Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:30:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1327.11 | 578.51 | 578.51 |
Net Site Energy | 1327.11 | 578.51 | 578.51 |
Total Source Energy | 3177.42 | 1385.10 | 1385.10 |
Net Source Energy | 3177.42 | 1385.10 | 1385.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 395.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 330.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 834.77 | 492.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 395.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 82.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 330.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 68.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 140.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 395.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 82.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 330.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 68.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 140.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 17.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 173.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 97.57 | 214.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.90 | 214.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 173.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 97.57 | 214.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.90 | 214.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 834.774 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 834.774 | 100.00 |
Total On-Site and Utility Electric Sources | 834.774 | 100.00 |
Total Electricity End Uses | 834.774 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 19.84 | 5.33 |
Air to Air Heat Recovery for Heating | 352.57 | 94.67 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 372.41 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 21.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2783.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 6.8133 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.4031 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 15.4031 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 15.4031 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 7.9050 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.9414 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.9414 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 6.8133 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 15.4031 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 15.4031 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 15.4031 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 7.9050 | 6.19 | 0.0000 | |
Total | 2293.99 | 13.9414 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 13.9414 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 13.9414 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-13:00 | 07-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 11-OCT-11:09 |
Heating | 0.00 | 190616.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33055.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7362.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4462.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74585.16 | 195078.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 190616.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33055.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7362.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4462.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 428.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 262.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1045.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 217.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 446.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 54.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 104.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2643.73 | 533.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 186.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 455.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 94.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1152.46 | 232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 186.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 455.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 94.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1152.46 | 232.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.54 |
CORE_RETAIL DIRECT AIR | 7.63 |
POINT_OF_SALE DIRECT AIR | 1.24 |
FRONT_RETAIL DIRECT AIR | 1.02 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.57 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 2.57 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 58453.46 |
PSZ-AC:1 HEATING COIL | 44710.18 |
PSZ-AC:2 HEATING COIL | 255091.07 |
PSZ-AC:3 HEATING COIL | 35803.06 |
PSZ-AC:4 HEATING COIL | 30817.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
PSZ-AC:2 | 7.63 | 7.63 | 7.63 | 7.63 | 7.85 | 7.85 | 1.00 | 0.971418 | 7.85 |
PSZ-AC:3 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC:4 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.54 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 7.85 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.24 | 0.178122 |
PSZ-AC:4_OA_CONTROLLER | 1.02 | 0.178122 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.54 | 1644.01 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.85 | 13230.48 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1377.65 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1132.18 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.01 | 30020.62 | 44710.18 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.85 | 7.85 | 7.85 | 5.18 | 165454.41 | 255091.07 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.821246 | 23487.85 | 35803.06 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.674916 | 20111.87 | 30817.81 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 1.54 | 0.768194 | 1.02 | 30020.62 | 15010.31 | 0.785470 | 0.785470 |
PSZ-AC:2 COOLING COIL | 7.85 | 3.93 | 5.24 | 165454.41 | 82727.21 | 0.755870 | 0.755870 |
PSZ-AC:3 COOLING COIL | 1.24 | 0.622156 | 0.829540 | 23487.85 | 11743.92 | 0.800420 | 0.800420 |
PSZ-AC:4 COOLING COIL | 1.02 | 0.511300 | 0.681733 | 20111.87 | 10055.93 | 0.782450 | 0.782450 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC:2 OA HEAT RECOVERY | 1.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 6.813 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.883 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.923 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 7.905 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.905 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 2588.286 | 6.813 | 316.489 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2588.286 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 24652.462 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24652.462 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 2322.948 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.948 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 2322.948 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.948 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 94.860 | 7.905 | 48.947 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 94.860 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7927 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.094 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | -0.18582341E-14 | 0.27940935E-16 | -0.15611726E-09 | 0.38969277E-16 |
25 | 8 | 0.22773384E-07 | 0.10745822E-12 | 0.38717117E-03 | -0.25894120E-09 |
26 | 7 | -0.12521196E-01 | 0.55263725E-08 | -0.23488382E-01 | 0.14237056E-03 |
27 | 6 | 0.41294844 | 0.19182782E-05 | 0.47855698 | -0.48373255E-02 |
28 | 5 | -5.2647085 | 0.71488872E-04 | -4.4909009 | 0.64103215E-01 |
29 | 4 | 33.330797 | 0.58379299E-03 | 21.634323 | -0.42647708 |
30 | 3 | -111.92391 | 0.12703862E-02 | -56.007508 | 1.5252745 |
31 | 2 | 197.82265 | 0.71362036E-03 | 78.226632 | -2.9116979 |
32 | 1 | -171.41994 | 0.76085797E-04 | -55.357141 | 2.7500639 |
33 | 0 | 57.057407 | 0.43247804E-06 | 15.541857 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 36 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 37 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CORE_RETAIL | 16 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.237 | 6.240E-004 | 2.832E-004 | 0.368 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.203 | 1.270E-004 | 1.032E-004 | 7.495E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 1.389E-002 | 1.157E-003 | 3.817E-004 | 0.683 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.7644E-004 |
2 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.1371E-004 |
3 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5762E-004 |
4 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.6077E-004 |
5 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5896E-004 |
6 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.5989E-004 |
7 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.8826E-004 |
8 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.8861E-004 |
9 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.8180E-004 |
10 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.2204E-004 |
11 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.3639E-004 |
12 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.9336E-004 |
13 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.3239E-004 |
14 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.0332E-004 |
15 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 3.3459E-004 |
16 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.5384E-004 |
17 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.9626E-004 |
18 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4265E-004 |
19 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.4827E-004 |
20 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.3300E-004 |
21 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.5185E-004 |
22 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4138E-004 |
23 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 3.6316E-004 |
24 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.5160E-004 |
25 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.9006E-004 |
26 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1327E-004 |
27 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.6926E-004 |
28 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1009E-004 |
29 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.7935E-004 |
30 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1701E-004 |
31 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 2.1006E-004 |
32 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.2163E-004 |
33 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.7120E-004 |
34 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 2.4034E-003 |
35 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.6938E-004 |
36 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 2.9297E-003 |
37 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.9138E-004 |
38 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.3172E-003 |
39 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.0423E-004 |
40 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 4.8861E-004 |
41 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 9.7201E-004 |
42 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 6.9402E-004 |
43 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 1.0858E-003 |
44 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 7.7100E-004 |
45 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 8.3848E-004 |
46 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 5.7632E-004 |
47 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.0755E-004 |
48 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 2.9208E-004 |
49 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.4431E-004 |
50 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2739E-004 |
51 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.7483E-004 |
52 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2614E-004 |
53 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.0407E-004 |
54 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3182E-004 |
55 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.3275E-004 |
56 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2274E-004 |
57 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 2.0459E-003 |
58 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1355E-004 |
59 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 2.4745E-003 |
60 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1559E-004 |
61 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.1744E-003 |
62 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1257E-004 |
63 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 4.5006E-004 |
64 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.5812E-004 |
65 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.1878E-003 |
66 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.0639E-003 |
67 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.1348E-003 |
68 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.0355E-003 |
69 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.2311E-003 |
70 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.4991E-003 |
71 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.0113E-003 |
72 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.1229E-003 |
73 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.7862E-004 |
74 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 4.9285E-003 |
75 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.4640E-004 |
76 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.2052E-003 |
77 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 5.0607E-004 |
78 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 6.2166E-003 |
79 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.3245E-004 |
80 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.6026E-003 |
81 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 3.7941E-003 |
82 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.4312E-004 |
83 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 3.9616E-003 |
84 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.3012E-004 |
85 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.9320E-003 |
86 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.8771E-004 |
87 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.1841E-003 |
88 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.2857E-004 |
89 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0706E-004 |
90 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3075E-004 |
91 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 5.7906E-004 |
92 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.2701E-004 |
93 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 8.2355E-004 |
94 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3972E-004 |
95 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0783E-004 |
96 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3139E-004 |
97 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.0380E-003 |
98 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.7268E-004 |
99 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 8.5646E-004 |
100 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 4.8964E-004 |
101 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.2897E-003 |
102 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 7.6223E-004 |
103 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 2.4225E-003 |
104 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 9.8043E-004 |
105 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 3.0323E-004 |
106 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.5093E-003 |
107 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.6342E-004 |
108 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.2450E-003 |
109 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 3.4048E-004 |
110 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.8912E-003 |
111 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 4.0205E-004 |
112 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 4.2090E-003 |
113 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.2748E-003 |
114 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.9827E-004 |
115 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.0595E-003 |
116 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.8131E-004 |
117 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.6691E-003 |
118 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2380E-004 |
119 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 3.2528E-003 |
120 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2074E-004 |
121 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.8707E-004 |
122 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2388E-004 |
123 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.3722E-004 |
124 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.1953E-004 |
125 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 4.9129E-004 |
126 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3097E-004 |
127 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 5.5315E-004 |
128 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3062E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 15436.83151 | 18524.19781 | 1.10367 | 1.32441 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 29522.44306 | 35426.93167 | 1.28032 | 1.53639 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 87907.20320 | 105488.64384 | 6.35732 | 7.62879 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
4 | CORE_RETAIL | Heating | 64422.54168 | 77307.05002 | 2.75618 | 3.30742 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13774.99909 | 16529.99890 | 1.03693 | 1.24431 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
6 | POINT_OF_SALE | Heating | 14354.00980 | 17224.81176 | 0.62443 | 0.74931 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11320.54424 | 13584.65309 | 0.85217 | 1.02260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
8 | FRONT_RETAIL | Heating | 14351.46804 | 17221.76165 | 0.62431 | 0.74918 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 48671.49040 | 58405.78848 | 2.14131 | 2.56958 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -16.30000 | 9.24091E-004 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 17903.25 | 1.36434 | 1.36434 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 44710.18 | 1.53639 | 1.53639 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 112399.79 | 7.85325 | 7.85325 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 157534.09 | 3.30742 | 3.30742 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17600.59 | 1.24431 | 1.24431 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 24672.88 | 0.74931 | 0.74931 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14710.64 | 1.02260 | 1.02260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 24669.85 | 0.74918 | 0.74918 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53639 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.62879 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24431 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02260 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.56958 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 2.56958 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 58453.46123 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53639 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53639 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53639 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53639 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53639 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53639 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.62879 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.62879 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.62879 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.62879 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.85325 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.85325 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97142 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24431 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24431 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24431 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24431 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24431 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24431 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02260 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02260 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02260 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02260 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02260 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02260 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.53639 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.85325 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.24431 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.02260 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53639 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53639 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1644.00764 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53639 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53639 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53639 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01402 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53639 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76819 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02426 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30020.62000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15010.31000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78547 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78547 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30020.62000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 44710.18475 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 44710.18475 |
64 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.85325 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89033 |
66 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC:2 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.89033 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.85325 |
68 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13230.48187 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.85325 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.85325 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.85325 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.18314 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.85325 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.92662 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.23550 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 165454.41000 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 82727.20500 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75587 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75587 |
