Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:28:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1830.16 | 3580.46 | 3580.46 |
Net Site Energy | 1830.16 | 3580.46 | 3580.46 |
Total Source Energy | 3989.40 | 7804.70 | 7804.70 |
Net Source Energy | 3989.40 | 7804.70 | 7804.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 85.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 171.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.44 | 312.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 52.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 962.79 | 867.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 85.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 171.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.44 | 312.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 30.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 85.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 171.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.44 | 312.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 52.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 736.89 | 777.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 982.53 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1883.57 | 1696.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 736.89 | 777.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 982.53 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1883.57 | 1696.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 962.794 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 962.794 | 100.00 |
Total On-Site and Utility Electric Sources | 962.794 | 100.00 |
Total Electricity End Uses | 962.794 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4250.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.9552 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.1538 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.9552 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.1538 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.2821 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JUN-17:19 | 27-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 14-FEB-07:40 |
Heating | 0.00 | 62296.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28776.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20336.83 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6538.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4437.23 | 26057.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1598.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 64193.69 | 101930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 62296.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28776.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6538.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4437.23 | 26057.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 440.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 964.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 92.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 544.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 408.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.91 | 338.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 165.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3049.17 | 940.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 180.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1064.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 798.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.39 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 323.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5965.27 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 180.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1064.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 798.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.39 | 662.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 323.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5965.27 | 1839.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.52 |
KITCHEN DIRECT AIR | 1.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.52 | 4.52 | 4.52 | 4.52 | 4.52 | 4.52 | 1.00 | 1.00 | 4.52 |
PSZ-AC_2:2 | 1.81 | 1.81 | 1.81 | 1.81 | 1.81 | 1.81 | 1.00 | 1.00 | 1.81 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.52 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.81 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.52 | 7667.55 |
PSZ-AC_2:2_ADDAQ FAN | 1.81 | 1941.03 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.52 | 4.52 | 4.52 | 2.98 | 96828.77 | 126766.82 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.20 | 45045.09 | 82784.51 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.52 | 2.26 | 3.01 | 96828.77 | 48414.39 | 0.750210 | 0.750210 |
PSZ-AC_2:2 COOLING COIL | 1.81 | 0.906983 | 1.21 | 45045.09 | 22522.54 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 126766.82 |
PSZ-AC_2:2 HEATING COIL | 82784.51 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.955 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.883 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.154 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1068.794 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2585.575 | 6.955 | 9.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2585.575 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1136.687 | 8.154 | 150.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1136.687 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.463_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.463_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.463_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.463_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.3335E-004 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.3151E-003 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.4769E-004 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.8773E-003 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.0580E-004 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.7747E-003 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.8584E-004 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.2816E-003 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.8916E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.8818E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1752E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.1635E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8150E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.8104E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.4376E-003 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.4378E-003 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.1807E-003 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.1692E-004 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.7125E-003 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.2723E-004 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.5923E-003 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.9033E-004 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.2816E-003 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8584E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 44818.21170 | 53781.85403 | 3.76823 | 4.52188 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7023.25264 | 8427.90317 | 0.34710 | 1.33138 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -5.20000 | 2.80840E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 21188.31249 | 25425.97499 | 1.51164 | 1.81397 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 72793.41 | 4.52188 | 4.52188 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63151.41 | 1.33138 | 1.33138 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 39433.40 | 1.81397 | 1.81397 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 57726.22 | 1.21700 | 1.21700 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.52188 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.81397 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.52188 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.52188 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.52188 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.52188 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.52188 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.52188 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.81397 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.81397 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.81397 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.81397 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81397 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81397 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.52188 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.81397 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.52188 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.52188 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7667.54663 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.52188 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.52188 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.52188 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.98444 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.52188 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.26094 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.01459 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 96828.77000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 48414.38500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75021 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75021 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 96828.77000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 126766.81913 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 126766.81913 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81397 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81397 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1941.02919 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81397 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81397 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81397 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19722 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81397 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90698 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.20931 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45045.09000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22522.54500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45045.09000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 82784.51381 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 82784.51381 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 93575.8 | 10.53 | 10.48 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 43755.8 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_EAST_0.25 | N/A | 2.632 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_SOUTH_0.25 | N/A | 2.632 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_WEST_0.25 | N/A | 2.632 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1145096555 | 0.2629166993 | Pass | Pass | 7.2048130065E-002 | 0.2113269612 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2409679056 | 0.6851359502 | Pass | Pass | 2.2497129810E-002 | 8.7210431672E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4788661127 | 0.4723747795 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1244.56 | 91.01 | 1066.60 | 23.93 | 1100.11 | 3526.22 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.463_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.632 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.463_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.632 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.463_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.632 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.632 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.632 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.9552 | 371.75 | 2585.58 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.21 | 0.0000 | Y | 38.45 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.1538 | 139.41 | 1136.69 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 16.28 |
Interior Lighting Total | 7.2821 | 511.15 | 3722.26 | 54.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2585.58 | 646.39 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2585.58 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 159.78 | AstronomicalClock | - | 48.77 | 48.77 | 1.46 | |
EXTERIOR_LIGHTS_B | 2015.63 | AstronomicalClock | - | 83.77 | 73.27 | 27.72 | |
Exterior Lighting Total | 2175.41 | 29.18 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 96828.77 | 72641.91 | 24186.86 | 0.75 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45045.09 | 31580.21 | 13464.88 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 93575.8 | 10.53 | 10.48 | ||||
PSZ-AC_2:2 COOLING COIL | 43755.8 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 126766.82 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 82784.51 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.52 | 7667.55 | 1695.65 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.81 | 1941.03 | 1070.05 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 44818.21 | 53781.85 | 144.67 | 3.768 | 4.522 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00835 | 37.97 | 0.00687 | 1.331 | 0.00 |
