Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31

Tabular Output Report in Format: HTML

Building: RetailStandalone

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:31:08


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 955.82 416.66 416.66
Net Site Energy 955.82 416.66 416.66
Total Source Energy 2830.75 1233.98 1233.98
Net Source Energy 2830.75 1233.98 1233.98


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 2293.99
Net Conditioned Building Area 2293.99
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 6.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 275.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 143.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 87.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 861.57 94.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 6.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 275.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 43.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 143.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 87.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 6.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 275.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 205.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 43.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 194.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 143.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 87.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.99
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 108.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 182.41 41.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 375.57 41.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 108.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 182.41 41.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06
Other 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 375.57 41.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.06


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 861.565 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 861.565 100.00
     
Total On-Site and Utility Electric Sources 861.565 100.00
Total Electricity End Uses 861.565 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 134.99 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 134.99 100.00
Total Water End Uses 134.99 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 95.83
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3072.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneHeatingSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ZoneElectricSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

PeakSpaceGainsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

SpaceGainComponentsAtCoolingPeakMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

ComfortReportSimple55Monthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

OccupantComfortDataSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

DXReportMonthly

| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |

WindowReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowEnergyReportMonthly

| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |

WindowZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

WindowEnergyZoneSummaryMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |

FanReportMonthly

| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |

ZoneTemperatureOscillationReportMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |

MechanicalVentilationLoadsMonthly

| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:31
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Above Ground Wall Area [m2] 1177.02 330.83 257.68 330.83 257.68
Window Opening Area [m2] 83.95 0.00 0.00 83.95 0.00
Gross Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00
Above Ground Window-Wall Ratio [%] 7.13 0.00 0.00 25.37 0.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 2293.99
Skylight Area [m2] 23.78
Skylight-Roof Ratio [%] 1.04


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BACK_SPACE 379.89 Yes Yes 2317.33 1.00 416.17 0.00 0.00 0.00 4.2065 46.45 8.0700
CORE_RETAIL 1600.48 Yes Yes 9762.95 1.00 356.86 0.00 0.00 0.00 10.1719 6.19 3.2300
POINT_OF_SALE 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 10.1719 6.19 21.5200
FRONT_RETAIL 150.81 Yes Yes 919.94 1.00 189.80 0.00 38.06 38.06 10.1719 6.19 3.2300
FRONT_ENTRY 12.00 Yes Yes 73.20 1.00 24.38 0.00 7.83 7.83 6.7813 6.19 0.0000
Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 9.1663 7.23 5.2170
Conditioned Total 2293.99     13993.36   1177.02 0.00 83.95 83.95 9.1663 7.23 5.2170
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BACK_SPACE 379.89 Yes Yes 1.00 BACK_SPACE GENERAL BACK_SPACE 4.2065 46.45 8.0700  
CORE_RETAIL 1600.48 Yes Yes 1.00 CORE_RETAIL GENERAL CORE_RETAIL 10.1719 6.19 3.2300  
POINT_OF_SALE 150.81 Yes Yes 1.00 POINT_OF_SALE GENERAL POINT_OF_SALE 10.1719 6.19 21.5200  
FRONT_RETAIL 150.81 Yes Yes 1.00 FRONT_RETAIL GENERAL FRONT_RETAIL 10.1719 6.19 3.2300  
FRONT_ENTRY 12.00 Yes Yes 1.00 FRONT_ENTRY GENERAL FRONT_ENTRY 6.7813 6.19 0.0000  
Total 2293.99             9.1663 3.62 5.2170  
Conditioned Total 2293.99             9.1663 3.62 5.2170  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 2293.99 2293.99 0.00 0.00 9.1663 7.23 5.2170
Total 2293.99 2293.99 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUN-14:00 02-JAN-07:10 - - - - - - - - - - 09-JAN-12:09
Heating 0.00 80451.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 53763.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 13181.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 12168.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 3257.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 89854.22 83709.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 80451.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 53763.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 13181.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 12168.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 3257.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 7.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 871.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 651.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 136.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 615.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 453.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 94.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2728.58 102.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 3.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 379.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 284.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 197.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 41.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1189.44 44.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 3.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 379.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 284.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 59.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 268.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 197.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 41.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1189.44 44.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BACK_SPACE DIRECT AIR 1.95
CORE_RETAIL DIRECT AIR 7.79
POINT_OF_SALE DIRECT AIR 1.36
FRONT_RETAIL DIRECT AIR 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER 1.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
FRONT_ENTRY UNIT HEATER FAN 1.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
FRONT_ENTRY UNIT HEATER HEATING COIL 31372.90
PSZ-AC:1 HEATING COIL 46053.00
PSZ-AC:2 HEATING COIL 206530.17
PSZ-AC:3 HEATING COIL 32569.52
PSZ-AC:4 HEATING COIL 27854.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 1.95 1.95 1.95 1.95 1.95 1.95 1.00 0.998668 1.95
PSZ-AC:2 7.79 7.79 7.79 7.79 8.03 8.03 1.00 0.970430 8.03
PSZ-AC:3 1.36 1.36 1.36 1.36 1.36 1.36 1.00 1.00 1.36
PSZ-AC:4 1.14 1.14 1.14 1.14 1.14 1.14 1.00 1.00 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 1.95
PSZ-AC:2_OA_CONTROLLER 8.03
PSZ-AC:3_OA_CONTROLLER 1.36
PSZ-AC:4_OA_CONTROLLER 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN 1.95 2087.69
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN 8.03 13528.31
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN 1.36 1508.29
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN 1.14 1259.46
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 1.95 1.95 1.95 1.29 35846.46 46053.00 40.00 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 8.03 8.03 8.03 5.30 161560.04 206530.17 40.00 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 1.36 1.36 1.36 0.899125 25010.22 32569.52 40.00 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 1.14 1.14 1.14 0.750790 21402.88 27854.97 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC:1 COOLING COIL 1.95 0.975512 1.30 35846.46 17923.23 0.800240 0.800240
PSZ-AC:2 COOLING COIL 8.03 4.02 5.35 161560.04 80780.02 0.773490 0.773490
PSZ-AC:3 COOLING COIL 1.36 0.681155 0.908207 25010.22 12505.11 0.800510 0.800510
PSZ-AC:4 COOLING COIL 1.14 0.568780 0.758373 21402.88 10701.44 0.800470 0.800470
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
BACK_SPACE_WALL_EAST BACK_SPACE_WALL_EAST_ROLLDOOR |
BACK_SPACE_WALL_NORTH BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 |
BACK_SPACE_WALL_WEST BACK_SPACE_WALL_WEST_ROLLDOOR |
CORE_RETAIL_WALL_WEST_2 CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 |
CORE_RETAIL_WALL_EAST_2 CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 |
CORE_RETAIL_ROOF SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 |
POINT_OF_SALE_WALL_SOUTH POINT_OF_SALE_WALL_SOUTH_GLAZING |
FRONT_RETAIL_WALL_SOUTH FRONT_RETAIL_WALL_SOUTH_GLAZING |
FRONT_ENTRY_WALL_SOUTH FRONT_ENTRY_WALL_SOUTH_GLAZING |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RetailStandalone 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 5 73 32


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BACK_SPACE 0.0 0.00 35.27 0.00 27.14 38.77 3.05 1 1 1 0.00 54.27 35.27 42.27 0.00 6.10 6.10 2317.33 TARP TARP 379.89 416.17 375.11 0.00 6 7 0 Yes
2 CORE_RETAIL 0.0 0.00 6.00 0.00 27.14 14.41 3.05 1 1 1 0.00 54.27 3.00 35.27 0.00 6.10 6.10 9762.95 TARP TARP 1600.48 356.86 345.15 23.78 10 22 0 Yes
3 POINT_OF_SALE 0.0 0.00 0.00 0.00 12.57 3.00 3.05 1 1 1 0.00 25.14 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
4 FRONT_RETAIL 0.0 29.14 0.00 0.00 41.70 3.00 3.05 1 1 1 29.14 54.27 0.00 6.00 0.00 6.10 6.10 919.94 TARP TARP 150.81 189.80 151.74 38.06 7 1 0 Yes
5 FRONT_ENTRY 0.0 25.14 0.00 0.00 27.14 1.50 3.05 1 1 1 25.14 29.14 0.00 3.00 0.00 6.10 6.10 73.20 TARP TARP 12.00 24.38 16.55 7.83 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BACK_SPACE 379.89 8.2 46.452 2.153E-002 4.207 8.070 0.000 0.000 0.000 0.000 12.277 No
2 CORE_RETAIL 1600.48 258.4 6.193 0.161 10.172 3.230 0.000 0.000 0.000 0.000 13.402 No
3 POINT_OF_SALE 150.81 24.4 6.193 0.161 10.172 21.520 0.000 0.000 0.000 0.000 31.692 No
4 FRONT_RETAIL 150.81 24.4 6.193 0.161 10.172 3.230 0.000 0.000 0.000 0.000 13.402 No
5 FRONT_ENTRY 12.00 1.9 6.192 0.162 6.781 0.000 0.000 0.000 0.000 0.000 6.781 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BACK_SPACE BLDG_OCC_SCH BACK_SPACE 379.89 8.2 8.2 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_RETAIL BLDG_OCC_SCH CORE_RETAIL 1600.48 258.4 258.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 258 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 POINT_OF_SALE BLDG_OCC_SCH POINT_OF_SALE 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 FRONT_RETAIL BLDG_OCC_SCH FRONT_RETAIL 150.81 24.4 24.4 0.161 6.193 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 24 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 FRONT_ENTRY BLDG_OCC_SCH FRONT_ENTRY 12.00 1.9 1.9 0.162 6.192 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BACK_SPACE_LIGHTS LTG_SCH_BACK BACK_SPACE 379.89 8.2 1598.021 4.207 195.402 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1598.021
2 CORE_RETAIL_LIGHTS LTG_SCH_CORE CORE_RETAIL 1600.48 258.4 16279.922 10.172 62.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16279.922
3 POINT_OF_SALE_LIGHTS LTG_SCH_SALE POINT_OF_SALE 150.81 24.4 1534.021 10.172 62.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1534.021
4 FRONT_RETAIL_LIGHTS LTG_SCH_FRONT FRONT_RETAIL 150.81 24.4 1534.021 10.172 62.994 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1534.021
5 FRONT_ENTRY_LIGHTS LTG_SCH_ENTRY FRONT_ENTRY 12.00 1.9 81.375 6.781 41.989 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 81.375


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BACK_SPACE_MISCPLUG_EQUIP BLDG_EQUIP_SCH BACK_SPACE 379.89 8.2 3065.712 8.070 374.868 0.000 0.500 0.000 0.500 MiscPlug 0.000 3065.712
2 CORE_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_RETAIL 1600.48 258.4 5169.560 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 5169.560
3 POINT_OF_SALE_MISCPLUG_EQUIP BLDG_EQUIP_SCH POINT_OF_SALE 150.81 24.4 3245.431 21.520 133.273 0.000 0.500 0.000 0.500 MiscPlug 0.000 3245.431
4 FRONT_RETAIL_MISCPLUG_EQUIP BLDG_EQUIP_SCH FRONT_RETAIL 150.81 24.4 487.116 3.230 20.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 487.116


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.253 0.900 0.900 0.700 0.700 MediumRough
7 BACK_SPACE_FLOOR_FFACTOR 38 2 7 0.167 0.2354 0.000 0.900 0.000 0.700 MediumRough
8 CORE_RETAIL_FLOOR_FFACTOR 39 2 7 0.167 0.4655E-01 0.000 0.900 0.000 0.700 MediumRough
9 POINT_OF_SALE_FLOOR_FFACTOR 40 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
10 FRONT_RETAIL_FLOOR_FFACTOR 41 2 7 0.167 0.2719 0.000 0.900 0.000 0.700 MediumRough
11 FRONT_ENTRY_FLOOR_FFACTOR 42 2 7 0.167 0.4506 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
10 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6308
11 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
12 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.172
13 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
14 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 21.40
15 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
16 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.601
17 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
18 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.601
19 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
20 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.142
21 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 9 0.15678677E-14 0.41668067E-16 -0.13443164E-09 -0.41464653E-17
25 8 0.19720454E-07 0.16552409E-12 0.35477227E-03 -0.22422834E-09
26 7 -0.11553319E-01 0.88069696E-08 -0.22094443E-01 0.13136543E-03
27 6 0.38664784 0.30990522E-05 0.45613010 -0.45273053E-02
28 5 -5.0080263 0.11685699E-03 -4.3185286 0.60920489E-01
29 4 32.195305 0.96442504E-03 20.960285 -0.41140105
30 3 -109.50767 0.21185031E-02 -54.674808 1.4903667
31 2 195.42750 0.12000320E-02 77.004857 -2.8736635
32 1 -170.53507 0.12893930E-03 -55.002816 2.7345555
33 0 57.057407 0.73918525E-06 15.601154  
34 7 -0.17867606E-08 -0.41848128E-15 0.59564440E-14 -0.80268503E-16
35 6 0.65885627E-05 0.45121803E-08 0.31870471E-02 -0.26735622E-04
36 5 -0.47407468E-03 0.26731137E-05 -0.22356413 0.19547341E-02
37 4 0.10906669E-01 0.12168607E-03 4.8268734 -0.45239294E-01
38 3 -0.95781928E-01 0.96775432E-03 -38.006321 0.39848689
39 2 0.34010998 0.16100142E-02 116.45457 -1.4175463
40 1 -0.49090295 0.49061009E-03 -143.89001 2.0487556
41 0 0.23934032 0.11861159E-04 60.838472  
42 7 -0.92098544E-08 0.58605081E-15 -0.29904982E-14 0.25019681E-16
43 6 0.19387148E-05 0.91388609E-09 0.32017682E-02 -0.26859115E-04
44 5 -0.10799279E-03 0.53275402E-06 -0.22440051 0.19621166E-02
45 4 0.22736042E-02 0.24052495E-04 4.8407977 -0.45373149E-01
46 3 -0.19287081E-01 0.18995237E-03 -38.084949 0.39935605
47 2 0.67516478E-01 0.31394945E-03 116.60756 -1.4195928
48 1 -0.96817688E-01 0.94848058E-04 -143.98006 2.0502357
49 0 0.47046370E-01 0.22824214E-05 60.838472  
50 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
51 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
52 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
53 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
54 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
55 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
56 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
57 0 0.27714917 0.13715070E-04 60.838472  
58 7 -0.15410587E-08 -0.27131508E-15 0.13739895E-13 -0.20869099E-15
59 6 0.75948721E-05 0.52202150E-08 0.31841660E-02 -0.26711453E-04
60 5 -0.54825752E-03 0.30939483E-05 -0.22340036 0.19532886E-02
61 4 0.12624073E-01 0.14086823E-03 4.8241453 -0.45213070E-01
62 3 -0.11089483 0.11205317E-02 -37.990908 0.39831653
63 2 0.39381345 0.18644394E-02 116.42457 -1.4171450
64 1 -0.56844024 0.56830838E-03 -143.87235 2.0484654
65 0 0.27714917 0.13715070E-04 60.838472  
66 7 -0.91256693E-09 -0.65654920E-16 0.14763662E-14 0.25811017E-17
67 6 0.12659591E-04 0.87293215E-08 0.31698558E-02 -0.26591407E-04
68 5 -0.91895148E-03 0.51830142E-05 -0.22258679 0.19461077E-02
69 4 0.21183618E-01 0.23613386E-03 4.8105909 -0.45082779E-01
70 3 -0.18612912 0.18798277E-02 -37.914317 0.39746999
71 2 0.66101200 0.31293459E-02 116.27548 -1.4151508
72 1 -0.95411819 0.95507326E-03 -143.78458 2.0470226
73 0 0.46518638 0.22828278E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4532_SHGC_0.25 36 1 VerySmooth 2.576 2.576 1.000 0.251    
2 NONRESSKYLIGHT_U_0.9_SHGC_0.6 37 1 VerySmooth 5.108 5.108 1.000 0.601    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   2.62661E-002 0.16139 0.61689 0.61689 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12093 1.00000 No
2 NONRES SKYLIGHT GLAZING LAYER SpectralAverage   2.00000E-003 0.46039 0.10300 0.10300 0.60000 0.13030 0.15164 0.00000 0.84000 0.84000 6.93520E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CORE_RETAIL 16 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CORE_RETAIL 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.731 0.1928


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BACK_SPACE_WALL_EAST 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
2 BACK_SPACE_WALL_EAST_ROLLDOOR 0 257.68 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
3 BACK_SPACE_WALL_NORTH 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
4 BACK_SPACE_WALL_NORTH_DOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
5 BACK_SPACE_WALL_NORTH_DOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 0 330.83 149.77 6.10 0 6.10 68.27 12.40 0.00 0 No No
9 BACK_SPACE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
10 BACK_SPACE_WALL_WEST_ROLLDOOR 0 257.68 96.73 6.10 0 6.10 68.27 12.40 0.00 0 No No
11 BACK_SPACE_WALL_SOUTH 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
12 BACK_SPACE_FLOOR 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
13 BACK_SPACE_ROOF 0 2293.99 205.08 0.00 0 6.10 68.27 12.40 0.00 0 No No
14 BACK_SPACE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 68.27 12.40 0.00 0 No No
15 CORE_RETAIL_WALL_SOUTH_3 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
16 CORE_RETAIL_WALL_SOUTH_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
17 CORE_RETAIL_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
18 CORE_RETAIL_WALL_SOUTH_2 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
19 CORE_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
20 CORE_RETAIL_WALL_WEST_2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
21 CORE_RETAIL_WALL_WEST_2_DOOR3 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
22 CORE_RETAIL_WALL_WEST_2_DOOR2 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
23 CORE_RETAIL_WALL_WEST_2_DOOR1 0 257.68 96.73 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
24 CORE_RETAIL_WALL_EAST_2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 4 No No
25 CORE_RETAIL_WALL_EAST_2_DOOR1 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
26 CORE_RETAIL_WALL_EAST_2_DOOR2 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
27 CORE_RETAIL_WALL_EAST_2_DOOR3 0 257.68 149.77 6.10 0 6.10 58.54 36.99 6.66E-002 0 No No
28 CORE_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
29 CORE_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
30 CORE_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
31 SKYLIGHTS_R4C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
32 SKYLIGHTS_R4C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
33 SKYLIGHTS_R4C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
34 SKYLIGHTS_R4C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
35 SKYLIGHTS_R1C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
36 SKYLIGHTS_R1C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
37 SKYLIGHTS_R1C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
38 SKYLIGHTS_R1C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
39 SKYLIGHTS_R2C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
40 SKYLIGHTS_R2C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
41 SKYLIGHTS_R2C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
42 SKYLIGHTS_R2C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
43 SKYLIGHTS_R3C2 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
44 SKYLIGHTS_R3C1 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
45 SKYLIGHTS_R3C3 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
46 SKYLIGHTS_R3C4 0 2293.99 205.08 0.00 0 6.10 58.54 36.99 6.66E-002 2 No No
47 CORE_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 58.54 36.99 6.66E-002 0 No No
48 POINT_OF_SALE_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
49 POINT_OF_SALE_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
50 POINT_OF_SALE_WALL_EAST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
51 POINT_OF_SALE_WALL_WEST 0 257.68 96.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
52 POINT_OF_SALE_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
53 POINT_OF_SALE_WALL_EAST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
54 POINT_OF_SALE_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
55 POINT_OF_SALE_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
56 POINT_OF_SALE_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
57 FRONT_RETAIL_WALLL_EAST 0 257.68 149.77 6.10 0 6.10 31.14 9.69 0.20 4 No No
58 FRONT_RETAIL_WALL_WEST_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
59 FRONT_RETAIL_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
60 FRONT_RETAIL_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 4 No No
61 FRONT_RETAIL_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 31.14 9.69 0.20 1 No No
62 FRONT_RETAIL_WALL_WEST_2 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
63 FRONT_RETAIL_FLOOR 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
64 FRONT_RETAIL_ROOF 0 2293.99 205.08 0.00 0 6.10 31.14 9.69 0.20 0 No No
65 FRONT_RETAIL_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 31.14 9.69 0.20 0 No No
66 FRONT_ENTRY_WALL_EAST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
67 FRONT_ENTRY_WALL_NORTH 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
68 FRONT_ENTRY_WALL_SOUTH 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 4 No No
69 FRONT_ENTRY_WALL_SOUTH_GLAZING 0 330.83 120.73 6.10 0 6.10 4.00 3.43 0.32 1 No No
70 FRONT_ENTRY_WALL_WEST 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
71 FRONT_ENTRY_FLOOR 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No
72 FRONT_ENTRY_ROOF 0 2293.99 205.08 0.00 0 6.10 4.00 3.43 0.32 0 No No
73 FRONT_ENTRY_INTERNALMASS_1 0 0.00 0.00 0.00 0 6.10 4.00 3.43 0.32 0 No No


FenestrationAssembly

Construction Name Frame and Divider Name NFRC Product Type Assembly U-Factor {W/m2-K} Assembly SHGC Assembly Visible Transmittance
1 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES CurtainWall 4.867 0.602 0.602


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 BACK_SPACE_INFILTRATION INFIL_SCH_PNNL BACK_SPACE 379.89 8.2 0.427 1.123E-003 5.097E-004 0.663 0.000 0.000 0.224 0.000
2 CORE_RETAIL_INFILTRATION INFIL_SCH_PNNL CORE_RETAIL 1600.48 258.4 0.366 2.286E-004 1.858E-004 0.135 0.000 0.000 0.224 0.000
3 POINT_OF_SALE_INFILTRATION INFIL_SCH_PNNL POINT_OF_SALE 150.81 24.4 0.195 1.290E-003 5.713E-004 0.761 0.000 0.000 0.224 0.000
4 FRONT_RETAIL_INFILTRATION INFIL_SCH_PNNL FRONT_RETAIL 150.81 24.4 0.195 1.290E-003 5.713E-004 0.761 0.000 0.000 0.224 0.000
5 FRONT_ENTRY_INFILTRATION INFIL_SCH_PNNL FRONT_ENTRY 12.00 1.9 2.500E-002 2.083E-003 6.871E-004 1.229 0.000 0.000 0.224 0.000
6 FRONT_ENTRY_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH FRONT_ENTRY 12.00 1.9 1.419 0.118 3.899E-002 69.771 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BACK_SPACE Mixing/Well-Stirred
2 CORE_RETAIL Mixing/Well-Stirred
3 POINT_OF_SALE Mixing/Well-Stirred
4 FRONT_RETAIL Mixing/Well-Stirred
5 FRONT_ENTRY Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone BACK_SPACE 1.2000
3 Zone CORE_RETAIL 1.2000
4 Zone POINT_OF_SALE 1.2000
5 Zone FRONT_RETAIL 1.2000
6 Zone FRONT_ENTRY 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.7445E-004
2 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 2.9910E-004
3 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.5741E-004
4 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 2.5157E-004
5 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.5706E-004
6 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 2.4966E-004
7 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT1 1.8996E-004
8 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C1 CORE_RETAIL_DAYLREFPT2 3.9043E-004
9 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 2.6975E-004
10 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 2.1760E-004
11 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 2.2911E-004
12 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.9109E-004
13 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 2.2500E-004
14 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 1.9696E-004
15 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT1 3.3656E-004
16 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C2 CORE_RETAIL_DAYLREFPT2 2.5584E-004
17 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 2.8402E-004
18 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 1.4408E-004
19 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 2.4062E-004
20 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 1.3505E-004
21 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 2.4188E-004
22 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 1.4000E-004
23 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT1 3.6506E-004
24 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C3 CORE_RETAIL_DAYLREFPT2 1.5288E-004
25 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.8833E-004
26 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 1.1592E-004
27 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.6894E-004
28 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 1.1315E-004
29 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 1.7495E-004
30 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 1.1735E-004
31 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT1 2.1191E-004
32 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R4C4 CORE_RETAIL_DAYLREFPT2 1.2226E-004
33 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 2.7459E-004
34 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 2.4114E-003
35 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 2.7225E-004
36 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 2.9114E-003
37 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 2.9140E-004
38 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 1.3861E-003
39 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT1 2.0604E-004
40 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C1 CORE_RETAIL_DAYLREFPT2 4.8996E-004
41 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 9.8001E-004
42 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 6.4832E-004
43 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 1.0886E-003
44 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 7.0723E-004
45 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 8.5629E-004
46 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 5.7045E-004
47 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT1 4.0930E-004
48 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C2 CORE_RETAIL_DAYLREFPT2 2.9411E-004
49 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 4.2126E-004
50 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 1.2904E-004
51 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 4.4282E-004
52 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 1.2774E-004
53 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 3.9861E-004
54 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 1.3210E-004
55 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT1 2.3470E-004
56 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C4 CORE_RETAIL_DAYLREFPT2 1.2341E-004
57 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 1.8865E-003
58 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 2.0952E-004
59 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 2.2437E-003
60 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 2.0960E-004
61 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 1.1933E-003
62 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 2.1058E-004
63 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT1 4.5161E-004
64 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R1C3 CORE_RETAIL_DAYLREFPT2 1.5950E-004
65 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.4085E-003
66 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 1.0783E-003
67 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 2.3961E-003
68 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 1.0512E-003
69 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 3.3292E-003
70 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 1.4668E-003
71 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT1 3.0002E-003
72 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C2 CORE_RETAIL_DAYLREFPT2 1.1197E-003
73 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 3.8551E-004
74 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 5.9835E-003
75 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 3.5371E-004
76 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 6.5088E-003
77 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 4.9544E-004
78 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 6.8706E-003
79 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT1 4.3409E-004
80 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C1 CORE_RETAIL_DAYLREFPT2 5.5970E-003
81 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 4.3389E-003
82 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 2.4308E-004
83 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 4.6273E-003
84 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 2.2954E-004
85 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 5.2499E-003
86 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 2.8033E-004
87 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT1 4.1741E-003
88 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C3 CORE_RETAIL_DAYLREFPT2 2.3050E-004
89 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 6.0567E-004
90 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 1.3311E-004
91 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 5.7650E-004
92 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 1.2951E-004
93 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 7.9683E-004
94 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 1.3935E-004
95 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT1 6.0842E-004
96 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R2C4 CORE_RETAIL_DAYLREFPT2 1.3229E-004
97 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 1.0064E-003
98 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 5.6261E-004
99 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 8.3647E-004
100 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 4.8202E-004
101 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 1.2214E-003
102 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 7.1504E-004
103 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT1 2.4124E-003
104 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C2 CORE_RETAIL_DAYLREFPT2 9.7824E-004
105 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 2.9909E-004
106 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.4760E-003
107 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 2.6128E-004
108 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.2265E-003
109 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 3.2835E-004
110 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 1.7888E-003
111 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT1 4.0382E-004
112 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C1 CORE_RETAIL_DAYLREFPT2 4.1990E-003
113 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 1.2488E-003
114 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.9923E-004
115 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 1.0437E-003
116 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 1.8251E-004
117 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 1.5713E-003
118 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 2.1713E-004
119 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT1 3.2416E-003
120 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C3 CORE_RETAIL_DAYLREFPT2 2.2265E-004
121 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 3.8242E-004
122 Clear Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 1.2654E-004
123 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 3.3364E-004
124 Clear Turbid Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 1.2246E-004
125 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 4.6422E-004
126 Intermediate Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 1.3066E-004
127 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT1 5.5411E-004
128 Overcast Sky 12/21 CORE_RETAIL_DAYLCTRL CORE_RETAIL SKYLIGHTS_R3C4 CORE_RETAIL_DAYLREFPT2 1.3150E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BACK_SPACE Cooling 20873.84876 25048.61851 1.62369 1.94842 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 379.89000 8.17812 0.23158 0.00000
2 BACK_SPACE Heating 20130.69968 24156.83961 0.93183 1.11819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 379.89000 8.17812 0.23158 0.00000
3 CORE_RETAIL Cooling 83558.69480 100270.43376 6.49382 7.79258 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 1600.48290 258.43418 1.89041 0.00000
4 CORE_RETAIL Heating 45972.87259 55167.44711 2.08694 2.50432 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 1600.48290 258.43418 1.89041 0.00000
5 POINT_OF_SALE Cooling 14046.01327 16855.21592 1.13526 1.36231 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 150.81000 24.35169 0.17813 0.00000
6 POINT_OF_SALE Heating 9722.44856 11666.93828 0.45184 0.54220 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 150.81000 24.35169 0.17813 0.00000
7 FRONT_RETAIL Cooling 11728.73643 14074.48372 0.94797 1.13756 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 40.80000 5.63111E-003 150.81000 24.35169 0.17813 0.00000
8 FRONT_RETAIL Heating 9720.03786 11664.04543 0.45172 0.54207 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 150.81000 24.35169 0.17813 0.00000
9 FRONT_ENTRY Cooling 0.00000 0.00000 0.00000 1.41732E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.63090E-003 12.00000 1.93800 1.41732E-002 0.00000
10 FRONT_ENTRY Heating 26141.48638 31369.78365 0.97514 1.17016 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 0.50000 4.31558E-003 12.00000 1.93800 1.41732E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 27192.11 1.95102 1.95102 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 28641.94 1.11819 1.11819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 PSZ-AC:2 Cooling Sensible 132253.81 8.03003 8.03003 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 94976.90 2.50432 2.50432 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
5 PSZ-AC:3 Cooling Sensible 19903.67 1.36231 1.36231 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 15366.33 0.54220 0.54220 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
7 PSZ-AC:4 Cooling Sensible 17165.94 1.13756 1.13756 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 15363.46 0.54207 0.54207 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BACK_SPACE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.94842
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 7.79258
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat POINT_OF_SALE DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.36231
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONT_RETAIL DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.13756
5 ZoneHVAC:UnitHeater FRONT_ENTRY UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 1.17016
6 Fan:ConstantVolume FRONT_ENTRY UNIT HEATER FAN Design Size Maximum Flow Rate [m3/s] 1.17016
7 Coil:Heating:Fuel FRONT_ENTRY UNIT HEATER HEATING COIL Design Size Nominal Capacity [W] 31372.89565
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.94842
9 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.94842
10 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.94842
11 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 1.94842
12 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 1.95102
13 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 1.95102
14 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 0.99867
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 7.79258
17 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 7.79258
18 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 7.79258
19 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 7.79258
20 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 8.03003
21 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 8.03003
22 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
23 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 0.97043
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.36231
25 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.36231
26 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.36231
27 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 1.36231
28 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 1.36231
29 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 1.36231
30 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
31 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.13756
33 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.13756
34 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.13756
35 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 1.13756
36 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 1.13756
37 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 1.13756
38 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
39 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
40 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 1.95102
41 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 8.03003
42 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 1.36231
43 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 1.13756
44 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.95102
45 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.95102
46 Fan:SystemModel PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 2087.68788
47 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.95102
48 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.95102
49 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.95102
50 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.28768
51 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.95102
52 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.97551
53 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.30068
54 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 35846.46000
55 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 17923.23000
56 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80024
57 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80024
58 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 35846.46000
59 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 46052.99781
60 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
61 AirLoopHVAC:UnitarySystem PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
62 Coil:Heating:Fuel PSZ-AC:1 HEATING COIL Design Size Nominal Capacity [W] 46052.99781
63 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.03003
64 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 8.03003
65 Fan:SystemModel PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 13528.30743
66 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 8.03003
67 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 8.03003
68 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 8.03003
69 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 5.29982
70 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 8.03003
71 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.01501
72 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.35335
73 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 161560.04000
74 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 80780.02000
75 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.77349
76 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.77349
77 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 161560.04000
78 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 206530.16961
79 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
80 AirLoopHVAC:UnitarySystem PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
81 Coil:Heating:Fuel PSZ-AC:2 HEATING COIL Design Size Nominal Capacity [W] 206530.16961
82 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.36231
83 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.36231
84 Fan:SystemModel PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1508.29388
85 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.36231
86 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.36231
87 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.36231
88 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.89912
89 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.36231
90 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.68116
91 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.90821
92 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 25010.22000
93 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 12505.11000
94 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80051
95 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80051
96 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 25010.22000
97 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 32569.52499
98 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
99 AirLoopHVAC:UnitarySystem PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
100 Coil:Heating:Fuel PSZ-AC:3 HEATING COIL Design Size Nominal Capacity [W] 32569.52499
101 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.13756
102 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.13756
103 Fan:SystemModel PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Design Electric Power Consumption [W] 1259.45948
104 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.13756
105 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.13756
106 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.13756
107 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.75079
108 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.13756
109 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.56878
110 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.75837
111 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 21402.88000
112 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 10701.44000
113 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80047
114 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80047
115 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 21402.88000
116 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 27854.97325
117 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
118 AirLoopHVAC:UnitarySystem PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Coil:Heating:Fuel PSZ-AC:4 HEATING COIL Design Size Nominal Capacity [W] 27854.97325


