Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:28:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1987.43 | 3888.12 | 3888.12 |
Net Site Energy | 1987.43 | 3888.12 | 3888.12 |
Total Source Energy | 4749.23 | 9291.21 | 9291.21 |
Net Source Energy | 4749.23 | 9291.21 | 9291.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 434.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 146.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.38 | 262.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1245.73 | 741.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 434.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 146.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.38 | 262.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 434.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 146.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.38 | 262.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 55.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1284.45 | 531.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 988.30 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2437.10 | 1451.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1284.45 | 531.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 988.30 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2437.10 | 1451.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1245.733 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1245.733 | 100.00 |
Total On-Site and Utility Electric Sources | 1245.733 | 100.00 |
Total Electricity End Uses | 1245.733 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1500.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6102.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.9552 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.1538 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.9552 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.1538 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.2821 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-18:10 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 06-MAR-07:00 |
Heating | 0.00 | 26957.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48354.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18727.72 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4436.43 | 17416.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1965.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 86025.67 | 57951.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 26957.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48354.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 17700.22 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4436.43 | 17416.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 695.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 10.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1375.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 463.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.73 | 284.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 174.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3945.24 | 804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2691.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 906.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.05 | 556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 341.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7718.30 | 1572.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2691.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 180.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 906.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.05 | 556.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 341.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7718.30 | 1572.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.46 |
KITCHEN DIRECT AIR | 1.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 1.00 | 1.00 | 4.46 |
PSZ-AC_2:2 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.68 | 1.00 | 1.00 | 1.68 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.46 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.68 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.46 | 7557.36 |
PSZ-AC_2:2_ADDAQ FAN | 1.68 | 1794.83 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.46 | 4.46 | 4.46 | 2.94 | 110675.41 | 122964.50 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 41652.30 | 70092.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.46 | 2.23 | 2.97 | 110675.41 | 55337.71 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.68 | 0.838669 | 1.12 | 41652.30 | 20826.15 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 122964.50 |
PSZ-AC_2:2 HEATING COIL | 70092.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.955 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.883 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.154 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1068.794 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2585.575 | 6.955 | 9.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2585.575 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1136.687 | 8.154 | 150.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1136.687 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.8711E-004 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.7631E-003 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.1727E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.4757E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.4675E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.1376E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.8584E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.2816E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.4042E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.3236E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5535E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4594E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.6655E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.6237E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.4376E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.4378E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.4636E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.3669E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.9174E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.3290E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.4050E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.9640E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.2816E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8584E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 49638.37541 | 59566.05049 | 3.71408 | 4.45690 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 3640.75108 | 4368.90129 | 0.16009 | 1.33138 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 6.30000 | 6.07234E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22023.84662 | 26428.61595 | 1.39778 | 1.67734 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 6.30000 | 6.07234E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 87084.24 | 4.45690 | 4.45690 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 52920.60 | 1.33138 | 1.33138 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 47889.32 | 1.67734 | 1.67734 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 48374.32 | 1.21700 | 1.21700 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.45690 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67734 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.45690 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.45690 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.45690 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.45690 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.45690 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.45690 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67734 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67734 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67734 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67734 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67734 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67734 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.45690 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.67734 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.45690 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.45690 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7557.36002 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.45690 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.45690 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.45690 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.94155 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.45690 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.22845 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.97127 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 110675.41000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 55337.70500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 110675.41000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 122964.50022 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 122964.50022 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67734 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67734 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1794.83103 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67734 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67734 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67734 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10704 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67734 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83867 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11823 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41652.30000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20826.15000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41652.30000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 70092.76235 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 70092.76235 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 107507.6 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40460.1 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1014096861 | 0.2506392167 | Pass | Pass | 0.1347666875 | 0.6421143616 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2439492716 | 0.7131285968 | Pass | Pass | 2.2518993055E-002 | 8.8571036408E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4162073335 | 0.4153891789 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 974.17 | -27.0 | -227.7 | 46.19 | 2373.00 | 3138.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.9552 | 371.75 | 2585.58 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.43 | 0.0000 | Y | 38.55 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.1538 | 139.41 | 1136.69 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 16.28 |
Interior Lighting Total | 7.2821 | 511.15 | 3722.26 | 54.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2585.58 | 646.39 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2585.58 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 159.78 | AstronomicalClock | - | 48.75 | 48.75 | 1.46 | |
EXTERIOR_LIGHTS_B | 2015.63 | AstronomicalClock | - | 83.75 | 73.25 | 27.72 | |
Exterior Lighting Total | 2175.41 | 29.18 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 110675.41 | 77592.32 | 33083.09 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41652.30 | 29201.59 | 12450.71 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 107507.6 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 40460.1 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 122964.50 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 70092.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.46 | 7557.36 | 1695.65 | 1.00 | 1.18 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1794.83 | 1070.05 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 49638.38 | 59566.05 | 160.23 | 3.714 | 4.457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 23.99 | 0.00853 | 41.90 | 0.00916 | 1.331 | 0.00 |
