Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:29:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2619.33 | 5124.36 | 5124.36 |
Net Site Energy | 2619.33 | 5124.36 | 5124.36 |
Total Source Energy | 4629.08 | 9056.15 | 9056.15 |
Net Source Energy | 4629.08 | 9056.15 | 9056.15 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 511.15 |
Net Conditioned Building Area | 511.15 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 894.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 76.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 123.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 75.51 | 395.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | 49.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 859.20 | 1760.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 894.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 76.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 417.59 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 123.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 75.51 | 395.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 894.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 76.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 449.99 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 123.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 75.51 | 395.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
Refrigeration | Unassigned | 49.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 539.33 | 2524.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 977.29 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1680.91 | 3443.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 164.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 539.33 | 2524.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Other | 977.29 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1680.91 | 3443.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 859.204 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 859.204 | 100.00 |
Total On-Site and Utility Electric Sources | 859.204 | 100.00 |
Total Electricity End Uses | 859.204 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2201.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
Total Water End Uses | 2201.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 22.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4695.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
Window Opening Area [m2] | 47.17 | 0.00 | 13.93 | 19.30 | 13.93 |
Gross Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Above Ground Window-Wall Ratio [%] | 17.11 | 0.00 | 20.22 | 28.00 | 20.22 |
Total | |
Gross Roof Area [m2] | 569.51 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 47.17 | 47.17 | 6.9552 | 1.33 | 64.9275 |
KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 8.1538 | 18.52 | 1060.6406 |
ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 47.17 | 47.17 | 7.2821 | 1.78 | 336.4852 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.9552 | 1.33 | 64.9275 | |
KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.1538 | 18.52 | 1060.6406 | |
ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Conditioned Total | 511.15 | 7.2821 | 0.89 | 336.4852 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 7.2821 | 1.78 | 336.4852 |
Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-11:00 | 02-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 22-MAR-18:40 |
Heating | 0.00 | 228896.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 34667.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22750.50 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8583.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2993.35 | 32219.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1747.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 73250.02 | 274693.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 228896.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 34667.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 21723.00 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8583.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 2993.35 | 32219.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 477.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 969.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 242.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 92.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1425.12 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 389.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 239.16 | 429.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 156.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2721.10 | 1907.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 474.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 762.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.87 | 839.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 307.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5323.45 | 3732.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 474.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 181.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2788.05 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 762.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 467.87 | 839.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 307.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5323.45 | 3732.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 3.73 |
KITCHEN DIRECT AIR | 1.58 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.73 | 3.73 | 3.73 | 3.73 | 3.73 | 3.73 | 1.00 | 0.999994 | 3.73 |
PSZ-AC_2:2 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.00 | 1.00 | 1.58 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.73 | 1.33 |
PSZ-AC_2:2_OA_CONTROLLER | 1.58 | 1.22 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 3.73 | 6368.20 |
PSZ-AC_2:2_ADDAQ FAN | 1.58 | 1687.66 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.73 | 3.73 | 3.73 | 2.46 | 92554.00 | 154261.74 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.58 | 1.58 | 1.58 | 1.04 | 39165.20 | 101956.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.73 | 1.86 | 2.48 | 92554.00 | 46277.00 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.58 | 0.788591 | 1.05 | 39165.20 | 19582.60 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 154261.74 |
PSZ-AC_2:2 HEATING COIL | 101956.36 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000140 | 0.016782 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000140 | 17.86 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 122.02 | 47.17 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 6.955 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 71.883 | No |
2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 8.154 | 411.365 | 649.276 | 0.000 | 0.000 | 0.000 | 1068.794 | No |
3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 2585.575 | 6.955 | 9.230 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2585.575 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1136.687 | 8.154 | 150.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1136.687 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 457.500 | 3.282 | 60.774 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 570.000 | 4.089 | 75.718 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.019 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1426 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2431 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7470 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.935 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.036 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.27769917E-12 | 0.13612904E-14 | -0.80830397E-13 | 0.78755032E-16 |
34 | 6 | 0.25767564E-07 | 0.27734673E-09 | 0.59270795E-08 | -0.11967802E-12 |
35 | 5 | -0.17525067E-03 | 0.24203254E-05 | -0.90321702E-04 | 0.58672059E-08 |
36 | 4 | 0.27459513 | 0.11984273E-02 | 0.93379247E-01 | -0.31111903E-04 |
37 | 3 | -6.9183358 | 0.37695562E-01 | -2.2356803 | 0.27304756E-01 |
38 | 2 | 39.723007 | 0.13580171 | 14.840691 | -0.32055548 |
39 | 1 | -79.665490 | 0.61986396E-01 | -28.760905 | 1.0598607 |
40 | 0 | 46.824344 | 0.12610511E-02 | 16.300551 | |
41 | 7 | -0.29769246E-08 | -0.18967486E-14 | 0.17735324E-14 | -0.50565546E-16 |
42 | 6 | 0.41018669E-05 | 0.27270264E-08 | 0.31943096E-02 | -0.26796545E-04 |
43 | 5 | -0.28850807E-03 | 0.16127836E-05 | -0.22397690 | 0.19583774E-02 |
44 | 4 | 0.65943933E-02 | 0.73359200E-04 | 4.8337480 | -0.45305377E-01 |
45 | 3 | -0.57777404E-01 | 0.58296435E-03 | -38.045154 | 0.39891614 |
46 | 2 | 0.20497420 | 0.96924505E-03 | 116.53015 | -1.4185573 |
47 | 1 | -0.29573351 | 0.29504543E-03 | -143.93450 | 2.0494869 |
48 | 0 | 0.14415612 | 0.71556298E-05 | 60.838472 | |
49 | 7 | -0.17284864E-08 | -0.37804902E-15 | 0.73321507E-14 | -0.99177345E-16 |
50 | 6 | 0.68009956E-05 | 0.46606830E-08 | 0.31864372E-02 | -0.26730506E-04 |
51 | 5 | -0.48976058E-03 | 0.27623059E-05 | -0.22352946 | 0.19544281E-02 |
52 | 4 | 0.11270010E-01 | 0.12574428E-03 | 4.8262959 | -0.45233742E-01 |
53 | 3 | -0.98979995E-01 | 0.10001134E-02 | -38.003058 | 0.39845083 |
54 | 2 | 0.35147541 | 0.16637932E-02 | 116.44822 | -1.4174614 |
55 | 1 | -0.50731320 | 0.50715641E-03 | -143.88627 | 2.0486942 |
56 | 0 | 0.24734252 | 0.12206389E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3615_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 0.749 | 0.2544 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.614 | 1.653E-003 | 3.632E-003 | 1.952 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6372E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6401E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5311E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4266E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3936E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4112E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.0828E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0008E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.0836E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.9821E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.0081E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.8864E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1114E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.0703E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0253E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0253E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5118E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4711E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2621E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3175E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.2433E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2573E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0008E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0828E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 40700.79833 | 48840.95800 | 3.10594 | 3.72713 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
2 | DINING | Heating | 13409.28615 | 16091.14338 | 0.60255 | 1.33138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
3 | KITCHEN | Cooling | 20315.24900 | 24378.29880 | 1.31432 | 1.57718 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
4 | KITCHEN | Heating | 3324.54027 | 3989.44832 | 0.13515 | 1.21700 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 59179.27 | 3.72715 | 3.72715 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 101722.32 | 1.33138 | 1.33138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 29970.88 | 1.57718 | 1.57718 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 92983.59 | 1.21700 | 1.21700 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.72713 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57718 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.72713 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.72713 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.72713 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.72713 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.72715 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.72715 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99999 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57718 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57718 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57718 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57718 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57718 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57718 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.72715 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.57718 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.72715 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.72715 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6368.20155 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.72715 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.72715 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.72715 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.45992 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.72715 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.86357 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.48477 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 92554.00000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 46277.00000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 92554.00000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 154261.73843 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 154261.73843 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57718 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57718 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1687.65989 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57718 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57718 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57718 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.04094 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57718 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78859 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05145 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39165.20000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19582.60000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39165.20000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 101956.35748 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 101956.35748 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 89904.9 | 10.76 | 10.71 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 38044.2 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | N/A | 2.054 | No | 13.93 | 13.93 | 13.93 | 90.