Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:29:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2547.51 | 1110.51 | 1110.51 |
Net Site Energy | 2547.51 | 1110.51 | 1110.51 |
Total Source Energy | 7894.25 | 3441.27 | 3441.27 |
Net Source Energy | 7894.25 | 3441.27 | 3441.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 476.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 439.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2464.11 | 83.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 476.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 439.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 476.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 125.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 439.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 83.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 262.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 726.59 | 36.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1074.16 | 36.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 262.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 726.59 | 36.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1074.16 | 36.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2464.113 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2464.113 | 100.00 |
Total On-Site and Utility Electric Sources | 2464.113 | 100.00 |
Total Electricity End Uses | 2464.113 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4911.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | FRONT_ENTRY UNIT HEATER HEATING COIL | PSZ-AC:1 COOLING COIL | PSZ-AC:2 COOLING COIL | PSZ-AC:3 COOLING COIL | PSZ-AC:4 COOLING COIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATER FAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.95 | 0.00 | 0.00 | 83.95 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 14.22 |
Skylight-Roof Ratio [%] | 0.62 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 9.3031 | 46.45 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 17.6219 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 17.6219 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.06 | 38.06 | 17.6219 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 10.3529 | 6.19 | 0.0000 |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 16.2063 | 7.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.95 | 83.95 | 16.2063 | 7.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BACK_SPACE | 379.89 | Yes | Yes | 1.00 | BACK_SPACE | GENERAL | BACK_SPACE | 9.3031 | 46.45 | 8.0700 | |
CORE_RETAIL | 1600.48 | Yes | Yes | 1.00 | CORE_RETAIL | GENERAL | CORE_RETAIL | 17.6219 | 6.19 | 3.2300 | |
POINT_OF_SALE | 150.81 | Yes | Yes | 1.00 | POINT_OF_SALE | GENERAL | POINT_OF_SALE | 17.6219 | 6.19 | 21.5200 | |
FRONT_RETAIL | 150.81 | Yes | Yes | 1.00 | FRONT_RETAIL | GENERAL | FRONT_RETAIL | 17.6219 | 6.19 | 3.2300 | |
FRONT_ENTRY | 12.00 | Yes | Yes | 1.00 | FRONT_ENTRY | GENERAL | FRONT_ENTRY | 10.3529 | 6.19 | 0.0000 | |
Total | 2293.99 | 16.2063 | 3.62 | 5.2170 | |||||||
Conditioned Total | 2293.99 | 16.2063 | 3.62 | 5.2170 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2293.99 | 2293.99 | 0.00 | 0.00 | 16.2063 | 7.23 | 5.2170 |
Total | 2293.99 | 2293.99 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-14:00 | 06-JAN-12:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99113.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33459.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4791.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 165949.88 | 4791.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 99113.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33459.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 22605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4791.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3885.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1508.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 398.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1392.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7803.85 | 90.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1693.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 173.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 607.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3401.86 | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1693.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 657.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 173.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 607.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3401.86 | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.45 |
CORE_RETAIL DIRECT AIR | 9.16 |
POINT_OF_SALE DIRECT AIR | 1.40 |
FRONT_RETAIL DIRECT AIR | 1.23 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.102066 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER FAN | 0.102066 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | 2364.97 |
PSZ-AC:1 HEATING COIL | 56785.02 |
PSZ-AC:2 HEATING COIL | 212180.06 |
PSZ-AC:3 HEATING COIL | 32287.77 |
PSZ-AC:4 HEATING COIL | 28332.85 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.45 | 2.45 | 2.45 | 2.45 | 2.45 | 2.45 | 1.00 | 1.00 | 2.45 |
PSZ-AC:2 | 9.16 | 9.16 | 9.16 | 9.16 | 9.16 | 9.16 | 1.00 | 1.00 | 9.16 |
PSZ-AC:3 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.40 | 1.00 | 1.00 | 1.40 |
PSZ-AC:4 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.45 | 0.289476 |
PSZ-AC:2_OA_CONTROLLER | 9.16 | 2.44 |
PSZ-AC:3_OA_CONTROLLER | 1.40 | 0.229834 |
PSZ-AC:4_OA_CONTROLLER | 1.23 | 0.229834 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.45 | 2676.36 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 9.16 | 16931.87 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.40 | 1597.33 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1399.96 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.45 | 2.45 | 2.45 | 2.45 | 51709.57 | 56785.02 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 9.16 | 9.16 | 9.16 | 9.16 | 227391.62 | 212180.06 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.40 | 1.40 | 1.40 | 1.40 | 32174.87 | 32287.77 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 29291.54 | 28332.85 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC:1 COOLING COIL | 2.45 | 1.22 | 2.45 | 51709.57 | 25494.04 | 51709.57 | 0.754800 | 0.754800 |
PSZ-AC:2 COOLING COIL | 9.16 | 4.58 | 9.16 | 227391.62 | 113695.80 | 227391.62 | 0.701080 | 0.701080 |
PSZ-AC:3 COOLING COIL | 1.40 | 0.700516 | 1.40 | 32174.87 | 15913.43 | 32174.87 | 0.726010 | 0.726010 |
PSZ-AC:4 COOLING COIL | 1.23 | 0.613957 | 1.23 | 29291.54 | 14495.09 | 29291.54 | 0.714130 | 0.714130 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.74 | 38.06 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 8.2 | 46.452 | 2.153E-002 | 9.303 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.373 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 17.622 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.852 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 17.622 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.142 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 17.622 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.852 | No |
5 | FRONT_ENTRY | 12.00 | 1.9 | 6.192 | 0.162 | 10.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.353 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 8.2 | 8.2 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.9 | 0.162 | 6.192 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | LTG_SCH_BACK | BACK_SPACE | 379.89 | 8.2 | 3534.151 | 9.303 | 432.147 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3534.151 |
2 | CORE_RETAIL_LIGHTS | LTG_SCH_CORE | CORE_RETAIL | 1600.48 | 258.4 | 28203.614 | 17.622 | 109.133 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28203.614 |
3 | POINT_OF_SALE_LIGHTS | LTG_SCH_SALE | POINT_OF_SALE | 150.81 | 24.4 | 2657.565 | 17.622 | 109.133 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2657.565 |
4 | FRONT_RETAIL_LIGHTS | LTG_SCH_FRONT | FRONT_RETAIL | 150.81 | 24.4 | 2657.565 | 17.622 | 109.133 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2657.565 |
5 | FRONT_ENTRY_LIGHTS | LTG_SCH_ENTRY | FRONT_ENTRY | 12.00 | 1.9 | 124.235 | 10.353 | 64.105 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 124.235 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 8.2 | 3065.712 | 8.070 | 374.868 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.2_SHGC_0.25 | 36 | 1 | VerySmooth | 6.813 | 5.832 | 1.168 | 0.251 | ||
2 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | 37 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41417 | 0.41417 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.39147 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.20656 | 0.20656 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2286.46 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 5.733 | 0.325 | 0.251 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 8.2 | 0.427 | 1.123E-003 | 5.097E-004 | 0.663 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.366 | 2.286E-004 | 1.858E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.195 | 1.290E-003 | 5.713E-004 | 0.761 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.195 | 1.290E-003 | 5.713E-004 | 0.761 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 1.9 | 2.500E-002 | 2.083E-003 | 6.871E-004 | 1.229 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 1.9 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 27755.89723 | 33307.07667 | 2.03772 | 2.44527 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 379.89000 | 8.17812 | 0.28948 | 0.00000 |
2 | BACK_SPACE | Heating | 6699.76132 | 8039.71358 | 0.28107 | 0.33728 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 379.89000 | 8.17812 | 0.28948 | 0.00000 |
3 | CORE_RETAIL | Cooling | 103938.60837 | 124726.33005 | 7.63088 | 9.15706 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 1600.48290 | 258.43418 | 2.43913 | 0.00000 |
4 | CORE_RETAIL | Heating | 22493.01378 | 26991.61653 | 0.93864 | 2.43913 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 1600.48290 | 258.43418 | 2.43913 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 15900.58640 | 19080.70368 | 1.16753 | 1.40103 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 150.81000 | 24.35169 | 0.22983 | 0.00000 |
6 | POINT_OF_SALE | Heating | 3229.75938 | 3875.71126 | 0.13527 | 0.22983 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.22983 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 13935.81774 | 16722.98128 | 1.02326 | 1.22791 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 35.20000 | 1.71581E-002 | 150.81000 | 24.35169 | 0.22983 | 0.00000 |
8 | FRONT_RETAIL | Heating | 3229.75938 | 3875.71126 | 0.13527 | 0.22983 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.22983 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.82880E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 12.00000 | 1.93800 | 1.82880E-002 | 0.00000 |
10 | FRONT_ENTRY | Heating | 1970.87271 | 2365.04725 | 8.50548E-002 | 0.10207 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 20.10000 | 1.47983E-002 | 12.00000 | 1.93800 | 1.82880E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 36748.47 | 2.44527 | 2.44527 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 8071.88 | 0.33728 | 0.33728 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 155523.03 | 9.15706 | 9.15706 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 58704.87 | 2.43913 | 2.43913 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 21930.49 | 1.40103 | 1.40103 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 5531.63 | 0.22983 | 0.22983 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 19609.23 | 1.22791 | 1.22791 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 5531.63 | 0.22983 | 0.22983 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.44527 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.15706 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.40103 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22791 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.10207 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATER FAN | Design Size Maximum Flow Rate [m3/s] | 0.10207 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER HEATING COIL | Design Size Nominal Capacity [W] | 2364.97365 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44527 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.44527 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.44527 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44527 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.44527 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.44527 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 9.15706 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 9.15706 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.15706 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 9.15706 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.15706 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 9.15706 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.40103 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40103 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.40103 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40103 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.40103 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.40103 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22791 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22791 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22791 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22791 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22791 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22791 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.44527 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 9.15706 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.40103 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.22791 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.44527 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.28948 |
46 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.44527 |
47 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2676.35920 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.44527 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.44527 |
50 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.44527 |
51 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.44527 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.44527 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22263 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.44527 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 51709.57000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 25494.04466 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 51709.57000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75480 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75480 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 51709.57000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56785.02387 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-AC:1 HEATING COIL | Design Size Nominal Capacity [W] | 56785.02387 |
65 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.15706 |
66 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.43913 |
67 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 9.15706 |
68 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 16931.87160 |
69 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 9.15706 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 9.15706 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 9.15706 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 9.15706 |
73 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 9.15706 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.57853 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 9.15706 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 227391.62000 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 113695.80333 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 227391.62000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
81 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 227391.62000 |
82 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 212180.05791 |
83 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
84 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
85 | Coil:Heating:Fuel | PSZ-AC:2 HEATING COIL | Design Size Nominal Capacity [W] | 212180.05791 |
86 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.40103 |
87 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22983 |
88 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.40103 |
89 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1597.33033 |
90 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.40103 |
91 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.40103 |
92 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.40103 |
93 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.40103 |
94 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.40103 |
95 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70052 |
96 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.40103 |
97 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32174.87000 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15913.43203 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32174.87000 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72601 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72601 |
102 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32174.87000 |
103 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32287.77027 |
104 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
106 | Coil:Heating:Fuel | PSZ-AC:3 HEATING COIL | Design Size Nominal Capacity [W] | 32287.77027 |
107 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22791 |
108 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22983 |
109 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22791 |
110 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1399.95601 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22791 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22791 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22791 |
114 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22791 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22791 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61396 |
117 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22791 |
118 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29291.54000 |
119 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14495.09114 |
120 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29291.54000 |
121 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71413 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71413 |
123 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29291.54000 |
124 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28332.85491 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
127 | Coil:Heating:Fuel | PSZ-AC:4 HEATING COIL | Design Size Nominal Capacity [W] | 28332.85491 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1 COOLING COIL | 49786.1 | 9.87 | 9.87 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2 COOLING COIL | 220167.5 | 9.60 | 9.60 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3 COOLING COIL | 31071.2 | 10.51 | 10.51 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4 COOLING COIL | 28323.6 | 10.55 | 10.55 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1586.27 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | N/A | 5.799 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 115.16 | 153.22 | 115.16 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 38.06 | 38.06 | 38.06 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.2_SHGC_0.25 | N/A | 6.813 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
1 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C4 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
2 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C1 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
3 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C2 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
4 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R2C3 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
5 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C3 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
6 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C1 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
7 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C4 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A | |||
8 | SKYLIGHT_FRAME_NONRES | Frame | SKYLIGHTS_R1C2 | Window5 Detailed Fenestration | N/A | N/A | 0.94 | 0.94 | * | N/A | N/A | 0.21 | N/A |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.0099526398E-002 | 0.2116292613 | Pass | Pass | 3.8015101534E-002 | 0.2049276231 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.1477901980E-002 | 0.1835581484 | Pass | Pass | 4.5755053764E-002 | 0.2383183952 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.0377460766E-002 | 0.2611190515 | Pass | Pass | 3.7821417443E-002 | 0.1910136318 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 5.2753844349E-002 | 0.2230210546 | Pass | Pass | 3.7474590177E-002 | 0.1939797734 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 7.8910512219E-002 | 0.1200277209 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5650.42 | -60.9 | 0.00 | -2335.6 | 5278.71 | 8532.62 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.227 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.046 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 1600.48 | 1586.27 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 153.22 | 115.16 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 153.22 | 115.16 | 180.00 | 90.00 | S |
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.260 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.420 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 | |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 12.00 | 12.00 | 180.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_SOUTH_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
CORE_RETAIL_WALL_SOUTH_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 180.00 | 90.00 | S |
CORE_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 330.83 | 330.83 | 0.00 | 90.00 | N |
CORE_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
POINT_OF_SALE_WALL_EAST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
POINT_OF_SALE_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