80 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 165454.41000 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 255091.06963 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
84 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 255091.06963 |
85 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24431 |
86 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
87 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24431 |
88 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1377.65162 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24431 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24431 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24431 |
92 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82125 |
93 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24431 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62216 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82954 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23487.85000 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11743.92500 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80042 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80042 |
100 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23487.85000 |
101 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35803.06144 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
104 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 35803.06144 |
105 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02260 |
106 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
107 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02260 |
108 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1132.18037 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02260 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02260 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02260 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67492 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02260 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51130 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68173 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20111.87000 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10055.93500 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78245 |
119 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78245 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20111.87000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30817.81321 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
124 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 30817.81321 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 28813.7 | 11.48 | 11.48 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 159277.5 | 10.60 | 10.60 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 22510.9 | 11.41 | 11.41 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 19308.4 | 11.49 | 11.49 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.793 | 0.709 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.6899844966E-002 | 0.2683643402 | Pass | Pass | 3.2316852140E-002 | 0.1112027817 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.9944590727E-002 | 0.2285780766 | Pass | Pass | 0.5858827076 | 6.2220918136 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.1766282768E-002 | 0.2934887524 | Pass | Pass | 4.8742721795E-002 | 0.1249868371 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1011541285 | 0.3297559822 | Pass | Pass | 3.3804267917E-002 | 0.1048641983 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1060911204 | 0.3887515304 | Pass | Pass | 0.1561292313 | 0.5313623829 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4242.17 | 185.96 | 0.00 | 797.86 | 474.56 | 5700.57 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.168 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.709 | 0.793 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.311 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.168 | 0.401 | 0.402 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.168 | 0.401 | 0.402 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.168 | 0.401 | 0.402 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 107.73 | 2.630 | 0.446 | 0.446 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 107.73 | 2.630 | 0.446 | 0.446 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 6.8133 | 379.89 | 2588.29 | LightsWired | LTG_SCH_BACK | 32.16 | 168.00 | 31.72 | 0.0000 | Y | 15.41 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 15.4031 | 1600.48 | 24652.46 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 54.87 | 0.0000 | Y | 253.91 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 15.4031 | 150.81 | 2322.95 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 15.4031 | 150.81 | 2322.95 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 7.9050 | 12.00 | 94.86 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.22 |
Interior Lighting Total | 13.9414 | 2293.99 | 31981.50 | 330.06 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.46 | 6163.12 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.46 | 6163.12 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 273.03 | AstronomicalClock | - | 42.04 | 42.04 | 2.15 | |
EXTERIOR_LIGHTS_B | 4967.84 | AstronomicalClock | - | 83.67 | 71.18 | 66.38 | |
Exterior Lighting Total | 5240.87 | 68.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30020.62 | 23580.30 | 6440.32 | 0.79 | 3.80 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 165454.41 | 125062.02 | 40392.39 | 0.76 | 3.40 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23487.85 | 18800.14 | 4687.71 | 0.80 | 3.80 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20111.87 | 15736.53 | 4375.34 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 28813.7 | 11.48 | 11.48 | ||||
PSZ-AC:2 COOLING COIL | 159277.5 | 10.60 | 10.60 | ||||
PSZ-AC:3 COOLING COIL | 22510.9 | 11.41 | 11.41 | ||||
PSZ-AC:4 COOLING COIL | 19308.4 | 11.49 | 11.49 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 58453.46 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 44710.18 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 255091.07 | 0.80 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 35803.06 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 30817.81 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.57 | 238.74 | 92.91 | 1.00 | 3.44 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1644.01 | 1070.05 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.85 | 13230.48 | 1684.71 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1377.65 | 1107.16 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1132.18 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 15436.83 | 18524.20 | 48.76 | 1.104 | 1.324 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00945 | 23.42 | 0.01335 | 0.232 | 0.00 |
CORE_RETAIL | 87907.20 | 105488.64 | 65.91 | 6.357 | 7.629 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00977 | 23.42 | 0.01335 | 1.890 | 0.00 |
POINT_OF_SALE | 13775.00 | 16530.00 | 109.61 | 1.037 | 1.244 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00906 | 30.14 | 0.01337 | 0.178 | 0.00 |
FRONT_RETAIL | 11320.54 | 13584.65 | 90.08 | 0.852 | 1.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00917 | 30.22 | 0.01337 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 0.00 | 30.51 | 0.01343 | 30.30 | 0.01337 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 29522.44 | 35426.93 | 93.26 | 1.280 | 1.536 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00743 | -16.30 | 0.00092 | 0.232 | 0.00 |
CORE_RETAIL | 64422.54 | 77307.05 | 48.30 | 2.756 | 3.307 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00745 | -16.30 | 0.00092 | 1.890 | 0.00 |
POINT_OF_SALE | 14354.01 | 17224.81 | 114.22 | 0.624 | 0.749 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_RETAIL | 14351.47 | 17221.76 | 114.20 | 0.624 | 0.749 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_ENTRY | 48671.49 | 58405.79 | 4867.15 | 2.141 | 2.570 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 21.00 | 0.00564 | -16.30 | 0.00092 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.36 | 1.36 | 1.54 | 1.54 | 1.5364 | 1.5364 | 1.5364 | 1.0000 | 1.0000 |
PSZ-AC:2 | 7.85 | 7.85 | 3.31 | 3.31 | 7.8532 | 7.6288 | 7.8532 | 0.9714 | 1.0000 |
PSZ-AC:3 | 1.24 | 1.24 | 0.75 | 0.75 | 1.2443 | 1.2443 | 1.2443 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.02 | 1.02 | 0.75 | 0.75 | 1.0226 | 1.0226 | 1.0226 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 58453.461 | 58453.461 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 58453.46 | 58453.46 | 2.569576 | 21.00 | 12.37 | 0.00563576 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00563576 | 35.6595 | 58405.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 30020.620 | 23580.296 | 1.536390 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 15010.31 | 12270.13 | 1.024260 | 25.98 | 17.90 | 0.00982040 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.6095 | 23.89 | 0.00900170 | 47.5184 | 15072.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 44710.185 | 44710.185 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44710.18 | 44710.18 | 1.536388 | 15.33 | 10.85 | 0.00645346 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 15.0731 | 21.11 | 0.00743483 | 46.5892 | 29522.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 165454.410 | 125062.025 | 7.853250 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 82727.21 | 64455.72 | 5.235500 | 26.91 | 18.56 | 0.01027962 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 36.1060 | 23.89 | 0.00923934 | 48.7581 | 83035.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 255091.070 | 255091.070 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 255091.07 | 255091.07 | 7.853248 | 11.92 | 8.74 | 0.00588199 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.0707 | 21.11 | 0.00745371 | 46.7033 | 64422.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 23487.850 | 18800.145 | 1.244310 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11743.92 | 9768.79 | 0.829540 | 25.72 | 17.69 | 0.00967417 | 12.80 | 11.87 | 0.00850000 | 30.22 | 0.01336682 | 21.81 | 21.4723 | 23.89 | 0.00905705 | 47.8109 | 13770.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 35803.061 | 35803.061 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35803.06 | 35803.06 | 1.244313 | 15.61 | 11.09 | 0.00656694 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.3149 | 21.11 | 0.00750965 | 47.0525 | 14354.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 20111.870 | 15736.533 | 1.022600 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10055.93 | 8120.51 | 0.681733 | 25.93 | 17.94 | 0.00990397 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 26.1277 | 23.89 | 0.00917279 | 48.4130 | 11310.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 30817.813 | 30817.813 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30817.81 | 30817.81 | 1.022600 | 14.45 | 10.38 | 0.00636246 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.4185 | 21.11 | 0.00750955 | 47.0518 | 14351.47 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 58453.461 | 58453.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 2.569576 | 3.01649066 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | Sensible | 58453.46 | 58453.46 | 1.0000 | 3.01649066 | 2.569576 | 21.00 | 12.37 | 0.00563576 | 35412.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58453.46 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.01 | 0.00563576 | 21.00 | 0.00563576 | 35.6595 | 58405.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30020.620 | 23580.296 | 1.536390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0956 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.536388 | 1.80360460 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | Sensible | 15010.31 | 12270.13 | 1.0000 | 1.20240474 | 1.024260 | 25.98 | 17.90 | 0.00982040 | 51142.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15010.31 | 30.30 | 0.01336696 | 21.83 | 0.23158056 | 22.6095 | 23.89 | 0.00900170 | 23.89 | 0.00900170 | 47.5184 | 15072.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44710.185 | 44710.185 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.536388 | 1.80360460 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44710.18 | 44710.18 | 1.0000 | 1.80360460 | 1.536388 | 15.33 | 10.85 | 0.00645346 | 31728.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44710.18 | -16.30 | 0.00092409 | -16.30 | 0.23158056 | 15.0731 | 20.94 | 0.00743483 | 21.11 | 0.00743483 | 46.5892 | 29522.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 165454.410 | 125062.025 | 7.853250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9493 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.853248 | 9.21912662 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | Sensible | 82727.21 | 64455.72 | 1.0000 | 6.14608598 | 5.235500 | 26.91 | 18.56 | 0.01027962 | 53258.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82727.21 | 30.30 | 0.01336696 | 21.83 | 1.89032875 | 36.1060 | 23.89 | 0.00923934 | 23.89 | 0.00923934 | 48.7581 | 83035.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 255091.070 | 255091.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.853248 | 9.21912662 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 255091.07 | 255091.07 | 1.0000 | 9.21912662 | 7.853248 | 11.92 | 8.74 | 0.00588199 | 26815.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 255091.07 | -16.30 | 0.00092409 | -16.30 | 1.89032875 | 24.0707 | 20.86 | 0.00745371 | 21.11 | 0.00745371 | 46.7033 | 64422.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23487.850 | 18800.145 | 1.244310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8238 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.244313 | 1.46073011 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11743.92 | 9768.79 | 1.0000 | 0.97381800 | 0.829540 | 25.72 | 17.69 | 0.00967417 | 50498.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11743.92 | 30.22 | 0.01336682 | 21.81 | 0.17812154 | 21.4723 | 23.89 | 0.00905705 | 23.89 | 0.00905705 | 47.8109 | 13770.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35803.061 | 35803.061 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.244313 | 1.46073011 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35803.06 | 35803.06 | 1.0000 | 1.46073011 | 1.244313 | 15.61 | 11.09 | 0.00656694 | 32297.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35803.06 | -16.30 | 0.00092409 | -16.30 | 0.17812154 | 14.3149 | 20.94 | 0.00750965 | 21.11 | 0.00750965 | 47.0525 | 14354.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20111.870 | 15736.533 | 1.022600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2510 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022600 | 1.20045586 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10055.93 | 8120.51 | 1.0000 | 0.80030402 | 0.681733 | 25.93 | 17.94 | 0.00990397 | 51299.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10055.93 | 30.30 | 0.01336696 | 21.83 | 0.17812154 | 26.1277 | 23.89 | 0.00917279 | 23.89 | 0.00917279 | 48.4130 | 11310.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30817.813 | 30817.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022600 | 1.20045586 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30817.81 | 30817.81 | 1.0000 | 1.20045586 | 1.022600 | 14.45 | 10.38 | 0.00636246 | 30605.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30817.81 | -16.30 | 0.00092409 | -16.30 | 0.17812154 | 17.4185 | 20.94 | 0.00750955 | 21.11 | 0.00750955 | 47.0518 | 14351.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.54 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.85 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.24 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2828.17 | 3907.17 | 2329.83 |
CORE_RETAIL | 2207.67 | 2886.67 | 989.33 |
POINT_OF_SALE | 2752.67 | 2792.00 | 1266.17 |
FRONT_RETAIL | 2795.00 | 3208.00 | 1594.83 |
FRONT_ENTRY | 2499.50 | 4404.00 | 2097.00 |
Facility | 3750.83 | 4515.33 | 2783.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 13.83 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 11.33 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 19.33 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 32.50 | 0.00 | 21.83 | 0.00 |
Facility | 64.00 | 0.00 | 21.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.04 | 8.18 | 2317.33 | 0.478 | 0.038 | 0.000 | 0.000 |
CORE_RETAIL | 127.51 | 258.43 | 9762.95 | 0.871 | 0.008 | 0.000 | 0.000 |
POINT_OF_SALE | 12.02 | 24.35 | 919.94 | 1.174 | 0.043 | 0.000 | 0.000 |
FRONT_RETAIL | 12.02 | 24.35 | 919.94 | 0.977 | 0.043 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 24.058 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.04 | 8.18 | 2317.33 | 0.349 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.51 | 258.43 | 9762.95 | 0.679 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.02 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.02 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.04 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 127.51 | 258.43 | 9762.95 | 1600.48 | 1.8903 | 1.890 |
POINT_OF_SALE | PSZ-AC:3 | 12.02 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_RETAIL | PSZ-AC:4 | 12.02 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 156.53 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 2.492 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 5362551.04 | 0.00 | 5362551.04 | 1407559.32 | 6770110.36 | 7303124.67 | 3845.46 | 4008.32 | 906.22 | 5.41 |
CORE_RETAIL | 41138017.21 | 0.00 | 41138017.21 | 1206950.68 | 42344967.89 | 59613407.55 | 3841.96 | 3413.20 | 1504.84 | 51.82 |
POINT_OF_SALE | 5239351.60 | 0.00 | 5239351.60 | 641927.05 | 5881278.65 | 5617240.89 | 3834.51 | 3038.75 | 1886.74 | 57.18 |
FRONT_RETAIL | 4349853.14 | 0.00 | 4349853.14 | 641927.05 | 4991780.19 | 5617240.89 | 3841.18 | 3537.92 | 1380.90 | 17.83 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 8646702.41 | 8646702.41 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 56089773.00 | 0.00 | 56089773.00 | 12545066.51 | 68634839.50 | 78597979.65 | 8760.00 | 4013.34 | 1896.18 | 63.45 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.3030 | 0.0000 | 0.3030 | 0.0239 | 0.3269 | 0.2316 | 0.00 | 4008.32 | 904.68 |
CORE_RETAIL | 2.3171 | 0.0000 | 2.3171 | 0.0205 | 2.3376 | 1.8903 | 0.00 | 3413.04 | 1499.96 |
POINT_OF_SALE | 0.2945 | 0.0000 | 0.2945 | 0.0109 | 0.3054 | 0.1781 | 0.00 | 3038.42 | 1874.58 |
FRONT_RETAIL | 0.2454 | 0.0000 | 0.2454 | 0.0109 | 0.2563 | 0.1781 | 0.00 | 3537.75 | 1375.25 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.4824 | 0.4824 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 3.1600 | 0.0000 | 3.1600 | 0.5487 | 3.7086 | 2.4923 | 4913.00 | 4012.67 | 1883.28 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 7390180.66 | 0.00 | 7390180.66 | 7303124.67 | 3844.53 | 0.00 | 4915.47 | 5.41 |
PSZ-AC:2 | 56692115.40 | 0.00 | 56692115.40 | 59613407.55 | 3839.64 | 0.25 | 4920.11 | 51.66 |
PSZ-AC:3 | 7220427.27 | 0.00 | 7220427.27 | 5617240.89 | 3827.56 | 0.22 | 4932.22 | 57.18 |
PSZ-AC:4 | 5994654.87 | 0.00 | 5994654.87 | 5617240.89 | 3838.59 | 0.04 | 4921.37 | 17.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.4175 | 0.0000 | 0.4175 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 3.1932 | 0.0000 | 3.1932 | 1.8903 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.4059 | 0.0000 | 0.4059 | 0.1781 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.3382 | 0.0000 | 0.3382 | 0.1781 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 4593.87 | 324.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 4404.36 | 560.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 4145.18 | 825.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 4448.19 | 482.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.4037 | 0.6175 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 3.1553 | 3.5260 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.3923 | 0.4795 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.3289 | 0.4276 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 464 |
Defaulted Fields | 432 |
Fields with Defaults | 1357 |
Autosized Fields | 77 |
Autosizable Fields | 183 |
Autocalculated Fields | 78 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
Electricity:Building | 525.22 | 2914.09 | 21-MAY-08:00 | 38307.35 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 65.40 | 519.98 | 01-JAN-00:10 | 3841.56 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 525.22 | 2914.09 | 21-MAY-08:00 | 38307.35 | 02-JAN-09:10 |
InteriorLights:Electricity | 330.06 | 1118.91 | 21-MAY-08:00 | 27536.32 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 15.41 | 60.13 | 01-JAN-00:10 | 1082.42 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 330.06 | 1118.91 | 21-MAY-08:00 | 27536.32 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 330.06 | 1118.91 | 21-MAY-08:00 | 27536.32 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 15.41 | 60.13 | 01-JAN-00:10 | 1082.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 330.06 | 1118.91 | 21-MAY-08:00 | 27536.32 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 338.21 | 1597.18 | 21-MAY-08:00 | 26839.82 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 253.91 | 821.75 | 21-MAY-08:00 | 22187.22 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 253.91 | 821.75 | 21-MAY-08:00 | 22187.22 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 82.69 | 602.96 | 01-JAN-00:10 | 5011.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 37.71 | 189.21 | 01-JAN-00:10 | 2529.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
ElectricityPurchased:Plant | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
Cogeneration:ElectricityPurchased | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
General:Cogeneration:ElectricityPurchased | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
ElectricityNet:Plant | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
Cogeneration:ElectricityNet | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
General:Cogeneration:ElectricityNet | 834.77 | 3119.52 | 30-APR-07:00 | 74585.16 | 15-JUL-14:00 |
Electricity:HVAC | 241.03 | 0.00 | 01-JAN-01:00 | 48117.26 | 20-JUL-06:10 |
Fans:Electricity | 140.91 | 0.00 | 01-JAN-01:00 | 11874.97 | 20-JUL-06:10 |
General:Fans:Electricity | 140.91 | 0.00 | 01-JAN-01:00 | 11874.97 | 20-JUL-06:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 82.92 | 0.00 | 01-JAN-00:10 | 35679.76 | 20-JUL-06:10 |
General:Cooling:Electricity | 82.92 | 0.00 | 01-JAN-00:10 | 35679.76 | 20-JUL-06:10 |
ExteriorLights:Electricity | 68.53 | 0.00 | 01-JAN-08:00 | 5240.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 68.53 | 0.00 | 01-JAN-08:00 | 5240.87 | 01-JAN-06:10 |
HeatRecovery:Electricity | 17.20 | 0.00 | 01-JAN-00:10 | 1406.31 | 01-JAN-09:10 |
General:HeatRecovery:Electricity | 17.20 | 0.00 | 01-JAN-00:10 | 1406.31 | 01-JAN-09:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 492.33 | 1862.00 | 01-JAN-00:10 | 195078.66 | 07-FEB-07:10 |
