Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:30:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1317.02 | 574.12 | 574.12 |
Net Site Energy | 1317.02 | 574.12 | 574.12 |
Total Source Energy | 3998.24 | 1742.92 | 1742.92 |
Net Source Energy | 3998.24 | 1742.92 | 1742.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 604.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 82.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1234.08 | 82.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 604.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 82.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 604.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 48.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 82.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 332.07 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 537.96 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 332.07 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 537.96 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1234.082 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1234.082 | 100.00 |
Total On-Site and Utility Electric Sources | 1234.082 | 100.00 |
Total Electricity End Uses | 1234.082 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3628.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 5.1792 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.8188 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 11.8188 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 11.8188 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 8.0600 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 10.6996 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 10.6996 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 5.1792 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 11.8188 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 11.8188 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 11.8188 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 8.0600 | 6.19 | 0.0000 | |
Total | 2293.99 | 10.6996 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 10.6996 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 10.6996 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 12-JAN-12:20 | - | - | - | - | - | - | - | - | - | - | 28-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79209.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 15467.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15089.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4859.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 120538.24 | 4859.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 79209.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 15467.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15089.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4859.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1914.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 723.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 153.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 498.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 89.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3908.34 | 89.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 834.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 217.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1703.73 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 834.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 315.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 217.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1703.73 | 39.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.08 |
CORE_RETAIL DIRECT AIR | 7.81 |
POINT_OF_SALE DIRECT AIR | 1.41 |
FRONT_RETAIL DIRECT AIR | 1.19 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.229099 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 0.229099 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 6746.94 |
PSZ-AC:1 HEATING COIL | 50850.71 |
PSZ-AC:2 HEATING COIL | 200445.96 |
PSZ-AC:3 HEATING COIL | 34403.20 |
PSZ-AC:4 HEATING COIL | 29454.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.08 | 2.08 | 2.08 | 2.08 | 2.08 | 2.08 | 1.00 | 1.00 | 2.08 |
PSZ-AC:2 | 7.81 | 7.81 | 7.81 | 7.81 | 8.02 | 8.02 | 1.00 | 0.973627 | 8.02 |
PSZ-AC:3 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
PSZ-AC:4 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.00 | 1.19 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.08 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 8.02 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.41 | 0.178122 |
PSZ-AC:4_OA_CONTROLLER | 1.19 | 0.178122 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.08 | 2227.12 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.02 | 13519.59 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1555.57 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.19 | 1319.90 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.08 | 2.08 | 2.08 | 1.37 | 41257.41 | 50850.71 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.02 | 8.02 | 8.02 | 5.30 | 199276.25 | 200445.96 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 0.927308 | 32906.81 | 34403.20 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.786818 | 28907.71 | 29454.48 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 2.08 | 1.04 | 1.39 | 41257.41 | 20628.71 | 0.780020 | 0.780020 |
PSZ-AC:2 COOLING COIL | 8.02 | 4.01 | 5.35 | 199276.25 | 99638.12 | 0.701080 | 0.701080 |
PSZ-AC:3 COOLING COIL | 1.41 | 0.702506 | 0.936673 | 32906.81 | 16453.40 | 0.719850 | 0.719850 |
PSZ-AC:4 COOLING COIL | 1.19 | 0.596074 | 0.794767 | 28907.71 | 14453.85 | 0.708990 | 0.708990 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 5.179 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.249 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 33.339 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 8.060 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.060 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 1967.545 | 5.179 | 240.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1967.545 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 18915.730 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18915.730 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 1782.388 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.388 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 1782.388 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.388 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 96.720 | 8.060 | 49.907 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 96.720 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.253 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6308 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.15678677E-14 | 0.41668067E-16 | -0.13443164E-09 | -0.41464653E-17 |
25 | 8 | 0.19720454E-07 | 0.16552409E-12 | 0.35477227E-03 | -0.22422834E-09 |
26 | 7 | -0.11553319E-01 | 0.88069696E-08 | -0.22094443E-01 | 0.13136543E-03 |
27 | 6 | 0.38664784 | 0.30990522E-05 | 0.45613010 | -0.45273053E-02 |
28 | 5 | -5.0080263 | 0.11685699E-03 | -4.3185286 | 0.60920489E-01 |
29 | 4 | 32.195305 | 0.96442504E-03 | 20.960285 | -0.41140105 |
30 | 3 | -109.50767 | 0.21185031E-02 | -54.674808 | 1.4903667 |
31 | 2 | 195.42750 | 0.12000320E-02 | 77.004857 | -2.8736635 |
32 | 1 | -170.53507 | 0.12893930E-03 | -55.002816 | 2.7345555 |
33 | 0 | 57.057407 | 0.73918525E-06 | 15.601154 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 36 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 37 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CORE_RETAIL | 16 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.731 | 0.1928 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.867 | 0.602 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.237 | 6.240E-004 | 2.832E-004 | 0.368 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.203 | 1.270E-004 | 1.032E-004 | 7.495E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 1.389E-002 | 1.157E-003 | 3.817E-004 | 0.683 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.7229E-004 |
2 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.8519E-004 |
3 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5739E-004 |
4 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.4453E-004 |
5 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5218E-004 |
6 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.4015E-004 |
7 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.8996E-004 |
8 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.9043E-004 |
9 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.5857E-004 |
10 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.1266E-004 |
11 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.2348E-004 |
12 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.8985E-004 |
13 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.1504E-004 |
14 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.9240E-004 |
15 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 3.3656E-004 |
16 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.5584E-004 |
17 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.7204E-004 |
18 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4504E-004 |
19 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.3491E-004 |
20 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.3745E-004 |
21 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.3372E-004 |
22 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.3921E-004 |
23 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 3.6506E-004 |
24 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.5288E-004 |
25 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.8600E-004 |
26 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1845E-004 |
27 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.6931E-004 |
28 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1651E-004 |
29 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.7187E-004 |
30 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1807E-004 |
31 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 2.1191E-004 |
32 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.2226E-004 |
33 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.5362E-004 |
34 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.5118E-003 |
35 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.4741E-004 |
36 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.7330E-003 |
37 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.6587E-004 |
38 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.1695E-003 |
39 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.0604E-004 |
40 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 4.8996E-004 |
41 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 7.8966E-004 |
42 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 6.0661E-004 |
43 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 8.4396E-004 |
44 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 6.5190E-004 |
45 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 7.6018E-004 |
46 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 5.4582E-004 |
47 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.0930E-004 |
48 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 2.9411E-004 |
49 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.0670E-004 |
50 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3151E-004 |
51 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.2355E-004 |
52 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3073E-004 |
53 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 3.8346E-004 |
54 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3176E-004 |
55 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.3470E-004 |
56 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2341E-004 |
57 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.3959E-003 |
58 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.0922E-004 |
59 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.5982E-003 |
60 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.0909E-004 |
61 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.0716E-003 |
62 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.0542E-004 |
63 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 4.5161E-004 |
64 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.5950E-004 |
65 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.5286E-003 |
66 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.2031E-003 |
67 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.5377E-003 |
68 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.1993E-003 |
69 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.2882E-003 |
70 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.4981E-003 |
71 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.0002E-003 |
72 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.1197E-003 |
73 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.7641E-004 |
74 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 8.2932E-003 |
75 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.4414E-004 |
76 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 9.4015E-003 |
77 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.4591E-004 |
78 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 8.4790E-003 |
79 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.3409E-004 |
80 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.5970E-003 |
81 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 5.7994E-003 |
82 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.5157E-004 |
83 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 6.4452E-003 |
84 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.3935E-004 |
85 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 6.2433E-003 |
86 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.7367E-004 |
87 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.1741E-003 |
88 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.3050E-004 |
89 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.5078E-004 |
90 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3658E-004 |
91 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.2900E-004 |
92 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3365E-004 |
93 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 7.8997E-004 |
94 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3873E-004 |
95 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0842E-004 |
96 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3229E-004 |
97 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.0074E-003 |
98 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.8021E-004 |
99 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 8.4677E-004 |
100 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.0407E-004 |
101 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.1473E-003 |
102 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 6.9773E-004 |
103 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 2.4124E-003 |
104 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 9.7824E-004 |
105 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.9561E-004 |
106 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.5255E-003 |
107 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.5963E-004 |
108 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.2913E-003 |
109 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 3.0056E-004 |
110 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.7823E-003 |
111 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 4.0382E-004 |
112 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 4.1990E-003 |
113 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.2987E-003 |
114 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.0338E-004 |
115 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.1060E-003 |
116 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.8788E-004 |
117 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.5698E-003 |
118 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.1231E-004 |
119 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 3.2416E-003 |
120 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2265E-004 |
121 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.9228E-004 |
122 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2961E-004 |
123 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.4622E-004 |
124 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2629E-004 |
125 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 4.5060E-004 |
126 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3054E-004 |
127 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 5.5411E-004 |
128 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3150E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 24430.24663 | 29316.29595 | 1.73444 | 2.08133 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 13232.92790 | 15879.51349 | 0.54885 | 0.65861 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 91999.04141 | 110398.84969 | 6.51101 | 7.81321 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
4 | CORE_RETAIL | Heating | 40997.74111 | 49197.28933 | 1.68731 | 2.02477 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 15903.99706 | 19084.79648 | 1.17084 | 1.40501 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
6 | POINT_OF_SALE | Heating | 6315.08421 | 7578.10106 | 0.26363 | 0.31636 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 13494.48477 | 16193.38172 | 0.99346 | 1.19215 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
8 | FRONT_RETAIL | Heating | 6305.17158 | 7566.20590 | 0.26321 | 0.31585 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 5622.57439 | 6747.08926 | 0.19092 | 0.22910 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 31299.17 | 2.08133 | 2.08133 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 17620.45 | 0.65861 | 0.65861 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 149646.31 | 8.02485 | 8.02485 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 65547.71 | 2.02477 | 2.02477 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 22915.39 | 1.40501 | 1.40501 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 9094.89 | 0.31636 | 0.31636 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 20060.89 | 1.19215 | 1.19215 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 9082.99 | 0.31585 | 0.31585 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.08133 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.81321 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40501 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19215 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.22910 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 0.22910 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 6746.93955 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.08133 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.08133 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.08133 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08133 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.08133 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.08133 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.81321 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.81321 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.81321 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.81321 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.02485 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.02485 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97363 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40501 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40501 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40501 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40501 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40501 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40501 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19215 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19215 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19215 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19215 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19215 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19215 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.08133 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.02485 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.40501 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.19215 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.08133 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.08133 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2227.12365 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.08133 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.08133 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.08133 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37368 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.08133 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.04067 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.38755 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41257.41000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20628.70500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78002 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78002 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41257.41000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50850.70776 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 50850.70776 |
64 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.02485 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89033 |
66 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.02485 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13519.58984 |
68 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.02485 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.02485 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.02485 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.29640 |
72 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.02485 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.01243 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.34990 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 199276.25000 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 99638.12500 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
79 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 199276.25000 |
80 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 200445.95762 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
83 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 200445.95762 |
84 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40501 |
85 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
86 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40501 |
87 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1555.57068 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40501 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40501 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40501 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92731 |
