00 |
August | 250.31 | 142.53 | 107.78 | 715.41 | 57.44 | 0.00 | 0.00 | 0.00 |
September | 205.39 | 98.72 | 106.67 | 556.18 | 75.84 | 0.00 | 0.00 | 0.00 |
October | 206.13 | 125.14 | 81.00 | 426.67 | 216.13 | 0.00 | 0.00 | 0.00 |
November | 159.21 | 95.58 | 63.63 | 251.66 | 315.60 | 0.00 | 0.00 | 0.00 |
December | 145.92 | 88.48 | 57.44 | 204.18 | 400.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 222.01 | 128.62 | 93.39 | 503.62 | 198.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.92 | 88.48 | 57.44 | 204.18 | 42.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 311.61 | 193.08 | 122.30 | 897.59 | 400.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 574.66 | 457.67 | 116.99 | 1164.88 | 454.20 | 0.00 | 0.00 | 0.00 |
February | 362.66 | 243.02 | 119.64 | 644.33 | 443.76 | 0.00 | 0.00 | 0.00 |
March | 306.18 | 157.96 | 148.22 | 575.76 | 414.59 | 0.00 | 0.00 | 0.00 |
April | 275.58 | 120.49 | 155.09 | 680.30 | 246.48 | 0.00 | 0.00 | 0.00 |
May | 183.57 | 38.01 | 145.56 | 507.42 | 178.60 | 0.00 | 0.00 | 0.00 |
June | 153.31 | 15.53 | 137.78 | 596.13 | 83.09 | 0.00 | 0.00 | 0.00 |
July | 155.49 | 18.71 | 136.78 | 577.67 | 64.29 | 0.00 | 0.00 | 0.00 |
August | 195.26 | 60.99 | 134.26 | 671.59 | 84.03 | 0.00 | 0.00 | 0.00 |
September | 272.36 | 119.08 | 153.28 | 784.65 | 110.59 | 0.00 | 0.00 | 0.00 |
October | 428.62 | 297.48 | 131.14 | 953.59 | 300.57 | 0.00 | 0.00 | 0.00 |
November | 496.35 | 380.16 | 116.19 | 983.47 | 425.55 | 0.00 | 0.00 | 0.00 |
December | 534.03 | 421.49 | 112.54 | 1031.46 | 537.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 328.20 | 194.20 | 134.00 | 765.29 | 277.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.31 | 15.53 | 112.54 | 507.42 | 64.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 574.66 | 457.67 | 155.09 | 1164.88 | 537.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.15 | 107.95 | 65.20 | 317.30 | 363.72 | 0.00 | 0.00 | 0.00 |
February | 140.06 | 67.95 | 72.10 | 200.43 | 347.03 | 0.00 | 0.00 | 0.00 |
March | 184.77 | 88.05 | 96.72 | 312.59 | 304.85 | 0.00 | 0.00 | 0.00 |
April | 282.59 | 160.72 | 121.87 | 644.19 | 177.98 | 0.00 | 0.00 | 0.00 |
May | 283.95 | 158.69 | 125.26 | 700.23 | 129.28 | 0.00 | 0.00 | 0.00 |
June | 300.86 | 176.43 | 124.44 | 867.13 | 59.74 | 0.00 | 0.00 | 0.00 |
July | 219.36 | 102.02 | 117.33 | 656.20 | 45.91 | 0.00 | 0.00 | 0.00 |
August | 209.75 | 105.19 | 104.56 | 620.75 | 59.89 | 0.00 | 0.00 | 0.00 |
September | 182.73 | 76.66 | 106.07 | 508.57 | 80.37 | 0.00 | 0.00 | 0.00 |
October | 187.71 | 107.50 | 80.21 | 399.70 | 232.69 | 0.00 | 0.00 | 0.00 |
November | 172.11 | 103.84 | 68.27 | 307.90 | 338.37 | 0.00 | 0.00 | 0.00 |
December | 138.80 | 79.00 | 59.80 | 222.21 | 434.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.56 | 111.32 | 95.23 | 480.94 | 214.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.80 | 67.95 | 59.80 | 200.43 | 45.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.86 | 176.43 | 125.26 | 867.13 | 434.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442226E+09 | 0.277955E+09 | 0.164272E+09 | 0.712634E+09 | 0.890557E+09 |
February | 0.395172E+09 | 0.226967E+09 | 0.168205E+09 | 0.572586E+09 | 0.791301E+09 |
March | 0.542426E+09 | 0.278030E+09 | 0.264396E+09 | 0.902823E+09 | 0.767896E+09 |
April | 0.747087E+09 | 0.443554E+09 | 0.303533E+09 | 0.166779E+10 | 0.417162E+09 |
May | 0.801856E+09 | 0.474276E+09 | 0.327580E+09 | 0.194629E+10 | 0.306591E+09 |
June | 0.807683E+09 | 0.500474E+09 | 0.307209E+09 | 0.232656E+10 | 0.139176E+09 |
July | 0.706360E+09 | 0.397421E+09 | 0.308939E+09 | 0.205366E+10 | 0.114476E+09 |
August | 0.670435E+09 | 0.381745E+09 | 0.288689E+09 | 0.191615E+10 | 0.153855E+09 |
September | 0.532368E+09 | 0.255886E+09 | 0.276482E+09 | 0.144162E+10 | 0.196572E+09 |
October | 0.552102E+09 | 0.335163E+09 | 0.216938E+09 | 0.114280E+10 | 0.578880E+09 |
November | 0.412683E+09 | 0.247754E+09 | 0.164930E+09 | 0.652293E+09 | 0.818032E+09 |
December | 0.390827E+09 | 0.236975E+09 | 0.153852E+09 | 0.546888E+09 | 0.107168E+10 |
Annual Sum or Average | 0.700122E+10 | 0.405620E+10 | 0.294502E+10 | 0.158821E+11 | 0.624618E+10 |
Minimum of Months | 0.390827E+09 | 0.226967E+09 | 0.153852E+09 | 0.546888E+09 | 0.114476E+09 |
Maximum of Months | 0.807683E+09 | 0.500474E+09 | 0.327580E+09 | 0.232656E+10 | 0.107168E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153917E+10 | 0.122582E+10 | 0.313356E+09 | 0.312002E+10 | 0.121653E+10 |
