Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:28:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2245.38 | 4392.77 | 4392.77 |
Net Site Energy | 2245.38 | 4392.77 | 4392.77 |
Total Source Energy | 5493.36 | 10746.99 | 10746.99 |
Net Source Energy | 5493.36 | 10746.99 | 10746.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 409.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 52.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.40 | 285.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 66.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1468.73 | 776.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 409.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 52.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 306.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.40 | 285.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 409.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 52.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 306.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.40 | 285.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 66.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1549.45 | 600.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1031.79 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2873.37 | 1519.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1549.45 | 600.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1031.79 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2873.37 | 1519.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1468.731 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1468.731 | 100.00 |
Total On-Site and Utility Electric Sources | 1468.731 | 100.00 |
Total Electricity End Uses | 1468.731 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1193.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5656.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 12.0182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6242 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 12.0182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6242 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 11.3653 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-18:00 | 05-FEB-07:49 | - | - | - | - | - | - | - | - | - | - | 13-FEB-19:10 |
Heating | 0.00 | 77652.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40111.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 19067.80 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11361.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4285.11 | 14008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2390.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85361.93 | 105238.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 77652.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40111.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 17700.22 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11361.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4285.11 | 14008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 769.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 23.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1297.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 306.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 165.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 970.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.79 | 309.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 211.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4651.47 | 841.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 45.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2538.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 324.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1898.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.17 | 605.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 413.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9099.96 | 1647.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 45.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2538.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 324.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1898.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.17 | 605.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 413.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9099.96 | 1647.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.97 |
KITCHEN DIRECT AIR | 1.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.97 | 3.97 | 3.97 | 3.97 | 3.97 | 3.97 | 1.00 | 0.999906 | 3.97 |
PSZ-AC_2:2 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.00 | 1.000000 | 1.65 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.97 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.65 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.97 | 7393.71 |
PSZ-AC_2:2_ADDAQ FAN | 1.65 | 1763.97 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.97 | 3.97 | 3.97 | 3.97 | 98543.80 | 117548.94 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.65 | 1.65 | 1.65 | 1.65 | 40936.10 | 71378.99 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.97 | 1.98 | 3.97 | 98543.80 | 49271.90 | 98543.80 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.65 | 0.824248 | 1.65 | 40936.10 | 20468.05 | 40936.10 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 117548.94 |
PSZ-AC_2:2 HEATING COIL | 71378.99 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 12.018 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 76.946 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.624 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.704 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 4467.734 | 12.018 | 15.948 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4467.734 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1341.663 | 9.624 | 178.225 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1341.663 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 45401.98097 | 54482.37716 | 3.30665 | 3.96798 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 4396.71184 | 5276.05421 | 0.18861 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 4.60000 | 5.25715E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22248.16358 | 26697.79629 | 1.37375 | 1.64850 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 33.18900 | 1.65350E-002 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | 00:10:00 | 4.60000 | 5.25715E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 69589.64 | 3.96836 | 3.96836 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 56981.68 | 1.33138 | 1.33138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 39418.77 | 1.64850 | 1.64850 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64205.86 | 1.50017 | 1.50017 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.96798 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.64850 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.96798 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.96798 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.96798 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.96798 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.96836 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.96836 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99991 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.64850 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64850 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.64850 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64850 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.64850 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.64850 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.96836 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.64850 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.96836 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.96836 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7393.71098 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.96836 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.96836 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.96836 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.96836 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.96836 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.98418 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.96836 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 98543.80000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 49271.90248 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 98543.80000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 98543.80000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 117548.93614 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 117548.93614 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.64850 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.64850 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1763.96932 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.64850 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.64850 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.64850 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.64850 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.64850 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82425 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.64850 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40936.10000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20468.04850 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40936.10000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40936.10000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71378.99244 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 71378.99244 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 95723.2 | 10.39 | 10.26 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 39764.4 | 11.29 | 11.15 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 2.7511410094E-002 | 0.1125128713 | Pass | Pass | 3.7644336937E-002 | 0.1046001982 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2346715964 | 0.6475902122 | Pass | Pass | 0.1397761106 | 0.4898402238 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4531387797 | 0.4525087452 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1178.02 | 2.87 | 15.56 | 49.05 | 2265.98 | 3511.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 12.0182 | 371.75 | 4467.73 | LightsWired | LTG_SCH_DINING | 93.20 | 168.00 | 92.65 | 0.0000 | Y | 77.70 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6242 | 139.41 | 1341.66 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.21 |
Interior Lighting Total | 11.3653 | 511.15 | 5809.40 | 96.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 3334.35 | AstronomicalClock | - | 83.73 | 83.73 | 52.40 | |
Exterior Lighting Total | 3334.35 | 52.40 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 98543.80 | 69087.09 | 29456.71 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40936.10 | 28699.48 | 12236.62 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 95723.2 | 10.39 | 10.26 | ||||
PSZ-AC_2:2 COOLING COIL | 39764.4 | 11.29 | 11.15 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 117548.94 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 71378.99 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1110.54 | 3.97 | 7393.71 | 1863.17 | 1.00 | 1.17 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.65 | 1763.97 | 1070.05 | 1.00 | 1.35 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 45401.98 | 54482.38 | 146.56 | 3.307 | 3.968 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 23.98 | 0.01106 | 33.74 | 0.01654 | 1.331 | 0.00 |