KITCHEN | 22023.85 | 26428.62 | 189.58 | 1.398 | 1.677 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 26.00 | 25.99 | 0.00876 | 41.13 | 0.00916 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3640.75 | 4368.90 | 11.75 | 0.160 | 1.331 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 25.15 | 0.00361 | 6.30 | 0.00607 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.46 | 4.46 | 1.33 | 1.33 | 4.4569 | 4.4569 | 4.4569 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.68 | 1.68 | 1.22 | 1.22 | 1.6773 | 1.6773 | 1.6773 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 110675.410 | 77592.316 | 4.456900 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 55337.71 | 45921.27 | 2.971267 | 29.37 | 18.13 | 0.00871610 | 11.39 | 9.72 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 44.8084 | 23.99 | 0.00852788 | 44.7762 | 49629.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 122964.500 | 122964.500 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 122964.50 | 122964.50 | 4.456899 | 16.61 | 12.34 | 0.00740160 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 29.8723 | 21.00 | 0.00796783 | 50.2125 | 3626.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41652.300 | 29201.594 | 1.677340 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 20826.15 | 17722.99 | 1.118227 | 38.14 | 21.10 | 0.00906397 | 11.91 | 9.95 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 108.8332 | 25.99 | 0.00876723 | 40.8505 | 22023.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 70092.762 | 70092.762 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 70092.76 | 70092.76 | 1.677338 | 4.57 | 4.57 | 0.00539739 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 72.5556 | 25.15 | 0.00361299 | 17.8327 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 110675.410 | 77592.316 | 4.456900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0428 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.456899 | 5.23144315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | Sensible | 55337.71 | 45921.27 | 1.0000 | 3.48762961 | 2.971267 | 29.37 | 18.13 | 0.00871610 | 51783.8 | 11.39 | 9.72 | 0.00700000 | 29095.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55337.71 | 42.00 | 0.00915790 | 22.26 | 1.33137743 | 44.8084 | 23.99 | 0.00852788 | 23.99 | 0.00852788 | 44.7762 | 49629.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 122964.500 | 122964.500 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.456899 | 5.23144315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 122964.50 | 122964.50 | 1.0000 | 5.23144315 | 4.456899 | 16.61 | 12.34 | 0.00740160 | 35428.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 122964.50 | 6.30 | 0.00607234 | 6.30 | 1.33137743 | 29.8723 | 21.00 | 0.00796783 | 21.00 | 0.00796783 | 50.2125 | 3626.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41652.300 | 29201.594 | 1.677340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6895 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.677338 | 1.96883505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | Sensible | 20826.15 | 17722.99 | 1.0000 | 1.31255820 | 1.118227 | 38.14 | 21.10 | 0.00906397 | 61635.9 | 11.91 | 9.95 | 0.00700000 | 29626.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20826.15 | 42.00 | 0.00915790 | 22.26 | 1.21700195 | 108.8332 | 25.95 | 0.00876723 | 25.99 | 0.00876723 | 40.8505 | 22023.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 70092.762 | 70092.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.677338 | 1.96883505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 70092.76 | 70092.76 | 1.0000 | 1.96883505 | 1.677338 | 4.57 | 4.57 | 0.00539739 | 18137.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70092.76 | 6.30 | 0.00607234 | 6.30 | 1.21700195 | 72.5556 | 0.00 | 0.00361299 | 25.15 | 0.00361299 | 17.8327 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 5890.83 | 3406.33 | 2495.17 |
KITCHEN | 6766.83 | 6420.33 | 6095.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6774.17 | 6991.33 | 6102.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 1.00 | 0.00 | 1.00 |
KITCHEN | 0.00 | 1774.00 | 0.00 | 1500.67 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1774.00 | 0.00 | 1500.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.365 | 0.879 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.261 | 0.012 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 3.993 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.914 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 34999216.14 | 0.00 | 34999216.14 | 6968875.75 | 41968091.90 | 41986318.57 | 1459.77 | 7300.23 | 0.00 | 117.76 |
KITCHEN | 31524339.80 | 0.00 | 31524339.80 | 50073.48 | 31574413.28 | 38379373.44 | 5236.61 | 3501.07 | 22.33 | 925.64 |
Total Facility | 66523555.95 | 0.00 | 66523555.95 | 7018949.23 | 73542505.18 | 80365692.01 | 5261.04 | 7302.34 | 22.33 | 927.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3316 | 0.0000 | 1.3316 | 0.2685 | 1.6000 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1629 | 0.0000 | 1.1629 | 0.0014 | 1.1643 | 1.2170 | 3708.28 | 3478.72 | 0.00 |
Total Facility | 2.4945 | 0.0000 | 2.4945 | 0.2699 | 2.7644 | 2.5484 | 3708.28 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48218622.89 | 0.00 | 48218622.89 | 41986318.57 | 1459.51 | 0.00 | 7300.49 | 117.76 |
PSZ-AC_2:2 | 43432339.35 | 0.00 | 43432339.35 | 38379373.44 | 1394.89 | 2.77 | 7362.34 | 925.64 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8345 | 0.0000 | 1.8345 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6022 | 0.0000 | 1.6022 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4.53 | 0.00 | 7300.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 4809.86 | 3302.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.8345 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.6598 | 1.5349 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
Electricity:Building | 511.75 | 3281.23 | 01-JAN-01:10 | 28991.58 | 02-JAN-11:10 |
Electricity:Zone:DINING | 163.83 | 856.89 | 01-JAN-01:10 | 8683.37 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 504.82 | 3144.96 | 01-JAN-01:10 | 26848.48 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.83 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 38.55 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 54.83 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 38.55 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 347.92 | 2424.34 | 01-JAN-01:10 | 20308.21 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 55.18 | 888.84 | 31-DEC-23:30 | 3219.34 | 17-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 124.08 | 1064.43 | 21-DEC-01:10 | 6553.34 | 28-AUG-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.61 | 0.00 | 01-JAN-11:10 | 1532.34 | 29-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 32.63 | 779.34 | 21-DEC-06:00 | 1076.23 | 02-JAN-14:40 |
ElectricityPurchased:Facility | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
ElectricityPurchased:Plant | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
Cogeneration:ElectricityPurchased | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
ElectricityNet:Plant | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
Cogeneration:ElectricityNet | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
General:Cogeneration:ElectricityNet | 1245.73 | 5756.60 | 21-DEC-01:10 | 86025.67 | 10-JUN-18:10 |
Electricity:HVAC | 580.72 | 0.00 | 01-JAN-01:10 | 58389.09 | 10-JUN-18:10 |
Fans:Electricity | 146.36 | 0.00 | 01-JAN-01:10 | 10176.32 | 22-JUN-17:10 |
General:Fans:Electricity | 146.36 | 0.00 | 01-JAN-01:10 | 10176.32 | 22-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 434.36 | 0.00 | 01-JAN-00:10 | 48354.39 | 10-JUN-18:10 |
General:Cooling:Electricity | 434.36 | 0.00 | 01-JAN-00:10 | 48354.39 | 10-JUN-18:10 |
ExteriorLights:Electricity | 29.18 | 0.00 | 01-JAN-07:20 | 2175.41 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 29.18 | 0.00 | 01-JAN-07:20 | 2175.41 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4741.58 | 23-JAN-07:40 |
Water Heater:WaterSystems:Electricity | 75.38 | 0.00 | 01-JAN-01:10 | 4741.58 | 23-JAN-07:40 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-MAR-14:40 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 30-MAR-14:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 741.69 | 2758.01 | 01-JAN-01:10 | 57951.44 | 03-JAN-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 9.68 | 0.00 | 01-JAN-01:10 | 31470.83 | 01-JAN-06:10 |
Heating:NaturalGas | 9.68 | 0.00 | 01-JAN-01:10 | 31470.83 | 01-JAN-06:10 |
General:Heating:NaturalGas | 9.68 | 0.00 | 01-JAN-01:10 | 31470.83 | 01-JAN-06:10 |
NaturalGas:Plant | 262.22 | 947.76 | 01-JAN-01:10 | 18629.68 | 17-JAN-19:20 |
WaterSystems:NaturalGas | 262.22 | 947.76 | 01-JAN-01:10 | 18629.68 | 17-JAN-19:20 |
Water Heater:WaterSystems:NaturalGas | 262.22 | 947.76 | 01-JAN-01:10 | 18629.68 | 17-JAN-19:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-MAR-18:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 28-MAR-18:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 06-MAR-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2786.93 | 3112.44 | 21-DEC-01:10 | 223909.18 | 28-AUG-18:10 |
EnergyTransfer:Building | 901.52 | 1556.22 | 21-DEC-01:10 | 60267.73 | 08-JUN-17:40 |
EnergyTransfer:Zone:KITCHEN | 461.88 | 1556.22 | 21-DEC-01:10 | 24683.11 | 05-JUN-10:40 |
Refrigeration:EnergyTransfer | 158.32 | 2838.37 | 31-DEC-23:30 | 7834.84 | 13-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.16 | 1419.19 | 31-DEC-23:30 | 3917.42 | 13-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 79.16 | 1419.19 | 31-DEC-23:30 | 3917.42 | 13-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 79.16 | 1419.19 | 31-DEC-23:30 | 3917.42 | 13-JAN-04:50 |
EnergyTransfer:Plant | 256.28 | 1556.22 | 21-DEC-01:10 | 15998.94 | 18-JAN-19:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.48 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.68 | 1348.03 | 21-DEC-06:00 | 2238.70 | 02-JAN-14:40 |
EnergyTransfer:Zone:DINING | 439.65 | 0.00 | 01-JAN-01:10 | 40145.60 | 07-JUN-17:10 |
Heating:EnergyTransfer | 2.99 | 0.00 | 01-JAN-00:10 | 14789.70 | 03-MAY-23:10 |
Heating:EnergyTransfer:Zone:DINING | 2.99 | 0.00 | 01-JAN-00:10 | 14789.70 | 03-MAY-23:10 |
General:Heating:EnergyTransfer | 2.99 | 0.00 | 01-JAN-00:10 | 14789.70 | 03-MAY-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.99 | 0.00 | 01-JAN-00:10 | 14789.70 | 03-MAY-23:10 |
Cooling:EnergyTransfer | 819.37 | 0.00 | 01-JAN-01:10 | 57706.72 | 08-JUN-17:40 |
Cooling:EnergyTransfer:Zone:DINING | 436.66 | 0.00 | 01-JAN-01:10 | 40145.60 | 07-JUN-17:10 |
General:Cooling:EnergyTransfer | 819.37 | 0.00 | 01-JAN-01:10 | 57706.72 | 08-JUN-17:40 |
General:Cooling:EnergyTransfer:Zone:DINING | 436.66 | 0.00 | 01-JAN-01:10 | 40145.60 | 07-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 304.86 | 06-MAY-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 304.86 | 06-MAY-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 382.71 | 0.00 | 01-JAN-01:10 | 20813.74 | 05-JUN-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 382.71 | 0.00 | 01-JAN-01:10 | 20813.74 | 05-JUN-10:40 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
WaterSystems:PlantLoopHeatingDemand | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
EnergyTransfer:HVAC | 1629.13 | 0.00 | 01-JAN-01:10 | 163055.39 | 25-AUG-11:10 |
HeatingCoils:EnergyTransfer | 7.75 | 0.00 | 01-JAN-01:10 | 25176.66 | 01-JAN-06:10 |
CoolingCoils:EnergyTransfer | 1621.38 | 0.00 | 01-JAN-00:10 | 163055.39 | 25-AUG-11:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 177.12 | 0.00 | 01-JAN-01:10 | 13400.86 | 18-JAN-07:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.989 | -436.653 | 0.000 | 0.000 | 208.914 | 38.554 | 93.957 | 45.087 | 0.000 | 38.690 | 37.348 | 0.000 | -10.403 | 0.000 | -18.483 | -0.001 |
KITCHEN | 0.000 | 0.000 | 0.000 | -382.707 | 0.000 | 0.000 | 4.638 | 16.277 | 287.132 | 0.000 | 0.000 | 0.152 | 74.710 | 0.000 | 0.000 | 0.000 | -0.202 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.585 | 31.471 | 0.000 | 0.000 | 0.000 | -48.056 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.990 | -819.360 | 0.000 | 0.000 | 213.552 | 54.830 | 381.090 | 45.087 | 0.000 | 55.427 | 143.528 | 0.000 | -10.403 | 0.000 | -66.741 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 30-MAY-04:01 | 0.00 | 0.00 | 0.00 | -63816.53 | 0.00 | 0.00 | 701.63 | 498.89 | 2172.30 | 51.65 | 0.00 | 12.42 | 60379.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | -50230.54 | 0.00 | 0.00 | 6.35 | 178.91 | 6916.85 | 0.00 | 0.00 | 0.00 | 43128.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-MAY-04:01 | 0.00 | 0.00 | 0.00 | -98369.92 | 0.00 | 0.00 | 701.01 | 677.80 | 9089.15 | 0.00 | 0.00 | 1222.94 | 86752.02 | 0.00 | -73.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-MAY-23:01 | 0.00 | 0.00 | 19671.83 | 0.00 | 0.00 | 0.00 | 973.89 | 374.16 | 543.07 | 961.39 | 0.00 | 366.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22890.45 |
KITCHEN | 06-MAY-04:03 | 0.00 | 0.00 | 2133.78 | 0.00 | 0.00 | 0.00 | 0.00 | 134.19 | 6916.85 | 0.00 | 0.00 | 3.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9188.03 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAY-23:01 | -9607.16 | 9607.16 | 19671.83 | -9607.16 | 0.00 | 0.00 | 996.37 | 508.34 | 3042.91 | 961.39 | 0.00 | 1521.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17095.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4569 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4569 | 0.2987 | 1.0000 | Not calculated | 1.3314 | 0.2987 | ||
PSZ-AC_2:2 | 1.6773 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6773 | 0.1089 | 1.0000 | Not calculated | 0.1826 | 0.1089 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.4569 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.4569 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2987 | ||
PSZ-AC_2:2 | 1.6773 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6773 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1089 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4569 | 4.4569 | 4.4569 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6773 | 1.6773 | 1.6773 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4569 | 4.4569 | 4.4569 | 4.4569 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6773 | 1.6773 | 1.6773 | 1.6773 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4569 | 4.4569 | 4.4569 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6773 | 1.6773 | 1.6773 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.4569 | 4.4569 | 4.4569 | 4.4569 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6773 | 1.6773 | 1.6773 | 1.6773 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1500.67 |
Number of hours not met | 1500.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 9.68 | 31470.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 434.36 | 48354.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.83 | 3050.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.18 | 2175.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 146.36 | 10176.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.38 | 4741.58 | 262.22 | 18629.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.61 | 1532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.63 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 505.17 | 1245.73 |
Natural Gas | 469.79 | 741.69 |
Additional | 0.00 | 0.00 |
