Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:30:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1737.38 | 757.36 | 757.36 |
Net Site Energy | 1737.38 | 757.36 | 757.36 |
Total Source Energy | 4066.10 | 1772.50 | 1772.50 |
Net Source Energy | 4066.10 | 1772.50 | 1772.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 592.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 100.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 316.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 352.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1047.90 | 689.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 592.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 100.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 316.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 83.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 352.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 592.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 100.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 316.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 83.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 352.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 96.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 174.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.37 | 300.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.80 | 300.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 174.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.37 | 300.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.80 | 300.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1047.903 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1047.903 | 100.00 |
Total On-Site and Utility Electric Sources | 1047.903 | 100.00 |
Total Electricity End Uses | 1047.903 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 13.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2851.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7283 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 14.6389 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 14.6389 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 14.6389 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 8.6004 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.4629 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 13.4629 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 7.7283 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 14.6389 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 14.6389 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 14.6389 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 8.6004 | 6.19 | 0.0000 | |
Total | 2293.99 | 13.4629 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 13.4629 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 13.4629 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-13:00 | 07-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 11-OCT-11:09 |
Heating | 0.00 | 256224.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45366.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21091.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18349.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4075.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 95578.87 | 260299.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 256224.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 45366.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21091.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18349.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4075.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 642.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 318.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1002.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 264.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1115.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 104.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3318.71 | 747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 138.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 436.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 486.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1446.69 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 138.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 436.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 486.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1446.69 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.53 |
CORE_RETAIL DIRECT AIR | 7.48 |
POINT_OF_SALE DIRECT AIR | 1.24 |
FRONT_RETAIL DIRECT AIR | 1.02 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.57 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 2.57 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 58439.09 |
PSZ-AC:1 HEATING COIL | 44581.65 |
PSZ-AC:2 HEATING COIL | 251819.01 |
PSZ-AC:3 HEATING COIL | 35814.59 |
PSZ-AC:4 HEATING COIL | 30777.45 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.53 | 1.00 | 1.00 | 1.53 |
PSZ-AC:2 | 7.48 | 7.48 | 7.48 | 7.48 | 7.73 | 7.73 | 1.00 | 0.967444 | 7.73 |
PSZ-AC:3 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC:4 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.53 | 0.231581 |
PSZ-AC:2_OA_CONTROLLER | 7.73 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.24 | 0.178122 |
PSZ-AC:4_OA_CONTROLLER | 1.02 | 0.178122 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.53 | 1637.89 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.73 | 14203.58 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1378.22 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1130.20 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.53 | 1.53 | 1.53 | 1.53 | 29627.04 | 44581.65 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.73 | 7.73 | 7.73 | 7.73 | 162742.88 | 251819.01 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 23495.85 | 35814.59 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 20084.41 | 30777.45 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 1.53 | 0.765337 | 1.53 | 29627.04 | 14571.58 | 29627.04 | 0.789430 | 0.789430 |
PSZ-AC:2 COOLING COIL | 7.73 | 3.87 | 7.73 | 162742.88 | 82728.77 | 162742.88 | 0.756130 | 0.756130 |
PSZ-AC:3 COOLING COIL | 1.24 | 0.622415 | 1.24 | 23495.85 | 11570.52 | 23495.85 | 0.800440 | 0.800440 |
PSZ-AC:4 COOLING COIL | 1.02 | 0.510404 | 1.02 | 20084.41 | 9898.17 | 20084.41 | 0.782330 | 0.782330 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 7.728 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.798 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 14.639 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 17.869 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 14.639 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.159 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 14.639 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 17.869 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 8.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.600 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 2935.892 | 7.728 | 358.994 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2935.892 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 23429.316 | 14.639 | 90.659 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 23429.316 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 2207.693 | 14.639 | 90.659 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2207.693 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 2207.693 | 14.639 | 90.659 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2207.693 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 103.204 | 8.600 | 53.253 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 103.204 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7084 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.244 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | -0.20034964E-14 | 0.26963808E-16 | -0.16003411E-09 | 0.42846997E-16 |
25 | 8 | 0.23322411E-07 | 0.96372825E-13 | 0.39283768E-03 | -0.26518382E-09 |
26 | 7 | -0.12689940E-01 | 0.49284520E-08 | -0.23731239E-01 | 0.14428925E-03 |
27 | 6 | 0.41753308 | 0.17068900E-05 | 0.48245321 | -0.48913675E-02 |
28 | 5 | -5.3094432 | 0.63487927E-04 | -4.5207885 | 0.64657911E-01 |
29 | 4 | 33.528635 | 0.51754632E-03 | 21.751062 | -0.42910387 |
30 | 3 | -112.34473 | 0.11244610E-02 | -56.238263 | 1.5313544 |
31 | 2 | 198.23960 | 0.63076360E-03 | 78.438415 | -2.9183194 |
32 | 1 | -171.57391 | 0.67164406E-04 | -55.419000 | 2.7527624 |
33 | 0 | 57.057407 | 0.38120757E-06 | 15.531865 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 36 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 37 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.605 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CORE_RETAIL | 16 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | CurtainWall | 4.099 | 0.605 | 0.602 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.237 | 6.240E-004 | 2.832E-004 | 0.368 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.203 | 1.270E-004 | 1.032E-004 | 7.495E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.168E-004 | 3.174E-004 | 0.423 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 1.389E-002 | 1.157E-003 | 3.817E-004 | 0.683 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.7644E-004 |
2 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.1371E-004 |
3 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5762E-004 |
4 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.6077E-004 |
5 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.5896E-004 |
6 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 2.5989E-004 |
7 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT1 | 1.8826E-004 |
8 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C1 | CORE_RETAIL_DAYLREFPT2 | 3.8861E-004 |
9 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.8180E-004 |
10 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.2204E-004 |
11 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.3639E-004 |
12 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 1.9336E-004 |
13 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 2.3239E-004 |
14 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.0332E-004 |
15 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT1 | 3.3459E-004 |
16 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C2 | CORE_RETAIL_DAYLREFPT2 | 2.5384E-004 |
17 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.9626E-004 |
18 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4265E-004 |
19 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.4827E-004 |
20 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.3300E-004 |
21 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 2.5185E-004 |
22 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.4138E-004 |
23 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT1 | 3.6316E-004 |
24 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C3 | CORE_RETAIL_DAYLREFPT2 | 1.5160E-004 |
25 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.9006E-004 |
26 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1327E-004 |
27 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.6926E-004 |
28 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1009E-004 |
29 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 1.7935E-004 |
30 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.1701E-004 |
31 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT1 | 2.1006E-004 |
32 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R4C4 | CORE_RETAIL_DAYLREFPT2 | 1.2163E-004 |
33 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.7120E-004 |
34 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 2.4034E-003 |
35 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.6938E-004 |
36 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 2.9297E-003 |
37 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.9138E-004 |
38 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 1.3172E-003 |
39 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT1 | 2.0423E-004 |
40 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C1 | CORE_RETAIL_DAYLREFPT2 | 4.8861E-004 |
41 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 9.7201E-004 |
42 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 6.9402E-004 |
43 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 1.0858E-003 |
44 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 7.7100E-004 |
45 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 8.3848E-004 |
46 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 5.7632E-004 |
47 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT1 | 4.0755E-004 |
48 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C2 | CORE_RETAIL_DAYLREFPT2 | 2.9208E-004 |
49 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.4431E-004 |
50 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2739E-004 |
51 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.7483E-004 |
52 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2614E-004 |
53 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 4.0407E-004 |
54 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.3182E-004 |
55 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT1 | 2.3275E-004 |
56 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C4 | CORE_RETAIL_DAYLREFPT2 | 1.2274E-004 |
57 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 2.0459E-003 |
58 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1355E-004 |
59 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 2.4745E-003 |
60 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1559E-004 |
61 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 1.1744E-003 |
62 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 2.1257E-004 |
63 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT1 | 4.5006E-004 |
64 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R1C3 | CORE_RETAIL_DAYLREFPT2 | 1.5812E-004 |
65 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.1878E-003 |
66 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.0639E-003 |
67 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 2.1348E-003 |
68 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.0355E-003 |
69 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.2311E-003 |
70 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.4991E-003 |
71 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT1 | 3.0113E-003 |
72 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C2 | CORE_RETAIL_DAYLREFPT2 | 1.1229E-003 |
73 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.7862E-004 |
74 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 4.9285E-003 |
75 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 3.4640E-004 |
76 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.2052E-003 |
77 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 5.0607E-004 |
78 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 6.2166E-003 |
79 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT1 | 4.3245E-004 |
80 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C1 | CORE_RETAIL_DAYLREFPT2 | 5.6026E-003 |
81 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 3.7941E-003 |
82 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.4312E-004 |
83 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 3.9616E-003 |
84 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.3012E-004 |
85 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.9320E-003 |
86 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.8771E-004 |
87 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT1 | 4.1841E-003 |
88 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C3 | CORE_RETAIL_DAYLREFPT2 | 2.2857E-004 |
89 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0706E-004 |
90 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3075E-004 |
91 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 5.7906E-004 |
92 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.2701E-004 |
93 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 8.2355E-004 |
94 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3972E-004 |
95 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT1 | 6.0783E-004 |
96 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R2C4 | CORE_RETAIL_DAYLREFPT2 | 1.3139E-004 |
97 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.0380E-003 |
98 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 5.7268E-004 |
99 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 8.5646E-004 |
100 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 4.8964E-004 |
101 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 1.2897E-003 |
102 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 7.6223E-004 |
103 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT1 | 2.4225E-003 |
104 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C2 | CORE_RETAIL_DAYLREFPT2 | 9.8043E-004 |
105 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 3.0323E-004 |
106 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.5093E-003 |
107 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 2.6342E-004 |
108 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.2450E-003 |
109 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 3.4048E-004 |
110 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 1.8912E-003 |
111 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT1 | 4.0205E-004 |
112 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C1 | CORE_RETAIL_DAYLREFPT2 | 4.2090E-003 |
113 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.2748E-003 |
114 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.9827E-004 |
115 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.0595E-003 |
116 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 1.8131E-004 |
117 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 1.6691E-003 |
118 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2380E-004 |
119 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT1 | 3.2528E-003 |
120 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C3 | CORE_RETAIL_DAYLREFPT2 | 2.2074E-004 |
121 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.8707E-004 |
122 | Clear Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.2388E-004 |
123 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 3.3722E-004 |
124 | Clear Turbid Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.1953E-004 |
125 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 4.9129E-004 |
126 | Intermediate Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3097E-004 |
127 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT1 | 5.5315E-004 |
128 | Overcast Sky | 01/21 | CORE_RETAIL_DAYLCTRL | CORE_RETAIL | SKYLIGHTS_R3C4 | CORE_RETAIL_DAYLREFPT2 | 1.3062E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 15794.40698 | 18953.28838 | 1.12945 | 1.35534 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
2 | BACK_SPACE | Heating | 29414.65403 | 35297.58483 | 1.27556 | 1.53067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 379.89000 | 8.17812 | 0.23158 | 0.00000 |
3 | CORE_RETAIL | Cooling | 86245.31309 | 103494.37571 | 6.23310 | 7.47973 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
4 | CORE_RETAIL | Heating | 66894.11340 | 80272.93609 | 2.86299 | 3.43559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1600.48290 | 258.43418 | 1.89033 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13780.71959 | 16536.86351 | 1.03736 | 1.24483 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
6 | POINT_OF_SALE | Heating | 14312.29950 | 17174.75940 | 0.62259 | 0.74711 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11300.70586 | 13560.84703 | 0.85067 | 1.02081 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
8 | FRONT_RETAIL | Heating | 14311.51395 | 17173.81674 | 0.62255 | 0.74706 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17812 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41732E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 48659.54884 | 58391.45860 | 2.14078 | 2.56894 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -16.30000 | 9.24091E-004 | 12.00000 | 1.93800 | 1.41732E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 18650.24 | 1.40083 | 1.40083 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 44581.65 | 1.53067 | 1.53067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 112746.34 | 7.73143 | 7.73143 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 160453.33 | 3.43559 | 3.43559 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17606.92 | 1.24483 | 1.24483 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 24623.23 | 0.74711 | 0.74711 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14686.52 | 1.02081 | 1.02081 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 24622.30 | 0.74706 | 0.74706 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53067 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.47973 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24483 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02081 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.56894 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 2.56894 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 58439.08889 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53067 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53067 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53067 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53067 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53067 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53067 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.47973 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.47973 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.47973 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.47973 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.73143 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.73143 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96744 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24483 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24483 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24483 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24483 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24483 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24483 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02081 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02081 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02081 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02081 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02081 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02081 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.53067 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.73143 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.24483 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.02081 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53067 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23158 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53067 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1637.89418 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53067 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53067 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53067 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53067 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53067 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76534 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53067 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29627.04000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14571.57899 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29627.04000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78943 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78943 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29627.04000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 44581.65026 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 44581.65026 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.73143 |