KITCHEN | 22248.16 | 26697.80 | 191.51 | 1.374 | 1.648 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01031 | 33.19 | 0.01654 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4396.71 | 5276.05 | 14.19 | 0.189 | 1.331 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00768 | 4.60 | 0.00526 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | 00:10:00 | 19.00 | 25.64 | 0.00474 | 4.60 | 0.00526 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.97 | 3.97 | 1.33 | 1.33 | 3.9684 | 3.9680 | 3.9684 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.65 | 1.65 | 1.50 | 1.50 | 1.6485 | 1.6485 | 1.6485 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 98543.800 | 69087.087 | 3.968360 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 98543.80 | 57999.31 | 3.968360 | 27.31 | 20.91 | 0.01289603 | 11.29 | 11.29 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 33.5498 | 23.98 | 0.01105741 | 59.2926 | 45384.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 117548.936 | 117548.936 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | 117548.94 | 117548.94 | 3.968359 | 15.50 | 11.57 | 0.00686964 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 33.5498 | 21.00 | 0.00768377 | 49.6579 | 4389.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 40936.100 | 28699.481 | 1.648500 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 40936.10 | 21695.11 | 1.648500 | 33.53 | 24.86 | 0.01625089 | 11.94 | 11.73 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 91.0021 | 25.99 | 0.01032534 | 49.1941 | 22248.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 71378.992 | 71378.992 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 71378.99 | 71378.99 | 1.648497 | 4.19 | 4.19 | 0.00521070 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 91.0023 | 25.64 | 0.00474092 | 23.2651 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 98543.800 | 69087.087 | 3.968360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.8131 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.968359 | 4.77459821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 98543.80 | 57999.31 | 1.0000 | 4.77459939 | 3.968360 | 27.31 | 20.91 | 0.01289603 | 60347.0 | 11.29 | 11.29 | 0.00850000 | 32785.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98543.80 | 33.90 | 0.01653638 | 25.13 | 1.33137743 | 33.5498 | 23.98 | 0.01105741 | 23.98 | 0.01105741 | 59.2926 | 45384.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 117548.936 | 117548.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.968359 | 4.77459821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | Sensible | 117548.94 | 117548.94 | 1.0000 | 4.77459821 | 3.968359 | 15.50 | 11.57 | 0.00686964 | 32951.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 117548.94 | 4.60 | 0.00525715 | 4.60 | 1.33137743 | 33.5498 | 21.00 | 0.00768377 | 21.00 | 0.00768377 | 49.6579 | 4389.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40936.100 | 28699.481 | 1.648500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1035.0496 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.648497 | 1.98341657 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 40936.10 | 21695.11 | 1.0000 | 1.98342063 | 1.648500 | 33.53 | 24.86 | 0.01625089 | 75352.5 | 11.94 | 11.73 | 0.00850000 | 33445.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40936.10 | 33.90 | 0.01653638 | 25.13 | 1.50017041 | 91.0021 | 25.95 | 0.01032534 | 25.99 | 0.01032534 | 49.1941 | 22248.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71378.992 | 71378.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.648497 | 1.98341657 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 71378.99 | 71378.99 | 1.0000 | 1.98341657 | 1.648497 | 4.19 | 4.19 | 0.00521070 | 17278.6 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71378.99 | 4.60 | 0.00525715 | 4.60 | 1.50017041 | 91.0023 | 0.00 | 0.00474092 | 25.64 | 0.00474092 | 23.2651 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 1.33 | 3.97 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 1.50 | 1.65 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5981.83 | 4220.17 | 3376.67 |
KITCHEN | 6307.50 | 6381.83 | 5647.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6311.67 | 6477.50 | 5656.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1463.33 | 0.00 | 1193.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1463.33 | 0.00 | 1193.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 5.127 | 0.909 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.293 | 0.045 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.094 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.373 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 41515945.15 | 0.00 | 41515945.15 | 7381991.54 | 48897936.69 | 41986318.57 | 1459.98 | 5631.33 | 1668.69 | 113.46 |
KITCHEN | 41186271.41 | 0.00 | 41186271.41 | 215126.85 | 41401398.25 | 47309374.20 | 1442.50 | 5908.12 | 1409.37 | 880.53 |
Total Facility | 82702216.56 | 0.00 | 82702216.56 | 7597118.38 | 90299334.94 | 89295692.77 | 1460.00 | 6369.24 | 2146.34 | 880.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.5809 | 0.0000 | 1.5809 | 0.2803 | 1.8612 | 1.3314 | 0.00 | 5538.52 | 1648.48 |
KITCHEN | 1.5273 | 0.0000 | 1.5273 | 0.0052 | 1.5325 | 1.5002 | 0.00 | 5816.42 | 1370.58 |
Total Facility | 3.1082 | 0.0000 | 3.1082 | 0.2855 | 3.3936 | 2.8315 | 0.00 | 6263.35 | 2095.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 60098921.47 | 0.00 | 60098921.47 | 41986318.57 | 1459.98 | 0.00 | 7300.02 | 113.46 |
PSZ-AC_2:2 | 59621682.29 | 0.00 | 59621682.29 | 47309374.20 | 1415.96 | 3.23 | 7340.81 | 880.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.2885 | 0.0000 | 2.2885 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 2.2109 | 0.0000 | 2.2109 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 918.59 | 757.95 | 5623.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5269.96 | 1653.36 | 1144.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 4.0224 | 2.8560 | 1.9276 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 2.1721 | 2.3775 | 2.1720 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
Electricity:Building | 574.49 | 4184.74 | 01-JAN-01:10 | 31858.89 | 02-JAN-11:10 |
Electricity:Zone:DINING | 202.98 | 1123.36 | 01-JAN-01:10 | 10843.36 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 557.63 | 3775.71 | 01-JAN-01:10 | 29493.74 | 02-JAN-11:10 |
InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 371.51 | 3061.38 | 01-JAN-01:10 | 21015.54 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.69 | 1038.02 | 04-FEB-23:30 | 3441.39 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 125.68 | 1103.96 | 05-FEB-01:10 | 6595.88 | 09-AUG-18:50 |
LowTempRefrigeration:Refrigeration:Electricity | 17.39 | 0.00 | 01-JAN-11:10 | 1521.73 | 11-JUL-04:10 |
MedTempRefrigeration:Refrigeration:Electricity | 32.45 | 750.86 | 05-FEB-06:00 | 1076.23 | 01-JAN-03:00 |
ElectricityPurchased:Facility | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
ElectricityPurchased:Plant | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
Cogeneration:ElectricityPurchased | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
General:Cogeneration:ElectricityPurchased | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
ElectricityNet:Plant | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
Cogeneration:ElectricityNet | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
General:Cogeneration:ElectricityNet | 1468.73 | 8623.05 | 05-FEB-01:10 | 85361.93 | 09-SEP-19:00 |
Electricity:HVAC | 716.16 | 0.00 | 01-JAN-01:10 | 51703.66 | 09-SEP-17:10 |
Fans:Electricity | 306.44 | 0.00 | 01-JAN-01:10 | 11361.08 | 02-NOV-04:10 |
General:Fans:Electricity | 306.44 | 0.00 | 01-JAN-01:10 | 11361.08 | 02-NOV-04:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 409.72 | 0.00 | 01-JAN-00:10 | 40342.57 | 09-SEP-17:10 |
General:Cooling:Electricity | 409.72 | 0.00 | 01-JAN-00:10 | 40342.57 | 09-SEP-17:10 |
ExteriorLights:Electricity | 52.40 | 0.00 | 01-JAN-07:30 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 52.40 | 0.00 | 01-JAN-07:30 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.40 | 0.00 | 01-JAN-01:10 | 4741.92 | 26-JAN-07:50 |
Water Heater:WaterSystems:Electricity | 75.40 | 0.00 | 01-JAN-01:10 | 4741.92 | 26-JAN-07:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-FEB-12:40 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 776.65 | 2803.57 | 01-JAN-01:10 | 105238.34 | 05-FEB-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 21.54 | 0.00 | 01-JAN-00:10 | 80737.50 | 05-FEB-06:10 |
Heating:NaturalGas | 21.54 | 0.00 | 01-JAN-00:10 | 80737.50 | 05-FEB-06:10 |
General:Heating:NaturalGas | 21.54 | 0.00 | 01-JAN-00:10 | 80737.50 | 05-FEB-06:10 |
NaturalGas:Plant | 285.32 | 993.32 | 01-JAN-00:10 | 19510.06 | 27-JAN-08:00 |
WaterSystems:NaturalGas | 285.32 | 993.32 | 01-JAN-00:10 | 19510.06 | 27-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 285.32 | 993.32 | 01-JAN-00:10 | 19510.06 | 27-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 13-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 13-MAR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-APR-18:30 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-APR-18:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2725.44 | 3209.16 | 05-FEB-01:10 | 214501.90 | 09-SEP-18:10 |
EnergyTransfer:Building | 897.32 | 1604.58 | 05-FEB-01:10 | 56818.56 | 03-AUG-17:30 |
EnergyTransfer:Zone:KITCHEN | 483.51 | 1604.58 | 05-FEB-01:10 | 34469.85 | 03-JAN-05:10 |
Refrigeration:EnergyTransfer | 163.53 | 2714.19 | 04-FEB-23:30 | 7834.84 | 02-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.76 | 1357.09 | 04-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 81.76 | 1357.09 | 04-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.76 | 1357.09 | 04-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
EnergyTransfer:Plant | 276.12 | 1604.58 | 05-FEB-01:10 | 16349.88 | 18-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.65 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.12 | 1262.59 | 05-FEB-06:00 | 2238.70 | 01-JAN-03:00 |
EnergyTransfer:Zone:DINING | 413.80 | 0.00 | 01-JAN-01:10 | 35336.74 | 09-SEP-18:10 |
Heating:EnergyTransfer | 2.12 | 0.00 | 01-JAN-00:10 | 15180.48 | 09-SEP-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.12 | 0.00 | 01-JAN-00:10 | 15180.48 | 09-SEP-23:10 |
General:Heating:EnergyTransfer | 2.12 | 0.00 | 01-JAN-00:10 | 15180.48 | 09-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.12 | 0.00 | 01-JAN-00:10 | 15180.48 | 09-SEP-23:10 |
Cooling:EnergyTransfer | 813.43 | 0.00 | 01-JAN-01:10 | 54152.71 | 03-AUG-17:30 |
Cooling:EnergyTransfer:Zone:DINING | 411.68 | 0.00 | 01-JAN-01:10 | 35336.74 | 09-SEP-18:10 |
General:Cooling:EnergyTransfer | 813.43 | 0.00 | 01-JAN-01:10 | 54152.71 | 03-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DINING | 411.68 | 0.00 | 01-JAN-01:10 | 35336.74 | 09-SEP-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 401.75 | 0.00 | 01-JAN-01:10 | 30552.43 | 03-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 401.75 | 0.00 | 01-JAN-01:10 | 30552.43 | 03-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
EnergyTransfer:HVAC | 1552.00 | 0.00 | 01-JAN-00:10 | 150290.04 | 06-OCT-11:30 |
HeatingCoils:EnergyTransfer | 17.23 | 0.00 | 01-JAN-00:10 | 64590.00 | 05-FEB-06:10 |
CoolingCoils:EnergyTransfer | 1534.77 | 0.00 | 01-JAN-00:10 | 150290.04 | 06-OCT-11:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 194.36 | 0.00 | 01-JAN-01:10 | 13559.41 | 23-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.124 | -411.675 | 0.000 | 0.000 | 209.110 | 77.705 | 93.957 | 39.776 | 0.000 | 18.990 | 12.158 | 0.000 | -12.819 | 0.000 | -29.327 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -401.741 | 0.000 | 0.000 | 4.918 | 19.212 | 297.857 | 0.000 | 0.000 | 0.123 | 81.319 | 0.000 | 0.000 | 0.000 | -1.687 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.276 | 40.616 | 0.000 | 0.000 | 0.000 | -49.892 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.124 | -813.415 | 0.000 | 0.000 | 214.029 | 96.917 | 391.814 | 39.776 | 0.000 | 28.389 | 134.092 | 0.000 | -12.819 | 0.000 | -80.906 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 25-AUG-04:01 | 0.00 | 0.00 | 0.00 | -46170.82 | 0.00 | 0.00 | 699.59 | 854.19 | 2172.30 | 0.00 | 0.00 | 0.00 | 42993.01 | 0.00 | -528.74 | 0.00 | -19.51 | 0.00 |
KITCHEN | 27-OCT-03:31 | 0.00 | 0.00 | 0.00 | -59487.95 | 0.00 | 0.00 | 0.00 | 158.38 | 3821.48 | 0.00 | 0.00 | 0.00 | 55889.56 | 0.00 | -0.00 | 0.00 | -381.47 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-04:01 | 0.00 | 0.00 | 0.00 | -90372.87 | 0.00 | 0.00 | 803.61 | 1065.36 | 9429.23 | 0.00 | 0.00 | 440.05 | 79954.85 | 0.00 | -1174.05 | 0.00 | -146.18 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 09-SEP-23:01 | 0.00 | 0.00 | 20354.67 | 0.00 | 0.00 | 0.00 | 973.97 | 854.19 | 543.07 | 695.34 | 0.00 | 505.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23926.75 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-SEP-23:01 | -12063.34 | 12063.34 | 20354.67 | -12063.34 | 0.00 | 0.00 | 992.53 | 1065.36 | 3382.99 | 695.34 | 0.00 | 1290.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15717.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.9680 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9684 | 0.3355 | 1.0000 | Not calculated | 1.3314 | 0.3355 | ||
PSZ-AC_2:2 | 1.6485 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6485 | 0.1108 | 1.0000 | Not calculated | 0.1826 | 0.1108 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.9680 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9680 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3355 | ||
PSZ-AC_2:2 | 1.6485 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6485 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.1108 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9680 | 3.9680 | 3.9680 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6485 | 1.6485 | 1.6485 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.9680 | 3.9684 | 3.9680 | 3.9680 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6485 | 1.6485 | 1.6485 | 1.6485 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9680 | 3.9680 | 3.9680 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6485 | 1.6485 | 1.6485 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.9680 | 3.9680 | 3.9680 | 3.9680 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6485 | 1.6485 | 1.6485 | 1.6485 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1193.00 |
Number of hours not met | 1193.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 21.54 | 80737.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 409.72 | 40342.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.92 | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 52.40 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 306.44 | 11361.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.40 | 4741.92 | 285.32 | 19510.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.39 | 1521.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.45 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 527.40 | 1468.73 |
Natural Gas | 469.79 | 776.65 |
Additional | 0.00 | 0.00 |
Total | 997.19 | 2245.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 189.60 |
Space Heating | 0.00 |
Space Cooling | 801.57 |