February | 0.877351E+09 | 0.587921E+09 | 0.289430E+09 | 0.155877E+10 | 0.107354E+10 |
March | 0.820077E+09 | 0.423076E+09 | 0.397001E+09 | 0.154210E+10 | 0.111045E+10 |
April | 0.714307E+09 | 0.312310E+09 | 0.401997E+09 | 0.176334E+10 | 0.638866E+09 |
May | 0.491686E+09 | 0.101806E+09 | 0.389880E+09 | 0.135906E+10 | 0.478364E+09 |
June | 0.397378E+09 | 40251097.26 | 0.357127E+09 | 0.154516E+10 | 0.215361E+09 |
July | 0.416454E+09 | 50109079.80 | 0.366344E+09 | 0.154723E+10 | 0.172204E+09 |
August | 0.522978E+09 | 0.163366E+09 | 0.359612E+09 | 0.179879E+10 | 0.225056E+09 |
September | 0.705956E+09 | 0.308658E+09 | 0.397298E+09 | 0.203382E+10 | 0.286660E+09 |
October | 0.114801E+10 | 0.796769E+09 | 0.351246E+09 | 0.255409E+10 | 0.805047E+09 |
November | 0.128654E+10 | 0.985367E+09 | 0.301172E+09 | 0.254915E+10 | 0.110303E+10 |
December | 0.143035E+10 | 0.112893E+10 | 0.301422E+09 | 0.276266E+10 | 0.143996E+10 |
Annual Sum or Average | 0.103503E+11 | 0.612438E+10 | 0.422589E+10 | 0.241342E+11 | 0.876507E+10 |
Minimum of Months | 0.397378E+09 | 40251097.26 | 0.289430E+09 | 0.135906E+10 | 0.172204E+09 |
Maximum of Months | 0.153917E+10 | 0.122582E+10 | 0.401997E+09 | 0.312002E+10 | 0.143996E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.463765E+09 | 0.289132E+09 | 0.174634E+09 | 0.849866E+09 | 0.974175E+09 |
February | 0.338831E+09 | 0.164396E+09 | 0.174435E+09 | 0.484869E+09 | 0.839529E+09 |
March | 0.494882E+09 | 0.235828E+09 | 0.259054E+09 | 0.837236E+09 | 0.816503E+09 |
April | 0.732467E+09 | 0.416586E+09 | 0.315881E+09 | 0.166974E+10 | 0.461312E+09 |
May | 0.760536E+09 | 0.425044E+09 | 0.335492E+09 | 0.187549E+10 | 0.346251E+09 |
June | 0.779838E+09 | 0.457297E+09 | 0.322541E+09 | 0.224760E+10 | 0.154847E+09 |
July | 0.587522E+09 | 0.273258E+09 | 0.314263E+09 | 0.175755E+10 | 0.122968E+09 |
August | 0.561804E+09 | 0.281742E+09 | 0.280062E+09 | 0.166263E+10 | 0.160417E+09 |
September | 0.473636E+09 | 0.198694E+09 | 0.274942E+09 | 0.131822E+10 | 0.208332E+09 |
October | 0.502757E+09 | 0.287935E+09 | 0.214822E+09 | 0.107056E+10 | 0.623231E+09 |
November | 0.446118E+09 | 0.269165E+09 | 0.176953E+09 | 0.798073E+09 | 0.877060E+09 |
December | 0.371775E+09 | 0.211595E+09 | 0.160180E+09 | 0.595169E+09 | 0.116411E+10 |
Annual Sum or Average | 0.651393E+10 | 0.351067E+10 | 0.300326E+10 | 0.151670E+11 | 0.674874E+10 |
Minimum of Months | 0.338831E+09 | 0.164396E+09 | 0.160180E+09 | 0.484869E+09 | 0.122968E+09 |
Maximum of Months | 0.779838E+09 | 0.457297E+09 | 0.335492E+09 | 0.224760E+10 | 0.116411E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1708.23 | 1110.38 | 912.92 | 669.39 | 243.53 | 0.00 | 0.00 |
February | 1037.71 | 1074.14 | 666.07 | 404.80 | 261.27 | 0.00 | 0.00 |
March | 1180.30 | 961.03 | 693.47 | 349.81 | 343.66 | 0.00 | 0.00 |
April | 1928.95 | 546.41 | 846.40 | 452.33 | 394.06 | 0.00 | 0.00 |
May | 1907.23 | 395.27 | 766.91 | 373.78 | 393.13 | 0.00 | 0.00 |
June | 2348.11 | 183.78 | 765.78 | 385.04 | 380.74 | 0.00 | 0.00 |
July | 1994.03 | 146.37 | 638.57 | 269.11 | 369.45 | 0.00 | 0.00 |
August | 2001.01 | 194.62 | 655.32 | 308.71 | 346.61 | 0.00 | 0.00 |
September | 1841.20 | 258.60 | 660.48 | 294.46 | 366.02 | 0.00 | 0.00 |
October | 1751.95 | 721.37 | 822.46 | 530.12 | 292.34 | 0.00 | 0.00 |
November | 1501.76 | 1038.26 | 827.68 | 579.59 | 248.09 | 0.00 | 0.00 |
December | 1403.07 | 1317.58 | 818.75 | 588.97 | 229.78 | 0.00 | 0.00 |
Annual Sum or Average | 1720.48 | 660.64 | 756.77 | 434.15 | 322.62 | 0.00 | 0.00 |
Minimum of Months | 1037.71 | 146.37 | 638.57 | 269.11 | 229.78 | 0.00 | 0.00 |
Maximum of Months | 2348.11 | 1317.58 | 912.92 | 669.39 | 394.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457531E+10 | 0.297405E+10 | 0.244516E+10 | 0.179290E+10 | 0.652262E+09 | 0.00 | 0.00 |
February | 0.251043E+10 | 0.259857E+10 | 0.161135E+10 | 0.979284E+09 | 0.632069E+09 | 0.00 | 0.00 |
March | 0.316133E+10 | 0.257401E+10 | 0.185738E+10 | 0.936934E+09 | 0.920451E+09 | 0.00 | 0.00 |
April | 0.499983E+10 | 0.141630E+10 | 0.219386E+10 | 0.117245E+10 | 0.102141E+10 | 0.00 | 0.00 |
May | 0.510833E+10 | 0.105869E+10 | 0.205408E+10 | 0.100113E+10 | 0.105295E+10 | 0.00 | 0.00 |
June | 0.608629E+10 | 0.476366E+09 | 0.198490E+10 | 0.998022E+09 | 0.986877E+09 | 0.00 | 0.00 |
July | 0.534081E+10 | 0.392026E+09 | 0.171033E+10 | 0.720789E+09 | 0.989546E+09 | 0.00 | 0.00 |
August | 0.535950E+10 | 0.521257E+09 | 0.175522E+10 | 0.826854E+09 | 0.928363E+09 | 0.00 | 0.00 |