66 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89033 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.73143 |
68 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14203.57549 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.73143 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.73143 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.73143 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.73143 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.73143 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.86571 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.73143 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 162742.88000 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 82728.76578 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 162742.88000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75613 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75613 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 162742.88000 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 251819.01192 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
84 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
85 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 251819.01192 |
86 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24483 |
87 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
88 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24483 |
89 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1378.22377 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24483 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24483 |
92 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24483 |
93 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24483 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24483 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62241 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24483 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23495.85000 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11570.52058 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23495.85000 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23495.85000 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35814.58848 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
106 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 35814.58848 |
107 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02081 |
108 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17812 |
109 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02081 |
110 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1130.19638 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02081 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02081 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02081 |
114 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02081 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02081 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51040 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02081 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20084.41000 |
119 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9898.17281 |
120 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20084.41000 |
121 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78233 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78233 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20084.41000 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30777.45111 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
127 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 30777.45111 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 28424.7 | 11.02 | 11.02 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 156661.8 | 10.13 | 10.13 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 22518.5 | 10.98 | 10.98 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 19282.4 | 11.05 | 11.05 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.708 | 0.641 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.6271409556E-002 | 0.2653299365 | Pass | Pass | 3.2636144062E-002 | 0.1117313778 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 5.2196036706E-002 | 0.2419763496 | Pass | Pass | 0.1007585052 | 0.4821538264 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.1656180320E-002 | 0.2923749577 | Pass | Pass | 4.9285700672E-002 | 0.1253852698 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1011170133 | 0.3291330146 | Pass | Pass | 3.3961016431E-002 | 0.1050356125 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1054056356 | 0.3881346666 | Pass | Pass | 0.1683592048 | 0.5476690542 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4237.82 | 183.16 | 0.00 | 784.65 | 573.44 | 5779.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.168 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.641 | 0.708 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.311 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.605 | 0.602 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.605 | 0.602 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.168 | 0.401 | 0.402 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 2.168 | 0.401 | 0.402 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.3815_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.168 | 0.401 | 0.402 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 107.73 | 2.630 | 0.446 | 0.446 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 107.73 | 2.630 | 0.446 | 0.446 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 7.7283 | 379.89 | 2935.89 | LightsWired | LTG_SCH_BACK | 31.69 | 168.00 | 31.25 | 0.0000 | Y | 17.22 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 14.6389 | 1600.48 | 23429.32 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 54.87 | 0.0000 | Y | 241.31 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 14.6389 | 150.81 | 2207.69 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 28.29 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 14.6389 | 150.81 | 2207.69 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 28.29 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 8.6004 | 12.00 | 103.20 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.32 |
Interior Lighting Total | 13.4629 | 2293.99 | 30883.80 | 316.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 23429.32 | 5857.33 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 23429.32 | 5857.33 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 5319.32 | AstronomicalClock | - | 83.67 | 83.67 | 83.54 | |
Exterior Lighting Total | 5319.32 | 83.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29627.04 | 23388.47 | 6238.57 | 0.79 | 3.80 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 162742.88 | 123054.77 | 39688.11 | 0.76 | 3.40 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23495.85 | 18807.02 | 4688.83 | 0.80 | 3.80 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20084.41 | 15712.64 | 4371.77 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 28424.7 | 11.02 | 11.02 | ||||
PSZ-AC:2 COOLING COIL | 156661.8 | 10.13 | 10.13 | ||||
PSZ-AC:3 COOLING COIL | 22518.5 | 10.98 | 10.98 | ||||
PSZ-AC:4 COOLING COIL | 19282.4 | 11.05 | 11.05 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 58439.09 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 44581.65 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 251819.01 | 0.80 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 35814.59 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 30777.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.57 | 238.68 | 92.91 | 1.00 | 3.44 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.53 | 1637.89 | 1070.05 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.73 | 14203.58 | 1837.12 | 1.00 | 1.15 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1378.22 | 1107.16 | 1.00 | 1.35 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1130.20 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 15794.41 | 18953.29 | 49.89 | 1.129 | 1.355 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00943 | 23.42 | 0.01335 | 0.232 | 0.00 |
CORE_RETAIL | 86245.31 | 103494.38 | 64.66 | 6.233 | 7.480 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00986 | 23.42 | 0.01335 | 1.890 | 0.00 |
POINT_OF_SALE | 13780.72 | 16536.86 | 109.65 | 1.037 | 1.245 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00906 | 30.14 | 0.01337 | 0.178 | 0.00 |
FRONT_RETAIL | 11300.71 | 13560.85 | 89.92 | 0.851 | 1.021 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00917 | 30.22 | 0.01337 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 0.00 | 30.51 | 0.01343 | 30.30 | 0.01337 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 29414.65 | 35297.58 | 92.92 | 1.276 | 1.531 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00743 | -16.30 | 0.00092 | 0.232 | 0.00 |
CORE_RETAIL | 66894.11 | 80272.94 | 50.16 | 2.863 | 3.436 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00750 | -16.30 | 0.00092 | 1.890 | 0.00 |
POINT_OF_SALE | 14312.30 | 17174.76 | 113.88 | 0.623 | 0.747 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_RETAIL | 14311.51 | 17173.82 | 113.88 | 0.623 | 0.747 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_ENTRY | 48659.55 | 58391.46 | 4865.95 | 2.141 | 2.569 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 21.00 | 0.00564 | -16.30 | 0.00092 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.40 | 1.40 | 1.53 | 1.53 | 1.5307 | 1.5307 | 1.5307 | 1.0000 | 1.0000 |
PSZ-AC:2 | 7.73 | 7.73 | 3.44 | 3.44 | 7.7314 | 7.4797 | 7.7314 | 0.9674 | 1.0000 |
PSZ-AC:3 | 1.24 | 1.24 | 0.75 | 0.75 | 1.2448 | 1.2448 | 1.2448 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.02 | 1.02 | 0.75 | 0.75 | 1.0208 | 1.0208 | 1.0208 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 58439.089 | 58439.089 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 58439.09 | 58439.09 | 2.568941 | 21.00 | 12.37 | 0.00563537 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00563537 | 35.6572 | 58391.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 29627.040 | 23388.474 | 1.530670 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 29627.04 | 24382.07 | 1.530670 | 25.93 | 17.84 | 0.00976737 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 15.1294 | 23.89 | 0.00898117 | 47.4116 | 15489.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 44581.650 | 44581.650 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44581.65 | 44581.65 | 1.530675 | 15.31 | 10.84 | 0.00644751 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 15.1293 | 21.11 | 0.00743213 | 46.5725 | 29414.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 162742.880 | 123054.774 | 7.731430 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 162742.88 | 127097.24 | 7.731430 | 27.03 | 18.59 | 0.01027414 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 24.4499 | 23.89 | 0.00923690 | 48.7454 | 83328.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 251819.012 | 251819.012 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 251819.01 | 251819.01 | 7.731429 | 11.77 | 8.68 | 0.00589378 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.4499 | 21.11 | 0.00750210 | 47.0027 | 66894.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 23495.850 | 18807.018 | 1.244830 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23495.85 | 19545.34 | 1.244830 | 25.72 | 17.69 | 0.00967375 | 12.80 | 11.87 | 0.00850000 | 30.22 | 0.01336682 | 21.81 | 14.3089 | 23.89 | 0.00905684 | 47.8098 | 13776.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 35814.588 | 35814.588 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35814.59 | 35814.59 | 1.244829 | 15.61 | 11.09 | 0.00656604 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.3089 | 21.11 | 0.00750815 | 47.0432 | 14312.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 20084.410 | 15712.636 | 1.020810 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 20084.41 | 16214.20 | 1.020810 | 25.93 | 17.95 | 0.00990625 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 17.4490 | 23.89 | 0.00917395 | 48.4190 | 11290.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 30777.451 | 30777.451 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30777.45 | 30777.45 | 1.020808 | 14.44 | 10.37 | 0.00635927 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.4491 | 21.11 | 0.00750812 | 47.0430 | 14311.51 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 58439.089 | 58439.089 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 2.568941 | 3.01574496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | Sensible | 58439.09 | 58439.09 | 1.0000 | 3.01574496 | 2.568941 | 21.00 | 12.37 | 0.00563537 | 35411.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58439.09 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.01 | 0.00563537 | 21.00 | 0.00563537 | 35.6572 | 58391.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29627.040 | 23388.474 | 1.530670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9970 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.530675 | 1.79689766 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | Sensible | 29627.04 | 24382.07 | 1.0000 | 1.79689226 | 1.530670 | 25.93 | 17.84 | 0.00976737 | 50953.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29627.04 | 30.30 | 0.01336696 | 21.83 | 0.23158056 | 15.1294 | 23.89 | 0.00898117 | 23.89 | 0.00898117 | 47.4116 | 15489.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44581.650 | 44581.650 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.530675 | 1.79689766 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44581.65 | 44581.65 | 1.0000 | 1.79689766 | 1.530675 | 15.31 | 10.84 | 0.00644751 | 31692.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44581.65 | -16.30 | 0.00092409 | -16.30 | 0.23158056 | 15.1293 | 20.94 | 0.00743213 | 21.11 | 0.00743213 | 46.5725 | 29414.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 162742.880 | 123054.774 | 7.731430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9391 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.731429 | 9.07612045 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | Sensible | 162742.88 | 127097.24 | 1.0000 | 9.07612139 | 7.731430 | 27.03 | 18.59 | 0.01027414 | 53368.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 162742.88 | 30.30 | 0.01336696 | 21.83 | 1.89032875 | 24.4499 | 23.89 | 0.00923690 | 23.89 | 0.00923690 | 48.7454 | 83328.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 251819.012 | 251819.012 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.731429 | 9.07612045 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 251819.01 | 251819.01 | 1.0000 | 9.07612045 | 7.731429 | 11.77 | 8.68 | 0.00589378 | 26691.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 251819.01 | -16.30 | 0.00092409 | -16.30 | 1.89032875 | 24.4499 | 20.85 | 0.00750210 | 21.11 | 0.00750210 | 47.0027 | 66894.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23495.850 | 18807.018 | 1.244830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8230 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.244829 | 1.46133676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23495.85 | 19545.34 | 1.0000 | 1.46133745 | 1.244830 | 25.72 | 17.69 | 0.00967375 | 50496.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23495.85 | 30.22 | 0.01336682 | 21.81 | 0.17812154 | 14.3089 | 23.89 | 0.00905684 | 23.89 | 0.00905684 | 47.8098 | 13776.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35814.588 | 35814.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.244829 | 1.46133676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35814.59 | 35814.59 | 1.0000 | 1.46133676 | 1.244829 | 15.61 | 11.09 | 0.00656604 | 32297.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35814.59 | -16.30 | 0.00092409 | -16.30 | 0.17812154 | 14.3089 | 20.94 | 0.00750815 | 21.11 | 0.00750815 | 47.0432 | 14312.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20084.410 | 15712.636 | 1.020810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2552 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.020808 | 1.19835223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 20084.41 | 16214.20 | 1.0000 | 1.19835470 | 1.020810 | 25.93 | 17.95 | 0.00990625 | 51307.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20084.41 | 30.30 | 0.01336696 | 21.83 | 0.17812154 | 17.4490 | 23.89 | 0.00917395 | 23.89 | 0.00917395 | 48.4190 | 11290.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30777.451 | 30777.451 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.020808 | 1.19835223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30777.45 | 30777.45 | 1.0000 | 1.19835223 | 1.020808 | 14.44 | 10.37 | 0.00635927 | 30585.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30777.45 | -16.30 | 0.00092409 | -16.30 | 0.17812154 | 17.4491 | 20.94 | 0.00750812 | 21.11 | 0.00750812 | 47.0430 | 14311.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.53 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.73 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.24 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2958.33 | 3897.67 | 2431.50 |
CORE_RETAIL | 2587.83 | 3153.00 | 1474.33 |
POINT_OF_SALE | 2798.50 | 2899.17 | 1421.00 |
FRONT_RETAIL | 2875.50 | 3233.67 | 1730.33 |
FRONT_ENTRY | 2561.33 | 4407.17 | 2161.00 |
Facility | 3792.33 | 4502.33 | 2851.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 11.17 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 20.83 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 26.67 | 0.00 | 13.50 | 0.00 |
Facility | 62.67 | 0.00 | 13.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.575 | 0.038 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 1.036 | 0.008 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 1.472 | 0.043 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 1.184 | 0.043 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 24.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.349 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.678 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.07 | 8.18 | 2317.33 | 379.89 | 0.2316 | 0.232 |
CORE_RETAIL | PSZ-AC:2 | 128.48 | 258.43 | 9762.95 | 1600.48 | 1.8903 | 1.890 |
POINT_OF_SALE | PSZ-AC:3 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_RETAIL | PSZ-AC:4 | 12.11 | 24.35 | 919.94 | 150.81 | 0.1781 | 0.178 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.014 | ||
Total Facility | 157.72 | 317.25 | 13993.36 | 2293.99 | 2.4782 | 2.492 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 6450124.19 | 0.00 | 6450124.19 | 1407559.32 | 7857683.52 | 7303124.67 | 3840.02 | 3819.32 | 1100.66 | 11.48 |
CORE_RETAIL | 49260153.27 | 0.00 | 49260153.27 | 1206950.68 | 50467103.95 | 59613407.55 | 3819.37 | 3283.97 | 1656.65 | 80.38 |
POINT_OF_SALE | 6577850.20 | 0.00 | 6577850.20 | 641927.05 | 7219777.25 | 5617240.89 | 3815.48 | 2874.45 | 2070.06 | 71.54 |
FRONT_RETAIL | 5276821.59 | 0.00 | 5276821.59 | 641927.05 | 5918748.64 | 5617240.89 | 3834.13 | 3369.56 | 1556.31 | 36.83 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 8646702.41 | 8646702.41 | 446965.66 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 67564949.26 | 0.00 | 67564949.26 | 12545066.51 | 80110015.76 | 78597979.65 | 8760.00 | 3826.86 | 2078.40 | 83.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.3638 | 0.0000 | 0.3638 | 0.0239 | 0.3877 | 0.2316 | 0.00 | 3819.32 | 1093.68 |
CORE_RETAIL | 2.7576 | 0.0000 | 2.7576 | 0.0205 | 2.7781 | 1.8903 | 0.00 | 3283.31 | 1629.69 |
POINT_OF_SALE | 0.3686 | 0.0000 | 0.3686 | 0.0109 | 0.3796 | 0.1781 | 0.00 | 2874.17 | 2038.83 |
FRONT_RETAIL | 0.2969 | 0.0000 | 0.2969 | 0.0109 | 0.3078 | 0.1781 | 0.00 | 3369.39 | 1543.61 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.4824 | 0.4824 | 0.0142 | 4913.00 | 0.00 | 0.00 |
Total Facility | 3.7869 | 0.0000 | 3.7869 | 0.5487 | 4.3356 | 2.4923 | 4913.00 | 3825.74 | 2044.12 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 8888920.29 | 0.00 | 8888920.29 | 7303124.67 | 3839.02 | 0.17 | 4920.81 | 11.48 |
PSZ-AC:2 | 67885448.84 | 0.00 | 67885448.84 | 59613407.55 | 3809.91 | 0.38 | 4949.71 | 80.38 |
PSZ-AC:3 | 9064939.58 | 0.00 | 9064939.58 | 5617240.89 | 3802.96 | 0.41 | 4956.64 | 71.54 |
PSZ-AC:4 | 7271991.22 | 0.00 | 7271991.22 | 5617240.89 | 3828.60 | 0.50 | 4930.90 | 36.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.5013 | 0.0000 | 0.5013 | 0.2316 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 3.8003 | 0.0000 | 3.8003 | 1.8903 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.5080 | 0.0000 | 0.5080 | 0.1781 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.4091 | 0.0000 | 0.4091 | 0.1781 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 4376.90 | 547.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 4192.11 | 801.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 3796.94 | 1187.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 4150.36 | 799.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.4669 | 0.7828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 3.6537 | 4.6520 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.4781 | 0.6098 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.3848 | 0.5411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 461 |
Defaulted Fields | 432 |
Fields with Defaults | 1336 |
Autosized Fields | 76 |
Autosizable Fields | 182 |
Autocalculated Fields | 78 |
Autocalculatable Fields | 156 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
Electricity:Building | 511.59 | 2869.28 | 21-MAY-08:00 | 37134.00 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 67.22 | 527.06 | 01-JAN-00:10 | 3968.99 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 511.59 | 2869.28 | 21-MAY-08:00 | 37134.00 | 02-JAN-09:10 |
InteriorLights:Electricity | 316.43 | 1074.11 | 21-MAY-08:00 | 26362.97 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 17.22 | 67.20 | 01-JAN-00:10 | 1209.85 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 316.43 | 1074.11 | 21-MAY-08:00 | 26362.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 316.43 | 1074.11 | 21-MAY-08:00 | 26362.97 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 17.22 | 67.20 | 01-JAN-00:10 | 1209.85 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 316.43 | 1074.11 | 21-MAY-08:00 | 26362.97 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 325.61 | 1556.41 | 21-MAY-08:00 | 25738.99 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 241.31 | 780.98 | 21-MAY-08:00 | 21086.38 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 241.31 | 780.98 | 21-MAY-08:00 | 21086.38 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 81.21 | 597.20 | 01-JAN-00:10 | 4907.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 28.29 | 110.38 | 01-JAN-00:10 | 1986.92 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 28.29 | 110.38 | 01-JAN-00:10 | 1986.92 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 36.23 | 183.45 | 01-JAN-00:10 | 2425.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 28.29 | 110.38 | 01-JAN-00:10 | 1986.92 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 28.29 | 110.38 | 01-JAN-00:10 | 1986.92 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.32 | 5.16 | 01-JAN-00:10 | 92.88 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.32 | 5.16 | 01-JAN-00:10 | 92.88 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.32 | 5.16 | 01-JAN-00:10 | 92.88 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
ElectricityPurchased:Plant | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
Cogeneration:ElectricityPurchased | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
General:Cogeneration:ElectricityPurchased | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
ElectricityNet:Plant | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
Cogeneration:ElectricityNet | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
General:Cogeneration:ElectricityNet | 1047.90 | 3064.53 | 30-APR-07:00 | 95578.87 | 15-JUL-14:00 |