Fans (All) | 599.50 |
Service Water Heating | 147.51 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2873.37 |
Subtotal | 2873.37 |
Natural Gas [MJ/m2] | |
Space Heating | 42.14 |
Service Water Heating | 558.19 |
Miscellaneous (All) | 1519.40 |
Subtotal | 1519.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.32 |
Space Heating | 0.96 |
Space Cooling | 18.25 |
Fans (All) | 13.65 |
Service Water Heating | 16.07 |
Receptacle Equipment | 41.44 |
Miscellaneous | 5.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4860. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7817.00 | 926.83 | 16.17 | 0.00 | 0.00 |
KITCHEN | 5836.67 | 2593.83 | 329.50 | 0.00 | 0.00 |
ATTIC | 5245.17 | 751.83 | 801.00 | 1001.50 | 960.50 |
Min | 5245.17 | 751.83 | 16.17 | 0.00 | 0.00 |
Max | 7817.00 | 2593.83 | 801.00 | 1001.50 | 960.50 |
Average | 6299.61 | 1424.17 | 382.22 | 333.83 | 320.17 |
Sum | 18898.83 | 4272.50 | 1146.67 | 1001.50 | 960.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822014.67 | 2055.67 | 151.67 | 0.00 | 0.00 |
KITCHEN | 14724.67 | 4384.50 | 123.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822014.67 | 4384.50 | 151.67 | 0.00 | 0.00 |
Average | 278913.11 | 2146.72 | 91.83 | 0.00 | 0.00 |
Sum | 836739.33 | 6440.17 | 275.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 3938.50 | 4815.00 | 6.50 | 0.00 | 0.00 |
KITCHEN | 2078.17 | 6636.67 | 45.17 | 0.00 | 0.00 |
ATTIC | 3478.33 | 2847.17 | 621.83 | 498.33 | 1314.33 |
Min | 2078.17 | 2847.17 | 6.50 | 0.00 | 0.00 |
Max | 3938.50 | 6636.67 | 621.83 | 498.33 | 1314.33 |
Average | 3165.00 | 4766.28 | 224.50 | 166.11 | 438.11 |
Sum | 9495.00 | 14298.83 | 673.50 | 498.33 | 1314.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 404735.33 | 419465.67 | 21.00 | 0.00 | 0.00 |
KITCHEN | 4811.83 | 14403.67 | 17.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 404735.33 | 419465.67 | 21.00 | 0.00 | 0.00 |
Average | 136515.72 | 144623.11 | 12.83 | 0.00 | 0.00 |
Sum | 409547.17 | 433869.33 | 38.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:34
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251726E+11 | 30048.11 | 20-JAN-05:01 | 17.00 | 17.00 | 0.143373E+11 | 14050.50 | 28-JAN-19:10 | 15.83 | 13.00 |
February | 0.238792E+11 | 27990.77 | 02-FEB-13:00 | 28.30 | 20.78 | 0.133031E+11 | 14051.41 | 25-FEB-19:00 | 18.80 | 17.36 |
March | 0.273734E+11 | 27627.21 | 30-MAR-12:00 | 28.30 | 22.50 | 0.150521E+11 | 14051.41 | 18-MAR-18:00 | 28.30 | 22.50 |
April | 0.312893E+11 | 33615.07 | 30-APR-04:01 | 21.25 | 19.78 | 0.148673E+11 | 14051.40 | 15-APR-18:49 | 21.25 | 19.78 |
May | 0.400016E+11 | 35975.17 | 26-MAY-04:02 | 25.00 | 23.72 | 0.154483E+11 | 14051.41 | 20-MAY-18:10 | 25.00 | 23.72 |
June | 0.406752E+11 | 39238.72 | 13-JUN-04:02 | 23.90 | 21.88 | 0.150303E+11 | 14051.40 | 03-JUN-18:00 | 23.90 | 21.88 |
July | 0.426559E+11 | 39777.93 | 18-JUL-04:02 | 24.40 | 22.88 | 0.153507E+11 | 14052.63 | 22-JUL-18:40 | 30.53 | 25.27 |
August | 0.433640E+11 | 46234.93 | 25-AUG-04:01 | 24.28 | 22.05 | 0.155466E+11 | 14051.41 | 12-AUG-18:10 | 24.28 | 22.05 |
September | 0.397166E+11 | 40818.88 | 29-SEP-04:02 | 23.80 | 22.30 | 0.149264E+11 | 14364.87 | 09-SEP-18:40 | 23.80 | 22.30 |
October | 0.392182E+11 | 41343.83 | 01-OCT-04:01 | 19.33 | 15.90 | 0.153277E+11 | 14051.42 | 21-OCT-18:49 | 24.50 | 23.88 |
November | 0.306448E+11 | 41713.29 | 04-NOV-04:01 | 20.85 | 20.49 | 0.146523E+11 | 14052.49 | 25-NOV-19:19 | 17.17 | 13.54 |
December | 0.276889E+11 | 39167.01 | 17-DEC-05:01 | 20.33 | 20.22 | 0.146106E+11 | 14052.68 | 23-DEC-19:40 | 17.67 | 13.79 |
Annual Sum or Average | 0.411680E+12 | 0.178453E+12 | ||||||||
Minimum of Months | 0.238792E+11 | 27627.21 | 17.00 | 15.90 | 0.133031E+11 | 14050.50 | 15.83 | 13.00 | ||
Maximum of Months | 0.433640E+11 | 46234.93 | 28.30 | 23.72 | 0.155466E+11 | 14364.87 | 30.53 | 25.27 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330427E+11 | 54279.63 | 03-JAN-05:01 | 3.83 | 1.49 | 0.105109E+11 | 6934.96 | 19-JAN-11:50 | 25.78 | 21.80 |
February | 0.294102E+11 | 57418.08 | 12-FEB-04:42 | 14.00 | 8.24 | 0.952317E+10 | 6934.94 | 09-FEB-11:00 | 14.00 | 8.24 |
March | 0.325302E+11 | 48196.80 | 24-MAR-03:31 | 16.77 | 12.24 | 0.105602E+11 | 6934.93 | 28-MAR-10:00 | 26.60 | 21.97 |
April | 0.319671E+11 | 58791.54 | 11-APR-03:41 | 11.35 | 8.60 | 0.102557E+11 | 6944.35 | 28-APR-10:50 | 29.62 | 23.32 |
May | 0.348356E+11 | 36776.32 | 12-MAY-03:21 | 23.05 | 20.22 | 0.106134E+11 | 6987.53 | 26-MAY-10:50 | 30.82 | 25.83 |
June | 0.340533E+11 | 33491.11 | 07-JUN-03:32 | 21.10 | 18.38 | 0.102884E+11 | 6995.64 | 19-JUN-10:00 | 31.70 | 26.19 |
July | 0.350580E+11 | 26980.53 | 18-JUL-03:21 | 24.40 | 22.88 | 0.106464E+11 | 7005.88 | 03-JUL-10:50 | 24.40 | 22.88 |
August | 0.357677E+11 | 36341.36 | 20-AUG-03:21 | 23.40 | 17.72 | 0.106421E+11 | 7006.12 | 14-AUG-10:00 | 23.40 | 17.72 |
September | 0.342716E+11 | 33302.55 | 22-SEP-03:21 | 21.65 | 20.10 | 0.102828E+11 | 6988.48 | 18-SEP-10:50 | 21.65 | 20.10 |
October | 0.348995E+11 | 59524.36 | 27-OCT-03:31 | 14.67 | 7.97 | 0.106137E+11 | 7020.84 | 06-OCT-10:50 | 14.67 | 7.97 |
November | 0.325410E+11 | 52027.26 | 17-NOV-04:11 | 13.87 | 11.22 | 0.102385E+11 | 6957.97 | 02-NOV-10:50 | 13.87 | 11.22 |
December | 0.333710E+11 | 56155.01 | 01-DEC-04:11 | 12.00 | 9.99 | 0.105363E+11 | 6937.83 | 15-DEC-11:00 | 28.00 | 23.07 |
Annual Sum or Average | 0.401748E+12 | 0.124711E+12 | ||||||||
Minimum of Months | 0.294102E+11 | 26980.53 | 3.83 | 1.49 | 0.952317E+10 | 6934.93 | 13.87 | 7.97 | ||
Maximum of Months | 0.357677E+11 | 59524.36 | 24.40 | 22.88 | 0.106464E+11 | 7020.84 | 31.70 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18.20 | 18.20 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 | 17.16 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 | 19.79 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 | 21.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 | 23.10 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 | 23.55 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 | 21.01 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 | 12.36 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12280914.19 | 7379.32 | 05-JAN-06:03 | 0.17 |
February | 20105534.14 | 10648.73 | 05-FEB-06:03 | -2.9 |
March | 6627405.76 | 6660.25 | 12-MAR-05:03 | 7.87 |
April | 39495235.57 | 6826.44 | 29-APR-23:02 | 25.50 |
May | 0.343035E+09 | 9238.22 | 02-MAY-23:02 | 26.93 |
June | 0.372550E+09 | 11300.65 | 28-JUN-23:01 | 28.22 |
July | 0.468590E+09 | 11487.20 | 04-JUL-23:01 | 28.30 |
August | 0.391929E+09 | 11608.54 | 24-AUG-23:01 | 28.52 |
September | 0.263538E+09 | 20345.55 | 09-SEP-23:01 | 33.88 |
October | 0.174241E+09 | 8902.34 | 13-OCT-23:02 | 26.83 |
November | 21984386.85 | 5844.59 | 01-NOV-23:02 | 24.75 |
December | 8477871.38 | 7930.13 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 0.212285E+10 | |||
Minimum of Months | 6627405.76 | 5844.59 | -2.9 | |
Maximum of Months | 0.468590E+09 | 20345.55 | 33.88 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656587E+10 | 3843.73 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.594703E+10 | 3843.73 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.667042E+10 | 3843.73 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.637984E+10 | 3843.73 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.661815E+10 | 3843.73 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.644748E+10 | 3843.73 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.655127E+10 | 3843.73 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.667042E+10 | 3843.73 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.638137E+10 | 3843.73 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.656511E+10 | 3843.73 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.635601E+10 | 3843.73 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.655204E+10 | 3843.73 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.777050E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.594703E+10 | 3843.73 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.667042E+10 | 3843.73 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162334E+10 | 950.33 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.147034E+10 | 950.33 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.164919E+10 | 950.33 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.157735E+10 | 950.33 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.163627E+10 | 950.33 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.159407E+10 | 950.33 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.161973E+10 | 950.33 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.164919E+10 | 950.33 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.157773E+10 | 950.33 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.162315E+10 | 950.33 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.157145E+10 | 950.33 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.161992E+10 | 950.33 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.192117E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.147034E+10 | 950.33 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.164919E+10 | 950.33 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.656587E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53131293.56 | 0.698552E+10 |
February | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98073991.54 | 0.512570E+10 |
March | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228182E+09 | 0.469494E+10 |
April | 0.292871E+11 | 0.637984E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736288E+09 | 0.199991E+10 |
May | 0.303219E+11 | 0.661815E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291224E+10 | 62267387.07 |
June | 0.295292E+11 | 0.644748E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343746E+10 | 51123938.47 |
July | 0.300798E+11 | 0.655127E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355630E+10 | 35633855.26 |
August | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334254E+10 | 0.103991E+09 |
September | 0.292871E+11 | 0.638137E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217958E+10 | 0.187619E+09 |
October | 0.300980E+11 | 0.656511E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185623E+10 | 0.104409E+10 |
November | 0.290996E+11 | 0.635601E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383073E+09 | 0.336126E+10 |
December | 0.300798E+11 | 0.655204E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206661E+09 | 0.567503E+10 |
Annual Sum or Average | 0.356244E+12 | 0.777050E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189898E+11 | 0.293271E+11 |
Minimum of Months | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53131293.56 | 35633855.26 |
Maximum of Months | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355630E+10 | 0.698552E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162334E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 22800.26 | 0.285995E+09 |
February | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 271581.73 | 0.206914E+09 |
March | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 998648.81 | 0.251173E+09 |
April | 0.786997E+09 | 0.157735E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 4758102.96 | 0.117589E+09 |
May | 0.814802E+09 | 0.163627E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 21086898.57 | 52054679.43 |
June | 0.793501E+09 | 0.159407E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 21037713.43 | 38691672.47 |
July | 0.808298E+09 | 0.161973E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19191357.80 | 34679636.31 |
August | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 22710973.46 | 56486584.03 |
September | 0.786997E+09 | 0.157773E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 15550674.59 | 68243015.68 |
October | 0.808786E+09 | 0.162315E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 14711229.04 | 0.140968E+09 |
November | 0.781956E+09 | 0.157145E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1410505.09 | 0.170620E+09 |
December | 0.808298E+09 | 0.161992E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 927468.36 | 0.263995E+09 |
Annual Sum or Average | 0.957291E+10 | 0.192117E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.122678E+09 | 0.168741E+10 |
Minimum of Months | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 22800.26 | 34679636.31 |
Maximum of Months | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 22710973.46 | 0.285995E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836824E+09 | 0.321293E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966300E+09 | 0.348662E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795341E+09 | 0.391637E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877701E+09 | 0.511399E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667014E+09 | 0.490384E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718973E+09 | 0.555476E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700332E+09 | 0.513241E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645137E+09 | 0.483047E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657023E+09 | 0.395984E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549011E+09 | 0.366980E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102739E+10 | 0.315850E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835328E+09 | 0.295244E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927637E+10 | 0.498920E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549011E+09 | 0.295244E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102739E+10 | 0.555476E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3843.73 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.21 | 02-JAN-13:00 | 11983.80 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3843.73 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.90 | 02-FEB-13:00 | 12957.18 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 3843.73 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2925.53 | 30-MAR-13:00 | 9027.74 | 08-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 3843.73 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4447.01 | 28-APR-13:00 | 6865.72 | 10-APR-19:53 |