September | 0.477238E+10 | 0.670288E+09 | 0.171196E+10 | 0.763238E+09 | 0.948723E+09 | 0.00 | 0.00 |
October | 0.469242E+10 | 0.193212E+10 | 0.220287E+10 | 0.141987E+10 | 0.783007E+09 | 0.00 | 0.00 |
November | 0.389255E+10 | 0.269116E+10 | 0.214534E+10 | 0.150229E+10 | 0.643055E+09 | 0.00 | 0.00 |
December | 0.375798E+10 | 0.352902E+10 | 0.219295E+10 | 0.157750E+10 | 0.615454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.542572E+11 | 0.208339E+11 | 0.238654E+11 | 0.136912E+11 | 0.101742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251043E+10 | 0.392026E+09 | 0.161135E+10 | 0.720789E+09 | 0.615454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.608629E+10 | 0.352902E+10 | 0.244516E+10 | 0.179290E+10 | 0.105295E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.637953E+10 | -0.622521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154323845.0 | 81.21 | 0.00 | 0.00 |
February | 0.577370E+10 | -0.563432E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -139378762.5 | 81.21 | 0.00 | 0.00 |
March | 0.644818E+10 | -0.629389E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154290394.0 | 81.21 | 0.00 | 0.00 |
April | 0.619278E+10 | -0.604350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149284171.3 | 81.21 | 0.00 | 0.00 |
May | 0.641450E+10 | -0.626021E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154288293.0 | 81.21 | 0.00 | 0.00 |
June | 0.623605E+10 | -0.608659E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149467476.3 | 81.21 | 0.00 | 0.00 |
July | 0.637149E+10 | -0.621712E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154367425.9 | 81.21 | 0.00 | 0.00 |
August | 0.644958E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154340487.8 | 81.21 | 0.00 | 0.00 |
September | 0.619414E+10 | -0.604484E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149293516.2 | 81.21 | 0.00 | 0.00 |
October | 0.637810E+10 | -0.622385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154246832.8 | 81.21 | 0.00 | 0.00 |
November | 0.617393E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149297193.9 | 81.21 | 0.00 | 0.00 |
December | 0.637149E+10 | -0.621712E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154361831.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753835E+11 | -0.735665E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181694E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577370E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -154367425.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644958E+10 | -0.563432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -139378762.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.204790E+11 | -0.196400E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839013073.6 | 58.99 | 0.00 | 0.00 |
February | 0.183522E+11 | -0.175943E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -757901580.5 | 58.99 | 0.00 | 0.00 |
March | 0.195396E+11 | -0.187008E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838857625.9 | 58.99 | 0.00 | 0.00 |
April | 0.173344E+11 | -0.165230E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811396930.8 | 58.99 | 0.00 | 0.00 |
May | 0.163443E+11 | -0.155057E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838619454.5 | 58.98 | 0.00 | 0.00 |
June | 0.146097E+11 | -0.137965E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -813120976.6 | 58.99 | 0.00 | 0.00 |
July | 0.142901E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839272150.2 | 58.98 | 0.00 | 0.00 |
August | 0.146579E+11 | -0.138187E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839187552.6 | 58.99 | 0.00 | 0.00 |
September | 0.150308E+11 | -0.142192E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811571124.4 | 58.99 | 0.00 | 0.00 |
October | 0.169679E+11 | -0.161296E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838300171.6 | 58.99 | 0.00 | 0.00 |
November | 0.179723E+11 | -0.171608E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811447806.7 | 58.98 | 0.00 | 0.00 |
