Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:28:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1935.93 | 3787.39 | 3787.39 |
Net Site Energy | 1935.93 | 3787.39 | 3787.39 |
Total Source Energy | 4040.33 | 7904.35 | 7904.35 |
Net Source Energy | 4040.33 | 7904.35 | 7904.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 190.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 66.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.47 | 343.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 932.20 | 1003.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 190.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 110.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 66.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 44.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.47 | 343.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 190.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 110.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 66.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 44.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 133.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.47 | 343.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 217.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 626.76 | 1044.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 979.86 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1823.73 | 1963.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 217.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 626.76 | 1044.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 979.86 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1823.73 | 1963.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 932.204 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 932.204 | 100.00 |
Total On-Site and Utility Electric Sources | 932.204 | 100.00 |
Total Electricity End Uses | 932.204 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3875.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 8.5664 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 9.6055 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 8.8498 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 8.5664 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.6055 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 8.8498 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 8.8498 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-17:19 | 15-DEC-07:49 | - | - | - | - | - | - | - | - | - | - | 30-JAN-07:00 |
Heating | 0.00 | 69087.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28024.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20336.83 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7873.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4427.01 | 27768.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1594.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 65295.86 | 110432.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 69087.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28024.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3022.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 19309.33 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7873.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4427.01 | 27768.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 440.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 960.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 206.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 210.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 141.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 423.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.01 | 372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 161.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2952.29 | 1088.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 403.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 411.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 828.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.60 | 728.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 315.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5775.74 | 2128.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 403.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 411.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 828.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.60 | 728.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 315.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5775.74 | 2128.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.66 |
KITCHEN DIRECT AIR | 1.89 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.66 | 4.66 | 4.66 | 4.66 | 4.66 | 4.66 | 1.00 | 1.00 | 4.66 |
PSZ-AC_2:2 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.66 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.89 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.66 | 7895.11 |
PSZ-AC_2:2_ADDAQ FAN | 1.89 | 2027.44 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.66 | 4.66 | 4.66 | 3.07 | 83966.63 | 126337.27 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 40709.33 | 73058.65 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.66 | 2.33 | 3.10 | 83966.63 | 41983.32 | 0.800480 | 0.800480 |
PSZ-AC_2:2 COOLING COIL | 1.89 | 0.947358 | 1.26 | 40709.33 | 20354.67 | 0.749260 | 0.749260 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 126337.27 |
PSZ-AC_2:2 HEATING COIL | 73058.65 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 8.566 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 73.494 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 9.605 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1070.246 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 3184.542 | 8.566 | 11.368 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3184.542 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1339.051 | 9.605 | 177.878 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1339.051 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1426 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2431 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.935 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.036 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.29769246E-08 | -0.18967486E-14 | 0.17735324E-14 | -0.50565546E-16 |
42 | 6 | 0.41018669E-05 | 0.27270264E-08 | 0.31943096E-02 | -0.26796545E-04 |
43 | 5 | -0.28850807E-03 | 0.16127836E-05 | -0.22397690 | 0.19583774E-02 |
44 | 4 | 0.65943933E-02 | 0.73359200E-04 | 4.8337480 | -0.45305377E-01 |
45 | 3 | -0.57777404E-01 | 0.58296435E-03 | -38.045154 | 0.39891614 |
46 | 2 | 0.20497420 | 0.96924505E-03 | 116.53015 | -1.4185573 |
47 | 1 | -0.29573351 | 0.29504543E-03 | -143.93450 | 2.0494869 |
48 | 0 | 0.14415612 | 0.71556298E-05 | 60.838472 | |
49 | 7 | -0.17284864E-08 | -0.37804902E-15 | 0.73321507E-14 | -0.99177345E-16 |
50 | 6 | 0.68009956E-05 | 0.46606830E-08 | 0.31864372E-02 | -0.26730506E-04 |
51 | 5 | -0.48976058E-03 | 0.27623059E-05 | -0.22352946 | 0.19544281E-02 |
52 | 4 | 0.11270010E-01 | 0.12574428E-03 | 4.8262959 | -0.45233742E-01 |
53 | 3 | -0.98979995E-01 | 0.10001134E-02 | -38.003058 | 0.39845083 |
54 | 2 | 0.35147541 | 0.16637932E-02 | 116.44822 | -1.4174614 |
55 | 1 | -0.50731320 | 0.50715641E-03 | -143.88627 | 2.0486942 |
56 | 0 | 0.24734252 | 0.12206389E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3815_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5028E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5135E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3690E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2837E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2989E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2799E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0828E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0008E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.1049E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.0865E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.7049E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.6830E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.9951E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.9871E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0253E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0253E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4894E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4730E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2537E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3315E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2473E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2719E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0008E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0828E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 43766.72331 | 52520.06798 | 3.88007 | 4.65609 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 7849.07181 | 9418.88618 | 0.40903 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | -7.90000 | 2.34317E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20988.16321 | 25185.79586 | 1.57893 | 1.89472 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 549.14932 | 658.97918 | 2.58907E-002 | 1.21700 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 66548.79 | 4.65609 | 4.65609 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63468.20 | 1.33138 | 1.33138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 34766.23 | 1.89472 | 1.89472 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 58015.80 | 1.21700 | 1.21700 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.65609 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89472 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.65609 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.65609 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.65609 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.65609 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.65609 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.65609 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89472 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89472 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89472 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89472 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89472 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.89472 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.65609 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.89472 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.65609 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.65609 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7895.11362 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.65609 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.65609 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.65609 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.07302 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.65609 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.32804 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.10406 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 83966.63000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41983.31500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80048 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80048 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 83966.63000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 126337.26702 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 126337.26702 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89472 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89472 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2027.43653 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89472 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89472 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89472 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25051 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89472 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94736 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26315 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40709.33000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20354.66500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74926 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74926 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40709.33000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 73058.64933 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 73058.64933 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 80577.5 | 10.23 | 10.18 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 39346.7 | 11.40 | 11.35 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | N/A | 2.168 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | N/A | 2.168 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | N/A | 2.168 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.143 | 0.138 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.243 | 0.230 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1185889246 | 0.3115091632 | Pass | Pass | 9.2221949875E-002 | 0.2420700995 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2118163351 | 0.6983165184 | Pass | Pass | 2.9031876226E-002 | 8.5096693637E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4830012680 | 0.5049791958 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 1219.40 | 125.39 | 1453.96 | 31.96 | 822.38 | 3653.10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.139 | 0.143 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.234 | 0.243 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 8.5664 | 371.75 | 3184.54 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 78.98 | 0.0000 | Y | 47.21 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.6055 | 139.41 | 1339.05 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 19.17 |