Total | 974.96 | 1987.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 107.27 |
Space Heating | 0.00 |
Space Cooling | 849.77 |
Fans (All) | 286.33 |
Service Water Heating | 147.47 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 2437.10 |
Subtotal | 2437.10 |
Natural Gas [MJ/m2] | |
Space Heating | 18.94 |
Service Water Heating | 513.01 |
Miscellaneous (All) | 1451.02 |
Subtotal | 1451.02 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.76 |
Space Heating | 0.49 |
Space Cooling | 21.86 |
Fans (All) | 7.36 |
Service Water Heating | 16.99 |
Receptacle Equipment | 46.28 |
Miscellaneous | 4.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7859.00 | 707.17 | 193.83 | 0.00 | 0.00 |
KITCHEN | 5503.67 | 2684.67 | 571.67 | 0.00 | 0.00 |
ATTIC | 4207.67 | 1110.17 | 1136.50 | 1133.17 | 1172.50 |
Min | 4207.67 | 707.17 | 193.83 | 0.00 | 0.00 |
Max | 7859.00 | 2684.67 | 1136.50 | 1133.17 | 1172.50 |
Average | 5856.78 | 1500.67 | 634.00 | 377.72 | 390.83 |
Sum | 17570.33 | 4502.00 | 1902.00 | 1133.17 | 1172.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821898.00 | 1701.00 | 623.00 | 0.00 | 0.00 |
KITCHEN | 14052.67 | 4144.50 | 1035.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821898.00 | 4144.50 | 1035.83 | 0.00 | 0.00 |
Average | 278650.22 | 1948.50 | 552.94 | 0.00 | 0.00 |
Sum | 835950.67 | 5845.50 | 1658.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 5419.17 | 3146.67 | 194.17 | 0.00 | 0.00 |
KITCHEN | 2256.50 | 6316.17 | 187.33 | 0.00 | 0.00 |
ATTIC | 3467.17 | 2266.67 | 912.00 | 503.67 | 1610.50 |
Min | 2256.50 | 2266.67 | 187.33 | 0.00 | 0.00 |
Max | 5419.17 | 6316.17 | 912.00 | 503.67 | 1610.50 |
Average | 3714.28 | 3909.83 | 431.17 | 167.89 | 536.83 |
Sum | 11142.83 | 11729.50 | 1293.50 | 503.67 | 1610.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 561162.00 | 262658.67 | 401.33 | 0.00 | 0.00 |
KITCHEN | 5232.50 | 13633.50 | 367.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 561162.00 | 262658.67 | 401.33 | 0.00 | 0.00 |
Average | 188798.17 | 92097.39 | 256.11 | 0.00 | 0.00 |
Sum | 566394.50 | 276292.17 | 768.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232235E+11 | 22232.83 | 05-JAN-05:01 | 5.75 | 5.56 | 0.141833E+11 | 14051.39 | 14-JAN-19:00 | 18.20 | 13.91 |
February | 0.238762E+11 | 24416.80 | 23-FEB-13:00 | 26.30 | 14.04 | 0.133889E+11 | 14052.34 | 04-FEB-19:30 | 26.30 | 14.04 |
March | 0.323738E+11 | 31787.73 | 28-MAR-17:02 | 34.60 | 18.91 | 0.154476E+11 | 14052.82 | 11-MAR-19:00 | 34.60 | 18.91 |
April | 0.396663E+11 | 37434.84 | 28-APR-04:02 | 27.93 | 17.10 | 0.149211E+11 | 14051.50 | 08-APR-18:00 | 27.93 | 17.10 |
May | 0.462511E+11 | 63845.41 | 30-MAY-04:01 | 30.87 | 21.02 | 0.154572E+11 | 14051.68 | 20-MAY-18:00 | 30.87 | 21.02 |
June | 0.461305E+11 | 61279.50 | 06-JUN-04:01 | 33.18 | 21.26 | 0.150424E+11 | 14051.97 | 24-JUN-18:00 | 27.40 | 25.19 |
July | 0.454060E+11 | 45090.38 | 01-JUL-04:01 | 29.80 | 24.06 | 0.153614E+11 | 15123.06 | 01-JUL-18:49 | 36.20 | 28.67 |
August | 0.442103E+11 | 45387.68 | 03-AUG-04:01 | 28.73 | 23.54 | 0.155511E+11 | 14051.93 | 19-AUG-18:49 | 26.08 | 25.54 |
September | 0.407949E+11 | 51137.59 | 29-SEP-04:01 | 24.00 | 21.14 | 0.149263E+11 | 14052.35 | 09-SEP-18:00 | 24.00 | 21.14 |
October | 0.385891E+11 | 45824.52 | 01-OCT-04:01 | 23.08 | 18.77 | 0.153295E+11 | 14052.88 | 21-OCT-18:00 | 25.60 | 17.80 |
November | 0.307346E+11 | 28919.08 | 09-NOV-13:00 | 29.30 | 18.21 | 0.146311E+11 | 14052.81 | 25-NOV-19:00 | 15.90 | 11.31 |
December | 0.254032E+11 | 23794.73 | 21-DEC-05:01 | 5.03 | 4.11 | 0.144093E+11 | 14052.47 | 02-DEC-19:30 | 5.03 | 4.11 |
Annual Sum or Average | 0.436659E+12 | 0.178649E+12 | ||||||||
Minimum of Months | 0.232235E+11 | 22232.83 | 5.03 | 4.11 | 0.133889E+11 | 14051.39 | 5.03 | 4.11 | ||
Maximum of Months | 0.462511E+11 | 63845.41 | 34.60 | 24.06 | 0.155511E+11 | 15123.06 | 36.20 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298752E+11 | 48639.80 | 27-JAN-05:01 | 11.60 | 10.18 | 0.105541E+11 | 6934.95 | 13-JAN-11:00 | 11.60 | 10.18 |
February | 0.269432E+11 | 48825.87 | 14-FEB-05:01 | 10.35 | 9.69 | 0.955868E+10 | 6934.99 | 09-FEB-11:00 | 10.35 | 9.69 |
March | 0.307870E+11 | 44269.65 | 24-MAR-03:11 | 18.13 | 14.39 | 0.106065E+11 | 6934.94 | 22-MAR-10:39 | 18.13 | 14.39 |
April | 0.317104E+11 | 32643.00 | 28-APR-03:31 | 28.40 | 17.10 | 0.102634E+11 | 6935.03 | 17-APR-10:00 | 28.40 | 17.10 |
May | 0.343714E+11 | 35522.24 | 07-MAY-03:22 | 29.85 | 18.25 | 0.106149E+11 | 6982.11 | 22-MAY-10:50 | 35.68 | 25.74 |
June | 0.334465E+11 | 33014.17 | 02-JUN-04:01 | 27.75 | 19.82 | 0.103092E+11 | 7020.44 | 28-JUN-10:00 | 32.50 | 28.26 |
July | 0.338947E+11 | 25390.58 | 11-JUL-04:01 | 26.73 | 24.05 | 0.106782E+11 | 7027.39 | 17-JUL-10:50 | 34.45 | 27.92 |
August | 0.339076E+11 | 25353.81 | 04-AUG-04:01 | 28.05 | 24.13 | 0.106912E+11 | 7042.03 | 25-AUG-10:50 | 32.72 | 28.77 |
September | 0.332341E+11 | 30722.04 | 29-SEP-04:01 | 24.00 | 21.14 | 0.102937E+11 | 7005.98 | 12-SEP-10:00 | 24.00 | 21.14 |
October | 0.336584E+11 | 40353.51 | 15-OCT-04:01 | 19.48 | 15.86 | 0.106031E+11 | 6937.65 | 04-OCT-10:00 | 19.48 | 15.86 |
November | 0.304602E+11 | 50268.56 | 24-NOV-05:01 | 10.48 | 9.31 | 0.102528E+11 | 6934.94 | 28-NOV-11:20 | 19.80 | 14.44 |
December | 0.304262E+11 | 48596.51 | 15-DEC-05:01 | 10.70 | 10.17 | 0.105654E+11 | 6934.96 | 29-DEC-11:50 | 19.00 | 14.12 |
Annual Sum or Average | 0.382715E+12 | 0.124991E+12 | ||||||||
Minimum of Months | 0.269432E+11 | 25353.81 | 10.35 | 9.31 | 0.955868E+10 | 6934.94 | 10.35 | 9.69 | ||
Maximum of Months | 0.343714E+11 | 50268.56 | 29.85 | 24.13 | 0.106912E+11 | 7042.03 | 35.68 | 28.77 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 | 7.85 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 | 12.96 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 | 16.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 | 18.24 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 | 22.58 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 | 24.65 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 | 21.85 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 | 9.11 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20903699.92 | 8211.89 | 01-JAN-06:03 | 6.60 |
February | 6404370.83 | 4578.64 | 11-FEB-06:03 | 9.30 |
March | 3106914.24 | 3278.67 | 11-MAR-06:05 | 23.80 |
April | 0.277299E+09 | 14806.27 | 27-APR-23:01 | 32.73 |
May | 0.630730E+09 | 19671.81 | 03-MAY-23:01 | 35.95 |
June | 0.712679E+09 | 19400.38 | 13-JUN-23:01 | 35.63 |
July | 0.610581E+09 | 18904.43 | 02-JUL-23:01 | 35.28 |
August | 0.435962E+09 | 13929.29 | 08-AUG-23:01 | 32.07 |
September | 0.251468E+09 | 11054.98 | 17-SEP-23:01 | 30.23 |
October | 28562235.05 | 9743.84 | 22-OCT-23:01 | 29.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 10507285.16 | 5993.42 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.298820E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.712679E+09 | 19671.81 | 35.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 |
May | 463311.28 | 2134.03 | 06-MAY-04:03 | 30.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 463311.28 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 463311.28 | 2134.03 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:01 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332281E+10 | 2244.98 | 02-JAN-17:30 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.298556E+10 | 2244.98 | 01-FEB-17:19 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.329193E+10 | 2244.98 | 01-MAR-18:19 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.311165E+10 | 2244.98 | 01-APR-18:19 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.322202E+10 | 2244.98 | 01-MAY-18:30 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.314231E+10 | 2244.98 | 01-JUN-18:49 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.321411E+10 | 2244.98 | 01-JUL-18:00 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.328938E+10 | 2244.98 | 01-AUG-18:00 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.316248E+10 | 2244.98 | 01-SEP-18:30 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.327696E+10 | 2244.98 | 02-OCT-17:00 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.321141E+10 | 2244.98 | 01-NOV-17:19 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.332292E+10 | 2244.98 | 01-DEC-17:19 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.385535E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.298556E+10 | 2244.98 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.332292E+10 | 2244.98 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137533E+10 | 805.14 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.124570E+10 | 805.14 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.139723E+10 | 805.14 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.133636E+10 | 805.14 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.138628E+10 | 805.14 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.135053E+10 | 805.14 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.137227E+10 | 805.14 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.139723E+10 | 805.14 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.133668E+10 | 805.14 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.137517E+10 | 805.14 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.133137E+10 | 805.14 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.137243E+10 | 805.14 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.162766E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.124570E+10 | 805.14 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.139723E+10 | 805.14 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.332281E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591174E+10 |
February | 0.272721E+11 | 0.298556E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85278959.96 | 0.327341E+10 |
March | 0.305458E+11 | 0.329193E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132947E+10 | 0.121404E+10 |
April | 0.292871E+11 | 0.311165E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486941E+10 | 98913857.98 |
May | 0.303219E+11 | 0.322202E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739194E+10 | 3287998.24 |
June | 0.295292E+11 | 0.314231E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733621E+10 | 1105848.22 |
July | 0.300798E+11 | 0.321411E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580551E+10 | 933388.05 |
August | 0.305458E+11 | 0.328938E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479562E+10 | 1036449.51 |
September | 0.292871E+11 | 0.316248E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394221E+10 | 2380105.27 |
October | 0.300980E+11 | 0.327696E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250196E+10 | 0.480393E+09 |
November | 0.290996E+11 | 0.321141E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629815E+09 | 0.223669E+10 |
December | 0.300798E+11 | 0.332292E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2844523.49 | 0.525865E+10 |
Annual Sum or Average | 0.356244E+12 | 0.385535E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386903E+11 | 0.184826E+11 |
Minimum of Months | 0.272721E+11 | 0.298556E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933388.05 |
Maximum of Months | 0.305458E+11 | 0.332292E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739194E+10 | 0.591174E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.137533E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40238476.66 |
February | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 28063.59 | 45576344.69 |
March | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 4106322.48 | 38753783.23 |
April | 0.786997E+09 | 0.133636E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 22170183.60 | 4651406.38 |
May | 0.814802E+09 | 0.138628E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 42040534.22 | 5338335.30 |
June | 0.793501E+09 | 0.135053E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 28148065.05 | 2373795.22 |
July | 0.808298E+09 | 0.137227E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 24797826.69 | 4279928.64 |
August | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12692424.61 | 3920309.83 |
September | 0.786997E+09 | 0.133668E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 10659791.11 | 4356653.44 |
October | 0.808786E+09 | 0.137517E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 6122177.88 | 3790157.99 |
November | 0.781956E+09 | 0.133137E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 861153.09 | 10974419.60 |
December | 0.808298E+09 | 0.137243E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37666588.67 |
Annual Sum or Average | 0.957291E+10 | 0.162766E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.151627E+09 | 0.201920E+09 |
Minimum of Months | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2373795.22 |
Maximum of Months | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 42040534.22 | 45576344.69 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168677E+10 | 0.298913E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126248E+10 | 0.317310E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131743E+10 | 0.452291E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154072E+10 | 0.513986E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129249E+10 | 0.521546E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125828E+10 | 0.516277E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758416E+09 | 0.401121E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767004E+09 | 0.381943E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115101E+10 | 0.333105E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177622E+10 | 0.417173E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189355E+10 | 0.346572E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188110E+10 | 0.305401E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165855E+11 | 0.480564E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758416E+09 | 0.298913E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189355E+10 | 0.521546E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2244.98 | 02-JAN-17:30 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7798.52 | 07-JAN-19:53 |