December | 0.198286E+11 | -0.189891E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839548129.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.205407E+12 | -0.195529E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.987824E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.142901E+11 | -0.196400E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -839548129.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.204790E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -757901580.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.858291E+10 | 50047.74 | 01-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.970164E+10 | 38050.47 | 01-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808821E+10 | 50361.07 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463108E+09 | 72516.44 | 08-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198459E+09 | 78282.97 | 29-MAY-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140314E+09 | 56837.15 | 13-JUN-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69844193.95 | 75428.46 | 02-JUL-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43828717.70 | 43392.74 | 25-AUG-03:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67398915.53 | 49662.32 | 16-SEP-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195555E+10 | 81123.07 | 17-OCT-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608373E+10 | 49089.89 | 23-NOV-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174364E+11 | 53799.00 | 06-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 43828717.70 | 38050.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174364E+11 | 81123.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143840E+11 | 0.141843E+11 | 123987.71 | 08-JAN-04:01 | 95626.46 | 0.00 |
February | 0.00 | 0.00 | 0.107246E+10 | 0.896674E+09 | 21068.19 | 18-FEB-13:53 | 15975.53 | 0.00 |
March | 0.00 | 0.00 | 0.159181E+11 | 0.151135E+11 | 123987.71 | 17-MAR-03:01 | 94882.23 | 0.00 |
April | 0.00 | 0.00 | 0.635834E+11 | 0.632351E+11 | 123987.71 | 15-APR-03:26 | 115822.77 | 0.00 |
May | 0.00 | 0.00 | 0.868506E+11 | 0.867647E+11 | 123987.71 | 06-MAY-03:01 | 123987.71 | 0.00 |
June | 0.00 | 0.00 | 0.122543E+12 | 0.121569E+12 | 123987.71 | 02-JUN-03:24 | 123156.12 | 0.00 |
July | 0.00 | 0.00 | 0.140344E+12 | 0.117537E+12 | 137758.50 | 14-JUL-03:01 | 58178.11 | 0.00 |
August | 0.00 | 0.00 | 0.136095E+12 | 0.113442E+12 | 133007.05 | 01-AUG-03:01 | 79556.34 | 0.00 |
September | 0.00 | 0.00 | 0.115890E+12 | 0.941681E+11 | 136210.37 | 04-SEP-03:01 | 56232.54 | 0.00 |
October | 0.00 | 0.00 | 0.535030E+11 | 0.485621E+11 | 133125.22 | 03-OCT-03:01 | 66524.42 | 0.00 |
November | 0.00 | 0.00 | 0.151551E+11 | 0.138672E+11 | 126618.85 | 13-NOV-04:01 | 53952.04 | 0.00 |
December | 0.00 | 0.00 | 0.602873E+10 | 0.599654E+10 | 35895.77 | 22-DEC-14:00 | 35895.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.771367E+12 | 0.695336E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.107246E+10 | 0.896674E+09 | 21068.19 | 15975.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140344E+12 | 0.121569E+12 | 137758.50 | 123987.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.773394E+10 | 0.750490E+10 | 41432.10 | 06-JAN-04:01 | 33903.51 | 0.00 |
February | 0.00 | 0.00 | 0.920824E+09 | 0.737773E+09 | 41432.10 | 02-FEB-04:01 | 30874.46 | 0.00 |
March | 0.00 | 0.00 | 0.892014E+10 | 0.807291E+10 | 41432.10 | 07-MAR-04:21 | 23157.06 | 0.00 |
April | 0.00 | 0.00 | 0.313920E+11 | 0.265051E+11 | 41432.10 | 02-APR-03:31 | 41432.10 | 0.00 |
May | 0.00 | 0.00 | 0.405252E+11 | 0.339457E+11 | 41432.10 | 04-MAY-03:01 | 41432.10 | 0.00 |
June | 0.00 | 0.00 | 0.507012E+11 | 0.418634E+11 | 41432.10 | 03-JUN-01:22 | 41432.10 | 0.00 |
July | 0.00 | 0.00 | 0.585105E+11 | 0.434957E+11 | 45851.08 | 14-JUL-03:01 | 18476.49 | 0.00 |
August | 0.00 | 0.00 | 0.572436E+11 | 0.420565E+11 | 45190.83 | 01-AUG-03:01 | 24504.62 | 0.00 |
September | 0.00 | 0.00 | 0.511947E+11 | 0.371034E+11 | 45272.61 | 02-SEP-00:11 | 27319.68 | 0.00 |
October | 0.00 | 0.00 | 0.254044E+11 | 0.207619E+11 | 44333.95 | 03-OCT-03:01 | 20584.45 | 0.00 |
November | 0.00 | 0.00 | 0.832613E+10 | 0.732347E+10 | 41432.10 | 03-NOV-03:01 | 24557.95 | 0.00 |