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC:1 COOLING COIL 34315.2     11.35 11.35  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC:2 COOLING COIL 155248.8     10.52 10.52  
3 Coil:Cooling:DX:MultiSpeed PSZ-AC:3 COOLING COIL 23941.0     11.34 11.34  
4 Coil:Cooling:DX:MultiSpeed PSZ-AC:4 COOLING COIL 20509.7     11.40 11.40  


Zone Surfaces

Zone Name # Surfaces
1 BACK_SPACE 14
2 CORE_RETAIL 33
3 POINT_OF_SALE 9
4 FRONT_RETAIL 9
5 FRONT_ENTRY 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BACK_SPACE_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   35.24 42.67 35.24 90.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 BACK_SPACE_WALL_EAST_ROLLDOOR Door BACK_SPACE_WALL_EAST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 90.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 BACK_SPACE_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   304.63 330.83 304.63 0.00 90.00 54.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 BACK_SPACE_WALL_NORTH_DOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 BACK_SPACE_WALL_NORTH_DOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 BACK_SPACE_WALL_NORTH_ROLLDOOR1 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 BACK_SPACE_WALL_NORTH_ROLLDOOR2 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 BACK_SPACE_WALL_NORTH_ROLLDOOR3 Door BACK_SPACE_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 BACK_SPACE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   35.24 42.67 35.24 270.00 90.00 7.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 BACK_SPACE_WALL_WEST_ROLLDOOR Door BACK_SPACE_WALL_WEST CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 270.00 90.00 3.05 2.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 BACK_SPACE_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 180.00 90.00 54.27 6.10 0.00 CORE_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 BACK_SPACE_FLOOR Floor   CTF - ConductionTransferFunction BACK_SPACE_FLOOR_FFACTOR 0.235 0.223   379.89 379.89 379.89 90.00 180.00 7.00 54.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 BACK_SPACE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   379.89 379.89 379.89 90.00 0.00 7.00 54.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
14 BACK_SPACE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   759.78 759.78 759.78 0.00 90.00 759.78 1.00 0.00 BACK_SPACE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 CORE_RETAIL_WALL_SOUTH_3 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 FRONT_RETAIL_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 CORE_RETAIL_WALL_SOUTH_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 180.00 90.00 25.14 6.10 0.00 POINT_OF_SALE_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
17 CORE_RETAIL_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
18 CORE_RETAIL_WALL_SOUTH_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 180.00 90.00 4.00 6.10 0.00 FRONT_ENTRY_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 CORE_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   330.83 330.83 330.83 0.00 90.00 54.27 6.10 0.00 BACK_SPACE_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 CORE_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   172.58 178.43 172.58 270.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 CORE_RETAIL_WALL_WEST_2_DOOR3 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 CORE_RETAIL_WALL_WEST_2_DOOR2 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
23 CORE_RETAIL_WALL_WEST_2_DOOR1 Door CORE_RETAIL_WALL_WEST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 CORE_RETAIL_WALL_EAST_2 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   172.58 178.43 172.58 90.00 90.00 29.27 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 CORE_RETAIL_WALL_EAST_2_DOOR1 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
26 CORE_RETAIL_WALL_EAST_2_DOOR2 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
27 CORE_RETAIL_WALL_EAST_2_DOOR3 Door CORE_RETAIL_WALL_EAST_2 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
28 CORE_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction CORE_RETAIL_FLOOR_FFACTOR 4.655E-002 4.603E-002   1600.48 1600.48 1600.48 0.00 180.00 40.01 40.01 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
30 CORE_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   1576.70 1600.48 1576.70 180.00 0.00 40.01 40.01 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
31 SKYLIGHTS_R4C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
32 SKYLIGHTS_R4C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
33 SKYLIGHTS_R4C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
34 SKYLIGHTS_R4C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
35 SKYLIGHTS_R1C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
36 SKYLIGHTS_R1C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
37 SKYLIGHTS_R1C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
38 SKYLIGHTS_R1C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
39 SKYLIGHTS_R2C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
40 SKYLIGHTS_R2C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
41 SKYLIGHTS_R2C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
42 SKYLIGHTS_R2C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
43 SKYLIGHTS_R3C2 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
44 SKYLIGHTS_R3C1 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 1.11E-016 1.00 4
45 SKYLIGHTS_R3C3 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
46 SKYLIGHTS_R3C4 Window CORE_RETAIL_ROOF Window5 Detailed Fenestration NONRESSKYLIGHT_U_0.9_SHGC_0.6 N/A 5.108 No 1.49 1.49 1.49 180.00 0.00 1.22 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 4.44E-016 1.00 4
47 CORE_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3200.97 3200.97 3200.97 0.00 90.00 3200.97 1.00 0.00 CORE_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
48 POINT_OF_SALE_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 POINT_OF_SALE_WALL_SOUTH_GLAZING Window POINT_OF_SALE_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4532_SHGC_0.25 N/A 2.576 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
50 POINT_OF_SALE_WALL_EAST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 POINT_OF_SALE_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   36.58 36.58 36.58 270.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 POINT_OF_SALE_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
53 POINT_OF_SALE_WALL_EAST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 POINT_OF_SALE_FLOOR Floor   CTF - ConductionTransferFunction POINT_OF_SALE_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 180.00 180.00 25.14 6.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
55 POINT_OF_SALE_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   150.81 150.81 150.81 180.00 0.00 25.14 6.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
56 POINT_OF_SALE_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 POINT_OF_SALE_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
57 FRONT_RETAIL_WALLL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   36.58 36.58 36.58 90.00 90.00 6.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 FRONT_RETAIL_WALL_WEST_1 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 FRONT_ENTRY_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 FRONT_RETAIL_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   153.22 153.22 153.22 0.00 90.00 25.14 6.10 0.00 CORE_RETAIL_WALL_SOUTH_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 FRONT_RETAIL_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   115.16 153.22 115.16 180.00 90.00 25.14 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 FRONT_RETAIL_WALL_SOUTH_GLAZING Window FRONT_RETAIL_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4532_SHGC_0.25 N/A 2.576 No 38.06 38.06 38.06 180.00 90.00 25.04 1.52 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 FRONT_RETAIL_WALL_WEST_2 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 CORE_RETAIL_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 FRONT_RETAIL_FLOOR Floor   CTF - ConductionTransferFunction FRONT_RETAIL_FLOOR_FFACTOR 0.272 0.255   150.81 150.81 150.81 90.00 180.00 6.00 25.14 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
64 FRONT_RETAIL_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   150.81 150.81 150.81 90.00 0.00 6.00 25.14 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
65 FRONT_RETAIL_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   301.62 301.62 301.62 0.00 90.00 301.62 1.00 0.00 FRONT_RETAIL_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
66 FRONT_ENTRY_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 90.00 90.00 3.00 6.10 0.00 FRONT_RETAIL_WALL_WEST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
67 FRONT_ENTRY_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   24.38 24.38 24.38 0.00 90.00 4.00 6.10 0.00 CORE_RETAIL_WALL_SOUTH_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
68 FRONT_ENTRY_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.253 1.055   16.55 24.38 16.55 180.00 90.00 4.00 6.10 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 FRONT_ENTRY_WALL_SOUTH_GLAZING Window FRONT_ENTRY_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4532_SHGC_0.25 N/A 2.576 No 7.83 7.83 7.83 180.00 90.00 3.00 2.61 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 FRONT_ENTRY_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.29 18.29 18.29 270.00 90.00 3.00 6.10 0.00 POINT_OF_SALE_WALL_EAST_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 FRONT_ENTRY_FLOOR Floor   CTF - ConductionTransferFunction FRONT_ENTRY_FLOOR_FFACTOR 0.451 0.406   12.00 12.00 12.00 180.00 180.00 4.00 3.00 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
72 FRONT_ENTRY_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   12.00 12.00 12.00 180.00 0.00 4.00 3.00 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
73 FRONT_ENTRY_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   24.00 24.00 24.00 0.00 90.00 24.00 1.00 0.00 FRONT_ENTRY_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BACK_SPACE RunPeriod: RUNPERIOD 1 7.1848621444E-002 0.2254342261 Pass Pass 0.1790242516 0.9693419537 Pass Pass
2 CORE_RETAIL RunPeriod: RUNPERIOD 1 4.9473511889E-002 0.1529719563 Pass Pass 0.4348977838 3.9615723829 Pass Pass
3 POINT_OF_SALE RunPeriod: RUNPERIOD 1 6.1346743054E-002 9.2301743581E-002 Pass Pass 5.4000552238E-002 0.1546412204 Pass Pass
4 FRONT_RETAIL RunPeriod: RUNPERIOD 1 7.9720089200E-002 0.1670679497 Pass Pass 0.1567444939 0.7731661071 Pass Pass
5 FRONT_ENTRY RunPeriod: RUNPERIOD 1 0.1565257014 0.3632343521 Pass Pass 1.4360483019E-002 9.2496651326E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3055.67 23.83 0.00 97.49 1204.73 4381.73



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.055 1.253 42.67 35.24 90.00 90.00 E
BACK_SPACE_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.055 1.253 330.83 304.63 0.00 90.00 N
BACK_SPACE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.055 1.253 42.67 35.24 270.00 90.00 W
BACK_SPACE_FLOOR BACK_SPACE_FLOOR_FFACTOR 1.00 0.227 0.235 379.89 379.89 90.00 180.00  
BACK_SPACE_ROOF NONRES_ROOF 0.55 0.221 0.228 379.89 379.89 90.00 0.00  
CORE_RETAIL_WALL_WEST_2 NONRES_EXT_WALL_GRD 0.30 1.055 1.253 178.43 172.58 270.00 90.00 W
CORE_RETAIL_WALL_EAST_2 NONRES_EXT_WALL_GRD 0.30 1.055 1.253 178.43 172.58 90.00 90.00 E
CORE_RETAIL_FLOOR CORE_RETAIL_FLOOR_FFACTOR 1.00 0.046 0.047 1600.48 1600.48 0.00 180.00  
CORE_RETAIL_ROOF NONRES_ROOF 0.55 0.221 0.228 1600.48 1576.70 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.055 1.253 153.22 115.16 180.00 90.00 S
POINT_OF_SALE_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.055 1.253 36.58 36.58 270.00 90.00 W
POINT_OF_SALE_FLOOR POINT_OF_SALE_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 180.00 180.00  
POINT_OF_SALE_ROOF NONRES_ROOF 0.55 0.221 0.228 150.81 150.81 180.00 0.00  
FRONT_RETAIL_WALLL_EAST NONRES_EXT_WALL_GRD 0.30 1.055 1.253 36.58 36.58 90.00 90.00 E
FRONT_RETAIL_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.055 1.253 153.22 115.16 180.00 90.00 S
FRONT_RETAIL_FLOOR FRONT_RETAIL_FLOOR_FFACTOR 1.00 0.260 0.272 150.81 150.81 90.00 180.00  
FRONT_RETAIL_ROOF NONRES_ROOF 0.55 0.221 0.228 150.81 150.81 90.00 0.00  
FRONT_ENTRY_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.055 1.253 24.38 16.55 180.00 90.00 S
FRONT_ENTRY_FLOOR FRONT_ENTRY_FLOOR_FFACTOR 1.00 0.420 0.451 12.00 12.00 180.00 180.00  
FRONT_ENTRY_ROOF NONRES_ROOF 0.55 0.221 0.228 12.00 12.00 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BACK_SPACE_WALL_SOUTH INT_WALL 0.30 2.511 6.299 330.83 330.83 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_3 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_SOUTH_1 INT_WALL 0.30 2.511 6.299 153.22 153.22 180.00 90.00 S
CORE_RETAIL_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
CORE_RETAIL_WALL_SOUTH_2 INT_WALL 0.30 2.511 6.299 24.38 24.38 180.00 90.00 S
CORE_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 330.83 330.83 0.00 90.00 N
CORE_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
POINT_OF_SALE_WALL_EAST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
POINT_OF_SALE_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
POINT_OF_SALE_WALL_EAST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_RETAIL_WALL_WEST_1 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_RETAIL_WALL_NORTH INT_WALL 0.30 2.511 6.299 153.22 153.22 0.00 90.00 N
FRONT_RETAIL_WALL_WEST_2 INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
FRONT_ENTRY_WALL_EAST INT_WALL 0.30 2.511 6.299 18.29 18.29 90.00 90.00 E
FRONT_ENTRY_WALL_NORTH INT_WALL 0.30 2.511 6.299 24.38 24.38 0.00 90.00 N
FRONT_ENTRY_WALL_WEST INT_WALL 0.30 2.511 6.299 18.29 18.29 270.00 90.00 W
BACK_SPACE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 759.78   0.00 90.00 N
CORE_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3200.97   0.00 90.00 N
POINT_OF_SALE_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_RETAIL_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 301.62   0.00 90.00 N
FRONT_ENTRY_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 24.00   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
SKYLIGHTS_R4C1 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C2 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C3 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R4C4 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C1 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C2 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C4 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R1C3 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C2 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C1 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C3 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R2C4 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C2 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C1 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C3 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
SKYLIGHTS_R3C4 NONRESSKYLIGHT_U_0.9_SHGC_0.6 SKYLIGHT_FRAME_NONRES 1.49 0.00 0.00 1.49 1.49 5.108 0.601 0.602 0.000 0.000 CurtainWall 4.867 0.602 0.602 No CORE_RETAIL_ROOF 180.00 0.00  
POINT_OF_SALE_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.4532_SHGC_0.25   38.06 0.00 0.00 38.06 38.06 2.576 0.251 0.251             No POINT_OF_SALE_WALL_SOUTH 180.00 90.00 S
FRONT_RETAIL_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.4532_SHGC_0.25   38.06 0.00 0.00 38.06 38.06 2.576 0.251 0.251             No FRONT_RETAIL_WALL_SOUTH 180.00 90.00 S
FRONT_ENTRY_WALL_SOUTH_GLAZING NONRESWINDOW_U_0.4532_SHGC_0.25   7.83 0.00 0.00 7.83 7.83 2.576 0.251 0.251             No FRONT_ENTRY_WALL_SOUTH 180.00 90.00 S
Total or Average             107.73 3.135 0.328 0.328                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             107.73 3.135 0.328 0.328                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
BACK_SPACE_WALL_EAST_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 BACK_SPACE_WALL_EAST
BACK_SPACE_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR1 OVERHEAD DOOR_CON 1.393 1.760 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR2 OVERHEAD DOOR_CON 1.393 1.760 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_NORTH_ROLLDOOR3 OVERHEAD DOOR_CON 1.393 1.760 7.43 BACK_SPACE_WALL_NORTH
BACK_SPACE_WALL_WEST_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 BACK_SPACE_WALL_WEST
CORE_RETAIL_WALL_WEST_2_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_WEST_2_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_WEST_2
CORE_RETAIL_WALL_EAST_2_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_EAST_2
CORE_RETAIL_WALL_EAST_2_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 CORE_RETAIL_WALL_EAST_2


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
SKYLIGHTS_R4C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R4C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R1C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R2C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SKYLIGHTS_R3C4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
POINT_OF_SALE_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_RETAIL_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
FRONT_ENTRY_WALL_SOUTH_GLAZING 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BACK_SPACE_LIGHTS BACK_SPACE BACK_SPACE GENERAL 4.2065 379.89 1598.02 LightsWired LTG_SCH_BACK 32.16 168.00 31.72 0.0000 Y 9.51
CORE_RETAIL_LIGHTS CORE_RETAIL CORE_RETAIL GENERAL 10.1719 1600.48 16279.92 LightsWired LTG_SCH_CORE 69.21 168.00 51.02 0.0000 Y 155.92
POINT_OF_SALE_LIGHTS POINT_OF_SALE POINT_OF_SALE GENERAL 10.1719 150.81 1534.02 LightsWired LTG_SCH_SALE 69.21 168.00 68.25 0.0000 Y 19.65
FRONT_RETAIL_LIGHTS FRONT_RETAIL FRONT_RETAIL GENERAL 10.1719 150.81 1534.02 LightsWired LTG_SCH_FRONT 69.21 168.00 68.25 0.0000 Y 19.65
FRONT_ENTRY_LIGHTS FRONT_ENTRY FRONT_ENTRY GENERAL 6.7813 12.00 81.38 LightsWired LTG_SCH_ENTRY 69.21 168.00 68.25 0.0000 Y 1.04
Interior Lighting Total       9.1663 2293.99 21027.36               205.79


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
CORE_RETAIL_DAYLREFPT1 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 16279.92 4069.98
CORE_RETAIL_DAYLREFPT2 CORE_RETAIL CORE_RETAIL_DAYLCTRL SplitFlux Continuous/Off 0.25 16279.92 4069.98


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 270.38 AstronomicalClock -   41.79 41.79 2.12
EXTERIOR_LIGHTS_B 3472.03 AstronomicalClock -   83.79 62.79 40.92
Exterior Lighting Total 3742.41           43.04



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 COOLING COIL Coil:Cooling:DX:MultiSpeed   35846.46 28685.77 7160.69 0.80 3.80    
PSZ-AC:2 COOLING COIL Coil:Cooling:DX:MultiSpeed   161560.04 124965.08 36594.96 0.77 3.40    
PSZ-AC:3 COOLING COIL Coil:Cooling:DX:MultiSpeed   25010.22 20020.93 4989.29 0.80 3.80    
PSZ-AC:4 COOLING COIL Coil:Cooling:DX:MultiSpeed   21402.88 17132.36 4270.52 0.80 3.80    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 COOLING COIL   34315.2     11.35 11.35  
PSZ-AC:2 COOLING COIL   155248.8     10.52 10.52  
PSZ-AC:3 COOLING COIL   23941.0     11.34 11.34  
PSZ-AC:4 COOLING COIL   20509.7     11.40 11.40  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:2 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:3 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC:4 COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FRONT_ENTRY UNIT HEATER HEATING COIL Coil:Heating:Fuel   31372.90 0.80
PSZ-AC:1 HEATING COIL Coil:Heating:Fuel   46053.00 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:Fuel   206530.17 0.81
PSZ-AC:3 HEATING COIL Coil:Heating:Fuel   32569.52 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:Fuel   27854.97 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 0.54 49.80 1.17 108.72 92.91 1.00 3.99 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.58 622.50 1.95 2087.69 1070.05 1.00 1.32 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.60 1018.41 8.03 13528.31 1684.71 1.00 1.15 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.36 1508.29 1107.16 1.00 1.33 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 0.56 622.50 1.14 1259.46 1107.16 1.00 1.37 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 0.82 0.73 0.19



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 20873.85 25048.62 65.94 1.624 1.948 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.89 23.89 0.00834 30.96 0.00562 0.232 0.00
CORE_RETAIL 83558.69 100270.43 62.65 6.494 7.793 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 23.89 23.89 0.00963 30.96 0.00562 1.890 0.00
POINT_OF_SALE 14046.01 16855.22 111.76 1.135 1.362 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 23.89 23.89 0.00872 40.80 0.00563 0.178 0.00
FRONT_RETAIL 11728.74 14074.48 93.33 0.948 1.138 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 23.89 23.89 0.00877 40.80 0.00563 0.178 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.000 0.014 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 0.00 39.86 0.00569 40.67 0.00563 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BACK_SPACE 20130.70 24156.84 63.59 0.932 1.118 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00746 0.50 0.00432 0.232 0.00
CORE_RETAIL 45972.87 55167.45 34.47 2.087 2.504 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00763 0.50 0.00432 1.890 0.00
POINT_OF_SALE 9722.45 11666.94 77.36 0.452 0.542 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00761 0.50 0.00432 0.178 0.00
FRONT_RETAIL 9720.04 11664.05 77.34 0.452 0.542 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.11 21.11 0.00761 0.50 0.00432 0.178 0.00
FRONT_ENTRY 26141.49 31369.78 2614.15 0.975 1.170 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 16.00 15.95 0.00576 0.50 0.00432 0.014 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 1.95 1.95 1.12 1.12 1.9510 1.9484 1.9510 0.9987 1.0000
PSZ-AC:2 8.03 8.03 2.50 2.50 8.0300 7.7926 8.0300 0.9704 1.0000
PSZ-AC:3 1.36 1.36 0.54 0.54 1.3623 1.3623 1.3623 1.0000 1.0000
PSZ-AC:4 1.14 1.14 0.54 0.54 1.1376 1.1376 1.1376 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:FUEL ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER 31372.896 31372.896 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 31372.90 31372.90 1.170162 15.95 9.78 0.00575934 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 15.95 0.00575934 46.5573 31369.78 0.00 -999.00 -999.00
PSZ-AC:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:1 35846.460 28685.771 1.951020 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 17923.23 17923.23 1.300680 26.93 16.01 0.00803135 12.80 10.77 0.00803135 40.80 0.00563111 18.58 17.8046 23.89 0.00836878 41.1771 19374.96 0.00 -999.00 -999.00
PSZ-AC:1 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 46052.998 46052.998 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 46053.00 46053.00 1.951024 18.49 12.12 0.00708341 40.00 20.06 0.00800000 0.50 0.00431558 0.50 11.8697 21.11 0.00745620 43.5071 20130.70 0.00 -999.00 -999.00
PSZ-AC:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:2 161560.040 124965.075 8.030030 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 80780.02 80780.02 5.353353 29.41 17.05 0.00830784 12.80 11.04 0.00830784 40.80 0.00563111 18.58 35.3126 23.89 0.00913951 44.9209 82216.25 0.00 -999.00 -999.00
PSZ-AC:2 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 206530.170 206530.170 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 206530.17 206530.17 8.030029 16.02 10.91 0.00684778 40.00 20.06 0.00800000 0.50 0.00431558 0.50 23.5417 21.11 0.00762745 44.4912 45972.87 0.00 -999.00 -999.00
PSZ-AC:3 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:3 25010.220 20020.931 1.362310 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 12505.11 12505.11 0.908207 27.09 16.30 0.00832044 12.80 11.06 0.00832044 40.80 0.00563111 18.58 19.6133 23.89 0.00872498 42.9093 14046.01 0.00 -999.00 -999.00
PSZ-AC:3 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 32569.525 32569.525 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 32569.52 32569.52 1.362310 18.24 12.11 0.00717673 40.00 20.06 0.00800000 0.50 0.00431558 0.50 13.0755 21.11 0.00760711 44.3762 9722.45 0.00 -999.00 -999.00
PSZ-AC:4 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC:4 21402.880 17132.363 1.137560 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 10701.44 10701.44 0.758373 27.53 16.41 0.00827586 12.80 11.01 0.00827586 40.80 0.00563111 18.58 23.4883 23.89 0.00876689 43.1126 11728.74 0.00 -999.00 -999.00
PSZ-AC:4 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 27854.973 27854.973 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 27854.97 27854.97 1.137560 17.71 11.82 0.00709148 40.00 20.06 0.00800000 0.50 0.00431558 0.50 15.6589 21.11 0.00760685 44.3748 9720.04 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
FRONT_ENTRY UNIT HEATER HEATING COIL COIL:HEATING:FUEL Zone Equipment ZONEHVAC:UNITHEATER FRONT_ENTRY UNIT HEATER FRONT_ENTRY N/A N/A N/A Yes No unknown No 31372.896 31372.896 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 FRONT_ENTRY UNIT HEATER FAN Fan:ConstantVolume 1.170162 1.27921433   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:10:00 Sensible 31372.90 31372.90 1.0000 1.27921433 1.170162 15.95 9.78 0.00575934 30600.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 31372.90 0.50 0.00431558 0.50 0.00000000 0.0000 15.95 0.00575934 15.95 0.00575934 46.5573 31369.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident CoolingDesignCapacity N/A No No unknown No 35846.460 28685.771 1.951020 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7699 1004.8586 1.0932 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.951024 2.13284813   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 Sensible 17923.23 17923.23 1.0000 1.42189585 1.300680 26.93 16.01 0.00803135 47552.8 12.80 10.77 0.00803135 33139.0 -999.0 -999.00 -999.00 -999.00 0.000 17923.23 40.80 0.00563111 18.58 0.23158056 17.8046 23.89 0.00836878 23.89 0.00836878 41.1771 19374.96 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:1 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 BACK_SPACE Coincident HeatingDesignCapacity N/A Yes No unknown No 46052.998 46052.998 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.951024 2.13284813   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 46053.00 46053.00 1.0000 2.13284813 1.951024 18.49 12.12 0.00708341 36534.8 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 46053.00 0.50 0.00431558 0.50 0.23158056 11.8697 20.91 0.00745620 21.11 0.00745620 43.5071 20130.70 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 161560.040 124965.075 8.030030 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.2839 1004.8586 1.0932 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.030029 8.77838127   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 Sensible 80780.02 80780.02 1.0000 5.85225490 5.353353 29.41 17.05 0.00830784 50781.3 12.80 11.04 0.00830784 33837.0 -999.0 -999.00 -999.00 -999.00 0.000 80780.02 40.80 0.00563111 18.58 1.89040796 35.3126 23.89 0.00913951 23.89 0.00913951 44.9209 82216.25 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 CORE_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 206530.170 206530.170 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 8.030029 8.77838127   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 206530.17 206530.17 1.0000 8.77838127 8.030029 16.02 10.91 0.00684778 33426.1 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 206530.17 0.50 0.00431558 0.50 1.89040796 23.5417 20.80 0.00762745 21.11 0.00762745 44.4912 45972.87 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident CoolingDesignCapacity N/A No No unknown No 25010.220 20020.931 1.362310 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3073 1004.8586 1.0932 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.362310 1.48926987   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 Sensible 12505.11 12505.11 1.0000 0.99284628 0.908207 27.09 16.30 0.00832044 48451.8 12.80 11.06 0.00832044 33868.9 -999.0 -999.00 -999.00 -999.00 0.000 12505.11 40.80 0.00563111 18.58 0.17812900 19.6133 23.89 0.00872498 23.89 0.00872498 42.9093 14046.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 POINT_OF_SALE Coincident HeatingDesignCapacity N/A Yes No unknown No 32569.525 32569.525 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.362310 1.48926987   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 32569.52 32569.52 1.0000 1.48926987 1.362310 18.24 12.11 0.00717673 36516.4 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 32569.52 0.50 0.00431558 0.50 0.17812900 13.0755 20.90 0.00760711 21.11 0.00760711 44.3762 9722.45 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident CoolingDesignCapacity N/A No No unknown No 21402.880 17132.363 1.137560 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.2244 1004.8586 1.0932 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.137560 1.24357400   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 10701.44 10701.44 1.0000 0.82904934 0.758373 27.53 16.41 0.00827586 48783.9 12.80 11.01 0.00827586 33756.3 -999.0 -999.00 -999.00 -999.00 0.000 10701.44 40.80 0.00563111 18.58 0.17812900 23.4883 23.89 0.00876689 23.89 0.00876689 43.1126 11728.74 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 FRONT_RETAIL Coincident HeatingDesignCapacity N/A Yes No unknown No 27854.973 27854.973 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN Fan:SystemModel 1.137560 1.24357400   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 27854.97 27854.97 1.0000 1.24357400 1.137560 17.71 11.82 0.00709148 35763.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 27854.97 0.50 0.00431558 0.50 0.17812900 15.6589 20.90 0.00760685 21.11 0.00760685 44.3748 9720.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-AC:1_OA_CONTROLLER DifferentialDryBulb 0.00 1.95 -      
PSZ-AC:2_OA_CONTROLLER DifferentialDryBulb 0.00 8.03 -      
PSZ-AC:3_OA_CONTROLLER DifferentialDryBulb 0.00 1.36 -      
PSZ-AC:4_OA_CONTROLLER DifferentialDryBulb 0.00 1.14 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BACK_SPACE BACK_SPACE_DCV 0.000000 0.000610 0.000000 0.000000 Sum   1.00 1.00  
CORE_RETAIL CORE_RETAIL_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
POINT_OF_SALE POINT_OF_SALE_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
FRONT_RETAIL FRONT_RETAIL_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BACK_SPACE 1541.67 2745.33 389.67
CORE_RETAIL 1750.67 1866.50 78.67
POINT_OF_SALE 2425.50 905.00 62.33
FRONT_RETAIL 2069.50 1296.50 84.33
FRONT_ENTRY 3595.17 4085.50 3009.67
Facility 3893.00 4681.33 3072.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 0.00
POINT_OF_SALE 0.00 0.33 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 100.17 0.00 95.83 0.00
Facility 100.17 0.33 95.83 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.05 8.18 2317.33 0.444 0.040 0.000 0.000
CORE_RETAIL 128.05 258.43 9762.95 0.718 0.008 0.000 0.000
POINT_OF_SALE 12.07 24.35 919.94 1.144 0.046 0.000 0.000
FRONT_RETAIL 12.07 24.35 919.94 0.914 0.046 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 35.421 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BACK_SPACE 4.05 8.18 2317.33 0.357 0.000 0.000 0.000
CORE_RETAIL 128.05 258.43 9762.95 0.392 0.000 0.000 0.000
POINT_OF_SALE 12.07 24.35 919.94 0.393 0.000 0.000 0.000
FRONT_RETAIL 12.07 24.35 919.94 0.392 0.000 0.000 0.000
FRONT_ENTRY 0.96 1.94 73.20 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BACK_SPACE PSZ-AC:1 4.05 8.18 2317.33 379.89 0.2316 0.232
CORE_RETAIL PSZ-AC:2 128.05 258.43 9762.95 1600.48 1.8904 0.976
POINT_OF_SALE PSZ-AC:3 12.07 24.35 919.94 150.81 0.1781 0.092
FRONT_RETAIL PSZ-AC:4 12.07 24.35 919.94 150.81 0.1781 0.092
FRONT_ENTRY   0.96 1.94 73.20 12.00   0.014
Total Facility   157.19 317.25 13993.36 2293.99 2.4782 1.405


