Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:28:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2279.95 | 4460.41 | 4460.41 |
Net Site Energy | 2279.95 | 4460.41 | 4460.41 |
Total Source Energy | 5613.39 | 10981.82 | 10981.82 |
Net Source Energy | 5613.39 | 10981.82 | 10981.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 338.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 369.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.42 | 286.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 64.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1508.36 | 771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 338.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 369.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.42 | 286.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 338.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 127.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 72.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 460.72 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 369.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.42 | 286.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 64.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1532.87 | 590.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1028.24 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2950.90 | 1509.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 389.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1532.87 | 590.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 1028.24 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2950.90 | 1509.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1508.364 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1508.364 | 100.00 |
Total On-Site and Utility Electric Sources | 1508.364 | 100.00 |
Total Electricity End Uses | 1508.364 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4656.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 14.4672 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.5854 | 18.52 | 1063.0801 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 13.6812 | 1.78 | 337.1505 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 14.4672 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.5854 | 18.52 | 1063.0801 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Conditioned Total | 511.15 | 13.6812 | 0.89 | 337.1505 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 13.6812 | 1.78 | 337.1505 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-17:10 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 24-FEB-19:10 |
Heating | 0.00 | 47441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46746.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20676.91 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13718.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4190.76 | 17504.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2066.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93711.61 | 78522.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 47441.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46746.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13718.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4190.76 | 17504.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 523.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 998.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 16.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1072.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 402.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 228.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1459.09 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1169.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.85 | 311.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 205.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4776.99 | 836.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2097.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2287.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.29 | 608.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 401.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9345.51 | 1636.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2097.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 788.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 446.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2854.50 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2287.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.29 | 608.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 401.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9345.51 | 1636.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 5.03 |
KITCHEN DIRECT AIR | 1.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 5.03 | 5.03 | 5.03 | 5.03 | 5.03 | 5.03 | 1.00 | 1.00 | 5.03 |
PSZ-AC_2:2 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 1.00 | 1.000000 | 1.90 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 5.03 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.90 | 1.50 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 5.03 | 9439.70 |
PSZ-AC_2:2_ADDAQ FAN | 1.90 | 2075.60 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 5.03 | 5.03 | 5.03 | 5.03 | 102712.04 | 134921.53 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.90 | 1.90 | 1.90 | 1.90 | 47091.57 | 82503.28 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 5.03 | 2.51 | 5.03 | 102712.04 | 51304.34 | 102712.04 | 0.767910 | 0.767910 |
PSZ-AC_2:2 COOLING COIL | 1.90 | 0.948189 | 1.90 | 47091.57 | 23545.79 | 47091.57 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 134921.53 |
PSZ-AC_2:2 HEATING COIL | 82503.28 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 14.467 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 79.395 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.585 | 413.804 | 649.276 | 0.000 | 0.000 | 0.000 | 1074.665 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 5378.143 | 14.467 | 19.198 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5378.143 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1615.060 | 11.585 | 214.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1615.060 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 515.917 | 3.701 | 68.534 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 851.667 | 6.109 | 113.135 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 6 | 0.167 | 1.500 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4325 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 6 | 0.19952834E-07 | 0.37147198E-09 | 0.46430291E-08 | -0.89111870E-13 |
34 | 5 | -0.14466088E-03 | 0.34030017E-05 | -0.74831287E-04 | 0.46077240E-08 |
35 | 4 | 0.23721950 | 0.17579200E-02 | 0.80016642E-01 | -0.26003020E-04 |
36 | 3 | -6.1742659 | 0.57392279E-01 | -2.0151465 | 0.23669466E-01 |
37 | 2 | 37.264580 | 0.21353215 | 13.926457 | -0.29319906 |
38 | 1 | -77.776780 | 0.10018737 | -27.938560 | 1.0196200 |
39 | 0 | 46.824358 | 0.20941775E-02 | 16.322275 | |
40 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
41 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
42 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
43 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
44 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
45 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
46 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
47 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
48 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
49 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
50 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
51 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
52 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
53 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
54 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
55 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
2 | NONRESWINDOW_U_0.7141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
3 | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 | ||
4 | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 4.059 | 4.059 | 1.000 | 0.254 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.13055 | 0.52274 | 0.52274 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 2.55531E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.747 | 0.2487 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 0.173 | 4.666E-004 | 1.025E-003 | 0.551 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 0.109 | 7.834E-004 | 1.007E-003 | 0.925 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 52321.45532 | 62785.74639 | 4.18984 | 5.02781 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 6642.08389 | 7970.50067 | 0.31359 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 0.50000 | 4.31558E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 23253.85619 | 27904.62742 | 1.58031 | 1.89638 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.50017 | 00:10:00 | 0.50000 | 4.31558E-003 | 139.40524 | 7.52790 | 1.50017 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 86336.16 | 5.02781 | 5.02781 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 57769.76 | 1.33138 | 1.33138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 50873.89 | 1.89638 | 1.89638 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 65093.85 | 1.50017 | 1.50017 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.02781 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89638 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.02781 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.02781 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.02781 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 5.02781 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02781 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 5.02781 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89638 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89638 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89638 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89638 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89638 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89638 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 5.02781 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.89638 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02781 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.02781 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 9439.70182 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.02781 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.02781 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.02781 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.02781 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.02781 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.51390 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.02781 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 102712.04000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 51304.33551 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 102712.04000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76791 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76791 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 102712.04000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 134921.52676 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 134921.52676 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89638 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.50017 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89638 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2075.59572 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89638 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89638 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89638 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.89638 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89638 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94819 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.89638 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47091.57000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 23545.78610 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 47091.57000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47091.57000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 82503.28420 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 82503.28420 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 99082.7 | 9.71 | 9.59 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 45743.7 | 10.12 | 9.99 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | N/A | 4.059 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | N/A | 4.059 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | N/A | 4.059 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.500 | 1.225 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.1254434624E-002 | 0.1795952048 | Pass | Pass | 5.6842248370E-002 | 0.1235693012 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1835476276 | 0.6033686802 | Pass | Pass | 6.1509738767E-002 | 0.2374857519 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4487100452 | 0.4070967818 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1105.87 | 61.02 | 775.12 | 118.24 | 1703.71 | 3763.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.225 | 1.500 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.7141_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.7141_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.7141_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 4.059 | 0.254 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 4.059 | 0.254 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 4.059 | 0.254 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 14.4672 | 371.75 | 5378.14 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 97.85 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.5854 | 139.41 | 1615.06 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.38 |
Interior Lighting Total | 13.6812 | 511.15 | 6993.20 | 127.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.79 | 83.79 | 72.01 | |
Exterior Lighting Total | 4578.48 | 72.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 102712.04 | 78873.60 | 23838.44 | 0.77 | 3.23 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47091.57 | 33014.96 | 14076.61 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 99082.7 | 9.71 | 9.59 | ||||