Electricity:HVAC | 452.77 | 0.00 | 01-JAN-01:00 | 63716.47 | 15-JUL-14:00 |
Fans:Electricity | 352.32 | 0.00 | 01-JAN-01:00 | 18588.57 | 01-JAN-08:30 |
General:Fans:Electricity | 352.32 | 0.00 | 01-JAN-01:00 | 18588.57 | 01-JAN-08:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 100.45 | 0.00 | 01-JAN-00:10 | 45366.58 | 15-JUL-14:00 |
General:Cooling:Electricity | 100.45 | 0.00 | 01-JAN-00:10 | 45366.58 | 15-JUL-14:00 |
ExteriorLights:Electricity | 83.54 | 0.00 | 01-JAN-08:00 | 5319.32 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 83.54 | 0.00 | 01-JAN-08:00 | 5319.32 | 01-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 689.48 | 1862.00 | 05-NOV-18:10 | 260299.51 | 07-FEB-07:10 |
NaturalGas:HVAC | 592.68 | 0.00 | 01-JAN-00:10 | 256224.49 | 07-FEB-07:10 |
Heating:NaturalGas | 592.68 | 0.00 | 01-JAN-00:10 | 256224.49 | 07-FEB-07:10 |
General:Heating:NaturalGas | 592.68 | 0.00 | 01-JAN-00:10 | 256224.49 | 07-FEB-07:10 |
NaturalGas:Plant | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.32 | 09-FEB-13:00 |
WaterSystems:NaturalGas | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.32 | 09-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 96.80 | 1862.00 | 01-JAN-07:10 | 5271.32 | 09-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-OCT-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1494.34 | 0.00 | 01-JAN-01:00 | 330108.52 | 07-FEB-07:10 |
EnergyTransfer:Building | 665.75 | 0.00 | 01-JAN-01:00 | 128666.14 | 06-FEB-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 86.60 | 0.00 | 01-JAN-00:10 | 27036.21 | 07-FEB-06:10 |
Heating:EnergyTransfer | 234.00 | 0.00 | 01-JAN-01:00 | 128317.12 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 59.76 | 0.00 | 01-JAN-00:10 | 27036.21 | 07-FEB-06:10 |
General:Heating:EnergyTransfer | 234.00 | 0.00 | 01-JAN-01:00 | 128317.12 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 59.76 | 0.00 | 01-JAN-00:10 | 27036.21 | 07-FEB-06:10 |
Cooling:EnergyTransfer | 431.75 | 0.00 | 01-JAN-00:10 | 77288.79 | 21-JUL-13:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 26.84 | 0.00 | 01-JAN-00:10 | 10949.61 | 06-AUG-08:10 |
General:Cooling:EnergyTransfer | 431.75 | 0.00 | 01-JAN-00:10 | 77288.79 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 26.84 | 0.00 | 01-JAN-00:10 | 10949.61 | 06-AUG-08:10 |
EnergyTransfer:Zone:CORE_RETAIL | 348.40 | 0.00 | 01-JAN-00:10 | 81483.43 | 30-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 39.18 | 0.00 | 01-JAN-00:10 | 77691.24 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 39.18 | 0.00 | 01-JAN-00:10 | 77691.24 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 309.22 | 0.00 | 01-JAN-00:10 | 61041.64 | 14-JUN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 309.22 | 0.00 | 01-JAN-00:10 | 61041.64 | 14-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 68.11 | 0.00 | 01-JAN-00:10 | 12370.47 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 8.59 | 0.00 | 01-JAN-00:10 | 12370.47 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 8.59 | 0.00 | 01-JAN-00:10 | 12370.47 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 59.52 | 0.00 | 01-JAN-00:10 | 11128.85 | 21-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 59.52 | 0.00 | 01-JAN-00:10 | 11128.85 | 21-SEP-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 51.67 | 0.00 | 01-JAN-00:10 | 13713.15 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 15.50 | 0.00 | 01-JAN-00:10 | 13713.15 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 15.50 | 0.00 | 01-JAN-00:10 | 13713.15 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 36.17 | 0.00 | 01-JAN-00:10 | 8972.46 | 21-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 36.17 | 0.00 | 01-JAN-00:10 | 8972.46 | 21-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 110.97 | 0.00 | 01-JAN-01:00 | 45695.30 | 06-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 110.97 | 0.00 | 01-JAN-01:00 | 45695.30 | 06-FEB-18:00 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 110.97 | 0.00 | 01-JAN-01:00 | 45695.30 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 21.47 | 12-NOV-08:00 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 21.47 | 12-NOV-08:00 |
EnergyTransfer:HVAC | 828.59 | 0.00 | 01-JAN-00:10 | 204979.60 | 07-FEB-07:10 |
HeatingCoils:EnergyTransfer | 474.14 | 0.00 | 01-JAN-00:10 | 204979.60 | 07-FEB-07:10 |
CoolingCoils:EnergyTransfer | 354.45 | 0.00 | 01-JAN-00:10 | 181370.09 | 21-JUL-06:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 59.760 | -26.837 | 0.000 | 0.000 | 5.370 | 17.223 | 49.992 | 0.000 | 0.000 | 0.140 | 0.002 | 0.000 | 0.000 | 0.000 | -22.724 | -82.924 |
CORE_RETAIL | 0.000 | 0.000 | 39.183 | -309.216 | 0.000 | 0.000 | 166.512 | 241.311 | 84.300 | 51.414 | 0.000 | 0.118 | 0.009 | 0.000 | -27.080 | 0.000 | -21.433 | -225.109 |
POINT_OF_SALE | 0.000 | 0.000 | 8.593 | -59.521 | 0.000 | 0.000 | 15.463 | 28.285 | 52.923 | 36.637 | 0.000 | 0.061 | 0.001 | 0.000 | -19.955 | 0.000 | -11.087 | -51.400 |
FRONT_RETAIL | 0.000 | 0.000 | 15.500 | -36.169 | 0.000 | 0.000 | 15.726 | 28.285 | 7.943 | 36.691 | 0.000 | 0.062 | 0.002 | 0.000 | -19.373 | 0.000 | -10.656 | -38.009 |
FRONT_ENTRY | 110.967 | -0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.275 | 1.322 | 0.000 | 7.430 | 0.000 | 0.005 | 0.000 | 0.000 | -3.913 | 0.000 | -115.272 | -1.815 |
Total Facility | 110.967 | -0.000 | 123.036 | -431.742 | 0.000 | 0.000 | 204.345 | 316.427 | 195.158 | 132.173 | 0.000 | 0.387 | 0.015 | 0.000 | -70.321 | 0.000 | -181.173 | -399.257 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 02-AUG-06:02 | 0.00 | 0.00 | 0.00 | -33339.73 | 0.00 | 0.00 | 53.32 | 268.87 | 1226.28 | 0.00 | 0.00 | 0.00 | 31791.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 15-JUN-06:02 | 0.00 | 0.00 | 0.00 | -207521.91 | 0.00 | 0.00 | 1615.38 | 4685.86 | 2067.82 | 270.98 | 0.00 | 0.00 | 199154.15 | 0.00 | -0.00 | 0.00 | -272.28 | 0.00 |
POINT_OF_SALE | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -27628.97 | 0.00 | 0.00 | 150.36 | 441.54 | 1298.17 | 0.00 | 0.00 | 0.00 | 26544.58 | 0.00 | -733.21 | 0.00 | -72.48 | 0.00 |
FRONT_RETAIL | 10-SEP-08:62 | 0.00 | 0.00 | 0.00 | -22469.25 | 0.00 | 0.00 | 154.03 | 220.77 | 146.13 | 1988.69 | 0.00 | 0.00 | 20014.99 | 0.00 | -0.00 | 0.00 | -55.36 | 0.00 |
FRONT_ENTRY | 12-NOV-08:00 | 0.00 | -21.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 0.00 | 332.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -52.91 | -263.23 |
Total Facility | 04-AUG-06:02 | 0.00 | 0.00 | 0.00 | -258179.97 | 0.00 | 0.00 | 1965.11 | 5858.45 | 4787.13 | 0.00 | 0.00 | 0.00 | 247857.74 | 0.00 | -1802.41 | 0.00 | -486.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 13-FEB-05:11 | 0.00 | 0.00 | 45698.46 | 0.00 | 0.00 | 0.00 | 0.00 | 67.20 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7401.25 | -38977.56 |
CORE_RETAIL | 24-JAN-06:01 | 0.00 | 0.00 | 259459.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.47 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2822.15 | 0.00 | -1248.70 | -257594.16 |
POINT_OF_SALE | 07-FEB-05:32 | 0.00 | 0.00 | 36469.06 | 0.00 | 0.00 | 0.00 | 0.00 | 110.38 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2225.07 | 0.00 | -2420.25 | -32583.21 |
FRONT_RETAIL | 06-FEB-05:11 | 0.00 | 0.00 | 31615.73 | 0.00 | 0.00 | 0.00 | 0.00 | 110.38 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2103.08 | 0.00 | -2256.36 | -27464.10 |
FRONT_ENTRY | 06-FEB-18:00 | 45694.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 92.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -513.77 | 0.00 | -45204.63 | -148.75 |
Total Facility | 26-FEB-08:61 | 6838.70 | 0.00 | 369269.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.60 | 1795.17 | 1045.66 | 0.00 | 0.00 | 0.00 | 0.00 | -927.92 | 0.00 | -5502.78 | -373983.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5307 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.5307 | 0.1653 | 1.0000 | Not calculated | 0.2316 | 0.1513 | ||
PSZ-AC:2 | 7.4797 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.7314 | 0.2445 | 1.0000 | Not calculated | 1.8903 | 0.2445 | ||
PSZ-AC:3 | 1.2448 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2448 | 0.1431 | 1.0000 | Not calculated | 0.1781 | 0.1431 | ||
PSZ-AC:4 | 1.0208 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0208 | 0.1745 | 1.0000 | Not calculated | 0.1781 | 0.1745 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.5307 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2316 | 1.5307 | 1.0000 | 1.0000 | Not calculated | 0.2316 | 0.1513 | ||
PSZ-AC:2 | 7.4797 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 1.8903 | 7.4797 | 1.0000 | 1.0000 | Not calculated | 1.8903 | 0.2527 | ||
PSZ-AC:3 | 1.2448 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.2448 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1431 | ||
PSZ-AC:4 | 1.0208 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.1781 | 1.0208 | 1.0000 | 1.0000 | Not calculated | 0.1781 | 0.1745 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8903 | 1.0000 | 1.8903 | 1.000 | 1.8903 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8903 | 1.8903 | 1.8903 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5307 | 1.5307 | 1.5307 | No | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4797 | 7.4797 | 7.4797 | No | 1.8903 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2448 | 1.2448 | 1.2448 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0208 | 1.0208 | 1.0208 | No | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5307 | 1.5307 | 1.5307 | 1.5307 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4797 | 7.7314 | 7.4797 | 7.4797 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.2448 | 1.2448 | 1.2448 | 1.2448 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0208 | 1.0208 | 1.0208 | 1.0208 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5307 | 1.5307 | 1.5307 | No | 0.2316 | 0.1513 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 7.4797 | 7.4797 | 7.4797 | No | 1.8903 | 0.5502 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2448 | 1.2448 | 1.2448 | No | 0.1781 | 0.2384 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0208 | 1.0208 | 1.0208 | No | 0.1781 | 0.2384 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.5307 | 1.5307 | 1.5307 | 1.5307 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4797 | 7.4797 | 7.4797 | 7.4797 | 1.8903 | 1.0000 |
PSZ-AC:3 | 1.2448 | 1.2448 | 1.2448 | 1.2448 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0208 | 1.0208 | 1.0208 | 1.0208 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 13.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 13.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 592.68 | 256224.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 100.45 | 45366.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 316.43 | 26362.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 83.54 | 5319.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 352.32 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 96.80 | 5271.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1047.90 |
Natural Gas | 0.00 | 689.48 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1737.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 137.94 |
Space Heating | 0.00 |
Space Cooling | 43.79 |
Fans (All) | 153.58 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 456.80 |
Subtotal | 456.80 |
Natural Gas [MJ/m2] | |
Space Heating | 258.36 |
Service Water Heating | 42.20 |
Miscellaneous (All) | 300.56 |
Subtotal | 300.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.21 |
Space Heating | 34.11 |
Space Cooling | 5.78 |
Fans (All) | 20.28 |
Service Water Heating | 5.57 |
Receptacle Equipment | 11.23 |
Miscellaneous | 4.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 1652. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | FRONT_ENTRY HEATING SP | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 8393.83 | 358.33 | 7.83 | 0.00 | 0.00 |
Min | 8393.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 358.33 | 7.83 | 0.00 | 0.00 |
Average | 8670.20 | 88.23 | 1.57 | 0.00 | 0.00 |
Sum | 43351.00 | 441.17 | 7.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1782.83 | 130.17 | 7.00 | 0.00 | 0.00 |
Min | 1782.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 130.17 | 7.00 | 0.00 | 0.00 |
Average | 148050.77 | 26.03 | 1.40 | 0.00 | 0.00 |
Sum | 740253.83 | 130.17 | 7.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 8150.00 | 610.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 8114.67 | 645.33 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8075.17 | 684.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 8103.83 | 656.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 7650.33 | 1109.67 | 0.00 | 0.00 | 0.00 |
Min | 7650.33 | 610.00 | 0.00 | 0.00 | 0.00 |
Max | 8150.00 | 1109.67 | 0.00 | 0.00 | 0.00 |
Average | 8018.80 | 741.20 | 0.00 | 0.00 | 0.00 |
Sum | 40094.00 | 3706.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16180.67 | 691.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 587435.50 | 22163.50 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 54448.00 | 1552.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 53919.00 | 2081.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1663.67 | 256.33 | 0.00 | 0.00 | 0.00 |
Min | 1663.67 | 256.33 | 0.00 | 0.00 | 0.00 |
Max | 587435.50 | 22163.50 | 0.00 | 0.00 | 0.00 |
Average | 142729.37 | 5348.83 | 0.00 | 0.00 | 0.00 |
Sum | 713646.83 | 26744.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 8760.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 8760.00 |
Average | 0.00 | 0.00 | 0.00 | 1752.00 |
Sum | 0.00 | 0.00 | 0.00 | 8760.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 609599.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 609599.00 |
Average | 0.00 | 0.00 | 0.00 | 121919.80 |
Sum | 0.00 | 0.00 | 0.00 | 609599.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 568766.03 | 2637.45 | 18-JAN-07:05 | 2.80 | 1.63 | 0.220220E+09 | 247.24 | 02-JAN-15:30 | 2.80 | 1.63 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.201090E+09 | 247.24 | 01-FEB-15:09 | 2.70 | 2.44 |
March | 0.151696E+09 | 4190.35 | 19-MAR-08:05 | 1.47 | 0.12 | 0.235933E+09 | 326.80 | 15-MAR-14:00 | 1.47 | 0.12 |
April | 0.391127E+09 | 4513.95 | 01-APR-06:05 | 0.10 | 0.06 | 0.223904E+09 | 311.05 | 08-APR-14:50 | 19.60 | 13.21 |
May | 0.128019E+10 | 3955.98 | 01-MAY-06:07 | 2.35 | 1.71 | 0.274909E+09 | 326.80 | 31-MAY-14:09 | 21.70 | 14.18 |
June | 0.502066E+10 | 29778.21 | 20-JUN-06:02 | 13.77 | 12.90 | 0.292720E+09 | 326.81 | 22-JUN-14:09 | 20.60 | 14.89 |
July | 0.785527E+10 | 31516.51 | 12-JUL-06:02 | 14.37 | 11.81 | 0.291709E+09 | 326.82 | 03-JUL-14:00 | 14.37 | 11.81 |
August | 0.720958E+10 | 33344.33 | 02-AUG-06:02 | 11.85 | 10.72 | 0.304158E+09 | 326.82 | 11-AUG-14:30 | 24.70 | 16.77 |
September | 0.360982E+10 | 25589.32 | 09-SEP-06:02 | 16.10 | 15.07 | 0.283787E+09 | 326.81 | 21-SEP-14:30 | 25.85 | 16.63 |
October | 0.117525E+10 | 5321.71 | 17-OCT-06:05 | -2.8 | -3.4 | 0.243024E+09 | 326.80 | 11-OCT-14:09 | -2.8 | -3.4 |
November | 0.139778E+09 | 4734.86 | 15-NOV-07:05 | -0.6 | -1.0 | 0.213294E+09 | 277.14 | 04-NOV-15:00 | -0.6 | -1.0 |
December | 3717771.01 | 3994.01 | 03-DEC-09:05 | 1.10 | -1.3 | 0.220554E+09 | 247.24 | 01-DEC-15:20 | 1.10 | -1.3 |
Annual Sum or Average | 0.268377E+11 | 0.300530E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.201090E+09 | 247.24 | -2.8 | -3.4 | ||
Maximum of Months | 0.785527E+10 | 33344.33 | 16.10 | 15.07 | 0.304158E+09 | 326.82 | 25.85 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647342E+10 | 59606.88 | 06-JAN-07:05 | -12.4 | -13.0 | 0.696391E+10 | 8335.22 | 11-JAN-15:00 | 11.70 | 10.14 |
February | 0.611307E+10 | 59086.48 | 05-FEB-09:05 | -11.7 | -12.4 | 0.635961E+10 | 8222.29 | 22-FEB-15:00 | 10.60 | 5.02 |
March | 0.164106E+11 | 133036.64 | 16-MAR-06:03 | 11.93 | 10.48 | 0.767517E+10 | 10327.62 | 16-MAR-14:39 | 19.23 | 15.63 |
April | 0.203136E+11 | 43254.56 | 17-APR-06:05 | -4.2 | -5.3 | 0.799091E+10 | 10327.53 | 08-APR-14:09 | -4.2 | -5.3 |
May | 0.303402E+11 | 186915.23 | 27-MAY-06:03 | 10.47 | 7.76 | 0.931653E+10 | 10327.82 | 13-MAY-15:39 | 10.47 | 7.76 |
June | 0.447684E+11 | 207526.94 | 15-JUN-06:02 | 9.97 | 7.43 | 0.927569E+10 | 10327.92 | 23-JUN-14:00 | 18.90 | 13.37 |
July | 0.511501E+11 | 168339.49 | 06-JUL-06:02 | 13.07 | 10.52 | 0.921904E+10 | 10327.30 | 12-JUL-14:09 | 22.20 | 15.10 |
August | 0.488495E+11 | 181855.00 | 03-AUG-06:02 | 11.57 | 9.86 | 0.961375E+10 | 10328.09 | 09-AUG-14:50 | 29.40 | 18.10 |
September | 0.362371E+11 | 190359.24 | 12-SEP-06:02 | 9.60 | 8.75 | 0.907078E+10 | 10327.91 | 09-SEP-15:00 | 9.60 | 8.75 |
October | 0.237203E+11 | 176090.82 | 06-OCT-06:03 | 10.00 | 8.53 | 0.850580E+10 | 10327.69 | 11-OCT-14:00 | 22.20 | 14.61 |
November | 0.167888E+11 | 41413.84 | 24-NOV-07:05 | -3.2 | -4.0 | 0.715603E+10 | 10327.05 | 16-NOV-15:09 | -3.2 | -4.0 |
December | 0.805297E+10 | 58855.23 | 10-DEC-09:05 | -11.4 | -11.8 | 0.699219E+10 | 8257.34 | 01-DEC-15:09 | -11.4 | -11.8 |
Annual Sum or Average | 0.309218E+12 | 0.981394E+11 | ||||||||
Minimum of Months | 0.611307E+10 | 41413.84 | -12.4 | -13.0 | 0.635961E+10 | 8222.29 | -11.4 | -11.8 | ||
Maximum of Months | 0.511501E+11 | 207526.94 | 13.07 | 10.52 | 0.961375E+10 | 10328.09 | 29.40 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120007E+10 | 4313.70 | 12-JAN-15:30 | -5.8 | -8.2 | 0.658531E+09 | 825.16 | 11-JAN-15:00 | -5.8 | -8.2 |
February | 0.118557E+10 | 4225.48 | 13-FEB-12:13 | -8.1 | -8.5 | 0.607105E+09 | 944.02 | 22-FEB-15:00 | 10.60 | 5.02 |
March | 0.306967E+10 | 15629.91 | 16-MAR-06:03 | 11.93 | 10.48 | 0.777100E+09 | 973.18 | 16-MAR-14:00 | 19.40 | 15.86 |
April | 0.348871E+10 | 6746.22 | 22-APR-14:00 | 15.60 | 7.18 | 0.798644E+09 | 973.15 | 08-APR-14:20 | 15.60 | 7.18 |
May | 0.543406E+10 | 24597.08 | 28-MAY-08:62 | 18.22 | 13.22 | 0.880310E+09 | 973.18 | 13-MAY-13:00 | 18.22 | 13.22 |
June | 0.797426E+10 | 26996.96 | 13-JUN-06:02 | 8.80 | 7.96 | 0.874006E+09 | 973.24 | 22-JUN-14:30 | 20.60 | 14.79 |
July | 0.979102E+10 | 26220.67 | 06-JUL-06:02 | 13.07 | 10.52 | 0.868737E+09 | 973.28 | 19-JUL-14:00 | 31.10 | 22.86 |
August | 0.101565E+11 | 27605.40 | 03-AUG-06:02 | 11.57 | 9.86 | 0.905939E+09 | 973.25 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.823414E+10 | 27631.45 | 11-SEP-06:02 | 11.70 | 9.59 | 0.855578E+09 | 973.27 | 16-SEP-15:00 | 26.70 | 19.57 |
October | 0.499117E+10 | 25605.83 | 12-OCT-06:02 | 13.90 | 11.93 | 0.846350E+09 | 973.21 | 10-OCT-14:39 | 13.90 | 11.93 |
November | 0.279810E+10 | 6034.86 | 01-NOV-12:00 | 11.10 | 6.28 | 0.735065E+09 | 973.09 | 04-NOV-10:20 | 14.27 | 11.96 |
December | 0.119790E+10 | 3990.92 | 07-DEC-18:03 | -6.9 | -8.4 | 0.666984E+09 | 973.08 | 16-DEC-14:50 | 5.10 | 2.71 |
Annual Sum or Average | 0.595212E+11 | 0.947435E+10 | ||||||||
Minimum of Months | 0.118557E+10 | 3990.92 | -8.1 | -8.5 | 0.607105E+09 | 825.16 | -5.8 | -8.2 | ||
Maximum of Months | 0.101565E+11 | 27631.45 | 18.22 | 13.22 | 0.905939E+09 | 973.28 | 31.10 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215303E+09 | 3687.01 | 06-JAN-17:33 | -3.7 | -5.8 | 0.655751E+09 | 736.18 | 02-JAN-15:39 | -3.7 | -5.8 |
February | 0.295225E+09 | 4259.13 | 10-FEB-16:33 | -6.7 | -7.6 | 0.599464E+09 | 796.40 | 22-FEB-15:50 | 10.60 | 5.00 |
March | 0.150344E+10 | 5186.72 | 15-MAR-13:40 | 25.73 | 15.91 | 0.724606E+09 | 973.17 | 15-MAR-14:00 | 25.60 | 16.24 |
April | 0.185728E+10 | 4520.58 | 22-APR-14:20 | 15.60 | 7.13 | 0.738759E+09 | 973.14 | 08-APR-14:09 | 15.60 | 7.13 |
May | 0.296152E+10 | 14790.69 | 24-MAY-06:02 | 18.03 | 15.62 | 0.860164E+09 | 973.17 | 13-MAY-13:00 | 18.03 | 15.62 |
June | 0.519460E+10 | 18760.41 | 11-JUN-08:62 | 21.97 | 14.79 | 0.871868E+09 | 973.18 | 16-JUN-14:00 | 24.40 | 16.20 |
July | 0.694874E+10 | 20959.61 | 12-JUL-06:02 | 14.37 | 11.81 | 0.868644E+09 | 973.25 | 21-JUL-14:09 | 31.52 | 21.93 |
August | 0.720202E+10 | 22252.42 | 04-AUG-06:02 | 12.67 | 10.89 | 0.905709E+09 | 973.25 | 18-AUG-14:00 | 30.00 | 20.99 |
September | 0.552671E+10 | 22472.15 | 10-SEP-08:62 | 13.48 | 10.62 | 0.851262E+09 | 973.24 | 09-SEP-14:09 | 13.48 | 10.62 |
October | 0.298154E+10 | 17011.32 | 12-OCT-06:02 | 13.90 | 11.93 | 0.796912E+09 | 973.17 | 10-OCT-14:00 | 13.90 | 11.93 |
November | 0.125180E+10 | 3640.89 | 15-NOV-07:05 | -0.6 | -1.0 | 0.680816E+09 | 973.10 | 16-NOV-15:09 | 17.20 | 13.33 |
December | 0.230876E+09 | 4675.96 | 27-DEC-15:32 | -8.3 | -10.1 | 0.658005E+09 | 832.15 | 16-DEC-14:09 | -8.3 | -10.1 |
Annual Sum or Average | 0.361691E+11 | 0.921196E+10 | ||||||||
Minimum of Months | 0.215303E+09 | 3640.89 | -8.3 | -10.1 | 0.599464E+09 | 736.18 | -8.3 | -10.1 | ||
Maximum of Months | 0.720202E+10 | 22472.15 | 25.73 | 15.91 | 0.905709E+09 | 973.25 | 31.52 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 52139233.62 | 58.59 | 14-JAN-16:00 | 3.30 | 2.84 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 47612756.12 | 58.59 | 18-FEB-16:00 | 1.10 | -0.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 55841916.10 | 96.73 | 15-MAR-14:09 | 26.02 | 16.09 |
April | 6430.99 | 8.85 | 10-APR-05:10 | 3.98 | 3.28 | 51643905.17 | 67.71 | 08-APR-11:09 | 3.98 | 3.28 |
May | 2092.37 | 10.46 | 19-MAY-06:13 | 9.07 | 7.64 | 56173054.61 | 95.61 | 10-MAY-14:20 | 9.07 | 7.64 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 67252805.29 | 132.52 | 12-JUN-14:09 | 30.50 | 20.19 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 81341446.01 | 142.96 | 21-JUL-14:09 | 31.52 | 21.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 81341257.58 | 133.97 | 10-AUG-14:09 | 30.50 | 20.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 60389810.72 | 106.95 | 16-SEP-13:50 | 27.20 | 19.76 |
October | 18107.15 | 15.18 | 22-OCT-08:50 | 17.43 | 11.54 | 53153486.18 | 73.68 | 11-OCT-14:00 | 17.43 | 11.54 |
November | 14550.50 | 21.47 | 12-NOV-08:00 | 0.60 | -1.2 | 50217402.91 | 58.62 | 04-NOV-10:09 | 0.60 | -1.2 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 52216838.37 | 58.59 | 30-DEC-16:00 | 0.60 | -0.9 |
Annual Sum or Average | 41181.01 | 0.709324E+09 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 47612756.12 | 58.59 | 0.60 | -1.2 | ||
Maximum of Months | 18107.15 | 21.47 | 18.85 | 16.93 | 81341446.01 | 142.96 | 31.52 | 21.93 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149383E+11 | 45594.43 | 09-JAN-05:11 | -9.4 |
February | 0.143428E+11 | 45698.48 | 13-FEB-05:11 | -9.1 |
March | 0.869162E+10 | 45463.43 | 06-MAR-05:42 | -11.1 |
April | 0.291864E+10 | 45057.94 | 17-APR-05:01 | -4.0 |
May | 0.270064E+09 | 24645.37 | 01-MAY-06:03 | 2.35 |
June | 0.161277E+09 | 2105.37 | 18-JUN-08:20 | 24.60 |
July | 0.140848E+09 | 2116.24 | 16-JUL-08:20 | 24.97 |
August | 0.153208E+09 | 1702.21 | 06-AUG-08:06 | 22.07 |
September | 0.159219E+09 | 1595.97 | 24-SEP-07:13 | 15.20 |
October | 0.927811E+09 | 44883.26 | 30-OCT-05:01 | -0.1 |
November | 0.401026E+10 | 45155.44 | 25-NOV-06:01 | -1.7 |
December | 0.130459E+11 | 45481.48 | 28-DEC-05:11 | -11.9 |
Annual Sum or Average | 0.597599E+11 | |||
Minimum of Months | 0.140848E+09 | 1595.97 | -11.9 | |
Maximum of Months | 0.149383E+11 | 45698.48 | 24.97 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929633E+10 | 259459.60 | 24-JAN-06:01 | -12.1 |
February | 0.888792E+10 | 259370.85 | 07-FEB-06:01 | -16.2 |
March | 0.391884E+10 | 258117.27 | 06-MAR-06:01 | -11.1 |
April | 0.167659E+10 | 256948.05 | 17-APR-05:01 | -4.0 |
May | 0.136585E+10 | 13709.14 | 28-MAY-07:13 | 17.97 |
June | 0.834764E+09 | 15971.68 | 18-JUN-08:08 | 24.50 |
July | 0.439011E+09 | 18931.80 | 21-JUL-06:08 | 25.68 |
August | 0.532276E+09 | 13790.83 | 20-AUG-07:01 | 15.78 |
September | 0.112034E+10 | 13758.97 | 24-SEP-07:13 | 15.20 |
October | 0.144295E+10 | 25566.23 | 30-OCT-06:05 | -0.4 |
November | 0.206960E+10 | 258764.61 | 25-NOV-06:01 | -1.7 |
December | 0.759895E+10 | 259070.23 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.391834E+11 | |||
Minimum of Months | 0.439011E+09 | 13709.14 | -18.5 | |
Maximum of Months | 0.929633E+10 | 259459.60 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229339E+10 | 35789.05 | 26-JAN-06:01 | -7.8 |