KITCHEN | 21188.31 | 25425.97 | 182.39 | 1.512 | 1.814 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.00883 | 36.93 | 0.00687 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7023.25 | 8427.90 | 22.67 | 0.347 | 1.331 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 20.05 | 0.00221 | -5.20 | 0.00281 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.52 | 4.52 | 1.33 | 1.33 | 4.5219 | 4.5219 | 4.5219 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.81 | 1.81 | 1.22 | 1.22 | 1.8140 | 1.8140 | 1.8140 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 96828.770 | 72641.912 | 4.521880 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 48414.39 | 43740.94 | 3.014587 | 28.14 | 15.84 | 0.00791569 | 11.21 | 8.66 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 44.1645 | 23.99 | 0.00835160 | 39.0218 | 44802.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 126766.819 | 126766.819 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 126766.82 | 126766.82 | 4.521881 | 13.29 | 8.86 | 0.00634405 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 29.4430 | 21.00 | 0.00781946 | 43.8540 | 7014.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 45045.090 | 31580.212 | 1.813970 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 22522.54 | 21636.55 | 1.209313 | 34.48 | 17.50 | 0.00745229 | 11.79 | 8.91 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 100.6358 | 25.98 | 0.00882150 | 36.5691 | 21188.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 82784.514 | 82784.514 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 82784.51 | 82784.51 | 1.813966 | -3.49 | -4.51 | 0.00261555 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 67.0907 | 20.35 | 0.00222239 | 13.0860 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 96828.770 | 72641.912 | 4.521880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5549 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.521881 | 4.72234349 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 48414.39 | 43740.94 | 1.0000 | 3.14822851 | 3.014587 | 28.14 | 15.84 | 0.00791569 | 48491.4 | 11.21 | 8.66 | 0.00700000 | 28914.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48414.39 | 38.10 | 0.00687148 | 18.17 | 1.33137743 | 44.1645 | 23.99 | 0.00835160 | 23.99 | 0.00835160 | 39.0218 | 44802.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 126766.819 | 126766.819 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.521881 | 4.72234349 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 126766.82 | 126766.82 | 1.0000 | 4.72234349 | 4.521881 | 13.29 | 8.86 | 0.00634405 | 29372.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 126766.82 | -5.20 | 0.00280840 | -5.20 | 1.33137743 | 29.4430 | 21.00 | 0.00781946 | 21.00 | 0.00781946 | 43.8540 | 7014.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45045.090 | 31580.212 | 1.813970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6934 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.813966 | 1.89438208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 22522.54 | 21636.55 | 1.0000 | 1.26292429 | 1.209313 | 34.48 | 17.50 | 0.00745229 | 53762.3 | 11.79 | 8.91 | 0.00700000 | 29511.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22522.54 | 38.10 | 0.00687148 | 18.17 | 1.21700195 | 100.6358 | 25.95 | 0.00882150 | 25.98 | 0.00882150 | 36.5691 | 21188.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82784.514 | 82784.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.813966 | 1.89438208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 82784.51 | 82784.51 | 1.0000 | 1.89438208 | 1.813966 | -3.49 | -4.51 | 0.00261555 | 3018.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82784.51 | -5.20 | 0.00280840 | -5.20 | 1.21700195 | 67.0907 | 0.00 | 0.00222239 | 20.35 | 0.00222239 | 13.0860 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.52 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3629.17 | 3404.33 | 786.33 |
KITCHEN | 5445.50 | 5625.00 | 4167.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5527.00 | 6764.17 | 4250.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 172.33 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 172.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.832 | 0.914 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.399 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.112 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.948 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 39338095.41 | 0.00 | 39338095.41 | 7418946.21 | 46757041.62 | 41986318.57 | 1460.00 | 5483.81 | 1816.19 | 113.00 |
KITCHEN | 32311227.50 | 0.00 | 32311227.50 | 147317.96 | 32458545.46 | 38379373.44 | 6695.00 | 2004.41 | 60.59 | 610.49 |
Total Facility | 71649322.91 | 0.00 | 71649322.91 | 7566264.17 | 79215587.07 | 80365692.01 | 6696.08 | 5493.54 | 1851.53 | 610.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.4983 | 0.0000 | 1.4983 | 0.2834 | 1.7817 | 1.3314 | 0.00 | 5385.35 | 1801.65 |
KITCHEN | 1.2038 | 0.0000 | 1.2038 | 0.0036 | 1.2073 | 1.2170 | 5143.95 | 1983.96 | 59.09 |
Total Facility | 2.7020 | 0.0000 | 2.7020 | 0.2870 | 2.9890 | 2.5484 | 5143.95 | 5395.08 | 1835.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 42903300.41 | 0.00 | 42903300.41 | 41986318.57 | 1460.00 | 0.00 | 7300.00 | 113.00 |
PSZ-AC_2:2 | 35239149.86 | 0.00 | 35239149.86 | 38379373.44 | 1427.23 | 1.07 | 7331.70 | 610.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.6341 | 0.0000 | 1.6341 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3128 | 0.0000 | 1.3128 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1387.66 | 435.18 | 5477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 495.21 | 2493.37 | 4808.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2798 | 1.8450 | 1.4524 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.3511 | 1.3245 | 1.3065 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
Electricity:Building | 511.65 | 3281.23 | 01-JAN-01:10 | 28991.58 | 02-JAN-11:10 |
Electricity:Zone:DINING | 163.72 | 856.89 | 01-JAN-01:10 | 8683.37 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 504.71 | 3144.96 | 01-JAN-01:10 | 26848.48 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.72 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:10 |
InteriorLights:Electricity:Zone:DINING | 38.45 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.72 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity | 54.72 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 38.45 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.72 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:10 |
Electricity:Zone:KITCHEN | 347.92 | 2424.34 | 01-JAN-01:10 | 20308.21 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 52.23 | 852.60 | 18-DEC-23:30 | 3219.34 | 19-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 121.18 | 1033.67 | 01-JAN-01:10 | 6440.17 | 30-SEP-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 14.76 | 0.00 | 01-JAN-11:10 | 1520.41 | 18-AUG-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 30.54 | 735.95 | 19-DEC-05:50 | 1076.23 | 10-MAR-04:50 |
ElectricityPurchased:Facility | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
ElectricityPurchased:Plant | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
Cogeneration:ElectricityPurchased | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
General:Cogeneration:ElectricityPurchased | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
ElectricityNet:Plant | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
Cogeneration:ElectricityNet | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
General:Cogeneration:ElectricityNet | 962.79 | 5725.85 | 01-JAN-01:10 | 64193.69 | 02-JUN-17:20 |
Electricity:HVAC | 300.78 | 0.00 | 01-JAN-01:10 | 35726.15 | 02-JUN-17:10 |
Fans:Electricity | 128.89 | 0.00 | 01-JAN-01:10 | 7123.95 | 21-JUL-18:00 |
General:Fans:Electricity | 128.89 | 0.00 | 01-JAN-01:10 | 7123.95 | 21-JUL-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 171.89 | 0.00 | 01-JAN-00:10 | 29126.35 | 02-JUN-17:10 |
General:Cooling:Electricity | 171.89 | 0.00 | 01-JAN-00:10 | 29126.35 | 02-JUN-17:10 |
ExteriorLights:Electricity | 29.18 | 0.00 | 01-JAN-07:20 | 2175.41 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 29.18 | 0.00 | 01-JAN-07:20 | 2175.41 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.44 | 0.00 | 01-JAN-01:10 | 4742.03 | 01-MAR-19:30 |
Water Heater:WaterSystems:Electricity | 75.44 | 0.00 | 01-JAN-01:10 | 4742.03 | 01-MAR-19:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 27-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 27-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 867.37 | 2758.01 | 01-JAN-01:10 | 101930.85 | 27-JAN-07:30 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 85.33 | 0.00 | 01-JAN-01:10 | 69984.95 | 03-FEB-07:00 |
Heating:NaturalGas | 85.33 | 0.00 | 01-JAN-01:10 | 69984.95 | 03-FEB-07:00 |
General:Heating:NaturalGas | 85.33 | 0.00 | 01-JAN-01:10 | 69984.95 | 03-FEB-07:00 |
NaturalGas:Plant | 312.25 | 947.76 | 01-JAN-01:10 | 26080.35 | 26-JAN-19:30 |
WaterSystems:NaturalGas | 312.25 | 947.76 | 01-JAN-01:10 | 26080.35 | 26-JAN-19:30 |
Water Heater:WaterSystems:NaturalGas | 312.25 | 947.76 | 01-JAN-01:10 | 26080.35 | 26-JAN-19:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-DEC-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-DEC-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1756.25 | 2931.37 | 06-JAN-01:10 | 170540.47 | 21-JUL-18:00 |
EnergyTransfer:Building | 780.81 | 1465.69 | 06-JAN-01:10 | 53805.54 | 17-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN | 435.94 | 1465.69 | 06-JAN-01:10 | 26935.89 | 08-DEC-05:10 |
Refrigeration:EnergyTransfer | 145.25 | 2620.94 | 18-DEC-23:10 | 7834.84 | 10-MAR-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.62 | 1310.47 | 18-DEC-23:10 | 3917.42 | 10-MAR-04:50 |
General:Refrigeration:EnergyTransfer | 72.62 | 1310.47 | 18-DEC-23:10 | 3917.42 | 10-MAR-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.62 | 1310.47 | 18-DEC-23:10 | 3917.42 | 10-MAR-04:50 |
EnergyTransfer:Plant | 289.46 | 1465.69 | 06-JAN-01:10 | 17927.52 | 06-FEB-19:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.21 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 60.41 | 1217.84 | 19-DEC-05:50 | 2238.70 | 10-MAR-04:50 |
EnergyTransfer:Zone:DINING | 344.88 | 0.00 | 01-JAN-01:10 | 33428.38 | 17-JUN-18:10 |
Heating:EnergyTransfer | 0.90 | 0.00 | 01-JAN-00:10 | 10858.12 | 02-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 0.90 | 0.00 | 01-JAN-00:10 | 10858.12 | 02-JUL-23:10 |
General:Heating:EnergyTransfer | 0.90 | 0.00 | 01-JAN-00:10 | 10858.12 | 02-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.90 | 0.00 | 01-JAN-00:10 | 10858.12 | 02-JUL-23:10 |
Cooling:EnergyTransfer | 707.29 | 0.00 | 01-JAN-01:10 | 51264.79 | 17-JUN-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 343.98 | 0.00 | 01-JAN-01:10 | 33428.38 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer | 707.29 | 0.00 | 01-JAN-01:10 | 51264.79 | 17-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 343.98 | 0.00 | 01-JAN-01:10 | 33428.38 | 17-JUN-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 287.25 | 03-JUL-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 287.25 | 03-JUL-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 363.31 | 0.00 | 01-JAN-01:10 | 23130.95 | 08-DEC-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 363.31 | 0.00 | 01-JAN-01:10 | 23130.95 | 08-DEC-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
PlantLoopHeatingDemand:Plant | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
General:WaterSystems:PlantLoopHeatingDemand | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
EnergyTransfer:HVAC | 685.97 | 0.00 | 01-JAN-01:10 | 109517.80 | 21-JUL-18:00 |
HeatingCoils:EnergyTransfer | 68.26 | 0.00 | 01-JAN-01:10 | 55987.96 | 03-FEB-07:00 |
CoolingCoils:EnergyTransfer | 617.71 | 0.00 | 01-JAN-00:10 | 109517.80 | 21-JUL-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
WaterUse:WaterSystems:EnergyTransfer | 216.84 | 0.00 | 01-JAN-01:10 | 15488.82 | 31-JAN-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.897 | -343.976 | 0.000 | 0.000 | 216.480 | 38.445 | 93.957 | 44.475 | 0.000 | 14.767 | 0.000 | 0.000 | -18.261 | 0.000 | -44.186 | -2.598 |
KITCHEN | 0.000 | 0.000 | 0.000 | -363.300 | 0.000 | 0.000 | 5.301 | 16.277 | 287.132 | 0.000 | 0.000 | 0.105 | 55.907 | 0.000 | 0.000 | 0.000 | -1.422 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.136 | 38.047 | 0.000 | 0.000 | 0.000 | -48.184 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.897 | -707.276 | 0.000 | 0.000 | 221.781 | 54.722 | 381.090 | 44.475 | 0.000 | 25.009 | 93.955 | 0.000 | -18.261 | 0.000 | -93.792 | -2.599 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-JUL-04:01 | 0.00 | 0.00 | 0.00 | -50000.33 | 0.00 | 0.00 | 709.46 | 498.89 | 2172.30 | 0.00 | 0.00 | 5.70 | 46688.31 | 0.00 | -74.32 | 0.00 | 0.00 | 0.00 |
KITCHEN | 25-APR-04:01 | 0.00 | 0.00 | 0.00 | -69116.73 | 0.00 | 0.00 | 5.20 | 178.91 | 6916.85 | 0.00 | 0.00 | 0.00 | 62066.97 | 0.00 | -0.00 | 0.00 | -51.20 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-04:01 | 0.00 | 0.00 | 0.00 | -82871.82 | 0.00 | 0.00 | 717.35 | 677.80 | 9089.15 | 0.00 | 0.00 | 482.87 | 71978.99 | 0.00 | -74.32 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 28-DEC-07:58 | 0.00 | 0.00 | 37726.37 | 0.00 | 0.00 | 0.00 | 9262.38 | 748.33 | 2715.37 | 523.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7122.83 | -43853.46 |
KITCHEN | 03-JUL-04:03 | 0.00 | 0.00 | 2011.19 | 0.00 | 0.00 | 0.00 | 7.89 | 178.91 | 6916.85 | 0.00 | 0.00 | 1.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9116.06 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-DEC-07:58 | -11604.49 | 11604.49 | 37726.37 | -11604.49 | 0.00 | 0.00 | 9534.40 | 1106.17 | 11104.56 | 523.84 | 0.00 | 1755.09 | 0.00 | 0.00 | 0.00 | 0.00 | -7122.83 | -43023.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5219 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5219 | 0.2944 | 1.0000 | Not calculated | 1.3314 | 0.2944 | ||
PSZ-AC_2:2 | 1.8140 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8140 | 0.1007 | 1.0000 | Not calculated | 0.1826 | 0.1007 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5219 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5219 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2944 | ||