PSZ-AC_2:2 COOLING COIL | 45743.7 | 10.12 | 9.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 134921.53 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 82503.28 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 2.83 | 2203.40 | 778.12 | 1.00 | 0.58 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.59 | 1110.54 | 5.03 | 9439.70 | 1877.50 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.90 | 2075.60 | 1094.51 | 1.00 | 1.29 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 52321.46 | 62785.75 | 168.89 | 4.190 | 5.028 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 23.99 | 0.00932 | 40.53 | 0.00563 | 1.331 | 0.00 |
KITCHEN | 23253.86 | 27904.63 | 200.17 | 1.580 | 1.896 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01009 | 39.60 | 0.00563 | 1.500 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 6642.08 | 7970.50 | 21.44 | 0.314 | 1.331 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.500 | 00:10:00 | 19.00 | 22.85 | 0.00394 | 0.50 | 0.00432 | 1.500 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 5.03 | 5.03 | 1.33 | 1.33 | 5.0278 | 5.0278 | 5.0278 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.90 | 1.90 | 1.50 | 1.50 | 1.8964 | 1.8964 | 1.8964 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 102712.040 | 78873.603 | 5.027810 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 102712.04 | 102712.04 | 5.027810 | 28.45 | 16.77 | 0.00834485 | 11.12 | 10.39 | 0.00834485 | 40.80 | 0.00563111 | 18.58 | 26.4803 | 23.99 | 0.00932350 | 45.5232 | 52268.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 134921.527 | 134921.527 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 | 134921.53 | 134921.53 | 5.027810 | 15.57 | 10.73 | 0.00685453 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 26.4803 | 21.00 | 0.00776901 | 45.6135 | 6635.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 47091.570 | 33014.958 | 1.896380 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 47091.57 | 47091.57 | 1.896380 | 38.14 | 18.36 | 0.00642835 | 11.82 | 8.70 | 0.00642835 | 40.80 | 0.00563111 | 18.58 | 79.1071 | 25.99 | 0.01008039 | 43.6543 | 22399.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 82503.284 | 82503.284 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 82503.28 | 82503.28 | 1.896378 | 0.40 | 0.33 | 0.00423621 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 79.1072 | 22.85 | 0.00393565 | 20.7674 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 102712.040 | 78873.603 | 5.027810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3527 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.027810 | 5.49637233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 102712.04 | 102712.04 | 1.0000 | 5.49637281 | 5.027810 | 28.45 | 16.77 | 0.00834485 | 49895.2 | 11.12 | 10.39 | 0.00834485 | 32213.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102712.04 | 40.80 | 0.00563111 | 18.58 | 1.33137743 | 26.4803 | 23.99 | 0.00932350 | 23.99 | 0.00932350 | 45.5232 | 52268.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 134921.527 | 134921.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 5.027810 | 5.49637233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:30:00 | Sensible | 134921.53 | 134921.53 | 1.0000 | 5.49637233 | 5.027810 | 15.57 | 10.73 | 0.00685453 | 32987.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 134921.53 | 0.50 | 0.00431558 | 0.50 | 1.33137743 | 26.4803 | 21.00 | 0.00776901 | 21.00 | 0.00776901 | 45.6135 | 6635.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47091.570 | 33014.958 | 1.896380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.7900 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.896378 | 2.07310904 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 47091.57 | 47091.57 | 1.0000 | 2.07311165 | 1.896380 | 38.14 | 18.36 | 0.00642835 | 54856.8 | 11.82 | 8.70 | 0.00642835 | 28090.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47091.57 | 40.80 | 0.00563111 | 18.58 | 1.50017041 | 79.1071 | 25.95 | 0.01008039 | 25.99 | 0.01008039 | 43.6543 | 22399.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 82503.284 | 82503.284 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.896378 | 2.07310904 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 82503.28 | 82503.28 | 1.0000 | 2.07310904 | 1.896378 | 0.40 | 0.33 | 0.00423621 | 10995.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82503.28 | 0.50 | 0.00431558 | 0.50 | 1.50017041 | 79.1072 | 0.00 | 0.00393565 | 22.85 | 0.00393565 | 20.7674 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 5.03 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.50 | 1.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4539.50 | 1402.17 | 328.00 |
KITCHEN | 6032.00 | 5564.33 | 4631.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6042.50 | 5737.33 | 4656.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 27.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 227.17 | 0.00 | 4.17 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 253.67 | 0.00 | 4.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 6.141 | 0.913 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 13.899 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.200 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 12.556 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 50276189.23 | 0.00 | 50276189.23 | 7437117.95 | 57713307.17 | 41986318.57 | 1430.35 | 4681.08 | 2648.57 | 232.36 |
KITCHEN | 43326927.25 | 0.00 | 43326927.25 | 230040.68 | 43556967.93 | 47309374.20 | 1391.90 | 5235.83 | 2132.27 | 700.93 |
Total Facility | 93603116.48 | 0.00 | 93603116.48 | 7667158.62 | 0.10E+09 | 89295692.77 | 1451.93 | 5763.12 | 3232.08 | 754.95 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.8966 | 0.0000 | 1.8966 | 0.2821 | 2.1787 | 1.3314 | 0.00 | 4611.25 | 2575.75 |
KITCHEN | 1.6022 | 0.0000 | 1.6022 | 0.0055 | 1.6077 | 1.5002 | 0.00 | 5152.01 | 2034.99 |
Total Facility | 3.4988 | 0.0000 | 3.4988 | 0.2876 | 3.7864 | 2.8315 | 0.00 | 5670.86 | 3094.60 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 60083736.90 | 0.00 | 60083736.90 | 41986318.57 | 1429.49 | 0.22 | 7330.29 | 232.36 |
PSZ-AC_2:2 | 51778866.73 | 0.00 | 51778866.73 | 47309374.20 | 1369.82 | 2.39 | 7387.78 | 700.93 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 2.2666 | 0.0000 | 2.2666 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.9147 | 0.0000 | 1.9147 | 1.5002 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1453.12 | 1290.91 | 4675.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4688.71 | 2328.88 | 870.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 4.2061 | 2.7035 | 1.5915 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 1.7931 | 2.2214 | 1.7942 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 377 |
Defaulted Fields | 276 |
Fields with Defaults | 887 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
Electricity:Building | 604.81 | 4434.71 | 01-JAN-01:10 | 33358.73 | 02-JAN-11:10 |
Electricity:Zone:DINING | 223.13 | 1289.45 | 01-JAN-01:10 | 11839.96 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 587.95 | 4025.67 | 01-JAN-01:10 | 30993.57 | 02-JAN-11:10 |
InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 97.85 | 806.72 | 01-JAN-01:10 | 4840.33 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 127.24 | 1048.98 | 01-JAN-01:10 | 6293.88 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 381.68 | 3145.26 | 01-JAN-01:10 | 21518.76 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 29.39 | 242.26 | 01-JAN-01:10 | 1453.55 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 460.72 | 2976.69 | 01-JAN-01:10 | 24699.69 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 335.44 | 2493.96 | 01-JAN-01:10 | 17700.06 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 64.87 | 1038.02 | 05-DEC-23:30 | 3441.39 | 13-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 16.85 | 255.65 | 01-JAN-23:30 | 2365.15 | 02-JAN-11:10 |
Electricity:Plant | 123.88 | 1103.54 | 08-DEC-01:10 | 6477.44 | 13-NOV-19:30 |
LowTempRefrigeration:Refrigeration:Electricity | 17.01 | 0.00 | 01-JAN-11:10 | 1501.56 | 28-APR-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 31.01 | 777.33 | 23-NOV-01:10 | 1076.23 | 08-JAN-14:30 |
ElectricityPurchased:Facility | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
ElectricityPurchased:Plant | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
Cogeneration:ElectricityPurchased | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
ElectricityNet:Plant | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
Cogeneration:ElectricityNet | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
General:Cogeneration:ElectricityNet | 1508.36 | 10116.73 | 08-DEC-01:10 | 93711.61 | 28-JUN-17:10 |
Electricity:HVAC | 707.66 | 0.00 | 01-JAN-01:10 | 60465.57 | 28-JUN-17:10 |
Fans:Electricity | 369.14 | 0.00 | 01-JAN-01:10 | 13718.70 | 03-JAN-05:10 |
General:Fans:Electricity | 369.14 | 0.00 | 01-JAN-01:10 | 13718.70 | 03-JAN-05:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 338.53 | 0.00 | 01-JAN-00:10 | 46746.86 | 28-JUN-17:10 |
General:Cooling:Electricity | 338.53 | 0.00 | 01-JAN-00:10 | 46746.86 | 28-JUN-17:10 |
ExteriorLights:Electricity | 72.01 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.01 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.94 | 27-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 75.42 | 0.00 | 01-JAN-01:10 | 4741.94 | 27-FEB-07:30 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 20-JAN-11:00 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 20-JAN-11:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 771.59 | 2803.57 | 01-JAN-01:10 | 78522.85 | 06-DEC-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 14.91 | 0.00 | 01-JAN-01:10 | 50171.43 | 06-DEC-07:00 |
Heating:NaturalGas | 14.91 | 0.00 | 01-JAN-01:10 | 50171.43 | 06-DEC-07:00 |
General:Heating:NaturalGas | 14.91 | 0.00 | 01-JAN-01:10 | 50171.43 | 06-DEC-07:00 |
NaturalGas:Plant | 286.90 | 993.32 | 01-JAN-00:10 | 21866.20 | 18-JAN-08:00 |
WaterSystems:NaturalGas | 286.90 | 993.32 | 01-JAN-00:10 | 21866.20 | 18-JAN-08:00 |
Water Heater:WaterSystems:NaturalGas | 286.90 | 993.32 | 01-JAN-00:10 | 21866.20 | 18-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 20-MAR-19:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 24-FEB-19:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2240.67 | 3207.54 | 06-DEC-01:10 | 198030.41 | 18-AUG-11:10 |
EnergyTransfer:Building | 932.17 | 1603.77 | 06-DEC-01:10 | 63912.01 | 26-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN | 485.23 | 1603.77 | 06-DEC-01:10 | 28919.25 | 21-APR-04:10 |
Refrigeration:EnergyTransfer | 154.56 | 2714.19 | 05-DEC-23:30 | 7834.84 | 28-APR-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.28 | 1357.09 | 05-DEC-23:30 | 3917.42 | 28-APR-03:20 |
General:Refrigeration:EnergyTransfer | 77.28 | 1357.09 | 05-DEC-23:30 | 3917.42 | 28-APR-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 77.28 | 1357.09 | 05-DEC-23:30 | 3917.42 | 28-APR-03:20 |
EnergyTransfer:Plant | 272.73 | 1603.77 | 06-DEC-01:10 | 16853.04 | 23-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 15.48 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.80 | 1341.99 | 23-NOV-01:10 | 2238.70 | 08-JAN-14:30 |
EnergyTransfer:Zone:DINING | 446.95 | 0.00 | 01-JAN-01:10 | 48359.02 | 17-OCT-03:50 |
Heating:EnergyTransfer | 3.11 | 0.00 | 01-JAN-00:10 | 18768.05 | 29-MAY-03:50 |
Heating:EnergyTransfer:Zone:DINING | 3.11 | 0.00 | 01-JAN-00:10 | 18768.05 | 29-MAY-03:50 |
General:Heating:EnergyTransfer | 3.11 | 0.00 | 01-JAN-00:10 | 18768.05 | 29-MAY-03:50 |
General:Heating:EnergyTransfer:Zone:DINING | 3.11 | 0.00 | 01-JAN-00:10 | 18768.05 | 29-MAY-03:50 |
Cooling:EnergyTransfer | 851.78 | 0.00 | 01-JAN-01:10 | 61285.08 | 26-AUG-18:10 |
Cooling:EnergyTransfer:Zone:DINING | 443.84 | 0.00 | 01-JAN-01:10 | 41575.73 | 28-JUN-17:20 |
General:Cooling:EnergyTransfer | 851.78 | 0.00 | 01-JAN-01:10 | 61285.08 | 26-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 443.84 | 0.00 | 01-JAN-01:10 | 41575.73 | 28-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 407.95 | 0.00 | 01-JAN-01:10 | 25075.07 | 21-APR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 407.95 | 0.00 | 01-JAN-01:10 | 25075.07 | 21-APR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
EnergyTransfer:HVAC | 1035.77 | 0.00 | 01-JAN-01:10 | 128067.54 | 19-JUL-12:00 |
HeatingCoils:EnergyTransfer | 11.93 | 0.00 | 01-JAN-01:10 | 40137.14 | 06-DEC-07:00 |
CoolingCoils:EnergyTransfer | 1023.85 | 0.00 | 01-JAN-00:10 | 128067.54 | 19-JUL-12:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 195.45 | 0.00 | 01-JAN-01:10 | 14210.44 | 25-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.112 | -443.832 | 0.000 | 0.000 | 208.302 | 97.852 | 93.957 | 53.758 | 0.000 | 28.894 | 11.968 | 0.000 | -22.142 | 0.000 | -31.870 | -0.001 |
KITCHEN | 0.000 | 0.000 | 0.000 | -407.935 | 0.000 | 0.000 | 5.055 | 29.385 | 297.857 | 0.000 | 0.000 | 0.410 | 76.972 | 0.000 | 0.000 | 0.000 | -1.743 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.272 | 35.644 | 0.000 | 0.000 | 0.000 | -46.917 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.112 | -851.767 | 0.000 | 0.000 | 213.357 | 127.237 | 391.814 | 53.758 | 0.000 | 40.576 | 124.584 | 0.000 | -22.142 | 0.000 | -80.531 | -0.002 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 10-NOV-04:01 | 0.00 | 0.00 | 0.00 | -122229.36 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 122859.58 | 0.00 | -2092.34 | 0.00 | -249.73 | 0.00 |
KITCHEN | 07-NOV-04:41 | 0.00 | 0.00 | 0.00 | -78567.91 | 0.00 | 0.00 | 0.00 | 242.26 | 3821.48 | 0.00 | 0.00 | 0.00 | 74833.42 | 0.00 | -0.00 | 0.00 | -329.24 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-NOV-04:01 | 0.00 | 0.00 | 0.00 | -189893.36 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1040.24 | 185650.07 | 0.00 | -2092.34 | 0.00 | -480.20 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-MAY-03:45 | 0.00 | 0.00 | 56758.54 | 0.00 | 0.00 | 0.00 | 0.00 | 806.72 | 905.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1288.29 | 0.00 | -36.32 | -57145.77 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-MAY-03:45 | -7562.00 | 7562.00 | 56758.54 | -7562.00 | 0.00 | 0.00 | 0.00 | 1048.98 | 4726.60 | 0.00 | 0.00 | 1249.92 | 0.00 | 0.00 | -1288.29 | 0.00 | -123.07 | -54810.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.0278 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 5.0278 | 0.2648 | 1.0000 | Not calculated | 1.3314 | 0.2648 | ||
