Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:30:50
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1193.54 | 520.29 | 520.29 |
Net Site Energy | 1193.54 | 520.29 | 520.29 |
Total Source Energy | 3545.00 | 1545.34 | 1545.34 |
Net Source Energy | 3545.00 | 1545.34 | 1545.34 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 345.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 87.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1080.75 | 112.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 345.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 68.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 135.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 87.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 345.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 316.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 68.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 135.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 87.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.88 | 49.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 93.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 471.12 | 49.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.88 | 49.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 93.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 471.12 | 49.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1080.750 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1080.750 | 100.00 |
Total On-Site and Utility Electric Sources | 1080.750 | 100.00 |
Total Electricity End Uses | 1080.750 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 291.26 | 89.31 |
Air to Air Heat Recovery for Heating | 34.85 | 10.69 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 326.11 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3366.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 6.8133 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.4031 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 15.4031 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 15.4031 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 7.9050 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.9414 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.9414 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 6.8133 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 15.4031 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 15.4031 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 15.4031 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 7.9050 | 6.19 | 0.0000 | |
Total | 2293.99 | 13.9414 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 13.9414 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 13.9414 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-SEP-16:00 | 11-MAR-12:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 42914.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41454.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25687.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7795.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4882.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87114.30 | 47797.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 42914.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 41454.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25687.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7795.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4882.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 27.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1001.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 216.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 429.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 61.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 94.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3422.74 | 122.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 11.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 477.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 436.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 94.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 41.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1492.04 | 53.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 11.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 477.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 436.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 94.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 41.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1492.04 | 53.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.67 |
CORE_RETAIL DIRECT AIR | 7.69 |
POINT_OF_SALE DIRECT AIR | 1.17 |
FRONT_RETAIL DIRECT AIR | 0.987649 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.59 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 1.59 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 36865.52 |
PSZ-AC:1 HEATING COIL | 43067.71 |
PSZ-AC:2 HEATING COIL | 216265.56 |
PSZ-AC:3 HEATING COIL | 30518.73 |
PSZ-AC:4 HEATING COIL | 26287.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.67 | 1.67 | 1.67 | 1.67 | 1.68 | 1.68 | 1.00 | 0.994155 | 1.68 |
PSZ-AC:2 | 7.69 | 7.69 | 7.69 | 7.69 | 7.89 | 7.89 | 1.00 | 0.974505 | 7.89 |
PSZ-AC:3 | 1.17 | 1.17 | 1.17 | 1.17 | 1.19 | 1.19 | 1.00 | 0.982753 | 1.19 |
PSZ-AC:4 | 0.987649 | 0.987649 | 0.987649 | 0.987649 | 0.987649 | 0.987649 | 1.00 | 1.00 | 0.987649 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.68 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 7.89 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.19 | 0.178122 |
PSZ-AC:4_OA_CONTROLLER | 0.987649 | 0.178122 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1793.20 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.89 | 13297.45 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.19 | 1319.41 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.987649 | 1093.48 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.11 | 33191.16 | 43067.71 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.89 | 7.89 | 7.89 | 5.21 | 194085.35 | 216265.56 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.786527 | 25727.76 | 30518.73 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.987649 | 0.987649 | 0.987649 | 0.651848 | 22417.17 | 26287.80 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 1.68 | 0.837907 | 1.12 | 33191.16 | 16595.58 | 0.780280 | 0.780280 |
PSZ-AC:2 COOLING COIL | 7.89 | 3.95 | 5.26 | 194085.35 | 97042.68 | 0.704500 | 0.704500 |
PSZ-AC:3 COOLING COIL | 1.19 | 0.595854 | 0.794473 | 25727.76 | 12863.88 | 0.746900 | 0.746900 |
PSZ-AC:4 COOLING COIL | 0.987650 | 0.493824 | 0.658433 | 22417.17 | 11208.58 | 0.730140 | 0.730140 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC:2 OA HEAT RECOVERY | 1.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 6.813 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.883 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.923 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 7.905 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.905 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 2588.286 | 6.813 | 316.489 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2588.286 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 24652.462 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24652.462 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 2322.948 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.948 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 2322.948 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.948 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 94.860 | 7.905 | 48.947 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 94.860 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.253 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6308 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.15678677E-14 | 0.41668067E-16 | -0.13443164E-09 | -0.41464653E-17 |
25 | 8 | 0.19720454E-07 | 0.16552409E-12 | 0.35477227E-03 | -0.22422834E-09 |
26 | 7 | -0.11553319E-01 | 0.88069696E-08 | -0.22094443E-01 | 0.13136543E-03 |
27 | 6 | 0.38664784 | 0.30990522E-05 | 0.45613010 | -0.45273053E-02 |
28 | 5 | -5.0080263 | 0.11685699E-03 | -4.3185286 | 0.60920489E-01 |
29 | 4 | 32.195305 | 0.96442504E-03 | 20.960285 | -0.41140105 |
30 | 3 | -109.50767 | 0.21185031E-02 | -54.674808 | 1.4903667 |
31 | 2 | 195.42750 | 0.12000320E-02 | 77.004857 | -2.8736635 |
32 | 1 | -170.53507 | 0.12893930E-03 | -55.002816 | 2.7345555 |
33 | 0 | 57.057407 | 0.73918525E-06 | 15.601154 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 36 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 37 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CORE_RETAIL | 16 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.237 | 6.240E-004 | 2.832E-004 | 0.368 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.203 | 1.270E-004 | 1.032E-004 | 7.495E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 1.389E-002 | 1.157E-003 | 3.817E-004 | 0.683 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.7348E-004 |
2 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.8822E-004 |
3 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5771E-004 |
4 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.4614E-004 |
5 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5209E-004 |
6 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.4445E-004 |
7 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.8996E-004 |
8 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.9043E-004 |
9 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.6179E-004 |
10 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.1358E-004 |
11 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.2501E-004 |
12 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.9041E-004 |
13 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.1674E-004 |
14 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.9702E-004 |
15 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 3.3656E-004 |
16 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.5584E-004 |
17 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.7440E-004 |
18 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4503E-004 |
19 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.3621E-004 |
20 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.3737E-004 |
21 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.3883E-004 |
22 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4108E-004 |
23 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 3.6506E-004 |
24 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.5288E-004 |
25 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.8650E-004 |
26 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1812E-004 |
27 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.6961E-004 |
28 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1613E-004 |
29 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.7560E-004 |
30 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1849E-004 |
31 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 2.1191E-004 |
32 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.2226E-004 |
33 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.4745E-004 |
34 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.6149E-003 |
35 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.4024E-004 |
36 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.8677E-003 |
37 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.6476E-004 |
38 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.2043E-003 |
39 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.0604E-004 |
40 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 4.8996E-004 |
41 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 7.6759E-004 |
42 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 6.8552E-004 |
43 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 8.1701E-004 |
44 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 7.5200E-004 |
45 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 7.5560E-004 |
46 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 5.8326E-004 |
47 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.0930E-004 |
48 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 2.9411E-004 |
49 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.4864E-004 |
50 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3353E-004 |
51 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.7602E-004 |
52 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3308E-004 |
53 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.0695E-004 |
54 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3348E-004 |
55 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.3470E-004 |
56 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2341E-004 |
57 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.6145E-003 |
58 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.2064E-004 |
59 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.8808E-003 |
60 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.2291E-004 |
61 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.1423E-003 |
62 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1355E-004 |
63 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 4.5161E-004 |
64 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.5950E-004 |
65 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.3169E-003 |
66 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.2680E-003 |
67 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.2839E-003 |
68 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.2778E-003 |
69 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.1242E-003 |
70 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.5824E-003 |
71 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.0002E-003 |
72 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.1197E-003 |
73 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.6498E-004 |
74 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 7.4485E-003 |
75 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.3154E-004 |
76 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 8.3391E-003 |
77 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.4138E-004 |
78 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 7.8732E-003 |
79 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.3409E-004 |
80 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.5970E-003 |
81 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 5.7212E-003 |
82 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.6017E-004 |
83 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 6.3530E-003 |
84 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.4907E-004 |
85 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 6.1684E-003 |
86 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.8682E-004 |
87 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.1741E-003 |
88 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.3050E-004 |
89 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.8474E-004 |
90 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3792E-004 |
91 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.6900E-004 |
92 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3511E-004 |
93 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 8.3866E-004 |
94 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.4097E-004 |
95 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0842E-004 |
96 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3229E-004 |
97 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 9.9500E-004 |
98 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.8506E-004 |
99 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 8.3055E-004 |
100 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.0892E-004 |
101 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.1372E-003 |
102 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 7.3225E-004 |
103 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 2.4124E-003 |
104 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 9.7824E-004 |
105 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.9455E-004 |
106 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.5066E-003 |
107 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.5741E-004 |
108 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.2690E-003 |
109 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.9950E-004 |
110 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.7921E-003 |
111 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 4.0382E-004 |
112 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 4.1990E-003 |
113 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.2908E-003 |
114 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.0528E-004 |
115 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.0963E-003 |
116 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.8984E-004 |
117 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.6051E-003 |
118 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2000E-004 |
119 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 3.2416E-003 |
120 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2265E-004 |
121 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.9663E-004 |
122 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2983E-004 |
123 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.5068E-004 |
124 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2648E-004 |
125 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 4.7348E-004 |
126 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3201E-004 |
127 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 5.5411E-004 |
128 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3150E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 19744.91294 | 23693.89553 | 1.38835 | 1.66602 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 20054.51452 | 24065.41743 | 0.84305 | 1.01166 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 90824.41170 | 108989.29405 | 6.40981 | 7.69177 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
4 | CORE_RETAIL | Heating | 51808.07281 | 62169.68738 | 2.14425 | 2.57310 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13644.24619 | 16373.09543 | 0.97596 | 1.17115 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
6 | POINT_OF_SALE | Heating | 9696.72223 | 11636.06667 | 0.40934 | 0.49121 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11206.02988 | 13447.23585 | 0.82304 | 0.98765 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
8 | FRONT_RETAIL | Heating | 9691.12882 | 11629.35459 | 0.40910 | 0.49092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 30712.55707 | 36855.06849 | 1.32314 | 1.58777 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 23771.76 | 1.67581 | 1.67581 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 27942.62 | 1.01166 | 1.01166 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 125418.54 | 7.89300 | 7.89300 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 96834.99 | 2.57310 | 2.57310 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 18130.92 | 1.19171 | 1.19171 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 14841.95 | 0.49121 | 0.49121 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 15395.51 | 0.98765 | 0.98765 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 14835.26 | 0.49092 | 0.49092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.66602 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.69177 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17115 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98765 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.58777 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 1.58777 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 36865.52473 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.66602 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.66602 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.66602 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66602 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67581 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67581 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99416 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.69177 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.69177 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.69177 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.69177 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.89300 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.89300 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97451 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17115 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17115 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17115 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17115 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19171 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19171 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 0.98275 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98765 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98765 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98765 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98765 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98765 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98765 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.67581 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.89300 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.19171 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.98765 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67581 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67581 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1793.20067 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67581 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67581 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67581 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10604 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67581 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83791 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11721 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33191.16000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16595.58000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78028 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78028 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33191.16000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43067.71362 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 43067.71362 |
64 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.89300 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89033 |
66 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC:2 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.89033 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.89300 |
68 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13297.45136 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.89300 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.89300 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.89300 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.20938 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.89300 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.94650 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.26200 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 194085.35000 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 97042.67500 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70450 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70450 |
80 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 194085.35000 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 216265.56045 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