Interior Lighting Total | 8.8498 | 511.15 | 4523.59 | 66.39 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 3184.54 | 796.14 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3184.54 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 158.08 | AstronomicalClock | - | 48.81 | 48.81 | 1.45 | |
EXTERIOR_LIGHTS_B | 3137.97 | AstronomicalClock | - | 83.71 | 73.24 | 43.14 | |
Exterior Lighting Total | 3296.05 | 44.59 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 83966.63 | 67213.61 | 16753.02 | 0.80 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40709.33 | 30501.87 | 10207.46 | 0.75 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 80577.5 | 10.23 | 10.18 | ||||
PSZ-AC_2:2 COOLING COIL | 39346.7 | 11.40 | 11.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 126337.27 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 73058.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.66 | 7895.11 | 1695.65 | 1.00 | 1.18 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2027.44 | 1070.05 | 1.00 | 1.32 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 43766.72 | 52520.07 | 141.28 | 3.880 | 4.656 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.99 | 0.00823 | 34.97 | 0.00570 | 1.331 | 0.00 |
KITCHEN | 20988.16 | 25185.80 | 180.67 | 1.579 | 1.895 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.98 | 0.00884 | 33.89 | 0.00570 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7849.07 | 9418.89 | 25.34 | 0.409 | 1.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | 21.00 | 21.00 | 0.00776 | -7.90 | 0.00234 | 1.331 | 0.00 |
KITCHEN | 549.15 | 658.98 | 4.73 | 0.026 | 1.217 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 19.00 | 19.00 | 0.00405 | -7.90 | 0.00234 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.66 | 4.66 | 1.33 | 1.33 | 4.6561 | 4.6561 | 4.6561 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.89 | 1.89 | 1.22 | 1.22 | 1.8947 | 1.8947 | 1.8947 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 83966.630 | 67213.608 | 4.656090 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 41983.32 | 39621.22 | 3.104060 | 27.17 | 14.64 | 0.00750632 | 11.12 | 8.17 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 42.8915 | 23.99 | 0.00823031 | 36.4749 | 43746.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 126337.267 | 126337.267 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 126337.27 | 126337.27 | 4.656087 | 12.74 | 8.04 | 0.00620917 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 28.5943 | 21.00 | 0.00775730 | 41.2636 | 7844.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 40709.330 | 30501.873 | 1.894720 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 20354.67 | 20354.67 | 1.263147 | 32.10 | 15.62 | 0.00672492 | 11.74 | 8.15 | 0.00672492 | 35.10 | 0.00569938 | 15.77 | 96.3468 | 25.98 | 0.00882978 | 34.7140 | 20988.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 73058.649 | 73058.649 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 73058.65 | 73058.65 | 1.894717 | 1.26 | -1.46 | 0.00309967 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 64.2313 | 19.00 | 0.00445815 | 26.9841 | 308.25 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 83966.630 | 67213.608 | 4.656090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.7939 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.656087 | 4.61142966 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 41983.32 | 39621.22 | 1.0000 | 3.07428863 | 3.104060 | 27.17 | 14.64 | 0.00750632 | 46450.6 | 11.12 | 8.17 | 0.00700000 | 28824.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41983.32 | 35.10 | 0.00569938 | 15.77 | 1.33137743 | 42.8915 | 23.99 | 0.00823031 | 23.99 | 0.00823031 | 36.4749 | 43746.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 126337.267 | 126337.267 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.656087 | 4.61142966 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 126337.27 | 126337.27 | 1.0000 | 4.61142966 | 4.656087 | 12.74 | 8.04 | 0.00620917 | 28473.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 126337.27 | -7.90 | 0.00234317 | -7.90 | 1.33137743 | 28.5943 | 21.00 | 0.00775730 | 21.00 | 0.00775730 | 41.2636 | 7844.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40709.330 | 30501.873 | 1.894720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.3413 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.894717 | 1.87654436 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 20354.67 | 20354.67 | 1.0000 | 1.25103169 | 1.263147 | 32.10 | 15.62 | 0.00672492 | 49475.9 | 11.74 | 8.15 | 0.00672492 | 28760.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20354.67 | 35.10 | 0.00569938 | 15.77 | 1.21700195 | 96.3468 | 25.94 | 0.00882978 | 25.98 | 0.00882978 | 34.7140 | 20988.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73058.649 | 73058.649 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.894717 | 1.87654436 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 73058.65 | 73058.65 | 1.0000 | 1.87654436 | 1.894717 | 1.26 | -1.46 | 0.00309967 | 9021.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73058.65 | -7.90 | 0.00234317 | -7.90 | 1.21700195 | 64.2313 | 17.70 | 0.00445815 | 19.00 | 0.00445815 | 26.9841 | 308.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 4.66 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.89 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3257.50 | 3787.50 | 669.00 |
KITCHEN | 4843.67 | 5879.33 | 3829.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4888.33 | 6638.50 | 3875.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 135.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 135.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.859 | 0.928 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.519 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.099 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.056 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 39718917.53 | 0.00 | 39718917.53 | 7578459.79 | 47297377.32 | 41986318.57 | 1460.00 | 5462.67 | 1837.33 | 113.00 |
KITCHEN | 32672047.92 | 0.00 | 32672047.92 | 159765.52 | 32831813.44 | 38379373.44 | 1448.57 | 5535.79 | 1775.64 | 525.84 |
Total Facility | 72390965.45 | 0.00 | 72390965.45 | 7738225.31 | 80129190.76 | 80365692.01 | 1460.00 | 5702.15 | 2014.70 | 525.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.5141 | 0.0000 | 1.5141 | 0.2891 | 1.8032 | 1.3314 | 0.00 | 5352.07 | 1834.93 |
KITCHEN | 1.2260 | 0.0000 | 1.2260 | 0.0038 | 1.2298 | 1.2170 | 0.00 | 5424.14 | 1762.86 |
Total Facility | 2.7400 | 0.0000 | 2.7400 | 0.2929 | 3.0329 | 2.5484 | 0.00 | 5590.35 | 2001.15 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 38960632.75 | 0.00 | 38960632.75 | 41986318.57 | 6922.27 | 16.44 | 1821.29 | 113.00 |
PSZ-AC_2:2 | 32047468.45 | 0.00 | 32047468.45 | 38379373.44 | 6983.70 | 1700.38 | 75.92 | 525.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.4852 | 0.0000 | 1.4852 | 1.3314 | 5351.66 | 16.43 | 1818.91 |
PSZ-AC_2:2 | 1.2025 | 0.0000 | 1.2025 | 1.2170 | 5423.47 | 1688.78 | 74.75 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1388.74 | 458.23 | 5453.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 1999.02 | 5713.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.1103 | 1.6820 | 1.3062 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.2296 | 1.1939 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
Electricity:Building | 523.31 | 3391.80 | 01-JAN-01:10 | 29524.97 | 02-JAN-11:10 |
Electricity:Zone:DINING | 172.49 | 943.57 | 01-JAN-01:10 | 9073.41 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 516.38 | 3255.52 | 01-JAN-01:10 | 27381.86 | 02-JAN-11:10 |
InteriorLights:Electricity | 66.39 | 580.51 | 29-MAY-05:00 | 3713.52 | 02-JAN-17:10 |
InteriorLights:Electricity:Zone:DINING | 47.21 | 422.43 | 29-MAY-05:00 | 2765.04 | 02-JAN-17:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 66.39 | 580.51 | 29-MAY-05:00 | 3713.52 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity | 66.39 | 580.51 | 29-MAY-05:00 | 3713.52 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 47.21 | 422.43 | 29-MAY-05:00 | 2765.04 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 66.39 | 580.51 | 29-MAY-05:00 | 3713.52 | 02-JAN-17:10 |
Electricity:Zone:KITCHEN | 350.82 | 2448.23 | 01-JAN-01:10 | 20451.55 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.17 | 158.07 | 01-JAN-01:10 | 948.48 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 50.86 | 852.59 | 22-DEC-23:30 | 3195.67 | 23-AUG-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 119.85 | 1033.59 | 06-MAY-00:10 | 6429.77 | 14-MAY-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 14.28 | 0.00 | 01-JAN-11:10 | 1522.74 | 01-AUG-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 29.65 | 735.97 | 30-NOV-06:00 | 1076.23 | 11-APR-03:50 |
ElectricityPurchased:Facility | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
ElectricityPurchased:Plant | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
Cogeneration:ElectricityPurchased | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
General:Cogeneration:ElectricityPurchased | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
ElectricityNet:Plant | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
Cogeneration:ElectricityNet | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
General:Cogeneration:ElectricityNet | 932.20 | 6621.96 | 06-MAY-00:10 | 65295.86 | 21-JUL-17:20 |
Electricity:HVAC | 244.45 | 0.00 | 01-JAN-01:10 | 36260.57 | 21-JUL-17:10 |
Fans:Electricity | 133.73 | 0.00 | 01-JAN-01:10 | 7938.72 | 21-JUL-17:10 |
General:Fans:Electricity | 133.73 | 0.00 | 01-JAN-01:10 | 7938.72 | 21-JUL-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 110.73 | 0.00 | 01-JAN-00:10 | 28321.85 | 21-JUL-17:10 |
General:Cooling:Electricity | 110.73 | 0.00 | 01-JAN-00:10 | 28321.85 | 21-JUL-17:10 |
ExteriorLights:Electricity | 44.59 | 0.00 | 01-JAN-07:20 | 3296.05 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 44.59 | 0.00 | 01-JAN-07:20 | 3296.05 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.26 | 30-OCT-07:00 |
Water Heater:WaterSystems:Electricity | 75.47 | 0.00 | 01-JAN-01:10 | 4742.26 | 30-OCT-07:00 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 07-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 07-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1003.73 | 2758.01 | 01-JAN-01:10 | 110432.19 | 15-DEC-07:50 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 190.48 | 0.00 | 01-JAN-01:10 | 77230.03 | 21-JAN-07:00 |
Heating:NaturalGas | 190.48 | 0.00 | 01-JAN-01:10 | 77230.03 | 21-JAN-07:00 |
General:Heating:NaturalGas | 190.48 | 0.00 | 01-JAN-01:10 | 77230.03 | 21-JAN-07:00 |
NaturalGas:Plant | 343.46 | 947.76 | 01-JAN-01:10 | 30037.57 | 02-FEB-19:30 |
WaterSystems:NaturalGas | 343.46 | 947.76 | 01-JAN-01:10 | 30037.57 | 02-FEB-19:30 |
Water Heater:WaterSystems:NaturalGas | 343.46 | 947.76 | 01-JAN-01:10 | 30037.57 | 02-FEB-19:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 14-FEB-08:00 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 30-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1614.34 | 2931.15 | 15-DEC-01:10 | 159775.92 | 21-JUL-17:20 |
EnergyTransfer:Building | 753.99 | 1465.57 | 15-DEC-01:10 | 54997.33 | 21-JUL-17:20 |
EnergyTransfer:Zone:KITCHEN | 428.06 | 1465.57 | 15-DEC-01:10 | 26730.95 | 07-NOV-05:10 |
Refrigeration:EnergyTransfer | 139.67 | 2620.85 | 13-JAN-23:10 | 7834.84 | 11-APR-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.83 | 1310.42 | 13-JAN-23:10 | 3917.42 | 11-APR-03:50 |
General:Refrigeration:EnergyTransfer | 69.83 | 1310.42 | 13-JAN-23:10 | 3917.42 | 11-APR-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.83 | 1310.42 | 13-JAN-23:10 | 3917.42 | 11-APR-03:50 |
EnergyTransfer:Plant | 311.47 | 1465.57 | 15-DEC-01:10 | 19314.79 | 13-FEB-19:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.10 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.74 | 1217.90 | 30-NOV-06:00 | 2238.70 | 11-APR-03:50 |
EnergyTransfer:Zone:DINING | 325.94 | 0.00 | 01-JAN-01:10 | 34751.74 | 21-JUL-17:10 |
Heating:EnergyTransfer | 0.85 | 0.00 | 01-JAN-00:10 | 9364.94 | 22-DEC-08:40 |
Heating:EnergyTransfer:Zone:DINING | 0.85 | 0.00 | 01-JAN-00:10 | 9364.94 | 22-DEC-08:40 |
General:Heating:EnergyTransfer | 0.85 | 0.00 | 01-JAN-00:10 | 9364.94 | 22-DEC-08:40 |
General:Heating:EnergyTransfer:Zone:DINING | 0.85 | 0.00 | 01-JAN-00:10 | 9364.94 | 22-DEC-08:40 |
Cooling:EnergyTransfer | 683.31 | 0.00 | 01-JAN-01:10 | 52800.00 | 21-JUL-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 325.09 | 0.00 | 01-JAN-01:10 | 34751.74 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer | 683.31 | 0.00 | 01-JAN-01:10 | 52800.00 | 21-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 325.09 | 0.00 | 01-JAN-01:10 | 34751.74 | 21-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 358.22 | 0.00 | 01-JAN-01:10 | 22939.86 | 07-NOV-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 358.22 | 0.00 | 01-JAN-01:10 | 22939.86 | 07-NOV-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
PlantLoopHeatingDemand:Plant | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
EnergyTransfer:HVAC | 548.88 | 0.00 | 01-JAN-01:10 | 91281.56 | 21-JUL-17:10 |
HeatingCoils:EnergyTransfer | 152.39 | 0.00 | 01-JAN-01:10 | 61784.03 | 21-JAN-07:00 |
CoolingCoils:EnergyTransfer | 396.50 | 0.00 | 01-JAN-00:10 | 91281.56 | 21-JUL-17:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 241.63 | 0.00 | 01-JAN-01:10 | 16945.12 | 06-FEB-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.852 | -325.080 | 0.000 | 0.000 | 221.472 | 47.214 | 93.957 | 68.685 | 0.000 | 7.585 | 0.000 | 0.000 | -20.576 | 0.000 | -66.280 | -27.829 |
KITCHEN | 0.000 | 0.000 | 0.000 | -358.208 | 0.000 | 0.000 | 5.659 | 19.174 | 287.132 | 0.000 | 0.000 | 0.051 | 48.166 | 0.000 | 0.000 | 0.000 | -1.975 | -0.002 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.750 | 37.142 | 0.000 | 0.000 | 0.000 | -45.892 | -0.000 |
