Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:28:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2071.38 | 4052.37 | 4052.37 |
Net Site Energy | 2071.38 | 4052.37 | 4052.37 |
Total Source Energy | 5079.08 | 9936.52 | 9936.52 |
Net Source Energy | 5079.08 | 9936.52 | 9936.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 538.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.36 | 241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 56.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1360.40 | 710.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 538.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 155.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.36 | 241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 538.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 155.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.36 | 241.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 56.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1507.23 | 471.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 990.05 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2661.43 | 1390.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1507.23 | 471.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 990.05 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2661.43 | 1390.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1360.397 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1360.397 | 100.00 |
Total On-Site and Utility Electric Sources | 1360.397 | 100.00 |
Total Electricity End Uses | 1360.397 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1832.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6898.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.9552 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.1538 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.9552 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.1538 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.2821 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:00 | 07-JAN-11:20 | - | - | - | - | - | - | - | - | - | - | 15-FEB-07:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52016.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22750.50 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9829.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2993.57 | 16649.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1769.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 91867.00 | 42897.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52016.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9829.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2993.57 | 16649.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 499.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1706.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 493.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 238.67 | 261.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 177.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4308.38 | 770.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3338.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 964.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.92 | 511.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 347.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8428.74 | 1507.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3338.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 964.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 466.92 | 511.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 347.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8428.74 | 1507.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 4.56 |
KITCHEN DIRECT AIR | 1.67 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 4.56 | 4.56 | 4.56 | 4.56 | 4.56 | 4.56 | 1.00 | 0.999939 | 4.56 |
PSZ-AC_2:2 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.00 | 1.00 | 1.67 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 4.56 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.67 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 4.56 | 7727.25 |
PSZ-AC_2:2_ADDAQ FAN | 1.67 | 1790.68 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 4.56 | 4.56 | 4.56 | 3.01 | 113163.34 | 118077.34 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.10 | 41555.91 | 62264.93 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 4.56 | 2.28 | 3.04 | 113163.34 | 56581.67 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.67 | 0.836728 | 1.12 | 41555.91 | 20777.96 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 118077.34 |
PSZ-AC_2:2 HEATING COIL | 62264.93 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.955 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.883 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.154 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1068.794 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2585.575 | 6.955 | 9.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2585.575 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1136.687 | 8.154 | 150.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1136.687 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6599 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27676364E-12 | 0.14086114E-14 | -0.80726913E-13 | 0.13375353E-15 |
34 | 6 | 0.24570021E-07 | 0.29950613E-09 | 0.56627273E-08 | -0.11332356E-12 |
35 | 5 | -0.16904970E-03 | 0.26370238E-05 | -0.87195956E-04 | 0.56086003E-08 |
36 | 4 | 0.26716054 | 0.13159717E-02 | 0.90714244E-01 | -0.30081483E-04 |
37 | 3 | -6.7706711 | 0.41679210E-01 | -2.1918931 | 0.26582329E-01 |
38 | 2 | 39.235515 | 0.15105986 | 14.660025 | -0.31512872 |
39 | 1 | -79.291398 | 0.69309750E-01 | -28.598630 | 1.0518895 |
40 | 0 | 46.824347 | 0.14172498E-02 | 16.304656 | |
41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.6398E-004 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.5401E-003 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.9084E-004 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 8.2416E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 8.2221E-004 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 7.7749E-003 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 6.8584E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 6.2816E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.1755E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1082E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.2679E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1900E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.5681E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.5307E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.4376E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.4378E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.3404E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 8.2741E-004 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.8212E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 7.2493E-004 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.1767E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8126E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 6.2816E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 6.8584E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 52031.71928 | 62438.06313 | 3.79734 | 4.55681 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 1364.02548 | 1636.83057 | 5.84942E-002 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 12.70000 | 9.15345E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 22530.97622 | 27037.17146 | 1.39455 | 1.67346 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.21700 | 00:10:00 | 12.70000 | 9.15345E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 91937.73 | 4.55709 | 4.55709 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 43959.14 | 1.33138 | 1.33138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 50275.86 | 1.67346 | 1.67346 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 40182.71 | 1.21700 | 1.21700 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.55681 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67346 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.55681 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.55681 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.55681 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 4.55681 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55709 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 4.55709 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99994 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67346 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67346 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67346 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67346 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67346 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67346 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 4.55709 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.67346 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55709 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.55709 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 7727.24547 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.55709 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.55709 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.55709 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.00768 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.55709 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.27854 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.03806 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 113163.34000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 56581.67000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 113163.34000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 118077.34067 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 118077.34067 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67346 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67346 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1790.67749 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67346 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67346 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67346 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10448 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67346 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83673 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11564 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41555.91000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20777.95500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41555.91000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62264.93410 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 62264.93410 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 109924.3 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 40366.5 | 11.66 | 11.61 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.119 | 0.958 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.6659532574E-002 | 0.2025897922 | Pass | Pass | 3.3888541369E-002 | 9.3154147972E-002 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2159938388 | 0.6353018206 | Pass | Pass | 5.7139992035E-002 | 0.2339452021 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3222241189 | 0.2549175781 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 980.98 | -66.7 | -684.4 | 30.03 | 2816.63 | 3076.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.958 | 1.119 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.9552 | 371.75 | 2585.58 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.14 | 0.0000 | Y | 38.41 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.1538 | 139.41 | 1136.69 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 16.28 |
Interior Lighting Total | 7.2821 | 511.15 | 3722.26 | 54.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2585.58 | 646.39 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2585.58 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 159.78 | AstronomicalClock | - | 48.85 | 48.85 | 1.47 | |
EXTERIOR_LIGHTS_B | 2015.63 | AstronomicalClock | - | 83.85 | 73.35 | 27.75 | |
Exterior Lighting Total | 2175.41 | 29.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 113163.34 | 79336.55 | 33826.79 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41555.91 | 29134.02 | 12421.89 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 109924.3 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 40366.5 | 11.66 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 118077.34 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 62264.93 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 4.56 | 7727.25 | 1695.65 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.67 | 1790.68 | 1070.05 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 52031.72 | 62438.06 | 167.96 | 3.797 | 4.557 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 23.99 | 0.00869 | 42.70 | 0.01078 | 1.331 | 0.00 |