PSZ-AC_2:2 | 1.8964 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8964 | 0.0963 | 1.0000 | Not calculated | 0.1826 | 0.0963 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 5.0278 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 5.0278 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2648 | ||
PSZ-AC_2:2 | 1.8964 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8964 | 0.1217 | 1.0000 | Not calculated | 0.1826 | 0.0963 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0278 | 5.0278 | 5.0278 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8964 | 1.8964 | 1.8964 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.0278 | 5.0278 | 5.0278 | 5.0278 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8964 | 1.8964 | 1.8964 | 1.8964 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0278 | 5.0278 | 5.0278 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8964 | 1.8964 | 1.8964 | No | 0.1826 | 0.1217 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 5.0278 | 5.0278 | 5.0278 | 5.0278 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8964 | 1.8964 | 1.8964 | 1.8964 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4.17 |
Number of hours not met | 4.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 14.91 | 50171.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 338.53 | 46746.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 127.24 | 6293.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.01 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 369.14 | 13718.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.42 | 4741.94 | 286.90 | 21866.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 16.85 | 2365.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.01 | 1501.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.01 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 525.59 | 1508.36 |
Natural Gas | 469.79 | 771.59 |
Additional | 0.00 | 0.00 |
Total | 995.37 | 2279.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 248.92 |
Space Heating | 0.00 |
Space Cooling | 662.28 |
Fans (All) | 722.16 |
Service Water Heating | 147.55 |
Receptacle Equipment | 901.33 |
Miscellaneous (All) | 2950.90 |
Subtotal | 2950.90 |
Natural Gas [MJ/m2] | |
Space Heating | 29.16 |
Service Water Heating | 561.27 |
Miscellaneous (All) | 1509.51 |
Subtotal | 1509.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.58 |
Space Heating | 0.65 |
Space Cooling | 14.85 |
Fans (All) | 16.19 |
Service Water Heating | 15.89 |
Receptacle Equipment | 40.81 |
Miscellaneous | 6.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3433. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8372.50 | 387.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7758.83 | 988.83 | 12.33 | 0.00 | 0.00 |
ATTIC | 5256.83 | 1048.50 | 904.33 | 1259.50 | 290.83 |
Min | 5256.83 | 387.50 | 0.00 | 0.00 | 0.00 |
Max | 8372.50 | 1048.50 | 904.33 | 1259.50 | 290.83 |
Average | 7129.39 | 808.28 | 305.56 | 419.83 | 96.94 |
Sum | 21388.17 | 2424.83 | 916.67 | 1259.50 | 290.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 822591.00 | 1631.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 822591.00 | 1631.00 | 0.00 | 0.00 | 0.00 |
Average | 280608.00 | 543.67 | 0.00 | 0.00 | 0.00 |
Sum | 841824.00 | 1631.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8350.83 | 409.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6853.17 | 1906.17 | 0.67 | 0.00 | 0.00 |
ATTIC | 5420.17 | 1604.17 | 458.50 | 361.50 | 915.67 |
Min | 5420.17 | 409.17 | 0.00 | 0.00 | 0.00 |
Max | 8350.83 | 1906.17 | 458.50 | 361.50 | 915.67 |
Average | 6874.72 | 1306.50 | 153.06 | 120.50 | 305.22 |
Sum | 20624.17 | 3919.50 | 459.17 | 361.50 | 915.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 813078.00 | 11144.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15830.50 | 3402.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 813078.00 | 11144.00 | 0.00 | 0.00 | 0.00 |
Average | 276302.83 | 4848.83 | 0.00 | 0.00 | 0.00 |
Sum | 828908.50 | 14546.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280785E+11 | 94508.25 | 08-JAN-04:01 | 17.00 | 11.36 | 0.149770E+11 | 14053.29 | 07-JAN-19:00 | 17.00 | 11.36 |
February | 0.201681E+11 | 20012.45 | 19-FEB-04:04 | 13.00 | 11.23 | 0.134661E+11 | 14050.30 | 25-FEB-19:10 | 14.83 | 9.57 |
March | 0.265926E+11 | 103542.81 | 22-MAR-03:01 | 13.62 | 9.20 | 0.151943E+11 | 14051.45 | 18-MAR-18:49 | 13.62 | 9.20 |
April | 0.383575E+11 | 120289.42 | 20-APR-03:01 | 13.83 | 5.67 | 0.148881E+11 | 14052.57 | 15-APR-18:00 | 13.83 | 5.67 |
May | 0.432225E+11 | 121301.29 | 01-MAY-03:01 | 13.58 | 4.86 | 0.154337E+11 | 14051.38 | 13-MAY-18:00 | 27.00 | 9.96 |
June | 0.498815E+11 | 101183.35 | 10-JUN-03:01 | 21.00 | 10.89 | 0.150277E+11 | 14054.36 | 17-JUN-18:49 | 37.33 | 20.40 |
July | 0.499472E+11 | 102919.22 | 02-JUL-03:01 | 19.82 | 7.15 | 0.153457E+11 | 14053.04 | 22-JUL-18:00 | 36.00 | 20.16 |
August | 0.500406E+11 | 102093.76 | 24-AUG-03:01 | 20.17 | 9.90 | 0.155400E+11 | 14052.91 | 05-AUG-18:30 | 20.17 | 9.90 |
September | 0.459698E+11 | 98786.80 | 29-SEP-03:41 | 20.37 | 11.27 | 0.149185E+11 | 14053.36 | 23-SEP-18:00 | 20.37 | 11.27 |
October | 0.378439E+11 | 121705.95 | 18-OCT-03:01 | 14.00 | 5.24 | 0.152435E+11 | 14051.48 | 21-OCT-18:00 | 22.00 | 14.08 |
November | 0.287558E+11 | 122247.23 | 10-NOV-04:01 | 12.83 | 5.58 | 0.145842E+11 | 14050.33 | 04-NOV-18:10 | 12.83 | 5.58 |
December | 0.249775E+11 | 25115.21 | 22-DEC-12:55 | 24.00 | 9.96 | 0.146419E+11 | 14051.38 | 02-DEC-19:00 | 24.00 | 9.96 |
Annual Sum or Average | 0.443836E+12 | 0.179261E+12 | ||||||||
Minimum of Months | 0.201681E+11 | 20012.45 | 12.83 | 4.86 | 0.134661E+11 | 14050.30 | 12.83 | 5.58 | ||
Maximum of Months | 0.500406E+11 | 122247.23 | 24.00 | 11.36 | 0.155400E+11 | 14054.36 | 37.33 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319629E+11 | 74639.75 | 28-JAN-04:01 | 9.50 | 2.42 | 0.105580E+11 | 6934.93 | 23-JAN-11:00 | 9.50 | 2.42 |
February | 0.288230E+11 | 69968.99 | 01-FEB-04:01 | 6.67 | 4.40 | 0.950982E+10 | 6934.89 | 17-FEB-11:00 | 18.00 | 14.26 |
March | 0.316348E+11 | 77864.89 | 28-MAR-03:41 | 3.90 | 0.57 | 0.105687E+11 | 6934.95 | 03-MAR-11:00 | 3.90 | 0.57 |
April | 0.328895E+11 | 77087.49 | 21-APR-03:01 | 9.67 | 1.37 | 0.102572E+11 | 6934.92 | 07-APR-10:00 | 9.67 | 1.37 |
May | 0.349747E+11 | 68673.31 | 14-MAY-03:01 | 14.00 | 4.29 | 0.106049E+11 | 6934.91 | 26-MAY-10:50 | 27.83 | 12.63 |
June | 0.364127E+11 | 59516.74 | 13-JUN-03:21 | 21.50 | 8.63 | 0.102669E+11 | 6934.92 | 30-JUN-10:09 | 34.33 | 19.17 |
July | 0.379790E+11 | 59646.29 | 02-JUL-03:21 | 19.45 | 6.99 | 0.106028E+11 | 6934.95 | 21-JUL-10:39 | 34.67 | 22.02 |
August | 0.378677E+11 | 57232.67 | 25-AUG-02:62 | 21.00 | 8.78 | 0.106092E+11 | 6934.97 | 01-AUG-10:00 | 21.00 | 8.78 |
September | 0.361440E+11 | 51199.46 | 29-SEP-01:22 | 21.35 | 11.60 | 0.102632E+11 | 6934.96 | 12-SEP-10:50 | 21.35 | 11.60 |
October | 0.346664E+11 | 76175.55 | 25-OCT-03:01 | 8.67 | 2.20 | 0.105883E+11 | 6934.94 | 11-OCT-10:50 | 8.67 | 2.20 |
November | 0.321930E+11 | 78574.04 | 07-NOV-04:41 | 7.17 | 1.17 | 0.102234E+11 | 6934.94 | 14-NOV-11:00 | 17.70 | 16.26 |
December | 0.323973E+11 | 73625.69 | 29-DEC-04:01 | 7.00 | 2.27 | 0.105221E+11 | 6934.90 | 01-DEC-11:09 | 7.00 | 2.27 |
Annual Sum or Average | 0.407945E+12 | 0.124575E+12 | ||||||||
Minimum of Months | 0.288230E+11 | 51199.46 | 3.90 | 0.57 | 0.950982E+10 | 6934.89 | 3.90 | 0.57 | ||
Maximum of Months | 0.379790E+11 | 78574.04 | 21.50 | 11.60 | 0.106092E+11 | 6934.97 | 34.67 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 | 1.81 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 | 11.09 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 | 14.60 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 | 18.35 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 | 16.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 | 15.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 | 10.27 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.00 | 0.00 | 4.27 | 1.81 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.00 | 0.00 | 29.40 | 18.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 337546.34 | 3169.59 | 02-JAN-05:03 | 4.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 1075015.33 | 8483.67 | 22-MAR-03:03 | 13.62 |
April | 0.130081E+09 | 52299.69 | 12-APR-03:47 | 18.17 |
May | 0.414127E+09 | 56759.26 | 15-MAY-03:45 | 19.00 |
June | 0.749584E+09 | 42920.57 | 11-JUN-03:44 | 21.17 |
July | 0.665730E+09 | 43744.66 | 03-JUL-03:44 | 21.17 |
August | 0.595089E+09 | 33464.97 | 25-AUG-03:30 | 21.50 |
September | 0.422060E+09 | 34789.85 | 29-SEP-03:30 | 21.10 |
October | 0.118636E+09 | 55814.52 | 17-OCT-03:47 | 17.17 |
November | 15096341.72 | 35229.71 | 01-NOV-03:47 | 19.88 |
December | 559336.67 | 3277.21 | 07-DEC-05:02 | -1.1 |
Annual Sum or Average | 0.311238E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.749584E+09 | 56759.26 | 21.50 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826825E+10 | 4840.33 | 02-JAN-10:09 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.748896E+10 | 4840.33 | 01-FEB-10:09 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.839991E+10 | 4840.33 | 01-MAR-10:09 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.803398E+10 | 4840.33 | 01-APR-16:10 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.833408E+10 | 4840.33 | 01-MAY-09:09 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.811917E+10 | 4840.33 | 01-JUN-09:09 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.824986E+10 | 4840.33 | 01-JUL-16:10 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.839991E+10 | 4840.33 | 01-AUG-09:09 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.803591E+10 | 4840.33 | 01-SEP-09:09 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.826728E+10 | 4840.33 | 02-OCT-09:09 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.800397E+10 | 4840.33 | 01-NOV-09:09 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.825082E+10 | 4840.33 | 01-DEC-10:09 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.978521E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.748896E+10 | 4840.33 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.839991E+10 | 4840.33 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.248296E+10 | 1453.55 | 02-JAN-10:09 | 0.284894E+11 | 17700.06 | 01-JAN-11:09 |
February | 0.224894E+10 | 1453.55 | 01-FEB-10:09 | 0.257324E+11 | 17700.06 | 01-FEB-11:09 |
March | 0.252250E+10 | 1453.55 | 01-MAR-10:09 | 0.284894E+11 | 17700.06 | 01-MAR-11:09 |
April | 0.241261E+10 | 1453.55 | 01-APR-16:10 | 0.275704E+11 | 17700.06 | 01-APR-10:09 |
May | 0.250273E+10 | 1453.55 | 01-MAY-09:09 | 0.284894E+11 | 17700.06 | 01-MAY-10:09 |
June | 0.243819E+10 | 1453.55 | 01-JUN-09:09 | 0.275704E+11 | 17700.06 | 01-JUN-10:09 |
July | 0.247744E+10 | 1453.55 | 01-JUL-16:10 | 0.284894E+11 | 17700.06 | 01-JUL-10:09 |
August | 0.252250E+10 | 1453.55 | 01-AUG-09:09 | 0.284894E+11 | 17700.06 | 01-AUG-10:09 |
September | 0.241319E+10 | 1453.55 | 01-SEP-09:09 | 0.275704E+11 | 17700.06 | 01-SEP-10:09 |
October | 0.248267E+10 | 1453.55 | 02-OCT-09:09 | 0.284894E+11 | 17700.06 | 01-OCT-10:09 |
November | 0.240360E+10 | 1453.55 | 01-NOV-09:09 | 0.275704E+11 | 17700.06 | 01-NOV-10:09 |
December | 0.247773E+10 | 1453.55 | 01-DEC-10:09 | 0.284894E+11 | 17700.06 | 01-DEC-11:09 |
Annual Sum or Average | 0.293850E+11 | 0.335440E+12 | ||||
Minimum of Months | 0.224894E+10 | 1453.55 | 0.257324E+11 | 17700.06 | ||
Maximum of Months | 0.252250E+10 | 1453.55 | 0.284894E+11 | 17700.06 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.826825E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65662457.51 | 0.496209E+10 |
February | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626138E+10 |
March | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172924E+09 | 0.466998E+10 |
April | 0.292871E+11 | 0.803398E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216335E+10 | 0.102812E+10 |
May | 0.303219E+11 | 0.833408E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373088E+10 | 0.380235E+09 |
June | 0.295292E+11 | 0.811917E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646768E+10 | 61750469.70 |
July | 0.300798E+11 | 0.824986E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561022E+10 | 55780770.46 |
August | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525696E+10 | 0.143272E+09 |
September | 0.292871E+11 | 0.803591E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385155E+10 | 0.229116E+09 |
October | 0.300980E+11 | 0.826728E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143708E+10 | 0.233460E+10 |
November | 0.290996E+11 | 0.800397E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122920E+09 | 0.482811E+10 |
December | 0.300798E+11 | 0.825082E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15148529.07 | 0.691599E+10 |
Annual Sum or Average | 0.356244E+12 | 0.978521E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288944E+11 | 0.318704E+11 |
Minimum of Months | 0.272721E+11 | 0.748896E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55780770.46 |
Maximum of Months | 0.305458E+11 | 0.839991E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646768E+10 | 0.691599E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.248296E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 211507.97 | 0.261661E+09 |
February | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194559E+09 |
March | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 735534.53 | 0.282621E+09 |
April | 0.786997E+09 | 0.241261E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 23970887.22 | 0.115000E+09 |
May | 0.814802E+09 | 0.250273E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 52127248.56 | 79364559.03 |
June | 0.793501E+09 | 0.243819E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.107881E+09 | 29753742.76 |
July | 0.808298E+09 | 0.247744E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 93182003.81 | 32088149.01 |
August | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 66154058.57 | 44702497.44 |
September | 0.786997E+09 | 0.241319E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 49070906.08 | 67109401.84 |
October | 0.808786E+09 | 0.248267E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 15969066.53 | 0.158202E+09 |