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 49.63 | 68.93 | 49.63 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | N/A | 2.054 | No | 19.30 | 19.30 | 19.30 | 180.00 | 90.00 | 21.10 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 36.20 | 50.13 | 36.20 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | N/A | 2.054 | No | 13.93 | 13.93 | 13.93 | 270.00 | 90.00 | 15.24 | 0.91 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.143 | 0.138 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.019 | 0.884 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.243 | 0.230 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.9525211979E-002 | 0.4036295829 | Pass | Pass | 1.6062201555 | 14.0507813690 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 9.5913755927E-002 | 0.5514200191 | Pass | Pass | 3.2323983227E-002 | 8.9873362517E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1407445189 | 0.1684289790 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 992.13 | 192.37 | 2200.33 | 7.52 | 753.92 | 4146.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 49.63 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 50.13 | 36.20 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.139 | 0.143 | 371.75 | 371.75 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 68.93 | 68.93 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 16.85 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.884 | 1.019 | 18.80 | 18.80 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.234 | 0.243 | 139.41 | 139.41 | 0.00 | 180.00 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 371.75 | 371.75 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 139.41 | 139.41 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | 19.30 | 0.00 | 0.00 | 19.30 | 19.30 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | 13.93 | 0.00 | 0.00 | 13.93 | 13.93 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 47.17 | 2.054 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 47.17 | 2.054 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.9552 | 371.75 | 2585.58 | LightsWired | LTG_SCH_DINING | 94.06 | 168.00 | 79.30 | 0.0000 | Y | 38.49 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.1538 | 139.41 | 1136.69 | LightsWired | LTG_SCH_KITCHEN | 76.73 | 168.00 | 76.28 | 0.0000 | Y | 16.28 |
Interior Lighting Total | 7.2821 | 511.15 | 3722.26 | 54.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.25 | 2585.58 | 646.39 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 2585.58 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 159.78 | AstronomicalClock | - | 49.24 | 49.24 | 1.48 | |
EXTERIOR_LIGHTS_B | 2015.63 | AstronomicalClock | - | 83.63 | 73.31 | 27.74 | |
Exterior Lighting Total | 2175.41 | 29.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 92554.00 | 64887.76 | 27666.24 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39165.20 | 27457.94 | 11707.26 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 89904.9 | 10.76 | 10.71 | ||||
PSZ-AC_2:2 COOLING COIL | 38044.2 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 154261.74 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 101956.36 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 2.55 | 824.13 | 323.38 | 1.00 | 1.42 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 1018.41 | 3.73 | 6368.20 | 1708.60 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.58 | 1687.66 | 1070.05 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.75 | 0.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 40700.80 | 48840.96 | 131.38 | 3.106 | 3.727 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01109 | 31.09 | 0.01536 | 1.331 | 0.00 |
KITCHEN | 20315.25 | 24378.30 | 174.87 | 1.314 | 1.577 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.99 | 0.01049 | 30.25 | 0.01536 | 1.217 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 13409.29 | 16091.14 | 43.29 | 0.603 | 1.331 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00758 | -26.20 | 0.00036 | 1.331 | 0.00 |
KITCHEN | 3324.54 | 3989.45 | 28.62 | 0.135 | 1.217 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00660 | -26.20 | 0.00036 | 1.217 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.73 | 3.73 | 1.33 | 1.33 | 3.7271 | 3.7271 | 3.7271 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.58 | 1.58 | 1.22 | 1.22 | 1.5772 | 1.5772 | 1.5772 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 92554.000 | 64887.758 | 3.727150 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 46277.00 | 27945.88 | 2.484767 | 26.56 | 19.96 | 0.01261402 | 11.35 | 11.08 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 53.5816 | 23.98 | 0.01108519 | 56.7531 | 40696.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 154261.738 | 154261.738 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 154261.74 | 154261.74 | 3.727150 | 4.14 | 3.71 | 0.00500035 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 35.7211 | 21.00 | 0.00757833 | 46.7643 | 13408.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 39165.200 | 27457.938 | 1.577180 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19582.60 | 10980.28 | 1.051453 | 29.26 | 21.88 | 0.01425113 | 11.90 | 11.31 | 0.00850000 | 30.25 | 0.01536331 | 22.87 | 115.7447 | 25.99 | 0.01049322 | 47.7125 | 20315.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 101956.357 | 101956.357 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | 101956.36 | 101956.36 | 1.577183 | -16.01 | -16.01 | 0.00179097 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 77.1630 | 19.00 | 0.00662150 | 46.3232 | 2193.41 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 92554.000 | 64887.758 | 3.727150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.2888 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.727150 | 4.28083952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 46277.00 | 27945.88 | 1.0000 | 2.85389324 | 2.484767 | 26.56 | 19.96 | 0.01261402 | 58855.6 | 11.35 | 11.08 | 0.00850000 | 32845.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46277.00 | 31.20 | 0.01536508 | 23.13 | 1.33137743 | 53.5816 | 23.98 | 0.01108519 | 23.98 | 0.01108519 | 56.7531 | 40696.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 154261.738 | 154261.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.727150 | 4.28083952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 154261.74 | 154261.74 | 1.0000 | 4.28083952 | 3.727150 | 4.14 | 3.71 | 0.00500035 | 16702.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 154261.74 | -26.20 | 0.00036134 | -26.20 | 1.33137743 | 35.7211 | 21.00 | 0.00757833 | 21.00 | 0.00757833 | 46.7643 | 13408.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39165.200 | 27457.938 | 1.577180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.3321 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.577183 | 1.81148221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19582.60 | 10980.28 | 1.0000 | 1.20765285 | 1.051453 | 29.26 | 21.88 | 0.01425113 | 65823.1 | 11.90 | 11.31 | 0.00850000 | 33400.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19582.60 | 30.25 | 0.01536331 | 22.87 | 1.21700195 | 115.7447 | 25.95 | 0.01049322 | 25.99 | 0.01049322 | 47.7125 | 20315.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 101956.357 | 101956.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.577183 | 1.81148221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | Sensible | 101956.36 | 101956.36 | 1.0000 | 1.81148221 | 1.577183 | -16.01 | -16.01 | 0.00179097 | -11662.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101956.36 | -26.20 | 0.00036134 | -26.20 | 1.21700195 | 77.1630 | 18.42 | 0.00662150 | 19.00 | 0.00662150 | 46.3232 | 2193.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 1.33 | 3.73 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.22 | 1.58 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4148.33 | 5718.50 | 2875.17 |
KITCHEN | 5360.67 | 6262.33 | 4583.83 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5470.67 | 7066.83 | 4695.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 9.00 | 0.00 | 0.17 | 0.00 |
KITCHEN | 0.00 | 101.50 | 0.00 | 22.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 9.00 | 101.50 | 0.17 | 22.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.491 | 0.961 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 9.444 | 0.048 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 118.20 | 280.14 | 1133.39 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 3.18 | 7.53 | 425.02 | 8.620 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 36645521.39 | 0.00 | 36645521.39 | 7872349.80 | 44517871.20 | 41986318.57 | 1458.26 | 6074.89 | 1226.85 | 130.51 |
KITCHEN | 29087438.98 | 0.00 | 29087438.98 | 239388.33 | 29326827.30 | 38379373.44 | 7663.86 | 1031.16 | 64.99 | 374.72 |
Total Facility | 65732960.37 | 0.00 | 65732960.37 | 8111738.13 | 73844698.50 | 80365692.01 | 7664.63 | 6085.77 | 1269.53 | 392.23 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 1.3942 | 0.0000 | 1.3942 | 0.2985 | 1.6927 | 1.3314 | 0.00 | 5960.30 | 1226.70 |
KITCHEN | 1.0993 | 0.0000 | 1.0993 | 0.0056 | 1.1049 | 1.2170 | 6105.72 | 1017.10 | 64.18 |
Total Facility | 2.4935 | 0.0000 | 2.4935 | 0.3041 | 2.7976 | 2.5484 | 6105.72 | 5971.09 | 1268.57 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 48341718.06 | 0.00 | 48341718.06 | 41986318.57 | 1457.61 | 0.13 | 7302.26 | 130.51 |
PSZ-AC_2:2 | 38371445.55 | 0.00 | 38371445.55 | 38379373.44 | 1453.22 | 0.03 | 7306.75 | 374.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.8392 | 0.0000 | 1.8392 | 1.3314 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4501 | 0.0000 | 1.4501 | 1.2170 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1088.31 | 160.40 | 6068.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 237.17 | 1665.88 | 5658.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 2.2728 | 2.0191 | 1.7566 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.6397 | 1.5439 | 1.4236 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 381 |
Defaulted Fields | 276 |
Fields with Defaults | 902 |
Autosized Fields | 41 |
Autosizable Fields | 97 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
Electricity:Building | 511.69 | 3281.23 | 01-JAN-01:10 | 28991.58 | 02-JAN-11:10 |
Electricity:Zone:DINING | 163.76 | 856.89 | 01-JAN-01:10 | 8683.37 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 504.76 | 3144.96 | 01-JAN-01:10 | 26848.48 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.76 | 445.98 | 21-MAY-05:00 | 3050.12 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 38.49 | 311.80 | 21-MAY-05:00 | 2244.98 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.76 | 445.98 | 21-MAY-05:00 | 3050.12 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 54.76 | 445.98 | 21-MAY-05:00 | 3050.12 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 38.49 | 311.80 | 21-MAY-05:00 | 2244.98 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.76 | 445.98 | 21-MAY-05:00 | 3050.12 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 347.92 | 2424.34 | 01-JAN-01:10 | 20308.21 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.28 | 134.19 | 01-JAN-01:10 | 805.14 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 449.99 | 2636.61 | 01-JAN-01:10 | 24359.61 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.28 | 482.73 | 01-JAN-01:10 | 6999.63 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.59 | 1609.11 | 01-JAN-01:10 | 23332.11 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 324.72 | 2153.88 | 01-JAN-01:10 | 17359.97 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 292.31 | 1126.38 | 01-JAN-01:10 | 16332.47 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 49.55 | 852.60 | 02-FEB-23:30 | 3219.34 | 18-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
Electricity:Plant | 118.58 | 1024.75 | 09-DEC-02:10 | 6492.09 | 26-JUL-19:00 |
LowTempRefrigeration:Refrigeration:Electricity | 13.66 | 0.00 | 01-JAN-11:10 | 1516.17 | 30-JUN-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 28.96 | 735.96 | 03-FEB-05:40 | 1076.23 | 14-APR-12:10 |
ElectricityPurchased:Facility | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
ElectricityPurchased:Plant | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
Cogeneration:ElectricityPurchased | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
General:Cogeneration:ElectricityPurchased | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
ElectricityNet:Plant | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
Cogeneration:ElectricityNet | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
General:Cogeneration:ElectricityNet | 859.20 | 5720.45 | 09-DEC-02:00 | 73250.02 | 04-AUG-12:00 |
Electricity:HVAC | 199.72 | 0.00 | 01-JAN-01:10 | 43763.36 | 04-AUG-13:00 |
Fans:Electricity | 123.11 | 0.00 | 01-JAN-01:10 | 8637.57 | 04-AUG-13:00 |
General:Fans:Electricity | 123.11 | 0.00 | 01-JAN-01:10 | 8637.57 | 04-AUG-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 76.61 | 0.00 | 01-JAN-00:10 | 35125.79 | 04-AUG-13:00 |
General:Cooling:Electricity | 76.61 | 0.00 | 01-JAN-00:10 | 35125.79 | 04-AUG-13:00 |
ExteriorLights:Electricity | 29.22 | 0.00 | 01-JAN-08:00 | 2175.41 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 29.22 | 0.00 | 01-JAN-08:00 | 2175.41 | 01-JAN-00:10 |
WaterSystems:Electricity | 75.51 | 0.00 | 01-JAN-01:10 | 4742.20 | 19-DEC-19:50 |
Water Heater:WaterSystems:Electricity | 75.51 | 0.00 | 01-JAN-01:10 | 4742.20 | 19-DEC-19:50 |
Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 18-JAN-00:10 |
General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 18-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1760.13 | 2758.01 | 19-MAR-00:10 | 274693.08 | 02-FEB-07:10 |
NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
NaturalGas:HVAC | 894.45 | 0.00 | 01-JAN-01:10 | 228896.72 | 02-FEB-07:10 |
Heating:NaturalGas | 894.45 | 0.00 | 01-JAN-01:10 | 228896.72 | 02-FEB-07:10 |
General:Heating:NaturalGas | 894.45 | 0.00 | 01-JAN-01:10 | 228896.72 | 02-FEB-07:10 |
NaturalGas:Plant | 395.90 | 947.76 | 01-JAN-00:10 | 35945.63 | 22-FEB-07:20 |
WaterSystems:NaturalGas | 395.90 | 947.76 | 01-JAN-00:10 | 35945.63 | 22-FEB-07:20 |
Water Heater:WaterSystems:NaturalGas | 395.90 | 947.76 | 01-JAN-00:10 | 35945.63 | 22-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 23-MAR-06:30 |
MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 23-MAR-06:30 |
WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 22-MAR-18:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1995.13 | 2896.03 | 09-DEC-02:10 | 237702.92 | 02-FEB-07:10 |
EnergyTransfer:Building | 635.85 | 1448.02 | 09-DEC-02:10 | 49699.33 | 02-FEB-04:20 |
EnergyTransfer:Zone:KITCHEN | 396.19 | 1448.02 | 09-DEC-02:10 | 27637.54 | 31-OCT-04:10 |