KITCHEN | 22530.98 | 27037.17 | 193.95 | 1.395 | 1.673 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.00 | 25.99 | 0.00874 | 41.93 | 0.01078 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 1364.03 | 1636.83 | 4.40 | 0.058 | 1.331 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 1.331 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.217 | 00:10:00 | 19.00 | 28.33 | 0.00678 | 12.70 | 0.00915 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 4.56 | 4.56 | 1.33 | 1.33 | 4.5571 | 4.5568 | 4.5571 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.67 | 1.67 | 1.22 | 1.22 | 1.6735 | 1.6735 | 1.6735 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 113163.340 | 79336.554 | 4.557090 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 56581.67 | 44271.98 | 3.038060 | 29.48 | 18.90 | 0.00929837 | 11.42 | 9.95 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 43.8233 | 23.99 | 0.00868609 | 46.7575 | 52030.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 118077.341 | 118077.341 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 118077.34 | 118077.34 | 4.557088 | 18.58 | 14.35 | 0.00846248 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 29.2155 | 21.00 | 0.00817730 | 52.8233 | 1360.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 41555.910 | 29134.017 | 1.673460 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 20777.96 | 16269.01 | 1.115640 | 38.75 | 22.42 | 0.01029206 | 11.93 | 10.17 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 109.0855 | 25.99 | 0.00874305 | 41.7737 | 22530.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 62264.934 | 62264.934 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 62264.93 | 62264.93 | 1.673456 | 9.24 | 9.24 | 0.00850495 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 72.7239 | 28.33 | 0.00677592 | 28.3004 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 113163.340 | 79336.554 | 4.557090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1252 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.557088 | 5.48488782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 56581.67 | 44271.98 | 1.0000 | 3.65659377 | 3.038060 | 29.48 | 18.90 | 0.00929837 | 53387.9 | 11.42 | 9.95 | 0.00700000 | 29132.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56581.67 | 42.80 | 0.01078182 | 23.86 | 1.33137743 | 43.8233 | 23.98 | 0.00868609 | 23.99 | 0.00868609 | 46.7575 | 52030.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 118077.341 | 118077.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 4.557088 | 5.48488782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | Sensible | 118077.34 | 118077.34 | 1.0000 | 5.48488782 | 4.557088 | 18.58 | 14.35 | 0.00846248 | 40121.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 118077.34 | 12.70 | 0.00915345 | 12.70 | 1.33137743 | 29.2155 | 21.00 | 0.00817730 | 21.00 | 0.00817730 | 52.8233 | 1360.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41555.910 | 29134.017 | 1.673460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9724 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.673456 | 2.01416376 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 20777.96 | 16269.01 | 1.0000 | 1.34277871 | 1.115640 | 38.75 | 22.42 | 0.01029206 | 65420.8 | 11.93 | 10.17 | 0.00700000 | 29651.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20777.96 | 42.80 | 0.01078182 | 23.86 | 1.21700195 | 109.0855 | 25.95 | 0.00874305 | 25.99 | 0.00874305 | 41.7737 | 22530.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62264.934 | 62264.934 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.673456 | 2.01416376 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 62264.93 | 62264.93 | 1.0000 | 2.01416376 | 1.673456 | 9.24 | 9.24 | 0.00850495 | 30697.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62264.93 | 12.70 | 0.00915345 | 12.70 | 1.21700195 | 72.7239 | 0.00 | 0.00677592 | 28.33 | 0.00677592 | 28.3004 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6892.33 | 2960.67 | 2797.50 |
KITCHEN | 7182.67 | 6898.50 | 6898.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7182.67 | 7061.17 | 6898.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 46.67 | 0.00 | 46.67 |
KITCHEN | 0.00 | 2170.50 | 0.00 | 1832.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 2170.50 | 0.00 | 1832.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.370 | 0.880 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 10.377 | 0.028 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.235 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.426 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 35029594.15 | 0.00 | 35029594.15 | 7007285.43 | 42036879.57 | 41986318.57 | 1458.12 | 7301.88 | 0.00 | 133.62 |
KITCHEN | 32224594.03 | 0.00 | 32224594.03 | 118319.23 | 32342913.26 | 38379373.44 | 4468.04 | 4228.26 | 63.70 | 1081.39 |
Total Facility | 67254188.17 | 0.00 | 67254188.17 | 7125604.66 | 74379792.83 | 80365692.01 | 4537.94 | 7309.05 | 63.70 | 1090.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3316 | 0.0000 | 1.3316 | 0.2685 | 1.6001 | 1.3314 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 1.1733 | 0.0000 | 1.1733 | 0.0031 | 1.1764 | 1.2170 | 2992.08 | 4194.92 | 0.00 |
Total Facility | 2.5049 | 0.0000 | 2.5049 | 0.2716 | 2.7765 | 2.5484 | 2992.08 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 50742132.95 | 0.00 | 50742132.95 | 41986318.57 | 1456.43 | 0.26 | 7303.31 | 133.62 |
PSZ-AC_2:2 | 46681103.37 | 0.00 | 46681103.37 | 38379373.44 | 1313.05 | 4.37 | 7442.58 | 1081.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6996 | 0.0000 | 1.6996 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 18.74 | 0.00 | 7301.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 5629.19 | 2639.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7489 | 1.6152 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
Electricity:Building | 511.61 | 3281.23 | 01-JAN-01:10 | 28991.58 | 02-JAN-11:10 |
Electricity:Zone:DINING | 163.69 | 856.89 | 01-JAN-01:10 | 8683.37 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 504.68 | 3144.96 | 01-JAN-01:10 | 26848.48 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.69 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 38.41 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.69 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 54.69 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 38.41 | 374.16 | 01-JAN-01:10 | 2244.98 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.69 | 508.34 | 01-JAN-01:10 | 3050.12 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 347.92 | 2424.34 | 01-JAN-01:10 | 20308.21 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 56.07 | 1004.46 | 02-JAN-23:30 | 3219.34 | 09-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 124.95 | 1191.11 | 20-JAN-01:10 | 6586.45 | 24-JUN-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.92 | 0.00 | 01-JAN-11:10 | 1532.35 | 18-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 33.23 | 868.51 | 21-JAN-05:20 | 1076.23 | 01-JAN-04:30 |
ElectricityPurchased:Facility | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
ElectricityPurchased:Plant | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
Cogeneration:ElectricityPurchased | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
ElectricityNet:Plant | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
Cogeneration:ElectricityNet | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
General:Cogeneration:ElectricityNet | 1360.40 | 5883.28 | 20-JAN-01:10 | 91867.00 | 16-AUG-12:00 |
Electricity:HVAC | 694.62 | 0.00 | 01-JAN-01:10 | 61846.52 | 16-AUG-12:00 |
Fans:Electricity | 155.75 | 0.00 | 01-JAN-01:10 | 10342.05 | 23-JUN-12:00 |
General:Fans:Electricity | 155.75 | 0.00 | 01-JAN-01:10 | 10342.05 | 23-JUN-12:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 538.87 | 0.00 | 01-JAN-00:10 | 52016.94 | 16-AUG-12:00 |
General:Cooling:Electricity | 538.87 | 0.00 | 01-JAN-00:10 | 52016.94 | 16-AUG-12:00 |
ExteriorLights:Electricity | 29.22 | 0.00 | 01-JAN-07:10 | 2175.41 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 29.22 | 0.00 | 01-JAN-07:10 | 2175.41 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.36 | 0.00 | 01-JAN-01:10 | 4739.23 | 09-JAN-07:20 |
Water Heater:WaterSystems:Electricity | 75.36 | 0.00 | 01-JAN-01:10 | 4739.23 | 09-JAN-07:20 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 25-MAR-10:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 710.98 | 2758.01 | 01-JAN-01:10 | 42897.82 | 07-JAN-11:20 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 0.01 | 0.00 | 01-JAN-00:10 | 1360.67 | 16-JAN-06:10 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 1360.67 | 16-JAN-06:10 |
General:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 1360.67 | 16-JAN-06:10 |
NaturalGas:Plant | 241.18 | 947.76 | 01-JAN-01:10 | 17305.15 | 03-JAN-07:20 |
WaterSystems:NaturalGas | 241.18 | 947.76 | 01-JAN-01:10 | 17305.15 | 03-JAN-07:20 |
Water Heater:WaterSystems:NaturalGas | 241.18 | 947.76 | 01-JAN-01:10 | 17305.15 | 03-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 15-FEB-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3172.77 | 3641.59 | 20-JAN-01:10 | 228412.50 | 09-SEP-18:40 |
EnergyTransfer:Building | 953.14 | 1820.79 | 20-JAN-01:10 | 61366.06 | 30-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 472.30 | 1820.79 | 20-JAN-01:10 | 26387.82 | 09-OCT-10:50 |
Refrigeration:EnergyTransfer | 162.02 | 3532.08 | 02-JAN-23:30 | 7834.84 | 03-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.01 | 1766.04 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 81.01 | 1766.04 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.01 | 1766.04 | 02-JAN-23:30 | 3917.42 | 03-JAN-04:50 |
EnergyTransfer:Plant | 241.40 | 1820.79 | 20-JAN-01:10 | 14621.25 | 09-JAN-19:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.55 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.46 | 1615.54 | 21-JAN-05:20 | 2238.70 | 01-JAN-04:30 |
EnergyTransfer:Zone:DINING | 480.85 | 0.00 | 01-JAN-01:10 | 42172.04 | 16-AUG-12:00 |
Heating:EnergyTransfer | 4.05 | 0.00 | 01-JAN-00:10 | 15540.40 | 20-JUL-23:10 |
Heating:EnergyTransfer:Zone:DINING | 4.05 | 0.00 | 01-JAN-00:10 | 15540.40 | 20-JUL-23:10 |
General:Heating:EnergyTransfer | 4.05 | 0.00 | 01-JAN-00:10 | 15540.40 | 20-JUL-23:10 |
General:Heating:EnergyTransfer:Zone:DINING | 4.05 | 0.00 | 01-JAN-00:10 | 15540.40 | 20-JUL-23:10 |
Cooling:EnergyTransfer | 868.08 | 0.00 | 01-JAN-01:10 | 58316.41 | 30-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 476.79 | 0.00 | 01-JAN-01:10 | 42172.04 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer | 868.08 | 0.00 | 01-JAN-01:10 | 58316.41 | 30-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 476.79 | 0.00 | 01-JAN-01:10 | 42172.04 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 335.38 | 03-JUL-04:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 335.38 | 03-JUL-04:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 391.29 | 0.00 | 01-JAN-01:10 | 22716.72 | 20-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 391.29 | 0.00 | 01-JAN-01:10 | 22716.72 | 20-JUL-19:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
PlantLoopHeatingDemand:Plant | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
General:WaterSystems:PlantLoopHeatingDemand | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
EnergyTransfer:HVAC | 1978.23 | 0.00 | 01-JAN-00:10 | 166710.48 | 21-AUG-20:00 |
HeatingCoils:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 1088.54 | 16-JAN-06:10 |
CoolingCoils:EnergyTransfer | 1978.22 | 0.00 | 01-JAN-00:10 | 166710.48 | 21-AUG-20:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 160.39 | 0.00 | 01-JAN-01:10 | 12020.89 | 10-JAN-07:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 4.056 | -476.787 | 0.000 | 0.000 | 206.227 | 38.411 | 93.957 | 45.996 | 0.000 | 50.761 | 51.455 | 0.000 | -6.469 | 0.000 | -7.606 | -0.001 |
KITCHEN | 0.000 | 0.000 | 0.000 | -391.281 | 0.000 | 0.000 | 4.415 | 16.277 | 287.132 | 0.000 | 0.000 | 0.427 | 83.424 | 0.000 | 0.000 | 0.000 | -0.394 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.488 | 26.311 | 0.000 | 0.000 | 0.000 | -39.799 | -0.001 |
Total Facility | 0.000 | 0.000 | 4.057 | -868.069 | 0.000 | 0.000 | 210.642 | 54.687 | 381.090 | 45.996 | 0.000 | 64.676 | 161.190 | 0.000 | -6.469 | 0.000 | -47.799 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-MAY-04:01 | 0.00 | 0.00 | 0.00 | -69206.98 | 0.00 | 0.00 | 693.01 | 498.89 | 2172.30 | 0.00 | 0.00 | 7.03 | 65885.54 | 0.00 | -49.79 | 0.00 | 0.00 | 0.00 |
KITCHEN | 06-JAN-04:21 | 0.00 | 0.00 | 0.00 | -51012.36 | 0.00 | 0.00 | 0.00 | 134.19 | 3481.39 | 0.00 | 0.00 | 0.00 | 47541.23 | 0.00 | -0.00 | 0.00 | -144.45 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:01 | 0.00 | 0.00 | 0.00 | -103014.06 | 0.00 | 0.00 | 697.57 | 677.80 | 9089.15 | 0.00 | 0.00 | 388.33 | 92212.74 | 0.00 | -49.79 | 0.00 | -1.74 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JUL-23:01 | 0.00 | 0.00 | 22605.53 | 0.00 | 0.00 | 0.00 | 973.97 | 374.16 | 543.07 | 1002.43 | 0.00 | 214.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25713.64 |
KITCHEN | 03-JUL-04:03 | 0.00 | 0.00 | 2347.39 | 0.00 | 0.00 | 0.00 | 7.36 | 178.91 | 6916.85 | 0.00 | 0.00 | 2.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9452.90 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-23:01 | -12528.11 | 12528.11 | 22605.53 | -12528.11 | 0.00 | 0.00 | 996.46 | 508.34 | 3042.91 | 1002.43 | 0.00 | 1244.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16871.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5568 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5571 | 0.2922 | 1.0000 | Not calculated | 1.3314 | 0.2922 | ||
PSZ-AC_2:2 | 1.6735 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6735 | 0.1091 | 1.0000 | Not calculated | 0.1826 | 0.1091 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 4.5568 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 4.5568 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.2922 | ||
PSZ-AC_2:2 | 1.6735 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.6735 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1091 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5568 | 4.5568 | 4.5568 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6735 | 1.6735 | 1.6735 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5568 | 4.5571 | 4.5568 | 4.5568 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6735 | 1.6735 | 1.6735 | 1.6735 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5568 | 4.5568 | 4.5568 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6735 | 1.6735 | 1.6735 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 4.5568 | 4.5568 | 4.5568 | 4.5568 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.6735 | 1.6735 | 1.6735 | 1.6735 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1832.83 |