PSZ-AC_2:2 | 1.8140 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8140 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1007 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5219 | 4.5219 | 4.5219 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8140 | 1.8140 | 1.8140 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5219 | 4.5219 | 4.5219 | 4.5219 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8140 | 1.8140 | 1.8140 | 1.8140 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5219 | 4.5219 | 4.5219 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8140 | 1.8140 | 1.8140 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5219 | 4.5219 | 4.5219 | 4.5219 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8140 | 1.8140 | 1.8140 | 1.8140 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 85.33 | 69984.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 171.89 | 29126.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.72 | 3050.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.18 | 2175.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 128.89 | 7123.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.44 | 4742.03 | 312.25 | 26080.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.76 | 1520.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 30.54 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 502.22 | 962.79 |
Natural Gas | 469.79 | 867.37 |
Additional | 0.00 | 0.00 |
Total | 972.01 | 1830.16 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 107.06 |
Space Heating | 0.00 |
Space Cooling | 336.27 |
Fans (All) | 252.16 |
Service Water Heating | 147.58 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 1883.57 |
Subtotal | 1883.57 |
Natural Gas [MJ/m2] | |
Space Heating | 166.93 |
Service Water Heating | 610.88 |
Miscellaneous (All) | 1696.89 |
Subtotal | 1696.89 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.99 |
Space Heating | 4.66 |
Space Cooling | 9.39 |
Fans (All) | 7.04 |
Service Water Heating | 21.18 |
Receptacle Equipment | 50.26 |
Miscellaneous | 4.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8561.00 | 199.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7602.83 | 1144.33 | 12.83 | 0.00 | 0.00 |
ATTIC | 5881.17 | 869.00 | 687.50 | 972.83 | 349.50 |
Min | 5881.17 | 199.00 | 0.00 | 0.00 | 0.00 |
Max | 8561.00 | 1144.33 | 687.50 | 972.83 | 349.50 |
Average | 7348.33 | 737.44 | 233.44 | 324.28 | 116.50 |
Sum | 22045.00 | 2212.33 | 700.33 | 972.83 | 349.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 823746.00 | 476.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823746.00 | 476.00 | 0.00 | 0.00 | 0.00 |
Average | 280993.00 | 158.67 | 0.00 | 0.00 | 0.00 |
Sum | 842979.00 | 476.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8243.83 | 516.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6296.33 | 2463.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 6102.67 | 1189.33 | 353.00 | 317.17 | 797.83 |
Min | 6102.67 | 516.17 | 0.00 | 0.00 | 0.00 |
Max | 8243.83 | 2463.67 | 353.00 | 317.17 | 797.83 |
Average | 6880.94 | 1389.72 | 117.67 | 105.72 | 265.94 |
Sum | 20642.83 | 4169.17 | 353.00 | 317.17 | 797.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 811696.67 | 12525.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14650.33 | 4582.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 811696.67 | 12525.33 | 0.00 | 0.00 | 0.00 |
Average | 275449.00 | 5702.67 | 0.00 | 0.00 | 0.00 |
Sum | 826347.00 | 17108.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195153E+11 | 27402.75 | 05-JAN-05:01 | -2.1 | -5.7 | 0.128183E+11 | 12939.37 | 03-JAN-12:00 | -2.1 | -5.7 |
February | 0.183802E+11 | 25987.95 | 01-FEB-05:01 | -0.6 | -3.3 | 0.121986E+11 | 14049.69 | 18-FEB-19:30 | 14.15 | 6.11 |
March | 0.216708E+11 | 24647.59 | 02-MAR-00:01 | -0.1 | -4.1 | 0.142748E+11 | 14051.38 | 25-MAR-18:10 | 18.62 | 7.41 |
April | 0.271650E+11 | 26015.73 | 19-APR-17:03 | 30.92 | 14.18 | 0.145639E+11 | 14051.39 | 08-APR-18:00 | 30.92 | 14.18 |
May | 0.334060E+11 | 30031.14 | 19-MAY-17:03 | 34.22 | 16.36 | 0.153776E+11 | 14051.86 | 27-MAY-18:00 | 27.20 | 17.08 |
June | 0.378402E+11 | 33438.43 | 17-JUN-18:02 | 35.45 | 16.60 | 0.150206E+11 | 14052.36 | 03-JUN-18:10 | 35.45 | 16.60 |
July | 0.391125E+11 | 49986.26 | 03-JUL-04:01 | 28.72 | 17.94 | 0.153399E+11 | 14053.03 | 08-JUL-18:10 | 24.90 | 20.69 |
August | 0.387841E+11 | 37967.67 | 04-AUG-04:01 | 23.22 | 17.32 | 0.155331E+11 | 14051.63 | 12-AUG-18:00 | 32.20 | 18.23 |
September | 0.358053E+11 | 38198.93 | 22-SEP-04:01 | 20.00 | 19.17 | 0.148692E+11 | 14052.83 | 09-SEP-18:10 | 20.00 | 19.17 |
October | 0.303906E+11 | 28700.37 | 03-OCT-11:53 | 30.00 | 18.56 | 0.150294E+11 | 14052.51 | 07-OCT-18:49 | 16.88 | 13.00 |
November | 0.229169E+11 | 25941.71 | 17-NOV-05:01 | -0.1 | -2.6 | 0.133894E+11 | 13201.79 | 18-NOV-19:19 | 11.50 | 2.50 |
December | 0.189930E+11 | 26812.51 | 22-DEC-05:01 | -3.4 | -5.2 | 0.126686E+11 | 12936.54 | 01-DEC-12:00 | -3.4 | -5.2 |
Annual Sum or Average | 0.343980E+12 | 0.171083E+12 | ||||||||
Minimum of Months | 0.183802E+11 | 24647.59 | -3.4 | -5.7 | 0.121986E+11 | 12936.54 | -3.4 | -5.7 | ||
Maximum of Months | 0.391125E+11 | 49986.26 | 35.45 | 19.17 | 0.155331E+11 | 14053.03 | 35.45 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292095E+11 | 33937.86 | 05-JAN-05:01 | -2.1 | -5.7 | 0.104711E+11 | 6934.71 | 03-JAN-11:50 | -2.1 | -5.7 |
February | 0.256962E+11 | 39473.95 | 07-FEB-04:42 | 12.02 | 4.07 | 0.949048E+10 | 6934.92 | 07-FEB-11:50 | 19.82 | 9.22 |
March | 0.282315E+11 | 34782.39 | 16-MAR-03:52 | 16.10 | 6.00 | 0.105444E+11 | 6934.92 | 07-MAR-11:50 | 16.10 | 6.00 |
April | 0.283454E+11 | 69071.64 | 25-APR-04:01 | 13.22 | 5.33 | 0.102466E+11 | 6934.95 | 06-APR-10:30 | 13.22 | 5.33 |
May | 0.310172E+11 | 65448.43 | 05-MAY-04:01 | 16.60 | 6.86 | 0.106036E+11 | 6934.93 | 18-MAY-10:09 | 24.27 | 15.99 |
June | 0.317689E+11 | 42281.12 | 13-JUN-03:31 | 18.13 | 6.52 | 0.102666E+11 | 6934.94 | 28-JUN-10:20 | 22.57 | 17.63 |
July | 0.335129E+11 | 36993.73 | 28-JUL-04:01 | 23.80 | 17.44 | 0.106031E+11 | 6934.91 | 20-JUL-10:00 | 23.80 | 17.44 |
August | 0.335215E+11 | 47710.68 | 27-AUG-04:01 | 19.50 | 13.08 | 0.106093E+11 | 6934.99 | 16-AUG-10:20 | 19.50 | 13.08 |
September | 0.319619E+11 | 46782.54 | 26-SEP-03:11 | 18.13 | 12.10 | 0.102613E+11 | 6934.93 | 26-SEP-10:09 | 22.38 | 13.90 |
October | 0.311959E+11 | 53778.20 | 31-OCT-04:01 | 15.22 | 6.61 | 0.105886E+11 | 6934.97 | 13-OCT-10:30 | 15.22 | 6.61 |
November | 0.291793E+11 | 42457.57 | 09-NOV-04:52 | 13.90 | 6.30 | 0.101854E+11 | 6934.97 | 10-NOV-11:30 | 20.85 | 11.99 |
December | 0.296731E+11 | 36766.63 | 19-DEC-05:01 | -3.7 | -7.3 | 0.104583E+11 | 6928.09 | 11-DEC-11:00 | -3.7 | -7.3 |
Annual Sum or Average | 0.363313E+12 | 0.124329E+12 | ||||||||
Minimum of Months | 0.256962E+11 | 33937.86 | -3.7 | -7.3 | 0.949048E+10 | 6928.09 | -3.7 | -7.3 | ||
Maximum of Months | 0.335215E+11 | 69071.64 | 23.80 | 17.44 | 0.106093E+11 | 6934.99 | 24.27 | 17.63 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 6.70 | 3.92 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 |
February | 0.00 | 0.00 | 01-FEB-00:02 | 6.42 | 1.84 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.32 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 | 2.41 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 | 8.41 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 | 11.56 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 | 17.07 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 | 17.18 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 | 8.67 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 | 5.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 | 5.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.00 | 0.00 | 6.42 | 1.84 | ||
Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.00 | 0.00 | 27.63 | 18.12 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75316524.31 | 10754.91 | 28-JAN-06:03 | -3.3 |
February | 65663489.14 | 9956.94 | 03-FEB-06:03 | -3.7 |
March | 34110801.56 | 10052.55 | 02-MAR-06:03 | -3.5 |
April | 6484085.08 | 3472.18 | 12-APR-05:03 | 4.22 |
May | 48737562.84 | 6949.20 | 19-MAY-23:02 | 28.03 |
June | 0.209062E+09 | 12109.50 | 14-JUN-23:01 | 31.83 |
July | 0.174516E+09 | 14423.72 | 02-JUL-23:01 | 33.48 |
August | 0.120165E+09 | 10102.87 | 06-AUG-23:01 | 30.40 |
September | 7518537.12 | 3268.22 | 21-SEP-23:02 | 25.32 |
October | 15805570.88 | 9209.52 | 01-OCT-23:01 | 29.63 |
November | 21907204.69 | 8540.90 | 28-NOV-06:03 | 1.02 |
December | 0.117363E+09 | 37725.61 | 28-DEC-07:58 | -1.1 |
Annual Sum or Average | 0.896651E+09 | |||
Minimum of Months | 6484085.08 | 3268.22 | -3.7 | |
Maximum of Months | 0.209062E+09 | 37725.61 | 33.48 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15837.57 | 263.96 | 28-JAN-05:04 | -2.9 |
February | 0.00 | 0.00 | 01-FEB-00:02 | 6.42 |
March | 573.32 | 9.56 | 02-MAR-05:04 | -3.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 172349.08 | 2010.74 | 03-JUL-04:03 | 28.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 52056.62 | 449.21 | 28-DEC-05:04 | -3.0 |
Annual Sum or Average | 240816.58 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 172349.08 | 2010.74 | 28.72 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:02 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.334683E+10 | 2244.98 | 02-JAN-17:10 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.300436E+10 | 2244.98 | 01-FEB-17:30 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.329819E+10 | 2244.98 | 01-MAR-17:49 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.310887E+10 | 2244.98 | 01-APR-18:19 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.319680E+10 | 2244.98 | 01-MAY-18:40 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.310270E+10 | 2244.98 | 01-JUN-19:10 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.315451E+10 | 2244.98 | 01-JUL-19:19 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.325601E+10 | 2244.98 | 01-AUG-18:10 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.313127E+10 | 2244.98 | 01-SEP-18:30 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.327696E+10 | 2244.98 | 02-OCT-17:40 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.322044E+10 | 2244.98 | 01-NOV-17:10 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.334837E+10 | 2244.98 | 01-DEC-16:49 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.384453E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.300436E+10 | 2244.98 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.334837E+10 | 2244.98 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137533E+10 | 805.14 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.124570E+10 | 805.14 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.139723E+10 | 805.14 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.133636E+10 | 805.14 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.138628E+10 | 805.14 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.135053E+10 | 805.14 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.137227E+10 | 805.14 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.139723E+10 | 805.14 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.133668E+10 | 805.14 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.137517E+10 | 805.14 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.133137E+10 | 805.14 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.137243E+10 | 805.14 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.162766E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.124570E+10 | 805.14 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.139723E+10 | 805.14 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.334683E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833179E+10 |
February | 0.272721E+11 | 0.300436E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645544E+10 |
March | 0.305458E+11 | 0.329819E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4728647.76 | 0.581923E+10 |
April | 0.292871E+11 | 0.310887E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693400E+09 | 0.240042E+10 |
May | 0.303219E+11 | 0.319680E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194217E+10 | 0.811280E+09 |
June | 0.295292E+11 | 0.310270E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384975E+10 | 0.205602E+09 |
July | 0.300798E+11 | 0.315451E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345519E+10 | 0.146651E+09 |
August | 0.305458E+11 | 0.325601E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284160E+10 | 0.393948E+09 |
September | 0.292871E+11 | 0.313127E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163558E+10 | 0.817181E+09 |
October | 0.300980E+11 | 0.327696E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344863E+09 | 0.303513E+10 |
November | 0.290996E+11 | 0.322044E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657100E+10 |
December | 0.300798E+11 | 0.334837E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919856E+10 |
Annual Sum or Average | 0.356244E+12 | 0.384453E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147673E+11 | 0.441862E+11 |
Minimum of Months | 0.272721E+11 | 0.300436E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146651E+09 |
Maximum of Months | 0.305458E+11 | 0.334837E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384975E+10 | 0.919856E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.137533E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198842E+09 |
February | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191673E+09 |
March | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199668E+09 |
April | 0.786997E+09 | 0.133636E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 5090384.23 | 0.132266E+09 |
May | 0.814802E+09 | 0.138628E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 16597413.37 | 89408074.60 |
June | 0.793501E+09 | 0.135053E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 33363272.28 | 40803468.14 |
July | 0.808298E+09 | 0.137227E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 24525519.48 | 32646288.35 |
August | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 18546371.83 | 41218644.37 |
September | 0.786997E+09 | 0.133668E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 5529432.25 | 38794232.03 |
October | 0.808786E+09 | 0.137517E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1546523.61 | 0.111569E+09 |
November | 0.781956E+09 | 0.133137E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166944E+09 |
December | 0.808298E+09 | 0.137243E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177929E+09 |
Annual Sum or Average | 0.957291E+10 | 0.162766E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.105199E+09 | 0.142176E+10 |
Minimum of Months | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32646288.35 |