May | 30255.31 | 06-MAY-18:10 | 3843.73 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5189.85 | 25-MAY-17:10 | 752.55 | 19-MAY-19:00 |
June | 30255.31 | 03-JUN-18:10 | 3843.73 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5399.17 | 13-JUN-17:03 | 925.13 | 07-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 3843.73 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5951.98 | 20-JUL-12:00 | 1121.57 | 11-JUL-19:55 |
August | 30255.31 | 05-AUG-18:10 | 3843.73 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6391.36 | 02-AUG-17:03 | 2004.63 | 16-AUG-19:00 |
September | 30255.31 | 02-SEP-18:10 | 3843.73 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7302.79 | 09-SEP-18:03 | 3022.33 | 07-SEP-17:53 |
October | 30255.31 | 07-OCT-18:10 | 3843.73 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5296.32 | 05-OCT-17:03 | 6769.88 | 27-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 3843.73 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3286.35 | 02-NOV-12:00 | 8808.11 | 15-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 3843.73 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2758.14 | 13-DEC-14:00 | 12071.33 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.21 | 752.55 | |||||
Maximum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 7302.79 | 12957.18 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 950.33 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 4.56 | 16-JAN-15:00 | 969.89 | 09-JAN-05:00 |
February | 813.01 | 04-FEB-19:10 | 950.33 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 26.41 | 02-FEB-13:00 | 1063.34 | 04-FEB-04:30 |
March | 813.01 | 04-MAR-19:10 | 950.33 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 24.51 | 27-MAR-15:00 | 1056.10 | 21-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 950.33 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 51.37 | 28-APR-15:00 | 773.18 | 02-APR-03:30 |
May | 813.01 | 06-MAY-18:10 | 950.33 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 64.89 | 25-MAY-13:55 | 403.43 | 05-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 950.33 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 76.86 | 08-JUN-15:00 | 419.75 | 08-JUN-02:50 |
July | 813.01 | 01-JUL-18:10 | 950.33 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 109.04 | 19-JUL-12:53 | 393.42 | 25-JUL-03:20 |
August | 813.01 | 05-AUG-18:10 | 950.33 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 69.73 | 21-AUG-15:00 | 567.17 | 16-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 950.33 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 230.33 | 09-SEP-23:10 | 579.45 | 05-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 950.33 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 97.01 | 09-OCT-13:55 | 653.56 | 29-OCT-01:50 |
November | 813.01 | 04-NOV-18:10 | 950.33 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 21.26 | 03-NOV-14:00 | 747.95 | 12-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 950.33 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 22.03 | 13-DEC-14:30 | 1063.44 | 20-DEC-04:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 4.56 | 393.42 | ||||||
Maximum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 230.33 | 1063.44 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1699.97 | 05-JAN-01:00 | 6903.07 | 21-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2179.26 | 10-FEB-07:53 | 7274.52 | 13-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2027.29 | 14-MAR-07:33 | 8091.62 | 13-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1894.79 | 11-APR-06:53 | 8666.04 | 21-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.68 | 02-MAY-23:00 | 8504.50 | 10-MAY-14:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1530.59 | 28-JUN-01:51 | 8500.62 | 28-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1552.60 | 15-JUL-05:00 | 8462.75 | 20-JUL-14:02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.52 | 31-AUG-06:20 | 8218.44 | 10-AUG-14:13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1510.48 | 01-SEP-06:45 | 7953.19 | 02-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.45 | 23-OCT-23:55 | 6932.97 | 02-OCT-13:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1679.75 | 23-NOV-07:25 | 6558.55 | 06-NOV-13:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2698.39 | 19-DEC-07:42 | 6433.81 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.45 | 6433.81 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2698.39 | 8666.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30048.11 | 20-JAN-05:01 | 16808.50 | 8541.86 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 |
February | 27990.77 | 02-FEB-13:00 | 53787.21 | 7687.45 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.90 | 0.00 |
March | 27627.21 | 30-MAR-12:00 | 53787.21 | 7687.45 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2631.41 | 0.00 |
April | 33615.07 | 30-APR-04:01 | 0.00 | 4484.40 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
May | 35975.17 | 26-MAY-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
June | 39238.72 | 13-JUN-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
July | 39777.93 | 18-JUL-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
August | 46234.93 | 25-AUG-04:01 | 11765.95 | 5979.30 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
September | 40818.88 | 29-SEP-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
October | 41343.83 | 01-OCT-04:01 | 0.00 | 6406.28 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 |
November | 41713.29 | 04-NOV-04:01 | 0.00 | 5125.03 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
December | 39167.01 | 17-DEC-05:01 | 0.00 | 5765.65 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27627.21 | 0.00 | 4484.40 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46234.93 | 53787.21 | 8541.86 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.90 | 67.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54279.63 | 03-JAN-05:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
February | 57418.08 | 12-FEB-04:42 | 0.00 | 950.30 | 21722.03 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 472.05 |
March | 48196.80 | 24-MAR-03:31 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 215.54 |
April | 58791.54 | 11-APR-03:41 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 |
May | 36776.32 | 12-MAY-03:21 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 159.80 |
June | 33491.11 | 07-JUN-03:32 | 0.00 | 950.30 | 21722.03 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 202.02 |
July | 26980.53 | 18-JUL-03:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 95.71 |
August | 36341.36 | 20-AUG-03:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 |
September | 33302.55 | 22-SEP-03:21 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 |
October | 59524.36 | 27-OCT-03:31 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 381.47 |
November | 52027.26 | 17-NOV-04:11 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 161.24 |
December | 56155.01 | 01-DEC-04:11 | 0.00 | 1425.45 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 311.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26980.53 | 0.00 | 950.30 | 21722.03 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | |
Maximum of Months | 59524.36 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 472.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.91 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.16 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.88 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.10 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.21 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.49 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.79 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1242.13 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.48 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.66 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 644.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1242.13 | 81.15 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.964549E+11 | 73328.79 | 19-JAN-11:00 | 0.749084E+11 | 86558.60 | 05-JAN-07:00 |
February | 0.899559E+11 | 71489.12 | 24-FEB-12:00 | 0.662577E+11 | 105238.34 | 05-FEB-07:49 |
March | 0.103228E+12 | 74206.60 | 07-MAR-11:39 | 0.691150E+11 | 79413.99 | 09-MAR-06:10 |
April | 0.111142E+12 | 76940.51 | 28-APR-11:00 | 0.624578E+11 | 43082.24 | 02-APR-10:30 |
May | 0.143065E+12 | 80469.11 | 26-MAY-10:00 | 0.630828E+11 | 42819.34 | 06-MAY-10:50 |
June | 0.141995E+12 | 81491.55 | 29-JUN-11:00 | 0.599515E+11 | 42619.12 | 04-JUN-10:30 |
July | 0.151449E+12 | 83586.10 | 18-JUL-11:09 | 0.611338E+11 | 42491.67 | 02-JUL-10:50 |
August | 0.149459E+12 | 82070.27 | 14-AUG-10:00 | 0.615546E+11 | 42538.53 | 27-AUG-10:50 |
September | 0.140598E+12 | 85361.93 | 09-SEP-18:00 | 0.603284E+11 | 42705.75 | 30-SEP-10:50 |
October | 0.133542E+12 | 84004.74 | 06-OCT-10:50 | 0.636655E+11 | 42953.25 | 29-OCT-10:00 |
November | 0.105938E+12 | 77480.88 | 07-NOV-12:00 | 0.632880E+11 | 43160.46 | 26-NOV-11:39 |
December | 0.101906E+12 | 75722.66 | 14-DEC-12:00 | 0.709033E+11 | 88654.47 | 21-DEC-07:10 |
Annual Sum or Average | 0.146873E+13 | 0.776647E+12 | ||||
Minimum of Months | 0.899559E+11 | 71489.12 | 0.599515E+11 | 42491.67 | ||
Maximum of Months | 0.151449E+12 | 85361.93 | 0.749084E+11 | 105238.34 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.818922E+10 | 0.503353E+10 | 0.391293E+11 | 0.00 | 0.256284E+11 | 37879553.69 | 0.00 | 0.666913E+10 | 0.00 | 0.00 | 0.00 | 0.638787E+10 | 0.00 |
February | 0.741737E+10 | 0.434733E+10 | 0.353426E+11 | 0.00 | 0.232721E+11 | 34213790.43 | 0.00 | 0.881331E+10 | 0.00 | 0.00 | 0.00 | 0.577898E+10 | 0.00 |
March | 0.831961E+10 | 0.451338E+10 | 0.391293E+11 | 0.00 | 0.258214E+11 | 37879553.69 | 0.00 | 0.134319E+11 | 0.00 | 0.00 | 0.00 | 0.645287E+10 | 0.00 |
April | 0.795718E+10 | 0.407724E+10 | 0.378671E+11 | 0.00 | 0.252431E+11 | 36657632.61 | 0.00 | 0.242711E+11 | 0.00 | 0.00 | 0.00 | 0.619351E+10 | 0.00 |
May | 0.825441E+10 | 0.395120E+10 | 0.391293E+11 | 0.00 | 0.262262E+11 | 37879553.69 | 0.00 | 0.532723E+11 | 0.00 | 0.00 | 0.00 | 0.641363E+10 | 0.00 |
June | 0.804156E+10 | 0.368112E+10 | 0.378671E+11 | 0.00 | 0.253643E+11 | 36657632.61 | 0.00 | 0.551459E+11 | 0.00 | 0.00 | 0.00 | 0.623434E+10 | 0.00 |
July | 0.817100E+10 | 0.387918E+10 | 0.391293E+11 | 0.00 | 0.262081E+11 | 37879553.69 | 0.00 | 0.618111E+11 | 0.00 | 0.00 | 0.00 | 0.636854E+10 | 0.00 |
August | 0.831961E+10 | 0.409125E+10 | 0.391293E+11 | 0.00 | 0.262152E+11 | 37879553.69 | 0.00 | 0.593841E+11 | 0.00 | 0.00 | 0.00 | 0.644722E+10 | 0.00 |
September | 0.795910E+10 | 0.424529E+10 | 0.378671E+11 | 0.00 | 0.253790E+11 | 36657632.61 | 0.00 | 0.532933E+11 | 0.00 | 0.00 | 0.00 | 0.619260E+10 | 0.00 |
October | 0.818826E+10 | 0.469143E+10 | 0.391293E+11 | 0.00 | 0.261745E+11 | 37879553.69 | 0.00 | 0.431945E+11 | 0.00 | 0.00 | 0.00 | 0.637732E+10 | 0.00 |
November | 0.792746E+10 | 0.479346E+10 | 0.378671E+11 | 0.00 | 0.251454E+11 | 36657632.61 | 0.00 | 0.185731E+11 | 0.00 | 0.00 | 0.00 | 0.617639E+10 | 0.00 |
December | 0.817196E+10 | 0.509955E+10 | 0.391293E+11 | 0.00 | 0.257604E+11 | 37879553.69 | 0.00 | 0.118637E+11 | 0.00 | 0.00 | 0.00 | 0.637755E+10 | 0.00 |
Annual Sum or Average | 0.969167E+11 | 0.524040E+11 | 0.460716E+12 | 0.00 | 0.306438E+12 | 0.446001E+09 | 0.00 | 0.409723E+12 | 0.00 | 0.00 | 0.00 | 0.754008E+11 | 0.00 |
Minimum of Months | 0.741737E+10 | 0.368112E+10 | 0.353426E+11 | 0.00 | 0.232721E+11 | 34213790.43 | 0.00 | 0.666913E+10 | 0.00 | 0.00 | 0.00 | 0.577898E+10 | 0.00 |
Maximum of Months | 0.831961E+10 | 0.509955E+10 | 0.391293E+11 | 0.00 | 0.262262E+11 | 37879553.69 | 0.00 | 0.618111E+11 | 0.00 | 0.00 | 0.00 | 0.645287E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.791430E+10 | 0.00 | 0.270944E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.589815E+10 | 0.00 | 0.243211E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.298158E+10 | 0.00 | 0.262337E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 7584694.67 | 0.00 | 0.238376E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.231831E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.213389E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.212341E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.216549E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.217158E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.237658E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.212595E+09 | 0.00 | 0.244628E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.452530E+10 | 0.00 | 0.264783E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.215395E+11 | 0.00 | 0.285320E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.212341E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.791430E+10 | 0.00 | 0.270944E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4794.05 | 02-JAN-10:09 | 3334.35 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 11361.08 | 01-JAN-00:10 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4794.05 | 01-FEB-10:09 | 3334.35 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 11361.08 | 01-FEB-00:20 | 17.86 | 01-FEB-12:39 | 0.00 | 01-FEB-00:10 |