NaturalGas:HVAC | 395.53 | 0.00 | 01-JAN-00:10 | 190616.52 | 07-FEB-07:10 |
Heating:NaturalGas | 395.53 | 0.00 | 01-JAN-00:10 | 190616.52 | 07-FEB-07:10 |
General:Heating:NaturalGas | 395.53 | 0.00 | 01-JAN-00:10 | 190616.52 | 07-FEB-07:10 |
NaturalGas:Plant | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.72 | 09-FEB-13:00 |
WaterSystems:NaturalGas | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.72 | 09-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.72 | 09-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1635.11 | 0.00 | 01-JAN-01:00 | 335749.88 | 07-FEB-07:10 |
EnergyTransfer:Building | 633.74 | 0.00 | 01-JAN-01:00 | 131417.46 | 07-FEB-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 85.03 | 0.00 | 01-JAN-00:10 | 29704.37 | 06-FEB-06:10 |
Heating:EnergyTransfer | 215.64 | 0.00 | 01-JAN-01:00 | 131417.46 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 57.06 | 0.00 | 01-JAN-00:10 | 29704.37 | 06-FEB-06:10 |
General:Heating:EnergyTransfer | 215.64 | 0.00 | 01-JAN-01:00 | 131417.46 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 57.06 | 0.00 | 01-JAN-00:10 | 29704.37 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 418.10 | 0.00 | 01-JAN-00:10 | 75898.64 | 21-JUL-13:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 27.97 | 0.00 | 01-JAN-00:10 | 10608.70 | 11-AUG-06:10 |
General:Cooling:EnergyTransfer | 418.10 | 0.00 | 01-JAN-00:10 | 75898.64 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 27.97 | 0.00 | 01-JAN-00:10 | 10608.70 | 11-AUG-06:10 |
EnergyTransfer:Zone:CORE_RETAIL | 314.89 | 0.00 | 01-JAN-00:10 | 75892.43 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 26.02 | 0.00 | 01-JAN-00:10 | 75892.43 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 26.02 | 0.00 | 01-JAN-00:10 | 75892.43 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 288.87 | 0.00 | 01-JAN-00:10 | 49415.55 | 21-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 288.87 | 0.00 | 01-JAN-00:10 | 49415.55 | 21-JUL-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 70.28 | 0.00 | 01-JAN-00:10 | 12883.96 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 7.73 | 0.00 | 01-JAN-00:10 | 12883.96 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 7.73 | 0.00 | 01-JAN-00:10 | 12883.96 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 62.55 | 0.00 | 01-JAN-00:10 | 11131.01 | 21-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 62.55 | 0.00 | 01-JAN-00:10 | 11131.01 | 21-SEP-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 52.83 | 0.00 | 01-JAN-00:10 | 13779.12 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 14.12 | 0.00 | 01-JAN-00:10 | 13779.12 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 14.12 | 0.00 | 01-JAN-00:10 | 13779.12 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 38.71 | 0.00 | 01-JAN-00:10 | 8966.69 | 21-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 38.71 | 0.00 | 01-JAN-00:10 | 8966.69 | 21-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 110.71 | 0.00 | 01-JAN-01:00 | 45701.00 | 06-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 110.71 | 0.00 | 01-JAN-01:00 | 45701.00 | 06-FEB-18:00 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 110.71 | 0.00 | 01-JAN-01:00 | 45701.00 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 92.51 | 22-OCT-08:50 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 92.51 | 22-OCT-08:50 |
EnergyTransfer:HVAC | 1001.37 | 0.00 | 01-JAN-00:10 | 216478.62 | 07-FEB-07:10 |
HeatingCoils:EnergyTransfer | 316.42 | 0.00 | 01-JAN-00:10 | 152493.22 | 07-FEB-07:10 |
CoolingCoils:EnergyTransfer | 312.54 | 0.00 | 01-JAN-00:10 | 154982.78 | 20-JUL-06:10 |
HeatRecoveryForHeating:EnergyTransfer | 352.57 | 0.00 | 01-JAN-00:10 | 65907.59 | 11-DEC-20:00 |
HeatRecoveryForCooling:EnergyTransfer | 19.84 | 0.00 | 01-JAN-00:10 | 31659.33 | 20-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 57.065 | -27.965 | 0.000 | 0.000 | 5.397 | 15.409 | 49.992 | 0.000 | 0.000 | 0.141 | 0.002 | 0.000 | 0.000 | 0.000 | -22.747 | -77.292 |
CORE_RETAIL | 0.000 | 0.000 | 26.022 | -288.869 | 0.000 | 0.000 | 162.206 | 253.909 | 84.300 | 51.136 | 0.000 | 0.118 | 0.008 | 0.000 | -27.762 | 0.000 | -22.060 | -238.998 |
POINT_OF_SALE | 0.000 | 0.000 | 7.725 | -62.553 | 0.000 | 0.000 | 15.525 | 29.762 | 52.923 | 36.642 | 0.000 | 0.061 | 0.000 | 0.000 | -20.101 | 0.000 | -11.135 | -48.849 |
FRONT_RETAIL | 0.000 | 0.000 | 14.119 | -38.714 | 0.000 | 0.000 | 15.776 | 29.762 | 7.943 | 36.694 | 0.000 | 0.062 | 0.002 | 0.000 | -19.525 | 0.000 | -10.709 | -35.407 |
FRONT_ENTRY | 110.706 | -0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.275 | 1.215 | 0.000 | 7.423 | 0.000 | 0.006 | 0.000 | 0.000 | -3.949 | 0.000 | -115.267 | -1.410 |
Total Facility | 110.706 | -0.000 | 104.931 | -418.101 | 0.000 | 0.000 | 200.180 | 330.058 | 195.158 | 131.894 | 0.000 | 0.387 | 0.012 | 0.000 | -71.338 | 0.000 | -181.918 | -401.957 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-AUG-06:02 | 0.00 | 0.00 | 0.00 | -31700.83 | 0.00 | 0.00 | 53.14 | 240.53 | 1226.28 | 0.00 | 0.00 | 0.00 | 30196.42 | 0.00 | -0.00 | 0.00 | -15.55 | 0.00 |
CORE_RETAIL | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | -202348.54 | 0.00 | 0.00 | 1633.00 | 1643.50 | 1550.87 | 4643.83 | 0.00 | 0.00 | 192975.09 | 0.00 | -0.00 | 0.00 | -97.73 | 0.00 |
POINT_OF_SALE | 03-AUG-06:02 | 0.00 | 0.00 | 0.00 | -27636.80 | 0.00 | 0.00 | 150.38 | 464.59 | 1298.17 | 0.00 | 0.00 | 0.00 | 26415.76 | 0.00 | -604.85 | 0.00 | -87.25 | 0.00 |
FRONT_RETAIL | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | -21094.36 | 0.00 | 0.00 | 153.13 | 464.59 | 194.85 | 0.00 | 0.00 | 0.00 | 21177.22 | 0.00 | -814.52 | 0.00 | -80.92 | 0.00 |
FRONT_ENTRY | 22-OCT-08:50 | 0.00 | -92.51 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 9.49 | 0.00 | 826.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -515.18 | -244.10 |
Total Facility | 02-AUG-06:02 | 0.00 | 0.00 | 0.00 | -254516.18 | 0.00 | 0.00 | 1971.06 | 6119.17 | 4787.13 | 0.00 | 0.00 | 0.00 | 243571.40 | 0.00 | -1932.58 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 07-FEB-05:32 | 0.00 | 0.00 | 46527.55 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5235.05 | -41965.76 |
CORE_RETAIL | 13-FEB-06:01 | 0.00 | 0.00 | 261765.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.62 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2376.70 | 0.00 | -1718.10 | -259936.75 |
POINT_OF_SALE | 13-FEB-05:11 | 0.00 | 0.00 | 36374.61 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1728.38 | 0.00 | -3072.39 | -32339.08 |
FRONT_RETAIL | 07-FEB-05:11 | 0.00 | 0.00 | 31668.15 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2155.39 | 0.00 | -2313.15 | -27413.18 |
FRONT_ENTRY | 06-FEB-18:00 | 45700.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -514.05 | 0.00 | -45204.63 | -146.65 |
Total Facility | 10-DEC-08:61 | 8583.39 | 0.00 | 372875.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.79 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2504.02 | 0.00 | -7381.77 | -374897.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5364 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.5364 | 0.1697 | 1.0000 | Not calculated | 0.2316 | 0.1507 | ||
PSZ-AC:2 | 7.6288 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.8532 | 0.2407 | 1.0000 | Not calculated | 1.8903 | 0.2407 | ||
PSZ-AC:3 | 1.2443 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2443 | 0.1431 | 1.0000 | Not calculated | 0.1781 | 0.1431 | ||
PSZ-AC:4 | 1.0226 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0226 | 0.1742 | 1.0000 | Not calculated | 0.1781 | 0.1742 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5364 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.5364 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.1507 | ||
PSZ-AC:2 | 7.6288 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.6288 | 1.0000 | 1.0000 | Not calculated | 1.8903 | 0.2478 | ||
PSZ-AC:3 | 1.2443 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2443 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1431 | ||
PSZ-AC:4 | 1.0226 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0226 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1742 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8903 | 1.0000 | 1.8903 | 1.000 | 1.8903 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8903 | 1.8903 | 1.8903 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5364 | 1.5364 | 1.5364 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6288 | 7.6288 | 7.6288 | No | 1.8903 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2443 | 1.2443 | 1.2443 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0226 | 1.0226 | 1.0226 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5364 | 1.5364 | 1.5364 | 1.5364 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6288 | 7.8532 | 7.6288 | 7.6288 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.2443 | 1.2443 | 1.2443 | 1.2443 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0226 | 1.0226 | 1.0226 | 1.0226 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5364 | 1.5364 | 1.5364 | No | 0.2316 | 0.1507 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6288 | 7.6288 | 7.6288 | No | 1.8903 | 0.5715 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2443 | 1.2443 | 1.2443 | No | 0.1781 | 0.2377 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0226 | 1.0226 | 1.0226 | No | 0.1781 | 0.2378 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5364 | 1.5364 | 1.5364 | 1.5364 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6288 | 7.6288 | 7.6288 | 7.6288 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.2443 | 1.2443 | 1.2443 | 1.2443 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0226 | 1.0226 | 1.0226 | 1.0226 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 21.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 21.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 395.53 | 190616.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 82.92 | 35679.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 330.06 | 27536.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 68.53 | 5240.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 140.91 | 11874.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 17.20 | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 96.80 | 5271.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 834.77 |
Natural Gas | 0.00 | 492.33 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1327.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 143.88 |
Space Heating | 0.00 |
Space Cooling | 36.14 |
Fans (All) | 61.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 363.90 |
Subtotal | 363.90 |
Natural Gas [MJ/m2] | |
Space Heating | 172.42 |
Service Water Heating | 42.20 |
Miscellaneous (All) | 214.62 |
Subtotal | 214.62 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.87 |
Space Heating | 29.80 |
Space Cooling | 6.25 |
Fans (All) | 10.62 |
Service Water Heating | 7.29 |
Receptacle Equipment | 14.71 |
Miscellaneous | 6.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 1677. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | FRONT_ENTRY HEATING SP | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8676.17 | 83.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 8387.33 | 365.00 | 7.67 | 0.00 | 0.00 |
Min | 8387.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 365.00 | 7.67 | 0.00 | 0.00 |
Average | 8666.20 | 92.27 | 1.53 | 0.00 | 0.00 |
Sum | 43331.00 | 461.33 | 7.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1783.33 | 129.83 | 6.83 | 0.00 | 0.00 |
Min | 1783.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 129.83 | 6.83 | 0.00 | 0.00 |
Average | 148050.87 | 25.97 | 1.37 | 0.00 | 0.00 |
Sum | 740254.33 | 129.83 | 6.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 8200.67 | 559.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8249.33 | 510.67 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8165.67 | 594.33 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8174.50 | 585.50 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 7646.67 | 1113.33 | 0.00 | 0.00 | 0.00 |
Min | 7646.67 | 510.67 | 0.00 | 0.00 | 0.00 |
Max | 8249.33 | 1113.33 | 0.00 | 0.00 | 0.00 |
Average | 8087.37 | 672.63 | 0.00 | 0.00 | 0.00 |
Sum | 40436.83 | 3363.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16324.00 | 548.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 595936.33 | 13662.67 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 55460.17 | 539.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 54662.33 | 1337.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1663.83 | 256.17 | 0.00 | 0.00 | 0.00 |
Min | 1663.83 | 256.17 | 0.00 | 0.00 | 0.00 |
Max | 595936.33 | 13662.67 | 0.00 | 0.00 | 0.00 |
Average | 144809.33 | 3268.87 | 0.00 | 0.00 | 0.00 |
Sum | 724046.67 | 16344.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 8760.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 8760.00 |
Average | 0.00 | 0.00 | 0.00 | 1752.00 |
Sum | 0.00 | 0.00 | 0.00 | 8760.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 609599.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 609599.00 |
Average | 0.00 | 0.00 | 0.00 | 121919.80 |
Sum | 0.00 | 0.00 | 0.00 | 609599.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 844753.93 | 3352.28 | 18-JAN-07:05 | 2.80 | 1.63 | 0.220220E+09 | 247.24 | 30-JAN-15:00 | -9.4 | -11.1 |
February | 65630.92 | 437.54 | 23-FEB-07:05 | 2.80 | 2.05 | 0.201090E+09 | 247.24 | 13-FEB-15:30 | 2.80 | 2.05 |
March | 0.237729E+09 | 5045.69 | 19-MAR-08:05 | 1.47 | 0.12 | 0.234739E+09 | 326.80 | 15-MAR-14:09 | 1.47 | 0.12 |
April | 0.744244E+09 | 6089.92 | 03-APR-06:05 | -2.8 | -3.4 | 0.221030E+09 | 297.85 | 08-APR-14:39 | 19.80 | 13.32 |
May | 0.189368E+10 | 4959.43 | 01-MAY-06:05 | 2.35 | 1.71 | 0.263280E+09 | 330.12 | 10-MAY-14:30 | 26.10 | 18.02 |
June | 0.479187E+10 | 26048.92 | 28-JUN-06:02 | 17.30 | 15.24 | 0.291336E+09 | 326.82 | 27-JUN-14:00 | 17.30 | 15.24 |
July | 0.753583E+10 | 31381.33 | 12-JUL-06:02 | 14.37 | 11.81 | 0.291670E+09 | 326.82 | 11-JUL-14:39 | 14.37 | 11.81 |
August | 0.693622E+10 | 31711.84 | 01-AUG-06:02 | 11.57 | 10.94 | 0.303970E+09 | 326.82 | 15-AUG-14:09 | 25.63 | 21.97 |
September | 0.364073E+10 | 22768.71 | 15-SEP-06:02 | 18.30 | 16.87 | 0.280640E+09 | 326.82 | 16-SEP-13:09 | 27.20 | 19.53 |
October | 0.186153E+10 | 6206.09 | 17-OCT-06:05 | -2.8 | -3.4 | 0.236307E+09 | 326.73 | 05-OCT-14:00 | -2.8 | -3.4 |
November | 0.317112E+09 | 5624.00 | 15-NOV-07:05 | -0.6 | -1.0 | 0.212794E+09 | 270.93 | 04-NOV-15:00 | -0.6 | -1.0 |
December | 5256943.63 | 5023.48 | 03-DEC-09:05 | 1.10 | -1.3 | 0.220554E+09 | 247.24 | 26-DEC-15:39 | -9.4 | -10.9 |
Annual Sum or Average | 0.279651E+11 | 0.297763E+10 | ||||||||
Minimum of Months | 65630.92 | 437.54 | -2.8 | -3.4 | 0.201090E+09 | 247.24 | -9.4 | -11.1 | ||
Maximum of Months | 0.753583E+10 | 31711.84 | 18.30 | 16.87 | 0.303970E+09 | 330.12 | 27.20 | 21.97 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.671366E+10 | 19583.74 | 04-JAN-07:05 | -12.9 | -13.7 | 0.712292E+10 | 9306.46 | 11-JAN-15:00 | 11.70 | 10.14 |
February | 0.619701E+10 | 21475.88 | 07-FEB-07:05 | -16.5 | -17.1 | 0.648761E+10 | 9365.76 | 18-FEB-15:00 | 2.20 | -0.3 |
March | 0.119363E+11 | 66949.52 | 16-MAR-06:03 | 11.93 | 10.48 | 0.854883E+10 | 10327.69 | 16-MAR-14:30 | 19.15 | 15.51 |
April | 0.156432E+11 | 28144.53 | 29-APR-16:50 | 8.98 | 7.78 | 0.884925E+10 | 10327.49 | 08-APR-14:09 | 8.98 | 7.78 |
May | 0.293218E+11 | 166155.49 | 28-MAY-08:62 | 18.22 | 13.22 | 0.939361E+10 | 10327.68 | 13-MAY-14:09 | 18.22 | 13.22 |
June | 0.443579E+11 | 202360.19 | 04-JUN-08:62 | 13.07 | 8.22 | 0.927877E+10 | 10327.95 | 19-JUN-14:09 | 22.88 | 17.85 |
July | 0.508045E+11 | 170744.90 | 06-JUL-06:02 | 13.07 | 10.52 | 0.921924E+10 | 10327.94 | 01-JUL-12:50 | 13.07 | 10.52 |
August | 0.489158E+11 | 185075.24 | 03-AUG-06:02 | 11.57 | 9.86 | 0.961410E+10 | 10327.94 | 26-AUG-13:50 | 25.00 | 21.45 |
September | 0.362186E+11 | 188060.20 | 11-SEP-06:02 | 11.70 | 9.59 | 0.908592E+10 | 10327.88 | 16-SEP-11:39 | 26.50 | 19.52 |
October | 0.199381E+11 | 141209.56 | 12-OCT-06:02 | 13.90 | 11.93 | 0.911542E+10 | 10327.81 | 12-OCT-14:00 | 18.30 | 15.23 |
November | 0.110130E+11 | 27236.23 | 01-NOV-15:50 | 9.40 | 6.80 | 0.838060E+10 | 10327.17 | 10-NOV-15:39 | 8.17 | 5.61 |
December | 0.781131E+10 | 21474.21 | 11-DEC-07:05 | -16.4 | -16.9 | 0.734889E+10 | 10327.17 | 01-DEC-15:20 | -16.4 | -16.9 |
Annual Sum or Average | 0.288871E+12 | 0.102445E+12 | ||||||||
Minimum of Months | 0.619701E+10 | 19583.74 | -16.5 | -17.1 | 0.648761E+10 | 9306.46 | -16.4 | -16.9 | ||
Maximum of Months | 0.508045E+11 | 202360.19 | 18.22 | 13.22 | 0.961410E+10 | 10327.95 | 26.50 | 21.45 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129031E+10 | 4743.91 | 09-JAN-16:42 | -5.5 | -7.0 | 0.656541E+09 | 778.62 | 11-JAN-15:00 | 11.70 | 10.14 |
February | 0.127711E+10 | 5241.80 | 13-FEB-12:23 | -8.1 | -8.5 | 0.603468E+09 | 886.28 | 22-FEB-15:00 | 10.60 | 5.02 |
March | 0.360820E+10 | 8945.83 | 16-MAR-06:03 | 11.93 | 10.48 | 0.760103E+09 | 973.19 | 16-MAR-14:00 | 19.40 | 15.86 |
April | 0.405301E+10 | 6824.43 | 22-APR-14:20 | 15.60 | 7.13 | 0.786783E+09 | 973.14 | 08-APR-14:30 | 15.60 | 7.13 |
May | 0.554270E+10 | 21071.85 | 24-MAY-06:02 | 18.03 | 15.62 | 0.875976E+09 | 973.19 | 30-MAY-14:20 | 17.80 | 14.42 |
June | 0.798519E+10 | 23911.16 | 20-JUN-06:02 | 13.77 | 12.90 | 0.873438E+09 | 973.26 | 12-JUN-14:20 | 13.77 | 12.90 |
July | 0.982423E+10 | 25060.76 | 13-JUL-06:02 | 13.07 | 11.71 | 0.868708E+09 | 973.26 | 29-JUL-14:20 | 25.60 | 21.33 |
August | 0.102303E+11 | 27643.76 | 03-AUG-06:02 | 11.57 | 9.86 | 0.905862E+09 | 973.23 | 05-AUG-14:20 | 29.80 | 17.31 |
September | 0.831878E+10 | 26793.73 | 11-SEP-06:02 | 11.70 | 9.59 | 0.854637E+09 | 973.27 | 16-SEP-12:00 | 27.20 | 19.47 |
October | 0.552581E+10 | 25522.86 | 12-OCT-06:02 | 13.90 | 11.93 | 0.839513E+09 | 973.20 | 12-OCT-14:00 | 18.30 | 15.23 |
November | 0.351873E+10 | 6416.78 | 01-NOV-12:00 | 11.10 | 6.28 | 0.723475E+09 | 973.14 | 04-NOV-14:00 | 18.30 | 13.74 |
December | 0.137901E+10 | 5507.33 | 10-DEC-11:23 | -9.4 | -10.4 | 0.663619E+09 | 944.22 | 16-DEC-14:20 | 5.40 | 2.79 |
Annual Sum or Average | 0.625533E+11 | 0.941212E+10 | ||||||||
Minimum of Months | 0.127711E+10 | 4743.91 | -9.4 | -10.4 | 0.603468E+09 | 778.62 | 5.40 | 2.79 | ||
Maximum of Months | 0.102303E+11 | 27643.76 | 18.03 | 15.62 | 0.905862E+09 | 973.27 | 29.80 | 21.33 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231150E+09 | 4001.93 | 16-JAN-09:05 | -0.9 | -2.2 | 0.655735E+09 | 736.18 | 23-JAN-15:09 | -7.9 | -9.0 |
February | 0.320425E+09 | 5365.19 | 07-FEB-13:32 | -7.9 | -9.6 | 0.598883E+09 | 758.11 | 22-FEB-15:39 | 10.60 | 4.98 |
March | 0.184635E+10 | 5335.78 | 15-MAR-13:40 | 25.73 | 15.91 | 0.718579E+09 | 973.14 | 15-MAR-14:00 | 25.60 | 16.24 |
April | 0.237392E+10 | 4646.23 | 03-APR-06:05 | -2.8 | -3.4 | 0.728491E+09 | 973.14 | 08-APR-14:09 | 20.40 | 13.67 |
May | 0.320276E+10 | 7877.89 | 24-MAY-06:02 | 18.03 | 15.62 | 0.848437E+09 | 973.17 | 10-MAY-14:00 | 18.03 | 15.62 |
June | 0.522871E+10 | 17205.78 | 28-JUN-06:02 | 17.30 | 15.24 | 0.869765E+09 | 973.20 | 21-JUN-14:00 | 17.30 | 15.24 |
July | 0.697489E+10 | 18926.62 | 12-JUL-06:02 | 14.37 | 11.81 | 0.868438E+09 | 973.20 | 27-JUL-14:09 | 29.40 | 19.92 |
August | 0.726976E+10 | 20806.10 | 01-AUG-06:02 | 11.57 | 10.94 | 0.905201E+09 | 973.25 | 09-AUG-14:09 | 29.40 | 18.10 |
September | 0.565579E+10 | 21102.34 | 22-SEP-06:02 | 12.80 | 11.44 | 0.847792E+09 | 973.24 | 16-SEP-13:20 | 12.80 | 11.44 |
October | 0.353916E+10 | 12207.16 | 12-OCT-06:02 | 13.90 | 11.93 | 0.786541E+09 | 973.20 | 12-OCT-14:00 | 18.30 | 15.23 |
November | 0.178239E+10 | 4262.63 | 15-NOV-07:05 | -0.6 | -1.0 | 0.676041E+09 | 973.09 | 16-NOV-15:09 | 17.20 | 13.33 |
December | 0.289539E+09 | 4344.00 | 04-DEC-18:53 | -2.8 | -4.7 | 0.657426E+09 | 802.30 | 16-DEC-14:09 | 5.50 | 2.82 |
Annual Sum or Average | 0.387148E+11 | 0.916133E+10 | ||||||||
Minimum of Months | 0.231150E+09 | 4001.93 | -7.9 | -9.6 | 0.598883E+09 | 736.18 | -7.9 | -9.0 | ||
Maximum of Months | 0.726976E+10 | 21102.34 | 25.73 | 15.91 | 0.905201E+09 | 973.25 | 29.40 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 52129712.14 | 58.59 | 28-JAN-16:00 | -6.7 | -8.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 47604826.80 | 58.59 | 11-FEB-16:00 | 0.00 | -2.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 55858598.93 | 96.79 | 15-MAR-14:09 | 26.02 | 16.09 |
April | 7672.87 | 11.42 | 07-APR-05:05 | 10.60 | 5.48 | 51660180.55 | 68.08 | 08-APR-11:09 | 19.40 | 12.82 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 56126269.78 | 95.53 | 10-MAY-14:20 | 26.10 | 17.96 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 67210018.93 | 132.44 | 12-JUN-14:09 | 30.50 | 20.19 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 81309926.61 | 142.90 | 21-JUL-14:09 | 31.52 | 21.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 81331285.73 | 133.93 | 10-AUG-14:09 | 30.50 | 20.17 |
September | 19896.81 | 33.16 | 04-SEP-09:00 | 16.70 | 13.10 | 60378266.83 | 106.91 | 16-SEP-13:50 | 27.20 | 19.76 |
October | 111912.26 | 92.51 | 22-OCT-08:50 | 17.43 | 11.54 | 53198571.92 | 73.78 | 11-OCT-14:00 | 17.43 | 11.54 |
November | 107788.49 | 38.14 | 05-NOV-08:40 | 18.13 | 13.74 | 50244162.31 | 58.60 | 04-NOV-10:09 | 18.13 | 13.74 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 52209013.21 | 58.59 | 16-DEC-16:00 | 3.30 | 1.70 |
Annual Sum or Average | 247270.42 | 0.709261E+09 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 47604826.80 | 58.59 | -6.7 | -8.3 | ||
Maximum of Months | 111912.26 | 92.51 | 18.85 | 16.93 | 81331285.73 | 142.90 | 31.52 | 21.93 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150495E+11 | 45755.55 | 30-JAN-05:11 | -9.6 |
February | 0.144934E+11 | 46527.52 | 07-FEB-05:32 | -15.9 |
March | 0.821885E+10 | 45459.61 | 06-MAR-06:01 | -11.1 |
April | 0.234045E+10 | 45208.97 | 17-APR-05:01 | -4.0 |
May | 0.157206E+09 | 35338.87 | 01-MAY-06:03 | 2.35 |
June | 61513304.57 | 985.28 | 18-JUN-08:20 | 24.60 |
July | 57651177.73 | 1158.13 | 16-JUL-08:20 | 24.97 |
August | 63695346.13 | 644.70 | 14-AUG-06:20 | 22.97 |
September | 63419049.87 | 1129.31 | 30-SEP-06:10 | 7.30 |
October | 0.593462E+09 | 44800.72 | 30-OCT-05:02 | -0.1 |
November | 0.306558E+10 | 45284.86 | 25-NOV-06:01 | -1.7 |
December | 0.128997E+11 | 45832.15 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.570645E+11 | |||
Minimum of Months | 57651177.73 | 644.70 | -15.9 | |
Maximum of Months | 0.150495E+11 | 46527.52 | 24.97 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.737770E+10 | 261012.28 | 10-JAN-06:01 | -13.0 |
February | 0.719440E+10 | 261764.76 | 13-FEB-06:01 | -9.4 |
March | 0.215815E+10 | 260205.08 | 08-MAR-06:01 | -11.3 |
April | 0.561712E+09 | 111063.21 | 17-APR-06:03 | -4.2 |
May | 0.529605E+09 | 5170.00 | 17-MAY-06:05 | 18.40 |
June | 0.410724E+09 | 7479.19 | 18-JUN-08:20 | 24.60 |
July | 0.273584E+09 | 7675.88 | 16-JUL-08:08 | 24.68 |
August | 0.325865E+09 | 6176.00 | 11-AUG-05:07 | 17.80 |
September | 0.486742E+09 | 6288.92 | 17-SEP-08:06 | 21.70 |
October | 0.530800E+09 | 5166.79 | 22-OCT-07:01 | 14.18 |
November | 0.710959E+09 | 154518.76 | 24-NOV-07:03 | -3.2 |
December | 0.546258E+10 | 260984.91 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.260228E+11 | |||