84 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 216265.56045 |
85 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19171 |
86 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
87 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19171 |
88 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1319.40912 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19171 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19171 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19171 |
92 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78653 |
93 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19171 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59585 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79447 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25727.76000 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12863.88000 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74690 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74690 |
100 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25727.76000 |
101 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30518.72568 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
104 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 30518.72568 |
105 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98765 |
106 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
107 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98765 |
108 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1093.48374 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98765 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98765 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98765 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65185 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98765 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49382 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65843 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22417.17000 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11208.58500 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73014 |
119 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73014 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22417.17000 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26287.79972 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
124 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 26287.79972 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 31874.4 | 11.51 | 11.51 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 187859.7 | 10.84 | 10.84 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 24790.0 | 11.69 | 11.69 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 21639.3 | 11.78 | 11.78 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 1.8048937112E-002 | 5.3444194113E-002 | Pass | Pass | 4.1004753487E-002 | 0.1687982593 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.0673124038E-002 | 0.1418864332 | Pass | Pass | 3.8042590721E-002 | 0.1557945111 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 5.0382752064E-002 | 0.1834001089 | Pass | Pass | 3.5370722652E-002 | 0.1240703794 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 4.2211066057E-002 | 0.1644509117 | Pass | Pass | 4.6810135368E-002 | 0.2220056449 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1651964850 | 0.3804662186 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3407.32 | 16.71 | 0.00 | -420.1 | 1644.48 | 4648.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.227 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.046 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.420 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.861 | 0.251 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.861 | 0.251 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.861 | 0.251 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 107.73 | 3.357 | 0.328 | 0.328 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 107.73 | 3.357 | 0.328 | 0.328 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 6.8133 | 379.89 | 2588.29 | LightsWired | LTG_SCH_BACK | 32.16 | 168.00 | 31.72 | 0.0000 | Y | 15.41 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 15.4031 | 1600.48 | 24652.46 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 51.87 | 0.0000 | Y | 240.03 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 15.4031 | 150.81 | 2322.95 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 15.4031 | 150.81 | 2322.95 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 7.9050 | 12.00 | 94.86 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.22 |
Interior Lighting Total | 13.9414 | 2293.99 | 31981.50 | 316.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.46 | 6163.12 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.46 | 6163.12 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 273.03 | AstronomicalClock | - | 41.73 | 41.73 | 2.14 | |
EXTERIOR_LIGHTS_B | 4967.84 | AstronomicalClock | - | 83.73 | 71.13 | 66.33 | |
Exterior Lighting Total | 5240.87 | 68.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33191.16 | 25898.40 | 7292.76 | 0.78 | 3.80 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 194085.35 | 136733.13 | 57352.22 | 0.70 | 3.40 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25727.76 | 19216.06 | 6511.70 | 0.75 | 3.80 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22417.17 | 16367.67 | 6049.50 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 31874.4 | 11.51 | 11.51 | ||||
PSZ-AC:2 COOLING COIL | 187859.7 | 10.84 | 10.84 | ||||
PSZ-AC:3 COOLING COIL | 24790.0 | 11.69 | 11.69 | ||||
PSZ-AC:4 COOLING COIL | 21639.3 | 11.78 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 36865.52 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 43067.71 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 216265.56 | 0.80 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 30518.73 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 26287.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 1.59 | 147.52 | 92.91 | 1.00 | 3.74 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.68 | 1793.20 | 1070.05 | 1.00 | 1.34 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.89 | 13297.45 | 1684.71 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1319.41 | 1107.16 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1093.48 | 1107.16 | 1.00 | 1.41 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19744.91 | 23693.90 | 62.37 | 1.388 | 1.666 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00915 | 28.05 | 0.01653 | 0.232 | 0.00 |
CORE_RETAIL | 90824.41 | 108989.29 | 68.10 | 6.410 | 7.692 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00965 | 28.05 | 0.01653 | 1.890 | 0.00 |
POINT_OF_SALE | 13644.25 | 16373.10 | 108.57 | 0.976 | 1.171 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00911 | 28.05 | 0.01653 | 0.178 | 0.00 |
FRONT_RETAIL | 11206.03 | 13447.24 | 89.17 | 0.823 | 0.988 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00917 | 33.90 | 0.01654 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 0.00 | 33.71 | 0.01659 | 33.90 | 0.01654 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20054.51 | 24065.42 | 63.35 | 0.843 | 1.012 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00753 | 4.60 | 0.00526 | 0.232 | 0.00 |
CORE_RETAIL | 51808.07 | 62169.69 | 38.84 | 2.144 | 2.573 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00777 | 4.60 | 0.00526 | 1.890 | 0.00 |
POINT_OF_SALE | 9696.72 | 11636.07 | 77.16 | 0.409 | 0.491 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00763 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_RETAIL | 9691.13 | 11629.35 | 77.11 | 0.409 | 0.491 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00763 | 4.60 | 0.00526 | 0.178 | 0.00 |
FRONT_ENTRY | 30712.56 | 36855.07 | 3071.26 | 1.323 | 1.588 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.08 | 0.00655 | 4.60 | 0.00526 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.68 | 1.68 | 1.01 | 1.01 | 1.6758 | 1.6660 | 1.6758 | 0.9942 | 1.0000 |
PSZ-AC:2 | 7.89 | 7.89 | 2.57 | 2.57 | 7.8930 | 7.6918 | 7.8930 | 0.9745 | 1.0000 |
PSZ-AC:3 | 1.19 | 1.19 | 0.49 | 0.49 | 1.1917 | 1.1712 | 1.1917 | 0.9828 | 1.0000 |
PSZ-AC:4 | 0.99 | 0.99 | 0.49 | 0.49 | 0.9876 | 0.9876 | 0.9876 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 36865.525 | 36865.525 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36865.52 | 36865.52 | 1.587767 | 21.08 | 13.51 | 0.00654819 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.08 | 0.00654819 | 42.1989 | 36855.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 33191.160 | 25898.398 | 1.675810 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 16595.58 | 12905.40 | 1.117207 | 25.40 | 18.18 | 0.01008234 | 12.80 | 12.09 | 0.00850000 | 28.55 | 0.01652632 | 23.72 | 20.7285 | 23.89 | 0.00904906 | 48.9537 | 19744.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 43067.714 | 43067.714 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43067.71 | 43067.71 | 1.675814 | 18.63 | 13.19 | 0.00721396 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 13.8190 | 21.11 | 0.00752773 | 48.3362 | 20054.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 194085.350 | 136733.129 | 7.893000 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 97042.68 | 69809.87 | 5.262000 | 27.73 | 19.66 | 0.01101791 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 35.9241 | 23.89 | 0.00920642 | 49.7970 | 86789.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 216265.560 | 216265.560 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 216265.56 | 216265.56 | 7.892999 | 16.85 | 12.42 | 0.00716792 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 23.9494 | 21.11 | 0.00776965 | 49.8677 | 51808.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 25727.760 | 19216.064 | 1.191710 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 12863.88 | 10010.67 | 0.794473 | 26.28 | 18.54 | 0.01017674 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 22.4201 | 23.89 | 0.00905913 | 49.0127 | 13521.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 30518.726 | 30518.726 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30518.73 | 30518.73 | 1.191707 | 18.49 | 13.20 | 0.00727931 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 14.9468 | 21.11 | 0.00763467 | 49.0144 | 9696.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 22417.170 | 16367.673 | 0.987650 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 11208.58 | 8408.11 | 0.658433 | 26.59 | 18.90 | 0.01050013 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.0523 | 23.89 | 0.00917196 | 49.6143 | 11206.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 26287.800 | 26287.800 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26287.80 | 26287.80 | 0.987649 | 17.98 | 12.92 | 0.00720533 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.0349 | 21.11 | 0.00763399 | 49.0101 | 9691.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 36865.525 | 36865.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 1.587767 | 1.91034860 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36865.52 | 36865.52 | 1.0000 | 1.91034860 | 1.587767 | 21.08 | 13.51 | 0.00654819 | 37810.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36865.52 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.08 | 0.00654819 | 21.08 | 0.00654819 | 42.1989 | 36855.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33191.160 | 25898.398 | 1.675810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5826 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675814 | 2.01628446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | Sensible | 16595.58 | 12905.40 | 1.0000 | 1.34418608 | 1.117207 | 25.40 | 18.18 | 0.01008234 | 51216.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16595.58 | 28.55 | 0.01652632 | 23.72 | 0.23158056 | 20.7285 | 23.89 | 0.00904906 | 23.89 | 0.00904906 | 48.9537 | 19744.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43067.714 | 43067.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.675814 | 2.01628446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43067.71 | 43067.71 | 1.0000 | 2.01628446 | 1.675814 | 18.63 | 13.19 | 0.00721396 | 37013.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43067.71 | 4.60 | 0.00525715 | 4.60 | 0.23158056 | 13.8190 | 20.88 | 0.00752773 | 21.11 | 0.00752773 | 48.3362 | 20054.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 194085.350 | 136733.129 | 7.893000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3218 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.892999 | 9.49659539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | Sensible | 97042.68 | 69809.87 | 1.0000 | 6.33106421 | 5.262000 | 27.73 | 19.66 | 0.01101791 | 55985.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97042.68 | 33.90 | 0.01653638 | 25.13 | 1.89032875 | 35.9241 | 23.89 | 0.00920642 | 23.89 | 0.00920642 | 49.7970 | 86789.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 216265.560 | 216265.560 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.892999 | 9.49659539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 216265.56 | 216265.56 | 1.0000 | 9.49659539 | 7.892999 | 16.85 | 12.42 | 0.00716792 | 35077.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 216265.56 | 4.60 | 0.00525715 | 4.60 | 1.89032875 | 23.9494 | 20.70 | 0.00776965 | 21.11 | 0.00776965 | 49.8677 | 51808.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25727.760 | 19216.064 | 1.191710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7580 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.191707 | 1.43382274 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 12863.88 | 10010.67 | 1.0000 | 0.95588401 | 0.794473 | 26.28 | 18.54 | 0.01017674 | 52358.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12863.88 | 33.90 | 0.01653638 | 25.13 | 0.17812154 | 22.4201 | 23.89 | 0.00905913 | 23.89 | 0.00905913 | 49.0127 | 13521.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30518.726 | 30518.726 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.191707 | 1.43382274 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30518.73 | 30518.73 | 1.0000 | 1.43382274 | 1.191707 | 18.49 | 13.20 | 0.00727931 | 37034.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30518.73 | 4.60 | 0.00525715 | 4.60 | 0.17812154 | 14.9468 | 20.93 | 0.00763467 | 21.11 | 0.00763467 | 49.0144 | 9696.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22417.170 | 16367.673 | 0.987650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3592 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.987649 | 1.18830606 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 11208.58 | 8408.11 | 1.0000 | 0.79220519 | 0.658433 | 26.59 | 18.90 | 0.01050013 | 53499.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11208.58 | 33.90 | 0.01653638 | 25.13 | 0.17812154 | 27.0523 | 23.89 | 0.00917196 | 23.89 | 0.00917196 | 49.6143 | 11206.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26287.800 | 26287.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.987649 | 1.18830606 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26287.80 | 26287.80 | 1.0000 | 1.18830606 | 0.987649 | 17.98 | 12.92 | 0.00720533 | 36332.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26287.80 | 4.60 | 0.00525715 | 4.60 | 0.17812154 | 18.0349 | 20.93 | 0.00763399 | 21.11 | 0.00763399 | 49.0101 | 9691.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.68 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 7.89 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.19 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3280.33 | 1724.67 | 448.83 |
CORE_RETAIL | 3716.50 | 643.83 | 116.67 |
POINT_OF_SALE | 3996.17 | 468.00 | 99.50 |
FRONT_RETAIL | 3843.00 | 894.00 | 327.33 |
FRONT_ENTRY | 3522.50 | 4551.83 | 3260.17 |
Facility | 4129.67 | 4737.17 | 3366.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 0.17 | 0.00 | 0.17 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.67 | 0.00 | 0.67 | 0.00 |
Facility | 0.67 | 0.17 | 0.67 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.421 | 0.021 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.821 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.999 | 0.025 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.889 | 0.025 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 35.508 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.353 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.687 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.683 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.683 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.07 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 128.48 | 258.43 | 9762.95 | 1600.48 | 1.8903 | 1.890 |
POINT_OF_SALE | PSZ-AC:3 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_RETAIL | PSZ-AC:4 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 157.72 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 2.492 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 4701131.88 | 0.00 | 4701131.88 | 778733.71 | 5479865.59 | 7303124.67 | 3844.92 | 4432.07 | 483.01 | 5.50 |
CORE_RETAIL | 38589590.49 | 0.00 | 38589590.49 | 667746.76 | 39257337.25 | 59613407.55 | 3846.38 | 3858.90 | 1054.73 | 16.68 |
POINT_OF_SALE | 4446397.25 | 0.00 | 4446397.25 | 355146.83 | 4801544.08 | 5617240.89 | 3838.22 | 3683.76 | 1238.03 | 43.04 |
FRONT_RETAIL | 3942908.56 | 0.00 | 3942908.56 | 355146.83 | 4298055.39 | 5617240.89 | 3842.45 | 3907.53 | 1010.02 | 18.88 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 12445908.58 | 12445908.58 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 51680028.17 | 0.00 | 51680028.17 | 14602682.72 | 66282710.89 | 78597979.65 | 8760.00 | 4561.91 | 1419.96 | 47.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.2655 | 0.0000 | 0.2655 | 0.0135 | 0.2790 | 0.2316 | 0.00 | 4432.07 | 480.93 |
CORE_RETAIL | 2.1799 | 0.0000 | 2.1799 | 0.0115 | 2.1915 | 1.8903 | 0.00 | 3858.90 | 1054.10 |
POINT_OF_SALE | 0.2503 | 0.0000 | 0.2503 | 0.0061 | 0.2564 | 0.1781 | 0.00 | 3683.76 | 1229.24 |
FRONT_RETAIL | 0.2224 | 0.0000 | 0.2224 | 0.0061 | 0.2286 | 0.1781 | 0.00 | 3907.53 | 1005.47 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.6968 | 0.6968 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 2.9181 | 0.0000 | 2.9181 | 0.7341 | 3.6522 | 2.4923 | 4913.00 | 4561.91 | 1409.99 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 6805391.62 | 0.00 | 6805391.62 | 7303124.67 | 3843.88 | 0.00 | 4916.12 | 5.50 |
PSZ-AC:2 | 55862700.69 | 0.00 | 55862700.69 | 59613407.55 | 3845.57 | 0.00 | 4914.43 | 16.68 |
PSZ-AC:3 | 6436732.50 | 0.00 | 6436732.50 | 5617240.89 | 3833.09 | 0.00 | 4926.91 | 43.04 |
PSZ-AC:4 | 5707866.79 | 0.00 | 5707866.79 | 5617240.89 | 3840.59 | 0.00 | 4919.41 | 18.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.3844 | 0.0000 | 0.3844 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 3.1557 | 0.0000 | 3.1557 | 1.8903 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.3623 | 0.0000 | 0.3623 | 0.1781 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.3220 | 0.0000 | 0.3220 | 0.1781 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 4620.44 | 298.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 4457.69 | 472.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 4365.79 | 590.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 4481.34 | 450.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.3677 | 0.6488 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 3.0856 | 3.8493 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.3424 | 0.5210 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.3098 | 0.4488 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 464 |
Defaulted Fields | 432 |
Fields with Defaults | 1357 |
Autosized Fields | 77 |
Autosizable Fields | 183 |
Autocalculated Fields | 78 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
Electricity:Building | 511.33 | 2914.09 | 04-JUN-07:40 | 38307.35 | 02-JAN-16:40 |
Electricity:Zone:BACK_SPACE | 65.40 | 519.98 | 01-JAN-00:10 | 3841.56 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 511.33 | 2914.09 | 04-JUN-07:40 | 38307.35 | 02-JAN-16:40 |
InteriorLights:Electricity | 316.18 | 1118.91 | 04-JUN-07:40 | 27536.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BACK_SPACE | 15.41 | 60.13 | 01-JAN-00:10 | 1082.42 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 316.18 | 1118.91 | 04-JUN-07:40 | 27536.32 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 316.18 | 1118.91 | 04-JUN-07:40 | 27536.32 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 15.41 | 60.13 | 01-JAN-00:10 | 1082.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 316.18 | 1118.91 | 04-JUN-07:40 | 27536.32 | 02-JAN-16:40 |
Electricity:Zone:CORE_RETAIL | 324.33 | 1597.18 | 04-JUN-07:40 | 26839.82 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 240.03 | 821.75 | 04-JUN-07:40 | 22187.22 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 240.03 | 821.75 | 04-JUN-07:40 | 22187.22 | 02-JAN-16:40 |
Electricity:Zone:POINT_OF_SALE | 82.69 | 602.96 | 01-JAN-00:10 | 5011.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 37.71 | 189.21 | 01-JAN-00:10 | 2529.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.22 | 4.74 | 01-JAN-00:10 | 85.37 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
ElectricityPurchased:Plant | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
Cogeneration:ElectricityPurchased | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
General:Cogeneration:ElectricityPurchased | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
ElectricityNet:Plant | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
Cogeneration:ElectricityNet | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
General:Cogeneration:ElectricityNet | 1080.75 | 3119.52 | 04-JUN-06:50 | 87114.30 | 09-SEP-17:00 |
Electricity:HVAC | 500.95 | 0.00 | 01-JAN-00:10 | 63352.82 | 10-SEP-08:10 |
Fans:Electricity | 135.72 | 0.00 | 01-JAN-00:10 | 12053.70 | 10-SEP-08:10 |
General:Fans:Electricity | 135.72 | 0.00 | 01-JAN-00:10 | 12053.70 | 10-SEP-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 345.74 | 0.00 | 01-JAN-00:10 | 49892.81 | 10-SEP-08:10 |
General:Cooling:Electricity | 345.74 | 0.00 | 01-JAN-00:10 | 49892.81 | 10-SEP-08:10 |
ExteriorLights:Electricity | 68.47 | 0.00 | 01-JAN-07:30 | 5240.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 68.47 | 0.00 | 01-JAN-07:30 | 5240.87 | 01-JAN-06:10 |
HeatRecovery:Electricity | 19.49 | 0.00 | 01-JAN-00:10 | 1406.31 | 01-JAN-11:10 |
General:HeatRecovery:Electricity | 19.49 | 0.00 | 01-JAN-00:10 | 1406.31 | 01-JAN-11:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 112.79 | 1862.00 | 12-FEB-20:10 | 47797.03 | 11-MAR-12:30 |
NaturalGas:HVAC | 25.25 | 0.00 | 01-JAN-00:10 | 44089.66 | 05-FEB-09:10 |
Heating:NaturalGas | 25.25 | 0.00 | 01-JAN-00:10 | 44089.66 | 05-FEB-09:10 |
General:Heating:NaturalGas | 25.25 | 0.00 | 01-JAN-00:10 | 44089.66 | 05-FEB-09:10 |
NaturalGas:Plant | 87.54 | 1862.00 | 12-FEB-20:10 | 4933.61 | 23-JAN-12:20 |
WaterSystems:NaturalGas | 87.54 | 1862.00 | 12-FEB-20:10 | 4933.61 | 23-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 87.54 | 1862.00 | 12-FEB-20:10 | 4933.61 | 23-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2510.55 | 0.00 | 01-JAN-00:10 | 324285.97 | 10-SEP-08:10 |
EnergyTransfer:Building | 870.56 | 0.00 | 01-JAN-00:10 | 99933.78 | 19-JUL-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 97.67 | 0.00 | 01-JAN-00:10 | 15677.39 | 10-SEP-08:10 |
Heating:EnergyTransfer | 24.30 | 0.00 | 01-JAN-00:10 | 30978.97 | 20-DEC-18:00 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 1.50 | 0.00 | 01-JAN-00:10 | 12754.77 | 06-FEB-07:10 |
General:Heating:EnergyTransfer | 24.30 | 0.00 | 01-JAN-00:10 | 30978.97 | 20-DEC-18:00 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 1.50 | 0.00 | 01-JAN-00:10 | 12754.77 | 06-FEB-07:10 |
Cooling:EnergyTransfer | 846.26 | 0.00 | 01-JAN-00:10 | 94095.01 | 19-JUL-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 96.17 | 0.00 | 01-JAN-00:10 | 15677.39 | 10-SEP-08:10 |
