Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:28:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2315.17 | 4529.31 | 4529.31 |
Net Site Energy | 2315.17 | 4529.31 | 4529.31 |
Total Source Energy | 5798.32 | 11343.61 | 11343.61 |
Net Source Energy | 5798.32 | 11343.61 | 11343.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 52.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 301.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.38 | 266.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 67.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1578.82 | 736.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 52.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 301.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.38 | 266.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 96.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 52.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 301.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.38 | 266.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 67.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1762.85 | 521.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1033.64 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3088.74 | 1440.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1762.85 | 521.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1033.64 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 3088.74 | 1440.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1578.817 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1578.817 | 100.00 |
Total On-Site and Utility Electric Sources | 1578.817 | 100.00 |
Total Electricity End Uses | 1578.817 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1331.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6700.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 12.0182 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6242 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 11.3653 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 12.0182 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6242 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 11.3653 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 11.3653 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JUL-11:09 | 04-FEB-06:00 | - | - | - | - | - | - | - | - | - | - | 28-FEB-07:00 |
Heating | 0.00 | 29054.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36685.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 23090.58 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11121.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3130.23 | 14702.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2710.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 81550.45 | 55523.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 29054.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36685.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 11766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11121.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3130.23 | 14702.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1089.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1659.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 306.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 166.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 954.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.72 | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 214.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5000.11 | 798.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3245.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 325.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1867.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.01 | 564.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 419.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9782.02 | 1561.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3245.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 600.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 325.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1867.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.01 | 564.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 419.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9782.02 | 1561.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.84 |
KITCHEN DIRECT AIR | 1.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 1.00 | 1.00 | 3.84 |
PSZ-AC_2:2 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.00 | 1.00 | 1.65 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.84 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.65 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.84 | 7156.52 |
PSZ-AC_2:2_ADDAQ FAN | 1.65 | 1761.64 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.84 | 3.84 | 3.84 | 3.84 | 95382.50 | 107994.63 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.65 | 1.65 | 1.65 | 1.65 | 40882.15 | 63814.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.84 | 1.92 | 3.84 | 95382.50 | 47691.21 | 95382.50 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.65 | 0.823162 | 1.65 | 40882.15 | 20441.02 | 40882.15 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 107994.63 |
PSZ-AC_2:2 HEATING COIL | 63814.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 12.018 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 76.946 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.624 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1072.704 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 4467.734 | 12.018 | 15.948 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4467.734 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1341.663 | 9.624 | 178.225 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1341.663 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 43930.84562 | 52717.01475 | 3.20088 | 3.84105 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.06600 | 1.71670E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 3058.71867 | 3670.46240 | 0.13126 | 1.33138 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 8.70000 | 6.99286E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22208.27760 | 26649.93312 | 1.37194 | 1.64632 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | 00:10:00 | 8.70000 | 6.99286E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 66704.26 | 3.84105 | 3.84105 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 50364.19 | 1.33138 | 1.33138 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 38217.62 | 1.64632 | 1.64632 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 56749.40 | 1.50017 | 1.50017 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.84105 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.64632 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.84105 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.84105 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.84105 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.84105 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.84105 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.84105 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.64632 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64632 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.64632 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64632 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.64632 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.64632 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.84105 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.64632 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.84105 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.84105 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7156.51901 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.84105 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.84105 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.84105 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.84105 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.84105 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.92053 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.84105 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 95382.50000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 47691.20934 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 95382.50000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 95382.50000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 107994.62644 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 107994.62644 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.64632 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.64632 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1761.64461 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.64632 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.64632 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.64632 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.64632 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.64632 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82316 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.64632 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40882.15000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20441.02309 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40882.15000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40882.15000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63814.94910 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 63814.94910 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 92652.4 | 10.39 | 10.26 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 39712.0 | 11.29 | 11.15 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 3.5730263009E-002 | 0.1421424860 | Pass | Pass | 6.9074081752E-002 | 0.2700755323 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1856598983 | 0.5478032392 | Pass | Pass | 0.2113196906 | 0.7339648800 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4081381706 | 0.4057566575 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1231.81 | -40.9 | -516.7 | 36.57 | 2787.85 | 3498.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 12.0182 | 371.75 | 4467.73 | LightsWired | LTG_SCH_DINING | 93.20 | 168.00 | 92.65 | 0.0000 | Y | 77.70 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6242 | 139.41 | 1341.66 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.21 |
Interior Lighting Total | 11.3653 | 511.15 | 5809.40 | 96.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 3334.35 | AstronomicalClock | - | 83.82 | 83.82 | 52.47 | |
Exterior Lighting Total | 3334.35 | 52.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 95382.50 | 66870.76 | 28511.74 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40882.15 | 28661.66 | 12220.49 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 92652.4 | 10.39 | 10.26 | ||||
PSZ-AC_2:2 COOLING COIL | 39712.0 | 11.29 | 11.15 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 107994.63 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 63814.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1110.54 | 3.84 | 7156.52 | 1863.17 | 1.00 | 1.17 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.65 | 1761.64 | 1070.05 | 1.00 | 1.35 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 43930.85 | 52717.01 | 141.81 | 3.201 | 3.841 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.98 | 0.01125 | 33.07 | 0.01717 | 1.331 | 0.00 |