November | 0.781956E+09 | 0.240360E+10 | 0.227653E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 440225.21 | 0.239665E+09 |
December | 0.808298E+09 | 0.247773E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 3.10 | 0.238665E+09 |
Annual Sum or Average | 0.957291E+10 | 0.293850E+11 | 0.276978E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.409742E+09 | 0.174339E+10 |
Minimum of Months | 0.732850E+09 | 0.224894E+10 | 0.212476E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29753742.76 |
Maximum of Months | 0.820818E+09 | 0.252250E+10 | 0.235241E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.107881E+09 | 0.282621E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113269E+10 | 0.290080E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682057E+09 | 0.288302E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678839E+09 | 0.366755E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106562E+10 | 0.500787E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113726E+10 | 0.525097E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951796E+09 | 0.529849E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654336E+09 | 0.482571E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854670E+09 | 0.463425E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673112E+09 | 0.362743E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114978E+10 | 0.326418E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949107E+09 | 0.283798E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134307E+10 | 0.271844E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112723E+11 | 0.469167E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654336E+09 | 0.271844E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134307E+10 | 0.529849E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 4840.33 | 02-JAN-10:09 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.27 | 31-JAN-14:00 | 8485.02 | 01-JAN-08:00 |
February | 30255.31 | 04-FEB-19:10 | 4840.33 | 01-FEB-10:09 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 9180.47 | 04-FEB-19:55 |
March | 30255.31 | 04-MAR-19:10 | 4840.33 | 01-MAR-10:09 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495.46 | 20-MAR-17:03 | 8320.71 | 26-MAR-06:10 |
April | 30255.31 | 01-APR-18:10 | 4840.33 | 01-APR-16:10 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5852.84 | 14-APR-17:03 | 4431.29 | 22-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 4840.33 | 01-MAY-09:09 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6933.81 | 31-MAY-17:03 | 3631.90 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 4840.33 | 01-JUN-09:09 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.91 | 28-JUN-17:10 | 1543.21 | 21-JUN-06:10 |
July | 30255.31 | 01-JUL-18:10 | 4840.33 | 01-JUL-16:10 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8298.16 | 22-JUL-18:03 | 2002.51 | 01-JUL-06:10 |
August | 30255.31 | 05-AUG-18:10 | 4840.33 | 01-AUG-09:09 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8983.69 | 25-AUG-17:03 | 4380.85 | 05-AUG-18:10 |
September | 30255.31 | 02-SEP-18:10 | 4840.33 | 01-SEP-09:09 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7077.55 | 07-SEP-17:03 | 2305.04 | 22-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 4840.33 | 02-OCT-09:09 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5443.38 | 06-OCT-12:00 | 6421.69 | 25-OCT-19:55 |
November | 30255.31 | 04-NOV-18:10 | 4840.33 | 01-NOV-09:09 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1982.46 | 01-NOV-13:00 | 8972.75 | 23-NOV-20:55 |
December | 30255.31 | 02-DEC-19:10 | 4840.33 | 01-DEC-10:09 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 752.96 | 25-DEC-14:00 | 10303.50 | 05-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.21 | |||||
Maximum of Months | 30255.31 | 4840.33 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 9524.91 | 10303.50 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 1453.55 | 02-JAN-10:09 | 14433.56 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 10.29 | 31-JAN-15:30 | 794.36 | 01-JAN-01:40 |
February | 813.01 | 04-FEB-19:10 | 1453.55 | 01-FEB-10:09 | 14433.56 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 730.90 | 05-FEB-04:00 |
March | 813.01 | 04-MAR-19:10 | 1453.55 | 01-MAR-10:09 | 14433.56 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 18.53 | 15-MAR-15:00 | 784.17 | 28-MAR-03:40 |
April | 813.01 | 01-APR-18:10 | 1453.55 | 01-APR-16:10 | 14433.56 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 100.89 | 30-APR-15:02 | 409.27 | 27-APR-00:20 |
May | 813.01 | 06-MAY-18:10 | 1453.55 | 01-MAY-09:09 | 14433.56 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 166.50 | 20-MAY-14:00 | 351.34 | 14-MAY-02:50 |
June | 813.01 | 03-JUN-18:10 | 1453.55 | 01-JUN-09:09 | 14433.56 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 223.10 | 19-JUN-13:53 | 252.18 | 13-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 1453.55 | 01-JUL-16:10 | 14433.56 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 216.46 | 22-JUL-15:53 | 430.35 | 27-JUL-00:40 |
August | 813.01 | 05-AUG-18:10 | 1453.55 | 01-AUG-09:09 | 14433.56 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 170.71 | 13-AUG-15:52 | 491.63 | 19-AUG-02:00 |
September | 813.01 | 02-SEP-18:10 | 1453.55 | 01-SEP-09:09 | 14433.56 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 226.23 | 18-SEP-00:20 | 380.46 | 16-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 1453.55 | 02-OCT-09:09 | 14433.56 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 85.93 | 10-OCT-14:53 | 554.44 | 26-OCT-02:00 |
November | 813.01 | 04-NOV-18:10 | 1453.55 | 01-NOV-09:09 | 14433.56 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 16.08 | 01-NOV-15:53 | 933.89 | 29-NOV-04:00 |
December | 813.01 | 02-DEC-19:10 | 1453.55 | 01-DEC-10:09 | 14433.56 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25-DEC-15:53 | 635.06 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 252.18 | ||||||
Maximum of Months | 813.01 | 1453.55 | 14433.56 | 7874.59 | 0.00 | 0.00 | 0.00 | 226.23 | 933.89 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.72 | 18-JAN-07:30 | 5756.96 | 09-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.36 | 02-FEB-05:35 | 7626.20 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.23 | 19-MAR-07:42 | 8149.54 | 26-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.20 | 30-APR-06:00 | 8225.39 | 27-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1699.29 | 14-MAY-06:32 | 7859.13 | 27-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.55 | 20-JUN-05:53 | 7679.39 | 25-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.42 | 07-JUL-03:51 | 7634.07 | 27-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1727.90 | 25-AUG-06:33 | 7489.85 | 07-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1849.62 | 17-SEP-04:53 | 7119.41 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.23 | 26-OCT-07:13 | 6276.90 | 04-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.79 | 19-NOV-03:00 | 6313.40 | 14-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2125.02 | 21-DEC-07:25 | 5382.91 | 14-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.23 | 5382.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2125.02 | 8225.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 94508.25 | 08-JAN-04:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.47 |
February | 20012.45 | 19-FEB-04:04 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.97 |
March | 103542.81 | 22-MAR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.54 |
April | 120289.42 | 20-APR-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.51 |
May | 121301.29 | 01-MAY-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.51 |
June | 101183.35 | 10-JUN-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.42 |
July | 102919.22 | 02-JUL-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.49 |
August | 102093.76 | 24-AUG-03:01 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.97 |
September | 98786.80 | 29-SEP-03:41 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.40 |
October | 121705.95 | 18-OCT-03:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.00 |
November | 122247.23 | 10-NOV-04:01 | 0.00 | 8067.21 | 12068.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.73 |
December | 25115.21 | 22-DEC-12:55 | 53787.21 | 9680.66 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20012.45 | 0.00 | 7260.49 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122247.23 | 53787.21 | 9680.66 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 265.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 74639.75 | 28-JAN-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 279.79 |
February | 69968.99 | 01-FEB-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 444.48 |
March | 77864.89 | 28-MAR-03:41 | 0.00 | 1938.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 653.83 |
April | 77087.49 | 21-APR-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 198.47 |
May | 68673.31 | 14-MAY-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 223.26 |
June | 59516.74 | 13-JUN-03:21 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 154.61 |
July | 59646.29 | 02-JUL-03:21 | 0.00 | 1938.07 | 28962.71 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 134.65 |
August | 57232.67 | 25-AUG-02:62 | 0.00 | 1453.55 | 13612.11 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 109.02 |
September | 51199.46 | 29-SEP-01:22 | 0.00 | 1211.29 | 13596.18 | 4073.06 | 0.00 | 0.00 | 0.00 | 0.00 | 130.15 |
October | 76175.55 | 25-OCT-03:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 238.35 |
November | 78574.04 | 07-NOV-04:41 | 0.00 | 2180.33 | 32583.05 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 329.24 |
December | 73625.69 | 29-DEC-04:01 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 214.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 51199.46 | 0.00 | 1211.29 | 13596.18 | 3258.45 | 0.00 | 0.00 | 0.00 | 0.00 | 109.02 | |
Maximum of Months | 78574.04 | 0.00 | 2422.59 | 36203.38 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 653.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.90 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.53 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.92 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.21 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 903.39 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.77 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.30 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.87 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.21 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.68 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.79 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.79 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.106878E+12 | 68191.73 | 31-JAN-18:19 | 0.698969E+11 | 70801.78 | 01-JAN-07:49 |
February | 0.903186E+11 | 57396.14 | 18-FEB-11:00 | 0.630476E+11 | 47219.64 | 28-FEB-07:10 |
March | 0.106956E+12 | 69047.88 | 17-MAR-10:00 | 0.692931E+11 | 70218.00 | 26-MAR-05:10 |
April | 0.124581E+12 | 79647.21 | 14-APR-17:10 | 0.627730E+11 | 43170.40 | 01-APR-10:00 |
May | 0.137487E+12 | 83033.87 | 31-MAY-17:19 | 0.630093E+11 | 42807.24 | 06-MAY-10:30 |
June | 0.150443E+12 | 93711.61 | 28-JUN-17:10 | 0.594020E+11 | 42548.27 | 03-JUN-10:09 |
July | 0.158279E+12 | 90974.87 | 19-JUL-11:00 | 0.603344E+11 | 42388.04 | 01-JUL-10:09 |
August | 0.157328E+12 | 91570.35 | 25-AUG-17:10 | 0.607855E+11 | 42429.67 | 27-AUG-10:39 |
September | 0.145556E+12 | 87556.61 | 01-SEP-11:00 | 0.598859E+11 | 42662.23 | 30-SEP-10:09 |
October | 0.123708E+12 | 82504.69 | 02-OCT-10:00 | 0.637782E+11 | 42977.01 | 28-OCT-10:09 |
November | 0.104117E+12 | 71966.82 | 01-NOV-10:00 | 0.648514E+11 | 65119.55 | 23-NOV-06:49 |
December | 0.102711E+12 | 65190.80 | 22-DEC-11:00 | 0.745336E+11 | 78522.85 | 06-DEC-07:10 |
Annual Sum or Average | 0.150836E+13 | 0.771591E+12 | ||||
Minimum of Months | 0.903186E+11 | 57396.14 | 0.594020E+11 | 42388.04 | ||
Maximum of Months | 0.158279E+12 | 93711.61 | 0.745336E+11 | 78522.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.107512E+11 | 0.705177E+10 | 0.391293E+11 | 0.00 | 0.308862E+11 | 37879553.69 | 0.00 | 0.725076E+10 | 0.00 | 0.00 | 0.00 | 0.638558E+10 | 0.00 |
February | 0.973789E+10 | 0.604909E+10 | 0.353426E+11 | 0.00 | 0.278697E+11 | 34213790.43 | 0.00 | 0.654972E+09 | 0.00 | 0.00 | 0.00 | 0.578090E+10 | 0.00 |
March | 0.109224E+11 | 0.621941E+10 | 0.391293E+11 | 0.00 | 0.309710E+11 | 37879553.69 | 0.00 | 0.779134E+10 | 0.00 | 0.00 | 0.00 | 0.645354E+10 | 0.00 |
April | 0.104466E+11 | 0.552989E+10 | 0.378671E+11 | 0.00 | 0.305483E+11 | 36657632.61 | 0.00 | 0.285950E+11 | 0.00 | 0.00 | 0.00 | 0.619381E+10 | 0.00 |
May | 0.108368E+11 | 0.529364E+10 | 0.391293E+11 | 0.00 | 0.316874E+11 | 37879553.69 | 0.00 | 0.385202E+11 | 0.00 | 0.00 | 0.00 | 0.641497E+10 | 0.00 |
June | 0.105574E+11 | 0.494751E+10 | 0.378671E+11 | 0.00 | 0.306319E+11 | 36657632.61 | 0.00 | 0.547516E+11 | 0.00 | 0.00 | 0.00 | 0.623621E+10 | 0.00 |
July | 0.107273E+11 | 0.517826E+10 | 0.391293E+11 | 0.00 | 0.317377E+11 | 37879553.69 | 0.00 | 0.594537E+11 | 0.00 | 0.00 | 0.00 | 0.637173E+10 | 0.00 |
August | 0.109224E+11 | 0.552439E+10 | 0.391293E+11 | 0.00 | 0.317185E+11 | 37879553.69 | 0.00 | 0.578795E+11 | 0.00 | 0.00 | 0.00 | 0.644981E+10 | 0.00 |
September | 0.104491E+11 | 0.580185E+10 | 0.378671E+11 | 0.00 | 0.307141E+11 | 36657632.61 | 0.00 | 0.490100E+11 | 0.00 | 0.00 | 0.00 | 0.619437E+10 | 0.00 |
October | 0.107500E+11 | 0.650510E+10 | 0.391293E+11 | 0.00 | 0.314556E+11 | 37879553.69 | 0.00 | 0.239141E+11 | 0.00 | 0.00 | 0.00 | 0.638007E+10 | 0.00 |
November | 0.104076E+11 | 0.672212E+10 | 0.378671E+11 | 0.00 | 0.300687E+11 | 36657632.61 | 0.00 | 0.757210E+10 | 0.00 | 0.00 | 0.00 | 0.617881E+10 | 0.00 |
December | 0.107286E+11 | 0.718638E+10 | 0.391293E+11 | 0.00 | 0.308476E+11 | 37879553.69 | 0.00 | 0.313378E+10 | 0.00 | 0.00 | 0.00 | 0.638015E+10 | 0.00 |
Annual Sum or Average | 0.127237E+12 | 0.720094E+11 | 0.460716E+12 | 0.00 | 0.369137E+12 | 0.446001E+09 | 0.00 | 0.338527E+12 | 0.00 | 0.00 | 0.00 | 0.754199E+11 | 0.00 |
Minimum of Months | 0.973789E+10 | 0.494751E+10 | 0.353426E+11 | 0.00 | 0.278697E+11 | 34213790.43 | 0.00 | 0.654972E+09 | 0.00 | 0.00 | 0.00 | 0.578090E+10 | 0.00 |
