Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:28:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2867.65 | 5610.15 | 5610.15 |
Net Site Energy | 2867.65 | 5610.15 | 5610.15 |
Total Source Energy | 4857.17 | 9502.38 | 9502.38 |
Net Source Energy | 4857.17 | 9502.38 | 9502.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1140.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 124.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.53 | 418.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 48.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 839.48 | 2028.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1140.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 124.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.53 | 418.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1140.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 124.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.53 | 418.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 48.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 502.04 | 3048.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 976.11 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1642.33 | 3967.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 502.04 | 3048.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 976.11 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1642.33 | 3967.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 839.483 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 839.483 | 100.00 |
Total On-Site and Utility Electric Sources | 839.483 | 100.00 |
Total Electricity End Uses | 839.483 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 4.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4751.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.9552 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.1538 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.9552 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.1538 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.2821 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-11:00 | 06-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-MAR-19:10 |
Heating | 0.00 | 219822.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31424.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22750.50 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7618.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2994.46 | 33104.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1722.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 69016.03 | 266503.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 219822.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 31424.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7618.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2994.46 | 33104.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 452.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1236.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 394.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.19 | 453.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 155.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2658.64 | 2198.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 347.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 772.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.95 | 886.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 303.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5201.26 | 4301.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 347.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 772.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.95 | 886.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 303.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5201.26 | 4301.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.72 |
KITCHEN DIRECT AIR | 1.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.72 | 3.72 | 3.72 | 3.72 | 3.72 | 3.72 | 1.00 | 1.00 | 3.72 |
PSZ-AC_2:2 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.72 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.57 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.72 | 6361.43 |
PSZ-AC_2:2_ADDAQ FAN | 1.57 | 1678.31 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.72 | 3.72 | 3.72 | 2.46 | 91968.65 | 164928.34 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.04 | 38948.24 | 111402.02 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.72 | 1.86 | 2.48 | 91968.65 | 45984.32 | 0.703380 | 0.703380 |
PSZ-AC_2:2 COOLING COIL | 1.57 | 0.784223 | 1.05 | 38948.24 | 19474.12 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 164928.34 |
PSZ-AC_2:2 HEATING COIL | 111402.02 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.955 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.883 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.154 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1068.794 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2585.575 | 6.955 | 9.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2585.575 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1136.687 | 8.154 | 150.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1136.687 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1050 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1783 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.443 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.530 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.40573980E-08 | -0.47641882E-14 | 0.11577972E-14 | -0.42564494E-16 |
42 | 6 | 0.31501510E-05 | 0.20111404E-08 | 0.31972303E-02 | -0.26821047E-04 |
43 | 5 | -0.21516100E-03 | 0.11872281E-05 | -0.22414286 | 0.19598423E-02 |
44 | 4 | 0.48742574E-02 | 0.53959658E-04 | 4.8365113 | -0.45331940E-01 |
45 | 3 | -0.42565487E-01 | 0.42848253E-03 | -38.060760 | 0.39908864 |
46 | 2 | 0.15080720 | 0.71196147E-03 | 116.56052 | -1.4189635 |
47 | 1 | -0.21745169 | 0.21649910E-03 | -143.95238 | 2.0497807 |
48 | 0 | 0.10596509 | 0.52647499E-05 | 60.838472 | |
49 | 7 | -0.23719953E-08 | -0.96251812E-15 | 0.52891692E-14 | -0.81535610E-16 |
50 | 6 | 0.50438818E-05 | 0.34118978E-08 | 0.31915223E-02 | -0.26773164E-04 |
51 | 5 | -0.35938785E-03 | 0.20195581E-05 | -0.22381849 | 0.19569793E-02 |
52 | 4 | 0.82455538E-02 | 0.91898775E-04 | 4.8311101 | -0.45280019E-01 |
53 | 3 | -0.72342982E-01 | 0.73057132E-03 | -38.030254 | 0.39875144 |
54 | 2 | 0.25678677 | 0.12150454E-02 | 116.50115 | -1.4181694 |
55 | 1 | -0.37057757 | 0.37005683E-03 | -143.91743 | 2.0492064 |
56 | 0 | 0.18066113 | 0.89639064E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2917_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9349E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9352E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.8319E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7025E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6143E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6504E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2279E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1303E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.7708E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.6838E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.1576E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.0590E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.5244E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.4779E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.1582E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.1582E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7692E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7106E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4832E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5376E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4395E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4458E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.1303E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2279E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 40861.34950 | 49033.61940 | 3.10266 | 3.72319 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 12890.89600 | 15469.07520 | 0.57658 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20298.14570 | 24357.77484 | 1.30704 | 1.56845 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 3263.31879 | 3915.98255 | 0.13205 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 57712.12 | 3.72319 | 3.72319 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 112232.36 | 1.33138 | 1.33138 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28413.35 | 1.56845 | 1.56845 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 102590.74 | 1.21700 | 1.21700 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.72319 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.56845 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.72319 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.72319 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.72319 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.72319 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.72319 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.72319 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.56845 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.56845 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.56845 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56845 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56845 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56845 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.72319 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.56845 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.72319 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.72319 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6361.42917 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.72319 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.72319 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.72319 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.45730 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.72319 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.86159 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.48213 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 91968.65000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 45984.32500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70338 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70338 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 91968.65000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 164928.33745 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 164928.33745 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56845 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56845 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1678.31088 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56845 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56845 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56845 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03517 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56845 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78422 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04563 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38948.24000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19474.12000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38948.24000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 111402.02148 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 111402.02148 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 89321.1 | 10.75 | 10.70 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 37833.4 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | N/A | 1.657 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | N/A | 1.657 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | N/A | 1.657 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.105 | 0.102 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.178 | 0.171 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.6455824461E-002 | 0.5047403118 | Pass | Pass | 0.3551010622 | 2.9245015852 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 5.4669268403E-002 | 0.3221030141 | Pass | Pass | 5.7293794749E-002 | 0.2121756596 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2661792926 | 0.2481660445 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 870.07 | 216.57 | 2584.84 | 9.80 | 701.91 | 4383.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.103 | 0.105 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.173 | 0.178 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 1.657 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 1.657 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.9552 | 371.75 | 2585.58 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.15 | 0.0000 | Y | 38.41 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.1538 | 139.41 | 1136.69 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 16.28 |
Interior Lighting Total | 7.2821 | 511.15 | 3722.26 | 54.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2585.58 | 646.39 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2585.58 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 159.78 | AstronomicalClock | - | 49.55 | 49.55 | 1.49 | |
EXTERIOR_LIGHTS_B | 2015.63 | AstronomicalClock | - | 83.52 | 73.33 | 27.74 | |
Exterior Lighting Total | 2175.41 | 29.23 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 91968.65 | 64688.91 | 27279.74 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38948.24 | 27305.83 | 11642.41 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 89321.1 | 10.75 | 10.70 | ||||
