Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:28:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1921.46 | 3759.06 | 3759.06 |
Net Site Energy | 1921.46 | 3759.06 | 3759.06 |
Total Source Energy | 3822.37 | 7477.94 | 7477.94 |
Net Source Energy | 3822.37 | 7477.94 | 7477.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 255.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.49 | 361.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 835.10 | 1086.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 255.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 66.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.49 | 361.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 255.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 35.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 66.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.49 | 361.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 218.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 436.28 | 1206.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 979.41 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1633.76 | 2125.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 218.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 436.28 | 1206.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 979.41 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1633.76 | 2125.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 835.100 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 835.100 | 100.00 |
Total On-Site and Utility Electric Sources | 835.100 | 100.00 |
Total Electricity End Uses | 835.100 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2676.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 8.5664 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6055 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 8.5664 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6055 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.8498 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-17:00 | 19-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 19-APR-18:30 |
Heating | 0.00 | 85236.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20336.83 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6115.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4243.93 | 14925.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1636.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 56329.63 | 113738.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 85236.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 20956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6115.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4243.93 | 14925.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 444.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 998.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 277.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 141.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.08 | 391.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 160.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2644.76 | 1177.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 541.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 413.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 689.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.73 | 765.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 313.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5174.11 | 2303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 541.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 413.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 689.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.73 | 765.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 313.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5174.11 | 2303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.65 |
KITCHEN DIRECT AIR | 1.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.65 | 3.65 | 3.65 | 3.65 | 3.65 | 3.65 | 1.00 | 1.00 | 3.65 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.65 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.54 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.65 | 6234.89 |
PSZ-AC_2:2_ADDAQ FAN | 1.54 | 1643.34 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.65 | 3.65 | 3.65 | 2.41 | 74603.98 | 122717.29 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.01 | 33678.44 | 72967.67 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.65 | 1.82 | 2.43 | 74603.98 | 37301.99 | 0.767690 | 0.767690 |
PSZ-AC_2:2 COOLING COIL | 1.54 | 0.767881 | 1.02 | 33678.44 | 16839.22 | 0.741530 | 0.741530 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 122717.29 |
PSZ-AC_2:2 HEATING COIL | 72967.67 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 8.566 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 73.494 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.605 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1070.246 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3184.542 | 8.566 | 11.368 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3184.542 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1339.051 | 9.605 | 177.878 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1339.051 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1426 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2431 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.935 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.036 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.29769246E-08 | -0.18967486E-14 | 0.17735324E-14 | -0.50565546E-16 |
42 | 6 | 0.41018669E-05 | 0.27270264E-08 | 0.31943096E-02 | -0.26796545E-04 |
43 | 5 | -0.28850807E-03 | 0.16127836E-05 | -0.22397690 | 0.19583774E-02 |
44 | 4 | 0.65943933E-02 | 0.73359200E-04 | 4.8337480 | -0.45305377E-01 |
45 | 3 | -0.57777404E-01 | 0.58296435E-03 | -38.045154 | 0.39891614 |
46 | 2 | 0.20497420 | 0.96924505E-03 | 116.53015 | -1.4185573 |
47 | 1 | -0.29573351 | 0.29504543E-03 | -143.93450 | 2.0494869 |
48 | 0 | 0.14415612 | 0.71556298E-05 | 60.838472 | |
49 | 7 | -0.17284864E-08 | -0.37804902E-15 | 0.73321507E-14 | -0.99177345E-16 |
50 | 6 | 0.68009956E-05 | 0.46606830E-08 | 0.31864372E-02 | -0.26730506E-04 |
51 | 5 | -0.48976058E-03 | 0.27623059E-05 | -0.22352946 | 0.19544281E-02 |
52 | 4 | 0.11270010E-01 | 0.12574428E-03 | 4.8262959 | -0.45233742E-01 |
53 | 3 | -0.98979995E-01 | 0.10001134E-02 | -38.003058 | 0.39845083 |
54 | 2 | 0.35147541 | 0.16637932E-02 | 116.44822 | -1.4174614 |
55 | 1 | -0.50731320 | 0.50715641E-03 | -143.88627 | 2.0486942 |
56 | 0 | 0.24734252 | 0.12206389E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3815_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6351E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6632E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5194E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4379E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3743E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4030E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0828E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0008E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0109E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0176E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.3003E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.3136E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.0831E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.0746E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0253E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0253E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6249E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5824E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3867E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4497E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3541E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3356E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0008E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0828E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 41219.12685 | 49462.95222 | 3.04094 | 3.64912 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7495.55615 | 8994.66738 | 0.32592 | 1.33138 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -4.20000 | 2.69032E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20444.72573 | 24533.67088 | 1.27980 | 1.53576 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 307.55515 | 369.06618 | 1.20991E-002 | 1.21700 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 57284.99 | 3.64912 | 3.64912 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 70190.08 | 1.33138 | 1.33138 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 27739.85 | 1.53576 | 1.53576 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64160.22 | 1.21700 | 1.21700 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.64912 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53576 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.64912 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.64912 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.64912 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.64912 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.64912 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.64912 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53576 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53576 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53576 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53576 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53576 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53576 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.64912 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.53576 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.64912 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.64912 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6234.88516 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.64912 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.64912 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.64912 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.40842 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.64912 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.82456 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.43275 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 74603.98000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37301.99000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76769 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76769 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 74603.98000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 122717.28537 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 122717.28537 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53576 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53576 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1643.33713 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53576 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53576 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53576 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01360 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53576 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76788 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02384 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33678.44000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16839.22000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74153 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74153 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33678.44000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 72967.67472 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 72967.67472 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 71970.0 | 10.45 | 10.40 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 32575.6 | 11.61 | 11.56 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | N/A | 2.168 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | N/A | 2.168 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | N/A | 2.168 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.143 | 0.138 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.243 | 0.230 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.2986126999E-002 | 0.3209315895 | Pass | Pass | 0.1058914970 | 0.2850968669 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1498558430 | 0.5622094729 | Pass | Pass | 2.7252395414E-002 | 9.2674253876E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 9.7468377884E-002 | 8.8075527627E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 799.43 | 151.72 | 1884.78 | 12.57 | 429.70 | 3278.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.139 | 0.143 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.234 | 0.243 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 8.5664 | 371.75 | 3184.54 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.64 | 0.0000 | Y | 47.60 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6055 | 139.41 | 1339.05 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.17 |
Interior Lighting Total | 8.8498 | 511.15 | 4523.59 | 66.78 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3184.54 | 796.14 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3184.54 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 158.08 | AstronomicalClock | - | 49.59 | 49.59 | 1.47 | |
EXTERIOR_LIGHTS_B | 3137.97 | AstronomicalClock | - | 83.55 | 73.36 | 43.21 | |
Exterior Lighting Total | 3296.05 | 44.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 74603.98 | 57272.73 | 17331.25 | 0.77 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33678.44 | 24973.57 | 8704.87 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 71970.0 | 10.45 | 10.40 | ||||