March | 4794.05 | 01-MAR-10:09 | 3334.35 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 11361.08 | 01-MAR-00:20 | 17.86 | 15-MAR-09:20 | 0.00 | 01-MAR-00:10 |
April | 4794.05 | 01-APR-16:10 | 3334.35 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 11361.08 | 01-APR-04:10 | 17.86 | 14-APR-10:30 | 0.00 | 01-APR-00:10 |
May | 4794.05 | 01-MAY-09:09 | 3334.35 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 11361.08 | 01-MAY-04:10 | 17.86 | 12-MAY-10:30 | 0.00 | 01-MAY-00:10 |
June | 4794.05 | 01-JUN-09:09 | 3334.35 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 11361.08 | 01-JUN-04:10 | 17.86 | 01-JUN-13:20 | 0.00 | 01-JUN-00:10 |
July | 4794.05 | 01-JUL-16:10 | 3334.35 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 11361.08 | 01-JUL-04:10 | 17.86 | 03-JUL-13:09 | 0.00 | 01-JUL-00:10 |
August | 4794.05 | 01-AUG-09:09 | 3334.35 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 11361.08 | 01-AUG-04:30 | 17.86 | 05-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4794.05 | 01-SEP-09:09 | 3334.35 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 11361.08 | 01-SEP-04:19 | 17.86 | 15-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 4794.05 | 02-OCT-09:09 | 3334.35 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 11361.08 | 01-OCT-04:19 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 4794.05 | 01-NOV-09:09 | 3334.35 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 11361.08 | 02-NOV-04:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 4794.05 | 01-DEC-10:09 | 3334.35 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 11361.08 | 01-DEC-00:20 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 11361.08 | 17.86 | 0.00 | ||||||
Maximum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 11361.08 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 27261.45 | 19-JAN-12:09 | 0.00 | 0.00 | 0.00 | 4741.92 | 26-JAN-07:49 | 0.00 |
February | 27094.10 | 24-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4741.29 | 13-FEB-19:49 | 0.00 |
March | 29099.79 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4741.52 | 09-MAR-19:00 | 0.00 |
April | 33320.74 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 4737.69 | 03-APR-06:40 | 0.00 |
May | 35890.46 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4736.68 | 16-MAY-06:49 | 0.00 |
June | 37063.34 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4736.94 | 20-JUN-06:30 | 0.00 |
July | 39005.38 | 22-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.92 | 12-JUL-18:49 | 0.00 |
August | 38074.18 | 24-AUG-17:40 | 0.00 | 0.00 | 0.00 | 4737.07 | 03-AUG-18:30 | 0.00 |
September | 40342.57 | 09-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4736.60 | 08-SEP-18:10 | 0.00 |
October | 38427.67 | 06-OCT-11:09 | 0.00 | 0.00 | 0.00 | 4738.30 | 30-OCT-06:19 | 0.00 |
November | 33071.79 | 07-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4740.19 | 16-NOV-07:49 | 0.00 |
December | 31327.49 | 14-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4741.33 | 21-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 27094.10 | 0.00 | 0.00 | 0.00 | 4736.60 | 0.00 | ||
Maximum of Months | 40342.57 | 0.00 | 0.00 | 0.00 | 4741.92 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 73328.79 | 19-JAN-11:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 25857.72 | 0.00 |
February | 71489.12 | 24-FEB-12:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 27094.10 | 0.00 |
March | 74206.60 | 07-MAR-11:39 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 26735.14 | 0.00 |
April | 76940.51 | 28-APR-11:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 32545.50 | 0.00 |
May | 80469.11 | 26-MAY-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 33132.93 | 0.00 |
June | 81491.55 | 29-JUN-11:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 37063.34 | 0.00 |
July | 83586.10 | 18-JUL-11:09 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 38618.08 | 0.00 |
August | 82070.27 | 14-AUG-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 34928.22 | 0.00 |
September | 85361.93 | 09-SEP-18:00 | 4794.05 | 19067.80 | 3334.35 | 0.00 | 11361.08 | 17.86 | 0.00 | 40111.33 | 0.00 |
October | 84004.74 | 06-OCT-10:50 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 36489.22 | 0.00 |
November | 77480.88 | 07-NOV-12:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 33071.79 | 0.00 |
December | 75722.66 | 14-DEC-12:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 31327.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 71489.12 | 4794.05 | 19067.80 | 0.00 | 0.00 | 11361.08 | 17.86 | 0.00 | 25857.72 | 0.00 | |
Maximum of Months | 85361.93 | 4794.05 | 24699.69 | 3334.35 | 0.00 | 11361.08 | 17.86 | 0.00 | 40111.33 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 62934.13 | 05-JAN-06:10 | 0.00 | 19510.06 | 27-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 80737.50 | 05-FEB-06:10 | 0.00 | 19333.54 | 06-FEB-07:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 52752.81 | 09-MAR-06:10 | 0.00 | 17799.46 | 03-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 5402.44 | 11-APR-05:00 | 0.00 | 17530.30 | 03-APR-18:49 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 17237.96 | 02-MAY-18:10 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16971.14 | 01-JUN-18:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16768.86 | 03-JUL-18:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16854.49 | 31-AUG-18:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 17063.83 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 17379.82 | 31-OCT-18:49 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 10276.41 | 15-NOV-06:10 | 0.00 | 17668.04 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 60936.27 | 21-DEC-06:10 | 0.00 | 18506.48 | 20-DEC-19:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16768.86 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 80737.50 | 0.00 | 19510.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 30.84 | 0.00 | 30.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 30.89 | 0.00 | 30.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 30.97 | 0.00 | 30.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.77 | 2.50 | 30.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 97.67 | 28.45 | 67.33 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 224.17 | 27.93 | 194.67 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 378.67 | 27.99 | 347.67 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 298.00 | 27.98 | 267.00 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 211.00 | 28.08 | 180.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 | 28.45 | 115.83 | 28.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 29.08 | 17.17 | 28.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 31.08 | 0.00 | 31.08 |
Annual Sum or Average | 0.00 | 0.00 | 1463.33 | 28.24 | 1193.00 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.93 | 0.00 | 27.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 378.67 | 31.08 | 347.67 | 31.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.67 | 22.16 | 278.33 | 22.93 | 96.67 | 23.05 |
February | 289.33 | 22.71 | 355.33 | 23.37 | 146.67 | 23.45 |
March | 260.83 | 22.79 | 390.17 | 23.52 | 113.50 | 23.60 |
April | 191.50 | 24.03 | 535.00 | 24.08 | 165.67 | 24.12 |
May | 375.17 | 24.36 | 611.00 | 24.28 | 375.17 | 24.30 |
June | 407.83 | 24.34 | 592.00 | 24.28 | 407.83 | 24.30 |
July | 564.00 | 24.27 | 609.00 | 24.26 | 564.00 | 24.27 |
August | 477.67 | 24.32 | 612.00 | 24.28 | 477.67 | 24.29 |
September | 507.33 | 24.26 | 590.00 | 24.24 | 507.33 | 24.24 |
October | 285.00 | 24.28 | 588.17 | 24.21 | 277.17 | 24.24 |
November | 193.17 | 23.45 | 470.83 | 23.89 | 124.33 | 23.95 |
December | 320.67 | 22.57 | 350.00 | 23.32 | 120.67 | 23.43 |
Annual Sum or Average | 4220.17 | 23.74 | 5981.83 | 23.98 | 3376.67 | 24.04 |
Minimum of Months | 191.50 | 22.16 | 278.33 | 22.93 | 96.67 | 23.05 |
Maximum of Months | 564.00 | 24.36 | 612.00 | 24.28 | 564.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.67 | 22.41 | 338.17 | 23.42 | 224.67 | 23.79 |
February | 422.17 | 23.69 | 407.33 | 24.30 | 300.33 | 24.56 |
March | 461.50 | 24.22 | 470.67 | 24.72 | 342.17 | 24.98 |
April | 516.67 | 25.82 | 562.83 | 25.80 | 501.33 | 25.85 |
May | 611.00 | 26.22 | 611.00 | 26.22 | 611.00 | 26.22 |
June | 592.00 | 26.55 | 592.00 | 26.55 | 592.00 | 26.55 |
July | 609.00 | 27.04 | 609.00 | 27.04 | 609.00 | 27.04 |
August | 612.00 | 26.78 | 612.00 | 26.78 | 612.00 | 26.78 |
September | 590.00 | 26.55 | 590.00 | 26.55 | 590.00 | 26.55 |
October | 573.50 | 26.34 | 600.17 | 26.31 | 567.17 | 26.34 |
November | 460.33 | 25.27 | 515.00 | 25.43 | 401.00 | 25.60 |
December | 475.00 | 23.53 | 399.33 | 24.31 | 297.17 | 24.65 |
Annual Sum or Average | 6381.83 | 25.54 | 6307.50 | 25.78 | 5647.83 | 25.93 |
Minimum of Months | 422.17 | 22.41 | 338.17 | 23.42 | 224.67 | 23.79 |
Maximum of Months | 612.00 | 27.04 | 612.00 | 27.04 | 612.00 | 27.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.91213 | 47.27404 | 0.26726 | 9.78963 |
February | 551.00000 | 23.29423 | 50.73941 | 0.38928 | 11.41527 |
March | 612.00000 | 23.45988 | 49.37306 | 0.41903 | 11.20864 |
April | 590.00000 | 24.01926 | 56.67880 | 0.63565 | 14.09835 |
May | 611.00000 | 24.22460 | 65.31248 | -0.0149 | 5.56774 |
June | 592.00000 | 24.23898 | 65.68104 | 0.01209 | 5.68025 |
July | 609.00000 | 24.25225 | 68.93721 | 0.05086 | 5.87718 |
August | 612.00000 | 24.24712 | 67.46941 | 0.05048 | 5.79476 |
September | 590.00000 | 24.22024 | 67.71509 | 0.02992 | 5.65989 |
October | 610.00000 | 24.14988 | 60.24430 | 0.74633 | 17.37628 |
November | 591.00000 | 23.80616 | 51.50601 | 0.55746 | 12.89999 |
December | 609.00000 | 23.21023 | 49.79100 | 0.37444 | 11.02222 |
Annual Sum or Average | 7187.00000 | 23.83828 | 58.43582 | 0.29210 | 9.68480 |
Minimum of Months | 551.00000 | 22.91213 | 47.27404 | -0.0149 | 5.56774 |
Maximum of Months | 612.00000 | 24.25225 | 68.93721 | 0.74633 | 17.37628 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.72502 | 49.49631 | 0.45357 | 19.58495 |
February | 551.00000 | 23.69374 | 51.60456 | 0.70125 | 25.05948 |
March | 612.00000 | 24.10159 | 50.05267 | 0.78972 | 26.20749 |
April | 590.00000 | 25.58270 | 55.63036 | 1.20765 | 37.30832 |
May | 611.00000 | 26.21524 | 63.78555 | 0.93048 | 23.94932 |
June | 592.00000 | 26.55011 | 63.92755 | 1.06423 | 30.23075 |
July | 609.00000 | 27.03772 | 65.93423 | 1.25409 | 39.33876 |
August | 612.00000 | 26.77728 | 64.96652 | 1.16907 | 35.14037 |
September | 590.00000 | 26.54696 | 64.64261 | 1.07457 | 30.59925 |
October | 610.00000 | 26.19281 | 58.29675 | 1.42420 | 47.62894 |
November | 591.00000 | 24.94072 | 51.15885 | 1.02782 | 32.10894 |
December | 609.00000 | 23.53059 | 50.93972 | 0.67172 | 24.37007 |
Annual Sum or Average | 7187.00000 | 25.33195 | 57.57199 | 0.98176 | 30.98975 |
Minimum of Months | 551.00000 | 22.72502 | 49.49631 | 0.45357 | 19.58495 |
Maximum of Months | 612.00000 | 27.03772 | 65.93423 | 1.42420 | 47.62894 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.148752E+11 | 0.453760E+10 | 155.62 | 0.896803E+10 | 0.590720E+10 | 0.00 | 0.69 | 19-JAN-12:20 | 0.00 | 01-JAN-00:10 | 65903.25 | 19-JAN-12:20 | 37140.27 | 19-JAN-12:03 | 29985.55 | 31-JAN-13:00 | 18361.27 | 19-JAN-12:20 | 0.00 | 01-JAN-00:10 |
February | 0.197109E+11 | 0.599457E+10 | 194.80 | 0.119086E+11 | 0.780223E+10 | 0.00 | 0.71 | 24-FEB-12:55 | 0.00 | 01-FEB-00:03 | 67168.14 | 24-FEB-12:55 | 42374.40 | 02-FEB-13:00 | 26368.24 | 24-FEB-12:35 | 18712.99 | 24-FEB-12:55 | 0.00 | 01-FEB-00:03 |
March | 0.300819E+11 | 0.908042E+10 | 277.03 | 0.187664E+11 | 0.113155E+11 | 0.00 | 0.74 | 30-MAR-12:00 | 0.00 | 01-MAR-00:03 | 71249.44 | 30-MAR-12:00 | 42732.29 | 30-MAR-13:00 | 32683.36 | 07-MAR-12:55 | 19593.09 | 30-MAR-12:55 | 0.00 | 01-MAR-00:03 |
April | 0.543234E+11 | 0.161668E+11 | 431.42 | 0.335855E+11 | 0.207378E+11 | 0.00 | 0.83 | 28-APR-17:10 | 0.00 | 01-APR-00:01 | 84135.63 | 28-APR-17:10 | 50044.91 | 28-APR-13:00 | 46858.55 | 28-APR-05:03 | 22869.38 | 28-APR-16:10 | 0.00 | 01-APR-00:01 |
May | 0.120203E+12 | 0.341551E+11 | 586.54 | 0.674540E+11 | 0.527492E+11 | 0.00 | 1.00 | 26-MAY-04:02 | 0.00 | 01-MAY-00:01 | 108015.72 | 26-MAY-04:02 | 53578.37 | 25-MAY-17:03 | 66678.09 | 26-MAY-04:02 | 26867.84 | 26-MAY-04:02 | 0.00 | 01-MAY-00:01 |
June | 0.126178E+12 | 0.354502E+11 | 566.80 | 0.698962E+11 | 0.562814E+11 | 0.00 | 1.00 | 15-JUN-04:02 | 0.00 | 01-JUN-00:01 | 108015.72 | 21-JUN-04:02 | 55318.61 | 13-JUN-17:03 | 68063.78 | 23-JUN-04:02 | 26867.84 | 15-JUN-04:02 | 0.00 | 01-JUN-00:01 |
July | 0.143774E+12 | 0.396879E+11 | 588.58 | 0.736360E+11 | 0.701383E+11 | 0.00 | 1.00 | 02-JUL-04:02 | 0.00 | 01-JUL-00:01 | 108015.72 | 05-JUL-04:02 | 58077.46 | 20-JUL-12:00 | 69793.82 | 11-JUL-04:01 | 28141.00 | 22-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.137534E+12 | 0.382418E+11 | 588.09 | 0.726789E+11 | 0.648555E+11 | 0.00 | 1.00 | 02-AUG-04:02 | 0.00 | 01-AUG-00:01 | 108015.72 | 15-AUG-04:02 | 60164.13 | 30-AUG-17:02 | 71240.72 | 19-AUG-04:02 | 27244.37 | 24-AUG-18:00 | 0.00 | 01-AUG-00:01 |