92 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40501 |
93 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70251 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.93667 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32906.81000 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16453.40500 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71985 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71985 |
99 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32906.81000 |
100 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34403.19947 |
101 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
103 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 34403.19947 |
104 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19215 |
105 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
106 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19215 |
107 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1319.89779 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19215 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19215 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19215 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78682 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19215 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59607 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79477 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28907.71000 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14453.85500 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70899 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70899 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28907.71000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29454.47599 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
123 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 29454.47599 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 39622.0 | 11.34 | 11.34 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 192945.3 | 10.86 | 10.86 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 31799.6 | 11.84 | 11.84 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 27967.6 | 11.91 | 11.91 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.253 | 1.055 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 2.7489242460E-002 | 2.9697629353E-002 | Pass | Pass | 0.4587617313 | 3.2401677416 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 2.9762915364E-002 | 5.1257716883E-002 | Pass | Pass | 5.3302332108E-002 | 0.1616414067 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 2.9445971354E-002 | 5.3221071047E-002 | Pass | Pass | 3.3096085664E-002 | 0.1046022070 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 3.0278536251E-002 | 4.1631797071E-002 | Pass | Pass | 3.9248150466E-002 | 0.1092718148 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1232887729 | 0.3256947342 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2378.03 | -30.0 | 0.00 | -1090.6 | 2755.99 | 4013.40 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.227 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.046 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.055 | 1.253 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.420 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.601 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.602 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.861 | 0.251 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.861 | 0.251 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5032_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.861 | 0.251 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 107.73 | 3.357 | 0.328 | 0.328 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 107.73 | 3.357 | 0.328 | 0.328 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 5.1792 | 379.89 | 1967.54 | LightsWired | LTG_SCH_BACK | 32.16 | 168.00 | 31.72 | 0.0000 | Y | 11.71 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 11.8188 | 1600.48 | 18915.73 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 47.87 | 0.0000 | Y | 169.96 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 11.8188 | 150.81 | 1782.39 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 11.8188 | 150.81 | 1782.39 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 8.0600 | 12.00 | 96.72 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 10.6996 | 2293.99 | 24544.77 | 228.59 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.73 | 4728.93 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.73 | 4728.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 270.38 | AstronomicalClock | - | 41.85 | 41.85 | 2.12 | |
EXTERIOR_LIGHTS_B | 3472.03 | AstronomicalClock | - | 83.85 | 71.25 | 46.44 | |
Exterior Lighting Total | 3742.41 | 48.56 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41257.41 | 32181.60 | 9075.81 | 0.78 | 3.73 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 199276.25 | 139708.59 | 59567.66 | 0.70 | 3.40 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32906.81 | 23687.97 | 9218.84 | 0.72 | 3.80 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28907.71 | 20495.28 | 8412.43 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 39622.0 | 11.34 | 11.34 | ||||
PSZ-AC:2 COOLING COIL | 192945.3 | 10.86 | 10.86 | ||||
PSZ-AC:3 COOLING COIL | 31799.6 | 11.84 | 11.84 | ||||
PSZ-AC:4 COOLING COIL | 27967.6 | 11.91 | 11.91 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 6746.94 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 50850.71 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 200445.96 | 0.80 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 34403.20 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 29454.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.23 | 21.29 | 92.91 | 1.00 | 7.31 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.08 | 2227.12 | 1070.05 | 1.00 | 1.31 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.02 | 13519.59 | 1684.71 | 1.00 | 1.15 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1555.57 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1319.90 | 1107.16 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 24430.25 | 29316.30 | 77.17 | 1.734 | 2.081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00729 | 35.62 | 0.01077 | 0.232 | 0.00 |
CORE_RETAIL | 91999.04 | 110398.85 | 68.98 | 6.511 | 7.813 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00809 | 35.62 | 0.01077 | 1.890 | 0.00 |
POINT_OF_SALE | 15904.00 | 19084.80 | 126.55 | 1.171 | 1.405 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00743 | 42.80 | 0.01078 | 0.178 | 0.00 |
FRONT_RETAIL | 13494.48 | 16193.38 | 107.38 | 0.993 | 1.192 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00751 | 42.80 | 0.01078 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 0.00 | 41.89 | 0.01084 | 42.70 | 0.01078 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 13232.93 | 15879.51 | 41.80 | 0.549 | 0.659 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00832 | 12.70 | 0.00915 | 0.232 | 0.00 |
CORE_RETAIL | 40997.74 | 49197.29 | 30.74 | 1.687 | 2.025 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00811 | 12.70 | 0.00915 | 1.890 | 0.00 |
POINT_OF_SALE | 6315.08 | 7578.10 | 50.25 | 0.264 | 0.316 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00828 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_RETAIL | 6305.17 | 7566.21 | 50.17 | 0.263 | 0.316 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00828 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_ENTRY | 5622.57 | 6747.09 | 562.26 | 0.191 | 0.229 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 16.00 | 0.00902 | 12.70 | 0.00915 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.08 | 2.08 | 0.66 | 0.66 | 2.0813 | 2.0813 | 2.0813 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.02 | 8.02 | 2.02 | 2.02 | 8.0249 | 7.8132 | 8.0249 | 0.9736 | 1.0000 |
PSZ-AC:3 | 1.41 | 1.41 | 0.32 | 0.32 | 1.4050 | 1.4050 | 1.4050 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.19 | 1.19 | 0.32 | 0.32 | 1.1921 | 1.1921 | 1.1921 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 6746.940 | 6746.940 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6746.94 | 6746.94 | 0.229099 | 16.00 | 13.88 | 0.00901809 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 16.00 | 0.00901809 | 79.5639 | 6747.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 41257.410 | 32181.605 | 2.081330 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 20628.71 | 18790.70 | 1.387553 | 26.11 | 16.42 | 0.00767875 | 12.80 | 10.55 | 0.00700000 | 35.62 | 0.01076950 | 21.86 | 16.6898 | 23.89 | 0.00729180 | 39.5723 | 24430.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 50850.708 | 50850.708 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50850.71 | 50850.71 | 2.081332 | 19.80 | 14.77 | 0.00841043 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 11.1266 | 21.11 | 0.00831740 | 53.3534 | 13232.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 199276.250 | 139708.593 | 8.024850 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 99638.12 | 85296.83 | 5.349900 | 29.76 | 18.28 | 0.00840854 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 35.3339 | 23.89 | 0.00766635 | 41.5829 | 89820.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 200445.958 | 200445.958 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 200445.96 | 200445.96 | 8.024854 | 18.84 | 14.35 | 0.00835584 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 23.5559 | 21.11 | 0.00811006 | 52.0416 | 40997.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 32906.810 | 23687.967 | 1.405010 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 16453.40 | 14734.87 | 0.936673 | 27.19 | 16.96 | 0.00785899 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 19.0164 | 23.89 | 0.00743465 | 40.3413 | 15904.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 34403.199 | 34403.199 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34403.20 | 34403.20 | 1.405011 | 19.75 | 14.74 | 0.00839425 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.6776 | 21.11 | 0.00828403 | 53.1419 | 6315.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 28907.710 | 20495.277 | 1.192150 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 14453.85 | 12762.09 | 0.794767 | 27.62 | 17.22 | 0.00799864 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.4118 | 23.89 | 0.00750976 | 40.7440 | 13494.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 29454.476 | 29454.476 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29454.48 | 29454.48 | 1.192149 | 19.57 | 14.69 | 0.00841446 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.9412 | 21.11 | 0.00828466 | 53.1459 | 6305.17 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 6746.940 | 6746.940 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.229099 | 0.27574234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 6746.94 | 6746.94 | 1.0000 | 0.27574234 | 0.229099 | 16.00 | 13.88 | 0.00901809 | 38904.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6746.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 16.00 | 0.00901809 | 16.00 | 0.00901809 | 79.5639 | 6747.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41257.410 | 32181.605 | 2.081330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1144 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.081332 | 2.50508077 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 20628.71 | 18790.70 | 1.0000 | 1.67005223 | 1.387553 | 26.11 | 16.42 | 0.00767875 | 45809.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20628.71 | 35.62 | 0.01076950 | 21.86 | 0.23158056 | 16.6898 | 23.93 | 0.00729180 | 23.89 | 0.00729180 | 39.5723 | 24430.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50850.708 | 50850.708 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.081332 | 2.50508077 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50850.71 | 50850.71 | 1.0000 | 2.50508077 | 2.081332 | 19.80 | 14.77 | 0.00841043 | 41238.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50850.71 | 12.70 | 0.00915345 | 12.70 | 0.23158056 | 11.1266 | 20.69 | 0.00831740 | 21.11 | 0.00831740 | 53.3534 | 13232.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 199276.250 | 139708.593 | 8.024850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4711 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.024854 | 9.65867459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | Sensible | 99638.12 | 85296.83 | 1.0000 | 6.43911279 | 5.349900 | 29.76 | 18.28 | 0.00840854 | 51403.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99638.12 | 42.80 | 0.01078182 | 23.86 | 1.89032875 | 35.3339 | 23.89 | 0.00766635 | 23.89 | 0.00766635 | 41.5829 | 89820.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 200445.958 | 200445.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.024854 | 9.65867459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 200445.96 | 200445.96 | 1.0000 | 9.65867459 | 8.024854 | 18.84 | 14.35 | 0.00835584 | 40120.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 200445.96 | 12.70 | 0.00915345 | 12.70 | 1.89032875 | 23.5559 | 20.73 | 0.00811006 | 21.11 | 0.00811006 | 52.0416 | 40997.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32906.810 | 23687.967 | 1.405010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4495 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.405011 | 1.69106470 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 16453.40 | 14734.87 | 1.0000 | 1.12737532 | 0.936673 | 27.19 | 16.96 | 0.00785899 | 47371.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16453.40 | 42.80 | 0.01078182 | 23.86 | 0.17812154 | 19.0164 | 23.89 | 0.00743465 | 23.89 | 0.00743465 | 40.3413 | 15904.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34403.199 | 34403.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.405011 | 1.69106470 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34403.20 | 34403.20 | 1.0000 | 1.69106470 | 1.405011 | 19.75 | 14.74 | 0.00839425 | 41151.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34403.20 | 12.70 | 0.00915345 | 12.70 | 0.17812154 | 12.6776 | 20.78 | 0.00828403 | 21.11 | 0.00828403 | 53.1419 | 6315.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28907.710 | 20495.277 | 1.192150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7091 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.192149 | 1.43486413 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 14453.85 | 12762.09 | 1.0000 | 0.95657717 | 0.794767 | 27.62 | 17.22 | 0.00799864 | 48163.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14453.85 | 42.80 | 0.01078182 | 23.86 | 0.17812154 | 22.4118 | 23.89 | 0.00750976 | 23.89 | 0.00750976 | 40.7440 | 13494.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29454.476 | 29454.476 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.192149 | 1.43486413 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29454.48 | 29454.48 | 1.0000 | 1.43486413 | 1.192149 | 19.57 | 14.69 | 0.00841446 | 41016.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29454.48 | 12.70 | 0.00915345 | 12.70 | 0.17812154 | 14.9412 | 20.78 | 0.00828466 | 21.11 | 0.00828466 | 53.1459 | 6305.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3465.33 | 449.33 | 94.67 |
CORE_RETAIL | 4243.00 | 785.83 | 666.33 |
POINT_OF_SALE | 4611.00 | 70.83 | 37.00 |
FRONT_RETAIL | 4462.33 | 165.83 | 74.17 |
FRONT_ENTRY | 4315.67 | 4049.17 | 3627.83 |
Facility | 4660.33 | 4151.00 | 3628.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 12.67 | 0.00 | 3.50 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 5.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.67 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 18.33 | 0.00 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.06 | 8.18 | 2317.33 | 0.371 | 0.026 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.720 | 0.005 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.719 | 0.030 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.719 | 0.030 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 35.336 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.06 | 8.18 | 2317.33 | 0.360 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.696 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.699 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.697 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.06 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 128.37 | 258.43 | 9762.95 | 1600.48 | 1.8903 | 1.890 |
POINT_OF_SALE | PSZ-AC:3 | 12.10 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_RETAIL | PSZ-AC:4 | 12.10 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 157.59 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 2.492 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 4404470.52 | 0.00 | 4404470.52 | 751726.75 | 5156197.27 | 7303124.67 | 3480.89 | 5279.11 | 0.00 | 384.07 |
CORE_RETAIL | 35917978.45 | 0.00 | 35917978.45 | 644588.90 | 36562567.34 | 59613407.55 | 3482.00 | 5278.00 | 0.00 | 365.00 |
POINT_OF_SALE | 3392474.99 | 0.00 | 3392474.99 | 342830.12 | 3735305.11 | 5617240.89 | 3480.27 | 5279.73 | 0.00 | 416.94 |
FRONT_RETAIL | 3388875.76 | 0.00 | 3388875.76 | 342830.12 | 3731705.88 | 5617240.89 | 3480.85 | 5279.15 | 0.00 | 396.91 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 12070694.67 | 12070694.67 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 47103799.72 | 0.00 | 47103799.72 | 14152670.55 | 61256470.27 | 78597979.65 | 8760.00 | 5279.75 | 0.00 | 422.02 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.2316 | 0.0000 | 0.2316 | 0.0160 | 0.2476 | 0.2316 | 0.00 | 4913.00 | 0.00 |
CORE_RETAIL | 1.8903 | 0.0000 | 1.8903 | 0.0137 | 1.9041 | 1.8903 | 0.00 | 4913.00 | 0.00 |
POINT_OF_SALE | 0.1781 | 0.0000 | 0.1781 | 0.0073 | 0.1854 | 0.1781 | 0.00 | 4913.00 | 0.00 |
FRONT_RETAIL | 0.1781 | 0.0000 | 0.1781 | 0.0073 | 0.1854 | 0.1781 | 0.00 | 4913.00 | 0.00 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.6760 | 0.6760 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 2.4782 | 0.0000 | 2.4782 | 0.7204 | 3.1986 | 2.4923 | 4913.00 | 4913.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 6380481.12 | 0.00 | 6380481.12 | 7303124.67 | 3480.26 | 0.08 | 5279.66 | 383.96 |
PSZ-AC:2 | 52031933.36 | 0.00 | 52031933.36 | 59613407.55 | 3482.00 | 0.00 | 5278.00 | 365.00 |
PSZ-AC:3 | 4914459.86 | 0.00 | 4914459.86 | 5617240.89 | 3479.16 | 0.00 | 5280.84 | 416.69 |
PSZ-AC:4 | 4909257.96 | 0.00 | 4909257.96 | 5617240.89 | 3480.04 | 0.04 | 5279.92 | 396.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.3355 | 0.0000 | 0.3355 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 2.7384 | 0.0000 | 2.7384 | 1.8903 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.2580 | 0.0000 | 0.2580 | 0.1781 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.2580 | 0.0000 | 0.2580 | 0.1781 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 5296.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 5278.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 5329.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 5309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.3355 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 2.7384 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.2580 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.2580 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 467 |
Defaulted Fields | 432 |
Fields with Defaults | 1337 |
Autosized Fields | 76 |
Autosizable Fields | 182 |
Autocalculated Fields | 78 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
Electricity:Building | 423.75 | 2654.48 | 19-FEB-09:00 | 31913.37 | 02-JAN-16:30 |
Electricity:Zone:BACK_SPACE | 61.71 | 505.56 | 01-JAN-00:10 | 3581.97 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 423.75 | 2654.48 | 19-FEB-09:00 | 31913.37 | 02-JAN-16:30 |
InteriorLights:Electricity | 228.59 | 859.31 | 19-FEB-09:00 | 21142.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 11.71 | 45.71 | 01-JAN-00:10 | 822.83 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 228.59 | 859.31 | 19-FEB-09:00 | 21142.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 228.59 | 859.31 | 19-FEB-09:00 | 21142.33 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 11.71 | 45.71 | 01-JAN-00:10 | 822.83 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 228.59 | 859.31 | 19-FEB-09:00 | 21142.33 | 02-JAN-16:30 |
Electricity:Zone:CORE_RETAIL | 254.27 | 1405.96 | 19-FEB-09:00 | 21676.76 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 169.97 | 630.52 | 19-FEB-09:00 | 17024.16 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 169.97 | 630.52 | 19-FEB-09:00 | 17024.16 | 02-JAN-16:30 |
Electricity:Zone:POINT_OF_SALE | 75.76 | 575.93 | 01-JAN-00:10 | 4525.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 30.78 | 162.19 | 01-JAN-00:10 | 2042.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 4.84 | 01-JAN-00:10 | 87.05 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 4.84 | 01-JAN-00:10 | 87.05 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 4.84 | 01-JAN-00:10 | 87.05 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
ElectricityNet:Plant | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1234.08 | 2812.11 | 26-FEB-08:00 | 120538.24 | 10-AUG-16:00 |
Electricity:HVAC | 761.77 | 0.00 | 01-JAN-00:10 | 94299.59 | 10-AUG-16:00 |
Fans:Electricity | 157.39 | 0.00 | 01-JAN-00:10 | 15935.29 | 08-AUG-06:10 |
General:Fans:Electricity | 157.39 | 0.00 | 01-JAN-00:10 | 15935.29 | 08-AUG-06:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 604.38 | 0.00 | 01-JAN-00:10 | 79209.82 | 10-AUG-16:00 |
General:Cooling:Electricity | 604.38 | 0.00 | 01-JAN-00:10 | 79209.82 | 10-AUG-16:00 |
ExteriorLights:Electricity | 48.56 | 0.00 | 01-JAN-07:10 | 3742.41 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 48.56 | 0.00 | 01-JAN-07:10 | 3742.41 | 01-JAN-06:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 82.93 | 1862.00 | 17-JAN-08:10 | 4859.48 | 12-JAN-12:20 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 82.93 | 1862.00 | 17-JAN-08:10 | 4859.48 | 12-JAN-12:20 |
WaterSystems:NaturalGas | 82.93 | 1862.00 | 17-JAN-08:10 | 4859.48 | 12-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 82.93 | 1862.00 | 17-JAN-08:10 | 4859.48 | 12-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3219.19 | 0.00 | 01-JAN-00:10 | 390498.84 | 08-AUG-06:10 |
EnergyTransfer:Building | 1067.58 | 0.00 | 01-JAN-00:10 | 117022.59 | 04-JUL-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 160.29 | 0.00 | 01-JAN-00:10 | 22154.09 | 06-AUG-08:10 |
Heating:EnergyTransfer | 1.80 | 0.00 | 01-JAN-00:10 | 15942.65 | 21-MAY-07:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.16 | 0.00 | 01-JAN-00:10 | 2034.17 | 02-MAR-06:20 |
General:Heating:EnergyTransfer | 1.80 | 0.00 | 01-JAN-00:10 | 15942.65 | 21-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 0.16 | 0.00 | 01-JAN-00:10 | 2034.17 | 02-MAR-06:20 |
Cooling:EnergyTransfer | 1065.78 | 0.00 | 01-JAN-00:10 | 114481.14 | 06-AUG-08:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 160.13 | 0.00 | 01-JAN-00:10 | 22154.09 | 06-AUG-08:10 |