Maximum of Months | 0.109224E+11 | 0.718638E+10 | 0.391293E+11 | 0.00 | 0.317377E+11 | 37879553.69 | 0.00 | 0.594537E+11 | 0.00 | 0.00 | 0.00 | 0.645354E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.182912E+10 | 0.00 | 0.281681E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.172714E+10 | 0.00 | 0.252820E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.240412E+10 | 0.00 | 0.269893E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 38296669.69 | 0.00 | 0.241221E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.141693E+09 | 0.00 | 0.229679E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 60104808.01 | 0.00 | 0.207293E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 25174664.70 | 0.00 | 0.204095E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 12572077.16 | 0.00 | 0.208732E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 27267459.81 | 0.00 | 0.212460E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.112798E+09 | 0.00 | 0.237657E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.128722E+10 | 0.00 | 0.249516E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.724216E+10 | 0.00 | 0.273918E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.149077E+11 | 0.00 | 0.286896E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 12572077.16 | 0.00 | 0.204095E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.724216E+10 | 0.00 | 0.281681E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6293.88 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24699.69 | 01-JAN-11:09 | 0.00 | 13718.70 | 03-JAN-05:10 | 17.86 | 20-JAN-10:00 | 0.00 | 01-JAN-00:10 |
February | 6293.88 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24699.69 | 01-FEB-11:09 | 0.00 | 13718.70 | 01-FEB-05:10 | 17.86 | 23-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 6293.88 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24699.69 | 01-MAR-11:09 | 0.00 | 13718.70 | 01-MAR-05:10 | 17.86 | 07-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 6293.88 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24699.69 | 01-APR-10:09 | 0.00 | 13718.70 | 07-APR-04:10 | 17.86 | 22-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 6293.88 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24699.69 | 01-MAY-10:09 | 0.00 | 13718.70 | 01-MAY-04:10 | 17.86 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 6293.88 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24699.69 | 01-JUN-10:09 | 0.00 | 13718.70 | 01-JUN-10:09 | 17.86 | 16-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 6293.88 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24699.69 | 01-JUL-10:09 | 0.00 | 13718.70 | 01-JUL-18:10 | 17.86 | 07-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 6293.88 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24699.69 | 01-AUG-10:09 | 0.00 | 13718.70 | 01-AUG-07:49 | 17.86 | 02-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 6293.88 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24699.69 | 01-SEP-10:09 | 0.00 | 13718.70 | 01-SEP-07:40 | 17.86 | 13-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 6293.88 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24699.69 | 01-OCT-10:09 | 0.00 | 13718.70 | 08-OCT-04:10 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 6293.88 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24699.69 | 01-NOV-10:09 | 0.00 | 13718.70 | 04-NOV-04:10 | 17.86 | 07-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 6293.88 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24699.69 | 01-DEC-11:09 | 0.00 | 13718.70 | 01-DEC-05:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13718.70 | 17.86 | 0.00 | ||||||
Maximum of Months | 6293.88 | 4578.48 | 24699.69 | 0.00 | 13718.70 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19613.73 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4740.49 | 02-JAN-07:40 | 0.00 |
February | 11085.21 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4741.94 | 27-FEB-07:30 | 0.00 |
March | 21063.45 | 20-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4741.09 | 13-MAR-06:49 | 0.00 |
April | 32746.53 | 14-APR-17:10 | 0.00 | 0.00 | 0.00 | 4739.84 | 27-APR-06:19 | 0.00 |
May | 35988.99 | 31-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4737.64 | 15-MAY-06:19 | 0.00 |
June | 46746.86 | 28-JUN-17:10 | 0.00 | 0.00 | 0.00 | 4736.97 | 27-JUN-06:19 | 0.00 |
July | 44392.35 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.94 | 03-JUL-06:19 | 0.00 |
August | 44911.63 | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.60 | 15-AUG-18:00 | 0.00 |
September | 39321.91 | 01-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4737.16 | 22-SEP-06:19 | 0.00 |
October | 34499.92 | 01-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4741.37 | 13-OCT-06:00 | 0.00 |
November | 24045.98 | 01-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4741.05 | 27-NOV-07:10 | 0.00 |
December | 16622.43 | 22-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4741.49 | 15-DEC-07:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11085.21 | 0.00 | 0.00 | 0.00 | 4736.60 | 0.00 | ||
Maximum of Months | 46746.86 | 0.00 | 0.00 | 0.00 | 4741.94 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68191.73 | 31-JAN-18:19 | 6293.88 | 20676.91 | 4578.48 | 0.00 | 13718.70 | 17.86 | 0.00 | 16452.49 | 0.00 |
February | 57396.14 | 18-FEB-11:00 | 5594.56 | 24699.69 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 6872.62 | 0.00 |
March | 69047.88 | 17-MAR-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 18052.19 | 0.00 |
April | 79647.21 | 14-APR-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 32746.53 | 0.00 |
May | 83033.87 | 31-MAY-17:19 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 35872.80 | 0.00 |
June | 93711.61 | 28-JUN-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 46746.86 | 0.00 |
July | 90974.87 | 19-JUL-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 42737.54 | 0.00 |
August | 91570.35 | 25-AUG-17:10 | 6293.88 | 20676.91 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 44911.63 | 0.00 |
September | 87556.61 | 01-SEP-11:00 | 6293.88 | 23090.58 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 39321.91 | 0.00 |
October | 82504.69 | 02-OCT-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 31382.59 | 0.00 |
November | 71966.82 | 01-NOV-10:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 20693.37 | 0.00 |
December | 65190.80 | 22-DEC-11:00 | 6293.88 | 24699.69 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 14351.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 57396.14 | 5594.56 | 20676.91 | 0.00 | 0.00 | 13718.70 | 17.86 | 0.00 | 6872.62 | 0.00 | |
Maximum of Months | 93711.61 | 6293.88 | 24699.69 | 4578.48 | 0.00 | 13718.70 | 17.86 | 0.00 | 46746.86 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 44701.52 | 01-JAN-06:10 | 0.00 | 21866.20 | 18-JAN-07:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 19961.75 | 09-FEB-05:00 | 0.00 | 21854.43 | 01-FEB-07:40 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 44084.68 | 26-MAR-05:00 | 0.00 | 20272.58 | 01-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 22269.84 | 12-APR-03:49 | 0.00 | 17631.94 | 03-APR-18:49 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 23979.13 | 29-MAY-03:49 | 0.00 | 17252.78 | 01-MAY-18:40 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 9986.35 | 11-JUN-03:49 | 0.00 | 16871.24 | 01-JUN-06:00 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 10176.51 | 03-JUL-03:49 | 0.00 | 16629.07 | 03-JUL-18:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 7663.27 | 25-AUG-03:30 | 0.00 | 16725.09 | 31-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 8996.91 | 16-SEP-03:49 | 0.00 | 17014.22 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 24366.85 | 17-OCT-03:49 | 0.00 | 17437.78 | 31-OCT-18:10 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 38948.38 | 23-NOV-06:00 | 0.00 | 18129.60 | 29-NOV-19:00 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 50171.43 | 06-DEC-06:00 | 0.00 | 21073.60 | 27-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 7663.27 | 0.00 | 16629.07 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 50171.43 | 0.00 | 21866.20 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.79 | 0.00 | 24.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.77 | 0.00 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.12 | 0.00 | 25.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.36 | 0.00 | 25.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.39 | 0.00 | 25.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.11 | 0.00 | 25.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.89 | 0.00 | 24.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.68 | 0.00 | 24.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.33 | 25.08 | 0.00 | 25.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.39 | 0.00 | 25.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.65 | 0.00 | 28.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.29 | 0.00 | 28.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 29.29 | 0.00 | 29.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.61 | 0.17 | 30.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 30.74 | 0.00 | 30.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 30.26 | 3.33 | 29.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 30.82 | 0.00 | 30.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 30.72 | 0.50 | 30.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 30.91 | 0.17 | 30.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 30.65 | 0.00 | 30.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 29.84 | 0.00 | 29.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.99 | 0.00 | 27.99 |
Annual Sum or Average | 0.00 | 0.00 | 227.17 | 30.42 | 4.17 | 30.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.99 | 0.00 | 27.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 30.91 | 3.33 | 30.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.00 | 22.28 | 198.17 | 23.11 | 7.67 | 23.11 |
February | 195.33 | 22.14 | 233.00 | 23.14 | 10.67 | 23.16 |
March | 176.83 | 22.26 | 261.00 | 23.30 | 0.50 | 23.29 |
April | 41.00 | 23.62 | 372.67 | 24.10 | 1.00 | 24.11 |
May | 17.33 | 24.58 | 417.50 | 24.25 | 2.33 | 24.27 |
June | 23.17 | 29.56 | 528.33 | 24.51 | 23.17 | 24.71 |
July | 64.17 | 26.13 | 584.17 | 24.44 | 64.00 | 24.60 |
August | 71.67 | 25.79 | 600.17 | 24.40 | 71.67 | 24.54 |
September | 74.67 | 25.33 | 584.50 | 24.33 | 74.67 | 24.43 |
October | 63.33 | 23.03 | 398.17 | 23.96 | 7.67 | 24.00 |
November | 181.67 | 22.77 | 287.33 | 23.52 | 53.00 | 23.56 |
December | 292.00 | 22.02 | 74.50 | 22.29 | 11.67 | 22.21 |
Annual Sum or Average | 1402.17 | 23.01 | 4539.50 | 23.88 | 328.00 | 23.96 |
Minimum of Months | 17.33 | 22.02 | 74.50 | 22.29 | 0.50 | 22.21 |
Maximum of Months | 292.00 | 29.56 | 600.17 | 24.51 | 74.67 | 24.71 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.00 | 23.34 | 396.00 | 24.37 | 226.17 | 24.68 |
February | 291.50 | 22.09 | 327.33 | 23.45 | 103.67 | 23.77 |
March | 408.17 | 23.81 | 432.00 | 24.64 | 258.83 | 24.92 |
April | 424.00 | 25.86 | 558.00 | 25.84 | 411.00 | 25.89 |
May | 459.83 | 26.00 | 606.67 | 25.96 | 459.67 | 25.97 |
June | 537.33 | 26.01 | 592.00 | 26.01 | 537.33 | 26.01 |
July | 591.83 | 26.00 | 609.00 | 26.00 | 591.83 | 26.00 |
August | 600.83 | 26.01 | 612.00 | 26.01 | 600.83 | 26.01 |
September | 589.67 | 26.00 | 590.00 | 26.00 | 589.67 | 26.00 |
October | 472.50 | 25.43 | 544.50 | 25.59 | 423.67 | 25.71 |
November | 414.50 | 24.11 | 433.67 | 24.78 | 289.17 | 25.03 |
December | 369.17 | 21.60 | 330.83 | 23.03 | 139.67 | 23.21 |
Annual Sum or Average | 5564.33 | 24.95 | 6032.00 | 25.33 | 4631.50 | 25.50 |
Minimum of Months | 291.50 | 21.60 | 327.33 | 23.03 | 103.67 | 23.21 |
Maximum of Months | 600.83 | 26.01 | 612.00 | 26.01 | 600.83 | 26.01 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.42364 | 26.16128 | 0.26060 | 7.84315 |
February | 551.00000 | 23.29700 | 39.92118 | 0.27902 | 8.02094 |
March | 612.00000 | 23.49215 | 30.46953 | 0.28446 | 8.10382 |
April | 590.00000 | 24.07133 | 21.80724 | 0.44816 | 9.64577 |
May | 611.00000 | 24.16076 | 20.68461 | -0.3275 | 7.90200 |
June | 592.00000 | 24.25558 | 28.07915 | -0.1812 | 6.84279 |
July | 609.00000 | 24.24783 | 44.29937 | -0.0700 | 6.31218 |
August | 612.00000 | 24.23461 | 46.40104 | -0.0560 | 6.09907 |
September | 590.00000 | 24.20315 | 46.77599 | -0.0765 | 5.98027 |
October | 610.00000 | 23.93730 | 29.82740 | 0.47412 | 10.66007 |
November | 591.00000 | 23.61078 | 31.10566 | 0.35971 | 9.18429 |
December | 609.00000 | 23.04244 | 19.88818 | 0.11299 | 7.38891 |
Annual Sum or Average | 7187.00000 | 23.83370 | 32.05696 | 0.12418 | 7.82927 |
Minimum of Months | 551.00000 | 23.04244 | 19.88818 | -0.3275 | 5.98027 |
Maximum of Months | 612.00000 | 24.25558 | 46.77599 | 0.47412 | 10.66007 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.77112 | 29.43842 | 0.54390 | 17.86267 |
February | 551.00000 | 22.94593 | 43.54003 | 0.43413 | 14.74843 |
March | 612.00000 | 24.01836 | 33.07739 | 0.62294 | 19.43566 |
April | 590.00000 | 25.63934 | 23.19568 | 0.99209 | 27.24845 |
May | 611.00000 | 25.91354 | 21.64146 | 0.50238 | 11.42364 |
June | 592.00000 | 26.00999 | 27.98162 | 0.64886 | 14.57379 |
July | 609.00000 | 26.00204 | 43.61519 | 0.77535 | 18.34799 |
August | 612.00000 | 26.00504 | 45.45946 | 0.78502 | 18.62328 |
September | 590.00000 | 26.00049 | 45.05623 | 0.77076 | 18.08979 |
October | 610.00000 | 25.23078 | 30.85198 | 0.96388 | 27.99421 |
November | 591.00000 | 24.18553 | 33.04682 | 0.70042 | 21.83660 |
December | 609.00000 | 22.76806 | 23.94912 | 0.27829 | 14.43722 |
Annual Sum or Average | 7187.00000 | 24.88408 | 33.33328 | 0.66890 | 18.73102 |
Minimum of Months | 551.00000 | 22.76806 | 21.64146 | 0.27829 | 11.42364 |
Maximum of Months | 612.00000 | 26.00999 | 45.45946 | 0.99209 | 27.99421 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.151046E+11 | 0.516336E+10 | 242.87 | 0.150298E+11 | 74789145.65 | 0.00 | 1.00 | 08-JAN-04:01 | 0.00 | 01-JAN-00:03 | 101330.28 | 08-JAN-04:01 | 84031.50 | 08-JAN-04:01 | 17298.78 | 08-JAN-04:01 | 28547.34 | 08-JAN-04:01 | 0.00 | 01-JAN-00:03 |
February | 0.135548E+10 | 0.479773E+09 | 52.11 | 0.120219E+10 | 0.153292E+09 | 0.00 | 0.27 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 | 22067.17 | 18-FEB-13:53 | 18140.88 | 18-FEB-13:57 | 10764.28 | 17-FEB-04:06 | 7573.53 | 18-FEB-13:53 | 0.00 | 01-FEB-00:03 |