KITCHEN | 22208.28 | 26649.93 | 191.17 | 1.372 | 1.646 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01037 | 32.60 | 0.01717 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3058.72 | 3670.46 | 9.87 | 0.131 | 1.331 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00778 | 8.70 | 0.00699 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | 00:10:00 | 19.00 | 27.27 | 0.00634 | 8.70 | 0.00699 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.84 | 3.84 | 1.33 | 1.33 | 3.8411 | 3.8411 | 3.8411 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.65 | 1.65 | 1.50 | 1.50 | 1.6463 | 1.6463 | 1.6463 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 95382.500 | 66870.763 | 3.841050 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 95382.50 | 53899.01 | 3.841050 | 27.18 | 21.16 | 0.01330143 | 11.30 | 11.30 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 34.6618 | 23.98 | 0.01124917 | 60.2837 | 43899.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 107994.626 | 107994.626 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | 107994.63 | 107994.63 | 3.841053 | 16.74 | 12.71 | 0.00750730 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 34.6618 | 21.00 | 0.00778022 | 50.2550 | 3054.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 40882.150 | 28661.658 | 1.646320 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 40882.15 | 20542.35 | 1.646320 | 32.01 | 24.65 | 0.01656232 | 11.94 | 11.73 | 0.00850000 | 32.60 | 0.01716606 | 25.17 | 91.1227 | 25.99 | 0.01036532 | 49.3638 | 22208.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 63814.949 | 63814.949 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 63814.95 | 63814.95 | 1.646324 | 7.93 | 7.93 | 0.00693503 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 91.1224 | 27.27 | 0.00634143 | 28.1791 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 95382.500 | 66870.763 | 3.841050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.5667 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.841053 | 4.61978417 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 95382.50 | 53899.01 | 1.0000 | 4.61978039 | 3.841050 | 27.18 | 21.16 | 0.01330143 | 61245.3 | 11.30 | 11.30 | 0.00850000 | 32786.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95382.50 | 33.20 | 0.01716721 | 25.32 | 1.33137743 | 34.6618 | 23.98 | 0.01124917 | 23.98 | 0.01124917 | 60.2837 | 43899.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 107994.626 | 107994.626 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.841053 | 4.61978417 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | Sensible | 107994.63 | 107994.63 | 1.0000 | 4.61978417 | 3.841053 | 16.74 | 12.71 | 0.00750730 | 35826.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 107994.63 | 8.70 | 0.00699286 | 8.70 | 1.33137743 | 34.6618 | 21.00 | 0.00778022 | 21.00 | 0.00778022 | 50.2550 | 3054.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40882.150 | 28661.658 | 1.646320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1035.6285 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.646324 | 1.98009810 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 40882.15 | 20542.35 | 1.0000 | 1.98009316 | 1.646320 | 32.01 | 24.65 | 0.01656232 | 74569.3 | 11.94 | 11.73 | 0.00850000 | 33445.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40882.15 | 32.60 | 0.01716606 | 25.17 | 1.50017041 | 91.1227 | 25.96 | 0.01036532 | 25.99 | 0.01036532 | 49.3638 | 22208.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63814.949 | 63814.949 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.646324 | 1.98009810 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 63814.95 | 63814.95 | 1.0000 | 1.98009810 | 1.646324 | 7.93 | 7.93 | 0.00693503 | 25412.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63814.95 | 8.70 | 0.00699286 | 8.70 | 1.50017041 | 91.1224 | 0.00 | 0.00634143 | 27.27 | 0.00634143 | 28.1791 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6915.00 | 3776.50 | 3616.83 |
KITCHEN | 7022.00 | 6809.83 | 6700.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7022.00 | 6861.17 | 6700.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1658.83 | 0.00 | 1331.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1658.83 | 0.00 | 1331.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.330 | 0.910 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.112 | 0.061 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.184 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.486 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 34992194.46 | 0.00 | 34992194.46 | 7401658.68 | 42393853.14 | 41986318.57 | 1460.00 | 7300.00 | 0.00 | 113.00 |
KITCHEN | 40314290.46 | 0.00 | 40314290.46 | 275830.74 | 40590121.20 | 47309374.20 | 1454.17 | 7300.21 | 5.62 | 1042.44 |
Total Facility | 75306484.92 | 0.00 | 75306484.92 | 7677489.42 | 82983974.34 | 89295692.77 | 1460.00 | 7300.21 | 5.62 | 1042.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3315 | 0.0000 | 1.3315 | 0.2802 | 1.6117 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.5002 | 0.0000 | 1.5002 | 0.0069 | 1.5071 | 1.5002 | 0.00 | 7187.00 | 0.00 |
Total Facility | 2.8317 | 0.0000 | 2.8317 | 0.2871 | 3.1188 | 2.8315 | 0.00 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50619041.75 | 0.00 | 50619041.75 | 41986318.57 | 1460.00 | 0.00 | 7300.00 | 113.00 |
PSZ-AC_2:2 | 58317884.42 | 0.00 | 58317884.42 | 47309374.20 | 1441.76 | 1.50 | 7316.74 | 1042.44 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9261 | 0.0000 | 1.9261 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 2.1701 | 0.0000 | 2.1701 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 0.00 | 0.00 | 7300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 6570.00 | 0.00 | 1659.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 2.1701 | 0.0000 | 2.1736 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
Electricity:Building | 574.49 | 4184.74 | 01-JAN-01:10 | 31858.89 | 02-JAN-11:10 |
Electricity:Zone:DINING | 202.98 | 1123.36 | 01-JAN-01:10 | 10843.36 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 557.63 | 3775.71 | 01-JAN-01:10 | 29493.74 | 02-JAN-11:10 |
InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 77.71 | 640.63 | 01-JAN-01:10 | 3843.73 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 96.92 | 799.01 | 01-JAN-01:10 | 4794.05 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 371.51 | 3061.38 | 01-JAN-01:10 | 21015.54 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.21 | 158.38 | 01-JAN-01:10 | 950.33 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 67.63 | 1063.72 | 03-FEB-23:30 | 3441.39 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 126.60 | 1126.01 | 16-MAR-00:10 | 6589.63 | 27-JUL-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.76 | 0.00 | 01-JAN-11:10 | 1522.79 | 28-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 33.02 | 762.94 | 04-FEB-06:00 | 1076.23 | 01-JAN-02:00 |
ElectricityPurchased:Facility | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
ElectricityPurchased:Plant | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
Cogeneration:ElectricityPurchased | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
General:Cogeneration:ElectricityPurchased | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
ElectricityNet:Plant | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
Cogeneration:ElectricityNet | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
General:Cogeneration:ElectricityNet | 1578.82 | 8645.10 | 16-MAR-00:10 | 81550.45 | 14-JUL-11:10 |
Electricity:HVAC | 825.26 | 0.00 | 01-JAN-01:10 | 48207.38 | 27-JUL-17:20 |
Fans:Electricity | 301.40 | 0.00 | 01-JAN-01:10 | 11121.57 | 18-JAN-21:40 |
General:Fans:Electricity | 301.40 | 0.00 | 01-JAN-01:10 | 11121.57 | 18-JAN-21:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 523.87 | 0.00 | 01-JAN-00:10 | 37085.81 | 27-JUL-17:20 |
General:Cooling:Electricity | 523.87 | 0.00 | 01-JAN-00:10 | 37085.81 | 27-JUL-17:20 |
ExteriorLights:Electricity | 52.47 | 0.00 | 01-JAN-07:20 | 3334.35 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 52.47 | 0.00 | 01-JAN-07:20 | 3334.35 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4740.60 | 16-MAR-06:40 |
Water Heater:WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4740.60 | 16-MAR-06:40 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 24-FEB-09:20 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 24-FEB-09:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 736.36 | 2803.57 | 01-JAN-01:10 | 55523.26 | 04-FEB-07:00 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.42 | 0.00 | 01-JAN-00:10 | 29830.34 | 04-FEB-06:10 |
Heating:NaturalGas | 0.42 | 0.00 | 01-JAN-00:10 | 29830.34 | 04-FEB-06:10 |
General:Heating:NaturalGas | 0.42 | 0.00 | 01-JAN-00:10 | 29830.34 | 04-FEB-06:10 |
NaturalGas:Plant | 266.14 | 993.32 | 01-JAN-00:10 | 17376.93 | 23-JAN-08:00 |
WaterSystems:NaturalGas | 266.14 | 993.32 | 01-JAN-00:10 | 17376.93 | 23-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 266.14 | 993.32 | 01-JAN-00:10 | 17376.93 | 23-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 09-JUN-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 09-JUN-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 28-FEB-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3171.03 | 3328.59 | 16-MAR-00:10 | 206671.17 | 27-JUL-18:10 |
EnergyTransfer:Building | 944.24 | 1664.29 | 16-MAR-00:10 | 56401.01 | 29-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN | 491.13 | 1664.29 | 16-MAR-00:10 | 26789.76 | 12-DEC-05:10 |
Refrigeration:EnergyTransfer | 167.11 | 2868.41 | 03-FEB-23:30 | 7834.84 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 83.55 | 1434.21 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 83.55 | 1434.21 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 83.55 | 1434.21 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
EnergyTransfer:Plant | 262.72 | 1664.29 | 16-MAR-00:10 | 14811.40 | 23-JAN-19:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.71 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.84 | 1298.81 | 04-FEB-06:00 | 2238.70 | 01-JAN-02:00 |
EnergyTransfer:Zone:DINING | 453.11 | 0.00 | 01-JAN-01:10 | 34896.93 | 29-JUL-18:10 |
Heating:EnergyTransfer | 2.96 | 0.00 | 01-JAN-00:10 | 9664.45 | 10-SEP-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.96 | 0.00 | 01-JAN-00:10 | 9664.45 | 10-SEP-23:10 |
General:Heating:EnergyTransfer | 2.96 | 0.00 | 01-JAN-00:10 | 9664.45 | 10-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.96 | 0.00 | 01-JAN-00:10 | 9664.45 | 10-SEP-23:10 |
Cooling:EnergyTransfer | 857.72 | 0.00 | 01-JAN-01:10 | 53427.14 | 29-JUL-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 450.15 | 0.00 | 01-JAN-01:10 | 34896.93 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer | 857.72 | 0.00 | 01-JAN-01:10 | 53427.14 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 450.15 | 0.00 | 01-JAN-01:10 | 34896.93 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 407.58 | 0.00 | 01-JAN-01:10 | 23507.56 | 04-FEB-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 407.58 | 0.00 | 01-JAN-01:10 | 23507.56 | 04-FEB-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
WaterSystems:PlantLoopHeatingDemand | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
EnergyTransfer:HVAC | 1964.08 | 0.00 | 01-JAN-00:10 | 145331.87 | 21-AUG-12:00 |
HeatingCoils:EnergyTransfer | 0.34 | 0.00 | 01-JAN-00:10 | 23864.27 | 04-FEB-06:10 |
CoolingCoils:EnergyTransfer | 1963.74 | 0.00 | 01-JAN-00:10 | 145331.87 | 21-AUG-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 179.16 | 0.00 | 01-JAN-01:10 | 12057.67 | 18-JAN-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.962 | -450.141 | 0.000 | 0.000 | 206.394 | 77.705 | 93.957 | 40.133 | 0.000 | 21.891 | 26.482 | 0.000 | -8.071 | 0.000 | -11.313 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.000 | -407.570 | 0.000 | 0.000 | 4.666 | 19.212 | 297.857 | 0.000 | 0.000 | 0.193 | 87.015 | 0.000 | 0.000 | 0.000 | -1.373 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.951 | 35.252 | 0.000 | 0.000 | 0.000 | -44.203 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.962 | -857.711 | 0.000 | 0.000 | 211.060 | 96.917 | 391.814 | 40.133 | 0.000 | 31.035 | 148.748 | 0.000 | -8.071 | 0.000 | -56.888 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 21-NOV-05:02 | 0.00 | 0.00 | 0.00 | -41370.45 | 0.00 | 0.00 | 732.75 | 854.19 | 2172.30 | 0.00 | 0.00 | 0.00 | 37950.11 | 0.00 | -334.73 | 0.00 | -4.16 | 0.00 |
KITCHEN | 31-JAN-04:21 | 0.00 | 0.00 | 0.00 | -56273.72 | 0.00 | 0.00 | 0.00 | 158.38 | 3821.48 | 0.00 | 0.00 | 0.00 | 52730.38 | 0.00 | -0.00 | 0.00 | -436.51 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-NOV-05:01 | 0.00 | 0.00 | 0.00 | -75776.40 | 0.00 | 0.00 | 0.00 | 799.01 | 9429.23 | 0.00 | 0.00 | 977.63 | 65551.87 | 0.00 | -900.43 | 0.00 | -80.92 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 10-SEP-23:01 | 0.00 | 0.00 | 13194.13 | 0.00 | 0.00 | 0.00 | 973.97 | 640.63 | 543.07 | 270.20 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15622.00 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-SEP-23:01 | -10441.52 | 10441.52 | 13194.13 | -10441.52 | 0.00 | 0.00 | 996.44 | 799.01 | 3382.99 | 270.20 | 0.00 | 357.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8558.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8411 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8411 | 0.3466 | 1.0000 | Not calculated | 1.3314 | 0.3466 | ||
PSZ-AC_2:2 | 1.6463 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6463 | 0.1109 | 1.0000 | Not calculated | 0.1826 | 0.1109 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.8411 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.8411 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3466 | ||
PSZ-AC_2:2 | 1.6463 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6463 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.1109 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8411 | 3.8411 | 3.8411 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6463 | 1.6463 | 1.6463 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8411 | 3.8411 | 3.8411 | 3.8411 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6463 | 1.6463 | 1.6463 | 1.6463 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8411 | 3.8411 | 3.8411 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6463 | 1.6463 | 1.6463 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.8411 | 3.8411 | 3.8411 | 3.8411 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6463 | 1.6463 | 1.6463 | 1.6463 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1331.83 |
Number of hours not met | 1331.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.42 | 29830.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 523.87 | 37085.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 96.92 | 4794.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 52.47 | 3334.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 301.40 | 11121.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.38 | 4740.60 | 266.14 | 17376.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.76 | 1522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.02 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 528.35 | 1578.82 |
Natural Gas | 469.79 | 736.36 |
Additional | 0.00 | 0.00 |
Total | 998.13 | 2315.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 189.60 |
Space Heating | 0.00 |
Space Cooling | 1024.87 |
Fans (All) | 589.64 |