Number of hours not met | 1832.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.01 | 1360.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 538.87 | 52016.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.69 | 3050.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.22 | 2175.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 155.75 | 10342.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.36 | 4739.23 | 241.18 | 17305.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.92 | 1532.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.23 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 506.07 | 1360.40 |
Natural Gas | 469.79 | 710.98 |
Additional | 0.00 | 0.00 |
Total | 975.85 | 2071.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 106.99 |
Space Heating | 0.00 |
Space Cooling | 1054.23 |
Fans (All) | 304.70 |
Service Water Heating | 147.43 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 2661.43 |
Subtotal | 2661.43 |
Natural Gas [MJ/m2] | |
Space Heating | 0.02 |
Service Water Heating | 471.84 |
Miscellaneous (All) | 1390.94 |
Subtotal | 1390.94 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.64 |
Space Heating | 0.00 |
Space Cooling | 26.02 |
Fans (All) | 7.52 |
Service Water Heating | 15.28 |
Receptacle Equipment | 44.40 |
Miscellaneous | 4.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7679.00 | 707.17 | 371.17 | 2.67 | 0.00 |
KITCHEN | 5117.83 | 2546.17 | 1045.33 | 50.67 | 0.00 |
ATTIC | 3605.67 | 1039.83 | 1499.17 | 1444.17 | 1171.17 |
Min | 3605.67 | 707.17 | 371.17 | 2.67 | 0.00 |
Max | 7679.00 | 2546.17 | 1499.17 | 1444.17 | 1171.17 |
Average | 5467.50 | 1431.06 | 971.89 | 499.17 | 390.39 |
Sum | 16402.50 | 4293.17 | 2915.67 | 1497.50 | 1171.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 821422.00 | 1668.33 | 1096.67 | 35.00 | 0.00 |
KITCHEN | 13405.17 | 3421.83 | 2252.33 | 153.67 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 821422.00 | 3421.83 | 2252.33 | 153.67 | 0.00 |
Average | 278275.72 | 1696.72 | 1116.33 | 62.89 | 0.00 |
Sum | 834827.17 | 5090.17 | 3349.00 | 188.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 4499.17 | 3937.83 | 319.17 | 3.83 | 0.00 |
KITCHEN | 1063.50 | 7035.50 | 633.83 | 27.17 | 0.00 |
ATTIC | 2790.67 | 2320.83 | 1244.67 | 761.33 | 1642.50 |
Min | 1063.50 | 2320.83 | 319.17 | 3.83 | 0.00 |
Max | 4499.17 | 7035.50 | 1244.67 | 761.33 | 1642.50 |
Average | 2784.44 | 4431.39 | 732.56 | 264.11 | 547.50 |
Sum | 8353.33 | 13294.17 | 2197.67 | 792.33 | 1642.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 495632.67 | 327800.67 | 749.00 | 39.67 | 0.00 |
KITCHEN | 2450.67 | 15179.00 | 1516.00 | 87.33 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 495632.67 | 327800.67 | 1516.00 | 87.33 | 0.00 |
Average | 166027.78 | 114326.56 | 755.00 | 42.33 | 0.00 |
Sum | 498083.33 | 342979.67 | 2265.00 | 127.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286413E+11 | 24993.15 | 23-JAN-12:57 | 27.40 | 16.52 | 0.151312E+11 | 14051.40 | 28-JAN-19:49 | 22.08 | 16.97 |
February | 0.272338E+11 | 28903.62 | 07-FEB-12:53 | 31.00 | 20.84 | 0.137923E+11 | 14051.42 | 11-FEB-19:10 | 19.33 | 13.92 |
March | 0.326558E+11 | 36813.46 | 02-MAR-06:02 | 28.80 | 15.43 | 0.154798E+11 | 14052.53 | 25-MAR-18:10 | 27.38 | 20.47 |
April | 0.356506E+11 | 37228.34 | 28-APR-11:55 | 42.00 | 19.18 | 0.149130E+11 | 14053.02 | 08-APR-18:10 | 42.00 | 19.18 |
May | 0.442471E+11 | 69237.52 | 12-MAY-04:01 | 28.67 | 19.72 | 0.154544E+11 | 14051.74 | 13-MAY-18:49 | 31.58 | 23.75 |
June | 0.458044E+11 | 60992.95 | 02-JUN-04:01 | 28.33 | 18.21 | 0.150406E+11 | 14051.86 | 03-JUN-18:10 | 35.28 | 25.40 |
July | 0.504604E+11 | 62860.88 | 04-JUL-04:01 | 30.42 | 16.66 | 0.154394E+11 | 14167.98 | 01-JUL-18:19 | 30.42 | 16.66 |
August | 0.523453E+11 | 53178.88 | 06-AUG-04:01 | 35.67 | 22.58 | 0.156828E+11 | 14745.50 | 22-AUG-17:30 | 36.00 | 30.49 |
September | 0.470399E+11 | 53020.44 | 02-SEP-04:01 | 30.48 | 22.94 | 0.149534E+11 | 14112.78 | 09-SEP-18:19 | 34.87 | 28.10 |
October | 0.442537E+11 | 57668.23 | 04-OCT-04:01 | 26.92 | 20.11 | 0.153567E+11 | 14051.88 | 14-OCT-18:40 | 31.40 | 24.17 |
November | 0.370738E+11 | 48551.18 | 03-NOV-04:01 | 24.08 | 22.27 | 0.148343E+11 | 14053.48 | 18-NOV-19:00 | 25.00 | 16.38 |
December | 0.313846E+11 | 35409.45 | 12-DEC-06:02 | 23.03 | 17.89 | 0.152580E+11 | 14053.65 | 02-DEC-19:40 | 23.03 | 17.89 |
Annual Sum or Average | 0.476791E+12 | 0.181336E+12 | ||||||||
Minimum of Months | 0.272338E+11 | 24993.15 | 23.03 | 15.43 | 0.137923E+11 | 14051.40 | 19.33 | 13.92 | ||
Maximum of Months | 0.523453E+11 | 69237.52 | 42.00 | 22.94 | 0.156828E+11 | 14745.50 | 42.00 | 30.49 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309869E+11 | 51013.20 | 06-JAN-04:21 | 14.25 | 12.94 | 0.105958E+11 | 6934.95 | 25-JAN-11:09 | 21.33 | 15.53 |
February | 0.281424E+11 | 47051.50 | 17-FEB-04:21 | 15.95 | 14.62 | 0.957489E+10 | 6934.94 | 10-FEB-11:09 | 15.95 | 14.62 |
March | 0.315219E+11 | 45571.81 | 10-MAR-04:11 | 17.27 | 14.12 | 0.106076E+11 | 6934.95 | 06-MAR-11:09 | 17.27 | 14.12 |
April | 0.313892E+11 | 32381.63 | 28-APR-03:31 | 26.33 | 15.47 | 0.102637E+11 | 6942.65 | 28-APR-10:00 | 40.00 | 18.54 |
May | 0.342354E+11 | 33961.81 | 21-MAY-03:22 | 27.95 | 19.67 | 0.106145E+11 | 6995.44 | 30-MAY-10:00 | 36.00 | 26.94 |
June | 0.333450E+11 | 36463.31 | 02-JUN-04:01 | 28.33 | 18.21 | 0.103141E+11 | 7013.71 | 09-JUN-10:50 | 38.63 | 27.06 |
July | 0.340514E+11 | 36765.35 | 03-JUL-04:01 | 29.00 | 16.97 | 0.107025E+11 | 7050.30 | 25-JUL-10:50 | 35.92 | 28.99 |
August | 0.343176E+11 | 27731.13 | 15-AUG-04:01 | 29.75 | 23.27 | 0.107284E+11 | 7054.05 | 08-AUG-10:00 | 29.75 | 23.27 |
September | 0.334916E+11 | 33983.63 | 26-SEP-04:01 | 26.97 | 19.72 | 0.103330E+11 | 7054.88 | 11-SEP-10:00 | 26.97 | 19.72 |
October | 0.349849E+11 | 39612.07 | 20-OCT-04:01 | 22.50 | 16.21 | 0.106180E+11 | 7008.71 | 07-OCT-10:50 | 22.50 | 16.21 |
November | 0.328183E+11 | 41601.25 | 26-NOV-05:01 | 17.00 | 14.53 | 0.102620E+11 | 6974.78 | 01-NOV-10:00 | 17.00 | 14.53 |
December | 0.320035E+11 | 46335.97 | 22-DEC-04:11 | 15.93 | 13.94 | 0.106003E+11 | 6934.97 | 15-DEC-11:39 | 15.93 | 13.94 |
Annual Sum or Average | 0.391288E+12 | 0.125215E+12 | ||||||||
Minimum of Months | 0.281424E+11 | 27731.13 | 14.25 | 12.94 | 0.957489E+10 | 6934.94 | 15.93 | 13.94 | ||
Maximum of Months | 0.349849E+11 | 51013.20 | 29.75 | 23.27 | 0.107284E+11 | 7054.88 | 40.00 | 28.99 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 | 14.59 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 | 18.46 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 | 23.56 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 | 23.24 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 | 27.02 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 | 25.04 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 | 21.17 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 | 15.63 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 0.00 | 0.00 | 15.70 | 12.84 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92549.66 | 617.00 | 29-JAN-06:05 | 22.00 |
February | 747388.02 | 1991.45 | 09-FEB-06:05 | 22.92 |
March | 26421529.26 | 7399.92 | 27-MAR-23:02 | 27.83 |
April | 99335104.88 | 8780.63 | 28-APR-23:02 | 28.83 |
May | 0.530315E+09 | 15648.29 | 31-MAY-23:01 | 33.03 |
June | 0.703911E+09 | 18651.31 | 08-JUN-23:01 | 34.83 |
July | 0.847517E+09 | 22601.83 | 20-JUL-23:01 | 37.67 |
August | 0.804419E+09 | 21794.54 | 05-AUG-23:01 | 37.00 |
September | 0.635427E+09 | 16017.59 | 04-SEP-23:01 | 33.22 |
October | 0.347221E+09 | 11917.16 | 05-OCT-23:01 | 30.67 |
November | 58396622.85 | 10003.93 | 01-NOV-23:01 | 29.50 |
December | 607181.51 | 2501.05 | 12-DEC-06:04 | 23.03 |
Annual Sum or Average | 0.405441E+10 | |||
Minimum of Months | 92549.66 | 617.00 | 22.00 | |
Maximum of Months | 0.847517E+09 | 22601.83 | 37.67 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 70534.35 | 705.34 | 21-MAY-04:03 | 27.75 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 271451.09 | 2347.67 | 03-JUL-04:03 | 29.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 341985.44 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 271451.09 | 2347.67 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.331438E+10 | 2244.98 | 02-JAN-17:30 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.298278E+10 | 2244.98 | 01-FEB-17:40 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.330409E+10 | 2244.98 | 01-MAR-18:10 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.312128E+10 | 2244.98 | 01-APR-18:19 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.321708E+10 | 2244.98 | 01-MAY-18:30 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.312105E+10 | 2244.98 | 01-JUN-18:40 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.319111E+10 | 2244.98 | 01-JUL-18:40 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.325154E+10 | 2244.98 | 01-AUG-19:10 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.313337E+10 | 2244.98 | 01-SEP-18:19 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.325902E+10 | 2244.98 | 02-OCT-17:40 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.319491E+10 | 2244.98 | 01-NOV-17:30 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.331998E+10 | 2244.98 | 01-DEC-17:30 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.384106E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.298278E+10 | 2244.98 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.331998E+10 | 2244.98 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137533E+10 | 805.14 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.124570E+10 | 805.14 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.139723E+10 | 805.14 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.133636E+10 | 805.14 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.138628E+10 | 805.14 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.135053E+10 | 805.14 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.137227E+10 | 805.14 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.139723E+10 | 805.14 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.133668E+10 | 805.14 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.137517E+10 | 805.14 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.133137E+10 | 805.14 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.137243E+10 | 805.14 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.162766E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.124570E+10 | 805.14 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.139723E+10 | 805.14 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.331438E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60770315.08 | 0.260765E+10 |
February | 0.272721E+11 | 0.298278E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404135E+09 | 0.178514E+10 |
March | 0.305458E+11 | 0.330409E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125890E+10 | 0.101748E+10 |
April | 0.292871E+11 | 0.312128E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306676E+10 | 0.256823E+09 |
May | 0.303219E+11 | 0.321708E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651403E+10 | 19703576.95 |
June | 0.295292E+11 | 0.312105E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726523E+10 | 2070435.13 |
July | 0.300798E+11 | 0.319111E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867210E+10 | 0.00 |
August | 0.305458E+11 | 0.325154E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891601E+10 | 0.00 |
September | 0.292871E+11 | 0.313337E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682303E+10 | 1753012.74 |
October | 0.300980E+11 | 0.325902E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503759E+10 | 30082010.72 |
November | 0.290996E+11 | 0.319491E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235592E+10 | 0.272563E+09 |
December | 0.300798E+11 | 0.331998E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386615E+09 | 0.161323E+10 |
Annual Sum or Average | 0.356244E+12 | 0.384106E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507611E+11 | 0.760649E+10 |
Minimum of Months | 0.272721E+11 | 0.298278E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60770315.08 | 0.00 |
Maximum of Months | 0.305458E+11 | 0.331998E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891601E+10 | 0.260765E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.137533E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 102176.55 | 84489574.26 |
February | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 2494206.74 | 85468143.53 |
March | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 9170931.55 | 55749897.67 |
April | 0.786997E+09 | 0.133636E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 22983447.11 | 31935295.96 |
May | 0.814802E+09 | 0.138628E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 57911916.96 | 8760810.64 |
June | 0.793501E+09 | 0.135053E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 67712603.37 | 5497086.66 |
July | 0.808298E+09 | 0.137227E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 80853659.78 | 830715.43 |
August | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 80391642.61 | 679516.08 |
September | 0.786997E+09 | 0.133668E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 53893140.20 | 5224166.95 |
October | 0.808786E+09 | 0.137517E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 36791192.31 | 14369707.70 |
November | 0.781956E+09 | 0.133137E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 13276079.15 | 32992626.39 |
December | 0.808298E+09 | 0.137243E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 1000010.23 | 67561317.23 |
Annual Sum or Average | 0.957291E+10 | 0.162766E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 0.426581E+09 | 0.393559E+09 |
Minimum of Months | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 102176.55 | 679516.08 |