February | 30255.31 | 04-FEB-19:10 | 2244.98 | 01-FEB-17:19 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.37 | 22-FEB-14:00 | 6519.14 | 02-FEB-20:53 |
March | 30255.31 | 04-MAR-19:10 | 2244.98 | 01-MAR-18:19 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6037.27 | 28-MAR-17:08 | 3402.98 | 01-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2244.98 | 01-APR-18:19 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8461.59 | 27-APR-17:08 | 1795.23 | 11-APR-06:10 |
May | 30255.31 | 06-MAY-18:10 | 2244.98 | 01-MAY-18:30 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10340.76 | 03-MAY-17:02 | 361.90 | 13-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2244.98 | 01-JUN-18:49 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10918.00 | 07-JUN-17:03 | 94.35 | 18-JUN-05:02 |
July | 30255.31 | 01-JUL-18:10 | 2244.98 | 01-JUL-18:00 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8593.95 | 03-JUL-17:03 | 51.35 | 19-JUL-03:00 |
August | 30255.31 | 05-AUG-18:10 | 2244.98 | 01-AUG-18:00 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7082.82 | 07-AUG-17:03 | 45.19 | 16-AUG-00:10 |
September | 30255.31 | 02-SEP-18:10 | 2244.98 | 01-SEP-18:30 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6781.63 | 17-SEP-20:00 | 121.00 | 27-SEP-05:02 |
October | 30255.31 | 07-OCT-18:10 | 2244.98 | 02-OCT-17:00 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6643.56 | 02-OCT-12:00 | 3029.28 | 29-OCT-06:20 |
November | 30255.31 | 04-NOV-18:10 | 2244.98 | 01-NOV-17:19 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.73 | 09-NOV-13:00 | 5449.81 | 25-NOV-19:53 |
December | 30255.31 | 02-DEC-19:10 | 2244.98 | 01-DEC-17:19 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.97 | 28-DEC-14:00 | 8043.86 | 30-DEC-19:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.19 | |||||
Maximum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10918.00 | 8043.86 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 805.14 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 174.91 | 14-JAN-04:40 |
February | 813.01 | 04-FEB-19:10 | 805.14 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 1.57 | 22-FEB-15:03 | 223.11 | 26-FEB-01:55 |
March | 813.01 | 04-MAR-19:10 | 805.14 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 30.36 | 27-MAR-15:00 | 636.00 | 25-MAR-00:10 |
April | 813.01 | 01-APR-18:10 | 805.14 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 86.70 | 15-APR-14:00 | 75.19 | 05-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 805.14 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 214.73 | 03-MAY-24:00 | 117.73 | 15-MAY-02:50 |
June | 813.01 | 03-JUN-18:10 | 805.14 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 100.73 | 30-JUN-23:02 | 122.36 | 18-JUN-01:20 |
July | 813.01 | 01-JUL-18:10 | 805.14 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 76.85 | 15-JUL-23:10 | 97.11 | 26-JUL-04:00 |
August | 813.01 | 05-AUG-18:10 | 805.14 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 43.37 | 09-AUG-24:00 | 73.99 | 31-AUG-03:20 |
September | 813.01 | 02-SEP-18:10 | 805.14 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 33.96 | 20-SEP-14:00 | 61.40 | 09-SEP-00:40 |
October | 813.01 | 07-OCT-18:10 | 805.14 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 40.48 | 03-OCT-14:57 | 122.47 | 12-OCT-02:40 |
November | 813.01 | 04-NOV-18:10 | 805.14 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 9.32 | 13-NOV-14:00 | 163.17 | 28-NOV-04:40 |
December | 813.01 | 02-DEC-19:10 | 805.14 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 325.17 | 29-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 61.40 | ||||||
Maximum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 214.73 | 636.00 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1899.03 | 19-JAN-07:15 | 5783.27 | 05-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.32 | 19-FEB-23:00 | 6653.09 | 20-FEB-13:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1864.29 | 05-MAR-07:23 | 7552.87 | 31-MAR-13:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.22 | 11-APR-06:25 | 8309.50 | 29-APR-14:12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2619.22 | 22-MAY-14:00 | 7957.85 | 14-MAY-13:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.22 | 03-JUN-19:00 | 8215.71 | 08-JUN-13:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.09 | 04-JUL-05:40 | 7678.37 | 10-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.12 | 06-AUG-22:00 | 6397.08 | 05-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1743.40 | 30-SEP-06:45 | 6332.16 | 15-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.50 | 02-OCT-06:45 | 7116.03 | 09-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.30 | 22-NOV-07:13 | 6104.38 | 04-NOV-13:20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2255.62 | 03-DEC-07:23 | 5717.87 | 02-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138.12 | 5717.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.22 | 8309.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22232.83 | 05-JAN-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24416.80 | 23-FEB-13:00 | 26893.61 | 1683.73 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.16 | 0.00 |
March | 31787.73 | 28-MAR-17:02 | 134468.03 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6037.26 | 0.00 |
April | 37434.84 | 28-APR-04:02 | 8404.25 | 2494.43 | 14482.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63845.41 | 30-MAY-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 0.00 |
June | 61279.50 | 06-JUN-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
July | 45090.38 | 01-JUL-04:01 | 0.00 | 2619.11 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | 0.00 |
August | 45387.68 | 03-AUG-04:01 | 11765.95 | 3492.21 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
September | 51137.59 | 29-SEP-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
October | 45824.52 | 01-OCT-04:01 | 0.00 | 2619.11 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28919.08 | 09-NOV-13:00 | 26893.61 | 1683.73 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3093.73 | 0.00 |
December | 23794.73 | 21-DEC-05:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22232.83 | 0.00 | 1683.73 | 6516.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 63845.41 | 134468.03 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6037.26 | 0.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 48639.80 | 27-JAN-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 |
February | 48825.87 | 14-FEB-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 44269.65 | 24-MAR-03:11 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 82.45 |
April | 32643.00 | 28-APR-03:31 | 0.00 | 939.30 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35522.24 | 07-MAY-03:22 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
June | 33014.17 | 02-JUN-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 |
July | 25390.58 | 11-JUL-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
August | 25353.81 | 04-AUG-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
September | 30722.04 | 29-SEP-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 |
October | 40353.51 | 15-OCT-04:01 | 0.00 | 1073.49 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
November | 50268.56 | 24-NOV-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48596.51 | 15-DEC-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25353.81 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50268.56 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 1.45 | 82.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1507.38 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.64 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.05 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.76 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.14 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.98 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.73 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.72 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.15 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1541.33 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.41 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1852.14 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.703553E+11 | 46390.52 | 26-JAN-11:00 | 0.724292E+11 | 57951.44 | 03-JAN-07:10 |
February | 0.693015E+11 | 50663.93 | 22-FEB-11:00 | 0.608825E+11 | 46756.75 | 02-FEB-07:10 |
March | 0.885212E+11 | 59791.19 | 10-MAR-18:40 | 0.647432E+11 | 43067.08 | 05-MAR-11:09 |
April | 0.102191E+12 | 70617.56 | 26-APR-17:19 | 0.603831E+11 | 42792.43 | 01-APR-10:50 |
May | 0.125213E+12 | 81259.39 | 17-MAY-17:19 | 0.602025E+11 | 42394.10 | 06-MAY-10:09 |
June | 0.132298E+12 | 86025.67 | 10-JUN-18:10 | 0.566486E+11 | 42131.97 | 03-JUN-10:20 |
July | 0.141073E+12 | 84676.92 | 01-JUL-17:19 | 0.576471E+11 | 41963.92 | 02-JUL-10:30 |
August | 0.139032E+12 | 83497.57 | 25-AUG-11:00 | 0.583285E+11 | 42070.08 | 27-AUG-10:20 |
September | 0.123789E+12 | 80744.67 | 14-SEP-17:19 | 0.578776E+11 | 42381.74 | 30-SEP-10:20 |
October | 0.100521E+12 | 69627.62 | 04-OCT-11:00 | 0.619500E+11 | 42715.93 | 29-OCT-10:20 |
November | 0.809853E+11 | 56527.22 | 09-NOV-11:00 | 0.622245E+11 | 43013.19 | 26-NOV-11:09 |
December | 0.724521E+11 | 48048.66 | 18-DEC-11:00 | 0.683780E+11 | 53722.57 | 23-DEC-06:30 |
Annual Sum or Average | 0.124573E+13 | 0.741695E+12 | ||||
Minimum of Months | 0.693015E+11 | 46390.52 | 0.566486E+11 | 41963.92 | ||
Maximum of Months | 0.141073E+12 | 86025.67 | 0.724292E+11 | 57951.44 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.469814E+10 | 0.286004E+10 | 0.382185E+11 | 0.00 | 0.104386E+11 | 37879553.69 | 0.00 | 0.328755E+10 | 0.00 | 0.00 | 0.00 | 0.638538E+10 | 0.00 |
February | 0.423127E+10 | 0.245884E+10 | 0.345199E+11 | 0.00 | 0.937786E+10 | 34213790.43 | 0.00 | 0.879850E+10 | 0.00 | 0.00 | 0.00 | 0.577609E+10 | 0.00 |
March | 0.468916E+10 | 0.252067E+10 | 0.382185E+11 | 0.00 | 0.105634E+11 | 37879553.69 | 0.00 | 0.213993E+11 | 0.00 | 0.00 | 0.00 | 0.644841E+10 | 0.00 |
April | 0.444802E+10 | 0.224206E+10 | 0.369856E+11 | 0.00 | 0.109504E+11 | 36657632.61 | 0.00 | 0.368196E+11 | 0.00 | 0.00 | 0.00 | 0.619235E+10 | 0.00 |
May | 0.460830E+10 | 0.214346E+10 | 0.382185E+11 | 0.00 | 0.132296E+11 | 37879553.69 | 0.00 | 0.558340E+11 | 0.00 | 0.00 | 0.00 | 0.641350E+10 | 0.00 |
June | 0.449285E+10 | 0.198101E+10 | 0.369856E+11 | 0.00 | 0.144861E+11 | 36657632.61 | 0.00 | 0.634238E+11 | 0.00 | 0.00 | 0.00 | 0.623322E+10 | 0.00 |
July | 0.458638E+10 | 0.209777E+10 | 0.382185E+11 | 0.00 | 0.161246E+11 | 37879553.69 | 0.00 | 0.687837E+11 | 0.00 | 0.00 | 0.00 | 0.636692E+10 | 0.00 |
August | 0.468661E+10 | 0.223743E+10 | 0.382185E+11 | 0.00 | 0.160054E+11 | 37879553.69 | 0.00 | 0.665293E+11 | 0.00 | 0.00 | 0.00 | 0.644458E+10 | 0.00 |
September | 0.449916E+10 | 0.235431E+10 | 0.369856E+11 | 0.00 | 0.136436E+11 | 36657632.61 | 0.00 | 0.554008E+11 | 0.00 | 0.00 | 0.00 | 0.619208E+10 | 0.00 |
October | 0.465213E+10 | 0.263814E+10 | 0.382185E+11 | 0.00 | 0.110636E+11 | 37879553.69 | 0.00 | 0.327752E+11 | 0.00 | 0.00 | 0.00 | 0.637773E+10 | 0.00 |
November | 0.454278E+10 | 0.272369E+10 | 0.369856E+11 | 0.00 | 0.101157E+11 | 36657632.61 | 0.00 | 0.159473E+11 | 0.00 | 0.00 | 0.00 | 0.617501E+10 | 0.00 |
December | 0.469535E+10 | 0.292138E+10 | 0.382185E+11 | 0.00 | 0.103618E+11 | 37879553.69 | 0.00 | 0.536464E+10 | 0.00 | 0.00 | 0.00 | 0.637583E+10 | 0.00 |
Annual Sum or Average | 0.548302E+11 | 0.291788E+11 | 0.449992E+12 | 0.00 | 0.146361E+12 | 0.446001E+09 | 0.00 | 0.434364E+12 | 0.00 | 0.00 | 0.00 | 0.753811E+11 | 0.00 |
Minimum of Months | 0.423127E+10 | 0.198101E+10 | 0.345199E+11 | 0.00 | 0.937786E+10 | 34213790.43 | 0.00 | 0.328755E+10 | 0.00 | 0.00 | 0.00 | 0.577609E+10 | 0.00 |
Maximum of Months | 0.469814E+10 | 0.292138E+10 | 0.382185E+11 | 0.00 | 0.161246E+11 | 37879553.69 | 0.00 | 0.687837E+11 | 0.00 | 0.00 | 0.00 | 0.644841E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.586348E+10 | 0.00 | 0.266660E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.118883E+10 | 0.00 | 0.236552E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.248435E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.217705E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.203028E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.180360E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.177474E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.184287E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.192649E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.220503E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.110064E+09 | 0.00 | 0.235018E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.252094E+10 | 0.00 | 0.259574E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.968332E+10 | 0.00 | 0.262225E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.177474E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.586348E+10 | 0.00 | 0.266660E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3050.12 | 02-JAN-17:30 | 2175.41 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 5395.22 | 01-JAN-06:10 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3050.12 | 01-FEB-17:19 | 2175.41 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 5163.48 | 02-FEB-06:10 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3050.12 | 01-MAR-18:19 | 2175.41 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 5273.65 | 28-MAR-17:10 | 17.86 | 30-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 3050.12 | 01-APR-18:19 | 2175.41 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 7207.56 | 26-APR-17:19 | 17.86 | 22-APR-14:09 | 0.00 | 01-APR-00:10 |