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BACK_SPACE 5155115.42 0.00 5155115.42 1512602.11 6667717.53 7303124.67 3780.54 4448.29 531.18 90.35
CORE_RETAIL 34589863.53 0.00 34589863.53 1297022.52 35886886.05 38574523.74 3773.25 3517.78 1468.98 111.13
POINT_OF_SALE 5249144.84 0.00 5249144.84 689832.53 5938977.37 3634792.93 3741.64 2993.59 2024.77 133.10
FRONT_RETAIL 4166589.14 0.00 4166589.14 689832.53 4856421.66 3634792.93 3768.82 3361.77 1629.41 105.32
FRONT_ENTRY 0.00 0.00 0.00 12518301.92 12518301.92 446965.66 8760.00 0.00 0.00 0.00
Total Facility 49160712.93 0.00 49160712.93 16707591.60 65868304.53 53594199.92 8760.00 4456.85 2033.21 142.89


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BACK_SPACE 0.2805 0.0000 0.2805 0.0254 0.3059 0.2316 0.00 4448.08 464.92
CORE_RETAIL 1.9091 0.0000 1.9091 0.0218 1.9308 1.4170 0.00 3517.11 1395.89
POINT_OF_SALE 0.2868 0.0000 0.2868 0.0116 0.2984 0.1335 0.00 2993.09 1919.91
FRONT_RETAIL 0.2290 0.0000 0.2290 0.0116 0.2406 0.1335 0.00 3361.44 1551.56
FRONT_ENTRY 0.0000 0.0000 0.0000 0.6991 0.6991 0.0142 4913.00 0.00 0.00
Total Facility 2.7054 0.0000 2.7054 0.7694 3.4748 1.9298 4913.00 4455.14 1923.72


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 6160698.55 0.00 6160698.55 7303124.67 3776.00 0.57 4983.43 90.35
PSZ-AC:2 41337435.20 0.00 41337435.20 38574523.74 3766.90 0.50 4992.60 111.13
PSZ-AC:3 6273116.74 0.00 6273116.74 3634792.93 3735.11 0.67 5024.23 133.10
PSZ-AC:4 4979386.64 0.00 4979386.64 3634792.93 3765.38 0.42 4994.20 105.32


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.3352 0.0000 0.3352 0.2316 0.00 0.00 4913.00
PSZ-AC:2 2.2815 0.0000 2.2815 1.4170 0.00 0.00 4913.00
PSZ-AC:3 0.3427 0.0000 0.3427 0.1335 0.00 0.00 4913.00
PSZ-AC:4 0.2737 0.0000 0.2737 0.1335 0.00 0.00 4913.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 313.10 262.63 0.00 0.00 0.00 4427.62 0.00 0.00 0.00
PSZ-AC:2 0.00 833.84 728.37 0.00 0.00 0.00 3461.92 0.00 0.00 0.00
PSZ-AC:3 0.00 1194.91 881.80 0.00 0.00 0.00 2969.40 0.00 0.00 0.00
PSZ-AC:4 0.00 948.29 747.84 0.00 0.00 0.00 3322.19 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 1.0940 0.5850 0.0000 0.0000 0.0000 0.2768 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 4.4546 2.8150 0.0000 0.0000 0.0000 1.6813 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.7546 0.4324 0.0000 0.0000 0.0000 0.1599 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.6301 0.3597 0.0000 0.0000 0.0000 0.1587 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Surfaces by Class

Total Outdoors
Wall 26 10
Floor 5 5
Roof 5 5
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 19 19
Door 13 13
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 4
Conditioned Zones 5
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 467
Defaulted Fields 428
Fields with Defaults 1337
Autosized Fields 72
Autosizable Fields 182
Autocalculated Fields 78
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
Electricity:Building 400.09 2478.04 09-JUL-08:00 28895.59 02-JAN-17:30
Electricity:Zone:BACK_SPACE 59.29 490.94 01-JAN-00:10 3419.71 02-JAN-09:10
Electricity:SpaceType:GENERAL 400.09 2478.04 09-JUL-08:00 28895.59 02-JAN-17:30
InteriorLights:Electricity 205.79 706.45 09-JUL-08:00 18154.70 02-JAN-17:30
InteriorLights:Electricity:Zone:BACK_SPACE 9.51 37.12 01-JAN-00:10 668.29 02-JAN-09:10
InteriorLights:Electricity:SpaceType:GENERAL 205.79 706.45 09-JUL-08:00 18154.70 02-JAN-17:30
LightsWired:InteriorLights:Electricity 205.79 706.45 09-JUL-08:00 18154.70 02-JAN-17:30
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE 9.51 37.12 01-JAN-00:10 668.29 02-JAN-09:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 205.79 706.45 09-JUL-08:00 18154.70 02-JAN-17:30
Electricity:Zone:CORE_RETAIL 239.85 1277.10 09-JUL-08:00 19291.51 02-JAN-17:30
InteriorLights:Electricity:Zone:CORE_RETAIL 155.92 511.85 09-JUL-08:00 14651.93 02-JAN-17:30
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL 155.92 511.85 09-JUL-08:00 14651.93 02-JAN-17:30
Electricity:Zone:POINT_OF_SALE 72.34 557.12 01-JAN-00:10 4293.33 02-JAN-09:10
InteriorLights:Electricity:Zone:POINT_OF_SALE 19.65 76.70 01-JAN-00:10 1380.62 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE 19.65 76.70 01-JAN-00:10 1380.62 02-JAN-09:10
Electricity:Zone:FRONT_RETAIL 27.56 148.81 01-JAN-00:10 1817.80 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_RETAIL 19.65 76.70 01-JAN-00:10 1380.62 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL 19.65 76.70 01-JAN-00:10 1380.62 02-JAN-09:10
Electricity:Zone:FRONT_ENTRY 1.04 4.07 01-JAN-00:10 73.24 02-JAN-09:10
InteriorLights:Electricity:Zone:FRONT_ENTRY 1.04 4.07 01-JAN-00:10 73.24 02-JAN-09:10
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY 1.04 4.07 01-JAN-00:10 73.24 02-JAN-09:10
InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE 49.77 453.82 01-JAN-00:10 2751.42 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 194.30 1771.59 01-JAN-00:10 10740.89 02-JAN-09:10
InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL 83.93 765.25 01-JAN-00:10 4639.58 02-JAN-09:10
InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE 52.69 480.42 01-JAN-00:10 2912.71 02-JAN-09:10
InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL 7.91 72.11 01-JAN-00:10 437.18 02-JAN-09:10
ElectricityPurchased:Facility 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
ElectricityPurchased:Plant 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
Cogeneration:ElectricityPurchased 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
General:Cogeneration:ElectricityPurchased 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
ElectricityNet:Plant 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
Cogeneration:ElectricityNet 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
General:Cogeneration:ElectricityNet 861.57 2621.26 09-JUL-07:00 89854.22 28-JUN-15:00
Electricity:HVAC 418.44 0.00 01-JAN-00:10 65932.16 28-JUN-15:00
Fans:Electricity 143.25 0.00 01-JAN-00:10 12308.97 14-JUL-06:10
General:Fans:Electricity 143.25 0.00 01-JAN-00:10 12308.97 14-JUL-06:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 275.19 0.00 01-JAN-00:10 53763.25 28-JUN-15:00
General:Cooling:Electricity 275.19 0.00 01-JAN-00:10 53763.25 28-JUN-15:00
ExteriorLights:Electricity 43.04 0.00 01-JAN-07:30 3742.41 01-JAN-06:10
General:ExteriorLights:Electricity 43.04 0.00 01-JAN-07:30 3742.41 01-JAN-06:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 94.25 1862.00 19-FEB-12:10 83709.11 02-JAN-07:10
NaturalGas:HVAC 6.94 0.00 01-JAN-00:10 81403.68 01-JAN-09:10
Heating:NaturalGas 6.94 0.00 01-JAN-00:10 81403.68 01-JAN-09:10
General:Heating:NaturalGas 6.94 0.00 01-JAN-00:10 81403.68 01-JAN-09:10
NaturalGas:Plant 87.31 1862.00 05-FEB-12:10 4956.95 23-JAN-12:40
WaterSystems:NaturalGas 87.31 1862.00 05-FEB-12:10 4956.95 23-JAN-12:40
Water Heater:WaterSystems:NaturalGas 87.31 1862.00 05-FEB-12:10 4956.95 23-JAN-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
Water:Plant 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
Water Heater:WaterSystems:Water 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
MainsWater:Facility 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
MainsWater:Plant 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10
Water Heater:WaterSystems:MainsWater 134.99 0.00 01-JAN-00:10 0.00 09-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1701.06 0.00 01-JAN-00:10 256484.18 23-JUL-08:10
EnergyTransfer:Building 767.34 0.00 01-JAN-00:10 101870.19 30-JUN-06:10
EnergyTransfer:Zone:BACK_SPACE 93.74 0.00 01-JAN-00:10 18529.62 23-JUL-08:10
Heating:EnergyTransfer 11.02 0.00 01-JAN-00:10 60379.75 01-JAN-08:10
Heating:EnergyTransfer:Zone:BACK_SPACE 3.99 0.00 01-JAN-00:10 17754.72 02-JAN-06:10
General:Heating:EnergyTransfer 11.02 0.00 01-JAN-00:10 60379.75 01-JAN-08:10
General:Heating:EnergyTransfer:Zone:BACK_SPACE 3.99 0.00 01-JAN-00:10 17754.72 02-JAN-06:10
Cooling:EnergyTransfer 756.32 0.00 01-JAN-00:10 99622.42 23-JUL-08:10
Cooling:EnergyTransfer:Zone:BACK_SPACE 89.75 0.00 01-JAN-00:10 18529.62 23-JUL-08:10
General:Cooling:EnergyTransfer 756.32 0.00 01-JAN-00:10 99622.42 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:BACK_SPACE 89.75 0.00 01-JAN-00:10 18529.62 23-JUL-08:10
EnergyTransfer:Zone:CORE_RETAIL 485.00 0.00 01-JAN-00:10 66491.51 30-JUN-06:10
Heating:EnergyTransfer:Zone:CORE_RETAIL 5.95 0.00 01-JAN-00:10 36250.59 01-JAN-09:10
General:Heating:EnergyTransfer:Zone:CORE_RETAIL 5.95 0.00 01-JAN-00:10 36250.59 01-JAN-09:10
Cooling:EnergyTransfer:Zone:CORE_RETAIL 479.04 0.00 01-JAN-00:10 64154.73 30-JUN-06:10
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL 479.04 0.00 01-JAN-00:10 64154.73 30-JUN-06:10
EnergyTransfer:Zone:POINT_OF_SALE 109.76 0.00 01-JAN-00:10 12568.47 06-OCT-14:20
Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.44 0.00 01-JAN-00:10 2297.93 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE 0.44 0.00 01-JAN-00:10 2297.93 13-FEB-07:10
Cooling:EnergyTransfer:Zone:POINT_OF_SALE 109.32 0.00 01-JAN-00:10 12568.47 06-OCT-14:20
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE 109.32 0.00 01-JAN-00:10 12568.47 06-OCT-14:20
EnergyTransfer:Zone:FRONT_RETAIL 78.74 0.00 01-JAN-00:10 10571.52 06-OCT-14:20
Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.52 0.00 01-JAN-00:10 4488.53 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL 0.52 0.00 01-JAN-00:10 4488.53 13-FEB-07:10
Cooling:EnergyTransfer:Zone:FRONT_RETAIL 78.22 0.00 01-JAN-00:10 10571.52 06-OCT-14:20
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL 78.22 0.00 01-JAN-00:10 10571.52 06-OCT-14:20
EnergyTransfer:Zone:FRONT_ENTRY 0.10 0.00 01-JAN-00:10 3018.74 01-JAN-08:10
Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.10 0.00 01-JAN-00:10 3018.74 01-JAN-08:10
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY 0.10 0.00 01-JAN-00:10 3018.74 01-JAN-08:10
Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 12.89 08-DEC-20:10
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY 0.00 0.00 01-JAN-00:10 12.89 08-DEC-20:10
EnergyTransfer:HVAC 933.73 0.00 01-JAN-00:10 162953.62 14-JUL-06:10
HeatingCoils:EnergyTransfer 5.56 0.00 01-JAN-00:10 65629.19 01-JAN-09:10
CoolingCoils:EnergyTransfer 928.17 0.00 01-JAN-00:10 162953.62 14-JUL-06:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BACK_SPACE 0.000 0.000 3.990 -89.744 0.000 0.000 5.055 9.514 49.772 0.000 0.000 2.925 26.699 0.000 0.000 0.000 -8.212 -0.001
CORE_RETAIL 0.000 0.000 5.955 -479.038 0.000 0.000 155.231 155.922 83.928 93.979 0.000 2.585 10.035 0.000 -20.485 0.000 -8.111 -0.013
POINT_OF_SALE 0.000 0.000 0.445 -109.316 0.000 0.000 14.545 19.654 52.690 42.286 0.000 1.249 0.003 0.000 -13.175 0.000 -4.653 -3.724
FRONT_RETAIL 0.000 0.000 0.524 -78.216 0.000 0.000 14.614 19.654 7.908 42.256 0.000 1.289 8.924 0.000 -12.626 0.000 -4.327 -0.001
FRONT_ENTRY 0.103 -0.000 0.000 0.000 0.000 0.000 0.875 1.043 0.000 8.142 0.000 3.558 0.000 0.000 -2.544 0.000 -8.218 -2.959
Total Facility 0.103 -0.000 10.913 -756.315 0.000 0.000 190.320 205.787 194.299 186.664 0.000 11.606 45.662 0.000 -48.830 0.000 -33.521 -6.698


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 13-MAY-06:02 0.00 0.00 0.00 -45046.94 0.00 0.00 52.16 74.26 917.14 0.00 0.00 0.00 44194.99 0.00 -0.00 0.00 -191.60 0.00
CORE_RETAIL 07-APR-06:02 0.00 0.00 0.00 -209182.19 0.00 0.00 1607.70 3188.97 2062.04 0.00 0.00 0.00 203964.70 0.00 -1340.37 0.00 -300.84 0.00
POINT_OF_SALE 01-JUL-05:02 0.00 0.00 0.00 -29015.42 0.00 0.00 0.00 76.70 480.42 0.00 0.00 0.00 29471.26 0.00 -966.28 0.00 -46.68 0.00
FRONT_RETAIL 19-OCT-06:02 0.00 0.00 0.00 -25772.83 0.00 0.00 150.36 306.80 194.30 0.00 0.00 0.00 26335.14 0.00 -1102.44 0.00 -111.34 0.00
FRONT_ENTRY 08-DEC-20:01 0.00 -116.02 0.00 0.00 0.00 0.00 59.01 40.69 0.00 0.00 0.00 0.00 230.44 0.00 -207.79 0.00 -6.33 0.00
Total Facility 01-MAY-06:02 0.00 0.00 0.00 -285496.11 0.00 0.00 1968.35 3880.10 4773.73 0.00 0.00 0.00 278772.11 0.00 -3225.09 0.00 -673.09 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BACK_SPACE 10-DEC-08:61 0.00 0.00 46895.02 0.00 0.00 0.00 0.00 37.12 453.82 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -91.55 -47294.40
CORE_RETAIL 01-JAN-08:61 0.00 0.00 212135.44 0.00 0.00 0.00 0.00 775.85 765.25 0.00 0.00 0.00 0.00 0.00 -1347.05 0.00 -447.29 -211882.20
POINT_OF_SALE 01-JAN-08:61 0.00 0.00 9718.13 0.00 0.00 0.00 0.00 76.70 480.42 825.32 0.00 0.00 0.00 0.00 -0.00 0.00 -238.79 -10861.78
FRONT_RETAIL 01-JAN-08:61 0.00 0.00 26012.06 0.00 0.00 0.00 0.00 76.70 72.11 873.78 0.00 0.00 0.00 0.00 -0.00 0.00 -238.28 -26796.37
FRONT_ENTRY 06-DEC-08:05 4192.66 0.00 0.00 0.00 0.00 0.00 34.16 32.55 0.00 331.27 0.00 0.00 0.00 0.00 -0.00 0.00 -3268.86 -1321.78
Total Facility 01-JAN-08:61 1829.99 0.00 294423.12 0.00 0.00 0.00 0.00 970.44 1771.59 1894.21 0.00 0.00 0.00 0.00 -1347.05 0.00 -5086.37 -294455.94



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 1.9484 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 1.9510 0.1187 1.0000 Not calculated 0.2316 0.1187    
PSZ-AC:2 7.7926 0.0000 258.4342 1.0000 Calculated from schedules 1.8904 8.0300 0.2354 1.0000 Not calculated 1.8904 0.2354    
PSZ-AC:3 1.3623 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3623 0.1308 1.0000 Not calculated 0.1781 0.1308    
PSZ-AC:4 1.1376 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.1376 0.1566 1.0000 Not calculated 0.1781 0.1566    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 1.9484 0.0000 8.1781 1.0000 Calculated from schedules 0.2316 1.9484 1.0000 1.0000 Not calculated 0.2316 0.1189    
PSZ-AC:2 7.7926 0.0000 258.4342 1.0000 Calculated from schedules 1.8904 7.7926 1.0000 1.0000 Not calculated 1.8904 0.2426    
PSZ-AC:3 1.3623 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.3623 1.0000 1.0000 Not calculated 0.1781 0.1308    
PSZ-AC:4 1.1376 0.0000 24.3517 1.0000 Calculated from schedules 0.1781 1.1376 1.0000 1.0000 Not calculated 0.1781 0.1566    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BACK_SPACE PSZ-AC:1 0.000000 8.1781 0.000610 379.89 0.2316 1.0000 0.2316 1.000 0.2316
CORE_RETAIL PSZ-AC:2 0.003540 258.4342 0.000610 1600.48 1.8904 1.0000 1.8904 1.000 1.8904
POINT_OF_SALE PSZ-AC:3 0.003540 24.3517 0.000610 150.81 0.1781 1.0000 0.1781 1.000 0.1781
FRONT_RETAIL PSZ-AC:4 0.003540 24.3517 0.000610 150.81 0.1781 1.0000 0.1781 1.000 0.1781


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.18 0.000610 379.8900 0.2316 0.2316 0.2316
PSZ-AC:2 0.003540 258.43 0.000610 1600.4829 1.8904 1.8904 1.8904
PSZ-AC:3 0.003540 24.35 0.000610 150.8100 0.1781 0.1781 0.1781
PSZ-AC:4 0.003540 24.35 0.000610 150.8100 0.1781 0.1781 0.1781


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.9484 1.9484 1.9484 No 0.2316 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.7926 7.7926 7.7926 No 1.8904 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3623 1.3623 1.3623 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.1376 1.1376 1.1376 No 0.1781 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 1.9484 1.9510 1.9484 1.9484 0.2316 1.0000
PSZ-AC:2 7.7926 8.0300 7.7926 7.7926 1.8904 1.0000
PSZ-AC:3 1.3623 1.3623 1.3623 1.3623 0.1781 1.0000
PSZ-AC:4 1.1376 1.1376 1.1376 1.1376 0.1781 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BACK_SPACE PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.9484 1.9484 1.9484 No 0.2316 0.2071 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_RETAIL PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 7.7926 7.7926 7.7926 No 1.8904 0.7549 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
POINT_OF_SALE PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.3623 1.3623 1.3623 No 0.1781 0.3285 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONT_RETAIL PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.1376 1.1376 1.1376 No 0.1781 0.3286 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 1.9484 1.9484 1.9484 1.9484 0.2316 1.0000
PSZ-AC:2 7.7926 7.7926 7.7926 7.7926 1.8904 1.0000
PSZ-AC:3 1.3623 1.3623 1.3623 1.3623 0.1781 1.0000
PSZ-AC:4 1.1376 1.1376 1.1376 1.1376 0.1781 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 2293.99
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BACK_SPACE 379.89 379.89 0.00 94.22
CORE_RETAIL 1600.48 1600.48 0.00 94.22
POINT_OF_SALE 150.81 150.81 0.00 94.22
FRONT_RETAIL 150.81 150.81 0.00 94.22
FRONT_ENTRY 12.00 12.00 0.00 94.22
Totals 2293.99 2293.99 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 95.83
Number of hours cooling loads not met 0.00
Number of hours not met 95.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 6.94 81403.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 275.19 53763.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 205.79 18154.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 43.04 3742.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 194.30 10740.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 143.25 12308.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 87.31 4956.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 194.30 861.57
Natural Gas 0.00 94.25
Additional 0.00 0.00
Total 194.30 955.82


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 89.71
Space Heating 0.00
Space Cooling 119.96
Fans (All) 62.45
Service Water Heating 0.00
Receptacle Equipment 84.70
Miscellaneous (All) 375.57
Subtotal 375.57


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 3.02
Service Water Heating 38.06
Miscellaneous (All) 41.09
Subtotal 41.09


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 21.53
Space Heating 0.73
Space Cooling 28.79
Fans (All) 14.99
Service Water Heating 9.14
Receptacle Equipment 20.33
Miscellaneous 4.50


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
FRONTENTRY_COILSCHED 8760. 8760.
FRONTENTRY_FANSCHED 8760. 8760.
LTG_SCH_ENTRY 3609. 8760.
LTG_SCH_CORE 3609. 8760.
LTG_SCH_BACK 1677. 8760.
LTG_SCH_SALE 3609. 8760.
LTG_SCH_FRONT 3609. 8760.
BLDG_OCC_SCH 2410. 4950.
BLDG_EQUIP_SCH 4552. 8760.
BLDG_ELEVATORS 2743. 4950.
INFIL_SCH 3551. 3551.
INFIL_HALF_ON_SCH 6156. 8760.
INFIL_DOOR_OPENING_SCH 2505. 4380.
BLDG_SWH_SCH 2009. 4950.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6543. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4950. 4950.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
INFIL_SCH_PNNL 4774. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4950. 4950.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6132. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_FRONTENTRY_STD2013 FRONT_ENTRY HEATING SP January 16.00 365 15.56 365
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP BACK_SPACE DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP BACK_SPACE DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 8380.33 379.67 0.00 0.00 0.00
CORE_RETAIL 8540.83 219.17 0.00 0.00 0.00
POINT_OF_SALE 7893.00 867.00 0.00 0.00 0.00
FRONT_RETAIL 8170.67 589.33 0.00 0.00 0.00
FRONT_ENTRY 5498.50 2720.00 540.33 1.17 0.00
Min 5498.50 219.17 0.00 0.00 0.00
Max 8540.83 2720.00 540.33 1.17 0.00
Average 7696.67 955.03 108.07 0.23 0.00
Sum 38483.33 4775.17 540.33 1.17 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BACK_SPACE 16872.00 0.00 0.00 0.00 0.00
CORE_RETAIL 609599.00 0.00 0.00 0.00 0.00
POINT_OF_SALE 56000.00 0.00 0.00 0.00 0.00
FRONT_RETAIL 56000.00 0.00 0.00 0.00 0.00
FRONT_ENTRY 953.17 609.50 356.17 1.17 0.00
Min 953.17 0.00 0.00 0.00 0.00
Max 609599.00 609.50 356.17 1.17 0.00
Average 147884.83 121.90 71.23 0.23 0.00
Sum 739424.17 609.50 356.17 1.17 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 8208.67 551.33 0.00 0.00 0.00
CORE_RETAIL 8258.00 502.00 0.00 0.00 0.00
POINT_OF_SALE 8007.83 752.17 0.00 0.00 0.00
FRONT_RETAIL 8094.83 665.17 0.00 0.00 0.00
FRONT_ENTRY 6301.50 2427.83 30.67 0.00 0.00
Min 6301.50 502.00 0.00 0.00 0.00
Max 8258.00 2427.83 30.67 0.00 0.00
Average 7774.17 979.70 6.13 0.00 0.00
Sum 38870.83 4898.50 30.67 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BACK_SPACE 16818.17 53.83 0.00 0.00 0.00
CORE_RETAIL 606937.33 2661.67 0.00 0.00 0.00
POINT_OF_SALE 55804.00 196.00 0.00 0.00 0.00
FRONT_RETAIL 55756.00 244.00 0.00 0.00 0.00
FRONT_ENTRY 1157.33 736.67 26.00 0.00 0.00
Min 1157.33 53.83 0.00 0.00 0.00
Max 606937.33 2661.67 26.00 0.00 0.00
Average 147294.57 778.43 5.20 0.00 0.00
Sum 736472.83 3892.17 26.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:31:08

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 8760.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 8760.00
Average 0.00 0.00 0.00 1752.00
Sum 0.00 0.00 0.00 8760.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BACK_SPACE 0.00 0.00 0.00 0.00
CORE_RETAIL 0.00 0.00 0.00 609599.00
POINT_OF_SALE 0.00 0.00 0.00 0.00
FRONT_RETAIL 0.00 0.00 0.00 0.00
FRONT_ENTRY 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 609599.00
Average 0.00 0.00 0.00 121919.80
Sum 0.00 0.00 0.00 609599.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.563468E+09 3319.25 04-JAN-07:05 7.17 3.09 0.262765E+09 326.80 25-JAN-15:09 23.00 10.66
February 0.807713E+09 3617.76 28-FEB-07:07 5.33 4.66 0.216953E+09 315.47 18-FEB-16:19 5.33 4.66
March 0.110260E+10 4475.57 27-MAR-06:05 1.97 -1.0 0.274620E+09 326.81 18-MAR-10:39 1.97 -1.0
April 0.665647E+10 43287.80 13-APR-06:02 16.17 7.41 0.287934E+09 326.80 26-APR-14:50 27.33 10.05
May 0.103739E+11 45041.83 13-MAY-06:02 14.67 8.59 0.298730E+09 326.80 13-MAY-12:50 27.67 11.04
June 0.166526E+11 39637.88 20-JUN-05:02 20.67 9.05 0.294626E+09 326.83 17-JUN-15:50 20.67 9.05
July 0.165753E+11 42468.10 01-JUL-05:02 18.83 6.90 0.292678E+09 326.83 17-JUL-14:00 38.00 20.59
August 0.154595E+11 39149.91 24-AUG-06:02 19.33 9.33 0.305252E+09 326.84 09-AUG-14:50 19.33 9.33
September 0.130377E+11 38359.46 16-SEP-06:02 19.58 12.28 0.288539E+09 326.82 09-SEP-13:30 19.58 12.28
October 0.619808E+10 39752.44 17-OCT-06:02 18.17 7.26 0.288525E+09 326.82 07-OCT-12:09 18.17 7.26
November 0.170468E+10 25783.47 03-NOV-06:02 15.83 12.39 0.266217E+09 326.81 01-NOV-14:09 15.83 12.39
December 0.613197E+09 5163.78 05-DEC-07:05 -0.5 -4.0 0.242513E+09 326.80 01-DEC-15:39 -0.5 -4.0
                     