Maximum of Months | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 33363272.28 | 0.199668E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892740E+09 | 0.273045E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834006E+09 | 0.284357E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859293E+09 | 0.380144E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847853E+09 | 0.450100E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825858E+09 | 0.477452E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723038E+09 | 0.531070E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563068E+09 | 0.531183E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666829E+09 | 0.501790E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893109E+09 | 0.470153E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855626E+09 | 0.359231E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954906E+09 | 0.291710E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121980E+10 | 0.268128E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101361E+11 | 0.481836E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563068E+09 | 0.268128E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121980E+10 | 0.531183E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2244.98 | 02-JAN-17:10 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 10445.89 | 26-JAN-19:55 |
February | 30255.31 | 04-FEB-19:10 | 2244.98 | 01-FEB-17:30 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 10365.81 | 08-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2244.98 | 01-MAR-17:49 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 476.16 | 22-MAR-13:00 | 11352.78 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2244.98 | 01-APR-18:19 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3627.95 | 21-APR-12:55 | 7412.97 | 10-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 2244.98 | 01-MAY-18:40 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5316.73 | 19-MAY-17:03 | 4077.49 | 06-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2244.98 | 01-JUN-19:10 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7423.74 | 02-JUN-17:03 | 2113.84 | 13-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 2244.98 | 01-JUL-19:19 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7210.29 | 03-JUL-17:03 | 1821.82 | 05-JUL-06:05 |
August | 30255.31 | 05-AUG-18:10 | 2244.98 | 01-AUG-18:10 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6304.91 | 07-AUG-17:03 | 3124.23 | 16-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 2244.98 | 01-SEP-18:30 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4665.39 | 19-SEP-17:02 | 4597.18 | 30-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 2244.98 | 02-OCT-17:40 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3233.44 | 04-OCT-17:02 | 6902.35 | 23-OCT-18:53 |
November | 30255.31 | 04-NOV-18:10 | 2244.98 | 01-NOV-17:10 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9545.10 | 27-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2244.98 | 01-DEC-16:49 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11487.71 | 26-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1821.82 | |||||
Maximum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 7423.74 | 11487.71 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 805.14 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 742.86 | 26-JAN-01:10 |
February | 813.01 | 04-FEB-19:10 | 805.14 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 1038.47 | 24-FEB-05:00 |
March | 813.01 | 04-MAR-19:10 | 805.14 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 789.14 | 20-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 805.14 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 76.10 | 21-APR-14:53 | 956.16 | 11-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 805.14 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 76.21 | 19-MAY-13:53 | 714.87 | 04-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 805.14 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 88.90 | 21-JUN-13:00 | 469.95 | 28-JUN-02:10 |
July | 813.01 | 01-JUL-18:10 | 805.14 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 231.45 | 02-JUL-23:01 | 253.40 | 28-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 805.14 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 64.49 | 26-AUG-14:55 | 370.87 | 14-AUG-00:50 |
September | 813.01 | 02-SEP-18:10 | 805.14 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 24.08 | 10-SEP-15:00 | 181.85 | 25-SEP-03:00 |
October | 813.01 | 07-OCT-18:10 | 805.14 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 37.45 | 02-OCT-00:40 | 493.60 | 24-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 805.14 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 695.36 | 10-NOV-04:40 |
December | 813.01 | 02-DEC-19:10 | 805.14 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 852.05 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 181.85 | ||||||
Maximum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 231.45 | 1038.47 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.69 | 02-JAN-07:55 | 5949.79 | 28-JAN-14:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2038.74 | 10-FEB-24:00 | 6529.40 | 09-FEB-12:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1791.14 | 06-MAR-02:70 | 7862.57 | 20-MAR-12:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.29 | 27-APR-05:40 | 8297.80 | 30-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.46 | 08-MAY-02:00 | 7827.72 | 12-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 14-JUN-03:55 | 8134.68 | 29-JUN-12:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1672.59 | 01-JUL-05:30 | 7778.53 | 06-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.46 | 26-AUG-06:00 | 7866.17 | 03-AUG-12:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.89 | 12-SEP-04:00 | 7740.15 | 05-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.63 | 16-OCT-01:55 | 6622.03 | 08-OCT-12:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2024.99 | 23-NOV-01:00 | 6221.31 | 07-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.07 | 20-DEC-03:52 | 6232.27 | 27-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.46 | 5949.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.07 | 8297.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27402.75 | 05-JAN-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.29 |
February | 25987.95 | 01-FEB-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.41 |
March | 24647.59 | 02-MAR-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.63 |
April | 26015.73 | 19-APR-17:03 | 80680.82 | 5051.20 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3605.41 | 0.00 |
May | 30031.14 | 19-MAY-17:03 | 107574.42 | 6734.93 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5316.73 | 0.00 |
June | 33438.43 | 17-JUN-18:02 | 151276.53 | 8418.67 | 26550.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6549.82 | 0.00 |
July | 49986.26 | 03-JUL-04:01 | 11765.95 | 3492.21 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 0.00 |
August | 37967.67 | 04-AUG-04:01 | 11765.95 | 3492.21 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
September | 38198.93 | 22-SEP-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
October | 28700.37 | 03-OCT-11:53 | 107574.42 | 6734.93 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3156.58 | 0.00 |
November | 25941.71 | 17-NOV-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26812.51 | 22-DEC-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24647.59 | 11765.95 | 3492.21 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49986.26 | 151276.53 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6549.82 | 388.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33937.86 | 05-JAN-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 |
February | 39473.95 | 07-FEB-04:42 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 |
March | 34782.39 | 16-MAR-03:52 | 0.00 | 670.93 | 16401.28 | 6788.44 | 0.00 | 0.00 | 0.00 | 0.00 | 196.67 |
April | 69071.64 | 25-APR-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 |
May | 65448.43 | 05-MAY-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 77.30 |
June | 42281.12 | 13-JUN-03:31 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 |
July | 36993.73 | 28-JUL-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.15 |
August | 47710.68 | 27-AUG-04:01 | 0.00 | 1073.49 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 |
September | 46782.54 | 26-SEP-03:11 | 0.00 | 1341.86 | 32802.55 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 |
October | 53778.20 | 31-OCT-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 64.40 |
November | 42457.57 | 09-NOV-04:52 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 72.77 |
December | 36766.63 | 19-DEC-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 33937.86 | 0.00 | 670.93 | 16401.28 | 6788.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69071.64 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 196.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.98 | 0.00 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.96 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.08 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.54 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.58 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.24 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.66 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.41 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.05 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.58 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.05 | 209.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.674646E+11 | 39962.70 | 03-JAN-17:10 | 0.916087E+11 | 101930.85 | 27-JAN-07:30 |
February | 0.616869E+11 | 42139.73 | 07-FEB-11:00 | 0.776895E+11 | 101358.00 | 03-FEB-07:10 |
March | 0.694555E+11 | 45328.10 | 22-MAR-10:00 | 0.787263E+11 | 88684.08 | 02-MAR-06:30 |
April | 0.758339E+11 | 50911.70 | 19-APR-11:00 | 0.663020E+11 | 56101.53 | 12-APR-06:10 |
May | 0.877595E+11 | 57468.41 | 19-MAY-10:00 | 0.654744E+11 | 43176.57 | 07-MAY-10:30 |
June | 0.953499E+11 | 64193.69 | 02-JUN-17:19 | 0.617436E+11 | 42897.48 | 04-JUN-10:30 |
July | 0.103821E+12 | 63932.68 | 03-JUL-17:19 | 0.625864E+11 | 42712.74 | 01-JUL-10:09 |
August | 0.984111E+11 | 62440.64 | 03-AUG-11:00 | 0.628280E+11 | 42687.35 | 27-AUG-10:30 |
September | 0.894666E+11 | 59912.66 | 15-SEP-11:00 | 0.616615E+11 | 42933.58 | 30-SEP-10:30 |
October | 0.792931E+11 | 57368.59 | 05-OCT-10:39 | 0.655644E+11 | 43219.83 | 29-OCT-10:09 |
November | 0.666981E+11 | 46569.88 | 10-NOV-11:50 | 0.750101E+11 | 76278.73 | 28-NOV-07:10 |
December | 0.675529E+11 | 39039.45 | 26-DEC-11:09 | 0.981750E+11 | 98265.49 | 27-DEC-07:10 |
Annual Sum or Average | 0.962794E+12 | 0.867370E+12 | ||||
Minimum of Months | 0.616869E+11 | 39039.45 | 0.616615E+11 | 42687.35 | ||
Maximum of Months | 0.103821E+12 | 64193.69 | 0.981750E+11 | 101930.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472216E+10 | 0.293313E+10 | 0.382185E+11 | 0.00 | 0.109555E+11 | 37879553.69 | 0.00 | 93608586.59 | 0.00 | 0.00 | 0.00 | 0.639244E+10 | 0.00 |
February | 0.425006E+10 | 0.248886E+10 | 0.345199E+11 | 0.00 | 0.978372E+10 | 34213790.43 | 0.00 | 0.102753E+10 | 0.00 | 0.00 | 0.00 | 0.578264E+10 | 0.00 |
March | 0.469542E+10 | 0.252720E+10 | 0.382185E+11 | 0.00 | 0.107040E+11 | 37879553.69 | 0.00 | 0.251975E+10 | 0.00 | 0.00 | 0.00 | 0.645558E+10 | 0.00 |
April | 0.444524E+10 | 0.221595E+10 | 0.369856E+11 | 0.00 | 0.103021E+11 | 36657632.61 | 0.00 | 0.113075E+11 | 0.00 | 0.00 | 0.00 | 0.619481E+10 | 0.00 |
May | 0.458308E+10 | 0.209255E+10 | 0.382185E+11 | 0.00 | 0.107823E+11 | 37879553.69 | 0.00 | 0.210415E+11 | 0.00 | 0.00 | 0.00 | 0.641477E+10 | 0.00 |
June | 0.445323E+10 | 0.192619E+10 | 0.369856E+11 | 0.00 | 0.108147E+11 | 36657632.61 | 0.00 | 0.304213E+11 | 0.00 | 0.00 | 0.00 | 0.623576E+10 | 0.00 |
July | 0.452678E+10 | 0.203382E+10 | 0.382185E+11 | 0.00 | 0.115664E+11 | 37879553.69 | 0.00 | 0.363951E+11 | 0.00 | 0.00 | 0.00 | 0.637105E+10 | 0.00 |
August | 0.465324E+10 | 0.220219E+10 | 0.382185E+11 | 0.00 | 0.111752E+11 | 37879553.69 | 0.00 | 0.310103E+11 | 0.00 | 0.00 | 0.00 | 0.644925E+10 | 0.00 |
September | 0.446796E+10 | 0.234387E+10 | 0.369856E+11 | 0.00 | 0.106063E+11 | 36657632.61 | 0.00 | 0.243331E+11 | 0.00 | 0.00 | 0.00 | 0.619420E+10 | 0.00 |
October | 0.465213E+10 | 0.266164E+10 | 0.382185E+11 | 0.00 | 0.106974E+11 | 37879553.69 | 0.00 | 0.120839E+11 | 0.00 | 0.00 | 0.00 | 0.637970E+10 | 0.00 |
November | 0.455181E+10 | 0.277590E+10 | 0.369856E+11 | 0.00 | 0.103834E+11 | 36657632.61 | 0.00 | 0.164272E+10 | 0.00 | 0.00 | 0.00 | 0.618209E+10 | 0.00 |
December | 0.472081E+10 | 0.298273E+10 | 0.382185E+11 | 0.00 | 0.111228E+11 | 37879553.69 | 0.00 | 10770377.73 | 0.00 | 0.00 | 0.00 | 0.638499E+10 | 0.00 |
Annual Sum or Average | 0.547219E+11 | 0.291840E+11 | 0.449992E+12 | 0.00 | 0.128894E+12 | 0.446001E+09 | 0.00 | 0.171887E+12 | 0.00 | 0.00 | 0.00 | 0.754373E+11 | 0.00 |
Minimum of Months | 0.425006E+10 | 0.192619E+10 | 0.345199E+11 | 0.00 | 0.978372E+10 | 34213790.43 | 0.00 | 10770377.73 | 0.00 | 0.00 | 0.00 | 0.578264E+10 | 0.00 |
Maximum of Months | 0.472216E+10 | 0.298273E+10 | 0.382185E+11 | 0.00 | 0.115664E+11 | 37879553.69 | 0.00 | 0.363951E+11 | 0.00 | 0.00 | 0.00 | 0.645558E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.214811E+11 | 0.00 | 0.302279E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.143430E+11 | 0.00 | 0.273081E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.936344E+10 | 0.00 | 0.294632E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.108931E+10 | 0.00 | 0.266000E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 23098759.17 | 0.00 | 0.255515E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.231310E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.226867E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.229283E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 19722686.85 | 0.00 | 0.230291E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.200822E+09 | 0.00 | 0.254639E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.976580E+10 | 0.00 | 0.266317E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.290426E+11 | 0.00 | 0.292327E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.853289E+11 | 0.00 | 0.312254E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.226867E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.290426E+11 | 0.00 | 0.302279E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3050.12 | 02-JAN-17:10 | 2175.41 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 6205.02 | 28-JAN-06:10 | 17.86 | 27-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3050.12 | 01-FEB-17:30 | 2175.41 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 6239.60 | 03-FEB-06:00 | 17.86 | 02-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3050.12 | 01-MAR-17:49 | 2175.41 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 6192.43 | 02-MAR-06:10 | 17.86 | 02-MAR-09:39 | 0.00 | 01-MAR-00:10 |