PSZ-AC_2:2 COOLING COIL | 32575.6 | 11.61 | 11.56 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 122717.29 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 72967.67 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.65 | 6234.89 | 1708.60 | 1.00 | 1.18 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1643.34 | 1070.05 | 1.00 | 1.36 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 41219.13 | 49462.95 | 133.06 | 3.041 | 3.649 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00999 | 29.30 | 0.00882 | 1.331 | 0.00 |
KITCHEN | 20444.73 | 24533.67 | 175.99 | 1.280 | 1.536 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.01038 | 28.46 | 0.00882 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7495.56 | 8994.67 | 24.20 | 0.326 | 1.331 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00763 | -4.20 | 0.00269 | 1.331 | 0.00 |
KITCHEN | 307.56 | 369.07 | 2.65 | 0.012 | 1.217 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.00 | 0.00295 | -4.20 | 0.00269 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.65 | 3.65 | 1.33 | 1.33 | 3.6491 | 3.6491 | 3.6491 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.22 | 1.22 | 1.5358 | 1.5358 | 1.5358 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 74603.980 | 57272.729 | 3.649120 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 37301.99 | 31545.70 | 2.432747 | 25.96 | 17.80 | 0.00956528 | 11.39 | 11.39 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 54.7273 | 23.99 | 0.00999259 | 52.9278 | 41212.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 122717.285 | 122717.285 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 122717.29 | 122717.29 | 3.649123 | 11.81 | 8.72 | 0.00582870 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 36.4849 | 21.00 | 0.00763148 | 48.6619 | 7486.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33678.440 | 24973.574 | 1.535760 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 16839.22 | 15557.51 | 1.023840 | 28.85 | 18.36 | 0.00907486 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 118.8664 | 25.99 | 0.01040157 | 48.8851 | 20444.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 72967.675 | 72967.675 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 72967.67 | 72967.67 | 1.535761 | 0.17 | -1.43 | 0.00282677 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 79.2442 | 19.00 | 0.00334775 | 24.3275 | 203.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 74603.980 | 57272.729 | 3.649120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6214 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.649123 | 4.33147531 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 37301.99 | 31545.70 | 1.0000 | 2.88764787 | 2.432747 | 25.96 | 17.80 | 0.00956528 | 50472.1 | 11.39 | 11.39 | 0.00850000 | 32885.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37301.99 | 29.40 | 0.00882150 | 18.34 | 1.33137743 | 54.7273 | 23.99 | 0.00999259 | 23.99 | 0.00999259 | 52.9278 | 41212.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 122717.285 | 122717.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.649123 | 4.33147531 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 122717.29 | 122717.29 | 1.0000 | 4.33147531 | 3.649123 | 11.81 | 8.72 | 0.00582870 | 26567.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 122717.29 | -4.20 | 0.00269032 | -4.20 | 1.33137743 | 36.4849 | 21.00 | 0.00763148 | 21.00 | 0.00763148 | 48.6619 | 7486.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33678.440 | 24973.574 | 1.535760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7097 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.535761 | 1.82293445 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 16839.22 | 15557.51 | 1.0000 | 1.21528864 | 1.023840 | 28.85 | 18.36 | 0.00907486 | 52167.7 | 11.92 | 11.61 | 0.00850000 | 33421.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16839.22 | 29.40 | 0.00882150 | 18.34 | 1.21700195 | 118.8664 | 25.94 | 0.01040157 | 25.99 | 0.01040157 | 48.8851 | 20444.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 72967.675 | 72967.675 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.535761 | 1.82293445 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 72967.67 | 72967.67 | 1.0000 | 1.82293445 | 1.535761 | 0.17 | -1.43 | 0.00282677 | 7237.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72967.67 | -4.20 | 0.00269032 | -4.20 | 1.21700195 | 79.2442 | 16.83 | 0.00334775 | 19.00 | 0.00334775 | 24.3275 | 203.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.65 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2100.50 | 5178.33 | 469.00 |
KITCHEN | 4153.83 | 5275.33 | 2568.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4262.17 | 7024.00 | 2676.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 66.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 66.17 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.477 | 0.935 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.835 | 0.032 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.105 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.405 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36507149.01 | 0.00 | 36507149.01 | 7603005.14 | 44110154.16 | 41986318.57 | 1460.00 | 5994.99 | 1305.01 | 113.00 |
KITCHEN | 27100391.99 | 0.00 | 27100391.99 | 156168.02 | 27256560.01 | 38379373.44 | 8731.68 | 27.45 | 0.87 | 359.36 |
Total Facility | 63607541.01 | 0.00 | 63607541.01 | 7759173.16 | 71366714.17 | 80365692.01 | 8732.03 | 5995.49 | 1305.71 | 359.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3901 | 0.0000 | 1.3901 | 0.2901 | 1.6802 | 1.3314 | 0.00 | 5882.01 | 1304.99 |
KITCHEN | 1.0260 | 0.0000 | 1.0260 | 0.0037 | 1.0297 | 1.2170 | 7159.21 | 27.38 | 0.42 |
Total Facility | 2.4160 | 0.0000 | 2.4160 | 0.2938 | 2.7098 | 2.5484 | 7159.21 | 5882.51 | 1305.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 51436496.39 | 0.00 | 51436496.39 | 41986318.57 | 1460.00 | 0.00 | 7300.00 | 113.00 |
PSZ-AC_2:2 | 38183020.78 | 0.00 | 38183020.78 | 38379373.44 | 1457.39 | 0.12 | 7302.49 | 359.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9585 | 0.0000 | 1.9585 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4455 | 0.0000 | 1.4455 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1073.26 | 239.05 | 5987.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 114.12 | 882.32 | 6549.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.3759 | 2.1147 | 1.8763 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7035 | 1.4674 | 1.4437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
Electricity:Building | 523.70 | 3391.80 | 01-JAN-01:10 | 29524.97 | 02-JAN-11:10 |
Electricity:Zone:DINING | 172.88 | 943.57 | 01-JAN-01:10 | 9073.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 516.77 | 3255.52 | 01-JAN-01:10 | 27381.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 66.78 | 542.10 | 10-JUN-05:00 | 3713.52 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:DINING | 47.61 | 384.03 | 10-JUN-05:00 | 2765.04 | 02-JAN-16:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 66.78 | 542.10 | 10-JUN-05:00 | 3713.52 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity | 66.78 | 542.10 | 10-JUN-05:00 | 3713.52 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 47.61 | 384.03 | 10-JUN-05:00 | 2765.04 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 66.78 | 542.10 | 10-JUN-05:00 | 3713.52 | 02-JAN-16:10 |
Electricity:Zone:KITCHEN | 350.82 | 2448.23 | 01-JAN-01:10 | 20451.55 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 50.64 | 852.62 | 19-FEB-23:30 | 3214.25 | 14-SEP-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 119.65 | 1033.97 | 12-FEB-01:10 | 6466.58 | 15-JUL-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 14.00 | 0.00 | 01-JAN-11:10 | 1504.25 | 12-SEP-03:50 |
MedTempRefrigeration:Refrigeration:Electricity | 29.71 | 737.53 | 25-MAR-05:00 | 1076.23 | 28-FEB-04:50 |
ElectricityPurchased:Facility | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
ElectricityPurchased:Plant | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
Cogeneration:ElectricityPurchased | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
General:Cogeneration:ElectricityPurchased | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
ElectricityNet:Plant | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
Cogeneration:ElectricityNet | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
General:Cogeneration:ElectricityNet | 835.10 | 6622.35 | 12-FEB-01:10 | 56329.63 | 10-AUG-18:00 |
Electricity:HVAC | 147.07 | 0.00 | 01-JAN-01:10 | 27072.30 | 10-AUG-18:00 |
Fans:Electricity | 111.24 | 0.00 | 01-JAN-01:10 | 6115.31 | 10-AUG-18:00 |
General:Fans:Electricity | 111.24 | 0.00 | 01-JAN-01:10 | 6115.31 | 10-AUG-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 35.83 | 0.00 | 01-JAN-00:10 | 20956.99 | 10-AUG-18:00 |
General:Cooling:Electricity | 35.83 | 0.00 | 01-JAN-00:10 | 20956.99 | 10-AUG-18:00 |
ExteriorLights:Electricity | 44.68 | 0.00 | 01-JAN-08:10 | 3296.05 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.68 | 0.00 | 01-JAN-08:10 | 3296.05 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.49 | 0.00 | 01-JAN-01:10 | 4741.89 | 11-MAY-06:30 |
Water Heater:WaterSystems:Electricity | 75.49 | 0.00 | 01-JAN-01:10 | 4741.89 | 11-MAY-06:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 01-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1086.36 | 2758.01 | 03-JAN-01:10 | 113738.73 | 19-FEB-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 255.56 | 0.00 | 01-JAN-01:10 | 91831.30 | 19-FEB-06:10 |
Heating:NaturalGas | 255.56 | 0.00 | 01-JAN-01:10 | 91831.30 | 19-FEB-06:10 |
General:Heating:NaturalGas | 255.56 | 0.00 | 01-JAN-01:10 | 91831.30 | 19-FEB-06:10 |
NaturalGas:Plant | 361.01 | 947.76 | 01-JAN-00:10 | 29775.80 | 09-FEB-19:50 |
WaterSystems:NaturalGas | 361.01 | 947.76 | 01-JAN-00:10 | 29775.80 | 09-FEB-19:50 |
Water Heater:WaterSystems:NaturalGas | 361.01 | 947.76 | 01-JAN-00:10 | 29775.80 | 09-FEB-19:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 04-MAY-18:30 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 04-MAY-18:30 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 19-APR-18:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1331.84 | 2933.07 | 25-MAR-00:10 | 147228.82 | 10-AUG-18:10 |
EnergyTransfer:Building | 672.55 | 1466.53 | 25-MAR-00:10 | 50905.59 | 10-AUG-17:20 |
EnergyTransfer:Zone:KITCHEN | 417.37 | 1466.53 | 25-MAR-00:10 | 24893.28 | 18-APR-04:10 |
Refrigeration:EnergyTransfer | 140.00 | 2621.06 | 19-FEB-23:30 | 7834.84 | 28-FEB-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.00 | 1310.53 | 19-FEB-23:30 | 3917.42 | 28-FEB-04:50 |
General:Refrigeration:EnergyTransfer | 70.00 | 1310.53 | 19-FEB-23:30 | 3917.42 | 28-FEB-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.00 | 1310.53 | 19-FEB-23:30 | 3917.42 | 28-FEB-04:50 |
EnergyTransfer:Plant | 325.55 | 1466.53 | 25-MAR-00:10 | 19357.11 | 27-FEB-19:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.10 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.90 | 1222.59 | 25-MAR-05:00 | 2238.70 | 28-FEB-04:50 |
EnergyTransfer:Zone:DINING | 255.18 | 0.00 | 01-JAN-01:10 | 31365.71 | 10-AUG-17:10 |
Heating:EnergyTransfer | 1.05 | 0.00 | 01-JAN-00:10 | 10268.24 | 08-JAN-09:50 |
Heating:EnergyTransfer:Zone:DINING | 1.05 | 0.00 | 01-JAN-00:10 | 10268.24 | 08-JAN-09:50 |
General:Heating:EnergyTransfer | 1.05 | 0.00 | 01-JAN-00:10 | 10268.24 | 08-JAN-09:50 |
General:Heating:EnergyTransfer:Zone:DINING | 1.05 | 0.00 | 01-JAN-00:10 | 10268.24 | 08-JAN-09:50 |
Cooling:EnergyTransfer | 601.49 | 0.00 | 01-JAN-01:10 | 48599.82 | 10-AUG-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 254.12 | 0.00 | 01-JAN-01:10 | 31365.71 | 10-AUG-17:10 |
General:Cooling:EnergyTransfer | 601.49 | 0.00 | 01-JAN-01:10 | 48599.82 | 10-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 254.12 | 0.00 | 01-JAN-01:10 | 31365.71 | 10-AUG-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 347.37 | 0.00 | 01-JAN-01:10 | 21143.03 | 18-APR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 347.37 | 0.00 | 01-JAN-01:10 | 21143.03 | 18-APR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
PlantLoopHeatingDemand:Plant | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
EnergyTransfer:HVAC | 333.74 | 0.00 | 01-JAN-01:10 | 81107.05 | 10-AUG-18:00 |
HeatingCoils:EnergyTransfer | 204.45 | 0.00 | 01-JAN-01:10 | 73465.04 | 19-FEB-06:10 |
CoolingCoils:EnergyTransfer | 129.29 | 0.00 | 01-JAN-00:10 | 81107.05 | 10-AUG-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 255.55 | 0.00 | 01-JAN-01:10 | 16834.37 | 13-FEB-07:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 1.053 | -254.122 | 0.000 | 0.000 | 230.514 | 47.605 | 93.957 | 39.701 | 0.000 | 0.710 | 0.001 | 0.000 | -20.785 | 0.000 | -93.046 | -45.588 |
KITCHEN | 0.000 | 0.000 | 0.000 | -347.355 | 0.000 | 0.000 | 5.894 | 19.174 | 287.132 | 0.000 | 0.000 | 0.003 | 37.705 | 0.000 | 0.000 | 0.000 | -2.553 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.318 | 28.793 | 0.000 | 0.000 | 0.000 | -35.111 | -0.000 |
Total Facility | 0.000 | 0.000 | 1.053 | -601.477 | 0.000 | 0.000 | 236.408 | 66.780 | 381.090 | 39.701 | 0.000 | 7.031 | 66.499 | 0.000 | -20.785 | 0.000 | -130.710 | -45.589 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 19-FEB-00:01 | 0.00 | 0.00 | 0.00 | -32788.30 | 0.00 | 0.00 | 1157.80 | 614.46 | 543.07 | 0.00 | 0.00 | 0.00 | 33042.36 | 0.00 | -2174.39 | 0.00 | -394.99 | 0.00 |