Refrigeration:EnergyTransfer | 135.30 | 2620.90 | 02-FEB-23:10 | 7834.84 | 18-APR-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 67.65 | 1310.45 | 02-FEB-23:10 | 3917.42 | 18-APR-03:50 |
General:Refrigeration:EnergyTransfer | 67.65 | 1310.45 | 02-FEB-23:10 | 3917.42 | 18-APR-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 67.65 | 1310.45 | 02-FEB-23:10 | 3917.42 | 18-APR-03:50 |
EnergyTransfer:Plant | 351.05 | 1448.02 | 09-DEC-02:10 | 21699.96 | 23-MAR-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.00 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.65 | 1217.88 | 03-FEB-05:40 | 2238.70 | 14-APR-12:10 |
EnergyTransfer:Zone:DINING | 239.66 | 0.00 | 01-JAN-01:10 | 47870.19 | 02-FEB-04:20 |
Heating:EnergyTransfer | 36.54 | 0.00 | 01-JAN-00:10 | 28235.99 | 02-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 36.52 | 0.00 | 01-JAN-00:10 | 28235.99 | 02-FEB-21:00 |
General:Heating:EnergyTransfer | 36.54 | 0.00 | 01-JAN-00:10 | 28235.99 | 02-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 36.52 | 0.00 | 01-JAN-00:10 | 28235.99 | 02-FEB-21:00 |
Cooling:EnergyTransfer | 531.66 | 0.00 | 01-JAN-01:10 | 46445.87 | 07-SEP-17:20 |
Cooling:EnergyTransfer:Zone:DINING | 203.14 | 0.00 | 01-JAN-01:10 | 29892.88 | 04-AUG-12:00 |
General:Cooling:EnergyTransfer | 531.66 | 0.00 | 01-JAN-01:10 | 46445.87 | 07-SEP-17:20 |
General:Cooling:EnergyTransfer:Zone:DINING | 203.14 | 0.00 | 01-JAN-01:10 | 29892.88 | 04-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.03 | 0.00 | 01-JAN-00:10 | 2387.85 | 03-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.03 | 0.00 | 01-JAN-00:10 | 2387.85 | 03-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 328.52 | 0.00 | 01-JAN-01:10 | 23829.97 | 31-OCT-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 328.52 | 0.00 | 01-JAN-01:10 | 23829.97 | 31-OCT-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
PlantLoopHeatingDemand:Plant | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
WaterSystems:PlantLoopHeatingDemand | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
General:WaterSystems:PlantLoopHeatingDemand | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
EnergyTransfer:HVAC | 1008.23 | 0.00 | 01-JAN-01:10 | 183117.37 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 715.56 | 0.00 | 01-JAN-01:10 | 183117.37 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 292.67 | 0.00 | 01-JAN-00:10 | 139008.69 | 04-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
WaterUse:WaterSystems:EnergyTransfer | 283.40 | 0.00 | 01-JAN-01:10 | 19651.84 | 21-FEB-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 36.517 | -203.140 | 0.000 | 0.000 | 230.796 | 38.488 | 93.957 | 43.399 | 0.000 | 2.506 | 0.000 | 0.000 | -28.844 | 0.000 | -143.127 | -70.553 |
KITCHEN | 0.000 | 0.000 | 0.025 | -328.507 | 0.000 | 0.000 | 6.120 | 16.277 | 287.132 | 0.000 | 0.000 | 0.017 | 24.151 | 0.000 | 0.000 | 0.000 | -5.215 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.547 | 27.536 | 0.000 | 0.000 | 0.000 | -33.083 | -0.001 |
Total Facility | 0.000 | 0.000 | 36.543 | -531.647 | 0.000 | 0.000 | 236.916 | 54.764 | 381.090 | 43.399 | 0.000 | 8.070 | 51.688 | 0.000 | -28.844 | 0.000 | -181.425 | -70.554 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-FEB-00:01 | 0.00 | 0.00 | 0.00 | -75003.41 | 0.00 | 0.00 | 1157.79 | 374.16 | 543.07 | 0.00 | 0.00 | 0.00 | 79633.59 | 0.00 | -4496.63 | 0.00 | -2208.57 | 0.00 |
KITCHEN | 31-JAN-05:01 | 0.00 | 0.00 | 0.00 | -59106.94 | 0.00 | 0.00 | 29.35 | 178.91 | 6916.85 | 0.00 | 0.00 | 0.00 | 52210.25 | 0.00 | -0.00 | 0.00 | -228.42 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-FEB-00:01 | 0.00 | 0.00 | 0.00 | -77490.93 | 0.00 | 0.00 | 1191.79 | 508.34 | 3042.91 | 0.00 | 0.00 | 527.63 | 78104.97 | 0.00 | -4296.80 | 0.00 | -1587.92 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 21-JAN-05:01 | 0.00 | 0.00 | 103125.62 | 0.00 | 0.00 | 0.00 | 0.00 | 374.16 | 2172.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2683.36 | 0.00 | -314.35 | -102674.36 |
KITCHEN | 03-FEB-05:02 | 0.00 | 0.00 | 21466.70 | 0.00 | 0.00 | 0.00 | 29.70 | 178.91 | 6916.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -128.13 | -28464.03 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-JAN-05:01 | -39804.41 | 39804.41 | 103125.62 | -39804.41 | 0.00 | 0.00 | 0.00 | 508.34 | 9089.15 | 0.00 | 0.00 | 307.17 | 0.00 | 0.00 | -2683.36 | 0.00 | -514.53 | -70027.97 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7271 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7271 | 0.3572 | 1.0000 | Not calculated | 1.3314 | 0.3572 | ||
PSZ-AC_2:2 | 1.5772 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5772 | 0.1158 | 1.0000 | Not calculated | 0.1826 | 0.1158 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.7271 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.7271 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3572 | ||
PSZ-AC_2:2 | 1.5772 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.5772 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1158 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7271 | 3.7271 | 3.7271 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5772 | 1.5772 | 1.5772 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7271 | 3.7271 | 3.7271 | 3.7271 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5772 | 1.5772 | 1.5772 | 1.5772 | 0.1826 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.7271 | 3.7271 | 3.7271 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5772 | 1.5772 | 1.5772 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.7271 | 3.7271 | 3.7271 | 3.7271 | 1.3314 | 1.0000 |
PSZ-AC_2:2 | 1.5772 | 1.5772 | 1.5772 | 1.5772 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 511.15 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 371.75 | 371.75 | 0.00 | 137.83 |
KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
Totals | 511.15 | 511.15 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 22.33 |
Number of hours not met | 22.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 894.45 | 228896.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 76.61 | 35125.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.76 | 3050.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 29.22 | 2175.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 417.59 | 23332.11 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 123.11 | 8637.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 75.51 | 4742.20 | 395.90 | 35945.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.66 | 1516.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.96 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 499.54 | 859.20 |
Natural Gas | 469.79 | 1760.13 |
Additional | 0.00 | 0.00 |
Total | 969.33 | 2619.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 107.14 |
Space Heating | 0.00 |
Space Cooling | 149.87 |
Fans (All) | 240.86 |
Service Water Heating | 147.73 |
Receptacle Equipment | 880.35 |
Miscellaneous (All) | 1680.91 |
Subtotal | 1680.91 |
Natural Gas [MJ/m2] | |
Space Heating | 1749.86 |
Service Water Heating | 774.51 |
Miscellaneous (All) | 3443.45 |
Subtotal | 3443.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.09 |
Space Heating | 34.15 |
Space Cooling | 2.92 |
Fans (All) | 4.70 |
Service Water Heating | 18.00 |
Receptacle Equipment | 35.11 |
Miscellaneous | 3.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4905. | 8760. |
LTG_SCH_KITCHEN | 4001. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
REST_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_HALF_ON_SCH | 5292. | 8760. |
INFIL_SCH_PNNL | 3559. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2744. | 6935. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8071.17 | 669.00 | 19.83 | 0.00 | 0.00 |
ATTIC | 7434.67 | 430.83 | 398.67 | 403.33 | 92.50 |
Min | 7434.67 | 22.67 | 0.00 | 0.00 | 0.00 |
Max | 8737.33 | 669.00 | 398.67 | 403.33 | 92.50 |
Average | 8081.06 | 374.17 | 139.50 | 134.44 | 30.83 |
Sum | 24243.17 | 1122.50 | 418.50 | 403.33 | 92.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 824205.67 | 16.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 19134.50 | 98.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 824205.67 | 98.50 | 0.00 | 0.00 | 0.00 |
Average | 281113.39 | 38.28 | 0.00 | 0.00 | 0.00 |
Sum | 843340.17 | 114.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7856.33 | 903.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6132.83 | 2625.83 | 1.33 | 0.00 | 0.00 |
ATTIC | 7323.50 | 775.67 | 244.33 | 203.17 | 213.33 |
Min | 6132.83 | 775.67 | 0.00 | 0.00 | 0.00 |
Max | 7856.33 | 2625.83 | 244.33 | 203.17 | 213.33 |
Average | 7104.22 | 1435.06 | 81.89 | 67.72 | 71.11 |
Sum | 21312.67 | 4305.17 | 245.67 | 203.17 | 213.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 750453.67 | 73768.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13411.50 | 5821.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 750453.67 | 73768.33 | 0.00 | 0.00 | 0.00 |
Average | 254621.72 | 26529.94 | 0.00 | 0.00 | 0.00 |
Sum | 763865.17 | 79589.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 824222.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 824222.00 | 0.00 | 0.00 |
Average | 0.00 | 274740.67 | 0.00 | 0.00 |
Sum | 0.00 | 824222.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223763E+10 | 69459.29 | 31-JAN-00:01 | -29.1 | -29.3 | 0.119945E+11 | 10742.59 | 14-JAN-19:19 | -29.1 | -29.3 |
February | 0.392765E+10 | 75005.20 | 02-FEB-00:01 | -33.0 | -33.1 | 0.108610E+11 | 10742.52 | 18-FEB-19:30 | -6.1 | -6.8 |
March | 0.833051E+10 | 51121.61 | 06-MAR-00:01 | -16.3 | -16.8 | 0.122748E+11 | 13216.38 | 25-MAR-18:19 | 14.63 | 10.09 |
April | 0.145419E+11 | 39355.88 | 03-APR-04:02 | -6.8 | -7.6 | 0.123587E+11 | 14052.73 | 15-APR-18:10 | 27.85 | 18.48 |
May | 0.228402E+11 | 26085.94 | 07-MAY-04:01 | 3.30 | 2.56 | 0.141588E+11 | 14052.02 | 06-MAY-18:19 | 3.30 | 2.56 |
June | 0.287360E+11 | 29004.69 | 26-JUN-17:03 | 30.92 | 21.61 | 0.144527E+11 | 14052.94 | 17-JUN-18:00 | 30.92 | 21.61 |
July | 0.319242E+11 | 32643.45 | 26-JUL-05:02 | 22.20 | 19.51 | 0.152469E+11 | 14052.91 | 15-JUL-18:00 | 22.20 | 19.51 |
August | 0.318679E+11 | 31738.28 | 03-AUG-05:02 | 23.30 | 22.56 | 0.153668E+11 | 14053.01 | 05-AUG-18:00 | 22.20 | 16.81 |
September | 0.272563E+11 | 29421.37 | 07-SEP-17:02 | 30.40 | 19.50 | 0.137743E+11 | 14052.96 | 02-SEP-18:10 | 30.40 | 19.50 |
October | 0.189388E+11 | 30095.29 | 23-OCT-04:01 | -1.9 | -2.9 | 0.125450E+11 | 13524.84 | 21-OCT-18:00 | -1.9 | -2.9 |
November | 0.966290E+10 | 62821.76 | 26-NOV-00:01 | -24.4 | -24.8 | 0.117446E+11 | 12681.15 | 03-NOV-11:00 | -24.4 | -24.8 |
December | 0.287816E+10 | 60277.41 | 09-DEC-00:01 | -22.8 | -23.0 | 0.119893E+11 | 10742.54 | 23-DEC-19:19 | -6.5 | -6.7 |
Annual Sum or Average | 0.203142E+12 | 0.156768E+12 | ||||||||
Minimum of Months | 0.223763E+10 | 26085.94 | -33.0 | -33.1 | 0.108610E+11 | 10742.52 | -29.1 | -29.3 | ||
Maximum of Months | 0.319242E+11 | 75005.20 | 30.92 | 22.56 | 0.153668E+11 | 14053.01 | 30.92 | 21.61 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235894E+11 | 58912.91 | 31-JAN-05:01 | -30.6 | -30.8 | 0.103965E+11 | 6819.65 | 05-JAN-11:00 | -30.6 | -30.8 |
February | 0.222285E+11 | 57865.82 | 03-FEB-05:01 | -33.9 | -34.0 | 0.939109E+10 | 6831.66 | 24-FEB-11:00 | 6.10 | 3.16 |
March | 0.261924E+11 | 42834.76 | 08-MAR-05:01 | -14.7 | -15.0 | 0.104183E+11 | 6881.42 | 28-MAR-10:00 | 12.80 | 7.63 |
April | 0.262588E+11 | 34333.88 | 01-APR-04:01 | -5.8 | -6.3 | 0.101225E+11 | 6934.92 | 17-APR-10:00 | 15.60 | 11.49 |
May | 0.280278E+11 | 33404.47 | 30-MAY-03:11 | 14.40 | 14.20 | 0.105594E+11 | 6935.00 | 26-MAY-10:00 | 14.40 | 14.20 |
June | 0.290409E+11 | 49479.51 | 20-JUN-03:21 | 13.60 | 12.14 | 0.102484E+11 | 6939.75 | 30-JUN-10:00 | 28.30 | 23.10 |
July | 0.307803E+11 | 41590.42 | 21-JUL-03:11 | 15.60 | 14.88 | 0.106015E+11 | 6940.29 | 03-JUL-10:00 | 15.60 | 14.88 |
August | 0.309831E+11 | 47685.51 | 11-AUG-03:21 | 13.85 | 12.88 | 0.106059E+11 | 6979.38 | 04-AUG-10:00 | 13.85 | 12.88 |
September | 0.295974E+11 | 43343.56 | 07-SEP-04:01 | 15.00 | 13.27 | 0.102177E+11 | 6934.98 | 12-SEP-10:00 | 16.10 | 15.06 |
October | 0.295827E+11 | 32873.84 | 31-OCT-04:01 | 0.00 | -0.9 | 0.104625E+11 | 6934.92 | 20-OCT-10:00 | 0.00 | -0.9 |
November | 0.267942E+11 | 50978.64 | 28-NOV-05:01 | -21.1 | -21.4 | 0.100892E+11 | 6931.11 | 08-NOV-11:50 | -21.1 | -21.4 |
December | 0.254427E+11 | 48972.88 | 11-DEC-05:01 | -22.2 | -22.6 | 0.103964E+11 | 6819.66 | 11-DEC-11:39 | -19.6 | -20.4 |
Annual Sum or Average | 0.328518E+12 | 0.123509E+12 | ||||||||
Minimum of Months | 0.222285E+11 | 32873.84 | -33.9 | -34.0 | 0.939109E+10 | 6819.65 | -30.6 | -30.8 | ||
Maximum of Months | 0.309831E+11 | 58912.91 | 15.60 | 14.88 | 0.106059E+11 | 6979.38 | 28.30 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -12.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 | -2.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 | 5.15 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 | 10.69 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 | 15.94 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 | 1.39 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 | -0.5 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143479E+11 | 103129.20 | 21-JAN-05:01 | -13.3 |
February | 0.836693E+10 | 85267.67 | 28-FEB-05:01 | -16.7 |
March | 0.232584E+10 | 86643.39 | 01-MAR-05:01 | -4.4 |
April | 0.613357E+09 | 88228.84 | 03-APR-04:01 | -6.8 |
May | 27543815.85 | 10189.45 | 02-MAY-05:03 | 2.20 |
June | 8268059.48 | 7219.75 | 03-JUN-05:03 | 5.78 |
July | 1715498.51 | 2724.17 | 25-JUL-23:03 | 25.00 |
August | 1209768.17 | 1807.80 | 02-AUG-23:03 | 24.40 |
September | 21372461.82 | 11050.68 | 30-SEP-05:03 | 0.10 |
October | 97090578.90 | 31774.92 | 15-OCT-06:00 | 4.40 |
November | 0.303283E+10 | 92718.33 | 27-NOV-05:01 | -9.4 |
December | 0.767284E+10 | 94130.44 | 12-DEC-05:01 | -20.0 |
Annual Sum or Average | 0.365169E+11 | |||
Minimum of Months | 1209768.17 | 1807.80 | -20.0 | |
Maximum of Months | 0.143479E+11 | 103129.20 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7105654.63 | 17650.19 | 07-JAN-05:02 | -25.7 |
February | 6764190.15 | 21490.69 | 03-FEB-05:02 | -33.9 |
March | 2457224.91 | 9930.85 | 13-MAR-04:03 | -9.4 |
April | 553636.74 | 4946.68 | 03-APR-04:03 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 2608979.08 | 16007.87 | 26-NOV-05:02 | -25.2 |
December | 5848277.76 | 16471.17 | 10-DEC-05:02 | -22.3 |
Annual Sum or Average | 25337963.26 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 7105654.63 | 21490.69 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.339445E+10 | 2244.98 | 02-JAN-16:30 | 0.106399E+11 | 6999.63 | 01-JAN-11:09 |
February | 0.302077E+10 | 2244.98 | 01-FEB-17:19 | 0.961025E+10 | 6999.63 | 01-FEB-11:09 |
March | 0.330161E+10 | 2244.98 | 01-MAR-17:19 | 0.106399E+11 | 6999.63 | 01-MAR-11:09 |