POINT_OF_SALE_WALL_EAST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_WEST_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_RETAIL_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 153.22 | 153.22 | 0.00 | 90.00 | N |
FRONT_RETAIL_WALL_WEST_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
FRONT_ENTRY_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 90.00 | 90.00 | E |
FRONT_ENTRY_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 24.38 | 24.38 | 0.00 | 90.00 | N |
FRONT_ENTRY_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 18.29 | 18.29 | 270.00 | 90.00 | W |
BACK_SPACE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 759.78 | 0.00 | 90.00 | N | ||
CORE_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3200.97 | 0.00 | 90.00 | N | ||
POINT_OF_SALE_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_RETAIL_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 301.62 | 0.00 | 90.00 | N | ||
FRONT_ENTRY_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 24.00 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_1.02_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 0.84 | 0.94 | 0.00 | 1.78 | 1.78 | 5.799 | 0.401 | 0.402 | 283.913 | 0.000 | CurtainWall | 5.733 | 0.325 | 0.251 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 6.813 | 0.251 | 0.252 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 38.06 | 0.00 | 0.00 | 38.06 | 38.06 | 6.813 | 0.251 | 0.252 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_1.2_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 6.813 | 0.251 | 0.252 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 98.16 | 6.666 | 0.272 | 0.273 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 98.16 | 6.666 | 0.272 | 0.273 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | BACK_SPACE | GENERAL | 9.3031 | 379.89 | 3534.15 | LightsWired | LTG_SCH_BACK | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 45.28 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | CORE_RETAIL | GENERAL | 17.6219 | 1600.48 | 28203.61 | LightsWired | LTG_SCH_CORE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 361.35 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | POINT_OF_SALE | GENERAL | 17.6219 | 150.81 | 2657.56 | LightsWired | LTG_SCH_SALE | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.05 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | FRONT_RETAIL | GENERAL | 17.6219 | 150.81 | 2657.56 | LightsWired | LTG_SCH_FRONT | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.05 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | FRONT_ENTRY | GENERAL | 10.3529 | 12.00 | 124.23 | LightsWired | LTG_SCH_ENTRY | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.59 |
Interior Lighting Total | 16.2063 | 2293.99 | 37177.13 | 476.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7996.55 | AstronomicalClock | - | 83.83 | 83.83 | 125.84 | |
Exterior Lighting Total | 7996.55 | 125.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 51709.57 | 39030.38 | 12679.19 | 0.75 | 3.30 | |||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 227391.62 | 159419.72 | 67971.90 | 0.70 | 3.13 | |||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32174.87 | 23359.28 | 8815.59 | 0.73 | 3.50 | |||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29291.54 | 20917.97 | 8373.57 | 0.71 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1 COOLING COIL | 49786.1 | 9.87 | 9.87 | ||||
PSZ-AC:2 COOLING COIL | 220167.5 | 9.60 | 9.60 | ||||
PSZ-AC:3 COOLING COIL | 31071.2 | 10.51 | 10.51 | ||||
PSZ-AC:4 COOLING COIL | 28323.6 | 10.55 | 10.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | Coil:Heating:Fuel | 2364.97 | 0.80 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | 56785.02 | 0.80 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | 212180.06 | 0.79 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | 32287.77 | 0.80 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | 28332.85 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.10 | 9.48 | 92.91 | 1.00 | 12.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 2.45 | 2676.36 | 1094.51 | 1.00 | 1.26 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 9.16 | 16931.87 | 1849.05 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.40 | 1597.33 | 1140.11 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.23 | 1399.96 | 1140.11 | 1.00 | 1.32 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 27755.90 | 33307.08 | 87.68 | 2.038 | 2.445 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 23.89 | 23.89 | 0.00900 | 35.12 | 0.01716 | 0.289 | 0.00 |
CORE_RETAIL | 103938.61 | 124726.33 | 77.93 | 7.631 | 9.157 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.89 | 0.00915 | 34.85 | 0.01716 | 2.439 | 0.00 |
POINT_OF_SALE | 15900.59 | 19080.70 | 126.52 | 1.168 | 1.401 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 23.89 | 23.89 | 0.00918 | 35.20 | 0.01716 | 0.230 | 0.00 |
FRONT_RETAIL | 13935.82 | 16722.98 | 110.89 | 1.023 | 1.228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 23.89 | 23.89 | 0.00927 | 35.20 | 0.01716 | 0.230 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.018 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 0.00 | 34.88 | 0.01721 | 35.12 | 0.01716 | 0.018 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 6699.76 | 8039.71 | 21.16 | 0.281 | 0.337 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01160 | 20.10 | 0.01480 | 0.289 | 0.00 |
CORE_RETAIL | 22493.01 | 26991.62 | 16.86 | 0.939 | 2.439 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00938 | 20.10 | 0.01480 | 2.439 | 0.00 |
POINT_OF_SALE | 3229.76 | 3875.71 | 25.70 | 0.135 | 0.230 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01155 | 20.10 | 0.01480 | 0.230 | 0.00 |
FRONT_RETAIL | 3229.76 | 3875.71 | 25.70 | 0.135 | 0.230 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01155 | 20.10 | 0.01480 | 0.230 | 0.00 |
FRONT_ENTRY | 1970.87 | 2365.05 | 197.09 | 0.085 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.12 | 0.01441 | 20.10 | 0.01480 | 0.018 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.45 | 2.45 | 0.34 | 0.34 | 2.4453 | 2.4453 | 2.4453 | 1.0000 | 1.0000 |
PSZ-AC:2 | 9.16 | 9.16 | 2.44 | 2.44 | 9.1571 | 9.1571 | 9.1571 | 1.0000 | 1.0000 |
PSZ-AC:3 | 1.40 | 1.40 | 0.23 | 0.23 | 1.4010 | 1.4010 | 1.4010 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.23 | 1.23 | 0.23 | 0.23 | 1.2279 | 1.2279 | 1.2279 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 2364.974 | 2364.974 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 2364.97 | 2364.97 | 0.102066 | 21.12 | 20.13 | 0.01440586 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.12 | 0.01440586 | 91.4678 | 2365.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 51709.570 | 39030.383 | 2.445270 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 51709.57 | 41272.86 | 2.445270 | 26.12 | 18.33 | 0.00997037 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 11.8382 | 23.89 | 0.00900508 | 48.7400 | 27752.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 56785.024 | 56785.024 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 56785.02 | 56785.02 | 2.445268 | 20.80 | 18.16 | 0.01197871 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 11.8382 | 21.11 | 0.01160011 | 74.0160 | 6699.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 227391.620 | 159419.717 | 9.157060 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 227391.62 | 160583.85 | 9.157060 | 28.41 | 20.08 | 0.01129719 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.6367 | 23.89 | 0.00915390 | 49.5352 | 103562.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 212180.058 | 212180.058 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 212180.06 | 212180.06 | 9.157061 | 20.84 | 17.16 | 0.01072539 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 26.6367 | 21.11 | 0.00924661 | 59.2262 | 11543.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 32174.870 | 23359.277 | 1.401030 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 32174.87 | 24192.57 | 1.401030 | 26.67 | 18.92 | 0.01049055 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 16.4047 | 23.89 | 0.00918212 | 49.6891 | 15900.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 32287.770 | 32287.770 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 32287.77 | 32287.77 | 1.401032 | 20.95 | 17.85 | 0.01152855 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.4046 | 19.50 | 0.01088690 | 76.8324 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 29291.540 | 20917.967 | 1.227910 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 29291.54 | 21434.11 | 1.227910 | 26.93 | 19.20 | 0.01074947 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 18.7175 | 23.89 | 0.00927370 | 50.1775 | 13935.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28332.855 | 28332.855 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28332.85 | 28332.85 | 1.227913 | 20.92 | 17.92 | 0.01161901 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.7175 | 19.50 | 0.01088690 | 76.8324 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 2364.974 | 2364.974 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATER FAN | Fan:ConstantVolume | 0.102066 | 0.12284582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 2364.97 | 2364.97 | 1.0000 | 0.12284582 | 0.102066 | 21.12 | 20.13 | 0.01440586 | 57816.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2364.97 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.12 | 0.01440586 | 21.12 | 0.01440586 | 91.4678 | 2365.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 51709.570 | 39030.383 | 2.445270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3744 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.445268 | 2.94311222 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | Sensible | 51709.57 | 41272.86 | 1.0000 | 2.94311470 | 2.445270 | 26.12 | 18.33 | 0.00997037 | 51661.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51709.57 | 35.20 | 0.01715815 | 25.83 | 0.28947580 | 11.8382 | 23.89 | 0.00900508 | 23.89 | 0.00900508 | 48.7400 | 27752.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56785.024 | 56785.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.445268 | 2.94311222 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 56785.02 | 56785.02 | 1.0000 | 2.94311222 | 2.445268 | 20.80 | 18.16 | 0.01197871 | 51320.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56785.02 | 20.10 | 0.01479830 | 20.10 | 0.28947580 | 11.8382 | 20.89 | 0.01160011 | 21.11 | 0.01160011 | 74.0160 | 6699.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 227391.620 | 159419.717 | 9.157060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8409 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 9.157061 | 11.02139219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | Sensible | 227391.62 | 160583.85 | 1.0000 | 11.02139146 | 9.157060 | 28.41 | 20.08 | 0.01129719 | 57402.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 227391.62 | 35.20 | 0.01715815 | 25.83 | 2.43913434 | 26.6367 | 23.89 | 0.00915390 | 23.89 | 0.00915390 | 49.5352 | 103562.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 212180.058 | 212180.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 9.157061 | 11.02139219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 212180.06 | 212180.06 | 1.0000 | 11.02139219 | 9.157061 | 20.84 | 17.16 | 0.01072539 | 48181.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 212180.06 | 20.10 | 0.01479830 | 20.10 | 2.43913434 | 26.6367 | 21.11 | 0.00924661 | 21.11 | 0.00924661 | 59.2262 | 11543.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32174.870 | 23359.277 | 1.401030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3414 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.401032 | 1.68627497 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | Sensible | 32174.87 | 24192.57 | 1.0000 | 1.68627268 | 1.401030 | 26.67 | 18.92 | 0.01049055 | 53552.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32174.87 | 35.20 | 0.01715815 | 25.83 | 0.22983429 | 16.4047 | 23.89 | 0.00918212 | 23.89 | 0.00918212 | 49.6891 | 15900.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32287.770 | 32287.770 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.401032 | 1.68627497 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 32287.77 | 32287.77 | 1.0000 | 1.68627497 | 1.401032 | 20.95 | 17.85 | 0.01152855 | 50327.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32287.77 | 20.10 | 0.01479830 | 20.10 | 0.22983429 | 16.4046 | 21.11 | 0.01088690 | 19.50 | 0.01088690 | 76.8324 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29291.540 | 20917.967 | 1.227910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8227 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.227913 | 1.47791020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | Sensible | 29291.54 | 21434.11 | 1.0000 | 1.47790631 | 1.227910 | 26.93 | 19.20 | 0.01074947 | 54480.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29291.54 | 35.20 | 0.01715815 | 25.83 | 0.22983429 | 18.7175 | 23.89 | 0.00927370 | 23.89 | 0.00927370 | 50.1775 | 13935.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28332.855 | 28332.855 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.227913 | 1.47791020 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 28332.85 | 28332.85 | 1.0000 | 1.47791020 | 1.227913 | 20.92 | 17.92 | 0.01161901 | 50533.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28332.85 | 20.10 | 0.01479830 | 20.10 | 0.22983429 | 18.7175 | 21.11 | 0.01088690 | 19.50 | 0.01088690 | 76.8324 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 4913.00 | 116.00 | 116.00 |
CORE_RETAIL | 4913.00 | 1794.50 | 1794.50 |
POINT_OF_SALE | 4913.00 | 269.50 | 269.50 |
FRONT_RETAIL | 4913.00 | 592.33 | 592.33 |
FRONT_ENTRY | 4913.00 | 4911.17 | 4911.17 |
Facility | 4913.00 | 4911.17 | 4911.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 118.33 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 85.83 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 111.83 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 100.83 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 130.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.465 | 0.034 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.931 | 0.007 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.930 | 0.039 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.930 | 0.039 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 35.360 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 4.07 | 8.18 | 2317.33 | 0.455 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.910 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.910 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.910 | 0.000 | 0.000 | 0.000 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 4.07 | 8.18 | 2317.33 | 379.89 | 0.2895 | 0.289 |
CORE_RETAIL | PSZ-AC:2 | 128.48 | 258.43 | 9762.95 | 1600.48 | 2.4391 | 2.439 |
POINT_OF_SALE | PSZ-AC:3 | 12.11 | 24.35 | 919.94 | 150.81 | 0.2298 | 0.230 |
FRONT_RETAIL | PSZ-AC:4 | 12.11 | 24.35 | 919.94 | 150.81 | 0.2298 | 0.230 |
FRONT_ENTRY | 0.96 | 1.94 | 73.20 | 12.00 | 0.018 | ||
Total Facility | 157.72 | 317.25 | 13993.36 | 2293.99 | 3.1883 | 3.207 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BACK_SPACE | 5657520.28 | 0.00 | 5657520.28 | 1096802.01 | 6754322.29 | 9128908.83 | 3396.60 | 5363.40 | 0.00 | 655.85 |
CORE_RETAIL | 47306976.68 | 0.00 | 47306976.68 | 940483.23 | 48247459.91 | 76920540.52 | 3432.07 | 5327.93 | 0.00 | 631.21 |
POINT_OF_SALE | 4472882.64 | 0.00 | 4472882.64 | 500204.05 | 4973086.70 | 7248054.14 | 3430.16 | 5329.84 | 0.00 | 650.73 |
FRONT_RETAIL | 4468783.00 | 0.00 | 4468783.00 | 500204.05 | 4968987.05 | 7248054.14 | 3432.96 | 5327.04 | 0.00 | 647.43 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 12007028.00 | 12007028.00 | 576729.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 61906162.60 | 0.00 | 61906162.60 | 15044721.35 | 76950883.96 | 0.10E+09 | 8760.00 | 5364.25 | 0.00 | 663.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BACK_SPACE | 0.2895 | 0.0000 | 0.2895 | 0.0209 | 0.3104 | 0.2895 | 0.00 | 4913.00 | 0.00 |
CORE_RETAIL | 2.4391 | 0.0000 | 2.4391 | 0.0179 | 2.4571 | 2.4391 | 0.00 | 4913.00 | 0.00 |
POINT_OF_SALE | 0.2298 | 0.0000 | 0.2298 | 0.0095 | 0.2394 | 0.2298 | 0.00 | 4913.00 | 0.00 |
FRONT_RETAIL | 0.2298 | 0.0000 | 0.2298 | 0.0095 | 0.2394 | 0.2298 | 0.00 | 4913.00 | 0.00 |
FRONT_ENTRY | 0.0000 | 0.0000 | 0.0000 | 0.6716 | 0.6716 | 0.0183 | 4913.00 | 0.00 | 0.00 |
Total Facility | 3.1883 | 0.0000 | 3.1883 | 0.7295 | 3.9178 | 3.2066 | 4913.00 | 4913.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC:1 | 8195715.15 | 0.00 | 8195715.15 | 9128908.83 | 3378.22 | 1.02 | 5380.76 | 655.29 |
PSZ-AC:2 | 68530820.32 | 0.00 | 68530820.32 | 76920540.52 | 3416.84 | 1.09 | 5342.08 | 631.21 |
PSZ-AC:3 | 6479600.65 | 0.00 | 6479600.65 | 7248054.14 | 3411.56 | 1.49 | 5346.95 | 650.53 |
PSZ-AC:4 | 6473661.73 | 0.00 | 6473661.73 | 7248054.14 | 3414.88 | 1.50 | 5343.62 | 647.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC:1 | 0.4193 | 0.0000 | 0.4193 | 0.2895 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:2 | 3.5334 | 0.0000 | 3.5334 | 2.4391 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:3 | 0.3329 | 0.0000 | 0.3329 | 0.2298 | 0.00 | 0.00 | 4913.00 |
PSZ-AC:4 | 0.3329 | 0.0000 | 0.3329 | 0.2298 | 0.00 | 0.00 | 4913.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC:1 | 0.00 | 5568.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:2 | 0.00 | 5544.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:3 | 0.00 | 5563.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC:4 | 0.00 | 5560.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC:1 | 0.0000 | 0.4193 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:2 | 0.0000 | 3.5334 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:3 | 0.0000 | 0.3329 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC:4 | 0.0000 | 0.3329 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 450 |
Defaulted Fields | 416 |
Fields with Defaults | 1298 |
Autosized Fields | 76 |
Autosizable Fields | 182 |
Autocalculated Fields | 70 |
Autocalculatable Fields | 140 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
Electricity:Building | 671.48 | 3654.03 | 01-JAN-00:10 | 44230.45 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 95.27 | 636.56 | 01-JAN-00:10 | 5939.88 | 02-JAN-09:10 |
Electricity:SpaceType:GENERAL | 671.48 | 3654.03 | 01-JAN-00:10 | 44230.45 | 02-JAN-09:10 |
InteriorLights:Electricity | 476.32 | 1858.86 | 01-JAN-00:10 | 33459.42 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 45.28 | 176.71 | 01-JAN-00:10 | 3180.74 | 02-JAN-09:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 476.32 | 1858.86 | 01-JAN-00:10 | 33459.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 476.32 | 1858.86 | 01-JAN-00:10 | 33459.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:BACK_SPACE | 45.28 | 176.71 | 01-JAN-00:10 | 3180.74 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 476.32 | 1858.86 | 01-JAN-00:10 | 33459.42 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 445.65 | 2185.61 | 01-JAN-00:10 | 30035.86 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 361.35 | 1410.18 | 01-JAN-00:10 | 25383.25 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_RETAIL | 361.35 | 1410.18 | 01-JAN-00:10 | 25383.25 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 86.97 | 619.69 | 01-JAN-00:10 | 5312.70 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.05 | 132.88 | 01-JAN-00:10 | 2391.81 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.05 | 132.88 | 01-JAN-00:10 | 2391.81 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 41.99 | 205.95 | 01-JAN-00:10 | 2830.21 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.05 | 132.88 | 01-JAN-00:10 | 2391.81 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.05 | 132.88 | 01-JAN-00:10 | 2391.81 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.59 | 6.21 | 01-JAN-00:10 | 111.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.59 | 6.21 | 01-JAN-00:10 | 111.81 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.59 | 6.21 | 01-JAN-00:10 | 111.81 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
ElectricityPurchased:Plant | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
Cogeneration:ElectricityPurchased | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
ElectricityNet:Plant | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
Cogeneration:ElectricityNet | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
General:Cogeneration:ElectricityNet | 2464.11 | 3654.03 | 01-JAN-06:20 | 165949.88 | 13-JUN-15:00 |
Electricity:HVAC | 1666.79 | 0.00 | 01-JAN-00:10 | 121719.43 | 13-JUN-15:00 |
Fans:Electricity | 439.84 | 0.00 | 01-JAN-00:10 | 22605.52 | 08-FEB-07:00 |
General:Fans:Electricity | 439.84 | 0.00 | 01-JAN-00:10 | 22605.52 | 08-FEB-07:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1226.95 | 0.00 | 01-JAN-00:10 | 99113.91 | 13-JUN-15:00 |
General:Cooling:Electricity | 1226.95 | 0.00 | 01-JAN-00:10 | 99113.91 | 13-JUN-15:00 |
ExteriorLights:Electricity | 125.84 | 0.00 | 01-JAN-06:20 | 7996.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 125.84 | 0.00 | 01-JAN-06:20 | 7996.55 | 01-JAN-00:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 83.39 | 1862.00 | 07-JAN-05:10 | 4791.82 | 06-JAN-12:30 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 83.39 | 1862.00 | 07-JAN-05:10 | 4791.82 | 06-JAN-12:30 |
WaterSystems:NaturalGas | 83.39 | 1862.00 | 07-JAN-05:10 | 4791.82 | 06-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 83.39 | 1862.00 | 07-JAN-05:10 | 4791.82 | 06-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5718.67 | 0.00 | 01-JAN-00:10 | 521536.19 | 08-MAY-04:10 |
EnergyTransfer:Building | 1666.91 | 0.00 | 01-JAN-00:10 | 147472.33 | 08-MAY-04:10 |
EnergyTransfer:Zone:BACK_SPACE | 303.19 | 0.00 | 01-JAN-00:10 | 28827.99 | 13-JUN-15:40 |
Heating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BACK_SPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1666.91 | 0.00 | 01-JAN-00:10 | 147472.33 | 08-MAY-04:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 303.19 | 0.00 | 01-JAN-00:10 | 28827.99 | 13-JUN-15:40 |
General:Cooling:EnergyTransfer | 1666.91 | 0.00 | 01-JAN-00:10 | 147472.33 | 08-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:BACK_SPACE | 303.19 | 0.00 | 01-JAN-00:10 | 28827.99 | 13-JUN-15:40 |