Total Facility | 0.000 | 0.000 | 0.852 | -683.288 | 0.000 | 0.000 | 227.131 | 66.389 | 381.090 | 68.685 | 0.000 | 16.386 | 85.309 | 0.000 | -20.576 | 0.000 | -114.147 | -27.831 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 22-AUG-04:01 | 0.00 | 0.00 | 0.00 | -50379.12 | 0.00 | 0.00 | 739.67 | 614.46 | 2172.30 | 0.00 | 0.00 | 0.00 | 47342.35 | 0.00 | -487.79 | 0.00 | -1.87 | 0.00 |
KITCHEN | 16-MAY-04:01 | 0.00 | 0.00 | 0.00 | -69917.82 | 0.00 | 0.00 | 4.50 | 210.77 | 6916.85 | 0.00 | 0.00 | 0.00 | 62818.34 | 0.00 | -0.00 | 0.00 | -32.64 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-04:01 | 0.00 | 0.00 | 0.00 | -90019.02 | 0.00 | 0.00 | 743.36 | 825.22 | 9089.15 | 0.00 | 0.00 | 265.72 | 79587.43 | 0.00 | -487.79 | 0.00 | -4.07 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 22-DEC-08:38 | 0.00 | 0.00 | 43423.54 | 0.00 | 0.00 | 0.00 | 9262.38 | 1382.51 | 3258.45 | 6445.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8503.65 | -55268.45 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-DEC-08:38 | -11798.16 | 11798.16 | 43423.54 | -11798.16 | 0.00 | 0.00 | 9534.39 | 2014.82 | 13119.97 | 6445.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8938.07 | -53801.72 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.6561 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.6561 | 0.2859 | 1.0000 | Not calculated | 1.3314 | 0.2859 | ||
PSZ-AC_2:2 | 1.8947 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8947 | 0.0964 | 1.0000 | Not calculated | 0.1826 | 0.0964 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.6561 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.6561 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2859 | ||
PSZ-AC_2:2 | 1.8947 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.8947 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.0964 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6561 | 4.6561 | 4.6561 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8947 | 1.8947 | 1.8947 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.6561 | 4.6561 | 4.6561 | 4.6561 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8947 | 1.8947 | 1.8947 | 1.8947 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6561 | 4.6561 | 4.6561 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8947 | 1.8947 | 1.8947 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.6561 | 4.6561 | 4.6561 | 4.6561 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.8947 | 1.8947 | 1.8947 | 1.8947 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 190.48 | 77230.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 110.73 | 28321.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 66.39 | 3713.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 44.59 | 3296.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 133.73 | 7938.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.47 | 4742.26 | 343.46 | 30037.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.28 | 1522.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.65 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 500.86 | 932.20 |
Natural Gas | 469.79 | 1003.73 |
Additional | 0.00 | 0.00 |
Total | 970.64 | 1935.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 129.88 |
Space Heating | 0.00 |
Space Cooling | 216.62 |
Fans (All) | 261.62 |
Service Water Heating | 147.65 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 1823.73 |
Subtotal | 1823.73 |
Natural Gas [MJ/m2] | |
Space Heating | 372.65 |
Service Water Heating | 671.93 |
Miscellaneous (All) | 1963.66 |
Subtotal | 1963.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.43 |
Space Heating | 9.84 |
Space Cooling | 5.72 |
Fans (All) | 6.91 |
Service Water Heating | 21.64 |
Receptacle Equipment | 47.51 |
Miscellaneous | 4.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7869.17 | 890.33 | 0.50 | 0.00 | 0.00 |
ATTIC | 6523.67 | 668.17 | 569.67 | 836.50 | 162.00 |
Min | 6523.67 | 28.00 | 0.00 | 0.00 | 0.00 |
Max | 8732.00 | 890.33 | 569.67 | 836.50 | 162.00 |
Average | 7708.28 | 528.83 | 190.06 | 278.83 | 54.00 |
Sum | 23124.83 | 1586.50 | 570.17 | 836.50 | 162.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824177.67 | 44.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19233.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824177.67 | 44.33 | 0.00 | 0.00 | 0.00 |
Average | 281136.89 | 14.78 | 0.00 | 0.00 | 0.00 |
Sum | 843410.67 | 44.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8631.83 | 128.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7238.67 | 1521.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 6775.50 | 871.83 | 292.00 | 289.50 | 531.17 |
Min | 6775.50 | 128.17 | 0.00 | 0.00 | 0.00 |
Max | 8631.83 | 1521.33 | 292.00 | 289.50 | 531.17 |
Average | 7548.67 | 840.44 | 97.33 | 96.50 | 177.06 |
Sum | 22646.00 | 2521.33 | 292.00 | 289.50 | 531.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 823610.67 | 611.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16871.50 | 2361.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 823610.67 | 2361.50 | 0.00 | 0.00 | 0.00 |
Average | 280160.72 | 990.94 | 0.00 | 0.00 | 0.00 |
Sum | 840482.17 | 2972.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:33
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166165E+11 | 31375.98 | 20-JAN-00:01 | -6.9 | -7.0 | 0.123076E+11 | 12855.58 | 05-JAN-12:00 | -6.9 | -7.0 |
February | 0.165266E+11 | 28198.99 | 06-FEB-00:01 | -4.4 | -6.2 | 0.113429E+11 | 12939.41 | 13-FEB-12:00 | 18.90 | 6.57 |
March | 0.214691E+11 | 25530.20 | 10-MAR-05:01 | -1.1 | -4.3 | 0.136203E+11 | 14051.38 | 25-MAR-18:10 | 17.33 | 5.38 |
April | 0.253976E+11 | 24492.57 | 13-APR-17:04 | 25.92 | 10.22 | 0.140482E+11 | 14051.41 | 29-APR-18:10 | 23.53 | 8.85 |
May | 0.293109E+11 | 27716.75 | 19-MAY-17:05 | 29.90 | 12.04 | 0.150593E+11 | 14051.73 | 27-MAY-18:00 | 24.40 | 12.44 |
June | 0.351570E+11 | 33904.54 | 28-JUN-17:03 | 37.23 | 14.64 | 0.149492E+11 | 14051.57 | 03-JUN-18:49 | 37.23 | 14.64 |
July | 0.392453E+11 | 39854.59 | 21-JUL-04:01 | 20.92 | 12.28 | 0.153315E+11 | 14053.09 | 01-JUL-18:49 | 20.92 | 12.28 |
August | 0.389762E+11 | 50388.36 | 22-AUG-04:01 | 21.70 | 15.47 | 0.155203E+11 | 14053.32 | 26-AUG-18:00 | 21.70 | 16.13 |
September | 0.341322E+11 | 32899.78 | 03-SEP-04:01 | 18.72 | 11.90 | 0.148457E+11 | 14053.54 | 23-SEP-18:19 | 17.80 | 12.90 |
October | 0.289962E+11 | 27052.70 | 05-OCT-17:02 | 26.32 | 11.05 | 0.144521E+11 | 14051.38 | 21-OCT-18:10 | 16.13 | 6.44 |
November | 0.219790E+11 | 25121.83 | 27-NOV-00:01 | -1.7 | -5.1 | 0.125446E+11 | 12939.77 | 09-NOV-12:00 | -1.7 | -5.1 |
December | 0.172785E+11 | 29963.96 | 22-DEC-08:37 | -5.8 | -7.3 | 0.120694E+11 | 11668.60 | 01-DEC-12:00 | -5.8 | -7.3 |
Annual Sum or Average | 0.325085E+12 | 0.166091E+12 | ||||||||
Minimum of Months | 0.165266E+11 | 24492.57 | -6.9 | -7.3 | 0.113429E+11 | 11668.60 | -6.9 | -7.3 | ||
Maximum of Months | 0.392453E+11 | 50388.36 | 37.23 | 15.47 | 0.155203E+11 | 14053.54 | 37.23 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287506E+11 | 35337.62 | 27-JAN-05:01 | -4.3 | -7.1 | 0.104219E+11 | 6894.39 | 05-JAN-11:00 | -4.3 | -7.1 |
February | 0.257453E+11 | 34342.17 | 28-FEB-05:01 | -3.0 | -3.9 | 0.942844E+10 | 6934.90 | 14-FEB-11:00 | -3.0 | -3.9 |
March | 0.285299E+11 | 33461.39 | 10-MAR-05:01 | -1.1 | -4.3 | 0.105014E+11 | 6934.91 | 08-MAR-11:00 | -1.1 | -4.3 |
April | 0.280735E+11 | 45042.43 | 28-APR-03:51 | 11.70 | 3.86 | 0.102140E+11 | 6934.91 | 21-APR-10:50 | 11.70 | 3.86 |
May | 0.298736E+11 | 69863.11 | 16-MAY-04:01 | 11.28 | 2.90 | 0.105856E+11 | 6934.99 | 24-MAY-10:00 | 17.80 | 14.22 |
June | 0.309116E+11 | 65674.71 | 20-JUN-04:01 | 11.78 | 5.18 | 0.102631E+11 | 6934.98 | 01-JUN-10:09 | 11.78 | 5.18 |
July | 0.330536E+11 | 45813.17 | 21-JUL-04:01 | 20.92 | 12.28 | 0.106030E+11 | 6934.91 | 17-JUL-10:39 | 20.92 | 12.28 |
August | 0.330017E+11 | 47310.27 | 20-AUG-04:01 | 18.98 | 12.01 | 0.106089E+11 | 6934.95 | 23-AUG-10:30 | 18.60 | 16.41 |
September | 0.308511E+11 | 58255.36 | 26-SEP-04:01 | 15.00 | 8.70 | 0.102594E+11 | 6934.98 | 07-SEP-10:09 | 15.00 | 8.70 |
October | 0.307722E+11 | 45446.61 | 06-OCT-03:11 | 14.07 | 7.77 | 0.105506E+11 | 6934.95 | 03-OCT-10:30 | 14.07 | 7.77 |
November | 0.293123E+11 | 32924.12 | 27-NOV-05:01 | -4.0 | -6.5 | 0.101267E+11 | 6934.95 | 09-NOV-11:00 | -4.0 | -6.5 |
December | 0.293462E+11 | 39790.36 | 15-DEC-05:01 | -9.1 | -11.9 | 0.104076E+11 | 6880.09 | 01-DEC-11:00 | -9.1 | -11.9 |
Annual Sum or Average | 0.358222E+12 | 0.123971E+12 | ||||||||
Minimum of Months | 0.257453E+11 | 32924.12 | -9.1 | -11.9 | 0.942844E+10 | 6880.09 | -9.1 | -11.9 | ||
Maximum of Months | 0.330536E+11 | 69863.11 | 20.92 | 12.28 | 0.106089E+11 | 6934.99 | 20.92 | 16.41 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 | -5.2 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 | 2.84 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 | 4.92 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 | 8.96 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 | 14.90 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.86 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 | 10.88 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 | 5.34 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.00 | 0.00 | -3.2 | -5.2 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.00 | 0.00 | 21.95 | 16.86 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256284E+09 | 19253.91 | 17-JAN-05:01 | -3.3 |
February | 0.193506E+09 | 29820.73 | 06-FEB-05:01 | -4.4 |
March | 51034443.71 | 35526.42 | 06-MAR-06:45 | -1.0 |
April | 9014975.68 | 6435.66 | 08-APR-05:03 | 2.62 |
May | 2248759.61 | 3998.96 | 06-MAY-05:03 | 6.02 |
June | 16429668.62 | 5565.18 | 28-JUN-23:02 | 27.12 |
July | 31229006.13 | 6184.85 | 22-JUL-23:02 | 27.70 |
August | 11266737.73 | 4226.92 | 20-AUG-23:02 | 26.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 8574301.70 | 8398.09 | 26-OCT-04:02 | -2.8 |
November | 37277991.53 | 8341.18 | 27-NOV-06:03 | -4.4 |
December | 0.234795E+09 | 43423.43 | 22-DEC-08:38 | -5.8 |
Annual Sum or Average | 0.851661E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.8 | |
Maximum of Months | 0.256284E+09 | 43423.43 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.410234E+10 | 2765.04 | 02-JAN-17:10 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.368854E+10 | 2765.04 | 01-FEB-17:30 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.405887E+10 | 2765.04 | 01-MAR-17:49 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.380857E+10 | 2765.04 | 01-APR-18:30 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.392247E+10 | 2765.04 | 01-MAY-18:49 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.379876E+10 | 2765.04 | 01-JUN-16:49 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.388750E+10 | 2765.04 | 01-JUL-19:19 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.396561E+10 | 2765.04 | 01-AUG-19:10 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.385109E+10 | 2765.04 | 01-SEP-18:30 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.402277E+10 | 2765.04 | 02-OCT-17:30 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.397440E+10 | 2765.04 | 01-NOV-16:49 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.413337E+10 | 2765.04 | 01-DEC-16:40 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.472143E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.368854E+10 | 2765.04 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.413337E+10 | 2765.04 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.162018E+10 | 948.48 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.146748E+10 | 948.48 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.164598E+10 | 948.48 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.157428E+10 | 948.48 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.163308E+10 | 948.48 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.159097E+10 | 948.48 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.161658E+10 | 948.48 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.164598E+10 | 948.48 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.157466E+10 | 948.48 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.161999E+10 | 948.48 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.156840E+10 | 948.48 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.161677E+10 | 948.48 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.191743E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.146748E+10 | 948.48 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.164598E+10 | 948.48 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.410234E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115299E+11 |
February | 0.272721E+11 | 0.368854E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937497E+10 |
March | 0.305458E+11 | 0.405887E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773107E+10 |
April | 0.292871E+11 | 0.380857E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30332064.51 | 0.470564E+10 |
May | 0.303219E+11 | 0.392247E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355826E+09 | 0.297290E+10 |
June | 0.295292E+11 | 0.379876E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207290E+10 | 0.117556E+10 |
July | 0.300798E+11 | 0.388750E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257700E+10 | 0.458392E+09 |
August | 0.305458E+11 | 0.396561E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183898E+10 | 0.750900E+09 |
September | 0.292871E+11 | 0.385109E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616562E+09 | 0.174320E+10 |
October | 0.300980E+11 | 0.402277E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93546182.09 | 0.526126E+10 |
November | 0.290996E+11 | 0.397440E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870408E+10 |
December | 0.300798E+11 | 0.413337E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118719E+11 |
Annual Sum or Average | 0.356244E+12 | 0.472143E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758515E+10 | 0.662798E+11 |
Minimum of Months | 0.272721E+11 | 0.368854E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458392E+09 |