Annual Sum or Average 0.897453E+11         0.331935E+10        
Minimum of Months 0.563468E+09 3319.25   -0.5 -4.0 0.216953E+09 315.47   -0.5 -4.0
Maximum of Months 0.166526E+11 45041.83   20.67 12.39 0.305252E+09 326.84   38.00 20.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.192993E+11 101127.44 08-JAN-09:02 18.17 12.71 0.905247E+10 10327.22 09-JAN-15:20 18.00 10.66
February 0.151746E+11 24360.15 01-FEB-15:20 15.33 6.93 0.813586E+10 10327.57 18-FEB-13:20 21.33 14.33
March 0.223757E+11 139043.09 17-MAR-06:03 14.30 9.49 0.950693E+10 10327.56 18-MAR-10:20 23.27 14.71
April 0.447428E+11 209181.76 07-APR-06:02 12.00 6.62 0.911600E+10 10327.27 14-APR-14:00 35.00 14.57
May 0.535744E+11 202693.22 01-MAY-06:02 13.50 5.09 0.944060E+10 10327.81 18-MAY-14:39 36.00 14.04
June 0.657812E+11 170226.30 21-JUN-06:02 19.17 9.24 0.931052E+10 10328.43 28-JUN-14:00 42.00 19.34
July 0.634185E+11 180453.64 01-JUL-05:02 18.83 6.90 0.924887E+10 10328.32 01-JUL-15:39 38.00 14.57
August 0.622941E+11 169142.14 24-AUG-06:02 19.33 9.33 0.964623E+10 10328.30 26-AUG-13:20 39.33 15.98
September 0.533350E+11 163981.20 16-SEP-06:02 19.58 12.28 0.911802E+10 10328.12 12-SEP-14:50 19.58 12.28
October 0.386934E+11 197870.64 19-OCT-06:02 14.33 7.38 0.921427E+10 10327.85 07-OCT-15:30 14.33 7.38
November 0.240663E+11 164450.24 02-NOV-06:02 16.00 11.38 0.880490E+10 10327.61 13-NOV-15:30 18.00 17.84
December 0.162851E+11 22348.51 01-DEC-15:30 23.30 10.04 0.882571E+10 10327.17 02-DEC-11:09 21.17 8.46
                     
Annual Sum or Average 0.479040E+12         0.109420E+12        
Minimum of Months 0.151746E+11 22348.51   12.00 5.09 0.813586E+10 10327.17   14.33 7.38
Maximum of Months 0.657812E+11 209181.76   23.30 12.71 0.964623E+10 10328.43   42.00 19.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.766543E+10 25252.90 08-JAN-09:02 18.17 12.71 0.868047E+09 973.14 21-JAN-13:39 17.67 11.10
February 0.405273E+10 7702.82 01-FEB-15:30 15.50 6.96 0.786371E+09 973.17 18-FEB-11:00 20.00 13.98
March 0.516215E+10 16640.37 17-MAR-06:03 14.30 9.49 0.901630E+09 973.15 11-MAR-15:20 14.30 9.49
April 0.904215E+10 26620.46 14-APR-06:02 16.50 7.47 0.859078E+09 973.17 14-APR-14:00 35.00 14.57
May 0.952053E+10 26567.31 18-MAY-06:02 17.83 8.62 0.889566E+09 973.16 20-MAY-14:09 36.00 13.67
June 0.118365E+11 27128.87 20-JUN-05:02 20.67 9.05 0.877311E+09 973.24 17-JUN-13:30 20.67 9.05
July 0.121516E+11 29021.41 01-JUL-05:02 18.83 6.90 0.871516E+09 973.28 15-JUL-13:09 33.17 21.23
August 0.127948E+11 26437.73 24-AUG-06:02 19.33 9.33 0.908971E+09 973.29 05-AUG-14:39 19.33 9.33
September 0.124516E+11 26897.35 29-SEP-05:02 21.42 11.53 0.859203E+09 973.28 13-SEP-14:00 21.42 11.53
October 0.105265E+11 27030.47 05-OCT-05:02 19.00 13.00 0.869889E+09 973.29 10-OCT-14:09 35.00 17.66
November 0.787777E+10 26364.40 02-NOV-06:02 16.00 11.38 0.836504E+09 973.27 01-NOV-14:00 16.00 11.38
December 0.623529E+10 9298.54 22-DEC-15:50 25.17 10.15 0.864644E+09 973.11 12-DEC-15:39 25.17 10.15
                     
Annual Sum or Average 0.109317E+12         0.103927E+11        
Minimum of Months 0.405273E+10 7702.82   14.30 6.90 0.786371E+09 973.11   14.30 9.05
Maximum of Months 0.127948E+11 29021.41   25.17 13.00 0.908971E+09 973.29   36.00 21.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.504443E+10 17854.14 08-JAN-09:02 18.17 12.71 0.862003E+09 973.12 21-JAN-13:50 17.83 11.17
February 0.220900E+10 5559.10 01-FEB-15:30 15.50 6.96 0.759052E+09 973.14 18-FEB-14:30 22.00 14.16
March 0.278105E+10 6233.59 18-MAR-14:50 27.02 12.43 0.886085E+09 973.14 18-MAR-10:20 27.02 12.43
April 0.638265E+10 25202.74 13-APR-06:02 16.17 7.41 0.858609E+09 973.14 14-APR-14:50 34.83 14.49
May 0.677919E+10 24492.86 16-MAY-06:02 17.00 6.19 0.889463E+09 973.13 20-MAY-14:09 36.00 13.67
June 0.906864E+10 22828.05 21-JUN-06:02 19.17 9.24 0.877301E+09 973.23 17-JUN-13:00 19.17 9.24
July 0.941485E+10 23783.38 01-JUL-05:02 18.83 6.90 0.871508E+09 973.26 26-JUL-14:50 34.83 20.28
August 0.994613E+10 22744.55 24-AUG-06:02 19.33 9.33 0.908960E+09 973.26 21-AUG-14:20 19.33 9.33
September 0.968669E+10 22588.66 29-SEP-05:02 21.42 11.53 0.859195E+09 973.26 23-SEP-15:30 21.42 11.53
October 0.779394E+10 25771.00 19-OCT-06:02 14.33 7.38 0.868193E+09 973.20 06-OCT-14:09 14.33 7.38
November 0.527677E+10 22615.23 02-NOV-06:02 16.00 11.38 0.832472E+09 973.21 01-NOV-14:00 16.00 11.38
December 0.383379E+10 7073.55 22-DEC-15:50 25.17 10.15 0.851039E+09 973.11 02-DEC-11:09 25.17 10.15
                     
Annual Sum or Average 0.782171E+11         0.103239E+11        
Minimum of Months 0.220900E+10 5559.10   14.33 6.19 0.759052E+09 973.11   14.33 7.38
Maximum of Months 0.994613E+10 25771.00   27.02 12.71 0.908960E+09 973.26   36.00 20.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27 1.81 58921486.27 117.91 31-JAN-15:00 29.00 10.73
February 0.00 0.00 01-FEB-00:10 11.90 4.43 33358932.07 66.52 18-FEB-14:50 22.00 13.89
March 0.00 0.00 01-MAR-00:10 11.85 8.83 57097680.59 115.34 16-MAR-14:00 28.80 13.71
April 0.00 0.00 01-APR-00:10 15.28 7.34 98807029.27 171.54 14-APR-14:00 35.00 14.57
May 0.00 0.00 01-MAY-00:10 19.10 7.18 0.120625E+09 182.01 20-MAY-15:09 35.83 13.83
June 0.00 0.00 01-JUN-00:10 25.83 11.09 0.146606E+09 186.05 01-JUN-14:09 37.17 17.05
July 0.00 0.00 01-JUL-00:10 27.73 14.60 0.138817E+09 186.05 01-JUL-12:00 37.00 14.14
August 0.00 0.00 01-AUG-00:10 29.40 18.35 0.142706E+09 186.05 08-AUG-14:09 38.00 20.60
September 0.00 0.00 01-SEP-00:10 26.22 16.66 0.125524E+09 186.05 01-SEP-14:09 36.70 21.94
October 0.00 0.00 01-OCT-00:10 25.15 15.51 87115692.68 176.11 06-OCT-14:00 35.00 14.90
November 0.00 0.00 01-NOV-00:10 17.23 10.27 55333207.75 119.40 01-NOV-14:00 29.00 16.20
December 7734.92 116.02 08-DEC-20:01 7.17 0.11 44620225.28 96.11 22-DEC-15:09 25.83 10.37
                     
Annual Sum or Average 7734.92         0.110953E+10        
Minimum of Months 0.00 0.00   4.27 0.11 33358932.07 66.52   22.00 10.37
Maximum of Months 7734.92 116.02   29.40 18.35 0.146606E+09 186.05   38.00 21.94



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.887939E+09 46602.90 02-JAN-06:01 4.33
February 0.558694E+09 46854.09 05-FEB-08:61 8.33
March 0.488730E+09 45728.82 27-MAR-05:02 2.52
April 0.126920E+09 2787.53 23-APR-17:03 32.83
May 92122157.68 3510.14 07-MAY-17:02 35.83
June 62058537.12 4346.93 28-JUN-19:02 39.50
July 57384601.93 4026.28 02-JUL-17:02 38.00
August 58183666.01 4487.62 27-AUG-17:02 39.83
September 52137007.84 3200.24 08-SEP-19:03 35.22
October 91040178.90 2703.33 01-OCT-17:03 32.83
November 0.203504E+09 25294.02 24-NOV-07:03 4.50
December 0.131130E+10 46895.02 10-DEC-08:61 7.67
         
Annual Sum or Average 0.399001E+10      
Minimum of Months 52137007.84 2703.33   2.52
Maximum of Months 0.131130E+10 46895.02   39.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.713872E+09 212135.34 01-JAN-08:61 1.37
February 0.495086E+09 5333.71 12-FEB-08:13 12.00
March 0.562042E+09 6491.07 19-MAR-17:03 25.72
April 0.551131E+09 14276.00 23-APR-17:03 32.83
May 0.389998E+09 17831.43 07-MAY-17:02 35.83
June 0.423813E+09 25117.63 28-JUN-19:02 39.50
July 0.402617E+09 22729.38 21-JUL-19:02 37.83
August 0.404401E+09 22912.09 10-AUG-19:02 37.67
September 0.361901E+09 18914.54 08-SEP-19:03 35.22
October 0.547190E+09 14444.94 01-OCT-17:03 32.83
November 0.531422E+09 5367.05 05-NOV-07:11 7.33
December 0.571425E+09 9045.86 06-DEC-07:10 -0.5
         
Annual Sum or Average 0.595490E+10      
Minimum of Months 0.361901E+09 5333.71   -0.5
Maximum of Months 0.713872E+09 212135.34   39.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 55948439.67 9718.12 01-JAN-08:61 1.37
February 54564805.48 8542.16 13-FEB-07:03 8.33
March 57065901.40 3770.48 27-MAR-06:03 1.97
April 36413719.92 1189.78 15-APR-05:05 20.83
May 24740819.01 1498.25 07-MAY-17:02 35.83
June 26273122.55 2111.98 28-JUN-19:02 39.50
July 20208953.48 1831.50 21-JUL-19:02 37.83
August 18093556.87 1931.62 10-AUG-19:02 37.67
September 16420617.38 1363.76 08-SEP-19:03 35.22
October 31003169.33 1373.48 06-OCT-05:04 19.00
November 47146260.10 924.74 11-NOV-09:04 20.97
December 56880717.84 620.62 08-DEC-07:00 2.00
         
Annual Sum or Average 0.444760E+09      
Minimum of Months 16420617.38 620.62   1.37
Maximum of Months 57065901.40 9718.12   39.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 59170087.90 26012.03 01-JAN-08:61 1.37
February 65701141.33 15417.94 13-FEB-06:03 8.00
March 70633875.72 13814.12 27-MAR-06:03 1.97
April 50594282.80 1155.74 23-APR-17:03 32.83
May 50361488.74 1520.28 07-MAY-17:02 35.83
June 24566440.45 2170.83 28-JUN-19:02 39.50
July 23724986.95 1908.59 21-JUL-19:02 37.83
August 22252763.54 1980.25 10-AUG-19:02 37.67
September 17787580.23 1482.89 08-SEP-19:03 35.22
October 32899675.75 1117.57 01-OCT-17:03 32.83
November 43103187.41 628.21 11-NOV-09:04 20.97
December 62970433.86 10434.99 07-DEC-07:03 1.33
         
Annual Sum or Average 0.523766E+09      
Minimum of Months 17787580.23 628.21   1.33
Maximum of Months 70633875.72 26012.03   39.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 15336231.90 3639.66 01-JAN-08:03 1.37
February 1419891.30 2614.68 01-FEB-08:05 5.67
March 22269237.85 3029.01 28-MAR-07:05 5.42
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 1468974.21 1639.84 25-OCT-07:04 5.50
November 8323883.61 2392.21 23-NOV-08:05 2.50
December 54070734.50 4192.76 06-DEC-08:05 2.67
         
Annual Sum or Average 0.102889E+09      
Minimum of Months 0.00 0.00   1.37
Maximum of Months 54070734.50 4192.76   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.797804E+09 668.29 02-JAN-09:09 0.419292E+10 2751.42 02-JAN-09:09
February 0.725896E+09 668.29 01-FEB-09:09 0.380401E+10 2751.42 01-FEB-09:09
March 0.828011E+09 668.29 01-MAR-09:09 0.429860E+10 2751.42 01-MAR-09:09
April 0.781231E+09 668.29 01-APR-09:09 0.408537E+10 2751.42 01-APR-09:09
May 0.812908E+09 668.29 01-MAY-08:09 0.424576E+10 2751.42 01-MAY-08:09
June 0.799008E+09 668.29 01-JUN-08:09 0.415080E+10 2751.42 01-JUN-08:09
July 0.795131E+09 668.29 01-JUL-09:09 0.417978E+10 2751.42 01-JUL-09:09
August 0.828011E+09 668.29 01-AUG-08:09 0.429860E+10 2751.42 01-AUG-08:09
September 0.781231E+09 668.29 01-SEP-08:09 0.408428E+10 2751.42 01-SEP-08:09
October 0.797804E+09 668.29 02-OCT-08:09 0.419346E+10 2751.42 02-OCT-08:09
November 0.771474E+09 668.29 01-NOV-08:09 0.405935E+10 2751.42 01-NOV-08:09
December 0.795131E+09 668.29 01-DEC-09:09 0.417924E+10 2751.42 01-DEC-09:09
             
Annual Sum or Average 0.951364E+10     0.497722E+11    
Minimum of Months 0.725896E+09 668.29   0.380401E+10 2751.42  
Maximum of Months 0.828011E+09 668.29   0.429860E+10 2751.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148236E+11 14651.93 02-JAN-17:30 0.707031E+10 4639.58 02-JAN-09:09
February 0.126538E+11 14651.93 01-FEB-17:00 0.641452E+10 4639.58 01-FEB-09:09
March 0.130461E+11 14254.00 09-MAR-17:00 0.724851E+10 4639.58 01-MAR-09:09
April 0.117843E+11 12252.53 22-APR-16:00 0.688896E+10 4639.58 01-APR-09:09
May 0.122879E+11 11921.00 19-MAY-16:00 0.715941E+10 4639.58 01-MAY-08:09
June 0.124698E+11 11996.72 07-JUN-16:00 0.699930E+10 4639.58 01-JUN-08:09
July 0.119554E+11 12818.15 08-JUL-16:00 0.704816E+10 4639.58 01-JUL-09:09
August 0.128611E+11 12857.64 05-AUG-16:00 0.724851E+10 4639.58 01-AUG-08:09
September 0.117523E+11 13238.63 26-SEP-16:00 0.688712E+10 4639.58 01-SEP-08:09
October 0.137029E+11 14285.10 31-OCT-16:00 0.707123E+10 4639.58 02-OCT-08:09
November 0.139878E+11 14651.93 06-NOV-17:30 0.684509E+10 4639.58 01-NOV-08:09
December 0.145968E+11 14651.93 01-DEC-16:30 0.704724E+10 4639.58 01-DEC-09:09
             
Annual Sum or Average 0.155922E+12     0.839284E+11    
Minimum of Months 0.117523E+11 11921.00   0.641452E+10 4639.58  
Maximum of Months 0.148236E+11 14651.93   0.724851E+10 4639.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164818E+10 1380.62 02-JAN-09:09 0.443872E+10 2912.71 02-JAN-09:09
February 0.149963E+10 1380.62 01-FEB-09:09 0.402701E+10 2912.71 01-FEB-09:09
March 0.171059E+10 1380.62 01-MAR-09:09 0.455059E+10 2912.71 01-MAR-09:09
April 0.161394E+10 1380.62 01-APR-09:09 0.432486E+10 2912.71 01-APR-09:09
May 0.167939E+10 1380.62 01-MAY-08:09 0.449465E+10 2912.71 01-MAY-08:09
June 0.165067E+10 1380.62 01-JUN-08:09 0.439413E+10 2912.71 01-JUN-08:09
July 0.164266E+10 1380.62 01-JUL-09:09 0.442481E+10 2912.71 01-JUL-09:09
August 0.171059E+10 1380.62 01-AUG-08:09 0.455059E+10 2912.71 01-AUG-08:09
September 0.161394E+10 1380.62 01-SEP-08:09 0.432371E+10 2912.71 01-SEP-08:09
October 0.164818E+10 1380.62 02-OCT-08:09 0.443929E+10 2912.71 02-OCT-08:09
November 0.159379E+10 1380.62 01-NOV-08:09 0.429732E+10 2912.71 01-NOV-08:09
December 0.164266E+10 1380.62 01-DEC-09:09 0.442423E+10 2912.71 01-DEC-09:09
             
Annual Sum or Average 0.196542E+11     0.526899E+11    
Minimum of Months 0.149963E+10 1380.62   0.402701E+10 2912.71  
Maximum of Months 0.171059E+10 1380.62   0.455059E+10 2912.71  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.164818E+10 1380.62 02-JAN-09:09 0.666220E+09 437.18 02-JAN-09:09
February 0.149963E+10 1380.62 01-FEB-09:09 0.604426E+09 437.18 01-FEB-09:09
March 0.171059E+10 1380.62 01-MAR-09:09 0.683011E+09 437.18 01-MAR-09:09
April 0.161394E+10 1380.62 01-APR-09:09 0.649132E+09 437.18 01-APR-09:09
May 0.167939E+10 1380.62 01-MAY-08:09 0.674616E+09 437.18 01-MAY-08:09
June 0.165067E+10 1380.62 01-JUN-08:09 0.659528E+09 437.18 01-JUN-08:09
July 0.164266E+10 1380.62 01-JUL-09:09 0.664132E+09 437.18 01-JUL-09:09
August 0.171059E+10 1380.62 01-AUG-08:09 0.683011E+09 437.18 01-AUG-08:09
September 0.161394E+10 1380.62 01-SEP-08:09 0.648959E+09 437.18 01-SEP-08:09
October 0.164818E+10 1380.62 02-OCT-08:09 0.666307E+09 437.18 02-OCT-08:09
November 0.159379E+10 1380.62 01-NOV-08:09 0.644998E+09 437.18 01-NOV-08:09
December 0.164266E+10 1380.62 01-DEC-09:09 0.664046E+09 437.18 01-DEC-09:09
             
Annual Sum or Average 0.196542E+11     0.790839E+10    
Minimum of Months 0.149963E+10 1380.62   0.604426E+09 437.18  
Maximum of Months 0.171059E+10 1380.62   0.683011E+09 437.18  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 87431017.75 73.24 02-JAN-09:09 0.00 0.00
February 79550654.62 73.24 01-FEB-09:09 0.00 0.00
March 90741356.17 73.24 01-MAR-09:09 0.00 0.00
April 85614725.88 73.24 01-APR-09:09 0.00 0.00
May 89086186.96 73.24 01-MAY-08:09 0.00 0.00
June 87562845.39 73.24 01-JUN-08:09 0.00 0.00
July 87138067.45 73.24 01-JUL-09:09 0.00 0.00
August 90741356.17 73.24 01-AUG-08:09 0.00 0.00
September 85614725.88 73.24 01-SEP-08:09 0.00 0.00
October 87431017.75 73.24 02-OCT-08:09 0.00 0.00
November 84545457.27 73.24 01-NOV-08:09 0.00 0.00
December 87138067.45 73.24 01-DEC-09:09 0.00 0.00
           
Annual Sum or Average 0.104260E+10     0.00 0.00
Minimum of Months 79550654.62 73.24   0.00 0.00
Maximum of Months 90741356.17 73.24   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.699524E+09 0.797804E+09 0.419292E+10 0.00 0.00 0.00 0.00 7298362.76 0.125197E+10
February 0.638757E+09 0.725896E+09 0.380401E+10 0.00 0.00 0.00 0.00 0.00 0.911722E+09
March 0.730614E+09 0.828011E+09 0.429860E+10 0.00 0.00 0.00 0.00 14771136.23 0.129866E+10
April 0.690691E+09 0.781231E+09 0.408537E+10 0.00 0.00 0.00 0.00 0.200020E+09 0.508507E+09
May 0.715069E+09 0.812908E+09 0.424576E+10 0.00 0.00 0.00 0.00 0.388846E+09 0.347891E+09
June 0.705176E+09 0.799008E+09 0.415080E+10 0.00 0.00 0.00 0.00 0.730764E+09 0.135424E+09
July 0.700584E+09 0.795131E+09 0.417978E+10 0.00 0.00 0.00 0.00 0.637096E+09 0.127036E+09
August 0.730614E+09 0.828011E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.457091E+09 0.149825E+09
September 0.690691E+09 0.781231E+09 0.408428E+10 0.00 0.00 0.00 0.00 0.349995E+09 0.262162E+09
October 0.699524E+09 0.797804E+09 0.419346E+10 0.00 0.00 0.00 0.00 0.126070E+09 0.759965E+09
November 0.673027E+09 0.771474E+09 0.405935E+10 0.00 0.00 0.00 0.00 11637855.44 0.121251E+10
December 0.700584E+09 0.795131E+09 0.417924E+10 0.00 0.00 0.00 0.00 1438316.13 0.124637E+10
                   
Annual Sum or Average 0.837485E+10 0.951364E+10 0.497722E+11 0.00 0.00 0.00 0.00 0.292503E+10 0.821205E+10
Minimum of Months 0.638757E+09 0.725896E+09 0.380401E+10 0.00 0.00 0.00 0.00 0.00 0.127036E+09
Maximum of Months 0.730614E+09 0.828011E+09 0.429860E+10 0.00 0.00 0.00 0.00 0.730764E+09 0.129866E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.221054E+11 0.148236E+11 0.707031E+10 0.00 0.00 0.00 0.00 4555349.05 0.128714E+10
February 0.201852E+11 0.126538E+11 0.641452E+10 0.00 0.00 0.00 0.00 0.00 0.971616E+09
March 0.230879E+11 0.130461E+11 0.724851E+10 0.00 0.00 0.00 0.00 12515144.31 0.134858E+10
April 0.218263E+11 0.117843E+11 0.688896E+10 0.00 0.00 0.00 0.00 0.169399E+09 0.484175E+09
May 0.225967E+11 0.122879E+11 0.715941E+10 0.00 0.00 0.00 0.00 0.334683E+09 0.314478E+09
June 0.222841E+11 0.124698E+11 0.699930E+10 0.00 0.00 0.00 0.00 0.651795E+09 0.103423E+09
July 0.221389E+11 0.119554E+11 0.704816E+10 0.00 0.00 0.00 0.00 0.573695E+09 94326792.96
August 0.230879E+11 0.128611E+11 0.724851E+10 0.00 0.00 0.00 0.00 0.408281E+09 0.121525E+09
September 0.218263E+11 0.117523E+11 0.688712E+10 0.00 0.00 0.00 0.00 0.308834E+09 0.214130E+09
October 0.221054E+11 0.137029E+11 0.707123E+10 0.00 0.00 0.00 0.00 0.110454E+09 0.715741E+09
November 0.212681E+11 0.139878E+11 0.684509E+10 0.00 0.00 0.00 0.00 9627161.52 0.119778E+10
December 0.221389E+11 0.145968E+11 0.704724E+10 0.00 0.00 0.00 0.00 794136.36 0.125763E+10
                   
Annual Sum or Average 0.264651E+12 0.155922E+12 0.839284E+11 0.00 0.00 0.00 0.00 0.258463E+10 0.811054E+10
Minimum of Months 0.201852E+11 0.117523E+11 0.641452E+10 0.00 0.00 0.00 0.00 0.00 94326792.96
Maximum of Months 0.230879E+11 0.148236E+11 0.724851E+10 0.00 0.00 0.00 0.00 0.651795E+09 0.134858E+10



Table of Contents

Report: SpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.164818E+10 0.443872E+10 0.00 0.00 0.00 0.00 2422807.61 0.735290E+09
February 0.190200E+10 0.149963E+10 0.402701E+10 0.00 0.00 0.00 0.00 0.00 0.525014E+09
March 0.217552E+10 0.171059E+10 0.455059E+10 0.00 0.00 0.00 0.00 6650468.17 0.710388E+09
April 0.205665E+10 0.161394E+10 0.432486E+10 0.00 0.00 0.00 0.00 85752848.71 0.278998E+09
May 0.212923E+10 0.167939E+10 0.449465E+10 0.00 0.00 0.00 0.00 0.168258E+09 0.184296E+09
June 0.209978E+10 0.165067E+10 0.439413E+10 0.00 0.00 0.00 0.00 0.317476E+09 72146716.75
July 0.208610E+10 0.164266E+10 0.442481E+10 0.00 0.00 0.00 0.00 0.271565E+09 74231590.32
August 0.217552E+10 0.171059E+10 0.455059E+10 0.00 0.00 0.00 0.00 0.190118E+09 95875997.76
September 0.205665E+10 0.161394E+10 0.432371E+10 0.00 0.00 0.00 0.00 0.146620E+09 0.169136E+09
October 0.208295E+10 0.164818E+10 0.443929E+10 0.00 0.00 0.00 0.00 54202985.31 0.425425E+09
November 0.200405E+10 0.159379E+10 0.429732E+10 0.00 0.00 0.00 0.00 5120306.15 0.674046E+09
December 0.208610E+10 0.164266E+10 0.442423E+10 0.00 0.00 0.00 0.00 422368.88 0.707802E+09
                   
Annual Sum or Average 0.249375E+11 0.196542E+11 0.526899E+11 0.00 0.00 0.00 0.00 0.124861E+10 0.465265E+10
Minimum of Months 0.190200E+10 0.149963E+10 0.402701E+10 0.00 0.00 0.00 0.00 0.00 72146716.75
Maximum of Months 0.217552E+10 0.171059E+10 0.455059E+10 0.00 0.00 0.00 0.00 0.317476E+09 0.735290E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.208295E+10 0.164818E+10 0.666220E+09 0.00 0.00 0.00 0.00 2422805.12 0.699516E+09
February 0.190200E+10 0.149963E+10 0.604426E+09 0.00 0.00 0.00 0.00 0.00 0.490857E+09
March 0.217552E+10 0.171059E+10 0.683011E+09 0.00 0.00 0.00 0.00 6653222.20 0.666030E+09
April 0.205665E+10 0.161394E+10 0.649132E+09 0.00 0.00 0.00 0.00 87145401.11 0.254379E+09
May 0.212923E+10 0.167939E+10 0.674616E+09 0.00 0.00 0.00 0.00 0.173090E+09 0.160642E+09
June 0.209978E+10 0.165067E+10 0.659528E+09 0.00 0.00 0.00 0.00 0.329301E+09 58519200.59
July 0.208610E+10 0.164266E+10 0.664132E+09 0.00 0.00 0.00 0.00 0.282542E+09 58114708.01
August 0.217552E+10 0.171059E+10 0.683011E+09 0.00 0.00 0.00 0.00 0.197145E+09 76937079.77
September 0.205665E+10 0.161394E+10 0.648959E+09 0.00 0.00 0.00 0.00 0.150519E+09 0.144793E+09
October 0.208295E+10 0.164818E+10 0.666307E+09 0.00 0.00 0.00 0.00 54889252.48 0.399244E+09
November 0.200405E+10 0.159379E+10 0.644998E+09 0.00 0.00 0.00 0.00 5120390.04 0.642146E+09
December 0.208610E+10 0.164266E+10 0.664046E+09 0.00 0.00 0.00 0.00 422368.66 0.676208E+09
                   
Annual Sum or Average 0.249375E+11 0.196542E+11 0.790839E+10 0.00 0.00 0.00 0.00 0.128925E+10 0.432739E+10
Minimum of Months 0.190200E+10 0.149963E+10 0.604426E+09 0.00 0.00 0.00 0.00 0.00 58114708.01
Maximum of Months 0.217552E+10 0.171059E+10 0.683011E+09 0.00 0.00 0.00 0.00 0.329301E+09 0.699516E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.165769E+09 87431017.75 0.00 0.00 0.00 0.00 0.00 0.00 0.137255E+10
February 0.151369E+09 79550654.62 0.00 0.00 0.00 0.00 0.00 0.00 0.143568E+10
March 0.173136E+09 90741356.17 0.00 0.00 0.00 0.00 0.00 4430419.19 0.977214E+09
April 0.163676E+09 85614725.88 0.00 0.00 0.00 0.00 0.00 0.180441E+09 0.246928E+09
May 0.169453E+09 89086186.96 0.00 0.00 0.00 0.00 0.00 0.498148E+09 69532555.42
June 0.167108E+09 87562845.39 0.00 0.00 0.00 0.00 0.00 0.101819E+10 15700051.32
July 0.166020E+09 87138067.45 0.00 0.00 0.00 0.00 0.00 0.784222E+09 35204097.04
August 0.173136E+09 90741356.17 0.00 0.00 0.00 0.00 0.00 0.686896E+09 75607181.46
September 0.163676E+09 85614725.88 0.00 0.00 0.00 0.00 0.00 0.324202E+09 0.115880E+09
October 0.165769E+09 87431017.75 0.00 0.00 0.00 0.00 0.00 61706000.27 0.762592E+09
November 0.159490E+09 84545457.27 0.00 0.00 0.00 0.00 0.00 0.00 0.139186E+10
December 0.166020E+09 87138067.45 0.00 0.00 0.00 0.00 0.00 0.00 0.171925E+10
                   