February | 0.241243E+10 | 36468.97 | 07-FEB-05:32 | -15.9 |
March | 0.755811E+09 | 35532.55 | 24-MAR-05:01 | -5.5 |
April | 0.310608E+09 | 35278.08 | 18-APR-05:01 | 4.50 |
May | 0.126052E+09 | 1293.58 | 28-MAY-07:13 | 17.97 |
June | 80631705.06 | 1826.10 | 18-JUN-08:06 | 24.50 |
July | 35724688.16 | 1963.95 | 20-JUL-05:05 | 23.90 |
August | 34564791.07 | 1834.80 | 15-AUG-05:07 | 22.70 |
September | 91582267.66 | 1575.76 | 17-SEP-07:05 | 22.12 |
October | 0.144249E+09 | 28398.34 | 30-OCT-05:01 | -0.1 |
November | 0.351874E+09 | 35506.61 | 25-NOV-06:01 | -1.7 |
December | 0.195599E+10 | 35726.54 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.859290E+10 | |||
Minimum of Months | 34564791.07 | 1293.58 | -18.5 | |
Maximum of Months | 0.241243E+10 | 36468.97 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413784E+10 | 31098.65 | 30-JAN-05:11 | -9.6 |
February | 0.407461E+10 | 31615.67 | 06-FEB-05:11 | -14.6 |
March | 0.145019E+10 | 30858.66 | 06-MAR-05:11 | -11.1 |
April | 0.607051E+09 | 30631.74 | 05-APR-05:01 | 1.60 |
May | 0.116006E+09 | 6667.07 | 01-MAY-06:03 | 2.35 |
June | 98328381.24 | 1582.81 | 18-JUN-08:06 | 24.50 |
July | 68100966.00 | 1341.10 | 15-JUL-06:06 | 23.72 |
August | 73973625.96 | 1194.70 | 14-AUG-06:06 | 22.88 |
September | 98268308.49 | 1084.00 | 24-SEP-07:13 | 15.20 |
October | 0.208271E+09 | 30412.49 | 30-OCT-05:01 | -0.1 |
November | 0.779568E+09 | 30734.37 | 25-NOV-06:01 | -1.7 |
December | 0.378796E+10 | 30913.82 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.155002E+11 | |||
Minimum of Months | 68100966.00 | 1084.00 | -18.5 | |
Maximum of Months | 0.413784E+10 | 31615.67 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218747E+11 | 42255.29 | 31-JAN-18:00 | -12.2 |
February | 0.203959E+11 | 45695.30 | 06-FEB-18:00 | -14.4 |
March | 0.147746E+11 | 37056.94 | 06-MAR-18:00 | -8.3 |
April | 0.869654E+10 | 29381.64 | 16-APR-11:10 | -3.1 |
May | 0.337178E+10 | 13680.05 | 11-MAY-17:00 | 8.90 |
June | 0.823966E+09 | 11980.39 | 13-JUN-11:10 | 10.00 |
July | 9484263.19 | 2868.47 | 02-JUL-11:05 | 18.48 |
August | 0.192535E+09 | 6763.11 | 31-AUG-11:10 | 14.60 |
September | 0.124292E+10 | 11542.17 | 28-SEP-17:00 | 10.60 |
October | 0.723372E+10 | 19650.10 | 08-OCT-17:00 | 4.40 |
November | 0.113634E+11 | 24850.09 | 23-NOV-18:00 | 0.60 |
December | 0.209874E+11 | 43314.46 | 10-DEC-18:00 | -12.8 |
Annual Sum or Average | 0.110967E+12 | |||
Minimum of Months | 9484263.19 | 2868.47 | -14.4 | |
Maximum of Months | 0.218747E+11 | 45695.30 | 18.48 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144431E+10 | 1209.85 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.131413E+10 | 1209.85 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.149900E+10 | 1209.85 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.141431E+10 | 1209.85 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.147165E+10 | 1209.85 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.144649E+10 | 1209.85 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.143947E+10 | 1209.85 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.149900E+10 | 1209.85 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.141431E+10 | 1209.85 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.144431E+10 | 1209.85 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.139664E+10 | 1209.85 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.143947E+10 | 1209.85 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.172231E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.131413E+10 | 1209.85 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.149900E+10 | 1209.85 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232366E+11 | 21086.38 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.191813E+11 | 21086.38 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.213412E+11 | 21086.38 | 01-MAR-15:00 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.182390E+11 | 21086.38 | 07-APR-16:00 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.188467E+11 | 21086.38 | 11-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.179862E+11 | 19329.19 | 01-JUN-16:40 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.178522E+11 | 19329.19 | 03-JUL-16:49 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.187556E+11 | 21086.38 | 28-AUG-16:10 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.193071E+11 | 21086.38 | 01-SEP-16:00 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.215139E+11 | 21086.38 | 02-OCT-16:40 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.218128E+11 | 21086.38 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.232385E+11 | 21086.38 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.241311E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.178522E+11 | 19329.19 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.232385E+11 | 21086.38 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.237199E+10 | 1986.92 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.215820E+10 | 1986.92 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.246180E+10 | 1986.92 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.232271E+10 | 1986.92 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.241689E+10 | 1986.92 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.237557E+10 | 1986.92 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.236404E+10 | 1986.92 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.246180E+10 | 1986.92 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.232271E+10 | 1986.92 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.237199E+10 | 1986.92 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.229370E+10 | 1986.92 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.236404E+10 | 1986.92 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.282854E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.215820E+10 | 1986.92 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.246180E+10 | 1986.92 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.237199E+10 | 1986.92 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.215820E+10 | 1986.92 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.246180E+10 | 1986.92 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.232271E+10 | 1986.92 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.241689E+10 | 1986.92 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.237557E+10 | 1986.92 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.236404E+10 | 1986.92 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.246180E+10 | 1986.92 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.232271E+10 | 1986.92 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.237199E+10 | 1986.92 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.229370E+10 | 1986.92 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.236404E+10 | 1986.92 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.282854E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.215820E+10 | 1986.92 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.246180E+10 | 1986.92 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.110885E+09 | 92.88 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.100890E+09 | 92.88 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.115083E+09 | 92.88 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.108581E+09 | 92.88 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.112984E+09 | 92.88 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.111052E+09 | 92.88 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.110513E+09 | 92.88 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.115083E+09 | 92.88 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.108581E+09 | 92.88 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.110885E+09 | 92.88 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.107225E+09 | 92.88 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.110513E+09 | 92.88 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132228E+10 | 0.00 | 0.00 | ||
Minimum of Months | 0.100890E+09 | 92.88 | 0.00 | 0.00 | |
Maximum of Months | 0.115083E+09 | 92.88 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.144431E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372611E+10 |
February | 0.638757E+09 | 0.131413E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396132E+10 |
March | 0.730614E+09 | 0.149900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523693.70 | 0.237844E+10 |
April | 0.690691E+09 | 0.141431E+10 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183816E+10 |
May | 0.715069E+09 | 0.147165E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1095339.07 | 0.106067E+10 |
June | 0.705176E+09 | 0.144649E+10 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28779053.17 | 0.713966E+09 |
July | 0.700584E+09 | 0.143947E+10 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61666869.06 | 0.384837E+09 |
August | 0.730614E+09 | 0.149900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43699463.51 | 0.476330E+09 |
September | 0.690691E+09 | 0.141431E+10 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3598673.97 | 0.711211E+09 |
October | 0.699524E+09 | 0.144431E+10 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148510E+10 |
November | 0.673027E+09 | 0.139664E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208009E+10 |
December | 0.700584E+09 | 0.143947E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390815E+10 |
Annual Sum or Average | 0.837485E+10 | 0.172231E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140363E+09 | 0.227244E+11 |
Minimum of Months | 0.638757E+09 | 0.131413E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384837E+09 |
Maximum of Months | 0.730614E+09 | 0.149900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61666869.06 | 0.396132E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.232366E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342842E+10 |
February | 0.201852E+11 | 0.191813E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362401E+10 |
March | 0.230879E+11 | 0.213412E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 920711.22 | 0.223415E+10 |
April | 0.218263E+11 | 0.182390E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182132E+10 |
May | 0.225967E+11 | 0.188467E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939227.40 | 0.107789E+10 |
June | 0.222841E+11 | 0.179862E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24505639.90 | 0.686482E+09 |
July | 0.221389E+11 | 0.178522E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51854242.04 | 0.370692E+09 |
August | 0.230879E+11 | 0.187556E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37078040.67 | 0.449146E+09 |
September | 0.218263E+11 | 0.193071E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3085795.80 | 0.679025E+09 |
October | 0.221054E+11 | 0.215139E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146477E+10 |
November | 0.212681E+11 | 0.218128E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199578E+10 |
December | 0.221389E+11 | 0.232385E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360150E+10 |
Annual Sum or Average | 0.264651E+12 | 0.241311E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118384E+09 | 0.214332E+11 |
Minimum of Months | 0.201852E+11 | 0.178522E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370692E+09 |
Maximum of Months | 0.230879E+11 | 0.232385E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51854242.04 | 0.362401E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.237199E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173078E+10 |
February | 0.190200E+10 | 0.215820E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183517E+10 |
March | 0.217552E+10 | 0.246180E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489524.36 | 0.116897E+10 |
April | 0.205665E+10 | 0.232271E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945020E+09 |
May | 0.212923E+10 | 0.241689E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499535.98 | 0.551863E+09 |
June | 0.209978E+10 | 0.237557E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12959490.39 | 0.362697E+09 |
July | 0.208610E+10 | 0.236404E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25973782.65 | 0.209376E+09 |
August | 0.217552E+10 | 0.246180E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19313903.21 | 0.255704E+09 |
September | 0.205665E+10 | 0.232271E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640695.15 | 0.367772E+09 |
October | 0.208295E+10 | 0.237199E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792647E+09 |
November | 0.200405E+10 | 0.229370E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105289E+10 |
December | 0.208610E+10 | 0.236404E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181382E+10 |
Annual Sum or Average | 0.249375E+11 | 0.282854E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60876931.75 | 0.110867E+11 |
Minimum of Months | 0.190200E+10 | 0.215820E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209376E+09 |
Maximum of Months | 0.217552E+10 | 0.246180E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25973782.65 | 0.183517E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.237199E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170392E+10 |
February | 0.190200E+10 | 0.215820E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181097E+10 |
March | 0.217552E+10 | 0.246180E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489547.05 | 0.112029E+10 |
April | 0.205665E+10 | 0.232271E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888497E+09 |
May | 0.212923E+10 | 0.241689E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499536.06 | 0.516666E+09 |
June | 0.209978E+10 | 0.237557E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13002771.21 | 0.336263E+09 |
July | 0.208610E+10 | 0.236404E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26831360.67 | 0.187489E+09 |
August | 0.217552E+10 | 0.246180E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19424694.56 | 0.234226E+09 |
September | 0.205665E+10 | 0.232271E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1641081.10 | 0.345605E+09 |
October | 0.208295E+10 | 0.237199E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742242E+09 |
November | 0.200405E+10 | 0.229370E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989936E+09 |
December | 0.208610E+10 | 0.236404E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178008E+10 |
Annual Sum or Average | 0.249375E+11 | 0.282854E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61888990.66 | 0.106562E+11 |
Minimum of Months | 0.190200E+10 | 0.215820E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187489E+09 |
Maximum of Months | 0.217552E+10 | 0.246180E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26831360.67 | 0.181097E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.110885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214752E+11 |
February | 0.151369E+09 | 0.100890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200429E+11 |
March | 0.173136E+09 | 0.115083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149743E+11 |
April | 0.163676E+09 | 0.108581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916727E+10 |
May | 0.169453E+09 | 0.112984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414616E+10 |
June | 0.167108E+09 | 0.111052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1908669.59 | 0.152908E+10 |
July | 0.166020E+09 | 0.110513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3423434.37 | 0.524339E+09 |
August | 0.173136E+09 | 0.115083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96345.94 | 0.851603E+09 |
September | 0.163676E+09 | 0.108581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225804E+10 |
October | 0.165769E+09 | 0.110885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803373E+10 |
November | 0.159490E+09 | 0.107225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116304E+11 |
December | 0.166020E+09 | 0.110513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206392E+11 |
Annual Sum or Average | 0.198462E+10 | 0.132228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5428449.91 | 0.115272E+12 |
Minimum of Months | 0.151369E+09 | 0.100890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524339E+09 |
Maximum of Months | 0.173136E+09 | 0.115083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3423434.37 | 0.214752E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 1209.85 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7538.22 | 12-JAN-06:00 |
February | 785.10 | 01-FEB-15:09 | 1209.85 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7886.15 | 13-FEB-06:00 |
March | 785.10 | 01-MAR-15:09 | 1209.85 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 15-MAR-14:00 | 4192.29 | 02-MAR-05:05 |
April | 785.10 | 01-APR-10:09 | 1209.85 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4171.08 | 16-APR-07:00 |
May | 785.10 | 01-MAY-14:09 | 1209.85 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 14-MAY-15:00 | 1919.14 | 05-MAY-21:00 |
June | 785.10 | 01-JUN-14:09 | 1209.85 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 298.90 | 12-JUN-13:00 | 2241.40 | 13-JUN-03:00 |
July | 785.10 | 01-JUL-10:09 | 1209.85 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 451.87 | 21-JUL-03:00 | 1582.38 | 06-JUL-02:00 |
August | 785.10 | 01-AUG-14:09 | 1209.85 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 372.99 | 13-AUG-18:03 | 1173.64 | 30-AUG-20:10 |
September | 785.10 | 01-SEP-14:09 | 1209.85 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.28 | 16-SEP-13:00 | 1839.52 | 29-SEP-04:00 |
October | 785.10 | 02-OCT-14:09 | 1209.85 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2126.01 | 07-OCT-02:00 |
November | 785.10 | 01-NOV-14:09 | 1209.85 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3747.06 | 17-NOV-02:00 |
December | 785.10 | 01-DEC-15:09 | 1209.85 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6232.22 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 1209.85 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.64 | |||||
Maximum of Months | 785.10 | 1209.85 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 451.87 | 7886.15 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 21086.38 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6568.51 | 12-JAN-02:00 |
February | 24809.68 | 01-FEB-15:09 | 21086.38 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6759.60 | 13-FEB-06:00 |
March | 24809.68 | 01-MAR-15:09 | 21086.38 | 01-MAR-15:00 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 | 15-MAR-14:00 | 4090.40 | 02-MAR-01:00 |
April | 24809.68 | 01-APR-10:09 | 21086.38 | 07-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3956.62 | 16-APR-02:00 |
May | 24809.68 | 01-MAY-14:09 | 21086.38 | 11-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 | 14-MAY-15:00 | 1990.35 | 05-MAY-21:00 |
June | 24809.68 | 01-JUN-14:09 | 19329.19 | 01-JUN-16:40 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.30 | 12-JUN-13:00 | 2142.31 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 19329.19 | 03-JUL-16:49 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 366.82 | 21-JUL-03:00 | 1543.21 | 06-JUL-02:00 |
August | 24809.68 | 01-AUG-14:09 | 21086.38 | 28-AUG-16:10 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.65 | 13-AUG-18:03 | 1052.23 | 30-AUG-20:50 |
September | 24809.68 | 01-SEP-14:09 | 21086.38 | 01-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.00 | 16-SEP-13:00 | 1867.12 | 29-SEP-04:00 |
October | 24809.68 | 02-OCT-14:09 | 21086.38 | 02-OCT-16:40 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2119.66 | 07-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 21086.38 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3924.48 | 17-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 21086.38 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5376.15 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 19329.19 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.23 | |||||
Maximum of Months | 24809.68 | 21086.38 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 366.82 | 6759.60 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1986.92 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3437.86 | 12-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 1986.92 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3596.53 | 13-FEB-05:52 |
March | 2337.76 | 01-MAR-15:09 | 1986.92 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 15-MAR-14:00 | 2121.78 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 1986.92 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1902.24 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 1986.92 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 14-MAY-15:00 | 1020.13 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1986.92 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.28 | 12-JUN-13:00 | 1091.97 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1986.92 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 15-JUL-15:00 | 789.34 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1986.92 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.41 | 13-AUG-18:03 | 555.11 | 30-AUG-20:20 |
September | 2337.76 | 01-SEP-14:09 | 1986.92 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 16-SEP-13:00 | 900.66 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1986.92 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1051.45 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1986.92 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1986.36 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1986.92 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2844.96 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1986.92 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.11 | |||||
Maximum of Months | 2337.76 | 1986.92 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 3596.53 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1986.92 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3437.86 | 12-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 1986.92 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3632.54 | 13-FEB-05:54 |
March | 2337.76 | 01-MAR-15:09 | 1986.92 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 15-MAR-14:00 | 2013.01 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 1986.92 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1902.29 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 1986.92 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 14-MAY-15:00 | 960.13 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1986.92 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.31 | 12-JUN-13:00 | 1041.96 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1986.92 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 15-JUL-15:00 | 731.58 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1986.92 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.03 | 13-AUG-18:03 | 538.51 | 30-AUG-20:10 |
September | 2337.76 | 01-SEP-14:09 | 1986.92 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 | 16-SEP-13:00 | 841.10 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1986.92 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1000.70 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1986.92 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1852.50 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1986.92 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2841.43 | 28-DEC-21:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 1986.92 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.51 | |||||
Maximum of Months | 2337.76 | 1986.92 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 186.10 | 3632.54 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 92.88 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41846.93 | 31-JAN-18:00 |
February | 186.05 | 01-FEB-15:09 | 92.88 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 45204.63 | 06-FEB-18:00 |
March | 186.05 | 01-MAR-15:09 | 92.88 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37057.19 | 06-MAR-18:00 |