Maximum of Months | 0.305458E+11 | 0.413337E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257700E+10 | 0.118719E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.162018E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248705E+09 |
February | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239164E+09 |
March | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259004E+09 |
April | 0.786997E+09 | 0.157428E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 290.79 | 0.176544E+09 |
May | 0.814802E+09 | 0.163308E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1953038.99 | 0.150138E+09 |
June | 0.793501E+09 | 0.159097E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 15400967.45 | 91992056.46 |
July | 0.808298E+09 | 0.161658E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19701426.89 | 60137779.85 |
August | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 10676015.10 | 78615860.03 |
September | 0.786997E+09 | 0.157466E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2677359.41 | 97463088.93 |
October | 0.808786E+09 | 0.161999E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 325334.49 | 0.150138E+09 |
November | 0.781956E+09 | 0.156840E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205173E+09 |
December | 0.808298E+09 | 0.161677E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217979E+09 |
Annual Sum or Average | 0.957291E+10 | 0.191743E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 50734433.11 | 0.197505E+10 |
Minimum of Months | 0.732850E+09 | 0.146748E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60137779.85 |
Maximum of Months | 0.820818E+09 | 0.164598E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 19701426.89 | 0.259004E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872039E+09 | 0.253388E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635102E+09 | 0.288165E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648942E+09 | 0.344285E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716588E+09 | 0.453346E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704041E+09 | 0.481793E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606812E+09 | 0.481831E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538784E+09 | 0.512726E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476502E+09 | 0.508157E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706649E+09 | 0.408208E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866219E+09 | 0.335206E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938016E+09 | 0.269967E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104046E+10 | 0.252117E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875015E+10 | 0.458919E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476502E+09 | 0.252117E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104046E+10 | 0.512726E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2765.04 | 02-JAN-17:10 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 14931.38 | 19-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2765.04 | 01-FEB-17:30 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 13566.94 | 04-FEB-20:00 |
March | 30255.31 | 04-MAR-19:10 | 2765.04 | 01-MAR-17:49 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 10037.48 | 04-MAR-20:00 |
April | 30255.31 | 01-APR-18:10 | 2765.04 | 01-APR-18:30 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 968.68 | 13-APR-17:02 | 8849.89 | 15-APR-18:10 |
May | 30255.31 | 06-MAY-18:10 | 2765.04 | 01-MAY-18:49 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.43 | 19-MAY-17:03 | 7403.27 | 01-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2765.04 | 01-JUN-16:49 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6454.26 | 28-JUN-17:02 | 6716.78 | 08-JUN-19:00 |
July | 30255.31 | 01-JUL-18:10 | 2765.04 | 01-JUL-19:19 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6564.02 | 21-JUL-17:03 | 2974.58 | 07-JUL-18:00 |
August | 30255.31 | 05-AUG-18:10 | 2765.04 | 01-AUG-19:10 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4587.32 | 04-AUG-17:03 | 3588.54 | 25-AUG-20:00 |
September | 30255.31 | 02-SEP-18:10 | 2765.04 | 01-SEP-18:30 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3059.05 | 20-SEP-17:02 | 4873.10 | 23-SEP-19:00 |
October | 30255.31 | 07-OCT-18:10 | 2765.04 | 02-OCT-17:30 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.14 | 11-OCT-13:00 | 10514.90 | 24-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2765.04 | 01-NOV-16:49 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 10647.26 | 27-NOV-21:00 |
December | 30255.31 | 02-DEC-19:10 | 2765.04 | 01-DEC-16:40 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 13417.06 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.58 | |||||
Maximum of Months | 30255.31 | 2765.04 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 6564.02 | 14931.38 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 948.48 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 888.61 | 17-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 948.48 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 895.85 | 05-FEB-01:10 |
March | 813.01 | 04-MAR-19:10 | 948.48 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1015.33 | 14-MAR-03:08 |
April | 813.01 | 01-APR-18:10 | 948.48 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.42 | 13-APR-16:53 | 1022.52 | 23-APR-04:00 |
May | 813.01 | 06-MAY-18:10 | 948.48 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 29.52 | 19-MAY-14:53 | 778.68 | 18-MAY-03:50 |
June | 813.01 | 03-JUN-18:10 | 948.48 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 66.34 | 17-JUN-15:53 | 611.15 | 02-JUN-03:50 |
July | 813.01 | 01-JUL-18:10 | 948.48 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 73.39 | 04-JUL-14:53 | 306.45 | 05-JUL-02:50 |
August | 813.01 | 05-AUG-18:10 | 948.48 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 38.76 | 02-AUG-13:00 | 383.46 | 08-AUG-00:50 |
September | 813.01 | 02-SEP-18:10 | 948.48 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 24.40 | 03-SEP-14:51 | 451.66 | 08-SEP-02:00 |
October | 813.01 | 07-OCT-18:10 | 948.48 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 9.49 | 01-OCT-15:52 | 558.77 | 12-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 948.48 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 967.35 | 25-NOV-05:00 |
December | 813.01 | 02-DEC-19:10 | 948.48 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1292.31 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 306.45 | ||||||
Maximum of Months | 813.01 | 948.48 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 73.39 | 1292.31 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1997.43 | 10-JAN-23:53 | 5299.58 | 29-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1687.93 | 14-FEB-07:23 | 6274.73 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.64 | 08-MAR-05:00 | 7062.44 | 30-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1844.39 | 01-APR-04:00 | 8148.69 | 08-APR-13:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1870.75 | 09-MAY-03:51 | 8258.16 | 28-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1816.71 | 20-JUN-02:00 | 7517.17 | 03-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.88 | 14-JUL-05:53 | 7250.59 | 28-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.65 | 17-AUG-04:10 | 7348.09 | 03-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1526.51 | 27-SEP-23:00 | 6916.01 | 09-SEP-12:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1786.60 | 29-OCT-22:00 | 6751.96 | 14-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1756.45 | 12-NOV-23:00 | 5877.28 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783.87 | 13-DEC-02:70 | 5595.89 | 22-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.65 | 5299.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1997.43 | 8258.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31375.98 | 20-JAN-00:01 | 16808.50 | 4608.35 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28198.99 | 06-FEB-00:01 | 16808.50 | 4608.35 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.07 |
March | 25530.20 | 10-MAR-05:01 | 16808.50 | 6144.57 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.63 |
April | 24492.57 | 13-APR-17:04 | 134468.03 | 10368.91 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 968.68 | 0.00 |
May | 27716.75 | 19-MAY-17:05 | 107574.42 | 8295.13 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.43 | 0.00 |
June | 33904.54 | 28-JUN-17:03 | 161361.63 | 12442.69 | 34756.79 | 0.00 | 0.00 | 0.00 | 0.00 | 6454.25 | 0.00 |
July | 39854.59 | 21-JUL-04:01 | 13446.80 | 4915.66 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
August | 50388.36 | 22-AUG-04:01 | 15127.65 | 5530.12 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
September | 32899.78 | 03-SEP-04:01 | 0.00 | 4147.52 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
October | 27052.70 | 05-OCT-17:02 | 134468.03 | 10368.91 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.13 | 0.00 |
November | 25121.83 | 27-NOV-00:01 | 16808.50 | 4608.35 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.13 |
December | 29963.96 | 22-DEC-08:37 | 134468.03 | 13825.05 | 43445.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8269.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24492.57 | 0.00 | 4147.52 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50388.36 | 161361.63 | 13825.05 | 43445.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6454.25 | 8269.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35337.62 | 27-JAN-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34342.17 | 28-FEB-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 |
March | 33461.39 | 10-MAR-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.83 |
April | 45042.43 | 28-APR-03:51 | 0.00 | 1422.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 117.92 |
May | 69863.11 | 16-MAY-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 |
June | 65674.71 | 20-JUN-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
July | 45813.17 | 21-JUL-04:01 | 361.34 | 1686.13 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
August | 47310.27 | 20-AUG-04:01 | 0.00 | 1264.60 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
September | 58255.36 | 26-SEP-04:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 |
October | 45446.61 | 06-OCT-03:11 | 0.00 | 1580.75 | 32802.55 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 |
November | 32924.12 | 27-NOV-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 |
December | 39790.36 | 15-DEC-05:01 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 32924.12 | 0.00 | 1264.60 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69863.11 | 451.67 | 2107.67 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.43 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.96 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.56 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.58 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.88 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.35 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.36 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.73 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.58 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.01 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.56 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.708467E+11 | 39747.50 | 20-JAN-11:09 | 0.124699E+12 | 106285.99 | 26-JAN-07:30 |
February | 0.636938E+11 | 39744.69 | 14-FEB-17:49 | 0.103131E+12 | 107114.96 | 06-FEB-07:30 |
March | 0.701691E+11 | 42911.30 | 08-MAR-18:10 | 0.891574E+11 | 86362.73 | 05-MAR-06:49 |
April | 0.713189E+11 | 47603.25 | 28-APR-18:49 | 0.724286E+11 | 65127.94 | 06-APR-06:49 |
May | 0.787770E+11 | 51232.26 | 23-MAY-10:00 | 0.693660E+11 | 48757.06 | 06-MAY-05:10 |
June | 0.873335E+11 | 64636.10 | 28-JUN-16:10 | 0.647659E+11 | 43402.09 | 03-JUN-10:20 |
July | 0.977975E+11 | 65295.86 | 21-JUL-17:19 | 0.654588E+11 | 43162.61 | 04-JUL-10:30 |
August | 0.944649E+11 | 59083.85 | 17-AUG-11:09 | 0.654778E+11 | 43088.04 | 27-AUG-10:00 |
September | 0.832329E+11 | 53981.93 | 03-SEP-10:00 | 0.639344E+11 | 43288.03 | 30-SEP-10:50 |
October | 0.757056E+11 | 52569.28 | 11-OCT-10:00 | 0.736082E+11 | 81600.48 | 26-OCT-06:00 |
November | 0.679192E+11 | 39925.74 | 09-NOV-11:39 | 0.871292E+11 | 94592.20 | 27-NOV-07:30 |
December | 0.709449E+11 | 39615.49 | 21-DEC-11:09 | 0.124575E+12 | 110432.19 | 15-DEC-07:49 |
Annual Sum or Average | 0.932204E+12 | 0.100373E+13 | ||||
Minimum of Months | 0.636938E+11 | 39615.49 | 0.639344E+11 | 43088.04 | ||
Maximum of Months | 0.977975E+11 | 65295.86 | 0.124699E+12 | 110432.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.572253E+10 | 0.454811E+10 | 0.382185E+11 | 0.00 | 0.119730E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639629E+10 | 0.00 |
February | 0.515602E+10 | 0.384214E+10 | 0.345199E+11 | 0.00 | 0.105812E+11 | 34213790.43 | 0.00 | 0.161148E+09 | 0.00 | 0.00 | 0.00 | 0.578792E+10 | 0.00 |
March | 0.570485E+10 | 0.386978E+10 | 0.382185E+11 | 0.00 | 0.111387E+11 | 37879553.69 | 0.00 | 0.575965E+09 | 0.00 | 0.00 | 0.00 | 0.645944E+10 | 0.00 |
April | 0.538285E+10 | 0.335166E+10 | 0.369856E+11 | 0.00 | 0.105537E+11 | 36657632.61 | 0.00 | 0.460720E+10 | 0.00 | 0.00 | 0.00 | 0.619847E+10 | 0.00 |
May | 0.555555E+10 | 0.313081E+10 | 0.382185E+11 | 0.00 | 0.109129E+11 | 37879553.69 | 0.00 | 0.100102E+11 | 0.00 | 0.00 | 0.00 | 0.641685E+10 | 0.00 |
June | 0.538973E+10 | 0.286913E+10 | 0.369856E+11 | 0.00 | 0.109681E+11 | 36657632.61 | 0.00 | 0.204028E+11 | 0.00 | 0.00 | 0.00 | 0.623634E+10 | 0.00 |
July | 0.550408E+10 | 0.303720E+10 | 0.382185E+11 | 0.00 | 0.116837E+11 | 37879553.69 | 0.00 | 0.282985E+11 | 0.00 | 0.00 | 0.00 | 0.637108E+10 | 0.00 |
August | 0.561159E+10 | 0.331209E+10 | 0.382185E+11 | 0.00 | 0.113847E+11 | 37879553.69 | 0.00 | 0.247984E+11 | 0.00 | 0.00 | 0.00 | 0.644932E+10 | 0.00 |
September | 0.542575E+10 | 0.357908E+10 | 0.369856E+11 | 0.00 | 0.106668E+11 | 36657632.61 | 0.00 | 0.158828E+11 | 0.00 | 0.00 | 0.00 | 0.619457E+10 | 0.00 |