Annual Sum or Average 0.198462E+10 0.104260E+10 0.00 0.00 0.00 0.00 0.00 0.355823E+10 0.821800E+10
Minimum of Months 0.151369E+09 79550654.62 0.00 0.00 0.00 0.00 0.00 0.00 15700051.32
Maximum of Months 0.173136E+09 90741356.17 0.00 0.00 0.00 0.00 0.00 0.101819E+10 0.171925E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 785.10 02-JAN-15:09 668.29 02-JAN-09:09 2751.42 02-JAN-09:09 0.00 0.00 0.00 0.00 99.11 31-JAN-13:55 2449.68 01-JAN-01:00
February 785.10 01-FEB-15:09 668.29 01-FEB-09:09 2751.42 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2865.48 02-FEB-23:00
March 785.10 01-MAR-15:09 668.29 01-MAR-09:09 2751.42 01-MAR-09:09 0.00 0.00 0.00 0.00 210.96 15-MAR-13:00 2590.84 28-MAR-04:00
April 785.10 01-APR-10:09 668.29 01-APR-09:09 2751.42 01-APR-09:09 0.00 0.00 0.00 0.00 1315.43 23-APR-18:03 1559.97 26-APR-21:00
May 785.10 01-MAY-14:09 668.29 01-MAY-08:09 2751.42 01-MAY-08:09 0.00 0.00 0.00 0.00 1682.72 07-MAY-18:03 1298.06 23-MAY-05:00
June 785.10 01-JUN-14:09 668.29 01-JUN-08:09 2751.42 01-JUN-08:09 0.00 0.00 0.00 0.00 2655.10 25-JUN-18:03 728.76 13-JUN-04:00
July 785.10 01-JUL-10:09 668.29 01-JUL-09:09 2751.42 01-JUL-09:09 0.00 0.00 0.00 0.00 2963.11 30-JUL-18:03 1220.58 26-JUL-24:00
August 785.10 01-AUG-14:09 668.29 01-AUG-08:09 2751.42 01-AUG-08:09 0.00 0.00 0.00 0.00 2721.15 13-AUG-18:02 927.25 07-AUG-01:00
September 785.10 01-SEP-14:09 668.29 01-SEP-08:09 2751.42 01-SEP-08:09 0.00 0.00 0.00 0.00 1295.47 06-SEP-20:03 1143.41 03-SEP-05:00
October 785.10 02-OCT-14:09 668.29 02-OCT-08:09 2751.42 02-OCT-08:09 0.00 0.00 0.00 0.00 817.12 01-OCT-19:00 2091.64 27-OCT-05:00
November 785.10 01-NOV-14:09 668.29 01-NOV-08:09 2751.42 01-NOV-08:09 0.00 0.00 0.00 0.00 162.35 19-NOV-15:00 2625.71 29-NOV-02:00
December 785.10 01-DEC-15:09 668.29 01-DEC-09:09 2751.42 01-DEC-09:09 0.00 0.00 0.00 0.00 58.48 21-DEC-14:20 2239.82 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 785.10   668.29   2751.42   0.00 0.00 0.00 0.00 0.00   728.76  
Maximum of Months 785.10   668.29   2751.42   0.00 0.00 0.00 0.00 2963.11   2865.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 24809.68 02-JAN-15:09 14651.93 02-JAN-17:30 4639.58 02-JAN-09:09 0.00 0.00 0.00 0.00 84.98 31-JAN-13:55 2521.03 01-JAN-01:00
February 24809.68 01-FEB-15:09 14651.93 01-FEB-17:00 4639.58 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3260.95 02-FEB-23:00
March 24809.68 01-MAR-15:09 14254.00 09-MAR-17:00 4639.58 01-MAR-09:09 0.00 0.00 0.00 0.00 180.89 15-MAR-13:00 2680.59 28-MAR-04:00
April 24809.68 01-APR-10:09 12252.53 22-APR-16:00 4639.58 01-APR-09:09 0.00 0.00 0.00 0.00 1129.15 23-APR-18:03 1483.35 26-APR-21:00
May 24809.68 01-MAY-14:09 11921.00 19-MAY-16:00 4639.58 01-MAY-08:09 0.00 0.00 0.00 0.00 1450.28 07-MAY-18:03 1184.98 23-MAY-05:00
June 24809.68 01-JUN-14:09 11996.72 07-JUN-16:00 4639.58 01-JUN-08:09 0.00 0.00 0.00 0.00 2295.85 25-JUN-18:03 618.11 13-JUN-04:00
July 24809.68 01-JUL-10:09 12818.15 08-JUL-16:00 4639.58 01-JUL-09:09 0.00 0.00 0.00 0.00 2561.66 30-JUL-18:03 1037.16 26-JUL-24:00
August 24809.68 01-AUG-14:09 12857.64 05-AUG-16:00 4639.58 01-AUG-08:09 0.00 0.00 0.00 0.00 2350.69 13-AUG-18:02 838.02 07-AUG-01:00
September 24809.68 01-SEP-14:09 13238.63 26-SEP-16:00 4639.58 01-SEP-08:09 0.00 0.00 0.00 0.00 1123.65 06-SEP-20:03 1010.09 03-SEP-05:00
October 24809.68 02-OCT-14:09 14285.10 31-OCT-16:00 4639.58 02-OCT-08:09 0.00 0.00 0.00 0.00 809.75 01-OCT-19:00 2183.44 27-OCT-05:00
November 24809.68 01-NOV-14:09 14651.93 06-NOV-17:30 4639.58 01-NOV-08:09 0.00 0.00 0.00 0.00 139.21 19-NOV-15:00 2715.63 29-NOV-02:00
December 24809.68 01-DEC-15:09 14651.93 01-DEC-16:30 4639.58 01-DEC-09:09 0.00 0.00 0.00 0.00 43.60 25-DEC-16:00 2238.44 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 24809.68   11921.00   4639.58   0.00 0.00 0.00 0.00 0.00   618.11  
Maximum of Months 24809.68   14651.93   4639.58   0.00 0.00 0.00 0.00 2561.66   3260.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1380.62 02-JAN-09:09 2912.71 02-JAN-09:09 0.00 0.00 0.00 0.00 45.20 31-JAN-13:55 1448.06 01-JAN-01:00
February 2337.76 01-FEB-15:09 1380.62 01-FEB-09:09 2912.71 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1734.04 02-FEB-23:00
March 2337.76 01-MAR-15:09 1380.62 01-MAR-09:09 2912.71 01-MAR-09:09 0.00 0.00 0.00 0.00 96.21 15-MAR-13:00 1351.30 28-MAR-04:00
April 2337.76 01-APR-10:09 1380.62 01-APR-09:09 2912.71 01-APR-09:09 0.00 0.00 0.00 0.00 579.98 23-APR-18:03 812.40 26-APR-21:00
May 2337.76 01-MAY-14:09 1380.62 01-MAY-08:09 2912.71 01-MAY-08:09 0.00 0.00 0.00 0.00 753.59 07-MAY-18:03 617.83 23-MAY-05:00
June 2337.76 01-JUN-14:09 1380.62 01-JUN-08:09 2912.71 01-JUN-08:09 0.00 0.00 0.00 0.00 1199.21 25-JUN-18:03 351.49 13-JUN-04:00
July 2337.76 01-JUL-10:09 1380.62 01-JUL-09:09 2912.71 01-JUL-09:09 0.00 0.00 0.00 0.00 1333.35 30-JUL-18:03 608.67 26-JUL-24:00
August 2337.76 01-AUG-14:09 1380.62 01-AUG-08:09 2912.71 01-AUG-08:09 0.00 0.00 0.00 0.00 1226.41 13-AUG-18:02 493.71 07-AUG-01:00
September 2337.76 01-SEP-14:09 1380.62 01-SEP-08:09 2912.71 01-SEP-08:09 0.00 0.00 0.00 0.00 565.01 06-SEP-20:03 594.06 03-SEP-05:00
October 2337.76 02-OCT-14:09 1380.62 02-OCT-08:09 2912.71 02-OCT-08:09 0.00 0.00 0.00 0.00 295.50 01-OCT-18:25 1159.87 27-OCT-05:00
November 2337.76 01-NOV-14:09 1380.62 01-NOV-08:09 2912.71 01-NOV-08:09 0.00 0.00 0.00 0.00 74.04 19-NOV-15:00 1489.03 29-NOV-02:00
December 2337.76 01-DEC-15:09 1380.62 01-DEC-09:09 2912.71 01-DEC-09:09 0.00 0.00 0.00 0.00 23.19 25-DEC-16:00 1204.35 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1380.62   2912.71   0.00 0.00 0.00 0.00 0.00   351.49  
Maximum of Months 2337.76   1380.62   2912.71   0.00 0.00 0.00 0.00 1333.35   1734.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2337.76 02-JAN-15:09 1380.62 02-JAN-09:09 437.18 02-JAN-09:09 0.00 0.00 0.00 0.00 45.20 31-JAN-13:55 1377.84 01-JAN-01:00
February 2337.76 01-FEB-15:09 1380.62 01-FEB-09:09 437.18 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1634.50 02-FEB-23:00
March 2337.76 01-MAR-15:09 1380.62 01-MAR-09:09 437.18 01-MAR-09:09 0.00 0.00 0.00 0.00 96.21 15-MAR-13:00 1287.31 28-MAR-04:00
April 2337.76 01-APR-10:09 1380.62 01-APR-09:09 437.18 01-APR-09:09 0.00 0.00 0.00 0.00 585.46 23-APR-18:03 754.22 26-APR-21:00
May 2337.76 01-MAY-14:09 1380.62 01-MAY-08:09 437.18 01-MAY-08:09 0.00 0.00 0.00 0.00 758.24 07-MAY-18:03 573.75 23-MAY-05:00
June 2337.76 01-JUN-14:09 1380.62 01-JUN-08:09 437.18 01-JUN-08:09 0.00 0.00 0.00 0.00 1203.67 25-JUN-18:03 309.59 13-JUN-04:00
July 2337.76 01-JUL-10:09 1380.62 01-JUL-09:09 437.18 01-JUL-09:09 0.00 0.00 0.00 0.00 1338.28 30-JUL-18:03 538.76 26-JUL-24:00
August 2337.76 01-AUG-14:09 1380.62 01-AUG-08:09 437.18 01-AUG-08:09 0.00 0.00 0.00 0.00 1229.98 13-AUG-18:02 427.02 07-AUG-01:00
September 2337.76 01-SEP-14:09 1380.62 01-SEP-08:09 437.18 01-SEP-08:09 0.00 0.00 0.00 0.00 573.23 06-SEP-20:03 542.28 03-SEP-05:00
October 2337.76 02-OCT-14:09 1380.62 02-OCT-08:09 437.18 02-OCT-08:09 0.00 0.00 0.00 0.00 307.89 01-OCT-18:25 1088.42 27-OCT-05:00
November 2337.76 01-NOV-14:09 1380.62 01-NOV-08:09 437.18 01-NOV-08:09 0.00 0.00 0.00 0.00 74.04 19-NOV-15:00 1421.98 29-NOV-02:00
December 2337.76 01-DEC-15:09 1380.62 01-DEC-09:09 437.18 01-DEC-09:09 0.00 0.00 0.00 0.00 23.19 25-DEC-16:00 1158.33 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2337.76   1380.62   437.18   0.00 0.00 0.00 0.00 0.00   309.59  
Maximum of Months 2337.76   1380.62   437.18   0.00 0.00 0.00 0.00 1338.28   1634.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 186.05 02-JAN-15:09 73.24 02-JAN-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 4914.80 21-JAN-12:01
February 186.05 01-FEB-15:09 73.24 01-FEB-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6079.27 01-FEB-12:01
March 186.05 01-MAR-15:09 73.24 01-MAR-09:09 0.00 0.00 0.00 0.00 0.00 882.80 14-MAR-13:53 4450.85 25-MAR-11:01
April 186.05 01-APR-10:09 73.24 01-APR-09:09 0.00 0.00 0.00 0.00 0.00 1076.81 30-APR-11:02 2406.99 07-APR-07:01
May 186.05 01-MAY-14:09 73.24 01-MAY-08:09 0.00 0.00 0.00 0.00 0.00 1914.82 14-MAY-11:02 1792.42 01-MAY-07:01
June 186.05 01-JUN-14:09 73.24 01-JUN-08:09 0.00 0.00 0.00 0.00 0.00 3649.92 28-JUN-11:01 583.99 13-JUN-07:03
July 186.05 01-JUL-10:09 73.24 01-JUL-09:09 0.00 0.00 0.00 0.00 0.00 3220.17 12-JUL-11:01 1273.34 28-JUL-15:53
August 186.05 01-AUG-14:09 73.24 01-AUG-08:09 0.00 0.00 0.00 0.00 0.00 4411.57 25-AUG-11:01 2625.82 05-AUG-16:52
September 186.05 01-SEP-14:09 73.24 01-SEP-08:09 0.00 0.00 0.00 0.00 0.00 1434.05 17-SEP-11:02 1531.48 15-SEP-07:01
October 186.05 02-OCT-14:09 73.24 02-OCT-08:09 0.00 0.00 0.00 0.00 0.00 1754.32 01-OCT-11:02 5599.84 25-OCT-11:01
November 186.05 01-NOV-14:09 73.24 01-NOV-08:09 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7041.59 23-NOV-12:01
December 186.05 01-DEC-15:09 73.24 01-DEC-09:09 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5933.92 04-DEC-12:01
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 186.05   73.24   0.00 0.00 0.00 0.00 0.00 0.00   583.99  
Maximum of Months 186.05   73.24   0.00 0.00 0.00 0.00 0.00 4411.57   7041.59  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3319.25 04-JAN-07:05 392.55 594.02 4891.41 0.00 0.00 0.00 0.00 0.00 311.22
February 3617.76 28-FEB-07:07 294.41 445.51 3668.56 0.00 0.00 0.00 0.00 0.00 405.45
March 4475.57 27-MAR-06:05 392.55 594.02 4891.41 0.00 0.00 0.00 0.00 0.00 604.64
April 43287.80 13-APR-06:02 490.69 742.52 6114.26 0.00 0.00 0.00 0.00 0.00 155.19
May 45041.83 13-MAY-06:02 490.69 371.30 4585.70 0.00 0.00 0.00 0.00 0.00 191.60
June 39637.88 20-JUN-05:02 0.00 222.73 3630.52 0.00 0.00 0.00 0.00 0.00 59.96
July 42468.10 01-JUL-05:02 0.00 222.73 2722.89 0.00 0.00 0.00 0.00 0.00 106.09
August 39149.91 24-AUG-06:02 490.69 742.52 6114.26 0.00 0.00 0.00 0.00 0.00 114.98
September 38359.46 16-SEP-06:02 490.69 371.30 4585.70 0.00 0.00 0.00 0.00 0.00 155.35
October 39752.44 17-OCT-06:02 490.69 742.52 6114.26 0.00 0.00 0.00 0.00 0.00 262.02
November 25783.47 03-NOV-06:02 490.69 742.52 6114.26 0.00 0.00 0.00 0.00 0.00 130.79
December 5163.78 05-DEC-07:05 392.55 594.02 4891.41 0.00 0.00 0.00 0.00 0.00 156.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3319.25   0.00 222.73 2722.89 0.00 0.00 0.00 0.00 0.00 59.96
Maximum of Months 45041.83   490.69 742.52 6114.26 0.00 0.00 0.00 0.00 0.00 604.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 101127.44 08-JAN-09:02 15506.05 6302.31 7732.63 0.00 0.00 0.00 0.00 0.00 190.45
February 24360.15 01-FEB-15:20 24809.68 11981.08 4639.58 0.00 0.00 0.00 0.00 0.00 100.91
March 139043.09 17-MAR-06:03 12404.84 13023.94 8248.14 0.00 0.00 0.00 0.00 0.00 281.20
April 209181.76 07-APR-06:02 15506.05 15944.85 10310.18 0.00 0.00 0.00 0.00 0.00 300.84
May 202693.22 01-MAY-06:02 15506.05 15508.56 10310.18 0.00 0.00 0.00 0.00 0.00 209.41
June 170226.30 21-JUN-06:02 15506.05 15401.30 10310.18 0.00 0.00 0.00 0.00 0.00 112.48
July 180453.64 01-JUL-05:02 0.00 4883.98 4591.48 0.00 0.00 0.00 0.00 0.00 85.09
August 169142.14 24-AUG-06:02 15506.05 15904.18 10310.18 0.00 0.00 0.00 0.00 0.00 97.67
September 163981.20 16-SEP-06:02 15506.05 8139.96 7732.63 0.00 0.00 0.00 0.00 0.00 132.98
October 197870.64 19-OCT-06:02 15506.05 16279.92 10310.18 0.00 0.00 0.00 0.00 0.00 218.02
November 164450.24 02-NOV-06:02 15506.05 16279.92 10310.18 0.00 0.00 0.00 0.00 0.00 151.87
December 22348.51 01-DEC-15:30 24809.68 12118.54 4639.58 0.00 0.00 0.00 0.00 0.00 6.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22348.51   0.00 4883.98 4591.48 0.00 0.00 0.00 0.00 0.00 6.49
Maximum of Months 209181.76   24809.68 16279.92 10310.18 0.00 0.00 0.00 0.00 0.00 300.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 25252.90 08-JAN-09:02 1461.10 767.01 4854.52 0.00 0.00 0.00 0.00 0.00 103.64
February 7702.82 01-FEB-15:30 2337.76 1380.62 2912.71 0.00 0.00 0.00 0.00 0.00 55.69
March 16640.37 17-MAR-06:03 1168.88 1227.22 5178.15 0.00 0.00 0.00 0.00 0.00 150.21
April 26620.46 14-APR-06:02 1461.10 1534.02 6472.69 0.00 0.00 0.00 0.00 0.00 74.16
May 26567.31 18-MAY-06:02 1461.10 1534.02 6472.69 0.00 0.00 0.00 0.00 0.00 74.21
June 27128.87 20-JUN-05:02 0.00 460.21 3843.35 0.00 0.00 0.00 0.00 0.00 26.38
July 29021.41 01-JUL-05:02 0.00 460.21 2882.52 0.00 0.00 0.00 0.00 0.00 46.68
August 26437.73 24-AUG-06:02 1461.10 1534.02 6472.69 0.00 0.00 0.00 0.00 0.00 47.04
September 26897.35 29-SEP-05:02 0.00 460.21 3843.35 0.00 0.00 0.00 0.00 0.00 71.04
October 27030.47 05-OCT-05:02 0.00 460.21 3843.35 0.00 0.00 0.00 0.00 0.00 64.96
November 26364.40 02-NOV-06:02 1461.10 1534.02 6472.69 0.00 0.00 0.00 0.00 0.00 76.97
December 9298.54 22-DEC-15:50 2337.76 1380.62 2912.71 0.00 0.00 0.00 0.00 1.89 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7702.82   0.00 460.21 2882.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29021.41   2337.76 1534.02 6472.69 0.00 0.00 0.00 0.00 1.89 150.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17854.14 08-JAN-09:02 1461.10 767.01 728.63 0.00 0.00 0.00 0.00 0.00 102.24
February 5559.10 01-FEB-15:30 2337.76 1380.62 437.18 0.00 0.00 0.00 0.00 0.00 55.69
March 6233.59 18-MAR-14:50 2337.76 1380.62 437.18 0.00 0.00 0.00 0.00 24.10 0.00
April 25202.74 13-APR-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 67.96
May 24492.86 16-MAY-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 101.30
June 22828.05 21-JUN-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 55.37
July 23783.38 01-JUL-05:02 0.00 460.21 432.65 0.00 0.00 0.00 0.00 0.00 44.20
August 22744.55 24-AUG-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 48.42
September 22588.66 29-SEP-05:02 0.00 460.21 576.86 0.00 0.00 0.00 0.00 0.00 64.44
October 25771.00 19-OCT-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 111.34
November 22615.23 02-NOV-06:02 1461.10 1534.02 971.51 0.00 0.00 0.00 0.00 0.00 78.48
December 7073.55 22-DEC-15:50 2337.76 1380.62 437.18 0.00 0.00 0.00 0.00 1.89 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5559.10   0.00 460.21 432.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25771.00   2337.76 1534.02 971.51 0.00 0.00 0.00 0.00 24.10 111.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 105.22
February 0.00 01-FEB-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 67.28
March 0.00 01-MAR-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 52.19
April 0.00 01-APR-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 46.37
May 0.00 01-MAY-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 32.51
June 0.00 01-JUN-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 7.40
July 0.00 01-JUL-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 13.17
August 0.00 01-AUG-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 1.79
September 0.00 01-SEP-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 9.95
October 0.00 01-OCT-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 16.73
November 0.00 01-NOV-00:10 0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 34.73
December 116.02 08-DEC-20:01 627.91 366.19 0.00 0.00 0.00 0.00 0.00 0.00 6.33
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 4.07 0.00 0.00 0.00 0.00 0.00 0.00 1.79
Maximum of Months 116.02   627.91 366.19 0.00 0.00 0.00 0.00 0.00 0.00 105.22



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.572159E+11 52824.80 31-JAN-16:00 0.925027E+10 83709.11 02-JAN-07:10
February 0.462242E+11 40513.19 22-FEB-15:00 0.833328E+10 25837.08 13-FEB-07:10
March 0.554588E+11 53119.45 18-MAR-15:00 0.859878E+10 33442.09 27-MAR-06:40
April 0.707960E+11 66005.88 14-APR-15:00 0.722952E+10 4891.34 03-APR-11:00
May 0.808420E+11 70129.28 31-MAY-15:00 0.727555E+10 4845.83 01-MAY-11:30
June 0.955044E+11 89854.22 28-JUN-14:00 0.690460E+10 4799.44 01-JUN-11:30
July 0.945158E+11 80534.04 20-JUL-14:00 0.700650E+10 4769.99 03-JUL-11:00
August 0.958467E+11 87790.49 26-AUG-15:00 0.708474E+10 4782.08 31-AUG-11:30
September 0.854519E+11 75991.97 08-SEP-14:00 0.694484E+10 4817.65 29-SEP-11:50
October 0.699854E+11 69102.21 06-OCT-15:30 0.733990E+10 5574.55 25-OCT-07:10
November 0.559384E+11 57698.67 01-NOV-14:00 0.747792E+10 14682.93 24-NOV-07:10
December 0.537857E+11 47759.35 22-DEC-17:19 0.108075E+11 48953.89 07-DEC-07:10
             
Annual Sum or Average 0.861565E+12     0.942534E+11    
Minimum of Months 0.462242E+11 40513.19   0.690460E+10 4769.99  
Maximum of Months 0.958467E+11 89854.22   0.108075E+11 83709.11  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.190052E+11 0.442058E+10 0.163682E+11 0.00 0.118176E+11 0.00 0.00 0.560425E+10 0.00 0.00 0.00 0.00 0.00
February 0.164585E+11 0.373100E+10 0.148500E+11 0.00 0.107235E+11 0.00 0.00 0.461126E+09 0.00 0.00 0.00 0.00 0.00
March 0.173860E+11 0.374021E+10 0.167807E+11 0.00 0.120134E+11 0.00 0.00 0.553852E+10 0.00 0.00 0.00 0.00 0.00
April 0.158790E+11 0.321994E+10 0.159483E+11 0.00 0.115507E+11 0.00 0.00 0.241980E+11 0.00 0.00 0.00 0.00 0.00
May 0.165487E+11 0.298349E+10 0.165744E+11 0.00 0.119729E+11 0.00 0.00 0.327624E+11 0.00 0.00 0.00 0.00 0.00
June 0.166577E+11 0.274390E+10 0.162038E+11 0.00 0.127788E+11 0.00 0.00 0.471202E+11 0.00 0.00 0.00 0.00 0.00
July 0.161230E+11 0.288918E+10 0.163169E+11 0.00 0.125929E+11 0.00 0.00 0.465939E+11 0.00 0.00 0.00 0.00 0.00
August 0.172011E+11 0.317211E+10 0.167807E+11 0.00 0.128038E+11 0.00 0.00 0.458890E+11 0.00 0.00 0.00 0.00 0.00
September 0.158471E+11 0.344224E+10 0.159441E+11 0.00 0.118710E+11 0.00 0.00 0.383475E+11 0.00 0.00 0.00 0.00 0.00
October 0.178845E+11 0.397373E+10 0.163703E+11 0.00 0.118749E+11 0.00 0.00 0.198820E+11 0.00 0.00 0.00 0.00 0.00
November 0.180314E+11 0.419446E+10 0.158468E+11 0.00 0.113695E+11 0.00 0.00 0.649628E+10 0.00 0.00 0.00 0.00 0.00
December 0.187644E+11 0.453060E+10 0.163148E+11 0.00 0.118833E+11 0.00 0.00 0.229275E+10 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.205787E+12 0.430415E+11 0.194299E+12 0.00 0.143252E+12 0.00 0.00 0.275186E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158471E+11 0.274390E+10 0.148500E+11 0.00 0.107235E+11 0.00 0.00 0.461126E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.190052E+11 0.453060E+10 0.167807E+11 0.00 0.128038E+11 0.00 0.00 0.471202E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.147135E+10 0.00 0.777892E+10 0.00 0.00
February 0.00 0.00 0.130231E+10 0.00 0.703097E+10 0.00 0.00
March 0.00 0.00 0.885903E+09 0.00 0.771288E+10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.722952E+10 0.00 0.00
May 0.00 0.00 0.00 0.00 0.727555E+10 0.00 0.00
June 0.00 0.00 0.00 0.00 0.690460E+10 0.00 0.00
July 0.00 0.00 0.00 0.00 0.700650E+10 0.00 0.00
August 0.00 0.00 0.00 0.00 0.708474E+10 0.00 0.00
September 0.00 0.00 0.00 0.00 0.694484E+10 0.00 0.00
October 0.00 0.00 1252098.96 0.00 0.733865E+10 0.00 0.00
November 0.00 0.00 0.187181E+09 0.00 0.729074E+10 0.00 0.00
December 0.00 0.00 0.309109E+10 0.00 0.771639E+10 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.693909E+10 0.00 0.873143E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.690460E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.309109E+10 0.00 0.777892E+10 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 18154.70 02-JAN-17:30 3742.41 01-JAN-06:10 10740.89 02-JAN-09:09 0.00 9701.20 01-JAN-09:09 0.00 0.00 01-JAN-00:10
February 18154.70 01-FEB-17:00 3742.41 01-FEB-06:10 10740.89 01-FEB-09:09 0.00 7876.50 13-FEB-07:40 0.00 0.00 01-FEB-00:10
March 17756.76 09-MAR-17:00 3742.41 01-MAR-06:10 10740.89 01-MAR-09:09 0.00 8394.62 17-MAR-06:10 0.00 0.00 01-MAR-00:10
April 15755.30 22-APR-16:00 3742.41 01-APR-05:10 10740.89 01-APR-09:09 0.00 9559.55 15-APR-06:10 0.00 0.00 01-APR-00:10
May 15423.77 19-MAY-16:00 3742.41 01-MAY-05:10 10740.89 01-MAY-08:09 0.00 10185.56 21-MAY-08:09 0.00 0.00 01-MAY-00:10
June 15499.49 07-JUN-16:00 3742.41 01-JUN-05:10 10740.89 01-JUN-08:09 0.00 12168.91 28-JUN-14:00 0.00 0.00 01-JUN-00:10
July 16320.92 08-JUL-16:00 3742.41 01-JUL-05:10 10740.89 01-JUL-09:09 0.00 12308.97 14-JUL-06:10 0.00 0.00 01-JUL-00:10
August 16360.41 05-AUG-16:00 3742.41 01-AUG-05:10 10740.89 01-AUG-08:09 0.00 11927.01 01-AUG-06:10 0.00 0.00 01-AUG-00:10
September 16741.40 26-SEP-16:00 3742.41 01-SEP-05:10 10740.89 01-SEP-08:09 0.00 11676.72 04-SEP-08:09 0.00 0.00 01-SEP-00:10
October 17787.87 31-OCT-16:00 3742.41 01-OCT-05:10 10740.89 02-OCT-08:09 0.00 11517.83 03-OCT-06:10 0.00 0.00 01-OCT-00:10
November 18154.70 06-NOV-17:30 3742.41 01-NOV-05:10 10740.89 01-NOV-08:09 0.00 9409.47 03-NOV-06:10 0.00 0.00 01-NOV-00:10
December 18154.70 01-DEC-16:30 3742.41 01-DEC-06:10 10740.89 01-DEC-09:09 0.00 8557.35 07-DEC-07:10 0.00 0.00 01-DEC-00:10
                         
Annual Sum or Average             0.00     0.00    
Minimum of Months 15423.77   3742.41   10740.89   0.00 7876.50   0.00 0.00  
Maximum of Months 18154.70   3742.41   10740.89   0.00 12308.97   0.00 0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 18706.84 31-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 7023.27 18-FEB-14:39 0.00 0.00 0.00 0.00 0.00
March 19591.02 18-MAR-15:30 0.00 0.00 0.00 0.00 0.00
April 33995.72 14-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 36995.34 19-MAY-14:09 0.00 0.00 0.00 0.00 0.00
June 53763.25 28-JUN-14:00 0.00 0.00 0.00 0.00 0.00
July 46824.99 19-JUL-13:30 0.00 0.00 0.00 0.00 0.00
August 50797.95 26-AUG-14:00 0.00 0.00 0.00 0.00 0.00
September 42530.06 08-SEP-14:00 0.00 0.00 0.00 0.00 0.00
October 35923.02 02-OCT-14:09 0.00 0.00 0.00 0.00 0.00
November 23925.97 01-NOV-14:00 0.00 0.00 0.00 0.00 0.00
December 13470.15 22-DEC-15:09 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7023.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 53763.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 52824.80 31-JAN-16:00 16870.30 10740.89 0.00 0.00 7353.50 0.00 0.00 17860.11 0.00
February 40513.19 22-FEB-15:00 15990.76 10740.89 0.00 0.00 7353.50 0.00 0.00 6428.04 0.00
March 53119.45 18-MAR-15:00 15592.43 10740.89 0.00 0.00 7353.50 0.00 0.00 19432.64 0.00
April 66005.88 14-APR-15:00 14789.41 10740.89 0.00 0.00 7462.72 0.00 0.00 33012.86 0.00
May 70129.28 31-MAY-15:00 14308.13 10740.89 0.00 0.00 8300.44 0.00 0.00 36779.82 0.00
June 89854.22 28-JUN-14:00 13181.17 10740.89 0.00 0.00 12168.91 0.00 0.00 53763.25 0.00
July 80534.04 20-JUL-14:00 13613.45 10740.89 0.00 0.00 10237.96 0.00 0.00 45941.75 0.00
August 87790.49 26-AUG-15:00 14967.30 10740.89 0.00 0.00 11497.72 0.00 0.00 50584.58 0.00
September 75991.97 08-SEP-14:00 13278.98 10740.89 0.00 0.00 9442.04 0.00 0.00 42530.06 0.00
October 69102.21 06-OCT-15:30 15825.33 10740.89 0.00 0.00 7912.91 0.00 0.00 34623.07 0.00
November 57698.67 01-NOV-14:00 15515.31 10740.89 0.00 0.00 7516.51 0.00 0.00 23925.97 0.00
December 47759.35 22-DEC-17:19 18154.70 10740.89 3742.41 0.00 7353.50 0.00 0.00 7767.86 0.00
                       