December | 0.00 | 0.00 | 0.366891E+10 | 0.361844E+10 | 41432.10 | 15-DEC-04:01 | 35687.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344542E+12 | 0.272989E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.920824E+09 | 0.737773E+09 | 41432.10 | 18476.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.585105E+11 | 0.434957E+11 | 45851.08 | 41432.10 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7795.09 | 14839.13 | 19-JAN-07:45 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7735.61 | 14805.94 | 02-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7445.12 | 14405.38 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6838.76 | 13424.33 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6254.53 | 12364.48 | 01-MAY-18:42 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5790.05 | 11243.75 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5490.17 | 10507.76 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5626.58 | 10816.47 | 31-AUG-18:22 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5952.95 | 11668.52 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6487.55 | 12883.26 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7084.30 | 13918.03 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 7552.91 | 14609.51 | 28-DEC-19:17 |
Annual Sum or Average | 0.00 | 6665.18 | ||||
Minimum of Months | 0.00 | 0.00 | 5490.17 | 10507.76 | ||
Maximum of Months | 0.00 | 0.00 | 7795.09 | 14839.13 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.545673E+10 | 0.65 | 2203.40 | 01-JAN-00:01 | 0.70 |
February | 0.489751E+10 | 0.64 | 2203.40 | 01-FEB-00:05 | 0.70 |
March | 0.543395E+10 | 0.64 | 2203.40 | 01-MAR-00:03 | 0.70 |
April | 0.544639E+10 | 0.67 | 2203.40 | 01-APR-00:50 | 0.70 |
May | 0.563190E+10 | 0.67 | 2203.40 | 01-MAY-00:12 | 0.70 |
June | 0.544232E+10 | 0.66 | 2203.40 | 01-JUN-00:09 | 0.70 |
July | 0.562490E+10 | 0.66 | 2203.40 | 01-JUL-00:08 | 0.70 |
August | 0.562450E+10 | 0.66 | 2203.40 | 01-AUG-00:08 | 0.69 |
September | 0.544232E+10 | 0.66 | 2203.40 | 01-SEP-00:09 | 0.70 |
October | 0.561736E+10 | 0.66 | 2203.40 | 01-OCT-00:09 | 0.70 |
November | 0.535322E+10 | 0.65 | 2203.40 | 01-NOV-00:12 | 0.70 |
December | 0.536287E+10 | 0.64 | 2203.40 | 01-DEC-00:02 | 0.70 |
Annual Sum or Average | 0.653340E+11 | 0.66 | |||
Minimum of Months | 0.489751E+10 | 0.64 | 2203.40 | 0.69 | |
Maximum of Months | 0.563190E+10 | 0.67 | 2203.40 | 0.70 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212098E+11 | 1.41 | 9502.15 | 01-JAN-08:15 | 1.70 |
February | 0.191563E+11 | 1.41 | 9502.15 | 02-FEB-08:58 | 1.70 |
March | 0.212115E+11 | 1.41 | 9502.15 | 01-MAR-05:10 | 1.69 |
April | 0.206051E+11 | 1.45 | 9502.15 | 01-APR-23:00 | 1.70 |
May | 0.213596E+11 | 1.45 | 9502.15 | 01-MAY-08:06 | 1.70 |
June | 0.206525E+11 | 1.45 | 9502.15 | 04-JUN-04:03 | 1.69 |
July | 0.213813E+11 | 1.45 | 9502.15 | 03-JUL-04:20 | 1.70 |
August | 0.213765E+11 | 1.45 | 9502.15 | 04-AUG-07:00 | 1.67 |
September | 0.207017E+11 | 1.44 | 9502.15 | 03-SEP-05:50 | 1.66 |
October | 0.212889E+11 | 1.44 | 9502.15 | 07-OCT-17:37 | 1.69 |
November | 0.205404E+11 | 1.42 | 9502.15 | 01-NOV-04:05 | 1.68 |
December | 0.212088E+11 | 1.42 | 9502.15 | 01-DEC-17:33 | 1.70 |
Annual Sum or Average | 0.250692E+12 | 1.43 | |||
Minimum of Months | 0.191563E+11 | 1.41 | 9502.15 | 1.66 | |
Maximum of Months | 0.213813E+11 | 1.45 | 9502.15 | 1.70 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.469676E+10 | 0.91 | 2082.83 | 02-JAN-17:22 | 0.99 |
February | 0.424181E+10 | 0.90 | 2082.83 | 09-FEB-18:33 | 0.99 |
March | 0.469936E+10 | 0.90 | 2082.83 | 02-MAR-16:15 | 0.99 |
April | 0.462059E+10 | 0.93 | 2082.83 | 03-APR-07:30 | 0.99 |
May | 0.480243E+10 | 0.92 | 2082.83 | 01-MAY-23:20 | 0.99 |
June | 0.468179E+10 | 0.90 | 2082.83 | 02-JUN-21:45 | 0.98 |
July | 0.486624E+10 | 0.90 | 2082.83 | 04-JUL-06:52 | 0.99 |
August | 0.486408E+10 | 0.90 | 2082.83 | 02-AUG-23:06 | 0.98 |
September | 0.470789E+10 | 0.91 | 2082.83 | 04-SEP-08:62 | 0.97 |
October | 0.477353E+10 | 0.92 | 2082.83 | 03-OCT-23:30 | 0.98 |
November | 0.456462E+10 | 0.91 | 2082.83 | 02-NOV-09:08 | 0.98 |
December | 0.468823E+10 | 0.89 | 2082.83 | 02-DEC-15:23 | 0.99 |
Annual Sum or Average | 0.562073E+11 | 0.91 | |||
Minimum of Months | 0.424181E+10 | 0.89 | 2082.83 | 0.97 | |
Maximum of Months | 0.486624E+10 | 0.93 | 2082.83 | 0.99 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 50.13 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 50.63 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.71 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 53.75 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.46 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 54.34 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 54.89 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.40 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.68 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.63 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.08 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 50.35 