October | 0.564276E+10 | 0.409721E+10 | 0.382185E+11 | 0.00 | 0.109942E+11 | 37879553.69 | 0.00 | 0.594696E+10 | 0.00 | 0.00 | 0.00 | 0.638350E+10 | 0.00 |
November | 0.554279E+10 | 0.430883E+10 | 0.369856E+11 | 0.00 | 0.108676E+11 | 36657632.61 | 0.00 | 42204829.91 | 0.00 | 0.00 | 0.00 | 0.618690E+10 | 0.00 |
December | 0.575014E+10 | 0.464304E+10 | 0.382185E+11 | 0.00 | 0.120032E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638926E+10 | 0.00 |
Annual Sum or Average | 0.663886E+11 | 0.445891E+11 | 0.449992E+12 | 0.00 | 0.133728E+12 | 0.446001E+09 | 0.00 | 0.110726E+12 | 0.00 | 0.00 | 0.00 | 0.754699E+11 | 0.00 |
Minimum of Months | 0.515602E+10 | 0.286913E+10 | 0.345199E+11 | 0.00 | 0.105537E+11 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578792E+10 | 0.00 |
Maximum of Months | 0.575014E+10 | 0.464304E+10 | 0.382185E+11 | 0.00 | 0.120032E+11 | 37879553.69 | 0.00 | 0.282985E+11 | 0.00 | 0.00 | 0.00 | 0.645944E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.521712E+11 | 0.00 | 0.326280E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.373749E+11 | 0.00 | 0.297177E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.168733E+11 | 0.00 | 0.323844E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.421025E+10 | 0.00 | 0.296057E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.758467E+09 | 0.00 | 0.287079E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 21705728.61 | 0.00 | 0.261316E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.255591E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.255781E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.253218E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.603785E+10 | 0.00 | 0.276706E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.198061E+11 | 0.00 | 0.287104E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.532292E+11 | 0.00 | 0.314458E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.190483E+12 | 0.00 | 0.343461E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.253218E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.532292E+11 | 0.00 | 0.326280E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3713.52 | 02-JAN-17:10 | 3296.05 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 6615.63 | 21-JAN-06:00 | 17.86 | 07-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3713.52 | 01-FEB-17:30 | 3296.05 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 6607.40 | 04-FEB-06:10 | 17.86 | 08-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3713.52 | 01-MAR-17:49 | 3296.05 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 6270.95 | 05-MAR-06:10 | 17.86 | 04-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 3713.52 | 01-APR-18:30 | 3296.05 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 5748.72 | 08-APR-05:10 | 17.86 | 07-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 3713.52 | 01-MAY-18:49 | 3296.05 | 01-MAY-05:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 5395.51 | 07-MAY-05:10 | 17.86 | 30-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 3713.52 | 01-JUN-16:49 | 3296.05 | 01-JUN-19:10 | 24359.61 | 01-JUN-10:09 | 0.00 | 7721.46 | 28-JUN-17:10 | 17.86 | 03-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 3713.52 | 01-JUL-19:19 | 3296.05 | 01-JUL-19:19 | 24359.61 | 01-JUL-10:09 | 0.00 | 7938.72 | 21-JUL-17:10 | 17.86 | 07-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 3713.52 | 01-AUG-19:10 | 3296.05 | 01-AUG-05:10 | 24359.61 | 01-AUG-10:09 | 0.00 | 6597.87 | 17-AUG-11:09 | 17.86 | 05-AUG-08:39 | 0.00 | 01-AUG-00:10 |
September | 3713.52 | 01-SEP-18:30 | 3296.05 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 5194.87 | 03-SEP-10:00 | 17.86 | 03-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 3713.52 | 02-OCT-17:30 | 3296.05 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 6164.49 | 26-OCT-05:10 | 17.86 | 20-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 3713.52 | 01-NOV-16:49 | 3296.05 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 6326.80 | 27-NOV-06:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3713.52 | 01-DEC-16:40 | 3296.05 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 6610.25 | 15-DEC-06:10 | 17.86 | 08-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 5194.87 | 17.86 | 0.00 | ||||||
Maximum of Months | 3713.52 | 3296.05 | 24359.61 | 0.00 | 7938.72 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4742.09 | 25-JAN-19:00 | 0.00 |
February | 5587.22 | 14-FEB-16:10 | 0.00 | 0.00 | 0.00 | 4742.04 | 07-FEB-07:49 | 0.00 |
March | 8019.45 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 4742.06 | 08-MAR-07:40 | 0.00 |
April | 12624.19 | 13-APR-17:10 | 0.00 | 0.00 | 0.00 | 4741.83 | 24-APR-06:49 | 0.00 |
May | 16085.12 | 19-MAY-17:19 | 0.00 | 0.00 | 0.00 | 4741.82 | 05-MAY-06:10 | 0.00 |
June | 27656.56 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 4737.60 | 05-JUN-06:19 | 0.00 |
July | 28321.85 | 21-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.90 | 05-JUL-18:00 | 0.00 |
August | 21578.45 | 17-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4736.69 | 11-AUG-18:30 | 0.00 |
September | 17623.01 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 4738.39 | 26-SEP-06:19 | 0.00 |
October | 14894.54 | 11-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4742.26 | 30-OCT-06:00 | 0.00 |
November | 4129.82 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4741.91 | 15-NOV-07:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4741.55 | 28-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4736.69 | 0.00 | ||
Maximum of Months | 28321.85 | 0.00 | 0.00 | 0.00 | 4742.26 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 39747.50 | 20-JAN-11:09 | 3022.26 | 24359.61 | 0.00 | 0.00 | 5870.61 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 39744.69 | 14-FEB-17:49 | 3713.52 | 21945.94 | 3296.05 | 0.00 | 4793.15 | 17.86 | 0.00 | 1283.71 | 0.00 |
March | 42911.30 | 08-MAR-18:10 | 3713.52 | 20336.83 | 3296.05 | 0.00 | 4793.15 | 17.86 | 0.00 | 4752.29 | 0.00 |
April | 47603.25 | 28-APR-18:49 | 3713.52 | 18727.72 | 3296.05 | 0.00 | 4793.15 | 17.86 | 0.00 | 10733.04 | 0.00 |
May | 51232.26 | 23-MAY-10:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4838.21 | 17.86 | 0.00 | 13087.12 | 0.00 |
June | 64636.10 | 28-JUN-16:10 | 3022.26 | 21945.94 | 0.00 | 0.00 | 7414.34 | 17.86 | 0.00 | 27656.56 | 0.00 |
July | 65295.86 | 21-JUL-17:19 | 3022.26 | 20336.83 | 0.00 | 0.00 | 7873.19 | 17.86 | 0.00 | 28024.57 | 0.00 |
August | 59083.85 | 17-AUG-11:09 | 3022.26 | 22750.50 | 0.00 | 0.00 | 6597.87 | 17.86 | 0.00 | 21577.64 | 0.00 |
September | 53981.93 | 03-SEP-10:00 | 2350.64 | 24359.61 | 0.00 | 0.00 | 5194.87 | 17.86 | 0.00 | 15796.07 | 0.00 |
October | 52569.28 | 11-OCT-10:00 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4968.29 | 17.86 | 0.00 | 13996.16 | 0.00 |
November | 39925.74 | 09-NOV-11:39 | 3022.26 | 24359.61 | 0.00 | 0.00 | 4793.15 | 17.86 | 0.00 | 1546.28 | 0.00 |
December | 39615.49 | 21-DEC-11:09 | 3022.26 | 24359.61 | 0.00 | 0.00 | 5729.92 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 39615.49 | 2350.64 | 18727.72 | 0.00 | 0.00 | 4793.15 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65295.86 | 3713.52 | 24359.61 | 3296.05 | 0.00 | 7873.19 | 17.86 | 0.00 | 28024.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 77230.03 | 21-JAN-06:00 | 0.00 | 29963.33 | 27-JAN-19:30 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 76686.94 | 04-FEB-06:10 | 0.00 | 30037.57 | 02-FEB-19:30 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 61632.15 | 05-MAR-06:10 | 0.00 | 29596.43 | 02-MAR-07:30 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 38279.31 | 08-APR-05:10 | 0.00 | 27510.54 | 03-APR-06:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 22162.73 | 07-MAY-05:10 | 0.00 | 24501.28 | 01-MAY-18:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 8509.92 | 09-JUN-05:10 | 0.00 | 20543.65 | 02-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 17672.12 | 03-JUL-18:40 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 17586.87 | 31-AUG-06:00 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 18558.60 | 29-SEP-18:19 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 57145.60 | 26-OCT-05:10 | 0.00 | 22874.75 | 31-OCT-06:40 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 64588.31 | 27-NOV-06:10 | 0.00 | 26374.87 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 76733.60 | 15-DEC-06:10 | 0.00 | 28723.59 | 29-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 17586.87 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 77230.03 | 0.00 | 30037.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 29.70 | 0.00 | 29.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 30.56 | 0.00 | 30.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 30.90 | 0.00 | 30.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 31.14 | 0.00 | 31.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 31.38 | 0.00 | 31.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 31.37 | 0.00 | 31.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 31.13 | 0.00 | 31.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 30.96 | 0.00 | 30.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 29.96 | 0.00 | 29.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 135.50 | 31.15 | 0.00 | 31.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 31.38 | 0.00 | 31.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 604.33 | 20.98 | 118.33 | 20.77 | 118.33 | 20.61 |
February | 527.67 | 21.05 | 85.83 | 20.84 | 85.83 | 20.67 |
March | 501.33 | 21.43 | 47.17 | 21.25 | 47.17 | 21.09 |
April | 303.17 | 21.80 | 55.33 | 21.99 | 11.50 | 21.91 |
May | 176.67 | 22.27 | 264.33 | 23.29 | 8.17 | 23.29 |
June | 46.17 | 22.72 | 505.67 | 23.96 | 9.67 | 23.96 |
July | 97.83 | 24.13 | 609.00 | 24.13 | 97.83 | 24.13 |
August | 72.17 | 24.09 | 610.50 | 24.10 | 71.83 | 24.10 |
September | 55.50 | 23.32 | 531.33 | 23.94 | 34.33 | 23.94 |
October | 261.67 | 21.61 | 247.33 | 22.66 | 14.50 | 22.60 |
November | 532.00 | 21.28 | 63.33 | 21.17 | 50.50 | 21.02 |
December | 609.00 | 20.81 | 119.33 | 20.63 | 119.33 | 20.50 |
Annual Sum or Average | 3787.50 | 21.43 | 3257.50 | 22.36 | 669.00 | 22.25 |
Minimum of Months | 46.17 | 20.81 | 47.17 | 20.63 | 8.17 | 20.50 |
Maximum of Months | 609.00 | 24.13 | 610.50 | 24.13 | 119.33 | 24.13 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 565.17 | 19.51 | 229.33 | 19.47 | 210.00 | 19.35 |
February | 468.50 | 19.58 | 198.67 | 19.82 | 153.17 | 19.67 |
March | 368.17 | 20.11 | 261.50 | 21.59 | 72.67 | 21.44 |
April | 356.33 | 23.29 | 376.33 | 24.33 | 194.83 | 24.59 |
May | 407.00 | 25.34 | 530.33 | 25.47 | 358.67 | 25.61 |
June | 514.00 | 25.97 | 585.83 | 25.89 | 510.83 | 25.93 |
July | 608.83 | 26.04 | 609.00 | 26.04 | 608.83 | 26.04 |
August | 608.33 | 26.01 | 612.00 | 26.01 | 608.33 | 26.01 |
September | 506.00 | 25.97 | 590.00 | 25.86 | 506.00 | 25.89 |
October | 433.17 | 23.71 | 428.33 | 24.47 | 282.00 | 24.75 |
November | 445.67 | 20.10 | 197.00 | 20.72 | 99.83 | 20.62 |
December | 598.17 | 19.30 | 225.33 | 19.20 | 224.33 | 19.14 |
Annual Sum or Average | 5879.33 | 22.99 | 4843.67 | 23.73 | 3829.50 | 23.96 |
Minimum of Months | 356.33 | 19.30 | 197.00 | 19.20 | 72.67 | 19.14 |
Maximum of Months | 608.83 | 26.04 | 612.00 | 26.04 | 608.83 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.00520 | 21.60178 | -0.4291 | 10.35153 |
February | 551.00000 | 21.17858 | 23.38323 | -0.3678 | 9.68615 |
March | 612.00000 | 21.89243 | 23.03555 | -0.1834 | 7.97383 |
April | 590.00000 | 22.86303 | 19.78231 | 0.06482 | 7.21582 |
May | 611.00000 | 23.48755 | 27.31783 | -0.6153 | 15.37171 |
June | 592.00000 | 23.95004 | 35.08272 | -0.3452 | 8.32683 |
July | 609.00000 | 24.12875 | 46.48078 | -0.1703 | 5.80908 |
August | 612.00000 | 24.09881 | 45.82583 | -0.1781 | 5.90191 |
September | 590.00000 | 23.92467 | 40.89419 | -0.2957 | 7.46862 |
October | 610.00000 | 22.95394 | 28.70006 | 0.18260 | 8.46949 |
November | 591.00000 | 21.54204 | 23.48050 | -0.2330 | 8.06424 |
December | 609.00000 | 20.81179 | 19.67824 | -0.4738 | 10.69635 |
Annual Sum or Average | 7187.00000 | 22.66110 | 29.65612 | -0.2533 | 8.78156 |
Minimum of Months | 551.00000 | 20.81179 | 19.67824 | -0.6153 | 5.80908 |
Maximum of Months | 612.00000 | 24.12875 | 46.48078 | 0.18260 | 15.37171 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.81907 | 29.13163 | -0.4420 | 11.62133 |
February | 551.00000 | 20.26261 | 30.58192 | -0.3330 | 11.64989 |
March | 612.00000 | 21.89542 | 29.07512 | 0.05056 | 11.73227 |
April | 590.00000 | 23.79449 | 24.96158 | 0.49672 | 16.66868 |
May | 611.00000 | 25.03400 | 30.02227 | 0.17886 | 12.38916 |
June | 592.00000 | 25.78529 | 36.01476 | 0.53530 | 12.80548 |
July | 609.00000 | 26.03722 | 45.18114 | 0.72341 | 16.45275 |
August | 612.00000 | 26.00132 | 44.57750 | 0.70187 | 15.91693 |
September | 590.00000 | 25.75991 | 40.71795 | 0.56128 | 13.19135 |
October | 610.00000 | 23.85782 | 32.14843 | 0.60004 | 20.48377 |
November | 591.00000 | 21.00972 | 29.45951 | -0.1181 | 10.46755 |
December | 609.00000 | 19.36201 | 27.30328 | -0.5471 | 12.47679 |
Annual Sum or Average | 7187.00000 | 23.23404 | 33.29285 | 0.20334 | 13.84402 |
Minimum of Months | 551.00000 | 19.36201 | 24.96158 | -0.5471 | 10.46755 |
Maximum of Months | 612.00000 | 26.03722 | 45.18114 | 0.72341 | 20.48377 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.322556E+09 | 0.105609E+09 | 12.17 | 0.322556E+09 | 0.00 | 0.00 | 0.36 | 14-FEB-14:00 | 0.00 | 01-FEB-00:01 | 12387.04 | 14-FEB-14:00 | 12387.04 | 14-FEB-14:00 | 0.00 | 14-FEB-16:18 | 3956.13 | 14-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.103673E+10 | 0.342969E+09 | 62.67 | 0.103651E+10 | 220102.33 | 0.00 | 0.52 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 | 18632.68 | 08-MAR-14:00 | 18632.68 | 08-MAR-14:00 | 123.21 | 16-MAR-12:30 | 5715.48 | 08-MAR-14:00 | 0.00 | 01-MAR-00:01 |