EnergyTransfer:Zone:CORE_RETAIL | 998.83 | 0.00 | 01-JAN-00:10 | 98996.29 | 08-MAY-04:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 998.83 | 0.00 | 01-JAN-00:10 | 98996.29 | 08-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:CORE_RETAIL | 998.83 | 0.00 | 01-JAN-00:10 | 98996.29 | 08-MAY-04:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 198.64 | 0.00 | 01-JAN-00:10 | 17327.20 | 08-DEC-14:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 198.64 | 0.00 | 01-JAN-00:10 | 17327.20 | 08-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 198.64 | 0.00 | 01-JAN-00:10 | 17327.20 | 08-DEC-14:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 166.25 | 0.00 | 01-JAN-00:10 | 15525.03 | 08-DEC-14:30 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 166.25 | 0.00 | 01-JAN-00:10 | 15525.03 | 08-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 166.25 | 0.00 | 01-JAN-00:10 | 15525.03 | 08-DEC-14:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 4051.76 | 0.00 | 01-JAN-00:10 | 377730.62 | 10-JUN-04:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 4051.76 | 0.00 | 01-JAN-00:10 | 377730.62 | 10-JUN-04:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.000 | -303.178 | 0.000 | 0.000 | 4.889 | 45.280 | 49.992 | 0.000 | 0.000 | 2.924 | 201.517 | 0.000 | 0.000 | 0.000 | -1.425 | -0.004 |
CORE_RETAIL | 0.000 | 0.000 | 0.000 | -998.824 | 0.000 | 0.000 | 154.488 | 361.351 | 84.300 | 18.956 | 0.000 | 2.650 | 380.628 | 0.000 | -2.664 | 0.000 | -0.886 | -0.020 |
POINT_OF_SALE | 0.000 | 0.000 | 0.000 | -198.629 | 0.000 | 0.000 | 14.557 | 34.049 | 52.923 | 40.010 | 0.000 | 1.320 | 63.685 | 0.000 | -7.054 | 0.000 | -0.861 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.000 | -166.241 | 0.000 | 0.000 | 14.557 | 34.049 | 7.943 | 40.176 | 0.000 | 1.339 | 75.143 | 0.000 | -6.296 | 0.000 | -0.671 | 0.000 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.590 | 1.592 | 0.000 | 6.257 | 0.000 | 1.270 | 0.000 | 0.000 | -1.832 | 0.000 | -2.476 | -5.401 |
Total Facility | 0.000 | 0.000 | 0.000 | -1666.872 | 0.000 | 0.000 | 189.081 | 476.322 | 195.158 | 105.399 | 0.000 | 9.504 | 720.973 | 0.000 | -17.846 | 0.000 | -6.318 | -5.426 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 23-FEB-05:01 | 0.00 | 0.00 | 0.00 | -43200.87 | 0.00 | 0.00 | 0.00 | 176.71 | 613.14 | 0.00 | 0.00 | 0.00 | 42486.42 | 0.00 | -0.00 | 0.00 | -75.41 | 0.00 |
CORE_RETAIL | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | -165156.55 | 0.00 | 0.00 | 0.00 | 1410.18 | 1033.91 | 0.00 | 0.00 | 0.00 | 163803.56 | 0.00 | -464.85 | 0.00 | -626.26 | 0.00 |
POINT_OF_SALE | 23-FEB-05:01 | 0.00 | 0.00 | 0.00 | -27135.25 | 0.00 | 0.00 | 0.00 | 132.88 | 649.09 | 0.00 | 0.00 | 0.00 | 27342.09 | 0.00 | -938.90 | 0.00 | -49.91 | 0.00 |
FRONT_RETAIL | 23-FEB-05:01 | 0.00 | 0.00 | 0.00 | -23395.89 | 0.00 | 0.00 | 0.00 | 132.88 | 97.42 | 0.00 | 0.00 | 0.00 | 24065.96 | 0.00 | -857.87 | 0.00 | -42.50 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-FEB-05:01 | 0.00 | 0.00 | 0.00 | -255942.66 | 0.00 | 0.00 | 0.00 | 1858.86 | 2393.56 | 0.00 | 0.00 | 0.00 | 254247.68 | 0.00 | -2320.67 | 0.00 | -236.78 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4453 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2895 | 2.4453 | 0.1184 | 1.0000 | Not calculated | 0.2895 | 0.1184 | ||
PSZ-AC:2 | 9.1571 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 2.4391 | 9.1571 | 0.2664 | 1.0000 | Not calculated | 2.4391 | 0.2664 | ||
PSZ-AC:3 | 1.4010 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.2298 | 1.4010 | 0.1640 | 1.0000 | Not calculated | 0.2298 | 0.1640 | ||
PSZ-AC:4 | 1.2279 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.2298 | 1.2279 | 0.1872 | 1.0000 | Not calculated | 0.2298 | 0.1872 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4453 | 0.0000 | 8.1781 | 1.0000 | Calculated from schedules | 0.2895 | 2.4453 | 1.0000 | 1.0000 | Not calculated | 0.2895 | 0.1184 | ||
PSZ-AC:2 | 9.1571 | 0.0000 | 258.4342 | 1.0000 | Calculated from schedules | 2.4391 | 9.1571 | 1.0000 | 1.0000 | Not calculated | 2.4391 | 0.2664 | ||
PSZ-AC:3 | 1.4010 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.2298 | 1.4010 | 1.0000 | 1.0000 | Not calculated | 0.2298 | 0.1640 | ||
PSZ-AC:4 | 1.2279 | 0.0000 | 24.3517 | 1.0000 | Calculated from schedules | 0.2298 | 1.2279 | 1.0000 | 1.0000 | Not calculated | 0.2298 | 0.1872 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 8.1781 | 0.000762 | 379.89 | 0.2895 | 1.0000 | 0.2895 | 1.000 | 0.2895 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001524 | 1600.48 | 2.4391 | 1.0000 | 2.4391 | 1.000 | 2.4391 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 8.18 | 0.000762 | 379.8900 | 0.2895 | 0.2895 | 0.2895 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001524 | 1600.4829 | 2.4391 | 2.4391 | 2.4391 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4453 | 2.4453 | 2.4453 | No | 0.2895 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 9.1571 | 9.1571 | 9.1571 | No | 2.4391 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4010 | 1.4010 | 1.4010 | No | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2279 | 1.2279 | 1.2279 | No | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4453 | 2.4453 | 2.4453 | 2.4453 | 0.2895 | 1.0000 |
PSZ-AC:2 | 9.1571 | 9.1571 | 9.1571 | 9.1571 | 2.4391 | 1.0000 |
PSZ-AC:3 | 1.4010 | 1.4010 | 1.4010 | 1.4010 | 0.2298 | 1.0000 |
PSZ-AC:4 | 1.2279 | 1.2279 | 1.2279 | 1.2279 | 0.2298 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4453 | 2.4453 | 2.4453 | No | 0.2895 | 0.8583 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_RETAIL | PSZ-AC:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 9.1571 | 9.1571 | 9.1571 | No | 2.4391 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
POINT_OF_SALE | PSZ-AC:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4010 | 1.4010 | 1.4010 | No | 0.2298 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
FRONT_RETAIL | PSZ-AC:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2279 | 1.2279 | 1.2279 | No | 0.2298 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4453 | 2.4453 | 2.4453 | 2.4453 | 0.2895 | 1.0000 |
PSZ-AC:2 | 9.1571 | 9.1571 | 9.1571 | 9.1571 | 2.4391 | 1.0000 |
PSZ-AC:3 | 1.4010 | 1.4010 | 1.4010 | 1.4010 | 0.2298 | 1.0000 |
PSZ-AC:4 | 1.2279 | 1.2279 | 1.2279 | 1.2279 | 0.2298 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 94.22 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1226.95 | 99113.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 476.32 | 33459.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 125.84 | 7996.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 439.84 | 22605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.39 | 4791.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 2464.11 |
Natural Gas | 0.00 | 83.39 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 2547.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.64 |
Space Heating | 0.00 |
Space Cooling | 534.85 |
Fans (All) | 191.74 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 1074.16 |
Subtotal | 1074.16 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.35 |
Miscellaneous (All) | 36.35 |
Subtotal | 36.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.70 |
Space Heating | 0.00 |
Space Cooling | 48.16 |
Fans (All) | 17.27 |
Service Water Heating | 3.27 |
Receptacle Equipment | 7.66 |
Miscellaneous | 4.94 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
LTG_SCH_ENTRY | 3609. | 8760. |
LTG_SCH_CORE | 3609. | 8760. |
LTG_SCH_BACK | 3609. | 8760. |
LTG_SCH_SALE | 3609. | 8760. |
LTG_SCH_FRONT | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | FRONT_ENTRY HEATING SP | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 6239.00 | 2434.00 | 87.00 | 0.00 | 0.00 |
CORE_RETAIL | 6457.33 | 2302.67 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 5845.00 | 2787.50 | 127.50 | 0.00 | 0.00 |
FRONT_RETAIL | 6016.33 | 2686.67 | 57.00 | 0.00 | 0.00 |
FRONT_ENTRY | 233.67 | 3242.83 | 4732.33 | 551.17 | 0.00 |
Min | 233.67 | 2302.67 | 0.00 | 0.00 | 0.00 |
Max | 6457.33 | 3242.83 | 4732.33 | 551.17 | 0.00 |
Average | 4958.27 | 2690.73 | 1000.77 | 110.23 | 0.00 |
Sum | 24791.33 | 13453.67 | 5003.83 | 551.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BACK_SPACE | 16872.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 609599.00 | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 56000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 29.33 | 215.50 | 1286.00 | 389.17 | 0.00 |
Min | 29.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 609599.00 | 215.50 | 1286.00 | 389.17 | 0.00 |
Average | 147700.07 | 43.10 | 257.20 | 77.83 | 0.00 |
Sum | 738500.33 | 215.50 | 1286.00 | 389.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 5196.50 | 3544.17 | 19.33 | 0.00 | 0.00 |
CORE_RETAIL | 3455.83 | 5304.17 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 5011.67 | 3710.17 | 38.17 | 0.00 | 0.00 |
FRONT_RETAIL | 4600.00 | 4142.67 | 17.33 | 0.00 | 0.00 |
FRONT_ENTRY | 1.67 | 4419.50 | 3875.50 | 463.33 | 0.00 |
Min | 1.67 | 3544.17 | 0.00 | 0.00 | 0.00 |
Max | 5196.50 | 5304.17 | 3875.50 | 463.33 | 0.00 |
Average | 3653.13 | 4224.13 | 790.07 | 92.67 | 0.00 |
Sum | 18265.67 | 21120.67 | 3950.33 | 463.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BACK_SPACE | 16668.17 | 203.83 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 426868.67 | 182730.33 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 54555.00 | 1445.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 51789.00 | 4211.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 505.17 | 1087.67 | 327.17 | 0.00 |
Min | 0.00 | 203.83 | 0.00 | 0.00 | 0.00 |
Max | 426868.67 | 182730.33 | 1087.67 | 327.17 | 0.00 |
Average | 109976.17 | 37819.07 | 217.53 | 65.43 | 0.00 |
Sum | 549880.83 | 189095.33 | 1087.67 | 327.17 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211981E+11 | 39466.71 | 18-JAN-05:01 | 19.97 | 19.97 | 0.291181E+09 | 326.84 | 28-JAN-15:39 | 32.07 | 21.72 |
February | 0.219469E+11 | 43202.41 | 23-FEB-05:01 | 24.08 | 21.14 | 0.265888E+09 | 326.84 | 22-FEB-15:09 | 24.08 | 21.14 |
March | 0.267404E+11 | 36254.94 | 03-MAR-05:01 | 22.83 | 20.19 | 0.304124E+09 | 326.85 | 20-MAR-14:00 | 35.00 | 24.82 |
April | 0.280547E+11 | 34117.91 | 27-APR-04:01 | 26.58 | 24.20 | 0.287504E+09 | 326.84 | 27-APR-14:00 | 34.00 | 25.50 |
May | 0.306347E+11 | 36535.73 | 11-MAY-04:01 | 24.17 | 23.96 | 0.297658E+09 | 326.85 | 08-MAY-14:09 | 24.17 | 23.96 |
June | 0.336023E+11 | 37770.99 | 20-JUN-04:01 | 24.08 | 23.67 | 0.293545E+09 | 326.86 | 19-JUN-14:09 | 24.08 | 23.67 |
July | 0.282538E+11 | 40299.11 | 19-JUL-04:01 | 24.42 | 23.71 | 0.291623E+09 | 326.86 | 15-JUL-14:00 | 24.42 | 23.71 |
August | 0.259792E+11 | 36390.78 | 16-AUG-04:01 | 24.92 | 24.29 | 0.304122E+09 | 326.80 | 04-AUG-14:00 | 24.92 | 24.29 |
September | 0.243747E+11 | 35606.83 | 12-SEP-04:01 | 26.33 | 24.43 | 0.287504E+09 | 326.80 | 16-SEP-10:09 | 29.00 | 26.25 |
October | 0.213747E+11 | 34696.68 | 11-OCT-04:01 | 24.00 | 23.26 | 0.291181E+09 | 326.80 | 11-OCT-14:00 | 24.50 | 24.50 |
November | 0.208635E+11 | 36120.77 | 25-NOV-05:01 | 20.08 | 18.67 | 0.280151E+09 | 326.80 | 27-NOV-15:00 | 27.00 | 23.97 |
December | 0.201695E+11 | 37511.34 | 27-DEC-05:01 | 19.00 | 18.34 | 0.291622E+09 | 326.80 | 30-DEC-11:39 | 31.00 | 25.16 |
Annual Sum or Average | 0.303193E+12 | 0.348610E+10 | ||||||||
Minimum of Months | 0.201695E+11 | 34117.91 | 19.00 | 18.34 | 0.265888E+09 | 326.80 | 24.08 | 21.14 | ||
Maximum of Months | 0.336023E+11 | 43202.41 | 26.58 | 24.43 | 0.304124E+09 | 326.86 | 35.00 | 26.25 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789427E+11 | 163058.61 | 23-JAN-05:01 | 18.95 | 17.06 | 0.920152E+10 | 10327.18 | 07-JAN-11:09 | 18.95 | 17.06 |
February | 0.776441E+11 | 162223.62 | 23-FEB-05:01 | 24.08 | 21.14 | 0.840219E+10 | 10327.18 | 11-FEB-11:09 | 24.08 | 21.14 |
March | 0.924833E+11 | 156680.44 | 03-MAR-05:01 | 22.83 | 20.19 | 0.961047E+10 | 10327.18 | 11-MAR-11:09 | 30.17 | 24.22 |
April | 0.907739E+11 | 142874.39 | 27-APR-04:01 | 26.58 | 24.20 | 0.908533E+10 | 10327.18 | 14-APR-14:00 | 26.58 | 24.20 |
May | 0.897312E+11 | 137637.52 | 11-MAY-04:01 | 24.17 | 23.96 | 0.940599E+10 | 10327.19 | 12-MAY-14:09 | 31.17 | 25.78 |
June | 0.917607E+11 | 139189.49 | 20-JUN-04:01 | 24.08 | 23.67 | 0.927587E+10 | 10327.18 | 24-JUN-15:09 | 32.38 | 26.43 |
July | 0.835157E+11 | 144423.56 | 31-JUL-04:01 | 24.35 | 23.15 | 0.921546E+10 | 10327.18 | 08-JUL-10:09 | 24.35 | 23.15 |
August | 0.835726E+11 | 138802.68 | 24-AUG-04:01 | 24.00 | 23.59 | 0.961047E+10 | 10327.19 | 04-AUG-14:09 | 24.00 | 23.59 |
September | 0.819562E+11 | 138454.21 | 13-SEP-04:01 | 24.42 | 24.11 | 0.908534E+10 | 10327.19 | 16-SEP-13:39 | 25.13 | 24.29 |
October | 0.768679E+11 | 136321.98 | 09-OCT-06:01 | 24.20 | 23.99 | 0.920152E+10 | 10327.19 | 11-OCT-14:09 | 24.08 | 24.08 |
November | 0.751648E+11 | 155244.02 | 25-NOV-05:01 | 20.08 | 18.67 | 0.885298E+10 | 10327.18 | 27-NOV-15:00 | 27.00 | 23.97 |
December | 0.764204E+11 | 165180.82 | 21-DEC-05:01 | 18.00 | 17.36 | 0.921546E+10 | 10327.19 | 18-DEC-15:00 | 18.00 | 17.36 |
Annual Sum or Average | 0.998833E+12 | 0.110163E+12 | ||||||||
Minimum of Months | 0.751648E+11 | 136321.98 | 18.00 | 17.06 | 0.840219E+10 | 10327.18 | 18.00 | 17.06 | ||
Maximum of Months | 0.924833E+11 | 165180.82 | 26.58 | 24.20 | 0.961047E+10 | 10327.19 | 32.38 | 26.43 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187312E+11 | 25310.52 | 18-JAN-05:01 | 19.97 | 19.97 | 0.867083E+09 | 973.35 | 06-JAN-15:00 | 19.97 | 19.97 |
February | 0.174917E+11 | 27136.49 | 23-FEB-05:01 | 24.08 | 21.14 | 0.791759E+09 | 973.35 | 09-FEB-15:39 | 24.08 | 21.14 |
March | 0.181914E+11 | 22057.22 | 03-MAR-05:01 | 22.83 | 20.19 | 0.905590E+09 | 973.35 | 27-MAR-14:00 | 33.00 | 25.65 |
April | 0.161154E+11 | 19843.04 | 27-APR-04:01 | 26.58 | 24.20 | 0.856091E+09 | 973.11 | 14-APR-14:00 | 26.58 | 24.20 |
May | 0.163031E+11 | 20424.41 | 11-MAY-04:01 | 24.17 | 23.96 | 0.886311E+09 | 973.33 | 05-MAY-14:09 | 24.17 | 23.96 |
June | 0.163254E+11 | 20452.03 | 20-JUN-04:01 | 24.08 | 23.67 | 0.874049E+09 | 973.33 | 16-JUN-14:09 | 24.08 | 23.67 |
July | 0.149430E+11 | 22476.79 | 19-JUL-04:01 | 24.42 | 23.71 | 0.868352E+09 | 973.11 | 08-JUL-10:09 | 24.42 | 23.71 |
August | 0.147208E+11 | 20385.82 | 16-AUG-04:01 | 24.92 | 24.29 | 0.905574E+09 | 973.11 | 04-AUG-14:00 | 24.92 | 24.29 |
September | 0.152822E+11 | 20747.99 | 12-SEP-04:01 | 26.33 | 24.43 | 0.856092E+09 | 973.33 | 30-SEP-14:09 | 32.50 | 27.49 |
October | 0.154305E+11 | 21040.08 | 11-OCT-04:01 | 24.00 | 23.26 | 0.867040E+09 | 973.35 | 28-OCT-13:00 | 31.00 | 26.40 |
November | 0.167966E+11 | 22388.11 | 25-NOV-05:01 | 20.08 | 18.67 | 0.834204E+09 | 973.36 | 18-NOV-15:09 | 20.08 | 18.67 |
December | 0.183049E+11 | 24118.25 | 27-DEC-05:01 | 19.00 | 18.34 | 0.868382E+09 | 973.36 | 30-DEC-15:50 | 30.42 | 25.66 |
Annual Sum or Average | 0.198636E+12 | 0.103805E+11 | ||||||||
Minimum of Months | 0.147208E+11 | 19843.04 | 19.00 | 18.34 | 0.791759E+09 | 973.11 | 19.97 | 18.67 | ||
Maximum of Months | 0.187312E+11 | 27136.49 | 26.58 | 24.43 | 0.905590E+09 | 973.36 | 33.00 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159673E+11 | 21859.71 | 18-JAN-05:01 | 19.97 | 19.97 | 0.867061E+09 | 973.33 | 17-JAN-15:00 | 19.97 | 19.97 |
February | 0.149847E+11 | 23397.50 | 23-FEB-05:01 | 24.08 | 21.14 | 0.791742E+09 | 973.33 | 04-FEB-16:10 | 24.08 | 21.14 |
March | 0.152941E+11 | 19162.20 | 03-MAR-05:01 | 22.83 | 20.19 | 0.905580E+09 | 973.32 | 28-MAR-14:00 | 35.00 | 25.48 |
April | 0.134349E+11 | 16951.62 | 27-APR-04:01 | 26.58 | 24.20 | 0.856091E+09 | 973.11 | 14-APR-14:00 | 26.58 | 24.20 |
May | 0.135840E+11 | 17242.51 | 11-MAY-04:01 | 24.17 | 23.96 | 0.886309E+09 | 973.31 | 05-MAY-14:00 | 24.17 | 23.96 |
June | 0.136941E+11 | 17552.60 | 20-JUN-04:01 | 24.08 | 23.67 | 0.874046E+09 | 973.29 | 13-JUN-14:30 | 24.08 | 23.67 |
July | 0.122468E+11 | 18905.68 | 19-JUL-04:01 | 24.42 | 23.71 | 0.868353E+09 | 973.11 | 08-JUL-10:09 | 24.42 | 23.71 |
August | 0.119921E+11 | 17352.83 | 16-AUG-04:01 | 24.92 | 24.29 | 0.905574E+09 | 973.11 | 04-AUG-14:00 | 24.92 | 24.29 |
September | 0.126596E+11 | 17502.69 | 12-SEP-04:01 | 26.33 | 24.43 | 0.856091E+09 | 973.11 | 16-SEP-15:00 | 27.40 | 25.35 |
October | 0.126877E+11 | 17941.45 | 08-OCT-06:01 | 24.22 | 23.39 | 0.867039E+09 | 973.11 | 11-OCT-14:00 | 24.50 | 24.50 |
November | 0.141464E+11 | 19700.21 | 25-NOV-05:01 | 20.08 | 18.67 | 0.834197E+09 | 973.24 | 18-NOV-13:39 | 20.08 | 18.67 |
December | 0.155557E+11 | 21059.94 | 27-DEC-05:01 | 19.00 | 18.34 | 0.868372E+09 | 973.33 | 30-DEC-14:50 | 31.17 | 25.09 |
Annual Sum or Average | 0.166247E+12 | 0.103805E+11 | ||||||||
Minimum of Months | 0.119921E+11 | 16951.62 | 19.00 | 18.34 | 0.791742E+09 | 973.11 | 19.97 | 18.67 | ||
Maximum of Months | 0.159673E+11 | 23397.50 | 26.58 | 24.43 | 0.905580E+09 | 973.33 | 35.00 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.115263E+09 | 168.09 | 05-JAN-15:09 | 33.73 | 23.23 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.111309E+09 | 177.06 | 28-FEB-15:09 | 34.60 | 24.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.130256E+09 | 186.01 | 21-MAR-14:09 | 35.67 | 23.99 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.124055E+09 | 179.49 | 01-APR-14:09 | 35.42 | 26.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 | 0.127178E+09 | 186.05 | 06-MAY-11:30 | 36.50 | 25.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 | 0.126302E+09 | 184.95 | 13-JUN-14:00 | 36.00 | 28.43 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.109872E+09 | 156.91 | 15-JUL-15:00 | 33.20 | 25.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.115806E+09 | 164.32 | 10-AUG-14:09 | 33.50 | 27.78 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 | 0.110963E+09 | 165.10 | 06-SEP-14:09 | 33.83 | 26.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.107161E+09 | 156.47 | 04-OCT-14:09 | 32.92 | 26.22 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.105200E+09 | 169.88 | 18-NOV-13:09 | 33.75 | 25.30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.111528E+09 | 158.83 | 07-DEC-15:09 | 32.63 | 22.66 |
Annual Sum or Average | 0.00 | 0.139489E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.105200E+09 | 156.47 | 32.63 | 22.66 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.130256E+09 | 186.05 | 36.50 | 28.43 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379716E+10 | 3180.74 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.345492E+10 | 3180.74 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.394093E+10 | 3180.74 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.371828E+10 | 3180.74 | 01-APR-09:09 | 0.410339E+10 | 2759.14 | 01-APR-09:09 |
May | 0.386905E+10 | 3180.74 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.380289E+10 | 3180.74 | 01-JUN-08:09 | 0.416906E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.378444E+10 | 3180.74 | 01-JUL-09:09 | 0.419831E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.394093E+10 | 3180.74 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.371828E+10 | 3180.74 | 01-SEP-08:09 | 0.410229E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.379716E+10 | 3180.74 | 02-OCT-08:09 | 0.421210E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.367184E+10 | 3180.74 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.378444E+10 | 3180.74 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.452803E+11 | 0.499923E+11 | ||||
Minimum of Months | 0.345492E+10 | 3180.74 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.394093E+10 | 3180.74 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.303025E+11 | 25383.25 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.275713E+11 | 25383.25 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.314498E+11 | 25383.25 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.296730E+11 | 25383.25 | 01-APR-09:09 | 0.691935E+10 | 4652.60 | 01-APR-09:09 |
May | 0.308762E+11 | 25383.25 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.303482E+11 | 25383.25 | 01-JUN-08:09 | 0.703008E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.302010E+11 | 25383.25 | 01-JUL-09:09 | 0.707940E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.314498E+11 | 25383.25 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.296730E+11 | 25383.25 | 01-SEP-08:09 | 0.691749E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.303025E+11 | 25383.25 | 02-OCT-08:09 | 0.710266E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.293024E+11 | 25383.25 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.302010E+11 | 25383.25 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.361351E+12 | 0.842996E+11 | ||||
Minimum of Months | 0.275713E+11 | 25383.25 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.314498E+11 | 25383.25 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285534E+10 | 2391.81 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.259798E+10 | 2391.81 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.296345E+10 | 2391.81 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.279602E+10 | 2391.81 | 01-APR-09:09 | 0.434394E+10 | 2920.89 | 01-APR-09:09 |
May | 0.290940E+10 | 2391.81 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.285965E+10 | 2391.81 | 01-JUN-08:09 | 0.441346E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.284577E+10 | 2391.81 | 01-JUL-09:09 | 0.444442E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.296345E+10 | 2391.81 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.279602E+10 | 2391.81 | 01-SEP-08:09 | 0.434278E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.285534E+10 | 2391.81 | 02-OCT-08:09 | 0.445903E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.276110E+10 | 2391.81 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.284577E+10 | 2391.81 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.340493E+11 | 0.529230E+11 | ||||
Minimum of Months | 0.259798E+10 | 2391.81 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.296345E+10 | 2391.81 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285534E+10 | 2391.81 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.259798E+10 | 2391.81 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.296345E+10 | 2391.81 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.279602E+10 | 2391.81 | 01-APR-09:09 | 0.651995E+09 | 438.40 | 01-APR-09:09 |
May | 0.290940E+10 | 2391.81 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.285965E+10 | 2391.81 | 01-JUN-08:09 | 0.662429E+09 | 438.40 | 01-JUN-08:09 |
July | 0.284577E+10 | 2391.81 | 01-JUL-09:09 | 0.667077E+09 | 438.40 | 01-JUL-09:09 |
August | 0.296345E+10 | 2391.81 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.279602E+10 | 2391.81 | 01-SEP-08:09 | 0.651820E+09 | 438.40 | 01-SEP-08:09 |
October | 0.285534E+10 | 2391.81 | 02-OCT-08:09 | 0.669269E+09 | 438.40 | 02-OCT-08:09 |
November | 0.276110E+10 | 2391.81 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.284577E+10 | 2391.81 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.340493E+11 | 0.794337E+10 | ||||