PSZ-AC_2:2 COOLING COIL | 37833.4 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 164928.34 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 111402.02 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.72 | 6361.43 | 1708.60 | 1.00 | 1.18 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1678.31 | 1070.05 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 40861.35 | 49033.62 | 131.90 | 3.103 | 3.723 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.01065 | 29.98 | 0.01273 | 1.331 | 0.00 |
KITCHEN | 20298.15 | 24357.77 | 174.73 | 1.307 | 1.568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01044 | 28.98 | 0.01272 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 12890.90 | 15469.08 | 41.61 | 0.577 | 1.331 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -32.70 | 0.00018 | 1.331 | 0.00 |
KITCHEN | 3263.32 | 3915.98 | 28.09 | 0.132 | 1.217 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00709 | -32.70 | 0.00018 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.72 | 3.72 | 1.33 | 1.33 | 3.7232 | 3.7232 | 3.7232 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.57 | 1.57 | 1.22 | 1.22 | 1.5684 | 1.5684 | 1.5684 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 91968.650 | 64688.909 | 3.723190 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 45984.32 | 31189.20 | 2.482127 | 26.17 | 18.99 | 0.01138902 | 11.36 | 11.12 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 53.6386 | 23.98 | 0.01064476 | 54.7796 | 40853.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 164928.337 | 164928.337 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 164928.34 | 164928.34 | 3.723186 | 1.80 | 1.80 | 0.00507563 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 35.7591 | 21.00 | 0.00779885 | 48.3308 | 12889.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38948.240 | 27305.832 | 1.568450 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19474.12 | 12810.37 | 1.045633 | 29.36 | 20.64 | 0.01232399 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 116.3890 | 25.98 | 0.01046101 | 47.8022 | 20298.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 111402.021 | 111402.021 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | 111402.02 | 111402.02 | 1.568446 | -21.25 | -21.25 | 0.00173577 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 77.5929 | 19.00 | 0.00711151 | 49.9417 | 2134.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 91968.650 | 64688.909 | 3.723190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.723186 | 4.29627687 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 45984.32 | 31189.20 | 1.0000 | 2.86418766 | 2.482127 | 26.17 | 18.99 | 0.01138902 | 55333.5 | 11.36 | 11.12 | 0.00850000 | 32849.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45984.32 | 30.10 | 0.01272586 | 21.13 | 1.33137743 | 53.6386 | 23.98 | 0.01064476 | 23.98 | 0.01064476 | 54.7796 | 40853.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 164928.337 | 164928.337 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.723186 | 4.29627687 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 164928.34 | 164928.34 | 1.0000 | 4.29627687 | 3.723186 | 1.80 | 1.80 | 0.00507563 | 14516.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 164928.34 | -32.70 | 0.00018338 | -32.70 | 1.33137743 | 35.7591 | 21.00 | 0.00779885 | 21.00 | 0.00779885 | 48.3308 | 12889.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38948.240 | 27305.832 | 1.568450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.7497 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.568446 | 1.80986830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19474.12 | 12810.37 | 1.0000 | 1.20658229 | 1.045633 | 29.36 | 20.64 | 0.01232399 | 60998.5 | 11.90 | 11.35 | 0.00850000 | 33401.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19474.12 | 30.10 | 0.01272586 | 21.13 | 1.21700195 | 116.3890 | 25.94 | 0.01046101 | 25.98 | 0.01046101 | 47.8022 | 20298.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 111402.021 | 111402.021 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.568446 | 1.80986830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:50:00 | Sensible | 111402.02 | 111402.02 | 1.0000 | 1.80986830 | 1.568446 | -21.25 | -21.25 | 0.00173577 | -17085.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 111402.02 | -32.70 | 0.00018338 | -32.70 | 1.21700195 | 77.5929 | 18.38 | 0.00711151 | 19.00 | 0.00711151 | 49.9417 | 2134.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.72 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4106.17 | 5759.67 | 2961.83 |
KITCHEN | 5454.67 | 6268.17 | 4671.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5533.33 | 7002.83 | 4751.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 12.00 | 0.00 | 0.33 | 0.00 |
KITCHEN | 0.00 | 69.83 | 0.00 | 4.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 12.00 | 69.83 | 0.33 | 4.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.484 | 0.962 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 9.398 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.14 | 280.14 | 1133.39 | 4.063 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.17 | 7.53 | 425.02 | 8.535 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.14 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.17 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.32 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36639865.91 | 0.00 | 36639865.91 | 7832569.52 | 44472435.43 | 41986318.57 | 1458.71 | 6056.04 | 1245.25 | 129.04 |
KITCHEN | 28967000.53 | 0.00 | 28967000.53 | 157339.58 | 29124340.11 | 38379373.44 | 7555.70 | 1173.34 | 30.96 | 330.35 |
Total Facility | 65606866.44 | 0.00 | 65606866.44 | 7989909.10 | 73596775.55 | 80365692.01 | 7556.36 | 6061.33 | 1267.80 | 346.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3942 | 0.0000 | 1.3942 | 0.2992 | 1.6934 | 1.3314 | 0.00 | 5941.98 | 1245.02 |
KITCHEN | 1.0966 | 0.0000 | 1.0966 | 0.0039 | 1.1005 | 1.2170 | 6005.99 | 1150.75 | 30.26 |
Total Facility | 2.4908 | 0.0000 | 2.4908 | 0.3030 | 2.7939 | 2.5484 | 6005.99 | 5947.25 | 1266.87 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48787445.92 | 0.00 | 48787445.92 | 41986318.57 | 1457.82 | 0.05 | 7302.14 | 129.04 |
PSZ-AC_2:2 | 38570867.97 | 0.00 | 38570867.97 | 38379373.44 | 1455.56 | 0.04 | 7304.40 | 330.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8564 | 0.0000 | 1.8564 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4602 | 0.0000 | 1.4602 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1080.99 | 184.56 | 6050.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 146.36 | 1726.46 | 5644.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2907 | 2.0375 | 1.7731 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6876 | 1.5607 | 1.4324 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
Electricity:Building | 511.61 | 3281.23 | 01-JAN-01:10 | 28991.58 | 02-JAN-11:10 |
Electricity:Zone:DINING | 163.69 | 856.89 | 01-JAN-01:10 | 8683.37 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 504.68 | 3144.96 | 01-JAN-01:10 | 26848.48 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.69 | 414.80 | 03-JUN-05:00 | 3050.12 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:DINING | 38.41 | 280.62 | 03-JUN-05:00 | 2244.98 | 02-JAN-16:20 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.69 | 414.80 | 03-JUN-05:00 | 3050.12 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity | 54.69 | 414.80 | 03-JUN-05:00 | 3050.12 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 38.41 | 280.62 | 03-JUN-05:00 | 2244.98 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.69 | 414.80 | 03-JUN-05:00 | 3050.12 | 02-JAN-16:20 |
Electricity:Zone:KITCHEN | 347.92 | 2424.34 | 01-JAN-01:10 | 20308.21 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 48.95 | 852.61 | 05-JAN-23:30 | 3219.34 | 28-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 117.99 | 1033.02 | 24-DEC-01:10 | 6462.85 | 03-SEP-10:40 |
LowTempRefrigeration:Refrigeration:Electricity | 13.48 | 0.00 | 01-JAN-11:10 | 1511.80 | 21-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 28.54 | 735.96 | 06-JAN-05:40 | 1076.23 | 16-MAY-03:50 |
ElectricityPurchased:Facility | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
ElectricityPurchased:Plant | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
Cogeneration:ElectricityPurchased | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
General:Cogeneration:ElectricityPurchased | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
ElectricityNet:Plant | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
Cogeneration:ElectricityNet | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
General:Cogeneration:ElectricityNet | 839.48 | 5725.19 | 24-DEC-01:10 | 69016.03 | 30-JUN-12:00 |
Electricity:HVAC | 180.65 | 0.00 | 01-JAN-01:10 | 40046.41 | 29-JUN-18:00 |
Fans:Electricity | 124.61 | 0.00 | 01-JAN-01:10 | 7735.44 | 29-JUN-18:00 |
General:Fans:Electricity | 124.61 | 0.00 | 01-JAN-01:10 | 7735.44 | 29-JUN-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 56.04 | 0.00 | 01-JAN-00:10 | 32324.40 | 29-JUN-17:50 |
General:Cooling:Electricity | 56.04 | 0.00 | 01-JAN-00:10 | 32324.40 | 29-JUN-17:50 |
ExteriorLights:Electricity | 29.23 | 0.00 | 01-JAN-08:20 | 2175.41 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 29.23 | 0.00 | 01-JAN-08:20 | 2175.41 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.12 | 22-FEB-07:50 |
Water Heater:WaterSystems:Electricity | 75.53 | 0.00 | 01-JAN-01:10 | 4742.12 | 22-FEB-07:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 05-MAR-10:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2028.17 | 2758.01 | 13-APR-00:10 | 266503.94 | 06-JAN-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 1140.27 | 0.00 | 01-JAN-01:10 | 219822.24 | 06-JAN-07:10 |
Heating:NaturalGas | 1140.27 | 0.00 | 01-JAN-01:10 | 219822.24 | 06-JAN-07:10 |
General:Heating:NaturalGas | 1140.27 | 0.00 | 01-JAN-01:10 | 219822.24 | 06-JAN-07:10 |
NaturalGas:Plant | 418.10 | 947.76 | 01-JAN-00:10 | 37637.99 | 23-FEB-19:40 |
WaterSystems:NaturalGas | 418.10 | 947.76 | 01-JAN-00:10 | 37637.99 | 23-FEB-19:40 |
Water Heater:WaterSystems:NaturalGas | 418.10 | 947.76 | 01-JAN-00:10 | 37637.99 | 23-FEB-19:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 03-NOV-07:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 03-NOV-07:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-MAR-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2125.44 | 2930.11 | 05-JAN-01:10 | 229001.92 | 06-JAN-07:10 |
EnergyTransfer:Building | 635.55 | 1465.05 | 05-JAN-01:10 | 50888.43 | 29-JUN-17:10 |
EnergyTransfer:Zone:KITCHEN | 392.09 | 1465.05 | 05-JAN-01:10 | 25311.05 | 14-APR-04:10 |
Refrigeration:EnergyTransfer | 132.66 | 2620.96 | 05-JAN-23:10 | 7834.84 | 16-MAY-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.33 | 1310.48 | 05-JAN-23:10 | 3917.42 | 16-MAY-03:50 |
General:Refrigeration:EnergyTransfer | 66.33 | 1310.48 | 05-JAN-23:10 | 3917.42 | 16-MAY-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.33 | 1310.48 | 05-JAN-23:10 | 3917.42 | 16-MAY-03:50 |
EnergyTransfer:Plant | 367.47 | 1465.05 | 05-JAN-01:10 | 22564.37 | 01-MAR-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 11.94 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 54.39 | 1217.89 | 06-JAN-05:40 | 2238.70 | 16-MAY-03:50 |
EnergyTransfer:Zone:DINING | 243.46 | 0.00 | 01-JAN-01:10 | 36099.11 | 22-FEB-05:30 |
Heating:EnergyTransfer | 51.29 | 0.00 | 01-JAN-00:20 | 25345.37 | 24-DEC-07:10 |
Heating:EnergyTransfer:Zone:DINING | 51.25 | 0.00 | 01-JAN-00:20 | 25345.37 | 24-DEC-07:10 |
General:Heating:EnergyTransfer | 51.29 | 0.00 | 01-JAN-00:20 | 25345.37 | 24-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 51.25 | 0.00 | 01-JAN-00:20 | 25345.37 | 24-DEC-07:10 |
Cooling:EnergyTransfer | 517.93 | 0.00 | 01-JAN-01:10 | 48532.86 | 29-JUN-17:10 |
Cooling:EnergyTransfer:Zone:DINING | 192.22 | 0.00 | 01-JAN-01:10 | 31688.59 | 29-JUN-17:10 |
General:Cooling:EnergyTransfer | 517.93 | 0.00 | 01-JAN-01:10 | 48532.86 | 29-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 192.22 | 0.00 | 01-JAN-01:10 | 31688.59 | 29-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 2140.58 | 01-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.04 | 0.00 | 01-JAN-00:10 | 2140.58 | 01-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 325.72 | 0.00 | 01-JAN-01:10 | 21611.31 | 07-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 325.72 | 0.00 | 01-JAN-01:10 | 21611.31 | 07-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
PlantLoopHeatingDemand:Plant | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
EnergyTransfer:HVAC | 1122.42 | 0.00 | 01-JAN-01:10 | 175857.79 | 06-JAN-07:10 |
HeatingCoils:EnergyTransfer | 912.22 | 0.00 | 01-JAN-01:10 | 175857.79 | 06-JAN-07:10 |
CoolingCoils:EnergyTransfer | 210.20 | 0.00 | 01-JAN-00:10 | 124659.97 | 29-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 301.14 | 0.00 | 01-JAN-01:10 | 20592.51 | 23-FEB-08:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 51.248 | -192.213 | 0.000 | 0.000 | 232.245 | 38.414 | 93.957 | 49.002 | 0.000 | 1.466 | 0.003 | 0.000 | -26.569 | 0.000 | -166.900 | -80.649 |
KITCHEN | 0.000 | 0.000 | 0.042 | -325.704 | 0.000 | 0.000 | 6.238 | 16.277 | 287.132 | 0.000 | 0.000 | 0.007 | 19.844 | 0.000 | 0.000 | 0.000 | -3.835 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.895 | 25.907 | 0.000 | 0.000 | 0.000 | -33.802 | -0.000 |
Total Facility | 0.000 | 0.000 | 51.290 | -517.918 | 0.000 | 0.000 | 238.482 | 54.690 | 381.090 | 49.002 | 0.000 | 9.368 | 45.754 | 0.000 | -26.569 | 0.000 | -204.537 | -80.650 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-JAN-00:01 | 0.00 | 0.00 | 0.00 | -74535.97 | 0.00 | 0.00 | 1157.79 | 374.16 | 543.07 | 0.00 | 0.00 | 0.00 | 76701.74 | 0.00 | -3566.53 | 0.00 | -674.26 | 0.00 |