Service Water Heating | 147.46 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 3088.74 |
Subtotal | 3088.74 |
Natural Gas [MJ/m2] | |
Space Heating | 0.83 |
Service Water Heating | 520.67 |
Miscellaneous (All) | 1440.58 |
Subtotal | 1440.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.19 |
Space Heating | 0.02 |
Space Cooling | 22.63 |
Fans (All) | 13.02 |
Service Water Heating | 14.75 |
Receptacle Equipment | 40.19 |
Miscellaneous | 5.21 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4860. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7499.83 | 1225.33 | 34.83 | 0.00 | 0.00 |
KITCHEN | 5466.17 | 3124.50 | 169.33 | 0.00 | 0.00 |
ATTIC | 4692.33 | 1038.67 | 983.67 | 1188.00 | 857.33 |
Min | 4692.33 | 1038.67 | 34.83 | 0.00 | 0.00 |
Max | 7499.83 | 3124.50 | 983.67 | 1188.00 | 857.33 |
Average | 5886.11 | 1796.17 | 395.94 | 396.00 | 285.78 |
Sum | 17658.33 | 5388.50 | 1187.83 | 1188.00 | 857.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821165.33 | 2690.33 | 366.33 | 0.00 | 0.00 |
KITCHEN | 14023.67 | 5203.83 | 5.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821165.33 | 5203.83 | 366.33 | 0.00 | 0.00 |
Average | 278396.33 | 2631.39 | 123.94 | 0.00 | 0.00 |
Sum | 835189.00 | 7894.17 | 371.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 3242.33 | 5513.33 | 4.33 | 0.00 | 0.00 |
KITCHEN | 885.33 | 7873.67 | 1.00 | 0.00 | 0.00 |
ATTIC | 2456.83 | 3658.83 | 753.83 | 646.83 | 1243.67 |
Min | 885.33 | 3658.83 | 1.00 | 0.00 | 0.00 |
Max | 3242.33 | 7873.67 | 753.83 | 646.83 | 1243.67 |
Average | 2194.83 | 5681.94 | 253.06 | 215.61 | 414.56 |
Sum | 6584.50 | 17045.83 | 759.17 | 646.83 | 1243.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 358526.00 | 465647.00 | 49.00 | 0.00 | 0.00 |
KITCHEN | 2100.83 | 17132.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 358526.00 | 465647.00 | 49.00 | 0.00 | 0.00 |
Average | 120208.94 | 160926.39 | 16.33 | 0.00 | 0.00 |
Sum | 360626.83 | 482779.17 | 49.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312150E+11 | 35104.21 | 30-JAN-05:01 | 20.92 | 20.55 | 0.152503E+11 | 14051.45 | 07-JAN-19:10 | 20.92 | 20.55 |
February | 0.298476E+11 | 33669.51 | 19-FEB-05:01 | 21.70 | 20.52 | 0.138145E+11 | 14051.44 | 18-FEB-19:10 | 21.70 | 20.52 |
March | 0.338111E+11 | 31945.36 | 14-MAR-04:02 | 23.80 | 22.55 | 0.154535E+11 | 14051.44 | 18-MAR-18:49 | 24.40 | 21.75 |
April | 0.358784E+11 | 38128.84 | 14-APR-04:02 | 23.80 | 22.37 | 0.149173E+11 | 14051.44 | 29-APR-18:10 | 22.12 | 20.03 |
May | 0.400884E+11 | 40652.92 | 16-MAY-04:02 | 25.00 | 21.55 | 0.154486E+11 | 14051.47 | 06-MAY-18:19 | 25.00 | 21.55 |
June | 0.408315E+11 | 39367.39 | 02-JUN-04:02 | 26.02 | 22.91 | 0.150350E+11 | 14051.40 | 17-JUN-18:19 | 28.70 | 22.86 |
July | 0.435901E+11 | 37846.42 | 07-JUL-04:02 | 23.30 | 21.44 | 0.153511E+11 | 14053.24 | 29-JUL-18:30 | 32.75 | 24.17 |
August | 0.433877E+11 | 37012.50 | 08-AUG-04:02 | 26.10 | 23.70 | 0.155501E+11 | 14051.42 | 12-AUG-18:00 | 26.10 | 24.11 |
September | 0.418766E+11 | 39024.09 | 15-SEP-04:02 | 24.40 | 22.75 | 0.149306E+11 | 14051.50 | 02-SEP-18:10 | 24.40 | 22.75 |
October | 0.413112E+11 | 39615.87 | 17-OCT-04:02 | 24.32 | 19.13 | 0.153549E+11 | 14051.40 | 14-OCT-18:49 | 24.32 | 19.13 |
November | 0.359096E+11 | 41416.27 | 21-NOV-05:02 | 25.60 | 21.37 | 0.148210E+11 | 14051.42 | 18-NOV-19:00 | 25.60 | 21.37 |
December | 0.323993E+11 | 36889.50 | 01-DEC-05:02 | 22.38 | 18.19 | 0.152425E+11 | 14051.44 | 30-DEC-19:40 | 20.73 | 19.58 |
Annual Sum or Average | 0.450146E+12 | 0.181169E+12 | ||||||||
Minimum of Months | 0.298476E+11 | 31945.36 | 20.92 | 18.19 | 0.138145E+11 | 14051.40 | 20.73 | 19.13 | ||
Maximum of Months | 0.435901E+11 | 41416.27 | 26.10 | 23.70 | 0.155501E+11 | 14053.24 | 32.75 | 24.17 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333595E+11 | 56257.99 | 31-JAN-04:21 | 13.05 | 10.86 | 0.105876E+11 | 6934.99 | 03-JAN-11:00 | 13.05 | 10.86 |
February | 0.300420E+11 | 45002.55 | 23-FEB-05:01 | 15.50 | 12.97 | 0.956795E+10 | 6934.97 | 17-FEB-11:00 | 15.50 | 12.97 |
March | 0.334789E+11 | 53802.79 | 21-MAR-04:01 | 12.12 | 9.55 | 0.106001E+11 | 6949.66 | 14-MAR-10:50 | 12.12 | 9.55 |
April | 0.330935E+11 | 37627.40 | 18-APR-03:31 | 19.60 | 15.28 | 0.102633E+11 | 6950.42 | 13-APR-10:50 | 19.60 | 15.28 |
May | 0.351572E+11 | 35359.90 | 07-MAY-04:01 | 21.02 | 19.55 | 0.106110E+11 | 6965.92 | 31-MAY-10:00 | 32.80 | 24.33 |
June | 0.343389E+11 | 27058.25 | 17-JUN-04:02 | 25.60 | 21.66 | 0.102920E+11 | 6988.34 | 06-JUN-10:50 | 25.60 | 21.66 |
July | 0.356818E+11 | 29973.39 | 07-JUL-03:21 | 23.30 | 21.44 | 0.106406E+11 | 7003.69 | 14-JUL-10:50 | 31.52 | 26.32 |
August | 0.355493E+11 | 26716.33 | 29-AUG-03:21 | 23.60 | 22.86 | 0.106442E+11 | 6996.71 | 04-AUG-10:50 | 23.60 | 22.86 |
September | 0.346068E+11 | 29219.31 | 05-SEP-03:21 | 23.30 | 21.69 | 0.102884E+11 | 6988.40 | 06-SEP-10:00 | 30.60 | 26.05 |
October | 0.352786E+11 | 36313.87 | 18-OCT-03:22 | 24.15 | 18.36 | 0.106149E+11 | 6996.72 | 04-OCT-10:00 | 24.15 | 18.36 |
November | 0.332937E+11 | 36603.61 | 02-NOV-04:01 | 20.50 | 19.05 | 0.102626E+11 | 6973.81 | 30-NOV-11:00 | 27.20 | 25.17 |
December | 0.336954E+11 | 54257.48 | 12-DEC-05:01 | 12.20 | 10.02 | 0.105902E+11 | 6938.55 | 07-DEC-11:50 | 12.20 | 10.02 |
Annual Sum or Average | 0.407576E+12 | 0.124963E+12 | ||||||||
Minimum of Months | 0.300420E+11 | 26716.33 | 12.12 | 9.55 | 0.956795E+10 | 6934.97 | 12.12 | 9.55 | ||
Maximum of Months | 0.356818E+11 | 56257.99 | 25.60 | 22.86 | 0.106442E+11 | 7003.69 | 32.80 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 | 19.26 | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 | 13.10 | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 | 13.44 | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 | 18.63 | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 | 20.01 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 | 24.42 | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 | 23.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 | 25.82 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 | 24.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 | 23.96 | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 | 21.03 | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 | 21.22 | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.00 | 0.00 | 16.65 | 13.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.00 | 0.00 | 28.60 | 25.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19028955.59 | 5182.51 | 07-JAN-00:02 | 24.32 |
February | 31136530.58 | 4218.27 | 11-FEB-00:03 | 23.90 |
March | 63509139.52 | 5551.89 | 14-MAR-04:03 | 23.80 |
April | 0.115284E+09 | 6833.20 | 12-APR-23:02 | 25.60 |
May | 0.320714E+09 | 8964.20 | 31-MAY-23:02 | 26.87 |
June | 0.520591E+09 | 13036.70 | 10-JUN-23:01 | 29.32 |
July | 0.455079E+09 | 11835.22 | 31-JUL-23:01 | 28.68 |
August | 0.504119E+09 | 12078.27 | 02-AUG-23:01 | 28.90 |
September | 0.416716E+09 | 13188.47 | 10-SEP-23:01 | 29.40 |
October | 0.311664E+09 | 9338.90 | 29-OCT-23:02 | 27.12 |
November | 0.156289E+09 | 8763.09 | 21-NOV-05:03 | 25.60 |
December | 47267913.82 | 7436.49 | 09-DEC-05:04 | 25.00 |
Annual Sum or Average | 0.296140E+10 | |||
Minimum of Months | 19028955.59 | 4218.27 | 23.80 | |
Maximum of Months | 0.520591E+09 | 13188.47 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.656587E+10 | 3843.73 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.594703E+10 | 3843.73 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.667042E+10 | 3843.73 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.637984E+10 | 3843.73 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.661815E+10 | 3843.73 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.644748E+10 | 3843.73 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.655127E+10 | 3843.73 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.667042E+10 | 3843.73 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.638137E+10 | 3843.73 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.656511E+10 | 3843.73 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.635601E+10 | 3843.73 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.655204E+10 | 3843.73 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.777050E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.594703E+10 | 3843.73 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.667042E+10 | 3843.73 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162334E+10 | 950.33 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.147034E+10 | 950.33 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.164919E+10 | 950.33 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.157735E+10 | 950.33 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.163627E+10 | 950.33 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.159407E+10 | 950.33 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.161973E+10 | 950.33 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.164919E+10 | 950.33 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.157773E+10 | 950.33 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.162315E+10 | 950.33 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.157145E+10 | 950.33 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.161992E+10 | 950.33 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.192117E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.147034E+10 | 950.33 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.164919E+10 | 950.33 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.656587E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217667E+09 | 0.310469E+10 |
February | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351697E+09 | 0.192676E+10 |
March | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417645E+09 | 0.184758E+10 |
April | 0.292871E+11 | 0.637984E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111978E+10 | 0.528901E+09 |
May | 0.303219E+11 | 0.661815E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248824E+10 | 0.105132E+09 |
June | 0.295292E+11 | 0.644748E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313695E+10 | 24084977.74 |
July | 0.300798E+11 | 0.655127E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375647E+10 | 40840260.10 |
August | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347928E+10 | 40478789.64 |
September | 0.292871E+11 | 0.638137E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311205E+10 | 33971104.68 |
October | 0.300980E+11 | 0.656511E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233491E+10 | 84051687.59 |
November | 0.290996E+11 | 0.635601E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115983E+10 | 0.901459E+09 |
December | 0.300798E+11 | 0.655204E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316963E+09 | 0.267459E+10 |
Annual Sum or Average | 0.356244E+12 | 0.777050E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218915E+11 | 0.113125E+11 |
Minimum of Months | 0.272721E+11 | 0.594703E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217667E+09 | 24084977.74 |
Maximum of Months | 0.305458E+11 | 0.667042E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375647E+10 | 0.310469E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162334E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 805791.13 | 0.172621E+09 |
February | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 1796928.13 | 0.241274E+09 |
March | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2561466.85 | 0.247549E+09 |
April | 0.786997E+09 | 0.157735E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 8807653.94 | 0.126804E+09 |
May | 0.814802E+09 | 0.163627E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 29905730.25 | 83359871.61 |
June | 0.793501E+09 | 0.159407E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 32001217.81 | 34743322.72 |
July | 0.808298E+09 | 0.161973E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 28475723.62 | 29396307.33 |
August | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 31578783.91 | 27442090.03 |
September | 0.786997E+09 | 0.157773E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 30563186.94 | 33390269.54 |
October | 0.808786E+09 | 0.162315E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 18897064.48 | 52555092.33 |
November | 0.781956E+09 | 0.157145E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 5739288.01 | 0.141724E+09 |
December | 0.808298E+09 | 0.161992E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1395830.15 | 0.181718E+09 |
Annual Sum or Average | 0.957291E+10 | 0.192117E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.192529E+09 | 0.137258E+10 |
Minimum of Months | 0.732850E+09 | 0.147034E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 805791.13 | 27442090.03 |