April | 186.05 | 01-APR-10:09 | 92.88 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 29282.19 | 16-APR-11:10 |
May | 186.05 | 01-MAY-14:09 | 92.88 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13982.73 | 11-MAY-17:00 |
June | 186.05 | 01-JUN-14:09 | 92.88 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.42 | 17-JUN-15:55 | 12836.53 | 13-JUN-11:10 |
July | 186.05 | 01-JUL-10:09 | 92.88 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.05 | 15-JUL-13:55 | 3917.67 | 02-JUL-11:05 |
August | 186.05 | 01-AUG-14:09 | 92.88 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 | 13-AUG-13:00 | 7437.34 | 31-AUG-11:10 |
September | 186.05 | 01-SEP-14:09 | 92.88 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11937.31 | 28-SEP-17:00 |
October | 186.05 | 02-OCT-14:09 | 92.88 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19711.80 | 23-OCT-17:00 |
November | 186.05 | 01-NOV-14:09 | 92.88 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 24657.58 | 22-NOV-18:00 |
December | 186.05 | 01-DEC-15:09 | 92.88 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 42965.22 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 92.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3917.67 | ||||
Maximum of Months | 186.05 | 92.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.05 | 45204.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2637.45 | 18-JAN-07:05 | 392.55 | 1075.48 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.16 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 67.20 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1902.28 |
March | 4190.35 | 19-MAR-08:05 | 392.55 | 537.74 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.84 |
April | 4513.95 | 01-APR-06:05 | 392.55 | 537.74 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.44 |
May | 3955.98 | 01-MAY-06:07 | 294.41 | 806.61 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29778.21 | 20-JUN-06:02 | 490.69 | 1344.34 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.65 |
July | 31516.51 | 12-JUL-06:02 | 490.69 | 1344.34 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 |
August | 33344.33 | 02-AUG-06:02 | 490.69 | 1344.34 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25589.32 | 09-SEP-06:02 | 490.69 | 672.17 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.39 |
October | 5321.71 | 17-OCT-06:05 | 392.55 | 1075.48 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.11 |
November | 4734.86 | 15-NOV-07:05 | 392.55 | 1075.48 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.57 |
December | 3994.01 | 03-DEC-09:05 | 392.55 | 537.74 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 67.20 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33344.33 | 490.69 | 1344.34 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1902.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59606.88 | 06-JAN-07:05 | 12404.84 | 18743.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.97 |
February | 59086.48 | 05-FEB-09:05 | 12404.84 | 6247.82 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.99 |
March | 133036.64 | 16-MAR-06:03 | 12404.84 | 18743.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.16 |
April | 43254.56 | 17-APR-06:05 | 12404.84 | 18743.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.19 |
May | 186915.23 | 27-MAY-06:03 | 12404.84 | 9371.73 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.55 |
June | 207526.94 | 15-JUN-06:02 | 15506.05 | 23429.32 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.28 |
July | 168339.49 | 06-JUL-06:02 | 15506.05 | 23429.32 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.47 |
August | 181855.00 | 03-AUG-06:02 | 15506.05 | 23429.32 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.51 |
September | 190359.24 | 12-SEP-06:02 | 15506.05 | 23429.32 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.15 |
October | 176090.82 | 06-OCT-06:03 | 12404.84 | 18743.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.68 |
November | 41413.84 | 24-NOV-07:05 | 12404.84 | 18743.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.84 |
December | 58855.23 | 10-DEC-09:05 | 12404.84 | 9371.73 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 41413.84 | 12404.84 | 6247.82 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.97 | |
Maximum of Months | 207526.94 | 15506.05 | 23429.32 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4313.70 | 12-JAN-15:30 | 2337.76 | 1986.92 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.94 |
February | 4225.48 | 13-FEB-12:13 | 6136.63 | 5960.77 | 8762.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.91 |
March | 15629.91 | 16-MAR-06:03 | 1168.88 | 1766.15 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.05 |
April | 6746.22 | 22-APR-14:00 | 2337.76 | 1986.92 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 |
May | 24597.08 | 28-MAY-08:62 | 1461.10 | 1103.85 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.85 |
June | 26996.96 | 13-JUN-06:02 | 1461.10 | 2207.69 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.65 |
July | 26220.67 | 06-JUL-06:02 | 1461.10 | 2207.69 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.73 |
August | 27605.40 | 03-AUG-06:02 | 1461.10 | 2207.69 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.25 |
September | 27631.45 | 11-SEP-06:02 | 1461.10 | 2207.69 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
October | 25605.83 | 12-OCT-06:02 | 1461.10 | 2207.69 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.74 |
November | 6034.86 | 01-NOV-12:00 | 2045.54 | 1986.92 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 |
December | 3990.92 | 07-DEC-18:03 | 4383.30 | 3311.54 | 8762.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3990.92 | 1168.88 | 1103.85 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 | |
Maximum of Months | 27631.45 | 6136.63 | 5960.77 | 8762.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3687.01 | 06-JAN-17:33 | 4383.30 | 5960.77 | 1315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.85 |
February | 4259.13 | 10-FEB-16:33 | 6136.63 | 5960.77 | 1315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.81 |
March | 5186.72 | 15-MAR-13:40 | 2045.54 | 1986.92 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 0.00 |
April | 4520.58 | 22-APR-14:20 | 2337.76 | 1986.92 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 |
May | 14790.69 | 24-MAY-06:02 | 1461.10 | 2207.69 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 |
June | 18760.41 | 11-JUN-08:62 | 1461.10 | 1103.85 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
July | 20959.61 | 12-JUL-06:02 | 1461.10 | 2207.69 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.42 |
August | 22252.42 | 04-AUG-06:02 | 1461.10 | 2207.69 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 |
September | 22472.15 | 10-SEP-08:62 | 1461.10 | 1103.85 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 |
October | 17011.32 | 12-OCT-06:02 | 1461.10 | 2207.69 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.99 |
November | 3640.89 | 15-NOV-07:05 | 1168.88 | 1766.15 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.93 |
December | 4675.96 | 27-DEC-15:32 | 9351.05 | 7947.70 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3640.89 | 1168.88 | 1103.85 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22472.15 | 9351.05 | 7947.70 | 1753.62 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 492.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.98 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.75 |
April | 8.85 | 10-APR-05:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
May | 10.46 | 19-MAY-06:13 | 69.77 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.55 |
October | 15.18 | 22-OCT-08:50 | 23.26 | 10.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.94 |
November | 21.47 | 12-NOV-08:00 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | |
Maximum of Months | 21.47 | 69.77 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.847202E+11 | 61041.90 | 02-JAN-16:49 | 0.158836E+12 | 226993.86 | 10-JAN-07:10 |
February | 0.744129E+11 | 61041.90 | 01-FEB-17:30 | 0.149724E+12 | 260299.51 | 07-FEB-07:10 |
March | 0.831751E+11 | 70100.81 | 15-MAR-16:30 | 0.849371E+11 | 220957.32 | 07-MAR-07:10 |
April | 0.757920E+11 | 55722.58 | 07-APR-16:00 | 0.349423E+11 | 158517.41 | 17-APR-06:10 |
May | 0.807232E+11 | 72907.61 | 10-MAY-15:20 | 0.124900E+11 | 34107.65 | 01-MAY-06:49 |
June | 0.939486E+11 | 88146.31 | 27-JUN-16:00 | 0.869295E+10 | 19673.68 | 13-JUN-11:09 |
July | 0.111822E+12 | 95578.87 | 15-JUL-13:00 | 0.787449E+10 | 6283.95 | 02-JUL-11:20 |
August | 0.107027E+12 | 89597.08 | 10-AUG-16:10 | 0.809719E+10 | 13095.90 | 31-AUG-11:09 |
September | 0.882814E+11 | 86609.94 | 16-SEP-15:50 | 0.899119E+10 | 18949.25 | 28-SEP-16:49 |
October | 0.823241E+11 | 68705.42 | 11-OCT-15:20 | 0.216966E+11 | 86622.49 | 30-OCT-06:10 |
November | 0.807889E+11 | 61041.90 | 06-NOV-16:00 | 0.491570E+11 | 161750.40 | 24-NOV-07:10 |
December | 0.848867E+11 | 61041.90 | 01-DEC-16:40 | 0.144038E+12 | 253386.23 | 11-DEC-07:10 |
Annual Sum or Average | 0.104790E+13 | 0.689476E+12 | ||||
Minimum of Months | 0.744129E+11 | 55722.58 | 0.787449E+10 | 6283.95 | ||
Maximum of Months | 0.111822E+12 | 95578.87 | 0.158836E+12 | 260299.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.295358E+11 | 0.877369E+10 | 0.164409E+11 | 0.00 | 0.299698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249127E+11 | 0.732151E+10 | 0.149157E+11 | 0.00 | 0.272630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278789E+11 | 0.727364E+10 | 0.168545E+11 | 0.00 | 0.303404E+11 | 0.00 | 0.00 | 0.827625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244073E+11 | 0.619807E+10 | 0.160187E+11 | 0.00 | 0.290980E+11 | 0.00 | 0.00 | 69954157.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252651E+11 | 0.566508E+10 | 0.166477E+11 | 0.00 | 0.299109E+11 | 0.00 | 0.00 | 0.323444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.242948E+11 | 0.512570E+10 | 0.162750E+11 | 0.00 | 0.290267E+11 | 0.00 | 0.00 | 0.192263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241303E+11 | 0.543847E+10 | 0.163892E+11 | 0.00 | 0.294660E+11 | 0.00 | 0.00 | 0.363982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252933E+11 | 0.607360E+10 | 0.168545E+11 | 0.00 | 0.299527E+11 | 0.00 | 0.00 | 0.288531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.254754E+11 | 0.667681E+10 | 0.160144E+11 | 0.00 | 0.288720E+11 | 0.00 | 0.00 | 0.112429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278131E+11 | 0.776195E+10 | 0.164431E+11 | 0.00 | 0.297054E+11 | 0.00 | 0.00 | 0.600570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279041E+11 | 0.825984E+10 | 0.159174E+11 | 0.00 | 0.287073E+11 | 0.00 | 0.00 | 293661.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295166E+11 | 0.897476E+10 | 0.163871E+11 | 0.00 | 0.300083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316427E+12 | 0.835431E+11 | 0.195158E+12 | 0.00 | 0.352321E+12 | 0.00 | 0.00 | 0.100453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.241303E+11 | 0.512570E+10 | 0.149157E+11 | 0.00 | 0.272630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.295358E+11 | 0.897476E+10 | 0.168545E+11 | 0.00 | 0.303404E+11 | 0.00 | 0.00 | 0.363982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.150330E+12 | 0.00 | 0.850563E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.141981E+12 | 0.00 | 0.774309E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.763397E+11 | 0.00 | 0.859738E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.267952E+11 | 0.00 | 0.814717E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.426204E+10 | 0.00 | 0.822797E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.876766E+09 | 0.00 | 0.781618E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5579069.07 | 0.00 | 0.786891E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.195386E+09 | 0.00 | 0.790180E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.133623E+10 | 0.00 | 0.765496E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136714E+11 | 0.00 | 0.802519E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.412298E+11 | 0.00 | 0.792719E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.135654E+12 | 0.00 | 0.838356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.592677E+12 | 0.00 | 0.967990E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5579069.07 | 0.00 | 0.765496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.150330E+12 | 0.00 | 0.859738E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 26362.97 | 02-JAN-09:09 | 5319.32 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 18588.57 | 01-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 26362.97 | 01-FEB-09:09 | 5319.32 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 18588.57 | 01-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 26362.97 | 01-MAR-15:00 | 5319.32 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 18588.57 | 01-MAR-11:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 26362.97 | 07-APR-16:00 | 5319.32 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 18588.57 | 04-APR-11:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26362.97 | 11-MAY-16:49 | 5319.32 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 18588.57 | 15-MAY-15:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24605.77 | 01-JUN-16:40 | 5319.32 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 18588.57 | 03-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 24605.77 | 03-JUL-16:49 | 5319.32 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 18588.57 | 02-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26362.97 | 28-AUG-16:10 | 5319.32 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 18588.57 | 30-AUG-11:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 26362.97 | 01-SEP-16:00 | 5319.32 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 18588.57 | 02-SEP-16:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26362.97 | 02-OCT-16:40 | 5319.32 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 18588.57 | 17-OCT-06:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 26362.97 | 01-NOV-08:09 | 5319.32 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 18588.57 | 02-NOV-09:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 26362.97 | 01-DEC-09:09 | 5319.32 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 18588.57 | 01-DEC-19:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24605.77 | 5319.32 | 10771.04 | 0.00 | 18588.57 | 0.00 | 0.00 | |||||
Maximum of Months | 26362.97 | 5319.32 | 10771.04 | 0.00 | 18588.57 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19180.75 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6578.37 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23973.46 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43127.71 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45366.58 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40076.73 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34153.81 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13994.97 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 148.13 | 05-NOV-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45366.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 61041.90 | 02-JAN-16:49 | 26362.97 | 10771.04 | 5319.32 | 0.00 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61041.90 | 01-FEB-17:30 | 26362.97 | 10771.04 | 5319.32 | 0.00 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70100.81 | 15-MAR-16:30 | 24605.77 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 16374.12 | 0.00 |
April | 55722.58 | 07-APR-16:00 | 26362.97 | 10771.04 | 0.00 | 0.00 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72907.61 | 10-MAY-15:20 | 21091.37 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 22695.31 | 0.00 |
June | 88146.31 | 27-JUN-16:00 | 22848.57 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 36176.81 | 0.00 |
July | 95578.87 | 15-JUL-13:00 | 21091.37 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 45366.58 | 0.00 |
August | 89597.08 | 10-AUG-16:10 | 24605.77 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 35870.39 | 0.00 |
September | 86609.94 | 16-SEP-15:50 | 24605.77 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 32883.24 | 0.00 |
October | 68705.42 | 11-OCT-15:20 | 26362.97 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 13221.52 | 0.00 |
November | 61041.90 | 06-NOV-16:00 | 26362.97 | 10771.04 | 5319.32 | 0.00 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61041.90 | 01-DEC-16:40 | 26362.97 | 10771.04 | 5319.32 | 0.00 | 18588.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 55722.58 | 21091.37 | 10771.04 | 0.00 | 0.00 | 18349.89 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95578.87 | 26362.97 | 10771.04 | 5319.32 | 0.00 | 18588.57 | 0.00 | 0.00 | 45366.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 222419.46 | 10-JAN-07:10 | 0.00 | 5207.94 | 26-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 256224.49 | 07-FEB-07:10 | 0.00 | 5271.32 | 09-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 217149.50 | 07-MAR-07:10 | 0.00 | 5181.92 | 10-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 156655.41 | 17-APR-06:10 | 0.00 | 5130.71 | 05-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 32245.65 | 01-MAY-06:49 | 0.00 | 5090.75 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 14657.21 | 13-JUN-11:09 | 0.00 | 5036.27 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 1556.91 | 02-JUL-11:09 | 0.00 | 4991.69 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 8128.01 | 31-AUG-11:09 | 0.00 | 4968.93 | 01-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 14129.36 | 28-SEP-16:00 | 0.00 | 4992.54 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 84760.49 | 30-OCT-06:10 | 0.00 | 5037.60 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 157188.42 | 24-NOV-07:10 | 0.00 | 5088.82 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 248817.98 | 11-DEC-07:10 | 0.00 | 5132.54 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 1556.91 | 0.00 | 4968.93 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 256224.49 | 0.00 | 5271.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
February | 6.67 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
March | 1.67 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
December | 2.67 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
Annual Sum or Average | 15.33 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
February | 5.67 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
March | 0.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
Annual Sum or Average | 11.17 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
February | 8.83 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
March | 1.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
April | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.17 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 20.83 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
February | 1.50 | 18.05 | 0.33 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
March | 3.33 | 19.59 | 2.00 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
April | 4.83 | 19.99 | 3.67 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
May | 1.50 | 20.27 | 1.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 20.00 | 2.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
November | 7.33 | 19.03 | 3.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
December | 3.33 | 18.19 | 0.83 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
Annual Sum or Average | 26.67 | 19.22 | 13.50 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 20.27 | 3.67 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.30 | 344.83 | 21.22 | 344.83 | 21.18 |
April | 405.00 | 21.35 | 216.00 | 21.26 | 216.00 | 21.22 |
May | 414.17 | 22.90 | 14.17 | 22.84 | 14.17 | 22.79 |
June | 199.17 | 23.77 | 145.50 | 23.82 | 49.33 | 23.83 |
July | 103.67 | 23.89 | 325.67 | 23.89 | 98.33 | 23.89 |
August | 85.83 | 23.87 | 225.17 | 23.89 | 62.50 | 23.89 |
September | 249.83 | 23.58 | 81.17 | 23.65 | 40.50 | 23.68 |
October | 414.00 | 21.93 | 95.17 | 21.77 | 95.17 | 21.67 |
November | 399.00 | 21.17 | 312.17 | 21.14 | 312.17 | 21.13 |
December | 415.00 | 21.11 | 408.50 | 21.11 | 408.50 | 21.11 |
Annual Sum or Average | 3897.67 | 21.87 | 2958.33 | 21.86 | 2431.50 | 21.74 |
Minimum of Months | 85.83 | 21.11 | 14.17 | 21.11 | 14.17 | 21.11 |
Maximum of Months | 422.00 | 23.89 | 414.00 | 23.89 | 414.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 367.83 | 21.11 | 367.83 | 21.11 |
February | 376.00 | 21.12 | 335.67 | 21.11 | 335.67 | 21.11 |
March | 396.00 | 21.38 | 156.17 | 21.32 | 153.33 | 21.27 |
April | 394.67 | 22.32 | 17.33 | 22.27 | 17.33 | 22.22 |
May | 165.50 | 23.42 | 59.50 | 23.55 | 2.17 | 23.55 |
June | 52.33 | 23.82 | 281.00 | 23.88 | 40.17 | 23.88 |
July | 98.50 | 23.90 | 404.50 | 23.89 | 98.50 | 23.89 |
August | 61.00 | 23.89 | 381.67 | 23.89 | 61.00 | 23.89 |
September | 69.00 | 23.65 | 214.33 | 23.83 | 37.83 | 23.84 |
October | 312.00 | 22.51 | 13.33 | 22.53 | 4.00 | 22.52 |
November | 399.00 | 21.63 | 54.83 | 21.56 | 54.83 | 21.52 |
December | 415.00 | 21.13 | 301.67 | 21.12 | 301.67 | 21.12 |
Annual Sum or Average | 3153.00 | 21.87 | 2587.83 | 22.18 | 1474.33 | 22.05 |
Minimum of Months | 52.33 | 21.11 | 13.33 | 21.11 | 2.17 | 21.11 |
Maximum of Months | 415.00 | 23.90 | 404.50 | 23.89 | 367.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.14 | 354.00 | 21.13 | 354.00 | 21.12 |
February | 376.00 | 21.20 | 308.83 | 21.16 | 308.83 | 21.14 |
March | 382.50 | 21.90 | 138.83 | 21.80 | 118.83 | 21.67 |
April | 332.17 | 22.66 | 39.00 | 22.52 | 36.17 | 22.39 |
May | 156.67 | 23.45 | 85.67 | 23.60 | 0.00 | 23.60 |
June | 56.33 | 23.80 | 291.00 | 23.88 | 35.83 | 23.88 |
July | 87.50 | 23.89 | 403.00 | 23.89 | 87.50 | 23.89 |
August | 51.33 | 23.89 | 400.33 | 23.89 | 50.33 | 23.89 |
September | 53.83 | 23.69 | 304.17 | 23.86 | 30.00 | 23.86 |
October | 213.83 | 22.97 | 79.17 | 23.17 | 5.00 | 23.14 |
November | 360.00 | 22.17 | 63.83 | 22.01 | 63.83 | 21.89 |
December | 415.00 | 21.20 | 330.67 | 21.16 | 330.67 | 21.15 |
Annual Sum or Average | 2899.17 | 22.05 | 2798.50 | 22.36 | 1421.00 | 22.19 |
Minimum of Months | 51.33 | 21.14 | 39.00 | 21.13 | 0.00 | 21.12 |
Maximum of Months | 415.00 | 23.89 | 403.00 | 23.89 | 354.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 388.17 | 21.11 | 388.17 | 21.11 |
February | 376.00 | 21.12 | 349.83 | 21.11 | 349.83 | 21.11 |
March | 395.83 | 21.37 | 185.67 | 21.34 | 174.33 | 21.29 |
April | 366.33 | 21.97 | 63.00 | 21.84 | 63.00 | 21.75 |
May | 239.33 | 23.03 | 42.83 | 23.14 | 4.33 | 23.13 |
June | 96.83 | 23.62 | 252.00 | 23.82 | 48.33 | 23.83 |
July | 99.17 | 23.89 | 394.50 | 23.89 | 96.83 | 23.89 |
August | 64.00 | 23.85 | 379.17 | 23.88 | 57.67 | 23.89 |
September | 90.17 | 23.39 | 263.00 | 23.76 | 36.00 | 23.77 |
October | 286.00 | 22.25 | 61.17 | 22.42 | 15.67 | 22.36 |
November | 391.00 | 21.63 | 122.67 | 21.51 | 122.67 | 21.43 |
December | 415.00 | 21.12 | 373.50 | 21.12 | 373.50 | 21.11 |
Annual Sum or Average | 3233.67 | 21.83 | 2875.50 | 22.12 | 1730.33 | 21.98 |
Minimum of Months | 64.00 | 21.11 | 42.83 | 21.11 | 4.33 | 21.11 |
Maximum of Months | 415.00 | 23.89 | 394.50 | 23.89 | 388.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.08 | 362.67 | 21.08 | 362.67 | 21.08 |
February | 376.00 | 21.09 | 328.17 | 21.08 | 328.17 | 21.08 |
March | 404.83 | 21.12 | 189.67 | 21.20 | 175.83 | 21.16 |
April | 405.00 | 21.13 | 79.17 | 21.11 | 79.17 | 21.09 |
May | 396.50 | 21.46 | 20.67 | 21.54 | 9.17 | 21.52 |
June | 298.83 | 23.08 | 201.83 | 23.89 | 114.67 | 24.15 |
July | 295.33 | 25.79 | 370.17 | 25.79 | 267.17 | 25.90 |
August | 276.17 | 25.14 | 327.83 | 25.48 | 206.67 | 25.68 |
September | 325.00 | 22.26 | 128.00 | 22.87 | 70.67 | 23.10 |
October | 401.50 | 21.27 | 29.50 | 21.28 | 23.17 | 21.26 |
November | 399.00 | 21.10 | 154.17 | 21.09 | 154.17 | 21.08 |
December | 415.00 | 21.08 | 369.50 | 21.08 | 369.50 | 21.08 |