Maximum of Months | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 80853659.78 | 85468143.53 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116514E+10 | 0.259554E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845108E+09 | 0.270595E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115202E+10 | 0.343856E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113343E+10 | 0.372112E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113090E+10 | 0.415388E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102433E+10 | 0.393069E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100158E+10 | 0.407441E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105355E+10 | 0.376744E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113513E+10 | 0.340359E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132743E+10 | 0.312836E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132661E+10 | 0.251405E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119297E+10 | 0.236530E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134882E+11 | 0.397989E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845108E+09 | 0.236530E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132743E+10 | 0.415388E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2244.98 | 02-JAN-17:30 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.91 | 23-JAN-14:00 | 3925.50 | 01-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2244.98 | 01-FEB-17:40 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4308.97 | 06-FEB-14:00 | 3964.19 | 20-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2244.98 | 01-MAR-18:10 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8200.42 | 27-MAR-11:10 | 3884.14 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2244.98 | 01-APR-18:19 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.26 | 28-APR-11:55 | 2873.60 | 01-APR-06:20 |
May | 30255.31 | 06-MAY-18:10 | 2244.98 | 01-MAY-18:30 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10410.61 | 31-MAY-19:00 | 1209.31 | 01-MAY-06:10 |
June | 30255.31 | 03-JUN-18:10 | 2244.98 | 01-JUN-18:40 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10826.25 | 12-JUN-12:00 | 1021.03 | 22-JUN-08:00 |
July | 30255.31 | 01-JUL-18:10 | 2244.98 | 01-JUL-18:40 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12354.03 | 21-JUL-11:57 | 0.00 | 01-JUL-00:01 |
August | 30255.31 | 05-AUG-18:10 | 2244.98 | 01-AUG-19:10 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12531.38 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 30255.31 | 02-SEP-18:10 | 2244.98 | 01-SEP-18:19 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9821.02 | 26-SEP-12:00 | 261.98 | 25-SEP-06:10 |
October | 30255.31 | 07-OCT-18:10 | 2244.98 | 02-OCT-17:40 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8139.26 | 04-OCT-12:00 | 1416.74 | 29-OCT-07:00 |
November | 30255.31 | 04-NOV-18:10 | 2244.98 | 01-NOV-17:30 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5099.23 | 01-NOV-11:55 | 2702.47 | 26-NOV-07:10 |
December | 30255.31 | 02-DEC-19:10 | 2244.98 | 01-DEC-17:30 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2555.45 | 01-DEC-13:00 | 3845.07 | 31-DEC-07:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.91 | 0.00 | |||||
Maximum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 12531.38 | 3964.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 805.14 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 8.94 | 23-JAN-13:50 | 467.47 | 18-JAN-04:10 |
February | 813.01 | 04-FEB-19:10 | 805.14 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 41.17 | 05-FEB-14:55 | 374.07 | 10-FEB-04:40 |
March | 813.01 | 04-MAR-19:10 | 805.14 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 86.05 | 27-MAR-11:00 | 232.13 | 14-MAR-03:30 |
April | 813.01 | 01-APR-18:10 | 805.14 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 108.11 | 28-APR-12:51 | 223.69 | 05-APR-01:10 |
May | 813.01 | 06-MAY-18:10 | 805.14 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 303.73 | 21-MAY-12:52 | 109.25 | 02-MAY-03:30 |
June | 813.01 | 03-JUN-18:10 | 805.14 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 167.33 | 09-JUN-23:04 | 159.18 | 06-JUN-04:00 |
July | 813.01 | 01-JUL-18:10 | 805.14 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 209.29 | 13-JUL-23:25 | 81.70 | 07-JUL-03:20 |
August | 813.01 | 05-AUG-18:10 | 805.14 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 225.58 | 01-AUG-24:00 | 76.71 | 08-AUG-04:00 |
September | 813.01 | 02-SEP-18:10 | 805.14 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 95.83 | 06-SEP-23:10 | 99.64 | 28-SEP-03:20 |
October | 813.01 | 07-OCT-18:10 | 805.14 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 96.93 | 19-OCT-14:55 | 172.86 | 20-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 805.14 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 58.72 | 01-NOV-23:03 | 172.38 | 21-NOV-04:30 |
December | 813.01 | 02-DEC-19:10 | 805.14 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 16.08 | 10-DEC-13:00 | 283.76 | 27-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 8.94 | 76.71 | ||||||
Maximum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 303.73 | 467.47 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1678.29 | 03-JAN-07:10 | 5416.38 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2451.29 | 15-FEB-07:42 | 5865.42 | 22-FEB-13:45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.64 | 27-MAR-06:43 | 6806.90 | 30-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2044.07 | 26-APR-06:00 | 6731.94 | 30-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.97 | 04-MAY-07:51 | 6500.95 | 30-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.71 | 16-JUN-05:50 | 6272.89 | 08-JUN-12:25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1755.41 | 04-JUL-04:40 | 6416.70 | 04-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.39 | 05-AUG-01:51 | 6369.18 | 30-AUG-11:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2474.64 | 30-SEP-07:41 | 5847.85 | 17-SEP-13:43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2441.81 | 29-OCT-04:55 | 5668.50 | 04-OCT-12:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1715.07 | 05-NOV-07:23 | 4968.60 | 07-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1715.01 | 19-DEC-05:00 | 5326.74 | 25-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.39 | 4968.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.97 | 6806.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24993.15 | 23-JAN-12:57 | 80680.82 | 5051.20 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.03 | 0.00 |
February | 28903.62 | 07-FEB-12:53 | 80680.82 | 5051.20 | 19550.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4238.20 | 0.00 |
March | 36813.46 | 02-MAR-06:02 | 16808.50 | 4988.87 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 523.63 | 0.00 |
April | 37228.34 | 28-APR-11:55 | 53787.21 | 3367.47 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.26 | 0.00 |
May | 69237.52 | 12-MAY-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
June | 60992.95 | 02-JUN-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 |
July | 62860.88 | 04-JUL-04:01 | 0.00 | 2619.11 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
August | 53178.88 | 06-AUG-04:01 | 0.00 | 2619.11 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 0.00 |
September | 53020.44 | 02-SEP-04:01 | 0.00 | 2619.11 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | 0.00 |
October | 57668.23 | 04-OCT-04:01 | 11765.95 | 3492.21 | 20274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
November | 48551.18 | 03-NOV-04:01 | 13446.80 | 3991.09 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 |
December | 35409.45 | 12-DEC-06:02 | 16808.50 | 4988.87 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24993.15 | 0.00 | 2619.11 | 13033.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69237.52 | 80680.82 | 5051.20 | 23171.20 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.26 | 136.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51013.20 | 06-JAN-04:21 | 0.00 | 939.30 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 144.45 |
February | 47051.50 | 17-FEB-04:21 | 0.00 | 939.30 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 |
March | 45571.81 | 10-MAR-04:11 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 |
April | 32381.63 | 28-APR-03:31 | 0.00 | 939.30 | 22961.79 | 9503.81 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 |
May | 33961.81 | 21-MAY-03:22 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 |
June | 36463.31 | 02-JUN-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
July | 36765.35 | 03-JUL-04:01 | 316.17 | 1252.40 | 45038.79 | 22809.15 | 0.00 | 0.00 | 0.00 | 1.12 | 0.00 |
August | 27731.13 | 15-AUG-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
September | 33983.63 | 26-SEP-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
October | 39612.07 | 20-OCT-04:01 | 361.34 | 1431.32 | 51472.90 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
November | 41601.25 | 26-NOV-05:01 | 0.00 | 1341.86 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 |
December | 46335.97 | 22-DEC-04:11 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27731.13 | 0.00 | 805.12 | 19681.53 | 8146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51013.20 | 361.34 | 1431.32 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 1.12 | 144.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.49 | 0.00 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.49 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.42 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.64 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.72 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.61 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.05 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.46 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.33 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.07 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.94 | 0.00 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.49 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.823905E+11 | 55343.37 | 24-JAN-11:00 | 0.641083E+11 | 42897.82 | 07-JAN-11:20 |
February | 0.781672E+11 | 59004.78 | 07-FEB-12:00 | 0.574012E+11 | 42856.78 | 04-FEB-11:20 |
March | 0.917159E+11 | 66462.95 | 27-MAR-10:00 | 0.623124E+11 | 42688.56 | 04-MAR-11:09 |
April | 0.992808E+11 | 75914.94 | 28-APR-11:00 | 0.583117E+11 | 42450.79 | 01-APR-10:50 |
May | 0.120753E+12 | 85142.73 | 31-MAY-11:00 | 0.584295E+11 | 42123.16 | 06-MAY-10:09 |
June | 0.132871E+12 | 88485.58 | 09-JUN-11:00 | 0.552858E+11 | 41913.29 | 03-JUN-10:20 |
July | 0.151242E+12 | 88532.92 | 19-JUL-11:39 | 0.565045E+11 | 41813.04 | 30-JUL-10:20 |
August | 0.155794E+12 | 91867.00 | 16-AUG-11:00 | 0.572771E+11 | 41929.51 | 27-AUG-10:20 |
September | 0.137194E+12 | 88189.47 | 07-SEP-11:00 | 0.567596E+11 | 42208.01 | 30-SEP-10:20 |
October | 0.121385E+12 | 82871.89 | 07-OCT-18:49 | 0.605339E+11 | 42475.68 | 29-OCT-10:00 |
November | 0.100394E+12 | 75293.66 | 01-NOV-11:00 | 0.603799E+11 | 42712.04 | 26-NOV-11:09 |
December | 0.892102E+11 | 59965.79 | 05-DEC-12:00 | 0.636789E+11 | 42882.22 | 31-DEC-11:30 |
Annual Sum or Average | 0.136040E+13 | 0.710983E+12 | ||||
Minimum of Months | 0.781672E+11 | 55343.37 | 0.552858E+11 | 41813.04 | ||
Maximum of Months | 0.155794E+12 | 91867.00 | 0.641083E+11 | 42897.82 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.468971E+10 | 0.281696E+10 | 0.382185E+11 | 0.00 | 0.106006E+11 | 37879553.69 | 0.00 | 0.150262E+11 | 0.00 | 0.00 | 0.00 | 0.638029E+10 | 0.00 |
February | 0.422849E+10 | 0.242882E+10 | 0.345199E+11 | 0.00 | 0.963855E+10 | 34213790.43 | 0.00 | 0.173419E+11 | 0.00 | 0.00 | 0.00 | 0.577393E+10 | 0.00 |
March | 0.470132E+10 | 0.252067E+10 | 0.382185E+11 | 0.00 | 0.108076E+11 | 37879553.69 | 0.00 | 0.243206E+11 | 0.00 | 0.00 | 0.00 | 0.644801E+10 | 0.00 |
April | 0.445765E+10 | 0.226033E+10 | 0.369856E+11 | 0.00 | 0.109311E+11 | 36657632.61 | 0.00 | 0.338837E+11 | 0.00 | 0.00 | 0.00 | 0.619235E+10 | 0.00 |
May | 0.460336E+10 | 0.219175E+10 | 0.382185E+11 | 0.00 | 0.128908E+11 | 37879553.69 | 0.00 | 0.516696E+11 | 0.00 | 0.00 | 0.00 | 0.641359E+10 | 0.00 |
June | 0.447158E+10 | 0.205410E+10 | 0.369856E+11 | 0.00 | 0.147807E+11 | 36657632.61 | 0.00 | 0.636293E+11 | 0.00 | 0.00 | 0.00 | 0.623285E+10 | 0.00 |
July | 0.456339E+10 | 0.214737E+10 | 0.382185E+11 | 0.00 | 0.174158E+11 | 37879553.69 | 0.00 | 0.776169E+11 | 0.00 | 0.00 | 0.00 | 0.636537E+10 | 0.00 |
August | 0.464877E+10 | 0.227137E+10 | 0.382185E+11 | 0.00 | 0.181450E+11 | 37879553.69 | 0.00 | 0.811264E+11 | 0.00 | 0.00 | 0.00 | 0.644252E+10 | 0.00 |
September | 0.447005E+10 | 0.236083E+10 | 0.369856E+11 | 0.00 | 0.156226E+11 | 36657632.61 | 0.00 | 0.668219E+11 | 0.00 | 0.00 | 0.00 | 0.618991E+10 | 0.00 |
October | 0.463420E+10 | 0.261726E+10 | 0.382185E+11 | 0.00 | 0.131146E+11 | 37879553.69 | 0.00 | 0.515689E+11 | 0.00 | 0.00 | 0.00 | 0.637675E+10 | 0.00 |
November | 0.452628E+10 | 0.268584E+10 | 0.369856E+11 | 0.00 | 0.110407E+11 | 36657632.61 | 0.00 | 0.343011E+11 | 0.00 | 0.00 | 0.00 | 0.617345E+10 | 0.00 |
December | 0.469241E+10 | 0.286265E+10 | 0.382185E+11 | 0.00 | 0.107597E+11 | 37879553.69 | 0.00 | 0.215657E+11 | 0.00 | 0.00 | 0.00 | 0.637149E+10 | 0.00 |
Annual Sum or Average | 0.546872E+11 | 0.292180E+11 | 0.449992E+12 | 0.00 | 0.155748E+12 | 0.446001E+09 | 0.00 | 0.538872E+12 | 0.00 | 0.00 | 0.00 | 0.753605E+11 | 0.00 |
Minimum of Months | 0.422849E+10 | 0.205410E+10 | 0.345199E+11 | 0.00 | 0.963855E+10 | 34213790.43 | 0.00 | 0.150262E+11 | 0.00 | 0.00 | 0.00 | 0.577393E+10 | 0.00 |