Minimum of Months | 0.259798E+10 | 2391.81 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.296345E+10 | 2391.81 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133480E+09 | 111.81 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.121449E+09 | 111.81 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.138534E+09 | 111.81 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.130707E+09 | 111.81 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.136007E+09 | 111.81 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.133681E+09 | 111.81 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.133033E+09 | 111.81 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.138534E+09 | 111.81 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.130707E+09 | 111.81 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.133480E+09 | 111.81 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.129075E+09 | 111.81 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.133033E+09 | 111.81 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159172E+10 | 0.00 | 0.00 | ||
Minimum of Months | 0.121449E+09 | 111.81 | 0.00 | 0.00 | |
Maximum of Months | 0.138534E+09 | 111.81 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.699524E+09 | 0.379716E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163622E+09 | 0.171438E+09 |
February | 0.638757E+09 | 0.345492E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215377E+09 | 83485782.17 |
March | 0.730614E+09 | 0.394093E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358284E+09 | 0.163915E+09 |
April | 0.690691E+09 | 0.371828E+10 | 0.410339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331773E+09 | 67885220.02 |
May | 0.715069E+09 | 0.386905E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371206E+09 | 0.106938E+09 |
June | 0.705176E+09 | 0.380289E+10 | 0.416906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338640E+09 | 0.152663E+09 |
July | 0.700584E+09 | 0.378444E+10 | 0.419831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225002E+09 | 99730520.61 |
August | 0.730614E+09 | 0.394093E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281175E+09 | 0.134581E+09 |
September | 0.690691E+09 | 0.371828E+10 | 0.410229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202573E+09 | 74513588.82 |
October | 0.699524E+09 | 0.379716E+10 | 0.421210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170673E+09 | 87076177.08 |
November | 0.673027E+09 | 0.367184E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136596E+09 | 0.100210E+09 |
December | 0.700584E+09 | 0.378444E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129270E+09 | 0.182159E+09 |
Annual Sum or Average | 0.837485E+10 | 0.452803E+11 | 0.499923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292419E+10 | 0.142459E+10 |
Minimum of Months | 0.638757E+09 | 0.345492E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129270E+09 | 67885220.02 |
Maximum of Months | 0.730614E+09 | 0.394093E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371206E+09 | 0.182159E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.303025E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143204E+09 | 0.136999E+09 |
February | 0.201852E+11 | 0.275713E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189163E+09 | 56045451.87 |
March | 0.230879E+11 | 0.314498E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317695E+09 | 0.107002E+09 |
April | 0.218263E+11 | 0.296730E+11 | 0.691935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307305E+09 | 26387312.83 |
May | 0.225967E+11 | 0.308762E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359205E+09 | 45835846.22 |
June | 0.222841E+11 | 0.303482E+11 | 0.703008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319225E+09 | 53027600.56 |
July | 0.221389E+11 | 0.302010E+11 | 0.707940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202678E+09 | 47259789.54 |
August | 0.230879E+11 | 0.314498E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250806E+09 | 76006591.55 |
September | 0.218263E+11 | 0.296730E+11 | 0.691749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180302E+09 | 45745333.47 |
October | 0.221054E+11 | 0.303025E+11 | 0.710266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149033E+09 | 62874656.90 |
November | 0.212681E+11 | 0.293024E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119234E+09 | 76826130.11 |
December | 0.221389E+11 | 0.302010E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112167E+09 | 0.151628E+09 |
Annual Sum or Average | 0.264651E+12 | 0.361351E+12 | 0.842996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265002E+10 | 0.885638E+09 |
Minimum of Months | 0.201852E+11 | 0.275713E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112167E+09 | 26387312.83 |
Maximum of Months | 0.230879E+11 | 0.314498E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359205E+09 | 0.151628E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.285534E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72636609.54 | 0.120897E+09 |
February | 0.190200E+10 | 0.259798E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95731383.01 | 67911452.25 |
March | 0.217552E+10 | 0.296345E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159782E+09 | 0.118936E+09 |
April | 0.205665E+10 | 0.279602E+10 | 0.434394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148509E+09 | 43319732.63 |
May | 0.212923E+10 | 0.290940E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169331E+09 | 48294594.98 |
June | 0.209978E+10 | 0.285965E+10 | 0.441346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157041E+09 | 58111736.03 |
July | 0.208610E+10 | 0.284577E+10 | 0.444442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102610E+09 | 42838149.03 |
August | 0.217552E+10 | 0.296345E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128136E+09 | 66069101.58 |
September | 0.205665E+10 | 0.279602E+10 | 0.434278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90956941.30 | 45046973.24 |
October | 0.208295E+10 | 0.285534E+10 | 0.445903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76548935.38 | 59457021.48 |
November | 0.200405E+10 | 0.276110E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61058527.25 | 70985779.02 |
December | 0.208610E+10 | 0.284577E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58085035.46 | 0.119064E+09 |
Annual Sum or Average | 0.249375E+11 | 0.340493E+11 | 0.529230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132043E+10 | 0.860931E+09 |
Minimum of Months | 0.190200E+10 | 0.259798E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58085035.46 | 42838149.03 |
Maximum of Months | 0.217552E+10 | 0.296345E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169331E+09 | 0.120897E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.285534E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72896403.03 | 0.104991E+09 |
February | 0.190200E+10 | 0.259798E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96164403.33 | 55544140.99 |
March | 0.217552E+10 | 0.296345E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161267E+09 | 89198695.14 |
April | 0.205665E+10 | 0.279602E+10 | 0.651995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152216E+09 | 23619501.17 |
May | 0.212923E+10 | 0.290940E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175099E+09 | 31894897.94 |
June | 0.209978E+10 | 0.285965E+10 | 0.662429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159974E+09 | 39718894.01 |
July | 0.208610E+10 | 0.284577E+10 | 0.667077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103800E+09 | 32543334.77 |
August | 0.217552E+10 | 0.296345E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129477E+09 | 46980318.36 |
September | 0.205665E+10 | 0.279602E+10 | 0.651820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91870613.79 | 33854269.87 |
October | 0.208295E+10 | 0.285534E+10 | 0.669269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77028566.54 | 47241106.81 |
November | 0.200405E+10 | 0.276110E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61328374.97 | 59336352.43 |
December | 0.208610E+10 | 0.284577E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58185127.84 | 0.106097E+09 |
Annual Sum or Average | 0.249375E+11 | 0.340493E+11 | 0.794337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133931E+10 | 0.671020E+09 |
Minimum of Months | 0.190200E+10 | 0.259798E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58185127.84 | 23619501.17 |
Maximum of Months | 0.217552E+10 | 0.296345E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175099E+09 | 0.106097E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.165769E+09 | 0.133480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167559.66 | 0.427434E+09 |
February | 0.151369E+09 | 0.121449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14850425.84 | 0.244693E+09 |
March | 0.173136E+09 | 0.138534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136428E+09 | 0.123567E+09 |
April | 0.163676E+09 | 0.130707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240921E+09 | 40029836.40 |
May | 0.169453E+09 | 0.136007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291672E+09 | 78061579.88 |
June | 0.167108E+09 | 0.133681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256360E+09 | 71098485.92 |
July | 0.166020E+09 | 0.133033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88121537.31 | 0.147203E+09 |
August | 0.173136E+09 | 0.138534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146318E+09 | 0.127221E+09 |
September | 0.163676E+09 | 0.130707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75841179.11 | 0.145300E+09 |
October | 0.165769E+09 | 0.133480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15589173.71 | 0.231527E+09 |
November | 0.159490E+09 | 0.129075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2697317.10 | 0.371525E+09 |
December | 0.166020E+09 | 0.133033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357988.25 | 0.468529E+09 |
Annual Sum or Average | 0.198462E+10 | 0.159172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127033E+10 | 0.247619E+10 |
Minimum of Months | 0.151369E+09 | 0.121449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357988.25 | 40029836.40 |
Maximum of Months | 0.173136E+09 | 0.138534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291672E+09 | 0.468529E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 785.10 | 02-JAN-15:09 | 3180.74 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 597.91 | 08-JAN-19:02 | 2371.90 | 07-JAN-05:00 |
February | 785.10 | 01-FEB-15:09 | 3180.74 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.03 | 20-FEB-19:02 | 338.05 | 20-FEB-07:00 |
March | 785.10 | 01-MAR-15:09 | 3180.74 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.46 | 19-MAR-18:01 | 667.41 | 14-MAR-22:00 |
April | 785.10 | 01-APR-10:09 | 3180.74 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 986.77 | 02-APR-18:02 | 294.32 | 22-APR-03:20 |
May | 785.10 | 01-MAY-14:09 | 3180.74 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.21 | 07-MAY-18:02 | 1259.77 | 08-MAY-22:00 |
June | 785.10 | 01-JUN-14:09 | 3180.74 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.61 | 11-JUN-18:01 | 1569.36 | 20-JUN-23:00 |
July | 785.10 | 01-JUL-10:09 | 3180.74 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.49 | 25-JUL-20:02 | 517.33 | 19-JUL-21:10 |
August | 785.10 | 01-AUG-14:09 | 3180.74 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.05 | 01-AUG-20:02 | 702.69 | 04-AUG-03:00 |
September | 785.10 | 01-SEP-14:09 | 3180.74 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.28 | 10-SEP-14:55 | 562.50 | 15-SEP-22:00 |
October | 785.10 | 02-OCT-14:09 | 3180.74 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 832.73 | 08-OCT-18:02 | 423.84 | 01-OCT-23:00 |
November | 785.10 | 01-NOV-14:09 | 3180.74 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 | 10-NOV-13:00 | 437.92 | 25-NOV-05:00 |
December | 785.10 | 01-DEC-15:09 | 3180.74 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.64 | 09-DEC-14:00 | 777.24 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 785.10 | 3180.74 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 | 294.32 | |||||
Maximum of Months | 785.10 | 3180.74 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.46 | 2371.90 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 25383.25 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 520.71 | 08-JAN-19:02 | 2329.06 | 07-JAN-05:00 |
February | 24809.68 | 01-FEB-15:09 | 25383.25 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.41 | 20-FEB-19:02 | 258.17 | 20-FEB-07:00 |
March | 24809.68 | 01-MAR-15:09 | 25383.25 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.72 | 19-MAR-18:01 | 513.94 | 14-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 25383.25 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 865.60 | 02-APR-18:02 | 222.36 | 22-APR-03:10 |
May | 24809.68 | 01-MAY-14:09 | 25383.25 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.23 | 07-MAY-18:02 | 924.24 | 08-MAY-22:00 |
June | 24809.68 | 01-JUN-14:09 | 25383.25 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.30 | 11-JUN-18:01 | 1040.98 | 20-JUN-23:00 |
July | 24809.68 | 01-JUL-10:09 | 25383.25 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 586.22 | 25-JUL-20:02 | 319.09 | 19-JUL-21:10 |
August | 24809.68 | 01-AUG-14:09 | 25383.25 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 735.13 | 01-AUG-20:02 | 569.88 | 04-AUG-03:00 |
September | 24809.68 | 01-SEP-14:09 | 25383.25 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 525.87 | 10-SEP-14:55 | 541.01 | 15-SEP-22:00 |
October | 24809.68 | 02-OCT-14:09 | 25383.25 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 730.65 | 08-OCT-18:02 | 307.72 | 23-OCT-22:50 |
November | 24809.68 | 01-NOV-14:09 | 25383.25 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.74 | 10-NOV-13:00 | 385.91 | 25-NOV-05:00 |
December | 24809.68 | 01-DEC-15:09 | 25383.25 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.83 | 09-DEC-14:00 | 714.91 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 24809.68 | 25383.25 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 308.74 | 222.36 | |||||
Maximum of Months | 24809.68 | 25383.25 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.72 | 2329.06 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2391.81 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 261.05 | 08-JAN-19:02 | 1381.48 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2391.81 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 336.49 | 20-FEB-19:02 | 237.92 | 09-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 2391.81 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 742.50 | 19-MAR-18:01 | 357.76 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2391.81 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 444.07 | 02-APR-18:02 | 169.11 | 01-APR-02:00 |
May | 2337.76 | 01-MAY-14:09 | 2391.81 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 594.29 | 07-MAY-18:02 | 557.69 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2391.81 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 556.48 | 11-JUN-18:01 | 686.87 | 20-JUN-23:00 |
July | 2337.76 | 01-JUL-10:09 | 2391.81 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 299.02 | 25-JUL-20:02 | 221.61 | 19-JUL-20:20 |
August | 2337.76 | 01-AUG-14:09 | 2391.81 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.25 | 01-AUG-20:02 | 341.39 | 04-AUG-03:00 |
September | 2337.76 | 01-SEP-14:09 | 2391.81 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 | 10-SEP-14:55 | 289.06 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2391.81 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 366.87 | 08-OCT-18:02 | 263.96 | 29-OCT-19:20 |
November | 2337.76 | 01-NOV-14:09 | 2391.81 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 | 10-NOV-13:00 | 236.89 | 24-NOV-22:20 |
December | 2337.76 | 01-DEC-15:09 | 2391.81 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.38 | 09-DEC-14:00 | 429.31 | 20-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2391.81 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 | 169.11 | |||||
Maximum of Months | 2337.76 | 2391.81 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 742.50 | 1381.48 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2391.81 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.48 | 08-JAN-19:02 | 1267.62 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2391.81 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 338.91 | 20-FEB-19:02 | 198.79 | 09-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 2391.81 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 747.00 | 19-MAR-18:01 | 320.96 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2391.81 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 447.51 | 02-APR-18:02 | 119.92 | 01-APR-02:00 |
May | 2337.76 | 01-MAY-14:09 | 2391.81 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 597.67 | 07-MAY-18:02 | 495.74 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2391.81 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 558.90 | 11-JUN-18:01 | 606.28 | 20-JUN-23:00 |
July | 2337.76 | 01-JUL-10:09 | 2391.81 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 302.74 | 25-JUL-20:02 | 188.66 | 19-JUL-20:20 |
August | 2337.76 | 01-AUG-14:09 | 2391.81 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 378.56 | 01-AUG-20:02 | 270.92 | 23-AUG-20:20 |
September | 2337.76 | 01-SEP-14:09 | 2391.81 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 279.69 | 10-SEP-14:55 | 241.75 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2391.81 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 369.79 | 08-OCT-18:02 | 231.11 | 29-OCT-19:20 |
November | 2337.76 | 01-NOV-14:09 | 2391.81 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 | 10-NOV-13:00 | 214.37 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2391.81 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.38 | 09-DEC-14:00 | 392.71 | 20-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2337.76 | 2391.81 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 | 119.92 | |||||
Maximum of Months | 2337.76 | 2391.81 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 747.00 | 1267.62 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 186.05 | 02-JAN-15:09 | 111.81 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 11-JAN-08:65 | 1630.11 | 24-JAN-08:61 |
February | 186.05 | 01-FEB-15:09 | 111.81 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.23 | 26-FEB-12:55 | 1281.20 | 21-FEB-09:53 |
March | 186.05 | 01-MAR-15:09 | 111.81 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1973.08 | 03-MAR-12:02 | 1901.33 | 14-MAR-11:02 |
April | 186.05 | 01-APR-10:09 | 111.81 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.60 | 09-APR-11:02 | 1306.87 | 14-APR-15:53 |
May | 186.05 | 01-MAY-14:09 | 111.81 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.52 | 05-MAY-11:02 | 1924.15 | 01-MAY-12:52 |
June | 186.05 | 01-JUN-14:09 | 111.81 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.08 | 16-JUN-11:02 | 1644.33 | 30-JUN-12:53 |
July | 186.05 | 01-JUL-10:09 | 111.81 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.89 | 01-JUL-11:03 | 1628.66 | 03-JUL-12:53 |
August | 186.05 | 01-AUG-14:09 | 111.81 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1770.00 | 16-AUG-11:02 | 2050.43 | 25-AUG-11:02 |
September | 186.05 | 01-SEP-14:09 | 111.81 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.39 | 22-SEP-15:55 | 1731.01 | 15-SEP-16:53 |
October | 186.05 | 02-OCT-14:09 | 111.81 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.31 | 19-OCT-11:05 | 1231.00 | 29-OCT-16:53 |
November | 186.05 | 01-NOV-14:09 | 111.81 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.06 | 18-NOV-12:55 | 1316.89 | 25-NOV-12:02 |
December | 186.05 | 01-DEC-15:09 | 111.81 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.32 | 29-DEC-18:55 | 1309.84 | 21-DEC-08:61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 186.05 | 111.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.32 | 1231.00 | ||||
Maximum of Months | 186.05 | 111.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.52 | 2050.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39466.71 | 18-JAN-05:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 |
February | 43202.41 | 23-FEB-05:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.41 |
March | 36254.94 | 03-MAR-05:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.25 |
April | 34117.91 | 27-APR-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.24 |
May | 36535.73 | 11-MAY-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.19 |
June | 37770.99 | 20-JUN-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.00 |
July | 40299.11 | 19-JUL-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36390.78 | 16-AUG-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 |
September | 35606.83 | 12-SEP-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 |
October | 34696.68 | 11-OCT-04:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 |
November | 36120.77 | 25-NOV-05:01 | 0.00 | 1590.37 | 4138.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.18 |
December | 37511.34 | 27-DEC-05:01 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 34117.91 | 0.00 | 1590.37 | 4138.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43202.41 | 0.00 | 1767.08 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 163058.61 | 23-JAN-05:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.71 |
February | 162223.62 | 23-FEB-05:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.25 |
March | 156680.44 | 03-MAR-05:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.18 |
April | 142874.39 | 27-APR-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 |
May | 137637.52 | 11-MAY-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.73 |
June | 139189.49 | 20-JUN-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.62 |
July | 144423.56 | 31-JUL-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.86 |
August | 138802.68 | 24-AUG-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.47 |
September | 138454.21 | 13-SEP-04:01 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 |
October | 136321.98 | 09-OCT-06:01 | 0.00 | 14101.81 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 |
November | 155244.02 | 25-NOV-05:01 | 0.00 | 12691.63 | 6978.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.87 |
December | 165180.82 | 21-DEC-05:01 | 0.00 | 11281.45 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 136321.98 | 0.00 | 11281.45 | 6978.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 | |
Maximum of Months | 165180.82 | 0.00 | 14101.81 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25310.52 | 18-JAN-05:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 |
February | 27136.49 | 23-FEB-05:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 |
March | 22057.22 | 03-MAR-05:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.54 |