General:Cooling:EnergyTransfer | 846.26 | 0.00 | 01-JAN-00:10 | 94095.01 | 19-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 96.17 | 0.00 | 01-JAN-00:10 | 15677.39 | 10-SEP-08:10 |
EnergyTransfer:Zone:CORE_RETAIL | 555.38 | 0.00 | 01-JAN-00:10 | 68540.99 | 19-JUL-06:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 4.53 | 0.00 | 01-JAN-00:10 | 9392.52 | 01-MAY-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 4.53 | 0.00 | 01-JAN-00:10 | 9392.52 | 01-MAY-06:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 550.85 | 0.00 | 01-JAN-00:10 | 63443.40 | 19-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 550.85 | 0.00 | 01-JAN-00:10 | 63443.40 | 19-JUL-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 116.20 | 0.00 | 01-JAN-00:10 | 12399.23 | 07-OCT-13:00 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.34 | 0.00 | 01-JAN-00:10 | 3376.37 | 12-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.34 | 0.00 | 01-JAN-00:10 | 3376.37 | 12-MAR-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 115.86 | 0.00 | 01-JAN-00:10 | 12399.23 | 07-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 115.86 | 0.00 | 01-JAN-00:10 | 12399.23 | 07-OCT-13:00 |
EnergyTransfer:Zone:FRONT_RETAIL | 83.77 | 0.00 | 01-JAN-00:10 | 10394.50 | 07-OCT-13:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.39 | 0.00 | 01-JAN-00:10 | 5124.92 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.39 | 0.00 | 01-JAN-00:10 | 5124.92 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 83.38 | 0.00 | 01-JAN-00:10 | 10394.50 | 07-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 83.38 | 0.00 | 01-JAN-00:10 | 10394.50 | 07-OCT-13:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 17.53 | 0.00 | 01-JAN-00:10 | 30978.97 | 20-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 17.53 | 0.00 | 01-JAN-00:10 | 30978.97 | 20-DEC-18:00 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 17.53 | 0.00 | 01-JAN-00:10 | 30978.97 | 20-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 7.65 | 29-JAN-09:20 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 7.65 | 29-JAN-09:20 |
EnergyTransfer:HVAC | 1640.00 | 0.00 | 01-JAN-00:10 | 233287.36 | 10-SEP-08:10 |
HeatingCoils:EnergyTransfer | 20.20 | 0.00 | 01-JAN-00:10 | 35271.72 | 05-FEB-09:10 |
CoolingCoils:EnergyTransfer | 1293.69 | 0.00 | 01-JAN-00:10 | 188943.65 | 10-SEP-08:10 |
HeatRecoveryForHeating:EnergyTransfer | 34.85 | 0.00 | 01-JAN-00:10 | 54840.20 | 09-JAN-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 291.26 | 0.00 | 01-JAN-00:10 | 55073.58 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 1.502 | -96.167 | 0.000 | 0.000 | 4.995 | 15.409 | 49.992 | 0.000 | 0.000 | 0.802 | 27.657 | 0.000 | 0.000 | 0.000 | -4.191 | -0.003 |
CORE_RETAIL | 0.000 | 0.000 | 4.530 | -550.841 | 0.000 | 0.000 | 154.558 | 240.026 | 84.300 | 82.817 | 0.000 | 0.696 | 3.316 | 0.000 | -15.246 | 0.000 | -4.156 | -0.004 |
POINT_OF_SALE | 0.000 | 0.000 | 0.338 | -115.862 | 0.000 | 0.000 | 14.589 | 29.762 | 52.923 | 35.121 | 0.000 | 0.345 | 0.002 | 0.000 | -11.015 | 0.000 | -2.356 | -3.846 |
FRONT_RETAIL | 0.000 | 0.000 | 0.390 | -83.376 | 0.000 | 0.000 | 14.650 | 29.762 | 7.943 | 35.113 | 0.000 | 0.354 | 7.747 | 0.000 | -10.431 | 0.000 | -2.153 | -0.001 |
FRONT_ENTRY | 17.535 | -0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.947 | 1.215 | 0.000 | 6.725 | 0.000 | 1.130 | 0.000 | 0.000 | -2.159 | 0.000 | -23.450 | -1.944 |
Total Facility | 17.535 | -0.000 | 6.760 | -846.246 | 0.000 | 0.000 | 189.740 | 316.175 | 195.158 | 159.776 | 0.000 | 3.328 | 38.722 | 0.000 | -38.851 | 0.000 | -36.305 | -5.798 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -42181.27 | 0.00 | 0.00 | 52.69 | 240.53 | 1226.28 | 0.00 | 0.00 | 0.00 | 40903.56 | 0.00 | -0.00 | 0.00 | -241.79 | 0.00 |
CORE_RETAIL | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 | -229715.67 | 0.00 | 0.00 | 1637.97 | 2259.81 | 1550.87 | 3608.50 | 0.00 | 0.00 | 220958.77 | 0.00 | -0.00 | 0.00 | -300.25 | 0.00 |
POINT_OF_SALE | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 | -29531.74 | 0.00 | 0.00 | 150.36 | 232.29 | 973.63 | 3476.61 | 0.00 | 0.00 | 24858.36 | 0.00 | -0.00 | 0.00 | -159.52 | 0.00 |
FRONT_RETAIL | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 | -28681.15 | 0.00 | 0.00 | 150.42 | 232.29 | 146.13 | 3489.80 | 0.00 | 0.00 | 24821.93 | 0.00 | -0.00 | 0.00 | -159.43 | 0.00 |
FRONT_ENTRY | 29-JAN-09:20 | 0.00 | -15.30 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 9.49 | 0.00 | 910.53 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -785.27 | -135.40 |
Total Facility | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | -325529.27 | 0.00 | 0.00 | 1962.88 | 6119.17 | 4787.13 | 0.00 | 0.00 | 0.00 | 317041.54 | 0.00 | -3693.10 | 0.00 | -688.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 06-FEB-06:02 | 0.00 | 0.00 | 42970.89 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -131.30 | -43512.86 |
CORE_RETAIL | 09-JUL-08:06 | 0.00 | 0.00 | 19891.28 | 0.00 | 0.00 | 0.00 | 1595.70 | 1643.50 | 1550.87 | 4800.36 | 0.00 | 63.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29545.17 |
POINT_OF_SALE | 12-MAR-08:62 | 0.00 | 0.00 | 11360.93 | 0.00 | 0.00 | 0.00 | 208.31 | 232.29 | 973.63 | 256.45 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.30 | -12960.32 |
FRONT_RETAIL | 05-FEB-08:62 | 0.00 | 0.00 | 24169.65 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24.58 | 0.00 | -287.46 | -24046.82 |
FRONT_ENTRY | 20-DEC-18:00 | 30980.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 592.42 | 0.00 | -345.93 | 0.00 | -31392.20 | 0.00 |
Total Facility | 05-FEB-08:62 | 7552.28 | 0.00 | 83304.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.79 | 1795.17 | 3.98 | 0.00 | 0.00 | 0.00 | 0.00 | -1379.08 | 0.00 | -7808.94 | -84997.49 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6660 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.6758 | 0.1382 | 1.0000 | Not calculated | 0.2316 | 0.1382 | ||
PSZ-AC:2 | 7.6918 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.8930 | 0.2395 | 1.0000 | Not calculated | 1.8903 | 0.2395 | ||
PSZ-AC:3 | 1.1712 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.1917 | 0.1495 | 1.0000 | Not calculated | 0.1781 | 0.1495 | ||
PSZ-AC:4 | 0.9876 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 0.9876 | 0.1803 | 1.0000 | Not calculated | 0.1781 | 0.1803 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6660 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.6660 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.1390 | ||
PSZ-AC:2 | 7.6918 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.6918 | 1.0000 | 1.0000 | Not calculated | 1.8903 | 0.2458 | ||
PSZ-AC:3 | 1.1712 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.1712 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1521 | ||
PSZ-AC:4 | 0.9876 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 0.9876 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1803 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8903 | 1.0000 | 1.8903 | 1.000 | 1.8903 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8903 | 1.8903 | 1.8903 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6660 | 1.6660 | 1.6660 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6918 | 7.6918 | 7.6918 | No | 1.8903 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1712 | 1.1712 | 1.1712 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9876 | 0.9876 | 0.9876 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6660 | 1.6758 | 1.6660 | 1.6660 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6918 | 7.8930 | 7.6918 | 7.6918 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.1712 | 1.1917 | 1.1712 | 1.1712 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9876 | 0.9876 | 0.9876 | 0.9876 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6660 | 1.6660 | 1.6660 | No | 0.2316 | 0.2289 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.6918 | 7.6918 | 7.6918 | No | 1.8903 | 0.7346 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1712 | 1.1712 | 1.1712 | No | 0.1781 | 0.3626 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9876 | 0.9876 | 0.9876 | No | 0.1781 | 0.3628 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6660 | 1.6660 | 1.6660 | 1.6660 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6918 | 7.6918 | 7.6918 | 7.6918 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.1712 | 1.1712 | 1.1712 | 1.1712 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9876 | 0.9876 | 0.9876 | 0.9876 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 25.25 | 44089.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 345.74 | 49892.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 316.18 | 27536.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 68.47 | 5240.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 135.72 | 12053.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 19.49 | 1406.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 87.54 | 4933.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1080.75 |
Natural Gas | 0.00 | 112.79 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1193.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 137.83 |
Space Heating | 0.00 |
Space Cooling | 150.72 |
Fans (All) | 59.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 471.12 |
Subtotal | 471.12 |
Natural Gas [MJ/m2] | |
Space Heating | 11.01 |
Service Water Heating | 38.16 |
Miscellaneous (All) | 49.17 |
Subtotal | 49.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.49 |
Space Heating | 2.12 |
Space Cooling | 28.97 |
Fans (All) | 11.37 |
Service Water Heating | 7.33 |
Receptacle Equipment | 16.35 |
Miscellaneous | 7.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 1677. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | FRONT_ENTRY HEATING SP | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 8263.67 | 496.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8660.83 | 99.17 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 7243.17 | 1516.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 7870.83 | 889.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 4510.83 | 3051.67 | 1178.17 | 19.33 | 0.00 |
Min | 4510.83 | 99.17 | 0.00 | 0.00 | 0.00 |
Max | 8660.83 | 3051.67 | 1178.17 | 19.33 | 0.00 |
Average | 7309.87 | 1210.63 | 235.63 | 3.87 | 0.00 |
Sum | 36549.33 | 6053.17 | 1178.17 | 19.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 863.67 | 435.83 | 609.83 | 10.67 | 0.00 |
Min | 863.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 435.83 | 609.83 | 10.67 | 0.00 |
Average | 147866.93 | 87.17 | 121.97 | 2.13 | 0.00 |
Sum | 739334.67 | 435.83 | 609.83 | 10.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 6160.50 | 2599.50 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 6472.83 | 2287.17 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 6210.33 | 2549.67 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 5982.83 | 2777.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 2993.83 | 5024.33 | 729.33 | 12.50 | 0.00 |
Min | 2993.83 | 2287.17 | 0.00 | 0.00 | 0.00 |
Max | 6472.83 | 5024.33 | 729.33 | 12.50 | 0.00 |
Average | 5564.07 | 3047.57 | 145.87 | 2.50 | 0.00 |
Sum | 27820.33 | 15237.83 | 729.33 | 12.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16049.50 | 822.50 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 594617.33 | 14981.67 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 55474.50 | 525.50 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 53471.33 | 2528.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 616.00 | 922.17 | 376.17 | 5.67 | 0.00 |
Min | 616.00 | 525.50 | 0.00 | 0.00 | 0.00 |
Max | 594617.33 | 14981.67 | 376.17 | 5.67 | 0.00 |
Average | 144045.73 | 3956.10 | 75.23 | 1.13 | 0.00 |
Sum | 720228.67 | 19780.50 | 376.17 | 5.67 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:50
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 8760.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 8760.00 |
Average | 0.00 | 0.00 | 0.00 | 1752.00 |
Sum | 0.00 | 0.00 | 0.00 | 8760.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 609599.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 609599.00 |
Average | 0.00 | 0.00 | 0.00 | 121919.80 |
Sum | 0.00 | 0.00 | 0.00 | 609599.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224848E+10 | 25196.55 | 02-JAN-07:02 | 15.83 | 15.23 | 0.253839E+09 | 326.80 | 28-JAN-16:30 | 22.50 | 14.24 |
February | 0.234901E+10 | 26447.96 | 01-FEB-07:02 | 16.10 | 16.10 | 0.243318E+09 | 326.81 | 25-FEB-12:30 | 21.10 | 18.53 |
March | 0.312513E+10 | 26375.18 | 31-MAR-06:02 | 16.37 | 16.37 | 0.286285E+09 | 326.81 | 24-MAR-14:00 | 16.37 | 16.37 |
April | 0.576342E+10 | 28578.10 | 19-APR-06:02 | 16.88 | 15.73 | 0.286714E+09 | 326.82 | 26-APR-14:00 | 27.70 | 22.63 |
May | 0.115624E+11 | 24260.58 | 30-MAY-05:02 | 25.50 | 24.21 | 0.297778E+09 | 326.82 | 13-MAY-12:20 | 25.50 | 24.21 |
June | 0.130332E+11 | 26722.36 | 16-JUN-05:02 | 24.50 | 23.35 | 0.293661E+09 | 326.83 | 17-JUN-10:00 | 31.70 | 25.12 |
July | 0.139949E+11 | 25836.48 | 19-JUL-05:01 | 27.12 | 24.30 | 0.291753E+09 | 326.83 | 26-JUL-14:09 | 31.78 | 25.34 |
August | 0.140994E+11 | 28389.54 | 31-AUG-05:01 | 24.13 | 22.97 | 0.304255E+09 | 326.83 | 31-AUG-14:09 | 31.70 | 24.97 |
September | 0.117887E+11 | 26513.82 | 02-SEP-05:02 | 24.23 | 23.82 | 0.287629E+09 | 326.83 | 02-SEP-13:50 | 32.52 | 24.59 |
October | 0.104364E+11 | 42185.28 | 27-OCT-06:02 | 14.83 | 7.57 | 0.291021E+09 | 326.82 | 05-OCT-14:00 | 14.83 | 7.57 |
November | 0.449415E+10 | 28925.72 | 05-NOV-08:62 | 18.17 | 15.31 | 0.276787E+09 | 326.82 | 04-NOV-15:00 | 18.17 | 15.31 |
December | 0.327500E+10 | 29715.96 | 17-DEC-09:02 | 19.00 | 14.29 | 0.266938E+09 | 326.82 | 15-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.961703E+11 | 0.337998E+10 | ||||||||
Minimum of Months | 0.224848E+10 | 24260.58 | 14.83 | 7.57 | 0.243318E+09 | 326.80 | 14.83 | 7.57 | ||
Maximum of Months | 0.140994E+11 | 42185.28 | 27.12 | 24.30 | 0.304255E+09 | 326.83 | 32.52 | 25.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264954E+11 | 158097.80 | 02-JAN-07:02 | 15.83 | 15.23 | 0.916692E+10 | 10327.73 | 28-JAN-16:00 | 22.00 | 14.40 |
February | 0.275544E+11 | 157866.21 | 25-FEB-07:02 | 14.77 | 14.77 | 0.837644E+10 | 10327.64 | 08-FEB-15:09 | 14.77 | 14.77 |
March | 0.346480E+11 | 183202.18 | 08-MAR-07:03 | 10.50 | 8.45 | 0.959364E+10 | 10327.72 | 04-MAR-11:20 | 10.50 | 8.45 |
April | 0.446015E+11 | 169106.66 | 18-APR-06:02 | 16.78 | 15.05 | 0.908813E+10 | 10328.05 | 05-APR-14:00 | 16.78 | 15.05 |
May | 0.574722E+11 | 144603.94 | 30-MAY-05:02 | 25.50 | 24.21 | 0.941015E+10 | 10327.99 | 09-MAY-14:09 | 25.50 | 24.21 |
June | 0.599495E+11 | 152223.59 | 14-JUN-05:02 | 25.00 | 22.88 | 0.927998E+10 | 10328.03 | 06-JUN-14:09 | 25.00 | 22.88 |
July | 0.608314E+11 | 146653.19 | 19-JUL-05:01 | 27.12 | 24.30 | 0.921966E+10 | 10328.04 | 12-JUL-14:00 | 27.12 | 24.30 |
August | 0.614932E+11 | 153689.94 | 31-AUG-05:01 | 24.13 | 22.97 | 0.961473E+10 | 10328.08 | 07-AUG-14:39 | 24.13 | 22.97 |
September | 0.547974E+11 | 145144.54 | 01-SEP-05:01 | 24.42 | 23.29 | 0.908928E+10 | 10328.03 | 05-SEP-14:39 | 25.23 | 23.10 |
October | 0.533093E+11 | 227764.40 | 27-OCT-06:02 | 14.83 | 7.57 | 0.920532E+10 | 10328.04 | 21-OCT-13:39 | 14.83 | 7.57 |
November | 0.382581E+11 | 229852.68 | 12-NOV-09:02 | 8.58 | 4.63 | 0.885483E+10 | 10328.06 | 07-NOV-15:00 | 8.58 | 4.63 |
December | 0.314382E+11 | 192257.29 | 01-DEC-07:02 | 11.33 | 10.63 | 0.919424E+10 | 10327.68 | 04-DEC-15:00 | 19.00 | 13.78 |
Annual Sum or Average | 0.550849E+12 | 0.110093E+12 | ||||||||
Minimum of Months | 0.264954E+11 | 144603.94 | 8.58 | 4.63 | 0.837644E+10 | 10327.64 | 8.58 | 4.63 | ||
Maximum of Months | 0.614932E+11 | 229852.68 | 27.12 | 24.30 | 0.961473E+10 | 10328.08 | 27.12 | 24.30 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.755506E+10 | 22513.12 | 29-JAN-09:02 | 17.50 | 15.30 | 0.858944E+09 | 973.23 | 12-JAN-15:39 | 17.50 | 15.30 |
February | 0.695055E+10 | 22688.01 | 25-FEB-07:02 | 14.77 | 14.77 | 0.784307E+09 | 973.26 | 27-FEB-15:30 | 25.80 | 20.48 |
March | 0.704825E+10 | 23769.34 | 19-MAR-08:62 | 16.78 | 12.81 | 0.893245E+09 | 973.21 | 18-MAR-10:39 | 16.78 | 12.81 |
April | 0.788235E+10 | 23124.32 | 18-APR-06:02 | 16.78 | 15.05 | 0.855839E+09 | 973.25 | 29-APR-12:39 | 30.90 | 23.14 |
May | 0.102698E+11 | 18151.44 | 06-MAY-05:03 | 24.40 | 21.68 | 0.886718E+09 | 973.26 | 05-MAY-14:39 | 24.40 | 21.68 |
June | 0.106050E+11 | 19566.57 | 16-JUN-05:02 | 24.50 | 23.35 | 0.874438E+09 | 973.25 | 03-JUN-13:20 | 24.50 | 23.35 |
July | 0.112081E+11 | 19403.12 | 19-JUL-05:01 | 27.12 | 24.30 | 0.868750E+09 | 973.25 | 24-JUL-14:00 | 27.20 | 24.02 |
August | 0.121662E+11 | 22363.13 | 31-AUG-05:01 | 24.13 | 22.97 | 0.905969E+09 | 973.26 | 07-AUG-14:50 | 24.13 | 22.97 |
September | 0.114249E+11 | 20751.86 | 02-SEP-05:02 | 24.23 | 23.82 | 0.856481E+09 | 973.25 | 21-SEP-14:00 | 28.30 | 23.96 |
October | 0.124266E+11 | 29080.65 | 27-OCT-06:02 | 14.83 | 7.57 | 0.867289E+09 | 973.28 | 02-OCT-14:20 | 14.83 | 7.57 |
November | 0.978287E+10 | 29542.44 | 12-NOV-09:02 | 8.58 | 4.63 | 0.834249E+09 | 973.29 | 04-NOV-14:30 | 8.58 | 4.63 |
December | 0.854526E+10 | 25687.20 | 02-DEC-07:02 | 12.17 | 12.17 | 0.861767E+09 | 973.27 | 09-DEC-12:39 | 26.67 | 19.83 |
Annual Sum or Average | 0.115865E+12 | 0.103480E+11 | ||||||||
Minimum of Months | 0.695055E+10 | 18151.44 | 8.58 | 4.63 | 0.784307E+09 | 973.21 | 8.58 | 4.63 | ||
Maximum of Months | 0.124266E+11 | 29542.44 | 27.12 | 24.30 | 0.905969E+09 | 973.29 | 30.90 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506015E+10 | 18926.18 | 02-JAN-07:02 | 15.83 | 15.23 | 0.844989E+09 | 973.23 | 19-JAN-15:00 | 25.00 | 20.82 |
February | 0.463835E+10 | 19196.32 | 25-FEB-07:02 | 14.77 | 14.77 | 0.773106E+09 | 973.20 | 27-FEB-15:30 | 25.80 | 20.48 |
March | 0.452827E+10 | 19599.28 | 01-MAR-07:02 | 15.30 | 14.01 | 0.876558E+09 | 973.20 | 16-MAR-14:50 | 21.78 | 15.25 |
April | 0.520796E+10 | 17219.84 | 20-APR-06:02 | 17.88 | 16.43 | 0.853818E+09 | 973.23 | 29-APR-13:20 | 30.73 | 23.80 |
May | 0.741880E+10 | 14738.39 | 12-MAY-06:02 | 23.40 | 20.68 | 0.886702E+09 | 973.22 | 10-MAY-14:30 | 23.40 | 20.68 |
June | 0.779038E+10 | 15800.23 | 16-JUN-05:02 | 24.50 | 23.35 | 0.874427E+09 | 973.21 | 23-JUN-14:20 | 31.70 | 24.87 |
July | 0.840470E+10 | 15820.11 | 19-JUL-05:01 | 27.12 | 24.30 | 0.868744E+09 | 973.22 | 01-JUL-11:39 | 27.12 | 24.30 |
August | 0.919108E+10 | 18339.68 | 31-AUG-05:01 | 24.13 | 22.97 | 0.905966E+09 | 973.22 | 12-AUG-11:00 | 24.13 | 22.97 |
September | 0.859601E+10 | 16883.35 | 02-SEP-05:02 | 24.23 | 23.82 | 0.856472E+09 | 973.22 | 25-SEP-14:00 | 27.20 | 23.86 |
October | 0.951498E+10 | 26542.54 | 27-OCT-06:02 | 14.83 | 7.57 | 0.866943E+09 | 973.25 | 02-OCT-14:30 | 14.83 | 7.57 |
November | 0.705875E+10 | 28692.46 | 12-NOV-09:02 | 8.58 | 4.63 | 0.833063E+09 | 973.23 | 04-NOV-14:20 | 8.58 | 4.63 |
December | 0.596839E+10 | 20332.28 | 03-DEC-09:02 | 13.17 | 13.17 | 0.846326E+09 | 973.24 | 16-DEC-11:20 | 26.33 | 21.98 |
Annual Sum or Average | 0.833778E+11 | 0.102871E+11 | ||||||||
Minimum of Months | 0.452827E+10 | 14738.39 | 8.58 | 4.63 | 0.773106E+09 | 973.20 | 8.58 | 4.63 | ||
Maximum of Months | 0.951498E+10 | 28692.46 | 27.12 | 24.30 | 0.905966E+09 | 973.25 | 31.70 | 24.87 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6099.59 | 15.30 | 29-JAN-09:20 | 18.00 | 15.50 | 57975935.13 | 101.79 | 02-JAN-15:09 | 18.00 | 15.50 |
February | 2098.47 | 6.99 | 14-FEB-07:15 | 9.60 | 8.09 | 56340325.47 | 103.41 | 25-FEB-16:00 | 27.20 | 18.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 | 67778477.11 | 111.07 | 27-MAR-14:00 | 28.30 | 21.49 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 77282381.35 | 155.86 | 28-APR-14:00 | 33.30 | 23.06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 | 0.109681E+09 | 156.45 | 18-MAY-14:00 | 33.30 | 23.27 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.114015E+09 | 172.16 | 14-JUN-14:09 | 34.72 | 24.33 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 | 0.111763E+09 | 181.88 | 22-JUL-15:00 | 36.10 | 27.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 | 0.116378E+09 | 171.51 | 03-AUG-14:00 | 35.00 | 24.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 | 98377810.93 | 176.01 | 09-SEP-15:00 | 35.60 | 26.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 95979119.66 | 164.07 | 05-OCT-14:00 | 34.00 | 24.05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 67823724.03 | 126.74 | 01-NOV-14:09 | 29.80 | 24.92 |
December | 1119.30 | 1.57 | 20-DEC-06:20 | 2.67 | 1.44 | 64080643.37 | 127.93 | 13-DEC-15:09 | 2.67 | 1.44 |
Annual Sum or Average | 9317.36 | 0.103748E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 2.67 | 1.44 | 56340325.47 | 101.79 | 2.67 | 1.44 | ||
Maximum of Months | 6099.59 | 15.30 | 25.13 | 24.22 | 0.116378E+09 | 181.88 | 36.10 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358557E+09 | 39354.81 | 11-JAN-07:03 | 8.17 |
February | 0.354509E+09 | 42970.90 | 06-FEB-06:02 | 2.88 |
March | 0.219668E+09 | 39721.80 | 12-MAR-08:62 | 9.18 |
April | 68671650.18 | 724.18 | 11-APR-06:00 | 8.30 |
May | 39883438.66 | 1982.44 | 28-MAY-08:08 | 27.48 |
June | 32662944.99 | 2061.32 | 18-JUN-08:08 | 28.25 |
July | 26270021.13 | 1629.84 | 19-JUL-06:08 | 26.88 |
August | 25554733.70 | 1830.95 | 27-AUG-08:08 | 27.33 |
September | 31114080.28 | 2060.44 | 03-SEP-08:08 | 28.07 |
October | 38094379.31 | 1092.70 | 26-OCT-05:04 | 22.83 |
November | 67650115.39 | 975.29 | 11-NOV-09:20 | 24.40 |
December | 0.239829E+09 | 38375.73 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 0.150246E+10 | |||
Minimum of Months | 25554733.70 | 724.18 | 0.83 | |
Maximum of Months | 0.358557E+09 | 42970.90 | 28.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533127E+09 | 5247.68 | 21-JAN-07:00 | 1.00 |
February | 0.481707E+09 | 5224.20 | 26-FEB-08:61 | 15.97 |
March | 0.524390E+09 | 6556.10 | 05-MAR-09:05 | 20.97 |
April | 0.383379E+09 | 7159.84 | 28-APR-06:06 | 23.22 |
May | 0.304242E+09 | 15515.14 | 28-MAY-08:06 | 27.48 |
June | 0.287945E+09 | 17170.40 | 18-JUN-08:06 | 28.25 |
July | 0.287965E+09 | 19888.32 | 09-JUL-08:06 | 29.60 |
August | 0.268953E+09 | 15085.88 | 27-AUG-08:06 | 27.33 |
September | 0.258074E+09 | 15499.74 | 03-SEP-08:06 | 28.07 |
October | 0.280856E+09 | 13144.79 | 07-OCT-06:06 | 26.67 |
November | 0.436822E+09 | 8950.61 | 11-NOV-09:06 | 24.40 |
December | 0.482164E+09 | 5924.65 | 15-DEC-07:06 | 21.17 |
Annual Sum or Average | 0.452962E+10 | |||
Minimum of Months | 0.258074E+09 | 5224.20 | 1.00 | |
Maximum of Months | 0.533127E+09 | 19888.32 | 29.60 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42255100.40 | 856.74 | 02-JAN-06:07 | 16.00 |
February | 38419460.82 | 11106.67 | 05-FEB-08:62 | -2.9 |
March | 46796132.59 | 11361.25 | 12-MAR-08:62 | 9.18 |
April | 31460056.33 | 922.15 | 28-APR-05:07 | 22.80 |
May | 21889856.72 | 1504.73 | 28-MAY-08:06 | 27.48 |
June | 19497540.81 | 1565.74 | 18-JUN-08:06 | 28.25 |
July | 18475072.48 | 1599.70 | 23-JUL-08:06 | 28.48 |
August | 17613205.65 | 1443.99 | 13-AUG-08:06 | 27.47 |
September | 17487637.70 | 1510.38 | 03-SEP-08:06 | 28.07 |
October | 15620799.92 | 1217.53 | 26-OCT-05:04 | 22.83 |
November | 31654027.17 | 1094.57 | 04-NOV-05:05 | 20.58 |
December | 37102767.67 | 1105.41 | 11-DEC-06:05 | 20.83 |
Annual Sum or Average | 0.338272E+09 | |||
Minimum of Months | 15620799.92 | 856.74 | -2.9 | |
Maximum of Months | 46796132.59 | 11361.25 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40774712.52 | 2920.84 | 10-JAN-07:03 | 3.17 |
February | 55635666.70 | 24169.64 | 05-FEB-08:62 | -2.9 |
March | 67725916.95 | 18106.15 | 12-MAR-07:03 | 6.97 |
April | 36447919.60 | 509.12 | 28-APR-06:06 | 23.22 |
May | 20659299.00 | 1412.75 | 28-MAY-08:06 | 27.48 |
June | 20912133.81 | 1558.91 | 18-JUN-08:06 | 28.25 |
July | 19177722.64 | 1229.51 | 19-JUL-06:06 | 26.88 |
August | 15268925.30 | 1318.93 | 27-AUG-08:06 | 27.33 |
September | 14925202.07 | 974.99 | 09-SEP-06:06 | 25.42 |
October | 16878037.08 | 819.57 | 26-OCT-05:04 | 22.83 |
November | 31693104.59 | 786.60 | 03-NOV-05:03 | 22.28 |