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.13 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.89 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 50.13 | 59.94 | 7795.09 | 14839.13 | 19-JAN-07:45 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 50.63 | 59.39 | 7735.61 | 14805.94 | 02-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.71 | 59.71 | 7445.12 | 14405.38 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.60 | 51.60 | 6838.76 | 13424.33 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.28 | 52.28 | 6254.53 | 12364.48 | 01-MAY-18:42 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.18 | 53.18 | 5790.05 | 11243.75 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.76 | 53.76 | 5490.17 | 10507.76 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.98 | 52.98 | 5626.58 | 10816.47 | 31-AUG-18:22 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.54 | 53.54 | 5952.95 | 11668.52 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.15 | 51.15 | 6487.55 | 12883.26 | 31-OCT-18:10 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.89 | 51.89 | 7084.30 | 13918.03 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 50.35 | 58.23 | 7552.91 | 14609.51 | 28-DEC-19:17 |
Annual Sum or Average | 0.00 | 6665.18 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.13 | 51.15 | 5490.17 | 10507.76 | ||
Maximum of Months | 0.00 | 0.00 | 53.76 | 59.94 | 7795.09 | 14839.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.261825E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.195385E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.266668E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.420008E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.508282E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.639542E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.682390E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.669241E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.586967E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.391861E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.257090E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.233112E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.511237E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.195385E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.682390E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.724009E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.455095E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.757589E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144306E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.176257E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.214953E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233229E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.229007E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204510E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.127274E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.724644E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.590694E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165474E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.455095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.233229E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.212098E+11 | 0.143840E+11 | 0.858291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191563E+11 | 0.107246E+10 | 0.970164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212115E+11 | 0.159181E+11 | 0.808821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206051E+11 | 0.635834E+11 | 0.463108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213596E+11 | 0.868506E+11 | 0.198459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206525E+11 | 0.122543E+12 | 0.140314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213813E+11 | 0.140344E+12 | 69844193.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213765E+11 | 0.136095E+12 | 43828717.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207017E+11 | 0.115890E+12 | 67398915.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212889E+11 | 0.535030E+11 | 0.195555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205404E+11 | 0.151551E+11 | 0.608373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212088E+11 | 0.602873E+10 | 0.174364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250692E+12 | 0.771367E+12 | 0.528313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191563E+11 | 0.107246E+10 | 43828717.