Annual Sum or Average           0.00   0.00     0.00
Minimum of Months 40513.19   13181.17 10740.89 0.00 0.00 7353.50 0.00 0.00 6428.04 0.00
Maximum of Months 89854.22   18154.70 10740.89 3742.41 0.00 12168.91 0.00 0.00 53763.25 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 81403.68 01-JAN-09:09 0.00 4956.95 23-JAN-12:39 0.00
February 0.00 0.00 23975.08 13-FEB-07:10 0.00 4956.86 03-FEB-12:00 0.00
March 0.00 0.00 31580.09 27-MAR-06:40 0.00 4937.45 01-MAR-12:50 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 4891.34 03-APR-11:00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 4845.83 01-MAY-11:30 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 4799.44 01-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 4769.99 03-JUL-11:00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 4782.08 31-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 4817.65 29-SEP-11:50 0.00
October 0.00 0.00 1002.04 25-OCT-07:10 0.00 4868.36 31-OCT-11:50 0.00
November 0.00 0.00 12820.93 24-NOV-07:10 0.00 4915.49 30-NOV-12:50 0.00
December 0.00 0.00 47091.89 07-DEC-07:10 0.00 4947.93 29-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 4769.99   0.00
Maximum of Months 0.00 0.00 81403.68   0.00 4956.95   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 28.43 0.00 28.43
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 28.42 0.00 28.42
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 28.43 0.00 28.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 28.43 0.00 28.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 14.82 4.83 14.82 0.00 14.82 0.00 14.82
February 38.50 14.68 36.17 14.67 0.00 14.67 0.00 14.67
March 13.50 14.90 12.83 14.89 0.00 14.89 0.00 14.89
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.67 15.28 0.67 15.28 0.00 15.28 0.00 15.28
November 11.83 14.68 10.83 14.69 0.00 14.69 0.00 14.69
December 30.83 14.72 30.50 14.71 0.00 14.71 0.00 14.71
                 
Annual Sum or Average 100.17 14.73 95.83 14.73 0.00 14.73 0.00 14.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38.50 15.28 36.17 15.28 0.00 15.28 0.00 15.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.00 22.58 49.67 22.42 49.67 22.29
February 376.00 21.67 32.83 21.62 32.83 21.58
March 421.33 22.65 39.50 22.52 39.50 22.42
April 292.17 23.86 1.83 23.86 0.00 23.86
May 192.17 23.89 0.00 23.89 0.00 23.89
June 1.00 23.89 96.67 24.17 0.00 24.17
July 6.17 23.95 329.00 23.99 6.17 23.99
August 8.17 24.05 365.17 23.98 8.17 23.98
September 12.50 23.95 314.17 23.99 12.50 23.99
October 248.00 23.60 70.67 23.69 0.33 23.69
November 358.83 23.07 51.67 23.01 50.00 22.97
December 415.00 21.86 190.50 21.62 190.50 21.50
             
Annual Sum or Average 2745.33 22.75 1541.67 22.98 389.67 22.85
Minimum of Months 1.00 21.67 0.00 21.62 0.00 21.50
Maximum of Months 421.33 24.05 365.17 24.17 190.50 24.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 379.33 23.55 12.33 23.50 11.17 23.45
February 325.33 23.25 0.00 23.25 0.00 23.25
March 267.33 23.51 10.33 23.53 0.00 23.53
April 65.50 23.86 53.17 23.97 0.00 23.97
May 25.17 23.88 40.33 24.14 0.00 24.14
June 0.00 0.00 284.83 24.00 0.00 24.00
July 5.33 24.06 367.67 23.98 5.33 23.98
August 9.00 24.07 398.50 23.98 9.00 23.98
September 11.83 23.94 377.17 23.97 11.83 23.97
October 113.00 23.77 128.00 23.89 0.00 23.89
November 249.67 23.68 67.83 23.73 30.83 23.75
December 415.00 23.20 10.50 23.15 10.50 23.10
             
Annual Sum or Average 1866.50 23.47 1750.67 23.71 78.67 23.70
Minimum of Months 0.00 0.00 0.00 23.15 0.00 23.10
Maximum of Months 415.00 24.07 398.50 24.14 30.83 24.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 97.67 23.62 94.67 23.79 3.83 23.78
February 169.50 23.38 33.83 23.49 0.00 23.49
March 190.33 23.49 49.33 23.58 2.17 23.56
April 48.50 23.86 147.67 24.00 0.00 24.00
May 28.33 23.86 115.17 24.08 0.00 24.08
June 0.00 0.00 334.67 23.99 0.00 23.99
July 5.00 23.93 387.50 23.98 5.00 23.98
August 8.33 24.09 411.50 23.98 8.33 23.98
September 9.17 23.97 400.50 23.97 9.17 23.97
October 35.83 23.76 257.33 23.96 0.17 23.96
November 88.67 23.84 163.33 23.93 28.83 23.94
December 223.67 23.59 30.00 23.58 4.83 23.54
             
Annual Sum or Average 905.00 23.60 2425.50 23.88 62.33 23.88
Minimum of Months 0.00 0.00 30.00 23.49 0.00 23.49
Maximum of Months 223.67 24.09 411.50 24.08 28.83 24.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 140.67 23.31 40.00 23.40 5.83 23.38
February 253.17 22.82 4.67 22.84 0.17 22.84
March 269.00 23.22 35.50 23.25 7.00 23.20
April 77.50 23.80 100.00 23.93 0.00 23.93
May 55.67 23.85 52.00 24.03 0.00 24.03
June 2.17 23.89 286.00 24.00 0.00 24.00
July 7.33 23.92 380.00 23.98 7.33 23.98
August 10.50 24.05 405.50 23.98 10.50 23.98
September 12.00 23.97 394.00 23.97 12.00 23.97
October 59.00 23.56 221.33 23.90 0.33 23.90
November 133.50 23.60 133.17 23.76 30.67 23.76
December 276.00 23.27 17.33 23.21 10.50 23.14
             
Annual Sum or Average 1296.50 23.30 2069.50 23.70 84.33 23.69
Minimum of Months 2.17 22.82 4.67 22.84 0.00 22.84
Maximum of Months 276.00 24.05 405.50 24.03 30.67 24.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 303.17 20.65 122.67 20.87 69.50 20.55
February 376.00 18.00 249.17 17.57 249.17 17.38
March 342.67 19.98 210.83 20.15 151.17 19.72
April 262.17 28.26 295.50 28.69 191.00 29.13
May 287.50 31.16 370.33 30.70 273.17 30.95
June 369.00 33.92 407.33 33.59 369.00 33.69
July 405.83 32.41 415.00 32.35 405.83 32.37
August 403.00 32.25 421.50 32.11 403.00 32.16
September 366.67 31.16 404.33 30.90 366.67 30.98
October 293.00 26.04 276.50 26.77 190.50 27.19
November 303.67 20.54 174.17 20.96 112.67 20.71
December 372.83 18.81 247.83 18.46 228.00 18.15
             
Annual Sum or Average 4085.50 26.24 3595.17 26.93 3009.67 27.24
Minimum of Months 262.17 18.00 122.67 17.57 69.50 17.38
Maximum of Months 405.83 33.92 421.50 33.59 405.83 33.69



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 22.57606 22.74398 -0.2355 7.27341
February 376.00000 21.67147 38.08163 -0.3448 8.01886
March 422.00000 22.65789 27.88466 -0.1638 6.94377
April 405.00000 23.92144 16.77083 0.18854 5.98306
May 418.00000 23.96581 15.23279 -0.6347 13.58326
June 408.00000 23.97136 22.94382 -0.4594 9.56844
July 415.00000 23.97310 39.44109 -0.3521 7.80367
August 422.00000 23.97015 42.25759 -0.3560 7.81281
September 405.00000 23.97005 41.96055 -0.3908 8.34889
October 414.00000 23.75614 26.14945 0.19786 6.74585
November 399.00000 23.15691 27.15439 -0.0249 6.63045
December 415.00000 21.85650 16.62702 -0.4446 10.28871
           
Annual Sum or Average 4913.00000 23.29738 28.04357 -0.2524 8.26102
Minimum of Months 376.00000 21.67147 15.23279 -0.6347 5.98306
Maximum of Months 422.00000 23.97310 42.25759 0.19786 13.58326



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.57502 24.60318 0.11356 6.02613
February 376.00000 23.33743 38.44689 0.12924 5.90878
March 422.00000 23.67294 29.48802 0.18842 6.34375
April 405.00000 23.96103 21.63393 0.32522 7.35546
May 418.00000 23.96797 20.39968 -0.5007 10.39452
June 408.00000 23.97093 28.27275 -0.3720 8.05663
July 415.00000 23.97218 43.55431 -0.2862 6.91578
August 422.00000 23.96964 46.06312 -0.2826 6.83279
September 405.00000 23.96936 45.68027 -0.3217 7.31741
October 414.00000 23.91637 29.73630 0.33525 7.75138
November 399.00000 23.77372 29.30382 0.22955 6.69406
December 415.00000 23.19931 19.94083 -0.0311 6.02307
           
Annual Sum or Average 4913.00000 23.77649 31.38662 -0.0417 7.14455
Minimum of Months 376.00000 23.19931 19.94083 -0.5007 5.90878
Maximum of Months 422.00000 23.97218 46.06312 0.33525 10.39452



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.89420 22.15794 0.31728 7.58138
February 376.00000 23.69725 34.96346 0.24291 6.83188
March 422.00000 23.76511 27.57407 0.23522 6.99224
April 405.00000 23.96471 20.71402 0.37700 8.21353
May 418.00000 23.96637 19.65615 -0.4627 9.71614
June 408.00000 23.97124 27.51381 -0.3131 7.28869
July 415.00000 23.97333 41.44573 -0.2128 6.18816
August 422.00000 23.97166 43.73491 -0.1826 5.91288
September 405.00000 23.97215 43.26994 -0.1773 5.86844
October 414.00000 23.95720 28.06407 0.45750 9.90970
November 399.00000 23.94115 26.98048 0.37815 8.43443
December 415.00000 23.76705 16.28921 0.19704 6.65208
           
Annual Sum or Average 4913.00000 23.90453 29.33262 0.06886 7.46762
Minimum of Months 376.00000 23.69725 16.28921 -0.4627 5.86844
Maximum of Months 422.00000 23.97333 43.73491 0.45750 9.90970



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 23.73711 22.86150 0.24990 7.05764
February 376.00000 23.17487 37.32005 0.11065 6.46604
March 422.00000 23.48869 28.92588 0.14630 6.70314
April 405.00000 23.95031 20.88918 0.33915 7.68630
May 418.00000 23.96300 19.70901 -0.5125 10.75469
June 408.00000 23.97110 27.57544 -0.3582 7.93288
July 415.00000 23.97300 42.50973 -0.2486 6.54550
August 422.00000 23.97113 44.86060 -0.2189 6.22587
September 405.00000 23.97173 44.24366 -0.2167 6.20225
October 414.00000 23.91394 28.55514 0.41728 9.31309
November 399.00000 23.83529 27.85668 0.32279 7.80885
December 415.00000 23.49537 17.49157 0.11084 6.54981
           
Annual Sum or Average 4913.00000 23.79079 30.19337 0.00977 7.44392
Minimum of Months 376.00000 23.17487 17.49157 -0.5125 6.20225
Maximum of Months 422.00000 23.97300 44.86060 0.41728 10.75469



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 414.00000 21.67578 23.97677 -0.1019 10.65532
February 376.00000 17.99780 46.83181 -0.8140 21.81739
March 422.00000 21.05072 30.04446 -0.3032 15.34216
April 405.00000 27.50631 13.22653 0.89884 29.47273
May 418.00000 29.66907 10.28846 0.80094 30.61601
June 408.00000 33.27168 13.01173 1.85864 62.61896
July 415.00000 32.29318 28.98553 1.78307 60.65840
August 422.00000 31.96923 31.37648 1.74688 59.06359
September 405.00000 30.64537 32.62773 1.43043 49.67329
October 414.00000 25.74833 23.38274 0.72550 30.01291
November 399.00000 21.57530 29.88863 -0.0760 12.87084
December 415.00000 19.38164 18.47516 -0.6131 19.90358
           
Annual Sum or Average 4913.00000 26.12593 25.02286 0.62142 33.66743
Minimum of Months 376.00000 17.99780 10.28846 -0.8140 10.65532
Maximum of Months 422.00000 33.27168 46.83181 1.85864 62.61896



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.188342E+09 56391044.23 44.00 0.188342E+09 0.00 0.00 0.25 31-JAN-17:00 0.00 01-JAN-00:10 3140.06 31-JAN-17:00 3140.06 31-JAN-17:00 0.00 31-JAN-15:30 978.80 31-JAN-17:00 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.827511E+09 0.240771E+09 83.25 0.826175E+09 1335918.72 0.00 0.38 18-MAR-16:00 0.00 01-MAR-00:10 5226.93 18-MAR-15:50 5226.93 18-MAR-15:50 129.89 18-MAR-10:30 1509.35 18-MAR-15:50 0.00 01-MAR-00:10
April 0.834454E+10 0.240340E+10 356.79 0.834356E+10 979819.42 0.00 1.00 04-APR-06:02 0.00 01-APR-00:10 33985.13 25-APR-06:02 33985.13 25-APR-06:02 2106.87 16-APR-08:62 7361.91 30-APR-08:62 0.00 01-APR-00:10
May 0.135107E+11 0.388956E+10 409.74 0.135107E+11 -0.0 0.00 1.00 01-MAY-06:02 0.00 01-MAY-00:10 34015.33 11-MAY-06:02 34015.33 11-MAY-06:02 0.00 05-MAY-06:02 7750.81 07-MAY-08:62 0.00 01-MAY-00:10
June 0.217983E+11 0.641611E+10 423.99 0.217795E+11 18839141.00 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 35608.05 30-JUN-05:01 35608.05 30-JUN-05:01 1522.50 17-JUN-17:00 8655.38 18-JUN-08:62 0.00 01-JUN-00:10
July 0.231182E+11 0.636919E+10 434.69 0.213366E+11 0.178160E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-00:10 39891.53 14-JUL-05:02 35477.59 31-JUL-05:02 19693.02 14-JUL-05:03 8984.64 23-JUL-08:62 0.00 01-JUL-00:10
August 0.217266E+11 0.600276E+10 436.21 0.198960E+11 0.183053E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 38674.13 01-AUG-05:01 36001.85 16-AUG-05:01 16939.42 04-AUG-06:04 8928.12 13-AUG-08:62 0.00 01-AUG-00:10
September 0.181892E+11 0.492397E+10 415.65 0.163636E+11 0.182554E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 39532.90 04-SEP-08:62 35054.70 20-SEP-06:02 21007.57 03-SEP-08:04 8517.42 02-SEP-06:02 0.00 01-SEP-00:10
October 0.707772E+10 0.197027E+10 289.48 0.678381E+10 0.293907E+09 0.00 1.00 01-OCT-08:62 0.00 01-OCT-00:10 37990.57 03-OCT-06:02 34791.64 01-OCT-08:62 14640.00 03-OCT-06:04 8263.43 02-OCT-05:01 0.00 01-OCT-00:10
November 0.818145E+09 0.233218E+09 98.79 0.791950E+09 26195467.77 0.00 1.00 03-NOV-06:02 0.00 01-NOV-00:10 24171.11 03-NOV-06:02 17567.87 03-NOV-06:02 6603.23 03-NOV-06:02 5141.55 03-NOV-06:02 0.00 01-NOV-00:10
December 7817712.55 2366803.73 5.67 7817712.55 -0.0 0.00 0.05 22-DEC-16:00 0.00 01-DEC-00:10 688.09 22-DEC-16:00 688.09 22-DEC-16:00 0.00 22-DEC-16:40 206.58 22-DEC-16:00 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.115607E+12 0.325080E+11 2998.27 0.109828E+12 0.577893E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.231182E+11 0.641611E+10 436.21 0.217795E+11 0.183053E+10 0.00 1.00   0.00   39891.53   36001.85   21007.57   8984.64   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.114234E+11 0.344625E+10 192.87 0.114063E+11 17170829.54 0.00 1.00 08-JAN-09:02 0.00 01-JAN-00:10 96787.59 08-JAN-09:02 82987.59 08-JAN-09:02 13800.00 08-JAN-09:02 22985.10 08-JAN-09:02 0.00 01-JAN-00:10
February 0.741630E+09 0.225707E+09 34.58 0.685966E+09 55663421.93 0.00 0.28 18-FEB-16:00 0.00 01-FEB-00:10 17836.42 18-FEB-16:00 15674.80 18-FEB-16:00 2725.81 18-FEB-14:00 5341.20 18-FEB-16:00 0.00 01-FEB-00:10
March 0.133434E+11 0.401657E+10 195.57 0.132151E+11 0.128331E+09 0.00 1.00 17-MAR-06:03 0.00 01-MAR-00:10 114591.18 17-MAR-06:03 100516.86 17-MAR-06:03 15020.02 18-MAR-06:03 27124.37 17-MAR-06:03 0.00 01-MAR-00:10
April 0.563673E+11 0.171422E+11 371.54 0.563516E+11 15639293.97 0.00 1.00 02-APR-08:62 0.00 01-APR-00:10 153516.07 25-APR-06:02 153516.07 25-APR-06:02 11912.29 17-APR-06:02 37129.34 25-APR-06:02 0.00 01-APR-00:10
May 0.745975E+11 0.231929E+11 415.46 0.745975E+11 32041.06 0.00 1.00 01-MAY-06:02 0.00 01-MAY-00:10 153518.95 11-MAY-06:02 153518.95 11-MAY-06:02 106.78 13-MAY-06:15 39179.94 07-MAY-08:62 0.00 01-MAY-00:10
June 0.994320E+11 0.326104E+11 420.31 0.992009E+11 0.231073E+09 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 160631.51 30-JUN-05:01 160631.51 30-JUN-05:01 12550.17 17-JUN-16:55 43667.14 18-JUN-08:62 0.00 01-JUN-00:10
July 0.104386E+12 0.319245E+11 431.71 0.939934E+11 0.103922E+11 0.00 1.00 01-JUL-05:02 0.00 01-JUL-00:10 178959.47 14-JUL-05:02 160306.15 31-JUL-05:02 82516.91 14-JUL-05:02 45040.35 23-JUL-08:62 0.00 01-JUL-00:10
August 0.102823E+12 0.313182E+11 434.06 0.916171E+11 0.112061E+11 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 174015.88 01-AUG-05:01 160537.89 16-AUG-05:01 74553.96 04-AUG-06:04 44769.49 13-AUG-08:62 0.00 01-AUG-00:10
September 0.864348E+11 0.257180E+11 413.22 0.758793E+11 0.105555E+11 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 177823.57 04-SEP-08:62 158147.63 20-SEP-05:01 90277.44 03-SEP-08:04 42756.10 02-SEP-06:02 0.00 01-SEP-00:10
October 0.441825E+11 0.132366E+11 332.82 0.421001E+11 0.208231E+10 0.00 1.00 01-OCT-08:62 0.00 01-OCT-00:10 171190.03 03-OCT-06:02 156403.55 01-OCT-08:62 63537.65 03-OCT-06:04 41721.29 02-OCT-05:01 0.00 01-OCT-00:10
November 0.140166E+11 0.416613E+10 198.51 0.132623E+11 0.754285E+09 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 160460.38 11-NOV-09:02 135991.49 11-NOV-09:02 62146.18 12-NOV-09:03 38186.63 11-NOV-09:02 0.00 01-NOV-00:10
December 0.410177E+10 0.124837E+10 92.07 0.410176E+10 14696.66 0.00 0.46 22-DEC-15:10 0.00 01-DEC-00:10 29382.26 22-DEC-15:10 29382.26 22-DEC-15:10 24.46 12-DEC-15:10 8990.76 22-DEC-15:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.611850E+12 0.188246E+12 3532.73 0.576411E+12 0.354384E+11 0.00                            
Minimum of Months 0.741630E+09 0.225707E+09 34.58 0.685966E+09 14696.66 0.00 0.28   0.00   17836.42   15674.80   24.46   5341.20   0.00  
Maximum of Months 0.104386E+12 0.326104E+11 434.06 0.992009E+11 0.112061E+11 0.00 1.00   0.00   178959.47   160631.51   90277.44   45040.35   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.512293E+10 0.125624E+10 274.62 0.509373E+10 29201789.95 0.00 1.00 08-JAN-09:02 0.00 01-JAN-00:10 23979.99 08-JAN-09:02 21214.26 08-JAN-09:02 2765.73 08-JAN-09:02 5094.61 08-JAN-09:02 0.00 01-JAN-00:10
February 0.658099E+09 0.172175E+09 105.03 0.630434E+09 27664318.41 0.00 0.53 22-FEB-15:50 0.00 01-FEB-00:10 5395.23 22-FEB-15:50 5395.23 22-FEB-15:50 566.82 18-FEB-11:40 1322.54 22-FEB-15:50 0.00 01-FEB-00:10
March 0.312567E+10 0.810898E+09 224.27 0.310167E+10 24004452.76 0.00 1.00 17-MAR-06:03 0.00 01-MAR-00:10 12234.69 17-MAR-06:03 10729.41 17-MAR-06:03 1505.28 17-MAR-06:03 2593.50 17-MAR-06:03 0.00 01-MAR-00:10
April 0.992184E+10 0.264088E+10 380.07 0.992063E+10 1214589.71 0.00 1.00 02-APR-08:62 0.00 01-APR-00:10 23757.53 25-APR-06:02 23757.53 25-APR-06:02 1408.94 16-APR-08:62 5141.65 25-APR-06:02 0.00 01-APR-00:10
May 0.115131E+11 0.320316E+10 420.62 0.115131E+11 -0.0 0.00 1.00 01-MAY-06:02 0.00 01-MAY-00:10 23750.46 11-MAY-06:02 23750.46 11-MAY-06:02 0.00 10-MAY-06:02 5415.05 07-MAY-08:62 0.00 01-MAY-00:10
June 0.151242E+11 0.446316E+10 424.59 0.150946E+11 29530216.97 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 24797.31 18-JUN-07:01 24797.31 18-JUN-07:01 1723.21 17-JUN-16:55 6030.52 18-JUN-07:01 0.00 01-JUN-00:10
July 0.165782E+11 0.456724E+10 437.38 0.151965E+11 0.138173E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-00:10 27887.17 14-JUL-05:02 25035.41 21-JUL-04:03 13558.76 14-JUL-05:02 6256.21 23-JUL-08:62 0.00 01-JUL-00:10
August 0.172669E+11 0.471771E+10 444.72 0.157096E+11 0.155728E+10 0.00 1.00 01-AUG-04:03 0.00 01-AUG-00:10 27067.19 01-AUG-05:01 25051.77 15-AUG-04:03 12036.61 04-AUG-06:02 6211.87 13-AUG-08:62 0.00 01-AUG-00:10
September 0.161770E+11 0.424818E+10 424.28 0.146296E+11 0.154741E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 27630.26 04-SEP-08:62 24859.68 17-SEP-07:02 14942.87 03-SEP-07:01 5927.25 02-SEP-06:02 0.00 01-SEP-00:10
October 0.103304E+11 0.262906E+10 365.52 0.100028E+11 0.327569E+09 0.00 1.00 01-OCT-07:03 0.00 01-OCT-00:10 26537.30 03-OCT-05:02 24123.08 01-OCT-08:62 10167.23 03-OCT-06:02 5773.25 02-OCT-05:01 0.00 01-OCT-00:10
November 0.509346E+10 0.124713E+10 265.06 0.487097E+10 0.222487E+09 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 24675.73 11-NOV-09:02 22241.84 19-NOV-09:02 6118.79 03-NOV-06:02 5254.74 11-NOV-09:02 0.00 01-NOV-00:10
December 0.258960E+10 0.642370E+09 182.61 0.258916E+10 439169.47 0.00 0.91 22-DEC-15:30 0.00 01-DEC-00:10 10146.03 22-DEC-15:30 10146.03 22-DEC-15:30 59.70 13-DEC-14:20 2417.23 22-DEC-15:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.113501E+12 0.305982E+11 3948.77 0.108353E+12 0.514854E+10 0.00                            
Minimum of Months 0.658099E+09 0.172175E+09 105.03 0.630434E+09 -0.0 0.00 0.53   0.00   5395.23   5395.23   0.00   1322.54   0.00  
Maximum of Months 0.172669E+11 0.471771E+10 444.72 0.157096E+11 0.155728E+10 0.00 1.00   0.00   27887.17   25051.77   14942.87   6256.21   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.337923E+10 0.845366E+09 239.80 0.336963E+10 9601458.52 0.00 1.00 08-JAN-09:02 0.00 01-JAN-00:10 16756.29 08-JAN-09:02 14700.28 08-JAN-09:02 2056.01 08-JAN-09:02 3559.83 08-JAN-09:02 0.00 01-JAN-00:10
February 0.237342E+09 63244345.04 53.87 0.232112E+09 5230417.45 0.00 0.41 22-FEB-15:50 0.00 01-FEB-00:10 3411.19 22-FEB-15:50 3411.19 22-FEB-15:50 262.13 18-FEB-14:20 866.23 22-FEB-15:50 0.00 01-FEB-00:10
March 0.176140E+10 0.470284E+09 172.97 0.175296E+10 8438066.60 0.00 0.78 18-MAR-15:00 0.00 01-MAR-00:10 7306.40 18-MAR-15:00 7306.40 18-MAR-15:00 353.51 18-MAR-11:30 1870.91 18-MAR-15:00 0.00 01-MAR-00:10
April 0.739886E+10 0.201152E+10 361.33 0.739814E+10 726047.09 0.00 1.00 03-APR-06:02 0.00 01-APR-00:10 20328.31 25-APR-06:02 20328.31 25-APR-06:02 1184.37 16-APR-08:62 4399.49 25-APR-06:02 0.00 01-APR-00:10
May 0.872063E+10 0.247680E+10 405.93 0.872063E+10 0.00 0.00 1.00 01-MAY-06:02 0.00 01-MAY-00:10 20332.95 11-MAY-06:02 20332.95 11-MAY-06:02 0.00 11-MAY-06:02 4633.40 07-MAY-08:62 0.00 01-MAY-00:10
June 0.121978E+11 0.363056E+10 422.43 0.121723E+11 25411644.50 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 21281.25 30-JUN-05:01 21281.25 30-JUN-05:01 1537.82 17-JUN-16:55 5164.56 18-JUN-08:62 0.00 01-JUN-00:10
July 0.134791E+11 0.373289E+10 434.34 0.122795E+11 0.119958E+10 0.00 1.00 01-JUL-05:02 0.00 01-JUL-00:10 23855.95 14-JUL-05:02 21219.96 31-JUL-05:02 11796.52 14-JUL-05:02 5362.59 23-JUL-08:62 0.00 01-JUL-00:10
August 0.140161E+11 0.385027E+10 437.18 0.126914E+11 0.132475E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 23142.34 01-AUG-05:01 21738.52 16-AUG-05:01 10141.53 04-AUG-06:02 5326.91 13-AUG-08:62 0.00 01-AUG-00:10
September 0.130806E+11 0.345734E+10 420.54 0.117587E+11 0.132185E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 23630.18 04-SEP-08:62 21241.80 17-SEP-07:02 12488.21 03-SEP-08:62 5077.29 02-SEP-06:02 0.00 01-SEP-00:10
October 0.794076E+10 0.204606E+10 346.51 0.766817E+10 0.272594E+09 0.00 1.00 01-OCT-07:03 0.00 01-OCT-00:10 22711.07 03-OCT-06:02 20686.07 01-OCT-08:62 8726.48 03-OCT-06:02 4936.96 02-OCT-05:01 0.00 01-OCT-00:10
November 0.341160E+10 0.849803E+09 227.95 0.329517E+10 0.116428E+09 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 20797.29 01-NOV-06:02 17356.55 01-NOV-06:02 5319.75 03-NOV-06:02 4425.33 01-NOV-06:02 0.00 01-NOV-00:10
December 0.158452E+10 0.399644E+09 136.56 0.158452E+10 0.00 0.00 0.83 22-DEC-15:30 0.00 01-DEC-00:10 7815.67 22-DEC-15:30 7815.67 22-DEC-15:30 0.00 01-DEC-14:20 1902.97 22-DEC-15:30 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.872078E+11 0.238338E+11 3659.42 0.829232E+11 0.428461E+10 0.00                            
Minimum of Months 0.237342E+09 63244345.04 53.87 0.232112E+09 0.00 0.00 0.41   0.00   3411.19   3411.19   0.00   866.23   0.00  
Maximum of Months 0.140161E+11 0.385027E+10 437.18 0.126914E+11 0.132475E+10 0.00 1.00   0.00   23855.95   21738.52   12488.21   5362.59   0.00  