September | 0.122624E+12 | 0.342540E+11 | 568.59 | 0.633676E+11 | 0.592565E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:01 | 108015.72 | 12-SEP-04:02 | 60866.41 | 09-SEP-17:08 | 70040.89 | 02-SEP-04:02 | 29228.18 | 09-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.996431E+11 | 0.281817E+11 | 525.48 | 0.552460E+11 | 0.443971E+11 | 0.00 | 1.00 | 06-OCT-04:02 | 0.00 | 01-OCT-00:01 | 108015.72 | 06-OCT-04:02 | 55865.61 | 05-OCT-17:03 | 73263.94 | 07-OCT-04:02 | 27879.44 | 06-OCT-11:02 | 0.00 | 01-OCT-00:01 |
November | 0.419727E+11 | 0.124092E+11 | 355.24 | 0.249156E+11 | 0.170571E+11 | 0.00 | 0.90 | 03-NOV-04:02 | 0.00 | 01-NOV-00:01 | 94132.36 | 03-NOV-04:02 | 47413.26 | 02-NOV-12:00 | 59308.09 | 03-NOV-04:02 | 24124.57 | 03-NOV-04:02 | 0.00 | 01-NOV-00:01 |
December | 0.268456E+11 | 0.799119E+10 | 242.19 | 0.156798E+11 | 0.111659E+11 | 0.00 | 0.79 | 14-DEC-13:00 | 0.00 | 01-DEC-00:03 | 79172.03 | 14-DEC-13:00 | 44251.97 | 15-DEC-14:00 | 46407.17 | 17-DEC-05:01 | 21167.68 | 14-DEC-13:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.937766E+12 | 0.266150E+12 | 5080.39 | 0.516103E+12 | 0.421664E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.148752E+11 | 0.453760E+10 | 155.62 | 0.896803E+10 | 0.590720E+10 | 0.00 | 0.69 | 0.00 | 65903.25 | 37140.27 | 26368.24 | 18361.27 | 0.00 | |||||||
Maximum of Months | 0.143774E+12 | 0.396879E+11 | 588.58 | 0.736360E+11 | 0.701383E+11 | 0.00 | 1.00 | 0.00 | 108015.72 | 60866.41 | 73263.94 | 29228.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.803146E+10 | 0.213153E+10 | 145.70 | 0.443048E+10 | 0.360098E+10 | 0.00 | 1.00 | 01-JAN-04:11 | 0.00 | 01-JAN-00:10 | 42283.31 | 19-JAN-04:02 | 21675.89 | 01-JAN-04:11 | 26983.31 | 19-JAN-04:02 | 9984.09 | 19-JAN-04:02 | 0.00 | 01-JAN-00:10 |
February | 0.106583E+11 | 0.281874E+10 | 184.06 | 0.596732E+10 | 0.469100E+10 | 0.00 | 1.00 | 02-FEB-05:01 | 0.00 | 01-FEB-00:03 | 42323.17 | 03-FEB-04:31 | 33493.39 | 12-FEB-04:42 | 26625.13 | 03-FEB-04:31 | 9986.78 | 03-FEB-04:31 | 0.00 | 01-FEB-00:03 |
March | 0.167639E+11 | 0.435145E+10 | 263.80 | 0.971980E+10 | 0.704407E+10 | 0.00 | 1.00 | 06-MAR-04:02 | 0.00 | 01-MAR-00:03 | 43973.44 | 07-MAR-11:45 | 28428.85 | 24-MAR-03:31 | 27597.79 | 07-MAR-04:31 | 10085.13 | 07-MAR-04:31 | 0.00 | 01-MAR-00:03 |
April | 0.318262E+11 | 0.810432E+10 | 439.36 | 0.187027E+11 | 0.131234E+11 | 0.00 | 1.00 | 01-APR-03:32 | 0.00 | 01-APR-00:01 | 44870.82 | 27-APR-10:32 | 32208.86 | 28-APR-15:05 | 28520.75 | 24-APR-10:40 | 10715.95 | 28-APR-15:05 | 0.00 | 01-APR-00:01 |
May | 0.801796E+11 | 0.191172E+11 | 656.57 | 0.425284E+11 | 0.376511E+11 | 0.00 | 1.00 | 01-MAY-03:03 | 0.00 | 01-MAY-00:01 | 44870.82 | 01-MAY-18:23 | 33403.05 | 28-MAY-15:13 | 30423.48 | 23-MAY-05:03 | 10841.35 | 07-MAY-13:55 | 0.00 | 01-MAY-00:01 |
June | 0.829527E+11 | 0.196957E+11 | 657.64 | 0.434044E+11 | 0.395484E+11 | 0.00 | 1.00 | 01-JUN-03:32 | 0.00 | 01-JUN-00:01 | 44870.82 | 01-JUN-12:21 | 34497.89 | 14-JUN-14:00 | 30913.47 | 29-JUN-20:55 | 11027.83 | 14-JUN-14:00 | 0.00 | 01-JUN-00:01 |
July | 0.941560E+11 | 0.221233E+11 | 702.35 | 0.438266E+11 | 0.503294E+11 | 0.00 | 1.00 | 01-JUL-00:42 | 0.00 | 01-JUL-00:01 | 44870.82 | 01-JUL-11:10 | 35226.01 | 08-JUL-12:00 | 31095.79 | 02-JUL-06:00 | 11225.96 | 21-JUL-15:53 | 0.00 | 01-JUL-00:01 |
August | 0.896282E+11 | 0.211423E+11 | 684.95 | 0.434761E+11 | 0.461520E+11 | 0.00 | 1.00 | 01-AUG-01:22 | 0.00 | 01-AUG-00:01 | 44870.82 | 02-AUG-06:00 | 37325.34 | 30-AUG-15:55 | 32197.17 | 09-AUG-19:00 | 11263.20 | 30-AUG-15:55 | 0.00 | 01-AUG-00:01 |
September | 0.806232E+11 | 0.190393E+11 | 642.85 | 0.371433E+11 | 0.434800E+11 | 0.00 | 1.00 | 01-SEP-03:21 | 0.00 | 01-SEP-00:01 | 44870.82 | 02-SEP-05:03 | 31603.29 | 01-SEP-14:00 | 31342.77 | 05-SEP-01:22 | 11281.95 | 09-SEP-16:53 | 0.00 | 01-SEP-00:01 |
October | 0.625123E+11 | 0.150128E+11 | 576.08 | 0.314212E+11 | 0.310911E+11 | 0.00 | 1.00 | 01-OCT-03:21 | 0.00 | 01-OCT-00:01 | 44870.82 | 06-OCT-04:03 | 35612.02 | 27-OCT-03:31 | 32842.86 | 07-OCT-00:08 | 10857.81 | 05-OCT-15:00 | 0.00 | 01-OCT-00:01 |
November | 0.244362E+11 | 0.616393E+10 | 349.37 | 0.130396E+11 | 0.113966E+11 | 0.00 | 1.00 | 01-NOV-03:32 | 0.00 | 01-NOV-00:01 | 44870.82 | 01-NOV-11:53 | 25346.35 | 03-NOV-13:55 | 30104.62 | 01-NOV-03:32 | 10281.72 | 01-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.152354E+11 | 0.387252E+10 | 231.20 | 0.801414E+10 | 0.722130E+10 | 0.00 | 1.00 | 01-DEC-04:11 | 0.00 | 01-DEC-00:03 | 44870.82 | 15-DEC-12:00 | 25497.18 | 13-DEC-15:00 | 28863.75 | 15-DEC-04:31 | 10165.49 | 12-DEC-13:52 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.597003E+12 | 0.143573E+12 | 5533.93 | 0.301674E+12 | 0.295329E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.803146E+10 | 0.213153E+10 | 145.70 | 0.443048E+10 | 0.360098E+10 | 0.00 | 1.00 | 0.00 | 42283.31 | 21675.89 | 26625.13 | 9984.09 | 0.00 | |||||||
Maximum of Months | 0.941560E+11 | 0.221233E+11 | 702.35 | 0.438266E+11 | 0.503294E+11 | 0.00 | 1.00 | 0.00 | 44870.82 | 37325.34 | 32842.86 | 11281.95 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 171.77 | 87.37 | 84.40 | 205.47 | 261.84 | 0.00 | 0.00 | 0.00 |
February | 191.85 | 92.62 | 99.23 | 241.10 | 224.14 | 0.00 | 0.00 | 0.00 |
March | 225.93 | 109.08 | 116.85 | 311.87 | 190.84 | 0.00 | 0.00 | 0.00 |
April | 247.58 | 111.89 | 135.69 | 392.05 | 124.46 | 0.00 | 0.00 | 0.00 |
May | 255.05 | 110.72 | 144.33 | 492.59 | 40.58 | 0.00 | 0.00 | 0.00 |
June | 258.18 | 102.29 | 155.90 | 515.20 | 36.48 | 0.00 | 0.00 | 0.00 |
July | 249.23 | 91.24 | 157.99 | 499.02 | 27.69 | 0.00 | 0.00 | 0.00 |
August | 229.80 | 79.07 | 150.72 | 456.95 | 37.46 | 0.00 | 0.00 | 0.00 |
September | 203.26 | 69.85 | 133.41 | 384.98 | 50.04 | 0.00 | 0.00 | 0.00 |
October | 201.17 | 84.95 | 116.21 | 358.46 | 84.16 | 0.00 | 0.00 | 0.00 |
November | 177.72 | 90.47 | 87.24 | 250.26 | 176.24 | 0.00 | 0.00 | 0.00 |
December | 140.21 | 63.60 | 76.61 | 173.73 | 233.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.72 | 91.06 | 121.66 | 357.44 | 123.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 140.21 | 63.60 | 76.61 | 173.73 | 27.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 258.18 | 111.89 | 157.99 | 515.20 | 261.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.66 | 382.22 | 153.44 | 785.44 | 344.93 | 0.00 | 0.00 | 0.00 |
February | 482.07 | 310.89 | 171.18 | 719.60 | 301.23 | 0.00 | 0.00 | 0.00 |
March | 314.80 | 144.87 | 169.92 | 478.17 | 273.03 | 0.00 | 0.00 | 0.00 |
April | 229.76 | 53.94 | 175.81 | 385.75 | 182.35 | 0.00 | 0.00 | 0.00 |
May | 176.73 | 8.71 | 168.02 | 376.48 | 57.45 | 0.00 | 0.00 | 0.00 |
June | 173.15 | 1.51 | 171.64 | 379.79 | 51.86 | 0.00 | 0.00 | 0.00 |
July | 181.03 | 2.97 | 178.07 | 395.24 | 38.72 | 0.00 | 0.00 | 0.00 |
August | 209.57 | 21.73 | 187.84 | 458.17 | 52.91 | 0.00 | 0.00 | 0.00 |
September | 256.98 | 68.41 | 188.57 | 516.83 | 70.39 | 0.00 | 0.00 | 0.00 |
October | 393.19 | 202.85 | 190.33 | 724.06 | 118.01 | 0.00 | 0.00 | 0.00 |
November | 510.27 | 352.77 | 157.50 | 809.90 | 239.08 | 0.00 | 0.00 | 0.00 |
December | 523.58 | 376.28 | 147.29 | 797.57 | 310.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 331.43 | 159.82 | 171.62 | 568.18 | 169.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.15 | 1.51 | 147.29 | 376.48 | 38.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 535.66 | 382.22 | 190.33 | 809.90 | 344.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.03 | 98.97 | 84.06 | 232.57 | 268.92 | 0.00 | 0.00 | 0.00 |
February | 207.71 | 105.31 | 102.40 | 276.46 | 231.10 | 0.00 | 0.00 | 0.00 |
March | 203.64 | 89.84 | 113.81 | 282.37 | 199.18 | 0.00 | 0.00 | 0.00 |
April | 253.18 | 116.34 | 136.84 | 406.75 | 128.29 | 0.00 | 0.00 | 0.00 |
May | 211.10 | 68.84 | 142.26 | 417.22 | 41.17 | 0.00 | 0.00 | 0.00 |
June | 234.26 | 82.20 | 152.06 | 472.61 | 37.28 | 0.00 | 0.00 | 0.00 |
July | 213.53 | 59.05 | 154.48 | 434.44 | 27.56 | 0.00 | 0.00 | 0.00 |
August | 215.78 | 65.61 | 150.18 | 434.89 | 38.03 | 0.00 | 0.00 | 0.00 |
September | 199.16 | 68.33 | 130.84 | 378.56 | 50.38 | 0.00 | 0.00 | 0.00 |
October | 204.36 | 88.54 | 115.82 | 367.82 | 87.05 | 0.00 | 0.00 | 0.00 |
November | 174.69 | 87.77 | 86.92 | 255.03 | 184.91 | 0.00 | 0.00 | 0.00 |
December | 167.47 | 88.79 | 78.67 | 225.51 | 236.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.54 | 84.76 | 120.78 | 348.96 | 126.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.47 | 59.05 | 78.67 | 225.51 | 27.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.18 | 116.34 | 154.48 | 472.61 | 268.92 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.460071E+09 | 0.234012E+09 | 0.226059E+09 | 0.550332E+09 | 0.701325E+09 |
February | 0.464120E+09 | 0.224067E+09 | 0.240053E+09 | 0.583263E+09 | 0.542236E+09 |
March | 0.605127E+09 | 0.292168E+09 | 0.312959E+09 | 0.835300E+09 | 0.511142E+09 |
April | 0.641737E+09 | 0.290024E+09 | 0.351714E+09 | 0.101619E+10 | 0.322607E+09 |
May | 0.683122E+09 | 0.296559E+09 | 0.386563E+09 | 0.131935E+10 | 0.108683E+09 |
June | 0.669209E+09 | 0.265125E+09 | 0.404084E+09 | 0.133539E+10 | 94567628.10 |
July | 0.667536E+09 | 0.244366E+09 | 0.423170E+09 | 0.133657E+10 | 74154856.80 |
August | 0.615489E+09 | 0.211794E+09 | 0.403695E+09 | 0.122389E+10 | 0.100339E+09 |
September | 0.526862E+09 | 0.181051E+09 | 0.345811E+09 | 0.997870E+09 | 0.129694E+09 |
October | 0.538802E+09 | 0.227535E+09 | 0.311267E+09 | 0.960088E+09 | 0.225417E+09 |
November | 0.460641E+09 | 0.234503E+09 | 0.226138E+09 | 0.648675E+09 | 0.456805E+09 |
December | 0.375530E+09 | 0.170339E+09 | 0.205190E+09 | 0.465306E+09 | 0.625805E+09 |
Annual Sum or Average | 0.670825E+10 | 0.287154E+10 | 0.383670E+10 | 0.112722E+11 | 0.389278E+10 |
Minimum of Months | 0.375530E+09 | 0.170339E+09 | 0.205190E+09 | 0.465306E+09 | 74154856.80 |
Maximum of Months | 0.683122E+09 | 0.296559E+09 | 0.423170E+09 | 0.133657E+10 | 0.701325E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143471E+10 | 0.102374E+10 | 0.410971E+09 | 0.210373E+10 | 0.923866E+09 |
February | 0.116622E+10 | 0.752103E+09 | 0.414119E+09 | 0.174087E+10 | 0.728736E+09 |
March | 0.843149E+09 | 0.388025E+09 | 0.455124E+09 | 0.128073E+10 | 0.731282E+09 |
April | 0.595525E+09 | 0.139814E+09 | 0.455711E+09 | 0.999856E+09 | 0.472639E+09 |
May | 0.473354E+09 | 23328503.82 | 0.450026E+09 | 0.100837E+10 | 0.153874E+09 |
June | 0.448817E+09 | 3923628.87 | 0.444894E+09 | 0.984403E+09 | 0.134412E+09 |
July | 0.484878E+09 | 7943441.78 | 0.476934E+09 | 0.105861E+10 | 0.103702E+09 |
August | 0.561325E+09 | 58208414.00 | 0.503116E+09 | 0.122715E+10 | 0.141725E+09 |
September | 0.666087E+09 | 0.177319E+09 | 0.488768E+09 | 0.133961E+10 | 0.182459E+09 |
October | 0.105311E+10 | 0.543326E+09 | 0.509782E+09 | 0.193933E+10 | 0.316076E+09 |
November | 0.132262E+10 | 0.914375E+09 | 0.408242E+09 | 0.209925E+10 | 0.619704E+09 |
December | 0.140234E+10 | 0.100783E+10 | 0.394514E+09 | 0.213621E+10 | 0.832274E+09 |
Annual Sum or Average | 0.104521E+11 | 0.503993E+10 | 0.541220E+10 | 0.179181E+11 | 0.534075E+10 |
Minimum of Months | 0.448817E+09 | 3923628.87 | 0.394514E+09 | 0.984403E+09 | 0.103702E+09 |
Maximum of Months | 0.143471E+10 | 0.102374E+10 | 0.509782E+09 | 0.213621E+10 | 0.923866E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.490222E+09 | 0.265083E+09 | 0.225140E+09 | 0.622908E+09 | 0.720274E+09 |
February | 0.502498E+09 | 0.254774E+09 | 0.247724E+09 | 0.668803E+09 | 0.559078E+09 |
March | 0.545437E+09 | 0.240621E+09 | 0.304817E+09 | 0.756309E+09 | 0.533491E+09 |
April | 0.656251E+09 | 0.301555E+09 | 0.354697E+09 | 0.105428E+10 | 0.332533E+09 |
May | 0.565400E+09 | 0.184372E+09 | 0.381028E+09 | 0.111748E+10 | 0.110272E+09 |
June | 0.607198E+09 | 0.213051E+09 | 0.394148E+09 | 0.122500E+10 | 96624857.64 |
July | 0.571924E+09 | 0.158165E+09 | 0.413759E+09 | 0.116359E+10 | 73829800.26 |
August | 0.577954E+09 | 0.175721E+09 | 0.402233E+09 | 0.116480E+10 | 0.101850E+09 |
September | 0.516228E+09 | 0.177099E+09 | 0.339129E+09 | 0.981238E+09 | 0.130592E+09 |
October | 0.547356E+09 | 0.237140E+09 | 0.310216E+09 | 0.985179E+09 | 0.233146E+09 |
November | 0.452790E+09 | 0.227488E+09 | 0.225302E+09 | 0.661039E+09 | 0.479286E+09 |
December | 0.448539E+09 | 0.237822E+09 | 0.210717E+09 | 0.604012E+09 | 0.632943E+09 |
Annual Sum or Average | 0.648180E+10 | 0.267289E+10 | 0.380891E+10 | 0.110047E+11 | 0.400392E+10 |
Minimum of Months | 0.448539E+09 | 0.158165E+09 | 0.210717E+09 | 0.604012E+09 | 73829800.26 |
Maximum of Months | 0.656251E+09 | 0.301555E+09 | 0.413759E+09 | 0.122500E+10 | 0.720274E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1187.65 | 839.87 | 890.46 | 568.56 | 321.90 | 0.00 | 0.00 |
February | 1207.12 | 726.43 | 881.63 | 508.82 | 372.81 | 0.00 | 0.00 |
March | 1048.58 | 639.23 | 744.37 | 343.79 | 400.57 | 0.00 | 0.00 |
April | 1167.26 | 417.82 | 730.52 | 282.17 | 448.35 | 0.00 | 0.00 |
May | 1284.03 | 136.93 | 642.87 | 188.27 | 454.61 | 0.00 | 0.00 |
June | 1365.74 | 123.77 | 665.60 | 186.00 | 479.60 | 0.00 | 0.00 |
July | 1327.72 | 93.00 | 643.79 | 153.25 | 490.54 | 0.00 | 0.00 |
August | 1348.71 | 127.11 | 655.16 | 166.41 | 488.74 | 0.00 | 0.00 |
September | 1278.79 | 169.23 | 659.40 | 206.59 | 452.82 | 0.00 | 0.00 |
October | 1445.91 | 284.78 | 798.71 | 376.34 | 422.37 | 0.00 | 0.00 |
November | 1295.96 | 581.00 | 862.67 | 531.01 | 331.67 | 0.00 | 0.00 |
December | 1174.88 | 758.77 | 831.25 | 528.67 | 302.58 | 0.00 | 0.00 |
Annual Sum or Average | 1261.30 | 406.48 | 749.69 | 335.63 | 414.06 | 0.00 | 0.00 |
Minimum of Months | 1048.58 | 93.00 | 642.87 | 153.25 | 302.58 | 0.00 | 0.00 |