Maximum of Months | 0.470132E+10 | 0.286265E+10 | 0.382185E+11 | 0.00 | 0.181450E+11 | 37879553.69 | 0.00 | 0.811264E+11 | 0.00 | 0.00 | 0.00 | 0.644801E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 11406974.97 | 0.00 | 0.241972E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.213628E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.224127E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.196991E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.185298E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.166732E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.166048E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.173774E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.181470E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.206342E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.217673E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.237791E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 11406974.97 | 0.00 | 0.241185E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.166048E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 11406974.97 | 0.00 | 0.241972E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3050.12 | 02-JAN-17:30 | 2175.41 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 5074.97 | 24-JAN-11:00 | 17.86 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3050.12 | 01-FEB-17:40 | 2175.41 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 5363.13 | 07-FEB-15:00 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 3050.12 | 01-MAR-18:10 | 2175.41 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 5968.10 | 27-MAR-11:09 | 17.86 | 25-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 3050.12 | 01-APR-18:19 | 2175.41 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 7422.82 | 28-APR-11:00 | 17.86 | 01-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 3050.12 | 01-MAY-18:30 | 2175.41 | 01-MAY-05:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 9859.78 | 30-MAY-17:00 | 17.86 | 04-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 3050.12 | 01-JUN-18:40 | 2175.41 | 01-JUN-05:10 | 24359.61 | 01-JUN-10:09 | 0.00 | 10342.05 | 23-JUN-11:00 | 17.86 | 09-JUN-23:10 | 0.00 | 01-JUN-00:10 |
July | 3050.12 | 01-JUL-18:40 | 2175.41 | 01-JUL-05:10 | 24359.61 | 01-JUL-10:09 | 0.00 | 10342.05 | 01-JUL-18:10 | 17.86 | 06-JUL-23:10 | 0.00 | 01-JUL-00:10 |
August | 3050.12 | 01-AUG-19:10 | 2175.41 | 01-AUG-05:10 | 24359.61 | 01-AUG-10:09 | 0.00 | 10342.05 | 02-AUG-17:10 | 17.86 | 03-AUG-23:10 | 0.00 | 01-AUG-00:10 |
September | 3050.12 | 01-SEP-18:19 | 2175.41 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 10342.05 | 07-SEP-11:39 | 17.86 | 01-SEP-23:10 | 0.00 | 01-SEP-00:10 |
October | 3050.12 | 02-OCT-17:40 | 2175.41 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 10262.95 | 07-OCT-18:00 | 17.86 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 3050.12 | 01-NOV-17:30 | 2175.41 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 8541.55 | 01-NOV-11:00 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3050.12 | 01-DEC-17:30 | 2175.41 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 5519.27 | 05-DEC-12:00 | 17.86 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 5074.97 | 17.86 | 0.00 | ||||||
Maximum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 10342.05 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19128.12 | 24-JAN-12:00 | 0.00 | 0.00 | 0.00 | 4739.23 | 09-JAN-07:19 | 0.00 |
February | 23777.79 | 07-FEB-12:00 | 0.00 | 0.00 | 0.00 | 4737.77 | 22-FEB-07:19 | 0.00 |
March | 29676.23 | 27-MAR-11:09 | 0.00 | 0.00 | 0.00 | 4737.44 | 08-MAR-07:19 | 0.00 |
April | 38561.39 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 4736.72 | 06-APR-18:30 | 0.00 |
May | 45577.96 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4737.02 | 19-MAY-18:30 | 0.00 |
June | 48196.88 | 09-JUN-11:00 | 0.00 | 0.00 | 0.00 | 4736.82 | 21-JUN-06:19 | 0.00 |
July | 49018.99 | 21-JUL-12:00 | 0.00 | 0.00 | 0.00 | 4736.67 | 03-JUL-18:30 | 0.00 |
August | 52016.94 | 16-AUG-11:00 | 0.00 | 0.00 | 0.00 | 4736.06 | 15-AUG-18:49 | 0.00 |
September | 47794.01 | 07-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4736.06 | 15-SEP-06:49 | 0.00 |
October | 42392.39 | 07-OCT-18:00 | 0.00 | 0.00 | 0.00 | 4736.77 | 18-OCT-18:19 | 0.00 |
November | 36758.88 | 01-NOV-11:00 | 0.00 | 0.00 | 0.00 | 4736.61 | 07-NOV-07:19 | 0.00 |
December | 24479.23 | 05-DEC-12:00 | 0.00 | 0.00 | 0.00 | 4737.94 | 18-DEC-07:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19128.12 | 0.00 | 0.00 | 0.00 | 4736.06 | 0.00 | ||
Maximum of Months | 52016.94 | 0.00 | 0.00 | 0.00 | 4739.23 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55343.37 | 24-JAN-11:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5074.97 | 17.86 | 0.00 | 17531.89 | 0.00 |
February | 59004.78 | 07-FEB-12:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 5285.30 | 17.86 | 0.00 | 23777.79 | 0.00 |
March | 66462.95 | 27-MAR-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5585.07 | 17.86 | 0.00 | 28126.72 | 0.00 |
April | 75914.94 | 28-APR-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 7422.82 | 17.86 | 0.00 | 38561.39 | 0.00 |
May | 85142.73 | 31-MAY-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 9562.30 | 17.86 | 0.00 | 45577.96 | 0.00 |
June | 88485.58 | 09-JUN-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 10268.56 | 17.86 | 0.00 | 48196.88 | 0.00 |
July | 88532.92 | 19-JUL-11:39 | 2488.87 | 22750.50 | 0.00 | 0.00 | 10342.05 | 17.86 | 0.00 | 48079.45 | 0.00 |
August | 91867.00 | 16-AUG-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 9829.58 | 17.86 | 0.00 | 52016.94 | 0.00 |
September | 88189.47 | 07-SEP-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 10342.05 | 17.86 | 0.00 | 47794.01 | 0.00 |
October | 82871.89 | 07-OCT-18:49 | 3050.12 | 18727.72 | 2175.41 | 0.00 | 10219.94 | 17.86 | 0.00 | 42253.61 | 0.00 |
November | 75293.66 | 01-NOV-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 8541.55 | 17.86 | 0.00 | 36758.88 | 0.00 |
December | 59965.79 | 05-DEC-12:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 5519.27 | 17.86 | 0.00 | 24479.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 55343.37 | 2488.87 | 18727.72 | 0.00 | 0.00 | 5074.97 | 17.86 | 0.00 | 17531.89 | 0.00 | |
Maximum of Months | 91867.00 | 3050.12 | 24359.61 | 2175.41 | 0.00 | 10342.05 | 17.86 | 0.00 | 52016.94 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 1360.67 | 16-JAN-06:10 | 0.00 | 17305.15 | 03-JAN-07:19 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 17262.63 | 01-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 17053.84 | 01-MAR-19:49 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 16694.66 | 03-APR-18:40 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 16363.13 | 01-MAY-18:19 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 16059.85 | 01-JUN-18:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 15912.80 | 03-JUL-18:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 16096.80 | 31-AUG-18:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 16391.20 | 29-SEP-18:10 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 16777.96 | 31-OCT-18:19 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 17094.87 | 30-NOV-19:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 17281.62 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 15912.80 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 1360.67 | 0.00 | 17305.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 24.88 | 19.33 | 24.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 25.01 | 24.33 | 25.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.83 | 3.00 | 24.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.67 | 24.94 | 46.67 | 24.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 25.01 | 24.33 | 25.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 30.90 | 0.00 | 30.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.98 | 0.00 | 30.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 31.08 | 0.00 | 31.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 30.63 | 4.00 | 30.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 28.82 | 59.50 | 28.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 329.50 | 28.44 | 299.50 | 28.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 509.83 | 29.15 | 476.50 | 29.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 549.50 | 29.39 | 513.67 | 29.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 403.33 | 28.71 | 372.83 | 28.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 129.67 | 28.85 | 98.67 | 28.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 30.45 | 8.17 | 29.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 31.09 | 0.00 | 31.09 |
Annual Sum or Average | 0.00 | 0.00 | 2170.50 | 29.12 | 1832.83 | 28.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 28.44 | 0.00 | 28.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 549.50 | 31.09 | 513.67 | 31.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.33 | 22.35 | 481.00 | 23.73 | 8.50 | 23.74 |
February | 85.00 | 23.31 | 487.67 | 23.91 | 45.00 | 23.94 |
March | 82.33 | 23.85 | 560.50 | 24.05 | 64.83 | 24.06 |
April | 120.67 | 24.41 | 584.83 | 24.20 | 120.67 | 24.23 |
May | 189.33 | 24.74 | 611.00 | 24.38 | 189.33 | 24.45 |
June | 416.50 | 24.42 | 592.00 | 24.35 | 416.50 | 24.37 |
July | 473.17 | 24.46 | 609.00 | 24.41 | 473.17 | 24.42 |
August | 514.00 | 24.46 | 612.00 | 24.42 | 514.00 | 24.44 |
September | 440.67 | 24.40 | 590.00 | 24.35 | 440.67 | 24.36 |
October | 287.33 | 24.46 | 610.00 | 24.31 | 287.33 | 24.34 |
November | 133.67 | 24.39 | 591.00 | 24.19 | 133.67 | 24.22 |
December | 125.67 | 23.81 | 563.33 | 23.98 | 103.83 | 23.99 |
Annual Sum or Average | 2960.67 | 24.32 | 6892.33 | 24.23 | 2797.50 | 24.28 |
Minimum of Months | 82.33 | 22.35 | 481.00 | 23.73 | 8.50 | 23.74 |
Maximum of Months | 514.00 | 24.74 | 612.00 | 24.42 | 514.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.67 | 25.99 | 605.67 | 25.79 | 484.67 | 25.85 |
February | 482.33 | 26.00 | 551.00 | 25.89 | 482.33 | 25.92 |
March | 570.00 | 26.02 | 612.00 | 25.98 | 570.00 | 25.99 |
April | 588.00 | 26.06 | 590.00 | 26.06 | 588.00 | 26.06 |
May | 611.00 | 26.24 | 611.00 | 26.24 | 611.00 | 26.24 |
June | 592.00 | 27.17 | 592.00 | 27.17 | 592.00 | 27.17 |
July | 609.00 | 28.38 | 609.00 | 28.38 | 609.00 | 28.38 |
August | 612.00 | 28.76 | 612.00 | 28.76 | 612.00 | 28.76 |
September | 590.00 | 27.63 | 590.00 | 27.63 | 590.00 | 27.63 |
October | 610.00 | 26.40 | 610.00 | 26.40 | 610.00 | 26.40 |
November | 591.00 | 26.07 | 591.00 | 26.07 | 591.00 | 26.07 |
December | 558.50 | 25.98 | 609.00 | 25.92 | 558.50 | 25.94 |
Annual Sum or Average | 6898.50 | 26.76 | 7182.67 | 26.71 | 6898.50 | 26.73 |
Minimum of Months | 482.33 | 25.98 | 551.00 | 25.79 | 482.33 | 25.85 |
Maximum of Months | 612.00 | 28.76 | 612.00 | 28.76 | 612.00 | 28.76 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.70579 | 51.00013 | 0.48950 | 10.71227 |
February | 551.00000 | 23.85980 | 54.35320 | 0.55867 | 11.98530 |
March | 612.00000 | 24.01193 | 51.43292 | 0.58470 | 12.48474 |
April | 590.00000 | 24.14854 | 55.00899 | 0.66341 | 14.49503 |
May | 611.00000 | 24.26133 | 57.65165 | -0.0450 | 5.99523 |
June | 592.00000 | 24.30274 | 65.44307 | 0.05167 | 6.37995 |
July | 609.00000 | 24.36205 | 67.79016 | 0.12126 | 7.01888 |
August | 612.00000 | 24.38873 | 69.13107 | 0.15984 | 7.16228 |
September | 590.00000 | 24.30375 | 67.99948 | 0.09867 | 6.56813 |
October | 610.00000 | 24.23784 | 61.62478 | 0.79082 | 18.62548 |
November | 591.00000 | 24.13903 | 57.69349 | 0.70633 | 15.70473 |
December | 609.00000 | 23.92926 | 55.61131 | 0.59659 | 12.79893 |
Annual Sum or Average | 7187.00000 | 24.13899 | 59.58338 | 0.39680 | 10.81699 |
Minimum of Months | 551.00000 | 23.70579 | 51.00013 | -0.0450 | 5.99523 |
Maximum of Months | 612.00000 | 24.38873 | 69.13107 | 0.79082 | 18.62548 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.60181 | 48.19955 | 1.14579 | 33.61803 |
February | 551.00000 | 25.78910 | 51.01457 | 1.21792 | 36.69015 |
March | 612.00000 | 25.94045 | 49.05496 | 1.24714 | 37.90364 |
April | 590.00000 | 26.05555 | 52.82541 | 1.32495 | 41.71692 |
May | 611.00000 | 26.23616 | 57.06432 | 0.92081 | 23.92438 |
June | 592.00000 | 27.16874 | 63.46249 | 1.30922 | 42.04431 |
July | 609.00000 | 28.38015 | 65.74798 | 1.75817 | 61.55344 |
August | 612.00000 | 28.75932 | 66.91568 | 1.91086 | 68.15583 |
September | 590.00000 | 27.63389 | 65.34921 | 1.49750 | 50.19647 |
October | 610.00000 | 26.40475 | 59.11197 | 1.51344 | 51.30393 |
November | 591.00000 | 26.07318 | 54.50503 | 1.36530 | 43.77679 |
December | 609.00000 | 25.86399 | 51.68519 | 1.25524 | 38.37297 |
Annual Sum or Average | 7187.00000 | 26.66550 | 57.10748 | 1.37344 | 44.16185 |
Minimum of Months | 551.00000 | 25.60181 | 48.19955 | 0.92081 | 23.92438 |
Maximum of Months | 612.00000 | 28.75932 | 66.91568 | 1.91086 | 68.15583 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.306497E+11 | 0.943392E+10 | 451.19 | 0.214367E+11 | 0.921300E+10 | 0.00 | 0.84 | 24-JAN-13:00 | 0.00 | 01-JAN-00:10 | 47125.26 | 24-JAN-13:00 | 33686.23 | 23-JAN-14:00 | 21043.62 | 30-JAN-14:00 | 12708.73 | 24-JAN-13:00 | 0.00 | 01-JAN-00:10 |
February | 0.365564E+11 | 0.109480E+11 | 445.39 | 0.250659E+11 | 0.114905E+11 | 0.00 | 1.00 | 07-FEB-12:43 | 0.00 | 01-FEB-00:03 | 60069.04 | 07-FEB-13:00 | 43687.77 | 06-FEB-14:00 | 25554.60 | 06-FEB-18:20 | 16074.17 | 07-FEB-13:00 | 0.00 | 01-FEB-00:03 |
March | 0.523078E+11 | 0.154262E+11 | 522.27 | 0.381904E+11 | 0.141174E+11 | 0.00 | 1.00 | 01-MAR-18:03 | 0.00 | 01-MAR-00:03 | 65818.03 | 28-MAR-11:23 | 58906.89 | 27-MAR-11:13 | 29363.41 | 28-MAR-18:00 | 19065.23 | 27-MAR-11:03 | 0.00 | 01-MAR-00:03 |
April | 0.751766E+11 | 0.213437E+11 | 545.59 | 0.530522E+11 | 0.221244E+11 | 0.00 | 1.00 | 03-APR-11:05 | 0.00 | 01-APR-00:01 | 84830.46 | 29-APR-19:00 | 71198.96 | 28-APR-11:55 | 42362.84 | 29-APR-19:00 | 25574.05 | 28-APR-11:55 | 0.00 | 01-APR-00:01 |
May | 0.113878E+12 | 0.325676E+11 | 587.59 | 0.801200E+11 | 0.337579E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:01 | 124040.47 | 18-MAY-04:02 | 88715.95 | 12-MAY-04:01 | 86603.42 | 30-MAY-04:01 | 33533.95 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.144278E+12 | 0.409094E+11 | 572.37 | 0.874083E+11 | 0.568698E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:01 | 124040.47 | 27-JUN-04:01 | 79083.36 | 02-JUN-04:01 | 87359.45 | 27-JUN-04:01 | 36079.82 | 09-JUN-12:00 | 0.00 | 01-JUN-00:01 |