Maximum of Months | 0.820818E+09 | 0.164919E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 32001217.81 | 0.247549E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101929E+10 | 0.283635E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611128E+09 | 0.268325E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570178E+09 | 0.373889E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664642E+09 | 0.444872E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572176E+09 | 0.439067E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647134E+09 | 0.442074E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826257E+09 | 0.526654E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841740E+09 | 0.406120E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730904E+09 | 0.394609E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938041E+09 | 0.322227E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759318E+09 | 0.255037E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769803E+09 | 0.263747E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895061E+10 | 0.442026E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570178E+09 | 0.255037E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101929E+10 | 0.526654E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 3843.73 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2663.22 | 02-JAN-14:00 | 7650.73 | 24-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 3843.73 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2426.08 | 02-FEB-14:00 | 8146.27 | 03-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 3843.73 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2993.03 | 13-MAR-17:03 | 6848.93 | 15-MAR-11:10 |
April | 30255.31 | 01-APR-18:10 | 3843.73 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4271.77 | 17-APR-17:03 | 3916.88 | 02-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 3843.73 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5662.61 | 22-MAY-12:00 | 1288.99 | 07-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 3843.73 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4323.35 | 09-JUN-12:00 | 294.93 | 13-JUN-17:00 |
July | 30255.31 | 01-JUL-18:10 | 3843.73 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6079.47 | 29-JUL-18:02 | 748.46 | 14-JUL-17:55 |
August | 30255.31 | 05-AUG-18:10 | 3843.73 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5645.72 | 23-AUG-12:00 | 1128.93 | 28-AUG-12:00 |
September | 30255.31 | 02-SEP-18:10 | 3843.73 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.15 | 13-SEP-12:00 | 565.16 | 05-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 3843.73 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4733.47 | 03-OCT-11:55 | 972.59 | 28-OCT-06:10 |
November | 30255.31 | 04-NOV-18:10 | 3843.73 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3007.91 | 17-NOV-13:00 | 5207.92 | 12-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 3843.73 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.43 | 08-DEC-14:00 | 8087.12 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.43 | 294.93 | |||||
Maximum of Months | 30255.31 | 3843.73 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 6079.47 | 8146.27 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 950.33 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 30.89 | 07-JAN-13:00 | 825.29 | 24-JAN-02:50 |
February | 813.01 | 04-FEB-19:10 | 950.33 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 37.34 | 02-FEB-14:00 | 1184.39 | 04-FEB-05:00 |
March | 813.01 | 04-MAR-19:10 | 950.33 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 46.71 | 13-MAR-17:00 | 1146.18 | 15-MAR-03:10 |
April | 813.01 | 01-APR-18:10 | 950.33 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 65.58 | 15-APR-16:53 | 583.08 | 23-APR-02:00 |
May | 813.01 | 06-MAY-18:10 | 950.33 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 98.17 | 22-MAY-14:31 | 574.27 | 25-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 950.33 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 149.98 | 16-JUN-23:11 | 400.28 | 18-JUN-02:00 |
July | 813.01 | 01-JUL-18:10 | 950.33 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 67.59 | 09-JUL-23:10 | 315.00 | 04-JUL-03:20 |
August | 813.01 | 05-AUG-18:10 | 950.33 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 108.38 | 26-AUG-23:40 | 505.66 | 14-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 950.33 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 105.36 | 23-SEP-24:00 | 274.05 | 26-SEP-04:00 |
October | 813.01 | 07-OCT-18:10 | 950.33 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 55.87 | 03-OCT-13:00 | 423.22 | 17-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 950.33 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 29.33 | 22-NOV-13:00 | 924.61 | 12-NOV-04:30 |
December | 813.01 | 02-DEC-19:10 | 950.33 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 41.18 | 10-DEC-15:00 | 1085.05 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 29.33 | 274.05 | ||||||
Maximum of Months | 813.01 | 950.33 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 149.98 | 1184.39 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.59 | 27-JAN-03:40 | 6709.97 | 17-JAN-13:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.35 | 28-FEB-07:15 | 6630.99 | 22-FEB-14:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1384.87 | 02-MAR-05:30 | 7651.25 | 21-MAR-12:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.75 | 09-APR-06:53 | 7727.91 | 10-APR-12:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1267.24 | 02-MAY-05:50 | 7765.17 | 01-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1373.12 | 10-JUN-03:00 | 7825.61 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.87 | 15-JUL-03:51 | 7971.46 | 07-JUL-12:45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1644.80 | 31-AUG-03:51 | 7423.01 | 30-AUG-12:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.64 | 12-SEP-02:30 | 7389.78 | 30-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1562.92 | 22-OCT-04:00 | 7660.65 | 06-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.19 | 07-NOV-06:40 | 6008.75 | 10-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.18 | 13-DEC-06:00 | 5771.84 | 04-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1267.24 | 5771.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.59 | 7971.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35104.21 | 30-JAN-05:01 | 13446.80 | 6833.49 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 |
February | 33669.51 | 19-FEB-05:01 | 0.00 | 4484.40 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 |
March | 31945.36 | 14-MAR-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.57 |
April | 38128.84 | 14-APR-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
May | 40652.92 | 16-MAY-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
June | 39367.39 | 02-JUN-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
July | 37846.42 | 07-JUL-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37012.50 | 08-AUG-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
September | 39024.09 | 15-SEP-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
October | 39615.87 | 17-OCT-04:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 |
November | 41416.27 | 21-NOV-05:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 |
December | 36889.50 | 01-DEC-05:02 | 10085.10 | 5125.12 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31945.36 | 0.00 | 4484.40 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41416.27 | 13446.80 | 6833.49 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 56257.99 | 31-JAN-04:21 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 436.51 |
February | 45002.55 | 23-FEB-05:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 109.18 |
March | 53802.79 | 21-MAR-04:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 |
April | 37627.40 | 18-APR-03:31 | 0.00 | 1267.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 249.06 |
May | 35359.90 | 07-MAY-04:01 | 0.00 | 1267.07 | 54193.56 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 |
June | 27058.25 | 17-JUN-04:02 | 0.00 | 791.92 | 33870.98 | 16292.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 |
July | 29973.39 | 07-JUL-03:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 |
August | 26716.33 | 29-AUG-03:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 70.88 |
September | 29219.31 | 05-SEP-03:21 | 0.00 | 1108.68 | 25342.37 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 |
October | 36313.87 | 18-OCT-03:22 | 0.00 | 950.30 | 21722.03 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 231.87 |
November | 36603.61 | 02-NOV-04:01 | 361.34 | 1689.42 | 54193.56 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
December | 54257.48 | 12-DEC-05:01 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26716.33 | 0.00 | 791.92 | 21722.03 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | |
Maximum of Months | 56257.99 | 451.67 | 2111.78 | 67741.96 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 436.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.30 | 0.00 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.70 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.50 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.07 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.81 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.20 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.82 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.14 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.18 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.77 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.06 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.70 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.112455E+12 | 74044.77 | 07-JAN-11:50 | 0.643391E+11 | 42942.41 | 21-JAN-11:20 |
February | 0.105882E+12 | 75395.35 | 11-FEB-11:50 | 0.582051E+11 | 55523.26 | 04-FEB-06:00 |
March | 0.120488E+12 | 75620.33 | 14-MAR-10:09 | 0.638304E+11 | 43071.98 | 16-MAR-05:00 |
April | 0.124546E+12 | 76758.63 | 13-APR-11:00 | 0.605972E+11 | 42754.99 | 01-APR-10:39 |
May | 0.140651E+12 | 79630.55 | 31-MAY-10:00 | 0.617067E+11 | 42580.05 | 06-MAY-10:09 |
June | 0.143376E+12 | 79445.86 | 06-JUN-11:09 | 0.590628E+11 | 42457.67 | 04-JUN-10:30 |
July | 0.149950E+12 | 81550.45 | 14-JUL-11:09 | 0.605221E+11 | 42390.43 | 02-JUL-10:50 |
August | 0.150402E+12 | 81200.14 | 23-AUG-10:09 | 0.609407E+11 | 42432.79 | 26-AUG-10:30 |
September | 0.143764E+12 | 80236.09 | 06-SEP-10:00 | 0.594881E+11 | 42563.26 | 30-SEP-10:39 |
October | 0.142698E+12 | 80120.36 | 04-OCT-10:00 | 0.623350E+11 | 42714.44 | 28-OCT-10:30 |
November | 0.127105E+12 | 78048.73 | 30-NOV-18:19 | 0.612643E+11 | 42831.35 | 25-NOV-11:30 |
December | 0.117501E+12 | 74740.48 | 08-DEC-11:39 | 0.640635E+11 | 42920.83 | 24-DEC-11:39 |
Annual Sum or Average | 0.157882E+13 | 0.736355E+12 | ||||
Minimum of Months | 0.105882E+12 | 74044.77 | 0.582051E+11 | 42390.43 | ||
Maximum of Months | 0.150402E+12 | 81550.45 | 0.643391E+11 | 55523.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.818922E+10 | 0.500553E+10 | 0.391293E+11 | 0.00 | 0.254965E+11 | 37879553.69 | 0.00 | 0.225810E+11 | 0.00 | 0.00 | 0.00 | 0.638095E+10 | 0.00 |
February | 0.741737E+10 | 0.431932E+10 | 0.353426E+11 | 0.00 | 0.230332E+11 | 34213790.43 | 0.00 | 0.248567E+11 | 0.00 | 0.00 | 0.00 | 0.577466E+10 | 0.00 |
March | 0.831961E+10 | 0.450937E+10 | 0.391293E+11 | 0.00 | 0.255342E+11 | 37879553.69 | 0.00 | 0.308306E+11 | 0.00 | 0.00 | 0.00 | 0.644884E+10 | 0.00 |
April | 0.795718E+10 | 0.409725E+10 | 0.378671E+11 | 0.00 | 0.247996E+11 | 36657632.61 | 0.00 | 0.380588E+11 | 0.00 | 0.00 | 0.00 | 0.619240E+10 | 0.00 |
May | 0.825441E+10 | 0.399322E+10 | 0.391293E+11 | 0.00 | 0.256303E+11 | 37879553.69 | 0.00 | 0.514261E+11 | 0.00 | 0.00 | 0.00 | 0.641371E+10 | 0.00 |
June | 0.804156E+10 | 0.375514E+10 | 0.378671E+11 | 0.00 | 0.248339E+11 | 36657632.61 | 0.00 | 0.569736E+11 | 0.00 | 0.00 | 0.00 | 0.623408E+10 | 0.00 |
July | 0.817100E+10 | 0.391519E+10 | 0.391293E+11 | 0.00 | 0.256660E+11 | 37879553.69 | 0.00 | 0.608330E+11 | 0.00 | 0.00 | 0.00 | 0.636882E+10 | 0.00 |
August | 0.831961E+10 | 0.412726E+10 | 0.391293E+11 | 0.00 | 0.256733E+11 | 37879553.69 | 0.00 | 0.608264E+11 | 0.00 | 0.00 | 0.00 | 0.644701E+10 | 0.00 |
September | 0.795910E+10 | 0.425130E+10 | 0.378671E+11 | 0.00 | 0.248341E+11 | 36657632.61 | 0.00 | 0.569942E+11 | 0.00 | 0.00 | 0.00 | 0.619240E+10 | 0.00 |
October | 0.818826E+10 | 0.466942E+10 | 0.391293E+11 | 0.00 | 0.256410E+11 | 37879553.69 | 0.00 | 0.528778E+11 | 0.00 | 0.00 | 0.00 | 0.637685E+10 | 0.00 |
November | 0.792746E+10 | 0.476545E+10 | 0.378671E+11 | 0.00 | 0.247619E+11 | 36657632.61 | 0.00 | 0.400334E+11 | 0.00 | 0.00 | 0.00 | 0.617369E+10 | 0.00 |
December | 0.817196E+10 | 0.505754E+10 | 0.391293E+11 | 0.00 | 0.254925E+11 | 37879553.69 | 0.00 | 0.275765E+11 | 0.00 | 0.00 | 0.00 | 0.637257E+10 | 0.00 |
Annual Sum or Average | 0.969167E+11 | 0.524660E+11 | 0.460716E+12 | 0.00 | 0.301396E+12 | 0.446001E+09 | 0.00 | 0.523868E+12 | 0.00 | 0.00 | 0.00 | 0.753760E+11 | 0.00 |
Minimum of Months | 0.741737E+10 | 0.375514E+10 | 0.353426E+11 | 0.00 | 0.230332E+11 | 34213790.43 | 0.00 | 0.225810E+11 | 0.00 | 0.00 | 0.00 | 0.577466E+10 | 0.00 |
Maximum of Months | 0.831961E+10 | 0.505754E+10 | 0.391293E+11 | 0.00 | 0.256733E+11 | 37879553.69 | 0.00 | 0.608330E+11 | 0.00 | 0.00 | 0.00 | 0.644884E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 9913364.39 | 0.00 | 0.244294E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.239450E+09 | 0.00 | 0.219272E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.120274E+09 | 0.00 | 0.238104E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.219846E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.218070E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.204502E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.206223E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.210410E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.208755E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.224353E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.226517E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 55108523.21 | 0.00 | 0.241087E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.424746E+09 | 0.00 | 0.266143E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.204502E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.239450E+09 | 0.00 | 0.244294E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 4794.05 | 02-JAN-10:09 | 3334.35 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 11121.57 | 18-JAN-21:40 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 4794.05 | 01-FEB-10:09 | 3334.35 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 11121.57 | 01-FEB-07:19 | 17.86 | 24-FEB-09:20 | 0.00 | 01-FEB-00:10 |