Minimum of Months | 0.273584E+09 | 5166.79 | -13.0 | |
Maximum of Months | 0.737770E+10 | 261764.76 | 24.68 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221389E+10 | 35831.27 | 10-JAN-06:01 | -13.0 |
February | 0.234534E+10 | 36374.57 | 13-FEB-05:11 | -9.1 |
March | 0.654467E+09 | 35575.38 | 07-MAR-05:01 | -13.3 |
April | 0.198003E+09 | 35346.64 | 17-APR-05:01 | -4.0 |
May | 49711602.05 | 529.95 | 11-MAY-06:00 | 13.90 |
June | 32576910.11 | 937.37 | 18-JUN-08:06 | 24.50 |
July | 20244144.83 | 1009.42 | 20-JUL-05:05 | 23.90 |
August | 18173105.41 | 1033.58 | 15-AUG-05:05 | 22.70 |
September | 38830417.15 | 783.73 | 17-SEP-07:05 | 22.12 |
October | 62436951.12 | 16354.69 | 30-OCT-05:02 | -0.1 |
November | 0.236469E+09 | 35494.23 | 25-NOV-06:01 | -1.7 |
December | 0.185513E+10 | 35648.71 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.772526E+10 | |||
Minimum of Months | 18173105.41 | 529.95 | -13.3 | |
Maximum of Months | 0.234534E+10 | 36374.57 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399666E+10 | 30936.66 | 09-JAN-05:11 | -9.4 |
February | 0.395657E+10 | 31668.11 | 07-FEB-05:11 | -15.8 |
March | 0.127098E+10 | 30811.74 | 07-MAR-05:01 | -13.3 |
April | 0.456224E+09 | 30734.21 | 17-APR-05:01 | -4.0 |
May | 50289111.58 | 12413.27 | 01-MAY-06:03 | 2.35 |
June | 39889658.04 | 827.10 | 18-JUN-08:06 | 24.50 |
July | 32038769.06 | 668.36 | 20-JUL-05:05 | 23.90 |
August | 34465789.30 | 531.69 | 15-AUG-05:05 | 22.70 |
September | 40242841.47 | 454.36 | 19-SEP-06:00 | 10.60 |
October | 0.115706E+09 | 30224.28 | 30-OCT-05:02 | -0.1 |
November | 0.558844E+09 | 30751.92 | 25-NOV-06:01 | -1.7 |
December | 0.356705E+10 | 30986.08 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.141190E+11 | |||
Minimum of Months | 32038769.06 | 454.36 | -17.8 | |
Maximum of Months | 0.399666E+10 | 31668.11 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218641E+11 | 42255.89 | 31-JAN-18:00 | -12.2 |
February | 0.203903E+11 | 45701.00 | 06-FEB-18:00 | -14.4 |
March | 0.147288E+11 | 37048.18 | 06-MAR-18:00 | -8.3 |
April | 0.863995E+10 | 29351.92 | 16-APR-11:10 | -3.1 |
May | 0.337338E+10 | 13690.23 | 11-MAY-17:00 | 8.90 |
June | 0.827565E+09 | 11984.72 | 13-JUN-11:10 | 10.00 |
July | 9847950.18 | 2867.60 | 02-JUL-11:05 | 18.48 |
August | 0.192769E+09 | 6769.42 | 31-AUG-11:10 | 14.60 |
September | 0.124360E+10 | 11549.40 | 28-SEP-17:00 | 10.60 |
October | 0.718891E+10 | 19612.61 | 08-OCT-17:00 | 4.40 |
November | 0.112855E+11 | 24813.54 | 23-NOV-18:00 | 0.60 |
December | 0.209621E+11 | 43307.42 | 10-DEC-18:00 | -12.8 |
Annual Sum or Average | 0.110707E+12 | |||
Minimum of Months | 9847950.18 | 2867.60 | -14.4 | |
Maximum of Months | 0.218641E+11 | 45701.00 | 18.48 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129219E+10 | 1082.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.117572E+10 | 1082.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.134112E+10 | 1082.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.126535E+10 | 1082.42 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.131665E+10 | 1082.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.129414E+10 | 1082.42 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.128786E+10 | 1082.42 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.134112E+10 | 1082.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.126535E+10 | 1082.42 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.129219E+10 | 1082.42 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.124954E+10 | 1082.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.128786E+10 | 1082.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.154091E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.117572E+10 | 1082.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.134112E+10 | 1082.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.244497E+11 | 22187.22 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.201827E+11 | 22187.22 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.224554E+11 | 22187.22 | 01-MAR-15:00 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.191911E+11 | 22187.22 | 07-APR-16:00 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.198306E+11 | 22187.22 | 11-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.189251E+11 | 20338.28 | 01-JUN-16:40 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.187842E+11 | 20338.28 | 03-JUL-16:49 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.197348E+11 | 22187.22 | 28-AUG-16:10 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.203150E+11 | 22187.22 | 01-SEP-16:00 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.226371E+11 | 22187.22 | 02-OCT-16:40 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.229516E+11 | 22187.22 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.244517E+11 | 22187.22 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.253909E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.187842E+11 | 20338.28 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.244517E+11 | 22187.22 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.244397E+10 | 2090.65 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.249958E+10 | 2090.65 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.244397E+10 | 2090.65 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.244397E+10 | 2090.65 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.249958E+10 | 2090.65 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.244397E+10 | 2090.65 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.101920E+09 | 85.37 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 92733309.19 | 85.37 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.105778E+09 | 85.37 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 99802281.75 | 85.37 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.103849E+09 | 85.37 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.102073E+09 | 85.37 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.101578E+09 | 85.37 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.105778E+09 | 85.37 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 99802281.75 | 85.37 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.101920E+09 | 85.37 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 98555820.41 | 85.37 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.101578E+09 | 85.37 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121537E+10 | 0.00 | 0.00 | ||
Minimum of Months | 92733309.19 | 85.37 | 0.00 | 0.00 | |
Maximum of Months | 0.105778E+09 | 85.37 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.129219E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372789E+10 |
February | 0.638757E+09 | 0.117572E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396269E+10 |
March | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1804970.42 | 0.238930E+10 |
April | 0.690691E+09 | 0.126535E+10 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185193E+10 |
May | 0.715069E+09 | 0.131665E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102740.23 | 0.102744E+10 |
June | 0.705176E+09 | 0.129414E+10 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28800475.23 | 0.710758E+09 |
July | 0.700584E+09 | 0.128786E+10 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61566761.71 | 0.386484E+09 |
August | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43710954.44 | 0.477764E+09 |
September | 0.690691E+09 | 0.126535E+10 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3598376.82 | 0.702073E+09 |
October | 0.699524E+09 | 0.129219E+10 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148212E+10 |
November | 0.673027E+09 | 0.124954E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211066E+10 |
December | 0.700584E+09 | 0.128786E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391772E+10 |
Annual Sum or Average | 0.837485E+10 | 0.154091E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140584E+09 | 0.227468E+11 |
Minimum of Months | 0.638757E+09 | 0.117572E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386484E+09 |
Maximum of Months | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61566761.71 | 0.396269E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.244497E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346604E+10 |
February | 0.201852E+11 | 0.201827E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365667E+10 |
March | 0.230879E+11 | 0.224554E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 920712.02 | 0.232787E+10 |
April | 0.218263E+11 | 0.191911E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193782E+10 |
May | 0.225967E+11 | 0.198306E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939228.76 | 0.109085E+10 |
June | 0.222841E+11 | 0.189251E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24507518.46 | 0.691186E+09 |
July | 0.221389E+11 | 0.187842E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51741094.64 | 0.374039E+09 |
August | 0.230879E+11 | 0.197348E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37067739.06 | 0.453325E+09 |
September | 0.218263E+11 | 0.203150E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3085190.33 | 0.684901E+09 |
October | 0.221054E+11 | 0.226371E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154560E+10 |
November | 0.212681E+11 | 0.229516E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215903E+10 |
December | 0.221389E+11 | 0.244517E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367288E+10 |
Annual Sum or Average | 0.264651E+12 | 0.253909E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118261E+09 | 0.220602E+11 |
Minimum of Months | 0.201852E+11 | 0.187842E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374039E+09 |
Maximum of Months | 0.230879E+11 | 0.244517E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51741094.64 | 0.367288E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173366E+10 |
February | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183605E+10 |
March | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489472.85 | 0.117253E+10 |
April | 0.205665E+10 | 0.244397E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952671E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499303.40 | 0.552037E+09 |
June | 0.209978E+10 | 0.249958E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12958592.12 | 0.364558E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25895139.42 | 0.211617E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19307970.08 | 0.258268E+09 |
September | 0.205665E+10 | 0.244397E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640627.88 | 0.369057E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799260E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106521E+10 |
December | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182039E+10 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60791105.75 | 0.111353E+11 |
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211617E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25895139.42 | 0.183605E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170751E+10 |
February | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181342E+10 |
March | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489589.60 | 0.112776E+10 |
April | 0.205665E+10 | 0.244397E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897778E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499357.57 | 0.512737E+09 |
June | 0.209978E+10 | 0.249958E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13001386.49 | 0.337104E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26715383.02 | 0.189445E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19411890.54 | 0.236342E+09 |
September | 0.205665E+10 | 0.244397E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1640824.78 | 0.345506E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747974E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100667E+10 |
December | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178703E+10 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61758432.00 | 0.107093E+11 |
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189445E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26715383.02 | 0.181342E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.101920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214749E+11 |
February | 0.151369E+09 | 92733309.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200425E+11 |
March | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149762E+11 |
April | 0.163676E+09 | 99802281.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916898E+10 |
May | 0.169453E+09 | 0.103849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414339E+10 |
June | 0.167108E+09 | 0.102073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088439.25 | 0.152493E+10 |
July | 0.166020E+09 | 0.101578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3597374.12 | 0.520538E+09 |
August | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125976.30 | 0.848926E+09 |
September | 0.163676E+09 | 99802281.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225671E+10 |
October | 0.165769E+09 | 0.101920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803650E+10 |
November | 0.159490E+09 | 98555820.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116337E+11 |
December | 0.166020E+09 | 0.101578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206396E+11 |
Annual Sum or Average | 0.198462E+10 | 0.121537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5811789.67 | 0.115267E+12 |
Minimum of Months | 0.151369E+09 | 92733309.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520538E+09 |
Maximum of Months | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3597374.12 | 0.214749E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 1082.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7493.36 | 12-JAN-05:50 |
February | 785.10 | 01-FEB-15:09 | 1082.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7886.15 | 13-FEB-06:00 |
March | 785.10 | 01-MAR-15:09 | 1082.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.05 | 14-MAR-14:00 | 4185.02 | 02-MAR-05:05 |
April | 785.10 | 01-APR-10:09 | 1082.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4201.78 | 16-APR-06:55 |
May | 785.10 | 01-MAY-14:09 | 1082.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 14-MAY-15:00 | 1878.53 | 05-MAY-21:00 |
June | 785.10 | 01-JUN-14:09 | 1082.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 298.88 | 12-JUN-13:00 | 2247.49 | 13-JUN-03:00 |
July | 785.10 | 01-JUL-10:09 | 1082.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 448.35 | 21-JUL-03:00 | 1588.12 | 06-JUL-02:00 |
August | 785.10 | 01-AUG-14:09 | 1082.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 373.52 | 13-AUG-18:03 | 1171.99 | 30-AUG-20:10 |
September | 785.10 | 01-SEP-14:09 | 1082.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.26 | 16-SEP-13:00 | 1808.40 | 29-SEP-04:00 |
October | 785.10 | 02-OCT-14:09 | 1082.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2092.60 | 07-OCT-02:00 |
November | 785.10 | 01-NOV-14:09 | 1082.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3816.08 | 17-NOV-02:00 |
December | 785.10 | 01-DEC-15:09 | 1082.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6231.86 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 1082.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.99 | |||||
Maximum of Months | 785.10 | 1082.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 448.35 | 7886.15 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22187.22 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6689.84 | 12-JAN-02:00 |
February | 24809.68 | 01-FEB-15:09 | 22187.22 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6834.59 | 13-FEB-06:00 |
March | 24809.68 | 01-MAR-15:09 | 22187.22 | 01-MAR-15:00 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 | 15-MAR-14:00 | 4179.31 | 02-MAR-01:00 |
April | 24809.68 | 01-APR-10:09 | 22187.22 | 07-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4224.95 | 16-APR-02:00 |
May | 24809.68 | 01-MAY-14:09 | 22187.22 | 11-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 | 14-MAY-15:00 | 2016.79 | 05-MAY-21:00 |
June | 24809.68 | 01-JUN-14:09 | 20338.28 | 01-JUN-16:40 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.27 | 12-JUN-13:00 | 2154.18 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 20338.28 | 03-JUL-16:49 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 362.83 | 21-JUL-03:00 | 1555.89 | 06-JUL-02:00 |
August | 24809.68 | 01-AUG-14:09 | 22187.22 | 28-AUG-16:10 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.75 | 13-AUG-18:03 | 1056.82 | 30-AUG-20:50 |
September | 24809.68 | 01-SEP-14:09 | 22187.22 | 01-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.98 | 16-SEP-13:00 | 1879.44 | 29-SEP-04:00 |
October | 24809.68 | 02-OCT-14:09 | 22187.22 | 02-OCT-16:40 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2144.58 | 07-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 22187.22 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4147.02 | 17-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 22187.22 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5377.62 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 20338.28 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.82 | |||||
Maximum of Months | 24809.68 | 22187.22 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 362.83 | 6834.59 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3417.40 | 12-JAN-05:50 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3612.38 | 13-FEB-05:54 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 15-MAR-14:00 | 2127.47 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1900.90 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 14-MAY-15:00 | 1025.21 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.28 | 12-JUN-13:00 | 1098.60 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 15-JUL-15:00 | 795.35 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.09 | 13-AUG-18:03 | 556.53 | 30-AUG-20:20 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.69 | 16-SEP-13:00 | 899.90 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1055.61 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2026.22 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2845.18 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.53 | |||||
Maximum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 3612.38 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3420.10 | 12-JAN-05:24 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3542.61 | 13-FEB-05:52 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 15-MAR-14:00 | 2027.91 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1902.22 | 16-APR-06:55 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 14-MAY-15:00 | 958.44 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.30 | 12-JUN-13:00 | 1048.60 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 15-JUL-15:00 | 737.49 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 | 13-AUG-18:03 | 536.02 | 30-AUG-20:20 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 16-SEP-13:20 | 834.86 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 999.89 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1895.92 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2841.65 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.02 | |||||
Maximum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 3542.61 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 85.37 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 41846.93 | 31-JAN-18:00 |
February | 186.05 | 01-FEB-15:09 | 85.37 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 45204.63 | 06-FEB-18:00 |
March | 186.05 | 01-MAR-15:09 | 85.37 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37057.19 | 06-MAR-18:00 |
April | 186.05 | 01-APR-10:09 | 85.37 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 29277.24 | 16-APR-11:10 |
May | 186.05 | 01-MAY-14:09 | 85.37 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13982.73 | 11-MAY-17:00 |
June | 186.05 | 01-JUN-14:09 | 85.37 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.90 | 17-JUN-15:55 | 12836.73 | 13-JUN-11:10 |
July | 186.05 | 01-JUL-10:09 | 85.37 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.01 | 15-JUL-13:55 | 3913.59 | 02-JUL-11:05 |
August | 186.05 | 01-AUG-14:09 | 85.37 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.45 | 13-AUG-13:00 | 7437.49 | 31-AUG-11:10 |
September | 186.05 | 01-SEP-14:09 | 85.37 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11937.31 | 28-SEP-17:00 |
October | 186.05 | 02-OCT-14:09 | 85.37 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19711.80 | 23-OCT-17:00 |
November | 186.05 | 01-NOV-14:09 | 85.37 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 24657.58 | 22-NOV-18:00 |
December | 186.05 | 01-DEC-15:09 | 85.37 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 42965.22 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3913.59 | ||||
Maximum of Months | 186.05 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.01 | 45204.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3352.28 | 18-JAN-07:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.28 |
February | 437.54 | 23-FEB-07:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.71 |
March | 5045.69 | 19-MAR-08:05 | 392.55 | 481.11 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.96 |
April | 6089.92 | 03-APR-06:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.97 |
May | 4959.43 | 01-MAY-06:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26048.92 | 28-JUN-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.64 |
July | 31381.33 | 12-JUL-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
August | 31711.84 | 01-AUG-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
September | 22768.71 | 15-SEP-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 |
October | 6206.09 | 17-OCT-06:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.72 |
November | 5624.00 | 15-NOV-07:05 | 392.55 | 962.12 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.68 |
December | 5023.48 | 03-DEC-09:05 | 392.55 | 481.11 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 437.54 | 392.55 | 481.11 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31711.84 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19583.74 | 04-JAN-07:05 | 12404.84 | 19721.97 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.53 |
February | 21475.88 | 07-FEB-07:05 | 12404.84 | 19721.97 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.22 |
March | 66949.52 | 16-MAR-06:03 | 9303.63 | 14791.48 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.72 |
April | 28144.53 | 29-APR-16:50 | 18607.26 | 18489.35 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.75 |
May | 166155.49 | 28-MAY-08:62 | 15506.05 | 10271.86 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.45 |
June | 202360.19 | 04-JUN-08:62 | 15506.05 | 8217.49 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 |
July | 170744.90 | 06-JUL-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.83 |
August | 185075.24 | 03-AUG-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.22 |
September | 188060.20 | 11-SEP-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.29 |