General:Cooling:EnergyTransfer | 1065.78 | 0.00 | 01-JAN-00:10 | 114481.14 | 06-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 160.13 | 0.00 | 01-JAN-00:10 | 22154.09 | 06-AUG-08:10 |
EnergyTransfer:Zone:CORE_RETAIL | 651.76 | 0.00 | 01-JAN-00:10 | 76924.71 | 04-JUL-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 1.48 | 0.00 | 01-JAN-00:10 | 12850.36 | 29-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 1.48 | 0.00 | 01-JAN-00:10 | 12850.36 | 29-MAY-07:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 650.28 | 0.00 | 01-JAN-00:10 | 71549.25 | 04-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 650.28 | 0.00 | 01-JAN-00:10 | 71549.25 | 04-JUL-08:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 144.77 | 0.00 | 01-JAN-00:10 | 13206.95 | 05-SEP-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.07 | 0.00 | 01-JAN-00:10 | 1279.92 | 02-MAR-06:20 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.07 | 0.00 | 01-JAN-00:10 | 1279.92 | 02-MAR-06:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 144.69 | 0.00 | 01-JAN-00:10 | 13206.95 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 144.69 | 0.00 | 01-JAN-00:10 | 13206.95 | 05-SEP-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 110.76 | 0.00 | 01-JAN-00:10 | 11220.34 | 05-SEP-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.08 | 0.00 | 01-JAN-00:10 | 1384.42 | 02-MAR-06:20 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.08 | 0.00 | 01-JAN-00:10 | 1384.42 | 02-MAR-06:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 110.68 | 0.00 | 01-JAN-00:10 | 11220.34 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 110.68 | 0.00 | 01-JAN-00:10 | 11220.34 | 05-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2151.61 | 0.00 | 01-JAN-00:10 | 292611.67 | 08-AUG-06:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2151.61 | 0.00 | 01-JAN-00:10 | 292611.67 | 08-AUG-06:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.157 | -160.126 | 0.000 | 0.000 | 4.890 | 11.714 | 49.992 | 0.000 | 0.000 | 3.641 | 91.090 | 0.000 | 0.000 | 0.000 | -1.359 | -0.002 |
CORE_RETAIL | 0.000 | 0.000 | 1.483 | -650.273 | 0.000 | 0.000 | 154.537 | 169.965 | 84.300 | 87.549 | 0.000 | 3.290 | 160.620 | 0.000 | -10.266 | 0.000 | -1.204 | -0.006 |
POINT_OF_SALE | 0.000 | 0.000 | 0.072 | -144.692 | 0.000 | 0.000 | 14.554 | 22.836 | 52.923 | 36.766 | 0.000 | 1.551 | 22.618 | 0.000 | -5.846 | 0.000 | -0.781 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.085 | -110.677 | 0.000 | 0.000 | 14.559 | 22.836 | 7.943 | 36.775 | 0.000 | 1.606 | 33.056 | 0.000 | -5.494 | 0.000 | -0.689 | -0.001 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.582 | 1.239 | 0.000 | 6.310 | 0.000 | 5.315 | 0.000 | 0.000 | -1.269 | 0.000 | -3.101 | -9.076 |
Total Facility | 0.000 | 0.000 | 1.796 | -1065.768 | 0.000 | 0.000 | 189.122 | 228.591 | 195.158 | 167.399 | 0.000 | 15.403 | 307.385 | 0.000 | -22.876 | 0.000 | -7.134 | -9.085 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | -38311.22 | 0.00 | 0.00 | 0.00 | 45.71 | 459.86 | 0.00 | 0.00 | 0.00 | 37808.18 | 0.00 | -0.00 | 0.00 | -2.52 | 0.00 |
CORE_RETAIL | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -176495.97 | 0.00 | 0.00 | 1632.82 | 3783.15 | 2067.82 | 0.00 | 0.00 | 0.00 | 170077.72 | 0.00 | -1046.48 | 0.00 | -19.06 | 0.00 |
POINT_OF_SALE | 10-MAY-05:01 | 0.00 | 0.00 | 0.00 | -29254.49 | 0.00 | 0.00 | 0.00 | 89.12 | 649.09 | 0.00 | 0.00 | 3.18 | 28774.15 | 0.00 | -261.04 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -25267.22 | 0.00 | 0.00 | 150.42 | 356.48 | 194.85 | 0.00 | 0.00 | 0.00 | 25082.63 | 0.00 | -508.32 | 0.00 | -8.84 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -267181.29 | 0.00 | 0.00 | 1996.65 | 4698.29 | 4787.13 | 0.00 | 0.00 | 0.00 | 257945.89 | 0.00 | -2183.24 | 0.00 | -63.42 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 05-AUG-05:07 | 0.00 | 0.00 | 3794.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.71 | 459.86 | 0.00 | 0.00 | 90.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4391.41 |
CORE_RETAIL | 06-AUG-07:06 | 0.00 | 0.00 | 28701.24 | 0.00 | 0.00 | 0.00 | 0.00 | 788.16 | 775.43 | 1942.27 | 0.00 | 40.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32248.06 |
POINT_OF_SALE | 06-AUG-07:04 | 0.00 | 0.00 | 2981.62 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 486.81 | 907.41 | 0.00 | 21.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4486.77 |
FRONT_RETAIL | 05-AUG-05:05 | 0.00 | 0.00 | 2842.12 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 73.07 | 326.54 | 0.00 | 41.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3372.68 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-AUG-07:06 | -8583.89 | 8583.89 | 30877.92 | -8583.89 | 0.00 | 0.00 | 0.00 | 1016.94 | 1795.17 | 3914.78 | 0.00 | 619.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29640.66 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.0813 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 2.0813 | 0.1113 | 1.0000 | Not calculated | 0.2316 | 0.1113 | ||
PSZ-AC:2 | 7.8132 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 8.0249 | 0.2356 | 1.0000 | Not calculated | 1.8903 | 0.2356 | ||
PSZ-AC:3 | 1.4050 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.4050 | 0.1268 | 1.0000 | Not calculated | 0.1781 | 0.1268 | ||
PSZ-AC:4 | 1.1921 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.1921 | 0.1494 | 1.0000 | Not calculated | 0.1781 | 0.1494 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.0813 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 2.0813 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.1113 | ||
PSZ-AC:2 | 7.8132 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.8132 | 1.0000 | 1.0000 | Not calculated | 1.8903 | 0.2419 | ||
PSZ-AC:3 | 1.4050 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.4050 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1268 | ||
PSZ-AC:4 | 1.1921 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.1921 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1494 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8903 | 1.0000 | 1.8903 | 1.000 | 1.8903 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8903 | 1.8903 | 1.8903 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0813 | 2.0813 | 2.0813 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8132 | 7.8132 | 7.8132 | No | 1.8903 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4050 | 1.4050 | 1.4050 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1921 | 1.1921 | 1.1921 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.0813 | 2.0813 | 2.0813 | 2.0813 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.8132 | 8.0249 | 7.8132 | 7.8132 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.4050 | 1.4050 | 1.4050 | 1.4050 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1921 | 1.1921 | 1.1921 | 1.1921 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0813 | 2.0813 | 2.0813 | No | 0.2316 | 0.3516 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.8132 | 7.8132 | 7.8132 | No | 1.8903 | 0.9336 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4050 | 1.4050 | 1.4050 | No | 0.1781 | 0.5630 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1921 | 1.1921 | 1.1921 | No | 0.1781 | 0.5639 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.0813 | 2.0813 | 2.0813 | 2.0813 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.8132 | 7.8132 | 7.8132 | 7.8132 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.4050 | 1.4050 | 1.4050 | 1.4050 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1921 | 1.1921 | 1.1921 | 1.1921 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 3.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 604.38 | 79209.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 228.59 | 21142.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 48.56 | 3742.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 157.39 | 15935.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 82.93 | 4859.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1234.08 |
Natural Gas | 0.00 | 82.93 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1317.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 99.65 |
Space Heating | 0.00 |
Space Cooling | 263.46 |
Fans (All) | 68.61 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 537.96 |
Subtotal | 537.96 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.15 |
Miscellaneous (All) | 36.15 |
Subtotal | 36.15 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.36 |
Space Heating | 0.00 |
Space Cooling | 45.89 |
Fans (All) | 11.95 |
Service Water Heating | 6.30 |
Receptacle Equipment | 14.82 |
Miscellaneous | 3.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 1677. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY HEATING SP | January | 16.00 | 365 | 15.56 | 365 |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 7269.33 | 1488.17 | 2.50 | 0.00 | 0.00 |
CORE_RETAIL | 7602.17 | 1157.83 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 6675.33 | 2046.00 | 38.67 | 0.00 | 0.00 |
FRONT_RETAIL | 7005.83 | 1732.00 | 22.17 | 0.00 | 0.00 |
FRONT_ENTRY | 2956.33 | 2281.17 | 2292.67 | 1210.83 | 19.00 |
Min | 2956.33 | 1157.83 | 0.00 | 0.00 | 0.00 |
Max | 7602.17 | 2281.17 | 2292.67 | 1210.83 | 19.00 |
Average | 6301.80 | 1741.03 | 471.20 | 242.17 | 3.80 |
Sum | 31509.00 | 8705.17 | 2356.00 | 1210.83 | 19.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 515.00 | 423.00 | 493.50 | 473.83 | 14.67 |
Min | 515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 423.00 | 493.50 | 473.83 | 14.67 |
Average | 147797.20 | 84.60 | 98.70 | 94.77 | 2.93 |
Sum | 738986.00 | 423.00 | 493.50 | 473.83 | 14.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 6358.00 | 2402.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 5817.17 | 2942.83 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 6135.83 | 2623.00 | 1.17 | 0.00 | 0.00 |
FRONT_RETAIL | 6213.17 | 2546.83 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 2032.67 | 3922.83 | 1694.33 | 953.00 | 157.17 |
Min | 2032.67 | 2402.00 | 0.00 | 0.00 | 0.00 |
Max | 6358.00 | 3922.83 | 1694.33 | 953.00 | 157.17 |
Average | 5311.37 | 2887.50 | 339.10 | 190.60 | 31.43 |
Sum | 26556.83 | 14437.50 | 1695.50 | 953.00 | 157.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16857.67 | 14.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 547202.83 | 62396.17 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 55930.00 | 70.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 55843.33 | 156.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 434.33 | 734.17 | 329.50 | 308.67 | 113.33 |
Min | 434.33 | 14.33 | 0.00 | 0.00 | 0.00 |
Max | 547202.83 | 62396.17 | 329.50 | 308.67 | 113.33 |
Average | 135253.63 | 12674.27 | 65.90 | 61.73 | 22.67 |
Sum | 676268.17 | 63371.33 | 329.50 | 308.67 | 113.33 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 8760.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 8760.00 |
Average | 0.00 | 0.00 | 0.00 | 1752.00 |
Sum | 0.00 | 0.00 | 0.00 | 8760.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 609599.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 609599.00 |
Average | 0.00 | 0.00 | 0.00 | 121919.80 |
Sum | 0.00 | 0.00 | 0.00 | 609599.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381419E+10 | 25043.26 | 30-JAN-07:02 | 20.17 | 17.39 | 0.289512E+09 | 326.81 | 31-JAN-15:00 | 22.60 | 16.53 |
February | 0.476121E+10 | 28599.29 | 08-FEB-07:02 | 21.08 | 18.76 | 0.265399E+09 | 326.81 | 25-FEB-14:00 | 22.00 | 15.87 |
March | 0.739727E+10 | 37689.07 | 27-MAR-06:02 | 22.67 | 13.33 | 0.304064E+09 | 326.82 | 30-MAR-14:20 | 27.33 | 20.20 |
April | 0.104634E+11 | 38311.28 | 29-APR-05:02 | 25.00 | 16.37 | 0.287595E+09 | 326.82 | 08-APR-15:30 | 25.00 | 16.37 |
May | 0.171054E+11 | 37950.64 | 05-MAY-05:02 | 26.00 | 15.80 | 0.297782E+09 | 326.83 | 22-MAY-14:00 | 37.00 | 23.71 |
June | 0.194232E+11 | 35062.80 | 01-JUN-05:01 | 28.67 | 21.41 | 0.293662E+09 | 326.84 | 02-JUN-14:30 | 39.50 | 21.96 |
July | 0.223309E+11 | 37188.26 | 22-JUL-04:02 | 32.08 | 20.78 | 0.291751E+09 | 326.83 | 29-JUL-10:50 | 39.92 | 24.53 |
August | 0.235219E+11 | 33426.27 | 06-AUG-06:02 | 34.98 | 22.48 | 0.304250E+09 | 326.80 | 08-AUG-14:09 | 36.17 | 30.22 |
September | 0.190341E+11 | 31581.37 | 26-SEP-05:01 | 26.25 | 18.48 | 0.287632E+09 | 326.83 | 02-SEP-11:09 | 26.25 | 18.48 |
October | 0.157577E+11 | 37361.62 | 20-OCT-05:01 | 23.17 | 16.23 | 0.291313E+09 | 326.83 | 06-OCT-14:00 | 23.17 | 16.23 |
November | 0.105387E+11 | 34940.07 | 18-NOV-07:02 | 20.75 | 15.04 | 0.280254E+09 | 326.82 | 14-NOV-15:00 | 20.75 | 15.04 |
December | 0.598222E+10 | 30887.17 | 10-DEC-09:02 | 23.60 | 19.20 | 0.291431E+09 | 326.82 | 02-DEC-15:20 | 23.60 | 19.20 |
Annual Sum or Average | 0.160130E+12 | 0.348464E+10 | ||||||||
Minimum of Months | 0.381419E+10 | 25043.26 | 20.17 | 13.33 | 0.265399E+09 | 326.80 | 20.75 | 15.04 | ||
Maximum of Months | 0.235219E+11 | 38311.28 | 34.98 | 22.48 | 0.304250E+09 | 326.84 | 39.92 | 30.22 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307598E+11 | 131320.74 | 29-JAN-09:02 | 23.22 | 19.02 | 0.915434E+10 | 10327.73 | 20-JAN-15:00 | 23.22 | 19.02 |
February | 0.323531E+11 | 131051.27 | 06-FEB-07:02 | 21.25 | 17.86 | 0.838626E+10 | 10327.85 | 10-FEB-15:30 | 21.80 | 13.67 |
March | 0.424552E+11 | 176496.12 | 23-MAR-06:02 | 22.83 | 12.05 | 0.960668E+10 | 10328.01 | 29-MAR-14:00 | 27.50 | 19.76 |
April | 0.492770E+11 | 174298.94 | 26-APR-06:02 | 23.97 | 12.28 | 0.908782E+10 | 10328.11 | 28-APR-14:00 | 35.00 | 23.22 |
May | 0.650679E+11 | 164469.61 | 11-MAY-05:01 | 28.00 | 16.07 | 0.941006E+10 | 10328.21 | 11-MAY-14:39 | 36.67 | 21.88 |
June | 0.688371E+11 | 146218.17 | 01-JUN-05:01 | 28.67 | 21.41 | 0.927981E+10 | 10327.93 | 17-JUN-10:09 | 34.33 | 24.93 |
July | 0.752606E+11 | 159790.86 | 04-JUL-07:01 | 31.33 | 17.56 | 0.921949E+10 | 10327.57 | 03-JUL-14:50 | 31.33 | 17.56 |
August | 0.782095E+11 | 133875.13 | 06-AUG-07:01 | 35.08 | 22.69 | 0.961449E+10 | 10327.20 | 26-AUG-10:30 | 37.05 | 25.85 |
September | 0.668970E+11 | 135341.96 | 26-SEP-06:02 | 26.10 | 17.87 | 0.908925E+10 | 10328.09 | 30-SEP-10:00 | 37.00 | 22.67 |
October | 0.590343E+11 | 161228.91 | 20-OCT-05:01 | 23.17 | 16.23 | 0.920561E+10 | 10328.00 | 18-OCT-14:39 | 23.17 | 16.23 |
November | 0.459445E+11 | 156521.53 | 19-NOV-09:02 | 25.40 | 16.09 | 0.885552E+10 | 10328.03 | 02-NOV-14:39 | 25.40 | 16.09 |
December | 0.361800E+11 | 136772.38 | 12-DEC-07:02 | 23.17 | 17.81 | 0.920513E+10 | 10327.88 | 02-DEC-12:39 | 23.17 | 17.81 |
Annual Sum or Average | 0.650276E+12 | 0.110114E+12 | ||||||||
Minimum of Months | 0.307598E+11 | 131051.27 | 21.25 | 12.05 | 0.838626E+10 | 10327.20 | 21.80 | 13.67 | ||
Maximum of Months | 0.782095E+11 | 176496.12 | 35.08 | 22.69 | 0.961449E+10 | 10328.21 | 37.05 | 25.85 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794550E+10 | 22598.52 | 29-JAN-09:02 | 23.22 | 19.02 | 0.866536E+09 | 973.24 | 10-JAN-15:39 | 23.22 | 19.02 |
February | 0.776468E+10 | 25279.39 | 05-FEB-09:02 | 23.55 | 16.79 | 0.791635E+09 | 973.23 | 02-FEB-15:00 | 23.55 | 16.79 |
March | 0.933858E+10 | 29158.11 | 28-MAR-05:02 | 25.67 | 14.74 | 0.905746E+09 | 973.23 | 11-MAR-16:19 | 25.67 | 14.74 |
April | 0.998263E+10 | 28698.27 | 29-APR-05:02 | 25.00 | 16.37 | 0.856438E+09 | 973.24 | 15-APR-15:00 | 25.00 | 16.37 |
May | 0.128512E+11 | 29255.40 | 10-MAY-05:01 | 28.00 | 15.72 | 0.886711E+09 | 973.27 | 22-MAY-14:00 | 37.00 | 23.71 |
June | 0.135715E+11 | 25626.29 | 02-JUN-05:01 | 27.00 | 17.61 | 0.874440E+09 | 973.28 | 03-JUN-13:30 | 39.40 | 23.88 |
July | 0.153950E+11 | 27734.22 | 04-JUL-07:01 | 31.33 | 17.56 | 0.868740E+09 | 973.27 | 29-JUL-10:50 | 39.92 | 24.53 |
August | 0.168112E+11 | 24410.50 | 06-AUG-06:02 | 34.98 | 22.48 | 0.905956E+09 | 973.11 | 08-AUG-14:09 | 36.17 | 30.22 |
September | 0.152223E+11 | 24462.06 | 26-SEP-05:01 | 26.25 | 18.48 | 0.856471E+09 | 973.29 | 30-SEP-11:09 | 37.00 | 22.76 |
October | 0.145544E+11 | 27815.75 | 20-OCT-05:01 | 23.17 | 16.23 | 0.867454E+09 | 973.30 | 04-OCT-14:00 | 23.17 | 16.23 |
November | 0.119643E+11 | 28046.04 | 05-NOV-07:01 | 21.17 | 15.81 | 0.834588E+09 | 973.24 | 03-NOV-14:39 | 21.17 | 15.81 |
December | 0.929364E+10 | 24245.54 | 27-DEC-07:02 | 20.92 | 15.39 | 0.868536E+09 | 973.24 | 22-DEC-15:00 | 20.92 | 15.39 |
Annual Sum or Average | 0.144695E+12 | 0.103833E+11 | ||||||||
Minimum of Months | 0.776468E+10 | 22598.52 | 20.92 | 14.74 | 0.791635E+09 | 973.11 | 20.92 | 14.74 | ||
Maximum of Months | 0.168112E+11 | 29255.40 | 34.98 | 22.48 | 0.905956E+09 | 973.30 | 39.92 | 30.22 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522746E+10 | 19429.09 | 29-JAN-09:02 | 23.22 | 19.02 | 0.864045E+09 | 973.21 | 28-JAN-15:00 | 23.22 | 19.02 |
February | 0.524924E+10 | 19031.02 | 05-FEB-09:02 | 23.55 | 16.79 | 0.790455E+09 | 973.21 | 03-FEB-15:30 | 23.55 | 16.79 |
March | 0.644251E+10 | 25267.28 | 23-MAR-06:02 | 22.83 | 12.05 | 0.905129E+09 | 973.22 | 24-MAR-14:09 | 27.00 | 20.21 |
April | 0.723181E+10 | 25029.85 | 26-APR-06:02 | 23.97 | 12.28 | 0.856347E+09 | 973.22 | 20-APR-14:00 | 23.97 | 12.28 |
May | 0.995780E+10 | 24961.33 | 11-MAY-05:01 | 28.00 | 16.07 | 0.886705E+09 | 973.23 | 22-MAY-14:00 | 37.00 | 23.71 |
June | 0.106976E+11 | 22035.30 | 01-JUN-05:01 | 28.67 | 21.41 | 0.874434E+09 | 973.25 | 02-JUN-14:20 | 39.67 | 22.17 |
July | 0.124609E+11 | 23839.56 | 04-JUL-07:01 | 31.33 | 17.56 | 0.868740E+09 | 973.26 | 29-JUL-15:50 | 40.75 | 21.50 |
August | 0.137619E+11 | 21066.93 | 06-AUG-06:02 | 34.98 | 22.48 | 0.905956E+09 | 973.23 | 26-AUG-10:09 | 36.42 | 25.59 |
September | 0.123508E+11 | 20464.02 | 26-SEP-05:01 | 26.25 | 18.48 | 0.856468E+09 | 973.24 | 30-SEP-11:09 | 37.00 | 22.76 |
October | 0.116477E+11 | 23635.84 | 20-OCT-05:01 | 23.17 | 16.23 | 0.867444E+09 | 973.26 | 18-OCT-14:20 | 23.17 | 16.23 |
November | 0.917620E+10 | 23889.29 | 05-NOV-07:01 | 21.17 | 15.81 | 0.834553E+09 | 973.26 | 02-NOV-14:09 | 21.17 | 15.81 |
December | 0.647534E+10 | 19520.65 | 10-DEC-09:02 | 23.60 | 19.20 | 0.868062E+09 | 973.22 | 02-DEC-16:30 | 23.60 | 19.20 |
Annual Sum or Average | 0.110679E+12 | 0.103783E+11 | ||||||||
Minimum of Months | 0.522746E+10 | 19031.02 | 21.17 | 12.05 | 0.790455E+09 | 973.21 | 21.17 | 12.28 | ||
Maximum of Months | 0.137619E+11 | 25267.28 | 34.98 | 22.48 | 0.905956E+09 | 973.26 | 40.75 | 25.59 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.84 | 63466390.98 | 110.71 | 28-JAN-14:09 | 27.67 | 14.14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.59 | 66432610.47 | 149.79 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.46 | 90183167.51 | 184.30 | 01-MAR-15:00 | 36.10 | 18.65 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.109467E+09 | 186.05 | 27-APR-14:09 | 36.90 | 20.91 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.56 | 0.146028E+09 | 186.05 | 05-MAY-14:09 | 36.92 | 20.64 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.24 | 0.151199E+09 | 186.05 | 01-JUN-14:09 | 40.00 | 21.79 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.02 | 0.156632E+09 | 186.05 | 01-JUL-11:20 | 39.00 | 26.32 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.164443E+09 | 186.05 | 01-AUG-14:09 | 39.83 | 25.67 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.04 | 0.147094E+09 | 186.05 | 01-SEP-14:09 | 38.97 | 25.46 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.132392E+09 | 186.05 | 04-OCT-14:09 | 36.00 | 21.07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.17 | 0.100503E+09 | 155.94 | 01-NOV-14:09 | 32.83 | 26.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.63 | 74747946.17 | 118.27 | 09-DEC-14:09 | 28.83 | 21.37 |
Annual Sum or Average | 0.00 | 0.140259E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.84 | 63466390.98 | 110.71 | 27.67 | 14.14 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.164443E+09 | 186.05 | 40.00 | 26.32 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3968018.45 | 1138.09 | 29-JAN-09:04 | 23.22 |
February | 3137431.76 | 1066.33 | 05-FEB-09:04 | 23.55 |
March | 14417541.00 | 2378.35 | 02-MAR-07:06 | 27.67 |
April | 18557874.42 | 1763.66 | 02-APR-08:20 | 26.80 |
May | 29659217.12 | 3324.29 | 21-MAY-08:06 | 31.67 |
June | 18339374.92 | 3000.98 | 11-JUN-07:17 | 32.33 |
July | 10756554.10 | 3176.05 | 11-JUL-05:06 | 32.83 |
August | 4765275.54 | 3795.20 | 05-AUG-05:07 | 35.00 |
September | 17154275.28 | 2963.32 | 04-SEP-07:07 | 31.55 |
October | 20842861.52 | 2290.10 | 15-OCT-08:06 | 27.67 |
November | 11778539.32 | 1912.62 | 11-NOV-09:06 | 25.52 |
December | 3622584.30 | 1290.11 | 12-DEC-07:06 | 23.17 |
Annual Sum or Average | 0.157000E+09 | |||
Minimum of Months | 3137431.76 | 1066.33 | 23.17 | |
Maximum of Months | 29659217.12 | 3795.20 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6734060.16 | 5844.80 | 29-JAN-09:04 | 23.22 |
February | 5749572.62 | 6392.43 | 05-FEB-09:04 | 23.55 |
March | 64039583.39 | 15496.56 | 02-MAR-07:06 | 27.67 |
April | 0.101015E+09 | 11574.56 | 02-APR-08:06 | 26.00 |
May | 0.239278E+09 | 24501.52 | 21-MAY-08:06 | 31.67 |
June | 0.201878E+09 | 21851.36 | 29-JUN-05:05 | 32.17 |
July | 0.209252E+09 | 26877.28 | 04-JUL-08:06 | 32.82 |
August | 0.215749E+09 | 28702.53 | 06-AUG-07:06 | 35.08 |
September | 0.165258E+09 | 20778.27 | 04-SEP-07:05 | 31.55 |
October | 0.196961E+09 | 16160.13 | 09-OCT-08:08 | 28.33 |
November | 67093397.94 | 11186.65 | 11-NOV-09:06 | 25.52 |
December | 9689635.32 | 6198.64 | 10-DEC-09:20 | 24.20 |
Annual Sum or Average | 0.148270E+10 | |||
Minimum of Months | 5749572.62 | 5844.80 | 23.22 | |
Maximum of Months | 0.239278E+09 | 28702.53 | 35.08 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 166298.86 | 983.78 | 29-JAN-09:04 | 23.22 |
February | 682547.95 | 1230.96 | 05-FEB-09:04 | 23.55 |
March | 5363980.25 | 1916.70 | 02-MAR-07:04 | 27.67 |
April | 7451413.79 | 1753.30 | 02-APR-08:04 | 26.00 |
May | 18415154.34 | 2115.01 | 23-MAY-05:04 | 30.40 |
June | 12292722.56 | 2098.03 | 18-JUN-07:04 | 29.92 |
July | 4268283.43 | 2541.57 | 11-JUL-05:04 | 32.83 |
August | 2928810.45 | 2981.84 | 06-AUG-07:04 | 35.08 |
September | 5735408.80 | 2180.00 | 04-SEP-07:05 | 31.55 |
October | 9472084.02 | 1453.46 | 11-OCT-05:04 | 26.83 |
November | 4230973.55 | 1365.11 | 20-NOV-06:04 | 25.85 |
December | 660322.92 | 1079.02 | 10-DEC-09:04 | 23.60 |
Annual Sum or Average | 71668000.92 | |||
Minimum of Months | 166298.86 | 983.78 | 23.22 | |
Maximum of Months | 18415154.34 | 2981.84 | 35.08 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 169065.71 | 790.36 | 29-JAN-09:04 | 23.22 |
February | 421256.82 | 915.20 | 05-FEB-09:04 | 23.55 |
March | 5475716.72 | 1742.20 | 02-MAR-07:04 | 27.67 |
April | 8095716.92 | 1524.58 | 02-APR-08:04 | 26.00 |
May | 18076774.37 | 1516.10 | 13-MAY-05:04 | 28.00 |
June | 15806135.32 | 2207.17 | 29-JUN-05:05 | 32.17 |
July | 8600616.22 | 2259.35 | 21-JUL-05:05 | 32.08 |
August | 5894443.43 | 2842.58 | 05-AUG-05:05 | 35.00 |
September | 9483366.61 | 2102.78 | 04-SEP-07:05 | 31.55 |
October | 9957826.96 | 1213.83 | 11-OCT-05:04 | 26.83 |
November | 2433084.46 | 1111.43 | 20-NOV-06:04 | 25.85 |
December | 402526.73 | 878.17 | 10-DEC-09:04 | 23.60 |
Annual Sum or Average | 84816530.28 | |||
Minimum of Months | 169065.71 | 790.36 | 23.22 | |