KITCHEN | 18-JUL-04:01 | 0.00 | 0.00 | 0.00 | -51469.42 | 0.00 | 0.00 | 6.27 | 210.77 | 6916.85 | 0.00 | 0.00 | 0.00 | 44377.67 | 0.00 | -0.00 | 0.00 | -42.13 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-04:01 | 0.00 | 0.00 | 0.00 | -67447.75 | 0.00 | 0.00 | 953.13 | 825.22 | 9089.15 | 0.00 | 0.00 | 722.63 | 57127.22 | 0.00 | -1178.57 | 0.00 | -91.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-JAN-09:48 | 0.00 | 0.00 | 47409.91 | 0.00 | 0.00 | 0.00 | 4631.19 | 1152.10 | 3801.52 | 2003.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4773.74 | -54224.44 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-JAN-09:48 | -10528.63 | 10528.63 | 47409.91 | -10528.63 | 0.00 | 0.00 | 4767.19 | 1679.03 | 15135.38 | 2003.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4868.76 | -55597.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.6491 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.6491 | 0.3648 | 1.0000 | Not calculated | 1.3314 | 0.3648 | ||
PSZ-AC_2:2 | 1.5358 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5358 | 0.1189 | 1.0000 | Not calculated | 0.1826 | 0.1189 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.6491 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.6491 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3648 | ||
PSZ-AC_2:2 | 1.5358 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5358 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1189 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6491 | 3.6491 | 3.6491 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5358 | 1.5358 | 1.5358 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.6491 | 3.6491 | 3.6491 | 3.6491 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5358 | 1.5358 | 1.5358 | 1.5358 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.6491 | 3.6491 | 3.6491 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5358 | 1.5358 | 1.5358 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.6491 | 3.6491 | 3.6491 | 3.6491 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5358 | 1.5358 | 1.5358 | 1.5358 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 255.56 | 91831.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 35.83 | 20956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 66.78 | 3713.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.68 | 3296.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 111.24 | 6115.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.49 | 4741.89 | 361.01 | 29775.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.00 | 1504.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.71 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 500.63 | 835.10 |
Natural Gas | 469.79 | 1086.36 |
Additional | 0.00 | 0.00 |
Total | 970.42 | 1921.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 130.64 |
Space Heating | 0.00 |
Space Cooling | 70.10 |
Fans (All) | 217.62 |
Service Water Heating | 147.69 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 1633.76 |
Subtotal | 1633.76 |
Natural Gas [MJ/m2] | |
Space Heating | 499.97 |
Service Water Heating | 706.27 |
Miscellaneous (All) | 2125.31 |
Subtotal | 2125.31 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.48 |
Space Heating | 13.30 |
Space Cooling | 1.86 |
Fans (All) | 5.79 |
Service Water Heating | 22.72 |
Receptacle Equipment | 47.87 |
Miscellaneous | 4.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7930.50 | 829.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7504.33 | 528.67 | 392.17 | 332.00 | 2.83 |
Min | 7504.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 829.50 | 392.17 | 332.00 | 2.83 |
Average | 8064.94 | 452.72 | 130.72 | 110.67 | 0.94 |
Sum | 24194.83 | 1358.17 | 392.17 | 332.00 | 2.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824222.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 281151.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 843455.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8731.17 | 28.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6596.00 | 2164.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7581.00 | 732.83 | 233.33 | 158.33 | 54.50 |
Min | 6596.00 | 28.83 | 0.00 | 0.00 | 0.00 |
Max | 8731.17 | 2164.00 | 233.33 | 158.33 | 54.50 |
Average | 7636.06 | 975.22 | 77.78 | 52.78 | 18.17 |
Sum | 22908.17 | 2925.67 | 233.33 | 158.33 | 54.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 822710.00 | 1512.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14770.00 | 4463.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822710.00 | 4463.00 | 0.00 | 0.00 | 0.00 |
Average | 279160.00 | 1991.67 | 0.00 | 0.00 | 0.00 |
Sum | 837480.00 | 5975.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111279E+11 | 31681.02 | 08-JAN-09:41 | -1.7 | -1.7 | 0.120091E+11 | 10742.43 | 21-JAN-19:10 | 2.12 | 1.06 |
February | 0.127981E+11 | 32789.84 | 19-FEB-00:01 | -2.5 | -3.6 | 0.109800E+11 | 12939.38 | 27-FEB-12:00 | 17.80 | 11.29 |
March | 0.187482E+11 | 29593.07 | 01-MAR-05:01 | 0.00 | -1.6 | 0.124353E+11 | 14051.39 | 18-MAR-18:00 | 16.70 | 8.15 |
April | 0.215152E+11 | 23928.29 | 24-APR-04:01 | 4.32 | 3.39 | 0.126058E+11 | 14052.20 | 29-APR-18:19 | 17.93 | 13.44 |
May | 0.246848E+11 | 23828.13 | 11-MAY-04:01 | 4.50 | 3.97 | 0.138225E+11 | 14051.86 | 13-MAY-18:40 | 17.40 | 11.14 |
June | 0.262556E+11 | 25597.30 | 28-JUN-17:03 | 26.52 | 16.73 | 0.142345E+11 | 14052.90 | 10-JUN-18:00 | 26.52 | 16.73 |
July | 0.297373E+11 | 28325.51 | 24-JUL-17:55 | 28.90 | 17.96 | 0.149560E+11 | 14052.65 | 08-JUL-18:49 | 28.90 | 17.96 |
August | 0.311516E+11 | 31372.89 | 10-AUG-17:03 | 31.62 | 18.84 | 0.152210E+11 | 14053.27 | 26-AUG-18:30 | 19.80 | 16.80 |
September | 0.261768E+11 | 24472.08 | 14-SEP-17:03 | 24.45 | 16.70 | 0.139541E+11 | 14052.54 | 09-SEP-18:10 | 24.45 | 16.70 |
October | 0.228048E+11 | 22400.03 | 13-OCT-04:01 | 6.02 | 4.73 | 0.130056E+11 | 13775.01 | 07-OCT-18:19 | 6.02 | 4.73 |
November | 0.163092E+11 | 27238.96 | 11-NOV-05:01 | 1.02 | 0.82 | 0.118282E+11 | 14048.99 | 04-NOV-18:00 | 1.02 | 0.82 |
December | 0.128146E+11 | 30160.65 | 26-DEC-00:01 | -0.7 | -0.7 | 0.119974E+11 | 10742.68 | 02-DEC-19:49 | -0.7 | -0.7 |
Annual Sum or Average | 0.254124E+12 | 0.157049E+12 | ||||||||
Minimum of Months | 0.111279E+11 | 22400.03 | -2.5 | -3.6 | 0.109800E+11 | 10742.43 | -0.7 | -0.7 | ||
Maximum of Months | 0.311516E+11 | 32789.84 | 31.62 | 18.84 | 0.152210E+11 | 14053.27 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287767E+11 | 31639.14 | 06-JAN-05:01 | -1.2 | -1.2 | 0.104081E+11 | 6880.75 | 11-JAN-11:00 | 11.10 | 8.57 |
February | 0.257470E+11 | 33928.42 | 19-FEB-05:01 | -5.6 | -6.1 | 0.942276E+10 | 6934.64 | 27-FEB-11:00 | 16.70 | 10.79 |
March | 0.290819E+11 | 31790.93 | 01-MAR-05:01 | 0.00 | -1.6 | 0.104643E+11 | 6934.79 | 09-MAR-11:00 | 17.20 | 12.45 |
April | 0.280784E+11 | 30959.01 | 28-APR-03:11 | 11.70 | 10.15 | 0.101682E+11 | 6934.92 | 27-APR-10:30 | 11.70 | 10.15 |
May | 0.293886E+11 | 39015.64 | 08-MAY-04:01 | 8.98 | 8.71 | 0.105503E+11 | 6934.95 | 31-MAY-10:50 | 18.80 | 14.69 |
June | 0.288292E+11 | 48152.39 | 09-JUN-04:01 | 11.10 | 9.86 | 0.102449E+11 | 6934.97 | 12-JUN-10:39 | 17.43 | 14.64 |
July | 0.303874E+11 | 51509.12 | 18-JUL-04:01 | 12.30 | 9.11 | 0.105930E+11 | 6934.95 | 17-JUL-10:00 | 12.30 | 9.11 |
August | 0.306922E+11 | 48881.23 | 15-AUG-03:21 | 13.20 | 11.39 | 0.106010E+11 | 6934.95 | 31-AUG-10:50 | 16.88 | 14.80 |
September | 0.289365E+11 | 43196.98 | 16-SEP-04:01 | 11.10 | 11.10 | 0.102384E+11 | 6934.97 | 01-SEP-10:00 | 11.10 | 11.10 |
October | 0.295298E+11 | 30027.54 | 06-OCT-03:42 | 11.20 | 10.58 | 0.105195E+11 | 6934.91 | 04-OCT-10:50 | 11.20 | 10.58 |
November | 0.287128E+11 | 28751.98 | 11-NOV-05:01 | 1.02 | 0.82 | 0.101138E+11 | 6930.53 | 06-NOV-11:00 | 1.02 | 0.82 |
December | 0.292057E+11 | 31151.98 | 26-DEC-05:01 | -0.6 | -0.6 | 0.104115E+11 | 6894.04 | 14-DEC-11:00 | -0.6 | -0.6 |
Annual Sum or Average | 0.347366E+12 | 0.123736E+12 | ||||||||
Minimum of Months | 0.257470E+11 | 28751.98 | -5.6 | -6.1 | 0.942276E+10 | 6880.75 | -0.6 | -0.6 | ||
Maximum of Months | 0.306922E+11 | 51509.12 | 13.20 | 11.39 | 0.106010E+11 | 6934.97 | 18.80 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 | 10.29 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 | 12.22 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 | 13.75 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 | 12.42 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 | 8.04 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.00 | 0.00 | 17.17 | 13.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365871E+09 | 47409.94 | 08-JAN-09:48 | -1.7 |
February | 0.240349E+09 | 40517.23 | 14-FEB-08:10 | 1.20 |
March | 75822984.74 | 11118.12 | 25-MAR-05:03 | 2.20 |
April | 46263330.11 | 10165.61 | 19-APR-05:03 | 1.78 |
May | 25780922.04 | 8225.33 | 29-MAY-05:03 | 9.50 |
June | 6140805.78 | 4954.25 | 15-JUN-05:03 | 8.98 |
July | 457680.63 | 1495.62 | 04-JUL-05:03 | 11.20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 |
September | 6159280.34 | 5671.48 | 28-SEP-05:03 | 8.30 |
October | 30664551.52 | 8589.73 | 29-OCT-05:03 | 6.70 |
November | 75784268.72 | 26490.99 | 28-NOV-05:04 | 4.40 |
December | 0.179746E+09 | 12422.75 | 25-DEC-06:03 | -0.1 |
Annual Sum or Average | 0.105304E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.7 | |
Maximum of Months | 0.365871E+09 | 47409.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.423035E+10 | 2765.04 | 02-JAN-16:10 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.374278E+10 | 2765.04 | 01-FEB-17:10 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.409408E+10 | 2765.04 | 01-MAR-17:40 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.382143E+10 | 2765.04 | 01-APR-18:30 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.391018E+10 | 2765.04 | 01-MAY-17:49 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.375854E+10 | 2765.04 | 01-JUN-19:40 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.382413E+10 | 2765.04 | 01-JUL-19:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.394423E+10 | 2765.04 | 01-AUG-19:10 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.387619E+10 | 2765.04 | 01-SEP-18:40 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.407996E+10 | 2765.04 | 02-OCT-17:40 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.407455E+10 | 2765.04 | 01-NOV-16:19 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.424883E+10 | 2765.04 | 01-DEC-16:19 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.476053E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.374278E+10 | 2765.04 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.424883E+10 | 2765.04 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162018E+10 | 948.48 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.146748E+10 | 948.48 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.164598E+10 | 948.48 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.157428E+10 | 948.48 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.163308E+10 | 948.48 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.159097E+10 | 948.48 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.161658E+10 | 948.48 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.164598E+10 | 948.48 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.157466E+10 | 948.48 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.161999E+10 | 948.48 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.156840E+10 | 948.48 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.161677E+10 | 948.48 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.191743E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.146748E+10 | 948.48 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.164598E+10 | 948.48 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.423035E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128314E+11 |
February | 0.272721E+11 | 0.374278E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104919E+11 |
March | 0.305458E+11 | 0.409408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955630E+10 |
April | 0.292871E+11 | 0.382143E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33577419.29 | 0.754513E+10 |
May | 0.303219E+11 | 0.391018E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1891753.96 | 0.647373E+10 |
June | 0.295292E+11 | 0.375854E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20627377.15 | 0.483312E+10 |
July | 0.300798E+11 | 0.382413E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194282E+09 | 0.364031E+10 |
August | 0.305458E+11 | 0.394423E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457126E+09 | 0.310364E+10 |
September | 0.292871E+11 | 0.387619E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2955990.78 | 0.518518E+10 |
October | 0.300980E+11 | 0.407996E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759141E+10 |
November | 0.290996E+11 | 0.407455E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981142E+10 |
December | 0.300798E+11 | 0.424883E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119829E+11 |
Annual Sum or Average | 0.356244E+12 | 0.476053E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710461E+09 | 0.930464E+11 |
Minimum of Months | 0.272721E+11 | 0.374278E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310364E+10 |
Maximum of Months | 0.305458E+11 | 0.424883E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457126E+09 | 0.128314E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162018E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284081E+09 |
February | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244540E+09 |
March | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255971E+09 |
April | 0.786997E+09 | 0.157428E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 78627.88 | 0.242732E+09 |
May | 0.814802E+09 | 0.163308E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209501E+09 |
June | 0.793501E+09 | 0.159097E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 9271.87 | 0.191893E+09 |
July | 0.808298E+09 | 0.161658E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 796045.00 | 0.159543E+09 |
August | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1964498.60 | 0.146312E+09 |