October | 141209.56 | 12-OCT-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.00 |
November | 27236.23 | 01-NOV-15:50 | 21708.47 | 22187.22 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.00 |
December | 21474.21 | 11-DEC-07:05 | 12404.84 | 19721.97 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19583.74 | 9303.63 | 8217.49 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 | |
Maximum of Months | 202360.19 | 21708.47 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4743.91 | 09-JAN-16:42 | 8182.17 | 8362.61 | 11683.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.49 |
February | 5241.80 | 13-FEB-12:23 | 8182.17 | 8362.61 | 11683.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 809.44 |
March | 8945.83 | 16-MAR-06:03 | 876.66 | 1393.77 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.65 |
April | 6824.43 | 22-APR-14:20 | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 |
May | 21071.85 | 24-MAY-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 |
June | 23911.16 | 20-JUN-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 |
July | 25060.76 | 13-JUL-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 |
August | 27643.76 | 03-AUG-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 |
September | 26793.73 | 11-SEP-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 |
October | 25522.86 | 12-OCT-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 |
November | 6416.78 | 01-NOV-12:00 | 2045.54 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 |
December | 5507.33 | 10-DEC-11:23 | 2337.76 | 3716.72 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4743.91 | 876.66 | 1393.77 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | |
Maximum of Months | 27643.76 | 8182.17 | 8362.61 | 11683.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 809.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4001.93 | 16-JAN-09:05 | 1168.88 | 929.18 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.23 |
February | 5365.19 | 07-FEB-13:32 | 8182.17 | 8362.61 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.99 |
March | 5335.78 | 15-MAR-13:40 | 2045.54 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 0.00 |
April | 4646.23 | 03-APR-06:05 | 1168.88 | 1858.36 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 |
May | 7877.89 | 24-MAY-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.41 |
June | 17205.78 | 28-JUN-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 |
July | 18926.62 | 12-JUL-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
August | 20806.10 | 01-AUG-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
September | 21102.34 | 22-SEP-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.92 |
October | 12207.16 | 12-OCT-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.32 |
November | 4262.63 | 15-NOV-07:05 | 1168.88 | 1858.36 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 |
December | 4344.00 | 04-DEC-18:53 | 5844.40 | 4645.90 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4001.93 | 1168.88 | 929.18 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21102.34 | 8182.17 | 8362.61 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 642.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.49 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.17 |
April | 11.42 | 07-APR-05:05 | 0.00 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
September | 33.16 | 04-SEP-09:00 | 23.26 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.30 |
October | 92.51 | 22-OCT-08:50 | 23.26 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.18 |
November | 38.14 | 05-NOV-08:40 | 23.26 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.08 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | |
Maximum of Months | 92.51 | 23.26 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.30 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.699151E+11 | 53318.69 | 31-JAN-17:00 | 0.106892E+12 | 172255.41 | 10-JAN-07:10 |
February | 0.609324E+11 | 53615.42 | 06-FEB-17:00 | 0.101141E+12 | 195078.66 | 07-FEB-07:10 |
March | 0.669805E+11 | 57923.94 | 15-MAR-16:30 | 0.577026E+11 | 164463.64 | 06-MAR-07:10 |
April | 0.596625E+11 | 47072.70 | 15-APR-16:00 | 0.286014E+11 | 102893.58 | 17-APR-06:10 |
May | 0.626716E+11 | 59195.64 | 10-MAY-16:40 | 0.127394E+11 | 28269.09 | 01-MAY-06:10 |
June | 0.733752E+11 | 69324.85 | 27-JUN-16:49 | 0.869727E+10 | 19679.37 | 13-JUN-11:09 |
July | 0.866692E+11 | 74585.16 | 15-JUL-13:00 | 0.787457E+10 | 6289.78 | 02-JUL-11:20 |
August | 0.838435E+11 | 71853.74 | 10-AUG-16:10 | 0.809806E+10 | 13103.65 | 31-AUG-11:09 |
September | 0.697949E+11 | 70098.72 | 16-SEP-15:50 | 0.902471E+10 | 18972.12 | 28-SEP-16:00 |
October | 0.657776E+11 | 57565.19 | 11-OCT-15:20 | 0.201121E+11 | 44648.39 | 30-OCT-06:10 |
November | 0.653149E+11 | 52402.48 | 22-NOV-17:00 | 0.357516E+11 | 111807.23 | 24-NOV-07:10 |
December | 0.698362E+11 | 53285.16 | 11-DEC-17:00 | 0.956986E+11 | 184990.08 | 11-DEC-07:10 |
Annual Sum or Average | 0.834774E+12 | 0.492334E+12 | ||||
Minimum of Months | 0.596625E+11 | 47072.70 | 0.787457E+10 | 6289.78 | ||
Maximum of Months | 0.866692E+11 | 74585.16 | 0.106892E+12 | 195078.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.308354E+11 | 0.746353E+10 | 0.164409E+11 | 0.00 | 0.130792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209597E+10 | 0.00 | 0.00 |
February | 0.259929E+11 | 0.614704E+10 | 0.149157E+11 | 0.00 | 0.119732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190358E+10 | 0.00 | 0.00 |
March | 0.290829E+11 | 0.598561E+10 | 0.168545E+11 | 0.00 | 0.123198E+11 | 0.00 | 0.00 | 0.701118E+09 | 0.00 | 0.00 | 0.203662E+10 | 0.00 | 0.00 |
April | 0.254442E+11 | 0.496399E+10 | 0.160187E+11 | 0.00 | 0.114174E+11 | 0.00 | 0.00 | 0.133966E+09 | 0.00 | 0.00 | 0.168420E+10 | 0.00 | 0.00 |
May | 0.263372E+11 | 0.442933E+10 | 0.166477E+11 | 0.00 | 0.115038E+11 | 0.00 | 0.00 | 0.298638E+10 | 0.00 | 0.00 | 0.767242E+09 | 0.00 | 0.00 |
June | 0.253205E+11 | 0.397091E+10 | 0.162750E+11 | 0.00 | 0.111026E+11 | 0.00 | 0.00 | 0.160236E+11 | 0.00 | 0.00 | 0.682567E+09 | 0.00 | 0.00 |
July | 0.251485E+11 | 0.420925E+10 | 0.163892E+11 | 0.00 | 0.112826E+11 | 0.00 | 0.00 | 0.285531E+11 | 0.00 | 0.00 | 0.108654E+10 | 0.00 | 0.00 |
August | 0.263623E+11 | 0.480326E+10 | 0.168545E+11 | 0.00 | 0.114489E+11 | 0.00 | 0.00 | 0.234541E+11 | 0.00 | 0.00 | 0.920304E+09 | 0.00 | 0.00 |
September | 0.265681E+11 | 0.543567E+10 | 0.160144E+11 | 0.00 | 0.110598E+11 | 0.00 | 0.00 | 0.102295E+11 | 0.00 | 0.00 | 0.487343E+09 | 0.00 | 0.00 |
October | 0.290228E+11 | 0.646672E+10 | 0.164431E+11 | 0.00 | 0.115058E+11 | 0.00 | 0.00 | 0.821671E+09 | 0.00 | 0.00 | 0.151745E+10 | 0.00 | 0.00 |
November | 0.291266E+11 | 0.699535E+10 | 0.159174E+11 | 0.00 | 0.113489E+11 | 0.00 | 0.00 | 11255232.02 | 0.00 | 0.00 | 0.191540E+10 | 0.00 | 0.00 |
December | 0.308160E+11 | 0.766164E+10 | 0.163871E+11 | 0.00 | 0.128702E+11 | 0.00 | 0.00 | 268997.82 | 0.00 | 0.00 | 0.210103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.330058E+12 | 0.685323E+11 | 0.195158E+12 | 0.00 | 0.140912E+12 | 0.00 | 0.00 | 0.829150E+11 | 0.00 | 0.00 | 0.171983E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251485E+11 | 0.397091E+10 | 0.149157E+11 | 0.00 | 0.110598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.308354E+11 | 0.766164E+10 | 0.168545E+11 | 0.00 | 0.130792E+11 | 0.00 | 0.00 | 0.285531E+11 | 0.00 | 0.00 | 0.210103E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.983862E+11 | 0.00 | 0.850555E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.933983E+11 | 0.00 | 0.774312E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.491052E+11 | 0.00 | 0.859745E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204556E+11 | 0.00 | 0.814576E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.450601E+10 | 0.00 | 0.823343E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.881056E+09 | 0.00 | 0.781621E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5554462.26 | 0.00 | 0.786901E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.195710E+09 | 0.00 | 0.790235E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.136890E+10 | 0.00 | 0.765581E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120867E+11 | 0.00 | 0.802540E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.278236E+11 | 0.00 | 0.792799E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.873163E+11 | 0.00 | 0.838224E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395529E+12 | 0.00 | 0.968043E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5554462.26 | 0.00 | 0.765581E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.983862E+11 | 0.00 | 0.859745E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27536.32 | 02-JAN-09:09 | 5240.87 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 10782.12 | 30-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27536.32 | 01-FEB-09:09 | 5240.87 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 11242.46 | 07-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27536.32 | 01-MAR-15:00 | 5240.87 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 10593.90 | 06-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27536.32 | 07-APR-16:00 | 5240.87 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 9260.11 | 17-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27536.32 | 11-MAY-16:49 | 5240.87 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 8949.26 | 17-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 25687.38 | 01-JUN-16:40 | 5240.87 | 01-JUN-19:49 | 10771.04 | 01-JUN-08:09 | 0.00 | 11109.98 | 18-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 25687.38 | 03-JUL-16:49 | 5240.87 | 01-JUL-19:00 | 10771.04 | 01-JUL-09:09 | 0.00 | 11874.97 | 20-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 27536.32 | 28-AUG-16:10 | 5240.87 | 01-AUG-19:40 | 10771.04 | 01-AUG-08:09 | 0.00 | 11323.25 | 14-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27536.32 | 01-SEP-16:00 | 5240.87 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 10879.77 | 17-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27536.32 | 02-OCT-16:40 | 5240.87 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 8173.33 | 12-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27536.32 | 01-NOV-08:09 | 5240.87 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 9493.50 | 24-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27536.32 | 01-DEC-09:09 | 5240.87 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 11100.24 | 11-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 25687.38 | 5240.87 | 10771.04 | 0.00 | 8173.33 | 0.00 | 0.00 | |||||
Maximum of Months | 27536.32 | 5240.87 | 10771.04 | 0.00 | 11874.97 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 1406.31 | 01-JAN-09:09 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 1406.31 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 15049.44 | 15-MAR-14:30 | 0.00 | 0.00 | 1406.31 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 6893.48 | 08-APR-13:39 | 0.00 | 0.00 | 1406.31 | 01-APR-06:10 | 0.00 | 0.00 |
May | 18279.09 | 10-MAY-14:30 | 0.00 | 0.00 | 1406.31 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 31005.38 | 27-JUN-12:00 | 0.00 | 0.00 | 1406.31 | 01-JUN-06:40 | 0.00 | 0.00 |
July | 35679.76 | 20-JUL-06:10 | 0.00 | 0.00 | 1406.31 | 01-JUL-13:00 | 0.00 | 0.00 |
August | 30082.10 | 14-AUG-06:10 | 0.00 | 0.00 | 1406.31 | 01-AUG-06:40 | 0.00 | 0.00 |
September | 26193.45 | 16-SEP-13:50 | 0.00 | 0.00 | 1406.31 | 01-SEP-06:19 | 0.00 | 0.00 |
October | 12877.71 | 11-OCT-14:00 | 0.00 | 0.00 | 1406.31 | 01-OCT-08:20 | 0.00 | 0.00 |
November | 1600.24 | 04-NOV-17:10 | 0.00 | 0.00 | 1406.31 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 156.15 | 01-DEC-11:20 | 0.00 | 0.00 | 1406.31 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 1406.31 | 0.00 | 0.00 | ||
Maximum of Months | 35679.76 | 0.00 | 0.00 | 1406.31 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53318.69 | 31-JAN-17:00 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 8364.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53615.42 | 06-FEB-17:00 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 8660.88 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57923.94 | 15-MAR-16:30 | 25687.38 | 10771.04 | 0.00 | 0.00 | 6953.73 | 0.00 | 0.00 | 13105.48 | 0.00 |
April | 47072.70 | 15-APR-16:00 | 27536.32 | 10771.04 | 0.00 | 0.00 | 7354.37 | 0.00 | 0.00 | 4.66 | 0.00 |
May | 59195.64 | 10-MAY-16:40 | 25687.38 | 10771.04 | 0.00 | 0.00 | 6953.73 | 0.00 | 0.00 | 14377.17 | 0.00 |
June | 69324.85 | 27-JUN-16:49 | 23838.45 | 10771.04 | 0.00 | 0.00 | 6982.38 | 0.00 | 0.00 | 26326.67 | 0.00 |
July | 74585.16 | 15-JUL-13:00 | 21989.51 | 10771.04 | 0.00 | 0.00 | 7362.93 | 0.00 | 0.00 | 33055.36 | 0.00 |
August | 71853.74 | 10-AUG-16:10 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7056.39 | 0.00 | 0.00 | 26932.62 | 0.00 |
September | 70098.72 | 16-SEP-15:50 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7040.16 | 0.00 | 0.00 | 25193.83 | 0.00 |
October | 57565.19 | 11-OCT-15:20 | 27536.32 | 10771.04 | 0.00 | 0.00 | 6953.73 | 0.00 | 0.00 | 12304.10 | 0.00 |
November | 52402.48 | 22-NOV-17:00 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 7447.95 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53285.16 | 11-DEC-17:00 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 8330.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 47072.70 | 21989.51 | 10771.04 | 0.00 | 0.00 | 6953.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74585.16 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 8660.88 | 0.00 | 0.00 | 33055.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 168408.90 | 30-JAN-07:10 | 0.00 | 5207.16 | 26-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 190616.52 | 07-FEB-07:10 | 0.00 | 5271.72 | 09-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 159964.89 | 06-MAR-07:10 | 0.00 | 5234.09 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 100917.56 | 17-APR-06:10 | 0.00 | 5131.94 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 26407.09 | 01-MAY-06:10 | 0.00 | 5091.75 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 14662.19 | 13-JUN-11:09 | 0.00 | 5036.18 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 1563.18 | 02-JUL-11:09 | 0.00 | 4991.72 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 8135.56 | 31-AUG-11:09 | 0.00 | 4969.35 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 14138.32 | 28-SEP-16:00 | 0.00 | 4993.49 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 42786.39 | 30-OCT-06:10 | 0.00 | 5038.74 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 109945.23 | 24-NOV-07:10 | 0.00 | 5086.88 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 183128.08 | 11-DEC-07:10 | 0.00 | 5132.46 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 1563.18 | 0.00 | 4969.35 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 190616.52 | 0.00 | 5271.72 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
February | 5.17 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
March | 1.50 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
December | 3.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
Annual Sum or Average | 13.83 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
February | 5.50 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
March | 0.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
Annual Sum or Average | 11.33 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
February | 7.83 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 0.50 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.33 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
Annual Sum or Average | 19.33 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 19.57 | 2.50 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
February | 3.17 | 19.64 | 2.33 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
March | 4.50 | 19.92 | 3.17 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
April | 4.83 | 19.50 | 3.00 | 19.88 | 0.00 | 19.88 | 0.00 | 19.88 |
May | 2.00 | 20.45 | 2.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
October | 2.67 | 20.17 | 2.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
November | 5.33 | 19.89 | 3.17 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
December | 6.17 | 19.02 | 3.33 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Annual Sum or Average | 32.50 | 19.68 | 21.83 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 20.54 | 3.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.26 | 341.00 | 21.19 | 341.00 | 21.17 |
April | 405.00 | 21.24 | 210.33 | 21.19 | 210.33 | 21.17 |
May | 418.00 | 22.47 | 15.50 | 22.42 | 15.50 | 22.38 |
June | 204.33 | 23.64 | 136.00 | 23.74 | 43.17 | 23.75 |
July | 97.17 | 23.88 | 303.83 | 23.89 | 88.50 | 23.89 |
August | 76.83 | 23.81 | 203.67 | 23.87 | 47.00 | 23.87 |
September | 265.83 | 23.37 | 71.33 | 23.48 | 37.83 | 23.52 |
October | 414.00 | 21.68 | 68.17 | 21.60 | 68.17 | 21.54 |
November | 399.00 | 21.15 | 282.33 | 21.13 | 282.33 | 21.13 |
December | 415.00 | 21.11 | 406.00 | 21.11 | 406.00 | 21.11 |
Annual Sum or Average | 3907.17 | 21.76 | 2828.17 | 21.78 | 2329.83 | 21.67 |
Minimum of Months | 76.83 | 21.11 | 15.50 | 21.11 | 15.50 | 21.11 |
Maximum of Months | 422.00 | 23.88 | 414.00 | 23.89 | 414.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.27 | 297.17 | 21.20 | 297.17 | 21.18 |
February | 376.00 | 21.25 | 246.83 | 21.20 | 246.83 | 21.17 |
March | 380.33 | 22.29 | 76.50 | 22.13 | 70.67 | 21.99 |
April | 344.83 | 23.34 | 2.33 | 23.32 | 2.33 | 23.31 |
May | 139.67 | 23.78 | 64.67 | 23.81 | 3.00 | 23.81 |
June | 37.67 | 23.88 | 284.50 | 23.89 | 28.17 | 23.89 |
July | 70.17 | 23.89 | 405.83 | 23.89 | 70.17 | 23.89 |
August | 37.67 | 23.89 | 388.67 | 23.89 | 37.67 | 23.89 |
September | 47.33 | 23.84 | 222.67 | 23.88 | 28.83 | 23.88 |
October | 238.33 | 23.55 | 14.00 | 23.57 | 0.00 | 23.57 |
November | 385.67 | 23.02 | 5.50 | 23.00 | 5.50 | 22.97 |
December | 415.00 | 21.48 | 199.00 | 21.36 | 199.00 | 21.30 |
Annual Sum or Average | 2886.67 | 22.40 | 2207.67 | 22.60 | 989.33 | 22.43 |
Minimum of Months | 37.67 | 21.25 | 2.33 | 21.20 | 0.00 | 21.17 |
Maximum of Months | 415.00 | 23.89 | 405.83 | 23.89 | 297.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.12 | 345.00 | 21.12 | 345.00 | 21.11 |
February | 376.00 | 21.16 | 305.17 | 21.14 | 305.17 | 21.13 |
March | 382.00 | 21.69 | 129.00 | 21.66 | 107.67 | 21.57 |
April | 319.00 | 22.40 | 34.17 | 22.31 | 30.33 | 22.21 |
May | 158.00 | 23.19 | 86.33 | 23.44 | 0.00 | 23.44 |
June | 48.00 | 23.65 | 292.50 | 23.86 | 22.67 | 23.86 |
July | 52.17 | 23.90 | 403.00 | 23.89 | 52.00 | 23.89 |
August | 26.33 | 23.86 | 401.00 | 23.89 | 24.50 | 23.89 |
September | 43.67 | 23.44 | 307.50 | 23.83 | 14.00 | 23.84 |
October | 207.50 | 22.70 | 87.00 | 23.02 | 3.83 | 22.99 |
November | 350.33 | 21.95 | 47.83 | 21.86 | 46.83 | 21.78 |
December | 415.00 | 21.17 | 314.17 | 21.14 | 314.17 | 21.13 |
Annual Sum or Average | 2792.00 | 21.85 | 2752.67 | 22.29 | 1266.17 | 22.11 |
Minimum of Months | 26.33 | 21.12 | 34.17 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 415.00 | 23.90 | 403.00 | 23.89 | 345.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 385.17 | 21.11 | 385.17 | 21.11 |
February | 376.00 | 21.11 | 345.17 | 21.11 | 345.17 | 21.11 |
March | 395.83 | 21.30 | 174.83 | 21.31 | 161.00 | 21.27 |
April | 362.17 | 21.81 | 50.50 | 21.72 | 50.50 | 21.65 |
May | 251.33 | 22.76 | 38.67 | 22.90 | 4.50 | 22.90 |
June | 93.17 | 23.42 | 251.50 | 23.76 | 38.50 | 23.77 |
July | 88.83 | 23.86 | 394.50 | 23.89 | 83.17 | 23.89 |
August | 52.67 | 23.77 | 380.17 | 23.87 | 42.50 | 23.88 |
September | 88.50 | 23.09 | 264.67 | 23.69 | 24.17 | 23.70 |
October | 288.33 | 22.07 | 61.17 | 22.30 | 11.50 | 22.26 |
November | 382.17 | 21.51 | 88.50 | 21.44 | 88.50 | 21.39 |
December | 415.00 | 21.12 | 360.17 | 21.11 | 360.17 | 21.11 |
Annual Sum or Average | 3208.00 | 21.72 | 2795.00 | 22.08 | 1594.83 | 21.95 |
Minimum of Months | 52.67 | 21.11 | 38.67 | 21.11 | 4.50 | 21.11 |
Maximum of Months | 415.00 | 23.86 | 394.50 | 23.89 | 385.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.08 | 362.67 | 21.08 | 362.67 | 21.08 |
February | 376.00 | 21.08 | 328.17 | 21.08 | 328.17 | 21.08 |
March | 404.50 | 21.12 | 178.00 | 21.20 | 163.33 | 21.17 |
April | 405.00 | 21.14 | 67.33 | 21.11 | 67.33 | 21.09 |
May | 397.00 | 21.45 | 20.33 | 21.53 | 9.17 | 21.51 |
June | 298.33 | 23.08 | 200.83 | 23.89 | 114.33 | 24.14 |
July | 294.33 | 25.79 | 370.00 | 25.79 | 266.00 | 25.89 |
August | 275.83 | 25.14 | 328.17 | 25.48 | 206.33 | 25.69 |
September | 324.67 | 22.25 | 128.17 | 22.87 | 70.33 | 23.10 |
October | 400.33 | 21.27 | 25.33 | 21.29 | 18.83 | 21.27 |
November | 399.00 | 21.11 | 125.83 | 21.09 | 125.83 | 21.08 |
December | 415.00 | 21.08 | 364.67 | 21.08 | 364.67 | 21.08 |
Annual Sum or Average | 4404.00 | 21.93 | 2499.50 | 22.29 | 2097.00 | 22.36 |
Minimum of Months | 275.83 | 21.08 | 20.33 | 21.08 | 9.17 | 21.08 |
Maximum of Months | 415.00 | 25.79 | 370.00 | 25.79 | 364.67 | 25.89 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10879 | 15.12170 | -0.7984 | 18.57935 |
February | 376.00000 | 21.10872 | 15.11816 | -0.8011 | 18.64180 |
March | 422.00000 | 21.26168 | 24.29644 | -0.6279 | 14.46653 |
April | 405.00000 | 21.23725 | 30.32787 | -0.5202 | 10.99179 |
May | 418.00000 | 22.46973 | 36.29349 | -1.2235 | 37.71872 |
June | 408.00000 | 23.76377 | 46.16846 | -0.6189 | 13.77969 |
July | 415.00000 | 23.88723 | 55.04391 | -0.4442 | 9.24990 |
August | 422.00000 | 23.87436 | 50.30730 | -0.4998 | 10.39458 |
September | 405.00000 | 23.55020 | 46.69106 | -0.7202 | 17.22391 |
October | 414.00000 | 21.68445 | 36.25535 | -0.3248 | 8.34772 |
November | 399.00000 | 21.14731 | 28.65742 | -0.5675 | 11.98673 |
December | 415.00000 | 21.10907 | 19.04036 | -0.7491 | 17.01891 |
Annual Sum or Average | 4913.00000 | 22.19394 | 33.75059 | -0.6575 | 15.70297 |
Minimum of Months | 376.00000 | 21.10872 | 15.11816 | -1.2235 | 8.34772 |
Maximum of Months | 422.00000 | 23.88723 | 55.04391 | -0.3248 | 37.71872 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.26618 | 25.94571 | -0.5532 | 11.79818 |
February | 376.00000 | 21.24861 | 25.89127 | -0.5576 | 11.84447 |
March | 422.00000 | 22.44723 | 33.02370 | -0.1685 | 7.77891 |
April | 405.00000 | 23.41865 | 34.96897 | 0.12174 | 6.19891 |
May | 418.00000 | 23.85153 | 36.88055 | -0.5899 | 12.67418 |
June | 408.00000 | 23.88872 | 46.12119 | -0.4046 | 8.64089 |
July | 415.00000 | 23.89100 | 54.05494 | -0.3127 | 7.11925 |
August | 422.00000 | 23.89015 | 50.74332 | -0.3562 | 7.74735 |
September | 405.00000 | 23.88283 | 47.25772 | -0.4551 | 9.55480 |
October | 414.00000 | 23.69225 | 38.79320 | 0.23879 | 6.70287 |
November | 399.00000 | 23.05278 | 36.05523 | 0.00212 | 6.17281 |
December | 415.00000 | 21.47595 | 29.48689 | -0.4658 | 10.42975 |
Annual Sum or Average | 4913.00000 | 23.01153 | 38.36311 | -0.2911 | 8.87734 |
Minimum of Months | 376.00000 | 21.24861 | 25.89127 | -0.5899 | 6.17281 |
Maximum of Months | 422.00000 | 23.89100 | 54.05494 | 0.23879 | 12.67418 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.12066 | 18.62817 | -0.6507 | 14.21691 |
February | 376.00000 | 21.15872 | 18.58428 | -0.6384 | 14.01804 |
March | 422.00000 | 21.90257 | 26.57398 | -0.2876 | 9.24082 |