Maximum of Months | 18076774.37 | 2842.58 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.982287E+09 | 822.83 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.893751E+09 | 822.83 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.101948E+10 | 822.83 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.961881E+09 | 822.83 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.100088E+10 | 822.83 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.983769E+09 | 822.83 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.978996E+09 | 822.83 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.101948E+10 | 822.83 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.961881E+09 | 822.83 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.982287E+09 | 822.83 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.949868E+09 | 822.83 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.978996E+09 | 822.83 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.117136E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.893751E+09 | 822.83 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.101948E+10 | 822.83 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157425E+11 | 17024.16 | 02-JAN-16:30 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.136172E+11 | 17024.16 | 01-FEB-16:00 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.146234E+11 | 17024.16 | 01-MAR-17:19 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.133467E+11 | 15605.48 | 01-APR-16:00 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.136641E+11 | 14186.80 | 01-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.132608E+11 | 14186.80 | 05-JUN-16:00 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.131520E+11 | 14186.80 | 14-JUL-08:09 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.138095E+11 | 14186.80 | 12-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.133744E+11 | 15605.48 | 05-SEP-16:00 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.143382E+11 | 17024.16 | 03-OCT-16:00 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.149435E+11 | 17024.16 | 01-NOV-16:40 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.160933E+11 | 17024.16 | 01-DEC-16:19 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.169965E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.131520E+11 | 14186.80 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.160933E+11 | 17024.16 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.228363E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.228363E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.103918E+09 | 87.05 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94551584.52 | 87.05 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107853E+09 | 87.05 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101759E+09 | 87.05 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105885E+09 | 87.05 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.104075E+09 | 87.05 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103570E+09 | 87.05 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107853E+09 | 87.05 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101759E+09 | 87.05 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103918E+09 | 87.05 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100488E+09 | 87.05 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103570E+09 | 87.05 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123920E+10 | 0.00 | 0.00 | ||
Minimum of Months | 94551584.52 | 87.05 | 0.00 | 0.00 | |
Maximum of Months | 0.107853E+09 | 87.05 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.982287E+09 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3675720.81 | 0.335236E+09 |
February | 0.638757E+09 | 0.893751E+09 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25384948.30 | 0.329032E+09 |
March | 0.730614E+09 | 0.101948E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85791775.42 | 0.180342E+09 |
April | 0.690691E+09 | 0.961881E+09 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183169E+09 | 97219083.49 |
May | 0.715069E+09 | 0.100088E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417311E+09 | 15984875.65 |
June | 0.705176E+09 | 0.983769E+09 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545731E+09 | 4641860.56 |
July | 0.700584E+09 | 0.978996E+09 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722503E+09 | 0.00 |
August | 0.730614E+09 | 0.101948E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733791E+09 | 0.00 |
September | 0.690691E+09 | 0.961881E+09 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487598E+09 | 3865896.56 |
October | 0.699524E+09 | 0.982287E+09 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291171E+09 | 25707170.69 |
November | 0.673027E+09 | 0.949868E+09 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125318E+09 | 0.107537E+09 |
December | 0.700584E+09 | 0.978996E+09 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19811041.53 | 0.259311E+09 |
Annual Sum or Average | 0.837485E+10 | 0.117136E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364125E+10 | 0.135888E+10 |
Minimum of Months | 0.638757E+09 | 0.893751E+09 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3675720.81 | 0.00 |
Maximum of Months | 0.730614E+09 | 0.101948E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733791E+09 | 0.335236E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.157425E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3151973.80 | 0.305964E+09 |
February | 0.201852E+11 | 0.136172E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21785592.24 | 0.301071E+09 |
March | 0.230879E+11 | 0.146234E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73941173.45 | 0.164573E+09 |
April | 0.218263E+11 | 0.133467E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158371E+09 | 83653423.14 |
May | 0.225967E+11 | 0.136641E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372405E+09 | 10277283.32 |
June | 0.222841E+11 | 0.132608E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498409E+09 | 1919800.14 |
July | 0.221389E+11 | 0.131520E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661886E+09 | 0.00 |
August | 0.230879E+11 | 0.138095E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667897E+09 | 0.00 |
September | 0.218263E+11 | 0.133744E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444413E+09 | 1736919.27 |
October | 0.221054E+11 | 0.143382E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261501E+09 | 15881261.91 |
November | 0.212681E+11 | 0.149435E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109644E+09 | 88094302.29 |
December | 0.221389E+11 | 0.160933E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17022929.20 | 0.231129E+09 |
Annual Sum or Average | 0.264651E+12 | 0.169965E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329043E+10 | 0.120430E+10 |
Minimum of Months | 0.201852E+11 | 0.131520E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3151973.80 | 0.00 |
Maximum of Months | 0.230879E+11 | 0.160933E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667897E+09 | 0.305964E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1675698.97 | 0.179450E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11301637.24 | 0.179651E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36373375.25 | 0.103912E+09 |
April | 0.205665E+10 | 0.187525E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80417333.17 | 57580499.15 |
May | 0.212923E+10 | 0.195129E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180139E+09 | 11086279.42 |
June | 0.209978E+10 | 0.191792E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235115E+09 | 3763562.30 |
July | 0.208610E+10 | 0.190862E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309456E+09 | 0.00 |
August | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313088E+09 | 20936.63 |
September | 0.205665E+10 | 0.187525E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202212E+09 | 4997238.82 |
October | 0.208295E+10 | 0.191503E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119335E+09 | 25532818.95 |
November | 0.200405E+10 | 0.185183E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52749738.59 | 72328753.20 |
December | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8946580.10 | 0.143137E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228363E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155081E+10 | 0.781461E+09 |
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1675698.97 | 0.00 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313088E+09 | 0.179651E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1676224.23 | 0.166018E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11348399.34 | 0.163181E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37353632.88 | 89915044.46 |
April | 0.205665E+10 | 0.187525E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81730232.57 | 47045251.34 |
May | 0.212923E+10 | 0.195129E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186542E+09 | 7518596.83 |
June | 0.209978E+10 | 0.191792E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245652E+09 | 2007417.03 |
July | 0.208610E+10 | 0.190862E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321908E+09 | 0.00 |
August | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323557E+09 | 0.00 |
September | 0.205665E+10 | 0.187525E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210313E+09 | 3098904.49 |
October | 0.208295E+10 | 0.191503E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123273E+09 | 18921242.98 |
November | 0.200405E+10 | 0.185183E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53744581.87 | 61479414.32 |
December | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8970740.92 | 0.130017E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228363E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160607E+10 | 0.689201E+09 |
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1676224.23 | 0.00 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323557E+09 | 0.166018E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.103918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126957.65 | 0.887253E+09 |
February | 0.151369E+09 | 94551584.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13657411.97 | 0.648701E+09 |
March | 0.173136E+09 | 0.107853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88390780.83 | 0.435057E+09 |
April | 0.163676E+09 | 0.101759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282546E+09 | 0.102873E+09 |
May | 0.169453E+09 | 0.105885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807551E+09 | 9484038.04 |
June | 0.167108E+09 | 0.104075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953777E+09 | 7058508.24 |
July | 0.166020E+09 | 0.103570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115031E+10 | 181250.39 |
August | 0.173136E+09 | 0.107853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106491E+10 | 289438.31 |
September | 0.163676E+09 | 0.101759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659489E+09 | 8478221.08 |
October | 0.165769E+09 | 0.103918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270715E+09 | 48142644.49 |
November | 0.159490E+09 | 0.100488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20646434.66 | 0.250157E+09 |
December | 0.166020E+09 | 0.103570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2524711.22 | 0.702974E+09 |
Annual Sum or Average | 0.198462E+10 | 0.123920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531465E+10 | 0.310065E+10 |
Minimum of Months | 0.151369E+09 | 94551584.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126957.65 | 181250.39 |
Maximum of Months | 0.173136E+09 | 0.107853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115031E+10 | 0.887253E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 822.83 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.33 | 29-JAN-12:00 | 914.30 | 18-JAN-04:00 |
February | 785.10 | 01-FEB-15:09 | 822.83 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 394.54 | 05-FEB-19:03 | 807.05 | 10-FEB-23:00 |
March | 785.10 | 01-MAR-15:09 | 822.83 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 547.82 | 02-MAR-04:00 | 683.56 | 06-MAR-06:00 |
April | 785.10 | 01-APR-10:09 | 822.83 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 636.29 | 28-APR-13:20 | 559.10 | 05-APR-01:00 |
May | 785.10 | 01-MAY-14:09 | 822.83 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.41 | 21-MAY-13:00 | 185.90 | 01-MAY-05:00 |
June | 785.10 | 01-JUN-14:09 | 822.83 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.67 | 09-JUN-20:02 | 218.91 | 07-JUN-05:00 |
July | 785.10 | 01-JUL-10:09 | 822.83 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1351.93 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 785.10 | 01-AUG-14:09 | 822.83 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.94 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 785.10 | 01-SEP-14:09 | 822.83 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1381.82 | 04-SEP-18:02 | 167.68 | 25-SEP-05:00 |
October | 785.10 | 02-OCT-14:09 | 822.83 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 929.32 | 09-OCT-18:02 | 358.18 | 20-OCT-05:00 |
November | 785.10 | 01-NOV-14:09 | 822.83 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 567.86 | 19-NOV-19:03 | 487.93 | 22-NOV-06:00 |
December | 785.10 | 01-DEC-15:09 | 822.83 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.63 | 10-DEC-13:00 | 655.40 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 822.83 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 106.33 | 0.00 | |||||
Maximum of Months | 785.10 | 822.83 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.94 | 914.30 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 17024.16 | 02-JAN-16:30 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 29-JAN-12:00 | 890.08 | 18-JAN-04:00 |
February | 24809.68 | 01-FEB-15:09 | 17024.16 | 01-FEB-16:00 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.27 | 05-FEB-19:03 | 773.71 | 10-FEB-23:00 |
March | 24809.68 | 01-MAR-15:09 | 17024.16 | 01-MAR-17:19 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.35 | 02-MAR-04:00 | 634.99 | 06-MAR-06:00 |
April | 24809.68 | 01-APR-10:09 | 15605.48 | 01-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 545.60 | 28-APR-13:20 | 500.50 | 05-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 14186.80 | 01-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.64 | 21-MAY-13:00 | 151.24 | 01-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 14186.80 | 05-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 933.08 | 09-JUN-20:02 | 153.77 | 07-JUN-05:00 |
July | 24809.68 | 01-JUL-10:09 | 14186.80 | 14-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.55 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 24809.68 | 01-AUG-14:09 | 14186.80 | 12-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.44 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 24809.68 | 01-SEP-14:09 | 15605.48 | 05-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1192.87 | 04-SEP-18:02 | 121.96 | 25-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 17024.16 | 03-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 803.29 | 09-OCT-18:02 | 277.11 | 20-OCT-05:00 |
November | 24809.68 | 01-NOV-14:09 | 17024.16 | 01-NOV-16:40 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 490.61 | 19-NOV-19:03 | 424.88 | 22-NOV-06:00 |
December | 24809.68 | 01-DEC-15:09 | 17024.16 | 01-DEC-16:19 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 | 10-DEC-13:00 | 602.89 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 14186.80 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 0.00 | |||||
Maximum of Months | 24809.68 | 17024.16 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.44 | 890.08 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 29-JAN-12:00 | 523.66 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.62 | 05-FEB-19:03 | 447.49 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.29 | 01-MAR-13:00 | 370.43 | 17-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.18 | 28-APR-13:20 | 284.84 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 799.22 | 21-MAY-13:00 | 96.47 | 01-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 488.05 | 09-JUN-20:02 | 116.27 | 07-JUN-05:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 609.90 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 954.12 | 16-AUG-20:02 | 6.51 | 31-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 623.74 | 04-SEP-18:02 | 93.19 | 25-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 416.35 | 09-OCT-18:02 | 220.93 | 20-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 249.59 | 19-NOV-19:03 | 249.82 | 22-NOV-06:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 10-DEC-13:00 | 316.88 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 0.00 | |||||
Maximum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 954.12 | 523.66 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 29-JAN-12:00 | 472.28 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.51 | 05-FEB-19:03 | 404.25 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.29 | 01-MAR-13:00 | 322.11 | 17-MAR-21:20 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.18 | 28-APR-13:20 | 255.91 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 799.23 | 21-MAY-13:00 | 85.04 | 01-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 490.18 | 09-JUN-20:02 | 93.90 | 07-JUN-05:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 611.81 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 957.30 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 04-SEP-18:02 | 82.25 | 25-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 418.01 | 09-OCT-18:02 | 188.96 | 20-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.01 | 19-NOV-19:03 | 230.03 | 22-NOV-06:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 10-DEC-13:00 | 294.81 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 | 0.00 | |||||
Maximum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 957.30 | 472.28 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 87.05 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.81 | 23-JAN-12:53 | 2595.88 | 09-JAN-08:61 |
February | 186.05 | 01-FEB-15:09 | 87.05 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.63 | 05-FEB-12:03 | 2764.33 | 20-FEB-12:02 |
March | 186.05 | 01-MAR-15:09 | 87.05 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4024.76 | 27-MAR-11:01 | 2074.49 | 31-MAR-07:01 |
April | 186.05 | 01-APR-10:09 | 87.05 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5210.37 | 28-APR-11:01 | 1634.90 | 01-APR-07:01 |
May | 186.05 | 01-MAY-14:09 | 87.05 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5219.13 | 09-MAY-11:01 | 1247.87 | 01-MAY-07:01 |
June | 186.05 | 01-JUN-14:09 | 87.05 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5936.07 | 12-JUN-11:01 | 911.80 | 22-JUN-07:53 |
July | 186.05 | 01-JUL-10:09 | 87.05 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.03 | 21-JUL-11:01 | 223.83 | 20-JUL-10:53 |
August | 186.05 | 01-AUG-14:09 | 87.05 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6725.16 | 16-AUG-11:01 | 938.82 | 04-AUG-13:52 |
September | 186.05 | 01-SEP-14:09 | 87.05 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4181.00 | 26-SEP-11:01 | 724.25 | 25-SEP-07:02 |
October | 186.05 | 02-OCT-14:09 | 87.05 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2564.87 | 09-OCT-11:01 | 1435.12 | 29-OCT-07:01 |
November | 186.05 | 01-NOV-14:09 | 87.05 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.49 | 05-NOV-11:02 | 1734.86 | 22-NOV-08:61 |
December | 186.05 | 01-DEC-15:09 | 87.05 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.13 | 10-DEC-12:05 | 3568.96 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 87.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.81 | 223.83 | ||||
Maximum of Months | 186.05 | 87.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.03 | 3568.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25043.26 | 30-JAN-07:02 | 490.69 | 914.22 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
February | 28599.29 | 08-FEB-07:02 | 490.69 | 914.22 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
March | 37689.07 | 27-MAR-06:02 | 490.69 | 914.22 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
April | 38311.28 | 29-APR-05:02 | 0.00 | 274.24 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
May | 37950.64 | 05-MAY-05:02 | 0.00 | 274.24 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
June | 35062.80 | 01-JUN-05:01 | 0.00 | 319.94 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
July | 37188.26 | 22-JUL-04:02 | 0.00 | 274.24 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 180.20 | 0.00 |
August | 33426.27 | 06-AUG-06:02 | 0.00 | 228.53 | 2299.28 | 0.00 | 0.00 | 0.00 | 0.00 | 176.34 | 0.00 |
September | 31581.37 | 26-SEP-05:01 | 0.00 | 319.94 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
October | 37361.62 | 20-OCT-05:01 | 0.00 | 319.94 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 |
November | 34940.07 | 18-NOV-07:02 | 490.69 | 457.16 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 |
December | 30887.17 | 10-DEC-09:02 | 490.69 | 457.16 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25043.26 | 0.00 | 228.53 | 2299.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38311.28 | 490.69 | 914.22 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 180.20 | 65.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 131320.74 | 29-JAN-09:02 | 15506.05 | 7093.40 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
February | 131051.27 | 06-FEB-07:02 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 |
March | 176496.12 | 23-MAR-06:02 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
April | 174298.94 | 26-APR-06:02 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
May | 164469.61 | 11-MAY-05:01 | 0.00 | 6620.51 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 0.00 |
June | 146218.17 | 01-JUN-05:01 | 0.00 | 6620.51 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 0.00 |
July | 159790.86 | 04-JUL-07:01 | 0.00 | 6305.24 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 0.00 |
August | 133875.13 | 06-AUG-07:01 | 0.00 | 5517.09 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 33.24 | 0.00 |
September | 135341.96 | 26-SEP-06:02 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
October | 161228.91 | 20-OCT-05:01 | 0.00 | 6620.51 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 |
November | 156521.53 | 19-NOV-09:02 | 15506.05 | 6305.24 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
December | 136772.38 | 12-DEC-07:02 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 131051.27 | 0.00 | 5517.09 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 176496.12 | 15506.05 | 18915.73 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 33.24 | 48.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22598.52 | 29-JAN-09:02 | 1461.10 | 891.19 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.38 |
February | 25279.39 | 05-FEB-09:02 | 1461.10 | 891.19 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 |
March | 29158.11 | 28-MAR-05:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
April | 28698.27 | 29-APR-05:02 | 0.00 | 534.72 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