September | 0.786997E+09 | 0.157466E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108032E+09 |
October | 0.808786E+09 | 0.161999E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225563E+09 |
November | 0.781956E+09 | 0.156840E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245922E+09 |
December | 0.808298E+09 | 0.161677E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238549E+09 |
Annual Sum or Average | 0.957291E+10 | 0.191743E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 2848443.35 | 0.255264E+10 |
Minimum of Months | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108032E+09 |
Maximum of Months | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1964498.60 | 0.284081E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573785E+09 | 0.877533E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533202E+09 | 0.144413E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499061E+09 | 0.247541E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384707E+09 | 0.365515E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397577E+09 | 0.494112E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360660E+09 | 0.500283E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384654E+09 | 0.537750E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463771E+09 | 0.413805E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781063E+09 | 0.347998E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592431E+09 | 0.188151E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551930E+09 | 0.106326E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794701E+09 | 0.774077E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631754E+10 | 0.351105E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360660E+09 | 0.774077E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794701E+09 | 0.537750E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2765.04 | 02-JAN-16:10 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 15411.98 | 07-JAN-20:00 |
February | 30255.31 | 04-FEB-19:10 | 2765.04 | 01-FEB-17:10 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 16592.08 | 18-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2765.04 | 01-MAR-17:40 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 11318.26 | 04-MAR-20:00 |
April | 30255.31 | 01-APR-18:10 | 2765.04 | 01-APR-18:30 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1360.97 | 01-APR-17:03 | 9905.67 | 17-APR-19:00 |
May | 30255.31 | 06-MAY-18:10 | 2765.04 | 01-MAY-17:49 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.98 | 05-MAY-16:00 | 8925.10 | 17-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2765.04 | 01-JUN-19:40 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1515.82 | 28-JUN-17:03 | 7360.48 | 06-JUN-17:53 |
July | 30255.31 | 01-JUL-18:10 | 2765.04 | 01-JUL-19:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2927.25 | 24-JUL-17:55 | 5797.10 | 12-JUL-11:20 |
August | 30255.31 | 05-AUG-18:10 | 2765.04 | 01-AUG-19:10 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4464.80 | 10-AUG-17:03 | 6182.25 | 01-AUG-11:10 |
September | 30255.31 | 02-SEP-18:10 | 2765.04 | 01-SEP-18:40 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 408.78 | 14-SEP-17:00 | 7353.30 | 16-SEP-18:55 |
October | 30255.31 | 07-OCT-18:10 | 2765.04 | 02-OCT-17:40 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 8912.34 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2765.04 | 01-NOV-16:19 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 11920.69 | 13-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2765.04 | 01-DEC-16:19 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 13792.76 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5797.10 | |||||
Maximum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4464.80 | 16592.08 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 948.48 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 875.58 | 28-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 948.48 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 784.54 | 16-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 948.48 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 629.64 | 29-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 948.48 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 8.23 | 01-APR-16:00 | 809.19 | 08-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 948.48 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 515.82 | 17-MAY-02:00 |
June | 813.01 | 03-JUN-18:10 | 948.48 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 2.08 | 28-JUN-17:00 | 944.56 | 13-JUN-03:00 |
July | 813.01 | 01-JUL-18:10 | 948.48 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 14.83 | 24-JUL-14:10 | 454.30 | 02-JUL-03:30 |
August | 813.01 | 05-AUG-18:10 | 948.48 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 24.22 | 08-AUG-17:00 | 711.35 | 11-AUG-03:50 |
September | 813.01 | 02-SEP-18:10 | 948.48 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 382.61 | 19-SEP-01:00 |
October | 813.01 | 07-OCT-18:10 | 948.48 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 646.89 | 28-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 948.48 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 643.44 | 29-NOV-03:00 |
December | 813.01 | 02-DEC-19:10 | 948.48 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 623.59 | 17-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 382.61 | ||||||
Maximum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 24.22 | 944.56 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1299.19 | 06-JAN-02:70 | 3923.39 | 20-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1563.79 | 27-FEB-03:55 | 4380.91 | 08-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.47 | 01-MAR-21:00 | 6506.04 | 14-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.64 | 27-APR-02:00 | 7198.09 | 18-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1309.32 | 15-MAY-03:00 | 8382.23 | 31-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.57 | 09-JUN-04:40 | 7685.50 | 09-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.52 | 08-JUL-02:53 | 7702.58 | 13-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1382.41 | 09-AUG-05:35 | 7323.64 | 06-AUG-12:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.81 | 10-SEP-05:00 | 6599.09 | 08-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.18 | 12-OCT-03:00 | 5037.32 | 11-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1499.40 | 04-NOV-20:00 | 4149.55 | 04-NOV-13:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.60 | 06-DEC-04:00 | 3286.24 | 06-DEC-12:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.57 | 3286.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.60 | 8382.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31681.02 | 08-JAN-09:41 | 67234.01 | 11520.96 | 50686.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4631.96 |
February | 32789.84 | 19-FEB-00:01 | 16808.50 | 6144.57 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.99 |
March | 29593.07 | 01-MAR-05:01 | 16808.50 | 6144.57 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.93 |
April | 23928.29 | 24-APR-04:01 | 16808.50 | 6144.57 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.56 |
May | 23828.13 | 11-MAY-04:01 | 16808.50 | 6144.57 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.21 |
June | 25597.30 | 28-JUN-17:03 | 80680.82 | 6221.35 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1515.82 | 0.00 |
July | 28325.51 | 24-JUL-17:55 | 53787.21 | 4147.56 | 11585.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2927.25 | 0.00 |
August | 31372.89 | 10-AUG-17:03 | 107574.42 | 8295.13 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 4464.80 | 0.00 |
September | 24472.08 | 14-SEP-17:03 | 107574.42 | 8295.13 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 272.30 | 0.00 |
October | 22400.03 | 13-OCT-04:01 | 16808.50 | 6144.57 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 |
November | 27238.96 | 11-NOV-05:01 | 0.00 | 4608.35 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 |
December | 30160.65 | 26-DEC-00:01 | 16808.50 | 4608.35 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22400.03 | 0.00 | 4147.56 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32789.84 | 107574.42 | 11520.96 | 50686.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4464.80 | 4631.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31639.14 | 06-JAN-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 |
February | 33928.42 | 19-FEB-05:01 | 0.00 | 1580.75 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.82 |
March | 31790.93 | 01-MAR-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
April | 30959.01 | 28-APR-03:11 | 0.00 | 1264.60 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 288.39 |
May | 39015.64 | 08-MAY-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 |
June | 48152.39 | 09-JUN-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 |
July | 51509.12 | 18-JUL-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 |
August | 48881.23 | 15-AUG-03:21 | 0.00 | 1264.60 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 122.21 |
September | 43196.98 | 16-SEP-04:01 | 0.00 | 1580.75 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 |
October | 30027.54 | 06-OCT-03:42 | 0.00 | 948.45 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 115.68 |
November | 28751.98 | 11-NOV-05:01 | 0.00 | 1580.75 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 |
December | 31151.98 | 26-DEC-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28751.98 | 0.00 | 948.45 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51509.12 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 288.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.80 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.31 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.55 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.25 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.83 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.65 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.80 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.84 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.96 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.697058E+11 | 39016.57 | 07-JAN-11:20 | 0.135943E+12 | 110474.76 | 06-JAN-07:49 |
February | 0.623263E+11 | 38876.75 | 13-FEB-11:09 | 0.112555E+12 | 113738.73 | 19-FEB-07:10 |
March | 0.680438E+11 | 38800.71 | 09-MAR-11:00 | 0.100150E+12 | 89757.42 | 02-MAR-07:19 |
April | 0.660334E+11 | 46512.33 | 27-APR-17:10 | 0.833511E+11 | 81229.07 | 19-APR-05:10 |
May | 0.690787E+11 | 47148.95 | 06-MAY-10:00 | 0.766631E+11 | 63166.15 | 18-MAY-06:30 |
June | 0.691661E+11 | 47505.77 | 28-JUN-17:19 | 0.682824E+11 | 45594.26 | 15-JUN-06:49 |
July | 0.761360E+11 | 53432.57 | 31-JUL-10:00 | 0.685881E+11 | 43662.75 | 04-JUL-10:39 |
August | 0.795779E+11 | 56329.63 | 10-AUG-17:00 | 0.686686E+11 | 43570.81 | 06-AUG-10:09 |
September | 0.698135E+11 | 47750.03 | 14-SEP-10:00 | 0.677265E+11 | 50202.82 | 27-SEP-06:30 |
October | 0.685465E+11 | 41718.34 | 04-OCT-17:49 | 0.789880E+11 | 60683.51 | 16-OCT-06:49 |
November | 0.669864E+11 | 41108.82 | 04-NOV-16:49 | 0.100453E+12 | 89752.01 | 13-NOV-07:40 |
December | 0.696857E+11 | 38941.59 | 26-DEC-11:09 | 0.124988E+12 | 103968.56 | 26-DEC-07:49 |
Annual Sum or Average | 0.835100E+12 | 0.108636E+13 | ||||
Minimum of Months | 0.623263E+11 | 38800.71 | 0.677265E+11 | 43570.81 | ||
Maximum of Months | 0.795779E+11 | 56329.63 | 0.135943E+12 | 113738.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.585053E+10 | 0.500692E+10 | 0.382185E+11 | 0.00 | 0.102348E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639739E+10 | 0.00 |
February | 0.521026E+10 | 0.407945E+10 | 0.345199E+11 | 0.00 | 0.901940E+10 | 34213790.43 | 0.00 | 30697114.10 | 0.00 | 0.00 | 0.00 | 0.578824E+10 | 0.00 |
March | 0.574006E+10 | 0.390933E+10 | 0.382185E+11 | 0.00 | 0.949944E+10 | 37879553.69 | 0.00 | 47757739.61 | 0.00 | 0.00 | 0.00 | 0.646183E+10 | 0.00 |
April | 0.539571E+10 | 0.317367E+10 | 0.369856E+11 | 0.00 | 0.894093E+10 | 36657632.61 | 0.00 | 0.116304E+10 | 0.00 | 0.00 | 0.00 | 0.620240E+10 | 0.00 |
May | 0.554326E+10 | 0.278674E+10 | 0.382185E+11 | 0.00 | 0.909247E+10 | 37879553.69 | 0.00 | 0.255827E+10 | 0.00 | 0.00 | 0.00 | 0.642064E+10 | 0.00 |
June | 0.534951E+10 | 0.244531E+10 | 0.369856E+11 | 0.00 | 0.874869E+10 | 36657632.61 | 0.00 | 0.496078E+10 | 0.00 | 0.00 | 0.00 | 0.623854E+10 | 0.00 |
July | 0.544071E+10 | 0.262722E+10 | 0.382185E+11 | 0.00 | 0.914656E+10 | 37879553.69 | 0.00 | 0.970050E+10 | 0.00 | 0.00 | 0.00 | 0.637277E+10 | 0.00 |
August | 0.559021E+10 | 0.303984E+10 | 0.382185E+11 | 0.00 | 0.927373E+10 | 37879553.69 | 0.00 | 0.123415E+11 | 0.00 | 0.00 | 0.00 | 0.645050E+10 | 0.00 |
September | 0.545085E+10 | 0.351778E+10 | 0.369856E+11 | 0.00 | 0.877201E+10 | 36657632.61 | 0.00 | 0.444560E+10 | 0.00 | 0.00 | 0.00 | 0.619704E+10 | 0.00 |
October | 0.569995E+10 | 0.426531E+10 | 0.382185E+11 | 0.00 | 0.914801E+10 | 37879553.69 | 0.00 | 0.447352E+09 | 0.00 | 0.00 | 0.00 | 0.638624E+10 | 0.00 |
November | 0.564295E+10 | 0.468062E+10 | 0.369856E+11 | 0.00 | 0.932160E+10 | 36657632.61 | 0.00 | 0.136287E+09 | 0.00 | 0.00 | 0.00 | 0.618757E+10 | 0.00 |
December | 0.586560E+10 | 0.515129E+10 | 0.382185E+11 | 0.00 | 0.100386E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638892E+10 | 0.00 |
Annual Sum or Average | 0.667796E+11 | 0.446835E+11 | 0.449992E+12 | 0.00 | 0.111236E+12 | 0.446001E+09 | 0.00 | 0.358317E+11 | 0.00 | 0.00 | 0.00 | 0.754921E+11 | 0.00 |
Minimum of Months | 0.521026E+10 | 0.244531E+10 | 0.345199E+11 | 0.00 | 0.874869E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578824E+10 | 0.00 |