March | 4794.05 | 01-MAR-10:09 | 3334.35 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 11121.57 | 01-MAR-05:10 | 17.86 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 4794.05 | 01-APR-16:10 | 3334.35 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 11121.57 | 01-APR-04:10 | 17.86 | 25-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 4794.05 | 01-MAY-09:09 | 3334.35 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 11121.57 | 01-MAY-04:00 | 17.86 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 4794.05 | 01-JUN-09:09 | 3334.35 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 11121.57 | 01-JUN-04:10 | 17.86 | 13-JUN-16:49 | 0.00 | 01-JUN-00:10 |
July | 4794.05 | 01-JUL-16:10 | 3334.35 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 11121.57 | 01-JUL-04:40 | 17.86 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 4794.05 | 01-AUG-09:09 | 3334.35 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 11121.57 | 01-AUG-04:10 | 17.86 | 01-AUG-10:30 | 0.00 | 01-AUG-00:10 |
September | 4794.05 | 01-SEP-09:09 | 3334.35 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 11121.57 | 01-SEP-07:19 | 17.86 | 02-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 4794.05 | 02-OCT-09:09 | 3334.35 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 11121.57 | 01-OCT-04:10 | 17.86 | 09-OCT-11:39 | 0.00 | 01-OCT-00:10 |
November | 4794.05 | 01-NOV-09:09 | 3334.35 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 11121.57 | 01-NOV-04:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 4794.05 | 01-DEC-10:09 | 3334.35 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 11121.57 | 01-DEC-05:30 | 17.86 | 02-DEC-09:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 11121.57 | 17.86 | 0.00 | ||||||
Maximum of Months | 4794.05 | 3334.35 | 24699.69 | 0.00 | 11121.57 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 31579.60 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4739.52 | 31-JAN-07:19 | 0.00 |
February | 30108.46 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4739.83 | 22-FEB-07:19 | 0.00 |
March | 30358.51 | 13-MAR-11:00 | 0.00 | 0.00 | 0.00 | 4740.60 | 16-MAR-06:40 | 0.00 |
April | 32594.16 | 13-APR-11:00 | 0.00 | 0.00 | 0.00 | 4737.38 | 19-APR-06:19 | 0.00 |
May | 35104.37 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4736.86 | 12-MAY-18:10 | 0.00 |
June | 34975.27 | 08-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.87 | 14-JUN-06:00 | 0.00 |
July | 37085.81 | 27-JUL-17:19 | 0.00 | 0.00 | 0.00 | 4736.81 | 14-JUL-18:10 | 0.00 |
August | 37029.30 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4737.01 | 08-AUG-06:00 | 0.00 |
September | 35875.10 | 22-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.71 | 12-SEP-18:10 | 0.00 |
October | 35582.95 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4736.98 | 11-OCT-18:30 | 0.00 |
November | 32538.35 | 30-NOV-12:30 | 0.00 | 0.00 | 0.00 | 4737.36 | 27-NOV-07:40 | 0.00 |
December | 29416.59 | 08-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4739.24 | 12-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29416.59 | 0.00 | 0.00 | 0.00 | 4736.71 | 0.00 | ||
Maximum of Months | 37085.81 | 0.00 | 0.00 | 0.00 | 4740.60 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 74044.77 | 07-JAN-11:50 | 4261.38 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 27057.78 | 0.00 |
February | 75395.35 | 11-FEB-11:50 | 4261.38 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 28399.65 | 0.00 |
March | 75620.33 | 14-MAR-10:09 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 27895.38 | 0.00 |
April | 76758.63 | 13-APR-11:00 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 32594.16 | 0.00 |
May | 79630.55 | 31-MAY-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 32546.00 | 0.00 |
June | 79445.86 | 06-JUN-11:09 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 34635.64 | 0.00 |
July | 81550.45 | 14-JUL-11:09 | 4794.05 | 23090.58 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 36685.34 | 0.00 |
August | 81200.14 | 23-AUG-10:09 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 33461.30 | 0.00 |
September | 80236.09 | 06-SEP-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 32939.71 | 0.00 |
October | 80120.36 | 04-OCT-10:00 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 32841.93 | 0.00 |
November | 78048.73 | 30-NOV-18:19 | 4794.05 | 20676.91 | 3334.35 | 0.00 | 11121.57 | 17.86 | 0.00 | 31583.86 | 0.00 |
December | 74740.48 | 08-DEC-11:39 | 4794.05 | 24699.69 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 27564.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 74044.77 | 4261.38 | 20676.91 | 0.00 | 0.00 | 11121.57 | 17.86 | 0.00 | 27057.78 | 0.00 | |
Maximum of Months | 81550.45 | 4794.05 | 24699.69 | 3334.35 | 0.00 | 11121.57 | 17.86 | 0.00 | 36685.34 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 3269.73 | 25-JAN-06:00 | 0.00 | 17376.93 | 23-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 29830.34 | 04-FEB-06:10 | 0.00 | 17361.12 | 03-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 18741.51 | 16-MAR-05:10 | 0.00 | 17282.83 | 01-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 17096.68 | 03-APR-18:19 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16925.59 | 01-MAY-18:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16749.62 | 01-JUN-18:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16646.41 | 03-JUL-18:40 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16721.71 | 31-AUG-18:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16858.01 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 17051.75 | 31-OCT-18:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 17233.11 | 27-NOV-07:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 7938.02 | 15-DEC-06:00 | 0.00 | 17328.96 | 21-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16646.41 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 29830.34 | 0.00 | 17376.93 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 31.09 | 0.33 | 31.02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 30.99 | 0.67 | 30.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 31.10 | 0.67 | 30.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 30.48 | 6.50 | 29.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 | 28.89 | 45.33 | 28.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 268.83 | 27.76 | 238.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 363.50 | 27.86 | 332.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 340.33 | 27.85 | 309.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 273.67 | 27.74 | 243.67 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 131.67 | 28.31 | 100.67 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 79.67 | 28.52 | 52.33 | 27.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 31.11 | 1.00 | 30.94 |
Annual Sum or Average | 0.00 | 0.00 | 1658.83 | 28.17 | 1331.83 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.74 | 0.33 | 27.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 363.50 | 31.11 | 332.50 | 31.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.50 | 23.73 | 529.33 | 24.00 | 97.50 | 24.04 |
February | 113.50 | 23.80 | 496.50 | 24.04 | 83.17 | 24.08 |
March | 181.67 | 23.96 | 551.67 | 24.09 | 144.83 | 24.14 |
April | 119.33 | 24.57 | 586.83 | 24.24 | 119.33 | 24.29 |
May | 315.17 | 24.41 | 611.00 | 24.29 | 315.17 | 24.32 |
June | 498.00 | 24.32 | 592.00 | 24.29 | 498.00 | 24.30 |
July | 502.00 | 24.31 | 609.00 | 24.28 | 502.00 | 24.29 |
August | 555.50 | 24.30 | 612.00 | 24.28 | 555.50 | 24.29 |
September | 478.00 | 24.31 | 590.00 | 24.28 | 478.00 | 24.29 |
October | 362.67 | 24.37 | 610.00 | 24.28 | 362.67 | 24.30 |
November | 299.00 | 24.24 | 571.17 | 24.20 | 286.50 | 24.23 |
December | 211.17 | 23.86 | 555.50 | 24.03 | 174.17 | 24.07 |
Annual Sum or Average | 3776.50 | 24.25 | 6915.00 | 24.21 | 3616.83 | 24.24 |
Minimum of Months | 113.50 | 23.73 | 496.50 | 24.00 | 83.17 | 24.04 |
Maximum of Months | 555.50 | 24.57 | 612.00 | 24.29 | 555.50 | 24.32 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.33 | 25.71 | 567.50 | 25.63 | 456.50 | 25.73 |
February | 477.17 | 25.73 | 518.33 | 25.76 | 453.17 | 25.83 |
March | 548.17 | 25.81 | 576.00 | 25.83 | 524.50 | 25.90 |
April | 581.00 | 26.06 | 590.00 | 26.04 | 581.00 | 26.05 |
May | 611.00 | 26.17 | 611.00 | 26.17 | 611.00 | 26.17 |
June | 592.00 | 26.62 | 592.00 | 26.62 | 592.00 | 26.62 |
July | 609.00 | 26.91 | 609.00 | 26.91 | 609.00 | 26.91 |
August | 612.00 | 26.84 | 612.00 | 26.84 | 612.00 | 26.84 |
September | 590.00 | 26.63 | 590.00 | 26.63 | 590.00 | 26.63 |
October | 610.00 | 26.32 | 610.00 | 26.32 | 610.00 | 26.32 |
November | 566.50 | 26.08 | 577.67 | 26.08 | 558.83 | 26.10 |
December | 532.67 | 25.66 | 568.50 | 25.70 | 502.50 | 25.79 |
Annual Sum or Average | 6809.83 | 26.24 | 7022.00 | 26.23 | 6700.50 | 26.26 |
Minimum of Months | 477.17 | 25.66 | 518.33 | 25.63 | 453.17 | 25.73 |
Maximum of Months | 612.00 | 26.91 | 612.00 | 26.91 | 612.00 | 26.91 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.93118 | 53.05669 | 0.59376 | 13.11827 |
February | 551.00000 | 23.97746 | 53.24851 | 0.61338 | 13.66846 |
March | 612.00000 | 24.01052 | 55.13972 | 0.63998 | 14.43731 |
April | 590.00000 | 24.17196 | 58.36785 | 0.71802 | 16.10820 |
May | 611.00000 | 24.22724 | 64.28110 | -0.0132 | 5.59782 |
June | 592.00000 | 24.26948 | 67.58721 | 0.04001 | 5.94117 |
July | 609.00000 | 24.25513 | 67.47401 | 0.05265 | 5.89355 |
August | 612.00000 | 24.27007 | 68.03775 | 0.05739 | 5.98471 |
September | 590.00000 | 24.25472 | 67.10456 | 0.05200 | 5.93337 |
October | 610.00000 | 24.22997 | 64.62815 | 0.80478 | 18.99687 |
November | 591.00000 | 24.13563 | 61.05500 | 0.73182 | 16.85733 |
December | 609.00000 | 23.95481 | 57.14568 | 0.63573 | 14.29784 |
Annual Sum or Average | 7187.00000 | 24.14133 | 61.47284 | 0.40900 | 11.38459 |
Minimum of Months | 551.00000 | 23.93118 | 53.05669 | -0.0132 | 5.59782 |
Maximum of Months | 612.00000 | 24.27007 | 68.03775 | 0.80478 | 18.99687 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.27151 | 52.17951 | 1.11179 | 33.67115 |
February | 551.00000 | 25.49583 | 51.95509 | 1.16607 | 36.04677 |
March | 612.00000 | 25.58872 | 53.60129 | 1.20684 | 37.78250 |
April | 590.00000 | 26.02354 | 56.78825 | 1.35147 | 43.16370 |
May | 611.00000 | 26.17097 | 62.13989 | 0.91529 | 23.28070 |
June | 592.00000 | 26.62198 | 64.78079 | 1.10450 | 31.88239 |
July | 609.00000 | 26.90901 | 65.01133 | 1.21943 | 37.56765 |
August | 612.00000 | 26.84187 | 65.20836 | 1.18716 | 35.96257 |
September | 590.00000 | 26.63071 | 64.59781 | 1.11605 | 32.39180 |
October | 610.00000 | 26.32252 | 62.26945 | 1.49368 | 50.56930 |
November | 591.00000 | 25.97575 | 58.64013 | 1.35960 | 44.28874 |
December | 609.00000 | 25.41420 | 55.64539 | 1.18112 | 36.92410 |
Annual Sum or Average | 7187.00000 | 26.10843 | 59.44405 | 1.20097 | 36.95522 |
Minimum of Months | 551.00000 | 25.27151 | 51.95509 | 0.91529 | 23.28070 |
Maximum of Months | 612.00000 | 26.90901 | 65.20836 | 1.49368 | 50.56930 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.516826E+11 | 0.157285E+11 | 505.86 | 0.323401E+11 | 0.193425E+11 | 0.00 | 0.83 | 02-JAN-14:00 | 0.00 | 01-JAN-00:03 | 81576.82 | 02-JAN-14:00 | 43675.15 | 02-JAN-13:55 | 44450.01 | 07-JAN-06:03 | 21496.87 | 02-JAN-14:00 | 0.00 | 01-JAN-00:03 |
February | 0.557960E+11 | 0.168597E+11 | 477.34 | 0.358752E+11 | 0.199208E+11 | 0.00 | 0.82 | 11-FEB-06:03 | 0.00 | 01-FEB-00:05 | 80907.98 | 11-FEB-06:03 | 41137.58 | 08-FEB-13:00 | 42624.30 | 11-FEB-06:03 | 21263.36 | 11-FEB-06:03 | 0.00 | 01-FEB-00:05 |
March | 0.691341E+11 | 0.205952E+11 | 541.25 | 0.421763E+11 | 0.269578E+11 | 0.00 | 0.91 | 14-MAR-04:02 | 0.00 | 01-MAR-00:03 | 93024.31 | 14-MAR-04:02 | 43598.91 | 13-MAR-17:03 | 53875.10 | 14-MAR-04:02 | 23738.18 | 14-MAR-04:02 | 0.00 | 01-MAR-00:03 |
April | 0.847175E+11 | 0.249284E+11 | 563.36 | 0.523299E+11 | 0.323877E+11 | 0.00 | 0.95 | 14-APR-04:02 | 0.00 | 01-APR-00:01 | 97785.72 | 14-APR-04:02 | 49093.37 | 17-APR-17:03 | 51877.92 | 13-APR-04:02 | 24689.05 | 14-APR-04:02 | 0.00 | 01-APR-00:01 |
May | 0.115735E+12 | 0.327125E+11 | 587.96 | 0.650777E+11 | 0.506569E+11 | 0.00 | 1.00 | 14-MAY-04:02 | 0.00 | 01-MAY-00:01 | 104550.57 | 14-MAY-04:02 | 55317.34 | 22-MAY-13:00 | 66251.50 | 29-MAY-04:02 | 26005.92 | 14-MAY-04:02 | 0.00 | 01-MAY-00:01 |
June | 0.131520E+12 | 0.361017E+11 | 569.64 | 0.686876E+11 | 0.628326E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:01 | 104550.57 | 10-JUN-04:02 | 50698.18 | 09-JUN-11:57 | 67399.55 | 07-JUN-04:02 | 26005.92 | 01-JUN-04:02 | 0.00 | 01-JUN-00:01 |
July | 0.141389E+12 | 0.389337E+11 | 588.62 | 0.749226E+11 | 0.664666E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:01 | 104550.57 | 25-JUL-04:02 | 58145.48 | 28-JUL-17:03 | 65537.14 | 26-JUL-04:02 | 26415.20 | 27-JUL-17:30 | 0.00 | 01-JUL-00:01 |