KITCHEN | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | -64456.05 | 0.00 | 0.00 | 28.88 | 178.91 | 6916.85 | 0.00 | 0.00 | 0.00 | 57496.58 | 0.00 | -0.00 | 0.00 | -165.17 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | -83355.92 | 0.00 | 0.00 | 1360.15 | 677.80 | 9089.15 | 0.00 | 0.00 | 400.93 | 74304.50 | 0.00 | -2270.58 | 0.00 | -206.01 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 06-MAR-05:01 | 0.00 | 0.00 | 105416.40 | 0.00 | 0.00 | 0.00 | 1351.65 | 498.89 | 2172.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2521.06 | 0.00 | -306.38 | -106611.80 |
KITCHEN | 01-JAN-05:02 | 0.00 | 0.00 | 19243.03 | 0.00 | 0.00 | 0.00 | 0.00 | 134.19 | 6916.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -161.31 | -26132.75 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAR-05:01 | -45338.12 | 45338.12 | 105416.40 | -45338.12 | 0.00 | 0.00 | 1380.95 | 677.80 | 9089.15 | 0.00 | 0.00 | 38.28 | 0.00 | 0.00 | -2521.06 | 0.00 | -498.08 | -68245.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7232 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7232 | 0.3576 | 1.0000 | Not calculated | 1.3314 | 0.3576 | ||
PSZ-AC_2:2 | 1.5684 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5684 | 0.1164 | 1.0000 | Not calculated | 0.1826 | 0.1164 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7232 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7232 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3576 | ||
PSZ-AC_2:2 | 1.5684 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5684 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1164 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7232 | 3.7232 | 3.7232 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5684 | 1.5684 | 1.5684 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7232 | 3.7232 | 3.7232 | 3.7232 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5684 | 1.5684 | 1.5684 | 1.5684 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7232 | 3.7232 | 3.7232 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5684 | 1.5684 | 1.5684 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7232 | 3.7232 | 3.7232 | 3.7232 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5684 | 1.5684 | 1.5684 | 1.5684 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 4.83 |
Number of hours not met | 5.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1140.27 | 219822.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 56.04 | 32324.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.69 | 3050.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.23 | 2175.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 124.61 | 7735.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.53 | 4742.12 | 418.10 | 37637.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.48 | 1511.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.54 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 498.94 | 839.48 |
Natural Gas | 469.79 | 2028.17 |
Additional | 0.00 | 0.00 |
Total | 968.73 | 2867.65 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.99 |
Space Heating | 0.00 |
Space Cooling | 109.64 |
Fans (All) | 243.78 |
Service Water Heating | 147.76 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 1642.33 |
Subtotal | 1642.33 |
Natural Gas [MJ/m2] | |
Space Heating | 2230.79 |
Service Water Heating | 817.96 |
Miscellaneous (All) | 3967.82 |
Subtotal | 3967.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.91 |
Space Heating | 39.76 |
Space Cooling | 1.95 |
Fans (All) | 4.35 |
Service Water Heating | 17.21 |
Receptacle Equipment | 32.07 |
Miscellaneous | 2.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8155.67 | 595.33 | 9.00 | 0.00 | 0.00 |
ATTIC | 7605.17 | 451.17 | 341.67 | 302.67 | 59.33 |
Min | 7605.17 | 12.50 | 0.00 | 0.00 | 0.00 |
Max | 8747.50 | 595.33 | 341.67 | 302.67 | 59.33 |
Average | 8169.44 | 353.00 | 116.89 | 100.89 | 19.78 |
Sum | 24508.33 | 1059.00 | 350.67 | 302.67 | 59.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824210.33 | 11.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19200.67 | 32.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824210.33 | 32.33 | 0.00 | 0.00 | 0.00 |
Average | 281137.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Sum | 843411.00 | 44.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8159.00 | 601.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6723.00 | 2036.50 | 0.50 | 0.00 | 0.00 |
ATTIC | 7589.00 | 687.83 | 205.67 | 138.00 | 139.50 |
Min | 6723.00 | 601.00 | 0.00 | 0.00 | 0.00 |
Max | 8159.00 | 2036.50 | 205.67 | 138.00 | 139.50 |
Average | 7490.33 | 1108.44 | 68.72 | 46.00 | 46.50 |
Sum | 22471.00 | 3325.33 | 206.17 | 138.00 | 139.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 771953.00 | 52269.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14828.33 | 4404.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 771953.00 | 52269.00 | 0.00 | 0.00 | 0.00 |
Average | 262260.44 | 18891.22 | 0.00 | 0.00 | 0.00 |
Sum | 786781.33 | 56673.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178774E+10 | 74537.68 | 06-JAN-00:01 | -32.3 | -32.4 | 0.119943E+11 | 10742.54 | 28-JAN-19:00 | -7.8 | -8.8 |
February | 0.346221E+10 | 66836.77 | 14-FEB-00:01 | -27.0 | -27.2 | 0.108606E+11 | 10742.58 | 11-FEB-19:49 | -27.0 | -27.2 |
March | 0.576069E+10 | 59012.27 | 05-MAR-00:01 | -21.5 | -21.7 | 0.121340E+11 | 10742.57 | 04-MAR-19:00 | -21.5 | -21.7 |
April | 0.142615E+11 | 42616.02 | 04-APR-23:01 | -10.1 | -11.5 | 0.121330E+11 | 14051.39 | 22-APR-18:19 | 16.27 | 7.08 |
May | 0.252784E+11 | 29103.40 | 07-MAY-04:01 | 1.20 | -1.3 | 0.140597E+11 | 14051.43 | 06-MAY-18:19 | 1.20 | -1.3 |
June | 0.282262E+11 | 33068.91 | 29-JUN-05:02 | 22.30 | 19.61 | 0.145292E+11 | 14053.15 | 10-JUN-18:30 | 22.30 | 19.61 |
July | 0.324264E+11 | 29163.51 | 29-JUL-18:04 | 27.93 | 21.15 | 0.151134E+11 | 14051.80 | 15-JUL-18:10 | 27.93 | 21.15 |
August | 0.303836E+11 | 28226.01 | 08-AUG-17:03 | 29.22 | 22.95 | 0.151606E+11 | 14052.94 | 26-AUG-18:00 | 22.20 | 17.55 |
September | 0.245152E+11 | 30134.87 | 06-SEP-04:01 | 1.10 | 1.10 | 0.133349E+11 | 14052.57 | 02-SEP-18:49 | 1.10 | 1.10 |
October | 0.168330E+11 | 38825.64 | 29-OCT-23:01 | -7.4 | -8.2 | 0.123474E+11 | 14049.61 | 21-OCT-18:19 | -7.4 | -8.2 |
November | 0.735252E+10 | 49538.42 | 25-NOV-00:01 | -15.0 | -15.4 | 0.116625E+11 | 12897.25 | 01-NOV-11:00 | -15.0 | -15.4 |
December | 0.192853E+10 | 72727.27 | 25-DEC-00:01 | -31.1 | -31.2 | 0.119888E+11 | 10742.50 | 16-DEC-19:19 | -31.1 | -31.2 |
Annual Sum or Average | 0.192216E+12 | 0.155318E+12 | ||||||||
Minimum of Months | 0.178774E+10 | 28226.01 | -32.3 | -32.4 | 0.108606E+11 | 10742.50 | -31.1 | -31.2 | ||
Maximum of Months | 0.324264E+11 | 74537.68 | 29.22 | 22.95 | 0.151606E+11 | 14053.15 | 27.93 | 21.15 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229522E+11 | 64170.39 | 06-JAN-05:01 | -34.9 | -35.0 | 0.103965E+11 | 6819.65 | 23-JAN-11:09 | -20.8 | -21.1 |
February | 0.218522E+11 | 61536.00 | 14-FEB-05:01 | -32.1 | -32.3 | 0.939103E+10 | 6831.08 | 21-FEB-11:00 | 6.10 | 2.99 |
March | 0.254635E+11 | 56579.14 | 05-MAR-05:01 | -28.1 | -28.3 | 0.104004E+11 | 6822.53 | 28-MAR-10:00 | 4.40 | 2.03 |
April | 0.265324E+11 | 40062.65 | 05-APR-04:01 | -12.4 | -13.3 | 0.101042E+11 | 6934.94 | 18-APR-10:00 | 17.20 | 11.08 |
May | 0.289007E+11 | 39447.56 | 26-MAY-03:11 | 19.40 | 15.80 | 0.105481E+11 | 6934.97 | 19-MAY-10:50 | 19.40 | 15.80 |
June | 0.287480E+11 | 47355.22 | 20-JUN-03:21 | 15.00 | 13.00 | 0.102521E+11 | 6952.30 | 30-JUN-10:50 | 30.92 | 23.73 |
July | 0.309473E+11 | 51613.69 | 11-JUL-04:01 | 12.02 | 11.79 | 0.105967E+11 | 6944.10 | 05-JUL-10:00 | 12.02 | 11.79 |
August | 0.306845E+11 | 44156.07 | 26-AUG-04:01 | 12.85 | 12.65 | 0.105985E+11 | 6934.99 | 15-AUG-10:00 | 12.85 | 12.65 |
September | 0.292461E+11 | 52202.08 | 12-SEP-04:01 | 11.52 | 11.16 | 0.102006E+11 | 6934.98 | 19-SEP-10:00 | 16.10 | 15.79 |
October | 0.298992E+11 | 39137.45 | 30-OCT-04:01 | -10.0 | -10.7 | 0.104377E+11 | 6934.61 | 19-OCT-10:00 | -10.0 | -10.7 |
November | 0.266702E+11 | 48269.62 | 29-NOV-05:01 | -19.6 | -19.9 | 0.100698E+11 | 6930.88 | 01-NOV-10:00 | -19.6 | -19.9 |
December | 0.238200E+11 | 55486.87 | 26-DEC-05:01 | -25.9 | -26.2 | 0.103964E+11 | 6819.65 | 18-DEC-11:39 | -25.9 | -26.2 |
Annual Sum or Average | 0.325716E+12 | 0.123392E+12 | ||||||||
Minimum of Months | 0.218522E+11 | 39137.45 | -34.9 | -35.0 | 0.939103E+10 | 6819.65 | -25.9 | -26.2 | ||
Maximum of Months | 0.309473E+11 | 64170.39 | 19.40 | 15.80 | 0.105985E+11 | 6952.30 | 30.92 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 | -3.3 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 | 0.38 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 | -1.4 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.4 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 | 13.57 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 | 0.51 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178621E+11 | 99482.12 | 23-JAN-05:01 | -22.8 |
February | 0.971032E+10 | 100125.17 | 16-FEB-05:01 | -14.0 |
March | 0.507064E+10 | 105419.56 | 06-MAR-05:01 | -18.4 |
April | 0.588630E+09 | 48330.78 | 04-APR-04:01 | -7.5 |
May | 39271796.40 | 11458.44 | 01-MAY-05:03 | -3.4 |
June | 12560394.67 | 7504.95 | 04-JUN-05:03 | 1.85 |
July | 606872.85 | 1980.42 | 10-JUL-05:03 | 9.68 |
August | 1208966.95 | 5855.75 | 19-AUG-05:03 | 4.60 |
September | 18324406.84 | 7422.82 | 23-SEP-05:03 | 4.90 |
October | 0.217717E+09 | 25569.61 | 04-OCT-05:40 | -0.2 |
November | 0.250053E+10 | 79194.83 | 25-NOV-05:01 | -19.0 |
December | 0.152252E+11 | 98830.07 | 16-DEC-05:01 | -15.9 |
Annual Sum or Average | 0.512471E+11 | |||
Minimum of Months | 606872.85 | 1980.42 | -22.8 | |
Maximum of Months | 0.178621E+11 | 105419.56 | 9.68 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14346604.35 | 19265.26 | 01-JAN-05:02 | -26.7 |
February | 9052591.70 | 16097.93 | 13-FEB-05:02 | -23.4 |
March | 4764704.44 | 11660.77 | 23-MAR-04:03 | -16.2 |
April | 887026.01 | 11194.28 | 05-APR-04:03 | -12.4 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 1400702.86 | 11004.86 | 26-NOV-05:03 | -10.6 |
December | 11937726.74 | 17820.96 | 21-DEC-05:02 | -26.9 |
Annual Sum or Average | 42389356.09 | |||
Minimum of Months | 0.00 | 0.00 | -26.9 | |
Maximum of Months | 14346604.35 | 19265.26 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.340202E+10 | 2244.98 | 02-JAN-16:19 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.301628E+10 | 2244.98 | 01-FEB-17:10 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.331101E+10 | 2244.98 | 01-MAR-17:19 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.308913E+10 | 2244.98 | 01-APR-18:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.313515E+10 | 2244.98 | 01-MAY-19:30 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.302419E+10 | 2244.98 | 01-JUN-19:49 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.308846E+10 | 2244.98 | 01-JUL-20:19 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.321430E+10 | 2244.98 | 01-AUG-19:40 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.312944E+10 | 2244.98 | 01-SEP-18:49 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.329704E+10 | 2244.98 | 02-OCT-17:19 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.328545E+10 | 2244.98 | 01-NOV-16:40 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.342132E+10 | 2244.98 | 01-DEC-16:19 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.384138E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.301628E+10 | 2244.98 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.342132E+10 | 2244.98 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137533E+10 | 805.14 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.124570E+10 | 805.14 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.139723E+10 | 805.14 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.133636E+10 | 805.14 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.138628E+10 | 805.14 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.135053E+10 | 805.14 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.137227E+10 | 805.14 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.139723E+10 | 805.14 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.133668E+10 | 805.14 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.137517E+10 | 805.14 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.133137E+10 | 805.14 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.137243E+10 | 805.14 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.162766E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.124570E+10 | 805.14 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.139723E+10 | 805.14 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.340202E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314042E+11 |
February | 0.272721E+11 | 0.301628E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233637E+11 |
March | 0.305458E+11 | 0.331101E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209161E+11 |
April | 0.292871E+11 | 0.308913E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9080372.58 | 0.119899E+11 |
May | 0.303219E+11 | 0.313515E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174798E+09 | 0.567772E+10 |
June | 0.295292E+11 | 0.302419E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481929E+09 | 0.314121E+10 |
July | 0.300798E+11 | 0.308846E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584594E+09 | 0.224723E+10 |
August | 0.305458E+11 | 0.321430E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208472E+09 | 0.338973E+10 |
September | 0.292871E+11 | 0.312944E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6734414.35 | 0.664259E+10 |