Annual Sum or Average | 4407.17 | 21.94 | 2561.33 | 22.28 | 2161.00 | 22.34 |
Minimum of Months | 276.17 | 21.08 | 20.67 | 21.08 | 9.17 | 21.08 |
Maximum of Months | 415.00 | 25.79 | 370.17 | 25.79 | 369.50 | 25.90 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10878 | 15.09171 | -0.7977 | 18.54727 |
February | 376.00000 | 21.10872 | 15.10395 | -0.7993 | 18.57827 |
March | 422.00000 | 21.30140 | 24.14460 | -0.6280 | 14.61533 |
April | 405.00000 | 21.34514 | 30.07529 | -0.5118 | 10.98251 |
May | 418.00000 | 22.91180 | 35.28219 | -1.1018 | 32.18817 |
June | 408.00000 | 23.83053 | 46.14522 | -0.5906 | 12.87891 |
July | 415.00000 | 23.89083 | 55.90337 | -0.4301 | 8.99819 |
August | 422.00000 | 23.88638 | 50.79661 | -0.4865 | 10.10642 |
September | 405.00000 | 23.69538 | 46.39148 | -0.6747 | 15.53152 |
October | 414.00000 | 21.92735 | 35.66011 | -0.2895 | 8.33989 |
November | 399.00000 | 21.16717 | 28.55891 | -0.5828 | 12.39940 |
December | 415.00000 | 21.10903 | 19.02179 | -0.7518 | 17.08809 |
Annual Sum or Average | 4913.00000 | 22.28478 | 33.65535 | -0.6363 | 15.01524 |
Minimum of Months | 376.00000 | 21.10872 | 15.09171 | -1.1018 | 8.33989 |
Maximum of Months | 422.00000 | 23.89083 | 55.90337 | -0.2895 | 32.18817 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.11448 | 19.14955 | -0.6370 | 13.68071 |
February | 376.00000 | 21.11562 | 19.07494 | -0.6355 | 13.62378 |
March | 422.00000 | 21.53690 | 27.63195 | -0.3963 | 10.06750 |
April | 405.00000 | 22.36096 | 32.31081 | -0.1278 | 6.94038 |
May | 418.00000 | 23.70281 | 35.94293 | -0.6416 | 14.52351 |
June | 408.00000 | 23.87879 | 46.80829 | -0.4001 | 8.64530 |
July | 415.00000 | 23.89117 | 56.47508 | -0.2932 | 6.90365 |
August | 422.00000 | 23.88940 | 51.75536 | -0.3490 | 7.67550 |
September | 405.00000 | 23.84574 | 47.19221 | -0.4688 | 9.98310 |
October | 414.00000 | 22.85013 | 37.18997 | 0.03999 | 6.61725 |
November | 399.00000 | 21.62624 | 31.86152 | -0.3363 | 8.39058 |
December | 415.00000 | 21.13026 | 22.87918 | -0.5925 | 12.62117 |
Annual Sum or Average | 4913.00000 | 22.59058 | 35.81592 | -0.4021 | 9.95648 |
Minimum of Months | 376.00000 | 21.11448 | 19.07494 | -0.6416 | 6.61725 |
Maximum of Months | 422.00000 | 23.89117 | 56.47508 | 0.03999 | 14.52351 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.14292 | 18.47560 | -0.6524 | 14.30507 |
February | 376.00000 | 21.19822 | 18.45431 | -0.6356 | 14.03953 |
March | 422.00000 | 22.08572 | 26.18030 | -0.2717 | 9.22092 |
April | 405.00000 | 22.88064 | 30.11724 | -0.0256 | 7.23236 |
May | 418.00000 | 23.72342 | 34.71156 | -0.6318 | 14.63111 |
June | 408.00000 | 23.87669 | 45.74107 | -0.3705 | 8.39322 |
July | 415.00000 | 23.89092 | 54.84460 | -0.2304 | 6.31119 |
August | 422.00000 | 23.88929 | 50.49484 | -0.2573 | 6.66786 |
September | 405.00000 | 23.86309 | 45.82329 | -0.3660 | 8.43885 |
October | 414.00000 | 23.41366 | 34.73423 | 0.19620 | 7.40557 |
November | 399.00000 | 22.33657 | 29.72751 | -0.1858 | 7.96544 |
December | 415.00000 | 21.20352 | 22.26568 | -0.6079 | 13.32607 |
Annual Sum or Average | 4913.00000 | 22.80362 | 34.42181 | -0.3352 | 9.80804 |
Minimum of Months | 376.00000 | 21.14292 | 18.45431 | -0.6524 | 6.31119 |
Maximum of Months | 422.00000 | 23.89092 | 54.84460 | 0.19620 | 14.63111 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10972 | 18.59220 | -0.6977 | 15.49698 |
February | 376.00000 | 21.11648 | 18.57647 | -0.6894 | 15.30366 |
March | 422.00000 | 21.52743 | 27.21344 | -0.4201 | 10.67575 |
April | 405.00000 | 22.15433 | 31.91163 | -0.2047 | 8.06168 |
May | 418.00000 | 23.39635 | 36.35973 | -0.7803 | 19.95455 |
June | 408.00000 | 23.82573 | 46.81361 | -0.4378 | 9.78973 |
July | 415.00000 | 23.88878 | 55.94860 | -0.2773 | 6.82930 |
August | 422.00000 | 23.88375 | 51.23854 | -0.3098 | 7.32604 |
September | 405.00000 | 23.77622 | 46.79829 | -0.4427 | 10.14890 |
October | 414.00000 | 22.75885 | 36.68005 | 0.03226 | 7.37582 |
November | 399.00000 | 21.67660 | 31.12979 | -0.3557 | 9.38088 |
December | 415.00000 | 21.12026 | 22.42996 | -0.6637 | 14.56292 |
Annual Sum or Average | 4913.00000 | 22.53105 | 35.43617 | -0.4360 | 11.22563 |
Minimum of Months | 376.00000 | 21.10972 | 18.57647 | -0.7803 | 6.82930 |
Maximum of Months | 422.00000 | 23.88878 | 55.94860 | 0.03226 | 19.95455 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.08484 | 14.65249 | -0.6994 | 15.69341 |
February | 376.00000 | 21.08605 | 14.48024 | -0.6892 | 15.42713 |
March | 422.00000 | 21.27176 | 23.67192 | -0.4576 | 11.18936 |
April | 405.00000 | 21.13208 | 30.17149 | -0.3885 | 8.78280 |
May | 418.00000 | 21.60789 | 37.83072 | -1.2365 | 38.60942 |
June | 408.00000 | 23.49689 | 49.38526 | -0.5249 | 20.16850 |
July | 415.00000 | 25.45465 | 58.25824 | 0.14996 | 13.39673 |
August | 422.00000 | 24.97409 | 51.69094 | -0.0207 | 14.84685 |
September | 405.00000 | 22.59116 | 50.43285 | -0.7322 | 21.62138 |
October | 414.00000 | 21.32256 | 36.55683 | -0.2260 | 7.11854 |
November | 399.00000 | 21.10144 | 27.94243 | -0.4691 | 10.21397 |
December | 415.00000 | 21.08467 | 18.19802 | -0.6776 | 15.04604 |
Annual Sum or Average | 4913.00000 | 22.19841 | 34.58863 | -0.4957 | 16.03752 |
Minimum of Months | 376.00000 | 21.08467 | 14.48024 | -1.2365 | 7.11854 |
Maximum of Months | 422.00000 | 25.45465 | 58.25824 | 0.14996 | 38.60942 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 40457359.20 | 11960743.08 | 6.17 | 38546520.23 | 1910838.97 | 0.00 | 0.10 | 15-MAR-14:50 | 0.00 | 01-MAR-00:10 | 2300.06 | 15-MAR-15:00 | 2203.53 | 15-MAR-14:40 | 113.49 | 15-MAR-17:00 | 683.32 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.250117E+09 | 71384409.32 | 52.83 | 0.230603E+09 | 19513579.29 | 0.00 | 0.19 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4607.45 | 14-MAY-15:00 | 3845.72 | 23-MAY-15:00 | 790.09 | 14-MAY-14:30 | 1330.89 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.512972E+10 | 0.139076E+10 | 261.20 | 0.396919E+10 | 0.116053E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 32968.82 | 18-JUN-08:62 | 21889.85 | 02-JUN-06:02 | 15748.29 | 18-JUN-08:04 | 6950.42 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.122656E+11 | 0.326777E+10 | 394.82 | 0.881224E+10 | 0.345333E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 33791.40 | 21-JUL-05:02 | 22152.79 | 15-JUL-06:02 | 18090.64 | 29-JUL-06:04 | 7039.56 | 21-JUL-06:15 | 0.00 | 01-JUL-00:10 |
August | 0.901279E+10 | 0.244716E+10 | 363.21 | 0.723972E+10 | 0.177307E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33071.24 | 14-AUG-06:02 | 24358.06 | 06-AUG-08:62 | 18097.29 | 14-AUG-06:06 | 6852.61 | 14-AUG-06:15 | 0.00 | 01-AUG-00:10 |
September | 0.238172E+10 | 0.642242E+09 | 184.57 | 0.173390E+10 | 0.647825E+09 | 0.00 | 1.00 | 09-SEP-06:02 | 0.00 | 01-SEP-00:10 | 32034.47 | 16-SEP-06:02 | 18112.66 | 17-SEP-08:62 | 15688.58 | 14-SEP-06:02 | 6714.09 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 759.57 | 215.44 | 3.17 | 645.92 | 113.66 | 0.00 | 0.00 | 12-OCT-15:50 | 0.00 | 01-OCT-00:10 | 0.17 | 12-OCT-15:50 | 0.14 | 03-OCT-14:30 | 0.04 | 12-OCT-15:50 | 0.05 | 12-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.290804E+11 | 0.783128E+10 | 1265.96 | 0.220242E+11 | 0.705618E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122656E+11 | 0.326777E+10 | 394.82 | 0.881224E+10 | 0.345333E+10 | 0.00 | 1.00 | 0.00 | 33791.40 | 24358.06 | 18097.29 | 7039.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.201017E+10 | 0.622267E+09 | 20.29 | 0.170942E+10 | 0.300745E+09 | 0.00 | 0.72 | 16-MAR-06:03 | 0.00 | 01-MAR-00:10 | 101153.32 | 16-MAR-06:03 | 71877.98 | 16-MAR-06:03 | 29275.34 | 16-MAR-06:03 | 26179.65 | 16-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.152703E+09 | 47304213.56 | 9.17 | 0.140289E+09 | 12414172.58 | 0.00 | 0.13 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 15660.67 | 08-APR-13:30 | 14683.45 | 08-APR-13:00 | 1532.19 | 08-APR-14:00 | 4809.57 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.866097E+10 | 0.259063E+10 | 117.81 | 0.785034E+10 | 0.810626E+09 | 0.00 | 1.00 | 11-MAY-06:03 | 0.00 | 01-MAY-00:10 | 166120.29 | 29-MAY-08:62 | 142798.10 | 17-MAY-06:02 | 65081.90 | 11-MAY-06:03 | 39441.35 | 29-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.498646E+11 | 0.145747E+11 | 324.91 | 0.380554E+11 | 0.118093E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 181784.90 | 18-JUN-08:62 | 149644.93 | 11-JUN-08:62 | 86776.99 | 08-JUN-06:02 | 42682.37 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.928620E+11 | 0.267476E+11 | 411.34 | 0.650951E+11 | 0.277669E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 184284.85 | 21-JUL-05:02 | 119557.88 | 15-JUL-06:02 | 96581.82 | 29-JUL-06:04 | 43183.29 | 21-JUL-06:04 | 0.00 | 01-JUL-00:10 |
August | 0.713888E+11 | 0.209897E+11 | 386.24 | 0.554431E+11 | 0.159456E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 182100.82 | 14-AUG-06:02 | 132289.42 | 06-AUG-08:62 | 96696.45 | 14-AUG-06:04 | 42077.27 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.279225E+11 | 0.814060E+10 | 236.11 | 0.204508E+11 | 0.747168E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 176323.75 | 16-SEP-06:02 | 124808.57 | 08-SEP-06:02 | 84443.59 | 14-SEP-06:04 | 41253.09 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.119647E+10 | 0.360569E+09 | 30.15 | 0.104925E+10 | 0.147221E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 162170.78 | 01-OCT-08:62 | 115479.15 | 12-OCT-06:02 | 60888.22 | 01-OCT-08:62 | 38590.59 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 613500.79 | 194462.52 | 0.83 | 514134.38 | 99366.41 | 0.00 | 0.00 | 05-NOV-15:40 | 0.00 | 01-NOV-00:10 | 467.48 | 05-NOV-15:40 | 380.89 | 05-NOV-10:50 | 96.84 | 05-NOV-15:40 | 148.13 | 05-NOV-15:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.254059E+12 | 0.740737E+11 | 1536.84 | 0.189794E+12 | 0.642646E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.928620E+11 | 0.267476E+11 | 411.34 | 0.650951E+11 | 0.277669E+11 | 0.00 | 1.00 | 0.00 | 184284.85 | 149644.93 | 96696.45 | 43183.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.448051E+09 | 0.120572E+09 | 21.21 | 0.398018E+09 | 50032360.47 | 0.00 | 0.49 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 9833.12 | 15-MAR-13:40 | 9410.17 | 15-MAR-13:50 | 1894.22 | 16-MAR-06:03 | 2633.14 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 64727444.06 | 17635580.46 | 11.67 | 62326749.50 | 2400694.56 | 0.00 | 0.23 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 4232.46 | 08-APR-13:30 | 4067.82 | 08-APR-13:30 | 262.89 | 08-APR-14:00 | 1130.89 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.136895E+10 | 0.365048E+09 | 110.03 | 0.127619E+10 | 92755801.79 | 0.00 | 1.00 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 | 23659.13 | 24-MAY-06:02 | 20540.62 | 28-MAY-08:62 | 6960.49 | 24-MAY-06:02 | 5034.78 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.733307E+10 | 0.191522E+10 | 305.06 | 0.586241E+10 | 0.147066E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26199.44 | 18-JUN-08:62 | 22149.39 | 11-JUN-08:62 | 12575.97 | 08-JUN-06:02 | 5513.24 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.140959E+11 | 0.362481E+10 | 408.58 | 0.104556E+11 | 0.364037E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 26881.38 | 21-JUL-05:02 | 17423.88 | 15-JUL-06:02 | 14270.94 | 29-JUL-06:02 | 5577.53 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.118970E+11 | 0.308753E+10 | 384.95 | 0.971655E+10 | 0.218044E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26267.19 | 14-AUG-06:02 | 19587.90 | 06-AUG-08:62 | 14370.17 | 14-AUG-06:04 | 5435.24 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.568041E+10 | 0.145447E+10 | 260.05 | 0.445205E+10 | 0.122836E+10 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 25381.52 | 16-SEP-06:02 | 18225.64 | 10-SEP-08:62 | 12299.82 | 14-SEP-06:02 | 5322.37 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.590329E+09 | 0.156349E+09 | 55.11 | 0.535008E+09 | 55320275.94 | 0.00 | 1.00 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 22380.16 | 12-OCT-06:02 | 16981.37 | 12-OCT-06:02 | 6469.73 | 13-OCT-06:02 | 4749.71 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 350877.39 | 99174.85 | 1.25 | 322341.25 | 28536.14 | 0.00 | 0.01 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 | 189.58 | 16-NOV-12:40 | 174.78 | 16-NOV-12:40 | 14.80 | 16-NOV-12:40 | 53.55 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.414788E+11 | 0.107417E+11 | 1557.90 | 0.327584E+11 | 0.872036E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.140959E+11 | 0.362481E+10 | 408.58 | 0.104556E+11 | 0.364037E+10 | 0.00 | 1.00 | 0.00 | 26881.38 | 22149.39 | 14370.17 | 5577.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.264881E+09 | 72824445.63 | 18.00 | 0.231449E+09 | 33431544.61 | 0.00 | 0.43 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 7156.21 | 15-MAR-13:40 | 6715.96 | 15-MAR-13:50 | 1256.38 | 14-MAR-13:00 | 1953.32 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 18196088.05 | 5014363.56 | 6.83 | 17057018.31 | 1139069.73 | 0.00 | 0.15 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 2338.17 | 08-APR-13:30 | 2195.68 | 08-APR-13:30 | 181.64 | 08-APR-14:00 | 637.91 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.765526E+09 | 0.207380E+09 | 75.04 | 0.706159E+09 | 59366968.98 | 0.00 | 0.84 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 | 16211.39 | 24-MAY-06:02 | 11172.57 | 24-MAY-06:02 | 5038.83 | 24-MAY-06:02 | 3628.98 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.509475E+10 | 0.134556E+10 | 266.06 | 0.396666E+10 | 0.112809E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 22393.19 | 18-JUN-08:62 | 18460.70 | 11-JUN-08:62 | 10854.65 | 18-JUN-08:04 | 4712.71 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.106094E+11 | 0.275798E+10 | 393.50 | 0.766743E+10 | 0.294198E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 22960.54 | 21-JUL-05:02 | 14659.87 | 15-JUL-06:02 | 12247.76 | 29-JUL-06:02 | 4768.83 | 21-JUL-06:04 | 0.00 | 01-JUL-00:10 |
August | 0.887869E+10 | 0.232867E+10 | 355.30 | 0.714512E+10 | 0.173358E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 22458.57 | 14-AUG-06:02 | 16399.86 | 06-AUG-08:62 | 12415.91 | 14-AUG-06:04 | 4646.24 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.388449E+10 | 0.100555E+10 | 226.18 | 0.300019E+10 | 0.884295E+09 | 0.00 | 1.00 | 09-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21722.09 | 16-SEP-06:02 | 15094.18 | 10-SEP-08:62 | 10599.72 | 14-SEP-06:02 | 4552.07 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.313840E+09 | 83652091.79 | 35.81 | 0.283490E+09 | 30349911.46 | 0.00 | 0.76 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 13359.35 | 12-OCT-06:02 | 9911.27 | 12-OCT-06:02 | 3448.09 | 12-OCT-06:02 | 3064.80 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 83.62 | 23.74 | 0.33 | 75.85 | 7.77 | 0.00 | 0.00 | 05-NOV-11:00 | 0.00 | 01-NOV-00:10 | 0.10 | 05-NOV-11:00 | 0.09 | 05-NOV-11:00 | 0.01 | 05-NOV-11:00 | 0.03 | 05-NOV-11:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.298298E+11 | 0.780663E+10 | 1377.05 | 0.230176E+11 | 0.681223E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.106094E+11 | 0.275798E+10 | 393.50 | 0.766743E+10 | 0.294198E+10 | 0.00 | 1.00 | 0.00 | 22960.54 | 18460.70 | 12415.91 | 4768.83 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.69 | 10.57 | 25.12 | 14.59 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 56.69 | 16.58 | 40.11 | 35.35 | 87.73 | 0.00 | 0.00 | 0.00 |
March | 87.41 | 44.84 | 42.58 | 80.30 | 65.37 | 0.00 | 0.00 | 0.00 |
April | 117.15 | 62.62 | 54.52 | 122.30 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 149.14 | 91.91 | 57.24 | 169.48 | 37.14 | 0.00 | 0.00 | 0.00 |
June | 172.74 | 108.39 | 64.35 | 209.93 | 26.86 | 0.00 | 0.00 | 0.00 |
July | 160.12 | 97.25 | 62.86 | 202.56 | 20.09 | 0.00 | 0.00 | 0.00 |
August | 135.86 | 75.28 | 60.58 | 169.27 | 24.76 | 0.00 | 0.00 | 0.00 |
September | 101.74 | 55.55 | 46.19 | 117.56 | 37.19 | 0.00 | 0.00 | 0.00 |
October | 63.23 | 27.40 | 35.83 | 60.10 | 52.64 | 0.00 | 0.00 | 0.00 |
November | 36.51 | 11.37 | 25.14 | 25.30 | 62.95 | 0.00 | 0.00 | 0.00 |
December | 31.51 | 6.77 | 24.74 | 11.75 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.84 | 50.90 | 44.95 | 101.90 | 53.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.51 | 6.77 | 24.74 | 11.75 | 20.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.74 | 108.39 | 64.35 | 209.93 | 92.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 974.40 | 568.79 | 405.61 | 824.38 | 1068.93 | 0.00 | 0.00 | 0.00 |
February | 1112.52 | 536.45 | 576.07 | 935.18 | 1038.18 | 0.00 | 0.00 | 0.00 |
March | 1357.91 | 763.00 | 594.91 | 1382.19 | 784.71 | 0.00 | 0.00 | 0.00 |
April | 1124.56 | 449.38 | 675.18 | 1188.59 | 623.74 | 0.00 | 0.00 | 0.00 |
May | 984.09 | 285.82 | 698.27 | 1120.98 | 438.05 | 0.00 | 0.00 | 0.00 |
June | 956.22 | 202.63 | 753.59 | 1203.58 | 297.44 | 0.00 | 0.00 | 0.00 |
July | 976.15 | 236.84 | 739.30 | 1351.66 | 213.76 | 0.00 | 0.00 | 0.00 |
August | 1095.88 | 355.31 | 740.57 | 1487.06 | 280.20 | 0.00 | 0.00 | 0.00 |
September | 1274.18 | 620.62 | 653.56 | 1597.56 | 431.73 | 0.00 | 0.00 | 0.00 |
October | 1219.21 | 696.43 | 522.77 | 1332.26 | 632.80 | 0.00 | 0.00 | 0.00 |
November | 873.17 | 492.93 | 380.24 | 848.19 | 761.83 | 0.00 | 0.00 | 0.00 |
December | 814.79 | 421.69 | 393.10 | 653.68 | 1047.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1063.26 | 468.91 | 594.35 | 1161.76 | 632.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.79 | 202.63 | 380.24 | 653.68 | 213.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.91 | 763.00 | 753.59 | 1597.56 | 1068.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 974.40 | 568.79 | 405.61 | 822.72 | 1060.12 | 0.00 | 0.00 | 0.00 |
February | 1112.52 | 536.45 | 576.07 | 933.94 | 1028.89 | 0.00 | 0.00 | 0.00 |
March | 1357.91 | 763.00 | 594.91 | 1389.94 | 759.82 | 0.00 | 0.00 | 0.00 |
April | 1124.56 | 449.38 | 675.18 | 1199.54 | 593.01 | 0.00 | 0.00 | 0.00 |
May | 984.09 | 285.82 | 698.27 | 1125.53 | 416.21 | 0.00 | 0.00 | 0.00 |
June | 956.22 | 202.63 | 753.59 | 1201.16 | 283.45 | 0.00 | 0.00 | 0.00 |
July | 976.15 | 236.84 | 739.30 | 1346.88 | 202.02 | 0.00 | 0.00 | 0.00 |
August | 1095.88 | 355.31 | 740.57 | 1482.01 | 267.89 | 0.00 | 0.00 | 0.00 |
September | 1274.18 | 620.62 | 653.56 | 1594.92 | 416.96 | 0.00 | 0.00 | 0.00 |
October | 1219.21 | 696.43 | 522.77 | 1340.29 | 602.84 | 0.00 | 0.00 | 0.00 |
November | 873.17 | 492.93 | 380.24 | 855.60 | 729.71 | 0.00 | 0.00 | 0.00 |
December | 814.79 | 421.69 | 393.10 | 653.17 | 1037.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1063.26 | 468.91 | 594.35 | 1163.46 | 614.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.79 | 202.63 | 380.24 | 653.17 | 202.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1357.91 | 763.00 | 753.59 | 1594.92 | 1060.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.47 | 117.02 | 83.45 | 164.65 | 217.62 | 0.00 | 0.00 | 0.00 |
February | 228.89 | 110.37 | 118.52 | 186.37 | 211.55 | 0.00 | 0.00 | 0.00 |
March | 279.37 | 156.98 | 122.39 | 280.12 | 154.38 | 0.00 | 0.00 | 0.00 |
April | 231.36 | 92.45 | 138.91 | 245.05 | 117.95 | 0.00 | 0.00 | 0.00 |
May | 202.46 | 58.80 | 143.66 | 234.08 | 79.77 | 0.00 | 0.00 | 0.00 |
June | 196.73 | 41.69 | 155.04 | 244.87 | 55.67 | 0.00 | 0.00 | 0.00 |
July | 200.83 | 48.73 | 152.10 | 266.40 | 42.35 | 0.00 | 0.00 | 0.00 |
August | 225.46 | 73.10 | 152.36 | 295.48 | 55.65 | 0.00 | 0.00 | 0.00 |
September | 262.15 | 127.69 | 134.46 | 327.87 | 80.97 | 0.00 | 0.00 | 0.00 |
October | 250.84 | 143.28 | 107.55 | 275.20 | 118.37 | 0.00 | 0.00 | 0.00 |
November | 179.64 | 101.41 | 78.23 | 173.54 | 147.04 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 86.76 | 80.88 | 130.49 | 213.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.75 | 96.47 | 122.28 | 235.61 | 124.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 41.69 | 78.23 | 130.49 | 42.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.37 | 156.98 | 155.04 | 327.87 | 217.62 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95585903.70 | 28303369.25 | 67282534.45 | 39076328.51 | 0.248038E+09 |
February | 0.137136E+09 | 40099040.40 | 97037459.02 | 85515000.30 | 0.212233E+09 |
March | 0.234129E+09 | 0.120088E+09 | 0.114041E+09 | 0.215067E+09 | 0.175080E+09 |
April | 0.303649E+09 | 0.162323E+09 | 0.141326E+09 | 0.316996E+09 | 0.127767E+09 |
May | 0.399468E+09 | 0.246165E+09 | 0.153303E+09 | 0.453948E+09 | 99475294.72 |
June | 0.447754E+09 | 0.280946E+09 | 0.166808E+09 | 0.544133E+09 | 69624222.70 |
July | 0.428859E+09 | 0.260486E+09 | 0.168373E+09 | 0.542549E+09 | 53801458.83 |
August | 0.363888E+09 | 0.201635E+09 | 0.162253E+09 | 0.453368E+09 | 66318051.80 |
September | 0.263715E+09 | 0.143994E+09 | 0.119721E+09 | 0.304716E+09 | 96403887.82 |
October | 0.169351E+09 | 73384353.92 | 95966648.62 | 0.160967E+09 | 0.140991E+09 |
November | 94642271.39 | 29475091.56 | 65167179.82 | 65588205.09 | 0.163174E+09 |
December | 84389218.75 | 18128761.08 | 66260457.66 | 31469753.53 | 0.239574E+09 |
Annual Sum or Average | 0.302257E+10 | 0.160503E+10 | 0.141754E+10 | 0.321339E+10 | 0.169248E+10 |
Minimum of Months | 84389218.75 | 18128761.08 | 65167179.82 | 31469753.53 | 53801458.83 |
Maximum of Months | 0.447754E+09 | 0.280946E+09 | 0.168373E+09 | 0.544133E+09 | 0.248038E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.220803E+10 | 0.286302E+10 |
February | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.226239E+10 | 0.251157E+10 |
March | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.370206E+10 | 0.210177E+10 |
April | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.308083E+10 | 0.161672E+10 |
May | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.300243E+10 | 0.117328E+10 |
June | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.311969E+10 | 0.770961E+09 |
July | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.362028E+10 | 0.572523E+09 |
August | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.398294E+10 | 0.750481E+09 |
September | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.414088E+10 | 0.111903E+10 |
October | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.356833E+10 | 0.169490E+10 |
November | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.219851E+10 | 0.197466E+10 |
December | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.175081E+10 | 0.280586E+10 |
Annual Sum or Average | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.366372E+11 | 0.199548E+11 |
Minimum of Months | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.175081E+10 | 0.572523E+09 |
Maximum of Months | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.414088E+10 | 0.286302E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.220357E+10 | 0.283942E+10 |
February | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.225939E+10 | 0.248908E+10 |
March | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.372281E+10 | 0.203510E+10 |
April | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.310920E+10 | 0.153708E+10 |
May | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.301463E+10 | 0.111476E+10 |
June | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.311342E+10 | 0.734706E+09 |
July | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.360747E+10 | 0.541099E+09 |
August | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.396941E+10 | 0.717510E+09 |
September | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.413403E+10 | 0.108076E+10 |
October | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.358983E+10 | 0.161466E+10 |
November | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.221772E+10 | 0.189140E+10 |
December | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.174945E+10 | 0.277787E+10 |
Annual Sum or Average | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.366909E+11 | 0.193735E+11 |
Minimum of Months | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.174945E+10 | 0.541099E+09 |
Maximum of Months | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.413403E+10 | 0.283942E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.536940E+09 | 0.313428E+09 | 0.223512E+09 | 0.441003E+09 | 0.582873E+09 |