May | 29255.40 | 10-MAY-05:01 | 0.00 | 623.84 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 |
June | 25626.29 | 02-JUN-05:01 | 0.00 | 623.84 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
July | 27734.22 | 04-JUL-07:01 | 0.00 | 712.96 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
August | 24410.50 | 06-AUG-06:02 | 0.00 | 445.60 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 0.00 |
September | 24462.06 | 26-SEP-05:01 | 0.00 | 623.84 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
October | 27815.75 | 20-OCT-05:01 | 0.00 | 623.84 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
November | 28046.04 | 05-NOV-07:01 | 0.00 | 712.96 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 |
December | 24245.54 | 27-DEC-07:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22598.52 | 0.00 | 445.60 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29255.40 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 49.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19429.09 | 29-JAN-09:02 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 |
February | 19031.02 | 05-FEB-09:02 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
March | 25267.28 | 23-MAR-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 |
April | 25029.85 | 26-APR-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
May | 24961.33 | 11-MAY-05:01 | 0.00 | 623.84 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.00 |
June | 22035.30 | 01-JUN-05:01 | 0.00 | 623.84 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
July | 23839.56 | 04-JUL-07:01 | 0.00 | 712.96 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
August | 21066.93 | 06-AUG-06:02 | 0.00 | 445.60 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 | 0.00 |
September | 20464.02 | 26-SEP-05:01 | 0.00 | 623.84 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
October | 23635.84 | 20-OCT-05:01 | 0.00 | 623.84 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 |
November | 23889.29 | 05-NOV-07:01 | 0.00 | 712.96 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
December | 19520.65 | 10-DEC-09:02 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19031.02 | 0.00 | 445.60 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25267.28 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 | 32.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
April | 0.00 | 01-APR-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 17.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.697418E+11 | 61205.60 | 23-JAN-17:00 | 0.739480E+10 | 4859.48 | 12-JAN-12:20 |
February | 0.674721E+11 | 69866.23 | 07-FEB-16:30 | 0.664121E+10 | 4854.05 | 01-FEB-12:09 |
March | 0.814187E+11 | 71498.10 | 01-MAR-17:00 | 0.725702E+10 | 4829.41 | 01-MAR-12:39 |
April | 0.890740E+11 | 82617.12 | 28-APR-11:00 | 0.681141E+10 | 4784.83 | 03-APR-11:39 |
May | 0.111090E+12 | 95610.94 | 31-MAY-15:00 | 0.685393E+10 | 4743.17 | 01-MAY-11:30 |
June | 0.123019E+12 | 103761.25 | 09-JUN-14:09 | 0.652463E+10 | 4705.69 | 01-JUN-11:20 |
July | 0.140503E+12 | 117747.88 | 20-JUL-13:30 | 0.665743E+10 | 4687.14 | 31-JUL-11:00 |
August | 0.148711E+12 | 120538.24 | 10-AUG-15:00 | 0.675787E+10 | 4711.42 | 31-AUG-11:50 |
September | 0.125407E+12 | 107673.57 | 07-SEP-14:39 | 0.665741E+10 | 4748.62 | 29-SEP-11:50 |
October | 0.109109E+12 | 96449.13 | 07-OCT-15:00 | 0.704236E+10 | 4795.66 | 31-OCT-11:30 |
November | 0.905563E+11 | 83334.37 | 01-NOV-14:00 | 0.698165E+10 | 4835.10 | 30-NOV-12:39 |
December | 0.779787E+11 | 70652.20 | 05-DEC-17:30 | 0.735514E+10 | 4856.78 | 29-DEC-12:50 |
Annual Sum or Average | 0.123408E+13 | 0.829348E+11 | ||||
Minimum of Months | 0.674721E+11 | 61205.60 | 0.652463E+10 | 4687.14 | ||
Maximum of Months | 0.148711E+12 | 120538.24 | 0.739480E+10 | 4859.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.206587E+11 | 0.470143E+10 | 0.164409E+11 | 0.00 | 0.119347E+11 | 0.00 | 0.00 | 0.160060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180904E+11 | 0.404769E+10 | 0.149157E+11 | 0.00 | 0.108402E+11 | 0.00 | 0.00 | 0.195781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197258E+11 | 0.419171E+10 | 0.168545E+11 | 0.00 | 0.121648E+11 | 0.00 | 0.00 | 0.284819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181608E+11 | 0.374850E+10 | 0.160187E+11 | 0.00 | 0.117147E+11 | 0.00 | 0.00 | 0.394314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186734E+11 | 0.362586E+10 | 0.166477E+11 | 0.00 | 0.126071E+11 | 0.00 | 0.00 | 0.595361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181845E+11 | 0.339372E+10 | 0.162750E+11 | 0.00 | 0.138843E+11 | 0.00 | 0.00 | 0.712816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180518E+11 | 0.354951E+10 | 0.163892E+11 | 0.00 | 0.164201E+11 | 0.00 | 0.00 | 0.860926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189119E+11 | 0.376283E+10 | 0.168545E+11 | 0.00 | 0.175190E+11 | 0.00 | 0.00 | 0.916629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181886E+11 | 0.392140E+10 | 0.160144E+11 | 0.00 | 0.142810E+11 | 0.00 | 0.00 | 0.730015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192544E+11 | 0.435787E+10 | 0.164431E+11 | 0.00 | 0.124746E+11 | 0.00 | 0.00 | 0.565794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196975E+11 | 0.448052E+10 | 0.159174E+11 | 0.00 | 0.115860E+11 | 0.00 | 0.00 | 0.388748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209931E+11 | 0.478002E+10 | 0.163871E+11 | 0.00 | 0.119680E+11 | 0.00 | 0.00 | 0.238506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228591E+12 | 0.485611E+11 | 0.195158E+12 | 0.00 | 0.157395E+12 | 0.00 | 0.00 | 0.604377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.180518E+11 | 0.339372E+10 | 0.149157E+11 | 0.00 | 0.108402E+11 | 0.00 | 0.00 | 0.160060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209931E+11 | 0.478002E+10 | 0.168545E+11 | 0.00 | 0.175190E+11 | 0.00 | 0.00 | 0.916629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.739480E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.664121E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.725702E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.681141E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.685393E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.652463E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.665743E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.675787E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.665741E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.704236E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.698165E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.735514E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.829348E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.652463E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.739480E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21142.33 | 02-JAN-16:30 | 3742.41 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 9562.26 | 29-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 21142.33 | 01-FEB-16:00 | 3742.41 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 10296.87 | 09-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21142.33 | 01-MAR-17:19 | 3742.41 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 9945.81 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19723.65 | 01-APR-16:00 | 3742.41 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 11592.20 | 30-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 18304.97 | 01-MAY-16:49 | 3742.41 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 12219.23 | 30-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 18304.97 | 05-JUN-16:00 | 3742.41 | 01-JUN-05:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 14447.05 | 09-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 18304.97 | 14-JUL-08:09 | 3742.41 | 01-JUL-05:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 15800.98 | 20-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 18304.97 | 12-AUG-16:00 | 3742.41 | 01-AUG-05:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 15935.29 | 08-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 19723.65 | 05-SEP-16:00 | 3742.41 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 14818.10 | 10-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21142.33 | 03-OCT-16:00 | 3742.41 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 13929.89 | 08-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21142.33 | 01-NOV-16:40 | 3742.41 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 11618.04 | 03-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21142.33 | 01-DEC-16:19 | 3742.41 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 9905.05 | 12-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 18304.97 | 3742.41 | 10771.04 | 0.00 | 9562.26 | 0.00 | 0.00 | |||||
Maximum of Months | 21142.33 | 3742.41 | 10771.04 | 0.00 | 15935.29 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 22531.44 | 30-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33184.65 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38242.38 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50750.61 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60196.92 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66709.51 | 09-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76283.72 | 20-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79209.82 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69938.09 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60163.64 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47893.61 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31536.36 | 05-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22531.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79209.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61205.60 | 23-JAN-17:00 | 21142.33 | 10771.04 | 3742.41 | 0.00 | 7448.87 | 0.00 | 0.00 | 18100.95 | 0.00 |
February | 69866.23 | 07-FEB-16:30 | 19723.65 | 10771.04 | 0.00 | 0.00 | 7448.87 | 0.00 | 0.00 | 31922.67 | 0.00 |
March | 71498.10 | 01-MAR-17:00 | 21142.33 | 10771.04 | 0.00 | 0.00 | 7448.87 | 0.00 | 0.00 | 32135.85 | 0.00 |
April | 82617.12 | 28-APR-11:00 | 12630.25 | 10771.04 | 0.00 | 0.00 | 8465.22 | 0.00 | 0.00 | 50750.61 | 0.00 |
May | 95610.94 | 31-MAY-15:00 | 15467.61 | 10771.04 | 0.00 | 0.00 | 11095.17 | 0.00 | 0.00 | 58277.12 | 0.00 |
June | 103761.25 | 09-JUN-14:09 | 14048.93 | 10771.04 | 0.00 | 0.00 | 12231.78 | 0.00 | 0.00 | 66709.51 | 0.00 |
July | 117747.88 | 20-JUL-13:30 | 15467.61 | 10771.04 | 0.00 | 0.00 | 15225.51 | 0.00 | 0.00 | 76283.72 | 0.00 |
August | 120538.24 | 10-AUG-15:00 | 15467.61 | 10771.04 | 0.00 | 0.00 | 15089.77 | 0.00 | 0.00 | 79209.82 | 0.00 |
September | 107673.57 | 07-SEP-14:39 | 14048.93 | 10771.04 | 0.00 | 0.00 | 13863.78 | 0.00 | 0.00 | 68989.82 | 0.00 |
October | 96449.13 | 07-OCT-15:00 | 16886.29 | 10771.04 | 0.00 | 0.00 | 11253.62 | 0.00 | 0.00 | 57538.18 | 0.00 |
November | 83334.37 | 01-NOV-14:00 | 16886.29 | 10771.04 | 0.00 | 0.00 | 8902.04 | 0.00 | 0.00 | 46775.00 | 0.00 |
December | 70652.20 | 05-DEC-17:30 | 21142.33 | 10771.04 | 3742.41 | 0.00 | 7448.87 | 0.00 | 0.00 | 27547.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61205.60 | 12630.25 | 10771.04 | 0.00 | 0.00 | 7448.87 | 0.00 | 0.00 | 18100.95 | 0.00 | |
Maximum of Months | 120538.24 | 21142.33 | 10771.04 | 3742.41 | 0.00 | 15225.51 | 0.00 | 0.00 | 79209.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4859.48 | 12-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4854.05 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4829.41 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4784.83 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4743.17 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4705.69 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4687.14 | 31-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4711.42 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4748.62 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4795.66 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4835.10 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4856.78 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4687.14 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4859.48 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.23 | 0.00 | 26.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.67 | 1.67 | 25.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.99 | 1.50 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.75 | 0.33 | 25.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 25.87 | 3.50 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.23 | 1.67 | 26.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.39 | 0.00 | 28.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.40 | 0.00 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.44 | 0.00 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 29.48 | 0.00 | 29.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.39 | 0.00 | 28.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.41 | 0.00 | 28.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 28.62 | 0.00 | 28.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 29.48 | 0.00 | 29.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.37 | 0.00 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.36 | 0.00 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.36 | 0.00 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 28.36 | 0.00 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.37 | 0.00 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 192.83 | 23.61 | 22.50 | 23.64 | 0.00 | 23.64 |
February | 72.33 | 23.62 | 58.50 | 23.74 | 0.17 | 23.74 |
March | 39.67 | 23.77 | 115.17 | 23.86 | 0.00 | 23.86 |
April | 1.33 | 23.96 | 304.00 | 23.89 | 1.33 | 23.89 |
May | 4.00 | 24.01 | 418.00 | 23.89 | 4.00 | 23.90 |
June | 15.17 | 23.99 | 408.00 | 23.90 | 15.17 | 23.90 |
July | 21.83 | 24.02 | 415.00 | 23.90 | 21.83 | 23.91 |
August | 18.67 | 24.03 | 422.00 | 23.90 | 18.67 | 23.91 |
September | 16.50 | 24.01 | 405.00 | 23.90 | 16.50 | 23.90 |
October | 11.67 | 23.98 | 398.83 | 23.90 | 11.67 | 23.90 |
November | 1.83 | 23.97 | 346.50 | 23.89 | 1.83 | 23.89 |
December | 53.50 | 23.72 | 151.83 | 23.85 | 3.50 | 23.85 |
Annual Sum or Average | 449.33 | 23.72 | 3465.33 | 23.87 | 94.67 | 23.88 |
Minimum of Months | 1.33 | 23.61 | 22.50 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 192.83 | 24.03 | 422.00 | 23.90 | 21.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.67 | 23.04 | 176.33 | 23.66 | 0.00 | 23.66 |
February | 24.67 | 23.04 | 250.67 | 23.81 | 0.00 | 23.81 |
March | 10.67 | 23.33 | 294.67 | 23.87 | 0.00 | 23.87 |
April | 2.83 | 23.92 | 372.17 | 23.89 | 2.83 | 23.89 |
May | 12.33 | 23.92 | 416.67 | 23.89 | 12.33 | 23.89 |
June | 81.50 | 23.90 | 408.00 | 23.90 | 81.50 | 23.90 |
July | 180.00 | 23.90 | 415.00 | 23.90 | 180.00 | 23.90 |
August | 187.50 | 23.90 | 422.00 | 23.90 | 187.50 | 23.90 |
September | 121.67 | 23.90 | 405.00 | 23.90 | 121.67 | 23.90 |
October | 61.33 | 23.91 | 409.33 | 23.89 | 61.33 | 23.90 |
November | 9.50 | 23.90 | 386.33 | 23.89 | 9.50 | 23.89 |
December | 29.17 | 23.43 | 286.83 | 23.85 | 9.67 | 23.85 |
Annual Sum or Average | 785.83 | 23.78 | 4243.00 | 23.87 | 666.33 | 23.88 |
Minimum of Months | 2.83 | 23.04 | 176.33 | 23.66 | 0.00 | 23.66 |
Maximum of Months | 187.50 | 23.92 | 422.00 | 23.90 | 187.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.00 | 23.45 | 288.33 | 23.86 | 0.00 | 23.86 |
February | 6.83 | 23.36 | 317.33 | 23.88 | 0.00 | 23.88 |
March | 4.17 | 23.67 | 355.50 | 23.89 | 0.00 | 23.89 |
April | 0.50 | 24.00 | 394.00 | 23.89 | 0.50 | 23.89 |
May | 1.67 | 23.98 | 418.00 | 23.89 | 1.67 | 23.89 |
June | 8.83 | 23.95 | 408.00 | 23.89 | 8.83 | 23.89 |
July | 10.50 | 23.97 | 415.00 | 23.90 | 10.50 | 23.90 |
August | 7.83 | 23.98 | 422.00 | 23.89 | 7.83 | 23.90 |
September | 4.83 | 23.98 | 405.00 | 23.89 | 4.83 | 23.89 |
October | 2.83 | 24.00 | 414.00 | 23.89 | 2.83 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 23.89 |
December | 1.83 | 23.67 | 374.83 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 70.83 | 23.73 | 4611.00 | 23.89 | 37.00 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 288.33 | 23.86 | 0.00 | 23.86 |
Maximum of Months | 21.00 | 24.00 | 422.00 | 23.90 | 10.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.33 | 23.03 | 237.67 | 23.75 | 0.00 | 23.75 |
February | 22.67 | 23.06 | 296.67 | 23.83 | 0.17 | 23.83 |
March | 13.50 | 23.29 | 318.00 | 23.86 | 0.17 | 23.86 |
April | 1.83 | 23.93 | 380.67 | 23.89 | 1.83 | 23.89 |
May | 4.83 | 23.94 | 418.00 | 23.89 | 4.83 | 23.89 |
June | 18.17 | 23.93 | 408.00 | 23.89 | 18.17 | 23.90 |
July | 18.83 | 23.95 | 415.00 | 23.90 | 18.83 | 23.90 |
August | 14.50 | 23.96 | 422.00 | 23.90 | 14.50 | 23.90 |
September | 9.33 | 23.97 | 405.00 | 23.89 | 9.33 | 23.90 |
October | 5.50 | 23.98 | 414.00 | 23.89 | 5.50 | 23.89 |
November | 0.83 | 23.98 | 398.33 | 23.89 | 0.83 | 23.89 |
December | 9.50 | 23.32 | 349.00 | 23.87 | 0.00 | 23.87 |
Annual Sum or Average | 165.83 | 23.48 | 4462.33 | 23.88 | 74.17 | 23.88 |
Minimum of Months | 0.83 | 23.03 | 237.67 | 23.75 | 0.00 | 23.75 |
Maximum of Months | 46.33 | 23.98 | 422.00 | 23.90 | 18.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 228.17 | 22.04 | 166.67 | 22.90 | 35.33 | 22.96 |
February | 190.83 | 24.02 | 220.83 | 24.76 | 87.17 | 25.13 |
March | 224.67 | 26.72 | 337.33 | 26.68 | 169.83 | 27.05 |
April | 351.00 | 29.34 | 396.17 | 29.15 | 345.67 | 29.24 |
May | 413.83 | 32.73 | 418.00 | 32.70 | 413.83 | 32.71 |
June | 408.00 | 33.79 | 408.00 | 33.79 | 408.00 | 33.79 |
July | 415.00 | 35.17 | 415.00 | 35.17 | 415.00 | 35.17 |
August | 422.00 | 35.31 | 422.00 | 35.31 | 422.00 | 35.31 |
September | 405.00 | 33.54 | 405.00 | 33.54 | 405.00 | 33.54 |
October | 409.67 | 31.48 | 414.00 | 31.45 | 409.67 | 31.46 |
November | 357.33 | 28.65 | 397.83 | 28.49 | 357.33 | 28.54 |
December | 223.67 | 24.60 | 314.83 | 24.94 | 159.00 | 25.12 |
Annual Sum or Average | 4049.17 | 30.86 | 4315.67 | 30.82 | 3627.83 | 31.15 |
Minimum of Months | 190.83 | 22.04 | 166.67 | 22.90 | 35.33 | 22.96 |
Maximum of Months | 422.00 | 35.31 | 422.00 | 35.31 | 422.00 | 35.31 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.75927 | 45.74881 | 0.29246 | 7.04595 |
February | 376.00000 | 23.83755 | 48.56485 | 0.36107 | 7.84065 |
March | 422.00000 | 23.87785 | 45.73151 | 0.38701 | 8.21696 |
April | 405.00000 | 23.88944 | 48.40158 | 0.46332 | 9.53696 |
May | 418.00000 | 23.89351 | 49.72088 | -0.2983 | 6.91428 |
June | 408.00000 | 23.89537 | 54.76153 | -0.2205 | 6.05741 |
July | 415.00000 | 23.89767 | 57.12912 | -0.1662 | 5.62022 |
August | 422.00000 | 23.89781 | 57.95230 | -0.1508 | 5.50734 |
September | 405.00000 | 23.89587 | 56.80063 | -0.2124 | 5.98227 |
October | 414.00000 | 23.89430 | 52.48505 | 0.55610 | 11.54635 |
November | 399.00000 | 23.89025 | 50.99422 | 0.48387 | 9.94051 |
December | 415.00000 | 23.86599 | 49.72690 | 0.38940 | 8.27200 |
Annual Sum or Average | 4913.00000 | 23.87478 | 51.51814 | 0.15457 | 7.69700 |
Minimum of Months | 376.00000 | 23.75927 | 45.73151 | -0.2983 | 5.50734 |
Maximum of Months | 422.00000 | 23.89781 | 57.95230 | 0.55610 | 11.54635 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.75420 | 47.64019 | 0.37663 | 8.24764 |
February | 376.00000 | 23.82949 | 49.97513 | 0.43694 | 9.12126 |
March | 422.00000 | 23.87074 | 47.34322 | 0.45762 | 9.48772 |
April | 405.00000 | 23.88904 | 50.00004 | 0.52209 | 10.77499 |
May | 418.00000 | 23.89268 | 52.03168 | -0.2491 | 6.38294 |
June | 408.00000 | 23.89406 | 58.51920 | -0.1788 | 5.73381 |
July | 415.00000 | 23.89546 | 61.47252 | -0.1325 | 5.43007 |
August | 422.00000 | 23.89566 | 62.81408 | -0.1180 | 5.33415 |
September | 405.00000 | 23.89462 | 61.21348 | -0.1701 | 5.65193 |
October | 414.00000 | 23.89332 | 55.84638 | 0.59561 | 12.52226 |
November | 399.00000 | 23.88977 | 53.35360 | 0.53130 | 10.96895 |
December | 415.00000 | 23.85136 | 51.64232 | 0.45524 | 9.46058 |
Annual Sum or Average | 4913.00000 | 23.87108 | 54.34923 | 0.20792 | 8.24339 |
Minimum of Months | 376.00000 | 23.75420 | 47.34322 | -0.2491 | 5.33415 |
Maximum of Months | 422.00000 | 23.89566 | 62.81408 | 0.59561 | 12.52226 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.86621 | 42.53436 | 0.45957 | 9.58288 |
February | 376.00000 | 23.87998 | 44.82849 | 0.49818 | 10.30971 |
March | 422.00000 | 23.88686 | 43.42791 | 0.50843 | 10.53751 |
April | 405.00000 | 23.88978 | 46.06254 | 0.56034 | 11.65331 |
May | 418.00000 | 23.89207 | 47.61660 | -0.1754 | 5.73855 |
June | 408.00000 | 23.89273 | 52.61311 | -0.1088 | 5.31169 |
July | 415.00000 | 23.89305 | 54.48263 | -0.0459 | 5.11103 |
August | 422.00000 | 23.89307 | 54.87183 | -0.0106 | 5.06826 |
September | 405.00000 | 23.89285 | 53.04333 | -0.0472 | 5.13991 |
October | 414.00000 | 23.89262 | 48.51986 | 0.68578 | 14.95713 |
November | 399.00000 | 23.89134 | 46.43583 | 0.62029 | 13.14783 |
December | 415.00000 | 23.88902 | 45.27575 | 0.52525 | 10.87744 |
Annual Sum or Average | 4913.00000 | 23.88835 | 48.33500 | 0.28661 | 8.92937 |
Minimum of Months | 376.00000 | 23.86621 | 42.53436 | -0.1754 | 5.06826 |
Maximum of Months | 422.00000 | 23.89307 | 54.87183 | 0.68578 | 14.95713 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.79170 | 44.75334 | 0.41973 | 8.98820 |
February | 376.00000 | 23.83740 | 47.27756 | 0.46696 | 9.74750 |
March | 422.00000 | 23.86687 | 45.31537 | 0.47806 | 9.94715 |
April | 405.00000 | 23.88875 | 47.84796 | 0.53656 | 11.10757 |
May | 418.00000 | 23.89225 | 48.89068 | -0.2131 | 6.04464 |
June | 408.00000 | 23.89295 | 54.28434 | -0.1435 | 5.49481 |
July | 415.00000 | 23.89361 | 56.01518 | -0.0800 | 5.19979 |
August | 422.00000 | 23.89362 | 56.34485 | -0.0446 | 5.10467 |
September | 405.00000 | 23.89315 | 54.61051 | -0.0812 | 5.22412 |
October | 414.00000 | 23.89280 | 49.89554 | 0.66309 | 14.31060 |
November | 399.00000 | 23.89124 | 48.08531 | 0.59701 | 12.54798 |
December | 415.00000 | 23.87310 | 47.66490 | 0.49970 | 10.35663 |
Annual Sum or Average | 4913.00000 | 23.87582 | 50.10277 | 0.25565 | 8.65216 |
Minimum of Months | 376.00000 | 23.79170 | 44.75334 | -0.2131 | 5.10467 |
Maximum of Months | 422.00000 | 23.89362 | 56.34485 | 0.66309 | 14.31060 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.87712 | 51.29786 | 0.28652 | 9.18173 |
February | 376.00000 | 24.06509 | 53.12240 | 0.54450 | 15.82522 |
March | 422.00000 | 25.83036 | 46.88200 | 0.85122 | 25.38928 |
April | 405.00000 | 28.85171 | 45.45645 | 1.45036 | 48.53733 |
May | 418.00000 | 32.66867 | 41.01717 | 2.03438 | 70.48641 |
June | 408.00000 | 33.78708 | 49.30041 | 2.48031 | 82.26662 |
July | 415.00000 | 35.17295 | 51.77683 | 2.96550 | 91.56637 |
August | 422.00000 | 35.31093 | 53.95309 | 3.08197 | 93.33001 |
September | 405.00000 | 33.54413 | 55.64408 | 2.57169 | 84.87149 |
October | 414.00000 | 31.41893 | 49.59043 | 2.14471 | 78.74122 |
November | 399.00000 | 28.33104 | 50.51868 | 1.49274 | 50.67980 |
December | 415.00000 | 24.50426 | 54.72020 | 0.67465 | 17.98526 |
Annual Sum or Average | 4913.00000 | 29.73941 | 50.24483 | 1.72371 | 56.01339 |