October | 0.300980E+11 | 0.329704E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115583E+11 |
November | 0.290996E+11 | 0.328545E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171157E+11 |
December | 0.300798E+11 | 0.342132E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294533E+11 |
Annual Sum or Average | 0.356244E+12 | 0.384138E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146561E+10 | 0.166900E+12 |
Minimum of Months | 0.272721E+11 | 0.301628E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224723E+10 |
Maximum of Months | 0.305458E+11 | 0.342132E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584594E+09 | 0.314042E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.137533E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609103E+09 |
February | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525052E+09 |
March | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384371E+09 |
April | 0.786997E+09 | 0.133636E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 21800.65 | 0.328790E+09 |
May | 0.814802E+09 | 0.138628E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 477611.34 | 0.177484E+09 |
June | 0.793501E+09 | 0.135053E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 3218658.25 | 0.122825E+09 |
July | 0.808298E+09 | 0.137227E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2775405.50 | 84093095.63 |
August | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 787695.85 | 0.125248E+09 |
September | 0.786997E+09 | 0.133668E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1339.20 | 0.187596E+09 |
October | 0.808786E+09 | 0.137517E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235756E+09 |
November | 0.781956E+09 | 0.133137E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424506E+09 |
December | 0.808298E+09 | 0.137243E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630462E+09 |
Annual Sum or Average | 0.957291E+10 | 0.162766E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 7282510.79 | 0.383529E+10 |
Minimum of Months | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84093095.63 |
Maximum of Months | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3218658.25 | 0.630462E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779211E+09 | 0.151469E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710032E+09 | 0.195347E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643355E+09 | 0.304480E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623377E+09 | 0.333815E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617771E+09 | 0.453921E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521404E+09 | 0.438233E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728588E+09 | 0.471821E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557402E+09 | 0.373077E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569394E+09 | 0.270349E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794965E+09 | 0.175827E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714101E+09 | 0.963815E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635036E+09 | 0.115478E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789464E+10 | 0.338020E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521404E+09 | 0.963815E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794965E+09 | 0.471821E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2244.98 | 02-JAN-16:19 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 36826.23 | 04-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2244.98 | 01-FEB-17:10 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 32691.76 | 01-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2244.98 | 01-MAR-17:19 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 28080.14 | 06-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2244.98 | 01-APR-18:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 863.86 | 23-APR-16:05 | 19026.72 | 04-APR-19:55 |
May | 30255.31 | 06-MAY-18:10 | 2244.98 | 01-MAY-19:30 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3100.77 | 25-MAY-18:00 | 9087.51 | 01-MAY-20:00 |
June | 30255.31 | 03-JUN-18:10 | 2244.98 | 01-JUN-19:49 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5768.82 | 29-JUN-17:05 | 6441.75 | 02-JUN-12:00 |
July | 30255.31 | 01-JUL-18:10 | 2244.98 | 01-JUL-20:19 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2922.32 | 29-JUL-17:03 | 6492.63 | 08-JUL-19:00 |
August | 30255.31 | 05-AUG-18:10 | 2244.98 | 01-AUG-19:40 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.22 | 08-AUG-17:03 | 7170.21 | 17-AUG-11:55 |
September | 30255.31 | 02-SEP-18:10 | 2244.98 | 01-SEP-18:49 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 716.80 | 01-SEP-16:05 | 9418.38 | 23-SEP-18:52 |
October | 30255.31 | 07-OCT-18:10 | 2244.98 | 02-OCT-17:19 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 14918.36 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2244.98 | 01-NOV-16:40 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 26716.16 | 25-NOV-19:10 |
December | 30255.31 | 02-DEC-19:10 | 2244.98 | 01-DEC-16:19 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 34620.73 | 19-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6441.75 | |||||
Maximum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5768.82 | 36826.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 805.14 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1518.25 | 04-JAN-03:00 |
February | 813.01 | 04-FEB-19:10 | 805.14 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1478.83 | 13-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 805.14 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1100.27 | 17-MAR-04:00 |
April | 813.01 | 01-APR-18:10 | 805.14 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 7.22 | 23-APR-15:55 | 885.09 | 02-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 805.14 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 9.49 | 24-MAY-15:00 | 532.18 | 09-MAY-04:00 |
June | 813.01 | 03-JUN-18:10 | 805.14 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 50.54 | 29-JUN-15:00 | 532.03 | 20-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 805.14 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 37.82 | 15-JUL-15:00 | 401.92 | 06-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 805.14 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 30.66 | 08-AUG-16:00 | 413.29 | 17-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 805.14 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.33 | 01-SEP-15:00 | 667.94 | 20-SEP-03:50 |
October | 813.01 | 07-OCT-18:10 | 805.14 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 770.40 | 31-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 805.14 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1299.12 | 22-NOV-02:00 |
December | 813.01 | 02-DEC-19:10 | 805.14 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1320.24 | 16-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 401.92 | ||||||
Maximum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 50.54 | 1518.25 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014.85 | 28-JAN-02:50 | 5357.51 | 27-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.01 | 17-FEB-07:45 | 5088.90 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.45 | 03-MAR-01:00 | 8433.49 | 23-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2090.38 | 22-APR-04:00 | 6960.73 | 21-APR-13:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.32 | 18-MAY-04:25 | 8045.90 | 01-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.61 | 04-JUN-04:00 | 7329.39 | 14-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2049.50 | 15-JUL-04:53 | 8221.20 | 13-JUL-12:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.97 | 05-AUG-03:52 | 7157.52 | 04-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.83 | 06-SEP-05:40 | 5839.41 | 01-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1860.45 | 25-OCT-07:00 | 5766.86 | 09-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1799.17 | 19-NOV-07:30 | 3444.55 | 07-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.39 | 03-DEC-01:25 | 4581.64 | 02-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1282.39 | 3444.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.97 | 8433.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 74537.68 | 06-JAN-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.26 |
February | 66836.77 | 14-FEB-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.39 |
March | 59012.27 | 05-MAR-00:01 | 16808.50 | 4988.87 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.62 |
April | 42616.02 | 04-APR-23:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.34 |
May | 29103.40 | 07-MAY-04:01 | 0.00 | 3741.59 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 |
June | 33068.91 | 29-JUN-05:02 | 16808.50 | 4157.39 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.74 |
July | 29163.51 | 29-JUL-18:04 | 151276.53 | 8418.67 | 26550.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2489.05 | 0.00 |
August | 28226.01 | 08-AUG-17:03 | 80680.82 | 5051.20 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.22 | 0.00 |
September | 30134.87 | 06-SEP-04:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38825.64 | 29-OCT-23:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49538.42 | 25-NOV-00:01 | 16808.50 | 4988.87 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.92 |
December | 72727.27 | 25-DEC-00:01 | 16808.50 | 4988.87 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28226.01 | 0.00 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74537.68 | 151276.53 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3066.22 | 1425.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64170.39 | 06-JAN-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 |
February | 61536.00 | 14-FEB-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 187.23 |
March | 56579.14 | 05-MAR-05:01 | 0.00 | 1341.86 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40062.65 | 05-APR-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 |
May | 39447.56 | 26-MAY-03:11 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 119.93 |
June | 47355.22 | 20-JUN-03:21 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 419.21 |
July | 51613.69 | 11-JUL-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 |
August | 44156.07 | 26-AUG-04:01 | 0.00 | 1341.86 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 |
September | 52202.08 | 12-SEP-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.71 |
October | 39137.45 | 30-OCT-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 52.53 |
November | 48269.62 | 29-NOV-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 71.16 |
December | 55486.87 | 26-DEC-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 136.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39137.45 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64170.39 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 419.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.81 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.77 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.88 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.80 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.16 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.47 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.14 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.44 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.32 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.41 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.16 | 134.32 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.696221E+11 | 39995.61 | 04-JAN-11:09 | 0.358865E+12 | 266503.94 | 06-JAN-07:10 |
February | 0.617296E+11 | 39688.94 | 13-FEB-11:09 | 0.268006E+12 | 252404.37 | 14-FEB-07:30 |
March | 0.671809E+11 | 39318.99 | 15-MAR-10:20 | 0.238940E+12 | 219402.76 | 05-MAR-07:19 |
April | 0.636552E+11 | 43656.50 | 23-APR-16:19 | 0.137841E+12 | 162932.71 | 05-APR-06:30 |
May | 0.701746E+11 | 53679.54 | 26-MAY-10:00 | 0.859384E+11 | 111823.45 | 01-MAY-06:30 |
June | 0.764840E+11 | 69016.03 | 30-JUN-11:00 | 0.730892E+11 | 62304.63 | 04-JUN-05:30 |
July | 0.847852E+11 | 62080.19 | 21-JUL-11:00 | 0.725086E+11 | 50189.76 | 03-JUL-18:30 |
August | 0.791566E+11 | 62187.12 | 08-AUG-17:19 | 0.722610E+11 | 57222.31 | 19-AUG-05:10 |
September | 0.658992E+11 | 52787.39 | 01-SEP-10:00 | 0.770743E+11 | 70716.11 | 06-SEP-06:10 |
October | 0.662454E+11 | 40273.49 | 19-OCT-17:19 | 0.121328E+12 | 140190.82 | 30-OCT-06:49 |
November | 0.651546E+11 | 39128.12 | 25-NOV-11:09 | 0.188952E+12 | 179126.47 | 29-NOV-07:40 |
December | 0.693961E+11 | 39843.64 | 20-DEC-11:09 | 0.333362E+12 | 237884.90 | 20-DEC-07:10 |
Annual Sum or Average | 0.839483E+12 | 0.202817E+13 | ||||
Minimum of Months | 0.617296E+11 | 39128.12 | 0.722610E+11 | 50189.76 | ||
Maximum of Months | 0.847852E+11 | 69016.03 | 0.358865E+12 | 266503.94 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.477735E+10 | 0.331557E+10 | 0.382185E+11 | 0.00 | 0.130718E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639956E+10 | 0.00 |
February | 0.426199E+10 | 0.268856E+10 | 0.345199E+11 | 0.00 | 0.109867E+11 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579176E+10 | 0.00 |
March | 0.470824E+10 | 0.256113E+10 | 0.382185E+11 | 0.00 | 0.113380E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646780E+10 | 0.00 |
April | 0.442549E+10 | 0.206063E+10 | 0.369856E+11 | 0.00 | 0.968406E+10 | 36657632.61 | 0.00 | 0.385302E+09 | 0.00 | 0.00 | 0.00 | 0.620820E+10 | 0.00 |
May | 0.452143E+10 | 0.178942E+10 | 0.382185E+11 | 0.00 | 0.927971E+10 | 37879553.69 | 0.00 | 0.552357E+10 | 0.00 | 0.00 | 0.00 | 0.642089E+10 | 0.00 |