April | 0.310532E+10 | 2244.98 | 01-APR-17:30 | 0.102967E+11 | 6999.63 | 01-APR-10:09 |
May | 0.316088E+10 | 2244.98 | 01-MAY-18:30 | 0.106399E+11 | 6999.63 | 01-MAY-10:09 |
June | 0.306132E+10 | 2244.98 | 01-JUN-18:30 | 0.102967E+11 | 6999.63 | 01-JUN-10:09 |
July | 0.311756E+10 | 2244.98 | 01-JUL-19:30 | 0.106399E+11 | 6999.63 | 01-JUL-10:09 |
August | 0.320588E+10 | 2244.98 | 01-AUG-19:30 | 0.106399E+11 | 6999.63 | 01-AUG-10:09 |
September | 0.312979E+10 | 2244.98 | 01-SEP-18:40 | 0.102967E+11 | 6999.63 | 01-SEP-10:09 |
October | 0.328236E+10 | 2244.98 | 02-OCT-17:40 | 0.106399E+11 | 6999.63 | 01-OCT-10:09 |
November | 0.327408E+10 | 2244.98 | 01-NOV-16:30 | 0.102967E+11 | 6999.63 | 01-NOV-10:09 |
December | 0.343366E+10 | 2244.98 | 01-DEC-16:30 | 0.106399E+11 | 6999.63 | 01-DEC-11:09 |
Annual Sum or Average | 0.384877E+11 | 0.125277E+12 | ||||
Minimum of Months | 0.302077E+10 | 2244.98 | 0.961025E+10 | 6999.63 | ||
Maximum of Months | 0.343366E+10 | 2244.98 | 0.106399E+11 | 6999.63 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137533E+10 | 805.14 | 02-JAN-10:09 | 0.275785E+11 | 17359.97 | 01-JAN-11:09 |
February | 0.124570E+10 | 805.14 | 01-FEB-10:09 | 0.249097E+11 | 17359.97 | 01-FEB-11:09 |
March | 0.139723E+10 | 805.14 | 01-MAR-10:09 | 0.275785E+11 | 17359.97 | 01-MAR-11:09 |
April | 0.133636E+10 | 805.14 | 01-APR-16:10 | 0.266889E+11 | 17359.97 | 01-APR-10:09 |
May | 0.138628E+10 | 805.14 | 01-MAY-09:09 | 0.275785E+11 | 17359.97 | 01-MAY-10:09 |
June | 0.135053E+10 | 805.14 | 01-JUN-09:09 | 0.266889E+11 | 17359.97 | 01-JUN-10:09 |
July | 0.137227E+10 | 805.14 | 01-JUL-16:10 | 0.275785E+11 | 17359.97 | 01-JUL-10:09 |
August | 0.139723E+10 | 805.14 | 01-AUG-09:09 | 0.275785E+11 | 17359.97 | 01-AUG-10:09 |
September | 0.133668E+10 | 805.14 | 01-SEP-09:09 | 0.266889E+11 | 17359.97 | 01-SEP-10:09 |
October | 0.137517E+10 | 805.14 | 02-OCT-09:09 | 0.275785E+11 | 17359.97 | 01-OCT-10:09 |
November | 0.133137E+10 | 805.14 | 01-NOV-09:09 | 0.266889E+11 | 17359.97 | 01-NOV-10:09 |
December | 0.137243E+10 | 805.14 | 01-DEC-10:09 | 0.275785E+11 | 17359.97 | 01-DEC-11:09 |
Annual Sum or Average | 0.162766E+11 | 0.324715E+12 | ||||
Minimum of Months | 0.124570E+10 | 805.14 | 0.249097E+11 | 17359.97 | ||
Maximum of Months | 0.139723E+10 | 805.14 | 0.275785E+11 | 17359.97 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.300980E+11 | 0.339445E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280278E+11 |
February | 0.272721E+11 | 0.302077E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212341E+11 |
March | 0.305458E+11 | 0.330161E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161967E+11 |
April | 0.292871E+11 | 0.310532E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109012E+09 | 0.105439E+11 |
May | 0.303219E+11 | 0.316088E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110942E+09 | 0.563148E+10 |
June | 0.295292E+11 | 0.306132E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745836E+09 | 0.284011E+10 |
July | 0.300798E+11 | 0.311756E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559081E+09 | 0.173909E+10 |
August | 0.305458E+11 | 0.320588E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577235E+09 | 0.226898E+10 |
September | 0.292871E+11 | 0.312979E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403851E+09 | 0.498113E+10 |
October | 0.300980E+11 | 0.328236E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101869E+11 |
November | 0.290996E+11 | 0.327408E+10 | 0.102967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161581E+11 |
December | 0.300798E+11 | 0.343366E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233185E+11 |
Annual Sum or Average | 0.356244E+12 | 0.384877E+11 | 0.125277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250596E+10 | 0.143127E+12 |
Minimum of Months | 0.272721E+11 | 0.302077E+10 | 0.961025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173909E+10 |
Maximum of Months | 0.305458E+11 | 0.343366E+10 | 0.106399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745836E+09 | 0.280278E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.808786E+09 | 0.137533E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886404E+09 |
February | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680186E+09 |
March | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597537E+09 |
April | 0.786997E+09 | 0.133636E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1636310.31 | 0.386808E+09 |
May | 0.814802E+09 | 0.138628E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 594576.77 | 0.248109E+09 |
June | 0.793501E+09 | 0.135053E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 6807155.79 | 0.161937E+09 |
July | 0.808298E+09 | 0.137227E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2172302.05 | 0.123848E+09 |
August | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 2894312.74 | 0.163467E+09 |
September | 0.786997E+09 | 0.133668E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 2611278.54 | 0.223471E+09 |
October | 0.808786E+09 | 0.137517E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365204E+09 |
November | 0.781956E+09 | 0.133137E+10 | 0.218838E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599631E+09 |
December | 0.808298E+09 | 0.137243E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778759E+09 |
Annual Sum or Average | 0.957291E+10 | 0.162766E+11 | 0.266253E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 16715936.21 | 0.521536E+10 |
Minimum of Months | 0.732850E+09 | 0.124570E+10 | 0.204249E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123848E+09 |
Maximum of Months | 0.820818E+09 | 0.139723E+10 | 0.226132E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 6807155.79 | 0.886404E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408674E+09 | 0.160177E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426381E+09 | 0.175880E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407306E+09 | 0.237460E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371026E+09 | 0.328070E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372545E+09 | 0.410845E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417295E+09 | 0.441185E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568547E+09 | 0.478535E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420710E+09 | 0.385895E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631806E+09 | 0.273518E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601087E+09 | 0.193908E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471909E+09 | 0.125612E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449685E+09 | 0.972423E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554697E+10 | 0.330833E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371026E+09 | 0.972423E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631806E+09 | 0.478535E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 30255.31 | 07-JAN-19:10 | 2244.98 | 02-JAN-16:30 | 6999.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 35156.08 | 30-JAN-21:00 |
February | 30255.31 | 04-FEB-19:10 | 2244.98 | 01-FEB-17:19 | 6999.63 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 39545.40 | 02-FEB-21:00 |
March | 30255.31 | 04-MAR-19:10 | 2244.98 | 01-MAR-17:19 | 6999.63 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 22034.30 | 05-MAR-21:00 |
April | 30255.31 | 01-APR-18:10 | 2244.98 | 01-APR-17:30 | 6999.63 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2984.81 | 15-APR-17:03 | 16716.86 | 03-APR-20:00 |
May | 30255.31 | 06-MAY-18:10 | 2244.98 | 01-MAY-18:30 | 6999.63 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3112.91 | 31-MAY-12:00 | 11007.54 | 01-MAY-19:55 |
June | 30255.31 | 03-JUN-18:10 | 2244.98 | 01-JUN-18:30 | 6999.63 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4013.77 | 26-JUN-17:03 | 8396.52 | 01-JUN-17:52 |
July | 30255.31 | 01-JUL-18:10 | 2244.98 | 01-JUL-19:30 | 6999.63 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3118.44 | 26-JUL-17:53 | 5111.42 | 10-JUL-12:00 |
August | 30255.31 | 05-AUG-18:10 | 2244.98 | 01-AUG-19:30 | 6999.63 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4074.84 | 04-AUG-11:53 | 5740.70 | 06-AUG-19:53 |
September | 30255.31 | 02-SEP-18:10 | 2244.98 | 01-SEP-18:40 | 6999.63 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3915.82 | 07-SEP-13:00 | 11274.60 | 29-SEP-19:55 |
October | 30255.31 | 07-OCT-18:10 | 2244.98 | 02-OCT-17:40 | 6999.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 14022.22 | 31-OCT-20:00 |
November | 30255.31 | 04-NOV-18:10 | 2244.98 | 01-NOV-16:30 | 6999.63 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 33444.56 | 25-NOV-20:00 |
December | 30255.31 | 02-DEC-19:10 | 2244.98 | 01-DEC-16:30 | 6999.63 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 31924.94 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5111.42 | |||||
Maximum of Months | 30255.31 | 2244.98 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4074.84 | 39545.40 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 813.01 | 07-JAN-19:10 | 805.14 | 02-JAN-10:09 | 14093.48 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2457.02 | 19-JAN-00:10 |
February | 813.01 | 04-FEB-19:10 | 805.14 | 01-FEB-10:09 | 14093.48 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1609.57 | 28-FEB-05:00 |
March | 813.01 | 04-MAR-19:10 | 805.14 | 01-MAR-10:09 | 14093.48 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1515.91 | 21-MAR-03:10 |
April | 813.01 | 01-APR-18:10 | 805.14 | 01-APR-16:10 | 14093.48 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 50.45 | 15-APR-15:00 | 1188.97 | 03-APR-00:10 |
May | 813.01 | 06-MAY-18:10 | 805.14 | 01-MAY-09:09 | 14093.48 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 22.65 | 31-MAY-12:55 | 859.48 | 02-MAY-03:10 |
June | 813.01 | 03-JUN-18:10 | 805.14 | 01-JUN-09:09 | 14093.48 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 66.17 | 18-JUN-16:00 | 602.12 | 02-JUN-03:40 |
July | 813.01 | 01-JUL-18:10 | 805.14 | 01-JUL-16:10 | 14093.48 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.78 | 25-JUL-15:55 | 438.83 | 25-JUL-03:10 |
August | 813.01 | 05-AUG-18:10 | 805.14 | 01-AUG-09:09 | 14093.48 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 28.69 | 03-AUG-16:00 | 476.99 | 19-AUG-03:40 |
September | 813.01 | 02-SEP-18:10 | 805.14 | 01-SEP-09:09 | 14093.48 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 35.15 | 06-SEP-14:00 | 544.29 | 27-SEP-04:00 |
October | 813.01 | 07-OCT-18:10 | 805.14 | 02-OCT-09:09 | 14093.48 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 960.06 | 24-OCT-04:00 |
November | 813.01 | 04-NOV-18:10 | 805.14 | 01-NOV-09:09 | 14093.48 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1758.25 | 21-NOV-01:10 |
December | 813.01 | 02-DEC-19:10 | 805.14 | 01-DEC-10:09 | 14093.48 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 3051.03 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 438.83 | ||||||
Maximum of Months | 813.01 | 805.14 | 14093.48 | 7874.59 | 0.00 | 0.00 | 0.00 | 66.17 | 3051.03 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.19 | 25-JAN-04:55 | 5199.88 | 30-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1143.44 | 21-FEB-05:50 | 4975.80 | 03-FEB-14:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1280.64 | 22-MAR-01:00 | 5288.06 | 13-MAR-11:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.65 | 05-APR-23:10 | 8515.13 | 26-APR-13:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.92 | 03-MAY-02:00 | 8419.61 | 21-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.44 | 08-JUN-00:30 | 8203.65 | 09-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.39 | 23-JUL-23:00 | 8057.16 | 05-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.52 | 05-AUG-05:00 | 6768.51 | 16-AUG-13:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.99 | 08-SEP-04:00 | 6638.64 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.14 | 31-OCT-07:05 | 5507.52 | 23-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.72 | 28-NOV-06:03 | 4361.82 | 12-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.91 | 04-DEC-07:55 | 3446.05 | 07-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 927.91 | 3446.05 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.99 | 8515.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 69459.29 | 31-JAN-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.51 |
February | 75005.20 | 02-FEB-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2208.57 |
March | 51121.61 | 06-MAR-00:01 | 16808.50 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.71 |
April | 39355.88 | 03-APR-04:02 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.26 |
May | 26085.94 | 07-MAY-04:01 | 0.00 | 3741.59 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.19 |
June | 29004.69 | 26-JUN-17:03 | 80680.82 | 5051.20 | 17378.40 | 0.00 | 0.00 | 0.00 | 0.00 | 4013.77 | 0.00 |
July | 32643.45 | 26-JUL-05:02 | 16808.50 | 4988.87 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.07 |
August | 31738.28 | 03-AUG-05:02 | 16808.50 | 4988.87 | 15688.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.69 |
September | 29421.37 | 07-SEP-17:02 | 134468.03 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3676.11 | 0.00 |
October | 30095.29 | 23-OCT-04:01 | 16808.50 | 4988.87 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 |
November | 62821.76 | 26-NOV-00:01 | 16808.50 | 4988.87 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.52 |
December | 60277.41 | 09-DEC-00:01 | 16808.50 | 4988.87 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3995.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26085.94 | 0.00 | 3741.59 | 7241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75005.20 | 134468.03 | 8418.67 | 28963.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4013.77 | 3995.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 58912.91 | 31-JAN-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 228.42 |
February | 57865.82 | 03-FEB-05:01 | 406.51 | 1610.23 | 57907.01 | 29326.04 | 0.00 | 0.00 | 0.00 | 0.00 | 128.82 |
March | 42834.76 | 08-MAR-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 |
April | 34333.88 | 01-APR-04:01 | 0.00 | 1341.86 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.55 |
May | 33404.47 | 30-MAY-03:11 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 206.17 |
June | 49479.51 | 20-JUN-03:21 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 229.98 |
July | 41590.42 | 21-JUL-03:11 | 0.00 | 1207.67 | 29522.30 | 12219.19 | 0.00 | 0.00 | 0.00 | 0.00 | 173.08 |
August | 47685.51 | 11-AUG-03:21 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 273.98 |
September | 43343.56 | 07-SEP-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.87 |
October | 32873.84 | 31-OCT-04:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 70.88 |
November | 50978.64 | 28-NOV-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.98 |