August | 0.141611E+12 | 0.387715E+11 | 588.67 | 0.734935E+11 | 0.681177E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 | 104550.57 | 02-AUG-04:02 | 56472.28 | 23-AUG-12:00 | 65012.44 | 05-AUG-04:02 | 26376.31 | 22-AUG-13:00 | 0.00 | 01-AUG-00:01 |
September | 0.131926E+12 | 0.363117E+11 | 569.66 | 0.695778E+11 | 0.623479E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:01 | 104550.57 | 22-SEP-04:01 | 52917.49 | 11-SEP-12:00 | 63502.11 | 23-SEP-04:02 | 26005.92 | 01-SEP-04:02 | 0.00 | 01-SEP-00:01 |
October | 0.120530E+12 | 0.337360E+11 | 588.19 | 0.659532E+11 | 0.545772E+11 | 0.00 | 1.00 | 01-OCT-04:02 | 0.00 | 01-OCT-00:01 | 104550.57 | 03-OCT-04:01 | 52419.88 | 03-OCT-12:00 | 68470.08 | 04-OCT-04:02 | 26005.92 | 01-OCT-04:02 | 0.00 | 01-OCT-00:01 |
November | 0.910146E+11 | 0.260099E+11 | 547.23 | 0.505907E+11 | 0.404238E+11 | 0.00 | 1.00 | 04-NOV-04:02 | 0.00 | 01-NOV-00:01 | 104550.57 | 23-NOV-05:02 | 52522.04 | 21-NOV-05:02 | 64114.38 | 05-NOV-04:02 | 26005.92 | 04-NOV-04:02 | 0.00 | 01-NOV-00:01 |
December | 0.626726E+11 | 0.186675E+11 | 526.73 | 0.364529E+11 | 0.262197E+11 | 0.00 | 0.93 | 09-DEC-05:02 | 0.00 | 01-DEC-00:02 | 95742.36 | 09-DEC-05:02 | 42603.58 | 09-DEC-05:02 | 53138.79 | 09-DEC-05:02 | 24283.46 | 09-DEC-05:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.119773E+13 | 0.339356E+12 | 6654.51 | 0.667478E+12 | 0.530251E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.516826E+11 | 0.157285E+11 | 477.34 | 0.323401E+11 | 0.193425E+11 | 0.00 | 0.82 | 0.00 | 80907.98 | 41137.58 | 42624.30 | 21263.36 | 0.00 | |||||||
Maximum of Months | 0.141611E+12 | 0.389337E+11 | 588.67 | 0.749226E+11 | 0.681177E+11 | 0.00 | 1.00 | 0.00 | 104550.57 | 58145.48 | 68470.08 | 26415.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.261490E+11 | 0.685247E+10 | 472.76 | 0.144766E+11 | 0.116724E+11 | 0.00 | 1.00 | 02-JAN-13:50 | 0.00 | 01-JAN-00:03 | 44811.71 | 07-JAN-11:45 | 26165.36 | 31-JAN-05:01 | 28762.98 | 07-JAN-04:22 | 10152.10 | 02-JAN-13:50 | 0.00 | 01-JAN-00:03 |
February | 0.305764E+11 | 0.799710E+10 | 490.01 | 0.180452E+11 | 0.125312E+11 | 0.00 | 1.00 | 11-FEB-11:33 | 0.00 | 01-FEB-00:05 | 44811.71 | 11-FEB-14:30 | 24058.48 | 11-FEB-14:00 | 26307.44 | 19-FEB-04:22 | 10197.13 | 11-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.400037E+11 | 0.102354E+11 | 578.34 | 0.218259E+11 | 0.181777E+11 | 0.00 | 1.00 | 02-MAR-05:01 | 0.00 | 01-MAR-00:03 | 44811.71 | 13-MAR-13:00 | 28203.58 | 17-MAR-04:01 | 28161.72 | 10-MAR-04:31 | 10152.10 | 04-MAR-11:32 | 0.00 | 01-MAR-00:03 |
April | 0.519981E+11 | 0.131304E+11 | 651.33 | 0.301939E+11 | 0.218042E+11 | 0.00 | 1.00 | 01-APR-14:30 | 0.00 | 01-APR-00:01 | 44811.71 | 01-APR-15:50 | 30652.01 | 15-APR-16:17 | 27760.38 | 25-APR-03:31 | 10435.34 | 15-APR-16:17 | 0.00 | 01-APR-00:01 |
May | 0.783739E+11 | 0.187136E+11 | 698.15 | 0.410645E+11 | 0.373094E+11 | 0.00 | 1.00 | 02-MAY-03:21 | 0.00 | 01-MAY-00:01 | 44811.71 | 06-MAY-16:38 | 34987.01 | 22-MAY-13:00 | 30620.22 | 29-MAY-03:22 | 10910.24 | 22-MAY-13:00 | 0.00 | 01-MAY-00:01 |
June | 0.894724E+11 | 0.208719E+11 | 681.04 | 0.429036E+11 | 0.465689E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:01 | 44811.71 | 07-JUN-08:30 | 29788.83 | 11-JUN-12:55 | 30671.10 | 25-JUN-03:22 | 10563.36 | 11-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.931665E+11 | 0.218994E+11 | 703.26 | 0.459878E+11 | 0.471786E+11 | 0.00 | 1.00 | 01-JUL-03:22 | 0.00 | 01-JUL-00:01 | 44811.71 | 07-JUL-20:15 | 34558.50 | 07-JUL-12:00 | 30461.37 | 03-JUL-03:22 | 11119.82 | 29-JUL-15:53 | 0.00 | 01-JUL-00:01 |
August | 0.943871E+11 | 0.220548E+11 | 703.91 | 0.449326E+11 | 0.494545E+11 | 0.00 | 1.00 | 01-AUG-03:21 | 0.00 | 01-AUG-00:01 | 44811.71 | 08-AUG-14:51 | 31533.77 | 23-AUG-12:00 | 30579.31 | 10-AUG-03:22 | 10827.07 | 23-AUG-13:00 | 0.00 | 01-AUG-00:01 |
September | 0.883527E+11 | 0.206825E+11 | 680.59 | 0.427170E+11 | 0.456357E+11 | 0.00 | 1.00 | 01-SEP-03:21 | 0.00 | 01-SEP-00:01 | 44811.71 | 27-SEP-18:55 | 31149.82 | 08-SEP-15:53 | 30034.48 | 27-SEP-19:40 | 10563.36 | 08-SEP-15:00 | 0.00 | 01-SEP-00:01 |
October | 0.805985E+11 | 0.191418E+11 | 700.26 | 0.401330E+11 | 0.404655E+11 | 0.00 | 1.00 | 01-OCT-03:22 | 0.00 | 01-OCT-00:01 | 44811.71 | 01-OCT-05:03 | 30798.45 | 23-OCT-10:55 | 31494.26 | 04-OCT-03:22 | 10563.36 | 09-OCT-10:53 | 0.00 | 01-OCT-00:01 |
November | 0.577806E+11 | 0.140235E+11 | 617.67 | 0.285177E+11 | 0.292629E+11 | 0.00 | 1.00 | 01-NOV-03:22 | 0.00 | 01-NOV-00:01 | 44811.71 | 04-NOV-08:28 | 26177.80 | 17-NOV-14:57 | 30331.65 | 04-NOV-03:22 | 10197.13 | 03-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.351535E+11 | 0.890903E+10 | 531.81 | 0.176052E+11 | 0.175483E+11 | 0.00 | 1.00 | 01-DEC-04:21 | 0.00 | 01-DEC-01:01 | 44811.71 | 09-DEC-12:00 | 26427.03 | 12-DEC-05:01 | 30452.58 | 24-DEC-04:22 | 10152.10 | 07-DEC-11:35 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.766013E+12 | 0.184512E+12 | 7509.13 | 0.388403E+12 | 0.377609E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.261490E+11 | 0.685247E+10 | 472.76 | 0.144766E+11 | 0.116724E+11 | 0.00 | 1.00 | 0.00 | 44811.71 | 24058.48 | 26307.44 | 10152.10 | 0.00 | |||||||
Maximum of Months | 0.943871E+11 | 0.220548E+11 | 703.91 | 0.459878E+11 | 0.494545E+11 | 0.00 | 1.00 | 0.00 | 44811.71 | 34987.01 | 31494.26 | 11119.82 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.24 | 81.58 | 88.66 | 237.69 | 163.59 | 0.00 | 0.00 | 0.00 |
February | 197.46 | 91.74 | 105.73 | 297.65 | 134.75 | 0.00 | 0.00 | 0.00 |
March | 240.53 | 113.72 | 126.81 | 366.47 | 110.21 | 0.00 | 0.00 | 0.00 |
April | 261.36 | 116.68 | 144.68 | 447.87 | 77.43 | 0.00 | 0.00 | 0.00 |
May | 247.28 | 98.86 | 148.41 | 462.74 | 40.93 | 0.00 | 0.00 | 0.00 |
June | 243.03 | 93.27 | 149.76 | 477.66 | 23.15 | 0.00 | 0.00 | 0.00 |
July | 250.05 | 90.23 | 159.81 | 508.95 | 30.34 | 0.00 | 0.00 | 0.00 |
August | 228.55 | 76.52 | 152.03 | 448.05 | 25.05 | 0.00 | 0.00 | 0.00 |
September | 220.19 | 79.51 | 140.68 | 439.71 | 33.88 | 0.00 | 0.00 | 0.00 |
October | 202.43 | 86.88 | 115.56 | 375.30 | 50.40 | 0.00 | 0.00 | 0.00 |
November | 164.84 | 65.64 | 99.19 | 271.15 | 86.64 | 0.00 | 0.00 | 0.00 |
December | 133.32 | 47.24 | 86.08 | 188.65 | 144.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 213.30 | 86.76 | 126.54 | 377.12 | 76.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.32 | 47.24 | 86.08 | 188.65 | 23.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.36 | 116.68 | 159.81 | 508.95 | 163.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 460.89 | 299.69 | 161.20 | 719.51 | 221.87 | 0.00 | 0.00 | 0.00 |
February | 406.87 | 231.40 | 175.47 | 665.27 | 187.08 | 0.00 | 0.00 | 0.00 |
March | 314.44 | 130.00 | 184.43 | 518.36 | 157.51 | 0.00 | 0.00 | 0.00 |
April | 225.46 | 46.18 | 179.27 | 411.23 | 110.13 | 0.00 | 0.00 | 0.00 |
May | 176.03 | 5.59 | 170.44 | 351.79 | 58.24 | 0.00 | 0.00 | 0.00 |
June | 166.04 | 0.35 | 165.70 | 354.14 | 32.92 | 0.00 | 0.00 | 0.00 |
July | 177.67 | 1.49 | 176.18 | 399.26 | 42.60 | 0.00 | 0.00 | 0.00 |
August | 199.74 | 14.94 | 184.80 | 424.66 | 34.80 | 0.00 | 0.00 | 0.00 |
September | 259.01 | 63.99 | 195.02 | 552.67 | 47.64 | 0.00 | 0.00 | 0.00 |
October | 359.47 | 170.92 | 188.55 | 682.10 | 70.18 | 0.00 | 0.00 | 0.00 |
November | 407.23 | 228.55 | 178.68 | 694.83 | 120.33 | 0.00 | 0.00 | 0.00 |
December | 444.35 | 280.57 | 163.78 | 708.64 | 195.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.27 | 122.33 | 176.94 | 539.58 | 106.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.04 | 0.35 | 161.20 | 351.79 | 32.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 460.89 | 299.69 | 195.02 | 719.51 | 221.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 153.38 | 66.32 | 87.06 | 214.11 | 169.77 | 0.00 | 0.00 | 0.00 |
February | 192.50 | 87.67 | 104.83 | 296.19 | 141.47 | 0.00 | 0.00 | 0.00 |
March | 238.45 | 109.00 | 129.45 | 371.59 | 116.49 | 0.00 | 0.00 | 0.00 |
April | 261.73 | 121.02 | 140.71 | 447.28 | 78.36 | 0.00 | 0.00 | 0.00 |
May | 239.37 | 92.42 | 146.96 | 448.79 | 41.91 | 0.00 | 0.00 | 0.00 |
June | 202.67 | 56.87 | 145.80 | 405.27 | 23.59 | 0.00 | 0.00 | 0.00 |
July | 226.15 | 69.89 | 156.26 | 464.85 | 30.70 | 0.00 | 0.00 | 0.00 |
August | 225.62 | 73.34 | 152.29 | 441.48 | 24.80 | 0.00 | 0.00 | 0.00 |
September | 192.53 | 56.74 | 135.79 | 389.60 | 34.46 | 0.00 | 0.00 | 0.00 |
October | 191.88 | 74.95 | 116.94 | 355.98 | 51.38 | 0.00 | 0.00 | 0.00 |
November | 157.85 | 57.82 | 100.03 | 263.96 | 91.08 | 0.00 | 0.00 | 0.00 |
December | 158.26 | 70.73 | 87.53 | 234.69 | 145.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 203.45 | 78.04 | 125.41 | 361.51 | 78.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.38 | 56.74 | 87.06 | 214.11 | 23.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.73 | 121.02 | 156.26 | 464.85 | 169.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455969E+09 | 0.218512E+09 | 0.237457E+09 | 0.636641E+09 | 0.438149E+09 |
February | 0.477698E+09 | 0.221926E+09 | 0.255772E+09 | 0.720078E+09 | 0.325996E+09 |
March | 0.644236E+09 | 0.304591E+09 | 0.339645E+09 | 0.981549E+09 | 0.295195E+09 |
April | 0.677444E+09 | 0.302425E+09 | 0.375019E+09 | 0.116089E+10 | 0.200709E+09 |
May | 0.662305E+09 | 0.264791E+09 | 0.397514E+09 | 0.123939E+10 | 0.109620E+09 |
June | 0.629926E+09 | 0.241761E+09 | 0.388165E+09 | 0.123808E+10 | 60007175.41 |
July | 0.669722E+09 | 0.241676E+09 | 0.428046E+09 | 0.136318E+10 | 81266819.14 |
August | 0.612147E+09 | 0.204954E+09 | 0.407194E+09 | 0.120006E+10 | 67097030.88 |
September | 0.570721E+09 | 0.206083E+09 | 0.364638E+09 | 0.113973E+10 | 87822997.17 |
October | 0.542201E+09 | 0.232694E+09 | 0.309507E+09 | 0.100520E+10 | 0.134995E+09 |
November | 0.427256E+09 | 0.170148E+09 | 0.257109E+09 | 0.702815E+09 | 0.224581E+09 |
December | 0.357075E+09 | 0.126515E+09 | 0.230559E+09 | 0.505275E+09 | 0.385922E+09 |
Annual Sum or Average | 0.672670E+10 | 0.273607E+10 | 0.399063E+10 | 0.118929E+11 | 0.241136E+10 |
Minimum of Months | 0.357075E+09 | 0.126515E+09 | 0.230559E+09 | 0.505275E+09 | 60007175.41 |
Maximum of Months | 0.677444E+09 | 0.304591E+09 | 0.428046E+09 | 0.136318E+10 | 0.438149E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123445E+10 | 0.802683E+09 | 0.431768E+09 | 0.192712E+10 | 0.594252E+09 |
February | 0.984290E+09 | 0.559803E+09 | 0.424488E+09 | 0.160942E+10 | 0.452586E+09 |
March | 0.842183E+09 | 0.348193E+09 | 0.493989E+09 | 0.138838E+10 | 0.421871E+09 |
April | 0.584381E+09 | 0.119709E+09 | 0.464672E+09 | 0.106591E+10 | 0.285453E+09 |
May | 0.471481E+09 | 14966438.46 | 0.456515E+09 | 0.942224E+09 | 0.155992E+09 |
June | 0.430386E+09 | 895899.24 | 0.429490E+09 | 0.917928E+09 | 85340266.74 |
July | 0.475874E+09 | 3995887.91 | 0.471878E+09 | 0.106937E+10 | 0.114090E+09 |
August | 0.534976E+09 | 40006713.83 | 0.494969E+09 | 0.113742E+10 | 93201392.15 |
September | 0.671363E+09 | 0.165858E+09 | 0.505505E+09 | 0.143251E+10 | 0.123493E+09 |
October | 0.962806E+09 | 0.457804E+09 | 0.505003E+09 | 0.182694E+10 | 0.187971E+09 |
November | 0.105554E+10 | 0.592402E+09 | 0.463137E+09 | 0.180099E+10 | 0.311899E+09 |
December | 0.119015E+10 | 0.751475E+09 | 0.438677E+09 | 0.189802E+10 | 0.524036E+09 |
Annual Sum or Average | 0.943788E+10 | 0.385779E+10 | 0.558009E+10 | 0.170162E+11 | 0.335019E+10 |
Minimum of Months | 0.430386E+09 | 895899.24 | 0.424488E+09 | 0.917928E+09 | 85340266.74 |
Maximum of Months | 0.123445E+10 | 0.802683E+09 | 0.505505E+09 | 0.192712E+10 | 0.594252E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.410811E+09 | 0.177640E+09 | 0.233171E+09 | 0.573477E+09 | 0.454714E+09 |
February | 0.465698E+09 | 0.212101E+09 | 0.253597E+09 | 0.716532E+09 | 0.342236E+09 |
March | 0.638670E+09 | 0.291954E+09 | 0.346715E+09 | 0.995265E+09 | 0.312012E+09 |
April | 0.678401E+09 | 0.313692E+09 | 0.364709E+09 | 0.115934E+10 | 0.203104E+09 |
May | 0.641140E+09 | 0.247532E+09 | 0.393608E+09 | 0.120205E+10 | 0.112240E+09 |
June | 0.525324E+09 | 0.147405E+09 | 0.377918E+09 | 0.105045E+10 | 61133415.36 |
July | 0.605721E+09 | 0.187194E+09 | 0.418527E+09 | 0.124505E+10 | 82225905.99 |
August | 0.604309E+09 | 0.196425E+09 | 0.407884E+09 | 0.118245E+10 | 66430605.36 |
September | 0.499048E+09 | 0.147069E+09 | 0.351978E+09 | 0.100985E+10 | 89318722.36 |
October | 0.513939E+09 | 0.200738E+09 | 0.313201E+09 | 0.953463E+09 | 0.137615E+09 |
November | 0.409143E+09 | 0.149859E+09 | 0.259284E+09 | 0.684177E+09 | 0.236080E+09 |
December | 0.423884E+09 | 0.189443E+09 | 0.234440E+09 | 0.628606E+09 | 0.389383E+09 |
Annual Sum or Average | 0.641609E+10 | 0.246105E+10 | 0.395503E+10 | 0.114007E+11 | 0.248649E+10 |
Minimum of Months | 0.409143E+09 | 0.147069E+09 | 0.233171E+09 | 0.573477E+09 | 61133415.36 |
Maximum of Months | 0.678401E+09 | 0.313692E+09 | 0.418527E+09 | 0.124505E+10 | 0.454714E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1156.85 | 540.76 | 784.51 | 447.59 | 336.92 | 0.00 | 0.00 |
February | 1247.99 | 452.19 | 796.83 | 410.81 | 386.02 | 0.00 | 0.00 |
March | 1240.14 | 367.94 | 793.42 | 352.73 | 440.69 | 0.00 | 0.00 |
April | 1300.39 | 259.93 | 748.54 | 283.88 | 464.66 | 0.00 | 0.00 |
May | 1260.96 | 138.72 | 662.68 | 196.87 | 465.81 | 0.00 | 0.00 |
June | 1235.47 | 78.07 | 611.74 | 150.49 | 461.26 | 0.00 | 0.00 |
July | 1372.21 | 102.79 | 653.87 | 161.61 | 492.25 | 0.00 | 0.00 |
August | 1313.91 | 84.36 | 653.91 | 164.79 | 489.12 | 0.00 | 0.00 |
September | 1380.93 | 114.94 | 671.73 | 200.24 | 471.50 | 0.00 | 0.00 |
October | 1412.13 | 170.70 | 753.79 | 332.75 | 421.04 | 0.00 | 0.00 |
November | 1224.90 | 293.03 | 729.91 | 352.01 | 377.91 | 0.00 | 0.00 |