June | 0.437472E+10 | 0.155935E+10 | 0.369856E+11 | 0.00 | 0.923179E+10 | 36657632.61 | 0.00 | 0.136167E+11 | 0.00 | 0.00 | 0.00 | 0.623800E+10 | 0.00 |
July | 0.446073E+10 | 0.168144E+10 | 0.382185E+11 | 0.00 | 0.966304E+10 | 37879553.69 | 0.00 | 0.197120E+11 | 0.00 | 0.00 | 0.00 | 0.637220E+10 | 0.00 |
August | 0.461153E+10 | 0.196347E+10 | 0.382185E+11 | 0.00 | 0.940749E+10 | 37879553.69 | 0.00 | 0.138404E+11 | 0.00 | 0.00 | 0.00 | 0.645081E+10 | 0.00 |
September | 0.446612E+10 | 0.229557E+10 | 0.369856E+11 | 0.00 | 0.895301E+10 | 36657632.61 | 0.00 | 0.269742E+10 | 0.00 | 0.00 | 0.00 | 0.620062E+10 | 0.00 |
October | 0.467221E+10 | 0.280522E+10 | 0.382185E+11 | 0.00 | 0.980230E+10 | 37879553.69 | 0.00 | 0.262309E+09 | 0.00 | 0.00 | 0.00 | 0.639339E+10 | 0.00 |
November | 0.461682E+10 | 0.309438E+10 | 0.369856E+11 | 0.00 | 0.104605E+11 | 36657632.61 | 0.00 | 4499929.23 | 0.00 | 0.00 | 0.00 | 0.619199E+10 | 0.00 |
December | 0.479376E+10 | 0.341607E+10 | 0.382185E+11 | 0.00 | 0.127282E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639141E+10 | 0.00 |
Annual Sum or Average | 0.546904E+11 | 0.292308E+11 | 0.449992E+12 | 0.00 | 0.124607E+12 | 0.446001E+09 | 0.00 | 0.560422E+11 | 0.00 | 0.00 | 0.00 | 0.755266E+11 | 0.00 |
Minimum of Months | 0.426199E+10 | 0.155935E+10 | 0.345199E+11 | 0.00 | 0.895301E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579176E+10 | 0.00 |
Maximum of Months | 0.479376E+10 | 0.341607E+10 | 0.382185E+11 | 0.00 | 0.130718E+11 | 37879553.69 | 0.00 | 0.197120E+11 | 0.00 | 0.00 | 0.00 | 0.646780E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.280619E+12 | 0.00 | 0.383467E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.196546E+12 | 0.00 | 0.354218E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.159657E+12 | 0.00 | 0.393834E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.624569E+11 | 0.00 | 0.367711E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.979765E+10 | 0.00 | 0.362410E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.119877E+10 | 0.00 | 0.332778E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.183752E+09 | 0.00 | 0.324251E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.421285E+09 | 0.00 | 0.319400E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.756714E+10 | 0.00 | 0.308945E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.484024E+11 | 0.00 | 0.330257E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.116661E+12 | 0.00 | 0.336789E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.256763E+12 | 0.00 | 0.366989E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.114027E+13 | 0.00 | 0.418105E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.183752E+09 | 0.00 | 0.308945E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.280619E+12 | 0.00 | 0.393834E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3050.12 | 02-JAN-16:19 | 2175.41 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 7126.12 | 06-JAN-07:10 | 17.86 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 |
February | 3050.12 | 01-FEB-17:10 | 2175.41 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 6979.33 | 14-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 3050.12 | 01-MAR-17:19 | 2175.41 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 6763.16 | 05-MAR-07:10 | 17.86 | 05-MAR-09:00 | 0.00 | 01-MAR-00:10 |
April | 3050.12 | 01-APR-18:10 | 2175.41 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 5726.17 | 05-APR-06:10 | 17.86 | 16-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 3050.12 | 01-MAY-19:30 | 2175.41 | 01-MAY-19:30 | 24359.61 | 01-MAY-10:09 | 0.00 | 5127.00 | 01-MAY-05:10 | 17.86 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 3050.12 | 01-JUN-19:49 | 2175.41 | 01-JUN-19:00 | 24359.61 | 01-JUN-10:09 | 0.00 | 7735.44 | 29-JUN-17:00 | 17.86 | 12-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 3050.12 | 01-JUL-20:19 | 2175.41 | 01-JUL-20:19 | 24359.61 | 01-JUL-10:09 | 0.00 | 6508.70 | 15-JUL-13:00 | 17.86 | 03-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 3050.12 | 01-AUG-19:40 | 2175.41 | 01-AUG-19:49 | 24359.61 | 01-AUG-10:09 | 0.00 | 6558.15 | 08-AUG-17:10 | 17.86 | 10-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 3050.12 | 01-SEP-18:49 | 2175.41 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 4677.75 | 06-SEP-05:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 3050.12 | 02-OCT-17:19 | 2175.41 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 5500.05 | 30-OCT-05:10 | 17.86 | 03-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 3050.12 | 01-NOV-16:40 | 2175.41 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 6139.61 | 25-NOV-07:10 | 17.86 | 20-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 3050.12 | 01-DEC-16:19 | 2175.41 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 6952.98 | 24-DEC-07:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 4677.75 | 17.86 | 0.00 | ||||||
Maximum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 7735.44 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.49 | 17-JAN-19:19 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4742.12 | 22-FEB-07:49 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 4742.00 | 08-MAR-07:40 | 0.00 |
April | 11868.10 | 23-APR-17:19 | 0.00 | 0.00 | 0.00 | 4741.94 | 19-APR-18:00 | 0.00 |
May | 19890.49 | 25-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4742.08 | 08-MAY-06:40 | 0.00 |
June | 32324.40 | 29-JUN-17:49 | 0.00 | 0.00 | 0.00 | 4740.59 | 02-JUN-06:19 | 0.00 |
July | 27517.71 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 4739.09 | 10-JUL-06:19 | 0.00 |
August | 26718.50 | 08-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4739.11 | 25-AUG-06:40 | 0.00 |
September | 16764.43 | 01-SEP-17:19 | 0.00 | 0.00 | 0.00 | 4740.86 | 06-SEP-06:49 | 0.00 |
October | 6665.63 | 19-OCT-16:10 | 0.00 | 0.00 | 0.00 | 4741.52 | 06-OCT-06:49 | 0.00 |
November | 527.39 | 01-NOV-16:19 | 0.00 | 0.00 | 0.00 | 4742.01 | 08-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.86 | 28-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4739.09 | 0.00 | ||
Maximum of Months | 32324.40 | 0.00 | 0.00 | 0.00 | 4742.12 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39995.61 | 04-JAN-11:09 | 2488.87 | 24359.61 | 0.00 | 0.00 | 6615.65 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 39688.94 | 13-FEB-11:09 | 2488.87 | 24359.61 | 0.00 | 0.00 | 6220.68 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 39318.99 | 15-MAR-10:20 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5808.24 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 43656.50 | 23-APR-16:19 | 1659.23 | 21945.94 | 0.00 | 0.00 | 4040.03 | 17.86 | 0.00 | 11276.26 | 0.00 |
May | 53679.54 | 26-MAY-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4458.59 | 17.86 | 0.00 | 16155.37 | 0.00 |
June | 69016.03 | 30-JUN-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 7618.05 | 17.86 | 0.00 | 31424.03 | 0.00 |
July | 62080.19 | 21-JUL-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 6316.53 | 17.86 | 0.00 | 25813.49 | 0.00 |
August | 62187.12 | 08-AUG-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 6556.69 | 17.86 | 0.00 | 26697.55 | 0.00 |
September | 52787.39 | 01-SEP-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4364.95 | 17.86 | 0.00 | 15563.33 | 0.00 |
October | 40273.49 | 19-OCT-17:19 | 3050.12 | 20336.83 | 2175.41 | 0.00 | 4040.03 | 17.86 | 0.00 | 4601.40 | 0.00 |
November | 39128.12 | 25-NOV-11:09 | 2212.31 | 24359.61 | 0.00 | 0.00 | 5729.84 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 39843.64 | 20-DEC-11:09 | 2488.87 | 24359.61 | 0.00 | 0.00 | 6325.76 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39128.12 | 1659.23 | 20336.83 | 0.00 | 0.00 | 4040.03 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69016.03 | 3050.12 | 24359.61 | 2175.41 | 0.00 | 7618.05 | 17.86 | 0.00 | 31424.03 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 219822.24 | 06-JAN-07:10 | 0.00 | 37286.05 | 31-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 209508.31 | 14-FEB-07:10 | 0.00 | 37637.99 | 23-FEB-19:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 192826.74 | 05-MAR-07:10 | 0.00 | 37589.34 | 06-MAR-07:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 120512.15 | 05-APR-05:10 | 0.00 | 36885.20 | 03-APR-18:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 74842.50 | 01-MAY-05:10 | 0.00 | 35364.52 | 01-MAY-06:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 45005.42 | 04-JUN-05:10 | 0.00 | 32943.12 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 14950.29 | 02-JUL-05:10 | 0.00 | 30333.51 | 03-JUL-06:49 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 30426.74 | 19-AUG-05:10 | 0.00 | 28542.33 | 01-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 40982.65 | 06-SEP-05:10 | 0.00 | 29070.62 | 29-SEP-06:49 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 103107.76 | 30-OCT-05:10 | 0.00 | 31258.73 | 30-OCT-06:49 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 148728.97 | 29-NOV-06:10 | 0.00 | 33770.43 | 30-NOV-07:49 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 206160.42 | 19-DEC-04:19 | 0.00 | 35753.78 | 28-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 14950.29 | 0.00 | 28542.33 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 219822.24 | 0.00 | 37637.99 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
February | 2.33 | 16.67 | 0.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
March | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.50 | 0.17 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.50 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
Annual Sum or Average | 12.00 | 16.37 | 0.33 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 19.50 | 0.17 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.76 | 0.00 | 29.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 30.68 | 0.00 | 30.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 30.00 | 3.33 | 29.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.70 | 1.50 | 30.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 30.87 | 0.00 | 30.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 30.64 | 0.00 | 30.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 29.80 | 0.00 | 29.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.83 | 30.56 | 4.83 | 30.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.87 | 3.33 | 30.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.70 | 568.50 | 20.69 | 568.50 | 20.68 |
February | 551.00 | 20.70 | 423.00 | 20.66 | 423.00 | 20.64 |
March | 612.00 | 20.70 | 336.17 | 20.62 | 336.17 | 20.57 |
April | 555.33 | 20.92 | 136.67 | 20.76 | 128.67 | 20.63 |
May | 367.00 | 21.43 | 184.17 | 22.09 | 22.50 | 21.98 |
June | 325.17 | 22.84 | 382.00 | 23.43 | 168.50 | 23.53 |
July | 275.17 | 23.37 | 514.33 | 23.76 | 199.33 | 23.81 |
August | 288.67 | 23.11 | 466.67 | 23.61 | 176.00 | 23.67 |
September | 401.83 | 21.46 | 191.33 | 22.14 | 50.83 | 22.17 |
October | 573.50 | 20.86 | 85.67 | 20.75 | 70.67 | 20.60 |
November | 591.00 | 20.76 | 256.50 | 20.64 | 256.50 | 20.57 |
December | 609.00 | 20.70 | 561.17 | 20.69 | 561.17 | 20.68 |
Annual Sum or Average | 5759.67 | 21.21 | 4106.17 | 21.52 | 2961.83 | 21.43 |
Minimum of Months | 275.17 | 20.70 | 85.67 | 20.62 | 22.50 | 20.57 |
Maximum of Months | 612.00 | 23.37 | 568.50 | 23.76 | 568.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.96 | 580.67 | 18.96 | 580.67 | 18.96 |
February | 551.00 | 18.96 | 480.83 | 18.96 | 480.83 | 18.96 |
March | 612.00 | 18.99 | 467.83 | 18.97 | 467.83 | 18.96 |
April | 513.33 | 19.53 | 296.67 | 19.90 | 231.50 | 19.75 |
May | 387.83 | 23.15 | 410.17 | 24.14 | 219.33 | 24.41 |
June | 461.33 | 25.54 | 536.33 | 25.58 | 424.00 | 25.69 |
July | 530.83 | 25.88 | 594.17 | 25.78 | 522.33 | 25.84 |
August | 487.33 | 25.82 | 592.67 | 25.68 | 477.50 | 25.76 |
September | 391.67 | 23.33 | 371.17 | 24.19 | 217.50 | 24.56 |
October | 535.50 | 19.71 | 196.67 | 20.16 | 134.00 | 20.13 |
November | 578.33 | 19.12 | 360.50 | 19.15 | 349.17 | 19.12 |
December | 609.00 | 18.96 | 567.00 | 18.96 | 567.00 | 18.96 |
Annual Sum or Average | 6268.17 | 21.23 | 5454.67 | 21.65 | 4671.67 | 21.68 |
Minimum of Months | 387.83 | 18.96 | 196.67 | 18.96 | 134.00 | 18.96 |
Maximum of Months | 612.00 | 25.88 | 594.17 | 25.78 | 580.67 | 25.84 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.69683 | 13.04032 | -0.7419 | 17.48839 |
February | 551.00000 | 20.69727 | 14.97190 | -0.6752 | 15.64909 |
March | 612.00000 | 20.70209 | 19.04421 | -0.6137 | 13.98063 |
April | 590.00000 | 21.10018 | 24.56945 | -0.4104 | 10.71524 |
May | 611.00000 | 22.43582 | 37.27988 | -0.9402 | 28.48963 |
June | 592.00000 | 23.30853 | 52.46141 | -0.5116 | 14.18814 |
July | 609.00000 | 23.65643 | 58.30303 | -0.3068 | 8.84629 |
August | 612.00000 | 23.49299 | 57.08625 | -0.3884 | 10.42003 |
September | 590.00000 | 22.22622 | 47.06614 | -0.9297 | 27.56940 |
October | 610.00000 | 21.03714 | 34.70392 | -0.3391 | 9.23295 |
November | 591.00000 | 20.75593 | 23.37125 | -0.5553 | 12.66034 |
December | 609.00000 | 20.69822 | 14.47369 | -0.7235 | 16.90162 |
Annual Sum or Average | 7187.00000 | 21.74169 | 33.14303 | -0.5939 | 15.50203 |
Minimum of Months | 551.00000 | 20.69683 | 13.04032 | -0.9402 | 8.84629 |
Maximum of Months | 612.00000 | 23.65643 | 58.30303 | -0.3068 | 28.48963 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.95989 | 19.91497 | -0.8336 | 20.05455 |
February | 551.00000 | 18.96411 | 22.88992 | -0.7839 | 18.40614 |
March | 612.00000 | 18.98998 | 27.72907 | -0.7238 | 16.55173 |
April | 590.00000 | 20.22950 | 32.80356 | -0.3539 | 13.18886 |
May | 611.00000 | 23.60969 | 40.20977 | -0.2696 | 21.10545 |
June | 592.00000 | 25.19299 | 50.36706 | 0.37074 | 14.11133 |
July | 609.00000 | 25.59497 | 54.64571 | 0.58108 | 15.02379 |
August | 612.00000 | 25.42475 | 53.17223 | 0.49935 | 13.75344 |