March | 0.156777E+11 | 0.533210E+10 | 243.65 | 0.153253E+11 | 0.352383E+09 | 0.00 | 1.00 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 | 101330.28 | 17-MAR-03:01 | 82934.80 | 17-MAR-03:01 | 18507.17 | 22-MAR-03:01 | 28547.34 | 17-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.554627E+11 | 0.185860E+11 | 465.60 | 0.553655E+11 | 97198020.15 | 0.00 | 1.00 | 02-APR-03:01 | 0.00 | 01-APR-00:01 | 101330.28 | 15-APR-03:14 | 101330.28 | 06-APR-03:01 | 20319.32 | 17-APR-03:01 | 28547.34 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.721865E+11 | 0.244758E+11 | 535.61 | 0.721769E+11 | 9586464.54 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 101330.28 | 11-MAY-03:01 | 101330.28 | 06-MAY-03:16 | 8082.04 | 11-MAY-03:14 | 28547.34 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.951163E+11 | 0.338557E+11 | 583.01 | 0.945695E+11 | 0.546760E+09 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 101330.28 | 06-JUN-03:52 | 101330.28 | 02-JUN-03:55 | 12051.40 | 17-JUN-17:10 | 30261.59 | 28-JUN-17:07 | 0.00 | 01-JUN-00:01 |
July | 0.109652E+12 | 0.370400E+11 | 610.45 | 0.934473E+11 | 0.162050E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 112447.12 | 14-JUL-03:01 | 101330.28 | 01-JUL-03:01 | 62355.22 | 14-JUL-03:02 | 29475.39 | 19-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.107421E+12 | 0.363223E+11 | 608.68 | 0.910542E+11 | 0.163671E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 108700.41 | 01-AUG-03:01 | 101330.28 | 24-AUG-03:14 | 48379.32 | 07-AUG-03:10 | 29125.66 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.940349E+11 | 0.310141E+11 | 573.79 | 0.781578E+11 | 0.158772E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 111270.35 | 04-SEP-03:01 | 101330.28 | 29-SEP-03:01 | 63684.24 | 04-SEP-03:03 | 29334.57 | 04-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.467644E+11 | 0.156304E+11 | 415.98 | 0.435061E+11 | 0.325835E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 108715.02 | 03-OCT-03:01 | 101330.28 | 14-OCT-03:01 | 51554.84 | 03-OCT-03:02 | 29126.82 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.154038E+11 | 0.520354E+10 | 224.10 | 0.143800E+11 | 0.102381E+10 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 103696.37 | 13-NOV-04:01 | 101330.28 | 10-NOV-04:01 | 59009.70 | 13-NOV-04:01 | 28734.25 | 13-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.658869E+10 | 0.227397E+10 | 134.42 | 0.658095E+10 | 7741866.93 | 0.00 | 0.42 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 | 35957.36 | 22-DEC-14:00 | 35957.36 | 22-DEC-14:00 | 1163.46 | 12-DEC-13:00 | 11886.15 | 22-DEC-14:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.634769E+12 | 0.215377E+12 | 4690.27 | 0.580795E+12 | 0.539731E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.135548E+10 | 0.479773E+09 | 52.11 | 0.120219E+10 | 7741866.93 | 0.00 | 0.27 | 0.00 | 22067.17 | 18140.88 | 1163.46 | 7573.53 | 0.00 | |||||||
Maximum of Months | 0.109652E+12 | 0.370400E+11 | 610.45 | 0.945695E+11 | 0.163671E+11 | 0.00 | 1.00 | 0.00 | 112447.12 | 101330.28 | 63684.24 | 30261.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.625278E+10 | 0.208740E+10 | 211.72 | 0.613726E+10 | 0.115519E+09 | 0.00 | 1.00 | 04-JAN-04:01 | 0.00 | 01-JAN-00:03 | 46458.05 | 06-JAN-04:01 | 44463.46 | 27-JAN-04:41 | 23551.94 | 09-JAN-04:01 | 12824.27 | 04-JAN-04:01 | 0.00 | 01-JAN-00:03 |
February | 0.517229E+09 | 0.175199E+09 | 36.64 | 0.401658E+09 | 0.115571E+09 | 0.00 | 1.00 | 01-FEB-04:01 | 0.00 | 01-FEB-00:03 | 46458.05 | 18-FEB-04:01 | 38641.87 | 10-FEB-04:01 | 26202.19 | 18-FEB-04:01 | 12824.27 | 01-FEB-04:01 | 0.00 | 01-FEB-00:03 |
March | 0.747833E+10 | 0.245925E+10 | 223.80 | 0.712430E+10 | 0.354035E+09 | 0.00 | 1.00 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 | 46458.05 | 11-MAR-04:51 | 38913.04 | 16-MAR-03:11 | 23653.89 | 06-MAR-04:11 | 12824.27 | 01-MAR-04:01 | 0.00 | 01-MAR-00:03 |
April | 0.313333E+11 | 0.100090E+11 | 465.88 | 0.311926E+11 | 0.140664E+09 | 0.00 | 1.00 | 01-APR-03:01 | 0.00 | 01-APR-00:01 | 46458.05 | 06-APR-03:01 | 46458.05 | 03-APR-03:41 | 13488.14 | 17-APR-03:01 | 12824.27 | 01-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.438262E+11 | 0.140444E+11 | 553.23 | 0.437753E+11 | 50855011.22 | 0.00 | 1.00 | 01-MAY-03:01 | 0.00 | 01-MAY-00:01 | 46458.05 | 01-MAY-03:01 | 46458.05 | 02-MAY-03:01 | 10811.56 | 26-MAY-03:01 | 13073.38 | 15-MAY-16:56 | 0.00 | 01-MAY-00:01 |
June | 0.633004E+11 | 0.208959E+11 | 620.02 | 0.630297E+11 | 0.270706E+09 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:01 | 47111.24 | 17-JUN-16:00 | 46458.05 | 14-JUN-03:21 | 6808.64 | 01-JUN-03:01 | 16581.96 | 16-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.723510E+11 | 0.224137E+11 | 650.25 | 0.617567E+11 | 0.105943E+11 | 0.00 | 1.00 | 01-JUL-00:11 | 0.00 | 01-JUL-00:01 | 51413.08 | 14-JUL-03:01 | 46458.05 | 01-JUL-00:42 | 31323.68 | 14-JUL-02:42 | 15104.08 | 12-JUL-13:52 | 0.00 | 01-JUL-00:01 |
August | 0.693005E+11 | 0.215572E+11 | 649.54 | 0.589746E+11 | 0.103258E+11 | 0.00 | 1.00 | 01-AUG-00:12 | 0.00 | 01-AUG-00:01 | 50672.74 | 01-AUG-03:01 | 46458.05 | 25-AUG-02:42 | 25439.97 | 01-AUG-04:02 | 16330.44 | 25-AUG-15:43 | 0.00 | 01-AUG-00:01 |
September | 0.587459E+11 | 0.179959E+11 | 608.23 | 0.483712E+11 | 0.103747E+11 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:01 | 50764.44 | 02-SEP-00:11 | 46458.05 | 18-SEP-01:08 | 31984.15 | 04-SEP-03:43 | 14004.60 | 08-SEP-16:00 | 0.00 | 01-SEP-00:01 |
October | 0.261834E+11 | 0.828365E+10 | 410.37 | 0.239215E+11 | 0.226187E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:01 | 49711.91 | 03-OCT-03:01 | 46458.05 | 14-OCT-03:01 | 27165.48 | 03-OCT-03:01 | 13074.33 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 |
November | 0.723628E+10 | 0.236856E+10 | 203.24 | 0.650394E+10 | 0.732340E+09 | 0.00 | 1.00 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 | 46458.05 | 03-NOV-03:01 | 44470.43 | 29-NOV-04:01 | 29287.81 | 12-NOV-04:01 | 12824.27 | 01-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.255225E+10 | 0.859818E+09 | 118.00 | 0.252780E+10 | 24452233.30 | 0.00 | 1.00 | 01-DEC-04:01 | 0.00 | 01-DEC-00:05 | 46458.05 | 01-DEC-04:01 | 45715.18 | 12-DEC-04:01 | 23040.30 | 13-DEC-04:01 | 12824.27 | 01-DEC-04:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.389078E+12 | 0.123150E+12 | 4750.91 | 0.353717E+12 | 0.353608E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.517229E+09 | 0.175199E+09 | 36.64 | 0.401658E+09 | 24452233.30 | 0.00 | 1.00 | 0.00 | 46458.05 | 38641.87 | 6808.64 | 12824.27 | 0.00 | |||||||
Maximum of Months | 0.723510E+11 | 0.224137E+11 | 650.25 | 0.630297E+11 | 0.105943E+11 | 0.00 | 1.00 | 0.00 | 51413.08 | 46458.05 | 31984.15 | 16581.96 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.11 | 103.78 | 61.33 | 257.14 | 354.72 | 0.00 | 0.00 | 0.00 |
February | 163.35 | 93.82 | 69.53 | 225.91 | 365.45 | 0.00 | 0.00 | 0.00 |
March | 202.52 | 103.80 | 98.71 | 327.72 | 306.77 | 0.00 | 0.00 | 0.00 |
April | 288.23 | 171.12 | 117.10 | 639.15 | 167.33 | 0.00 | 0.00 | 0.00 |
May | 299.38 | 177.07 | 122.30 | 725.38 | 117.29 | 0.00 | 0.00 | 0.00 |
June | 311.61 | 193.08 | 118.52 | 898.62 | 53.68 | 0.00 | 0.00 | 0.00 |
July | 263.72 | 148.38 | 115.34 | 767.52 | 43.19 | 0.00 | 0.00 | 0.00 |
August | 250.31 | 142.53 | 107.78 | 715.96 | 58.17 | 0.00 | 0.00 | 0.00 |
September | 205.39 | 98.72 | 106.67 | 556.30 | 77.40 | 0.00 | 0.00 | 0.00 |
October | 206.13 | 125.14 | 81.00 | 421.63 | 226.82 | 0.00 | 0.00 | 0.00 |
November | 159.21 | 95.58 | 63.63 | 243.99 | 338.09 | 0.00 | 0.00 | 0.00 |
December | 145.92 | 88.48 | 57.44 | 196.33 | 428.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 222.01 | 128.62 | 93.39 | 499.26 | 210.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 145.92 | 88.48 | 57.44 | 196.33 | 43.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 311.61 | 193.08 | 122.30 | 898.62 | 428.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 574.66 | 457.67 | 116.99 | 1151.91 | 484.15 | 0.00 | 0.00 | 0.00 |
February | 362.66 | 243.02 | 119.64 | 626.63 | 494.20 | 0.00 | 0.00 | 0.00 |
March | 306.18 | 157.96 | 148.22 | 564.21 | 443.33 | 0.00 | 0.00 | 0.00 |
April | 275.58 | 120.49 | 155.09 | 677.60 | 258.31 | 0.00 | 0.00 | 0.00 |
May | 183.57 | 38.01 | 145.56 | 506.92 | 183.76 | 0.00 | 0.00 | 0.00 |
June | 153.31 | 15.53 | 137.78 | 597.55 | 83.06 | 0.00 | 0.00 | 0.00 |
July | 155.49 | 18.71 | 136.78 | 578.75 | 64.93 | 0.00 | 0.00 | 0.00 |
August | 195.26 | 60.99 | 134.26 | 672.38 | 85.08 | 0.00 | 0.00 | 0.00 |
September | 272.36 | 119.08 | 153.28 | 784.89 | 112.84 | 0.00 | 0.00 | 0.00 |
October | 428.62 | 297.48 | 131.14 | 947.56 | 316.01 | 0.00 | 0.00 | 0.00 |
November | 496.35 | 380.16 | 116.19 | 971.26 | 454.88 | 0.00 | 0.00 | 0.00 |
December | 534.03 | 421.49 | 112.54 | 1017.01 | 573.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 328.20 | 194.20 | 134.00 | 759.14 | 295.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.31 | 15.53 | 112.54 | 506.92 | 64.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 574.66 | 457.67 | 155.09 | 1151.91 | 573.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 173.15 | 107.95 | 65.20 | 313.51 | 390.72 | 0.00 | 0.00 | 0.00 |
February | 140.06 | 67.95 | 72.10 | 193.21 | 388.22 | 0.00 | 0.00 | 0.00 |
March | 184.77 | 88.05 | 96.72 | 306.59 | 327.82 | 0.00 | 0.00 | 0.00 |
April | 282.59 | 160.72 | 121.87 | 642.42 | 186.80 | 0.00 | 0.00 | 0.00 |
May | 283.95 | 158.69 | 125.26 | 699.86 | 133.05 | 0.00 | 0.00 | 0.00 |
June | 300.86 | 176.43 | 124.44 | 868.13 | 59.72 | 0.00 | 0.00 | 0.00 |
July | 219.36 | 102.02 | 117.33 | 656.96 | 46.38 | 0.00 | 0.00 | 0.00 |
August | 209.75 | 105.19 | 104.56 | 621.31 | 60.66 | 0.00 | 0.00 | 0.00 |
September | 182.73 | 76.66 | 106.07 | 508.75 | 82.03 | 0.00 | 0.00 | 0.00 |
October | 187.71 | 107.50 | 80.21 | 397.66 | 246.25 | 0.00 | 0.00 | 0.00 |
November | 172.11 | 103.84 | 68.27 | 304.09 | 364.37 | 0.00 | 0.00 | 0.00 |
December | 138.80 | 79.00 | 59.80 | 217.89 | 465.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.56 | 111.32 | 95.23 | 478.74 | 228.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.80 | 67.95 | 59.80 | 193.21 | 46.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.86 | 176.43 | 125.26 | 868.13 | 465.76 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442226E+09 | 0.277955E+09 | 0.164272E+09 | 0.688724E+09 | 0.950094E+09 |
February | 0.395172E+09 | 0.226967E+09 | 0.168205E+09 | 0.546514E+09 | 0.884109E+09 |
March | 0.542426E+09 | 0.278030E+09 | 0.264396E+09 | 0.877764E+09 | 0.821644E+09 |
April | 0.747087E+09 | 0.443554E+09 | 0.303533E+09 | 0.165669E+10 | 0.433718E+09 |
May | 0.801856E+09 | 0.474276E+09 | 0.327580E+09 | 0.194285E+10 | 0.314141E+09 |
June | 0.807683E+09 | 0.500474E+09 | 0.307209E+09 | 0.232921E+10 | 0.139143E+09 |
July | 0.706360E+09 | 0.397421E+09 | 0.308939E+09 | 0.205572E+10 | 0.115676E+09 |
August | 0.670435E+09 | 0.381745E+09 | 0.288689E+09 | 0.191762E+10 | 0.155809E+09 |
September | 0.532368E+09 | 0.255886E+09 | 0.276482E+09 | 0.144194E+10 | 0.200630E+09 |
October | 0.552102E+09 | 0.335163E+09 | 0.216938E+09 | 0.112930E+10 | 0.607506E+09 |
November | 0.412683E+09 | 0.247754E+09 | 0.164930E+09 | 0.632430E+09 | 0.876338E+09 |
December | 0.390827E+09 | 0.236975E+09 | 0.153852E+09 | 0.525846E+09 | 0.114635E+10 |
Annual Sum or Average | 0.700122E+10 | 0.405620E+10 | 0.294502E+10 | 0.157446E+11 | 0.664515E+10 |
Minimum of Months | 0.390827E+09 | 0.226967E+09 | 0.153852E+09 | 0.525846E+09 | 0.115676E+09 |
Maximum of Months | 0.807683E+09 | 0.500474E+09 | 0.327580E+09 | 0.232921E+10 | 0.114635E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153917E+10 | 0.122582E+10 | 0.313356E+09 | 0.308528E+10 | 0.129674E+10 |
February | 0.877351E+09 | 0.587921E+09 | 0.289430E+09 | 0.151594E+10 | 0.119556E+10 |
March | 0.820077E+09 | 0.423076E+09 | 0.397001E+09 | 0.151118E+10 | 0.118741E+10 |
April | 0.714307E+09 | 0.312310E+09 | 0.401997E+09 | 0.175635E+10 | 0.669529E+09 |
May | 0.491686E+09 | 0.101806E+09 | 0.389880E+09 | 0.135775E+10 | 0.492171E+09 |
June | 0.397378E+09 | 40251097.26 | 0.357127E+09 | 0.154885E+10 | 0.215297E+09 |
July | 0.416454E+09 | 50109079.80 | 0.366344E+09 | 0.155012E+10 | 0.173918E+09 |
August | 0.522978E+09 | 0.163366E+09 | 0.359612E+09 | 0.180090E+10 | 0.227873E+09 |
September | 0.705956E+09 | 0.308658E+09 | 0.397298E+09 | 0.203443E+10 | 0.292480E+09 |
October | 0.114801E+10 | 0.796769E+09 | 0.351246E+09 | 0.253795E+10 | 0.846403E+09 |
November | 0.128654E+10 | 0.985367E+09 | 0.301172E+09 | 0.251751E+10 | 0.117906E+10 |
December | 0.143035E+10 | 0.112893E+10 | 0.301422E+09 | 0.272396E+10 | 0.153504E+10 |
Annual Sum or Average | 0.103503E+11 | 0.612438E+10 | 0.422589E+10 | 0.239402E+11 | 0.931148E+10 |
Minimum of Months | 0.397378E+09 | 40251097.26 | 0.289430E+09 | 0.135775E+10 | 0.173918E+09 |
Maximum of Months | 0.153917E+10 | 0.122582E+10 | 0.401997E+09 | 0.308528E+10 | 0.153504E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.463765E+09 | 0.289132E+09 | 0.174634E+09 | 0.839701E+09 | 0.104651E+10 |
February | 0.338831E+09 | 0.164396E+09 | 0.174435E+09 | 0.467422E+09 | 0.939170E+09 |
March | 0.494882E+09 | 0.235828E+09 | 0.259054E+09 | 0.821175E+09 | 0.878039E+09 |
April | 0.732467E+09 | 0.416586E+09 | 0.315881E+09 | 0.166516E+10 | 0.484187E+09 |
May | 0.760536E+09 | 0.425044E+09 | 0.335492E+09 | 0.187450E+10 | 0.356349E+09 |
June | 0.779838E+09 | 0.457297E+09 | 0.322541E+09 | 0.225018E+10 | 0.154792E+09 |
July | 0.587522E+09 | 0.273258E+09 | 0.314263E+09 | 0.175961E+10 | 0.124225E+09 |
August | 0.561804E+09 | 0.281742E+09 | 0.280062E+09 | 0.166413E+10 | 0.162484E+09 |
September | 0.473636E+09 | 0.198694E+09 | 0.274942E+09 | 0.131868E+10 | 0.212609E+09 |
October | 0.502757E+09 | 0.287935E+09 | 0.214822E+09 | 0.106508E+10 | 0.659566E+09 |
November | 0.446118E+09 | 0.269165E+09 | 0.176953E+09 | 0.788213E+09 | 0.944450E+09 |
December | 0.371775E+09 | 0.211595E+09 | 0.160180E+09 | 0.583587E+09 | 0.124748E+10 |
Annual Sum or Average | 0.651393E+10 | 0.351067E+10 | 0.300326E+10 | 0.150975E+11 | 0.720986E+10 |
Minimum of Months | 0.338831E+09 | 0.164396E+09 | 0.160180E+09 | 0.467422E+09 | 0.124225E+09 |
Maximum of Months | 0.779838E+09 | 0.457297E+09 | 0.335492E+09 | 0.225018E+10 | 0.124748E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1676.80 | 1183.83 | 912.92 | 669.39 | 243.53 | 0.00 | 0.00 |
February | 994.83 | 1196.95 | 666.07 | 404.80 | 261.27 | 0.00 | 0.00 |
March | 1149.49 | 1028.88 | 693.47 | 349.81 | 343.66 | 0.00 | 0.00 |
April | 1916.65 | 569.90 | 846.40 | 452.33 | 394.06 | 0.00 | 0.00 |