May | 3050.12 | 01-MAY-18:30 | 2175.41 | 01-MAY-05:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 9082.27 | 17-MAY-17:10 | 17.86 | 07-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 3050.12 | 01-JUN-18:49 | 2175.41 | 01-JUN-05:10 | 24359.61 | 01-JUN-10:09 | 0.00 | 10176.32 | 22-JUN-17:10 | 17.86 | 02-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 3050.12 | 01-JUL-18:00 | 2175.41 | 01-JUL-05:10 | 24359.61 | 01-JUL-10:09 | 0.00 | 10176.32 | 01-JUL-17:10 | 17.86 | 03-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 3050.12 | 01-AUG-18:00 | 2175.41 | 01-AUG-05:10 | 24359.61 | 01-AUG-10:09 | 0.00 | 10176.32 | 25-AUG-11:09 | 17.86 | 07-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 3050.12 | 01-SEP-18:30 | 2175.41 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 9894.99 | 14-SEP-17:10 | 17.86 | 08-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 3050.12 | 02-OCT-17:00 | 2175.41 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 7235.71 | 04-OCT-11:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 3050.12 | 01-NOV-17:19 | 2175.41 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 4941.23 | 09-NOV-11:00 | 17.86 | 26-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 3050.12 | 01-DEC-17:19 | 2175.41 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 5380.32 | 23-DEC-06:10 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 4941.23 | 17.86 | 0.00 | ||||||
Maximum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 10176.32 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10907.16 | 12-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4741.58 | 23-JAN-07:40 | 0.00 |
February | 15503.74 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4738.82 | 07-FEB-07:10 | 0.00 |
March | 24729.89 | 28-MAR-17:10 | 0.00 | 0.00 | 0.00 | 4737.66 | 06-MAR-07:19 | 0.00 |
April | 34512.00 | 26-APR-17:10 | 0.00 | 0.00 | 0.00 | 4736.71 | 19-APR-18:30 | 0.00 |
May | 43450.67 | 17-MAY-17:10 | 0.00 | 0.00 | 0.00 | 4736.80 | 24-MAY-18:40 | 0.00 |
June | 48354.39 | 10-JUN-18:10 | 0.00 | 0.00 | 0.00 | 4736.52 | 02-JUN-18:00 | 0.00 |
July | 45515.18 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 4736.22 | 19-JUL-06:49 | 0.00 |
August | 43794.45 | 28-AUG-17:10 | 0.00 | 0.00 | 0.00 | 4736.12 | 04-AUG-06:10 | 0.00 |
September | 42749.79 | 17-SEP-19:00 | 0.00 | 0.00 | 0.00 | 4736.69 | 26-SEP-18:30 | 0.00 |
October | 32424.26 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 4736.70 | 18-OCT-18:30 | 0.00 |
November | 19834.50 | 09-NOV-12:00 | 0.00 | 0.00 | 0.00 | 4737.41 | 16-NOV-07:19 | 0.00 |
December | 12833.82 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4740.07 | 04-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10907.16 | 0.00 | 0.00 | 0.00 | 4736.12 | 0.00 | ||
Maximum of Months | 48354.39 | 0.00 | 0.00 | 0.00 | 4741.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 46390.52 | 26-JAN-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4565.01 | 17.86 | 0.00 | 8806.89 | 0.00 |
February | 50663.93 | 22-FEB-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4565.01 | 17.86 | 0.00 | 13041.81 | 0.00 |
March | 59791.19 | 10-MAR-18:40 | 3050.12 | 20336.83 | 2175.41 | 0.00 | 5189.52 | 17.86 | 0.00 | 23033.78 | 0.00 |
April | 70617.56 | 26-APR-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 7207.56 | 17.86 | 0.00 | 34505.36 | 0.00 |
May | 81259.39 | 17-MAY-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 9073.33 | 17.86 | 0.00 | 43285.87 | 0.00 |
June | 86025.67 | 10-JUN-18:10 | 2488.87 | 18727.72 | 0.00 | 0.00 | 10034.70 | 17.86 | 0.00 | 48354.39 | 0.00 |
July | 84676.92 | 01-JUL-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 10176.32 | 17.86 | 0.00 | 45450.73 | 0.00 |
August | 83497.57 | 25-AUG-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 10176.32 | 17.86 | 0.00 | 43278.38 | 0.00 |
September | 80744.67 | 14-SEP-17:19 | 2488.87 | 20336.83 | 0.00 | 0.00 | 9881.87 | 17.86 | 0.00 | 41894.67 | 0.00 |
October | 69627.62 | 04-OCT-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 7235.71 | 17.86 | 0.00 | 32424.26 | 0.00 |
November | 56527.22 | 09-NOV-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4941.23 | 17.86 | 0.00 | 18504.83 | 0.00 |
December | 48048.66 | 18-DEC-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4565.01 | 17.86 | 0.00 | 10460.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 46390.52 | 2488.87 | 18727.72 | 0.00 | 0.00 | 4565.01 | 17.86 | 0.00 | 8806.89 | 0.00 | |
Maximum of Months | 86025.67 | 3050.12 | 24359.61 | 2175.41 | 0.00 | 10176.32 | 17.86 | 0.00 | 48354.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 31470.83 | 01-JAN-06:10 | 0.00 | 18629.68 | 17-JAN-19:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 20833.68 | 02-FEB-06:10 | 0.00 | 18138.89 | 03-FEB-19:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 17570.25 | 01-MAR-07:00 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 17145.46 | 03-APR-18:00 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16732.49 | 01-MAY-18:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16348.47 | 01-JUN-18:40 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 16110.00 | 03-JUL-18:10 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16286.71 | 31-AUG-18:19 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16627.25 | 29-SEP-18:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 17100.46 | 31-OCT-18:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 10099.90 | 27-NOV-06:10 | 0.00 | 17496.66 | 30-NOV-07:19 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 31020.81 | 23-DEC-06:10 | 0.00 | 17763.36 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 16110.00 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 31470.83 | 0.00 | 18629.68 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.82 | 1.00 | 24.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.82 | 1.00 | 24.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.82 | 1.00 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 30.41 | 0.00 | 30.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 30.65 | 0.00 | 30.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 30.98 | 0.00 | 30.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 31.29 | 0.00 | 31.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 111.50 | 28.30 | 81.67 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 296.50 | 28.37 | 266.83 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 495.83 | 28.44 | 464.33 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 478.50 | 28.67 | 447.33 | 28.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 270.50 | 28.03 | 240.50 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 31.33 | 0.00 | 31.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 30.91 | 0.00 | 30.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 30.44 | 0.00 | 30.44 |
Annual Sum or Average | 0.00 | 0.00 | 1774.00 | 28.59 | 1500.67 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.03 | 0.00 | 27.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 495.83 | 31.33 | 464.33 | 31.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 332.17 | 21.38 | 138.83 | 22.07 | 7.67 | 22.04 |
February | 178.83 | 21.67 | 302.00 | 23.12 | 2.83 | 23.12 |
March | 45.67 | 22.71 | 535.33 | 23.93 | 3.83 | 23.93 |
April | 25.83 | 26.26 | 587.00 | 24.28 | 25.83 | 24.36 |
May | 212.00 | 24.69 | 611.00 | 24.38 | 212.00 | 24.45 |
June | 394.83 | 24.43 | 592.00 | 24.36 | 394.83 | 24.38 |
July | 591.00 | 24.30 | 609.00 | 24.29 | 591.00 | 24.29 |
August | 612.00 | 24.26 | 612.00 | 24.26 | 612.00 | 24.26 |
September | 529.17 | 24.25 | 590.00 | 24.24 | 529.17 | 24.24 |
October | 111.17 | 24.40 | 606.50 | 24.14 | 111.17 | 24.17 |
November | 84.00 | 22.06 | 463.83 | 23.68 | 0.17 | 23.68 |
December | 289.67 | 21.57 | 243.33 | 22.64 | 4.67 | 22.63 |
Annual Sum or Average | 3406.33 | 23.61 | 5890.83 | 23.96 | 2495.17 | 24.04 |
Minimum of Months | 25.83 | 21.38 | 138.83 | 22.07 | 0.17 | 22.04 |
Maximum of Months | 612.00 | 26.26 | 612.00 | 24.38 | 612.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.83 | 23.67 | 425.83 | 24.45 | 257.67 | 24.80 |
February | 399.50 | 25.27 | 482.67 | 25.35 | 347.50 | 25.52 |
March | 533.00 | 26.00 | 612.00 | 25.91 | 533.00 | 25.94 |
April | 586.83 | 26.05 | 590.00 | 26.05 | 586.83 | 26.05 |
May | 611.00 | 26.25 | 611.00 | 26.25 | 611.00 | 26.25 |
June | 592.00 | 27.00 | 592.00 | 27.00 | 592.00 | 27.00 |
July | 609.00 | 27.77 | 609.00 | 27.77 | 609.00 | 27.77 |
August | 612.00 | 27.87 | 612.00 | 27.87 | 612.00 | 27.87 |
September | 590.00 | 26.74 | 590.00 | 26.74 | 590.00 | 26.74 |
October | 603.33 | 26.03 | 610.00 | 26.03 | 603.33 | 26.03 |
November | 457.33 | 25.90 | 575.33 | 25.73 | 449.83 | 25.80 |
December | 412.50 | 24.54 | 457.00 | 24.94 | 303.00 | 25.20 |
Annual Sum or Average | 6420.33 | 26.24 | 6766.83 | 26.28 | 6095.17 | 26.37 |
Minimum of Months | 399.50 | 23.67 | 425.83 | 24.45 | 257.67 | 24.80 |
Maximum of Months | 612.00 | 27.87 | 612.00 | 27.87 | 612.00 | 27.87 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.51798 | 46.51902 | 0.12559 | 7.58674 |
February | 551.00000 | 23.18931 | 48.31025 | 0.32121 | 8.74165 |
March | 612.00000 | 23.90223 | 47.93702 | 0.53065 | 11.29152 |
April | 590.00000 | 24.19484 | 47.50780 | 0.64495 | 14.04373 |
May | 611.00000 | 24.27647 | 56.85582 | -0.0297 | 5.92415 |
June | 592.00000 | 24.30435 | 63.80054 | 0.04412 | 6.24599 |
July | 609.00000 | 24.28868 | 71.04887 | 0.08669 | 6.36808 |
August | 612.00000 | 24.26479 | 72.61458 | 0.08543 | 6.15751 |
September | 590.00000 | 24.22356 | 69.82878 | 0.03708 | 5.75855 |
October | 610.00000 | 24.08710 | 55.17091 | 0.67952 | 14.88467 |
November | 591.00000 | 23.64991 | 48.69460 | 0.48417 | 10.65043 |
December | 609.00000 | 22.78978 | 45.50982 | 0.20741 | 7.92058 |
Annual Sum or Average | 7187.00000 | 23.80972 | 56.20252 | 0.26725 | 8.79363 |
Minimum of Months | 551.00000 | 22.51798 | 45.50982 | -0.0297 | 5.75855 |
Maximum of Months | 612.00000 | 24.30435 | 72.61458 | 0.67952 | 14.88467 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.73020 | 47.49040 | 0.64578 | 20.34043 |
February | 551.00000 | 24.86631 | 47.66727 | 0.93281 | 26.81648 |
March | 612.00000 | 25.83500 | 47.31831 | 1.19396 | 35.47851 |
April | 590.00000 | 26.05222 | 48.25017 | 1.29845 | 40.37450 |
May | 611.00000 | 26.25254 | 57.00250 | 0.93174 | 24.21850 |
June | 592.00000 | 27.00031 | 62.34527 | 1.24474 | 38.89790 |
July | 609.00000 | 27.76925 | 66.35394 | 1.53490 | 52.80934 |
August | 612.00000 | 27.87284 | 66.17168 | 1.56910 | 54.30660 |
September | 590.00000 | 26.74213 | 64.20886 | 1.15598 | 34.50676 |
October | 610.00000 | 26.02195 | 53.51837 | 1.34216 | 42.58906 |
November | 591.00000 | 25.49057 | 48.24113 | 1.12884 | 33.13722 |
December | 609.00000 | 24.25387 | 45.87036 | 0.78003 | 22.66344 |
Annual Sum or Average | 7187.00000 | 25.99687 | 54.58171 | 1.14775 | 35.57303 |
Minimum of Months | 551.00000 | 23.73020 | 45.87036 | 0.64578 | 20.34043 |
Maximum of Months | 612.00000 | 27.87284 | 66.35394 | 1.56910 | 54.30660 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.617505E+10 | 0.202185E+10 | 212.14 | 0.492559E+10 | 0.124946E+10 | 0.00 | 0.51 | 12-JAN-14:00 | 0.00 | 01-JAN-00:02 | 24523.13 | 12-JAN-14:00 | 20758.66 | 12-JAN-14:00 | 6328.30 | 13-JAN-14:00 | 7523.67 | 12-JAN-14:00 | 0.00 | 01-JAN-00:02 |
February | 0.176835E+11 | 0.555647E+10 | 313.08 | 0.138440E+11 | 0.383957E+10 | 0.00 | 0.73 | 22-FEB-14:00 | 0.00 | 01-FEB-00:03 | 36886.66 | 22-FEB-14:00 | 31171.12 | 22-FEB-12:55 | 11148.47 | 25-FEB-18:10 | 10682.19 | 22-FEB-14:00 | 0.00 | 01-FEB-00:03 |
March | 0.463983E+11 | 0.138181E+11 | 502.71 | 0.365577E+11 | 0.984065E+10 | 0.00 | 1.00 | 10-MAR-18:03 | 0.00 | 01-MAR-00:03 | 59341.18 | 10-MAR-18:20 | 51844.80 | 28-MAR-17:10 | 22044.16 | 10-MAR-20:00 | 16707.85 | 28-MAR-17:10 | 0.00 | 01-MAR-00:03 |
April | 0.786500E+11 | 0.234697E+11 | 557.09 | 0.658699E+11 | 0.127801E+11 | 0.00 | 1.00 | 01-APR-17:03 | 0.00 | 01-APR-00:01 | 77721.78 | 18-APR-12:00 | 63880.68 | 28-APR-17:10 | 29574.95 | 26-APR-05:03 | 23856.00 | 26-APR-17:10 | 0.00 | 01-APR-00:01 |
May | 0.118992E+12 | 0.353035E+11 | 591.20 | 0.873719E+11 | 0.316199E+11 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:01 | 121313.40 | 20-MAY-04:01 | 86134.86 | 30-MAY-04:01 | 80548.82 | 23-MAY-04:01 | 31302.29 | 17-MAY-17:10 | 0.00 | 01-MAY-00:01 |
June | 0.140352E+12 | 0.405815E+11 | 580.56 | 0.885730E+11 | 0.517791E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:01 | 121313.40 | 16-JUN-04:01 | 86161.66 | 06-JUN-04:01 | 84147.61 | 28-JUN-04:02 | 35923.18 | 10-JUN-18:10 | 0.00 | 01-JUN-00:01 |
July | 0.163754E+12 | 0.441090E+11 | 596.51 | 0.825282E+11 | 0.812260E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:01 | 121313.40 | 27-JUL-04:01 | 68773.71 | 03-JUL-17:10 | 85679.52 | 19-JUL-04:01 | 33896.41 | 01-JUL-17:03 | 0.00 | 01-JUL-00:01 |
August | 0.162717E+12 | 0.425973E+11 | 589.94 | 0.756504E+11 | 0.870661E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 | 121313.40 | 01-AUG-04:01 | 62191.23 | 07-AUG-17:10 | 87164.35 | 30-AUG-04:01 | 32614.93 | 28-AUG-17:03 | 0.00 | 01-AUG-00:01 |
September | 0.131114E+12 | 0.343158E+11 | 569.07 | 0.658286E+11 | 0.652858E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:01 | 121313.40 | 04-SEP-04:01 | 60509.65 | 29-SEP-04:01 | 83615.44 | 12-SEP-04:01 | 31108.96 | 14-SEP-17:10 | 0.00 | 01-SEP-00:01 |