Maximum of Months | 0.586560E+10 | 0.515129E+10 | 0.382185E+11 | 0.00 | 0.102348E+11 | 37879553.69 | 0.00 | 0.123415E+11 | 0.00 | 0.00 | 0.00 | 0.646183E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.635244E+11 | 0.00 | 0.325189E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.469258E+11 | 0.00 | 0.295912E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.275843E+11 | 0.00 | 0.326657E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.141574E+11 | 0.00 | 0.305811E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.618339E+10 | 0.00 | 0.305800E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.986541E+09 | 0.00 | 0.286832E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 86906429.64 | 0.00 | 0.286015E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 77585109.40 | 0.00 | 0.286913E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.118305E+10 | 0.00 | 0.279308E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.945007E+10 | 0.00 | 0.296382E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.320794E+11 | 0.00 | 0.297609E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.533216E+11 | 0.00 | 0.317669E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.255560E+12 | 0.00 | 0.361010E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 77585109.40 | 0.00 | 0.279308E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.635244E+11 | 0.00 | 0.326657E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3713.52 | 02-JAN-16:10 | 3296.05 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 5487.96 | 15-JAN-07:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3713.52 | 01-FEB-17:10 | 3296.05 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 5744.87 | 19-FEB-06:10 | 17.86 | 07-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3713.52 | 01-MAR-17:40 | 3296.05 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 5136.78 | 01-MAR-06:10 | 17.86 | 05-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 3713.52 | 01-APR-18:30 | 3296.05 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 5075.94 | 19-APR-05:10 | 17.86 | 17-APR-23:10 | 0.00 | 01-APR-00:10 |
May | 3713.52 | 01-MAY-17:49 | 3296.05 | 01-MAY-19:19 | 24359.61 | 01-MAY-10:09 | 0.00 | 4712.09 | 18-MAY-05:10 | 17.86 | 19-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 3713.52 | 01-JUN-19:40 | 3296.05 | 01-JUN-19:00 | 24359.61 | 01-JUN-10:09 | 0.00 | 4400.55 | 15-JUN-05:10 | 17.86 | 11-JUN-09:30 | 0.00 | 01-JUN-00:10 |
July | 3713.52 | 01-JUL-19:10 | 3296.05 | 01-JUL-20:10 | 24359.61 | 01-JUL-10:09 | 0.00 | 5176.67 | 31-JUL-17:19 | 17.86 | 01-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 3713.52 | 01-AUG-19:10 | 3296.05 | 01-AUG-19:40 | 24359.61 | 01-AUG-10:09 | 0.00 | 6115.31 | 10-AUG-17:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 3713.52 | 01-SEP-18:40 | 3296.05 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 4488.44 | 27-SEP-05:10 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 3713.52 | 02-OCT-17:40 | 3296.05 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 4655.14 | 29-OCT-05:10 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 3713.52 | 01-NOV-16:19 | 3296.05 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 5185.88 | 11-NOV-06:10 | 17.86 | 17-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 3713.52 | 01-DEC-16:19 | 3296.05 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 5307.21 | 26-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 4400.55 | 17.86 | 0.00 | ||||||
Maximum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 6115.31 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.12 | 12-JAN-19:30 | 0.00 |
February | 2810.22 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 4741.41 | 13-FEB-07:49 | 0.00 |
March | 2985.97 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 4741.24 | 23-MAR-06:49 | 0.00 |
April | 13326.01 | 27-APR-17:19 | 0.00 | 0.00 | 0.00 | 4741.84 | 07-APR-06:30 | 0.00 |
May | 12446.03 | 05-MAY-17:00 | 0.00 | 0.00 | 0.00 | 4741.89 | 11-MAY-06:30 | 0.00 |
June | 14242.03 | 28-JUN-17:19 | 0.00 | 0.00 | 0.00 | 4739.59 | 01-JUN-06:30 | 0.00 |
July | 17702.79 | 31-JUL-17:19 | 0.00 | 0.00 | 0.00 | 4737.87 | 03-JUL-06:19 | 0.00 |
August | 20956.99 | 10-AUG-17:00 | 0.00 | 0.00 | 0.00 | 4738.45 | 18-AUG-06:19 | 0.00 |
September | 13465.56 | 14-SEP-17:10 | 0.00 | 0.00 | 0.00 | 4738.69 | 28-SEP-06:40 | 0.00 |
October | 6737.82 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4740.84 | 18-OCT-06:19 | 0.00 |
November | 6449.13 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4740.91 | 15-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.24 | 20-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4737.87 | 0.00 | ||
Maximum of Months | 20956.99 | 0.00 | 0.00 | 0.00 | 4741.89 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39016.57 | 07-JAN-11:20 | 2686.43 | 24359.61 | 0.00 | 0.00 | 5024.57 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 38876.75 | 13-FEB-11:09 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4900.12 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 38800.71 | 09-MAR-11:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 3975.42 | 17.86 | 0.00 | 1283.25 | 0.00 |
April | 46512.33 | 27-APR-17:10 | 3022.26 | 20336.83 | 0.00 | 0.00 | 3997.63 | 17.86 | 0.00 | 13234.15 | 0.00 |
May | 47148.95 | 06-MAY-10:00 | 2686.43 | 24359.61 | 0.00 | 0.00 | 4059.37 | 17.86 | 0.00 | 9425.35 | 0.00 |
June | 47505.77 | 28-JUN-17:19 | 3022.26 | 20336.83 | 0.00 | 0.00 | 4118.15 | 17.86 | 0.00 | 14242.03 | 0.00 |
July | 53432.57 | 31-JUL-10:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4493.54 | 17.86 | 0.00 | 15542.03 | 0.00 |
August | 56329.63 | 10-AUG-17:00 | 3022.26 | 20336.83 | 0.00 | 0.00 | 6115.31 | 17.86 | 0.00 | 20956.99 | 0.00 |
September | 47750.03 | 14-SEP-10:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4114.85 | 17.86 | 0.00 | 10227.07 | 0.00 |
October | 41718.34 | 04-OCT-17:49 | 3713.52 | 20336.83 | 3296.05 | 0.00 | 3975.42 | 17.86 | 0.00 | 4650.51 | 0.00 |
November | 41108.82 | 04-NOV-16:49 | 3713.52 | 21945.94 | 3296.05 | 0.00 | 3975.42 | 17.86 | 0.00 | 3531.66 | 0.00 |
December | 38941.59 | 26-DEC-11:09 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4995.71 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 38800.71 | 2686.43 | 20336.83 | 0.00 | 0.00 | 3975.42 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56329.63 | 3713.52 | 24359.61 | 3296.05 | 0.00 | 6115.31 | 17.86 | 0.00 | 20956.99 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 77898.92 | 08-JAN-06:00 | 0.00 | 29723.16 | 31-JAN-19:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 91831.30 | 19-FEB-06:10 | 0.00 | 29775.80 | 09-FEB-19:49 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 57121.23 | 01-MAR-06:10 | 0.00 | 29610.24 | 02-MAR-07:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 54443.75 | 19-APR-05:10 | 0.00 | 28555.73 | 04-APR-06:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 33675.44 | 18-MAY-05:10 | 0.00 | 27009.30 | 02-MAY-06:49 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 17432.38 | 15-JUN-05:10 | 0.00 | 25120.46 | 02-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 9056.91 | 04-JUL-05:10 | 0.00 | 23210.69 | 05-JUL-06:00 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 6080.14 | 21-AUG-05:10 | 0.00 | 22581.10 | 31-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 21036.41 | 27-SEP-05:10 | 0.00 | 23719.99 | 27-SEP-06:30 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 29897.79 | 29-OCT-05:10 | 0.00 | 25653.25 | 30-OCT-06:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 60230.55 | 11-NOV-06:10 | 0.00 | 27511.67 | 30-NOV-07:49 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 67101.75 | 26-DEC-07:10 | 0.00 | 28895.04 | 29-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 6080.14 | 0.00 | 22581.10 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 91831.30 | 0.00 | 29775.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 30.19 | 0.00 | 30.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 29.77 | 0.00 | 29.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 30.28 | 0.00 | 30.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 30.21 | 0.00 | 30.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 30.66 | 0.00 | 30.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 30.75 | 0.00 | 30.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 30.92 | 0.00 | 30.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 30.68 | 0.00 | 30.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 30.05 | 0.00 | 30.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 30.11 | 0.00 | 30.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 66.17 | 30.68 | 0.00 | 30.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 30.92 | 0.00 | 30.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.75 | 118.33 | 20.58 | 118.33 | 20.46 |
February | 543.67 | 20.81 | 90.17 | 20.64 | 89.83 | 20.51 |
March | 599.67 | 20.93 | 58.17 | 20.77 | 58.17 | 20.64 |
April | 507.17 | 21.17 | 69.33 | 21.24 | 29.50 | 21.12 |
May | 418.00 | 21.41 | 132.67 | 21.94 | 8.33 | 21.89 |
June | 258.17 | 21.72 | 274.00 | 22.88 | 1.67 | 22.89 |
July | 152.50 | 22.03 | 406.50 | 23.44 | 2.67 | 23.44 |
August | 117.67 | 22.04 | 461.83 | 23.58 | 5.00 | 23.58 |
September | 274.17 | 21.58 | 265.83 | 22.74 | 1.83 | 22.73 |
October | 512.67 | 21.18 | 75.33 | 21.39 | 15.83 | 21.31 |
November | 575.67 | 20.90 | 57.67 | 20.80 | 47.17 | 20.68 |
December | 609.00 | 20.75 | 90.67 | 20.57 | 90.67 | 20.43 |
Annual Sum or Average | 5178.33 | 21.09 | 2100.50 | 21.63 | 469.00 | 21.50 |
Minimum of Months | 117.67 | 20.75 | 57.67 | 20.57 | 1.67 | 20.43 |
Maximum of Months | 610.00 | 22.04 | 461.83 | 23.58 | 118.33 | 23.58 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 600.17 | 19.25 | 183.67 | 19.21 | 176.33 | 19.16 |
February | 481.33 | 19.53 | 199.67 | 19.82 | 141.33 | 19.70 |
March | 490.83 | 20.20 | 144.67 | 20.62 | 67.83 | 20.52 |
April | 343.67 | 21.27 | 269.00 | 22.59 | 79.50 | 22.82 |
May | 344.83 | 23.50 | 414.83 | 24.30 | 189.83 | 24.63 |
June | 375.50 | 25.53 | 531.17 | 25.37 | 342.17 | 25.53 |
July | 435.17 | 25.96 | 594.33 | 25.69 | 433.17 | 25.78 |
August | 469.83 | 25.97 | 609.33 | 25.74 | 469.67 | 25.81 |
September | 354.67 | 25.54 | 535.67 | 25.28 | 327.50 | 25.45 |
October | 315.67 | 22.17 | 330.67 | 23.33 | 97.50 | 23.67 |
November | 458.83 | 19.96 | 189.50 | 20.59 | 92.33 | 20.57 |
December | 604.83 | 19.43 | 151.33 | 19.32 | 151.17 | 19.25 |
Annual Sum or Average | 5275.33 | 22.05 | 4153.83 | 22.99 | 2568.33 | 23.26 |
Minimum of Months | 315.67 | 19.25 | 144.67 | 19.21 | 67.83 | 19.16 |
Maximum of Months | 604.83 | 25.97 | 609.33 | 25.74 | 469.67 | 25.81 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.75199 | 35.26521 | -0.4739 | 10.46812 |
February | 551.00000 | 20.85042 | 37.05379 | -0.4102 | 9.68517 |
March | 612.00000 | 20.99405 | 38.36406 | -0.3296 | 8.34130 |
April | 590.00000 | 21.55473 | 42.32504 | -0.1406 | 7.53757 |
May | 611.00000 | 22.18389 | 46.18167 | -0.9691 | 28.61490 |
June | 592.00000 | 22.94462 | 47.16546 | -0.6759 | 17.78035 |
July | 609.00000 | 23.42599 | 49.50699 | -0.4665 | 11.79558 |
August | 612.00000 | 23.54895 | 52.66780 | -0.3961 | 10.14750 |
September | 590.00000 | 22.78290 | 52.91735 | -0.6899 | 18.73579 |
October | 610.00000 | 21.60372 | 46.68738 | -0.0933 | 6.95303 |
November | 591.00000 | 20.97016 | 43.97378 | -0.3173 | 8.31090 |
December | 609.00000 | 20.75384 | 37.42401 | -0.4461 | 9.89612 |
Annual Sum or Average | 7187.00000 | 21.87026 | 44.16038 | -0.4510 | 12.37116 |
Minimum of Months | 551.00000 | 20.75199 | 35.26521 | -0.9691 | 6.95303 |
Maximum of Months | 612.00000 | 23.54895 | 52.91735 | -0.0933 | 28.61490 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.31535 | 43.50825 | -0.4883 | 11.04972 |
February | 551.00000 | 20.05821 | 43.58767 | -0.3090 | 11.32465 |
March | 612.00000 | 20.88031 | 44.28430 | -0.0928 | 9.40603 |
April | 590.00000 | 22.30626 | 46.13969 | 0.26677 | 12.76419 |
May | 611.00000 | 23.65554 | 47.58530 | -0.1905 | 16.16040 |
June | 592.00000 | 24.88995 | 46.59932 | 0.24397 | 11.51429 |
July | 609.00000 | 25.42152 | 48.14225 | 0.45877 | 12.44016 |
August | 612.00000 | 25.53912 | 50.13319 | 0.51746 | 13.03298 |
September | 590.00000 | 24.79143 | 50.72639 | 0.23880 | 11.60481 |
October | 610.00000 | 22.82049 | 47.97582 | 0.41899 | 13.61762 |
November | 591.00000 | 20.72081 | 48.83006 | -0.0916 | 10.65692 |
December | 609.00000 | 19.45385 | 45.62201 | -0.4355 | 10.20321 |
Annual Sum or Average | 7187.00000 | 22.50101 | 46.94295 | 0.04643 | 11.99052 |
Minimum of Months | 551.00000 | 19.31535 | 43.50825 | -0.4883 | 9.40603 |
Maximum of Months | 612.00000 | 25.53912 | 50.72639 | 0.51746 | 16.16040 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 26678950.03 | 9100822.27 | 4.37 | 23968781.41 | 2710168.63 | 0.00 | 0.16 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 | 4719.58 | 27-FEB-15:00 | 4383.64 | 27-FEB-15:00 | 373.31 | 27-FEB-14:00 | 1581.07 | 27-FEB-15:00 | 0.00 | 01-FEB-00:01 |
March | 61498842.90 | 20782407.57 | 5.50 | 61491697.40 | 7145.50 | 0.00 | 0.18 | 18-MAR-17:03 | 0.00 | 01-MAR-00:01 | 5454.06 | 18-MAR-17:03 | 5454.06 | 18-MAR-17:03 | 11.91 | 18-MAR-13:40 | 1816.74 | 18-MAR-17:03 | 0.00 | 01-MAR-00:01 |
April | 0.227592E+10 | 0.688959E+09 | 49.10 | 0.208118E+10 | 0.194735E+09 | 0.00 | 0.93 | 27-APR-17:10 | 0.00 | 01-APR-00:01 | 33558.37 | 27-APR-17:10 | 29384.16 | 27-APR-17:13 | 4261.03 | 27-APR-19:00 | 9181.26 | 27-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.467109E+10 | 0.143588E+10 | 104.03 | 0.383932E+10 | 0.831771E+09 | 0.00 | 0.82 | 05-MAY-18:00 | 0.00 | 01-MAY-00:01 | 29239.81 | 05-MAY-18:00 | 24637.57 | 15-MAY-17:02 | 8323.90 | 05-MAY-18:00 | 8162.92 | 05-MAY-18:00 | 0.00 | 01-MAY-00:01 |
June | 0.886284E+10 | 0.272023E+10 | 215.00 | 0.758159E+10 | 0.128125E+10 | 0.00 | 0.98 | 28-JUN-17:20 | 0.00 | 01-JUN-00:01 | 36037.62 | 28-JUN-17:20 | 32087.48 | 28-JUN-17:03 | 5763.12 | 22-JUN-17:40 | 9706.59 | 28-JUN-17:20 | 0.00 | 01-JUN-00:01 |