May | 1903.96 | 405.88 | 766.91 | 373.78 | 393.13 | 0.00 | 0.00 |
June | 2351.56 | 183.73 | 765.78 | 385.04 | 380.74 | 0.00 | 0.00 |
July | 1996.62 | 147.89 | 638.57 | 269.11 | 369.45 | 0.00 | 0.00 |
August | 2002.85 | 197.11 | 655.32 | 308.71 | 346.61 | 0.00 | 0.00 |
September | 1841.65 | 263.97 | 660.48 | 294.46 | 366.02 | 0.00 | 0.00 |
October | 1735.97 | 758.21 | 822.46 | 530.12 | 292.34 | 0.00 | 0.00 |
November | 1471.99 | 1109.99 | 827.68 | 579.59 | 248.09 | 0.00 | 0.00 |
December | 1369.29 | 1404.94 | 818.75 | 588.97 | 229.78 | 0.00 | 0.00 |
Annual Sum or Average | 1704.64 | 702.11 | 756.77 | 434.15 | 322.62 | 0.00 | 0.00 |
Minimum of Months | 994.83 | 147.89 | 638.57 | 269.11 | 229.78 | 0.00 | 0.00 |
Maximum of Months | 2351.56 | 1404.94 | 912.92 | 669.39 | 394.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449113E+10 | 0.317076E+10 | 0.244516E+10 | 0.179290E+10 | 0.652262E+09 | 0.00 | 0.00 |
February | 0.240669E+10 | 0.289565E+10 | 0.161135E+10 | 0.979284E+09 | 0.632069E+09 | 0.00 | 0.00 |
March | 0.307878E+10 | 0.275575E+10 | 0.185738E+10 | 0.936934E+09 | 0.920451E+09 | 0.00 | 0.00 |
April | 0.496796E+10 | 0.147719E+10 | 0.219386E+10 | 0.117245E+10 | 0.102141E+10 | 0.00 | 0.00 |
May | 0.509956E+10 | 0.108712E+10 | 0.205408E+10 | 0.100113E+10 | 0.105295E+10 | 0.00 | 0.00 |
June | 0.609523E+10 | 0.476221E+09 | 0.198490E+10 | 0.998022E+09 | 0.986877E+09 | 0.00 | 0.00 |
July | 0.534775E+10 | 0.396122E+09 | 0.171033E+10 | 0.720789E+09 | 0.989546E+09 | 0.00 | 0.00 |
August | 0.536443E+10 | 0.527938E+09 | 0.175522E+10 | 0.826854E+09 | 0.928363E+09 | 0.00 | 0.00 |
September | 0.477355E+10 | 0.684214E+09 | 0.171196E+10 | 0.763238E+09 | 0.948723E+09 | 0.00 | 0.00 |
October | 0.464963E+10 | 0.203078E+10 | 0.220287E+10 | 0.141987E+10 | 0.783007E+09 | 0.00 | 0.00 |
November | 0.381539E+10 | 0.287708E+10 | 0.214534E+10 | 0.150229E+10 | 0.643055E+09 | 0.00 | 0.00 |
December | 0.366752E+10 | 0.376299E+10 | 0.219295E+10 | 0.157750E+10 | 0.615454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.537576E+11 | 0.221418E+11 | 0.238654E+11 | 0.136912E+11 | 0.101742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.240669E+10 | 0.396122E+09 | 0.161135E+10 | 0.720789E+09 | 0.615454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.609523E+10 | 0.376299E+10 | 0.244516E+10 | 0.179290E+10 | 0.105295E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638544E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160269711.9 | 81.22 | 0.00 | 0.00 |
February | 0.578085E+10 | -0.563429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146554915.1 | 81.22 | 0.00 | 0.00 |
March | 0.645338E+10 | -0.629386E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159513044.2 | 81.21 | 0.00 | 0.00 |
April | 0.619368E+10 | -0.604348E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150203167.4 | 81.21 | 0.00 | 0.00 |
May | 0.641475E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154558466.2 | 81.21 | 0.00 | 0.00 |
June | 0.623608E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149502286.2 | 81.21 | 0.00 | 0.00 |
July | 0.637151E+10 | -0.621712E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154392535.6 | 81.21 | 0.00 | 0.00 |
August | 0.644960E+10 | -0.629524E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154364247.6 | 81.21 | 0.00 | 0.00 |
September | 0.619417E+10 | -0.604485E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149319928.1 | 81.21 | 0.00 | 0.00 |
October | 0.638005E+10 | -0.622384E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156207069.6 | 81.21 | 0.00 | 0.00 |
November | 0.617852E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153913501.3 | 81.22 | 0.00 | 0.00 |
December | 0.638005E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162952631.6 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754181E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.185175E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578085E+10 | -0.629524E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162952631.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645338E+10 | -0.563429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146554915.1 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.205333E+11 | -0.196400E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -893324890.6 | 58.99 | 0.00 | 0.00 |
February | 0.184180E+11 | -0.175945E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -823482978.4 | 58.99 | 0.00 | 0.00 |
March | 0.195875E+11 | -0.187011E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -886404346.0 | 58.98 | 0.00 | 0.00 |
April | 0.173430E+11 | -0.165231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -819838369.2 | 58.99 | 0.00 | 0.00 |
May | 0.163467E+11 | -0.155055E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -841169532.9 | 58.99 | 0.00 | 0.00 |
June | 0.146101E+11 | -0.137968E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -813325374.1 | 58.98 | 0.00 | 0.00 |
July | 0.142904E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839503488.2 | 58.98 | 0.00 | 0.00 |
August | 0.146581E+11 | -0.138187E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839408661.2 | 58.99 | 0.00 | 0.00 |
September | 0.150310E+11 | -0.142192E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -811817648.7 | 58.99 | 0.00 | 0.00 |
October | 0.169860E+11 | -0.161298E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -856276362.3 | 58.99 | 0.00 | 0.00 |
November | 0.180146E+11 | -0.171609E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -853705148.5 | 58.99 | 0.00 | 0.00 |
December | 0.199071E+11 | -0.189892E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -917979997.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.205726E+12 | -0.195530E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.101962E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.142904E+11 | -0.196400E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -917979997.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.205333E+11 | -0.134509E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -811817648.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.635393E+09 | 21685.17 | 01-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.568627E+09 | 10147.20 | 28-FEB-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940619E+09 | 26052.56 | 26-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30637335.75 | 53447.61 | 12-APR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113354E+09 | 57549.92 | 29-MAY-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48083846.41 | 39945.41 | 11-JUN-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20139731.76 | 40706.05 | 03-JUL-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10057661.73 | 30653.09 | 25-AUG-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21813967.85 | 32341.85 | 29-SEP-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49196110.04 | 58480.44 | 17-OCT-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.425701E+09 | 41279.07 | 10-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246228E+10 | 26047.46 | 07-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.532591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10057661.73 | 10147.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246228E+10 | 58480.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.827904E+09 | 22643.43 | 01-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.813085E+09 | 13679.69 | 25-FEB-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.982679E+09 | 23501.20 | 27-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41042226.46 | 7708.72 | 26-OCT-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.604072E+09 | 23365.62 | 23-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333145E+10 | 24088.96 | 14-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333145E+10 | 24088.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151046E+11 | 0.150298E+11 | 101330.28 | 08-JAN-04:01 | 84031.50 | 0.00 |
February | 0.00 | 0.00 | 0.135548E+10 | 0.120219E+10 | 22067.17 | 18-FEB-13:53 | 18140.36 | 0.00 |
March | 0.00 | 0.00 | 0.156777E+11 | 0.153253E+11 | 101330.28 | 17-MAR-03:01 | 82934.80 | 0.00 |
April | 0.00 | 0.00 | 0.554627E+11 | 0.553655E+11 | 101330.28 | 15-APR-03:14 | 101330.28 | 0.00 |
May | 0.00 | 0.00 | 0.721865E+11 | 0.721769E+11 | 101330.28 | 11-MAY-03:01 | 94925.70 | 0.00 |
June | 0.00 | 0.00 | 0.951163E+11 | 0.945695E+11 | 101330.28 | 06-JUN-03:52 | 101330.28 | 0.00 |
July | 0.00 | 0.00 | 0.109652E+12 | 0.934473E+11 | 112447.12 | 14-JUL-03:01 | 50476.72 | 0.00 |
August | 0.00 | 0.00 | 0.107421E+12 | 0.910542E+11 | 108700.41 | 01-AUG-03:01 | 70566.05 | 0.00 |
September | 0.00 | 0.00 | 0.940349E+11 | 0.781578E+11 | 111270.35 | 04-SEP-03:01 | 47927.19 | 0.00 |
October | 0.00 | 0.00 | 0.467644E+11 | 0.435061E+11 | 108715.02 | 03-OCT-03:01 | 57961.06 | 0.00 |
November | 0.00 | 0.00 | 0.154038E+11 | 0.143800E+11 | 103696.37 | 13-NOV-04:01 | 44686.66 | 0.00 |
December | 0.00 | 0.00 | 0.658869E+10 | 0.658095E+10 | 35957.36 | 22-DEC-14:00 | 35957.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.634769E+12 | 0.580795E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.135548E+10 | 0.120219E+10 | 22067.17 | 18140.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109652E+12 | 0.945695E+11 | 112447.12 | 101330.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.625278E+10 | 0.613726E+10 | 46458.05 | 06-JAN-04:01 | 37073.19 | 0.00 |
February | 0.00 | 0.00 | 0.517229E+09 | 0.401658E+09 | 46458.05 | 18-FEB-04:01 | 20255.86 | 0.00 |
March | 0.00 | 0.00 | 0.747833E+10 | 0.712430E+10 | 46458.05 | 11-MAR-04:51 | 36853.34 | 0.00 |
April | 0.00 | 0.00 | 0.313333E+11 | 0.311926E+11 | 46458.05 | 06-APR-03:01 | 45059.34 | 0.00 |
May | 0.00 | 0.00 | 0.438262E+11 | 0.437753E+11 | 46458.05 | 01-MAY-03:01 | 45080.87 | 0.00 |
June | 0.00 | 0.00 | 0.633004E+11 | 0.630297E+11 | 47111.24 | 17-JUN-16:00 | 46042.74 | 0.00 |
July | 0.00 | 0.00 | 0.723510E+11 | 0.617567E+11 | 51413.08 | 14-JUL-03:01 | 20369.05 | 0.00 |
August | 0.00 | 0.00 | 0.693005E+11 | 0.589746E+11 | 50672.74 | 01-AUG-03:01 | 26391.94 | 0.00 |
September | 0.00 | 0.00 | 0.587459E+11 | 0.483712E+11 | 50764.44 | 02-SEP-00:11 | 29180.58 | 0.00 |
October | 0.00 | 0.00 | 0.261834E+11 | 0.239215E+11 | 49711.91 | 03-OCT-03:01 | 22546.43 | 0.00 |
November | 0.00 | 0.00 | 0.723628E+10 | 0.650394E+10 | 46458.05 | 03-NOV-03:01 | 27080.58 | 0.00 |
December | 0.00 | 0.00 | 0.255225E+10 | 0.252780E+10 | 46458.05 | 01-DEC-04:01 | 35679.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.389078E+12 | 0.353717E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.517229E+09 | 0.401658E+09 | 46458.05 | 20255.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.723510E+11 | 0.630297E+11 | 51413.08 | 46042.74 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 7794.97 | 14844.03 | 24-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7735.52 | 14791.60 | 01-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7444.85 | 14377.86 | 02-MAR-19:27 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6838.88 | 13424.56 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6254.48 | 12364.77 | 01-MAY-18:43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5789.93 | 11248.97 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5490.03 | 10493.03 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5626.58 | 10815.95 | 31-AUG-18:46 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5952.92 | 11668.31 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6487.73 | 12874.29 | 31-OCT-18:06 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 7084.43 | 13917.97 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 7552.66 | 14624.45 | 29-DEC-19:57 |
Annual Sum or Average | 0.00 | 6665.12 | ||||
Minimum of Months | 0.00 | 0.00 | 5490.03 | 10493.03 | ||
Maximum of Months | 0.00 | 0.00 | 7794.97 | 14844.03 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.514275E+10 | 0.61 | 2203.40 | 01-JAN-00:03 | 0.70 |
February | 0.462715E+10 | 0.61 | 2203.40 | 01-FEB-00:03 | 0.71 |
March | 0.521876E+10 | 0.62 | 2203.40 | 01-MAR-00:03 | 0.70 |
April | 0.540520E+10 | 0.66 | 2203.40 | 01-APR-03:01 | 0.70 |
May | 0.562778E+10 | 0.67 | 2203.40 | 01-MAY-00:19 | 0.70 |
June | 0.544120E+10 | 0.67 | 2203.40 | 01-JUN-00:10 | 0.70 |
July | 0.562476E+10 | 0.66 | 2203.40 | 01-JUL-00:08 | 0.70 |
August | 0.562437E+10 | 0.66 | 2203.40 | 01-AUG-00:08 | 0.70 |
September | 0.544206E+10 | 0.66 | 2203.40 | 01-SEP-00:09 | 0.70 |
October | 0.551508E+10 | 0.65 | 2203.40 | 01-OCT-00:09 | 0.70 |
November | 0.510999E+10 | 0.63 | 2203.40 | 01-NOV-00:55 | 0.70 |
December | 0.512093E+10 | 0.61 | 2203.40 | 01-DEC-00:05 | 0.70 |
Annual Sum or Average | 0.639000E+11 | 0.64 | |||
Minimum of Months | 0.462715E+10 | 0.61 | 2203.40 | 0.70 | |
Maximum of Months | 0.562778E+10 | 0.67 | 2203.40 | 0.71 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210765E+11 | 1.42 | 9439.70 | 01-JAN-05:20 | 1.70 |
February | 0.190311E+11 | 1.41 | 9439.70 | 07-FEB-06:20 | 1.69 |
March | 0.210811E+11 | 1.42 | 9439.70 | 02-MAR-11:43 | 1.69 |
April | 0.205438E+11 | 1.45 | 9439.70 | 01-APR-08:43 | 1.70 |
May | 0.212704E+11 | 1.45 | 9439.70 | 02-MAY-06:43 | 1.70 |
June | 0.205338E+11 | 1.44 | 9439.70 | 03-JUN-10:33 | 1.69 |
July | 0.212692E+11 | 1.45 | 9439.70 | 01-JUL-20:57 | 1.70 |
August | 0.212535E+11 | 1.44 | 9439.70 | 02-AUG-07:23 | 1.68 |
September | 0.205855E+11 | 1.43 | 9439.70 | 01-SEP-08:62 | 1.67 |
October | 0.211885E+11 | 1.45 | 9439.70 | 02-OCT-09:20 | 1.68 |
November | 0.204218E+11 | 1.43 | 9439.70 | 01-NOV-06:40 | 1.68 |
December | 0.210700E+11 | 1.42 | 9439.70 | 01-DEC-11:07 | 1.70 |
Annual Sum or Average | 0.249325E+12 | 1.43 | |||
Minimum of Months | 0.190311E+11 | 1.41 | 9439.70 | 1.67 | |
Maximum of Months | 0.212704E+11 | 1.45 | 9439.70 | 1.70 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.466698E+10 | 0.86 | 2075.60 | 01-JAN-00:13 | 0.99 |
February | 0.421146E+10 | 0.85 | 2075.60 | 01-FEB-05:20 | 0.99 |
March | 0.467120E+10 | 0.87 | 2075.60 | 01-MAR-16:05 | 0.98 |
April | 0.459929E+10 | 0.92 | 2075.60 | 01-APR-08:05 | 0.99 |
May | 0.478915E+10 | 0.93 | 2075.60 | 01-MAY-08:07 | 0.99 |
June | 0.465694E+10 | 0.90 | 2075.60 | 01-JUN-06:05 | 0.99 |
July | 0.484376E+10 | 0.90 | 2075.60 | 01-JUL-06:27 | 0.99 |
August | 0.484062E+10 | 0.90 | 2075.60 | 01-AUG-04:06 | 0.97 |
September | 0.468657E+10 | 0.91 | 2075.60 | 01-SEP-04:08 | 0.97 |
October | 0.475204E+10 | 0.91 | 2075.60 | 01-OCT-07:00 | 0.98 |