October | 0.734350E+11 | 0.208273E+11 | 554.86 | 0.518018E+11 | 0.216332E+11 | 0.00 | 1.00 | 01-OCT-04:01 | 0.00 | 01-OCT-00:01 | 113390.44 | 04-OCT-04:01 | 57100.48 | 02-OCT-11:53 | 57820.43 | 04-OCT-04:01 | 28206.28 | 04-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 0.343088E+11 | 0.103422E+11 | 424.31 | 0.268320E+11 | 0.747681E+10 | 0.00 | 0.93 | 09-NOV-13:00 | 0.00 | 01-NOV-00:01 | 50421.67 | 09-NOV-13:00 | 40307.15 | 09-NOV-13:00 | 15215.25 | 08-NOV-18:50 | 13735.38 | 09-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.101523E+11 | 0.327629E+10 | 260.05 | 0.792347E+10 | 0.222880E+10 | 0.00 | 0.61 | 28-DEC-14:00 | 0.00 | 01-DEC-00:03 | 29535.51 | 28-DEC-14:00 | 24209.43 | 28-DEC-14:00 | 6446.80 | 18-DEC-13:00 | 8848.35 | 28-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.983732E+12 | 0.276219E+12 | 5751.51 | 0.607706E+12 | 0.376025E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.617505E+10 | 0.202185E+10 | 212.14 | 0.492559E+10 | 0.124946E+10 | 0.00 | 0.51 | 0.00 | 24523.13 | 20758.66 | 6328.30 | 7523.67 | 0.00 | |||||||
Maximum of Months | 0.163754E+12 | 0.441090E+11 | 596.51 | 0.885730E+11 | 0.870661E+11 | 0.00 | 1.00 | 0.00 | 121313.40 | 86161.66 | 87164.35 | 35923.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.439970E+10 | 0.126570E+10 | 248.49 | 0.336988E+10 | 0.102982E+10 | 0.00 | 1.00 | 17-JAN-04:21 | 0.00 | 01-JAN-00:02 | 41091.96 | 17-JAN-05:01 | 27104.36 | 27-JAN-05:01 | 16400.42 | 17-JAN-05:01 | 10027.54 | 17-JAN-05:01 | 0.00 | 01-JAN-00:02 |
February | 0.120333E+11 | 0.324204E+10 | 355.08 | 0.934439E+10 | 0.268887E+10 | 0.00 | 1.00 | 10-FEB-04:21 | 0.00 | 01-FEB-00:03 | 41091.96 | 10-FEB-05:01 | 26033.30 | 17-FEB-05:01 | 16680.50 | 10-FEB-04:21 | 10027.54 | 10-FEB-05:01 | 0.00 | 01-FEB-00:03 |
March | 0.298002E+11 | 0.758115E+10 | 581.00 | 0.243138E+11 | 0.548637E+10 | 0.00 | 1.00 | 02-MAR-05:01 | 0.00 | 01-MAR-00:03 | 41091.96 | 08-MAR-05:01 | 31877.61 | 28-MAR-16:18 | 20738.05 | 31-MAR-03:11 | 10027.54 | 07-MAR-04:11 | 0.00 | 01-MAR-00:03 |
April | 0.516259E+11 | 0.133500E+11 | 670.90 | 0.457086E+11 | 0.591730E+10 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:01 | 44331.18 | 25-APR-03:31 | 39437.94 | 15-APR-15:03 | 22314.32 | 25-APR-03:31 | 11727.46 | 15-APR-15:03 | 0.00 | 01-APR-00:01 |
May | 0.788840E+11 | 0.205305E+11 | 704.67 | 0.616534E+11 | 0.172306E+11 | 0.00 | 1.00 | 01-MAY-03:32 | 0.00 | 01-MAY-00:01 | 45655.87 | 20-MAY-04:01 | 42300.50 | 02-MAY-17:42 | 28818.15 | 22-MAY-22:35 | 13654.08 | 03-MAY-15:00 | 0.00 | 01-MAY-00:01 |
June | 0.891426E+11 | 0.228422E+11 | 683.84 | 0.598363E+11 | 0.293063E+11 | 0.00 | 1.00 | 01-JUN-03:32 | 0.00 | 01-JUN-00:01 | 45655.87 | 24-JUN-11:20 | 42355.99 | 07-JUN-18:52 | 31257.58 | 28-JUN-03:22 | 13565.80 | 07-JUN-14:55 | 0.00 | 01-JUN-00:01 |
July | 0.101815E+12 | 0.246747E+11 | 707.64 | 0.519195E+11 | 0.498960E+11 | 0.00 | 1.00 | 01-JUL-00:08 | 0.00 | 01-JUL-00:01 | 45655.87 | 11-JUL-10:00 | 38985.72 | 04-JUL-18:00 | 32643.12 | 19-JUL-03:22 | 12313.58 | 02-JUL-15:55 | 0.00 | 01-JUL-00:01 |
August | 0.101468E+12 | 0.239320E+11 | 707.88 | 0.457461E+11 | 0.557219E+11 | 0.00 | 1.00 | 01-AUG-00:07 | 0.00 | 01-AUG-00:01 | 45655.87 | 10-AUG-14:50 | 30634.99 | 07-AUG-14:00 | 33024.00 | 15-AUG-00:07 | 11655.18 | 07-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.901197E+11 | 0.210849E+11 | 683.84 | 0.439077E+11 | 0.462120E+11 | 0.00 | 1.00 | 01-SEP-00:08 | 0.00 | 01-SEP-00:01 | 45655.87 | 01-SEP-04:02 | 34159.62 | 26-SEP-15:27 | 32222.11 | 13-SEP-03:22 | 11695.23 | 17-SEP-20:00 | 0.00 | 01-SEP-00:01 |
October | 0.489947E+11 | 0.119479E+11 | 659.45 | 0.351729E+11 | 0.138218E+11 | 0.00 | 1.00 | 01-OCT-03:22 | 0.00 | 01-OCT-00:01 | 45655.87 | 06-OCT-10:48 | 34111.58 | 02-OCT-10:54 | 28340.45 | 12-OCT-03:22 | 10817.70 | 04-OCT-11:02 | 0.00 | 01-OCT-00:01 |
November | 0.218988E+11 | 0.560501E+10 | 475.49 | 0.174940E+11 | 0.440474E+10 | 0.00 | 1.00 | 01-NOV-10:52 | 0.00 | 01-NOV-00:01 | 41091.96 | 04-NOV-04:01 | 27645.13 | 13-NOV-05:01 | 14946.86 | 03-NOV-03:11 | 10027.54 | 04-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.746636E+10 | 0.208835E+10 | 297.19 | 0.567499E+10 | 0.179137E+10 | 0.00 | 1.00 | 15-DEC-04:21 | 0.00 | 01-DEC-00:03 | 41091.96 | 15-DEC-05:01 | 25730.12 | 15-DEC-05:01 | 15564.59 | 15-DEC-04:21 | 10027.54 | 15-DEC-05:01 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.637649E+12 | 0.158144E+12 | 6775.48 | 0.404142E+12 | 0.233507E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.439970E+10 | 0.126570E+10 | 248.49 | 0.336988E+10 | 0.102982E+10 | 0.00 | 1.00 | 0.00 | 41091.96 | 25730.12 | 14946.86 | 10027.54 | 0.00 | |||||||
Maximum of Months | 0.101815E+12 | 0.246747E+11 | 707.88 | 0.616534E+11 | 0.557219E+11 | 0.00 | 1.00 | 0.00 | 45655.87 | 42355.99 | 33024.00 | 13654.08 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.35 | 62.66 | 93.69 | 172.69 | 247.81 | 0.00 | 0.00 | 0.00 |
February | 190.47 | 78.64 | 111.83 | 258.93 | 193.98 | 0.00 | 0.00 | 0.00 |
March | 232.45 | 96.10 | 136.35 | 387.83 | 117.92 | 0.00 | 0.00 | 0.00 |
April | 276.68 | 129.00 | 147.68 | 576.19 | 44.98 | 0.00 | 0.00 | 0.00 |
May | 271.86 | 120.64 | 151.21 | 649.31 | 10.61 | 0.00 | 0.00 | 0.00 |
June | 220.77 | 73.06 | 147.71 | 575.62 | 7.53 | 0.00 | 0.00 | 0.00 |
July | 185.29 | 38.73 | 146.56 | 472.40 | 3.23 | 3.33 | 0.00 | 0.00 |
August | 167.47 | 29.14 | 138.33 | 400.01 | 8.00 | 0.00 | 0.00 | 0.00 |
September | 178.61 | 49.62 | 128.99 | 378.23 | 24.72 | 0.00 | 0.00 | 0.00 |
October | 195.41 | 78.73 | 116.68 | 366.95 | 97.65 | 0.00 | 0.00 | 0.00 |
November | 173.05 | 73.99 | 99.07 | 262.38 | 179.04 | 0.00 | 0.00 | 0.00 |
December | 151.47 | 60.14 | 91.33 | 178.07 | 246.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.93 | 74.09 | 125.84 | 390.32 | 98.07 | 3.33 | 0.00 | 0.00 |
Minimum of Months | 151.47 | 29.14 | 91.33 | 172.69 | 3.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 276.68 | 129.00 | 151.21 | 649.31 | 247.81 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 461.44 | 280.87 | 180.56 | 664.57 | 337.69 | 0.00 | 0.00 | 0.00 |
February | 437.78 | 243.17 | 194.61 | 680.39 | 271.21 | 0.00 | 0.00 | 0.00 |
March | 371.99 | 163.12 | 208.87 | 666.95 | 169.90 | 0.00 | 0.00 | 0.00 |
April | 265.21 | 76.48 | 188.72 | 629.50 | 64.47 | 0.00 | 0.00 | 0.00 |
May | 191.19 | 16.10 | 175.08 | 576.25 | 15.05 | 0.00 | 0.00 | 0.00 |
June | 172.92 | 3.01 | 169.92 | 552.21 | 10.53 | 0.00 | 0.00 | 0.00 |
July | 179.61 | 1.76 | 177.85 | 514.02 | 4.47 | 3.33 | 0.00 | 0.00 |
August | 189.38 | 8.30 | 181.08 | 483.58 | 11.20 | 0.00 | 0.00 | 0.00 |
September | 262.05 | 72.15 | 189.90 | 571.08 | 34.67 | 0.00 | 0.00 | 0.00 |
October | 443.65 | 248.83 | 194.82 | 841.66 | 137.96 | 0.00 | 0.00 | 0.00 |
November | 553.55 | 366.72 | 186.83 | 926.43 | 250.62 | 0.00 | 0.00 | 0.00 |
December | 492.42 | 308.81 | 183.60 | 735.03 | 333.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 334.49 | 148.55 | 185.94 | 653.07 | 136.16 | 3.33 | 0.00 | 0.00 |
Minimum of Months | 172.92 | 1.76 | 169.92 | 483.58 | 4.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 553.55 | 366.72 | 208.87 | 926.43 | 337.69 | 3.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 153.16 | 59.59 | 93.56 | 183.03 | 262.60 | 0.00 | 0.00 | 0.00 |
February | 175.58 | 64.87 | 110.71 | 244.86 | 205.26 | 0.00 | 0.00 | 0.00 |
March | 227.56 | 91.21 | 136.35 | 385.34 | 124.56 | 0.00 | 0.00 | 0.00 |
April | 275.67 | 129.10 | 146.58 | 574.21 | 46.69 | 0.00 | 0.00 | 0.00 |
May | 261.34 | 110.86 | 150.48 | 629.79 | 10.68 | 0.00 | 0.00 | 0.00 |
June | 245.87 | 95.76 | 150.12 | 620.46 | 7.50 | 0.00 | 0.00 | 0.00 |
July | 181.98 | 35.26 | 146.71 | 467.05 | 3.11 | 3.33 | 0.00 | 0.00 |
August | 167.05 | 29.44 | 137.61 | 399.89 | 8.02 | 0.00 | 0.00 | 0.00 |
September | 184.47 | 54.55 | 129.92 | 389.05 | 25.03 | 0.00 | 0.00 | 0.00 |
October | 191.84 | 76.60 | 115.24 | 365.20 | 101.71 | 0.00 | 0.00 | 0.00 |
November | 173.34 | 73.99 | 99.35 | 275.37 | 189.06 | 0.00 | 0.00 | 0.00 |
December | 147.91 | 56.24 | 91.66 | 181.66 | 254.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.78 | 73.02 | 125.75 | 393.42 | 102.78 | 3.33 | 0.00 | 0.00 |
Minimum of Months | 147.91 | 29.44 | 91.66 | 181.66 | 3.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.67 | 129.10 | 150.48 | 629.79 | 262.60 | 3.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418765E+09 | 0.167833E+09 | 0.250932E+09 | 0.462545E+09 | 0.663740E+09 |
February | 0.460784E+09 | 0.190248E+09 | 0.270536E+09 | 0.626398E+09 | 0.469275E+09 |
March | 0.622589E+09 | 0.257395E+09 | 0.365195E+09 | 0.103875E+10 | 0.315831E+09 |
April | 0.717144E+09 | 0.334366E+09 | 0.382778E+09 | 0.149349E+10 | 0.116587E+09 |
May | 0.728141E+09 | 0.323134E+09 | 0.405007E+09 | 0.173910E+10 | 28416406.97 |
June | 0.572235E+09 | 0.189364E+09 | 0.382871E+09 | 0.149201E+10 | 19522711.41 |
July | 0.496293E+09 | 0.103745E+09 | 0.392547E+09 | 0.126529E+10 | 8661995.87 |
August | 0.448559E+09 | 78046346.03 | 0.370512E+09 | 0.107139E+10 | 21436325.66 |
September | 0.462963E+09 | 0.128614E+09 | 0.334349E+09 | 0.980377E+09 | 64065302.98 |
October | 0.523377E+09 | 0.210873E+09 | 0.312504E+09 | 0.982842E+09 | 0.261551E+09 |
November | 0.448557E+09 | 0.191777E+09 | 0.256780E+09 | 0.680083E+09 | 0.464078E+09 |
December | 0.405708E+09 | 0.161089E+09 | 0.244619E+09 | 0.476938E+09 | 0.659654E+09 |
Annual Sum or Average | 0.630511E+10 | 0.233648E+10 | 0.396863E+10 | 0.123092E+11 | 0.309282E+10 |
Minimum of Months | 0.405708E+09 | 78046346.03 | 0.244619E+09 | 0.462545E+09 | 8661995.87 |
Maximum of Months | 0.728141E+09 | 0.334366E+09 | 0.405007E+09 | 0.173910E+10 | 0.663740E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123592E+10 | 0.752294E+09 | 0.483624E+09 | 0.177997E+10 | 0.904467E+09 |
February | 0.105908E+10 | 0.588276E+09 | 0.470803E+09 | 0.164599E+10 | 0.656114E+09 |
March | 0.996329E+09 | 0.436903E+09 | 0.559426E+09 | 0.178636E+10 | 0.455048E+09 |
April | 0.687413E+09 | 0.198241E+09 | 0.489172E+09 | 0.163166E+10 | 0.167118E+09 |
May | 0.512073E+09 | 43134635.72 | 0.468938E+09 | 0.154343E+10 | 40313615.40 |
June | 0.448214E+09 | 7793966.94 | 0.440420E+09 | 0.143134E+10 | 27296901.08 |
July | 0.481069E+09 | 4710887.01 | 0.476358E+09 | 0.137675E+10 | 11983825.68 |
August | 0.507234E+09 | 22229786.61 | 0.485004E+09 | 0.129521E+10 | 29986133.62 |
September | 0.679241E+09 | 0.187019E+09 | 0.492223E+09 | 0.148024E+10 | 89868893.27 |
October | 0.118829E+10 | 0.666468E+09 | 0.521817E+09 | 0.225431E+10 | 0.369524E+09 |
November | 0.143479E+10 | 0.950531E+09 | 0.484260E+09 | 0.240131E+10 | 0.649600E+09 |
December | 0.131889E+10 | 0.827121E+09 | 0.491766E+09 | 0.196871E+10 | 0.892681E+09 |
Annual Sum or Average | 0.105485E+11 | 0.468472E+10 | 0.586381E+10 | 0.205953E+11 | 0.429400E+10 |
Minimum of Months | 0.448214E+09 | 4710887.01 | 0.440420E+09 | 0.129521E+10 | 11983825.68 |
Maximum of Months | 0.143479E+10 | 0.950531E+09 | 0.559426E+09 | 0.240131E+10 | 0.904467E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.410216E+09 | 0.159619E+09 | 0.250598E+09 | 0.490230E+09 | 0.703345E+09 |
February | 0.424757E+09 | 0.156929E+09 | 0.267828E+09 | 0.592359E+09 | 0.496570E+09 |
March | 0.609495E+09 | 0.244285E+09 | 0.365210E+09 | 0.103209E+10 | 0.333620E+09 |
April | 0.714544E+09 | 0.334621E+09 | 0.379923E+09 | 0.148835E+10 | 0.121008E+09 |
May | 0.699979E+09 | 0.296940E+09 | 0.403038E+09 | 0.168684E+10 | 28613976.59 |
June | 0.637301E+09 | 0.248203E+09 | 0.389099E+09 | 0.160823E+10 | 19440609.91 |
July | 0.487409E+09 | 94450518.15 | 0.392958E+09 | 0.125093E+10 | 8317526.95 |
August | 0.447429E+09 | 78844667.90 | 0.368585E+09 | 0.107108E+10 | 21475421.91 |
September | 0.478154E+09 | 0.141398E+09 | 0.336756E+09 | 0.100843E+10 | 64873077.50 |
October | 0.513830E+09 | 0.205159E+09 | 0.308671E+09 | 0.978153E+09 | 0.272420E+09 |
November | 0.449301E+09 | 0.191776E+09 | 0.257525E+09 | 0.713764E+09 | 0.490043E+09 |
December | 0.396160E+09 | 0.150647E+09 | 0.245513E+09 | 0.486547E+09 | 0.681519E+09 |
Annual Sum or Average | 0.626858E+10 | 0.230287E+10 | 0.396570E+10 | 0.124070E+11 | 0.324125E+10 |
Minimum of Months | 0.396160E+09 | 78844667.90 | 0.245513E+09 | 0.486547E+09 | 8317526.95 |
Maximum of Months | 0.714544E+09 | 0.334621E+09 | 0.403038E+09 | 0.168684E+10 | 0.703345E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 995.15 | 822.95 | 770.95 | 403.13 | 367.81 | 0.00 | 0.00 |
February | 1169.00 | 655.28 | 803.83 | 386.68 | 417.15 | 0.00 | 0.00 |
March | 1429.74 | 402.00 | 831.99 | 350.43 | 481.57 | 0.00 | 0.00 |
April | 1776.91 | 153.15 | 817.55 | 334.58 | 482.98 | 0.00 | 0.00 |
May | 1855.17 | 36.17 | 724.38 | 247.61 | 476.77 | 0.00 | 0.00 |
June | 1748.20 | 25.47 | 639.56 | 171.82 | 467.74 | 0.00 | 0.00 |
July | 1453.47 | 10.81 | 546.88 | 75.76 | 471.13 | 0.00 | 0.00 |
August | 1283.45 | 27.19 | 523.90 | 66.88 | 457.03 | 0.00 | 0.00 |
September | 1337.98 | 84.03 | 625.14 | 176.32 | 448.81 | 0.00 | 0.00 |
October | 1570.70 | 334.21 | 830.90 | 404.16 | 426.74 | 0.00 | 0.00 |
November | 1455.60 | 610.14 | 899.94 | 514.69 | 385.25 | 0.00 | 0.00 |
December | 1075.11 | 814.38 | 791.80 | 425.20 | 366.60 | 0.00 | 0.00 |
Annual Sum or Average | 1429.70 | 329.89 | 733.20 | 295.66 | 437.54 | 0.00 | 0.00 |
Minimum of Months | 995.15 | 10.81 | 523.90 | 66.88 | 366.60 | 0.00 | 0.00 |
Maximum of Months | 1855.17 | 822.95 | 899.94 | 514.69 | 482.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266540E+10 | 0.220420E+10 | 0.206490E+10 | 0.107975E+10 | 0.985154E+09 | 0.00 | 0.00 |
February | 0.282804E+10 | 0.158525E+10 | 0.194462E+10 | 0.935452E+09 | 0.100917E+10 | 0.00 | 0.00 |
March | 0.382941E+10 | 0.107671E+10 | 0.222841E+10 | 0.938583E+09 | 0.128983E+10 | 0.00 | 0.00 |
April | 0.460575E+10 | 0.396962E+09 | 0.211910E+10 | 0.867228E+09 | 0.125187E+10 | 0.00 | 0.00 |
May | 0.496888E+10 | 96864563.58 | 0.194019E+10 | 0.663209E+09 | 0.127698E+10 | 0.00 | 0.00 |
June | 0.453132E+10 | 66006435.29 | 0.165775E+10 | 0.445361E+09 | 0.121239E+10 | 0.00 | 0.00 |
July | 0.389297E+10 | 28957581.33 | 0.146477E+10 | 0.202907E+09 | 0.126186E+10 | 0.00 | 0.00 |
August | 0.343760E+10 | 72816779.43 | 0.140322E+10 | 0.179121E+09 | 0.122410E+10 | 0.00 | 0.00 |