April | 19843.04 | 27-APR-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 |
May | 20424.41 | 11-MAY-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 |
June | 20452.03 | 20-JUN-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.64 |
July | 22476.79 | 19-JUL-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20385.82 | 16-AUG-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
September | 20747.99 | 12-SEP-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 |
October | 21040.08 | 11-OCT-04:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 |
November | 22388.11 | 25-NOV-05:01 | 0.00 | 1195.90 | 4381.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.30 |
December | 24118.25 | 27-DEC-05:01 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19843.04 | 0.00 | 1195.90 | 4381.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27136.49 | 0.00 | 1328.78 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21859.71 | 18-JAN-05:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
February | 23397.50 | 23-FEB-05:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 |
March | 19162.20 | 03-MAR-05:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.76 |
April | 16951.62 | 27-APR-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
May | 17242.51 | 11-MAY-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 |
June | 17552.60 | 20-JUN-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.81 |
July | 18905.68 | 19-JUL-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17352.83 | 16-AUG-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
September | 17502.69 | 12-SEP-04:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 |
October | 17941.45 | 08-OCT-06:01 | 0.00 | 1328.78 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.14 |
November | 19700.21 | 25-NOV-05:01 | 0.00 | 1195.90 | 657.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.30 |
December | 21059.94 | 27-DEC-05:01 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16951.62 | 0.00 | 1195.90 | 657.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23397.50 | 0.00 | 1328.78 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.86 |
April | 0.00 | 01-APR-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | |
Maximum of Months | 0.00 | 0.00 | 6.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.194393E+12 | 143821.86 | 04-JAN-12:00 | 0.713522E+10 | 4791.82 | 06-JAN-12:30 |
February | 0.183328E+12 | 149710.10 | 28-FEB-14:00 | 0.644763E+10 | 4790.77 | 02-FEB-12:39 |
March | 0.212808E+12 | 153028.01 | 28-MAR-14:39 | 0.715093E+10 | 4786.07 | 02-MAR-12:39 |
April | 0.212576E+12 | 157360.63 | 01-APR-13:00 | 0.685348E+10 | 4777.52 | 03-APR-11:09 |
May | 0.224582E+12 | 165355.96 | 06-MAY-14:00 | 0.704920E+10 | 4769.26 | 01-MAY-11:00 |
June | 0.222667E+12 | 165949.88 | 13-JUN-14:00 | 0.681542E+10 | 4761.60 | 01-JUN-11:09 |
July | 0.203404E+12 | 148345.49 | 21-JUL-14:00 | 0.699071E+10 | 4757.70 | 31-JUL-11:50 |
August | 0.215160E+12 | 156212.73 | 11-AUG-14:09 | 0.705470E+10 | 4762.46 | 31-AUG-11:50 |
September | 0.205271E+12 | 155754.17 | 30-SEP-10:00 | 0.682688E+10 | 4770.01 | 29-SEP-11:20 |
October | 0.202556E+12 | 149072.69 | 04-OCT-14:09 | 0.706907E+10 | 4779.57 | 31-OCT-11:50 |
November | 0.193224E+12 | 147304.79 | 18-NOV-12:00 | 0.686832E+10 | 4787.26 | 30-NOV-12:09 |
December | 0.194146E+12 | 143576.22 | 30-DEC-13:00 | 0.713190E+10 | 4791.00 | 27-DEC-12:09 |
Annual Sum or Average | 0.246411E+13 | 0.833935E+11 | ||||
Minimum of Months | 0.183328E+12 | 143576.22 | 0.644763E+10 | 4757.70 | ||
Maximum of Months | 0.224582E+12 | 165949.88 | 0.715093E+10 | 4791.82 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.399439E+11 | 0.112080E+11 | 0.164409E+11 | 0.00 | 0.368589E+11 | 0.00 | 0.00 | 0.899411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363436E+11 | 0.996530E+10 | 0.149157E+11 | 0.00 | 0.335362E+11 | 0.00 | 0.00 | 0.885670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414562E+11 | 0.106946E+11 | 0.168545E+11 | 0.00 | 0.377605E+11 | 0.00 | 0.00 | 0.106042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391141E+11 | 0.101044E+11 | 0.160187E+11 | 0.00 | 0.364049E+11 | 0.00 | 0.00 | 0.110934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.407000E+11 | 0.102628E+11 | 0.166477E+11 | 0.00 | 0.376977E+11 | 0.00 | 0.00 | 0.119274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.400041E+11 | 0.981656E+10 | 0.162750E+11 | 0.00 | 0.368167E+11 | 0.00 | 0.00 | 0.119755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.398100E+11 | 0.102244E+11 | 0.163892E+11 | 0.00 | 0.371436E+11 | 0.00 | 0.00 | 0.998366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414562E+11 | 0.103539E+11 | 0.168545E+11 | 0.00 | 0.377939E+11 | 0.00 | 0.00 | 0.108701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.391141E+11 | 0.102772E+11 | 0.160144E+11 | 0.00 | 0.362815E+11 | 0.00 | 0.00 | 0.103584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399439E+11 | 0.108961E+11 | 0.164431E+11 | 0.00 | 0.370101E+11 | 0.00 | 0.00 | 0.982631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386255E+11 | 0.107570E+11 | 0.159174E+11 | 0.00 | 0.356201E+11 | 0.00 | 0.00 | 0.923035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398100E+11 | 0.112799E+11 | 0.163871E+11 | 0.00 | 0.369187E+11 | 0.00 | 0.00 | 0.897500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476322E+12 | 0.125840E+12 | 0.195158E+12 | 0.00 | 0.439843E+12 | 0.00 | 0.00 | 0.122695E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.363436E+11 | 0.981656E+10 | 0.149157E+11 | 0.00 | 0.335362E+11 | 0.00 | 0.00 | 0.885670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.414562E+11 | 0.112799E+11 | 0.168545E+11 | 0.00 | 0.377939E+11 | 0.00 | 0.00 | 0.119755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.713522E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.644763E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.715093E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.685348E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.704920E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.681542E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.699071E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.705470E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.682688E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.706907E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.686832E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.713190E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.833935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.644763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.715093E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33459.42 | 02-JAN-09:09 | 7996.55 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 22605.52 | 18-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33459.42 | 01-FEB-09:09 | 7996.55 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 22605.52 | 08-FEB-06:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33459.42 | 01-MAR-09:09 | 7996.55 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 22605.52 | 03-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33459.42 | 01-APR-09:09 | 7996.55 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 22605.52 | 01-APR-05:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33459.42 | 01-MAY-08:09 | 7996.55 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 22605.52 | 08-MAY-12:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33459.42 | 01-JUN-08:09 | 7996.55 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 22605.52 | 09-JUN-12:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33459.42 | 01-JUL-09:09 | 7996.55 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 22605.52 | 01-JUL-05:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33459.42 | 01-AUG-08:09 | 7996.55 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 22605.52 | 14-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33459.42 | 01-SEP-08:09 | 7996.55 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 22605.52 | 01-SEP-05:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33459.42 | 02-OCT-08:09 | 7996.55 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 22605.52 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33459.42 | 01-NOV-08:09 | 7996.55 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 22605.52 | 16-NOV-20:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33459.42 | 01-DEC-09:09 | 7996.55 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 22605.52 | 07-DEC-06:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 33459.42 | 7996.55 | 10771.04 | 0.00 | 22605.52 | 0.00 | 0.00 | |||||
Maximum of Months | 33459.42 | 7996.55 | 10771.04 | 0.00 | 22605.52 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 76985.89 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82874.13 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86192.04 | 28-MAR-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 90524.65 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98519.99 | 06-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99113.91 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81509.52 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89376.76 | 11-AUG-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88918.20 | 30-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82236.72 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80468.82 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76740.25 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 76740.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99113.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 143821.86 | 04-JAN-12:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 76985.89 | 0.00 |
February | 149710.10 | 28-FEB-14:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 82874.13 | 0.00 |
March | 153028.01 | 28-MAR-14:39 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 86192.04 | 0.00 |
April | 157360.63 | 01-APR-13:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 90524.65 | 0.00 |
May | 165355.96 | 06-MAY-14:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 98519.99 | 0.00 |
June | 165949.88 | 13-JUN-14:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 99113.91 | 0.00 |
July | 148345.49 | 21-JUL-14:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 81509.52 | 0.00 |
August | 156212.73 | 11-AUG-14:09 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 89376.76 | 0.00 |
September | 155754.17 | 30-SEP-10:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 88918.20 | 0.00 |
October | 149072.69 | 04-OCT-14:09 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 82236.72 | 0.00 |
November | 147304.79 | 18-NOV-12:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 80468.82 | 0.00 |
December | 143576.22 | 30-DEC-13:00 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 76740.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 143576.22 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 76740.25 | 0.00 | |
Maximum of Months | 165949.88 | 33459.42 | 10771.04 | 0.00 | 0.00 | 22605.52 | 0.00 | 0.00 | 99113.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4791.82 | 06-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4790.77 | 02-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4786.07 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4777.52 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4769.26 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4761.60 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4757.70 | 31-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4762.46 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4770.01 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4779.57 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4787.26 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4791.00 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4757.70 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4791.82 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.58 | 0.00 | 24.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 24.66 | 0.00 | 24.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.92 | 0.00 | 24.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 25.14 | 0.00 | 25.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 25.52 | 0.00 | 25.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 25.82 | 0.00 | 25.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.03 | 0.00 | 25.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.15 | 0.00 | 25.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.91 | 0.00 | 24.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.76 | 0.00 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.67 | 0.00 | 24.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.57 | 0.00 | 24.57 |
Annual Sum or Average | 0.00 | 0.00 | 118.33 | 25.10 | 0.00 | 25.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.57 | 0.00 | 24.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 25.82 | 0.00 | 25.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.49 | 0.00 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.52 | 0.00 | 24.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.68 | 0.00 | 24.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.81 | 0.00 | 24.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.78 | 0.00 | 24.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.77 | 0.00 | 24.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.69 | 0.00 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.68 | 0.00 | 24.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.59 | 0.00 | 24.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.54 | 0.00 | 24.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.50 | 0.00 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 85.83 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.49 | 0.00 | 24.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.81 | 0.00 | 24.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.90 | 0.00 | 24.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 24.98 | 0.00 | 24.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.08 | 0.00 | 25.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.17 | 0.00 | 25.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.19 | 0.00 | 25.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.15 | 0.00 | 25.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.85 | 0.00 | 24.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.99 | 0.00 | 24.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.00 | 0.00 | 25.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.94 | 0.00 | 24.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.93 | 0.00 | 24.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.87 | 0.00 | 24.87 |
Annual Sum or Average | 0.00 | 0.00 | 111.83 | 25.01 | 0.00 | 25.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.85 | 0.00 | 24.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.19 | 0.00 | 25.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.79 | 0.00 | 24.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.83 | 0.00 | 24.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.92 | 0.00 | 24.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.98 | 0.00 | 24.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.07 | 0.00 | 25.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.01 | 0.00 | 25.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.86 | 0.00 | 24.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.86 | 0.00 | 24.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.81 | 0.00 | 24.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.82 | 0.00 | 24.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.80 | 0.00 | 24.80 |
Annual Sum or Average | 0.00 | 0.00 | 100.83 | 24.89 | 0.00 | 24.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.74 | 0.00 | 24.74 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.07 | 0.00 | 25.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 23.89 |
April | 3.83 | 23.89 | 405.00 | 23.89 | 3.83 | 23.89 |
May | 29.83 | 23.89 | 418.00 | 23.89 | 29.83 | 23.89 |
June | 3.33 | 23.89 | 408.00 | 23.89 | 3.33 | 23.89 |
July | 2.00 | 23.89 | 415.00 | 23.89 | 2.00 | 23.89 |
August | 37.00 | 23.89 | 422.00 | 23.89 | 37.00 | 23.89 |
September | 11.00 | 23.89 | 405.00 | 23.89 | 11.00 | 23.89 |
October | 26.33 | 23.89 | 414.00 | 23.89 | 26.33 | 23.89 |
November | 2.67 | 23.89 | 399.00 | 23.89 | 2.67 | 23.89 |
December | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 116.00 | 23.89 | 4913.00 | 23.89 | 116.00 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 37.00 | 23.89 | 422.00 | 23.89 | 37.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 23.89 | 414.00 | 23.89 | 19.67 | 23.89 |
February | 6.17 | 23.89 | 376.00 | 23.89 | 6.17 | 23.89 |
March | 18.17 | 23.89 | 422.00 | 23.89 | 18.17 | 23.89 |
April | 103.50 | 23.89 | 405.00 | 23.89 | 103.50 | 23.89 |
May | 263.33 | 23.89 | 418.00 | 23.89 | 263.33 | 23.89 |
June | 247.50 | 23.89 | 408.00 | 23.89 | 247.50 | 23.89 |
July | 96.67 | 23.89 | 415.00 | 23.89 | 96.67 | 23.89 |
August | 322.33 | 23.89 | 422.00 | 23.89 | 322.33 | 23.89 |
September | 258.17 | 23.89 | 405.00 | 23.89 | 258.17 | 23.89 |
October | 273.17 | 23.89 | 414.00 | 23.89 | 273.17 | 23.89 |
November | 129.67 | 23.89 | 399.00 | 23.89 | 129.67 | 23.89 |
December | 56.17 | 23.89 | 415.00 | 23.89 | 56.17 | 23.89 |
Annual Sum or Average | 1794.50 | 23.89 | 4913.00 | 23.89 | 1794.50 | 23.89 |
Minimum of Months | 6.17 | 23.89 | 376.00 | 23.89 | 6.17 | 23.89 |
Maximum of Months | 322.33 | 23.89 | 422.00 | 23.89 | 322.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 23.89 | 414.00 | 23.89 | 0.50 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 23.89 |
April | 6.50 | 23.89 | 405.00 | 23.89 | 6.50 | 23.89 |
May | 66.83 | 23.89 | 418.00 | 23.89 | 66.83 | 23.89 |
June | 44.33 | 23.89 | 408.00 | 23.89 | 44.33 | 23.89 |
July | 2.50 | 23.89 | 415.00 | 23.89 | 2.50 | 23.89 |
August | 83.67 | 23.89 | 422.00 | 23.89 | 83.67 | 23.89 |
September | 34.50 | 23.89 | 405.00 | 23.89 | 34.50 | 23.89 |
October | 28.83 | 23.89 | 414.00 | 23.89 | 28.83 | 23.89 |
November | 1.50 | 23.89 | 399.00 | 23.89 | 1.50 | 23.89 |
December | 0.33 | 23.89 | 415.00 | 23.89 | 0.33 | 23.89 |
Annual Sum or Average | 269.50 | 23.89 | 4913.00 | 23.89 | 269.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 83.67 | 23.89 | 422.00 | 23.89 | 83.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 23.89 | 414.00 | 23.89 | 2.50 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
March | 2.83 | 23.89 | 422.00 | 23.89 | 2.83 | 23.89 |
April | 27.17 | 23.89 | 405.00 | 23.89 | 27.17 | 23.89 |
May | 115.00 | 23.89 | 418.00 | 23.89 | 115.00 | 23.89 |
June | 87.50 | 23.89 | 408.00 | 23.89 | 87.50 | 23.89 |
July | 27.67 | 23.89 | 415.00 | 23.89 | 27.67 | 23.89 |
August | 160.83 | 23.89 | 422.00 | 23.89 | 160.83 | 23.89 |
September | 71.83 | 23.89 | 405.00 | 23.89 | 71.83 | 23.89 |
October | 82.50 | 23.89 | 414.00 | 23.89 | 82.50 | 23.89 |
November | 11.00 | 23.89 | 399.00 | 23.89 | 11.00 | 23.89 |
December | 3.50 | 23.89 | 415.00 | 23.89 | 3.50 | 23.89 |
Annual Sum or Average | 592.33 | 23.89 | 4913.00 | 23.89 | 592.33 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 160.83 | 23.89 | 422.00 | 23.89 | 160.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.17 | 29.59 | 414.00 | 29.58 | 412.17 | 29.58 |
February | 376.00 | 30.31 | 376.00 | 30.31 | 376.00 | 30.31 |
March | 422.00 | 30.55 | 422.00 | 30.55 | 422.00 | 30.55 |
April | 405.00 | 30.66 | 405.00 | 30.66 | 405.00 | 30.66 |
May | 418.00 | 30.57 | 418.00 | 30.57 | 418.00 | 30.57 |
June | 408.00 | 30.64 | 408.00 | 30.64 | 408.00 | 30.64 |
July | 415.00 | 28.98 | 415.00 | 28.98 | 415.00 | 28.98 |
August | 422.00 | 29.09 | 422.00 | 29.09 | 422.00 | 29.09 |
September | 405.00 | 29.26 | 405.00 | 29.26 | 405.00 | 29.26 |
October | 414.00 | 28.73 | 414.00 | 28.73 | 414.00 | 28.73 |
November | 399.00 | 29.02 | 399.00 | 29.02 | 399.00 | 29.02 |
December | 415.00 | 29.23 | 415.00 | 29.23 | 415.00 | 29.23 |
Annual Sum or Average | 4911.17 | 29.72 | 4913.00 | 29.72 | 4911.17 | 29.72 |
Minimum of Months | 376.00 | 28.73 | 376.00 | 28.73 | 376.00 | 28.73 |
Maximum of Months | 422.00 | 30.66 | 422.00 | 30.66 | 422.00 | 30.66 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89001 | 53.11826 | 0.61324 | 12.92247 |
February | 376.00000 | 23.89005 | 52.65183 | 0.64124 | 13.66580 |
March | 422.00000 | 23.89005 | 53.24587 | 0.66479 | 14.33371 |
April | 405.00000 | 23.89001 | 55.24476 | 0.70292 | 15.43028 |
May | 418.00000 | 23.89018 | 57.09317 | -0.0699 | 5.26194 |
June | 408.00000 | 23.89034 | 55.65277 | -0.0272 | 5.18260 |
July | 415.00000 | 23.89003 | 54.02000 | -0.1176 | 5.37792 |
August | 422.00000 | 23.89001 | 58.88746 | -0.1273 | 5.50568 |
September | 405.00000 | 23.89001 | 58.04117 | -0.1379 | 5.49755 |
October | 414.00000 | 23.89001 | 59.08792 | 0.65191 | 13.96647 |
November | 399.00000 | 23.89001 | 56.57444 | 0.64029 | 13.63830 |
December | 415.00000 | 23.89000 | 54.73887 | 0.61288 | 12.90995 |
Annual Sum or Average | 4913.00000 | 23.89006 | 55.71564 | 0.33406 | 10.27142 |
Minimum of Months | 376.00000 | 23.89000 | 52.65183 | -0.1379 | 5.18260 |
Maximum of Months | 422.00000 | 23.89034 | 59.08792 | 0.70292 | 15.43028 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89001 | 58.00963 | 0.66665 | 14.38070 |
February | 376.00000 | 23.89001 | 57.95943 | 0.68804 | 15.00114 |
March | 422.00000 | 23.89001 | 58.59051 | 0.70789 | 15.59794 |
April | 405.00000 | 23.89001 | 62.32113 | 0.74002 | 16.57342 |
May | 418.00000 | 23.89001 | 65.86390 | -0.0669 | 5.18630 |
June | 408.00000 | 23.89001 | 65.54604 | -0.0493 | 5.14914 |
July | 415.00000 | 23.89001 | 62.27785 | -0.1139 | 5.34270 |
August | 422.00000 | 23.89001 | 66.73187 | -0.0931 | 5.30299 |
September | 405.00000 | 23.89001 | 65.64075 | -0.0899 | 5.26507 |
October | 414.00000 | 23.89002 | 65.81807 | 0.70994 | 15.64122 |
November | 399.00000 | 23.89001 | 62.99293 | 0.69596 | 15.22026 |
December | 415.00000 | 23.89001 | 60.00599 | 0.67106 | 14.50112 |
Annual Sum or Average | 4913.00000 | 23.89001 | 62.67533 | 0.36885 | 11.05456 |
Minimum of Months | 376.00000 | 23.89001 | 57.95943 | -0.1139 | 5.14914 |
Maximum of Months | 422.00000 | 23.89002 | 66.73187 | 0.74002 | 16.57342 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89038 | 50.81563 | 0.77967 | 17.92761 |
February | 376.00000 | 23.89037 | 51.13946 | 0.79246 | 18.34330 |
March | 422.00000 | 23.89015 | 53.06019 | 0.77214 | 17.66290 |
April | 405.00000 | 23.89001 | 57.04312 | 0.76861 | 17.50678 |
May | 418.00000 | 23.89005 | 59.86206 | -0.0081 | 5.16744 |
June | 408.00000 | 23.89004 | 59.66705 | 0.00507 | 5.15180 |
July | 415.00000 | 23.89001 | 56.91895 | -0.0631 | 5.19736 |
August | 422.00000 | 23.89001 | 61.14329 | -0.0547 | 5.26096 |