December | 48972.88 | 11-DEC-05:01 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 187.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 32873.84 | 0.00 | 1073.49 | 26242.04 | 10861.50 | 0.00 | 0.00 | 0.00 | 0.00 | 28.87 | |
Maximum of Months | 58912.91 | 451.67 | 1789.14 | 64341.12 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 273.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.94 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.79 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910.22 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.04 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.31 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.26 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.79 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.72 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.68 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.07 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.07 | 154.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.691834E+11 | 40059.80 | 19-JAN-11:20 | 0.315634E+12 | 243237.74 | 31-JAN-07:10 |
February | 0.614682E+11 | 40488.37 | 02-FEB-11:20 | 0.236581E+12 | 274693.08 | 02-FEB-07:10 |
March | 0.665994E+11 | 38705.29 | 01-MAR-11:20 | 0.180940E+12 | 164115.79 | 05-MAR-21:40 |
April | 0.656628E+11 | 55967.12 | 18-APR-10:00 | 0.123985E+12 | 135020.73 | 03-APR-06:19 |
May | 0.695951E+11 | 55312.44 | 31-MAY-10:00 | 0.802438E+11 | 87496.41 | 02-MAY-06:19 |
June | 0.800488E+11 | 63285.25 | 30-JUN-11:09 | 0.712099E+11 | 57029.29 | 03-JUN-05:10 |
July | 0.880791E+11 | 69012.52 | 26-JUL-17:00 | 0.700676E+11 | 46550.49 | 03-JUL-18:49 |
August | 0.864419E+11 | 73250.02 | 04-AUG-11:00 | 0.697535E+11 | 44511.47 | 03-AUG-18:19 |
September | 0.725154E+11 | 57641.19 | 11-SEP-10:00 | 0.745969E+11 | 87395.37 | 29-SEP-06:40 |
October | 0.660719E+11 | 40186.13 | 20-OCT-11:00 | 0.104237E+12 | 102625.35 | 23-OCT-06:19 |
November | 0.650464E+11 | 39282.37 | 26-NOV-11:09 | 0.173840E+12 | 218202.56 | 26-NOV-07:10 |
December | 0.684912E+11 | 39861.04 | 09-DEC-11:20 | 0.259042E+12 | 211285.49 | 12-DEC-04:19 |
Annual Sum or Average | 0.859204E+12 | 0.176013E+13 | ||||
Minimum of Months | 0.614682E+11 | 38705.29 | 0.697535E+11 | 44511.47 | ||
Maximum of Months | 0.880791E+11 | 73250.02 | 0.315634E+12 | 274693.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.476978E+10 | 0.318113E+10 | 0.382185E+11 | 0.00 | 0.127650E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639959E+10 | 0.00 |
February | 0.426648E+10 | 0.262069E+10 | 0.345199E+11 | 0.00 | 0.107699E+11 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579150E+10 | 0.00 |
March | 0.469884E+10 | 0.255200E+10 | 0.382185E+11 | 0.00 | 0.106887E+11 | 37879553.69 | 0.00 | 5153562.62 | 0.00 | 0.00 | 0.00 | 0.646617E+10 | 0.00 |
April | 0.444168E+10 | 0.211153E+10 | 0.369856E+11 | 0.00 | 0.962552E+10 | 36657632.61 | 0.00 | 0.228711E+10 | 0.00 | 0.00 | 0.00 | 0.620637E+10 | 0.00 |
May | 0.454716E+10 | 0.189045E+10 | 0.382185E+11 | 0.00 | 0.924595E+10 | 37879553.69 | 0.00 | 0.477761E+10 | 0.00 | 0.00 | 0.00 | 0.641994E+10 | 0.00 |
June | 0.441186E+10 | 0.169337E+10 | 0.369856E+11 | 0.00 | 0.935715E+10 | 36657632.61 | 0.00 | 0.168688E+11 | 0.00 | 0.00 | 0.00 | 0.623788E+10 | 0.00 |
July | 0.448983E+10 | 0.179930E+10 | 0.382185E+11 | 0.00 | 0.982407E+10 | 37879553.69 | 0.00 | 0.226672E+11 | 0.00 | 0.00 | 0.00 | 0.637157E+10 | 0.00 |
August | 0.460311E+10 | 0.204426E+10 | 0.382185E+11 | 0.00 | 0.978705E+10 | 37879553.69 | 0.00 | 0.206380E+11 | 0.00 | 0.00 | 0.00 | 0.645005E+10 | 0.00 |
September | 0.446647E+10 | 0.230993E+10 | 0.369856E+11 | 0.00 | 0.909344E+10 | 36657632.61 | 0.00 | 0.909936E+10 | 0.00 | 0.00 | 0.00 | 0.619867E+10 | 0.00 |
October | 0.465753E+10 | 0.275692E+10 | 0.382185E+11 | 0.00 | 0.962391E+10 | 37879553.69 | 0.00 | 0.261571E+09 | 0.00 | 0.00 | 0.00 | 0.639143E+10 | 0.00 |
November | 0.460545E+10 | 0.298735E+10 | 0.369856E+11 | 0.00 | 0.103968E+11 | 36657632.61 | 0.00 | 920491.21 | 0.00 | 0.00 | 0.00 | 0.619021E+10 | 0.00 |
December | 0.480609E+10 | 0.326858E+10 | 0.382185E+11 | 0.00 | 0.119374E+11 | 37879553.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639130E+10 | 0.00 |
Annual Sum or Average | 0.547643E+11 | 0.292155E+11 | 0.449992E+12 | 0.00 | 0.123115E+12 | 0.446001E+09 | 0.00 | 0.766057E+11 | 0.00 | 0.00 | 0.00 | 0.755147E+11 | 0.00 |
Minimum of Months | 0.426648E+10 | 0.169337E+10 | 0.345199E+11 | 0.00 | 0.909344E+10 | 34213790.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579150E+10 | 0.00 |
Maximum of Months | 0.480609E+10 | 0.326858E+10 | 0.382185E+11 | 0.00 | 0.127650E+11 | 37879553.69 | 0.00 | 0.226672E+11 | 0.00 | 0.00 | 0.00 | 0.646617E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.398997E+11 | 0.00 | 0.238844E+12 | 0.00 | 0.368903E+11 | 0.00 | 0.00 |
February | 0.360384E+11 | 0.00 | 0.166548E+12 | 0.00 | 0.339943E+11 | 0.00 | 0.00 |
March | 0.398997E+11 | 0.00 | 0.103470E+12 | 0.00 | 0.375700E+11 | 0.00 | 0.00 |
April | 0.386126E+11 | 0.00 | 0.505655E+11 | 0.00 | 0.348071E+11 | 0.00 | 0.00 |
May | 0.398997E+11 | 0.00 | 0.632570E+10 | 0.00 | 0.340184E+11 | 0.00 | 0.00 |
June | 0.386126E+11 | 0.00 | 0.156007E+10 | 0.00 | 0.310372E+11 | 0.00 | 0.00 |
July | 0.398997E+11 | 0.00 | 27473272.73 | 0.00 | 0.301404E+11 | 0.00 | 0.00 |
August | 0.398997E+11 | 0.00 | 0.105542E+09 | 0.00 | 0.297482E+11 | 0.00 | 0.00 |
September | 0.386126E+11 | 0.00 | 0.700128E+10 | 0.00 | 0.289830E+11 | 0.00 | 0.00 |
October | 0.398997E+11 | 0.00 | 0.330637E+11 | 0.00 | 0.312737E+11 | 0.00 | 0.00 |
November | 0.386126E+11 | 0.00 | 0.103045E+12 | 0.00 | 0.321828E+11 | 0.00 | 0.00 |
December | 0.398997E+11 | 0.00 | 0.183892E+12 | 0.00 | 0.352502E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.469787E+12 | 0.00 | 0.894448E+12 | 0.00 | 0.395896E+12 | 0.00 | 0.00 |
Minimum of Months | 0.360384E+11 | 0.00 | 27473272.73 | 0.00 | 0.289830E+11 | 0.00 | 0.00 |
Maximum of Months | 0.398997E+11 | 0.00 | 0.238844E+12 | 0.00 | 0.375700E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 3050.12 | 02-JAN-16:30 | 2175.41 | 01-JAN-00:10 | 24359.61 | 01-JAN-11:09 | 0.00 | 7062.98 | 31-JAN-07:10 | 17.86 | 18-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3050.12 | 01-FEB-17:19 | 2175.41 | 01-FEB-00:10 | 24359.61 | 01-FEB-11:09 | 0.00 | 7506.19 | 02-FEB-07:10 | 17.86 | 01-FEB-00:20 | 0.00 | 01-FEB-00:10 |
March | 3050.12 | 01-MAR-17:19 | 2175.41 | 01-MAR-00:10 | 24359.61 | 01-MAR-11:09 | 0.00 | 5991.34 | 05-MAR-23:30 | 17.86 | 18-MAR-23:10 | 0.00 | 01-MAR-00:10 |
April | 3050.12 | 01-APR-17:30 | 2175.41 | 01-APR-05:10 | 24359.61 | 01-APR-10:09 | 0.00 | 5555.71 | 03-APR-05:10 | 17.86 | 12-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 3050.12 | 01-MAY-18:30 | 2175.41 | 01-MAY-19:10 | 24359.61 | 01-MAY-10:09 | 0.00 | 4917.29 | 03-MAY-05:10 | 17.86 | 02-MAY-23:10 | 0.00 | 01-MAY-00:10 |
June | 3050.12 | 01-JUN-18:30 | 2175.41 | 01-JUN-19:40 | 24359.61 | 01-JUN-10:09 | 0.00 | 6425.44 | 30-JUN-11:09 | 17.86 | 09-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 3050.12 | 01-JUL-19:30 | 2175.41 | 01-JUL-19:00 | 24359.61 | 01-JUL-10:09 | 0.00 | 8018.96 | 26-JUL-17:00 | 17.86 | 04-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 3050.12 | 01-AUG-19:30 | 2175.41 | 01-AUG-19:40 | 24359.61 | 01-AUG-10:09 | 0.00 | 8637.57 | 04-AUG-12:00 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 3050.12 | 01-SEP-18:40 | 2175.41 | 01-SEP-05:10 | 24359.61 | 01-SEP-10:09 | 0.00 | 5339.03 | 11-SEP-11:00 | 17.86 | 12-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 3050.12 | 02-OCT-17:40 | 2175.41 | 01-OCT-05:10 | 24359.61 | 01-OCT-10:09 | 0.00 | 5119.35 | 23-OCT-05:10 | 17.86 | 06-OCT-23:10 | 0.00 | 01-OCT-00:10 |
November | 3050.12 | 01-NOV-16:30 | 2175.41 | 01-NOV-05:10 | 24359.61 | 01-NOV-10:09 | 0.00 | 6925.75 | 26-NOV-07:10 | 17.86 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 3050.12 | 01-DEC-16:30 | 2175.41 | 01-DEC-00:10 | 24359.61 | 01-DEC-11:09 | 0.00 | 6613.68 | 09-DEC-07:10 | 17.86 | 01-DEC-00:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 4917.29 | 17.86 | 0.00 | ||||||
Maximum of Months | 3050.12 | 2175.41 | 24359.61 | 0.00 | 8637.57 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 4741.70 | 24-JAN-07:49 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 4741.87 | 24-FEB-07:49 | 0.00 |
March | 840.01 | 19-MAR-16:19 | 0.00 | 0.00 | 0.00 | 4742.09 | 10-MAR-19:49 | 0.00 |
April | 20113.68 | 18-APR-11:00 | 0.00 | 0.00 | 0.00 | 4741.88 | 24-APR-18:30 | 0.00 |
May | 20215.25 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 4741.70 | 03-MAY-06:49 | 0.00 |
June | 26759.59 | 11-JUN-15:09 | 0.00 | 0.00 | 0.00 | 4740.16 | 02-JUN-06:00 | 0.00 |
July | 32087.37 | 26-JUL-17:00 | 0.00 | 0.00 | 0.00 | 4738.33 | 12-JUL-06:19 | 0.00 |
August | 35125.79 | 04-AUG-12:00 | 0.00 | 0.00 | 0.00 | 4739.33 | 16-AUG-06:19 | 0.00 |
September | 22187.03 | 11-SEP-11:00 | 0.00 | 0.00 | 0.00 | 4741.13 | 29-SEP-18:00 | 0.00 |
October | 6888.82 | 20-OCT-12:00 | 0.00 | 0.00 | 0.00 | 4742.12 | 18-OCT-18:30 | 0.00 |
November | 517.21 | 07-NOV-04:19 | 0.00 | 0.00 | 0.00 | 4741.66 | 27-NOV-19:49 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 4742.20 | 19-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4738.33 | 0.00 | ||
Maximum of Months | 35125.79 | 0.00 | 0.00 | 0.00 | 4742.20 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 40059.80 | 19-JAN-11:20 | 2488.87 | 24359.61 | 0.00 | 0.00 | 6562.77 | 17.86 | 0.00 | 0.00 | 0.00 |
February | 40488.37 | 02-FEB-11:20 | 2488.87 | 24359.61 | 0.00 | 0.00 | 6985.80 | 17.86 | 0.00 | 0.00 | 0.00 |
March | 38705.29 | 01-MAR-11:20 | 2488.87 | 24359.61 | 0.00 | 0.00 | 5190.47 | 17.86 | 0.00 | 0.00 | 0.00 |
April | 55967.12 | 18-APR-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4595.76 | 17.86 | 0.00 | 18283.77 | 0.00 |
May | 55312.44 | 31-MAY-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4529.15 | 17.86 | 0.00 | 17958.34 | 0.00 |
June | 63285.25 | 30-JUN-11:09 | 2488.87 | 22750.50 | 0.00 | 0.00 | 6425.44 | 17.86 | 0.00 | 26459.89 | 0.00 |
July | 69012.52 | 26-JUL-17:00 | 2488.87 | 20336.83 | 0.00 | 0.00 | 8018.96 | 17.86 | 0.00 | 32087.37 | 0.00 |
August | 73250.02 | 04-AUG-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 8583.91 | 17.86 | 0.00 | 34667.73 | 0.00 |
September | 57641.19 | 11-SEP-10:00 | 2488.87 | 24359.61 | 0.00 | 0.00 | 4749.32 | 17.86 | 0.00 | 20059.45 | 0.00 |
October | 40186.13 | 20-OCT-11:00 | 2488.87 | 22750.50 | 0.00 | 0.00 | 4046.48 | 17.86 | 0.00 | 6224.03 | 0.00 |
November | 39282.37 | 26-NOV-11:09 | 1935.78 | 24359.61 | 0.00 | 0.00 | 5966.71 | 17.86 | 0.00 | 0.00 | 0.00 |
December | 39861.04 | 09-DEC-11:20 | 2212.31 | 24359.61 | 0.00 | 0.00 | 6313.66 | 17.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 38705.29 | 1935.78 | 20336.83 | 0.00 | 0.00 | 4046.48 | 17.86 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73250.02 | 2488.87 | 24359.61 | 0.00 | 0.00 | 8583.91 | 17.86 | 0.00 | 34667.73 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26248.62 | 01-JAN-11:09 | 0.00 | 199509.43 | 31-JAN-07:10 | 0.00 | 35689.61 | 31-JAN-19:00 | 0.00 |
February | 26248.62 | 01-FEB-11:09 | 0.00 | 228896.72 | 02-FEB-07:10 | 0.00 | 35945.63 | 22-FEB-07:19 | 0.00 |
March | 26248.62 | 01-MAR-11:09 | 0.00 | 130950.54 | 05-MAR-23:30 | 0.00 | 35888.15 | 01-MAR-19:19 | 0.00 |
April | 26248.62 | 01-APR-10:09 | 0.00 | 98541.17 | 03-APR-05:10 | 0.00 | 34737.48 | 04-APR-06:30 | 0.00 |
May | 26248.62 | 01-MAY-10:09 | 0.00 | 54022.07 | 03-MAY-05:10 | 0.00 | 32857.12 | 01-MAY-06:30 | 0.00 |
June | 26248.62 | 01-JUN-10:09 | 0.00 | 30246.15 | 03-JUN-05:10 | 0.00 | 29914.16 | 01-JUN-06:49 | 0.00 |
July | 26248.62 | 01-JUL-10:09 | 0.00 | 6036.38 | 23-JUL-05:10 | 0.00 | 26706.75 | 03-JUL-06:19 | 0.00 |
August | 26248.62 | 01-AUG-10:09 | 0.00 | 12519.21 | 07-AUG-05:10 | 0.00 | 24633.78 | 07-AUG-06:30 | 0.00 |
September | 26248.62 | 01-SEP-10:09 | 0.00 | 59632.40 | 30-SEP-05:10 | 0.00 | 26073.07 | 29-SEP-06:40 | 0.00 |
October | 26248.62 | 01-OCT-10:09 | 0.00 | 67817.81 | 23-OCT-05:10 | 0.00 | 28956.70 | 31-OCT-18:30 | 0.00 |
November | 26248.62 | 01-NOV-10:09 | 0.00 | 189578.88 | 26-NOV-07:10 | 0.00 | 31888.37 | 30-NOV-07:40 | 0.00 |
December | 26248.62 | 01-DEC-11:09 | 0.00 | 192827.17 | 09-DEC-04:10 | 0.00 | 34180.68 | 29-DEC-19:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26248.62 | 0.00 | 6036.38 | 0.00 | 24633.78 | 0.00 | |||
Maximum of Months | 26248.62 | 0.00 | 228896.72 | 0.00 | 35945.63 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
February | 1.00 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
March | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
April | 0.17 | 20.15 | 0.17 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
December | 4.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
Annual Sum or Average | 9.00 | 16.49 | 0.17 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 20.15 | 0.17 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 30.03 | 0.00 | 30.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 30.36 | 0.00 | 30.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 30.88 | 0.00 | 30.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 30.02 | 8.17 | 29.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 29.51 | 14.17 | 28.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 30.86 | 0.00 | 30.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 29.80 | 0.00 | 29.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 29.67 | 0.00 | 29.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 101.50 | 30.08 | 22.33 | 29.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 30.88 | 14.17 | 30.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.70 | 550.50 | 20.68 | 550.50 | 20.68 |
February | 551.00 | 20.70 | 369.50 | 20.64 | 369.50 | 20.62 |
March | 610.00 | 20.82 | 258.83 | 20.69 | 258.83 | 20.61 |
April | 526.83 | 21.04 | 193.67 | 21.15 | 140.83 | 21.04 |
May | 410.67 | 21.83 | 232.17 | 22.47 | 87.17 | 22.53 |
June | 320.50 | 22.81 | 422.83 | 23.48 | 163.83 | 23.57 |
July | 334.33 | 23.85 | 568.83 | 23.94 | 308.67 | 23.96 |
August | 322.00 | 23.58 | 532.00 | 23.82 | 260.67 | 23.86 |
September | 280.67 | 21.43 | 295.83 | 22.62 | 29.83 | 22.58 |
October | 555.00 | 20.94 | 75.67 | 20.86 | 56.83 | 20.71 |
November | 588.50 | 20.84 | 208.83 | 20.71 | 208.83 | 20.64 |
December | 609.00 | 20.70 | 439.67 | 20.65 | 439.67 | 20.63 |
Annual Sum or Average | 5718.50 | 21.36 | 4148.33 | 21.73 | 2875.17 | 21.68 |
Minimum of Months | 280.67 | 20.70 | 75.67 | 20.64 | 29.83 | 20.61 |
Maximum of Months | 610.00 | 23.85 | 568.83 | 23.94 | 550.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.96 | 552.00 | 18.96 | 552.00 | 18.96 |
February | 551.00 | 18.97 | 414.83 | 18.96 | 414.83 | 18.96 |
March | 576.17 | 19.25 | 373.33 | 19.30 | 345.50 | 19.21 |
April | 496.83 | 20.32 | 313.83 | 20.88 | 239.83 | 20.89 |