September | 0.346804E+10 | 0.217810E+09 | 0.162036E+10 | 0.457030E+09 | 0.116333E+10 | 0.00 | 0.00 |
October | 0.420696E+10 | 0.895154E+09 | 0.222549E+10 | 0.108250E+10 | 0.114299E+10 | 0.00 | 0.00 |
November | 0.377292E+10 | 0.158148E+10 | 0.233265E+10 | 0.133408E+10 | 0.998564E+09 | 0.00 | 0.00 |
December | 0.287957E+10 | 0.218123E+10 | 0.212075E+10 | 0.113886E+10 | 0.981898E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.450869E+11 | 0.104034E+11 | 0.231222E+11 | 0.932408E+10 | 0.137981E+11 | 0.00 | 0.00 |
Minimum of Months | 0.266540E+10 | 28957581.33 | 0.140322E+10 | 0.179121E+09 | 0.981898E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496888E+10 | 0.220420E+10 | 0.233265E+10 | 0.133408E+10 | 0.128983E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638523E+10 | -0.622516E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160078891.8 | 81.22 | 0.00 | 0.00 |
February | 0.577603E+10 | -0.563426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -141767061.5 | 81.22 | 0.00 | 0.00 |
March | 0.644824E+10 | -0.629388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154355335.6 | 81.21 | 0.00 | 0.00 |
April | 0.619222E+10 | -0.604348E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148743047.0 | 81.22 | 0.00 | 0.00 |
May | 0.641335E+10 | -0.626018E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153167540.7 | 81.22 | 0.00 | 0.00 |
June | 0.623306E+10 | -0.608657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -146492131.0 | 81.21 | 0.00 | 0.00 |
July | 0.636662E+10 | -0.621708E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149543101.6 | 81.22 | 0.00 | 0.00 |
August | 0.644449E+10 | -0.629520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149298136.2 | 81.22 | 0.00 | 0.00 |
September | 0.619189E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -147069462.5 | 81.21 | 0.00 | 0.00 |
October | 0.637761E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153781670.3 | 81.21 | 0.00 | 0.00 |
November | 0.617486E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -150240911.7 | 81.21 | 0.00 | 0.00 |
December | 0.637565E+10 | -0.621706E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158595165.5 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.753793E+11 | -0.735661E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.181313E+10 | 81.22 | 0.00 | 0.00 |
Minimum of Months | 0.577603E+10 | -0.629520E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160078891.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644824E+10 | -0.563426E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -141767061.5 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.194257E+11 | -0.185340E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -891694149.9 | 58.99 | 0.00 | 0.00 |
February | 0.171928E+11 | -0.164132E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -779510678.7 | 58.99 | 0.00 | 0.00 |
March | 0.179540E+11 | -0.171149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839128148.5 | 58.98 | 0.00 | 0.00 |
April | 0.155483E+11 | -0.147421E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -806233594.2 | 58.98 | 0.00 | 0.00 |
May | 0.142984E+11 | -0.134701E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -828264322.7 | 58.98 | 0.00 | 0.00 |
June | 0.125412E+11 | -0.117558E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -785480427.6 | 58.98 | 0.00 | 0.00 |
July | 0.122429E+11 | -0.114478E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795054296.0 | 58.98 | 0.00 | 0.00 |
August | 0.127932E+11 | -0.120004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -792756752.9 | 58.98 | 0.00 | 0.00 |
September | 0.135293E+11 | -0.127383E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -791066969.3 | 58.99 | 0.00 | 0.00 |
October | 0.157033E+11 | -0.148694E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -833915280.7 | 58.98 | 0.00 | 0.00 |
November | 0.169409E+11 | -0.161207E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -820201364.6 | 58.99 | 0.00 | 0.00 |
December | 0.188519E+11 | -0.179741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -877827115.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.187022E+12 | -0.177181E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.984113E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.122429E+11 | -0.185340E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -891694149.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.194257E+11 | -0.114478E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -779510678.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.77 | 0.75 | 01-JAN-07:00 | 748.10 | 24.40 | 204.50 | 282.17 | 796.41 | 24.69 | 209.33 | 284.83 |
February | 303.83 | 0.77 | 0.75 | 01-FEB-07:49 | 757.52 | 23.08 | 169.67 | 268.50 | 746.33 | 22.47 | 153.17 | 268.33 |
March | 364.50 | 0.77 | 0.75 | 01-MAR-07:40 | 794.71 | 20.57 | 129.83 | 324.50 | 809.13 | 20.28 | 122.67 | 325.83 |
April | 379.83 | 0.77 | 0.75 | 01-APR-07:10 | 822.73 | 19.45 | 88.67 | 336.83 | 712.27 | 19.43 | 82.33 | 336.17 |
May | 406.00 | 0.77 | 0.75 | 01-MAY-06:49 | 607.90 | 18.95 | 62.17 | 352.33 | 616.88 | 18.90 | 59.50 | 352.50 |
June | 386.67 | 0.78 | 0.75 | 01-JUN-07:19 | 544.61 | 18.80 | 60.17 | 331.67 | 546.90 | 18.59 | 46.67 | 332.83 |
July | 379.83 | 0.78 | 0.75 | 01-JUL-06:49 | 512.84 | 18.69 | 40.83 | 324.50 | 519.61 | 18.71 | 39.00 | 325.17 |
August | 372.50 | 0.78 | 0.75 | 01-AUG-06:00 | 535.98 | 18.66 | 51.83 | 313.83 | 527.87 | 18.66 | 53.33 | 312.17 |
September | 344.33 | 0.77 | 0.75 | 01-SEP-07:19 | 654.58 | 19.53 | 90.83 | 296.33 | 687.87 | 19.52 | 93.17 | 296.17 |
October | 347.33 | 0.77 | 0.75 | 01-OCT-07:10 | 793.75 | 21.15 | 149.33 | 302.50 | 812.02 | 21.34 | 154.83 | 302.00 |
November | 317.83 | 0.77 | 0.75 | 01-NOV-07:19 | 872.75 | 24.14 | 192.00 | 281.17 | 803.77 | 24.19 | 194.50 | 284.83 |
December | 315.50 | 0.77 | 0.75 | 01-DEC-07:30 | 818.26 | 24.11 | 201.17 | 284.17 | 870.35 | 26.07 | 219.67 | 287.00 |
Annual Sum or Average | 4237.50 | 0.77 | 698.45 | 20.78 | 1441.00 | 3698.50 | 696.50 | 20.87 | 1428.17 | 3707.83 | ||
Minimum of Months | 303.83 | 0.77 | 0.75 | 512.84 | 18.66 | 40.83 | 268.50 | 519.61 | 18.59 | 39.00 | 268.33 | |
Maximum of Months | 406.00 | 0.78 | 0.75 | 872.75 | 24.40 | 204.50 | 352.33 | 870.35 | 26.07 | 219.67 | 352.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.436928E+10 | 28522.61 | 01-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948370E+09 | 23815.43 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88050994.13 | 15780.23 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193000E+10 | 28145.60 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436928E+10 | 28522.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.321508E+09 | 8745.11 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2694376.21 | 1083.53 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86754175.24 | 7921.80 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.321508E+09 | 8745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.617505E+10 | 0.492559E+10 | 24523.13 | 12-JAN-14:00 | 20758.66 | 0.00 |
February | 0.00 | 0.00 | 0.176835E+11 | 0.138440E+11 | 36886.66 | 22-FEB-14:00 | 30982.99 | 0.00 |
March | 0.00 | 0.00 | 0.463983E+11 | 0.365577E+11 | 59341.18 | 10-MAR-18:20 | 38585.17 | 0.00 |
April | 0.00 | 0.00 | 0.786500E+11 | 0.658699E+11 | 77721.78 | 18-APR-12:00 | 54451.49 | 0.00 |
May | 0.00 | 0.00 | 0.118992E+12 | 0.873719E+11 | 121313.40 | 20-MAY-04:01 | 63368.71 | 0.00 |
June | 0.00 | 0.00 | 0.140352E+12 | 0.885730E+11 | 121313.40 | 16-JUN-04:01 | 53903.55 | 0.00 |
July | 0.00 | 0.00 | 0.163754E+12 | 0.825282E+11 | 121313.40 | 27-JUL-04:01 | 46647.41 | 0.00 |
August | 0.00 | 0.00 | 0.162717E+12 | 0.756504E+11 | 121313.40 | 01-AUG-04:01 | 44246.43 | 0.00 |
September | 0.00 | 0.00 | 0.131114E+12 | 0.658286E+11 | 121313.40 | 04-SEP-04:01 | 40555.33 | 0.00 |
October | 0.00 | 0.00 | 0.734350E+11 | 0.518018E+11 | 113390.44 | 04-OCT-04:01 | 55570.01 | 0.00 |
November | 0.00 | 0.00 | 0.343088E+11 | 0.268320E+11 | 50421.67 | 09-NOV-13:00 | 40307.15 | 0.00 |
December | 0.00 | 0.00 | 0.101523E+11 | 0.792347E+10 | 29535.51 | 28-DEC-14:00 | 24209.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.983732E+12 | 0.607706E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.617505E+10 | 0.492559E+10 | 24523.13 | 20758.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.163754E+12 | 0.885730E+11 | 121313.40 | 63368.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.439970E+10 | 0.336988E+10 | 41091.96 | 17-JAN-05:01 | 24691.53 | 0.00 |
February | 0.00 | 0.00 | 0.120333E+11 | 0.934439E+10 | 41091.96 | 10-FEB-05:01 | 24629.82 | 0.00 |
March | 0.00 | 0.00 | 0.298002E+11 | 0.243138E+11 | 41091.96 | 08-MAR-05:01 | 26260.46 | 0.00 |
April | 0.00 | 0.00 | 0.516259E+11 | 0.457086E+11 | 44331.18 | 25-APR-03:31 | 22016.86 | 0.00 |
May | 0.00 | 0.00 | 0.788840E+11 | 0.616534E+11 | 45655.87 | 20-MAY-04:01 | 26083.51 | 0.00 |
June | 0.00 | 0.00 | 0.891426E+11 | 0.598363E+11 | 45655.87 | 24-JUN-11:20 | 17404.54 | 0.00 |
July | 0.00 | 0.00 | 0.101815E+12 | 0.519195E+11 | 45655.87 | 11-JUL-10:00 | 20304.76 | 0.00 |
August | 0.00 | 0.00 | 0.101468E+12 | 0.457461E+11 | 45655.87 | 10-AUG-14:50 | 16485.86 | 0.00 |
September | 0.00 | 0.00 | 0.901197E+11 | 0.439077E+11 | 45655.87 | 01-SEP-04:02 | 19125.00 | 0.00 |
October | 0.00 | 0.00 | 0.489947E+11 | 0.351729E+11 | 45655.87 | 06-OCT-10:48 | 24997.55 | 0.00 |
November | 0.00 | 0.00 | 0.218988E+11 | 0.174940E+11 | 41091.96 | 04-NOV-04:01 | 26197.50 | 0.00 |
December | 0.00 | 0.00 | 0.746636E+10 | 0.567499E+10 | 41091.96 | 15-DEC-05:01 | 25730.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.637649E+12 | 0.404142E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.439970E+10 | 0.336988E+10 | 41091.96 | 16485.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101815E+12 | 0.616534E+11 | 45655.87 | 26260.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 7382.68 | 14039.77 | 19-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7247.98 | 13958.69 | 01-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6854.15 | 13368.66 | 01-MAR-19:13 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6153.74 | 12190.52 | 03-APR-18:23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5496.67 | 10969.19 | 01-MAY-18:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5004.63 | 9774.39 | 01-JUN-18:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4744.76 | 9040.16 | 03-JUL-18:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4950.17 | 9615.17 | 31-AUG-18:42 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5382.98 | 10654.58 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 6018.27 | 12056.23 | 31-OCT-18:23 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6684.33 | 13170.22 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 7174.12 | 13879.73 | 28-DEC-07:15 |
Annual Sum or Average | 0.00 | 6084.82 | ||||
Minimum of Months | 0.00 | 0.00 | 4744.76 | 9040.16 | ||
Maximum of Months | 0.00 | 0.00 | 7382.68 | 14039.77 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191660E+10 | 0.23 | 824.13 | 01-JAN-00:02 | 0.27 |
February | 0.178948E+10 | 0.24 | 824.13 | 01-FEB-00:03 | 0.27 |
March | 0.207730E+10 | 0.25 | 824.13 | 01-MAR-00:03 | 0.27 |
April | 0.203911E+10 | 0.26 | 824.13 | 01-APR-00:20 | 0.27 |
May | 0.210448E+10 | 0.26 | 824.13 | 01-MAY-00:12 | 0.27 |
June | 0.203681E+10 | 0.25 | 824.13 | 01-JUN-00:12 | 0.27 |
July | 0.210569E+10 | 0.25 | 824.13 | 01-JUL-00:08 | 0.27 |
August | 0.210583E+10 | 0.25 | 824.13 | 01-AUG-00:07 | 0.27 |
September | 0.203577E+10 | 0.25 | 824.13 | 01-SEP-00:08 | 0.27 |
October | 0.210163E+10 | 0.26 | 824.13 | 01-OCT-00:09 | 0.27 |
November | 0.198768E+10 | 0.25 | 824.13 | 01-NOV-00:30 | 0.27 |
December | 0.193180E+10 | 0.24 | 824.13 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.242322E+11 | 0.25 | |||
Minimum of Months | 0.178948E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.210583E+10 | 0.26 | 824.13 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.690833E+10 | 0.73 | 4074.74 | 01-JAN-06:03 | 1.04 |
February | 0.612923E+10 | 0.72 | 3901.16 | 02-FEB-06:03 | 1.01 |
March | 0.674796E+10 | 0.72 | 3252.81 | 28-MAR-17:10 | 0.90 |
April | 0.672442E+10 | 0.73 | 4792.13 | 26-APR-17:10 | 1.13 |
May | 0.797622E+10 | 0.79 | 7557.36 | 02-MAY-04:01 | 1.41 |
June | 0.888483E+10 | 0.85 | 7557.36 | 03-JUN-04:01 | 1.41 |
July | 0.997461E+10 | 0.89 | 7557.36 | 01-JUL-04:01 | 1.40 |
August | 0.990655E+10 | 0.88 | 7557.36 | 01-AUG-04:01 | 1.40 |
September | 0.809950E+10 | 0.80 | 7557.36 | 01-SEP-04:01 | 1.40 |
October | 0.683012E+10 | 0.72 | 6965.75 | 04-OCT-04:01 | 1.36 |
November | 0.653281E+10 | 0.72 | 3604.85 | 27-NOV-06:03 | 0.96 |
December | 0.681838E+10 | 0.72 | 4060.84 | 23-DEC-06:03 | 1.04 |
Annual Sum or Average | 0.915330E+11 | 0.77 | |||
Minimum of Months | 0.612923E+10 | 0.72 | 3252.81 | 0.90 | |
Maximum of Months | 0.997461E+10 | 0.89 | 7557.36 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161370E+10 | 0.47 | 1794.83 | 17-JAN-05:01 | 0.90 |
February | 0.145916E+10 | 0.49 | 1794.83 | 10-FEB-05:01 | 0.90 |
March | 0.173815E+10 | 0.54 | 1794.83 | 07-MAR-04:11 | 0.90 |
April | 0.218685E+10 | 0.61 | 1794.83 | 17-APR-10:43 | 0.89 |
May | 0.314895E+10 | 0.71 | 1794.83 | 01-MAY-10:53 | 0.89 |
June | 0.356450E+10 | 0.77 | 1794.83 | 02-JUN-03:21 | 0.89 |
July | 0.404429E+10 | 0.80 | 1794.83 | 01-JUL-04:01 | 0.89 |
August | 0.399298E+10 | 0.79 | 1794.83 | 01-AUG-03:21 | 0.88 |
September | 0.350835E+10 | 0.76 | 1794.83 | 01-SEP-03:22 | 0.88 |
October | 0.213184E+10 | 0.59 | 1794.83 | 01-OCT-04:01 | 0.89 |
November | 0.159517E+10 | 0.52 | 1794.83 | 04-NOV-04:01 | 0.90 |
December | 0.161165E+10 | 0.48 | 1794.83 | 15-DEC-05:01 | 0.90 |
Annual Sum or Average | 0.305956E+11 | 0.63 | |||
Minimum of Months | 0.145916E+10 | 0.47 | 1794.83 | 0.88 | |