November | 0.453687E+10 | 0.88 | 2075.60 | 01-NOV-06:50 | 0.98 |
December | 0.465660E+10 | 0.86 | 2075.60 | 01-DEC-11:03 | 0.99 |
Annual Sum or Average | 0.559115E+11 | 0.89 | |||
Minimum of Months | 0.421146E+10 | 0.85 | 2075.60 | 0.97 | |
Maximum of Months | 0.484376E+10 | 0.93 | 2075.60 | 0.99 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:03 | 5.36 | 5.36 | 49.72 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.51 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 50.73 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.85 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.75 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 54.14 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 55.21 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.39 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.67 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.62 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.88 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 50.87 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 49.72 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.21 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 49.72 | 59.80 | 7794.97 | 14844.03 | 24-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.51 | 59.65 | 7735.52 | 14791.60 | 01-FEB-19:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.73 | 59.42 | 7444.85 | 14377.86 | 02-MAR-19:27 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.60 | 51.60 | 6838.88 | 13424.56 | 03-APR-18:42 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 52.46 | 52.46 | 6254.48 | 12364.77 | 01-MAY-18:43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.04 | 53.04 | 5789.93 | 11248.97 | 01-JUN-06:58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.80 | 53.80 | 5490.03 | 10493.03 | 03-JUL-06:53 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.99 | 52.99 | 5626.58 | 10815.95 | 31-AUG-18:46 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.54 | 53.54 | 5952.92 | 11668.31 | 29-SEP-18:23 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.19 | 51.19 | 6487.73 | 12874.29 | 31-OCT-18:06 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.27 | 52.27 | 7084.43 | 13917.97 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.87 | 58.51 | 7552.66 | 14624.45 | 29-DEC-19:57 |
Annual Sum or Average | 0.00 | 6665.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.72 | 51.19 | 5490.03 | 10493.03 | ||
Maximum of Months | 0.00 | 0.00 | 53.80 | 59.80 | 7794.97 | 14844.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.262398E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.195109E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.264132E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.391298E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.457462E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.543894E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.583091E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.575757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.515995E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.368190E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256254E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.233440E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.464702E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.195109E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.583091E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.675438E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.438666E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.713045E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146083E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188336E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.255529E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272575E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.263978E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.226825E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130357E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.690544E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.551641E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179062E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.272575E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.210765E+11 | 0.151046E+11 | 0.635393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190311E+11 | 0.135548E+10 | 0.568627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210811E+11 | 0.156777E+11 | 0.940619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205438E+11 | 0.554627E+11 | 30637335.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212704E+11 | 0.721865E+11 | 0.113354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205338E+11 | 0.951163E+11 | 48083846.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.212692E+11 | 0.109652E+12 | 20139731.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212535E+11 | 0.107421E+12 | 10057661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205855E+11 | 0.940349E+11 | 21813967.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211885E+11 | 0.467644E+11 | 49196110.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204218E+11 | 0.154038E+11 | 0.425701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210700E+11 | 0.658869E+10 | 0.246228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249325E+12 | 0.634769E+12 | 0.532591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190311E+11 | 0.135548E+10 | 10057661.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212704E+11 | 0.109652E+12 | 0.246228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.466698E+10 | 0.625278E+10 | 0.827904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421146E+10 | 0.517229E+09 | 0.813085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467120E+10 | 0.747833E+10 | 0.982679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459929E+10 | 0.313333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478915E+10 | 0.438262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465694E+10 | 0.633004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.484376E+10 | 0.723510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.484062E+10 | 0.693005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468657E+10 | 0.587459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475204E+10 | 0.261834E+11 | 41042226.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453687E+10 | 0.723628E+10 | 0.604072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.465660E+10 | 0.255225E+10 | 0.333145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559115E+11 | 0.389078E+12 | 0.660023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421146E+10 | 0.517229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.484376E+10 | 0.723510E+11 | 0.333145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.210765E+11 | 0.00 | 0.00 | 0.00 | 0.516336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190311E+11 | 0.00 | 0.00 | 0.00 | 0.479773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210811E+11 | 0.00 | 0.00 | 0.00 | 0.533210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205438E+11 | 0.00 | 0.00 | 0.00 | 0.185860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.212704E+11 | 0.00 | 0.00 | 0.00 | 0.244758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205338E+11 | 0.00 | 0.00 | 0.00 | 0.338557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.212692E+11 | 0.00 | 0.00 | 0.00 | 0.370400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212535E+11 | 0.00 | 0.00 | 0.00 | 0.363223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.205855E+11 | 0.00 | 0.00 | 0.00 | 0.310141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211885E+11 | 0.00 | 0.00 | 0.00 | 0.156304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204218E+11 | 0.00 | 0.00 | 0.00 | 0.520354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210700E+11 | 0.00 | 0.00 | 0.00 | 0.227397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249325E+12 | 0.00 | 0.00 | 0.00 | 0.215377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190311E+11 | 0.00 | 0.00 | 0.00 | 0.479773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212704E+11 | 0.00 | 0.00 | 0.00 | 0.370400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.466698E+10 | 0.00 | 0.00 | 0.00 | 0.208740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421146E+10 | 0.00 | 0.00 | 0.00 | 0.175199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467120E+10 | 0.00 | 0.00 | 0.00 | 0.245925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459929E+10 | 0.00 | 0.00 | 0.00 | 0.100090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478915E+10 | 0.00 | 0.00 | 0.00 | 0.140444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465694E+10 | 0.00 | 0.00 | 0.00 | 0.208959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.484376E+10 | 0.00 | 0.00 | 0.00 | 0.224137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.484062E+10 | 0.00 | 0.00 | 0.00 | 0.215572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468657E+10 | 0.00 | 0.00 | 0.00 | 0.179959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475204E+10 | 0.00 | 0.00 | 0.00 | 0.828365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.453687E+10 | 0.00 | 0.00 | 0.00 | 0.236856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.465660E+10 | 0.00 | 0.00 | 0.00 | 0.859818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559115E+11 | 0.00 | 0.00 | 0.00 | 0.123150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421146E+10 | 0.00 | 0.00 | 0.00 | 0.175199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.484376E+10 | 0.00 | 0.00 | 0.00 | 0.224137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130679E+11 | 13876350.65 | 0.00 | 0.111913E+09 | 0.00 | 3730470.12 | 0.347441E+11 | 0.00 | 6.05 |
February | 0.141557E+11 | 0.00 | 0.00 | 62172214.67 | 0.00 | 0.00 | 0.358285E+11 | 0.00 | 5.16 |
March | 0.122606E+11 | 50865243.41 | 0.00 | 0.105642E+09 | 0.00 | 2285870.26 | 0.339263E+11 | 0.00 | 6.01 |
April | 0.184871E+10 | 0.251096E+10 | 494192.64 | 0.132772E+09 | 1568111.26 | 4736221.37 | 0.162376E+11 | 44439.69 | 5.17 |
May | 0.843782E+09 | 0.562551E+10 | 229333.57 | 91954197.31 | 2745222.08 | 7808606.92 | 0.931372E+10 | 77120.52 | 4.66 |
June | 0.385978E+09 | 0.159821E+11 | 1787790.86 | 25815711.02 | 59497547.43 | 1864076.20 | 0.236424E+10 | 247931.31 | 4.23 |
July | 0.227392E+09 | 0.252620E+11 | 742524.85 | 10282243.15 | 0.193678E+09 | 1282102.85 | 0.102473E+10 | 31004.49 | 4.03 |
August | 0.299003E+09 | 0.232568E+11 | 429629.71 | 13264674.43 | 0.150500E+09 | 145215.95 | 0.145852E+10 | 70372.77 | 4.34 |
September | 0.513355E+09 | 0.168372E+11 | 1649571.51 | 20590626.57 | 0.106722E+09 | 497686.34 | 0.297129E+10 | 93640.55 | 4.74 |
October | 0.443069E+10 | 0.380199E+10 | 249744.72 | 0.110014E+09 | 16489181.35 | 2256781.48 | 0.249820E+11 | 11112.41 | 5.95 |
November | 0.973436E+10 | 74120000.40 | 2337018.94 | 0.107577E+09 | 1060901.06 | 3007767.30 | 0.373025E+11 | 62076.92 | 6.18 |
December | 0.208616E+11 | 0.00 | 0.00 | 83432635.05 | 0.00 | 5885883.41 | 0.336826E+11 | 0.00 | 5.42 |
Annual Sum or Average | 0.786291E+11 | 0.934155E+11 | 7919806.79 | 0.875430E+09 | 0.532261E+09 | 33500682.19 | 0.233836E+12 | 637698.65 | 5.16 |
Minimum of Months | 0.227392E+09 | 0.00 | 0.00 | 10282243.15 | 0.00 | 0.00 | 0.102473E+10 | 0.00 | 4.03 |
Maximum of Months | 0.208616E+11 | 0.252620E+11 | 2337018.94 | 0.132772E+09 | 0.193678E+09 | 7808606.92 | 0.373025E+11 | 247931.31 | 6.18 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172072E+11 | 0.00 | 0.00 | 88499806.13 | 0.00 | 0.00 | 0.317183E+11 | 0.00 | 11.89 |
February | 0.183357E+11 | 0.00 | 0.00 | 44562217.26 | 0.00 | 0.00 | 0.287272E+11 | 0.00 | 11.18 |
March | 0.155335E+11 | 0.00 | 0.00 | 89080217.24 | 0.00 | 0.00 | 0.316616E+11 | 0.00 | 11.91 |
April | 0.184026E+10 | 0.421380E+09 | 0.00 | 0.160652E+09 | 0.00 | 0.00 | 0.238686E+11 | 0.00 | 12.11 |
May | 0.172044E+09 | 0.171114E+10 | 0.00 | 0.159057E+09 | 0.00 | 0.00 | 0.174706E+11 | 0.00 | 12.01 |
June | 0.00 | 0.926514E+10 | 0.00 | 83800770.55 | 0.00 | 0.00 | 0.616556E+10 | 0.00 | 11.76 |
July | 0.00 | 0.147803E+11 | 0.00 | 37121530.28 | 0.00 | 0.00 | 0.252813E+10 | 0.00 | 11.89 |
August | 0.00 | 0.126355E+11 | 0.00 | 39984782.43 | 0.00 | 0.00 | 0.337282E+10 | 0.00 | 12.09 |
September | 0.00 | 0.804088E+10 | 0.00 | 65131693.53 | 0.00 | 0.00 | 0.615162E+10 | 0.00 | 12.42 |
October | 0.503486E+10 | 0.142393E+10 | 0.00 | 0.115917E+09 | 0.00 | 0.00 | 0.273870E+11 | 0.00 | 12.33 |
November | 0.127964E+11 | 0.00 | 0.00 | 90840189.51 | 0.00 | 0.00 | 0.336299E+11 | 0.00 | 11.99 |
December | 0.280349E+11 | 0.00 | 0.00 | 59210614.51 | 0.00 | 0.00 | 0.275284E+11 | 0.00 | 11.42 |
Annual Sum or Average | 0.989549E+11 | 0.482783E+11 | 0.00 | 0.103386E+10 | 0.00 | 0.00 | 0.240210E+12 | 0.00 | 11.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 37121530.28 | 0.00 | 0.00 | 0.252813E+10 | 0.00 | 11.18 |
Maximum of Months | 0.280349E+11 | 0.147803E+11 | 0.00 | 0.160652E+09 | 0.00 | 0.00 | 0.336299E+11 | 0.00 | 12.42 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.578146E+11 | 0.886405E+10 | 0.130492E+12 | 0.186031E+11 | 0.542101E+11 |
February | 0.653298E+11 | 0.103957E+11 | 0.135323E+12 | 0.129351E+11 | 0.234347E+11 |
March | 0.921254E+11 | 0.988039E+10 | 0.128542E+12 | 0.181979E+11 | 0.571525E+11 |
April | 0.125074E+12 | 0.555962E+10 | 0.699689E+11 | 0.905451E+10 | 0.145933E+12 |
May | 0.132559E+12 | 0.381098E+10 | 0.427371E+11 | 0.556946E+10 | 0.186347E+12 |
June | 0.137857E+12 | 0.797854E+09 | -0.125625E+11 | 0.199306E+10 | 0.245662E+12 |
July | 0.122968E+12 | -0.121873E+10 | -0.409517E+11 | 0.281410E+09 | 0.274689E+12 |
August | 0.104196E+12 | -0.108624E+10 | -0.330266E+11 | 0.850935E+09 | 0.268625E+12 |
September | 0.860712E+11 | -350957908.5 | -0.108804E+11 | 0.167531E+10 | 0.231315E+12 |
October | 0.768933E+11 | 0.496552E+10 | 0.832829E+11 | 0.147891E+11 | 0.124370E+12 |
November | 0.603804E+11 | 0.858716E+10 | 0.126746E+12 | 0.194768E+11 | 0.541418E+11 |
December | 0.445997E+11 | 0.108178E+11 | 0.155454E+12 | 0.148098E+11 | 0.378301E+11 |
Annual Sum or Average | 0.110587E+13 | 0.610231E+11 | 0.775125E+12 | 0.118236E+12 | 0.170371E+13 |
Minimum of Months | 0.445997E+11 | -0.121873E+10 | -0.409517E+11 | 0.281410E+09 | 0.234347E+11 |
Maximum of Months | 0.137857E+12 | 0.108178E+11 | 0.155454E+12 | 0.194768E+11 | 0.274689E+12 |