July | 0.176780E+12 | 0.514286E+11 | 610.77 | 0.102553E+12 | 0.742266E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:01 | 124040.47 | 06-JUL-05:03 | 84885.62 | 04-JUL-04:01 | 90609.29 | 05-JUL-04:02 | 36706.88 | 21-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.187094E+12 | 0.544572E+11 | 618.12 | 0.105798E+12 | 0.812959E+11 | 0.00 | 1.00 | 01-AUG-03:11 | 0.00 | 01-AUG-00:01 | 124040.47 | 31-AUG-04:01 | 85457.18 | 16-AUG-12:00 | 89438.66 | 22-AUG-03:18 | 38543.66 | 10-AUG-12:55 | 0.00 | 01-AUG-00:01 |
September | 0.156630E+12 | 0.435139E+11 | 576.52 | 0.874944E+11 | 0.691358E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:01 | 124040.47 | 29-SEP-04:02 | 76725.58 | 13-SEP-04:01 | 90259.56 | 11-SEP-04:01 | 35815.22 | 07-SEP-11:53 | 0.00 | 01-SEP-00:01 |
October | 0.118814E+12 | 0.323906E+11 | 586.41 | 0.733988E+11 | 0.454156E+11 | 0.00 | 1.00 | 01-OCT-04:02 | 0.00 | 01-OCT-00:01 | 124040.47 | 01-OCT-04:02 | 73964.43 | 04-OCT-04:01 | 88886.95 | 08-OCT-04:01 | 31737.45 | 07-OCT-19:00 | 0.00 | 01-OCT-00:01 |
November | 0.779983E+11 | 0.215888E+11 | 546.22 | 0.509946E+11 | 0.270037E+11 | 0.00 | 1.00 | 01-NOV-04:02 | 0.00 | 01-NOV-00:01 | 124040.47 | 03-NOV-04:01 | 58005.97 | 03-NOV-04:01 | 66034.50 | 03-NOV-04:01 | 30853.84 | 03-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.461500E+11 | 0.135477E+11 | 504.35 | 0.301404E+11 | 0.160096E+11 | 0.00 | 1.00 | 05-DEC-12:40 | 0.00 | 01-DEC-00:05 | 63094.71 | 05-DEC-13:00 | 39599.31 | 12-DEC-06:02 | 30306.49 | 05-DEC-13:00 | 15929.15 | 12-DEC-06:02 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.121631E+13 | 0.347556E+12 | 6566.77 | 0.755653E+12 | 0.460660E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.306497E+11 | 0.943392E+10 | 445.39 | 0.214367E+11 | 0.921300E+10 | 0.00 | 0.84 | 0.00 | 47125.26 | 33686.23 | 21043.62 | 12708.73 | 0.00 | |||||||
Maximum of Months | 0.187094E+12 | 0.544572E+11 | 618.12 | 0.105798E+12 | 0.812959E+11 | 0.00 | 1.00 | 0.00 | 124040.47 | 88715.95 | 90609.29 | 38543.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.215220E+11 | 0.559232E+10 | 526.28 | 0.145939E+11 | 0.692809E+10 | 0.00 | 1.00 | 01-JAN-05:01 | 0.00 | 01-JAN-00:10 | 40996.86 | 12-JAN-05:01 | 30887.33 | 05-JAN-05:01 | 19277.74 | 06-JAN-04:21 | 10004.33 | 06-JAN-04:21 | 0.00 | 01-JAN-00:10 |
February | 0.253103E+11 | 0.639389E+10 | 515.45 | 0.169225E+11 | 0.838786E+10 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:03 | 40996.86 | 03-FEB-05:01 | 27640.74 | 16-FEB-05:01 | 20558.39 | 17-FEB-04:21 | 10004.33 | 03-FEB-05:01 | 0.00 | 01-FEB-00:03 |
March | 0.355414E+11 | 0.889438E+10 | 624.27 | 0.259958E+11 | 0.954562E+10 | 0.00 | 1.00 | 01-MAR-04:02 | 0.00 | 01-MAR-01:01 | 43579.02 | 28-MAR-11:00 | 38909.17 | 27-MAR-10:58 | 23262.29 | 24-MAR-03:31 | 11208.76 | 27-MAR-11:00 | 0.00 | 01-MAR-00:03 |
April | 0.513720E+11 | 0.125400E+11 | 655.62 | 0.369179E+11 | 0.144541E+11 | 0.00 | 1.00 | 01-APR-10:31 | 0.00 | 01-APR-00:01 | 45550.21 | 29-APR-20:20 | 41479.13 | 28-APR-12:15 | 25426.26 | 29-APR-19:55 | 12990.30 | 28-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.759767E+11 | 0.191020E+11 | 704.90 | 0.564285E+11 | 0.195482E+11 | 0.00 | 1.00 | 01-MAY-03:32 | 0.00 | 01-MAY-00:01 | 45550.21 | 24-MAY-05:03 | 42419.49 | 31-MAY-18:00 | 29359.52 | 30-MAY-03:22 | 12893.41 | 31-MAY-19:00 | 0.00 | 01-MAY-00:01 |
June | 0.898721E+11 | 0.227199E+11 | 684.19 | 0.578030E+11 | 0.320691E+11 | 0.00 | 1.00 | 01-JUN-00:08 | 0.00 | 01-JUN-00:01 | 45550.21 | 07-JUN-22:05 | 42468.14 | 27-JUN-11:02 | 31877.63 | 08-JUN-03:22 | 12891.35 | 12-JUN-11:53 | 0.00 | 01-JUN-00:01 |
July | 0.100544E+12 | 0.261882E+11 | 709.12 | 0.634087E+11 | 0.371356E+11 | 0.00 | 1.00 | 01-JUL-00:09 | 0.00 | 01-JUL-00:01 | 45550.21 | 02-JUL-05:03 | 42355.74 | 20-JUL-19:07 | 31143.95 | 27-JUL-03:50 | 13756.39 | 21-JUL-11:53 | 0.00 | 01-JUL-00:01 |
August | 0.102384E+12 | 0.266692E+11 | 709.86 | 0.632536E+11 | 0.391301E+11 | 0.00 | 1.00 | 01-AUG-00:06 | 0.00 | 01-AUG-00:01 | 45550.21 | 31-AUG-03:22 | 42435.55 | 15-AUG-11:25 | 32118.78 | 08-AUG-03:50 | 13641.57 | 16-AUG-11:53 | 0.00 | 01-AUG-00:01 |
September | 0.938404E+11 | 0.233081E+11 | 684.81 | 0.548522E+11 | 0.389882E+11 | 0.00 | 1.00 | 01-SEP-00:07 | 0.00 | 01-SEP-00:01 | 45550.21 | 09-SEP-05:30 | 42149.35 | 26-SEP-13:10 | 31262.78 | 10-SEP-06:00 | 12539.46 | 26-SEP-12:23 | 0.00 | 01-SEP-00:01 |
October | 0.797519E+11 | 0.191782E+11 | 704.24 | 0.500748E+11 | 0.296771E+11 | 0.00 | 1.00 | 01-OCT-00:08 | 0.00 | 01-OCT-00:01 | 45550.21 | 07-OCT-08:30 | 39218.06 | 09-OCT-10:43 | 33297.56 | 07-OCT-03:22 | 11414.79 | 05-OCT-12:00 | 0.00 | 01-OCT-00:01 |
November | 0.533387E+11 | 0.127122E+11 | 658.24 | 0.350247E+11 | 0.183140E+11 | 0.00 | 1.00 | 01-NOV-03:22 | 0.00 | 01-NOV-00:01 | 45550.21 | 02-NOV-20:00 | 30893.12 | 20-NOV-05:02 | 27420.24 | 08-NOV-04:22 | 10859.79 | 01-NOV-13:55 | 0.00 | 01-NOV-00:01 |
December | 0.324567E+11 | 0.801798E+10 | 587.18 | 0.204572E+11 | 0.119995E+11 | 0.00 | 1.00 | 01-DEC-04:31 | 0.00 | 01-DEC-01:01 | 40996.86 | 20-DEC-05:01 | 29138.88 | 19-DEC-05:01 | 24266.08 | 26-DEC-04:11 | 10004.33 | 16-DEC-05:01 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.761910E+12 | 0.191316E+12 | 7764.16 | 0.495733E+12 | 0.266177E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.215220E+11 | 0.559232E+10 | 515.45 | 0.145939E+11 | 0.692809E+10 | 0.00 | 1.00 | 0.00 | 40996.86 | 27640.74 | 19277.74 | 10004.33 | 0.00 | |||||||
Maximum of Months | 0.102384E+12 | 0.266692E+11 | 709.86 | 0.634087E+11 | 0.391301E+11 | 0.00 | 1.00 | 0.00 | 45550.21 | 42468.14 | 33297.56 | 13756.39 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 150.78 | 45.48 | 105.30 | 198.08 | 157.83 | 0.00 | 0.00 | 0.00 |
February | 164.65 | 44.62 | 120.02 | 238.31 | 132.11 | 0.00 | 0.00 | 0.00 |
March | 182.03 | 44.90 | 137.13 | 300.30 | 100.14 | 0.00 | 0.00 | 0.00 |
April | 221.59 | 64.48 | 157.11 | 429.37 | 63.37 | 0.00 | 0.00 | 0.00 |
May | 247.24 | 78.74 | 168.51 | 573.64 | 19.29 | 1.00 | 0.00 | 0.00 |
June | 242.19 | 74.04 | 168.15 | 597.78 | 6.90 | 0.50 | 0.00 | 0.00 |
July | 226.08 | 65.14 | 160.94 | 633.90 | 0.34 | 1.33 | 0.00 | 0.00 |
August | 231.57 | 71.10 | 160.47 | 644.45 | 0.27 | 0.50 | 0.00 | 0.00 |
September | 217.57 | 67.21 | 150.36 | 536.42 | 10.16 | 3.83 | 0.00 | 0.00 |
October | 197.38 | 64.39 | 132.99 | 428.63 | 32.71 | 2.33 | 0.00 | 0.00 |
November | 165.34 | 52.22 | 113.12 | 299.64 | 76.19 | 0.00 | 0.00 | 0.00 |
December | 134.06 | 36.86 | 97.20 | 191.13 | 133.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.50 | 59.16 | 139.35 | 423.68 | 60.70 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 134.06 | 36.86 | 97.20 | 191.13 | 0.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 247.24 | 78.74 | 168.51 | 644.45 | 157.83 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 375.36 | 177.27 | 198.10 | 567.83 | 216.00 | 0.00 | 0.00 | 0.00 |
February | 350.90 | 143.52 | 207.38 | 559.08 | 184.84 | 0.00 | 0.00 | 0.00 |
March | 285.77 | 75.42 | 210.35 | 502.52 | 144.75 | 0.00 | 0.00 | 0.00 |
April | 228.22 | 25.21 | 203.01 | 472.79 | 92.85 | 0.00 | 0.00 | 0.00 |
May | 193.08 | 3.64 | 189.44 | 526.66 | 28.19 | 1.00 | 0.00 | 0.00 |
June | 181.09 | 0.22 | 180.86 | 544.55 | 10.04 | 0.50 | 0.00 | 0.00 |
July | 180.84 | 1.20 | 179.64 | 634.73 | 0.48 | 1.33 | 0.00 | 0.00 |
August | 209.19 | 13.92 | 195.28 | 703.03 | 0.37 | 0.17 | 0.00 | 0.00 |
September | 277.29 | 63.76 | 213.53 | 725.99 | 14.19 | 3.83 | 0.00 | 0.00 |
October | 363.20 | 144.76 | 218.44 | 773.54 | 45.60 | 2.33 | 0.00 | 0.00 |
November | 401.97 | 194.75 | 207.23 | 727.65 | 106.16 | 0.00 | 0.00 | 0.00 |
December | 371.99 | 184.08 | 187.90 | 592.50 | 183.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.51 | 85.33 | 199.18 | 611.26 | 85.10 | 9.17 | 0.00 | 0.00 |
Minimum of Months | 180.84 | 0.22 | 179.64 | 472.79 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 401.97 | 194.75 | 218.44 | 773.54 | 216.00 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.56 | 42.73 | 105.83 | 201.58 | 165.78 | 0.00 | 0.00 | 0.00 |
February | 169.55 | 48.51 | 121.04 | 252.14 | 138.15 | 0.00 | 0.00 | 0.00 |
March | 200.28 | 59.30 | 140.98 | 336.46 | 105.19 | 0.00 | 0.00 | 0.00 |
April | 219.00 | 61.52 | 157.47 | 423.57 | 66.74 | 0.00 | 0.00 | 0.00 |
May | 238.24 | 71.30 | 166.94 | 554.77 | 19.99 | 0.83 | 0.00 | 0.00 |
June | 246.11 | 77.55 | 168.57 | 601.21 | 7.09 | 0.33 | 0.00 | 0.00 |
July | 225.73 | 64.46 | 161.27 | 629.79 | 0.31 | 1.00 | 0.00 | 0.00 |
August | 231.60 | 70.28 | 161.32 | 642.21 | 0.23 | 0.17 | 0.00 | 0.00 |
September | 220.69 | 69.43 | 151.26 | 539.05 | 9.97 | 3.67 | 0.00 | 0.00 |
October | 196.30 | 63.64 | 132.66 | 424.22 | 33.28 | 2.17 | 0.00 | 0.00 |
November | 168.78 | 55.38 | 113.40 | 308.22 | 80.95 | 0.00 | 0.00 | 0.00 |
December | 140.74 | 42.37 | 98.37 | 209.44 | 140.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.58 | 60.58 | 140.00 | 427.87 | 63.64 | 8.17 | 0.00 | 0.00 |
Minimum of Months | 140.74 | 42.37 | 98.37 | 201.58 | 0.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 246.11 | 77.55 | 168.57 | 642.21 | 165.78 | 3.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.403852E+09 | 0.121807E+09 | 0.282045E+09 | 0.530528E+09 | 0.422744E+09 |
February | 0.398315E+09 | 0.107953E+09 | 0.290362E+09 | 0.576510E+09 | 0.319594E+09 |
March | 0.487539E+09 | 0.120260E+09 | 0.367279E+09 | 0.804332E+09 | 0.268221E+09 |
April | 0.574366E+09 | 0.167138E+09 | 0.407227E+09 | 0.111294E+10 | 0.164268E+09 |
May | 0.662213E+09 | 0.210887E+09 | 0.451326E+09 | 0.153643E+10 | 51666016.12 |
June | 0.627756E+09 | 0.191905E+09 | 0.435851E+09 | 0.154945E+10 | 17878405.52 |
July | 0.605530E+09 | 0.174479E+09 | 0.431051E+09 | 0.169785E+10 | 899933.32 |
August | 0.620233E+09 | 0.190426E+09 | 0.429808E+09 | 0.172610E+10 | 721303.44 |
September | 0.563950E+09 | 0.174212E+09 | 0.389738E+09 | 0.139040E+10 | 26337032.49 |
October | 0.528668E+09 | 0.172460E+09 | 0.356207E+09 | 0.114804E+10 | 87606517.79 |
November | 0.428573E+09 | 0.135354E+09 | 0.293219E+09 | 0.776679E+09 | 0.197481E+09 |
December | 0.359053E+09 | 98724595.84 | 0.260329E+09 | 0.511935E+09 | 0.356942E+09 |
Annual Sum or Average | 0.626005E+10 | 0.186561E+10 | 0.439444E+10 | 0.133612E+11 | 0.191436E+10 |
Minimum of Months | 0.359053E+09 | 98724595.84 | 0.260329E+09 | 0.511935E+09 | 721303.44 |
Maximum of Months | 0.662213E+09 | 0.210887E+09 | 0.451326E+09 | 0.172610E+10 | 0.422744E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100537E+10 | 0.474797E+09 | 0.530578E+09 | 0.152087E+10 | 0.578538E+09 |
February | 0.848898E+09 | 0.347198E+09 | 0.501700E+09 | 0.135252E+10 | 0.447160E+09 |
March | 0.765409E+09 | 0.201996E+09 | 0.563414E+09 | 0.134594E+10 | 0.387710E+09 |
April | 0.591541E+09 | 65334216.03 | 0.526207E+09 | 0.122548E+10 | 0.240664E+09 |
May | 0.517154E+09 | 9758207.31 | 0.507396E+09 | 0.141061E+10 | 75506611.96 |
June | 0.469381E+09 | 580490.77 | 0.468800E+09 | 0.141148E+10 | 26022665.09 |
July | 0.484351E+09 | 3204865.85 | 0.481147E+09 | 0.170005E+10 | 1275540.87 |
August | 0.560307E+09 | 37270545.30 | 0.523037E+09 | 0.188299E+10 | 984372.65 |
September | 0.718745E+09 | 0.165272E+09 | 0.553472E+09 | 0.188176E+10 | 36771679.74 |
October | 0.972804E+09 | 0.387733E+09 | 0.585071E+09 | 0.207184E+10 | 0.122137E+09 |
November | 0.104192E+10 | 0.504791E+09 | 0.537128E+09 | 0.188608E+10 | 0.275172E+09 |
December | 0.996325E+09 | 0.493047E+09 | 0.503277E+09 | 0.158695E+10 | 0.491831E+09 |
Annual Sum or Average | 0.897221E+10 | 0.269098E+10 | 0.628123E+10 | 0.192766E+11 | 0.268377E+10 |
Minimum of Months | 0.469381E+09 | 580490.77 | 0.468800E+09 | 0.122548E+10 | 984372.65 |
Maximum of Months | 0.104192E+10 | 0.504791E+09 | 0.585071E+09 | 0.207184E+10 | 0.578538E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397897E+09 | 0.114453E+09 | 0.283444E+09 | 0.539924E+09 | 0.444024E+09 |
February | 0.410173E+09 | 0.117346E+09 | 0.292827E+09 | 0.609967E+09 | 0.334209E+09 |
March | 0.536435E+09 | 0.158823E+09 | 0.377613E+09 | 0.901181E+09 | 0.281736E+09 |
April | 0.567641E+09 | 0.159470E+09 | 0.408171E+09 | 0.109789E+10 | 0.172977E+09 |
May | 0.638114E+09 | 0.190981E+09 | 0.447133E+09 | 0.148590E+10 | 53542148.78 |
June | 0.637928E+09 | 0.200997E+09 | 0.436930E+09 | 0.155835E+10 | 18386344.79 |
July | 0.604602E+09 | 0.172661E+09 | 0.431940E+09 | 0.168683E+10 | 830790.72 |
August | 0.620321E+09 | 0.188250E+09 | 0.432070E+09 | 0.172009E+10 | 622152.30 |
September | 0.572036E+09 | 0.179958E+09 | 0.392078E+09 | 0.139721E+10 | 25846117.06 |
October | 0.525773E+09 | 0.170450E+09 | 0.355324E+09 | 0.113622E+10 | 89147790.65 |
November | 0.437471E+09 | 0.143536E+09 | 0.293935E+09 | 0.798915E+09 | 0.209829E+09 |
December | 0.376967E+09 | 0.113494E+09 | 0.263474E+09 | 0.560954E+09 | 0.375763E+09 |
Annual Sum or Average | 0.632536E+10 | 0.191042E+10 | 0.441494E+10 | 0.134934E+11 | 0.200691E+10 |
Minimum of Months | 0.376967E+09 | 0.113494E+09 | 0.263474E+09 | 0.539924E+09 | 622152.30 |
Maximum of Months | 0.638114E+09 | 0.200997E+09 | 0.447133E+09 | 0.172009E+10 | 0.444024E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 954.89 | 527.01 | 674.70 | 265.48 | 409.22 | 0.00 | 0.00 |
February | 1039.65 | 445.22 | 685.10 | 236.65 | 448.45 | 0.00 | 0.00 |
March | 1132.27 | 343.07 | 668.08 | 179.61 | 488.47 | 0.00 | 0.00 |
April | 1321.18 | 218.40 | 668.81 | 151.21 | 517.59 | 0.00 | 0.00 |
May | 1652.99 | 65.39 | 678.57 | 153.68 | 524.89 | 0.00 | 0.00 |
June | 1743.27 | 23.76 | 669.39 | 151.81 | 517.59 | 0.00 | 0.00 |
July | 1898.41 | 1.11 | 632.65 | 130.80 | 501.84 | 0.00 | 0.00 |
August | 1989.69 | 0.87 | 672.36 | 155.30 | 517.07 | 0.00 | 0.00 |
September | 1800.95 | 33.81 | 715.56 | 200.40 | 515.16 | 0.00 | 0.00 |
October | 1624.77 | 109.98 | 756.89 | 272.79 | 484.10 | 0.00 | 0.00 |
November | 1330.57 | 258.35 | 736.10 | 302.35 | 433.75 | 0.00 | 0.00 |
December | 984.66 | 448.78 | 646.78 | 263.32 | 383.47 | 0.00 | 0.00 |
Annual Sum or Average | 1458.51 | 205.15 | 683.59 | 205.07 | 478.52 | 0.00 | 0.00 |
Minimum of Months | 954.89 | 0.87 | 632.65 | 130.80 | 383.47 | 0.00 | 0.00 |
Maximum of Months | 1989.69 | 527.01 | 756.89 | 302.35 | 524.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255757E+10 | 0.141155E+10 | 0.180712E+10 | 0.711056E+09 | 0.109607E+10 | 0.00 | 0.00 |