September | 590.00000 | 23.42575 | 47.85568 | -0.2417 | 19.02194 |
October | 610.00000 | 20.23454 | 41.66199 | -0.2474 | 11.31510 |
November | 591.00000 | 19.23740 | 30.72523 | -0.5980 | 14.33006 |
December | 609.00000 | 18.96236 | 21.15600 | -0.8045 | 19.02566 |
Annual Sum or Average | 7187.00000 | 21.58630 | 37.00879 | -0.2803 | 16.31876 |
Minimum of Months | 551.00000 | 18.95989 | 19.91497 | -0.8336 | 11.31510 |
Maximum of Months | 612.00000 | 25.59497 | 54.64571 | 0.58108 | 21.10545 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.738912E+09 | 0.231697E+09 | 24.03 | 0.606139E+09 | 0.132773E+09 | 0.00 | 0.65 | 23-APR-17:10 | 0.00 | 01-APR-00:01 | 26760.22 | 23-APR-17:10 | 21254.94 | 23-APR-17:05 | 5763.49 | 23-APR-18:10 | 7917.81 | 23-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.114324E+11 | 0.341432E+10 | 188.13 | 0.895317E+10 | 0.247923E+10 | 0.00 | 1.00 | 25-MAY-17:03 | 0.00 | 01-MAY-00:01 | 51498.79 | 25-MAY-17:43 | 38525.34 | 25-MAY-17:57 | 18818.48 | 26-MAY-12:00 | 13570.88 | 25-MAY-17:53 | 0.00 | 01-MAY-00:01 |
June | 0.292846E+11 | 0.825904E+10 | 327.41 | 0.186962E+11 | 0.105884E+11 | 0.00 | 1.00 | 24-JUN-17:03 | 0.00 | 01-JUN-00:01 | 83112.22 | 29-JUN-18:00 | 52605.25 | 29-JUN-17:10 | 41058.53 | 30-JUN-05:03 | 22392.34 | 29-JUN-18:00 | 0.00 | 01-JUN-00:01 |
July | 0.438661E+11 | 0.121202E+11 | 429.96 | 0.260719E+11 | 0.177942E+11 | 0.00 | 1.00 | 03-JUL-16:05 | 0.00 | 01-JUL-00:01 | 68934.27 | 03-JUL-17:30 | 39741.26 | 29-JUL-17:10 | 35128.62 | 05-JUL-11:02 | 17778.46 | 15-JUL-14:00 | 0.00 | 01-JUL-00:01 |
August | 0.290674E+11 | 0.829732E+10 | 349.72 | 0.176507E+11 | 0.114167E+11 | 0.00 | 1.00 | 08-AUG-11:05 | 0.00 | 01-AUG-00:01 | 70913.63 | 08-AUG-17:10 | 40581.56 | 08-AUG-17:10 | 30333.14 | 08-AUG-17:20 | 17970.02 | 08-AUG-17:10 | 0.00 | 01-AUG-00:01 |
September | 0.452858E+10 | 0.141183E+10 | 128.08 | 0.321980E+10 | 0.130878E+10 | 0.00 | 0.93 | 01-SEP-17:10 | 0.00 | 01-SEP-00:01 | 42287.28 | 01-SEP-11:55 | 28453.88 | 01-SEP-17:02 | 15519.77 | 01-SEP-11:20 | 11394.74 | 01-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.437707E+09 | 0.145102E+09 | 22.22 | 0.363252E+09 | 74455884.04 | 0.00 | 0.36 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 | 13810.43 | 19-OCT-13:00 | 11303.39 | 19-OCT-16:05 | 3109.67 | 19-OCT-13:00 | 4404.28 | 19-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.119356E+12 | 0.338795E+11 | 1469.56 | 0.755612E+11 | 0.437945E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.438661E+11 | 0.121202E+11 | 429.96 | 0.260719E+11 | 0.177942E+11 | 0.00 | 1.00 | 0.00 | 83112.22 | 52605.25 | 41058.53 | 22392.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.565997E+09 | 0.153606E+09 | 31.79 | 0.475617E+09 | 90379142.67 | 0.00 | 0.87 | 23-APR-16:20 | 0.00 | 01-APR-00:01 | 16014.10 | 23-APR-16:20 | 13378.88 | 23-APR-16:20 | 2864.07 | 23-APR-18:00 | 3993.72 | 23-APR-16:20 | 0.00 | 01-APR-00:01 |
May | 0.822913E+10 | 0.210925E+10 | 226.49 | 0.646065E+10 | 0.176848E+10 | 0.00 | 1.00 | 17-MAY-04:01 | 0.00 | 01-MAY-00:01 | 38424.27 | 26-MAY-03:11 | 28151.47 | 19-MAY-03:31 | 16370.22 | 26-MAY-03:11 | 9212.19 | 19-MAY-03:31 | 0.00 | 01-MAY-00:01 |
June | 0.220606E+11 | 0.535766E+10 | 387.40 | 0.136165E+11 | 0.844409E+10 | 0.00 | 1.00 | 07-JUN-03:22 | 0.00 | 01-JUN-00:01 | 42691.89 | 29-JUN-10:56 | 30687.42 | 29-JUN-17:00 | 25667.76 | 30-JUN-02:53 | 10308.40 | 29-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.320378E+11 | 0.759182E+10 | 477.11 | 0.183403E+11 | 0.136975E+11 | 0.00 | 1.00 | 01-JUL-03:11 | 0.00 | 01-JUL-00:01 | 42691.89 | 23-JUL-11:00 | 24025.35 | 29-JUL-16:20 | 28066.06 | 05-JUL-10:52 | 9742.84 | 15-JUL-13:53 | 0.00 | 01-JUL-00:01 |
August | 0.227303E+11 | 0.554309E+10 | 420.56 | 0.131369E+11 | 0.959339E+10 | 0.00 | 1.00 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 | 40215.90 | 08-AUG-16:53 | 24251.71 | 08-AUG-15:30 | 23328.08 | 30-AUG-04:01 | 9275.27 | 09-AUG-03:32 | 0.00 | 01-AUG-00:01 |
September | 0.479651E+10 | 0.128559E+10 | 184.20 | 0.317830E+10 | 0.161821E+10 | 0.00 | 1.00 | 01-SEP-03:31 | 0.00 | 01-SEP-00:01 | 38424.27 | 12-SEP-04:01 | 19572.84 | 12-SEP-04:01 | 21507.51 | 01-SEP-03:31 | 9212.19 | 12-SEP-04:01 | 0.00 | 01-SEP-00:01 |
October | 0.406915E+09 | 0.117207E+09 | 27.53 | 0.331785E+09 | 75129808.07 | 0.00 | 0.51 | 19-OCT-15:55 | 0.00 | 01-OCT-00:01 | 8603.62 | 19-OCT-15:55 | 7158.07 | 19-OCT-15:25 | 2083.73 | 20-OCT-03:05 | 2362.81 | 19-OCT-15:55 | 0.00 | 01-OCT-00:01 |
November | 14757669.03 | 4499929.23 | 4.25 | 9696324.49 | 5061344.54 | 0.00 | 0.11 | 01-NOV-16:20 | 0.00 | 01-NOV-00:01 | 1740.34 | 01-NOV-16:20 | 1147.70 | 01-NOV-15:20 | 612.52 | 01-NOV-16:20 | 527.39 | 01-NOV-16:20 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.908420E+11 | 0.221627E+11 | 1759.34 | 0.555497E+11 | 0.352923E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.320378E+11 | 0.759182E+10 | 477.11 | 0.183403E+11 | 0.136975E+11 | 0.00 | 1.00 | 0.00 | 42691.89 | 30687.42 | 28066.06 | 10308.40 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 182.18 | 75.71 | 106.46 | 78.76 | 567.30 | 0.00 | 0.00 | 0.00 |
February | 289.22 | 124.50 | 164.72 | 186.45 | 443.00 | 0.00 | 0.00 | 0.00 |
March | 392.61 | 197.26 | 195.35 | 321.20 | 340.63 | 0.00 | 0.00 | 0.00 |
April | 540.47 | 291.11 | 249.36 | 550.27 | 207.01 | 0.00 | 0.00 | 0.00 |
May | 587.11 | 258.66 | 328.45 | 674.03 | 114.80 | 0.00 | 0.00 | 0.00 |
June | 662.46 | 316.54 | 345.92 | 810.59 | 83.11 | 0.00 | 0.00 | 0.00 |
July | 650.28 | 305.59 | 344.69 | 808.29 | 79.21 | 0.00 | 0.00 | 0.00 |
August | 500.60 | 218.53 | 282.07 | 601.39 | 93.79 | 0.00 | 0.00 | 0.00 |
September | 402.07 | 180.28 | 221.79 | 439.83 | 139.75 | 0.00 | 0.00 | 0.00 |
October | 242.25 | 91.11 | 151.14 | 205.57 | 215.48 | 0.00 | 0.00 | 0.00 |
November | 155.34 | 51.85 | 103.49 | 83.22 | 338.91 | 0.00 | 0.00 | 0.00 |
December | 142.89 | 53.78 | 89.11 | 50.19 | 550.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 396.01 | 180.55 | 215.46 | 401.81 | 263.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.89 | 51.85 | 89.11 | 50.19 | 79.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 662.46 | 316.54 | 345.92 | 810.59 | 567.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 796.57 | 554.46 | 242.11 | 709.99 | 695.40 | 0.00 | 0.00 | 0.00 |
February | 995.97 | 669.68 | 326.30 | 986.96 | 578.53 | 0.00 | 0.00 | 0.00 |
March | 877.50 | 552.63 | 324.87 | 891.20 | 468.75 | 0.00 | 0.00 | 0.00 |
April | 802.95 | 436.35 | 366.60 | 883.54 | 303.03 | 0.00 | 0.00 | 0.00 |
May | 687.61 | 244.02 | 443.59 | 819.69 | 170.90 | 0.00 | 0.00 | 0.00 |
June | 604.26 | 160.68 | 443.58 | 755.84 | 120.71 | 0.00 | 0.00 | 0.00 |
July | 664.99 | 213.21 | 451.79 | 860.62 | 114.68 | 0.00 | 0.00 | 0.00 |
August | 705.18 | 294.36 | 410.82 | 887.19 | 133.46 | 0.00 | 0.00 | 0.00 |
September | 742.90 | 389.29 | 353.61 | 877.91 | 199.12 | 0.00 | 0.00 | 0.00 |
October | 659.07 | 392.76 | 266.30 | 704.22 | 296.30 | 0.00 | 0.00 | 0.00 |
November | 574.68 | 359.87 | 214.81 | 544.31 | 441.29 | 0.00 | 0.00 | 0.00 |
December | 611.77 | 400.77 | 211.00 | 506.78 | 673.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.24 | 387.27 | 337.97 | 784.26 | 348.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.68 | 160.68 | 211.00 | 506.78 | 114.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 995.97 | 669.68 | 451.79 | 986.96 | 695.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 187.16 | 79.37 | 107.79 | 89.29 | 571.91 | 0.00 | 0.00 | 0.00 |
February | 302.53 | 138.94 | 163.59 | 214.98 | 456.02 | 0.00 | 0.00 | 0.00 |
March | 396.41 | 203.21 | 193.21 | 336.64 | 351.79 | 0.00 | 0.00 | 0.00 |
April | 505.72 | 256.28 | 249.43 | 511.50 | 214.94 | 0.00 | 0.00 | 0.00 |
May | 621.86 | 297.17 | 324.69 | 722.90 | 120.52 | 0.00 | 0.00 | 0.00 |
June | 597.70 | 257.89 | 339.81 | 726.98 | 85.50 | 0.00 | 0.00 | 0.00 |
July | 639.03 | 296.96 | 342.07 | 797.47 | 81.89 | 0.00 | 0.00 | 0.00 |
August | 524.56 | 237.51 | 287.05 | 636.02 | 95.41 | 0.00 | 0.00 | 0.00 |
September | 411.75 | 184.66 | 227.08 | 454.79 | 142.51 | 0.00 | 0.00 | 0.00 |
October | 260.64 | 104.90 | 155.74 | 234.00 | 219.59 | 0.00 | 0.00 | 0.00 |
November | 158.76 | 54.08 | 104.67 | 91.98 | 343.33 | 0.00 | 0.00 | 0.00 |
December | 140.00 | 48.65 | 91.35 | 50.06 | 552.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 396.02 | 180.22 | 215.81 | 406.67 | 268.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 140.00 | 48.65 | 91.35 | 50.06 | 81.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 639.03 | 297.17 | 342.07 | 797.47 | 571.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.487943E+09 | 0.202791E+09 | 0.285152E+09 | 0.210942E+09 | 0.151946E+10 |
February | 0.699679E+09 | 0.301198E+09 | 0.398481E+09 | 0.451063E+09 | 0.107172E+10 |
March | 0.105156E+10 | 0.528328E+09 | 0.523227E+09 | 0.860298E+09 | 0.912347E+09 |
April | 0.140089E+10 | 0.754560E+09 | 0.646329E+09 | 0.142631E+10 | 0.536575E+09 |
May | 0.157253E+10 | 0.692804E+09 | 0.879725E+09 | 0.180533E+10 | 0.307480E+09 |
June | 0.171708E+10 | 0.820463E+09 | 0.896621E+09 | 0.210104E+10 | 0.215422E+09 |
July | 0.174171E+10 | 0.818489E+09 | 0.923223E+09 | 0.216491E+10 | 0.212155E+09 |
August | 0.134081E+10 | 0.585316E+09 | 0.755498E+09 | 0.161076E+10 | 0.251197E+09 |
September | 0.104217E+10 | 0.467276E+09 | 0.574891E+09 | 0.114004E+10 | 0.362228E+09 |
October | 0.648845E+09 | 0.244025E+09 | 0.404820E+09 | 0.550586E+09 | 0.577129E+09 |
November | 0.402643E+09 | 0.134408E+09 | 0.268235E+09 | 0.215696E+09 | 0.878459E+09 |
December | 0.382704E+09 | 0.144039E+09 | 0.238665E+09 | 0.134432E+09 | 0.147381E+10 |
Annual Sum or Average | 0.124886E+11 | 0.569370E+10 | 0.679487E+10 | 0.126714E+11 | 0.831798E+10 |
Minimum of Months | 0.382704E+09 | 0.134408E+09 | 0.238665E+09 | 0.134432E+09 | 0.212155E+09 |
Maximum of Months | 0.174171E+10 | 0.820463E+09 | 0.923223E+09 | 0.216491E+10 | 0.151946E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213354E+10 | 0.148508E+10 | 0.648466E+09 | 0.190164E+10 | 0.186256E+10 |
February | 0.240946E+10 | 0.162008E+10 | 0.789383E+09 | 0.238765E+10 | 0.139958E+10 |
March | 0.235030E+10 | 0.148016E+10 | 0.870143E+09 | 0.238699E+10 | 0.125551E+10 |
April | 0.208125E+10 | 0.113103E+10 | 0.950218E+09 | 0.229013E+10 | 0.785462E+09 |
May | 0.184168E+10 | 0.653580E+09 | 0.118811E+10 | 0.219547E+10 | 0.457748E+09 |
June | 0.156624E+10 | 0.416478E+09 | 0.114977E+10 | 0.195914E+10 | 0.312889E+09 |
July | 0.178112E+10 | 0.571050E+09 | 0.121006E+10 | 0.230510E+10 | 0.307148E+09 |
August | 0.188874E+10 | 0.788408E+09 | 0.110033E+10 | 0.237624E+10 | 0.357454E+09 |
September | 0.192559E+10 | 0.100905E+10 | 0.916548E+09 | 0.227554E+10 | 0.516118E+09 |
October | 0.176525E+10 | 0.105198E+10 | 0.713271E+09 | 0.188618E+10 | 0.793600E+09 |
November | 0.148958E+10 | 0.932780E+09 | 0.556796E+09 | 0.141086E+10 | 0.114383E+10 |
December | 0.163857E+10 | 0.107343E+10 | 0.565140E+09 | 0.135737E+10 | 0.180351E+10 |
Annual Sum or Average | 0.228713E+11 | 0.122131E+11 | 0.106582E+11 | 0.247323E+11 | 0.109954E+11 |
Minimum of Months | 0.148958E+10 | 0.416478E+09 | 0.556796E+09 | 0.135737E+10 | 0.307148E+09 |
Maximum of Months | 0.240946E+10 | 0.162008E+10 | 0.121006E+10 | 0.238765E+10 | 0.186256E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.501294E+09 | 0.212587E+09 | 0.288707E+09 | 0.239157E+09 | 0.153181E+10 |
February | 0.731881E+09 | 0.336115E+09 | 0.395766E+09 | 0.520092E+09 | 0.110320E+10 |
March | 0.106176E+10 | 0.544264E+09 | 0.517492E+09 | 0.901664E+09 | 0.942222E+09 |
April | 0.131082E+10 | 0.664287E+09 | 0.646530E+09 | 0.132580E+10 | 0.557120E+09 |
May | 0.166558E+10 | 0.795942E+09 | 0.869642E+09 | 0.193622E+10 | 0.322809E+09 |
June | 0.154925E+10 | 0.668461E+09 | 0.880787E+09 | 0.188434E+10 | 0.221624E+09 |
July | 0.171157E+10 | 0.795377E+09 | 0.916196E+09 | 0.213593E+10 | 0.219330E+09 |
August | 0.140498E+10 | 0.636155E+09 | 0.768830E+09 | 0.170351E+10 | 0.255542E+09 |
September | 0.106725E+10 | 0.478648E+09 | 0.588601E+09 | 0.117881E+10 | 0.369396E+09 |
October | 0.698099E+09 | 0.280962E+09 | 0.417136E+09 | 0.626737E+09 | 0.588149E+09 |
November | 0.411497E+09 | 0.140183E+09 | 0.271313E+09 | 0.238409E+09 | 0.889909E+09 |
December | 0.374976E+09 | 0.130303E+09 | 0.244673E+09 | 0.134088E+09 | 0.148097E+10 |
Annual Sum or Average | 0.124890E+11 | 0.568329E+10 | 0.680567E+10 | 0.128248E+11 | 0.848208E+10 |
Minimum of Months | 0.374976E+09 | 0.130303E+09 | 0.244673E+09 | 0.134088E+09 | 0.219330E+09 |
Maximum of Months | 0.171157E+10 | 0.795942E+09 | 0.916196E+09 | 0.213593E+10 | 0.153181E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 766.02 | 1722.60 | 1165.91 | 709.55 | 456.36 | 0.00 | 0.00 |
February | 1322.95 | 1412.11 | 1587.72 | 933.12 | 654.61 | 0.00 | 0.00 |
March | 1497.08 | 1109.20 | 1666.52 | 953.09 | 713.43 | 0.00 | 0.00 |
April | 1906.76 | 686.43 | 1849.13 | 983.75 | 865.38 | 0.00 | 0.00 |
May | 2195.79 | 385.39 | 1896.58 | 799.85 | 1096.73 | 0.00 | 0.00 |
June | 2281.36 | 277.28 | 1864.42 | 735.11 | 1129.31 | 0.00 | 0.00 |
July | 2456.89 | 266.29 | 1954.30 | 815.75 | 1138.55 | 0.00 | 0.00 |
August | 2117.79 | 315.85 | 1730.34 | 750.40 | 979.94 | 0.00 | 0.00 |
September | 1760.43 | 469.29 | 1556.72 | 754.23 | 802.48 | 0.00 | 0.00 |
October | 1131.92 | 719.50 | 1161.96 | 588.77 | 573.19 | 0.00 | 0.00 |
November | 686.98 | 1091.00 | 888.78 | 465.81 | 422.97 | 0.00 | 0.00 |
December | 513.30 | 1682.80 | 894.66 | 503.20 | 391.46 | 0.00 | 0.00 |
Annual Sum or Average | 1553.84 | 842.49 | 1517.28 | 748.04 | 769.24 | 0.00 | 0.00 |
Minimum of Months | 513.30 | 266.29 | 888.78 | 465.81 | 391.46 | 0.00 | 0.00 |
Maximum of Months | 2456.89 | 1722.60 | 1954.30 | 983.75 | 1138.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205172E+10 | 0.461382E+10 | 0.312278E+10 | 0.190046E+10 | 0.122233E+10 | 0.00 | 0.00 |