April | 3050.12 | 01-APR-18:19 | 2175.41 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 5373.19 | 12-APR-05:10 | 17.86 | 04-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 3050.12 | 01-MAY-18:40 | 2175.41 | 01-MAY-05:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 5349.22 | 19-MAY-11:00 | 17.86 | 21-MAY-08:20 | 0.00 | 01-MAY-00:10 |
June | 3050.12 | 01-JUN-19:10 | 2175.41 | 01-JUN-19:10 | 24359.61 | 01-JUN-10:09 | 0.00 | 6599.80 | 02-JUN-17:10 | 17.86 | 02-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 3050.12 | 01-JUL-19:19 | 2175.41 | 01-JUL-19:19 | 24359.61 | 01-JUL-10:09 | 0.00 | 7123.95 | 21-JUL-17:00 | 17.86 | 02-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 3050.12 | 01-AUG-18:10 | 2175.41 | 01-AUG-05:10 | 24359.61 | 01-AUG-10:09 | 0.00 | 6589.93 | 02-AUG-11:00 | 17.86 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 3050.12 | 01-SEP-18:30 | 2175.41 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 6093.07 | 15-SEP-11:00 | 17.86 | 03-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 3050.12 | 02-OCT-17:40 | 2175.41 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 5399.68 | 04-OCT-17:19 | 17.86 | 01-OCT-08:39 | 0.00 | 01-OCT-00:10 |
November | 3050.12 | 01-NOV-17:10 | 2175.41 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 5816.08 | 28-NOV-06:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3050.12 | 01-DEC-16:49 | 2175.41 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 6204.69 | 28-DEC-06:10 | 17.86 | 20-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 5349.22 | 17.86 | 0.00 | ||||||
Maximum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 7123.95 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 3933.88 | 03-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.79 | 11-JAN-07:00 | 0.00 |
February | 7527.67 | 06-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.84 | 17-FEB-07:49 | 0.00 |
March | 10175.88 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 4742.03 | 01-MAR-19:30 | 0.00 |
April | 17514.76 | 21-APR-12:00 | 0.00 | 0.00 | 0.00 | 4741.96 | 12-APR-06:40 | 0.00 |
May | 22034.85 | 19-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4740.33 | 02-MAY-06:19 | 0.00 |
June | 29126.35 | 02-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.87 | 02-JUN-06:49 | 0.00 |
July | 28296.65 | 03-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.84 | 21-JUL-18:00 | 0.00 |
August | 26019.45 | 03-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4736.72 | 03-AUG-06:49 | 0.00 |
September | 23878.17 | 15-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4737.15 | 29-SEP-06:19 | 0.00 |
October | 21339.48 | 04-OCT-17:19 | 0.00 | 0.00 | 0.00 | 4738.87 | 27-OCT-06:19 | 0.00 |
November | 10855.99 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4742.02 | 21-NOV-07:40 | 0.00 |
December | 648.93 | 09-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4741.89 | 06-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 648.93 | 0.00 | 0.00 | 0.00 | 4736.72 | 0.00 | ||
Maximum of Months | 29126.35 | 0.00 | 0.00 | 0.00 | 4742.03 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39962.70 | 03-JAN-17:10 | 3050.12 | 21945.94 | 2175.41 | 0.00 | 4667.56 | 17.86 | 0.00 | 3531.38 | 0.00 |
February | 42139.73 | 07-FEB-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4667.56 | 17.86 | 0.00 | 4797.95 | 0.00 |
March | 45328.10 | 22-MAR-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4667.56 | 17.86 | 0.00 | 7828.45 | 0.00 |
April | 50911.70 | 19-APR-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 4667.56 | 17.86 | 0.00 | 16342.08 | 0.00 |
May | 57468.41 | 19-MAY-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5104.98 | 17.86 | 0.00 | 19684.45 | 0.00 |
June | 64193.69 | 02-JUN-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 6538.02 | 17.86 | 0.00 | 28776.45 | 0.00 |
July | 63932.68 | 03-JUL-17:19 | 2863.03 | 20336.83 | 0.00 | 0.00 | 6449.43 | 17.86 | 0.00 | 28203.19 | 0.00 |
August | 62440.64 | 03-AUG-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 6566.62 | 17.86 | 0.00 | 25936.53 | 0.00 |
September | 59912.66 | 15-SEP-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 6093.07 | 17.86 | 0.00 | 23878.17 | 0.00 |
October | 57368.59 | 05-OCT-10:39 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5128.40 | 17.86 | 0.00 | 19157.62 | 0.00 |
November | 46569.88 | 10-NOV-11:50 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4667.56 | 17.86 | 0.00 | 8978.37 | 0.00 |
December | 39039.45 | 26-DEC-11:09 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5508.68 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39039.45 | 2488.87 | 20336.83 | 0.00 | 0.00 | 4667.56 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64193.69 | 3050.12 | 24359.61 | 2175.41 | 0.00 | 6566.62 | 17.86 | 0.00 | 28776.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 67997.56 | 28-JAN-06:10 | 0.00 | 26080.35 | 26-JAN-19:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 69984.95 | 03-FEB-06:00 | 0.00 | 26012.75 | 03-FEB-07:00 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 67791.93 | 02-MAR-06:10 | 0.00 | 25171.13 | 01-MAR-19:30 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 29047.41 | 12-APR-05:00 | 0.00 | 21944.01 | 03-APR-06:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 4398.88 | 02-MAY-05:00 | 0.00 | 17761.71 | 01-MAY-06:00 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 17356.31 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17062.18 | 03-JUL-06:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 17073.33 | 30-AUG-18:49 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 4908.49 | 30-SEP-05:00 | 0.00 | 17346.23 | 29-SEP-18:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 12899.64 | 25-OCT-05:10 | 0.00 | 18034.39 | 30-OCT-06:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 49271.05 | 28-NOV-06:10 | 0.00 | 22323.62 | 30-NOV-19:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 68442.91 | 28-DEC-06:10 | 0.00 | 24999.80 | 28-DEC-07:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 17062.18 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 69984.95 | 0.00 | 26080.35 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 29.57 | 0.00 | 29.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 29.86 | 0.00 | 29.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 29.97 | 0.00 | 29.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 30.85 | 0.00 | 30.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 31.00 | 0.00 | 31.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 31.22 | 0.00 | 31.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 31.36 | 0.00 | 31.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 31.36 | 0.00 | 31.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 31.32 | 0.00 | 31.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 30.99 | 0.00 | 30.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 30.33 | 0.00 | 30.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 29.56 | 0.00 | 29.56 |
Annual Sum or Average | 0.00 | 0.00 | 172.33 | 31.13 | 0.00 | 31.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 29.56 | 0.00 | 29.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 31.36 | 0.00 | 31.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 584.33 | 21.29 | 71.50 | 21.11 | 71.50 | 20.96 |
February | 489.83 | 21.72 | 45.00 | 21.55 | 45.00 | 21.40 |
March | 447.33 | 21.88 | 34.00 | 21.73 | 33.83 | 21.60 |
April | 181.33 | 22.37 | 157.33 | 23.10 | 2.83 | 23.07 |
May | 46.67 | 22.94 | 419.17 | 23.98 | 2.50 | 23.98 |
June | 22.67 | 24.51 | 551.67 | 24.21 | 18.50 | 24.22 |
July | 224.17 | 24.34 | 609.00 | 24.22 | 224.17 | 24.25 |
August | 111.83 | 24.37 | 612.00 | 24.20 | 111.83 | 24.22 |
September | 133.17 | 23.91 | 556.17 | 24.04 | 117.83 | 24.05 |
October | 164.00 | 22.55 | 411.00 | 23.59 | 49.83 | 23.62 |
November | 396.50 | 21.46 | 80.33 | 21.62 | 26.50 | 21.49 |
December | 602.50 | 21.29 | 82.00 | 21.09 | 82.00 | 20.92 |
Annual Sum or Average | 3404.33 | 22.02 | 3629.17 | 22.93 | 786.33 | 22.91 |
Minimum of Months | 22.67 | 21.29 | 34.00 | 21.09 | 2.50 | 20.92 |
Maximum of Months | 602.50 | 24.51 | 612.00 | 24.22 | 224.17 | 24.25 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.33 | 20.08 | 191.33 | 20.78 | 80.67 | 20.63 |
February | 319.83 | 20.66 | 268.50 | 22.19 | 82.50 | 22.12 |
March | 344.00 | 21.95 | 355.00 | 23.50 | 129.67 | 23.68 |
April | 397.50 | 25.25 | 513.17 | 25.52 | 342.83 | 25.65 |
May | 501.83 | 25.99 | 602.00 | 25.95 | 498.33 | 25.97 |
June | 567.83 | 26.05 | 592.00 | 26.05 | 567.83 | 26.05 |
July | 609.00 | 26.06 | 609.00 | 26.06 | 609.00 | 26.06 |
August | 611.67 | 26.05 | 612.00 | 26.05 | 611.67 | 26.05 |
September | 558.33 | 25.98 | 585.83 | 25.95 | 556.33 | 25.96 |
October | 467.33 | 25.72 | 570.00 | 25.62 | 444.50 | 25.72 |
November | 369.50 | 22.02 | 329.00 | 23.33 | 145.83 | 23.62 |
December | 441.83 | 19.73 | 217.67 | 20.45 | 98.00 | 20.25 |
Annual Sum or Average | 5625.00 | 24.17 | 5445.50 | 24.78 | 4167.17 | 24.99 |
Minimum of Months | 319.83 | 19.73 | 191.33 | 20.45 | 80.67 | 20.25 |
Maximum of Months | 611.67 | 26.06 | 612.00 | 26.06 | 611.67 | 26.06 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.40284 | 27.55251 | -0.2925 | 8.42972 |
February | 551.00000 | 21.96872 | 23.81760 | -0.1808 | 7.83745 |
March | 612.00000 | 22.44548 | 22.26442 | -0.0716 | 7.39896 |
April | 590.00000 | 23.51241 | 24.47439 | 0.24182 | 7.58492 |
May | 611.00000 | 23.99126 | 32.83470 | -0.3957 | 9.09857 |
June | 592.00000 | 24.18260 | 37.76769 | -0.2474 | 6.69778 |
July | 609.00000 | 24.18096 | 53.80694 | -0.1220 | 5.63883 |
August | 612.00000 | 24.16340 | 48.56913 | -0.1617 | 5.87119 |
September | 590.00000 | 24.00488 | 47.28734 | -0.2253 | 6.70487 |
October | 610.00000 | 23.57415 | 41.15976 | 0.41023 | 9.66594 |
November | 591.00000 | 22.27960 | 27.97272 | -0.0368 | 7.62574 |
December | 609.00000 | 21.32132 | 24.37770 | -0.3292 | 8.87295 |
Annual Sum or Average | 7187.00000 | 23.09078 | 34.40856 | -0.1176 | 7.62180 |
Minimum of Months | 551.00000 | 21.32132 | 22.26442 | -0.3957 | 5.63883 |
Maximum of Months | 612.00000 | 24.18260 | 53.80694 | 0.41023 | 9.66594 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.17768 | 33.07715 | -0.0809 | 10.09854 |
February | 551.00000 | 22.32670 | 29.04462 | 0.15412 | 12.59205 |
March | 612.00000 | 23.22757 | 27.32639 | 0.35726 | 14.87970 |
April | 590.00000 | 25.15130 | 27.66003 | 0.85004 | 23.63743 |
May | 611.00000 | 25.87343 | 33.74427 | 0.52012 | 12.20637 |
June | 592.00000 | 26.04463 | 37.80548 | 0.65919 | 14.67242 |
July | 609.00000 | 26.05583 | 50.79153 | 0.78503 | 18.37400 |
August | 612.00000 | 26.04825 | 46.54427 | 0.74512 | 17.13946 |
September | 590.00000 | 25.89110 | 45.88905 | 0.67630 | 15.91700 |
October | 610.00000 | 25.27195 | 41.13670 | 1.01795 | 29.10851 |
November | 591.00000 | 22.86691 | 32.21028 | 0.34358 | 15.21667 |
December | 609.00000 | 20.91035 | 30.44330 | -0.1523 | 10.44108 |
Annual Sum or Average | 7187.00000 | 24.24543 | 36.36896 | 0.49091 | 16.20606 |
Minimum of Months | 551.00000 | 20.91035 | 27.32639 | -0.1523 | 10.09854 |
Maximum of Months | 612.00000 | 26.05583 | 50.79153 | 1.01795 | 29.10851 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.128195E+09 | 43373560.20 | 10.83 | 0.126372E+09 | 1823125.73 | 0.00 | 0.21 | 03-JAN-14:00 | 0.00 | 01-JAN-00:02 | 8102.57 | 03-JAN-14:00 | 8102.57 | 03-JAN-14:00 | 419.12 | 12-JAN-14:00 | 2682.58 | 03-JAN-14:00 | 0.00 | 01-JAN-00:02 |
February | 0.169096E+10 | 0.555987E+09 | 71.50 | 0.169047E+10 | 491637.03 | 0.00 | 0.41 | 06-FEB-14:00 | 0.00 | 01-FEB-00:02 | 16464.45 | 06-FEB-14:00 | 16464.45 | 06-FEB-14:00 | 93.02 | 14-FEB-13:55 | 5193.62 | 06-FEB-14:00 | 0.00 | 01-FEB-00:02 |
March | 0.444141E+10 | 0.144267E+10 | 154.08 | 0.444110E+10 | 307675.07 | 0.00 | 0.54 | 14-MAR-17:06 | 0.00 | 01-MAR-00:02 | 22791.17 | 14-MAR-17:06 | 22791.17 | 14-MAR-17:06 | 52.74 | 03-MAR-18:50 | 6941.37 | 14-MAR-17:06 | 0.00 | 01-MAR-00:02 |
April | 0.228452E+11 | 0.698141E+10 | 353.56 | 0.224355E+11 | 0.409733E+09 | 0.00 | 0.87 | 21-APR-12:55 | 0.00 | 01-APR-00:01 | 39147.30 | 21-APR-12:55 | 39147.30 | 21-APR-12:55 | 5283.80 | 18-APR-18:00 | 11478.31 | 21-APR-12:55 | 0.00 | 01-APR-00:01 |
May | 0.438033E+11 | 0.130924E+11 | 496.62 | 0.412572E+11 | 0.254617E+10 | 0.00 | 1.00 | 19-MAY-11:02 | 0.00 | 01-MAY-00:01 | 50764.40 | 19-MAY-11:55 | 47600.30 | 19-MAY-17:03 | 13884.29 | 24-MAY-11:30 | 14723.86 | 19-MAY-11:55 | 0.00 | 01-MAY-00:01 |
June | 0.624312E+11 | 0.187748E+11 | 539.50 | 0.577033E+11 | 0.472795E+10 | 0.00 | 1.00 | 01-JUN-17:03 | 0.00 | 01-JUN-00:01 | 57166.69 | 14-JUN-17:05 | 57166.69 | 14-JUN-17:05 | 19764.68 | 19-JUN-18:00 | 18768.22 | 02-JUN-17:08 | 0.00 | 01-JUN-00:01 |
July | 0.785379E+11 | 0.222908E+11 | 570.74 | 0.583405E+11 | 0.201974E+11 | 0.00 | 1.00 | 01-JUL-11:23 | 0.00 | 01-JUL-00:01 | 68529.92 | 21-JUL-18:00 | 63267.97 | 03-JUL-04:01 | 35486.40 | 22-JUL-05:03 | 18586.98 | 26-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.660236E+11 | 0.191056E+11 | 552.80 | 0.533714E+11 | 0.126522E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 | 63895.27 | 02-AUG-11:55 | 54481.63 | 07-AUG-17:10 | 30255.33 | 02-AUG-05:03 | 17181.61 | 03-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 0.524868E+11 | 0.151087E+11 | 484.95 | 0.416678E+11 | 0.108190E+11 | 0.00 | 1.00 | 01-SEP-11:02 | 0.00 | 01-SEP-00:01 | 62683.33 | 22-SEP-04:01 | 47034.06 | 19-SEP-17:10 | 33596.34 | 22-SEP-04:01 | 16223.02 | 22-SEP-04:01 | 0.00 | 01-SEP-00:01 |