September | 405.00000 | 23.89002 | 59.15469 | -0.0259 | 5.19972 |
October | 414.00000 | 23.89002 | 58.57380 | 0.75459 | 17.09335 |
November | 399.00000 | 23.89007 | 54.84297 | 0.77605 | 17.78969 |
December | 415.00000 | 23.89025 | 52.12532 | 0.77807 | 17.87122 |
Annual Sum or Average | 4913.00000 | 23.89011 | 56.23282 | 0.43594 | 12.45659 |
Minimum of Months | 376.00000 | 23.89001 | 50.81563 | -0.0631 | 5.15180 |
Maximum of Months | 422.00000 | 23.89038 | 61.14329 | 0.79246 | 18.34330 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89019 | 51.71078 | 0.76017 | 17.28549 |
February | 376.00000 | 23.89021 | 51.95615 | 0.77293 | 17.69412 |
March | 422.00000 | 23.89007 | 54.20832 | 0.75305 | 17.04520 |
April | 405.00000 | 23.89001 | 58.56090 | 0.75377 | 17.02473 |
May | 418.00000 | 23.89004 | 61.68512 | -0.0308 | 5.17859 |
June | 408.00000 | 23.89002 | 61.34708 | -0.0171 | 5.15443 |
July | 415.00000 | 23.89001 | 58.70940 | -0.0871 | 5.26733 |
August | 422.00000 | 23.89002 | 63.40176 | -0.0747 | 5.30350 |
September | 405.00000 | 23.89001 | 61.05106 | -0.0483 | 5.22521 |
October | 414.00000 | 23.89001 | 60.59496 | 0.74197 | 16.68154 |
November | 399.00000 | 23.89001 | 56.23150 | 0.75984 | 17.25294 |
December | 415.00000 | 23.89017 | 53.18395 | 0.75968 | 17.26562 |
Annual Sum or Average | 4913.00000 | 23.89006 | 57.76318 | 0.41663 | 12.14339 |
Minimum of Months | 376.00000 | 23.89001 | 51.71078 | -0.0871 | 5.15443 |
Maximum of Months | 422.00000 | 23.89021 | 63.40176 | 0.77293 | 17.69412 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 29.56674 | 59.57550 | 1.93797 | 71.81329 |
February | 376.00000 | 30.31379 | 58.62884 | 2.08109 | 77.22716 |
March | 422.00000 | 30.54787 | 59.86854 | 2.07901 | 76.72196 |
April | 405.00000 | 30.65618 | 68.66505 | 2.14641 | 79.74925 |
May | 418.00000 | 30.57494 | 76.71003 | 1.86019 | 65.64716 |
June | 408.00000 | 30.63712 | 77.05291 | 1.89714 | 67.10385 |
July | 415.00000 | 28.97515 | 72.28579 | 1.33624 | 44.16844 |
August | 422.00000 | 29.08766 | 82.38927 | 1.44108 | 49.09479 |
September | 405.00000 | 29.26338 | 79.57874 | 1.51702 | 52.41406 |
October | 414.00000 | 28.73241 | 79.63184 | 1.84910 | 67.86640 |
November | 399.00000 | 29.02409 | 72.43234 | 1.90989 | 70.61949 |
December | 415.00000 | 29.23339 | 64.44548 | 1.90952 | 70.59730 |
Annual Sum or Average | 4913.00000 | 29.71400 | 71.01449 | 1.82783 | 65.96976 |
Minimum of Months | 376.00000 | 28.73241 | 58.62884 | 1.33624 | 44.16844 |
Maximum of Months | 422.00000 | 30.65618 | 82.38927 | 2.14641 | 79.74925 |
Report: DXReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.375033E+11 | 0.117802E+11 | 467.22 | 0.279835E+11 | 0.951980E+10 | 0.00 | 1.00 | 01-JAN-07:01 | 0.00 | 01-JAN-00:10 | 58928.00 | 09-JAN-05:01 | 41094.08 | 18-JAN-05:01 | 29544.39 | 09-JAN-05:06 | 14005.41 | 04-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.379744E+11 | 0.119517E+11 | 425.28 | 0.286390E+11 | 0.933539E+10 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:10 | 58693.28 | 20-FEB-07:01 | 46127.84 | 23-FEB-05:01 | 28004.29 | 20-FEB-07:06 | 14101.69 | 20-FEB-07:42 | 0.00 | 01-FEB-00:10 |
March | 0.470376E+11 | 0.147416E+11 | 478.04 | 0.347883E+11 | 0.122494E+11 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 59611.65 | 27-MAR-04:01 | 38626.07 | 03-MAR-05:01 | 30584.44 | 27-MAR-04:08 | 14368.80 | 28-MAR-04:09 | 0.00 | 01-MAR-00:10 |
April | 0.514910E+11 | 0.158520E+11 | 459.58 | 0.361790E+11 | 0.153121E+11 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 59567.46 | 06-APR-04:01 | 37241.19 | 28-APR-04:01 | 31821.16 | 03-APR-04:07 | 14434.42 | 30-APR-06:42 | 0.00 | 01-APR-00:10 |
May | 0.583060E+11 | 0.175760E+11 | 475.24 | 0.390312E+11 | 0.192748E+11 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 59686.88 | 17-MAY-04:01 | 38963.75 | 11-MAY-04:01 | 37663.88 | 22-MAY-04:07 | 15328.87 | 28-MAY-06:55 | 0.00 | 01-MAY-00:10 |
June | 0.614172E+11 | 0.182800E+11 | 467.53 | 0.417837E+11 | 0.196336E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 59627.76 | 08-JUN-04:01 | 39964.67 | 20-JUN-04:01 | 35164.25 | 10-JUN-04:10 | 15044.10 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.492387E+11 | 0.148805E+11 | 471.28 | 0.353163E+11 | 0.139225E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 58855.70 | 21-JUL-04:01 | 43331.80 | 19-JUL-04:01 | 27560.10 | 01-JUL-04:04 | 14181.27 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 |
August | 0.514866E+11 | 0.153811E+11 | 477.32 | 0.333839E+11 | 0.181027E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 59688.99 | 06-AUG-06:01 | 39035.91 | 16-AUG-04:01 | 34613.26 | 13-AUG-06:08 | 14682.25 | 02-AUG-04:10 | 0.00 | 01-AUG-00:10 |
September | 0.473577E+11 | 0.142980E+11 | 458.92 | 0.314630E+11 | 0.158947E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 59658.72 | 02-SEP-04:01 | 38917.33 | 12-SEP-04:01 | 30741.78 | 02-SEP-04:08 | 14367.11 | 03-SEP-06:43 | 0.00 | 01-SEP-00:10 |
October | 0.430042E+11 | 0.130388E+11 | 469.30 | 0.281865E+11 | 0.148178E+11 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 59474.65 | 30-OCT-04:01 | 37449.20 | 08-OCT-06:01 | 30722.08 | 30-OCT-04:07 | 14181.28 | 05-OCT-04:14 | 0.00 | 01-OCT-00:10 |
November | 0.397612E+11 | 0.121875E+11 | 451.65 | 0.273790E+11 | 0.123822E+11 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 58514.90 | 13-NOV-05:01 | 38752.10 | 07-NOV-05:01 | 28433.81 | 12-NOV-07:13 | 14212.84 | 23-NOV-07:42 | 0.00 | 01-NOV-00:10 |
December | 0.370896E+11 | 0.115596E+11 | 467.49 | 0.267937E+11 | 0.102959E+11 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 58709.01 | 11-DEC-05:01 | 39204.03 | 07-DEC-05:01 | 28988.99 | 11-DEC-05:06 | 14019.12 | 10-DEC-07:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.561668E+12 | 0.171527E+12 | 5568.85 | 0.390927E+12 | 0.170741E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.370896E+11 | 0.115596E+11 | 425.28 | 0.267937E+11 | 0.933539E+10 | 0.00 | 1.00 | 0.00 | 58514.90 | 37241.19 | 27560.10 | 14005.41 | 0.00 | |||||||
Maximum of Months | 0.614172E+11 | 0.182800E+11 | 478.04 | 0.417837E+11 | 0.196336E+11 | 0.00 | 1.00 | 0.00 | 59688.99 | 46127.84 | 37663.88 | 15328.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.192461E+12 | 0.612245E+11 | 465.96 | 0.126692E+12 | 0.657695E+11 | 0.00 | 1.00 | 01-JAN-07:01 | 0.00 | 01-JAN-00:10 | 253665.47 | 10-JAN-05:01 | 163629.64 | 24-JAN-05:01 | 115762.85 | 02-JAN-05:04 | 64844.44 | 03-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.189587E+12 | 0.603914E+11 | 423.87 | 0.125359E+12 | 0.642289E+11 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:10 | 253665.24 | 16-FEB-05:01 | 174146.20 | 23-FEB-05:01 | 111113.96 | 16-FEB-05:12 | 65014.29 | 16-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.229998E+12 | 0.731316E+11 | 475.82 | 0.150342E+12 | 0.796562E+11 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 256278.63 | 28-MAR-04:01 | 165889.19 | 03-MAR-05:01 | 116440.49 | 25-MAR-04:06 | 66544.66 | 28-MAR-04:05 | 0.00 | 01-MAR-00:10 |
April | 0.248819E+12 | 0.771413E+11 | 458.17 | 0.149384E+12 | 0.994351E+11 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 258636.83 | 03-APR-04:01 | 160573.56 | 27-APR-04:01 | 121500.39 | 30-APR-06:07 | 66850.05 | 30-APR-06:42 | 0.00 | 01-APR-00:10 |
May | 0.271688E+12 | 0.824661E+11 | 473.12 | 0.150129E+12 | 0.121559E+12 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 261915.45 | 20-MAY-04:01 | 148796.56 | 11-MAY-04:01 | 146629.55 | 22-MAY-04:12 | 69862.42 | 28-MAY-06:43 | 0.00 | 01-MAY-00:10 |
June | 0.273443E+12 | 0.823816E+11 | 461.62 | 0.150491E+12 | 0.122952E+12 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 261681.97 | 11-JUN-06:02 | 149087.63 | 20-JUN-04:01 | 139296.32 | 10-JUN-04:09 | 67999.95 | 13-JUN-14:40 | 0.00 | 01-JUN-00:10 |
July | 0.223710E+12 | 0.689695E+11 | 468.74 | 0.133127E+12 | 0.905832E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 255581.77 | 01-JUL-04:01 | 157489.39 | 03-JUL-04:01 | 120345.20 | 01-JUL-04:04 | 65675.58 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 |
August | 0.254133E+12 | 0.760083E+11 | 475.98 | 0.135867E+12 | 0.118266E+12 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 261399.35 | 13-AUG-06:01 | 149805.12 | 24-AUG-04:01 | 135983.09 | 13-AUG-06:06 | 68046.96 | 02-AUG-04:07 | 0.00 | 01-AUG-00:10 |
September | 0.239907E+12 | 0.722806E+11 | 457.11 | 0.132111E+12 | 0.107796E+12 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 258433.95 | 05-SEP-04:01 | 151274.42 | 12-SEP-04:01 | 126018.82 | 17-SEP-06:04 | 66328.01 | 05-SEP-04:42 | 0.00 | 01-SEP-00:10 |
October | 0.226737E+12 | 0.685770E+11 | 466.99 | 0.124672E+12 | 0.102064E+12 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 256561.49 | 26-OCT-04:01 | 148171.34 | 09-OCT-06:01 | 125377.43 | 26-OCT-04:13 | 65675.39 | 16-OCT-04:03 | 0.00 | 01-OCT-00:10 |
November | 0.206673E+12 | 0.635312E+11 | 449.98 | 0.120888E+12 | 0.857855E+11 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 255922.41 | 12-NOV-07:01 | 157722.20 | 25-NOV-05:01 | 123575.12 | 12-NOV-07:13 | 65675.61 | 14-NOV-05:02 | 0.00 | 01-NOV-00:10 |
December | 0.195184E+12 | 0.613145E+11 | 466.85 | 0.122845E+12 | 0.723384E+11 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 255104.62 | 11-DEC-05:01 | 164259.89 | 21-DEC-05:01 | 122372.90 | 11-DEC-05:05 | 65094.59 | 10-DEC-07:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.275234E+13 | 0.847418E+12 | 5544.21 | 0.162191E+13 | 0.113043E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.189587E+12 | 0.603914E+11 | 423.87 | 0.120888E+12 | 0.642289E+11 | 0.00 | 1.00 | 0.00 | 253665.24 | 148171.34 | 111113.96 | 64844.44 | 0.00 | |||||||
Maximum of Months | 0.273443E+12 | 0.824661E+11 | 475.98 | 0.150491E+12 | 0.122952E+12 | 0.00 | 1.00 | 0.00 | 261915.45 | 174146.20 | 146629.55 | 69862.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.315160E+11 | 0.894039E+10 | 468.48 | 0.232547E+11 | 0.826132E+10 | 0.00 | 1.00 | 01-JAN-07:01 | 0.00 | 01-JAN-00:10 | 37008.92 | 09-JAN-05:01 | 25820.02 | 18-JAN-05:01 | 18575.28 | 09-JAN-05:05 | 8225.98 | 04-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.298831E+11 | 0.854487E+10 | 425.72 | 0.220142E+11 | 0.786891E+10 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:10 | 36765.51 | 20-FEB-07:01 | 28657.78 | 23-FEB-05:01 | 17796.44 | 20-FEB-07:05 | 8270.07 | 20-FEB-07:42 | 0.00 | 01-FEB-00:10 |
March | 0.332254E+11 | 0.960236E+10 | 477.74 | 0.236747E+11 | 0.955071E+10 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 37113.48 | 25-MAR-04:01 | 23323.46 | 03-MAR-05:01 | 19602.66 | 27-MAR-04:06 | 8427.54 | 28-MAR-04:07 | 0.00 | 01-MAR-00:10 |
April | 0.330065E+11 | 0.947221E+10 | 459.40 | 0.216683E+11 | 0.113382E+11 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 37125.48 | 24-APR-04:01 | 21742.15 | 27-APR-04:01 | 20493.44 | 03-APR-04:06 | 8469.01 | 30-APR-06:42 | 0.00 | 01-APR-00:10 |
May | 0.359162E+11 | 0.101378E+11 | 474.39 | 0.220302E+11 | 0.138860E+11 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 37140.64 | 09-MAY-04:01 | 21854.84 | 11-MAY-04:01 | 23939.08 | 22-MAY-04:06 | 8843.39 | 28-MAY-06:43 | 0.00 | 01-MAY-00:10 |
June | 0.357778E+11 | 0.100488E+11 | 462.55 | 0.218902E+11 | 0.138876E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 37118.63 | 05-JUN-04:01 | 22004.62 | 30-JUN-04:01 | 23338.40 | 10-JUN-04:08 | 8499.00 | 11-JUN-06:42 | 0.00 | 01-JUN-00:10 |
July | 0.299007E+11 | 0.848662E+10 | 470.16 | 0.196361E+11 | 0.102645E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 36883.28 | 02-JUL-06:01 | 24345.73 | 19-JUL-04:01 | 18655.68 | 02-JUL-06:05 | 8317.88 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 |
August | 0.329965E+11 | 0.917911E+10 | 477.31 | 0.196733E+11 | 0.133232E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 37139.86 | 06-AUG-06:02 | 21959.80 | 16-AUG-04:01 | 22642.03 | 13-AUG-06:06 | 8607.83 | 02-AUG-04:08 | 0.00 | 01-AUG-00:10 |
September | 0.322468E+11 | 0.898961E+10 | 458.57 | 0.200326E+11 | 0.122141E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 37121.03 | 02-SEP-04:01 | 22750.72 | 12-SEP-04:01 | 20300.33 | 02-SEP-04:06 | 8402.82 | 05-SEP-04:42 | 0.00 | 01-SEP-00:10 |
October | 0.318021E+11 | 0.882778E+10 | 468.87 | 0.199595E+11 | 0.118426E+11 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 37129.45 | 30-OCT-04:01 | 22489.46 | 11-OCT-04:01 | 19631.30 | 23-OCT-04:02 | 8320.13 | 05-OCT-04:07 | 0.00 | 01-OCT-00:10 |
November | 0.314560E+11 | 0.875817E+10 | 451.98 | 0.211319E+11 | 0.103241E+11 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 36746.15 | 08-NOV-05:01 | 23584.08 | 07-NOV-05:01 | 18498.48 | 12-NOV-07:04 | 8338.91 | 23-NOV-07:42 | 0.00 | 01-NOV-00:10 |
December | 0.317060E+11 | 0.890956E+10 | 468.55 | 0.227021E+11 | 0.900382E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 36824.58 | 11-DEC-05:01 | 24628.26 | 07-DEC-05:01 | 18334.38 | 11-DEC-05:05 | 8267.33 | 10-DEC-07:42 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.389433E+12 | 0.109897E+12 | 5563.73 | 0.257668E+12 | 0.131765E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.298831E+11 | 0.848662E+10 | 425.72 | 0.196361E+11 | 0.786891E+10 | 0.00 | 1.00 | 0.00 | 36746.15 | 21742.15 | 17796.44 | 8225.98 | 0.00 | |||||||
Maximum of Months | 0.359162E+11 | 0.101378E+11 | 477.74 | 0.236747E+11 | 0.138876E+11 | 0.00 | 1.00 | 0.00 | 37140.64 | 28657.78 | 23939.08 | 8843.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.281819E+11 | 0.799593E+10 | 467.93 | 0.201612E+11 | 0.802070E+10 | 0.00 | 1.00 | 01-JAN-07:01 | 0.00 | 01-JAN-00:10 | 33615.74 | 09-JAN-05:01 | 22047.26 | 18-JAN-05:01 | 17450.74 | 09-JAN-05:05 | 7488.20 | 04-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.268779E+11 | 0.767913E+10 | 425.31 | 0.192067E+11 | 0.767122E+10 | 0.00 | 1.00 | 01-FEB-05:01 | 0.00 | 01-FEB-00:10 | 33398.37 | 20-FEB-07:01 | 24583.98 | 23-FEB-05:01 | 16652.44 | 20-FEB-07:05 | 7532.62 | 20-FEB-07:42 | 0.00 | 01-FEB-00:10 |
March | 0.296496E+11 | 0.856618E+10 | 477.57 | 0.204373E+11 | 0.921232E+10 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 33787.59 | 25-MAR-04:01 | 20148.93 | 03-MAR-05:01 | 18371.85 | 27-MAR-04:06 | 7671.16 | 28-MAR-04:07 | 0.00 | 01-MAR-00:10 |
April | 0.295831E+11 | 0.846864E+10 | 459.14 | 0.186595E+11 | 0.109236E+11 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 33798.51 | 24-APR-04:01 | 18616.03 | 27-APR-04:01 | 19242.34 | 03-APR-04:05 | 7709.23 | 30-APR-06:42 | 0.00 | 01-APR-00:10 |
May | 0.323576E+11 | 0.909370E+10 | 474.14 | 0.189734E+11 | 0.133843E+11 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 33812.32 | 09-MAY-04:01 | 18416.92 | 11-MAY-04:01 | 22361.15 | 22-MAY-04:04 | 8039.30 | 28-MAY-06:43 | 0.00 | 01-MAY-00:10 |
June | 0.323635E+11 | 0.904456E+10 | 462.38 | 0.189293E+11 | 0.134342E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 33792.28 | 05-JUN-04:01 | 18799.10 | 30-JUN-04:01 | 21763.25 | 10-JUN-04:06 | 7730.50 | 11-JUN-06:42 | 0.00 | 01-JUN-00:10 |
July | 0.264278E+11 | 0.749993E+10 | 469.88 | 0.166083E+11 | 0.981953E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 33562.12 | 02-JUL-06:01 | 20457.48 | 19-JUL-04:01 | 17728.14 | 01-JUL-04:03 | 7570.70 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 |
August | 0.293235E+11 | 0.813261E+10 | 476.68 | 0.166058E+11 | 0.127177E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 33811.61 | 06-AUG-06:01 | 18649.45 | 16-AUG-04:01 | 21139.52 | 13-AUG-06:06 | 7831.40 | 02-AUG-04:08 | 0.00 | 01-AUG-00:10 |
September | 0.288335E+11 | 0.801530E+10 | 458.37 | 0.170852E+11 | 0.117483E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 33794.46 | 02-SEP-04:01 | 19242.77 | 12-SEP-04:01 | 19043.82 | 02-SEP-04:05 | 7649.80 | 05-SEP-04:42 | 0.00 | 01-SEP-00:10 |
October | 0.282187E+11 | 0.781953E+10 | 468.66 | 0.168852E+11 | 0.113335E+11 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 33802.13 | 30-OCT-04:01 | 19210.06 | 08-OCT-06:01 | 18722.74 | 23-OCT-04:02 | 7574.52 | 06-OCT-04:12 | 0.00 | 01-OCT-00:10 |
November | 0.281454E+11 | 0.782655E+10 | 451.74 | 0.181630E+11 | 0.998238E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 33449.12 | 08-NOV-05:01 | 20165.15 | 24-NOV-05:01 | 17498.65 | 12-NOV-07:04 | 7597.79 | 23-NOV-07:42 | 0.00 | 01-NOV-00:10 |
December | 0.283545E+11 | 0.796628E+10 | 468.64 | 0.196235E+11 | 0.873104E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:10 | 33463.78 | 11-DEC-05:01 | 21037.81 | 27-DEC-05:01 | 17271.94 | 11-DEC-05:05 | 7535.24 | 10-DEC-07:42 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.348317E+12 | 0.981084E+11 | 5560.43 | 0.221338E+12 | 0.126979E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.264278E+11 | 0.749993E+10 | 425.31 | 0.166058E+11 | 0.767122E+10 | 0.00 | 1.00 | 0.00 | 33398.37 | 18416.92 | 16652.44 | 7488.20 | 0.00 | |||||||
Maximum of Months | 0.323635E+11 | 0.909370E+10 | 477.57 | 0.204373E+11 | 0.134342E+11 | 0.00 | 1.00 | 0.00 | 33812.32 | 24583.98 | 22361.15 | 8039.30 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 16.01 | 17.56 | 67.56 | 14.53 | 0.00 | 0.00 | 0.00 |
February | 38.81 | 20.12 | 18.70 | 78.86 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 44.92 | 26.27 | 18.65 | 91.10 | 12.41 | 0.00 | 0.00 | 0.00 |
April | 45.48 | 25.41 | 20.07 | 92.84 | 8.82 | 0.00 | 0.00 | 0.00 |
May | 38.08 | 16.49 | 21.59 | 79.49 | 7.46 | 0.00 | 0.00 | 0.00 |
June | 41.15 | 20.30 | 20.86 | 85.53 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 34.66 | 11.44 | 23.23 | 71.68 | 9.42 | 0.00 | 0.00 | 0.00 |
August | 38.25 | 16.35 | 21.90 | 74.31 | 8.68 | 0.00 | 0.00 | 0.00 |
September | 35.35 | 13.66 | 21.69 | 72.69 | 8.42 | 0.00 | 0.00 | 0.00 |
October | 32.33 | 11.40 | 20.93 | 63.19 | 8.90 | 0.00 | 0.00 | 0.00 |
November | 30.92 | 11.70 | 19.22 | 62.31 | 11.02 | 0.00 | 0.00 | 0.00 |
December | 31.17 | 13.96 | 17.21 | 62.86 | 14.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 16.89 | 20.14 | 75.14 | 10.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.92 | 11.40 | 17.21 | 62.31 | 7.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.48 | 26.27 | 23.23 | 92.84 | 14.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.11 | 241.32 | 321.78 | 1872.43 | 336.17 | 0.00 | 0.00 | 0.00 |
February | 491.19 | 175.21 | 315.99 | 1737.06 | 289.73 | 0.00 | 0.00 | 0.00 |
March | 339.03 | 62.04 | 276.99 | 1302.97 | 237.13 | 0.00 | 0.00 | 0.00 |
April | 238.68 | 0.24 | 238.44 | 989.27 | 139.68 | 0.00 | 0.00 | 0.00 |
May | 238.71 | 0.00 | 238.71 | 1014.14 | 142.14 | 0.00 | 0.00 | 0.00 |
June | 237.85 | 0.00 | 237.85 | 1010.72 | 154.60 | 0.00 | 0.00 | 0.00 |
July | 245.02 | 0.00 | 245.02 | 918.90 | 203.48 | 0.00 | 0.00 | 0.00 |
August | 238.83 | 0.66 | 238.16 | 843.40 | 170.99 | 0.00 | 0.00 | 0.00 |
September | 268.24 | 12.80 | 255.45 | 1006.89 | 184.69 | 0.00 | 0.00 | 0.00 |
October | 357.69 | 67.29 | 290.40 | 1180.69 | 218.34 | 0.00 | 0.00 | 0.00 |
November | 459.86 | 147.68 | 312.18 | 1537.12 | 252.81 | 0.00 | 0.00 | 0.00 |
December | 558.38 | 241.32 | 317.07 | 1838.98 | 355.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 352.48 | 78.68 | 273.80 | 1268.70 | 223.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.85 | 0.00 | 237.85 | 843.40 | 139.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.11 | 241.32 | 321.78 | 1872.43 | 355.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.11 | 241.32 | 321.78 | 1876.62 | 310.34 | 0.00 | 0.00 | 0.00 |
February | 491.19 | 175.21 | 315.99 | 1741.13 | 264.82 | 0.00 | 0.00 | 0.00 |
March | 339.03 | 62.04 | 276.99 | 1308.04 | 208.44 | 0.00 | 0.00 | 0.00 |
April | 238.68 | 0.24 | 238.44 | 995.50 | 114.63 | 0.00 | 0.00 | 0.00 |
May | 238.71 | 0.00 | 238.71 | 1021.24 | 119.67 | 0.00 | 0.00 | 0.00 |
June | 237.85 | 0.00 | 237.85 | 1015.87 | 132.18 | 0.00 | 0.00 | 0.00 |
July | 245.02 | 0.00 | 245.02 | 923.59 | 181.18 | 0.00 | 0.00 | 0.00 |
August | 238.83 | 0.66 | 238.16 | 849.79 | 148.31 | 0.00 | 0.00 | 0.00 |
September | 268.24 | 12.80 | 255.45 | 1011.33 | 162.55 | 0.00 | 0.00 | 0.00 |
October | 357.69 | 67.29 | 290.40 | 1187.44 | 193.01 | 0.00 | 0.00 | 0.00 |
November | 459.86 | 147.68 | 312.18 | 1542.11 | 230.50 | 0.00 | 0.00 | 0.00 |
December | 558.38 | 241.32 | 317.07 | 1843.04 | 331.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 352.48 | 78.68 | 273.80 | 1273.97 | 199.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.85 | 0.00 | 237.85 | 849.79 | 114.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.11 | 241.32 | 321.78 | 1876.62 | 331.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.85 | 49.65 | 66.20 | 318.32 | 84.37 | 0.00 | 0.00 | 0.00 |
February | 101.06 | 36.05 | 65.01 | 284.33 | 76.97 | 0.00 | 0.00 | 0.00 |
March | 69.75 | 12.76 | 56.99 | 197.10 | 64.35 | 0.00 | 0.00 | 0.00 |
April | 49.11 | 0.05 | 49.06 | 136.14 | 40.96 | 2.33 | 0.00 | 0.00 |
May | 49.11 | 0.00 | 49.11 | 139.05 | 41.01 | 132.83 | 0.00 | 0.00 |
June | 48.94 | 0.00 | 48.94 | 137.65 | 43.90 | 54.00 | 0.00 | 0.00 |
July | 50.41 | 0.00 | 50.41 | 137.85 | 49.00 | 8.33 | 0.00 | 0.00 |
August | 49.14 | 0.14 | 49.00 | 121.37 | 43.58 | 22.83 | 0.00 | 0.00 |
September | 55.19 | 2.63 | 52.56 | 151.83 | 47.42 | 19.50 | 0.00 | 0.00 |
October | 73.59 | 13.84 | 59.75 | 190.06 | 54.37 | 41.33 | 0.00 | 0.00 |
November | 94.61 | 30.38 | 64.23 | 257.32 | 64.49 | 7.33 | 0.00 | 0.00 |
December | 114.88 | 49.65 | 65.23 | 314.58 | 87.30 | 14.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.52 | 16.19 | 56.33 | 198.40 | 58.09 | 302.50 | 0.00 | 0.00 |
Minimum of Months | 48.94 | 0.00 | 48.94 | 121.37 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.85 | 49.65 | 66.20 | 318.32 | 87.30 | 132.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89903492.18 | 42878086.04 | 47025406.14 | 0.180957E+09 | 38923644.33 |
February | 93896120.01 | 48663904.31 | 45232215.69 | 0.190787E+09 | 36232285.67 |
March | 0.120321E+09 | 70368282.40 | 49953029.19 | 0.244009E+09 | 33244984.27 |
April | 0.117882E+09 | 65868205.57 | 52013770.77 | 0.240643E+09 | 22872464.21 |
May | 0.102005E+09 | 44174749.94 | 57830236.49 | 0.212910E+09 | 19985279.02 |
June | 0.106674E+09 | 52604745.87 | 54069002.40 | 0.221705E+09 | 19084731.94 |
July | 92846373.31 | 30635490.67 | 62210882.64 | 0.191982E+09 | 25241222.60 |
August | 0.102456E+09 | 43796979.30 | 58659495.64 | 0.199036E+09 | 23260139.82 |
September | 91624679.57 | 35399825.23 | 56224854.34 | 0.188401E+09 | 21821503.18 |
October | 86582524.56 | 30531079.13 | 56051445.44 | 0.169239E+09 | 23832045.23 |
November | 80147350.51 | 30326260.31 | 49821090.20 | 0.161502E+09 | 28557171.99 |
December | 83494232.60 | 37386838.36 | 46107394.24 | 0.168358E+09 | 39978373.66 |
Annual Sum or Average | 0.116783E+10 | 0.532634E+09 | 0.635199E+09 | 0.236953E+10 | 0.333034E+09 |
Minimum of Months | 80147350.51 | 30326260.31 | 45232215.69 | 0.161502E+09 | 19084731.94 |
Maximum of Months | 0.120321E+09 | 70368282.40 | 62210882.64 | 0.244009E+09 | 39978373.66 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.501513E+10 | 0.900386E+09 |
February | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.420229E+10 | 0.700919E+09 |
March | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.348986E+10 | 0.635135E+09 |
April | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.256418E+10 | 0.362055E+09 |
May | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.271626E+10 | 0.380704E+09 |
June | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.261978E+10 | 0.400730E+09 |
July | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.246119E+10 | 0.544988E+09 |
August | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.225897E+10 | 0.457982E+09 |
September | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.260987E+10 | 0.478713E+09 |
October | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.316235E+10 | 0.584801E+09 |
November | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.398422E+10 | 0.655287E+09 |
December | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.492553E+10 | 0.952458E+09 |
Annual Sum or Average | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.400096E+11 | 0.705416E+10 |
Minimum of Months | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.225897E+10 | 0.362055E+09 |
Maximum of Months | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.501513E+10 | 0.952458E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.502633E+10 | 0.831204E+09 |
February | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.421213E+10 | 0.640641E+09 |
March | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.350345E+10 | 0.558295E+09 |
April | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.258034E+10 | 0.297128E+09 |
May | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.273528E+10 | 0.320530E+09 |
June | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.263314E+10 | 0.342601E+09 |
July | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.247375E+10 | 0.485280E+09 |
August | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.227609E+10 | 0.397232E+09 |
September | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.262137E+10 | 0.421323E+09 |
October | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.318044E+10 | 0.516967E+09 |
November | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.399714E+10 | 0.597454E+09 |
December | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.493640E+10 | 0.886854E+09 |
Annual Sum or Average | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.401759E+11 | 0.629551E+10 |
Minimum of Months | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.227609E+10 | 0.297128E+09 |
Maximum of Months | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.502633E+10 | 0.886854E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.852579E+09 | 0.225980E+09 |
February | 0.244476E+09 | 87203086.32 | 0.157273E+09 | 0.687855E+09 | 0.186213E+09 |
March | 0.186821E+09 | 34185410.24 | 0.152636E+09 | 0.527906E+09 | 0.172364E+09 |
April | 0.127282E+09 | 128142.59 | 0.127154E+09 | 0.352877E+09 | 0.106165E+09 |
May | 0.131541E+09 | 0.00 | 0.131541E+09 | 0.372431E+09 | 0.109830E+09 |
June | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.356790E+09 | 0.113794E+09 |
July | 0.135019E+09 | 0.00 | 0.135019E+09 | 0.369220E+09 | 0.131247E+09 |
August | 0.131603E+09 | 364283.72 | 0.131239E+09 | 0.325072E+09 | 0.116724E+09 |
September | 0.143047E+09 | 6824098.16 | 0.136223E+09 | 0.393549E+09 | 0.122902E+09 |
October | 0.197101E+09 | 37077754.33 | 0.160023E+09 | 0.509053E+09 | 0.145630E+09 |
November | 0.245230E+09 | 78750983.49 | 0.166479E+09 | 0.666963E+09 | 0.167145E+09 |
December | 0.307695E+09 | 0.132978E+09 | 0.174718E+09 | 0.842581E+09 | 0.233831E+09 |
Annual Sum or Average | 0.228695E+10 | 0.510493E+09 | 0.177646E+10 | 0.625688E+10 | 0.183182E+10 |
Minimum of Months | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.325072E+09 | 0.106165E+09 |
Maximum of Months | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.852579E+09 | 0.233831E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 540.49 | 116.26 | 268.53 | 128.07 | 140.46 | 0.00 | 0.00 |
February | 630.91 | 119.82 | 310.50 | 160.93 | 149.58 | 0.00 | 0.00 |
March | 728.82 | 99.30 | 359.38 | 210.18 | 149.20 | 0.00 | 0.00 |
April | 742.72 | 70.59 | 363.83 | 203.30 | 160.54 | 0.00 | 0.00 |
May | 635.93 | 59.69 | 304.67 | 131.94 | 172.73 | 0.00 | 0.00 |
June | 684.27 | 58.90 | 329.24 | 162.36 | 166.88 | 0.00 | 0.00 |
July | 573.42 | 75.39 | 277.32 | 91.50 | 185.82 | 0.00 | 0.00 |
August | 594.49 | 69.47 | 306.02 | 130.82 | 175.21 | 0.00 | 0.00 |
September | 581.48 | 67.35 | 282.79 | 109.26 | 173.53 | 0.00 | 0.00 |
October | 505.49 | 71.18 | 258.61 | 91.19 | 167.42 | 0.00 | 0.00 |
November | 498.46 | 88.14 | 247.37 | 93.60 | 153.77 | 0.00 | 0.00 |
December | 502.86 | 119.41 | 249.39 | 111.67 | 137.72 | 0.00 | 0.00 |
Annual Sum or Average | 601.10 | 84.48 | 296.25 | 135.12 | 161.14 | 0.00 | 0.00 |
Minimum of Months | 498.46 | 58.90 | 247.37 | 91.19 | 137.72 | 0.00 | 0.00 |
Maximum of Months | 742.72 | 119.82 | 363.83 | 210.18 | 185.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1872.43 | 336.17 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
February | 1737.06 | 289.73 | 491.19 | 175.21 | 315.99 | 0.00 | 0.00 |
March | 1302.97 | 237.13 | 339.03 | 62.04 | 276.99 | 0.00 | 0.00 |
April | 989.27 | 139.68 | 238.68 | 0.24 | 238.44 | 0.00 | 0.00 |
May | 1014.14 | 142.14 | 238.71 | 0.00 | 238.71 | 0.00 | 0.00 |
June | 1010.72 | 154.60 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
July | 918.90 | 203.48 | 245.02 | 0.00 | 245.02 | 0.00 | 0.00 |
August | 843.40 | 170.99 | 238.83 | 0.66 | 238.16 | 0.00 | 0.00 |
September | 1006.89 | 184.69 | 268.24 | 12.80 | 255.45 | 0.00 | 0.00 |
October | 1180.69 | 218.34 | 357.69 | 67.29 | 290.40 | 0.00 | 0.00 |
November | 1537.12 | 252.81 | 459.86 | 147.68 | 312.18 | 0.00 | 0.00 |
December | 1838.98 | 355.61 | 558.38 | 241.32 | 317.07 | 0.00 | 0.00 |
Annual Sum or Average | 1268.70 | 223.69 | 352.48 | 78.68 | 273.80 | 0.00 | 0.00 |
Minimum of Months | 843.40 | 139.68 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
Maximum of Months | 1872.43 | 355.61 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1876.62 | 310.34 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
February | 1741.13 | 264.82 | 491.19 | 175.21 | 315.99 | 0.00 | 0.00 |
March | 1308.04 | 208.44 | 339.03 | 62.04 | 276.99 | 0.00 | 0.00 |
April | 995.50 | 114.63 | 238.68 | 0.24 | 238.44 | 0.00 | 0.00 |
May | 1021.24 | 119.67 | 238.71 | 0.00 | 238.71 | 0.00 | 0.00 |
June | 1015.87 | 132.18 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
July | 923.59 | 181.18 | 245.02 | 0.00 | 245.02 | 0.00 | 0.00 |
August | 849.79 | 148.31 | 238.83 | 0.66 | 238.16 | 0.00 | 0.00 |
September | 1011.33 | 162.55 | 268.24 | 12.80 | 255.45 | 0.00 | 0.00 |
October | 1187.44 | 193.01 | 357.69 | 67.29 | 290.40 | 0.00 | 0.00 |
November | 1542.11 | 230.50 | 459.86 | 147.68 | 312.18 | 0.00 | 0.00 |
December | 1843.04 | 331.11 | 558.38 | 241.32 | 317.07 | 0.00 | 0.00 |
Annual Sum or Average | 1273.97 | 199.63 | 352.48 | 78.68 | 273.80 | 0.00 | 0.00 |
Minimum of Months | 849.79 | 114.63 | 237.85 | 0.00 | 237.85 | 0.00 | 0.00 |
Maximum of Months | 1876.62 | 331.11 | 563.11 | 241.32 | 321.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.32 | 84.37 | 115.85 | 49.65 | 66.20 | 0.00 | 0.00 |
February | 284.33 | 76.97 | 101.06 | 36.05 | 65.01 | 0.00 | 0.00 |
March | 197.10 | 64.35 | 69.75 | 12.76 | 56.99 | 0.00 | 0.00 |
April | 136.14 | 40.96 | 49.11 | 0.05 | 49.06 | 0.00 | 0.00 |
May | 139.05 | 41.01 | 49.11 | 0.00 | 49.11 | 0.00 | 0.00 |
June | 137.65 | 43.90 | 48.94 | 0.00 | 48.94 | 0.00 | 0.00 |
July | 137.85 | 49.00 | 50.41 | 0.00 | 50.41 | 0.00 | 0.00 |
August | 121.37 | 43.58 | 49.14 | 0.14 | 49.00 | 0.00 | 0.00 |
September | 151.83 | 47.42 | 55.19 | 2.63 | 52.56 | 0.00 | 0.00 |
October | 190.06 | 54.37 | 73.59 | 13.84 | 59.75 | 0.00 | 0.00 |
November | 257.32 | 64.49 | 94.61 | 30.38 | 64.23 | 0.00 | 0.00 |
December | 314.58 | 87.30 | 114.88 | 49.65 | 65.23 | 0.00 | 0.00 |
Annual Sum or Average | 198.40 | 58.09 | 72.52 | 16.19 | 56.33 | 0.00 | 0.00 |
Minimum of Months | 121.37 | 40.96 | 48.94 | 0.00 | 48.94 | 0.00 | 0.00 |
Maximum of Months | 318.32 | 87.30 | 115.85 | 49.65 | 66.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144765E+10 | 0.311389E+09 | 0.719228E+09 | 0.343025E+09 | 0.376203E+09 | 0.00 | 0.00 |
February | 0.152630E+10 | 0.289858E+09 | 0.751169E+09 | 0.389311E+09 | 0.361858E+09 | 0.00 | 0.00 |
March | 0.195207E+10 | 0.265960E+09 | 0.962570E+09 | 0.562946E+09 | 0.399624E+09 | 0.00 | 0.00 |
April | 0.192514E+10 | 0.182980E+09 | 0.943056E+09 | 0.526946E+09 | 0.416110E+09 | 0.00 | 0.00 |
May | 0.170328E+10 | 0.159882E+09 | 0.816040E+09 | 0.353398E+09 | 0.462642E+09 | 0.00 | 0.00 |
June | 0.177364E+10 | 0.152678E+09 | 0.853390E+09 | 0.420838E+09 | 0.432552E+09 | 0.00 | 0.00 |
July | 0.153586E+10 | 0.201930E+09 | 0.742771E+09 | 0.245084E+09 | 0.497687E+09 | 0.00 | 0.00 |
August | 0.159229E+10 | 0.186081E+09 | 0.819652E+09 | 0.350376E+09 | 0.469276E+09 | 0.00 | 0.00 |
September | 0.150721E+10 | 0.174572E+09 | 0.732997E+09 | 0.283199E+09 | 0.449799E+09 | 0.00 | 0.00 |
October | 0.135391E+10 | 0.190656E+09 | 0.692660E+09 | 0.244249E+09 | 0.448412E+09 | 0.00 | 0.00 |
November | 0.129202E+10 | 0.228457E+09 | 0.641179E+09 | 0.242610E+09 | 0.398569E+09 | 0.00 | 0.00 |
December | 0.134687E+10 | 0.319827E+09 | 0.667954E+09 | 0.299095E+09 | 0.368859E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189562E+11 | 0.266427E+10 | 0.934267E+10 | 0.426108E+10 | 0.508159E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129202E+10 | 0.152678E+09 | 0.641179E+09 | 0.242610E+09 | 0.361858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195207E+10 | 0.319827E+09 | 0.962570E+09 | 0.562946E+09 | 0.497687E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501513E+10 | 0.900386E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
February | 0.420229E+10 | 0.700919E+09 | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.00 | 0.00 |
March | 0.348986E+10 | 0.635135E+09 | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.00 | 0.00 |
April | 0.256418E+10 | 0.362055E+09 | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.00 | 0.00 |
May | 0.271626E+10 | 0.380704E+09 | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.00 | 0.00 |
June | 0.261978E+10 | 0.400730E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
July | 0.246119E+10 | 0.544988E+09 | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.00 | 0.00 |
August | 0.225897E+10 | 0.457982E+09 | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.00 | 0.00 |
September | 0.260987E+10 | 0.478713E+09 | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.00 | 0.00 |
October | 0.316235E+10 | 0.584801E+09 | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.00 | 0.00 |
November | 0.398422E+10 | 0.655287E+09 | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.00 | 0.00 |
December | 0.492553E+10 | 0.952458E+09 | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.400096E+11 | 0.705416E+10 | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.225897E+10 | 0.362055E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501513E+10 | 0.952458E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.502633E+10 | 0.831204E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
February | 0.421213E+10 | 0.640641E+09 | 0.118830E+10 | 0.423856E+09 | 0.764439E+09 | 0.00 | 0.00 |
March | 0.350345E+10 | 0.558295E+09 | 0.908059E+09 | 0.166160E+09 | 0.741899E+09 | 0.00 | 0.00 |
April | 0.258034E+10 | 0.297128E+09 | 0.618665E+09 | 622845.10 | 0.618043E+09 | 0.00 | 0.00 |
May | 0.273528E+10 | 0.320530E+09 | 0.639367E+09 | 0.00 | 0.639367E+09 | 0.00 | 0.00 |
June | 0.263314E+10 | 0.342601E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
July | 0.247375E+10 | 0.485280E+09 | 0.656273E+09 | 0.00 | 0.656273E+09 | 0.00 | 0.00 |
August | 0.227609E+10 | 0.397232E+09 | 0.639670E+09 | 1770623.90 | 0.637899E+09 | 0.00 | 0.00 |
September | 0.262137E+10 | 0.421323E+09 | 0.695290E+09 | 33168957.91 | 0.662121E+09 | 0.00 | 0.00 |
October | 0.318044E+10 | 0.516967E+09 | 0.958025E+09 | 0.180219E+09 | 0.777806E+09 | 0.00 | 0.00 |
November | 0.399714E+10 | 0.597454E+09 | 0.119196E+10 | 0.382774E+09 | 0.809183E+09 | 0.00 | 0.00 |
December | 0.493640E+10 | 0.886854E+09 | 0.149558E+10 | 0.646347E+09 | 0.849229E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401759E+11 | 0.629551E+10 | 0.111159E+11 | 0.248128E+10 | 0.863463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.227609E+10 | 0.297128E+09 | 0.616515E+09 | 0.00 | 0.616515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502633E+10 | 0.886854E+09 | 0.150822E+10 | 0.646363E+09 | 0.861861E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.852579E+09 | 0.225980E+09 | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.00 | 0.00 |
February | 0.687855E+09 | 0.186213E+09 | 0.244476E+09 | 87203086.32 | 0.157273E+09 | 0.00 | 0.00 |
March | 0.527906E+09 | 0.172364E+09 | 0.186821E+09 | 34185410.24 | 0.152636E+09 | 0.00 | 0.00 |
April | 0.352877E+09 | 0.106165E+09 | 0.127282E+09 | 128142.59 | 0.127154E+09 | 0.00 | 0.00 |
May | 0.372431E+09 | 0.109830E+09 | 0.131541E+09 | 0.00 | 0.131541E+09 | 0.00 | 0.00 |
June | 0.356790E+09 | 0.113794E+09 | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.00 | 0.00 |
July | 0.369220E+09 | 0.131247E+09 | 0.135019E+09 | 0.00 | 0.135019E+09 | 0.00 | 0.00 |
August | 0.325072E+09 | 0.116724E+09 | 0.131603E+09 | 364283.72 | 0.131239E+09 | 0.00 | 0.00 |
September | 0.393549E+09 | 0.122902E+09 | 0.143047E+09 | 6824098.16 | 0.136223E+09 | 0.00 | 0.00 |
October | 0.509053E+09 | 0.145630E+09 | 0.197101E+09 | 37077754.33 | 0.160023E+09 | 0.00 | 0.00 |
November | 0.666963E+09 | 0.167145E+09 | 0.245230E+09 | 78750983.49 | 0.166479E+09 | 0.00 | 0.00 |
December | 0.842581E+09 | 0.233831E+09 | 0.307695E+09 | 0.132978E+09 | 0.174718E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.625688E+10 | 0.183182E+10 | 0.228695E+10 | 0.510493E+09 | 0.177646E+10 | 0.00 | 0.00 |
Minimum of Months | 0.325072E+09 | 0.106165E+09 | 0.126840E+09 | 0.00 | 0.126840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.852579E+09 | 0.233831E+09 | 0.310298E+09 | 0.132981E+09 | 0.177317E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.176213E+10 | -0.138733E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374798543.9 | 58.99 | 0.00 | 0.00 |
February | 0.159229E+10 | -0.125525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -337042979.7 | 58.99 | 0.00 | 0.00 |
March | 0.177399E+10 | -0.140189E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -372092757.7 | 58.99 | 0.00 | 0.00 |
April | 0.166248E+10 | -0.130410E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -358381117.5 | 58.99 | 0.00 | 0.00 |
May | 0.168963E+10 | -0.132033E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -369303842.9 | 58.99 | 0.00 | 0.00 |
June | 0.163106E+10 | -0.127516E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -355902166.4 | 58.99 | 0.00 | 0.00 |
July | 0.164244E+10 | -0.127251E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -369923345.7 | 58.99 | 0.00 | 0.00 |
August | 0.169521E+10 | -0.132281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -372396248.4 | 58.99 | 0.00 | 0.00 |
September | 0.164033E+10 | -0.127999E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -360342715.3 | 58.99 | 0.00 | 0.00 |
October | 0.170641E+10 | -0.133229E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374120765.8 | 58.99 | 0.00 | 0.00 |
November | 0.167363E+10 | -0.131116E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -362466939.4 | 58.99 | 0.00 | 0.00 |
December | 0.175823E+10 | -0.138258E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -375653572.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.202278E+11 | -0.158454E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.438242E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.159229E+10 | -0.140189E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -375653572.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.177399E+10 | -0.125525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -337042979.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.375033E+11 | 0.279835E+11 | 58928.00 | 09-JAN-05:01 | 30524.78 | 0.00 |
February | 0.00 | 0.00 | 0.379744E+11 | 0.286390E+11 | 58693.28 | 20-FEB-07:01 | 32133.24 | 0.00 |
March | 0.00 | 0.00 | 0.470376E+11 | 0.347883E+11 | 59611.65 | 27-MAR-04:01 | 30649.37 | 0.00 |
April | 0.00 | 0.00 | 0.514910E+11 | 0.361790E+11 | 59567.46 | 06-APR-04:01 | 31433.31 | 0.00 |
May | 0.00 | 0.00 | 0.583060E+11 | 0.390312E+11 | 59686.88 | 17-MAY-04:01 | 27937.18 | 0.00 |
June | 0.00 | 0.00 | 0.614172E+11 | 0.417837E+11 | 59627.76 | 08-JUN-04:01 | 32635.97 | 0.00 |
July | 0.00 | 0.00 | 0.492387E+11 | 0.353163E+11 | 58855.70 | 21-JUL-04:01 | 34950.15 | 0.00 |
August | 0.00 | 0.00 | 0.514866E+11 | 0.333839E+11 | 59688.99 | 06-AUG-06:01 | 27183.74 | 0.00 |
September | 0.00 | 0.00 | 0.473577E+11 | 0.314630E+11 | 59658.72 | 02-SEP-04:01 | 30214.00 | 0.00 |
October | 0.00 | 0.00 | 0.430042E+11 | 0.281865E+11 | 59474.65 | 30-OCT-04:01 | 29817.59 | 0.00 |
November | 0.00 | 0.00 | 0.397612E+11 | 0.273790E+11 | 58514.90 | 13-NOV-05:01 | 31787.39 | 0.00 |
December | 0.00 | 0.00 | 0.370896E+11 | 0.267937E+11 | 58709.01 | 11-DEC-05:01 | 31079.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.561668E+12 | 0.390927E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.370896E+11 | 0.267937E+11 | 58514.90 | 27183.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.614172E+11 | 0.417837E+11 | 59688.99 | 34950.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192461E+12 | 0.126692E+12 | 253665.47 | 10-JAN-05:01 | 143686.57 | 0.00 |
February | 0.00 | 0.00 | 0.189587E+12 | 0.125359E+12 | 253665.24 | 16-FEB-05:01 | 148234.19 | 0.00 |
March | 0.00 | 0.00 | 0.229998E+12 | 0.150342E+12 | 256278.63 | 28-MAR-04:01 | 149725.62 | 0.00 |
April | 0.00 | 0.00 | 0.248819E+12 | 0.149384E+12 | 258636.83 | 03-APR-04:01 | 144633.16 | 0.00 |
May | 0.00 | 0.00 | 0.271688E+12 | 0.150129E+12 | 261915.45 | 20-MAY-04:01 | 130373.91 | 0.00 |
June | 0.00 | 0.00 | 0.273443E+12 | 0.150491E+12 | 261681.97 | 11-JUN-06:02 | 131697.90 | 0.00 |
July | 0.00 | 0.00 | 0.223710E+12 | 0.133127E+12 | 255581.77 | 01-JUL-04:01 | 137912.29 | 0.00 |
August | 0.00 | 0.00 | 0.254133E+12 | 0.135867E+12 | 261399.35 | 13-AUG-06:01 | 130069.69 | 0.00 |
September | 0.00 | 0.00 | 0.239907E+12 | 0.132111E+12 | 258433.95 | 05-SEP-04:01 | 143328.16 | 0.00 |
October | 0.00 | 0.00 | 0.226737E+12 | 0.124672E+12 | 256561.49 | 26-OCT-04:01 | 135923.16 | 0.00 |
November | 0.00 | 0.00 | 0.206673E+12 | 0.120888E+12 | 255922.41 | 12-NOV-07:01 | 136682.60 | 0.00 |
December | 0.00 | 0.00 | 0.195184E+12 | 0.122845E+12 | 255104.62 | 11-DEC-05:01 | 136943.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.275234E+13 | 0.162191E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.189587E+12 | 0.120888E+12 | 253665.24 | 130069.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273443E+12 | 0.150491E+12 | 261915.45 | 149725.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.315160E+11 | 0.232547E+11 | 37008.92 | 09-JAN-05:01 | 19282.89 | 0.00 |
February | 0.00 | 0.00 | 0.298831E+11 | 0.220142E+11 | 36765.51 | 20-FEB-07:01 | 19837.23 | 0.00 |
March | 0.00 | 0.00 | 0.332254E+11 | 0.236747E+11 | 37113.48 | 25-MAR-04:01 | 18814.02 | 0.00 |
April | 0.00 | 0.00 | 0.330065E+11 | 0.216683E+11 | 37125.48 | 24-APR-04:01 | 18394.70 | 0.00 |
May | 0.00 | 0.00 | 0.359162E+11 | 0.220302E+11 | 37140.64 | 09-MAY-04:01 | 16776.35 | 0.00 |
June | 0.00 | 0.00 | 0.357778E+11 | 0.218902E+11 | 37118.63 | 05-JUN-04:01 | 17526.23 | 0.00 |
July | 0.00 | 0.00 | 0.299007E+11 | 0.196361E+11 | 36883.28 | 02-JUL-06:01 | 19011.64 | 0.00 |
August | 0.00 | 0.00 | 0.329965E+11 | 0.196733E+11 | 37139.86 | 06-AUG-06:02 | 15431.25 | 0.00 |
September | 0.00 | 0.00 | 0.322468E+11 | 0.200326E+11 | 37121.03 | 02-SEP-04:01 | 17533.86 | 0.00 |
October | 0.00 | 0.00 | 0.318021E+11 | 0.199595E+11 | 37129.45 | 30-OCT-04:01 | 18563.50 | 0.00 |
November | 0.00 | 0.00 | 0.314560E+11 | 0.211319E+11 | 36746.15 | 08-NOV-05:01 | 20382.05 | 0.00 |
December | 0.00 | 0.00 | 0.317060E+11 | 0.227021E+11 | 36824.58 | 11-DEC-05:01 | 19400.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.389433E+12 | 0.257668E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.298831E+11 | 0.196361E+11 | 36746.15 | 15431.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.359162E+11 | 0.236747E+11 | 37140.64 | 20382.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.281819E+11 | 0.201612E+11 | 33615.74 | 09-JAN-05:01 | 16594.97 | 0.00 |
February | 0.00 | 0.00 | 0.268779E+11 | 0.192067E+11 | 33398.37 | 20-FEB-07:01 | 17222.66 | 0.00 |
March | 0.00 | 0.00 | 0.296496E+11 | 0.204373E+11 | 33787.59 | 25-MAR-04:01 | 16157.16 | 0.00 |
April | 0.00 | 0.00 | 0.295831E+11 | 0.186595E+11 | 33798.51 | 24-APR-04:01 | 15761.85 | 0.00 |
May | 0.00 | 0.00 | 0.323576E+11 | 0.189734E+11 | 33812.32 | 09-MAY-04:01 | 14507.43 | 0.00 |
June | 0.00 | 0.00 | 0.323635E+11 | 0.189293E+11 | 33792.28 | 05-JUN-04:01 | 14960.83 | 0.00 |
July | 0.00 | 0.00 | 0.264278E+11 | 0.166083E+11 | 33562.12 | 02-JUL-06:01 | 16503.56 | 0.00 |
August | 0.00 | 0.00 | 0.293235E+11 | 0.166058E+11 | 33811.61 | 06-AUG-06:01 | 13450.12 | 0.00 |
September | 0.00 | 0.00 | 0.288335E+11 | 0.170852E+11 | 33794.46 | 02-SEP-04:01 | 15168.24 | 0.00 |
October | 0.00 | 0.00 | 0.282187E+11 | 0.168852E+11 | 33802.13 | 30-OCT-04:01 | 15991.54 | 0.00 |
November | 0.00 | 0.00 | 0.281454E+11 | 0.181630E+11 | 33449.12 | 08-NOV-05:01 | 17473.69 | 0.00 |
December | 0.00 | 0.00 | 0.283545E+11 | 0.196235E+11 | 33463.78 | 11-DEC-05:01 | 16671.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.348317E+12 | 0.221338E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.264278E+11 | 0.166058E+11 | 33398.37 | 13450.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.323635E+11 | 0.204373E+11 | 33812.32 | 17473.69 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATER FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.437334E+10 | 0.56 | 2676.36 | 01-JAN-09:30 | 0.88 |
February | 0.398506E+10 | 0.57 | 2676.36 | 01-FEB-06:30 | 0.89 |
March | 0.449877E+10 | 0.57 | 2676.36 | 01-MAR-07:30 | 0.89 |
April | 0.434873E+10 | 0.57 | 2676.36 | 01-APR-06:40 | 0.88 |
May | 0.451290E+10 | 0.57 | 2676.36 | 01-MAY-11:02 | 0.89 |
June | 0.441718E+10 | 0.58 | 2676.36 | 04-JUN-14:40 | 0.89 |
July | 0.443397E+10 | 0.57 | 2676.36 | 01-JUL-06:50 | 0.88 |
August | 0.451164E+10 | 0.57 | 2676.36 | 01-AUG-15:40 | 0.89 |
September | 0.432062E+10 | 0.57 | 2676.36 | 02-SEP-06:10 | 0.88 |
October | 0.439821E+10 | 0.56 | 2676.36 | 02-OCT-19:20 | 0.89 |
November | 0.422938E+10 | 0.56 | 2676.36 | 01-NOV-05:10 | 0.88 |
December | 0.437605E+10 | 0.56 | 2676.36 | 01-DEC-06:10 | 0.89 |