February | 0.320049E+10 | 0.341618E+10 | 0.384102E+10 | 0.225739E+10 | 0.158363E+10 | 0.00 | 0.00 |
March | 0.400977E+10 | 0.297089E+10 | 0.446362E+10 | 0.255275E+10 | 0.191086E+10 | 0.00 | 0.00 |
April | 0.494232E+10 | 0.177923E+10 | 0.479295E+10 | 0.254988E+10 | 0.224308E+10 | 0.00 | 0.00 |
May | 0.588120E+10 | 0.103222E+10 | 0.507980E+10 | 0.214233E+10 | 0.293747E+10 | 0.00 | 0.00 |
June | 0.591328E+10 | 0.718700E+09 | 0.483258E+10 | 0.190540E+10 | 0.292717E+10 | 0.00 | 0.00 |
July | 0.658053E+10 | 0.713221E+09 | 0.523440E+10 | 0.218492E+10 | 0.304948E+10 | 0.00 | 0.00 |
August | 0.567228E+10 | 0.845964E+09 | 0.463454E+10 | 0.200988E+10 | 0.262466E+10 | 0.00 | 0.00 |
September | 0.456304E+10 | 0.121639E+10 | 0.403501E+10 | 0.195497E+10 | 0.208004E+10 | 0.00 | 0.00 |
October | 0.303174E+10 | 0.192712E+10 | 0.311219E+10 | 0.157697E+10 | 0.153523E+10 | 0.00 | 0.00 |
November | 0.178064E+10 | 0.282787E+10 | 0.230372E+10 | 0.120737E+10 | 0.109634E+10 | 0.00 | 0.00 |
December | 0.137482E+10 | 0.450722E+10 | 0.239625E+10 | 0.134777E+10 | 0.104848E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490018E+11 | 0.265688E+11 | 0.478488E+11 | 0.235901E+11 | 0.242588E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137482E+10 | 0.713221E+09 | 0.230372E+10 | 0.120737E+10 | 0.104848E+10 | 0.00 | 0.00 |
Maximum of Months | 0.658053E+10 | 0.461382E+10 | 0.523440E+10 | 0.255275E+10 | 0.304948E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639959E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174411564.4 | 81.22 | 0.00 | 0.00 |
February | 0.579166E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157363787.5 | 81.22 | 0.00 | 0.00 |
March | 0.646765E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173795987.8 | 81.22 | 0.00 | 0.00 |
April | 0.620809E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -164616235.2 | 81.22 | 0.00 | 0.00 |
May | 0.642074E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160555000.4 | 81.21 | 0.00 | 0.00 |
June | 0.623776E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151176469.1 | 81.21 | 0.00 | 0.00 |
July | 0.637209E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154986764.0 | 81.21 | 0.00 | 0.00 |
August | 0.645067E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155455202.4 | 81.21 | 0.00 | 0.00 |
September | 0.620043E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155617889.3 | 81.22 | 0.00 | 0.00 |
October | 0.639339E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -169566854.4 | 81.22 | 0.00 | 0.00 |
November | 0.619184E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167217248.8 | 81.22 | 0.00 | 0.00 |
December | 0.639134E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174252594.1 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755252E+11 | -0.735662E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195902E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.579166E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174411564.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646765E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151176469.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288301E+11 | -0.278072E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102298E+10 | 58.99 | 0.00 | 0.00 |
February | 0.266686E+11 | -0.257462E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922403145.3 | 58.99 | 0.00 | 0.00 |
March | 0.296623E+11 | -0.286450E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101731E+10 | 58.99 | 0.00 | 0.00 |
April | 0.276243E+11 | -0.266726E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -951756492.6 | 58.99 | 0.00 | 0.00 |
May | 0.271293E+11 | -0.262330E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -896248827.6 | 59.00 | 0.00 | 0.00 |
June | 0.248133E+11 | -0.239845E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -828857267.5 | 58.99 | 0.00 | 0.00 |
July | 0.240578E+11 | -0.232126E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -845179892.3 | 58.99 | 0.00 | 0.00 |
August | 0.236641E+11 | -0.228144E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849670277.3 | 59.00 | 0.00 | 0.00 |
September | 0.228953E+11 | -0.220260E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -869249521.2 | 58.99 | 0.00 | 0.00 |
October | 0.245409E+11 | -0.235624E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -978528542.7 | 58.99 | 0.00 | 0.00 |
November | 0.251372E+11 | -0.241617E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -975531543.7 | 58.99 | 0.00 | 0.00 |
December | 0.274967E+11 | -0.264752E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102149E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312520E+12 | -0.301341E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111792E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228953E+11 | -0.286450E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102298E+10 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.296623E+11 | -0.220260E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -828857267.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.76 | 0.75 | 01-JAN-08:30 | 3397.41 | 33.73 | 196.33 | 231.83 | 3599.84 | 35.20 | 216.00 | 231.67 |
February | 265.33 | 0.76 | 0.75 | 01-FEB-08:39 | 1940.37 | 27.33 | 211.17 | 252.50 | 2045.11 | 27.44 | 205.33 | 252.33 |
March | 254.17 | 0.76 | 0.75 | 02-MAR-10:39 | 1637.57 | 23.31 | 175.67 | 313.00 | 1571.85 | 23.48 | 187.83 | 314.17 |
April | 296.33 | 0.76 | 0.75 | 01-APR-07:40 | 1506.29 | 21.05 | 143.17 | 353.67 | 1543.17 | 20.99 | 135.00 | 352.17 |
May | 437.50 | 0.76 | 0.75 | 01-MAY-05:49 | 1341.08 | 21.72 | 221.50 | 417.00 | 1308.83 | 21.09 | 215.83 | 417.50 |
June | 401.83 | 0.76 | 0.75 | 01-JUN-04:00 | 1214.11 | 22.70 | 239.83 | 422.67 | 1315.05 | 21.20 | 187.33 | 410.67 |
July | 409.17 | 0.76 | 0.75 | 01-JUL-05:10 | 1305.87 | 22.89 | 259.33 | 425.00 | 1539.86 | 21.50 | 205.33 | 417.33 |
August | 352.83 | 0.76 | 0.75 | 01-AUG-07:40 | 1360.53 | 21.90 | 194.83 | 372.83 | 1292.72 | 21.69 | 192.50 | 374.17 |
September | 344.17 | 0.76 | 0.75 | 01-SEP-06:40 | 1257.78 | 21.71 | 186.50 | 328.83 | 1313.34 | 22.03 | 203.67 | 328.67 |
October | 299.00 | 0.76 | 0.75 | 01-OCT-06:49 | 1049.93 | 23.63 | 183.00 | 287.17 | 1013.53 | 23.64 | 181.00 | 286.83 |
November | 255.50 | 0.77 | 0.75 | 01-NOV-07:00 | 2516.17 | 32.64 | 211.83 | 230.00 | 2504.01 | 32.65 | 209.33 | 229.83 |
December | 226.33 | 0.76 | 0.75 | 01-DEC-08:09 | 2503.62 | 33.43 | 192.67 | 214.50 | 2532.34 | 33.64 | 198.50 | 211.50 |
Annual Sum or Average | 3785.50 | 0.76 | 1650.89 | 24.77 | 2415.83 | 3849.00 | 1698.75 | 24.52 | 2337.67 | 3826.83 | ||
Minimum of Months | 226.33 | 0.76 | 0.75 | 1049.93 | 21.05 | 143.17 | 214.50 | 1013.53 | 20.99 | 135.00 | 211.50 | |
Maximum of Months | 437.50 | 0.77 | 0.75 | 3397.41 | 33.73 | 259.33 | 425.00 | 3599.84 | 35.20 | 216.00 | 417.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139457E+12 | 164928.34 | 01-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.988421E+11 | 164928.34 | 01-FEB-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824190E+11 | 164928.34 | 05-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355679E+11 | 92480.76 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.663975E+10 | 46711.84 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.886664E+09 | 35002.04 | 04-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147001E+09 | 19912.66 | 02-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.327942E+09 | 29239.28 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.565322E+10 | 32206.53 | 06-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301418E+11 | 65473.34 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.631385E+11 | 138182.45 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128503E+12 | 164928.34 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.147001E+09 | 19912.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139457E+12 | 164928.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.850382E+11 | 88373.65 | 06-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583946E+11 | 75831.55 | 25-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.453066E+11 | 72591.36 | 05-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143976E+11 | 52646.08 | 05-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119837E+10 | 24766.57 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72350710.28 | 12488.13 | 04-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9085458.43 | 5379.23 | 19-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400493E+09 | 12108.95 | 06-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858019E+10 | 35517.66 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301900E+11 | 57205.40 | 29-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769077E+11 | 83630.36 | 24-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.850382E+11 | 88373.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.738912E+09 | 0.606139E+09 | 26760.22 | 23-APR-17:10 | 21251.22 | 0.00 |
May | 0.00 | 0.00 | 0.114324E+11 | 0.895317E+10 | 51498.79 | 25-MAY-17:43 | 38463.00 | 0.00 |
June | 0.00 | 0.00 | 0.292846E+11 | 0.186962E+11 | 83112.22 | 29-JUN-18:00 | 50040.00 | 0.00 |
July | 0.00 | 0.00 | 0.438661E+11 | 0.260719E+11 | 68934.27 | 03-JUL-17:30 | 35757.87 | 0.00 |
August | 0.00 | 0.00 | 0.290674E+11 | 0.176507E+11 | 70913.63 | 08-AUG-17:10 | 40581.56 | 0.00 |
September | 0.00 | 0.00 | 0.452858E+10 | 0.321980E+10 | 42287.28 | 01-SEP-11:55 | 26966.37 | 0.00 |
October | 0.00 | 0.00 | 0.437707E+09 | 0.363252E+09 | 13810.43 | 19-OCT-13:00 | 10700.76 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119356E+12 | 0.755612E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.438661E+11 | 0.260719E+11 | 83112.22 | 50040.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.565997E+09 | 0.475617E+09 | 16014.10 | 23-APR-16:20 | 13378.88 | 0.00 |
May | 0.00 | 0.00 | 0.822913E+10 | 0.646065E+10 | 38424.27 | 26-MAY-03:11 | 22054.05 | 0.00 |
June | 0.00 | 0.00 | 0.220606E+11 | 0.136165E+11 | 42691.89 | 29-JUN-10:56 | 23107.58 | 0.00 |
July | 0.00 | 0.00 | 0.320378E+11 | 0.183403E+11 | 42691.89 | 23-JUL-11:00 | 22150.06 | 0.00 |
August | 0.00 | 0.00 | 0.227303E+11 | 0.131369E+11 | 40215.90 | 08-AUG-16:53 | 23096.53 | 0.00 |
September | 0.00 | 0.00 | 0.479651E+10 | 0.317830E+10 | 38424.27 | 12-SEP-04:01 | 19572.84 | 0.00 |
October | 0.00 | 0.00 | 0.406915E+09 | 0.331785E+09 | 8603.62 | 19-OCT-15:55 | 7111.71 | 0.00 |
November | 0.00 | 0.00 | 14757669.03 | 9696324.49 | 1740.34 | 01-NOV-16:20 | 1127.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.908420E+11 | 0.555497E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.320378E+11 | 0.183403E+11 | 42691.89 | 23107.58 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10838.35 | 20954.25 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 11098.27 | 21166.00 | 27-FEB-19:10 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 11150.41 | 21176.44 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 10746.64 | 20740.16 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10251.58 | 19964.82 | 01-MAY-06:46 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9711.40 | 18828.89 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 9126.35 | 17725.70 | 03-JUL-18:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8978.23 | 17037.68 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8957.74 | 17161.38 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 9256.67 | 18033.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9780.38 | 19129.74 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 10342.10 | 20150.02 | 29-DEC-19:20 |
Annual Sum or Average | 0.00 | 10013.40 | ||||
Minimum of Months | 0.00 | 0.00 | 8957.74 | 17037.68 | ||
Maximum of Months | 0.00 | 0.00 | 11150.41 | 21176.44 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.28 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.28 |
March | 0.183946E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.28 |
April | 0.178420E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.191487E+10 | 0.24 | 824.13 | 01-MAY-04:01 | 0.27 |
June | 0.192043E+10 | 0.25 | 824.13 | 01-JUN-04:01 | 0.27 |
July | 0.204739E+10 | 0.25 | 824.13 | 01-JUL-00:35 | 0.27 |
August | 0.204053E+10 | 0.25 | 824.13 | 01-AUG-00:55 | 0.27 |
September | 0.185967E+10 | 0.24 | 824.13 | 01-SEP-00:20 | 0.27 |
October | 0.184873E+10 | 0.23 | 824.13 | 01-OCT-03:15 | 0.27 |
November | 0.178012E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.27 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.223758E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.204739E+10 | 0.25 | 824.13 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.896529E+10 | 0.98 | 6361.43 | 01-JAN-04:02 | 1.47 |
February | 0.744399E+10 | 0.93 | 6361.43 | 01-FEB-04:05 | 1.47 |
March | 0.759063E+10 | 0.89 | 6361.43 | 05-MAR-04:01 | 1.47 |
April | 0.631941E+10 | 0.81 | 4684.81 | 05-APR-04:01 | 1.27 |
May | 0.583488E+10 | 0.75 | 3625.60 | 01-MAY-05:03 | 1.11 |
June | 0.565817E+10 | 0.74 | 5247.69 | 29-JUN-18:00 | 1.32 |
July | 0.580036E+10 | 0.74 | 4041.67 | 22-JUL-18:10 | 1.16 |
August | 0.572153E+10 | 0.73 | 4223.29 | 08-AUG-17:10 | 1.19 |
September | 0.562710E+10 | 0.75 | 3289.91 | 06-SEP-05:03 | 1.04 |
October | 0.637704E+10 | 0.79 | 4059.79 | 30-OCT-04:01 | 1.18 |
November | 0.695746E+10 | 0.86 | 5742.46 | 25-NOV-05:01 | 1.40 |
December | 0.869512E+10 | 0.96 | 6361.43 | 02-DEC-05:01 | 1.47 |
Annual Sum or Average | 0.809910E+11 | 0.83 | |||
Minimum of Months | 0.562710E+10 | 0.73 | 3289.91 | 1.04 | |
Maximum of Months | 0.896529E+10 | 0.98 | 6361.43 | 1.47 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226707E+10 | 0.60 | 1470.15 | 06-JAN-05:02 | 0.87 |
February | 0.188123E+10 | 0.57 | 1356.78 | 25-FEB-05:02 | 0.84 |