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213813E+11 | 0.140344E+12 | 0.174364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.469676E+10 | 0.773394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424181E+10 | 0.920824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469936E+10 | 0.892014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.462059E+10 | 0.313920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.480243E+10 | 0.405252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468179E+10 | 0.507012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.486624E+10 | 0.585105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.486408E+10 | 0.572436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.470789E+10 | 0.511947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477353E+10 | 0.254044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456462E+10 | 0.832613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468823E+10 | 0.366891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.562073E+11 | 0.344542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.424181E+10 | 0.920824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486624E+10 | 0.585105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.212098E+11 | 0.00 | 0.00 | 0.00 | 0.497268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191563E+11 | 0.00 | 0.00 | 0.00 | 0.382119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212115E+11 | 0.00 | 0.00 | 0.00 | 0.545527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206051E+11 | 0.00 | 0.00 | 0.00 | 0.213957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213596E+11 | 0.00 | 0.00 | 0.00 | 0.294686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206525E+11 | 0.00 | 0.00 | 0.00 | 0.433016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213813E+11 | 0.00 | 0.00 | 0.00 | 0.468577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213765E+11 | 0.00 | 0.00 | 0.00 | 0.455476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207017E+11 | 0.00 | 0.00 | 0.00 | 0.379950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212889E+11 | 0.00 | 0.00 | 0.00 | 0.178972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205404E+11 | 0.00 | 0.00 | 0.00 | 0.516860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212088E+11 | 0.00 | 0.00 | 0.00 | 0.210237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250692E+12 | 0.00 | 0.00 | 0.00 | 0.260544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191563E+11 | 0.00 | 0.00 | 0.00 | 0.382119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213813E+11 | 0.00 | 0.00 | 0.00 | 0.468577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.469676E+10 | 0.00 | 0.00 | 0.00 | 0.254332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424181E+10 | 0.00 | 0.00 | 0.00 | 0.309145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469936E+10 | 0.00 | 0.00 | 0.00 | 0.287653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.462059E+10 | 0.00 | 0.00 | 0.00 | 0.980997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.480243E+10 | 0.00 | 0.00 | 0.00 | 0.128233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468179E+10 | 0.00 | 0.00 | 0.00 | 0.168135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.486624E+10 | 0.00 | 0.00 | 0.00 | 0.184566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.486408E+10 | 0.00 | 0.00 | 0.00 | 0.180366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.470789E+10 | 0.00 | 0.00 | 0.00 | 0.157431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477353E+10 | 0.00 | 0.00 | 0.00 | 0.795387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456462E+10 | 0.00 | 0.00 | 0.00 | 0.268182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468823E+10 | 0.00 | 0.00 | 0.00 | 0.121871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.562073E+11 | 0.00 | 0.00 | 0.00 | 0.109266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.424181E+10 | 0.00 | 0.00 | 0.00 | 0.309145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486624E+10 | 0.00 | 0.00 | 0.00 | 0.184566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333379E+11 | 0.134447E+09 | 0.00 | 82545867.11 | 0.00 | 0.297055E+09 | 0.258083E+11 | 0.00 | 7.87 |
February | 0.434616E+11 | 0.00 | 0.00 | 26622307.46 | 0.00 | 18116149.26 | 0.198508E+11 | 0.00 | 7.38 |