July | 0.194990E+11 | 0.572316E+10 | 328.41 | 0.154987E+11 | 0.400027E+10 | 0.00 | 1.00 | 20-JUL-17:05 | 0.00 | 01-JUL-00:01 | 46332.31 | 31-JUL-17:10 | 39366.42 | 24-JUL-17:55 | 11794.13 | 15-JUL-18:20 | 12167.04 | 31-JUL-17:10 | 0.00 | 01-JUL-00:01 |
August | 0.260081E+11 | 0.745815E+10 | 375.24 | 0.206787E+11 | 0.532940E+10 | 0.00 | 1.00 | 07-AUG-17:03 | 0.00 | 01-AUG-00:01 | 53949.64 | 10-AUG-18:00 | 47517.68 | 10-AUG-17:10 | 12148.74 | 29-AUG-13:00 | 14508.40 | 10-AUG-18:00 | 0.00 | 01-AUG-00:01 |
September | 0.807789E+10 | 0.243566E+10 | 171.04 | 0.602825E+10 | 0.204964E+10 | 0.00 | 0.94 | 14-SEP-17:10 | 0.00 | 01-SEP-00:01 | 33996.21 | 14-SEP-17:10 | 27639.28 | 14-SEP-17:03 | 10882.76 | 14-SEP-11:53 | 9275.24 | 14-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.466237E+09 | 0.151545E+09 | 25.18 | 0.447115E+09 | 19121723.55 | 0.00 | 0.46 | 04-OCT-12:00 | 0.00 | 01-OCT-00:01 | 14608.89 | 04-OCT-12:00 | 14412.17 | 04-OCT-12:00 | 1204.66 | 08-OCT-14:00 | 4544.23 | 04-OCT-12:00 | 0.00 | 01-OCT-00:01 |
November | 0.161955E+09 | 52667003.94 | 6.17 | 0.112311E+09 | 49643804.06 | 0.00 | 0.37 | 04-NOV-13:00 | 0.00 | 01-NOV-00:01 | 11296.98 | 04-NOV-13:00 | 7698.93 | 04-NOV-13:00 | 3598.05 | 04-NOV-13:00 | 3600.21 | 04-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.701111E+11 | 0.206961E+11 | 1284.04 | 0.563526E+11 | 0.137585E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.260081E+11 | 0.745815E+10 | 375.24 | 0.206787E+11 | 0.532940E+10 | 0.00 | 1.00 | 0.00 | 53949.64 | 47517.68 | 12148.74 | 14508.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 73453862.82 | 21596291.83 | 7.87 | 60082084.03 | 13371778.79 | 0.00 | 0.43 | 24-FEB-05:01 | 0.00 | 01-FEB-00:01 | 6129.93 | 24-FEB-05:01 | 3794.87 | 27-FEB-15:00 | 2695.35 | 25-FEB-05:01 | 1719.02 | 24-FEB-05:01 | 0.00 | 01-FEB-00:01 |
March | 91713547.33 | 26975332.04 | 12.06 | 84209384.18 | 7504163.15 | 0.00 | 0.75 | 09-MAR-05:01 | 0.00 | 01-MAR-00:01 | 11570.83 | 09-MAR-05:01 | 7359.34 | 09-MAR-05:01 | 4211.50 | 09-MAR-05:01 | 2983.03 | 09-MAR-05:01 | 0.00 | 01-MAR-00:01 |
April | 0.179404E+10 | 0.474080E+09 | 73.21 | 0.158792E+10 | 0.206117E+09 | 0.00 | 1.00 | 27-APR-14:45 | 0.00 | 01-APR-00:01 | 17600.65 | 27-APR-16:17 | 16429.53 | 27-APR-16:17 | 6930.45 | 28-APR-03:51 | 4222.65 | 27-APR-16:17 | 0.00 | 01-APR-00:01 |
May | 0.428125E+10 | 0.112239E+10 | 168.24 | 0.331796E+10 | 0.963288E+09 | 0.00 | 1.00 | 05-MAY-03:41 | 0.00 | 01-MAY-00:01 | 22741.11 | 08-MAY-04:01 | 13921.39 | 05-MAY-16:00 | 10718.01 | 08-MAY-04:01 | 5454.12 | 08-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.849294E+10 | 0.224055E+10 | 306.81 | 0.682996E+10 | 0.166299E+10 | 0.00 | 1.00 | 03-JUN-03:42 | 0.00 | 01-JUN-00:01 | 33225.37 | 12-JUN-04:01 | 20184.60 | 23-JUN-03:21 | 16451.55 | 12-JUN-04:01 | 7965.75 | 09-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.157598E+11 | 0.397734E+10 | 410.11 | 0.119952E+11 | 0.376461E+10 | 0.00 | 1.00 | 06-JUL-03:52 | 0.00 | 01-JUL-00:01 | 33225.37 | 07-JUL-04:01 | 23059.95 | 24-JUL-14:55 | 16689.39 | 25-JUL-03:11 | 7965.75 | 07-JUL-03:21 | 0.00 | 01-JUL-00:01 |
August | 0.196298E+11 | 0.488331E+10 | 441.68 | 0.150665E+11 | 0.456324E+10 | 0.00 | 1.00 | 01-AUG-03:11 | 0.00 | 01-AUG-00:01 | 33225.37 | 08-AUG-03:11 | 26620.56 | 10-AUG-16:55 | 17415.90 | 16-AUG-04:01 | 7965.75 | 08-AUG-03:11 | 0.00 | 01-AUG-00:01 |
September | 0.771456E+10 | 0.200994E+10 | 272.49 | 0.535700E+10 | 0.235756E+10 | 0.00 | 1.00 | 01-SEP-03:02 | 0.00 | 01-SEP-00:01 | 33225.37 | 05-SEP-03:11 | 19995.95 | 05-SEP-03:11 | 16476.91 | 14-SEP-04:01 | 7965.75 | 05-SEP-03:11 | 0.00 | 01-SEP-00:01 |
October | 0.103425E+10 | 0.295807E+09 | 80.49 | 0.808022E+09 | 0.226233E+09 | 0.00 | 1.00 | 06-OCT-03:42 | 0.00 | 01-OCT-00:01 | 16593.63 | 06-OCT-03:42 | 8829.19 | 04-OCT-16:17 | 7988.89 | 06-OCT-03:42 | 3981.41 | 06-OCT-03:42 | 0.00 | 01-OCT-00:01 |
November | 0.307272E+09 | 83620252.97 | 16.21 | 0.193248E+09 | 0.114024E+09 | 0.00 | 0.74 | 04-NOV-15:03 | 0.00 | 01-NOV-00:01 | 11338.69 | 04-NOV-15:03 | 7642.63 | 04-NOV-15:03 | 4074.93 | 04-NOV-10:55 | 2933.28 | 04-NOV-15:03 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.591791E+11 | 0.151356E+11 | 1789.18 | 0.453001E+11 | 0.138789E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.196298E+11 | 0.488331E+10 | 441.68 | 0.150665E+11 | 0.456324E+10 | 0.00 | 1.00 | 0.00 | 33225.37 | 26620.56 | 17415.90 | 7965.75 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.83 | 23.76 | 71.06 | 36.17 | 322.02 | 0.00 | 0.00 | 0.00 |
February | 174.69 | 61.87 | 112.81 | 121.08 | 273.90 | 0.00 | 0.00 | 0.00 |
March | 261.80 | 94.94 | 166.87 | 232.74 | 217.61 | 0.00 | 0.00 | 0.00 |
April | 404.35 | 167.79 | 236.56 | 426.69 | 173.77 | 0.00 | 0.00 | 0.00 |
May | 430.54 | 149.91 | 280.63 | 474.08 | 147.68 | 0.00 | 0.00 | 0.00 |
June | 515.30 | 224.28 | 291.02 | 600.11 | 119.29 | 0.00 | 0.00 | 0.00 |
July | 480.57 | 216.06 | 264.51 | 578.54 | 108.36 | 0.00 | 0.00 | 0.00 |
August | 471.75 | 235.98 | 235.77 | 583.35 | 108.83 | 0.00 | 0.00 | 0.00 |
September | 349.36 | 161.41 | 187.95 | 392.44 | 150.01 | 0.00 | 0.00 | 0.00 |
October | 228.44 | 97.61 | 130.83 | 217.97 | 199.60 | 0.00 | 0.00 | 0.00 |
November | 111.79 | 31.66 | 80.14 | 65.27 | 253.31 | 0.00 | 0.00 | 0.00 |
December | 91.45 | 29.39 | 62.06 | 45.28 | 319.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.80 | 124.83 | 176.96 | 315.45 | 199.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.45 | 23.76 | 62.06 | 36.17 | 108.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 515.30 | 235.98 | 291.02 | 600.11 | 322.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.83 | 216.44 | 147.40 | 333.46 | 419.16 | 0.00 | 0.00 | 0.00 |
February | 559.89 | 347.38 | 212.51 | 583.10 | 366.77 | 0.00 | 0.00 | 0.00 |
March | 593.93 | 314.01 | 279.92 | 651.11 | 305.83 | 0.00 | 0.00 | 0.00 |
April | 627.58 | 269.34 | 358.24 | 726.67 | 253.80 | 0.00 | 0.00 | 0.00 |
May | 584.72 | 178.26 | 406.46 | 685.84 | 213.12 | 0.00 | 0.00 | 0.00 |
June | 529.04 | 141.59 | 387.45 | 626.36 | 174.47 | 0.00 | 0.00 | 0.00 |
July | 574.78 | 208.70 | 366.08 | 738.42 | 161.59 | 0.00 | 0.00 | 0.00 |
August | 612.76 | 281.56 | 331.20 | 806.05 | 159.81 | 0.00 | 0.00 | 0.00 |
September | 679.63 | 371.71 | 307.92 | 847.15 | 213.53 | 0.00 | 0.00 | 0.00 |
October | 614.78 | 376.39 | 238.39 | 710.79 | 273.97 | 0.00 | 0.00 | 0.00 |
November | 367.93 | 210.60 | 157.32 | 364.01 | 338.51 | 0.00 | 0.00 | 0.00 |
December | 385.07 | 249.02 | 136.05 | 386.51 | 422.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 540.90 | 263.23 | 277.67 | 621.73 | 274.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.83 | 141.59 | 136.05 | 333.46 | 159.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 679.63 | 376.39 | 406.46 | 847.15 | 422.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.04 | 30.06 | 70.99 | 46.44 | 324.22 | 0.00 | 0.00 | 0.00 |
February | 180.25 | 67.67 | 112.58 | 133.28 | 279.59 | 0.00 | 0.00 | 0.00 |
March | 252.50 | 85.37 | 167.13 | 226.29 | 224.52 | 0.00 | 0.00 | 0.00 |
April | 383.68 | 146.51 | 237.18 | 405.28 | 178.77 | 0.00 | 0.00 | 0.00 |
May | 494.66 | 201.39 | 293.28 | 564.09 | 149.23 | 0.00 | 0.00 | 0.00 |
June | 474.70 | 183.96 | 290.74 | 546.23 | 121.70 | 0.00 | 0.00 | 0.00 |
July | 586.82 | 308.37 | 278.46 | 728.74 | 113.09 | 0.00 | 0.00 | 0.00 |
August | 485.66 | 247.71 | 237.94 | 607.71 | 113.55 | 0.00 | 0.00 | 0.00 |
September | 396.78 | 190.87 | 205.91 | 463.85 | 153.54 | 0.00 | 0.00 | 0.00 |
October | 226.91 | 93.28 | 133.63 | 218.24 | 202.69 | 0.00 | 0.00 | 0.00 |
November | 112.37 | 31.95 | 80.43 | 68.47 | 257.10 | 0.00 | 0.00 | 0.00 |
December | 94.85 | 32.93 | 61.92 | 54.26 | 325.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 316.68 | 135.52 | 181.16 | 339.90 | 203.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.85 | 30.06 | 61.92 | 46.44 | 113.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 586.82 | 308.37 | 293.28 | 728.74 | 325.29 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253988E+09 | 63650096.24 | 0.190338E+09 | 96880689.24 | 0.862504E+09 |
February | 0.422602E+09 | 0.149687E+09 | 0.272915E+09 | 0.292927E+09 | 0.662615E+09 |
March | 0.701216E+09 | 0.254274E+09 | 0.446942E+09 | 0.623359E+09 | 0.582849E+09 |
April | 0.104808E+10 | 0.434921E+09 | 0.613160E+09 | 0.110598E+10 | 0.450400E+09 |
May | 0.115315E+10 | 0.401509E+09 | 0.751645E+09 | 0.126978E+10 | 0.395535E+09 |
June | 0.133566E+10 | 0.581335E+09 | 0.754321E+09 | 0.155548E+10 | 0.309201E+09 |
July | 0.128716E+10 | 0.578707E+09 | 0.708457E+09 | 0.154957E+10 | 0.290242E+09 |
August | 0.126353E+10 | 0.632047E+09 | 0.631487E+09 | 0.156245E+10 | 0.291492E+09 |
September | 0.905532E+09 | 0.418372E+09 | 0.487160E+09 | 0.101720E+10 | 0.388834E+09 |
October | 0.611853E+09 | 0.261436E+09 | 0.350417E+09 | 0.583808E+09 | 0.534598E+09 |
November | 0.289766E+09 | 82055791.34 | 0.207710E+09 | 0.169190E+09 | 0.656574E+09 |
December | 0.244939E+09 | 78727652.34 | 0.166212E+09 | 0.121273E+09 | 0.855553E+09 |
Annual Sum or Average | 0.951748E+10 | 0.393672E+10 | 0.558076E+10 | 0.994790E+10 | 0.628040E+10 |
Minimum of Months | 0.244939E+09 | 63650096.24 | 0.166212E+09 | 96880689.24 | 0.290242E+09 |
Maximum of Months | 0.133566E+10 | 0.632047E+09 | 0.754321E+09 | 0.156245E+10 | 0.862504E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.974494E+09 | 0.579706E+09 | 0.394788E+09 | 0.893149E+09 | 0.112268E+10 |
February | 0.135448E+10 | 0.840384E+09 | 0.514099E+09 | 0.141063E+10 | 0.887280E+09 |
March | 0.159078E+10 | 0.841047E+09 | 0.749730E+09 | 0.174394E+10 | 0.819123E+09 |
April | 0.162670E+10 | 0.698136E+09 | 0.928563E+09 | 0.188353E+10 | 0.657838E+09 |
May | 0.156612E+10 | 0.477462E+09 | 0.108865E+10 | 0.183696E+10 | 0.570809E+09 |
June | 0.137127E+10 | 0.367006E+09 | 0.100426E+10 | 0.162352E+10 | 0.452219E+09 |
July | 0.153948E+10 | 0.558984E+09 | 0.980496E+09 | 0.197778E+10 | 0.432807E+09 |
August | 0.164122E+10 | 0.754129E+09 | 0.887088E+09 | 0.215893E+10 | 0.428040E+09 |
September | 0.176159E+10 | 0.963469E+09 | 0.798119E+09 | 0.219581E+10 | 0.553480E+09 |
October | 0.164663E+10 | 0.100812E+10 | 0.638505E+09 | 0.190377E+10 | 0.733794E+09 |
November | 0.953667E+09 | 0.545886E+09 | 0.407781E+09 | 0.943526E+09 | 0.877416E+09 |
December | 0.103137E+10 | 0.666974E+09 | 0.364401E+09 | 0.103523E+10 | 0.113128E+10 |
Annual Sum or Average | 0.170578E+11 | 0.830131E+10 | 0.875649E+10 | 0.196068E+11 | 0.866676E+10 |
Minimum of Months | 0.953667E+09 | 0.367006E+09 | 0.364401E+09 | 0.893149E+09 | 0.428040E+09 |
Maximum of Months | 0.176159E+10 | 0.100812E+10 | 0.108865E+10 | 0.219581E+10 | 0.113128E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270636E+09 | 80508928.08 | 0.190127E+09 | 0.124381E+09 | 0.868394E+09 |
February | 0.436050E+09 | 0.163699E+09 | 0.272351E+09 | 0.322422E+09 | 0.676376E+09 |
March | 0.676293E+09 | 0.228649E+09 | 0.447644E+09 | 0.606082E+09 | 0.601362E+09 |
April | 0.994508E+09 | 0.379742E+09 | 0.614765E+09 | 0.105049E+10 | 0.463363E+09 |
May | 0.132490E+10 | 0.539393E+09 | 0.785510E+09 | 0.151085E+10 | 0.399700E+09 |
June | 0.123042E+10 | 0.476827E+09 | 0.753591E+09 | 0.141583E+10 | 0.315459E+09 |
July | 0.157175E+10 | 0.825928E+09 | 0.745821E+09 | 0.195184E+10 | 0.302897E+09 |
August | 0.130078E+10 | 0.663476E+09 | 0.637307E+09 | 0.162768E+10 | 0.304139E+09 |
September | 0.102846E+10 | 0.494729E+09 | 0.533729E+09 | 0.120229E+10 | 0.397973E+09 |
October | 0.607747E+09 | 0.249838E+09 | 0.357909E+09 | 0.584535E+09 | 0.542891E+09 |
November | 0.291268E+09 | 82801934.61 | 0.208466E+09 | 0.177476E+09 | 0.666408E+09 |
December | 0.254051E+09 | 88193011.09 | 0.165858E+09 | 0.145334E+09 | 0.871255E+09 |
Annual Sum or Average | 0.998686E+10 | 0.427378E+10 | 0.571308E+10 | 0.107192E+11 | 0.641022E+10 |
Minimum of Months | 0.254051E+09 | 80508928.08 | 0.165858E+09 | 0.124381E+09 | 0.302897E+09 |
Maximum of Months | 0.157175E+10 | 0.825928E+09 | 0.785510E+09 | 0.195184E+10 | 0.871255E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 388.20 | 1037.53 | 559.71 | 270.26 | 289.45 | 0.00 | 0.00 |
February | 813.55 | 896.34 | 914.82 | 476.92 | 437.90 | 0.00 | 0.00 |
March | 1092.20 | 730.03 | 1108.23 | 494.31 | 613.92 | 0.00 | 0.00 |
April | 1537.25 | 584.93 | 1415.62 | 583.64 | 831.98 | 0.00 | 0.00 |
May | 1709.14 | 495.15 | 1509.92 | 529.56 | 980.36 | 0.00 | 0.00 |
June | 1758.57 | 401.34 | 1519.04 | 549.83 | 969.20 | 0.00 | 0.00 |
July | 2030.17 | 367.52 | 1642.17 | 733.13 | 909.04 | 0.00 | 0.00 |
August | 1981.60 | 366.69 | 1570.17 | 765.25 | 804.91 | 0.00 | 0.00 |
September | 1688.59 | 502.24 | 1425.76 | 723.99 | 701.78 | 0.00 | 0.00 |
October | 1133.46 | 662.72 | 1070.13 | 567.28 | 502.85 | 0.00 | 0.00 |
November | 483.38 | 834.54 | 592.09 | 274.21 | 317.88 | 0.00 | 0.00 |
December | 461.72 | 1042.76 | 571.37 | 311.34 | 260.03 | 0.00 | 0.00 |
Annual Sum or Average | 1258.92 | 659.08 | 1159.38 | 523.59 | 635.79 | 0.00 | 0.00 |
Minimum of Months | 388.20 | 366.69 | 559.71 | 270.26 | 260.03 | 0.00 | 0.00 |
Maximum of Months | 2030.17 | 1042.76 | 1642.17 | 765.25 | 980.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103975E+10 | 0.277892E+10 | 0.149912E+10 | 0.723865E+09 | 0.775253E+09 | 0.00 | 0.00 |
February | 0.196814E+10 | 0.216843E+10 | 0.221314E+10 | 0.115377E+10 | 0.105936E+10 | 0.00 | 0.00 |
March | 0.292536E+10 | 0.195531E+10 | 0.296829E+10 | 0.132397E+10 | 0.164432E+10 | 0.00 | 0.00 |
April | 0.398455E+10 | 0.151615E+10 | 0.366929E+10 | 0.151280E+10 | 0.215649E+10 | 0.00 | 0.00 |
May | 0.457775E+10 | 0.132621E+10 | 0.404417E+10 | 0.141836E+10 | 0.262581E+10 | 0.00 | 0.00 |
June | 0.455823E+10 | 0.104027E+10 | 0.393734E+10 | 0.142517E+10 | 0.251217E+10 | 0.00 | 0.00 |
July | 0.543761E+10 | 0.984355E+09 | 0.439839E+10 | 0.196362E+10 | 0.243477E+10 | 0.00 | 0.00 |
August | 0.530751E+10 | 0.982135E+09 | 0.420553E+10 | 0.204965E+10 | 0.215588E+10 | 0.00 | 0.00 |