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.10 67.85 20.24 107.71 62.70 6.17 0.00 0.00
February 87.74 56.84 30.90 101.21 53.90 5.50 0.00 0.00
March 120.12 76.05 44.07 147.35 51.26 0.00 0.00 0.00
April 190.61 147.56 43.05 254.56 38.84 0.00 0.00 0.00
May 207.90 163.22 44.68 282.03 33.28 0.00 0.00 0.00
June 219.32 179.34 39.99 311.67 20.63 0.00 0.00 0.00
July 177.65 128.66 48.99 254.87 14.10 0.00 0.00 0.00
August 163.80 121.14 42.66 235.28 17.69 0.00 0.00 0.00
September 131.67 82.63 49.04 187.48 20.41 0.00 0.00 0.00
October 117.33 88.21 29.11 153.11 45.88 0.00 0.00 0.00
November 88.41 64.36 24.05 106.78 57.27 0.00 0.00 0.00
December 76.69 56.05 20.64 88.49 71.70 0.00 0.00 0.00
                 
Annual Sum or Average 139.33 102.86 36.47 186.25 40.60 11.67 0.00 0.00
Minimum of Months 76.69 56.05 20.24 88.49 14.10 0.00 0.00 0.00
Maximum of Months 219.32 179.34 49.04 311.67 71.70 6.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1365.53 1090.61 274.92 2118.96 686.31 0.00 0.00 0.00
February 863.40 582.31 281.09 1218.92 639.29 0.00 0.00 0.00
March 718.42 370.02 348.39 1094.27 579.76 0.00 0.00 0.00
April 611.56 247.13 364.43 1170.20 371.61 0.00 0.00 0.00
May 409.81 67.71 342.11 854.34 269.14 0.00 0.00 0.00
June 350.92 27.05 323.87 936.80 134.32 0.00 0.00 0.00
July 358.58 37.10 321.48 919.58 105.73 0.00 0.00 0.00
August 436.01 120.49 315.52 1072.41 136.15 0.00 0.00 0.00
September 628.25 268.03 360.22 1321.71 187.95 0.00 0.00 0.00
October 1001.04 692.87 308.17 1700.20 464.62 0.00 0.00 0.00
November 1166.59 893.55 273.04 1783.95 640.11 0.00 0.00 0.00
December 1269.53 1005.01 264.53 1882.44 808.74 0.00 0.00 0.00
                 
Annual Sum or Average 764.99 450.07 314.92 1340.87 417.76 0.00 0.00 0.00
Minimum of Months 350.92 27.05 264.53 854.34 105.73 0.00 0.00 0.00
Maximum of Months 1365.53 1090.61 364.43 2118.96 808.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1365.53 1090.61 274.92 2120.42 666.30 0.00 0.00 0.00
February 863.40 582.31 281.09 1225.98 606.56 0.00 0.00 0.00
March 718.42 370.02 348.39 1098.46 555.74 0.00 0.00 0.00
April 611.56 247.13 364.43 1166.19 355.22 0.00 0.00 0.00
May 409.81 67.71 342.11 850.11 253.86 0.00 0.00 0.00
June 350.92 27.05 323.87 933.72 122.50 0.00 0.00 0.00
July 358.58 37.10 321.48 916.31 95.94 0.00 0.00 0.00
August 436.01 120.49 315.52 1067.64 125.34 0.00 0.00 0.00
September 628.25 268.03 360.22 1316.73 176.13 0.00 0.00 0.00
October 1001.04 692.87 308.17 1696.93 449.65 0.00 0.00 0.00
November 1166.59 893.55 273.04 1784.15 621.17 0.00 0.00 0.00
December 1269.53 1005.01 264.53 1886.53 785.48 0.00 0.00 0.00
                 
Annual Sum or Average 764.99 450.07 314.92 1339.94 400.37 0.00 0.00 0.00
Minimum of Months 350.92 27.05 264.53 850.11 95.94 0.00 0.00 0.00
Maximum of Months 1365.53 1090.61 364.43 2120.42 785.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 280.94 224.38 56.56 437.46 127.36 0.00 0.00 0.00
February 177.63 119.80 57.83 266.70 105.42 0.00 0.00 0.00
March 147.80 76.13 71.68 232.25 105.08 0.00 0.00 0.00
April 125.82 50.84 74.98 220.50 76.54 0.00 0.00 0.00
May 84.31 13.93 70.38 146.82 58.19 0.00 0.00 0.00
June 72.20 5.57 66.63 140.16 33.02 0.00 0.00 0.00
July 73.77 7.63 66.14 142.41 27.12 0.00 0.00 0.00
August 89.70 24.79 64.91 175.28 35.22 0.00 0.00 0.00
September 129.25 55.14 74.11 234.17 46.07 0.00 0.00 0.00
October 205.95 142.55 63.40 334.97 94.06 0.00 0.00 0.00
November 240.01 183.84 56.18 369.42 117.13 0.00 0.00 0.00
December 261.19 206.77 54.42 396.81 143.76 0.00 0.00 0.00
                 
Annual Sum or Average 157.39 92.60 64.79 258.19 80.68 0.00 0.00 0.00
Minimum of Months 72.20 5.57 54.42 140.16 27.12 0.00 0.00 0.00
Maximum of Months 280.94 224.38 74.98 437.46 143.76 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R4C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R1C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R2C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: SKYLIGHTS_R3C4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235959E+09 0.181740E+09 54219438.54 0.288482E+09 0.167941E+09
February 0.212266E+09 0.137513E+09 74753010.79 0.244847E+09 0.130400E+09
March 0.321734E+09 0.203698E+09 0.118036E+09 0.394651E+09 0.137303E+09
April 0.494070E+09 0.382485E+09 0.111585E+09 0.659811E+09 0.100674E+09
May 0.556841E+09 0.437176E+09 0.119665E+09 0.755396E+09 89128708.99
June 0.568490E+09 0.464841E+09 0.103649E+09 0.807852E+09 53462001.98
July 0.475822E+09 0.344606E+09 0.131216E+09 0.682650E+09 37770621.91
August 0.438730E+09 0.324468E+09 0.114262E+09 0.630174E+09 47381712.43
September 0.341279E+09 0.214179E+09 0.127101E+09 0.485949E+09 52905824.23
October 0.314251E+09 0.236272E+09 77979578.17 0.410084E+09 0.122875E+09
November 0.229172E+09 0.166830E+09 62341635.83 0.276779E+09 0.148444E+09
December 0.205405E+09 0.150119E+09 55286044.15 0.237016E+09 0.192047E+09
           
Annual Sum or Average 0.439402E+10 0.324393E+10 0.115009E+10 0.587369E+10 0.128033E+10
Minimum of Months 0.205405E+09 0.137513E+09 54219438.54 0.237016E+09 37770621.91
Maximum of Months 0.568490E+09 0.464841E+09 0.131216E+09 0.807852E+09 0.192047E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: POINT_OF_SALE_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.365742E+10 0.292108E+10 0.736344E+09 0.567542E+10 0.183821E+10
February 0.208875E+10 0.140872E+10 0.680024E+09 0.294881E+10 0.154656E+10
March 0.192420E+10 0.991064E+09 0.933140E+09 0.293090E+10 0.155284E+10
April 0.158517E+10 0.640559E+09 0.944606E+09 0.303315E+10 0.963217E+09
May 0.109764E+10 0.181341E+09 0.916294E+09 0.228827E+10 0.720852E+09
June 0.909576E+09 70116109.53 0.839460E+09 0.242819E+10 0.348168E+09
July 0.960408E+09 99361596.00 0.861046E+09 0.246300E+10 0.283196E+09
August 0.116781E+10 0.322723E+09 0.845084E+09 0.287233E+10 0.364660E+09
September 0.162842E+10 0.694722E+09 0.933695E+09 0.342586E+10 0.487155E+09
October 0.268120E+10 0.185579E+10 0.825411E+09 0.455382E+10 0.124444E+10
November 0.302381E+10 0.231608E+10 0.707730E+09 0.462401E+10 0.165917E+10
December 0.340032E+10 0.269181E+10 0.708510E+09 0.504192E+10 0.216614E+10
           
Annual Sum or Average 0.241247E+11 0.141934E+11 0.993135E+10 0.422857E+11 0.131746E+11
Minimum of Months 0.909576E+09 70116109.53 0.680024E+09 0.228827E+10 0.283196E+09
Maximum of Months 0.365742E+10 0.292108E+10 0.944606E+09 0.567542E+10 0.216614E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_RETAIL_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.365742E+10 0.292108E+10 0.736344E+09 0.567933E+10 0.178461E+10
February 0.208875E+10 0.140872E+10 0.680024E+09 0.296588E+10 0.146740E+10
March 0.192420E+10 0.991064E+09 0.933140E+09 0.294212E+10 0.148851E+10
April 0.158517E+10 0.640559E+09 0.944606E+09 0.302275E+10 0.920731E+09
May 0.109764E+10 0.181341E+09 0.916294E+09 0.227694E+10 0.679933E+09
June 0.909576E+09 70116109.53 0.839460E+09 0.242021E+10 0.317520E+09
July 0.960408E+09 99361596.00 0.861046E+09 0.245425E+10 0.256979E+09
August 0.116781E+10 0.322723E+09 0.845084E+09 0.285956E+10 0.335704E+09
September 0.162842E+10 0.694722E+09 0.933695E+09 0.341297E+10 0.456537E+09
October 0.268120E+10 0.185579E+10 0.825411E+09 0.454504E+10 0.120435E+10
November 0.302381E+10 0.231608E+10 0.707730E+09 0.462452E+10 0.161008E+10
December 0.340032E+10 0.269181E+10 0.708510E+09 0.505287E+10 0.210383E+10
           
Annual Sum or Average 0.241247E+11 0.141934E+11 0.993135E+10 0.422564E+11 0.126262E+11
Minimum of Months 0.909576E+09 70116109.53 0.680024E+09 0.227694E+10 0.256979E+09
Maximum of Months 0.365742E+10 0.292108E+10 0.944606E+09 0.567933E+10 0.210383E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: FRONT_ENTRY_WALL_SOUTH_GLAZING

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.752469E+09 0.600976E+09 0.151493E+09 0.117168E+10 0.341129E+09
February 0.429733E+09 0.289827E+09 0.139906E+09 0.645207E+09 0.255033E+09
March 0.395880E+09 0.203899E+09 0.191981E+09 0.622047E+09 0.281445E+09
April 0.326127E+09 0.131787E+09 0.194340E+09 0.571544E+09 0.198380E+09
May 0.225824E+09 37308670.65 0.188515E+09 0.393246E+09 0.155863E+09
June 0.187133E+09 14425512.42 0.172707E+09 0.363283E+09 85586853.06
July 0.197591E+09 20442405.41 0.177148E+09 0.381430E+09 72647030.95
August 0.240261E+09 66396258.78 0.173864E+09 0.469482E+09 94333235.02
September 0.335026E+09 0.142930E+09 0.192095E+09 0.606957E+09 0.119419E+09
October 0.551622E+09 0.381805E+09 0.169817E+09 0.897179E+09 0.251921E+09
November 0.622111E+09 0.476505E+09 0.145606E+09 0.957543E+09 0.303606E+09
December 0.699572E+09 0.553805E+09 0.145767E+09 0.106282E+10 0.385051E+09
           
Annual Sum or Average 0.496335E+10 0.292011E+10 0.204324E+10 0.814242E+10 0.254441E+10
Minimum of Months 0.187133E+09 14425512.42 0.139906E+09 0.363283E+09 72647030.95
Maximum of Months 0.752469E+09 0.600976E+09 0.194340E+09 0.117168E+10 0.385051E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1723.31 1003.23 1409.55 1085.66 323.89 0.00 0.00
February 1619.36 862.43 1403.88 909.48 494.40 0.00 0.00
March 2357.53 820.21 1921.95 1216.83 705.11 0.00 0.00
April 4072.91 621.44 3049.81 2361.02 688.79 0.00 0.00
May 4512.52 532.43 3326.41 2611.57 714.84 0.00 0.00
June 4986.74 330.01 3509.20 2869.39 639.81 0.00 0.00
July 4077.96 225.63 2842.42 2058.58 783.85 0.00 0.00
August 3764.48 283.04 2620.85 1938.28 682.57 0.00 0.00
September 2999.68 326.58 2106.66 1322.09 784.57 0.00 0.00
October 2449.73 734.02 1877.25 1411.42 465.83 0.00 0.00
November 1708.51 916.32 1414.64 1029.81 384.82 0.00 0.00
December 1415.86 1147.23 1227.03 896.77 330.26 0.00 0.00
               
Annual Sum or Average 2980.06 649.58 2229.33 1645.83 583.51 0.00 0.00
Minimum of Months 1415.86 225.63 1227.03 896.77 323.89 0.00 0.00
Maximum of Months 4986.74 1147.23 3509.20 2869.39 784.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2118.96 686.31 1365.53 1090.61 274.92 0.00 0.00
February 1218.92 639.29 863.40 582.31 281.09 0.00 0.00
March 1094.27 579.76 718.42 370.02 348.39 0.00 0.00
April 1170.20 371.61 611.56 247.13 364.43 0.00 0.00
May 854.34 269.14 409.81 67.71 342.11 0.00 0.00
June 936.80 134.32 350.92 27.05 323.87 0.00 0.00
July 919.58 105.73 358.58 37.10 321.48 0.00 0.00
August 1072.41 136.15 436.01 120.49 315.52 0.00 0.00
September 1321.71 187.95 628.25 268.03 360.22 0.00 0.00
October 1700.20 464.62 1001.04 692.87 308.17 0.00 0.00
November 1783.95 640.11 1166.59 893.55 273.04 0.00 0.00
December 1882.44 808.74 1269.53 1005.01 264.53 0.00 0.00
               
Annual Sum or Average 1340.87 417.76 764.99 450.07 314.92 0.00 0.00
Minimum of Months 854.34 105.73 350.92 27.05 264.53 0.00 0.00
Maximum of Months 2118.96 808.74 1365.53 1090.61 364.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2120.42 666.30 1365.53 1090.61 274.92 0.00 0.00
February 1225.98 606.56 863.40 582.31 281.09 0.00 0.00
March 1098.46 555.74 718.42 370.02 348.39 0.00 0.00
April 1166.19 355.22 611.56 247.13 364.43 0.00 0.00
May 850.11 253.86 409.81 67.71 342.11 0.00 0.00
June 933.72 122.50 350.92 27.05 323.87 0.00 0.00
July 916.31 95.94 358.58 37.10 321.48 0.00 0.00
August 1067.64 125.34 436.01 120.49 315.52 0.00 0.00
September 1316.73 176.13 628.25 268.03 360.22 0.00 0.00
October 1696.93 449.65 1001.04 692.87 308.17 0.00 0.00
November 1784.15 621.17 1166.59 893.55 273.04 0.00 0.00
December 1886.53 785.48 1269.53 1005.01 264.53 0.00 0.00
               
Annual Sum or Average 1339.94 400.37 764.99 450.07 314.92 0.00 0.00
Minimum of Months 850.11 95.94 350.92 27.05 264.53 0.00 0.00
Maximum of Months 2120.42 785.48 1365.53 1090.61 364.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 437.46 127.36 280.94 224.38 56.56 0.00 0.00
February 266.70 105.42 177.63 119.80 57.83 0.00 0.00
March 232.25 105.08 147.80 76.13 71.68 0.00 0.00
April 220.50 76.54 125.82 50.84 74.98 0.00 0.00
May 146.82 58.19 84.31 13.93 70.38 0.00 0.00
June 140.16 33.02 72.20 5.57 66.63 0.00 0.00
July 142.41 27.12 73.77 7.63 66.14 0.00 0.00
August 175.28 35.22 89.70 24.79 64.91 0.00 0.00
September 234.17 46.07 129.25 55.14 74.11 0.00 0.00
October 334.97 94.06 205.95 142.55 63.40 0.00 0.00
November 369.42 117.13 240.01 183.84 56.18 0.00 0.00
December 396.81 143.76 261.19 206.77 54.42 0.00 0.00
               
Annual Sum or Average 258.19 80.68 157.39 92.60 64.79 0.00 0.00
Minimum of Months 140.16 27.12 72.20 5.57 54.42 0.00 0.00
Maximum of Months 437.46 143.76 280.94 224.38 74.98 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.461571E+10 0.268705E+10 0.377534E+10 0.290783E+10 0.867511E+09 0.00 0.00
February 0.391754E+10 0.208639E+10 0.339626E+10 0.220021E+10 0.119605E+10 0.00 0.00
March 0.631441E+10 0.219685E+10 0.514774E+10 0.325916E+10 0.188858E+10 0.00 0.00
April 0.105570E+11 0.161078E+10 0.790512E+10 0.611976E+10 0.178535E+10 0.00 0.00
May 0.120863E+11 0.142606E+10 0.890946E+10 0.699482E+10 0.191464E+10 0.00 0.00
June 0.129256E+11 0.855392E+09 0.909584E+10 0.743746E+10 0.165838E+10 0.00 0.00
July 0.109224E+11 0.604330E+09 0.761315E+10 0.551370E+10 0.209945E+10 0.00 0.00
August 0.100828E+11 0.758107E+09 0.701968E+10 0.519149E+10 0.182819E+10 0.00 0.00
September 0.777518E+10 0.846493E+09 0.546046E+10 0.342686E+10 0.203361E+10 0.00 0.00
October 0.656135E+10 0.196600E+10 0.502802E+10 0.378035E+10 0.124767E+10 0.00 0.00
November 0.442847E+10 0.237510E+10 0.366675E+10 0.266928E+10 0.997466E+09 0.00 0.00
December 0.379225E+10 0.307275E+10 0.328648E+10 0.240191E+10 0.884577E+09 0.00 0.00
               
Annual Sum or Average 0.939791E+11 0.204853E+11 0.703043E+11 0.519028E+11 0.184015E+11 0.00 0.00
Minimum of Months 0.379225E+10 0.604330E+09 0.328648E+10 0.220021E+10 0.867511E+09 0.00 0.00
Maximum of Months 0.129256E+11 0.307275E+10 0.909584E+10 0.743746E+10 0.209945E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.567542E+10 0.183821E+10 0.365742E+10 0.292108E+10 0.736344E+09 0.00 0.00
February 0.294881E+10 0.154656E+10 0.208875E+10 0.140872E+10 0.680024E+09 0.00 0.00
March 0.293090E+10 0.155284E+10 0.192420E+10 0.991064E+09 0.933140E+09 0.00 0.00
April 0.303315E+10 0.963217E+09 0.158517E+10 0.640559E+09 0.944606E+09 0.00 0.00
May 0.228827E+10 0.720852E+09 0.109764E+10 0.181341E+09 0.916294E+09 0.00 0.00
June 0.242819E+10 0.348168E+09 0.909576E+09 70116109.53 0.839460E+09 0.00 0.00
July 0.246300E+10 0.283196E+09 0.960408E+09 99361596.00 0.861046E+09 0.00 0.00
August 0.287233E+10 0.364660E+09 0.116781E+10 0.322723E+09 0.845084E+09 0.00 0.00
September 0.342586E+10 0.487155E+09 0.162842E+10 0.694722E+09 0.933695E+09 0.00 0.00
October 0.455382E+10 0.124444E+10 0.268120E+10 0.185579E+10 0.825411E+09 0.00 0.00
November 0.462401E+10 0.165917E+10 0.302381E+10 0.231608E+10 0.707730E+09 0.00 0.00
December 0.504192E+10 0.216614E+10 0.340032E+10 0.269181E+10 0.708510E+09 0.00 0.00
               
Annual Sum or Average 0.422857E+11 0.131746E+11 0.241247E+11 0.141934E+11 0.993135E+10 0.00 0.00
Minimum of Months 0.228827E+10 0.283196E+09 0.909576E+09 70116109.53 0.680024E+09 0.00 0.00
Maximum of Months 0.567542E+10 0.216614E+10 0.365742E+10 0.292108E+10 0.944606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.567933E+10 0.178461E+10 0.365742E+10 0.292108E+10 0.736344E+09 0.00 0.00
February 0.296588E+10 0.146740E+10 0.208875E+10 0.140872E+10 0.680024E+09 0.00 0.00
March 0.294212E+10 0.148851E+10 0.192420E+10 0.991064E+09 0.933140E+09 0.00 0.00
April 0.302275E+10 0.920731E+09 0.158517E+10 0.640559E+09 0.944606E+09 0.00 0.00
May 0.227694E+10 0.679933E+09 0.109764E+10 0.181341E+09 0.916294E+09 0.00 0.00
June 0.242021E+10 0.317520E+09 0.909576E+09 70116109.53 0.839460E+09 0.00 0.00
July 0.245425E+10 0.256979E+09 0.960408E+09 99361596.00 0.861046E+09 0.00 0.00
August 0.285956E+10 0.335704E+09 0.116781E+10 0.322723E+09 0.845084E+09 0.00 0.00
September 0.341297E+10 0.456537E+09 0.162842E+10 0.694722E+09 0.933695E+09 0.00 0.00
October 0.454504E+10 0.120435E+10 0.268120E+10 0.185579E+10 0.825411E+09 0.00 0.00
November 0.462452E+10 0.161008E+10 0.302381E+10 0.231608E+10 0.707730E+09 0.00 0.00
December 0.505287E+10 0.210383E+10 0.340032E+10 0.269181E+10 0.708510E+09 0.00 0.00
               
Annual Sum or Average 0.422564E+11 0.126262E+11 0.241247E+11 0.141934E+11 0.993135E+10 0.00 0.00
Minimum of Months 0.227694E+10 0.256979E+09 0.909576E+09 70116109.53 0.680024E+09 0.00 0.00
Maximum of Months 0.567933E+10 0.210383E+10 0.365742E+10 0.292108E+10 0.944606E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117168E+10 0.341129E+09 0.752469E+09 0.600976E+09 0.151493E+09 0.00 0.00
February 0.645207E+09 0.255033E+09 0.429733E+09 0.289827E+09 0.139906E+09 0.00 0.00
March 0.622047E+09 0.281445E+09 0.395880E+09 0.203899E+09 0.191981E+09 0.00 0.00
April 0.571544E+09 0.198380E+09 0.326127E+09 0.131787E+09 0.194340E+09 0.00 0.00
May 0.393246E+09 0.155863E+09 0.225824E+09 37308670.65 0.188515E+09 0.00 0.00
June 0.363283E+09 85586853.06 0.187133E+09 14425512.42 0.172707E+09 0.00 0.00
July 0.381430E+09 72647030.95 0.197591E+09 20442405.41 0.177148E+09 0.00 0.00
August 0.469482E+09 94333235.02 0.240261E+09 66396258.78 0.173864E+09 0.00 0.00
September 0.606957E+09 0.119419E+09 0.335026E+09 0.142930E+09 0.192095E+09 0.00 0.00
October 0.897179E+09 0.251921E+09 0.551622E+09 0.381805E+09 0.169817E+09 0.00 0.00
November 0.957543E+09 0.303606E+09 0.622111E+09 0.476505E+09 0.145606E+09 0.00 0.00
December 0.106282E+10 0.385051E+09 0.699572E+09 0.553805E+09 0.145767E+09 0.00 0.00
               
Annual Sum or Average 0.814242E+10 0.254441E+10 0.496335E+10 0.292011E+10 0.204324E+10 0.00 0.00
Minimum of Months 0.363283E+09 72647030.95 0.187133E+09 14425512.42 0.139906E+09 0.00 0.00
Maximum of Months 0.117168E+10 0.385051E+09 0.752469E+09 0.600976E+09 0.194340E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.228936E+10 -0.191143E+10 0.00 0.00 744.00 0.00 -377925996.0 58.99 0.00 0.00
February 0.207133E+10 -0.172301E+10 0.00 0.00 672.00 0.00 -348311252.1 59.00 0.00 0.00
March 0.223528E+10 -0.186008E+10 0.00 0.00 744.00 0.00 -375198950.9 58.99 0.00 0.00
April 0.197001E+10 -0.162768E+10 0.00 0.00 720.00 0.00 -342334306.6 58.99 0.00 0.00
May 0.187621E+10 -0.152686E+10 0.00 0.00 744.00 0.00 -349356868.2 58.99 0.00 0.00
June 0.170313E+10 -0.137086E+10 0.00 0.00 720.00 0.00 -332269806.2 58.99 0.00 0.00
July 0.165600E+10 -0.131262E+10 0.00 0.00 744.00 0.00 -343373163.7 58.99 0.00 0.00
August 0.171963E+10 -0.137460E+10 0.00 0.00 744.00 0.00 -345026531.4 58.99 0.00 0.00
September 0.173669E+10 -0.140142E+10 0.00 0.00 720.00 0.00 -335273879.5 58.99 0.00 0.00
October 0.192762E+10 -0.157115E+10 0.00 0.00 744.00 0.00 -356473443.8 58.99 0.00 0.00
November 0.202002E+10 -0.166271E+10 0.00 0.00 720.00 0.00 -357309760.7 58.99 0.00 0.00
December 0.223730E+10 -0.185210E+10 0.00 0.00 744.00 0.00 -385201105.0 58.99 0.00 0.00
                     
Annual Sum or Average 0.234426E+11 -0.191945E+11 0.00 0.00 8760.00 0.00 -0.424806E+10 58.99 0.00 0.00
Minimum of Months 0.165600E+10 -0.191143E+10 0.00 0.00 672.00 0.00 -385201105.0 58.99 0.00 0.00
Maximum of Months 0.228936E+10 -0.131262E+10 0.00 0.00 744.00 0.00 -332269806.2 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.82 0.50 06-JAN-11:00 215.15 5.45 0.00 2.83 177.60 4.08 0.00 0.00
February 241.00 0.75 0.50 05-FEB-12:09 300.83 7.04 0.00 33.50 248.41 5.55 0.00 15.67
March 344.33 0.71 0.50 02-MAR-10:09 365.69 8.29 0.00 92.67 305.10 6.76 0.00 52.00
April 380.33 0.69 0.50 02-APR-11:09 372.93 9.04 0.00 78.00 3919.77 7.43 0.00 73.67
May 403.17 0.70 0.50 01-MAY-10:20 357.69 10.14 0.00 45.50 301.86 8.41 0.00 27.33
June 418.17 0.73 0.50 04-JUN-11:39 315.48 9.92 0.00 18.83 265.83 8.07 0.00 9.50
July 399.50 0.70 0.50 01-JUL-11:39 362.83 10.55 0.00 80.33 306.24 8.90 0.00 43.17
August 361.83 0.70 0.50 01-AUG-09:39 586.88 9.42 0.00 66.50 491.79 7.89 0.00 49.50
September 350.17 0.68 0.50 01-SEP-08:00 2543.82 9.40 0.00 123.17 2718.07 7.82 0.00 83.17
October 348.00 0.76 0.50 01-OCT-08:30 281.28 6.32 0.00 35.50 237.82 4.90 0.00 19.00
November 288.50 0.79 0.50 01-NOV-11:00 243.04 6.15 0.00 10.83 453.52 4.71 0.00 11.33
December 290.67 0.79 0.50 02-DEC-11:30 219.13 5.71 0.00 1.00 1428.66 4.28 0.00 45.17
                         
Annual Sum or Average 4135.50 0.73     522.99 8.33 0.00 588.67 924.81 6.76 0.00 429.50
Minimum of Months 241.00 0.68 0.50   215.15 5.45 0.00 1.00 177.60 4.08 0.00 0.00
Maximum of Months 418.17 0.82 0.50   2543.82 10.55 0.00 123.17 3919.77 8.90 0.00 83.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.803926E+09 46053.00 01-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 0.978745E+09 46053.00 05-FEB-08:61 0.00 0.00 0.00 0.00 0.00
March 0.579737E+09 46053.00 26-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.143308E+09 29440.27 24-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.182236E+10 46053.00 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.432808E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182236E+10 46053.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.337000E+09 206530.17 01-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 8608977.11 6404.35 13-FEB-07:40 0.00 0.00 0.00 0.00 0.00
March 28902030.23 11119.80 27-MAR-06:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.534465E+09 27846.25 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.908976E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.534465E+09 206530.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 5120865.74 9382.36 01-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 5429334.55 9753.07 13-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 9481093.02 5405.74 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 10120043.46 2027.65 07-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 30151336.77     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 10120043.46 9753.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 21191410.40 26239.21 01-JAN-08:61 0.00 0.00 0.00 0.00 0.00
February 48285178.79 16162.49 13-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 74033980.78 15953.91 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 64384405.50 12454.30 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.207895E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 74033980.78 26239.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONT_ENTRY UNIT HEATER HEATING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 14003172.55 3092.82 01-JAN-08:03 0.00 0.00 0.00 0.00 0.00
February 887243.18 2403.93 01-FEB-08:05 0.00 0.00 0.00 0.00 0.00
March 16925315.55 2382.17 26-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1001679.17 1373.03 25-OCT-07:10 0.00 0.00 0.00 0.00 0.00
November 6436521.79 2040.60 23-NOV-08:10 0.00 0.00 0.00 0.00 0.00
December 48138409.23 3709.06 16-DEC-08:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 87392341.47     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 48138409.23 3709.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.188342E+09 0.188342E+09 3140.06 31-JAN-17:00 3140.06 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.827511E+09 0.826175E+09 5226.93 18-MAR-15:50 5226.93 0.00
April 0.00 0.00 0.834454E+10 0.834356E+10 33985.13 25-APR-06:02 33985.13 0.00
May 0.00 0.00 0.135107E+11 0.135107E+11 34015.33 11-MAY-06:02 34015.33 0.00
June 0.00 0.00 0.217983E+11 0.217795E+11 35608.05 30-JUN-05:01 35608.05 0.00
July 0.00 0.00 0.231182E+11 0.213366E+11 39891.53 14-JUL-05:02 20309.52 0.00
August 0.00 0.00 0.217266E+11 0.198960E+11 38674.13 01-AUG-05:01 24657.06 0.00
September 0.00 0.00 0.181892E+11 0.163636E+11 39532.90 04-SEP-08:62 19436.74 0.00
October 0.00 0.00 0.707772E+10 0.678381E+10 37990.57 03-OCT-06:02 23470.65 0.00
November 0.00 0.00 0.818145E+09 0.791950E+09 24171.11 03-NOV-06:02 17567.87 0.00
December 0.00 0.00 7817712.55 7817712.55 688.09 22-DEC-16:00 688.09 0.00
                 