December | 49982532.98 | 11545.33 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.390081E+09 | |||
Minimum of Months | 14925202.07 | 509.12 | -2.9 | |
Maximum of Months | 67725916.95 | 24169.64 | 28.25 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523887E+10 | 26885.70 | 04-JAN-18:00 | 6.00 |
February | 0.368903E+10 | 29345.14 | 04-FEB-18:00 | 5.00 |
March | 0.299701E+10 | 26956.15 | 11-MAR-12:10 | 6.28 |
April | 0.296253E+09 | 6999.47 | 02-APR-11:10 | 16.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 1203405.34 | 1047.94 | 07-SEP-17:00 | 19.80 |
October | 0.166563E+09 | 6281.62 | 27-OCT-17:00 | 17.00 |
November | 0.105048E+10 | 19204.27 | 15-NOV-18:00 | 10.00 |
December | 0.409524E+10 | 30978.97 | 20-DEC-18:00 | 4.00 |
Annual Sum or Average | 0.175346E+11 | |||
Minimum of Months | 0.00 | 0.00 | 4.00 | |
Maximum of Months | 0.523887E+10 | 30978.97 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129219E+10 | 1082.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.117572E+10 | 1082.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.134112E+10 | 1082.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.126535E+10 | 1082.42 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.131665E+10 | 1082.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.129414E+10 | 1082.42 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.128786E+10 | 1082.42 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.134112E+10 | 1082.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.126535E+10 | 1082.42 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.129219E+10 | 1082.42 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.124954E+10 | 1082.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.128786E+10 | 1082.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.154091E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.117572E+10 | 1082.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.134112E+10 | 1082.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.229415E+11 | 22187.22 | 02-JAN-16:40 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.197467E+11 | 22187.22 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.211208E+11 | 22187.22 | 01-MAR-16:40 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.188385E+11 | 22187.22 | 14-APR-08:09 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.190107E+11 | 20338.28 | 01-MAY-16:40 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.183803E+11 | 20338.28 | 05-JUN-16:49 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.178486E+11 | 20338.28 | 27-JUL-16:00 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.187331E+11 | 20338.28 | 11-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.182562E+11 | 22187.22 | 27-SEP-16:00 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.199529E+11 | 22187.22 | 02-OCT-16:49 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.219379E+11 | 22187.22 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.232591E+11 | 22187.22 | 01-DEC-15:30 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.240026E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.178486E+11 | 20338.28 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.232591E+11 | 22187.22 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.244397E+10 | 2090.65 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.249958E+10 | 2090.65 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.244397E+10 | 2090.65 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.244397E+10 | 2090.65 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.249958E+10 | 2090.65 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.244397E+10 | 2090.65 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.101920E+09 | 85.37 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 92733309.19 | 85.37 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.105778E+09 | 85.37 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 99802281.75 | 85.37 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.103849E+09 | 85.37 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.102073E+09 | 85.37 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.101578E+09 | 85.37 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.105778E+09 | 85.37 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 99802281.75 | 85.37 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.101920E+09 | 85.37 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 98555820.41 | 85.37 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.101578E+09 | 85.37 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121537E+10 | 0.00 | 0.00 | ||
Minimum of Months | 92733309.19 | 85.37 | 0.00 | 0.00 | |
Maximum of Months | 0.105778E+09 | 85.37 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.129219E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2503340.82 | 0.821165E+09 |
February | 0.638757E+09 | 0.117572E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5051180.37 | 0.591632E+09 |
March | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13963928.19 | 0.682561E+09 |
April | 0.690691E+09 | 0.126535E+10 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30668514.65 | 0.275501E+09 |
May | 0.715069E+09 | 0.131665E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119199E+09 | 57335418.22 |
June | 0.705176E+09 | 0.129414E+10 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112541E+09 | 55766457.47 |
July | 0.700584E+09 | 0.128786E+10 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135265E+09 | 29506793.87 |
August | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144497E+09 | 81007904.02 |
September | 0.690691E+09 | 0.126535E+10 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115988E+09 | 0.104742E+09 |
October | 0.699524E+09 | 0.129219E+10 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100923E+09 | 0.303330E+09 |
November | 0.673027E+09 | 0.124954E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13108302.10 | 0.451249E+09 |
December | 0.700584E+09 | 0.128786E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8199787.30 | 0.736871E+09 |
Annual Sum or Average | 0.837485E+10 | 0.154091E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801908E+09 | 0.419067E+10 |
Minimum of Months | 0.638757E+09 | 0.117572E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2503340.82 | 29506793.87 |
Maximum of Months | 0.730614E+09 | 0.134112E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144497E+09 | 0.821165E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.229415E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2113699.56 | 0.848136E+09 |
February | 0.201852E+11 | 0.197467E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4267559.16 | 0.609847E+09 |
March | 0.230879E+11 | 0.211208E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11944757.80 | 0.686872E+09 |
April | 0.218263E+11 | 0.188385E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26236987.37 | 0.266246E+09 |
May | 0.225967E+11 | 0.190107E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101950E+09 | 54859208.27 |
June | 0.222841E+11 | 0.183803E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97290867.60 | 48607975.45 |
July | 0.221389E+11 | 0.178486E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119315E+09 | 22520131.03 |
August | 0.230879E+11 | 0.187331E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126910E+09 | 66095207.58 |
September | 0.218263E+11 | 0.182562E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101521E+09 | 92348529.17 |
October | 0.221054E+11 | 0.199529E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86681108.06 | 0.278317E+09 |
November | 0.212681E+11 | 0.219379E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11198880.43 | 0.433513E+09 |
December | 0.221389E+11 | 0.232591E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6978295.55 | 0.748320E+09 |
Annual Sum or Average | 0.264651E+12 | 0.240026E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696408E+09 | 0.415568E+10 |
Minimum of Months | 0.201852E+11 | 0.178486E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2113699.56 | 22520131.03 |
Maximum of Months | 0.230879E+11 | 0.232591E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126910E+09 | 0.848136E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123750.95 | 0.458516E+09 |
February | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2269014.49 | 0.319123E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6351505.79 | 0.355048E+09 |
April | 0.205665E+10 | 0.244397E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13888324.80 | 0.143292E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51340955.60 | 42204790.29 |
June | 0.209978E+10 | 0.249958E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49473460.81 | 36052008.91 |
July | 0.208610E+10 | 0.248746E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56711318.87 | 23220211.33 |
August | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61542681.16 | 56742849.08 |
September | 0.205665E+10 | 0.244397E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48452168.16 | 75799361.10 |
October | 0.208295E+10 | 0.249582E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44010452.98 | 0.190086E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5924237.73 | 0.248378E+09 |
December | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3710764.01 | 0.407570E+09 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344799E+09 | 0.235603E+10 |
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123750.95 | 23220211.33 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61542681.16 | 0.458516E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1123651.37 | 0.435414E+09 |
February | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2269124.04 | 0.301680E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6351752.81 | 0.331032E+09 |
April | 0.205665E+10 | 0.244397E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13915315.31 | 0.130294E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52915435.18 | 28247602.81 |
June | 0.209978E+10 | 0.249958E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50721500.49 | 25254775.99 |
July | 0.208610E+10 | 0.248746E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59995899.94 | 14271675.10 |
August | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63471462.06 | 41722361.84 |
September | 0.205665E+10 | 0.244397E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49767805.59 | 59026191.45 |
October | 0.208295E+10 | 0.249582E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44318622.93 | 0.168589E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5930423.25 | 0.234076E+09 |
December | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3710881.16 | 0.383794E+09 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354492E+09 | 0.215340E+10 |
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1123651.37 | 14271675.10 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63471462.06 | 0.435414E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.101920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628671E+10 |
February | 0.151369E+09 | 92733309.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451832E+10 |
March | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2933348.95 | 0.362111E+10 |
April | 0.163676E+09 | 99802281.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23537223.24 | 0.723217E+09 |
May | 0.169453E+09 | 0.103849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251259E+09 | 77397253.87 |
June | 0.167108E+09 | 0.102073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288035E+09 | 42256368.23 |
July | 0.166020E+09 | 0.101578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273288E+09 | 84929193.45 |
August | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208895E+09 | 0.111058E+09 |
September | 0.163676E+09 | 99802281.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71650247.59 | 0.229667E+09 |
October | 0.165769E+09 | 0.101920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9427187.50 | 0.618706E+09 |
November | 0.159490E+09 | 98555820.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000695.71 | 0.203072E+10 |
December | 0.166020E+09 | 0.101578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36871.94 | 0.510556E+10 |
Annual Sum or Average | 0.198462E+10 | 0.121537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113006E+10 | 0.234497E+11 |
Minimum of Months | 0.151369E+09 | 92733309.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42256368.23 |
Maximum of Months | 0.173136E+09 | 0.105778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288035E+09 | 0.628671E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 1082.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 19-JAN-12:10 | 1779.44 | 21-JAN-06:00 |
February | 785.10 | 01-FEB-15:09 | 1082.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.82 | 02-FEB-13:00 | 2415.39 | 05-FEB-08:00 |
March | 785.10 | 01-MAR-15:09 | 1082.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.34 | 28-MAR-14:00 | 2110.24 | 20-MAR-22:00 |
April | 785.10 | 01-APR-10:09 | 1082.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.07 | 29-APR-16:00 | 1193.94 | 01-APR-21:10 |
May | 785.10 | 01-MAY-14:09 | 1082.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 469.39 | 07-MAY-18:03 | 269.82 | 05-MAY-04:00 |
June | 785.10 | 01-JUN-14:09 | 1082.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 463.64 | 09-JUN-20:03 | 426.15 | 06-JUN-21:20 |
July | 785.10 | 01-JUL-10:09 | 1082.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 486.61 | 04-JUL-18:03 | 218.59 | 31-JUL-02:30 |
August | 785.10 | 01-AUG-14:09 | 1082.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 744.32 | 22-AUG-20:03 | 591.15 | 25-AUG-24:00 |
September | 785.10 | 01-SEP-14:09 | 1082.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 728.19 | 09-SEP-23:00 | 539.83 | 05-SEP-03:00 |
October | 785.10 | 02-OCT-14:09 | 1082.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.76 | 08-OCT-18:03 | 1054.83 | 29-OCT-02:00 |
November | 785.10 | 01-NOV-14:09 | 1082.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.94 | 07-NOV-13:00 | 1520.61 | 12-NOV-07:00 |
December | 785.10 | 01-DEC-15:09 | 1082.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.92 | 13-DEC-14:00 | 2102.48 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 1082.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 218.59 | |||||
Maximum of Months | 785.10 | 1082.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 744.32 | 2415.39 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22187.22 | 02-JAN-16:40 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 19-JAN-12:10 | 1675.99 | 26-JAN-03:00 |
February | 24809.68 | 01-FEB-15:09 | 22187.22 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.17 | 02-FEB-13:00 | 2432.45 | 16-FEB-21:10 |
March | 24809.68 | 01-MAR-15:09 | 22187.22 | 01-MAR-16:40 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.77 | 28-MAR-14:00 | 2065.94 | 20-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 22187.22 | 14-APR-08:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.41 | 29-APR-16:00 | 1087.01 | 02-APR-06:00 |
May | 24809.68 | 01-MAY-14:09 | 20338.28 | 01-MAY-16:40 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 403.50 | 07-MAY-18:03 | 239.87 | 05-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 20338.28 | 05-JUN-16:49 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.33 | 09-JUN-20:03 | 397.68 | 06-JUN-21:20 |
July | 24809.68 | 01-JUL-10:09 | 20338.28 | 27-JUL-16:00 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 420.73 | 04-JUL-18:03 | 182.45 | 31-JUL-02:40 |
August | 24809.68 | 01-AUG-14:09 | 20338.28 | 11-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 642.57 | 22-AUG-20:03 | 528.96 | 25-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 22187.22 | 27-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 666.24 | 09-SEP-23:00 | 460.25 | 05-SEP-03:00 |
October | 24809.68 | 02-OCT-14:09 | 22187.22 | 02-OCT-16:49 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 384.12 | 08-OCT-18:03 | 1024.04 | 29-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 22187.22 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.71 | 07-NOV-13:00 | 1401.63 | 12-NOV-07:00 |
December | 24809.68 | 01-DEC-15:09 | 22187.22 | 01-DEC-15:30 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.68 | 13-DEC-14:00 | 2226.83 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 20338.28 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 182.45 | |||||
Maximum of Months | 24809.68 | 22187.22 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 666.24 | 2432.45 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 19-JAN-12:10 | 900.08 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.85 | 02-FEB-13:00 | 1260.21 | 16-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 28-MAR-14:00 | 1026.91 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.28 | 29-APR-16:00 | 573.65 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.57 | 07-MAY-18:03 | 161.63 | 05-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.24 | 09-JUN-20:03 | 246.85 | 06-JUN-21:20 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.36 | 19-JUL-13:00 | 134.13 | 31-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.21 | 22-AUG-20:03 | 306.34 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 | 09-SEP-21:03 | 305.50 | 05-SEP-03:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.81 | 08-OCT-18:03 | 553.91 | 29-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 | 07-NOV-13:00 | 770.40 | 12-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 13-DEC-14:00 | 1089.51 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 134.13 | |||||
Maximum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 331.21 | 1260.21 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 19-JAN-12:10 | 856.82 | 26-JAN-03:00 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.85 | 02-FEB-13:00 | 1169.63 | 16-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 28-MAR-14:00 | 976.28 | 20-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.28 | 29-APR-16:00 | 543.57 | 01-APR-21:10 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.70 | 07-MAY-18:03 | 121.22 | 05-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.47 | 09-JUN-20:03 | 202.83 | 06-JUN-21:10 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.36 | 19-JUL-13:00 | 98.75 | 31-JUL-02:70 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 334.72 | 22-AUG-20:03 | 275.58 | 25-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.95 | 09-SEP-21:03 | 262.56 | 05-SEP-03:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 08-OCT-18:03 | 525.91 | 29-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 | 07-NOV-13:00 | 747.37 | 12-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 13-DEC-14:00 | 1017.65 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 98.75 | |||||
Maximum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 334.72 | 1169.63 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 85.37 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 27527.86 | 04-JAN-18:00 |
February | 186.05 | 01-FEB-15:09 | 85.37 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 29729.83 | 04-FEB-18:00 |
March | 186.05 | 01-MAR-15:09 | 85.37 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.12 | 30-MAR-13:00 | 26976.84 | 11-MAR-12:10 |
April | 186.05 | 01-APR-10:09 | 85.37 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.38 | 28-APR-11:03 | 7578.62 | 02-APR-11:10 |
May | 186.05 | 01-MAY-14:09 | 85.37 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1412.35 | 27-MAY-11:02 | 1378.05 | 13-MAY-11:53 |
June | 186.05 | 01-JUN-14:09 | 85.37 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415.29 | 14-JUN-11:02 | 1558.99 | 18-JUN-13:53 |
July | 186.05 | 01-JUL-10:09 | 85.37 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.19 | 18-JUL-11:02 | 1779.28 | 31-JUL-11:02 |
August | 186.05 | 01-AUG-14:09 | 85.37 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.89 | 01-AUG-11:02 | 1747.63 | 06-AUG-15:53 |
September | 186.05 | 01-SEP-14:09 | 85.37 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.88 | 10-SEP-11:02 | 2783.69 | 02-SEP-15:52 |
October | 186.05 | 02-OCT-14:09 | 85.37 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.86 | 06-OCT-11:05 | 7212.32 | 27-OCT-16:00 |
November | 186.05 | 01-NOV-14:09 | 85.37 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.25 | 01-NOV-14:00 | 19959.76 | 15-NOV-18:00 |
December | 186.05 | 01-DEC-15:09 | 85.37 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 | 13-DEC-11:55 | 31392.20 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.05 | ||||
Maximum of Months | 186.05 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2173.19 | 31392.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25196.55 | 02-JAN-07:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.29 |
February | 26447.96 | 01-FEB-07:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 |
March | 26375.18 | 31-MAR-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.48 |
April | 28578.10 | 19-APR-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.66 |
May | 24260.58 | 30-MAY-05:02 | 0.00 | 300.63 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26722.36 | 16-JUN-05:02 | 0.00 | 300.63 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25836.48 | 19-JUL-05:01 | 0.00 | 420.88 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
August | 28389.54 | 31-AUG-05:01 | 0.00 | 481.01 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 |
September | 26513.82 | 02-SEP-05:02 | 0.00 | 360.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42185.28 | 27-OCT-06:02 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.79 |
November | 28925.72 | 05-NOV-08:62 | 490.69 | 601.39 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.65 |
December | 29715.96 | 17-DEC-09:02 | 490.69 | 601.39 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24260.58 | 0.00 | 300.63 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42185.28 | 490.69 | 1202.65 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 241.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 158097.80 | 02-JAN-07:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.35 |
February | 157866.21 | 25-FEB-07:02 | 15506.05 | 12326.23 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 183202.18 | 08-MAR-07:03 | 12404.84 | 19721.97 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.44 |
April | 169106.66 | 18-APR-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 |
May | 144603.94 | 30-MAY-05:02 | 0.00 | 6163.12 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 152223.59 | 14-JUN-05:02 | 0.00 | 7395.74 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
July | 146653.19 | 19-JUL-05:01 | 0.00 | 8628.36 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 0.00 |
August | 153689.94 | 31-AUG-05:01 | 0.00 | 9860.98 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 145144.54 | 01-SEP-05:01 | 0.00 | 8628.36 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 227764.40 | 27-OCT-06:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.23 |
November | 229852.68 | 12-NOV-09:02 | 15506.05 | 11299.05 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.25 |
December | 192257.29 | 01-DEC-07:02 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 144603.94 | 0.00 | 6163.12 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 229852.68 | 15506.05 | 24652.46 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 332.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22513.12 | 29-JAN-09:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
February | 22688.01 | 25-FEB-07:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23769.34 | 19-MAR-08:62 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 |
April | 23124.32 | 18-APR-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 |
May | 18151.44 | 06-MAY-05:03 | 0.00 | 464.59 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 |
June | 19566.57 | 16-JUN-05:02 | 0.00 | 580.74 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19403.12 | 19-JUL-05:01 | 0.00 | 813.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