May | 411.33 | 23.95 | 458.17 | 24.55 | 279.00 | 24.80 |
June | 471.83 | 25.50 | 542.33 | 25.54 | 430.33 | 25.67 |
July | 570.00 | 25.99 | 606.17 | 25.93 | 570.00 | 25.95 |
August | 535.67 | 25.96 | 603.83 | 25.85 | 531.83 | 25.90 |
September | 442.50 | 24.30 | 438.83 | 24.80 | 325.50 | 25.05 |
October | 486.33 | 20.32 | 218.00 | 20.98 | 126.67 | 21.00 |
November | 501.67 | 19.24 | 329.67 | 19.56 | 258.67 | 19.42 |
December | 609.00 | 18.96 | 509.67 | 18.96 | 509.67 | 18.96 |
Annual Sum or Average | 6262.33 | 21.66 | 5360.67 | 22.10 | 4583.83 | 22.17 |
Minimum of Months | 411.33 | 18.96 | 218.00 | 18.96 | 126.67 | 18.96 |
Maximum of Months | 610.00 | 25.99 | 606.17 | 25.93 | 570.00 | 25.95 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.69921 | 15.80082 | -0.7191 | 16.81011 |
February | 551.00000 | 20.70214 | 20.43192 | -0.6504 | 14.98343 |
March | 612.00000 | 20.83213 | 26.95284 | -0.5295 | 12.39141 |
April | 590.00000 | 21.35296 | 35.55852 | -0.2991 | 10.42432 |
May | 611.00000 | 22.50650 | 50.10142 | -0.8786 | 25.60895 |
June | 592.00000 | 23.32960 | 56.86461 | -0.4747 | 13.89089 |
July | 609.00000 | 23.87366 | 61.21616 | -0.2254 | 6.92702 |
August | 612.00000 | 23.72859 | 59.59586 | -0.2848 | 8.24519 |
September | 590.00000 | 22.72978 | 44.90716 | -0.7507 | 22.60176 |
October | 610.00000 | 21.19590 | 35.38477 | -0.2822 | 8.59270 |
November | 591.00000 | 20.85626 | 29.06032 | -0.4842 | 11.49181 |
December | 609.00000 | 20.70125 | 18.66599 | -0.6619 | 15.15377 |
Annual Sum or Average | 7187.00000 | 21.88363 | 37.98837 | -0.5192 | 13.91066 |
Minimum of Months | 551.00000 | 20.69921 | 15.80082 | -0.8786 | 6.92702 |
Maximum of Months | 612.00000 | 23.87366 | 61.21616 | -0.2254 | 25.60895 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.96030 | 22.69979 | -0.7980 | 18.83416 |
February | 551.00000 | 18.96826 | 28.09820 | -0.7441 | 17.20457 |
March | 612.00000 | 19.55094 | 34.34015 | -0.5328 | 14.10607 |
April | 590.00000 | 20.91659 | 41.36685 | -0.1389 | 14.97067 |
May | 611.00000 | 24.01249 | 49.33905 | -0.0962 | 17.25995 |
June | 592.00000 | 25.17846 | 53.96324 | 0.40118 | 15.25328 |
July | 609.00000 | 25.85593 | 56.14410 | 0.67707 | 16.06888 |
August | 612.00000 | 25.70308 | 54.68235 | 0.61899 | 15.60916 |
September | 590.00000 | 24.15990 | 45.62195 | 0.01157 | 18.60741 |
October | 610.00000 | 21.03046 | 40.74688 | -0.0618 | 11.34079 |
November | 591.00000 | 19.90253 | 35.03006 | -0.4071 | 13.56725 |
December | 609.00000 | 18.96459 | 25.78196 | -0.7368 | 16.77707 |
Annual Sum or Average | 7187.00000 | 21.95239 | 40.72323 | -0.1468 | 15.78968 |
Minimum of Months | 551.00000 | 18.96030 | 22.69979 | -0.7980 | 11.34079 |
Maximum of Months | 612.00000 | 25.85593 | 56.14410 | 0.67707 | 18.83416 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.497787E+10 | 0.141504E+10 | 63.67 | 0.325162E+10 | 0.172625E+10 | 0.00 | 1.00 | 18-APR-11:05 | 0.00 | 01-APR-00:01 | 53092.48 | 18-APR-12:00 | 33097.36 | 15-APR-17:10 | 21050.26 | 18-APR-11:50 | 13581.97 | 18-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.901052E+10 | 0.266061E+10 | 149.72 | 0.588841E+10 | 0.312211E+10 | 0.00 | 1.00 | 31-MAY-11:05 | 0.00 | 01-MAY-00:01 | 52449.78 | 31-MAY-12:00 | 37325.96 | 31-MAY-12:00 | 18685.01 | 30-MAY-18:00 | 13723.98 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.375526E+11 | 0.103814E+11 | 355.97 | 0.230417E+11 | 0.145109E+11 | 0.00 | 1.00 | 09-JUN-11:40 | 0.00 | 01-JUN-00:01 | 68631.02 | 26-JUN-18:00 | 43600.97 | 26-JUN-17:10 | 34544.19 | 13-JUN-12:00 | 17715.45 | 26-JUN-18:00 | 0.00 | 01-JUN-00:01 |
July | 0.505420E+11 | 0.138548E+11 | 462.89 | 0.283962E+11 | 0.221458E+11 | 0.00 | 1.00 | 01-JUL-18:03 | 0.00 | 01-JUL-00:01 | 89892.42 | 26-JUL-18:00 | 41567.39 | 03-JUL-17:23 | 51724.99 | 26-JUL-19:00 | 22510.50 | 26-JUL-18:00 | 0.00 | 01-JUL-00:01 |
August | 0.454930E+11 | 0.125758E+11 | 433.10 | 0.260493E+11 | 0.194437E+11 | 0.00 | 1.00 | 01-AUG-11:05 | 0.00 | 01-AUG-00:01 | 101450.19 | 03-AUG-05:02 | 47086.07 | 04-AUG-11:53 | 65202.15 | 03-AUG-05:02 | 25253.99 | 04-AUG-13:00 | 0.00 | 01-AUG-00:01 |
September | 0.195328E+11 | 0.566909E+10 | 245.99 | 0.144404E+11 | 0.509240E+10 | 0.00 | 1.00 | 06-SEP-11:02 | 0.00 | 01-SEP-00:01 | 57963.95 | 11-SEP-12:00 | 43521.17 | 07-SEP-13:00 | 22310.21 | 11-SEP-12:00 | 14957.26 | 06-SEP-13:00 | 0.00 | 01-SEP-00:01 |
October | 0.338668E+09 | 0.110763E+09 | 15.22 | 0.284322E+09 | 54346027.77 | 0.00 | 0.40 | 20-OCT-13:00 | 0.00 | 01-OCT-00:01 | 15355.87 | 20-OCT-13:00 | 13414.27 | 20-OCT-13:00 | 1941.61 | 20-OCT-13:00 | 4854.88 | 20-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.167447E+12 | 0.466675E+11 | 1726.56 | 0.101352E+12 | 0.660955E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.505420E+11 | 0.138548E+11 | 462.89 | 0.283962E+11 | 0.221458E+11 | 0.00 | 1.00 | 0.00 | 101450.19 | 47086.07 | 65202.15 | 25253.99 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 17088833.48 | 5153562.62 | 3.17 | 11276670.78 | 5812162.71 | 0.00 | 0.18 | 19-MAR-16:13 | 0.00 | 01-MAR-00:01 | 2821.04 | 19-MAR-16:13 | 1850.22 | 19-MAR-16:13 | 970.82 | 19-MAR-16:13 | 841.38 | 19-MAR-16:13 | 0.00 | 01-MAR-00:01 |
April | 0.360351E+10 | 0.872073E+09 | 70.87 | 0.237341E+10 | 0.123010E+10 | 0.00 | 1.00 | 15-APR-10:32 | 0.00 | 01-APR-00:01 | 38638.33 | 16-APR-03:42 | 22706.29 | 18-APR-03:42 | 18104.50 | 16-APR-03:42 | 9263.50 | 16-APR-03:42 | 0.00 | 01-APR-00:01 |
May | 0.834760E+10 | 0.211700E+10 | 234.67 | 0.524572E+10 | 0.310187E+10 | 0.00 | 1.00 | 05-MAY-03:42 | 0.00 | 01-MAY-00:01 | 30087.60 | 31-MAY-10:57 | 22420.94 | 31-MAY-10:57 | 15859.46 | 30-MAY-03:11 | 6945.38 | 31-MAY-10:57 | 0.00 | 01-MAY-00:01 |
June | 0.273059E+11 | 0.648737E+10 | 402.57 | 0.164795E+11 | 0.108264E+11 | 0.00 | 1.00 | 09-JUN-03:41 | 0.00 | 01-JUN-00:01 | 42929.72 | 30-JUN-10:53 | 26973.37 | 11-JUN-16:00 | 25441.09 | 26-JUN-03:32 | 10099.72 | 11-JUN-14:53 | 0.00 | 01-JUN-00:01 |
July | 0.374931E+11 | 0.881236E+10 | 529.29 | 0.201465E+11 | 0.173466E+11 | 0.00 | 1.00 | 01-JUL-03:02 | 0.00 | 01-JUL-00:01 | 42929.72 | 03-JUL-12:35 | 23695.86 | 02-JUL-10:57 | 28799.05 | 26-JUL-18:53 | 9664.50 | 03-JUL-14:55 | 0.00 | 01-JUL-00:01 |
August | 0.341247E+11 | 0.806221E+10 | 490.28 | 0.186253E+11 | 0.154994E+11 | 0.00 | 1.00 | 01-AUG-03:11 | 0.00 | 01-AUG-00:01 | 42929.72 | 03-AUG-11:35 | 26014.39 | 04-AUG-15:00 | 30201.42 | 04-AUG-05:03 | 10190.54 | 04-AUG-15:00 | 0.00 | 01-AUG-00:01 |
September | 0.138040E+11 | 0.343027E+10 | 286.71 | 0.102918E+11 | 0.351221E+10 | 0.00 | 1.00 | 01-SEP-03:31 | 0.00 | 01-SEP-00:01 | 39084.50 | 11-SEP-03:02 | 25496.45 | 06-SEP-15:10 | 20201.73 | 12-SEP-03:31 | 9293.67 | 11-SEP-03:02 | 0.00 | 01-SEP-00:01 |
October | 0.526508E+09 | 0.150808E+09 | 39.19 | 0.399136E+09 | 0.127372E+09 | 0.00 | 0.57 | 21-OCT-15:00 | 0.00 | 01-OCT-00:01 | 9785.41 | 21-OCT-15:00 | 8304.90 | 20-OCT-14:55 | 2630.43 | 21-OCT-15:10 | 2646.61 | 21-OCT-15:00 | 0.00 | 01-OCT-00:01 |
November | 3076214.89 | 920491.21 | 0.59 | 1657371.58 | 1418843.31 | 0.00 | 0.45 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 | 7512.52 | 09-NOV-05:01 | 4018.26 | 09-NOV-05:01 | 3494.26 | 09-NOV-05:01 | 2095.59 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.125225E+12 | 0.299382E+11 | 2057.35 | 0.735744E+11 | 0.516511E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.374931E+11 | 0.881236E+10 | 529.29 | 0.201465E+11 | 0.173466E+11 | 0.00 | 1.00 | 0.00 | 42929.72 | 26973.37 | 30201.42 | 10190.54 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 177.99 | 72.94 | 105.05 | 75.89 | 631.98 | 0.00 | 0.00 | 0.00 |
February | 237.00 | 104.31 | 132.69 | 135.70 | 499.96 | 0.00 | 0.00 | 0.00 |
March | 321.88 | 127.71 | 194.17 | 252.52 | 319.57 | 0.00 | 0.00 | 0.00 |
April | 392.86 | 171.22 | 221.64 | 390.00 | 220.92 | 0.00 | 0.00 | 0.00 |
May | 496.39 | 217.11 | 279.28 | 577.76 | 127.60 | 0.00 | 0.00 | 0.00 |
June | 545.52 | 237.64 | 307.87 | 693.93 | 91.88 | 0.00 | 0.00 | 0.00 |
July | 551.51 | 254.58 | 296.92 | 712.38 | 83.32 | 0.00 | 0.00 | 0.00 |
August | 464.96 | 200.38 | 264.58 | 599.31 | 98.27 | 0.00 | 0.00 | 0.00 |
September | 416.56 | 197.57 | 218.99 | 499.31 | 160.87 | 0.00 | 0.00 | 0.00 |
October | 263.79 | 109.80 | 153.99 | 239.45 | 244.08 | 0.00 | 0.00 | 0.00 |
November | 156.04 | 50.64 | 105.39 | 83.21 | 390.57 | 0.00 | 0.00 | 0.00 |
December | 120.42 | 51.56 | 68.86 | 51.85 | 573.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.95 | 149.83 | 196.11 | 360.49 | 285.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.42 | 50.64 | 68.86 | 51.85 | 83.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.51 | 254.58 | 307.87 | 712.38 | 631.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 719.44 | 492.92 | 226.52 | 642.89 | 786.72 | 0.00 | 0.00 | 0.00 |
February | 775.56 | 526.18 | 249.38 | 725.45 | 626.73 | 0.00 | 0.00 | 0.00 |
March | 664.34 | 347.77 | 316.58 | 656.43 | 440.82 | 0.00 | 0.00 | 0.00 |
April | 592.27 | 271.44 | 320.84 | 655.99 | 318.48 | 0.00 | 0.00 | 0.00 |
May | 505.13 | 141.30 | 363.82 | 601.15 | 190.46 | 0.00 | 0.00 | 0.00 |
June | 482.20 | 96.30 | 385.91 | 628.52 | 134.41 | 0.00 | 0.00 | 0.00 |
July | 511.72 | 127.98 | 383.74 | 691.17 | 121.06 | 0.00 | 0.00 | 0.00 |
August | 567.06 | 196.37 | 370.68 | 774.41 | 143.35 | 0.00 | 0.00 | 0.00 |
September | 684.65 | 353.29 | 331.36 | 877.58 | 228.36 | 0.00 | 0.00 | 0.00 |
October | 737.81 | 465.16 | 272.65 | 835.93 | 333.88 | 0.00 | 0.00 | 0.00 |
November | 552.22 | 345.74 | 206.48 | 527.74 | 505.74 | 0.00 | 0.00 | 0.00 |
December | 588.00 | 445.31 | 142.69 | 563.36 | 731.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.12 | 316.32 | 297.80 | 681.46 | 379.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.20 | 96.30 | 142.69 | 527.74 | 121.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.56 | 526.18 | 385.91 | 877.58 | 786.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 177.84 | 72.32 | 105.52 | 80.32 | 639.31 | 0.00 | 0.00 | 0.00 |
February | 259.56 | 127.79 | 131.77 | 169.91 | 505.06 | 0.00 | 0.00 | 0.00 |
March | 309.76 | 115.21 | 194.55 | 241.31 | 326.66 | 0.00 | 0.00 | 0.00 |
April | 452.99 | 224.17 | 228.82 | 476.04 | 224.09 | 0.00 | 0.00 | 0.00 |
May | 453.90 | 181.73 | 272.17 | 524.65 | 133.43 | 0.00 | 0.00 | 0.00 |
June | 531.00 | 229.60 | 301.39 | 675.82 | 95.46 | 0.00 | 0.00 | 0.00 |
July | 570.33 | 270.58 | 299.75 | 743.88 | 86.54 | 0.00 | 0.00 | 0.00 |
August | 497.97 | 227.87 | 270.10 | 649.16 | 102.40 | 0.00 | 0.00 | 0.00 |
September | 404.07 | 191.47 | 212.60 | 483.93 | 163.26 | 0.00 | 0.00 | 0.00 |
October | 283.25 | 126.54 | 156.71 | 271.43 | 249.84 | 0.00 | 0.00 | 0.00 |
November | 169.00 | 62.75 | 106.25 | 105.79 | 397.08 | 0.00 | 0.00 | 0.00 |
December | 130.08 | 61.56 | 68.53 | 70.69 | 579.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.69 | 157.66 | 196.02 | 375.42 | 290.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.08 | 61.56 | 68.53 | 70.69 | 86.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 570.33 | 270.58 | 301.39 | 743.88 | 639.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476716E+09 | 0.195360E+09 | 0.281355E+09 | 0.203259E+09 | 0.169270E+10 |
February | 0.573345E+09 | 0.252349E+09 | 0.320996E+09 | 0.328291E+09 | 0.120951E+10 |
March | 0.862134E+09 | 0.342057E+09 | 0.520077E+09 | 0.676355E+09 | 0.855932E+09 |
April | 0.101830E+10 | 0.443811E+09 | 0.574486E+09 | 0.101088E+10 | 0.572632E+09 |
May | 0.132953E+10 | 0.581500E+09 | 0.748031E+09 | 0.154747E+10 | 0.341755E+09 |
June | 0.141398E+10 | 0.615974E+09 | 0.798002E+09 | 0.179867E+10 | 0.238163E+09 |
July | 0.147716E+10 | 0.681876E+09 | 0.795283E+09 | 0.190804E+10 | 0.223158E+09 |
August | 0.124535E+10 | 0.536701E+09 | 0.708653E+09 | 0.160519E+10 | 0.263206E+09 |
September | 0.107973E+10 | 0.512095E+09 | 0.567635E+09 | 0.129422E+10 | 0.416982E+09 |
October | 0.706543E+09 | 0.294088E+09 | 0.412455E+09 | 0.641350E+09 | 0.653739E+09 |
November | 0.404445E+09 | 0.131263E+09 | 0.273182E+09 | 0.215674E+09 | 0.101235E+10 |
December | 0.322525E+09 | 0.138092E+09 | 0.184433E+09 | 0.138874E+09 | 0.153486E+10 |
Annual Sum or Average | 0.109098E+11 | 0.472517E+10 | 0.618459E+10 | 0.113683E+11 | 0.901498E+10 |
Minimum of Months | 0.322525E+09 | 0.131263E+09 | 0.184433E+09 | 0.138874E+09 | 0.223158E+09 |
Maximum of Months | 0.147716E+10 | 0.681876E+09 | 0.798002E+09 | 0.190804E+10 | 0.169270E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192695E+10 | 0.132024E+10 | 0.606711E+09 | 0.172190E+10 | 0.210716E+10 |
February | 0.187623E+10 | 0.127293E+10 | 0.603304E+09 | 0.175502E+10 | 0.151618E+10 |
March | 0.177938E+10 | 0.931462E+09 | 0.847920E+09 | 0.175818E+10 | 0.118069E+10 |
April | 0.153517E+10 | 0.703560E+09 | 0.831612E+09 | 0.170033E+10 | 0.825498E+09 |
May | 0.135293E+10 | 0.378466E+09 | 0.974466E+09 | 0.161013E+10 | 0.510118E+09 |
June | 0.124987E+10 | 0.249603E+09 | 0.100027E+10 | 0.162913E+10 | 0.348378E+09 |
July | 0.137059E+10 | 0.342779E+09 | 0.102781E+10 | 0.185122E+10 | 0.324254E+09 |
August | 0.151881E+10 | 0.525966E+09 | 0.992841E+09 | 0.207418E+10 | 0.383953E+09 |
September | 0.177461E+10 | 0.915724E+09 | 0.858891E+09 | 0.227469E+10 | 0.591921E+09 |
October | 0.197616E+10 | 0.124589E+10 | 0.730275E+09 | 0.223896E+10 | 0.894275E+09 |
November | 0.143136E+10 | 0.896162E+09 | 0.535200E+09 | 0.136789E+10 | 0.131089E+10 |
December | 0.157491E+10 | 0.119273E+10 | 0.382184E+09 | 0.150890E+10 | 0.195892E+10 |
Annual Sum or Average | 0.193670E+11 | 0.997550E+10 | 0.939148E+10 | 0.214905E+11 | 0.119522E+11 |
Minimum of Months | 0.124987E+10 | 0.249603E+09 | 0.382184E+09 | 0.136789E+10 | 0.324254E+09 |
Maximum of Months | 0.197616E+10 | 0.132024E+10 | 0.102781E+10 | 0.227469E+10 | 0.210716E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476332E+09 | 0.193698E+09 | 0.282634E+09 | 0.215119E+09 | 0.171232E+10 |
February | 0.627930E+09 | 0.309147E+09 | 0.318783E+09 | 0.411056E+09 | 0.122185E+10 |
March | 0.829666E+09 | 0.308579E+09 | 0.521088E+09 | 0.646332E+09 | 0.874923E+09 |
April | 0.117415E+10 | 0.581039E+09 | 0.593112E+09 | 0.123389E+10 | 0.580846E+09 |
May | 0.121573E+10 | 0.486759E+09 | 0.728975E+09 | 0.140523E+10 | 0.357368E+09 |
June | 0.137634E+10 | 0.595130E+09 | 0.781214E+09 | 0.175174E+10 | 0.247434E+09 |
July | 0.152757E+10 | 0.724721E+09 | 0.802853E+09 | 0.199240E+10 | 0.231779E+09 |
August | 0.133375E+10 | 0.610315E+09 | 0.723437E+09 | 0.173872E+10 | 0.274272E+09 |
September | 0.104734E+10 | 0.496284E+09 | 0.551054E+09 | 0.125436E+10 | 0.423182E+09 |
October | 0.758646E+09 | 0.338924E+09 | 0.419722E+09 | 0.726991E+09 | 0.669164E+09 |
November | 0.438038E+09 | 0.162646E+09 | 0.275392E+09 | 0.274218E+09 | 0.102922E+10 |
December | 0.348414E+09 | 0.164872E+09 | 0.183542E+09 | 0.189331E+09 | 0.155326E+10 |
Annual Sum or Average | 0.111539E+11 | 0.497211E+10 | 0.618181E+10 | 0.118394E+11 | 0.917563E+10 |
Minimum of Months | 0.348414E+09 | 0.162646E+09 | 0.183542E+09 | 0.189331E+09 | 0.231779E+09 |