April | 0.926905E+10 | 0.288548E+10 | 211.00 | 0.926454E+10 | 4506178.75 | 0.00 | 0.78 | 13-APR-17:02 | 0.00 | 01-APR-00:01 | 30164.45 | 13-APR-17:02 | 30164.45 | 13-APR-17:02 | 788.70 | 14-APR-20:00 | 8623.12 | 13-APR-17:02 | 0.00 | 01-APR-00:01 |
May | 0.205419E+11 | 0.619293E+10 | 344.76 | 0.200812E+11 | 0.460797E+09 | 0.00 | 0.95 | 19-MAY-17:03 | 0.00 | 01-MAY-00:01 | 38693.47 | 19-MAY-17:03 | 38693.47 | 19-MAY-17:03 | 4791.90 | 24-MAY-11:55 | 10689.63 | 19-MAY-17:03 | 0.00 | 01-MAY-00:01 |
June | 0.430527E+11 | 0.127046E+11 | 458.69 | 0.414868E+11 | 0.156582E+10 | 0.00 | 1.00 | 12-JUN-17:02 | 0.00 | 01-JUN-00:01 | 56748.83 | 28-JUN-17:03 | 56748.83 | 28-JUN-17:03 | 7978.11 | 30-JUN-14:00 | 18074.55 | 28-JUN-17:03 | 0.00 | 01-JUN-00:01 |
July | 0.611539E+11 | 0.176508E+11 | 546.03 | 0.524875E+11 | 0.866639E+10 | 0.00 | 1.00 | 03-JUL-11:23 | 0.00 | 01-JUL-00:01 | 58135.81 | 21-JUL-17:08 | 58135.81 | 21-JUL-17:08 | 17836.51 | 31-JUL-18:00 | 18642.70 | 21-JUL-17:08 | 0.00 | 01-JUL-00:01 |
August | 0.543292E+11 | 0.155623E+11 | 524.53 | 0.465942E+11 | 0.773504E+10 | 0.00 | 1.00 | 01-AUG-11:15 | 0.00 | 01-AUG-00:01 | 60867.84 | 22-AUG-04:01 | 48226.51 | 21-AUG-17:10 | 16979.29 | 13-AUG-04:01 | 16312.81 | 22-AUG-04:01 | 0.00 | 01-AUG-00:01 |
September | 0.341598E+11 | 0.998339E+10 | 435.58 | 0.302622E+11 | 0.389759E+10 | 0.00 | 1.00 | 01-SEP-13:00 | 0.00 | 01-SEP-00:01 | 42605.81 | 05-SEP-12:55 | 40778.04 | 20-SEP-17:06 | 15769.72 | 05-SEP-12:55 | 11301.33 | 02-SEP-17:02 | 0.00 | 01-SEP-00:01 |
October | 0.123430E+11 | 0.372791E+10 | 230.57 | 0.114035E+11 | 0.939501E+09 | 0.00 | 0.92 | 11-OCT-11:53 | 0.00 | 01-OCT-00:01 | 36972.62 | 11-OCT-11:53 | 33255.47 | 05-OCT-17:02 | 10706.71 | 02-OCT-17:10 | 10161.12 | 11-OCT-11:53 | 0.00 | 01-OCT-00:01 |
November | 42140776.10 | 14187943.09 | 4.00 | 39588246.51 | 2552529.59 | 0.00 | 0.22 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 | 7283.27 | 09-NOV-14:00 | 7027.77 | 09-NOV-14:00 | 345.37 | 09-NOV-12:50 | 2407.10 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.236251E+12 | 0.691701E+11 | 2830.00 | 0.212979E+12 | 0.232724E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.611539E+11 | 0.176508E+11 | 546.03 | 0.524875E+11 | 0.866639E+10 | 0.00 | 1.00 | 0.00 | 60867.84 | 58135.81 | 17836.51 | 18642.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.187397E+09 | 55538957.49 | 17.42 | 0.187340E+09 | 56952.54 | 0.00 | 0.41 | 14-FEB-16:08 | 0.00 | 01-FEB-00:01 | 6927.35 | 14-FEB-16:08 | 6927.35 | 14-FEB-16:08 | 188.80 | 14-FEB-04:40 | 1990.11 | 14-FEB-16:08 | 0.00 | 01-FEB-00:01 |
March | 0.780619E+09 | 0.232996E+09 | 76.89 | 0.778159E+09 | 2460213.94 | 0.00 | 0.47 | 08-MAR-16:07 | 0.00 | 01-MAR-00:01 | 8230.58 | 08-MAR-16:07 | 8230.58 | 08-MAR-16:07 | 478.10 | 28-MAR-03:10 | 2323.84 | 08-MAR-16:07 | 0.00 | 01-MAR-00:01 |
April | 0.620205E+10 | 0.172172E+10 | 239.11 | 0.618400E+10 | 18053526.80 | 0.00 | 1.00 | 11-APR-03:41 | 0.00 | 01-APR-00:01 | 40161.67 | 28-APR-03:11 | 37652.74 | 28-APR-03:11 | 2741.65 | 28-APR-03:51 | 9800.52 | 28-APR-03:11 | 0.00 | 01-APR-00:01 |
May | 0.143809E+11 | 0.381722E+10 | 387.88 | 0.137128E+11 | 0.668123E+09 | 0.00 | 1.00 | 09-MAY-03:21 | 0.00 | 01-MAY-00:01 | 40161.67 | 21-MAY-03:52 | 40161.67 | 09-MAY-04:01 | 16287.71 | 30-MAY-04:01 | 9800.52 | 09-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.293830E+11 | 0.769822E+10 | 509.41 | 0.279501E+11 | 0.143290E+10 | 0.00 | 1.00 | 01-JUN-03:11 | 0.00 | 01-JUN-00:01 | 40161.67 | 22-JUN-01:32 | 38695.72 | 28-JUN-00:53 | 13344.34 | 04-JUN-03:22 | 10350.45 | 28-JUN-15:57 | 0.00 | 01-JUN-00:01 |
July | 0.415662E+11 | 0.106478E+11 | 602.23 | 0.354299E+11 | 0.613631E+10 | 0.00 | 1.00 | 01-JUL-02:52 | 0.00 | 01-JUL-00:01 | 40544.60 | 04-JUL-00:42 | 37644.81 | 21-JUL-00:42 | 19153.26 | 29-JUL-02:52 | 9989.64 | 22-JUL-15:00 | 0.00 | 01-JUL-00:01 |
August | 0.363567E+11 | 0.923606E+10 | 581.13 | 0.306799E+11 | 0.567685E+10 | 0.00 | 1.00 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 | 40161.67 | 20-AUG-01:22 | 35629.79 | 16-AUG-01:22 | 23832.63 | 13-AUG-04:01 | 9800.52 | 02-AUG-02:52 | 0.00 | 01-AUG-00:01 |
September | 0.229938E+11 | 0.589943E+10 | 473.34 | 0.196111E+11 | 0.338279E+10 | 0.00 | 1.00 | 01-SEP-03:31 | 0.00 | 01-SEP-00:01 | 40161.67 | 23-SEP-03:11 | 34656.29 | 22-SEP-03:41 | 23262.94 | 06-SEP-04:01 | 9800.52 | 03-SEP-03:21 | 0.00 | 01-SEP-00:01 |
October | 0.830011E+10 | 0.221904E+10 | 265.90 | 0.740803E+10 | 0.892076E+09 | 0.00 | 1.00 | 01-OCT-03:11 | 0.00 | 01-OCT-00:01 | 40161.67 | 01-OCT-03:11 | 31427.36 | 06-OCT-03:51 | 17017.71 | 11-OCT-03:11 | 9800.52 | 01-OCT-03:11 | 0.00 | 01-OCT-00:01 |
November | 93210989.52 | 28016886.82 | 12.35 | 79013884.94 | 14197104.58 | 0.00 | 0.35 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 | 5915.03 | 09-NOV-14:00 | 5384.50 | 09-NOV-14:00 | 1980.01 | 03-NOV-03:04 | 1722.71 | 09-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.160244E+12 | 0.415560E+11 | 3165.65 | 0.142020E+12 | 0.182238E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.415662E+11 | 0.106478E+11 | 602.23 | 0.354299E+11 | 0.613631E+10 | 0.00 | 1.00 | 0.00 | 40544.60 | 40161.67 | 23832.63 | 10350.45 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.39 | 172.05 | 135.34 | 277.72 | 344.00 | 0.00 | 0.00 | 0.00 |
February | 372.25 | 200.10 | 172.15 | 366.27 | 310.46 | 0.00 | 0.00 | 0.00 |
March | 494.68 | 281.82 | 212.86 | 544.23 | 242.29 | 0.00 | 0.00 | 0.00 |
April | 671.05 | 381.87 | 289.19 | 804.80 | 170.37 | 0.00 | 0.00 | 0.00 |
May | 641.09 | 365.16 | 275.93 | 806.09 | 131.48 | 0.00 | 0.00 | 0.00 |
June | 691.38 | 425.86 | 265.52 | 948.66 | 88.19 | 0.00 | 0.00 | 0.00 |
July | 639.42 | 365.53 | 273.89 | 914.44 | 61.20 | 0.00 | 0.00 | 0.00 |
August | 632.87 | 348.83 | 284.04 | 875.96 | 71.02 | 0.00 | 0.00 | 0.00 |
September | 527.73 | 295.29 | 232.44 | 690.37 | 119.25 | 0.00 | 0.00 | 0.00 |
October | 459.78 | 291.97 | 167.81 | 535.77 | 199.82 | 0.00 | 0.00 | 0.00 |
November | 357.59 | 209.78 | 147.82 | 360.27 | 278.45 | 0.00 | 0.00 | 0.00 |
December | 291.28 | 177.67 | 113.61 | 263.88 | 359.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.72 | 293.37 | 214.35 | 616.82 | 197.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 291.28 | 172.05 | 113.61 | 263.88 | 61.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 691.38 | 425.86 | 289.19 | 948.66 | 359.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1132.82 | 880.95 | 251.86 | 1326.62 | 461.90 | 0.00 | 0.00 | 0.00 |
February | 1116.63 | 817.22 | 299.41 | 1333.73 | 423.21 | 0.00 | 0.00 | 0.00 |
March | 830.32 | 506.67 | 323.65 | 1011.73 | 344.70 | 0.00 | 0.00 | 0.00 |
April | 637.69 | 261.33 | 376.36 | 801.45 | 251.48 | 0.00 | 0.00 | 0.00 |
May | 429.17 | 97.09 | 332.08 | 542.21 | 190.46 | 0.00 | 0.00 | 0.00 |
June | 358.77 | 43.08 | 315.69 | 524.26 | 130.59 | 0.00 | 0.00 | 0.00 |
July | 397.14 | 62.31 | 334.83 | 630.16 | 87.99 | 0.00 | 0.00 | 0.00 |
August | 540.24 | 170.39 | 369.85 | 818.85 | 103.02 | 0.00 | 0.00 | 0.00 |
September | 766.94 | 431.72 | 335.22 | 1080.67 | 171.63 | 0.00 | 0.00 | 0.00 |
October | 1033.26 | 760.05 | 273.21 | 1325.08 | 275.20 | 0.00 | 0.00 | 0.00 |
November | 1165.55 | 897.03 | 268.52 | 1399.60 | 373.05 | 0.00 | 0.00 | 0.00 |
December | 1235.35 | 1019.76 | 215.58 | 1454.00 | 472.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 801.87 | 493.95 | 307.92 | 1018.88 | 273.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.77 | 43.08 | 215.58 | 524.26 | 87.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1235.35 | 1019.76 | 376.36 | 1454.00 | 472.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.01 | 180.79 | 136.22 | 310.28 | 361.78 | 0.00 | 0.00 | 0.00 |
February | 407.26 | 235.00 | 172.27 | 426.46 | 323.66 | 0.00 | 0.00 | 0.00 |
March | 454.43 | 241.39 | 213.04 | 501.68 | 254.98 | 0.00 | 0.00 | 0.00 |
April | 581.39 | 309.42 | 271.96 | 685.68 | 177.60 | 0.00 | 0.00 | 0.00 |
May | 552.86 | 285.66 | 267.21 | 687.08 | 135.17 | 0.00 | 0.00 | 0.00 |
June | 589.11 | 328.09 | 261.02 | 813.75 | 94.32 | 0.00 | 0.00 | 0.00 |
July | 531.88 | 259.90 | 271.98 | 768.13 | 63.63 | 0.00 | 0.00 | 0.00 |
August | 544.07 | 251.28 | 292.78 | 758.22 | 74.22 | 0.00 | 0.00 | 0.00 |
September | 493.64 | 260.63 | 233.01 | 650.51 | 124.55 | 0.00 | 0.00 | 0.00 |
October | 451.76 | 281.39 | 170.37 | 535.51 | 210.56 | 0.00 | 0.00 | 0.00 |
November | 353.01 | 207.66 | 145.35 | 362.67 | 287.63 | 0.00 | 0.00 | 0.00 |
December | 303.12 | 189.29 | 113.84 | 290.56 | 371.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.00 | 252.42 | 212.58 | 566.34 | 206.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.12 | 180.79 | 113.84 | 290.56 | 63.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 589.11 | 328.09 | 292.78 | 813.75 | 371.42 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823309E+09 | 0.460814E+09 | 0.362495E+09 | 0.743836E+09 | 0.921362E+09 |
February | 0.900536E+09 | 0.484081E+09 | 0.416455E+09 | 0.886085E+09 | 0.751055E+09 |
March | 0.132495E+10 | 0.754821E+09 | 0.570126E+09 | 0.145766E+10 | 0.648951E+09 |
April | 0.173937E+10 | 0.989803E+09 | 0.749570E+09 | 0.208604E+10 | 0.441591E+09 |
May | 0.171710E+10 | 0.978046E+09 | 0.739051E+09 | 0.215902E+10 | 0.352164E+09 |
June | 0.179206E+10 | 0.110384E+10 | 0.688216E+09 | 0.245893E+10 | 0.228592E+09 |
July | 0.171262E+10 | 0.979037E+09 | 0.733588E+09 | 0.244924E+10 | 0.163912E+09 |
August | 0.169507E+10 | 0.934296E+09 | 0.760770E+09 | 0.234616E+10 | 0.190209E+09 |
September | 0.136788E+10 | 0.765398E+09 | 0.602484E+09 | 0.178943E+10 | 0.309084E+09 |
October | 0.123148E+10 | 0.782015E+09 | 0.449467E+09 | 0.143502E+10 | 0.535192E+09 |
November | 0.926882E+09 | 0.543745E+09 | 0.383137E+09 | 0.933814E+09 | 0.721749E+09 |
December | 0.780158E+09 | 0.475874E+09 | 0.304285E+09 | 0.706774E+09 | 0.962098E+09 |
Annual Sum or Average | 0.160114E+11 | 0.925177E+10 | 0.675964E+10 | 0.194520E+11 | 0.622596E+10 |
Minimum of Months | 0.780158E+09 | 0.460814E+09 | 0.304285E+09 | 0.706774E+09 | 0.163912E+09 |
Maximum of Months | 0.179206E+10 | 0.110384E+10 | 0.760770E+09 | 0.245893E+10 | 0.962098E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303413E+10 | 0.235954E+10 | 0.674595E+09 | 0.355322E+10 | 0.123716E+10 |
February | 0.270136E+10 | 0.197702E+10 | 0.724336E+09 | 0.322655E+10 | 0.102384E+10 |
March | 0.222393E+10 | 0.135706E+10 | 0.866876E+09 | 0.270982E+10 | 0.923244E+09 |
April | 0.165289E+10 | 0.677374E+09 | 0.975514E+09 | 0.207735E+10 | 0.651841E+09 |
May | 0.114949E+10 | 0.260044E+09 | 0.889445E+09 | 0.145226E+10 | 0.510130E+09 |
June | 0.929943E+09 | 0.111665E+09 | 0.818278E+09 | 0.135889E+10 | 0.338480E+09 |
July | 0.106370E+10 | 0.166901E+09 | 0.896798E+09 | 0.168782E+10 | 0.235680E+09 |
August | 0.144699E+10 | 0.456374E+09 | 0.990617E+09 | 0.219320E+10 | 0.275921E+09 |
September | 0.198792E+10 | 0.111902E+10 | 0.868897E+09 | 0.280111E+10 | 0.444877E+09 |
October | 0.276749E+10 | 0.203572E+10 | 0.731779E+09 | 0.354910E+10 | 0.737088E+09 |
November | 0.302111E+10 | 0.232510E+10 | 0.696011E+09 | 0.362775E+10 | 0.966942E+09 |
December | 0.330875E+10 | 0.273134E+10 | 0.577419E+09 | 0.389438E+10 | 0.126548E+10 |
Annual Sum or Average | 0.252877E+11 | 0.155771E+11 | 0.971056E+10 | 0.321315E+11 | 0.861069E+10 |
Minimum of Months | 0.929943E+09 | 0.111665E+09 | 0.577419E+09 | 0.135889E+10 | 0.235680E+09 |
Maximum of Months | 0.330875E+10 | 0.273134E+10 | 0.990617E+09 | 0.389438E+10 | 0.126548E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.849074E+09 | 0.484231E+09 | 0.364843E+09 | 0.831060E+09 | 0.968995E+09 |
February | 0.985250E+09 | 0.568501E+09 | 0.416748E+09 | 0.103169E+10 | 0.783008E+09 |
March | 0.121714E+10 | 0.646543E+09 | 0.570602E+09 | 0.134369E+10 | 0.682928E+09 |
April | 0.150695E+10 | 0.802021E+09 | 0.704932E+09 | 0.177729E+10 | 0.460345E+09 |
May | 0.148079E+10 | 0.765106E+09 | 0.715684E+09 | 0.184026E+10 | 0.362048E+09 |
June | 0.152696E+10 | 0.850402E+09 | 0.676560E+09 | 0.210923E+10 | 0.244484E+09 |
July | 0.142460E+10 | 0.696121E+09 | 0.728478E+09 | 0.205735E+10 | 0.170426E+09 |
August | 0.145722E+10 | 0.673032E+09 | 0.784193E+09 | 0.203082E+10 | 0.198799E+09 |
September | 0.127951E+10 | 0.675554E+09 | 0.603961E+09 | 0.168613E+10 | 0.322822E+09 |
October | 0.120999E+10 | 0.753674E+09 | 0.456312E+09 | 0.143431E+10 | 0.563958E+09 |
November | 0.914990E+09 | 0.538252E+09 | 0.376739E+09 | 0.940051E+09 | 0.745530E+09 |
December | 0.811882E+09 | 0.506984E+09 | 0.304898E+09 | 0.778240E+09 | 0.994820E+09 |
Annual Sum or Average | 0.146644E+11 | 0.796042E+10 | 0.670395E+10 | 0.178601E+11 | 0.649817E+10 |
Minimum of Months | 0.811882E+09 | 0.484231E+09 | 0.304898E+09 | 0.778240E+09 | 0.170426E+09 |
Maximum of Months | 0.152696E+10 | 0.850402E+09 | 0.784193E+09 | 0.210923E+10 | 0.994820E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1876.44 | 1129.50 | 1757.21 | 1233.79 | 523.42 | 0.00 | 0.00 |
February | 2095.45 | 1026.33 | 1896.14 | 1252.32 | 643.82 | 0.00 | 0.00 |
March | 2024.95 | 809.28 | 1779.43 | 1029.88 | 749.55 | 0.00 | 0.00 |
April | 2259.27 | 566.79 | 1890.13 | 952.62 | 937.51 | 0.00 | 0.00 |
May | 2017.88 | 439.63 | 1623.12 | 747.91 | 875.22 | 0.00 | 0.00 |
June | 2272.07 | 298.50 | 1639.26 | 797.03 | 842.23 | 0.00 | 0.00 |
July | 2307.88 | 207.97 | 1568.45 | 687.75 | 880.70 | 0.00 | 0.00 |
August | 2445.36 | 240.58 | 1717.17 | 770.50 | 946.68 | 0.00 | 0.00 |
September | 2409.43 | 403.30 | 1788.32 | 987.64 | 800.67 | 0.00 | 0.00 |
October | 2374.84 | 664.05 | 1944.80 | 1333.41 | 611.39 | 0.00 | 0.00 |
November | 2093.45 | 910.04 | 1876.15 | 1314.47 | 561.68 | 0.00 | 0.00 |
December | 1961.11 | 1155.78 | 1829.75 | 1386.72 | 443.03 | 0.00 | 0.00 |
Annual Sum or Average | 2177.98 | 652.46 | 1774.59 | 1039.74 | 734.85 | 0.00 | 0.00 |
Minimum of Months | 1876.44 | 207.97 | 1568.45 | 687.75 | 443.03 | 0.00 | 0.00 |
Maximum of Months | 2445.36 | 1155.78 | 1944.80 | 1386.72 | 946.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.502585E+10 | 0.302525E+10 | 0.470652E+10 | 0.330458E+10 | 0.140193E+10 | 0.00 | 0.00 |
February | 0.506932E+10 | 0.248289E+10 | 0.458714E+10 | 0.302961E+10 | 0.155754E+10 | 0.00 | 0.00 |