February | 0.553723E+09 | 0.267001E+09 | 0.286723E+09 | 0.450873E+09 | 0.511779E+09 |
March | 0.748269E+09 | 0.420448E+09 | 0.327821E+09 | 0.750267E+09 | 0.413495E+09 |
April | 0.599695E+09 | 0.239640E+09 | 0.360055E+09 | 0.635180E+09 | 0.305714E+09 |
May | 0.542279E+09 | 0.157501E+09 | 0.384778E+09 | 0.626960E+09 | 0.213647E+09 |
June | 0.509923E+09 | 0.108055E+09 | 0.401868E+09 | 0.634694E+09 | 0.144304E+09 |
July | 0.537900E+09 | 0.130512E+09 | 0.407388E+09 | 0.713518E+09 | 0.113421E+09 |
August | 0.603882E+09 | 0.195794E+09 | 0.408088E+09 | 0.791412E+09 | 0.149043E+09 |
September | 0.679485E+09 | 0.330960E+09 | 0.348525E+09 | 0.849841E+09 | 0.209869E+09 |
October | 0.671839E+09 | 0.383767E+09 | 0.288072E+09 | 0.737105E+09 | 0.317043E+09 |
November | 0.465636E+09 | 0.262867E+09 | 0.202769E+09 | 0.449814E+09 | 0.381139E+09 |
December | 0.448988E+09 | 0.232372E+09 | 0.216617E+09 | 0.349495E+09 | 0.570658E+09 |
Annual Sum or Average | 0.689856E+10 | 0.304234E+10 | 0.385622E+10 | 0.743016E+10 | 0.391298E+10 |
Minimum of Months | 0.448988E+09 | 0.108055E+09 | 0.202769E+09 | 0.349495E+09 | 0.113421E+09 |
Maximum of Months | 0.748269E+09 | 0.420448E+09 | 0.408088E+09 | 0.849841E+09 | 0.582873E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.43 | 1481.71 | 571.00 | 169.08 | 401.93 | 0.00 | 0.00 |
February | 565.58 | 1403.66 | 906.99 | 265.21 | 641.78 | 0.00 | 0.00 |
March | 1284.75 | 1045.88 | 1398.62 | 717.37 | 681.25 | 0.00 | 0.00 |
April | 1956.77 | 788.68 | 1874.38 | 1001.99 | 872.38 | 0.00 | 0.00 |
May | 2711.76 | 594.24 | 2386.31 | 1470.52 | 915.79 | 0.00 | 0.00 |
June | 3358.85 | 429.78 | 2763.91 | 1734.24 | 1029.68 | 0.00 | 0.00 |
July | 3241.03 | 321.39 | 2561.88 | 1556.07 | 1005.81 | 0.00 | 0.00 |
August | 2708.29 | 396.17 | 2173.76 | 1204.51 | 969.26 | 0.00 | 0.00 |
September | 1880.96 | 595.09 | 1627.87 | 888.85 | 739.02 | 0.00 | 0.00 |
October | 961.57 | 842.24 | 1011.65 | 438.38 | 573.28 | 0.00 | 0.00 |
November | 404.87 | 1007.25 | 584.21 | 181.95 | 402.27 | 0.00 | 0.00 |
December | 187.99 | 1431.15 | 504.12 | 108.30 | 395.82 | 0.00 | 0.00 |
Annual Sum or Average | 1630.34 | 858.69 | 1533.52 | 814.32 | 719.20 | 0.00 | 0.00 |
Minimum of Months | 187.99 | 321.39 | 504.12 | 108.30 | 395.82 | 0.00 | 0.00 |
Maximum of Months | 3358.85 | 1481.71 | 2763.91 | 1734.24 | 1029.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 824.38 | 1068.93 | 974.40 | 568.79 | 405.61 | 0.00 | 0.00 |
February | 935.18 | 1038.18 | 1112.52 | 536.45 | 576.07 | 0.00 | 0.00 |
March | 1382.19 | 784.71 | 1357.91 | 763.00 | 594.91 | 0.00 | 0.00 |
April | 1188.59 | 623.74 | 1124.56 | 449.38 | 675.18 | 0.00 | 0.00 |
May | 1120.98 | 438.05 | 984.09 | 285.82 | 698.27 | 0.00 | 0.00 |
June | 1203.58 | 297.44 | 956.22 | 202.63 | 753.59 | 0.00 | 0.00 |
July | 1351.66 | 213.76 | 976.15 | 236.84 | 739.30 | 0.00 | 0.00 |
August | 1487.06 | 280.20 | 1095.88 | 355.31 | 740.57 | 0.00 | 0.00 |
September | 1597.56 | 431.73 | 1274.18 | 620.62 | 653.56 | 0.00 | 0.00 |
October | 1332.26 | 632.80 | 1219.21 | 696.43 | 522.77 | 0.00 | 0.00 |
November | 848.19 | 761.83 | 873.17 | 492.93 | 380.24 | 0.00 | 0.00 |
December | 653.68 | 1047.59 | 814.79 | 421.69 | 393.10 | 0.00 | 0.00 |
Annual Sum or Average | 1161.76 | 632.76 | 1063.26 | 468.91 | 594.35 | 0.00 | 0.00 |
Minimum of Months | 653.68 | 213.76 | 814.79 | 202.63 | 380.24 | 0.00 | 0.00 |
Maximum of Months | 1597.56 | 1068.93 | 1357.91 | 763.00 | 753.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 822.72 | 1060.12 | 974.40 | 568.79 | 405.61 | 0.00 | 0.00 |
February | 933.94 | 1028.89 | 1112.52 | 536.45 | 576.07 | 0.00 | 0.00 |
March | 1389.94 | 759.82 | 1357.91 | 763.00 | 594.91 | 0.00 | 0.00 |
April | 1199.54 | 593.01 | 1124.56 | 449.38 | 675.18 | 0.00 | 0.00 |
May | 1125.53 | 416.21 | 984.09 | 285.82 | 698.27 | 0.00 | 0.00 |
June | 1201.16 | 283.45 | 956.22 | 202.63 | 753.59 | 0.00 | 0.00 |
July | 1346.88 | 202.02 | 976.15 | 236.84 | 739.30 | 0.00 | 0.00 |
August | 1482.01 | 267.89 | 1095.88 | 355.31 | 740.57 | 0.00 | 0.00 |
September | 1594.92 | 416.96 | 1274.18 | 620.62 | 653.56 | 0.00 | 0.00 |
October | 1340.29 | 602.84 | 1219.21 | 696.43 | 522.77 | 0.00 | 0.00 |
November | 855.60 | 729.71 | 873.17 | 492.93 | 380.24 | 0.00 | 0.00 |
December | 653.17 | 1037.14 | 814.79 | 421.69 | 393.10 | 0.00 | 0.00 |
Annual Sum or Average | 1163.46 | 614.33 | 1063.26 | 468.91 | 594.35 | 0.00 | 0.00 |
Minimum of Months | 653.17 | 202.02 | 814.79 | 202.63 | 380.24 | 0.00 | 0.00 |
Maximum of Months | 1594.92 | 1060.12 | 1357.91 | 763.00 | 753.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.65 | 217.62 | 200.47 | 117.02 | 83.45 | 0.00 | 0.00 |
February | 186.37 | 211.55 | 228.89 | 110.37 | 118.52 | 0.00 | 0.00 |
March | 280.12 | 154.38 | 279.37 | 156.98 | 122.39 | 0.00 | 0.00 |
April | 245.05 | 117.95 | 231.36 | 92.45 | 138.91 | 0.00 | 0.00 |
May | 234.08 | 79.77 | 202.46 | 58.80 | 143.66 | 0.00 | 0.00 |
June | 244.87 | 55.67 | 196.73 | 41.69 | 155.04 | 0.00 | 0.00 |
July | 266.40 | 42.35 | 200.83 | 48.73 | 152.10 | 0.00 | 0.00 |
August | 295.48 | 55.65 | 225.46 | 73.10 | 152.36 | 0.00 | 0.00 |
September | 327.87 | 80.97 | 262.15 | 127.69 | 134.46 | 0.00 | 0.00 |
October | 275.20 | 118.37 | 250.84 | 143.28 | 107.55 | 0.00 | 0.00 |
November | 173.54 | 147.04 | 179.64 | 101.41 | 78.23 | 0.00 | 0.00 |
December | 130.49 | 213.06 | 167.63 | 86.76 | 80.88 | 0.00 | 0.00 |
Annual Sum or Average | 235.61 | 124.08 | 218.75 | 96.47 | 122.28 | 0.00 | 0.00 |
Minimum of Months | 130.49 | 42.35 | 167.63 | 41.69 | 78.23 | 0.00 | 0.00 |
Maximum of Months | 327.87 | 217.62 | 279.37 | 156.98 | 155.04 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.625221E+09 | 0.396862E+10 | 0.152937E+10 | 0.452854E+09 | 0.107652E+10 | 0.00 | 0.00 |
February | 0.136824E+10 | 0.339572E+10 | 0.219418E+10 | 0.641585E+09 | 0.155260E+10 | 0.00 | 0.00 |
March | 0.344108E+10 | 0.280129E+10 | 0.374607E+10 | 0.192141E+10 | 0.182465E+10 | 0.00 | 0.00 |
April | 0.507194E+10 | 0.204427E+10 | 0.485839E+10 | 0.259717E+10 | 0.226122E+10 | 0.00 | 0.00 |
May | 0.726317E+10 | 0.159160E+10 | 0.639149E+10 | 0.393865E+10 | 0.245284E+10 | 0.00 | 0.00 |
June | 0.870613E+10 | 0.111399E+10 | 0.716406E+10 | 0.449514E+10 | 0.266892E+10 | 0.00 | 0.00 |
July | 0.868078E+10 | 0.860823E+09 | 0.686175E+10 | 0.416778E+10 | 0.269397E+10 | 0.00 | 0.00 |
August | 0.725388E+10 | 0.106109E+10 | 0.582221E+10 | 0.322615E+10 | 0.259605E+10 | 0.00 | 0.00 |
September | 0.487546E+10 | 0.154246E+10 | 0.421944E+10 | 0.230391E+10 | 0.191553E+10 | 0.00 | 0.00 |
October | 0.257546E+10 | 0.225585E+10 | 0.270962E+10 | 0.117415E+10 | 0.153547E+10 | 0.00 | 0.00 |
November | 0.104941E+10 | 0.261078E+10 | 0.151428E+10 | 0.471601E+09 | 0.104267E+10 | 0.00 | 0.00 |
December | 0.503516E+09 | 0.383318E+10 | 0.135023E+10 | 0.290060E+09 | 0.106017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514143E+11 | 0.270797E+11 | 0.483611E+11 | 0.256805E+11 | 0.226806E+11 | 0.00 | 0.00 |
Minimum of Months | 0.503516E+09 | 0.860823E+09 | 0.135023E+10 | 0.290060E+09 | 0.104267E+10 | 0.00 | 0.00 |
Maximum of Months | 0.870613E+10 | 0.396862E+10 | 0.716406E+10 | 0.449514E+10 | 0.269397E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220803E+10 | 0.286302E+10 | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.00 | 0.00 |
February | 0.226239E+10 | 0.251157E+10 | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.00 | 0.00 |
March | 0.370206E+10 | 0.210177E+10 | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.00 | 0.00 |
April | 0.308083E+10 | 0.161672E+10 | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.00 | 0.00 |
May | 0.300243E+10 | 0.117328E+10 | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.00 | 0.00 |
June | 0.311969E+10 | 0.770961E+09 | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.00 | 0.00 |
July | 0.362028E+10 | 0.572523E+09 | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.00 | 0.00 |
August | 0.398294E+10 | 0.750481E+09 | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.00 | 0.00 |
September | 0.414088E+10 | 0.111903E+10 | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.00 | 0.00 |
October | 0.356833E+10 | 0.169490E+10 | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.00 | 0.00 |
November | 0.219851E+10 | 0.197466E+10 | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.00 | 0.00 |
December | 0.175081E+10 | 0.280586E+10 | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.366372E+11 | 0.199548E+11 | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175081E+10 | 0.572523E+09 | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414088E+10 | 0.286302E+10 | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220357E+10 | 0.283942E+10 | 0.260983E+10 | 0.152344E+10 | 0.108640E+10 | 0.00 | 0.00 |
February | 0.225939E+10 | 0.248908E+10 | 0.269141E+10 | 0.129777E+10 | 0.139364E+10 | 0.00 | 0.00 |
March | 0.372281E+10 | 0.203510E+10 | 0.363701E+10 | 0.204361E+10 | 0.159340E+10 | 0.00 | 0.00 |
April | 0.310920E+10 | 0.153708E+10 | 0.291486E+10 | 0.116478E+10 | 0.175008E+10 | 0.00 | 0.00 |
May | 0.301463E+10 | 0.111476E+10 | 0.263579E+10 | 0.765542E+09 | 0.187025E+10 | 0.00 | 0.00 |
June | 0.311342E+10 | 0.734706E+09 | 0.247852E+10 | 0.525209E+09 | 0.195331E+10 | 0.00 | 0.00 |
July | 0.360747E+10 | 0.541099E+09 | 0.261451E+10 | 0.634363E+09 | 0.198014E+10 | 0.00 | 0.00 |
August | 0.396941E+10 | 0.717510E+09 | 0.293521E+10 | 0.951667E+09 | 0.198355E+10 | 0.00 | 0.00 |
September | 0.413403E+10 | 0.108076E+10 | 0.330269E+10 | 0.160865E+10 | 0.169404E+10 | 0.00 | 0.00 |
October | 0.358983E+10 | 0.161466E+10 | 0.326552E+10 | 0.186533E+10 | 0.140019E+10 | 0.00 | 0.00 |
November | 0.221772E+10 | 0.189140E+10 | 0.226326E+10 | 0.127768E+10 | 0.985573E+09 | 0.00 | 0.00 |
December | 0.174945E+10 | 0.277787E+10 | 0.218234E+10 | 0.112946E+10 | 0.105288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.366909E+11 | 0.193735E+11 | 0.335310E+11 | 0.147875E+11 | 0.187434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174945E+10 | 0.541099E+09 | 0.218234E+10 | 0.525209E+09 | 0.985573E+09 | 0.00 | 0.00 |
Maximum of Months | 0.413403E+10 | 0.283942E+10 | 0.363701E+10 | 0.204361E+10 | 0.198355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.441003E+09 | 0.582873E+09 | 0.536940E+09 | 0.313428E+09 | 0.223512E+09 | 0.00 | 0.00 |
February | 0.450873E+09 | 0.511779E+09 | 0.553723E+09 | 0.267001E+09 | 0.286723E+09 | 0.00 | 0.00 |
March | 0.750267E+09 | 0.413495E+09 | 0.748269E+09 | 0.420448E+09 | 0.327821E+09 | 0.00 | 0.00 |
April | 0.635180E+09 | 0.305714E+09 | 0.599695E+09 | 0.239640E+09 | 0.360055E+09 | 0.00 | 0.00 |
May | 0.626960E+09 | 0.213647E+09 | 0.542279E+09 | 0.157501E+09 | 0.384778E+09 | 0.00 | 0.00 |
June | 0.634694E+09 | 0.144304E+09 | 0.509923E+09 | 0.108055E+09 | 0.401868E+09 | 0.00 | 0.00 |
July | 0.713518E+09 | 0.113421E+09 | 0.537900E+09 | 0.130512E+09 | 0.407388E+09 | 0.00 | 0.00 |
August | 0.791412E+09 | 0.149043E+09 | 0.603882E+09 | 0.195794E+09 | 0.408088E+09 | 0.00 | 0.00 |
September | 0.849841E+09 | 0.209869E+09 | 0.679485E+09 | 0.330960E+09 | 0.348525E+09 | 0.00 | 0.00 |
October | 0.737105E+09 | 0.317043E+09 | 0.671839E+09 | 0.383767E+09 | 0.288072E+09 | 0.00 | 0.00 |
November | 0.449814E+09 | 0.381139E+09 | 0.465636E+09 | 0.262867E+09 | 0.202769E+09 | 0.00 | 0.00 |
December | 0.349495E+09 | 0.570658E+09 | 0.448988E+09 | 0.232372E+09 | 0.216617E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.743016E+10 | 0.391298E+10 | 0.689856E+10 | 0.304234E+10 | 0.385622E+10 | 0.00 | 0.00 |
Minimum of Months | 0.349495E+09 | 0.113421E+09 | 0.448988E+09 | 0.108055E+09 | 0.202769E+09 | 0.00 | 0.00 |
Maximum of Months | 0.849841E+09 | 0.582873E+09 | 0.748269E+09 | 0.420448E+09 | 0.408088E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288495E+10 | -0.244830E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436649527.0 | 58.99 | 0.00 | 0.00 |
February | 0.265624E+10 | -0.226169E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -394554723.3 | 58.99 | 0.00 | 0.00 |
March | 0.296012E+10 | -0.253115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -428970466.4 | 58.99 | 0.00 | 0.00 |
April | 0.272180E+10 | -0.231156E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -410233755.4 | 58.99 | 0.00 | 0.00 |
May | 0.265822E+10 | -0.225594E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -402282945.9 | 59.00 | 0.00 | 0.00 |
June | 0.245052E+10 | -0.207662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373896414.3 | 59.00 | 0.00 | 0.00 |
July | 0.236352E+10 | -0.198184E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -381684411.1 | 58.99 | 0.00 | 0.00 |
August | 0.238891E+10 | -0.200620E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382716300.5 | 58.99 | 0.00 | 0.00 |
September | 0.231936E+10 | -0.194287E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376487338.6 | 58.99 | 0.00 | 0.00 |
October | 0.249021E+10 | -0.207662E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -413586884.7 | 58.99 | 0.00 | 0.00 |
November | 0.254359E+10 | -0.213050E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -413089045.9 | 58.99 | 0.00 | 0.00 |
December | 0.278403E+10 | -0.234892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -435109155.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312215E+11 | -0.263722E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.484926E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.231936E+10 | -0.253115E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -436649527.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.296012E+10 | -0.194287E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -373896414.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.89 | 0.67 | 22-JAN-11:30 | 240.94 | 7.05 | 0.00 | 1.67 | 184.65 | 5.55 | 0.00 | 0.00 |
February | 262.50 | 0.80 | 0.50 | 10-FEB-12:09 | 767.93 | 8.74 | 0.00 | 52.17 | 257.01 | 7.21 | 0.00 | 3.00 |
March | 339.33 | 0.80 | 0.50 | 10-MAR-11:50 | 382.68 | 8.56 | 0.00 | 47.50 | 269.01 | 7.00 | 0.00 | 20.00 |
April | 371.17 | 0.75 | 0.50 | 01-APR-11:09 | 976.72 | 9.50 | 0.00 | 139.33 | 318.01 | 7.92 | 0.00 | 66.33 |
May | 332.17 | 0.74 | 0.50 | 01-MAY-10:39 | 2574.75 | 10.08 | 0.00 | 125.83 | 2704.09 | 8.35 | 0.00 | 83.67 |
June | 430.67 | 0.75 | 0.50 | 01-JUN-09:50 | 412.95 | 10.88 | 0.00 | 136.67 | 345.46 | 9.06 | 0.00 | 91.33 |
July | 439.00 | 0.75 | 0.50 | 01-JUL-10:20 | 500.33 | 10.71 | 0.00 | 143.83 | 468.63 | 8.98 | 0.00 | 89.17 |
August | 406.00 | 0.74 | 0.50 | 01-AUG-08:50 | 1900.12 | 10.30 | 0.00 | 155.83 | 1904.45 | 8.61 | 0.00 | 102.17 |
September | 289.17 | 0.77 | 0.50 | 01-SEP-09:50 | 376.36 | 8.85 | 0.00 | 73.33 | 313.32 | 7.28 | 0.00 | 44.83 |
October | 314.33 | 0.83 | 0.50 | 02-OCT-12:30 | 432.11 | 7.98 | 0.00 | 13.50 | 395.63 | 6.45 | 0.00 | 6.00 |
November | 258.33 | 0.85 | 0.50 | 01-NOV-11:09 | 666.31 | 6.93 | 0.00 | 29.83 | 669.45 | 5.49 | 0.00 | 28.17 |
December | 230.67 | 0.89 | 0.67 | 09-DEC-10:39 | 229.62 | 7.28 | 0.00 | 0.00 | 186.34 | 5.79 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.79 | 827.13 | 9.16 | 0.00 | 919.50 | 707.83 | 7.54 | 0.00 | 534.67 | ||
Minimum of Months | 230.67 | 0.74 | 0.50 | 229.62 | 6.93 | 0.00 | 0.00 | 184.65 | 5.49 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.89 | 0.67 | 2574.75 | 10.88 | 0.00 | 155.83 | 2704.09 | 9.06 | 0.00 | 102.17 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221541E+11 | 44581.65 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211107E+11 | 44581.65 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132229E+11 | 44581.65 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.494402E+10 | 44581.65 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186159E+09 | 29459.10 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3129475.10 | 1148.56 | 30-SEP-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173750E+10 | 44581.65 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.701889E+10 | 44581.65 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197868E+11 | 44581.65 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221541E+11 | 44581.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604904E+11 | 251819.01 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569887E+11 | 251819.01 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272350E+11 | 251819.01 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.597028E+10 | 251819.01 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33706825.83 | 15485.13 | 01-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169485E+10 | 59437.03 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116971E+11 | 251819.01 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.533923E+11 | 251819.01 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.604904E+11 | 251819.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.647465E+10 | 35814.59 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629801E+10 | 35814.59 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205384E+10 | 35814.59 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571662E+09 | 35814.59 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6256736.29 | 3088.28 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109128E+09 | 28734.66 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800098E+09 | 35814.59 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579433E+10 | 35814.59 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.647465E+10 | 35814.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968468E+10 | 30777.45 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.918091E+10 | 30777.45 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410611E+10 | 30777.45 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155558E+10 | 30777.45 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76085770.59 | 10032.56 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2548823.93 | 1218.08 | 30-SEP-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.464935E+09 | 30777.45 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240292E+10 | 30777.45 | 09-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.895820E+10 | 30777.45 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.968468E+10 | 30777.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214605E+11 | 42016.61 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200062E+11 | 45456.62 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144539E+11 | 36818.25 | 06-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.839459E+10 | 29154.69 | 16-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310743E+10 | 13441.36 | 11-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.701413E+09 | 11725.77 | 13-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4463255.26 | 1476.07 | 02-JUL-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156308E+09 | 6502.41 | 31-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106331E+10 | 11303.49 | 28-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.693069E+10 | 19411.42 | 08-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110648E+11 | 24611.41 | 23-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205918E+11 | 43075.77 | 10-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4463255.26 | 1476.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214605E+11 | 45456.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 40457359.20 | 38546520.23 | 2300.06 | 15-MAR-15:00 | 2198.32 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.250117E+09 | 0.230603E+09 | 4607.45 | 14-MAY-15:00 | 3835.82 | 0.00 |
June | 0.00 | 0.00 | 0.512972E+10 | 0.396919E+10 | 32968.82 | 18-JUN-08:62 | 17281.46 | 0.00 |
July | 0.00 | 0.00 | 0.122656E+11 | 0.881224E+10 | 33791.40 | 21-JUL-05:02 | 16057.77 | 0.00 |
August | 0.00 | 0.00 | 0.901279E+10 | 0.723972E+10 | 33071.24 | 14-AUG-06:02 | 15080.31 | 0.00 |
September | 0.00 | 0.00 | 0.238172E+10 | 0.173390E+10 | 32034.47 | 16-SEP-06:02 | 17233.01 | 0.00 |
October | 0.00 | 0.00 | 759.57 | 645.92 | 0.17 | 12-OCT-15:50 | 0.13 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.290804E+11 | 0.220242E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122656E+11 | 0.881224E+10 | 33791.40 | 17281.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.201017E+10 | 0.170942E+10 | 101153.32 | 16-MAR-06:03 | 71877.98 | 0.00 |
April | 0.00 | 0.00 | 0.152703E+09 | 0.140289E+09 | 15660.67 | 08-APR-13:30 | 14420.26 | 0.00 |
May | 0.00 | 0.00 | 0.866097E+10 | 0.785034E+10 | 166120.29 | 29-MAY-08:62 | 118342.22 | 0.00 |
June | 0.00 | 0.00 | 0.498646E+11 | 0.380554E+11 | 181784.90 | 18-JUN-08:62 | 96353.84 | 0.00 |
July | 0.00 | 0.00 | 0.928620E+11 | 0.650951E+11 | 184284.85 | 21-JUL-05:02 | 96825.57 | 0.00 |
August | 0.00 | 0.00 | 0.713888E+11 | 0.554431E+11 | 182100.82 | 14-AUG-06:02 | 85599.43 | 0.00 |
September | 0.00 | 0.00 | 0.279225E+11 | 0.204508E+11 | 176323.75 | 16-SEP-06:02 | 97983.05 | 0.00 |
October | 0.00 | 0.00 | 0.119647E+10 | 0.104925E+10 | 162170.78 | 01-OCT-08:62 | 101282.56 | 0.00 |
November | 0.00 | 0.00 | 613500.79 | 514134.38 | 467.48 | 05-NOV-15:40 | 370.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.254059E+12 | 0.189794E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.928620E+11 | 0.650951E+11 | 184284.85 | 118342.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.448051E+09 | 0.398018E+09 | 9833.12 | 15-MAR-13:40 | 9409.00 | 0.00 |
April | 0.00 | 0.00 | 64727444.06 | 62326749.50 | 4232.46 | 08-APR-13:30 | 4067.82 | 0.00 |
May | 0.00 | 0.00 | 0.136895E+10 | 0.127619E+10 | 23659.13 | 24-MAY-06:02 | 16698.64 | 0.00 |
June | 0.00 | 0.00 | 0.733307E+10 | 0.586241E+10 | 26199.44 | 18-JUN-08:62 | 13740.87 | 0.00 |
July | 0.00 | 0.00 | 0.140959E+11 | 0.104556E+11 | 26881.38 | 21-JUL-05:02 | 13149.97 | 0.00 |
August | 0.00 | 0.00 | 0.118970E+11 | 0.971655E+10 | 26267.19 | 14-AUG-06:02 | 11930.65 | 0.00 |
September | 0.00 | 0.00 | 0.568041E+10 | 0.445205E+10 | 25381.52 | 16-SEP-06:02 | 14069.27 | 0.00 |
October | 0.00 | 0.00 | 0.590329E+09 | 0.535008E+09 | 22380.16 | 12-OCT-06:02 | 16981.37 | 0.00 |
November | 0.00 | 0.00 | 350877.39 | 322341.25 | 189.58 | 16-NOV-12:40 | 174.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.414788E+11 | 0.327584E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140959E+11 | 0.104556E+11 | 26881.38 | 16981.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.264881E+09 | 0.231449E+09 | 7156.21 | 15-MAR-13:40 | 6706.45 | 0.00 |
April | 0.00 | 0.00 | 18196088.05 | 17057018.31 | 2338.17 | 08-APR-13:30 | 2195.68 | 0.00 |
May | 0.00 | 0.00 | 0.765526E+09 | 0.706159E+09 | 16211.39 | 24-MAY-06:02 | 11172.57 | 0.00 |
June | 0.00 | 0.00 | 0.509475E+10 | 0.396666E+10 | 22393.19 | 18-JUN-08:62 | 11584.12 | 0.00 |
July | 0.00 | 0.00 | 0.106094E+11 | 0.766743E+10 | 22960.54 | 21-JUL-05:02 | 10873.12 | 0.00 |
August | 0.00 | 0.00 | 0.887869E+10 | 0.714512E+10 | 22458.57 | 14-AUG-06:02 | 10074.03 | 0.00 |
September | 0.00 | 0.00 | 0.388449E+10 | 0.300019E+10 | 21722.09 | 16-SEP-06:02 | 11768.96 | 0.00 |
October | 0.00 | 0.00 | 0.313840E+09 | 0.283490E+09 | 13359.35 | 12-OCT-06:02 | 9911.27 | 0.00 |
November | 0.00 | 0.00 | 83.62 | 75.85 | 0.10 | 05-NOV-11:00 | 0.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.298298E+11 | 0.230176E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106094E+11 | 0.766743E+10 | 22960.54 | 11768.96 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.500195E+09 | 0.06 | 238.68 | 01-JAN-00:10 | 0.08 |
February | 0.467763E+09 | 0.06 | 238.68 | 01-FEB-00:10 | 0.08 |
March | 0.393617E+09 | 0.05 | 238.68 | 01-MAR-05:01 | 0.08 |
April | 0.359454E+09 | 0.05 | 238.68 | 01-APR-04:10 | 0.08 |
May | 0.250149E+09 | 0.03 | 238.68 | 01-MAY-05:05 | 0.08 |
June | 92629151.41 | 0.01 | 238.68 | 01-JUN-07:06 | 0.08 |
July | 3451504.49 | 0.00 | 238.68 | 02-JUL-11:05 | 0.08 |
August | 27705348.98 | 0.00 | 238.68 | 01-AUG-07:07 | 0.08 |
September | 0.136051E+09 | 0.02 | 238.68 | 01-SEP-07:10 | 0.08 |
October | 0.308910E+09 | 0.04 | 238.68 | 01-OCT-07:06 | 0.08 |
November | 0.366192E+09 | 0.05 | 238.68 | 01-NOV-07:10 | 0.08 |
December | 0.482781E+09 | 0.06 | 238.68 | 01-DEC-05:10 | 0.08 |
Annual Sum or Average | 0.338890E+10 | 0.04 | |||