September | 0.437684E+10 | 0.130182E+10 | 0.369558E+10 | 0.187657E+10 | 0.181901E+10 | 0.00 | 0.00 |
October | 0.303586E+10 | 0.177503E+10 | 0.286623E+10 | 0.151940E+10 | 0.134683E+10 | 0.00 | 0.00 |
November | 0.125293E+10 | 0.216313E+10 | 0.153470E+10 | 0.710744E+09 | 0.823957E+09 | 0.00 | 0.00 |
December | 0.123668E+10 | 0.279293E+10 | 0.153036E+10 | 0.833895E+09 | 0.696470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.397012E+11 | 0.207847E+11 | 0.365621E+11 | 0.165118E+11 | 0.200503E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103975E+10 | 0.982135E+09 | 0.149912E+10 | 0.710744E+09 | 0.696470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.543761E+10 | 0.279293E+10 | 0.439839E+10 | 0.204965E+10 | 0.262581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639743E+10 | -0.622516E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172276301.6 | 81.22 | 0.00 | 0.00 |
February | 0.578810E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -153820313.2 | 81.22 | 0.00 | 0.00 |
March | 0.646177E+10 | -0.629385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167921550.8 | 81.22 | 0.00 | 0.00 |
April | 0.620227E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158800984.3 | 81.22 | 0.00 | 0.00 |
May | 0.642051E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160333139.4 | 81.22 | 0.00 | 0.00 |
June | 0.623837E+10 | -0.608656E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151808023.9 | 81.22 | 0.00 | 0.00 |
July | 0.637256E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155471444.3 | 81.21 | 0.00 | 0.00 |
August | 0.645037E+10 | -0.629525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155123946.8 | 81.21 | 0.00 | 0.00 |
September | 0.619682E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152004413.2 | 81.21 | 0.00 | 0.00 |
October | 0.638626E+10 | -0.622381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162444846.3 | 81.22 | 0.00 | 0.00 |
November | 0.618743E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162815637.6 | 81.22 | 0.00 | 0.00 |
December | 0.638890E+10 | -0.621707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171830111.2 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754908E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.192465E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.578810E+10 | -0.629525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172276301.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646177E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151808023.9 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.241398E+11 | -0.231365E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100333E+10 | 58.99 | 0.00 | 0.00 |
February | 0.219763E+11 | -0.210864E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -889906227.5 | 58.99 | 0.00 | 0.00 |
March | 0.242514E+11 | -0.232880E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -963444431.4 | 58.99 | 0.00 | 0.00 |
April | 0.226424E+11 | -0.217439E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -898491395.6 | 58.99 | 0.00 | 0.00 |
May | 0.225735E+11 | -0.216795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -894010626.5 | 58.99 | 0.00 | 0.00 |
June | 0.211073E+11 | -0.202728E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -834496106.8 | 58.99 | 0.00 | 0.00 |
July | 0.209817E+11 | -0.201323E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -849456528.5 | 58.98 | 0.00 | 0.00 |
August | 0.210533E+11 | -0.202069E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -846400430.8 | 58.99 | 0.00 | 0.00 |
September | 0.205067E+11 | -0.196705E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -836188465.9 | 58.99 | 0.00 | 0.00 |
October | 0.218140E+11 | -0.209008E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -913222539.7 | 58.98 | 0.00 | 0.00 |
November | 0.219820E+11 | -0.210469E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -935129234.5 | 58.98 | 0.00 | 0.00 |
December | 0.235310E+11 | -0.225318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -999210436.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.266559E+12 | -0.255696E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.108633E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.205067E+11 | -0.232880E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.100333E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.242514E+11 | -0.196705E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834496106.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.77 | 0.75 | 01-JAN-09:39 | 1654.49 | 30.67 | 187.00 | 205.00 | 1730.09 | 31.89 | 204.50 | 203.50 |
February | 259.50 | 0.77 | 0.75 | 01-FEB-08:39 | 1184.55 | 25.62 | 165.50 | 233.50 | 1089.57 | 24.81 | 150.17 | 234.50 |
March | 247.00 | 0.77 | 0.75 | 01-MAR-07:19 | 1182.67 | 22.38 | 146.00 | 300.83 | 1195.24 | 22.71 | 154.17 | 302.50 |
April | 379.50 | 0.77 | 0.75 | 01-APR-06:00 | 1073.57 | 20.67 | 174.33 | 344.33 | 1118.69 | 20.64 | 173.33 | 344.83 |
May | 427.83 | 0.77 | 0.75 | 01-MAY-07:10 | 1119.34 | 20.81 | 190.17 | 386.17 | 1036.57 | 20.55 | 192.83 | 385.67 |
June | 375.17 | 0.77 | 0.75 | 01-JUN-05:40 | 1014.99 | 21.91 | 194.50 | 397.17 | 947.61 | 20.45 | 158.50 | 395.17 |
July | 471.00 | 0.77 | 0.75 | 01-JUL-05:19 | 986.64 | 20.93 | 171.33 | 405.17 | 1009.41 | 19.34 | 141.17 | 410.83 |
August | 366.67 | 0.77 | 0.75 | 01-AUG-05:40 | 1314.85 | 20.29 | 128.00 | 381.17 | 1117.39 | 20.30 | 141.00 | 380.83 |
September | 301.17 | 0.76 | 0.75 | 01-SEP-07:40 | 1328.37 | 22.00 | 154.67 | 315.83 | 1400.79 | 22.54 | 187.67 | 319.50 |
October | 245.33 | 0.77 | 0.75 | 01-OCT-07:49 | 1099.81 | 23.51 | 159.17 | 276.50 | 1131.36 | 23.95 | 173.00 | 274.50 |
November | 242.67 | 0.77 | 0.75 | 01-NOV-07:00 | 1414.05 | 29.83 | 187.50 | 212.33 | 1404.78 | 29.74 | 186.83 | 212.67 |
December | 160.33 | 0.77 | 0.75 | 01-DEC-09:39 | 2478.50 | 35.06 | 133.33 | 191.67 | 2508.72 | 34.81 | 131.17 | 190.67 |
Annual Sum or Average | 3714.00 | 0.77 | 1243.22 | 23.42 | 1991.50 | 3649.67 | 1222.58 | 23.14 | 1994.33 | 3655.17 | ||
Minimum of Months | 160.33 | 0.76 | 0.75 | 986.64 | 20.29 | 128.00 | 191.67 | 947.61 | 19.34 | 131.17 | 190.67 | |
Maximum of Months | 471.00 | 0.77 | 0.75 | 2478.50 | 35.06 | 194.50 | 405.17 | 2508.72 | 34.81 | 204.50 | 410.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397670E+11 | 80141.83 | 08-JAN-09:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291001E+11 | 70384.46 | 19-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190790E+11 | 40274.49 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102836E+11 | 38373.68 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482614E+10 | 30079.77 | 18-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.789233E+09 | 22118.13 | 15-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69525143.71 | 15232.04 | 04-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 62068087.52 | 8060.16 | 21-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946441E+09 | 25032.98 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.739395E+10 | 29225.64 | 29-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220616E+11 | 48250.85 | 28-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347076E+11 | 44048.56 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 62068087.52 | 8060.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397670E+11 | 80141.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110525E+11 | 25929.71 | 15-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844054E+10 | 31422.06 | 19-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298841E+10 | 18064.55 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104225E+10 | 17189.07 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120577E+09 | 8788.92 | 11-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166106E+09 | 5466.40 | 15-OCT-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360194E+10 | 19017.45 | 11-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794974E+10 | 21541.56 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110525E+11 | 31422.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 26678950.03 | 23968781.41 | 4719.58 | 27-FEB-15:00 | 4383.64 | 0.00 |
March | 0.00 | 0.00 | 61498842.90 | 61491697.40 | 5454.06 | 18-MAR-17:03 | 5454.06 | 0.00 |
April | 0.00 | 0.00 | 0.227592E+10 | 0.208118E+10 | 33558.37 | 27-APR-17:10 | 29345.58 | 0.00 |
May | 0.00 | 0.00 | 0.467109E+10 | 0.383932E+10 | 29239.81 | 05-MAY-18:00 | 20915.92 | 0.00 |
June | 0.00 | 0.00 | 0.886284E+10 | 0.758159E+10 | 36037.62 | 28-JUN-17:20 | 31734.93 | 0.00 |
July | 0.00 | 0.00 | 0.194990E+11 | 0.154987E+11 | 46332.31 | 31-JUL-17:10 | 37723.45 | 0.00 |
August | 0.00 | 0.00 | 0.260081E+11 | 0.206787E+11 | 53949.64 | 10-AUG-18:00 | 45608.56 | 0.00 |
September | 0.00 | 0.00 | 0.807789E+10 | 0.602825E+10 | 33996.21 | 14-SEP-17:10 | 27626.90 | 0.00 |
October | 0.00 | 0.00 | 0.466237E+09 | 0.447115E+09 | 14608.89 | 04-OCT-12:00 | 14412.17 | 0.00 |
November | 0.00 | 0.00 | 0.161955E+09 | 0.112311E+09 | 11296.98 | 04-NOV-13:00 | 7698.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.701111E+11 | 0.563526E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.260081E+11 | 0.206787E+11 | 53949.64 | 45608.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 73453862.82 | 60082084.03 | 6129.93 | 24-FEB-05:01 | 3474.91 | 0.00 |
March | 0.00 | 0.00 | 91713547.33 | 84209384.18 | 11570.83 | 09-MAR-05:01 | 7359.34 | 0.00 |
April | 0.00 | 0.00 | 0.179404E+10 | 0.158792E+10 | 17600.65 | 27-APR-16:17 | 16429.53 | 0.00 |
May | 0.00 | 0.00 | 0.428125E+10 | 0.331796E+10 | 22741.11 | 08-MAY-04:01 | 12023.10 | 0.00 |
June | 0.00 | 0.00 | 0.849294E+10 | 0.682996E+10 | 33225.37 | 12-JUN-04:01 | 16773.83 | 0.00 |
July | 0.00 | 0.00 | 0.157598E+11 | 0.119952E+11 | 33225.37 | 07-JUL-04:01 | 19807.53 | 0.00 |
August | 0.00 | 0.00 | 0.196298E+11 | 0.150665E+11 | 33225.37 | 08-AUG-03:11 | 17707.27 | 0.00 |
September | 0.00 | 0.00 | 0.771456E+10 | 0.535700E+10 | 33225.37 | 05-SEP-03:11 | 19995.95 | 0.00 |
October | 0.00 | 0.00 | 0.103425E+10 | 0.808022E+09 | 16593.63 | 06-OCT-03:42 | 8604.74 | 0.00 |
November | 0.00 | 0.00 | 0.307272E+09 | 0.193248E+09 | 11338.69 | 04-NOV-15:03 | 7642.63 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.591791E+11 | 0.453001E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196298E+11 | 0.150665E+11 | 33225.37 | 19995.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9098.23 | 17382.46 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9175.84 | 17436.02 | 13-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9154.35 | 17375.83 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 8849.13 | 16976.66 | 04-APR-18:57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8554.92 | 16471.15 | 02-MAY-18:06 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 8282.40 | 15854.92 | 01-JUN-06:27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7978.33 | 15304.92 | 03-JUL-18:15 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8006.38 | 15096.10 | 31-AUG-18:25 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8050.88 | 15426.17 | 29-SEP-18:12 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8264.76 | 15973.14 | 31-OCT-06:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8580.76 | 16567.46 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 8872.78 | 17093.07 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 8568.88 | ||||
Minimum of Months | 0.00 | 0.00 | 7978.33 | 15096.10 | ||
Maximum of Months | 0.00 | 0.00 | 9175.84 | 17436.02 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.22 | 824.13 | 01-JAN-00:01 | 0.27 |
February | 0.166491E+10 | 0.22 | 824.13 | 01-FEB-00:01 | 0.27 |
March | 0.184342E+10 | 0.22 | 824.13 | 01-MAR-00:01 | 0.27 |
April | 0.180410E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.27 |
May | 0.190325E+10 | 0.23 | 824.13 | 01-MAY-03:55 | 0.27 |
June | 0.190349E+10 | 0.24 | 824.13 | 01-JUN-03:02 | 0.27 |
July | 0.203428E+10 | 0.25 | 824.13 | 01-JUL-01:10 | 0.27 |
August | 0.205103E+10 | 0.25 | 824.13 | 01-AUG-00:40 | 0.27 |
September | 0.191858E+10 | 0.24 | 824.13 | 01-SEP-01:05 | 0.27 |
October | 0.188248E+10 | 0.23 | 824.13 | 01-OCT-03:02 | 0.27 |
November | 0.179236E+10 | 0.22 | 824.13 | 01-NOV-04:01 | 0.27 |
December | 0.183946E+10 | 0.22 | 824.13 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.224768E+11 | 0.23 | |||
Minimum of Months | 0.166491E+10 | 0.22 | 824.13 | 0.27 | |
Maximum of Months | 0.205103E+10 | 0.25 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.677877E+10 | 0.81 | 4937.01 | 08-JAN-09:48 | 1.28 |
February | 0.591490E+10 | 0.79 | 4639.56 | 19-FEB-05:01 | 1.24 |
March | 0.614811E+10 | 0.76 | 3721.69 | 01-MAR-06:03 | 1.10 |
April | 0.570043E+10 | 0.74 | 3663.74 | 19-APR-05:03 | 1.09 |
May | 0.571363E+10 | 0.73 | 3410.91 | 18-MAY-05:03 | 1.04 |
June | 0.541100E+10 | 0.72 | 3168.21 | 15-JUN-05:03 | 1.00 |
July | 0.558414E+10 | 0.71 | 3333.15 | 31-JUL-17:10 | 1.02 |
August | 0.563006E+10 | 0.72 | 4084.34 | 10-AUG-18:00 | 1.15 |
September | 0.541579E+10 | 0.71 | 3257.06 | 27-SEP-05:03 | 1.01 |
October | 0.579190E+10 | 0.73 | 3384.87 | 29-OCT-05:03 | 1.04 |
November | 0.605947E+10 | 0.77 | 3964.84 | 28-NOV-05:04 | 1.14 |
December | 0.662454E+10 | 0.80 | 3836.74 | 26-DEC-06:03 | 1.12 |
Annual Sum or Average | 0.707727E+11 | 0.75 | |||
Minimum of Months | 0.541100E+10 | 0.71 | 3168.21 | 1.00 | |
Maximum of Months | 0.677877E+10 | 0.81 | 4937.01 | 1.28 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161652E+10 | 0.48 | 1007.72 | 15-JAN-06:03 | 0.70 |
February | 0.143959E+10 | 0.47 | 1081.94 | 19-FEB-05:04 | 0.73 |
March | 0.150791E+10 | 0.46 | 901.44 | 02-MAR-06:03 | 0.66 |
April | 0.143640E+10 | 0.46 | 1634.10 | 28-APR-03:11 | 0.88 |
May | 0.147560E+10 | 0.46 | 1021.78 | 08-MAY-04:01 | 0.70 |
June | 0.143419E+10 | 0.48 | 1643.34 | 09-JUN-04:01 | 0.89 |
July | 0.152813E+10 | 0.50 | 1643.34 | 07-JUL-03:21 | 0.89 |