Annual Sum or Average | 0.524058E+11 | 0.57 | |||
Minimum of Months | 0.398506E+10 | 0.56 | 2676.36 | 0.88 | |
Maximum of Months | 0.451290E+10 | 0.58 | 2676.36 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.275789E+11 | 0.95 | 16931.87 | 01-JAN-07:01 | 1.49 |
February | 0.250867E+11 | 0.95 | 16931.87 | 08-FEB-07:00 | 1.50 |
March | 0.282409E+11 | 0.96 | 16931.87 | 03-MAR-06:10 | 1.50 |
April | 0.272228E+11 | 0.96 | 16931.87 | 01-APR-04:01 | 1.49 |
May | 0.281774E+11 | 0.95 | 16931.87 | 04-MAY-12:05 | 1.49 |
June | 0.275147E+11 | 0.96 | 16931.87 | 09-JUN-12:40 | 1.49 |
July | 0.277876E+11 | 0.95 | 16931.87 | 01-JUL-04:01 | 1.49 |
August | 0.282688E+11 | 0.96 | 16931.87 | 14-AUG-13:10 | 1.49 |
September | 0.271457E+11 | 0.95 | 16931.87 | 01-SEP-04:01 | 1.49 |
October | 0.276963E+11 | 0.94 | 16931.87 | 01-OCT-06:01 | 1.49 |
November | 0.266519E+11 | 0.94 | 16931.87 | 01-NOV-04:01 | 1.49 |
December | 0.276291E+11 | 0.95 | 16931.87 | 07-DEC-06:50 | 1.49 |
Annual Sum or Average | 0.329001E+12 | 0.95 | |||
Minimum of Months | 0.250867E+11 | 0.94 | 16931.87 | 1.49 | |
Maximum of Months | 0.282688E+11 | 0.96 | 16931.87 | 1.50 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261598E+10 | 0.59 | 1597.33 | 01-JAN-08:40 | 0.92 |
February | 0.238007E+10 | 0.59 | 1597.33 | 01-FEB-07:00 | 0.93 |
March | 0.267719E+10 | 0.60 | 1597.33 | 01-MAR-17:40 | 0.92 |
April | 0.257740E+10 | 0.59 | 1597.33 | 01-APR-12:10 | 0.92 |
May | 0.266942E+10 | 0.59 | 1597.33 | 01-MAY-08:20 | 0.92 |
June | 0.260408E+10 | 0.60 | 1597.33 | 02-JUN-08:50 | 0.92 |
July | 0.262439E+10 | 0.59 | 1597.33 | 01-JUL-06:50 | 0.92 |
August | 0.267343E+10 | 0.60 | 1597.33 | 01-AUG-06:20 | 0.92 |
September | 0.256724E+10 | 0.59 | 1597.33 | 01-SEP-07:15 | 0.92 |
October | 0.262105E+10 | 0.59 | 1597.33 | 03-OCT-16:40 | 0.92 |
November | 0.252640E+10 | 0.58 | 1597.33 | 01-NOV-06:30 | 0.92 |
December | 0.261953E+10 | 0.59 | 1597.33 | 01-DEC-07:30 | 0.92 |
Annual Sum or Average | 0.311562E+11 | 0.59 | |||
Minimum of Months | 0.238007E+10 | 0.58 | 1597.33 | 0.92 | |
Maximum of Months | 0.267719E+10 | 0.60 | 1597.33 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229070E+10 | 0.59 | 1399.96 | 01-JAN-12:20 | 0.92 |
February | 0.208437E+10 | 0.59 | 1399.96 | 01-FEB-07:00 | 0.93 |
March | 0.234359E+10 | 0.60 | 1399.96 | 02-MAR-07:30 | 0.92 |
April | 0.225601E+10 | 0.59 | 1399.96 | 01-APR-07:30 | 0.92 |
May | 0.233798E+10 | 0.59 | 1399.96 | 01-MAY-10:10 | 0.92 |
June | 0.228069E+10 | 0.59 | 1399.96 | 01-JUN-13:00 | 0.92 |
July | 0.229764E+10 | 0.59 | 1399.96 | 01-JUL-06:50 | 0.92 |
August | 0.234002E+10 | 0.59 | 1399.96 | 01-AUG-07:00 | 0.92 |
September | 0.224795E+10 | 0.59 | 1399.96 | 01-SEP-12:10 | 0.92 |
October | 0.229453E+10 | 0.59 | 1399.96 | 01-OCT-08:50 | 0.92 |
November | 0.221247E+10 | 0.58 | 1399.96 | 02-NOV-07:00 | 0.92 |
December | 0.229409E+10 | 0.59 | 1399.96 | 01-DEC-06:30 | 0.92 |
Annual Sum or Average | 0.272800E+11 | 0.59 | |||
Minimum of Months | 0.208437E+10 | 0.58 | 1399.96 | 0.92 | |
Maximum of Months | 0.234359E+10 | 0.60 | 1399.96 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.161536E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159367E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192404E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.202008E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.220889E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.193145E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.198927E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.186186E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.174370E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.164169E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.159357E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.223933E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159357E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226972E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.888034E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.854781E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101372E+12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104364E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.110643E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.109896E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.967572E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104277E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.994263E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.962733E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.901831E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.889436E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117642E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.854781E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.110643E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115564E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109249E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122796E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120496E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128072E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126529E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.111110E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.118525E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115569E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114488E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112846E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.115291E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141053E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109249E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128072E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102866E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.976350E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109098E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107247E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114317E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.113253E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.979756E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104726E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102632E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101141E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100390E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.102604E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125388E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.976350E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114317E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.437334E+10 | 0.375033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398506E+10 | 0.379744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449877E+10 | 0.470376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434873E+10 | 0.514910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451290E+10 | 0.583060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.441718E+10 | 0.614172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.443397E+10 | 0.492387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.451164E+10 | 0.514866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432062E+10 | 0.473577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439821E+10 | 0.430042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422938E+10 | 0.397612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437605E+10 | 0.370896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524058E+11 | 0.561668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.398506E+10 | 0.370896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451290E+10 | 0.614172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.275789E+11 | 0.192461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250867E+11 | 0.189587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282409E+11 | 0.229998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272228E+11 | 0.248819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281774E+11 | 0.271688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275147E+11 | 0.273443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.277876E+11 | 0.223710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.282688E+11 | 0.254133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271457E+11 | 0.239907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276963E+11 | 0.226737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266519E+11 | 0.206673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276291E+11 | 0.195184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329001E+12 | 0.275234E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250867E+11 | 0.189587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282688E+11 | 0.273443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261598E+10 | 0.315160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238007E+10 | 0.298831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267719E+10 | 0.332254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257740E+10 | 0.330065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266942E+10 | 0.359162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260408E+10 | 0.357778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262439E+10 | 0.299007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267343E+10 | 0.329965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256724E+10 | 0.322468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262105E+10 | 0.318021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252640E+10 | 0.314560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261953E+10 | 0.317060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311562E+11 | 0.389433E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.238007E+10 | 0.298831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.267719E+10 | 0.359162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229070E+10 | 0.281819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208437E+10 | 0.268779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234359E+10 | 0.296496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225601E+10 | 0.295831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233798E+10 | 0.323576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228069E+10 | 0.323635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.229764E+10 | 0.264278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234002E+10 | 0.293235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224795E+10 | 0.288335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229453E+10 | 0.282187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221247E+10 | 0.281454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229409E+10 | 0.283545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272800E+11 | 0.348317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208437E+10 | 0.264278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234359E+10 | 0.323635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.437334E+10 | 0.00 | 0.00 | 0.00 | 0.117802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398506E+10 | 0.00 | 0.00 | 0.00 | 0.119517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449877E+10 | 0.00 | 0.00 | 0.00 | 0.147416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434873E+10 | 0.00 | 0.00 | 0.00 | 0.158520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451290E+10 | 0.00 | 0.00 | 0.00 | 0.175760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.441718E+10 | 0.00 | 0.00 | 0.00 | 0.182800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.443397E+10 | 0.00 | 0.00 | 0.00 | 0.148805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.451164E+10 | 0.00 | 0.00 | 0.00 | 0.153811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.432062E+10 | 0.00 | 0.00 | 0.00 | 0.142980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439821E+10 | 0.00 | 0.00 | 0.00 | 0.130388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422938E+10 | 0.00 | 0.00 | 0.00 | 0.121875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437605E+10 | 0.00 | 0.00 | 0.00 | 0.115596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524058E+11 | 0.00 | 0.00 | 0.00 | 0.171527E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.398506E+10 | 0.00 | 0.00 | 0.00 | 0.115596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.451290E+10 | 0.00 | 0.00 | 0.00 | 0.182800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.275789E+11 | 0.00 | 0.00 | 0.00 | 0.612245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250867E+11 | 0.00 | 0.00 | 0.00 | 0.603914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282409E+11 | 0.00 | 0.00 | 0.00 | 0.731316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272228E+11 | 0.00 | 0.00 | 0.00 | 0.771413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281774E+11 | 0.00 | 0.00 | 0.00 | 0.824661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275147E+11 | 0.00 | 0.00 | 0.00 | 0.823816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.277876E+11 | 0.00 | 0.00 | 0.00 | 0.689695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.282688E+11 | 0.00 | 0.00 | 0.00 | 0.760083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271457E+11 | 0.00 | 0.00 | 0.00 | 0.722806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276963E+11 | 0.00 | 0.00 | 0.00 | 0.685770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266519E+11 | 0.00 | 0.00 | 0.00 | 0.635312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276291E+11 | 0.00 | 0.00 | 0.00 | 0.613145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329001E+12 | 0.00 | 0.00 | 0.00 | 0.847418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.250867E+11 | 0.00 | 0.00 | 0.00 | 0.603914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282688E+11 | 0.00 | 0.00 | 0.00 | 0.824661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261598E+10 | 0.00 | 0.00 | 0.00 | 0.894039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238007E+10 | 0.00 | 0.00 | 0.00 | 0.854487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267719E+10 | 0.00 | 0.00 | 0.00 | 0.960236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257740E+10 | 0.00 | 0.00 | 0.00 | 0.947221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266942E+10 | 0.00 | 0.00 | 0.00 | 0.101378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260408E+10 | 0.00 | 0.00 | 0.00 | 0.100488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.262439E+10 | 0.00 | 0.00 | 0.00 | 0.848662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267343E+10 | 0.00 | 0.00 | 0.00 | 0.917911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256724E+10 | 0.00 | 0.00 | 0.00 | 0.898961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262105E+10 | 0.00 | 0.00 | 0.00 | 0.882778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252640E+10 | 0.00 | 0.00 | 0.00 | 0.875817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.890956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311562E+11 | 0.00 | 0.00 | 0.00 | 0.109897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.238007E+10 | 0.00 | 0.00 | 0.00 | 0.848662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.267719E+10 | 0.00 | 0.00 | 0.00 | 0.101378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.229070E+10 | 0.00 | 0.00 | 0.00 | 0.799593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208437E+10 | 0.00 | 0.00 | 0.00 | 0.767913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234359E+10 | 0.00 | 0.00 | 0.00 | 0.856618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225601E+10 | 0.00 | 0.00 | 0.00 | 0.846864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233798E+10 | 0.00 | 0.00 | 0.00 | 0.909370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228069E+10 | 0.00 | 0.00 | 0.00 | 0.904456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.229764E+10 | 0.00 | 0.00 | 0.00 | 0.749993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234002E+10 | 0.00 | 0.00 | 0.00 | 0.813261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224795E+10 | 0.00 | 0.00 | 0.00 | 0.801530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229453E+10 | 0.00 | 0.00 | 0.00 | 0.781953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221247E+10 | 0.00 | 0.00 | 0.00 | 0.782655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229409E+10 | 0.00 | 0.00 | 0.00 | 0.796628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272800E+11 | 0.00 | 0.00 | 0.00 | 0.981084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208437E+10 | 0.00 | 0.00 | 0.00 | 0.749993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234359E+10 | 0.00 | 0.00 | 0.00 | 0.909370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.101554E+11 | 0.00 | 1336252.23 | 0.00 | 0.00 | 2720549.47 | 0.00 | 0.28 |
February | 0.00 | 0.103899E+11 | 0.00 | 60459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
March | 0.00 | 0.128242E+11 | 0.00 | 35731.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.158625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.189869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.193373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.142555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.174537E+11 | 0.00 | 55886.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.161485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.149262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
November | 0.00 | 0.128221E+11 | 0.00 | 270609.22 | 0.00 | 0.00 | 43169.51 | 0.00 | 0.28 |
December | 0.00 | 0.109159E+11 | 0.00 | 884616.13 | 0.00 | 0.00 | 2276924.19 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.174078E+12 | 0.00 | 2643555.98 | 0.00 | 0.00 | 5040643.17 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.101554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.193373E+11 | 0.00 | 1336252.23 | 0.00 | 0.00 | 2720549.47 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.756341E+11 | 0.00 | 6057566.05 | 0.00 | 0.00 | 27141757.17 | 0.00 | 0.56 |
February | 0.00 | 0.774876E+11 | 0.00 | 38960.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.00 | 0.972234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.119130E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.140869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.141561E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.101698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.130005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.120004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.111517E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.00 | 0.949736E+11 | 0.00 | 1212110.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.00 | 0.810369E+11 | 0.00 | 3488159.44 | 0.00 | 0.00 | 1997233.99 | 0.00 | 0.56 |
Annual Sum or Average | 0.00 | 0.129114E+13 | 0.00 | 10796796.42 | 0.00 | 0.00 | 29138991.16 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.756341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.00 | 0.141561E+12 | 0.00 | 6057566.05 | 0.00 | 0.00 | 27141757.17 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.857715E+10 | 0.00 | 1351367.84 | 0.00 | 0.00 | 732220.30 | 0.00 | 0.57 |
February | 0.00 | 0.856333E+10 | 0.00 | 234790.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.00 | 0.102429E+11 | 0.00 | 170739.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.122034E+11 | 0.00 | 15290.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.144333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.144391E+11 | 0.00 | 14294.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.106425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.133350E+11 | 0.00 | 85625.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.125657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.119622E+11 | 0.00 | 3481.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.00 | 0.105589E+11 | 0.00 | 221792.07 | 0.00 | 0.00 | 64175.73 | 0.00 | 0.57 |
December | 0.00 | 0.925133E+10 | 0.00 | 906653.10 | 0.00 | 0.00 | 585652.46 | 0.00 | 0.57 |
Annual Sum or Average | 0.00 | 0.136775E+12 | 0.00 | 3004034.25 | 0.00 | 0.00 | 1382048.49 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.856333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.00 | 0.144391E+11 | 0.00 | 1351367.84 | 0.00 | 0.00 | 732220.30 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.837628E+10 | 0.00 | 1143098.50 | 0.00 | 0.00 | 1050672.87 | 0.00 | 0.56 |
February | 0.00 | 0.839690E+10 | 0.00 | 176177.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.00 | 0.997820E+10 | 0.00 | 98283.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.118694E+11 | 0.00 | 3160.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.140258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.140715E+11 | 0.00 | 8445.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.102487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.128289E+11 | 0.00 | 69096.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.121593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.115169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.00 | 0.102639E+11 | 0.00 | 183486.01 | 0.00 | 0.00 | 95832.77 | 0.00 | 0.57 |
December | 0.00 | 0.901588E+10 | 0.00 | 776209.20 | 0.00 | 0.00 | 1262782.28 | 0.00 | 0.57 |
Annual Sum or Average | 0.00 | 0.132752E+12 | 0.00 | 2457957.02 | 0.00 | 0.00 | 2409287.92 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.837628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.00 | 0.140715E+11 | 0.00 | 1143098.50 | 0.00 | 0.00 | 1262782.28 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.398389E+12 | -0.263000E+10 | 0.00 | -0.133268E+12 | 0.379603E+12 |
February | 0.403432E+12 | -0.302634E+10 | 0.00 | -0.137977E+12 | 0.372890E+12 |
March | 0.544317E+12 | -0.618285E+10 | 0.00 | -0.172396E+12 | 0.445953E+12 |
April | 0.550417E+12 | -0.679151E+10 | 0.00 | -0.216961E+12 | 0.473834E+12 |
May | 0.527098E+12 | -0.851216E+10 | 0.00 | -0.259075E+12 | 0.517542E+12 |
June | 0.538982E+12 | -0.808032E+10 | 0.00 | -0.254016E+12 | 0.522757E+12 |
July | 0.441136E+12 | -0.422010E+10 | 0.00 | -0.188470E+12 | 0.429114E+12 |
August | 0.569877E+12 | -0.719601E+10 | 0.00 | -0.231767E+12 | 0.476641E+12 |
September | 0.445632E+12 | -0.479918E+10 | 0.00 | -0.219436E+12 | 0.451929E+12 |
October | 0.476589E+12 | -0.429039E+10 | 0.00 | -0.205570E+12 | 0.428025E+12 |
November | 0.383316E+12 | -0.298242E+10 | 0.00 | -0.173545E+12 | 0.398339E+12 |
December | 0.371232E+12 | -0.222461E+10 | 0.00 | -0.143055E+12 | 0.382084E+12 |
Annual Sum or Average | 0.565042E+13 | -0.609359E+11 | 0.00 | -0.233554E+13 | 0.527871E+13 |
Minimum of Months | 0.371232E+12 | -0.851216E+10 | 0.00 | -0.259075E+12 | 0.372890E+12 |
Maximum of Months | 0.569877E+12 | -0.222461E+10 | 0.00 | -0.133268E+12 | 0.522757E+12 |