April | 405.00000 | 22.71850 | 30.69138 | -0.0328 | 7.24138 |
May | 418.00000 | 23.62402 | 35.23870 | -0.6528 | 15.50286 |
June | 408.00000 | 23.86011 | 45.20584 | -0.3796 | 8.57355 |
July | 415.00000 | 23.88960 | 53.41965 | -0.2401 | 6.39282 |
August | 422.00000 | 23.88656 | 49.45866 | -0.2632 | 6.71786 |
September | 405.00000 | 23.83847 | 45.27584 | -0.3739 | 8.64170 |
October | 414.00000 | 23.29435 | 35.12761 | 0.19232 | 7.48227 |
November | 399.00000 | 22.18679 | 30.12379 | -0.1834 | 7.91086 |
December | 415.00000 | 21.17152 | 22.39589 | -0.6039 | 13.16635 |
Annual Sum or Average | 4913.00000 | 22.73249 | 34.34799 | -0.3416 | 9.90701 |
Minimum of Months | 376.00000 | 21.12066 | 18.58428 | -0.6528 | 6.39282 |
Maximum of Months | 422.00000 | 23.88960 | 53.41965 | 0.19232 | 15.50286 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10952 | 18.68191 | -0.6924 | 15.34865 |
February | 376.00000 | 21.11056 | 18.65615 | -0.6864 | 15.21032 |
March | 422.00000 | 21.46139 | 27.42774 | -0.4153 | 10.45939 |
April | 405.00000 | 22.02539 | 32.33898 | -0.2066 | 7.89338 |
May | 418.00000 | 23.20449 | 37.21789 | -0.8238 | 21.72020 |
June | 408.00000 | 23.77893 | 46.73764 | -0.4522 | 10.21744 |
July | 415.00000 | 23.88163 | 54.88150 | -0.2861 | 6.93887 |
August | 422.00000 | 23.87007 | 50.56691 | -0.3164 | 7.43622 |
September | 405.00000 | 23.70968 | 46.66786 | -0.4592 | 10.68373 |
October | 414.00000 | 22.61807 | 37.11248 | 0.02417 | 7.30139 |
November | 399.00000 | 21.61445 | 31.37684 | -0.3374 | 8.98496 |
December | 415.00000 | 21.11544 | 22.50553 | -0.6557 | 14.34675 |
Annual Sum or Average | 4913.00000 | 22.46949 | 35.47448 | -0.4412 | 11.36539 |
Minimum of Months | 376.00000 | 21.10952 | 18.65615 | -0.8238 | 6.93887 |
Maximum of Months | 422.00000 | 23.88163 | 54.88150 | 0.02417 | 21.72020 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.08058 | 14.65282 | -0.6989 | 15.68576 |
February | 376.00000 | 21.08217 | 14.48188 | -0.6898 | 15.45076 |
March | 422.00000 | 21.27529 | 23.65492 | -0.4463 | 10.98798 |
April | 405.00000 | 21.13721 | 30.17938 | -0.3732 | 8.50863 |
May | 418.00000 | 21.59909 | 37.86538 | -1.2403 | 38.77136 |
June | 408.00000 | 23.49308 | 49.39735 | -0.5289 | 20.24257 |
July | 415.00000 | 25.45498 | 58.25669 | 0.14814 | 13.33739 |
August | 422.00000 | 24.97890 | 51.67159 | -0.0204 | 14.78704 |
September | 405.00000 | 22.59201 | 50.42590 | -0.7325 | 21.64598 |
October | 414.00000 | 21.33516 | 36.53665 | -0.2122 | 6.96329 |
November | 399.00000 | 21.11001 | 27.98216 | -0.4451 | 9.74288 |
December | 415.00000 | 21.08124 | 18.20657 | -0.6734 | 14.94592 |
Annual Sum or Average | 4913.00000 | 22.19940 | 34.59181 | -0.4908 | 15.95079 |
Minimum of Months | 376.00000 | 21.08058 | 14.48188 | -1.2403 | 6.96329 |
Maximum of Months | 422.00000 | 25.45498 | 58.25669 | 0.14814 | 38.77136 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 15569901.55 | 4609006.90 | 4.50 | 14447634.38 | 1122267.17 | 0.00 | 0.18 | 15-MAR-16:10 | 0.00 | 01-MAR-00:10 | 2116.23 | 15-MAR-16:10 | 1956.64 | 15-MAR-16:10 | 159.59 | 15-MAR-16:10 | 609.57 | 15-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.108758E+09 | 31004536.56 | 31.50 | 99776523.36 | 8981179.46 | 0.00 | 0.27 | 10-MAY-14:30 | 0.00 | 01-MAY-00:10 | 3278.69 | 10-MAY-14:30 | 2706.08 | 10-MAY-14:30 | 572.61 | 10-MAY-14:30 | 931.07 | 10-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 0.445628E+10 | 0.114402E+10 | 263.99 | 0.332900E+10 | 0.112728E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 33381.44 | 18-JUN-08:62 | 21886.64 | 12-JUN-06:02 | 16122.55 | 18-JUN-08:04 | 7042.13 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.110213E+11 | 0.273449E+10 | 396.31 | 0.767200E+10 | 0.334931E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 34238.41 | 21-JUL-05:02 | 22318.83 | 15-JUL-06:02 | 18359.35 | 29-JUL-06:04 | 7131.43 | 21-JUL-06:15 | 0.00 | 01-JUL-00:10 |
August | 0.809210E+10 | 0.206446E+10 | 364.23 | 0.631460E+10 | 0.177750E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33490.29 | 14-AUG-06:02 | 24534.16 | 06-AUG-08:62 | 18312.16 | 14-AUG-06:06 | 6942.27 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.206796E+10 | 0.534361E+09 | 173.61 | 0.145516E+10 | 0.612797E+09 | 0.00 | 1.00 | 14-SEP-06:02 | 0.00 | 01-SEP-00:10 | 32403.96 | 16-SEP-06:02 | 18215.42 | 17-SEP-08:62 | 16025.43 | 14-SEP-06:02 | 6797.86 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 202.11 | 57.37 | 1.00 | 154.25 | 47.86 | 0.00 | 0.00 | 12-OCT-15:10 | 0.00 | 01-OCT-00:10 | 0.10 | 12-OCT-15:10 | 0.08 | 12-OCT-15:10 | 0.02 | 12-OCT-15:10 | 0.03 | 12-OCT-15:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.257620E+11 | 0.651295E+10 | 1235.14 | 0.188850E+11 | 0.687698E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110213E+11 | 0.273449E+10 | 396.31 | 0.767200E+10 | 0.334931E+10 | 0.00 | 1.00 | 0.00 | 34238.41 | 24534.16 | 18359.35 | 7131.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.175445E+10 | 0.522543E+09 | 62.39 | 0.138641E+10 | 0.368034E+09 | 0.00 | 0.52 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 | 37422.04 | 15-MAR-14:50 | 31386.28 | 15-MAR-14:40 | 10006.63 | 16-MAR-06:03 | 11050.09 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 |
April | 0.277440E+09 | 84553376.62 | 165.83 | 0.249894E+09 | 27546400.76 | 0.00 | 0.26 | 08-APR-13:40 | 0.00 | 01-APR-00:10 | 16820.17 | 08-APR-13:40 | 14841.14 | 08-APR-13:30 | 2229.29 | 08-APR-14:00 | 4993.31 | 08-APR-13:40 | 0.00 | 01-APR-00:10 |
May | 0.811528E+10 | 0.234963E+10 | 233.70 | 0.720515E+10 | 0.910125E+09 | 0.00 | 1.00 | 14-MAY-08:63 | 0.00 | 01-MAY-00:10 | 165951.91 | 24-MAY-06:02 | 143805.12 | 17-MAY-06:03 | 46919.02 | 24-MAY-06:02 | 39477.85 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.428135E+11 | 0.118772E+11 | 353.56 | 0.322018E+11 | 0.106117E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 184477.21 | 18-JUN-08:62 | 152146.11 | 11-JUN-08:62 | 89230.18 | 08-JUN-06:02 | 43386.29 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.748178E+11 | 0.202841E+11 | 409.49 | 0.518175E+11 | 0.230003E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 186501.04 | 21-JUL-05:02 | 122405.33 | 15-JUL-06:02 | 97098.37 | 29-JUL-06:04 | 43864.06 | 21-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.598237E+11 | 0.165755E+11 | 397.65 | 0.450041E+11 | 0.148196E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 183936.25 | 14-AUG-06:02 | 134314.46 | 13-AUG-08:62 | 94506.84 | 14-AUG-06:04 | 42731.72 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.260175E+11 | 0.721792E+10 | 304.26 | 0.186311E+11 | 0.738637E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 178871.58 | 16-SEP-06:02 | 125765.87 | 08-SEP-06:02 | 84931.52 | 14-SEP-06:04 | 41899.49 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.156097E+10 | 0.464751E+09 | 223.44 | 0.132319E+10 | 0.237775E+09 | 0.00 | 1.00 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 131091.90 | 12-OCT-06:02 | 95201.81 | 12-OCT-06:02 | 43118.48 | 13-OCT-06:03 | 31109.67 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 19835084.83 | 6258630.45 | 103.50 | 17482949.64 | 2352135.19 | 0.00 | 0.08 | 04-NOV-17:10 | 0.00 | 01-NOV-00:10 | 5142.54 | 04-NOV-17:10 | 4094.83 | 04-NOV-17:10 | 1047.72 | 04-NOV-17:10 | 1600.24 | 04-NOV-17:10 | 0.00 | 01-NOV-00:10 |
December | 847514.53 | 268997.82 | 5.83 | 682498.93 | 165015.60 | 0.00 | 0.01 | 01-DEC-11:20 | 0.00 | 01-DEC-00:10 | 492.45 | 01-DEC-11:20 | 409.97 | 01-DEC-11:20 | 82.48 | 01-DEC-11:20 | 156.15 | 01-DEC-11:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.215201E+12 | 0.593827E+11 | 2259.65 | 0.157837E+12 | 0.573640E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.748178E+11 | 0.202841E+11 | 409.49 | 0.518175E+11 | 0.230003E+11 | 0.00 | 1.00 | 0.00 | 186501.04 | 152146.11 | 97098.37 | 43864.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.438340E+09 | 0.109715E+09 | 22.72 | 0.379837E+09 | 58503446.93 | 0.00 | 0.84 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 9190.68 | 15-MAR-13:40 | 8711.87 | 15-MAR-13:40 | 1807.46 | 14-MAR-11:25 | 2224.37 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 0.149861E+09 | 39630198.76 | 30.17 | 0.144307E+09 | 5553480.14 | 0.00 | 0.49 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 4750.28 | 08-APR-13:40 | 4454.21 | 08-APR-13:30 | 402.93 | 08-APR-14:00 | 1184.44 | 08-APR-13:40 | 0.00 | 01-APR-00:10 |
May | 0.159334E+10 | 0.402164E+09 | 151.72 | 0.146298E+10 | 0.130356E+09 | 0.00 | 1.00 | 17-MAY-06:03 | 0.00 | 01-MAY-00:10 | 23630.91 | 24-MAY-06:02 | 16639.64 | 24-MAY-06:02 | 6991.26 | 24-MAY-06:02 | 5029.13 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.745428E+10 | 0.178567E+10 | 334.60 | 0.583132E+10 | 0.162296E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26185.98 | 18-JUN-08:62 | 22120.73 | 11-JUN-08:62 | 12581.73 | 08-JUN-06:02 | 5511.27 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.135252E+11 | 0.314800E+10 | 412.64 | 0.983429E+10 | 0.369088E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 26871.94 | 21-JUL-05:02 | 17485.63 | 15-JUL-06:02 | 14127.11 | 29-JUL-06:02 | 5574.16 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.117209E+11 | 0.275573E+10 | 405.56 | 0.936795E+10 | 0.235294E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26234.98 | 14-AUG-06:02 | 19596.42 | 06-AUG-08:62 | 14261.44 | 14-AUG-06:04 | 5432.65 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.628111E+10 | 0.147598E+10 | 296.45 | 0.487578E+10 | 0.140533E+10 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 25349.37 | 16-SEP-06:02 | 17867.90 | 08-SEP-06:02 | 12162.60 | 14-SEP-06:02 | 5318.27 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.942702E+09 | 0.234187E+09 | 81.35 | 0.819042E+09 | 0.123660E+09 | 0.00 | 1.00 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 22364.23 | 12-OCT-06:02 | 16969.63 | 12-OCT-06:02 | 5394.60 | 12-OCT-06:02 | 4746.02 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 18097599.15 | 4996601.58 | 9.83 | 15124777.34 | 2972821.82 | 0.00 | 0.20 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 | 1726.14 | 16-NOV-12:40 | 1555.25 | 16-NOV-12:40 | 253.64 | 04-NOV-14:50 | 465.47 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.421238E+11 | 0.995607E+10 | 1745.06 | 0.327306E+11 | 0.939316E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.135252E+11 | 0.314800E+10 | 412.64 | 0.983429E+10 | 0.369088E+10 | 0.00 | 1.00 | 0.00 | 26871.94 | 22120.73 | 14261.44 | 5574.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.247848E+09 | 64251506.02 | 19.33 | 0.212052E+09 | 35795955.49 | 0.00 | 0.73 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 6663.56 | 15-MAR-13:40 | 6184.74 | 15-MAR-13:50 | 1242.90 | 14-MAR-13:00 | 1666.89 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 36449751.03 | 9782386.60 | 12.00 | 33841550.44 | 2608200.59 | 0.00 | 0.35 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 2767.09 | 08-APR-13:30 | 2531.40 | 08-APR-13:30 | 284.35 | 08-APR-14:00 | 717.96 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.787318E+09 | 0.203589E+09 | 95.86 | 0.717057E+09 | 70260780.93 | 0.00 | 0.81 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 | 7669.27 | 24-MAY-06:02 | 5266.63 | 23-MAY-14:30 | 2552.60 | 24-MAY-06:02 | 1737.87 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.498917E+10 | 0.121671E+10 | 288.77 | 0.379540E+10 | 0.119377E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 22402.11 | 18-JUN-08:62 | 14795.47 | 02-JUN-06:02 | 10779.75 | 18-JUN-08:04 | 4718.69 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.100897E+11 | 0.238646E+10 | 399.91 | 0.712779E+10 | 0.296189E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 22992.50 | 21-JUL-05:02 | 14763.89 | 15-JUL-06:02 | 12242.83 | 29-JUL-06:02 | 4775.23 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.862190E+10 | 0.205844E+10 | 375.42 | 0.678598E+10 | 0.183591E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 22469.76 | 14-AUG-06:02 | 16440.49 | 06-AUG-08:62 | 12347.22 | 14-AUG-06:04 | 4651.98 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.419177E+10 | 0.100128E+10 | 253.79 | 0.320579E+10 | 0.985980E+09 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21731.80 | 16-SEP-06:02 | 13835.51 | 13-SEP-06:02 | 10505.89 | 14-SEP-06:02 | 4556.38 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.487359E+09 | 0.122734E+09 | 54.45 | 0.418871E+09 | 68488251.86 | 0.00 | 1.00 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 9817.99 | 12-OCT-06:02 | 7117.70 | 11-OCT-14:40 | 2722.36 | 12-OCT-06:02 | 2084.36 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.294515E+11 | 0.706325E+10 | 1499.53 | 0.222968E+11 | 0.715470E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100897E+11 | 0.238646E+10 | 399.91 | 0.712779E+10 | 0.296189E+10 | 0.00 | 1.00 | 0.00 | 22992.50 | 16440.49 | 12347.22 | 4775.23 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.41 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.14 | 88.52 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 79.01 | 67.65 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 120.54 | 51.93 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.20 | 37.52 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.98 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.58 | 20.18 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.89 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.49 | 37.41 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 58.93 | 55.06 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 23.91 | 67.51 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.44 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.34 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.44 | 20.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 93.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 974.40 | 568.79 | 405.61 | 824.34 | 1072.08 | 0.00 | 0.00 | 0.00 |
February | 1112.52 | 536.45 | 576.07 | 935.63 | 1040.55 | 0.00 | 0.00 | 0.00 |
March | 1357.91 | 763.00 | 594.91 | 1382.66 | 791.14 | 0.00 | 0.00 | 0.00 |
April | 1124.56 | 449.38 | 675.18 | 1187.65 | 632.39 | 0.00 | 0.00 | 0.00 |
May | 984.09 | 285.82 | 698.27 | 1123.07 | 439.32 | 0.00 | 0.00 | 0.00 |
June | 956.22 | 202.63 | 753.59 | 1204.85 | 299.09 | 0.00 | 0.00 | 0.00 |
July | 976.15 | 236.84 | 739.30 | 1352.31 | 215.71 | 0.00 | 0.00 | 0.00 |
August | 1095.88 | 355.31 | 740.57 | 1487.56 | 282.60 | 0.00 | 0.00 | 0.00 |
September | 1274.18 | 620.62 | 653.56 | 1598.25 | 433.72 | 0.00 | 0.00 | 0.00 |
October | 1219.21 | 696.43 | 522.77 | 1331.22 | 639.74 | 0.00 | 0.00 | 0.00 |
November | 873.17 | 492.93 | 380.24 | 846.23 | 775.05 | 0.00 | 0.00 | 0.00 |
December | 814.79 | 421.69 | 393.10 | 653.41 | 1053.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1063.26 | 468.91 | 594.35 | 1161.91 | 637.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.79 | 202.63 | 380.24 | 653.41 | 215.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.91 | 763.00 | 753.59 | 1598.25 | 1072.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 974.40 | 568.79 | 405.61 | 822.40 | 1063.56 | 0.00 | 0.00 | 0.00 |
February | 1112.52 | 536.45 | 576.07 | 933.84 | 1031.82 | 0.00 | 0.00 | 0.00 |
March | 1357.91 | 763.00 | 594.91 | 1388.65 | 768.64 | 0.00 | 0.00 | 0.00 |
April | 1124.56 | 449.38 | 675.18 | 1198.13 | 602.60 | 0.00 | 0.00 | 0.00 |
May | 984.09 | 285.82 | 698.27 | 1129.11 | 415.10 | 0.00 | 0.00 | 0.00 |
June | 956.22 | 202.63 | 753.59 | 1203.16 | 284.67 | 0.00 | 0.00 | 0.00 |
July | 976.15 | 236.84 | 739.30 | 1347.68 | 203.80 | 0.00 | 0.00 | 0.00 |
August | 1095.88 | 355.31 | 740.57 | 1482.72 | 269.89 | 0.00 | 0.00 | 0.00 |
September | 1274.18 | 620.62 | 653.56 | 1596.22 | 418.04 | 0.00 | 0.00 | 0.00 |
October | 1219.21 | 696.43 | 522.77 | 1339.66 | 609.48 | 0.00 | 0.00 | 0.00 |
November | 873.17 | 492.93 | 380.24 | 852.63 | 745.44 | 0.00 | 0.00 | 0.00 |
December | 814.79 | 421.69 | 393.10 | 652.61 | 1042.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1063.26 | 468.91 | 594.35 | 1163.56 | 619.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.79 | 202.63 | 380.24 | 652.61 | 203.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.91 | 763.00 | 753.59 | 1596.22 | 1063.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.47 | 117.02 | 83.45 | 164.56 | 218.18 | 0.00 | 0.00 | 0.00 |
February | 228.89 | 110.37 | 118.52 | 186.30 | 211.98 | 0.00 | 0.00 | 0.00 |
March | 279.37 | 156.98 | 122.39 | 279.60 | 156.24 | 0.00 | 0.00 | 0.00 |
April | 231.36 | 92.45 | 138.91 | 244.33 | 120.32 | 0.00 | 0.00 | 0.00 |
May | 202.46 | 58.80 | 143.66 | 234.10 | 80.15 | 0.00 | 0.00 | 0.00 |
June | 196.73 | 41.69 | 155.04 | 244.93 | 55.97 | 0.00 | 0.00 | 0.00 |
July | 200.83 | 48.73 | 152.10 | 266.40 | 42.68 | 0.00 | 0.00 | 0.00 |
August | 225.46 | 73.10 | 152.36 | 295.44 | 56.08 | 0.00 | 0.00 | 0.00 |
September | 262.15 | 127.69 | 134.46 | 327.84 | 81.43 | 0.00 | 0.00 | 0.00 |
October | 250.84 | 143.28 | 107.55 | 274.62 | 120.38 | 0.00 | 0.00 | 0.00 |
November | 179.64 | 101.41 | 78.23 | 172.80 | 150.56 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 86.76 | 80.88 | 130.33 | 214.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.75 | 96.47 | 122.28 | 235.37 | 125.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 41.69 | 78.23 | 130.33 | 42.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.37 | 156.98 | 155.04 | 327.84 | 218.18 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 38583394.36 | 0.250536E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85009420.57 | 0.214153E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.211632E+09 | 0.181190E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.312451E+09 | 0.134596E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453173E+09 | 0.100484E+09 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544149E+09 | 69927251.22 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542599E+09 | 54055071.50 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453363E+09 | 66664637.82 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304537E+09 | 96960361.04 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.157847E+09 | 0.147475E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 61985632.08 | 0.174984E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 30643757.90 | 0.244129E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.319597E+10 | 0.173515E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 30643757.90 | 54055071.50 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544149E+09 | 0.250536E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.220792E+10 | 0.287145E+10 |
February | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.226347E+10 | 0.251730E+10 |
March | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.370331E+10 | 0.211899E+10 |
April | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.307840E+10 | 0.163915E+10 |
May | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.300804E+10 | 0.117669E+10 |
June | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.312297E+10 | 0.775242E+09 |
July | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.362202E+10 | 0.577769E+09 |
August | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.398428E+10 | 0.756904E+09 |
September | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.414267E+10 | 0.112421E+10 |
October | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.356555E+10 | 0.171348E+10 |
November | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.219343E+10 | 0.200893E+10 |
December | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.175009E+10 | 0.282107E+10 |
Annual Sum or Average | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.366421E+11 | 0.201012E+11 |
Minimum of Months | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.175009E+10 | 0.577769E+09 |
Maximum of Months | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.414267E+10 | 0.287145E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.220272E+10 | 0.284864E+10 |
February | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.225915E+10 | 0.249619E+10 |
March | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.371937E+10 | 0.205872E+10 |
April | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.310556E+10 | 0.156193E+10 |
May | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.302421E+10 | 0.111181E+10 |
June | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.311860E+10 | 0.737854E+09 |
July | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.360962E+10 | 0.545863E+09 |
August | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.397131E+10 | 0.722885E+09 |
September | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.413741E+10 | 0.108357E+10 |
October | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.358814E+10 | 0.163243E+10 |
November | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.221001E+10 | 0.193218E+10 |
December | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.174796E+10 | 0.279325E+10 |
Annual Sum or Average | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.366941E+11 | 0.195253E+11 |
Minimum of Months | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.174796E+10 | 0.545863E+09 |
Maximum of Months | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.413741E+10 | 0.284864E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.536940E+09 | 0.313428E+09 | 0.223512E+09 | 0.440758E+09 | 0.584372E+09 |
February | 0.553723E+09 | 0.267001E+09 | 0.286723E+09 | 0.450702E+09 | 0.512814E+09 |
March | 0.748269E+09 | 0.420448E+09 | 0.327821E+09 | 0.748891E+09 | 0.418470E+09 |
April | 0.599695E+09 | 0.239640E+09 | 0.360055E+09 | 0.633302E+09 | 0.311863E+09 |
May | 0.542279E+09 | 0.157501E+09 | 0.384778E+09 | 0.627008E+09 | 0.214680E+09 |
June | 0.509923E+09 | 0.108055E+09 | 0.401868E+09 | 0.634867E+09 | 0.145066E+09 |
July | 0.537900E+09 | 0.130512E+09 | 0.407388E+09 | 0.713522E+09 | 0.114310E+09 |
August | 0.603882E+09 | 0.195794E+09 | 0.408088E+09 | 0.791320E+09 | 0.150194E+09 |
September | 0.679485E+09 | 0.330960E+09 | 0.348525E+09 | 0.849764E+09 | 0.211062E+09 |
October | 0.671839E+09 | 0.383767E+09 | 0.288072E+09 | 0.735545E+09 | 0.322418E+09 |
November | 0.465636E+09 | 0.262867E+09 | 0.202769E+09 | 0.447909E+09 | 0.390239E+09 |
December | 0.448988E+09 | 0.232372E+09 | 0.216617E+09 | 0.349077E+09 | 0.573554E+09 |
Annual Sum or Average | 0.689856E+10 | 0.304234E+10 | 0.385622E+10 | 0.742267E+10 | 0.394904E+10 |
Minimum of Months | 0.448988E+09 | 0.108055E+09 | 0.202769E+09 | 0.349077E+09 | 0.114310E+09 |
Maximum of Months | 0.748269E+09 | 0.420448E+09 | 0.408088E+09 | 0.849764E+09 | 0.584372E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.49 | 1496.63 | 571.00 | 169.08 | 401.93 | 0.00 | 0.00 |
February | 562.23 | 1416.35 | 906.99 | 265.21 | 641.78 | 0.00 | 0.00 |
March | 1264.23 | 1082.38 | 1398.62 | 717.37 | 681.25 | 0.00 | 0.00 |
April | 1928.71 | 830.84 | 1874.38 | 1001.99 | 872.38 | 0.00 | 0.00 |
May | 2707.12 | 600.26 | 2386.31 | 1470.52 | 915.79 | 0.00 | 0.00 |
June | 3358.94 | 431.65 | 2763.91 | 1734.24 | 1029.68 | 0.00 | 0.00 |
July | 3241.33 | 322.91 | 2561.88 | 1556.07 | 1005.81 | 0.00 | 0.00 |
August | 2708.26 | 398.24 | 2173.76 | 1204.51 | 969.26 | 0.00 | 0.00 |
September | 1879.86 | 598.52 | 1627.87 | 888.85 | 739.02 | 0.00 | 0.00 |
October | 942.93 | 880.97 | 1011.65 | 438.38 | 573.28 | 0.00 | 0.00 |
November | 382.63 | 1080.15 | 584.21 | 181.95 | 402.27 | 0.00 | 0.00 |