October | 0.242183E+11 | 0.726310E+10 | 347.85 | 0.200649E+11 | 0.415335E+10 | 0.00 | 1.00 | 03-OCT-11:33 | 0.00 | 01-OCT-00:01 | 52471.71 | 04-OCT-17:20 | 40815.19 | 04-OCT-17:10 | 19121.47 | 03-OCT-20:00 | 14151.15 | 04-OCT-17:10 | 0.00 | 01-OCT-00:01 |
November | 0.276647E+10 | 0.894853E+09 | 99.67 | 0.260114E+10 | 0.165334E+09 | 0.00 | 0.57 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 | 24095.50 | 09-NOV-14:00 | 22750.98 | 09-NOV-14:00 | 3784.21 | 03-NOV-11:53 | 7286.80 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 401973.01 | 139216.80 | 0.17 | 401973.01 | 0.00 | 0.00 | 0.02 | 08-DEC-14:00 | 0.00 | 01-DEC-00:03 | 680.15 | 08-DEC-14:00 | 680.15 | 08-DEC-14:00 | 0.00 | 08-DEC-14:00 | 235.54 | 08-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.359374E+12 | 0.105554E+12 | 3682.28 | 0.303700E+12 | 0.556737E+11 | 0.00 | ||||||||||||||
Minimum of Months | 401973.01 | 139216.80 | 0.17 | 401973.01 | 0.00 | 0.00 | 0.02 | 0.00 | 680.15 | 680.15 | 0.00 | 235.54 | 0.00 | |||||||
Maximum of Months | 0.785379E+11 | 0.222908E+11 | 570.74 | 0.583405E+11 | 0.201974E+11 | 0.00 | 1.00 | 0.00 | 68529.92 | 63267.97 | 35486.40 | 18768.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.165426E+09 | 50235026.38 | 20.59 | 0.154699E+09 | 10726329.70 | 0.00 | 0.29 | 03-JAN-17:20 | 0.00 | 01-JAN-00:02 | 5242.85 | 03-JAN-17:20 | 5242.85 | 03-JAN-17:20 | 859.84 | 13-JAN-04:10 | 1551.81 | 03-JAN-17:20 | 0.00 | 01-JAN-00:02 |
February | 0.160625E+10 | 0.471543E+09 | 103.41 | 0.158675E+10 | 19504788.59 | 0.00 | 1.00 | 07-FEB-04:42 | 0.00 | 01-FEB-00:02 | 22194.06 | 07-FEB-04:42 | 20387.88 | 07-FEB-04:42 | 1875.35 | 28-FEB-04:10 | 5420.17 | 07-FEB-04:42 | 0.00 | 01-FEB-00:02 |
March | 0.371616E+10 | 0.107708E+10 | 197.46 | 0.368820E+10 | 27958212.39 | 0.00 | 1.00 | 16-MAR-03:52 | 0.00 | 01-MAR-00:02 | 22194.06 | 16-MAR-03:52 | 21637.39 | 16-MAR-03:52 | 921.85 | 14-MAR-03:08 | 5420.17 | 16-MAR-03:52 | 0.00 | 01-MAR-00:02 |
April | 0.162283E+11 | 0.432608E+10 | 411.64 | 0.158179E+11 | 0.410408E+09 | 0.00 | 1.00 | 02-APR-03:02 | 0.00 | 01-APR-00:01 | 44439.10 | 29-APR-03:11 | 44439.10 | 03-APR-03:22 | 16319.44 | 30-APR-03:11 | 10844.33 | 03-APR-03:22 | 0.00 | 01-APR-00:01 |
May | 0.306826E+11 | 0.794901E+10 | 549.60 | 0.287844E+11 | 0.189829E+10 | 0.00 | 1.00 | 01-MAY-03:11 | 0.00 | 01-MAY-00:01 | 44439.10 | 01-MAY-03:52 | 44439.10 | 20-MAY-00:53 | 19303.27 | 29-MAY-03:11 | 10844.33 | 01-MAY-03:52 | 0.00 | 01-MAY-00:01 |
June | 0.440916E+11 | 0.116465E+11 | 599.92 | 0.406227E+11 | 0.346886E+10 | 0.00 | 1.00 | 01-JUN-00:53 | 0.00 | 01-JUN-00:01 | 44439.10 | 17-JUN-03:36 | 44439.10 | 02-JUN-00:53 | 19018.59 | 04-JUN-03:32 | 11041.03 | 15-JUN-01:32 | 0.00 | 01-JUN-00:01 |
July | 0.569108E+11 | 0.141042E+11 | 634.90 | 0.414124E+11 | 0.154984E+11 | 0.00 | 1.00 | 01-JUL-00:53 | 0.00 | 01-JUL-00:01 | 48987.35 | 21-JUL-11:00 | 43958.86 | 03-JUL-01:22 | 33140.32 | 21-JUL-03:31 | 11147.42 | 03-JUL-01:22 | 0.00 | 01-JUL-00:01 |
August | 0.471419E+11 | 0.119047E+11 | 618.27 | 0.374210E+11 | 0.972089E+10 | 0.00 | 1.00 | 01-AUG-00:42 | 0.00 | 01-AUG-00:01 | 47216.21 | 02-AUG-03:32 | 43617.79 | 23-AUG-00:42 | 27353.43 | 02-AUG-03:32 | 11032.87 | 02-AUG-03:32 | 0.00 | 01-AUG-00:01 |
September | 0.367918E+11 | 0.922448E+10 | 539.27 | 0.282599E+11 | 0.853188E+10 | 0.00 | 1.00 | 01-SEP-00:53 | 0.00 | 01-SEP-00:01 | 46923.40 | 22-SEP-01:22 | 35289.16 | 11-SEP-01:32 | 29731.72 | 22-SEP-03:21 | 11013.00 | 22-SEP-01:22 | 0.00 | 01-SEP-00:01 |
October | 0.183676E+11 | 0.482082E+10 | 417.62 | 0.144370E+11 | 0.393060E+10 | 0.00 | 1.00 | 01-OCT-12:30 | 0.00 | 01-OCT-00:01 | 44439.10 | 05-OCT-02:52 | 44286.98 | 02-OCT-00:18 | 23401.17 | 17-OCT-03:31 | 10844.33 | 02-OCT-00:18 | 0.00 | 01-OCT-00:01 |
November | 0.259782E+10 | 0.747864E+09 | 149.48 | 0.233160E+10 | 0.266221E+09 | 0.00 | 1.00 | 03-NOV-03:41 | 0.00 | 01-NOV-00:01 | 44439.10 | 03-NOV-03:41 | 38710.58 | 09-NOV-04:52 | 21098.11 | 03-NOV-03:41 | 10844.33 | 03-NOV-03:41 | 0.00 | 01-NOV-00:01 |
December | 34095643.73 | 10631160.93 | 11.35 | 32133938.48 | 1961705.26 | 0.00 | 0.19 | 01-DEC-04:10 | 0.00 | 01-DEC-00:03 | 3425.66 | 01-DEC-04:10 | 2500.47 | 01-DEC-04:10 | 925.19 | 01-DEC-04:10 | 1037.52 | 01-DEC-04:10 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.258334E+12 | 0.663331E+11 | 4253.51 | 0.214549E+12 | 0.437857E+11 | 0.00 | ||||||||||||||
Minimum of Months | 34095643.73 | 10631160.93 | 11.35 | 32133938.48 | 1961705.26 | 0.00 | 0.19 | 0.00 | 3425.66 | 2500.47 | 859.84 | 1037.52 | 0.00 | |||||||
Maximum of Months | 0.569108E+11 | 0.141042E+11 | 634.90 | 0.414124E+11 | 0.154984E+11 | 0.00 | 1.00 | 0.00 | 48987.35 | 44439.10 | 33140.32 | 11147.42 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.09 | 89.45 | 75.63 | 165.05 | 317.55 | 0.00 | 0.00 | 0.00 |
February | 221.56 | 126.34 | 95.23 | 258.79 | 280.91 | 0.00 | 0.00 | 0.00 |
March | 273.10 | 150.37 | 122.73 | 347.91 | 236.07 | 0.00 | 0.00 | 0.00 |
April | 329.22 | 182.60 | 146.62 | 498.17 | 143.07 | 0.00 | 0.00 | 0.00 |
May | 339.38 | 184.37 | 155.01 | 575.98 | 89.48 | 0.00 | 0.00 | 0.00 |
June | 339.53 | 188.79 | 150.73 | 653.31 | 50.10 | 0.00 | 0.00 | 0.00 |
July | 304.68 | 159.29 | 145.39 | 588.44 | 41.71 | 0.00 | 0.00 | 0.00 |
August | 290.23 | 148.62 | 141.61 | 537.09 | 57.69 | 0.00 | 0.00 | 0.00 |
September | 287.95 | 164.43 | 123.52 | 495.02 | 104.58 | 0.00 | 0.00 | 0.00 |
October | 220.40 | 118.72 | 101.68 | 316.94 | 171.73 | 0.00 | 0.00 | 0.00 |
November | 197.34 | 114.62 | 82.72 | 224.02 | 276.15 | 0.00 | 0.00 | 0.00 |
December | 165.21 | 87.55 | 77.66 | 155.72 | 348.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.17 | 142.85 | 118.32 | 401.82 | 175.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.09 | 87.55 | 75.63 | 155.72 | 41.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 339.53 | 188.79 | 155.01 | 653.31 | 348.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.85 | 443.91 | 141.93 | 815.63 | 419.98 | 0.00 | 0.00 | 0.00 |
February | 551.19 | 390.90 | 160.29 | 779.90 | 379.66 | 0.00 | 0.00 | 0.00 |
March | 431.19 | 244.29 | 186.90 | 622.81 | 338.79 | 0.00 | 0.00 | 0.00 |
April | 300.45 | 112.79 | 187.67 | 485.30 | 216.59 | 0.00 | 0.00 | 0.00 |
May | 213.21 | 31.27 | 181.94 | 384.09 | 134.09 | 0.00 | 0.00 | 0.00 |
June | 182.37 | 11.47 | 170.89 | 408.70 | 72.92 | 0.00 | 0.00 | 0.00 |
July | 185.20 | 16.42 | 168.78 | 413.92 | 60.36 | 0.00 | 0.00 | 0.00 |
August | 233.78 | 59.40 | 174.39 | 487.02 | 84.61 | 0.00 | 0.00 | 0.00 |
September | 370.22 | 192.35 | 177.87 | 699.85 | 154.24 | 0.00 | 0.00 | 0.00 |
October | 508.19 | 345.27 | 162.92 | 818.39 | 237.76 | 0.00 | 0.00 | 0.00 |
November | 611.64 | 467.84 | 143.80 | 882.31 | 368.68 | 0.00 | 0.00 | 0.00 |
December | 601.44 | 451.85 | 149.59 | 819.59 | 455.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 396.98 | 229.71 | 167.28 | 633.77 | 242.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.37 | 11.47 | 141.93 | 384.09 | 60.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 611.64 | 467.84 | 187.67 | 882.31 | 455.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.34 | 98.27 | 76.07 | 193.22 | 331.66 | 0.00 | 0.00 | 0.00 |
February | 196.24 | 104.13 | 92.11 | 231.70 | 299.16 | 0.00 | 0.00 | 0.00 |
March | 267.77 | 143.58 | 124.19 | 350.16 | 251.73 | 0.00 | 0.00 | 0.00 |
April | 307.28 | 165.75 | 141.53 | 468.89 | 154.38 | 0.00 | 0.00 | 0.00 |
May | 331.61 | 177.47 | 154.14 | 566.67 | 96.33 | 0.00 | 0.00 | 0.00 |
June | 322.67 | 173.25 | 149.41 | 624.86 | 52.50 | 0.00 | 0.00 | 0.00 |
July | 286.56 | 142.38 | 144.17 | 557.93 | 43.13 | 0.00 | 0.00 | 0.00 |
August | 277.46 | 141.36 | 136.10 | 516.00 | 60.80 | 0.00 | 0.00 | 0.00 |
September | 284.86 | 159.02 | 125.83 | 498.87 | 112.68 | 0.00 | 0.00 | 0.00 |
October | 245.44 | 143.69 | 101.75 | 368.89 | 179.12 | 0.00 | 0.00 | 0.00 |
November | 204.79 | 124.60 | 80.18 | 251.87 | 291.74 | 0.00 | 0.00 | 0.00 |
December | 165.17 | 89.67 | 75.49 | 171.06 | 367.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.56 | 138.69 | 116.87 | 400.72 | 186.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.17 | 89.67 | 75.49 | 171.06 | 43.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.61 | 177.47 | 154.14 | 624.86 | 367.17 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442168E+09 | 0.239590E+09 | 0.202578E+09 | 0.442082E+09 | 0.850533E+09 |
February | 0.536009E+09 | 0.305637E+09 | 0.230372E+09 | 0.626065E+09 | 0.679570E+09 |
March | 0.731465E+09 | 0.402751E+09 | 0.328713E+09 | 0.931839E+09 | 0.632284E+09 |
April | 0.853344E+09 | 0.473295E+09 | 0.380050E+09 | 0.129127E+10 | 0.370838E+09 |
May | 0.908999E+09 | 0.493811E+09 | 0.415188E+09 | 0.154271E+10 | 0.239654E+09 |
June | 0.880050E+09 | 0.489349E+09 | 0.390701E+09 | 0.169338E+10 | 0.129860E+09 |
July | 0.816055E+09 | 0.426640E+09 | 0.389415E+09 | 0.157609E+10 | 0.111729E+09 |
August | 0.777364E+09 | 0.398072E+09 | 0.379292E+09 | 0.143855E+10 | 0.154520E+09 |
September | 0.746366E+09 | 0.426204E+09 | 0.320162E+09 | 0.128309E+10 | 0.271063E+09 |
October | 0.590314E+09 | 0.317974E+09 | 0.272340E+09 | 0.848905E+09 | 0.459966E+09 |
November | 0.511514E+09 | 0.297102E+09 | 0.214412E+09 | 0.580652E+09 | 0.715769E+09 |
December | 0.442501E+09 | 0.234486E+09 | 0.208016E+09 | 0.417093E+09 | 0.933753E+09 |
Annual Sum or Average | 0.823615E+10 | 0.450491E+10 | 0.373124E+10 | 0.126717E+11 | 0.554954E+10 |
Minimum of Months | 0.442168E+09 | 0.234486E+09 | 0.202578E+09 | 0.417093E+09 | 0.111729E+09 |
Maximum of Months | 0.908999E+09 | 0.493811E+09 | 0.415188E+09 | 0.169338E+10 | 0.933753E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156913E+10 | 0.118897E+10 | 0.380156E+09 | 0.218457E+10 | 0.112488E+10 |
February | 0.133344E+10 | 0.945666E+09 | 0.387776E+09 | 0.188674E+10 | 0.918467E+09 |
March | 0.115491E+10 | 0.654312E+09 | 0.500594E+09 | 0.166813E+10 | 0.907408E+09 |
April | 0.778778E+09 | 0.292345E+09 | 0.486433E+09 | 0.125791E+10 | 0.561405E+09 |
May | 0.571068E+09 | 83748796.49 | 0.487320E+09 | 0.102874E+10 | 0.359135E+09 |
June | 0.472697E+09 | 29742386.48 | 0.442954E+09 | 0.105934E+10 | 0.189008E+09 |
July | 0.496037E+09 | 43978708.57 | 0.452058E+09 | 0.110866E+10 | 0.161672E+09 |
August | 0.626166E+09 | 0.159088E+09 | 0.467077E+09 | 0.130444E+10 | 0.226607E+09 |
September | 0.959621E+09 | 0.498569E+09 | 0.461052E+09 | 0.181401E+10 | 0.399796E+09 |
October | 0.136113E+10 | 0.924764E+09 | 0.436369E+09 | 0.219197E+10 | 0.636826E+09 |
November | 0.158537E+10 | 0.121263E+10 | 0.372737E+09 | 0.228694E+10 | 0.955630E+09 |
December | 0.161091E+10 | 0.121025E+10 | 0.400659E+09 | 0.219518E+10 | 0.122099E+10 |
Annual Sum or Average | 0.125192E+11 | 0.724407E+10 | 0.527518E+10 | 0.199866E+11 | 0.766182E+10 |
Minimum of Months | 0.472697E+09 | 29742386.48 | 0.372737E+09 | 0.102874E+10 | 0.161672E+09 |
Maximum of Months | 0.161091E+10 | 0.121263E+10 | 0.500594E+09 | 0.228694E+10 | 0.122099E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.466949E+09 | 0.263195E+09 | 0.203754E+09 | 0.517516E+09 | 0.888317E+09 |
February | 0.474741E+09 | 0.251906E+09 | 0.222834E+09 | 0.560539E+09 | 0.723720E+09 |
March | 0.717199E+09 | 0.384564E+09 | 0.332635E+09 | 0.937881E+09 | 0.674237E+09 |
April | 0.796478E+09 | 0.429627E+09 | 0.366851E+09 | 0.121536E+10 | 0.400166E+09 |
May | 0.888178E+09 | 0.475324E+09 | 0.412854E+09 | 0.151776E+10 | 0.258001E+09 |
June | 0.836356E+09 | 0.449072E+09 | 0.387284E+09 | 0.161964E+10 | 0.136086E+09 |
July | 0.767517E+09 | 0.381361E+09 | 0.386155E+09 | 0.149436E+10 | 0.115521E+09 |
August | 0.743160E+09 | 0.378618E+09 | 0.364542E+09 | 0.138205E+10 | 0.162853E+09 |
September | 0.738344E+09 | 0.412181E+09 | 0.326163E+09 | 0.129308E+10 | 0.292067E+09 |
October | 0.657375E+09 | 0.384850E+09 | 0.272524E+09 | 0.988046E+09 | 0.479751E+09 |
November | 0.530809E+09 | 0.322970E+09 | 0.207839E+09 | 0.652855E+09 | 0.756201E+09 |
December | 0.442383E+09 | 0.240185E+09 | 0.202197E+09 | 0.458176E+09 | 0.983426E+09 |
Annual Sum or Average | 0.805949E+10 | 0.437385E+10 | 0.368563E+10 | 0.126372E+11 | 0.587035E+10 |
Minimum of Months | 0.442383E+09 | 0.240185E+09 | 0.202197E+09 | 0.458176E+09 | 0.115521E+09 |
Maximum of Months | 0.888178E+09 | 0.475324E+09 | 0.412854E+09 | 0.161964E+10 | 0.983426E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1130.60 | 1025.90 | 925.27 | 631.63 | 293.64 | 0.00 | 0.00 |
February | 1229.09 | 918.42 | 968.99 | 621.37 | 347.63 | 0.00 | 0.00 |
March | 1279.64 | 785.34 | 972.06 | 538.24 | 433.82 | 0.00 | 0.00 |
April | 1419.85 | 481.53 | 936.96 | 461.14 | 475.82 | 0.00 | 0.00 |
May | 1511.85 | 305.01 | 884.20 | 393.10 | 491.10 | 0.00 | 0.00 |
June | 1681.89 | 170.55 | 844.56 | 373.52 | 471.04 | 0.00 | 0.00 |
July | 1555.59 | 140.50 | 776.44 | 318.09 | 458.34 | 0.00 | 0.00 |
August | 1533.65 | 196.64 | 801.48 | 349.38 | 452.10 | 0.00 | 0.00 |
September | 1677.83 | 355.59 | 943.03 | 515.80 | 427.23 | 0.00 | 0.00 |
October | 1489.74 | 574.13 | 974.02 | 607.67 | 366.35 | 0.00 | 0.00 |
November | 1319.84 | 898.22 | 1013.77 | 707.06 | 306.71 | 0.00 | 0.00 |
December | 1091.27 | 1116.55 | 931.82 | 629.08 | 302.74 | 0.00 | 0.00 |
Annual Sum or Average | 1410.30 | 579.06 | 913.71 | 511.25 | 402.46 | 0.00 | 0.00 |
Minimum of Months | 1091.27 | 140.50 | 776.44 | 318.09 | 293.64 | 0.00 | 0.00 |
Maximum of Months | 1681.89 | 1116.55 | 1013.77 | 707.06 | 491.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302820E+10 | 0.274776E+10 | 0.247825E+10 | 0.169176E+10 | 0.786488E+09 | 0.00 | 0.00 |
February | 0.297342E+10 | 0.222184E+10 | 0.234419E+10 | 0.150321E+10 | 0.840982E+09 | 0.00 | 0.00 |
March | 0.342738E+10 | 0.210346E+10 | 0.260357E+10 | 0.144163E+10 | 0.116194E+10 | 0.00 | 0.00 |
April | 0.368026E+10 | 0.124814E+10 | 0.242860E+10 | 0.119527E+10 | 0.123333E+10 | 0.00 | 0.00 |
May | 0.404935E+10 | 0.816929E+09 | 0.236825E+10 | 0.105288E+10 | 0.131536E+10 | 0.00 | 0.00 |
June | 0.435946E+10 | 0.442054E+09 | 0.218910E+10 | 0.968164E+09 | 0.122094E+10 | 0.00 | 0.00 |
July | 0.416648E+10 | 0.376305E+09 | 0.207961E+10 | 0.851980E+09 | 0.122763E+10 | 0.00 | 0.00 |
August | 0.410773E+10 | 0.526686E+09 | 0.214669E+10 | 0.935778E+09 | 0.121091E+10 | 0.00 | 0.00 |