Annual Sum or Average 0.00 0.00 0.115607E+12 0.109828E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.231182E+11 0.217795E+11 39891.53   35608.05 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.114234E+11 0.114063E+11 96787.59 08-JAN-09:02 82987.59 0.00
February 0.00 0.00 0.741630E+09 0.685966E+09 17836.42 18-FEB-16:00 15674.80 0.00
March 0.00 0.00 0.133434E+11 0.132151E+11 114591.18 17-MAR-06:03 100516.86 0.00
April 0.00 0.00 0.563673E+11 0.563516E+11 153516.07 25-APR-06:02 153516.07 0.00
May 0.00 0.00 0.745975E+11 0.745975E+11 153518.95 11-MAY-06:02 153518.95 0.00
June 0.00 0.00 0.994320E+11 0.992009E+11 160631.51 30-JUN-05:01 160631.51 0.00
July 0.00 0.00 0.104386E+12 0.939934E+11 178959.47 14-JUL-05:02 96442.56 0.00
August 0.00 0.00 0.102823E+12 0.916171E+11 174015.88 01-AUG-05:01 112949.52 0.00
September 0.00 0.00 0.864348E+11 0.758793E+11 177823.57 04-SEP-08:62 92029.08 0.00
October 0.00 0.00 0.441825E+11 0.421001E+11 171190.03 03-OCT-06:02 108285.62 0.00
November 0.00 0.00 0.140166E+11 0.132623E+11 160460.38 11-NOV-09:02 135991.49 0.00
December 0.00 0.00 0.410177E+10 0.410176E+10 29382.26 22-DEC-15:10 29382.26 0.00
                 
Annual Sum or Average 0.00 0.00 0.611850E+12 0.576411E+12       0.00
Minimum of Months 0.00 0.00 0.741630E+09 0.685966E+09 17836.42   15674.80 0.00
Maximum of Months 0.00 0.00 0.104386E+12 0.992009E+11 178959.47   160631.51 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.512293E+10 0.509373E+10 23979.99 08-JAN-09:02 21214.26 0.00
February 0.00 0.00 0.658099E+09 0.630434E+09 5395.23 22-FEB-15:50 5395.23 0.00
March 0.00 0.00 0.312567E+10 0.310167E+10 12234.69 17-MAR-06:03 10729.41 0.00
April 0.00 0.00 0.992184E+10 0.992063E+10 23757.53 25-APR-06:02 23757.53 0.00
May 0.00 0.00 0.115131E+11 0.115131E+11 23750.46 11-MAY-06:02 23750.46 0.00
June 0.00 0.00 0.151242E+11 0.150946E+11 24797.31 18-JUN-07:01 24797.31 0.00
July 0.00 0.00 0.165782E+11 0.151965E+11 27887.17 14-JUL-05:02 14328.41 0.00
August 0.00 0.00 0.172669E+11 0.157096E+11 27067.19 01-AUG-05:01 17342.52 0.00
September 0.00 0.00 0.161770E+11 0.146296E+11 27630.26 04-SEP-08:62 13448.33 0.00
October 0.00 0.00 0.103304E+11 0.100028E+11 26537.30 03-OCT-05:02 17186.66 0.00
November 0.00 0.00 0.509346E+10 0.487097E+10 24675.73 11-NOV-09:02 21749.69 0.00
December 0.00 0.00 0.258960E+10 0.258916E+10 10146.03 22-DEC-15:30 10146.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.113501E+12 0.108353E+12       0.00
Minimum of Months 0.00 0.00 0.658099E+09 0.630434E+09 5395.23   5395.23 0.00
Maximum of Months 0.00 0.00 0.172669E+11 0.157096E+11 27887.17   24797.31 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 COOLING COIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.337923E+10 0.336963E+10 16756.29 08-JAN-09:02 14700.28 0.00
February 0.00 0.00 0.237342E+09 0.232112E+09 3411.19 22-FEB-15:50 3411.19 0.00
March 0.00 0.00 0.176140E+10 0.175296E+10 7306.40 18-MAR-15:00 7306.40 0.00
April 0.00 0.00 0.739886E+10 0.739814E+10 20328.31 25-APR-06:02 20328.31 0.00
May 0.00 0.00 0.872063E+10 0.872063E+10 20332.95 11-MAY-06:02 20332.95 0.00
June 0.00 0.00 0.121978E+11 0.121723E+11 21281.25 30-JUN-05:01 21281.25 0.00
July 0.00 0.00 0.134791E+11 0.122795E+11 23855.95 14-JUL-05:02 12059.43 0.00
August 0.00 0.00 0.140161E+11 0.126914E+11 23142.34 01-AUG-05:01 14756.51 0.00
September 0.00 0.00 0.130806E+11 0.117587E+11 23630.18 04-SEP-08:62 11573.59 0.00
October 0.00 0.00 0.794076E+10 0.766817E+10 22711.07 03-OCT-06:02 13984.59 0.00
November 0.00 0.00 0.341160E+10 0.329517E+10 20797.29 01-NOV-06:02 17356.55 0.00
December 0.00 0.00 0.158452E+10 0.158452E+10 7815.67 22-DEC-15:30 7815.67 0.00
                 
Annual Sum or Average 0.00 0.00 0.872078E+11 0.829232E+11       0.00
Minimum of Months 0.00 0.00 0.237342E+09 0.232112E+09 3411.19   3411.19 0.00
Maximum of Months 0.00 0.00 0.140161E+11 0.126914E+11 23855.95   21281.25 0.00



Table of Contents

Report: FanReportMonthly

For: FRONT_ENTRY UNIT HEATER FAN

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 877372.62 0.00 108.72 01-JAN-08:61 0.08
February 189173.28 0.00 108.72 01-FEB-08:05 0.08
March 1462287.71 0.00 108.72 13-MAR-07:04 0.08
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 225050.97 0.00 108.72 25-OCT-07:04 0.08
November 847862.83 0.00 108.72 04-NOV-07:04 0.08
December 3873185.70 0.00 108.72 04-DEC-08:04 0.08
           
Annual Sum or Average 7474933.11 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 3873185.70 0.00 108.72   0.08



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135988E+10 0.35 2087.69 01-JAN-08:61 0.97
February 0.124115E+10 0.36 2087.69 05-FEB-08:61 0.96
March 0.137761E+10 0.36 2087.69 26-MAR-08:61 0.97
April 0.130989E+10 0.35 2087.69 05-APR-06:02 0.97
May 0.135453E+10 0.35 2087.69 02-MAY-06:02 0.97
June 0.142771E+10 0.37 2087.69 01-JUN-06:02 0.96
July 0.141282E+10 0.36 2087.69 01-JUL-05:02 0.97
August 0.141076E+10 0.36 2087.69 01-AUG-05:01 0.95
September 0.132101E+10 0.35 2087.69 01-SEP-05:02 0.95
October 0.134079E+10 0.35 2087.69 01-OCT-08:62 0.96
November 0.129365E+10 0.35 1635.83 24-NOV-07:03 0.87
December 0.139036E+10 0.36 2087.69 06-DEC-06:02 0.97
           
Annual Sum or Average 0.162402E+11 0.36      
Minimum of Months 0.124115E+10 0.35 1635.83   0.87
Maximum of Months 0.142771E+10 0.37 2087.69   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.868243E+10 0.55 13528.31 01-JAN-08:61 1.52
February 0.787057E+10 0.55 5663.02 13-FEB-07:40 0.94
March 0.882654E+10 0.56 9538.12 17-MAR-06:03 1.28
April 0.850099E+10 0.56 13528.31 03-APR-06:02 1.53
May 0.881892E+10 0.56 13528.31 01-MAY-06:02 1.53
June 0.945538E+10 0.59 13528.31 01-JUN-06:02 1.52
July 0.927261E+10 0.57 13528.31 01-JUL-05:02 1.52
August 0.939239E+10 0.58 13528.31 01-AUG-05:01 1.50
September 0.865482E+10 0.56 13528.31 01-SEP-05:02 1.50
October 0.869377E+10 0.55 13528.31 01-OCT-08:62 1.51
November 0.836282E+10 0.55 13528.31 01-NOV-06:02 1.51
December 0.870943E+10 0.55 6505.73 06-DEC-07:10 1.04
           
Annual Sum or Average 0.105241E+12 0.56      
Minimum of Months 0.787057E+10 0.55 5663.02   0.94
Maximum of Months 0.945538E+10 0.59 13528.31   1.53



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.966766E+09 0.36 1508.29 08-JAN-09:02 0.99
February 0.877616E+09 0.36 874.32 13-FEB-07:03 0.76
March 0.984159E+09 0.37 753.52 27-MAR-06:03 0.70
April 0.949100E+09 0.37 1508.29 15-APR-06:02 1.00
May 0.981908E+09 0.37 1508.29 02-MAY-06:02 1.00
June 0.104271E+10 0.39 1508.29 01-JUN-06:02 1.00
July 0.104766E+10 0.38 1508.29 01-JUL-05:02 1.00
August 0.109937E+10 0.39 1508.29 01-AUG-05:01 0.98
September 0.104020E+10 0.38 1508.29 01-SEP-05:02 0.98
October 0.100566E+10 0.37 1508.29 01-OCT-08:62 0.99
November 0.933414E+09 0.36 1508.29 01-NOV-06:02 0.99
December 0.968968E+09 0.36 659.66 07-DEC-07:05 0.65
           
Annual Sum or Average 0.118975E+11 0.37      
Minimum of Months 0.877616E+09 0.36 659.66   0.65
Maximum of Months 0.109937E+10 0.39 1508.29   1.00



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.807694E+09 0.36 1215.63 01-JAN-08:61 0.99
February 0.734013E+09 0.36 942.25 13-FEB-07:03 0.87
March 0.823579E+09 0.37 936.60 27-MAR-06:03 0.87
April 0.790750E+09 0.37 1259.46 06-APR-06:02 1.00
May 0.817573E+09 0.37 1259.46 05-MAY-06:02 1.00
June 0.852976E+09 0.38 1259.46 01-JUN-06:02 1.00
July 0.859791E+09 0.37 1259.46 01-JUL-06:02 1.00
August 0.901318E+09 0.39 1259.46 01-AUG-05:01 0.98
September 0.854985E+09 0.38 1259.46 01-SEP-05:02 0.98
October 0.834408E+09 0.37 1259.46 01-OCT-08:62 0.99
November 0.778805E+09 0.36 1259.46 01-NOV-06:02 0.99
December 0.810622E+09 0.36 841.66 07-DEC-07:03 0.83
           
Annual Sum or Average 0.986651E+10 0.37      
Minimum of Months 0.734013E+09 0.36 841.66   0.83
Maximum of Months 0.901318E+09 0.39 1259.46   1.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.141627E+10 0.00 0.00
February 0.00 0.00 0.00 0.124115E+10 0.00 0.00
March 0.00 0.00 0.00 0.161838E+10 0.00 0.00
April 0.00 0.00 0.00 0.371329E+10 0.00 0.00
May 0.00 0.00 0.00 0.524409E+10 0.00 0.00
June 0.00 0.00 0.00 0.784383E+10 0.00 0.00
July 0.00 0.00 0.00 0.778200E+10 0.00 0.00
August 0.00 0.00 0.00 0.741352E+10 0.00 0.00
September 0.00 0.00 0.00 0.624498E+10 0.00 0.00
October 0.00 0.00 0.00 0.331106E+10 0.00 0.00
November 0.00 0.00 0.00 0.152687E+10 0.00 0.00
December 0.00 0.00 0.00 0.139273E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.487482E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.124115E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.784383E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.121287E+11 0.00 0.00
February 0.00 0.00 0.00 0.809627E+10 0.00 0.00
March 0.00 0.00 0.00 0.128431E+11 0.00 0.00
April 0.00 0.00 0.00 0.256431E+11 0.00 0.00
May 0.00 0.00 0.00 0.320118E+11 0.00 0.00
June 0.00 0.00 0.00 0.420657E+11 0.00 0.00
July 0.00 0.00 0.00 0.411972E+11 0.00 0.00
August 0.00 0.00 0.00 0.407106E+11 0.00 0.00
September 0.00 0.00 0.00 0.343729E+11 0.00 0.00
October 0.00 0.00 0.00 0.219303E+11 0.00 0.00
November 0.00 0.00 0.00 0.125290E+11 0.00 0.00
December 0.00 0.00 0.00 0.995779E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.293487E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.809627E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.420657E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.222301E+10 0.00 0.00
February 0.00 0.00 0.00 0.104979E+10 0.00 0.00
March 0.00 0.00 0.00 0.179506E+10 0.00 0.00
April 0.00 0.00 0.00 0.358998E+10 0.00 0.00
May 0.00 0.00 0.00 0.418507E+10 0.00 0.00
June 0.00 0.00 0.00 0.550587E+10 0.00 0.00
July 0.00 0.00 0.00 0.561490E+10 0.00 0.00
August 0.00 0.00 0.00 0.581708E+10 0.00 0.00
September 0.00 0.00 0.00 0.528837E+10 0.00 0.00
October 0.00 0.00 0.00 0.363472E+10 0.00 0.00
November 0.00 0.00 0.00 0.218054E+10 0.00 0.00
December 0.00 0.00 0.00 0.161134E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.424957E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.104979E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.581708E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.165306E+10 0.00 0.00
February 0.00 0.00 0.00 0.797257E+09 0.00 0.00
March 0.00 0.00 0.00 0.129386E+10 0.00 0.00
April 0.00 0.00 0.00 0.280227E+10 0.00 0.00
May 0.00 0.00 0.00 0.329438E+10 0.00 0.00
June 0.00 0.00 0.00 0.448353E+10 0.00 0.00
July 0.00 0.00 0.00 0.459268E+10 0.00 0.00
August 0.00 0.00 0.00 0.475159E+10 0.00 0.00
September 0.00 0.00 0.00 0.431233E+10 0.00 0.00
October 0.00 0.00 0.00 0.288046E+10 0.00 0.00
November 0.00 0.00 0.00 0.162861E+10 0.00 0.00
December 0.00 0.00 0.00 0.121027E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.337003E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.797257E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.475159E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135988E+10 0.188342E+09 0.803926E+09 0.00 0.00 0.00 0.00 0.00
February 0.124115E+10 0.00 0.978745E+09 0.00 0.00 0.00 0.00 0.00
March 0.137761E+10 0.827511E+09 0.579737E+09 0.00 0.00 0.00 0.00 0.00
April 0.130989E+10 0.834454E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135453E+10 0.135107E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142771E+10 0.217983E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141282E+10 0.231182E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141076E+10 0.217266E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132101E+10 0.181892E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.134079E+10 0.707772E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.129365E+10 0.818145E+09 0.143308E+09 0.00 0.00 0.00 0.00 0.00
December 0.139036E+10 7817712.55 0.182236E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162402E+11 0.115607E+12 0.432808E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142771E+10 0.231182E+11 0.182236E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.868243E+10 0.114234E+11 0.337000E+09 0.00 0.00 0.00 0.00 0.00
February 0.787057E+10 0.741630E+09 8608977.11 0.00 0.00 0.00 0.00 0.00
March 0.882654E+10 0.133434E+11 28902030.23 0.00 0.00 0.00 0.00 0.00
April 0.850099E+10 0.563673E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.881892E+10 0.745975E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.945538E+10 0.994320E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.927261E+10 0.104386E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.939239E+10 0.102823E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.865482E+10 0.864348E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.869377E+10 0.441825E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.836282E+10 0.140166E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.870943E+10 0.410177E+10 0.534465E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105241E+12 0.611850E+12 0.908976E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.787057E+10 0.741630E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945538E+10 0.104386E+12 0.534465E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.966766E+09 0.512293E+10 5120865.74 0.00 0.00 0.00 0.00 0.00
February 0.877616E+09 0.658099E+09 5429334.55 0.00 0.00 0.00 0.00 0.00
March 0.984159E+09 0.312567E+10 9481093.02 0.00 0.00 0.00 0.00 0.00
April 0.949100E+09 0.992184E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.981908E+09 0.115131E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.104271E+10 0.151175E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.104766E+10 0.165690E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109937E+10 0.172453E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.104020E+10 0.161682E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100566E+10 0.103304E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.933414E+09 0.509346E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.968968E+09 0.258960E+10 10120043.46 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118975E+11 0.113455E+12 30151336.77 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.877616E+09 0.658099E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109937E+10 0.172453E+11 10120043.46 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.807694E+09 0.337923E+10 21191410.40 0.00 0.00 0.00 0.00 0.00
February 0.734013E+09 0.237342E+09 48285178.79 0.00 0.00 0.00 0.00 0.00
March 0.823579E+09 0.176140E+10 74033980.78 0.00 0.00 0.00 0.00 0.00
April 0.790750E+09 0.739886E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.817573E+09 0.872063E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.852976E+09 0.121978E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.859791E+09 0.134791E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.901318E+09 0.140150E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.854985E+09 0.130806E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.834408E+09 0.794076E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.778805E+09 0.341160E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.810622E+09 0.158452E+10 64384405.50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.986651E+10 0.872067E+11 0.207895E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.734013E+09 0.237342E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.901318E+09 0.140150E+11 74033980.78 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135988E+10 0.00 0.00 0.00 56391044.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137761E+10 0.00 0.00 0.00 0.240771E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130989E+10 0.00 0.00 0.00 0.240340E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135453E+10 0.00 0.00 0.00 0.388956E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142771E+10 0.00 0.00 0.00 0.641611E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141282E+10 0.00 0.00 0.00 0.636919E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141076E+10 0.00 0.00 0.00 0.600276E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132101E+10 0.00 0.00 0.00 0.492397E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.134079E+10 0.00 0.00 0.00 0.197027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.129365E+10 0.00 0.00 0.00 0.233218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139036E+10 0.00 0.00 0.00 2366803.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.162402E+11 0.00 0.00 0.00 0.325080E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142771E+10 0.00 0.00 0.00 0.641611E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.868243E+10 0.00 0.00 0.00 0.344625E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.787057E+10 0.00 0.00 0.00 0.225707E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.882654E+10 0.00 0.00 0.00 0.401657E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.850099E+10 0.00 0.00 0.00 0.171422E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.881892E+10 0.00 0.00 0.00 0.231929E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.945538E+10 0.00 0.00 0.00 0.326104E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.927261E+10 0.00 0.00 0.00 0.319245E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.939239E+10 0.00 0.00 0.00 0.313182E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.865482E+10 0.00 0.00 0.00 0.257180E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.869377E+10 0.00 0.00 0.00 0.132366E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.836282E+10 0.00 0.00 0.00 0.416613E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.870943E+10 0.00 0.00 0.00 0.124837E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.105241E+12 0.00 0.00 0.00 0.188246E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.787057E+10 0.00 0.00 0.00 0.225707E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945538E+10 0.00 0.00 0.00 0.326104E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.966766E+09 0.00 0.00 0.00 0.125624E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.877616E+09 0.00 0.00 0.00 0.172175E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.984159E+09 0.00 0.00 0.00 0.810898E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.949100E+09 0.00 0.00 0.00 0.264088E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.981908E+09 0.00 0.00 0.00 0.320316E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.104271E+10 0.00 0.00 0.00 0.446316E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.104766E+10 0.00 0.00 0.00 0.456724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109937E+10 0.00 0.00 0.00 0.471771E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.104020E+10 0.00 0.00 0.00 0.424818E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.100566E+10 0.00 0.00 0.00 0.262906E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.933414E+09 0.00 0.00 0.00 0.124713E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.968968E+09 0.00 0.00 0.00 0.642370E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.118975E+11 0.00 0.00 0.00 0.305982E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.877616E+09 0.00 0.00 0.00 0.172175E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109937E+10 0.00 0.00 0.00 0.471771E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.807694E+09 0.00 0.00 0.00 0.845366E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.734013E+09 0.00 0.00 0.00 63244345.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.823579E+09 0.00 0.00 0.00 0.470284E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.790750E+09 0.00 0.00 0.00 0.201152E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.817573E+09 0.00 0.00 0.00 0.247680E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.852976E+09 0.00 0.00 0.00 0.363056E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.859791E+09 0.00 0.00 0.00 0.373289E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.901318E+09 0.00 0.00 0.00 0.385027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.854985E+09 0.00 0.00 0.00 0.345734E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.834408E+09 0.00 0.00 0.00 0.204606E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.778805E+09 0.00 0.00 0.00 0.849803E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.810622E+09 0.00 0.00 0.00 0.399644E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.986651E+10 0.00 0.00 0.00 0.238338E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.734013E+09 0.00 0.00 0.00 63244345.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.901318E+09 0.00 0.00 0.00 0.385027E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BACK_SPACE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145701E+10 9772790.00 0.00 67393.32 7549452.63 0.363041E+09 66764810.77 0.00 0.22
February 0.200045E+10 0.00 0.00 0.00 0.00 0.655689E+09 0.00 0.00 0.20
March 0.151602E+10 64959854.73 0.00 567689.56 7596163.48 0.365564E+09 0.213702E+09 0.00 0.24
April 0.159433E+09 0.114291E+10 0.00 3938718.51 28911860.18 0.00 0.795331E+09 0.00 0.31
May 31307080.41 0.196755E+10 0.00 4129851.64 33011409.91 0.00 0.409461E+09 0.00 0.27
June 902119.89 0.366976E+10 0.00 3539278.50 30676557.73 0.00 0.187911E+09 0.00 0.25
July 1985191.59 0.452007E+10 0.00 1909642.96 47753355.49 0.00 73086869.37 0.00 0.24
August 3207723.03 0.438075E+10 0.00 3101225.26 41037668.04 0.00 0.143513E+09 0.00 0.26
September 7950652.91 0.332614E+10 0.00 3608275.85 40487271.41 0.00 0.206855E+09 0.00 0.29
October 0.597172E+09 0.100158E+10 0.00 4146181.99 10856246.61 0.00 0.109648E+10 0.00 0.34
November 0.150029E+10 74903373.59 0.00 1345601.27 5764239.65 79966793.33 0.861219E+09 0.00 0.27
December 0.168905E+10 0.00 68240.36 0.00 23933115.88 0.100676E+10 0.00 2380.55 0.21
                   
Annual Sum or Average 0.896478E+10 0.201584E+11 68240.36 26353858.86 0.277577E+09 0.247102E+10 0.405433E+10 2380.55 0.26
Minimum of Months 902119.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20
Maximum of Months 0.200045E+10 0.452007E+10 68240.36 4146181.99 47753355.49 0.100676E+10 0.109648E+10 2380.55 0.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.703640E+10 0.00 0.00 36180411.69 0.00 0.237592E+09 0.176130E+11 0.00 0.48
February 0.117005E+11 0.00 0.00 18150435.69 0.00 0.00 0.178123E+11 0.00 0.39
March 0.624089E+10 12392079.18 0.00 36806741.72 0.00 0.00 0.204070E+11 0.00 0.50
April 0.484679E+09 0.294935E+10 0.00 49986533.07 29104836.04 0.00 0.772235E+10 0.00 0.41
May 0.323117E+09 0.665775E+10 0.00 29001011.68 74025315.27 0.00 0.294627E+10 0.00 0.37
June 26472077.16 0.167457E+11 0.00 13587671.01 0.127183E+09 0.00 0.110941E+10 0.00 0.34
July 7692046.54 0.229458E+11 0.00 5845009.65 0.238024E+09 0.00 0.367642E+09 0.00 0.33
August 30766321.61 0.223996E+11 0.00 10310656.09 0.208391E+09 0.00 0.703455E+09 0.00 0.36
September 59050598.23 0.162617E+11 0.00 12417805.96 0.202588E+09 0.00 0.924580E+09 0.00 0.38
October 0.202366E+10 0.388858E+10 0.00 48790422.42 49388053.29 0.00 0.136048E+11 0.00 0.48
November 0.511533E+10 69523054.72 0.00 45845174.83 3453004.81 0.00 0.213008E+11 0.00 0.51
December 0.145124E+11 5121314.79 0.00 19596818.52 0.00 0.128639E+09 0.147052E+11 0.00 0.41
                   
Annual Sum or Average 0.475609E+11 0.919355E+11 0.00 0.326519E+09 0.932157E+09 0.366231E+09 0.119217E+12 0.00 0.41
Minimum of Months 7692046.54 0.00 0.00 5845009.65 0.00 0.00 0.367642E+09 0.00 0.33
Maximum of Months 0.145124E+11 0.229458E+11 0.00 49986533.07 0.238024E+09 0.237592E+09 0.213008E+11 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: POINT_OF_SALE

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.211059E+09 148609.13 0.00 17764071.59 0.00 3222784.00 0.401389E+10 0.00 0.96
February 0.503951E+09 0.00 0.00 8091149.04 0.00 4144818.71 0.440751E+10 0.00 0.81
March 0.365334E+09 3576522.42 0.00 9523109.97 0.00 6175957.21 0.344297E+10 0.00 0.87
April 23054258.09 0.321286E+09 0.00 8192123.52 1130281.56 0.00 0.109156E+10 0.00 0.56
May 19328741.92 0.695813E+09 0.00 3604109.02 3033467.63 0.00 0.413801E+09 0.00 0.44
June 690807.00 0.166731E+10 0.00 1742060.10 4433188.29 0.00 0.144935E+09 0.00 0.38
July 281239.73 0.242523E+10 0.00 1150257.84 8652952.17 0.00 53764736.49 0.00 0.36
August 2658648.61 0.246115E+10 0.00 1893407.82 6628634.83 0.00 0.125281E+09 0.00 0.42
September 2196709.60 0.187218E+10 0.00 2866241.72 6058488.84 0.00 0.212276E+09 0.00 0.48
October 62067891.24 0.442558E+09 0.00 13188597.66 1111893.54 0.00 0.238727E+10 0.00 0.79
November 0.119566E+09 19017766.85 0.00 16765569.57 0.00 0.00 0.432565E+10 0.00 0.99
December 0.471113E+09 821151.55 0.00 14085221.75 0.00 619753.11 0.486041E+10 0.00 0.91
                   
Annual Sum or Average 0.178130E+10 0.990910E+10 0.00 98865919.59 31048906.85 14163313.04 0.254793E+11 0.00 0.66
Minimum of Months 281239.73 0.00 0.00 1150257.84 0.00 0.00 53764736.49 0.00 0.36
Maximum of Months 0.503951E+09 0.246115E+10 0.00 17764071.59 8652952.17 6175957.21 0.486041E+10 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_RETAIL

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.447292E+09 47356.52 0.00 10840617.02 0.00 10623229.25 0.273584E+10 0.00 0.74
February 0.961684E+09 0.00 0.00 3555967.13 0.00 29563905.35 0.235958E+10 0.00 0.53
March 0.633701E+09 2804513.02 0.00 4519034.29 0.00 37810091.98 0.197990E+10 0.00 0.61
April 56008615.82 0.314072E+09 0.00 5218849.28 1828651.21 0.00 0.739093E+09 0.00 0.47
May 22062543.93 0.688801E+09 0.00 2406438.10 6430532.70 0.00 0.265248E+09 0.00 0.39
June 2359153.27 0.165626E+10 0.00 1214375.23 8159358.78 0.00 98881065.32 0.00 0.36
July 1212798.81 0.227970E+10 0.00 823916.64 13427607.44 0.00 39275018.46 0.00 0.34
August 2638149.60 0.228530E+10 0.00 1519168.30 10673079.93 0.00 98955303.76 0.00 0.39
September 2790764.81 0.171650E+10 0.00 2253229.77 7977718.47 0.00 0.162346E+09 0.00 0.44
October 0.150535E+09 0.416141E+09 0.00 8914553.86 1463251.62 0.00 0.174038E+10 0.00 0.64
November 0.343469E+09 11133889.76 0.00 10467462.41 125412.11 0.00 0.300995E+10 0.00 0.75
December 0.808784E+09 720391.10 0.00 7595044.19 0.00 35795538.12 0.295597E+10 0.00 0.65
                   
Annual Sum or Average 0.343254E+10 0.937149E+10 0.00 59328656.21 50085612.27 0.113793E+09 0.161854E+11 0.00 0.53
Minimum of Months 1212798.81 0.00 0.00 823916.64 0.00 0.00 39275018.46 0.00 0.34
Maximum of Months 0.961684E+09 0.228530E+10 0.00 10840617.02 13427607.44 37810091.98 0.300995E+10 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONT_ENTRY

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:31:08

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.160798E+12 0.568492E+10 0.00 0.342431E+11 0.260083E+11
February 0.193051E+12 0.458306E+10 0.00 0.404652E+11 0.235855E+10
March 0.262333E+12 0.527303E+10 0.00 0.351692E+11 0.247734E+11
April 0.337834E+12 0.155068E+10 0.00 0.635026E+10 0.106230E+12
May 0.346140E+12 0.118454E+09 0.00 -0.565668E+10 0.141104E+12
June 0.362914E+12 -0.191000E+10 0.00 -0.223179E+11 0.195672E+12
July 0.339677E+12 -0.280240E+10 0.00 -0.319239E+11 0.204155E+12
August 0.300535E+12 -0.195447E+10 0.00 -0.306662E+11 0.201722E+12
September 0.241804E+12 -0.112531E+10 0.00 -0.218344E+11 0.172229E+12
October 0.209598E+12 0.298469E+10 0.00 0.159257E+11 0.894135E+11
November 0.174774E+12 0.540122E+10 0.00 0.365468E+11 0.298735E+11
December 0.126212E+12 0.602680E+10 0.00 0.411854E+11 0.111881E+11
           
Annual Sum or Average 0.305567E+13 0.238307E+11 0.00 0.974864E+11 0.120473E+13
Minimum of Months 0.126212E+12 -0.280240E+10 0.00 -0.319239E+11 0.235855E+10
Maximum of Months 0.362914E+12 0.602680E+10 0.00 0.411854E+11 0.204155E+12