Minimum of Months | 376.00000 | 22.87712 | 41.01717 | 0.28652 | 9.18173 |
Maximum of Months | 422.00000 | 35.31093 | 55.64408 | 3.08197 | 93.33001 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.452146E+10 | 0.124481E+10 | 342.46 | 0.378391E+10 | 0.737555E+09 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 37602.46 | 30-JAN-07:02 | 26873.60 | 30-JAN-07:02 | 10728.86 | 30-JAN-07:02 | 8064.53 | 30-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.646307E+10 | 0.177396E+10 | 340.19 | 0.533759E+10 | 0.112548E+10 | 0.00 | 1.00 | 06-FEB-07:02 | 0.00 | 01-FEB-00:10 | 44701.48 | 09-FEB-07:02 | 31172.08 | 08-FEB-07:02 | 14863.52 | 09-FEB-07:02 | 9589.43 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.105188E+11 | 0.291509E+10 | 402.63 | 0.907457E+10 | 0.144419E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 44518.87 | 29-MAR-06:02 | 41282.25 | 27-MAR-06:02 | 14797.34 | 29-MAR-06:02 | 9833.57 | 02-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.162272E+11 | 0.450213E+10 | 406.25 | 0.137310E+11 | 0.249618E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 45153.12 | 30-APR-08:62 | 41907.85 | 29-APR-05:02 | 17139.04 | 30-APR-08:04 | 9717.29 | 28-APR-05:02 | 0.00 | 01-APR-00:10 |
May | 0.269253E+11 | 0.746071E+10 | 441.71 | 0.227831E+11 | 0.414223E+10 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 46560.94 | 24-MAY-05:01 | 41789.45 | 05-MAY-05:02 | 19318.85 | 24-MAY-05:04 | 10824.69 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.336124E+11 | 0.910048E+10 | 436.03 | 0.258307E+11 | 0.778176E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 47410.56 | 19-JUN-05:01 | 38958.49 | 01-JUN-05:01 | 24903.07 | 19-JUN-05:06 | 11042.56 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.405647E+11 | 0.111553E+11 | 451.72 | 0.300914E+11 | 0.104733E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 47302.13 | 06-JUL-05:01 | 42179.62 | 22-JUL-04:02 | 24647.07 | 05-JUL-05:07 | 11283.28 | 23-JUL-08:15 | 0.00 | 01-JUL-00:10 |
August | 0.431983E+11 | 0.118617E+11 | 463.15 | 0.315742E+11 | 0.116240E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 47183.65 | 09-AUG-05:01 | 39333.88 | 06-AUG-06:02 | 25253.76 | 08-AUG-05:08 | 11253.75 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.345027E+11 | 0.912505E+10 | 433.50 | 0.251356E+11 | 0.936708E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 47302.13 | 11-SEP-05:03 | 35180.33 | 02-SEP-05:01 | 23611.95 | 11-SEP-05:07 | 10931.79 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.263149E+11 | 0.695289E+10 | 438.35 | 0.204178E+11 | 0.589713E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 47441.58 | 02-OCT-05:01 | 40146.19 | 20-OCT-05:01 | 23113.23 | 02-OCT-05:05 | 10337.63 | 08-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.166847E+11 | 0.445286E+10 | 403.97 | 0.133086E+11 | 0.337616E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 45539.99 | 03-NOV-05:01 | 38952.37 | 19-NOV-09:02 | 17629.21 | 03-NOV-06:04 | 9800.76 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.852631E+10 | 0.230649E+10 | 386.30 | 0.679966E+10 | 0.172665E+10 | 0.00 | 1.00 | 01-DEC-07:03 | 0.00 | 01-DEC-00:10 | 44338.17 | 11-DEC-07:02 | 34415.17 | 10-DEC-09:02 | 15571.65 | 06-DEC-07:02 | 9582.03 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.268060E+12 | 0.728515E+11 | 4946.26 | 0.207868E+12 | 0.601917E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.452146E+10 | 0.124481E+10 | 340.19 | 0.378391E+10 | 0.737555E+09 | 0.00 | 1.00 | 0.00 | 37602.46 | 26873.60 | 10728.86 | 8064.53 | 0.00 | |||||||
Maximum of Months | 0.431983E+11 | 0.118617E+11 | 463.15 | 0.315742E+11 | 0.116240E+11 | 0.00 | 1.00 | 0.00 | 47441.58 | 42179.62 | 25253.76 | 11283.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.370705E+11 | 0.107625E+11 | 352.14 | 0.276335E+11 | 0.943698E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 209610.71 | 29-JAN-09:02 | 147616.88 | 29-JAN-09:02 | 61993.83 | 29-JAN-09:02 | 50570.88 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.465423E+11 | 0.134435E+11 | 342.62 | 0.344017E+11 | 0.121406E+11 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 214892.15 | 09-FEB-07:02 | 142328.84 | 06-FEB-07:02 | 84473.99 | 07-FEB-07:02 | 50753.63 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.681385E+11 | 0.198422E+11 | 399.76 | 0.531405E+11 | 0.149981E+11 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 214680.00 | 29-MAR-06:02 | 193578.72 | 23-MAR-06:02 | 87591.13 | 29-MAR-06:02 | 52088.68 | 02-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.948568E+11 | 0.276477E+11 | 403.83 | 0.729898E+11 | 0.218670E+11 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 220760.09 | 30-APR-08:62 | 192984.20 | 26-APR-06:02 | 101376.21 | 30-APR-08:04 | 51738.88 | 03-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.140302E+12 | 0.414141E+11 | 437.76 | 0.108380E+12 | 0.319223E+11 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 221444.43 | 30-MAY-06:02 | 191235.18 | 10-MAY-06:02 | 102591.85 | 01-MAY-06:04 | 57554.43 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.172333E+12 | 0.497006E+11 | 433.67 | 0.118036E+12 | 0.542971E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 227157.61 | 25-JUN-08:62 | 168877.64 | 01-JUN-05:01 | 121188.16 | 25-JUN-08:06 | 58649.82 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.205620E+12 | 0.597387E+11 | 444.01 | 0.134337E+12 | 0.712828E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 227809.82 | 27-JUL-06:02 | 187945.19 | 04-JUL-07:01 | 122913.37 | 20-JUL-06:06 | 59559.54 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.218672E+12 | 0.632222E+11 | 450.75 | 0.139159E+12 | 0.795130E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 227866.65 | 26-AUG-06:02 | 169372.24 | 06-AUG-07:01 | 124927.35 | 08-AUG-06:06 | 59910.70 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.178861E+12 | 0.501457E+11 | 431.06 | 0.113616E+12 | 0.652449E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 228453.41 | 11-SEP-06:02 | 160414.61 | 04-SEP-08:62 | 125772.48 | 11-SEP-06:06 | 57935.81 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.136639E+12 | 0.383439E+11 | 433.49 | 0.939837E+11 | 0.426553E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 227772.29 | 08-OCT-08:62 | 173448.74 | 20-OCT-06:02 | 121102.57 | 08-OCT-08:06 | 54383.29 | 08-OCT-08:06 | 0.00 | 01-OCT-00:10 |
November | 0.929025E+11 | 0.262457E+11 | 398.50 | 0.656448E+11 | 0.272578E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 220694.52 | 03-NOV-06:02 | 177612.56 | 19-NOV-09:02 | 100390.81 | 03-NOV-06:04 | 52064.24 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.565442E+11 | 0.161401E+11 | 384.31 | 0.399397E+11 | 0.166045E+11 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 213415.78 | 11-DEC-07:02 | 151730.37 | 12-DEC-07:02 | 79400.31 | 11-DEC-07:02 | 50860.93 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144848E+13 | 0.416647E+12 | 4911.91 | 0.100126E+13 | 0.447220E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.370705E+11 | 0.107625E+11 | 342.62 | 0.276335E+11 | 0.943698E+10 | 0.00 | 1.00 | 0.00 | 209610.71 | 142328.84 | 61993.83 | 50570.88 | 0.00 | |||||||
Maximum of Months | 0.218672E+12 | 0.632222E+11 | 450.75 | 0.139159E+12 | 0.795130E+11 | 0.00 | 1.00 | 0.00 | 228453.41 | 193578.72 | 125772.48 | 59910.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.948713E+10 | 0.238080E+10 | 393.05 | 0.778231E+10 | 0.170482E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 34754.53 | 30-JAN-07:02 | 25639.09 | 29-JAN-09:02 | 10014.52 | 30-JAN-07:02 | 7473.23 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.100613E+11 | 0.253987E+10 | 368.76 | 0.809799E+10 | 0.196327E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 35453.45 | 09-FEB-07:02 | 28755.13 | 05-FEB-09:02 | 12360.60 | 09-FEB-07:02 | 7496.59 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.126583E+11 | 0.327311E+10 | 421.39 | 0.105205E+11 | 0.213779E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 35433.66 | 29-MAR-06:02 | 32716.06 | 28-MAR-05:02 | 12825.04 | 29-MAR-06:02 | 7913.81 | 02-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.152329E+11 | 0.404473E+10 | 414.71 | 0.123979E+11 | 0.283500E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 36154.86 | 30-APR-07:01 | 32220.62 | 26-APR-06:02 | 14829.05 | 30-APR-08:62 | 7613.04 | 28-APR-05:02 | 0.00 | 01-APR-00:10 |
May | 0.211082E+11 | 0.577644E+10 | 444.21 | 0.171079E+11 | 0.400039E+10 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 37396.54 | 24-MAY-05:01 | 32864.15 | 10-MAY-05:01 | 16926.20 | 24-MAY-05:03 | 8482.35 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.249243E+11 | 0.671407E+10 | 438.55 | 0.183372E+11 | 0.658705E+10 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 37814.55 | 20-JUN-05:01 | 28810.64 | 01-JUN-05:01 | 19859.22 | 19-JUN-05:03 | 8646.34 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.297315E+11 | 0.811185E+10 | 459.32 | 0.211165E+11 | 0.861504E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 37728.07 | 06-JUL-05:01 | 32103.31 | 22-JUL-04:02 | 19705.03 | 05-JUL-05:03 | 8787.02 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.323916E+11 | 0.882232E+10 | 475.28 | 0.227663E+11 | 0.962537E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 37633.57 | 09-AUG-05:01 | 29448.49 | 06-AUG-06:02 | 19837.78 | 08-AUG-05:03 | 8791.27 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.279134E+11 | 0.733549E+10 | 443.67 | 0.198505E+11 | 0.806292E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 37686.92 | 11-SEP-04:02 | 27345.12 | 02-SEP-04:02 | 18161.28 | 11-SEP-05:03 | 8523.98 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.236665E+11 | 0.607461E+10 | 442.80 | 0.180789E+11 | 0.558768E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 37777.95 | 08-OCT-07:02 | 30312.01 | 21-OCT-05:02 | 18801.45 | 08-OCT-07:03 | 8054.25 | 08-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.178446E+11 | 0.447781E+10 | 416.33 | 0.140039E+11 | 0.384073E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 36510.50 | 03-NOV-05:01 | 30014.99 | 05-NOV-07:01 | 13952.64 | 03-NOV-06:02 | 7740.84 | 20-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.124438E+11 | 0.309907E+10 | 413.84 | 0.980518E+10 | 0.263859E+10 | 0.00 | 1.00 | 01-DEC-07:03 | 0.00 | 01-DEC-00:10 | 35392.64 | 11-DEC-07:02 | 26962.29 | 27-DEC-07:02 | 12351.97 | 06-DEC-07:02 | 7495.83 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.237464E+12 | 0.626502E+11 | 5131.92 | 0.179865E+12 | 0.575987E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.948713E+10 | 0.238080E+10 | 368.76 | 0.778231E+10 | 0.170482E+10 | 0.00 | 1.00 | 0.00 | 34754.53 | 25639.09 | 10014.52 | 7473.23 | 0.00 | |||||||
Maximum of Months | 0.323916E+11 | 0.882232E+10 | 475.28 | 0.227663E+11 | 0.962537E+10 | 0.00 | 1.00 | 0.00 | 37814.55 | 32864.15 | 19859.22 | 8791.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.629679E+10 | 0.161792E+10 | 365.41 | 0.494547E+10 | 0.135133E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 30490.38 | 29-JAN-09:02 | 21768.33 | 29-JAN-09:02 | 8722.05 | 29-JAN-09:02 | 6574.12 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.705399E+10 | 0.182084E+10 | 347.87 | 0.546517E+10 | 0.158883E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 31333.14 | 09-FEB-07:02 | 21214.16 | 05-FEB-09:02 | 12061.60 | 07-FEB-07:02 | 6602.26 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.928822E+10 | 0.245153E+10 | 401.56 | 0.748312E+10 | 0.180510E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 31238.95 | 29-MAR-06:02 | 28069.05 | 23-MAR-06:02 | 12665.55 | 29-MAR-06:02 | 6936.62 | 02-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.120210E+11 | 0.323681E+10 | 405.89 | 0.949962E+10 | 0.252134E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 31872.75 | 30-APR-08:62 | 27990.87 | 26-APR-06:02 | 14268.85 | 30-APR-08:62 | 6696.89 | 03-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.178041E+11 | 0.488489E+10 | 441.38 | 0.140480E+11 | 0.375612E+10 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:10 | 32853.17 | 24-MAY-05:01 | 27843.09 | 11-MAY-05:01 | 15830.06 | 24-MAY-05:01 | 7459.35 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.215329E+11 | 0.576639E+10 | 435.92 | 0.152753E+11 | 0.625761E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 33221.49 | 14-JUN-05:01 | 24808.42 | 01-JUN-05:01 | 18660.08 | 19-JUN-05:03 | 7603.30 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.262565E+11 | 0.708676E+10 | 455.00 | 0.179670E+11 | 0.828953E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 33143.03 | 06-JUL-05:01 | 27180.15 | 04-JUL-07:01 | 18640.79 | 05-JUL-05:12 | 7724.50 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.287965E+11 | 0.775675E+10 | 467.38 | 0.194905E+11 | 0.930599E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 33060.02 | 09-AUG-05:03 | 25346.24 | 06-AUG-06:02 | 18827.75 | 08-AUG-05:12 | 7732.96 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.245355E+11 | 0.639519E+10 | 439.21 | 0.167802E+11 | 0.775534E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 33188.62 | 28-SEP-05:01 | 23062.02 | 26-SEP-06:02 | 17316.48 | 11-SEP-05:04 | 7497.87 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.203184E+11 | 0.520796E+10 | 440.67 | 0.149976E+11 | 0.532082E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 33300.58 | 08-OCT-07:02 | 25459.58 | 21-OCT-05:02 | 17431.13 | 08-OCT-07:03 | 7073.52 | 08-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.146148E+11 | 0.369842E+10 | 410.83 | 0.110650E+11 | 0.354984E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 32067.28 | 03-NOV-05:01 | 25248.90 | 05-NOV-07:01 | 13423.24 | 03-NOV-06:02 | 6735.78 | 03-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.908356E+10 | 0.230490E+10 | 396.58 | 0.684743E+10 | 0.223613E+10 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:10 | 31120.04 | 11-DEC-07:02 | 21953.82 | 10-DEC-09:02 | 11780.00 | 11-DEC-07:02 | 6598.24 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.197602E+12 | 0.522284E+11 | 5007.68 | 0.143864E+12 | 0.537380E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.629679E+10 | 0.161792E+10 | 347.87 | 0.494547E+10 | 0.135133E+10 | 0.00 | 1.00 | 0.00 | 30490.38 | 21214.16 | 8722.05 | 6574.12 | 0.00 | |||||||
Maximum of Months | 0.287965E+11 | 0.775675E+10 | 467.38 | 0.194905E+11 | 0.930599E+10 | 0.00 | 1.00 | 0.00 | 33300.58 | 28069.05 | 18827.75 | 7732.96 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.97 | 30.66 | 49.30 | 97.86 | 39.50 | 0.00 | 0.00 | 0.00 |
February | 97.29 | 39.96 | 57.33 | 123.44 | 34.04 | 0.00 | 0.00 | 0.00 |
March | 116.64 | 48.62 | 68.03 | 153.90 | 29.45 | 0.00 | 0.00 | 0.00 |
April | 138.72 | 61.78 | 76.94 | 191.69 | 23.17 | 0.00 | 0.00 | 0.00 |
May | 156.82 | 76.25 | 80.57 | 226.98 | 12.32 | 0.00 | 0.00 | 0.00 |
June | 163.54 | 83.20 | 80.34 | 239.01 | 9.17 | 0.00 | 0.00 | 0.00 |
July | 158.62 | 80.50 | 78.12 | 239.74 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 150.93 | 74.10 | 76.83 | 229.38 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 135.85 | 65.32 | 70.52 | 199.83 | 9.88 | 0.00 | 0.00 | 0.00 |
October | 113.91 | 53.42 | 60.49 | 161.79 | 17.63 | 0.00 | 0.00 | 0.00 |
November | 90.89 | 39.90 | 50.98 | 122.35 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 74.14 | 28.72 | 45.42 | 93.21 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.22 | 56.95 | 66.28 | 173.51 | 20.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.14 | 28.72 | 45.42 | 93.21 | 3.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 163.54 | 83.20 | 80.57 | 239.74 | 39.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 736.84 | 346.42 | 390.42 | 1111.64 | 440.46 | 0.00 | 0.00 | 0.00 |
February | 691.93 | 283.03 | 408.90 | 1103.17 | 379.48 | 0.00 | 0.00 | 0.00 |
March | 569.49 | 154.61 | 414.87 | 1002.21 | 303.11 | 0.00 | 0.00 | 0.00 |
April | 447.66 | 47.46 | 400.20 | 917.96 | 203.05 | 0.00 | 0.00 | 0.00 |
May | 379.21 | 5.81 | 373.40 | 982.31 | 71.43 | 0.00 | 0.00 | 0.00 |
June | 357.13 | 0.44 | 356.68 | 1009.06 | 31.65 | 0.00 | 0.00 | 0.00 |
July | 357.12 | 3.03 | 354.08 | 1157.55 | 3.92 | 0.00 | 0.00 | 0.00 |
August | 414.23 | 29.35 | 384.88 | 1290.71 | 2.90 | 0.00 | 0.00 | 0.00 |
September | 546.16 | 125.17 | 420.99 | 1358.63 | 47.57 | 0.00 | 0.00 | 0.00 |
October | 715.03 | 284.26 | 430.77 | 1479.59 | 126.50 | 0.00 | 0.00 | 0.00 |
November | 788.82 | 380.27 | 408.55 | 1408.73 | 244.96 | 0.00 | 0.00 | 0.00 |
December | 732.27 | 361.72 | 370.55 | 1163.35 | 381.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.54 | 167.85 | 392.68 | 1165.83 | 185.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.12 | 0.44 | 354.08 | 917.96 | 2.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 788.82 | 380.27 | 430.77 | 1479.59 | 440.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 736.84 | 346.42 | 390.42 | 1112.80 | 423.17 | 0.00 | 0.00 | 0.00 |
February | 691.93 | 283.03 | 408.90 | 1102.84 | 362.63 | 0.00 | 0.00 | 0.00 |
March | 569.49 | 154.61 | 414.87 | 1000.72 | 286.17 | 0.00 | 0.00 | 0.00 |
April | 447.66 | 47.46 | 400.20 | 915.14 | 188.05 | 0.00 | 0.00 | 0.00 |
May | 379.21 | 5.81 | 373.40 | 982.09 | 61.66 | 0.00 | 0.00 | 0.00 |
June | 357.13 | 0.44 | 356.68 | 1011.32 | 24.99 | 0.00 | 0.00 | 0.00 |
July | 357.12 | 3.03 | 354.08 | 1163.82 | 2.49 | 0.00 | 0.00 | 0.00 |
August | 414.23 | 29.35 | 384.88 | 1296.01 | 1.72 | 0.00 | 0.00 | 0.00 |
September | 546.16 | 125.17 | 420.99 | 1358.46 | 40.12 | 0.00 | 0.00 | 0.00 |
October | 715.03 | 284.26 | 430.77 | 1476.25 | 114.32 | 0.00 | 0.00 | 0.00 |
November | 788.82 | 380.27 | 408.55 | 1406.07 | 231.10 | 0.00 | 0.00 | 0.00 |
December | 732.27 | 361.72 | 370.55 | 1162.58 | 365.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.54 | 167.85 | 392.68 | 1166.11 | 174.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.12 | 0.44 | 354.08 | 915.14 | 1.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 788.82 | 380.27 | 430.77 | 1476.25 | 423.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.60 | 71.27 | 80.32 | 228.81 | 82.18 | 0.00 | 0.00 | 0.00 |
February | 142.35 | 58.23 | 84.13 | 221.27 | 72.36 | 0.00 | 0.00 | 0.00 |
March | 117.16 | 31.81 | 85.35 | 192.36 | 60.74 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 9.76 | 82.34 | 160.42 | 45.26 | 0.00 | 0.00 | 0.00 |
May | 78.02 | 1.19 | 76.82 | 147.25 | 19.76 | 0.00 | 0.00 | 0.00 |
June | 73.47 | 0.09 | 73.38 | 142.77 | 11.53 | 0.00 | 0.00 | 0.00 |
July | 73.47 | 0.62 | 72.85 | 159.06 | 3.06 | 0.00 | 0.00 | 0.00 |
August | 85.22 | 6.04 | 79.18 | 182.42 | 3.25 | 4.00 | 0.00 | 0.00 |
September | 112.37 | 25.75 | 86.61 | 214.91 | 17.60 | 3.17 | 0.00 | 0.00 |
October | 147.11 | 58.48 | 88.62 | 257.66 | 36.34 | 2.17 | 0.00 | 0.00 |
November | 162.29 | 78.24 | 84.05 | 263.53 | 57.76 | 0.00 | 0.00 | 0.00 |
December | 150.65 | 74.42 | 76.24 | 231.94 | 75.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.32 | 34.53 | 80.79 | 200.08 | 40.23 | 9.33 | 0.00 | 0.00 |
Minimum of Months | 73.47 | 0.09 | 72.85 | 142.77 | 3.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.29 | 78.24 | 88.62 | 263.53 | 82.18 | 4.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214181E+09 | 82128671.26 | 0.132052E+09 | 0.262106E+09 | 0.105801E+09 |
February | 0.235363E+09 | 96680824.76 | 0.138682E+09 | 0.298615E+09 | 82337503.71 |
March | 0.312419E+09 | 0.130216E+09 | 0.182203E+09 | 0.412205E+09 | 78871927.91 |
April | 0.359551E+09 | 0.160125E+09 | 0.199427E+09 | 0.496849E+09 | 60060225.34 |
May | 0.420026E+09 | 0.204216E+09 | 0.215810E+09 | 0.607935E+09 | 32989294.88 |
June | 0.423909E+09 | 0.215661E+09 | 0.208247E+09 | 0.619519E+09 | 23763212.77 |
July | 0.424841E+09 | 0.215602E+09 | 0.209239E+09 | 0.642120E+09 | 10224704.98 |
August | 0.404259E+09 | 0.198481E+09 | 0.205777E+09 | 0.614360E+09 | 8967569.40 |
September | 0.352114E+09 | 0.169321E+09 | 0.182792E+09 | 0.517961E+09 | 25615436.90 |
October | 0.305090E+09 | 0.143075E+09 | 0.162015E+09 | 0.433336E+09 | 47220897.16 |
November | 0.235577E+09 | 0.103426E+09 | 0.132151E+09 | 0.317144E+09 | 71177831.72 |
December | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 94618146.66 |
Annual Sum or Average | 0.388591E+10 | 0.179585E+10 | 0.209006E+10 | 0.547179E+10 | 0.641648E+09 |
Minimum of Months | 0.198584E+09 | 76919180.52 | 0.121665E+09 | 0.249643E+09 | 8967569.40 |
Maximum of Months | 0.424841E+09 | 0.215661E+09 | 0.215810E+09 | 0.642120E+09 | 0.105801E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197356E+10 | 0.927857E+09 | 0.104570E+10 | 0.297740E+10 | 0.117974E+10 |
February | 0.167391E+10 | 0.684700E+09 | 0.989207E+09 | 0.266878E+10 | 0.918034E+09 |
March | 0.152531E+10 | 0.414113E+09 | 0.111120E+10 | 0.268432E+10 | 0.811855E+09 |
April | 0.116033E+10 | 0.123017E+09 | 0.103732E+10 | 0.237935E+10 | 0.526301E+09 |
May | 0.101567E+10 | 15553865.02 | 0.100011E+10 | 0.263101E+10 | 0.191326E+09 |
June | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.261547E+10 | 82037602.95 |
July | 0.956499E+09 | 8127288.41 | 0.948372E+09 | 0.310038E+10 | 10509966.63 |
August | 0.110946E+10 | 78609578.58 | 0.103085E+10 | 0.345705E+10 | 7775282.80 |
September | 0.141565E+10 | 0.324436E+09 | 0.109121E+10 | 0.352157E+10 | 0.123293E+09 |
October | 0.191514E+10 | 0.761374E+09 | 0.115376E+10 | 0.396292E+10 | 0.338814E+09 |
November | 0.204463E+10 | 0.985663E+09 | 0.105897E+10 | 0.365143E+10 | 0.634930E+09 |
December | 0.196131E+10 | 0.968824E+09 | 0.992481E+09 | 0.311593E+10 | 0.102173E+10 |
Annual Sum or Average | 0.176771E+11 | 0.529342E+10 | 0.123837E+11 | 0.367656E+11 | 0.584635E+10 |
Minimum of Months | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.237935E+10 | 7775282.80 |
Maximum of Months | 0.204463E+10 | 0.985663E+09 | 0.115376E+10 | 0.396292E+10 | 0.117974E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197356E+10 | 0.927857E+09 | 0.104570E+10 | 0.298053E+10 | 0.113342E+10 |
February | 0.167391E+10 | 0.684700E+09 | 0.989207E+09 | 0.266798E+10 | 0.877280E+09 |
March | 0.152531E+10 | 0.414113E+09 | 0.111120E+10 | 0.268033E+10 | 0.766485E+09 |
April | 0.116033E+10 | 0.123017E+09 | 0.103732E+10 | 0.237205E+10 | 0.487431E+09 |
May | 0.101567E+10 | 15553865.02 | 0.100011E+10 | 0.263042E+10 | 0.165163E+09 |
June | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.262135E+10 | 64763998.19 |
July | 0.956499E+09 | 8127288.41 | 0.948372E+09 | 0.311717E+10 | 6676683.69 |
August | 0.110946E+10 | 78609578.58 | 0.103085E+10 | 0.347124E+10 | 4604981.33 |
September | 0.141565E+10 | 0.324436E+09 | 0.109121E+10 | 0.352112E+10 | 0.103983E+09 |
October | 0.191514E+10 | 0.761374E+09 | 0.115376E+10 | 0.395399E+10 | 0.306192E+09 |
November | 0.204463E+10 | 0.985663E+09 | 0.105897E+10 | 0.364454E+10 | 0.598999E+09 |
December | 0.196131E+10 | 0.968824E+09 | 0.992481E+09 | 0.311386E+10 | 0.979309E+09 |
Annual Sum or Average | 0.176771E+11 | 0.529342E+10 | 0.123837E+11 | 0.367746E+11 | 0.549431E+10 |
Minimum of Months | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.237205E+10 | 4604981.33 |
Maximum of Months | 0.204463E+10 | 0.985663E+09 | 0.115376E+10 | 0.395399E+10 | 0.113342E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406034E+09 | 0.190895E+09 | 0.215139E+09 | 0.612850E+09 | 0.220113E+09 |
February | 0.344385E+09 | 0.140868E+09 | 0.203516E+09 | 0.535305E+09 | 0.175042E+09 |