February | 0.251511E+10 | 0.107708E+10 | 0.165739E+10 | 0.572496E+09 | 0.108489E+10 | 0.00 | 0.00 |
March | 0.303266E+10 | 0.918871E+09 | 0.178938E+10 | 0.481078E+09 | 0.130831E+10 | 0.00 | 0.00 |
April | 0.342449E+10 | 0.566088E+09 | 0.173355E+10 | 0.391943E+09 | 0.134161E+10 | 0.00 | 0.00 |
May | 0.442737E+10 | 0.175141E+09 | 0.181748E+10 | 0.411627E+09 | 0.140585E+10 | 0.00 | 0.00 |
June | 0.451856E+10 | 61574319.30 | 0.173506E+10 | 0.393483E+09 | 0.134158E+10 | 0.00 | 0.00 |
July | 0.508470E+10 | 2978713.96 | 0.169448E+10 | 0.350345E+09 | 0.134414E+10 | 0.00 | 0.00 |
August | 0.532917E+10 | 2322428.23 | 0.180086E+10 | 0.415946E+09 | 0.138491E+10 | 0.00 | 0.00 |
September | 0.466807E+10 | 87643820.76 | 0.185473E+10 | 0.519442E+09 | 0.133529E+10 | 0.00 | 0.00 |
October | 0.435180E+10 | 0.294579E+09 | 0.202724E+10 | 0.730643E+09 | 0.129660E+10 | 0.00 | 0.00 |
November | 0.344883E+10 | 0.669645E+09 | 0.190796E+10 | 0.783681E+09 | 0.112428E+10 | 0.00 | 0.00 |
December | 0.263730E+10 | 0.120200E+10 | 0.173235E+10 | 0.705266E+09 | 0.102708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459956E+11 | 0.646948E+10 | 0.215576E+11 | 0.646701E+10 | 0.150906E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251511E+10 | 2322428.23 | 0.165739E+10 | 0.350345E+09 | 0.102708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532917E+10 | 0.141155E+10 | 0.202724E+10 | 0.783681E+09 | 0.140585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.638016E+10 | -0.622520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154960124.1 | 81.21 | 0.00 | 0.00 |
February | 0.577382E+10 | -0.563431E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -139504997.8 | 81.21 | 0.00 | 0.00 |
March | 0.644794E+10 | -0.629388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154067448.8 | 81.21 | 0.00 | 0.00 |
April | 0.619225E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148774112.9 | 81.22 | 0.00 | 0.00 |
May | 0.641340E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153217573.6 | 81.21 | 0.00 | 0.00 |
June | 0.623268E+10 | -0.608658E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -146101156.5 | 81.21 | 0.00 | 0.00 |
July | 0.636517E+10 | -0.621709E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148085375.0 | 81.22 | 0.00 | 0.00 |
August | 0.644235E+10 | -0.629519E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147158330.8 | 81.22 | 0.00 | 0.00 |
September | 0.618982E+10 | -0.604481E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -145016909.3 | 81.22 | 0.00 | 0.00 |
October | 0.637660E+10 | -0.622383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152775916.3 | 81.21 | 0.00 | 0.00 |
November | 0.617331E+10 | -0.602462E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -148682616.2 | 81.21 | 0.00 | 0.00 |
December | 0.637136E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154262403.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.753589E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179261E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.577382E+10 | -0.629519E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -154960124.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.644794E+10 | -0.563431E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -139504997.8 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.174401E+11 | -0.165952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -844921424.0 | 58.99 | 0.00 | 0.00 |
February | 0.153509E+11 | -0.145922E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -758673702.1 | 58.98 | 0.00 | 0.00 |
March | 0.159969E+11 | -0.151603E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -836691575.2 | 58.99 | 0.00 | 0.00 |
April | 0.138808E+11 | -0.130744E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -806450943.5 | 58.98 | 0.00 | 0.00 |
May | 0.128695E+11 | -0.120408E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -828760810.0 | 58.98 | 0.00 | 0.00 |
June | 0.114402E+11 | -0.106582E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -782052779.9 | 58.98 | 0.00 | 0.00 |
July | 0.113270E+11 | -0.105454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -781549564.6 | 58.98 | 0.00 | 0.00 |
August | 0.119398E+11 | -0.111666E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -773226982.5 | 58.98 | 0.00 | 0.00 |
September | 0.126298E+11 | -0.118577E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -772163077.8 | 58.98 | 0.00 | 0.00 |
October | 0.145669E+11 | -0.137421E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -824827632.6 | 58.99 | 0.00 | 0.00 |
November | 0.155477E+11 | -0.147419E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -805777702.0 | 58.98 | 0.00 | 0.00 |
December | 0.170938E+11 | -0.162554E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -838362346.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.170084E+12 | -0.160430E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.965346E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.113270E+11 | -0.165952E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -844921424.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.174401E+11 | -0.105454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -758673702.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.77 | 0.75 | 01-JAN-07:00 | 771.95 | 24.51 | 219.00 | 292.33 | 741.26 | 24.23 | 220.33 | 292.67 |
February | 308.33 | 0.77 | 0.75 | 01-FEB-07:00 | 720.36 | 21.84 | 153.17 | 268.83 | 710.43 | 21.89 | 159.50 | 268.33 |
March | 357.50 | 0.77 | 0.75 | 01-MAR-08:20 | 723.34 | 19.89 | 100.00 | 312.17 | 705.90 | 20.00 | 114.17 | 313.00 |
April | 375.00 | 0.77 | 0.75 | 01-APR-07:30 | 699.66 | 19.31 | 81.67 | 328.83 | 612.17 | 19.36 | 83.17 | 326.33 |
May | 405.33 | 0.77 | 0.75 | 01-MAY-06:40 | 622.53 | 19.22 | 71.67 | 356.83 | 625.74 | 19.20 | 73.00 | 356.67 |
June | 403.50 | 0.77 | 0.75 | 01-JUN-06:49 | 587.75 | 20.73 | 106.50 | 348.50 | 612.98 | 19.18 | 71.83 | 348.67 |
July | 405.00 | 0.78 | 0.75 | 01-JUL-06:00 | 581.58 | 19.51 | 79.67 | 347.33 | 592.68 | 19.04 | 77.00 | 346.33 |
August | 395.83 | 0.77 | 0.75 | 01-AUG-06:00 | 692.92 | 19.49 | 99.50 | 345.67 | 638.66 | 19.50 | 103.17 | 344.67 |
September | 358.83 | 0.77 | 0.75 | 01-SEP-07:10 | 747.90 | 20.21 | 124.33 | 322.33 | 701.39 | 20.18 | 125.33 | 319.83 |
October | 351.17 | 0.77 | 0.75 | 01-OCT-07:10 | 791.03 | 21.40 | 177.33 | 318.00 | 867.05 | 22.17 | 202.83 | 316.83 |
November | 318.83 | 0.76 | 0.75 | 01-NOV-06:00 | 858.62 | 24.44 | 237.17 | 296.17 | 832.82 | 24.60 | 239.17 | 298.17 |
December | 319.00 | 0.77 | 0.75 | 01-DEC-07:30 | 780.12 | 24.36 | 218.33 | 285.50 | 732.02 | 24.25 | 217.00 | 286.17 |
Annual Sum or Average | 4323.33 | 0.77 | 708.26 | 21.08 | 1668.33 | 3822.50 | 691.80 | 20.95 | 1686.50 | 3817.67 | ||
Minimum of Months | 308.33 | 0.76 | 0.75 | 581.58 | 19.22 | 71.67 | 268.83 | 592.68 | 19.04 | 71.83 | 268.33 | |
Maximum of Months | 405.33 | 0.78 | 0.75 | 858.62 | 24.51 | 237.17 | 356.83 | 867.05 | 24.60 | 239.17 | 356.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9125579.98 | 1088.54 | 16-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9125579.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9125579.98 | 1088.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306497E+11 | 0.214367E+11 | 47125.26 | 24-JAN-13:00 | 26338.42 | 0.00 |
February | 0.00 | 0.00 | 0.365564E+11 | 0.250659E+11 | 60069.04 | 07-FEB-13:00 | 43536.05 | 0.00 |
March | 0.00 | 0.00 | 0.523078E+11 | 0.381904E+11 | 65818.03 | 28-MAR-11:23 | 38375.94 | 0.00 |
April | 0.00 | 0.00 | 0.751766E+11 | 0.530522E+11 | 84830.46 | 29-APR-19:00 | 42467.62 | 0.00 |
May | 0.00 | 0.00 | 0.113878E+12 | 0.801200E+11 | 124040.47 | 18-MAY-04:02 | 51968.32 | 0.00 |
June | 0.00 | 0.00 | 0.144278E+12 | 0.874083E+11 | 124040.47 | 27-JUN-04:01 | 36681.02 | 0.00 |
July | 0.00 | 0.00 | 0.176780E+12 | 0.102553E+12 | 124040.47 | 06-JUL-05:03 | 47312.59 | 0.00 |
August | 0.00 | 0.00 | 0.187094E+12 | 0.105798E+12 | 124040.47 | 31-AUG-04:01 | 42489.60 | 0.00 |
September | 0.00 | 0.00 | 0.156630E+12 | 0.874944E+11 | 124040.47 | 29-SEP-04:02 | 38553.95 | 0.00 |
October | 0.00 | 0.00 | 0.118814E+12 | 0.733988E+11 | 124040.47 | 01-OCT-04:02 | 40498.27 | 0.00 |
November | 0.00 | 0.00 | 0.779983E+11 | 0.509946E+11 | 124040.47 | 03-NOV-04:01 | 58005.97 | 0.00 |
December | 0.00 | 0.00 | 0.461500E+11 | 0.301404E+11 | 63094.71 | 05-DEC-13:00 | 32788.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121631E+13 | 0.755653E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.306497E+11 | 0.214367E+11 | 47125.26 | 26338.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187094E+12 | 0.105798E+12 | 124040.47 | 58005.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.215220E+11 | 0.145939E+11 | 40996.86 | 12-JAN-05:01 | 25038.04 | 0.00 |
February | 0.00 | 0.00 | 0.253103E+11 | 0.169225E+11 | 40996.86 | 03-FEB-05:01 | 24484.95 | 0.00 |
March | 0.00 | 0.00 | 0.355414E+11 | 0.259958E+11 | 43579.02 | 28-MAR-11:00 | 23839.10 | 0.00 |
April | 0.00 | 0.00 | 0.513720E+11 | 0.369179E+11 | 45550.21 | 29-APR-20:20 | 20165.38 | 0.00 |
May | 0.00 | 0.00 | 0.759767E+11 | 0.564285E+11 | 45550.21 | 24-MAY-05:03 | 18184.03 | 0.00 |
June | 0.00 | 0.00 | 0.898721E+11 | 0.578030E+11 | 45550.21 | 07-JUN-22:05 | 18747.83 | 0.00 |
July | 0.00 | 0.00 | 0.100544E+12 | 0.634087E+11 | 45550.21 | 02-JUL-05:03 | 19632.49 | 0.00 |
August | 0.00 | 0.00 | 0.102384E+12 | 0.632536E+11 | 45550.21 | 31-AUG-03:22 | 17172.88 | 0.00 |
September | 0.00 | 0.00 | 0.938404E+11 | 0.548522E+11 | 45550.21 | 09-SEP-05:30 | 18920.19 | 0.00 |
October | 0.00 | 0.00 | 0.797519E+11 | 0.500748E+11 | 45550.21 | 07-OCT-08:30 | 14351.11 | 0.00 |
November | 0.00 | 0.00 | 0.533387E+11 | 0.350247E+11 | 45550.21 | 02-NOV-20:00 | 23145.29 | 0.00 |
December | 0.00 | 0.00 | 0.324567E+11 | 0.204572E+11 | 40996.86 | 20-DEC-05:01 | 27874.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.761910E+12 | 0.495733E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.215220E+11 | 0.145939E+11 | 40996.86 | 14351.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102384E+12 | 0.634087E+11 | 45550.21 | 27874.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6661.34 | 12637.14 | 12-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6497.25 | 12518.46 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 6126.86 | 11944.21 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5512.12 | 10852.81 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4964.78 | 9831.85 | 01-MAY-18:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4583.64 | 8865.78 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4408.95 | 8401.81 | 31-JUL-18:27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4640.28 | 9004.55 | 31-AUG-18:10 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5043.97 | 9927.55 | 29-SEP-18:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5598.44 | 11111.02 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6153.93 | 12047.30 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 6534.30 | 12581.26 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 5555.39 | ||||
Minimum of Months | 0.00 | 0.00 | 4408.95 | 8401.81 | ||
Maximum of Months | 0.00 | 0.00 | 6661.34 | 12637.14 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.206863E+10 | 0.25 | 824.13 | 01-JAN-00:10 | 0.26 |
February | 0.187881E+10 | 0.25 | 824.13 | 01-FEB-00:03 | 0.26 |
March | 0.209257E+10 | 0.25 | 824.13 | 01-MAR-00:03 | 0.26 |
April | 0.203552E+10 | 0.25 | 824.13 | 01-APR-00:20 | 0.26 |
May | 0.210804E+10 | 0.25 | 824.13 | 01-MAY-00:12 | 0.26 |
June | 0.203641E+10 | 0.25 | 824.13 | 01-JUN-00:08 | 0.26 |
July | 0.210766E+10 | 0.25 | 824.13 | 01-JUL-00:09 | 0.26 |
August | 0.210816E+10 | 0.25 | 824.13 | 01-AUG-00:06 | 0.26 |
September | 0.203799E+10 | 0.25 | 824.13 | 01-SEP-00:07 | 0.26 |
October | 0.210292E+10 | 0.25 | 824.13 | 01-OCT-00:08 | 0.26 |
November | 0.203829E+10 | 0.25 | 824.13 | 01-NOV-00:10 | 0.26 |
December | 0.209245E+10 | 0.25 | 824.13 | 01-DEC-00:05 | 0.26 |
Annual Sum or Average | 0.247074E+11 | 0.25 | |||
Minimum of Months | 0.187881E+10 | 0.25 | 824.13 | 0.26 | |
Maximum of Months | 0.210816E+10 | 0.25 | 824.13 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.689924E+10 | 0.70 | 3133.64 | 16-JAN-06:10 | 0.85 |
February | 0.623138E+10 | 0.70 | 3242.80 | 07-FEB-13:00 | 0.86 |
March | 0.690338E+10 | 0.70 | 3579.51 | 27-MAR-12:00 | 0.92 |
April | 0.674296E+10 | 0.70 | 4821.38 | 29-APR-19:00 | 1.09 |
May | 0.776819E+10 | 0.74 | 7727.25 | 13-MAY-04:01 | 1.37 |
June | 0.915693E+10 | 0.83 | 7727.25 | 01-JUN-04:01 | 1.37 |
July | 0.112360E+11 | 0.91 | 7727.25 | 01-JUL-04:02 | 1.36 |
August | 0.118907E+11 | 0.95 | 7727.25 | 01-AUG-04:01 | 1.36 |
September | 0.985503E+10 | 0.86 | 7727.25 | 01-SEP-04:01 | 1.37 |
October | 0.790063E+10 | 0.75 | 7727.25 | 01-OCT-04:02 | 1.36 |
November | 0.681465E+10 | 0.70 | 7727.25 | 03-NOV-04:01 | 1.37 |
December | 0.689912E+10 | 0.70 | 3341.85 | 12-DEC-06:02 | 0.88 |
Annual Sum or Average | 0.982983E+11 | 0.77 | |||
Minimum of Months | 0.623138E+10 | 0.70 | 3133.64 | 0.85 | |
Maximum of Months | 0.118907E+11 | 0.95 | 7727.25 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163272E+10 | 0.49 | 1790.68 | 06-JAN-04:21 | 0.88 |
February | 0.152836E+10 | 0.50 | 1790.68 | 03-FEB-05:01 | 0.87 |
March | 0.181161E+10 | 0.52 | 1790.68 | 17-MAR-03:11 | 0.87 |
April | 0.215265E+10 | 0.58 | 1790.68 | 18-APR-03:31 | 0.87 |
May | 0.301453E+10 | 0.67 | 1790.68 | 02-MAY-03:31 | 0.87 |
June | 0.358733E+10 | 0.74 | 1790.68 | 01-JUN-04:01 | 0.87 |
July | 0.407214E+10 | 0.77 | 1790.68 | 01-JUL-03:23 | 0.86 |
August | 0.414614E+10 | 0.78 | 1790.68 | 01-AUG-00:06 | 0.86 |
September | 0.372960E+10 | 0.75 | 1790.68 | 01-SEP-00:07 | 0.86 |
October | 0.311102E+10 | 0.68 | 1790.68 | 01-OCT-00:08 | 0.86 |
November | 0.218778E+10 | 0.58 | 1790.68 | 01-NOV-03:22 | 0.87 |
December | 0.176812E+10 | 0.52 | 1790.68 | 16-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.327420E+11 | 0.63 | |||