December | 1124.69 | 477.83 | 735.93 | 398.53 | 337.39 | 0.00 | 0.00 |
Annual Sum or Average | 1272.61 | 255.94 | 716.03 | 287.13 | 428.90 | 0.00 | 0.00 |
Minimum of Months | 1124.69 | 78.07 | 611.74 | 150.49 | 336.92 | 0.00 | 0.00 |
Maximum of Months | 1412.13 | 540.76 | 796.83 | 447.59 | 492.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.309851E+10 | 0.144838E+10 | 0.210123E+10 | 0.119884E+10 | 0.902396E+09 | 0.00 | 0.00 |
February | 0.301914E+10 | 0.109393E+10 | 0.192769E+10 | 0.993830E+09 | 0.933856E+09 | 0.00 | 0.00 |
March | 0.332160E+10 | 0.985490E+09 | 0.212509E+10 | 0.944739E+09 | 0.118035E+10 | 0.00 | 0.00 |
April | 0.337062E+10 | 0.673751E+09 | 0.194023E+10 | 0.735826E+09 | 0.120440E+10 | 0.00 | 0.00 |
May | 0.337736E+10 | 0.371539E+09 | 0.177493E+10 | 0.527289E+09 | 0.124764E+10 | 0.00 | 0.00 |
June | 0.320233E+10 | 0.202349E+09 | 0.158564E+10 | 0.390062E+09 | 0.119557E+10 | 0.00 | 0.00 |
July | 0.367534E+10 | 0.275324E+09 | 0.175132E+10 | 0.432865E+09 | 0.131845E+10 | 0.00 | 0.00 |
August | 0.351917E+10 | 0.225961E+09 | 0.175143E+10 | 0.441386E+09 | 0.131005E+10 | 0.00 | 0.00 |
September | 0.357938E+10 | 0.297923E+09 | 0.174113E+10 | 0.519011E+09 | 0.122212E+10 | 0.00 | 0.00 |
October | 0.378224E+10 | 0.457216E+09 | 0.201895E+10 | 0.891235E+09 | 0.112771E+10 | 0.00 | 0.00 |
November | 0.317494E+10 | 0.759523E+09 | 0.189194E+10 | 0.912409E+09 | 0.979530E+09 | 0.00 | 0.00 |
December | 0.301238E+10 | 0.127983E+10 | 0.197111E+10 | 0.106743E+10 | 0.903677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401330E+11 | 0.807121E+10 | 0.225807E+11 | 0.905492E+10 | 0.135258E+11 | 0.00 | 0.00 |
Minimum of Months | 0.301238E+10 | 0.202349E+09 | 0.158564E+10 | 0.390062E+09 | 0.902396E+09 | 0.00 | 0.00 |
Maximum of Months | 0.378224E+10 | 0.144838E+10 | 0.212509E+10 | 0.119884E+10 | 0.131845E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638087E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155683606.5 | 81.21 | 0.00 | 0.00 |
February | 0.577452E+10 | -0.563432E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -140206973.1 | 81.21 | 0.00 | 0.00 |
March | 0.644874E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154867149.4 | 81.21 | 0.00 | 0.00 |
April | 0.619229E+10 | -0.604348E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148812583.9 | 81.22 | 0.00 | 0.00 |
May | 0.641354E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153344454.7 | 81.22 | 0.00 | 0.00 |
June | 0.623391E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147341028.6 | 81.21 | 0.00 | 0.00 |
July | 0.636866E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151569481.6 | 81.21 | 0.00 | 0.00 |
August | 0.644694E+10 | -0.629521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151731160.0 | 81.21 | 0.00 | 0.00 |
September | 0.619213E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147305595.2 | 81.21 | 0.00 | 0.00 |
October | 0.637679E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152960725.5 | 81.21 | 0.00 | 0.00 |
November | 0.617355E+10 | -0.602463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148922158.8 | 81.21 | 0.00 | 0.00 |
December | 0.637240E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155296939.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753743E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.180804E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577452E+10 | -0.629521E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155683606.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644874E+10 | -0.563432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -140206973.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.175289E+11 | -0.166777E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -851226849.1 | 58.98 | 0.00 | 0.00 |
February | 0.157128E+11 | -0.149475E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -765323391.0 | 58.99 | 0.00 | 0.00 |
March | 0.170265E+11 | -0.161827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -843744218.3 | 58.98 | 0.00 | 0.00 |
April | 0.156259E+11 | -0.148189E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -807005207.6 | 58.99 | 0.00 | 0.00 |
May | 0.154099E+11 | -0.145799E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -829902886.3 | 58.98 | 0.00 | 0.00 |
June | 0.143910E+11 | -0.135974E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -793523874.9 | 58.99 | 0.00 | 0.00 |
July | 0.144562E+11 | -0.136426E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -813601621.5 | 58.98 | 0.00 | 0.00 |
August | 0.147947E+11 | -0.139794E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -815312091.8 | 58.99 | 0.00 | 0.00 |
September | 0.147294E+11 | -0.139361E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -793322196.3 | 58.99 | 0.00 | 0.00 |
October | 0.159215E+11 | -0.150950E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -826443991.7 | 58.99 | 0.00 | 0.00 |
November | 0.161591E+11 | -0.153510E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -808116063.7 | 58.99 | 0.00 | 0.00 |
December | 0.172665E+11 | -0.164187E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -847763802.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.189022E+12 | -0.179227E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.979529E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.143910E+11 | -0.166777E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -851226849.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.175289E+11 | -0.135974E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -765323391.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6478518.77 | 2177.67 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98467403.14 | 22806.69 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58344191.32 | 17169.15 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30339421.03 | 7172.59 | 15-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98467403.14 | 22806.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1452172.74 | 651.76 | 25-JAN-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93092706.63 | 12339.69 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37875224.04 | 8467.48 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13747397.54 | 2412.84 | 21-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93092706.63 | 12339.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.516826E+11 | 0.323401E+11 | 81576.82 | 02-JAN-14:00 | 43668.06 | 0.00 |
February | 0.00 | 0.00 | 0.557960E+11 | 0.358752E+11 | 80907.98 | 11-FEB-06:03 | 38283.68 | 0.00 |
March | 0.00 | 0.00 | 0.691341E+11 | 0.421763E+11 | 93024.31 | 14-MAR-04:02 | 39149.20 | 0.00 |
April | 0.00 | 0.00 | 0.847175E+11 | 0.523299E+11 | 97785.72 | 14-APR-04:02 | 45946.96 | 0.00 |
May | 0.00 | 0.00 | 0.115735E+12 | 0.650777E+11 | 104550.57 | 14-MAY-04:02 | 44590.87 | 0.00 |
June | 0.00 | 0.00 | 0.131520E+12 | 0.686876E+11 | 104550.57 | 10-JUN-04:02 | 45097.08 | 0.00 |
July | 0.00 | 0.00 | 0.141389E+12 | 0.749226E+11 | 104550.57 | 25-JUL-04:02 | 43018.98 | 0.00 |
August | 0.00 | 0.00 | 0.141611E+12 | 0.734935E+11 | 104550.57 | 02-AUG-04:02 | 47801.41 | 0.00 |
September | 0.00 | 0.00 | 0.131926E+12 | 0.695778E+11 | 104550.57 | 22-SEP-04:01 | 43314.21 | 0.00 |
October | 0.00 | 0.00 | 0.120530E+12 | 0.659532E+11 | 104550.57 | 03-OCT-04:01 | 36746.46 | 0.00 |
November | 0.00 | 0.00 | 0.910146E+11 | 0.505907E+11 | 104550.57 | 23-NOV-05:02 | 43778.19 | 0.00 |
December | 0.00 | 0.00 | 0.626726E+11 | 0.364529E+11 | 95742.36 | 09-DEC-05:02 | 42603.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119773E+13 | 0.667478E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.516826E+11 | 0.323401E+11 | 80907.98 | 36746.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141611E+12 | 0.749226E+11 | 104550.57 | 47801.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.261490E+11 | 0.144766E+11 | 44811.71 | 07-JAN-11:45 | 23993.94 | 0.00 |
February | 0.00 | 0.00 | 0.305764E+11 | 0.180452E+11 | 44811.71 | 11-FEB-14:30 | 23244.17 | 0.00 |
March | 0.00 | 0.00 | 0.400037E+11 | 0.218259E+11 | 44811.71 | 13-MAR-13:00 | 21651.83 | 0.00 |
April | 0.00 | 0.00 | 0.519981E+11 | 0.301939E+11 | 44811.71 | 01-APR-15:50 | 20485.22 | 0.00 |
May | 0.00 | 0.00 | 0.783739E+11 | 0.410645E+11 | 44811.71 | 06-MAY-16:38 | 21070.03 | 0.00 |
June | 0.00 | 0.00 | 0.894724E+11 | 0.429036E+11 | 44811.71 | 07-JUN-08:30 | 19564.18 | 0.00 |
July | 0.00 | 0.00 | 0.931665E+11 | 0.459878E+11 | 44811.71 | 07-JUL-20:15 | 24129.61 | 0.00 |
August | 0.00 | 0.00 | 0.943871E+11 | 0.449326E+11 | 44811.71 | 08-AUG-14:51 | 19020.46 | 0.00 |
September | 0.00 | 0.00 | 0.883527E+11 | 0.427170E+11 | 44811.71 | 27-SEP-18:55 | 14796.12 | 0.00 |
October | 0.00 | 0.00 | 0.805985E+11 | 0.401330E+11 | 44811.71 | 01-OCT-05:03 | 16907.11 | 0.00 |
November | 0.00 | 0.00 | 0.577806E+11 | 0.285177E+11 | 44811.71 | 04-NOV-08:28 | 17929.35 | 0.00 |
December | 0.00 | 0.00 | 0.351535E+11 | 0.176052E+11 | 44811.71 | 09-DEC-12:00 | 24015.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.766013E+12 | 0.388403E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.261490E+11 | 0.144766E+11 | 44811.71 | 14796.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.943871E+11 | 0.459878E+11 | 44811.71 | 24129.61 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 6691.12 | 12686.05 | 17-JAN-19:23 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6643.64 | 12651.00 | 02-FEB-07:35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6507.24 | 12433.55 | 01-MAR-19:06 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6183.17 | 11916.45 | 03-APR-18:25 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5910.25 | 11405.50 | 01-MAY-19:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5713.28 | 10880.80 | 01-JUN-18:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5561.06 | 10572.95 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5687.15 | 10808.83 | 31-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5843.93 | 11218.13 | 28-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6101.84 | 11807.75 | 30-OCT-18:13 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6388.12 | 12292.06 | 28-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 6595.14 | 12588.67 | 28-DEC-07:20 |
Annual Sum or Average | 0.00 | 6149.44 | ||||
Minimum of Months | 0.00 | 0.00 | 5561.06 | 10572.95 | ||
Maximum of Months | 0.00 | 0.00 | 6691.12 | 12686.05 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.553818E+10 | 0.59 | 2203.40 | 01-JAN-00:03 | 0.63 |
February | 0.500447E+10 | 0.59 | 2203.40 | 01-FEB-00:05 | 0.63 |
March | 0.556454E+10 | 0.59 | 2203.40 | 01-MAR-00:03 | 0.63 |
April | 0.545782E+10 | 0.60 | 2203.40 | 01-APR-00:12 | 0.63 |
May | 0.562397E+10 | 0.60 | 2203.40 | 01-MAY-00:12 | 0.63 |
June | 0.544153E+10 | 0.60 | 2203.40 | 01-JUN-00:09 | 0.63 |
July | 0.562463E+10 | 0.60 | 2203.40 | 01-JUL-00:09 | 0.63 |
August | 0.562503E+10 | 0.60 | 2203.40 | 01-AUG-00:08 | 0.63 |
September | 0.544232E+10 | 0.60 | 2203.40 | 01-SEP-00:09 | 0.63 |
October | 0.562159E+10 | 0.60 | 2203.40 | 01-OCT-00:08 | 0.63 |
November | 0.541687E+10 | 0.60 | 2203.40 | 01-NOV-00:10 | 0.63 |
December | 0.552580E+10 | 0.59 | 2203.40 | 01-DEC-00:02 | 0.63 |
Annual Sum or Average | 0.658868E+11 | 0.60 | |||
Minimum of Months | 0.500447E+10 | 0.59 | 2203.40 | 0.63 | |
Maximum of Months | 0.562503E+10 | 0.60 | 2203.40 | 0.63 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159734E+11 | 1.26 | 7156.52 | 01-JAN-09:32 | 1.51 |
February | 0.144275E+11 | 1.26 | 7156.52 | 01-FEB-15:20 | 1.51 |
March | 0.159734E+11 | 1.26 | 7156.52 | 02-MAR-12:00 | 1.52 |
April | 0.154581E+11 | 1.26 | 7156.52 | 01-APR-21:30 | 1.52 |
May | 0.159734E+11 | 1.26 | 7156.52 | 09-MAY-05:00 | 1.51 |
June | 0.154581E+11 | 1.26 | 7156.52 | 05-JUN-11:50 | 1.51 |
July | 0.159734E+11 | 1.26 | 7156.52 | 05-JUL-11:20 | 1.51 |
August | 0.159734E+11 | 1.26 | 7156.52 | 01-AUG-11:04 | 1.51 |
September | 0.154581E+11 | 1.26 | 7156.52 | 28-SEP-05:30 | 1.51 |
October | 0.159734E+11 | 1.26 | 7156.52 | 15-OCT-04:20 | 1.50 |
November | 0.154581E+11 | 1.26 | 7156.52 | 06-NOV-15:13 | 1.52 |
December | 0.159734E+11 | 1.26 | 7156.52 | 03-DEC-16:27 | 1.52 |
Annual Sum or Average | 0.188073E+12 | 1.26 | |||
Minimum of Months | 0.144275E+11 | 1.26 | 7156.52 | 1.50 | |
Maximum of Months | 0.159734E+11 | 1.26 | 7156.52 | 1.52 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.398498E+10 | 0.83 | 1761.64 | 13-JAN-00:30 | 0.87 |
February | 0.360119E+10 | 0.83 | 1761.64 | 09-FEB-10:27 | 0.87 |
March | 0.399627E+10 | 0.83 | 1761.64 | 01-MAR-13:00 | 0.87 |
April | 0.388366E+10 | 0.84 | 1761.64 | 01-APR-09:03 | 0.87 |
May | 0.403295E+10 | 0.84 | 1761.64 | 01-MAY-05:07 | 0.86 |
June | 0.393432E+10 | 0.84 | 1761.64 | 01-JUN-04:06 | 0.86 |
July | 0.406801E+10 | 0.84 | 1761.64 | 01-JUL-06:30 | 0.86 |
August | 0.407494E+10 | 0.84 | 1761.64 | 01-AUG-06:00 | 0.86 |
September | 0.393373E+10 | 0.84 | 1761.64 | 01-SEP-07:38 | 0.87 |
October | 0.404607E+10 | 0.84 | 1761.64 | 01-OCT-09:40 | 0.87 |
November | 0.388691E+10 | 0.84 | 1761.64 | 14-NOV-15:40 | 0.87 |
December | 0.399333E+10 | 0.83 | 1761.64 | 18-DEC-09:50 | 0.87 |
Annual Sum or Average | 0.474363E+11 | 0.84 | |||
Minimum of Months | 0.360119E+10 | 0.83 | 1761.64 | 0.86 | |