March | 0.313813E+09 | 85198588.17 | 0.228615E+09 | 0.515213E+09 | 0.162680E+09 |
April | 0.238723E+09 | 25309186.14 | 0.213414E+09 | 0.415816E+09 | 0.117305E+09 |
May | 0.208960E+09 | 3200013.16 | 0.205760E+09 | 0.394400E+09 | 52936472.46 |
June | 0.190444E+09 | 235681.66 | 0.190208E+09 | 0.370054E+09 | 29875035.17 |
July | 0.196787E+09 | 1672087.92 | 0.195115E+09 | 0.426035E+09 | 8209235.83 |
August | 0.228257E+09 | 16172937.42 | 0.212084E+09 | 0.488602E+09 | 8694124.85 |
September | 0.291251E+09 | 66748736.30 | 0.224503E+09 | 0.557046E+09 | 45612747.34 |
October | 0.394015E+09 | 0.156643E+09 | 0.237372E+09 | 0.690122E+09 | 97338865.85 |
November | 0.420657E+09 | 0.202788E+09 | 0.217869E+09 | 0.683081E+09 | 0.149703E+09 |
December | 0.403514E+09 | 0.199323E+09 | 0.204190E+09 | 0.621223E+09 | 0.201235E+09 |
Annual Sum or Average | 0.363684E+10 | 0.108906E+10 | 0.254778E+10 | 0.630975E+10 | 0.126875E+10 |
Minimum of Months | 0.190444E+09 | 235681.66 | 0.190208E+09 | 0.370054E+09 | 8209235.83 |
Maximum of Months | 0.420657E+09 | 0.202788E+09 | 0.237372E+09 | 0.690122E+09 | 0.220113E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1565.75 | 632.02 | 1279.46 | 490.61 | 788.84 | 0.00 | 0.00 |
February | 1974.97 | 544.56 | 1556.63 | 639.42 | 917.21 | 0.00 | 0.00 |
March | 2462.39 | 471.16 | 1866.30 | 777.87 | 1088.43 | 0.00 | 0.00 |
April | 3066.97 | 370.74 | 2219.45 | 988.42 | 1231.03 | 0.00 | 0.00 |
May | 3631.63 | 197.07 | 2509.12 | 1219.93 | 1289.18 | 0.00 | 0.00 |
June | 3824.19 | 146.69 | 2616.72 | 1331.24 | 1285.48 | 0.00 | 0.00 |
July | 3835.84 | 61.08 | 2537.88 | 1287.94 | 1249.94 | 0.00 | 0.00 |
August | 3670.01 | 53.57 | 2414.93 | 1185.67 | 1229.26 | 0.00 | 0.00 |
September | 3197.29 | 158.12 | 2173.54 | 1045.19 | 1128.35 | 0.00 | 0.00 |
October | 2588.63 | 282.08 | 1822.52 | 854.69 | 967.83 | 0.00 | 0.00 |
November | 1957.68 | 439.37 | 1454.18 | 638.43 | 815.75 | 0.00 | 0.00 |
December | 1491.30 | 565.22 | 1186.28 | 459.49 | 726.79 | 0.00 | 0.00 |
Annual Sum or Average | 2776.15 | 325.54 | 1971.54 | 911.14 | 1060.41 | 0.00 | 0.00 |
Minimum of Months | 1491.30 | 53.57 | 1186.28 | 459.49 | 726.79 | 0.00 | 0.00 |
Maximum of Months | 3835.84 | 632.02 | 2616.72 | 1331.24 | 1289.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1111.64 | 440.46 | 736.84 | 346.42 | 390.42 | 0.00 | 0.00 |
February | 1103.17 | 379.48 | 691.93 | 283.03 | 408.90 | 0.00 | 0.00 |
March | 1002.21 | 303.11 | 569.49 | 154.61 | 414.87 | 0.00 | 0.00 |
April | 917.96 | 203.05 | 447.66 | 47.46 | 400.20 | 0.00 | 0.00 |
May | 982.31 | 71.43 | 379.21 | 5.81 | 373.40 | 0.00 | 0.00 |
June | 1009.06 | 31.65 | 357.13 | 0.44 | 356.68 | 0.00 | 0.00 |
July | 1157.55 | 3.92 | 357.12 | 3.03 | 354.08 | 0.00 | 0.00 |
August | 1290.71 | 2.90 | 414.23 | 29.35 | 384.88 | 0.00 | 0.00 |
September | 1358.63 | 47.57 | 546.16 | 125.17 | 420.99 | 0.00 | 0.00 |
October | 1479.59 | 126.50 | 715.03 | 284.26 | 430.77 | 0.00 | 0.00 |
November | 1408.73 | 244.96 | 788.82 | 380.27 | 408.55 | 0.00 | 0.00 |
December | 1163.35 | 381.47 | 732.27 | 361.72 | 370.55 | 0.00 | 0.00 |
Annual Sum or Average | 1165.83 | 185.39 | 560.54 | 167.85 | 392.68 | 0.00 | 0.00 |
Minimum of Months | 917.96 | 2.90 | 357.12 | 0.44 | 354.08 | 0.00 | 0.00 |
Maximum of Months | 1479.59 | 440.46 | 788.82 | 380.27 | 430.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1112.80 | 423.17 | 736.84 | 346.42 | 390.42 | 0.00 | 0.00 |
February | 1102.84 | 362.63 | 691.93 | 283.03 | 408.90 | 0.00 | 0.00 |
March | 1000.72 | 286.17 | 569.49 | 154.61 | 414.87 | 0.00 | 0.00 |
April | 915.14 | 188.05 | 447.66 | 47.46 | 400.20 | 0.00 | 0.00 |
May | 982.09 | 61.66 | 379.21 | 5.81 | 373.40 | 0.00 | 0.00 |
June | 1011.32 | 24.99 | 357.13 | 0.44 | 356.68 | 0.00 | 0.00 |
July | 1163.82 | 2.49 | 357.12 | 3.03 | 354.08 | 0.00 | 0.00 |
August | 1296.01 | 1.72 | 414.23 | 29.35 | 384.88 | 0.00 | 0.00 |
September | 1358.46 | 40.12 | 546.16 | 125.17 | 420.99 | 0.00 | 0.00 |
October | 1476.25 | 114.32 | 715.03 | 284.26 | 430.77 | 0.00 | 0.00 |
November | 1406.07 | 231.10 | 788.82 | 380.27 | 408.55 | 0.00 | 0.00 |
December | 1162.58 | 365.63 | 732.27 | 361.72 | 370.55 | 0.00 | 0.00 |
Annual Sum or Average | 1166.11 | 174.22 | 560.54 | 167.85 | 392.68 | 0.00 | 0.00 |
Minimum of Months | 915.14 | 1.72 | 357.12 | 0.44 | 354.08 | 0.00 | 0.00 |
Maximum of Months | 1476.25 | 423.17 | 788.82 | 380.27 | 430.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.81 | 82.18 | 151.60 | 71.27 | 80.32 | 0.00 | 0.00 |
February | 221.27 | 72.36 | 142.35 | 58.23 | 84.13 | 0.00 | 0.00 |
March | 192.36 | 60.74 | 117.16 | 31.81 | 85.35 | 0.00 | 0.00 |
April | 160.42 | 45.26 | 92.10 | 9.76 | 82.34 | 0.00 | 0.00 |
May | 147.25 | 19.76 | 78.02 | 1.19 | 76.82 | 0.00 | 0.00 |
June | 142.77 | 11.53 | 73.47 | 0.09 | 73.38 | 0.00 | 0.00 |
July | 159.06 | 3.06 | 73.47 | 0.62 | 72.85 | 0.00 | 0.00 |
August | 182.42 | 3.25 | 85.22 | 6.04 | 79.18 | 0.00 | 0.00 |
September | 214.91 | 17.60 | 112.37 | 25.75 | 86.61 | 0.00 | 0.00 |
October | 257.66 | 36.34 | 147.11 | 58.48 | 88.62 | 0.00 | 0.00 |
November | 263.53 | 57.76 | 162.29 | 78.24 | 84.05 | 0.00 | 0.00 |
December | 231.94 | 75.13 | 150.65 | 74.42 | 76.24 | 0.00 | 0.00 |
Annual Sum or Average | 200.08 | 40.23 | 115.32 | 34.53 | 80.79 | 0.00 | 0.00 |
Minimum of Months | 142.77 | 3.06 | 73.47 | 0.09 | 72.85 | 0.00 | 0.00 |
Maximum of Months | 263.53 | 82.18 | 162.29 | 78.24 | 88.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.419369E+10 | 0.169281E+10 | 0.342690E+10 | 0.131406E+10 | 0.211284E+10 | 0.00 | 0.00 |
February | 0.477784E+10 | 0.131740E+10 | 0.376580E+10 | 0.154689E+10 | 0.221891E+10 | 0.00 | 0.00 |
March | 0.659528E+10 | 0.126195E+10 | 0.499871E+10 | 0.208346E+10 | 0.291525E+10 | 0.00 | 0.00 |
April | 0.794958E+10 | 0.960964E+09 | 0.575282E+10 | 0.256199E+10 | 0.319082E+10 | 0.00 | 0.00 |
May | 0.972696E+10 | 0.527829E+09 | 0.672042E+10 | 0.326746E+10 | 0.345295E+10 | 0.00 | 0.00 |
June | 0.991230E+10 | 0.380211E+09 | 0.678254E+10 | 0.345058E+10 | 0.333196E+10 | 0.00 | 0.00 |
July | 0.102739E+11 | 0.163595E+09 | 0.679746E+10 | 0.344963E+10 | 0.334783E+10 | 0.00 | 0.00 |
August | 0.982977E+10 | 0.143481E+09 | 0.646814E+10 | 0.317570E+10 | 0.329244E+10 | 0.00 | 0.00 |
September | 0.828738E+10 | 0.409847E+09 | 0.563382E+10 | 0.270914E+10 | 0.292468E+10 | 0.00 | 0.00 |
October | 0.693338E+10 | 0.755534E+09 | 0.488144E+10 | 0.228921E+10 | 0.259224E+10 | 0.00 | 0.00 |
November | 0.507430E+10 | 0.113885E+10 | 0.376923E+10 | 0.165481E+10 | 0.211442E+10 | 0.00 | 0.00 |
December | 0.399429E+10 | 0.151389E+10 | 0.317734E+10 | 0.123071E+10 | 0.194663E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.875487E+11 | 0.102664E+11 | 0.621746E+11 | 0.287336E+11 | 0.334410E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399429E+10 | 0.143481E+09 | 0.317734E+10 | 0.123071E+10 | 0.194663E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102739E+11 | 0.169281E+10 | 0.679746E+10 | 0.345058E+10 | 0.345295E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297740E+10 | 0.117974E+10 | 0.197356E+10 | 0.927857E+09 | 0.104570E+10 | 0.00 | 0.00 |
February | 0.266878E+10 | 0.918034E+09 | 0.167391E+10 | 0.684700E+09 | 0.989207E+09 | 0.00 | 0.00 |
March | 0.268432E+10 | 0.811855E+09 | 0.152531E+10 | 0.414113E+09 | 0.111120E+10 | 0.00 | 0.00 |
April | 0.237935E+10 | 0.526301E+09 | 0.116033E+10 | 0.123017E+09 | 0.103732E+10 | 0.00 | 0.00 |
May | 0.263101E+10 | 0.191326E+09 | 0.101567E+10 | 15553865.02 | 0.100011E+10 | 0.00 | 0.00 |
June | 0.261547E+10 | 82037602.95 | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.00 | 0.00 |
July | 0.310038E+10 | 10509966.63 | 0.956499E+09 | 8127288.41 | 0.948372E+09 | 0.00 | 0.00 |
August | 0.345705E+10 | 7775282.80 | 0.110946E+10 | 78609578.58 | 0.103085E+10 | 0.00 | 0.00 |
September | 0.352157E+10 | 0.123293E+09 | 0.141565E+10 | 0.324436E+09 | 0.109121E+10 | 0.00 | 0.00 |
October | 0.396292E+10 | 0.338814E+09 | 0.191514E+10 | 0.761374E+09 | 0.115376E+10 | 0.00 | 0.00 |
November | 0.365143E+10 | 0.634930E+09 | 0.204463E+10 | 0.985663E+09 | 0.105897E+10 | 0.00 | 0.00 |
December | 0.311593E+10 | 0.102173E+10 | 0.196131E+10 | 0.968824E+09 | 0.992481E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367656E+11 | 0.584635E+10 | 0.176771E+11 | 0.529342E+10 | 0.123837E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237935E+10 | 7775282.80 | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.00 | 0.00 |
Maximum of Months | 0.396292E+10 | 0.117974E+10 | 0.204463E+10 | 0.985663E+09 | 0.115376E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298053E+10 | 0.113342E+10 | 0.197356E+10 | 0.927857E+09 | 0.104570E+10 | 0.00 | 0.00 |
February | 0.266798E+10 | 0.877280E+09 | 0.167391E+10 | 0.684700E+09 | 0.989207E+09 | 0.00 | 0.00 |
March | 0.268033E+10 | 0.766485E+09 | 0.152531E+10 | 0.414113E+09 | 0.111120E+10 | 0.00 | 0.00 |
April | 0.237205E+10 | 0.487431E+09 | 0.116033E+10 | 0.123017E+09 | 0.103732E+10 | 0.00 | 0.00 |
May | 0.263042E+10 | 0.165163E+09 | 0.101567E+10 | 15553865.02 | 0.100011E+10 | 0.00 | 0.00 |
June | 0.262135E+10 | 64763998.19 | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.00 | 0.00 |
July | 0.311717E+10 | 6676683.69 | 0.956499E+09 | 8127288.41 | 0.948372E+09 | 0.00 | 0.00 |
August | 0.347124E+10 | 4604981.33 | 0.110946E+10 | 78609578.58 | 0.103085E+10 | 0.00 | 0.00 |
September | 0.352112E+10 | 0.103983E+09 | 0.141565E+10 | 0.324436E+09 | 0.109121E+10 | 0.00 | 0.00 |
October | 0.395399E+10 | 0.306192E+09 | 0.191514E+10 | 0.761374E+09 | 0.115376E+10 | 0.00 | 0.00 |
November | 0.364454E+10 | 0.598999E+09 | 0.204463E+10 | 0.985663E+09 | 0.105897E+10 | 0.00 | 0.00 |
December | 0.311386E+10 | 0.979309E+09 | 0.196131E+10 | 0.968824E+09 | 0.992481E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367746E+11 | 0.549431E+10 | 0.176771E+11 | 0.529342E+10 | 0.123837E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237205E+10 | 4604981.33 | 0.925670E+09 | 1145545.50 | 0.924524E+09 | 0.00 | 0.00 |
Maximum of Months | 0.395399E+10 | 0.113342E+10 | 0.204463E+10 | 0.985663E+09 | 0.115376E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612850E+09 | 0.220113E+09 | 0.406034E+09 | 0.190895E+09 | 0.215139E+09 | 0.00 | 0.00 |
February | 0.535305E+09 | 0.175042E+09 | 0.344385E+09 | 0.140868E+09 | 0.203516E+09 | 0.00 | 0.00 |
March | 0.515213E+09 | 0.162680E+09 | 0.313813E+09 | 85198588.17 | 0.228615E+09 | 0.00 | 0.00 |
April | 0.415816E+09 | 0.117305E+09 | 0.238723E+09 | 25309186.14 | 0.213414E+09 | 0.00 | 0.00 |
May | 0.394400E+09 | 52936472.46 | 0.208960E+09 | 3200013.16 | 0.205760E+09 | 0.00 | 0.00 |
June | 0.370054E+09 | 29875035.17 | 0.190444E+09 | 235681.66 | 0.190208E+09 | 0.00 | 0.00 |
July | 0.426035E+09 | 8209235.83 | 0.196787E+09 | 1672087.92 | 0.195115E+09 | 0.00 | 0.00 |
August | 0.488602E+09 | 8694124.85 | 0.228257E+09 | 16172937.42 | 0.212084E+09 | 0.00 | 0.00 |
September | 0.557046E+09 | 45612747.34 | 0.291251E+09 | 66748736.30 | 0.224503E+09 | 0.00 | 0.00 |
October | 0.690122E+09 | 97338865.85 | 0.394015E+09 | 0.156643E+09 | 0.237372E+09 | 0.00 | 0.00 |
November | 0.683081E+09 | 0.149703E+09 | 0.420657E+09 | 0.202788E+09 | 0.217869E+09 | 0.00 | 0.00 |
December | 0.621223E+09 | 0.201235E+09 | 0.403514E+09 | 0.199323E+09 | 0.204190E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.630975E+10 | 0.126875E+10 | 0.363684E+10 | 0.108906E+10 | 0.254778E+10 | 0.00 | 0.00 |
Minimum of Months | 0.370054E+09 | 8209235.83 | 0.190444E+09 | 235681.66 | 0.190208E+09 | 0.00 | 0.00 |
Maximum of Months | 0.690122E+09 | 0.220113E+09 | 0.420657E+09 | 0.202788E+09 | 0.237372E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.197428E+10 | -0.161531E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -358967583.8 | 58.99 | 0.00 | 0.00 |
February | 0.175144E+10 | -0.142941E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -322036493.6 | 58.99 | 0.00 | 0.00 |
March | 0.186191E+10 | -0.150829E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -353618479.4 | 58.99 | 0.00 | 0.00 |
April | 0.162696E+10 | -0.128837E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -338593235.7 | 58.99 | 0.00 | 0.00 |
May | 0.153082E+10 | -0.118623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -344596625.6 | 58.99 | 0.00 | 0.00 |
June | 0.139119E+10 | -0.105950E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -331686983.0 | 58.99 | 0.00 | 0.00 |
July | 0.137008E+10 | -0.102961E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -340469528.5 | 58.99 | 0.00 | 0.00 |
August | 0.145171E+10 | -0.111116E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -340553392.9 | 58.99 | 0.00 | 0.00 |
September | 0.150095E+10 | -0.116924E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -331708487.8 | 58.99 | 0.00 | 0.00 |
October | 0.168438E+10 | -0.133893E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -345454130.5 | 58.99 | 0.00 | 0.00 |
November | 0.176709E+10 | -0.142858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -338506646.2 | 58.99 | 0.00 | 0.00 |
December | 0.194099E+10 | -0.158584E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -355149843.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.198518E+11 | -0.157505E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.410134E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.137008E+10 | -0.161531E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -358967583.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.197428E+10 | -0.102961E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -322036493.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.74 | 0.50 | 01-JAN-11:50 | 399.60 | 9.42 | 0.00 | 118.67 | 328.67 | 7.90 | 0.00 | 58.67 |
February | 308.33 | 0.71 | 0.50 | 01-FEB-10:30 | 463.42 | 10.29 | 0.00 | 145.50 | 384.05 | 8.69 | 0.00 | 92.17 |
March | 357.50 | 0.67 | 0.50 | 01-MAR-10:09 | 2090.96 | 11.36 | 0.00 | 225.00 | 1848.24 | 9.71 | 0.00 | 134.83 |
April | 375.00 | 0.68 | 0.50 | 01-APR-09:30 | 532.30 | 12.09 | 0.00 | 206.00 | 446.34 | 10.45 | 0.00 | 148.00 |
May | 405.33 | 0.68 | 0.50 | 01-MAY-08:50 | 518.01 | 13.10 | 0.00 | 226.33 | 433.11 | 11.46 | 0.00 | 157.00 |
June | 403.50 | 0.67 | 0.50 | 01-JUN-08:00 | 521.68 | 13.65 | 0.00 | 230.00 | 432.54 | 11.92 | 0.00 | 162.33 |
July | 405.00 | 0.67 | 0.50 | 01-JUL-08:30 | 532.53 | 13.42 | 0.00 | 237.00 | 441.16 | 11.75 | 0.00 | 165.83 |
August | 395.83 | 0.67 | 0.50 | 01-AUG-08:00 | 559.28 | 12.87 | 0.00 | 233.83 | 465.33 | 11.22 | 0.00 | 171.33 |
September | 358.83 | 0.67 | 0.50 | 01-SEP-08:50 | 581.37 | 12.08 | 0.00 | 211.17 | 485.18 | 10.42 | 0.00 | 153.83 |
October | 351.17 | 0.69 | 0.50 | 01-OCT-08:50 | 516.99 | 10.72 | 0.00 | 186.00 | 431.00 | 9.17 | 0.00 | 130.50 |
November | 318.83 | 0.72 | 0.50 | 01-NOV-09:39 | 433.91 | 9.92 | 0.00 | 135.00 | 357.87 | 8.35 | 0.00 | 78.50 |
December | 319.00 | 0.76 | 0.50 | 01-DEC-10:00 | 380.82 | 9.26 | 0.00 | 98.67 | 312.09 | 7.73 | 0.00 | 35.17 |
Annual Sum or Average | 4323.33 | 0.69 | 630.86 | 11.66 | 0.00 | 2253.17 | 533.25 | 10.03 | 0.00 | 1488.17 | ||
Minimum of Months | 308.33 | 0.67 | 0.50 | 380.82 | 9.26 | 0.00 | 98.67 | 312.09 | 7.73 | 0.00 | 35.17 | |
Maximum of Months | 405.33 | 0.76 | 0.50 | 2090.96 | 13.65 | 0.00 | 237.00 | 1848.24 | 11.92 | 0.00 | 171.33 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.452146E+10 | 0.378391E+10 | 37602.46 | 30-JAN-07:02 | 26873.60 | 0.00 |
February | 0.00 | 0.00 | 0.646307E+10 | 0.533759E+10 | 44701.48 | 09-FEB-07:02 | 29837.96 | 0.00 |
March | 0.00 | 0.00 | 0.105188E+11 | 0.907457E+10 | 44518.87 | 29-MAR-06:02 | 29721.53 | 0.00 |
April | 0.00 | 0.00 | 0.162272E+11 | 0.137310E+11 | 45153.12 | 30-APR-08:62 | 28387.14 | 0.00 |
May | 0.00 | 0.00 | 0.269253E+11 | 0.227831E+11 | 46560.94 | 24-MAY-05:01 | 27558.38 | 0.00 |
June | 0.00 | 0.00 | 0.336124E+11 | 0.258307E+11 | 47410.56 | 19-JUN-05:01 | 23615.09 | 0.00 |
July | 0.00 | 0.00 | 0.405647E+11 | 0.300914E+11 | 47302.13 | 06-JUL-05:01 | 26087.49 | 0.00 |
August | 0.00 | 0.00 | 0.431983E+11 | 0.315742E+11 | 47183.65 | 09-AUG-05:01 | 25011.20 | 0.00 |
September | 0.00 | 0.00 | 0.345027E+11 | 0.251356E+11 | 47302.13 | 11-SEP-05:03 | 24992.87 | 0.00 |
October | 0.00 | 0.00 | 0.263149E+11 | 0.204178E+11 | 47441.58 | 02-OCT-05:01 | 25079.65 | 0.00 |
November | 0.00 | 0.00 | 0.166847E+11 | 0.133086E+11 | 45539.99 | 03-NOV-05:01 | 29504.91 | 0.00 |
December | 0.00 | 0.00 | 0.852631E+10 | 0.679966E+10 | 44338.17 | 11-DEC-07:02 | 30420.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268060E+12 | 0.207868E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.452146E+10 | 0.378391E+10 | 37602.46 | 23615.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.431983E+11 | 0.315742E+11 | 47441.58 | 30420.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.370705E+11 | 0.276335E+11 | 209610.71 | 29-JAN-09:02 | 147616.88 | 0.00 |
February | 0.00 | 0.00 | 0.465423E+11 | 0.344017E+11 | 214892.15 | 09-FEB-07:02 | 135201.83 | 0.00 |
March | 0.00 | 0.00 | 0.681385E+11 | 0.531405E+11 | 214680.00 | 29-MAR-06:02 | 127088.87 | 0.00 |
April | 0.00 | 0.00 | 0.948568E+11 | 0.729898E+11 | 220760.09 | 30-APR-08:62 | 119936.23 | 0.00 |
May | 0.00 | 0.00 | 0.140302E+12 | 0.108380E+12 | 221444.43 | 30-MAY-06:02 | 122855.34 | 0.00 |
June | 0.00 | 0.00 | 0.172333E+12 | 0.118036E+12 | 227157.61 | 25-JUN-08:62 | 106732.37 | 0.00 |
July | 0.00 | 0.00 | 0.205620E+12 | 0.134337E+12 | 227809.82 | 27-JUL-06:02 | 106351.43 | 0.00 |
August | 0.00 | 0.00 | 0.218672E+12 | 0.139159E+12 | 227866.65 | 26-AUG-06:02 | 106351.02 | 0.00 |
September | 0.00 | 0.00 | 0.178861E+12 | 0.113616E+12 | 228453.41 | 11-SEP-06:02 | 103743.09 | 0.00 |
October | 0.00 | 0.00 | 0.136639E+12 | 0.939837E+11 | 227772.29 | 08-OCT-08:62 | 107160.06 | 0.00 |
November | 0.00 | 0.00 | 0.929025E+11 | 0.656448E+11 | 220694.52 | 03-NOV-06:02 | 120905.64 | 0.00 |
December | 0.00 | 0.00 | 0.565442E+11 | 0.399397E+11 | 213415.78 | 11-DEC-07:02 | 134015.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144848E+13 | 0.100126E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.370705E+11 | 0.276335E+11 | 209610.71 | 103743.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218672E+12 | 0.139159E+12 | 228453.41 | 147616.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.948713E+10 | 0.778231E+10 | 34754.53 | 30-JAN-07:02 | 24740.01 | 0.00 |
February | 0.00 | 0.00 | 0.100613E+11 | 0.809799E+10 | 35453.45 | 09-FEB-07:02 | 23092.85 | 0.00 |
March | 0.00 | 0.00 | 0.126583E+11 | 0.105205E+11 | 35433.66 | 29-MAR-06:02 | 22608.61 | 0.00 |
April | 0.00 | 0.00 | 0.152329E+11 | 0.123979E+11 | 36154.86 | 30-APR-07:01 | 22327.88 | 0.00 |
May | 0.00 | 0.00 | 0.211082E+11 | 0.171079E+11 | 37396.54 | 24-MAY-05:01 | 20769.02 | 0.00 |
June | 0.00 | 0.00 | 0.249243E+11 | 0.183372E+11 | 37814.55 | 20-JUN-05:01 | 19524.28 | 0.00 |
July | 0.00 | 0.00 | 0.297315E+11 | 0.211165E+11 | 37728.07 | 06-JUL-05:01 | 20213.63 | 0.00 |
August | 0.00 | 0.00 | 0.323916E+11 | 0.227663E+11 | 37633.57 | 09-AUG-05:01 | 18864.78 | 0.00 |
September | 0.00 | 0.00 | 0.279134E+11 | 0.198505E+11 | 37686.92 | 11-SEP-04:02 | 20079.65 | 0.00 |
October | 0.00 | 0.00 | 0.236665E+11 | 0.180789E+11 | 37777.95 | 08-OCT-07:02 | 19228.73 | 0.00 |
November | 0.00 | 0.00 | 0.178446E+11 | 0.140039E+11 | 36510.50 | 03-NOV-05:01 | 23527.35 | 0.00 |
December | 0.00 | 0.00 | 0.124438E+11 | 0.980518E+10 | 35392.64 | 11-DEC-07:02 | 23124.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237464E+12 | 0.179865E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.948713E+10 | 0.778231E+10 | 34754.53 | 18864.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.323916E+11 | 0.227663E+11 | 37814.55 | 24740.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.629679E+10 | 0.494547E+10 | 30490.38 | 29-JAN-09:02 | 21768.33 | 0.00 |
February | 0.00 | 0.00 | 0.705399E+10 | 0.546517E+10 | 31333.14 | 09-FEB-07:02 | 19306.25 | 0.00 |
March | 0.00 | 0.00 | 0.928822E+10 | 0.748312E+10 | 31238.95 | 29-MAR-06:02 | 18573.40 | 0.00 |
April | 0.00 | 0.00 | 0.120210E+11 | 0.949962E+10 | 31872.75 | 30-APR-08:62 | 17603.90 | 0.00 |
May | 0.00 | 0.00 | 0.178041E+11 | 0.140480E+11 | 32853.17 | 24-MAY-05:01 | 17023.10 | 0.00 |
June | 0.00 | 0.00 | 0.215329E+11 | 0.152753E+11 | 33221.49 | 14-JUN-05:01 | 16534.93 | 0.00 |
July | 0.00 | 0.00 | 0.262565E+11 | 0.179670E+11 | 33143.03 | 06-JUL-05:01 | 15987.19 | 0.00 |
August | 0.00 | 0.00 | 0.287965E+11 | 0.194905E+11 | 33060.02 | 09-AUG-05:03 | 15321.52 | 0.00 |
September | 0.00 | 0.00 | 0.245355E+11 | 0.167802E+11 | 33188.62 | 28-SEP-05:01 | 17195.18 | 0.00 |
October | 0.00 | 0.00 | 0.203184E+11 | 0.149976E+11 | 33300.58 | 08-OCT-07:02 | 16133.09 | 0.00 |
November | 0.00 | 0.00 | 0.146148E+11 | 0.110650E+11 | 32067.28 | 03-NOV-05:01 | 19350.36 | 0.00 |
December | 0.00 | 0.00 | 0.908356E+10 | 0.684743E+10 | 31120.04 | 11-DEC-07:02 | 19340.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197602E+12 | 0.143864E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.629679E+10 | 0.494547E+10 | 30490.38 | 15321.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287965E+11 | 0.194905E+11 | 33300.58 | 21768.33 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142735E+10 | 0.32 | 1862.98 | 30-JAN-07:02 | 0.80 |
February | 0.129644E+10 | 0.32 | 2227.12 | 06-FEB-07:02 | 0.87 |
March | 0.145499E+10 | 0.32 | 2227.12 | 01-MAR-07:02 | 0.87 |
April | 0.140150E+10 | 0.32 | 2227.12 | 02-APR-08:62 | 0.87 |
May | 0.147963E+10 | 0.32 | 2227.12 | 01-MAY-05:02 | 0.86 |
June | 0.160574E+10 | 0.35 | 2227.12 | 01-JUN-05:01 | 0.87 |
July | 0.195030E+10 | 0.38 | 2227.12 | 01-JUL-05:01 | 0.86 |
August | 0.208613E+10 | 0.40 | 2227.12 | 01-AUG-04:02 | 0.86 |
September | 0.162506E+10 | 0.35 | 2227.12 | 01-SEP-05:01 | 0.86 |
October | 0.146242E+10 | 0.32 | 2227.12 | 01-OCT-07:01 | 0.86 |
November | 0.138386E+10 | 0.31 | 2227.12 | 01-NOV-05:02 | 0.87 |
December | 0.143189E+10 | 0.32 | 2227.12 | 03-DEC-09:02 | 0.87 |
Annual Sum or Average | 0.186053E+11 | 0.34 | |||
Minimum of Months | 0.129644E+10 | 0.31 | 1862.98 | 0.80 | |
Maximum of Months | 0.208613E+10 | 0.40 | 2227.12 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.866440E+10 | 0.50 | 13519.59 | 29-JAN-09:02 | 1.37 |
February | 0.786981E+10 | 0.50 | 13519.59 | 06-FEB-07:02 | 1.37 |
March | 0.883130E+10 | 0.51 | 13519.59 | 01-MAR-07:02 | 1.36 |
April | 0.850583E+10 | 0.50 | 13519.59 | 02-APR-08:62 | 1.37 |
May | 0.923020E+10 | 0.52 | 13519.59 | 01-MAY-06:02 | 1.36 |
June | 0.103010E+11 | 0.56 | 13519.59 | 01-JUN-05:01 | 1.37 |
July | 0.121608E+11 | 0.60 | 13519.59 | 01-JUL-05:01 | 1.36 |
August | 0.129024E+11 | 0.63 | 13519.59 | 01-AUG-05:01 | 1.36 |
September | 0.104778E+11 | 0.56 | 13519.59 | 01-SEP-05:01 | 1.36 |
October | 0.905323E+10 | 0.51 | 13519.59 | 01-OCT-07:01 | 1.35 |
November | 0.840588E+10 | 0.49 | 13519.59 | 01-NOV-06:02 | 1.36 |
December | 0.868752E+10 | 0.50 | 13519.59 | 03-DEC-09:02 | 1.36 |
Annual Sum or Average | 0.115090E+12 | 0.53 | |||
Minimum of Months | 0.786981E+10 | 0.49 | 13519.59 | 1.35 | |
Maximum of Months | 0.129024E+11 | 0.63 | 13519.59 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.997034E+09 | 0.33 | 1555.57 | 29-JAN-09:02 | 0.90 |
February | 0.905629E+09 | 0.33 | 1555.57 | 05-FEB-09:02 | 0.90 |
March | 0.101632E+10 | 0.33 | 1555.57 | 01-MAR-07:02 | 0.90 |
April | 0.978140E+09 | 0.33 | 1555.57 | 02-APR-08:62 | 0.90 |
May | 0.102909E+10 | 0.33 | 1555.57 | 01-MAY-05:02 | 0.89 |