Maximum of Months | 1445.91 | 839.87 | 890.46 | 568.56 | 490.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.318100E+10 | 0.224950E+10 | 0.238500E+10 | 0.152283E+10 | 0.862170E+09 | 0.00 | 0.00 |
February | 0.292027E+10 | 0.175739E+10 | 0.213284E+10 | 0.123094E+10 | 0.901896E+09 | 0.00 | 0.00 |
March | 0.280853E+10 | 0.171210E+10 | 0.199371E+10 | 0.920814E+09 | 0.107290E+10 | 0.00 | 0.00 |
April | 0.302554E+10 | 0.108299E+10 | 0.189351E+10 | 0.731392E+09 | 0.116212E+10 | 0.00 | 0.00 |
May | 0.343914E+10 | 0.366762E+09 | 0.172188E+10 | 0.504259E+09 | 0.121762E+10 | 0.00 | 0.00 |
June | 0.353999E+10 | 0.320808E+09 | 0.172522E+10 | 0.482100E+09 | 0.124313E+10 | 0.00 | 0.00 |
July | 0.355617E+10 | 0.249089E+09 | 0.172434E+10 | 0.410474E+09 | 0.131386E+10 | 0.00 | 0.00 |
August | 0.361239E+10 | 0.340457E+09 | 0.175477E+10 | 0.445724E+09 | 0.130904E+10 | 0.00 | 0.00 |
September | 0.331463E+10 | 0.438654E+09 | 0.170918E+10 | 0.535468E+09 | 0.117371E+10 | 0.00 | 0.00 |
October | 0.387271E+10 | 0.762760E+09 | 0.213927E+10 | 0.100800E+10 | 0.113126E+10 | 0.00 | 0.00 |
November | 0.335912E+10 | 0.150596E+10 | 0.223605E+10 | 0.137637E+10 | 0.859683E+09 | 0.00 | 0.00 |
December | 0.314679E+10 | 0.203228E+10 | 0.222641E+10 | 0.141599E+10 | 0.810422E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.397763E+11 | 0.128188E+11 | 0.236422E+11 | 0.105844E+11 | 0.130578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280853E+10 | 0.249089E+09 | 0.170918E+10 | 0.410474E+09 | 0.810422E+09 | 0.00 | 0.00 |
Maximum of Months | 0.387271E+10 | 0.224950E+10 | 0.238500E+10 | 0.152283E+10 | 0.131386E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638778E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162600475.8 | 81.21 | 0.00 | 0.00 |
February | 0.577884E+10 | -0.563431E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144535366.2 | 81.21 | 0.00 | 0.00 |
March | 0.645274E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158869815.1 | 81.21 | 0.00 | 0.00 |
April | 0.619339E+10 | -0.604346E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149927900.0 | 81.21 | 0.00 | 0.00 |
May | 0.641348E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153286252.2 | 81.22 | 0.00 | 0.00 |
June | 0.623412E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147549198.7 | 81.21 | 0.00 | 0.00 |
July | 0.636837E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151277095.2 | 81.22 | 0.00 | 0.00 |
August | 0.644712E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151916804.0 | 81.22 | 0.00 | 0.00 |
September | 0.619237E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147546112.7 | 81.21 | 0.00 | 0.00 |
October | 0.637722E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153382229.7 | 81.21 | 0.00 | 0.00 |
November | 0.617617E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151549947.8 | 81.21 | 0.00 | 0.00 |
December | 0.637744E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160349826.1 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.753990E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.183279E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577884E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162600475.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645274E+10 | -0.563431E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144535366.2 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.196739E+11 | -0.187591E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -914841838.8 | 58.99 | 0.00 | 0.00 |
February | 0.176425E+11 | -0.168375E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -804975314.0 | 58.99 | 0.00 | 0.00 |
March | 0.189735E+11 | -0.180931E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -880403366.5 | 58.98 | 0.00 | 0.00 |
April | 0.171195E+11 | -0.163025E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -816972621.9 | 58.98 | 0.00 | 0.00 |
May | 0.165183E+11 | -0.156888E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -829560215.6 | 58.99 | 0.00 | 0.00 |
June | 0.151008E+11 | -0.143055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -795357526.5 | 58.98 | 0.00 | 0.00 |
July | 0.149520E+11 | -0.141411E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -810967079.8 | 58.98 | 0.00 | 0.00 |
August | 0.152907E+11 | -0.144741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -816616237.0 | 58.98 | 0.00 | 0.00 |
September | 0.154068E+11 | -0.146116E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -795239179.5 | 58.98 | 0.00 | 0.00 |
October | 0.169863E+11 | -0.161562E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -830068552.2 | 58.98 | 0.00 | 0.00 |
November | 0.176227E+11 | -0.167906E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -832094042.9 | 58.99 | 0.00 | 0.00 |
December | 0.191699E+11 | -0.182758E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -894114710.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.204457E+12 | -0.194436E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.100212E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.149520E+11 | -0.187591E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -914841838.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.196739E+11 | -0.141411E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795239179.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317215E+10 | 35811.22 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242105E+10 | 43885.36 | 05-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133091E+10 | 31397.23 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5553673.41 | 3770.09 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85440373.17 | 7761.95 | 16-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185345E+10 | 35257.04 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317215E+10 | 43885.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315929E+10 | 25658.05 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229747E+10 | 32030.59 | 05-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105435E+10 | 22058.86 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 514082.32 | 551.86 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84635813.47 | 5902.73 | 16-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176679E+10 | 27262.32 | 21-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315929E+10 | 32030.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.148752E+11 | 0.896803E+10 | 65903.25 | 19-JAN-12:20 | 36974.22 | 0.00 |
February | 0.00 | 0.00 | 0.197109E+11 | 0.119086E+11 | 67168.14 | 24-FEB-12:55 | 41209.03 | 0.00 |
March | 0.00 | 0.00 | 0.300819E+11 | 0.187664E+11 | 71249.44 | 30-MAR-12:00 | 42031.88 | 0.00 |
April | 0.00 | 0.00 | 0.543234E+11 | 0.335855E+11 | 84135.63 | 28-APR-17:10 | 47026.41 | 0.00 |
May | 0.00 | 0.00 | 0.120203E+12 | 0.674540E+11 | 108015.72 | 26-MAY-04:02 | 41337.63 | 0.00 |
June | 0.00 | 0.00 | 0.126178E+12 | 0.698962E+11 | 108015.72 | 21-JUN-04:02 | 43238.48 | 0.00 |
July | 0.00 | 0.00 | 0.143774E+12 | 0.736360E+11 | 108015.72 | 05-JUL-04:02 | 44128.38 | 0.00 |
August | 0.00 | 0.00 | 0.137534E+12 | 0.726789E+11 | 108015.72 | 15-AUG-04:02 | 44746.38 | 0.00 |
September | 0.00 | 0.00 | 0.122624E+12 | 0.633676E+11 | 108015.72 | 12-SEP-04:02 | 47862.51 | 0.00 |
October | 0.00 | 0.00 | 0.996431E+11 | 0.552460E+11 | 108015.72 | 06-OCT-04:02 | 40242.00 | 0.00 |
November | 0.00 | 0.00 | 0.419727E+11 | 0.249156E+11 | 94132.36 | 03-NOV-04:02 | 34824.27 | 0.00 |
December | 0.00 | 0.00 | 0.268456E+11 | 0.156798E+11 | 79172.03 | 14-DEC-13:00 | 42534.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.937766E+12 | 0.516103E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.148752E+11 | 0.896803E+10 | 65903.25 | 34824.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143774E+12 | 0.736360E+11 | 108015.72 | 47862.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.803146E+10 | 0.443048E+10 | 42283.31 | 19-JAN-04:02 | 15300.00 | 0.00 |
February | 0.00 | 0.00 | 0.106583E+11 | 0.596732E+10 | 42323.17 | 03-FEB-04:31 | 15698.04 | 0.00 |
March | 0.00 | 0.00 | 0.167639E+11 | 0.971980E+10 | 43973.44 | 07-MAR-11:45 | 20521.11 | 0.00 |
April | 0.00 | 0.00 | 0.318262E+11 | 0.187027E+11 | 44870.82 | 27-APR-10:32 | 20781.20 | 0.00 |
May | 0.00 | 0.00 | 0.801796E+11 | 0.425284E+11 | 44870.82 | 01-MAY-18:23 | 21403.45 | 0.00 |
June | 0.00 | 0.00 | 0.829527E+11 | 0.434044E+11 | 44870.82 | 01-JUN-12:21 | 20784.20 | 0.00 |
July | 0.00 | 0.00 | 0.941560E+11 | 0.438266E+11 | 44870.82 | 01-JUL-11:10 | 21640.50 | 0.00 |
August | 0.00 | 0.00 | 0.896282E+11 | 0.434761E+11 | 44870.82 | 02-AUG-06:00 | 13619.03 | 0.00 |
September | 0.00 | 0.00 | 0.806232E+11 | 0.371433E+11 | 44870.82 | 02-SEP-05:03 | 14224.00 | 0.00 |
October | 0.00 | 0.00 | 0.625123E+11 | 0.314212E+11 | 44870.82 | 06-OCT-04:03 | 13921.25 | 0.00 |
November | 0.00 | 0.00 | 0.244362E+11 | 0.130396E+11 | 44870.82 | 01-NOV-11:53 | 20883.53 | 0.00 |
December | 0.00 | 0.00 | 0.152354E+11 | 0.801414E+10 | 44870.82 | 15-DEC-12:00 | 24189.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597003E+12 | 0.301674E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.803146E+10 | 0.443048E+10 | 42283.31 | 13619.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.941560E+11 | 0.438266E+11 | 44870.82 | 24189.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7466.86 | 14200.68 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7423.07 | 14171.08 | 03-FEB-07:35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7218.54 | 13828.48 | 03-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6753.98 | 13145.81 | 03-APR-18:53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6322.88 | 12332.45 | 01-MAY-18:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5985.30 | 11547.97 | 01-JUN-18:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5746.79 | 10953.92 | 07-JUL-18:08 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5870.79 | 11201.25 | 31-AUG-18:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6103.45 | 11832.60 | 29-SEP-18:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6497.36 | 12735.13 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6941.94 | 13501.47 | 30-NOV-19:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 7286.94 | 13983.62 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 6630.41 | ||||
Minimum of Months | 0.00 | 0.00 | 5746.79 | 10953.92 | ||
Maximum of Months | 0.00 | 0.00 | 7466.86 | 14200.68 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.516423E+10 | 0.55 | 2203.40 | 01-JAN-00:10 | 0.63 |
February | 0.477790E+10 | 0.57 | 2203.40 | 01-FEB-00:03 | 0.63 |
March | 0.533345E+10 | 0.57 | 2203.40 | 01-MAR-00:03 | 0.63 |
April | 0.536982E+10 | 0.59 | 2203.40 | 01-APR-00:20 | 0.63 |
May | 0.562285E+10 | 0.60 | 2203.40 | 01-MAY-00:19 | 0.63 |
June | 0.544391E+10 | 0.60 | 2203.40 | 01-JUN-00:12 | 0.63 |
July | 0.562516E+10 | 0.60 | 2203.40 | 01-JUL-00:09 | 0.63 |
August | 0.562397E+10 | 0.60 | 2203.40 | 01-AUG-00:09 | 0.63 |
September | 0.544087E+10 | 0.60 | 2203.40 | 01-SEP-00:09 | 0.63 |
October | 0.559585E+10 | 0.60 | 2203.40 | 01-OCT-00:09 | 0.63 |
November | 0.529268E+10 | 0.59 | 2203.40 | 01-NOV-00:12 | 0.63 |
December | 0.527650E+10 | 0.57 | 2203.40 | 01-DEC-00:03 | 0.63 |
Annual Sum or Average | 0.645672E+11 | 0.59 | |||
Minimum of Months | 0.477790E+10 | 0.55 | 2203.40 | 0.63 | |
Maximum of Months | 0.562516E+10 | 0.60 | 2203.40 | 0.63 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165028E+11 | 1.27 | 7393.71 | 01-JAN-19:50 | 1.51 |
February | 0.149057E+11 | 1.26 | 7393.71 | 04-FEB-15:32 | 1.53 |
March | 0.165028E+11 | 1.26 | 7393.71 | 02-MAR-16:34 | 1.52 |
April | 0.159704E+11 | 1.26 | 7393.71 | 01-APR-10:43 | 1.51 |
May | 0.165028E+11 | 1.26 | 7393.71 | 09-MAY-04:20 | 1.50 |
June | 0.159704E+11 | 1.26 | 7393.71 | 01-JUN-04:07 | 1.50 |
July | 0.165028E+11 | 1.26 | 7393.71 | 05-JUL-18:25 | 1.51 |
August | 0.165028E+11 | 1.26 | 7393.71 | 01-AUG-11:20 | 1.51 |
September | 0.159718E+11 | 1.26 | 7393.71 | 09-SEP-19:40 | 1.51 |
October | 0.165028E+11 | 1.26 | 7393.71 | 02-OCT-07:10 | 1.51 |
November | 0.159704E+11 | 1.26 | 7393.71 | 04-NOV-05:00 | 1.50 |
December | 0.165028E+11 | 1.26 | 7393.71 | 01-DEC-18:10 | 1.52 |
Annual Sum or Average | 0.194308E+12 | 1.26 | |||
Minimum of Months | 0.149057E+11 | 1.26 | 7393.71 | 1.50 | |
Maximum of Months | 0.165028E+11 | 1.27 | 7393.71 | 1.53 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.396136E+10 | 0.76 | 1763.97 | 01-JAN-17:52 | 0.87 |
February | 0.358847E+10 | 0.78 | 1763.97 | 01-FEB-11:30 | 0.87 |
March | 0.398523E+10 | 0.78 | 1763.97 | 03-MAR-11:33 | 0.88 |
April | 0.390288E+10 | 0.81 | 1763.97 | 01-APR-05:30 | 0.86 |
May | 0.410056E+10 | 0.83 | 1763.97 | 01-MAY-06:10 | 0.86 |
June | 0.395002E+10 | 0.83 | 1763.97 | 01-JUN-08:42 | 0.87 |
July | 0.408016E+10 | 0.84 | 1763.97 | 02-JUL-23:20 | 0.86 |
August | 0.408845E+10 | 0.83 | 1763.97 | 02-AUG-05:10 | 0.86 |
September | 0.396632E+10 | 0.83 | 1763.97 | 01-SEP-19:43 | 0.87 |
October | 0.407585E+10 | 0.82 | 1763.97 | 01-OCT-09:22 | 0.87 |
November | 0.388234E+10 | 0.80 | 1763.97 | 01-NOV-05:10 | 0.86 |
December | 0.398113E+10 | 0.78 | 1763.97 | 01-DEC-15:37 | 0.87 |
Annual Sum or Average | 0.475628E+11 | 0.81 | |||
Minimum of Months | 0.358847E+10 | 0.76 | 1763.97 | 0.86 | |