March | 0.316025E+11 | 0.424123E+09 | 0.00 | 73228416.71 | 0.00 | 96701254.86 | 0.245140E+11 | 0.00 | 7.85 |
April | 0.748523E+10 | 0.938698E+10 | 720632.98 | 76483586.03 | 3779254.44 | 13123145.97 | 0.115363E+11 | 148466.21 | 7.68 |
May | 0.258238E+10 | 0.184864E+11 | 1832874.17 | 50351182.50 | 7919700.43 | 9884757.12 | 0.756905E+10 | 649324.71 | 7.52 |
June | 0.428422E+09 | 0.413656E+11 | 4968793.72 | 16738027.06 | 0.144828E+09 | 2430725.43 | 0.219316E+10 | 1012001.49 | 7.43 |
July | 0.333405E+09 | 0.547247E+11 | 2247608.77 | 8106566.66 | 0.334835E+09 | 3696298.78 | 0.950878E+09 | 246849.69 | 7.36 |
August | 0.431074E+09 | 0.507566E+11 | 3404600.76 | 9815962.58 | 0.262136E+09 | 35813.51 | 0.136084E+10 | 375943.13 | 7.50 |
September | 0.726208E+09 | 0.374366E+11 | 10279813.60 | 13068507.12 | 0.152039E+09 | 208184.81 | 0.268732E+10 | 440398.18 | 7.66 |
October | 0.128687E+11 | 0.100135E+11 | 725182.45 | 74628576.26 | 32009824.92 | 8585410.07 | 0.198520E+11 | 46196.37 | 7.95 |
November | 0.276587E+11 | 0.427060E+09 | 0.00 | 74078337.96 | 0.00 | 16723337.03 | 0.283001E+11 | 0.00 | 7.86 |
December | 0.527289E+11 | 8571011.83 | 0.00 | 48930705.77 | 0.00 | 58612055.00 | 0.209229E+11 | 0.00 | 7.57 |
Annual Sum or Average | 0.213645E+12 | 0.223165E+12 | 24179506.46 | 0.554598E+09 | 0.937547E+09 | 0.525172E+09 | 0.165546E+12 | 2919179.77 | 7.64 |
Minimum of Months | 0.333405E+09 | 0.00 | 0.00 | 8106566.66 | 0.00 | 35813.51 | 0.950878E+09 | 0.00 | 7.36 |
Maximum of Months | 0.527289E+11 | 0.547247E+11 | 10279813.60 | 82545867.11 | 0.334835E+09 | 0.297055E+09 | 0.283001E+11 | 1012001.49 | 7.95 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.142096E+09 | 0.00 | 0.00 | 0.447545E+11 | 0.00 | 9.47 |
February | 0.00 | 0.00 | 0.00 | 0.111106E+09 | 0.00 | 0.00 | 0.438574E+11 | 0.00 | 8.31 |
March | 0.00 | 0.00 | 0.00 | 0.142221E+09 | 0.00 | 0.00 | 0.431269E+11 | 0.00 | 9.36 |
April | 0.00 | 309272.95 | 0.00 | 0.185041E+09 | 0.00 | 0.00 | 0.238694E+11 | 0.00 | 7.13 |
May | 85096.66 | 0.00 | 0.00 | 0.192381E+09 | 0.00 | 0.00 | 0.174674E+11 | 0.00 | 5.61 |
June | 0.00 | 81509486.72 | 0.00 | 0.191148E+09 | 0.00 | 0.00 | 0.796130E+10 | 0.00 | 3.49 |
July | 0.00 | 0.198022E+10 | 0.00 | 84990272.74 | 0.00 | 0.00 | 0.332365E+10 | 0.00 | 3.69 |
August | 0.00 | 0.148374E+10 | 0.00 | 95026500.47 | 0.00 | 0.00 | 0.403749E+10 | 0.00 | 4.49 |
September | 0.00 | 0.125068E+10 | 0.00 | 0.106598E+09 | 0.00 | 0.00 | 0.673012E+10 | 0.00 | 5.95 |
October | 0.00 | 0.106928E+09 | 0.00 | 0.148966E+09 | 0.00 | 0.00 | 0.307203E+11 | 0.00 | 8.68 |
November | 0.00 | 0.00 | 0.00 | 0.134581E+09 | 0.00 | 0.00 | 0.430831E+11 | 0.00 | 9.71 |
December | 0.00 | 0.00 | 0.00 | 0.140631E+09 | 0.00 | 0.00 | 0.485550E+11 | 0.00 | 8.36 |
Annual Sum or Average | 85096.66 | 0.490339E+10 | 0.00 | 0.167479E+10 | 0.00 | 0.00 | 0.317486E+12 | 0.00 | 7.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 84990272.74 | 0.00 | 0.00 | 0.332365E+10 | 0.00 | 3.49 |
Maximum of Months | 85096.66 | 0.198022E+10 | 0.00 | 0.192381E+09 | 0.00 | 0.00 | 0.485550E+11 | 0.00 | 9.71 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:27:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.581013E+11 | 0.810017E+10 | 0.193045E+12 | 0.404647E+11 | 0.576337E+11 |
February | 0.655330E+11 | 0.909131E+10 | 0.200888E+12 | 0.367318E+11 | 0.268438E+11 |
March | 0.923322E+11 | 0.905640E+10 | 0.184368E+12 | 0.389126E+11 | 0.615201E+11 |
April | 0.124975E+12 | 0.457805E+10 | 0.118913E+12 | 0.184570E+11 | 0.156885E+12 |
May | 0.132402E+12 | 0.269779E+10 | 0.100045E+12 | 0.110624E+11 | 0.201685E+12 |
June | 0.137616E+12 | -371565669.6 | 0.290923E+11 | 0.342514E+10 | 0.266353E+12 |
July | 0.122750E+12 | -0.191819E+10 | -0.471584E+11 | 0.892609E+09 | 0.297492E+12 |
August | 0.104018E+12 | -0.179735E+10 | -0.416033E+11 | 0.207074E+10 | 0.290730E+12 |
September | 0.859621E+11 | -0.106478E+10 | -0.137287E+11 | 0.416002E+10 | 0.250266E+12 |
October | 0.769380E+11 | 0.422490E+10 | 0.117757E+12 | 0.275552E+11 | 0.132842E+12 |
November | 0.605771E+11 | 0.782693E+10 | 0.180242E+12 | 0.389199E+11 | 0.570521E+11 |
December | 0.450427E+11 | 0.960697E+10 | 0.235137E+12 | 0.410399E+11 | 0.435281E+11 |
Annual Sum or Average | 0.110625E+13 | 0.500306E+11 | 0.125700E+13 | 0.263692E+12 | 0.184283E+13 |
Minimum of Months | 0.450427E+11 | -0.191819E+10 | -0.471584E+11 | 0.892609E+09 | 0.268438E+11 |
Maximum of Months | 0.137616E+12 | 0.960697E+10 | 0.235137E+12 | 0.410399E+11 | 0.297492E+12 |