June | 0.107703E+10 | 0.35 | 1555.57 | 01-JUN-05:01 | 0.90 |
July | 0.125407E+10 | 0.38 | 1555.57 | 01-JUL-05:01 | 0.89 |
August | 0.137001E+10 | 0.41 | 1555.57 | 01-AUG-04:02 | 0.89 |
September | 0.118221E+10 | 0.38 | 1555.57 | 01-SEP-04:02 | 0.89 |
October | 0.106364E+10 | 0.34 | 1555.57 | 01-OCT-07:01 | 0.89 |
November | 0.972932E+09 | 0.33 | 1555.57 | 01-NOV-05:02 | 0.90 |
December | 0.100024E+10 | 0.33 | 1555.57 | 03-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.128464E+11 | 0.35 | |||
Minimum of Months | 0.905629E+09 | 0.33 | 1555.57 | 0.89 | |
Maximum of Months | 0.137001E+10 | 0.41 | 1555.57 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.845948E+09 | 0.33 | 1319.90 | 29-JAN-09:02 | 0.90 |
February | 0.768318E+09 | 0.33 | 1319.90 | 06-FEB-07:02 | 0.90 |
March | 0.862138E+09 | 0.33 | 1319.90 | 01-MAR-07:02 | 0.90 |
April | 0.829228E+09 | 0.33 | 1319.90 | 02-APR-08:62 | 0.90 |
May | 0.868177E+09 | 0.33 | 1319.90 | 01-MAY-06:02 | 0.89 |
June | 0.900537E+09 | 0.35 | 1319.90 | 01-JUN-05:01 | 0.90 |
July | 0.105486E+10 | 0.38 | 1319.90 | 01-JUL-05:01 | 0.89 |
August | 0.116050E+10 | 0.40 | 1319.90 | 01-AUG-04:02 | 0.89 |
September | 0.995927E+09 | 0.37 | 1319.90 | 01-SEP-05:01 | 0.89 |
October | 0.895355E+09 | 0.34 | 1319.90 | 01-OCT-07:01 | 0.89 |
November | 0.823327E+09 | 0.33 | 1319.90 | 01-NOV-05:02 | 0.90 |
December | 0.848350E+09 | 0.33 | 1319.90 | 03-DEC-09:02 | 0.90 |
Annual Sum or Average | 0.108527E+11 | 0.34 | |||
Minimum of Months | 0.768318E+09 | 0.33 | 1319.90 | 0.89 | |
Maximum of Months | 0.116050E+10 | 0.40 | 1319.90 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.267216E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.307040E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.437008E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.590363E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.894034E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107062E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131056E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.139478E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.107501E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.841531E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.583672E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.373838E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.914568E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.267216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.139478E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.194269E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213133E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.286735E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.361535E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.506443E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.600016E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.718995E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.761245E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.606235E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.473972E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.346516E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.248276E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.531737E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194269E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.761245E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.337784E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.344550E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.428943E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.502287E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.680553E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.779110E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.936592E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.101923E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.851770E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.713826E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.545074E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.409930E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.754965E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.337784E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.101923E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.246387E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.258916E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.331367E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.406604E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.575306E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.666693E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.814162E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.891725E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.739112E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.610332E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.452174E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.315325E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.630810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.246387E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.891725E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142735E+10 | 0.452146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129644E+10 | 0.646307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145499E+10 | 0.105188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140150E+10 | 0.162272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147963E+10 | 0.269253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160574E+10 | 0.336124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195030E+10 | 0.405647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208613E+10 | 0.431983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162506E+10 | 0.345027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146242E+10 | 0.263149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138386E+10 | 0.166847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143189E+10 | 0.852631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186053E+11 | 0.268060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129644E+10 | 0.452146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208613E+10 | 0.431983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.866440E+10 | 0.370705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786981E+10 | 0.465423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.883130E+10 | 0.681385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.850583E+10 | 0.948568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.923020E+10 | 0.140302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103010E+11 | 0.172333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121608E+11 | 0.205620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129024E+11 | 0.218672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104778E+11 | 0.178861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.905323E+10 | 0.136639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.840588E+10 | 0.929025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868752E+10 | 0.565442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115090E+12 | 0.144848E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.786981E+10 | 0.370705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129024E+11 | 0.218672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.997034E+09 | 0.948713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.905629E+09 | 0.100613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101632E+10 | 0.126583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.978140E+09 | 0.152329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102909E+10 | 0.211082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107703E+10 | 0.249243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125407E+10 | 0.297315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137001E+10 | 0.323916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118221E+10 | 0.279134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106364E+10 | 0.236665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972932E+09 | 0.178446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100024E+10 | 0.124438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128464E+11 | 0.237464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.905629E+09 | 0.948713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137001E+10 | 0.323916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.845948E+09 | 0.629679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768318E+09 | 0.705399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.862138E+09 | 0.928822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829228E+09 | 0.120210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.868177E+09 | 0.178041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.900537E+09 | 0.215329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105486E+10 | 0.262565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116050E+10 | 0.287965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995927E+09 | 0.245355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895355E+09 | 0.203184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.823327E+09 | 0.146148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848350E+09 | 0.908356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108527E+11 | 0.197602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.768318E+09 | 0.629679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116050E+10 | 0.287965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142735E+10 | 0.00 | 0.00 | 0.00 | 0.124481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129644E+10 | 0.00 | 0.00 | 0.00 | 0.177396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145499E+10 | 0.00 | 0.00 | 0.00 | 0.291509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140150E+10 | 0.00 | 0.00 | 0.00 | 0.450213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147963E+10 | 0.00 | 0.00 | 0.00 | 0.746071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160574E+10 | 0.00 | 0.00 | 0.00 | 0.910048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195030E+10 | 0.00 | 0.00 | 0.00 | 0.111553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.208613E+10 | 0.00 | 0.00 | 0.00 | 0.118617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162506E+10 | 0.00 | 0.00 | 0.00 | 0.912505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146242E+10 | 0.00 | 0.00 | 0.00 | 0.695289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138386E+10 | 0.00 | 0.00 | 0.00 | 0.445286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143189E+10 | 0.00 | 0.00 | 0.00 | 0.230649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186053E+11 | 0.00 | 0.00 | 0.00 | 0.728515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129644E+10 | 0.00 | 0.00 | 0.00 | 0.124481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208613E+10 | 0.00 | 0.00 | 0.00 | 0.118617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.866440E+10 | 0.00 | 0.00 | 0.00 | 0.107625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786981E+10 | 0.00 | 0.00 | 0.00 | 0.134435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.883130E+10 | 0.00 | 0.00 | 0.00 | 0.198422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.850583E+10 | 0.00 | 0.00 | 0.00 | 0.276477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.923020E+10 | 0.00 | 0.00 | 0.00 | 0.414141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103010E+11 | 0.00 | 0.00 | 0.00 | 0.497006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121608E+11 | 0.00 | 0.00 | 0.00 | 0.597387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129024E+11 | 0.00 | 0.00 | 0.00 | 0.632222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104778E+11 | 0.00 | 0.00 | 0.00 | 0.501457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.905323E+10 | 0.00 | 0.00 | 0.00 | 0.383439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.840588E+10 | 0.00 | 0.00 | 0.00 | 0.262457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868752E+10 | 0.00 | 0.00 | 0.00 | 0.161401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115090E+12 | 0.00 | 0.00 | 0.00 | 0.416647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.786981E+10 | 0.00 | 0.00 | 0.00 | 0.107625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129024E+11 | 0.00 | 0.00 | 0.00 | 0.632222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.997034E+09 | 0.00 | 0.00 | 0.00 | 0.238080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.905629E+09 | 0.00 | 0.00 | 0.00 | 0.253987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101632E+10 | 0.00 | 0.00 | 0.00 | 0.327311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.978140E+09 | 0.00 | 0.00 | 0.00 | 0.404473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102909E+10 | 0.00 | 0.00 | 0.00 | 0.577644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107703E+10 | 0.00 | 0.00 | 0.00 | 0.671407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125407E+10 | 0.00 | 0.00 | 0.00 | 0.811185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137001E+10 | 0.00 | 0.00 | 0.00 | 0.882232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118221E+10 | 0.00 | 0.00 | 0.00 | 0.733549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106364E+10 | 0.00 | 0.00 | 0.00 | 0.607461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.972932E+09 | 0.00 | 0.00 | 0.00 | 0.447781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100024E+10 | 0.00 | 0.00 | 0.00 | 0.309907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128464E+11 | 0.00 | 0.00 | 0.00 | 0.626502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.905629E+09 | 0.00 | 0.00 | 0.00 | 0.238080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137001E+10 | 0.00 | 0.00 | 0.00 | 0.882232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.845948E+09 | 0.00 | 0.00 | 0.00 | 0.161792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768318E+09 | 0.00 | 0.00 | 0.00 | 0.182084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.862138E+09 | 0.00 | 0.00 | 0.00 | 0.245153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829228E+09 | 0.00 | 0.00 | 0.00 | 0.323681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.868177E+09 | 0.00 | 0.00 | 0.00 | 0.488489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.900537E+09 | 0.00 | 0.00 | 0.00 | 0.576639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105486E+10 | 0.00 | 0.00 | 0.00 | 0.708676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116050E+10 | 0.00 | 0.00 | 0.00 | 0.775675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995927E+09 | 0.00 | 0.00 | 0.00 | 0.639519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895355E+09 | 0.00 | 0.00 | 0.00 | 0.520796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.823327E+09 | 0.00 | 0.00 | 0.00 | 0.369842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848350E+09 | 0.00 | 0.00 | 0.00 | 0.230490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108527E+11 | 0.00 | 0.00 | 0.00 | 0.522284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.768318E+09 | 0.00 | 0.00 | 0.00 | 0.161792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116050E+10 | 0.00 | 0.00 | 0.00 | 0.775675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.758782E+09 | 0.352702E+09 | 0.00 | 3886534.81 | 8688504.07 | 0.00 | 0.623468E+09 | 0.00 | 0.22 |
February | 0.445331E+09 | 0.811877E+09 | 0.00 | 3517610.97 | 360766.51 | 0.00 | 0.373820E+09 | 0.00 | 0.22 |
March | 0.299106E+09 | 0.179412E+10 | 0.00 | 3719501.51 | 2946649.67 | 0.00 | 0.288546E+09 | 0.00 | 0.23 |
April | 0.126994E+09 | 0.396756E+10 | 0.00 | 3253081.32 | 16291538.79 | 0.00 | 0.150600E+09 | 0.00 | 0.22 |
May | 8471010.98 | 0.733163E+10 | 0.00 | 2413273.24 | 29865592.28 | 0.00 | 35420608.57 | 0.00 | 0.22 |
June | 1476601.13 | 0.108466E+11 | 0.00 | 987405.85 | 32280111.86 | 0.00 | 6079643.21 | 0.00 | 0.23 |
July | 499540.53 | 0.139884E+11 | 0.00 | 1015407.03 | 21567148.72 | 0.00 | 5043252.04 | 0.00 | 0.23 |
August | 0.00 | 0.152617E+11 | 0.00 | 0.00 | 16827785.91 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 680978.06 | 0.119886E+11 | 0.00 | 547622.52 | 34936500.88 | 0.00 | 2881490.05 | 0.00 | 0.23 |
October | 5420418.13 | 0.783754E+10 | 0.00 | 1471067.18 | 52441408.04 | 0.00 | 32145233.75 | 0.00 | 0.22 |
November | 53137814.45 | 0.413699E+10 | 0.00 | 1542830.88 | 20288890.92 | 0.00 | 31708972.34 | 0.00 | 0.22 |
December | 0.382133E+09 | 0.135745E+10 | 0.00 | 3949198.07 | 3697650.79 | 0.00 | 0.319127E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.208203E+10 | 0.796752E+11 | 0.00 | 26303533.36 | 0.240193E+09 | 0.00 | 0.186884E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.352702E+09 | 0.00 | 0.00 | 360766.51 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.758782E+09 | 0.152617E+11 | 0.00 | 3949198.07 | 52441408.04 | 0.00 | 0.623468E+09 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.602470E+10 | 0.199768E+10 | 0.00 | 37938331.84 | 45626440.51 | 0.00 | 0.744076E+10 | 0.00 | 0.43 |
February | 0.354217E+10 | 0.552052E+10 | 0.00 | 29023347.10 | 24610597.13 | 0.00 | 0.404651E+10 | 0.00 | 0.43 |
March | 0.252844E+10 | 0.123827E+11 | 0.00 | 23445891.16 | 40918003.39 | 0.00 | 0.259835E+10 | 0.00 | 0.44 |
April | 0.997467E+09 | 0.297472E+11 | 0.00 | 12011911.47 | 0.185179E+09 | 0.00 | 0.107942E+10 | 0.00 | 0.43 |
May | 74979036.65 | 0.560778E+11 | 0.00 | 5867255.41 | 0.447057E+09 | 0.00 | 0.157312E+09 | 0.00 | 0.44 |
June | 9391325.05 | 0.826618E+11 | 0.00 | 1812126.69 | 0.634086E+09 | 0.00 | 27185037.74 | 0.00 | 0.44 |
July | 4398256.52 | 0.106963E+12 | 0.00 | 2050015.65 | 0.701275E+09 | 0.00 | 24939064.92 | 0.00 | 0.44 |
August | 0.00 | 0.116030E+12 | 0.00 | 0.00 | 0.699372E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 7743849.12 | 0.909271E+11 | 0.00 | 814996.31 | 0.642867E+09 | 0.00 | 23220429.99 | 0.00 | 0.44 |
October | 70100922.84 | 0.582327E+11 | 0.00 | 4383756.91 | 0.972440E+09 | 0.00 | 0.175119E+09 | 0.00 | 0.43 |
November | 0.409040E+09 | 0.300971E+11 | 0.00 | 5462702.75 | 0.325659E+09 | 0.00 | 0.275335E+09 | 0.00 | 0.43 |
December | 0.319540E+10 | 0.911900E+10 | 0.00 | 28037705.35 | 41168448.51 | 0.00 | 0.357746E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.168638E+11 | 0.599757E+12 | 0.00 | 0.150848E+09 | 0.476026E+10 | 0.00 | 0.194256E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.199768E+10 | 0.00 | 0.00 | 24610597.13 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.602470E+10 | 0.116030E+12 | 0.00 | 37938331.84 | 0.972440E+09 | 0.00 | 0.744076E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313198E+09 | 0.560668E+09 | 0.00 | 7498656.69 | 225599.34 | 0.00 | 0.625070E+09 | 0.00 | 0.43 |
February | 0.197023E+09 | 0.971459E+09 | 0.00 | 4357663.93 | 144661.98 | 0.00 | 0.294835E+09 | 0.00 | 0.43 |
March | 0.146747E+09 | 0.165480E+10 | 0.00 | 3716554.21 | 530767.36 | 0.00 | 0.223775E+09 | 0.00 | 0.44 |
April | 65504013.62 | 0.337098E+10 | 0.00 | 1864197.34 | 6733615.28 | 0.00 | 0.101807E+09 | 0.00 | 0.43 |
May | 3898833.83 | 0.597324E+10 | 0.00 | 1013405.79 | 24080372.17 | 0.00 | 17369254.76 | 0.00 | 0.44 |
June | 1021040.14 | 0.869464E+10 | 0.00 | 464906.86 | 32816003.77 | 0.00 | 2766740.18 | 0.00 | 0.44 |
July | 318313.95 | 0.112424E+11 | 0.00 | 393721.75 | 12795044.94 | 0.00 | 2561309.79 | 0.00 | 0.44 |
August | 0.00 | 0.123268E+11 | 0.00 | 0.00 | 7896971.89 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 202682.01 | 0.986821E+10 | 0.00 | 166799.29 | 18775719.65 | 0.00 | 583802.38 | 0.00 | 0.44 |
October | 2354904.26 | 0.665991E+10 | 0.00 | 857551.19 | 37187791.53 | 0.00 | 11655315.85 | 0.00 | 0.43 |
November | 16908368.38 | 0.385494E+10 | 0.00 | 1137144.41 | 10804517.79 | 0.00 | 28126022.02 | 0.00 | 0.43 |
December | 0.149439E+09 | 0.157341E+10 | 0.00 | 4304304.76 | 516607.11 | 0.00 | 0.254841E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.896616E+09 | 0.667514E+11 | 0.00 | 25774906.22 | 0.152508E+09 | 0.00 | 0.156339E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.560668E+09 | 0.00 | 0.00 | 144661.98 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.313198E+09 | 0.123268E+11 | 0.00 | 7498656.69 | 37187791.53 | 0.00 | 0.625070E+09 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495933E+09 | 0.396081E+09 | 0.00 | 5016360.20 | 2487260.04 | 0.00 | 0.556721E+09 | 0.00 | 0.43 |
February | 0.304725E+09 | 0.768702E+09 | 0.00 | 3372698.42 | 200417.78 | 0.00 | 0.291169E+09 | 0.00 | 0.43 |
March | 0.230856E+09 | 0.144120E+10 | 0.00 | 2464889.95 | 1270671.50 | 0.00 | 0.205105E+09 | 0.00 | 0.44 |
April | 94402192.49 | 0.312403E+10 | 0.00 | 1342898.50 | 7217836.38 | 0.00 | 0.103641E+09 | 0.00 | 0.43 |
May | 5504382.73 | 0.575680E+10 | 0.00 | 849761.79 | 27888843.10 | 0.00 | 20309575.03 | 0.00 | 0.44 |
June | 1260377.73 | 0.839879E+10 | 0.00 | 385803.99 | 39105545.91 | 0.00 | 3515800.46 | 0.00 | 0.44 |
July | 376938.95 | 0.109370E+11 | 0.00 | 349629.08 | 28290836.44 | 0.00 | 2634182.06 | 0.00 | 0.44 |
August | 0.00 | 0.120224E+11 | 0.00 | 0.00 | 22104185.38 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 448048.91 | 0.957171E+10 | 0.00 | 212363.03 | 35050116.00 | 0.00 | 1291561.03 | 0.00 | 0.44 |
October | 2478827.40 | 0.641975E+10 | 0.00 | 692571.66 | 43155024.60 | 0.00 | 14399618.03 | 0.00 | 0.43 |
November | 27541125.04 | 0.361140E+10 | 0.00 | 892472.07 | 10903878.71 | 0.00 | 29789523.53 | 0.00 | 0.43 |
December | 0.241817E+09 | 0.131156E+10 | 0.00 | 3337489.22 | 2131697.55 | 0.00 | 0.255262E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.140534E+10 | 0.637594E+11 | 0.00 | 18916937.91 | 0.219806E+09 | 0.00 | 0.148384E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.396081E+09 | 0.00 | 0.00 | 200417.78 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.495933E+09 | 0.120224E+11 | 0.00 | 5016360.20 | 43155024.60 | 0.00 | 0.556721E+09 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.136368E+12 | 0.181223E+10 | 0.00 | 0.376511E+11 | 0.733819E+11 |
February | 0.162306E+12 | 0.114142E+10 | 0.00 | 0.158602E+11 | 0.896987E+11 |
March | 0.212413E+12 | 0.283051E+09 | 0.00 | -0.284480E+10 | 0.129086E+12 |
April | 0.237336E+12 | -0.123305E+10 | 0.00 | -0.447597E+11 | 0.177769E+12 |
May | 0.261515E+12 | -0.344772E+10 | 0.00 | -0.112360E+12 | 0.265676E+12 |
June | 0.256966E+12 | -0.565449E+10 | 0.00 | -0.170628E+12 | 0.323684E+12 |
July | 0.256679E+12 | -0.730128E+10 | 0.00 | -0.224672E+12 | 0.388266E+12 |
August | 0.245898E+12 | -0.742035E+10 | 0.00 | -0.237252E+12 | 0.414722E+12 |
September | 0.205746E+12 | -0.540612E+10 | 0.00 | -0.187080E+12 | 0.338814E+12 |
October | 0.164131E+12 | -0.301596E+10 | 0.00 | -0.123088E+12 | 0.263518E+12 |
November | 0.121696E+12 | -807630804.8 | 0.00 | -0.504033E+11 | 0.180922E+12 |
December | 0.116974E+12 | 0.102396E+10 | 0.00 | 0.895618E+10 | 0.110448E+12 |
Annual Sum or Average | 0.237803E+13 | -0.300259E+11 | 0.00 | -0.109062E+13 | 0.275599E+13 |
Minimum of Months | 0.116974E+12 | -0.742035E+10 | 0.00 | -0.237252E+12 | 0.733819E+11 |
Maximum of Months | 0.261515E+12 | 0.181223E+10 | 0.00 | 0.376511E+11 | 0.414722E+12 |