Minimum of Months | 0.152836E+10 | 0.49 | 1790.68 | 0.86 | |
Maximum of Months | 0.414614E+10 | 0.78 | 1790.68 | 0.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:10 | 5.36 | 5.36 | 50.91 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:03 | 5.36 | 5.36 | 51.33 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:03 | 5.36 | 5.36 | 51.65 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 54.20 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 54.08 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 55.09 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:03 | 5.36 | 5.36 | 54.99 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:03 | 5.36 | 5.36 | 54.91 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:03 | 5.36 | 5.36 | 55.44 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 53.53 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:02 | 5.36 | 5.36 | 54.35 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:05 | 5.36 | 5.36 | 51.78 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 50.91 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 55.44 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.91 | 59.47 | 6661.34 | 12637.14 | 12-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.33 | 58.14 | 6497.25 | 12518.46 | 01-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.65 | 58.12 | 6126.86 | 11944.21 | 01-MAR-19:10 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.12 | 53.12 | 5512.12 | 10852.81 | 03-APR-19:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 53.31 | 53.31 | 4964.78 | 9831.85 | 01-MAY-18:25 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 54.32 | 54.32 | 4583.64 | 8865.78 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 54.59 | 54.59 | 4408.95 | 8401.81 | 31-JUL-18:27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 54.24 | 54.24 | 4640.28 | 9004.55 | 31-AUG-18:10 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 54.43 | 54.43 | 5043.97 | 9927.55 | 29-SEP-18:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 51.97 | 51.97 | 5598.44 | 11111.02 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 53.45 | 53.45 | 6153.93 | 12047.30 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.78 | 58.38 | 6534.30 | 12581.26 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 5555.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.91 | 51.97 | 4408.95 | 8401.81 | ||
Maximum of Months | 0.00 | 0.00 | 54.59 | 59.47 | 6661.34 | 12637.14 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163332E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171794E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.223296E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.280867E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.403358E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.500663E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.626647E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.663479E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.533689E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.402913E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.284035E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204468E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.445854E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163332E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.663479E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.722504E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.792226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107060E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146927E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.221165E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.263072E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.302604E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.308153E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.270377E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.222893E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149000E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.978611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224058E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.722504E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.308153E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.689924E+10 | 0.306497E+11 | 9125579.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623138E+10 | 0.365564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690338E+10 | 0.523078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.674296E+10 | 0.751766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.776819E+10 | 0.113878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.915693E+10 | 0.144278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112360E+11 | 0.176780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118907E+11 | 0.187094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.985503E+10 | 0.156630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.790063E+10 | 0.118814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.681465E+10 | 0.779983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689912E+10 | 0.461500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.982983E+11 | 0.121631E+13 | 9125579.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.623138E+10 | 0.306497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118907E+11 | 0.187094E+12 | 9125579.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163272E+10 | 0.215220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152836E+10 | 0.253103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181161E+10 | 0.355414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215265E+10 | 0.513720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301453E+10 | 0.759767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358733E+10 | 0.898721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407214E+10 | 0.100544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414614E+10 | 0.102384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372960E+10 | 0.938404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.311102E+10 | 0.797519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218778E+10 | 0.533387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176812E+10 | 0.324567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327420E+11 | 0.761910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152836E+10 | 0.215220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.414614E+10 | 0.102384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.689924E+10 | 0.00 | 0.00 | 0.00 | 0.943392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623138E+10 | 0.00 | 0.00 | 0.00 | 0.109480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690338E+10 | 0.00 | 0.00 | 0.00 | 0.154262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.674296E+10 | 0.00 | 0.00 | 0.00 | 0.213437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.776819E+10 | 0.00 | 0.00 | 0.00 | 0.325676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.915693E+10 | 0.00 | 0.00 | 0.00 | 0.409094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112360E+11 | 0.00 | 0.00 | 0.00 | 0.514286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118907E+11 | 0.00 | 0.00 | 0.00 | 0.544572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.985503E+10 | 0.00 | 0.00 | 0.00 | 0.435139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.790063E+10 | 0.00 | 0.00 | 0.00 | 0.323906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.681465E+10 | 0.00 | 0.00 | 0.00 | 0.215888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689912E+10 | 0.00 | 0.00 | 0.00 | 0.135477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.982983E+11 | 0.00 | 0.00 | 0.00 | 0.347556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.623138E+10 | 0.00 | 0.00 | 0.00 | 0.943392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118907E+11 | 0.00 | 0.00 | 0.00 | 0.544572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163272E+10 | 0.00 | 0.00 | 0.00 | 0.559232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152836E+10 | 0.00 | 0.00 | 0.00 | 0.639389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181161E+10 | 0.00 | 0.00 | 0.00 | 0.889438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215265E+10 | 0.00 | 0.00 | 0.00 | 0.125400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301453E+10 | 0.00 | 0.00 | 0.00 | 0.191020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358733E+10 | 0.00 | 0.00 | 0.00 | 0.227199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407214E+10 | 0.00 | 0.00 | 0.00 | 0.261882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414614E+10 | 0.00 | 0.00 | 0.00 | 0.266692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372960E+10 | 0.00 | 0.00 | 0.00 | 0.233081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.311102E+10 | 0.00 | 0.00 | 0.00 | 0.191782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218778E+10 | 0.00 | 0.00 | 0.00 | 0.127122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176812E+10 | 0.00 | 0.00 | 0.00 | 0.801798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327420E+11 | 0.00 | 0.00 | 0.00 | 0.191316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152836E+10 | 0.00 | 0.00 | 0.00 | 0.559232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.414614E+10 | 0.00 | 0.00 | 0.00 | 0.266692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.719522E+10 | 0.663001E+09 | 0.00 | 71320454.37 | 0.00 | 0.00 | 0.123788E+11 | 0.00 | 3.59 |
February | 0.415745E+10 | 0.270833E+10 | 0.00 | 57387994.61 | 5445609.85 | 0.00 | 0.881580E+10 | 0.00 | 3.61 |
March | 0.245190E+10 | 0.664516E+10 | 0.00 | 52525430.24 | 21591568.53 | 0.00 | 0.661577E+10 | 0.00 | 3.63 |
April | 0.767797E+09 | 0.195545E+11 | 0.00 | 12372851.81 | 0.129925E+09 | 0.00 | 0.223054E+10 | 0.00 | 3.63 |
May | 53947894.76 | 0.436337E+11 | 0.00 | 2561184.61 | 0.821949E+09 | 0.00 | 0.316687E+09 | 0.00 | 3.65 |
June | 9379266.75 | 0.669197E+11 | 0.00 | 2047023.16 | 0.143781E+10 | 0.00 | 67165111.53 | 0.00 | 3.69 |
July | 8751880.44 | 0.889551E+11 | 0.00 | 961380.34 | 0.247427E+10 | 0.00 | 47675219.87 | 0.00 | 3.71 |
August | 257767.62 | 0.952624E+11 | 0.00 | 426060.71 | 0.225860E+10 | 0.00 | 8447695.94 | 0.00 | 3.72 |
September | 2259161.25 | 0.749760E+11 | 0.00 | 2122894.24 | 0.151676E+10 | 0.00 | 62376335.75 | 0.00 | 3.67 |
October | 72883234.90 | 0.464845E+11 | 0.00 | 4111839.97 | 0.739848E+09 | 0.00 | 0.222514E+09 | 0.00 | 3.63 |
November | 0.668779E+09 | 0.197669E+11 | 0.00 | 13310078.32 | 0.119021E+09 | 0.00 | 0.192378E+10 | 0.00 | 3.62 |
December | 0.361218E+10 | 0.471119E+10 | 0.00 | 53323635.39 | 6941215.40 | 0.00 | 0.862160E+10 | 0.00 | 3.60 |
Annual Sum or Average | 0.190008E+11 | 0.470280E+12 | 0.00 | 0.272471E+09 | 0.953216E+10 | 0.00 | 0.413112E+11 | 0.00 | 3.65 |
Minimum of Months | 257767.62 | 0.663001E+09 | 0.00 | 426060.71 | 0.00 | 0.00 | 8447695.94 | 0.00 | 3.59 |
Maximum of Months | 0.719522E+10 | 0.952624E+11 | 0.00 | 71320454.37 | 0.247427E+10 | 0.00 | 0.123788E+11 | 0.00 | 3.72 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227919E+10 | 0.263039E+09 | 0.00 | 96783715.06 | 0.00 | 0.00 | 0.238304E+11 | 0.00 | 8.12 |
February | 0.935128E+09 | 0.114306E+10 | 0.00 | 90080789.48 | 0.00 | 0.00 | 0.174379E+11 | 0.00 | 8.24 |
March | 0.437810E+09 | 0.286500E+10 | 0.00 | 96133240.56 | 0.00 | 0.00 | 0.145004E+11 | 0.00 | 8.42 |
April | 46279963.17 | 0.100761E+11 | 0.00 | 53647212.40 | 0.00 | 0.00 | 0.501872E+10 | 0.00 | 8.76 |
May | 2759.33 | 0.255751E+11 | 0.00 | 16423154.02 | 0.00 | 0.00 | 0.792748E+09 | 0.00 | 9.11 |
June | 0.00 | 0.393917E+11 | 0.00 | 2000845.44 | 0.00 | 0.00 | 45678271.38 | 0.00 | 9.58 |
July | 255407.45 | 0.482216E+11 | 0.00 | 1166065.85 | 0.00 | 0.00 | 41473273.36 | 0.00 | 10.13 |
August | 0.00 | 0.495213E+11 | 0.00 | 4171.79 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
September | 0.00 | 0.431054E+11 | 0.00 | 931144.51 | 0.00 | 0.00 | 21357250.09 | 0.00 | 9.68 |
October | 2297461.51 | 0.288523E+11 | 0.00 | 14075610.94 | 5582.54 | 0.00 | 0.742477E+09 | 0.00 | 9.16 |
November | 48126886.78 | 0.106416E+11 | 0.00 | 46622022.00 | 163287.66 | 0.00 | 0.441080E+10 | 0.00 | 8.74 |
December | 0.716259E+09 | 0.277640E+10 | 0.00 | 84827515.49 | 0.00 | 0.00 | 0.165951E+11 | 0.00 | 8.33 |
Annual Sum or Average | 0.446535E+10 | 0.262433E+12 | 0.00 | 0.502695E+09 | 168870.20 | 0.00 | 0.834371E+11 | 0.00 | 9.05 |
Minimum of Months | 0.00 | 0.263039E+09 | 0.00 | 4171.79 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
Maximum of Months | 0.227919E+10 | 0.495213E+11 | 0.00 | 96783715.06 | 163287.66 | 0.00 | 0.238304E+11 | 0.00 | 10.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.527543E+11 | 0.496816E+10 | 0.937191E+11 | 0.815752E+10 | 0.890606E+11 |
February | 0.617061E+11 | 0.351948E+10 | 0.625823E+11 | 0.615685E+10 | 0.996256E+11 |
March | 0.848201E+11 | 0.219162E+10 | 0.438476E+11 | 0.561084E+10 | 0.135985E+12 |
April | 0.975566E+11 | -0.174866E+10 | -0.151286E+11 | 0.460253E+10 | 0.184796E+12 |
May | 0.109457E+12 | -0.671469E+10 | -0.923277E+11 | 0.186119E+10 | 0.268343E+12 |
June | 0.109664E+12 | -0.116700E+11 | -0.151004E+12 | -57559369.3 | 0.324648E+12 |
July | 0.108428E+12 | -0.154978E+11 | -0.190975E+12 | -0.304158E+10 | 0.383480E+12 |
August | 0.106039E+12 | -0.174154E+11 | -0.200687E+12 | -0.429927E+10 | 0.399094E+12 |
September | 0.867841E+11 | -0.142762E+11 | -0.167137E+12 | -399733609.8 | 0.344374E+12 |
October | 0.674393E+11 | -0.865582E+10 | -0.103489E+12 | 0.784184E+09 | 0.276503E+12 |
November | 0.500291E+11 | -0.332235E+10 | -0.196688E+11 | 0.388071E+10 | 0.188611E+12 |
December | 0.462991E+11 | 0.196773E+10 | 0.559101E+11 | 0.677304E+10 | 0.122105E+12 |
Annual Sum or Average | 0.980977E+12 | -0.666539E+11 | -0.684357E+12 | 0.300287E+11 | 0.281662E+13 |
Minimum of Months | 0.462991E+11 | -0.174154E+11 | -0.200687E+12 | -0.429927E+10 | 0.890606E+11 |
Maximum of Months | 0.109664E+12 | 0.496816E+10 | 0.937191E+11 | 0.815752E+10 | 0.399094E+12 |