August | 22363.13 | 31-AUG-05:01 | 0.00 | 929.18 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 20751.86 | 02-SEP-05:02 | 0.00 | 696.88 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29080.65 | 27-OCT-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.11 |
November | 29542.44 | 12-NOV-09:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.52 |
December | 25687.20 | 02-DEC-07:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18151.44 | 0.00 | 464.59 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29542.44 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18926.18 | 02-JAN-07:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 |
February | 19196.32 | 25-FEB-07:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19599.28 | 01-MAR-07:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.50 |
April | 17219.84 | 20-APR-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
May | 14738.39 | 12-MAY-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 |
June | 15800.23 | 16-JUN-05:02 | 0.00 | 580.74 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15820.11 | 19-JUL-05:01 | 0.00 | 813.03 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 0.00 |
August | 18339.68 | 31-AUG-05:01 | 0.00 | 929.18 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 16883.35 | 02-SEP-05:02 | 0.00 | 696.88 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26542.54 | 27-OCT-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.87 |
November | 28692.46 | 12-NOV-09:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.43 |
December | 20332.28 | 03-DEC-09:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14738.39 | 0.00 | 580.74 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28692.46 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.72 | 159.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15.30 | 29-JAN-09:20 | 46.51 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785.27 |
February | 6.99 | 14-FEB-07:15 | 46.51 | 37.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
April | 0.00 | 01-APR-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
December | 1.57 | 20-DEC-06:20 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 4.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | |
Maximum of Months | 15.30 | 46.51 | 37.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 785.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.721291E+11 | 74398.17 | 19-JAN-17:00 | 0.153855E+11 | 37904.79 | 09-JAN-17:00 |
February | 0.672160E+11 | 71492.39 | 24-FEB-15:00 | 0.125360E+11 | 45951.66 | 05-FEB-09:09 |
March | 0.769303E+11 | 71614.98 | 06-MAR-15:00 | 0.121026E+11 | 47797.03 | 11-MAR-12:30 |
April | 0.826630E+11 | 77524.58 | 28-APR-14:00 | 0.755887E+10 | 12809.35 | 02-APR-11:20 |
May | 0.103109E+12 | 77663.72 | 27-MAY-15:20 | 0.733173E+10 | 4848.54 | 01-MAY-11:09 |
June | 0.103581E+12 | 82614.19 | 28-JUN-14:00 | 0.700252E+10 | 4814.29 | 01-JUN-11:50 |
July | 0.106899E+12 | 84014.79 | 22-JUL-15:00 | 0.712685E+10 | 4791.98 | 03-JUL-11:20 |
August | 0.109077E+12 | 84212.29 | 30-AUG-16:19 | 0.720094E+10 | 4801.51 | 31-AUG-11:09 |
September | 0.101798E+12 | 87114.30 | 09-SEP-16:00 | 0.702788E+10 | 5119.41 | 07-SEP-16:49 |
October | 0.991453E+11 | 86384.15 | 07-OCT-15:50 | 0.755442E+10 | 12410.39 | 27-OCT-16:00 |
November | 0.804702E+11 | 79426.32 | 02-NOV-15:09 | 0.849563E+10 | 27439.72 | 15-NOV-17:00 |
December | 0.777318E+11 | 77857.24 | 16-DEC-17:40 | 0.134677E+11 | 47225.25 | 20-DEC-17:00 |
Annual Sum or Average | 0.108075E+13 | 0.112791E+12 | ||||
Minimum of Months | 0.672160E+11 | 71492.39 | 0.700252E+10 | 4791.98 | ||
Maximum of Months | 0.109077E+12 | 87114.30 | 0.153855E+11 | 47797.03 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.293273E+11 | 0.673086E+10 | 0.164409E+11 | 0.00 | 0.113904E+11 | 0.00 | 0.00 | 0.695361E+10 | 0.00 | 0.00 | 0.128607E+10 | 0.00 | 0.00 |
February | 0.255569E+11 | 0.576655E+10 | 0.149157E+11 | 0.00 | 0.103176E+11 | 0.00 | 0.00 | 0.959098E+10 | 0.00 | 0.00 | 0.106814E+10 | 0.00 | 0.00 |
March | 0.277483E+11 | 0.591328E+10 | 0.168545E+11 | 0.00 | 0.115494E+11 | 0.00 | 0.00 | 0.136308E+11 | 0.00 | 0.00 | 0.123395E+10 | 0.00 | 0.00 |
April | 0.250916E+11 | 0.526586E+10 | 0.160187E+11 | 0.00 | 0.110457E+11 | 0.00 | 0.00 | 0.239171E+11 | 0.00 | 0.00 | 0.132402E+10 | 0.00 | 0.00 |
May | 0.255174E+11 | 0.502967E+10 | 0.166477E+11 | 0.00 | 0.114558E+11 | 0.00 | 0.00 | 0.423421E+11 | 0.00 | 0.00 | 0.211622E+10 | 0.00 | 0.00 |
June | 0.247757E+11 | 0.464325E+10 | 0.162750E+11 | 0.00 | 0.112676E+11 | 0.00 | 0.00 | 0.445539E+11 | 0.00 | 0.00 | 0.206559E+10 | 0.00 | 0.00 |
July | 0.242129E+11 | 0.491647E+10 | 0.163892E+11 | 0.00 | 0.116496E+11 | 0.00 | 0.00 | 0.476300E+11 | 0.00 | 0.00 | 0.210103E+10 | 0.00 | 0.00 |
August | 0.253606E+11 | 0.524979E+10 | 0.168545E+11 | 0.00 | 0.118224E+11 | 0.00 | 0.00 | 0.476534E+11 | 0.00 | 0.00 | 0.213647E+10 | 0.00 | 0.00 |
September | 0.245093E+11 | 0.553000E+10 | 0.160144E+11 | 0.00 | 0.112858E+11 | 0.00 | 0.00 | 0.424083E+11 | 0.00 | 0.00 | 0.205040E+10 | 0.00 | 0.00 |
October | 0.263387E+11 | 0.619314E+10 | 0.164431E+11 | 0.00 | 0.115745E+11 | 0.00 | 0.00 | 0.368477E+11 | 0.00 | 0.00 | 0.174819E+10 | 0.00 | 0.00 |
November | 0.281129E+11 | 0.639160E+10 | 0.159174E+11 | 0.00 | 0.109484E+11 | 0.00 | 0.00 | 0.180902E+11 | 0.00 | 0.00 | 0.100970E+10 | 0.00 | 0.00 |
December | 0.296235E+11 | 0.683463E+10 | 0.163871E+11 | 0.00 | 0.114152E+11 | 0.00 | 0.00 | 0.121235E+11 | 0.00 | 0.00 | 0.134788E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.316175E+12 | 0.684651E+11 | 0.195158E+12 | 0.00 | 0.135723E+12 | 0.00 | 0.00 | 0.345742E+12 | 0.00 | 0.00 | 0.194877E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242129E+11 | 0.464325E+10 | 0.149157E+11 | 0.00 | 0.103176E+11 | 0.00 | 0.00 | 0.695361E+10 | 0.00 | 0.00 | 0.100970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.296235E+11 | 0.683463E+10 | 0.168545E+11 | 0.00 | 0.118224E+11 | 0.00 | 0.00 | 0.476534E+11 | 0.00 | 0.00 | 0.213647E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.767705E+10 | 0.00 | 0.770842E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.557880E+10 | 0.00 | 0.695724E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.443781E+10 | 0.00 | 0.766474E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.320935E+09 | 0.00 | 0.723793E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.733173E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.700252E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.712685E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.720094E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 871504.39 | 0.00 | 0.702700E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.187154E+09 | 0.00 | 0.736727E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122684E+10 | 0.00 | 0.726879E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.581991E+10 | 0.00 | 0.764781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.252494E+11 | 0.00 | 0.875413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.695724E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.767705E+10 | 0.00 | 0.770842E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 27536.32 | 02-JAN-16:40 | 5240.87 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 9519.66 | 20-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 27536.32 | 01-FEB-09:09 | 5240.87 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 9969.47 | 03-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 27536.32 | 01-MAR-16:40 | 5240.87 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 10735.06 | 07-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27536.32 | 14-APR-08:09 | 5240.87 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 10975.82 | 29-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 25687.38 | 01-MAY-16:40 | 5240.87 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 11388.60 | 21-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 25687.38 | 05-JUN-16:49 | 5240.87 | 01-JUN-05:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 11394.34 | 04-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 25687.38 | 27-JUL-16:00 | 5240.87 | 01-JUL-05:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 11571.67 | 03-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 25687.38 | 11-AUG-16:00 | 5240.87 | 01-AUG-05:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 11444.57 | 06-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 27536.32 | 27-SEP-16:00 | 5240.87 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 12053.70 | 10-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27536.32 | 02-OCT-16:49 | 5240.87 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 11451.19 | 06-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27536.32 | 01-NOV-08:09 | 5240.87 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 11055.75 | 02-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 27536.32 | 01-DEC-15:30 | 5240.87 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 11009.46 | 16-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 25687.38 | 5240.87 | 10771.04 | 0.00 | 9519.66 | 0.00 | 0.00 | |||||
Maximum of Months | 27536.32 | 5240.87 | 10771.04 | 0.00 | 12053.70 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 27505.88 | 19-JAN-15:09 | 0.00 | 0.00 | 1406.31 | 01-JAN-11:09 | 0.00 | 0.00 |
February | 27331.12 | 24-FEB-13:30 | 0.00 | 0.00 | 1406.31 | 01-FEB-07:49 | 0.00 | 0.00 |
March | 27202.52 | 28-MAR-11:00 | 0.00 | 0.00 | 1406.31 | 01-MAR-07:40 | 0.00 | 0.00 |
April | 36094.08 | 28-APR-14:00 | 0.00 | 0.00 | 1406.31 | 01-APR-06:10 | 0.00 | 0.00 |
May | 37299.63 | 30-MAY-12:00 | 0.00 | 0.00 | 1406.31 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 41146.80 | 28-JUN-14:09 | 0.00 | 0.00 | 1406.31 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 43807.11 | 22-JUL-15:00 | 0.00 | 0.00 | 1406.31 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 41721.24 | 03-AUG-14:00 | 0.00 | 0.00 | 1406.31 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 49892.81 | 10-SEP-08:09 | 0.00 | 0.00 | 1406.31 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 42871.37 | 07-OCT-12:00 | 0.00 | 0.00 | 1406.31 | 01-OCT-09:50 | 0.00 | 0.00 |
November | 34793.07 | 02-NOV-14:30 | 0.00 | 0.00 | 1406.31 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 31343.71 | 16-DEC-12:00 | 0.00 | 0.00 | 1406.31 | 01-DEC-07:19 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 27202.52 | 0.00 | 0.00 | 1406.31 | 0.00 | 0.00 | ||
Maximum of Months | 49892.81 | 0.00 | 0.00 | 1406.31 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 74398.17 | 19-JAN-17:00 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 7001.42 | 0.00 | 0.00 | 22442.21 | 0.00 |
February | 71492.39 | 24-FEB-15:00 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7093.70 | 0.00 | 0.00 | 26533.96 | 0.00 |
March | 71614.98 | 06-MAR-15:00 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7007.57 | 0.00 | 0.00 | 26742.68 | 0.00 |
April | 77524.58 | 28-APR-14:00 | 21989.51 | 10771.04 | 0.00 | 0.00 | 7263.64 | 0.00 | 0.00 | 36094.08 | 0.00 |
May | 77663.72 | 27-MAY-15:20 | 21989.51 | 10771.04 | 0.00 | 0.00 | 7181.28 | 0.00 | 0.00 | 36315.57 | 0.00 |
June | 82614.19 | 28-JUN-14:00 | 21989.51 | 10771.04 | 0.00 | 0.00 | 7675.79 | 0.00 | 0.00 | 40771.54 | 0.00 |
July | 84014.79 | 22-JUL-15:00 | 20140.58 | 10771.04 | 0.00 | 0.00 | 7889.75 | 0.00 | 0.00 | 43807.11 | 0.00 |
August | 84212.29 | 30-AUG-16:19 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7539.52 | 0.00 | 0.00 | 38808.03 | 0.00 |
September | 87114.30 | 09-SEP-16:00 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7795.40 | 0.00 | 0.00 | 41454.17 | 0.00 |
October | 86384.15 | 07-OCT-15:50 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7975.20 | 0.00 | 0.00 | 40544.21 | 0.00 |
November | 79426.32 | 02-NOV-15:09 | 25687.38 | 10771.04 | 0.00 | 0.00 | 7546.80 | 0.00 | 0.00 | 34014.78 | 0.00 |
December | 77857.24 | 16-DEC-17:40 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 7007.21 | 0.00 | 0.00 | 25895.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 71492.39 | 20140.58 | 10771.04 | 0.00 | 0.00 | 7001.42 | 0.00 | 0.00 | 22442.21 | 0.00 | |
Maximum of Months | 87114.30 | 27536.32 | 10771.04 | 5240.87 | 0.00 | 7975.20 | 0.00 | 0.00 | 43807.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 34123.77 | 04-JAN-17:00 | 0.00 | 4933.61 | 23-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 44089.66 | 05-FEB-09:09 | 0.00 | 4931.53 | 06-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 42914.44 | 11-MAR-12:30 | 0.00 | 4915.36 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 8566.33 | 02-APR-11:09 | 0.00 | 4882.45 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4848.54 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4814.29 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4791.98 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4801.51 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 1037.94 | 07-SEP-16:00 | 0.00 | 4827.79 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 7667.63 | 27-OCT-16:00 | 0.00 | 4865.95 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 23820.94 | 15-NOV-17:00 | 0.00 | 4900.24 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 42438.91 | 20-DEC-17:00 | 0.00 | 4925.74 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4791.98 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 44089.66 | 0.00 | 4933.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.17 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.41 | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 0.67 | 20.47 | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 342.00 | 22.03 | 97.33 | 22.19 | 65.83 | 22.20 |
February | 254.50 | 22.32 | 149.67 | 22.63 | 70.17 | 22.59 |
March | 284.00 | 22.79 | 130.17 | 23.03 | 41.17 | 23.01 |
April | 120.50 | 23.69 | 243.83 | 23.82 | 25.50 | 23.83 |
May | 37.33 | 23.92 | 418.00 | 23.90 | 37.33 | 23.90 |
June | 11.50 | 23.94 | 408.00 | 23.90 | 11.50 | 23.90 |
July | 25.17 | 23.95 | 415.00 | 23.90 | 25.17 | 23.90 |
August | 26.33 | 23.96 | 422.00 | 23.90 | 26.33 | 23.90 |
September | 37.33 | 23.93 | 405.00 | 23.90 | 37.33 | 23.90 |
October | 68.50 | 23.80 | 322.17 | 23.88 | 29.67 | 23.88 |
November | 215.83 | 23.51 | 138.50 | 23.66 | 20.33 | 23.67 |
December | 301.67 | 22.47 | 130.67 | 22.74 | 58.50 | 22.73 |
Annual Sum or Average | 1724.67 | 22.80 | 3280.33 | 23.45 | 448.83 | 23.43 |
Minimum of Months | 11.50 | 22.03 | 97.33 | 22.19 | 11.50 | 22.20 |
Maximum of Months | 342.00 | 23.96 | 422.00 | 23.90 | 70.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.83 | 23.69 | 127.33 | 23.77 | 23.83 | 23.78 |
February | 141.67 | 23.69 | 190.83 | 23.80 | 35.67 | 23.81 |
March | 113.17 | 23.71 | 206.83 | 23.83 | 7.17 | 23.83 |
April | 20.67 | 23.87 | 329.00 | 23.89 | 11.83 | 23.89 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 23.89 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 23.89 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 23.89 |
August | 0.50 | 23.89 | 422.00 | 23.89 | 0.50 | 23.89 |
September | 4.17 | 23.89 | 405.00 | 23.89 | 4.17 | 23.89 |
October | 3.67 | 23.84 | 366.83 | 23.89 | 0.00 | 23.89 |
November | 37.00 | 23.87 | 246.33 | 23.89 | 9.00 | 23.89 |
December | 135.17 | 23.72 | 181.33 | 23.82 | 24.50 | 23.82 |
Annual Sum or Average | 643.83 | 23.72 | 3716.50 | 23.87 | 116.67 | 23.87 |
Minimum of Months | 0.00 | 0.00 | 127.33 | 23.77 | 0.00 | 23.78 |
Maximum of Months | 187.83 | 23.89 | 422.00 | 23.89 | 35.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.17 | 22.93 | 197.50 | 23.58 | 14.33 | 23.59 |
February | 86.33 | 22.98 | 233.50 | 23.62 | 12.33 | 23.61 |
March | 116.50 | 23.03 | 228.00 | 23.59 | 6.67 | 23.59 |
April | 25.33 | 23.59 | 322.50 | 23.87 | 6.50 | 23.87 |
May | 16.83 | 23.92 | 418.00 | 23.89 | 16.83 | 23.89 |
June | 4.67 | 23.94 | 408.00 | 23.89 | 4.67 | 23.89 |
July | 10.67 | 23.94 | 415.00 | 23.89 | 10.67 | 23.90 |
August | 9.50 | 23.95 | 422.00 | 23.89 | 9.50 | 23.90 |
September | 10.50 | 23.94 | 405.00 | 23.89 | 10.50 | 23.90 |
October | 6.67 | 23.70 | 383.67 | 23.89 | 3.67 | 23.89 |
November | 12.00 | 23.56 | 322.33 | 23.88 | 0.33 | 23.88 |
December | 72.83 | 22.96 | 240.67 | 23.68 | 3.50 | 23.68 |
Annual Sum or Average | 468.00 | 23.14 | 3996.17 | 23.81 | 99.50 | 23.81 |
Minimum of Months | 4.67 | 22.93 | 197.50 | 23.58 | 0.33 | 23.59 |
Maximum of Months | 116.50 | 23.95 | 422.00 | 23.89 | 16.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 156.17 | 22.66 | 160.50 | 23.27 | 21.00 | 23.29 |
February | 132.67 | 22.74 | 211.17 | 23.40 | 29.00 | 23.41 |
March | 157.50 | 22.63 | 204.00 | 23.32 | 16.83 | 23.32 |
April | 72.33 | 23.52 | 303.67 | 23.82 | 33.50 | 23.82 |
May | 46.67 | 23.90 | 418.00 | 23.89 | 46.67 | 23.89 |
June | 24.17 | 23.90 | 408.00 | 23.89 | 24.17 | 23.89 |
July | 44.83 | 23.91 | 415.00 | 23.89 | 44.83 | 23.90 |
August | 35.33 | 23.91 | 422.00 | 23.89 | 35.33 | 23.90 |
September | 33.33 | 23.91 | 405.00 | 23.89 | 33.33 | 23.90 |
October | 20.50 | 23.70 | 375.50 | 23.88 | 13.50 | 23.88 |
November | 31.83 | 23.36 | 295.00 | 23.84 | 6.33 | 23.84 |
December | 138.67 | 22.74 | 225.17 | 23.42 | 22.83 | 23.43 |
Annual Sum or Average | 894.00 | 23.05 | 3843.00 | 23.73 | 327.33 | 23.73 |
Minimum of Months | 20.50 | 22.63 | 160.50 | 23.27 | 6.33 | 23.29 |
Maximum of Months | 157.50 | 23.91 | 422.00 | 23.89 | 46.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.67 | 21.87 | 117.33 | 22.33 | 91.00 | 22.53 |
February | 345.67 | 22.45 | 154.00 | 22.94 | 137.33 | 23.19 |
March | 369.67 | 22.80 | 185.33 | 23.48 | 147.83 | 23.76 |
April | 350.17 | 24.62 | 276.83 | 25.21 | 229.33 | 25.46 |
May | 418.00 | 28.60 | 418.00 | 28.60 | 418.00 | 28.60 |
June | 408.00 | 29.27 | 408.00 | 29.27 | 408.00 | 29.27 |
July | 415.00 | 29.18 | 415.00 | 29.18 | 415.00 | 29.18 |
August | 422.00 | 29.14 | 422.00 | 29.14 | 422.00 | 29.14 |
September | 405.00 | 27.88 | 405.00 | 27.88 | 405.00 | 27.88 |
October | 363.00 | 27.60 | 359.83 | 27.80 | 321.17 | 27.98 |
November | 314.67 | 23.76 | 198.50 | 24.56 | 141.83 | 24.96 |
December | 365.00 | 22.67 | 162.67 | 23.39 | 123.67 | 23.75 |
Annual Sum or Average | 4551.83 | 26.01 | 3522.50 | 26.70 | 3260.17 | 27.02 |
Minimum of Months | 314.67 | 21.87 | 117.33 | 22.33 | 91.00 | 22.53 |
Maximum of Months | 422.00 | 29.27 | 422.00 | 29.27 | 422.00 | 29.27 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.35624 | 43.32833 | -0.1048 | 8.00823 |
February | 376.00000 | 22.82028 | 47.86067 | 0.04637 | 8.17834 |
March | 422.00000 | 23.14937 | 45.41232 | 0.12155 | 7.77646 |
April | 405.00000 | 23.82973 | 52.07704 | 0.39285 | 8.63201 |
May | 418.00000 | 23.89428 | 58.25877 | -0.3384 | 7.40112 |
June | 408.00000 | 23.89467 | 57.14048 | -0.3115 | 7.04460 |
July | 415.00000 | 23.89591 | 59.41447 | -0.2830 | 6.69723 |
August | 422.00000 | 23.89571 | 58.69041 | -0.2911 | 6.78468 |
September | 405.00000 | 23.89517 | 59.76846 | -0.3179 | 7.14125 |
October | 414.00000 | 23.87660 | 54.06881 | 0.49054 | 10.34170 |
November | 399.00000 | 23.68144 | 47.52223 | 0.29961 | 7.73291 |
December | 415.00000 | 22.85872 | 45.73256 | 0.05696 | 7.83629 |
Annual Sum or Average | 4913.00000 | 23.50729 | 52.47500 | -0.0217 | 7.79353 |
Minimum of Months | 376.00000 | 22.35624 | 43.32833 | -0.3384 | 6.69723 |
Maximum of Months | 422.00000 | 23.89591 | 59.76846 | 0.49054 | 10.34170 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.79865 | 43.44670 | 0.33469 | 7.84297 |
February | 376.00000 | 23.81270 | 47.37044 | 0.38521 | 8.78825 |
March | 422.00000 | 23.84132 | 44.88126 | 0.39297 | 8.69905 |
April | 405.00000 | 23.88873 | 50.19047 | 0.49924 | 10.36855 |
May | 418.00000 | 23.89187 | 53.23440 | -0.2860 | 6.74049 |
June | 408.00000 | 23.89212 | 52.82312 | -0.2669 | 6.52613 |
July | 415.00000 | 23.89277 | 55.06260 | -0.2521 | 6.36272 |
August | 422.00000 | 23.89277 | 54.59345 | -0.2591 | 6.43079 |
September | 405.00000 | 23.89244 | 56.03636 | -0.2740 | 6.59614 |
October | 414.00000 | 23.89098 | 51.12365 | 0.53698 | 11.17880 |
November | 399.00000 | 23.88676 | 46.96539 | 0.44701 | 9.39999 |
December | 415.00000 | 23.83387 | 46.03678 | 0.38481 | 8.58346 |
Annual Sum or Average | 4913.00000 | 23.86819 | 50.16545 | 0.13402 | 8.11486 |
Minimum of Months | 376.00000 | 23.79865 | 43.44670 | -0.2860 | 6.36272 |
Maximum of Months | 422.00000 | 23.89277 | 56.03636 | 0.53698 | 11.17880 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.66655 | 39.26254 | 0.37579 | 9.08314 |
February | 376.00000 | 23.68053 | 42.79657 | 0.40621 | 9.87130 |
March | 422.00000 | 23.65009 | 42.69619 | 0.37147 | 9.30076 |
April | 405.00000 | 23.87115 | 49.26306 | 0.51209 | 10.78882 |
May | 418.00000 | 23.89261 | 55.93076 | -0.2127 | 5.99233 |
June | 408.00000 | 23.89265 | 55.79133 | -0.1908 | 5.81277 |
July | 415.00000 | 23.89299 | 57.79845 | -0.1610 | 5.60036 |
August | 422.00000 | 23.89285 | 56.30971 | -0.1460 | 5.51107 |
September | 405.00000 | 23.89288 | 55.93111 | -0.1582 | 5.63162 |
October | 414.00000 | 23.88794 | 49.87482 | 0.64067 | 13.89513 |
November | 399.00000 | 23.87878 | 43.36420 | 0.53273 | 11.26664 |
December | 415.00000 | 23.72696 | 41.65482 | 0.43346 | 10.06377 |
Annual Sum or Average | 4913.00000 | 23.81930 | 49.27658 | 0.19762 | 8.54832 |
Minimum of Months | 376.00000 | 23.65009 | 39.26254 | -0.2127 | 5.51107 |
Maximum of Months | 422.00000 | 23.89299 | 57.79845 | 0.64067 | 13.89513 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.42121 | 41.09210 | 0.29849 | 8.52925 |
February | 376.00000 | 23.47882 | 44.93594 | 0.33996 | 9.41957 |
March | 422.00000 | 23.41507 | 44.93728 | 0.29874 | 8.94931 |
April | 405.00000 | 23.82084 | 52.02664 | 0.48137 | 10.31308 |
May | 418.00000 | 23.89227 | 58.81777 | -0.2422 | 6.26325 |
June | 408.00000 | 23.89225 | 58.37601 | -0.2222 | 6.07903 |
July | 415.00000 | 23.89316 | 60.52353 | -0.1890 | 5.79509 |
August | 422.00000 | 23.89313 | 58.78907 | -0.1781 | 5.71838 |
September | 405.00000 | 23.89290 | 58.63547 | -0.1890 | 5.84333 |
October | 414.00000 | 23.88109 | 51.50618 | 0.61496 | 13.25369 |
November | 399.00000 | 23.84536 | 45.05400 | 0.50003 | 10.66026 |
December | 415.00000 | 23.50135 | 43.80682 | 0.36208 | 9.51892 |
Annual Sum or Average | 4913.00000 | 23.73648 | 51.59763 | 0.15362 | 8.34522 |
Minimum of Months | 376.00000 | 23.41507 | 41.09210 | -0.2422 | 5.71838 |
Maximum of Months | 422.00000 | 23.89316 | 60.52353 | 0.61496 | 13.25369 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.07707 | 45.58505 | 0.08251 | 8.84309 |
February | 376.00000 | 22.52098 | 51.32413 | 0.20695 | 11.07775 |
March | 422.00000 | 23.01808 | 49.20669 | 0.24746 | 12.80732 |
April | 405.00000 | 24.67684 | 57.76373 | 0.66632 | 21.31278 |
May | 418.00000 | 28.60102 | 64.79037 | 1.03271 | 32.17788 |
June | 408.00000 | 29.26614 | 64.49372 | 1.23790 | 40.08976 |
July | 415.00000 | 29.18216 | 72.05013 | 1.31086 | 43.54971 |
August | 422.00000 | 29.14459 | 69.30261 | 1.30633 | 43.40555 |
September | 405.00000 | 27.87710 | 73.09742 | 0.99106 | 30.96458 |
October | 414.00000 | 27.20641 | 61.19216 | 1.35999 | 47.90133 |
November | 399.00000 | 23.79390 | 52.85422 | 0.55861 | 18.90492 |
December | 415.00000 | 22.82049 | 49.68853 | 0.28647 | 14.05607 |
Annual Sum or Average | 4913.00000 | 25.87806 | 59.33636 | 0.77844 | 27.23550 |
Minimum of Months | 376.00000 | 22.07707 | 45.58505 | 0.08251 | 8.84309 |