Maximum of Months | 0.407494E+10 | 0.84 | 1761.64 | 0.87 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:03 | 5.36 | 5.36 | 51.46 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:05 | 5.36 | 5.36 | 51.44 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.97 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 53.84 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 53.74 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 54.41 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 54.00 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.51 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 53.60 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 52.98 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 53.63 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 51.79 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 51.44 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.51 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 51.46 | 59.83 | 6691.12 | 12686.05 | 17-JAN-19:23 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.44 | 58.37 | 6643.64 | 12651.00 | 02-FEB-07:35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.97 | 59.32 | 6507.24 | 12433.55 | 01-MAR-19:06 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.82 | 52.82 | 6183.17 | 11916.45 | 03-APR-18:25 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.74 | 52.74 | 5910.25 | 11405.50 | 01-MAY-19:00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.46 | 53.46 | 5713.28 | 10880.80 | 01-JUN-18:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.16 | 53.16 | 5561.06 | 10572.95 | 03-JUL-18:10 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.61 | 53.61 | 5687.15 | 10808.83 | 31-AUG-18:16 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.75 | 52.75 | 5843.93 | 11218.13 | 28-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.32 | 51.32 | 6101.84 | 11807.75 | 30-OCT-18:13 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.68 | 52.68 | 6388.12 | 12292.06 | 28-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 51.79 | 59.31 | 6595.14 | 12588.67 | 28-DEC-07:20 |
Annual Sum or Average | 0.00 | 6149.44 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.32 | 51.32 | 5561.06 | 10572.95 | ||
Maximum of Months | 0.00 | 0.00 | 53.61 | 59.83 | 6691.12 | 12686.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.317019E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.312872E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.365686E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.403865E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.486858E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.515598E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.549070E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.547449E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.517698E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.497093E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.414680E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.346408E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.527430E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.312872E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.549070E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108374E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115983E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142316E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.170141E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.227466E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.248062E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259674E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261298E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246162E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.231879E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179104E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.129024E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231948E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108374E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261298E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159734E+11 | 0.516826E+11 | 6478518.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144275E+11 | 0.557960E+11 | 98467403.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159734E+11 | 0.691341E+11 | 58344191.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154581E+11 | 0.847175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159734E+11 | 0.115735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154581E+11 | 0.131520E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159734E+11 | 0.141389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159734E+11 | 0.141611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154581E+11 | 0.131926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159734E+11 | 0.120530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154581E+11 | 0.910146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159734E+11 | 0.626726E+11 | 30339421.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188073E+12 | 0.119773E+13 | 0.193630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144275E+11 | 0.516826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159734E+11 | 0.141611E+12 | 98467403.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.398498E+10 | 0.261490E+11 | 1452172.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360119E+10 | 0.305764E+11 | 93092706.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399627E+10 | 0.400037E+11 | 37875224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388366E+10 | 0.519981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403295E+10 | 0.783739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.393432E+10 | 0.894724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.406801E+10 | 0.931665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.407494E+10 | 0.943871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.393373E+10 | 0.883527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.404607E+10 | 0.805985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388691E+10 | 0.577806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399333E+10 | 0.351535E+11 | 13747397.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474363E+11 | 0.766013E+12 | 0.146168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360119E+10 | 0.261490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407494E+10 | 0.943871E+11 | 93092706.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.157285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144275E+11 | 0.00 | 0.00 | 0.00 | 0.168597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.205952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154581E+11 | 0.00 | 0.00 | 0.00 | 0.249284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.327125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154581E+11 | 0.00 | 0.00 | 0.00 | 0.361017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.389337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.387715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154581E+11 | 0.00 | 0.00 | 0.00 | 0.363117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.337360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154581E+11 | 0.00 | 0.00 | 0.00 | 0.260099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.186675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188073E+12 | 0.00 | 0.00 | 0.00 | 0.339356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144275E+11 | 0.00 | 0.00 | 0.00 | 0.157285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159734E+11 | 0.00 | 0.00 | 0.00 | 0.389337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.398498E+10 | 0.00 | 0.00 | 0.00 | 0.685247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360119E+10 | 0.00 | 0.00 | 0.00 | 0.799710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399627E+10 | 0.00 | 0.00 | 0.00 | 0.102354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388366E+10 | 0.00 | 0.00 | 0.00 | 0.131304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.403295E+10 | 0.00 | 0.00 | 0.00 | 0.187136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.393432E+10 | 0.00 | 0.00 | 0.00 | 0.208719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.406801E+10 | 0.00 | 0.00 | 0.00 | 0.218994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.407494E+10 | 0.00 | 0.00 | 0.00 | 0.220548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.393373E+10 | 0.00 | 0.00 | 0.00 | 0.206825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.404607E+10 | 0.00 | 0.00 | 0.00 | 0.191418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388691E+10 | 0.00 | 0.00 | 0.00 | 0.140235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399333E+10 | 0.00 | 0.00 | 0.00 | 0.890903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474363E+11 | 0.00 | 0.00 | 0.00 | 0.184512E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.360119E+10 | 0.00 | 0.00 | 0.00 | 0.685247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407494E+10 | 0.00 | 0.00 | 0.00 | 0.220548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458284E+10 | 0.640947E+10 | 0.00 | 57535783.19 | 18409329.66 | 0.00 | 0.131964E+11 | 0.00 | 3.60 |
February | 0.367254E+10 | 0.734707E+10 | 0.00 | 44404314.17 | 27100717.13 | 5100875.20 | 0.702474E+10 | 0.00 | 3.59 |
March | 0.351162E+10 | 0.121528E+11 | 0.00 | 40758496.65 | 63620846.02 | 4585875.44 | 0.671165E+10 | 0.00 | 3.59 |
April | 0.552207E+09 | 0.180690E+11 | 0.00 | 16278073.74 | 0.100554E+09 | 0.00 | 0.196254E+10 | 0.00 | 3.60 |
May | 0.127309E+09 | 0.384290E+11 | 0.00 | 1754339.87 | 0.337211E+09 | 0.00 | 0.135393E+09 | 0.00 | 3.62 |
June | 20066643.56 | 0.517733E+11 | 0.00 | 1112991.88 | 0.695274E+09 | 0.00 | 12275894.55 | 0.00 | 3.62 |
July | 54192399.07 | 0.577222E+11 | 0.00 | 1114756.36 | 0.644659E+09 | 0.00 | 26406688.28 | 0.00 | 3.61 |
August | 20111761.47 | 0.574231E+11 | 0.00 | 1184484.48 | 0.728209E+09 | 0.00 | 9379241.61 | 0.00 | 3.62 |
September | 36040949.34 | 0.514410E+11 | 0.00 | 1488773.14 | 0.577827E+09 | 0.00 | 18709206.51 | 0.00 | 3.62 |
October | 0.126561E+09 | 0.414005E+11 | 0.00 | 1793008.12 | 0.404648E+09 | 0.00 | 94644532.93 | 0.00 | 3.63 |
November | 0.141046E+10 | 0.251261E+11 | 0.00 | 18743526.30 | 0.194863E+09 | 0.00 | 0.344067E+10 | 0.00 | 3.61 |
December | 0.423787E+10 | 0.112562E+11 | 0.00 | 40344414.96 | 69857564.83 | 0.00 | 0.977091E+10 | 0.00 | 3.60 |
Annual Sum or Average | 0.183518E+11 | 0.378550E+12 | 0.00 | 0.226513E+09 | 0.386223E+10 | 9686750.64 | 0.424037E+11 | 0.00 | 3.61 |
Minimum of Months | 20066643.56 | 0.640947E+10 | 0.00 | 1112991.88 | 18409329.66 | 0.00 | 9379241.61 | 0.00 | 3.59 |
Maximum of Months | 0.458284E+10 | 0.577222E+11 | 0.00 | 57535783.19 | 0.728209E+09 | 5100875.20 | 0.131964E+11 | 0.00 | 3.63 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.457051E+10 | 0.275387E+10 | 0.00 | 73167348.29 | 677452.09 | 0.00 | 0.227392E+11 | 0.00 | 11.00 |
February | 0.329718E+10 | 0.304944E+10 | 0.00 | 69114232.86 | 0.00 | 0.00 | 0.150246E+11 | 0.00 | 10.99 |
March | 0.352795E+10 | 0.593778E+10 | 0.00 | 63271399.62 | 0.00 | 0.00 | 0.133809E+11 | 0.00 | 11.03 |
April | 0.147544E+09 | 0.822372E+10 | 0.00 | 58541006.53 | 354850.89 | 0.00 | 0.624376E+10 | 0.00 | 11.10 |
May | 1861366.44 | 0.268150E+11 | 0.00 | 6158813.73 | 27045.63 | 0.00 | 0.610487E+09 | 0.00 | 11.21 |
June | 0.00 | 0.386940E+11 | 0.00 | 495487.70 | 0.00 | 0.00 | 20644910.54 | 0.00 | 11.32 |
July | 0.00 | 0.400999E+11 | 0.00 | 862135.65 | 0.00 | 0.00 | 65007866.90 | 0.00 | 11.33 |
August | 0.00 | 0.416577E+11 | 0.00 | 317511.10 | 0.00 | 0.00 | 25450909.84 | 0.00 | 11.35 |
September | 0.00 | 0.373493E+11 | 0.00 | 1031980.06 | 0.00 | 0.00 | 97426328.69 | 0.00 | 11.34 |
October | 0.00 | 0.289117E+11 | 0.00 | 8619667.82 | 0.00 | 0.00 | 0.566512E+09 | 0.00 | 11.28 |
November | 0.111782E+10 | 0.172822E+11 | 0.00 | 33353987.89 | 464577.22 | 0.00 | 0.767358E+10 | 0.00 | 11.14 |
December | 0.401014E+10 | 0.671226E+10 | 0.00 | 65192793.63 | 307801.22 | 0.00 | 0.180442E+11 | 0.00 | 11.03 |
Annual Sum or Average | 0.166730E+11 | 0.257487E+12 | 0.00 | 0.380126E+09 | 1831727.04 | 0.00 | 0.844917E+11 | 0.00 | 11.18 |
Minimum of Months | 0.00 | 0.275387E+10 | 0.00 | 317511.10 | 0.00 | 0.00 | 20644910.54 | 0.00 | 10.99 |
Maximum of Months | 0.457051E+10 | 0.416577E+11 | 0.00 | 73167348.29 | 677452.09 | 0.00 | 0.227392E+11 | 0.00 | 11.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.697710E+11 | 0.383749E+10 | 0.750179E+11 | 0.727876E+10 | 0.123277E+12 |
February | 0.841112E+11 | 0.274911E+10 | 0.464279E+11 | 0.549895E+10 | 0.131636E+12 |
March | 0.118590E+12 | 0.265733E+10 | 0.324742E+11 | 0.501739E+10 | 0.163174E+12 |
April | 0.130290E+12 | -67581715.4 | -0.827321E+10 | 0.332387E+10 | 0.200231E+12 |
May | 0.131737E+12 | -0.524142E+10 | -0.820186E+11 | 0.189042E+10 | 0.271531E+12 |
June | 0.115706E+12 | -0.832915E+10 | -0.123258E+12 | 0.226194E+09 | 0.304517E+12 |
July | 0.122580E+12 | -0.877014E+10 | -0.131397E+12 | 0.424219E+09 | 0.325127E+12 |
August | 0.130032E+12 | -0.996130E+10 | -0.134863E+12 | 0.149515E+09 | 0.325452E+12 |
September | 0.991279E+11 | -0.897341E+10 | -0.119548E+12 | 0.766498E+09 | 0.303939E+12 |
October | 0.920416E+11 | -0.740868E+10 | -0.902377E+11 | 0.157780E+10 | 0.280423E+12 |
November | 0.685155E+11 | -0.357225E+10 | -0.264614E+11 | 0.422289E+10 | 0.210701E+12 |
December | 0.693075E+11 | 0.213782E+10 | 0.454727E+11 | 0.619356E+10 | 0.147841E+12 |
Annual Sum or Average | 0.123181E+13 | -0.409422E+11 | -0.516663E+12 | 0.365701E+11 | 0.278785E+13 |
Minimum of Months | 0.685155E+11 | -0.996130E+10 | -0.134863E+12 | 0.149515E+09 | 0.123277E+12 |
Maximum of Months | 0.131737E+12 | 0.383749E+10 | 0.750179E+11 | 0.727876E+10 | 0.325452E+12 |