March | 0.190793E+10 | 0.54 | 1327.49 | 05-MAR-05:02 | 0.83 |
April | 0.158045E+10 | 0.49 | 1147.20 | 05-APR-04:03 | 0.77 |
May | 0.152996E+10 | 0.48 | 1678.31 | 26-MAY-03:11 | 0.91 |
June | 0.165319E+10 | 0.52 | 1678.31 | 19-JUN-04:01 | 0.91 |
July | 0.181529E+10 | 0.55 | 1678.31 | 03-JUL-04:01 | 0.91 |
August | 0.164544E+10 | 0.53 | 1678.31 | 08-AUG-03:11 | 0.91 |
September | 0.146624E+10 | 0.48 | 1678.31 | 12-SEP-04:01 | 0.92 |
October | 0.157653E+10 | 0.48 | 992.38 | 30-OCT-05:03 | 0.71 |
November | 0.172295E+10 | 0.52 | 1188.42 | 29-NOV-05:03 | 0.78 |
December | 0.219358E+10 | 0.58 | 1427.28 | 24-DEC-05:02 | 0.86 |
Annual Sum or Average | 0.212399E+11 | 0.53 | |||
Minimum of Months | 0.146624E+10 | 0.48 | 992.38 | 0.71 | |
Maximum of Months | 0.226707E+10 | 0.60 | 1678.31 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 46.64 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.62 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 45.45 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 49.56 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 49.86 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 50.59 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.33 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 51.57 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.01 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 50.28 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 50.90 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 46.39 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.45 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.01 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 46.64 | 59.92 | 10838.35 | 20954.25 | 31-JAN-20:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.62 | 59.00 | 11098.27 | 21166.00 | 27-FEB-19:10 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 45.45 | 59.31 | 11150.41 | 21176.44 | 02-MAR-19:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.68 | 47.68 | 10746.64 | 20740.16 | 03-APR-18:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.18 | 48.18 | 10251.58 | 19964.82 | 01-MAY-06:46 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 48.86 | 48.86 | 9711.40 | 18828.89 | 01-JUN-06:57 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 48.98 | 48.98 | 9126.35 | 17725.70 | 03-JUL-18:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 49.42 | 49.42 | 8978.23 | 17037.68 | 01-AUG-18:47 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 49.91 | 49.91 | 8957.74 | 17161.38 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.21 | 47.21 | 9256.67 | 18033.27 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.35 | 49.35 | 9780.38 | 19129.74 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 46.39 | 58.89 | 10342.10 | 20150.02 | 29-DEC-19:20 |
Annual Sum or Average | 0.00 | 10013.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.45 | 47.21 | 8957.74 | 17037.68 | ||
Maximum of Months | 0.00 | 0.00 | 49.91 | 59.92 | 11150.41 | 21176.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.896529E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.744399E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.759063E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.655110E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.924920E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139172E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179206E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.140188E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.703893E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.652214E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.695746E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.869512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114870E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.652214E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.179206E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.226707E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.188123E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.190793E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173406E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.363921E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.701085E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.940710E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.718853E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.275183E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.169374E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172745E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.219358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.434026E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.169374E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.940710E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.896529E+10 | 0.00 | 0.139457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744399E+10 | 0.00 | 0.988421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759063E+10 | 0.00 | 0.824190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631941E+10 | 0.738912E+09 | 0.355679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583488E+10 | 0.114324E+11 | 0.663975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565817E+10 | 0.292846E+11 | 0.886664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.580036E+10 | 0.438661E+11 | 0.147001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572153E+10 | 0.290674E+11 | 0.327942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562710E+10 | 0.452858E+10 | 0.565322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637704E+10 | 0.437707E+09 | 0.301418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695746E+10 | 0.00 | 0.631385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869512E+10 | 0.00 | 0.128503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.809910E+11 | 0.119356E+12 | 0.591723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562710E+10 | 0.00 | 0.147001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896529E+10 | 0.438661E+11 | 0.139457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226707E+10 | 0.00 | 0.850382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188123E+10 | 0.00 | 0.583946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190793E+10 | 0.00 | 0.453066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158045E+10 | 0.565997E+09 | 0.143976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152996E+10 | 0.822815E+10 | 0.119837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165319E+10 | 0.220331E+11 | 72350710.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181529E+10 | 0.320320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164544E+10 | 0.227267E+11 | 9085458.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146624E+10 | 0.479651E+10 | 0.400493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157653E+10 | 0.406915E+09 | 0.858019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172295E+10 | 14757669.03 | 0.301900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219358E+10 | 0.00 | 0.769077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212399E+11 | 0.908042E+11 | 0.320495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226707E+10 | 0.320320E+11 | 0.850382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.896529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631941E+10 | 0.00 | 0.00 | 0.00 | 0.231697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.583488E+10 | 0.00 | 0.00 | 0.00 | 0.341432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565817E+10 | 0.00 | 0.00 | 0.00 | 0.825904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.580036E+10 | 0.00 | 0.00 | 0.00 | 0.121202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572153E+10 | 0.00 | 0.00 | 0.00 | 0.829732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562710E+10 | 0.00 | 0.00 | 0.00 | 0.141183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637704E+10 | 0.00 | 0.00 | 0.00 | 0.145102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.809910E+11 | 0.00 | 0.00 | 0.00 | 0.338795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.562710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896529E+10 | 0.00 | 0.00 | 0.00 | 0.121202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.226707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158045E+10 | 0.00 | 0.00 | 0.00 | 0.153606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152996E+10 | 0.00 | 0.00 | 0.00 | 0.210925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165319E+10 | 0.00 | 0.00 | 0.00 | 0.535766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181529E+10 | 0.00 | 0.00 | 0.00 | 0.759182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164544E+10 | 0.00 | 0.00 | 0.00 | 0.554309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146624E+10 | 0.00 | 0.00 | 0.00 | 0.128559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157653E+10 | 0.00 | 0.00 | 0.00 | 0.117207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172295E+10 | 0.00 | 0.00 | 0.00 | 4499929.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212399E+11 | 0.00 | 0.00 | 0.00 | 0.221627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226707E+10 | 0.00 | 0.00 | 0.00 | 0.759182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129249E+12 | 0.00 | 0.00 | 3.55 |
February | 0.241658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844245E+11 | 0.00 | 0.00 | 3.54 |
March | 0.412875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590161E+11 | 0.00 | 0.00 | 3.54 |
April | 0.511149E+11 | 24629506.84 | 0.00 | 6956425.21 | 0.00 | 0.101312E+11 | 0.330026E+10 | 0.00 | 3.60 |
May | 0.265914E+11 | 0.509573E+09 | 0.00 | 40389971.79 | 0.00 | 0.527915E+09 | 0.115842E+11 | 0.00 | 3.84 |
June | 0.115944E+11 | 0.513067E+10 | 0.00 | 54246770.98 | 21553021.20 | 46440232.65 | 0.128281E+11 | 0.00 | 4.04 |
July | 0.724379E+10 | 0.776414E+10 | 0.00 | 59835502.35 | 8767412.04 | 11689302.52 | 0.106850E+11 | 0.00 | 4.09 |
August | 0.924521E+10 | 0.300264E+10 | 0.00 | 67668955.00 | 0.00 | 7994609.53 | 0.157087E+11 | 0.00 | 4.10 |
September | 0.287107E+11 | 85957068.74 | 0.00 | 30968958.54 | 0.00 | 94899474.06 | 0.136512E+11 | 0.00 | 3.83 |
October | 0.558296E+11 | 0.00 | 0.00 | 5601385.88 | 0.00 | 0.405984E+10 | 0.276605E+10 | 0.00 | 3.59 |
November | 0.476370E+11 | 0.00 | 0.00 | 264525.00 | 0.00 | 0.361109E+11 | 0.461528E+09 | 0.00 | 3.56 |
December | 0.119633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121350E+12 | 0.00 | 0.00 | 3.53 |
Annual Sum or Average | 0.327903E+12 | 0.165176E+11 | 0.00 | 0.265932E+09 | 30320433.25 | 0.445031E+12 | 0.709850E+11 | 0.00 | 3.74 |
Minimum of Months | 0.724379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7994609.53 | 0.00 | 0.00 | 3.53 |
Maximum of Months | 0.558296E+11 | 0.776414E+10 | 0.00 | 67668955.00 | 21553021.20 | 0.129249E+12 | 0.157087E+11 | 0.00 | 4.10 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120621E+12 | 0.00 | 0.00 | 0.00 | 0.128720E+09 | 0.300676E+09 | 0.00 | 0.00 | 8.37 |
February | 0.933946E+11 | 0.00 | 0.00 | 0.00 | 16947771.22 | 0.172488E+09 | 0.00 | 0.00 | 8.18 |
March | 0.864593E+11 | 0.00 | 0.00 | 0.00 | 93611889.57 | 0.112811E+09 | 0.00 | 0.00 | 7.96 |
April | 0.514063E+11 | 0.00 | 0.00 | 9113155.81 | 0.00 | 9200848.44 | 0.534060E+10 | 0.00 | 7.58 |
May | 0.183538E+11 | 0.171138E+09 | 0.00 | 55299633.36 | 0.00 | 0.00 | 0.211563E+11 | 0.00 | 7.55 |
June | 0.609363E+10 | 0.293213E+10 | 0.00 | 75761853.49 | 0.00 | 0.00 | 0.201116E+11 | 0.00 | 7.84 |
July | 0.335107E+10 | 0.416023E+10 | 0.00 | 87482621.80 | 0.00 | 0.00 | 0.162937E+11 | 0.00 | 8.07 |
August | 0.344106E+10 | 0.175050E+10 | 0.00 | 92025970.65 | 0.00 | 0.00 | 0.222327E+11 | 0.00 | 7.83 |
September | 0.163406E+11 | 0.00 | 0.00 | 47018941.56 | 0.00 | 0.00 | 0.240778E+11 | 0.00 | 7.53 |
October | 0.470429E+11 | 0.00 | 0.00 | 8595863.03 | 0.00 | 0.00 | 0.629936E+10 | 0.00 | 7.48 |
November | 0.700974E+11 | 0.00 | 0.00 | 1018848.59 | 46669480.87 | 17786964.74 | 0.112487E+10 | 0.00 | 7.82 |
December | 0.113122E+12 | 0.00 | 0.00 | 0.00 | 0.110533E+09 | 0.231441E+09 | 0.00 | 0.00 | 8.28 |
Annual Sum or Average | 0.629724E+12 | 0.901400E+10 | 0.00 | 0.376317E+09 | 0.396481E+09 | 0.844404E+09 | 0.116637E+12 | 0.00 | 7.87 |
Minimum of Months | 0.335107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
Maximum of Months | 0.120621E+12 | 0.416023E+10 | 0.00 | 92025970.65 | 0.128720E+09 | 0.300676E+09 | 0.240778E+11 | 0.00 | 8.37 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.267940E+11 | 0.354253E+11 | 0.407477E+12 | 0.00 | 0.682574E+11 |
February | 0.494484E+11 | 0.275437E+11 | 0.316802E+12 | 0.00 | 0.518413E+11 |
March | 0.729603E+11 | 0.263207E+11 | 0.298105E+12 | 0.00 | 0.472373E+11 |
April | 0.101654E+12 | 0.175988E+11 | 0.201429E+12 | 0.368119E+09 | 0.307678E+11 |
May | 0.118483E+12 | 0.118758E+11 | 0.140769E+12 | 0.163836E+10 | 0.483870E+11 |
June | 0.125366E+12 | 0.704744E+10 | 0.862902E+11 | 0.192341E+10 | 0.889638E+11 |
July | 0.127026E+12 | 0.435938E+10 | 0.629612E+11 | 0.154876E+10 | 0.122042E+12 |
August | 0.104280E+12 | 0.662030E+10 | 0.946337E+11 | 0.222354E+10 | 0.894041E+11 |
September | 0.765773E+11 | 0.110321E+11 | 0.148275E+12 | 0.176222E+10 | 0.321656E+11 |
October | 0.373951E+11 | 0.151706E+11 | 0.193962E+12 | 0.330470E+09 | 0.257812E+11 |
November | 0.148905E+11 | 0.203011E+11 | 0.250253E+12 | 5041901.84 | 0.347554E+11 |
December | 0.151926E+11 | 0.332782E+11 | 0.383884E+12 | 0.00 | 0.623018E+11 |
Annual Sum or Average | 0.870067E+12 | 0.216573E+12 | 0.258484E+13 | 0.979992E+10 | 0.701905E+12 |
Minimum of Months | 0.148905E+11 | 0.435938E+10 | 0.629612E+11 | 0.00 | 0.257812E+11 |
Maximum of Months | 0.127026E+12 | 0.354253E+11 | 0.407477E+12 | 0.222354E+10 | 0.122042E+12 |