Maximum of Months | 422.00000 | 29.26614 | 73.09742 | 1.35999 | 47.90133 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.140980E+10 | 0.366622E+09 | 85.97 | 0.936002E+09 | 0.473800E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 34812.94 | 20-JAN-07:02 | 16436.25 | 20-JAN-07:02 | 18376.69 | 20-JAN-07:02 | 7349.33 | 20-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.207338E+10 | 0.537400E+09 | 127.69 | 0.139630E+10 | 0.677078E+09 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 35233.93 | 03-FEB-07:02 | 18603.02 | 28-FEB-07:02 | 17911.66 | 03-FEB-07:02 | 7406.88 | 03-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.351784E+10 | 0.912331E+09 | 188.39 | 0.242832E+10 | 0.108952E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 36180.97 | 07-MAR-07:02 | 25081.25 | 30-MAR-06:02 | 17043.85 | 28-MAR-06:02 | 7510.05 | 07-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.811923E+10 | 0.207532E+10 | 336.09 | 0.589279E+10 | 0.222644E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 36326.08 | 29-APR-06:02 | 26666.41 | 23-APR-08:62 | 19092.26 | 30-APR-08:04 | 7640.49 | 29-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.211241E+11 | 0.517128E+10 | 436.83 | 0.147159E+11 | 0.640817E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 37431.43 | 23-MAY-06:02 | 27111.72 | 30-MAY-05:02 | 18680.26 | 23-MAY-06:06 | 8031.07 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.234791E+11 | 0.568778E+10 | 426.89 | 0.165044E+11 | 0.697470E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 36960.92 | 05-JUN-05:02 | 29708.47 | 16-JUN-05:02 | 16492.38 | 08-JUN-06:04 | 8080.38 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.264685E+11 | 0.630630E+10 | 437.73 | 0.175832E+11 | 0.888530E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 37994.70 | 03-JUL-05:02 | 28433.65 | 19-JUL-05:01 | 18478.59 | 02-JUL-08:06 | 8212.82 | 09-JUL-08:15 | 0.00 | 01-JUL-00:10 |
August | 0.260579E+11 | 0.619453E+10 | 444.52 | 0.175520E+11 | 0.850590E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 37467.17 | 11-AUG-05:02 | 30983.95 | 31-AUG-05:01 | 16733.68 | 06-AUG-08:15 | 8108.20 | 06-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.220587E+11 | 0.523479E+10 | 425.49 | 0.143887E+11 | 0.766998E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 37889.77 | 05-SEP-05:02 | 29290.67 | 02-SEP-05:02 | 23457.57 | 05-SEP-05:02 | 8554.95 | 10-SEP-08:17 | 0.00 | 01-SEP-00:10 |
October | 0.176008E+11 | 0.423886E+10 | 402.77 | 0.120587E+11 | 0.554208E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 37630.84 | 08-OCT-07:02 | 31234.99 | 27-OCT-06:02 | 17993.05 | 22-OCT-08:06 | 7960.23 | 07-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.546631E+10 | 0.137264E+10 | 252.09 | 0.374512E+10 | 0.172119E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 36427.50 | 02-NOV-06:02 | 27243.04 | 06-NOV-07:02 | 18053.58 | 04-NOV-06:04 | 7710.48 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.341662E+10 | 0.862694E+09 | 142.07 | 0.227462E+10 | 0.114200E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 36258.79 | 15-DEC-07:02 | 23674.11 | 17-DEC-09:02 | 19634.73 | 16-DEC-07:02 | 7520.27 | 15-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.160792E+12 | 0.389605E+11 | 3706.52 | 0.109476E+12 | 0.513162E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.140980E+10 | 0.366622E+09 | 85.97 | 0.936002E+09 | 0.473800E+09 | 0.00 | 1.00 | 0.00 | 34812.94 | 16436.25 | 16492.38 | 7349.33 | 0.00 | |||||||
Maximum of Months | 0.264685E+11 | 0.630630E+10 | 444.52 | 0.175832E+11 | 0.888530E+10 | 0.00 | 1.00 | 0.00 | 37994.70 | 31234.99 | 23457.57 | 8554.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.167810E+11 | 0.472759E+10 | 257.51 | 0.110109E+11 | 0.577005E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 208514.34 | 31-JAN-07:02 | 130031.75 | 01-JAN-09:02 | 109608.77 | 31-JAN-07:02 | 48735.07 | 31-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.240147E+11 | 0.669873E+10 | 255.38 | 0.157185E+11 | 0.829625E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 206523.90 | 26-FEB-09:02 | 108915.27 | 28-FEB-07:02 | 104449.74 | 22-FEB-07:02 | 48472.36 | 26-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.354233E+11 | 0.995927E+10 | 312.58 | 0.246022E+11 | 0.108211E+11 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 210033.48 | 07-MAR-07:02 | 150130.40 | 05-MAR-09:02 | 97300.16 | 28-MAR-06:02 | 48914.47 | 07-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.619995E+11 | 0.174783E+11 | 384.37 | 0.434623E+11 | 0.185372E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 210365.96 | 29-APR-06:02 | 171076.61 | 18-APR-06:02 | 105405.95 | 14-APR-06:02 | 49763.24 | 29-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.101775E+12 | 0.291505E+11 | 437.07 | 0.700025E+11 | 0.317729E+11 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 212437.37 | 23-MAY-06:02 | 165122.62 | 30-MAY-05:02 | 87140.78 | 23-MAY-06:04 | 52172.63 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.106031E+12 | 0.303890E+11 | 426.11 | 0.729719E+11 | 0.330592E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 211265.96 | 19-JUN-06:02 | 171897.44 | 14-JUN-05:02 | 79190.94 | 19-JUN-06:02 | 52446.34 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.113036E+12 | 0.319733E+11 | 435.26 | 0.741010E+11 | 0.389348E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 211280.31 | 31-JUL-06:02 | 165090.41 | 19-JUL-05:01 | 81894.03 | 31-JUL-06:04 | 53321.57 | 09-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.112432E+12 | 0.318118E+11 | 442.66 | 0.745707E+11 | 0.378612E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 211540.28 | 17-AUG-06:02 | 171744.14 | 31-AUG-05:01 | 84134.88 | 17-AUG-06:04 | 52713.92 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.102415E+12 | 0.284870E+11 | 424.61 | 0.656912E+11 | 0.367233E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 213809.13 | 17-SEP-08:62 | 163482.44 | 01-SEP-05:01 | 90111.90 | 05-SEP-06:04 | 55606.99 | 10-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.869303E+11 | 0.244558E+11 | 412.33 | 0.590782E+11 | 0.278521E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 213099.79 | 22-OCT-08:62 | 179790.24 | 27-OCT-06:02 | 90021.45 | 22-OCT-08:04 | 51732.14 | 07-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.439001E+11 | 0.123418E+11 | 335.86 | 0.301654E+11 | 0.137347E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 210735.54 | 01-NOV-06:02 | 151226.58 | 06-NOV-07:02 | 98395.02 | 08-NOV-07:02 | 50371.53 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.294635E+11 | 0.822499E+10 | 308.74 | 0.193498E+11 | 0.101136E+11 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 211287.65 | 16-DEC-07:02 | 136355.94 | 11-DEC-07:02 | 97427.76 | 09-DEC-07:02 | 49048.48 | 16-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.834201E+12 | 0.235698E+12 | 4432.50 | 0.560725E+12 | 0.273477E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.167810E+11 | 0.472759E+10 | 255.38 | 0.110109E+11 | 0.577005E+10 | 0.00 | 1.00 | 0.00 | 206523.90 | 108915.27 | 79190.94 | 48472.36 | 0.00 | |||||||
Maximum of Months | 0.113036E+12 | 0.319733E+11 | 442.66 | 0.745707E+11 | 0.389348E+11 | 0.00 | 1.00 | 0.00 | 213809.13 | 179790.24 | 109608.77 | 55606.99 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.461230E+10 | 0.109350E+10 | 210.14 | 0.348604E+10 | 0.112626E+10 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:10 | 27560.05 | 31-JAN-07:02 | 17755.36 | 01-JAN-09:02 | 14472.59 | 31-JAN-07:02 | 5771.71 | 31-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.589229E+10 | 0.137858E+10 | 237.28 | 0.435965E+10 | 0.153263E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 27331.47 | 03-FEB-07:02 | 21370.39 | 27-FEB-07:02 | 13677.92 | 03-FEB-07:02 | 5743.96 | 03-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.672799E+10 | 0.160939E+10 | 274.90 | 0.506392E+10 | 0.166408E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 27845.93 | 07-MAR-07:02 | 20716.19 | 30-MAR-06:02 | 13210.17 | 28-MAR-06:02 | 5802.50 | 07-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.104594E+11 | 0.253258E+10 | 374.91 | 0.773457E+10 | 0.272488E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 28044.99 | 30-APR-08:62 | 20314.74 | 23-APR-08:62 | 15029.29 | 30-APR-08:62 | 5905.21 | 29-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.183805E+11 | 0.442657E+10 | 439.82 | 0.126861E+11 | 0.569443E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 28799.45 | 23-MAY-06:02 | 21259.76 | 06-MAY-05:03 | 13690.11 | 23-MAY-06:02 | 6224.81 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.192801E+11 | 0.465386E+10 | 429.27 | 0.132698E+11 | 0.601037E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 28843.61 | 05-JUN-05:02 | 22464.66 | 16-JUN-05:02 | 13132.80 | 08-JUN-06:02 | 6261.97 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.213890E+11 | 0.509885E+10 | 439.05 | 0.139649E+11 | 0.742417E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 29600.45 | 03-JUL-05:02 | 21833.34 | 19-JUL-05:01 | 15545.57 | 03-JUL-05:02 | 6358.38 | 09-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.221168E+11 | 0.526285E+10 | 445.74 | 0.148718E+11 | 0.724506E+10 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 29254.70 | 11-AUG-05:02 | 24841.36 | 31-AUG-05:01 | 14866.66 | 16-AUG-05:03 | 6272.97 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.202907E+11 | 0.475065E+10 | 427.77 | 0.134766E+11 | 0.681409E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 29429.42 | 05-SEP-05:02 | 23482.35 | 02-SEP-05:02 | 18129.13 | 05-SEP-05:02 | 6606.89 | 10-SEP-08:04 | 0.00 | 01-SEP-00:10 |
October | 0.189203E+11 | 0.445381E+10 | 419.36 | 0.135738E+11 | 0.534654E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 29299.04 | 08-OCT-07:02 | 24202.29 | 26-OCT-06:02 | 16625.81 | 20-OCT-05:02 | 6164.25 | 07-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.105838E+11 | 0.248554E+10 | 361.10 | 0.804630E+10 | 0.253749E+10 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 27931.29 | 02-NOV-06:02 | 23586.51 | 03-NOV-05:02 | 13468.64 | 08-NOV-07:02 | 5952.19 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.748605E+10 | 0.175104E+10 | 273.78 | 0.561065E+10 | 0.187540E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 28033.46 | 16-DEC-07:02 | 20844.18 | 11-DEC-06:03 | 15433.02 | 14-DEC-07:02 | 5820.28 | 16-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.166139E+12 | 0.394972E+11 | 4333.11 | 0.116144E+12 | 0.499954E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.461230E+10 | 0.109350E+10 | 210.14 | 0.348604E+10 | 0.112626E+10 | 0.00 | 1.00 | 0.00 | 27331.47 | 17755.36 | 13132.80 | 5743.96 | 0.00 | |||||||
Maximum of Months | 0.221168E+11 | 0.526285E+10 | 445.74 | 0.148718E+11 | 0.742417E+10 | 0.00 | 1.00 | 0.00 | 29600.45 | 24841.36 | 18129.13 | 6606.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.318375E+10 | 0.765906E+09 | 177.24 | 0.228244E+10 | 0.901317E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 24038.09 | 31-JAN-07:02 | 15207.62 | 01-JAN-09:02 | 13062.70 | 31-JAN-07:02 | 5031.81 | 31-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.412332E+10 | 0.976265E+09 | 196.38 | 0.290026E+10 | 0.122306E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 23819.42 | 03-FEB-07:02 | 17436.54 | 27-FEB-07:02 | 12209.58 | 03-FEB-07:02 | 5005.46 | 03-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.472446E+10 | 0.114979E+10 | 232.35 | 0.335076E+10 | 0.137370E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 24482.02 | 07-MAR-07:02 | 16949.18 | 26-MAR-08:62 | 11905.65 | 28-MAR-06:02 | 5076.24 | 07-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.743917E+10 | 0.183094E+10 | 344.28 | 0.520941E+10 | 0.222976E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 24571.25 | 29-APR-06:02 | 16717.54 | 23-APR-08:62 | 13204.30 | 30-APR-08:62 | 5162.70 | 29-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.148525E+11 | 0.359379E+10 | 438.42 | 0.966425E+10 | 0.518828E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 25391.81 | 23-MAY-06:02 | 16745.31 | 30-MAY-05:02 | 13508.07 | 23-MAY-06:04 | 5424.10 | 28-MAY-08:04 | 0.00 | 01-MAY-00:10 |
June | 0.158524E+11 | 0.382317E+10 | 426.60 | 0.102783E+11 | 0.557410E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 25085.71 | 05-JUN-05:02 | 17933.48 | 16-JUN-05:02 | 11945.93 | 19-JUN-06:04 | 5464.91 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.179214E+11 | 0.425159E+10 | 436.93 | 0.109665E+11 | 0.695492E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 25772.50 | 03-JUL-05:02 | 17642.05 | 19-JUL-05:01 | 13894.58 | 03-JUL-05:02 | 5548.89 | 09-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.184931E+11 | 0.438417E+10 | 444.96 | 0.116955E+11 | 0.679755E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 25464.14 | 11-AUG-05:02 | 20202.04 | 31-AUG-05:01 | 12059.11 | 06-AUG-08:04 | 5464.46 | 06-AUG-08:04 | 0.00 | 01-AUG-00:10 |
September | 0.168129E+11 | 0.393586E+10 | 427.25 | 0.104631E+11 | 0.634984E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 25620.42 | 05-SEP-05:02 | 18909.78 | 02-SEP-05:02 | 16150.05 | 05-SEP-06:02 | 5778.99 | 10-SEP-08:13 | 0.00 | 01-SEP-00:10 |
October | 0.157189E+11 | 0.369927E+10 | 411.70 | 0.106754E+11 | 0.504345E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 25510.89 | 08-OCT-07:02 | 20523.52 | 27-OCT-06:02 | 14804.84 | 20-OCT-05:02 | 5375.57 | 07-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.798129E+10 | 0.189023E+10 | 335.61 | 0.574927E+10 | 0.223202E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 24592.29 | 02-NOV-06:02 | 18923.26 | 03-NOV-05:02 | 12049.54 | 08-NOV-07:02 | 5201.44 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.544953E+10 | 0.128482E+10 | 240.47 | 0.388206E+10 | 0.156747E+10 | 0.00 | 1.00 | 02-DEC-07:02 | 0.00 | 01-DEC-00:10 | 24447.90 | 16-DEC-07:02 | 16036.90 | 17-DEC-09:02 | 13497.20 | 16-DEC-07:02 | 5073.27 | 16-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.132553E+12 | 0.315858E+11 | 4112.17 | 0.871173E+11 | 0.454355E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.318375E+10 | 0.765906E+09 | 177.24 | 0.228244E+10 | 0.901317E+09 | 0.00 | 1.00 | 0.00 | 23819.42 | 15207.62 | 11905.65 | 5005.46 | 0.00 | |||||||
Maximum of Months | 0.184931E+11 | 0.438417E+10 | 444.96 | 0.116955E+11 | 0.695492E+10 | 0.00 | 1.00 | 0.00 | 25772.50 | 20523.52 | 16150.05 | 5778.99 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.25 | 57.55 | 28.70 | 101.47 | 57.61 | 13.00 | 0.00 | 0.00 |
February | 110.70 | 76.21 | 34.49 | 133.71 | 50.45 | 4.33 | 0.00 | 0.00 |
March | 120.04 | 74.54 | 45.51 | 148.69 | 42.98 | 1.50 | 0.00 | 0.00 |
April | 153.64 | 100.01 | 53.63 | 201.12 | 30.75 | 0.00 | 0.00 | 0.00 |
May | 146.89 | 83.85 | 63.03 | 205.59 | 13.58 | 0.00 | 0.00 | 0.00 |
June | 162.14 | 93.58 | 68.56 | 229.23 | 13.46 | 0.00 | 0.00 | 0.00 |
July | 151.00 | 77.63 | 73.37 | 212.92 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 140.71 | 70.31 | 70.40 | 199.37 | 12.89 | 0.00 | 0.00 | 0.00 |
September | 120.86 | 60.42 | 60.44 | 168.32 | 15.43 | 0.00 | 0.00 | 0.00 |
October | 113.52 | 67.04 | 46.48 | 156.44 | 22.34 | 0.00 | 0.00 | 0.00 |
November | 93.48 | 64.04 | 29.44 | 117.02 | 42.30 | 2.50 | 0.00 | 0.00 |
December | 78.93 | 52.15 | 26.78 | 94.67 | 51.12 | 3.50 | 0.00 | 0.00 |
Annual Sum or Average | 123.18 | 73.02 | 50.16 | 164.13 | 30.22 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 78.93 | 52.15 | 26.78 | 94.67 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.14 | 100.01 | 73.37 | 229.23 | 57.61 | 13.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1054.85 | 752.29 | 302.56 | 1532.12 | 714.11 | 0.00 | 0.00 | 0.00 |
February | 956.69 | 619.25 | 337.44 | 1421.54 | 607.79 | 0.00 | 0.00 | 0.00 |
March | 610.77 | 275.64 | 335.13 | 937.34 | 532.57 | 0.00 | 0.00 | 0.00 |
April | 452.70 | 106.08 | 346.62 | 769.85 | 355.68 | 0.00 | 0.00 | 0.00 |
May | 345.89 | 14.70 | 331.19 | 731.14 | 121.42 | 0.00 | 0.00 | 0.00 |
June | 341.69 | 3.18 | 338.50 | 741.07 | 113.70 | 0.00 | 0.00 | 0.00 |
July | 357.69 | 6.57 | 351.11 | 767.58 | 85.51 | 0.00 | 0.00 | 0.00 |
August | 420.80 | 50.51 | 370.29 | 905.58 | 122.58 | 0.00 | 0.00 | 0.00 |
September | 504.89 | 133.06 | 371.83 | 1008.28 | 158.75 | 0.00 | 0.00 | 0.00 |
October | 783.34 | 408.05 | 375.30 | 1438.65 | 263.67 | 0.00 | 0.00 | 0.00 |
November | 996.85 | 686.34 | 310.51 | 1571.97 | 493.90 | 0.00 | 0.00 | 0.00 |
December | 1030.72 | 740.21 | 290.51 | 1557.08 | 637.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.14 | 314.76 | 338.39 | 1113.68 | 349.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.69 | 3.18 | 290.51 | 731.14 | 85.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.85 | 752.29 | 375.30 | 1571.97 | 714.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1054.85 | 752.29 | 302.56 | 1536.59 | 688.09 | 0.00 | 0.00 | 0.00 |
February | 956.69 | 619.25 | 337.44 | 1425.40 | 583.44 | 0.00 | 0.00 | 0.00 |
March | 610.77 | 275.64 | 335.13 | 940.42 | 506.90 | 0.00 | 0.00 | 0.00 |
April | 452.70 | 106.08 | 346.62 | 769.15 | 336.23 | 0.00 | 0.00 | 0.00 |
May | 345.89 | 14.70 | 331.19 | 728.55 | 107.13 | 0.00 | 0.00 | 0.00 |
June | 341.69 | 3.18 | 338.50 | 737.84 | 99.32 | 0.00 | 0.00 | 0.00 |
July | 357.69 | 6.57 | 351.11 | 765.25 | 72.84 | 0.00 | 0.00 | 0.00 |
August | 420.80 | 50.51 | 370.29 | 902.73 | 108.62 | 0.00 | 0.00 | 0.00 |
September | 504.89 | 133.06 | 371.83 | 1005.72 | 144.34 | 0.00 | 0.00 | 0.00 |
October | 783.34 | 408.05 | 375.30 | 1435.68 | 248.05 | 0.00 | 0.00 | 0.00 |
November | 996.85 | 686.34 | 310.51 | 1571.35 | 477.43 | 0.00 | 0.00 | 0.00 |
December | 1030.72 | 740.21 | 290.51 | 1560.56 | 612.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.14 | 314.76 | 338.39 | 1113.41 | 330.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.69 | 3.18 | 290.51 | 728.55 | 72.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.85 | 752.29 | 375.30 | 1571.35 | 688.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 217.02 | 154.77 | 62.25 | 315.18 | 133.39 | 0.00 | 0.00 | 0.00 |
February | 196.83 | 127.40 | 69.42 | 290.87 | 113.40 | 0.00 | 0.00 | 0.00 |
March | 125.66 | 56.71 | 68.95 | 190.29 | 99.24 | 0.00 | 0.00 | 0.00 |
April | 93.14 | 21.82 | 71.31 | 151.01 | 67.06 | 0.00 | 0.00 | 0.00 |
May | 71.16 | 3.02 | 68.14 | 123.67 | 27.31 | 0.00 | 0.00 | 0.00 |
June | 70.30 | 0.66 | 69.64 | 122.31 | 26.53 | 0.00 | 0.00 | 0.00 |
July | 73.59 | 1.35 | 72.24 | 127.16 | 20.90 | 4.50 | 0.00 | 0.00 |
August | 86.57 | 10.39 | 76.18 | 154.53 | 29.36 | 3.83 | 0.00 | 0.00 |
September | 103.87 | 27.38 | 76.50 | 182.29 | 36.02 | 0.00 | 0.00 | 0.00 |
October | 161.16 | 83.95 | 77.21 | 273.01 | 57.27 | 1.83 | 0.00 | 0.00 |
November | 205.09 | 141.21 | 63.88 | 316.82 | 94.19 | 0.00 | 0.00 | 0.00 |
December | 212.06 | 152.29 | 59.77 | 316.85 | 119.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.38 | 64.76 | 69.62 | 213.26 | 68.47 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 70.30 | 0.66 | 59.77 | 122.31 | 20.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.02 | 154.77 | 77.21 | 316.85 | 133.39 | 4.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231014E+09 | 0.154143E+09 | 76871375.21 | 0.271777E+09 | 0.154307E+09 |
February | 0.267804E+09 | 0.184361E+09 | 83442977.59 | 0.323474E+09 | 0.122039E+09 |
March | 0.321528E+09 | 0.199641E+09 | 0.121886E+09 | 0.398249E+09 | 0.115128E+09 |
April | 0.398227E+09 | 0.259219E+09 | 0.139008E+09 | 0.521306E+09 | 79704421.69 |
May | 0.393425E+09 | 0.224597E+09 | 0.168828E+09 | 0.550660E+09 | 36382231.29 |
June | 0.420266E+09 | 0.242553E+09 | 0.177713E+09 | 0.594164E+09 | 34883101.74 |
July | 0.404436E+09 | 0.207932E+09 | 0.196504E+09 | 0.570291E+09 | 29509244.10 |
August | 0.376875E+09 | 0.188325E+09 | 0.188550E+09 | 0.533996E+09 | 34526066.88 |
September | 0.313260E+09 | 0.156611E+09 | 0.156650E+09 | 0.436274E+09 | 39981923.49 |
October | 0.304056E+09 | 0.179565E+09 | 0.124491E+09 | 0.419012E+09 | 59844795.49 |
November | 0.242306E+09 | 0.165996E+09 | 76310874.48 | 0.303307E+09 | 0.109650E+09 |
December | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 0.136925E+09 |
Annual Sum or Average | 0.388460E+10 | 0.230261E+10 | 0.158199E+10 | 0.517607E+10 | 0.952881E+09 |
Minimum of Months | 0.211405E+09 | 0.139672E+09 | 71732841.45 | 0.253558E+09 | 29509244.10 |
Maximum of Months | 0.420266E+09 | 0.259219E+09 | 0.196504E+09 | 0.594164E+09 | 0.154307E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282532E+10 | 0.201494E+10 | 0.810379E+09 | 0.410364E+10 | 0.191267E+10 |
February | 0.231443E+10 | 0.149809E+10 | 0.816342E+09 | 0.343899E+10 | 0.147036E+10 |
March | 0.163590E+10 | 0.738281E+09 | 0.897617E+09 | 0.251057E+10 | 0.142643E+10 |
April | 0.117340E+10 | 0.274955E+09 | 0.898441E+09 | 0.199544E+10 | 0.921924E+09 |
May | 0.926445E+09 | 39372436.09 | 0.887073E+09 | 0.195827E+10 | 0.325204E+09 |
June | 0.885648E+09 | 8255052.06 | 0.877393E+09 | 0.192085E+10 | 0.294706E+09 |
July | 0.958034E+09 | 17608478.54 | 0.940425E+09 | 0.205588E+10 | 0.229041E+09 |
August | 0.112708E+10 | 0.135282E+09 | 0.991793E+09 | 0.242551E+10 | 0.328313E+09 |
September | 0.130868E+10 | 0.344891E+09 | 0.963786E+09 | 0.261346E+10 | 0.411485E+09 |
October | 0.209810E+10 | 0.109291E+10 | 0.100519E+10 | 0.385329E+10 | 0.706216E+09 |
November | 0.258384E+10 | 0.177900E+10 | 0.804841E+09 | 0.407455E+10 | 0.128020E+10 |
December | 0.276068E+10 | 0.198257E+10 | 0.778109E+09 | 0.417049E+10 | 0.170814E+10 |
Annual Sum or Average | 0.205976E+11 | 0.992616E+10 | 0.106714E+11 | 0.351209E+11 | 0.110147E+11 |
Minimum of Months | 0.885648E+09 | 8255052.06 | 0.778109E+09 | 0.192085E+10 | 0.229041E+09 |
Maximum of Months | 0.282532E+10 | 0.201494E+10 | 0.100519E+10 | 0.417049E+10 | 0.191267E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282532E+10 | 0.201494E+10 | 0.810379E+09 | 0.411559E+10 | 0.184297E+10 |
February | 0.231443E+10 | 0.149809E+10 | 0.816342E+09 | 0.344833E+10 | 0.141146E+10 |
March | 0.163590E+10 | 0.738281E+09 | 0.897617E+09 | 0.251882E+10 | 0.135768E+10 |
April | 0.117340E+10 | 0.274955E+09 | 0.898441E+09 | 0.199363E+10 | 0.871512E+09 |
May | 0.926445E+09 | 39372436.09 | 0.887073E+09 | 0.195135E+10 | 0.286932E+09 |
June | 0.885648E+09 | 8255052.06 | 0.877393E+09 | 0.191248E+10 | 0.257446E+09 |
July | 0.958034E+09 | 17608478.54 | 0.940425E+09 | 0.204965E+10 | 0.195088E+09 |
August | 0.112708E+10 | 0.135282E+09 | 0.991793E+09 | 0.241787E+10 | 0.290923E+09 |
September | 0.130868E+10 | 0.344891E+09 | 0.963786E+09 | 0.260682E+10 | 0.374117E+09 |
October | 0.209810E+10 | 0.109291E+10 | 0.100519E+10 | 0.384533E+10 | 0.664384E+09 |
November | 0.258384E+10 | 0.177900E+10 | 0.804841E+09 | 0.407293E+10 | 0.123751E+10 |
December | 0.276068E+10 | 0.198257E+10 | 0.778109E+09 | 0.417980E+10 | 0.164105E+10 |
Annual Sum or Average | 0.205976E+11 | 0.992616E+10 | 0.106714E+11 | 0.351126E+11 | 0.104311E+11 |
Minimum of Months | 0.885648E+09 | 8255052.06 | 0.778109E+09 | 0.191248E+10 | 0.195088E+09 |
Maximum of Months | 0.282532E+10 | 0.201494E+10 | 0.100519E+10 | 0.417980E+10 | 0.184297E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581274E+09 | 0.414549E+09 | 0.166725E+09 | 0.844177E+09 | 0.357277E+09 |
February | 0.476165E+09 | 0.308214E+09 | 0.167951E+09 | 0.703683E+09 | 0.274332E+09 |
March | 0.336565E+09 | 0.151892E+09 | 0.184673E+09 | 0.509668E+09 | 0.265792E+09 |
April | 0.241411E+09 | 56568474.08 | 0.184842E+09 | 0.391423E+09 | 0.173832E+09 |
May | 0.190604E+09 | 8100386.19 | 0.182503E+09 | 0.331249E+09 | 73138065.14 |
June | 0.182210E+09 | 1698373.70 | 0.180512E+09 | 0.317038E+09 | 68771787.54 |
July | 0.197103E+09 | 3622724.19 | 0.193480E+09 | 0.340594E+09 | 55991061.07 |
August | 0.231881E+09 | 27832674.19 | 0.204048E+09 | 0.413889E+09 | 78638180.61 |
September | 0.269243E+09 | 70957010.63 | 0.198286E+09 | 0.472490E+09 | 93356816.54 |
October | 0.431658E+09 | 0.224853E+09 | 0.206805E+09 | 0.731242E+09 | 0.153389E+09 |
November | 0.531592E+09 | 0.366007E+09 | 0.165585E+09 | 0.821199E+09 | 0.244136E+09 |
December | 0.567975E+09 | 0.407890E+09 | 0.160086E+09 | 0.848657E+09 | 0.320504E+09 |
Annual Sum or Average | 0.423768E+10 | 0.204218E+10 | 0.219550E+10 | 0.672531E+10 | 0.215916E+10 |
Minimum of Months | 0.182210E+09 | 1698373.70 | 0.160086E+09 | 0.317038E+09 | 55991061.07 |
Maximum of Months | 0.581274E+09 | 0.414549E+09 | 0.206805E+09 | 0.848657E+09 | 0.357277E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1623.52 | 921.79 | 1380.01 | 920.81 | 459.21 | 0.00 | 0.00 |
February | 2139.38 | 807.14 | 1771.19 | 1219.32 | 551.87 | 0.00 | 0.00 |
March | 2379.03 | 687.74 | 1920.71 | 1192.60 | 728.11 | 0.00 | 0.00 |
April | 3217.94 | 492.00 | 2458.19 | 1600.12 | 858.07 | 0.00 | 0.00 |
May | 3289.49 | 217.34 | 2350.21 | 1341.68 | 1008.53 | 0.00 | 0.00 |
June | 3667.68 | 215.33 | 2594.23 | 1497.24 | 1096.99 | 0.00 | 0.00 |