Maximum of Months | 0.410056E+10 | 0.84 | 1763.97 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 49.90 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.41 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.83 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 53.51 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 53.02 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 53.85 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 54.40 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.49 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 54.03 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 53.61 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 52.72 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.15 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.90 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.49 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.90 | 59.42 | 7466.86 | 14200.68 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.41 | 58.23 | 7423.07 | 14171.08 | 03-FEB-07:35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.83 | 58.54 | 7218.54 | 13828.48 | 03-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.02 | 52.02 | 6753.98 | 13145.81 | 03-APR-18:53 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.05 | 52.05 | 6322.88 | 12332.45 | 01-MAY-18:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.83 | 52.83 | 5985.30 | 11547.97 | 01-JUN-18:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.17 | 53.17 | 5746.79 | 10953.92 | 07-JUL-18:08 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.53 | 53.53 | 5870.79 | 11201.25 | 31-AUG-18:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.11 | 53.11 | 6103.45 | 11832.60 | 29-SEP-18:50 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.35 | 51.35 | 6497.36 | 12735.13 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.79 | 51.79 | 6941.94 | 13501.47 | 30-NOV-19:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.15 | 58.71 | 7286.94 | 13983.62 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 6630.41 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.90 | 51.35 | 5746.79 | 10953.92 | ||
Maximum of Months | 0.00 | 0.00 | 53.53 | 59.42 | 7466.86 | 14200.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210404E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.209003E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.255832E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.321372E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.506579E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.514206E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.561906E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.547445E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.502258E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.446844E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.283796E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.244940E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.460458E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209003E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.561906E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.609289E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.640721E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.833668E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120072E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232178E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.236457E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.262034E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252308E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.230056E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190887E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100463E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.785365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191136E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.609289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.262034E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165028E+11 | 0.148752E+11 | 0.317215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149057E+11 | 0.197109E+11 | 0.242105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165028E+11 | 0.300819E+11 | 0.133091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159704E+11 | 0.543234E+11 | 5553673.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165028E+11 | 0.120203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159704E+11 | 0.126178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165028E+11 | 0.143774E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165028E+11 | 0.137534E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159718E+11 | 0.122624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165028E+11 | 0.996431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159704E+11 | 0.419727E+11 | 85440373.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165028E+11 | 0.268456E+11 | 0.185345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194308E+12 | 0.937766E+12 | 0.886856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149057E+11 | 0.148752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165028E+11 | 0.143774E+12 | 0.317215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.396136E+10 | 0.803146E+10 | 0.315929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358847E+10 | 0.106583E+11 | 0.229747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398523E+10 | 0.167639E+11 | 0.105435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390288E+10 | 0.318262E+11 | 514082.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410056E+10 | 0.801796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395002E+10 | 0.829527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408016E+10 | 0.941560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408845E+10 | 0.896282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396632E+10 | 0.806232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407585E+10 | 0.625123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388234E+10 | 0.244362E+11 | 84635813.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398113E+10 | 0.152354E+11 | 0.176679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475628E+11 | 0.597003E+12 | 0.836304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358847E+10 | 0.803146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410056E+10 | 0.941560E+11 | 0.315929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.453760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149057E+11 | 0.00 | 0.00 | 0.00 | 0.599457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.908042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159704E+11 | 0.00 | 0.00 | 0.00 | 0.161668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.341551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159704E+11 | 0.00 | 0.00 | 0.00 | 0.354502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.396879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.382418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159718E+11 | 0.00 | 0.00 | 0.00 | 0.342540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.281817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159704E+11 | 0.00 | 0.00 | 0.00 | 0.124092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.799119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194308E+12 | 0.00 | 0.00 | 0.00 | 0.266150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149057E+11 | 0.00 | 0.00 | 0.00 | 0.453760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165028E+11 | 0.00 | 0.00 | 0.00 | 0.396879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.396136E+10 | 0.00 | 0.00 | 0.00 | 0.213153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358847E+10 | 0.00 | 0.00 | 0.00 | 0.281874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398523E+10 | 0.00 | 0.00 | 0.00 | 0.435145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390288E+10 | 0.00 | 0.00 | 0.00 | 0.810432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.410056E+10 | 0.00 | 0.00 | 0.00 | 0.191172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.395002E+10 | 0.00 | 0.00 | 0.00 | 0.196957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408016E+10 | 0.00 | 0.00 | 0.00 | 0.221233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.408845E+10 | 0.00 | 0.00 | 0.00 | 0.211423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396632E+10 | 0.00 | 0.00 | 0.00 | 0.190393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407585E+10 | 0.00 | 0.00 | 0.00 | 0.150128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388234E+10 | 0.00 | 0.00 | 0.00 | 0.616393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398113E+10 | 0.00 | 0.00 | 0.00 | 0.387252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475628E+11 | 0.00 | 0.00 | 0.00 | 0.143573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358847E+10 | 0.00 | 0.00 | 0.00 | 0.213153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.410056E+10 | 0.00 | 0.00 | 0.00 | 0.221233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236286E+11 | 0.170691E+10 | 0.00 | 40599993.93 | 1574993.54 | 94658277.88 | 0.209231E+11 | 0.00 | 4.42 |
February | 0.145876E+11 | 0.244480E+10 | 0.00 | 54194842.96 | 534795.46 | 0.338993E+09 | 0.215468E+11 | 0.00 | 4.77 |
March | 0.126492E+11 | 0.445740E+10 | 0.00 | 57739931.48 | 1755041.85 | 35653399.64 | 0.215201E+11 | 0.00 | 4.80 |
April | 0.306466E+10 | 0.104289E+11 | 0.00 | 61206684.68 | 45729198.51 | 0.00 | 0.163902E+11 | 0.00 | 5.05 |
May | 95895474.40 | 0.423466E+11 | 0.00 | 1872451.70 | 0.397310E+09 | 0.00 | 0.296445E+09 | 0.00 | 3.70 |
June | 71196843.78 | 0.477570E+11 | 0.00 | 1609513.54 | 0.480021E+09 | 0.00 | 0.241419E+09 | 0.00 | 3.67 |
July | 13634390.39 | 0.598113E+11 | 0.00 | 1167817.93 | 0.726050E+09 | 0.00 | 23938158.26 | 0.00 | 3.62 |
August | 84735769.90 | 0.537386E+11 | 0.00 | 1407824.00 | 0.579202E+09 | 0.00 | 0.140067E+09 | 0.00 | 3.64 |
September | 0.134170E+09 | 0.448951E+11 | 0.00 | 2789585.31 | 0.394349E+09 | 0.00 | 0.420382E+09 | 0.00 | 3.71 |
October | 0.137608E+10 | 0.323852E+11 | 0.00 | 24791950.77 | 0.253343E+09 | 0.00 | 0.760092E+10 | 0.00 | 4.24 |
November | 0.670282E+10 | 0.849305E+10 | 0.00 | 59329973.63 | 36512865.50 | 0.00 | 0.219173E+11 | 0.00 | 5.06 |
December | 0.172750E+11 | 0.470232E+10 | 0.00 | 43417846.60 | 7223309.64 | 52967687.93 | 0.207138E+11 | 0.00 | 4.61 |
Annual Sum or Average | 0.796835E+11 | 0.313167E+12 | 0.00 | 0.350128E+09 | 0.292360E+10 | 0.522272E+09 | 0.131734E+12 | 0.00 | 4.27 |
Minimum of Months | 13634390.39 | 0.170691E+10 | 0.00 | 1167817.93 | 534795.46 | 0.00 | 23938158.26 | 0.00 | 3.62 |
Maximum of Months | 0.236286E+11 | 0.598113E+11 | 0.00 | 61206684.68 | 0.726050E+09 | 0.338993E+09 | 0.219173E+11 | 0.00 | 5.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280950E+11 | 0.397017E+09 | 0.00 | 42205821.29 | 0.00 | 0.00 | 0.180828E+11 | 0.00 | 11.00 |
February | 0.172316E+11 | 0.515998E+09 | 0.00 | 62226311.93 | 0.00 | 0.00 | 0.205349E+11 | 0.00 | 11.17 |
March | 0.148568E+11 | 0.171070E+10 | 0.00 | 64624072.90 | 0.00 | 0.00 | 0.218347E+11 | 0.00 | 11.27 |
April | 0.271284E+10 | 0.471751E+10 | 0.00 | 88465012.04 | 0.00 | 0.00 | 0.201293E+11 | 0.00 | 11.66 |
May | 0.00 | 0.288665E+11 | 0.00 | 7438384.94 | 0.00 | 0.00 | 0.112321E+10 | 0.00 | 11.47 |
June | 7672685.16 | 0.324293E+11 | 0.00 | 4425819.34 | 0.00 | 0.00 | 0.765945E+09 | 0.00 | 11.41 |
July | 0.00 | 0.415358E+11 | 0.00 | 605877.95 | 0.00 | 0.00 | 61242457.71 | 0.00 | 11.37 |
August | 0.00 | 0.369188E+11 | 0.00 | 3805831.45 | 0.00 | 0.00 | 0.567028E+09 | 0.00 | 11.41 |
September | 0.00 | 0.310343E+11 | 0.00 | 7976690.87 | 0.00 | 0.00 | 0.118440E+10 | 0.00 | 11.50 |
October | 0.106183E+10 | 0.211610E+11 | 0.00 | 42857900.40 | 0.00 | 0.00 | 0.992303E+10 | 0.00 | 11.58 |
November | 0.775604E+10 | 0.491700E+10 | 0.00 | 68149179.08 | 0.00 | 0.00 | 0.227642E+11 | 0.00 | 11.48 |
December | 0.192927E+11 | 0.223180E+10 | 0.00 | 47435266.39 | 0.00 | 0.00 | 0.203595E+11 | 0.00 | 11.15 |
Annual Sum or Average | 0.910144E+11 | 0.206436E+12 | 0.00 | 0.440216E+09 | 0.00 | 0.00 | 0.137330E+12 | 0.00 | 11.37 |
Minimum of Months | 0.00 | 0.397017E+09 | 0.00 | 605877.95 | 0.00 | 0.00 | 61242457.71 | 0.00 | 11.00 |
Maximum of Months | 0.280950E+11 | 0.415358E+11 | 0.00 | 88465012.04 | 0.00 | 0.00 | 0.227642E+11 | 0.00 | 11.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:34
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.750279E+11 | 0.107151E+11 | 0.136393E+12 | 0.588677E+10 | 0.531509E+11 |
February | 0.835886E+11 | 0.783780E+10 | 0.111115E+12 | 0.749516E+10 | 0.628977E+11 |
March | 0.101948E+12 | 0.797947E+10 | 0.103737E+12 | 0.752611E+10 | 0.851536E+11 |
April | 0.117307E+12 | 0.385988E+10 | 0.516889E+11 | 0.785555E+10 | 0.138478E+12 |
May | 0.119210E+12 | -0.563230E+10 | -0.871682E+11 | 0.194608E+09 | 0.283715E+12 |
June | 0.118200E+12 | -0.631963E+10 | -0.103009E+12 | 0.142647E+09 | 0.294456E+12 |
July | 0.121978E+12 | -0.921060E+10 | -0.136696E+12 | 17216108.22 | 0.330566E+12 |
August | 0.114160E+12 | -0.837444E+10 | -0.118450E+12 | 0.100897E+09 | 0.316586E+12 |
September | 0.947218E+11 | -0.699539E+10 | -0.945344E+11 | 0.272920E+09 | 0.283467E+12 |
October | 0.980038E+11 | -0.323800E+10 | -0.353569E+11 | 0.345429E+10 | 0.231330E+12 |
November | 0.674997E+11 | 0.418123E+10 | 0.762904E+11 | 0.921113E+10 | 0.108825E+12 |
December | 0.663772E+11 | 0.806394E+10 | 0.111556E+12 | 0.689398E+10 | 0.773519E+11 |
Annual Sum or Average | 0.117802E+13 | 0.286701E+10 | 0.155650E+11 | 0.490513E+11 | 0.226598E+13 |
Minimum of Months | 0.663772E+11 | -0.921060E+10 | -0.136696E+12 | 17216108.22 | 0.531509E+11 |
Maximum of Months | 0.121978E+12 | 0.107151E+11 | 0.136393E+12 | 0.921113E+10 | 0.330566E+12 |