Minimum of Months | 3451504.49 | 0.00 | 238.68 | 0.08 | |
Maximum of Months | 0.500195E+09 | 0.06 | 238.68 | 0.08 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.266124E+10 | 0.57 | 1637.89 | 02-JAN-07:20 | 0.90 |
February | 0.243278E+10 | 0.60 | 1637.89 | 01-FEB-06:06 | 0.90 |
March | 0.268631E+10 | 0.56 | 1637.89 | 01-MAR-11:00 | 0.90 |
April | 0.256643E+10 | 0.55 | 1637.89 | 01-APR-06:10 | 0.90 |
May | 0.264749E+10 | 0.54 | 1637.89 | 02-MAY-05:15 | 0.90 |
June | 0.258263E+10 | 0.54 | 1637.89 | 01-JUN-10:00 | 0.89 |
July | 0.262980E+10 | 0.53 | 1637.89 | 02-JUL-16:20 | 0.89 |
August | 0.267108E+10 | 0.54 | 1637.89 | 02-AUG-07:00 | 0.89 |
September | 0.256494E+10 | 0.54 | 1637.89 | 07-SEP-19:00 | 0.90 |
October | 0.262391E+10 | 0.54 | 1637.89 | 11-OCT-07:00 | 0.90 |
November | 0.253041E+10 | 0.54 | 1637.89 | 01-NOV-08:50 | 0.90 |
December | 0.266099E+10 | 0.57 | 1637.89 | 01-DEC-14:30 | 0.90 |
Annual Sum or Average | 0.312580E+11 | 0.55 | |||
Minimum of Months | 0.243278E+10 | 0.53 | 1637.89 | 0.89 | |
Maximum of Months | 0.268631E+10 | 0.60 | 1637.89 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.227582E+11 | 0.93 | 14203.58 | 01-JAN-08:30 | 1.55 |
February | 0.206680E+11 | 0.94 | 14203.58 | 01-FEB-18:00 | 1.54 |
March | 0.231632E+11 | 0.94 | 14203.58 | 01-MAR-12:00 | 1.55 |
April | 0.222428E+11 | 0.93 | 14203.58 | 04-APR-11:50 | 1.54 |
May | 0.229587E+11 | 0.93 | 14203.58 | 10-MAY-09:40 | 1.53 |
June | 0.223962E+11 | 0.93 | 14203.58 | 02-JUN-11:02 | 1.53 |
July | 0.228053E+11 | 0.91 | 14203.58 | 01-JUL-12:20 | 1.53 |
August | 0.231632E+11 | 0.93 | 14203.58 | 01-AUG-12:40 | 1.53 |
September | 0.222428E+11 | 0.93 | 14203.58 | 02-SEP-16:30 | 1.54 |
October | 0.227541E+11 | 0.92 | 14203.58 | 11-OCT-10:50 | 1.54 |
November | 0.219360E+11 | 0.92 | 14203.58 | 02-NOV-09:40 | 1.54 |
December | 0.228107E+11 | 0.93 | 14203.58 | 01-DEC-20:00 | 1.54 |
Annual Sum or Average | 0.269899E+12 | 0.93 | |||
Minimum of Months | 0.206680E+11 | 0.91 | 14203.58 | 1.53 | |
Maximum of Months | 0.231632E+11 | 0.94 | 14203.58 | 1.55 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222124E+10 | 0.59 | 1378.22 | 01-JAN-08:06 | 0.93 |
February | 0.202441E+10 | 0.61 | 1378.22 | 01-FEB-06:10 | 0.93 |
March | 0.224990E+10 | 0.57 | 1378.22 | 01-MAR-06:30 | 0.93 |
April | 0.215864E+10 | 0.56 | 1378.22 | 01-APR-06:15 | 0.93 |
May | 0.222776E+10 | 0.56 | 1378.22 | 01-MAY-06:10 | 0.93 |
June | 0.217318E+10 | 0.56 | 1378.22 | 01-JUN-07:04 | 0.92 |
July | 0.221288E+10 | 0.55 | 1378.22 | 01-JUL-07:07 | 0.92 |
August | 0.224761E+10 | 0.56 | 1378.22 | 01-AUG-07:13 | 0.92 |
September | 0.215830E+10 | 0.56 | 1378.22 | 01-SEP-11:40 | 0.92 |
October | 0.220791E+10 | 0.55 | 1378.22 | 01-OCT-08:30 | 0.92 |
November | 0.212876E+10 | 0.55 | 1378.22 | 03-NOV-05:02 | 0.93 |
December | 0.222345E+10 | 0.58 | 1378.22 | 01-DEC-07:10 | 0.93 |
Annual Sum or Average | 0.262340E+11 | 0.57 | |||
Minimum of Months | 0.202441E+10 | 0.55 | 1378.22 | 0.92 | |
Maximum of Months | 0.224990E+10 | 0.61 | 1378.22 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182891E+10 | 0.60 | 1130.20 | 03-JAN-06:40 | 0.93 |
February | 0.166999E+10 | 0.62 | 1130.20 | 11-FEB-14:00 | 0.93 |
March | 0.184736E+10 | 0.58 | 1130.20 | 01-MAR-10:30 | 0.93 |
April | 0.177069E+10 | 0.56 | 1130.20 | 02-APR-10:30 | 0.93 |
May | 0.182685E+10 | 0.56 | 1130.20 | 01-MAY-07:20 | 0.93 |
June | 0.178209E+10 | 0.56 | 1130.20 | 21-JUN-07:13 | 0.92 |
July | 0.181464E+10 | 0.55 | 1130.20 | 05-JUL-08:00 | 0.92 |
August | 0.184312E+10 | 0.56 | 1130.20 | 02-AUG-08:70 | 0.92 |
September | 0.176989E+10 | 0.56 | 1130.20 | 02-SEP-19:10 | 0.93 |
October | 0.181057E+10 | 0.55 | 1130.20 | 03-OCT-06:50 | 0.93 |
November | 0.174588E+10 | 0.56 | 1130.20 | 02-NOV-06:13 | 0.93 |
December | 0.183043E+10 | 0.60 | 1130.20 | 01-DEC-08:20 | 0.93 |
Annual Sum or Average | 0.215404E+11 | 0.57 | |||
Minimum of Months | 0.166999E+10 | 0.55 | 1130.20 | 0.92 | |
Maximum of Months | 0.184736E+10 | 0.62 | 1130.20 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.266124E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.243278E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.269827E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.256643E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.271888E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.397340E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.589757E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.511824E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.320718E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.262391E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.253041E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.266099E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390893E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.243278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.589757E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.227582E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.206680E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.237855E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.222901E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.255493E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.369709E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.495529E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.441529E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.303834E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.231147E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.219362E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.228107E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.343973E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206680E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.495529E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.222124E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202441E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.237047E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.217627E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.259281E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.408840E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.583769E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.533514E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.361276E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.236426E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.212886E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.222345E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.369758E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.202441E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.583769E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182891E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166999E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192018E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177570E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203423E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312765E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.457263E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.417179E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.277544E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189423E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174588E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183043E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.293471E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166999E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.457263E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.266124E+10 | 0.00 | 0.221541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243278E+10 | 0.00 | 0.211107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268631E+10 | 40457359.20 | 0.132229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256643E+10 | 0.00 | 0.494402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264749E+10 | 0.250117E+09 | 0.186159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.258263E+10 | 0.512972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262980E+10 | 0.122656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267108E+10 | 0.901279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256494E+10 | 0.238172E+10 | 3129475.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262391E+10 | 759.57 | 0.173750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253041E+10 | 0.00 | 0.701889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266099E+10 | 0.00 | 0.197868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312580E+11 | 0.290804E+11 | 0.901641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.243278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.268631E+10 | 0.122656E+11 | 0.221541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.227582E+11 | 0.00 | 0.604904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206680E+11 | 0.00 | 0.569887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231632E+11 | 0.201017E+10 | 0.272350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222428E+11 | 0.152703E+09 | 0.597028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229587E+11 | 0.866097E+10 | 33706825.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.223962E+11 | 0.498646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.228053E+11 | 0.928620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.231632E+11 | 0.713888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.222428E+11 | 0.279225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227541E+11 | 0.119647E+10 | 0.169485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219360E+11 | 613500.79 | 0.116971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228107E+11 | 0.00 | 0.533923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269899E+12 | 0.254059E+12 | 0.217502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.231632E+11 | 0.928620E+11 | 0.604904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.222124E+10 | 0.00 | 0.647465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202441E+10 | 0.00 | 0.629801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224990E+10 | 0.448051E+09 | 0.205384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215864E+10 | 64727444.06 | 0.571662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222776E+10 | 0.136895E+10 | 6256736.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217318E+10 | 0.733307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221288E+10 | 0.140959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224761E+10 | 0.118970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215830E+10 | 0.568041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220791E+10 | 0.590329E+09 | 0.109128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212876E+10 | 350877.39 | 0.800098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222345E+10 | 0.00 | 0.579433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262340E+11 | 0.414788E+11 | 0.221080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224990E+10 | 0.140959E+11 | 0.647465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182891E+10 | 0.00 | 0.968468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166999E+10 | 0.00 | 0.918091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184736E+10 | 0.264881E+09 | 0.410611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177069E+10 | 18196088.05 | 0.155558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182685E+10 | 0.765526E+09 | 76085770.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178209E+10 | 0.509475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181464E+10 | 0.106094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184312E+10 | 0.887869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176989E+10 | 0.388449E+10 | 2548823.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181057E+10 | 0.313840E+09 | 0.464935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174588E+10 | 83.62 | 0.240292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183043E+10 | 0.00 | 0.895820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215404E+11 | 0.298298E+11 | 0.364320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184736E+10 | 0.106094E+11 | 0.968468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.266124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268631E+10 | 0.00 | 0.00 | 0.00 | 11960743.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.256643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264749E+10 | 0.00 | 0.00 | 0.00 | 71384409.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.258263E+10 | 0.00 | 0.00 | 0.00 | 0.139076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262980E+10 | 0.00 | 0.00 | 0.00 | 0.326777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267108E+10 | 0.00 | 0.00 | 0.00 | 0.244716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256494E+10 | 0.00 | 0.00 | 0.00 | 0.642242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262391E+10 | 0.00 | 0.00 | 0.00 | 215.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312580E+11 | 0.00 | 0.00 | 0.00 | 0.783128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.243278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.268631E+10 | 0.00 | 0.00 | 0.00 | 0.326777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.227582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231632E+11 | 0.00 | 0.00 | 0.00 | 0.622267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222428E+11 | 0.00 | 0.00 | 0.00 | 47304213.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229587E+11 | 0.00 | 0.00 | 0.00 | 0.259063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.223962E+11 | 0.00 | 0.00 | 0.00 | 0.145747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.228053E+11 | 0.00 | 0.00 | 0.00 | 0.267476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.231632E+11 | 0.00 | 0.00 | 0.00 | 0.209897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.222428E+11 | 0.00 | 0.00 | 0.00 | 0.814060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227541E+11 | 0.00 | 0.00 | 0.00 | 0.360569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219360E+11 | 0.00 | 0.00 | 0.00 | 194462.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269899E+12 | 0.00 | 0.00 | 0.00 | 0.740737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.231632E+11 | 0.00 | 0.00 | 0.00 | 0.267476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.222124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224990E+10 | 0.00 | 0.00 | 0.00 | 0.120572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215864E+10 | 0.00 | 0.00 | 0.00 | 17635580.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222776E+10 | 0.00 | 0.00 | 0.00 | 0.365048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217318E+10 | 0.00 | 0.00 | 0.00 | 0.191522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.221288E+10 | 0.00 | 0.00 | 0.00 | 0.362481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.224761E+10 | 0.00 | 0.00 | 0.00 | 0.308753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215830E+10 | 0.00 | 0.00 | 0.00 | 0.145447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220791E+10 | 0.00 | 0.00 | 0.00 | 0.156349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212876E+10 | 0.00 | 0.00 | 0.00 | 99174.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262340E+11 | 0.00 | 0.00 | 0.00 | 0.107417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224990E+10 | 0.00 | 0.00 | 0.00 | 0.362481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.182891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184736E+10 | 0.00 | 0.00 | 0.00 | 72824445.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177069E+10 | 0.00 | 0.00 | 0.00 | 5014363.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182685E+10 | 0.00 | 0.00 | 0.00 | 0.207380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.178209E+10 | 0.00 | 0.00 | 0.00 | 0.134556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181464E+10 | 0.00 | 0.00 | 0.00 | 0.275798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184312E+10 | 0.00 | 0.00 | 0.00 | 0.232867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176989E+10 | 0.00 | 0.00 | 0.00 | 0.100555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181057E+10 | 0.00 | 0.00 | 0.00 | 83652091.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174588E+10 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215404E+11 | 0.00 | 0.00 | 0.00 | 0.780663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184736E+10 | 0.00 | 0.00 | 0.00 | 0.275798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2199733.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997553E+10 | 0.00 | 0.00 | 0.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929149E+10 | 0.00 | 0.00 | 0.20 |
March | 0.448893E+09 | 3115668.92 | 143460.74 | 338.71 | 9639832.44 | 0.699705E+10 | 3262006.53 | 1510.76 | 0.21 |
April | 0.166723E+10 | 0.00 | 0.00 | 0.00 | 123356.58 | 0.340680E+10 | 0.00 | 0.00 | 0.21 |
May | 0.263509E+10 | 26170444.32 | 0.00 | 824167.67 | 10566980.14 | 0.177594E+09 | 0.102548E+10 | 0.00 | 0.29 |
June | 0.434094E+09 | 0.935640E+09 | 0.00 | 5779447.86 | 2825390.90 | 0.00 | 0.322502E+10 | 0.00 | 0.53 |
July | 27084445.94 | 0.251748E+10 | 0.00 | 5482103.49 | 12059144.54 | 0.00 | 0.124377E+10 | 0.00 | 0.55 |
August | 88604446.95 | 0.144050E+10 | 0.00 | 8332943.95 | 1274829.05 | 0.00 | 0.258166E+10 | 0.00 | 0.56 |
September | 0.957946E+09 | 0.307072E+09 | 0.00 | 4916763.91 | 301474.26 | 0.00 | 0.325045E+10 | 0.00 | 0.52 |
October | 0.331569E+10 | 0.00 | 0.00 | 109631.18 | 371171.70 | 0.125972E+10 | 0.202330E+09 | 0.00 | 0.21 |
November | 0.647348E+09 | 0.00 | 23235.93 | 0.00 | 181006.50 | 0.512263E+10 | 0.00 | 48497.86 | 0.20 |
December | 7060067.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952540E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.102312E+11 | 0.522999E+10 | 166696.67 | 25445396.77 | 37343186.12 | 0.457562E+11 | 0.115320E+11 | 50008.62 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.331569E+10 | 0.251748E+10 | 143460.74 | 8332943.95 | 12059144.54 | 0.997553E+10 | 0.325045E+10 | 48497.86 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.497369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371630E+11 | 0.00 | 0.00 | 0.39 |
February | 0.455584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351220E+11 | 0.00 | 0.00 | 0.39 |
March | 0.536719E+11 | 779843.65 | 0.00 | 3338516.13 | 0.00 | 0.111726E+11 | 0.310196E+10 | 0.00 | 0.42 |
April | 0.397863E+11 | 0.00 | 0.00 | 7875670.96 | 0.00 | 0.217789E+10 | 0.121951E+11 | 0.00 | 0.45 |
May | 0.811076E+10 | 0.167197E+09 | 0.00 | 49050738.06 | 5591839.19 | 0.00 | 0.443640E+11 | 0.00 | 0.72 |
June | 0.147409E+10 | 0.661157E+10 | 0.00 | 62299866.18 | 46722050.43 | 0.00 | 0.310426E+11 | 0.00 | 0.87 |
July | 0.630252E+09 | 0.179331E+11 | 0.00 | 35175408.84 | 0.163583E+09 | 0.00 | 0.762009E+10 | 0.00 | 0.78 |
August | 0.104008E+10 | 0.928406E+10 | 0.00 | 62278767.64 | 36060332.19 | 0.00 | 0.182573E+11 | 0.00 | 0.82 |
September | 0.279442E+10 | 0.212355E+10 | 0.00 | 62793680.36 | 12023057.92 | 0.00 | 0.376743E+11 | 0.00 | 0.89 |
October | 0.331156E+11 | 0.00 | 0.00 | 17278192.25 | 0.00 | 0.466096E+09 | 0.201092E+11 | 0.00 | 0.51 |
November | 0.488347E+11 | 0.00 | 0.00 | 872440.74 | 0.00 | 0.411351E+10 | 0.213924E+10 | 0.00 | 0.40 |
December | 0.529769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301765E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.337730E+12 | 0.361203E+11 | 0.00 | 0.300963E+09 | 0.263980E+09 | 0.120392E+12 | 0.176504E+12 | 0.00 | 0.59 |
Minimum of Months | 0.630252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.536719E+11 | 0.179331E+11 | 0.00 | 62793680.36 | 0.163583E+09 | 0.371630E+11 | 0.443640E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347046E+10 | 0.00 | 0.00 | 0.39 |
February | 0.414954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341643E+10 | 0.00 | 0.00 | 0.39 |
March | 0.450268E+10 | 3385245.73 | 0.00 | 1512037.89 | 0.00 | 0.956620E+09 | 0.134012E+10 | 0.00 | 0.47 |
April | 0.231936E+10 | 0.00 | 0.00 | 3863674.24 | 0.00 | 0.386744E+09 | 0.376489E+10 | 0.00 | 0.63 |
May | 0.549304E+09 | 23847997.43 | 0.00 | 9052807.57 | 0.00 | 1138412.73 | 0.644975E+10 | 0.00 | 1.13 |
June | 0.106131E+09 | 0.804056E+09 | 0.00 | 9818728.35 | 220257.53 | 0.00 | 0.435438E+10 | 0.00 | 1.34 |
July | 38611780.06 | 0.229162E+10 | 0.00 | 5538735.75 | 2162180.65 | 0.00 | 0.119460E+10 | 0.00 | 1.17 |
August | 62476386.22 | 0.124461E+10 | 0.00 | 11022016.19 | 205636.61 | 0.00 | 0.267447E+10 | 0.00 | 1.26 |
September | 0.148063E+09 | 0.419808E+09 | 0.00 | 13159027.18 | 9555.26 | 0.00 | 0.571744E+10 | 0.00 | 1.49 |
October | 0.144133E+10 | 0.00 | 0.00 | 7634800.30 | 0.00 | 56251117.71 | 0.579893E+10 | 0.00 | 0.82 |
November | 0.355922E+10 | 0.00 | 0.00 | 1793455.82 | 0.00 | 0.408377E+09 | 0.198586E+10 | 0.00 | 0.49 |
December | 0.467485E+10 | 0.00 | 0.00 | 46922.50 | 0.00 | 0.305297E+10 | 67252774.83 | 0.00 | 0.39 |
Annual Sum or Average | 0.261965E+11 | 0.478732E+10 | 0.00 | 63442205.79 | 2597630.05 | 0.117490E+11 | 0.333477E+11 | 0.00 | 0.83 |
Minimum of Months | 38611780.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.467485E+10 | 0.229162E+10 | 0.00 | 13159027.18 | 2162180.65 | 0.347046E+10 | 0.644975E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680269E+10 | 0.00 | 0.00 | 0.39 |
February | 0.140449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613880E+10 | 0.00 | 0.00 | 0.39 |
March | 0.368426E+10 | 1594814.21 | 0.00 | 375195.15 | 0.00 | 0.240150E+10 | 0.250050E+09 | 0.00 | 0.43 |
April | 0.302705E+10 | 0.00 | 0.00 | 1169981.94 | 0.00 | 0.862167E+09 | 0.125890E+10 | 0.00 | 0.48 |
May | 0.119995E+10 | 18107150.01 | 0.00 | 4146164.05 | 15949.54 | 51744863.54 | 0.351501E+10 | 0.00 | 0.76 |
June | 0.276319E+09 | 0.673288E+09 | 0.00 | 5944455.66 | 1269584.98 | 0.00 | 0.307400E+10 | 0.00 | 1.02 |
July | 42407396.40 | 0.186896E+10 | 0.00 | 3974981.49 | 3415847.59 | 0.00 | 0.944462E+09 | 0.00 | 0.96 |
August | 73776682.94 | 0.104263E+10 | 0.00 | 7548991.61 | 374703.23 | 0.00 | 0.204941E+10 | 0.00 | 1.01 |
September | 0.441924E+09 | 0.286798E+09 | 0.00 | 8427985.77 | 54015.05 | 0.00 | 0.396705E+10 | 0.00 | 1.13 |
October | 0.263248E+10 | 0.00 | 0.00 | 3101450.88 | 0.00 | 0.299755E+09 | 0.248508E+10 | 0.00 | 0.60 |
November | 0.317162E+10 | 0.00 | 0.00 | 339929.72 | 0.00 | 0.152282E+10 | 0.473962E+09 | 0.00 | 0.41 |
December | 0.111318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665381E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.183761E+11 | 0.389138E+10 | 0.00 | 35029136.27 | 5130100.39 | 0.247333E+11 | 0.180179E+11 | 0.00 | 0.67 |
Minimum of Months | 42407396.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.368426E+10 | 0.186896E+10 | 0.00 | 8427985.77 | 3415847.59 | 0.680269E+10 | 0.396705E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.120612E+12 | 0.326697E+11 | 0.00 | 0.113104E+12 | 0.300661E+11 |
February | 0.213018E+12 | 0.317656E+11 | 0.00 | 0.105081E+12 | 0.283961E+11 |
March | 0.352912E+12 | 0.223150E+11 | 0.00 | 0.885175E+11 | 0.188591E+11 |
April | 0.449089E+12 | 0.151525E+11 | 0.00 | 0.708653E+11 | 0.566461E+10 |
May | 0.577882E+12 | 0.764277E+10 | 0.00 | 0.678914E+11 | 0.151324E+11 |
June | 0.633158E+12 | 0.334603E+10 | 0.00 | 0.349949E+11 | 0.868238E+11 |
July | 0.590383E+12 | 0.508283E+09 | 0.00 | -0.130010E+11 | 0.166232E+12 |
August | 0.498169E+12 | 0.174388E+10 | 0.00 | 0.138673E+11 | 0.130069E+12 |
September | 0.366907E+12 | 0.442878E+10 | 0.00 | 0.518913E+11 | 0.513792E+11 |
October | 0.226161E+12 | 0.129594E+11 | 0.00 | 0.712102E+11 | 0.543548E+10 |
November | 0.104859E+12 | 0.183410E+11 | 0.00 | 0.719820E+11 | 0.824722E+10 |
December | 0.104672E+12 | 0.322883E+11 | 0.00 | 0.108248E+12 | 0.271308E+11 |
Annual Sum or Average | 0.423782E+13 | 0.183161E+12 | 0.00 | 0.784652E+12 | 0.573437E+12 |
Minimum of Months | 0.104672E+12 | 0.508283E+09 | 0.00 | -0.130010E+11 | 0.543548E+10 |
Maximum of Months | 0.633158E+12 | 0.326697E+11 | 0.00 | 0.113104E+12 | 0.166232E+12 |