July | 3406.76 | 176.28 | 2415.99 | 1242.13 | 1173.86 | 0.00 | 0.00 |
August | 3189.94 | 206.25 | 2251.35 | 1125.00 | 1126.34 | 0.00 | 0.00 |
September | 2693.05 | 246.80 | 1933.71 | 966.73 | 966.97 | 0.00 | 0.00 |
October | 2503.06 | 357.50 | 1816.34 | 1072.67 | 743.67 | 0.00 | 0.00 |
November | 1872.26 | 676.85 | 1495.72 | 1024.66 | 471.05 | 0.00 | 0.00 |
December | 1514.68 | 817.95 | 1262.87 | 834.36 | 428.51 | 0.00 | 0.00 |
Annual Sum or Average | 2626.11 | 483.45 | 1970.88 | 1168.25 | 802.63 | 0.00 | 0.00 |
Minimum of Months | 1514.68 | 176.28 | 1262.87 | 834.36 | 428.51 | 0.00 | 0.00 |
Maximum of Months | 3667.68 | 921.79 | 2594.23 | 1600.12 | 1173.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1532.12 | 714.11 | 1054.85 | 752.29 | 302.56 | 0.00 | 0.00 |
February | 1421.54 | 607.79 | 956.69 | 619.25 | 337.44 | 0.00 | 0.00 |
March | 937.34 | 532.57 | 610.77 | 275.64 | 335.13 | 0.00 | 0.00 |
April | 769.85 | 355.68 | 452.70 | 106.08 | 346.62 | 0.00 | 0.00 |
May | 731.14 | 121.42 | 345.89 | 14.70 | 331.19 | 0.00 | 0.00 |
June | 741.07 | 113.70 | 341.69 | 3.18 | 338.50 | 0.00 | 0.00 |
July | 767.58 | 85.51 | 357.69 | 6.57 | 351.11 | 0.00 | 0.00 |
August | 905.58 | 122.58 | 420.80 | 50.51 | 370.29 | 0.00 | 0.00 |
September | 1008.28 | 158.75 | 504.89 | 133.06 | 371.83 | 0.00 | 0.00 |
October | 1438.65 | 263.67 | 783.34 | 408.05 | 375.30 | 0.00 | 0.00 |
November | 1571.97 | 493.90 | 996.85 | 686.34 | 310.51 | 0.00 | 0.00 |
December | 1557.08 | 637.75 | 1030.72 | 740.21 | 290.51 | 0.00 | 0.00 |
Annual Sum or Average | 1113.68 | 349.27 | 653.14 | 314.76 | 338.39 | 0.00 | 0.00 |
Minimum of Months | 731.14 | 85.51 | 341.69 | 3.18 | 290.51 | 0.00 | 0.00 |
Maximum of Months | 1571.97 | 714.11 | 1054.85 | 752.29 | 375.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1536.59 | 688.09 | 1054.85 | 752.29 | 302.56 | 0.00 | 0.00 |
February | 1425.40 | 583.44 | 956.69 | 619.25 | 337.44 | 0.00 | 0.00 |
March | 940.42 | 506.90 | 610.77 | 275.64 | 335.13 | 0.00 | 0.00 |
April | 769.15 | 336.23 | 452.70 | 106.08 | 346.62 | 0.00 | 0.00 |
May | 728.55 | 107.13 | 345.89 | 14.70 | 331.19 | 0.00 | 0.00 |
June | 737.84 | 99.32 | 341.69 | 3.18 | 338.50 | 0.00 | 0.00 |
July | 765.25 | 72.84 | 357.69 | 6.57 | 351.11 | 0.00 | 0.00 |
August | 902.73 | 108.62 | 420.80 | 50.51 | 370.29 | 0.00 | 0.00 |
September | 1005.72 | 144.34 | 504.89 | 133.06 | 371.83 | 0.00 | 0.00 |
October | 1435.68 | 248.05 | 783.34 | 408.05 | 375.30 | 0.00 | 0.00 |
November | 1571.35 | 477.43 | 996.85 | 686.34 | 310.51 | 0.00 | 0.00 |
December | 1560.56 | 612.70 | 1030.72 | 740.21 | 290.51 | 0.00 | 0.00 |
Annual Sum or Average | 1113.41 | 330.77 | 653.14 | 314.76 | 338.39 | 0.00 | 0.00 |
Minimum of Months | 728.55 | 72.84 | 341.69 | 3.18 | 290.51 | 0.00 | 0.00 |
Maximum of Months | 1571.35 | 688.09 | 1054.85 | 752.29 | 375.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 315.18 | 133.39 | 217.02 | 154.77 | 62.25 | 0.00 | 0.00 |
February | 290.87 | 113.40 | 196.83 | 127.40 | 69.42 | 0.00 | 0.00 |
March | 190.29 | 99.24 | 125.66 | 56.71 | 68.95 | 0.00 | 0.00 |
April | 151.01 | 67.06 | 93.14 | 21.82 | 71.31 | 0.00 | 0.00 |
May | 123.67 | 27.31 | 71.16 | 3.02 | 68.14 | 0.00 | 0.00 |
June | 122.31 | 26.53 | 70.30 | 0.66 | 69.64 | 0.00 | 0.00 |
July | 127.16 | 20.90 | 73.59 | 1.35 | 72.24 | 0.00 | 0.00 |
August | 154.53 | 29.36 | 86.57 | 10.39 | 76.18 | 0.00 | 0.00 |
September | 182.29 | 36.02 | 103.87 | 27.38 | 76.50 | 0.00 | 0.00 |
October | 273.01 | 57.27 | 161.16 | 83.95 | 77.21 | 0.00 | 0.00 |
November | 316.82 | 94.19 | 205.09 | 141.21 | 63.88 | 0.00 | 0.00 |
December | 316.85 | 119.66 | 212.06 | 152.29 | 59.77 | 0.00 | 0.00 |
Annual Sum or Average | 213.26 | 68.47 | 134.38 | 64.76 | 69.62 | 0.00 | 0.00 |
Minimum of Months | 122.31 | 20.90 | 70.30 | 0.66 | 59.77 | 0.00 | 0.00 |
Maximum of Months | 316.85 | 133.39 | 217.02 | 154.77 | 77.21 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434843E+10 | 0.246891E+10 | 0.369623E+10 | 0.246629E+10 | 0.122994E+10 | 0.00 | 0.00 |
February | 0.517559E+10 | 0.195263E+10 | 0.428486E+10 | 0.294977E+10 | 0.133509E+10 | 0.00 | 0.00 |
March | 0.637198E+10 | 0.184205E+10 | 0.514444E+10 | 0.319426E+10 | 0.195018E+10 | 0.00 | 0.00 |
April | 0.834090E+10 | 0.127527E+10 | 0.637163E+10 | 0.414751E+10 | 0.222412E+10 | 0.00 | 0.00 |
May | 0.881056E+10 | 0.582116E+09 | 0.629480E+10 | 0.359355E+10 | 0.270125E+10 | 0.00 | 0.00 |
June | 0.950662E+10 | 0.558130E+09 | 0.672425E+10 | 0.388085E+10 | 0.284341E+10 | 0.00 | 0.00 |
July | 0.912466E+10 | 0.472148E+09 | 0.647098E+10 | 0.332691E+10 | 0.314407E+10 | 0.00 | 0.00 |
August | 0.854394E+10 | 0.552417E+09 | 0.603001E+10 | 0.301321E+10 | 0.301680E+10 | 0.00 | 0.00 |
September | 0.698038E+10 | 0.639711E+09 | 0.501217E+10 | 0.250577E+10 | 0.250640E+10 | 0.00 | 0.00 |
October | 0.670419E+10 | 0.957517E+09 | 0.486489E+10 | 0.287304E+10 | 0.199185E+10 | 0.00 | 0.00 |
November | 0.485291E+10 | 0.175440E+10 | 0.387690E+10 | 0.265593E+10 | 0.122097E+10 | 0.00 | 0.00 |
December | 0.405693E+10 | 0.219080E+10 | 0.338248E+10 | 0.223475E+10 | 0.114773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.828171E+11 | 0.152461E+11 | 0.621536E+11 | 0.368418E+11 | 0.253118E+11 | 0.00 | 0.00 |
Minimum of Months | 0.405693E+10 | 0.472148E+09 | 0.338248E+10 | 0.223475E+10 | 0.114773E+10 | 0.00 | 0.00 |
Maximum of Months | 0.950662E+10 | 0.246891E+10 | 0.672425E+10 | 0.414751E+10 | 0.314407E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.410364E+10 | 0.191267E+10 | 0.282532E+10 | 0.201494E+10 | 0.810379E+09 | 0.00 | 0.00 |
February | 0.343899E+10 | 0.147036E+10 | 0.231443E+10 | 0.149809E+10 | 0.816342E+09 | 0.00 | 0.00 |
March | 0.251057E+10 | 0.142643E+10 | 0.163590E+10 | 0.738281E+09 | 0.897617E+09 | 0.00 | 0.00 |
April | 0.199544E+10 | 0.921924E+09 | 0.117340E+10 | 0.274955E+09 | 0.898441E+09 | 0.00 | 0.00 |
May | 0.195827E+10 | 0.325204E+09 | 0.926445E+09 | 39372436.09 | 0.887073E+09 | 0.00 | 0.00 |
June | 0.192085E+10 | 0.294706E+09 | 0.885648E+09 | 8255052.06 | 0.877393E+09 | 0.00 | 0.00 |
July | 0.205588E+10 | 0.229041E+09 | 0.958034E+09 | 17608478.54 | 0.940425E+09 | 0.00 | 0.00 |
August | 0.242551E+10 | 0.328313E+09 | 0.112708E+10 | 0.135282E+09 | 0.991793E+09 | 0.00 | 0.00 |
September | 0.261346E+10 | 0.411485E+09 | 0.130868E+10 | 0.344891E+09 | 0.963786E+09 | 0.00 | 0.00 |
October | 0.385329E+10 | 0.706216E+09 | 0.209810E+10 | 0.109291E+10 | 0.100519E+10 | 0.00 | 0.00 |
November | 0.407455E+10 | 0.128020E+10 | 0.258384E+10 | 0.177900E+10 | 0.804841E+09 | 0.00 | 0.00 |
December | 0.417049E+10 | 0.170814E+10 | 0.276068E+10 | 0.198257E+10 | 0.778109E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.351209E+11 | 0.110147E+11 | 0.205976E+11 | 0.992616E+10 | 0.106714E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192085E+10 | 0.229041E+09 | 0.885648E+09 | 8255052.06 | 0.778109E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417049E+10 | 0.191267E+10 | 0.282532E+10 | 0.201494E+10 | 0.100519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.411559E+10 | 0.184297E+10 | 0.282532E+10 | 0.201494E+10 | 0.810379E+09 | 0.00 | 0.00 |
February | 0.344833E+10 | 0.141146E+10 | 0.231443E+10 | 0.149809E+10 | 0.816342E+09 | 0.00 | 0.00 |
March | 0.251882E+10 | 0.135768E+10 | 0.163590E+10 | 0.738281E+09 | 0.897617E+09 | 0.00 | 0.00 |
April | 0.199363E+10 | 0.871512E+09 | 0.117340E+10 | 0.274955E+09 | 0.898441E+09 | 0.00 | 0.00 |
May | 0.195135E+10 | 0.286932E+09 | 0.926445E+09 | 39372436.09 | 0.887073E+09 | 0.00 | 0.00 |
June | 0.191248E+10 | 0.257446E+09 | 0.885648E+09 | 8255052.06 | 0.877393E+09 | 0.00 | 0.00 |
July | 0.204965E+10 | 0.195088E+09 | 0.958034E+09 | 17608478.54 | 0.940425E+09 | 0.00 | 0.00 |
August | 0.241787E+10 | 0.290923E+09 | 0.112708E+10 | 0.135282E+09 | 0.991793E+09 | 0.00 | 0.00 |
September | 0.260682E+10 | 0.374117E+09 | 0.130868E+10 | 0.344891E+09 | 0.963786E+09 | 0.00 | 0.00 |
October | 0.384533E+10 | 0.664384E+09 | 0.209810E+10 | 0.109291E+10 | 0.100519E+10 | 0.00 | 0.00 |
November | 0.407293E+10 | 0.123751E+10 | 0.258384E+10 | 0.177900E+10 | 0.804841E+09 | 0.00 | 0.00 |
December | 0.417980E+10 | 0.164105E+10 | 0.276068E+10 | 0.198257E+10 | 0.778109E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.351126E+11 | 0.104311E+11 | 0.205976E+11 | 0.992616E+10 | 0.106714E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191248E+10 | 0.195088E+09 | 0.885648E+09 | 8255052.06 | 0.778109E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417980E+10 | 0.184297E+10 | 0.282532E+10 | 0.201494E+10 | 0.100519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.844177E+09 | 0.357277E+09 | 0.581274E+09 | 0.414549E+09 | 0.166725E+09 | 0.00 | 0.00 |
February | 0.703683E+09 | 0.274332E+09 | 0.476165E+09 | 0.308214E+09 | 0.167951E+09 | 0.00 | 0.00 |
March | 0.509668E+09 | 0.265792E+09 | 0.336565E+09 | 0.151892E+09 | 0.184673E+09 | 0.00 | 0.00 |
April | 0.391423E+09 | 0.173832E+09 | 0.241411E+09 | 56568474.08 | 0.184842E+09 | 0.00 | 0.00 |
May | 0.331249E+09 | 73138065.14 | 0.190604E+09 | 8100386.19 | 0.182503E+09 | 0.00 | 0.00 |
June | 0.317038E+09 | 68771787.54 | 0.182210E+09 | 1698373.70 | 0.180512E+09 | 0.00 | 0.00 |
July | 0.340594E+09 | 55991061.07 | 0.197103E+09 | 3622724.19 | 0.193480E+09 | 0.00 | 0.00 |
August | 0.413889E+09 | 78638180.61 | 0.231881E+09 | 27832674.19 | 0.204048E+09 | 0.00 | 0.00 |
September | 0.472490E+09 | 93356816.54 | 0.269243E+09 | 70957010.63 | 0.198286E+09 | 0.00 | 0.00 |
October | 0.731242E+09 | 0.153389E+09 | 0.431658E+09 | 0.224853E+09 | 0.206805E+09 | 0.00 | 0.00 |
November | 0.821199E+09 | 0.244136E+09 | 0.531592E+09 | 0.366007E+09 | 0.165585E+09 | 0.00 | 0.00 |
December | 0.848657E+09 | 0.320504E+09 | 0.567975E+09 | 0.407890E+09 | 0.160086E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.672531E+10 | 0.215916E+10 | 0.423768E+10 | 0.204218E+10 | 0.219550E+10 | 0.00 | 0.00 |
Minimum of Months | 0.317038E+09 | 55991061.07 | 0.182210E+09 | 1698373.70 | 0.160086E+09 | 0.00 | 0.00 |
Maximum of Months | 0.848657E+09 | 0.357277E+09 | 0.581274E+09 | 0.414549E+09 | 0.206805E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.223170E+10 | -0.182575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -405953739.3 | 59.00 | 0.00 | 0.00 |
February | 0.201082E+10 | -0.164893E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -361891994.0 | 58.99 | 0.00 | 0.00 |
March | 0.219522E+10 | -0.179967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -395555055.5 | 58.99 | 0.00 | 0.00 |
April | 0.197747E+10 | -0.160596E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -371507994.0 | 58.99 | 0.00 | 0.00 |
May | 0.192136E+10 | -0.154466E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376701106.7 | 58.99 | 0.00 | 0.00 |
June | 0.178469E+10 | -0.142136E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363333903.0 | 58.99 | 0.00 | 0.00 |
July | 0.175427E+10 | -0.137997E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374305968.1 | 58.99 | 0.00 | 0.00 |
August | 0.181449E+10 | -0.143976E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374730981.7 | 58.99 | 0.00 | 0.00 |
September | 0.180380E+10 | -0.143981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363990093.4 | 58.99 | 0.00 | 0.00 |
October | 0.195188E+10 | -0.157352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -378359497.2 | 58.99 | 0.00 | 0.00 |
November | 0.200200E+10 | -0.162692E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -375075220.0 | 58.99 | 0.00 | 0.00 |
December | 0.218144E+10 | -0.178270E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -398747518.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236292E+11 | -0.190890E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.454015E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.175427E+10 | -0.182575E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -405953739.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.223170E+10 | -0.137997E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -361891994.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.84 | 0.50 | 02-JAN-11:30 | 272.08 | 6.79 | 0.00 | 23.67 | 227.06 | 5.44 | 0.00 | 5.83 |
February | 295.50 | 0.80 | 0.50 | 01-FEB-12:09 | 330.03 | 7.75 | 0.00 | 33.50 | 274.44 | 6.23 | 0.00 | 22.33 |
March | 296.00 | 0.75 | 0.50 | 02-MAR-12:50 | 406.79 | 8.97 | 0.00 | 99.67 | 342.15 | 7.45 | 0.00 | 62.33 |
April | 347.33 | 0.74 | 0.50 | 01-APR-09:09 | 426.88 | 10.30 | 0.00 | 122.33 | 355.97 | 8.62 | 0.00 | 76.67 |
May | 353.67 | 0.72 | 0.50 | 01-MAY-08:50 | 449.59 | 12.17 | 0.00 | 152.67 | 374.14 | 10.51 | 0.00 | 86.67 |
June | 394.00 | 0.71 | 0.50 | 01-JUN-09:09 | 460.86 | 12.70 | 0.00 | 163.00 | 387.98 | 11.04 | 0.00 | 100.67 |
July | 390.00 | 0.69 | 0.50 | 01-JUL-08:30 | 501.02 | 13.06 | 0.00 | 182.67 | 420.45 | 11.44 | 0.00 | 124.50 |
August | 380.83 | 0.69 | 0.50 | 01-AUG-08:30 | 777.30 | 12.27 | 0.00 | 196.00 | 726.47 | 10.60 | 0.00 | 130.33 |
September | 342.17 | 0.70 | 0.50 | 01-SEP-10:09 | 1832.85 | 10.95 | 0.00 | 166.33 | 1945.28 | 9.34 | 0.00 | 116.83 |
October | 330.00 | 0.73 | 0.50 | 04-OCT-10:00 | 436.57 | 9.66 | 0.00 | 113.33 | 363.95 | 8.08 | 0.00 | 74.00 |
November | 308.00 | 0.84 | 0.50 | 01-NOV-11:50 | 288.09 | 6.98 | 0.00 | 18.67 | 241.07 | 5.54 | 0.00 | 8.33 |
December | 282.83 | 0.85 | 0.50 | 11-DEC-11:30 | 268.74 | 6.91 | 0.00 | 9.83 | 223.10 | 5.52 | 0.00 | 2.17 |
Annual Sum or Average | 4027.67 | 0.75 | 550.63 | 10.11 | 0.00 | 1281.67 | 502.70 | 8.54 | 0.00 | 810.67 | ||
Minimum of Months | 282.83 | 0.69 | 0.50 | 268.74 | 6.79 | 0.00 | 9.83 | 223.10 | 5.44 | 0.00 | 2.17 | |
Maximum of Months | 394.00 | 0.85 | 0.50 | 1832.85 | 13.06 | 0.00 | 196.00 | 1945.28 | 11.44 | 0.00 | 130.33 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.903137E+09 | 43067.71 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681202E+09 | 43067.71 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.420537E+09 | 43067.71 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 194156.79 | 323.59 | 16-NOV-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528708E+09 | 43067.71 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.903137E+09 | 43067.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27409433.70 | 3341.83 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47920873.68 | 11018.14 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45879762.86 | 13787.52 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40717658.08 | 4708.28 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47920873.68 | 13787.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114876E+09 | 6329.24 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145087E+09 | 24674.80 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184496E+09 | 18534.76 | 12-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115370E+09 | 15789.63 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184496E+09 | 24674.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.509622E+10 | 26738.18 | 04-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358883E+10 | 29197.62 | 04-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289934E+10 | 26808.75 | 11-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256748E+09 | 6853.06 | 02-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 697203.51 | 830.35 | 07-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149723E+09 | 6134.10 | 27-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.981274E+09 | 19056.75 | 15-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397113E+10 | 30831.45 | 20-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509622E+10 | 30831.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.140980E+10 | 0.936002E+09 | 34812.94 | 20-JAN-07:02 | 16436.25 | 0.00 |
February | 0.00 | 0.00 | 0.207338E+10 | 0.139630E+10 | 35233.93 | 03-FEB-07:02 | 17322.27 | 0.00 |
March | 0.00 | 0.00 | 0.351784E+10 | 0.242832E+10 | 36180.97 | 07-MAR-07:02 | 21399.18 | 0.00 |
April | 0.00 | 0.00 | 0.811923E+10 | 0.589279E+10 | 36326.08 | 29-APR-06:02 | 22998.76 | 0.00 |
May | 0.00 | 0.00 | 0.211241E+11 | 0.147159E+11 | 37431.43 | 23-MAY-06:02 | 19102.30 | 0.00 |
June | 0.00 | 0.00 | 0.234791E+11 | 0.165044E+11 | 36960.92 | 05-JUN-05:02 | 23060.76 | 0.00 |
July | 0.00 | 0.00 | 0.264685E+11 | 0.175832E+11 | 37994.70 | 03-JUL-05:02 | 19919.53 | 0.00 |
August | 0.00 | 0.00 | 0.260579E+11 | 0.175520E+11 | 37467.17 | 11-AUG-05:02 | 21643.48 | 0.00 |
September | 0.00 | 0.00 | 0.220587E+11 | 0.143887E+11 | 37889.77 | 05-SEP-05:02 | 14432.20 | 0.00 |
October | 0.00 | 0.00 | 0.176008E+11 | 0.120587E+11 | 37630.84 | 08-OCT-07:02 | 20620.47 | 0.00 |
November | 0.00 | 0.00 | 0.546631E+10 | 0.374512E+10 | 36427.50 | 02-NOV-06:02 | 22705.71 | 0.00 |
December | 0.00 | 0.00 | 0.341662E+10 | 0.227462E+10 | 36258.79 | 15-DEC-07:02 | 22369.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160792E+12 | 0.109476E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.140980E+10 | 0.936002E+09 | 34812.94 | 14432.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.264685E+11 | 0.175832E+11 | 37994.70 | 23060.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167810E+11 | 0.110109E+11 | 208514.34 | 31-JAN-07:02 | 98905.57 | 0.00 |
February | 0.00 | 0.00 | 0.240147E+11 | 0.157185E+11 | 206523.90 | 26-FEB-09:02 | 103101.81 | 0.00 |
March | 0.00 | 0.00 | 0.354233E+11 | 0.246022E+11 | 210033.48 | 07-MAR-07:02 | 129069.29 | 0.00 |
April | 0.00 | 0.00 | 0.619995E+11 | 0.434623E+11 | 210365.96 | 29-APR-06:02 | 132047.30 | 0.00 |
May | 0.00 | 0.00 | 0.101775E+12 | 0.700025E+11 | 212437.37 | 23-MAY-06:02 | 126885.77 | 0.00 |
June | 0.00 | 0.00 | 0.106031E+12 | 0.729719E+11 | 211265.96 | 19-JUN-06:02 | 132075.02 | 0.00 |
July | 0.00 | 0.00 | 0.113036E+12 | 0.741010E+11 | 211280.31 | 31-JUL-06:02 | 130997.68 | 0.00 |
August | 0.00 | 0.00 | 0.112432E+12 | 0.745707E+11 | 211540.28 | 17-AUG-06:02 | 128924.00 | 0.00 |
September | 0.00 | 0.00 | 0.102415E+12 | 0.656912E+11 | 213809.13 | 17-SEP-08:62 | 125331.12 | 0.00 |
October | 0.00 | 0.00 | 0.869303E+11 | 0.590782E+11 | 213099.79 | 22-OCT-08:62 | 124540.14 | 0.00 |
November | 0.00 | 0.00 | 0.439001E+11 | 0.301654E+11 | 210735.54 | 01-NOV-06:02 | 131067.30 | 0.00 |
December | 0.00 | 0.00 | 0.294635E+11 | 0.193498E+11 | 211287.65 | 16-DEC-07:02 | 124204.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.834201E+12 | 0.560725E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167810E+11 | 0.110109E+11 | 206523.90 | 98905.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113036E+12 | 0.745707E+11 | 213809.13 | 132075.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.461230E+10 | 0.348604E+10 | 27560.05 | 31-JAN-07:02 | 13087.47 | 0.00 |
February | 0.00 | 0.00 | 0.589229E+10 | 0.435965E+10 | 27331.47 | 03-FEB-07:02 | 13653.54 | 0.00 |
March | 0.00 | 0.00 | 0.672799E+10 | 0.506392E+10 | 27845.93 | 07-MAR-07:02 | 17860.66 | 0.00 |
April | 0.00 | 0.00 | 0.104594E+11 | 0.773457E+10 | 28044.99 | 30-APR-08:62 | 13015.70 | 0.00 |
May | 0.00 | 0.00 | 0.183805E+11 | 0.126861E+11 | 28799.45 | 23-MAY-06:02 | 15109.34 | 0.00 |
June | 0.00 | 0.00 | 0.192801E+11 | 0.132698E+11 | 28843.61 | 05-JUN-05:02 | 17509.37 | 0.00 |
July | 0.00 | 0.00 | 0.213890E+11 | 0.139649E+11 | 29600.45 | 03-JUL-05:02 | 14054.88 | 0.00 |
August | 0.00 | 0.00 | 0.221168E+11 | 0.148718E+11 | 29254.70 | 11-AUG-05:02 | 16912.84 | 0.00 |
September | 0.00 | 0.00 | 0.202907E+11 | 0.134766E+11 | 29429.42 | 05-SEP-05:02 | 11300.28 | 0.00 |
October | 0.00 | 0.00 | 0.189203E+11 | 0.135738E+11 | 29299.04 | 08-OCT-07:02 | 12824.66 | 0.00 |
November | 0.00 | 0.00 | 0.105838E+11 | 0.804630E+10 | 27931.29 | 02-NOV-06:02 | 17986.37 | 0.00 |
December | 0.00 | 0.00 | 0.748605E+10 | 0.561065E+10 | 28033.46 | 16-DEC-07:02 | 12746.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166139E+12 | 0.116144E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.461230E+10 | 0.348604E+10 | 27331.47 | 11300.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221168E+11 | 0.148718E+11 | 29600.45 | 17986.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.318375E+10 | 0.228244E+10 | 24038.09 | 31-JAN-07:02 | 10975.38 | 0.00 |
February | 0.00 | 0.00 | 0.412332E+10 | 0.290026E+10 | 23819.42 | 03-FEB-07:02 | 11609.84 | 0.00 |
March | 0.00 | 0.00 | 0.472446E+10 | 0.335076E+10 | 24482.02 | 07-MAR-07:02 | 14369.11 | 0.00 |
April | 0.00 | 0.00 | 0.743917E+10 | 0.520941E+10 | 24571.25 | 29-APR-06:02 | 14486.34 | 0.00 |
May | 0.00 | 0.00 | 0.148525E+11 | 0.966425E+10 | 25391.81 | 23-MAY-06:02 | 11962.03 | 0.00 |
June | 0.00 | 0.00 | 0.158524E+11 | 0.102783E+11 | 25085.71 | 05-JUN-05:02 | 14232.71 | 0.00 |
July | 0.00 | 0.00 | 0.179214E+11 | 0.109665E+11 | 25772.50 | 03-JUL-05:02 | 11877.92 | 0.00 |
August | 0.00 | 0.00 | 0.184931E+11 | 0.116955E+11 | 25464.14 | 11-AUG-05:02 | 13624.74 | 0.00 |
September | 0.00 | 0.00 | 0.168129E+11 | 0.104631E+11 | 25620.42 | 05-SEP-05:02 | 9610.13 | 0.00 |
October | 0.00 | 0.00 | 0.157189E+11 | 0.106754E+11 | 25510.89 | 08-OCT-07:02 | 10894.35 | 0.00 |
November | 0.00 | 0.00 | 0.798129E+10 | 0.574927E+10 | 24592.29 | 02-NOV-06:02 | 14477.60 | 0.00 |
December | 0.00 | 0.00 | 0.544953E+10 | 0.388206E+10 | 24447.90 | 16-DEC-07:02 | 10950.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132553E+12 | 0.871173E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.318375E+10 | 0.228244E+10 | 23819.42 | 9610.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184931E+11 | 0.116955E+11 | 25772.50 | 14486.34 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133640E+09 | 0.03 | 147.52 | 01-JAN-18:00 | 0.08 |
February | 95844850.55 | 0.02 | 147.52 | 01-FEB-08:07 | 0.08 |
March | 92539380.93 | 0.02 | 147.52 | 01-MAR-08:07 | 0.08 |
April | 31826731.61 | 0.01 | 147.52 | 01-APR-14:10 | 0.08 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 265536.24 | 0.00 | 147.52 | 07-SEP-16:40 | 0.07 |
October | 14393539.61 | 0.00 | 147.52 | 17-OCT-07:05 | 0.08 |
November | 53819770.99 | 0.01 | 147.52 | 08-NOV-16:50 | 0.08 |
December | 0.110294E+09 | 0.02 | 147.52 | 01-DEC-08:07 | 0.08 |
Annual Sum or Average | 0.532624E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133640E+09 | 0.03 | 147.52 | 0.08 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117196E+10 | 0.32 | 1793.20 | 05-JAN-07:03 | 0.88 |
February | 0.106067E+10 | 0.32 | 1793.20 | 01-FEB-07:02 | 0.87 |
March | 0.118103E+10 | 0.32 | 1793.20 | 07-MAR-07:02 | 0.86 |
April | 0.112703E+10 | 0.32 | 1793.20 | 01-APR-06:02 | 0.86 |
May | 0.117795E+10 | 0.32 | 1793.20 | 01-MAY-06:02 | 0.86 |
June | 0.117926E+10 | 0.33 | 1793.20 | 01-JUN-06:02 | 0.87 |
July | 0.126597E+10 | 0.33 | 1793.20 | 01-JUL-05:03 | 0.86 |
August | 0.124453E+10 | 0.33 | 1793.20 | 01-AUG-06:02 | 0.86 |
September | 0.116714E+10 | 0.32 | 1793.20 | 01-SEP-05:01 | 0.87 |
October | 0.118053E+10 | 0.32 | 1793.20 | 01-OCT-08:62 | 0.87 |
November | 0.111051E+10 | 0.31 | 1793.20 | 01-NOV-06:02 | 0.86 |
December | 0.116646E+10 | 0.32 | 1793.20 | 11-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.140331E+11 | 0.32 | |||
Minimum of Months | 0.106067E+10 | 0.31 | 1793.20 | 0.86 | |
Maximum of Months | 0.126597E+10 | 0.33 | 1793.20 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.852950E+10 | 0.50 | 13297.45 | 01-JAN-09:02 | 1.37 |
February | 0.774711E+10 | 0.50 | 13297.45 | 01-FEB-07:02 | 1.36 |
March | 0.869369E+10 | 0.51 | 13297.45 | 01-MAR-07:02 | 1.37 |
April | 0.836308E+10 | 0.50 | 13297.45 | 01-APR-06:02 | 1.36 |
May | 0.866273E+10 | 0.50 | 13297.45 | 01-MAY-06:02 | 1.36 |
June | 0.845724E+10 | 0.51 | 13297.45 | 01-JUN-06:02 | 1.37 |
July | 0.862650E+10 | 0.50 | 13297.45 | 01-JUL-06:02 | 1.36 |
August | 0.875788E+10 | 0.51 | 13297.45 | 01-AUG-06:02 | 1.36 |
September | 0.840404E+10 | 0.50 | 13297.45 | 01-SEP-05:01 | 1.37 |
October | 0.858209E+10 | 0.50 | 13297.45 | 01-OCT-08:62 | 1.37 |
November | 0.824124E+10 | 0.50 | 13297.45 | 01-NOV-06:02 | 1.36 |
December | 0.855871E+10 | 0.50 | 13297.45 | 01-DEC-07:02 | 1.37 |
Annual Sum or Average | 0.101624E+12 | 0.50 | |||
Minimum of Months | 0.774711E+10 | 0.50 | 13297.45 | 1.36 | |
Maximum of Months | 0.875788E+10 | 0.51 | 13297.45 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849586E+09 | 0.33 | 1319.41 | 01-JAN-09:02 | 0.90 |
February | 0.772608E+09 | 0.33 | 1319.41 | 01-FEB-07:02 | 0.90 |