Maximum of Months | 0.152757E+10 | 0.724721E+09 | 0.802853E+09 | 0.199240E+10 | 0.171232E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 684.56 | 1943.48 | 1075.27 | 638.18 | 437.09 | 0.00 | 0.00 |
February | 928.55 | 1529.23 | 1272.12 | 758.28 | 513.84 | 0.00 | 0.00 |
March | 1107.91 | 1044.69 | 1295.99 | 590.69 | 705.30 | 0.00 | 0.00 |
April | 1492.28 | 733.74 | 1438.13 | 666.82 | 771.30 | 0.00 | 0.00 |
May | 1682.79 | 430.71 | 1455.42 | 540.15 | 915.28 | 0.00 | 0.00 |
June | 1986.48 | 309.95 | 1558.71 | 563.54 | 995.17 | 0.00 | 0.00 |
July | 2138.95 | 282.44 | 1633.56 | 653.14 | 980.42 | 0.00 | 0.00 |
August | 2011.90 | 333.04 | 1529.99 | 624.62 | 905.37 | 0.00 | 0.00 |
September | 1845.38 | 537.06 | 1505.28 | 742.32 | 762.96 | 0.00 | 0.00 |
October | 1325.37 | 806.35 | 1284.85 | 701.50 | 583.35 | 0.00 | 0.00 |
November | 672.19 | 1248.84 | 877.25 | 459.13 | 418.12 | 0.00 | 0.00 |
December | 610.37 | 1808.82 | 838.50 | 558.43 | 280.08 | 0.00 | 0.00 |
Annual Sum or Average | 1376.18 | 914.64 | 1313.76 | 623.82 | 689.94 | 0.00 | 0.00 |
Minimum of Months | 610.37 | 282.44 | 838.50 | 459.13 | 280.08 | 0.00 | 0.00 |
Maximum of Months | 2138.95 | 1943.48 | 1633.56 | 758.28 | 995.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.183354E+10 | 0.520543E+10 | 0.288000E+10 | 0.170930E+10 | 0.117070E+10 | 0.00 | 0.00 |
February | 0.224634E+10 | 0.369952E+10 | 0.307751E+10 | 0.183442E+10 | 0.124308E+10 | 0.00 | 0.00 |
March | 0.296742E+10 | 0.279810E+10 | 0.347118E+10 | 0.158210E+10 | 0.188908E+10 | 0.00 | 0.00 |
April | 0.386799E+10 | 0.190186E+10 | 0.372762E+10 | 0.172841E+10 | 0.199921E+10 | 0.00 | 0.00 |
May | 0.450720E+10 | 0.115361E+10 | 0.389820E+10 | 0.144673E+10 | 0.245147E+10 | 0.00 | 0.00 |
June | 0.514895E+10 | 0.803394E+09 | 0.404019E+10 | 0.146071E+10 | 0.257948E+10 | 0.00 | 0.00 |
July | 0.572896E+10 | 0.756497E+09 | 0.437533E+10 | 0.174938E+10 | 0.262595E+10 | 0.00 | 0.00 |
August | 0.538866E+10 | 0.892006E+09 | 0.409791E+10 | 0.167298E+10 | 0.242493E+10 | 0.00 | 0.00 |
September | 0.478324E+10 | 0.139206E+10 | 0.390168E+10 | 0.192410E+10 | 0.197758E+10 | 0.00 | 0.00 |
October | 0.354986E+10 | 0.215974E+10 | 0.344135E+10 | 0.187890E+10 | 0.156245E+10 | 0.00 | 0.00 |
November | 0.174232E+10 | 0.323700E+10 | 0.227384E+10 | 0.119007E+10 | 0.108377E+10 | 0.00 | 0.00 |
December | 0.163481E+10 | 0.484475E+10 | 0.224585E+10 | 0.149569E+10 | 0.750160E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.433993E+11 | 0.288439E+11 | 0.414307E+11 | 0.196728E+11 | 0.217579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163481E+10 | 0.756497E+09 | 0.224585E+10 | 0.119007E+10 | 0.750160E+09 | 0.00 | 0.00 |
Maximum of Months | 0.572896E+10 | 0.520543E+10 | 0.437533E+10 | 0.192410E+10 | 0.262595E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.639950E+10 | -0.622518E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174322938.9 | 81.22 | 0.00 | 0.00 |
February | 0.579154E+10 | -0.563428E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157255768.6 | 81.22 | 0.00 | 0.00 |
March | 0.646604E+10 | -0.629387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172177641.6 | 81.22 | 0.00 | 0.00 |
April | 0.620626E+10 | -0.604347E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162787606.4 | 81.22 | 0.00 | 0.00 |
May | 0.641973E+10 | -0.626019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159539502.4 | 81.22 | 0.00 | 0.00 |
June | 0.623771E+10 | -0.608660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -151108541.4 | 81.21 | 0.00 | 0.00 |
July | 0.637143E+10 | -0.621711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154324184.2 | 81.21 | 0.00 | 0.00 |
August | 0.644991E+10 | -0.629522E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -154687966.7 | 81.21 | 0.00 | 0.00 |
September | 0.619855E+10 | -0.604482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -153732407.7 | 81.21 | 0.00 | 0.00 |
October | 0.639137E+10 | -0.622382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167550072.1 | 81.22 | 0.00 | 0.00 |
November | 0.619012E+10 | -0.602461E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -165506802.8 | 81.22 | 0.00 | 0.00 |
December | 0.639108E+10 | -0.621710E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173977217.9 | 81.22 | 0.00 | 0.00 |
Annual Sum or Average | 0.755132E+11 | -0.735663E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.194697E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.579154E+10 | -0.629522E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174322938.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.646604E+10 | -0.563428E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -151108541.4 | 81.22 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.276587E+11 | -0.266365E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102213E+10 | 58.99 | 0.00 | 0.00 |
February | 0.255183E+11 | -0.245969E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921424752.6 | 58.99 | 0.00 | 0.00 |
March | 0.282022E+11 | -0.271997E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100250E+10 | 58.99 | 0.00 | 0.00 |
April | 0.260424E+11 | -0.251074E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -935022755.9 | 58.99 | 0.00 | 0.00 |
May | 0.253449E+11 | -0.244580E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -886907804.9 | 58.99 | 0.00 | 0.00 |
June | 0.230054E+11 | -0.221772E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -828168022.3 | 58.99 | 0.00 | 0.00 |
July | 0.222165E+11 | -0.213773E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839157624.2 | 58.99 | 0.00 | 0.00 |
August | 0.219025E+11 | -0.210602E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -842257467.4 | 58.98 | 0.00 | 0.00 |
September | 0.213539E+11 | -0.205017E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -852183350.6 | 58.99 | 0.00 | 0.00 |
October | 0.231355E+11 | -0.221754E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -960094137.3 | 58.99 | 0.00 | 0.00 |
November | 0.239257E+11 | -0.229658E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -959897463.2 | 58.99 | 0.00 | 0.00 |
December | 0.263397E+11 | -0.253208E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101894E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294646E+12 | -0.283577E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.110687E+11 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213539E+11 | -0.271997E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102213E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282022E+11 | -0.205017E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -828168022.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.76 | 0.75 | 01-JAN-09:39 | 3074.85 | 31.37 | 152.83 | 234.17 | 3354.71 | 33.46 | 170.83 | 234.67 |
February | 226.83 | 0.76 | 0.75 | 01-FEB-07:49 | 1379.15 | 26.21 | 167.33 | 248.67 | 1413.39 | 25.57 | 156.00 | 247.17 |
March | 334.33 | 0.76 | 0.75 | 01-MAR-07:49 | 1078.15 | 21.64 | 179.50 | 320.67 | 1109.18 | 21.87 | 180.83 | 320.17 |
April | 285.17 | 0.76 | 0.75 | 01-APR-06:00 | 1392.59 | 21.10 | 127.50 | 345.00 | 1251.01 | 21.35 | 134.83 | 342.17 |
May | 428.67 | 0.76 | 0.75 | 01-MAY-06:40 | 986.49 | 20.71 | 164.83 | 398.50 | 1143.47 | 20.53 | 154.83 | 396.50 |
June | 400.67 | 0.76 | 0.75 | 01-JUN-05:19 | 1109.43 | 22.41 | 210.33 | 399.00 | 1076.21 | 20.96 | 183.33 | 399.17 |
July | 414.00 | 0.76 | 0.75 | 01-JUL-05:49 | 1155.93 | 22.10 | 218.83 | 407.17 | 1316.31 | 21.26 | 193.67 | 407.67 |
August | 410.83 | 0.76 | 0.75 | 01-AUG-05:00 | 1272.15 | 20.94 | 192.17 | 383.67 | 1112.60 | 20.97 | 200.67 | 381.33 |
September | 326.50 | 0.76 | 0.75 | 01-SEP-06:10 | 1298.12 | 22.03 | 181.17 | 332.50 | 1330.68 | 22.22 | 184.00 | 329.17 |
October | 325.17 | 0.76 | 0.75 | 01-OCT-06:49 | 1092.83 | 23.67 | 201.17 | 301.00 | 1065.18 | 23.56 | 212.33 | 301.17 |
November | 254.83 | 0.76 | 0.75 | 01-NOV-07:40 | 1296.02 | 26.67 | 169.50 | 239.50 | 1307.57 | 26.93 | 171.67 | 239.83 |
December | 186.17 | 0.77 | 0.75 | 01-DEC-07:00 | 4210.93 | 35.45 | 149.33 | 202.17 | 4321.21 | 36.18 | 153.17 | 202.00 |
Annual Sum or Average | 3807.33 | 0.76 | 1442.20 | 23.59 | 2114.50 | 3812.00 | 1473.10 | 23.51 | 2096.17 | 3801.00 | ||
Minimum of Months | 186.17 | 0.76 | 0.75 | 986.49 | 20.71 | 127.50 | 202.17 | 1065.18 | 20.53 | 134.83 | 202.00 | |
Maximum of Months | 428.67 | 0.77 | 0.75 | 4210.93 | 35.45 | 218.83 | 407.17 | 4321.21 | 36.18 | 212.33 | 407.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120270E+12 | 154261.74 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856061E+11 | 154261.74 | 01-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.562062E+11 | 131689.40 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295230E+11 | 128797.72 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.443678E+10 | 37781.42 | 03-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123198E+10 | 28632.03 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21978618.19 | 8121.41 | 23-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84433553.23 | 18035.35 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.478267E+10 | 40870.39 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211727E+11 | 54464.06 | 15-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.554897E+11 | 154261.74 | 26-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952660E+11 | 154261.74 | 09-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 21978618.19 | 8121.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120270E+12 | 154261.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.708054E+11 | 79555.19 | 31-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.476322E+11 | 92352.44 | 03-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265697E+11 | 54042.25 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109294E+11 | 38577.95 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623782E+09 | 17005.74 | 03-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16074560.28 | 6124.92 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.818358E+09 | 18350.64 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.527827E+10 | 21891.39 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269463E+11 | 74888.97 | 26-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518477E+11 | 71343.97 | 10-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.708054E+11 | 92352.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.497787E+10 | 0.325162E+10 | 53092.48 | 18-APR-12:00 | 32069.55 | 0.00 |
May | 0.00 | 0.00 | 0.901052E+10 | 0.588841E+10 | 52449.78 | 31-MAY-12:00 | 37325.96 | 0.00 |
June | 0.00 | 0.00 | 0.375526E+11 | 0.230417E+11 | 68631.02 | 26-JUN-18:00 | 41813.57 | 0.00 |
July | 0.00 | 0.00 | 0.505420E+11 | 0.283962E+11 | 89892.42 | 26-JUL-18:00 | 40593.55 | 0.00 |
August | 0.00 | 0.00 | 0.454930E+11 | 0.260493E+11 | 101450.19 | 03-AUG-05:02 | 36248.03 | 0.00 |
September | 0.00 | 0.00 | 0.195328E+11 | 0.144404E+11 | 57963.95 | 11-SEP-12:00 | 35653.74 | 0.00 |
October | 0.00 | 0.00 | 0.338668E+09 | 0.284322E+09 | 15355.87 | 20-OCT-13:00 | 13414.27 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167447E+12 | 0.101352E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.505420E+11 | 0.283962E+11 | 101450.19 | 41813.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 17088833.48 | 11276670.78 | 2821.04 | 19-MAR-16:13 | 1850.22 | 0.00 |
April | 0.00 | 0.00 | 0.360351E+10 | 0.237341E+10 | 38638.33 | 16-APR-03:42 | 20533.83 | 0.00 |
May | 0.00 | 0.00 | 0.834760E+10 | 0.524572E+10 | 30087.60 | 31-MAY-10:57 | 22420.94 | 0.00 |
June | 0.00 | 0.00 | 0.273059E+11 | 0.164795E+11 | 42929.72 | 30-JUN-10:53 | 22845.29 | 0.00 |
July | 0.00 | 0.00 | 0.374931E+11 | 0.201465E+11 | 42929.72 | 03-JUL-12:35 | 20733.10 | 0.00 |
August | 0.00 | 0.00 | 0.341247E+11 | 0.186253E+11 | 42929.72 | 03-AUG-11:35 | 20482.73 | 0.00 |
September | 0.00 | 0.00 | 0.138040E+11 | 0.102918E+11 | 39084.50 | 11-SEP-03:02 | 21190.32 | 0.00 |
October | 0.00 | 0.00 | 0.526508E+09 | 0.399136E+09 | 9785.41 | 21-OCT-15:00 | 7212.02 | 0.00 |
November | 0.00 | 0.00 | 3076214.89 | 1657371.58 | 7512.52 | 09-NOV-05:01 | 4018.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125225E+12 | 0.735744E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.374931E+11 | 0.201465E+11 | 42929.72 | 22845.29 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 10402.01 | 20081.82 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 10623.88 | 20227.75 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 10611.79 | 20182.73 | 03-MAR-20:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 10144.02 | 19642.70 | 03-APR-18:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 9589.91 | 18723.08 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 9015.76 | 17538.45 | 01-JUN-18:08 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 8442.55 | 16396.01 | 03-JUL-18:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 8324.18 | 15757.05 | 01-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8370.91 | 16094.52 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 8739.79 | 17121.92 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 9319.62 | 18278.38 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 9911.91 | 19325.18 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 9451.13 | ||||
Minimum of Months | 0.00 | 0.00 | 8324.18 | 15757.05 | ||
Maximum of Months | 0.00 | 0.00 | 10623.88 | 20227.75 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183946E+10 | 0.23 | 824.13 | 01-JAN-00:01 | 0.28 |
February | 0.166145E+10 | 0.23 | 824.13 | 01-FEB-00:01 | 0.28 |
March | 0.183946E+10 | 0.23 | 824.13 | 01-MAR-00:01 | 0.28 |
April | 0.180163E+10 | 0.23 | 824.13 | 01-APR-04:01 | 0.28 |
May | 0.190782E+10 | 0.24 | 824.13 | 01-MAY-04:01 | 0.28 |
June | 0.195197E+10 | 0.25 | 824.13 | 01-JUN-00:55 | 0.28 |
July | 0.207518E+10 | 0.26 | 824.13 | 01-JUL-00:25 | 0.27 |
August | 0.206051E+10 | 0.26 | 824.13 | 01-AUG-00:40 | 0.27 |
September | 0.190652E+10 | 0.25 | 824.13 | 01-SEP-00:55 | 0.27 |
October | 0.185368E+10 | 0.23 | 824.13 | 01-OCT-04:01 | 0.28 |
November | 0.178865E+10 | 0.23 | 824.13 | 01-NOV-04:01 | 0.28 |
December | 0.183946E+10 | 0.23 | 824.13 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.225258E+11 | 0.24 | |||
Minimum of Months | 0.166145E+10 | 0.23 | 824.13 | 0.27 | |
Maximum of Months | 0.207518E+10 | 0.26 | 824.13 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.871557E+10 | 0.97 | 6368.20 | 06-JAN-04:01 | 1.48 |
February | 0.727441E+10 | 0.92 | 6368.20 | 01-FEB-04:01 | 1.48 |
March | 0.707863E+10 | 0.85 | 5809.11 | 06-MAR-05:01 | 1.42 |
April | 0.623425E+10 | 0.80 | 5737.48 | 03-APR-04:01 | 1.41 |
May | 0.579755E+10 | 0.75 | 3483.09 | 03-MAY-05:03 | 1.08 |
June | 0.565581E+10 | 0.75 | 4076.58 | 26-JUN-18:00 | 1.17 |
July | 0.584942E+10 | 0.74 | 5513.43 | 26-JUL-18:00 | 1.36 |
August | 0.587585E+10 | 0.75 | 6368.20 | 03-AUG-05:02 | 1.45 |
September | 0.564041E+10 | 0.75 | 3559.60 | 30-SEP-05:03 | 1.10 |