March | 0.542362E+10 | 0.216757E+10 | 0.476602E+10 | 0.275842E+10 | 0.200760E+10 | 0.00 | 0.00 |
April | 0.585603E+10 | 0.146913E+10 | 0.489921E+10 | 0.246920E+10 | 0.243002E+10 | 0.00 | 0.00 |
May | 0.540470E+10 | 0.117750E+10 | 0.434737E+10 | 0.200320E+10 | 0.234418E+10 | 0.00 | 0.00 |
June | 0.588921E+10 | 0.773717E+09 | 0.424896E+10 | 0.206591E+10 | 0.218305E+10 | 0.00 | 0.00 |
July | 0.618143E+10 | 0.557039E+09 | 0.420092E+10 | 0.184206E+10 | 0.235886E+10 | 0.00 | 0.00 |
August | 0.654964E+10 | 0.644375E+09 | 0.459928E+10 | 0.206370E+10 | 0.253558E+10 | 0.00 | 0.00 |
September | 0.624523E+10 | 0.104535E+10 | 0.463532E+10 | 0.255997E+10 | 0.207534E+10 | 0.00 | 0.00 |
October | 0.636078E+10 | 0.177859E+10 | 0.520896E+10 | 0.357140E+10 | 0.163756E+10 | 0.00 | 0.00 |
November | 0.542621E+10 | 0.235881E+10 | 0.486298E+10 | 0.340709E+10 | 0.145589E+10 | 0.00 | 0.00 |
December | 0.525264E+10 | 0.309565E+10 | 0.490079E+10 | 0.371419E+10 | 0.118660E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.686847E+11 | 0.205759E+11 | 0.559635E+11 | 0.327893E+11 | 0.231742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.502585E+10 | 0.557039E+09 | 0.420092E+10 | 0.184206E+10 | 0.118660E+10 | 0.00 | 0.00 |
Maximum of Months | 0.654964E+10 | 0.309565E+10 | 0.520896E+10 | 0.371419E+10 | 0.253558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639624E+10 | -0.622517E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -171069383.9 | 81.22 | 0.00 | 0.00 |
February | 0.578776E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -153477860.7 | 81.22 | 0.00 | 0.00 |
March | 0.645927E+10 | -0.629388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165390610.6 | 81.22 | 0.00 | 0.00 |
April | 0.619830E+10 | -0.604349E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154808218.6 | 81.21 | 0.00 | 0.00 |
May | 0.641671E+10 | -0.626020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156512839.3 | 81.21 | 0.00 | 0.00 |
June | 0.623616E+10 | -0.608660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149557692.3 | 81.21 | 0.00 | 0.00 |
July | 0.637093E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153829582.4 | 81.21 | 0.00 | 0.00 |
August | 0.644914E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153924099.8 | 81.21 | 0.00 | 0.00 |
September | 0.619438E+10 | -0.604484E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -149538781.4 | 81.21 | 0.00 | 0.00 |
October | 0.638343E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159602409.7 | 81.22 | 0.00 | 0.00 |
November | 0.618672E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162093002.5 | 81.22 | 0.00 | 0.00 |
December | 0.638922E+10 | -0.621706E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172155257.3 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.754682E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190196E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.578776E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172155257.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.645927E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149538781.4 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.242257E+11 | -0.232334E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -992246890.4 | 58.99 | 0.00 | 0.00 |
February | 0.220765E+11 | -0.211898E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -886747184.1 | 58.99 | 0.00 | 0.00 |
March | 0.240261E+11 | -0.230858E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -940282559.3 | 58.99 | 0.00 | 0.00 |
April | 0.218506E+11 | -0.209887E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -861938696.7 | 58.99 | 0.00 | 0.00 |
May | 0.210678E+11 | -0.202087E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -859141317.6 | 58.99 | 0.00 | 0.00 |
June | 0.190576E+11 | -0.182437E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -813910557.5 | 58.99 | 0.00 | 0.00 |
July | 0.185271E+11 | -0.176927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -834392880.5 | 58.98 | 0.00 | 0.00 |
August | 0.185480E+11 | -0.177126E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -835407261.6 | 58.99 | 0.00 | 0.00 |
September | 0.184062E+11 | -0.175925E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -813682019.0 | 58.99 | 0.00 | 0.00 |
October | 0.202336E+11 | -0.193463E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -887300362.3 | 58.99 | 0.00 | 0.00 |
November | 0.211342E+11 | -0.202055E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -928652347.6 | 58.99 | 0.00 | 0.00 |
December | 0.232680E+11 | -0.222658E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100222E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.252421E+12 | -0.241765E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.106559E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.184062E+11 | -0.232334E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.100222E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.242257E+11 | -0.175925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -813682019.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.76 | 0.75 | 01-JAN-07:40 | 1410.12 | 25.10 | 164.17 | 285.00 | 1280.32 | 25.72 | 172.83 | 286.00 |
February | 282.00 | 0.76 | 0.75 | 01-FEB-07:40 | 1736.57 | 24.95 | 173.67 | 271.00 | 1221.45 | 24.32 | 169.67 | 271.83 |
March | 351.33 | 0.76 | 0.75 | 01-MAR-06:00 | 1108.95 | 20.61 | 129.67 | 329.67 | 1510.44 | 21.29 | 154.67 | 330.50 |
April | 381.83 | 0.76 | 0.75 | 01-APR-06:40 | 1344.75 | 21.10 | 177.67 | 362.83 | 1397.33 | 21.04 | 158.83 | 360.83 |
May | 378.00 | 0.76 | 0.75 | 01-MAY-06:19 | 1303.33 | 20.68 | 135.33 | 386.50 | 1560.92 | 20.69 | 97.17 | 376.67 |
June | 412.83 | 0.76 | 0.75 | 01-JUN-05:49 | 861.38 | 20.67 | 86.83 | 385.33 | 1539.30 | 19.75 | 77.33 | 394.33 |
July | 395.33 | 0.76 | 0.75 | 01-JUL-06:49 | 884.73 | 20.43 | 106.00 | 382.33 | 1395.58 | 20.37 | 124.00 | 382.83 |
August | 408.83 | 0.76 | 0.75 | 01-AUG-05:00 | 1237.06 | 20.90 | 154.00 | 382.00 | 1247.52 | 20.90 | 169.33 | 381.50 |
September | 359.33 | 0.76 | 0.75 | 01-SEP-06:30 | 1214.96 | 21.20 | 144.17 | 335.67 | 1089.34 | 20.66 | 122.67 | 338.17 |
October | 329.00 | 0.76 | 0.75 | 01-OCT-06:49 | 1451.27 | 23.28 | 157.00 | 317.17 | 1692.42 | 22.97 | 160.33 | 319.00 |
November | 284.17 | 0.76 | 0.75 | 01-NOV-06:49 | 1458.20 | 26.24 | 169.83 | 281.67 | 1519.84 | 25.98 | 174.00 | 280.33 |
December | 265.67 | 0.76 | 0.75 | 01-DEC-07:49 | 1919.03 | 27.73 | 153.00 | 268.67 | 2000.86 | 28.42 | 157.50 | 269.67 |
Annual Sum or Average | 4149.83 | 0.76 | 1291.61 | 22.41 | 1751.33 | 3987.83 | 1444.30 | 22.32 | 1738.33 | 3991.67 | ||
Minimum of Months | 265.67 | 0.76 | 0.75 | 861.38 | 20.43 | 86.83 | 268.67 | 1089.34 | 19.75 | 77.33 | 269.67 | |
Maximum of Months | 412.83 | 0.76 | 0.75 | 1919.03 | 27.73 | 177.67 | 386.50 | 2000.86 | 28.42 | 174.00 | 394.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278143E+11 | 46625.21 | 17-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201022E+11 | 58924.50 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.985473E+10 | 60863.93 | 06-MAR-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274302E+10 | 28102.77 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.562535E+09 | 21425.38 | 07-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17364582.89 | 13462.90 | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368431E+10 | 35912.20 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113588E+11 | 38927.13 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285834E+11 | 74884.58 | 22-DEC-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285834E+11 | 74884.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139227E+11 | 25699.25 | 20-JAN-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.979771E+10 | 25877.85 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364388E+10 | 20395.26 | 05-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625182E+09 | 11867.68 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44238519.72 | 4868.85 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114597E+10 | 19031.50 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448609E+10 | 23828.69 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140000E+11 | 25819.92 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140000E+11 | 25877.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.322556E+09 | 0.322556E+09 | 12387.04 | 14-FEB-14:00 | 12387.04 | 0.00 |
March | 0.00 | 0.00 | 0.103673E+10 | 0.103651E+10 | 18632.68 | 08-MAR-14:00 | 18632.68 | 0.00 |
April | 0.00 | 0.00 | 0.926905E+10 | 0.926454E+10 | 30164.45 | 13-APR-17:02 | 30164.45 | 0.00 |
May | 0.00 | 0.00 | 0.205419E+11 | 0.200812E+11 | 38693.47 | 19-MAY-17:03 | 38693.47 | 0.00 |
June | 0.00 | 0.00 | 0.430527E+11 | 0.414868E+11 | 56748.83 | 28-JUN-17:03 | 56748.83 | 0.00 |
July | 0.00 | 0.00 | 0.611539E+11 | 0.524875E+11 | 58135.81 | 21-JUL-17:08 | 58135.81 | 0.00 |
August | 0.00 | 0.00 | 0.543292E+11 | 0.465942E+11 | 60867.84 | 22-AUG-04:01 | 46396.03 | 0.00 |
September | 0.00 | 0.00 | 0.341598E+11 | 0.302622E+11 | 42605.81 | 05-SEP-12:55 | 26836.09 | 0.00 |
October | 0.00 | 0.00 | 0.123430E+11 | 0.114035E+11 | 36972.62 | 11-OCT-11:53 | 29440.91 | 0.00 |
November | 0.00 | 0.00 | 42140776.10 | 39588246.51 | 7283.27 | 09-NOV-14:00 | 7027.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236251E+12 | 0.212979E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.611539E+11 | 0.524875E+11 | 60867.84 | 58135.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.187397E+09 | 0.187340E+09 | 6927.35 | 14-FEB-16:08 | 6927.35 | 0.00 |
March | 0.00 | 0.00 | 0.780619E+09 | 0.778159E+09 | 8230.58 | 08-MAR-16:07 | 8230.58 | 0.00 |
April | 0.00 | 0.00 | 0.620205E+10 | 0.618400E+10 | 40161.67 | 28-APR-03:11 | 37652.74 | 0.00 |
May | 0.00 | 0.00 | 0.143809E+11 | 0.137128E+11 | 40161.67 | 21-MAY-03:52 | 26430.98 | 0.00 |
June | 0.00 | 0.00 | 0.293830E+11 | 0.279501E+11 | 40161.67 | 22-JUN-01:32 | 32649.87 | 0.00 |
July | 0.00 | 0.00 | 0.415662E+11 | 0.354299E+11 | 40544.60 | 04-JUL-00:42 | 26432.09 | 0.00 |
August | 0.00 | 0.00 | 0.363567E+11 | 0.306799E+11 | 40161.67 | 20-AUG-01:22 | 32091.00 | 0.00 |
September | 0.00 | 0.00 | 0.229938E+11 | 0.196111E+11 | 40161.67 | 23-SEP-03:11 | 20926.04 | 0.00 |
October | 0.00 | 0.00 | 0.830011E+10 | 0.740803E+10 | 40161.67 | 01-OCT-03:11 | 26161.34 | 0.00 |
November | 0.00 | 0.00 | 93210989.52 | 79013884.94 | 5915.03 | 09-NOV-14:00 | 5384.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160244E+12 | 0.142020E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.415662E+11 | 0.354299E+11 | 40544.60 | 37652.74 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9133.73 | 17532.66 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 9218.32 | 17557.44 | 14-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 9078.78 | 17404.45 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 8558.06 | 16637.81 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8006.69 | 15678.67 | 01-MAY-18:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 7501.20 | 14521.41 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 7069.46 | 13635.52 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 7076.88 | 13411.29 | 31-AUG-18:55 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 7250.45 | 14029.07 | 28-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 7685.44 | 15081.64 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 8256.53 | 16206.16 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 8773.46 | 17061.68 | 29-DEC-07:35 |
Annual Sum or Average | 0.00 | 8127.83 | ||||
Minimum of Months | 0.00 | 0.00 | 7069.46 | 13411.29 | ||
Maximum of Months | 0.00 | 0.00 | 9218.32 | 17557.44 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.27 | 824.13 | 01-JAN-00:01 | 0.32 |
February | 0.166268E+10 | 0.27 | 824.13 | 01-FEB-00:01 | 0.32 |
March | 0.184900E+10 | 0.27 | 824.13 | 01-MAR-00:01 | 0.32 |
April | 0.185850E+10 | 0.28 | 824.13 | 01-APR-04:01 | 0.32 |
May | 0.200798E+10 | 0.29 | 824.13 | 01-MAY-03:02 | 0.32 |
June | 0.201067E+10 | 0.30 | 824.13 | 01-JUN-00:40 | 0.32 |
July | 0.210881E+10 | 0.30 | 824.13 | 01-JUL-00:12 | 0.32 |
August | 0.210494E+10 | 0.30 | 824.13 | 01-AUG-00:12 | 0.32 |
September | 0.202067E+10 | 0.30 | 824.13 | 01-SEP-00:12 | 0.32 |
October | 0.196027E+10 | 0.28 | 824.13 | 01-OCT-00:35 | 0.32 |
November | 0.179268E+10 | 0.27 | 824.13 | 01-NOV-02:55 | 0.32 |
December | 0.183946E+10 | 0.27 | 824.13 | 01-DEC-00:02 | 0.32 |
Annual Sum or Average | 0.230551E+11 | 0.28 | |||
Minimum of Months | 0.166268E+10 | 0.27 | 824.13 | 0.32 | |
Maximum of Months | 0.210881E+10 | 0.30 | 824.13 | 0.32 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.809166E+10 | 0.93 | 4906.28 | 17-JAN-05:01 | 1.34 |
February | 0.712036E+10 | 0.92 | 5367.44 | 06-FEB-05:01 | 1.41 |
March | 0.741826E+10 | 0.88 | 5440.16 | 06-MAR-06:45 | 1.42 |
April | 0.692423E+10 | 0.86 | 4211.77 | 08-APR-05:03 | 1.23 |
May | 0.706985E+10 | 0.85 | 3961.40 | 07-MAY-05:03 | 1.19 |
June | 0.693660E+10 | 0.86 | 5230.87 | 28-JUN-17:03 | 1.39 |
July | 0.729192E+10 | 0.86 | 5410.19 | 21-JUL-17:08 | 1.41 |
August | 0.715916E+10 | 0.85 | 5385.36 | 22-AUG-04:01 | 1.39 |
September | 0.682142E+10 | 0.85 | 3190.84 | 01-SEP-13:00 | 1.02 |
October | 0.718690E+10 | 0.86 | 4504.59 | 26-OCT-05:03 | 1.28 |
November | 0.724728E+10 | 0.89 | 4617.63 | 27-NOV-06:03 | 1.30 |
December | 0.812050E+10 | 0.93 | 5965.87 | 22-DEC-08:38 | 1.49 |
Annual Sum or Average | 0.873881E+11 | 0.88 | |||
Minimum of Months | 0.682142E+10 | 0.85 | 3190.84 | 1.02 | |
Maximum of Months | 0.812050E+10 | 0.93 | 5965.87 | 1.49 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204192E+10 | 0.58 | 1238.88 | 20-JAN-00:55 | 0.84 |
February | 0.179811E+10 | 0.57 | 1241.85 | 04-FEB-06:03 | 0.84 |
March | 0.187146E+10 | 0.55 | 1150.57 | 05-MAR-06:03 | 0.80 |
April | 0.177102E+10 | 0.56 | 1008.58 | 08-APR-05:03 | 0.74 |
May | 0.183503E+10 | 0.58 | 2027.44 | 09-MAY-04:01 | 1.07 |
June | 0.202079E+10 | 0.63 | 2027.44 | 20-JUN-04:01 | 1.07 |
July | 0.228294E+10 | 0.67 | 2027.44 | 07-JUL-04:01 | 1.06 |