December | 183.06 | 1458.36 | 504.12 | 108.30 | 395.82 | 0.00 | 0.00 |
Annual Sum or Average | 1621.50 | 880.34 | 1533.52 | 814.32 | 719.20 | 0.00 | 0.00 |
Minimum of Months | 183.06 | 322.91 | 504.12 | 108.30 | 395.82 | 0.00 | 0.00 |
Maximum of Months | 3358.94 | 1496.63 | 2763.91 | 1734.24 | 1029.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 824.34 | 1072.08 | 974.40 | 568.79 | 405.61 | 0.00 | 0.00 |
February | 935.63 | 1040.55 | 1112.52 | 536.45 | 576.07 | 0.00 | 0.00 |
March | 1382.66 | 791.14 | 1357.91 | 763.00 | 594.91 | 0.00 | 0.00 |
April | 1187.65 | 632.39 | 1124.56 | 449.38 | 675.18 | 0.00 | 0.00 |
May | 1123.07 | 439.32 | 984.09 | 285.82 | 698.27 | 0.00 | 0.00 |
June | 1204.85 | 299.09 | 956.22 | 202.63 | 753.59 | 0.00 | 0.00 |
July | 1352.31 | 215.71 | 976.15 | 236.84 | 739.30 | 0.00 | 0.00 |
August | 1487.56 | 282.60 | 1095.88 | 355.31 | 740.57 | 0.00 | 0.00 |
September | 1598.25 | 433.72 | 1274.18 | 620.62 | 653.56 | 0.00 | 0.00 |
October | 1331.22 | 639.74 | 1219.21 | 696.43 | 522.77 | 0.00 | 0.00 |
November | 846.23 | 775.05 | 873.17 | 492.93 | 380.24 | 0.00 | 0.00 |
December | 653.41 | 1053.27 | 814.79 | 421.69 | 393.10 | 0.00 | 0.00 |
Annual Sum or Average | 1161.91 | 637.40 | 1063.26 | 468.91 | 594.35 | 0.00 | 0.00 |
Minimum of Months | 653.41 | 215.71 | 814.79 | 202.63 | 380.24 | 0.00 | 0.00 |
Maximum of Months | 1598.25 | 1072.08 | 1357.91 | 763.00 | 753.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 822.40 | 1063.56 | 974.40 | 568.79 | 405.61 | 0.00 | 0.00 |
February | 933.84 | 1031.82 | 1112.52 | 536.45 | 576.07 | 0.00 | 0.00 |
March | 1388.65 | 768.64 | 1357.91 | 763.00 | 594.91 | 0.00 | 0.00 |
April | 1198.13 | 602.60 | 1124.56 | 449.38 | 675.18 | 0.00 | 0.00 |
May | 1129.11 | 415.10 | 984.09 | 285.82 | 698.27 | 0.00 | 0.00 |
June | 1203.16 | 284.67 | 956.22 | 202.63 | 753.59 | 0.00 | 0.00 |
July | 1347.68 | 203.80 | 976.15 | 236.84 | 739.30 | 0.00 | 0.00 |
August | 1482.72 | 269.89 | 1095.88 | 355.31 | 740.57 | 0.00 | 0.00 |
September | 1596.22 | 418.04 | 1274.18 | 620.62 | 653.56 | 0.00 | 0.00 |
October | 1339.66 | 609.48 | 1219.21 | 696.43 | 522.77 | 0.00 | 0.00 |
November | 852.63 | 745.44 | 873.17 | 492.93 | 380.24 | 0.00 | 0.00 |
December | 652.61 | 1042.88 | 814.79 | 421.69 | 393.10 | 0.00 | 0.00 |
Annual Sum or Average | 1163.56 | 619.14 | 1063.26 | 468.91 | 594.35 | 0.00 | 0.00 |
Minimum of Months | 652.61 | 203.80 | 814.79 | 202.63 | 380.24 | 0.00 | 0.00 |
Maximum of Months | 1596.22 | 1063.56 | 1357.91 | 763.00 | 753.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.56 | 218.18 | 200.47 | 117.02 | 83.45 | 0.00 | 0.00 |
February | 186.30 | 211.98 | 228.89 | 110.37 | 118.52 | 0.00 | 0.00 |
March | 279.60 | 156.24 | 279.37 | 156.98 | 122.39 | 0.00 | 0.00 |
April | 244.33 | 120.32 | 231.36 | 92.45 | 138.91 | 0.00 | 0.00 |
May | 234.10 | 80.15 | 202.46 | 58.80 | 143.66 | 0.00 | 0.00 |
June | 244.93 | 55.97 | 196.73 | 41.69 | 155.04 | 0.00 | 0.00 |
July | 266.40 | 42.68 | 200.83 | 48.73 | 152.10 | 0.00 | 0.00 |
August | 295.44 | 56.08 | 225.46 | 73.10 | 152.36 | 0.00 | 0.00 |
September | 327.84 | 81.43 | 262.15 | 127.69 | 134.46 | 0.00 | 0.00 |
October | 274.62 | 120.38 | 250.84 | 143.28 | 107.55 | 0.00 | 0.00 |
November | 172.80 | 150.56 | 179.64 | 101.41 | 78.23 | 0.00 | 0.00 |
December | 130.33 | 214.14 | 167.63 | 86.76 | 80.88 | 0.00 | 0.00 |
Annual Sum or Average | 235.37 | 125.22 | 218.75 | 96.47 | 122.28 | 0.00 | 0.00 |
Minimum of Months | 130.33 | 42.68 | 167.63 | 41.69 | 78.23 | 0.00 | 0.00 |
Maximum of Months | 327.84 | 218.18 | 279.37 | 156.98 | 155.04 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.617334E+09 | 0.400857E+10 | 0.152937E+10 | 0.452854E+09 | 0.107652E+10 | 0.00 | 0.00 |
February | 0.136015E+10 | 0.342645E+10 | 0.219418E+10 | 0.641585E+09 | 0.155260E+10 | 0.00 | 0.00 |
March | 0.338612E+10 | 0.289903E+10 | 0.374607E+10 | 0.192141E+10 | 0.182465E+10 | 0.00 | 0.00 |
April | 0.499921E+10 | 0.215354E+10 | 0.485839E+10 | 0.259717E+10 | 0.226122E+10 | 0.00 | 0.00 |
May | 0.725076E+10 | 0.160774E+10 | 0.639149E+10 | 0.393865E+10 | 0.245284E+10 | 0.00 | 0.00 |
June | 0.870638E+10 | 0.111884E+10 | 0.716406E+10 | 0.449514E+10 | 0.266892E+10 | 0.00 | 0.00 |
July | 0.868158E+10 | 0.864881E+09 | 0.686175E+10 | 0.416778E+10 | 0.269397E+10 | 0.00 | 0.00 |
August | 0.725381E+10 | 0.106663E+10 | 0.582221E+10 | 0.322615E+10 | 0.259605E+10 | 0.00 | 0.00 |
September | 0.487259E+10 | 0.155137E+10 | 0.421944E+10 | 0.230391E+10 | 0.191553E+10 | 0.00 | 0.00 |
October | 0.252555E+10 | 0.235960E+10 | 0.270962E+10 | 0.117415E+10 | 0.153547E+10 | 0.00 | 0.00 |
November | 0.991770E+09 | 0.279974E+10 | 0.151428E+10 | 0.471601E+09 | 0.104267E+10 | 0.00 | 0.00 |
December | 0.490300E+09 | 0.390607E+10 | 0.135023E+10 | 0.290060E+09 | 0.106017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.511356E+11 | 0.277625E+11 | 0.483611E+11 | 0.256805E+11 | 0.226806E+11 | 0.00 | 0.00 |
Minimum of Months | 0.490300E+09 | 0.864881E+09 | 0.135023E+10 | 0.290060E+09 | 0.104267E+10 | 0.00 | 0.00 |
Maximum of Months | 0.870638E+10 | 0.400857E+10 | 0.716406E+10 | 0.449514E+10 | 0.269397E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220792E+10 | 0.287145E+10 | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.00 | 0.00 |
February | 0.226347E+10 | 0.251730E+10 | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.00 | 0.00 |
March | 0.370331E+10 | 0.211899E+10 | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.00 | 0.00 |
April | 0.307840E+10 | 0.163915E+10 | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.00 | 0.00 |
May | 0.300804E+10 | 0.117669E+10 | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.00 | 0.00 |
June | 0.312297E+10 | 0.775242E+09 | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.00 | 0.00 |
July | 0.362202E+10 | 0.577769E+09 | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.00 | 0.00 |
August | 0.398428E+10 | 0.756904E+09 | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.00 | 0.00 |
September | 0.414267E+10 | 0.112421E+10 | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.00 | 0.00 |
October | 0.356555E+10 | 0.171348E+10 | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.00 | 0.00 |
November | 0.219343E+10 | 0.200893E+10 | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.00 | 0.00 |
December | 0.175009E+10 | 0.282107E+10 | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.366421E+11 | 0.201012E+11 | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175009E+10 | 0.577769E+09 | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414267E+10 | 0.287145E+10 | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220272E+10 | 0.284864E+10 | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.00 | 0.00 |
February | 0.225915E+10 | 0.249619E+10 | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.00 | 0.00 |
March | 0.371937E+10 | 0.205872E+10 | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.00 | 0.00 |
April | 0.310556E+10 | 0.156193E+10 | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.00 | 0.00 |
May | 0.302421E+10 | 0.111181E+10 | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.00 | 0.00 |
June | 0.311860E+10 | 0.737854E+09 | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.00 | 0.00 |
July | 0.360962E+10 | 0.545863E+09 | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.00 | 0.00 |
August | 0.397131E+10 | 0.722885E+09 | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.00 | 0.00 |
September | 0.413741E+10 | 0.108357E+10 | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.00 | 0.00 |
October | 0.358814E+10 | 0.163243E+10 | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.00 | 0.00 |
November | 0.221001E+10 | 0.193218E+10 | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.00 | 0.00 |
December | 0.174796E+10 | 0.279325E+10 | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.366941E+11 | 0.195253E+11 | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174796E+10 | 0.545863E+09 | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.00 | 0.00 |
Maximum of Months | 0.413741E+10 | 0.284864E+10 | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.440758E+09 | 0.584372E+09 | 0.536940E+09 | 0.313428E+09 | 0.223512E+09 | 0.00 | 0.00 |
February | 0.450702E+09 | 0.512814E+09 | 0.553723E+09 | 0.267001E+09 | 0.286723E+09 | 0.00 | 0.00 |
March | 0.748891E+09 | 0.418470E+09 | 0.748269E+09 | 0.420448E+09 | 0.327821E+09 | 0.00 | 0.00 |
April | 0.633302E+09 | 0.311863E+09 | 0.599695E+09 | 0.239640E+09 | 0.360055E+09 | 0.00 | 0.00 |
May | 0.627008E+09 | 0.214680E+09 | 0.542279E+09 | 0.157501E+09 | 0.384778E+09 | 0.00 | 0.00 |
June | 0.634867E+09 | 0.145066E+09 | 0.509923E+09 | 0.108055E+09 | 0.401868E+09 | 0.00 | 0.00 |
July | 0.713522E+09 | 0.114310E+09 | 0.537900E+09 | 0.130512E+09 | 0.407388E+09 | 0.00 | 0.00 |
August | 0.791320E+09 | 0.150194E+09 | 0.603882E+09 | 0.195794E+09 | 0.408088E+09 | 0.00 | 0.00 |
September | 0.849764E+09 | 0.211062E+09 | 0.679485E+09 | 0.330960E+09 | 0.348525E+09 | 0.00 | 0.00 |
October | 0.735545E+09 | 0.322418E+09 | 0.671839E+09 | 0.383767E+09 | 0.288072E+09 | 0.00 | 0.00 |
November | 0.447909E+09 | 0.390239E+09 | 0.465636E+09 | 0.262867E+09 | 0.202769E+09 | 0.00 | 0.00 |
December | 0.349077E+09 | 0.573554E+09 | 0.448988E+09 | 0.232372E+09 | 0.216617E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.742267E+10 | 0.394904E+10 | 0.689856E+10 | 0.304234E+10 | 0.385622E+10 | 0.00 | 0.00 |
Minimum of Months | 0.349077E+09 | 0.114310E+09 | 0.448988E+09 | 0.108055E+09 | 0.202769E+09 | 0.00 | 0.00 |
Maximum of Months | 0.849764E+09 | 0.584372E+09 | 0.748269E+09 | 0.420448E+09 | 0.408088E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288489E+10 | -0.244829E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436595296.3 | 58.99 | 0.00 | 0.00 |
February | 0.265618E+10 | -0.226169E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -394488415.6 | 58.99 | 0.00 | 0.00 |
March | 0.295980E+10 | -0.253116E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -428631536.2 | 58.99 | 0.00 | 0.00 |
April | 0.272166E+10 | -0.231155E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -410106166.1 | 58.99 | 0.00 | 0.00 |
May | 0.266178E+10 | -0.225593E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -405854153.7 | 59.00 | 0.00 | 0.00 |
June | 0.245101E+10 | -0.207663E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -374384887.3 | 58.99 | 0.00 | 0.00 |
July | 0.236347E+10 | -0.198184E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -381625676.4 | 58.99 | 0.00 | 0.00 |
August | 0.238892E+10 | -0.200620E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382720742.8 | 58.99 | 0.00 | 0.00 |
September | 0.232047E+10 | -0.194288E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -377590548.6 | 58.99 | 0.00 | 0.00 |
October | 0.249141E+10 | -0.207663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -414777761.8 | 58.99 | 0.00 | 0.00 |
November | 0.254244E+10 | -0.213047E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -411968781.7 | 59.00 | 0.00 | 0.00 |
December | 0.278376E+10 | -0.234892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -434838420.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312258E+11 | -0.263722E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.485358E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.232047E+10 | -0.253116E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -436595296.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.295980E+10 | -0.194288E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374384887.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.89 | 0.67 | 22-JAN-11:30 | 240.94 | 7.05 | 0.00 | 1.67 | 184.65 | 5.55 | 0.00 | 0.00 |
February | 262.50 | 0.80 | 0.50 | 10-FEB-12:09 | 767.93 | 8.74 | 0.00 | 52.17 | 257.01 | 7.21 | 0.00 | 3.00 |
March | 339.33 | 0.80 | 0.50 | 10-MAR-11:50 | 382.68 | 8.56 | 0.00 | 47.50 | 269.01 | 7.00 | 0.00 | 20.00 |
April | 371.17 | 0.75 | 0.50 | 01-APR-11:09 | 976.72 | 9.50 | 0.00 | 139.33 | 318.01 | 7.92 | 0.00 | 66.33 |
May | 332.17 | 0.74 | 0.50 | 01-MAY-10:39 | 2574.75 | 10.08 | 0.00 | 125.83 | 2704.09 | 8.35 | 0.00 | 83.67 |
June | 430.67 | 0.75 | 0.50 | 01-JUN-09:50 | 412.95 | 10.88 | 0.00 | 136.67 | 345.46 | 9.06 | 0.00 | 91.33 |
July | 439.00 | 0.75 | 0.50 | 01-JUL-10:20 | 500.33 | 10.71 | 0.00 | 143.83 | 468.63 | 8.98 | 0.00 | 89.17 |
August | 406.00 | 0.74 | 0.50 | 01-AUG-08:50 | 1900.12 | 10.30 | 0.00 | 155.83 | 1904.45 | 8.61 | 0.00 | 102.17 |
September | 289.17 | 0.77 | 0.50 | 01-SEP-09:50 | 376.36 | 8.85 | 0.00 | 73.33 | 313.32 | 7.28 | 0.00 | 44.83 |
October | 314.33 | 0.83 | 0.50 | 02-OCT-12:30 | 432.11 | 7.98 | 0.00 | 13.50 | 395.63 | 6.45 | 0.00 | 6.00 |
November | 258.33 | 0.85 | 0.50 | 01-NOV-11:09 | 666.31 | 6.93 | 0.00 | 29.83 | 669.45 | 5.49 | 0.00 | 28.17 |
December | 230.67 | 0.89 | 0.67 | 09-DEC-10:39 | 229.62 | 7.28 | 0.00 | 0.00 | 186.34 | 5.79 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.79 | 827.13 | 9.16 | 0.00 | 919.50 | 707.83 | 7.54 | 0.00 | 534.67 | ||
Minimum of Months | 230.67 | 0.74 | 0.50 | 229.62 | 6.93 | 0.00 | 0.00 | 184.65 | 5.49 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.89 | 0.67 | 2574.75 | 10.88 | 0.00 | 155.83 | 2704.09 | 9.06 | 0.00 | 102.17 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233431E+11 | 44710.18 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222268E+11 | 44710.18 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139183E+11 | 44710.18 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537905E+10 | 44710.18 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345503E+09 | 40379.79 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17566304.30 | 4160.98 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205509E+10 | 44710.18 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724073E+10 | 44710.18 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207727E+11 | 44710.18 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.952989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233431E+11 | 44710.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160573E+11 | 255091.07 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154871E+11 | 255091.07 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394923E+10 | 255091.07 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217950E+09 | 123945.16 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5766031.22 | 4203.55 | 30-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455208E+09 | 167932.31 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122635E+11 | 255091.07 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160573E+11 | 255091.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.745694E+10 | 35803.06 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717597E+10 | 35803.06 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248823E+10 | 35803.06 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.705586E+09 | 35803.06 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21813913.44 | 3334.93 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 191822.14 | 171.88 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153099E+09 | 19586.34 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100034E+10 | 35803.06 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.667966E+10 | 35803.06 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.745694E+10 | 35803.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103938E+11 | 30817.81 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.982014E+10 | 30817.81 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451361E+10 | 30817.81 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171932E+10 | 30817.81 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128136E+09 | 16241.67 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12627261.90 | 2170.79 | 30-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568141E+09 | 30817.81 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257415E+10 | 30817.81 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.956276E+10 | 30817.81 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103938E+11 | 30817.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214578E+11 | 42017.15 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200086E+11 | 45462.26 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144147E+11 | 36809.44 | 06-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834259E+10 | 29131.32 | 16-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310935E+10 | 13451.49 | 11-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704845E+09 | 11729.75 | 13-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4443569.81 | 1480.19 | 02-JUL-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156568E+09 | 6508.45 | 31-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106473E+10 | 11310.65 | 28-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688730E+10 | 19373.87 | 08-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109885E+11 | 24574.80 | 23-NOV-17:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205745E+11 | 43068.68 | 10-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4443569.81 | 1480.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214578E+11 | 45462.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 15569901.55 | 14447634.38 | 2116.23 | 15-MAR-16:10 | 1956.64 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.108758E+09 | 99776523.36 | 3278.69 | 10-MAY-14:30 | 2706.08 | 0.00 |
June | 0.00 | 0.00 | 0.445628E+10 | 0.332900E+10 | 33381.44 | 18-JUN-08:62 | 17309.77 | 0.00 |
July | 0.00 | 0.00 | 0.110213E+11 | 0.767200E+10 | 34238.41 | 21-JUL-05:02 | 16235.26 | 0.00 |
August | 0.00 | 0.00 | 0.809210E+10 | 0.631460E+10 | 33490.29 | 14-AUG-06:02 | 15290.71 | 0.00 |
September | 0.00 | 0.00 | 0.206796E+10 | 0.145516E+10 | 32403.96 | 16-SEP-06:02 | 17433.69 | 0.00 |
October | 0.00 | 0.00 | 202.11 | 154.25 | 0.10 | 12-OCT-15:10 | 0.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.257620E+11 | 0.188850E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110213E+11 | 0.767200E+10 | 34238.41 | 17433.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175445E+10 | 0.138641E+10 | 37422.04 | 15-MAR-14:50 | 31317.81 | 0.00 |
April | 0.00 | 0.00 | 0.277440E+09 | 0.249894E+09 | 16820.17 | 08-APR-13:40 | 14806.28 | 0.00 |
May | 0.00 | 0.00 | 0.811528E+10 | 0.720515E+10 | 165951.91 | 24-MAY-06:02 | 119032.89 | 0.00 |
June | 0.00 | 0.00 | 0.428135E+11 | 0.322018E+11 | 184477.21 | 18-JUN-08:62 | 97819.42 | 0.00 |
July | 0.00 | 0.00 | 0.748178E+11 | 0.518175E+11 | 186501.04 | 21-JUL-05:02 | 99991.82 | 0.00 |
August | 0.00 | 0.00 | 0.598237E+11 | 0.450041E+11 | 183936.25 | 14-AUG-06:02 | 89838.36 | 0.00 |
September | 0.00 | 0.00 | 0.260175E+11 | 0.186311E+11 | 178871.58 | 16-SEP-06:02 | 99722.40 | 0.00 |
October | 0.00 | 0.00 | 0.156097E+10 | 0.132319E+10 | 131091.90 | 12-OCT-06:02 | 95201.81 | 0.00 |
November | 0.00 | 0.00 | 19835084.83 | 17482949.64 | 5142.54 | 04-NOV-17:10 | 4094.83 | 0.00 |
December | 0.00 | 0.00 | 847514.53 | 682498.93 | 492.45 | 01-DEC-11:20 | 409.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.215201E+12 | 0.157837E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.748178E+11 | 0.518175E+11 | 186501.04 | 119032.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.438340E+09 | 0.379837E+09 | 9190.68 | 15-MAR-13:40 | 8711.87 | 0.00 |
April | 0.00 | 0.00 | 0.149861E+09 | 0.144307E+09 | 4750.28 | 08-APR-13:40 | 4415.98 | 0.00 |
May | 0.00 | 0.00 | 0.159334E+10 | 0.146298E+10 | 23630.91 | 24-MAY-06:02 | 16639.64 | 0.00 |
June | 0.00 | 0.00 | 0.745428E+10 | 0.583132E+10 | 26185.98 | 18-JUN-08:62 | 13752.02 | 0.00 |
July | 0.00 | 0.00 | 0.135252E+11 | 0.983429E+10 | 26871.94 | 21-JUL-05:02 | 13173.76 | 0.00 |
August | 0.00 | 0.00 | 0.117209E+11 | 0.936795E+10 | 26234.98 | 14-AUG-06:02 | 12012.37 | 0.00 |
September | 0.00 | 0.00 | 0.628111E+10 | 0.487578E+10 | 25349.37 | 16-SEP-06:02 | 14152.29 | 0.00 |
October | 0.00 | 0.00 | 0.942702E+09 | 0.819042E+09 | 22364.23 | 12-OCT-06:02 | 16969.63 | 0.00 |
November | 0.00 | 0.00 | 18097599.15 | 15124777.34 | 1726.14 | 16-NOV-12:40 | 1555.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.421238E+11 | 0.327306E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135252E+11 | 0.983429E+10 | 26871.94 | 16969.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.247848E+09 | 0.212052E+09 | 6663.56 | 15-MAR-13:40 | 6176.74 | 0.00 |
April | 0.00 | 0.00 | 36449751.03 | 33841550.44 | 2767.09 | 08-APR-13:30 | 2531.40 | 0.00 |
May | 0.00 | 0.00 | 0.787318E+09 | 0.717057E+09 | 7669.27 | 24-MAY-06:02 | 5116.67 | 0.00 |
June | 0.00 | 0.00 | 0.498917E+10 | 0.379540E+10 | 22402.11 | 18-JUN-08:62 | 11675.36 | 0.00 |
July | 0.00 | 0.00 | 0.100897E+11 | 0.712779E+10 | 22992.50 | 21-JUL-05:02 | 10911.35 | 0.00 |
August | 0.00 | 0.00 | 0.862190E+10 | 0.678598E+10 | 22469.76 | 14-AUG-06:02 | 10158.28 | 0.00 |
September | 0.00 | 0.00 | 0.419177E+10 | 0.320579E+10 | 21731.80 | 16-SEP-06:02 | 11851.15 | 0.00 |
October | 0.00 | 0.00 | 0.487359E+09 | 0.418871E+09 | 9817.99 | 12-OCT-06:02 | 7095.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.294515E+11 | 0.222968E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100897E+11 | 0.712779E+10 | 22992.50 | 11851.15 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.496881E+09 | 0.06 | 238.74 | 01-JAN-00:10 | 0.08 |
February | 0.465563E+09 | 0.06 | 238.74 | 01-FEB-00:20 | 0.08 |
March | 0.385096E+09 | 0.05 | 238.74 | 01-MAR-05:01 | 0.08 |
April | 0.347663E+09 | 0.04 | 238.74 | 01-APR-05:02 | 0.08 |
May | 0.248957E+09 | 0.03 | 238.74 | 01-MAY-05:10 | 0.08 |
June | 93529426.72 | 0.01 | 238.74 | 01-JUN-07:06 | 0.08 |
July | 3281260.58 | 0.00 | 238.74 | 02-JUL-11:05 | 0.08 |
August | 27549060.24 | 0.00 | 238.74 | 01-AUG-07:07 | 0.08 |
September | 0.136379E+09 | 0.02 | 238.74 | 01-SEP-07:10 | 0.08 |
October | 0.303113E+09 | 0.04 | 238.74 | 01-OCT-07:06 | 0.08 |
November | 0.355470E+09 | 0.04 | 238.74 | 01-NOV-07:10 | 0.08 |
December | 0.478030E+09 | 0.06 | 238.74 | 01-DEC-06:02 | 0.08 |
Annual Sum or Average | 0.334151E+10 | 0.03 | |||
Minimum of Months | 3281260.58 | 0.00 | 238.74 | 0.08 | |
Maximum of Months | 0.496881E+09 | 0.06 | 238.74 | 0.08 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158308E+10 | 0.45 | 1644.01 | 01-JAN-07:01 | 0.90 |
February | 0.146671E+10 | 0.47 | 1644.01 | 01-FEB-05:01 | 0.90 |
March | 0.138488E+10 | 0.40 | 1644.01 | 01-MAR-05:01 | 0.90 |
April | 0.114882E+10 | 0.35 | 1644.01 | 01-APR-05:02 | 0.90 |
May | 0.107057E+10 | 0.33 | 1548.47 | 01-MAY-06:03 | 0.87 |
June | 0.103845E+10 | 0.33 | 1644.01 | 12-JUN-06:02 | 0.89 |
July | 0.106300E+10 | 0.32 | 1644.01 | 02-JUL-08:62 | 0.89 |
August | 0.107695E+10 | 0.33 | 1644.01 | 01-AUG-06:02 | 0.89 |
September | 0.103088E+10 | 0.33 | 1644.01 | 14-SEP-06:02 | 0.88 |
October | 0.109882E+10 | 0.33 | 1644.01 | 16-OCT-06:03 | 0.90 |
November | 0.117557E+10 | 0.36 | 1644.01 | 03-NOV-05:02 | 0.90 |
December | 0.152625E+10 | 0.43 | 1644.01 | 01-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.146640E+11 | 0.37 | |||
Minimum of Months | 0.103088E+10 | 0.32 | 1548.47 | 0.87 | |
Maximum of Months | 0.158308E+10 | 0.47 | 1644.01 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.897779E+10 | 0.53 | 13230.48 | 01-JAN-08:61 | 1.42 |
February | 0.818140E+10 | 0.54 | 13230.48 | 01-FEB-06:01 | 1.42 |