March | 0.863485E+09 | 0.33 | 1319.41 | 01-MAR-07:02 | 0.90 |
April | 0.834692E+09 | 0.33 | 1319.41 | 01-APR-06:02 | 0.89 |
May | 0.890667E+09 | 0.34 | 1319.41 | 01-MAY-06:02 | 0.89 |
June | 0.903129E+09 | 0.35 | 1319.41 | 01-JUN-06:02 | 0.90 |
July | 0.972607E+09 | 0.35 | 1319.41 | 01-JUL-05:03 | 0.89 |
August | 0.100889E+10 | 0.36 | 1319.41 | 01-AUG-06:02 | 0.89 |
September | 0.946549E+09 | 0.36 | 1319.41 | 01-SEP-05:01 | 0.90 |
October | 0.989832E+09 | 0.36 | 1319.41 | 01-OCT-08:62 | 0.90 |
November | 0.846424E+09 | 0.33 | 1319.41 | 01-NOV-06:02 | 0.90 |
December | 0.865232E+09 | 0.33 | 1319.41 | 02-DEC-07:02 | 0.90 |
Annual Sum or Average | 0.107437E+11 | 0.34 | |||
Minimum of Months | 0.772608E+09 | 0.33 | 1319.41 | 0.89 | |
Maximum of Months | 0.100889E+10 | 0.36 | 1319.41 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.705713E+09 | 0.33 | 1093.48 | 01-JAN-09:02 | 0.90 |
February | 0.641421E+09 | 0.33 | 1093.48 | 01-FEB-07:02 | 0.90 |
March | 0.718636E+09 | 0.33 | 1093.48 | 01-MAR-07:02 | 0.90 |
April | 0.689114E+09 | 0.33 | 1093.48 | 01-APR-06:02 | 0.89 |
May | 0.724494E+09 | 0.33 | 1093.48 | 01-MAY-06:02 | 0.89 |
June | 0.727939E+09 | 0.34 | 1093.48 | 01-JUN-06:02 | 0.90 |
July | 0.784481E+09 | 0.35 | 1093.48 | 01-JUL-06:02 | 0.89 |
August | 0.811111E+09 | 0.36 | 1093.48 | 01-AUG-06:02 | 0.89 |
September | 0.767798E+09 | 0.35 | 1093.48 | 01-SEP-05:01 | 0.90 |
October | 0.807651E+09 | 0.35 | 1093.48 | 01-OCT-08:62 | 0.90 |
November | 0.696438E+09 | 0.33 | 1093.48 | 01-NOV-06:02 | 0.89 |
December | 0.714552E+09 | 0.33 | 1093.48 | 09-DEC-07:02 | 0.90 |
Annual Sum or Average | 0.878935E+10 | 0.34 | |||
Minimum of Months | 0.641421E+09 | 0.33 | 1093.48 | 0.89 | |
Maximum of Months | 0.811111E+09 | 0.36 | 1093.48 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.153858E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159807E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209337E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.320235E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.634923E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.686704E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.757227E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.743907E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.640193E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.541939E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.248315E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.202915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.529936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153858E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.757227E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132571E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144458E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186530E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.258414E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.378132E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.388463E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.405998E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.405697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.368910E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.330379E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.205830E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167837E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337322E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132571E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.405998E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.194308E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215119E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247288E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.336728E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.531724E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.555699E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.607145E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.627174E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.569719E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.544364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.333197E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261628E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.502409E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194308E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.627174E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.147162E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161769E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186842E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.252005E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.431829E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.455111E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.503607E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.519528E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.470366E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.450692E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.258667E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.403751E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147162E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.519528E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117196E+10 | 0.140980E+10 | 0.903137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106067E+10 | 0.207338E+10 | 0.681202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118103E+10 | 0.351784E+10 | 0.420537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112703E+10 | 0.811923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117795E+10 | 0.211241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117926E+10 | 0.234791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126597E+10 | 0.264685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124453E+10 | 0.260579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116714E+10 | 0.220587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118053E+10 | 0.176008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111051E+10 | 0.546631E+10 | 194156.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116646E+10 | 0.341662E+10 | 0.528708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140331E+11 | 0.160792E+12 | 0.253378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106067E+10 | 0.140980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126597E+10 | 0.264685E+11 | 0.903137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.852950E+10 | 0.167810E+11 | 0.00 | 0.113379E+11 | 0.130489E+10 | 0.00 | 0.00 | 0.00 |
February | 0.774711E+10 | 0.240147E+11 | 0.00 | 0.699061E+10 | 0.211658E+10 | 0.00 | 0.00 | 0.00 |
March | 0.869369E+10 | 0.354233E+11 | 0.00 | 0.557381E+10 | 0.428558E+10 | 0.00 | 0.00 | 0.00 |
April | 0.836308E+10 | 0.619995E+11 | 0.00 | 0.529850E+09 | 0.104456E+11 | 0.00 | 0.00 | 0.00 |
May | 0.866273E+10 | 0.101775E+12 | 0.00 | 0.00 | 0.412882E+11 | 0.00 | 0.00 | 0.00 |
June | 0.845724E+10 | 0.106031E+12 | 0.00 | 0.00 | 0.462585E+11 | 0.00 | 0.00 | 0.00 |
July | 0.862650E+10 | 0.113036E+12 | 0.00 | 0.00 | 0.539136E+11 | 0.00 | 0.00 | 0.00 |
August | 0.875788E+10 | 0.112432E+12 | 0.00 | 0.00 | 0.501788E+11 | 0.00 | 0.00 | 0.00 |
September | 0.840404E+10 | 0.102415E+12 | 0.00 | 0.00 | 0.394419E+11 | 0.00 | 0.00 | 0.00 |
October | 0.858209E+10 | 0.869303E+11 | 0.00 | 0.286703E+09 | 0.303323E+11 | 0.00 | 0.00 | 0.00 |
November | 0.824124E+10 | 0.439001E+11 | 0.00 | 0.173904E+10 | 0.778913E+10 | 0.00 | 0.00 | 0.00 |
December | 0.855871E+10 | 0.294635E+11 | 0.00 | 0.839102E+10 | 0.390615E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101624E+12 | 0.834201E+12 | 0.00 | 0.348490E+11 | 0.291261E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.774711E+10 | 0.167810E+11 | 0.00 | 0.00 | 0.130489E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875788E+10 | 0.113036E+12 | 0.00 | 0.113379E+11 | 0.539136E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.849586E+09 | 0.461230E+10 | 27409433.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772608E+09 | 0.589229E+10 | 47920873.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863485E+09 | 0.672799E+10 | 45879762.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834692E+09 | 0.104594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.890667E+09 | 0.183805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.903129E+09 | 0.192801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.972607E+09 | 0.213890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100889E+10 | 0.221168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946549E+09 | 0.202907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989832E+09 | 0.189203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846424E+09 | 0.105838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865232E+09 | 0.748605E+10 | 40717658.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107437E+11 | 0.166139E+12 | 0.161928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.772608E+09 | 0.461230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100889E+10 | 0.221168E+11 | 47920873.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.705713E+09 | 0.318375E+10 | 0.114876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641421E+09 | 0.412332E+10 | 0.145087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.718636E+09 | 0.472446E+10 | 0.184496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689114E+09 | 0.743917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.724494E+09 | 0.148525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727939E+09 | 0.158524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.784481E+09 | 0.179214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811111E+09 | 0.184931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.767798E+09 | 0.168129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.807651E+09 | 0.157189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.696438E+09 | 0.798129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.714552E+09 | 0.544953E+10 | 0.115370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878935E+10 | 0.132553E+12 | 0.559829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.641421E+09 | 0.318375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811111E+09 | 0.184931E+11 | 0.184496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117196E+10 | 0.00 | 0.00 | 0.00 | 0.366622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106067E+10 | 0.00 | 0.00 | 0.00 | 0.537400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118103E+10 | 0.00 | 0.00 | 0.00 | 0.912331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112703E+10 | 0.00 | 0.00 | 0.00 | 0.207532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117795E+10 | 0.00 | 0.00 | 0.00 | 0.517128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117926E+10 | 0.00 | 0.00 | 0.00 | 0.568778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126597E+10 | 0.00 | 0.00 | 0.00 | 0.630630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124453E+10 | 0.00 | 0.00 | 0.00 | 0.619453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116714E+10 | 0.00 | 0.00 | 0.00 | 0.523479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118053E+10 | 0.00 | 0.00 | 0.00 | 0.423886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111051E+10 | 0.00 | 0.00 | 0.00 | 0.137264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116646E+10 | 0.00 | 0.00 | 0.00 | 0.862694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140331E+11 | 0.00 | 0.00 | 0.00 | 0.389605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106067E+10 | 0.00 | 0.00 | 0.00 | 0.366622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126597E+10 | 0.00 | 0.00 | 0.00 | 0.630630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.852950E+10 | 0.00 | 0.00 | 0.00 | 0.472759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.774711E+10 | 0.00 | 0.00 | 0.00 | 0.669873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.869369E+10 | 0.00 | 0.00 | 0.00 | 0.995927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.836308E+10 | 0.00 | 0.00 | 0.00 | 0.174783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.866273E+10 | 0.00 | 0.00 | 0.00 | 0.291505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.845724E+10 | 0.00 | 0.00 | 0.00 | 0.303890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.862650E+10 | 0.00 | 0.00 | 0.00 | 0.319733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.875788E+10 | 0.00 | 0.00 | 0.00 | 0.318118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.840404E+10 | 0.00 | 0.00 | 0.00 | 0.284870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858209E+10 | 0.00 | 0.00 | 0.00 | 0.244558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.824124E+10 | 0.00 | 0.00 | 0.00 | 0.123418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855871E+10 | 0.00 | 0.00 | 0.00 | 0.822499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101624E+12 | 0.00 | 0.00 | 0.00 | 0.235698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.774711E+10 | 0.00 | 0.00 | 0.00 | 0.472759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875788E+10 | 0.00 | 0.00 | 0.00 | 0.319733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.849586E+09 | 0.00 | 0.00 | 0.00 | 0.109350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772608E+09 | 0.00 | 0.00 | 0.00 | 0.137858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.863485E+09 | 0.00 | 0.00 | 0.00 | 0.160939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.834692E+09 | 0.00 | 0.00 | 0.00 | 0.253258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.890667E+09 | 0.00 | 0.00 | 0.00 | 0.442657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.903129E+09 | 0.00 | 0.00 | 0.00 | 0.465386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.972607E+09 | 0.00 | 0.00 | 0.00 | 0.509885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100889E+10 | 0.00 | 0.00 | 0.00 | 0.526285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946549E+09 | 0.00 | 0.00 | 0.00 | 0.475065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.989832E+09 | 0.00 | 0.00 | 0.00 | 0.445381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846424E+09 | 0.00 | 0.00 | 0.00 | 0.248554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865232E+09 | 0.00 | 0.00 | 0.00 | 0.175104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107437E+11 | 0.00 | 0.00 | 0.00 | 0.394972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.772608E+09 | 0.00 | 0.00 | 0.00 | 0.109350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100889E+10 | 0.00 | 0.00 | 0.00 | 0.526285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.705713E+09 | 0.00 | 0.00 | 0.00 | 0.765906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641421E+09 | 0.00 | 0.00 | 0.00 | 0.976265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.718636E+09 | 0.00 | 0.00 | 0.00 | 0.114979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.689114E+09 | 0.00 | 0.00 | 0.00 | 0.183094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.724494E+09 | 0.00 | 0.00 | 0.00 | 0.359379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.727939E+09 | 0.00 | 0.00 | 0.00 | 0.382317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.784481E+09 | 0.00 | 0.00 | 0.00 | 0.425159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811111E+09 | 0.00 | 0.00 | 0.00 | 0.438417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.767798E+09 | 0.00 | 0.00 | 0.00 | 0.393586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.807651E+09 | 0.00 | 0.00 | 0.00 | 0.369927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.696438E+09 | 0.00 | 0.00 | 0.00 | 0.189023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.714552E+09 | 0.00 | 0.00 | 0.00 | 0.128482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878935E+10 | 0.00 | 0.00 | 0.00 | 0.315858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.641421E+09 | 0.00 | 0.00 | 0.00 | 0.765906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811111E+09 | 0.00 | 0.00 | 0.00 | 0.438417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232096E+10 | 0.276018E+09 | 1875417.51 | 652420.34 | 34326508.76 | 0.438695E+09 | 0.323033E+09 | 3144.41 | 0.22 |
February | 0.147788E+10 | 0.406272E+09 | 0.00 | 1149840.80 | 24384450.96 | 0.336476E+09 | 0.484099E+09 | 0.00 | 0.24 |
March | 0.140743E+10 | 0.903459E+09 | 0.00 | 1042472.41 | 11407619.44 | 0.222648E+09 | 0.607227E+09 | 0.00 | 0.25 |
April | 0.251529E+09 | 0.211079E+10 | 0.00 | 2765853.30 | 11936757.72 | 0.00 | 0.108231E+10 | 0.00 | 0.31 |
May | 0.00 | 0.711819E+10 | 0.00 | 0.00 | 42593819.22 | 0.00 | 0.00 | 0.00 | 0.21 |
June | 298249.55 | 0.819597E+10 | 0.00 | 240646.24 | 36500137.93 | 0.00 | 2586924.29 | 0.00 | 0.21 |
July | 0.00 | 0.982293E+10 | 0.00 | 0.00 | 22630843.08 | 0.00 | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.915339E+10 | 0.00 | 0.00 | 15828030.40 | 0.00 | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.764147E+10 | 0.00 | 62785.74 | 30784230.13 | 0.00 | 676403.41 | 0.00 | 0.21 |
October | 96997311.68 | 0.559663E+10 | 0.00 | 2694561.06 | 15172543.24 | 0.00 | 0.715276E+09 | 0.00 | 0.25 |
November | 0.785464E+09 | 0.161383E+10 | 0.00 | 2811780.15 | 18370674.11 | 0.00 | 0.129432E+10 | 0.00 | 0.30 |
December | 0.192974E+10 | 0.975374E+09 | 5215343.55 | 835513.53 | 39606039.45 | 0.296729E+09 | 0.418018E+09 | 25803.66 | 0.23 |
Annual Sum or Average | 0.827030E+10 | 0.538143E+11 | 7090761.07 | 12255873.55 | 0.303542E+09 | 0.129455E+10 | 0.492754E+10 | 28948.06 | 0.24 |
Minimum of Months | 0.00 | 0.276018E+09 | 0.00 | 0.00 | 11407619.44 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.232096E+10 | 0.982293E+10 | 5215343.55 | 2811780.15 | 42593819.22 | 0.438695E+09 | 0.129432E+10 | 25803.66 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236544E+10 | 0.202242E+10 | 0.00 | 36234186.23 | 4585118.45 | 0.00 | 0.261715E+11 | 0.00 | 0.48 |
February | 0.151850E+10 | 0.266031E+10 | 0.00 | 34881629.67 | 3289757.82 | 0.00 | 0.200292E+11 | 0.00 | 0.51 |
March | 0.132573E+10 | 0.525661E+10 | 0.00 | 37734612.49 | 20128103.15 | 0.00 | 0.207460E+11 | 0.00 | 0.52 |
April | 99244395.54 | 0.987813E+10 | 0.00 | 31182051.73 | 60594067.91 | 0.00 | 0.953630E+10 | 0.00 | 0.52 |
May | 0.00 | 0.250560E+11 | 0.00 | 0.00 | 0.489922E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 59609.84 | 0.275053E+11 | 0.00 | 0.00 | 0.464137E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.332130E+11 | 0.00 | 0.00 | 0.485856E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.311747E+11 | 0.00 | 0.00 | 0.448352E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.289241E+11 | 0.00 | 0.00 | 0.375130E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 0.110972E+09 | 0.205589E+11 | 0.00 | 19258453.94 | 0.237206E+09 | 0.00 | 0.548303E+10 | 0.00 | 0.45 |
November | 0.197123E+09 | 0.712298E+10 | 0.00 | 43827480.68 | 73690997.79 | 0.00 | 0.180568E+11 | 0.00 | 0.55 |
December | 0.174959E+10 | 0.527787E+10 | 0.00 | 35075301.65 | 44057746.10 | 0.00 | 0.225768E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.736666E+10 | 0.198650E+12 | 0.00 | 0.238194E+09 | 0.270695E+10 | 0.00 | 0.122600E+12 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.202242E+10 | 0.00 | 0.00 | 3289757.82 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.236544E+10 | 0.332130E+11 | 0.00 | 43827480.68 | 0.489922E+09 | 0.00 | 0.261715E+11 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.673116E+09 | 0.516577E+09 | 0.00 | 9220059.88 | 2577.07 | 634074.98 | 0.446198E+10 | 0.00 | 0.75 |
February | 0.525080E+09 | 0.751013E+09 | 0.00 | 6275832.05 | 124648.98 | 8952213.06 | 0.282596E+10 | 0.00 | 0.70 |
March | 0.594960E+09 | 0.105626E+10 | 0.00 | 6217304.02 | 1341484.48 | 9992258.04 | 0.255496E+10 | 0.00 | 0.70 |
April | 92330641.68 | 0.197776E+10 | 0.00 | 3949394.92 | 1889178.15 | 0.00 | 0.110263E+10 | 0.00 | 0.62 |
May | 0.00 | 0.585824E+10 | 0.00 | 0.00 | 13074002.35 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.652786E+10 | 0.00 | 101322.15 | 11544022.91 | 0.00 | 3855873.61 | 0.00 | 0.41 |
July | 0.00 | 0.781343E+10 | 0.00 | 40026.01 | 13688598.81 | 0.00 | 31221.59 | 0.00 | 0.40 |
August | 0.00 | 0.741844E+10 | 0.00 | 5718.38 | 11431275.31 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.647137E+10 | 0.00 | 106569.36 | 9996719.92 | 0.00 | 951941.93 | 0.00 | 0.40 |
October | 28189864.91 | 0.495147E+10 | 0.00 | 3665730.60 | 4905167.35 | 0.00 | 0.800128E+09 | 0.00 | 0.52 |
November | 63768870.32 | 0.169282E+10 | 0.00 | 9009446.47 | 1563770.13 | 0.00 | 0.255525E+10 | 0.00 | 0.76 |
December | 0.524381E+09 | 0.113674E+10 | 0.00 | 8195558.37 | 1890908.97 | 2222708.47 | 0.344660E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.250183E+10 | 0.461720E+11 | 0.00 | 46786962.21 | 71452354.42 | 21801254.56 | 0.177523E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.516577E+09 | 0.00 | 0.00 | 2577.07 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.673116E+09 | 0.781343E+10 | 0.00 | 9220059.88 | 13688598.81 | 9992258.04 | 0.446198E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119995E+10 | 0.425816E+09 | 0.00 | 4788206.89 | 948739.67 | 29358087.24 | 0.266490E+10 | 0.00 | 0.58 |
February | 0.874807E+09 | 0.625972E+09 | 0.00 | 3456566.90 | 358846.90 | 38164292.94 | 0.170011E+10 | 0.00 | 0.56 |
March | 0.930640E+09 | 0.885587E+09 | 0.00 | 3171905.72 | 2195552.12 | 80189736.58 | 0.138867E+10 | 0.00 | 0.56 |
April | 0.168740E+09 | 0.168778E+10 | 0.00 | 2538865.06 | 5696830.78 | 0.00 | 0.888492E+09 | 0.00 | 0.56 |
May | 0.00 | 0.540250E+10 | 0.00 | 0.00 | 22607960.98 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 641550.20 | 0.613004E+10 | 0.00 | 73782.68 | 19772645.11 | 0.00 | 527798.93 | 0.00 | 0.41 |
July | 0.00 | 0.739131E+10 | 0.00 | 16391.31 | 17438395.64 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.703107E+10 | 0.00 | 0.00 | 11738753.18 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 17216.32 | 0.606266E+10 | 0.00 | 90826.00 | 12721671.97 | 0.00 | 1335541.82 | 0.00 | 0.40 |
October | 46499708.42 | 0.472449E+10 | 0.00 | 2513311.08 | 3846601.90 | 0.00 | 0.603433E+09 | 0.00 | 0.48 |
November | 0.183482E+09 | 0.153747E+10 | 0.00 | 6280188.70 | 3602295.89 | 0.00 | 0.198213E+10 | 0.00 | 0.66 |
December | 0.991590E+09 | 0.100032E+10 | 0.00 | 4952836.34 | 5006725.11 | 76214070.25 | 0.209613E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.439636E+10 | 0.429050E+11 | 0.00 | 27882880.67 | 0.105935E+09 | 0.223926E+09 | 0.113257E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.425816E+09 | 0.00 | 0.00 | 358846.90 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.119995E+10 | 0.739131E+10 | 0.00 | 6280188.70 | 22607960.98 | 80189736.58 | 0.266490E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:50
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.216798E+12 | 0.898021E+10 | 0.00 | 0.474509E+11 | 0.344759E+11 |
February | 0.244620E+12 | 0.647062E+10 | 0.00 | 0.302673E+11 | 0.468104E+11 |
March | 0.289670E+12 | 0.553031E+10 | 0.00 | 0.230679E+11 | 0.649120E+11 |
April | 0.338176E+12 | 0.847681E+09 | 0.00 | -0.123883E+11 | 0.111999E+12 |
May | 0.346923E+12 | -0.275623E+10 | 0.00 | -0.852905E+11 | 0.198475E+12 |
June | 0.348261E+12 | -0.226517E+10 | 0.00 | -0.951413E+11 | 0.209197E+12 |
July | 0.358740E+12 | -0.320229E+10 | 0.00 | -0.112694E+12 | 0.226445E+12 |
August | 0.327801E+12 | -0.332617E+10 | 0.00 | -0.105444E+12 | 0.226753E+12 |
September | 0.277478E+12 | -0.282894E+10 | 0.00 | -0.889669E+11 | 0.203985E+12 |
October | 0.268967E+12 | -0.116033E+10 | 0.00 | -0.582255E+11 | 0.176056E+12 |
November | 0.195655E+12 | 0.313915E+10 | 0.00 | 0.706581E+10 | 0.862670E+11 |
December | 0.194227E+12 | 0.728199E+10 | 0.00 | 0.301559E+11 | 0.591032E+11 |
Annual Sum or Average | 0.340732E+13 | 0.167108E+11 | 0.00 | -0.420142E+12 | 0.164448E+13 |
Minimum of Months | 0.194227E+12 | -0.332617E+10 | 0.00 | -0.112694E+12 | 0.344759E+11 |
Maximum of Months | 0.358740E+12 | 0.898021E+10 | 0.00 | 0.474509E+11 | 0.226753E+12 |