August | 0.212062E+10 | 0.64 | 2027.44 | 13-AUG-04:01 | 1.06 |
September | 0.182471E+10 | 0.61 | 2027.44 | 06-SEP-04:01 | 1.06 |
October | 0.184701E+10 | 0.57 | 1358.99 | 06-OCT-03:11 | 0.88 |
November | 0.182768E+10 | 0.56 | 1207.73 | 27-NOV-05:04 | 0.83 |
December | 0.204320E+10 | 0.58 | 1240.89 | 15-DEC-06:03 | 0.84 |
Annual Sum or Average | 0.232845E+11 | 0.59 | |||
Minimum of Months | 0.177102E+10 | 0.55 | 1008.58 | 0.74 | |
Maximum of Months | 0.228294E+10 | 0.67 | 2027.44 | 1.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 48.89 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 48.02 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 48.30 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 51.40 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 52.58 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 52.89 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:05 | 5.36 | 5.36 | 53.18 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 52.57 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 53.42 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 52.92 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:05 | 5.36 | 5.36 | 51.85 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 48.87 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.02 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 53.42 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 48.89 | 59.91 | 9133.73 | 17532.66 | 30-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 48.02 | 58.73 | 9218.32 | 17557.44 | 14-FEB-07:58 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 48.30 | 58.84 | 9078.78 | 17404.45 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.98 | 49.98 | 8558.06 | 16637.81 | 03-APR-18:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 50.23 | 50.23 | 8006.69 | 15678.67 | 01-MAY-18:30 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.37 | 51.37 | 7501.20 | 14521.41 | 01-JUN-18:15 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.78 | 51.78 | 7069.46 | 13635.52 | 03-JUL-18:57 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.44 | 51.44 | 7076.88 | 13411.29 | 31-AUG-18:55 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.05 | 52.05 | 7250.45 | 14029.07 | 28-SEP-18:28 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 49.71 | 49.71 | 7685.44 | 15081.64 | 31-OCT-18:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.50 | 50.50 | 8256.53 | 16206.16 | 30-NOV-19:55 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 48.87 | 58.38 | 8773.46 | 17061.68 | 29-DEC-07:35 |
Annual Sum or Average | 0.00 | 8127.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.02 | 49.71 | 7069.46 | 13411.29 | ||
Maximum of Months | 0.00 | 0.00 | 52.05 | 59.91 | 9218.32 | 17557.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.809166E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.722597E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.776123E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.980971E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132628E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.196412E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.249427E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.227215E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168048E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109148E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.726147E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.812050E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156558E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.722597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.249427E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.204192E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.185365E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.210446E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.349274E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.565225E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.971902E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.129307E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.113567E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.772415E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.406605E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185569E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204320E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648405E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129307E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.809166E+10 | 0.00 | 0.278143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.712036E+10 | 0.322556E+09 | 0.201022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741826E+10 | 0.103673E+10 | 0.985473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692423E+10 | 0.926905E+10 | 0.274302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.706985E+10 | 0.205419E+11 | 0.562535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693660E+10 | 0.430527E+11 | 17364582.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729192E+10 | 0.611539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.715916E+10 | 0.543292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682142E+10 | 0.341598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.718690E+10 | 0.123430E+11 | 0.368431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724728E+10 | 42140776.10 | 0.113588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.812050E+10 | 0.00 | 0.285834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873881E+11 | 0.236251E+12 | 0.104721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.682142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.812050E+10 | 0.611539E+11 | 0.285834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204192E+10 | 0.00 | 0.139227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179811E+10 | 0.187397E+09 | 0.979771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187146E+10 | 0.780619E+09 | 0.364388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177102E+10 | 0.620023E+10 | 0.625182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183503E+10 | 0.143785E+11 | 44238519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202079E+10 | 0.293576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.228294E+10 | 0.414882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212062E+10 | 0.362851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182471E+10 | 0.229836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184701E+10 | 0.829598E+10 | 0.114597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182768E+10 | 93210989.52 | 0.448609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204320E+10 | 0.00 | 0.140000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232845E+11 | 0.160050E+12 | 0.476658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.228294E+10 | 0.414882E+11 | 0.140000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.809166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.712036E+10 | 0.00 | 0.00 | 0.00 | 0.105609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741826E+10 | 0.00 | 0.00 | 0.00 | 0.342969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692423E+10 | 0.00 | 0.00 | 0.00 | 0.288548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.706985E+10 | 0.00 | 0.00 | 0.00 | 0.619293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693660E+10 | 0.00 | 0.00 | 0.00 | 0.127046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729192E+10 | 0.00 | 0.00 | 0.00 | 0.176508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.715916E+10 | 0.00 | 0.00 | 0.00 | 0.155623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.682142E+10 | 0.00 | 0.00 | 0.00 | 0.998339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.718690E+10 | 0.00 | 0.00 | 0.00 | 0.372791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724728E+10 | 0.00 | 0.00 | 0.00 | 14187943.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.812050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873881E+11 | 0.00 | 0.00 | 0.00 | 0.691701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.682142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.812050E+10 | 0.00 | 0.00 | 0.00 | 0.176508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179811E+10 | 0.00 | 0.00 | 0.00 | 55538957.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187146E+10 | 0.00 | 0.00 | 0.00 | 0.232996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177102E+10 | 0.00 | 0.00 | 0.00 | 0.172172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183503E+10 | 0.00 | 0.00 | 0.00 | 0.381722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202079E+10 | 0.00 | 0.00 | 0.00 | 0.769822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.228294E+10 | 0.00 | 0.00 | 0.00 | 0.106478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212062E+10 | 0.00 | 0.00 | 0.00 | 0.923606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182471E+10 | 0.00 | 0.00 | 0.00 | 0.589943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184701E+10 | 0.00 | 0.00 | 0.00 | 0.221904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182768E+10 | 0.00 | 0.00 | 0.00 | 28016886.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232845E+11 | 0.00 | 0.00 | 0.00 | 0.415560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.228294E+10 | 0.00 | 0.00 | 0.00 | 0.106478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.545481E+11 | 0.00 | 0.00 | 1854064.47 | 0.00 | 0.526378E+10 | 0.231275E+10 | 0.00 | 3.53 |
February | 0.447649E+11 | 0.00 | 0.00 | 7111761.16 | 0.00 | 0.374756E+10 | 0.386051E+10 | 0.00 | 3.62 |
March | 0.358071E+11 | 0.00 | 0.00 | 28738297.41 | 0.00 | 0.537282E+09 | 0.123945E+11 | 0.00 | 3.88 |
April | 0.188746E+11 | 0.00 | 0.00 | 72218601.36 | 0.00 | 69647499.27 | 0.185090E+11 | 0.00 | 4.31 |
May | 0.951329E+10 | 74120549.38 | 0.00 | 0.111356E+09 | 0.00 | 20528858.81 | 0.194404E+11 | 0.00 | 4.42 |
June | 0.323612E+10 | 0.291800E+10 | 0.00 | 0.101591E+09 | 1354871.49 | 3749994.09 | 0.111530E+11 | 0.00 | 4.21 |
July | 0.930951E+09 | 0.630187E+10 | 0.00 | 53378910.45 | 15143688.68 | 0.00 | 0.460990E+10 | 0.00 | 4.17 |
August | 0.121928E+10 | 0.360880E+10 | 0.00 | 85354089.79 | 4304744.73 | 0.00 | 0.814275E+10 | 0.00 | 4.32 |
September | 0.329202E+10 | 0.563953E+09 | 0.00 | 0.138387E+09 | 0.00 | 0.00 | 0.169782E+11 | 0.00 | 4.57 |
October | 0.189870E+11 | 30251486.80 | 0.00 | 83571528.86 | 0.00 | 0.144221E+09 | 0.206094E+11 | 0.00 | 4.35 |
November | 0.416782E+11 | 0.00 | 0.00 | 9269859.26 | 0.00 | 0.489085E+09 | 0.841379E+10 | 0.00 | 3.58 |
December | 0.579718E+11 | 0.00 | 0.00 | 54699.41 | 0.00 | 0.509566E+10 | 0.355904E+09 | 0.00 | 3.52 |
Annual Sum or Average | 0.290823E+12 | 0.134970E+11 | 0.00 | 0.692886E+09 | 20803304.90 | 0.153715E+11 | 0.126780E+12 | 0.00 | 4.04 |
Minimum of Months | 0.930951E+09 | 0.00 | 0.00 | 54699.41 | 0.00 | 0.00 | 0.355904E+09 | 0.00 | 3.52 |
Maximum of Months | 0.579718E+11 | 0.630187E+10 | 0.00 | 0.138387E+09 | 15143688.68 | 0.526378E+10 | 0.206094E+11 | 0.00 | 4.57 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556981E+11 | 0.00 | 0.00 | 1176751.10 | 0.00 | 0.00 | 0.295521E+10 | 0.00 | 8.57 |
February | 0.445928E+11 | 0.00 | 0.00 | 6854230.70 | 0.00 | 0.00 | 0.506610E+10 | 0.00 | 8.61 |
March | 0.313974E+11 | 0.00 | 0.00 | 27993590.59 | 0.00 | 0.00 | 0.160706E+11 | 0.00 | 8.71 |
April | 0.162656E+11 | 0.00 | 0.00 | 68171552.84 | 0.00 | 0.00 | 0.223067E+11 | 0.00 | 8.85 |
May | 0.634368E+10 | 161311.32 | 0.00 | 0.111948E+09 | 0.00 | 0.00 | 0.251190E+11 | 0.00 | 8.98 |
June | 0.148134E+10 | 0.370670E+09 | 0.00 | 0.145882E+09 | 0.00 | 0.00 | 0.171222E+11 | 0.00 | 9.13 |
July | 79079117.88 | 0.791567E+09 | 0.00 | 0.153179E+09 | 0.00 | 0.00 | 0.909214E+10 | 0.00 | 9.32 |
August | 0.134232E+09 | 0.222934E+09 | 0.00 | 0.163266E+09 | 0.00 | 0.00 | 0.130307E+11 | 0.00 | 9.30 |
September | 0.934533E+09 | 3241650.51 | 0.00 | 0.145239E+09 | 0.00 | 0.00 | 0.215718E+11 | 0.00 | 9.14 |
October | 0.155852E+11 | 0.00 | 0.00 | 79163908.09 | 0.00 | 0.00 | 0.233334E+11 | 0.00 | 8.90 |
November | 0.366125E+11 | 0.00 | 0.00 | 9589002.57 | 0.00 | 0.00 | 0.115695E+11 | 0.00 | 8.60 |
December | 0.581079E+11 | 0.00 | 0.00 | 234087.39 | 0.00 | 0.00 | 0.922533E+09 | 0.00 | 8.56 |
Annual Sum or Average | 0.267232E+12 | 0.138857E+10 | 0.00 | 0.912698E+09 | 0.00 | 0.00 | 0.168160E+12 | 0.00 | 8.89 |
Minimum of Months | 79079117.88 | 0.00 | 0.00 | 234087.39 | 0.00 | 0.00 | 0.922533E+09 | 0.00 | 8.56 |
Maximum of Months | 0.581079E+11 | 0.791567E+09 | 0.00 | 0.163266E+09 | 0.00 | 0.00 | 0.251190E+11 | 0.00 | 9.32 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:33
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.544072E+11 | 0.160475E+11 | 0.190997E+12 | 35959640.97 | 0.287944E+11 |
February | 0.718858E+11 | 0.142402E+11 | 0.162103E+12 | 0.549715E+09 | 0.254068E+11 |
March | 0.101896E+12 | 0.135364E+11 | 0.155135E+12 | 0.266900E+10 | 0.275246E+11 |
April | 0.135442E+12 | 0.111919E+11 | 0.128590E+12 | 0.504029E+10 | 0.444350E+11 |
May | 0.147567E+12 | 0.947322E+10 | 0.110017E+12 | 0.526248E+10 | 0.712718E+11 |
June | 0.139294E+12 | 0.591052E+10 | 0.639318E+11 | 0.313624E+10 | 0.120690E+12 |
July | 0.140601E+12 | 0.381860E+10 | 0.290035E+11 | 0.150008E+10 | 0.160158E+12 |
August | 0.134067E+12 | 0.508162E+10 | 0.458106E+11 | 0.255188E+10 | 0.144097E+12 |
September | 0.104435E+12 | 0.642433E+10 | 0.825673E+11 | 0.514373E+10 | 0.995831E+11 |
October | 0.797674E+11 | 0.101928E+11 | 0.133132E+12 | 0.550712E+10 | 0.509721E+11 |
November | 0.603466E+11 | 0.133263E+11 | 0.159907E+12 | 0.560547E+09 | 0.219741E+11 |
December | 0.496914E+11 | 0.161424E+11 | 0.192769E+12 | 0.00 | 0.274737E+11 |
Annual Sum or Average | 0.121940E+13 | 0.125386E+12 | 0.145396E+13 | 0.319570E+11 | 0.822381E+12 |
Minimum of Months | 0.496914E+11 | 0.381860E+10 | 0.290035E+11 | 0.00 | 0.219741E+11 |
Maximum of Months | 0.147567E+12 | 0.161424E+11 | 0.192769E+12 | 0.550712E+10 | 0.160158E+12 |