September | 0.434893E+10 | 0.921688E+09 | 0.244433E+10 | 0.133695E+10 | 0.110738E+10 | 0.00 | 0.00 |
October | 0.399012E+10 | 0.153775E+10 | 0.260882E+10 | 0.162759E+10 | 0.981233E+09 | 0.00 | 0.00 |
November | 0.342103E+10 | 0.232818E+10 | 0.262769E+10 | 0.183270E+10 | 0.794988E+09 | 0.00 | 0.00 |
December | 0.292285E+10 | 0.299057E+10 | 0.249579E+10 | 0.168492E+10 | 0.810872E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444752E+11 | 0.182614E+11 | 0.288149E+11 | 0.161228E+11 | 0.126921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292285E+10 | 0.376305E+09 | 0.207961E+10 | 0.851980E+09 | 0.786488E+09 | 0.00 | 0.00 |
Maximum of Months | 0.435946E+10 | 0.299057E+10 | 0.262769E+10 | 0.183270E+10 | 0.131536E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639231E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167143022.3 | 81.22 | 0.00 | 0.00 |
February | 0.578255E+10 | -0.563431E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148236614.2 | 81.21 | 0.00 | 0.00 |
March | 0.645545E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161592625.5 | 81.22 | 0.00 | 0.00 |
April | 0.619467E+10 | -0.604348E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151188826.0 | 81.21 | 0.00 | 0.00 |
May | 0.641456E+10 | -0.626021E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154348184.6 | 81.21 | 0.00 | 0.00 |
June | 0.623558E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148995846.2 | 81.21 | 0.00 | 0.00 |
July | 0.637089E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153797141.9 | 81.21 | 0.00 | 0.00 |
August | 0.644907E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153851945.6 | 81.21 | 0.00 | 0.00 |
September | 0.619403E+10 | -0.604483E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149201980.1 | 81.21 | 0.00 | 0.00 |
October | 0.637964E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155792580.3 | 81.21 | 0.00 | 0.00 |
November | 0.618179E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157185843.6 | 81.22 | 0.00 | 0.00 |
December | 0.638494E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167863854.9 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754355E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186920E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578255E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167863854.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645545E+10 | -0.563431E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148236614.2 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.222960E+11 | -0.213397E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -956288517.4 | 58.99 | 0.00 | 0.00 |
February | 0.201344E+11 | -0.192955E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -838946910.5 | 58.99 | 0.00 | 0.00 |
March | 0.216711E+11 | -0.207658E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -905345520.0 | 58.98 | 0.00 | 0.00 |
April | 0.194382E+11 | -0.186094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -828821611.1 | 58.99 | 0.00 | 0.00 |
May | 0.185216E+11 | -0.176822E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839464693.5 | 59.00 | 0.00 | 0.00 |
June | 0.166443E+11 | -0.158358E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -808485527.1 | 58.98 | 0.00 | 0.00 |
July | 0.162146E+11 | -0.153806E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834025809.8 | 58.98 | 0.00 | 0.00 |
August | 0.164168E+11 | -0.155822E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834591293.5 | 58.99 | 0.00 | 0.00 |
September | 0.165601E+11 | -0.157494E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -810697632.9 | 58.99 | 0.00 | 0.00 |
October | 0.184541E+11 | -0.176016E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -852462138.5 | 58.99 | 0.00 | 0.00 |
November | 0.194567E+11 | -0.185730E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -883686719.8 | 58.99 | 0.00 | 0.00 |
December | 0.214911E+11 | -0.205282E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -962957569.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.227299E+12 | -0.216943E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.103558E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.162146E+11 | -0.213397E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -962957569.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.222960E+11 | -0.153806E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -808485527.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.76 | 0.75 | 01-JAN-08:09 | 1019.80 | 24.95 | 140.50 | 268.67 | 932.10 | 25.21 | 127.67 | 271.17 |
February | 268.33 | 0.76 | 0.75 | 01-FEB-07:49 | 989.51 | 23.61 | 131.00 | 262.00 | 898.15 | 23.77 | 115.33 | 262.00 |
March | 351.83 | 0.76 | 0.75 | 01-MAR-06:00 | 779.17 | 19.60 | 78.83 | 325.17 | 911.16 | 20.14 | 95.67 | 327.33 |
April | 373.83 | 0.76 | 0.75 | 01-APR-06:49 | 833.89 | 19.57 | 74.50 | 345.50 | 787.79 | 19.59 | 53.50 | 340.83 |
May | 408.83 | 0.76 | 0.75 | 01-MAY-06:10 | 900.81 | 19.26 | 54.00 | 379.33 | 932.76 | 19.33 | 32.17 | 373.17 |
June | 398.00 | 0.76 | 0.75 | 01-JUN-06:10 | 593.08 | 20.85 | 54.17 | 371.00 | 944.62 | 19.24 | 13.83 | 362.17 |
July | 400.17 | 0.76 | 0.75 | 01-JUL-06:19 | 601.40 | 19.56 | 40.33 | 375.50 | 817.19 | 19.19 | 25.33 | 364.50 |
August | 377.83 | 0.76 | 0.75 | 01-AUG-06:19 | 829.96 | 19.44 | 70.83 | 351.00 | 734.52 | 19.41 | 47.50 | 349.83 |
September | 365.83 | 0.77 | 0.75 | 01-SEP-05:00 | 712.23 | 19.40 | 61.00 | 327.67 | 710.63 | 19.46 | 78.00 | 328.33 |
October | 318.83 | 0.76 | 0.75 | 01-OCT-06:00 | 1014.13 | 22.90 | 139.83 | 308.17 | 1025.30 | 22.22 | 115.67 | 308.50 |
November | 295.83 | 0.76 | 0.75 | 01-NOV-12:39 | 896.93 | 24.80 | 129.83 | 283.00 | 975.30 | 24.08 | 110.67 | 278.83 |
December | 289.50 | 0.76 | 0.75 | 01-DEC-07:19 | 939.75 | 25.48 | 152.67 | 275.00 | 941.04 | 25.55 | 145.00 | 274.67 |
Annual Sum or Average | 4125.67 | 0.76 | 827.40 | 21.31 | 1127.50 | 3872.00 | 878.35 | 21.10 | 960.33 | 3841.33 | ||
Minimum of Months | 268.33 | 0.76 | 0.75 | 593.08 | 19.26 | 40.33 | 262.00 | 710.63 | 19.19 | 13.83 | 262.00 | |
Maximum of Months | 408.83 | 0.77 | 0.75 | 1019.80 | 25.48 | 152.67 | 379.33 | 1025.30 | 25.55 | 145.00 | 373.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129994E+11 | 41683.40 | 28-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.854311E+10 | 41448.01 | 03-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594375E+10 | 41333.35 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801302E+09 | 24418.67 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18479007.34 | 4030.71 | 02-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15778149.48 | 4488.97 | 25-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160658E+09 | 17434.27 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620584E+10 | 33760.11 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167907E+11 | 64818.64 | 28-DEC-07:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167907E+11 | 64818.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418553E+10 | 25638.78 | 28-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293131E+10 | 22235.50 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154700E+10 | 26684.33 | 02-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70149543.69 | 7771.38 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160679E+10 | 17166.68 | 28-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.644334E+10 | 27002.19 | 27-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.644334E+10 | 27002.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128195E+09 | 0.126372E+09 | 8102.57 | 03-JAN-14:00 | 8102.57 | 0.00 |
February | 0.00 | 0.00 | 0.169096E+10 | 0.169047E+10 | 16464.45 | 06-FEB-14:00 | 16464.45 | 0.00 |
March | 0.00 | 0.00 | 0.444141E+10 | 0.444110E+10 | 22791.17 | 14-MAR-17:06 | 22791.17 | 0.00 |
April | 0.00 | 0.00 | 0.228452E+11 | 0.224355E+11 | 39147.30 | 21-APR-12:55 | 39147.30 | 0.00 |
May | 0.00 | 0.00 | 0.438033E+11 | 0.412572E+11 | 50764.40 | 19-MAY-11:55 | 45349.47 | 0.00 |
June | 0.00 | 0.00 | 0.624312E+11 | 0.577033E+11 | 57166.69 | 14-JUN-17:05 | 57166.69 | 0.00 |
July | 0.00 | 0.00 | 0.785379E+11 | 0.583405E+11 | 68529.92 | 21-JUL-18:00 | 43403.79 | 0.00 |
August | 0.00 | 0.00 | 0.660236E+11 | 0.533714E+11 | 63895.27 | 02-AUG-11:55 | 42583.02 | 0.00 |
September | 0.00 | 0.00 | 0.524868E+11 | 0.416678E+11 | 62683.33 | 22-SEP-04:01 | 29086.99 | 0.00 |
October | 0.00 | 0.00 | 0.242183E+11 | 0.200649E+11 | 52471.71 | 04-OCT-17:20 | 40006.59 | 0.00 |
November | 0.00 | 0.00 | 0.276647E+10 | 0.260114E+10 | 24095.50 | 09-NOV-14:00 | 22750.98 | 0.00 |
December | 0.00 | 0.00 | 401973.01 | 401973.01 | 680.15 | 08-DEC-14:00 | 680.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.359374E+12 | 0.303700E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 401973.01 | 401973.01 | 680.15 | 680.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.785379E+11 | 0.583405E+11 | 68529.92 | 57166.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.165426E+09 | 0.154699E+09 | 5242.85 | 03-JAN-17:20 | 5242.85 | 0.00 |
February | 0.00 | 0.00 | 0.160625E+10 | 0.158675E+10 | 22194.06 | 07-FEB-04:42 | 20387.88 | 0.00 |
March | 0.00 | 0.00 | 0.371616E+10 | 0.368820E+10 | 22194.06 | 16-MAR-03:52 | 21637.39 | 0.00 |
April | 0.00 | 0.00 | 0.162283E+11 | 0.158179E+11 | 44439.10 | 29-APR-03:11 | 31818.19 | 0.00 |
May | 0.00 | 0.00 | 0.306826E+11 | 0.287844E+11 | 44439.10 | 01-MAY-03:52 | 43601.29 | 0.00 |
June | 0.00 | 0.00 | 0.440916E+11 | 0.406227E+11 | 44439.10 | 17-JUN-03:36 | 39819.69 | 0.00 |
July | 0.00 | 0.00 | 0.569108E+11 | 0.414124E+11 | 48987.35 | 21-JUL-11:00 | 20640.54 | 0.00 |
August | 0.00 | 0.00 | 0.471419E+11 | 0.374210E+11 | 47216.21 | 02-AUG-03:32 | 19862.78 | 0.00 |
September | 0.00 | 0.00 | 0.367918E+11 | 0.282599E+11 | 46923.40 | 22-SEP-01:22 | 17649.78 | 0.00 |
October | 0.00 | 0.00 | 0.183676E+11 | 0.144370E+11 | 44439.10 | 05-OCT-02:52 | 28502.75 | 0.00 |
November | 0.00 | 0.00 | 0.259782E+10 | 0.233160E+10 | 44439.10 | 03-NOV-03:41 | 23340.99 | 0.00 |
December | 0.00 | 0.00 | 34095643.73 | 32133938.48 | 3425.66 | 01-DEC-04:10 | 2500.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.258334E+12 | 0.214549E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 34095643.73 | 32133938.48 | 3425.66 | 2500.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569108E+11 | 0.414124E+11 | 48987.35 | 43601.29 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 8428.33 | 16087.05 | 30-JAN-19:45 |
February | 0.00 | 0.00 | 01-FEB-00:02 | 8437.01 | 16097.81 | 01-FEB-19:27 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 8214.10 | 15800.38 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7641.93 | 14919.73 | 03-APR-18:20 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 7065.55 | 13891.96 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6573.89 | 12789.65 | 01-JUN-06:53 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 6207.97 | 11937.13 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 6283.22 | 11983.38 | 31-AUG-06:57 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 6540.99 | 12759.16 | 29-SEP-18:24 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7035.53 | 13894.13 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7627.85 | 14973.46 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8125.72 | 15813.97 | 28-DEC-07:59 |
Annual Sum or Average | 0.00 | 7342.33 | ||||
Minimum of Months | 0.00 | 0.00 | 6207.97 | 11937.13 | ||
Maximum of Months | 0.00 | 0.00 | 8437.01 | 16097.81 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:02 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184599E+10 | 0.25 | 824.13 | 01-JAN-00:02 | 0.30 |
February | 0.168226E+10 | 0.26 | 824.13 | 01-FEB-00:02 | 0.31 |
March | 0.188426E+10 | 0.26 | 824.13 | 01-MAR-00:02 | 0.31 |
April | 0.194503E+10 | 0.28 | 824.13 | 01-APR-03:20 | 0.30 |
May | 0.208766E+10 | 0.29 | 824.13 | 01-MAY-00:40 | 0.31 |
June | 0.204231E+10 | 0.29 | 824.13 | 01-JUN-00:19 | 0.30 |
July | 0.210749E+10 | 0.29 | 824.13 | 01-JUL-00:12 | 0.30 |
August | 0.210743E+10 | 0.29 | 824.13 | 01-AUG-00:10 | 0.30 |
September | 0.203236E+10 | 0.29 | 824.13 | 01-SEP-00:12 | 0.30 |
October | 0.204663E+10 | 0.28 | 824.13 | 01-OCT-00:55 | 0.30 |
November | 0.182838E+10 | 0.26 | 824.13 | 01-NOV-03:02 | 0.30 |
December | 0.184401E+10 | 0.25 | 824.13 | 01-DEC-00:03 | 0.30 |
Annual Sum or Average | 0.234538E+11 | 0.27 | |||
Minimum of Months | 0.168226E+10 | 0.25 | 824.13 | 0.30 | |
Maximum of Months | 0.210749E+10 | 0.29 | 824.13 | 0.31 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.731735E+10 | 0.84 | 4579.76 | 28-JAN-06:03 | 1.25 |
February | 0.649315E+10 | 0.84 | 4571.22 | 03-FEB-06:03 | 1.24 |
March | 0.706129E+10 | 0.83 | 4567.06 | 02-MAR-06:03 | 1.24 |
April | 0.665384E+10 | 0.81 | 3953.20 | 12-APR-05:03 | 1.14 |
May | 0.684744E+10 | 0.81 | 3444.93 | 19-MAY-11:55 | 1.04 |
June | 0.669967E+10 | 0.81 | 4279.50 | 14-JUN-17:05 | 1.19 |
July | 0.708586E+10 | 0.82 | 4776.00 | 03-JUL-04:01 | 1.26 |
August | 0.694199E+10 | 0.81 | 4353.73 | 03-AUG-11:53 | 1.19 |
September | 0.664723E+10 | 0.80 | 4219.55 | 22-SEP-04:01 | 1.17 |
October | 0.685449E+10 | 0.81 | 3699.73 | 25-OCT-05:03 | 1.09 |
November | 0.684998E+10 | 0.83 | 4292.22 | 28-NOV-06:03 | 1.20 |
December | 0.745494E+10 | 0.85 | 5419.37 | 28-DEC-07:58 | 1.36 |
Annual Sum or Average | 0.829072E+11 | 0.82 | |||
Minimum of Months | 0.649315E+10 | 0.80 | 3444.93 | 1.04 | |
Maximum of Months | 0.745494E+10 | 0.85 | 5419.37 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179218E+10 | 0.52 | 1137.10 | 28-JAN-05:04 | 0.78 |
February | 0.160831E+10 | 0.53 | 1089.22 | 02-FEB-06:03 | 0.76 |
March | 0.175846E+10 | 0.53 | 1151.81 | 02-MAR-05:04 | 0.78 |
April | 0.170327E+10 | 0.56 | 1941.03 | 25-APR-04:01 | 1.02 |
May | 0.184721E+10 | 0.58 | 1941.03 | 05-MAY-04:01 | 1.01 |
June | 0.207268E+10 | 0.62 | 1547.54 | 20-JUN-03:31 | 0.91 |
July | 0.237308E+10 | 0.65 | 1941.03 | 14-JUL-04:01 | 1.00 |
August | 0.212579E+10 | 0.62 | 1941.03 | 01-AUG-04:01 | 1.00 |
September | 0.192675E+10 | 0.60 | 1941.03 | 02-SEP-03:21 | 1.00 |
October | 0.179626E+10 | 0.57 | 1941.03 | 13-OCT-03:21 | 1.01 |
November | 0.170506E+10 | 0.53 | 1017.91 | 28-NOV-01:00 | 0.73 |
December | 0.182385E+10 | 0.53 | 1156.28 | 27-DEC-05:04 | 0.78 |
Annual Sum or Average | 0.225329E+11 | 0.57 | |||