October | 0.620996E+10 | 0.78 | 3896.31 | 15-OCT-06:00 | 1.15 |
November | 0.688168E+10 | 0.85 | 6368.20 | 26-NOV-04:01 | 1.48 |
December | 0.807630E+10 | 0.92 | 6368.20 | 09-DEC-04:03 | 1.48 |
Annual Sum or Average | 0.792898E+11 | 0.82 | |||
Minimum of Months | 0.564041E+10 | 0.74 | 3483.09 | 1.08 | |
Maximum of Months | 0.871557E+10 | 0.97 | 6368.20 | 1.48 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220996E+10 | 0.59 | 1465.18 | 31-JAN-05:02 | 0.87 |
February | 0.183400E+10 | 0.56 | 1592.28 | 03-FEB-05:02 | 0.90 |
March | 0.177062E+10 | 0.51 | 1211.79 | 08-MAR-05:03 | 0.79 |
April | 0.158964E+10 | 0.49 | 1224.87 | 18-APR-10:55 | 0.78 |
May | 0.154058E+10 | 0.48 | 1158.30 | 31-MAY-10:57 | 0.76 |
June | 0.174936E+10 | 0.54 | 1687.66 | 11-JUN-14:25 | 0.91 |
July | 0.189947E+10 | 0.57 | 1687.66 | 03-JUL-10:35 | 0.91 |
August | 0.185069E+10 | 0.56 | 1687.66 | 01-AUG-03:11 | 0.92 |
September | 0.154651E+10 | 0.51 | 1687.66 | 07-SEP-04:01 | 0.92 |
October | 0.156028E+10 | 0.48 | 892.48 | 23-OCT-05:03 | 0.67 |
November | 0.172648E+10 | 0.52 | 1418.84 | 26-NOV-05:02 | 0.86 |
December | 0.202168E+10 | 0.56 | 1383.63 | 10-DEC-05:02 | 0.84 |
Annual Sum or Average | 0.212993E+11 | 0.53 | |||
Minimum of Months | 0.154058E+10 | 0.48 | 892.48 | 0.67 | |
Maximum of Months | 0.220996E+10 | 0.59 | 1687.66 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 47.44 | 0.14 |
February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 45.99 | 0.14 |
March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:01 | 5.36 | 5.36 | 46.06 | 0.14 |
April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:03 | 5.36 | 5.36 | 50.24 | 0.14 |
May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:03 | 5.36 | 5.36 | 50.33 | 0.14 |
June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:03 | 5.36 | 5.36 | 50.60 | 0.14 |
July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 51.73 | 0.14 |
August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 52.57 | 0.14 |
September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 52.71 | 0.14 |
October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:03 | 5.36 | 5.36 | 51.23 | 0.14 |
November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:03 | 5.36 | 5.36 | 50.87 | 0.14 |
December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:01 | 5.36 | 5.36 | 47.24 | 0.14 |
Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 45.99 | 0.14 | |
Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 52.71 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 47.44 | 59.93 | 10402.01 | 20081.82 | 31-JAN-19:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 45.99 | 59.26 | 10623.88 | 20227.75 | 17-FEB-19:20 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 46.06 | 59.55 | 10611.79 | 20182.73 | 03-MAR-20:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.84 | 47.84 | 10144.02 | 19642.70 | 03-APR-18:15 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 48.36 | 48.36 | 9589.91 | 18723.08 | 01-MAY-18:10 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.03 | 49.03 | 9015.76 | 17538.45 | 01-JUN-18:08 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.08 | 50.08 | 8442.55 | 16396.01 | 03-JUL-18:50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.49 | 50.49 | 8324.18 | 15757.05 | 01-AUG-06:53 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.40 | 50.40 | 8370.91 | 16094.52 | 29-SEP-18:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 47.98 | 47.98 | 8739.79 | 17121.92 | 31-OCT-18:30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 49.51 | 49.51 | 9319.62 | 18278.38 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.24 | 59.88 | 9911.91 | 19325.18 | 29-DEC-19:50 |
Annual Sum or Average | 0.00 | 9451.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.99 | 47.84 | 8324.18 | 15757.05 | ||
Maximum of Months | 0.00 | 0.00 | 50.49 | 59.93 | 10623.88 | 20227.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.871557E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.727441E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.707863E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.764929E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.845816E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.160372E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.197042E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184516E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113095E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.632072E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.688168E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.807630E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125957E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.632072E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.197042E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.220996E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.183400E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.177578E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.246171E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.365758E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.823673E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.107118E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.991290E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.497678E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.171109E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172740E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.202168E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.512374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107118E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.871557E+10 | 0.00 | 0.120270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.727441E+10 | 0.00 | 0.856061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707863E+10 | 0.00 | 0.562062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623425E+10 | 0.497787E+10 | 0.295230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579755E+10 | 0.901052E+10 | 0.443678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565581E+10 | 0.375526E+11 | 0.123198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584942E+10 | 0.505420E+11 | 21978618.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587585E+10 | 0.454930E+11 | 84433553.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564041E+10 | 0.195328E+11 | 0.478267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.620996E+10 | 0.338668E+09 | 0.211727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688168E+10 | 0.00 | 0.554897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807630E+10 | 0.00 | 0.952660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792898E+11 | 0.167447E+12 | 0.474091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564041E+10 | 0.00 | 21978618.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.871557E+10 | 0.505420E+11 | 0.120270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220996E+10 | 0.00 | 0.708054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183400E+10 | 0.00 | 0.476322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177062E+10 | 17088833.48 | 0.265697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158964E+10 | 0.360062E+10 | 0.109294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154058E+10 | 0.834760E+10 | 0.623782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174936E+10 | 0.273005E+11 | 16074560.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189947E+10 | 0.374751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185069E+10 | 0.341080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154651E+10 | 0.137992E+11 | 0.818358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156028E+10 | 0.526508E+09 | 0.527827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172648E+10 | 3076214.89 | 0.269463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202168E+10 | 0.00 | 0.518477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212993E+11 | 0.125178E+12 | 0.241467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220996E+10 | 0.374751E+11 | 0.708054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.871557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.727441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.707863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623425E+10 | 0.00 | 0.00 | 0.00 | 0.141504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579755E+10 | 0.00 | 0.00 | 0.00 | 0.266061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565581E+10 | 0.00 | 0.00 | 0.00 | 0.103814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584942E+10 | 0.00 | 0.00 | 0.00 | 0.138548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587585E+10 | 0.00 | 0.00 | 0.00 | 0.125758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.564041E+10 | 0.00 | 0.00 | 0.00 | 0.566909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.620996E+10 | 0.00 | 0.00 | 0.00 | 0.110763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.688168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792898E+11 | 0.00 | 0.00 | 0.00 | 0.466675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.871557E+10 | 0.00 | 0.00 | 0.00 | 0.138548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.220996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177062E+10 | 0.00 | 0.00 | 0.00 | 5153562.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158964E+10 | 0.00 | 0.00 | 0.00 | 0.872073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154058E+10 | 0.00 | 0.00 | 0.00 | 0.211700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174936E+10 | 0.00 | 0.00 | 0.00 | 0.648737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189947E+10 | 0.00 | 0.00 | 0.00 | 0.881236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185069E+10 | 0.00 | 0.00 | 0.00 | 0.806221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154651E+10 | 0.00 | 0.00 | 0.00 | 0.343027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156028E+10 | 0.00 | 0.00 | 0.00 | 0.150808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172648E+10 | 0.00 | 0.00 | 0.00 | 920491.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212993E+11 | 0.00 | 0.00 | 0.00 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220996E+10 | 0.00 | 0.00 | 0.00 | 0.881236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112037E+12 | 0.00 | 0.00 | 3.56 |
February | 0.296641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673388E+11 | 0.00 | 0.00 | 3.56 |
March | 0.439936E+11 | 0.00 | 0.00 | 498006.36 | 0.00 | 0.342323E+11 | 0.777443E+09 | 0.00 | 3.57 |
April | 0.422223E+11 | 0.860517E+09 | 0.00 | 8313234.20 | 0.00 | 0.106243E+11 | 0.294657E+10 | 0.00 | 3.63 |
May | 0.234687E+11 | 0.708881E+09 | 0.00 | 30995887.17 | 0.00 | 0.241879E+09 | 0.130759E+11 | 0.00 | 3.82 |
June | 0.116251E+11 | 0.773874E+10 | 0.00 | 42866768.91 | 12142263.08 | 43572606.75 | 0.854192E+10 | 0.00 | 3.97 |
July | 0.412496E+10 | 0.958140E+10 | 0.00 | 53171134.08 | 8792292.33 | 0.00 | 0.930888E+10 | 0.00 | 4.12 |
August | 0.584677E+10 | 0.847871E+10 | 0.00 | 55545801.87 | 23161355.63 | 3700577.41 | 0.111732E+11 | 0.00 | 4.11 |
September | 0.209848E+11 | 0.208245E+10 | 0.00 | 44094646.58 | 0.00 | 0.352354E+09 | 0.110604E+11 | 0.00 | 3.87 |
October | 0.498135E+11 | 0.00 | 0.00 | 5527925.64 | 0.00 | 0.190792E+10 | 0.424504E+10 | 0.00 | 3.59 |
November | 0.436966E+11 | 0.00 | 0.00 | 232669.41 | 0.00 | 0.338642E+11 | 0.735064E+09 | 0.00 | 3.56 |
December | 0.259999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819902E+11 | 0.00 | 0.00 | 3.53 |
Annual Sum or Average | 0.315682E+12 | 0.294507E+11 | 0.00 | 0.241246E+09 | 44095911.04 | 0.342636E+12 | 0.618644E+11 | 0.00 | 3.74 |
Minimum of Months | 0.412496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
Maximum of Months | 0.498135E+11 | 0.958140E+10 | 0.00 | 55545801.87 | 23161355.63 | 0.112037E+12 | 0.130759E+11 | 0.00 | 4.12 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107389E+12 | 0.00 | 0.00 | 0.00 | 0.167758E+09 | 0.172684E+09 | 0.00 | 0.00 | 8.33 |
February | 0.830379E+11 | 0.00 | 0.00 | 0.00 | 66880651.98 | 0.136661E+09 | 0.00 | 0.00 | 8.09 |
March | 0.651938E+11 | 0.00 | 0.00 | 2047503.37 | 63497152.97 | 38240527.92 | 0.279084E+10 | 0.00 | 7.85 |
April | 0.428171E+11 | 0.344290E+09 | 0.00 | 14352362.64 | 5878198.53 | 8461492.48 | 0.651580E+10 | 0.00 | 7.65 |
May | 0.138714E+11 | 0.236668E+09 | 0.00 | 56106437.39 | 0.00 | 0.00 | 0.229794E+11 | 0.00 | 7.61 |
June | 0.545652E+10 | 0.432237E+10 | 0.00 | 64585705.58 | 0.00 | 0.00 | 0.161055E+11 | 0.00 | 8.01 |
July | 0.136681E+10 | 0.580294E+10 | 0.00 | 82962658.23 | 0.00 | 0.00 | 0.133123E+11 | 0.00 | 8.24 |
August | 0.183276E+10 | 0.520100E+10 | 0.00 | 80352306.04 | 0.00 | 0.00 | 0.161050E+11 | 0.00 | 8.13 |
September | 0.124248E+11 | 0.517501E+09 | 0.00 | 68539267.24 | 0.00 | 0.00 | 0.208561E+11 | 0.00 | 7.73 |
October | 0.379319E+11 | 0.00 | 0.00 | 12269397.56 | 0.00 | 0.00 | 0.119470E+11 | 0.00 | 7.51 |
November | 0.616760E+11 | 0.00 | 0.00 | 3586160.48 | 42536318.53 | 35142835.58 | 0.594771E+10 | 0.00 | 7.83 |
December | 0.912435E+11 | 0.00 | 0.00 | 0.00 | 55152654.82 | 85547473.77 | 0.00 | 0.00 | 8.12 |
Annual Sum or Average | 0.524241E+12 | 0.164248E+11 | 0.00 | 0.384802E+09 | 0.401703E+09 | 0.476737E+09 | 0.116560E+12 | 0.00 | 7.93 |
Minimum of Months | 0.136681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
Maximum of Months | 0.107389E+12 | 0.580294E+10 | 0.00 | 82962658.23 | 0.167758E+09 | 0.172684E+09 | 0.229794E+11 | 0.00 | 8.33 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.405829E+11 | 0.328589E+11 | 0.364019E+12 | 0.00 | 0.595319E+11 |
February | 0.508215E+11 | 0.257013E+11 | 0.283874E+12 | 0.00 | 0.444591E+11 |
March | 0.906630E+11 | 0.215254E+11 | 0.237542E+12 | 1605872.62 | 0.344820E+11 |
April | 0.110678E+12 | 0.160295E+11 | 0.174266E+12 | 0.420758E+09 | 0.374211E+11 |
May | 0.130393E+12 | 0.116420E+11 | 0.131762E+12 | 0.134466E+10 | 0.442996E+11 |
June | 0.136168E+12 | 0.611220E+10 | 0.667449E+11 | 0.131084E+10 | 0.105128E+12 |
July | 0.133255E+12 | 0.365793E+10 | 0.415019E+11 | 0.116629E+10 | 0.136240E+12 |
August | 0.119473E+12 | 0.416594E+10 | 0.543381E+11 | 0.148037E+10 | 0.123623E+12 |
September | 0.780844E+11 | 0.858433E+10 | 0.118306E+12 | 0.151809E+10 | 0.646870E+11 |
October | 0.553504E+11 | 0.145907E+11 | 0.179363E+12 | 0.276222E+09 | 0.233980E+11 |
November | 0.293336E+11 | 0.201642E+11 | 0.236466E+12 | 0.00 | 0.329741E+11 |
December | 0.173288E+11 | 0.273365E+11 | 0.312150E+12 | 0.00 | 0.476724E+11 |
Annual Sum or Average | 0.992132E+12 | 0.192369E+12 | 0.220033E+13 | 0.751883E+10 | 0.753916E+12 |
Minimum of Months | 0.173288E+11 | 0.365793E+10 | 0.415019E+11 | 0.00 | 0.233980E+11 |
Maximum of Months | 0.136168E+12 | 0.328589E+11 | 0.364019E+12 | 0.151809E+10 | 0.136240E+12 |