Maximum of Months | 0.404429E+10 | 0.80 | 1794.83 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:02 | 5.36 | 5.36 | 50.29 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 50.98 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.38 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 52.95 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:02 | 5.36 | 5.36 | 54.44 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 55.03 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 55.45 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.45 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 54.29 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:02 | 5.36 | 5.36 | 52.99 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 54.12 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:03 | 5.36 | 5.36 | 51.45 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.29 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.45 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 50.29 | 59.88 | 7382.68 | 14039.77 | 19-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.98 | 59.70 | 7247.98 | 13958.69 | 01-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.38 | 59.62 | 6854.15 | 13368.66 | 01-MAR-19:13 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.04 | 52.04 | 6153.74 | 12190.52 | 03-APR-18:23 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.49 | 53.49 | 5496.67 | 10969.19 | 01-MAY-18:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.92 | 53.92 | 5004.63 | 9774.39 | 01-JUN-18:38 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.62 | 54.62 | 4744.76 | 9040.16 | 03-JUL-18:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.74 | 53.74 | 4950.17 | 9615.17 | 31-AUG-18:42 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.54 | 53.54 | 5382.98 | 10654.58 | 29-SEP-18:33 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.47 | 51.47 | 6018.27 | 12056.23 | 31-OCT-18:23 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.85 | 52.85 | 6684.33 | 13170.22 | 30-NOV-19:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.45 | 59.75 | 7174.12 | 13879.73 | 28-DEC-07:15 |
Annual Sum or Average | 0.00 | 6084.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.29 | 51.47 | 4744.76 | 9040.16 | ||
Maximum of Months | 0.00 | 0.00 | 54.62 | 59.88 | 7382.68 | 14039.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.893018E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116857E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.205661E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.301941E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.432797E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.494664E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.540836E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.525039E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.424153E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.276574E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.168750E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100947E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.367752E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.893018E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.540836E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.287940E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.470120E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.931930E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.155368E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.236794E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.264067E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.287189E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.279250E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.245933E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140797E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720019E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.369999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.188740E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.287940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.287189E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.690833E+10 | 0.617505E+10 | 0.436928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612923E+10 | 0.176835E+11 | 0.948370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674796E+10 | 0.463983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672442E+10 | 0.786500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.797622E+10 | 0.118992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888483E+10 | 0.140352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997461E+10 | 0.163754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.990655E+10 | 0.162717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.809950E+10 | 0.131114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683012E+10 | 0.734350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653281E+10 | 0.343088E+11 | 88050994.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.681838E+10 | 0.101523E+11 | 0.193000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915330E+11 | 0.983732E+12 | 0.733570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.612923E+10 | 0.617505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997461E+10 | 0.163754E+12 | 0.436928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161370E+10 | 0.439970E+10 | 0.321508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145916E+10 | 0.120333E+11 | 2694376.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173815E+10 | 0.298002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218685E+10 | 0.516259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314895E+10 | 0.788840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356450E+10 | 0.891426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.404429E+10 | 0.101815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399298E+10 | 0.101468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350835E+10 | 0.901197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213184E+10 | 0.489947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159517E+10 | 0.218988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161165E+10 | 0.746636E+10 | 86754175.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305956E+11 | 0.637649E+12 | 0.410957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145916E+10 | 0.439970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.404429E+10 | 0.101815E+12 | 0.321508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.690833E+10 | 0.00 | 0.00 | 0.00 | 0.202185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612923E+10 | 0.00 | 0.00 | 0.00 | 0.555647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674796E+10 | 0.00 | 0.00 | 0.00 | 0.138181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672442E+10 | 0.00 | 0.00 | 0.00 | 0.234697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.797622E+10 | 0.00 | 0.00 | 0.00 | 0.353035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.888483E+10 | 0.00 | 0.00 | 0.00 | 0.405815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997461E+10 | 0.00 | 0.00 | 0.00 | 0.441090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.990655E+10 | 0.00 | 0.00 | 0.00 | 0.425973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.809950E+10 | 0.00 | 0.00 | 0.00 | 0.343158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683012E+10 | 0.00 | 0.00 | 0.00 | 0.208273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653281E+10 | 0.00 | 0.00 | 0.00 | 0.103422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.681838E+10 | 0.00 | 0.00 | 0.00 | 0.327629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.915330E+11 | 0.00 | 0.00 | 0.00 | 0.276219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.612923E+10 | 0.00 | 0.00 | 0.00 | 0.202185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997461E+10 | 0.00 | 0.00 | 0.00 | 0.441090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161370E+10 | 0.00 | 0.00 | 0.00 | 0.126570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145916E+10 | 0.00 | 0.00 | 0.00 | 0.324204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173815E+10 | 0.00 | 0.00 | 0.00 | 0.758115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218685E+10 | 0.00 | 0.00 | 0.00 | 0.133500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314895E+10 | 0.00 | 0.00 | 0.00 | 0.205305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356450E+10 | 0.00 | 0.00 | 0.00 | 0.228422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.404429E+10 | 0.00 | 0.00 | 0.00 | 0.246747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399298E+10 | 0.00 | 0.00 | 0.00 | 0.239320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.350835E+10 | 0.00 | 0.00 | 0.00 | 0.210849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213184E+10 | 0.00 | 0.00 | 0.00 | 0.119479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159517E+10 | 0.00 | 0.00 | 0.00 | 0.560501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161165E+10 | 0.00 | 0.00 | 0.00 | 0.208835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305956E+11 | 0.00 | 0.00 | 0.00 | 0.158144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145916E+10 | 0.00 | 0.00 | 0.00 | 0.126570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.404429E+10 | 0.00 | 0.00 | 0.00 | 0.246747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239514E+11 | 0.00 | 0.00 | 42528460.78 | 0.00 | 0.108531E+09 | 0.159825E+11 | 0.00 | 3.58 |
February | 0.121095E+11 | 0.101875E+09 | 0.00 | 66754899.84 | 0.00 | 41614113.47 | 0.128051E+11 | 0.00 | 3.60 |
March | 0.363497E+10 | 0.489574E+10 | 0.00 | 73601510.86 | 5341004.22 | 0.00 | 0.832490E+10 | 0.00 | 3.62 |
April | 0.318104E+09 | 0.195925E+11 | 0.00 | 14431827.75 | 0.226926E+09 | 0.00 | 0.118890E+10 | 0.00 | 3.64 |
May | 15689882.22 | 0.467947E+11 | 0.00 | 1128714.35 | 0.803853E+09 | 0.00 | 31945896.59 | 0.00 | 3.67 |
June | 6342582.12 | 0.637695E+11 | 0.00 | 641462.25 | 0.140479E+10 | 0.00 | 13192478.60 | 0.00 | 3.68 |
July | 0.00 | 0.812851E+11 | 0.00 | 354923.66 | 0.160215E+10 | 0.00 | 2957081.30 | 0.00 | 3.70 |
August | 2401487.25 | 0.800919E+11 | 0.00 | 1605919.76 | 0.135887E+10 | 0.00 | 9008161.80 | 0.00 | 3.69 |
September | 7221606.12 | 0.583712E+11 | 0.00 | 1971990.32 | 0.907676E+09 | 0.00 | 21233808.64 | 0.00 | 3.67 |
October | 0.130487E+10 | 0.159777E+11 | 0.00 | 21731713.49 | 66374781.34 | 0.00 | 0.311794E+10 | 0.00 | 3.63 |
November | 0.704362E+10 | 0.197178E+10 | 0.00 | 82197289.93 | 0.00 | 3559330.85 | 0.113134E+11 | 0.00 | 3.61 |
December | 0.195549E+11 | 0.00 | 0.00 | 57181271.08 | 0.00 | 79064243.89 | 0.165262E+11 | 0.00 | 3.58 |
Annual Sum or Average | 0.679491E+11 | 0.372852E+12 | 0.00 | 0.364130E+09 | 0.637597E+10 | 0.232769E+09 | 0.693373E+11 | 0.00 | 3.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 354923.66 | 0.00 | 0.00 | 2957081.30 | 0.00 | 3.58 |
Maximum of Months | 0.239514E+11 | 0.812851E+11 | 0.00 | 82197289.93 | 0.160215E+10 | 0.108531E+09 | 0.165262E+11 | 0.00 | 3.70 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160836E+11 | 0.00 | 0.00 | 62092469.06 | 0.00 | 0.00 | 0.271198E+11 | 0.00 | 8.01 |
February | 0.763347E+10 | 0.00 | 0.00 | 84474385.46 | 0.00 | 0.00 | 0.232545E+11 | 0.00 | 8.08 |
March | 0.834818E+09 | 0.117664E+10 | 0.00 | 0.126932E+09 | 0.00 | 0.00 | 0.189468E+11 | 0.00 | 8.33 |
April | 22134687.97 | 0.749808E+10 | 0.00 | 73753261.19 | 0.00 | 0.00 | 0.488786E+10 | 0.00 | 8.78 |
May | 1023174.24 | 0.267674E+11 | 0.00 | 5137937.83 | 0.00 | 0.00 | 0.138657E+09 | 0.00 | 9.19 |
June | 0.00 | 0.380017E+11 | 0.00 | 391350.89 | 0.00 | 0.00 | 8124514.50 | 0.00 | 9.55 |
July | 0.00 | 0.501476E+11 | 0.00 | 15370.73 | 0.00 | 0.00 | 52337.53 | 0.00 | 9.82 |
August | 0.00 | 0.499670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
September | 0.00 | 0.404338E+11 | 0.00 | 536709.76 | 0.00 | 0.00 | 23194150.79 | 0.00 | 9.42 |
October | 0.112508E+09 | 0.701607E+10 | 0.00 | 80070248.56 | 578586.49 | 0.00 | 0.727985E+10 | 0.00 | 8.72 |
November | 0.285505E+10 | 0.154771E+09 | 0.00 | 0.135402E+09 | 0.00 | 0.00 | 0.234523E+11 | 0.00 | 8.18 |
December | 0.129371E+11 | 0.00 | 0.00 | 79345104.51 | 0.00 | 0.00 | 0.279177E+11 | 0.00 | 8.01 |
Annual Sum or Average | 0.404797E+11 | 0.221163E+12 | 0.00 | 0.648151E+09 | 578586.49 | 0.00 | 0.133029E+12 | 0.00 | 8.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
Maximum of Months | 0.160836E+11 | 0.501476E+11 | 0.00 | 0.135402E+09 | 578586.49 | 0.00 | 0.279177E+11 | 0.00 | 9.82 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.535062E+11 | 0.886066E+10 | 0.148559E+12 | 0.105085E+11 | 0.375037E+11 |
February | 0.638320E+11 | 0.639800E+10 | 0.107017E+12 | 0.824279E+10 | 0.605812E+11 |
March | 0.916084E+11 | 0.402600E+10 | 0.637824E+11 | 0.603609E+10 | 0.124517E+12 |
April | 0.112329E+12 | -617712228.2 | -0.148444E+11 | 0.144547E+10 | 0.195230E+12 |
May | 0.122376E+12 | -0.629485E+10 | -0.100567E+12 | -355941103.0 | 0.283979E+12 |
June | 0.108865E+12 | -0.983566E+10 | -0.144877E+12 | -0.189635E+10 | 0.322539E+12 |
July | 0.894042E+11 | -0.138913E+11 | -0.189414E+12 | -0.197412E+10 | 0.360440E+12 |
August | 0.748793E+11 | -0.146848E+11 | -0.187637E+12 | -447379143.8 | 0.356014E+12 |
September | 0.783915E+11 | -0.112279E+11 | -0.144681E+12 | 0.500595E+09 | 0.301537E+12 |
October | 0.722624E+11 | -0.136203E+10 | 0.303043E+10 | 0.499336E+10 | 0.184770E+12 |
November | 0.588883E+11 | 0.362764E+10 | 0.909154E+11 | 0.828039E+10 | 0.989539E+11 |
December | 0.478232E+11 | 0.796226E+10 | 0.141018E+12 | 0.108567E+11 | 0.469362E+11 |
Annual Sum or Average | 0.974166E+12 | -0.270397E+11 | -0.227698E+12 | 0.461901E+11 | 0.237300E+13 |
Minimum of Months | 0.478232E+11 | -0.146848E+11 | -0.189414E+12 | -0.197412E+10 | 0.375037E+11 |
Maximum of Months | 0.122376E+12 | 0.886066E+10 | 0.148559E+12 | 0.108567E+11 | 0.360440E+12 |