Minimum of Months | 0.160831E+10 | 0.52 | 1017.91 | 0.73 | |
Maximum of Months | 0.237308E+10 | 0.65 | 1941.03 | 1.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:02 | 5.36 | 5.36 | 49.44 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:02 | 5.36 | 5.36 | 48.87 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:02 | 5.36 | 5.36 | 49.54 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 52.55 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.73 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 53.72 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 53.45 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.04 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 53.39 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.07 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 52.79 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 50.53 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.87 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.04 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 49.44 | 59.87 | 8428.33 | 16087.05 | 30-JAN-19:45 |
February | 0.00 | 0.00 | 01-FEB-00:02 | 48.87 | 58.70 | 8437.01 | 16097.81 | 01-FEB-19:27 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 49.54 | 58.73 | 8214.10 | 15800.38 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 50.75 | 50.75 | 7641.93 | 14919.73 | 03-APR-18:20 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 51.38 | 51.38 | 7065.55 | 13891.96 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.38 | 52.38 | 6573.89 | 12789.65 | 01-JUN-06:53 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.51 | 52.51 | 6207.97 | 11937.13 | 03-JUL-06:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.75 | 52.75 | 6283.22 | 11983.38 | 31-AUG-06:57 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.36 | 52.36 | 6540.99 | 12759.16 | 29-SEP-18:24 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 50.19 | 50.19 | 7035.53 | 13894.13 | 31-OCT-18:17 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.25 | 51.25 | 7627.85 | 14973.46 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.53 | 59.24 | 8125.72 | 15813.97 | 28-DEC-07:59 |
Annual Sum or Average | 0.00 | 7342.33 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.87 | 50.19 | 6207.97 | 11937.13 | ||
Maximum of Months | 0.00 | 0.00 | 52.75 | 59.87 | 8437.01 | 16097.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.736072E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.704914E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.850396E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136353E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.199399E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.254745E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.293767E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.260476E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.217559E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141176E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.774483E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.745508E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188461E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.704914E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293767E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.184242E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.207985E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.283555E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.602935E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.979623E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.137191E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164773E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.140304E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.111512E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.661708E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.245293E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183448E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.888660E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183448E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164773E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.731735E+10 | 0.128195E+09 | 0.129994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649315E+10 | 0.169096E+10 | 0.854311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706129E+10 | 0.444141E+10 | 0.594375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.665384E+10 | 0.228452E+11 | 0.801302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684744E+10 | 0.438033E+11 | 18479007.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669967E+10 | 0.624312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708586E+10 | 0.785379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.694199E+10 | 0.660236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664723E+10 | 0.524868E+11 | 15778149.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.685449E+10 | 0.242183E+11 | 0.160658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684998E+10 | 0.276647E+10 | 0.620584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745494E+10 | 401973.01 | 0.167907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829072E+11 | 0.359374E+12 | 0.514790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649315E+10 | 401973.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.745494E+10 | 0.785379E+11 | 0.167907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.179218E+10 | 0.165426E+09 | 0.418553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160831E+10 | 0.160625E+10 | 0.293131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175846E+10 | 0.371616E+10 | 0.154700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170327E+10 | 0.162188E+11 | 70149543.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184721E+10 | 0.306216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.207268E+10 | 0.439230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237308E+10 | 0.566472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212579E+10 | 0.469088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192675E+10 | 0.367463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179626E+10 | 0.183349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170506E+10 | 0.259388E+10 | 0.160679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182385E+10 | 34095643.73 | 0.644334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225329E+11 | 0.257516E+12 | 0.167841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160831E+10 | 34095643.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237308E+10 | 0.566472E+11 | 0.644334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.731735E+10 | 0.00 | 0.00 | 0.00 | 43373560.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649315E+10 | 0.00 | 0.00 | 0.00 | 0.555987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706129E+10 | 0.00 | 0.00 | 0.00 | 0.144267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.665384E+10 | 0.00 | 0.00 | 0.00 | 0.698141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684744E+10 | 0.00 | 0.00 | 0.00 | 0.130924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669967E+10 | 0.00 | 0.00 | 0.00 | 0.187748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708586E+10 | 0.00 | 0.00 | 0.00 | 0.222908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.694199E+10 | 0.00 | 0.00 | 0.00 | 0.191056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664723E+10 | 0.00 | 0.00 | 0.00 | 0.151087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.685449E+10 | 0.00 | 0.00 | 0.00 | 0.726310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.684998E+10 | 0.00 | 0.00 | 0.00 | 0.894853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.745494E+10 | 0.00 | 0.00 | 0.00 | 139216.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.829072E+11 | 0.00 | 0.00 | 0.00 | 0.105554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649315E+10 | 0.00 | 0.00 | 0.00 | 139216.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.745494E+10 | 0.00 | 0.00 | 0.00 | 0.222908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.179218E+10 | 0.00 | 0.00 | 0.00 | 50235026.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160831E+10 | 0.00 | 0.00 | 0.00 | 0.471543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175846E+10 | 0.00 | 0.00 | 0.00 | 0.107708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170327E+10 | 0.00 | 0.00 | 0.00 | 0.432608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184721E+10 | 0.00 | 0.00 | 0.00 | 0.794901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.207268E+10 | 0.00 | 0.00 | 0.00 | 0.116465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237308E+10 | 0.00 | 0.00 | 0.00 | 0.141042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212579E+10 | 0.00 | 0.00 | 0.00 | 0.119047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192675E+10 | 0.00 | 0.00 | 0.00 | 0.922448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179626E+10 | 0.00 | 0.00 | 0.00 | 0.482082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170506E+10 | 0.00 | 0.00 | 0.00 | 0.747864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182385E+10 | 0.00 | 0.00 | 0.00 | 10631160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225329E+11 | 0.00 | 0.00 | 0.00 | 0.663331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160831E+10 | 0.00 | 0.00 | 0.00 | 10631160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237308E+10 | 0.00 | 0.00 | 0.00 | 0.141042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431153E+11 | 0.00 | 0.00 | 6523716.96 | 0.00 | 0.104733E+10 | 0.582319E+10 | 0.00 | 3.61 |
February | 0.298035E+11 | 0.00 | 0.00 | 21864359.01 | 0.00 | 0.113870E+10 | 0.106524E+11 | 0.00 | 3.89 |
March | 0.247900E+11 | 0.00 | 0.00 | 44871421.08 | 0.00 | 0.375749E+09 | 0.168154E+11 | 0.00 | 4.14 |
April | 0.906595E+10 | 0.383362E+09 | 0.00 | 96325894.72 | 0.00 | 28242730.55 | 0.150772E+11 | 0.00 | 4.25 |
May | 0.298487E+10 | 0.283497E+10 | 0.00 | 92155672.74 | 1207814.87 | 0.00 | 0.917182E+10 | 0.00 | 4.12 |
June | 0.645202E+09 | 0.864811E+10 | 0.00 | 37817802.24 | 40249465.18 | 0.00 | 0.281471E+10 | 0.00 | 3.92 |
July | 0.277864E+09 | 0.178703E+11 | 0.00 | 6815507.44 | 0.108069E+09 | 0.00 | 0.996906E+09 | 0.00 | 3.97 |
August | 0.592877E+09 | 0.994907E+10 | 0.00 | 34501780.47 | 61534747.16 | 0.00 | 0.369899E+10 | 0.00 | 4.09 |
September | 0.233656E+10 | 0.605173E+10 | 0.00 | 69099376.39 | 12600578.09 | 0.00 | 0.763178E+10 | 0.00 | 4.21 |
October | 0.837211E+10 | 0.121883E+10 | 0.00 | 90824082.73 | 2317362.50 | 3973710.87 | 0.193103E+11 | 0.00 | 4.50 |
November | 0.276340E+11 | 0.00 | 0.00 | 38012079.24 | 0.00 | 0.210852E+09 | 0.163580E+11 | 0.00 | 4.01 |
December | 0.461410E+11 | 0.00 | 0.00 | 3661793.10 | 0.00 | 0.224443E+10 | 0.491331E+10 | 0.00 | 3.56 |
Annual Sum or Average | 0.195759E+12 | 0.469564E+11 | 0.00 | 0.542473E+09 | 0.225979E+09 | 0.504927E+10 | 0.113264E+12 | 0.00 | 4.02 |
Minimum of Months | 0.277864E+09 | 0.00 | 0.00 | 3661793.10 | 0.00 | 0.00 | 0.996906E+09 | 0.00 | 3.56 |
Maximum of Months | 0.461410E+11 | 0.178703E+11 | 0.00 | 96325894.72 | 0.108069E+09 | 0.224443E+10 | 0.193103E+11 | 0.00 | 4.50 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.351146E+11 | 0.00 | 0.00 | 10854430.68 | 0.526520E+09 | 0.00 | 0.138640E+11 | 0.00 | 8.56 |
February | 0.253254E+11 | 0.00 | 0.00 | 30353745.04 | 0.324267E+09 | 0.00 | 0.177510E+11 | 0.00 | 8.58 |
March | 0.217455E+11 | 0.00 | 0.00 | 52551565.98 | 0.114100E+09 | 0.00 | 0.234571E+11 | 0.00 | 8.63 |
April | 0.663982E+10 | 0.333189E+09 | 0.00 | 0.107753E+09 | 27230625.31 | 0.00 | 0.252306E+11 | 0.00 | 8.76 |
May | 0.127388E+10 | 0.162428E+10 | 0.00 | 0.128071E+09 | 0.00 | 0.00 | 0.187420E+11 | 0.00 | 8.98 |
June | 73504106.72 | 0.314726E+10 | 0.00 | 0.111074E+09 | 0.00 | 0.00 | 0.851559E+10 | 0.00 | 9.18 |
July | 11620075.38 | 0.806711E+10 | 0.00 | 42409392.51 | 511570.45 | 0.00 | 0.253188E+10 | 0.00 | 9.30 |
August | 47759023.27 | 0.344234E+10 | 0.00 | 0.105950E+09 | 0.00 | 0.00 | 0.738417E+10 | 0.00 | 9.21 |
September | 0.721148E+09 | 0.175341E+10 | 0.00 | 0.126733E+09 | 0.00 | 0.00 | 0.139218E+11 | 0.00 | 9.10 |
October | 0.439569E+10 | 0.588989E+09 | 0.00 | 0.113252E+09 | 0.00 | 0.00 | 0.273904E+11 | 0.00 | 8.84 |
November | 0.209661E+11 | 0.00 | 0.00 | 46963988.41 | 0.343427E+09 | 0.00 | 0.242015E+11 | 0.00 | 8.58 |
December | 0.398483E+11 | 0.00 | 0.00 | 9053903.03 | 0.409245E+09 | 5443398.51 | 0.122711E+11 | 0.00 | 8.53 |
Annual Sum or Average | 0.156163E+12 | 0.189566E+11 | 0.00 | 0.885020E+09 | 0.174530E+10 | 5443398.51 | 0.195261E+12 | 0.00 | 8.85 |
Minimum of Months | 11620075.38 | 0.00 | 0.00 | 9053903.03 | 0.00 | 0.00 | 0.253188E+10 | 0.00 | 8.53 |
Maximum of Months | 0.398483E+11 | 0.806711E+10 | 0.00 | 0.128071E+09 | 0.526520E+09 | 5443398.51 | 0.273904E+11 | 0.00 | 9.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.637031E+11 | 0.130123E+11 | 0.160090E+12 | 0.524234E+09 | 0.235067E+11 |
February | 0.696194E+11 | 0.110821E+11 | 0.137089E+12 | 0.197977E+10 | 0.263758E+11 |
March | 0.119019E+12 | 0.116619E+11 | 0.142184E+12 | 0.376792E+10 | 0.353805E+11 |
April | 0.133845E+12 | 0.810286E+10 | 0.994920E+11 | 0.363573E+10 | 0.758244E+11 |
May | 0.150867E+12 | 0.537883E+10 | 0.614850E+11 | 0.225164E+10 | 0.122489E+12 |
June | 0.142319E+12 | 0.300836E+10 | 0.166123E+11 | 0.785352E+09 | 0.164907E+12 |
July | 0.133137E+12 | 0.669576E+09 | -0.207501E+11 | -185369747.2 | 0.201489E+12 |
August | 0.120372E+12 | 0.257986E+10 | 0.116473E+11 | 0.103169E+10 | 0.173221E+12 |
September | 0.104305E+12 | 0.363518E+10 | 0.415844E+11 | 0.190070E+10 | 0.142470E+12 |
October | 0.890317E+11 | 0.724967E+10 | 0.102202E+12 | 0.484889E+10 | 0.803127E+11 |
November | 0.661746E+11 | 0.111913E+11 | 0.145199E+12 | 0.320662E+10 | 0.293431E+11 |
December | 0.521683E+11 | 0.134401E+11 | 0.169764E+12 | 0.178841E+09 | 0.247938E+11 |
Annual Sum or Average | 0.124456E+13 | 0.910121E+11 | 0.106660E+13 | 0.239260E+11 | 0.110011E+13 |
Minimum of Months | 0.521683E+11 | 0.669576E+09 | -0.207501E+11 | -185369747.2 | 0.235067E+11 |
Maximum of Months | 0.150867E+12 | 0.134401E+11 | 0.169764E+12 | 0.484889E+10 | 0.201489E+12 |