March | 0.875341E+10 | 0.53 | 13230.48 | 01-MAR-06:01 | 1.42 |
April | 0.829436E+10 | 0.52 | 9149.30 | 17-APR-06:03 | 1.19 |
May | 0.855800E+10 | 0.52 | 13230.48 | 17-MAY-06:03 | 1.41 |
June | 0.837775E+10 | 0.52 | 13230.48 | 01-JUN-06:02 | 1.40 |
July | 0.855188E+10 | 0.51 | 13230.48 | 01-JUL-06:02 | 1.41 |
August | 0.867174E+10 | 0.52 | 13230.48 | 01-AUG-06:02 | 1.41 |
September | 0.831167E+10 | 0.52 | 13230.48 | 01-SEP-06:03 | 1.40 |
October | 0.847944E+10 | 0.51 | 10541.78 | 12-OCT-06:02 | 1.27 |
November | 0.818743E+10 | 0.51 | 10518.15 | 24-NOV-07:03 | 1.28 |
December | 0.887949E+10 | 0.53 | 13230.48 | 07-DEC-06:01 | 1.42 |
Annual Sum or Average | 0.102224E+12 | 0.52 | |||
Minimum of Months | 0.818140E+10 | 0.51 | 9149.30 | 1.19 | |
Maximum of Months | 0.897779E+10 | 0.54 | 13230.48 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105991E+10 | 0.40 | 1377.65 | 01-JAN-07:01 | 0.93 |
February | 0.974520E+09 | 0.42 | 1377.65 | 01-FEB-06:01 | 0.93 |
March | 0.956848E+09 | 0.36 | 1377.65 | 01-MAR-06:01 | 0.93 |
April | 0.879305E+09 | 0.34 | 1377.65 | 05-APR-05:01 | 0.93 |
May | 0.891390E+09 | 0.34 | 1377.65 | 24-MAY-06:02 | 0.92 |
June | 0.875689E+09 | 0.34 | 1377.65 | 02-JUN-06:02 | 0.92 |
July | 0.919467E+09 | 0.34 | 1377.65 | 01-JUL-06:02 | 0.92 |
August | 0.922334E+09 | 0.35 | 1377.65 | 01-AUG-06:02 | 0.92 |
September | 0.869086E+09 | 0.34 | 1377.65 | 08-SEP-06:02 | 0.92 |
October | 0.886433E+09 | 0.34 | 1377.65 | 12-OCT-06:02 | 0.93 |
November | 0.874185E+09 | 0.34 | 1377.65 | 24-NOV-06:01 | 0.93 |
December | 0.104284E+10 | 0.39 | 1377.65 | 02-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.111520E+11 | 0.36 | |||
Minimum of Months | 0.869086E+09 | 0.34 | 1377.65 | 0.92 | |
Maximum of Months | 0.105991E+10 | 0.42 | 1377.65 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.961583E+09 | 0.44 | 1132.18 | 01-JAN-07:01 | 0.93 |
February | 0.884979E+09 | 0.46 | 1132.18 | 01-FEB-05:01 | 0.93 |
March | 0.839543E+09 | 0.38 | 1132.18 | 01-MAR-06:01 | 0.93 |
April | 0.747301E+09 | 0.35 | 1132.18 | 03-APR-05:02 | 0.93 |
May | 0.734847E+09 | 0.34 | 810.88 | 01-MAY-06:03 | 0.79 |
June | 0.717137E+09 | 0.34 | 1132.18 | 02-JUN-06:02 | 0.92 |
July | 0.744947E+09 | 0.34 | 1132.18 | 02-JUL-08:62 | 0.92 |
August | 0.750362E+09 | 0.34 | 1132.18 | 01-AUG-06:02 | 0.92 |
September | 0.711781E+09 | 0.34 | 1132.18 | 09-SEP-06:02 | 0.92 |
October | 0.738027E+09 | 0.34 | 1132.18 | 30-OCT-05:02 | 0.93 |
November | 0.756268E+09 | 0.35 | 1132.18 | 12-NOV-08:62 | 0.93 |
December | 0.943546E+09 | 0.43 | 1132.18 | 02-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.953032E+10 | 0.37 | |||
Minimum of Months | 0.711781E+09 | 0.34 | 810.88 | 0.79 | |
Maximum of Months | 0.961583E+09 | 0.46 | 1132.18 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158308E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146671E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138949E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114882E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110158E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.218247E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.379749E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314141E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.156524E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.117557E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152625E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211769E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.379749E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.897779E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.818140E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.927595E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.837891E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109076E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.202549E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.288360E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252472E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155296E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.894419E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.819369E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.887976E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161607E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.818140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.288360E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.105991E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.974520E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106656E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.918935E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129355E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.266136E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.406747E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.367806E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.234506E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.112062E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.879182E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104284E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211081E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.879182E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.406747E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.961583E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.884979E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.903795E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.757084E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.938436E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.193384E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.313141E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.280881E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171306E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.860761E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.756268E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.943546E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.756268E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.313141E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158308E+10 | 0.00 | 0.233431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146671E+10 | 0.00 | 0.222268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138488E+10 | 15569901.55 | 0.139183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114882E+10 | 0.00 | 0.537905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107057E+10 | 0.108758E+09 | 0.345503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103845E+10 | 0.445628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106300E+10 | 0.110213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107695E+10 | 0.809210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103088E+10 | 0.206796E+10 | 17566304.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109882E+10 | 202.11 | 0.205509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117557E+10 | 0.00 | 0.724073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152625E+10 | 0.00 | 0.207727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146640E+11 | 0.257620E+11 | 0.952989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158308E+10 | 0.110213E+11 | 0.233431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.897779E+10 | 0.00 | 0.160573E+11 | 0.661751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.818140E+10 | 0.00 | 0.154871E+11 | 0.612633E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875341E+10 | 0.175445E+10 | 0.394923E+10 | 0.524231E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829436E+10 | 0.277440E+09 | 0.217950E+09 | 0.314392E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.855800E+10 | 0.811528E+10 | 0.00 | 0.673102E+10 | 99789409.07 | 0.00 | 0.00 | 0.00 |
June | 0.837775E+10 | 0.428135E+11 | 0.00 | 0.111425E+10 | 0.395260E+10 | 0.00 | 0.00 | 0.00 |
July | 0.855188E+10 | 0.748178E+11 | 0.00 | 0.122582E+09 | 0.985251E+10 | 0.00 | 0.00 | 0.00 |
August | 0.867174E+10 | 0.598237E+11 | 0.00 | 0.559101E+09 | 0.517920E+10 | 0.00 | 0.00 | 0.00 |
September | 0.831167E+10 | 0.260175E+11 | 0.00 | 0.255767E+10 | 0.751980E+09 | 0.00 | 0.00 | 0.00 |
October | 0.847944E+10 | 0.156097E+10 | 5766031.22 | 0.230606E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818743E+10 | 19835084.83 | 0.455208E+09 | 0.429005E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.887949E+10 | 847514.53 | 0.122635E+11 | 0.642267E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102224E+12 | 0.215201E+12 | 0.484360E+11 | 0.352573E+12 | 0.198361E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.818140E+10 | 0.00 | 0.00 | 0.122582E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.897779E+10 | 0.748178E+11 | 0.160573E+11 | 0.661751E+11 | 0.985251E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105991E+10 | 0.00 | 0.745694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.974520E+09 | 0.00 | 0.717597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956848E+09 | 0.438340E+09 | 0.248823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879305E+09 | 0.149861E+09 | 0.705586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.891390E+09 | 0.159334E+10 | 21813913.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875689E+09 | 0.745428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.919467E+09 | 0.135252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.922334E+09 | 0.117209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.869086E+09 | 0.628111E+10 | 191822.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886433E+09 | 0.942702E+09 | 0.153099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874185E+09 | 18097599.15 | 0.100034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104284E+10 | 0.00 | 0.667966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111520E+11 | 0.421238E+11 | 0.256818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.869086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105991E+10 | 0.135252E+11 | 0.745694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.961583E+09 | 0.00 | 0.103938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884979E+09 | 0.00 | 0.982014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839543E+09 | 0.247848E+09 | 0.451361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747301E+09 | 36449751.03 | 0.171932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.734847E+09 | 0.787318E+09 | 0.128136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717137E+09 | 0.498917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.744947E+09 | 0.100897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750362E+09 | 0.862190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.711781E+09 | 0.419177E+10 | 12627261.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.738027E+09 | 0.487359E+09 | 0.568141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756268E+09 | 0.00 | 0.257415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943546E+09 | 0.00 | 0.956276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953032E+10 | 0.294515E+11 | 0.392927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.711781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961583E+09 | 0.100897E+11 | 0.103938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138488E+10 | 0.00 | 0.00 | 0.00 | 4609006.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107057E+10 | 0.00 | 0.00 | 0.00 | 31004536.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103845E+10 | 0.00 | 0.00 | 0.00 | 0.114402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106300E+10 | 0.00 | 0.00 | 0.00 | 0.273449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107695E+10 | 0.00 | 0.00 | 0.00 | 0.206446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103088E+10 | 0.00 | 0.00 | 0.00 | 0.534361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109882E+10 | 0.00 | 0.00 | 0.00 | 57.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146640E+11 | 0.00 | 0.00 | 0.00 | 0.651295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158308E+10 | 0.00 | 0.00 | 0.00 | 0.273449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.897779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.818140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875341E+10 | 0.00 | 0.00 | 0.00 | 0.522543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829436E+10 | 0.00 | 0.00 | 0.00 | 84553376.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.855800E+10 | 0.00 | 0.00 | 0.00 | 0.234963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.837775E+10 | 0.00 | 0.00 | 0.00 | 0.118772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.855188E+10 | 0.00 | 0.00 | 0.00 | 0.202841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.867174E+10 | 0.00 | 0.00 | 0.00 | 0.165755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831167E+10 | 0.00 | 0.00 | 0.00 | 0.721792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.847944E+10 | 0.00 | 0.00 | 0.00 | 0.464751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818743E+10 | 0.00 | 0.00 | 0.00 | 6258630.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.887949E+10 | 0.00 | 0.00 | 0.00 | 268997.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102224E+12 | 0.00 | 0.00 | 0.00 | 0.593827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.818140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.897779E+10 | 0.00 | 0.00 | 0.00 | 0.202841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.974520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956848E+09 | 0.00 | 0.00 | 0.00 | 0.109715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879305E+09 | 0.00 | 0.00 | 0.00 | 39630198.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.891390E+09 | 0.00 | 0.00 | 0.00 | 0.402164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.875689E+09 | 0.00 | 0.00 | 0.00 | 0.178567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.919467E+09 | 0.00 | 0.00 | 0.00 | 0.314800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.922334E+09 | 0.00 | 0.00 | 0.00 | 0.275573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.869086E+09 | 0.00 | 0.00 | 0.00 | 0.147598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886433E+09 | 0.00 | 0.00 | 0.00 | 0.234187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874185E+09 | 0.00 | 0.00 | 0.00 | 4996601.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111520E+11 | 0.00 | 0.00 | 0.00 | 0.995607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.869086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.105991E+10 | 0.00 | 0.00 | 0.00 | 0.314800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.961583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839543E+09 | 0.00 | 0.00 | 0.00 | 64251506.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.747301E+09 | 0.00 | 0.00 | 0.00 | 9782386.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.734847E+09 | 0.00 | 0.00 | 0.00 | 0.203589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717137E+09 | 0.00 | 0.00 | 0.00 | 0.121671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.744947E+09 | 0.00 | 0.00 | 0.00 | 0.238646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750362E+09 | 0.00 | 0.00 | 0.00 | 0.205844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.711781E+09 | 0.00 | 0.00 | 0.00 | 0.100128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.738027E+09 | 0.00 | 0.00 | 0.00 | 0.122734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953032E+10 | 0.00 | 0.00 | 0.00 | 0.706325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.711781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961583E+09 | 0.00 | 0.00 | 0.00 | 0.238646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2201611.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998045E+10 | 0.00 | 0.00 | 0.20 |
February | 752349.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929275E+10 | 0.00 | 0.00 | 0.20 |
March | 0.510627E+09 | 500078.47 | 109545.32 | 0.00 | 12633196.24 | 0.692626E+10 | 0.00 | 1273.07 | 0.20 |
April | 0.192132E+10 | 0.00 | 0.00 | 0.00 | 182978.42 | 0.311703E+10 | 0.00 | 0.00 | 0.20 |
May | 0.282830E+10 | 14982581.37 | 0.00 | 336468.32 | 17782799.71 | 0.190379E+09 | 0.275777E+09 | 0.00 | 0.23 |
June | 0.684955E+09 | 0.916903E+09 | 0.00 | 4513604.45 | 2296098.21 | 0.00 | 0.197059E+10 | 0.00 | 0.38 |
July | 48976838.29 | 0.257196E+10 | 0.00 | 4158002.12 | 7288440.29 | 0.00 | 0.743010E+09 | 0.00 | 0.40 |
August | 0.175025E+09 | 0.144431E+10 | 0.00 | 6773890.68 | 1528514.65 | 0.00 | 0.166697E+10 | 0.00 | 0.41 |
September | 0.120390E+10 | 0.320203E+09 | 0.00 | 3668479.48 | 941451.09 | 1167853.40 | 0.195906E+10 | 0.00 | 0.37 |
October | 0.359006E+10 | 0.00 | 0.00 | 28924.43 | 832061.25 | 0.974904E+09 | 37126978.10 | 0.00 | 0.20 |
November | 0.122950E+10 | 0.00 | 24587.89 | 0.00 | 135932.65 | 0.454009E+10 | 0.00 | 51682.63 | 0.20 |
December | 8764951.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952675E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.122044E+11 | 0.526885E+10 | 134133.21 | 19479369.47 | 43621472.51 | 0.445498E+11 | 0.665254E+10 | 52955.70 | 0.27 |
Minimum of Months | 752349.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.359006E+10 | 0.257196E+10 | 109545.32 | 6773890.68 | 17782799.71 | 0.998045E+10 | 0.197059E+10 | 51682.63 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102684E+11 | 0.00 | 0.00 | 0.39 |
February | 0.182639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101259E+11 | 0.00 | 0.00 | 0.39 |
March | 0.196852E+11 | 0.00 | 0.00 | 6698076.52 | 0.00 | 0.245989E+10 | 0.628171E+10 | 0.00 | 0.41 |
April | 0.837709E+10 | 0.00 | 0.00 | 19949365.60 | 0.00 | 94253972.62 | 0.229451E+11 | 0.00 | 0.42 |
May | 0.121532E+10 | 79364943.35 | 0.00 | 51342685.63 | 2807103.35 | 0.00 | 0.372101E+11 | 0.00 | 0.55 |
June | 0.179139E+09 | 0.389956E+10 | 0.00 | 59500663.66 | 43580379.32 | 0.00 | 0.226567E+11 | 0.00 | 0.63 |
July | 0.106756E+09 | 0.110760E+11 | 0.00 | 30054591.55 | 74633694.16 | 0.00 | 0.475444E+10 | 0.00 | 0.58 |
August | 0.220331E+09 | 0.543339E+10 | 0.00 | 64048361.26 | 17881751.76 | 0.00 | 0.124844E+11 | 0.00 | 0.61 |
September | 0.371708E+09 | 0.176633E+10 | 0.00 | 61496305.71 | 8433805.37 | 0.00 | 0.284295E+11 | 0.00 | 0.64 |
October | 0.450761E+10 | 923652.22 | 0.00 | 31950211.21 | 3218390.91 | 0.00 | 0.304348E+11 | 0.00 | 0.45 |
November | 0.142876E+11 | 0.00 | 0.00 | 8637399.77 | 0.00 | 0.307348E+09 | 0.118387E+11 | 0.00 | 0.40 |
December | 0.215029E+11 | 0.00 | 0.00 | 277579.46 | 0.00 | 0.808222E+10 | 0.509440E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.109181E+12 | 0.222556E+11 | 0.00 | 0.333955E+09 | 0.150555E+09 | 0.313381E+11 | 0.177545E+12 | 0.00 | 0.49 |
Minimum of Months | 0.106756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.215029E+11 | 0.110760E+11 | 0.00 | 64048361.26 | 74633694.16 | 0.102684E+11 | 0.372101E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.479072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333151E+10 | 0.00 | 0.00 | 0.39 |
February | 0.424767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331589E+10 | 0.00 | 0.00 | 0.39 |
March | 0.486416E+10 | 4206655.61 | 0.00 | 1306474.09 | 0.00 | 0.877330E+09 | 0.857276E+09 | 0.00 | 0.44 |
April | 0.259566E+10 | 0.00 | 0.00 | 3761504.07 | 0.00 | 0.301475E+09 | 0.304008E+10 | 0.00 | 0.56 |
May | 0.664175E+09 | 25128938.11 | 0.00 | 8710633.18 | 13766.14 | 0.00 | 0.498082E+10 | 0.00 | 0.86 |
June | 0.133727E+09 | 0.859156E+09 | 0.00 | 9211540.38 | 504995.98 | 0.00 | 0.303392E+10 | 0.00 | 0.96 |
July | 18613216.87 | 0.244994E+10 | 0.00 | 4723525.05 | 536768.33 | 0.00 | 0.710886E+09 | 0.00 | 0.84 |
August | 39903734.70 | 0.132530E+10 | 0.00 | 10157730.99 | 181060.36 | 0.00 | 0.172788E+10 | 0.00 | 0.91 |
September | 0.191399E+09 | 0.505857E+09 | 0.00 | 12373517.61 | 40988.02 | 0.00 | 0.403232E+10 | 0.00 | 1.06 |
October | 0.158626E+10 | 0.00 | 0.00 | 7684540.26 | 0.00 | 37321184.50 | 0.467486E+10 | 0.00 | 0.67 |
November | 0.374593E+10 | 0.00 | 0.00 | 1861096.61 | 0.00 | 0.330408E+09 | 0.165703E+10 | 0.00 | 0.46 |
December | 0.486935E+10 | 0.00 | 0.00 | 19881.06 | 0.00 | 0.287759E+10 | 46238068.89 | 0.00 | 0.39 |
Annual Sum or Average | 0.277476E+11 | 0.516959E+10 | 0.00 | 59810443.29 | 1277578.83 | 0.110715E+11 | 0.247613E+11 | 0.00 | 0.66 |
Minimum of Months | 18613216.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.486935E+10 | 0.244994E+10 | 0.00 | 12373517.61 | 536768.33 | 0.333151E+10 | 0.498082E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672603E+10 | 0.00 | 0.00 | 0.39 |
February | 0.145169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609809E+10 | 0.00 | 0.00 | 0.39 |
March | 0.397505E+10 | 1731759.66 | 0.00 | 373619.60 | 0.00 | 0.215250E+10 | 0.156456E+09 | 0.00 | 0.41 |
April | 0.322475E+10 | 0.00 | 0.00 | 1145549.95 | 0.00 | 0.729323E+09 | 0.997430E+09 | 0.00 | 0.45 |
May | 0.145079E+10 | 17744722.83 | 0.00 | 3711390.27 | 0.00 | 51216400.11 | 0.251332E+10 | 0.00 | 0.60 |
June | 0.351688E+09 | 0.695966E+09 | 0.00 | 5404098.85 | 1656907.80 | 0.00 | 0.216365E+10 | 0.00 | 0.75 |
July | 58169244.74 | 0.197218E+10 | 0.00 | 3216333.36 | 2422955.48 | 0.00 | 0.555065E+09 | 0.00 | 0.71 |
August | 0.102076E+09 | 0.108638E+10 | 0.00 | 6823142.08 | 519874.27 | 0.00 | 0.134807E+10 | 0.00 | 0.74 |
September | 0.544480E+09 | 0.342070E+09 | 0.00 | 7723275.62 | 160053.01 | 0.00 | 0.277040E+10 | 0.00 | 0.82 |
October | 0.285603E+10 | 0.00 | 0.00 | 3024088.28 | 0.00 | 0.209722E+09 | 0.186817E+10 | 0.00 | 0.52 |
November | 0.360644E+10 | 0.00 | 0.00 | 368953.44 | 0.00 | 0.111862E+10 | 0.388990E+09 | 0.00 | 0.40 |
December | 0.132475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644920E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.203427E+11 | 0.411608E+10 | 0.00 | 31790451.46 | 4759790.57 | 0.235347E+11 | 0.127615E+11 | 0.00 | 0.55 |
Minimum of Months | 58169244.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.397505E+10 | 0.197218E+10 | 0.00 | 7723275.62 | 2422955.48 | 0.672603E+10 | 0.277040E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.120106E+12 | 0.331287E+11 | 0.00 | 0.123135E+12 | 0.196772E+11 |
February | 0.212734E+12 | 0.321843E+11 | 0.00 | 0.114060E+12 | 0.186797E+11 |
March | 0.353424E+12 | 0.227722E+11 | 0.00 | 0.101159E+12 | 0.129784E+11 |
April | 0.450149E+12 | 0.155686E+11 | 0.00 | 0.788074E+11 | 0.468884E+10 |
May | 0.578388E+12 | 0.767680E+10 | 0.00 | 0.579177E+11 | 0.144923E+11 |
June | 0.633862E+12 | 0.326711E+10 | 0.00 | 0.219951E+11 | 0.759130E+11 |
July | 0.591142E+12 | 0.309041E+09 | 0.00 | -0.208468E+11 | 0.138008E+12 |
August | 0.498692E+12 | 0.162345E+10 | 0.00 | 0.392286E+10 | 0.111752E+12 |
September | 0.367094E+12 | 0.439945E+10 | 0.00 | 0.384508E+11 | 0.490616E+11 |
October | 0.226593E+12 | 0.132036E+11 | 0.00 | 0.738751E+11 | 0.623005E+10 |
November | 0.105571E+12 | 0.189736E+11 | 0.00 | 0.859618E+11 | 0.561392E+10 |
December | 0.104421E+12 | 0.328570E+11 | 0.00 | 0.119424E+12 | 0.174644E+11 |
Annual Sum or Average | 0.424217E+13 | 0.185964E+12 | 0.00 | 0.797862E+12 | 0.474559E+12 |
Minimum of Months | 0.104421E+12 | 0.309041E+09 | 0.00 | -0.208468E+11 | 0.468884E+10 |
Maximum of Months | 0.633862E+12 | 0.331287E+11 | 0.00 | 0.123135E+12 | 0.138008E+12 |