August | 0.159264E+10 | 0.51 | 1643.34 | 08-AUG-03:11 | 0.89 |
September | 0.143764E+10 | 0.48 | 1643.34 | 14-SEP-04:01 | 0.89 |
October | 0.147362E+10 | 0.46 | 731.20 | 15-OCT-24:00 | 0.58 |
November | 0.146977E+10 | 0.46 | 914.32 | 11-NOV-06:03 | 0.66 |
December | 0.157460E+10 | 0.47 | 948.42 | 26-DEC-06:03 | 0.68 |
Annual Sum or Average | 0.179866E+11 | 0.47 | |||
Minimum of Months | 0.143419E+10 | 0.46 | 731.20 | 0.58 | |
Maximum of Months | 0.161652E+10 | 0.51 | 1643.34 | 0.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 48.62 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 48.29 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 48.30 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 51.46 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 51.29 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 51.42 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 52.81 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.56 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.27 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 51.83 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 51.96 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 48.69 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.29 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.81 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.62 | 59.92 | 9098.23 | 17382.46 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 48.29 | 58.63 | 9175.84 | 17436.02 | 13-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 48.30 | 58.59 | 9154.35 | 17375.83 | 01-MAR-07:25 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.88 | 49.88 | 8849.13 | 16976.66 | 04-APR-18:57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.89 | 49.89 | 8554.92 | 16471.15 | 02-MAY-18:06 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.09 | 50.09 | 8282.40 | 15854.92 | 01-JUN-06:27 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.62 | 50.62 | 7978.33 | 15304.92 | 03-JUL-18:15 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.03 | 51.03 | 8006.38 | 15096.10 | 31-AUG-18:25 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.80 | 50.80 | 8050.88 | 15426.17 | 29-SEP-18:12 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.49 | 48.49 | 8264.76 | 15973.14 | 31-OCT-06:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.57 | 50.57 | 8580.76 | 16567.46 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 48.69 | 58.67 | 8872.78 | 17093.07 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 8568.88 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.29 | 48.49 | 7978.33 | 15096.10 | ||
Maximum of Months | 0.00 | 0.00 | 51.03 | 59.92 | 9175.84 | 17436.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.677877E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.592400E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.616890E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.638939E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.714950E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.813123E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.113073E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.130882E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.785145E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.594345E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.611214E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.662454E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.914689E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.592400E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130882E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.161652E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146119E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153489E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.191047E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.259799E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.367474E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.550547E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.647595E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.344757E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176943E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.155339E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157460E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.331222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146119E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.647595E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.677877E+10 | 0.00 | 0.397670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591490E+10 | 26678950.03 | 0.291001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614811E+10 | 61498842.90 | 0.190790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570043E+10 | 0.227592E+10 | 0.102836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571363E+10 | 0.467109E+10 | 0.482614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.541100E+10 | 0.886284E+10 | 0.789233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558414E+10 | 0.194990E+11 | 69525143.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563006E+10 | 0.260081E+11 | 62068087.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.541579E+10 | 0.807789E+10 | 0.946441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.579190E+10 | 0.466237E+09 | 0.739395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.605947E+10 | 0.161955E+09 | 0.220616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662454E+10 | 0.00 | 0.347076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707727E+11 | 0.701111E+11 | 0.169086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.541100E+10 | 0.00 | 62068087.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677877E+10 | 0.260081E+11 | 0.397670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161652E+10 | 0.00 | 0.110525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143959E+10 | 73453862.82 | 0.844054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150791E+10 | 91713547.33 | 0.298841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143640E+10 | 0.179404E+10 | 0.104225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147560E+10 | 0.428125E+10 | 0.120577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143419E+10 | 0.849294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152813E+10 | 0.157565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159264E+10 | 0.196256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143764E+10 | 0.771372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147362E+10 | 0.103425E+10 | 0.166106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146977E+10 | 0.307272E+09 | 0.360194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157460E+10 | 0.00 | 0.794974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179866E+11 | 0.591707E+11 | 0.353621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161652E+10 | 0.196256E+11 | 0.110525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.677877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591490E+10 | 0.00 | 0.00 | 0.00 | 9100822.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614811E+10 | 0.00 | 0.00 | 0.00 | 20782407.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570043E+10 | 0.00 | 0.00 | 0.00 | 0.688959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571363E+10 | 0.00 | 0.00 | 0.00 | 0.143588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.541100E+10 | 0.00 | 0.00 | 0.00 | 0.272023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558414E+10 | 0.00 | 0.00 | 0.00 | 0.572316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563006E+10 | 0.00 | 0.00 | 0.00 | 0.745815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.541579E+10 | 0.00 | 0.00 | 0.00 | 0.243566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.579190E+10 | 0.00 | 0.00 | 0.00 | 0.151545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.605947E+10 | 0.00 | 0.00 | 0.00 | 52667003.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707727E+11 | 0.00 | 0.00 | 0.00 | 0.206961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.541100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677877E+10 | 0.00 | 0.00 | 0.00 | 0.745815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143959E+10 | 0.00 | 0.00 | 0.00 | 21596291.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150791E+10 | 0.00 | 0.00 | 0.00 | 26975332.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143640E+10 | 0.00 | 0.00 | 0.00 | 0.474080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147560E+10 | 0.00 | 0.00 | 0.00 | 0.112239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143419E+10 | 0.00 | 0.00 | 0.00 | 0.224055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152813E+10 | 0.00 | 0.00 | 0.00 | 0.397734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159264E+10 | 0.00 | 0.00 | 0.00 | 0.488331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143764E+10 | 0.00 | 0.00 | 0.00 | 0.200994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147362E+10 | 0.00 | 0.00 | 0.00 | 0.295807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146977E+10 | 0.00 | 0.00 | 0.00 | 83620252.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179866E+11 | 0.00 | 0.00 | 0.00 | 0.151356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161652E+10 | 0.00 | 0.00 | 0.00 | 0.488331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.592856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761430E+10 | 0.00 | 0.00 | 3.55 |
February | 0.510528E+11 | 0.00 | 0.00 | 1158844.56 | 0.00 | 0.469482E+10 | 0.615969E+09 | 0.00 | 3.58 |
March | 0.511243E+11 | 0.00 | 0.00 | 2351392.43 | 0.00 | 0.942248E+09 | 0.171316E+10 | 0.00 | 3.57 |
April | 0.396779E+11 | 21001629.07 | 0.00 | 15782776.31 | 0.00 | 0.363235E+09 | 0.531607E+10 | 0.00 | 3.63 |
May | 0.293892E+11 | 4262042.74 | 0.00 | 35964094.10 | 0.00 | 0.112690E+09 | 0.123551E+11 | 0.00 | 3.75 |
June | 0.170016E+11 | 4760937.82 | 0.00 | 60683450.12 | 0.00 | 43331162.38 | 0.183849E+11 | 0.00 | 3.94 |
July | 0.105035E+11 | 0.433739E+09 | 0.00 | 90787556.80 | 0.00 | 5924956.70 | 0.188096E+11 | 0.00 | 4.03 |
August | 0.857015E+10 | 0.121607E+10 | 0.00 | 78664679.33 | 0.00 | 0.00 | 0.168705E+11 | 0.00 | 4.04 |
September | 0.183456E+11 | 8047348.75 | 0.00 | 57262521.59 | 0.00 | 37160192.09 | 0.178304E+11 | 0.00 | 3.89 |
October | 0.373971E+11 | 0.00 | 0.00 | 11798511.22 | 0.00 | 0.119687E+09 | 0.845302E+10 | 0.00 | 3.63 |
November | 0.511617E+11 | 0.00 | 0.00 | 1871777.80 | 0.00 | 0.114186E+10 | 0.136499E+10 | 0.00 | 3.57 |
December | 0.596258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391431E+10 | 0.00 | 0.00 | 3.55 |
Annual Sum or Average | 0.433135E+12 | 0.168789E+10 | 0.00 | 0.356326E+09 | 0.00 | 0.189896E+11 | 0.101714E+12 | 0.00 | 3.73 |
Minimum of Months | 0.857015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 |
Maximum of Months | 0.596258E+11 | 0.121607E+10 | 0.00 | 90787556.80 | 0.00 | 0.761430E+10 | 0.188096E+11 | 0.00 | 4.04 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.531892E+11 | 0.00 | 0.00 | 270800.18 | 0.00 | 0.00 | 0.861219E+09 | 0.00 | 7.43 |
February | 0.412897E+11 | 0.00 | 0.00 | 4124310.70 | 0.00 | 0.00 | 0.613157E+10 | 0.00 | 7.45 |
March | 0.395048E+11 | 0.00 | 0.00 | 6415128.60 | 0.00 | 0.00 | 0.791814E+10 | 0.00 | 7.29 |
April | 0.251463E+11 | 0.00 | 0.00 | 25687199.99 | 0.00 | 0.00 | 0.179202E+11 | 0.00 | 7.30 |
May | 0.162496E+11 | 0.00 | 0.00 | 56185526.75 | 0.00 | 0.00 | 0.259533E+11 | 0.00 | 7.33 |
June | 0.761168E+10 | 0.00 | 0.00 | 81131287.46 | 0.00 | 0.00 | 0.293800E+11 | 0.00 | 7.40 |
July | 0.320284E+10 | 0.193587E+09 | 0.00 | 0.114594E+09 | 0.00 | 0.00 | 0.289339E+11 | 0.00 | 7.52 |
August | 0.246131E+10 | 0.386624E+09 | 0.00 | 0.102154E+09 | 0.00 | 0.00 | 0.252882E+11 | 0.00 | 7.67 |
September | 0.688520E+10 | 0.00 | 0.00 | 77191491.10 | 0.00 | 0.00 | 0.301704E+11 | 0.00 | 7.42 |
October | 0.183759E+11 | 0.00 | 0.00 | 27654324.82 | 0.00 | 0.00 | 0.255217E+11 | 0.00 | 7.33 |
November | 0.344047E+11 | 0.00 | 0.00 | 8318704.69 | 0.00 | 0.00 | 0.112812E+11 | 0.00 | 7.31 |
December | 0.489766E+11 | 0.00 | 0.00 | 295828.28 | 0.00 | 0.00 | 0.235610E+10 | 0.00 | 7.35 |
Annual Sum or Average | 0.297298E+12 | 0.580211E+09 | 0.00 | 0.504022E+09 | 0.00 | 0.00 | 0.211716E+12 | 0.00 | 7.40 |
Minimum of Months | 0.246131E+10 | 0.00 | 0.00 | 270800.18 | 0.00 | 0.00 | 0.861219E+09 | 0.00 | 7.29 |
Maximum of Months | 0.531892E+11 | 0.386624E+09 | 0.00 | 0.114594E+09 | 0.00 | 0.00 | 0.301704E+11 | 0.00 | 7.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.758906E+10 | 0.159000E+11 | 0.199653E+12 | 0.00 | 0.246699E+11 |
February | 0.263875E+11 | 0.139650E+11 | 0.173689E+12 | 79332297.41 | 0.217812E+11 |
March | 0.533365E+11 | 0.144003E+11 | 0.174023E+12 | 92766088.87 | 0.219206E+11 |
April | 0.928823E+11 | 0.135984E+11 | 0.156826E+12 | 0.531095E+09 | 0.266669E+11 |
May | 0.125368E+12 | 0.138000E+11 | 0.154307E+12 | 0.117299E+10 | 0.348346E+11 |
June | 0.129462E+12 | 0.120944E+11 | 0.137148E+12 | 0.253280E+10 | 0.444746E+11 |
July | 0.136570E+12 | 0.105565E+11 | 0.121741E+12 | 0.287335E+10 | 0.697089E+11 |
August | 0.106015E+12 | 0.825397E+10 | 0.105404E+12 | 0.257270E+10 | 0.809084E+11 |
September | 0.669985E+11 | 0.986849E+10 | 0.139290E+12 | 0.208137E+10 | 0.414285E+11 |
October | 0.402614E+11 | 0.117416E+11 | 0.161647E+12 | 0.556835E+09 | 0.203270E+11 |
November | 0.112682E+11 | 0.129975E+11 | 0.169908E+12 | 73122671.36 | 0.198572E+11 |
December | 0.329125E+10 | 0.145440E+11 | 0.191147E+12 | 0.00 | 0.231158E+11 |
Annual Sum or Average | 0.799430E+12 | 0.151720E+12 | 0.188478E+13 | 0.125664E+11 | 0.429694E+12 |
Minimum of Months | 0.329125E+10 | 0.825397E+10 | 0.105404E+12 | 0.00 | 0.198572E+11 |
Maximum of Months | 0.136570E+12 | 0.159000E+11 | 0.199653E+12 | 0.287335E+10 | 0.809084E+11 |